ENCLOSURES AND
JUNCTION BOXES
When one spark makes the difference
between a normal day and a big problem,
Appleton enclosures are an absolute
necessity. Designed to fully contain and
confine an explosive force within the
enclosure, they are strong enough to
withstand the effects of corrosion and time.

ENCLOSURES
AND JUNCTION
BOXES

Enclosures and Junction Boxes

Enclosures and Junction Boxes

Hazardous Location and Ordinary Location

Enclosures and Junction Boxes

Description

Page

Hazardous Location Conduit Outlet Boxes
GR and GRF Conduit Outlet Boxes

499

GRH Conduit Outlet Boxes

504

GRSS Conduit Outlet Boxes with Multiple Hubs

505

CPU Universal Conduit Outlet Boxes and Covers

506

CPU Universal Conduit Outlet Boxes and Covers

507

GRU Universal Conduit Outlet Boxes

508

GRUE Universal Conduit Outlet Boxes

509

GRUE Universal Conduit Outlet Boxes

510

GRJS Universal Conduit Outlet Box

512

GRJS Universal Conduit Outlet Boxes

513

GRJ Conduit Outlet Boxes

514

GRJ Conduit Outlet Boxes

515

GRUO with Multiple Hubs Conduit Outlet Boxes

516

GRUJ Conduit Outlet Boxes with Multiple Hubs

517

GRU Conduit Outlet Boxes with Union Hubs

518

GU Conduit Outlet Boxes

520

GR

GRF

GRH

GRSS

CPU

GRU/GRUE

GRJS

GRJ

GRUO

GRUJ

GRU

GU

BJE, JBEL and JBEP

PJB, JBEP and ECEP

SJB/JBES

JBES and ECES

JBDR

JBDA/JBDF – ECDA, ECDF

V
V
V
V

Hazardous Location Outlet Boxes — Cable
BJE Series Polycarbonate Junction Boxes

521

ATX JBEL and JBEP Series Polycarbonate and
Polyester Junction Boxes

523

ATX JBEP Series Pre-Drilled Fiberglass Reinforced
Polyester Junction Boxes

528

PJB Series Fiberglass Reinforced Polyester
Enclosures

536

ATX JBEP and ECEP Series Undrilled Fiberglass
Reinforced Polyester Enclosures

543

ATX SJB Series 316L Stainless Steel Junction Box

551

ATX JBES Series Pre-Drilled 316L Stainless Steel
Junction Boxes

557

ATX JBES and ECES Series 316L Stainless Steel
Enclosures

561

ATX JBDR Series Pre-Drilled Round Junction Boxes

571

ATX JBDA and JBDF – ECDA, ECDF and ACSEW
Series Customized Enclosures

574

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

497

Enclosures and Junction Boxes

Enclosures and Junction Boxes

Enclosures and Junction Boxes

Hazardous Location and Ordinary Location

Description

Page

Hazardous Location Junction Boxes: Explosionproof
GUBB, GUBBD and GUBBM Cast Junction Boxes

580

DER, GUB and GUBM Cast Junction Boxes

587

AGUB Instrument and Meter Enclosures

593

AJBEW Cast Junction Boxes

599

EXB Cast Iron Junction Boxes

606

DTX Series Junction Boxes

611

XP Series Junction Boxes

620

V
GUBB, GUBB. GUBBM,
DER, GUB and GUBM

AGUB

AJBEW

EXB

DTX

XP — V

V

Ordinary Location Junction Boxes
W Series Cast Boxes Options

623

• WYS Type Unflanged Junction or Pull Boxes

633

• WYL Type Overlapping Cover Boxes

635

• WYW Type Hinged Cover Boxes

637

• WYF Type Flat Flanged Boxes

639

• WYU Type Inside Flanged Recessed Cover Boxes

641

• WYR Outside Flanged Recessed Cover Boxes

642

• WYT Type Checkered Cover Sidewalk Boxes

644

• WYC Type Box with Hinged Door and Trim
Cabinet

645

• WY58E Type Checkered Cover Sidewalk Topping
Box

646

• WYNY Type Checkered Cover Roadway Topping
Box

647

WYS Type

WYL Type

WYT Type

WYW Type

WY58E Type

WYF Type

WYC Type

WYU Type

498

WYR Type

WYNY Type

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GR and GRF Conduit Outlet Boxes
Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw and O-Ring.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 4

Applications
Enclosures and Junction Boxes

•	
•	
•	
•	
•	

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

•	 GR boxes offers ten hub arrangements.
•	 GRF boxes have integral mounting flange.
•	 Malleable iron bodies have high tensile strength, ductility and
provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints
and ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Function as sealing fittings when used with sealing covers (see
NEC for restrictions).
•	 Internally threaded body with externally threaded cover.
•	 Covers have pry notches for bar or wrench.
•	 Accommodate sealing, dome, hub and union hub covers, and
canopies.
•	 Standard O-rings provide raintight fit. NEMA 3, 4.
•	 Internal ground screw standard.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

Standard Materials
•	 Body: malleable iron or copperfree (4/10 of 1% max.) aluminum
•	 Cover: copperfree (4/10 of 1% max.) aluminum

Standard Finishes
•	 Malleable iron bodies and covers: triple-coat — (1) zinc
electroplate, (2) chromate, and (3) epoxy powder coat
•	 Aluminum bodies and covers: epoxy powder coat

Options
•	 To order body without cover, add suffix -LC to catalog number.
•	 For malleable iron body and cover, add suffix -M.
•	 PVC coating available on specified products. Add suffix -PVC
to catalog number. To add PVC coating to items not specified,
contact your local sales representative.

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 30
CSA Certified: 013017

 In Class I, Division 1, Group B atmospheres, all conduit runs must have a sealing fitting (not supplied) field-installed adjacent to the enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

499

GR Conduit Outlet Boxes

Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw and O-Ring.

Enclosures and Junction Boxes

Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 4

Hub Type

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

GRE

GRC 

GRL 

GRLB 

GRN 

GRT 

GRX 

Conduit Size
(Inches)
1/2

Catalog Number 
Malleable Iron 
Aluminum
Cover Opening
Capacity
Form
Body With
Body with
Inches/Millimeters in3/dm3 Number  Aluminum Cover Aluminum Cover
3.38/85.9
18.0/.29
1
GRE50
GRE50-A

3/4

3.38/85.9

18.0/.29

1

GRE75

GRE75-A

1

3.38/85.9

18.0/.29

1

GRE100

GRE100-A

1-1/4
1-1/2
1/2

3.94/100.1
4.88/124.0
3.38/85.9

31.0/.51
72.0/1.18
18.0/.29

2
3
1

GRE125
GRE150
GRC50

GRE125-A
GRE150-A
GRC50-A

3/4

3.38/85.9

18.0/.29

1

GRC75

GRC75-A

1

3.38/85.9

18.0/.29

1

GRC100

GRC100-A

1-1/4

3.94/100.1

31.0/.51

2

GRC125

GRC125-A

1-1/2
2
1/2

4.88/124.0
4.88/124.0
3.38/85.9

72.0/1.18
76.0/1.25
18.0/.29

3
3
1

GRC150
GRC200
GRL50

GRC150-A
GRC200-A
GRL50-A

3/4

3.38/85.9

18.0/.29

1

GRL75

GRL75-A

1

3.38/85.9

18.0/.29

1

GRL100

GRL100-A

1-1/4

3.94/100.1

31.0/.51

2

GRL125

GRL125-A

1-1/2
2
1/2

4.88/124.0
4.88/124.0
3.38/85.9

72.0/1.18
76.0/1.25
18.0/.29

3
3
1

GRL150
GRL200
GRLB50

GRL150-A
GRL200-A
GRLB50-A

3/4

3.38/85.9

18.0/.29

1

GRLB75

GRLB75-A

1

3.38/85.9

18.0/.29

1

GRLB100

GRLB100-A

1-1/4

3.94/100.1

31.0/.51

2

GRLB125

GRLB125-A

1-1/2
2
1/2

4.88/124.0
4.88/124.0
3.38/85.9

72.0/1.18
76.0/1.25
18.0/.29

3
3
1

GRLB150
GRLB200
GRN50

GRLB150-A
GRLB200-A
GRN50-A

3/4

3.38/85.9

18.0/.29

1

GRN75

GRN75-A

1

3.38/85.9

18.0/.29

1

GRN100

GRN100-A

1-1/4

3.94/100.1

31.0/.51

2

GRN125

GRN125-A

1-1/2

4.88/124.0

72.0/1.18

3

GRN150

GRN150-A

1/2

3.38/85.9

18.0/.29

1

GRT50

GRT50-A

3/4

3.38/85.9

18.0/.29

1

GRT75

GRT75-A

1

3.38/85.9

18.0/.29

1

GRT100

GRT100-A

1-1/4

3.94/100.1

31.0/.51

2

GRT125

GRT125-A

1-1/2
2
1/2

4.88/124.0
4.88/124.0
3.38/85.9

72.0/1.18
76.0/1.25
18.0/.29

3
3
1

GRT150
GRT200
GRX50

GRT150-A
GRT200-A
GRX50-A

3/4

3.38/85.9

18.0/.29

1

GRX75

GRX75-A

1

3.38/85.9

18.0/.29

1

GRX100

GRX100-A

1-1/4

3.94/100.1

31.0/.51

2

GRX125

GRX125-A

1-1/2
2

4.88/124.0
4.88/124.0

72.0/1.18
76.0/1.25

3
3

GRX150
GRX200

GRX150-A
GRX200-A

 In Class I, Division 1, Group B atmospheres, all conduit runs must have a sealing fitting (not supplied) field-installed adjacent to the enclosure.
① Other covers available—see GR and GRF Conduit Outlet Box Covers page. Order separately.
 For malleable iron body and cover, add suffix -M.
 Form number designates body and matching cover sizes. To order body without cover, add suffix -LC to catalog number.
 PVC coating available, add suffix -PVC to catalog number.

500

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GR Conduit Outlet Boxes

Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw and O-Ring.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 4

Cover Opening
Inches/Millimeters

Capacity
in3/dm3

1/2

3.38/85.9

18.0/0.29

1

GRCA50

GRCA50-A

3/4

3.38/85.9

18.0/0.29

1

GRCA75

GRCA75-A

1/2

3.38/85.9

18.0/0.29

1

GRLA50

GRLA50-A

3/4

3.38/85.9

18.0/0.29

1

GRLA75

GRLA75-A

1/2

3.38/85.9

18.0/0.29

1

GRTA50

GRTA50-A

3/4

3.38/85.9

18.0/0.29

1

GRTA75

GRTA75-A

GRCA

GRLA

GRTA

Dimensions
Hub Size
(Inches)
A
GR Series, Form 1
1/2

3.75/95.3

B
2.44/62

Dimensions in Inches/Millimeters
C
D
E
2.88/73.2

0.75/19.1

0.81/20.6

F

G

2.25/57.2

1.25/31.8

3/4

3.75/95.3

2.44/62

2.88/73.2

0.75/19.1

0.81/20.6

2.25/57.2

1.25/31.8

1

3.75/95.3

2.44/62

2.88/73.2

0.94/23.9

0.94/23.9

2.25/57.2

1.06/26.9

3.56/90.4

1.19/30.2

0.88/22.4

2.75/69.9

1.13/28.7

GR Series, Forms 2 and 3
1-1/4

4.50/114.3 2.69/68.3

1-1/2

5.75/146.1 3.75/95.3 4.81/122.2 1.38/35.1

2

5.75/146.1 4.00/101.6 5.06/128.5 1.63/41.4

0.94/23.9 4.06/103.1 1.50/38.1
1/25.4

4.25/108.0 1.25/31.8

 In Class I, Division 1, Group B atmospheres, all conduit runs must have a sealing fitting (not supplied) field-installed adjacent to the enclosure.
 Other covers available—see GR and GRF Conduit Outlet Box Covers page. Order separately.
 For malleable iron body and cover, add suffix -M.
 Form number designates body and matching cover sizes. To order body without cover, add suffix -LC to catalog number.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

501

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Conduit Size
(Inches)

Enclosures and Junction Boxes

Hub Type

Catalog Number 
Malleable Iron 
Aluminum
Form
Body With
Body with
Number  Aluminum Cover Aluminum Cover

GRF Flanged Conduit Outlet Boxes
Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw and O-Ring.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 4

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Catalog Number 

Hub Type

GRFC

GRFL

GRFT

GRFX

Malleable Iron 
Aluminum
Form
Body With
Body with
Number  Aluminum Cover Aluminum Cover

Conduit Size
(Inches)

Cover Opening
Inches/Millimeters

Capacity
in3/dm3

1/2

3.38/85.9

18.0/0.29

1

GRFC50

GRFC50-A

3/4

3.38/85.9

18.0/0.29

1

GRFC75

GRFC75-A

1

3.38/85.9

18.0/0.29

1

GRFC100

GRFC100-A

1/2

3.38/85.9

18.0/0.29

1

GRFL50

GRFL50-A

3/4

3.38/85.9

18.0/0.29

1

GRFL75

GRFL75-A

1

3.38/85.9

18.0/0.29

1

GRFL100

GRFL100-A

1/2

3.38/85.9

18.0/0.29

1

GRFT50

GRFT50-A

3/4

3.38/85.9

18.0/0.29

1

GRFT75

GRFT75-A

1

3.38/85.9

18.0/0.29

1

GRFT100

GRFT100-A

1/2

3.38/85.9

18.0/0.29

1

GRFX50

GRFX50-A

3/4

3.38/85.9

18.0/0.29

1

GRFX75

GRFX75-A

1

3.38/85.9

18.0/0.29

1

GRFX100

GRFX100-A

Dimensions

 In Class I, Division 1, Group B atmospheres, all conduit runs must have a sealing fitting (not supplied) field-installed adjacent to the enclosure.
 Other covers available—see GR and GRF Conduit Outlet Box Covers page. Order separately
 For malleable iron body and cover, add suffix -M.
 Form number designates body and matching cover sizes. To order body without cover, add suffix -LC to catalog number.

502

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GR and GRF Conduit Outlet Box Covers
Explosionproof, Dust-Ignitionproof

Covers and O-rings Fit Bodies with Corresponding Form Numbers.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 4

Cover Opening
Fixture Stem Size
Form
Inches/Millimeters Inches/Millimeters Number 

Catalog Number
Malleable Iron
Aluminum

1

GRK-1M

GRK-1

3.94/100.1

2

GRK-2M

GRK-2

4.88/124.0

3

GRK-3M

GRK-3

3.38/85.9

1

GRK-1SC

GRK-1SC-A

3.94/100.1

2

GRK-2SC

GRK-2SC-A

4.88/124.0

3

GRK-3SC

GRK-3SC-A

2” Deep Dome
UL Listed: E185964

3.38/85.9

1

Union Hub

3.38/85.9

0.75/19.1

1

GRK-75U

GRK-75UA

3.38/85.9

0.50/12.7

1

GRK-50

GRK50-A

3.38/85.9

0.75/19.1

1

GRK-75

GRK75-A

3.38/85.9

0.50/12.7

1

GRK-50C

—

3.38/85.9

0.75/19.1

1

GRK-75C

—

3.38/85.9

1.00/25.4

1

GRK-100C

—

Surface 

Sealing 

GRK-1DC

—

Hub

Canopy
Length 4-1/2”

Catalog Number
O-Rings — Buna-N
Provide Raintight fit when used on following series:
GR (Forms 1, 2 and 3), GRF (Form 1), GRH, and GRU
(Form 1).

1

GRG-1

2

GRG-2

3

GRG-3

GRTB Terminal Strip
For use in standard GR series boxes Weidmuller type MK terminal block  with wire range of #22-#12 AWG.
Mounts on 2 predrilled and tapped standard holes (furnished in internal GR boxes).

6 position terminal block kit

1+2

GRTB6-12

6 position terminal block kit

3

GRTB6-3

12 position terminal block kit

3

GRTB12-3

 In Class I, Division 1, Group B atmospheres, all conduit runs must have a sealing fitting (not supplied) field-installed adjacent to the enclosure.
 Form numbers designate cover and matching body sizes.
 PVC coating available, add suffix -PVC to catalog number.
 Terminal block is UL listed for 300 Volt, 25 Amp. CSA certified for 300 Volt, 13 Amp.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

503

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

3.38/85.9

Enclosures and Junction Boxes

Hub Type

GRH Conduit Outlet Boxes

Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw and O-Ring.
Class I, Division 1 and 2, Groups A, B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 4

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Applications
•	
•	
•	
•	
•	

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features
•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints
and ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Designed for use in Class I, Groups A, B, C, and D; Class II,
Groups E, F, and G; and Class III.
•	 Internally threaded body with externally threaded covers.
•	 Standard O-rings provide raintight fit. NEMA 3, 4.
•	 Internal ground screw standard.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

Hub
Type

GRHC

GRHL

GRHLB

GRHT

GRHX

504

Conduit Cover Opening
Catalog
Size
Inches/
Capacity
Number
(Inches) Millimeters
in3/dm3 Malleable Iron
1/2

3.38/85.9

13.8/0.23 GRHC50

3/4

3.38/85.9

13.8/0.23 GRHC75

1

3.38/85.9

13.8/0.23 GRHC100

1/2

3.38/85.9

13.8/0.23 GRHL50

3/4

3.38/85.9

13.8/0.23 GRHL75

1

3.38/85.9

13.8/0.23 GRHL100

•	 Body: malleable iron
•	 Cover: copperfree (4/10 of 1% max.) aluminum

Standard Finishes
•	 Body: triple-coat — (1) zinc electroplate, (2) chromate, and (3)
epoxy powder coat
•	 Cover: epoxy powder coat

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 30
CSA Certified: 013017

Dimensions in Inches/Millimeters

Hub Size
(Inches)

A

B

C

D

E

F

G

1/2

3.75/
95.3

2.44/
62

2.63/
66.8

0.75/
19.1

0.81/
20.6

1.63/
41.4

1.25/
31.8

1/2

3.38/85.9

13.8/0.23 GRHLB50

3/4

3.38/85.9

13.8/0.23 GRHLB75

3/4

3.75/
95.3

2.44/
62

2.63/
66.8

0.75/
19.1

0.81/
20.6

1.63/
41.4

1.25/
31.8

1

3.38/85.9

13.8/0.23 GRHLB100

1

3.75/
95.3

2.44/
62

2.63/
66.8

0.94/
23.9

0.94/
23.9

1.63/
41.4

1.06/
26.9

1/2

3.38/85.9

13.8/0.23 GRHT50

3/4

3.38/85.9

13.8/0.23 GRHT75

1

3.38/85.9

13.8/0.23 GRHT100

1/2

3.38/85.9

13.8/0.23 GRHX50

3/4

3.38/85.9

13.8/0.23 GRHX75

1

3.38/85.9

13.8/0.23 GRHX100

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GRSS Conduit Outlet Boxes with Multiple Hubs
Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw and O-Ring gasket.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Applications

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features

•	 Bodies and covers: copperfree (4/10 of 1% max.) aluminum

Standard Finishes
•	 Epoxy powder coat

Certifications and Compliances

Box Type

Conduit Size
(Inches)

•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 30
CSA Certified: 025875

Cover Opening
Inches/Millimeters

Hubs

Plugs

Capacity
in3/dm3

Catalog
Number 

GRSS Outlet Box with Cover
Internally threaded aluminum bodies with externally threaded aluminum form 1 covers.
Has 7 hubs; 2 on each of the sides, 1 on the top, 1 on the bottom and 1 on the center in the back.
Furnished with 4 close-up plugs and O-Ring.

1/2
GRSS

3.38/85.9

7

4

29.0/0.48

GRSS50

3/4

3.38/85.9

7

4

29.0/0.48

GRSS75

1

3.38/85.9

7

4

29.0/0.48

GRSS100

GRSSA Outlet Box with Cover
Internally threaded aluminum bodies with externally threaded aluminum form 1 covers.
Has 13 hubs; 2 on each side, 2 each on top and bottom and 5 in the back.
Furnished with 5 close-up plugs and O-Ring.

GRSSA

1/2

3.38/85.9

13

5

29.0/0.48

GRSSA50

3/4

3.38/85.9

13

5

29.0/0.48

GRSSA75

Dimensions
GRSS

GRSSA

 In Class I, Division 1, Group B atmospheres, all conduit runs must have a sealing fitting (not supplied) field-installed adjacent to the enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

505

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Multiple hubs permit flexibility.
•	 Copperfree aluminum body and cover provide superior
corrosion resistance.
•	 Internal ground screw standard.

Enclosures and Junction Boxes

•	
•	
•	
•	
•	

CPU Universal Conduit Outlet Boxes and Covers
Explosionproof, Dust-Ignitionproof
UNILETS® for use with Threaded Metal Conduit.
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

•	 Bodies and covers : malleable iron
•	 Connection block: phenolic

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate,
(2) chromate, and (3) epoxy powder coat

Features
•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Universal design with four threaded universal hubs and three
close-up plugs.
•	 Serve as mounting outlets for lighting fixtures when used with
hub cover.
•	 Wide, accurately ground explosion-proof mating surfaces.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.
Conduit
Size
(Inches)

Box Type

Fixture
Cover
Stem Size
Opening
Inches Inches/Millimeters

Certifications and Compliances
•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

Capacity
in3/dm3

Catalog
Number

Dimensions
CPU Box with Cover

CPU Box with Blank Cover
Furnished with four threaded universal 3/4” hubs, four 3/4” to 1/2” reducers, and three 1/2” close-up
plugs.

1/2 or 3/4

Blank

3.81/96.8

21.0/0.34 CPU20

CPU Box with Hub Cover
(Supports lbs – 112.5 kg. Furnished with four threaded universal 3/4” hubs, four 3/4” to 1/2” reducers,
and three 1/2” close-up plugs.

1/2 or 3/4

1/2

3.81/96.8

21.0/0.34 CPU20-50

1/2 or 3/4

3/4

3.81/96.8

21.0/0.34 CPU20-75

Blank

3.81/96.8

21.0/0.34 CPSK20B

CPU Covers only
Furnished with fastening screws.

Cover

Connection Block
Hub
Covers

1/2

3.81/96.8

21.0/0.34 CPSK20-50

3/4

3.81/96.8

21.0/0.34 CPSK20-75

1.31”/
33.3 mm

CPU Connection Block
Phenolic. With fastening strap and two mounting screws.

5-Wire, 20 Amp, 300 Volt

506

2.88”/73.0 mm

➤

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

•	
•	
•	
•	
•	

➤

Enclosures and Junction Boxes

Applications

0.22”/5.6 mm

CB205

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

CPU Universal Conduit Outlet Boxes and Covers V
CSA Certification Only. Explosionproof, Dust-Ignitionproof
UNILETS® for use with Threaded Metal Conduit.
Class I, Division 1 and 2, Groups C, D
Class I, Zone 1 and 2, IIB T6
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 3

•	
•	
•	
•	
•	

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

•	 Bodies and covers : malleable iron or copperfree (4/10 of 1%
max.) aluminum
•	 Connection block: phenolic

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate, (2)
chromate, and (3) epoxy powder coat

Features

Box Type

Conduit
Size
(Inches)

Fixture
Cover
Stem Opening
Size
Inches/
Inches Millimeters

Capacity
in3/dm3

Options
•	 To order with CB205 connection block installed add suffix -CB.

Certifications and Compliances

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Universal design with four threaded universal hubs and three
close-up plugs.
•	 Serve as mounting outlets for lighting fixtures when used with
hub cover.
•	 Wide, accurately ground explosion-proof mating surfaces.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

•	 CSA Standard: C22.2 No. 25, C22.2 No. 30
•	 CSA Certified: 013017

Catalog Number
Malleable Iron
Aluminum

Dimensions
CPU Box with Cover

CPU Box with Blank Cover
Furnished with four threaded universal 3/4” hubs, four 3/4” to 1/2” reducers, and three 1/2” close-up plugs. To
order with CB205 connection block installed add suffix -CB.

1/2 or 3/4 Blank 3.81/96.8 21.0/0.34 CPU20CN

CPU20ACN

CPU Box with Hub Cover
(Supports lbs – 112.5 kg. Furnished with four threaded universal 3/4” hubs, four 3/4” to 1/2” reducers, and
three 1/2” close-up plugs. To order with CB205 connection block installed add suffix -CB.

1/2 or 3/4

1/2

3.81/96.8 21.0/0.34 CPU20-50CN

CPU20-50ACN

1/2 or 3/4

3/4

3.81/96.8 21.0/0.34 CPU20-75CN

CPU20-75ACN

Blank 3.81/96.8 21.0/0.34 CPSK20BCN

CPSK20B-ACN

CPU Covers only
Furnished with fastening screws.

Cover

1/2

3.81/96.8 21.0/0.34 CPSK20-50CN

CPSK20-50ACN

3/4

3.81/96.8 21.0/0.34 CPSK20-75CN

CPSK20-75ACN

Hub
Covers

CPU Connection Block — With fastening strap and two mounting screws
5-Wire, 20 Amp, 300 Volt

CB205CN

V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes

Applications

507

GRU Universal Conduit Outlet Boxes
Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw. Furnished with O-Ring.

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Applications
•	
•	
•	
•	
•	

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features

•	 Bodies and covers: copperfree (4/10 of 1% max.) aluminum

Standard Finishes
•	 Bodies and covers: epoxy powder coat

Certifications and Compliances

•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Universal design with five threaded universal hubs and three
close-up plugs.
•	 Copperfree aluminum body and cover provide resistance to
corrosive atmospheres.
•	 Internally threaded body and externally threaded cover with
O-ring for raintight fit, NEMA 3, 4.
•	 Covers have pry notches for bar or wrench.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 30
CSA Certified: 025875

Furnished with externally threaded aluminum surface cover, O-Ring, five threaded hubs, and three close-up plugs.
For Form numbers designate body and matching cover sizes.

Conduit Size
(Inches)

Cover Body Opening
Inches/Millimeters

Capacity
in3/dm3

Form
Number

Catalog
Number

1/2

3.38/85.9

13.5/0.22

1

GRU50-A

3/4

3.38/85.9

13.5/0.22

1

GRU75-A

1

3.38/85.9

17.5/0.29

1

GRU100-A *

Dimensions

Dimensions in Inches/Millimeters
C
D

Hub Size Inches

A

B

1/2

3.75/95.3

2.25/57.2

2.69/68.3

3/4

3.75/95.3

2.25/57.2

2.69/68.3

1

3.75/95.3

2.44/62.0

2.88/73.2

E

F

G

0.69/17.5

1.38/35.1

4.06/103.1

2.00/50.8

0.69/17.5

1.38/35.1

4.06/103.1

2.00/50.8

0.94/23.9

1.44/36.6

5.44/138.2

2.19/55.6

* Not CSA Certified.

508

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GRUE Universal Conduit Outlet Boxes
Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw.
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Applications

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features

•	 Bodies and covers: epoxy powder coat

Certifications and Compliances
•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

Furnished with internally threaded aluminum surface cover, five threaded hubs, and three close-up plugs.
For Form numbers designate body and matching cover sizes.

Conduit Size
(Inches)

Cover Body Opening
Inches/Millimeters

Capacity
in3/dm3

Catalog
Number

1/2

3.38/85.9

13.5/0.22

GRUE50-A

3/4

3.38/85.9

13.5/0.22

GRUE75-A

1

3.38/85.9

17.5/0.29

GRUE100-A *

Dimensions

Dimensions in Inches/Millimeters
D
E

Hub Size
Inches

A

B

C

F

G

1/2

4.25/108.0

2.25/57.2

2.75/69.9

0.69/17.5

1.44/36.6

4.06/103.1

2.06/52.3

3/4

4.25/108.0

2.25/57.2

2.75/69.9

0.69/17.5

1.44/36.6

4.06/103.1

2.06/52.3

1

4.25/108.0

2.44/62.0

3.00/76.2

0.94/23.9

1.50/38.1

5.44/138.2

2.25/57.2

* Not CSA Certified.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

509

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Universal design with five threaded universal hubs and three
close-up plugs.
•	 Copperfree aluminum body and cover provide resistance to
corrosive atmospheres.
•	 Covers have pry notches for bar or wrench.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

•	 Bodies and covers: copperfree (4/10 of 1% max.) aluminum

Standard Finishes

Enclosures and Junction Boxes

•	
•	
•	
•	
•	

GRUE Universal Conduit Outlet Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof

GRUE-100 Series UNILETS® for 1/2", 3/4" and 1" threaded metal conduit. GRUE-200 Series UNILETS® for 1-1/4", 1-1/2" and 2" threaded metal conduit.

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2, IIB + H2 T6
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 3

Applications
•	
•	
•	
•	
•	

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Universal design with five threaded universal hubs and three
close-up plugs.
•	 Copperfree aluminum body and cover provide resistance to
corrosive atmospheres.
•	 GRUE-100 Series functions as sealing fittings when used with
sealing covers (see CEC for restrictions).

Conduit Size
(Inches)

•	 Covers have pry notches for bar or wrench.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

Standard Materials
•	 Bodies and covers : malleable iron or copperfree (4/10 of 1%
max.) aluminum

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate, (2)
chromate, and (3) epoxy powder coat

Options
•	 GRUE-100 Series
— To order GRUE-100 Series universal junction box complete
with sealing cover add suffix -SC.

Certifications and Compliances
•	 CSA Standard: C22.2 No. 25, C22.2 No. 30
•	 CSA Certified: 013017

Hub
Configuration

Catalog Number
Malleable Iron
Aluminum

GRUE-100 Series Universal Junction Box

Furnished with internally threaded surface cover, five threaded hubs and three close-up plugs. To order GRUE-100 Series junction box complete with sealing
cover add suffix -SC.

1/2
3/4

XP

1

GRUE50CN

GRUE50-ACN

GRUE75CN

GRUE75-ACN

GRUE100CN

GRUE100-ACN

GRUC-SC-F

GRUC-SC

GRUE-100 Series Sealing Cover

Sealing cover for GRUE-100 Series junction boxes listed above.

GRUE-100 Dimensions
Hub Size
Inches

Dimensions in Inches/Millimeters
H

1/2

0.75/19.1

3/4

0.75/19.1

1

0.88/22.2

Body

Cover

V CSA Certification Only.

510

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GRUE Universal Conduit Outlet Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof
GRUE-200 Series UNILETS® for 1-1/4", 1-1/2" and 2" threaded metal conduit.
Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2, IIB + H2 T6
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 3

Hub
Configuration

Catalog Number
Malleable Iron
Aluminum

Enclosures and Junction Boxes

Conduit Size
(Inches)
GRUE-200 Series

Furnished with internally threaded surface cover. Entries are supplied as listed.

1-1/4
1-1/2

C

2
1-1/4
CB

2
1-1/4

GRUE-125C-A

GRUE-150C

GRUE-150C-A

GRUE-200C

GRUE-200C-A

GRUE-125CB

GRUE-125CB-A

GRUE-150CB

GRUE-150CB-A

GRUE-200CB

GRUE-200CB-A

GRUE-125E

GRUE-125E-A

GRUE-150E

GRUE-150E-A

2

GRUE-200E

GRUE-200E-A

1-1/4

GRUE-125L

GRUE-125L-A

GRUE-150L

GRUE-150L-A

GRUE-200L

GRUE-200L-A

1-1/2

1-1/2

E

L

2
1-1/4
1-1/2

LB

2
1-1/4
1-1/2

T

2
1-1/4
1-1/2

TB

2
1-1/4
1-1/2

X

2
1-1/4
1-1/2
2

XB

GRUE-125LB

GRUE-125LB-A

GRUE-150LB

GRUE-150LB-A

GRUE-200LB

GRUE-200LB-A

GRUE-125T

GRUE-125T-A

GRUE-150T

GRUE-150T-A

GRUE-200T

GRUE-200T-A

GRUE-125TB

GRUE-125TB-A

GRUE-150TB

GRUE-150TB-A

GRUE-200TB

GRUE-200TB-A

GRUE-125X

GRUE-125X-A

GRUE-150X

GRUE-150X-A

GRUE-200X

GRUE-200X-A

GRUE-125XB

GRUE-125XB-A

GRUE-150XB

GRUE-150XB-A

GRUE-200XB

GRUE-200XB-A

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

1-1/2

GRUE-125C

GRUE-200 Dimensions
Body

Cover

V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

511

GRJS Universal Conduit Outlet Box
Explosionproof, Dust-Ignitionproof
UNILETS® for use with Threaded Metal Conduit.
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
Raintight

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Applications
•	
•	
•	
•	
•	

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features
•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Universal design with five threaded openings and three closeup plugs.
•	 Compact round box for use where space is limited.
•	 Serve as mounting means for lighting fixtures when used with
hub cover.
•	 Internally threaded body with externally threaded cover.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

Box Type
GRJS Universal Box with Cover

Conduit
Size
(Inches)

Cover
Opening
Inches/Millimeters

•	 Bodies: malleable iron
•	 Covers: copperfree (4/10 of 1% max.) aluminum

Standard Finishes
•	 Bodies: triple-coat — (1) zinc electroplate, (2) chromate, and (3)
epoxy powder coat
•	 Covers: epoxy powder coat

Certifications and Compliances
•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

Dimensions
Capacity
in3/dm3

Catalog
Number

Top

Internally threaded malleable iron body with externally threaded aluminum surface cover.
Complete with five threaded universal openings and three close-up plugs.

1/2

2.56/65.0

7.3/0.12

GRJS50

3/4

2.56/65.0

7.3/0.12

GRJS75

1

2.56/65.0

7.3/0.12

GRJS100

2.56/65.0

7.3/0.12

GRJSK

GRJS Aluminum Covers

Surface

Side

Hub

512

1/2

2.56/65.0

7.3/0.12

GRJSK-50

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GRJS Universal Conduit Outlet Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof, Weather Resistant (Raintight)
UNILETS® for use with Threaded Metal Conduit.
Class I, Division 1 and 2, Groups C, D
Class I, Zone 1 and 2, IIB T6
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 3

Applications

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features

Standard Finishes
•	 Bodies: triple-coat — (1) zinc electroplate, (2) chromate, and (3)
epoxy powder coat
•	 Covers: epoxy powder coat

Certifications and Compliances
•	 CSA Standard: C22.2 No. 25, C22.2 No. 30
•	 CSA Certified: 013017

Catalog Number

Conduit Size
(Inches)

Malleable Iron

Aluminum

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Universal design with five threaded openings and three closeup plugs.
•	 Compact round box for use where space is limited.
•	 Serve as mounting means for lighting fixtures when used with
hub cover.
•	 Function as sealing fittings when used with sealing covers (see
CEC for restrictions).
•	 Internally threaded body with externally threaded cover.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

•	 Bodies: malleable iron or copperfree (4/10 of 1% max.)
aluminum
•	 Covers: copperfree (4/10 of 1% max.) aluminum

Dimensions
Top

GRJS Universal Box with Cover
The Unilet has five threaded hubs, one in each of four sides and one in bottom. Three close-up plugs are
furnished. Unilet opening is 2-9/16". Furnished with externally threaded blank surface cover and three close-up
plugs. Supplied with O-Ring.

1/2

GRJS50CN

3/4

GRJS75CN

GRJS75-ACN

1

GRJS100CN

GRJS100-ACN

GRJS50-ACN

GRJS Aluminum Covers
Furnished with internal threads.

Surface Cover

GRJSKCN
Side

Sealing Cover

GRJSK-SCCN

1/2" Hub Cover

GRJSK-50CN

V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes

•	
•	
•	
•	
•	

513

GRJ Conduit Outlet Boxes

Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw.
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Applications
•	
•	
•	
•	
•	

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Conduit
Size
Box Type (Inches)

Cover
Opening Capacity
in/mm
in3/dm3

Catalog
Number

GRJ Box with Cover

Features

1/2

2.13/
54.1

7.3/
0.12

GRJC50

3/4

2.13/
54.1

7.3/
0.12

GRJC75

1/2

2.13/
54.1

7.3/
0.12

GRJCA50

3/4

2.13/
54.1

7.3/
0.12

GRJCA75

1/2

2.13/
54.1

7.3/
0.12

GRJEA50

3/4

2.13/
54.1

7.3/
0.12

GRJEA75

1/2

2.13/
54.1

7.3/
0.12

GRJL50

3/4

2.13/
54.1

7.3/
0.12

GRJL75

1/2

2.13/
54.1

7.3/
0.12

GRJT50

3/4

2.13/
54.1

7.3/
0.12

GRJT75

1/2

2.13/
54.1

7.3/
0.12

GRJTA50

3/4

2.13/
54.1

7.3/
0.12

GRJTA75

1/2

2.13/
54.1

7.3/
0.12

GRJX50

3/4

2.13/
54.1

7.3/
0.12

GRJX75

GRJ Surface
Covers

2.13/
54.1

GRJC

•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints
and ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Small, round conduit outlet boxes.
•	 Externally threaded body with internally threaded cover.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

GRJCA

Standard Materials

GRJEA

•	 Bodies and covers: malleable iron

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate, (2)
chromate, and (3) epoxy powder coat

Certifications and Compliances

GRJL

•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

GRJT

Dimensions

GRJTA

GRJX

GRJ Covers

514

GRJK-S

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GRJ Conduit Outlet Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof, Weather Resistant (Raintight)
UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw.
Class I, Division 1 and 2, Groups C, D
Class I, Zone 1 and 2, IIB T6
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 3

Applications
Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Box Type

Conduit Size
(Inches)

Catalog Number

GRJ Box with Cover
Furnished with internally threaded surface cover.

Features

GRJC50CN

3/4

GRJC75CN

GRJCA

1/2

GRJCA50CN

Includes a
rear hub.

3/4

GRJCA75CN

GRJEA

Includes a
rear hub.

1/2

GRJEA50CN

Standard Materials

3/4

GRJEA75CN

1/2

GRJL50CN

3/4

GRJL75CN

1/2

GRJT50CN

3/4

GRJT75CN

1/2

GRJTA50CN

3/4

GRJTA75CN

1/2

GRJX50CN

3/4

GRJX75CN

•	 Bodies and covers: malleable iron

Standard Finishes
•	 Bodies and covers: zinc electroplate

GRJL

Certifications and Compliances
•	 CSA Standard: C22.2 No. 25, C22.2 No. 30
•	 CSA Certified: 013017

GRJT

GRJTA

Dimensions

Includes a
rear hub.

GRJX

GRJ Covers
Furnished with internal threads.

GRJK-SCN

Surface Cover

GRJK-SCN

Sealing Cover

GRJK-SCCN

V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

515

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

1/2
GRJC

•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints
and ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Small, round conduit outlet boxes.
•	 Bodies have external threads around cover opening, and the
covers are threaded internally. Unilet opening is 2-1/8".
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.
•	 Function as sealing fittings when used with sealing covers (see
CEC for restrictions).

Enclosures and Junction Boxes

•	
•	
•	
•	
•	

GRUO with Multiple Hubs Conduit Outlet Boxes
Explosionproof, Dust-Ignitionproof
UNILETS® for use with Threaded Metal Conduit.
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Applications
•	
•	
•	
•	
•	

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

•	 Bodies and covers: malleable iron

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate, (2)
chromate, and (3) epoxy powder coat

Certifications and Compliances

Features
•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Union hubs permit easy wiring.
•	 Externally threaded body with internally threaded cover.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

Each Side

•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 25
CSA Certified: 013017, 025875

Number and Size of Hubs
Top
Bottom

Back

Capacity
in3/dm3

Catalog
Number

GRUO Box with Cover
Externally threaded malleable iron body complete with internally threaded malleable iron surface cover;
eight conduit hubs and close-up plugs for all but three 3/4” hubs. Cover opening — 3.25”/82.6 mm

1 — 3/4”

2 — 3/4”

2 — 3/4”

1 — 3/4”

1 — 1”

25.0/0.41

GRUO-2

25.0/0.41

GRU Covers
Malleable iron with internal threads. Cover opening — 3.25”/82.6 mm

Surface

GRUK-S

Dimensions

516

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GRUJ Conduit Outlet Boxes with Multiple Hubs
Explosionproof, Dust-Ignitionproof
UNILETS® for use with Threaded Metal Conduit.
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Applications

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Enclosures and Junction Boxes

•	
•	
•	
•	
•	

•	 Bodies and covers: malleable iron

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate, (2)
chromate, and (3) epoxy powder coat

Certifications and Compliances

Features

Each Side

•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

Number and Size of Hubs
Top
Bottom

Back

Capacity
in3/dm3

Catalog
Number

GRUJ Box with Cover
Externally threaded malleable iron body complete with internally threaded malleable iron surface cover; choice of
hub arrangements, furnished with close-up plugs for all but three 3/4” hubs. Cover opening—3.25”/82.6 mm

2 — 3/4”

2 — 3/4”

1 — 3/4”

None

25.0/0.41

GRUJ-1P

2 — 3/4”

2 — 3/4”

1 — 3/4”

4 — 3/4”

25.0/0.41

GRUJ-2P

2 — 3/4”

2 — 3/4”

1 — 3/4”

4 — 1”

25.0/0.41

GRUJ-3P

GRU Covers
Malleable iron with internal threads. Cover opening—3.25”/82.6 mm.

Surface

GRUK-S

Dimensions

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

517

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Union hubs permit easy wiring.
•	 Externally threaded body with internally threaded cover.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.

GRU Conduit Outlet Boxes with Union Hubs
Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw.
Class I, Division 1 and 2, Groups C ,D
Class II, Division 1 and 2, Groups E, F, G
Class III

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Applications
•	
•	
•	
•	
•	

Standard Materials

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features
•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints and
ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Union hubs permit easy wiring.
•	 Externally threaded body with internally threaded cover.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation

Box Type

Conduit Size
(Inches)

•	 GRUT and GRUSE bodies and covers: malleable iron
•	 GRUSE body and cover: copper free (4/10 of 1% max)
aluminum.

