Omron F3SJ Safety Light Curtain Datasheet

2014-11-11

: Pdf 552406-Attachment 552406-Attachment 006085 Batch12 unilog

Open the PDF directly: View PDF PDF.
Page Count: 88

DownloadOmron F3SJ Safety Light Curtain Datasheet
Open PDF In BrowserView PDF
Safety Light Curtain (Type 4)
F3SJ Ver. 2

New Models for Body
Protection or Presence
Detection
OMRON Corporation
Industrial Automation Company
Safety Devices Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)75-344-7093/Fax: (81)75-344-8197

Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388

OMRON SCIENTIFIC TECHNOLOGIES INC.
6550 Dumbarton Circle Fremont,
CA 94555-3605 U.S.A.
Tel: (1)510-608-3400/Fax: (1)510-744-1442

Authorized Distributor:
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
239920 Singapore
Tel: (65)6835-3011/Fax: (65)6835-2711

OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Road (M),
Shanghai, 200120 China
Tel: (86)21-5037-2222/Fax: (86)21-5037-2200

Cat. No. F074-E1-06

Note: Specifications subject to change without notice.

Printed in Japan
0207-1M (0605) (H)

Continuing advances in the F3SJ help to
create even safer production systems.
The new F3SJ will satisfy your safety needs. Two new
tools make this Safety Light Curtain easier to set up and
use. The first is a newly developed setting support
software that allows all parameters to be set and the
system status to be checked with a personal computer.
The second is a Setting Console that lets you easily set
parameters and check the system status without having
to bring a personal computer to the worksite.
A number of new functions have also been provided to
ensure that you can use the Safety Light Curtain without
lowering productivity.
As a result, you can boost the safety of applications that
previously did not lend themselves to the use of a Safety
Light Curtain.

Choose from two new tools for setting parameters
and checking the system status.
"SD Manager" PC Setting Support Software

F3SJ

To a USB terminal

F39-JC@A Singleend Connector Cable or F39-JC@B
Double-end Connector Cable

Branch
Connector
Connection Cable

All parameters can be set and the system status
can be checked with a personal computer. In
addition to making it easy to monitor the beam
alignment, the ambient incident light intensity
can be displayed in bar graph form for an easy
check of the system status.

F39-GWUM "SD
Manager" PC Setting
Support Software

The "SD Manager" PC Setting Support Software helps reduce the time required for installing and troubleshooting the Safety Light Curtain.
● Beam alignment is easier.

● The ambient incident light intensity can be checked. ● The error log can be displayed.

The incident light level can be displayed
in a bar graph for each beam.

The incident light level when the light
emission of the Safety Light Curtain is
stopped is displayed in a bar graph.

The cause of the errors and
countermeasures are both displayed.

Setting Console

F3SJ

When you don't want to carry a
personal computer onto the
worksite, the Setting Console is a
handy way to set parameters and
check the system status.

● Ver. 2 Label Color

F39-JC@A Singleend Connector Cable or F39-JC@B
Double-end Connector Cable

Ver. 2 models have a yellow label. Models
with a white label are a previous version.

2

Branch
Connector

F39-MC21
Setting Console for the F3SJ
Note: The range of parameter setting and system status
checking capabilities is different for the PC Setting
Support Software and the Setting Console.

3

Continuing advances in the F3SJ help to
create even safer production systems.
The new F3SJ will satisfy your safety needs. Two new
tools make this Safety Light Curtain easier to set up and
use. The first is a newly developed setting support
software that allows all parameters to be set and the
system status to be checked with a personal computer.
The second is a Setting Console that lets you easily set
parameters and check the system status without having
to bring a personal computer to the worksite.
A number of new functions have also been provided to
ensure that you can use the Safety Light Curtain without
lowering productivity.
As a result, you can boost the safety of applications that
previously did not lend themselves to the use of a Safety
Light Curtain.

Choose from two new tools for setting parameters
and checking the system status.
"SD Manager" PC Setting Support Software

F3SJ

To a USB terminal

F39-JC@A Singleend Connector Cable or F39-JC@B
Double-end Connector Cable

Branch
Connector
Connection Cable

All parameters can be set and the system status
can be checked with a personal computer. In
addition to making it easy to monitor the beam
alignment, the ambient incident light intensity
can be displayed in bar graph form for an easy
check of the system status.

F39-GWUM "SD
Manager" PC Setting
Support Software

The "SD Manager" PC Setting Support Software helps reduce the time required for installing and troubleshooting the Safety Light Curtain.
● Beam alignment is easier.

● The ambient incident light intensity can be checked. ● The error log can be displayed.

The incident light level can be displayed
in a bar graph for each beam.

The incident light level when the light
emission of the Safety Light Curtain is
stopped is displayed in a bar graph.

The cause of the errors and
countermeasures are both displayed.

Setting Console

F3SJ

When you don't want to carry a
personal computer onto the
worksite, the Setting Console is a
handy way to set parameters and
check the system status.

● Ver. 2 Label Color

F39-JC@A Singleend Connector Cable or F39-JC@B
Double-end Connector Cable

Ver. 2 models have a yellow label. Models
with a white label are a previous version.

2

Branch
Connector

F39-MC21
Setting Console for the F3SJ
Note: The range of parameter setting and system status
checking capabilities is different for the PC Setting
Support Software and the Setting Console.

3

New functions respond to
a variety of safety needs.
A number of new functions have been provided to ensure that you can use the Safety
Light Curtain without lowering productivity. This lets you boost the safety of applications
that previously did not lend themselves to the use of a Safety Light Curtain.
Note: The new functions on this page require the use of a setting tool. For details, see page 63 Using Setting Tools.

Two new functions have been added to the muting function.

The blanking function disables specific beams of the Safety Light Curtain.

The muting function temporarily disables the Safety Light Curtain when an object must pass through the detection zone, such
as when supplying a workpiece to your equipment. "Partial muting," which further heightens the level of safety, and "position
detection muting," which allows muting when the safety status can be determined by the position of a machine (such as a
robot), have been newly added to the muting function.

When a part of a machine is located inside the detection zone of the Safety Light Curtain,
the safety output will normally remain OFF and the machine cannot operate. The blanking
function makes it possible to disable specific beams for applications such as this.

● Partial muting

● Fixed blanking

● Floating blanking

Partial muting raises safety by muting only the beams of the Safety
Light Curtain in the area where the workpiece passes through,
while preventing muting in all other areas.

The Safety Light Curtain
beams in all areas other than
where the workpiece passes
through are constantly
ON.

In this case, 2-beam floating
blanking is set. If three or more
beams are interrupted, the
output goes OFF.

The beam that would otherwise be
constantly interrupted by the
workbench is disabled.
Only the beams of the Safety Light Curtain that
would be interrupted by the workpiece are muted.

● Position detection muting
This is used in applications where the workpiece is set in position each time by an
operator, and then a turntable or positioning robot moves the workpiece to the area
where the work is done. A limit switch or other means is used to detect when the
robot is in a safe position, and muting is then applied.

A warning zone can be set to alert people before they enter a danger zone.
For example, you can set the F3SJ to generate only an alarm when someone approaches the danger zone, and to turn OFF
the control output when someone actually enters the danger zone. You can also divide the detection zone for a single F3SJ
into two zones, or set a warning zone for multiple, series-connected F3SJ Units. Plus, the auxiliary output can be used to
activate a flashing lamp as a warning to alert the person before turning OFF the machinery.

● Dividing the zone between series-connected sensors
Detection zone

Warning zone

4

● A single sensor can also be divided
Detection zone

Warning zone

5

New functions respond to
a variety of safety needs.
A number of new functions have been provided to ensure that you can use the Safety
Light Curtain without lowering productivity. This lets you boost the safety of applications
that previously did not lend themselves to the use of a Safety Light Curtain.
Note: The new functions on this page require the use of a setting tool. For details, see page 63 Using Setting Tools.

Two new functions have been added to the muting function.

The blanking function disables specific beams of the Safety Light Curtain.

The muting function temporarily disables the Safety Light Curtain when an object must pass through the detection zone, such
as when supplying a workpiece to your equipment. "Partial muting," which further heightens the level of safety, and "position
detection muting," which allows muting when the safety status can be determined by the position of a machine (such as a
robot), have been newly added to the muting function.

When a part of a machine is located inside the detection zone of the Safety Light Curtain,
the safety output will normally remain OFF and the machine cannot operate. The blanking
function makes it possible to disable specific beams for applications such as this.

● Partial muting

● Fixed blanking

● Floating blanking

Partial muting raises safety by muting only the beams of the Safety
Light Curtain in the area where the workpiece passes through,
while preventing muting in all other areas.

The Safety Light Curtain
beams in all areas other than
where the workpiece passes
through are constantly
ON.

In this case, 2-beam floating
blanking is set. If three or more
beams are interrupted, the
output goes OFF.

The beam that would otherwise be
constantly interrupted by the
workbench is disabled.
Only the beams of the Safety Light Curtain that
would be interrupted by the workpiece are muted.

● Position detection muting
This is used in applications where the workpiece is set in position each time by an
operator, and then a turntable or positioning robot moves the workpiece to the area
where the work is done. A limit switch or other means is used to detect when the
robot is in a safe position, and muting is then applied.

A warning zone can be set to alert people before they enter a danger zone.
For example, you can set the F3SJ to generate only an alarm when someone approaches the danger zone, and to turn OFF
the control output when someone actually enters the danger zone. You can also divide the detection zone for a single F3SJ
into two zones, or set a warning zone for multiple, series-connected F3SJ Units. Plus, the auxiliary output can be used to
activate a flashing lamp as a warning to alert the person before turning OFF the machinery.

● Dividing the zone between series-connected sensors
Detection zone

Warning zone

4

● A single sensor can also be divided
Detection zone

Warning zone

5

Selecting a device is as easy as 1-2-3.

Easier to install,
easier to use.

The thin sensor saves valuable space.
The sensor is 6 mm thinner than our previous models. When
you include the newly designed mounting brackets, which
also enable beams to be aligned after the sensor is mounted,
the total thickness is 26 mm - a reduction of 19 mm compared
to previous models. The low profile means the sensor will not
get in the way when adding safety applications to existing
equipment.

Select the required sensor length.
The F3SJ incorporates the "perfect fit" concept that is a
feature of OMRON's other Safety Light Curtains. With a lineup of products in 1-beam increments, you can find the
sensor that fits your setup perfectly. Refer to the list of
sensor models on pages 13 and 15 to select the minimum
sensor length required to cover the area you want to protect.
Note: We can also manufacture sensors with lengths not included in the list
of models. For details, please consult your OMRON sales
representative.

Sensor length = Protective height

2500 mm
Maximum

Previous model

30 mm

F3SJ

24 mm

245 mm
Minimum

Choose the PNP type when installing in safety system
configurations that comply with the Machinery Directive or
when using with a dedicated controller (F3SP-B1P or F3SX).
NPN types are also available as standard products when
replacing existing area sensors.

The direction of all screws can be
oriented perpendicular to the lens
surface. Easy screwdriver access.

2 mm

15 mm

45 mm

The F3SJ cables (0.3 m) have M12 connectors and can be
routed in any direction. Problems with connector
compatibility have been eliminated.

Select the application.

Protective height

Note: After selecting the type of device, calculate the safety distance
described on page 60 and change your selection if necessary.

P

PNP
output

N

NPN
output

14
20
30
55

Output type

Finger
Hand
Hand/arm
Leg/body-protection and
Presence Detection

The sensor can be rotated along
its axis. Beam alignment can be
fine-tuned, even when mounted
side by side on a surface.

26 mm

Flexible cable with a 5 mm bending
radius makes wiring a snap.

(0245 to 2495 mm)

The included mounting brackets, which are suitable for
general use, have been redesigned with ease of use in mind.
The new design allows easy screwdriver access, even when
mounting in tight spaces.
Also, after aligning the beams, screws can be tightened
while oriented perpendicular to the lens surface, just like the
panel mounting screws. On previous models, the carefully
adjusted beam angles would sometimes come out of
alignment when tightening the final screws. This problem has
been solved with the F3SJ, because the screw-tightening
direction is different from the angle adjustment direction. The
result is reduced installation time.
Previous model F3SJ

Select the output transistor.

In addition to finger protection, hand protection, and
hand/arm protection models, new models have been added
that detects a leg or the presence of a person.
For areas where there is only a short distance to the source F3SJ-A
of danger, select a finger protection model. For areas
where there is some distance to the hazardous point and
where the machinery stops with sufficient time to spare,
choose an economical hand/arm/body protection model.

The included standard mounting
brackets are easier than ever to use.

Side-mounting in tight spaces is simple.
When using standard mounting brackets to mount a sensor
on its side, the bracket protrudes outward in front of the lens
surface. When this protrusion is of concern, use the F39-LJ2
side-mounting brackets (sold separately).

Free-directional cables can be
routed down, back, left or right.
10 mm

Detection type

Hand-protection Detection

Easy to change from previous models.

Capability: 20 mm
diameter (Beam gap: 15
mm)

When replacing your previous standard multiple-beam area
sensor, use the F39-LJ4 top / bottom mounting bracket B
(sold separately), which features enlarged mounting holes.

Flexible cables with 5 mm
bending radius can be
adhesively mounted to the
floor.

Can be used with a pitch of 18 to 20 mm

6 mm
Capability: 30 mm
diameter (Beam gap: 25
mm)

6

Finger-protection
Detection

Hand-protection
Detection

Hand/arm-protection
Detection

Leg/body-protection and
Presence Detection

Capability: 14 mm diameter
(Beam gap: 9 mm)

Capability: 20 mm diameter
(Beam gap: 15 mm)

Capability: 30 mm diameter
(Beam gap: 25 mm)

Capability: 55 mm diameter
(Beam gap: 50 mm)

37 mm

7

Selecting a device is as easy as 1-2-3.

Easier to install,
easier to use.

The thin sensor saves valuable space.
The sensor is 6 mm thinner than our previous models. When
you include the newly designed mounting brackets, which
also enable beams to be aligned after the sensor is mounted,
the total thickness is 26 mm - a reduction of 19 mm compared
to previous models. The low profile means the sensor will not
get in the way when adding safety applications to existing
equipment.

Select the required sensor length.
The F3SJ incorporates the "perfect fit" concept that is a
feature of OMRON's other Safety Light Curtains. With a lineup of products in 1-beam increments, you can find the
sensor that fits your setup perfectly. Refer to the list of
sensor models on pages 13 and 15 to select the minimum
sensor length required to cover the area you want to protect.
Note: We can also manufacture sensors with lengths not included in the list
of models. For details, please consult your OMRON sales
representative.

Sensor length = Protective height

2500 mm
Maximum

Previous model

30 mm

F3SJ

24 mm

245 mm
Minimum

Choose the PNP type when installing in safety system
configurations that comply with the Machinery Directive or
when using with a dedicated controller (F3SP-B1P or F3SX).
NPN types are also available as standard products when
replacing existing area sensors.

The direction of all screws can be
oriented perpendicular to the lens
surface. Easy screwdriver access.

2 mm

15 mm

45 mm

The F3SJ cables (0.3 m) have M12 connectors and can be
routed in any direction. Problems with connector
compatibility have been eliminated.

Select the application.

Protective height

Note: After selecting the type of device, calculate the safety distance
described on page 60 and change your selection if necessary.

P

PNP
output

N

NPN
output

14
20
30
55

Output type

Finger
Hand
Hand/arm
Leg/body-protection and
Presence Detection

The sensor can be rotated along
its axis. Beam alignment can be
fine-tuned, even when mounted
side by side on a surface.

26 mm

Flexible cable with a 5 mm bending
radius makes wiring a snap.

(0245 to 2495 mm)

The included mounting brackets, which are suitable for
general use, have been redesigned with ease of use in mind.
The new design allows easy screwdriver access, even when
mounting in tight spaces.
Also, after aligning the beams, screws can be tightened
while oriented perpendicular to the lens surface, just like the
panel mounting screws. On previous models, the carefully
adjusted beam angles would sometimes come out of
alignment when tightening the final screws. This problem has
been solved with the F3SJ, because the screw-tightening
direction is different from the angle adjustment direction. The
result is reduced installation time.
Previous model F3SJ

Select the output transistor.

In addition to finger protection, hand protection, and
hand/arm protection models, new models have been added
that detects a leg or the presence of a person.
For areas where there is only a short distance to the source F3SJ-A
of danger, select a finger protection model. For areas
where there is some distance to the hazardous point and
where the machinery stops with sufficient time to spare,
choose an economical hand/arm/body protection model.

The included standard mounting
brackets are easier than ever to use.

Side-mounting in tight spaces is simple.
When using standard mounting brackets to mount a sensor
on its side, the bracket protrudes outward in front of the lens
surface. When this protrusion is of concern, use the F39-LJ2
side-mounting brackets (sold separately).

Free-directional cables can be
routed down, back, left or right.
10 mm

Detection type

Hand-protection Detection

Easy to change from previous models.

Capability: 20 mm
diameter (Beam gap: 15
mm)

When replacing your previous standard multiple-beam area
sensor, use the F39-LJ4 top / bottom mounting bracket B
(sold separately), which features enlarged mounting holes.

Flexible cables with 5 mm
bending radius can be
adhesively mounted to the
floor.

Can be used with a pitch of 18 to 20 mm

6 mm
Capability: 30 mm
diameter (Beam gap: 25
mm)

6

Finger-protection
Detection

Hand-protection
Detection

Hand/arm-protection
Detection

Leg/body-protection and
Presence Detection

Capability: 14 mm diameter
(Beam gap: 9 mm)

Capability: 20 mm diameter
(Beam gap: 15 mm)

Capability: 30 mm diameter
(Beam gap: 25 mm)

Capability: 55 mm diameter
(Beam gap: 50 mm)

37 mm

7

A variety of features
are provided for easier use.

Select the configuration that best
meets your safety needs.
The F3SJ-A Safety Light Curtain is a Type 4 safety sensor that can be used to configure a Category 4
safety circuit. Several suggested configurations that are ideal for a variety of safety needs are outlined
below.

Resistant to mutual interference. No wiring between
sensors and no interference for up to three sets.

Space-efficient and low-cost system
This configuration, which only OMRON can provide, features a sensor unit with
an output feedback function required for Safety Category 4. Simply by using a
pair G7SA or G7S-E Safety Relays, you can easily and economically configure
a Category 4 safety circuit.

● Low-cost and
space-efficient
The built-in external device
monitoring function
eliminates the need for a
Safety Relay Unit.

No Safety Relay Unit

F39-JC@A
G7SA

A welded contact
detection circuit can
be created using two
Safety Relays.

Contactor

Motor

OMRON has developed a unique interference light prevention algorithm that
automatically prevents malfunction, even when light is received from three sets.
This feature is ideal for applications
where it is not possible to perform wiring
with an interference sensor, such as
A G V
between an AGV and installed equipment.
Also, the Setting Tool can be used to
adjust the emitted light intensity to
minimize the effect of light on other
devices.
(Updated function)

Wire-saving configuration
Using single Safety Relays requires a lot of labor for wiring. To simplify the connection process, use
F39-JC@B Double-end Connector Cable and an F3SP-B1P Dedicated Controller. (Use a PNP type
for this configuration. NPN types cannot be connected when using an F3SP-B1P Relay.)

● Reduced wiring and
easy maintenance

25 mm

Sensors with protective heights of up to nearly 2.5 meters are available for
applications that involve large-sized workpieces. And if you happen to make changes
in the future, you can always extend the protective height with series connections. Up
to four sets, or 400 beams, can be series-connected, and with series connection
cables up to 15 meters in length, applications can cover a wide area.

Connector type

Cables with connectors on
both ends simplify
connection, and prevent
wiring errors.
F39-JC@B

Series connection cable up to 15 m long

Maximum protective height of 2,500 mm.
Series connection is more convenient than ever.

F3SP-B1P
Dedicated Controller

Contactor

Motor

20 mm gap between end beams when
connected side by side

Approx. 2.5 m (100 beams)

Total length: Approx. 10 m (400 beams)

No bottlenecks in workflow. Free-location brackets
Side-by-side Series
Connection Cable
make vertical installation easy.

Multi-input safety circuit configuration
When an emergency stop switch or door switch is used with the F3SJ-A Safety
Light Curtain, the safety circuit may become complex, making circuit design
difficult. For this, we recommend using the F3SX Safety Controller. Select the
model that best matches the required input combination. Use an F39-CN5
Branch Connector (sold separately) to significantly reduce the amount of labor
required for wiring to the terminal block.

To create "perfect fit" installations with no dead zones or extra space when
making series connections in L- or U-shaped configurations, use the F39LJ3 free-location mounting brackets (sold separately) and F39-JJR06L or
F39-JJR15L Side-by-side Series Connection Cable.

(F39-JJR06L)

F39-LJ3 free-location mounting
brackets can be mounted in any
location, without getting in the
way of the adjacent sensor.

25 mm
F39-JC@T
Connector Cable
for F3SX use

Emergency Stop
Switch

■ Application example
U-shaped configuration
25 mm
25 mm

Branch Connector
F39-CN5
F39-JC@B Connector
Cable for F3SJ use
F3SX
Relays with Forcibly Guided Contacts

8

■ Keep a 25-mm beam gap in L-shaped installations.
The cable (F39-JJR06L) does not get in the way
when used in series connections.

9

A variety of features
are provided for easier use.

Select the configuration that best
meets your safety needs.
The F3SJ-A Safety Light Curtain is a Type 4 safety sensor that can be used to configure a Category 4
safety circuit. Several suggested configurations that are ideal for a variety of safety needs are outlined
below.

Resistant to mutual interference. No wiring between
sensors and no interference for up to three sets.

Space-efficient and low-cost system
This configuration, which only OMRON can provide, features a sensor unit with
an output feedback function required for Safety Category 4. Simply by using a
pair G7SA or G7S-E Safety Relays, you can easily and economically configure
a Category 4 safety circuit.

● Low-cost and
space-efficient
The built-in external device
monitoring function
eliminates the need for a
Safety Relay Unit.

No Safety Relay Unit

F39-JC@A
G7SA

A welded contact
detection circuit can
be created using two
Safety Relays.

Contactor

Motor

OMRON has developed a unique interference light prevention algorithm that
automatically prevents malfunction, even when light is received from three sets.
This feature is ideal for applications
where it is not possible to perform wiring
with an interference sensor, such as
A G V
between an AGV and installed equipment.
Also, the Setting Tool can be used to
adjust the emitted light intensity to
minimize the effect of light on other
devices.
(Updated function)

Wire-saving configuration
Using single Safety Relays requires a lot of labor for wiring. To simplify the connection process, use
F39-JC@B Double-end Connector Cable and an F3SP-B1P Dedicated Controller. (Use a PNP type
for this configuration. NPN types cannot be connected when using an F3SP-B1P Relay.)

● Reduced wiring and
easy maintenance

25 mm

Sensors with protective heights of up to nearly 2.5 meters are available for
applications that involve large-sized workpieces. And if you happen to make changes
in the future, you can always extend the protective height with series connections. Up
to four sets, or 400 beams, can be series-connected, and with series connection
cables up to 15 meters in length, applications can cover a wide area.

Connector type

Cables with connectors on
both ends simplify
connection, and prevent
wiring errors.
F39-JC@B

Series connection cable up to 15 m long

Maximum protective height of 2,500 mm.
Series connection is more convenient than ever.

F3SP-B1P
Dedicated Controller

Contactor

Motor

20 mm gap between end beams when
connected side by side

Approx. 2.5 m (100 beams)

Total length: Approx. 10 m (400 beams)

No bottlenecks in workflow. Free-location brackets
Side-by-side Series
Connection Cable
make vertical installation easy.

Multi-input safety circuit configuration
When an emergency stop switch or door switch is used with the F3SJ-A Safety
Light Curtain, the safety circuit may become complex, making circuit design
difficult. For this, we recommend using the F3SX Safety Controller. Select the
model that best matches the required input combination. Use an F39-CN5
Branch Connector (sold separately) to significantly reduce the amount of labor
required for wiring to the terminal block.

To create "perfect fit" installations with no dead zones or extra space when
making series connections in L- or U-shaped configurations, use the F39LJ3 free-location mounting brackets (sold separately) and F39-JJR06L or
F39-JJR15L Side-by-side Series Connection Cable.

(F39-JJR06L)

F39-LJ3 free-location mounting
brackets can be mounted in any
location, without getting in the
way of the adjacent sensor.

25 mm
F39-JC@T
Connector Cable
for F3SX use

Emergency Stop
Switch

■ Application example
U-shaped configuration
25 mm
25 mm

Branch Connector
F39-CN5
F39-JC@B Connector
Cable for F3SJ use
F3SX
Relays with Forcibly Guided Contacts

8

■ Keep a 25-mm beam gap in L-shaped installations.
The cable (F39-JJR06L) does not get in the way
when used in series connections.

9

New functions for extra reliability.

A measure to prevent you from forgetting
to connect a series connection cable.

Combine safety and productivity with a
controller-less muting function.
The muting function temporarily disables the light curtain
when an object must pass through the detection zone, such
as when supplying a workpiece to your equipment.
In the past, this function required a dedicated muting
controller, but now it is built into the F3SJ. To use the muting
function, purchase the F39-CN6 Key Cap for Muting (sold
separately). The muting function is enabled simply by
replacing the Unit's cap with this Key Cap. In addition, a
muting sensor that determines the muting timing, as well as
a muting lamp that communicates the muting status to other
operators, should be connected to the F3SJ.

Built-in muting function

■ No controller required. Simply attach the Key Cap (sold separately) to
the sensor.
F39-CN6
Key Cap for Muting
The Safety Light Curtain can be disabled when
an AGV carrying a workpiece passes through.

