Open PDF In BrowserView PDF
QO® and Homeline® Load
Centers and Enclosures
Catalog

Class 1100

1100CT0501

2007

CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page
QO® Circuit Breakers and Load Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
QO®, QOM2 and Q-Frame Enclosed Circuit Breakers . . . . . . . . . . . . . . . 34
Homeline® Circuit Breakers and Load Centers . . . . . . . . . . . . . . . . . . . . . 40

QO® and Homeline® Load Centers and Enclosures
Table of Contents
TABLE OF CONTENTS
Product Description 3
Features 3
QO® Catalog Number Description 4
General information and Application Data 5
Service 5
Ratings 5
Branch Circuit Breakers 5
Indoor Enclosures (Type 1) 6
Indoor Covers 6
Rainproof Enclosures (Type 3R) 6
Bolt-On Hubs 6
Class CTL 7
Phasing 7
Line Lugs 7
Neutral Assemblies 7
Single Phase, 2 16 Circuits, 30 125 A, Fixed Mains 8
Single-Phase,12 42 Circuits, 100 225 A, Convertible Mains 9
Special Purpose 11
Generator Panels 12
Three-Phase, 3 4 2 Circuits, 60 22 5 A, Convertible or Fixed Mains 13
Single-Phase, 12 42 Circuits, 300 400 A, Fixed Mains 15
Accessories 16
Technical Information 19
Grounding Bar Kits 19
Main Lugs and Main Circuit Breakers Ratings 20
Dimensions and Knockouts 26
QO 1-Phase and 3-Phase Label Samples 28 29
Wiring Diagrams 30

NOTE: For information on Replacement Parts with specific part numbers,
go to www.schneider-electric.us, click on Product FAQ’s, enter the device
catalog number, click SEARCH, then look for the information required.

2

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
Product Description
PRODUCT DESCRIPTION
QO® Circuit Breaker Load Centers from Square D® are Underwriters
Laboratories (UL) Listed panelboards. They are designed to meet
residential, commercial, and industrial requirements to protect electrical
systems, equipment, and people.

Features
Single- or three-phase construction
30 400 A main lug or main circuit breaker ratings
2 4 2 circuit indoor or outdoor versions
Flush or surface mounting
Aluminum bus construction on fixed mains panels
Service entrance equipment capable panels
Straight-in wiring to minimize service cable installation
Convertible mains to meet changing job site requirements
QO® Circuit Breaker Load Center

Standard 22/10 k AIR series rating on main circuit breaker panels,
increasing application capability
65 k AIR ratings for main lugs panels for industrial applications
65 k AIR rating with optional main circuit breaker on three-phase panels
for industrial applications
Shielded one-piece plated copper bus construction on convertible mains
panels, an industry exclusive for protection and performance
Single captive screw interior mounting on indoor panels to ease removal
Split branch neutral for clutter-free wiring
Top or bottom feed by rotating convertible mains panels 180 degrees
Top or bottom feed for three-phase convertible panels by removing main
circuit breaker and rotating panel 180 degrees
Combination slot/square drive neutral, ground, and cover screws for
positive drive and improved torque
Three grounding bar mounting locations for ease of wiring
Automatic flush adjustment cover to speed installation
Tangential main service knockouts that eliminate offsets
Equipment grounding bar included with main lug load centers
Covers sold separately
Provisions for door lock on convertible mains panel covers
Two branch circuit breaker twistouts that are factory removed for easier
installation of circuit breakers
Side hinge doors on outdoor convertible main panels
Outdoor panel covers lockable with padlock
Manual and automatic transfer switch capability

03/2007

© 2007 Schneider Electric All Rights Reserved

3

QO® and Homeline® Load Centers and Enclosures
Catalog Number Description
CATALOG NUMBER DESCRIPTION
QO® Load Centers
Number Segment
Load Center Family

Character

Description

QO®

UL and NOM Listed

CQO

CSA® Certified

Phase

1

Spaces / Circuits

3040

Mains Type

QO®

1

3040

L

200

G

—

—

Blank or 1 = Single
3 = Three

M

Main circuit breaker

MX

Main circuit breaker for Automatic Transfer Switch

L

Main lugs

U

Universal mains (studs only)

Blank

Purchase separately

G

Included

N

Neutral installed

T

Factory-installed

Blank

Purchase cover separately

C

Combination flush / surface indoor cover

DF

Flush cover with door

DS

Surface cover with door

F

Flush cover

R

Rainproof

RB

Rainproof for B hub

S

Surface cover

CU

Copper bussing

FT

Feed-thru lugs

GP

Generator panel

NM

Non-metallic enclosure

R

Generator receptacle

WG

Wide gutter riser panel

Amperes

Grounding Bar

Cover

Special Construction

QO® Circuit Breakers
Number
Segment
Brand

Character

Description

QO®

1

15

QO

Full Size

QOT

Tandem

Blank

10,000 AIR

EPD

30 mA equipment ground fault protection

GFI

Ground fault circuit interruption

HID

For use on high intensity discharge lighting systems

HM

High magnetic trip circuit breakers are recommended for
applications where high initial inrush current may occur

K

Key operated

PL

Remote control switching capability

SWN

Switch neutral common trip

VH

22,000 AIR

AFI

Arc fault circuit interruption

CAFI

Combination arc fault circuit interruption

—

Number of Poles
Amperes

Device Name

4

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
GENERAL INFORMATION AND APPLICATION DATA
Circuit breaker load centers for use on electrical systems are UL Listed
under File E-6294 (panelboards) and meet Federal Specifications
W-P-115c, Type 1, Class 2 for use in government housing. Select from QO,
QOT, QO-PL, QO-GFI (UL Class A ground fault protection), QO-AFI
(arc fault circuit interrupter), QO-CAFI (combination arc fault interrupter), or
QO-EPD (30 mA equipment ground fault protection) branch circuit breakers.

Service
120 Vac, 1φ2W

240/120 Vac delta, 3φ4W

120/240 Vac, 1φ3W

240 Vac corner grounded delta, 3φ3W

240 Vac delta, 3φ3W

48 Vdc maximum (1φ convertible main
lug 12 4 2 circuit only)

208Y/120 Vac, 3φ4W

Ratings

QO® Circuit Breaker Load Center

Main Lugs

Main Circuit Breaker

Single-Phase

30 400 A

100 4 00 A

Three-Phase

60 225 A

100 2 25 A

Branch Circuit Breakers
10,000 AIR
1-pole, 10 70 A
QO

2-pole, 10 12 5 A
3-pole, 10 10 0 A

QOT
QO-EPD
QO
1-Pole

QO
2-Pole

QO
3-Pole

QO-GFI

QO-EPD 1-Pole

QO-AFI
QO-CAFI

1-pole, 15 20 A
1-pole, 15 30 A
2-pole, 15 60 A
1-pole, 15 30 A
2-pole, 15 60 A
1-pole, 15 20 A
1-pole, 15 20 A
1-pole, 15 50 A

QO-HID

2-pole, 15 50 A
3-pole, 15 30 A

QO-PL
QO-PLILC
QO-SWN
QOK
QO-GFI
1-Pole

QO-GFI
2-Pole

QO-CAFI 1-Pole

1-pole, 10 20 A, 30 A
2-pole, 10 60 A
3-pole, 15 60 A
2-wire, 10 50 A
3-wire, 10 50 A
1-pole, 10 30 A

22,000 AIR

QO-AFI 1-Pole
QO-VHGFI

1-pole, 15 30 A
1-pole, 15 30 A

QO-VH

2-pole, 15 12 5 A
3-pole, 15 10 0 A

QOB-VH

2-pole, 150 A 1
3-pole, 110 150 A 1

42,000 AIR
QOH

2-pole, 40 12 5 A

65,000 AIR
1-pole, 15 30 A
QO-PL 2-Pole

QH

2-pole, 15 30 A
3-pole, 15 30 A

QOK, 1-Pole

03/2007

QO-SWN, 1-Pole

1

For use with 300 A and 400 A load centers only. Requires PK3CA
mounting kit, ordered separately.

© 2007 Schneider Electric All Rights Reserved

5

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Indoor Enclosures (Type 1)
Welded sheet steel with knockouts at top, bottom, back, and sides
Finish: gray baked enamel, electrodeposited over cleaned,
phosphatized steel
Most 100 225 A indoor enclosures are 14.25 in. (362 mm) wide (see
Dimensions and Knockouts on page 26)
300 A and 400 A indoor enclosures are 20 in. (508 mm) wide
Top or bottom feed by rotating enclosure

Indoor Covers
Doors to cover circuit breaker handles, except on 2 4, 4 8, 6 12 , and
8 16 circuit models
Shutter-type twistouts
Flush and surface covers available, sold separately
QO130M150

Flush covers have automatic flush adjustment
Field-installed door lock provisions available on most covers
QOFP filler plates available for all covers
QOM1FP filler plates available for 100 1 25 A convertible load center
covers
QOM2FP filler plates available for 150 2 25 A convertible load center
covers
Q2FP filler plates available for 3-phase load center covers
Triple lead cover screws for fast cover installation

Indoor Cover

Rainproof Enclosures (Type 3R)
Complete enclosure includes interior trim and door
Welded, galvannealed steel
Finish: gray baked enamel, electrodeposited over cleaned,
phosphatized, galvannealed steel
RB devices have provisions for interchangeable bolt-on hub
Top-centered rainproof mounting boss on the back of the enclosure
simplifies installation and saves time
Stainless steel door latch on the enclosure provides secure closure and
maximum durability
Convertible main panels are side-hinge door devices
Allow 1.25 in. (32 mm) on the left side for the door to open

QO140M200RB

Side-hinged door provides full wiring access without door removal

Bolt-On Hubs
Hubs available from 0.75 in. (19 mm) to 4 in. (102 mm) conduit size
No gasket required with hubs from 0.75 in. (19 mm) to 2.50 in. (64 mm)
when used on RB type load centers

Bolt-On Hubs

6

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Class CTL
Class CTL load centers are UL Listed
Circuit breaker mounting rails have slots to accept tandem circuit
breakers, on specified load centers

Meets paragraph 408.35 of the 2005 National Electrical Code® (NEC®)

Phasing
Load centers have distributed phase bussing
Most branch circuit breakers can be mounted in any position

Line Lugs
All lugs suitable for 75 °C copper or aluminum wires (see Main Lugs
and Main Circuit Breaker Ratings on page 20)
Tandem circuit breaker mounts on rails.

Main lugs and main circuit breaker load centers have wire binding screw
torque values on the wiring diagrams and circuit breaker labels

Neutral Assemblies
All lugs suitable for copper or aluminum wire (see Main Lugs and Main
Circuit Breaker Ratings on page 20)
Branch neutral terminals suitable for one #14 #4 AWG copper or one
#12 #4 AWG aluminum wire
Three #14 1/0 AWG copper or #14 #6 AWG aluminum terminals
provided on 12 42 circuits, 100 225 A load centers
Suitable lugs provided on the neutrals for termination of the grounding
conductor
All unused neutral terminals may be used to terminate bare or green
equipment grounding conductors when the load center is used as
service equipment:
Branch Circuit Breaker

one or two #14 # 12 AWG copper
one or two #12 # 10 AWG aluminum

Neutral assemblies accept copper or aluminum wire.

03/2007

© 2007 Schneider Electric All Rights Reserved

7

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Single Phase, 2–16 Circuits, 30–125 A, Fixed Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 20)
Federal Specification W-P-115c, Type 1, Class 2
CSA Certified
File LL-89066-21
For other CSA certified load centers, see Supplemental Digest 174.
Short Circuit Current Rating
QO24L70S

UL short circuit current rating depends on lowest interrupting rating of
circuit breaker installed (see Technical Information on page 20)
Interior
Tin plated aluminum bus
Tin plated copper bus is an available option on 6 12 and 8 16 circuit
load centers
Tin plated copper bus is standard on 4 8 circuit load centers
Mains
Factory-installed main lugs
Top mains positioning only
Top or bottom feed
A backfed main circuit breaker can be field-installed in 4 8 , 6 12 and
8 16 load centers using the PK2MB retaining kit
Cover

QO816L100DS

Flush- or surface-mounted cover included with load centers
A cover with a door is an available option on 6 1 2 and 8 16 circuit load
centers

QO148L125GF

8

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains
UL Listed
File E-6294
Federal Specification W-P-115c, Type 1, Class 2
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 20)
Short Circuit Current Rating
Main Circuit Breaker

Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of
branch circuit breakers installed)
Main circuit breaker: 22,000 AIR standard
22,000 AIR main circuit breaker kits (refer to page 10 and Technical
Information on page 20)
Interior
Shielded, one-piece tin plated copper bus
Removable interior with single, captive mounting screw
Split branch neutral with up to 50% more terminations than required
Multiple mounting locations for equipment grounding bar kits: left, right,
and bottom

Main Lug

Main lugs load centers have equipment grounding bar kits included (not
factory-installed)
Mains
Factory-installed main lugs convertible to main circuit breaker
Load Center Amperage

Main Circuit Breaker Kit Amperage

125

50 125

150

100 15 0

200

100 20 0

225

100 22 5

Factory-installed main circuit breaker convertible to main lugs
Main Circuit Breaker Amperage

Main Lug Kit Amperage

Load Center Amperage

100

125

100

125

125

125

150

225

150

200

225

200

225

225

225

Top or bottom mains positioning. Rotate
entire load center 180 degrees.

03/2007

© 2007 Schneider Electric All Rights Reserved

9

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains,
Continued
Covers
Flush and surface covers sold separately
Flush covers have spring-loaded interior trim for automatic flush
adjustment
Positive action, easy-open door latch
Main Lugs Kits
Field-installable in main circuit breaker or main lugs load centers
QOL125 kit for use in 100 125 A load centers
QOL225 kit for use in 150 225 A load centers
Main Circuit Breaker Kits
Field-installable in main lugs or main circuit breaker load centers
50 2 25 A main circuit breaker kit is 22,000 AIR series rated with 10,000
AIR branch circuit breakers

Cover

Field-Installable Main Circuit Breaker (Convertible Main Load Centers Only)
Main Circuit
Breaker Ampere
Rating 1
QOL125 Kit

Use with
Convertible
Load Center
Mains Rating

22,000 AIR

Lug Wire Size 2
AWG/kcmil
Main Circuit
Al or Cu
Breaker

Lug Torque
lb-in. / N•m

QOM1 Frame Size

QOL225 Kit

50

100 125 A

QOM50VH

60

100 125 A

QOM60VH

70

100 125 A

QOM70VH

80

100 125 A

QOM80VH

90

100 125 A

QOM90VH

100

100 125 A

QOM100VH

110

125 A

QOM110VH

125

125 A

QOM125VH

#12 2/0

50 lb-in.
(6 N•m)

QOM2 Frame Size 3 4

QOM1
Main Frame Size
50–125 A

100

150 225 A

QOM2100VH

125

150 225 A

QOM2125VH

150

150 225 A

QOM2150VH

175

200 225 A

QOM2175VH

200

200 225 A

QOM2200VH

225

225 A

QOM2225VH

#4 30 0

250 lb-in.
(28 N•m)

1

Do not exceed the load center mains rating.

2

Wire range listed for QOM circuit breaker kits is the wire range of that circuit breaker. To find
out maximum wire size permitted in a particular load center per UL, see Main Wire Size
AWG/kcmil on page 20.

3

Add suffix 1021 for shunt trip.

4

Add suffix 8041 for control wire taps.