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate, (2)
chromate, and (3) epoxy powder coat

Certifications and Compliances
•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

Cover Opening
Inches/Millimeters

Capacity
in3/dm3

Catalog Number
Malleable Iron
Aluminum

GRU with Union Hubs
GRUT 1/2” thru 1” and GRUSE 1/2” thru 3/4” — Malleable iron externally threaded body complete with internally
threaded malleable iron surface cover.
GRUSE 1” — Copper free aluminum cover and body with externally threaded cover.

GRUT

GRUSE

1/2

3.25/82.6

19.0/0.31

GRUT50

—

3/4

3.25/82.6

19.0/0.31

GRUT75

—

1

3.25/82.6

19.0/0.31

GRUT100

—

1/2

3.25/82.6

19.0/0.31

GRUSE50

—

3/4

3.25/82.6

19.0/0.31

GRUSE75

—

1

3.75/95.3

29.0/0.48

—

GRUSE100

GRU Covers
Malleable iron with internal threads. For GRUT and GRUSE listed above. Do not use with GRUSE100.

Surface

518

3.25/0.05

GRUK-S

—

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GRU Conduit Outlet Boxes with Union Hubs Dimensions
Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw.

GRUSE50 and GRUSE75

Enclosures and Junction Boxes

GRUT

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

GRUSE100

Hub Size
(Inches)

Dimensions in Inches/Millimeters
D
E

A

B

C

F

G

1/2

4.19/106.4

2.69/68.3

6.25/158.8

0.75/19.1

8.25/209.6

2.31/58.7

–

3/4

4.19/106.4

2.69/68.3

6.25/158.8

1

4.19/106.4

2.69/68.3

6.50/165.1

0.75/19.1

8.25/209.6

2.31/58.7

–

0.94/23.9

8.75/222.3

2.31/58.7

–

4.19/106.4

2.56/65.0

6.13/155.7

0.94/23.9

8/203.2

2.19/55.6

2.13/54.1

8.00/203.2

4.63117.6

2.38/60.5

3.75/95.3

3.48/88.4

4.63/117.6

–

GRUT

GRUSE50 and GRUSE75
1/2 and 3/4
GRUSE100
—

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

519

GU Conduit Outlet Boxes

Explosionproof, Dust-Ignitionproof

UNILETS® for use with Threaded Metal Conduit. Furnished with Internal Ground Screw.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III

Enclosures and Junction Boxes: Hazardous Location Conduit Outlet Boxes

Enclosures and Junction Boxes

Applications
•	
•	
•	
•	
•	

Hub
Type

Complies with a wide range of classified area requirements.
Corrosion-resistant: ideal indoors or out.
For pulling of wires.
Connect conduit lengths and change direction of conduit runs.
Provide access for maintenance.

Features

GUC

•	 Malleable iron bodies have high tensile strength and ductility.
Provides great resistance to corrosion, impact, and shock.
•	 Accurately tapped, tapered hub threads for tight, rigid joints
and ground continuity.
•	 Furnished with covers.
•	 General purpose wiring.
•	 Designed for Class I, Groups B, C, D; Class II, Groups E, F, G;
and Class III.
•	 Externally threaded body with internally threaded cover.
•	 Smooth, rounded integral bushing in each hub type box
protects conductor insulation.
•	 Internal ground screw standard.

GUL

Standard Materials

GULB

•	 Bodies and covers: malleable iron

Standard Finishes
•	 Bodies and covers: triple-coat — (1) zinc electroplate, (2)
chromate, and (3) epoxy powder coat

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 30
CSA Certified: 025875

GUT

GUX

Conduit Cover
Size Opening Capacity
(Inches) in/mm in3/dm3

Catalog
Number 

1/2

3.38/
98.6

19.0/
0.31

GUC50

3/4

3.38/
98.6

19.0/
0.31

GUC75

1

3.38/
98.6

19.0/
0.31

GUC100

1/2

3.38/
98.6

19.0/
0.31

GUL50

3/4

3.38/
98.6

19.0/
0.31

GUL75

1

3.38/
98.6

19.0/
0.31

GUL100

1/2

3.38/
98.6

19.0/
0.31

GULB50

3/4

3.38/
98.6

19.0/
0.31

GULB75

1

3.38/
98.6

19.0/
0.31

GULB100

1/2

3.38/
98.6

19.0/
0.31

GUT50

3/4

3.38/
98.6

19.0/
0.31

GUT75

1

3.38/
98.6

19.0/
0.31

GUT100

1/2

3.38/
98.6

19.0/
0.31

GUX50

3/4

3.38/
98.6

19.0/
0.31

GUX75

1

3.38/
98.6

19.0/
0.31

GUX100

Dimensions
Dimensions in Inches/Millimeters
C
D

Body and Cover

Hub Size
(Inches)

A

B

E

F

1/2

4.28/108.7

2.44/62.0

2.97/75.4

0.75/19.1

0.81/20.6

2.25/57.2

3/4

4.28/108.7

2.44/62.0

2.97/75.4

0.75/19.1

0.81/20.6

2.25/57.2

1

4.28/108.7

2.44/62.0

2.97/75.4

0.94/23.9

0.94/23.9

2.25/57.2

 In Class I, Division 1, Group B atmospheres, all conduit runs must have a sealing fitting (not supplied) field-installed adjacent to the enclosure.

520

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

BJE Series Octagonal Polycarbonate Junction Boxes
cCSAus Certification
CEC/NEC:
Zone 1 and 2 A/Exe II T6
Enclosure: IP66

Applications

BJE1

BJE2

BJE1 for Armored Cable

BJE2 for Armored Cable

Enclosures and Junction Boxes

•	 Small terminal/junction box enclosure for various electrical
connections in hazardous areas.
•	 Designed for use in Zone 1 or 2 areas, where flammable gases
or vapors are present either continuously or intermittently, such
as:
	 — Petroleum refineries
	 — Chemical refineries
	 — Other industrial process facilities
•	 Ideal for wet or corrosive atmospheres.
•	 Designed for use in Zone 21 or 22 areas (international),
where flammable dusts are present either continuously or
intermittently, such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Other commercial facilities

Features

Standard Materials
•	 Enclosure: static and impact resistant polycarbonate
•	 Hardware: 316L stainless steel

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

•	 High impact resistant black polycarbonate enclosure.
•	 Choose from two versions; external or internal hubs.
•	 BJE1: Supplied with 4 interconnected earth terminals.
Maximum capacity per terminal: 0.002 x 0.006 in2/1 x 4 mm2.
•	 BJE1 is supplied with 4 connection terminals. Maximum
capacity per terminal: 0.006 x 0.004 in2/ 4 x 2.5 mm2 or 0.003 x
0.006 in2/2 x 4 mm2 + 0.003 x 0.004 in2/2 x 2.5 mm2.
Minimum capacity per terminal: 0.003 x 0.002 in2/2 x 1.5 mm2.
Available in three depths, 7.87"/200 mm, 9.84"/250 mm and
11.81"/300 mm.
•	 BJE2: Supplied with 4 interconnected earth terminals. Maximum
capacity per terminal: 0.002 x 0.016 in2/1 x 10 mm2.
•	 BJE2 is supplied with 4 connection terminals. Maximum
capacity per terminal: 0.006 x 0.009 in2/4 x 6mm2 or 0.005 x
0.016 in2/3 x 10 mm2 + 0.006 in2/4 mm2.
•	 BJE2 has telescopic cover retaining ring which can be
unclipped.
•	 All hardware 316 Stainless Steel.
•	 Available for non-armored or armored cable. Armored cable
version supplied with ground continuity plate.
•	 Several entry options available.
•	 Operating temperature:
	 — BJE1: -58 °F/-50 °C to +131 °F/+55 °C
	 — BJE2: -40 °F/-40 °C to +131 °F/+55 °C
•	 Poured in place polyurethane door gasket.

Certifications and Compliances
•	
	
	
	
	
•	
	
	
	
	
	
	
	
	
	
	
	

North American
— CEC/NEC
— cCSAus Approved
— Zone 1 and 2 A/Exe II T6
— Enclosure IP66
International
— CENELEC
— ATEX O2 6069 /99 6003
— EEx e II G/D T6
— IEC 60049-0/7
— Ex e II T6
— IP66 to EN60529 and IEC 60529
— IK10 to EN 50102
— CE Declaration of Conformity: No. 50226/50209
— Combustible Dust: EN 50281-1-1/IEC
— 61241-1-1
— Zone 1, 2, 21, 22

521

BJE Series Octagonal Polycarbonate Junction Boxes
cCSAus Certification
CEC/NEC:
Zone 1 and 2 A/Exe II T6
Enclosure: IP66

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Armored Enclosures — Supplied with Two Plugs
Entry

Entries

Size

Plug

Weight lb/kg

Volume

Catalog Number

No

4

PG16

Knockouts

0.88/0.4

122.04/2.0

BJE1TN4P16

Yes

4

M20

2-M20

1.10/0.5

122.04/2.0

BJE1TA4M20

No

3

M20

No

1.32/0.6

274.60/4.5

BJE2TN3M20

No

4

M20

No

1.32/0.6

274.60/4.5

BJE2TN4M20

No

3

M25

No

1.32/0.6

274.60/4.5

BJE2TN3M25

No

4

M25

No

1.32/0.6

274.60/4.5

BJE2TN4M25

Yes

4

M20

2-M20

1.32/0.6

274.60/4.5

BJE2TA4M20

Yes

4

M25

2-M25

1.32/0.6

274.60/4.5

BJE2TA4M25

Nickel Plated Adapters
Description

Catalog Number

M20 to 1/2” NPT adapter for armored box

737EM2T15

M20 to 3/4” NPT adapter for armored box

737EM2T25

M25 to 3/4” NPT adapter for armored box

737EM3T25

M25 to 1” NPT adapter for armored box

737EM3T35

Dimensions in Inches/Millimeters

BJE1TA4M20

522

BJE2TA4M20

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEL and JBEP Series Polycarbonate and Polyester Junction Boxes

Increased Safety

Furnished complete with Terminals.
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Applications

JBEL for Unarmored Cable

•	 Small terminal junction boxes designed to facilitate electrical
connections in hazardous areas.
•	 Designed for use in Zone 1 or 2 areas, where flammable gases or
vapors are present either continuously or intermittently such as:
	 — Petroleum
	 — Chemical
	 — Refineries
	 — Other industrial process facilities
•	 Ideal for wet or corrosive atmospheres.
•	 Designed for use in Zone 21 or 22 areas where flammable dusts
are present either continuously or intermittently such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Other commercial facilities

JBEL for Armored Cable

Enclosures and Junction Boxes

Features

JBEP with Pillar Terminals

Standard Materials
•	
	
	
	
•	

JBEL Series
— Enclosure: static and impact resistant polycarbonate
— Cover gasket: polyurethane
— Hardware: stainless steel
JBEP Series
— Enclosure: static resistant carbon filled fiberglass reinforced
polyester (FRP)
	 — Hardware: stainless steel

JBEP with Screw Terminals

Certifications and Compliances
•	
	
	
	
	
	
	
	
	
	
	
	
	
•	
	
	
	
	
	
	
	
	
	
	

Certification Type BJe1
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II
– T Rating: T6
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T75 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 50226
— ATEX Certificate: LCIE 02 ATEX 6069
— IECEx Certificate: LCIE Ex 02.008
Certification Type BJe2
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II
– T Rating: T6
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T80 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 50209

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

	
	
•	
	
	
	
	
	
	
	
	
	
	
	
	
•	
•	
•	
•	
•	

— ATEX Certificate: LCIE 99 ATEX 6003
— IECEx Certificate: LCIE Ex 99.005
Certification Type CSPe
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II, Ex ia IIC, Ex ib IIC, EX de IIC,
	 Ex demb IIC
– T Rating: T6
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T75 °C
— Ambient Temperature: -67 °F/-55 °C to 140 °F/60 °C
— CE Declaration of Conformity: 50284
— ATEX Certificate: LCIE 09 ATEX 3032X
— IECEx Certificate: IECx LCI 09.0016X
Other Certifications: GOST
Ingress Protection (solid and liquid): IP66
Impact Resistance (shock): IK10
Ex Standards: EN/IEC 60079-0; 60079-7; 61241-0, 61241-1
Other Standards: EN/IEC 60529 (IP), 62262 (IK)

523

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

•	 Pillar type terminal block for easy connection.
•	 Available in two sizes: 0.006 in2/4 mm2 or 0.016 in2/10 mm2 for
polycarbonate version and up to 0.009 in2/6 mm2 for polyester
version.
•	 Unarmored or armored versions with earth continuity brass
device.
•	 Operating temperature -40 °F/-40 °C to 131 °F/55 °C for
polycarbonate version and -67 °F/-55 °C to 140 °F/60 °C for
polyester version.

JBEL and JBEP Series Polycarbonate and Polyester Junction Boxes

Increased Safety

Furnished complete with Terminals.
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

JBEL Series
Type

Equipment

Rating
(Amps)

Weight
lb/kg

Volume
in3/dm3

Catalog Number

Packs

JBEL1N4P16G

1

103.74/1.7

JBEL1A4M20

1

274.60/4.5

JBEL2N3M20G

1

274.60/4.5

JBEL2N4M20G

1

274.60/4.5

JBEL2N3M25G

1

274.60/4.5

JBEL2N4M25G

1

274.60/4.5

JBEL2A4M20

1

274.60/4.5

JBEL2A4M25

1

274.60/4.5

JBEL2A4M05

1

274.60/4.5

JBEL2A4M06

1

For Unarmored Cables 0.004/0.006 in2 / 2.5/4 mm2 660 V

Supplied with 4 connection terminals. Maximum capacity per terminal:
0.006 x 0.004 in2 / 4 x 2.5 mm2 or 0.003 x 0.004 in2 / 2 x 4 mm2 + 0.003 x 0.004 in2 / 2 x 2.5 mm and 4 interconnected earth terminals.
Maximum capacity per earth terminal: 0.001 x 0.004 in2 / 1 x 4 mm2

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

BJe1

4 x PG16 entries with knock-out caps †
28 A/
4 x Integrated cable glands for unarmored
0.004 in2/2.5 mm2
0.88/0.4
cable (diameter 0.31" to 0.69"/8 to 16 mm)
38 A/
Important: Cables must be secured to structure
2
2
0.006
in
/4
mm
close to box entries

103.74/1.7

For Armored Cables 0.004/0.006 in2 / 2.5/4 mm2 660 V

Supplied with 4 connection terminals. Maximum capacity per terminal:
0.006 x 0.004 in2 / 4 x 2.5 mm2 or 0.003 x 0.004 in2 / 2 x 4 mm2 + 0.003 x 0.004 in2 / 2 x 2.5 mm and 4 interconnected earth terminals.
Maximum capacity per earth terminal: 0.001 x 0.004 in2 / 1 x 4 mm2

BJe1

4 x M20 entries with earth brass continuity
device
2 x blanking plugs

28 A/
0.004 in2/2.5 mm2
0.88/0.4
38 A/
0.006 in2/4 mm2

For Unarmored Cables 0.009/0.016 in2 / 6/10 mm2 690 V

Supplied with 4 connection terminals. Maximum capacity per terminal:
0.004 x 0.009 in2 / 4 x 6 mm2 or 0.005 x 0.016 in2 / 3 x 10 mm2 + 0.004 / 4 mm2 and 4 interconnected earth terminals.
Maximum capacity per earth terminal: 0.001 x 0.016 in2 / 1 x 10 mm2

BJe2

3 x M20 entries
3 x cable glands for unarmored cable
(diameter 0.26" to 0.57"/6.5 to 14.5 mm)

BJe2

4 x M20 entries
4 x cable glands for unarmored cable
(diameter 0.26" to 0.57"/6.5 to 14.5 mm)

BJe2

3 x M25 entries
3 x cable glands for unarmored cable
(diameter 0.31" to 0.73"/8 to 18.5 mm)

BJe2

4 x M25 entries
4 x cable glands for unarmored cable
(diameter 0.31" to 0.73"/8 to 18.5 mm)

1.54/0.7
42 A/
0.016 in2/10 mm2 1.54/0.7
30 A/
0.009 in2/6 mm2
18 A/
1.54/0.7
0.006 in2/4 mm2
1.54/0.7

For Armored Cables 0.009/0.016 in2 / 6/10 mm2 690 V

Supplied with 4 connection terminals. Maximum capacity per terminal:
0.004 x 0.009 in2 / 4 x 6 mm2 or 0.005 x 0.016 in2 / 3 x 10 mm2 + 0.004 / 4 mm2 and 4 interconnected earth terminals.
Maximum capacity per earth terminal: 0.001 x 0.016 in2 / 1 x 10 mm2

BJe2

4 x M20 entries with earth brass continuity
device.
2 x M20 blanking plugs

BJe2

4 x M25 entries with earth brass continuity
device.
2 x M25 blanking plugs

BJe2

2 x M25 + 2 x M20 entries with earth brass
continuity device.
1 x M25 + 1 x M20 blanking plugs

BJe2

3 x M25 + 1 x M20 entries with earth brass
continuity device.
1 x M25 + 1 x M20 blanking plugs

1.54/0.7
42 A/
0.016 in2/10 mm2 1.54/0.7
30 A/
0.009 in2/6 mm2
18 A/
1.54/0.7
0.006 in2/4 mm2
1.54/0.7

† Knock-out caps can be used as plugs.

524

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEL and JBEP Series Polycarbonate and Polyester Junction Boxes

Increased Safety

Furnished complete with Terminals.
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

JBEP Series With Pillar Terminals
Type

Equipment

Entry
Layout

Weight
lb/kg

Volume
in3/dm3

Catalog Number

Pack

Supplied with 4 connection terminals. Maximum capacity per terminal:
0.006 x 0.009 in2 / 4 x 6 mm2 – Rating 30 Amps
2 x M20 at bottom with earth continuity device

2.20/1.0

244.09/4.0 JBEP3A2M20

1

CSPe1

2 x M20 at bottom with two cable glands for
unarmored cable
(diameter 0.26" to 0.57"/6.5 to 14.5 mm)

2.65/1.2

244.09/4.0 JBEP3N2M20G

1

CSPe1

4 x M20 with earth continuity device and two
blanking plugs

2.65/1.2

244.09/4.0 JBEP3A4M20

1

CSPe1

4 x M20 with four cable glands for
unarmoured cable
(diameter 0.26" to 0.57"/6.5 to 14.5 mm)

2.65/1.2

244.09/4.0 JBEP3N4M20G

1

Supplied with 8 connection terminals. Maximum capacity per terminal:
0.006 x 0.009 in2 / 4 x 6 mm2 – Rating 30 Amps
4 x M20 with earth continuity device and two
blanking plugs

3.09/1.4

244.09/4.0 JBEP4A4M20

1

CSPe2

4 x M20 with four cable glands for
unarmoured cable
(diameter 0.26" to 0.57"/6.5 to 14.5 mm)

3.09/1.4

244.09/4.0 JBEP4N4M20G

1

CSPe2

6 x M20 with earth continuity device and two
blanking plugs

3.09/1.4

244.09/4.0 JBEP4A6M20

1

CSPe2

6 x M20 with six cable glands for
unarmoured cable
(diameter 0.26" to 0.57"/6.5 to 14.5 mm)

3.09/1.4

244.09/4.0 JBEP4N6M20G

1

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

525

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

CSPe2

Enclosures and Junction Boxes

CSPe1

JBEL and JBEP Series Polycarbonate and Polyester Junction Boxes

Increased Safety

Furnished complete with Terminals.
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

JBEP Series With Screw Terminals
Catalog Number
Type

Equipment

Entry
Layout

Weight
lb/kg

Volume
in3/dm3

Standard
Terminal

Terminals Jumped
2 by 2

Pack

Enclosures and Junction Boxes

Supplied with 4 terminals and 2 earth terminals
CSPe1

4 x M20 with earth continuity
device and two blanking plugs

2.20/
1.0

244.09/
JBEP3A4M206
4.0

JBEP3A4M206J

1

CSPe1

4 x M20 with 4 cable glands for
unarmored cable (diameter
0.26" to 0.57"/6.5 to 14.5 mm)

2.65/
1.2

244.09/
JBEP3N4M206G
4.0

JBEP3N4M206JG

1

CSPe1

4 x M20 with earth continuity
device and two blanking plugs

2.20/
1.0

244.09/
JBEP3A4M2011
4.0

JBEP3A4M2011J

1

CSPe1

4 x M20 with 4 cable glands for
unarmored cable (diameter
0.26" to 0.57"/6.5 to 14.5 mm)

2.65/
1.2

244.09/
JBEP3N4M2011G
4.0

JBEP3N4M2011JG

1

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Catalog Number
Type

Equipment

Entry
Layout

Weight
lb/kg

Volume
in3/dm3

Standard
Terminal

Terminals Jumped
3 by 3

Pack

Supplied with 6 terminals and 3 earth terminals
CSPe2

6 x M20 with earth continuity
device and two blanking plugs

3.09/
1.4

244.09/
JBEP4A6M208
4.0

JBEP4A6M208J

1

CSPe2

6 x M20 with 4 cable glands for
unarmored cable (diameter
0.26" to 0.57"/6.5 to 14.5 mm)

3.09/
1.4

244.09/
JBEP4N6M208G
4.0

JBEP4N6M208JG

1

Supplied with 12 terminals and 3 earth terminals

526

CSPe2

6 x M20 with earth continuity
device and two blanking plugs

3.09/
1.4

244.09/
JBEP4A6M2015
4.0

JBEP4A6M2015J

CSPe2

6 x M20 with 4 cable glands for
unarmored cable (diameter
0.26" to 0.57"/6.5 to 14.5 mm)

3.09/
1.4

244.09/
JBEP4N6M2015G
4.0

JBEP4N6M2015JG

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEL and JBEP Series Polycarbonate and Polyester Junction Box Dimensions

Increased Safety

Furnished complete with Terminals.

Dimensions in Inches/Millimeters
JBEL Series

BJe1 with Cable Glands for Unarmored Cables

1.97/
50

0.67/
17

0.24/6.2

0.24/6.2

0.23/
6

0.67/17

4 x M20

0.23/
6

0.23/
6

0.45/
11.5

0.24/6.2

4 x PG16

0.23/
6

4.92/125
0.24/6.2

5.35/136
Fix. 4.88/124

Enclosures and Junction Boxes

0.67/17

0.67/
17

1.97/
50

4.92/125

0.45/
11.5
5.35/136
Fix. 4.88/124

BJe1 without Cable Glands for Armored Cables

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

BJe2 without
Cable Glands for Armored Cables
2.10/
0.24/
6.2

BJe2 with Cable Glands for Unarmored Cables

53.3

2.15/
54.7

Fix. 83

2.83/72

2.15/54.7
4.25 x 108

4.72/120

Fix. 4.06/103

2.83/72

4.72/120

4.92 x 4.92 /
125 x 125

4.92 x 4.92 /
125 x 125

0.24/
6.2

2.15/54.7

7.28 x 7.28 / 185 x 185

4.72/120
JBEP Series

4.72/120
CSPe2

9.06/230

6.69/170

Fix. 5.24/133

Fix. 5.24/133

6.69/170
Fix. 83

4.72/120

Fix. 83

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Fix. 4.06/103

Fix. 4.06/103

4.72/120

Fix. 4.06/103

Fix. 4.06/103

3.58/91

4.72/120

Fix. 4.06/103

4.72/120

4.72/120

Fix. 4.06/103

4.72/120

Fix. 5.24/133

Fix. 7.60/193

9.06/230

6.69/170

4.72/120

Fix. 7.60/193

CSPe1

Fix. 4.06/103

527
9.06/230
Fix. 7.60/193

3.58/

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Enclosures and Junction Boxes

Applications

Pre-Drilled Junction Box without Terminals

•	 Terminal junction boxes designed to facilitate electrical
connections in hazardous areas.
•	 Designed for use in Zone 1 or 2 areas, where flammable gases or
vapors are present either continuously or intermittently such as:
	 — Petroleum
	 — Chemical
	 — Refineries
	 — Other industrial process facilities
•	 Ideal for wet or corrosive atmospheres.
•	 Designed for use in Zone 21 or 22 areas where flammable dusts
are present either continuously or intermittently such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Other commercial facilities

Pre-Drilled Junction Box Equipped with Terminals

Features
•	 Operating temperature -67 °F/-55 °C to 140 °F/60 °C (CSPe
type) and -40 °F/-40 °C to 131 °F/55 °C (CAe type).
•	 For use only with Ex certified terminal blocks.
•	 Factory drilled and equipped.

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Standard Materials
•	 Enclosure: static resistant carbon filled fiberglass reinforced
polyester (FRP)
•	 Hardware: stainless steel
•	 Label: yellow laminated plastic with black lettering

Options
•	 For use with other equipment than Ex terminal blocks, see
ECEP Series.

Certifications and Compliances
•	
	
	
	
	
	
	
	
	
	
	
	
	
•	
	
	
	
	
	
	
	
	
	
	
	
	

528

Certification Type CSPe
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II, Ex eia IIC, Ex eib IIC
– T Rating: T6
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T167 °F/T75 °C
— Ambient Temperature: -67 °F/-55 °C to 140 °F/60 °C
— CE Declaration of Conformity: 50284
— ATEX Certificate: LCIE 09 ATEX 3032X
— IECEx Certificate: IECEx LCI 09.0016X
Certification Type CAe
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II, Ex eia IIC, Ex eib IIC
– T Rating: T6 for Ta ≤ 104 °F /40 °C, T5 for 104 °F /40 °C
≤ Ta 131 °F /55 °C
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T176 °F to T203 °F / T80 °C to T95 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 50235
— ATEX Certificate: LCIE 02 ATEX 6248X
— IECEx Certificate: IECEx LCI 04.0016

•	
•	
•	
•	

Other Certifications: GOST
Ingress Protection (solid and liquid): IP66
Impact Resistance (shock): IK10
Ex Standards: EN/IEC 60079-0; 60079-7; 60079-11; 61241-0;
61241-1; 61241-11
•	 Other Standards: EN/IEC 60529 (IP), 62262 (IK)

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Catalog Numbering Guide
JBEP

12

12

Series
ATEX/IEC Certified:
JB - Junction Box
E - Increased Safety
I - Intrinsic Safety
P - Polyester

09

D1

Depth Dimensions in/mm:
09 - 3.58/91.0
15 - 5.91/150.0

Options:
D1 - 5 x M20
D2 - 4 x M20 + 1 x M25
D3 - 7 x M20 + 1 x M25
D5 - 7 x M20 + 1 x M25
D6 - 12 x M20 + 1 x M32
D7 - 19 x M20 + 1 x M32
D8 - 27 x M20 + 1 x M40
P _ _ - Unarmored Cable
A _ _ - Armored Cable
L _ _ - Lead Sheath Armored Cable
E - Earth Continuity Brass Plate
# - Customized Enclosure (6 Digit

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

number will be assigned
at time of order placement.)

Width Dimensions in/mm:
12 - 4.72/120.0
20 - 7.87/200.0

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes

Length Dimensions in/mm:
12 - 4.72/120.0
17 - 6.69/170.0
21 - 8.27/210.0
23 - 9.06/230.0
32 - 12.60/320.0
42 - 16.73/425.0
57 - 22.64/575.0

529

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Factory Drilled Ex e II Polyester Junction Boxes

Fitted with: one horizontal symmetrical zinc plated rail. For use with EX terminals only (not supplied). Yellow laminated plastic label with black lettering. Internal
earth terminal. Cable glands and plugs ordered separately.

Dimension
L x W x D in/mm

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Type

A
D

B

Rail Length
Capacity
in/mm

A

B

Clearance Holes Per Side
C

D

Weight
lb/kg

Volume
in3/dm3

Catalog
Number

CSPe1

4.72 x 4.72 x 3.58/
120 x 120 x 91

2.44/62.0

1 x M20

1 x M20

2 x M20 1 x M20 1.76/0.8

244/4

JBEP121209D1

CSPe2

6.69 x 4.72 x 3.58/
170 x 120 x 91

4.41/112.0

–

1 x M20

2 x M20
1 x M20 2.20/1.0
1 x M25

244/4

JBEP171209D2

CSPe3

9.06 x 4.72 x 3.58/
230 x 120 x 91

6.77/172.0

–

2 x M20

3 x M20
2 x M20 2.65/1.2
1 x M25

244/4

JBEP231209D3

C

Factory Drilled Exe II Instrumentation Polyester Junction Boxes

Fitted with: yellow laminated plastic label with black lettering. Set of two insulated side supports (096115). One horizontal symmetrical zinc plated rail. For use
with Ex terminals only (not supplied). Also available for use with copper bar 12 x 2 mm or 12 x 4 mm. 2 x 10 mm2 internal earth terminals. Cable glands and plugs
ordered separately.

Dimension
L x W x D in/mm

Type

A
D

B
C

Rail Length
Capacity
in/mm

Cable

4.13/105.0

Threaded Holes
Side C

Weight
lb/kg

Volume
in3/dm3

Catalog
Number

976/16

JBEP212015D5

CAe1

8.46 x 7.87 x 5.91/
215 x 200 x 150

7 Pairs

1 x M25

7 x M20

7.50/3.4

CAe2

12.60 x 7.87 x 5.91/
8.11/206.0 12 Pairs
320 x 200 x 150

1 x M32

12 x M20

9.26/4.2 1403/23 JBEP322015D6

CAe3

16.73 x 7.87 x 5.91/
12.20/310.0 19 Pairs
425 x 200 x 150

1 x M32

19 x M20

11.46/5.2 1586/26 JBEP422015D7

CAe4

22.64 x 7.87 x 5.91/
12.40/315.0 27 Pairs
575 x 200 x 150

1 x M40 †

27 x M20

15.00/6.8 2013/33 JBEP572015D8

Factory Assembled Ex Terminal Block for Junction Boxes Shown Above

Screwed/screwed terminal block fitted with continuity shield.

Cable

Terminals
0.0008/0.004 in2
0.5/2.5 mm2
Qty.

Continuity
Shield Qty.

8.46 x 7.87 x 5.91/
215 x 200 x 150

7 Pairs

14

7

0.66/0.3 30.5/0.5

096039

12.60 x 7.87 x 5.91/
320 x 200 x 150

12 Pairs

24

12

0.88/0.4 67.1/1.1

096041

16.73 x 7.87 x 5.91/
425 x 200 x 150

19 Pairs

38

19

1.10/0.5 79.3/1.3

096043

22.64 x 7.87 x 5.91/
575 x 200 x 150

27 Pairs

54

27

1.32/0.6 103.7/1.7

096044

For Junction Boxes
L x W x D in/mm

Weight
lb/kg

Volume
in3/dm3

Catalog
Number

† Clearance hole.

530

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Factory Drilled and Equipped with Terminals Ex e II Polyester Junction Boxes for
Instrumentation Applications with Unarmored Cables
Fitted with: horizontal beige terminal block. Copper bar with cable clamps or continuity shields. Yellow
laminated plastic label with black lettering. M16 to M32 threaded entries. M40 to M50 clearance holes.
Cable glands and plugs ordered separately.

Earth Terminal
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
1
1
1
1
1
1
1
1
1
1
1
1

Type
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4

For
Cable
EGSF
07IP05
07IT05
12IP05
12IT05
19IP05
27IP05
07IP09
07IT09
12IP09
12IT09
19IP09
27IP09

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
14
21
24
36
38
54
14
21
24
36
38
54

Type
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4

For
Cable
EISF
07IP05
07IT05
12IP05
12IT05
19IP05
27IP05
07IP09
07IT09
12IP09
12IT09
19IP09
27IP09

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
15
22
25
37
39
55
15
22
25
37
29
55

Copper Bar
0.39 x 0.12 in
10 x 3 mm
Qty.
1
1
1
1
1
1
1
1
1
1
1
1

Multi-cable Single Cable
Cable
Entries
Entry
M20
Qty. 1
Qty.
M20
3
M25
6
M25
9
M32
12
M32
13
M32
18
M20
3
M25
6
M32
9
M32
12
M32
13
M40
18

Catalog
Number
JBEP212015P01
JBEP212015P02
JBEP322015P03
JBEP322015P04
JBEP322015P05
JBEP422015P06
JBEP212015P07
JBEP212015P08
JBEP322015P09
JBEP322015P10
JBEP322015P11
JBEP422015P12

Continuity
Shield
Qty.
7
7
12
12
19
27
7
7
12
12
19
27

Multi-cable Single Cable
Cable
Entries
Entry
M16
Qty. 1
Qty.
M20
7
M20
7
M25
12
M25
12
M32
19
M32
27
M25
7
M25
7
M32
12
M32
12
M32
19
M40
27

Catalog
Number
JBEP212015P21
JBEP212015P22
JBEP322015P23
JBEP322015P24
JBEP422015P25
JBEP572015P26
JBEP212015P27
JBEP212015P28
JBEP322015P29
JBEP322015P30
JBEP422015P31
JBEP572015P32

Continuity
Shield
Qty.
8
8
13
13
20
28
8
8
13
13
20
28

Multi-cable Single Cable
Cable
Entries
Entry
M16
Qty. 1
Qty.
M25
7
M32
7
M32
12
M32
12
M40
19
M40
27
M32
7
M32
7
M40
12
M40
12
M50
19
M50
27

Catalog
Number
JBEP212015P41
JBEP212015P42
JBEP322015P43
JBEP322015P44
JBEP422015P45
JBEP572015P46
JBEP212015P47
JBEP212015P48
JBEP322015P49
JBEP322015P50
JBEP422015P51
JBEP572015P52

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Cable Clamp
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
5
8
11
14
15
20
5
8
11
14
15
20

531

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
7
12
19
24
27
37
7
12
19
24
27
37

Enclosures and Junction Boxes

Type
CAe1
CAe1
CAe2
CAe2
CAe2
CAe3
CAe1
CAe1
CAe2
CAe2
CAe2
CAe3

For
Cable
U1000
RO2V
07G1.5
12G1.5
19G1.5
24G1.5
27G1.5
37G1.5
07G2.5
12G2.5
19G2.5
24G2.5
27G2.5
37G2.5

Unarmored Cables

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Factory Drilled and Equipped with Terminals Ex e II Polyester Junction Boxes for
Instrumentation Applications with Armored Cables

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Fitted with: horizontal beige terminal block. Copper bar with cable clamps or continuity shields. Yellow
laminated plastic label with black lettering. Earth continuity brass plate. M8 external earth crossing
terminal. M20 to M32 threaded entries. M40 to M50 clearance holes. Cable glands and plugs ordered
separately.

Type
CAe1
CAe1
CAe2
CAe2
CAe2
CAe3
CAe1
CAe1
CAe2
CAe2
CAe2
CAe3

For
Cable
U1000
RVFV
07G1.5
12G1.5
19G1.5
24G1.5
27G1.5
37G1.5
07G2.5
12G2.5
19G2.5
24G2.5
27G2.5
37G2.5

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
7
12
19
24
27
37
7
12
19
24
27
37

Earth Terminal
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
1
1
1
1
1
1
1
1
1
1
1
1

Type
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4

For
Cable
EGFA
07IP05
07IT05
12IP05
12IT05
19IP05
27IP05
07IP09
07IT09
12IP09
12IT09
19IP09
27IP09

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
14
21
24
36
38
54
14
21
24
36
38
54

Type
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4

For
Cable
EIFA
07IP05
07IT05
12IP05
12IT05
19IP05
27IP05
07IP09
07IT09
12IP09
12IT09
19IP09
27IP09

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
15
22
25
37
39
55
15
22
25
37
39
55

532

Copper Bar
0.39 x 0.12"
10 x 3 mm
Qty.
1
1
1
1
1
1
1
1
1
1
1
1

Cable Clamp
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
5
8
11
14
15
20
5
8
11
14
15
20

Armored
Cables
Multi-cable
Cable
Entry
Qty. 1
M20
M20
M25
M25
M25
M32
M20
M25
M25
M32
M32
M32

Single Cable
Entries
M20
Qty.
3
6
9
12
13
18
3
6
9
12
13
18

Catalog
Number
JBEP212015A01E
JBEP212015A02E
JBEP322015A03E
JBEP322015A04E
JBEP322015A05E
JBEP422015A06E
JBEP212015A07E
JBEP212015A08E
JBEP322015A09E
JBEP322015A10E
JBEP322015A11E
JBEP422015A12E

Continuity
Shield
Qty.
7
7
12
12
19
27
7
7
12
12
19
27

Multi-cable
Cable
Entry
Qty. 1
M20
M20
M25
M25
M25
M32
M25
M25
M25
M32
M32
M40

Single Cable
Entries
M20
Qty.
7
7
12
12
19
27
7
7
12
12
19
27

Catalog
Number
JBEP212015A21E
JBEP212015A22E
JBEP322015A23E
JBEP322015A24E
JBEP422015A25E
JBEP572015A26E
JBEP212015A27E
JBEP212015A28E
JBEP322015A29E
JBEP322015A30E
JBEP422015A31E
JBEP572015A32E

Continuity
Shield
Qty.
8
8
13
13
20
28
8
8
13
13
20
28

Multi-cable
Cable
Entry
Qty. 1
M25
M25
M32
M32
M32
M40
M32
M32
M40
M40
M40
M50

Single Cable
Entries
M20
Qty.
7
7
12
12
19
27
7
7
12
12
19
27

Catalog
Number
JBEP212015A41E
JBEP212015A42E
JBEP322015A43E
JBEP322015A44E
JBEP422015A45E
JBEP572015A46E
JBEP212015A47E
JBEP212015A48E
JBEP322015A49E
JBEP322015A50E
JBEP422015A51E
JBEP572015A52E

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Factory Drilled and Equipped with Terminals Ex e II Polyester Junction Boxes for
Instrumentation Applications with Lead Sheath Armored Cables
Fitted with: horizontal beige terminal block. Copper bar with cable clamps or continuity shields. Yellow
laminated plastic label with black lettering. Earth continuity brass plate. M8 external earth crossing
terminal. M20 to M32 threaded entries. M40 to M50 clearance holes. Cable glands and plugs ordered
separately.

Earth Terminal
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
1
1
1
1
1
1
1
1
1
1
1
1

Type
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4

For
Cable
EGPF
07IP05
07IT05
12IP05
12IT05
19IP05
27IP05
07IP09
07IT09
12IP09
12IT09
19IP09
27IP09

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
14
21
24
36
38
54
14
21
24
36
38
54

Type
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4
CAe1
CAe1
CAe2
CAe2
CAe3
CAe4

For
Cable
EIPF
07IP05
07IT05
12IP05
12IT05
19IP05
27IP05
07IP09
07IT09
12IP09
12IT09
19IP09
27IP09

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
15
22
25
37
39
55
15
22
25
37
39
55

Copper Bar
0.39 x 0.12"
10 x 3 mm
Qty.
1
1
1
1
1
1
1
1
1
1
1
1

Multi-cable
Cable
Entry
Qty. 1
M20
M25
M25
M32
M32
M32
M20
M25
M32
M32
M32
M40

Single Cable
Entries
M20
Qty.
3
6
9
12
13
18
3
6
9
12
13
18

Catalog
Number
JBEP212015L01E
JBEP212015L02E
JBEP322015L03E
JBEP322015L04E
JBEP322015L05E
JBEP422015L06E
JBEP212015L07E
JBEP212015L08E
JBEP322015L09E
JBEP322015L10E
JBEP322015L11E
JBEP422015L12E

Continuity
Shield
Qty.
7
7
12
12
19
27
7
7
12
12
19
27

Multi-cable
Cable
Entry
Qty. 1
M20
M20
M25
M25
M25
M32
M25
M25
M32
M32
M40
M40

Single Cable
Entries
M20
Qty.
7
7
12
12
19
27
7
7
12
12
19
27

Catalog
Number
JBEP212015L21E
JBEP212015L22E
JBEP322015L23E
JBEP322015L24E
JBEP422015L25E
JBEP572015L26E
JBEP212015L27E
JBEP212015L28E
JBEP322015L29E
JBEP322015L30E
JBEP422015L31E
JBEP572015L32E

Continuity
Shield
Qty.
8
8
13
13
20
28
8
8
13
13
20
28

Multi-cable
Cable
Entry
Qty. 1
M25
M32
M32
M32
M40
M50
M32
M32
M40
M40
M50
M50

Single Cable
Entries
M20
Qty.
7
7
12
12
19
27
7
7
12
12
19
27

Catalog
Number
JBEP212015L41E
JBEP212015L42E
JBEP322015L43E
JBEP322015L44E
JBEP422015L45E
JBEP572015L46E
JBEP212015L47E
JBEP212015L48E
JBEP322015L49E
JBEP322015L50E
JBEP422015L51E
JBEP572015L52E

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Cable Clamp
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
5
8
11
14
15
20
5
8
11
14
15
20

533

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Terminal Block
0.0008/0.004 in2
0.5/2.5 mm2
Qty.
7
12
19
24
27
37
7
12
19
24
27
37

Enclosures and Junction Boxes

Type
CAe1
CAe1
CAe2
CAe2
CAe2
CAe3
CAe1
CAe1
CAe2
CAe2
CAe2
CAe3

For
Cable
U1000
RGPFV
07 x 1.5
12 x 1.5
19 x 1.5
24 x 1.5
27 x 1.5
37 x 1.5
07 x 2.5
12 x 2.5
19 x 2.5
24 x 2.5
27 x 2.5
37 x 2.5

Armored Cables
With lead sheath

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety
Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Defining maximum terminal block quantity according to power dissipation:
•	 Junction boxes used for instrumentation applications carry very low current levels. Therefore there is no risk of overheating whatever the
number of terminals inside the box.
•	 For applications other than instrumentation, the following tables allow you to define your junction box depending on the number of terminals
and the maximum authorized current being carried.