Emitter

● Indication Patterns and Light Levels of the Incident Light Level Indicator

1

2

3

4

5

Incident light level

LEVEL-5

From 130 to 170% of control output ON level

LEVEL-4

From 100 to 130% of control output ON level

LEVEL-3

From 75 to 100% of control output ON level

IEC61496-1, IEC61496-2, IEC61508 1998 (SIL3)

EU legislation EN standards

Machinery Directive, EMC Directive, EN61496-1, prEN61496-2, EN61508 2001 (SIL3)

JIS standards

JIS B9704-1, B9704-2

North American standards

UL61496-1, UL61496-2, UL508, UL1998, CAN/CSA22.2 NO.14, CAN/CSA22.2 NO.0.8

Can also be used with equipment subject to US OSHA standards (29 CFR 1910.212).
Satisfies the requirements of the ANSI/RIA R15.06-1999 standards for industrial robots.

cUL

From 50 to 75% of control output ON level

LEVEL-2

Less than 50% of control output ON level

LEVEL-1
● Error Mode Indication Patterns and Causes of Errors

ERROR-B
OFF

ERROR-A

International standards

ON

170% or higher of control output ON level

ERROR-C

The connectors for series connection feature an intelligent
design. To connect a series connection cable to the F3SJ,
remove the Key Cap that is required when the sensor is used by
itself. If you should happen to forget to connect the series
connection cable, the sensor will not operate by itself without the
Key Cap. This solves the problem of sensors operating
independently when a series connection cable is accidentally left
unconnected, such as when equipment is moved.

Like previous Type 4 Safety Light Curtains, the F3SJ conforms to the latest
required safety standards and regulations. Since the F3SJ also complies with
IEC61508, the international standard for functional safety, safety is ensured
regardless of where it is used.

OFF

Receiver

Does not operate
without the Key Cap.

Complies with the latest international safety standards and regulations.

A new and improved LED indicator.
The incident light level indicator uses orange LED lights for
levels 1 to 3, and green LED lights for levels 4 to 5. The
green LED lights indicate that a stable amount of light is
being received. The error indicator uses a variety of
illumination and blinking patterns, enabling more detailed
diagnosis results to be communicated via the display.

Operates as a single
sensor when the Key
Cap is attached.

A

Blinking

B

ON

C

Cause of error
Mutual interference or ambient incident light.
Power supply voltage of F3SJ is out of the rated range.
Insufficient current capacity of power supply.

Incident light to blanking beams.
Failure in communication line.
Emitter and receiver have different F3SJ type
names or number of series connections.

New core technology that supports reliability and customizability.
The quality of Safety Light Curtain performance is determined
by the quality of the emitter/receiver elements. With previous
models, one faulty beam resulted in the malfunction of the
entire sensor. However, the F3SJ features a newly developed
"1-bit module" that integrates the lens and other optical parts
with the emitter IC and receiver IC, which are key devices.
With characteristic inspection performed on each beam, as
well as a thorough quality traceability system using 2D codes,
performance is assured.

Outside the effective range of parameters set by setting tool.
Cap is not attached.
External device monitor failure.

Lens
Holder cap

Failure in interlock selection input line or reset input line.
Muting wiring failure.

Holder

Failure in control output wiring.
30 dia.

30 dia.

Failure in series connection cable wiring.
Failure in wiring of external display lamp output.

Shield plate

Failure in wiring of auxiliary output.
Broken series connection cable.
Wiring error or broken communications wire.
Influence of electrical noise, or failure in a series-connected F3SJ.

10

IC package

The newly developed board-free "1bit module" is freely mounted on flat
cable.
In addition to our standard products, we
are now able to manufacture devices with a
different number of beams, or with a variety of
beam gaps. For details about these special
products, consult your OMRON sales representative.

11

New functions for extra reliability.

A measure to prevent you from forgetting
to connect a series connection cable.

Combine safety and productivity with a
controller-less muting function.
The muting function temporarily disables the light curtain
when an object must pass through the detection zone, such
as when supplying a workpiece to your equipment.
In the past, this function required a dedicated muting
controller, but now it is built into the F3SJ. To use the muting
function, purchase the F39-CN6 Key Cap for Muting (sold
separately). The muting function is enabled simply by
replacing the Unit's cap with this Key Cap. In addition, a
muting sensor that determines the muting timing, as well as
a muting lamp that communicates the muting status to other
operators, should be connected to the F3SJ.

Built-in muting function

■ No controller required. Simply attach the Key Cap (sold separately) to
the sensor.
F39-CN6
Key Cap for Muting
The Safety Light Curtain can be disabled when
an AGV carrying a workpiece passes through.

Emitter

● Indication Patterns and Light Levels of the Incident Light Level Indicator

1

2

3

4

5

Incident light level

LEVEL-5

From 130 to 170% of control output ON level

LEVEL-4

From 100 to 130% of control output ON level

LEVEL-3

From 75 to 100% of control output ON level

IEC61496-1, IEC61496-2, IEC61508 1998 (SIL3)

EU legislation EN standards

Machinery Directive, EMC Directive, EN61496-1, prEN61496-2, EN61508 2001 (SIL3)

JIS standards

JIS B9704-1, B9704-2

North American standards

UL61496-1, UL61496-2, UL508, UL1998, CAN/CSA22.2 NO.14, CAN/CSA22.2 NO.0.8

Can also be used with equipment subject to US OSHA standards (29 CFR 1910.212).
Satisfies the requirements of the ANSI/RIA R15.06-1999 standards for industrial robots.

cUL

From 50 to 75% of control output ON level

LEVEL-2

Less than 50% of control output ON level

LEVEL-1
● Error Mode Indication Patterns and Causes of Errors

ERROR-B
OFF

ERROR-A

International standards

ON

170% or higher of control output ON level

ERROR-C

The connectors for series connection feature an intelligent
design. To connect a series connection cable to the F3SJ,
remove the Key Cap that is required when the sensor is used by
itself. If you should happen to forget to connect the series
connection cable, the sensor will not operate by itself without the
Key Cap. This solves the problem of sensors operating
independently when a series connection cable is accidentally left
unconnected, such as when equipment is moved.

Like previous Type 4 Safety Light Curtains, the F3SJ conforms to the latest
required safety standards and regulations. Since the F3SJ also complies with
IEC61508, the international standard for functional safety, safety is ensured
regardless of where it is used.

OFF

Receiver

Does not operate
without the Key Cap.

Complies with the latest international safety standards and regulations.

A new and improved LED indicator.
The incident light level indicator uses orange LED lights for
levels 1 to 3, and green LED lights for levels 4 to 5. The
green LED lights indicate that a stable amount of light is
being received. The error indicator uses a variety of
illumination and blinking patterns, enabling more detailed
diagnosis results to be communicated via the display.

Operates as a single
sensor when the Key
Cap is attached.

A

Blinking

B

ON

C

Cause of error
Mutual interference or ambient incident light.
Power supply voltage of F3SJ is out of the rated range.
Insufficient current capacity of power supply.

Incident light to blanking beams.
Failure in communication line.
Emitter and receiver have different F3SJ type
names or number of series connections.

New core technology that supports reliability and customizability.
The quality of Safety Light Curtain performance is determined
by the quality of the emitter/receiver elements. With previous
models, one faulty beam resulted in the malfunction of the
entire sensor. However, the F3SJ features a newly developed
"1-bit module" that integrates the lens and other optical parts
with the emitter IC and receiver IC, which are key devices.
With characteristic inspection performed on each beam, as
well as a thorough quality traceability system using 2D codes,
performance is assured.

Outside the effective range of parameters set by setting tool.
Cap is not attached.
External device monitor failure.

Lens
Holder cap

Failure in interlock selection input line or reset input line.
Muting wiring failure.

Holder

Failure in control output wiring.
30 dia.

30 dia.

Failure in series connection cable wiring.
Failure in wiring of external display lamp output.

Shield plate

Failure in wiring of auxiliary output.
Broken series connection cable.
Wiring error or broken communications wire.
Influence of electrical noise, or failure in a series-connected F3SJ.

10

IC package

The newly developed board-free "1bit module" is freely mounted on flat
cable.
In addition to our standard products, we
are now able to manufacture devices with a
different number of beams, or with a variety of
beam gaps. For details about these special
products, consult your OMRON sales representative.

11

Ordering Information
■ Main Units
Safety Light Curtain F3SJ-A (Type 4)
Application

Detection
capability

Finger
protection

14-mm-dia.

Hand
protection

20-mm-dia.

Beam
gap

Appearance

Infrared light

Operating range

9 mm

15 mm

0.2 to 9 m

0.2 to 9 m
0.2 to 7 m

25 mm-dia.

20 mm

0.2 to 9 m
0.2 to 7 m

30-mm-dia.

25 mm

0.2 to 9 m
0.2 to 7 m

Leg/body
protection,
Presence
Detection

26 to 180

245 to 1,631 mm

16 to 100

F3SJF3SJA@@@@P20 A@@@@N20
1,655 to 2,495 mm (See note 1.)

0.2 to 9 m

0.2 to 7 m

Hand/arm
protection

Number of Protective height
Model
beams
PNP Output NPN Output

55 mm-dia.

50 mm

0.2 to 9 m
0.2 to 7 m

110 to 166
16 to 100
110 to 166
13 to 82
83 to 125

F3SJF3SJA@@@@P14 A@@@@N14
(See note 1.)

245 to 1,505 mm

--F3SJA@@@@P20
1,655 to 2,495 mm -TS
(See note 2.)
245 to 1,505 mm

--F3SJA@@@@P25
1660 to 2500 mm -TS
(See note 2.)

260 to 1640 mm

70 to 100

F3SJF3SJA@@@@P30 A@@@@N30
1,745 to 2,495 mm (See note 1.)

6 to 33

270 to 1620 mm

10 to 65

34 to 50

245 to 1,620 mm

--F3SJA@@@@P55 (See note 3.)
1670 to 2470 mm (See note 1.)

Note: 1. Models with S-mark certification have an "-S" at the end of the model number. Example: F3SJ-A0245P14-S
2. Models with fixed auto reset (-TS). Parameters cannot be set using the F39-MC21 Setting Console or F39-GWUM "SD Manager" Setting
Support Software for F3SJ. See the Ratings and Performance data for other differences between this and standard models.
3. Models with NPN output can also be manufactured. Consult your OMRON representative for details.
4. Connection cables are not included with the products and are to be purchased separately, as needed. You must purchase optional
connector cable.

12

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Safety Light Curtains
■ Safety Light Curtain Model List
Products other than those listed below are also available. Please contact your OMRON sales representative for details.

F3SJ-A14 Series (9 mm gap)
Model
PNP Output

NPN Output

No. of
Beams

Protective Height
(mm) (See note.)

F3SJ-A20 Series (15-mm gap), F3SJ-A20-TS
Series (15-mm gap) (See note 1.)
Model

No. of Protective Height
Beams (mm) (See note 2.)

F3SJ-A0245P14

F3SJ-A0245N14

26

245

F3SJ-A0263P14

F3SJ-A0263N14

28

263

F3SJ-A0281P14

F3SJ-A0281N14

30

281

F3SJ-A0245P20

F3SJ-A0245N20

16

245

F3SJ-A0275N20

18

275

PNP Output
(See note 1.)

NPN Output

F3SJ-A0299P14

F3SJ-A0299N14

32

299

F3SJ-A0275P20

F3SJ-A0317P14

F3SJ-A0317N14

34

317

F3SJ-A0305P20

F3SJ-A0305N20

20

305

F3SJ-A0335P14

F3SJ-A0335N14

36

335

F3SJ-A0335P20

F3SJ-A0335N20

22

335

353

F3SJ-A0365P20

F3SJ-A0365N20

24

365

F3SJ-A0395N20

26

395

F3SJ-A0353P14

F3SJ-A0353N14

38

F3SJ-A0371P14

F3SJ-A0371N14

40

371

F3SJ-A0395P20

F3SJ-A0389P14

F3SJ-A0389N14

42

389

F3SJ-A0425P20

F3SJ-A0425N20

28

425

F3SJ-A0407P14

F3SJ-A0407N14

44

407

F3SJ-A0455P20

F3SJ-A0455N20

30

455

425

F3SJ-A0485P20

F3SJ-A0485N20

32

485

F3SJ-A0515N20

34

515

F3SJ-A0425P14

F3SJ-A0425N14

46

F3SJ-A0443P14

F3SJ-A0443N14

48

443

F3SJ-A0515P20

F3SJ-A0461P14

F3SJ-A0461N14

50

461

F3SJ-A0545P20

F3SJ-A0545N20

36

545

F3SJ-A0479P14

F3SJ-A0479N14

52

479

F3SJ-A0575P20

F3SJ-A0575N20

38

575

497

F3SJ-A0605P20

F3SJ-A0605N20

40

605

F3SJ-A0635N20

42

635

F3SJ-A0497P14

F3SJ-A0497N14

54

F3SJ-A0515P14

F3SJ-A0515N14

56

515

F3SJ-A0635P20

F3SJ-A0533P14

F3SJ-A0533N14

58

533

F3SJ-A0665P20

F3SJ-A0665N20

44

665

F3SJ-A0551P14

F3SJ-A0551N14

60

551

F3SJ-A0695P20

F3SJ-A0695N20

46

695

569

F3SJ-A0725P20

F3SJ-A0725N20

48

725

F3SJ-A0755N20

50

755

F3SJ-A0569P14

F3SJ-A0569N14

62

F3SJ-A0587P14

F3SJ-A0587N14

64

587

F3SJ-A0755P20

F3SJ-A0605P14

F3SJ-A0605N14

66

605

F3SJ-A0785P20

F3SJ-A0785N20

52

785

F3SJ-A0623P14

F3SJ-A0623N14

68

623

F3SJ-A0815P20

F3SJ-A0815N20

54

815

659

F3SJ-A0845P20

F3SJ-A0845N20

56

845

F3SJ-A0875N20

58

875

F3SJ-A0659P14

F3SJ-A0659N14

72

F3SJ-A0695P14

F3SJ-A0695N14

76

695

F3SJ-A0875P20

F3SJ-A0731P14

F3SJ-A0731N14

80

731

F3SJ-A0905P20

F3SJ-A0905N20

60

905

F3SJ-A0767P14

F3SJ-A0767N14

84

767

F3SJ-A0935P20

F3SJ-A0935N20

62

935

803

F3SJ-A0965P20

F3SJ-A0965N20

64

965

F3SJ-A0995N20

66

995

F3SJ-A0803P14

F3SJ-A0803N14

88

F3SJ-A0839P14

F3SJ-A0839N14

92

839

F3SJ-A0995P20

F3SJ-A0875P14

F3SJ-A0875N14

96

875

F3SJ-A1025P20

F3SJ-A1025N20

68

1025

F3SJ-A0911P14

F3SJ-A0911N14

100

911

F3SJ-A1055P20

F3SJ-A1055N20

70

1055

983

F3SJ-A1085P20

F3SJ-A1085N20

72

1085

F3SJ-A1115N20

74

1115

F3SJ-A0983P14

F3SJ-A0983N14

108

F3SJ-A1055P14

F3SJ-A1055N14

116

1055

F3SJ-A1115P20

F3SJ-A1127P14

F3SJ-A1127N14

124

1127

F3SJ-A1145P20

F3SJ-A1145N20

76

1145

F3SJ-A1199P14

F3SJ-A1199N14

132

1199

F3SJ-A1175P20

F3SJ-A1175N20

78

1175

1271

F3SJ-A1205P20

F3SJ-A1205N20

80

1205

F3SJ-A1235N20

82

1235

F3SJ-A1271P14

F3SJ-A1271N14

140

F3SJ-A1343P14

F3SJ-A1343N14

148

1343

F3SJ-A1235P20

F3SJ-A1415P14

F3SJ-A1415N14

156

1415

F3SJ-A1265P20

F3SJ-A1265N20

84

1265

F3SJ-A1487P14

F3SJ-A1487N14

164

1487

F3SJ-A1325P20

F3SJ-A1325N20

88

1325

1559

F3SJ-A1385P20

F3SJ-A1385N20

92

1385

1631

F3SJ-A1445P20

F3SJ-A1445N20

96

1445

F3SJ-A1505P20

F3SJ-A1505N20

100

1505

F3SJ-A1655P20

F3SJ-A1655N20

110

1655

F3SJ-A1805P20

F3SJ-A1805N20

120

1805

F3SJ-A1955P20

F3SJ-A1955N20

130

1955

F3SJ-A2105P20

F3SJ-A2105N20

140

2105

F3SJ-A2255P20

F3SJ-A2255N20

150

2255

F3SJ-A2405P20

F3SJ-A2405N20

160

2405

F3SJ-A2495P20

F3SJ-A2495N20

166

2495

F3SJ-A1559P14
F3SJ-A1631P14

F3SJ-A1559N14
F3SJ-A1631N14

172
180

Note: Protective Height (mm) = Total sensor length

Note: 1. The suffix "-TS" is attached to the model number of models
with fixed auto reset.
2. Protective Height (mm) = Total sensor length

Safety Light Curtain (Type 4)

F3SJ Ver. 2

13

F3SJ-A25-TS Series (20-mm gap) (See note 1.)
Model
PNP output

No. of Protective Height
Beams (mm) (See note 2.)

F3SJ-A30 Series (25-mm gap)
Model
PNP Output

NPN Output

No. of
Beams

Protective Height
(mm) (See note.)

F3SJ-A0260P25-TS

13

260

F3SJ-A0245P30

F3SJ-A0245N30

10

245

F3SJ-A0300P25-TS

15

300

F3SJ-A0270P30

F3SJ-A0270N30

11

270

F3SJ-A0340P25-TS

17

340

F3SJ-A0295P30

F3SJ-A0295N30

12

295

F3SJ-A0380P25-TS

19

380

F3SJ-A0320P30

F3SJ-A0320N30

13

320

F3SJ-A0420P25-TS

21

420

F3SJ-A0345P30

F3SJ-A0345N30

14

345

F3SJ-A0460P25-TS

23

460

F3SJ-A0370P30

F3SJ-A0370N30

15

370

F3SJ-A0500P25-TS

25

500

F3SJ-A0395P30

F3SJ-A0395N30

16

395

F3SJ-A0540P25-TS

27

540

F3SJ-A0420P30

F3SJ-A0420N30

17

420

F3SJ-A0580P25-TS

29

580

F3SJ-A0445P30

F3SJ-A0445N30

18

445

F3SJ-A0620P25-TS

31

620

F3SJ-A0470P30

F3SJ-A0470N30

19

470

F3SJ-A0660P25-TS

33

660

F3SJ-A0495P30

F3SJ-A0495N30

20

495

F3SJ-A0700P25-TS

35

700

F3SJ-A0520P30

F3SJ-A0520N30

21

520

F3SJ-A0740P25-TS

37

740

F3SJ-A0545P30

F3SJ-A0545N30

22

545

F3SJ-A0780P25-TS

39

780

F3SJ-A0570P30

F3SJ-A0570N30

23

570

F3SJ-A0820P25-TS

41

820

F3SJ-A0595P30

F3SJ-A0595N30

24

595

F3SJ-A0860P25-TS

43

860

F3SJ-A0620P30

F3SJ-A0620N30

25

620

F3SJ-A0900P25-TS

45

900

F3SJ-A0645P30

F3SJ-A0645N30

26

645

F3SJ-A0940P25-TS

47

940

F3SJ-A0670P30

F3SJ-A0670N30

27

670

F3SJ-A0980P25-TS

49

980

F3SJ-A0695P30

F3SJ-A0695N30

28

695

F3SJ-A1020P25-TS

51

1020

F3SJ-A0720P30

F3SJ-A0720N30

29

720

F3SJ-A1060P25-TS

53

1060

F3SJ-A0745P30

F3SJ-A0745N30

30

745

F3SJ-A1100P25-TS

55

1100

F3SJ-A0770P30

F3SJ-A0770N30

31

770

F3SJ-A1140P25-TS

57

1140

F3SJ-A0795P30

F3SJ-A0795N30

32

795

F3SJ-A1180P25-TS

59

1180

F3SJ-A0820P30

F3SJ-A0820N30

33

820

F3SJ-A1220P25-TS

61

1220

F3SJ-A0845P30

F3SJ-A0845N30

34

845

F3SJ-A1260P25-TS

63

1260

F3SJ-A0870P30

F3SJ-A0870N30

35

870

F3SJ-A1300P25-TS

65

1300

F3SJ-A0895P30

F3SJ-A0895N30

36

895

F3SJ-A1340P25-TS

67

1340

F3SJ-A0920P30

F3SJ-A0920N30

37

920

F3SJ-A1380P25-TS

69

1380

F3SJ-A0945P30

F3SJ-A0945N30

38

945

F3SJ-A1420P25-TS

71

1420

F3SJ-A0970P30

F3SJ-A0970N30

39

970

F3SJ-A1460P25-TS

73

1460

F3SJ-A0995P30

F3SJ-A0995N30

40

995

F3SJ-A1500P25-TS

75

1500

F3SJ-A1020P30

F3SJ-A1020N30

41

1020

F3SJ-A1540P25-TS

77

1540

F3SJ-A1045P30

F3SJ-A1045N30

42

1045

F3SJ-A1580P25-TS

79

1580

F3SJ-A1070P30

F3SJ-A1070N30

43

1070

F3SJ-A1620P25-TS

81

1620

F3SJ-A1095P30

F3SJ-A1095N30

44

1095

F3SJ-A1660P25-TS

83

1660

F3SJ-A1120P30

F3SJ-A1120N30

45

1120

F3SJ-A1700P25-TS

85

1700

F3SJ-A1145P30

F3SJ-A1145N30

46

1145

F3SJ-A1740P25-TS

87

1740

F3SJ-A1170P30

F3SJ-A1170N30

47

1170

F3SJ-A1780P25-TS

89

1780

F3SJ-A1195P30

F3SJ-A1195N30

48

1195

F3SJ-A1820P25-TS

91

1820

F3SJ-A1220P30

F3SJ-A1220N30

49

1220

F3SJ-A1860P25-TS

93

1860

F3SJ-A1245P30

F3SJ-A1245N30

50

1245

F3SJ-A1900P25-TS

95

1900

F3SJ-A1270P30

F3SJ-A1270N30

51

1270

F3SJ-A1940P25-TS

97

1940

F3SJ-A1295P30

F3SJ-A1295N30

52

1295

F3SJ-A1980P25-TS

99

1980

F3SJ-A1395P30

F3SJ-A1395N30

56

1395

F3SJ-A2020P25-TS

101

2020

F3SJ-A1495P30

F3SJ-A1495N30

60

1495

F3SJ-A2060P25-TS

103

2060

F3SJ-A1620P30

F3SJ-A1620N30

65

1620

F3SJ-A2100P25-TS

105

2100

F3SJ-A1745P30

F3SJ-A1745N30

70

1745

F3SJ-A2140P25-TS

107

2140

F3SJ-A1870P30

F3SJ-A1870N30

75

1870

F3SJ-A2180P25-TS

109

2180

F3SJ-A1995P30

F3SJ-A1995N30

80

1995

F3SJ-A2220P25-TS

111

2220

F3SJ-A2120P30

F3SJ-A2120N30

85

2120

F3SJ-A2260P25-TS

113

2260

F3SJ-A2245P30

F3SJ-A2245N30

90

2245

F3SJ-A2300P25-TS

115

2300

F3SJ-A2370P30

F3SJ-A2370N30

95

2370

F3SJ-A2340P25-TS

117

2340

F3SJ-A2495P30

F3SJ-A2495N30

100

2495

F3SJ-A2380P25-TS

119

2380

F3SJ-A2420P25-TS

121

2420

F3SJ-A2460P25-TS

123

2460

F3SJ-A2500P25-TS

125

2500

Note: Protective Height (mm)= Total sensor length

Note: 1. The models in the F3SJ-A25-TS Series have only an auto reset.
2. Protective Height (mm)= Total sensor length

14

Safety Light Curtain (Type 4) F3SJ

Ver. 2

F3SJ-A55 Series (50-mm gap)
Model
PNP Output
F3SJ-A0270P55

NPN Output
(See note 1.)
---

No. of
Beams

Protective Height
(mm) (See note 2.)

6

270

F3SJ-A0320P55

7

320

F3SJ-A0370P55

8

370

F3SJ-A0420P55

9

420

F3SJ-A0470P55

10

470

F3SJ-A0520P55

11

520

F3SJ-A0570P55

12

570

F3SJ-A0620P55

13

620

F3SJ-A0670P55

14

670

F3SJ-A0720P55

15

720

F3SJ-A0770P55

16

770

F3SJ-A0820P55

17

820

F3SJ-A0870P55

18

870

F3SJ-A0920P55

19

920

F3SJ-A0970P55

20

970

F3SJ-A1020P55

21

1020

F3SJ-A1070P55

22

1070

F3SJ-A1120P55

23

1120

F3SJ-A1170P55

24

1170

F3SJ-A1220P55

25

1220

F3SJ-A1270P55

26

1270

F3SJ-A1320P55

27

1320

F3SJ-A1370P55

28

1370

F3SJ-A1420P55

29

1420

F3SJ-A1470P55

30

1470

F3SJ-A1520P55

31

1520

F3SJ-A1570P55

32

1570

F3SJ-A1620P55

33

1620

F3SJ-A1670P55

34

1670

F3SJ-A1720P55

35

1720

F3SJ-A1770P55

36

1770

F3SJ-A1820P55

37

1820

F3SJ-A1870P55

38

1870

F3SJ-A1920P55

39

1920

F3SJ-A1970P55

40

1970

F3SJ-A2020P55

41

2020

F3SJ-A2070P55

42

2070

F3SJ-A2120P55

43

2120

F3SJ-A2170P55

44

2170

F3SJ-A2220P55

45

2220

F3SJ-A2270P55

46

2270

F3SJ-A2320P55

47

2320

F3SJ-A2370P55

48

2370

F3SJ-A2420P55

49

2420

F3SJ-A2470P55

50

2470

Note: 1. Models with NPN output can also be manufactured.
2. Protective Height (mm)= Total sensor length

Safety Light Curtain (Type 4)

F3SJ Ver. 2

15

■ Accessories (Optional)
Single-end Connector Cable (2 cables per set, for emitter and receiver)
For wiring with safety circuit such as single safety relay, safety relay unit, and safety controller
Appearance

Cable length

Specifications

3m

Model

M12 connector (8-pin)

F39-JC3A

7m

F39-JC7A

10 m

F39-JC10A

15 m

F39-JC15A

20 m

F39-JC20A

Double-end Connector Cable (2 cables per set, for emitter and receiver)
For connection with F3SP-B1P control unit, and for extension when series-connected (See note.)
Appearance

Cable length

Specifications

0.5 m

Model

M12 connector (8-pin)

F39-JCR5B

1m

F39-JC1B

3m

F39-JC3B

5m

F39-JC5B

7m

F39-JC7B

10 m

F39-JC10B

15 m

F39-JC15B

20 m

F39-JC20B

Note: To extend the cable length under series connection, use F39-JJR3W and F39-JC@B in combination.

