Schaltschrank-Kühlgerät
Cooling unit
Climatiseur
Koelaggregat
Kylaggregat
Condizionatori per armadi
di comando
Refrigerador para armarios

SK 3302.xxx
SK 3302.3xx
SK 3303.xxx
SK 3304.xxx
SK 3305.xxx

Montage-, Installations- und Bedienungsanleitung
Assembly and operating instructions
Manuel d’installation et de maintenance
Montage- en bedieningshandleiding
Montage- och hanteringsanvisning
Istruzioni di montaggio e funzionamento
Instrucciones de montaje

SK 3328.xxx
SK 3329.xxx
SK 3332.xxx
SK 3361.xxx
SK 3366.xxx

Contents
1 Notes on documentation. . . . . . . . . . 4
1.1
1.2
1.3
1.4

Associated documents. . . . . . . . . . . . . . . .
CE labelling . . . . . . . . . . . . . . . . . . . . . . . . .
Retention of documents. . . . . . . . . . . . . . .
Symbols used . . . . . . . . . . . . . . . . . . . . . . .

4
4
4
4

2 Safety instructions. . . . . . . . . . . . . . . 4
3 Device description . . . . . . . . . . . . . . . 5
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.1.6
3.1.7
3.1.8
3.2
3.3

Functional description . . . . . . . . . . . . . . . .
How it works . . . . . . . . . . . . . . . . . . . . . . . . .
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bus mode (e-Comfort controller only). . . . . .
Safety equipment . . . . . . . . . . . . . . . . . . . . .
Condensation . . . . . . . . . . . . . . . . . . . . . . . .
Filter mats . . . . . . . . . . . . . . . . . . . . . . . . . . .
Door limit switch . . . . . . . . . . . . . . . . . . . . . .
Additional interface X3 . . . . . . . . . . . . . . . . .
Proper usage . . . . . . . . . . . . . . . . . . . . . . . .
Scope of supply . . . . . . . . . . . . . . . . . . . . .

5
5
5
5
6
6
6
6
7
7
7

4 Assembly and connection . . . . . . . . 7
4.1
4.2
4.2.1
4.2.2
4.3
4.3.1
4.3.2
4.3.3
4.3.4
4.4
4.5
4.5.1
4.5.2
4.5.3
4.5.4
4.5.5
4.5.6
4.6
4.6.1

4.6.2
4.6.3
4.6.4
4.7
4.7.1
4.7.2
4.7.3

Choosing the installation site . . . . . . . . . . 7
Assembly instructions . . . . . . . . . . . . . . . . 7
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Layout of the electronic components
in the enclosure . . . . . . . . . . . . . . . . . . . . . . 8
Fitting the cooling unit . . . . . . . . . . . . . . . . 8
Cutting out on the enclosure. . . . . . . . . . . . . 9
External mounting of the cooling unit . . . . . . 9
Partial internal mounting
of the cooling unit . . . . . . . . . . . . . . . . . . . . . 9
Full internal mounting of the cooling unit . . 11
Connecting the condensate discharge. . 12
Notes on electrical installation . . . . . . . . 12
Connection data . . . . . . . . . . . . . . . . . . . . . 12
Overvoltage protection
and supply line load . . . . . . . . . . . . . . . . . . 12
Three-phase devices . . . . . . . . . . . . . . . . . 12
Door limit switch . . . . . . . . . . . . . . . . . . . . . 13
Notes on the flicker standard . . . . . . . . . . . 13
Potential equalisation . . . . . . . . . . . . . . . . . 13
Carrying out the electrical installation . . 13
Bus connection
(only in conjunction with several units with
an e-Comfort controller) . . . . . . . . . . . . . . . 13
Connection X3 for serial interface. . . . . . . . 13
Installing external transformers. . . . . . . . . . 13
Installing the power supply. . . . . . . . . . . . . 14
Finalising assembly . . . . . . . . . . . . . . . . . 20
Installing the filter media . . . . . . . . . . . . . . 20
Fitting the cooling unit. . . . . . . . . . . . . . . . . 20
Setting the filter mat monitor
(only with e-Comfort controller). . . . . . . . . . 20

Rittal cooling unit assembly and operating instructions

5 Commissioning . . . . . . . . . . . . . . . . 20
6 Operation . . . . . . . . . . . . . . . . . . . . . 21
6.1
6.1.1
6.1.2
6.1.3
6.1.4
6.1.5
6.2
6.2.1
6.2.2
6.2.3
6.2.4
6.2.5
6.2.6
6.2.7

Control using the Basic controller . . . . .
Properties . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating and error display. . . . . . . . . . . .
Test mode for the Basic controller . . . . . . .
Setting the temperature . . . . . . . . . . . . . . .
Resetting the Basic controller . . . . . . . . . .
Control using the e-Comfort controller .
Properties . . . . . . . . . . . . . . . . . . . . . . . . . .
Eco-mode. . . . . . . . . . . . . . . . . . . . . . . . . .
Launching test mode . . . . . . . . . . . . . . . . .
General programming information . . . . . . .
Editable parameters. . . . . . . . . . . . . . . . . .
Programming overview . . . . . . . . . . . . . . .
Defining system messages
for evaluation . . . . . . . . . . . . . . . . . . . . . . .
6.2.8 Setting the master-slave identifier . . . . . . .
6.2.9 Evaluating system messages. . . . . . . . . . .
6.2.10 Resetting the e-Comfort controller . . . . . . .

21
21
22
23
23
23
23
23
24
24
24
25
26
27
28
28
30

7 Inspection and maintenance. . . . . . 30
7.1
7.1.1
7.1.2

General . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Compressed air cleaning
SK 3304.xxx, SK 3305.xxx . . . . . . . . . . . . . 30
Compressed air cleaning
SK 3328.xxx, SK 3329.xxx, SK 3332.xxx . . 34

8 Storage and disposal. . . . . . . . . . . . 39
9 Technical specifications . . . . . . . . . 39
10 List of spare parts . . . . . . . . . . . . . . 43
11 Appendix:
Cut-out and hole sizes . . . . . . . . . . . 47
11.1
11.2
11.3

Dimensions for external mounting . . . . . 47
Dimensions for partial
internal mounting . . . . . . . . . . . . . . . . . . . 48
Dimensions for full internal mounting . . 49

3

EN

1 Notes on documentation
1

EN

Notes on documentation

These assembly instructions are aimed at tradespersons who are familiar with assembly and installation
of the cooling unit, and at trained specialists who are
familiar with operation of the cooling unit.

1.1 Associated documents
There are two sets of instructions for the unit types
described here:
– Assembly and installation instructions enclosed
with the unit in the form of a paper document
– Assembly, installation and operating instructions
enclosed with the unit in the form of a PDF file
(Adobe Acrobat) on CD-ROM
We cannot accept any liability for damage associated with failure to observe these instructions. Where
applicable, the instructions for any accessories used
also apply.

1.2 CE labelling
The declaration of conformity is supplied with the unit
as a separate document.

1.3 Retention of documents
These instructions and all associated documents
constitute an integral part of the product. They must
be given to the plant operator. The plant operator is
responsible for storage of the documents so they are
readily available when needed.

1.4 Symbols used
Please observe the following safety instructions and
other notes in this guide:
Symbol for an instructed action:
• The bullet point indicates that you should perform
an action.
Safety and other instructions:

2

Safety instructions

Please observe the following general safety instructions when assembling and operating the unit:
– Assembly, installation and servicing may only be
performed by properly trained specialists.
– Screw the enclosure to the floor to prevent it from
tipping over when the cooling unit is installed.
– Do not obstruct the air inlet and air outlet of the
cooling unit inside and outside the enclosure
(see also section 4.2.2).
– To ensure problem-free opening and closing of
the enclosure door, use a ride-up door roller (refer
to the accessories in the Rittal Catalogue).
This raises the door slightly and balances out the
weight of the cooling unit, to prevent buckling of
the door and associated seal problems.
– The heat loss of the components installed in the
enclosure must not exceed the specific useful
cooling output of the cooling unit.
– When transporting the enclosure with the cooling
unit externally mounted, always use an additional
shipping brace to support the cooling unit.
– The cooling unit must always be transported in an
upright position.
– Use only original spare parts and accessories.
– Do not make any changes to the cooling unit other
than those described in these instructions or associated instructions.
– Risk of burn injuries! For cooling units with automatic condensate evaporation, the surface of the
thermal element will get very hot during operation,
and will remain so for some time afterwards.
– The mains connector of the cooling unit must only
be connected and disconnected with the system
de-energised. Connect the pre-fuse specified on
the rating plate.

Danger!
Immediate danger to life and limb!

Caution!
Potential threat to the product
and its environment.
Note:
Useful information
and special features.

4

Rittal cooling unit assembly and operating instructions

3 Device description
3

Device description

Depending on the model chosen, your cooling unit
may vary in appearance from the illustrations contained in these instructions. However, the functions
are identical in principle.

into the hermetically sealed cooling circuit provides
effective protection against moisture, acid, dirt
particles, and foreign bodies within the cooling
circuit.
Condenser (3)
PSAH

8
9

1

14

2

10

3

pressureoperated
switch
Compressor
(2)

Condenser fan
Filter dryer (5)

External circuit
Internal circuit

Temperature
control

4
5

11

6

12

Evaporator coil (1)
Expansion valve (4)
Evaporator fan

13

Fig. 2:

7

15
16

Fig. 1:

Device description

Legend
1
Blind rivet nut
2
Evaporator fan
3
Electrical wiring plan
4
X2 master-slave connection
5
X3 optional serial interface
6
X1 terminal strip
7
Air outlet hole
8
Front half of the enclosure
9
Rear half of the enclosure
10 Louvred grille for air outlet
11 Display
12 Infill panel
13 Louvred grille for air inlet
14 Rating plate
15 Condensate discharge
16 Dispatch bag

3.1 Functional description
Enclosure cooling units are designed to dissipate
heat from enclosures by cooling the air inside the
enclosure and so protect the temperature-sensitive
components. They are built into the side or rear
panel or into the door of the enclosure.
3.1.1 How it works
The cooling unit (compression refrigeration system)
is comprised of four main components (cf. Fig. 2):
the evaporator (1), the coolant compressor (2), the
condenser (3), and the control or expansion valve
(4), which are connected by suitable pipework. This
circuit is filled with a readily boiling substance, the
refrigerant. Coolant R134a (CH2FCF3) is chlorinefree. Its ozone destruction potential is 0, making it
very eco-friendly. A filter dryer (5) which is integrated
Rittal cooling unit assembly and operating instructions

Cooling circuit

In the evaporator coil (1), the liquid coolant is converted to a gaseous state. The energy needed for
this purpose is taken from the enclosure air in the
form of heat, which has the effect of cooling the
enclosure air. In the compressor (2), the coolant is
heavily compressed, so that it achieves a higher
temperature inside the condenser (3) than the ambient air. This means that excess heat may be emitted
to the ambient air via the surface of the condenser,
as a result of which the temperature of the coolant
drops and it is converted back into liquid. It is reinjected into the evaporator coil via a thermostatic
expansion valve (4), which causes it to cool down
further, and is then once again able to absorb the
energy from the enclosure air in the evaporator coil.
The whole cycle begins again.
3.1.2 Control
Rittal enclosure cooling units are fitted with a controller for setting the functions of the cooling unit.
Depending on the design, this is either a Basic controller (display of the operating status via LED) or a
e-Comfort controller (display plus extended functions, see chapter “6 Operation”, page 21).
3.1.3 Bus mode (e-Comfort controller only)
The serial unit interface X2 allows you to create a bus
connection with up to ten cooling units using the
master-slave cable (shielded, four-wire cable, Model
No. SK 3124.100). This allows you to implement the
following functions:
– Parallel unit control (the cooling units in the network
can be switched on and off simultaneously)
– Parallel door status message (“door open”)
– Parallel collective fault message
Data is exchanged via the master-slave connection.
During commissioning, assign an address to each
unit that also includes the identifier “master” or
“slave”.

