16011089.001 503792 CB Certification
2016-04-11
: Pdf 503792 Cb Certification 503792_CB_Certification CertsReports 503792 ProductFiles
Open the PDF directly: View PDF .
Page Count: 86
Download | |
Open PDF In Browser | View PDF |
www.tuv.com <16011089 001> Page 2 of 73 Copy of marking plate(s): With Euro-plug: With BS plug: The GS mark, T-mark, CE mark, indoor use and class II symbol are moulded on enclosure. With Australian plug: With Indian plug: These are representative labels, the others are identical to them except the model number and input voltage rang and output ratings as listed in the model list on page 5. Summary of testing: 1. The tested samples comply with the requirements of this standard. 2. Compliance with the National requirements of countries which are same as national differences countries as given in CB Bulletin 112A. 3. The models DSA-5W-05 FEU 050100, DSA-5W-12 FEU 082061 and DSA-5W-12 FEU 120042 have been selected for test, and unless otherwise specified, the model DSA-5W-12 FEU 120042 was tested. 4. The models are in compliance with the requirements of subclause 2.5 (limited power source). TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 3 of 73 Particulars: test item vs. test requirements Equipment mobility .......................................: Direct plug-in equipment Operating condition .......................................: Continuous Mains supply tolerance (%) ...........................: + 10% / - 10% (as request by client) Tested for IT power systems ........................: Yes, Norway IT testing, phase-phase voltage (V) .............: 230 (only for Norway) Class of equipment .......................................: Class II Mass of equipment (kg).................................: Approx. 0.08kg Protection against ingress of water ..............: IPX0 Test case verdicts Test case does not apply to the test object ..: N/A Test item does meet the requirement ..........: P(ass) Test item does not meet the requirement ....: F(ail) Testing Date of receipt of test item ...........................: 25 Oct, 2007 Date(s) of performance of test .....................: 25 Oct, 2007 – 30 Oct, 2007 General remarks ”This report is not valid as a CB Test Report unless appended by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02”. The test result presented in this report relate only to the object(s) tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. ”(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a point is used as the decimal separator. Comments: Summary of compliance with National Differences (for explanation of codes see below): AT, AU, BE, CH, DE, DK, FI, FR, GB, GR, HU, IL, IN, IT, KE, MY, NL, NO, PL, SE, SG, SI, SK AT=Austria, AU=Australia, BE=Belgium, CH=Switzerland, DE=Germany, DK=Denmark, FI=Finland, FR=France, GB=United Kingdom, GR=Greece, HU=Hungary, IL=Israel, IN=India, IT=Italy, KE=Kenya, MY=Malaysia, NL=The Netherlands, NO=Norway, PL=Poland, SE=Sweden, SG=Singapore, SI=Slovenia, SK=Slovakia All national differences of EU group considered according to EN 60950-1:2001, Annex ZA, Annex ZB and Annex ZC on pages 28–37; National differences of Australia considered according to AS/NZS 60950.1-2003 on pages 53–59; EN 60950-1/A11 have been added to original TRF, see page 28-37. The dimension of European plug checked according to EN 50075 (see appended table on page 60), the British plug was evaluated according to BS1363 (see appended table on pages 61-62), the Australian plug was evaluated according to AS/NZS 3112 (see appended table on pages 63-72). The Indian plug was evaluated according to BS 4573 (see appended table on pages 73) Factories: 1) Dee Van Electronics (Shenzhen) Co., Ltd. th The 5 Industrial District, Gongming, Bao An District, Shenzhen, Guangdong 518106, P.R. China 2) Dee Van Electronics (Longchuan) Co., Ltd. Meichun Industrial District, Longchuan Country, Heyuan, Guangdong 517300, P.R. China 3) Dee Van Technology (Longchuan) Co., Ltd. Meichun Industrial District, Longchuan Country, Heyuan, Guangdong 517300, P.R. China TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 4 of 73 General product information: Brief description of the test sample: 1. The equipment models DSA-5W-a Ab xy, DSA-5W-a Fb xy are Switching Adapter (direct plug-in type) used for DC supply of IT or office equipment. 2. The power supply’s top enclosure is secured to bottom enclosure by ultrasonic welding. 3. The test items are pre-production samples without serial numbers. 4. The model reference is DSA-5W-a Ab xy, DSA-5W-a Fb xy, ‘a’ represents output voltage range, ‘b’ represents used plug type, ‘x’ represents the output voltage and ‘y’ represents the output current, details see model list on page 5; 5. The plug pin holder of European plug and Indian plug were fixed into the enclosure of plug portion by a screw. The pin parts of British plug and Australian plug were moulded into the enclosure of plug portion. It is impossible to remain in the mains socket-outlet after removal of the adapter, details see photo document. 6. The maximum ambient temperature is 40°C. Difference between models: 1. The models DSA-5W-a Ab xy are identical to models DSA-5W-a Fb xy except for the model name and input voltage range; 2. Transformer: The adaptors with different output voltage have different secondary winding of transformer, details see model list in page 5; 3. R10, R11, R12, R13, R15, R17, C7, C9, D8, Z1, Z2, Z3: The parameters of these components depend on output power and output voltage. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 5 of 73 Model list: DSA-5W-a Ab xy; DSA-5W-a Fb xy: No MODEL 1 DSA-5W-05 Ab xy 2 DSA-5W-12 Ab xy 3 DSA-5W-05 Fb xy 4 DSA-5W-12 Fb xy INPUT V, A 200–240VAC, 50/60Hz, 0.2A 100–240VAC, 50/60Hz, 0.2A OUTPUT T1 sec winding V dc Max. A Max. W 5.0 – 8.1 1.00 5 0.35mmx14Ts 8.2-12.0 0.61 5 0.20mmx18Ts 5.0 – 8.1 1.00 5 0.35mmx14Ts 8.2-12.0 0.61 5 0.20mmx18Ts Note: ’a’ can be 05, 12; ‘b’ can be ‘EU’, ‘UK’, ‘US’, ‘CH’, ‘AU’, ‘KA’, ‘JP’ or ‘IN’, EU means European plug used, UK means British plug used, US means American or Japanese plug used, CH means Chinese plug used, AU means Australian plug used, KA means Korean plug used, JP means Japanese plug used, IN means Indian plug used; ‘x’ is 3 digit number which represents the output voltage in Volt after dividing by 10, from 5.0V to 12.0V in step of 0.1V, for example, 090 represents the output voltage is 9.0 V, 120 represents the output voltage is 12.0V; ‘y’ is 3 digit number which represents the output current in Ampere after dividing by 100 which is up to 1.0A in step of 0.01A, for example, 041 represents the output current is 0.41A, 100 represents the output current is 1.00A. By multiplication of output voltage and output current, the type designations are limited through the max. output power. Only the European plug, British plug, Australian plug and Indian were considered in this report. Other types of plug should be evaluated during national approval. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 6 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 1 GENERAL P 1.5 Components P 1.5.1 General Components which were found to affect safety aspects comply with the requirements of this standard or within the safety aspects of the relevant IEC component standards. P Comply with IEC 60950 or relevant component standard (see appended table 1.5.1) P 1.5.2 Evaluation and testing of components Components which are certified to IEC and /or national standards are used correctly within their ratings. Components not covered by IEC standards are tested under the conditions present in the equipment. P 1.5.3 Thermal controls No thermal controls provided. N/A 1.5.4 Transformers Transformer used are suitable for their intended application and comply with the relevant requirements of the standard and particularly Annex C. P 1.5.5 Interconnecting cables Interconnection o/p cable to other device is carrying only SELV on an energy level below 240 VA. P → Except for the insulation material, there are no further requirements for the o/p interconnection cable. 1.5.6 Capacitors in primary circuits ...............................: No such capacitor used. 1.5.7 Double insulation or reinforced insulation bridged by components 1.5.7.1 General 1.5.7.2 Bridging capacitors Between primary side and secondary: Y1-capacitor (CY1) according to IEC 60384-14. P 1.5.7.3 Bridging resistors No such resistor used. P 1.5.7.4 Accessible parts See clause 2.4 P 1.5.8 Components in equipment for IT power systems No such component 1.6 Power interface 1.6.1 AC power distribution systems TRF No.:IECEN60950_1B See below. N/A P P N/A P IT power system for Norway only, TN power system for others P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 7 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark 1.6.2 Input current Highest load according to 1.2.2.1 for this equipment is the operation with the max. specified DC-load. Verdict P Results see appended table 1.6.3 Voltage limit of hand-held equipment Not hand-held equipment. N/A 1.6.4 Neutral conductor Class II equipment without earth connection. N/A 1.7 Marking and instructions 1.7.1 Power rating P See below. P Rated voltage(s) or voltage range(s) (V) .............: AC100-240V for DSA-5W-a Fb xy; AC200-240V for DSA-5W-a Ab xy Symbol for nature of supply, for d.c. only .............: Mains from AC source P N/A Rated frequency or rated frequency range (Hz) ..: 50/60Hz P Rated current (mA or A) ......................................: 0.2A P Manufacturer’s name or trademark or identification Not shown / trademark of DVE mark .....................................................................: P Type/model or type reference...............................: DSA-5W-a Ab xy; DSA-5W-a Fb xy P Symbol for Class II equipment only .....................: Double square symbol provided. P Other symbols ......................................................: Additional symbols or marking does not give rise to misunderstanding. P Certification marks ...............................................: Refer to the copy of the label drawings for details. P 1.7.2 Safety instructions "User' s Manual" provided that contains information regarding the maximum ambient temperature. P 1.7.3 Short duty cycles Equipment is designed for continuous operation. 1.7.4 Supply voltage adjustment ...................................: No voltage selector. N/A Methods and means of adjustment; reference to installation instructions .........................................: N/A 1.7.5 Power outlets on the equipment ..........................: No power outlets provided. N/A 1.7.6 Fuse identification (marking, special fusing Fusing resistor used, marking characteristics, cross-reference) .........................: adjacent to the fusing resistor on PCB as: N/A P RF1 4.7ohm 1W 1.7.7 Wiring terminals TRF No.:IECEN60950_1B See below. N/A TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 8 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 1.7.7.1 Protective earthing and bonding terminals ..........: Class II equipment without earth connection. N/A 1.7.7.2 Terminal for a.c. mains supply conductors Direct plug-in equipment. N/A 1.7.7.3 Terminals for d.c. mains supply conductors No d.c. mains supply. N/A 1.7.8 Controls and indicators No safety related switches or indicators. N/A 1.7.8.1 Identification, location and marking .....................: N/A 1.7.8.2 Colours ...............................................................: N/A 1.7.8.3 Symbols according to IEC 60417 .........................: N/A 1.7.8.4 Markings using figures ........................................: N/A 1.7.9 Isolation of multiple power sources .....................: Only one supply from the mains. N/A 1.7.10 IT power distribution systems Only for Norway P 1.7.11 Thermostats and other regulating devices No such device. N/A 1.7.12 Language(s) .........................................................: Installation instruction in English and German. Versions in other languages have to be provided during the corresponding national approvals. 1.7.13 Durability The label was subjected to the permanence of marking test. The label was rubbed with cloth soaked with water for 15 sec. And then again for 15 sec. With the cloth soaked with petroleum spirit. After this test there was no damage to the label. The marking on the label did not fade. There was no curling nor lifting of the label edge. 1.7.14 Removable parts No removable part. N/A 1.7.15 Replaceable batteries No battery provided. N/A Language(s)..........................................................: P 1.7.16 Operator access with a tool ..................................: No operator accessible area that needs to be accessed by the use of a tool. N/A 1.7.17 Equipment for restricted access locations ............: Not limited for use in restricted access locations. N/A 2 PROTECTION FROM HAZARDS P 2.1 Protection from electric shock and energy hazards P TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 9 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 2.1.1 Protection in operator access areas No access with test finger and test pin to any parts with only basic insulation to ELV or hazardous voltage. P 2.1.1.1 Access to energized parts See above. P Test by inspection ................................................: See above. P Test with test finger ..............................................: See above. P Test with test pin ..................................................: See above. P Test with test probe .............................................: No TNV. N/A 2.1.1.2 Battery compartments .........................................: No battery compartment. N/A 2.1.1.3 Access to ELV wiring N/A No ELV wiring in operator accessible area. Working voltage (Vpeak or Vrms); minimum distance (mm) through insulation 2.1.1.4 Access to hazardous voltage circuit wiring 2.1.1.5 Energy hazards ....................................................: Energy does not exceed 240VA between any two points in accessible parts (o/p connector of secondary circuit). Results see appended table 2.1.1.5. No energy hazard in operator access area. 2.1.1.6 Manual controls No manual controls. N/A 2.1.1.7 Discharge of capacitors in equipment No capacitor provided between line and neutral. N/A No hazardous voltage wiring in operator accessible area. Time-constant (s); measured voltage (V) .............: N/A P 2.1.2 Protection in service access areas No operator accessible area that needs to be accessed by the use of a tool. N/A 2.1.3 Protection in restricted access locations Not limited for use in restricted access locations. N/A 2.2 SELV circuits 2.2.1 General requirements 2.2.2 Voltages under normal conditions (V) ..................: Between any conductor of the SELV circuits 42.4 V peak or 60 V d.c. are not exceeded. P The secondary circuits were tested as SELV. See 2.2.1 to 2.2.4. P P See appended table 2.2.2. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 10 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test 2.2.3 Voltages under fault conditions (V).......................: Single fault did not cause excessive voltage in accessible SELV circuits. Limits of 71V peak and 120V d.c. were not exceeded within 0.2 seconds and limits 42.4V peak and 60V d.c. were not exceeded for longer than 0.2 seconds. P 2.2.3.1 Separation by double insulation or reinforced insulation (method 1) P 2.2.3.2 Separation by earthed screen (method 2) N/A 2.2.3.3 Protection by earthing of the SELV circuit (method 3) N/A 2.2.4 Connection of SELV circuits to other circuits........: See 2.2.2 and 2.2.3. 