QOM2
Main Frame Size
100–225 A

10

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Special Purpose
Recreational Vehicle and Manufactured Housing Load Centers
UL Listed (File E-6294) and CSA Certified (LL89066-14)
Single-phase, 2- and 3-wire
Factory-installed equipment grounding bar
Covers included with load centers
Load Centers with Covers
QO2L30TTS

Combination flush/surface cover included with load centers
Equipment grounding bar included on main lug load centers
Top or bottom feed on incoming service by rotating complete load
center 180 degrees
Convertible main load centers
Non-Metallic Load Center
UL Listed
Suitable for use as service equipment
Side-hinge door device
10,000 AIR rating
Single-phase, 2- and 3-wire
Factory-installed grounding bar
Cover included with load center

QO130M150

Knockouts in bottom endwall, side and back
Main Circuit Breaker with Feed-Thru Lugs
Available rainproof enclosure only
Side hinge door devices
Allow 1.25 in. (32 mm) on the left side for the door to open
125, 150, and 200 A mains rating
125, 150, and 200 A feed-thru lugs
Space for up to 8 single-pole circuit breakers

QO24L60NRNM

QO1816M200FTRB

03/2007

© 2007 Schneider Electric All Rights Reserved

11

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Generator Panels
Generator Panel Manu al Transfer
Connects utility and standby power to installed branch circuits
Includes two factory-installed 2-pole main circuit breakers tied together
with a mechanical interlock
30 A and 60 A main circuit breaker versions
Supply up to 8 branch circuits using tandem circuit breakers
Available indoor enclosure only
Cover with door included
QO48M60DSGP

Generator Panel Automatic

Transfer

QO® load center platform construction
Automatic transfer from utility to back-up power source
Transfer cycle less than 10 seconds
Indoor and outdoor enclosures
120 / 240 Vac single-phase
150, 200 and 225 A main circuit breaker
42 circuit maximum construction, indoor, 28 circuit maximum outdoor
125 A maximum branch feeder connection to an alternative energy source
Service entrance rated
Manual override capability
Easy removal of interior and transfer switch for rough in wiring
5-year limited warranty
Compatible with standard load center field-installable accessories
Riser Panels
Offset interior provides ample wire gutter space for high rise applications
Factory-installed main lugs (125 A), convertible to main circuit breaker
with standard QOC cover and optional Mono-Flat cover

QO® Intelligent Load Center

Factory-installed main lugs (200 A), convertible to main circuit breaker
when used with QOC cover only
Available in 12 to 40 circuits
Indoor only

Optional Mono-Flat® cover available for both 125 A and 200 A panels
(sold separately)

Wide Gutter

12

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Three-Phase, 3–42 Circuits, 60–225 A, Convertible or Fixed Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 19)
Short Circuit Current Rating
Main lugs: up to 65,000 AIR (depends on lowest interrupting rating of
branch circuit breakers installed)
Main circuit breaker up to 225 A: 22,000 AIR standard; optional up to
65,000 AIR for 100 A to 225 A main circuit breakers
Mains
Factory-installed main lugs or main circuit breaker
Main neutral terminal located next to the phase terminals on 125 2 25 A
main circuit breaker devices
QO330L200G

Top or bottom feed (see Technical Information on page 24)
Fully convertible from main circuit breaker to main lugs (100 225 A)

100 A maximum back-fed main QO® circuit breaker; requires the use of
retaining kit PK3MB
Cover
Flush- and surface-mount covers sold separately
Flush covers have spring-loaded interior trim for automatic flush
adjustment
Positive action, easy-to-open door latch
Interior
Shielded one-piece plated copper bus on 100 2 25 A
Removable interior with single, captive mounting screw on 100 22 5 A
(indoor only)
Main lugs load centers have equipment grounding bar kits included
(not factory-installed)
Branch Neutral Termination
Suitable for copper or aluminum wire
Terminals suitable for one #14 #4 AWG coppe r or one #12 #4 AWG
aluminum wire
Positioned on both sides of the mains compartment
QO330MQ150

03/2007

Slot/square drive wire binding screws
Three (3) #14 1 /0 AWG copper or #14 # 6 AWG aluminum terminations
standard on 12 4 2 circuits, 100 22 5 A load centers

© 2007 Schneider Electric All Rights Reserved

13

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Three-Phase, 3–42 Circuits, 60–225 A, Convertible or Fixed
Mains (Continued)
Main Lugs Kits
Field-installable in main circuit breaker or main lugs load centers
QOL3125 kit for use in 100 125 A load centers
QOL3225 kit for use in 150 225 A load centers
Main Circuit Breakers
Field-installable in main circuit breaker load centers

25,000 AIR QDL main circuit breakers series rated with 10,000 AIR QO®
branch circuit breakers
100 225 A main circuit breakers are series rated up to 100,000 AIR (see
table below) with 10,000 AIR branch circuit breakers in 30 circuit or
larger main circuit breaker load centers with optional QJL main circuit
breaker

QOL3225
Main Lugs Kit

Back-fed QO-VH (100 A maximum) main circuit breaker may be field
installed in main lugs and main circuit breaker load centers (requires
PK3MB retaining kit)
27 circuit, 100 A main circuit breaker load center includes factoryinstalled back-fed QO-VH main circuit breaker
Electrical accessories are not available on QDL, QGL, or QJL circuit
breakers
30 4 2 circuit, 125 22 5 A main circuit breaker load centers include
integral QDL circuit breakers. Optional QGL and QJL circuit breakers
available as shown:

QDL Circuit Breaker
70–225 A

1

14

© 2007 Schneider Electric All Rights Reserved

Amperage

25,000 AIR

65,000 AIR

100,000 AIR 1

70

QDL32070

QGL32070

QJL32070

80

QDL32080

QGL32080

QJL32080

90

QDL32090

QGL32090

QJL32090

100

QDL32100

QGL32100

QJL32100

110

QDL32110

QGL32110

QJL32110

125

QDL32125

QGL32125

QJL32125

150

QDL32150

QGL32150

QJL32150

175

QDL32175

QGL32175

QJL32175

200

QDL32200

QGL32200

QJL32200

225

QDL32225

QGL32225

QJL32225

When these 3-pole circuit breakers are used as the main circuit breaker of a three-phase
load center, the maximum AIR rating is 65,000 at 240 Vac and 100,000 at 208 Vac.

03/2007

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Single-Phase, 12–42 Circuits, 300–400 A, Fixed Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 20)
Short Circuit Current Rating
Main lugs: up to 65,000 AIR
Main circuit breaker: 42,000 AIR fully rated (see Technical Information
on page 20)
Mains
Factory-installed main lugs and main circuit breaker
Multiple wire terminals for phases and neutral
Top or bottom mains positioning (see Technical Information on
page 20)
Cover
Flush- and surface-mount covers sold separately
Interior
Available in single-phase construction

Interiors accept QO® and QOB-VH 110 150 A maximum circuit
breakers (QOB-VH circuit breakers require connector kit PK3CA)
Tin plated aluminum bus
QON42MS400 and MH68

Tin plated copper connector fingers
Neutral assemblies positioned opposite the mains compartment
Enclosures
20 in. (508 mm) wide galvanized steel
Embossed 0.25 in. (6 mm) standoffs
End walls, one blank and one with knockouts, are standard; both are
removable and interchangeable
Embossed keyholes centered at both ends and in visual positioning
Multiple grounding bar mounting locations
Wire management braces

QON42LS400 and MH53

03/2007

© 2007 Schneider Electric All Rights Reserved

15

QO® Circuit Breaker Load Centers—Class 1130
General Information and Application Data
Accessories
Grounding Bar Kits
Field-installable in all load centers
Same wire size as terminals (see page 19)
PG18GTA Grounding Bar Kit

Suitable for copper or aluminum wire
Available with #1 4/0 lug PK15GTA-L, PK18GTA-L, and PK23GTA-L
(see page 19)
Flush Lock Kits
Available for indoor load centers
Two keys provided with each lock kit
PK6FL for convertible 12 42 circuit load centers
PK4FL for 300 and 400 A load centers

PK6FL Flush Lock Kit

Auxiliary Neutral Lugs
UL Listed for copper or aluminum wire
Field-installable on neutral assembly
LK70AN:#12 # 2 AWG Al or #14 #4 AWG Cu
LK100AN:#6 2 /0 AWG (Al/Cu)
LK125AN:#14 2/0 AWG (Al/Cu)
PK4FL Flush Lock Kit

LK150AN:#2 3 /0 AWG (Al/Cu)
LK225AN:#4 3 00 kcmil (Al/Cu), use ONLY in Series S, 150 22 5 A
QO® or Homeline® load center
Cover Filler Plates
Fast to install, snap-in type
QOFP branch circuit
QOM1FP for 70 125 A, single-phase, main circuit breakers
QOM2FP for 150 22 5 A, single-phase, main circuit breakers
Q2FP for 125 225 A, three-phase, main circuit breakers

LK150AN

LK100AN

LK70AN

Auxiliary Neutral Lugs

QOFP Cover Filler Plate

16

© 2007 Schneider Electric All Rights Reserved

Q2FP Cover Filler Plate

03/2007

QO® and Homeline® Load Centers and Enclosures
General Information and Application Data
Accessories (Continued)
Surgebreaker® Secondary Surge Arrester
QO2175SB UL Listed secondary surge arrester
Easy plug-on installation for QO® load centers
LED indicates operational status
Plug-on design requires two pole spaces
Designed to protect electrical service and major household appliances ,
excluding electronic devices
Back-Fed Main Circuit Breaker Retaining Kits
Back-fed main circuit breaker retaining kits secure 2-pole, 10 125 A circuit
breakers to single-phase or three-phase mains interiors when used as
back-fed main circuit breakers. Mounting of retaining kits is based on
top-feed applications.
QO2175SB

Catalog No.

Description

PK2MB

QO 6 1 2, 4 8, and 8 16 loa d centers

PK3MB

Three-phase load centers

PK4MB2LA

Mounts on the right side of QO single-phase, 100 125 A convertible main load
center, series S01 and S02. Retains one 2-pole QO circuit breaker with or
without electrical accessories.

PK4MB2HA

Mounts on the right side of QO single-phase, 150 225 A convertible main load
center, series S01 and S02. Retains one 2-pole QO circuit breaker with or
without electrical accessories.

UL Listed Manual Transfer Equipment Kits
Manual transfer equipment kits secure two 2-pole, 10 125 A circuit breakers.
Back-fed Main Circuit Breaker
Retaining Kit (PK4MB2LA)

QO Manual Transfer
Equipment Kit (PK4DTIM4HA)

Catalog No.

Description

QO2DTI

For interlocking the handles of two 2-pole or one 2-pole and one 1-pole QO
and Q1 circuit breakers mounted side-by-side so that only one circuit breaker
can be ON at a time.

QO2DTIM

QO2DTI mechanical interlock attachment with retaining kits for securing two
adjacent back-fed circuit breakers in dual power supply applications. Can be
used with two 2-pole or one 2-pole and one 1-pole QO circuit breakers in
QO816L100 load centers.

PK4DTIM4LA

Mounts on the right side of QO single-phase, 100 125 A convertible main load
center, series S01 and S02. Retains two 2-pole QO circuit breakers with a
QO2DTI kit included for dual power supply applications.

PK4DTIM4HA

Mounts on the right side of QO single-phase, 150 225 A convertible main load
center, series S01 and S02. Retains two 2-pole QO circuit breakers with a
QO2DTI kit included for dual power supply applications.

PK4DTIM4LAL

Mounts on the left side of QO single-phase, 100 1 25 A convertible main load
center, series S01 and S02. Retains two 2-pole QO circuit breakers with a
QO2DTI kit included for dual power supply applications.

Generator Circuit Breaker Interlock Kit
Catalog No.

Description

QOCRBGK1

For use on "G" and "S" Series NEMA Type 1 and "G", "S1" and "S2" Series
NEMA Type 3R load centers. Interlocks a QOM1, 2-pole main circuit breaker
of a load center (100-125 A) with a QO, 2-pole (15-125 A) branch circuit
breaker. Includes a retaining kit.

QOCGK2

For use on G and S Series NEMA Type 1 and G and S1 Series NEMA
Type 3R load centers. Interlocks a QOM2, 2-pole main circuit breaker of a
load center (150 22 5 A) with a QO 2-pole (15 12 5 A) branch circuit breaker.
Includes a retaining kit.

QORBGK2

For use on S2 Series NEMA Type 3R load centers. Interlocks a QOM2 2-pole
main circuit breaker of a load center (150 225 A) with a QO 2-pole (15 1 25 A)
branch circuit breaker. Includes a retaining kit.

Generator Interlock Kit Installed

03/2007

© 2007 Schneider Electric All Rights Reserved

17

QO® Circuit Breaker Load Centers—Class 1130
General Information and Application Data
Accessories (Continued)
Auxiliary Gutters and Tap Kits
Field-installable on the left or right side of load centers
Auxiliary gutters are 13.50 in. wide x 26.12 in. height x 3.75 in. deep
Conduit riser sizes: 1-3/4, 2, 2-1/2 or 3 in. (3 in. requires use of B300
bolt-on hubs)
Flush cover included with auxiliary gutter
Tap kits required for each riser wire to be tapped (see below for tap kits)
Wire range on tap kits is #4 AWG to 300 kcmil copper or aluminum
Tap kits include mechanical-type lugs or studs for crimp-type lugs
Crimp-type lugs not included in tap kits (order separately)
Auxiliary Gutter (SDAG26) to Load Center Catalog Number Reference
QO® Single-Phase

QO112L125G
QO11224L125G
QO112L125GC
QO11224L125GC
QO116L125G
QO11624L125G
QO120L125G
QO12024L125G
QO124L125G
QO120L125GC

QO® Three-Phase

QO312L125G
QO320L125G
QO324L125G

SDAG26
With Tap Kits Installed

QO112M100
QO116M100
QO120M100
QO124M100
QO124M125
QO112M100C
QO11220M100C
QO116M100C
QO120M100C

Tap Kits
UL Listed for Use with Auxiliary Gutter SDAG26
Riser Wire
Catalog Number

Tap Kit with
Mechanical Lugs

Tap Kit for
Crimp Lugs

Tap Off Wire

Lug Type

SDGT30020

Mechanical

SDGT300300

Mechanical

Wire Size

Lug Type

Wire Size

(2) #6 AWG 3 00 kcmil Mechanical (1) #6 AWG 2 /0 AWG
(2) #6 AWG 3 00 kcmil Mechanical (1) #6 AWG 30 0 kcmil

SDGT300C10C

Crimp

(2) #4 AWG 3 00 kcmil

Crimp

(1) #8 AWG 1 /0 AWG

SDGT300C300C

Crimp

(2) #4 AWG 3 00 kcmil

Crimp

(1) #4 AWG 30 0 kcmil

QOGL20
(grounding lugs)

Mechanical

(2) #6 AWG 2/0 AWG

Auxiliary Gutter
UL Listed for Use with Standard Load Centers for Riser Applications
SDAG26

Flush

No

N/A

See Tap
Kit

No

Bolt-On Hubs

RB Hub

Equipment with an RB suffix, meaning Rainproof Type 3R construction,
uses the bolt-on hubs listed below. RB devices will accept 0.75 in. (19 mm)
through 2.50 in. (64 mm) bolt-on hubs without the use of reducers. Offcenter conduit thread openings and elongated mounting holes provide quick
and easy adjustment to eliminate costly conduit offsets and bends. Hubs are
suitable for use with conduit having ANSI standard taper pipe thread.
UL Listed Bolt-On Hubs for RB Devices
Conduit Size

0.75 in.
19 mm

1.00 in.
25 mm

1.25 in.
32 mm

1.50 in.
38 mm

2.00 in.
51 mm

2.50 in.
64 mm

Hub Cat. No.

B075

B100

B125

B150

B200

B250

NOTE: Closing cap (catalog number B-CAP) is provided factory-installed on each device having the RB suffix.

BC200 Enclosure Coupling

UL Listed Enclosure Coupling for RB Devices
Cat. No.
BC200

18

© 2007 Schneider Electric All Rights Reserved

Designed for connecting wireway or other enclosures to units having RB
bolt-on conduit provisions. Provides a bushed opening equal to 2 inch conduit.
Eliminates the need for conduit nippling.

03/2007

QO® and Homeline® Load Centers and Enclosures
Technical Information
TECHNICAL INFORMATION

Slot / Robertson screw

Grounding Bar Kits

0.437
[11]

All PK equipment grounding kits are supplied with mounting screws,
necessary installation instructions, and an Equipment Grounding Terminal
self-adhesive label.
Terminals
Catalog
Number

0.3125
[8]

Quantity Each Size
See “Wire Range
Table” below.
I

Cross Section of Size 1 Ground Bar
in.
Dimensions: [mm]

PK0GTA21

2

PK0GTA6

2

6

PK3GTA1

3

PK4GTA3

II

III IV V VI
2
6

Distance
Between
Mounting
Holes

Mounting

in.

mm

in.

mm

1.75

44

One
hole

One
hole

Top

4.61

117

1.69

43

Top

One
hole

Top

One
hole

Top

3

3

1.38

35

One
hole

4

4

1.63

41

One
hole

4

PK5GTA

5

5

2.25

57

1.25

32

Top

PK7GTA3

7

7

2.88

73

1.25

32

Top or side

PK9GTA13

9

9

3.25

83

One
hole

One
hole

Top

3

9

9

3.78

96

3.13

80

Top

PK12GTA3

12

12

4.70

119

3.13

80

Top

PK15GTA3

15

15

5.63

143

3.13

80

Top

PK15GTAL5

16

15

8.13

207

3.13

80

Top

PK15GTA66

21

15

5.88

149

7

7

Top

PK18GTA3

18

18

6.56

167

3.13

80

Top

PK18GTAL5

19

18

8.81

224

3.13

80

Top

PK23GTA3

23

23

8.11

206

3.13

80

Top

PK23GTAL5

24

23

9.44

240

3.13

80

Top

27 or
26

27
26

9.36

238

3.13

80

Top

PK9GTA

PK27GTA

03/2007

Total
Qty.

Approximate
Overall
Length

38

1
6
1
1
1

1

Mounting screw 40205-065-01 (one required).

2

Mounting screw 21922-18360 (two required).

3

Mounting screw 21594-14220 (two required).

4

Mounting screw 21594-14241 (two required).

5

Mounting screw 21594-14302 (two required).