Power Cable (Included with the main unit) (2 cables per set, for emitter and
receiver)
Appearance

Cable length

Model

0.3 m

F39-JJR3K

Series Connection Cable (2 cables per set, for emitter and receiver)
Type

Appearance

Cable length

Model

Application

Series connection cable

0.3 m

F39-JJR3W

For series connection (See note
1.)
When using the Water-resistant
Case. (See note 2.)

Extension cable

0.5 to 15 m

F39-JC@B

To change series connection
length in combination with F39JJR3W

Side-by-side Series
connection cable

0.06 m

F39-JJR06L

0.15 m

F39-JJR15L

Dedicated series connection
cable with minimum length, used
in place of the sensor's cable
with connector

Note: 1. Total cable length of series connection is 0.6 m to connect to connector cable of the main sensor unit.
For series connection with minimum length, use the F39-JJR06L or F39-JJR15L.
2. When using the F39-EJ@@@@-L/D Water-resistant Case in series connection configurations, use the special series connection cables
for the Water-resistant Case. Refer to page 21 for details.

16

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Safety Controller (Dedicated PNP output type) (See note.)
Type

Appearance

Specifications

F3SX Safety Controller
(See note.)

Model

Remarks

• Can connect 2 sets of F3SJs and emergency stop switch F3SX-EL2
• DC semiconductor safety output

For other models
and functions, refer
to the Safety
Components
Series (Cat. No.
Y106).

• Can connect 4 sets of F3SJs and emergency stop switch F3SX-E-L2L2
• DC semiconductor safety output
• Can connect 2 sets of F3SJs and emergency stop switch F3SX-N-L2R
• Relay output (2NO+1NC)
• Can connect 4 sets of F3SJs and emergency stop switch F3SX-N-L2L2R
• Relay output (2NO+1NC)
Note: F3SJ for NPN output type cannot be connected.

Connection Cable for F3SX
(F3SX↔F39-CN5)
Appearance

Cable length

Branch Connector for F3SX
(F39-JC@T↔F39-JC@B)
Model

1m

F39-JC1T

3m

F39-JC3T

5m

F39-JC5T

7m

F39-JC7T

10 m

F39-JC10T

15 m

F39-JC15T

Appearance

Model
F39-CN5

Accessory connection example

F3SJ
Receiver

F3SJ
Emitter

Wire color:
Gray

Wire color:
Black
Branch connector for
safety light curtains
F39-CN5
Gray

Black
Double-end connector cable
F39-JC@B-D (black)

Double-end connector cable:
F39-JC@B-L (gray)

Connection cable for F3SX
F39-JC@T

F3SX

Safety Light Curtain (Type 4)

F3SJ Ver. 2

17

Relays with Forcibly Guided Contacts
Type

Appearance

Specifications

Model

• No. of contacts: 4
G7SA-2A2B
• Contact type: 2NO+2NC
• Rated switch load: 250 VAC 6 A, 30 VDC 6 A

G7SA Relays with
Forcibly Guided
Contacts

Remarks
For other models and
functions, refer to For
other models and Socket
models, refer to the
Safety Components
Series (Cat. No. Y106).

• No. of contacts: 4
G7SA-3A1B
• Contact type: 3NO+1NC
• Rated switch load: 250 VAC 6 A, 30 VDC 6 A
• No. of contacts: 6
G7S-4A2B-E
• Contact type: 4NO+2NC
• Rated switch load: 250 VAC 10 A, 30 VDC 10 A

G7S@-E Relays with
Forcibly Guided
Contacts

• No. of contacts: 6
G7S-3A3B-E
• Contact type: 3NO+3NC
• Rated switch load: 250 VAC 10 A, 30 VDC 10 A

Control unit (Can not be used as a muting system)
(Dedicated PNP output type) (See note.)
Appearance

Output
Relay, 3NO+1NC

Model

Remarks

F3SP-B1P (See note.)

For connection with F3SJ-A, use an F39-JC@B double-end
connector cable

Note: F3SJ for NPN output type cannot be connected.

Dedicated External Indicator Set (Can be connected to either an emitter or a
receiver)
Appearance

Color

Model

Remarks

Red

F39-A01PR-PAC

Indicator (red), mounting bracket (1 set), and dedicated
connection cable (0.1 m)

Green

F39-A01PG-PAC

Indicator (green), mounting bracket (1 set), and dedicated
connection cable (0.1 m)

Yellow

F39-A01PY-PAC

Indicator (yellow), mounting bracket (1 set), and dedicated
connection cable (0.1 m)

Note: For indication timing (operation mode) see "Ratings and Performance" on page 22.

General External Indicator Cable
Appearance

Cable length
3m

Specifications

Model

Cable to connect top of the main unit and an off-the shelf external F39-JJ3N
indicator (2-wire)

Spatter Protection Cover (Includes two pieces for emitter and receiver)
(Each unit reduces the operating range by 10%)
Appearance

Applicable sensor
F3SJ-A series

Model
F39-HJ@@@@ (See note.)

Note: The same 4-digit numbers as the protective heights (@@@@ in the light curtain type names) are substituted by @@@@ in the model names.

18

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Sensor Mounting Bracket (Sold separately)
Appearance

Specifications
Standard mounting
bracket (for top/bottom)

Model
F39-LJ1

Application

Remarks

(included in the main unit)

2 for emitter,
2 for receiver
(total of 4 per set)

Flat side mounting bracket F39-LJ2

Use these small-sized brackets when
performing side mounting with standard
mounting brackets, so that they do not
protrude from the detection surface.

2 for emitter,
2 for receiver
(total of 4 per set)

Free-location mounting
bracket (also used as
standard intermediate
bracket)

F39-LJ3

Use these brackets for mounting on any
place without using standard bracket.

1 set with 2 pieces

Top/bottom mounting
bracket B (mounting hole
pitch 19 mm)

F39-LJ4

2 for emitter,
Mounting bracket used when replacing
existing area sensors (other than F3SN or 2 for receiver
(total of 4 per set)
F3WN) with the F3SJ.
For front mounting.
Suitable for mounting hole pitch of 18 to
20 mm.

Bracket for replacing short- F39-LJ5
length F3SN

Mounting bracket used when an F3SN with 2 for emitter,
protective height of 300 mm or less is
2 for receiver
replaced by an F3SJ.
(total of 4 per set)

Space-saving mounting
bracket

Use these brackets to mount facing inward. 2 for emitter,
Length is 12 mm shorter than the standard 2 for receiver
(total of 4 per set)
F39-LJ1 bracket.

F39-LJ8

Mounting bracket used
F39-LJ9
when replacing an F3W-C.

Top/bottom mounting
bracket C (mounting hole
pitch 13 mm)

F39-LJ11

Mounting bracket used when replacing
existing F3W-C series area sensors with
the F3SJ.
For front mounting or side mounting.
Mounting hole pitch 16 mm.

2 for emitter,
2 for receiver
(total of 4 per set)

Mounting bracket used when replacing
existing area sensors having a mounting
pitch of 13 mm with the F3SJ.

2 for emitter,
2 for receiver
(total of 4 per set)

Key cap for muting
Appearance

Model
F39-CN6

Remarks
Cap attaches to the main unit to enable muting function.
Attach it to either an emitter or a receiver. (Case: orange)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

19

Setting Tools (See note 1.)
Type

Appearance

Model

Remarks

"SD Manager" Setting
Support Software for the
F3SJ

F39-GWUM

Accessories: SD Manager CD-ROM (1),
F39-CN1 Branch Connector (1),
Connector Cap (1), 2-m Dedicated Cable
(1), 0.3-m Dedicated Cable with Plug (1),
Instruction Manual

Setting Console

F39-MC21 (See note
2.)

Accessories: F39-CN1 Branch Connector
(1), Connector Cap (1), 2-m Dedicated
Cable (1), 0.3-m Dedicated Cable with
Plug (1), Instruction Manual

Note: 1. The setting tools described above can be connected only to F3SJ-A models with built-in software of Ver. 2 or later.
Note that the setting tools cannot be used with products shipped prior to December 2005. The setting tools cannot be used for setting
parameters on the F3SJ-A@-TS series, but the monitoring function can be used.
2. This product is for use only with the F3SJ-A. It cannot be connected to conventional models of the F3SN-A series.
Similarly, the F39-MC11 and F39-MT11 Dedicated Consoles for the F3SN-A cannot be connected to the F3SJ-A series.

Protector (Main unit mounting bracket (1) and a rear mounting bracket set)
(See note 1.)
Model

Remarks

Protector Set

Type

Appearance

F39-PJ@@@@-S (See
note 2.)

Rear Mounting Brackets (2), including
intermediate brackets to match protective
height (0 to 2).

Intermediate brackets for
side mounting

F39-PJ-MS

For side mounting, order to suit the desired
protective height.
Protective height of up to 1,000 mm: 0
intermediate brackets
Protective height of 1,001 to 2,000 mm: 1
intermediate bracket
Protective height of 2,001 mm or more: 2
intermediate brackets

Note: 1. When using for both emitter and receiver, order two sets.
2. The same four digits indicating protective height that are used in the Sensor model number (@@@@) are used in the @@@@ part of the
Protector model number.

20

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Water-resistant Case (Set of 1 tube, packing, and dedicated connector cable)
(See note 1.)
Appearance

---

Specifications

Model

Remarks

For emitter

F39-EJ@@@@-L (See
note 2.)

Includes gray cable for emitter.

For receiver

F39-EJ@@@@-D (See
note 2.)

Includes black cable for receiver.

Rear Mounting Brackets

F39-EJ-R (See note 3.) Top/bottom 1 each, total of 2

Side Mounting Brackets

F39-EJ-S (See note 3.) Top/bottom 1 each, total of 2

Series connection cable
(for emitter)

F39-JJR3WE-L

Series connection cable
(for receiver)

F39-JJR3WE-D

Purchase additionally for series
connection when using the Waterresistant Case.

Note: 1. When using for both emitter and receiver, order two sets.
2. The same four digits indicating protective height that are used in the Sensor model number (@@@@) are used in the @@@@ part of the
Case model number.
3. Be sure to purchase brackets with the Case to match the mounting direction (rear or side).

Safety Light Curtain (Type 4)

F3SJ Ver. 2

21

Ratings and Performance (For details, refer to the instruction manual.)
■ Main Units
F3SJ-A@@@@P14/P20/P30/P55/N14/N20/N30
Model

PNP
outputs

F3SJ-A@@@@P14

F3SJ-A@@@@P20

F3SJ-A@@@@P30

F3SJ-A@@@@P55

NPN
outputs

F3SJ-A@@@@N14

F3SJ-A@@@@N20

F3SJ-A@@@@N30

---

Sensor type

Type 4 safety light curtain

Software version

Ver. 2

Setting tool connection

Connectable

Applicable safety category

Category 4, 3, 2, 1, or B

Detection capability

Opaque objects
14 mm in diameter

Opaque objects
20 mm in diameter

Opaque objects
30 mm in diameter

Opaque objects
55 mm in diameter

Beam gap (P)

9 mm

15 mm

25 mm

50 mm

Number of beams (n)

26 to 180

16 to 166

10 to 100

6 to 50

Protective height (PH)

245 to 1,631 mm

245 to 2,495 mm

Lens diameter

Diameter 5 mm

Operating range

0.2 to 9 m (protective height 1,640 mm max.),
0.2 to 7 m (protective height 1,655 mm max.)
(Depending on the setting tool, the detection distance can be shortened to 0.5 m.)

Response time
(For details, see
"Response Time"
on page 27.)

270 to 2,470 mm

ON to
OFF

1 set, 0245 to 983: 11 ms to
17.5 ms max.
1,055 or higher: 20 ms to 25 ms
max.

1 set, 0245 to 1,205: 10 ms to 1 set: 10 ms to 17.5 ms max.
15 ms max.
1,235 or higher: 17.5 ms to 22.5
ms max.

1 set: 10 ms to 13 ms max.

OFF to
ON

1 set, 0245 to 983: 44 ms to 70
ms max.
1,055 or higher: 80 ms to 100
ms max.

1 set, 0245 to 1,205: 40 ms to 1 set: 40 ms to 70 ms max.
60 ms max.
1,235 or higher: 70 ms to 90 ms
max.

1 set: 40 ms to 52 ms max.

Startup waiting time

2 s max. (2.2 s max. for series connection)

Power supply voltage (Vs)

24 VDC ±20% (ripple p-p10% max.)

Current
consumption (no
load)

Up to 50 beams: 76 mA max., 51 to 100 beams: 106 mA max., 101 to 150 beams: 130 mA max.,
151 to 180 beams: 153 mA max., 201 to 234 beams: 165 mA max.

Emitter

Receiver Up to 50 beams: 68 mA max., 51 to 100 beams: 90 mA max., 101 to 150 beams: 111 mA max.,
151 to 180 beams: 128 mA max.

Light source (emitted
wavelength)

Infrared LED (870 nm)

Effective aperture angle
(EAA)

Based on IEC61496-2. Within ±2.5° for both emitter and receiver when the detection distance is 3 m or over

Control outputs
(OSSD)

PNP
outputs

Two PNP transistor outputs, load current 300 mA max., residual voltage 2 V max. (except for voltage drop due to cable extension),
allowable capacity load 2.2 µF, leak current 1 mA max.
(This can be different from traditional logic (ON/OFF) because safety circuit is used.)

NPN
outputs

Two NPN transistor outputs, load current 300 mA max., residual voltage 2 V max. (except for voltage --drop due to cable extension), allowable capacity load 2.2 µF, leak current 2 mA max.
(This can be different from traditional logic (ON/OFF) because safety circuit is used.)

PNP
output

One PNP transistor output, load current 300 mA max., residual voltage 2 V max. (except for voltage drop due to cable extension), leak
current 1 mA max.

NPN
output

One NPN transistor output, load current 300 mA max., residual voltage 2 V max. (except for voltage --drop due to cable extension), leak current 1 mA max.

Auxiliary output 1
(non-safety
output)

Auxiliary output 2 PNP
(non-safety
output
output, basic
system functions) NPN
output

One PNP transistor output, load current 50 mA max., residual voltage 2 V max. (except for voltage drop due to cable extension), leak
current 1 mA max.

External indicator output
(non-safety output)

Available indicators
• Incandescent lamp: 24 VDC, 3 to 7 W
• LED lamp: Load current 10 mA to 300 mA max., leak current 1 mA max.
(To use an external indicator, an F39-JJ3N universal indicator cable or an F39-A01P@-PAC dedicated external indicator kit is required.)

Output operation
mode

Receiver Control outputs 1, 2:
ON when receiving light
Auxiliary output 1:
Inverse of control output signals (Operating mode can be changed with the setting tool.)
External indicator output 1:Inverse of control output signals for a basic system (Operating mode can be changed with the setting tool.)
ON when muting/override for a muting system (Operating mode can be changed with the setting tool.)
Emitter

22

One NPN transistor output, load current 50 mA max., residual voltage 2 V max. (except for voltage --drop due to cable extension), leak current 1 mA max.

Auxiliary output 2:

Turns ON when the point of 30,000 operating hours is reached
(Operating mode can be changed with the setting tool.)
External indicator output 2:ON when lock-out for a basic system (Operating mode can be changed with the setting tool.)
ON when muting/override for a muting system (Operating mode can be changed with the setting tool.)

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Model

Input voltage

PNP
outputs

F3SJ-A@@@@P14

F3SJ-A@@@@P20

F3SJ-A@@@@P30

F3SJ-A@@@@P55

NPN
outputs

F3SJ-A@@@@N14

F3SJ-A@@@@N20

F3SJ-A@@@@N30

---

PNP
output

Test input, interlock selection input, reset input, and muting input are all
ON voltage: 9 to 24 V (Vs) (sink current: 3 mA max.)
OFF voltage: 0 to 1.5 V, or open
External device monitoring input
ON voltage: 9 to 24 V (Vs) (sink current: 5 mA max.)
OFF voltage: 0 to 1.5 V, or open

NPN
output

Test input, interlock selection input, reset input, and muting input are all
ON voltage: 0 to 1.5 V (short-circuit current 3 mA max.)
OFF voltage: 9 to 24 V, or open
External device monitoring input
ON voltage: 0 to 1.5 V (short-circuit current 5 mA max.)
OFF voltage: 9 to 24 V, or open

Internal indicators Emitter

---

Light intensity level indicators (green LED × 2, orange LED × 3): ON based on the light intensity
Error mode indicators (red LED × 3): Blink to indicate error details
Power indicator (green LED × 1): ON while power is on
Interlock indicator (yellow LED × 1): ON while under interlock, ON while under interlock, blinks at lockout.
External device monitoring indicator (muting input 1 indicator), Blanking/test indicator (muting input 2 indicator) (green LED × 2):
ON/flash according to function

Receiver Light intensity level indicators (green LED × 2, orange LED × 3): ON based on the light intensity
Error mode indicators (red LED × 3): Blink to indicate error details
OFF output indicator (red LED × 1): ON when safety output is OFF, blinks at lockout.
ON output indicator (green LED × 1): ON while safety output is ON muting error indicator, Blanking /test indicator (green LED × 2):
ON/flash according to function
Mutual interference
prevention function
Series connection

Interference light prevention algorithm, detection distance change function
Time division emission by series connection
Number of connections: up to 4 sets
Total number of beams: up to 400 beams
Maximum cable length for 2 sets: no longer than 15 m
Response time under connection: See page 27

•
•
•
•
Test functions

• Self test (when power is turned ON and while power is supplied)
• External test (emission stop function by test input)

Safety functions

•
•
•
•
•

Connection type

Connectors (M12, 8-pin)

Protective circuits

Output short-circuit protection, and power supply reverse polarity protection

Ambient temperature

Operating: −10 to 55°C (no icing), Storage: −30 to 70°C

Ambient humidity

Operating: 35% to 85% (no condensation), Storage: 35% to 95%

Ambient operating light
intensity

Incandescent lamp: 3,000 lx max. (light intensity on the receiver surface), Sunlight: 10,000 lx max. (light intensity on the receiver
surface)

Insulation resistance

20 MΩ min. (at 500 VDC)

Start interlock, restart interlock (Must be set with a setting tool when the muting function is used.)
External device monitor
Muting (Lamp burnout detection, override function included. F39-CN6 key cap for muting is required.)
Fixed blanking (must be set by a setting tool)
Floating blanking (must be set by a setting tool)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

23

Model

PNP
outputs

F3SJ-A@@@@P14

F3SJ-A@@@@P20

F3SJ-A@@@@P30

F3SJ-A@@@@P55

NPN
outputs

F3SJ-A@@@@N14

F3SJ-A@@@@N20

F3SJ-A@@@@N30

---

Dielectric strength

1,000 VAC 50/60 Hz, 1 min

Degree of protection

IP65 (IEC60529)

Vibration resistance

Malfunction: 10 to 55 Hz, 0.7-mm double amplitude, 20 sweeps in X, Y, and Z directions

Shock resistance

Malfunction: 100 m/s2, 1,000 times each in X, Y, and Z directions

Connection cable,
Series connection cable
(F39-JJR@L, F39-JJR3W)

6-mm-dia., 8-wire cable (0.15 mm2 × 8) with braided shield, allowable bending radius R5 mm

Extension cable
(F39-JC@A, F39-JC@B)

6.6-mm-dia., 8-wire cable (0.3 mm2 × 4P, resistance 0.058 Ω/m), with braided shield, allowable bending radius R36 mm
(To extend a cable length, use an equivalent or higher-performance cable. Do not place it in the same duct as high-voltage cables or
power cables.)
For available length for extension (cable extension length), see page 28.

Materials

Casing (including metal parts on both ends): Aluminum, zinc die-cast
Cap: ABS resin
Optical cover: PMMA resin (acrylic)
Cable: Oil resistant PVC

Weight (packed state)

Calculate using the following equations:
(1) For F3SJ-A@@@@P14, weight (g)=(protective height) × 1.7 + α
(2) For F3SJ-A@@@@P20/F3SJ-A@@@@P30, weight (g)=(protective height) × 1.5 + α
(3) For F3SJ-A@@@@P55, weight (g)=(protective height) × 1.4 + α
The values for α are as follows:
Protected height 245 to 596 mm: α = 1,100 protected height 1667 to 2180 mm: α = 2,400
Protected height 605 to 1,130 mm: α = 1,500 protected height 2195 to 2495 mm: α = 2,600
Protected height 1,136 to 1,658 mm: α = 2,000

Accessories

Test rod (See note 1.), instruction manual, mounting brackets (top and bottom), mounting brackets (intermediate) (See note 2.), error
mode label, User's Manual (CD-ROM)
Note: 1. The F3SJ-A@@@@P55 is not included.
2. Number of intermediate mounting brackets depends on protective height of F3SJ.
• For protective height from 605 to 1,130 mm: 1 set for each of the emitter and receiver is included
• For protective height from 1,136 to 1,658 mm: 2 sets for each of the emitter and receiver are included
• For protective height from 1,667 to 2,180 mm: 3 sets for each of the emitter and receiver are included
• For protective height from 2,195 to 2,495 mm: 4 sets for each of the emitter and receiver are included

Applicable standards

IEC61496-1, EN61496-1 UL61496-1, Type 4 ESPE (Electro-Sensitive Protective Equipment)
IEC61496-2, prEN61496-2, UL61496-2, Type 4 AOPD (Active Opto-electronic Protective Devices)
IEC61508, EN61508 SIL3

24

Safety Light Curtain (Type 4) F3SJ

Ver. 2

F3SJ-A@@@@P20-TS/P25-TS
Model

F3SJ-A@@@@P20-TS

F3SJ-A@@@@P25-TS

Sensor type

Type 4 safety light curtain

Software version

Ver. 2

Setting tool connection

Parameter setting: Not possible
Monitoring: Possible

Applicable safety category

Category 4, 3, 2, 1, or B

Detection capability

Opaque objects
20 mm in diameter

Opaque objects
25 mm in diameter

Beam gap (P)

15 mm

20 mm

Number of beams (n)

16 to 166

13 to 125

Protective height (PH)

245 to 2,495 mm

260 to 2,500 mm

Lens diameter

Diameter 5 mm

Operating range
Response time
(For details, see
"Response Time"
on page 27.)

0.2 to 9 m (protective height 1,640 mm max.), 0.2 to 7 m (protective height 1,655 mm max.)
ON to OFF 1 set, 0245 to 1,205: 10 ms to 15 ms max.
1,220 or higher: 17.5 ms to 22.5 ms max.
3 sets (240 beams): 45.5 ms

1 set, 0260 to 1,600: 10 ms to 15 ms max.
1,620 or higher: 17.5 ms to 20.0 ms max.
3 sets (240 beams): 45.5 ms

OFF to ON 1 set, 0245 to 1,205: 40 ms to 60 ms max.
1,220 or higher: 70 ms to 90 ms max.
3 sets (240 beams): 200 ms

1 set, 0260 to 1,600: 40 ms to 60 ms max.
1,620 or higher: 70 ms to 80 ms max.
3 sets (240 beams): 200 ms

Startup waiting time

2 s max. (2.2 s max. for series connection)

Power supply voltage (Vs)

24 VDC ±20% (ripple p-p10% max.)

Current
consumption (no
load)

Emitter

Up to 50 beams: 76 mA max., 51 to 100 beams: 106 mA max., 101 to 150 beams: 130 mA max.,
151 to 166 beams: 153 mA max

Receiver

Up to 50 beams: 68 mA max., 51 to 100 beams: 90 mA max., 101 to 150 beams: 111 mA max.,
151 to 166 beams: 128 mA max.

Light source (emitted
wavelength)

Infrared LED (870 nm)

Effective aperture angle (EAA) Based on IEC61496-2. Within ±2.5° for both emitter and receiver when the detection distance is 3 m or over
Control outputs (OSSD)

Two PNP transistor outputs, load current 300 mA max., residual voltage 2 V max. (except for voltage drop due to cable extension),
allowable capacity load 2.2 µF, leak current 1 mA max.
(This can be different from traditional logic (ON/OFF) because safety circuit is used.)

Auxiliary output 1
(non-safety output)

One PNP transistor output, load current 300 mA max., residual voltage 2 V max. (except for voltage drop due to cable extension),
leak current 1 mA max.

External indicator output
(non-safety output)

Available indicators

• Incandescent lamp: 24 VDC, 3 to 7 W
• LED lamp: Load current 10 mA to 300 mA max., leak current 1 mA max.
(To use an external indicator, an F39-JJ3N universal indicator cable or an F39-A01P@-PAC dedicated external indicator kit is required.)