2.3 TNV circuits 2.3.1 Limits 2.3.2 2.3.3 Result – Remark Double or reinforced for the highest working voltage across a particular insulation is provided. P N/A No TNV. N/A Type of TNV circuits .............................................: Separation from other circuits and from accessible parts N/A Insulation employed..............................................: Separation from hazardous voltages N/A Insulation employed..............................................: 2.3.4 Verdict Connection of TNV circuits to other circuits N/A Insulation employed..............................................: 2.3.5 Test for operating voltages generated externally 2.4 Limited current circuits P 2.4.1 General requirements P 2.4.2 Limit values P Frequency (Hz) .....................................................: (see appended table) Measured current (mA).........................................: (see appended table) Measured voltage (V) ...........................................: (see appended table) Measured capacitance (µF) ..................................: 2200pF N/A 2.4.3 Connection of limited current circuits to other circuits 2.5 Limited power sources P Inherently limited output N/A TRF No.:IECEN60950_1B See 2.2.2 and 2.2.3. No direct connection between SELV and any primary circuit. N/A TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 11 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict Impedance limited output N/A Overcurrent protective device limited output N/A Regulating network limited output under normal operating and single fault condition P Regulating network limited output under normal operating conditions and overcurrent protective device limited output under single fault condition N/A Output voltage (V), output current (A), apparent (See appended table) power (VA)............................................................: Current rating of overcurrent protective device (A) 2.6 Provisions for earthing and bonding P 2.6.1 Protective earthing Class II equipment. 2.6.2 Functional earthing Secondary functional ground separated to primary by reinforced or double insulation. 2.6.3 Protective earthing and protective bonding conductors N/A 2.6.3.1 General N/A 2.6.3.2 Size of protective earthing conductors N/A Rated current (A), cross-sectional area (mm2), AWG .....................................................................: 2.6.3.3 Size of protective bonding conductors N/A P N/A Rated current (A), cross-sectional area (mm2), AWG .....................................................................: 2.6.3.4 Resistance (Ω) of earthing conductors and their terminations, test current (A) ................................: N/A 2.6.3.5 Colour of insulation ...............................................: N/A 2.6.4 Terminals N/A 2.6.4.1 General N/A 2.6.4.2 Protective earthing and bonding terminals N/A Rated current (A), type and nominal thread diameter (mm) ......................................................: 2.6.4.3 Separation of the protective earthing conductor from protective bonding conductors N/A 2.6.5 Integrity of protective earthing N/A 2.6.5.1 Interconnection of equipment N/A 2.6.5.2 Components in protective earthing conductors and protective bonding conductors N/A 2.6.5.3 Disconnection of protective earth N/A 2.6.5.4 Parts that can be removed by an operator N/A 2.6.5.5 Parts removed during servicing N/A TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 12 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test 2.6.5.6 Corrosion resistance N/A 2.6.5.7 Screws for protective bonding N/A 2.6.5.8 Reliance on telecommunication network or cable distribution system 2.7 Overcurrent and earth fault protection in primary circuits P 2.7.1 Basic requirements Equipment relies on 16A rated fuse or circuit breaker of the wall outlet installation protection of the building installation in regard to L to N short circuit. Overcurrent protection is provided by the fusing resistor. P Instructions when protection relies on building installation Not applicable for pluggable equipment type A. N/A 2.7.2 Faults not covered in 5.3 The protection device is well dimensioned and mounted. P 2.7.3 Short-circuit backup protection Pluggable equipment type A. Building installation is considered as providing shortcircuit backup protection. P 2.7.4 Number and location of protective devices ..........: Over current protection by one built-in fusing resistor. P 2.7.5 Protection by several devices 2.7.6 Warning to service personnel ...............................: No service work is necessary. N/A 2.8 Safety interlocks N/A 2.8.1 General principles 2.8.2 Protection requirements N/A 2.8.3 Inadvertent reactivation N/A 2.8.4 Fail-safe operation N/A 2.8.5 Moving parts N/A 2.8.6 Overriding N/A 2.8.7 Switches and relays N/A 2.8.7.1 Contact gaps (mm) ..............................................: N/A 2.8.7.2 Overload test N/A 2.8.7.3 Endurance test N/A 2.8.7.4 Electric strength test N/A 2.8.8 Mechanical actuators N/A 2.9 Electrical insulation TRF No.:IECEN60950_1B Result – Remark No TNV Verdict N/A Only one fusing resistor provided. No safety interlock. N/A N/A P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 13 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 2.9.1 Properties of insulating materials Natural rubber, asbestos or hygroscopic material is not used. P 2.9.2 Humidity conditioning 120hr P Humidity (%) ........................................................: 95% R.H. Temperature (°C) .................................................: 40°C 2.9.3 Grade of insulation P 2.10 Clearances, creepage distances and distances through insulation P 2.10.1 General See 2.10.3, 2.10.4 and 2.10.5. P 2.10.2 Determination of working voltage The rms and the peak voltage were measured on the direct plug-in adaptor. The unit was connected to a 240Vac power supply and floating secondary circuits was assumed to be earthed at the point by which the highest working voltage is obtained. Results see appended table 2.10.2. P 2.10.3 Clearances See below and advantage of annex G is not considered. P 2.10.3.1 General See below, Annex G was not considered. P 2.10.3.2 Clearances in primary circuits Annex F and minimum clearances considered. P 2.10.3.3 Clearances in secondary circuits 2.10.3.4 Measurement of transient voltage levels No transient voltage across the clearance lower than due or normal. 2.10.4 Creepage distances (see appended table 2.10.3 and 2.10.4) Insulation complies with subclauses 2.10, 4.5.1 and 5.2. P N/A P CTI tests ...............................................................: CTI rating for all materials of min. 100. 2.10.5 Solid insulation See below. P 2.10.5.1 Minimum distance through insulation (see appended table 2.10.5) P 2.10.5.2 Thin sheet material Thin sheet material was not used as reinforced insulation. N/A 2.10.5.3 Number of layers (pcs) .........................................: Electric strength test Printed boards Distance through insulation TRF No.:IECEN60950_1B No multi-layer PCBs provided. N/A N/A TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 14 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Electric strength test for thin sheet insulating material Number of layers (pcs) .........................................: 2.10.5.4 Wound components Verdict N/A Approved source of triple insulated wire used as seondary winding of T1. P Number of layers (pcs) .........................................: 3 P Two wires in contact inside wound component; By insulation tape. angle between 45° and 90° ..................................: P 2.10.6 Coated printed boards 2.10.6.1 General N/A 2.10.6.2 Sample preparation and preliminary inspection N/A 2.10.6.3 Thermal cycling N/A 2.10.6.4 Thermal ageing (°C) .............................................: N/A 2.10.6.5 Electric strength test 2.10.6.6 Abrasion resistance test No coated printed boards. N/A Electric strength test 2.10.7 2.10.8 N/A Enclosed and sealed parts ...................................: No hermetically sealed component. N/A Temperature T1=T2 + Tma – Tamb +10K (°C)....: N/A Spacings filled by insulating compound................: No such component. N/A Electric strength test 2.10.9 Component external terminations See appended table 2.10.2 and 2.10.3. 2.10.10 Insulation with varying dimensions No such transformer used. 3 WIRING, CONNECTIONS AND SUPPLY P 3.1 General P 3.1.1 Current rating and overcurrent protection Internal wiring is PVC insulated, the wiring gauge is suitable for current intended to be carried. P N/A P Internal wiring for primary power distribution protected by built-in fuse. 3.1.2 Protection against mechanical damage Wires do not touch sharp edges which could damage the insulation and cause hazard. P 3.1.3 Securing of internal wiring The internal wiring are secured by solder pins or tubing so that loosening of the terminal connections is unlikely. P TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 15 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark 3.1.4 Insulation of conductors The insulation of the individual conductors are suitable for the application and the working voltage. For the insulation material see 3.1.1. (see appended table 5.2) 3.1.5 Beads and ceramic insulators Not used. N/A 3.1.6 Screws for electrical contact pressure No such screws provided. N/A 3.1.7 Insulating materials in electrical connections All current carrying connections are metal to metal. N/A 3.1.8 Self-tapping and spaced thread screws Not used. N/A 3.1.9 Termination of conductors All conductors are reliable secured. P 10 N pull test Force of 10 N applied to the termination points of the conductors. P 3.1.10 Sleeving on wiring No sleeving used to provide supplementary insulation. N/A 3.2 Connection to an a.c. mains supply or a d.c. mains supply P 3.2.1 Means of connection ............................................: A mains plug, that is part of direct plug-in equipment P 3.2.1.1 Connection to an a.c. mains supply See above P 3.2.1.2 Connection to a d.c. mains supply AC Source N/A 3.2.2 Multiple supply connections Only one supply connection. N/A 3.2.3 Permanently connected equipment Not permanently connected equipment. N/A Number of conductors, diameter (mm) of cable and conduits ........................................................: Verdict P 3.2.4 Appliance inlets Direct plug-in equipment. N/A 3.2.5 Power supply cords No power cord. N/A 3.2.5.1 AC power supply cords N/A Type......................................................................: Rated current (A), cross-sectional area (mm2), AWG .....................................................................: 3.2.5.2 DC power supply cords AC Source. N/A 3.2.6 Cord anchorages and strain relief No power cord. N/A Mass of equipment (kg), pull (N) ........................: Longitudinal displacement (mm) ..........................: 3.2.7 Protection against mechanical damage Direct plug-in equipment. No sharp edges. N/A 3.2.8 Cord guards No cord guard provided. N/A TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 16 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict D (mm); test mass (g) ..........................................: Radius of curvature of cord (mm).........................: 3.2.9 Supply wiring space 3.3 Wiring terminals for connection of external conductors N/A 3.3.1 Wiring terminals N/A 3.3.2 Connection of non-detachable power supply cords N/A 3.3.3 Screw terminals N/A 3.3.4 Conductor sizes to be connected N/A Not permanent connection or non-detachable power cord type. Direct plug-in equipment. Rated current (A), cord/cable type, cross-sectional area (mm2) ...........................................................: 3.3.5 N/A Wiring terminal sizes N/A Rated current (A), type and nominal thread diameter (mm) .....................................................: 3.3.6 Wiring terminals design N/A 3.3.7 Grouping of wiring terminals N/A 3.3.8 Stranded wire N/A 3.4 Disconnection from the mains supply 3.4.1 General requirement Disconnect device provided. P 3.4.2 Disconnect devices Plug of this direct plug-in equipment was used as disconnected device. P 3.4.3 Permanently connected equipment Not permanently connected equipment. 3.4.4 Parts which remain energized There is no parts remained with hazardous voltage or energy in the equipment when SPS is separated from AC mains. 3.4.5 Switches in flexible cords No flexible cords. 3.4.6 Single-phase equipment and d.c. equipment The mains plug disconnects both poles simultaneously. 3.4.7 Three-phase equipment Single phase equipment. N/A 3.4.8 Switches as disconnect devices See sub-clause 3.4.2. N/A 3.4.9 Plugs as disconnect devices See sub-clause 3.4.2. N/A 3.4.10 Interconnected equipment No interconnections using hazardous voltages. N/A 3.4.11 Multiple power sources Only one supply connection provided. N/A TRF No.:IECEN60950_1B P N/A P N/A P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 17 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test 3.5 Interconnection of equipment 3.5.1 General requirements 3.5.2 Types of interconnection circuits ..........................: Interconnection circuits of SELV through the connector. No ELV interconnection circuits. 3.5.3 ELV circuits as interconnection circuits 4 PHYSICAL REQUIREMENTS 4.1 Stability Angle of 10° Result – Remark Verdict P This power supply is not considered for connection to TNV. No ELV interconnection P P N/A P N/A Direct plug-in equipment. Test: force (N).......................................................: N/A N/A 4.2 Mechanical strength 4.2.1 General See below. After tests, unit comply with 2.1.1, 2.6.1, 2.10 and 4.4.1. P 4.2.2 Steady force test, 10 N 10N applied to components other than parts serving as an enclosure. P 4.2.3 Steady force test, 30 N No internal enclosure. 4.2.4 Steady force test, 250 N 250N applied to outer enclosure. No energy or other hazards. 4.2.5 Impact test Direct plug-in equipment. P N/A P N/A Fall test N/A Swing test N/A 4.2.6 Drop test No hazard as result from drop test. P 4.2.7 Stress relief test After 7 hours at temperature of 75°C and cooling down to room temperature, no shrinkage and distortion or loosening any enclosure part was noticeable on the adapter. P Test was performed for all sources of enclosure material. 