6

Mounting screws 21594-14241(two required) and 21594-17121(two required).

7

3.13 in. (80 mm) on small terminals; 5.25 in. (133 mm) on large terminals.

8

PK27GTA includes one main grounding lug that mounts with two terminal screws and requires
three terminals for mounting.
Size

Cu (AWG)

Al (AWG)

I

(1) #14 # 4 or (2) #14 or #12

(1) #12 #4 or (2) #12 or #10
(1) #1 4/0

II

(1) #1 4/ 0

III

(1) #6 2/ 0

(1) #6 2/0

IV

(1) #6 3/ 0

(1) #6 3/0

V

(1) #14 1 /0

(1) #14 1/0

VI

(1) #10 2/0

(1) #6 2 /0

© 2007 Schneider Electric All Rights Reserved

19

QO® Circuit Breaker Load Centers—Class 1130
Technical Information
Main Lugs and Main Circuit Breaker Ratings
Single-Phase, Three-Wire, 120/240 Vac; Main Lugs
Mains
Rating in
Amps

Load Center Catalog
Number

Load Center
Cover Catalog
Number

Indoor

UL Listed
Service
Equipment
(See notes)

Maximum
UL Short
Circuit
Rating 1

Main Wire Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Page 26)

Top
or Bottom
Mains
Position

UL Listed for
Corner
Grounded
Delta
Systems

Fixed Mains – Factory-Installed Main Lugs
30

QO2L30S

Included

No

10,000 A

#12 10 Al
#14 10 Cu

1

Top

No

70

QO24L70F/S

Included

B

10,000 A

#12 3 Al
#14 4 Cu

2

Top

No

100

100

125

QO612L100F/S

Included

B, C

10,000 A

#8 1

4

Top

QO612L100DF/S

Included

B, C

10,000 A

#8 1

4

Top

QO612L100DFCU/SCU

Included

B, C

10,000 A

#8 1

4

Top

QO816L100F/S

Included

B, C

10,000 A

#8 1

4

Top

QO816L100DF/S

Included

B, C

10,000 A

#8 1

4

Top

QO816L100DFCU/SCU

Included

B, C

10,000 A

#8 1

4

Top

QO148L125GF/S

Included

B, C

10,000 A

#12 2 /0 Al
#14 2/ 0 Cu

21

Top

No

No

No

Convertible Mains – Factory-Installed Main Lugs
QOM1 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus

125

QO112L125G

QOC16UF/S

B, C

65,000 A 2 3

#6 2/ 0

6

Both

QO11224L125G

QOC16UF/S

B, C

65,000 A 2 3

#6 2/ 0

6

Both

QO116L125G

QOC24UF/S

B, C

65,000 A 2 3

#6 2/ 0

7

Both

QO11624L125G

QOC24UF/S

B, C

65,000 A 2 3

#6 2/ 0

7

Both

QO120L125G

QOC24UF/S

B

65,000 A 2 3

#6 2/ 0

7

Both

QO12024L125G

QOC24UF/S

B

7

Both

QOC24UF/S

B

65,000 A 2 3
65,000 A 2 3

#6 2/ 0

QO124L125G

#6 2/ 0

7

Both

QO132L125G

QOC32UF/S

B

65,000 A 2 3

#6 2/ 0

8

Both

Yes

Convertible Mains – Factory-Installed Main Lugs
QOM2 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus
150

200

225

QO12030L125G

QOC30UF/S

B, C

65,000 A 2 3

#6 25 0

9

Both

QO124L150G

QOC30UF/S

B, C

65,000 A 2 3

#6 25 0

9

Both

QO130L150G

QOC30UF/S

B, C

65,000 A 2 3

#6 25 0

9

Both

Yes

QO112L200G

QOC30UF/S

B, C

9

Both

QOC40UF/S

B, C

65,000 A 2 3
65,000 A 2 3

#6 25 0

QO12436L200TFT

#6 25 0

10

Both

QO130L200G

QOC30UF/S

B, C

65,000 A 2 3

#6 25 0

9

Both

QO13040L200G

QOC30UF/S

B, C

65,000 A 2 3

#6 25 0

9

Both

QO140L200G

QOC40UF/S

B, C

65,000 A 2 3

#6 25 0

10

Both

QO142L225G

QOC42UF/S

B

65,000 A 2 3

#6 30 0

11

Both

Yes

MHC50VF/S

C

65,000 A 4

15

Both

Yes

MHC50QVF/S

No

65,000 A 4

15

Both

Yes

MHC53QVF/S

No

65,000 A 4

17

Both

Yes

Yes

Fixed Mains – Factory-Installed Main Lugs
QON12LS400 (Interior)
MH50 (Enclosure)
400

QON30LS400 (Interior)
MH50 (Enclosure)
QON42LS400 (Interior)
MH53 (Enclosure)

(1)1/0 750
(2)1/0 300
(1)1/0 750
(2)1/0 300
(1)1/0 750
(2)1/0 300

1

Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.

2

UL Listed for 5000 A rms symmetrical short circuit rating when used in 3-phase, 240 Vac, corner grounded Delta systems, when used as main lugs load center only.
Use 240 Vac circuit breakers only.

3

22,000 A rms symmetrical maximum when supplied by integral type QOM-VH main circuit breaker from Square D® with 22,000 A rms symmetrical minimum
interrupting rating and when all installed QO® branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.

4

UL Listed for 5000 A rms symmetrical short circuit rating when used on 3-phase, 240 Vac, corner grounded Delta systems. Use 240 Vac circuit breakers only.

B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and
when not used as a lighting and appliance branch circuit panelboard.

20

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
Technical Information
Single-Phase, Three-Wire, 120/240 Vac; Main Circuit Breaker Ind oor
Mains
Rating in
Amps

Load Center
Catalog Number

Load Center
Cover Catalog
Number

UL Listed
Service
Equipment
(See Notes)

Maximum
UL Short
Circuit
Rating 1

Main Wire Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Page 26)

Top
or Bottom
Mains
Position

UL Listed for
Corner
Grounded
Delta Systems

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM1 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker – Copper Bus

100

125

QO112M100

QOC12UF/S

A, B

22,000 A 2

#4 1

5

Both

QO116M100

QOC20U100F/S

A, B

22,000 A 2

#4 1

6

Both

QO120M100

QOC20U100F/S

A, B

22,000 A 2

#4 1

6

Both

QO124M100

QOC24UF/S

A, B

22,000 A 2

#4 1

7

Both

QO132M100

QOC32UF

A, B

22,000 A 2

#4 1

8

Both

QO124M125

QOC24UF/S

A, B

22,000 A 2

#4 2/0

7

Both

QO132M125

QOC32UF

A, B

22,000 A 2

#4 2/0

8

Both

No

No

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM2 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker – Copper Bus

150

200

225

QO12030M150

QOC30UF/S

A, B

22,000 A 2

#4 250

9

Both

QO124M150

QOC30UF/S

A, B

22,000 A 2

#4 250

9

Both

QO130M150

QOC30UF/S

A, B

22,000 A 2

#4 250

9

Both

2

No

QO132M150

QOC40UF/S

A, B

22,000 A

#4 250

10

Both

QO12040M200

QOC30UF/S

A, B

22,000 A 2

#4 250

9

Both

QO124M200

QOC30UF/S

A, B

22,000 A 2

#4 250

9

Both

QO130M200

QOC30UF/S

A, B

22,000 A 2

#4 250

9

Both

QO13040M200

QOC30UF/S

A, B

22,000 A 2

#4 250

9

Both

QO140M200

QOC40UF/S

A, B

22,000 A 2

#4 250

10

Both

QO142M200

QOC42UF/S

A, B

22,000 A 2

#4 250

11

Both

QO140M225

QOC42UF/S

A, B

22,000 A 2

#4 300

11

Both

QO142M225

QOC42UF/S

A, B

22,000 A 2

#4 300

11

Both

16

Both

Yes

16

Both

Yes

No

No

Fixed Mains – Factory-Installed Main Circuit Breaker
300
400

QON42MS300
MH68 (Enclosure)
QON42MS400
MH68 (Enclosure)

MHC68VF/S

A

42,000 A 3

MHC68VF/S

A

42,000 A 3

(1)#4 500
(2)#4 3 /0
(1)#4 600
(2)#4 250

1

Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.

2

22,000 A rms symmetrical maximum when supplied by integral type QOM-VH main circuit breaker from Square D® with 22,000 A rms symmetrical minimum
interrupting rating and when all installed QO® branch circuit breakers have 10,0000 A rms symmetrical minimum interrupting rating. 65,000 A rms symmetrical
maximum when main lugs kits are installed.

3

UL Listed for 5000 A rms symmetrical short circuit current rating when used in 3-phase, 240 Vac, corner grounded Delta systems. Use 240 Vac circuit breakers only.

A UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with factory-installed service disconnect.
B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field installed main lugs when not more than six disconnecting
means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch Circuit Panelboard.

03/2007

© 2007 Schneider Electric All Rights Reserved

21

QO® and Homeline® Load Centers and Enclosures
Technical Information
Single-Phase, Three-Wire, 120/240 Vac; Main Lugs
Mains
Rating in
Amps

Load Center
Catalog Number

Load Center
Cover Catalog
Number 1

Rainproof

UL Listed
Service
Equipment
(See Notes)

Maximum UL
Short Circuit
Rating 2

Main Wire Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Page 27)

Top
or Bottom
Mains
Position

UL Listed for
Corner Grounded
Delta Systems

Fixed Mains – Factory-Installed Main Lugs
40

QO2L40RB

Included

B

10,000 A

#12 6
#14 10

1R

Top

No

60

QO24L60NRNM

Included

B

10,000 A

#14 4

1NM

Top

No

10,000 A

#12 3
#14 4

1R

Top

No

Top

70

100

100
125

QO24L70RB

Included

B

QO612L100RB

Included

B, C

10,000 A

#8 1

2R

QO612L100TRB

Included

B, C

10,000 A

#8 1

2R

Top

QO612L100RBCU

Included

B, C

10,000 A

#8 1

2R

Top

QO816L100RB

Included

B, C

10,000 A

#8 1

2R

Top

QO816L100RBCU

Included

B, C

10,000 A

#8 1

2R

Top

QO148L125GRB

Included

B, C

10,000 A

#12 2/ 0
#14 2/ 0

15R

Top

No

No
No

Convertible Mains – Factory-Installed Main Lugs
QOM1 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus

125

QO112L125GRB

Included

B, C

65,000 A 3 4

#6 2 /0

3R

Top

QO11224L125GRB

Included

B, C

65,000 A 3 4

#6 2 /0

3R

Top

QO11624L125GRB

Included

B, C

65,000 A 3 4

#6 2 /0

4R

Top

QO124L125GRB

Included

B, C

65,000 A 3 4

#6 2 /0

4R

Top

Yes

Convertible Mains – Factory-Installed Main Lugs
QOM2 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus
150

200

225

QO130L150GRB

Included

B, C

65,000 A 3 4

#6 250

6R

Top

QO112L200GRB

Included

B, C

65,000 A 3 4

#6 250

5R

Top

QO130L200GRB

Included

B, C

65,000 A 3 4

#6 250

6R

Top

QO13040L200GRB

Included

B, C

65,000 A 3 4

#6 250

6R

Top

QO140L200GRB

Included

B, C

7R

Top

Yes

Included

B, C

65,000 A 3 4
65,000 A 3 4

#6 250

QO142L225GRB

#6 300

8R

Top

Yes

Yes
Yes

1

Convertible mains load center has a side-hinge door. Allow 1.25 in. (32 mm) on the left side for the door to open.

2

Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.

3

UL Listed at 5000 A rms symmetrical short circuit current rating when used in 3-phase, corner grounded, Delta systems, when used as main lugs load center only.
Use 240 Vac circuit breakers only.

4

22,000 A rms symmetrical maximum when supplied by integral type QOM-VH main circuit breaker from Square D® with 22,000 A rms symmetrical minimum
interrupting rating and when all QO® installed branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.

B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and
when not used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch Circuit Panelboard.

22

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
Technical Information
Single-Phase, Three-Wire, 120/240 Vac; Main Circuit Breaker
Mains
Rating
in
Amps

Load Center
Catalog
Number

Load Center
Cover Catalog
Number 1

UL Listed
Service
Equipment
(See Notes)

Rainproof
Maximum
UL Short
Circuit
Rating 2

Main Wire
Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Page 27)

Top
or Bottom
Mains
Position

UL Listed for
Corner
Grounded
Delta Systems

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM1 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker – Copper Bus
100
125

QO112M100RB

Included

A, D

22,000 A 3

#6 2/0

3R

Top

QO116M100RB

Included

A, D

22,000 A 3

#6 2/0

4R

Top

QO120M100RB

Included

A, D

22,000 A 3

#6 2/0

4R

Top

QO124M125RB

Included

A, D

22,000 A 3

#6 2/0

4R

Top

No
No

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM2 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker – Copper Bus
150

200

QO12030M150RB

Included

A, D

22,000 A 3

#4 250

5R

Top

QO130M150RB

Included

A, D

22,000 A 3

#4 250

6R

Top

QO12040M200RB

Included

A, D

22,000 A 3

#4 250

5R

Top

QO130M200RB

Included

A, D

22,000 A 3

#4 250

6R

Top

QO140M200RB

Included

A, D

22,000 A 3

#4 250

7R

Top

No

No

Convertible Mains – Factory-Installed Main Circuit Breaker with Feed-Thru Lugs
QOM1/QOM2 Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker – Copper Bus
125

QO1612M125FTRB 4

Included

A, D

22,000 A 3

#4 2/0

3R

Top

No

150

QO1816M150FTRB

4

Included

A, D

22,000 A 3

#4 250

6R

Top

No

200

QO1816M200FTRB 4

Included

A, D

22,000 A 3

#4 250

6R

Top

No

1

Convertible mains load center has a side-hinge door. Allow 1.25 in. (32 mm) on the left side for the door to open.

2

Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.

3

22,000 A rms symmetrical maximum when supplied by integral type QOM-VH main circuit breaker from Square D® with 22,000 A rms symmetrical minimum
interrupting rating and when all installed QO® branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating. 65,000 A rms symmetrical
maximum when main lug kits installed.

4

QO1612M125FTRB provided with QOM1 frame main circuit breaker. QO1816M150/200FTRB provided with QOM2 frame main circuit breaker.

A UL Listed as suitable for use as service equipment (neutral bonded at time of installation) with factory-installed service disconnect.
D UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs when not more than six service
disconnecting means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch
Circuit Panelboard.

03/2007

© 2007 Schneider Electric All Rights Reserved

23

QO® Circuit Breaker Load Centers—Class 1130
Technical Information
3-Phase, 4-Wire, 208Y/120 Vac; 3-Phase, 4-Wire, 240/120 Vac, Delta;
3-Phase, 3-Wire, 240 Vac, Delta; Main Lugs, Main Circuit Breaker In door
Mains
Rating
in Amps

Load Center
Catalog Number

UL Listed
Load Center
Service
Cover Catalog
Equipment
Number
(See Notes)

Maximum UL
Short Circuit
Rating 1

Main Wire Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Page 26)

Top or
Bottom
Mains
Position

UL Listed for
Corner
Grounded Delta
Systems

No

Fixed Mains – Factory-Installed Main Lugs – Copper Bus
60

QO312L125G
125

200
225

Included

B

22,000 A 1

#10-6

13

Top

2

QOC16UF/S

B, C

65,000 A 1

#6 2 /0

#6 2/ 0

6

Both

QO403L60NF/S
QO320L125G 2

QOC24UF/S

B, C

65,000 A 1

#6 2 /0

#6 2/ 0

7

Both

QO324L125G 2

QOC24UF/S

B, C

65,000 A 1

#6 2 /0

#6 2/ 0

7

Both

QO318L200G 2

QOC30UF/S

B, C

65,000 A 1

#6 250

#6 2 50

9

Both

2

QOC30UF/S

B, C

65,000 A 1

#6 250

#6 2 50

9

Both

QO342L225G 2

QOC42UF/S

B

65,000 A 1

#6 300

#6 3 00

11

Both

QO330L200G

No

No
No

Convertible Mains – Factory-Installed QDL Main Circuit Breaker – Copper Bus
100

QO327M100 3

QOC30UF/S

A, D

#4 2/ 0

9

Both

No

QO330MQ125 2 4

QOC342MQF/S

A, D

22,000 A
100,000 A 5 6

#4 2 /0

125

#4 300

#4 3 00

12

H

No

QO330MQ150 2 4

QOC342MQF/S

A, D

100,000 A 5 6

#4 300

#4 3 00

12

H

QO342MQ150 2 4

QOC342MQF/S

A, D

100,000 A 5 6

#4 300

#4 3 00

12

H

56

150
200
225

24

QOC342MQF/S

A, D

#4 3 00

12

H

QOC342MQF/S

A, D

100,000 A
100,000 A 5 6

#4 300

QO342MQ200 2 4

#4 300

#4 3 00

12

H

QO342MQ225 2 4

QOC342MQF/S

A, D

100,000 A 5 6

#4 300

#4 3 00

12

H

QO330MQ200

No
No
No

1

Short circuit current rating depends on lowest AIR rating of branch circuit breaker installed.