5

EN

3 Device description
EN

3.1.4 Safety equipment
– In the cooling cycle, the cooling unit has a tested
pressure-operated switch to EN 12 263 which is
set to maximum PS (admissible pressure); this
operates via an automatic reset device whenever
the pressure drops again.
– Temperature monitoring prevents the evaporator
coil from icing over. If there is a risk of icing, the
compressor switches itself off and automatically
switches itself back on again at higher temperatures.
– The refrigerant compressor and the fans are
equipped with thermal winding shields to protect
against excess current and excess temperatures.
– In order to allow a reduction of pressure inside the
compressor and hence a safe restart, once it has
been switched off (e.g. upon reaching the set temperature via the door limit switch function or via deenergising), the device will switch back on with a
delay of 180 seconds.
– The device has floating contacts on the connection
pins (terminals 3 – 5), via which system messages
from the device may be polled, e.g. using a PLC
(1x change-over contact Basic controller, 2 x normally open contacts e-Comfort controller).
3.1.5 Condensation
At high levels of humidity and low temperatures inside the enclosure, condensation may form on the
evaporator coil.
The cooling units (except SK 3302.xxx, SK 3303.xxx
and SK 3361.xxx) have automatic, electric condensate evaporation. The thermal component used for
this purpose is based on self-regulating PTC technology. Condensate arising on the evaporator coil
is collected in a tank in the external circuit of the cooling unit, and partially evaporated via the airflow.
When the water level rises, the water enters the PTC
thermal component and is evaporated (through-flow
heater principle). The water vapour streams out of
the cooling unit with the airflow from the external fan.
The PTC thermal component is permanently connected and has no switchpoint. It is protected
against short-circuits with miniature fuses (F1.1,
F1.2). If the fuse has tripped, any condensation is
drained off via the safety overflow.
For unit types SK 3302.xxx, SK 3303.xxx and
SK 3361.xxx, the condensation is routed downwards
out of the unit via a drain pipe on the evaporator coil
divider panel. For this purpose, a hose must be connected to the condensate nozzle (see “4.4 Connecting the condensate drain”, page 12). External condensate evaporators are available as accessories
for these unit types (refer also to the accessories in
the Rittal Catalogue).

6

3.1.6 Filter mats
The cooling unit condenser is finished all over with a
dirt-repelling, easy-to-clean RiNano coating. In many
cases, therefore, the use of filter media is unnecessary, particularly in the case of dry dusts.
For dry, coarse dust and lint in the ambient air, we
recommend installing an additional PU foam filter
mat (available as an accessory) in the cooling unit.
Depending on the incidence of dust, you will need
to replace the filter from time to time.
For air containing oil condensation, we recommend
the use of metal filters (also available as an accessory). These may be cleaned with suitable detergents
and reused.
Function of the filter mat monitor:
Dirt on the filter mat is automatically determined by
measuring the temperature difference in the external
circuit of the cooling unit. As the level of filter mat soiling rises, the temperature difference will increase.
The nominal value of the temperature difference in
the external circuit adapts automatically to the relevant operating points in the performance diagrams.
Hence there is no need to readjust the nominal value
for different operating points of the cooling unit.
3.1.7 Door limit switch
The cooling unit may be operated with a floating door
limit switch connected. The door limit switch is not included with the supply (available as an accessory,
Model No. PS 4127.010).
The door limit switch function causes the fans and
the compressor in the cooling unit to be switched off
after approximately 15 seconds when the enclosure
door is opened (contacts 1 and 2 closed). This prevents the formation of condensation inside the enclosure while the enclosure door is open. In order to
prevent damage to the unit, it is equipped with an
ON delay: The evaporator fan cuts back in with a delay of approximately 15 seconds after the door has
been closed, while the condenser fan and compressor switch on after approximately 3 minutes.
Note:
– No external voltage must be applied to
the door contacts (terminals 1 and 2).
– For Basic controller cooling units with
230/115 V and 400 V/2-phase connection, the evaporator fan remains operational even with the door open.

Rittal cooling unit assembly and operating instructions

4 Assembly and connection
3.1.8 Additional interface X3
Note:
The electrical signals at the interface are of
an extra-low voltage (not extra-low safety
voltages to EN 60 335).
An additional interface card may be connected to
the 9-pole SUB-D connector X3 in order to incorporate the cooling unit into higher-level monitoring
systems (available as an accessory, interface card
Model No. SK 324.200).

3.2 Proper usage
Rittal enclosure cooling units were developed and
designed in accordance with the state-of-the-art and
the recognised rules governing technical safety.
Nevertheless, if used improperly, they may pose a
threat to life and limb or cause damage to property.
The unit is only intended for cooling enclosures. Any
other use is deemed improper. The manufacturer will
not be liable for any damages caused as a result of
improper use, or for incorrect assembly, installation
or use. All risk is borne solely by the user.
Proper usage also includes the observation of all
valid documents and compliance with the inspection
and servicing conditions.

3.3 Scope of supply
The unit is supplied in a packaging unit in a fully
assembled state.
Please check the delivery for completeness:
Qty.

Description

1

Enclosure cooling unit

1
1
1

Dispatch bag:
– Assembly and installation instructions
– Assembly, installation and operating
instructions on CD-ROM
– Safety instructions
– Self-adhesive tape
– Connector X1
– Self-tapping screws
– Declaration of conformity
– Nuts, washers

1
1
1
4 – 10
1
1

4

Assembly and connection

EN

4.1 Choosing the installation site
When choosing the installation site for the enclosure,
please observe the following:
– The site for the enclosure, and hence the arrangement of the cooling unit, must be carefully selected
so as to ensure good ventilation (distances between units and distances between the unit and the
wall must be at least 200 mm in each case).
– The cooling unit must be installed and operated in
a vertical position (maximum deviation: 2°).
– The site must be free from excessive dirt and
moisture.
– The ambient temperature must not exceed 55°C.
– It must be possible to fit a condensate discharge
(see “4.4 Connecting the condensate discharge”,
page 12).
– The mains connection data as stated on the rating
plate of the unit must be guaranteed.

4.2 Assembly instructions
4.2.1 General
– Check the packaging carefully for signs of damage.
Traces of oil on damaged packaging are an indication of refrigerant loss and leakages. Packaging
damage may be the cause of a subsequent functional failure.
– The enclosure must be sealed on all sides (IP 54).
Increased condensation will occur if the enclosure
is not airtight.
– In order to avoid excessive condensation inside
the enclosure, we recommend installing a door
limit switch (e.g. PS 4127.010) which deactivates
the cooling unit when the enclosure door is opened
(see “3.1.7 Door limit switch”, page 6).

Drilling template

Tab. 1: Scope of supply

Rittal cooling unit assembly and operating instructions

7

4 Assembly and connection
EN

4.2.2 Layout of the electronic components
in the enclosure
Caution!
Risk of condensation!
When arranging the components inside
the enclosure, please ensure that the
cold airflow from the cooling unit is not
directed at active components. Please
also ensure that the cold airflow is not
directed at the warm exhaust airflow
from active components such as converters. This may lead to an air shortcircuit and therefore prevent adequate
climate control, or may even cause the
cooling unit’s internal safety devices to
cease cooling operation.

x

Fig. 4:

Air circulation inside the enclosure

4.3 Fitting the cooling unit
The enclosure cooling unit may optionally be externally mounted on the enclosure (1), partially internally mounted (2) or fully internally mounted (3):

1

Fig. 3:

3

Never direct the cold airflow at active components

Air diversion components are available as accessories – please refer to the Rittal catalogue.
It is important to ensure even air circulation inside the
enclosure. Under no circumstances should air inlet
and outlet openings be obstructed, otherwise the
cooling performance of the unit will be reduced.
Ensure the distance “x” (see Fig. 4) from electronic
components and other installed enclosures so that
the required air circulation is not obstructed and prevented.

8

2

Fig. 5:

Installation method

To this end, cut the side panel or door of the enclosure as per the drilling template included with the
supply, and drill the relevant holes.
Note:
Units of type SK 3302.xxx can only be either
externally mounted or fully internally mounted.
Units of type SK 3332.xxx can only be either
externally mounted or partially internally
mounted.
For mounting the units SK 3328.xxx,
SK 3329.xxx and SK 3332.xxx in the TS side
panel or rear panel, we recommend the use
of enclosure panel fasteners TS 8800.071
(see Rittal Catalogue).

Rittal cooling unit assembly and operating instructions

4 Assembly and connection
4.3.1 Cutting out on the enclosure
• Stick the supplied drilling template onto the side
panel or door of the enclosure using adhesive
tape.
There are dimensioning lines on the drilling template
to suit the various installation options for your cooling
unit.
• Using the dimension drawings (see Appendix),
identify the valid lines and dimensions for your
installation type on the drilling template.
Risk of injury!
Carefully deburr all drilled holes and
cut-outs to prevent injuries caused by
sharp edges.
• Mark, drill and deburr the holes.
• Make the cut-outs including the line width as per
the drilling template.
Deburr the cut-outs.

EN

Fig. 8:

Secure the cooling unit
(SK 3302.1xx “external mounting” only)

4.3.3 Partial internal mounting of the cooling unit
• Carefully remove the louvred grille and, where
applicable, the infill panel, from the enclosure by
pulling forwards.
• Carefully disconnect the connector from the rear of
the display and gently push it inwards through the
cable gland.

4.3.2 External mounting of the cooling unit
• Cut the supplied sealing tape to the correct length
and stick it carefully along the back of the unit so
that no gaps are left at the joints.

Fig. 6:

Attach the sealing tape

• Screw the supplied grub screws into the blind nuts
on the rear of the unit.
• Secure the unit using the supplied washers and
nuts.

Fig. 9:

Remove the louvred grille & disconnect the display

Risk of damage!
Stability of the cooling unit is only
guaranteed in its assembled state.
Brace the rear enclosure half to prevent
it from falling over before removing the
front enclosure half.

Fig. 7:

Secure the cooling unit
(all models except SK 3302.1xx)

Rittal cooling unit assembly and operating instructions

• Loosen the four nuts on the front enclosure half and
pull the enclosure forwards by approx. 5 cm.
• Loosen the flat-pin connectors of the PE conductor
between the two enclosure halves.
• Disconnect the fan connection.
• Remove the front enclosure tray completely.