4.2.8 Cathode ray tubes No CRT provided. Picture tube separately certified ...........................: N/A 4.2.9 High pressure lamps 4.2.10 Wall or ceiling mounted equipment; force (N) .....: Direct plug-in equipment. TRF No.:IECEN60950_1B N/A No High pressure lamps provided. N/A N/A TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 18 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 4.3 Design and construction 4.3.1 Edges and corners 4.3.2 Handles and manual controls; force (N) ...............: No handles or controls provided. N/A 4.3.3 Adjustable controls No controls provided. N/A 4.3.4 Securing of parts No connection likely to be exposed to mechanical stress is provided in unit. P 4.3.5 Connection of plugs and sockets No mismating of connectors, plugs or sockets possible. P 4.3.6 Direct plug-in equipment The prevention of imposing to undue strain on the socketoutlet was done by construction of the plug of adaptor. P P All edges and corners are rounded and /or smoothed. P For European plug: 0.02Nm; For British plug: 0.02Nm; For Australian plug: 0.02Nm; For Indian plug: 0.05Nm Dimensions (mm) of mains plug for direct plug-in : (See attached partial test reports) P Torque and pull test of mains plug for direct See above. plug-in; torque (Nm); pull (N) ................................: P 4.3.7 Heating elements in earthed equipment No heating elements provided. N/A 4.3.8 Batteries No batteries provided. N/A 4.3.9 Oil and grease No heating elements provided. N/A 4.3.10 Dust, powders, liquids and gases Equipment in intended use not considered to be exposed to these. N/A 4.3.11 Containers for liquids or gases No container for liquid or gas. N/A 4.3.12 Flammable liquids.................................................: No such flammable liquid. N/A Quantity of liquid (l) ...............................................: N/A Flash point (°C).....................................................: N/A 4.3.13 Radiation; type of radiation ..................................: No optical radiation present. N/A 4.3.13.1 General N/A 4.3.13.2 Ionizing radiation N/A 4.3.13.3 Measured radiation (pA/kg) .................................: Measured high-voltage (kV) ................................: Measured focus voltage (kV) ...............................: CRT markings .....................................................: Effect of ultraviolet (UV) radiation on materials N/A Part, property, retention after test, flammability classification ........................................................: N/A TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 19 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test 4.3.13.4 Human exposure to ultraviolet (UV) radiation ......: 4.3.13.5 Laser (including LEDs) Result – Remark Verdict N/A No optical radiation present. N/A Laser class ...........................................................: 4.3.13.6 Other types ..........................................................: N/A 4.4 Protection against hazardous moving parts N/A 4.4.1 General 4.4.2 Protection in operator access areas N/A 4.4.3 Protection in restricted access locations N/A 4.4.4 Protection in service access areas N/A 4.5 Thermal requirements 4.5.1 Maximum temperatures No moving parts. N/A P See appended table 4.5.1. P Normal load condition per Annex L.......................: See 1.6.2. P 4.5.2 Resistance to abnormal heat P 4.6 Openings in enclosures 4.6.1 Top and side openings See appended table 4.5.2. P No openings P Dimensions (mm) ................................................: 4.6.2 Bottoms of fire enclosures No openings P Construction of the bottom ...................................: 4.6.3 Doors or covers in fire enclosures No such things. N/A 4.6.4 Openings in transportable equipment No opening. N/A 4.6.5 Adhesives for constructional purposes No adhesive. N/A Conditioning temperature (°C)/time (weeks) ........: 4.7 Resistance to fire P 4.7.1 Reducing the risk of ignition and spread of flame Use of materials with the required flammability classes. P Method 1, selection and application of components wiring and materials (see appended table 4.7) P Method 2, application of all of simulated fault condition tests 4.7.2 Conditions for a fire enclosure TRF No.:IECEN60950_1B N/A See below. P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 20 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark 4.7.2.1 Parts requiring a fire enclosure With having the following parts: Verdict P Components in primary Components in secondary Components having unenclosed arcing parts at hazardous voltage or energy level Insulated wiring The fire enclosure is required. 4.7.2.2 Parts not requiring a fire enclosure 4.7.3 Materials 4.7.3.1 General Parts mounted on PCB of flammability class V-0 or better. P 4.7.3.2 Materials for fire enclosures The fire enclosure is V-1 or better material. P 4.7.3.3 Materials for components and other parts outside fire enclosures No part outside fire enclosure. 4.7.3.4 Materials for components and other parts inside fire enclosures Internal components except small parts are V-2 or better. 4.7.3.5 Materials for air filter assemblies No air filters provided. N/A 4.7.3.6 Materials used in high-voltage components No high voltage components provided. N/A 5 ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS P 5.1 Touch current and protective conductor current P 5.1.1 General See sub-clauses 5.1.2 to 5.1.6. P 5.1.2 Equipment under test (EUT) EUT has only one mains connection. P 5.1.3 Test circuit Equipment of figure 5A used. P 5.1.4 Application of measuring instrument Using measuring instrument in annex D. P 5.1.5 Test procedure The touch current was measured from mains to DC output connector and to a 100 mm × 200 mm metal foil wrapped on accessible nonconductive parts (plastic enclosure). P 5.1.6 Test measurements See below. P N/A P N/A P Test voltage (V) ...................................................: See appended table 5.1.6. Measured touch current (mA) ..............................: See appended table 5.1.6. Max. allowed touch current (mA) .........................: See appended table 5.1.6. Measured protective conductor current (mA) ......: TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 21 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Max. allowed protective conductor current (mA) .: Verdict 5.1.7 Equipment with touch current exceeding 3.5 mA : Neither stationary permanently connected equipment nor stationary pluggable equipment type B. N/A 5.1.8 Touch currents to and from telecommunication No TNV. networks and cable distribution systems and from telecommunication networks N/A 5.1.8.1 Limitation of the touch current to a telecommunication network and a cable distribution system N/A Test voltage (V) ...................................................: Measured touch current (mA) ..............................: Max. allowed touch current (mA) .........................: 5.1.8.2 Summation of touch currents from telecommunication networks ................................: N/A 5.2 Electric strength 5.2.1 General (see appended table 5.2) P 5.2.2 Test procedure (see appended table 5.2) P 5.3 Abnormal operating and fault conditions 5.3.1 Protection against overload and abnormal operation P P Output overload test, the most unfavorable load test. P (see appended table 5.3) 5.3.2 Motors No motors. 5.3.3 Transformers With the shorted o/p of the transformer, no high temperature of the transformer was recorded. N/A P Results of the short-circuit tests see appended table 5.3 and Annex C. 5.3.4 Functional insulation .............................................: Method c). Test results see appended table 5.3. 5.3.5 Electromechanical components No electromechanical component provided. 5.3.6 Simulation of faults Results see appended table. 5.3.7 Unattended equipment None of the listed components was provided. N/A 5.3.8 Compliance criteria for abnormal operating and fault conditions No fire propagated beyond the equipment. No molten metal was emitted. Electric strength test primary to SELV was passed. P TRF No.:IECEN60950_1B P N/A P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 22 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark 6 CONNECTION TO TELECOMMUNICATION NETWORKS N/A 6.1 Protection of telecommunication network service persons, and users of other equipment connected to the network, from hazards in the equipment N/A 6.1.1 Protection from hazardous voltages N/A 6.1.2 Separation of the telecommunication network from earth N/A 6.1.2.1 Requirements N/A No TNV. Verdict Test voltage (V) ...................................................: Current in the test circuit (mA) ............................: 6.1.2.2 Exclusions.............................................................: N/A 6.2 Protection of equipment users from overvoltages on telecommunication networks N/A 6.2.1 Separation requirements N/A 6.2.2 Electric strength test procedure N/A 6.2.2.1 Impulse test N/A 6.2.2.2 Steady-state test N/A 6.2.2.3 Compliance criteria N/A 6.3 Protection of the telecommunication wiring system from overheating N/A No TNV. Max. output current (A) .........................................: No TNV. Current limiting method ........................................: 7 CONNECTION TO CABLE DISTRIBUTION SYSTEMS N/A 7.1 Protection of cable distribution system service persons, and users of other equipment connected to the system, from hazardous voltages in the equipment N/A 7.2 Protection of equipment users from overvoltages on the cable distribution system N/A 7.3 Insulation between primary circuits and cable distribution systems N/A 7.3.1 General N/A 7.3.2 Voltage surge test N/A 7.3.3 Impulse test N/A A ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE N/A A.1 Flammability test for fire enclosures of movable equipment having a total mass exceeding 18 kg, and of stationary equipment (see 4.7.3.2) N/A A.1.1 Samples................................................................: Wall thickness (mm) .............................................: TRF No.:IECEN60950_1B Not connected to cable distribution system TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 23 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark A.1.2 Conditioning of samples; temperature (°C) ..........: N/A A.1.3 Mounting of samples ............................................: N/A A.1.4 Test flame (see IEC 60695-11-3) N/A Flame A, B, C or D ...............................................: Verdict A.1.5 Test procedure N/A A.1.6 Compliance criteria N/A Sample 1 burning time (s) ....................................: Sample 2 burning time (s) ....................................: Sample 3 burning time (s) ....................................: A.2 Flammability test for fire enclosures of movable equipment having a total mass not exceeding 18 kg, and for material and components located inside fire enclosures (see 4.7.3.2 and 4.7.3.4) A.2.1 Samples, material.................................................: Wall thickness (mm) .............................................: N/A A.2.2 Conditioning of samples N/A A.2.3 Mounting of samples ...........................................: N/A A.2.4 Test flame (see IEC 60695-11-4) N/A Flame A, B or C ...................................................: A.2.5 Test procedure N/A A.2.6 Compliance criteria N/A A.2.7 Sample 1 burning time (s) ....................................: Sample 2 burning time (s) ....................................: Sample 3 burning time (s) ....................................: Alternative test acc. To IEC 60695-2-2, cl. 4 and 8 N/A Sample 1 burning time (s) ....................................: Sample 2 burning time (s) ....................................: Sample 3 burning time (s) ....................................: A.3 Hot flaming oil test (see 4.6.2) N/A A.3.1 Mounting of samples N/A A.3.2 Test procedure N/A A.3.3 Compliance criterion N/A B ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2 and 5.3.2) N/A B.1 General requirements N/A No motor provided. Position ................................................................: Manufacturer ........................................................: Type .....................................................................: TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 24 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Rated values .......................................................: Verdict B.2 Test conditions N/A B.3 Maximum temperatures N/A B.4 Running overload test N/A B.5 Locked-rotor overload test N/A Test duration (days) .............................................: Electric strength test: test voltage (V) ..................: B.6 Running overload test for d.c. motors in secondary circuits N/A B.7 Locked-rotor overload test for d.c. motors in secondary circuits N/A B.7.1 Test procedure N/A B.7.2 Alternative test procedure; test time (h)................: N/A B.7.3 Electric strength test N/A B.8 Test for motors with capacitors N/A B.9 Test for three-phase motors N/A B.10 Test for series motors N/A Operating voltage (V) ...........................................: ANNEX C, TRANSFORMERS (see 1.5.4 and 5.3.3) P Position ................................................................: T1 Manufacturer ........................................................: See appended table 1.5.1 Type .....................................................................: See appended table 1.5.1 Rated values .......................................................: Class B Method of protection .............................................: By protection circuit design. C.1 Overload test See appended table 5.3. P C.2 Insulation See appended table C.2. P C Protection from displacement of windings ............: By insulation tape P D ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS (see 5.1.4) P D.1 Measuring instrument P D.2 Alternative measuring instrument N/A E ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13) N/A F ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES (see 2.10) TRF No.:IECEN60950_1B P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 25 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict G ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM CLEARANCES N/A G.1 Summary of the procedure for determining minimum clearances N/A G.2 Determination of mains transient voltage (V) .......: N/A G.2.1 AC mains supply N/A G.2.2 DC mains supply N/A G.3 Determination of telecommunication network transient voltage (V)..............................................: N/A G.4 Determination of required withstand voltage (V)...: N/A G.5 Measurement of transient levels (V).....................: N/A G.6 Determination of minimum clearances .................: N/A H ANNEX H, IONIZING RADIATION (see 4.3.13) N/A J ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6) N/A Metal used ...........................................................: No risk of corrosion. K ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7) N/A K.1 Making and breaking capacity N/A K.2 Thermostat reliability; operating voltage (V) .........: N/A K.3 Thermostat endurance test; operating voltage (V) .......................................................................: N/A K.4 Temperature limiter endurance; operating voltage (V) ........................................................................: N/A K.5 Thermal cut-out reliability N/A K.6 Stability of operation N/A L ANNEX L, NORMAL LOAD CONDITIONS FOR SOME TYPES OF ELECTRICAL BUSINESS EQUIPMENT (see 1.2.2.1 and 4.5.1) L.1 Typewriters N/A L.2 Adding machines and cash registers N/A L.3 Erasers N/A L.4 Pencil sharpeners N/A L.5 Duplicators and copy machines N/A L.6 Motor-operated files N/A L.7 Other business equipment M ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1) N/A M.1 Introduction N/A TRF No.:IECEN60950_1B P P No telephone signal. TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 26 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict M.2 Method A N/A M.3 Method B N/A M.3.1 Ringing signal N/A M.3.1.1 Frequency (Hz) ....................................................: M.3.1.2 Voltage (V) ...........................................................: M.3.1.3 Cadence; time (s), voltage (V) .............................: M.3.1.4 Single fault current (mA) .......................................: M.3.2 Tripping device and monitoring voltage ................: N/A M.3.2.1 Conditions for use of a tripping device or a monitoring voltage N/A M.3.2.2 Tripping device N/A M.3.2.3 Monitoring voltage (V)...........................................: N/A N ANNEX N, IMPULSE TEST GENERATORS (see 2.10.3.4, 6.2.2.1, 7.3.2 and clause G.5) N/A N.1 ITU-T impulse test generators N/A N.2 IEC 60065 impulse test generator N/A P ANNEX P, NORMATIVE REFERENCES P Q ANNEX Q, BIBLIOGRAPHY P R ANNEX R, EXAMPLES OF REQUIREMENTS FOR QUALITY CONTROL PROGRAMMES N/A R.1 Minimum separation distances for unpopulated coated printed boards (see 2.10.6) N/A R.2 Reduced clearances (see 2.10.3) N/A S ANNEX S, PROCEDURE FOR IMPULSE TESTING (see 6.2.2.3) N/A S.1 Test equipment N/A S.2 Test procedure N/A S.3 Examples of waveforms during impulse testing N/A T ANNEX T, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER (see 1.1.2) N/A U ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED INSULATION (see 