2

Certified to IEC 60439-1 for use on 415Y/240 Vac 3-phase 4-wire, 3,000 SCCR when QODX ... branch circuit breakers are used and 10,000 SCCR when QO...VS
branch circuit breakers are used. CE marked.

3

Includes factory-installed back-fed QO3100VH main circuit breaker.

4

Mains positioning from top to bottom feed: first rotate the main circuit breaker 180 degrees, then rotate the complete load center 180 degrees.

5

100,000 A rms at 208 Vac symmetrical maximum when type QJL main circuit breaker from Square D® with 100,000 A rms minimum interrupting rating is installed
and when all installed QO® and Q1 branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.

6

25,000 A rms symmetrical maximum when supplied by integral type QDL main circuit breaker from Square D® with 25,000 A rms minimum interrupting rating and
when all installed QO® and Q1 branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.

A UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with factory-installed service disconnect.
B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and
when not used as a lighting and appliance branch circuit panelboard. See NEC Section 384-14.
D UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs, when not more than six service
disconnecting means are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch
Circuit Panelboard.

24

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
Technical Information
Mains
Rating
in
Amps

Load Center
Catalog Number

Load Center
Cover
Catalog
Number

UL Listed Service
Equipment
(See Notes)

Maximum UL
Short
Circuit Rating 1

Main Wire Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Pages 26
and 27)

UL Listed for
Top or Bottom
Corner Grounded
Mains Position
Delta Systems

Load Center with Cover – 1-Phase, 3-Wire, 120/240 Vac – UL Listed; Complete QO® Load Center – Box, Interior and Combination Cover (in one package)
Convertible Mains – Factory-Installed Main Lugs; QOM1 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus
125

QO112L125GC

Included

B, C

65,000 A 2 3

#4 2 /0

6

Both

Yes

QO11224L125GC

Included

B, C

65,000 A 2 3

#4 2 /0

6

Both

Yes

QO120L125GC

Included

B, C

65,000 A 2 3

#4 2 /0

7

Both

Yes

Convertible Mains – Factory-Installed Main Lugs; QOM2 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus
150

QO130L150TC

Included

B, C

65,000 A 2 3

#4 2 50

9

Both

Yes

200

QO13040L200GC

Included

B, C

65,000 A 2 3

#4 2 50

9

Both

Yes

Convertible Mains – Factory-Installed Main Circuit Breaker – 22,000 RMS Symmetrical Amperes Short Circuit Current Rating
QOM1 Main Frame Size – Convertible to Main Lugs – Copper Bus

100

QO112M100C

Included

A, D

22,000 A 2

#4-1/0

5

Both

Yes

QO11220M100C

Included

A, D

22,000 A 2

#4-1/0

5

Both

Yes

QO116M100C

Included

A, D

22,000 A 2

#4-1/0

6

Both

Yes

QO120M100C

Included

A, D

22,000 A 2

#4-1/0

6

Both

Yes

Convertible Mains – Factory-Installed Main Circuit Breaker – 22,000 RMS Sym. Amperes Short Circuit Current Rating
QOM2 Main Frame Size – Convertible to Main Lugs – Copper Bus
150

200 A

QO12030M150C

Included

A, D

22,000 A 2

#4 2 50

9

Both

No

QO130M150C

Included

A, D

22,000 A 2

#4 2 50

9

Both

No

QO12040M200C

Included

A, D

22,000 A 2

#4 2 50

9

Both

No

QO130M200C

Included

A, D

22,000 A 2

#4 2 50

9

Both

No

QO13040M200C

Included

A, D

22,000 A 2

#4 2 50

9

Both

No

QO140M200C

Included

A, D

22,000 A 2

#4 2 50

10

Both

No

10,000 A

#14 4

1NM

Bottom

No

Non-Metallic 1-Phase, 3-Wire, 120/240 Vac – Main Lugs Only
60

QO24L60NRNM

Included

B, C

Riser , 1-Phase, 3-Wire, 120/240 Vac – Factory-Installed Main Lugs – Offset Interior Wide Gutter QOM1/QOM2 4 Main Frame Size – Convertible to Main Circuit Breaker – Copper Bus 3

125

200

QO11224L125WG
QO12030L125WG
QO13040L200WG

QOC20UFWG

QOC30UFW

B, C

65,000 A 2

#4 2 /0

14

Both

B

65,000 A 2

#4 2 /0

14

Both

B, C

65,000 A

#4 2 50

23

Both

Yes

Yes

Generator Panel, 1-Phase, 3-Wire, 120/240 Vac – Factory-Installed Main Circuit Breakers with Mechanical Interlock
30

QO48M30DSGP

60

QO48M60DSGP

Included

No

10,000 A

#14 8

4

Bottom

A

10,000 A

#8 2

4

Bottom

No

Generator Panel - Use with Automatic Transfer Switch, 1-Phase, 3-Wire, 120 / 240 Vac, Factory- / Field-Installed Main Circuit Breaker –
22,000 RMS Sym. Amperes Short Circuit Current Rating 5
150

QO13842MX150

A

22,000 A

#4-250

12

Both

No

200

QO13842MX200

A

22,000 A

#4-250

12

Both

No

225
150
200
1
2
3
4
5
6

A
B
C
D

QO13842MX225

QOC38MXUF

QO13842UX225

A

22,000 A

#4-250

12

Both

No

B

22,000 A

#4-250

12

Both

No

QO11428MX150FTRB6

Included

A

22,000 A

#4-250

7R

Both

No

QO11428MX200FTRB6

Included

A

22,000 A

#4-250

7R

Both

No

QO11428UX200FTRB6

Included

B

22,000 A

#4-250

7R

Both

No

Short circuit current rating depends on lowest AIR rating of main or branch circuit breaker installed.
22,000 A rms symmetrical maximum when supplied by integral type QOM-VH main circuit breaker from Square D® with 22,000 A rms symmetrical minimum interrupting rating
and when all installed QO® branch circuit breakers have 10,000 A rms symmetrical minimum interrupting rating.
UL Listed for 5000 A rms symmetrical short circuit rating when used in 3-phase, 240 Vac, corner grounded Delta systems, when used as main lugs load center only. Use QOH 240 Vac circuit breakers only.
QOM2 Load Center is ONLY convertible to main circuit breaker when used with QOC cover.
One main circuit breaker is included with panel. Alternate source main circuit breaker (QO 125 A max.) must be ordered separately. Automatic transfer switch and generator kit
for secondary power sources are ordered through a Kohler® authorized dealer or contractor.
Side-hinge door device allow 1.25 in. (32mm) on the left side for the door to open.
UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with factory-installed service disconnect.
UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and when not
used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch Circuit Panelboard.
UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs and not more than six service disconnecting means
are provided and when not used as a lighting and appliance branch circuit panelboard. See NEC Article for Lighting and Appliance Branch Circuit Panelboard.

03/2007

© 2007 Schneider Electric All Rights Reserved

25

QO® Circuit Breaker Load Centers—Class 1130

Indoor Dimensions
W

Indoor Dimensions

H

D

Box
No.

in.

mm

in.

mm

in.

mm

1

3.81

97

6.72

171

3.00

76

2

4.81

122

9.30

236

3.19

3

4.81

122

9.30

236

3.19

4

8.88

226

12.57

319

5

14.25

362

14.92

6

14.25

362

17.92

7

14.25

362

8

14.25

362

9

14.25

10
11
12

W

Box
No.

H

A

D

in.

mm

in.

mm

in.

mm

13

5.88

149

13.12

333

3.38

86

81

14

14.25

362

20.92

531

3.75

95

81

15

20.00

508

50.00

1270

5.75

146

3.80

97

16

20.00

508

68.00

1727

5.75

146

379

3.75

95

17

20.00

508

53.00

1346

5.75

146

455

3.75

95

18

5.88

149

16.12

409

3.38

86

20.92

531

3.75

95

19

7.56

192

23.12

587

4.25

108

26.04

661

3.75

95

20

9.62

244

26.12

663

4.75

121

362

29.86

758

3.75

95

21

8.88

226

14.80

376

3.80

97

14.25

362

33.78

858

3.75

95

22

8.55

217

23.92

608

3.95

100

14.25

362

37.98

965

3.75

95

23

14.25

362

29.86

758

3.75

95

14.25

362

39.37

1000

3.75

95

A,
B,
C

A

Box 1

Symbol

A

B

C

D

E

F

G

H

I

0.50 in.
13 mm

0.75 in.
19 mm

1.00 in.
25 mm

1.25 in.
32 mm

1.50 in.
38 mm

2.00 in.
51 mm

2.50 in.
64 mm

3.00 in.
76 mm

3.50 in.
89 mm

B, C, D, E

C, D,
B, C,
E, F, G
A A, B
D, E
C, D,
B, C,
E, F
D, E

A,
B, C, D, E
B, C,B A
B, C, D, E
D, E

A, B
A

A
B, C,
D, E

B, C, D, E
B, C, D, E

Box 5

A, B,
C, D

A, B
A
A

A

A

Box 3

C, D, E,
B, C, D, E F,G
A A, B
C, D, E,
C, D, E,
C, D, E, F
B, C, D, E
B, C, D, E F,G
A A, B
D, E, F, G
F,G
D, E, F, G
A A, B
B, C, D,E
C, D, E,
C, D, E, F
B, C, D, E
A A, B
B, C, D, E F,G
D,
E,
B, C
D, E, F, G
C, D, E, F
F, G
B, C, D, E
C, D, E, F
B, C
A, B
A, B

A, B

A

Box 2

Box 4

Conduit
Size

C, D, E, F

A, B

A

Knockouts

C, D, E,
B, C, D, E F,G
A A, B

A, B, C, D
A, B, C

A, B,
C A

A, B, C
A

A, B, C, D

A, B, C, D

Box 6

B, C, D, E

Box 7

D, E,
F, G

A, B, C, D

Box 8

C, D, E,
B, C, C, D, E,
C, D, D, E F, G A
A A, B
B, C, D, E F, G
A, B
E, F
C, D, E, F
D, E,
B, C, D, E B, C, D, E
D, E, F, G
C, D, E, F
F, G
D, E, F, GD, E, F, G
A, B, C, D
B,
C
B, C

B, C, D, E

A, B, C, D
C, D, E, F

Box 9

D, E,
F, G

A, B, C, D,
C, D, E, F

Box 10

D, E, F,
A, B, C D, E, F, G
A, B G, H
A, B
A
C, D, E, F C, D, E, F

D, E, F, G, H, I

A, B

A, B

A, B
A

A

A
A, B, C, D
B, C, D, E

Box 14

Box 13
A, B, C, D C, D, E, F

D, E, F, G

Box 11
A, B, C, D

A, B, C, D
B, C, D, E

C, D, E, F

Box 12
C, D, E, F
D, E, F, G

C, D, E, F
D, E, F, G

Box 15, 16, 17
E, F, G, H
A, B A B, C, D, E
B, C, D, E
B, C, D, E

C, D, E, F
D, E, F, G

A, B, C D, E, F, G
A
A, B
B, C, D, E
D, E, F, G

B, C
A, B

A, B

A

C, D, E, F
B, C, D, E

B, C, D, E

A

B, C, D, E

Box 18

Box 19

Box 20

Box 21

Box 22
D, E, F, G

Box 23

26

© 2007 Schneider Electric All Rights Reserved

A, B, C, D
C, D, E, F

03/2007

QO® and Homeline® Load Centers and Enclosures
Outdoor Dimensions and Knockouts

OUTDOOR DIMENSIONS AND KNOCKOUTS

2.5 in. (64 mm)
Hub Max.

Outdoor Dimensions

2.5 in. (64 mm)
Hub Max.

W

H

D

Box No.

Box 1NM

Box 1R

Box 2R

2.5 in. (64 mm)
Hub Max.

2.5 in. (64 mm)
Hub Max.

C, D, E F, G

C, D,
C, D, E, F
E, F A A, C, D, A, B, C
B E, F,
G

C, D, E F

C, D, E
F, G

C
A A, C, D,A,EB,
F, G
B

Box 3R, 4R

Box 5R
1

2.5 in. (64 mm)
Hub Max.

in.

mm

in.

mm

1NM

6.52

166

8.79

223

3.90

99

1R1

4.88

124

9.38

238

4.00

102

2R

8.88

226

12.65

321

4.27

108

3R

14.75

375

18.92

481

4.52

115

4R

14.75

375

22.06

560

4.52

115

5R

14.75

375

26.04

661

4.52

115

6R

14.75

375

29.86

758

4.52

115

7R

14.75

375

33.78

858

4.52

115

8R

14.75

375

37.98

965

4.52

115

9R

4.56

116

6.50

165

3.88

99

10R

6.92

176

13.18

335

4.12

105

11R

7.56

192

192

590

4.75

121

12R

9.62

244

26.24

666

5.50

140

13R

6.92

176

16.18

411

4.12

105

14R

14.75

375

39.37

1000

4.52

115

15R

8.88

226

14.80

376

4.27

108

16R

8.55

217

24.75

629

4.16

106

LOAD CENTERS

A
B, C, D, E
B, C,
A, B
A
D, E
B, C, D, E A, B

A, B, C, D

mm

1

A, B, C

in.

HOME250SPA top endwall has no hub opening.

Knockouts
Symbol
Conduit
Size

A

B

C

D

E

F

G

H

0.50 in. 0.75 in. 1.00 in. 1.25 in. 1.50 in. 2.00 in. 2.50 in. 3.00 in.
13 mm 19 mm 25 mm 32 mm 38 mm 51 mm 64 mm 76 mm

C, D, E, F, G
A, B, C
C, D,
E, F

Box 9R

C, D, E, F
A, B, C
A A, BC, D,
E, F, G

2.5 in. (64 mm)
Hub Max.

Box 6R, 7R, 8R

2.5 in. (64 mm)
Hub Max.

C, D,
B, C, D, E
E, F A, B,
B, C, D, E
C, D
Box 10R, 13R

2.5 in. (64 mm)
Hub Max.

2.5 in. (64 mm)
Hub Max.

2.5 in. (64 mm)
Hub Max.

A, B

C, D, E, F, G
B, C, D, EA

B, C, D, E C, D,
B, C, D, E A, B
E, F

D, E, F, G
E, F, G, H

D, E,
F, G
Box 11R

2.5 in. (64 mm)
Hub Max.

E, F
Box 12R

C, D, E, F
C, D, E, F
B, C
A A, B C, D,A,
E, F, G

Box 15R

Box 16R

Box 14R

03/2007

© 2007 Schneider Electric All Rights Reserved

27

QO® Circuit Breaker Load Centers—Class 1130
QO Single-Phase Labels
QO SINGLE-PHASE LABELS
The labels below represent typical labels. Information may not be applicable or may change without notice. See the actual label in
the load center for the latest information.
QO Single-Phase Box Label Sample

Number of circuits maximum.
Enclosure catalog number.
Catalog number of covers; flush
or surface.
See panelboard interior for the
catalog number.
Voltage ratings.
Amperage rating.
QO® LOAD CENTER
See Panelboard interior for Catalog No.
Box Cat. No. / Caja No. de Catalogo:
BX18C
Use Cover Cat. No. /
Utilice la Cubierta No. de Catalogo:
QOC16US or/or QOC16UF
Mains 125A max.
Lina principal de 125A maximo.
See main or service disconnect
rating if installed.
240 V ~ Max. 1Ø, 50 / 60 Hz.
24 circuit max. / 24 circuitos maximo.
Type 1 Enclosure
Gabinete Tipo 1
For installation, repairs or alterations,
Call an electrical contractor or electrician.

Short circuit ratings.
Short circuit ratings and additional of
replacement circuit breakers.

Wire range for lug torque data table.

LUG TORQUE DATA

UL Listing.
Underwriter’s
Laboratories, Inc.®

SHORT CIRCUIT RATING

See circuit breakers and field installed
units for wire binding screw torque

RMS Symmetrical Amperes at 120 / 240 V ~ Maximum

Wire Range (AWG/kcmil)

Torque (in/lbs.)

Line Neutral
Lug

Panel
Rating

4 - 2/0 CU/AL

50

*65,000

Main Lug

6 - 2/0 CU/AL

50

*42,000

Alternate
Main Breaker

See Main
Breaker

See Main
Breaker

*22,000

----

Lugs

22,000 / OQ.VH

*10,000

----

Lugs

10,000 / OO, QOT & Q1

Integral
Main

Branch (min.)/
Cat. prefix

----

Lugs

65,000 / QH

----

Lugs

42,000 / QOH

**5,000

----

Lugs

5,000 / QO...H (2 pole)

Torque (in./lbs.)