9

4 Assembly and connection
EN

Fig. 10:

Remove the cover

• Remove the four spacer bolts.
• Cut the supplied sealing tape to the correct length
and stick it carefully along the inside of the rear
enclosure half so that no gaps are left at the connection points.

Fig. 11:

Fig. 12:

Secure the cooling unit

• Connect the fan connector and PE conductor.
• Mount the front enclosure tray using the washers
and nuts.

Attach the sealing tape

• Push the rear enclosure half into the mounting cutout and secure it with the four spacer bolts.
• Push the display cable through the cable gland of
the front enclosure half.
Fig. 13:

Connect the display connector

• Carefully connect the display connector.
• Push the louvred grille and, where applicable,
the infill panel, onto the enclosure.

10

Rittal cooling unit assembly and operating instructions

4 Assembly and connection
4.3.4 Full internal mounting of the cooling unit
• Carefully remove the louvred grille and the infill
panel from the enclosure by pulling forwards.
• Carefully disconnect the connector from the rear of
the display.

Only for SK 3302.xxx:
• Before installing, remove the four screws as shown.

4x

Fig. 16: Only for SK 3302.xxx: Remove the four screws

Fig. 14:

Remove the louvred grille and disconnect
the display

• Cut the supplied sealing tape to the correct length
and stick it carefully along the front enclosure half
so that no gaps are left at the connection points.

Fig. 17:
Fig. 15:

Attach the sealing tape

• Loosen the four nuts and washers from the front
enclosure half.
• Push the unit into the mounting cut-out from the
inside of the enclosure, and secure it to the enclosure from the outside using the washers and
nuts.

Rittal cooling unit assembly and operating instructions

Secure the cooling unit

• Where necessary, additionally secure the unit
using the supplied mounting plates as shown in
Fig. 17.
• Carefully connect the display connector.
• Push the louvred grille and, where applicable,
the infill panel, onto the enclosure.

11

EN

4 Assembly and connection
4.4 Connecting the condensate discharge

EN

Unit types SK 3302.xxx, SK 3303.xxx and
SK 3361.xxx support the installation of a condensate
discharge hose (Ø 1/2˝).
The condensate discharge
– must be laid with a suitable and constant gradient
(no siphoning)
– must be laid without kinks
– must not have a reduced cross-section if extended.
The condensate hose is available as an accessory
(refer also to Accessories in the Rittal Catalogue).

Fig. 18:

Connecting the condensate discharge

• Connect a suitable hose to the condensate nozzle
and secure using a hose clip.
• Lay the condensate hose into a pay-off or into the
external condensate evaporator (refer to accessories in the Rittal Catalogue).

4.5 Notes on electrical installation
When performing the electrical installation, it is important to observe all valid national and regional regulations as well as the provisions of the responsible
power supply company. Electrical installation must
only be carried out by a qualified electrician who is
responsible for compliance with the existing standards and regulations.
4.5.1 Connection data
– The connected voltage and frequency must
correspond to the values stated on the rating plate.
– The cooling unit must be connected to the mains
via an all-pin isolating device, which ensures at
least 3 mm contact opening when switched off.
– No additional temperature control may be connected upstream of the unit at the supply end.
– Install the pre-fuse specified on the rating plate
to protect the cable and equipment from shortcircuits.
– The mains connection must ensure low-noise
potential equalisation.

12

4.5.2 Overvoltage protection and supply line
load
– The unit does not have its own overvoltage protection. Measures must be taken by the operator at
the supply end to ensure effective lightning and
overvoltage protection. The mains voltage must
not exceed a tolerance of ±10%.
– In accordance with IEC 61 000-3-11, the unit is
intended solely for use at sites with a continuous
current-carrying capacity (incoming mains power
supply) of more than 100 A per phase and with
a supply voltage of 400/230 V. If necessary, the
power supply company must be consulted to
ensure that the continuous current-carrying capacity at the point of connection to the public grid is
sufficient for connection of such a unit.
– The fans and compressors in single- and threephase units are intrinsically safe (thermal winding
protection). The same also applies to the transformer versions of types SK 3304.510, SK 3305.510,
SK 3328.510 and SK 3329.510 and to specialvoltage units which are likewise equipped with a
transformer.
– Install the slow pre-fuse specified on the rating
plate (miniature circuit-breaker with appropriate
characteristic – e. g. K characteristic – or fuse
gG standard type, power circuit-breaker or transformer circuit-breaker) to protect the cable and
equipment from short-circuits. Select a suitable
circuit-breaker in accordance with the information
specified on the rating plate: Set it to the minimum
specified value. This will achieve the best shortcircuit protection for cables and equipment.
Example: Specified setting range 6.3 – 10 A;
set to 6.3 A.
4.5.3 Three-phase devices
– The three-phase version of models SK 3304.xxx,
SK 3305.xxx, SK 3328.xxx, SK 3329.xxx and
SK 3332.xxx must be connected to a TN network
with star earthing via a circuit-breaker for plant
protection (current setting as per the rating plate).
Three-phase units with special voltages must be
protected with a circuit-breaker for transformer
protection (category AC-3) as per the rating plate.
– Units designed for three phase 400/460 V feature
additional monitoring of the rotary field or the
absence of a phase. If the rotary field is incorrect
or a phase is absent, the unit will not run.

Rittal cooling unit assembly and operating instructions

4 Assembly and connection
4.5.4 Door limit switch
– Each door limit switch must only be assigned to
one cooling unit.
– Several door limit switches may be connected in
parallel and operated on one cooling unit.
– The minimum cross-section for the connection
cable is 0.3 mm2 for a cable length of 2 m.
– The line resistance to the door limit switch must not
exceed a maximum of 50 :.
– The door limit switch only supports a floating
connection; no external voltages.
– The contact of the door limit switch must be closed
when the door is open.
The safety extra-low voltage for the door limit switch
is provided by the internal power pack: Current
approx. 30 mA DC.
• Connect the door limit switch to terminals 1 and 2
of the connector.
4.5.5 Notes on the flicker standard
The flicker limits specified in standard EN 61 000-3-3
or -3-11 are adhered to, provided the supply impedance is less than approx. 1.5 :.
Where necessary, the unit operator should measure
the connected impedance or consult the responsible
power supply company. If there is no way of influencing the supply impedance and sensitive installed
components (e.g. BUS) are subjected to interference, a line reactor or starting-current limiting device
should be connected upstream of the cooling unit to
restrict the startup current of the cooling unit.
4.5.6 Potential equalisation
If, for EMC reasons, the unit is to be integrated into
the existing potential equalisation system at the
customer, a conductor with a larger nominal crosssection can be connected to the potential equalisation connection point (attachment points) on wallmounted cooling units.
According to the standard, the PE conductor in the
mains connection cable is not classified as an equipotential bonding conductor.

When interconnecting, please note the following:
– De-energise the cooling units to be connected.
– Ensure proper electrical insulation.
– Make sure the cables are not laid in parallel to
power lines.
– Make sure that the lines are short.
Caution!
Regarding the last slave unit in the
group, do not, under any circumstances,
connect the remaining socket of the
Y cable SK 3124.100 into interface X3
of the cooling unit!
4.6.2 Connection X3 for serial interface
The interface card (Model No. SK 3124.200) may be
connected to X3. This is used to evaluate system
messages in a PLC, for remotely setting parameters
and monitoring, or for integration into the facility
management system.
4.6.3 Installing external transformers
For SK 3361.x40 only.

Attachment of the
unit’s rear panel

Electrical connection
cooling unit

4.6 Carrying out the electrical installation
4.6.1 Bus connection
(only in conjunction with several units
with an e-Comfort controller)
When using several cooling units, the serial device
interface X2 can be used to connect up to ten cooling units with the bus cable (Model No. SK 3124.100).

EN

Mounted on 35 mm
support rail
DIN EN 50 022

230 V

Connection at
the customer’s

Fig. 19:

Installing external transformers (SK 3361.x40 only)

Note:
The electrical signals at the X2 interface are
of an extra-low voltage (not extra-low safety
voltages to EN 60 335-1).

Rittal cooling unit assembly and operating instructions

13

4 Assembly and connection
EN

CMC
1
I/O unit
2

RTT
Master

Adr.: 09

RTT
Slave

Adr.: 11

X3

St. X2

Adr.: 12

X3

X2

X3 Bu.

RTT
Slave

Adr.: 19

X1

X1

X1
X2

RTT
Slave

X2

X1
X3

X2

St. X2

St. X2

X3

St. X2

X2 X2

X2 X2

X2

Bu. St.

Bu. St.

Bu.

3

Fig. 20:

Connection example: Master-slave operation

Legend
1
Serial interface (Model No. SK 3124.200)
2
Serial interface cable
3
Master-slave bus cable (Model No. SK 3124.100)
RTT Rittal TopTherm cooling units
X1 Supply connection/door limit switch/alarms

X2

X2

Adr.: 06
1
X10 L1

L2
N

X2

Adr.: 11
2

PE 1 2 3 4 5 X10 L1 L2 L3 PE 1 2 3 4 5

L2
N

Master-slave connection Sub-D, 9-pole
Serial interface Sub-D, 9-pole
Sub-D connector, 9-pole
Sub-D jack, 9-pole
Address

X2

Adr.: 12
2
X10 L1

X2
X3
St.
Bu.
Adr.

X2

Adr.: 13
2

PE 1 2 3 4 5

X2

Adr.: 14
2

X10 L1 L2 L3 PE 1 2 3 4 5

X10 L1 L2 L3 PE 1 2 3 4 5

Adr.: 15
2
X10 L1 L2 L3 PE 1 2 3 4 5
X2

L1

L2
N

PE 1 2 3 4 5

X10

Adr.: 16

1 2
3

Fig. 21:

4

3

2

Connection example: Door limit switch and master-slave operation

Legend
1
Master cooling unit
2
Slave cooling units
3
2-door enclosure with two door limit switches
4
Enclosure with door limit switch

14

5 6

4

3
4

4.6.4 Installing the power supply
• Complete the electrical installation by following
the wiring plan on the rear of the cooling unit
(see Fig. 1 on page 5, for key see page 19).
• If you would like the system messages from the
cooling unit to be evaluated via the system
message relay, you should also connect a suitable
low-voltage cable to connection clamps 3 – 5.