2.10.5.4) TRF No.:IECEN60950_1B P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 27 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Approved TIW used. Verdict V ANNEX V, AC POWER DISTRIBUTION SYSTEMS (see 1.6.1) P V.1 Introduction P V.2 TN power distribution systems P V.3 TT power systems V.4 IT power systems W ANNEX W, SUMMATION OF TOUCH CURRENTS P W.1 Touch current from electronic circuits P W.1.2 Earthed circuits N/A W.2 Interconnection of several equipments N/A W.2.1 Isolation N/A W.2.2 Common return, isolated from earth N/A W.2.3 Common return, connected to protective earth N/A X ANNEX X, MAXIMUM HEATING EFFECT IN TRANSFORMER TESTS (see clause C.1) X.1 Determination of maximum input current X.2 Overload test procedure Y ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3) N/A Y.1 Test apparatus .....................................................: N/A Y.2 Mounting of test samples .....................................: N/A Y.3 Carbon-arc light-exposure apparatus ..................: N/A Y.4 Xenon-arc light exposure apparatus ....................: N/A TRF No.:IECEN60950_1B N/A IT-power system for Norway. See table 5.1.6 P P N/A P TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 28 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark EU Group Differences [C], EU Special National Conditions [S], EU A-Deviations [A] (EN 60950-1:2001, Annex ZB and Annex ZC) General C: Delete all the "country" notes in the reference document according to the following list: 1.1.5 Note 2 1.7.2 Note 4 2.2.3 Note 2.3.3 Note 1, 2 2.10.3.1 Note 4 3.2.5.1 Note 2 4.7.3.1 Note 2 6.2.2 Note 7 Note 4 G2.1 Note 1, 2 1.5.8 1.7.12 2.2.4 2.3.4 3.2.1.1 4.3.6 6.1.2.1 6.2.2.1 7.1 Annex H Note 2 Note 2 Note Note 2,3 Note Note 1,2 Note Note 2 Note Note 2 1.6.1 2.6 2.3.2 2.7.1 3.2.3 4.7.2.2 6.1.2.2 6.2.2.2 Verdict P Deleted. N/A Note Note Note 2, 7, 8 Note Note 1, 2 Note Note Note 1.2.4.1 S (DK): Certain types of Class I appliances (see 3.2.1.1) may be provided with a plug not establishing earthing conditions when inserted into Danish socket-outlets. Class II equipment. N/A 1.5.1 A (SE, Ordinance 1990:944 and CH, Ordinance on environmentally hazardous substances SR 814.013, Annex 3.2, Mercury): Add NOTE – Switches containing mercury such as No switch. N/A 1.5.8 S (NO): Due to the IT power system used (see annex V, Fig. V.7), capacitors are required to be rated for the applicable line-to-line voltage (230 V). Class II equipment. N/A 1.7.2 S (FI, NO, SE): CLASS I PLUGGABLE EQUIPMENT intended for connection to other equipment or a network shall, if safety relies on connection to protective earth or if surge suppressors are connected between the network terminals and accessible parts, have a marking stating that the equipment must be connected to an earthed mains socket-outlet. Class II equipment. N/A FI: "Laite on liitettävä suojamaadoituskoskettimilla Class II equipment. varustettuun pistorasiaan" N/A NO: "Apparatet må tilkoples jordet stikkontakt" Class II equipment. N/A SE: "Apparaten skall anslutas till jordat uttag" Class II equipment. N/A A (DK, Heavy Current Regulations): Supply cords Class II equipment. of class I equipment, which is delivered without a plug, must be provided with a visible tag with the following text: N/A thermostats, relays and level controllers are not allowed. TYPE A The marking text in the applicable countries shall be as follows: Vigtigt! Lederen med grøn/gul isolation må kun tilsluttes en klemme mærket eller If essential for the safety of the equipment, the tag must in addition be provided with a diagram which shows the connection of the other conductors, or be provided with the following text: TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 29 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict "For tilslutning af de øvrige ledere, se medfølgende instalationsvejledning." 1.7.5 S (DK): Socket-outlets for providing power to other equipment shall be in accordance with the Heavy Current Regulations, Section 107-2-D1, Standard Sheet DK 1-3a, DK 1-5a or DK 1-7a, when used on Class I equipment. For stationary equipment the socket-outlet shall be in accordance with Standard Sheet DK 1-1b or DK 1-5a. No socket-outlet. N/A 1.7.5 A (DK, Heavy Current Regulations): No socket outlet. CLASS II EQUIPMENT shall not be fitted with socketoutlets for providing power to other equipment. N/A 1.7.12 A (DE, Gesetz über technische Arbeitsmittel Not labour equipment. (Gerätesicherheitsgesetz) [Law on technical rd labour equipment {Equipment safety law}], of 23 rd nd October 1992, Article 3, 3 paragraph, 2 sentence, together with the "Allgemeine Verwaltungsvorschrift zur Durchführung des Zweiten Abschnitts des Gerätesicherheitsgesetzes" [General administrative regulation on the execution of the Second Section of the th Equipment safety law], of 10 January 1996, th article 2, 4 paragraph item 2): Directions for use with rules to prevent certain hazards for (among others) maintenance of the technical labour equipment, also for imported technical labour equipment shall be written in the German language. N/A NOTE: Of this requirement, rules for use even only by service personnel are not exempted. 1.7.15 No batteries. N/A A (DE, Regulation on protection against hazards No radiation. th by X-ray, of 8 January 1987, Article 5 [Operation of X-ray emission source], clauses 1 to 4): a) A licence is required by those who operate an X-ray emission source. b) A licence in accordance with Cl. 1 is not required by those who operate an X-ray emission source on which the electron acceleration voltage does not exceed 20 kV if 1) the local dose rate at a distance of 0,1 m from the surface does not exceed 1 Sv/h and 2) it is adequately indicated on the X-ray emission source that i) X-rays are generated and ii) the electron acceleration voltage must not exceed the maximum value stipulated by the manufacturer or importer. c) A licence in accordance with Cl. 1 is also not required by persons who operate an X-ray emission source on which the electron acceleration voltage exceeds 20 kV if N/A A (CH, Ordinance on environmentally hazardous substances SR 814.013): Annex 4.10 of SR 814.013 applies for batteries. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 30 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 1) the X-ray emission source has been granted a type approval and 2) it is adequately indicated on the X-ray emission source that i) X-rays are generated ii) the device stipulated by the manufacturer or importer guarantees that the maximum permissible local dose rate in accordance with the type approval is not exceeded and iii) the electron acceleration voltage must not exceed the maximum value stipulated by the manufacturer or importer. d) Furthermore, a licence in accordance with Cl. 1 is also not required by persons who operate X-ray emission sources on which the electron acceleration voltage does not exceed 30 kV if 1) the X-rays are generated only by intrinsically safe CRTs complying with Enclosure III, No. 6, 2) the values stipulated in accordance with Enclosure III, No. 6.2 are limited by technical measures and specified in the device and 3) it is adequately indicated on the X-ray emission source that the X-rays generated are adequately screened by the intrinsically safe CRT. 2.2.4 S (NO): Requirements according to this annex, 1.7.2 and 6.1.2.1 apply. Not TNV. N/A 2.3.2 S (NO): Requirements according to this annex, 6.1.2.1 apply. Not TNV. N/A 2.3.3 and 2.3.4 S (NO): Requirements according to this annex, 1.7.2 and 6.1.2.1 apply. Not TNV. N/A 2.6.3.3 S (GB): The current rating of the circuit shall be taken as 13 A, not 16 A. Class II equipment. N/A 2.7.1 C: Replace the subclause as follows: Replaced. P Basic requirements To protect against excessive current, shortcircuits and earth faults in PRIMARY CIRCUITS, protective devices shall be included either as integral parts of the equipment or as parts of the building installation, subject to the following, a), b) and c): a) except as detailed in b) and c), protective devices necessary to comply with the requirements of 5.3 shall be included as parts of the equipment; b) for components in series with the mains input to the equipment such as the supply cord, appliance coupler, r.f.i. filter and switch, shortcircuit and earth fault protection may be provided by protective devices in the building installation; c) it is permitted for PLUGGABLE EQUIPMENT TYPE B or PERMANENTLY CONNECTED EQUIPMENT, to rely on dedicated overcurrent and short-circuit TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 31 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict protection in the building installation, provided that the means of protection, e.g. fuses or circuit breakers, is fully specified in the installation instructions. If reliance is placed on protection in the building installation, the installation instructions shall so state, except that for PLUGGABLE EQUIPMENT TYPE A the building installation shall be regarded as providing protection in accordance with the rating of the wall socket outlet. S (GB): To protect against excessive currents Built-in fusible resistor was and short-circuits in the PRIMARY CIRCUIT OF used as protective device. DIRECT PLUG-IN EQUIPMENT, protective device shall be included as integral parts of the DIRECT PLUGIN EQUIPMENT. P N/A 2.7.2 C: Void. 2.10.2 C: Replace in the first line "(see also 1.4.7)" by "(see also 1.4.8)". Replaced. P 2.10.3.1 S (NO): Due to the IT power distribution system used (see annex V, Fig. V.7), the A.C. MAINS SUPPLY voltage is considered to be equal to the line-to-line voltage and will remain at 230 V in case of a single earth fault Considered. P 3.2.1.1 S (CH): Supply cords of equipment having a RATED CURRENT not exceeding 10 A shall be provided with a plug complying with SEV 1011 or IEC 60884-1 and one of the following dimension sheets: Direct plug-in equipment. N/A SEV 6532-2.1991, Plug type 15, 3P+N+PE 250/400 V, 10 A SEV 6533-2.1991, Plug type 11, L+N 250 V, 10 A SEV 6534-2.1991, Plug type 12, L+N+PE 250 V, 10 A In general, EN 60309 applies for plugs for currents exceeding 10 A. However, a 16 A plug and socket-outlet system is being introduced in Switzerland, the plugs of which are according to the following dimension sheets, published in February 1998: SEV 5932-2.1998, Plug type 25, 3L+N+PE 230/400 V, 16 A SEV 5933-2.1998, Plug type 21, L+N 250 V, 16 A SEV 5934-2.1998, Plug type 23, L+N+PE 250 V, 16 A TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 32 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict S (DK): Supply cords of single-phase equipment having a rated current not exceeding 13 A shall be provided with a plug according to the Heavy Current Regulations, Section 107-2-D1. Direct plug-in equipment. N/A Direct plug-in equipment. N/A Direct plug-in equipment. N/A Direct plug-in equipment. N/A CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which are intended to be used in locations where protection against indirect contact is required according to the wiring rules shall be provided with a plug in accordance with standard sheet DK 2-1a or DK 2-5a. If ply-phase equipment and single-phase equipment having a RATED CURRENT exceeding 13 A is provided with a supply cord with a plug, this plug shall be in accordance with the Heavy Current Regulations, Section 107-2-D1 or EN 60309-2. S (ES): Supply cords of single-phase equipment having a rated current not exceeding 10 A shall be provided with a plug according to UNE 20315:1994. Supply cords of single-phase equipment having a rated current not exceeding 2,5 A shall be provided with a plug according to UNE-EN 50075:1993. CLASS I EQUIPMENT provided with socket-outlets with earth contacts or which are intended to be used in locations where protection against indirect contact is required according to the wiring rules, shall be provided with a plug in accordance with standard UNE 20315:1994. If poly-phase equipment is provided with a supply cord with a plug, this plug shall be in accordance with UNE-EN 60309-2. S (GB): Apparatus which is fitted with a flexible cable or cord and is designed to be connected to a mains socket conforming to BS 1363 by means of that flexible cable or cord and plug, shall be fitted with a ' standard plug'in accordance with Statutory Instrument 1768:1994 – The Plugs and Socket etc. (Safety) Regulations 1994, unless exempted by those regulations. NOTE – ' Standard plug'is defined in SI 1768:1994 and essentially means an approved plug conforming to BS 1363 or an approved conversion plug. S (IE): Apparatus which is fitted with a flexible cable or cord and is designed to be connected to a mains socket conforming to I.S. 411 by means of that flexible cable or cord and plug, shall be fitted with a 13 A plug in accordance with Statutory Instrument 525:1997 – National Standards Authority of Ireland (section 28) (13 A Plugs and Conversion Adaptors for Domestic Use) Regulations 1997. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 33 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 3.2.3 C: Delete Note 1 and in Table 3A, delete the conduit sizes in parentheses. Deleted. N/A 3.2.5.1 C: Replace Replaced. N/A "60245 IEC 53" by "H05 RR-F"; "60227 IEC 52" by "H03 VV-F or H03 VVH2-F"; "60227 IEC 53" by "H05 VV-F or H05 VVH2-F2". In Table 3B, replace the first four lines by the following: Up to and including 6 2) Over 6 up to and including 10 (0,75) 3) Over 10 up to and including 16 (1,0) 1) 0,75 1,0 1,5 In the Conditions applicable to Table 3B delete 1) the words "in some countries" in condition . In Note 1, applicable to Table 3B, delete the second sentence. 3.2.5.1 S (GB): A power supply cord with conductor of 2 1,25 mm is allowed for equipment with a rated current over 10 A and up to and including 13 A. Direct plug-in equipment. N/A 3.3.4 C: In table 3D, delete the fourth line: conductor sizes for 10 to 13 A, and replace with the following: Deleted. N/A N/A "Over 10 up to and including 16 1,5 to 2,5 1,5 to 4" Delete the fifth line: conductor sizes for 13 to 16 A. 3.3.4 S (GB): The range of conductor sizes of flexible cords to be accepted by terminals for equipment with a RATED CURRENT of over 10 A up to and including 13 A is: 2 2 - 1,25 mm to 1,5 mm nominal cross-sectional area. Direct plug-in equipment. 4.3.6 S (GB): The torque test is performed using a socket outlet complying with BS 1363 and the plug part of DIRECT PLUG-IN EQUIPMENT shall be assessed to BS 1363: Part 1, 12.1, 12.2, 12.3, 12.9, 12.11, 12.12, 12.16 and 12.17, except that the test of 12.17 is performed at not less than 125 °C. See IEC 60950-1 and attached BS 1363 test report. P See IEC 60950-1 and attached S (IE): DIRECT PLUG-IN EQUIPMENT is known as BS 1363 test report. plug similar devices. Such devices shall comply with Statutory Instrument 526:1997 – National Standards Authority of Ireland (Section 28) (Electrical plugs, plug similar devices and sockets for domestic use) Regulations, 1997. P 4.3.13.6 C: Add the following note: Added. N/A No TNV. N/A NOTE Attention is drawn to 1999/519/EC: Council Recommendation on the limitation of exposure of the general public to electromagnetic fields 0 Hz to 300 GHz. Standards taking into account this recommendation are currently under development. 