Bar with 1

100,000

--100-200A,300V T Fuse

Lugs

10,000 / QO & QOT

screw size

42,0000

QOH

Lugs

10,000 / QO & QOT

22,000

Q2...H, KD, QO...VH

65,000

KG

Lugs

10,000 / QO & QOT

22,000

----

QOM...VH

10,000 / QO, QOT & Q1

1/0 - 3 CU / AL

Large 50

Small

4 CU / AL

Large 45

Small

35

6 CU / AL

Large 45

Small 25

35

8 CU / AL

Large 40

Small 10

25

10-14 CU, 10-12 AL

Large 35

Small 10
35

Two 10 AL

35

10

10,000 / QO & QOT

** 240 v ~ 3Ph. 3W. Grounded B” phase requires 240 V ~ branch
breakers.
* The rating is equal to the lowest interrupting rating of any circuit breaker
installed. Refer to branch breaker for individual ratings. Additional or
replacement branch circuit breakers, main breaker, or service disconnect
MUST have an interrupting rating equal to or greater than that of the
circuit breaker with the lowest interrupting rating presently installed.
See panelboard interior for breaker types.

20

Equipment Ground Combinations

Two 14 or 12 CU, Two 12 AL

Lugs

25
25

LISTED
Electric
Cabinet Box
Issue No. V-2813

®

Bar with 2 screw sizes

Branch Neutral and Equipment Ground Bar
Wire Range (AWG)

Remote
Main

Install loose label with Spanish translation
on back of cover.
Adhiera la etiqueta suelta con las traducciones
~
en espanol en la parte posterior del frente.
Please read information before installing
Por favor lea la informacion antes de instalar.
/

001021

15

40265-381-03

QO Single-Phase Wiring Diagram Sample

Line / Linea
N

O

1

O

N
N

3

2
N

O

O
4

4.

Main Breaker diagram

28

N

Service ground
when required. /
Tierra de acometida
cuando fuese
necesario

3.

© 2007 Schneider Electric All Rights Reserved

LOAD / CARGAS

* Suitable for use as service equipment when
service disconnect (main breaker) is installed.
* Suitable for use as service equipment when
not more than six main disconnecting means
are provided and when not used as a lighting
and appliance branch circuit panelboard.
See Article 384-14 of the NEC.
* When used as service equipment, all unused
neutral terminals may be used for terminating
equipment ground wires.

1. Box bonding when required. / Conexion a la caja
cuando fuese necesario.
2. Main breaker type: QOM1 or QOM1A. / Interruptor
automatico principal tipo: QOM1 o QOM1A.

LOAD / CARGAS

Suitable for use with 75oC
Copper or Aluminum
main conductors. See
branch breakers for
branch wire ratings.

Installation of back-fed main circuit breaker and
Type of circuit breakers
required kit.
from Square D that
Alternate wiring diagram for main circuit breaker or
may be used in this
main lug.
panelboard.

LOAD / CARGAS

Service Equipment marking.
Use of unused neutral branch terminal for
equipment grounding, service equipment
application only.

Main Lugs diagram

Main lugs kit no:
QOL125. / No. de
accesorio de las
zapatas
principales:
QOL125.

Two single poles. One plug
on space or may use one
single pole. One two pole
requires two spaces.
Torque Note: When main
breaker or main lug
connector mounting nuts
are loosened or removed,
retighten to 75 lbs./in.
torque.
Equipment Grounding
Terminals

Load center accessories.
Neutral lug for 1/0 AWG or larger wire.
Load Center Accessories - Kits
PK4MB2LA
Back-fed Main Cir. Brkr. Retaining
QO2175SB
Plug-0n Surge Arrestor *
SDSA1175
1 Phase Surge Arrestor
QOSAMK
SDSA1175 Mounting Bracket
QOL2125
1 Phase Plug-on Subfeed Lugs *
PK9--27GTA(L) Equipment Ground Bar
PKGTAB
Equipment Ground Bar Insulator
LK70AN
70A Max. Neutral Lug
LK100AN
125A Max. Neutral Lug
QOL125
Main Lugs
PK6FL
Indoor Cover Lock
* May plug on two adjacent spaces.
Torque Note: When interior mounting screw is
loosened or removed, retighten to 35 lbs./in.

Made in U.S.A.

15

40265-668-02

03/2007

QO® and Homeline® Load Centers and Enclosures
QO Three-Phase Label Samples
QO THREE-PHASE LABEL SAMPLES
The labels below represent typical labels. Information may not be applicable or may change without notice. See the actual label in
the load center for the latest information.
QO Three-Phase Box Label Sample

Number of circuits maximum.
Enclosure catalog number.
Catalog number of covers; flush
or surface.
See panelboard interior for the
catalog number.
Voltage ratings.
Amperage rating.
QO® LOAD CENTER

See Panelboard interior for Catalog No.
Box Cat. No. / Caja No. de Catalogo:
BX338C
Use Cover Cat. No. /
Utilice la Cubierta No. de Catalogo:
QOC42US or/or QOC42UF
Mains 225A / Lina principal de
225A maximo.
See main or service disconnect
rating if installed.
240 V ~ Max. 3Ø, 50 / 60 Hz.
42 circuit max. / 42 circuitos maximo.
Type 1 Enclosure
Gabinete Tipo 1

Short circuit ratings.
Short circuit ratings and additional of
replacement circuit breakers.

Wire range for lug torque data table.

UL Listing.

SHORT CIRCUIT RATING

LUG TORQUE DATA

Panel
Rating

Remote
Main

Integral
Main

Branch (min.)/
Cat. prefix

Wire Range (AWG/kcmil)

Torque (in/lbs.)

Line Neutral
Lug

*65,000

----

Lugs

65,000 / QH

4 - 300 CU/AL

250

*42,000

----

Lugs

42,000 / QOH

Main Lug

4 - 300 CU/AL

250

Alternate
Main Breaker

See Main
Breaker

See Main
Breaker

Branch Neutral and Equipment Ground Bar
Wire Range (AWG)

Torque (in./lbs.)

Bar with 1

Bar with 2 screw sizes

screw size

1/0 - 3 CU / AL

Large 50

Small

4 CU / AL

Large 45

Small

6 CU / AL

Large 45

Small 25

Underwriter’s
Laboratories, Inc.®

RMS Symmetrical Amperes at 120 / 240 V ~ Maximum

See circuit breakers and field installed
units for wire binding screw torque

35
35

8 CU / AL
Large 40
Small 10
240V, 3PH, 3W: For this system neutral is not
used and only breakers rated 240V are to be used. 10-14 CU, 10-12 AL
Large 35
Small 10
240V, 3PH, 4W: When wired for delta system,
Equipment Ground Combinations
phase “B” must be 208V to neutral. Breaker
Two 14 or 12 CU, Two 12 AL
35
10
poles connected to phase “B” must be rated 240V.
Two 10 AL
35
1PH: Single pole breakers can not be connected
to phase B.

25
20
25
25

*22,000

----

Lugs

22,000 / OQ.VH

*10,000

----

Lugs

10,000 / OO&Q1,QO...H

**5,000

----

Lugs

5,000 / QO...H(2 POLE)

100,000

100-200A,300V T Fuse

Lugs

10,000 / QO

22,000

KD, QO...VH

Lugs

10,000 / QO
10,000 / QO (10A-60A)

22,000

Q2...H

Lugs

65,000

KG

Lugs

65,000

----

KG

10,000 QO&Q1

22,000

----

KD

10,000 QO&Q1

22,000

----

QO...VH

10,000 / QO

10,000 / QO

** 240 v ~ 3Ph. 3W. Grounded “B” phase requires 240 V ~ branch
breakers.
* The rating is equal to the lowest interrupting rating of any circuit breaker
installed. Refer to branch breaker for individual ratings. Additional or
replacement branch circuit breakers, main breaker, or service disconnect
MUST have an interrupting rating equal to or greater than that of the
circuit breaker with the lowest interrupting rating presently installed.
See panelboard interior for breaker types.

®

LISTED
Electric
Cabinet Box
Issue No. V-2813

For installation, repairs or alterations,
Call an electrical contractor or electrician.
Install loose label with Spanish translation
on back of cover.
Adhiera la etiqueta sauelat con la traduccion
~ en la parte posterior de la cubierta.
en Espanol
Please read information before installing.
Por favor lea la informacion antes de instalor.
/

001021

15

40265-381-03

QO Three-Phase Wiring Diagram Sample

Service Equipment marking.
Use of unused neutral branch
terminal for equipment grounding,
service equipment application only.

Alternate wiring diagram for main circuit breaker or
main lug.
Installation of back-fed main circuit breaker and
required kit.

Suitable for use with 75oC
Copper or Aluminum
main conductors. See
branch breakers for
branch wire ratings.

03/2007

/

OOO

6.
Line /
Linea

2

4

Line / Linea
N

O
O
O
5. Line /
Linea
Load /
Cargas

N

N
3

OOO

N
1

/

Load /
Cargas

* Suitable for use as service equipment when
service disconnect (main breaker) is installed.
* Suitable for use as service equipment when
not more than six main disconnecting means
are provided and when not used as a lighting
and appliance branch circuit panelboard.
See Article 384-14 of the NEC.
* When used as service equipment, all unused
neutral terminals may be used for terminating
equipment ground wires.

1. Box bonding when required. /
Conexion a la caja cuando fuese
necesario.
2. Service ground when required. /
Tierra de acometida cuando fuese
necesario
3. Main lugs kit no: QOL3225. / No.
de accesorio de las zapatas principales:
QOL3225.
4. Lug kit when installed. / Accesorio
de la zapata, cuando se instala.
5. Back fed main circuit breaker
when installed. / Interruptor
~
automatico
principal de alimentacion
posterior, cuando se instala.
6. Integral main circuit breaker when
~
installed. / Interruptor automatico
integral principal, cuando se instala.

Type of circuit breakers
from Square D that
may be used in this
panelboard.

Load center accessories.
Neutral lug for 1/0 AWG or larger wire.

Load Center Accessories - Kits
PK3MB
Back-fed Main Cir. Brkr. Retaining
SDSA3650
3 Phase Surge Arrestor
QO60SL
1 Phase Plug-on Subfeed Lugs *
QO2125SL
1 Phase Plug-on Subfeed Lugs *
QO3125SL
3 Phase Plug-on Subfeed Lugs +
PK9-27GTA(L) Equipment Ground Bar
One single pole. One plug
PKGTAB
Equipment Ground Bar Insulator
on space. One two pole
LK100AN
125A Max. Neutral Lug
requires two plug on
LK150AN
150A Max. Neutral Lug
spaces. One three pole
QOL3225
Main Lugs
requires three plug on spaces. PK6FL
Indoor Cover Lock
Torque Note: When main
* May plug on two adjacent spaces.
breaker or main lug
+ May plug on three adjacent spaces.
connector mounting nuts
Torque Note: When interior or main breaker
are loosened or removed,
mounting screws are loosened or removed,
retighten to 75 lbs./in.
retighten to 35 lbs./in.
torque.
Equipment Grounding
Terminals
Made in U.S.A.
40265-545-01
15

© 2007 Schneider Electric All Rights Reserved

29

QO® Circuit Breaker Load Centers—Class 1130
Wiring Diagrams
WIRING DIAGRAMS
G/B
S
N

S
N

QO2L30S
QO2L40RB

G/B

S
N

S
N

G
B

QO2L30TTS

S
N

QO24L70F/S
QO24L70RB

QO24L60NRNM

S/N

QO24L70TS

S
N

S/N
S/N

S
N

G
B

S
N

QO612L100F/S
QO612L100DF/S
QO612L100DFCU/SCU
QO612L100RB
QO612L100RBCU

Line

QO816L100TF/S
QO816L100DTF/S

S
N

S
N

QO24L50TTS
S
N

S
N

S
N

S/N

G
B

QO816L100F/S
QO816L100DF/S
QO816L100DFCU/SCU
QO816L100RB
QO816L100RBCU

G
B

QO35FM30TTF/S

QO12030L150G

QO120L125G
QO120L125GC

S
N

S
N

S
N

S
N

S
N
S/N
S/N

G
B

QO12436L200TFT

QO112L125G
QO112L125GC
QO112L125GRB
QO112L200G
QO112L200GRB

QO12024L125G
QO12030L125WG

QO132L125G

G
B

QO612L100TF/S
QO612L100DTF/S
QO612L100TRB

QO148L125GF/S
QO148L125GRB

S/N

S/N
S
N

S/N

S
N

S
N

QO11224L125G
QO11224L125GRB
QO11224L125WG
QO11224L125GC

QON12LS400

QON30LS400

QON42LS400

S
N
S
N

S
N

S
N

S
N

S
N

S
N

S
N

S
N

S
N

S
N

S
N

QO11624L125G
QO11624L125GRB

QO116L125G

S
N

S
N

S
N

G
B

QO124L125G
QO124L150G
QO124L125GRB

QO130L150G
QO130L200G
QO130L150GRB
QO130L200GRB

QO130L150TC

QO13040L200G
QO13040L200GRB
QO13040L200GC
QO13040L200WG

QO140L200G
QO140L200GRB

QO142L225G
QO142L225GRB

1-Phase, 3-Wire Main Lugs
30

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
Wiring Diagrams

S
N

S
N

MAIN

MAIN

S
N

S
N

S
N

MAIN

S
N

S
N

MAIN

S
N

MAIN

S
N

S
N

S
N

S
F

S
N

MAIN

QO112M100
QO112M100RB
QO112M100C

QO1816M150FTRB
QO1816M200FTRB

QO1612M125FTRB

S
N

S
N

MAIN

QO116M100
QO116M100RB
QO116M100C

S
N

S
N

MAIN

QO1428MX150FTRB
QO1428MX200FTRB

QO1428UX200FTRB

S
N
S
N

QO120M100
QO120M100RB
QO120M100C

QO12030M150
QO12030M150RB
QO12030M150C

S
N
S
N

MAIN

MAIN

S
N

S
N

S
N

QO130M150
QO130M200
QO130M150RB
QO130M150C
QO130M200C
QO130M200RB

S
N

S
N

S
N

MAIN

MAIN

S
N

S
N

QO13040M200
QO13040M200C

S
N

S
N

MAIN

MAIN

S
N

QO132M100
QO132M125
QO132M150

S/N

S
N

S
N

QO11220M100C

QO12040M200
QO12040M200RB
QO12040M200C

S
N

QO124M125
QO124M125RB
QO124M150
QO124M200
QO124M100

S
N

MAIN

MAIN

S/N

Main Main

QO48M30DSGP
QO48M60DSGP

QO13842MX150
QO13842MX200
QO13842MX225

QO13842UX225

QO140M200
QO140M225
QO140M200RB
QO140M200C

MAIN

QO142M200
QO142M225
QO142M225RB

QON42MS300
QON42MS400

1-Phase, 3-Wire Main Circuit Breakers

03/2007

© 2007 Schneider Electric All Rights Reserved

31

QO® Circuit Breaker Load Centers—Class 1130
Wiring Diagrams

S
N

S
N

S
N

S
N

S
N

S
N

S
N
QO403L60NF/S
QO403L60NRB
QO312L125G
QO312L125GRB
QO320L125G
QO320L125GRB

S
N

S
N

S
N

S
N

S
N

QO318L200G
QO318L200GRB

S
N

QO324L125G
QO330L200G
QO330L200GRB

QO342L225G
QO342L225GRB

3-Phase, 4-Wire Main Lugs

S
N

S
N

MAIN

S
N

S
N

S
N

MAIN

S
N

M
A
I
N

QO327M100
QO327M100RB

QO330MQ125
QO330MQ150
QO330MQ200
QO330MQ125RB
QO330MQ150RB
QO330MQ200RB
QO342MQ150
QO342MQ200
QO342MQ225
QO342MQ200RB
QO342MQ225RB

3-Phase, 4-Wire Main Circuit Breakers

32

© 2007 Schneider Electric All Rights Reserved

03/2007

QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131
Table of Contents
TABLE OF CONTENTS
General Information and Application Data 34
Type 34
Service 34
Ratings 34
Enclosure 34
Type 3R Rainproof 34
Circuit Breakers 35
Knockouts 35
Equipment Grounding Bar 35
Neutral Assemblies 35
Bolt-On Hubs 35

Technical Information 36
Enclosed Molded-Case Circuit Breaker Ratings 36

Dimensions and Knockouts 37
NOTE: For information on Replacement Parts with specific part numbers,
go to www.schneider-electric.us, click on Product FAQ’s, enter the device
catalog number, click SEARCH, then look for the information required.

03/2007

© 2007 Schneider Electric All Rights Reserved

33

QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131
General Information and Application Data
GENERAL INFORMATION AND APPLICATION DATA
Type
Enclosed molded case circuit breakers are UL® Listed; File E136861, for
enclosures and File E10027 for circuit breakers.
Molded case circuit breakers meet Federal Specifications W-C-375-B.
Enclosed molded case switches are UL Listed under File E59921.