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

For other terminal block configurations, please consult our drilling guide available online at: www.egsatx.com.

T Rating:
T6

CSPe1
5 x 5 x 4"/
120 x 120 x
91 mm

Type
CSPe2
7 x 5 x 4"/
120 x 170 x
91 mm

CSPe3
9 x 5 x 4"/
120 x 230 x
91 mm

0.004 in2/ Qty.
2.5 mm2 1 max.

12
15 A

22
13 A

33
12 A

0.004 in2/
2.5 mm2

Qty.
1 max.

20
16 A

21
16 A

23
16 A

29
14 A

0.006 in2/ Qty.
4 mm2 1 max.

10
20 A

18
19 A

28
16 A

0.006 in2/
4 mm2

Qty.
1 max.

19
20 A

20
20 A

23
20 A

33
16 A

0.009 in2/ Qty.
6 mm2 1 max.

7
32 A

14
27 A

21
24 A

0.009 in2/
6 mm2

Qty.
1 max.

12
32 A

13
32 A

14
32 A

18
28 A

0.016 in2/ Qty.
10 mm2 1 max.

4
50 A

6
50 A

8
50 A

0.016 in2/
10 mm2

Qty.
1 max.

10
40 A

11
40 A

18
32 A

22
28 A

0.024 in2/
16 mm2

Qty.
1 max.

8
28 A

10
27 A

13
25 A

15
26 A

0.039 in2/
25 mm2

Qty.
1 max.

8
67 A

8
73 A

10
69 A

10
70 A

0.054 in2/
35 mm2

Qty.
1 max.

8
79 A

8
86 A

10
80 A

10
80 A

534

Type
CAe1
CAe2
CAe3
CAe4
T Rating:
8 x 9 x 6"/ 8 x 13 x 6"/ 8 x 17 x 6"/ 8 x 23 x 6"/
T6 @ Ta 104 °F/40 °C 200 x 215 x 200 x 320 x 200 x 425 x 200 x 575 x
T5 @ Ta 131 °F/55° C
150 mm
150 mm
150 mm
150 mm

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP Series Pre-Drilled Fiberglass Reinforced Polyester Junction Boxes

Increased Safety

Dimension in Inches/Millimeters *

CSPe2

CSPe3
3.58/91
4.72/120

4.72/120

Fix. 4.06/103

9.06/230

9.06/230

Fix. 7.60/193

Fix. 7.60/193

6.69/170

6.69/170

Fix. 4.06/103
Fix. 4.06/103Fix. 4.06/103

Fix. 5.24/133

4.72/120

Fix. 5.24/133

Fix. 83
6.69/170

4.72/120

Fix. 83

4.72/120

Fix. 83

4.72/120

3.58/91

Enclosures and Junction Boxes

4.72/120

4.72/120

3.58/91

4.72/120

4.72/120

Fix. 5.24/133
9.06/230

4.72/120

4.72/120

Fix. 7.60/193

CSPe1

Fix. 4.06/103Fix. 4.06/103

Fix. 4.06/103
Fix. 4.06/103Fix. 4.06/103

CAe1 to CAe4

A

External
B

C

D

Internal
E

F

G

Fixings
H

Thick

CAe1

7.87/200

8.46/215

5.91/150

7.28/185

7.87/200

4.92/125

5.75/146

7.44/189

0.24/6

Ø
0.28/7

CAe2

7.87/200

12.60/320

5.91/150

7.28/185

12.01/305

4.92/125

5.75/146

11.57/294

0.24/6

0.28/7

CAe3

7.87/200

425/16.73

5.91/150

7.28/185

16.14/410

4.92/125

5.75/146

15.71/399

0.24/6

0.28/7

CAe4

7.87/200

22.64/575

5.91/150

7.28/185

22.05/560

4.92/125

5.75/146

21.57/548

0.24/6

0.28/7

* Fixing details for all types: four holes Ø 0.20"/5 mm.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

535

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Type

PJB Series Polyester Nonmetallic Enclosures
cCSAus Certification

CEC/NEC:
Zone 1 and 2 A/Exe IIC T6 to T3
Enclosure: IP66

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Applications
•	 Terminal, junction box enclosure for various electrical devices.
•	 Designed for use in Zone 1 or 2 areas, where flammable gases
or vapors are present either continuously or intermittently, such
as:
	 — Petroleum refineries
	 — Chemical refineries
	 — Other industrial process facilities
•	 Ideal for wet or corrosive atmospheres.
•	 Designed for use in Zone 21 or 22 areas (international),
where flammable dusts are present either continuously or
intermittently, such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Other commercial facilities

Features
•	 Static resistant black fiberglass reinforced polyester enclosure.
•	 Five different sizes to choose from
•	 Available in three depths, 7.87"/200 mm, 9.84"/250 mm and
11.81"/300 mm.
•	 Enclosures can be coupled together for added space.
•	 Protective Flange at top and bottom.
•	 Pad lockable double bar locks, Key supplied.
•	 Operating temperature -40 °F/-40 °C to +131 °F/+55 °C.
•	 Poured in place polyurethane door gasket.
•	 Many optional accessories.

Standard Materials
•	 Enclosure: static resistant carbon filled fiberglass reinforced
polyester (FRP)
•	 Hardware: 316L stainless steel

Options or Accessories
•	
•	
•	
•	
•	
•	
•	
•	
•	
•	
•	
•	
•	
•	

536

Mounting Pan.
Gland Plates.
Interior side rails.
Din Rails.
Side Rail and Din rail assembly.
See table for several terminal block options and limitations.
Supplied installed in enclosure. Other terminal block
configurations available. Contact your local sales representative.
Ground bars.
Terminals for Ground bar.
Terminal spacers, 3.94"/100 mm or 1.97"/50 mm.
Padlocking Device.
Factory drilled entries.
Earth Continuity Plate.
Terminal Blocks, see following pages for a guide. Many other
configurations and combinations available, contact your local
sales representative.
Enclosure coupling kit, contact your local sales representative.

Certifications and Compliances
•	
	
	
	
	
	
•	
	
	
	
	
	
	
	
	
	

North America
— CEC/NEC
— cCSAus Approved
— Zone 1 and 2 A/Exe IIC T6 to T3 depending on equipment.
— Enclosure IP66
— 600 Vac/400 Amp Max
International
— EEx e II/EEx ei
— Type CAe
— CENELEC LCIE 02 ATEX 6248X
— IEC LCIE Ex 02.032X
— IP66 to EN60529 and IEC 60529
— IK10 to EN 50102
— Combustible Dust EN 50281-1-1
— CE Declaration of Conformity No. 50201
— Zone 1, 2, 21, 22

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

PJB Series Polyester Nonmetallic Enclosures
cCSAus Certification

CEC/NEC:
Zone 1 and 2 A/Exe IIC T6 to T3
Enclosure: IP66

Catalog Numbering Guide

Confirm size and gland plate availability in below table.

PJB

40

30

Series

20

0

N

Depth Dimensions in/mm:
09 - 3.58/91.0
15 - 5.91/150.0
20 - 7.87/200.0
25 - 9.84/250.0
30 - 11.81/300.0

010

Earth Continuity Plate:
N - None
E - Supplied

Gland Plates:
0 - none
1 - one bottom
3 - two sides and bottom

Terminal Block
Size in/mm:
25 - 0.10/2.5
04 - 0.16/4.0
06 - 0.24/6.0
10 - 0.39/10.0
16 - 0.63/16.0
35 - 1.378/35.0

Mounting Pan:
N - None
P - Mounting pan

Terminal Block
Quantity:
010 - 10
050 - 50
100 - 100

Confirm Size and Gland Plate Availability
Possible Gland Plates
0
1
3

Height

Dimensions in Inches/Millimeters
Width
Depth

Volume
in3/dm3

Weight
lb/kg

Catalog
Number

x

x

x

15.78/400

11.81/300

7.87/200

1526/25

10.58/4.8

PJB403020

x

x

x

19.68/500

15.78/400

7.87/200

3112/51

13.67/6.2

PJB504020

x

x

x

23.62/600

15.78/400

9.84/250

4882/80

16.98/7.7

PJB604025

x

x

x

31.50/800

23.62/600

11.81/300

11595/190

40.34/18.3

PJB806030

x

x

x

39.37/1000

31.50/800

11.81/300

19100/313

52.03/23.6

PJB108030

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

537

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Width Dimensions in/mm:
12 - 4.72/120.0
20 - 7.87/200.0
30 - 11.81/300.0
40 - 15.75/400.0
60 - 23.62/600.0
80 - 31.50/800.0

25

Enclosures and Junction Boxes

Length Dimensions in/mm:
12 - 4.72/120.0
17 - 6.69/170.0
21 - 8.27/210.0
23 - 9.06/230.0
32 - 12.60/320.0
40 - 15.75/400.0
42 - 16.75/425.0
50 - 19.68/500.0
57 - 22.50/575.0
60 - 23.62/600.0
80 - 31.50/800.0
10 - 39.37/1000.0

N

PJB Series Polyester Nonmetallic Enclosure Terminal Blocks
cCSAus Certification

CEC/NEC:
Zone 1 and 2 A/Exe IIC T6 to T3
Enclosure: IP66

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Maximum Terminal Block Information
Number
Rails

Terminal
Size in/mm

Qty Max *
Physical

Terminal
Amp

Qty Max
At Max. Amps

Terminal
Amp

Catalog
Number

3

0.10/2.5

100

5

22

15

PJB403020

3

0.16/4

75

10

20

20

PJB403020

2

0.24/6

36

15

12

30

PJB403020

4

0.16/4

100

10

30

20

PJB504020

4

0.24/6

76

15

18

30

PJB504020

3

0.39/10

64

20

18

40

PJB504020

4

0.24/6

136

12

27

30

PJB604025

4

0.39/10

112

16

25

40

PJB604025

4

0.63/16

88

20

24

50

PJB604025

6

0.39/10

190

14

27

40

PJB806030

5

0.63/16

190

15

24

50

PJB806030

4

1.38/35

124

30

16

90

PJB806030

7

0.63/16

364

12

28

50

PJB108030

5

1.38/35

218

20

20

90

PJB108030

3

2.76/70

84

40

9

145

PJB108030

Small Junction Boxes
Type

PJB121209
5 x 5 x 4”/120 x 120 x 91 mm

PJB171209
7 x 5 x 4”/120 x 170 x 91 mm

PJB231209
9 x 5 x 4”/120 x 230 x 91 mm

Quantity

Maximum Amps

12

15 A

10

20 A

7

32 A

4

50 A

22

13 A

18

19 A

14

27 A

6

50 A

33

12 A

28

16 A

21

24 A

8

50 A

* Maximum physical at amperage indicated, capable of accepting more terminals at lower amperage. Contact your local sales representative.
To order terminal blocks: Use nomenclature above. Supplied installed on a mounting pan. Can be installed on uprights and rails. Contact your local sales
representative.

538

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

PJB Series Polyester Nonmetallic Enclosure Accessories
cCSAus Certification

Accessories and Options — Order as follows for field installed
Dimensions in Inches/Millimeters
Length

Catalog
Number

15.78/400

13.27/337

PJBSR400

19.68/500

17.20/437

PJBSR500

23.62/600

21.14/537

PJBSR600

Height
Interior Side Rails/Uprights — Set of 2 — Supplied in Packages of 5

29.02/737

PJBSR800

36.89/937

PJBSR100

For Enclosure

Crosspiece

Catalog
Number

11.81/300

9.57/243

PJBDR300

Width in Inches/Millimeters
Cross Piece Din Rails — Set of 10

13.50/343

PJBDR400

21.38/543

PJBDR600

31.50/800

29.25/743

PJBDR800

Dimensions in Inches/Millimeters
Enclosure H x W
HxW

Weight
lb/kg

Catalog
Number

Perforated Mounting Plate — To Order Separately
15.78/400 x 300

13.78/350 x 9.84/250

2.65/1.2

PJBMP400

19.68/500 x 15.75/400

17.72/450 x 13.78/350

2.43/1.1

PJBMP500

23.62/600 x 15.75/400

21.65/550 x 13.78/350

3.31/1.5

PJBMP600

31.50/800 x 23.62/600

29.53/750 x 21.65/550

6.61/3.0

PJBMP800

39.37/1000 x 31.50/800

37.40950 x 29.53/750

12.13/5.5

PJBMP100

Volume
in3/dm3

Weight
lb/kg

Catalog
Number

5.12/130 x 10.39/264

79/1.3

0.66/0.3

PJBGP130

4.49/114 x 12.68/322

85/1.4

0.88/0.4

PJBGP114

Dimension
H x W in/mm
Gland Plates — To Order Separately

Door Padlocking Device
PJBPL

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

539

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

15.78/400
23.62/600

Enclosures and Junction Boxes

31.50/800
39.37/1000

PJB Series Polyester Nonmetallic Enclosures
cCSAus Certification

CEC/NEC:
Zone 1 and 2 A/Exe IIC T6 to T3
Enclosure: IP66

JBEP Series for Terminal Junction Box Application Only.
The size of the junction box needed to meet your requirements can be selected based on the table shown below.

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

1. Define maximum cable entries according to number of modules available per side.
Cable Entry Metric Thread

Number of Modules

M20

1

M25

1

M32

1

M40

2

M50

3

Type

Length

Dimensions in/mm
Width

H

Depth

B/D

Number of Modules
A/C

A’/C’ (1)

Allowable
Max. Size

Terminal Dim.
H — in/mm

PJB121209

4.72/120

4.72/120

3.58/91

2

2

–

M25

4.72/120

PJB171209

6.69/170

4.72/120

3.58/91

3

2

–

M32

4.72/120

PJB231209

9.06/230

4.72/120

3.58/91

4

2

–

M32

4.72/120

PJB212015

8.46/215

7.87/200

5.91/150

11

8

–

M50

7.87/200

PJB322015

12.60/320

7.87/200

5.91/150

18

8

–

M50

7.87/200

PJB422015

16.73/425

7.87/200

5.91/150

26

8

–

M50

7.87/200

PJB572015

22.64/575

7.87/200

5.91/150

38

8

–

M50

7.87/200

PJB403020

15.75/400

11.81/300

8.11/206

18

18

–

M50

15.75/400

PJB504020

19.68/500

15.75/400

8.11/206

24

10

10

M50

19.68/500

PJB604025

24.02/610

15.75/400

10.12/257

48

10

10

M75

24.02/610

PJB806030

32.28/820

24.02/610

11.81/300

72

54

–

M100

32.28/820

PJB108030

40.16/1020

31.89/810

11.81/300

96

78

–

M100

40.16/1020

2. Maximum rail arrangement according to physical dimensions.
Maximum Quantity of Horizontal Rails Per Quantity
Terminal Capacity

540

(in2/mm2)

0.004/2.5

0.006/4

0.009/6

0.016/10

0.025/16

0.054/35

0.078/50

PJB 12/17/23 1209

1

1

1

1

0

0

0

PJB 21/32/42/57 2015

1

1

1

1

1

1

0

PJB403020

3

3

3

2

2

2

1

PJB504020

4

4

3

3

3

2

1

PJB604025

4

4

4

4

3

3

2

PJB806030

6

6

5

5

5

4

3

PJB108030

8

8

7

7

6

5

3

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

PJB Series Polyester Nonmetallic Enclosures
cCSAus Certification

CEC/NEC:
Zone 1 and 2 A/Exe IIC T6 to T3
Enclosure: IP66

3. Defining maximum terminal block quantity according to power dissipation:
•	 Junction boxes used for instrumentation applications have very low current levels, therefore there is no risk of overheating whatever the
number of terminals inside the box.
•	 For applications other than instrumentation, the following tables allow you to define your junction box depending on the number of terminals
and the maximum authorized current being carried with feed-through terminals.
•	 For single feed terminals using cross connection, please consult your local representative for a calculation.
For other terminal block configurations, please consult our drilling guide available online at: www.appletonelec.com.

Small Junction Boxes
Type
PJB121209
PJB171209
PJB231209
5 x 5 x 4"/
7 x 5 x 4"/
9 x 5 x 4"/
120 x 120 x 91 120 x 170 x 91 120 x 230 x 91
mm
mm
mm

Type
PJB212015 PJB322015 PJB422015 PJB572015
T Rating:
8 x 9 x 6"/ 8 x 13 x 6"/ 8 x 17 x 6"/ 8 x 23 x 6"/
T6 @ Ta 104 °F/40 °C 200 x 215 x 200 x 320 x 200 x 425 x 200 x 575 x
T5 @ Ta 131 °F/55° C
150 mm
150 mm
150 mm
150 mm

12
15 A

22
13 A

33
12 A

0.004 in2/
2.5 mm2

Qty.
1 max.

20
16 A

21
16 A

23
16 A

29
14 A

0.006 in2/ Qty.
4 mm2 1 max.

10
20 A

18
19 A

28
16 A

0.006 in2/
4 mm2

Qty.
1 max.

19
20 A

20
20 A

23
20 A

33
16 A

0.009 in2/ Qty.
6 mm2 1 max.

7
32 A

14
27 A

21
24 A

0.009 in2/
6 mm2

Qty.
1 max.

12
32 A

13
32 A

14
32 A

18
28 A

0.016 in2/ Qty.
10 mm2 1 max.

4
50 A

6
50 A

8
50 A

0.016 in2/
10 mm2

Qty.
1 max.

10
40 A

11
40 A

18
32 A

22
28 A

0.024 in2/
16 mm2

Qty.
1 max.

8
28 A

10
27 A

13
25 A

15
26 A

0.039 in2/
25 mm2

Qty.
1 max.

8
67 A

8
73 A

10
69 A

10
70 A

0.054 in2/
35 mm2

Qty.
1 max.

8
79 A

8
86 A

10
80 A

10
80 A

Hinged Junction Boxes

PJB403020
T Rating:
16 x 12 x 8"/
T6 @ Ta 104 °F/40 °C 400 x 300 x
T5 @ Ta 131 °F/55° C
206 mm

Type
PJB504020
PJB604025
PJB806030
PJB108030
20 x 16 x 8"/ 24 x 16 x 10"/ 32 x 24 x 12"/ 40 x 32 x 12"/
500 x 400 x
610 x 400 x
820 x 610 x 1020 x 810 x
206 mm
257 mm
300 mm
300 mm

0.054 in2/ Qty.
35 mm2 1 Max.

12
100 A

16
100 A

16
100 A

—

—

0.078 in2/ Qty.
50 mm2 1 Max.

8
125 A

12
125 A

16
125 A

—

—

0.109 in2/ Qty.
70 mm2 1 Max.

8
160 A

10
160 A

12
160 A

—

—

0.147 in2/ Qty.
95 mm2 1 Max.

8
200 A

10
200 A

12
200 A

—

—

0.186 in2/ Qty.
120 mm2 1 Max.

—

8
250 A

8
250 A

12
200 A

16
150 A

0.233 in2/ Qty.
150 mm2 1 Max.

—

—

6
250 A

9
250 A

12
190 A

0.287 in2/ Qty.
185 mm2 1 Max.

—

—

—

8
300 A

10
240 A

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

541

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

0.004 in2/ Qty.
2.5 mm2 1 max.

Enclosures and Junction Boxes

T Rating:
T6

Non-Hinged Junction Boxes

PJB Series Polyester Nonmetallic Enclosure Dimensions
cCSAus Certification

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Dimensions in Inches/Millimeters

Catalog
Number

A

B

External
C

D

E

F

Fitting
G

PJB403020

15.94/405

12.01/305

7.87/200

8.46/215

7.09/180

12.83/326

13.23/336

PJB504020

19.68/500

15.78/400

7.87/200

8.46/215

7.09/180

16.73/425

18.31/465

PJB604025

23.62/600

15.78/400

9.84/250

10.43/265

9.06/230

16.73/425

22.28/566

PJB806030

32.60/828

24.33/618

11.81/300

12.40/315

11.02/280

25.91/658

30.24/768

PJB108030

40.47/1028

32.20/818

11.81/300

12.40/315

11.02/280

33.78/858

38.11/968

542

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP and ECEP Series Undrilled Fiberglass Reinforced Polyester Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Applications

•	 Available in a wide range of sizes.
•	 Operating temperature -67 °F/-55 °C to 140 °F/60 °C (CSPe)
and -40 °F/-40 °C to 131 °F/55 °C (CAe).
•	 Hinges standard on all sizes above
15.75 x 11.81" / 400 x 300 mm.
•	 Hinged enclosures:
	 — Reversible door opening 180°.
	 — Door with double bar lock.
	 — Key locking facility.
	 — Protective flange at top and bottom.

Standard Materials
•	 Enclosures: static resistant carbon filled fiberglass reinforced
polyester (FRP)
•	 Hardware: stainless steel

Accessories
•	
•	
•	
•	
•	

Mounting pan.
Rail mounting.
Padlocking device.
Inside pocket for documents.
Refer to technical data to define permitted number and size of
terminals and cable entries.

Options
•	
•	
•	
•	

Removable gland plates.
Nameplates.
Consult factory for custom drilling and assembly requirements.
Empty enclosure with Ex “U” component marking for
re-certification by notified body for CAe type.

Certifications and Compliances
•	 Certification Type CSPe
	 — Gas, Zones 1 and 2
II 2 G
	
– Conforming to ATEX 94/9/CE: CE 0081
	
– ATEX/IEC Protection: Ex e II, Ex ia IIC, Ex ib IIC, Ex de IIC,
Ex demb IIC
	
– T Rating: T6
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

CAe Type – Non-Hinged Version

CAe Type – Hinged Versions

	
	
	
	
	
	
	
	
	
•	
	
	
	
	
	
	
	
	
	
	
	
	
	
•	
	
	
	
	
	
	
	
	
	
	
•	
•	
•	
•	

— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T167 °F/T75 °C
— Ambient Temperature: -67 °F/-55 °C to 140 °F/60 °C
— CE Declaration of Conformity: 50284
— ATEX Certificate: LCIE 09 ATEX 3032X
— IECEx Certificate: IECEx LCI 09.0016X
— Other Certifications: GOST
Certification Type CAe
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II, Ex ia IIC, Ex ib IIC, Ex de IIC,
Ex demb IIC
– T Rating: T6 to T2
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T176 °F to T203 °F / T80 °C to T95 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 50235
— ATEX Certificate: LCIE 02 ATEX 6248X
— IECEx Certificate: IECEx LCI 04.0016
— Other Certifications: GOST
Certification Type CAe U
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II,
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 5C241
— ATEX Certificate: LCIE 09 ATEX 3036 U
— IEC Certificate: LCIE Ex 09.002 U
Ingress Protection (solid and liquid): IP66
Impact Resistance (shock): IK10
Ex Standards: EN/IEC 60079-0; 60079-1; 60079-7; 60079-11,
61241-0; 61241-1; 61241-11
Other Standards: EN/IEC 60529 (IP), 62262 (IK)

543

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Features

CSPe Type – Small Version

Enclosures and Junction Boxes

•	 Designed for use in Zone 1 or 2 areas, where flammable gases or
vapors are present either continuously or intermittently such as:
	 — Petroleum
	 — Chemical
	 — Refineries
	 — Other industrial process facilities
•	 Ideal for wet or corrosive atmospheres.
•	 Designed for use in Zone 21 or 22 areas where flammable dusts
are present either continuously or intermittently such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Other commercial facilities
•	 JBEP Series
— Terminal junction boxes for electrical low voltage and
instrumentation connections in hazardous areas.
— Refer to technical data to define permitted number of
terminal blocks and cable entries on selected junction boxes.
•	 ECEP Series
— Enclosure for distribution and control applications. Can
be modified at our manufacturing facility to house a large
range of components; i.e. control units, switches, breakers,
transformers, meters, etc.

JBEP and ECEP Series Undrilled Fiberglass Reinforced Polyester Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Catalog Numbering Guide
JBEP

12

12

Series
ATEX/IEC Certified:
EC - Enclosure and Controls
JB - Junction Box
E - Increased Safety
I - Intrinsic Safety
P - Polyester

09

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

0

Depth Dimensions in/mm:
09 - 3.58/91.0
15 - 5.91/150.0
20 - 7.87/200.0
25 - 9.84/250.0
30 - 11.81/300.0

Length Dimensions in/mm:
12 - 4.72/120.0
17 - 6.69/170.0
21 - 8.27 /210.0
23 - 9.06 /230.0
32 - 12.60 /320.0
40 - 15.75 /400.0
42 - 16.73 /425.0
50 - 19.68 /500.0
57 - 22.64 /575.0
60 - 23.62 /600.0
80 - 31.50 /800.0
10 - 39.37 /1000.0
Width Dimensions in/mm:
12 - 4.72/120.0
20 - 7.87/200.0
30 - 11.81/300.0
40 - 15.75/400.0
60 - 23.62/600.0
80 - 31.50/800.0

544

0

Gland plate for
hinged enclosures only:
0 - None
1 - One Bottom
2 - One Top and Bottom
3 - Two Sides and Bottom
4 - All Sides

Options:

(options must be listed
alphabetically)

E - Earth Continuity Brass Plate
M - Mounting Pan
U - Component Certification “U”
# - Customized Enclosure
(6 Digit number will be assigned
at time of order placement.)

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP Series Undrilled Fiberglass Reinforced Polyester Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

JBEP Series
Dimension
L x W x D in/mm

Type

Rail Length
Capacity in/mm

Weight
lb/kg

Volume
in3/dm3

Catalog
Number

Exe II Small Polyester Junction Boxes

For use with Ex certified terminals only (not supplied). Mounting rails supplied. Yellow laminated plastic label with black lettering.

CSPe1

4.72 x 4.72 x 3.58 / 120 x 120 x 91

2.44/62.0

1.76/0.8

244/4

JBEP1212090

CSPe2

6.69 x 4.72 x 3.58 / 170 x 120 x 91

4.41/112.0

2.20/1.0

244/4

JBEP1712090

CSPe3

9.06 x 4.72 x 3.58 / 230 x 120 x 91

6.77/172.0

2.65/1.2

244/4

JBEP2312090

For use with Ex terminals only (not supplied). Mounting rails to be ordered separately. Yellow laminated plastic label with black lettering.

CAe1

8.47 x 7.87 x 5.91 / 215 x 200 x 150

7.52/191.0

6.61/3.0

793/13

JBEP2120150

CAe2

12.60 x 7.87 x 5.91 / 320 x 200 x 150

11.54/293.0

8.38/3.8

1404/23

JBEP3220150

CAe3

16.73 x 7.87 x 5.91 / 425 x 200 x 150

15.75/400.0

10.80/4.9

1587/26

JBEP4220150

CAe4

22.64 x 7.87 x 5.91 / 575 x 200 x 150

21.81/554.0

13.67/6.2

2014/33

JBEP5720150

Exe II Hinged Junction Boxes without Gland Plate

Enclosures and Junction Boxes

Exe II Non-Hinged Junction Boxes

For use with Ex terminals only (not supplied). Mounting pan and rails to be ordered separately.

15.75 x 11.81 x 8.11 / 400 x 300 x 206

9.57/243.0

9.70/4.4

2014/33

JBEP4030200

CAe7

19.68 x 15.75 x 8.11 / 500 x 400 x 206

13.50/343.0

11.68/5.3

2868/47

JBEP5040200

CAe8

24.02 x 15.75 x 10.12 / 610 x 400 x 257

13.50/343.0

17.00/7.7

5126/8.4 JBEP6040250

CAe10

32.28 x 24.02 x 11.81 / 820 x 610 x 300

21.38/543.0

40.34/18.3 11595/190 JBEP8060300

CAe11

40.16 x 31.89 x 11.81 / 1020 x 810 x 300

29.25/743.0

52.03/23.6 19100/313 JBEP1080300

Exe II Hinged Junction Boxes with Bottom Opening for Gland Plate

For use with Ex terminals only (not supplied). Opening at bottom 4.49 x 12.68 in / 114 x 322 mm. Mounting pan, rails and gland plate to be ordered separately.

CAe7

19.68 x 15.75 x 8.11 / 500 x 400 x 206

13.50/343.0

11.68/5.3

2868/47

JBEP5040201

CAe8

24.02 x 15.75 x 10.12 / 610 x 400 x 257

13.50/343.0

17.00/7.7

5126/84

JBEP6040251

Description

Size in/mm

Drilling

Weight
lb/kg

Volume
in3/dm3

Gland Plate

4.49 x 12.68 / 114 x 322

Blank

3.09/1.4

24.41/0.4 JBEPGP400

Gland Plate

4.49 x 12.68 / 114 x 322

Clearance holes for
17 x M20 + 3 x M25

3.09/1.4

24.41/0.4 JBEPGP400D12

Gland Plate

5.12 x 10.39 / 130 x 264 †

Blank

2.87/1.3

18.31/0.3 JBEPGP300

Description

Size in/mm

Weight
lb/kg

Coupling
Flange

4.49 x 12.68 / 114 x 322

2.87/1.3

Removable Gland Plate
Catalog
Number

Coupling Flange
Volume
in3/dm3

Catalog
Number

12.20/0.2 JBEP CF1

† To be used with customized enclosure CAe6.

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

545

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

CAe6

ECEP Series Undrilled Fiberglass Reinforced Polyester Enclosure Accessories

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

Zinc Plated Symetrical Steel Rail

Enclosure Type
CAe1
CAe2

11.54/293

JBEPDR320

1

15.75/400

JBEPDR425

1

CAe4

21.81/554

JBEPDR575

1

CAe6

9.57/243

JBEPDR300

1

CAe7 / CAe8

13.50/343

JBEPDR400

1

Zinc Plated Symetrical Steel Rail

Enclosures and Junction Boxes

Zinc Plated Steel Uprights —
­ Set of Two

CAe10

21.38/543

JBEPDR600

1

CAe11

29.25/743

JBEPDR800

1

CAe6

13.27/337

JBEPSR400

1

CAe7

17.20/437

JBEPSR500

1

CAe8

21.14/537

JBEPSR600

1

CAe10

29.02/737

JBEPSR800

1

JBEPSR100

1

CAe11

36.89/937
Bar Length in/mm
6.30/160

Copper Bar (0.47 x 0.16" / 12 x 4 mm)
Copper bar not perforated for cable clamps.

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Catalog Number Pack
JBEPDR215 1

CAe3

For direct fixing. Set of two 2.36"/60 mm height
spacers supplied.

For fixing onto uprights with clip nut supplied.

Rail Length in/mm
7.52/191

Catalog Number Pack
097270
1

7.87/200

097271

1

12.20/310

097272

1

19.68/500

097273

1

27.17/690

097274

1

42.13/1070

097275

1

0.002 to 0.006 in2 / 1.5 mm2 to 4 mm2 capacity.

097203

1

0.009 to 0.025 in2 / 6 mm2 to 16 mm2 capacity.

097204

1

096115

1

Cable Clamp for Copper Bar (0.47 x 0.16" / 12 x 4 mm)

Insulated Side Support – Set of Two
For mounting symmetrical, asymmetrical rails and copper bar
0.47 x 0.08" / 12 x 2 mm or 0.47 x 0.16" / 12 x 4 mm.
See dimensional data page for more details.

Mounting Pan
Perforated mounting pan “Telequick”.

Enclosure Type
Dimensions in/mm
Catalog Number Pack
CAe6
13.78 x 9.84 / 350 x 250
JBEPMP400 1
CAe7

17.72 x 13.78 / 450 x 350

JBEPMP500

1

CAe8

21.65 x 13.78 / 550 x 350

JBEPMP600

1

CAe10

29.53 x 21.65 / 750 x 550

JBEPMP800

1

CAe11

37.40 x 29.53 / 950 x 750

JBEPMP100

1

External dimensions: 10 x 6" / 260 x 165 mm.
Internal dimensions: 9 x 5 x 1" / 230 x 130 x 18 mm.

097263

1

External dimensions: 13 x 9" / 340 x 235 mm.
Internal dimensions: 12 x 8 x 1" / 310 x 200 x 18 mm.

097264

1

JBEPPL

1

Self Adhesive Pocket for Drawings

Padlocking Device.
Takes 3 safety padlocks shackle dia.
0.24" / 6 mm maximum.

546

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP Series Undrilled Fiberglass Reinforced Polyester Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

JBEP Series for Terminal Junction Box Application Only.
The size of the junction box needed to meet your requirements can be selected based on the table shown below. We also offer you the
possibility to drill and equip, please consult our drilling guide available online at: www.egsatx.com
1. Define maximum cable entries according to number of modules available per side.
Cable Entry Metric Thread

Number of Modules

M20

1

M25

1

M32

1

M40

2

M50

3

H

Dimensions in/mm
Width

Depth

B/D

Number of Modules
A/C

A’/C’ (1)

Allowable
Max. Size

Terminal Dim.
H — in/mm

CSPe1

4.72/120

4.72/120

3.58/91

2

2

–

M25

4.72/120

CSPe2

6.69/170

4.72/120

3.58/91

3

2

–

M32

4.72/120

CSPe3

9.06/230

4.72/120

3.58/91

4

2

–

M32

4.72/120

CAe1

8.46/215

7.87/200

5.91/150

11

8

–

M50

7.87/200

CAe2

12.60/320

7.87/200

5.91/150

18

8

–

M50

7.87/200

CAe3

16.73/425

7.87/200

5.91/150

26

8

–

M50

7.87/200

CAe4

22.64/575

7.87/200

5.91/150

38

8

–

M50

7.87/200

CAe6

15.75/400

11.81/300

8.11/206

18

18

–

M50

15.75/400

CAe7

19.68/500

15.75/400

8.11/206

24

10

10

M50

19.68/500

CAe8

24.02/610

15.75/400

10.12/257

48

10

10

M75

24.02/610

CAe10

32.28/820

24.02/610

11.81/300

72

54

–

M100

32.28/820

CAe11

40.16/1020

31.89/810

11.81/300

96

78

–

M100

40.16/1020

0.025/16

0.054/35

0.078/50

2. Maximum rail arrangement according to physical dimensions.
Maximum Quantity of Horizontal Rails Per Quantity
Terminal Capacity

(in2/mm2)

0.004/2.5

0.006/4

0.009/6

0.016/10

CSPe1/2/3

1

1

1

1

0

0

0

CAe1/2/3/4

1

1

1

1

1

1

0

CAe6

3

3

3

2

2

2

1

CAe7

4

4

3

3

3

2

1

CAe8

4

4

4

4

3

3

2

CAe10

6

6

5

5

5

4

3

CAe11

8

8

7

7

6

5

3

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

547

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Length

Enclosures and Junction Boxes

Type

JBEP Series Undrilled Fiberglass Reinforced Polyester Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IECEx
IP66 – IK10

3. Defining maximum terminal block quantity according to power dissipation:
•	 Junction boxes used for instrumentation applications have very low current levels, therefore there is no risk of overheating whatever the
number of terminals inside the box.
•	 For applications other than instrumentation, the following tables allow you to define your junction box depending on the number of terminals
and the maximum authorized current being carried with feed-through terminals.
•	 For single feed terminals using cross connection, please consult your local representative for a calculation.
For other terminal block configurations, please consult our drilling guide available online at: www.appletonelec.com

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Small Junction Boxes

T Rating:
T6

Non-Hinged Junction Boxes

Type
CSPe1
CSPe2
CSPe3
5 x 5 x 4"/
7 x 5 x 4"/
9 x 5 x 4"/
120 x 120 x 91 120 x 170 x 91 120 x 230 x 91
mm
mm
mm

Type
CAe1
CAe2
CAe3
CAe4
T Rating:
8 x 9 x 6"/ 8 x 13 x 6"/ 8 x 17 x 6"/ 8 x 23 x 6"/
T6 @ Ta 104 °F/40 °C 200 x 215 x 200 x 320 x 200 x 425 x 200 x 575 x
T5 @ Ta 131 °F/55° C
150 mm
150 mm
150 mm
150 mm

0.004 in2/ Qty.
2.5 mm2 1 max.

12
15 A

22
13 A

33
12 A

0.004 in2/
2.5 mm2

Qty.
1 max.

20
16 A

21
16 A

23
16 A

29
14 A

0.006 in2/ Qty.
4 mm2 1 max.

10
20 A

18
19 A

28
16 A

0.006 in2/
4 mm2

Qty.
1 max.

19
20 A

20
20 A

23
20 A

33
16 A

0.009 in2/ Qty.
6 mm2 1 max.

7
32 A

14
27 A

21
24 A

0.009 in2/
6 mm2

Qty.
1 max.

12
32 A

13
32 A

14
32 A

18
28 A

0.016 in2/ Qty.
10 mm2 1 max.

4
50 A

6
50 A

8
50 A

0.016 in2/
10 mm2

Qty.
1 max.

10
40 A

11
40 A

18
32 A

22
28 A

0.024 in2/
16 mm2

Qty.
1 max.

8
28 A

10
27 A

13
25 A

15
26 A

0.039 in2/
25 mm2

Qty.
1 max.

8
67 A

8
73 A

10
69 A

10
70 A

0.054 in2/
35 mm2

Qty.
1 max.

8
79 A

8
86 A

10
80 A

10
80 A

Hinged Junction Boxes

CAe6
T Rating:
16 x 12 x 8"/
T6 @ Ta 104 °F/40 °C 400 x 300 x
T5 @ Ta 131 °F/55° C
206 mm

Type
CAe7
CAe8
CAe10
CAe11
20 x 16 x 8"/ 24 x 16 x 10"/ 32 x 24 x 12"/ 40 x 32 x 12"/
500 x 400 x
610 x 400 x
820 x 610 x 1020 x 810 x
206 mm
257 mm
300 mm
300 mm

0.054 in2/ Qty.
35 mm2 1 Max.

12
100 A

16
100 A

16
100 A

—

—

0.078 in2/ Qty.
50 mm2 1 Max.

8
125 A

12
125 A

16
125 A

—

—

0.109 in2/ Qty.
70 mm2 1 Max.

8
160 A

10
160 A

12
160 A

—

—

0.147 in2/ Qty.
95 mm2 1 Max.

8
200 A

10
200 A

12
200 A

—

—

0.186 in2/ Qty.
120 mm2 1 Max.

—

8
250 A

8
250 A

12
200 A

16
150 A

0.233 in2/ Qty.
150 mm2 1 Max.

—

—

6
250 A

9
250 A

12
190 A

0.287 in2/ Qty.
185 mm2 1 Max.

—

—

—

8
300 A

10
240 A

548

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBEP and ECEP Series Undrilled Fiberglass Reinforced Polyester Enclosure
Dimensions

Increased Safety

Dimensions in Inches/Millimeters

3.58/91

4.72/120

Fixing details for below boxes: four holes Ø 0.20"/5 mm.
4.72/120

Fix. 4.06/103

Fix. 4.06/103

Fix. 4.06/103

Fix. 4.06/103

Fix. 7.60/193

9.06/230

Fix. 7.60/193
9.06/230

6.69/170

Fix. 4.06/103

Fix. 4.06/103

Fix. 4.06/103

3.58/91

4.72/120

Fix. 5.24/133

Fix. 83

4.72/120

6.69/170

Fix. 83

4.72/120

Fix. 4.06/103

Fix. 4.06/103

CSPe3

Enclosures and Junction Boxes

4.72/120

4.72/120
Fix. 5.24/133

6.69/170

Fix. 83

4.72/120

4.72/120

Fix. 5.24/133

4.72/120

Fix. 7.60/193

4.72/120

3.58/91

4.72/120

CSPe2
9.06/230

CSPe1

Type
CAe1

A

External
B

C

Internal
E

D

Fixings
F

G

H

7.87/200.0 8.46/215.0 5.91/150.0 7.28/185.0 7.87/200.0 4.92/125.0 5.75/146.0 7.44/189.0

Thick

Ø

0.24/6.0

0.26/6.5

CAe2

7.87/200.0 12.60/320.0 5.91/150.0 7.28/185.0 12.01/305.0 4.92/125.0 5.75/146.0 11.57/294.0

0.24/6.0

0.26/6.5

CAe3

7.87/200.0 16.73/425.0 5.91/150.0 7.28/185.0 16.14/410.0 4.92/125.0 5.75/146.0 15.71/399.0

0.24/6.0

0.26/6.5

CAe4

7.87/200.0 22.64/575.0 5.91/150.0 7.28/185.0 22.05/560.0 4.92/125.0 5.75/146.0 21.57/548.0

0.24/6.0

0.26/6.5

Insulated Side Support (Rail Holder) 096115
Equipment Capacity
L

M

CAe1

4.13/105.0 5.08/129.0

CAe2

8.11/206.0 9.21/234.0

CAe3

12.20/310.0 13.35/339.0

CAe4

12.40/315.0 13.58/345.0

DIN rail depth 0.59”/15 mm

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

6.50/165

Type

Earth bar

549

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

CAe1 to CAe4

JBEP and ECEP Series Undrilled Fiberglass Reinforced Polyester Enclosures
Dimensions

Increased Safety

Dimensions in Inches/Millimeters
CAe6 to CAe11
8
1/1
0.31/8

0.7

External
Type

A

B

C

D

T

Fixing With horizontal lug
U
Y

R

Fixing With vertical lug
S

V

CAe6 15.75/400.0 11.81/300.0 8.11/206.0

8.74/222.0 13.43/341.0 14.57/370.0 16.73/425.0 18.50/470.0 9.50/241.0 20.67/525.0

CAe7 19.68/500.0 15.75/400.0 8.11/206.0

8.74/222.0 17.36/441.0 18.50/470.0 20.67/525.0 22.44/570.0 13.43/341.0 24.61/625.0

CAe8 24.02/610.0 15.75/400.0 10.12/257.0 10.75/273.0 21.69/551.0 18.50/470.0 20.67/525.0 26.77/680.0 13.43/341.0 28.94/735.0
CAe10 32.28/820.0 24.02/610.0 11.81/300.0 12.44/316.0 29.84/758.0 26.65/677.0 28.82/732.0 34.92/887.0 21.57/548.0 37.09/942.0
CAe11 40.16/1020.0 31.89/810.0 11.81/300.0 12.44/316.0 37.72/958.0 34.53/877.0 36.69/932.0 42.80/1087.0 29.45/748.0 44.96/1142.0

Gland Plates
JBEPGP300

JBEPGP400D12

JBEPGP400

550

0.55/14

4.49/114

12.68/322

10.39/264

5.11/130

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

1.08/27.5

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

SJB Series 316L Stainless Steel Junction Boxes

Explosion Protected Terminal Enclosure
cCSAus Approved
CEC/NEC
Class I Zone 1
Exe/AExe II, T5 or T6
Enclosure: IP66

CSA Approved
CSA Type 4X

Applications

Without Terminals

•	 Terminal, junction box enclosure for various electrical devices.
•	 Designed for use in areas designed for Zone 1, where
flammable gases or vapors are present either continuously or
intermittently such as:
	 — Petroleum
	 — Chemical
	 — Refineries
	 — Other industrial process facilities.
	 — Food processing
	 — Dairy
	 — Brewing
	 — Other commercial facilities.
•	 Ideal for wet or corrosive atmospheres.