6.1.2.1 S (FI, NO, SE): Add the following text between the first and second paragraph: TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 34 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict If this insulation is solid, including insulation forming part of a component, it shall at least consist of either - two layers of thin sheet material, each of which shall pass the electric strength test below, or - one layer having a distance through insulation of at least 0,4 mm, which shall pass the electric strength test below. If this insulation forms part of a semiconductor component (e.g. an optocoupler), there is no distance through insulation requirement for the insulation consisting of an insulating compound completely filling the casing, so that CLEARANCES AND CREEPAGE DISTANCES do not exist, if the component passes the electric strength test in accordance with the compliance clause below and in addition - passes the tests and inspection criteria of 2.10.8 with an electric strength test of 1,5 kV multiplied by 1,6 (the electric strength test of 2.10.7 shall be performed using 1,5 kV), and - is subject to ROUTINGE TESTING for electric strength during manufacturing, using a test voltage of 1,5 kV. It is permitted to bridge this insulation with a capacitor complying with EN 132400:1994, subclass Y2. A capacitor classified Y3 according to EN 132400:1994, may bridge this insulation under the following conditions: - the insulation requirements are satisfied by having a capacitor classified Y3 as defined by EN 132400, which in addition to the Y3 testing, is tested with an impulse test of 2,5 kV defined in EN 60950:2000, 6.2.2.1; - the additional testing shall be performed on all the test specimens as described in EN 132400; - the impulse test of 2,5 kV is to be performed before the endurance test in EN 132400, in the sequence of tests as described in EN 132400. 6.1.2.2 S (FI, NO, SE): The exclusions are applicable for No TNV. PERMANENTLY CONNECTED EQUIPMENT and PLUGGABLE EQUIPMENT TYPE B and equipment intended to be used in a RESTRICTED ACCESS LOCATION where equipotential bonding has been applied, e.g. in a telecommunication centre, and which has provision for a permanently connected PROTECTIVE EARTHING CONDUCTOR and is provided with instructions for the installation of that conductor by a service person. TRF No.:IECEN60950_1B N/A TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 35 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Verdict 7.1 S (FI, NO, SE): Requirements according to this No TNV. annex, 6.1.2.1 and 6.1.2.2 apply with the term TELECOMMUNICATION NETWORK in 6.1.2 being replaced by the term CABLE DISTRIBUTION SYSTEM. N/A G.2.1 S (NO): Due to the IT power distribution system used (see annex V, Fig. V.7), the A.C. MAINS SUPPLY voltage is considered to be equal to the line-to-line voltage, and will remain at 230 V in case of a single earth fault. Annex G not applied for. N/A Annex H C: Replace the last paragraph of this annex by: Replaced. N/A Replaced. N/A At any point 10 cm from the surface of the operator access area, the dose rate shall not exceed 1 µSv/h (0,1 mR/h) (see note). Account is taken of the background level. Replace the notes as follows: NOTE These values appear in Directive 96/29/Euratom. Delete Note 2. Annex P C: Replace the text of this annex by: See annex ZA. Annex Q C: Replace the title of IEC 61032 by "Protection of persons and equipment by enclosures – Probes for verification". P Add the following notes for the standards indicated: IEC 60127 NOTE Harmonized as EN 60127 (Series) (not modified) IEC 60269-2-1 NOTE Harmonized as HD 630.2.1 S4:2000 (modified) IEC 60529 NOTE Harmonized as EN 60529:1991 (not modified) IEC 61032 NOTE Harmonized as EN 61032:1998 (not modified) IEC 61140 NOTE Harmonized as EN 61140:2001 (not modified) ITU-T Recommendation K.31 NOTE in Europe, the suggested document is EN 50083-1. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 36 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test Result – Remark Annex ZA C: NORMATIVE REFERENCES TO INTERNATIONAL PUBLICATIONS WITH THEIR RELEVANT EUROPEAN PUBLICATIONS Verdict P This European Standard incorporates, by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this European Standard only when incorporated in it by amendment or revision. For undated references, the latest edition of the publication referred to applies (including amendments). NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. EN 60065:1998 + corr. June 1999 EN 60073:1996 HD 566 S1:1990 HD 214 S2:1980 HD 611.4.1.S1:1992 1) HD 21 Series 2) HD 22 Series EN 60309 Series EN 60317-43:1997 EN 60320 Series HD 384.3 S2:1995 HD 384.4.41 S2:1996 4) EN 132400:1994 + A2:1998 + A3:1998 + A4:2001 EN 60417-1 HD 625.1 S1:1996 + corr. Nov. 1996 EN 60695-2-2:1994 EN 60695-2-11:2001 EN 60695-11-10:1999 EN 60695-11-20:1999 EN 60730-1:2000 EN 60825-1:1994 + corr. Febr. 1995 + A11:1996 + corr. July 1997 EN 60825-2:2000 EN 60851-3:1996 EN 60851-5:1996 EN 60851-6:1996 EN 60990:1999 EN 61965:2001 EN ISO 178:1996 EN ISO 179 Series EN ISO 180:2000 EN ISO 527 Series EN ISO 4892 Series TRF No.:IECEN60950_1B IEC 60050-151 IEC 60050-195 IEC 60065 (mod):1998 IEC 60073:1996 IEC 60085:1984 IEC 60112:1979 IEC 60216-4-1:1990 IEC 60227 (mod) Series IEC 60245 (mod) Series IEC 60309 Series IEC 60317-43:1997 IEC 60320 (mod) Series IEC 60364-3 (mod):1993 3) IEC 60364-4-41 (mod):1992 IEC 60384-14:1993 IEC 60417-1 IEC 60664-1 (mod):1992 IEC 60695-2-2:1991 IEC 60695-2-11:2000 IEC 60695-2-20:1995 IEC 60695-10-2:1995 IEC 60695-11-3:2000 IEC 60695-11-4:2000 IEC 60695-11-10:1999 IEC 60695-11-20:1999 IEC 60730-1:1999 (mod) IEC 60825-1:1993 IEC 60825-2:2000 IEC 60825-9:1999 IEC 60851-3:1996 IEC 60825-5:1996 IEC 60851-6:1996 IEC 60885-1:1987 IEC 60990:1999 IEC 61058-1:2000 IEC 61965:2000 ISO 178:1993 ISO 179 Series ISO 180:1993 ISO 261:1998 ISO 262:1998 ISO 527 Series ISO 386:1984 ISO 4892 Series TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 37 of 73 IEC 60950-1 / EN 60950-1 Clause Requirement – Test EN ISO 8256:1996 EN ISO 9773:1998 Result – Remark Verdict ISO 7000:1989 ISO 8256:1990 ISO 9772:1994 ISO 9773:1998 ITU-T:1988 Recommendation K.17 ITU-T:2000 Recommendation K.21 1) The HD 21 series is related to, but not directly equivalent with the IEC 60227 series 2) The HD 22 series is related to, but not directly equivalent with the IEC 60245 series 3) IEC 60364-4-41:1992 is superseded by IEC 60364-4-41:2001 4) EN 132400, Sectional Specification: Fixed capacitors for electromagnetic interference suppression and connection to the supply mains (Assessment level D), and its amendments are related to, but not directly equivalent to IEC 60384-14 TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> 1.5.1 Page 38 of 73 TABLE: list of critical components P Object/part no. Manufacturer/ trademark Type/model Transformer Dee Van Enterprise Co., Ltd. 90E5W0005-xxH Pri. Winding (pin 1-A): 90E5W0012-xxH 0.16mmx2px21Ts (pin A-2): (xx can be 00– 0.16mmx126Ts 99) (T1) Technical data Standard Mark(s) of conformity Applicable part of IEC 60950-1 and according to IEC 60085 Tested with appliance Auxiliary primary winding (pin 4-3): 0.16mmx12Ts Shield winding: 0.16mmx2px21Ts Sec. Winding of 90E5W0005-xxH (pin B-C): 0.35mmx14Ts Sec. Winding of 90E5W0012-xxH (pin B-C): 0.20mmx18Ts Class B Triple insulated wire for secondary winding Furukawa Electric Co., Ltd. TEX-E Class B IEC/EN 60950-1 VDE (Alt.) Kuo Kuang SEFU-B Class B IEC/EN 60950-1 VDE (Alt.) Cosmolink TIW-M Class B IEC/EN 60950-1 VDE Fusing resistor (RF1) TZAI YUAN KNF 4.7ohm; 1W -- Tested with appliance (Alt.) VIS Electronics Ltd. FRT 4.7ohm; 1W -- Tested with appliance (Alt.) Jiangsu Xinyang Electronics Ltd. RF10 4.7ohm; 1W -- Tested with appliance (Alt.) Dong Guan Anson Electronics Co., Ltd. FKN 4.7ohm; 1W -- Tested with appliance Diode (D1-D4) Various Various Min. 1A; 800V -- -- Storage Cap. (C1, C2) Various Various 1.0-10µF; Min. 400VDC; 105°C -- -- TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 39 of 73 Common Choke Dee Van (L1) Enterprise Co., Ltd. 30D003330-xxH (xx can be 00– 99) (Alt.) Dee Van Enterprise Co., Ltd. 30D003400-xxH Pin 1-2: (xx can be 00-99) 0.12x400.5Ts, min. 3.0mH, 130°C Y capacitor (CY1) TDK CD Max. 2200pF, IEC/EN 60384AC250V, 25/125/56/B, 14 Y1 type. VDE (Alt.) Murata KX Max. 2200pF, AC250V, 25/125/21, Y1 type. IEC/EN 6038414 VDE (Alt.) Success SE, SB Max. 2200pF, IEC/EN 60384AC250V, 30/125/56/C, 14 Y1 type. VDE (Alt.) JYA-NAY JN Max. 2200pF, IEC/EN 60384AC250V, 25/125/21/C, 14 Y1 type. VDE (Alt.) Jyh Chung JD Max. 2200pF, IEC/EN 60384AC250V, 25/125/21/C, 14 Y1 type. VDE (Alt.) Welson WD Max. 2200pF, IEC/EN 60384AC250V, 25/125/21/C, 14 Y1 type. VDE (Alt) Chyun Fuh CD Max. 2200pF; AC250V; 25/085/21/C, Y1 type IEC/EN 6038414 VDE (Alt) Jin Yang X1Y1 Max. 2200pF; AC250V; 25/085/21/C, Y1 type IEC/EN 6038414 VDE (Alt) Songtian CD Max. 2200pF, IEC/EN 60384AC400V, 25/125/21/C, 14 Y1 type VDE Euro-plug Dee Van Enterprise Co., Ltd. DVE 2.5A; 250VAC EN 50075 TÜV Rheinland (J 2156136) BS plug Dee Van Enterprise Co., Ltd. DVE-UK 0.3A; 250VAC BS 1363 Tested with appliance - Pin sleeve of BS plug Nan Ya plastic 6410G5 Corp. PA66, V-0, 130°C -- UL E130155 (Optional) TRF No.:IECEN60950_1B Pin 1-2: 0.09mmx330Ts; min. 3mH; 130°C -- -- -- -- TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 40 of 73 Australian plug portion Dee Van DVE-AU Enterprise Co., Ltd. AC 250V, 0.3A AS/NZS 3112 Tested with appliance - Pin sleeve for AU plug Dupont FR50 PA66, V-0, 130°C -- UL E41938 Indian plug Dee Van Enterprise Co., Ltd. DVE-IN AC 250V, 0.3A BS 4573 Tested with appliance - Pin holder for Indian plug GE Plastic SE1X PPE+PS, V-1, 105°C -- UL E121562 Enclosure GE Plastic SE1X PPE+PS, V-1, 105°C, thickness: min. 2.0mm, -- UL E121562 Insulation tape Symbio 35660Y/MY130 130°C -- UL E50292 Shrinkable tube Shenzhen Woer RSFR 125°C, VW-1, 600V -- UL E203950 (Alt.) Various Various 125°C, VW-1, 600V -- UL PCB WuZhou WZ-2 V-0 or better; min. 130°C -- UL E170968 (Alt.) Various Various V-0 or better; min. 130°C -- UL Primary lead wire Dong Ju 1007 80°C; min. 24AWG; VW-1. -- UL E189674 (Alt.) Various Various 80°C; min. 24AWG; VW-1 -- UL Output cord Xin Ya Electronics 2468 80°C, 22AWG Min. VW-1 -- UL E170689 (Alt.) Various Various 80°C, 22AWG Min. VW-1 -- UL Output cord (if the part in enclosure covered with heat shrinkable tube) Various Various 60°C, 22AWG Min. VW-1 -- UL Note(s): -1.6.2 TABLE: electrical data (in normal conditions) Fuse # Irated (mA) U (V) P (W) I (mA) P Ifuse (mA) Condition/status Model DSA-5W-05 FEU 050100 RF1 -- 90 7.4 138 138 Rated load at 50 Hz RF1 -- 90 7.4 140 140 Rated load at 60 Hz RF1 200 100 7.4 127 127 Rated load at 50 Hz RF1 200 100 7.4 129 129 Rated load at 60 Hz TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 41 of 73 RF1 200 240 7.9 62 62 Rated load at 50 Hz RF1 200 240 7.9 68 68 Rated load at 60 Hz RF1 -- 264 8.2 60 60 Rated load at 50 Hz RF1 -- 264 8.2 65 65 Rated load at 60 Hz Model DSA-5W-12 FEU 082061 RF1 -- 90 6.6 118 118 Rated load at 50 Hz RF1 -- 90 6.6 119 119 Rated load at 60 Hz RF1 200 100 6.4 108 108 Rated load at 50 Hz RF1 200 100 6.5 110 110 Rated load at 60 Hz RF1 200 240 7.0 53 53 Rated load at 50 Hz RF1 200 240 7.1 54 54 Rated load at 60 Hz RF1 -- 264 7.4 52 52 Rated load at 50 Hz RF1 -- 264 7.3 53 53 Rated load at 60 Hz Model DSA-5W-12 FEU 120041 RF1 -- 90 6.5 122 122 Rated load at 50 Hz RF1 -- 90 6.5 125 125 Rated load at 60 Hz RF1 200 100 6.5 115 115 Rated load at 50 Hz RF1 200 100 6.5 117 117 Rated load at 60 Hz RF1 200 240 7.3 61 61 Rated load at 50 Hz RF1 200 240 7.3 63 63 Rated load at 60 Hz RF1 -- 264 7.6 57 57 Rated load at 50 Hz RF1 -- 264 7.6 60 60 Rated load at 60 Hz Note(s):-2.1.1.5 TABLE: max. V, A, VA test Voltage (rated) (V) P Current (rated) (A) Voltage (max.) (V) Current (max.) (A) VA (max.) (VA) 5.9 1.40 5.2 13.4 0.64 6.0 Model DSA-5W-05 FEU 050100 5.0 1.00 Model DSA-5W-12 FEU 120041 12.0 0.41 Note(s): Test voltage: 264 V Test frequency: 60 Hz 2.1.1.7 Condition TABLE: discharge test τ calculated (s) TRF No.:IECEN60950_1B N/A τ measured (s) t u→ 0V (s) Comments TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 42 of 73 Note(s): -2.2.2 TABLE: Hazardous voltage measurement Transformer P Location max. Voltage V peak V d.c. Pin B-C 48.3 -- Output -- 13.6 Voltage Limitation Component Model DSA-5W-12 FEU 120041 T1 D8 -- Note(s): Test voltage: 240 V Test frequency: 60 Hz 2.2.3 TABLE: SEL voltage measurement Location P Voltage measured (V) Comments Model DSA-5W-12 FEU 120041 Output 0 Short-circuit D8, circuit protected immediately. Note(s): -2.4.2 TABLE: limited current circuit measurement Location Voltage (V) P Current (mA) Freq. (Hz) Limit (mA) Comments 4.8 58k 40.6 -- Model DSA-5W-12 FEU 120041 CY1 9.6 Note(s): 1. Capacitance of CY1: 2200pF 2.5 TABLE: limited power source measurement Limits P Measured Verdict ≤8 0.56 P ≤5*Uoc= 67.0 6.0 P ≤8 0 (unit shut down immediately) P ≤5*Uoc= 67.0 0 (unit shut down immediately) P Model DSA-5W-12 FEU 120041 Uoc = 13.4 V (measured under no load conditions) According to Table 2B (normal condition) current (in A) apparent power (in VA) According to Table 2B (Z1 short-circuited) current (in A) apparent power (in VA) TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 43 of 73 According to Table 2B (C10 short-circuited) current (in A) apparent power (in VA) ≤8 0 (unit shut down immediately) P ≤5*Uoc= 67.0 0 (unit shut down immediately) P ≤8 1.40 P ≤5*Uoc= 29.5 5.2 P ≤8 0 (unit shut down immediately) P ≤5*Uoc= 29.5 0 (unit shut down immediately) P ≤8 0.79 (unit shut down immediately) P ≤5*Uoc= 29.5 0.53 (unit shut down immediately) P Model DSA-5W-05 FEU 050100 Uoc = 5.9 V (measured under no load conditions) According to Table 2B (normal condition) current (in A) apparent power (in VA) According to Table 2B (Z1 short-circuited) current (in A) apparent power (in VA) According to Table 2B (C10 short-circuited) current (in A) apparent power (in VA) Note(s): -2.6.3.3 TABLE: ground continue test Location N/A Resistance measured (mΩ) Comments Note(s): -2.10.2 Table: working voltage measurement Location RMS voltage (V) P Peak voltage (V) Comments Model DSA-5W-12 FEU 120041 T1 pin 1-B 122 364 T1 pin 2-B 216 508 T1 pin 4-B 123 326 T1 pin 3-B 129 333 T1 pin 1-C 125 408 T1 pin 2-C 202 496 T1 pin 4-C 125 339 T1 pin 3-C 129 351 Highest working voltage Note(s): Test voltage: 240 V Test frequency: 60 Hz TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 44 of 73 2.10.3 and TABLE: clearance and creepage distance measurements 2.10.4 P Clearance cl and creepage distance dcr at/of: Up (V) U r.m.s. (V) Required cl (mm) cl (mm) Required dcr (mm) dcr (mm) Unit: primary components (with 10N) → secondary components (with 10N) 508 250 4.4 6.8 5.0 7.8 Unit: core of T1 (with 10N) → secondary components (with 10N) 508 250 4.4 6.6 5.0 6.6 PCB: primary → secondary traces under transformer 508 250 4.4 7.9 5.0 7.9 PCB: primary → secondary traces 508 250 4.4 6.7 5.0 6.7 Unit: primary components → accessible part (outside enclosure) 508 250 4.4 6.5 5.0 6.5 L, N before fusing resistor 420 250 1.5 2.7 2.5 2.7 Two pins of fusing resistor 420 250 1.5 2.7 2.5 2.7 Note(s): 1) Functional insulation shorted, see sub-clause 5.3.4. 2) Reinforced insulation provided between primary and secondary winding. 2.10.5 TABLE: distance through insulation measurements Distance through insulation di at/of: P U r.m.s. (V) Test voltage (V) Required di (mm) di (mm) 250 3000 0.4 2.0 Enclosure material (reinforced insulation) Note(s): 1.) Further details are provided in table 1.5.1. 