Service
120/240 Vac, 1φ3W
240 Vac, 1φ2W
240 Vac, 1φ3W
240/120 Vac, 3φ4W
208Y/120 Vac, 3φ4W

Ratings
QO2100BNS

QO2100BNRB

Enclosed Molded Case Circuit Breakers
QO

10,000 A

QOM2

22,000 A

QB

10,000 A

QD

25,000 A

QG

65,000 A

QJ

65,000 A @ 240 V or 100,000 A @ 208Y / 120

Enclosure
Type 1 indoor general purpose
Welded sheet steel with knockouts at top, bottom, back and sides
Finish: gray baked enamel, electrodeposited over cleaned,
phosphatized steel
Padlock provisions for locking circuit breaker handle in ON (I) or
OFF (O) position
Flush or surface mount covers

Type 3R Rainproof
Welded, galvannealed sheet steel
QOM22225NRB

34

Q22200NS
With Cover Removed
(Order Q-Frame Circuit
Breaker Separately)

© 2007 Schneider Electric All Rights Reserved

Finish: gray baked enamel, electrodeposited over cleaned,
phosphatized, galvannealed steel
Provisions to padlock cover closed
RB devices have provisions for interchangeable bolt-on hubs

03/2007

QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131
General Information and Application Data
Circuit Breakers
Visi-Trip® indication (QO® circuit breakers)
Lugs suitable for aluminum or copper wire
(refer to catalog sections listed below:)

QOM2200VH

QO

Class 730

QB, QD, QG and QJ

Class 734

QOM2

Class 736

Molded-case switches

Class 601

Knockouts
Located in back, side and bottom of all devices

Equipment Grounding Bar
Field-installable PKOGTA2
Suitable for #6 AWG 2/0 aluminum or #10 AWG 2/0 AWG copper wire
Circuit Breakers

Neutral Assemblies
Insulated, groundable (except QO2TR)
Suitable for aluminum or copper wire
Grounding terminal provided

Bolt-On Hubs
Hubs available from 0.75 in. (19 mm) to 2.50 in. (64 mm) conduit size
Off-center thread openings keep conduit close to wall
No gasket required with hubs
Factory-installed equipment grounding bar.

QO Base Assemblies

QOM2 Base

Neutral Assemblies
PKOGTA2 field installed.

Hubs

03/2007

© 2007 Schneider Electric All Rights Reserved

35

QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131
Technical Information
TECHNICAL INFORMATION
Enclosed Molded-Case Circuit Breaker Ratings
Circuit Breaker 1

Enclosure
Service

Rating in
Amperes

Type 1
Catalog
Number

Enclosure
UL® Listed
No.
Catalog Interrupting Rating
(Page 37) Number
in RMS Amps
Symmetrical

Type 3R
Catalog
Number

Neutral Assembly
Terminal Wire Size
AWG/kcmil

Terminal
Lug Wire
Neutral
Size
AWG/kcmil Terminals

Grounding
Terminals

Enclosed Circuit Breaker Mounting Base
G
B

60 A 2

QO2TR 3

1R

QO210 to
QO260

#14 4
Al or Cu 4

10,000 AIR

#14 8
Al or Cu

240 Vac

Enclosed Circuit Breakers

100 A

S
N

125 A

QO2100BNF/S 5

QO2125BNF/S 5

QO2100BNRB 5

QO2125BNRB 5

QO
QO-PL
QO-GFI

10,000 AIR

QO-VH

22,000 AIR

QO
QO-PL
QO-GFI

10,000 AIR

QO-VH

22,000 AIR

6, 6R

QOM2-VH

22,000 AIR

10,000 AIR

1, 2R

QO
QO-PL
QO-GFI
QO-VH

22,000 AIR

QBL
QDL
QGL
QJL

10,000 AIR
25,000 AIR
65,000 AIR
100,000 AIR

QBL
QDL
QGL
QJL

10,000 AIR
25,000 AIR
65,000 AIR
100,000 AIR9

1, 2R

2, 3R

120/240 Vac

100-225 A

S
N

100 A

QOM22225NF/S
6

QO3100BNF/S 5

QOM22225NRB
6

QO3100BNRB 5

240 Vac

S
N
2-pole
240 Vac Max.

S
N

Q22200NS 7 8

Q22200NRB 7 8

3, 4R

100-225 A

100-225 A

Q23225NF/S

8

Q23225NF/S

8

Q23225NRB

8

Q23225NRB

8

4, 5R

4, 5R

3-pole
240 Vac

#12 1 Al
or
#14 1 Cu

#12 1 Al
or
#14 1 Cu

#12 2/ 0 Al
#14 2/0 Cu

#12 2/0 Al
#14 2 /0 Cu

4 - #4 2 50
kcmil Al/Cu

1

Order circuit breaker separately.

2

Not suitable for service equipment.

3

Top endwall has no hub opening; back and bottom feed only.

4

Load terminals use #6 maximum.

5

Enclosures will accept QO circuit breakers with factory-installed accessories.

6

Enclosure will accept QOM2 circuit breaker with factory-installed accessories.

7

Accepts 200 A maximum, 2-pole Q-frame circuit breakers.

8

Equipment grounding kit factory-installed.

9

When these 3-pole circuit breakers are mounted in an enclosure, the maximum AIR rating is 65,000 at 240 Vac and 100,000 at 208 Vac.

36

© 2007 Schneider Electric All Rights Reserved

#12 1 Al
or
#14 1 Cu

2 - #4 25 0
kcmil
4 - #14 2/ 0
Al or Cu
#12 1 Al
or
#14 1 Cu

#12 2 Al
or
#14 2 Cu

2 - #6 2 /0 Al
2 - #10 2/0 Cu

#12 2 Al
or
#14 2 Cu

#4 2 50
Al or Cu

#4 300
Al or Cu

#4 3 00
Al or Cu

#12 1/ 0 Al
or
#14 1/0 Cu

#4 3 00
Al or Cu

03/2007

QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131
Dimensions and Knockouts
DIMENSIONS AND KNOCKOUTS
Dimensions
W

Enclosure No.

H

D

in.

mm

in.

mm

in.

mm

1

5.88

149

13.12

333

3.38

86

2

5.88

149

16.12

409

3.38

86

1R

4.56

116

6.50

165

3.88

99

2R

6.92

176

13.12

333

4.12

105

3R

6.92

176

16.12

409

4.12

105

3

7.56

192

23.12

587

4.25

108

4

9.62

244

26.12

663

4.75

121

4R

7.56

192

23.24

590

4.75

121

5R

9.62

244

26.24

666

5.50

140

6

8.55

217

23.92

608

3.95

100

6R

8.55

217

24.75

629

4.16

106

Knockouts
A

Symbol
Conduit Size

B

C

D

E

F

0.50 in.

0.75 in.

1.00 in.

1.25 in.

1.50 in.

2.00 in.

G
2.50 in.

H
3.00 in.

13 mm

19 mm

25 mm

32 mm

38 mm

51 mm

64 mm

76 mm

D, E, F, G

2-1/2 in.
Hub Max.

C,D,E,F
A,B,C,D
A,B

C,D,E,F

A,B,C

Box 1R

Box 1, 2

E,F,G,H
C,D,E,F
D,E,F,G

B,C,D,E

Box 2R, 3R

Box 3

2-1/2 in.
Hub Max.

2-1/2 in.
Hub Max.

A,B,C,D

2-1/2 in.
Hub Max.

C,D,E,F
A,B

A,B
D,E,F,G

Box 4

A,B

D,E,F,G
E,F,G,H

Box 4R

C,D,E,F

C,D,E,F

C,D,E,F

Box 5R

Box 6

Box 6R

Outdoor Dimensions and Knockouts

03/2007

© 2007 Schneider Electric All Rights Reserved

37

QO®, QOM2 and Q-Frame Enclosed Circuit Breakers—Class 1131
Dimensions and Knockouts

38

© 2007 Schneider Electric All Rights Reserved

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
Table of Contents
TABLE OF CONTENTS
Product Description 40
Features 40
Homeline® Catalog Number Description 41

General Information and Application Data 42
Type 42
Service 42
Ratings 42
UL Listed 42
Class CTL 42
Branch Circuit Breakers 42
Main Circuit Breaker QOM-VH 42
Indoor Enclosures (NEMA Type 1) 43
Indoor Covers 43
Rainproof Enclosures (NEMA Type 3R) 43
Bolt-On Hubs 43
Single-Phase, 2 12 Circuits, 70 125 A, Fixed Mains 44
Single-Phase, 12 4 2 Circuits, 100 2 25 A, Convertible Mains 44
Surgebreaker® Secondary Surge Arrester 46
Accessories 46

Technical Information 48
Grounding Bar Kits 48
Wire Range Table 48
Main Lugs and Main Circuit Breakers Ratings 49

Dimensions and Knockouts 26-28
Homeline® Label Samples 52
Wiring Diagrams 53
INDEX 55

03/2007

© 2007 Schneider Electric All Rights Reserved

39

Homeline® Circuit Breakers and Load Centers—Class 1170
Product Description
PRODUCT DESCRIPTION
Homeline® circuit breaker load centers from Square D® are UL Listed
panelboards. They are designed to meet residential, commercial, and
industrial requirements to protect electrical systems, equipment, and people.

Features
Single-phase construction
30 2 25 A main lug or main circuit breaker ratings
2 42 circuit indoor or outdoor versions
Combination cover for flush or surface mounting
Aluminum bus construction on main lug or main circuit breaker panels
Service entrance equipment capable panels
Straight-in wiring to help minimize service cable installation
Convertible mains meet changing job site requirements
Standard 22/10 k AIR series rating on main circuit breaker panels
increases application capability
Single captive screw interior mounting on indoor panels to ease removal
Split branch neutral for clutter-free wiring
Top or bottom feed by rotating convertible mains panels 180 degrees
®

Homeline Circuit Breaker Load Center

Combination slot/square drive neutral, ground, and cover screws for
positive drive and improved torque
Three ground bar mounting locations for ease of wiring
Automatic flush adjustment cover speeds installation
Tangential main service knockouts eliminate offsets
Equipment grounding bar included with main lug load centers
Cover supplied with load center
Provisions for door lock on convertible mains panel covers
Two branch circuit breaker twistouts are factory removed for easier
installation of circuit breakers
New side hinge doors on outdoor convertible main panels
Outdoor panel covers are lockable with padlock

40

© 2007 Schneider Electric All Rights Reserved

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
Product Description
Homeline® Load Centers
Number Segment

Character

Description

Load Center Family

HOM

UL Listed

Spaces / Circuits

3040
M

Main circuit breaker

Mains Type

L

Main lugs

U

Universal mains

HOM

3040

L

200

—

C

Amps
Ground Bar
Special Construction

Cover

G

Factory included

T

Factory-installed

Blank

Purchase separately

FT

Feed-thru

C

Combination flush / surface indoor cover

F

Flush

RB

Rainproof

S

Surface

Homeline® Circuit Breakers
Number Segment
Brand

Character Description

HOM

1

HOM

Full Size

HOMT

Tandem

AFI

Arc fault circuit interruption

Blank

10,000 AIR

CAFI

Combination arc fault circuit interruption

EPD

Equipment protection device

GFI

Ground fault circuit interruption

HM

High magnetic trip

15

—

Number of Poles
Amps

Device Name

03/2007

© 2007 Schneider Electric All Rights Reserved

41

Homeline® Circuit Breakers and Load Centers—Class 1170
General Information and Application Data
GENERAL INFORMATION AND APPLICATION DATA
Type
Circuit breaker load centers for use on ac systems. They are UL Listed
under file E-6294 (panelboards) and meet Federal Specifications W-P-115b
NEMA Type 1, Class 2.

Service
120 Vac, 1φ2W
120/240 Vac, 1φ3W

Ratings
Main lugs: 70 2 25 A
Main circuit breaker: 50 2 25 A
HOM24M125C

UL Listed
File E-6294 (panelboards)
Suitable for use as service equipment
75 °C wire rating

Class CTL
UL Listed Class CTL load centers

Meets the National Electrical Code® (NEC®) article for Lighting and
Appliance Branch Circuit panelboards.
HOM 1-Pole
1 space required.

HOM 2-Pole
2 spaces required.

Branch Circuit Breakers
10,000 AIR
1-pole, 15 5 0 A

HOM

2-pole, 15 1 25 A
1-pole, 15 3 0 A

HOMT

2-pole, 15 5 0 A
1-pole, 15 2 0 A

HOM-GFI

HOMT 1-Pole Tandem
1 space required.

HOMT Quad Circuit Breaker
2 spaces required.

2-pole, 15, 20, 30, 40, 50 A

HOM-AFI

1-pole, 15 2 0 A

HOM-CAFI

1-pole, 15 2 0 A

Main Circuit Breaker Kits
50 225 A main circuit breaker kit is 22,000 AIR series rated with
10,000 AIR branch circuit breakers
Refer to Main Circuit Breaker Kits on page 10 for listing.

HOM 1-Pole GFI
with ground fault
circuit interrupter;
1 space required.

42

HOM 2-Pole GFI
with ground fault
circuit interrupter;
2 space required.

© 2007 Schneider Electric All Rights Reserved

QOM2 Frame Size
100–225 A
HOM-AFI
1 space required.

QOM1 Frame Size
50–125 A

HOM-CAFI
1 space required.

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
General Information and Application Data
Indoor Enclosures (NEMA Type 1)
Welded sheet steel with knockouts at top, bottom, back and sides
Finish: gray baked enamel electrodeposited over cleaned, phosphatized
steel
Most indoor enclosures are 14.25 in (362 mm) wide
Top or bottom feed by rotating enclosure

Indoor Covers
Doors to cover circuit breaker handles, except on 2 4 , 4 8 and 6 1 2
circuit models
Combination flush and surface cover with latch opening door included
with load centers
Automatic flush adjustment is standard
Triple lead cover screws for fast cover installation
Shutter-type twistouts
HOMFP snap-in style filler plates available for all covers
HOM40M200C With Cover

QOM1FP filler plates available for 100 12 5 A convertible load center
covers
QOM2FP filler plates available for 150 22 5 A convertible load center
covers

Rainproof Enclosures (NEMA Type 3R)
Complete enclosure includes interior trim and door
Welded galvannealed steel
Finish: gray baked enamel electrodeposited over cleaned,
phosphatized, galvannealed steel
RB devices have provisions for interchangeable bolt-on hub
Top centered rainproof mounting boss on the back of the enclosure
simplifies installation and saves time
Stainless steel door latch on the enclosure provides a secure closure
and maximum durability
Convertible main panels are side-hinge door devices
Side-hinged door provides full wiring access without door removal
Allow 1.25 in (32 mm) on the left side for the door to open
New RB Device

Bolt-On Hubs
Hubs available for 0.75 in (19 mm) to 4 in (102 mm) conduit size (see
page 46)
No gasket required with hubs from 0.75 in (19 mm) to 2.50 in (64 mm)
when used on RB type load centers

Bolt-On Hubs

03/2007

© 2007 Schneider Electric All Rights Reserved

43

Homeline® Circuit Breakers and Load Centers—Class 1170
General Information and Application Data
Single-Phase, 2–12 Circuits, 70–125 A, Fixed Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 49)
Short Circuit Current Rating
Main lugs: up to 10,000 AIR (see Technical Information on page 49)
Interior
Tin plated aluminum bus
Mains
HOM612L100F

Factory-installed fixed main lugs
Top mains positioning only
Top or bottom feed (see Technical Information on page 49)
A backfed main circuit breaker can be field installed in a 6 12 load
center using the HOM1RK retaining kit
Cover
Combination flush and surface cover

Single-Phase, 12–42 Circuits, 100–225 A, Convertible Mains
UL Listed
File E-6294
Suitable for use as service equipment
75 °C wire rating (see Technical Information on page 48)
Flush Cover

Short Circuit Current Rating
Main lugs: up to 10,000 AIR
Main circuit breaker: 22,000 AIR standard (see Technical Information
on page 48)
Interior
Tin plated aluminum bus
Removable interior with single, captive mounting screw
Split branch neutral with up to 50% more terminations than required
Multiple mounting locations for equipment ground bar kits: left, right, bottom
Mains
Factory-Installed Main Lugs
Convertible to Main Circuit Breaker

Combination Cover with Door

Factory-Installed Main Circuit Breaker
Convertible to Main Lugs

Load Center
Amperage

Main Circuit
Breaker Kit
Amperage

Main Circuit
Breaker
Amperage

Main Lug
Kit
Amperage

Load
Center
Amperage

125
150
200
225

50 - 125
100 - 150
100 - 200
100 - 225

100
125
150
200
225

125
125
225
225
225

100
125
150
200
225

Top or bottom mains positioning, by rotating the complete indoor load center 180 degrees.
(see Technical Information on page 48)

44

© 2007 Schneider Electric All Rights Reserved

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
General Information and Application Data
Single-Phase, 12–42 Circuit, 100–225 A, Convertible Mains,
Continued
Cover
Combination flush and surface cover included with load centers
Optional door lock kit for indoor load centers
Positive action, easy open door latch
Main Circuit Breaker with Feed-Thru Lugs
Rainproof only, side hinged
150 and 200 A mains rating
Space for up to 8 single-pole circuit breakers
Factory-installed main circuit breaker
Factory-installed feed-thru lugs
HOM816M200FTRB

Universal Mains Load Centers, Studs Only
No factory-installed main circuit breaker or main lugs
200 A mains rating
Indicated by a U in the catalog number
Purchase main lug kit or main circuit breaker kit and field install
Combination flush / surface cover included with indoor load center
Factory-installed ground bar kit
Universal Mains Load Center with Feed-Thru Lugs
No factory-installed main circuit breaker or main lugs
200 A mains rating
Feed-thru lugs are factory-installed
Rainproof only, side hinged
Space for up to 8 single-pole circuit breakers
Purchase main lug kit or main circuit breaker kit and field install
HOM816U200FTRB

Main Circuit Breaker Mobile Home Load Centers
Covers included with load centers
Factory-installed grounding bar, indicated by a T in the catalog number
Top or bottom feed on incoming service by rotating the complete load
center 180 degrees

HOM3040U200TC

03/2007

© 2007 Schneider Electric All Rights Reserved

45

Homeline® Circuit Breakers and Load Centers—Class 1170
General Information and Application Data
Accessories
Bolt-On Hubs
Equipment with an RB suffix, meaning Rainproof NEMA Type 3R
construction, uses the bolt-on hubs listed below. RB de vices will accept
0.75 in (19 mm) through 2.50 in (64 mm) bolt-on hubs without the use of
reducers.
Off-center conduit thread openings and elongated mounting holes provide
quick and easy adjustment to eliminate costly conduit offsets and bends.
Hubs are suitable for use with conduit having ANSI standard taper pipe
thread.
UL Listed Bolt-On Hubs for RB Devices
RB Hub

Conduit Size

0.75 in

1.00 in

1.25 in

1.50 in

2.00 in

2.50 in

9 mm

25 mm

32 mm

38 mm

51 mm

64 mm

B075

B100

B125

B150

B200

B250

Hub Cat. No.