Output operation
mode

Receiver

Control outputs 1, 2:
ON when receiving light
Auxiliary output 1:
Inverse of control output signals (Operating mode can be changed with the setting tool.)
External indicator output 1:Inverse of control output signals for a basic system (Operating mode can be changed with the setting
tool.)
ON when muting/override for a muting system (Operating mode can be changed with the setting tool.)

Emitter

External indicator output 2:ON when lock-out for a basic system (Operating mode can be changed with the setting tool.)
ON when muting/override for a muting system (Operating mode can be changed with the setting tool.)

Input voltage

Test input, reset input, and muting input are all
ON voltage: 9 to 24 V (Vs) (sink current: 3 mA max.)
OFF voltage: 0 to 1.5 V, or open
External device monitoring input
ON voltage: 9 to 24 V (Vs) (sink current: 5 mA max.)
OFF voltage: 0 to 1.5 V, or open

Internal indicators Emitter

Light intensity level indicators (green LED × 2, orange LED × 3): ON based on the light intensity
Error mode indicators (red LED × 3): Blink to indicate error details
Power indicator (green LED × 1): ON while power is on
Lockout indicator (yellow LED × 1): Blinks to indicate lockout.
External device monitoring indicator (muting input 1 indicator), Test indicator (muting input 2 indicator) (green LED × 2):
ON/flash according to function

Receiver

Light intensity level indicators (green LED × 2, orange LED × 3): ON based on the light intensity
Error mode indicators (red LED × 3): Blink to indicate error details
OFF output indicator (red LED × 1): ON when safety output is OFF, blinks at lockout.
ON output indicator (green LED × 1): ON while safety output is ON muting error indicator, Test indicator (green LED × 2): ON/flash
according to function

Mutual interference prevention Interference light prevention algorithm
function
Series connection

Time division emission by series connection
Number of connections: up to 3 sets
Total number of beams: up to 240 beams
Maximum cable length for 2 sets: no longer than 15 m
Response time under connection: See page 27

•
•
•
•
Test functions

• Self test (when power is turned ON and while power is supplied)
• External test (emission stop function by test input)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

25

Model
Safety functions

F3SJ-A@@@@P20-TS

F3SJ-A@@@@P25-TS

• External device monitor
• Muting (Override function included. F39-CN6 Key Cap for muting is required.)
Lockout occurs under either of the following conditions:

• When more than 3 Units are connected in series.
• When the total number of beams connected in series exceeds 240.
• When any model other than a "-TS" model is included in a series connection.
Connection type

Connectors (M12, 8-pin)

Protective circuits

Output short-circuit protection, and power supply reverse polarity protection

Ambient temperature

Operating: −10 to 55°C (no icing), Storage: −30 to 70°C

Ambient humidity

Operating: 35% to 85% (no condensation), Storage: 35% to 95%

Ambient operating light
intensity

Incandescent lamp: 3,000 lx max. (light intensity on the receiver surface), Sunlight: 10,000 lx max. (light intensity on the receiver
surface)

Insulation resistance

20 MΩ min. (at 500 VDC)

Dielectric strength

1,000 VAC 50/60 Hz, 1 min

Degree of protection

IP65 (IEC60529)

Vibration resistance

Malfunction: 10 to 55 Hz, 0.7-mm double amplitude, 20 sweeps in X, Y, and Z directions

Shock resistance

Malfunction: 100 m/s2, 1,000 times each in X, Y, and Z directions

Connection cable, Series
6-mm-dia., 8-wire cable (0.15 mm2 × 8) with braided shield, allowable bending radius R5 mm
connection cable (F39-JJR@L,
F39-JJR3W)
Extension cable (F39-JC@A,
F39-JC@B)

6.6-mm-dia., 8-wire cable (0.3 mm2 × 4P, resistance 0.058 Ω/m), allowable bending radius R36 mm
(To extend a cable length, use an equivalent or higher-performance cable. Do not place it in the same duct as high-voltage cables
or power cables.)
For available length for extension (cable extension length), see page 28.

Materials

Casing (including metal parts on both ends): Aluminum, zinc die-cast
Cap: ABS resin
Optical cover: PMMA resin (acrylic)
Cable: Oil resistant PVC

Weight (packed state)

Calculate using the following equations:
For F3SJ-A@@@@P@@-TS, weight (g)=(protective height) × 1.5 + α
The values for α are as follows:
Protected height 245 to 580 mm: α = 1,100 protected height 1,700 to 2,180 mm: α = 2,400
Protected height 605 to 1,115 mm: α = 1,500 protected height 2,200 to 2,500 mm: α = 2,600
Protected height 1,140 to 1,660 mm: α = 2,000

Accessories

Test rod, instruction manual, mounting brackets (top and bottom), mounting brackets (intermediate) (See note.), error mode label,
User's Manual (CD-ROM)
Note: Number of intermediate mounting brackets depends on protective height of F3SJ.
• For protective height from 605 to 1,115 mm: 1 set for each of the emitter and receiver is included
• For protective height from 1,140 to 1,660 mm: 2 sets for each of the emitter and receiver are included
• For protective height from 1,700 to 2,180 mm: 3 sets for each of the emitter and receiver are included
• For protective height from 2,220 to 2,500 mm: 4 sets for each of the emitter and receiver are included

Applicable standards

IEC61496-1, EN61496-1 UL61496-1, Type 4 ESPE (Electro-Sensitive Protective Equipment)
IEC61496-2, prEN61496-2, UL61496-2, Type 4 AOPD (Active Opto-electronic Protective Devices)
IEC61508, EN61508 SIL3

26

Safety Light Curtain (Type 4) F3SJ

Ver. 2

■ Response Time
Model
F3SJ-A@14
series

F3SJ-A@20
series
F3SJ-A@P20-TS
series

F3SJ-A@P25-TS
series

F3SJ-A@30
series

F3SJ-A@55
series

Protective Height (mm)

Number of Beams

Response time ms (ON to OFF) Response time ms (OFF to ON)

245 to 263

26 to 28

11

44

281 to 389

30 to 42

12

48

407 to 497

44 to 54

13

52

515 to 605

56 to 66

14

56

623 to 731

68 to 80

15

60

767 to 983

84 to 108

17.5

70

1,055 to 1,271

116 to 140

20

80

1,343 to 1,559

148 to 172

22.5

90

1,631

180

25

100

245

16

10

40

275 to 425

18 to 28

11

44

455 to 635

30 to 42

12

48

665 to 815

44 to 54

13

52

845 to 995

56 to 66

14

56

1,025 to 1,205

68 to 80

15

60

1,235 to 1,655

82 to 110

17.5

70

1,805 to 2,105

120 to 140

20

80

2,255 to 2,495

150 to 166

22.5

90

260 to 320

13 to 16

10

40

340 to 580

17 to 29

11

44

600 to 840

30 to 42

12

48

860 to 1100

43 to 55

13

52

1120 to 1340

56 to 67

14

56

1360 to 1600

68 to 80

15

60

1620 to 2240

81 to 112

17.5

70

2260 to 2500

113 to 125

20.0

80

245 to 395

10 to 16

10

40

420 to 720

17 to 29

11

44

745 to 1,045

30 to 42

12

48

1,070 to 1,295

43 to 52

13

52

1,395 to 1,620

56 to 65

14

56

1,745 to 1,995

70 to 80

15

60

2,120 to 2,495

85 to 100

17.5

70

270 to 770

6 to 16

10

40

820 to 1420

17 to 29

11

44

1470 to 2070

30 to 42

12

48

2120 to 2470

43 to 50

13

52

Note: Use the following expressions for series connection.
For 2-set series connection:
Response time (ON to OFF): Response time of the 1st unit + Response time of the 2nd unit - 1 (ms)
Response time (OFF to ON): Response time calculated by the above x 4 (ms)
For 3-set series connection:
Response time (ON to OFF): Response time of the 1st unit + Response time of the 2nd unit + Response time of 3rd unit - 5 (ms)
Response time (OFF to ON): Response time calculated by the above x 5 (ms)
(For models with the "-TS" suffix, multiply the response time obtained by the above x 5 (ms),
or use 200 ms, whichever is less.)
For 4-set series connection:
Response time (ON to OFF): Response time of the 1st unit + Response time of the 2nd unit + Response time of the 3rd unit +
Response time of the 4th unit - 8 (ms)
Response time (OFF to ON): Response time calculated by the above x 5 (ms)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

27

■ Cable Extension Length
Total cable extension length must be no greater than the lengths described below.

When the F3SJ and an external power supply are directly connected, or when the F3SJ is connected to a G9SA-300-SC.
Condition

1 set

2 sets

3 sets

4 sets

Using incandescent lamp for auxiliary output
and external indicator output

45 m

40 m

30 m

20 m

Not using incandescent lamp

100 m

60 m

45 m

30 m

When connected to the F3SP-B1P.
Condition

1 set

2 sets

3 sets

4 sets

Using incandescent lamp for external indicator 40 m
output 2

30 m

25 m

20 m

Using incandescent lamp for external indicator 60 m
output 1

45 m

30 m

20 m

60 m

45 m

30 m

Using incandescent lamp for auxiliary output 1
Not using incandescent lamp

100 m

Note: Keep the cable length within the rated length. Failure to do so is dangerous as it may prevent safety functions from operating normally.

■ Accessories
Control Unit
Item

Model

F3SP-B1P

Applicable sensor

F3SJ-A (Only for PNP output type) (See note.)

Power supply voltage

24 VDC±10%

Power consumption

DC1.7 W max. (not including sensor’s current consumption)

Operation time

100 ms max. (not including sensor’s response time)

Response time

10 ms max. (not including sensor’s response time)

Relay
output

Number of contacts 3NO+1NC
Rated load

25 VAC 5 A (cosφ= 1),
30 VDC 5 A L/R = 0 ms

Rated current

5A

Connection Between sensors
type
Others

M12 connector (8-pin)

Weight (packed state)

Approx. 280 g

Accessories

Instruction manual

Terminal block

Note: NPN output type cannot be connected. Also, the system cannot be used as a muting system.

Dedicated External Indicator Set
Model

F39-A01PR-PAC

F39-A01PG-PAC

F39-A01PY-PAC

Item
Applicable sensor

F3SJ-A
(Common for PNP/NPN output type. Can be attached to emitters and/or receivers)

Light source

Red LED

Power supply voltage

24 VDC±10% (supplied by sensor)

Consumption current

50 mA max. (supplied by sensor)

Connection type

Dedicated accessory connector cable
(Sensor side: Dedicated 10-pin connector, Indicator side: M12 8-pin connector)

Set contents

Indicator (yellow), Dedicated
Indicator (green), Dedicated
Indicator (red), Dedicated
connector cable (0.1 m), Dedicated connector cable (0.1 m), Dedicated connector cable (0.1 m), Dedicated
mounting brackets (1 for each)
mounting brackets (1 for each)
mounting brackets (1 for each)

28

Safety Light Curtain (Type 4) F3SJ

Green LED

Ver. 2

Yellow LED

I/O Circuit
■ PNP Output Type
The numbers in white circles indicate the connector's pin numbers.
The black circles indicate connectors for series connection.
The words in brackets ([ ]) indicate the signal name for muting system.

External indicator output 2
Brown

Indication
2 Brown

+24 VDC

5
Test input
3 Green
Emitter
Main Circuit

Blue
10

1 White Interlock selection input
[Muting input 1] (See note 1.)
Yellow Reset input
4

8 Red

7
5

Pink
Communication line (−)

Communication line (+)
Gray

5

6

Pink
2

External indicator output 1
Brown
5

Blue
Shield

6

Gray

Auxiliary output 2
[Muting input 2] (See note 2.)

8
Receiver
Main Circuit 2

1

Brown
Red External device
monitoring input
White Control output 2

Blue
10

Load
3
Receiver
Main Circuit 1
4

Green Control output 1

Load
Auxiliary output 1
Yellow
Load

Indication
7

Blue

0V

Shield
Note: 1. Open or muting input 1 for models with the "-TS" suffix.
2. Open or muting input 2 for models with the "-TS" suffix.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

29

■ NPN Output Type
The numbers in white circles indicate the connector's pin numbers.
The black circles indicate connectors for series connection.
The words in brackets ([ ]) indicate the signal name for muting system.

External indicator output 2
Brown

Indication
2

Brown

+24 VDC

5
3
Emitter
Main Circuit

Blue
10

1
4

Green Test input
White Interlock selection input
[Muting input 1]
Yellow Reset input

8 Red

7
5

Gray
Communication line (+)
Gray

5

Auxiliary output 2
[Muting input 2]

Blue
Shield

6
Pink
Communication line (−)
Pink
6

Brown
2
Load

White
External indicator output 1
Brown
5

1

Control output 2
Load

Receiver
Main Circuit 2

1

Green

3

Blue
10

Control output 1
Load
Yellow

4

Receiver
Main Circuit 1

Auxiliary output 1

8

Red

External device
monitoring input

Indication
7

0V

Blue
Shield

■ Single-end Connector Cable
Model

Internal wiring

Pin
No.

Wire
color

Signal Name
Basic system (See note 1.)
Receiver

F39JC3A (3 m)
F39JC7A (7 m)

1
2

F39JC10A (10 m)

4
3

3
6

8
2

F39JC15A (15 m)

5

7
1

4
5
6
7

Wire color
White
Brown
Green
Yellow
Gray
Pink
Blue
Red

8

Muting system (See note 1.)

Emitter

Receiver

White

Safety output 2

Interlock selection Safety output 2
input (See note 2.)

Muting input 1

(2)

Brown

+24 VDC

+24 VDC

+24 VDC

+24 VDC

(3)

Green

Control output 1

Test Input

Control output 1

Test Input

(4)

Yellow

Auxiliary output 1

Reset input

Auxiliary output 1

Reset input

(5)

Gray

Communication
line (+)

Communication
line (+)

Communication
line (+)

Communication
line (+)

(6)

Pink

Communication
line (-)

Communication
line (-)

Communication
line (-)

Communication
line (-)

(7)

Blue

0V

0V

0V

0V

(8)

Red

External device
monitoring input

Auxiliary output 2
(See note 2.)

External device
monitoring input

Muting input 2

Note: 1. Basic system indicates a system with default factory settings.
Muting system indicates a system attached with a muting keycap (F39-CN6) to enable muting function.
2. N.C. for models with the "-TS" suffix.

30

Safety Light Curtain (Type 4) F3SJ

Emitter

(1)

Ver. 2

Nomenclature
■ Main Unit and Cables
Beam center-line mark
(A line indicates where the beam is
aligned. This line indicates the
reference line used to measure the
safety distance.)

Cap

Emitter

Beam
To attach or detach the cap
and power cable, remove
the 4 screws shown above.
Indicator
Receiver

Power cable
(Gray)

Power cable (Black)

Extension cable

Component
Emitter, receiver

Model
F3SJ-A@@@@P@@
or
F3SJ-A@@@@N@@

Description
Select a type name based on the required protective height and
detection capability.
(Cap and power cable are included)
The type name can be understood as follows:
F3SJ-A@@@@P@@-@

1 2 3 4
1: Protective height (mm)
2: Output type (P=PNP output type, N=NPN output type)
3: Diameter of detection capability (mm)
4: L is emitter, D is receiver, and a blank is emitter/receiver set.
For models with fixed auto reset, the suffix "-L-TS" is an emitter,
"-D-TS" is a receiver, and "-TS" is an emitter/receiver set.
Extension Single-end connector cable
cable

Double-end connector cable

F39-JC@A

This extension cable is used to connect to a terminal block controller
(e.g. F3SX, G9SA, G9SB, G9SX) or to a safety processing system
(e.g. DeviceNet safety).

F39-JC@B

This extension cable is used when the length of the connection cable
is insufficient, or when connecting to an F3SP-B1P controller. The
length can be specified.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

31

■ Internal Indicators
Total View
Receiver

Emitter
LEVEL

1. Light intensity
level indicators

2. Error mode indicators

LEVEL

LEVEL-5 (Green)

5

5

LEVEL-4 (Green)

4

4

LEVEL-4 (Green)

LEVEL-3 (Orange)

3

3

LEVEL-3 (Orange)

LEVEL-2 (Orange)

2

2

LEVEL-2 (Orange)

LEVEL-1 (Orange)

1

1

LEVEL-1 (Orange)

ERROR-C (Red)

C

C

ERROR-C (Red)

ERROR-B (Red)

B

B

ERROR-B (Red)

ERROR-A (Red)

A

A

ERROR-A (Red)

ERROR

ERROR

POWER

OFF

INTLK

ON

3. Power indicator (Green)

EDM

2. Error mode indicators

8. ON-state indicator (Green)
9. Not used (Green)
[Muting error indicator]

BLANKING
(TEST)

BLANKING
(TEST)

RECEIVER

5. External device monitoring
indicator (Green)
[Muting input 1 indicator]
6. Blanking/Test indicator (Green)
[Muting input 2 indicator]
(See note 2.)

1. Light intensity
level indicators

7. OFF-state indicator (Red)

EMITTER

4. Interlock indicator (Yellow) (See note 1.)

LEVEL-5 (Green)

30 dia.

(See
note 3.)

10. Not used (Green)
[Blanking/Test indicator]
(See note 2.)

30 dia.

The words in brackets ([ ]) represent
the indicator name for the muting.
No.

Internal Indicators

Description
For basic system

For muting system

1

Light intensity level indicators (LEVEL-1 to ON
5)
(refer to page 33.)

Indication status of LEVEL-1 to 5 shows the light intensity level status of the F3SJ.

2

Error mode indicators (ERROR-A to C)
(refer to page 33.)

Turns ON or blinks only on the sensor where the error occurred when the F3SJ enters lockout. The
error mode indicators turn OFF on sensors (emitters or receivers) where an error did not occur, or on
other series-connected sensors. The indication status of ERROR-A to C shows the cause of the
error. Affix the error mode label (included) near the F3SJ to allow for quick troubleshooting when
errors occur.

3

Power indicator (POWER)

4

Interlock indicator (INTLK) (See note 1.)

5

External device monitoring indicator
(EDM)
Muting input 1 indicator (MUTE1)

6

Blanking/Test indicator (BLANKING/
TEST) (See note 2.)
Muting input 2 indicator (MUTE2)

7

OFF output indicator (OFF)

8

ON output indicator (ON)

ON/
Blinking

ON

Turns ON while the power is ON.

Blinking

Blinks when in maintenance mode.

ON

Turns ON when F3SJ is in interlock state.

Blinking

Blinks when under lockout.

ON

Turns ON when an input is given to external device Turns ON when an input is given to muting input
monitoring input.
1.

Blinking

Not used

ON

Turns ON when the blanking function and warning Turns ON when an input is given to muting input 2.
zone function are enabled.

Blinks during muting override.

Blinking

Blinks when external test is being performed.

ON

Turns ON when control output is OFF.

Blinking

Blinks in the following states:
• Lockout state
• One or more beams are blocked in maintenance mode

Blinks during muting override.

ON

Turns ON when safety output is ON.

Blinking

Blinks when no beams are blocked in maintenance mode

9

Muting error indicator (MUTING ERROR) ON

Not used

10

Blanking/Test indicator (BLANKING/
TEST) (See note 2.)

ON

Not used

Turns ON when a muting error occurs.
Turns ON when the blanking function is enabled.

Blinking

Not used

Blinks when external test is being performed.

Note: 1. Lockout indicator (LOCKOUT) for models with the "-TS" suffix.
2. In the TS model, this is a test indicator labeled TEST.
3. This label is included with the F39-CN6 key cap for muting. Affix the label when the muting function is used.

32

Safety Light Curtain (Type 4) F3SJ

Ver. 2

■ Indication Patterns and Intensity Levels of the Light Intensity Level
Indicators (LEVEL-1 to 5)
ON

OFF
1

2

3

4

5

Light intensity level
170% or higher of control output ON level
From 130 to 170% of control output ON level
From 100 to 130% of control output ON level
From 75 to 100% of control output ON level
From 50 to 75% of control output ON level
Less than 50% of control output ON level

Note: Operation is possible with light intensity level of 100% or more, but to ensure stability, operate when at least 5 of the
indication lamps are ON.

■ Error Mode Indication Patterns and Cause of Errors (ERROR-A to C)
OFF Blinking ON
A

B

C

Cause of error
Mutual interference or ambient incident light.
Power supply voltage of F3SJ is out of the rated range. Insufficient current capacity of
power supply.
Incident light to blanking beams.
Failure in communication line.
Emitter and receiver have different F3SJ type names or number of series connections.
Outside the effective range of parameters set by setting tool.
Cap is not attached.
External device monitor failure.
Failure in interlock selection input line or reset input line.
Muting wiring failure.
Failure in control output wiring.
Failure in series connection cable wiring.
Failure in wiring of external display lamp output.
Failure in wiring of auxiliary output.
Broken series connection cable.
Wiring error or broken communications wire.
Influence of electrical noise, or failure in a series-connected F3SJ.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

33

Safety-related Functions
Interlock Function

Manual Reset Wiring Procedure:

The F3SJ turns the safety outputs OFF when the power is turned ON
or when a beam is interrupted, and maintains this state until a reset
signal is applied. This state is called "interlock".
You can reset this interlock by 2 methods; “auto reset that
automatically turns safety output ON when an interrupting object is
removed” and “manual reset mode that keeps safety output OFF until
a reset signal is provided if the interrupting object is removed”.

Auto Reset Mode
When an interrupting object is removed, safety output automatically
turns ON. Auto reset is used on machines where a worker is not able
to enter the area between the detection zone and the hazardous part
of the machine.

Auto reset wiring procedure:
For NPN output

1. Open the interlock selection 1. Open the interlock selection
input line, or short-circuit it to 9
input line, or short-circuit it to 0
to 24 V (pin 1/white).
to 1.5 V (pin 1/white).
2. Short-circuit the reset input
2. Short-circuit the reset input
line to 0 to 1.5 V (pin 4/yellow).
line to 9 to 24 V (pin 4/yellow).
3. Turn ON the power of F3SJ. 3. Turn ON the power of F3SJ.

Manual Reset Mode
When a reset input is given while no interrupting object exists in a
detection zone, the safety outputs turn ON. This allows the machine
to be manually reset using a reset switch after ensuring safety,
preventing unexpected startup.
Light
incident
Light incident/
Light interrupted Light

interrupted

Reset Input

Control output

250 ms min.

ON
OFF

ON
OFF

Sensor status

Interlock state

Normal operation

A sensor enters interlock state when:
• The power is turned ON (start interlock). This is useful if you want
to keep the machine stopped until start inspection is completed
after the power is turned ON.
• F3SJ is interrupted (restart interlock). After F3SJ is interrupted and
the machine stops, the machine can be restarted after safety is
ensured.

34

Safety Light Curtain (Type 4) F3SJ

Ver. 2

For NPN output

To reset:
For PNP output
Apply voltage of 9 to 24 V for
250 ms or longer to the reset
input line, and set it open or to 0
to 1.5 V.

Note: Auto reset is always used in the F3SJ-A@-TS series.

For PNP output

For PNP output

1. Connect the interlock selection
1. Connect the interlock
input line to 0 to 1.5 V (pin 1/
selection input line to 9 to 24 V
white).
(pin 1/white).
2. Connect the reset input line to 2. Connect the reset input line to
0 to 1.5 V via the reset switch
9 to 24 V via the reset switch
(NO-contact) (pin 4/yellow).
(NO-contact) (pin 4/yellow).
3. Keep the reset switch contact 3. Keep the reset switch contact
open, and turn the power of
open, and turn the power of
F3SJ ON.
F3SJ ON.

For NPN output
Apply voltage of 0 to 1.5 V for
250 ms or longer to the reset
input line, and set it open or to
9 to 24 V.

Note: Install the reset switch outside the hazardous area, where the
operator can clearly see the hazardous area.

Interlock Function in a Muting System
Because the interlock selection input line is used as muting input 1
when using the muting function, the default setting is auto reset. Use
a setting tool for manual reset.

■ Diagnostic Functions
Self-test

External Device Monitoring Function

A self-test is performed to check for errors when the power is turned
ON (within 2 seconds / within 2.2 seconds when series connected).
Also, the self-test is regularly performed (within the response time)
while operating.

This function detects malfunctions, such as welded contacts in
external relays (or contactors) that control the hazardous area of a
machine.

Waveform of Control Outputs
When the F3SJ is receiving light, the control outputs cyclically turn
OFF as shown below to test the output circuit. When this OFF signal
is fed back, the output circuit is diagnosed as normal. If the output
signal does not include an OFF pulse signal, the receiver determines
that a failure has occurred with the output circuit or wiring, and enters
lockout state. (Refer to the following illustration.)
Approx. 15 ms

This function constantly monitors that a specified voltage is applied
to the receiver's external device monitoring input line, and enters
lockout state when an error occurs. The relay's operational delay can
be up to 300 ms without being evaluated as an error.
For example, if a specified voltage is not applied to the external
device monitoring line because the normally closed (NC) contact is
not closed within 300 ms after the control outputs turn from ON to
OFF, it is evaluated as an error and enters a lockout state.
To utilize this function properly, use safety relays and contactors that
have forcibly guided or mechanically linked contact structure.

Other Functions
ON
Control output 1,2

Auxiliary Output (Non-safety output)

OFF

The auxiliary output is used to monitor the status of the F3SJ.

OFF signal

This output can be connected to a device such as a relay, indication
lamp, programmable controller, etc.
There are two auxiliary outputs: Auxiliary output 1 and auxiliary
output 2.
• Auxiliary output 1: Control output inversion signal
• Auxiliary output 2: Turns ON when the point of 30,000 operating
hours is reached
The auxiliary output modes can be changed with a setting tool. See
the User's Manual for details on the modes that can be set.