2.) Test voltages are a.c. 4.5.1 TABLE: temperature rise measurements P test voltage (V) ..................................................... : a): 90 V, 60 Hz b): 264 V, 50 Hz t1 (°C) .................................................................. : 40.0 t2 (°C) .................................................................. : 40.0 T (°C) Rise ∆T of part/at: Test voltage: allowed Tmax (°C) a) b) -- Plug portion 47.5 45.8 -- T1 winding 98.8 97.1 110 T1 core 97.4 94.8 110 Model DSA-5W-05 FEU 050100 TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 45 of 73 Y capacitor CY1 74.9 70.3 85 Linear Filter L1 winding 78.2 83.4 130 PCB under Q1 105.5 107.5 130 PCB under D8 91.3 89.5 130 Electrolytic Capacitor C2 87.0 88.5 105 Primary lead wire 60.0 59.3 80 Output cord 59.4 56.7 80 Enclosure (inside) 64.5 62.3 105 Enclosure (outside) 55.9 53.6 95 Ambient 40.0 40.0 -- Plug portion 45.7 44.8 -- T1 winding 102.3 88.7 110 T1 core 100.1 86.3 110 Y capacitor CY1 76.6 66.6 85 Linear Filter L1 winding 77.1 71.2 130 PCB under Q1 112.5 89.3 130 PCB under D8 88.9 79.7 130 Electrolytic Capacitor C2 97.1 81.5 105 Primary lead wire 60.1 55.8 80 Output cord 65.5 59.5 80 Enclosure (inside) 64.1 57.9 105 Enclosure (outside) 58.1 53.4 95 Ambient 40.0 40.0 -- Plug portion 46.8 46.4 -- T1 winding 98.9 95.7 110 T1 core 96.5 92.1 110 Y capacitor CY1 70.7 67.3 85 Linear Filter L1 winding 75.9 75.7 130 PCB under Q1 105.8 91.6 130 PCB under D8 78.0 76.0 130 Electrolytic Capacitor C2 87.9 80.8 105 Primary lead wire 67.2 68.0 80 Output cord 60.9 59.0 80 Enclosure (inside) 59.5 56.9 105 Enclosure (outside) 55.3 53.1 95 Model DSA-5W-12 FEU 082061 Model DSA-5W-12 FEU 120041 TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 46 of 73 Ambient 40.0 40.0 -- R1 (Ω) R2 (Ω) T (°C) Allowed Tmax (°C) insulation class -- -- -- -- -- -- -- -- -- -- -- -- Temperature rise ∆T of winding: Note(s): The temperatures were measured under worst case normal mode defined in 1.2.2.1 and as described in subclause 1.6.2 and at voltages as described above. With a rated maximum ambient temperature of 40 °C, the maximum temperature rises are calculated as follows: Winding components providing safety isolation: - Class B for T1 → Tmax = 120°C-10°C = 110°C (thermocouple method) Components with maximum absolute temperature of: - Electrolytic Capacitor 105 °C - Y Capacitor 85 °C - PCB 130 °C - L1 winding 130 °C - Output cord 80 °C - Primary lead wire 105 °C - enclosure (inside) 105 °C Operator touchable surface with maximum temperature rise of: - 95°C 4.5.2 TABLE: ball pressure test of thermoplastic parts P allowed impression diameter (mm) ................. : ≤ 2 mm Part Test temperature (°C) Impression diameter (mm) Pin sleeving material for BS plug 125 1.0 Plug holder material for Euro-plug 125 1.0 Plug holder material for Indian plug 125 1.0 Pin sleeving material of Australian plug 125 1.0 PCB 125 1.0 Enclosure 125 1.3 Note(s): 1. The bobbin material of T1 and L1 is phenolic, no test is required. 4.6.1, 4.6.2 Table: enclosure openings P Location Size (mm) Comments Bottom -- No openings Sides -- No openings Top -- No openings Note(s):-TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> 4.7 Page 47 of 73 Table: resistance to fire Part N/A Manufacturer of material Type of material Thickness (mm) Flammability class Note(s): refer to table 1.5.1 for details. 5.1.6 TABLE: touch current measurement Condition L→ terminal A (mA) P N → terminal A (mA) Limit (mA) Comments Model DSA-5W-12 FEU 120041 System ON 0.18 0.18 0.25 Test location: o/p connector System ON 0.01 0.01 0.25 Test location: enclosure wrapped with metal foil Note(s): Test voltage: 264 V Test frequency: 60 Hz 5.2 TABLE: electric strength tests and impulse tests P Test voltage applied between: Test voltage (V) Breakdown Unit: primary circuit to secondary circuit 4240 V d.c. No Unit: primary circuit to accessible enclosure 3000 V a.c. No T1: primary winding to secondary winding 3000 V a.c. No T1: core to secondary winding 3000 V a.c. No Note(s): -5.3 TABLE: fault condition tests P ambient temperature (°C) ................................. : 40°C if not specified model/type of power supply .............................. : -- manufacturer of power supply .......................... : Dee Van rated markings of power supply ....................... : See model list No. Component no. Fault Test voltage (V) Test time Fuse Fuse Result no. current (A) Model DSA-5W-12 FEU 120041 TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> 1 D1 Page 48 of 73 s-c 264 1s RF1 -- With fusible resistor type KNF: RF1 opened immediately, no hazards. With fusible resistor type FKN: RF1 opened immediately, no hazards. With fusible resistor type RF10: RF1 opened immediately, no hazards. With fusible resistor type FRT: RF1 opened immediately, D3 damaged, no hazards. Repeated 10 times each on these fusible resistors and got same result. 2 C1 s-c 264 1s RF1 -- With fusible resistor type KNF: RF1 opened immediately, L1 damaged, no hazards. With fusible resistor type FKN: RF1 opened immediately, no hazards. With fusible resistor type RF10: RF1 opened immediately, no hazards. With fusible resistor type FRT: RF1 opened immediately, D1, D3 damaged, no hazards Repeated 10 times each on these fusible resistors and got same result. 3 C2 s-c 264 1s RF1 -- With fusible resistor type KNF: RF1 opened immediately, L1 damaged, no hazards. With fusible resistor type FKN: RF1 opened immediately, no hazards. With fusible resistor type RF10: RF1 opened immediately, no hazards. With fusible resistor type FRT: RF1 opened immediately, D1, D3 damaged, no hazards Repeated 10 times each on these fusible resistors and got same result. 4 C3 s-c 264 30 min RF1 0.05 Unit work normally, no hazards. 5 D5 s-c 264 30 min RF1 0.06 Unit work normally, no hazards. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> 6 Q1 pin c-e Page 49 of 73 s-c 264 1s RF1 -- With fusible resistor type KNF: RF1 opened immediately, L1 damaged, no hazards. With fusible resistor type FKN: RF1 opened immediately, no hazards. With fusible resistor type RF10: RF1 opened immediately, no hazards. With fusible resistor type FRT: RF1 opened immediately, no hazards. Repeated 10 times each on these fusible resistors and got same result. 7 Q1 pin c-b s-c 264 1s RF1 -- With fusible resistor type KNF: RF1 opened immediately, L1, R9, Q1, Z1, D7 damaged, no hazards. With fusible resistor type FKN: RF1 opened immediately, no hazards. With fusible resistor type RF10: RF1 opened immediately, no hazards. With fusible resistor type FRT: RF1 opened immediately, no hazards Repeated 10 times each on these fusible resistors and got same result. 8 Q1 pin b-e s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. 9 Z1 s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. 10 Z2 s-c 264 30 min RF1 0.06 Unit worked normally, no hazards. 11 D6 s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> 12 D7 Page 50 of 73 s-c 264 1s RF1 -- With fusible resistor type KNF: RF1 opened immediately, L1, R9, Q1, Z1 damaged, no hazards. With fusible resistor type FKN: RF1 opened immediately,Q1 damaged, no hazards. With fusible resistor type RF10: RF1 opened immediately, Q1 damaged, no hazards. With fusible resistor type FRT: RF1 opened immediately, Q1 damaged, no hazards. Repeated 10 times each on these fusible resistors and got same result. 13 C8 s-c 264 1s RF1 -- With fusible resistor type KNF: RF1 opened immediately, L1, R9, Q1, Q2, Z1, D7, D8 damaged, no hazards. With fusible resistor type FKN: RF1 opened immediately, Q1 damaged, no hazards. With fusible resistor type RF10: RF1 opened immediately, Q1 damaged, no hazards. With fusible resistor type FRT: RF1 opened immediately, Q1 damaged, no hazards. Repeated 10 times each on these fusible resistors and got same result. 14 C10 s-c 264 30 min RF1 0.23 Unit shut down immediately, no hazards. 15 T1 pin 3-4 s-c 264 5 min RF1 0.02 Unit shutdown immediately, no hazards. 16 T1 pin B-C s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. 17 D9 s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. 18 C7 s-c 264 5 min RF1 0.01 Unit shutdown immediately, no hazards. 19 Output o-l 264 2h RF1 0.07 The output overload to 0.64A, T1 coil = 100°C at ambient temperature 23°C, no hazards. 20 Output s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. 264 1.8 h RF1 0.08 The output overload to 1.40A, T1 coil = 102°C at ambient temperature 23°C, no hazards. Model DSA-5W-05 FEU 050100 21 Output TRF No.:IECEN60950_1B o-l TRF originator: SGS Fimko www.tuv.com <16011089 001> 22 Output Page 51 of 73 s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. Model DSA-5W-12 FEU 082061 23 Output o-l 264 2h RF1 0.06 The output overload to 0.82A, T1 coil = 102°C at ambient temperature 24°C, no hazards. 24 Output s-c 264 5 min RF1 0.01 Unit shut down immediately, no hazards. Note(s): - In fault column, where s-c=short-circuited, o-l= over-loaded, o-c= open-circuited. C.2 Safety isolation transformer P Construction details: Transformer part name: T1 Manufacturer: see table 1.5.1 Type: see table 1.5.1 Recurring peak voltage 508 Vpeak Required clearance for reinforced insulation (from table 2H and 2J) 4.4 mm Effective voltage rms 250 Vrms Required creepage distance for reinforced insulation (from table 2L) 5.0 mm Measured min. creepage distance Location inside (mm) outside (mm) prim-sec TIW used 8.6 core-sec TIW used 8.6 prim-core -- -- prim-sec TIW used 8.6 core-sec TIW used 8.6 prim-core -- -- Measured min. clearances Construction: Concentric windings on EF-16 size bobbin. 2 layer of insulation tape between primary (enamelled copper wire) and secondary windings (triple insulation wire), 2 layers on outer winding. Winding ends additionally fixed with tape, outer winding is secondary. Pin numbers TRF No.:IECEN60950_1B TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 52 of 73 Prim. 1→2; 4→3 Sec. B→C Bobbin Material Hitachi, Phenolic, type CP-J-8800 Thickness 1.0 mm Electric strength test With AC 3000V after humidity treatment Result TRF No.:IECEN60950_1B Pass TRF originator: SGS Fimko www.tuv.com <16011089 001> Page 53 of 73 National Differences Clause Result – Remark Requirement − Test APPENDIX Australian National Differences according to CB Bulletin No. 112A, December 2006 (AS/NZS 60950.1:2003) Verdict P (IEC Publication 60950-1:2001) EXPLANATION FOR ABBREVIATIONS P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right. Annex ZZ Variations 1.2 Between the definitions for "Person, service" and "Range, rated frequency" insert the following: Potential ignition source 1.2.12.15 Inserted. P 1.2.12.201 After the definition of 1.2.12.15, add the following: Added. P 1.2.12.201 Potential ignition source: Possible fault which can start a fire if the opencircuit voltage measured across an interruption or faulty contact exceeds a value of 50 V (peak) a.c. or d.c. and the product of the peak value of this voltage and the measured r.m.s. current under normal operating conditions exceeds 15 VA. Such a faulty contact or interruption in an electrical connection includes those which may occur in conductive patterns on printed boards. NOTE 201: An electronic protection circuit may be used to prevent such a fault from becoming a potential ignition source. NOTE 202: This definition is from AS/NZS 60065:2003. 1.5.1 Add the following to the end of first paragraph: Added. P "or the relevant Australian/New Zealand Standard." 1.5.2 Add the following to the end of first and third dash Added and see plug test items: report. P "or the relevant Australian/New Zealand Standard." 2.1 Delete the Note. Deleted P 3.2.3 Delete Note 2. Deleted N/A 3.2.5 Modify Table 3B as follows: Replaced. N/A Rated current of equipment A Nominal crosssectional 2 area mm AWG or kcmil (cross-sectional 2 area in mm ) see note 2 Over 0.2 up to and including 3 0.5 1) 18 [0.8] Over 3 up to and including 7.5 0.75 16 [1.3] Over 7.5 up to and including 10 (0.75) 1.00 2) 16 [1.3] Australian National Differences according to CB Bulletin No. CB Bulletin No. 112A, December 2006 www.tuv.com <16011089 001> Page 54 of 73 National Differences Clause Result – Remark Requirement − Test Over 10 up to and including 16 3) (1.0) 1.5 Verdict 14 [2] Replace footnote 1) with the following: 1) This nominal cross-sectional area is only allowed for Class II appliances if the length of the power supply cord, measured between the point where the cord, or cord guard, enters the appliances, and the entry to the plug does not exceed 2 m (0.5 mm² three-core supply flexible cords are not permitted; see AS/NZS 3191). Delete Note 1. 4.3.6 Replace paragraph three with: Replaced. N/A Equipment with a plug portion, suitable for insertion into a 10 A 3-pin flat-pin socket-outlet complying with AS/NZS 3112, shall comply with the requirements in AS/NZS 3112 for equipment with integral pins for insertion into socket-outlets. 4.3.13.5 Add the following to the end of the first paragraph: Added. P ", or AS/NZS 2211.1" 4.7 Add the following paragraph: Added. P Added. P For alternative tests refer to clause 4.7.201. 4.7.201 Add the following after clause 4.7.3.6: 4.7.201 Resistance to fire - Alternative tests 4.7.201.1 General Enclosure, PCB, bobbin, pin Parts of non-metallic material shall be resistant to sleeving ignition and spread of fire. This requirement does not apply to decorative trims, knobs and other parts unlikely to be ignited or to propagate flames originating from inside the apparatus, or the following: (a) Components that are contained in an enclosure having a flammability category of FV-0 according to AS/NSZ 4695.707 and having openings only for the connecting wires filling the openings completely, and for the ventilation not exceeding 1 mm in width regardless of the length. (b) The following parts which would contribute negligible fuel to a fire: - small mechanical parts, the mass of which does not exceed 4 g, such as mounting parts, gears, cams, belts and bearings; - small electrical components, such as capacitors with a volume not exceeding 3 1750 mm , integrated circuits, transistors and optocoupler packages, if these components are mounted on material flammability category FV-1 or better according to AS/NZS Australian National Differences according to CB Bulletin No. CB Bulletin No. 112A, December 2006 P www.tuv.com <16011089 001> Page 55 of 73 National Differences Clause Requirement − Test Result – Remark Verdict 4695.707 NOTE - In considering how to minimize propagation of fire and what “small parts” are, account should be taken of the cumulative effect of small parts adjacent to each other for the possible effect of propagating fire from one part to another. Compliance is checked by tests of 4.7.201.2, 4.7.201.3, 4.7.201.4 and 4.7.201.5. For the base materials of printed boards, compliance is checked by the test of 4.7.201.5. The tests shall be carried out on parts of nonmetallic material, which have been removed from the apparatus. When the glow-wire test is carried out, the parts shall be placed in the same orientation, as they would be in normal use. These tests are not carried out on internal wiring. 4.7.201.2 Parts of non-metallic material are subjected to glow wire test of AS/NZS 4695.2.11, which is carried out at 550 °C. Enclosure P PCB, bobbin, Pin sleeve P Parts for which the glow-wire test cannot be carried out, such as those made of soft or foamy material, shall meet the requirements specified in ISO 9772 for category FH-3 material. The glowwire test shall be not carried out on parts of materials classified at least FH-3 according to ISO 9772 provided that the sample was not thicker than the relevant part. 4.7.201.3 Testing of insulating materials Parts of insulating materials supporting potential ignition sources shall be subject to the glow-wire test of AN/NZS 4695.2.11, which is carried out at 750 °C. The test shall be also carried out on other parts of insulating material which are within a distance of 3 mm of the connection. NOTE - Contacts in components such as switch contacts are considered to be connections. For parts, which withstand the glow-wire test but produce a flame, other parts above the connection within the envelope of a vertical cylinder having a diameter of 20 mm and a height of 50 mm shall be subjected to the needle-flame test. However, parts shielded by a barrier which meets the needle-flame test shall not be tested. The needle-flame test shall be made in accordance with AS/NZS 4695.2.2 with the following modifications: 5 Severities Replace with: Australian National Differences according to CB Bulletin No. CB Bulletin No. 112A, December 2006 www.tuv.com <16011089 001> Page 56 of 73 National Differences Clause Requirement − Test Result – Remark Verdict The duration of application of the test flame shall be 30 s 1 s. 8 Test procedure 8.2 Modification: Replace the first sentence with: The specimen shall be arranged so that the flame can be applied to a vertical or horizontal edge as shown in the examples of figure 1. 