NOTE: Closing cap (catalog number B-CAP) is provided factory-installed on each device having
the RB suffix.
BC200 Enclosure Coupling

UL Listed Enclosure Coupling for RB Devices
Cat. No.
BC200

Designed for connecting wireway or other enclosures to units having RB
bolt-on conduit provisions. Provides a bushed opening equal to 2 in conduit.
Eliminates the need for conduit nippling.

Surgebreaker® Secondary Surge Arrester
HOM2175SB UL Listed secondary surge arrester

Easy plug-on installation for Homeline® load center
LED indicates operational status
HOM Surgebreaker®
Surge Arrester
2 spaces required.

Plug-on design requires two pole spaces
Designed to protect electrical service and major household appliances ,
excluding electronic devices
Grounding Bar Kits
Field installable in all load centers
Wire size of terminals (see Technical Information on page 48)
Suitable for copper or aluminum wire

PK15GTA

Available with #1 4/0 AWG lug PK15GTA-L, PK18GTA-L and PK23GTA-L
(see Technical Information on page 48)
Auxiliary Neutral Lugs
UL Listed for copper or aluminum wire

LK100AN

Field installable on neutral assembly
LK70AN: #12 2 Al or #14 4 Cu AWG
LK100AN: #6 2/0 Al/Cu AWG
LK125AN: #14 2/0 Al/Cu AWG

HOMFP
QOM1FP

Cover Filler Plates
Fast to install; snap-in type
HOMFP branch circuit
QOM1FP 50 1 25 A main circuit breaker
QOM2FP 150 225 A main circuit breaker

QOM2FP

46

© 2007 Schneider Electric All Rights Reserved

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
General Information and Application Data
Back-Fed Main Circuit Breaker Retaining Kits
HOM1RK: secures circuit breaker to interior when used as back-fed
main for HOM612L100F/S and RB load centers
HOM4RK2LA: mounts on the right side of HOM 100 125 A convertible
main load centers, series S01 and S02 (retains one 2-pole HOM circuit
breaker)
HOM4RK2HA: mounts on the right side of HOM 150 2 25 A convertible
main load centers, series S01 and S02 (retains one 2-pole HOM circuit
breaker)
Back-Fed Main Circuit Breaker Retaining Kit

Generator Circuit Breaker Interlock Kit
HOMCRBGK1: interlocks a QOM1 2-pole main circuit breaker of a load
center (100 125 A) with a Homeline® 2-pole (15 125 A) branch circuit
breaker, "S" series NEMA Type 1 and "S1" and "S2" series NEMA type 3R
load centers
HOMCGK2: interlocks a QOM2 2-pole main circuit breaker of a load center
(150 225 A) with a Homeline 2-pole (15 125 A) branch circuit breaker, S
series NEMA Type 1 and S01 series NEMA Type 3R load centers
HOMRBGK2: interlocks a QOM2 2-pole main circuit breaker of a load
center (150 225 A) with a Homeline 2-pole (15 125 A) branch circuit
breaker, S02 series NEMA Type 3R load centers

Cutaway Showing Installed Generator Interlock Kit

Flush Lock Kits
Available for indoor load centers
Two keys provided with each lock kit
PK6FL for single-phase convertible 8 42 circuit load centers
Main Lugs Kits

PK6FL

Field installable in main circuit breaker or main lugs load centers
125 A kit usable in 100 125 A load centers, QOL125
225 A kit usable in 150 225 A load centers, QOL225
Main Circuit Breaker Kits

QOL125

Field installable in main lugs or main circuit breaker load centers
50 225 A main circuit breaker kit with 22,000 AIR usable with 10,000
AIR branch circuit breakers (see page 10)

QOL225

03/2007

© 2007 Schneider Electric All Rights Reserved

47

Homeline® Circuit Breakers and Load Centers—Class 1170
Technical Information
TECHNICAL INFORMATION
Grounding Bar Kits
Slot / Robertson screw

All PK equipment grounding bar kits are supplied with mounting screws,
necessary installation instructions and an Equipment Grounding Terminal
self-adhesive label.
Terminals
0.437
[11]

Catalog
Number

Quantity Each Size
See “Wire Range
Table” below.

Total
Qty.
I

0.3125
[8]

in
Dimensions:
[mm]

Cross Section of Size 1 Ground Bar

II

III

IV

V

Distance
Approximate
Between
Overall
Mounting
Mounting
Length
Holes

VI

in

[mm]

in

[mm]

2

1.75

[44]

One
hole

One
hole

Top

4.61

[117]

1.69

[43]

Top

PK0GTA2 1

2

PK0GTA6 2

6

PK3GTA1 3

3

3

1.38

[35]

One
hole

One
hole

Top

PK4GTA 3

4

4

1.63

[41]

One
hole

One
hole

Top

4

5

5

2.25

[57]

1.25

[32]

Top

PK7GTA 3

7

7

2.88

[73]

1.25

[32]

Top
or
Side

PK9GTA1 3

9

9

3.25

[83]

One
hole

One
hole

Top

PK5GTA

PK9GTA

3

PK12GTA 3
PK15GTA 3

6

9

9

3.78

[96]

3.13

[80]

Top

12

12

4.70

[119]

3.13

[80]

Top

5.63

[143]

3.13

[80]

Top
Top

15

15

5

16

15

PK15GTA6 6

21

15

PK18GTA 3

18

18

PK18GTAL 5

19

18

PK15GTAL

PK23GTA

3

23

23

PK23GTAL5

24

23

PK27GTA 3 8

27
or
26

27
or
26

1
6
1
1
1

8.13

[207]

3.13

[80]

5.88

[149]

7

7

Top

6.56

[167]

3.13

[80]

Top

8.81

[224]

3.13

[80]

Top

8.11

[206]

3.13

[80]

Top

9.44

[240]

3.13

[80]

Top

9.36

[238]

3.13

[80]

Top

1

Mounting screw 40205-065-01 (one required).

2

Mounting screw 21922-18360 (two required).

3

Mounting screw 21594-14220 (two required).

4

Mounting screw 21594-14241 (two required).

5

Mounting screw 21594-14302 (two required).

6

Mounting screws 21594-14241(two required) and 21594-17121(two required).

7

3.13 in. (80 mm) on small terminals; 5.25 in. (133 mm) on large terminals.

8

PK27GTA includes one main grounding lug that mounts with two terminal screws and requires
three terminals for mounting.

Wire Range Table

48

© 2007 Schneider Electric All Rights Reserved

Size

Cu (AWG)

Al (AWG)

I

(1) #14 #4 or (2) #14 or #12

(1) #12 #4 or (2) #12 or #10
(1) #1 4 /0

II

(1) #1 4 /0

III

(1) #6 2 /0

(1) #6 2 /0

IV

(1) #6 3 /0

(1) #6 3 /0

V

(1) #14 1/0

(1) #14 1 /0

VI

(1) #10 2/0

(1) #6 2 /0

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
Main Lugs and Main Circuit Breakers Ratings
MAIN LUGS AND MAIN CIRCUIT BREAKERS RATINGS
Single-Phase, Three-Wire, 120/240 Vac Main Lugs

Mains
Rating
in
Amps

Load Center
Catalog Number

LoadCenter
Cover
Catalog
Number

Indoor

UL Listed
Service
Equipment
(See Notes)

Maximum
UL Short
Circuit
Rating 1

B

10,000 A

Main Wire Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Page 27)

Top or
Bottom
Mains
Position

UL Listed for
Corner Grounded
Delta Systems

2

Top

No

Fixed Mains – Factory-Installed Main Lugs
70

HOM24L70F/S

Included

#12 3
#14 4

100

HOM612L100F/S

Included

B, C

10,000 A

#8 1

4

Top

No

125

HOM48L125GC

Included

B, C

10,000 A

#4 2/ 0

21

Top

No

Convertible Mains – Factory-Installed Main Lugs
QOM1 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker

125

HOM816L125C

Included

B, C

10,000 A

#6 2/ 0

6

Both

HOM816L125TC

Included

B, C

10,000 A

#6 2/ 0

6

Both

HOM12L125C

Included

B, C

10,000 A

#6 2/ 0

6

Both

HOM1224L125TC

Included

B, C

10,000 A

#6 2/ 0

6

Both

HOM1624L125C

Included

B, C

10,000 A

#6 2/ 0

8

Both

HOM20L125C

Included

B, C

10,000 A

#6 2/ 0

8

Both

HOM20-24L125TC

Included

B, C

10,000 A

#6 2/ 0

8

Both

HOM24L125TC

Included

B, C

10,000 A

#6 2/ 0

8

Both

No

Convertible Mains – Factory-Installed Main Lugs
QOM2 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker
150

200

225

HOM30L150C

Included

B, C

10,000 A

#4 250

10

Both

HOM30L150TC

Included

B, C

10,000 A

#6 250

10

Both

HOM1632L200TC

Included

B, C

10,000 A

#4 250

9

Both

HOM1632L200TCFT 2

Included

B, C

10,000 A

#6 250

10

Both

HOM2040L200TC

Included

B, C

10,000 A

#6 250

9

Both

HOM30L200C

Included

B, C

10,000 A

#6 250

10

Both

HOM30L200TC

Included

B, C

10,000 A

#6 250

9

Both

HOM3040L200TC

Included

B, C

10,000 A

#6 250

10

Both

HOM40L200C

Included

B, C

10,000 A

#6 250

12

Both

HOM40L200TC

Included

B, C

10,000 A

#6 250

12

Both

HOM42L225C

Included

B, C

10,000 A

#6 250

10

Both

1

UL short circuit rating with optional QOM-VH main circuit breaker, 22,000 AIR.

2

Supplied with feed-thru lugs.

No

B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) when not more than six service disconnecting means are provided and
when not used as a lighting and appliance branch circuit panelboard.

03/2007

© 2007 Schneider Electric All Rights Reserved

49

Homeline® Circuit Breakers and Load Centers—Class 1170
Main Lugs and Main Circuit Breakers Ratings
Single-Phase, Three-Wire, 120/240 Vac Main Circuit Breaker

Mains
Rating
in
Amps

Load
Center Catalog
Number

Load
Center Cover
Catalog
Number

UL Listed
Service
Equipment
(See Notes)

Indoor

Maximum
UL Short
Circuit
Rating 1▲

Main Wire Size
AWG/kcmil
Al/Cu

Enclosure
No.
(Page 27)

Top or
Bottom
Mains
Position

22,000 A

#6 1

5

Both

UL Listed for
Corner
Grounded Delta
Systems

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM1 Main Frame Size – Convertible to Main Lugs
HOM816M100C

100

125

Included

A, C

HOM816M100TC

Included

A, C

22,000 A

#6 1

5

Both

HOM12M100C

Included

A, C

22,000 A

#4 2 /0

6

Both

HOM1224M100TC

Included

A, C

22,000 A

#4 2 /0

6

Both

HOM20M100C

Included

A, C

22,000 A

#4 2 /0

8

Both

HOM24M100C

Included

A, C

22,000 A

#4 2 /0

8

Both

HOM30M100C

Included

A, C

22,000 A

#4 2 /0

10

Both

HOM1224M125C

Included

A, C

22,000 A

#4 2 /0

6

Both

HOM1224M125TC

Included

A, C

22,000 A

#4 2 /0

6

Both

HOM24M125C

Included

A, C

22,000 A

#4 2 /0

8

Both

HOM30M125C

Included

A, C

22,000 A

#4 2 /0

10

Both

No

No

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM2 Main Frame Size – Convertible to Main Lugs
150

200

225

HOM1632M150TC

Included

A, C

22,000 A

#4 250

9

Both

HOM2030M150TC

Included

A, C

22,000 A

#4 250

9

Both

HOM30M150C

Included

A, C

22,000 A

#4 250

10

Both

HOM1224M200TC

Included

A, C

22,000 A

#4 250

9

Both

HOM1632M200TC

Included

A, C

22,000 A

#4 250

9

Both

HOM2040M200C

Included

A, C

22,000 A

#4 250

9

Both

HOM2040M200TC

Included

A, C

22,000 A

#4 250

9

Both

HOM30M200C

Included

A, C

22,000 A

#4 250

10

Both

HOM3040M200TC

Included

A, C

22,000 A

#4 250

10

Both

HOM40M200C

Included

A, C

22,000 A

#4 250

12

Both

HOM42M200C

Included

A, C

22,000 A

#4 250

12

Both

HOM42M225C

Included

A, C

22,000 A

#4 250

12

Both

No

No

No

Universal Mains – No Factory-Installed Main Circuit Breaker or Main Lugs
QOM2 Main Frame Size – Field-Installed Main Lugs or 22,000 AIR Main Circuit Breaker
200
1

HOM1632U200TC

Included

B, C

10,000 A

#4 250

9

Both

HOM2040U200TC

Included

B, C

10,000 A

#4 250

9

Both

HOM3040U200TC

Included

B, C

10,000 A

#4 250

10

Both

No

UL short circuit rating with optional QOM-VH main circuit breaker, 22,000 AIR.

A UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with a factory-installed service disconnect.
B UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs when not more than six disconnecting
means are provided and when not used as lighting and appliance branch circuit panelboard.