Approx. 65 µs
Approx. 140 µs

!WARNING

External Test
This function performs a test to ensure that the safety system stops
properly when the F3SJ is interrupted, by using an external signal to
forcibly stop emission.
To stop emission, apply 9 to 24 V for PNP output types or 0 to 1.5 V
for NPN output types to the test input line of the emitter. Apply the
voltage for a minimum of 4 x the safety output response time.

Lockout

Do not use the auxiliary output or external indicator output for safety
applications.
Failure of these outputs may prevent detection of people and result in
serious injury.
Note: 1. Auxiliary output 1 has a load current of 300 mA max., and
auxiliary output 2 has a load current of 50 mA.
2. The timing when auxiliary output 1 is set as a control output
inversion signal is shown in the diagram below.

If an error is found in the self-test, the sensor enters lockout state,
keeps the safety output in the OFF state, and indicates the error at
the same time.

Light incident/
Light interrupted

Resetting Lockout

Control
output

Light
incident
Light
interrupted

Toff

When a cause of lockout is removed, you can release the lockout by
using either of the following methods.
• Cycle the power back ON
• Reset input
[For PNP output]
After manual reset, apply voltage of 9 to 24 V for 100 ms or longer to
the reset input line, and set it open or apply 0 to 1.5 V.
After auto reset, apply voltage of 0 to 1.5 V for 100 ms or longer to
the reset input line, and set it open or apply 9 to 24 V.

OFF
(See note.)
Toff × 2 or less

Auxiliary
output 1

Ton

ON
(See note.)
Toff × 2 or less

ON
OFF

Toff: Response time of control output's ON to OFF, Ton: Response
time of control output's OFF to ON
Note: When auxiliary output 2 is set as a control output inversion
signal, the response delay for control output becomes Toff x 3
max.

[For NPN output]
After manual reset, apply voltage of 0 to 1.5 V for 100 ms or longer to
the reset input line, and set it open or apply 9 to 24 V.
After auto reset, apply voltage of 9 to 24 V for 100 ms or longer to the
reset input line, and set it open or apply 0 to 1.5 V.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

35

Selecting the System Configuration
Selection Flowchart
The necessary system configuration varies depending on the functions to be used. Use the following flowchart to decide what kind of system is
required.

Will the muting function be NO
used?
YES

Will the fixed blanking function be used?
Will the floating blanking function be used?
Will the detection distance be changed?
Will other functions be used or changed?

NO

YES

Will the fixed blanking function be used?
Will the floating blanking function be used?
Will the detection distance be changed?
Will other functions be used or changed?
YES

Basic system

Basic system plus a setting tool
for setting or changing parameters

NO

Muting system*

Muting system*
plus a setting tool for setting or
changing parameters
*F39-CN6 Key Cap for muting is required.

Note: Refer to the User's Manual to determine whether the functions can be used in combination or not.

36

Safety Light Curtain (Type 4) F3SJ

Ver. 2

System Configuration and Connection (Basic system)
"Basic system" refers to the F3SJ with its default factory settings. The basic system provides basic safety light curtain functions.
Most functions can be used without performing additional configuration.

Basic Connection
For PNP output (See page 39 for NPN output wiring.)

Emitter

Receiver

Wiring when using manual reset mode, external device monitoring

(See
note 2.)

(See
note 1.)

S2
(See
note 1.)

K1

K2

K3

K1

Shield

0 V (Blue)

Control output 2 (White)

Control output 1 (Green)

Auxiliary output 1 (Yellow)

24 V (Brown)

24 V (Brown)

Reset input (Yellow)

Test input (Green)

S1

(Pink)
Communication
line (−)

External device monitoring input (Red)

K4

Interlock selection input (White)

Auxiliary output 2 (Red)

0 V (Blue)

Shield

(Gray) Communication line (+)

K2

(See
note 2.)

24 VDC
Power
0 V supply

S1:
External test switch (connect to 0 V if the switch is not necessary.)
S2:
Interlock/lockout reset switch
K1, K2: Relay or other device that controls hazardous parts of the machine
K3, K4: Load or PLC, etc. (for monitoring)
Note: 1. Use a switch for micro loads (Input specifications: 24 V, 1.8 mA).
2. F3SJ operates even when K3 and K4 are not connected.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

37

Wiring for auto reset mode

Emitter

The auto reset mode will be enabled when the emitter is wired as shown below.

Communication line (+) (Gray)

K4
(See
note 2.)

S1

24 V (Brown)

Reset input (Yellow)

Test input (Green)

Interlock selection input (White)

Auxiliary output 2 (Red)

0 V (Blue)

Shield

Communication line (−) (Pink)
S1:
S3:
K4:

External test switch (connect to 0 V if the switch
is not necessary.)
Lockout reset switch (connect to 24 V if the
switch is not necessary)
Load or PLC, etc. (for monitoring)

Note: 1. Use a switch for micro loads (Input specifications:
24 V, 1.8 mA).
2. F3SJ operates even when K4 is not connected.

S3
(See
note 1.)

(See
note 1.)

24 VDC
Power
0 V supply

Wiring when the external device monitoring function will not be used

Receiver

• Use a setting tool to set the external device monitoring function to "Disabled."
• When using an auxiliary output 1 that has not been changed (output operation mode is "control output data," and inverse of control output
signals is "Enabled), the external device monitoring function will be disabled when auxiliary output 1 and the external device monitoring input are
connected as shown below.

(Gray) Communication line (+)

K3

K1

K2

Shield

0 V (Blue)

Control output 2 (White)

Control output 1 (Green)

Auxiliary output 1
(Yellow)

External device monitoring input (Red)

24 V (Brown)

(Pink) Communication line (−)

K1, K2:
K3:

Relay or other device that controls
hazardous parts of the machine
Load or PLC, etc. (for monitoring)

Note: The F3SJ operates even when K3 is not connected.
When K3 is not necessary, connect auxiliary output
1 only to the external device monitoring input.

(See
note.)

24 VDC
Power
0 V supply

38

Safety Light Curtain (Type 4) F3SJ

Ver. 2

For NPN output (See page 37 for PNP output wiring.)

Emitter

Receiver

Wiring when using manual reset mode, external device monitoring

(See
note 2.)

S2
(See
note 1.)

K1

K2

K3

K1

Shield

0 V (Blue)

Control output 2 (White)

Control output 1 (Green)

Auxiliary output 1 (Yellow)

24 V (Brown)

24 V (Brown)

Reset input (Yellow)

Test input (Green)

S1
(See
note 1.)

(Pink)
Communication
line (−)

External device monitoring input (Red)

K4

Interlock selection input (White)

Auxiliary output 2 (Red)

0 V (Blue)

Shield

(Gray) Communication line (+)

K2

(See
note 2.)

24 VDC
Power
0 V supply

S1:
S2:
K1, K2:
K3, K4:

External test switch (connect to 24 V if the switch is not necessary.)
Interlock/lockout reset switch
Relay or other device that controls hazardous parts of the machine
Load or PLC, etc. (for monitoring)

Note: 1. Use a switch for micro loads (Input specifications: 5 V, 1 mA).
2. F3SJ operates even when K3 and K4 are not connected.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

39

Wiring for auto reset mode

Emitter

The auto reset mode will be enabled when the emitter is wired as shown below.

Communication line (+) (Gray)

K4
(See
note 2.)

S1

24 V (Brown)

Reset input (Yellow)

Test input (Green)

Interlock selection input (White)

Auxiliary output 2 (Red)

0 V (Blue)

Shield

Communication line (−) (Pink)

S1:
S3:
K4:

External test switch (connect to 0 V if the switch
is not necessary.)
Lockout reset switch (connect to 24 V if the
switch is not necessary)
Load or PLC, etc. (for monitoring)

Note: 1. Use a switch for micro loads (Input specifications:
5 V, 1 mA).
2. F3SJ operates even when K4 is not connected.

S3

(See
note 1.)

(See
note 1.)

24 VDC
Power
0 V supply

Wiring when the external device monitoring function will not be used

Receiver

• Use a setting tool to set the external device monitoring function to "Disabled."
• When using an auxiliary output 1 that has not been changed (output operation mode is "control output data," and inverse of control output
signals is "Enabled), the external device monitoring function will be disabled when auxiliary output 1 and the external device monitoring input are
connected as shown below.

(Gray) Communication line (+)

K3

K1

K2

Shield

0 V (Blue)

Control output 2 (White)

Control output 1 (Green)

Auxiliary output 1
(Yellow)

External device monitoring input (Red)

24 V (Brown)

(Pink) Communication line (−)

K1, K2:
K3:

Relay or other device that controls
hazardous parts of the machine
Load or PLC, etc. (for monitoring)

Note: The F3SJ operates even when K3 is not connected.
When K3 is not necessary, connect auxiliary output
1 only to the external device monitoring input.

(See
note.)

24 VDC
Power
0 V supply

40

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Examples of Safety Circuits
For PNP output (See page 46 for NPN output wiring.)
Wiring for single F3SJ application (category 4)
• Use of welded relay contact detection and interlock is possible without a controller or relay unit.

Emitter

• Manual reset mode
• Using external device monitoring
function

Receiver

F39-JC@A-L

F39-JC@A-D

KM2

Shield

Control output 2 (White)

KM1

0 V (Blue)

Control output 1 (Green)

KM1

Auxiliary output 1 (Yellow)

External device monitoring input (Red)

Communication
line (−) (Pink)

KM4

+24 V (Brown)

+24 V (Brown)

Interlock selection input (White)

Reset input (Yellow)

Test input (Green)
S2

S1

Auxiliary output 2 (Red)

0 V (Blue)

Shield

Communication
line (+) (Gray)

KM1
KM2

KM2

KM3

+24 VDC

OUT

IN

M

E1
0V

Timing Chart

Light incident
Light interrupted

External test switch (S1)
Reset switch (S2)
Control output
KM1,KM2 N.O. contact

PLC
S1:

External test switch (connect to 0 V if the
switch is not necessary.)
S2:
Interlock/lockout reset switch
KM1, KM2:Safety relay with forcibly-guided contacts
(G7SA) or magnetic contactor
KM3:
Load, PLC (for monitor)
KM4:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety
system)

KM1,KM2 N.C. contact
PLC input (See note.)
PLC output
Note: The output operation mode for auxiliary output 1 is control
output data/inverse of control output signals enabled
(default setting).

Safety Light Curtain (Type 4)

F3SJ Ver. 2

41

Wiring for connection with a controller F3SP-B1P (category 4) (PNP models only)
• Reduced wiring due to connector connection
• Safety relay included

Emitter

• Manual reset mode
• Using external device monitoring
function

Receiver

PLC
IN1

F39-JC@B-L

IN2

OUT

F39-JC@B-D

KM3

S1
S2
A1

H1

L1
Interlock
selection
OSSD1

K1

A2
+24 VDC

J1

H1

X1

Test

P1

23

33

41

Reset Auxiliary
output 1

OSSD2 K1

KM1

K2

KM2

K2

PE

External device
monitoring
T31

F3SP-B1P

T32

KM2

0V

14

24

34

42

M

KM1

E1

Timing Chart

13

KM1

KM2
S1:
External test switch
S2:
Interlock/lockout reset switch
KM1, KM2:Magnetic contactor
KM3:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related
to safety system)

Light incident
Light interrupted
External test switch (S1)
Reset switch (S2)

Wiring for auto reset mode
Control output

S1
K1,K2 N.O. contact

S2

KM1,KM2 N.O. contact

H1

L1

J1

H1

X1

K1,K2 N.C. contact

Interlock
selection

KM1,KM2 N.C. contact

Test

Wiring when the external device
monitoring function will not be used

PLC input 1 (See note 1.)
PLC input 2

External device
monitoring

PLC output

Note: 1. The output operation mode for auxiliary output 1 is control
output data/inverse of control output signals enabled (default
setting).
2. When the F3SP-B1P is used, the system cannot be used as
a muting system.

42

Safety Light Curtain (Type 4) F3SJ

Reset

Ver. 2

T31

T32

Included short bar

Wiring for connection with a controller F3SX-E-L2R (category 4) (PNP models only)
• Emergency stop switch can be connected.
• Door switch, two hand control, single beam, or relay unit can be used in combination with F3SX.
• Various settings can be changed and input/output terminals can be monitored using the setting support software for F3SX.
L2 Module

F3SJ settings
• Auto reset mode
• External device monitoring
function disabled

F3SJ (1st unit)
2

8

6

1

3

4

5

7

12

10

Emitter

Receiver

Wiring when safety light curtain
F3SJ is not used
15

9

11

16

14

13

F3SX-E-L2R settings
• Manual reset mode
• Using feedback time monitoring function
Model F39-JC@A-L
cable for emitter

Wiring for auto reset mode

Model F39-JC@A-D
cable for receiver

0 V (Blue)
Shield

Control output 1 (White)

24 VDC (Brown)

Control output 1 (Green)

Y3

Communication
line (−) (Pink)

External device
monitoring input (Red)
(See note 2.)
Auxiliary output 1 (Yellow)

Y2

24 VDC (Brown)

E1
Y1

Reset input (Yellow)

Shield

24 VDC

Interlock selection input (White)

0 V (Blue)

S2

Auxiliary output 2 (Red)
Open
Test input (Green)

Communication
line (+) (Gray)

Relay Output Module

Main Module

(R Module)
S2
11

21

12

22

S1
Fuse

24 VDC
E1
A1

T11

T12

T21

T22

Y1

Y2

2

Y3

8

6

1

3

4

5

11

7

Control Circuit

23

33

K1

24 VDC

24 VDC

AC
COM

E1

24 VDC
K2

0V
A2

SSC

AS3

AS2

AS1

SS1

SS2

RY1

RY2

FB

15

9

11

16

14

13

12

10

12

24

34

KM1

KM2

E1
24 VDC

24 VDC
E1

(operation command)
Motor controller
RY1

KM1

Shield
0 V (Blue)

Control output 2 (White)

Control output 1 (Green)

Emitter

24 VDC (Brown)

Open (Red)

Shield

Test SW

Reset input (Yellow)

Model F39-JC@A-D
cable for receiver

Model F39-JC@A-L
cable for emitter

Interlock selection input (White)

24 VDC (Brown)

External device monitoring
input (Red) (See note 2.)
(See note 2.)
Auxiliary output 1 (Yellow)

Wiring when F3SJ's
testing function is used

0 V (Blue)

Note: 1. This wiring example is for category 4.
2. This example shows the connection when auxiliary output
1 is in the standard setting (ON when light is interrupted).
3. When the F3SJ is series-connected, or 5 or more sets are
connected to the total system of F3SX, power must be
supplied to F3SJ from external source.
For details, see instruction manual of F3SX.

Communication
line (−) (Pink)
Communication
line (+) (Gray)

Test input (Green)

S1:

24 VDC (Brown)

Reset input (Yellow)

Interlock selection input
(White)

Shield

Emergency stop switch
(direct opening contacts)(A165E, A22E)
S2:
Reset switch
KM1, KM2: Magnetic contactor (LC1D)
RY1, RY2: Relay
M:
3-phase motor
E1:
24 VDC power supply (S82K)

0 V (Blue)

M

Auxiliary output 2 (Red)
Open
Test input (Green)

RY2
KM2

Receiver
F3SJ (2nd unit)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

43

Wiring for connection with a controller G9SA-301 (category 4) (PNP models only)

Emitter

Receiver

F3SJ settings
• Auto reset mode
• External device monitoring function disabled
G9SA-301 settings
• Manual reset mode
• Using feedback loop
Using emergency stop switch
F39-JC@A-L

F39-JC@A-D

0 V (Blue)

IN2

OUT

Shield

IN1

Control output 2 (White)

Control output 1 (Green)

Auxiliary output 1
(Yellow)

+24 V (Brown)

Communication
line (−) (Pink)

PLC

External device monitoring
input (Red)

+24 V (Brown)

Interlock selection input (White)

0 V (Blue)

Auxiliary output 2 (Red)
Open
S1
Test input (Green)
S4
Reset input (Yellow)

Shield

Communication
line (+) (Gray)

KM3
(See
note 1.)

+24 VDC
E1
0V

12

22

11

21

KM1
KM2
S3

S2

KM1
KM2
A1

A2

T11

T12

T31

33

M

41

K1

K2

K1

23

3
4

1
N.O.

13

T32

K2
K1
N.C.

K2

a
b

Control
Circuit

JP

2
5

1
2
3
4
5
6

6
PE

T21

T23 T22

A

B

14

24

34

42

G9SA-301
KM1

Timing Chart

KM2

Light incident
Light interrupted
External test switch
(S1)

Note: 1. If an emergency stop switch is not used,
connect control output 1 to T12 terminal and
control output 2 to T23 directly.
S1:
External test switch (connect to 0 V if the switch is
not necessary.)
S2:
Interlock reset switch
S3:
Emergency stop switch (direct opening contacts)
(A165E, A22E)
S4:
Lockout reset switch (connect to 24 V if the switch
is not necessary.)
KM1, KM2:Magnetic contactor
KM3:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety system)

Wiring for auto reset mode

Interlock reset switch
(S2)
Emergency stop switch
(S3)

KM1

Control output
KM2

K1,K2 N.O. contact
T31 T32

KM1,KM2 N.O. contact
K1

K1,K2 N.C. contact

K2

KM1,KM2 N.C. contact

Control
Circuit

PLC input 1 (See note 2.)
PLC input 2

A

PLC output

Note: 2. The output operation mode for auxiliary output 1 is control output
data/inverse of control output signals enabled (default setting).

44

Safety Light Curtain (Type 4) F3SJ

Ver. 2

B

Wiring for connection with a controller G9SX-AD322-T15 (category 4) (PNP models only)
• Can be configured for partial control and total control.
• Can be extended to connect a door switch or a relay unit.

Emitter

Receiver

F3SJ settings
• Auto reset mode
• External device monitoring function disabled

F39-JC@A-L

G9SX-AD322-T15 settings
• Auto reset mode
• Using feedback loop

F39-JC@A-D

0 V (Blue)

Feedback loop
Shield

Control output 2 (White)

Control output 1 (Green)

Auxiliary output 1 (Yellow)

Communication
line (−) (Pink)

+24 V (Brown)
External device monitoring
input (Red)

+24 V (Brown)

Interlock selection input (White)

Reset input (Yellow)
S2

Auxiliary output 2 (Red)
Open
S1
Test input (Green)

0 V (Blue)

Shield

Communication
line (+) (Gray)

KM1
KM2

Motor controller

KM3
KM4
+24 V

A1
+24 VDC
E1
0V

T11 T12 T21 T22
Open
Open

+24 V

KM1

KM3

KM2

KM4

S34

AND

T31 T32 T33 Y1

M1

T41 T42
Open Open

M2

OFF

Control circuit

A2

S14 S24 S34 S44 S54 L1
KM1 KM2

KM3 KM4

Motor controller
(operation command)

Timing Chart
Control output
KM1,KM2 N.C. contact

X1 X2
PLC, etc.

G9SX-AD322-T15

S1:

External test switch (connect to 0 V if the switch is
not necessary.)
S2:
Lockout reset switch (connect to 24 V if the switch
is not necessary.)
KM1 to KM4: Magnetic contactor
M1, M2:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety
system)

Wiring for manual reset mode

KM3,KM4 N.C. contact
KM1,KM2 N.O. contact

Feedback loop

KM3,KM4 N.O. contact
Motor operation command

KM1
Motor rotation
OFF-delay time

KM2
S3
KM3
KM4

+24 V

T31 T32 T33 Y1

S3: Reset switch

Safety Light Curtain (Type 4)

F3SJ Ver. 2

45

For NPN output (See page 41 for PNP output wiring.)
Wiring for single F3SJ application (category 4)
• Use of relay welded relay contact detection and interlock is possible without a controller or relay unit.

• Manual reset mode
• Using external device monitoring
function

Receiver

Emitter

F39-JC@A-L

F39-JC@A-D

KM1

Shield

0 V (Blue)

External device monitoring
input (Red)

Control output 2 (White)

KM1 KM2

Auxiliary output 1 (Yellow)

KM3

Control output 1 (Green)

Communication
line (−) (Pink)

KM4

+24 V (Brown)

+24 V (Brown)

Auxiliary output 2 (Red)

Interlock selection input (White)

Reset input (Yellow)

Test input (Green)
S2

0 V (Blue)
S1

Shield

Communication
line (+) (Gray)

KM1
KM2

KM2

M
IN

24 VDC

OUT

E1
PLC

0V

Timing Chart
Light incident
Light interrupted

S1:

External test switch (connect to 24 V if the
switch is not necessary.)
S2:
Interlock/lockout reset switch
KM1, KM2: Safety relay with forcibly-guided contacts
(G7SA) or magnetic contactor
KM3:
Load, PLC (for monitor)
KM4:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety
system)

External test switch (S1)
Reset switch (S2)
Control output
KM1,KM2 N.O. contact
KM1,KM2 N.C.contact
PLC input (See note.)
PLC output
Note: The output operation mode for auxiliary output 1 is control output
data/inverse of control output signals enabled (default setting).

46

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Wiring for connection with a controller G9SA-301-P (category 4) (NPN models only)
Emitter

F3SJ settings
• Auto reset mode
• External device monitoring function disabled

Receiver

G9SA-301-P settings
• Manual reset mode
• Using feedback loop
Using emergency stop switch

F39-JC@A-L

F39-JC@A-D

0 V (Blue)

IN2

OUT

Shield

IN1

Control output 2 (White)

Control output 1 (Green)

Auxiliary output 1
(Yellow)

+24 V (Brown)

PLC
External device monitoring
input (Red)

Communication
line (−) (Pink)

+24 V (Brown)

Reset input (Yellow)

Interlock selection input (White)

Test input (Green)
S1

Auxiliary output 2 (Red)
Open

0 V (Blue)

Shield

Communication
line (+) (Gray)

KM3
(See
note 1.)

+24 VDC
E1
0V

12

22

11

21

KM1
KM2
S3

S2

KM1
KM2
A1

A2

T11

T12

33

M

41

K1

K2

K1

23

3
4

6
a

13

T31 T32

K2
K1
b

K2

a
b

Control
Circuit

JP

2
5

1
2
3
4
5
6

1
PE T21

T23 T22

G9SA-301-P

Timing Chart

A

B

14

KM1

24

34

42

KM2

Light incident
Light interrupted
External test switch
(S1)
Interlock reset switch
(S2)
Emergency stop switch
(S3)

Note: 1. If an emergency stop switch is not used,
connect control output 1 to T12 terminal and
control output 2 to T23 directly.
S1:

External test switch (connect to 24 V if the switch
is not necessary.)
S2:
Interlock reset switch
S3:
Emergency stop switch (direct opening contacts)
(A165E, A22E)
S4:
Lockout reset switch (connect to 0 V if the switch
is not necessary.)
KM1, KM2: Magnetic contactor
KM3:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety
system)

Wiring for auto reset mode

Control output
K1,K2 N.O. contact
KM1

KM1,KM2 N.O. contact
KM2

K1,K2 N.C. contact
T31 T32

KM1,KM2 N.C. contact
PLC input 1 (See note 2.)
K1

PLC input 2
K2

PLC output

Note: 2. The output operation mode for auxiliary output 1 is control
output data/inverse of control output signals enabled
(default setting).

Control
Circuit

A

Safety Light Curtain (Type 4)

B

F3SJ Ver. 2

47

System Configuration and Connection (Muting system)
Muting System

Muting Sensor

The muting function temporarily disables the safety function of the
F3SJ, keeping the control outputs ON even if beams are interrupted.
This makes it possible to install safety light curtains for AGV
passage, enabling both safety and productivity.

The muting sensor is the sensor that is the trigger for temporarily
disabling the safety functions of F3SJ. You can use a photoelectric
switch of through-beam or retro-reflective types, proximity sensor, or
limit switch. (OMRON's E3Z series, E2E series, and D4N series
sensors are recommended.) For the PNP type F3SJ, use a sensor
with PNP transistor outputs or N.O type contacts. For the NPN type
F3SJ, use a sensor with NPN transistor outputs or N.O type
contacts. For NPN type F3SJ, use a sensor with NPN transistor
outputs or N.O type contacts.

When muting, the muting lamp (external indicator) blinks to notify
people in the surrounding area that the safety functions are disabled.

Muting Lamp (External indicator)
To notify workers that the muting function is working, external lamp(s)
must be installed. Use the F39-A01P@-PAC external indicator set or
an F39-JJ3N universal indicator cable with a commercially available
external indicator.

F3SJ Internal Indicators
• The muting input 1 indicator turns ON when input is applied to
muting input 1.
• The muting input 2 indicator turns ON when input is applied to
muting input 2.
• The muting input 1 indicator and muting input 2 indicator blink
under muting override.
• The muting error indicator on the receiver side turns ON when
there is a muting error.

!WARNING
The muting and override functions disable the safety functions of the
device. Additional safety measures must be taken to ensure safety
while these functions are working.
Install muting sensors so that they can distinguish between the
object that is being allowed to be pass through the detection zone
and a person.
If the muting function is activated by the detection of a person, it may
result in serious injury.
Muting lamps (external indicators) that indicate the state of the
muting and override functions must be installed where they are
clearly visible to workers from all the operating positions.

Upgrading F3SJ for Muting System
1. Remove the caps of the emitter and receiver.
(A screwdriver is included with the key cap for muting.)
2. Install a muting lamp (external indicator) on either the emitter or
receiver.
3. Attach the key cap for muting to the emitter/receiver on which the
muting lamp (external indicator) was not installed.
Muting lamp (external indicator)
External indicator set
Model F39-A01P@-PAC
Commercially
available
external
indicator

2.

Universal indicator
cable
Model F39-JJ3N
Brown: +, Blue: −

Cap

Key Cap for Muting
F39-CN6
(Case: orange)

1.

(Case: black)

48

3.

1.