8.4 Modification: The first paragraph does not apply. Addition: If possible, the flame shall be applied at least 10 mm from a corner. 8.5 Replacement: The test shall be made on one specimen. If the specimen does not withstand the test, the test may be repeated on two further specimens, both of which shall then withstand the test. 10 Evaluation of test results Replace with: The duration of burning (tb) shall not exceed 30 s. However, for printed circuit boards, it shall not exceed 15 s. The needle-flame test shall not be carried out on parts of material classified as V-0 or V-1 according to IEC 60695-11-10, provided that the sample tested was not thicker than the relevant part. 4.7.201.4 Testing in the event of non-extinguishing material Added. If parts, other than enclosures, do not withstand the glow-wire tests of 4.7.201.3, by failure to extinguish within 30 s after the removal of the glow-wire tip, the needle-flame test detailed in 4.7.201.3 is made on all parts of non-metallic material which are within a distance of 50 mm or which are likely to be impinged upon by flame during the tests of 4.7.201.3. Parts shielded by a separate barrier which meets the needle-flame test need not to be tested. NOTE 1 - If the enclosure does not withstand the glow-wire test the equipment is considered to have failed to meet the requirement of clause 4.7.201 without the need for consequential testing. NOTE 2 - If other parts do not withstand the glowwire test due to ignition of the tissue paper and if this indicates that burring or glowing particles can Australian National Differences according to CB Bulletin No. CB Bulletin No. 112A, December 2006 N/A www.tuv.com <16011089 001> Page 57 of 73 National Differences Clause Requirement − Test Result – Remark Verdict fall onto an external surface underneath the equipment, the equipment is considered to have failed to meet the requirement of clause 4.7.201 without the need for consequential testing. NOTE 3 - Parts likely to be impinged upon by the flame are considered to be those within the envelope of a vertical cylinder having a radius of 10 mm and a height equal to the height of the flame, positioned above the point of the material supporting in contact with or in close proximity to connections. 4.7.201.5 Testing of printed boards Added. The base material of printed boards is subjected to needle-flame test to Clause 4.7.201.3. The flame is applied to the edge of the board where the heat sink effect is lowest when the board is positioned as in normal use. The flame shall not be applied to an edge, consisting of broken perforations, unless the edge is less than 3 mm for a potential ignition source. The test is not carried out if the – - Printed board does not carry any potential ignition source; - Base material of printed boards, on which the available apparent power at a connection exceeds 15 VA operating at a voltage exceeding 50 V and equal or less than 400 V (peak) a.c. or d.c. under normal operating conditions, is of flammability category FV-1 or better according to AS/NZS 4695.707, or the printed boards are protected by an enclosure meeting the flammability category FV-0 according to AS/NZS 4695.707, or made of metal, having openings only for connecting wires which fill the opening completely, or - Base material of printed boards, on which the available apparatus power at a connection exceeds 15 VA operating at a voltage exceeding 400 V (peak) a.c. or d.c. under normal operating conditions, and base material printed boards supporting spark gaps which provide protection against overvoltages, is of flammability category FV-0 according to AS/NSZ 4695.707 or the printed boards are contained in a metal enclosure, having openings only for connecting wires fill the openings completely. Compliance is determined using the smallest thickness of the material. NOTE - Available apparent power is the maximum apparent power, which can be drawn from the supplying circuit through a resistive load whose value is chosen to maximise the apparent power for more than 2 min when the circuit Australian National Differences according to CB Bulletin No. CB Bulletin No. 112A, December 2006 N/A www.tuv.com <16011089 001> Page 58 of 73 National Differences Clause Result – Remark Requirement − Test Verdict supplied is disconnected. 6.2.2 Add the following after the first paragraph: No TNV. N/A No TNV. N/A No TNV. N/A In Australia (this variation does not apply in New Zealand), compliance with 6.2.2 is checked by the tests of both 6.2.2.1 and 6.2.2.2. Delete the note. 6.2.2.1 Delete Note 2. Add the following after the first paragraph: In Australia (this variation does not apply in New Zealand), the electrical separation is subjected to 10 impulses of alternating polarity, using the impulse test generator of annex N for 10/700 µs impulses. The interval between successive impulses is 60 s and the initial voltage, Uc, is: - for 6.2.1 a): 7.0 kV for hand-held telephones and for headsets and 2.5 kV for other equipment; and - for 6.2.1b) and 6.2.1c): 1.5 kV. NOTE 201 - The 7 kV impulse simulates lightning surges on typical rural and semi-rural network lines. NOTE 202 – The 2.5 kV impulse for 6.2.1a) was chosen to ensure adequacy of the insulation concerned and does not necessarily simulate likely overvoltages. 6.2.2.2 Delete the note. Add the following after the second paragraph: In Australia (this variation does not apply in New Zealand), the a.c. test voltage is: - for 6.2.1a): 3 kV; and - for 6.2.1b) and 6.2.1c): 1.5 kV. NOTE 201 – Where there are capacitors across the insulation under test, it is recommended that d.c. test voltages are used. NOTE 202 – The 3 kV and 1.5 kV values have been determined considering the low frequency induced voltages from the power supply distribution system. Annex P Add the following Normative References to Annex Added. P: IEC 60065, Audio, Video and similar electronic apparatus - Safety requirements AS/NZS 3112, Approval and test specification Plugs and socket-outlets AS/NZS 3191, Approval and test specification - Australian National Differences according to CB Bulletin No. CB Bulletin No. 112A, December 2006 P www.tuv.com <16011089 001> Page 59 of 73 National Differences Clause Requirement − Test Result – Remark Electric flexible cords AS/NZS 4695.707, Fire hazard testing of electrotechnical products - Methods of test for the determination of the flammability of solid electrical insulating materials when exposed to an igniting source Australian National Differences according to CB Bulletin No. CB Bulletin No. 112A, December 2006 Verdict www.tuv.com <16011089 001> Page 60 of 73 EN 50075 (Partial) Clause Requirement − Test Result – Remark Verdict 7 Dimensions P Plug shall comply with Standard Sheet 1 P Between two pins (pin base) 18.0 – 19.2 mm 18.4 mm P Between two pins (pin top) 17.0 – 18.0 mm 17.3 mm P Diameter of pin (metallic part) 4± 4.0 mm P Diameter of pin (pin base) max. 4.0 mm 3.8 mm P Diameter of pin (middle part) max. 3.8 mm 3.5 mm P 0.06 mm ± 0.5 mm 19.4 mm P + 1.0 mm 10.3 mm P Pin length 19 Length of pin except metal part 10 Shape of pin top Round shape P ± 0.7 mm 35.5 mm P 0.7 mm 13.8 mm P 26.4 mm P Length of plug base 35.3 Width of plug base 13.7± 0.5 Diagonal dimension of plug base <26.1± mm within a distance of 18mm 0.5 <26.1± mm 26.3 mm Note: Only the dimensions of Euro-plug have been measured and recorded since it is a certified plug (see table 1.5.1). www.tuv.com <16011089 001> Page 61 of 73 BS 1363 (Partial) Clause Requirement − Test Result – Remark Verdict 12 Construction P 12.1 Disposition of the pins is same as fig. 4 P 12.2 Plugs shall comply with fig. 4 P Disposition of pins P Between E and left plane max. 25.37 mm 24.30 mm P Between E and right plane max. 25.37 mm 24.32 mm P Between E and L 11.05~11.18mm 11.08 mm P Between E and N 11.05~11.18mm 11.08 mm P Between L or N and top plane max. 34.6mm 27.74 mm P Between E and L, N 22.10~22.36mm 22.30 mm P Radius of top right corner min. 15mm 15.50 mm P Radius of top left corner min. 15mm 15.50 mm P Shape of earth pin P Length 22.23~23.23mm 22.60 mm P Width 7.80~8.05mm 8.00 mm P Thickness 3.90~4.05mm 4.00 mm P Length of chamfer 1.35~1.85mm 1.68 mm P Angle of chamfer 58°~62° 59 ° P Shape of L and N pin P Length 17.2~18.2mm 17.80 mm P Width 6.22~6.48mm 6.30 mm P Thickness 3.90~4.05mm 4.00 mm P Length of insulating material max. 9.5mm 9.36 mm P Length of conductive material max. 9.2mm 8.44 mm P Length of chamfer 1.35~1.85mm 1.56 mm P Angle of chamfer 58°~62° 59 ° P Maintenance of these dimensions not rely on the terminal screws P The plug portion should enter the gauge fully with a Complied, sample was entered force less than 10N was applied to the centre of into the gauge fully with a force the sample at right angle. of 10N. P 12.3 No part of a line or neutral pin shall be less than 9,5mm from the periphery of the plug measured along the engagement surface. Complied, both line and neutral pin are measured larger that 9.5mm P 12.9 Plug pins were constructed of brass Complied. P www.tuv.com <16011089 001> Page 62 of 73 BS 1363 (Partial) Clause Requirement − Test Result – Remark 12.9.1 Exposed surface of plug pins were smooth and free from burrs or sharp edges and other irregularities, which could cause damage or excessive wear to sockets or shutters. Complied. P 12.9.4 The adaptor plug pins were tested as specified in the standard. Complied. After being subjected to a forced of 1100N, the pin portion could fit the relevant gauge. P 12.9.5 The adaptor plug pins were tested as specified in the standard. Complied. After being subjected to 5000 insertions and withdraws, the shutters of the socket-outlet can operate satisfactorily and the socket contact is safely shielded. P 12.9.6 Each pin of the adaptor was subjected to a torque of 1Nm for 60s as specified in the standard. Complied. After the test, the pin portion could fit the relevant gauge. P 12.11 The adaptors were tested as specified in the standard. After being placed in an oven at 70°C for 1 hour, each pin of the samples was subjected for 60 sec. to a pull of 100N in the oven. Complied. After the above test, no plug pin was detached and the plug pins could fit the relevant gauge. P 12.12 The degree of flexibility of mounting of the plug pins was checked according to 12.12.1 Complied. During the test, no declination was observed to the plug pins (limit: Max. 3° 30’). P 12.16 Line and neutral plug pin shall be fitted with insulating sleeves. The dimensions of the pin and sleeve shall fall within the specific limit. Complied. Both line and neutral pins were fitted with insulating sleeves. P 12.17.1 Plug pin sleeve shall be compliance with 12.17.2 to Complied. 12.17.4 P 12.17.2 Electric strength test applied between the metal part of plug pin and the sleeve (1250±30V) Complied. No breakdown and flashover occur. P 12.17.3 Abrasion test for plug pin sleeve Complied. After the test, the sleeves showed no damage that impaired further use and could satisfy the electric strength test in 12.17.2 P Complied. After the tests, the thicknesses of sleeve of plug pins (line and neutral pins) remaining at the impression point were reduced by less than 5%. P The plug pin sleeves were subjected to 20000 movements of abrasion as specified in the standard. 12.17.4 Resistance to deformation The plug pins with sleeves were placed in a heating cabinet at 200°C and tested according to the standard for 120min. Notes: clause 12.4, 12.5, 12.6, 12.7, 12.8, 12.9.2, 12.9.3, 12.10, 12.13, 12.14, 12.15 were not applicable. Verdict www.tuv.com <16011089 001> Page 63 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test J1 Scope This Appendix applies to only the plug portion of equipment with integral pins and shall be read in conjunction with section 2 contained in the body of this standard. Where the term ‘plug’ is used in section 2 it shall be taken to mean the plug portion of equipment with integral pins. Result – Remark Verdict P Plug portion with integrated pins P J2 Requirements for plug portion P J2.1 definition P J2.2 requirments J2.2.1 Plug pins of plug portions Material for pins J2.2.2 See below. P P Copper alloy containing 62% copper. P Assembly of pins P Form of pin P Insulation of plug pin P Ratings and dimensions for low voltage plug portions Comply with 10A 250V two-pin plug. General P P Compliance with dimensional requirements of Figure 2.1 See attached dimension table. J2.2.3 Internal connections for plug portions No earthing pin. N/A J2.2.4 Arrangement of earthing connections for plug portions No earthing pin. N/A J2.2.5 Configuration of plug portions P J2.2.6.1 General P J2.2.6.2 High voltage test (3112.2.13.3) P The plug shall withstand without failure an a. c. voltage of the value indicated in Table 2.3, applied between the parts set our in Items (a) and (c) of Clause 2.13.2 for 1 min in each case. P The plug shall further withstand, without failure, a voltage of 3500 V a. c. applied between the parts set out in Items (b) and (d) of Clause 2.13.2 for 1 min in each case. P The insulation of insulated pin plugs shall withstand a voltage of 1 250V a. c. for 1 min applied in accordance with Clause 2.13.2(e). P Mechanical strength of pin tests P J2.2.6.3 P www.tuv.com <16011089 001> Page 64 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test J2.2.6.3.1 Tumbling barrel test (3112.2.13.7.1) P The tumbling barrel test is applied to determine the mechanical strength of the plug pins. P Three samples which have not been subjected to any previous test are tested to the requirements of Clause 2.13.7 however, the test is modified for plug portions of equipment with integral pins as follows: P A sample of equipment with integral pins is dropped – P Weight: 75g. a) 500 times if the mass of the specimen does not exceed 250 g. The pins being straightened 500 times. after 100 drops and at the completion of the test to pass through the appropriate gauge of Figure A1, B1 or F1; and P b) 250 times if the mass of the specimen exceeds 250 g. The pins being straightened after 25 drops and at the completion of the test to pass through the appropriate gauge of Figure A1, B1 or F1 J2.2.6.3.2 Result – Remark Verdict N/A Pin bending test P The pins of the plug portion of three samples not subjected to any previous tests shall be tested for compliance with the pin bending test of clause 2.13.7.2. P All flat-pins of plugs rated up to and including 15 A shall be subjected to a pin bending test. P www.tuv.com <16011089 001> Page 65 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test Three sample plugs not subjected to any previous tests shall be tested as follows: Pins of assembled plugs shall be tested by clamping the plug in a rigid holding block and applying a bending force, as shown in Figure 2.8, to the pin under test. The pins shall be straight at the beginning of the test. If there is any doubt about the straightness of the pin, it shall be checked by the appropriate plug gauge shown in Appendices A, B or F. The point of application of the force shall be 14 ±0.5 mm from the face of the plug. The direction of the force shall be along a line parallel to the face of the plug. Active and neutral pins shall be forced towards the centroid of the plug and then back to the starting point. On the first sample plug, any earth pin shall be forced but in one direction only and then back to the starting point.On the second sample plug, any earth pin shall be forced in the opposite direction to that used for testing the first sample plug. On the third sample plug, any earth pin shall be forced in the direction that gave the least favourable result during testing of the first two sample plugs. NOTE: This is intended to simulate damage that may occur when a plug is walked on and bent pins are straightened. The distance moved from the point of application shall be 7.5+/-0.3 mm, and then the pin shall be forced back to the starting point. Any ’spring-back'is ignored NOTE: ’Spring-back'means that the pin is allowed to move back to a position less than the travel distance, when the force is removed. The travel from the starting point, to the end point (7,5 mm), and back to the starting point is one cycle (i.e. one cycle is two separate movements). The speed of deflections shall be a maximum of 50 mm/s, without intentional delay between consecutive movements within each cycle. The interval between successive cycles shall be a minimum of 10 s. The duration of one cycle shall be a maximum of 60 s. The pins shall be tested for 20 complete cycles. After the tests the pins shall be inspected with normal or corrected to normal vision. Result – Remark Verdict P www.tuv.com <16011089 001> Page 66 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test Result – Remark The pin shall not be broken off. Verdict P NOTE: Cracking of the pin, less than full thickness, is not deemed to be broken off. If in doubt pins shall be disassembled from the plug and any insulation removed, NOTE: In some cases the break may be below the face of the plug or the insulation may hold the broken pieces together, retaining electrical contact. J2.2.6.4 Temperature rise test (3112.2.13.8) The test current have been specified and tested with the integral adaptor. 