50

© 2007 Schneider Electric All Rights Reserved

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
Main Lugs and Main Circuit Breakers Ratings
Single-Phase, Three-Wire, 120/240 Vac Main Lugs
Mains
Rating
in
Amps

Load
Center Catalog
Number

Load
Center Cover
Catalog
Number

Rainproof

UL Listed
Service
Equipment
(See Notes)

Maximum
Main Wire Size
UL Short
AWG/kcmil
Circuit
Al/Cu
Rating 1▲

Enclosure
No.
(Page 28)

Top or
Bottom
Mains
Position

UL Listed for
Corner Grounded
Delta Systems

#12 3 Al
#14 4 Cu

1R

Top

No

Fixed Mains – Factory-Installed Main Lugs
70

HOM24L70RB

Included

B

10,000 A

100

HOM612L100RB

Included

B, C

10,000 A

#8 1

2R

Top

No

10,000 A

#12 2/ 0 Al
#14 2/0 Cu

16R

Top

No

125

HOM48L125GRB

Included

B, C

Convertible Mains – Factory-Installed Main Lugs – QOM1 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker

125

HOM816L125RB

Included

B, C

10,000 A

#6 2 /0

3R

Top

HOM12L125RB

Included

B, C

10,000 A

#6 2 /0

3R

Top

HOM1224L125RB

Included

B, C

10,000 A

#6 2 /0

3R

Top

HOM20L125RB

Included

B, C

10,000 A

#6 2 /0

4R

Top

No

Convertible Mains – Factory-Installed Main Lugs – QOM2 Main Frame Size – Convertible to 22,000 AIR Main Circuit Breaker

200

HOM12L200RB

Included

B, C

10,000 A

#6 250

5R

Top

HOM2040L200RB

Included

B, C

10,000 A

#6 250

6R

Top

HOM30L200RB

Included

B, C

10,000 A

#6 250

7R

Top

HOM40L200RB

Included

B, C

10,000 A

#6 250

8R

Top

Single-Phase Three Wire 120/240 Vac Main Breaker

No

Rainproof

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM1 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker

100

125

HOM816M100RB

Included

A, C

22,000 A

#4 2 /0

3R

Top

HOM12M100RB

Included

A, C

22,000 A

#4 2 /0

3R

Top

HOM20M100RB

Included

A, C

22,000 A

#4 2 /0

4R

Top

No

HOM24M100RB

Included

A, C

22,000 A

#4 2 /0

6R

Top

HOM24M125RB

Included

A, C

22,000 A

#4 2 /0

6R

Top

No

No

Convertible Mains – Factory-Installed Main Circuit Breaker
QOM2 Main Frame Size – Convertible to Main Lugs or Lower Amperage Main Circuit Breaker
150

200

225

HOM30M150RB

Included

A, C

22,000 A

#4 250

7R

Top

HOM2040M200RB

Included

A, C

22,000 A

#4 250

6R

Top

HOM30M200RB

Included

A, C

22,000 A

#4 250

7R

Top

HOM3040M200RB

Included

A, C

22,000 A

#4 250

7R

Top

8R

HOM40M200RB

Included

A, C

22,000 A

#4 250

HOM1624M225RB

Included

A, C

22,000 A

#4-250

Top

HOM42M225RB

Included

A, C

22,000 A

#4-250

Top

No

Top
No

Factory-Installed Main Circuit Breaker with Feed-Thru Lugs
150

HOM816M150FTRB

Included

A, C

22,000 A

#4 250

6R

Top

No

200

HOM816M200FTRB

Included

A, C

22,000 A

#4 250

6R

Top

No

B

22,000 A

#4 250

6R

Top

No

Universal Main Circuit Breaker with Feed-Thru Lugs
200
1

HOM816U200FTRB

Included

UL short circuit rating with optional QOM-VH main circuit breaker, 22,000 AIR.

A UL Listed as suitable for use as service equipment (neutral bonded at time of installation) with factory-installed service disconnect.
B UL Listed as suitable for use as service equipment (neutral bonded at time of installation) with field-installed service disconnect.
C UL Listed as suitable for use as service equipment (neutral bonded at the time of installation) with field-installed main lugs when not more than six service
disconnecting means are provided and when not used as a lighting and appliance branch circuit panelboard.

03/2007

© 2007 Schneider Electric All Rights Reserved

51

Homeline® Circuit Breakers and Load Centers—Class 1170
Homeline Label Samples
HOMELINE LABEL SAMPLES
For information on two-tier and three-tier series ratings, see Data Bulletin number 4100DB0301, Square D® Load Center Short
Circuit Current Ratings , located on the Technical Library at www.SquareD.com.

Homeline Box Label Sample

Number of circuits maximum.
Enclosure catalog number.
Catalog number of covers; flush
or surface.
See panelboard interior for the
catalog number.
Voltage ratings.
Amperage rating.

Wire range for lug torque data table.

HOM LOAD CENTER
See Panelboard interior for Catalog No.
Box Cat. No. / Caja No. de Catalogo:
BXH34A
Use Cover Cat. No. /
Utilice la Cubierta No. de Catalogo:
HOMC30UC
Mains 200A max. / Lina Principal de.
200A maximo.
See main or service disconnect
rating if installed.
120/240 V ~ Max. 1Ø, 50 / 60 Hz.
30 circuit max. / 30 circuitos maximo.
Type 1 Enclosure
Gabinete Tipo 1
For installation, repairs or alterations,
Call an electrical contractor or electrician.

Short circuit ratings.
Short circuit ratings and additional of replacement
circuit breakers.

LUG TORQUE DATA

Underwriter’s
Laboratories, Inc.®

SHORT CIRCUIT RATING

See circuit breakers and field installed
units for wire binding screw torque

RMS Symmetrical Amperes at 120 / 240 V ~ Maximum

Wire Range (AWG/kcmil)

Torque (in/lbs.)

Main Lug

4 - 250 CU/AL

250

Service
Ground Lug

6 - 2/0 CU/AL

50

Alternate
Main Breaker

See Main
Breaker

See Main
Breaker

Branch Neutral and Equipment Ground Bar
Wire Range (AWG)

Torque (in./lbs.)

6 CU / AL

Large 45

8 CU / AL

Large 40

14-10 CU, 12-10 AL

Large 35

Equipment Ground Combinations

UL listing.

Two 14 or 12 CU

25

Two 12 or 10 AL

10

Panel
Rating

Remote
Main

Integral
Main

Branch (min.)/
Cat. prefix

42,000

QOH

Lugs

10,000 / HOM
10,000 / HOM

22,000

QOME..VH

Lugs

*10,000

----

Lugs

10,000 HOM

22,000

----

QOM2...VH

10,000 HOM

10,000

----

QOM2

10,000 HOM

LISTED
Electric
Cabinet Box
Issue No. V-2813

®

* The rating is equal to the lowest interrupting rating of any circuit breaker
installed. Refer to branch breaker for individual ratings. Additional or
replacement branch circuit breakers, main breaker, or service disconnect
MUST have an interrupting rating equal to or greater than that of the
circuit breaker with the lowest interrupting rating presently installed.
See panelboard interior for breaker types.

Install loose label with Spanish translation
on back of cover.
Adhiera la etiqueta suelta con las traducciones
~
en espanol en la parte posterior del frente.
Please read information before installing
Por favor lea la informacion antes de instalar.
/

001021

15

40265-381-03

Homeline Wiring Diagram Sample

Service Equipment marking.
Use of unused neutral branch terminal for
equipment grounding, service equipment
application only.

52

Line / Lines
1

N

O

O

2

O

O

Main Breaker diagram

© 2007 Schneider Electric All Rights Reserved

LOAD / CARGAS

4

Main Lugs diagram

Service ground
when required. /
Tierra de acometida
cuando fuese
necesario
4. Main lugs kit no:
QOL125. / No. de
accesorio de las
zapatas
principales:
QOL125.

Type of circuit breakers
from Square D that
may be used in this
panelboard.

One single pole. One plug
on space. One two pole
requires two plug on
spaces.

3.

3

N

N

LOAD / CARGAS

* Suitable for use as service equipment when
service disconnect (main breaker) is installed.
* Suitable for use as service equipment when
not more than six main disconnecting means
are provided and when not used as a lighting
and appliance branch circuit panelboard.
See Article 384-14 of the NEC.
* When used as service equipment, all unused
neutral terminals may be used for terminating
equipment ground wires.

1. Box bonding when required. / Conexion a la caja
cuando fuese necesario.
2. Main breaker type: QOM1 or QOM1A. / Interruptor
automatico principal tipo: QOM1 o QOM1A.

LOAD / CARGAS

Suitable for use with 75oC
Copper or Aluminum
main conductors. See
branch breakers for
branch wire ratings.

Installation of back-fed main circuit breaker and
required kit.
Alternate wiring diagram for main circuit breaker or
main lug.

Torque Note: When main
breaker or main lug
connector mounting nuts
are loosened or removed,
retighten to 75 lbs./in.
torque.
Equipment Grounding
Terminals

Load center accessories.
Neutral lug for 1/0 AWG or larger wire.
Load Center Accessories - Kits
HOM4K2LA
Back-fed Main Circuit Brkr. Retaining
HOM2175SB
Plug-0n Surge Arrestor *
SDSA1175
1 Phase Surge Arrestor
QOSAMK
SDSA1175 Mounting Bracket
HOML2125
1 Phase Plug-on Subfeed Lugs *
PK9--27GTA(L) Equipment Ground Bar
PKGTAB
Equipment Ground Bar Insulator
LK70AN
70A Max. Neutral Lug
LK100AN
125A Max. Neutral Lug
QOL125
Main Lugs
PK6FL
Indoor Cover Lock
* May plug on two adjacent spaces.
Torque Note: When interior mounting screw is
loosened or removed, retighten to 35 lbs./in.

Made in U.S.A.

15

40265-668-02

03/2007

Homeline® Circuit Breakers and Load Centers—Class 1170
Wiring Diagrams
WIRING DIAGRAMS

S/N

S
N

S/N

S
N

S
N

HOM24L70F/S
HOM24L70RB

HOM48L125GC
HOM48L125GRB
S
N

S
N

HOM612L100F/S
HOM612L100RB
S
N

S
N

S
N

G
B

HOM816L125TC

S
N

HOM12L125C
HOM12L125RB
HOM12L200RB

S
N

HOM20L125C
HOM20L125RB

S
N

S
N

S
N

HOM1224L125RB

HOM1624L125C

S
N

S
N

G
B

HOM1632L200TC

HOM246125TC

S
N

S
N

S
N

HOM1632L200TCFT

S
N

S
N

HOM2040L200TC

G
B

HOM30L150C
HOM30L200C
HOM30L200RB
HOM30L200TC

HOM3040L200TC
HOM40L200C
HOM40L200RB

S
N

S
N

S
N

HOM42L225C

S
N

S
N

S
N

HOM1632U200TC

S
N

S
N

1-Phase, 3-Wire Main Lugs

S
N

S
N

S
N

G
B

HOM2040L200RB

S
N

S
N

G
B

G
B

G
B

S
N

S
N

S
N

S
N

S
N

S
N

HOM2024L125TC

S
N

G
B

HOM1224L125TC
S
N

S
N

HOM816L125C
HOM816L125RB

G
B

HOM2040U200TC

S
N

G
B

G
B

HOM3040U200TC

HOM816U200FTRB

Requires Field Installed Main

Universal Mains

03/2007

© 2007 Schneider Electric All Rights Reserved

53

Homeline® Circuit Breakers and Load Centers—Class 1170
Wiring Diagrams

S
N

S
N

MAIN

S
N

HOM816M100C
HOM816M100RB

S
N

S
N

MAIN

G
B

HOM816M100TC

S
N

S
N

MAIN

HOM12M100C
HOM12M100RB

HOM816M150FTRB
HOM816M200FTRB

S
N
S
N

S
N

S
N

MAIN

HOM1224M100TC
HOM1224M125TC
HOM1224M200TC

HOM1224M125C

S
N

S
N

MAIN

S
N

MAIN

S
N

MAIN

G
B

HOM1624M225RB

HOM1632M150TC
HOM1632M200TC

MAIN

S
N

S
N

G
B

HOM2030M150TC

MAIN

S
N

S
N

HOM2040M200C
HOM2040M200RB

S
N

G
B

HOM20M100C
HOM20M100RB

MAIN

S
N

S
N

MAIN

MAIN

S
N

MAIN

S
N

G
B

HOM2040M200TC

S
N

S
N

MAIN

S
N

MAIN

S
N
S
N

S
N

MAIN

S
N

HOM24M100C
HOM24M100RB
HOM24M125C
HOM24M125RB
HOM24M200C

S
N

S
N

MAIN

S
N

G
B

HOM30M100C
HOM30M125C
HOM30M150C
HOM30M200C
HOM30M150RB
HOM30M200RB

HOM3040M200TC
HOM3040M200RB

HOM40M200C
HOM40M200RB

HOM42M225C
HOM42M200C
HOM42M225RB

1-Phase, 3-Wire Main Circuit Breakers

54

© 2007 Schneider Electric All Rights Reserved

03/2007

QO® and Homeline® Load Centers and Enclosures
Index

1100CT0501
03/2007

INDEX
A

F

N

accessories
cover filler plates 16, 46
flush lock kits 16, 47
generator circuit breaker interlock kit 17, 47
grounding bar kits 16, 19, 51
manual transfer equipment kit 17
secondary surge arrester 17, 46
assemblies
base 35
neutral 7, 35
auxiliary
gutters and tap kits 18
neutral lugs 16, 46

feed-thru
lugs 11, 45, 53, 51
universal main 45, 47
fixed
main lugs, single-phase 8, 15, 20, 45, 47
main lugs, three-phase 13
mains, single-phase 10, 15, 20, 21, 45,
47, 51
mains, three-phase 14, 24, 29
flush lock kits 16, 47

neutral assemblies 7, 35

B
back-fed circuit breaker retaining kit 17, 47
base assemblies 35
bolt-on hubs 6, 18, 35, 46
branch circuit breakers 5, 42

C
catalog number description 4, 41
circuit breakers
back-fed 17, 47
branch 5, 42
enclosed molded case 36
lugs 10
main 10, 13, 44
ratings 5, 9, 20, 34, 36, 44, 47
with Visi-Trip® 35
class CTL 7, 42
convertible
main circuit breakers, single-phase 9, 47
main lugs, single-phase 10, 20, 47
mains, single-phase 8, 15, 45
mains, three-phase 13, 14
cover filler plates 16, 46
covers
indoor 6, 44
load centers 8, 10, 13, 44
CSA certified 8, 11

D
dimensions and knockouts
indoor 26, 37
outdoor 27, 37

E
enclosures
type 1, indoor 6, 34, 43
type 3R, outdoor 6, 34, 43

© 2007 Schneider Electric All Rights Reserved

G
generator panels 12, 25
grounding bar kits 16, 19, 35, 46, 48

H
hubs, bolt-on 6, 18, 35, 46, 46

I
interiors 8, 9, 13, 15, 44

K
kits

auxiliary gutters and taps 18
back-fed main circuit breakers 17, 47
flush lock 16, 47
grounding bar 16, 19, 35, 46, 47
main circuit breakers 10, 45, 47
main lugs 10, 14, 47
manual transfer 17
retaining 17, 47

L
load centers
Homeline® circuit breaker 42
QO® circuit breaker 3
lugs
auxiliary neutral 16, 46
feed-thru 11, 26, 45, 51
line 7
main 7,11,14, 20-26, 44, 45, 47
ratings 5, 9, 20, 44, 46

M
main circuit breakers
features 3, 11,12,16, 45
kits 10, 47
mobile home load centers 45
ratings 5, 9, 35, 36, 45
sizes 12,13,15, 44
mains
back-fed 17, 47
convertible, single-phase 9, 20-24, 28, 49
convertible, three-phase 13
fixed, single-phase 20, 44, 49, 51
fixed, three-phase 24, 29
lug kits 10, 14, 47
lugs 14, 20 2 8, 44, 46
manual transfer kits 17

R
ratings
circuit breakers 5, 20, 34, 36, 44, 47
enclosed molded case circuit breakers 34,
36
grounding bar 16, 19, 35, 46, 51
main circuit breakers 5, 13, 20, 45, 47
indoor, single-phase 9, 10, 20, 49
indoor, three-phase 24, 28
rainproof, single-phase 11, 18, 46
rainproof, three-phase 24, 25
main lugs 5, 20-28, 44, 45
main lugs and main circuit breakers 5,
20 2 8, 45, 47
indoor, single-phase 9,10, 20, 49
indoor, three-phase 24, 25
rainproof, single-phase 11,12, 20,
47, 51
rainproof, three-phase 24, 25
recreational vehicle and manufactured
housing 11
short circuit 8, 9,13, 15, 20-25, 44, 47
tap kits 18
RB devices 6, 18, 34, 46
recreational vehicle and manufactured
housing 11
replacement parts - see note below
retaining kits 17, 47

S
service 5, 34, 42
short circuit ratings 9,13,15, 20-25, 44, 49
special purpose 11 12
surge arresters, secondary 17, 46

T
transfer switches, manual and automatic 12

U
UL listed 8 9, 13, 15, 17, 18, 20-26, 36, 42,
46, 49

W
wiring diagrams 30 33, 53

NOTE: For information on Replacement
Parts with specific part numbers, go to
www.schneider-electric.us, click on
Product FAQ’s, enter the device catalog
number, click SEARCH, then look for
the information required.

55

QO® and Homeline® Circuit Breaker Load Centers and Enclosures
Catalog

Schneider Electric USA
1601 Mercer Road
Lexington, KY 40511 USA
1-888-SquareD
(1-888-778-2733)
www.us.SquareD.com

Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
1100CT0501 © 2007 Schneider Electric All Rights Reserved
Replaces 1100CT9901 dated September 2000.
03/2007



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
Create Date                     : 2007:02:19 12:51:11Z
Creator                         : FrameMaker 7.1
Modify Date                     : 2012:06:25 14:41:32+05:30
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Producer                        : Acrobat Distiller 7.0.5 (Windows)
Creator Tool                    : FrameMaker 7.1
Metadata Date                   : 2012:06:25 14:41:32+05:30
Format                          : application/pdf
Title                           : untitled
Document ID                     : uuid:ae77d331-d5d0-40e2-85af-b6aa61dd1ecb
Instance ID                     : uuid:85ed5e4e-5711-4798-a95a-2beec4fe47e7
Page Mode                       : UseNone
Page Count                      : 56
EXIF Metadata provided by EXIF.tools

Navigation menu