Equipped with Terminals
Enclosures and Junction Boxes

Features

Standard Materials
•	 Enclosure: 316L chrome plated Molybdenum stainless steel
with natural brushed finish
•	 Hardware: 316L stainless steel

Options
•	
•	
•	
•	
•	
•	

•	
•	
•	
•	
•	
•	
•	

Mounting pan
Gland plates
Interior side rails
DIN rails
Side rail and DIN rail assembly
Terminal Blocks (Enclosure size varies, based on # terminals
blocks, cross section or terminal block, current, ambient
temperature and desired T rating, contact your local sales
representative.)
Ground bars
Terminals for Ground bar
Terminal spacers: 3.94"/100 mm or 1.97"/50 mm
Padlocking device
Locking hinge
Factory drilled entries
Enclosure coupling kit available, contact your local sales
representative.

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

•	 Austenitic stainless steel contains at least 10.5% Chrome (Cr).
Chrome is a protective layer that shields the material from
humidity in the air.
•	 316L stainless steel contains Molybdenum (Mo), which provides
excellent corrosion resistance especially against chlorides.
•	 Smooth, continuos welded seams.
•	 Many different sizes and depths to choose from.
•	 Available in three depths, 3.74"/95 mm, 7.87"/200 mm and
11.81"/300 mm.
•	 Can be supplied with 1, 2, 3 or even 4 neoprene sealed gland
plates for ease of cable installation.
•	 316L Stainless steel captive screws.
•	 Hinges standard on all sizes above 14.57" x 10.24" /
370 mm x 260 mm.
•	 Poured in place polyurethane door gasket.
•	 M8 feed-thru earth/ground stud.
•	 Patented reversible door, opens 210 degrees, from any location
Top/bottom, left or right, by means of removable hinges that can
be installed in any position.
•	 Patented reversible anti vibration mounting brackets, on the top,
bottom or side positions.
•	 Optional patented removable pad locking device.
•	 Numerous optional accessories.

Certifications and Compliances
•	
	
•	
	
	
	
	
	
	
•	
	
	
	
	
	
	

North American
— cCSAus Approved
CEC/NEC
— Class 1 Zone 1, Exe/AExe II, T5 or T6
— Enclosure rating: IP66
— 600 Volt Max, 400 Amp Max
— Maximum Dissipated Power: 489 Amp
— CSA Listed: 0130170000
— CSA Type 4X
International
— CENELEC LCIE 02 ATEX 6118X
— IEC LCIE Ex 02.010X
— EEx ed/ EEx « i « IIC, T3 to T6
— IP66, IK10
— CE Declaration of Conformity
— Standards: EN 50281-1-1 and IEC 61241-1-1

551

SJB Series 316L Stainless Steel Junction Boxes

Explosion Protected Terminal Enclosure
cCSAus Approved
CEC/NEC
Class I Zone 1
Exe/AExe II, T5 or T6
Enclosure: IP66

CSA Approved
CSA Type 4X

Enclosures and Junction Boxes

Illustrated Features
Optional Patented
Removable Locking
Device.
Part Number 097209.

Patented Reversible
Door. Opens to 210°,
top, bottom, left or
right, by moving the
location of the hinges.

Patented Reversible
Anti-vibration mounting
brackets, can be
mounted in top, side or
bottom positions.

Polyurethane Poured in
Place Door Gasket and
Stainless Steel Captive
Screws.

M8 Feed-thru Earth/
Ground Terminal.

Optional Removable
Gland Plate.

Catalog Numbering Guide

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Confirm size and gland plate availability in below table.

SJB

12

12

SJB Series

95

N

Depth Dimensions in/mm:
95 - 3.74/95
15 - 5.91/150
20 - 7.87/200
30 - 11.81/300

Height Dimensions in/mm:
12 - 4.72/120
18 - 7.09/180
22 - 8.66/220
26 - 10.24/260
37 - 14.57/370
56 - 22.05/560
75 - 29.58/750
11 - 44.49/1130
Width Dimensions in/mm:
12 - 4.72/120
18 - 7.09/180
22 - 8.66/220
26 - 10.24/260
37 - 14.57/370
56 - 22.05/560
75 - 29.58/750

552

0

25

010

Terminal Block
Size in/mm:
25 - 0.10/2.5
04 - 0.16/4.0
06 - 0.24/6.0
10 - 0.39/10.0
16 - 0.63/16.0
35 - 1.378/35.0

Gland Plates:
0 - none
1 - one bottom
3 - two sides and bottom
4 - All sides

Terminal Block
Quantity:
010 - 10
050 - 50
100 - 100

Mounting Pan:
N - None
P - Mounting pan

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

SJB Series 316L Stainless Steel Junction Boxes

Explosion Protected Terminal Enclosure
cCSAus Approved
CEC/NEC
Class I Zone 1
Exe/AExe II, T5 or T6
Enclosure: IP66

CSA Approved
CSA Type 4X

Height

Dimension in Inches/Millimeters
Width

Depth

0

Possible Gland Plates
1
2
3

4.72/120

4.72/120

4

Catalog Number

3.74/95



—

—

—

—

SJB121295

4.72/120

7.09/180

3.74/96



—

—

—

—

SJB121895

7.09/180

4.72/120

3.74/97



—

—

—

—

SJB181295

7.09/180

7.09/180

3.74/98



—

—

—

—

SJB181895

10.24/260

5.91/150











SJB222615

8.66/220

5.91/151











SJB262215

8.66/220

14.57/370

7.87/200











SJB223720 †

14.57/370

8.66/220

7.87/201











SJB372220

10.24/260

14.57/370

7.87/202











SJB263720

14.57/370

10.24/260

7.87/203











SJB372620 †

14.57/370

14.57/370

7.87/204











SJB373720 †

14.57/370

22.05/560

7.87/205











SJB375620











SJB563720 †

14.57/370

7.87/206

29.53/750

7.87/207











SJB377520

29.53/750

14.57/370

7.87/208











SJB753720

22.05/560

22.05/560

7.87/209











SJB565620 ‡

22.05/560

29.53/750

7.87/210











SJB567520

14.57/370

14.57/370

11.81/300











SJB373730

14.57/370

22.05/560

11.81/301











SJB375630

22.05/560

14.57/370

11.81/302











SJB563730

14.57/370

29.53/750

11.81/303











SJB377530

29.53/750

14.57/370

11.81/304











SJB753730

22.05/560

22.05/560

11.81/305











SJB565630

22.05/560

29.53/750

11.81/306











SJB567530

29.53/750

22.05/560

11.81/307











SJB755630

44.49/1130

29.53/750

11.81/308

—

—

—

—

—

SJB117530

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

22.05/560
14.57/370

Enclosures and Junction Boxes

8.66/220
10.24/260

† No gland plates.
‡ One gland plate.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

553

SJB Series 316L Stainless Steel Junction Boxes

Explosion Protected Terminal Enclosure
cCSAus Approved
CEC/NEC
Class I Zone 1
Exe/AExe II, T5 or T6
Enclosure: IP66

CSA Approved
CSA Type 4X

Maximum Terminal Block Information
To order terminal blocks: Use nomenclature below. Supplied installed on a mounting pan. Can be installed on uprights and rails. Contact your local sales
representative.

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Catalog
Number

Number
Qty.
Qty.
Rails
Max.
Max.
Hori- Terminal Size Physi- Terminal at Max. Terminal
zontal
in/mm
cal
Amp
Amps
Amp

SJB121295

1

0.10/2.5

SJB121295

1

SJB121895

1

SJB121895

Catalog
Number

Number
Qty.
Qty.
Rails
Max.
Max.
Hori- Terminal Size Physi- Terminal at Max. Terminal
zontal
in/mm
cal
Amp
Amps
Amp

10

10

4

15

SJB377520

6

0.39/10.0

150

15

30

40

0.16/4.0

8

10

5

20

SJB377520

5

0.63/16.0

100

20

30

50

0.10/2.5

20

10

9

15

SJB753720

3

0.39/10.0

189

15

33

40

1

0.16/4.0

18

10

10

20

SJB753720

2

0.63/16.0

104

20

32

50

SJB181295

1

0.10/2.5

10

10

4

15

SJB565620

4

0.39/10.0

176

15

36

40

SJB181295

1

0.16/4.0

8

10

5

20

SJB565620

4

0.63/16.0

104

30

36

50

SJB181895

1

0.10/2.5

21

10

10

15

SJB567520

5

0.63/16.0

180

20

45

50

SJB181895

1

0.16/4.0

18

15

11

20

SJB567520

4

1.38/35.0

116

40

32

90

SJB222615

2

0.10/2.5

40

10

18

15

SJB373730

3

0.27/6.0

93

15

27

30

SJB222615

2

0.16/4.0

30

15

18

20

SJB373730

2

0.39/10.0

74

20

26

40

SJB262215

1

0.16/4.0

23

10

15

20

SJB375630

4

0.27/6.0

124

15

36

30

SJB262215

1

0.27/6.0

17

20

12

30

SJB375630

4

0.39/10.0

100

20

32

40

SJB223720

3

0.16/4.0

48

10

27

20

SJB563730

3

0.27/6.0

165

10

36

30

SJB223720

3

0.27/6.0

36

20

15

30

SJB563730

3

0.39/10.0

132

20

33

40

SJB372220

1

0.16/4.0

41

15

27

20

SJB377530

6

0.39/10.0

150

20

42

40

SJB372220

1

0.27/6.0

31

20

15

30

SJB377530

5

0.63/16.0

100

30

40

50

SJB263720

3

0.16/4.0

69

10

30

20

SJB753730

3

0.39/10.0

189

15

42

40

SJB263720

2

0.27/6.0

32

20

18

30

SJB753730

2

0.63/16.0

104

30

42

50

SJB372620

2

0.16/4.0

82

10

30

20

SJB565630

4

0.39/10.0

176

20

44

40

SJB372620

2

0.27/6.0

62

15

18

30

SJB565630

4

0.63/16.0

104

30

44

50

SJB373720

3

0.27/6.0

93

10

21

30

SJB567530

5

0.63/16.0

180

20

55

50

SJB373720

2

0.39/10.0

74

20

21

40

SJB567530

4

1.38/35.0

116

40

36

90

SJB375620

4

0.27/6.0

124

15

30

30

SJB755630

3

0.63/16.0

104

30

54

50

SJB375620

4

0.39/10.0

100

20

28

40

SJB755630

3

1.38/35.0

84

50

36

90

SJB563720

3

0.27/6.0

165

10

30

30

SJB117530

6

1.38/35.0

252

40

60

90

SJB563720

3

0.39/10.0

132

15

27

40

SJB117530

4

2.76/70.0

112

80

36

145

* Maximum physical at amperage indicated, capable of accepting more terminals at lower amperage. Contact your local sales representative.

554

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

SJB Series 316L Stainless Steel Junction Boxes

Explosion Protected Terminal Enclosure
cCSAus Approved
CEC/NEC
Class I Zone 1
Exe/AExe II, T5 or T6
Enclosure: IP66

CSA Approved
CSA Type 4X

Catalog Number
Rail Length in/mm
Zinc Plated Steel Rail

Symmetrical Depth = 0.59"/15 mm

Asymmetrical

For fixing onto uprights with clip nut supplied.

Symmetrical

SJBSCP100

—

6.30/160

SJBSCP160

—

6.69/170

SJBSCP170

SJBACP170

7.87/200

SJBSCP200

SJBACP200

12.60/320

SJBSCP320

SJBACP320

20.08/510

SJBSCP510

SJBACP510

27.56/700

SJBSCP700

SJBACP700

42.52/1080

SJBSCP1080

SJBACP1080

Bar Length
in/mm
Zinc Plated Steel Uprights

Enclosures and Junction Boxes

Asymmetrical

3.93/100

Catalog
Number

7.87/200

SJBSR200

12.20/310

SJBSR310

19.68/500

SJBSR500

27.17/690

SJBSR690

42.13/1070

SJBSR1070

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Set of two.

Copper Bar (.47 x .16" / 12 x 4 mm)

Copper bar not perforated for cable clamps.

6.30/160

SJBCGB160

7.87/200

SJBCGB200

12.20/310

SJBCGB310

19.68/500

SJBCGB500

27.17/690

SJBCGB690

42.13/1070

SJBCGB1070

Cable Clamp for Copper Bar (.47 x .16" / 12 x 4 mm)
0.002 in2 to 0.006 in2 / 1.5 mm2 to 4 mm2 Capacity — Set of 100
0.009

in2

to 0.025

in2

/6

mm2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

to 16

mm2

Capacity — Set of 10

SJBGBC154
SJBGBC616

555

SJB Series 316L Stainless Steel Junction Boxes

Explosion Protected Terminal Enclosure
cCSAus Approved
CEC/NEC
Class I Zone 1
Exe/AExe II, T5 or T6
Enclosure: IP66

CSA Approved
CSA Type 4X

Dimensions Inches/Millimeters
Height

Width

Catalog Number

8.66/220

14.57/370

SJBGP370

14.57/370

10.24/260

SJBGP260

10.24/260

14.57/370

SJBGP370

14.57/370

14.57/370

SJBGP370

22.05/560

14.57/370

SJBGP370

14.57/370

22.05/560

SJBGP560

29.53/750

14.57/370

SJBGP370

14.57/370

29.53/750

SJBGP750

22.05/560

22.05/560

SJBGP560

29.53/750

22.05/560

SJBGP560

22.05/560

29.53/750

SJBGP750

Enclosures and Junction Boxes

Mounting Pan – Zinc Plated Steel

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Spacers for Mounting at Back of Box

Set of two insulated pillars for copper bar .47 x .16" / 12 x 4 mm.

Height = 3.94"/100 mm

SJBS100

Height = 1.97"/50 mm

SJBS500

Additional Door Padlocking Device
Padlock not supplied

556

SJBPL

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBES Series Pre-Drilled 316L Stainless Steel Junction Boxes

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Applications

JBe10 — Without Terminals

JBe46 — Equipped with Terminals

JBe46 — Equipped with Terminals

JBe46 — Equipped with Terminals

Features

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

•	 Smooth, continuously welded seams.
•	 Hinges supplied on all boxes from 14.57" x 10.24" /
370 mm x 260 mm sizes.
•	 Poured-in-place polyurethane door gasket.
•	 Earth crossing terminal.
•	 Factory drilled and equipped.

Standard Material
•	 Enclosure: 316L chrome plated molybdenum stainless steel with
natural burnished finish
•	 Hardware: 316L stainless steel

Options
•	 For use with equipment other than Ex terminal blocks, see
ECES series enclosures and controls.

Certifications and Compliances
•	
	
	
	
	
	
	
	
	
	
	
	
	
•	
•	
•	
•	

Certification Type JBe
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e II, Ex ia IIC, Ex ib IIC,
– T Rating: T6 to T5
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T176 °F/T80 °C to T203 °F/T95 °C
— Ambient Temperature: -58 °F/-50 °C to 158 °F/70 °C
— CE Declaration of Conformity: 50232
— ATEX Certificate: LCIE 02 ATEX 6118X
— IEC Certificate: IEC Ex 02.010X
Other Certifications: GOST
Ingress Protection (solid and liquid): IP66
Impact Resistance (shock): IK10
Ex Standards: EN/IEC 60079-0; 60079-1; 60079-11, 61241-0;
61241-1; 61241-11
•	 Other Standards: EN/IEC 60529 (IP), 62262 (IK)

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes

•	 Terminal junction boxes designed to facilitate electrical
connections in hazardous areas.
•	 Designed for use in Zone 1 or 2 areas, where flammable gases or
vapors are present either continuously or intermittently such as:
	 — Petroleum
	 — Chemical
	 — Refineries
	 — Other industrial process facilities
•	 Ideal for wet or corrosive atmospheres.
•	 Designed for use in Zone 21 or 22 areas, where flammable
dusts are present either continuously or intermittently, such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Pharmaceutical industry
	 — Silos and other facilities

557

JBES Series Pre-Drilled 316L Stainless Steel Junction Boxes

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Catalog Numbering Guide
JBES

12

12

09

Series
ATEX/IEC Certified:
E - Increased Safety
I - Intrinsic Safety

0

Depth Dimensions in/mm:
09 - 3.74/95.0
15 - 5.91/150.0
20 - 7.87/200.0

Length Dimensions in/mm:
12 - 4.72/120.0
18 - 7.09/180.0
22 - 8.66/220.0
26 - 10.24/260.0
37 - 14.57/370.0

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

0

Gland plate:
0 - None
1 - One Bottom
2 - One Top and Bottom
3 - Two Sides and Bottom
4 - All Sides

Width Dimensions in/mm:
12 - 4.72/120.0
18 - 7.09/180.0
22 - 8.66/220.0
26 - 10.24/260.0
37 - 14.57/370.0

Options:

(options must be listed alphabetically)

D1 - 5 x M20
D2 - 4 x M20 + 1 x M25
D3 - 7 x M20 + 1 x M25
F1 - Fitted with 0.019 x 0.004 in2 /
12 x 2.5 mm2 Terminals and Drilled
F2 - Fitted with 0.031 x 0.004 in2 /
20 x 2.5 mm2 Terminals and Drilled
F3 - Fitted with 0.062 x 0.004 in2 /
40 x 2.5 mm2 Terminals and Drilled
F4 - Fitted with 0.093 x 0.004 in2 /
60 x 2.5 mm2 Terminals and Drilled
F5 - Fitted with 0.022 x 0.004 in2 /
14 x 2.5 mm2 Terminals and Drilled
F6 - Fitted with 0.037 x 0.004 in2 /
24 x 2.5 mm2 Terminals and Drilled
F7 - Fitted with 0.057 x 0.004 in2 /
38 x 2.5 mm2 Terminals and Drilled
F8 - Fitted with 0.084 x 0.004 in2 /
54 x 2.5 mm2 Terminals and Drilled
# - Customized Enclosure (6 Digit number

will be assigned at time of order placement.)

Maximum Rail Arrangement According to Physical Dimensions
Type
JBe10

JBe20

Protection
T6 @ Ta = 131 °F/55° C

T6 @ Ta = 131 °F/55° C

Terminal Size
in2/mm2

Quantity

Max.
Amps

0.004/2.5

10

16A

0.006/4.0

8

25A

0.009/6.0

6

32A

0.004/2.5

21

16A

0.006/4.0

18

25A

0.009/6.0

13

32A

For other terminal block configurations, consult our drilling guide available online at our website www.egsatx.com.

558

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBES Series Pre-Drilled 316L Stainless Steel Junction Boxes

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Type

Dimensions
L x W x D in/mm

Rail Length
Capacity
in/mm

Clearance Holes per side
A

B

C

D

Weight
lb/kg

Volume
in3/dm3

Catalog
Number

Factory Drilled Ex e II 316L Stainless Steel Junction Boxes Fitted with:

One horizontal symmetrical zinc plated rail. For use only with Ex terminals (not supplied). M6 external earth crossing terminal.

A
B
C

4.72 x 4.72 x 3.74/
120 x 120 x 95

4/100

JBe20

4.72 x 4.72 x 3.74/
120 x 120 x 95

6/160

–

JBe20

4.72 x 4.72 x 3.74/
120 x 120 x 95

6/160

–

1 x M20 1 x M20 2 x M20 1 x M20

2.20/
1.0

85.43/
1.4

JBES1212090D1

1 x M20

2 x M20
1 x M20
1 x M25

3.31/
1.5

122.05/
2.0

JBES1218090D2

2 x M20

3 x M20
2 x M20
1 x M25

3.31/
1.5

122.05/
2.0

JBES1218090D3

Factory Drilled and Equipped with Terminals Ex e II 316L Stainless Steel Instrumentation Junction Boxes Fitted with:

Vertical beige Exe terminal block. Insulated copper bar with connectors. White laminated plastic tag with black lettering. M8 external earth crossing terminal.
Cable glands and plugs to be ordered separately.

D

7.09 x 4.72 x 3.74/
180 x 120 x 95

12
(6 Pairs)

8

3 x M20

1 x M25
3 x M20
1 x M20

5.51/
2.5

122.05/
2.0

JBES1812090F1

JBe36

10.24 x 8.66 x 5.91/
20
260 x 220 x 150
(10 Pairs)

12

5 x M20

1 x M32
5 x M20
1 x M20

8.82/
4.0

524.80/
8.6

JBES2622150F2

JBe46

14.57 x 8.66 x 7.87/
40
370 x 220 x 200
(20 Pairs)

22

10 x M20

1 x M40
19.84/
10 x M20
1 x M20
9.0

994.69/
16.3

JBES372220F3

JBe47

14.57 x 10.24 x 7.87/
60
370 x 260 x 200
(30 pairs)

32

15 x M20

1 x M50
11.0/
15 x M20
1 x M20
24.25

1177.76/
19.3

JBES3726200F4

B
C

Ex ia IIC Version: Replace Third Digit “E” with “I” (Example: JBES1812090F1 becomes JBIS1812090F1) Fitted with:

Vertical blue terminal block. Insulated copper bar with connectors. Blue laminated plastic tag with white lettering. M8 external earth crossing terminal. Cable
glands and plugs to be ordered separately.

Factory Drilled and Equipped with Terminals Ex e II 316L Stainless Steel Instrumentation Junction Boxes Fitted with:

Horizontal beige Exe terminal block. Continuity shield. White laminated plastic tag with black lettering. M8 External earth crossing terminal. Cable glands and
plugs to be ordered separately.

D

A
C

JBe36

8.66 x 10.24 x 5.91/
220 x 260 x 150

14
(7 Pairs)

7

1 x M25 7 x M20

8.82/
4.0

524.80/
8.6

JBES2226150F5

JBe36

8.66 x 10.24 x 5.91/
24
220 x 260 x 150
(12 pairs)

12

1 x M32 12 x M20

8.82/
4.0

524.80/
8.6

JBES2226150F6

JBe46

8.66 x 14.57 x 7.87/
38
220 x 370 x 200
(19 pairs)

19

1 x M32 19 x M20

19.84/
9.0

994.69/
16.3

JBES2237200F7

JBe46

8.66 x 14.57 x 7.87/
54
220 x 370 x 200
(27 pairs)

27

1 x M40 27 x M20

19.84/
9.0

994.69/
16.3

JBES2237200F8

B

Ex ia IIC Version: Replace Third Digit “E” with “I” (Example: JBES2226150F5 becomes JBIS2226150F5) Fitted with:

Horizontal blue terminal block. Continuity shield. Blue laminated plastic tag with white lettering. M8 external earth crossing terminal. Cable glands and plugs to be
ordered separately.

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

559

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

A

JBe20

Enclosures and Junction Boxes

D

JBe10

JBES Series Pre-Drilled 316L Stainless Steel Junction Box Dimensions

Increased Safety

Dimensions in Inches/Millimeters
Factory Drilled without Terminal Block (DIN rail supplied)

4.33/110

Fix. 5.51/140
6.30/160

3.74/95
2.95/75

0.31/8

3.15/80

3.15/80

4.72/120

0.31/8

4.72/120

4.72/120
3.15/80

JBe20
7.09/180
5.51/140

3.74/95
2.95/75

4.33/110

JBe10

Fix. 7.87/200

4.09/104

Factory Drilled and Equipped with Vertical Terminal Block
JBe20
8.66/220

7.67/194

Fix. 8.86/225

7.09/180

5.83/148
6.69/170

8.66/220

Fix. 7.87/200

5.90/150

5.51/140
Fix. 10.11/257
11.25/286

0.08/2
4.09/104

3.15/80

0.35/9

6.06/154

2M 0.23 x 0.63/
6 x 16

10.24/260

3.74/95
2.95/75

7.09/180
5.51/140

0.31/8

JBe36

4.72/120

0.10/2.5

Factory Drilled and Equipped with Vertical Terminal Block
JBe46

JBe47

8.66/220

13.78/350
11.42/290

11.97/304

14.57/370

11.97/304

7.87/200

Fix. 13.19/335

11.42/290

14.57/370

7.87/200
6.69/170

10.24/260
7.64/194

13.19/335

0.35/9

6.06/154

7.09/180
Fix. 11.69/297
5.51/140
Fix. 10.12/257

0.10/2.5

12.83/326

0.10/2.5

11.26/286

Factory Drilled and Equipped with Horizontal Terminal Block
JBe46

2.5/.010

6.06/154

7.87/200
5.51/140

Fix. 7.28/185

6.06/154
7.09/180

11.42/290
Fix. 16.02/407
17.17/436

7.87/200
6.69/170

0.35/9

7.87/200
5.51/140

4.72/120

0.35/9

8.66/220

7.64/194

Fix. 11.69/297

14.57/370
11.97/304

5.91/150

Fix. 7.28/185

JBe36
10.24/260

8.66/220

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

8.66/220

0.10/2.5

12.91/328

560

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBES and ECES Series 316L Stainless Steel Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Applications

•	 Smooth, continuously welded seams.
•	 Available in a wide range of sizes.
•	 Operating temperature -58 °F/-50 °C to 158 °F/70 °C (JBES
series) and -58 °F/-50 °C to 131 °F/55 °C (ECES series).
•	 Can be supplied with 1, 2, 3 or even 4 neoprene sealed gland
plates for ease of cable installation.
•	 Hinges standard on all sizes above 14.57" x 10.24" /
370.0 mm x 260.0 mm.
•	 Poured-in-place polyurethane door gasket.
•	 Feed-thru earth grounding stud.
•	 Reversible door, opens 210 degrees, from any location top;
bottom, left or right, by means of removable hinges that can be
installed in any position.
•	 Reversible anti-vibration mounting brackets can be mounted on
the top, bottom or side positions.
•	 Optional removable padlocking device.

Standard Materials
•	 Enclosure: 316L chrome plated stainless steel
•	 Hardware: 316L stainless steel

Standard Finishes
•	 Natural brushed finish

Accessories
•	
•	
•	
•	
•	
•	

Mounting pan
Rail mounting
Padlocking device
Door locking bracket for easy access
Inside pocket
Refer to technical data to define permitted number of terminals
and cable entries acceptance

Options
•	 Removable gland plates.
•	 Nameplate.

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

ECES Series

Closed

Open
•	 Factory drilled and assembled, contact your local representative
for information.
•	 Medium voltage application (11 kV max.), contact your local
representative for information.
•	 Intrinsic safety version (JBIS) available with the use of intrinsic
terminals.
•	 CSA and CUL certified terminal junction box available. Contact
your local representative for information.

Certifications and Compliances
•	 Certification Type JBe
	 — Gas, Zones 1 and 2
	
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
	
– ATEX/IEC Protection: Ex e II, Ex ia IIC, Ex ib IIC, Ex de IIC,
Ex demb IIC
	
– T Rating: T6 to T4
	 — Dust, Zones 21 and 22
	
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
	
– ATEX/IEC Protection: Ex tD A21
	
– Surface Temperature: T176 °F/T80 °C to T266 °F/T130 °C
	 — Ambient Temperature: -58 °F/-50 °C to 158 °F/70 °C
	 — CE Declaration of Conformity: 50232
	 — ATEX Certificate: LCIE 02 ATEX 6118X
	 — IEC Certificate: LCIE Ex 02.010X
	 — Other Certifications: GOST
•	 Certification Type JBe U
	 — Gas, Zones 1 and 2
	
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
	
– ATEX/IEC Protection: Ex e II
	 — Dust, Zones 21 and 22
	
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
	
– ATEX/IEC Protection: Ex tD A21
	 — Ambient Temperature: -58 °F/-50 °C to 158 °F/70 °C
	 — CE Declaration of Conformity: 5C240
	 — ATEX Certificate: LCIE 09 ATEX 3025U
	 — IEC Certificate: LCIE Ex 09.001U
•	 Ingress Protection (solid and liquid): IP66
•	 Impact Resistance (shock): IK10
•	 Ex Standards: EN/IEC 60079-0; 60079-1; 60079-7; 60079-11,
61241-0; 61241-1; 61241-11
•	 Other Standards: EN/IEC 60529 (IP), 62262 (IK)

561

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Features

JBES Series

Enclosures and Junction Boxes

•	 Designed for use in Zone 1 or 2 areas where flammable gases
or vapors are present either continuously or intermittently.
•	 Ideal for use in wet or corrosive atmospheres such as:
	 — Petroleum
	 — Chemical
	 — Refineries
	 — Other industrial process facilities
•	 Designed for use in Zone 21 or 22 areas where flammable dusts
are present either continuously or intermittently such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Pharmaceutical industry
	 — Other commercial facilities
•	 JBES Series
— Terminal junction box for electrical low voltage and
instrumentation connections for use in hazardous areas.
— Refer to technical data to define permitted number of
terminal blocks and cable entries on selected junction boxes.
•	 ECES Series
— Enclosure for distribution and control applications must
be customized at our workshop to house a large range
of components such as control units, switches, breakers,
transformers, meters, etc.

JBES and ECES Series 316L Stainless Steel Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Illustrated Features
Optional removable locking device.
Part Number 097209

Reversible antivibration mounting brackets,
can be mounted in top, side or bottom
positions.

M8 feed-thru earth/ground terminal.

Polyurethane poured in place door gasket and
stainless steel captive screws.

Reversible door. Opens to 210°, top, bottom,
left or right, by moving the location of the
hinges

Optional removable gland plate.

Catalog Numbering Guide
JBES

12

12

Series
ATEX/IEC Certified:
EC - Enclosure and Controls
JB - Junction Box
E - Increased Safety
I - Intrinsic Safety
S - Stainless Steel

09

M

Depth Dimensions in/mm:
09 - 3.58/91.0
15 - 5.91/150.0
20 - 7.87/200.0
30 - 11.81/300.0

Length Dimensions in/mm:
12 - 4.72/120.0
18 - 7.09/180.0
22 - 8.66/220.0
26 - 10.24/260.0
37 - 14.57/370.0
56 - 22.05/560.0
75 - 29.53/750.0
11 - 44.49/1130.0
Width Dimensions in/mm:
12 - 4.72/120.0
18 - 7.09/180.0
22 - 8.66/220.0
26 - 10.24/260.0
37 - 14.57/370.0
56 - 22.05/560.0
75 - 29.53/750.0

562

0

Gland plate:
0 - None
1 - One Bottom
2 - One Top and Bottom
3 - Two Sides and Bottom
4 - All Sides

Options:

(options must be listed
alphabetically)

M - Mounting Pan
U - Component Certification
“U”
# - Customized Enclosure (6

Digit number will be assigned
at time of order placement.)

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBES and ECES Series 316L Stainless Steel Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

JBES Series

Type

Dimensions
L x W x D in/mm

Hinged
Door ‡

Vertical
Horizontal
Orientation
Orientation
Rail Length in/mm Rail Length in/mm

Weight
lb/kg

Volume
in3/dm3

Catalog
Number

Ex e II 316L Stainless Steel Junction Boxes without Gland Plate

For use only with Ex terminals (not supplied). External earth crossing terminal. (M6 for JBe10/20/30 and M8 for other boxes). Mounting pan and rails to be ordered
separately.

N

–

3.94/
100

2.20/
1.0

85.43/
1.4

JBES1212090_

JBe20

4.72 x 7.09 x 3.74/
120 x 180 x 95

N

–

6.30/
160

3.31/
1.5

122.05/
2.0

JBES1218090_

JBe30

7.09 x 7.09 x 3.74/
180 x 180 x 95

N

–

6.30/
160

3.97/
1.8

183.07/
3.0

JBES1818090_

JBe36

8.66 x 10.24 x 5.91/
220 x 260 x 150

R

6.69/
170

8.27/
210

11.02/
5.0

524.80/
8.6

JBES2226150_

JBe36

10.24 x 8.66 x 5.91/
260 x 220 x 150

R

8.27/
210

6.69/
170

11.02/
5.0

524.80/
8.6

JBES2622150_

JBe46

8.66 x 14.57 x 7.87/
220 x 370 x 200 †

R

6.69/
170

12.60/
320

18.74/
8.5

994.69/
16.3

JBES2237200_

JBe47

10.24 x 14.57 x 7.87/
260 x 370 x 200 †

Y

8.27/
210

12.60/
320

19.84/
9.0

1177.76/
19.3

JBES2637200_

JBe46

14.57 x 8.66 x 7.87/
370 x 220 x 200 †

R

12.60/
320

6.69/
170

18.74/
8.5

1012.99/
16.6

JBES3722200_

JBe47

14.57 x 10.24 x 7.87/
370 x 260 x 200 †

Y

12.60/
320

8.27/
210

19.84/
9.0

1177.76/
19.3

JBES3726200_

JBe55

14.57 x 14.57 x 7.87/
370 x 370 x 200 †

Y

12.60/
320

12.60/
320

28.66/
13.0

1672.05/
27.4

JBES3737200_

JBe65

14.57 x 22.05 x 7.87/
370 x 560 x 200 †

Y

12.60/
320

20.08/
510

19.84/
19.0

2532.49/
41.5

JBES3756200_

JBe75

14.57 x 29.53 x 7.87/
370 x 750 x 200 †

Y

12.60/
320

27.56/
700

52.91/
24.0

3386.82/
55.5

JBES3775200_

JBe65

22.05 x 14.57 x 7.87/
560 x 370 x 200 †

Y

20.08/
510

12.60/
320

19.84/
19.0

2532.49/
41.5

JBES5637200_

JBE77

22.05 x 22.05 x 7.87/
560 x 560 x 200 †

Y

20.08/
510

20.08/
510

61.73/
28.0

3832.29/
62.8

JBES5656200_

JBe79

22.05 x 29.53 x 7.87/
560 x 750 x 200 †

Y

20.08/
510

27.56/
700

72.75/
33.0

5125.99/
84.0

JBES5675200_

JBe75

29.53 x 14.57 x 7.87/
750 x 370 x 200 †

Y

27.56/
700

12.60/
320

52.91/
24.0

3386.82/
55.5

JBES7537200_

JBe79

29.53 x 22.05 x 7.87/
750 x 560 x 200 †

Y

27.56/
700

20.08/
510

72.75/
33.0

5125.99/
84.0

JBES7556200_

JBe86

44.49 x 29.53 x 11.81/
1130 x 750 x 300

Y

42.52/
1080

27.56/
700

110.23/
50.0

14340.58/
235.0

JBES1175300_

† 7.87"/200 mm depth enclosure available with 11.81"/300 mm depth – replace digit 2 with 3 – Example: JBES3737304.
‡ N: Not Available, R: On request or separate accessories, Y: Supplied.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

563

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

4.72 x 4.72 x 3.74/
120 x 120 x 95

Enclosures and Junction Boxes

JBe10

JBES and ECES Series 316L Stainless Steel Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

JBES Series
Type

Dimensions
L x W x D in/mm

Hinged
Door ‡

One Gland Plate
Catalog Number

Two Gland Plates
Catalog Number

Three Gland Plate
Catalog Number

Four Gland Plates
Catalog Number

Ex e II 316L Stainless Steel Terminal Junction Boxes with Gland Plates 0.12"/3 mm Thick

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

For use only with Ex terminals (not supplied). M8 External earth crossing terminal. Mounting pan and rails to be ordered separately.

One Gland Plate

Two Gland Plate

Gland Plate Three

JBe36

8.66 x 10.24 x 5.91/
220 x 260 x 150

R

JBES2226151_

JBES2226152_

JBES2226153_

JBES2226154_

JBe36

8.66 x 10.24 x 5.91/
220 x 260 x 150

R

JBES2622151_

JBES2622152_

JBES2622153_

JBES2622154_

JBe46

8.66 x 14.57 x 7.87/
220 x 370 x 200 †

R

JBES2237201_

JBES2237202_

JBES2237203_

JBES2237204_

JBe47

8.66 x 14.57 x 7.87/
220 x 370 x 200 †

Y

JBES2637201_

JBES2637202_

JBES2637203_

JBES2637204_

JBe46

14.57 x 8.66 x 7.87/
370 x 220 x 200 †

R

JBES3722201_

JBES3722202_

JBES3722203_

JBES3722204_

JBe47

14.57 x 10.24 x 7.87/
370 x 260 x 200 †

Y

JBES3726201_

JBES3726202_

JBES3726203_

JBES3726204_

JBe55

14.57 x 14.57 x 7.87/
370 x 370 x 200 †

Y

JBES3737201_

JBES3737202_

JBES3737203_

JBES3737204_

JBe65

14.57 x 22.05 x 7.87/
370 x 560 x 200 †

Y

JBES3756201_

JBES3756202_

JBES3756203_

JBES3756204_

JBe75

14.57 x 29.53 x 7.87/
370 x 750 x 200 †

Y

JBES3775201_

JBES3775202_

JBES3775203_

JBES3775204_

JBe65

22.05 x 14.57 x 7.87/
560 x 370 x 200 †

Y

JBES5637201_

JBES5637202_

JBES5637203_

JBES5637204_

JBe77

22.05 x 22.05 x 7.87/
560 x 560 x 200 †

Y

JBES5656201_

JBES5656202_

JBES5656203_

JBES5656204_

JBe79

22.05 x 29.53 x 7.87/
560 x 750 x 200 †

Y

JBES5675201_

JBES5675202_

JBES5675203_

JBES5675204_

JBe75

29.53 x 14.57 x 7.87/
750 x 370 x 200 †

Y

JBES7537201_

JBES7537202_

JBES7537203_

JBES7537204_

JBe79

29.53 x 22.05 x 7.87/
750 x 560 x 200 †

Y

JBES7556201_

JBES7556202_

JBES7556203_

JBES7556204_

JBe86

44.49 x 29.53 x 11.81/
1130 x 750 x 300

Y

JBES1175301_

JBES1175302_

JBES1175303_

JBES1175304_

Four Gland Plate

† 7.87"/200 mm depth enclosure available with 11.81"/300 mm depth – replace digit 2 with 3 – Example: JBES3737304.
‡ N: Not Available, R: On request or separate accessories, Y: Supplied.

564

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBES and ECES Series 316L Stainless Steel Enclosure Accessories

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Catalog Number
Enclosure Length in/mm
Zinc Plated Steel Rail

Rail Length in/mm

Symmetrical Depth = 0.59"/15 mm

Asymmetrical

Pack

For fixing onto uprights with clip nut supplied.

Symmetrical

3.93/100

097246

—

1

7.09/180

6.30/160

097247

—

1

8.66/220

6.69/170

097240

097250

1

10.24/260

8.27/210

097241

097251

1

14.57/370

12.60/320

097242

097252

1

22.05/560

20.08/510

097243

097253

1

27.56/700

097244

097254

1

42.52/1080

097245

097255

1

Bar Length
in/mm

Catalog
Number

Pack

8.66/220

6.30/160

097230

1

10.24/260

7.87/200

097231

1

Enclosure Length in/mm
Zinc Plated Steel Uprights
Set of two.

14.57/370

12.20/310

097232

1

22.05/560

19.68/500

097233

1

29.53/750

27.17/690

097234

1

44.49/1130

42.13/1070

097235

1

Copper Bar (.47 x .16" / 12 x 4 mm)

Copper bar not perforated for cable clamps.