Rittal cooling unit assembly and operating instructions

4 Assembly and connection
EN

SK 3302.100/.110, SK 3302.300/.310

21

PE
5
Mains

A2

22

S1

L1

X1

L2
N

1

PE

1 2 3
L
N
Power

L1
2

1

3

2

5

4

3

R1

L2

2

1

2

NTC I red

S1
Kx

B2

8

Term
A1

B1

2

NTC E blue

2
F2 1
M2
1 2 3

M1
1 2 3

P

M4
1 2 3

F2

C4
C1
S
R

C2

C

M

M

1~

1~

M2

M4

F3

M1

Fig. 22:

Electrical wiring plan no. 1

21

SK 3303.500/.510, SK 3303.600/.610, SK 3361.500/.510, SK 3361.600/.610

Mains
22

S1

PE
5

L2
N

X1 L1

1

PE

2

3

5

4

X3

X2
3

1 2 3

1

2

L
N
Power

S1

K2

3

2

1

K1

A2

8

MS1

Serial

NTC_I
NTC_E

Kx

NTC_C
PE

NTC_A

M2
1 2 3

M4
1 2 3

F2

2
2

B1
B2
B3
B4
B5

4

Term

M1
1 2 3

2

2

Level

A1

2

2
1

P

F2

C4

PE
C1
S

R
C

C2
F3

M

M

1~

1~

M2

M4

M1

Fig. 23:

Electrical wiring plan no. 2

Rittal cooling unit assembly and operating instructions

15

4 Assembly and connection
EN

SK 3361.540/.640
Mains
L2

PE

21

L1

5

X2

S1

22

T1

L2
N

L1

X1

PE

2

1

1 2 3
L

X3
PE

3

230 V

PE

1

N

4

3

2

3

2

1

B1

NTC I red

Serial

MS1

K1

Power

A2

5

2

K2

S1

PE

8

2

B2

NTC E blue

Kx

2

B3

NTC C white
2

PE

B4

NTC A yellow
2

B5

Level green

A1

4

Term

M4
1 2 3

M2
1 2 3

M1
1 2 3

2
1

F2

F2

P

PE
C1
S

R
M
C

F3

M

1~

1~

M2

M4

M1

Fig. 24:

Electrical wiring plan no. 3

21

SK 3304.500/.600/.510/.520/.504/.514/.610
S1
22

Mains
PE

X2

5
X1

L1

L2

L2

L1

PE

N

1

2

3

5

4

A2

PE

E1

F11

X3

3

PE

6

T1
L

N

PE

1 2 3

1

L

S1

N

Power

2

3

2

1

MS1

NTC I red

Serial

NTC E blue
K1

K2

NTC C white

Kx

NTC A yellow

A1

Level green
Term
M1
1 2 3

M2
1 2 3

M4
1 2 3

F2

2

B1

2

B2

2

B3

2

B4

2

B5

4

2
1

P
F2

C1

1
R

S
F3
3
M1

Fig. 25:
16

M

M

1~

1~

M2

M4

C

Electrical wiring plan no. 4
Rittal cooling unit assembly and operating instructions

4 Assembly and connection
SK 3305.500/.510/.504/.514/.520, SK 3328.500/.510/.504/.514/.520, SK 3329.500/.510/.504/.514/.520,
SK 3305.600/.610, SK 3328.600/.610, SK 3329.600/.610

5

X2

21

L1 L2
N

X3
PE

S1

Mains

PE

22

PE
T1

L1

A2

L2/N

F11 E1 X1 L1

F10

L2
N

F11
1

1

PE

2

3

6

3

5

4

E1

2 3
1 2 3
L

1

2

N

3

2

1

K2
S1

Power

2

NTC I red

Serial

MS1

K1
Kx

1 2 3

F2

B5

4

Term

M4

B4

2

Level green

M2

B3

2

NTC A yellow

M1
1 2 3

B2

2

NTC C white
A1

B1

2

NTC E blue

2
P

1

1 2 3
F2

A3

A

R

C

4
C12

P

1

C11

2
5
M
1~

M2

M4

M1

F3

Fig. 26:

M
1~

Electrical wiring plan no. 5

SK 3304.540, SK 3304.544, SK 3305.540, SK 3305.544, SK 3328.540/.544, SK 3329.540/.544,
SK 3304.640, SK 3305.640, SK 3328.640, SK 3329.640, SK 3366.540, SK 3366.640
Mains
22

PE

X1

L1

L2

L3

1

PE

2

3

4

21

5

S1

X3

X2

5
3

F11 F12

8
A2

E1

T1

3

2

1

1 2

Power

2

4

K2

1

3

MS1

NTC I red

Serial

K1

NTC E blue

S1

NTC C white

Kx

NTC A yellow
Level green
A1

M1
1 2 3 4

Term

F4
M2
1 2 3 4 1 2 3

F3 F2
1 2 3 4

M4

F5

1 2 3

1 2

2
2
2
2
2

B1
B2
B3
B4
B5

4

P
F2

U

V
M
F3

W

M

3~

3~

M2

M4

M1

Fig. 27:

Electrical wiring plan no. 6

Rittal cooling unit assembly and operating instructions

17

EN

4 Assembly and connection
EN

21

SK 3366.500/.510/.600/.610

5

S1

Mains
22

L1 L2
N

PE

X2

A2

X3

T1
L2
N

X1 L1
L1

L2/N

F11

F10
E1

1

PE

2

3

3

5

4

6

F11
E1

1 2 3

1 2 3
L

1

2

N

3

2

1

K2

Serial

M51

NTC I red

K1

S1

Power

NTC E blue
Kx
NTC C white
NTC A yellow

A1

Level green

2

B1

2
B2
2
2

B3
B4

2
B5
4

Term

F2
M1
3

M2
1

2

1 2

1

3

2

2
P

1

M4
3

F2
A1

A3
1

1

C1.2

2

C1.1

C4

2

5

A

P

C2

M

M

1~

1~

M2

M4

1~
F3
C

M1

Fig. 28:

Electrical wiring plan no. 7

21

SK 3332.540/.640
S1
22

Mains

A2

PE
L2

L1

X1

6

L3

PE

1

2

3

X2

5

4

X3
3

8

F11 F12
E1

T1
3
R

2
S

1

1

2

2

4

1

3
MS1

T

K2

Serial

K1

2
2

NTC E blue

S1

Power

NTC I red

NTC C white

Kx

2
2

NTC A yellow
Level green

A1

Term
M1

F3

1 2 3 4

1 2 3

U

V

F2

F4

M2
4

1

2

3 4

1 2 3

M4

F5

1 2 3

1

2

B1
B2
B3
B4
B5

4

2

F2
M

M

P
3~

3~

M2

M4

W
M1

Fig. 29:
18

Electrical wiring plan no. 8
Rittal cooling unit assembly and operating instructions

4 Assembly and connection
Legend
A1
A2
A3
B1
B2
B3
B4
B5
C1.2
C1.1, C2, C4
E1
F2
F3
F11/F12
K1
K2
L1
L2
M1
M2
M4
R1
S1
T1
X1
X2
X3

Power PCB
Display terminal
Starter relay and RC element
Temperature sensor, internal temperature
Icing hazard temperature sensor
Condenser temperature sensor
Ambient temperature sensor
Condensate warning sensor (optional)
Start-up capacitor
Running capacitors
Condensate evaporator
PSAH pressure-operated switch (3302.1x0 has bridge instead of pressostat)
Bimetal contact compressor
Miniature fuses, condensate evaporator
Relay collective fault 1
Relay collective fault 2
LED operational green
LED alarm red
Compressor
Condenser fan
Evaporator fan
Potentiometer for setting the temperature
Door limit switch (without door limit switch: terminal 1, 2 open)
Transformer (optional)
Main terminal strip
Master-slave connection
Optional interface

EN

Note:
For technical data refer to the rating plate.

AC

DC

cos f = 1

L/R = 20 ms

I max. = 2 A
U max. = 250 V

I min. = 100 mA
U max. = 200 V
U min. = 18 V
I max. = 2 A

Tab. 2: Contact data

Rittal cooling unit assembly and operating instructions

19

5 Commissioning
4.7 Finalising assembly

EN

4.7.1 Installing the filter media
The cooling unit condenser is finished all over with a
dirt-repelling, easy-to-clean RiNano coating. In many
cases, therefore, the use of filter media is unnecessary, particularly in the case of dry dusts.
For dry, coarse dust and lint in the ambient air, we
recommend installing an additional PU foam filter
mat (available as an accessory) in the cooling unit.
For air containing oil condensation, we recommend
the use of metal filters (also available as an accessory). When used in textile plants with heavy lint contamination, lint screens should be used (available as
an optional extra).
• Pull the louvred air inlet grille from the enclosure.
• Insert the filter mat into the louvred grille as shown
in Fig. 30 and push it back onto the enclosure.

4.7.3 Setting the filter mat monitor
(only with e-Comfort controller)
Function of the filter mat monitor:
Dirt on the filter mat is automatically detected by
measuring the temperature difference in the external
circuit of the cooling unit (see “6.2.6 Programming
overview”, page 26). As the level of filter mat soiling
rises, the temperature difference will increase. The
nominal value of the temperature difference in the
external circuit adapts automatically to the relevant
operating points in the performance diagrams.
Hence there is no need to readjust the nominal value
for different operating points of the cooling unit.

5

Commissioning
Caution! Risk of damage!
The oil must collect in the compressor in
order to ensure effective lubrication and
cooling.
Do not operate the cooling unit for
at least 30 min. after assembling the
equipment.

Fig. 30:

Installing the filter mat

4.7.2 Fitting the cooling unit
For partial and full internal mounting only.
• Connect the connector to the rear of the display.
• Place the louvred grille onto the unit at the front,
and press it down until you hear it snap into place.

Fig. 31:

20

• Once all the assembly and installation work is complete, switch on the power supply to the cooling
unit.
The cooling unit starts running:
– With Basic controller: The green operating LED
(“line”) is illuminated.
– With e-Comfort controller: The software version
of the controller first appears for approx. 2 sec.,
followed by “ECO” for activated eco-mode. Then
the enclosure internal temperature appears in the
7-segment display.
You can now make your individual settings on the
unit, e.g. set the temperature or (with e-Comfort controller only) assign the network identifier, etc. (refer to
the “Operation” chapter).

Connect the display and attach the louvred grille

Rittal cooling unit assembly and operating instructions

6 Operation
6

Operation

You can operate the cooling unit using the controller
on the front of the device (Fig. 1, no. 11, page 5).
Depending on the model, the unit is equipped with
a Basic or an e-Comfort controller.

6.1 Control using the Basic controller
For unit types SK 3302.xxx.
1

3

4

2
5

Fig. 32:

Basic controller

Legend
1
Controller trim panel
2
Temperature setting
3
LED green (“line”)
4
LED red (“alarm”)
5
Reset button

Rittal cooling unit assembly and operating instructions

6.1.1 Properties
– Two voltage variants are supported:
– 115 V
– 230 V
– Integral start-up delay and door limit switch
function
– Protective function to prevent icing
– Monitoring of all motors (compressor,
condenser fan, evaporator fan)
– Phase monitoring for three-phase units
– Visualisation of the operating status via LED
display:
– Voltage on, unit operational
– Door open (only if door limit switch installed)
– Warning of overtemperature
– High-pressure-operated switch has switched
– Switching hysteresis: 5 K.
If the cooling unit is oversized and compressor
running times are < 1 minute the switching
hysteresis is automatically increased to protect
the cooling unit.
– Floating system message contact in case
of overtemperature
– Temperature setting
(setting range 30 – 55°C) via potentiometer
– Test function
– System messages via flashing mode
(see “6.1.2 Operating and error system”,
page 22)

EN

The cooling unit operates automatically i.e. after
switching on the power supply, the evaporator fan
(see Fig. 2, page 5) will run continuously and permanently circulate the internal enclosure air. The built-in
Basic controller ensures automatic normal shutdown operation of the cooling unit by the value of the
fixed preset switching difference of 5 K.

21

6 Operation
EN

6.1.2 Operating and error display
The Basic controller monitors and controls the cooling unit. It indicates the operating and error status via
the green and red LEDs (Fig. 32, no. 3 and 4):
LED

Status

Cause

Solution

Green
(line)

Illuminated

Voltage present,
unit operational

–

Flashing

Only with door limit switch installed:
Enclosure door open

In order to avoid condensation, close the
enclosure door as quickly as possible.