2.13.8 Temperature rise test Plugs shall be so constructed that they comply with the following temperature rise test: P P Non-rewireable plugs P a) Non-rewireable plugs are tested as delivered (specially prepared sample with access to terminals for temperature measurement). b) Rewireable plugs are fitted with polyvinyl chloride flexible cords with conductors having the minimum crosssectional area specified in the manufacturers instructions. The terminal screws or nuts are tightened with a No screws or nuts used. torque equal to two-thirds of that specified in test No.5. N/A NOTE: To ensure normal cooling of the terminals, the conductors connected to plugs should have a length of at least 1 m. Direct plug-in equipment. N/A Direct plug-in equipment. The fixed socket outlet shall be mounted in an appropriate metal-wall box installed in a draught free position, and fitted with PVC insulated conductors at least 2.5 m long, having nominal cross-sectional areas as shown in Table 3.4. N/A Direct plug-in equipment. N/A The test socket shall consist of a fixed socket outlet of a type complying with this Standard. NOTE: In the case of a dispute, the test should be repeated using a new socket outlet. The cables supplying the socket outlet shall be enclosed for a distance of 1 m in conduit terminated at the wall box. The plug is inserted into the socket outlet and an alternating current of 1.1 times rated current is passed for 1 h. P www.tuv.com <16011089 001> Page 67 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test Result – Remark The temperature of the flexible cord terminal is Direct plug-in equipment. determined by means of melting particles, colour changing indicators or thermocouples, so chosen and positioned that they have negligible effect on the temperature being determined. J2.2.6.5 Verdict N/A The temperature rise of the terminals shall not exceed 45 K. P Securement of pins (3112.2.13.9) P Movement of pins (2.13.9.1) P Plugs shall be tested for pin movement by clamping the pin or pins not under test in a rigid holding block positioned 5 ±0.5 mm from the plug face and applying a force of 18±1 N to the pin under test. The design of the block shall be such that the pin under test shall not come into contact with the block during the test. P Except for non-rewireable plugs, the test shall be carried out without a cord attached to the plug, and with the terminal screws loosened sufficiently to allow a 1mm2 conductor to be connected. N/A The plug and test equipment shall be preconditioned at a temperature of 40±1ºC for 1 h, without the test force applied. Throughout the test, all parts of the plug and test equipment shall be maintained at this temperature. P For all plugs, the point of application of the force of the plug along the pins, and the direction of the force shall be- P a) in both directions along the line perpendicular to the plane of the pin, and passing through the centre of the pin; and b) in that plane in both directions along a line at right angles to that specified in Item(a). Over a period of 10 s, the force shall be gradually applied to each of the pins in the manner prescribed in Items (a) and (b), maintained at its maximum value for 10 s, and then released. The deflection of the pins shall be measured along the line of force relative to the face of the rigid holding block during the period when the force is applied. The maximum deflection shall not exceed 2.0 mm. P www.tuv.com <16011089 001> Page 68 of 73 AS/NZS 3112 (Partial) Clause J2.2.6.6 Requirement − Test Result – Remark Verdict Following the test on all pins of a plug conforming to Figure 2.1, any distortion 5 min after the completion of the test on the last pin shall be such that it will not prevent the plug from being inserted in the appropriate standard gauges shown in Appendix A, Appendix B and Appendix F without the application of undue force. P For other types of plugs, any distortion after 5 min shall be such as will not prevent the plug being inserted into an appropriate socket-outlet without the application of undue force. N/A Fixing of pins (2.13.9.2) P A separate sample of a plug shall be heated to a temperature of 50±20ºC for 1 h and maintained at that temperature during the whole of tests, including the 5 min period after removal of the test load. P The plug shall be held firmly in such a manner that there will be no undue squeezing or distortion of the body, and the means of holding shall not assist in maintaining the pins in their original position, P Each pin, in turn, shall have applied to it a force which, over a period of 10 s, shall be increased steadily to 60+0.6N and held at this value for 10 min. P Two tests on each pin shall be conducted, one with the direction of force along the length of the pin towards the body of the plug, and the other with the direction of force along the length o f the pin away from the body. P The attachment of pins shall be considered inadequate if any pin is displaced relative to the adjacent material of the body by more than 2.4 mm at any time during these tests, or if any pin fails to return to within 0.8 mm of its nominal length specified in Figure 2.1 within 5 min of the removal of the test force, P Additional tests for plugs with insulated pins (3112.2.13.13) P 2.13.13 Additional tests on the insulation material of insulated pin plugs P 2.13.13.1 General P www.tuv.com <16011089 001> Page 69 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test Result – Remark Verdict The material of the pin-insulation shall be resistant to the stresses to which it may be subjected at the high temperature likely to occur in conditions approaching the bad connection conditions and at low temperatures in particular conditions of service. P Compliance shall be checked by the tests of Clause 2.13.13.2 to 2.13.13.5 P (a) Pressure test at high temperature (2.13.13.2) P A specimen of one insulated pin only shall be subjected to the following test by means of the apparatus shown in Figure 2.2. This apparatus shall have a blade having a round shape with a diameter of 6 mm and a thickness of 0.7 mm. P The specimen shall be placed in position as shown in the Figure 2.5 and a force of 2.5 N shall be applied through the blade to specimen. P The apparatus, with the specimen in position, shall be maintained for 2 h in a heating cabinet at a temperature of 160+5ºC. The specimen shall then be removed from the apparatus and within 10 s, cooled by immersion in cold water. P The thickness of the insulation shall be measured immediately at the point of impression. P The thickness within the area of the impression shall be not less than 50% of the thickness measured before the test. The impression no more than 50% P Visual inspection shall be made and no cracks on the insulation material shall be visible with normal, or corrected to normal, vision without additional magnification, and the dimension of the insulating material shall not have changed below the minimum size shown in Figure 2.4. P (b) Static damp heat test (2.13.13.3) P An insulated pin plug shall be subjected to two damp heat cycles in accordance with IEC 60068-2-30. Db (12+12 h cycle), 95% relative humidity, lower temperature 25+3ºC and upper temperature 40ºC. P www.tuv.com <16011089 001> Page 70 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test After this treatment and after recovery to room temperature, the specimen shall be subjected to- Result – Remark Verdict P a) the insulation resistance test in accordance with CLAUSE 2.13.2(E); b) high voltage test in accordance with Clause 2.13.3 and; c) abrasion test in accordance with Clause 2.13.13.6. NOTE: At the manufacturer’s option, the same sample may be used for this test and the low temperature test (see Clause 2.13.13.4) and a single abrasion test may be done. (c) Low temperature test (2.13.13.4) P An insulated pin plug shall be maintained at – 15+2ºC for at least 24 h and returned to room temperature. P The specimen shall be subjected to – P a) the insulation resistance test in accordance with Clause 2.13.2(e); b) high voltage test in accordance with Clause 2.13.3 and; c) abrasion test in accordance with Clause 2.13.13.6. NOTE: At the manufacturer’s option, the same sample may be used for this test and the static damp heat test (see Clause 2.13.13.3) and a single abrasion test may be done. (d) Impact test at low temperature (2.13.13.5) P A specimen of one insulated pin only shall be subjected to an impact test by means of the apparatus shown in Figure 2.6. The mass of the falling weight shall be 100+1 g. P The apparatus, on a sponge rubber pad 40 mm thick, together with the specimen, shall be maintained at –15+20ºC for at least 24 h. P At the end of this period, the specimen shall be placed in position, as shown in Figure 2.6, and the falling weight shall be allowed to fall from a height of 100mm. Four impacts shall be applied successively to the same specimen, rotating it through 90º between impacts. P www.tuv.com <16011089 001> Page 71 of 73 AS/NZS 3112 (Partial) Clause Requirement − Test Result – Remark After the test the specimen shall be allowed to return to room temperature and then examined, No cracks of the insulating material shall be visible with normal, or corrected to normal, vision without additional magnification. Verdict P NOTE: The cooling period of 14 h includes the time necessary to cool down the apparatus. J2.2.6.7 (e) Abrasion test (2.13.13.6) P An insulated pin of an insulated pin plug shall be subjected to the following test by means of an apparatus as shown in Figure 2.7. P The test apparatus comprises a horizontally disposed beam, which shall be pivoted about its centre point. A short length of steel wire, 1 mm in diameter and bent into a U-shape, the base of the U being straight, shall be rigidly attached, at both ends, to one end of the beam, so that the straight part projects below the beam and shall be parallel to the axis of the beam pivot. P The plug shall be held in a suitable clamp in such a position that the straight part of the steel wire rests on the major axis face of the plug pin, at right angles to it. The pin shall slope downwards at an angle of 10º to the horizontal. P The beam shall be loaded so that the wire exerts a force of 4 N on the pin. P The plug shall be moved backwards and forwards in horizontal direction in the plane of the axis of the beam, so that the wire rubs along the pin. The length of the pin thus abraded shall be approximately 9 mm, of which approximately 7 mm shall be over the insulation. P The number of movement s shall be 20 000 (10 000 in each direction) and the rate of operation shall be 30 movements per min. P After the test, the pins shall show no damage which may affect safety or impair the further use of the plug, in particular, the insulating sleeve shall not have punctured or rucked up. P Equipment with integral pins intended to be supported by the contacts of a socket-outlet Torque: 0.03 Nm P www.tuv.com <16011089 001> Page 72 of 73 AS/NZS 3112 (Partial) Clause Result – Remark Requirement − Test G Verdict H K I J M L N O P Symbol Requirement Measured (mm) Symbol (mm) Requirement Measured (mm) (mm) A 6.2 – 6.5 6.3 K 60 ° 60° C 1.58 – 1.78 1.60 L > 8.6 10.5 D 7.92 7.96 M R 19.0 – 21.0 20.7 F 16.66 – 17.46 17.20 N < R 1.0 0.9 G < 21.9 or > 27.0 20.7 P 8.2 – 9.2 8.3 H < 21.9 or > 27.0 20.7 S 0.90 0.10 0.98 I < 21.9 or > 27.0 20.7 V 6.0 6.0 J < 21.9 or > 27.0 20.7 R 0.35 0.05 0.32 www.tuv.com <16011089 001> Page 73 of 73 BS 4573 (Partial) Clause Result – Remark Requirement − Test Verdict Plug dimensions (BS 4573: 1970) Location Requirement Measured Verdict A: Diameter of plug pins 5.08±0.03 mm 5.07 mm P B: Length of projection of plug pins 15.87+1.0 mm 15.9 mm P C: Length of radiuses portion at the end of plug pins 1.57+0.25 mm 1.65 mm P D: Nominal distance the centers of plug pins 16.66±0.03 mm 16.67 mm P Note: Each of the above values is the average value of three samples. Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 1 Picture 2 Page 1 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 3 European plug pins were fixed into enclosure by a screw. Picture 4 Page 2 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 5 Picture 6 Page 3 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy UK plug pins were molded into enclosure. Picture 7 Picture 8 Page 4 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Australian plug pins were molded into enclosure. Picture 9 Picture 10 Page 5 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 11 Picture 12 Page 6 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 13 The plug holder of Indian plug is fixed into enclosure by screw. Picture 14 Page 7 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Y capacitor is optional Picture 15 The cr and cl between two pins of fusing resistor is 2.7mm. The cr and cl between primary and secondary trace on PCB is 6.7mm. Picture 16 Page 8 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 17 Picture 18 Page 9 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 19 Picture 20 Page 10 of 11 Report Number: 16011089 001 Model: DSA-5W-a Ab xy; DSA-5W-a Fb xy Picture 21 Picture 22 Page 11 of 11
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Create Date : 0000:01:01 00:00:00Z Modify Date : 2007:11:20 11:41:42+08:00 Page Count : 86 Has XFA : No Producer : GNU Ghostscript 7.06 Creation Date : 0-01-01T00:00:00Z Author : gzpsqwq Mod Date : 2007:11:20 11:41:42+08:00 Metadata Date : 2007:11:20 11:41:42+08:00 Title : Microsoft Word - 16011089.001.doc Creator : gzpsqwqEXIF Metadata provided by EXIF.tools