8.66/220

6.30/160

097270

1

10.24/260

7.87/200

097271

1

14.57/370

12.20/310

097272

1

22.05/560

19.68/500

097273

1

29.53/750

27.17/690

097274

1

44.49/1130

42.13/1070

097275

1

0.002 in2 to 0.006 in2 / 1.5 mm2 to 4 mm2 Capacity

097203

1

0.009 in2 to 0.025 in2 / 6 mm2 to 16 mm2 Capacity

097204

1

Cable Clamp for Copper Bar (.47 x .16" / 12 x 4 mm)

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

565

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

29.53/750
44.49/1130

Enclosures and Junction Boxes

Asymmetrical

4.72/120

JBES and ECES Series 316L Stainless Steel Enclosure Accessories

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Enclosure Dimensions Inches/Millimeters
Height
Width

Mounting Pan Dimensions
Inches/Millimeters

Catalog Number

Pack

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Mounting Pan – Zinc Plated Steel
4.72/120

4.72/120

3.93 x 3.93 / 100 x 100

097277

1

4.72/120

7.09/180

3.93 x 6.30 / 100 x 160

097278

1

7.09/180

7.09/180

6.30 x 6.30 / 160 x 160

097279

1

8.66/220

10.24/260

6.30 x 7.87 / 160 x 200

097280

1

8.66/220

14.57/370

6.30 x 12.20 / 160 x 310

097281

1

10.24/260

14.57/370

7.87 x 12.20 / 200 x 310

097282

1

14.57/370

14.57/370

12.20 x 21.20 / 310 x 310

097283

1

14.57/370

22.05/560

12.20 x 19.68 / 310 x 500

097284

1

14.57/370

29.53/750

12.20 x 27.17 / 310 x 690

097285

1

22.05/560

22.05/560

19.68 x 19.68 / 500 x 500

097286

1

22.05/560

29.53/750

19.68 x 27.17 / 500 x 690

097287

1

44.49/1130

29.53/750

27.17 x 42.13 / 690 x 1070

097288

1

Height = 3.94"/100 mm

097206

1

Height = 1.97"/50 mm

097207

1

097202

1

097201

1

097200

1

External dimensions: 10.24 x 6.50" / 260 x 165 mm
Internal dimensions: 9.06 x 5.12 x .071" / 230 x 130 x 18 mm

097263

1

External dimensions: 13.39 x 9.25" / 340 x 235 mm
Internal dimensions: 12.20 x 7.87 x 0.71" / 310 x 200 x 18 mm

097264

1

Spacers for Mounting at Back of Box

Set of two insulated pillars for copper bar .47 x .16" / 12 x 4 mm.

Conversion Kit — Door to Cover
Must be used to remove hinges.

Spare Hinges
Set of Two

Spare Mounting Brackets — Set of Two
One left and one right.

Self Adhesive Pocket for Drawings

Additional Door Padlocking Device
Padlock not supplied.

097209
1

Locking Bracket
Locks door in open position during wiring

566

097265

1

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBES and ECES Series 316L Stainless Steel Enclosure Accessories

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Dimensions Inches/Millimeters
Enclosure Width

Height

Gland Plate/Coupling Flange
Dimensions
Inches/Millimeters

Catalog Number

Pack

Spare Gland Plate
8.66/220

5.91/150

B/D

6.69 x 4.72 / 170 x 120

JBESGP221B

1

10.24/260

5.91/150

A/C

9.84 x 4.72 / 250 x 120

JBESGP261A

1

10.24/260

7.87/200

A/C

9.84 x 6.69 / 250 x 170

JBESGP262A

1

7.87/200

B/D

8.27 x 6.69 / 210 x 170

JBESGP262B

1

7.87/200

A/C

14.17 x 6.69 / 360 x 170

JBESGP372A

1

14.57/370

7.87/200

B/D

12.60 x 6.69 / 320 x 170

JBESGP372B

1

22.05/560

7.87/200

A/C

21.65 x 6.69 / 550 x 170

JBESGP562A

1

7.87/200

B/D

20.08 x 6.69 / 510 x 170

JBESGP562B

1

7.87/200

A/C

29.13 x 6.69 / 740 x 170

JBESGP752A

1

29.53/750

7.87/200

B/D

27.56 x 6.69 / 700 x 170

JBESGP752B

1

10.24/260

11.81/300

A/C

9.84 x 10.63 / 250 x 270

JBESGP263A

1

14.57/370

11.81/300

A/C

14.17 x 10.63 / 360 x 270

JBESGP373A

1

14.57/370

11.81/300

B/D

12.60 x 10.63 / 320 x 270

JBESGP373B

1

22.05/560

11.81/300

A/C

21.65 x 10.63 / 550 x 270

JBESGP563A

1

22.05/560

11.81/300

B/D

20.08 x 10.63 / 510 x 270

JBESGP563B

1

29.53/750

11.81/300

A/C

29.13 x 10.63 / 740 x 270

JBESGP753A

1

29.53/750

11.81/300

B/D

27.56 x 10.63 / 700 x 270

JBESGP753B

1

7.87/200

A/C

9.84 x 4.72 / 250 x 120

JBESCF262A

1

Coupling Flange
10.24/260
14.57/370

7.87/200

A/C

14.17 x 6.69 / 360 x 170

JBESCF372A

1

14.57/370

7.87/200

B/D

12.60 x 6.69 / 320 x 170

JBESCF372B

1

22.05/560

7.87/200

A/C

21.65 x 6.69 / 550 x 170

JBESCF562A

1

22.05/560

7.87/200

B/D

20.08 x 6.69 / 510 x 170

JBESCF562B

1

29.53/750

7.87/200

A/C

29.13 x 6.69 / 740 x 170

JBESCF752A

1

29.53/750

7.87/200

B/D

27.56 x 6.69 / 700 x 170

JBESCF752B

1

14.57/370

11.81/300

A/C

14.17 x 10.63 / 360 x 270

JBESCF373A

1

14.57/370

11.81/300

B/D

12.60 x 10.63 / 320 x 270

JBESCF373B

1

22.05/560

11.81/300

A/C

21.65 x 10.63 / 550 x 270

JBESCF563A

1

22.05/560

11.81/300

B/D

20.08 x 10.63 / 510 x 270

JBESCF563B

1

29.53/750

11.81/300

A/C

29.13 x 10.63 / 740 x 270

JBESCF753A

1

29.53/750

11.81/300

B/D

27.56 x 10.63 / 700 x 270

JBESCF753B

1

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

567

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

22.05/560
29.53/750

Enclosures and Junction Boxes

10.24/260
14.57/370

JBES and ECES Series 316L Stainless Steel Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

JBES Series for Terminal Junction Box Application Only.
Use the table shown below to select the proper size junction box based upon your requirements. Custom drilled and equipped boxes can be
configured using our drilling guide available online at www.egsatx.com.
Define maximum cable entries according to number of modules available per side.
Number of Modules

M20

1

M25

1

M32

1

M40

2

M50

3

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Cable Entry Metric Thread

H

Dimensions Inches/Millimeters
Height
Width
Depth

Type

Number of Modules
A/C
B/D

Number of Modules †
A’/C’
B’/D’

Terminal Dim.
H — in/mm

JBe10

4.72/120

4.72/120

3.74/95

5

5

–

–

8.66/220

JBe20

4.72/120

7.09/180

3.74/95

9

5

–

–

8.66/220

JBe30

7.09/180

7.09/180

3.74/95

9

9

–

–

8.66/220

JBe36

8.66/220

10.24/260

5.91/150

11

7

9

5

8.66/220

JBe36

10.24/260

8.66/220

5.91/150

7

11

5

9

10.24/260

JBe46

8.66/220

14.57/370

7.87/200

31

16

19

7

10.24/260

JBe46

14.57/370

8.66/220

7.87/200

16

31

7

9

14.57/370

JBe47

14.57/370

10.24/260

7.87/200

20

31

14

20

14.57/370

JBe47

10.24/260

14.57/370

7.87/200

31

20

19

10

10.24/260

JBe55

14.57/370

14.57/370

7.87/200

31

31

19

18

14.57/370

JBe65

22.05/560

14.57/370

7.87/200

31

49

19

31

22.05/560

JBe65

14.57/370

22.05/560

7.87/200

49

31

34

18

14.57/370

JBe75

29.53/750

14.57/370

7.87/200

31

66

19

47

29.53/750

JBe75

14.57/370

29.53/750

7.87/200

66

31

49

18

14.57/370

JBe77

22.05/560

22.05/560

7.87/200

49

49

34

31

22.05/560

JBe79

29.53/750

22.05/560

7.87/200

49

66

34

45

29.53/750

JBe79

22.05/560

29.53/750

7.87/200

66

49

49

31

22.05/560

JBe86

44.49/1130

29.53/750

11.81/300

102

–

82

–

44.49/1130

2. Maximum rail arrangement according to physical dimensions.
Maximum Quantity of Horizontal Rails Per Quantity
0.004/2.5

0.006/4

0.009/6

0.016/10

0.025/16

0.054/35

0.078/50

0.109/70

JBe10/20/30/36

1

1

1

1

1

1

0

0

JBe36/46/47

2

2

2

1

1

1

0

0

JBe46/47/55/65/75

3

3

2

2

2

2

1

1

JBe65/77/79

5

5

4

4

4

3

2

2

JBe75/79

7

7

6

6

5

4

3

2

JBe86

10

10

9

9

8

6

4

4

Terminal Capacity

(in2/mm2)

† Enclosure with gland plate.

568

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBES and ECES Series 316L Stainless Steel Enclosures

Increased Safety

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

3. Defining maximum terminal block quantity according to power dissipation:
•	 Junction boxes used for instrumentation applications carry very low current levels. Therefore there is no risk of overheating whatever the
number of terminals inside the box.
•	 For applications other than instrumentation, the following tables allow you to define your junction box depending on the number of terminals
and the maximum authorized current being carried with feed-through terminals.
•	 For single feed terminals using cross connection, consult factory for calculation.
For other terminal block configurations, please consult our drilling guide available online at www.egsatx.com.

Small Junction Boxes
Type

Type

JBe10
JBe20
JBe30
5 x 5 x 4" 5 x 7 x 4" 7 x 7 x 4"
120 x 120 x 120 x 180 x 180 x 180 x
95 mm
95 mm
95 mm

JBe36
JBe46
JBe47
JBe55
9 x 10 x 6" 9 x 15 x 8" 10 x 15 x 8' 15 x 15 x 8"
220 x 260 x 220 x 370 x 260 x 370 x 370 x 370 x
150 mm
200 mm
200 mm
200 mm

T Rating:
T6 @ Ta 131 °F/55° C

Qty.
1 max.

10
16 A

21
16 A

21
16 A

0.004 in2/
2.5 mm2

Qty.
1 max.

33
16 A

50
14 A

70
12 A

110
10 A

0.006 in2/
4 mm2

Qty.
1 max.

8
25 A

17
25 A

16
25 A

0.006 in2/
4 mm2

Qty.
1 max.

21
25 A

38
20 A

62
16 A

80
15 A

0.009 in2/
6 mm2

Qty.
1 max.

6
32 A

13
32 A

13
32 A

0.009 in2/
6 mm2

Qty.
1 max.

19
32 A

22
32 A

23
32 A

26
32 A

0.016 in2/
10 mm2

Qty.
1 max.

5
50 A

10
50 A

9
50 A

0.016 in2/
10 mm2

Qty.
1 max.

12
50 A

14
50 A

15
50 A

20
45 A

0.024 in2/
16 mm2

Qty.
1 max.

8
63 A

10
63 A

17
50 A

20
50 A

0.039 in2/
25 mm2

Qty.
1 max.

12
80 A

14
80 A

16
76 A

20
76 A

0.054 in2/
35 mm2

Qty.
1 max.

9
100 A

11
100 A

12
100 A

16
93 A

Hinged Junction Boxes
Type
T Rating:
T6 @ Ta 104 °F/40 °C
T5 @ Ta 131 °F/55° C

CAe6
CAe7
CAe8
CAe10
CAe11
16 x 12 x 8" 20 x 16 x 8" 24 x 16 x 10" 32 x 24 x 12" 40 x 32 x 12"
400 x 300 x 500 x 400 x 610 x 400 x 820 x 610 x 1020 x 810 x
206 mm
206 mm
257 mm
300 mm
300 mm

0.054 in2/
35 mm2

Qty.
1 Max.

12
100 A

16
100 A

16
100 A

—

—

0.078 in2/
50 mm2

Qty.
1 Max.

8
125 A

12
125 A

16
125 A

—

—

0.109 in2/
70 mm2

Qty.
1 Max.

8
160 A

10
160 A

12
160 A

—

—

0.147 in2/
95 mm2

Qty.
1 Max.

8
200 A

10
200 A

12
200 A

—

—

0.186 in2/
120 mm2

Qty.
1 Max.

—

8
250 A

8
250 A

12
200 A

16
150 A

0.233 in2/
150 mm2

Qty.
1 Max.

—

—

6
250 A

9
250 A

12
190 A

0.287 in2/
185 mm2

Qty.
1 Max.

—

—

—

8
300 A

10
240 A

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

569

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

0.004 in2/
2.5 mm2

Enclosures and Junction Boxes

T Rating:
T6 @ Ta 131 °F/55° C

Non-Hinged Junction Boxes

JBES and ECES Series 316L Stainless Steel Enclosure Dimensions

Increased Safety

Dimensions in Inches/Millimeters

0.08/2

Box 3.74/95 Depth

Fix. J

0.08/2

2

0.73/
18.50

Fix. J

2

0.31/8

Box 7.87/200 or 11.81/300 Depth

Mounting Bracket
1.30/33

Fix. J

0.73/
18.50

Enclosures and Junction Boxes

0.31/8

0.65/16.5

0.35/9

0.10/2.5

Fix. J

0.73/18.5

0.35/9

0.45/11.5

Fix. I

0.35/9

Fix. I

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

0.45/11.5

L x W x D in/mm
A
B
Box Depth 3.74/95
4.72 x 4.72 x 3.74/
4.72/120 4.72/120
120 x 120 x 95
4.72 x 7.09 x 3.74/
4.72/120 7.09/180
120 x 180 x 95
7.06 x 7.09 x 3.74
7.09/180 7.09/180
180 x 180 x 95/
Box Depth 7.87/200
8.66 x 14.57 x 7.87/
8.66/220 14.57/370
220 x 370 x 200/
14.57 x 10.24 x 7.87/
14.57/370 10.24/260
370 x 260 x 200
14.57 x 14.57 x 7.87/
14.57/370 14.57/370
370 x 370 x 200
22.05 x 14.57 x 7.87/
22.05/560 14.57/370
560 x 370 x 200
29.53 x 14.57 x 7.87/
29.53/750 14.57/370
750 x 370 x 200
22.05 x 22.05 x 7.87/
22.05/560 22.05/560
560 x 560 x 200
29.53 x 22.05 x 7.87/
29.53/750 22.05/560
750 x 560 x 200
Box Depth 11.81/300
14.57 x 14.57 x 11.81/
14.57/370 14.57/370
370 x 370 x 300
22.05 x 14.57 x 11.81/
22.05/560 14.57/370
560 x 370 x 300/
29.53 x 14.57 x 11.81/
29.53/750 14.57/370
750 x 370 x 300
22.05 x 22.05 x 11.81/
22.05/560 22.05/560
560 x 560 x 300
29.53 x 22.05 x 11.81/
29.53/750 22.05/560
750 x 560 x 300
44.49 x 29.53 x 11.81/
44.49/1130 29.53/750
1130 x 750 x 300

570

C

D

E

F

G

H

I

J

K

3.74/95

5.00/127

5.00/127

4.09/104

3.31/84

3.46/88

3.74/95

5.00/127

7.36/187

4.09/104

5.67/144 5.83/148 8.66/220 7.87/200 0.06/1.5

3.74/95

7.36/187

7.36/187

6.47/164

5.67/144 5.83/148 8.66/220 7.87/200 0.06/1.5

7.87/200

6.54/166 12.44/316 5.51/140 11.42/290 17.17/436 7.28/185 16.02/407 0.06/1.5

6.30/160 5.51/140 0.06/1.5

7.87/200 12.44/316 8.11/206 11.42/290 7.09/180 12.83/326 13.19/335 11.69/297 0.06/1.5
7.87/200 12.44/316 12.44/316 11.42/290 11.42/290 17.17/436 13.19/335 16.02/407 0.08/2
7.87/200 19.92/506 12.44/316 18.90/480 11.42/290 17.17/436 20.67/525 16.02/407 0.08/2
7.87/200

63.74/95 12.44/316 26.38/670 11.42/290 17.17/436 28.15/715 16.02/407 0.08/2

7.87/200 19.92/506 19.92/506 18.90/480 18.90/480 24.65/626 20.67/525 23.50/597 0.08/2
7.87/200 24.40/696 19.92/506 26.38/670 18.90/480 24.65/626 28.15/715 23.50/597 0.08/2
11.81/300 12.44/316 12.44/316 11.42/290 11.42/290 17.17/436 13.19/335 16.02/407 0.08/2
11.81/300 19.92/506 12.44/316 18.90/480 11.42/290 17.17/436 20.67/525 16.02/407 0.08/2
11.81/300 63.74/95 12.44/316 26.38/670 11.42/290 17.17/436 28.15/715 16.02/407 0.08/2
11.81/300 19.92/506 19.92/506 18.90/480 18.90/480 24.65/626 20.67/525 23.50/597 0.08/2
11.81/300 24.40/696 19.92/506 26.38/670 18.90/480 24.65/626 28.15/715 23.50/597 0.08/2
11.81/300 42.36/1076 19.92/506 41.34/1050 26.38/670 32.13/816 103.74/95 30.98/787 0.08/2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBDR Series Pre-Drilled Round Junction Boxes

Flameproof

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Applications

2 Entry Version with Cable Glands

Features

3 Entry Version

4 Entry Version

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

•	 IK10 (20 Joules) high impact resistant box.
•	 Pillar type terminal block (4 x terminals) for easy connection.
•	 Terminal capacity: 0.006 x 0.006 in2 / 4 x 4 mm2 or 0.003 x
0.009 in2 / 2 x 6 mm2.
•	 Internal Earth: ground plate with 4 x M4 screws for connection
to 4 mm diameter lugs.
•	 External Earth: M5 screw.
•	 Back plate supplied.
•	 Operating temperature -40 °F/-40 °C to 131 °F/55 °C.

Enclosures and Junction Boxes

•	 Small terminal junction boxes designed to facilitate electrical
connections in hazardous areas.
•	 Designed for use in Zone 1 or 2 areas, where flammable gases
or vapors are present either continuously or intermittently.
•	 Ideal for use in wet or corrosive atmospheres such as:
	 — Petroleum refineries
	 — Chemical refineries
	 — Other industrial process facilities
•	 Designed for use in Zone 21 or 22 areas, where flammable
dusts are present either continuously or intermittently such as:
	 — Food processing
	 — Dairy
	 — Brewing
	 — Silos
	 — Other facilities

Standard Materials
•	 Housing: gray painted marine grade aluminum
•	 Hardware: stainless steel

Certifications and Compliances
•	
	
	
	
	
	
	
	
	
	
	
	
	
	
•	
•	
•	
•	
•	

Certification Type BR1d
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e IIC
– T Rating: T6 to T4 = 104 °C/40 ºC
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T203 °F/T95 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 50230
— ATEX Certificate: LCIE 02 ATEX 6056
— IEC Certificate: LCIE Ex 02.005
— Other Certifications: GOST
Ingress Protection (solid and liquid): IP66
Impact Resistance (shock): IK10
Internal Volume: ≤ 2dm3 (2 liters)
Ex Standards: EN/IEC 60079-0; 60079-1; 61241-0; 61241-1
Other Standards: EN/IEC 60529 (IP), 62262 (IK)

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

571

JBDR Series Pre-Drilled Round Junction Boxes

Flameproof

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Catalog Numbering Guide
JBDR

1

Series
ATEX/IEC Certified:
JB - Junction Box
D - Flameproof
R - Round Shape in Aluminum

G

Entry Size: †
0 - M20
5 - M25
3 - 3/4" NPT
1 - 1" NPT
Number of Entries:
1
2
3
4

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

0

Options:
G - Cable Gland supplied
T - With Pillar Terminal Block

Equipment

Weight lb/kg

Volume in3/dm3

Catalog Number

Threaded Entries with M25 Integrated Cable Gland:
For unarmored cable: – sealed Ø: 0.35 to 0.59" / 9 to 15 mm (093496)

2 Entry

2 x M25 entries (feed through)
2 integrated cable glands supplied

1.76/0.8

122.05/2

JBDR25G

3 x M25 entries (in a “T”)
3 integrated cable glands supplied

1.76/0.8

122.05/2

JBDR35G

4 x M25 entries (in a cross)
4 integrated cable glands supplied

1.98/0.9

122.05/2

JBDR45G

2 x M20 entries (feed through)

0.7/1.54

122.05/2

JBDR20

3 x M20 entries (in a “T”)

0.7/1.54

122.05/2

JBDR30

4 x M20 entries (in a cross)

1.76/0.8

122.05/2

JBDR40

2 x 3/4” NPT entries (feed through)

0.7/1.54

122.05/2

JBDR23

3 x 3/4” NPT entries (in a “T”)

0.7/1.54

122.05/2

JBDR33

4 x 3/4” NPT entries (in a cross)

1.76/0.8

122.05/2

JBDR43

1.76/0.8

122.05/2

JBDR41

Weight lb/kg

Volume in3/dm3

Catalog Number

0.22/0.1

24.41/0.4

TBP44

1.32/0.6

54.92/0.9

093496

Threaded Entries for M20 Cable Gland – Not Supplied

3 Entry

Threaded Entries for NPT 3/4” Cable Gland – Not Supplied

4 Entry

Threaded Entries for NPT 1” Cable Gland – Not Supplied
4 x 1” NPT entries (in a cross)

Accessories
Description
Pillar Terminal Block
4 terminals
0.006 x 0.006 in2 / 4 x 4 mm2 or 0.003 x 0.009 in2 / 2 x 6 mm2 cables
M25 Integrated Cable Gland
for unarmored cables (dia. 0.35 to 0.59" / 9 to 15 mm)

† For other entry size, use adaptor.

572

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBDR Series Pre-Drilled Round Junction Box Dimensions

Flameproof

Dimensions in Inches/Millimeters
2 Entry Version
0.28/7

Enclosures and Junction Boxes

0.28/
7

7.68/195

0.35/9

3.23/82
5.91/150

3.15/80

1.97/
50

3.35/85

3.23/82
4.33/110

3 Entry Version
1.97/50

0.28/7

5.98/152

3.15/80

3.23/82

5.12/130

1.61/
41

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

0.35/9

0.28/
7
3.23/82
4.33/110
5.91/150

3.35/85

7.68/195

3 Entry Version
0.28/7

7.68/195

3.23/82

1.61/
41

3.15/80

1.97/
50

0.35/9

0.28/
7
3.23/82
4.33/110
5.91/150

3.35/85

7.68/195

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

573

JBDA and JBDF – ECDA and ECDF Series Customized Enclosures

Flameproof

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Applications
•	 Designed for use in Zones 1, 2, 21 and 22 in the oil and gas
industry such as:
	 — Petroleum
	 — Chemical
	 — Refineries
	 — Other industrial process facilities
•	 Junction box applications:
— JBD series enclosures may be customized to house
terminal blocks.
•	 Enclosure and control applications:
— ECD series enclosures may be customized to house a large
range of components such as:
	 – Control units
	 – Breakers
	 – Starters
	 – Relays
	 – Meters
	 – Etc.

Features
•	
•	
•	
•	
•	
•	
•	
•	

JBDA

ECDF

ECDA

JBDF

Customized Enclosures

Enclosures are available in a wide range of sizes.
Precision machined flameproof joint between body and cover.
Wall thickness suitable for all sizes of cable entries.
External fixing lugs.
Internal mounting pan.
Square and round windows available in a wide range of sizes.
Machining and drilling must be completed in our workshops.
Power dissipated calculation including cables must be
completed according to each size of certified enclosure.

Standard Materials
•	 Enclosures: gray painted cast iron or marine grade aluminum
alloy
•	 Hardware: stainless steel

Options
•	 Indirect cable entries available through Ex e connection
enclosure.
•	 Factory assembled and wired.
•	 Empty enclosure with Ex “U” component marking for
re-certification by notified body (CF10B to CF70B).

Certifications and Compliances
•	
	
	
	
	
	
	
	
	
	
	
	
	
	
	

574

Certification Type CF2/A/B/C
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e IIB
– T Rating: T6 to T2
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T203 °F/T95 °C to T554 °F/T290 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C.
— CE Declaration of Conformity: 50254
— ATEX Certificate: LCIE 03 ATEX 6061X
— IEC Certificate: LCIE Ex 03.006X
— Other Certifications: GOST
— Internal Volume: ≤ 2dm3 (2 liters)

•	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
	
•	
	
	
	
	

Certification Type CF10B to CF70B, CF10C to CF70C
— Gas, Zones 1 and 2
II 2 G
– Conforming to ATEX 94/9/CE: CE 0081
– ATEX/IEC Protection CF10B to CF70B: Ex e IIB
– ATEX/IEC Protection CF10C to CF70C: Ex e IIC
– T Rating: T6 to T4
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T80 °C to T130 °C
— Ambient Temperature CF30B, CF70B, CF70C: -4 °F/-20 °C 	
to 131 °F/55 °C
— Ambient Temperature CF10B, CF20B, CF40B, CF50B,
CF10C, CF30C, CF50C: -40 °F/-40 °C to 131 °F/55 °C.
— Ambient Temperature CF60B: -58 °F/-50 °C to 131 °F/55 °C
— CE Declaration of Conformity: 50229
— ATEX Certificate: LCIE 02 ATEX 6057X
— IECEx Certificate: IECEx LCI 08.0023X
— Other Certifications: GOST
— Internal Volume: ≤ 2dm3 (2 liters)
Certification Type CF1A/B/D/E
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e IIC
– T Rating: T6 to T2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBDA and JBDF – ECDA and ECDF Series Customized Enclosures

Flameproof

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

	

•	
	
	
	
	
	
	
	
	
	
	
	
	
•	
•	
•	
•	

Certification Type JBEW
— Gas, Zones 1 and 2
II 2 G
– Conforming to ATEX 94/9/CE: CE 0081
– ATEX/IEC Protection: Ex d IIB + H2
– T Rating: T6 to T4
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T80 °C to T130 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 50279
— ATEX Certificate: LCIE 07 ATEX 6069X
— Internal Volume: > 2dm3 (2 liters)
Ingress Protection (solid and liquid): IP66
Impact Resistance (shock): IK10
Ex Standards: EN/IEC 60079-0; 60079-1; 61241-0; 61241-1
Other Standards: EN/IEC 60529 (IP), 62262 (IK)

Catalog Numbering Guide
JBDA

B

Series
ATEX/IEC Certified:
JB - Junction Box
EC - Enclosure and Controls
D - Flameproof
A - Aluminum
F - Cast Iron

–– –– ––

U

Dimensions (in/mm):
Length x Width x Depth

(see ordering information on following pages)

Classification:
B - IIB
C - IIC

Options:

(options must be listed alphabetically)

U - Component Certification “U”
# - Customized Enclosure (6 Digit number will be
assigned at time of order placement.)

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

575

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

	
	
	

— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
– Surface Temperature: T203 °F/T95 °C to T554 °F/T290 °C
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C.
— CE Declaration of Conformity: 50257
— ATEX Certificate: LCIE 03 ATEX 6044X
— IEC Certificate: LCIE Ex 03.003X
— Other Certifications: GOST
— Internal Volume CF1A/B/D/E: > 2dm3 (2 liters)
— Internal Volume CF1E: ≤ 2dm3 (2 liters)
Certification Type CF10BU to CF70BU
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex e IIB
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
— Ambient Temperature CF30BU, CF60BU, CF70BU:
-4 °F/-20 °C to 131 °F/55 °C
— Ambient Temperature CF10BU, CF20BU, CF40BU, CF50BU:
-40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 5C238
— ATEX Certificate: LCIE 07 ATEX 0005U
— Internal Volume: > 2dm3 (2 liters)

Enclosures and Junction Boxes

	
	
	
	
	
	
	
	
	
	
	
•	
	
	
	
	
	
	
	

JBDA and JBDF – ECDA and ECDF Series Customized Enclosures

Flameproof

Zone 1 and 2 – 21 and 22
II 2 GD
ATEX / IEC
IP66 – IK10

Type

Dimensions in/mm
LxWxD

Hinged
Door

Weight
lb/kg

Volume
in3/dm3

Catalog Number †
JBD Series
ECD Series

Ex d IIB Enclosure in Cast Iron with Flanged Flameproof Joint
CF2C

5.12 x 5.12 x 3.54/
130 x 130 x 90

–

8.82/
4

183.07/
3

JBDFB131309

ECDFB131309

CF2A

8.07 x 5.71 x 5.00/
205 x 145 x 127

–

20.72/
9.4

183.07/
3

JBDFB201413

ECDFB201413

CF2B

10.63 x 7.48 x 4.72/
270 x 190 x 120

–

27.78/
12.6

427.17/
7

JBDFB271912

ECDFB271912

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

Enclosures and Junction Boxes

Ex d IIB Enclosure in Cast Aluminum with Flanged Flameproof Joint
CF10B

10.24 x 10.63 x 8.19/
260 x 270 x 208

–

19.84/
9

1037.40/
17

JBDAB262720

ECDAB262720

CF20B

15.57 x 10.63 x 8.19/
370 x 270 x 208

–

28.66
13

1464.57/
24

JBDAB372720

ECDAB372720

CF30B

13.39 x 12.60 x 9.06/
340 x 320 x 230

Yes

63.93/
29

4149.61/
68

JBDAB343223

ECDAB343223

CF40B

17.91 x 12.60 x 13.66/
455 x 320 x 347

Yes

110.23/
50

7688.99/
126

JBDAB453234

ECDAB453234

CF50B

17.97 x 17.32 x 13.66/
455 x 440 x 347

Yes

143.30/
65

14645.70/
240

JBDAB454434

ECDAB454434

CF60B

26.77 x 17.32 x 16.26/
680 x 440 x 413

Yes

233.69/
106

23066.98/
378

JBDAB684441

ECDAB684441

CF70B

26.77 x 25.20 x 16.26/
680 x 640 x 413

Yes

286.60/
130

23311.07/
382

JBDAB686441

ECDAB686441

Ex d IIC Enclosure in Cast Aluminum with Spigot Flameproof Joint
CF1E

5.51 x 6.38 x 3.94/
140 x 162 x 100

–

3.31/
1.5

134.25/
2.2

JBDAC141610

ECDAC141610

CF1B

8.27 x 9.06 x 4.92/
210 x 230 x 125

–

8.82/
4

335.63/
5.5

JBDAC212312

ECDAC212312

CF1A

11.61 x 10.43 x 7.68/
295 x 265 x 195

–

22.05/
10

585.83/
9.6

JBDAC292619

ECDAC292619

CF1D

14.17 x 13.19 x 7.87/
360 x 335 x 200

–

22.05/
10

890.95/
14.6

JBDAC363320

ECDAC363320

Ex d IIC Enclosure in Cast Aluminum with Screwed Flameproof Joint
CF10C

9.05 x 8.46 x 9.37/
230 x 215 x 238

–

26.46/
12

976.38/
16

JBDAC232124

ECDAC232124

CF30C

12.60 x 13.39 x 9.21/
320 x 340 x 234

–

61.73/
28

4149.61/
68

JBDAC323423

ECDAC323423

CF50C

17.32 x 17.91 x 13.58/
440 x 455 x 345

–

141.10/
64

14950.82/
245

JBDAC444534

ECDAC444534

JBDFC686445

ECDFC686445

Ex d IIC Enclosure in Cast Iron with Screwed Flameproof Joint
CF70C

26.77 x 25.20 x 17.72/
680 x 640 x 450

Yes

683.43/
310

23311.07/
382

† Options: Component Certification “U” and/or Customized Enclosure # add digits as per examples: JBDAB2627203 #, JBDAB2627203U #.

576

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBDA and JBDF – ECDA and ECDF Series Customized Enclosure Dimensions

Flameproof

A
D (L)

B
(W)
C

Type

Dimensions in/mm
LxWxD

A
M20

Maximum Quantity of Threaded Entries Per Side
B
C
D
M20
M20
M20

Max.
Size †

Rail Length Capacity
for Terminal Block in/mm
(L)
(W)

CF2C

5.12 x 5.12 x 3.54/
130 x 130 x 90

1

2

1

2

M25

–

2.52/
64

CF2A

8.07 x 5.71 x 5.00/
205 x 145 x 127

1

3

1

1

M32

–

4.72/
120

CF2B

10.63 x 7.48 x 4.72/
270 x 190 x 120

2

4

2

4

M50

–

6.38/
162

Ex d IIB Enclosure in Cast Aluminum
10.24 x 10.63 x 8.19/
260 x 270 x 208

8

6

8

6

M75

6.10/
155

5.83/
148

CF20B

15.57 x 10.63 x 8.19/
370 x 270 x 208

6

12

6

12

M75

10.24/
260

5.83/
148

CF30B

13.39 x 12.60 x 9.06/
340 x 320 x 230

8

8

8

8

M75

10.24/
260

8.58/
218

CF40B

17.91 x 12.60 x 13.66/
455 x 320 x 347

16

28

16

28

M75

12.99/
330

7.87/
200

CF50B

17.97 x 17.32 x 13.66/
455 x 440 x 347

26

26

26

26

M75

11.61/
295

12.99/
330

CF60B

26.77 x 17.32 x 16.26/
680 x 440 x 413

26

51

26

51

M100

21.26/
540

11.81/
300

CF70B

26.77 x 25.20 x 16.26/
680 x 640 x 413

38

42

38

42

M100

20.87/
530

20.87/
530

Ex d IIC Enclosure in Cast Iron
CF1E

5.51 x 6.38 x 3.94/
140 x 162 x 100

1

2

1

2

M32

–

3.90/
99

CF1B

8.27 x 9.06 x 4.92/
210 x 230 x 125

1

3

2

3

M32

–

6.10/
155

CF1A

11.61 x 10.43 x 7.68/
295 x 265 x 195

6

6

5

6

M63

7.48/
190

7.48/
190

CF1D

14.17 x 13.19 x 7.87/
360 x 335 x 200

16

17

15

17

M63

7.09/
180

9.84/
250

Ex d IIC Enclosure in Cast Aluminum
CF10C

9.05 x 8.46 x 9.37/
230 x 215 x 238

5

5

5

5

M75

4.72/
120

4.13/
105

CF30C

12.60 x 13.39 x 9.21/
320 x 340 x 234

8

8

8

8

M75

10.24/
260

8.46/
215

CF50C

17.32 x 17.91 x 13.58/
440 x 455 x 345

26

26

26

26

M75

11.61/
295

12.99/
330

† Consult your local sales representative for quantity.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

577

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

CF10B

Enclosures and Junction Boxes

Ex d IIB Enclosure in Cast Iron

JBDA and JBDF – ECDA and ECDF Series Customized Enclosure Dimensions

Flameproof

Dimension in Inches/Millimeters

JBDF and ECDF: CF2C
5.12/130
Fix. 3.39/86

3.54/90
2.56/65

Enclosures and Junction Boxes

5.19/130
3.54/90

Fix. 3.39/86

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

JBDF and ECDF: CF2A and CF2B

0.28/7

3.54/90

0.31/8

JBDA and ECDA: CF10B and CF20B

Type

A

B

JBDA and ECDA: CF30B and CF70B

C

D

E

F

G

H

K

Ø

JBDF and ECDF: CF2A and CF2B
CF2A

7.95/202

5.67/144

3.78/96

6.14/156

6.06/154

2.58/65.5

3.86/98

6.14/156

0.39/10

0.27/7

CF2B

10.51/267

736/187

4.53/115

7.95/202

7.78/200

3.19/81

4.80/122

7.95/202

0.47/12

0.27/7

JBDA and ECDA: CF10B and CF20B
CF10B

10.20/259

10.63/270

8.15/207

7.48/190

6.89/175

6.34/161

5.51/140

9.65/245

0.59/15

0.43/11

CF20B

14.53/369

10.63/270

8.15/207

11.81/300

6.89/175

6.34/161

9.84/250

9.65/245

0.59/15

0.43/11

JBDA and ECDA: CF30B and CF70B
CF30B

13.39/340

12.60/320

9.37/238

11.22/285

10.43/265

6.34/161

11.73/298

10.94/278

0.79/20

0.35/9

CF40B

17.91/455

12.60/320

14.84/377

15.55/395

10.43/265

9.96/253

15.39/391

10.08/256

0.98/25

0.43/11

CF50B

17.91/455

17.32/440

14.96/380

15.75/400

14.80/376

9.96/253

15.39/391

14.80/376

0.98/25

0.43/11

CF60B

26.77/680

17.32/440

17.52/445

24.02/610

14.80/376

11.50/292

24.25/616

14.80/376

0.98/25

0.55/14

CF70B

26.77/680

25.20/640

17.52/445

24.02/610

22.68/576

11.50/292

24.25/616

22.68/576

0.98/25

0.55/14

578

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

JBDA and JBDF – ECDA and ECDF Series Customized Enclosure Dimensions

Flameproof

Dimension in Inches/Millimeters

JBDA and ECDA: CF1D

80

e

et

am

Di

0.47/
12

JBDA and ECDA: CF1B and CF1E Type

7.87/200

/2

.02

1
r1

0.59/
15

Enclosures and Junction Boxes

14.17/360

13.19/335

12.60 x 11.61/

JBDF and ECDF: CF10C to CF70C

6.10/155

JBDA and ECDA: CF1A Type
0.59/15

10.43/265

0.43/
11

0.35/9
11.61/295

Type

A

B

7.68/195

C

D

E

F

G

H

K

Ø

JBDF and ECDF: CF10C to CF70C
CF10C

9.06/230

8.46/215

9.37/238

7.09/180

6.50/165

6.89/175

7.40/188

6.81/173

0.79/20

0.35/9

CF30C

12.60/320

13.39/340

9.21/234

10.67/271

11.42/290

6.06/154

10.94/278

11.73/298

0.79/20

0.35/9

CF50C

17.32/440

17.91/455

13.58/345

15.20/386

15.79/401

9.49/241

14.80/376

15.39/391

0.98/25

0.43/11

CF70C

26.77/680

25.20/640

17.72/450

24.25/616

22.68/576

11.42/290

24.25/616

22.68/576

0.98/25

0.55/14

JBDA and ECDA: CF1B and CF1E Type
CF1B

9.06/230

8.27/210

4.92/125

6.89/175

6.89/175

3.54/90

8.27/210

3.94/100

0.59/15

0.35/9

CF1E

5.51/140

6.38/162

4.76/121

4.72/120

4.72/120

3.15/80

4.72/120

4.72/120

0.47/12

0.35/9

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

579

Enclosures and Junction Boxes: Hazardous Location Outlet Boxes — Cable

10.31/262

GUBB, GUBBD and GUBBM Cast Junction Boxes
Explosionproof, Dust-Ignitionproof
UNILETS® for Use with Threaded Metal Conduit.
GUBB
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4, 7BCD, 9EFG

GUBBD
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4

GUBBM
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4

Applications
•	 Explosionproof and dust-ignitionproof, for use in classified
locations.
•	 Corrosion-resistant: ideal indoors or outdoors.
•	 Junction or pull box for pulling and splicing of wires and as an
enclosure for electrical devices.
•	 Ideal where number and size of conductors require a junction
box with additional space.

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Features
•	 All GUBB/GUBBD/GUBBM Series Boxes
— Provided with mounting lugs.
— Furnished with covers.
— All conduit hubs and openings provide a minimum of five full
threads to meet UL requirements.
— Accurately tapped, tapered conduit threads provide tight,
rigid joints and ground continuity.
• GUBB Series
— Wide selection of sizes and locations for drilled and tapped
conduit openings.
— Suitable for use as an enclosure for relays, instrument and
other control apparatus in classified locations.
— Available in high tensile strength malleable iron or copperfree
aluminum bodies.
— Provided with mounting lugs.
— O-Rings standard for forms 1, 2 and 3 to provide raintight fit.
•	 GUBBD Series (Dome and Plate)
— GUBB junction boxes with dome cover and mounting plate
provide flexibility for a wide variety of applications.
— Ideal for housing relays, contactors, terminal blocks and
other classified area applications.
— Mounting plate can be drilled to accommodate a variety of
devices.
— Dome cover has nominal depth of 6”/152mm or 17”/431mm,
depending upon box selected. Provides significant increase
in cubic inch capacity.
— O-Rings standard to provide raintight fit.
— Provided with mounting lugs.
•	 GUBBM Series (Instrument)
— GUBBM junction boxes serve as an enclosure for meters,
gauges and similar devices.
— Complete with round, explosionproof glass window cover.
Permits direct reading of enclosed instrument.
— Furnished with one 3/4” drilled and tapped entry.
— Mounted bosses provided in back of GUBBM can be drilled
and tapped for fastening of instrument mounting bracket.
— O-Rings standard to provide raintight fit.
— Provided with mounting lugs.

Standard Materials
•	 GUBB bodies: copperfree (4/10 of 1% max.) aluminum or
malleable iron bodies
•	 GUBBD bodies: malleable iron bodies
•	 GUBB, GUBBD covers: copperfree (4/10 of 1% max.) aluminum
•	 GUBBM bodies: copperfree (4/10 of 1% max.) aluminum
•	 GUBBM covers: copperfree (4/10 of 1% max.) aluminum
and glass
•	 O-Ring: neoprene

580

GUBB

GUBBD
Dome Cover

GUBBM
Instrument Box

Standard Finishes
•	 GUBB malleable iron bodies: triple-coat — (1) zinc electroplate,
(2) chromate, and (3) epoxy powder coat.
•	 GUBB aluminum covers and aluminum bodies: epoxy powder
coat

Options
•	 GUBB
— Less cover, add suffix —LC.
— Terminal blocks. Information provided upon request.
•	 Instrument mounting plate and bracket for GUBBM. Information
provided upon request (submit complete dimensions of
instrument to be used).

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E10444
CSA Standard: C22.2 No. 25, C22.2 No. 30
CSA Certified: 025875

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GUBB Cast Junction Boxes for Drilling and Tapping Blank Body Ordering Information
Explosionproof, Dust-Ignitionproof
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4, 7BCD, 9EFG

If a “Standard Conduit Opening Arrangement” is not suitable for the
application, or when openings are to be more accurately spaced,
submit sketch, locating openings (1) from centerlines of box and
(2) from outside back of box (or from mounting lug surface if lugs
are supplied).