Only with door limit switch installed:
Enclosure door closed

Check the position of the door limit switch.

Red
(alarm)

Alarm/error/warning

Number of
flash intervals
for the red LED

Flash interval

Implement
a reset

Device reset

(12)

|_|_|_|_|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|_|_|_|_|

High pressure alarm

(0)

|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|

Sensors

Potentiometer defective
or display error

(3)

|_|_|*****|_|_|*****|_|_|*****|_|_|*****|_|_|*****

Interior temperature
sensor defective

(4)

|_|_|_|*****|_|_|_|*****|_|_|_|*****|_|_|_|*****

Anti-icing sensor
defective

(5)

|_|_|_|_|*****|_|_|_|_|*****|_|_|_|_|*****|_|_|_|_|

Compressor overloaded

(6)

|_|_|_|_|_|*****|_|_|_|_|_|*****|_|_|_|_|_|*****

Interior fan overloaded

(7)

|_|_|_|_|_|_|*****|_|_|_|_|_|_|*****|_|_|_|_|_|_|

Exterior fan overloaded

(8)

|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|*****

Device
status/
condition

Overload mode
(heat loss)

(9)

|_|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|_|*****

Warning
(ambient
conditions)

Anti-icing alarm

(2)

|_|*****|_|*****|_|*****|_|*****|_|*****|_|*****|_|

No
display

No power

–

Check power supply

Rotary current phase
monitoring:
“LED off” = Incorrect
phase connection

–

Swap phases

Overload

Off

Tab. 3: Operating and error display of the Basic controller

Key to flash intervals
|
= 500 ms (red LED on)
_
= 500 ms (red LED off)
***** = 3 s pause (red LED off)

The overtemperature message (red LED illuminated)
may also be polled via an integral floating contact on
the connection clamp of the cooling unit (system
message relay with changeover contact, see connection diagrams under “4.6.4 Installing the power
supply”, page 14):

22

– Terminal 3: NC (normally closed)
– Terminal 4: C (connection of the supply voltage
to the system message relay)
– Terminal 5: NO (normally open)
The NC and NO definitions refer to the de-energised
state. As soon as power is applied to the cooling unit,
the system message relay picks up, so that the relay
contacts change status (contact 3 – 4 open; contact
4 – 5 closed). This is the normal operating state of the
cooling unit. As soon as an error message occurs or
the power supply is interrupted, the relay drops out
and contact 3 – 4 is closed.

Rittal cooling unit assembly and operating instructions

6 Operation
6.1.3 Test mode for the Basic controller
The Basic controller is equipped with a test function
whereby the cooling unit commences cooling operation independently of the set temperature or door
limit switch function.
First you must dismantle the trim panel of the controller.
• Switch off the mains voltage.
• Remove the louvred grille or infill panel in which the
controller is installed.
• Release the display lock from behind and pull it
forwards slightly.

To change the temperature setting:
• Dismantle the trim panel of the controller as
described in “6.1.3 Test mode for the Basic
controller”, page 23.
• Set the required temperature on the temperature
setting device (Fig. 32, page 21).
• Carefully push the trim panel onto the display until
you hear it snap into place.
• Push the display back into the infill panel or louvred
grille.
• Re-attach the louvred grille or infill panel to the
cooling unit.
6.1.5 Resetting the Basic controller
Following a high-pressure alarm in the cooling cycle,
and once the cause has been rectified, you will need
to manually reset the Basic controller:
• Dismantle the trim panel of the Basic controller
as described in “6.1.3 Test mode for the Basic
controller”, page 23.
• Press the reset button (Fig. 32, no. 5) for at least
3 sec.
The red LED is extinguished.
• Re-install the Basic controller.

Fig. 33:

Loosen the trim panel of the Basic controller

• Carefully raise the trim panel, e.g. using your
thumb or a flat screwdriver, and remove it.
You can now start test mode.
• Rotate the potentiometer to the left-hand stop, then
hold the rubberised potentiometer display down
while you re-connect the mains voltage.
The cooling unit will commence operation and the
green LED will flash (I_II_I_II_ . . .). Test mode is
completed after approximately 5 minutes. The unit
switches off and changes to normal operation.
Key
I = LED 500 ms on
_ = LED 500 ms off

In normal operation, the green LED is permanently
illuminated.
• Next, rotate the potentiometer back to the required
setpoint.
6.1.4 Setting the temperature
Note:
With the Basic controller, the temperature
is preset at the factory to +35°C. In order
to save energy, do not set the temperature
any lower than is actually necessary.

Rittal cooling unit assembly and operating instructions

6.2 Control using the e-Comfort controller
For unit types SK 33xx.5xx and SK 33xx.6xx.
1

4

Fig. 34:

2

3

e-Comfort controller

Legend
1
Programming button, also display of the set
temperature unit (degrees Celsius)
2
Set button
3
Programming button, also display of the set
temperature unit (degrees Fahrenheit)
4
7-segment display

6.2.1 Properties
– Three voltage variants are supported:
– 115 V
– 230 V
– 400/460 V, 3-phase, supports multiple voltages
without rewiring
– Integral start-up delay and door limit switch
function

23

EN

6 Operation
EN

– Protective function to prevent icing
– Monitoring of all motors (compressor,
condenser fan, evaporator fan)
– Phase monitoring for three-phase units
– Master-slave function with a maximum of ten units.
One device functions as a master unit. Once the
set temperature is reached by one of the connected slave devices or in the event of the door limit
switch function, the affected slave unit will report
to the master unit, which will switch all the other
cooling units on or off as required.
– Switching hysteresis: Adjustable within the range
2 – 10 K, preset to 5 K.
– Visualisation of the current enclosure internal temperature and all error messages in the 7-segment
display.
– Using an interface card (Model No. SK 3124.100),
the unit may be incorporated into higher-level
remote monitoring systems such as the Rittal
Computer Multi Control CMC.
The cooling unit operates automatically i.e. after
switching on the power supply, the evaporator fan
(see Fig. 2, page 5) starts to run and circulates the
internal enclosure air. The compressor and condenser fan are regulated by the e-Comfort controller.
The e-Comfort controller has a 7-segment display
(Fig. 34, no. 4). After switching on the power supply,
the current software version initially appears on this
display for approx. 2 seconds, as well as the activated eco-mode. Followed by a preset option (e. g. t10)
or the temperature.
In regular operation, the display shows both the temperature (in degrees Celsius or Fahrenheit – users
may switch between the two) and any error messages.
The current enclosure internal temperature is usually
displayed permanently. In the event of an error message, this will alternate with the temperature display.
The unit is programmed using buttons 1 – 3 (Fig. 34).
The relevant parameters also appear in the display.
6.2.2 Eco-mode
All Rittal TopTherm cooling units with e-Comfort
controller from firmware 3.2 have the energy-saving
eco-mode, which is activated in the delivered state.
The eco-mode is used to save energy in the cooling
unit if there is no thermal load, or there is a low thermal load in the enclosure (e. g. standby operation,
no production or weekend). During this process the
evaporator fan in the internal circuit is switched off as
appropriate if the actual enclosure internal temperature drops to 10 K below the setpoint temperature
set. To reliably measure the internal temperature
also during this process, the fan starts cyclically for
30 sec. (see Fig. 35). If the internal temperature
reaches the range 5 K below the setpoint set again,
the fan switches back to continuous operation.

24

If required, the eco-mode can be deactivated via the
control display. For this purpose switch the parameter from 1 to 0 in the programming level (see Tab. 4,
page 25). The fan then runs continuously.
Setpoint
–5°C
Setpoint
–10°C

Internal
temperature

ON
OFF

Internal fan
status
10 min.

10 min.

Time

30 sec.

Fig. 35:

Diagram of eco-mode

6.2.3 Launching test mode
The e-Comfort controller is equipped with a test function whereby the cooling unit commences cooling
operation independently of the set temperature or
door limit switch function.
• Simultaneously press buttons 1 and 2 (Fig. 34)
for at least 5 sec.
The cooling unit will commence operation.
After approximately 5 minutes, test mode will end.
The unit switches off and changes to normal operation.
6.2.4 General programming information
Using buttons 1, 2 and 3 (Fig. 34) you can change
24 parameters within the preset ranges (min. value –
max. value).
Tables 4 and 5 show the parameters which can be
altered. Fig. 36 of page 26 shows which buttons
must be pressed.
Note on switching hysteresis:
With a low hysteresis and short switching
cycles, there is a risk that cooling may not
be adequate or that only partial sections
of the enclosure are cooled. If the cooling
unit is oversized and compressor running
times are < 1 minute the switching hysteresis
is automatically increased to protect the
cooling unit.
Note on temperature settings:
With the e-Comfort controller, the temperature is preset at the factory to +35°C.
In order to save energy, and due to the
risk of increased condensation, do not set
the temperature lower than that actually
necessary.
Note on useful cooling output:
Interactive performance diagrams for
calculating the useful cooling output may
be found at www.rittal.com.

Rittal cooling unit assembly and operating instructions

6 Operation
• Keep the programming button ▲ (°C) held down
until “22” appears.
• Press button 2 (“Set”) to confirm the code.
You can now alter the parameter within the preset
limits.
• Press one of the programming buttons ▲ (°C) or
▼ (°F) until the required value appears.
• Press button 2 (“Set”) to confirm the change.
You can now alter other parameters in the same way.
There is no need to re-enter the authorisation code
“22”.
• To exit programming mode, press button 2 (“Set”)
again for approximately 5 sec.
“Acc” will appear in the display to indicate that the
changes have been saved. The display will then
switch back to regular operation (enclosure internal
temperature).
You can also program the e-Comfort controller
using a diagnosis software package (Model No.
SK 3159.100), the supply of which also includes
a connection cable to the PC. The cable connector
on the rear of the e-Comfort controller display serves
as an interface.

In principle, the programming is identical for all
editable parameters.
To enter programming mode:
• Press button 2 (“Set”) for approx. 5 sec.
The controller is now in programming mode. While in
programming mode, if you do not press any buttons
for approx. 30 sec., the display will first flash, then
the controller will switch back to normal display
mode. The “Esc” display indicates that any made
changes have not been saved.
• Press the programming buttons ▲ (°C) or ▼ (°F)
to switch back and forth between the editable
parameters (see tables 4 and 5).
• Press button 2 (“Set”) to select the displayed
parameter for editing.
The current value of this parameter is displayed.
• Press one of the programming buttons ▲ (°C) or
▼ (°F).
The “Cod” display will appear. In order to be able to
change a value, you must enter the authorisation
code “22”.

6.2.5 Editable parameters
See also Fig. 36 on page 26.
Progr.
level

Display
screen

Parameter

Min.
value

Max.
value

Factory
setting

Description

1

St

Internal enclosure
temperature
setpoint Ti

20

55

35

The setting of the enclosure internal temperature
is preset at the factory to 35°C and may be altered
within a range of 20 – 55°C.