Cap
(Case: black)

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Attachment Positions for Included Labels
Internal indicator labels are included with the F39-CN6 Key Cap for
Muting. When using a muting system, attach the internal indicator
labels so the arrows will be in line with the positions of the indicators,
as shown by the shading below.
Emitter

Receiver
Internal
indicator labels

Standard Muting Mode
The F3SJ is set to this operation mode when it is shipped from the
factory. The muting function is enabled by providing a time lag
between muting inputs 1 and 2. Use a separately purchased setting
tool to change parameters related to muting time, or to select other
muting operation modes.

Start Conditions
If both of the following 2 conditions are present, muting is activated.

• T2: Muting time limit
This is the continuous time of the muting function, and is set to
60 s. If the muting status exceeds this time, muting is cancelled.
• T3: Allowable pulse-change time for muting input signals
This is the maximum time allowed for a change in the waveform
pulse of muting inputs 1 and 2 while in the muting status.
Note: The muting status can be released even when the system
enters lockout.
The following values can be changed using the Setting Support
Software for the F3SJ:

1. No interrupting object is found in the F3SJ's detection zone, and
control output is ON.
2. After muting input 1 is turned ON (connected to 9 to 24 V for PNP
types, or to 0 to 1.5 V for NPN types), muting input 2 is turned ON
(connected to 9 to 24 V for PNP types, or to 0 to 1.5 V for NPN
types) within the muting input time limit T1 min. to T1 max. (0.03
to 3 s).

• T1 min: Muting input time limit (min.)
• T1 max: Muting input time limit (max.)
• T2: Muting time limit

Once the conditions in item 2 above are met, the muting function will
be enabled in 0.15 s max.

Installation Standard for Muting Sensors

When condition 1 is satisfied but time condition of 2 is not, a muting
sequence error occurs and receiver’s muting error indicator turns
ON.
However, the F3SJ safety functions will continue operating and the
F3SJ will operate normally even during a muting error.
A muting error is released when either of the following occurs:
• When muting is started using a proper procedure
• When power is turned on while muting inputs 1 and 2 are OFF

End Conditions
If either of the following conditions are satisfied, the muting state is
released.
1. Muting input 1 or 2 turns OFF for T3 (0.1 s) or longer.
2. When the muting continuation time exceeds the muting time limit
of T2 (60 s) (a setting tool can be used to change the limit in the
range of 1 to 600 s, or to eliminate the time limit)

The following values can be changed using the Setting Console:
• T2: Muting time limit

• Set the muting sensors so that they can detect all of the passing
detection objects (palettes, automobiles, etc.). Do not install in a
position so that only the front or rear end of the detection object is
detected.
• Set the muting sensors so that they detect the objects even when
they are loaded on palettes or other transport devices.
• Install the F3SJ and muting sensors so that each object passes
through all muting sensors before the next object arrives at the first
muting sensor. Also, install all F3SJ and muting sensors so that no
person is able to accidentally enter the hazardous area while the
muting function is enabled.
• When objects pass through the muting area at different speeds,
consider limiting the muting time.
• For a muting sensor installation example, see the instruction
manual.
• For details about the override function, see the instruction manual.

T3 (0.1 s) max.
ON
Muting input 1

Muting input 2

OFF

T1 min. to T1 max.
T3 (0.1 s) max.

ON
OFF
T2 max.
0.15 s max.∗

Muting status
Muting lamp
(external
indicator)

0.25 s max.

Enabled
Disabled
Blink
OFF
Light
incident

F3SJ
Light incident/
Light
Light interrupted
interrupted
Control output

ON
OFF

∗: This value is the time when the F3SJ is used singly. When used in
a series, this time is as shown in the table below.
∗ Time (s)

Number of Connected Units
1

0.15

Series of 2

0.26

Series of 3

0.29

Series of 4

0.32

• T1 min: Muting input time limit (min.)
This is the minimum input time lag between muting inputs 1 and 2,
and is set to 0.03 s. If the time lag between muting inputs 1 and 2
are shorter than this value, a muting error is generated.
• T1 max: Muting input time limit (max.)
This is the maximum input time lag between muting inputs 1 and 2,
and is set to 3 s. The minimum value must be less than the
maximum value (min. < max.).

Safety Light Curtain (Type 4)

F3SJ Ver. 2

49

Basic Connection for Muting System
For PNP output (See page 51 for NPN output wiring.)
Wiring when using muting and external device monitoring functions
(See
note 4.)

Emitter

Receiver

(See
note 4.)

A1

S1

Shield

0 V (Blue)

24 V (Brown)

Reset input (Yellow)

(Pink)
Communication line (−)

24 V (Brown)
External device
monitoring input (Red)
Auxiliary output 1
(Yellow)
Control output 1
(Green)
Control output 2
(White)

B1

Test input (Green)

0 V (Blue)
Muting input 2
(Red)
Muting input 1
(White)

Shield

(Gray)
Communication line (+)

K1

S2

K3

(See
(See
(See
note 1.) note 1.) note 2.)

K2

K1

K2

(See
note 3.)

24 VDC

(See
note 4.)

Power
0 V supply

S1:
S2:
A1:
B1:
K1, K2:
K3:
M1:

External test switch (connect to 0 V if the switch is not necessary.)
Lockout reset switch (connect to 24 V if the switch is not necessary.)
Contact by muting sensor A1
Contact by muting sensor B1
Relay or other device that controls hazardous parts of the machine
Load or PLC, etc. (for monitoring)
Muting lamp

Note: 1.
2.
3.
4.

Use a switch for small loads (input specifications: 24 V, 1.8 mA)
When using the interlock function, this also functions as an interlock reset switch. (Must be set with a setting tool.)
The F3SJ will operate even if K3 is not connected.
Connect the muting lamp to either the external indicator output or auxiliary output 1 for the emitter or the receiver. When
connecting the muting lamp to auxiliary output 1, the parameter must be changed with a setting tool.

Wiring when the external device monitoring function will not be used

Receiver

• Use a setting tool to set the external device monitoring function to "Disabled."
• When using an auxiliary output 1 that has not been changed (output operation mode is "control output data," and inverse of control output
signals is "Enabled), the external device monitoring function will be disabled when auxiliary output 1 and the external device monitoring input are
connected as shown below.

(Gray) Communication line (+)

K3

K1

K2

Shield

0 V (Blue)

External device
monitoring input (Red)
Auxiliary
output 1 (Yellow)
Control output 1
(Green)
Control output 2
(White)

24 V (Brown)

(Pink) Communication line (−)

K1, K2:
K3:

Relay or other device that controls
hazardous parts of the machine
Load, PLC, etc. (for monitoring)

Note: The F3SJ operates even when K3 is not connected.
When K3 is not necessary, connect auxiliary output 1
only to the external device monitoring input.

(See
note.)

24 VDC
Power
0 V supply

50

Safety Light Curtain (Type 4) F3SJ

Ver. 2

For NPN output (See page 50 for PNP output wiring.)
Wiring when using muting and external device monitoring functions
(See
note 4.)

Emitter

Receiver

(See
note 4.)

B1

A1 S1

Shield

0 V (Blue)

External device
monitoring input (Red)
Auxiliary output 1
(Yellow)
Control output 1
(Green)
Control output 2
(White)

(Pink)
Communication line (−)

24 V (Brown)

24 V (Brown)

Reset input (Yellow)

Test input (Green)

0 V (Blue)
Muting input 2
(Red)
Muting input 1
(White)

Shield

(Gray)
Communication line (+)

K1

K2

S2

(See
(See
note 1.) notes 1
and 2.)

K3

K1

K2

(See
note 3.)

24 VDC

(See
note 4.)

Power
0 V supply

S1:
S2:
A1:
B1:
K1, K2:
K3:
M1:

External test switch (connect to 24 V if the switch is not necessary.)
Lockout reset switch (connect to 0 V if the switch is not necessary.)
Contact by muting sensor A1
Contact by muting sensor B1
Relay or other device that controls hazardous parts of the machine
Load or PLC, etc. (for monitoring)
Muting lamp

Note: 1.
2.
3.
4.

Use a switch for small loads (input specifications: 5 V, 1 mA).
When using the interlock function, this also functions as an interlock reset switch. (Must be set with a setting tool.)
The F3SJ operates even when K3 is not connected.
Connect the muting lamp to either the external indicator output or auxiliary output 1 for the emitter or the receiver. When
connecting the muting lamp to auxiliary output 1, the parameter must be changed with a setting tool.

Wiring when the external device monitoring function will not be used

Receiver

• Use a setting tool to set the external device monitoring function to "Disabled."
• When using an auxiliary output 1 that has not been changed (output operation mode is "control output data," and inverse of control output
signals is "Enabled), the external device monitoring function will be disabled when auxiliary output 1 and the external device monitoring input are
connected as shown below.

(Gray) Communication line (+)

K3

K1

K2

Shield

0 V (Blue)

24 V (Brown)

External device
monitoring input (Red)
Auxiliary
output 1 (Yellow)
Control output 1
(Green)
Control output 2
(White)

(Pink) Communication line (−)

K1, K2:
K3:

Relay or other device that controls
hazardous parts of the machine
Load, PLC, etc. (for monitoring)

Note: The F3SJ operates even when K3 is not connected.
When K3 is not necessary, connect auxiliary output 1
only to the external device monitoring input.

(See
note.)

24 VDC
0V

Power
supply

Safety Light Curtain (Type 4)

F3SJ Ver. 2

51

Example of a Safety Circuit with the Muting System
For PNP output
Wiring for muting function with single F3SJ application (category 4)
When two muting sensors are connected
• Attaching a keycap for muting (F39-CN6) enables the muting function to be used.

Muting lamp
(external indicator)

• Auto reset mode
• Using external device monitoring
function

Emitter

Receiver

F39-JC@A-L

F39-JC@A-D

KM3

KM1

Shield

0 V (Blue)

Control output 2 (White)

KM2

Control output 1 (Green)

KM1

Auxiliary output 1 (Yellow)

24 V (Brown)

External device
monitoring input (Red)

(Pink)
Communication line (−)

24 V (Brown)

Muting input 1
(White)

Reset input
(Yellow)
S2

S1 Test input
(Green)

0 V (Blue)
Muting input 2
(Red)

Shield

(Gray)
Communication line (+)

KM1
KM2

KM2

M
Muting sensor
(PNP output)

IN

24 VDC

OUT

E1
0V

PLC

Reflector

Timing Chart

S1:

External test switch (connect to 0 V if the switch is not
necessary.)
S2:
Lockout reset switch (connect to 24 V if the switch is not
necessary.)
KM1, KM2: Safety relay with forcibly-guided contacts (G7SA) or
magnetic contactor
KM3:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller (Used for monitoring -- not
related to safety system)
Muting sensor: Retro-reflective photoelectric sensor (E3Z-R81)

Light incident
Light interrupted
Muting input 1
Muting input 2
Control output
KM1, KM2 N.O. contact
KM1, KM2 N.C. contact
PLC input (See note 1.)
PLC output

Note: 1. The output operation mode for auxiliary output 1 is control output data/inverse of control output signals enabled (default setting).
2. Start interlock and restart interlock can be used with a setting tool.

52

Safety Light Curtain (Type 4) F3SJ

Ver. 2

When four muting sensors are connected
• The muting function can be used by attaching the F39-CN6 Key Cap.

Muting lamp
(external indicator)

• Auto reset mode
• Using external device monitoring function
S1:

Emitter

Receiver

F39-JC@A-L

External test switch (connect to 0 V if the
switch is not necessary.)
S2:
Lockout reset switch (connect to 24 V if the
switch is not necessary.)
KM1, KM2: Safety relay with forcibly-guided contacts
(G7SA) or magnetic contactor
KM3:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety
system)
A1, B1, A2, B2, Muting sensor: Retro-reflective
photoelectric sensor (E3Z-R81)

F39-JC@A-D

KM3

Shield

0 V (Blue)

24 V (Brown)
External device
monitoring input (Red)
Auxiliary
output 1
(Yellow)
Control
output 1 (Green)
Control output
2 (White)

24 V (Brown)

Muting input 1
(White)

(Pink)
Communication line (−)

KM1
KM2

KM1

S2

S1

0 V (Blue)
Muting input 2
(Red)
Test input
(Green)
Reset input
(Yellow)

Shield

(Gray)
Communication
line (+)

KM1 KM2

KM2
M

Timing Chart
IN

OUT

Light incident
Light interrupted

PLC

A1 Control output
+DC24V
E1
0V

Reflector

B1 Control output
A2 Control output

A2

B1

B2 Control output

Muting input 1

Workpiece

Muting input 2
A1

Muting sensor
(PNP output)

B2

F3SJ Control output

F3SJ

KM1, KM2 N.O. contact
KM1, KM2 N.C. contact
PLC input (See note 1.)
PLC output

Note: 1. The output operation mode for auxiliary output 1 is control output data/inverse of control output signals enabled (default setting).
2. Start interlock and restart interlock can be used with a setting tool.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

53

For NPN output
Wiring for muting function with single F3SJ application (category 4)
When two muting sensors are connected
• Attaching a keycap for muting (F39-CN6) enables the muting function to be used.

Muting lamp
(external indicator)

• Auto reset mode
• Using external device monitoring
function

Receiver
Emitter

F39-JC@A-D
F39-JC@A-L

Shield

0 V (Blue)

External device
monitoring input (Red)

Auxiliary output 1 (Yellow)

Control output 2 (White)

Control output 1 (Green)

+24 V (Brown)

+24 V (Brown)

Muting input 2 (Red)

Muting input 1 (White)

Reset input (Yellow)

Communication
line (−) (Pink)

KM3

S2

Test input (Green)

0 V (Blue)
S1

Shield

Communication
line (+) (Gray)

KM1

KM1

KM1 KM2

KM2

KM2

M

Muting sensor
(NPN output)

IN

+24 VDC

OUT

E1
PLC

0V

Reflector

Timing Chart

Light incident
Light interrupted

S1:

External test switch (connect to 24 V if the switch is not
necessary.)
S2:
Lockout reset switch (connect to 0 V if the switch is not
necessary.)
KM1, KM2: Safety relay with forcibly-guided contacts (G7SA) or
magnetic contactor
KM3:
Solid state contactor (G3J)
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety system)
Muting sensor: Retro-reflective photoelectric sensor (E3Z-R61)

Muting input 1
Muting input 2
Control output
KM1,KM2 N.O. contact
KM1,KM2 N.C. contact
PLC input (See note 1.)
PLC output

Note: 1. The output operation mode for auxiliary output 1 is control output data/
inverse of control output signals enabled (default setting).
2. Start interlock and restart interlock can be used with a setting tool.

54

Safety Light Curtain (Type 4) F3SJ

Ver. 2

When four muting sensors are connected
• The muting function can be used by attaching the F39-CN6 Key Cap.

Muting lamp
(external indicator)

• Auto reset mode
• Using external device monitoring function
S1:

External test switch (connect to 24 V if the
switch is not necessary.)
S2:
Lockout reset switch (connect to 0 V if the switch
is not necessary.)
KM1, KM2: Safety relay with forcibly-guided contacts
(G7SA) or magnetic contactor
Solid state contactor (G3J)
Receiver KM3:
M:
3-phase motor
E1:
24 VDC power supply (S82K)
PLC:
Programmable controller
(Used for monitoring -- not related to safety
system)
A1, B1, A2, B2, Muting sensor: Retro-reflective
photoelectric sensor (E3Z-R61)

Emitter

F39-JC@A-D

F39-JC@A-L

KM3

KM1

Shield

0 V (Blue)

24 V (Brown)
Control
output 1 (Green)
Control
output 2
(White)
Auxiliary output 1
(Yellow)
External device
monitoring input (Red)

24 V (Brown)

(Pink)
Communication line (−)

S2

S1

0 V (Blue)
Muting input 2
(Red)
Test input
(Green)
Reset input
(Yellow)
Muting input 1
(White)

Shield

(Gray)
Communication
line (+)

KM1
KM2

KM1

KM2

KM2
M

IN

Reflector

PLC

Light
incident
Light
interrupted
A1 Control output

+DC24V
E1
0V

B1 Control output
A2 Control output

A2

B1

Timing Chart

OUT

B2 Control output

Workpiece

Muting input 1
Muting input 2
A1

B2
F3SJ Control output

Muting sensor
(NPN output)

F3SJ

KM1, KM2 N.O. contact
KM1, KM2 N.C. contact
PLC input (See note 1.)
PLC output

Note: 1. The output operation mode for auxiliary output 1 is control output data/inverse of control output signals enabled (default setting).
2. Start interlock and restart interlock can be used with a setting tool.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

55

Setting Bi-directional Muting
Connect the outer muting sensors A1 and A2 to muting input 1 and the inner muting sensors B1 and B2 to muting input 2.

Connected to muting input 1
Connected to muting input 2
A1

Workpiece

B1

B2

A2

When muting sensors A1 and then B1 (or A2 and then B2)
turn ON in that order, the F3SJ will enter the muting state.

V

A1, A2, B1, B2: Retro-reflective Photoelectric Sensors

F3SJ
Muting from the opposite direction is also possible.

A1 B1

B2 A2

V

Workpiece

F3SJ
D

L

Note: 1. This example arrangement uses E3Z-R@@ Retro-reflective Photoelectric Sensors as the muting sensors. Mutual interference must be
taken into account when installing these Sensors.
2. The muting sensors must be installed so that distance D between muting sensors A1 and A2 is smaller than workpiece length L.
3. Through-beam or Retro-reflective Photoelectric Sensors, Proximity Sensors, or Limit Switches can be used as the muting sensors.

56

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Safety Precautions
This catalog is intended as a guide for product selection. Be sure to use the instruction manual provided with the product for actual operation.

■ Regulations and Standards

■ Precautions for Safe Use

1. Application of an F3SJ-A sensor alone cannot receive type
certification provided by Article 44-2 of the Labour Safety and
Health Law of Japan. It is necessary to apply it in a system.
Therefore, when using the F3SJ-A in Japan as a "safety system
for pressing or shearing machines" prescribed in Article 42 of that
law, the system must receive type certification.
2. The F3SJ-A is electro-sensitive protective equipment (ESPE) in
accordance with European Union (EU) Machinery Directive Index
Annex IV, B, Safety Components, Item 1.

Indication and meaning for safe use

3. The F3SJ-A complies with the following legislation and standards:
1. EU Regulations
• Machinery Directive: Directive 98/37/EC
• EMC Directive: Directive 89/336/EEC
2. European standards:
EN61496-1 (TYPE 4 ESPE),
prEN61496-2 (TYPE 4 AOPD),
EN61508-1 to -7 (SIL3)
3. International standards:
IEC61496-1 (TYPE 4 ESPE),
IEC61496-2 (TYPE 4 AOPD),
EN61508-1 to -7 (SIL3)
4. JIS standards:
JIS B9704-1 (TYPE 4 ESPE),
JIS B9704-2 (TYPE 4 AOPD)
4. The F3SJ-A received the following certification from the EUaccredited body, TÜV SÜD Product Service GmbH:
• EC type test based on machinery directive
Type 4 ESPE (EN61496-1),
Type 4 AOPD(prEN61496-2)
• EMC Competent Body Certificate (Test power supply:
OMRON's S82K)
• TÜV SÜD Product Service Type Certification
Type 4 ESPE (EN61496-1),
Type 4 AOPD (prEN61496-2),
SIL1, 2, 3 (EN61508-1 to -7)
Application: EN954-1 categories B, 1, 2, 3, 4
5. The F3SJ-A has received certificates of UL listing for US and
Canadian safety standards from the Third Party Assessment
Body UL.
• Type 4 ESPE (UL61496-1),
Type 4 AOPD (UL61496-2)
6. The F3SJ-A is designed according to the standards listed below.
To make sure that the final system complies with the following
standards and regulations, you are asked to design and use it in
accordance with all other related standards, laws, and
regulations. If you have any questions, consult with specialized
organizations such as the body responsible for prescribing and/or
enforcing machinery safety regulations in the location where the
equipment is to be used.
• European Standards: EN415-4, EN692, EN693
• US Occupational Safety and Health Administration: OSHA 29
CFR 1910.212
• US Occupational Safety and Health Administration: OSHA 29
CFR 1910.217

Meanings of Signal Words
To ensure safe use of the F3SJ-A, signal words and an alert symbol
are used in this catalog to indicate safety-related instructions.
Because these instructions describe details very important to your
safety, it is extremely important that you understand and follow the
instructions. The signal words and alert symbol used in this catalog
are shown below.

!WARNING
Indicates a potentially hazardous situation which, if not avoided, will
result in minor or moderate injury, or may result in serious injury or
death. Additionally, there may by significant property damage.

!CAUTION
Indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury or in property damage.

Definition of Symbol
Prohibited
Indicates a prohibited action.

Warning Labels
For users
!WARNING
The FS3J must be installed, set, and integrated into the mechanical
control system by a qualified technician who has received the
appropriate training. Failure to make correct settings may prevent
detection of people and result in serious injury.
When changing parameters with a setting tool (F39-GWUM or F39MC21), the change must be made and the contents of the change
must be managed by the person in charge of the system.
Unintentional or mistaken parameter changes may prevent detection
of people and result in serious injury.

For machines
!WARNING
Do not use this sensor for machines that cannot possibly be stopped
by electrical control. For example, do not use it for a pressing machine
that uses full-rotation clutch. Otherwise, the machine may not stop
before a person reaches the hazardous part, resulting in serious
injury.
Do not use the auxiliary output or external indicator output for safety
applications. Failure of the F3SJ may cause a person to go
undetected, resulting in serious injury.

• American National Standard Institute: ANSI B11.1 to B11.19
• American National Standard Institute ANSI/RIA 15.06
• Canadian Standards Association CSA Z142, Z432, Z434
• SEMI standard SEMI S2
• Japanese Ministry of Health, Labour and Welfare
Announcement: "Guidelines for Comprehensive Safety
Standards of Machinery" Announcement No.501, June 1, 2001

Safety Light Curtain (Type 4)

F3SJ Ver. 2

57

For mounting

When using more than 1 set of F3SJ, install them so that mutual
interference does not occur, such as by configuring series
connections or using physical barriers between adjacent sets.

!WARNING
Make sure to test the operation of the F3SJ after installation to verify
that the F3SJ operates as intended. Do not operate the machine until
the test has been completed and F3SJ operation has been verified.
Unintended function settings may cause a person to go undetected,
resulting in serious injury.
Make sure to secure the safety distance between the F3SJ and the
hazardous parts. Otherwise, the machine may not stop before a
person reaches the hazardous part, resulting in serious injury.
Install a protective structure so that the hazardous part of a machine
can only be reached by passing through the sensor's detection zone.
Install the sensors so that part of the person is always present in the
detection zone when working in a machine's hazardous areas. If a
person is able to step into the hazardous area of a machine and
remain behind the F3SJ's detection zone, configure the system with
an interlock function that prevents the machine from being restarted.
Otherwise it may result in heavy injury.

Make sure that the F3SJ is securely mounted and its cables and
connectors are properly connected.
Make sure that no foreign material, such as water, oil or dust, enters
the inside of the F3SJ while the cap is removed.
Do not use the sensor system with mirrors in as retro-reflective
configuration. Doing so may hinder detection. It is possible to use
mirrors to "bend" the detection zone to a 90-degree angle.

Reflector

Install the interlock reset switch in a location that provides a clear view
of the entire hazardous area and where it cannot be activated from
within the hazardous area.
The F3SJ cannot protect a person from an object flying from a
hazardous area. Install protective cover(s) or fence(s).
When detection of an area has been disabled by the fixed blanking
function, provide a protective structure around the entire area that will
prevent a person from passing through it and reaching the hazardous
part of the machinery. Failure to do so may prevent detection of
people and result in serious injury.

Position with retro-reflection

After setting the fixed blanking function, be sure to confirm that a test
rod is detected within all areas that require detection. Failure to do so
may prevent detection of people and result in serious injury.
When the fixed blanking function or the floating blanking function is
used, the diameter for the smallest detectable object becomes larger.
Be sure to use the diameter for the smallest detectable object for the
fixed blanking function or the floating blanking function when
calculating the safety distance. Failure to do so may prevent the
machinery from stopping before a person reaches the hazardous part
of the machinery, and result in serious injury.
The muting and override functions disable the safety functions of the
device. Additional safety measures must be taken to ensure safety
while these functions are working.
Install muting sensors so that they can distinguish between the object
that is being allowed to be pass through the detection zone and a
person. If the muting function is activated by the detection of a person,
it may result in serious injury.
Muting lamps (external indicators) that indicate the state of the muting
and override functions must be installed where they are clearly visible
to workers from all the operating positions.
Muting times must be precisely set according to the application by
qualified personnel who have received appropriate training. In
particular, if the muting time limit is to be set to infinity, the person who
makes the setting must bear responsibility.
Use two independent input devices for the muting inputs.
Install the F3SJ, Muting Sensors, or a protective wall so that workers
cannot enter hazardous areas while muting is in effect, and set muting
times.
Position the switch that is used to activate the override function in a
location where the entire hazardous area can be seen, and where the
switch cannot be operated from inside the hazardous area. Make sure
that nobody is in the hazardous area before activating the override
function.
Install the sensor system so that it is not affected by reflective
surfaces. Failure to do so may hinder detection, resulting in serious
injury.

58

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Reflector

Position with detection
zone bent at 90°
When using series connections, perform inspection of all connected
F3SJs as instructed in the User's Manual.

For wiring
!WARNING
For PNP output, connect the load between the output and 0 V line.
For NPN output, connect the load between the output and +24 V line.
Connecting the load between the +24 V and 0 V lines results in a
dangerous condition because the operation mode is reversed to "ON
when light is interrupted".
[For PNP output]
Do not short-circuit an output line to +24 V line. Otherwise, the output
is always ON, creating a dangerous situation. Also, 0 V of the power
supply must be grounded so that output should not turn ON due to
grounding of the output line.
[For NPN output]
Do not short-circuit an output line to 0 V line. Otherwise, the output is
always ON, creating a dangerous situation. Also, the +24 V line of the
power supply must be grounded so that output does not turn ON due
to grounding of the output line.