Determine catalog number as follows: (1) select GUBB junction
box catalog number; (2) select “Conduit Opening Arrangement
Diagram” number; and (3) select symbols that represent conduit
opening sizes from “Symbol Table.”
Where no opening is required, the symbol 0 must be inserted.
Add suffix for other Optional Features. The various divisions of the
complete catalog number should be separated by dashes.
Example
The junction box selected is GUBB-33 and the “Conduit Opening
Arrangement” is diagram #1. Opening “a” is to be 3/4”; “b”, no
opening required; “c”, 2”; and “d”, 1-1/4”.

GUBB-11,22
(also GUBB-11A, 22A)

In this example, the complete catalog number is
GUBB-33—1—B0FD
Standard Conduit Opening Arrangement Diagrams
Opening “a” is always TOP of box
Standard Conduit Opening Arrangement Diagrams

Symbol Table

Opening “a” is always TOP of box. All conduit openings will be located in
centerline of walls and evenly spaced unless otherwise specified.

Diag.
#2

Diag.
#3

Diag.
#4

Drilling and Tapping (Five Threads Minimum)

Conduit Size
Inches
0
1/2
3/4
1
1-1/4
1-1/2

Conduit Size
Inches
–
2
2-1/2
3
3-1/2
4

Symbol
Blank
A
B
C
D
E

Enclosures and Junction Boxes

Diag.
#1

GUBB-33
(also GUBB-33A)

Symbol
–
F
G
H
J
K

Contact your local representative for drilling the back side of GUBB boxes.

Allowance made for clearance over bushings. When unions or seals are used, additional space must be allowed.
Table shows minimum distances between conduit-opening centerlines in various size combinations. For example, if 1-1/2” and 3/4” openings
are to be drilled and tapped into one side of box, the minimum spacing between centerlines would be 2.13”.
Conduit
Size
Inches
1/2

1/2
1.25/31.8

3/4

3/4

1.38/35.1

1.50/38.1

Minimum Space Between Conduit Opening Centerlines in Inches/Millimeters
1

1-1/4

1-1/2

2

1

1.56/39.6

1.69/42.9

1.88/47.8

1-1/4

1.88/47.8

2.00/50.8

2.19/55.6

2.44/62.0

1-1/2

2.00/50.8

2.13/54.1

2.31/58.7

2.63/66.8

2.75/69.9

2

2.38/60.5

2.50/63.5

2.69/68.3

2.94/74.7

3.13/79.5

3.44/87.4

2-1/2

2.50/63.5

2.63/66.8

2.81/71.4

3.13/79.5

3.25/82.6

3.63/92.2

2-1/2

3

3-1/2

3.75/95.3

3

2.88/73.2

3.00/76.2

3.19/81.0

3.44/87.4

3.63/92.2

3.94/100.1

4.13/104.9

4.44/112.8

3-1/2

3.13/79.5

3.25/82.6

3.44/87.4

3.75/95.3

3.88/98.6

4.25/108.0

4.38/111.3

4.75/120.7

5.00/127.0

4

3.44/87.4

3.56/90.4

3.75/95.3

4.06/103.1

4.19/106.4

4.56/115.8

4.69/119.1

5.06/128.5

5.31/134.9

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

4

5.63/143.0

581

Enclosures and Junction Boxes: Hazardous Junction Boxes

Minimum Recommended Spacing Between Conduit Openings

GUBB Cast Junction Boxes for Drilling and Tapping Blank Body Ordering Information
Explosionproof, Dust-Ignitionproof
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4, 7BCD, 9EFG

Diameters of Bushings, Unions, Conduit and Seals (in Inches/Millimeters)
Diameters of fittings for 1/2 through 4” conduit
Conduit Size Inches
BBU Bushing

1/2
1.06/26.9

3/4
1.31/33.3

1
1.56/39.6

1-1/4
1.94/49.3

1-1/2
2.19/55.6

2
2.69/68.3

2-1/2
3.19/81.0

3
3-1/2
4
3.88/98.6 4.38/111.3 4.88/124.0

3.25/82.6

3.88/98.6 4.56/115.8 5.06/128.5

BU Bushing

1.13/28.7

1.25/31.8

1.63/41.4

2.06/52.3

2.31/58.7

2.94/74.7

UNY-UNF (R) Union

1.50/38.1

1.75/44.5

2.00/50.8

2.81/71.4

3.06/77.7

3.75/95.3 4.94/125.5 5.44/138.2 5.94 /150.9 6.50/165.1

0.88/22.4

1.06/26.9

1.38/35.1

1.69/42.9

1.94/49.3

2.38/60.5

2.88/73.2

3.50/88.9 4.00/101.6 4.50/114.3

1.06/26.9

1.19/30.2

1.38/35.1

1.75/44.5

2.06/52.3

2.31/58.7

2.69/68.3

3.13/79.5

Conduit
EYM-EYF Seals T.R.

†

3.44/87.4

3.69/93.7

Wall Thickness and Maximum Conduit Size (in Inches/Millimeters)
Top, Bottom and Sides

Back

Wall
Thickness
0.44/11.2

Maximum
Conduit Size
2

Wall Thickness
0.44/11.2

Maximum
Conduit Size
2

GUBB-22, GUBB-22A

0.44/11.2

2

0.63/16.0

4

GUBB-33, GUBB-33A

0.63/16.0

2

0.81/20.6

4

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Box Type
GUBB-11, GUBB-11A

† T.R. is turning radius.

582

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GUBB Cast Junction Boxes for Drilling and Tapping
Explosionproof, Dust-Ignitionproof

Drilled and tapped openings from 1/2” thru 4” as specified.
Class I, Division 1 and 2, Groups B, C, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4, 7BCD, 9EFG

Size LxWxD
Inches/Millimeters

Cover Opening
Form
Inches/Millimeters Number

Volume
in3/dm3

Catalog Number
Malleable Iron ‡

Aluminum ‡

7.00 x 6.50 x 6.75/
177.8 x 165.1 x 171.5

5.38/136.7

1

120/
2.0

GUBB-11

GUBB-11A

10.00 x 8.00 x 6.88/
254.0 x 203.2 x 174.8

7.19/182.6

2

224/
3.7

GUBB-22

GUBB-22A

12.00 x 12.00 x 7.75/
304.8 x 304.8 x 196.9

9.69/246.1

3

455/
7.5

GUBB-33

GUBB-33A

Class I, Division 1 Sealing Requirements
Box

Group

GUBB

B, C

GUBB

D

Seals Required 
Yes



No

Mounting Lugs
2

GUBB-22, 22A

2

GUBB-33, ­­­33A

4

Enclosures and Junction Boxes

Catalog Number
GUBB-11, 11A

A

B

C

D

E

F

G

H

J

K†

L

M

N

U

GUBB-11

6.50/
165.1

7.00/
177.8

5.50/
139.7

5.94/
150.9

5.38/
163.7

6.00/
152.4

7.75/
196.9

0.50/
12.7

6.75/
171.5

3.69/
93.7

5.25/
133.4

4.63/
117.6

6.25/
158.8

8.75/
222.3

8.00/
203.2

10.00/
254.0

7.13/
181.1

9.00/
228.6

7.19/
182.6

9.00/
228.6

9.25/
235.0

0.50/
12.7

6.88/
174.8

3.50/
88.9

5.25/
133.4

4.63/
117.6

8.00/
203.2

10.25/
260.4

12.00/
304.8

12.00/
304.8

10.75/
273.1

10.75/
273.1

9.69/
246.1

10.00/
254.0

13.13/
333.5

0.63/
16.0

7.75/
196.9

3.94/
100.0

5.75/
146.1

5.38/
136.7

11.00/
279.4

14.38/
365.3

GUBB-11A
GUBB-22
GUBB-22A
GUBB-33
GUBB-33A

‡ Malleable iron and aluminum boxes furnished with aluminum cover.
† Inside dimensions.
 Sealing fitting must be installed within 2” of each conduit entrance (max. conduit for Group B and C is 2”). Seals not required in Class I, Division 2 areas
provided there are no arcing or sparking devices in the box.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

583

Enclosures and Junction Boxes: Hazardous Junction Boxes

Dimensions in Inches/Millimeters
Catalog Number

GUBBM Instrument Enclosures
Explosionproof, Dust-Ignitionproof

GUBBM: Furnished with one 3/4” threaded conduit opening. Aluminum body with aluminum/glass cover.
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4

Type Box

Conduit Opening Size Cover Opening
Wall Thickness
(Inches-NPT)
Inches/Millimeters Inches/Millimeters

Form
Number

Catalog Number

GUBB-11A

3/4

5.38/136.7

0.44/11.2

1

GUBBM-1A

GUBB-22A

3/4

7.19/182.6

0.44/11.2

2

GUBBM-2A

GUBB-33A

3/4

9.69/246.1

0.56/14.2

3

GUBBM-3A

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Other drilled and tapped conduit opening arrangements and sizes available in addition to the one 3/4” conduit opening provided.
GUBB Cast Junction Boxes for Drilling and Tapping Blank Body Ordering Information
For Covers and Mounting Plates, Order from GUBB Surface and Special Purpose Covers page.

584

Type Box

Mounting
Lugs

GUBBM-1A

Dimensions in Inches/Millimeters
A

B

C

D

E

F

G

2

6.50/
165.1

7.00/
177.8

3.13/
79.5

5.63/
143.0

2.06/
52.3

4.63/
117.6

0.50/
12.7

GUBBM-2A

2

8.00/
203.2

10.00/
254.0

4.75/
120.7

5.63/
143.0

2.06/
52.3

4.63/
117.6

0.50/
12.7

GUBBM-3A

4

12.00/
304.8

12.00/
304.8

6.88/
174.8

8.94/
227.1

3.50/
88.9

5.38/
136.7

0.63/
16.0

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

GUBBD Cast Boxes for Drilling and Tapping With Dome Cover and Mounting Plate
Explosionproof, Dust-Ignitionproof

Malleable iron junction boxes furnished with aluminum cover.
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4

Nominal Cover Depth
Inches/Millimeters

Width of Mounting Plate
Inches/Millimeters

Adjustment
Inches/Millimeters †

Form Number

Catalog Number

10.00/254.0

3.50/88.9

1.00/25.4

1

GUBBD-1-10

4.88/124.0

1.50/38.1

2

GUBBD-2-6

6.00/152.4
12.00/304.8

GUBBD-2-12

6.00/152.4

GUBBD-3-6

12.00/304.8

Cover removed,
showing mounting
plate

Body with
dome cover

6.25/158.8

2.13/54.1

GUBBD-3-12

3

GUBBD-3-17

17.00/431.8

Dimensions

Enclosures and Junction Boxes

GUBBD-1 (2 Lugs), GUBBD-2 (2 Lugs), GUBBD-3 (4 Lugs)

All Types

A

B

C‡

D‡

E

K‡

L‡

M

N

U

GUBBD-1-10

6.50/
165.1

7.00/
177.8

6.06/
153.9

6.56/
166.6

5.38/
136.7

6.00/
152.4

7.75/
196.9

0.50/
12.7

16.13/
409.7

3.75/
95.3

14.75/
374.7

4.63/
117.6

6.25/
41.0

8.75/
222.3

GUBBD-2-6

8.00/
203.2

10.00/
254.0

7.56/
192.0

9.56/
242.8

7.19/
182.6

9.00/
228.6

9.25/
235.0

0.50/
12.7

12.19/
309.6

3.81/
96.8

10.75/
273.1

4.63/
117.6

8.06/
77.1

10.25/
260.4

GUBBD-2-12

8.00/
203.2

10.00/
254.0

7.56/
192.0

9.56/
242.8

7.19/
182.6

9.00/
228.6

9.25/
235.0

0.50/
12.7

18.19/
462.0

3.81/
96.8

16.75/
425.5

4.63/
117.6

8.06/
77.1

10.25/
260.4

GUBBD-3-6

12.00/
304.8

12.00/
304.8

11.38/
289.1

11.38/
289.1

9.69/
246.1

10.00/
254.0

13.13/
333.5

0.63/
16.0

13.81/
350.8

4.38/
111.3

11.56/
293.6

5.38/
136.7

11.00/
125.2

14.38/
365.3

GUBBD-3-12

12.00/
304.8

12.00/
304.8

11.38/
289.1

11.38/
289.1

9.69/
246.1

10.00/
254.0

13.13/
333.5

0.63/
16.0

19.81/
503.2

4.38/
111.3

17.56/
446.0

5.38/
136.7

11.00/
125.2

14.38/
365.3

GUBBD-3-17

12.00/
304.8

12.00/
304.8

11.38/
289.1

11.38/
289.1

9.69/
246.1

10.00/
254.0

13.13/
333.5

0.63/
16.0

25.31/
642.9

4.38/
111.3

23.06/
585.7

5.38/
136.7

11.00/
125.2

14.38/
365.3

† Mounting plate is adjustable. May be centered or located to one side.
‡ Inside dimensions.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

585

Enclosures and Junction Boxes: Hazardous Junction Boxes

Dimensions in Inches/Millimeters
F
G
H
J

Catalog Number

GUBB/GUBBD/GUBBM Cast Junction Box Surface and Special Purpose Covers
Explosionproof, Dust-Ignitionproof

Covers provide raintight fit when used with O-rings. Available in malleable iron, aluminum, and aluminum/glass.
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 3, 3R, 4

Fits Box Catalog Number

Nominal Cover
Depth Inches/
Millimeters

Nominal Cover
Window
Diameter Inches/ Diameter Inches/ Form
Millimeters
Millimeters
Number Catalog Number

Covers — Aluminum — O-Ring Gasket Included

GUBK-1, GUBK-2

GUBB-11 (11A)

Surface

5.38/136.7

2.12/53.8

1

GUBK-1

GUBB-22 (22A)

Surface

7.19/182.6

4.75/120.7

2

GUBK-2

GUBB-33 (33A)

Surface

9.69/246.1

7.00/177.8

3

GUBK-3

GUBK-3
Instrument Box Covers — Aluminum and Glass

GUBMK-1, GUBMK-2

GUBB-11 (11A)

—

5.38/136.7

1

GUBMK-1

GUBB-22 (22A)

—

7.19/182.6

2

GUBMK-2

GUBB-33 (33A)

—

9.69/246.1

3

GUBMK-3

GUBMK-3

Enclosures and Junction Boxes

Dome Covers for GUBB Boxes — Aluminum — O-Ring Gasket Included
GUBB-11 (11A)

10.00/254.0

5.38/136.7

1

GUBK-1-10

GUBB-22 (22A)

6.00/152.4

7.19/182.6

2

GUBK-2-6

GUBB-22 (22A)

12.00/304.8

7.19/182.6

2

GUBK-2-12

GUBB-33 (33A)

6.00/152.4

9.69/246.1

3

GUBK-3-6

GUBB-33 (33A)

12.00/304.8

9.69/246.1

3

GUBK-3-12

GUBB-33 (33A)

17.00/431.8

9.69/246.1

3

GUBK-3-17

GUBB-11 (11A)

1

GUBG-1

GUBB-22 (22A)

2

GUBG-2

GUBB-33 (33A)

3

GUBG-3

Replacement O-Rings—Neoprene

Enclosures and Junction Boxes: Hazardous Junction Boxes

Provide raintight fit for GUBB, GUBBM and GUBBD Boxes

Mounting Plates—0.13”/3.3mm Thick Aluminum. 4 standoffs, 4 mounting screws
GUBB-11 (11A) *

4.50 x 4.50/
114.3 x 114.3

1

GUBBMP-11

GUBB-22 (22A) *

6.50 x 6.50/
165.1 x 165.1

2

GUBBMP-22

GUBB-33 (33A) *

9.00 x 9.00/
228.6 x 228.6

3

GUBBMP-33

* GUBB boxes are predrilled to accept a mounting plate.

586

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DER, GUB and GUBM Cast Junction Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof, Watertight
Furnished with surface cover and mounting lugs.
CSA Certified
Class I, Division 1 and 2, Groups A, B, C, D
Class I, Zone 1 and 2
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 4

Applications
•	 Explosionproof and dust-ignitionproof for use in classified
locations.
•	 Corrosion-resistant: ideal indoors or outdoors.
•	 Junction or pull box for pulling and splicing of wires and as an
enclosure for electrical devices.
•	 Ideal where number and size of conductors require a junction
box with additional space.

Features
GUB2C

GUBM-2C

Options
•	 Other hub arrangements and sizes are available. Contact your
local representative for details.
•	 Other means of instrument fastening are available. Contact your
local representative for details.
•	 Instrument mounting plates or brackets can be furnished.
On receipt of complete instrument dimensions, prices will be
quoted. Contact your local representative for details.
•	 To order DER1C or DER1CA without mounting lugs add
suffix -LF.

Certifications and Compliances
•	 CSA Standard: C22.2 No. 25, C22.2 No. 30
•	 CSA Certified: 013017

•	 Bodies: copperfree (4/10 of 1% max.) aluminum or malleable
iron bodies
•	 DER and GUB covers: copperfree (4/10 of 1% max.) aluminum
•	 GUBM covers: copperfree (4/10 of 1% max.) aluminum and
glass
•	 O-Ring: neoprene

V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

587

Enclosures and Junction Boxes: Hazardous Junction Boxes

Standard Materials

DER1C

Enclosures and Junction Boxes

•	 Provided with mounting lugs.
•	 Furnished with covers.
•	 All conduit hubs and openings provide a minimum of five full
threads to meet CSA requirements.
•	 Accurately tapped, tapered conduit threads provide tight, rigid
joints and ground continuity.
• DER and GUB Series
— Wide selection of sizes and locations for drilled and tapped
conduit openings.
— Suitable for use as an enclosure for relays, instrument and
other control apparatus in classified locations.
— Available in high tensile strength malleable iron or copperfree
aluminum bodies.
— O-Rings standard for forms 1, 2 and 3 to provide raintight fit.
•	 GUBM Series (Instrument)
— GUBM junction boxes serve as an enclosure for meters,
gauges and similar devices.
— Complete with round, explosionproof glass window cover.
Permits direct reading of enclosed instrument.
— Furnished with one 3/4” drilled and tapped entry.
— Mounting bosses are provided in the bottom of GUBM can
be drilled and tapped for fastening of instrument mounting
bracket.
— O-Rings standard to provide raintight fit.
•	 Surface covers furnished with DER and GUB junction boxes
have lugs to take a bar or wrench. Other style covers, as listed
below, are available.
•	 Sealing covers have a plugged hole through which the box
can be filled with sealing cement after installation. See Fittings
Section for information regarding sealing cement. Note: When
sealing covers are used, splices or taps within the Unilets are
prohibited by the CEC.
•	 Dome covers permit conductors to be pulled in with the ends
extending well out beyond box body where splices can easily
be made. The splices need not be crowded back into the
box, but can be left as is when dome cover is used for their
enclosure and protection.

DER, GUB and GUBM Cast Junction Box Ordering Information V
CSA Certification Only. Explosionproof, Dust-Ignitionproof, Watertight
Furnished with surface cover and mounting lugs.
CSA Certified
Class I, Division 1 and 2, Groups A, B, C, D
Class I, Zone 1 and 2
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 4

Determining Catalog Numbers

Enclosures and Junction Boxes

• To determine the catalog number of junction boxes with entries, the following information should be shown:
1)	 Junction box catalog number from listings on the following pages
2)	 Sketch number of hub arrangement selected from the illustration below.
3)	 Entry symbols taken from the table shown below. Start from the left (at Hub “A”) on the top of the junction box and continue in rotation
clockwise around its body. Where no entry is required, the symbol X should be inserted. The three various divisions of the catalog number
should be separated by dashes.
Conduit Entry Symbols
Example (Inches/Millimeters)
GUB2C junction box is required with
Drilling and Tapped or Threaded Hubs
threaded conduit entries and unions.
Size
in/mm
Symbol
Size in/mm
Symbol
The arrangement of entries is per
sketch #16.
0.50/12.7
1
2.00/50.8
6
A — is to be 2.00/50.8 drilled and
0.75/19.1
2
2.50/63.5
7
tapped entry
1.00/25.4
3
3.00/76.2
8
B — 1.25/31.8
C — Blank (no entry)
1.25/31.8
4
3.50/88.9
9
D — 2.00/50.8
1.50/38.1
5
4.00/101.6
10
E — Blank
F — 1.00/25.4
J — Blank
The catalog number is:
GUB2C-16-64X634X.
Unions are required at B and D.

Union Hubs (GUB4 only)
Symbol
Size in/mm

Symbol

0.50/12.7

1E

2.00/50.8

6E

0.75/19.1

2E

2.50/63.5

7E

1.00/25.4

3E

3.00/76.2

8E

1.25/31.8

4E

3.50/88.9

9E

1.50/38.1

5E

4.00/101.6

10E

A

A

Order UNY male unions from the Fittings
Section of the catalog.
A

A

A

A
B

2

A

B

A

A

5

J

B

J
E

C

C

12

13

A

C

D

14

A

C

B

15

23

24

H

C

G

D

G

B

F

E

D
F

17

E

18

M

D

B

J

C

C

C B

C B

8

9

10

11

M
L
K
J

A

B

A

B
J

E
C

H G

C

C

D

19

20

21

22

A B

A B

E

A

B

H
J

L

A

B

C
D
E
F

ABC C
D
E
F

B

A B
C

J

A BC
M
L
K

J

C
D

C

16

A BC
J

A

H

D

D

B
J

B

B

A
J

B

7

J

D

E

A

F

B

6

A

B

E

D

J

C

4
B

A

A
J

J

C

3

A

E

A

A

D

C

B

1

Enclosures and Junction Boxes: Hazardous Junction Boxes

Size in/mm

C

J

F

G

C BA

F E D

J HG

K J HG

B A

B A

25

26

27

28

29

30

D
F

31

32

E

33

Send sketch and description for other arrangements.

Top *
Side *

Back

Front

Bottom

* GUB2C shown. Top and bottom measures 9.25"/235.0 mm x 5.25"/139.7 mm and sides measure 10.63"/269.9 mm x 5.50"/139.7 mm.
V CSA Certification Only.

588

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DER and GUB Cast Junction Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof, Watertight
Furnished with surface cover and mounting lugs.
CSA Certified
Class I, Division 1 and 2, Groups A, B, C, D
Class I, Zone 1 and 2
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 4

DER and GUB Junction Boxes
Dimensions in Inches/Millimeters
Outside
Cover Dia. (in./mm)

DER1C

GUB2C

GUB1C

Catalog Number
Ferrous Alloy
Aluminum

5.13/130.3 x 5.13/130.3 x 4.06/103.1

3.88/98.8

DER1C †

DER1CA †

7.00/177.8 x 7.00/177.8 x 6.50/165.1

5.38/136.7

GUB1C

GUB1CA

10.63/270.0 x 9.25/235.0 x 6.75/171.5

7.19/182.6

GUB2C

GUB2CA

12.44/316.0 x 12.44/316.0 x 8.44/214.4

9.81/249.2

GUB3C

GUB3CA

GUB3C

Maximum Size and Number of Entries Supplied on Any One Side

0.50/12.7

0.75/19.1

1.00/25.4

Dimensions in Inches/Millimeters
1.25/31.8
1.50/38.1
2.00/50.8
2.50/63.5

3.00/76.2

3.50/88.9

4.00/101.6

—

—

—

—

Drilled and Tapped - With Clearance for Conduit Seals
DER1C

3

2

2‡

1‡

—

—

4

4

4

2

2

1

—

—

—

—

4

4

4

3

3

2

2‡

—

—

—

GUB3C

4

4

4

3

3

2

2

—

—

—

DER1C

3

2

2‡

1‡

—

—

—

—

—

—

GUB1C

3

3

4

2

2

—

—

—

—

—

GUB2C

4

4

4

3

3

2

1‡

—

—

—

GUB3C

4

4

4

3

3

2

1

—

—

—

With UNY Male Unions

Maximum Entry in Back
GUB1C - 2”; GUB2C - 2”; GUB3C - 6”

† To order DER1C or DER1CA without mounting lugs add the suffix -LF to the catalog number.
‡ Requires pad. Available on special order, contact your local sales representative.
V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

589

Enclosures and Junction Boxes: Hazardous Junction Boxes

GUB1C
GUB2C

Enclosures and Junction Boxes

Catalog Number

GUBM Cast Junction Boxes and DER, GUB and GUBM Covers V
CSA Certification Only. Explosionproof, Dust-Ignitionproof, Watertight
Furnished with surface cover and mounting lugs.
CSA Certified
Class I, Division 1 and 2, Groups A, B, C, D
Class I, Zone 1 and 2
Class II, Division 1 and 2, Groups E, F, G
Class III, Enclosure 4

GUBM Instrument Junction Boxes

GUB-1C

Catalog Number
Ferrous Alloy
Aluminum

Type
of Body

Mounting
Lugs

Hub Size
(Inches)

Cover Opening *
In Inches/Millimeters

GUB-1C

2

3/4

5.38/136.5

GUBM-1C

GUBM-1CA

GUB-2C

2

3/4

7.44/188.9

GUBM-2C

GUBM-2CA

GUB-2C

DER, GUB and GUBM Junction Box Covers

DER Form 1 and GR Form 2 have the same cover opening.

DER and GUB junction boxes are furnished with surface covers. Order the remaining below listed covers as follows: Specify junction box
catalog number and the catalog number of the cover required from the listings below.
Example: GUB-2-16-64EX63E4EX, except with GUBK-2-6 dome cover.
Type of Body

Type of Cover

DER1C
Enclosures and Junction Boxes

GUB1C
GUB2C

Surface Covers

GUB3C
Sealing Covers

Catalog Number

3.56/90.5

GRK-2C

4.63/117.5

GUBK-1C

6.25/158.8

GUBK-2C

8.88/225.4

GUBK-3C

3.56/90.5

GRK-2SC

Enclosures and Junction Boxes: Hazardous Junction Boxes

DER1C

Inside Diameter in Inches/Millimeters

V CSA Certification Only.

590

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DER, GUB and GUBM Cast Junction Box Dimensions V

CSA Certification Only. Explosionproof, Dust-Ignitionproof, Watertight
Furnished with surface cover and mounting lugs.

Dimensions of GUBM

Catalog
Number

Mounting
Lugs

Dimensions in Inches/Millimeters
E
F
G - Dia.

A

B

C

D

H - Dia.

J

K - Dia.

L

7.00/
177.8

6.50/
165.1

5.25/
133.4

8.25/
209.6

6.00/
152.4

3.63/
92.1

5.38/
136.5

4.63/
117.5

0.50/
12.7

2.06/
52.4

10.59/
269.1

6.72/
170.7

5.63/
142.9

10.38/
263.5

9.59/
243.4

5.00/
127.0

7.31/
185.7

4.38/
111.1

0.50/
12.7

2.06/
52.4

GUBM-1C

2

7.00/
177.8

GUBM-2C

2

9.27/
235.3

Enclosures and Junction Boxes

Box
Type

A

B

C

GUB3C (4 Lugs)

D

E

3.91/
99.2

3.91/
99.2

F

All Types

Dimensions in Inches/Millimeters
G
H
J
K
L

M

N

O

T

U

Z

2.31/
58.7

DER1C

5.13/ 5.13/ 4.38/
130.2 130.2 111.1

4.00/ 6.00/
101.6 152.4

0.31/
7.9

4.06/
103.2

2.44/
61.9

3.25/
82.6

4.50/
114.3

—

—

7.00/
177.8

—

GUB1C

7.00/ 7.00/ 5.75/ 5.41/ 7.19/ 6.00/ 8.25/
177.8 177.8 146.1 137.3 182.6 152.4 209.6

0.50/
12.7

6.38/
161.9

3.81/
96.8

5.03/ 4.63/ 6.19/
127.8 117.5 157.2

—

—

9.25/
235.0

0.13/
3.2

GUB2C

9.25/ 10.63/ 8.13/ 7.25/ 7.19/ 9.60/ 10.38/ 0.50/
235.0 269.9 206.4 184.2 182.6 243.7 263.5 12.7

6.63/ 3.94/ 5.22/ 5.06/ 8.00/
168.3 100.0 132.6 128.6 203.2

—

—

11.38/ 0.13/
288.9
3.2

GUB3C

12.44/ 12.44/ 10.94/ 9.88/ 9.88/ 9.00/ 14.00/ 0.63/
315.9 315.9 277.8 250.8 250.8 228.6 355.6 15.9

8.25/ 4.44/ 6.19/ 5.63/ 10.75/ 7.00/ 7.00/ 14.94/ 0.31/
209.6 112.7 157.2 142.9 273.1 177.8 177.8 379.4
7.9

V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

591

Enclosures and Junction Boxes: Hazardous Junction Boxes

DER1C, GUB1C, GUB2C (2 Lugs)

DER, GUB and GUBM Cast Junction Box Dimensions V

CSA Certification Only. Explosionproof, Dust-Ignitionproof, Watertight
Furnished with surface cover and mounting lugs.

Threaded Entries ‡
Top or Bottom Side
9-1/4” x 5-1/2”
Left or Right Side
10-5/8” x 5-1/2”

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Type
DER1C

GUB1C

GUB2C

GUB3C

GUB2C

Entry
Size
1/2
3/4
1†
1-1/4 †
1/2
3/4
1
1-1/4
1-1/2
2
1/2
3/4
1
1-1/4
1-1/2
2
2-1/2 †
1/2
3/4
1
1-1/4
1-1/2
2
2-1/2
1/2
3/4
1
1-1/4
1-1/2
2
2-1/2 †

P
1.44/36.5
1.44/36.5
1.44/36.5 †
1.44/36.5 †
2.06/52.4
2.06/52.4
2.06/52.4
2.06/52.4
2.06/52.4
2.50/63.5
2.06/52.4
2.06/52.4
2.06/52.4
2.06/52.4
2.06/52.4
2.63/66.8
2.63/66.8 †
3.25/82.6
3.25/82.6
3.25/82.6
3.25/82.6
3.25/82.6
3.25/82.6
3.25/82.6
2.06/52.4
2.06/52.4
2.06/52.4
2.06/52.4
2.06/52.4
2.63/66.8
2.63/66.8 †

Dimensions in Inches/Millimeters
Q
R
X
Y
AA
BB
CC
DD
1.19/30.2 1.44/36.5
—
—
2
0.97/24.6
—
—
1.19/30.2
—
—
—
—
—
—
—
1.19/30.2 †
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
1.44/36.5 1.75/44.5 0.69/17.5 1.38/34.9 3.38/85.7 1.75/44.5 3.50/88.9 1.69/42.9
1.44/36.5 1.75/44.5 0.69/17.5 1.38/34.9 3.38/85.7 1.75/44.5 3.50/88.9 1.69/42.9
1.44/36.5 1.75/44.5 0.69/17.5  1.13/28.6  3.38/85.7 1.75/44.5 3.50/88.9  1.69/42.9 
1.44/36.5
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2.06/52.4 2.81/71.4
1.00/254
2.00/50.8 3.31/84.1 2.00/50.8 3.56/90.5 3.75/95.3
2.06/52.4 2.81/71.4
1.00/254
2.00/50.8 3.31/84.1 2.00/50.8 3.56/90.5 3.75/95.3
2.06/52.4 2.81/71.4
1.00/254
2.00/50.8 3.31/84.1 2.00/50.8 3.56/90.5 3.75/95.3
2.06/52.4 2.81/71.4
—
—
3.31/84.1 22.00/50.8
—
—
—
—
—
—
2.06/52.4 2.81/71.4 
3.31/84.1  2.00/50.8 
2.25/57.2
—
—
—
—
—
—
—
2.25/57.2 †
—
—
—
—
—
—
—
2.38/60.3 3.25/82.6 1.19/30.2 2.38/60.3 3.88/98.4 2.69/68.3 2.69/68.3 3.88/98.4
2.38/60.3 3.25/82.6 1.19/30.2 2.38/60.3 3.88/98.4 2.69/68.3 2.69/68.3 3.88/98.4
2.38/60.3 3.25/82.6 1.19/30.2 2.38/60.3 3.88/98.4 2.69/68.3 2.69/68.3 3.88/98.4
2.38/60.3 3.25/82.6
—
—
3.88/98.4 2.69/68.3
—
—
2.38/60.3 3.25/82.6
—
—
3.88/98.4 2.69/68.3
—
—
2.38/60.3
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2.38/60.3 †
2.06/52.4 2.81/71.4
1.00/254
2.00/50.8 3.31/84.1 2.00/50.8 3.56/90.5 1.75/44.5
2.06/52.4 2.81/71.4
1.00/254
2.00/50.8 3.31/84.1 2.00/50.8 3.56/90.5 1.75/44.5
2.06/52.4 2.81/71.4
1.00/254
2.00/50.8 3.31/84.1 2.00/50.8 3.56/90.5 1.75/44.5
2.06/52.4 2.81/71.4 1.19/30.2 * 2.31/58.7 * 3.31/84.1 2.00/50.8 3.44/87.3 * 0.88/47.6 *
2.06/52.4 3.13/79.4
—
—
3.31/84.1 2.00/50.8
—
—
2.25/57.2
—
—
—
—
—
—
—
2.25/57.2 †
—
—
—
—
—
—
—

Caution: Dimensions between hub centres are for use with hubs of the same size. These dimensions will not necessarily hold true for a combination of hubs of
extreme sizes. Please consult Engineering Dept. for special combinations of hubs.
‡ Dimensions permit assembly of seals on adjacent conduit runs.
 Seals must be staggered for assembly on adjacent conduit runs.
† Requires pad. Available only on special order from factory.
* Dimensions will not permit assembly of unions on adjacent conduit runs.
V CSA Certification Only.

592

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

AGUB Instrument and Meter Enclosures
Explosionproof, Dust-Ignitionproof

Furnished with aluminum body and solid or window cover.
Class I, Division 1 and 2, Groups B◊, C◊, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG

Application
•	 To pull or splice wires and/or to mount and enclose electrical
devices in hazardous locations.

Features
•	 Precision threaded flame path between box and cover.
•	 O-ring gasket provided to seal out moisture, dust, oil, dirt etc.
for interior and exterior locations.
•	 Cast mounting feet provided on all enclosures.
•	 Large cover opening for easy access.
•	 Available with solid or window covers.

Standard Materials
•	 Bodies: copperfree (4/10 of 1% max.) aluminum
•	 AGUB covers: copperfree (4/10 of 1% max.) aluminum
•	 AGUBSW covers: copperfree (4/10 of 1% max.) aluminum
and glass
•	 O-ring: neoprene

AGUB Series

Standard Finishes
•	 Corrosion resistant gray powder coat epoxy standard

Certifications and Compliances
UL Standard: UL 886 (UL 1203)
UL Listed: E85310
CSA Standard: C22.2 No. 25, C22.2 No. 30
CSA Certified: 020945
cUL Listed: E84577

Enclosures and Junction Boxes

•	
•	
•	
•	
•	

Enclosures and Junction Boxes: Hazardous Junction Boxes

◊ Shaded items on following page are for Groups B and C, all conduits must be sealed within specified distance of enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

593

AGUB Enclosures for Drilling and Tapping Blank Body Ordering Information
Explosionproof, Dust-Ignitionproof

Furnished with aluminum body and solid or window cover.
Class I, Division 1 and 2, Groups B◊, C◊, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG

If a “Standard Conduit Opening Arrangement” is not suitable for the
application, or when openings are to be more accurately spaced,
submit sketch, locating openings (1) from centerlines of box and
(2) from outside back of box (or from mounting lug surface if lugs
are supplied).

Determine catalog number as follows: (1) select AGUB enclosure
catalog number; (2) select “Conduit Opening Arrangement
Diagram” number; and (3) select symbols that represent conduit
opening sizes from “Symbol Table.”
Where no opening is required, the symbol 0 must be inserted.
Add suffix for other Optional Features. The various divisions of the
complete catalog number should be separated by dashes.
Example
The junction box selected is AGUB443A and the “Conduit Opening
Arrangement” is diagram #1. Opening “a” is to be 3/4”; “b”, no
opening required; “c”, 2”; and “d”, 1-1/4”.
In this example, the complete catalog number is
AGUB443A-1-BOFD
Standard Conduit Opening Arrangement Diagrams
Opening “a” is always TOP of box

Symbol Table

Opening “a” is always TOP of box. All conduit openings will be located in
centerline of walls and evenly spaced unless otherwise specified.

Drilling and Tapping (Five Threads Minimum)

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Standard Conduit Opening Arrangement Diagrams

Diag.
#1

Diag.
#2

Diag.
#3

Diag.
#4

Conduit Size
Inches
0
1/2
3/4
1
1-1/4
1-1/2

Conduit Size
Inches
–
2
2-1/2
3
3-1/2
4

Symbol
Blank
A
B
C
D
E

Symbol
–
F
G
H
J
K

Contact your local representative for drilling the back side of GUBB boxes.

Minimum Recommended Spacing Between Conduit Openings
Allowance made for clearance over bushings. When unions or seals are used, additional space must be allowed.
Table shows minimum distances between conduit-opening centerlines in various size combinations. For example, if 1-1/2” and 3/4” openings
are to be drilled and tapped into one side of box, the minimum spacing between centerlines would be 2.13”.
Conduit
Size
Inches
1/2

Minimum Space Between Conduit Opening Centerlines in Inches/Millimeters
1/2
1.25/31.8

3/4

3/4

1.38/35.1

1.50/38.1

1

1.56/39.6

1.69/42.9

1

1-1/4

1-1/2

2

2-1/2

3

3-1/2

4

1.88/47.8

1-1/4

1.88/47.8

2.00/50.8

2.19/55.6

2.44/62.0

1-1/2

2.00/50.8

2.13/54.1

2.31/58.7

2.63/66.8

2.75/69.9

2

2.38/60.5

2.50/63.5

2.69/68.3

2.94/74.7

3.13/79.5

3.44/87.4

2-1/2

2.50/63.5

2.63/66.8

2.81/71.4

3.13/79.5

3.25/82.6

3.63/92.2

3.75/95.3

3

2.88/73.2

3.00/76.2

3.19/81.0

3.44/87.4

3.63/92.2

3.94/100.1

4.13/104.9

4.44/112.8

3-1/2

3.13/79.5

3.25/82.6

3.44/87.4

3.75/95.3

3.88/98.6

4.25/108.0

4.38/111.3

4.75/120.7

5.00/127.0

4

3.44/87.4

3.56/90.4

3.75/95.3

4.06/103.1

4.19/106.4

4.56/115.8

4.69/119.1

5.06/128.5

5.31/134.9

5.63/143.0

◊ Shaded items on following page are for Groups B and C, all conduits must be sealed within specified distance of enclosure.

594

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

AGUB Instrument and Meter Enclosures
Explosionproof, Dust-Ignitionproof

Furnished with aluminum body and solid or window cover.
Class I, Division 1 and 2, Groups B◊, C◊, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG

Inside Dimensions
in Inches/Millimeters
Box with Cover

Box with Window Cover
AGUBSW443A

AGUB555A

AGUBSW555A

AGUB664A

AGUBSW664A

AGUB976A

AGUBSW976A

AGUB984A

AGUBSW984A

AGUB1093A

AGUBSW1093A

AGUB10105A

AGUBSW10105A

AGUB10106A

AGUBSW10106A

AGUB10108A

AGUBSW10108A

AGUB12128A

AGUBSW12128A

AGUB121212A

AGUBSW121212A

Height

Depth

4.25/
108.0
5.38/
136.5
6.13/
155.6
7.50/
190.5
8.13/
206.4
9.00/
228.6
10.63/
269.9
10.13/
257.2
10.13/
257.2
12.13/
308.0
12.13/
308.0

3.25/
82.6
5.00/
127
4.25/
108.0
6.00/
152.4
4.38/
111.1
3.94/
100.0
5.25/
133.4
6.00/
152.4
8.00/
203.2
8.00/
203.2
12.00/
304.8

3/4
3/4
2
2
2
2
3
3
4
4
4

18.00/
457.2
18.00/
457.2
18.00/
457.2
18.00/
457.2
18.00/
457.2
3.00/
76.2
3.00/
76.2
3.00/
76.2
3.00/
76.2

4.00/
101.6
4.50/
114.3
5.94/
150.8
7.00/
177.8
7.94/
201.6
8.88/
225.4
9.88/
250.8
9.25/
235.0
9.25/
235.0
11.25/
285.8
11.25/
285.8

3”
2
2
2
2
2
2
2
2
2
2

3-1/2”
1
1
2
2
2
2

4”
1
1
1
1
1
1

None
None

Maximum Number of Drilled and Tapped Conduit Entries
Catalog Number
AGUB443A
AGUB555A
AGUB664A
AGUB976A
AGUB984A
AGUB1093A
AGUB10105A
AGUB10106A
AGUB10108A
AGUB12128A
AGUB121212A

Side
Long
Short
Long
Short
Long
Short
Long
Short
Long
Short
Long
Short
Long
Short
Long
Short
Long
Short
Long
Short
Long
Short

1/2”
2
2
3
3
3
3
5
4
5
5
6
5
6
6
6
6
6
6
7
7
7
7

3/4”
2
2
2
2
3
3
4
3
5
5
5
4
5
5
5
5
5
5
6
6
6
6

1”
2
2
4
3
4
4
4
4
5
5
4
4
4
4
5
5
5
5

1-1/4”
2
2
3
2
3
3
3
3
4
4
3
3
3
3
4
4
4
4

Trade Size of Conduit
1-1/2”
2”
2
1
2
1
3
2
2
2
3
2
3
2
3
2
3
2
3
3
3
3
3
2
3
2
3
2
3
2
4
3
4
3
4
3
4
3

2-1/2”
2
2
2
2
2
2
2
2
2
2

Ordering Information for Drilled and Tapped Enclosures
For custom arrangement, see Modifications and Accessories and use the AGUB Series Custom Drill and Tap Schedule.