2

Fi

Filter mat
monitoring

10

60

99
(= off)

To activate filter mat monitoring, set the display to
at least 10 K above the temperature differential
displayed in programming mode “Fi”. Filter mat
monitoring is preset to “deactivated” in the factory
(99 = off).

3

Ad

Master-slave
identifier

0

19

0

See “6.2.8 Setting the master-slave identifier”,
page 28.

4

CF

Temperature
conversion
°C/°F

0

1

0

The temperature display can be switched from
°C (0) to °F (1). The corresponding LED displays
the current unit of temperature.

5

H1

Setting for
switching
difference
(hysteresis)

2

10

5

The cooling unit is preset in the factory to a
switching hysteresis of 5 K. This parameter should
only be changed in consultation with us.
Please contact us for advice.

6

H2

Differential for
error message A2

3

15

5

If the internal enclosure temperature exceeds the
set value by more than 5 K, then error message
A2 (enclosure internal temperature too high)
appears on the display terminal. If necessary,
the differential may be altered here within the
range of 3 – 15 K.

26

ECO

Eco-mode operation 0

1

1

Eco-mode OFF: 0 / Eco-mode ON: 1

Tab. 4: Editable parameters

Rittal cooling unit assembly and operating instructions

25

EN

6 Operation
6.2.6 Programming overview

= 5 sec.

= 5 sec.

EN

Fig. 36:
26

Programming overview
Rittal cooling unit assembly and operating instructions

6 Operation
6.2.7 Defining system messages for evaluation
System messages are shown on the display screen
of the e-Comfort controller via the displays A1 to A20
and E0.

A more detailed explanation of the system messages
may be found in section “6.2.9 Evaluating system
messages”, page 28.
See also Fig. 36 on page 26.

Progr.
level

Display
screen

Min.
value

Max.
value

Factory
setting

Type or location of fault

7

A1

0

2

0

Enclosure door open

8

A2

0

2

0

Internal temperature of enclosure too high

9

A3

0

2

0

Filter monitoring

10

A4

0

2

0

Ambient temperature too high/too low

11

A5

0

2

0

Icing hazard

12

A6

0

2

1

PSAH pressure-operated switch

13

A7

0

2

2

Evaporator coil

14

A8

0

2

1

Condensate warning

15

A9

0

2

1

Condenser fan blocked or defective

16

A10

0

2

1

Evaporator fan blocked or defective

17

A11

0

2

2

Compressor

18

A12

0

2

1

Condenser

19

A13

0

2

1

Ambient temperature sensor

20

A14

0

2

1

Icing temperature sensor

21

A15

0

2

1

Condensate warning temperature sensor

22

A16

0

2

1

Internal temperature sensor

23

A17

0

2

1

Phase monitoring

24

A18

0

2

0

EPROM

25

A19

0

2

0

LAN/Master-Slave

Tab. 5: System messages which may be evaluated via relays

The system messages A1 – A19 may additionally be
evaluated via two floating system message relays. In
this way, one of the two system message relays may
be allocated to each system message.
System alarm relay with normally open contact: see
connection diagrams under “4.6.4 Installing the
power supply”, page 14:
– Terminal 3: NO (normally open, relay 2)
– Terminal 4: C (connection of the supply voltage
to the system message relay)
– Terminal 5: NO (normally open, relay 1)

This is the normal operating state of the cooling unit.
As soon as a system message occurs or the power
supply is interrupted, the corresponding relay will
drop out and open the contact.
Program system messages with the value
0: System message is not sent to the system
message relay, but merely appears in the
display
1: System message is evaluated by relay 1
2: System message is evaluated by relay 2

The definition NO refers to the de-energised state.
As soon as power is applied to the cooling unit, both
system message relays (relay 1 and 2) energise.

Rittal cooling unit assembly and operating instructions

27

EN

6 Operation
EN

6.2.8 Setting the master-slave identifier
When several cooling units are connected together
(maximum ten), one of the cooling units must be
defined as the “master” and the others as “slaves”.
For this purpose, assign a corresponding identifier
(address) to each cooling unit which will enable the
cooling unit to be identified in the network.
If one of the slave units reaches the set temperature
or if the door limit switch function is activated, the
affected slave unit will report to the master unit,
which then deactivates all the other cooling units.
Notes:
– Only one unit may be configured as
master, and its identifier must match the
number of slave units connected.
– The slave units must have different
identifiers.
– The identifiers must be numbered in
ascending order without any gaps.
On the master cooling unit (00 = factory setting),
set the number of slave units present in the network:
01: Master with 1 slave cooling unit
02: Master with 2 slave cooling units
03: Master with 3 slave cooling units
04: Master with 4 slave cooling units
05: Master with 5 slave cooling units
06: Master with 6 slave cooling units
07: Master with 7 slave cooling units
08: Master with 8 slave cooling units
09: Master with 9 slave cooling units

28

On the slave cooling unit (00 = factory setting),
set its own address:
11: Slave cooling unit no. 1
12: Slave cooling unit no. 2
13: Slave cooling unit no. 3
14: Slave cooling unit no. 4
15: Slave cooling unit no. 5
16: Slave cooling unit no. 6
17: Slave cooling unit no. 7
18: Slave cooling unit no. 8
19: Slave cooling unit no. 9

Master
02

Fig. 37:

Slave
11

Slave
12

Master-slave connection (example)

For further connection examples, see “4.6.1 Bus
connection (only in conjunction with several units
with an e-Comfort controller)”, page 13.
For details of how to set the identifier, see “6.2.5
Editable parameters”, page 25 or “6.2.6 Programming overview”, page 26, parameter “Ad”.
6.2.9 Evaluating system messages
In the e-Comfort controller, system messages are
indicated by a number in the display.
Following the appearance of messages A03, A06
and A07 and after rectifying their cause, you will
need to reset the e-Comfort controller (see “6.2.10
Resetting the e-Comfort controller”, page 30).

Rittal cooling unit assembly and operating instructions

6 Operation
Display
screen

System message

Possible cause

Measures to rectify the fault

A01

Enclosure door open

Door open or door limit switch
incorrectly positioned

Close door, position door limit switch correctly,
check connection if necessary

A02

Internal temperature
of enclosure too high

Cooling capacity inadequate/unit undersized. Check cooling capacity
Error as a consequence of messages A03 to
A17.

A03

Filter monitoring

Filter mat soiled

Clean or replace;
reset the e-Comfort controller

A04

Ambient temperature
too high/too low

Ambient temperature outside of admissible
operating range (+10°C to +60°C)

Raise or lower the ambient temperature
(e.g. heat or ventilate the room)

A05

Icing hazard

Operational display in case of icing hazard. Set the enclosure interior temperature to
Evaporator coil fan may be mechanically
a higher value. Check the evaporator fan;
blocked, defective, or cold air outlet
release or exchange if necessary.
obstructed.

A06

PSAH pressure-operated
switch

Ambient temperature too high

Lower the ambient temperature;
reset the e-Comfort controller

Condenser soiled

Clean the condenser;
reset the e-Comfort controller

Filter mat soiled

Clean or replace;
reset the e-Comfort controller

Condenser fan defective

Replace; reset the e-Comfort controller

E-valve defective

Have the sensor repaired by a refrigeration
engineer; reset the e-Comfort controller

PSAH pressure-operated switch defective

Have the switch replaced by a refrigeration
engineer; reset the e-Comfort controller

A07

Evaporator coil

Lack of coolant; sensor in front of or behind
condenser defective.

Have the sensor repaired by a refrigeration
engineer; reset the e-Comfort controller

A08

Condensate warning

Condensate discharge kinked or blocked

Check condensate discharge; repair any kinks
or blockages in the hose as necessary

Only in units with optional
condensate evaporation

Check the evaporation unit,
exchange if necessary
Clear the blockage; replace if necessary

A09

Condenser fan

Blocked or defective

A10

Evaporator fan

Blocked or defective

Clear the blockage; replace if necessary

A11

Compressor

Compressor overloaded
(internal winding protection)

No action required;
unit switches back on automatically.

Defective
Exchange by refrigeration engineer
(check by measuring the winding resistance)
A12

Condenser temperature
sensor

Open or short-circuit

Replace

A13

Ambient temperature
sensor

Open or short-circuit

Replace

A14

Icing temperature sensor

Open or short-circuit

Replace

A15

Condensate warning
temperature sensor

Open or short-circuit

Replace

A16

Internal temperature sensor Open or short-circuit

Replace

A17

Phase monitoring

For three-phase devices only:
Incorrect rotary field/phase absent

Exchange two phases

A18

EPROM error

New board obstructed

Software update needed (only following board
installation with more recent software):
Enter the programming level with Code 22;
press button 1 and confirm with “Set” until
“Acc” appears. Next, disconnect the unit from
the mains and reconnect.

A19

LAN/Master-Slave

Master and slave not connected

Check setting and/or cable

A20

Voltage drop

Error display not shown

Event is stored in the log file

E0

Display message

Connection problem between the display
and the controller board

Reset: Switch power supply off, then switch
on again after approx. 2 sec.

Cable defective; connection loose

Exchange the boards

OL

Overload

Ambient parameters or heat loss outside of the applicable limits

b07

Cooling circuit leak

Sensor B3 and B4 mixed up

rSt

Reset

Manual device reset required,
see “6.2.10 Resetting the e-Comfort controller”, page 30.

Correct sensor position

Tab. 6: Troubleshooting with the e-Comfort controller

Rittal cooling unit assembly and operating instructions

29

EN

7 Inspection and maintenance
EN

6.2.10 Resetting the e-Comfort controller
After the occurrence of faults A03, A06 and A07,
you will need to reset the e-Comfort controller.
• Press buttons 1 (▲) and 3 (▼) (Fig. 34) simultaneously for 5 sec.
The system messages will disappear and the temperature display will be shown.

7

7.1.1 Compressed air cleaning
SK 3304.xxx, SK 3305.xxx

Inspection and maintenance
Risk of electric shock!
The unit is live.
Switch off the power supply before opening, and take suitable precautions against
it being accidentally switched back on.

Fig. 38:

Disconnect the power cord

Fig. 39:

Remove the upper louvred grille

7.1 General
The cooling circuit is designed in the form of a maintenance-free, hermetically sealed system. The cooling unit is filled with the required quantity of refrigerant at the factory, checked for leaks, and subjected
to a functional test run.
The installed maintenance-free fans are mounted on
ball bearings, protected against moisture and dust,
and fitted with a temperature monitor. The life expectancy is at least 30,000 operating hours. The cooling
unit is thus largely maintenance-free. All that may be
required from time to time is to clean the components
of the external air circuit using a vacuum cleaner or
compressed air if they become visibly dirty. Any
stubborn, oily stains may be removed using a nonflammable detergent, such as degreaser.
Maintenance interval: 2000 operating hours. Depending on the level of contamination in the ambient air,
the maintenance interval may be reduced to suit the
air pollution intensity.
Caution!
Risk of fire!
Never use flammabel liquids
for cleaning.
Sequence of maintenance measures:
– Check the level of dirt.
– Filter soiling? Replace the filter if necessary.
– Cooling membranes soiled? Clean if necessary.
– Activate test mode; cooling function OK?
– Check noise generation of compressor and fans.