Configure the system by using the optimal number of control outputs
that satisfy the requirements of the necessary safety category.
Do not connect each line of F3SJ to a DC power supply higher than
24 V+20%. Also, do not connect to an AC power supply.
Failure to do so may result in electric shock.
For F3SJ to comply with IEC 61496-1 and UL 508, the DC power
supply unit must satisfy all of the following conditions:
• Must be within rated power voltage (24 VDC±20%).
• Must have tolerance against the total rated current of devices if it is
connected to multiple devices.
• Must comply with EMC directives (industrial environment)
• Double or enhanced insulation must be applied between the primary
and secondary circuits.
• Automatic recovery of overcurrent protection characteristics
(reversed L sagging)
• Output holding time must be 20 ms or longer.
• Must satisfy output characteristic requirements for class 2 circuit or
limited voltage current circuit defined by UL508.
• Must comply with EMC, laws, and regulations of a country or a
region where F3SJ is used. (Ex: In EU, the power supply must
comply with EMC Low Voltage Directive.)

Correct position
The hazardous area of a machine can be reached only by passing
through the sensor's detection zone.

A person can only reach the hazardous part of the
machinery by passing through the sensor's detection zone.

A person enters the detection zone during operation.

Double or enhanced insulation from hazardous voltage must be
applied to all input and output lines. Failure to do so may result in
electric shock.
The cable extension length must be no greater than the specified
length. Otherwise, the safety functions may fail to work properly,
resulting in danger.

Others

Incorrect positions
!WARNING

To use the F3SJ in PSDI mode (restart of cycle operation by the
sensor), you must configure an appropriate circuit between the F3SJ
and the machine. For details about PSDI, refer to OSHA1910.217,
IEC61496-1, and other relevant standards and regulations.

A person can reach the hazardous part of the machinery
without passing through the sensor's detection zone.

Do not try to disassemble, repair, or modify this product. Doing so may
cause the safety functions to stop working properly.
Do not use the F3SJ in environments where flammable or explosive
gases are present. Doing so may result in explosion.
Perform daily and 6-month inspections for the F3SJ. Otherwise, the
system may fail to work properly, resulting in serious injury.

Installation Conditions

A person is between the sensor's detection zone and the
hazardous part of the machinery.

Operating Range and Approach
!WARNING
Install a protective structure so that the hazardous part of a machine
can only be reached by passing through the sensor's detection zone.
Install the sensors so that part of the person is always present in the
detection zone when working in a machine's hazardous areas.
If a person is able to step into the hazardous area of a machine and
remain behind the F3SJ's detection zone, configure the system with
an interlock function that prevents the machine from being restarted.
Otherwise it may result in heavy injury.
Install the interlock reset switch in a location that provides a clear view
of the entire hazardous area and where it cannot be activated from
within the hazardous area.
The F3SJ cannot protect a person from an object flying from a
hazardous area. Install protective cover(s) or fence(s).

Safety Light Curtain (Type 4)

F3SJ Ver. 2

59

Safety Distance

If the result exceeds 500 mm, use the following equation
where K = 1,600 mm/s.

The safety distance is the distance that must be set between the
F3SJ and a machine's hazardous part to stop the hazardous part
before a person or object reaches it. The safety distance varies
according to the standards of each country and the individual
specifications of each machine. In addition, the calculation of the
safety distance differs if the direction of approach is not
perpendicular to the detection zone of the F3SJ. Always refer to
relevant standards.
Safety distance (S)

S = 1,600 mm/s x (Tm + Ts) + 8 x (d - 14 mm) . . . Eq. (3)
If the result of this Eq. (3) is less than 500 mm,
use S = 500 mm.
Systems with a Smallest Detectable Object Size (Diameter) Greater
than 40 mm
Assuming K = 1,600 mm/s and C = 850 mm, the following calculation
is made using Eq. (1).
S = 1,600 mm/s x (Tm + Ts) + 850 … Eq. 4,
• S = Safety distance (mm)
• Tm = Machine's response time (s)
• Ts = Response time of the F3SJ from ON to OFF (s)

Hazardous
area

Calculation example:
When Tm = 0.05 s and Ts = 0.01 s,
S = 1,600 mm/s x (0.05 s + 0.01 s) + 850 mm = 946 mm
How to calculate the safety distance specified by American
standard ANSI B11.19
(Ref.)

!WARNING
Make sure to secure the safety distance (S) between the F3SJ and
the hazardous part. Otherwise, the machine may not stop before a
person reaches the hazardous part, resulting in serious injury.
Note: The response time of a machine is the time period from when
the machine receives a stop signal to when the machine's
hazardous part stops.
Measure the response time on the actual system. Also,
periodically check that the response time of the machine has
not changed.
How to calculate the safety distance specified by International
standard ISO13855-2002 (European standard EN999-1999)
(reference)
If a person approaches the detection zone of the F3SJ
perpendicularly, calculate the safety distance as shown below.
S = K x T + C . . . Eq. (1)
•
•
•
•

S: Safety distance
K: Approach speed to the detection zone
T: Total response time of the machine and F3SJ
C: Additional distance calculated by the detection capability of the
F3SJ

System that has detection capability of 40 mm max.
Use K = 2,000 mm/s and C = 8 x (d - 14 mm) in equation (1) for the
calculation.
S = 2,000 mm/s x (Tm + Ts) + 8 x (d - 14 mm)
•
•
•
•

S = Safety distance (mm)
Tm = Machine's response time (s)
Ts = Response time of the F3SJ from ON to OFF (s)
d = Size of F3SJ‘s detection capability (mm)

• S: Safety distance
• K: Approach speed to the detection zone (the value recommended
by OSHA standard is 1,600 mm/s)
Approach speed K is not specified in the ANSI B.11.19 standard. To
determine the value of K to apply, consider all factors, including the
operator's physical ability.
• Ts = Machine's stop time (s)
• Tr = Response time of the F3SJ from ON to OFF (s)
• Tc = Machine control circuit's maximum response time required to
activate its brake (s)
• Tbm = Additional time (s)
If a machine has a brake monitor, "Tbm = Brake monitor setting time
- (Ts + Tc)". If it has no brake monitor, we recommend using 20% or
more of (Ts + Tc) as additional time.
• Dpf = Additional distance
According to ANSI's formula, Dpf is calculated as shown below:
Dpf = 3.4 x (d - 7.0): Where d is the detection capability of the F3SJ
(unit: mm)
[Calculation example]
When K = 1,600 mm/s, Ts + Tc = 0.06 s, brake monitor setting time =
0.1 s, Tr = 0.01 s, d = 14 mm:
Dpf = 3.4 x (14 - 7.0) = 23.8 mm
S = 1,600 x (0.06 + 0.01 + 0.04) + 23.8 = 199.8 mm

When Tm = 0.05 s, Ts = 0.01 s, and d = 14 mm:
S = 2,000 mm/s x (0.05 s + 0.01 s) + 8 x (14 mm - 14 mm)
= 120 mm . . . Eq. (2)
If the result is less than 100 mm, use S = 100 mm.

Safety Light Curtain (Type 4) F3SJ

S = K x (Ts + Tc + Tr + Tbm) + Dpf

Tbm = 0.1 - 0.06 = 0.04 s

[Calculation example]

60

If a person approaches the detection zone of the F3SJ
perpendicularly, calculate the safety distance as shown below.

Ver. 2

Distance from Glossy Surface

Prevention of Mutual Interference

!WARNING
Install the sensor system so that it is not affected by reflection from a
glossy surface. Failure to do so may hinder detection, resulting in
serious injury.
Install the sensor system at distance D or further from highly
reflective surfaces such as metallic walls, floors, ceilings, or
workpieces, as shown below.

When using more than 1 set of F3SJ, install them so that
mutual interference does not occur, such as by
configuring series connections or using physical barriers
between adjacent sets.
Mutual interference from other F3SJ is prevented in up to 3 sets
without series connection.

Reflective ceiling

For series connection

D

Emitter

Do not use a sensor system in a reflective configuration.
Doing so may hinder detection.
Mirrors can be used change the optical route.

Receiver

Detection zone
L

Series connections can prevent mutual interference when multiple
sensors are used. Up to 4 sets, 400 beams, can be connected
(except for the F3SJ-A@-TS Series, for which up to 3 sets,
240 beams, can be connected). The emission of series-connected
F3SJ is time-divided, so mutual interference does not occur and
safety is ensured.
Emitter 1

Receiver 1

F39-JJR3W,
F39-JJR15L, or
F39-JJR06L
Connecting
Cable
Emitter 2

Receiver 2

Emitter 3

Receiver 3

Emitter 4

Receiver 4

D

Reflective floor

Reflective surface

Emitter

D
5°

5°

Receiver

L
Distance between emitter and
receiver (Detection Distance L)

Allowable installation
distance D

For 0.2 to 3 m

0.13 m

For 3 m or more

L/2 x tan5° = L x 0.044 (m)

For no series connection
An interference light prevention algorithm prevents mutual
interference in up to 3 unconnected sets. If 4 or more sets of F3SJ
are installed and are not connected to each other, arrange them so
that mutual interference does not occur. If 2 sets are installed near
each other, reflection from the surface of the F3SJ may cause mutual
interference. When mutual interference occurs, the F3SJ enters
lockout. Combining countermeasures 1 to 3 below is effective.
1. Install a physical barrier
Emitter 1

Receiver 1

Safety Light Curtain (Type 4)

Emitter 2

Receiver 2

F3SJ Ver. 2

61

2. Alternate the direction of emission (alternation)
Aligned vertically

Aligned horizontally
Receiver 1

Emitter 1

Emitter 2

4. Keep sufficient distance between them

Receiver 2

Emitter 1

Emitter

Receiver

Receiver 1

Emitter

Receiver
5°

D
Emitter

Receiver 2

D
Receiver

Emitter

5°

Emitter 2

L

Aligned fore and aft
Receiver 1

Receiver

Emitter 1

Emitter 2

Distance between emitter and
receiver (Detection Distance L)

Receiver 2

If sensors of 2 sets are installed too close to each other, mutual
interference may occur due to reflection by the surface.
This can be resolved by using a setting tool to shorten the detection
distance.

Allowable installation
distance D

For 0.2 to 3 m

0.26 m

For 3 m or more

L x tan5° = L x 0.088 (m)

The installations shown below may cause mutual interference.
When mutual interference occurs, the F3SJ enters lockout.

3. Shorten the detection distance (Must be set with a setting tool).
Before changing
Emitter

Receiver

Ambient light

Aligned horizontally
Emitter 1

Emitter

Receiver 1 Emitter 2

Aligned vertically
Receiver 2

Emitter 1

Receiver 1

Emitter 2

Receiver 2

Receiver

After changing
Emitter

Receiver
Ambient light
Aligned fore and aft
Emitter

62

Receiver

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Emitter 1

Receiver 1

Emitter 2

Receiver 2

Using Setting Tools
The following setting tools (sold separately) can be purchased in
order to change or confirm various F3SJ-series parameters.

F3SJ Versions

• F39-MC21 Setting Console
• F39-GWUM SD Manager Setting Support Software for the F3SJ

Setting tools can be used with Version 2 and later versions of the
F3SJ. The setting tools cannot be used with Version 1.
The setting tools cannot be used even if a Version 1 F3SJ is
combined in series with compatible F3SJ Units. (A communications
error lockout will occur.)

The Setting Console cannot be used with the F3SJ-A@-TS Series.

!WARNING

Unfortunately, the F3SJ's version cannot be upgraded.

The FS3J must be installed, set, and integrated into the mechanical
control system by a qualified technician who has received the
appropriate training. Failure to make correct settings may prevent
detection of people and result in serious injury.

The F3SJ's version number appears on its label, as shown in the
following diagram.
Location of the F3SJ's Version Number (Within Dashed-line Box)
Emitter

Receiver

Close-up View of Dashed-line Box
Serial No. :
Year :

A
B

Version : C
OMRON Corporation Kyoto, JAPAN

A: Serial number
B: Year of manufacture
C: F3SJ's version number (Verify that the version is Version 2 or later.)

Functions Editable with Setting Tools
❍: Can be used.

×: Cannot be used.
Function or monitored item

F39-MC21 Setting Console F39-GWUM SD Manager Setting
Support Software for the F3SJ

Fixed blanking function (See note 1.)

❍

❍

Floating braking function (See note 1.)

❍

❍

Warning zone function (See note 1.)

❍

❍

Muting function (See note 2.)
(when using the muting system)

❍

❍

Override function (See note 2.)
(when using the muting system)

❍

❍

Auxiliary output (See note 2.)

❍

❍

Specified light beam output function (See note 1.)

×

❍

External indicator output (See note 2.)

❍

❍

Interlock function (See note 2.)

❍

❍

External device monitoring function (See note 2.)

❍

❍

Changing detection Change detection distance function (See note 1.)
distance

❍

❍

Monitoring
operation

Light intensity indicators (See note 1.)

❍

❍

Ambient light intensity indicators (See note 1.)

❍

❍

Status indicators (See note 1.)

×

❍

Error log (See note 1.)

❍

❍

Power ON time (See note 1.)

❍

❍

Number of load switching operations (See note 1.)

❍

❍

Recovering
settings

Recover settings function (See note 1.)

❍

❍

Other functions

Safety distance calculation function (See note 1.)

×

❍

Power cable length calculation Function (See note 1.)

×

❍

Rated response time check (See note 1.)

❍

❍

Settings for
individual
applications

Indicator and I/O
settings

Maintenance
information

Note: 1. These functions were newly added in Version 2. A setting tool can be used to enable these functions or read the function settings.
2. These functions can be used even without a setting tool. A setting tool can be used to make more detailed settings.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

63

Two Kinds of Setting Tools
The following accessories (sold separately) can be purchased in
order to use various F3SJ-series functions and change settings.
• F39-MC21 Setting Console
A Setting Console can easily make settings onsite.
• F39-GWUM SD Manager Setting Support Software for the F3SJ
With this software, a personal computer can be connected to make
settings. The SD Manager Setting Support Software for the F3SJ
can make more detailed settings than the Setting Console.

Setting Console
The following items are included with the F39-MC21 Setting
Console.
•
•
•
•
•
•

Setting Console
Branch Connector (with Connector Cap)
Special Cable
Special Cable with Plug
Error Mode Label
Instruction Manual

SD Manager Setting Support Software
for the F3SJ
The following items are included with the F39-GWUM SD Manager
Setting Support Software for the F3SJ.
• CD-ROM (SD Manager Setting Support Software for the F3SJ,
Communications Unit Driver)
• Communications Unit
• Branch Connector (with Connector Cap)
• Special Cable
• Instruction Manual (Installation Guide)
• Special Cable with Plug
The F3SJ's operating status can be checked and its parameters can
be changed in the SD Manager Setting Support Software for the
F3SJ.

Connecting the SD Manager Setting Support Software

Connecting the Setting Console
Connect the F3SJ to the Setting Console as shown in the following
diagram. The Branch Connector can be used on either the emitter
side or receiver side. After the F3SJ has been wired, turn ON the
power and change parameters as required. If it is not possible to
connect a branch connector because the connector is concealed by
equipment or otherwise inaccessible, use the Special Cable with
Plug to connect to the + and − communications lines. For details,
refer to the F39-MC21 Instruction Manual.

Connect the F3SJ, Communications Unit, and personal computer as
shown in the following diagram. The branch connector can be used
on either the emitter side or receiver side. After the F3SJ has been
wired, turn ON the power and start the Setting Support Software. If it
is not possible to connect a branch connector because the connector
is concealed by equipment or otherwise inaccessible, use the
Special Cable with Plug to connect to the + and - communications
lines. For details, refer to the SD Manager's Help function.

F39-GWUM SD Manager Setting
Support Software for the F3SJ
(Accessory, sold separately)
F39-MC21 Setting Console
(Accessory, sold separately)

PC

64

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Applications Supported by the Setting Tools
Fixed Blanking Function

Floating Blanking Function

Summary

Summary

Disables specific F3SJ light beams.

Increases the diameter of the F3SJ's smallest detectable object and
turns OFF the control output when multiple objects are detected.

!WARNING
When the fixed blanking function is used to disable detection in an
area, install blocking structures or shielding to prevent passage into
the entire hazardous area where detection has been disabled.
Failure to do so may prevent detection of people and result in serious
injury.
When an allowable range of light beams has been set for fixed
blanking, the size of the smallest detectable object will be larger in the
vicinity of interrupting objects. Calculate the safety distance to match
the settings.
After setting the fixed blanking function, you must verify that the F3SJ
detects a test rod at any position in the entire area where intrusion
must be detected. Failure to do so may prevent detection of people
and result in serious injury.

Example Application
In this example, there is always an object such as a conveyor belt in
the detection area, and we want to ignore the conveyor belt.

Description of Functions

!WARNING
When the floating blanking function is used, it increases the diameter
of the F3SJ's smallest detectable object. Always use the larger
diameter when calculating the safety distance. If the incorrect
diameter is used in the calculation, the machinery may fail to stop
before an operator reaches the hazardous area, resulting in serious
injury.
After setting the floating blanking function, always verify that the F3SJ
system operates as expected. Serious injury may result if an
individual is not detected.

Example Application
When there is a moving object with a fixed width in the detection area
that we do not want to detect, the detection function can be disabled.

Description of Functions

Floating Blanking Function
This function increases the diameter of the smallest detectable
object to allow passage of objects of a certain size or allow
interrupting objects in multiple locations.

Fixed Blanking Function
This function disables part of the F3SJ's detection area and
maintains the control output's ON status even if there is an object in
the disabled area.
The light beams set for fixed blanking must be one area of
consecutive light beams and up to five areas can be set (areas 1 to
5). Fixed blanking cannot be set for all of the light beams.

Setting the Fixed Blanking Area
Set the area that will be subject to fixed blanking.

Setting the Floating Blanking Area
When the Setting Console is being used, all of the light beams are
set as the floating blanking area. When the SD Manager Setting
Support Software is being used, just one area can be set but the
range of the area can be specified. In the following example, the
floating blanking area is set from the 5th light beam to the 10th light
beam (counting from the bottom). An interrupting object can be
placed in the detection area to perform teaching and specify light
beams for manual settings.

An interrupting object can be placed in the detection area to perform
teaching and specify light beams for manual settings.
Higher

Higher

Higher

Higher
Light beam #10
Floating blanking area
Light beam #5

Light beam #10
Fixed blanking area
Light beam #5

Lower

Lower

Lower

Lower

Floating Light Beams
Note: 1. When the Setting Console is being used, only one area can
be set as a fixed blanking area.
2. When the SD Manager Setting Support Software is being
used, up to five areas can be set as fixed blanking areas.

The following charts show the relationship between the number of
floating light beams and the safety output operation (safety output
not going OFF). Measure the size of the interrupting object
(maximum diameter) and set the number of floating light beams so
that the object's size is less than the corresponding dimension shown
in the chart.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

65

Example Setting

Floating Blanking Mode

When an F3SJ-A@14 is being used with an interrupting object that is
20 mm in diameter, set three light beams as floating light beams.
With this setting, the F3SJ's safety output will not turn OFF even if
there is an interrupting object up to 22-mm wide in the floating
blanking area.

The floating blanking function has two operation modes.

Effective Range vs. Number of Floating Light Beams
F3SJ-A@14 Series
Permitted Floating Range
4

Settable Range

Example Setting Size

With 1 floating light beam
13
With 2 floating light beams

22
With 3 floating light beams
31
With 4 floating light beams
0

10

20
30
Size of Interrupting Object (mm)

40

F3SJ-A@20 Series
Permitted Floating Range
10

Settable Range

With 1 floating light beam
25
With 2 floating light beams
40
With 3 floating light beams

55
With 4 floating light beams
0

10

20
30
40
Size of Interrupting Object (mm)

50

60

F3SJ-A@30 Series
Permitted Floating Range
20

Settable Range

With 1 floating light beam
45
With 2 floating light beams
70
With 3 floating light beams

95
With 4 floating light beams
0

20

40
60
Size of Interrupting Object (mm)

80

100

F3SJ-A@55 series
Permitted Floating Range
45

Settable Range

With 1 floating light beam
95
With 2 floating light beams
145
With 3 floating light beams

195
With 4 floating light beams
0

66

40

80
120
Size of Interrupting Object (mm)

160

Safety Light Curtain (Type 4) F3SJ

200

Ver. 2

1. Continuous Light Beam Mode
The safety output will not go OFF if the interrupting object is
smaller than the set size, although the safety output will go OFF if
objects pass through several areas in the detection area.
The floating blanking monitor function can be set in this mode.
Refer to the User's Manual for details.
2. Discontinuous Light Beam Mode
A light blockage is detected when the number of light beams
blocked in the area is equal to or greater than the preset number
of light beams.

Warning Zone Function

Figure 3

Upper

Summary
The detection zone can be divided into the detection zone and a
warning zone.

!WARNING
The warning zone output is not a safety output. Do not include this
area in the safety distance calculation. Shortening the safety distance
may result in serious injury.

Detection
zone
All light
beams

2CH

The warning zone cannot be used for safety purposes. Always install
the system so that the hazard is reached by passing through the
detection zone.
The warning zone function can be
used only when the F3SJ is
installed horizontally. This function
cannot be used when the F3SJ is
installed vertically.

Warning zone
All light beams

Lower
1CH

Upper
Hazardous
area

Detection zone

Warning zone

Lower

Examples of Unacceptable Warning Zone Settings
(Figures 4 and 5)
Figure 4

All light beams
Warning zone

Example Application
When an individual enters, a warning lamp lights or buzzer sounds
without stopping the equipment.

Upper

Description of Function

Figure 5

Lower

Detection zone Warning zone

Warning Zone Function
Use teaching to set the light beams that you want to set as the
warning zone or manually specify the light beams from the lowest or
highest beam. (See figures 1 and 2.)
To indicate that the warning zone is blocked, allocate the auxiliary
output or external indicator output as the warning zone information.
The following settings cannot be made:
• Setting all light beams as the warning zone (figure 4)
• Setting a warning zone that does not include one of the outer light
beams (figure 5)

Detection zone

Upper

Lower

Warning Zone Display Label
When the warning zone is set, affix this label to indicate which areas
belong to the normal detection zone and the warning zone.
Normal light beam

Warning light beam

If Safety Light Curtains are connected in series, and at least one of
an F3SJ's light beams is a normal light beam, all of a Light Curtain's
light beams can be set as a warning zone (figure 3).

Example Warning Zone Settings (Figures 1 to 3)

DETECTION
ZONE

WARNING
ZONE

Figure 1
Warning zone
6 upper light beams

Detection zone

Detection zone

Warning zone

Lower

Upper

Figure 2
Detection zone

Upper

Warning zone
4 lower light beams

Lower

Safety Light Curtain (Type 4)

F3SJ Ver. 2

67

Muting Function

Example Applications
• Allowing only work pieces to pass into the conveyor entrance
• Operating the muting function in a specific area only
• Setting a different muting mode when standard muting is not
appropriate for the application

Summary
Makes settings related to the muting function.

!WARNING

Description of Functions (See User's Manual for details.)

The muting function disables the safety functions of the device.
Additional safety measures must be taken to ensure safety while this
function is working.
Install muting sensors so that they can distinguish between the object
that is being allowed to be pass through the detection zone and a
person.
Muting lamps (external indicators) that indicate the status of the
muting function must be installed where they are clearly visible to
workers from all the operating positions.
Muting times must be precisely set according to the application by
qualified personnel who have received appropriate training. In
particular, if the muting time limit is to be set to infinity, the person who
makes the setting must bear responsibility.
Use two independent input devices for the muting inputs. (For the
PNP output-type F3SJ, use a sensor with a PNP transistor output or
N.O. contact. For the NPN output-type F3SJ, use a sensor with an
NPN transistor output or N.O. type contact.)
To prevent a worker from entering the hazardous area while the
muting function is engaged, install the F3SJ, muting sensor, and then
a protective barrier and set a limited muting time.

Operation Modes
When the SD Manager Setting Support Software is being used, any
one of the following three operation modes can be selected for the
muting function.
1. Standard Muting Mode
This is the default operation mode, which is set when the F3SJ is
shipped from the factory.
The muting function is enabled by turning ON muting inputs 1 and
2 with a time lag.
Note: Settings such as the muting time limit value can be changed.
2. Specialized Exit Muting Mode (Can be set with the SD Manager
Setting Support Software only.)
The muting function is enabled by turning ON muting inputs 1 and
2 with a time lag.
Installation of the muting input sensors is simpler than standard
mode because the Safety Light Curtain's blocked light status is
used to end muting.
3. Position Detection Muting Mode (Can be set with the SD Manager
Setting Support Software only.)
Sensors such as limit switches are used for the muting inputs and
the muting function is enabled by turning muting input from OFF
to ON and then turning muting input 2 from ON to OFF within time
difference T1 max. Use hybrid redundant inputs such as a
combination of an N.O. contact input and an N.C. contact input.
(When using a PNP-output photoelectric switch, use L/ON
operation on one side and D/ON operation on the other side.)
This mode is useful when you want to disable the F3SJ
temporarily, such as when a person is placing an object at the
conveyor entrance.

Partial Muting (Muting area) Settings
The light beams controlled by the muting function can be specified
with a setting tool. (When the F3SJ is shipped, all light beams are
set.)
The light beams can be specified by teaching/recording the blocked
light beams as muting light beams or manually specifying the desired
light beams.

68

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Indicator and I/O Settings
Auxiliary Output (Non-safety) and External Indicator Output (Non-safety)
Summary
A setting tool can be used to change the allocation of auxiliary
outputs 1 and 2, and external indicator outputs 1 and 2.