◊ For Groups B and C, all conduits must be sealed within specified distance of enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

595

Enclosures and Junction Boxes: Hazardous Junction Boxes

18.00/
457.2
3.00/
76.2
18.00/
457.2
18.00/
457.2
18.00/
457.2
18.00/
457.2
18.00/
457.2
3.00/
76.2
3.00/
76.2
3.00/
76.2
3.00/
76.2

Enclosures and Junction Boxes

AGUB443A

Width
4.25/
108.0
5.38/
136.5
6.13/
155.6
9.25/
235.0
9.13/
231.8
10.00/
254.0
10.63/
269.9
10.13/
257.2
10.13/
257.2
12.13/
308.0
12.13/
308.0

Maximum
Cover
Seal Distance
Conduit in Inches/Millimeters Opening in
Size
Inches/
(In. - NPT) Group B ◊ Group C ◊ Millimeters

AGUB Instrument and Meter Enclosure Modifications and Accessories
Explosionproof, Dust-Ignitionproof
Class I, Division 1 and 2, Groups B◊, C◊, D
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 4X, 7BCD, 9EFG

Grounding Kits

Replacement Window Covers
Wire Capacity
AI-Cu/Tinned Copper

Catalog Number

AGUBSW-443A

#14-4 AWG

ASW-555A

AGUBSW-555A

AGK-10

#8-1/0 AWG

ASW-664A

AGUBSW-664A

AGK-25

#6 AWG-250MCM

ASW-976A

AGUBSW-976A

ASW-984A

AGUBSW-984A

ASW-1093A

AGUBSW-1093A

Catalog Number
Aluminum
Galvanized Steel

Enclosures and Junction Boxes

Use With Box Catalog Number

AGK-04

Mounting Plates — Standard

Enclosures and Junction Boxes: Hazardous Junction Boxes

Catalog Number
ASW-443A

Use With
Box Catalog Number

ASW-10105A

AGUBSW-10105A

ASW-10106A

AGUBSW-10106/8A

ASW-12128

AGUBSW-12128/12A

AMPA-443

AMPG-443

AGUB-443A

AMPA-555

AMPG-555

AGUB-555A

AMPA-664

AMPG-664

AGUB-664A

AMPA-976

AMPG-976

AGUB-976A

Replacement Flat Covers
Catalog Number

AMPA-984

AMPG-984

AGUB-984A

AFC-443A

AGUB-443A

AMPA-1093

AMPG-1093

AGUB-1093A

AFC-555A

AGUB-555A

Use With Box Catalog Number

AMPA-10105

AMPG-10105

AGUB-10105A

AFC-664A

AGUB-664A

AMPA-10106

AMPG-10106

AGUB-10106A

AFC-976A

AGUB-976A

AMPA-10108

AMPG-10108

AGUB-10108A

AFC-984A

AGUB-984A

AMPA-12128

AMPG-12128

AGUB-12128A

AFC-1093A

AGUB-1093A

AMPA-121212

AMPG-121212

AGUB-121212A

AFC-10105A

AGUB-10105A

AFC-1010A

AGUB-10106/8A

AFC-1212A

AGUB-12128/12A

Mounting Plates — 90°
Catalog Number
Aluminum
Galvanized Steel

Use With
Box Catalog Number

AMD-4-664A

AMD-4-664G

AGUB-664A

AMD-10-664A

AMD-10-664G

AGUB-664A

AMD-6-984A

AMD-6-984G

AGUB-984A

AMD-8-1093A

AMD-8-1093G

AGUB-1093A

AMD-10-10105A

AMD-10-10105G

AGUB-10105A

NEMA 4X Breather/Drain Fittings
Suffix
Factory-Installed *

Catalog Number
Field-Installed

Drain Fitting

DN

DRNB4X

Breather Fitting

BR

BRTB4X

Description

Drill and Tap Options
Conduit Size
(Inches - NPT)

596

Symbol

1/2

A

3/4

B

1

C

1-1/4

D

1-1/2

E

2

F

2-1/2

G

3

H

3-1/2

J

4

K

* Drilled and tapped installation included.
◊ Shaded items on previous page are for Groups B and C,
all conduits must be sealed within specified distance of enclosure.

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

AGUB Instrument and Meter Enclosure Custom Drill and Tap Schedule

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Hazardous Junction Boxes

AGUB/GUBSW-443	
AGUB/GUBSW-555	
AGUB/GUBSW-664	
AGUB/GUBSW-984	
	

AGUB/GUBSW-976
AGUB/GUBSW-1093
AGUB/GUBSW-10105
AGUB/GUBSW-10106/8
AGUB/GUBSW-12128/12

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

597

AGUB Instrument and Meter Enclosure Dimensions
Explosionproof, Dust-Ignitionproof
Solid Cover and Window Cover

AGUB Solid Cover * and AGUBSW Window Cover Series

B

D
M

1-5/16 MAX.

U

P-TYP.

X

Z
M

R DIA.
OPENING

A

F-MTG. S-DIA.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Hazardous Junction Boxes

Pan

P-(TYP.)

N
C

Front View Less Cover

Catalog
Number

T
V

G

E-MTG.

S-DIA.

Side View

Outside Dimensions

End View

Instrument Cover

Dimensions in Inches/Millimeters
Cover
Conduit Space
Open

Mounting Lugs

Cover Window
Dia.
Dia.

Section View

Wall
Thickness

Depth

A

B

C

D

E

F

G

M

N

P

R

S

T

U

V

X

Z

443A

5.31/
134.9

5.31/
134.9

5.19/
131.8

4.56/
115.9

6.25/
158.8

3.88/
98.4

0.38/
9.5

2.81/
71.4

3.75/
95.3

0.75/
19.1

4.00/
101.6

4.63/
117.5

2.50/
63.5

4.00/
101.6

3.00/
76.2

0.44/
11.1

0.44/
11.1

555A

6.25/
158.8

6.25/
158.8

6.94/
176.2

6.25/
158.8

7.50/
190.5

5.00
127.0

0.38/
9.5

4.06/
103.2

4.25/
108.0

0.94/
23.8

4.25/
108.0

5.25/
133.4

3.19/
81.0

5.50/
139.7

4.63/
117.5

0.44/
11.1

0.75/
19.1

664A

7.00/
177.8

7.00/
177.8

6.50/
165.1

5.69/
144.5

8.13/
206.4

5.75/
146.1

0.38/
9.5

3.75/
95.3

5.50/
139.7

0.88/
22.2

5.94/
150.8

6.50/
165.1

4.00/
101.6

5.00/
127.0

4.00/
101.6

0.44/
11.1

0.44/
11.1

976A

10.25/
260.4

8.50/
215.9

8.44/
214.3

7.44/
188.9

9.75/
247.7

9.00/
228.6

0.38/
9.5

4.94/
1254

6.50/
165.1

0.81/
20.6

7.00/
177.8

7.75/
196.9

5.44/
138.1

6.38/
161.9

5.50/
139.7

0.50/
12.7

0.44/
11.1

984A

10.00/
254.0

9.00/
228.6

6.63/
168.3

5.88/
149.2

10.13/
257.2

8.50/
215.9

0.38/
9.5

3.81/
97.1

7.50/
190.5

0.94/
23.8

7.94/
201.6

8.63/
219.1

5.63/
142.9

5.06/
128.6

4.06/
103.2

0.44/
11.1

0.69/
17.5

1093A

11.56/
293.7

10.56/
268.2

6.44/
163.5

5.69/
144.5

12.00
304.8

9.25/
235.0

0.38/
9.5

3.44/
87.3

7.88/
200.1

0.94/
23.8

8.94/
227.0

9.75/
247.7

5.63/
142.9

4.63/
117.5

3.63/
92.1

0.69/
17.5

0.69/
17.5

10105A

12.00
304.8

12.00
304.8

8.75/
222.3

7.50/
190.5

13.62/
346.1

10.00/
254.0

0.63/
15.9

4.81/
122.2

9.75/
247.7

1.25/
31.8

9.88/
250.9

11.00/
279.4

7.50/
190.5

6.50/
165.1

5.19/
131.8

0.69/
17.5

0.69/
17.5

10106A

11.62/
295.3

11.62/
295.3

9.38/
238.1

7.88/
200.1

13.00/
330.2

10.00/
254.0

0.63/
15.9

4.69/
119.1

8.88/
225.4

1.38/
35.0

9.25/
235.0

10.25/
260.4

7.38/
187.3

6.56/
166.7

5.50/
139.7

0.75/
19.1

0.69/
17.5

10118A

11.62/
295.3

11.62/
295.3

11.38/
288.9

9.88/
250.8

13.00/
330.2

10.00/
254.0

0.63/
15.9

6.69/
169.9

8.88/
225.4

1.38/
35.0

9.25/
235.0

10.25/
260.4

7.38/
187.3

8.56/
217.4

7.50/
190.5

0.75/
19.1

0.69/
17.5

12128A

13.62/
346.1

13.62/
346.1

11.75/
298.5

9.88/
250.8

15.00/
381.0

10.00/
254.0

0.63/
15.9

6.69/
169.9

10.88/
276.2

1.38/
35.0

11.25/
285.8

12.25/
311.2

9.44/
239.7

8.56/
217.4

7.50/
190.5

0.75/
19.1

0.69/
17.5

121212A

13.62/
346.1

13.62/
346.1

15.75/
400.1

13.88/
352.4

15.00/
381.0

10.00/
254.0

0.63/
15.9

10.69/
271.5

10.88/
276.2

1.38/
35.0

11.25/
285.8

12.25/
311.2

9.44/
239.7

12.56/
319.1

11.50/
292.1

0.75/
19.1

0.69/
17.5

* AGUB Solid Cover Series do not have a window.

598

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

AJBEW Cast Junction Boxes
Explosionproof, Dust-Ignitionproof
Class I, Division 1, 2, Groups B◊, C◊, D
Class I, Zone 1, 2, Groups IIA, IIB◊+H2◊, IP66
Class II, Division 1, 2, Groups E, F, G
Class III
NEMA 4, 7B◊C◊D, 9EFG

Application
•	 Explosionproof junction boxes are used where hazardous
materials are handled or stored. These enclosures may be used
for:
— Terminals
— Splicing wires
— Pull boxes
— Bus boxes

Features
•	 Precision machined flame path between box and cover.
•	 Bolt on stainless steel slotted mounting feet for horizontal or
vertical mounting.
•	 Flexible hinge mounting either left or right side is standard on all
boxes 12 x 12 x 06 and larger.
•	 External flange maximizes internal space.
•	 Wall thickness suitable for minimum of five full threads.
•	 Provision for mounting pan.
•	 Wide range of drilled and tapped outlets.
•	 Ground lug package and installation instructions for termination
of ground wires enclosed.
•	 O-ring gasket insures watertight integrity.

Standard Materials

Standard Finishes
•	 Bodies and covers: shot blast finish standard

Options

Certifications and Compliances
•	
•	
•	
•	
•	
	
	
	
	
	
	
	
	
	
	
	
•	
•	
•	
•	

UL Standard: UL 886 (UL 1203)
UL Listed: E85310
CSA Standard: C22.2 No. 25, C22.2 No.30
CSA Certified: 042129
Certification Type JBEW U2
— Gas, Zones 1 and 2
– Conforming to ATEX 94/9/CE: CE 0081
II 2 G
– ATEX/IEC Protection: Ex d IIB + H2
— Dust, Zones 21 and 22
– Conforming to ATEX 94/9/CE: CE 0081 II2 D
– ATEX/IEC Protection: Ex tD A21
— Ambient Temperature: -40 °F/-40 °C to 131 °F/55 °C
— CE Declaration of Conformity: 5C239
— ATEX Certificate: LCIE 06 ATEX 0010U
— IECEx Certificate: IECEx LCI 08.001X
— Internal Volume: > 2dm3 (2 liters)
Ingress Protection (solid and liquid): IP66
Impact Resistance (shock): IK10
Ex Standards: EN/IEC 60079-0; 60079-1; 61241-0; 61241-1
Other Standards: EN/IEC 60529 (IP), 62262 (IK)

◊ For Groups B and C, all conduits must be sealed within 2”/50.8 mm of the enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

599

Enclosures and Junction Boxes: Hazardous Junction Boxes

•	 Custom drilling and tapping.
•	 Set of 4 standoffs 0.50”/12.7mm high. For factory-installed
option add suffix -AB.
•	 Breather, NEMA 4X (includes outlets & installation). For factoryinstalled option add suffix -BR, for field-installed option order
catalog number BRTB4X.
•	 Drain, NEMA 4X (includes outlets & installation). For factoryinstalled option add suffix -DN for field-installed option order
catalog number ECD50B4X.
•	 Desiccate package. For factory-installed option add suffix
-DP1, for field-installed option order catalog number
AWG13/1CT.
•	 External grounding stud 3/8”-16. For factory-installed option
add suffix -EGS.
•	 Gray epoxy powder coat (outside). For factory-installed option
add suffix -G1.
•	 Gray epoxy powder coat available to provide NEMA 4X rating
(inside & outside). For factory-installed option add suffix -G2.
•	 Internal Ground Stud, #14 - #2. For factory-installed option add
suffix -GNDKIT.
•	 Hinges: stainless steel hinge available for boxes up to 11 x 30 x
03. For factory-installed option add suffix -H.
•	 Hinge Kit, 2 light duty SS hinges. For field-installed option order
catalog number AHOF12SS.
•	 Hinge Kit, 2 heavy duty SS hinges. For field-installed option
order catalog number AHOF22SS.
•	 Hinge Kit, 3 heavy duty SS hinges. For field-installed option
order catalog number AHOF23SS.

•	 Terminal blocks 600 Volt, 30 Amp Indicate number of points:
example: 5 points = 5K. For factory-installed option add suffix -K.
•	 Plastic nameplate, 2.00 x 4.00” / 50.8 x 101.6 mm, .13”/3.3 mm
black letters on white surface, 3 lines max, specify legend. For
factory-installed option add suffix -NP.
•	 SS captive Quad-Lead bolts. For factory-installed option add
suffix -Q.
•	 ATEX complete product certification add suffix -X.
•	 ATEX U component certification add suffix -XU.
•	 Mounting pan. For factory-installed option add suffix -Z.

Enclosures and Junction Boxes

•	 Bodies and covers: sand cast copperfree (4/10 of 1% max.)
aluminum
•	 Cover bolts: stainless steel
•	 O-ring: neoprene
•	 Hinges: stainless steel
•	 Mounting pan: galvanized steel

AJBEW Cast Junction Boxes
Explosionproof, Dust-Ignitionproof
Class I, Division 1, 2, Groups B◊, C◊, D
Class I, Zone 1, 2, Groups IIA, IIB◊+H2◊, IP66
Class II, Division 1, 2, Groups E, F, G
Class III
NEMA 4, 7B◊C◊D, 9EFG

Dimensions in Inches/Millimeters

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Catalog
Number

Overall Dimensions
F
E
G

A

Mounting Dimensions
AA
B
BB

Inside Dimensions
H
Db
Dc

W

K

Max.
Mounting
Conduit Ship Hardware
Size Weight Catalog
Inches lb/kg Number

AJBEW040604

7.13/
181.1

9.13/
231.9

6.13/
155.7

N/A

6.75/
171.5

N/A

2.13/
54.1

4.00/
101.6

6.00/
152.4

3.75/
95.3

0.75/
19.1

2.50/
63.5

1-1/2

20.00/
AMH2
9.1

AJBEW050903

8.94/
227.1

13.50/
342.9

6.13/
155.7

4.00/
101.6

N/A

11/
279.4

N/A

5.06/
128.5

9.50/
241.3

3.50/
88.9

1.13/
28.7

2.00/
50.8

1-1/2

20.00/
AMH2
9.1

AJBEW060604

9.63/
244.6

9.33/
237.0

6.25/
158.8

N/A

8.75/
222.3

N/A

12.13/
308.1

6.00/
152.4

6.00/
152.4

4.00/
101.6

0.75/
19.1

2.38/
60.5

2

20.00/
AMH2
9.1

AJBEW060804

10.40/ 12.40/
264.2 315.0

6.50/
165.1

4.50/
114.3

9.13/
231.9

10.56/
268.2

4.50/
114.3

6.00/
152.4

8.00/
203.2

3.75/
95.3

0.75/
19.1

2.50/
63.5

2

20.00/
AMH2
9.1

AJBEW060806

10.40/ 12.50/
264.2 317.5

8.13/
206.5

N/A

9.38/
238.3

N/A

4.50/
114.3

6.00/
152.4

8.00/
203.2

5.75/
146.1

0.75/
19.1

2.38/
60.5

2

20.00/
AMH2
9.1

AJBEW061004

10.63/ 15.25/
270.0 387.4

6.75/
171.5

5.50/
139.7

N/A

13.13/
333.5

N/A

6.13/
155.7

10.75/
273.1

3.81/
96.8

1.44/
36.6

2.00/
50.8

2

27.00/
AMH2
12.2

AJBEW061204

10.63/ 16.60/
270.0 421.6

6.38/
162.1

N/A

9.13/
231.9

N/A

8.50/
215.9

6.13/
155.7

12.13/
308.1

4.06/
103.1

1.00/
25.4

2.25/
57.2

2

25.00/
AMH2
11.3

AJBEW061604

11.00/ 20.50/
279.4 520.7

6.88/
174.8

6.00/
152.4

N/A

18.00/
457.2

N/A

6.50/
165.1

16.00/
406.4

4.13/
104.9

1.38/
35.1

2.31/
58.7

2

32.00/
AMH2
14.5

AJBEW071106

12.25/ 15.88/ 10.00/
311.2 403.4 254.0

6.38/
162.1

N/A

13.50/
342.9

N/A

7.38/
187.5

11.38/
289.1

5.88/
149.4

2.50/
63.5

3.38/
85.9

2

35.00/
AMH2
15.9

AJBEW080806

12.25/ 12.25/
311.2 311.2

8.25/
209.6

4.50/
114.3

10.75/ 10.75/
273.1 273.1

4.50/
114.3

8.00/
203.2

8.00/
203.2

5.75/
146.1

0.75/
19.1

3.25/
82.6

2

30.00/
AMH2
13.6

AJBEW081006

12.50/ 14.50/
317.5 368.3

8.50/
215.9

7.00/
177.8

10.75/ 12.50/
273.1 317.5

6.50/
165.1

8.00/
203.2

10.00/
254.0

5.75/
146.1

0.75/
19.1

3.50/
88.9

2

36.00/
AMH2
16.3

AJBEW081307

12.50/ 17.44/ 10.38/
317.5 443.0 263.7

10.00/
254

8.50/
215.9

8.00/
203.2

13.06/
331.7

3.50/
88.9

3.50/
88.9

2.75/
69.9

2

30.00/
AMH2
13.6

AJBEW091105

13.88/ 15.50/
352.6 393.7

8.69/
220.7

7.25/
184.2

11.82/ 13.13/
300.2 333.5

8.56/
217.4

9.00/
238.3

11.13/
282.7

4.81/
122.2

1.88/
47.8

3.25/
82.6

2

22.00/
AMH2
10.0

AJBEW091504

14.25
/362

20.44/
519.2

8.50/
215.9

7.25/
184.2

11.81/ 17.88/ 13.31/
300.0 454.2 338.1

9.50/
241.3

15.56/
395.2

4.75/
120.7

1.75/
44.5

3.00/
76.2

2

33.00/
AMH2
15.0

AJBEW101006

14.81/ 14.81/
376.2 376.2

9.13/
231.9

6.50/
165.1

10.78/ 13.00/
273.8 330.2

10.25/ 10.25/
260.4 260.4

5.75/
146.1

1.50/
38.1

3.38/
85.9

2

44.00/
AMH2
20.00

AJBEW101406

14.50/ 18.50/
368.3 469.9

8.44/
214.4

7.00/
177.8

13.00/ 16.63/ 10.63/ 10.00/ 14.00/
330.2 422.4
270
254.0 355.6

5.88/
149.4

0.75/
19.1

3.13/
79.5

2

55.00/
AMH4
24.9

AJBEW101408

14.50/ 18.50/
368.3 469.9

9.63/
244.6

N/A

13.00/
330.2

10.63/ 10.00/ 14.00/
270
254.0 355.6

7.75/
196.9

0.75/
19.1

4.44/
112.8

4

60.00/
AMH2
27.2

AJBEW112005

16.38/ 25.13/
416.1 638.3

7.50/
190.5

10.25/ 14.50/ 22.63/ 16.88/ 11.38/ 20.00/
260.4 368.3 574.8 428.8 289.1 508.0

4.88/
124.0

1.50/
38.1

3.50/
88.9

3

85.00/
AMH2
38.6

AJBEW112406

15.75/ 29.38/ 10.19/
400.1 746.3 258.8

8.50/
215.9

6.00/
152.4

1.63/
41.4

4.00/
101.6

3

72.00/
AMH8
32.7

N/A

N/A

N/A

4.50/
114.3

14.13/ 27.13/ 20.00/ 10.75/ 24.38/
358.9 689.1
508
273.1 619.3

◊ For Groups B and C, all conduits must be sealed within 2”/50.8 mm of the enclosure.

600

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

AJBEW Cast Junction Boxes
Explosionproof, Dust-Ignitionproof
Class I, Division 1, 2, Groups B◊, C◊, D
Class I, Zone 1, 2, Groups IIA, IIB◊+H2◊, IP66
Class II, Division 1, 2, Groups E, F, G
Class III
NEMA 4, 7B◊C◊D, 9EFG

Dimensions in Inches/Millimeters
A

AJBEW113006

16.38/ 35.00/ 10.25/
416.1 889.0 260.4

9.50/
241.3

15.13/ 32.88/ 27.25/ 11.25/ 29.88/
384.3 835.2 692.2 285.8 759.0

6.19/
157.2

1.88/
47.8

4.19/
106.4

3

113.00/
AMH8
51.3

AJBEW121206

17.38/ 17.38/
441.5 441.5

9.25/
235

8.63/
219.2

15.63/ 15.63/
397.0 397.0

8.63/
219.2

12.25/ 12.25/
311.2 311.2

5.75/
146.1

1.50/
38.1

3.75/
95.3

3

65.00/
AMH8
29.5

AJBEW121208

17.38/ 17.38/ 11.50/
441.5 441.5 292.1

8.63/
219.2

15.63/ 15.63/
397.0 397.0

8.63/
219.2

12.25/ 12.25/
311.2 311.2

7.75/
196.9

1.50/
38.1

4.75/
120.7

3

70.00/
AMH8
31.8

AJBEW121806

17.00/ 23.00/
431.8 584.2

9.13/
231.9

7.00/
177.8

15.75/ 21.00/ 14.13/ 12.25/ 18.25/
400.1 533.4 358.9 311.2 463.6

5.75/
146.1

1.50/
38.1

3.50/
88.9

4

90.00/
AMH5
40.8

AJBEW121808

17.00/ 23.00/ 11.13/
431.8 584.2 282.7

7.00/
177.8

15.75/ 21.00/ 14.13/ 12.25/ 18.25/
400.1 533.4 358.9 311.2 463.6

8.75/
222.3

1.50/
38.1

4.25/
108.0

4

101.00/
AMH5
45.8

AJBEW122408

16.75/ 28.75/ 11.13/
425.5 730.3 282.7

N/A

15.75/
400.1

N/A

18.38/ 12.00/ 24.00/
466.9 304.8 609.6

7.75/
196.9

1.00/
25.4

4.25/
108.0

4

138.00/
AMH4
62.6

AJBEW123608

16.75/ 40.75/ 11.88/
425.5 1035.1 301.8

N/A

15.75/
400.1

N/A

29.00/ 12.00/ 36.00/
736.6 304.8 914.4

7.75/
196.9

1.50/
38.1

4.56/
115.8

4

218.00/
AMH5
98.9

AJBEW133806

18.00/ 42.50/ 10.44/ 16.13/ 11.88/ 40.75/ 33.75/ 13.63/ 37.88/
457.2 1079.5 265.2 409.7 301.8 1035.1 857.3 346.2 962.2

6.13/
155.7

1.50/
38.1

4.31/
109.5

3-1/2

190.00/
AMH8
86.2

AJBEW141406

19.38/ 19.38/
492.3 492.3

9.56/
242.8

9.75/
247.7

17.75/ 17.75/
450.9 450.9

9.75/
247.7

14.75/ 14.75/
374.7 374.7

5.75/
146.1

1.38/
35.1

3.88/
98.6

3-1/2

98.00/
AMH8
44.5

AJBEW141408

19.38/ 19.38/ 11.56/
492.3 492.3 293.6

9.75/
247.7

17.75/ 17.75/
450.9 450.9

9.75/
247.7

14.75/ 14.75/
374.7 374.7

7.75/
196.9

1.38/
35.1

4.00/
101.6

3

105.00/
AMH8
47.6

AJBEW142408

19.63/ 29.00/ 12.00/ 13.13/
498.6 736.6 304.8 333.5

N/A

14.88/ 24.25/
378
616.0

8.00/
203.2

1.50/
38.1

4.00/
101.6

4

131.00/
AMH6
59.4

AJBEW153707

21.25/ 43.00/ 12.06/ 13.75/ 20.00/ 41.63/ 32.00/ 15.63/ 37.25/
539.8 1092.2 306.3 349.3 508.0 1057.4 812.8
397
946.2

7.44/
189.0

1.50/
38.1

5.25/
133.4

4

250.00/
AMH8
113.4

AJBEW161606

21.00/ 21.00/
533.4 533.4

11.00/ 19.75/ 19.75/ 11.00/ 16.50/ 16.50/
279.4 501.7 501.7 279.4 419.1 419.1

5.75/
146.1

1.50/
38.1

3.88/
98.6

3-1/2

132.00/
AMH8
59.9

AJBEW161608

21.00/ 21.00/ 12.39/ 11.00/ 19.75/ 19.75/ 11.00/ 16.50/ 16.50/
533.4 533.4 314.7 279.4 501.7 501.7 279.4 419.1 419.1

8.38/
212.9

1.50/
38.1

4.88/
124.0

4

140.00/
AMH8
63.5

AJBEW161812

21.38/ 23.38/ 15.06/ 12.00/ 19.00/ 21.00/ 14.00/ 16.25/ 18.25/ 11.88/
543.1 593.9 382.5 304.8 482.6 533.4 355.6 412.8 463.6 301.8

0.38/
9.7

7.00/
177.8

4

150.00/
AMH8
68.0

AJBEW162206

21.50/ 27.31/
546.1 693.7

5.75/
146.1

1.25/
31.8

3.31/
84.1

3

130.00/
AMH8
59.0

AJBEW162408

21.00/ 28.00/ 12.13/
533.4 711.2 308.1

18.38/ 16.25/ 24.25/
466.9 412.8 616.0

8.25/
209.6

1.50/
38.1

5.31/
134.9

4

180.00/
AMH6
81.6

AJBEW162806

20.75/ 32.75/
527.1 831.9

AJBEW181806

23.38/ 23.38/
593.9 593.9

9.06/
230.1

N/A

27.50/
698.5

W

Inside Dimensions
H
Db
Dc

13.00/ 19.88/ 25.25/ 15.50/ 16.44/ 22.50/
330.2 505.0 641.4 393.7 417.6 571.5

K

N/A

19.75/
501.7

N/A

8.63/
219.2

13.00/
330.2

N/A

30.75/
781.1

16.25/ 28.25/
412.8 717.6

5.75/
146.1

1.50/
38.1

3.13/
79.5

3

150.00/
AMH5
68.0

9.94/
252.5

13.00/ 21.75/ 21.75/ 13.00/ 18.25/ 18.25/
330.2 552.5 552.5 330.2 463.6 463.6

5.75/
146.1

1.50
/38.1

4.13/
104.9

3-1/2

188.00/
AMH8
85.3

N/A

◊ For Groups B and C, all conduits must be sealed within 2”/50.8 mm of the enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

601

Enclosures and Junction Boxes: Hazardous Junction Boxes

Overall Dimensions
F
E
G

Enclosures and Junction Boxes

Catalog
Number

9.81/
249.2

Mounting Dimensions
AA
B
BB

Max.
Mounting
Conduit Ship Hardware
Size Weight Catalog
Inches lb/kg Number

AJBEW Cast Junction Boxes
Explosionproof, Dust-Ignitionproof
Class I, Division 1, 2, Groups B◊, C◊, D
Class I, Zone 1, 2, Groups IIA, IIB◊+H2◊
Class II, Division 1, 2, Groups E, F, G
Class III
NEMA 4, 7B◊C◊D, 9EFG

Dimensions in Inches/Millimeters

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Catalog
Number

Overall Dimensions
F
E
G

A

Mounting Dimensions
AA
B
BB

W

Inside Dimensions
H
Db
Dc

K

Max.
Mounting
Conduit Ship Hardware
Size Weight Catalog
Inches lb/kg Number

AJBEW181808

23.38/ 23.38/ 11.94/ 13.00/ 21.75/ 21.75/ 13.00/ 18.25/ 18.25/
593.9 593.9 303.3 330.2 552.5 552.5 330.2 463.6 463.6

7.75/
196.9

1.50/
38.1

4.50/
114.3

4

198.00/
AMH8
89.8

AJBEW182408

23.94/ 30.00/ 12.18/ 16.13/ 21.75/ 27.75/ 18.38/ 18.25/ 24.19/
608.1 762.0 309.4 409.7 552.5 704.9 466.9 463.6 614.4

7.75/
196.9

1.50/
38.1

5.06/
128.5

4

224.00/
AMH8
101.6

AJBEW182410

23.94/ 30.00/ 14.18/ 16.13/ 21.75/ 27.75/ 18.38/ 18.25/ 24.19/
608.1 762.0 360.2 409.7 552.5 704.9 466.9 463.6 614.4

9.75/
247.7

1.50/
38.1

5.75/
146.1

4

235.00/
AMH8
106.6

AJBEW183008

22.63/ 34.63/ 12.13/
574.8 879.6 308.1

23.00/ 18.25/ 30.25/
584.2 463.6 768.4

7.75/
196.9

1.50/
38.1

4.75/
120.7

4

265.00/
AMH5
120.2

AJBEW183608

23.50/ 41.75/ 12.31/ 11.00/ 21.75/ 39.50/ 29.00/ 18.25/ 36.50/
596.9 1060.5 312.7 279.4 552.5 1003.3 736.6 463.6 927.1

7.75/
196.9

1.50/
38.1

4.75/
120.7

4

250.00/
AMH8
113.4

AJBEW183610

23.50/ 41.75/ 14.31/ 11.00/ 21.75/ 39.50/ 29.00/ 18.25/ 36.50/
596.9 1060.5 363.5 279.4 552.5 1003.3 736.6 463.6 927.1

9.75/
247.7

1.50/
38.1

5.50/
139.7

4

270.00/
AMH8
122.5

AJBEW184207

23.88/ 47.88/ 11.88/ 16.00/ 23.00/ 45.38/ 38.38/ 18.63/ 42.25/ 7.00/
606.6 1216.2 301.8 406.4 584.2 1152.7 974.9 473.2 1073.2 177.8

1.50/
38.1

5.00/
127.0

4

310.00/
AMH8
140.6

AJBEW206008

25.00/ 65.00/ 12.75/
635.0 1651.0 323.9

1.50/
38.1

4.75/
120.7

4

521.00/
AMH5
236.3

AJBEW242408

29.38/ 29.38/ 12.31/ 18.38/ 28.00/ 28.00/ 18.38/ 24.50/ 24.50/
746.3 746.3 312.7 466.9 711.2 711.2 466.9 622.3 622.3

7.75/
196.9

1.50/
38.1

5.00/
127.0

4

225.00/
AMH8
102.1

AJBEW242410

29.38/ 29.38/ 14.31/ 18.38/ 28.00/ 28.00/ 18.38/ 24.50/ 24.50/
746.3 746.3 363.5 466.9 711.2 711.2 466.9 622.3 622.3

9.75/
247.7

1.50/
38.1

6.13/
155.7

4

240.00/
AMH8
108.9

AJBEW243008

29.00/ 35.00/ 13.00/ 18.00/ 28.00/ 34.00/ 23.00/ 24.00/ 30.00/
736.6 889.0 330.2 457.2 711.2 863.6 584.2 609.6 762.0

8.00/
203.2

1.94/
49.3

5.25/
133.4

4

420.00/
AMH8
190.5

AJBEW243608

30.75/ 43.00/ 13.06/ 18.25/ 28.00/ 40.00/ 29.00/ 24.25/ 36.25/
781.1 1092.2 331.7 463.6 711.2 1016.0 736.6 616.0 920.8

7.75/
196.9

1.63/
41.4

5.13/
130.3

4

420.00/
AMH5
190.5

AJBEW243610

30.75/ 43.00/ 15.06/ 18.25/ 28.00/ 40.00/ 29.00/ 24.25/ 36.25/
781.1 1092.2 382.5 463.6 711.2 1016.0 736.6 616.0 920.8

9.75/
247.7

1.63/
41.4

6.00/
152.4

4

450.00/
AMH5
204.1

AJBEW303808

36.00/ 44.00/ 13.75/
914.4 1117.6 349.3

N/A

35.00/
889.0

N/A

29.00/ 30.00/ 38.00/
736.6 762.0 965.2

7.75/
196.9

2.00/
50.8

6.13/
155.7

4

600.00/
AMH6
272.2

AJBEW303816

36.00/ 44.00/ 20.06/
914.4 1117.6 509.5

N/A

35.00/
889.0

N/A

29.00/ 30.00/ 38.00/ 15.50/
736.6 762.0 965.2 393.7

7.75/
196.9

6.13/
155.7

4

800.00/
AMH6
362.9

N/A

N/A

21.75/
552.5

23.50/
596.9

N/A

N/A

50.00/ 20.00/ 60.00/ 6.88/
1270.0 508.0 1524.0 174.8

◊ For Groups B and C, all conduits must be sealed within 2”/50.8 mm of the enclosure.

602

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

AJBEW Cast Junction Box Options and Accessories
Explosionproof, Dust-Ignitionproof
Class I, Division 1, 2, Groups B◊, C◊, D
Class I, Zone 1, 2, Groups IIA, IIB◊+H2◊
Class II, Division 1, 2, Groups E, F, G
Class III
NEMA 4, 7B◊C◊D, 9EFG

Options
Factory-Installed Field-Installed
Suffix
Catalog Number

Description

AB

Not Available

Set of 4 standoffs 0.50”/12.7mm high

BR

BRTB4X

Breather, NEMA 4X (includes outlets & installation)

DN

ECD50B4X

Drain, NEMA 4X (includes outlets & installation)

DP1

AWG13/1CT

Desiccate package

EGS

EGSKIT

External grounding stud 3/8”-16

G1

Not Available

Gray powder coat epoxy (outside)

G2

Not Available

Gray powder coat epoxy (inside & outside)

GNDKIT

Internal Ground Stud, #14 - #2

H

Hinges stainless steel
Hinge Kit, 2 light duty SS hinges

AHOF22SS

Hinge Kit, 2 heavy duty SS hinges

AHOF23SS

Hinge Kit, 3 heavy duty SS hinges

K

Not Available

Terminal blocks 600 Volt, 30 Amp Indicate number of points: example: 5 points = 5K

NP

Not Available

Plastic nameplate, 2.00 x 4.00” / 50.8 x 101.6 mm, .13”/3.3 mm
black letters on white surface, 3 lines max, specify legend.

Q

Not Available

SS captive Quad-Lead bolts

XU

Not Available

ATEX Certification

Z

See table on
following page

Mounting pan

Mounting Hardware

Drill and Tap Options

(For drill and tap schedule, Drilling and Tapping Guidelines)

Conduit Size (NPT)
Inches

Symbol

Conduit Size (NPT)
Inches

A

1/2

F

2

B

3/4

G

2-1/2

C

1

H

3

D

1-1/4

J

3-1/2

E

1-1/2

K

4

FactoryField-Installed
Installed Suffix Catalog Number

Blind Tapped Holes
Suffix

Screw Size

BT1

#6 - 1/4”

BT2

5/16” - 1/2”

MH1

AMH1

MH2

AMH2

MH3

AMH3

MH4

AMH4

MH5

AMH5

MH6

AMH6

MH7

AMH7

MH8

AMH8

Description
1/4” - 20 X 1-1/4” Bolt,
1/4” - 20 Hex Nut, 1/4” Washers
3/8” -16 X 1-1/4” Bolt,
3/8” -16 Hex Nut, 3/8” Washers
7/16” - 14 X 1-3/4” Bolt,
7/16” - 14 Hex Nut, 7/16” Washers
1/2” - 13 x 1-3/4” Bolt,
1/2” - 13 Hex Nut, 1/2” Washers
1/2” - 13 X 2” Bolt,
1/2” - 13 Hex Nut, 1/2” Washers
5/8” - 11 X 2” Bolt,
5/8” - 11 Hex Nut, 5/8” Washers
1/2” - 13 X 1-1/4” Bolt,
1/2” - 13 Hex Nut, 1/2” Washers
5/8” - 11 X 1-1/4” Bolt,
5/8” - 11 Hex Nut, 5/8” Washers

◊ For Groups B and C, all conduits must be sealed within 2”/50.8 mm of the enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

603

Enclosures and Junction Boxes: Hazardous Junction Boxes

Symbol

Refer to ordering information for Enclosure-Mounting Hardware Correlation.

Enclosures and Junction Boxes

AHOF12SS

AJBEW Cast Junction Box Options and Accessories
Explosionproof, Dust-Ignitionproof
Class I, Division 1, 2, Groups B◊, C◊, D
Class I, Zone 1, 2, Groups IIA, IIB◊+H2◊
Class II, Division 1, 2, Groups E, F, G
Class III
NEMA 4, 7B◊C◊D, 9EFG

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Mounting Pans
Overall Dimensions
in Inches/Millimeters
W
H

Mounting Pan
Catalog Number

Junction Box
Catalog Number

AZ-464

AJBEW040604

3.00/76.2

AZ-664

AJBEW060604

AZ-686

AJBEW060806

AZ-593

Overall Dimensions
in Inches/Millimeters
W
H

Mounting Pan
Catalog Number

Junction Box
Catalog Number

5.00/127.0

AZ-14146/8

AJBEW141406

12.25/311.2

12.25/311.2

4.75/120.7

4.75/120.7

AZ-14146/8

AJBEW141408

12.25/311.2

12.25/311.2

4.50/114.3

6.50/165.1

AZ-14248

AJBEW142408

14.00/355.6

22.38/568.5

AJBEW050903

4.00/101.6

8.50/215.9

AZ-15377

AJBEW153707

14.50/368.3

35.50/901.7

AZ-684

AJBEW060804

4.50/114.3

6.50/165.1

AZ-16166/8

AJBEW161606

15.00/381.0

15.00/381.0

AZ-6104

AJBEW061004

5.00/127.0

10.50/266.7

AZ-16166/8

AJBEW161608

15.00/381.0

15.00/381.0

AZ-6124

AJBEW061204

5.50/139.7

11.00/279.4

AZ-161812

AJBEW161812

15.00/381.0

16.00/406.4

AZ-6164

AJBEW061604

5.25/133.4

15.00/381.0

AZ-16226

AJBEW162206

14.00/355.6

20.00/508.0

AZ-7116

AJBEW071106

6.50/165.1

10.00/254.0

AZ-16248

AJBEW162408

14.75/374.7

22.75/577.9

AZ-886

AJBEW080806

6.50/165.1

6.50/165.1

AZ-16286

AJBEW162806

14.00/355.6

26.00/660.4

AZ-8106

AJBEW081006

6.50/165.1

8.50/215.9

AZ-18186/8

AJBEW181806

16.00/406.4

16.00/406.4

AZ-8137

AJBEW081307

6.00/152.4

11.00/279.4

AZ-18186/8

AJBEW181808

16.00/406.4

16.00/406.4

AZ-9115

AJBEW091105

8.25/209.6

10.00/254.0

AZ-18248/10

AJBEW182408

16.00/406.4

22.00/558.8

AZ-9154

AJBEW091504

8.13/206.5

14.75/374.7

AZ-18248/10

AJBEW182410

16.00/406.4

22.00/558.8

AZ-10104/6

AJBEW101006

7.50/190.5

7.50/190.5

AZ-18308

AJBEW183008

16.00/406.4

28.00/711.2

AZ-10146/8

AJBEW101408

9.00/228.6

13.00/330.2

AZ-18368/10

AJBEW183608

17.00/431.8

34.75/882.7

AZ-10146/8

AJBEW101408

9.00/228.6

13.00/330.2

AZ-18368/10

AJBEW183610

17.00/431.8

34.75/882.7

AZ-11205

AJBEW112005

10.50/266.7

19.00/482.6

AZ-18427

AJBEW184207

17.00/431.8

40.00/1016.0

AZ-11246

AJBEW112406

9.88/251.0

23.25/590.6

AZ-205610

AJBEW205610

17.00/431.8

54.00/1371.6

AZ-11306

AJBEW113006

9.88/251.0

28.50/723.9

AZ-20608

AJBEW206008

18.00/457.2

57.50/1460.5

AZ-12126/8

AJBEW121206

10.50/266.7

10.50/266.7

AZ-24248/10

AJBEW242408

22.00/558.8

22.00/558.8

AZ-12126/8

AJBEW121208

10.50/266.7

10.50/266.7

AZ-24248/10

AJBEW242410

22.00/558.8

22.00/558.8

AZ-12186/8

AJBEW121806

10.50/266.7

16.50/419.1

AZ-24308

AJBEW243008

22.50/571.5

28.00/711.2

AZ-12186/8

AJBEW121808

10.50/266.7

16.50/419.1

AZ-24368/10

AJBEW243608

22.00/558.8

34.00/863.6

AZ-12248/10

AJBEW122408

10.75/273.05

22.63/574.8

AZ-24368/10

AJBEW243610

22.00/558.8

34.00/863.6

AZ-12368

AJBEW123608

10.00/254.0

34.00/863.6

AZ-30388

AJBEW303808

28.00/711.2

36.00/914.4

AZ-13386

AJBEW133806

11.50/292.1

36.38/924.1

AZ-30388

AJBEW303816

28.00/711.2

36.00/914.4

◊ For Groups B and C, all conduits must be sealed within 2”/50.8 mm of the enclosure.