30

Rittal cooling unit assembly and operating instructions

7 Inspection and maintenance
EN

Fig. 40:

Fig. 41:

Remove the lower louvred grille

Fig. 42:

Disconnect the connector from the display (1)

Fig. 43:

Disconnect the connector from the display (2)

Remove the infill panel

Rittal cooling unit assembly and operating instructions

31

7 Inspection and maintenance
EN

Fig. 47:

Disconnect the fan connectors

Fig. 44:

Cooling unit without grille

Fig. 48:

Dismantle cover (loosen 4 nuts)

Fig. 45:

Remove the external circuit fan
(loosen the four screws)

Fig. 49:

Push back the display cable

Fig. 46:

Remove the fan

Fig. 50:

Push the display cable through the cable gland

32

Rittal cooling unit assembly and operating instructions

7 Inspection and maintenance
EN

Fig. 51:

Fig. 52:

Fig. 53:

Loosen the earthing cable between the cover
and the chassis (1)

Fig. 54:

Loosen the earthing cable between the cover
and the chassis (2)

Fig. 55:

Clean out the heat exchanger coil and compressor
chamber using compressed air (1)

Remove the cover (1)

Remove the cover (2)

Rittal cooling unit assembly and operating instructions

33

7 Inspection and maintenance
EN

Fig. 56:

Clean out the heat exchanger coil and compressor
chamber using compressed air (2)

Fig. 58:

Remove the upper louvred grille (1)

Fig. 59:

Remove the upper louvred grille (2)

7.1.2 Compressed air cleaning
SK 3328.xxx, SK 3329.xxx, SK 3332.xxx

Fig. 57:

34

Disconnect the power cord

Rittal cooling unit assembly and operating instructions

7 Inspection and maintenance
EN

Fig. 60:

Remove the upper louvred grille (3)

Fig. 62:

Remove the lower louvred grille (2)

Fig. 61:

Remove the lower louvred grille (1)

Fig. 63:

Remove the infill panel

Rittal cooling unit assembly and operating instructions

35

7 Inspection and maintenance
EN

Fig. 64:

Disconnect the display cable

Fig. 68:

Remove the external circuit fan

Fig. 65:

Push back the display cable and press it through
the cable gland (1)

Fig. 69:

Disconnect the fan connectors (1)

Fig. 66:

Push back the display cable and press it through
the cable gland (2)

Fig. 70:

Disconnect the fan connectors (2)

Fig. 67:

Loosen the four screws of the external circuit fan

Fig. 71:

Disconnect the fan connectors (3)

36

Rittal cooling unit assembly and operating instructions

7 Inspection and maintenance
EN

Fig. 72:

Disconnect the fan earthing cable (1)

Fig. 73:

Disconnect the fan earthing cable (2)

Fig. 75:

Remove the cover

Fig. 74:

Loosen the four nuts of the cover

Fig. 76:

Disconnect the earthing cable (1)

Rittal cooling unit assembly and operating instructions

37

7 Inspection and maintenance
EN

Fig. 77:

Disconnect the earthing cable (2)

Fig. 79:

Clean out the heat exchanger coil and compressor
chamber using compressed air (2)

Fig. 78:

Clean out the heat exchanger coil and compressor
chamber using compressed air (1)

Fig. 80:

Clean out the heat exchanger coil and compressor
chamber using compressed air (3)

38

Rittal cooling unit assembly and operating instructions

8 Storage and disposal
8

Storage and disposal

9

Technical specifications

EN

Caution! Risk of damage!
The cooling unit must not be subjected
to temperatures above +70°C during
storage.
During storage, the cooling unit must stand upright.
The closed cooling circuit contains refrigerant and oil
which must be properly disposed of for the sake of
the environment. Disposal can be performed at the
Rittal plant.
Please contact us for advice.

Fig. 81:

Rating plate (technical specifications)

– Observe the mains connection data (voltage and
frequency) as per the rating plate.
– Observe the pre-fuse as per the specifications on
the rating plate.

Rittal cooling unit assembly and operating instructions

39

9 Technical specifications
EN

Unit

Model No. SK

Basic controller,
RAL 7035

–

3302.100

3302.110

3302.300

3302.310

–

–

–

–

Basic controller,
stainless steel

–

3302.200

3302.210

–

–

–

–

–

–

e-Comfort controller,
RAL 7035

–

–

–

–

–

3303.500

3303.510

3304.500

3304.510

e-Comfort controller,
NEMA 4X

–

–

–

–

–

3303.504

3303.514

3304.504

3304.514

e-Comfort controller,
stainless steel cover

–

–

–

–

–

3303.600

3303.610

3304.600

3304.610

Rated voltage

V
Hz

230, 1~,
50/60

115, 1~,
60

230, 1~,
50/60

115, 1~,
60

230, 1~,
50/60

115, 1~,
60

230, 1~,
50/60

115, 1~,
50/60

Rated current

A

1.6/1.7

3.3

1.6/1.7

4.0

2.6/2.6

5.7

3.9/4.3

8.0/8.8

Start-up current

A

3.0/3.4

8.0

4.3/5.3

12.0

5.1/6.4

11.5

12.0/14.0

26.0/28.0

Pre-fuse T

A

10.0

10.0

10.0

10.0

10.0

10.0

10.0

11.0 – 16.0

Motor circuit-breaker

–

–

–

–

–

–

–

–

–

Transformer circuit-breaker

–

–

–

–

–

–

–

–

䡲

Miniature circuit breaker or
fuse gG (T)

–

䡲

䡲

䡲

䡲

䡲

䡲

䡲

–

.

Useful cooling output Qk
to DIN 3168

L 35 L 35
L 35 L 50

W
W

300/320
150/170

300
150

300/320
150/160

300
150

500/610
280/350

500
280

1000/1450
1050/1100

1000/1450
980/1050

Power consumption Pel
to DIN 3168

L 35 L 35
L 35 L 50

W
W

245/255
255/275

290
340

285/300
320/340

290
340

360/380
420/390

470
500

640/720
750/850

670/750
780/880

1.2

1.2

1.1

1.1

1.4

1.4

1.6

1.6

R134a
100

R134a
100

R134a
100

R134a
95

R134a
170

R134a
170

R134a
325

R134a
325

25

25

25

25

28

28

25

25

.

Refrigeration factor H = Qk/Pel
Refrigerant
– Type
– Filling

–
g

Admissible pressure

bar

Temperature setting range

°C

+20 to +55

+20 to +55

+20 to +55

+20 to +55

+20 to +55

+20 to +55

+20 to +55

+20 to +55

Setting range

°C

+30 to +55

+30 to +55

+30 to +55

+30 to +55

+20 to +55

+20 to +55

+20 to +55

+20 to +55

< 61

< 61

< 61

< 61

< 61

< 64

< 64

Noise level

dB (A) < 61

Protection category to EN 60 529
– Internal circuit
– External circuit

–
–

IP 54
IP 34

Protection category

–

(NEMA 4X)1)

Dimensions (W x H x D)

mm

280 x 550 x 140

525 x 340 x 153

280 x 550 x 206
(285 x 620 x 298)1)

400 x 950 x 260
(405 x 1020 x 358)1)

Weight

kg

13

13

17 (25)1)

39 (49)1)

1) Information

40

13

17

17 (25)1)

44 (54)1)

relevant for NEMA 4X

Rittal cooling unit assembly and operating instructions

9 Technical specifications
Unit

Model No. SK

e-Comfort controller,
RAL 7035

–

3304.540

3305.500

3305.510

3305.540

3328.500

3328.510

3328.540

3329.500

e-Comfort controller,
NEMA 4X

–

3304.544

3305.504

3305.514

3305.544

3328.504

3328.514

3328.544

3329.504

e-Comfort controller,
stainless steel cover

–

3304.640

3305.600

3305.610

3305.640

3328.600

3328.610

3328.640

3329.600

400, 3~, 50/ 230, 1~,
460, 3~, 60 50/60

115, 1~,
50/60

400, 3~, 50/ 230, 1~,
460, 3~, 60 50/60

115, 1~,
50/60

400, 3~, 50/ 230, 1~,
460, 3~, 60 50/60

EN

Rated voltage

V, Hz

Rated current

A

2.2/2.1

5.5/5.8

11.5/12.5

2.5/2.8

6.1/6.6

13.4/14.8

2.8/3.3

8.2/9.3

Start-up current

A

11.5/12.7

22.0/24.0

26.0/28.0

12.2/11.3

20.0/22.0

40.0/38.0

6.8/7.8

20.0/24.0

Pre-fuse T

A

6.3 – 10.0

16.0

14.0 – 20.0

6.3 – 10.0

16.0

18.0 – 25.0

6.3 – 10.0

16.0

Motor circuit-breaker

–

䡲

–

–

䡲

–

–

䡲

–

Transformer circuit-breaker

–

–

–

䡲

–

–

䡲

–

–

Miniature circuit breaker or
fuse gG (T)

–

–

䡲

–

–

䡲

–

–

䡲

Useful cooling output Qk L 35 L 35
to DIN 3168
L 35 L 50

W
W

1000/1460
880/990

1500/1510
1150/1200

1500/1660
1150/1270

1500/1510
1230/1250

2000/2360
1620/1745

2000/2360
1620/1745

2000/2350
1450/1690

2500/2660
1840/1920

L 35 L 35
L 35 L 50

W
W

670/820
760/930

870/980
1030/1150

1010/900
1180/1060

820/1000
980/1170

935/1055
1080/1250

965/1085
1110/1280

920/1145
1145/1395

1270/1410
1470/1700

1.7

1.7

1.5

1.8

2.1

2.1

2.2

2.0

R134a
325

R134a
600

R134a
600

R134a
600

R134a
950

R134a
950

R134a
950

R134a
950

28

28

28

< 64

< 64

.

Power consumption Pel
to DIN 3168
.

Refrigeration factor H = Qk/Pel
Refrigerant
– Type
– Filling

–
g

Admissible pressure

bar

25

25

25

25

28

Temperature setting range

°C

+20 to +55

+20 to +53

+20 to +53

+20 to +55

+20 to +55 (+20 to +50)1)

°C

+20 to +55

Setting range
Noise level

dB (A) < 64

Protection category to EN 60 529
– Internal circuit
– External circuit

–
–

IP 54
IP 34

Protection category

–

(NEMA 4X)1)

Dimensions (W x H x D)
Weight
1) Information

mm
kg

+20 to +50

+20 to +50

+20 to +55

+20 to +55 (+20 to +50)1)

< 64

< 64

< 64

< 64

400 x 950 x 260 (405 x 1020 x 358)1)
40

(50)1)

41

(51)1)

46

(56)1)

< 64

400 x 1580 x 295 (405 x 1650 x 388)1)
42

(52)1)

66 (80)1)

73 (87)1)

67 (80)1)

69 (83)1)

relevant for NEMA 4X

Rittal cooling unit assembly and operating instructions

41

9 Technical specifications
Model No. SK

Unit

EN

e-Comfort controller, RAL 7035

–

3329.510

3329.540

3332.540

3361.500

3361.510

e-Comfort controller, NEMA 4X

–

3329.514

3329.544

–

–

–

–

e-Comfort controller, stainless steel cover

–

3329.610

3329.640

3332.640

3361.600

3361.610

3361.640

Rated voltage

V, Hz

115, 1~,
50/60

400, 3~, 50/
460, 3~, 60

400, 3~, 50/
460, 3~, 60

230, 1~,
50/60

115, 1~,
60

400, 2~,
50/60

Rated current

A

17.0/20.0

3.7/3.8

4.2/4.2

2.7/2.7

5.3

1.2/1.4

Start-up current

A

44.0/42.0

6.8/7.6

9.2/11.0

6.0/9.6

12.0

3.1/3.3

Pre-fuse T

A

18.0 – 25.0

6.3 – 10.0

6.3 – 10.0

10.0

10.0

6.3 – 10.0

Motor circuit-breaker

–

–

䡲

䡲

–

–

–

Transformer circuit-breaker

–

䡲

–

–

–

–

䡲

Miniature circuit breaker or fuse gG (T)

–

–

–

–

䡲

䡲

–

.