!WARNING
Do not use the auxiliary outputs or external indicator outputs for
safety purposes. Serious injury may result if an output fails and a
person is not detected.

Example Applications
• Allocating a lockout output or warning zone output to an auxiliary
output
• Connecting an external indicator to an auxiliary output and making
it flash
An auxiliary output or external indicator output can be connected to
an incandescent light to function as a broken-wire or short-circuit
detector. Refer to the User's Manual for details.

Output Operation Modes (when allocated to an auxiliary output or external indicator output)
Output operation mode

Description of operation
(Output will go ON in the following situation.)

Setting Console

SD Manager Setting
Support Software

Control output

The control output is ON

❍

❍

Light intensity diagnosis (See note 1.)

The F3SJ is ON and the received light intensity ❍
is 100% to 130% of the threshold value for more
than 10 seconds.

❍

Error/Lockout

The F3SJ is in error or lockout status.

❍

❍

Muting/Override

The F3SJ is in muting or override status.

❍

❍

Blanking/Warning Zone (See note 2.)

The fixed blanking, floating blanking, or warning ❍
zone function is enabled.

❍

Specified light beam output (See note 3.) A specified light beam is blocked.
Power ON time

×

❍

The power ON time has exceeded the threshold ❍
value.

❍
❍

Warning zone (See note 4.)

Light is blocked in the warning zone.

❍

Test input ON

The test input went ON.

❍

❍

Blanking light beam incident light

A fixed or floating light beam is receiving incident ❍
light.

❍

Interlock

The F3SJ is in interlock status.

❍

❍

Muting error

The F3SJ is in muting error status.

❍

❍

Number of load switching operations
exceeded

The number of load switching operations
exceeded the threshold value.

❍

❍

Information trigger

An interlock, lockout, or muting error has
occurred.

×

❍

Individual linked sensor output (channel Channel 1 control output is ON when Units are
1)
linked in series.

❍ (Auxiliary output 1 only) ❍ (Auxiliary output 1 only)

Individual linked sensor output (channel Channel 2 control output is ON when Units are
2)
linked in series.

❍ (Auxiliary output 1 only) ❍ (Auxiliary output 1 only)

Individual linked sensor output (channel Channel 3 control output is ON when Units are
3)
linked in series.

❍ (Auxiliary output 1 only) ❍ (Auxiliary output 1 only)

Individual linked sensor output (channel Channel 4 control output is ON when Units are
4)
linked in series.

❍ (Auxiliary output 1 only) ❍ (Auxiliary output 1 only)

Note: 1. A light blockage was detected even though the output is not turned OFF because the blockage occurred at a light beam subject to fixed
blanking, floating blanking, or muting. Blockages are also not processed during overrides.
2. The fixed blanking light beams or floating blanking light beams must be set.
3. The specified light beam must be set.
4. The warning zone light beams must be set.
5. When "specified light beam output" is allocated as the output operation mode for auxiliary output 1 or 2 or external indicator output 1 or
2, that mode cannot be allocated to the other output operations.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

69

Changing the Detection Distance
Change detection distance function
Summary
The F3SJ's detection distance can be shortened.

Example Application
The F3SJ's detection distance can be shortened to avoid affecting
other photoelectric sensors.
When devices are installed close together, shortening the detection
distance can reduce mutual interference.

Description of Function
The detection distance can be set to 0.5 m, 1 m, 2 m, 3 m, 5 m, or
MAX (either 7 m or 9 m).
The most suitable detection distance can be set to match the
installation distance.
Note: MAX represents the rated detection distance.

Monitoring Operation
Received Light Intensity Indicator

Ambient Light Intensity Indicator

Summary

Summary

It is possible to read the F3SJ's received light intensity.

It is possible to read the intensity of the light received by the F3SJ
from ambient sources, such as other photoelectric sensors.

Example Application
Adjust the light beams while checking the F3SJ's received light
intensity.

Example Application

Description of Function

Display the ambient light level while taking steps to reduce light
interference form sources such as photoelectric switches in the area
and neighboring F3SJ Units.

Indicates the F3SJ's received light intensity.

Description of Function

The F3SJ's received light intensity level can be checked with a
setting tool.

Indicates the ambient light level at the F3SJ from other light sources
such as photoelectric sensors.
This function can help identify the photoelectric sensors that are the
source of the light interference and identify the light beams being
affected by the ambient light.

Other Functions
The F3SJ is also equipped with the following functions.
Refer to the User's Manual for details on using these functions.
•
•
•
•
•
•
•

Status indicators
Error log
Power ON time
Number of load switching operations
Safety distance calculation function
Power cable length calculation function
Rated response time check function

70

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Dimensions
Note: All units are in millimeters unless otherwise indicated.

■ Main Units
When Using Standard Mounting Brackets
Backside mounting

Top/bottom mounting bracket

Intermediate mounting bracket

2-Top/bottom mounting brackets
5.5

2-Mounting holes

Mounting screw holes

30
20
(13.75)

4-M5
20

16.5
1

3.75
6.25

30
24

31
22
7

Intermediate mounting
bracket

22
2-M5

5.5
B
D

53

A
B

42

42

C (Protective
height)
2-Mounting holes

Beam

10

E

4-Mounting holes

37

300
6 dia.

13.75

6.5 dia.
2-Mounting holes

43

15 dia.

E

9 dia.

C (protective height): 4-digit number in the table
A = C + 74, B = C + 46.5
D = C - 20, E = See table below.
Protective height Number of intermediate brackets E (See note.)

M12 Waterproof connector

26
46

0245 to 0596

0

---

0600 to 1130

1

E=B/2

1136 to 1658

2

E=B/3

1660 to 2180

3

E=B/4

2195 to 2500

4

E=B/5

Note: Use E = 530 or less when none of the E values shown
above are used.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

71

Side mounting
Mounting screw holes
2-Top/bottom
mounting brackets

30
20

2-Mounting holes

5.5

35

(13.75)

4-M5

20

30

16.5
3.75
6.25

24

5.5
31
B

15

B

15

A
D

53
11

C (Protective height)
36
43

2-M5
31
Beam

E

E
5

10
4-Mounting
holes

10
37

300
6 dia.

13.75
6.5 dia.
2-Mounting holes

43

9 dia.

M12 Waterproof connector

C (protective height): 4-digit number in the table
A = C + 74, B = C + 46.5
D = C - 20, E = See table below.
51

Protective height Number of intermediate brackets E (See note.)
53

0245 to 0596

0

---

0600 to 1130

1

E=B/2

1136 to 1658

2

E=B/3

1660 to 2180

3

E=B/4

2195 to 2500

4

E=B/5

Note: Use E = 530 or less when none of the E values shown
above are used.

F39-LJ1 Detailed Dimensions of Bracket
13.5
11.5

A
16
10

9 dia.
A

9

19.6

12 dia.
A-A

30
9 dia.

Material: Brass

2

5.5

6.5 dia.

16.5

8

18 36.5
5.6

14.5
2-M3
Through holes

11
21

5.5

30
21

19.6

.

.5

dia

3
2-

10
Material: Stainless steel

72

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Material: Stainless steel

Using Side Flat Mounting Bracket (F39-LJ2)
F39-LJ2
Material: Stainless steel
Use standard brackets

5.5

(17.25)

37.6
20

Mounting screw holes
27

35
4-M5

25.5

A

C (Protective height)

B

B

5
19
0.3
37
9.7

20

17.25 6.5 dia.
9 dia.

Dimensions A to C
44

35
2

A

C + 74

B

C + 39.5

C

4-digit number of the model
name (protective height)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

73

Using Free Location Mounting Bracket (F39-LJ3)
Backside mounting

Mounting screw holes

31
22

1

6-M5

F39-LJ3

45

Material: Zinc die-cast
42

7

5.5

B C (Protective
height)

B

42

16

F

F

53

42

42
45

24

25

46

Side mounting
43
36

F39-LJ3

Mounting screw holes

Material: Zinc die-cast/stainless
6-M5

45
11

15
5.5

C (Protective
height)

B

B
15

F
16

F

5

15
53
45

51

30
2
24

5

43

74

Safety Light Curtain (Type 4) F3SJ

Ver. 2

15

Dimensions B, C, and F

Dimension F

B

C - 90

C

4-digit number of the model name (protective height)

Protective height

F

Depends on the protective height. See the table on the
right.

Number of intermediate
mounting brackets

F
(See note.)

0245 to 0440

2

---

0443 to 0785

3

B/2

0794 to 1140

4

B/3

1145 to 1490

5

B/4

1495 to 1840

6

B/5

1845 to 2180

7

B/6

2195 to 2500

8

B/7

Note: Use F = 350 or less when none of the F values shown above
are used.
When only F39-LJ3 free-location mounting brackets are used without standard brackets, allow a space of at least 350 mm between the brackets.
The number of brackets required varies according to the protective height. For details about the number of required brackets, refer to the table
below.
The standard included intermediate mounting brackets are the same as the F39-LJ3 free-location mounting brackets. Purchase brackets as
necessary if there are fewer intermediate mounting brackets than required. When intermediate mounting brackets are included, they can be used
as free-location mounting brackets.

Required number of F39-LJ3 free-location mounting brackets for 1 F3SJ set (emitter/receiver) (2 pieces are included with
F39-LJ3)
Protective height

Number of included free location
brackets as intermediate brackets

Number of free location
brackets to mount F3SJ

Number of free location
brackets to be purchased

0245 to 0440

0

4

2 sets

0443 to 0596

0

6

3 sets

0600 to 0785

2

6

2 sets

0794 to 1130

2

8

3 sets

1136 to 1140

4

8

2 sets

1145 to 1490

4

10

3 sets

1495 to 1658

4

12

4 sets

1660 to 1840

6

12

3 sets

1845 to 2180

6

14

4 sets

2195 to 2500

8

16

4 sets

Using Top/Bottom Mounting Bracket B (F39-LJ4)
Mounting screw holes

30
19

Backside mounting
F39-LJ4
Material: Stainless steel

6

6

2

4-M5

(21.5)

37

Use standard
brackets
1

A B

C (Protective height)

45

19 (See note.)

21.5

Dimensions A to C
A

C + 109

B

C + 66

C

4-digit number of the model name (protective height)

B

Note: Using M5 bolt, available range for
mounting is 18 to 20.

30
26

Note: Refer to the User's Manual (Cat. No. SCHG-718 and SCHG-719) for the dimensions for side mounting.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

75

Using Mounting Bracket for Short-length F3SN (F39-LJ5)
Mounting screw holes

30
20

Inward-facing mounting
F39-LJ5
Material: Stainless steel

Use standard
brackets

5.5

5.5

4-M5
(16.5)
6.5 dia.
9 dia.

2

B A

C (Protective height)

B

19.9
32

21

11.5

16.5

20

Dimensions A to C
A
44.9

C + 23

B

C − 10

C

4-digit number of the model
name (protective height)

30
30
20

Outward-facing mounting

5.5

2

Mounting screw holes
5.5
4-M5

Use standard
brackets

F39-LJ5
Material: Stainless steel

21

(15.5)

B A

C (Protective height)

B

6.5 dia.
32

5.8
4.2

15.5
9 dia.

20

19.9

Dimensions A to C
A
44
30

76

Safety Light Curtain (Type 4) F3SJ

Ver. 2

C + 65

B

C + 34

C

4-digit number of the model
name (protective height)

Inward + outward-facing mounting

30
20
5.5

Use standard F39-LJ5
Material: Stainless steel
brackets

Mounting screw holes
5.5
4-M5

(11.5)
21

(16.5)

2

C (Protective height)
B

B A

6.5 dia.
32.5

5.8

32

4.2

15.5
9 dia.

20

19.9

Dimensions A to C
A
44

C + 44

B

C + 12

C

4-digit number of the model
name (protective height)

30

F3SN replacement correspondence table (F3SN mounting holes can be used without modification)
When replacing F3SN-@@@@P(N)14 with F3SJ-A@@@@P(N)14
F3SN
Model

Replacement F3SJ
Protective height

Model

Replacement method using
F39-LJ5

Protective height

F3SN-@0153P(N)14

153

---

---

---

F3SN-@0180P(N)14

180

F3SJ-A0245P(N)14

245

Inward-facing mounting

F3SN-@0189P(N)14

189

F3SJ-A0245P(N)14

245

Inward-facing mounting

F3SN-@0198P(N)14

198

F3SJ-A0245P(N)14

245

Inward + outward-facing mounting

F3SN-@0207P(N)14

207

F3SJ-A0245P(N)14

245

Inward + outward-facing mounting

F3SN-@0216P(N)14

216

F3SJ-A0245P(N)14

245

Outward-facing mounting

F3SN-@0225P(N)14

225

F3SJ-A0245P(N)14

245

Outward-facing mounting

For length greater than F3SN-@0234P(N)14:
Add 11 to the F3SN's 4-digit number and apply it as the F3SJ's 4-digit number, and then replace with the standard brackets included with the
product.
[Selection example] F3SN-A0315P(N)14 becomes F3SJ-A0326P(N)14 (replace with standard brackets)
Note: 1. The protective height becomes 11 mm longer.
2. Replace with outward-facing mounting of F39-LJ5 when you want to set the detection surface height to be same as the F3SN.
However, the F39-LJ5 and intermediate mounting brackets cannot be mounted simultaneously, so set the protective height to 600 mm or
less.
When replacing F3SN-@@@@P (N)25 with F3SJ-A@@@@P (N)20
F3SN
Model

Replacement F3SJ
Protective height

Model

Protective height

Replacement method using
F39-LJ5

F3SN-@0187P(N)25

187

---

---

---

F3SN-@0217P(N)25

217

F3SJ-A0260P(N)20

260

Inward-facing mounting

F3SN-@0232P(N)25

232

F3SJ-A0260P(N)20

260

Inward + outward-facing mounting

F3SN-@0247P(N)25

247

F3SJ-A0245P(N)20

245

Outward-facing mounting

For length greater than F3SN-@0262P(N)25:
Subtract 17 from the F3SN's 4-digit number and apply it as the F3SJ's 4-digit number, and then replace with the standard brackets included with
the product.
[Selection example] F3SN-A0322P(N)25 becomes F3SJ-A0305P(N)20 (replace with standard brackets)
Note: 1. The protective height gets 17 mm shorter.
2. Replace with outward-facing mounting of F39-LJ5 when you want to set the detection surface height to be same as the F3SN.
However, the F39-LJ5 and intermediate mounting brackets cannot be mounted simultaneously, so set the protective height to 600 mm or
less.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

77

Using Space-saving Mounting Bracket (F39-LJ8)
Backside mounting
30
20

F39-LJ8
Material: Stainless steel
5.5

Use standard brackets

Mounting screw holes

5.5

4-M5
(16.65)
7
2

C (Protective height)

B

A

B

8

25.65

16.65

11.5

20

Dimensions A to C
A

C + 23

B

C − 10.3

C

4-digit number of the model
name (protective height)

Note: Because the F39-LJ8 cannot be mounted together with an
intermediate bracket, keep the protective height at 600 mm max.

33

Mounting Bracket (F39-LJ9) Used when Replacing an F3W-C.
Backside mounting
F39-LJ9
Material: Stainless steel

Mounting screw holes

30
16
3

Use standard brackets

6

2

6

4-M5

8

10
33

1

C
(Protective
B
height)

Dimensions A to C

B

A

69.3
28

A

C + 102.3

B

C + 77.3

C

4-digit number of the model
name (protective height)

78

(17)

16

3

Safety Light Curtain (Type 4) F3SJ

26

Ver. 2

Note: Refer to the User's Manual (Cat. No. SCHG-718 and SCHG719) for the dimensions for side mounting.

F3W-C replacement correspondence table (F3W-C mounting holes can be used without modification)
When replacing F3W-C@@@ with F3SJ-A@@@@@30
F3W-C
Model

Replacement F3SJ
Protective height

Model

Protective height

F3W-C044

120

---

---

F3W-C084

280

F3SJ-A0320@30

320

F3W-C124

440

F3SJ-A0470@30

470

F3W-C164

600

F3SJ-A0620@30 (See note.)

620

F3W-C204

760

F3SJ-A0795@30 (See note.)

795

F3W-C244

920

F3SJ-A0945@30 (See note.)

945

Note: New holes must be drilled for the intermediate bracket.

Using Top/Bottom Mounting Bracket C (F39-LJ11)
F39-LJ11
Material: Stainless steel

30
13

26
2

Use standard brackets

Mounting screw holes

6
3

4-M5
(20)

34
(54.5)
1

B

C (Protective height)

A

B

54.5
20

Dimensions A to C
A

13
4-Mounting holes

C + 109

B

C + 69

C

4-digit number of the model
name (protective height)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

79

■ Accessories
Single-end Connector Cable
F39-JC3A (L = 3 m)
F39-JC7A (L = 7 m)

F39-JC10A (L = 10 m)
F39-JC15A (L = 15 m)
F39-JC20A (L = 20 m)
39.5

L (See note.)

15 dia.

Waterproof connector

Color: Emitter (gray)
Receiver (black)

Insulated vinyl round cable 6.6 dia. with braided shield
8-wire (4-pair) (Cross section of conductor: 0.3 mm2/insulator diameter: 1.15 mm)
Standard length L

Note: Cables with L=3, 7, 10, 15, and 20 m are available.

Cables with Connectors on Both Ends
F39-JCR5B (L = 0.5 m)
F39-JC1B (L = 1 m)
F39-JC3B (L = 3 m)
F39-JC5B (L = 5 m)

F39-JC7B (L = 7 m)
F39-JC10B (L = 10 m)
F39-JC15B (L = 15 m)
F39-JC20B (L = 20 m)
39.5

L

43

15 dia.

15 dia.
Waterproof connector

Waterproof connector

Vinyl-insulated round cable: 6.6 dia. with braided shield
8-wire (4-pair) (Cross section of conductor: 0.3 mm2/ Insulator diameter: 1.15 mm)
Standard length L

Color: Emitter (gray)
Receiver (black)

Control Unit

Emitter

F3SP-B1P
Receiver
91

24-M3

10.5

Mounting screw holes

5.9
7×5=35

2-4.2 dia. or M4

4.6 dia.
13 max.

9

76 max. 63

84±0.3

43

5.6
9
45 max.

80

Safety Light Curtain (Type 4) F3SJ

R2.3

Ver. 2

5
111 max.

35±0.3

Dedicated External Indicator Set
54
30 dia.

F39-A01@-PAC

20
173

90

9 dia.
6.5 dia.
18

16

2

6

6
19
34

32

Material: Stainless steel

Spatter Protection Cover
F39-HJ@@@@

Assembled dimensions

32

32

10

Four digits in the model number (protective height) − 10

29.5

Material: polycarbonate (for the protective cover)

Safety Light Curtain (Type 4)

F3SJ Ver. 2

81

Setting Support Software for the F3SJ
F39-GWUM
(625.7)
(46)

67.9

(11.8)

(12) (16)

35.8

Insulated vinyl round cable 4.6 dia.
Standard length: 0.5 m
3.6
17.8

(8)

0.7

(4.5)

Setting Console
Communications jack

F39-MC21

52.8

22

Connection indicator
Function selection indicator
Channel indicator
Channel key
Mode indicator
Up cursor key

136
Right cursor key

Down cursor key

Left cursor key

Enter key

Delete key

50

82

Safety Light Curtain (Type 4) F3SJ

Ver. 2

Protective Bar
F39-PJ@@@@-S
Backside mounting

Mounting screw holes
24
9 dia.
6.5 dia.

30
20

3-M5 bolts with
hexagonal holes and
attached washers

Mounting bracket (2)
5.5

(13.75)

When using M6, M8

When using M5
20

2-M8

16.5

4-M5

(6)

3.75

6.25

(37)
1

2-M6

D
Sensor

5.5 dia.

16
8

D

D

10

23

39

43
B C (Protective
height)

39
B

A

B

M5

Mounting hole

M5

Intermediate
brackets
(3)

(37)
3.75

20
2-Mounting holes
2-Mounting holes

(13.75)

(6)

4-Mounting holes

Mounting
bracket (1)

4-M3 bolts with
hexagonal holes
and attached
washers

6.25

20

Protective support

C (protective height): 4-digit number in the table

15

A = C + 74, B = C + 46.5
64

Protective height
20
69

Number of intermediate
brackets used (3)

D

0245 to 0995

0

---

1001 to 2000

1

B/2

2009 to 2500

2

B/3

Note: For reference, D is the dimension that will not interfere with
the intermediate bracket on the Safety Light Curtain body.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

83

Side mounting

Mounting screw holes
30
20
5.5

9 dia.
6.5 dia.

24
4

Mounting bracket (2)

3-M5 bolts with
hexagonal holes and
attached washers

When using M6, M8

When using M5
20

(13.75)

16.5

2-M8
4-M5

(6)

3.75

6.25

(37)
5

2-M6

D

23

D

Intermediate
brackets (4)
for side
mounting
(See note.)

8

D

10 20
B

C (Protective
height)

B

B
M5

M5

5.5 dia.
36

39

39
A

Mounting hole

Sensor

(37)
(6)
2-Mounting holes
2-Mounting holes

20

(13.75)
4-Mounting holes

3.75
20

Protective support
4-M3 bolts with
hexagonal holes
and attached
washers

Mounting bracket (1)

Note: 2. The four intermediate brackets (F39-PJ-MS)
for side mounting are not provided.
69
20

32

15

64

C (protective height): 4-digit number in the table
A = C + 74, B = C + 46.5
Protective height

Number of protective
brackets used (4)

D

0245 to 0995

0

---

1001 to 2000

1

B/2

2009 to 2500

2

B/3

Note: 1. For reference, D is the dimension that will not interfere
with the intermediate bracket on the Safety Light Curtain
body.

84

Safety Light Curtain (Type 4) F3SJ

Ver. 2

6.25

Water-resistant Case
32

F39-EJ@@@@-L(D)
Backside mounting

Mounting screw holes
60.5 dia.
9 dia.
6.5 dia.
8

When using M5

20

When using M6, M8
2-M8

5.5

8

4-M5

(16)
13.5
2

2

2-M6

B
A

B

C
D
(Protective
height)

B

22
2

Dimensions A to D
A

32
16
20

C + 108

B

C + 76

C

4-digit number of the model
name (protective height)

D

C + 44

8
20

2-Mounting Brackets
(See note.)

Side mounting

Note: The Mounting Brackets (F39-EJ-R)
are sold separately.

32

Mounting screw holes
60.5 dia.
9 dia.
6.5 dia.
8

When using M5

20

When using M6, M8
2-M8

5.5

8

4-M5

(16)
13.5
2

2

2-M6

B
A

B

C
D
(Protective
height)

B

22
2

Dimensions A to D

32

16

20

8
20

A

C + 108

B

C + 76

C

4-digit number of the model
name (protective height)

D

C + 44

2-Mounting Brackets
(See note.)

Note: The Mounting Brackets (F39-EJ-S)
are sold separately.

Safety Light Curtain (Type 4)

F3SJ Ver. 2

85

86

Safety Light Curtain (Type 4) F3SJ

Ver. 2

READ AND UNDERSTAND THIS CATALOG
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions
or comments.

Warranty and Limitations of Liability
WARRANTY
OMRON’s exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if
specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT,
MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT
THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.

LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR
COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY,
NEGLIGENCE, OR STRICT LIABILITY.
In no event shall responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS
OMRON’S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND
NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.

Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the
customer’s application or use of the product.
At the customer’s request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply
to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end
product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all
possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles,
safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT
THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY RATED
AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.

Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the product may be changed without any notice. When in doubt, special model numbers may be assigned to fix
or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual
specifications of purchased products.

DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.

ERRORS AND OMISSIONS
The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical,
typographical, or proofreading errors, or omissions.

PERFORMANCE DATA
Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may
represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject
to the OMRON Warranty and Limitations of Liability.

PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user’s programming of a programmable product, or any consequence thereof.

Copyright and Copy Permission
COPYRIGHT AND COPY PERMISSION
This document shall not be copied for sales or promotions without permission.
This document is protected by copyright and is intended solely for use in conjunction with the product. Please notify us before copying or
reproducing this document in any manner, for any other purpose. If copying or transmitting this document to another, please copy or transmit it in
its entirety.

Safety Light Curtain (Type 4)
F3SJ Ver. 2

New Models for Body
Protection or Presence
Detection
OMRON Corporation
Industrial Automation Company
Safety Devices Division
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)75-344-7093/Fax: (81)75-344-8197

Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388

OMRON SCIENTIFIC TECHNOLOGIES INC.
6550 Dumbarton Circle Fremont,
CA 94555-3605 U.S.A.
Tel: (1)510-608-3400/Fax: (1)510-744-1442

Authorized Distributor:
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
239920 Singapore
Tel: (65)6835-3011/Fax: (65)6835-2711

OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Road (M),
Shanghai, 200120 China
Tel: (86)21-5037-2222/Fax: (86)21-5037-2200

Cat. No. F074-E1-06

Note: Specifications subject to change without notice.

Printed in Japan
0207-1M (0605) (H)



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Extract, Print high-res
Author                          : Factory Controls
Create Date                     : 2009:10:06 09:00:17+11:00
Modify Date                     : 2009:10:06 12:04:10+11:00
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Metadata Date                   : 2009:10:06 12:04:10+11:00
Format                          : application/pdf
Title                           : Omron F3SJ Safety Light Curtain Datasheet
Creator                         : Factory Controls
Document ID                     : uuid:93dd4fdb-8c4e-4c16-b6be-2f51be1aeaa5
Instance ID                     : uuid:670b30d8-f01f-473a-9cdf-ea8e1c80af97
Page Layout                     : OneColumn
Page Mode                       : UseOutlines
Page Count                      : 88
EXIF Metadata provided by EXIF.tools

Navigation menu