3361.540

Useful cooling output Qk
to DIN 3168

L 35 L 35
L 35 L 50

W
W

255/2660
1840/1920

2500/2700
1900/1950

4000/4400
3070/3570

750/790
570/570

750
500

750/790
570/570

Power consumption Pel
to DIN 3168

L 35 L 35
L 35 L 50

W
W

1300/1440
1500/1730

1295/1495
1545/1845

1720/2120
1990/2460

420/450
480/510

570
670

420/450
480/510

1.9

1.9

2.3

1.8

1.3

1.7

R134a
950

R134a
950

R134a
3000

R134a
280

R134a
260

R134a
280

28

28

28

.

Refrigeration factor H = Qk/Pel
Refrigerant
– Type
– Filling

–
g

Admissible pressure

bar

28

Temperature setting range

°C

+20 to +55 (+20 to +50)1)

Setting range

°C

+20 to +55 (+20 to +50)1)

Noise level

dB (A)

< 64

Protection category to EN 60 529
– Internal circuit
– External circuit

–
–

IP 54
IP 34

Protection category

–

(NEMA 4X)1)

Dimensions (W x H x D)

mm

Weight
1) Information

kg

< 64

400 x 1580 x 295
(405 x 1650 x 388)1)
76

(90)1)

70

< 64

< 64

28

28

+20 to +52

+20 to +55

+20 to +52

+20 to +55

< 64

< 64

500 x 1580 x 340 280 x 550 x 206
(83)1)

91

22

22

Model No. SK

Unit
e-Comfort controller, RAL 7035

–

3366.500

3366.510

3366.540

e-Comfort controller, stainless steel cover

–

3366.600

3366.610

3366.640

V, Hz

230, 1~,
50/60

115, 1~,
50/60

400, 3~, 50/
460, 3~, 60
2.7/2.9

Rated voltage
Rated current

A

6.7/6.9

13.6/13.8

Start-up current

A

22.0/24.0

43.0/47.0

8.0/8.8

Pre-fuse T

A

10.0

14.0 – 20.0

6.3 – 10.0

Motor circuit-breaker

–

–

–

䡲

Transformer circuit-breaker

–

–

䡲

–

–

䡲

–

–

Useful cooling output Qk
to DIN 3168

L 35 L 35
L 35 L 50

W
W

1500/1500
1050/1100

1500/1500
1050/1100

1500/1500
980/1080

Power consumption Pel
to DIN 3168

L 35 L 35
L 35 L 50

W
W

940/1070
1115/1230

940/1070
1115/1230

970/1120
1140/1310

1.6

1.6

1.5

R134a
700

R134a
700

R134a
700

Miniature circuit breaker or fuse gG (T)
.

.

Refrigeration factor H = Qk/Pel
Refrigerant
– Type
– Filling

–
g

Admissible pressure

bar

28

28

28

Temperature setting range

°C

+20 to +55

+20 to +55

+20 to +55

Setting range

°C

+20 to +55

+20 to +55

+20 to +55

72

72

72

49

46

Noise level
Protection category to EN 60 529
– Internal circuit
– External circuit

dB (A)
–
–

IP 54
IP 34

Dimensions (W x H x D)

mm

450 x 1590 x 195

Weight

kg

45

42

22

relevant for NEMA 4X

Rittal cooling unit assembly and operating instructions

10 List of spare parts
10 List of spare parts

EN

75

SK 3302.xxx
40

10

71

25
45
1

100

55

71
90
15

5

Fig. 82:

Spare parts for SK 3302.xxx

SK 3302.3xx
10

90
71 20

71

25

100

45

40

1

5

15

55

Fig. 83:

Spare parts for SK 3302.3xx

Rittal cooling unit assembly and operating instructions

43

10 List of spare parts
EN

SK 3303.xxx
SK 3361.xxx

10
40
71
30
75

25
1

45

15
55

100

90
5
71

71
20
71

Fig. 84:

Spare parts for SK 3303.xxx, SK 3361.xxx

SK 3304.xxx
SK 3305.xxx

10

40
71

30
102
75

1
45
25
100
71

50

80

15

20
55

90
45

5
71
71
101

Fig. 85:
44

Spare parts for SK 3304.xxx, SK 3305.xxx
Rittal cooling unit assembly and operating instructions

10 List of spare parts
75

SK 3328.xxx
SK 3329.xxx

EN

10

40

46
71
30

102

45

71
20
50
1

55

100
45

46
90

80

5
71
71

15

101

Fig. 86:

Spare parts for SK 3328.xxx, SK 3329.xxx

75

SK 3332.xxx

10

46
40
71

102
45
25
100

50
55
1
45

71
90

46
71

71
20

15

5
30

101

Fig. 87:

Spare parts for SK 3332.xxx

Rittal cooling unit assembly and operating instructions

45

10 List of spare parts
EN

SK 3366.xxx

75

75

100
40

46

10

71

102
45
20
90
50

30

71

55
1
25
45

101
46
5

80

15

Fig. 88:

Spare parts for SK 3366.xxx, SK 3377.xxx

Legend
1
Compressor
5
Condenser fan
10 Evaporator fan
15 Dispatch bag
20 Expansion valve
25 Filter dryer
30 PSAH pressure-operated switch
40 Controller board
45 Louvred grille 1
46 Louvred grille 2
50 Infill panel
55 Display
71 Temperature sensor
75 Enclosure tray
80 Transformer
90 Evaporator coil
100 Condenser
101 Condensate evaporator
102 Miniature fuse, condensate evaporator
(T4A; 6.3 x 32 mm)

46

Note:
As well as the spare part number, when
ordering spare parts the following information must be provided:
– Unit model
– Fabrication number
– Date of manufacture
This information may be found
on the rating plate.

Rittal cooling unit assembly and operating instructions

11 Appendix: Cut-out and hole sizes
11 Appendix:
Cut-out and hole sizes

353

11.1 Dimensions for external mounting

EN

55

340

260

78.5

354

326

251

360

280
140

85.5

Fig. 92:

49
Ø8
155
(10x)

260

354

165.5

501

550

353

360

354

354

SK 3366.xxx, SK 3377.xxx external mounting

250

350

260

280

32.5

SK 3302.xxx external mounting
(except SK 3302.3xx)

255

400

Fig. 89:

525
6

385

350

281

340

950

Ø 9.5 (8x)

255

153

471

25

15

350

Fig. 93:
Fig. 90:

SK 3304.xxx, SK 3305.xxx external mounting

SK 3302.3xx external mounting
35

400
280

295

262

350

380

206
310

15.5

280

1580

550

532

480

550

266

Ø 13 (10x)

25

275

SK 3303.xxx, SK 3361.xxx external mounting
340

Fig. 91:

320

325

260

Ø 8 (4x)

Fig. 94:

Rittal cooling unit assembly and operating instructions

SK 3328.xxx, SK 3329.xxx external mounting

47

11 Appendix: Cut-out and hole sizes
400

500

370

340

380

145

440

380

320

150

R9.5 (2x)

1580

500

330

45

EN

1580

1540

1558

1554

25

Fig. 95:

376

275

375

440

360

164

Ø 13 (10x)

Ø 13 (4x)

SK 3332.xxx external mounting

R9.5 (2x)

11.2 Dimensions for partial internal
mounting

320

Fig. 98:

SK 3328.xxx, SK 3329.xxx partial internal mounting

280
100

20

254

106
500
25

145

195

550

497

266

523

524

362

18 x 45

1580

474

1530

1550

Ø 8 (4x)

(230)

Fig. 96:

SK 3303.xxx, SK 3361.xxx partial internal mounting
Ø 13 (4x)
400
370
105

330

155

Fig. 99:

380

SK 3332.xxx partial internal mounting

920

920

950

25 x 45

Ø 9.5 (4x)

Fig. 97:

48

SK 3304.xxx, SK 3305.xxx partial internal mounting

Rittal cooling unit assembly and operating instructions

11 Appendix: Cut-out and hole sizes
11.3 Dimensions for full internal mounting
98

280

210

370
25

R6 (4x)

25

200

EN

400
42

254

25 x 45

2

50

920

950

920

550

266

518

492

524

Ø 15 (2x)

380

Ø 8 (4x)

18 x 45°
Ø 9.5 (4x)

(230)

Fig. 100: SK 3302.1xx full internal mounting

98

55

Fig. 103: SK 3304.xxx, SK 3305.xxx full internal mounting

525
510

400
370
245

50

R9.5 (2x)

325

20 x 45

314

340

320

Ø 7.5 (4x)

Fig. 101: SK 3302.3xx full internal mounting

376

1580

1540

1558

1554

499

42
280

164

25

254
200

Ø 13 (4x)

Ø 19 (2x)
R9.5 (2x)

550

518

492

524

320
266

Fig. 104:

SK 3328.xxx, SK 3329.xxx full internal mounting

18 x 45°
45

Ø 8 (4x)
400

5

R9

200
(230)

1500
45

1510

Fig. 102: SK 3303.xxx, SK 3361.xxx full internal mounting

Fig. 105:

Rittal cooling unit assembly and operating instructions

SK 3366.xxx, SK 3377.xxx full internal mounting

49

䡲
䡲
䡲
䡲

1st edition 07.2011 / ID no. 328 124 / Drawing no. A4491200SK23

䡲

Enclosures
Power Distribution
Climate Control
IT Infrastructure
Software & Services

RITTAL GmbH & Co. KG
Postfach 1662 䡠 D-35726 Herborn
Phone +49(0)2772 505-0 䡠 Fax +49(0)2772 505-2319
E-mail: info@rittal.de 䡠 www.rittal.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : 3.1-701
Producer                        : Acrobat Distiller 8.2.0 (Windows)
Creator Tool                    : FrameMaker 8.0
Modify Date                     : 2011:08:22 09:34:21+02:00
Create Date                     : 2011:08:10 15:02:07+02:00
Metadata Date                   : 2011:08:22 09:34:21+02:00
Format                          : application/pdf
Title                           : 03_innen_engl_sk_3302.fm
Creator                         : TYPOGRAFIK
Document ID                     : uuid:7ede3987-ed1a-4e64-ba18-f51860b438b6
Instance ID                     : uuid:760efd60-2413-41bf-9a7a-1f865e327cd4
Page Count                      : 50
Author                          : TYPOGRAFIK
EXIF Metadata provided by EXIF.tools

Navigation menu