604

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

AJBEW Cast Junction Box Dimensions and Drilling and Tapping Guidelines
Explosionproof, Dust-Ignitionproof

Dimensions — See Catalog Number Tables

Enclosures and Junction Boxes

Conduit
Size (NPT)

Minimum Spacing For Conduit Centers in Inches/Millimeters
1-1/4
1-1/2
2
2-1/2

1/2

3/4

1

1/2

2.13/54.1

2.13/54.1

2.25/57.2

2.63/66.8

2.81/71.4

3.13/79.5

3.63/92.2

4.00/101.6 4.50/114.3 4.50/114.3

3/4

2.13/54.1

2.13/54.1

2.25/57.2

2.63/66.8

2.81/71.4

3.13/79.5

3.63/92.2

4.00/101.6 4.50/114.3 4.50/114.3

1

2.25/57.2

2.25/57.2

2.38/60.5

2.81/71.4

3.00/76.2

3.25/82.6

3.75/95.3

4.13/104.9 4.50/114.3 4.63/117.6

1-1/4

2.63/66.8

2.63/66.8

2.81/71.4

3.13/79.5

3.31/84.1

3.63/92.2

4.13/104.9 4.50/114.3 4.75/120.7 5.00/127.0

1-1/2

2.81/71.4

2.81/71.4

3.00/76.2

3.31/84.1

3.50/88.9

3.81/96.8

4.31/109.5 4.63/117.6 4.94/125.5 5.25/133.4

2

3.13/79.5

3.13/79.5

3.25/82.6

3.63/92.2

3.81/96.8

4.13/104.9 4.63/117.6 5.00/127.0 5.83/148.1 5.75/146.1

2-1/2

3.63/92.2

3.63/92.2

3.75/95.3

4.13/104.9 4.31/109.5 4.63/117.6 5.13/130.3

3

4.00/101.6 4.00/101.6 4.13/104.9 4.50/114.3 4.63/117.6 5.00/127.0

3-1/2

4.50/114.3 4.50/114.3 4.50/114.3 4.75/120.7 4.94/125.5 5.38/136.7 5.75/146.1 6.00/152.4 6.25/158.8 6.50/165.1

4

4.50/114.3 4.50/114.3 4.63/117.6 5.00/127.0 5.25/133.4 5.75/146.1 6.13/155.7 6.25/158.8 6.50/165.1 6.75/171.5

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

3.31/84.1

3

3.31/84.1

3-1/2

4

5.75/146.1 6.13/155.7

5.75/146.1 6.00/152.4 6.25/158.8

605

Enclosures and Junction Boxes: Hazardous Junction Boxes

Drilling and Tapping Guidelines

EXB Cast Iron Junction Boxes

Explosionproof, Dust-Ignitionproof. Integrally Cast Mounting Feet
Drilled and tapped openings 1/2” thru 6” as specified.
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2 Groups E, F, G
Class III

Features
•	 Wide selection of sizes and locations for drilled and tapped
openings.
•	 Extra wide, accurately ground mating surfaces with closely
spaced stainless steel hex head cap screws assure a flametight joint.
•	 Provided with mounting lugs.

Standard Materials
•	 Bodies and covers: cast iron

Standard Finishes
•	 Hot-dip galvanized

Options
•	 For factory installed hinges, add suffix -HNG.
•	 For factory installed mounting plate, add suffix -WYM
•	 Refer to Junction Box Mounting Plate Information for complete
listing of available mounting plates.

Certifications and Compliances

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

Nominal Inside
Dimensions L x W x D
Inches/Millimeters
4 x 4 x 4 / 101.6 x 101.6 x 101.6
6 x 6 x 4 / 152.4 x 152.4 x 101.6
6 x 6 x 6 / 152.4 x 152.4 x 152.4
8 x 4 x 4 / 203.2 x 101.6 x 101.6
8 x 6 x 4 / 203.2 x 152.4 x 101.6
8 x 6 x 6 / 203.2 x152.4 x 152.4
8 x 8 x 4 / 203.2 x 203.2 x 101.6
8 x 8 x 6 / 203.2 x 203.2 x 152.4
8 x 8 x 8 / 20.32 x 203.2 x 203.2
10 x 8 x 4 / 254.0 x 203.2 x 101.6
10 x 8 x 6 / 245.0 x 203.2 x 152.4
10 x 8 x 8 / 254.0 x 203.2 x 203.2
10 x 10 x 4 / 254.0 x 254.0 x 101.6
10 x 10 x 6 / 254.0 x 254.0 x 152.4
10 x 10 x 8 / 254.0 x 254.0 x 203.2
12 x 8 x 4 / 304.8 x 203.2 x 101.6
12 x 12 x 4 / 304.8 x 304.8 x 101.6
12 x 12 x 6 / 304.8 x 304.8 x 152.4
12 x 12 x 8 / 304.8 x 304.8 x 203.2
12 x 12 x 10 / 304.8 x 304.8 x 254.0
12 x 12 x 12 / 304.8 x 304.8 x 304.8

Approximate Side Wall Thickness
Inches/Millimeters
0.47/11.9
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.63/16.0
0.69/17.5
0.69/17.5
0.69/17.5
0.69/17.5
0.69/17.5

Maximum
Conduit Size
(Inches)
2
2
3-1/2
2
2
3-1/2
2
3-1/2
5
2
3-1/2
5
2
3-1/2
5
2
2
3-1/2
5
6
6

Catalog
Number †
EXB040404
EXB060604
EXB060606
EXB080404
EXB080604
EXB080606
EXB080804
EXB080806
EXB080808
EXB100804
EXB100806
EXB100808
EXB101004
EXB101006
EXB101008
EXB120804
EXB121204
EXB121206
EXB121208
EXB121210
EXB121212

† See EXB Ordering Information page for drilling and tapping options.

606

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

EXB Cast Iron Junction Boxes

Explosionproof, Dust-Ignitionproof. Integrally Cast Mounting Feet
Drilled and tapped openings 1/2” thru 6” as specified.
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2 Groups E, F, G
Class III

Approximate
Side Wall Thickness
Inches/Millimeters
0.81/20.6
0.81/20.6
0.81/20.6
0.81/20.6
0.81/20.6
0.81/20.6
0.81/20.6
0.81/20.6
0.81/20.6
0.81/20.6
0.94/23.9
0.94/23.9
0.94/23.9
0.94/23.9
0.94/23.9
0.94/23.9
1.06/26.9
1.06/26.9
1.06/26.9
1.06/26.9

Maximum
Conduit Size
2
3-1/2
5
6
3-1/2
5
6
5
6
6
3
6
6
6
5
6
6
5
6
6

Catalog
Number †
EXB181204
EXB181206
EXB181208
EXB181212
EXB181806
EXB181808
EXB181812
EXB241208
EXB241210
EXB241212
EXB241806
EXB241808
EXB241810
EXB241812
EXB242408
EXB242412
EXB301210
EXB302408
EXB302410
EXB302412

Enclosures and Junction Boxes

Nom. Inside
Dimensions LxWxD
Inches/Millimeters
18 x 12 x 4 / 457.2 x 304.8 x 101.6
18 x 12 x 6 / 457.2 x 304.8 x 152.4
18 x 12 x 8 / 457.2 x 304.8 x 203.2
18 x 12 x 12 / 457.2 x 304.8 x 304.8
18 x 18 x 6 / 457.2 x 457.2 x 152.4
18 x 18 x 8 / 457.2 x 457.2 x 203.2
18 x 18 x 12 / 457.2 x 457.2 x 304.8
24 x 12 x 8 / 609.9 x 304.8 x 203.2
24 x 12 x 10 / 609.9 x 304.8 x 245.0
24 x 12 x 12 / 609.9 x 304.8 x 304.8
24 x 18 x 6 / 609.9 x 457.2 x 152.4
24 x 18 x 8 / 609.9 x 457.2 x 203.2
24 x 18 x 10 / 609.9 x 457.2 x 245.0
24 x 18 x 12 / 609.9 x 457.2 x 304.8
24 x 24 x 8 / 609.9 x 609.9 x 203.2
24 x 24 x 12 / 609.9 x 609.9 x 304.8
30 x 12 x 10 / 762.0 x 304.8 x 245.0
30 x 24 x 8 / 762.0 x 609.9 x 203.2
30 x 24 x 10 / 762.0 x 609.9 x 245.0
30 x 24 x 12 / 762.0 x 609.9 x 304.8

Hinges (Malleable Iron, Hot Dip Galvanized)
Catalog Number
AHNG-22G
AHNG-23G
AHNG-24G
AHNG-34G

Number of Hinges per set
2
2
2
3

Enclosures and Junction Boxes: Hazardous Junction Boxes

EXB Box Size
Up to 12” x 12” / 304.8 x 304.8 mm
Up to 24” x 18” / 609.9 x 457.2 mm
Up to 30” x 12” / 762.0 x 304.8 mm
Larger than 30” x 12” / 762.0 x 304.8 mm

† See EXB Ordering Information page for drilling and tapping options.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

607

EXB Series Junction Box Mounting Plate Information
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2 Groups E, F, G
Class III

Mounting plates are used for mounting equipment up off the back of an enclosure. Steel Plates are all 0.13”/3.3mm thick hot dip galvanized
material. Aluminum plates are 0.13”/3.3 mm thick material up to and including 12 x 12” / 304.8 x 304.8 mm size. All larger sizes are constructed
of 0.19”/4.8mm thick aluminum plate. The catalog numbers shown in the table below include the mounting buttons.
Select mounting plates based on inside length and width of box. Order as a separate item immediately following the catalog number of the
box as follows:
Example: 	Line 1	
EXB181204
	
Line 2	
WYM-1812-1

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

For mounting plates in smaller boxes than listed, use similar catalog number logic. Example: A steel mounting plate for a EXB040404 box
would be WYM-0404-1. Pricing will be based upon a WYM-0808-1 price.

Inside Length & Width
of Junction Box in in/mm
8 x 8/203.2 x 203.2
10 x 8/254.0 x 203.2
10 x 10/254.0 x 254.0
12 x 8/304.8 x 203.2
12 x 10/304.8 x 254.0
12 x 12/304.8 x 304.8
14 x 8355.6 x 203.2
14 x 14/355.6 x 355.6
16 x 8/406.4 x 203.2
16 x 12/406.4 x 304.8
16 x 16/406.4 x 406.4
18 x 8/457.2 x 203.2
18 x 10/457.2 x 254.0
18 x 12/457.2 x 304.8
18 x 14/457.2 x 355.6
18 x 16/457.2 x 406.4
18 x 18/457.2 x 457.2
20 x 10/508.0 x 254.0
24.00 x 12.00/609.6 x 304.8
24.00 x 18.00/609.6 x 457.2
24.00 x 24.00/609.6 x 609.6
28.00 x 12.00/711.2 x 304.8
30.00 x 12.00/762.0 x 304.8
30.00 x 18.00/762.0 x 457.2
30.00 x 24.00/762.0 x 609.6
36.00 x 12.00/914.4 x 304.8
36.00 x 18.00/914.4 x 457.2
36.00 x 24.00/914.4 x 609.6
36.00 x 30.00/914.4 x 762.0
36.00 x 36.00/914.4 x 914.4

608

Catalog Number
Steel Plates
Aluminum Plates
WYM-0808-1
WYM-0808-1A
WYM-1008-1
WYM-1008-1A
WYM-1010-1
WYM-1010-1A
WYM-1208-1
WYM-1208-1A
WYM-1210-1
WYM-1210-1A
WYM-1212-1
WYM-1212-1A
WYM-1408-1
WYM-1408-1A
WYM-1414-1
WYM-1414-1A
WYM-1608-1
WYM-1608-1A
WYM-1612-1
WYM-1612-1A
WYM-1616-1
WYM-1616-1A
WYM-1808-1
WYM-1808-1A
WYM-1810-1
WYM-1810-1A
WYM-1812-1
WYM-1812-1A
WYM-1814-1
WYM-1814-1A
—
—
WYM-1818-1
WYM-1818-1A
WYM-2010-1
WYM-2010-1A
WYM-2412-1
WYM-2412-1A
WYM-2418-1
WYM-2418-1A
WYM-2424-1
WYM-2424-1A
WYM-2812-1
WYM-2812-1A
WYM-3012-1
WYM-3012-1A
WYM-3018-1
WYM-3018-1A
WYM-3024-1
WYM-3024-1A
WYM-3612-1
WYM-3612-1A
WYM-3618-1
WYM-3618-1A
WYM-3624-1
WYM-3624-1A
WYM-3630-1
WYM-3630-1A
WYM-3636-1
WYM-3636-1A

Style
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
—
1
1
2
2
3
2
2
2
3
2
2
3
3
3

L
6.75/171.5
8.75/222.3
8.75/222.3
10.75/273.1
10.75/273.1
10.75/273.1
12.75/323.9
12.75/323.9
14.75/374.7
14.75/374.7
14.75/374.7
16.75/171.5
16.75/171.5
16.75/171.5
16.75/171.5
—
16.75/171.5
18.75/222.3
21.75/552.5
21.75/552.5
21.75/552.5
25.75/654.1
27.75/704.9
27.75/704.9
27.75/704.9
33.75/857.3
33.75/857.3
33.75/857.3
33.75/857.3
33.75/857.3

Dimension in Inches/Millimeters
W
A
6.75/171.5
6.00/152.4
6.75/171.5
8.00/203.2
8.75/222.3
8.00/203.2
6.75/171.5
10.00/254.0
8.75/222.3
10.00/254.0
10.75/273.1
10.00/254.0
6.75/171.5
12.00/304.8
12.75/323.9
12.00/304.8
6.75/171.5
14.00/355.6
10.75/273.1
14.00/355.6
14.75/374.7
14.00/355.6
6.75/171.5
16.00/152.4
8.75/222.3
16.00/152.4
10.75/273.1
16.00/152.4
12.75/323.9
16.00/152.4
—
—
16.75/171.5
16.00/152.4
8.75/222.3
18.00/203.2
9.75/247.7
21.00/533.4
15.75/400.1
21.00/533.4
21.75/552.5
21.00/533.4
9.75/247.7
25.00/635.0
9.75/247.7
27.00/685.8
15 .75/400.1
27.00/685.8
21.75/552.5
27.00/685.8
9.75/247.7
33.00/838.2
15.75/400.1
33.00/838.2
21.75/552.5
33.00/838.2
27.75/704.9
33.00/838.2
33.75/857.3
33.00/838.2

B
6.00/152.4
8.00/203.2
8.00/203.2
6.00/152.4
8.00/203.2
10.00/254.0
6.00/152.4
12.00/304.8
6.00/152.4
10.00/254.0
14.00/355.6
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
—
16.00/152.4
8.00/203.2
9.00/228.6
15.00/381.0
21.00/533.4
9.00/228.6
9.00/228.6
15.00/381.0
21.00/533.4
9.00/228.6
15.00/381.0
21.00/533.4
27.00/685.8
33.00/838.2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

EXB Cast Iron Junction Box Blank Bodies for Drilling and Tapping
Explosionproof, Dust-Ignitionproof. Integrally Cast Mounting Feet
Drilled and tapped openings 1/2” thru 6” as specified.
Class I, Division 1 and 2, Group D
Class II, Division 1 and 2 Groups E, F, G
Class III

Determine catalog number as follows:
(1) Select EXB junction box catalog number
(2) Select “Conduit Opening Arrangement Diagram” number
(3) Select symbols that represent conduit opening sizes from
“Symbol Table.”
Where no opening is required, the symbol 0 must be inserted.
Add suffix for other optional features. The various divisions of the
complete catalog number should be separated by dashes.
Example:
The junction box selected is EXB181208 with steel mounting plate
and the “Conduit Opening Arrangement” is diagram #1. Opening
“a” is to be 1/2”; “b”, 1-1/4”; “c”, no opening needed; and “d”,
1-1/2”. In this example, the complete catalog number is:
EXB181208—1—AD0E—WYM-1812-1

Standard Conduit Opening Arrangement Diagrams
Opening “a” is always TOP of box

Diag.
#1

Diag.
#2

Diag.
#3

Diag.
#4

Symbol Table
Drilling and Tapping (Five Threads Minimum)
Size
Blank
1/2
3/4
1
1-1/4
1-1/2

Symbol
F
G
H
J
K
L
M

Size
2
2-1/2
3
3-1/2
4
5
6

All Conduit Openings will be located in centerline of walls and
evenly spaced unless otherwise specified.
If a “Standard Conduit Opening Arrangement” is not suitable
for the application,or when openings are to be more accurately
spaced, submit Drill and Tap Schedule.
Enclosures and Junction Boxes

Symbol
0
A
B
C
D
E

Minimum Recommended Spacing Between Conduit Openings
Allowance made for clearance over bushings. When unions or seals are used, additional space must be allowed.
Table shows minimum distances between conduit-opening centerlines in various size combinations. For example, if 1-1/2” and 3/4”
openings are to be drilled and tapped into one side of box, the minimum spacing between centerlines would be 2.13”/54.1mm.

1/2
3/4
1
1-1/4
1-1/2
2
2-1/2
3
3-1/2
4

Minimum space between conduit opening centerlines Inches/Millimeters
1/2
1.25/31.8
1.38/35.1
1.56/39.6
1.88/47.8
2.00/50.8
2.38/60.5
2.50/63.5
2.88/73.2
3.13/79.5
3.44/87.4

3/4
1.50/38.1
1.69/42.9
2.00/50.8
2.13/54.1
2.50/63.5
2.63/66.8
3.00/76.2
3.25/82.6
3.56/90.4

1

1-1/4

1.88/47.8
2.19/55.6 2.44/62.0
2.31/58.7 2.63/66.8
2.69/68.3 2.94/74.7
2.81/71.4 3.13/79.5
3.19/81.0 3.44/87.4
3.44/87.4 3.75/95.3
3.75/95.3 4.05/102.9

1-1/2

2

2.75/69.9
3.13/79.5
3.25/82.6
3.63/92.2
3.88/98.6
4.19/106.4

3.44/87.4
3.63/92.2
3.94/100.1
4.25/108.0
4.56/115.8

2-1/2

3

3-1/2

4

3.75/95.3
4.13/104.9 4.44/112.8
4.38/111.3 4.75/120.7 5.00/127.0
4.69/119.1 5.06/128.5 5.31/134.9 5.63/143.0

Diameters of Bushings, Unions, Conduit and Seals, Inches/Millimeters
Conduit Size
Inches
BBU Bushing
BU Bushing
UNY/UNF
(R) Union
Conduit
EYM-EYF Seals
Turning Radius

Diameters of Fittings for 1/2” through 4” Conduit
1/2
1.06/26.9
1.13/28.7

3/4
1.31/33.3
1.25/31.8

1
1.56/39.6
1.63/41.4

1-1/4
1.94/49.3
2.06/52.3

1-1/2
2.19/55.6
2.31/58.7

2
2.69/68.3
2.94/74.7

1.50/38.1
0.88/22.4
1.06/26.9

1.75/44.5
1.06/26.9
1.19/30.2

2.00/50.8
1.38/35.1
1.38/35.1

2.81/71.4
1.69/42.9
1.75/44.5

3.06/77.7
1.94/49.3
2.06/52.3

3.75/95.3 4.94/125.5 5.44/138.2 5.94/150.9 6.50/165.1
2.38/60.5 2.88/73.2 3.50/88.9 4.00/101.6 4.50/114.3
2.31/58.7 2.69/68.3 3.13/79.5 3.44/87.4 3.69/93.7

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

2-1/2
3.19/81.0
3.25/82.6

3
3-1/2
4
3.88/98.6 4.38/111.3 4.88/124.0
3.88/98.6 4.56/115.8 5.06/128.5

609

Enclosures and Junction Boxes: Hazardous Junction Boxes

Conduit Size
Inches

EXB Series Junction Box Drill and Tap Schedule
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.

Ordering Information

ARE INDICATED CONDUIT
SIZES WITHIN THE CATALOG
PUBLISHED MAXIMUM ON
PAGES K-40 AND K-43?

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

CHECK FOR MINIMUM
SPACING BETWEEN CONDUIT
OPENINGS PER CONDUIT
SPACING TABLE, ON PAGE
K-41.

ENCLOSURE

610

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DTX Series Junction Boxes
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 9EFG

Applications
•	 DTX dust tight and watertight boxes are specially designed
and constructed for hazardous locations where ignitable dusts,
fibers or flyings are present such as:
•	 Grain elevators
•	 Grain storage areas
•	 Paper mills
•	 Coal storage facilities
•	 Textile factories

Features
•	 Provided with mounting lugs.
•	 Mechanically attached gaskets.

Standard Materials
•	 Bodies and covers: cast iron
•	 Gasket: vellumoid
•	 Cover bolts: stainless steel

Standard Finishes
•	 Cast iron bodies and covers: hot dip galvanized finish

Optional Materials
Enclosures and Junction Boxes

•	 Cast aluminum box and cover. Add suffix - A.
•	 For factory installed mounting plate, add suffix -WYM
•	 Refer to Junction Box Mounting Plate Information for complete
listing of available mounting plates.

Certifications and Compliances
•	 UL Standard: UL 886 (UL 1203)
•	 UL Listed: E10444

Enclosures and Junction Boxes: Hazardous Junction Boxes

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

611

DTX Series Junction Boxes
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 9EFG

Approximate
Thickness
Side Walls
in/mm
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.25/6.4
0.31/7.9
0.31/7.9
0.31/7.9
0.31/7.9
0.25/6.4
0.25/6.4
0.25/6.4
0.31/7.9
0.31/7.9

Maximum
Conduit
Size
(In.-NPT)
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
2
2
2
2
3/4
3/4
3/4
2
2

Inside Dim. Inches/Millimeters
L
4.00/101.6
4.00/101.6
5.00/127.0
6.00/152.4
6.00/152.4
6.00/152.4
6.00/152.4
6.00/152.4
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
10.00/254.0
10.00/254.0
10.00/254.0
10.00/254.0
10.00/254.0
10.00/254.0
10.00/254.0
10.00/254.0
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
14.00/101.6
14.00/101.6
14.00/101.6
14.00/101.6
14.00/101.6

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

W
4.00/101.6
4.00/101.6
5.00/127.0
4.00/101.6
4.00/101.6
6.00/152.4
6.00/152.4
6.00/152.4
4.00/101.6
4.00/101.6
6.00/152.4
6.00/152.4
6.00/152.4
8.00/203.2
8.00/203.2
8.00/203.2
6.00/152.4
6.00/152.4
8.00/203.2
8.00/203.2
8.00/203.2
10.00/254.0
10.00/254.0
10.00/254.0
4.00/101.6
6.00/152.4
6.00/152.4
8.00/203.2
8.00/203.2
8.00/203.2
10.00/254.0
10.00/254.0
10.00/254.0
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
8.00/203.2
8.00/203.2
8.00/203.2
14.00/101.6
14.00/101.6

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

D
3.00/76.2
4.00/101.6
4.00/101.6
3.00/76.2
4.00/101.6
3.00/76.2
4.00/101.6
6.00/152.4
3.00/76.2
4.00/101.6
3.00/76.2
4.00/101.6
6.00/152.4
4.00/101.6
6.00/152.4
8.00/203.2
4.00/101.6
6.00/152.4
4.00/101.6
6.00/152.4
8.00/203.2
4.00/101.6
6.00/152.4
8.00/203.2
4.00/101.6
4.00/101.6
6.00/152.4
4.00/101.6
6.00/152.4
8.00/203.2
4.00/101.6
6.00/152.4
8.00/203.2
4.00/101.6
6.00/152.4
7.00/177.8
8.00/203.2
10.00/254.0
12.00/304.8
4.00/101.6
6.00/152.4
8.00/203.2
6.00/152.4
8.00/203.2

Iron Weight
lb/kg
7.00/3.2
8.00/3.6
8.00/3.6
8.00/3.6
8.00/3.6
11.00/5.0
15.00/6.8
18.00/8.2
11.00/5.0
12.00/5.4
15.00/6.8
16.00/7.3
22.00/10.00
24.00/10.9
29.00/13.2
33.00/15.0
22.00/10.00
24.00/10.9
29.00/13.2
34.00/15.4
41.00/18.6
31.00/14.1
39.00/17.7
45.00/20.4
23.00/10.4
27.00/12.2
32.00/14.5
31.00/14.1
40.00/18.1
48.00/21.8
44.00/20.0
47.00/21.3
50.00/22.7
45.00/20.4
54.00/24.5
60.00/27.2
66.00/29.9
72.00/32.7
82.00/37.2
35.00/15.9
40.00/18.1
52.00/23.6
75.00/34.0
85.00/38.6

Aluminum Weight
lb/kg
2.00/0.9
3.00/1.4
3.00/1.4
3.00/1.4
3.00/1.4
4.00/1.8
6.00/2.7
7.00/3.2
4.00/1.8
5.00/2.3
6.00/2.7
6.00/2.7
8.00/3.6
9.00/4.1
11.00/5.0
13.00/5.9
8.00/3.6
9.00/4.1
11.00/5.0
13.00/5.9
15.00/6.8
12.00/5.4
15.00/6.8
18.00/8.2
9.00/4.1
10.00/4.5
12.00/5.4
12.00/5.4
15.00/6.8
18.00/8.2
17.00/7.7
18.00/8.2
19.00/8.6
17.00/7.7
19.00/8.6
22.00/10.0
25.00/11.3
27.00/12.2
31.00/14.1
13.00/5.9
15.00/6.8
20.00/9.1
28.00/12.7
32.00/14.5

Catalog
Number †
DTX-040403
DTX-040404
DTX-050504
DTX-060403
DTX-060404
DTX-060603
DTX-060604
DTX-060606
DTX-080403
DTX-080404
DTX-080603
DTX-080604
DTX-080606
DTX-080804
DTX-080806
DTX-080808
DTX-100604
DTX-100606
DTX-100804
DTX-100806
DTX-100808
DTX-101004
DTX-101006
DTX-101008
DTX-120404
DTX-120604
DTX-120606
DTX-120804
DTX-120806
DTX-120808
DTX-121004
DTX-121006
DTX-121008
DTX-121204
DTX-121206
DTX-121207
DTX-121208
DTX-121210
DTX-121212
DTX-140804
DTX-140806
DTX-140808
DTX-141406
DTX-141408

† Type DTX boxes must have a minimum of 3-1/2 full threads at all conduit entrances. The “Max. Conduit Size” listed herein indicates the maximum drilled and
tapped conduit entrance which can be machined into the four unbossed sides of a given box to provide these 3-1/2 full threads. If larger conduit openings
than those listed herein are required, bosses can be supplied by us at an additional cost to provide the minimum 3-1/2 full thread requirement. In addition to
the minimum 3-1/2 full thread requirement, the length of thread at conduit entrances must also be at least 1/4”. A 3/8” conduit entrance therefore requires a
minimum of a 0.25”/6.4mm wall thickness. For aluminum box and cover, add suffix —A.

612

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DTX Series Junction Boxes
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 9EFG

Inside Dim. Inches/Millimeters
L
14.00/355.6
16.00/406.4
16.00/406.4
16.00/406.4
16.00/406.4
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
28.00/711.2
28.00/711.2
30.00/762.0
30.00/762.0
30.00/762.0
30.00/762.0
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

W
14.00/355.6
12.00/304.8
12.00/304.8
12.00/304.8
16.00/406.4
6.00/152.4
8.00/203.2
8.00/203.2
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
12.00/304.8
12.00/304.8
12.00/304.8
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
12.00/304.8
12.00/304.8
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
24.00/609.6
36.00/914.4
36.00/914.4
36.00/914.4

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

D
10.00/254.0
4.00/101.6
6.00/152.4
8.00/203.2
6.00/152.4
6.00/152.4
4.00/101.6
6.00/152.4
4.00/101.6
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
18.00/457.2
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
6.00/152.4
8.00/203.2
12.00/304.8
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
8.00/203.2
12.00/304.8
8.00/203.2
10.00/254.0
12.00/304.8
18.00/457.2
6.00/152.4
8.00/203.2
12.00/304.8
18.00/457.2
18.00/457.2
8.00/203.2
12.00/304.8
18.00/457.2

Iron Weight lb/kg
92.00/41.7
62.00/28.1
73.00/33.1
81.00/36.7
100.00/45.4
50.00/22.7
52.00/23.6
57.00/25.9
61.00/27.7
82.00/37.2
97.00/44.0
107.00/48.5
125.00/56.7
171.00/77.6
130.00/59.0
141.00/64.0
156.00/70.8
181.00/82.1
105.00/47.6
125.00/56.7
160.00/72.6
165.00/74.8
175.00/79.4
190.00/86.2
235.00/106.6
225.00/102.1
235.00/106.6
260.00/117.9
300.00/136.1
150.00/68.0
185.00/83.9
310.00/140.6
335.00/152.0
360.00/163.3
480.00/217.7
245.00/111.1
360.00/163.3
350.00/158.8
550.00/249.5
650.00/294.8
485.00/220.0
530.00/240.4
850.00/385.6

Aluminum Weight
lb/kg
34.00/15.4
23.00/10.4
27.00/12.2
30.00/13.6
37.00/16.8
19.00/8.6
20.00/9.1
21.00/9.5
23.00/10.4
31.00/14.1
36.00/16.3
40.00/18.1
47.00/21.3
64.00/29.0
48.00/21.8
52.00/23.6
58.00/26.3
67.00/30.4
39.00/17.7
47.00/21.3
60.00/27.2
61.00/27.7
65.00/29.5
70.00/31.8
87.00/39.5
84.00/38.1
87.00/39.5
96.00/43.5
111.00/50.3
56.00/25.4
69.00/31.3
115.00/52.2
124.00/56.2
134.00/60.8
159.00/72.1
91.00/41.3
96.00/43.5
130.00/59.0
209.00/94.8
245.00/111.1
184.00/83.5
200.00/90.7
315.00/142.9

Catalog
Number †
DTX-141410
DTX-161204
DTX-161206
DTX-161208
DTX-161606
DTX-180606
DTX-180804
DTX-180806
DTX-181204
DTX-181206
DTX-181208
DTX-181210
DTX-181212
DTX-181218
DTX-181806
DTX-181808
DTX-181810
DTX-181812
DTX-241206
DTX-241208
DTX-241212
DTX-241806
DTX-241808
DTX-241810
DTX-241812
DTX-242406
DTX-242408
DTX-242410
DTX-242412
DTX-281208
DTX-281212
DTX-302408
DTX-302410
DTX-302412
DTX-302418
DTX-361806
DTX-361808
DTX-361812
DTX-361818
DTX-362418
DTX-363608
DTX-363612
DTX-363618

† Type DTX boxes must have a minimum of 3-1/2 full threads at all conduit entrances. The “Max. Conduit Size” listed herein indicates the maximum drilled and
tapped conduit entrance which can be machined into the four unbossed sides of a given box to provide these 3-1/2 full threads. If larger conduit openings
than those listed herein are required, bosses can be supplied by us at an additional cost to provide the minimum 3-1/2 full thread requirement. In addition to
the minimum 3-1/2 full thread requirement, the length of thread at conduit entrances must also be at least 1/4”. A 3/8” conduit entrance therefore requires a
minimum of a 0.25”/6.4mm wall thickness. For aluminum box and cover, add suffix —A.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

613

Enclosures and Junction Boxes: Hazardous Junction Boxes

Maximum
Conduit
Size
(In.-NPT)
2
3/4
3/4
3/4
2
3/4
3/4
3/4
3/4
3/4
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
5
6
6

Enclosures and Junction Boxes

Approximate
Thickness
Side Walls
in/mm
0.31/7.9
0.28/7.1
0.28/7.1
0.28/7.1
0.31/7.9
0.28/7.1
0.28/7.1
0.28/7.1
0.25/6.4
0.28/7.1
0.31/7.9
0.31/7.9
0.31/7.9
0.34/8.6
0.31/7.9
0.31/7.9
0.31/7.9
0.31/7.9
0.31/7.9
0.31/7.9
0.31/7.9
0.34/8.6
0.34/8.6
0.34/8.6
0.34/8.6
0.34/8.6
0.34/8.6
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.41/10.4
0.44/11.2
0.44/11.2
0.44/11.2

DTX Series Junction Box Mounting Plate Information
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.
Class II, Division 1 and 2, Groups E, F, G
Class III
NEMA 4, 9EFG

Mounting plates are used for mounting equipment up off the back of an enclosure. Steel Plates are all 0.13”/3.3mm thick hot dip galvanized
material. Aluminum plates are 0.13”/3.3 mm thick material up to and including 12 x 12” / 304.8 x 304.8 mm size. All larger sizes are constructed
of 0.19”/4.8mm thick aluminum plate. The catalog numbers shown in the table below include the mounting buttons.
Select mounting plates based on inside length and width of box. Order as a separate item immediately following the catalog number of the
box as follows:
Example: 	Line 1	
DTX-181204
	
Line 2	
WYM-1812-1

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

For mounting plates in smaller boxes than listed, use similar catalog number logic. Example: A steel mounting plate for a DTX-040404 box
would be WYM-0404-1. Pricing will be based upon a WYM-0808-1 price.

Inside Length & Width
of Junction Box in in/mm
8 x 8/203.2 x 203.2
10 x 8/254.0 x 203.2
10 x 10/254.0 x 254.0
12 x 8/304.8 x 203.2
12 x 10/304.8 x 254.0
12 x 12/304.8 x 304.8
14 x 8355.6 x 203.2
14 x 14/355.6 x 355.6
16 x 8/406.4 x 203.2
16 x 12/406.4 x 304.8
16 x 16/406.4 x 406.4
18 x 8/457.2 x 203.2
18 x 10/457.2 x 254.0
18 x 12/457.2 x 304.8
18 x 14/457.2 x 355.6
18 x 16/457.2 x 406.4
18 x 18/457.2 x 457.2
20 x 10/508.0 x 254.0
24.00 x 12.00/609.6 x 304.8
24.00 x 18.00/609.6 x 457.2
24.00 x 24.00/609.6 x 609.6
28.00 x 12.00/711.2 x 304.8
30.00 x 12.00/762.0 x 304.8
30.00 x 18.00/762.0 x 457.2
30.00 x 24.00/762.0 x 609.6
36.00 x 12.00/914.4 x 304.8
36.00 x 18.00/914.4 x 457.2
36.00 x 24.00/914.4 x 609.6
36.00 x 30.00/914.4 x 762.0
36.00 x 36.00/914.4 x 914.4

614

Catalog Number
Steel Plates
Aluminum Plates
WYM-0808-1
WYM-0808-1A
WYM-1008-1
WYM-1008-1A
WYM-1010-1
WYM-1010-1A
WYM-1208-1
WYM-1208-1A
WYM-1210-1
WYM-1210-1A
WYM-1212-1
WYM-1212-1A
WYM-1408-1
WYM-1408-1A
WYM-1414-1
WYM-1414-1A
WYM-1608-1
WYM-1608-1A
WYM-1612-1
WYM-1612-1A
WYM-1616-1
WYM-1616-1A
WYM-1808-1
WYM-1808-1A
WYM-1810-1
WYM-1810-1A
WYM-1812-1
WYM-1812-1A
WYM-1814-1
WYM-1814-1A
—
—
WYM-1818-1
WYM-1818-1A
WYM-2010-1
WYM-2010-1A
WYM-2412-1
WYM-2412-1A
WYM-2418-1
WYM-2418-1A
WYM-2424-1
WYM-2424-1A
WYM-2812-1
WYM-2812-1A
WYM-3012-1
WYM-3012-1A
WYM-3018-1
WYM-3018-1A
WYM-3024-1
WYM-3024-1A
WYM-3612-1
WYM-3612-1A
WYM-3618-1
WYM-3618-1A
WYM-3624-1
WYM-3624-1A
WYM-3630-1
WYM-3630-1A
WYM-3636-1
WYM-3636-1A

Style
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
—
1
1
2
2
3
2
2
2
3
2
2
3
3
3

L
6.75/171.5
8.75/222.3
8.75/222.3
10.75/273.1
10.75/273.1
10.75/273.1
12.75/323.9
12.75/323.9
14.75/374.7
14.75/374.7
14.75/374.7
16.75/171.5
16.75/171.5
16.75/171.5
16.75/171.5
—
16.75/171.5
18.75/222.3
21.75/552.5
21.75/552.5
21.75/552.5
25.75/654.1
27.75/704.9
27.75/704.9
27.75/704.9
33.75/857.3
33.75/857.3
33.75/857.3
33.75/857.3
33.75/857.3

Dimension in Inches/Millimeters
W
A
6.75/171.5
6.00/152.4
6.75/171.5
8.00/203.2
8.75/222.3
8.00/203.2
6.75/171.5
10.00/254.0
8.75/222.3
10.00/254.0
10.75/273.1
10.00/254.0
6.75/171.5
12.00/304.8
12.75/323.9
12.00/304.8
6.75/171.5
14.00/355.6
10.75/273.1
14.00/355.6
14.75/374.7
14.00/355.6
6.75/171.5
16.00/152.4
8.75/222.3
16.00/152.4
10.75/273.1
16.00/152.4
12.75/323.9
16.00/152.4
—
—
16.75/171.5
16.00/152.4
8.75/222.3
18.00/203.2
9.75/247.7
21.00/533.4
15.75/400.1
21.00/533.4
21.75/552.5
21.00/533.4
9.75/247.7
25.00/635.0
9.75/247.7
27.00/685.8
15 .75/400.1
27.00/685.8
21.75/552.5
27.00/685.8
9.75/247.7
33.00/838.2
15.75/400.1
33.00/838.2
21.75/552.5
33.00/838.2
27.75/704.9
33.00/838.2
33.75/857.3
33.00/838.2

B
6.00/152.4
8.00/203.2
8.00/203.2
6.00/152.4
8.00/203.2
10.00/254.0
6.00/152.4
12.00/304.8
6.00/152.4
10.00/254.0
14.00/355.6
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
—
16.00/152.4
8.00/203.2
9.00/228.6
15.00/381.0
21.00/533.4
9.00/228.6
9.00/228.6
15.00/381.0
21.00/533.4
9.00/228.6
15.00/381.0
21.00/533.4
27.00/685.8
33.00/838.2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DTX Series Junction Box Drill and Tap Schedule
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.

Ordering Information

ARE INDICATED CONDUIT
SIZES WITHIN THE CATALOG
PUBLISHED MAXIMUM ON
PAGES K-40 AND K-43?
CHECK FOR MINIMUM
SPACING BETWEEN CONDUIT
OPENINGS PER CONDUIT
SPACING TABLE, ON PAGE
K-41.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Hazardous Junction Boxes

ENCLOSURE

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

615

DTX Series Junction Box Dimensions
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.

Outside Flange Dimensional Data in Inches/Millimeters
Useable
Conduit Area

C
D
M

A
E-MTG

Useable
Conduit Area

S
Opening

P

X

M
X

B

F
MTG

L/2

Front View

G
Dia.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Hazardous Junction Boxes

C

D

E

T
Opening

F

Y

N
End View

Front View
Less Cover
Mounting
Thickness Depth

G

P

J
N/2

Conduit Area
L

M

N

P

Section View

Clear
Opening

Wall Thickness

S

X

T

Y

Z

Catalog
Number

J

K

5.56/ 5.56/ 3.34/ 3.16/ 5.56/ 3.00/ 0.31/
141.2 141.2 84.8 80.3 141.2 76.2
7.9

0.13/
3.3

3.00/
76.2

5.56/ 5.56/ 4.34/ 4.16/ 5.56/ 4.00/ 0.31/
141.2 141.2 110.2 105.7 141.2 101.6 7.9

0.13/
3.3

4.00/ 3.50/ 2.31/ 3.50/ 0.44/ 4.00/ 4.00/ 0.16/ 0.19/ 0.16/
DTX-040404
101.6 88.9 58.7 88.9 11.2 101.6 101.6 4.1 4.8 4.1

6.81/ 6.81/ 4.38/ 4.19/ 6.50/ 4.00/ 0.31/
173/0 173.0 111.3 106.4 165.1 101.6 7.9

0.13/
3.3

4.00/ 4.50/ 3.31/ 3.50/ 0.44/ 5.00/ 5.00/ 0.19/ 0.19/ 0.19/
DTX-050504
101.6 114.3 84.1 88.9 11.2 127.0 127.0 4.8 4.8 4.8

5.56/ 7.56/ 3.34/ 3.16/ 5.38/ 5.00/ 0.31/
141.2 192.0 84.8 80.3 136.7 127.0 7.9

0.13/
3.3

3.00/ 5.50/ 2.31/ 3.50/ 0.44/ 4.00/ 6.00/ 0.16/ 0.19/ 0.16/
DTX-060403
76.2 139.7 58.7 88.9 11.2 101.6 152.4 4.1 4.8 4.1

5.56/ 7.56/ 4.34/ 4.16/ 5.38/ 5.00/ 0.31/
141.2 192.0 110.2 105.7 136.7 127.0 7.9

0.13/
3.3

3.00/ 5.50/ 3.31/ 3.50/ 0.44/ 4.00/ 6.00/ 0.16/ 0.19/ 0.16/
DTX-060404
76.2 139.7 84.1 88.9 11.2 101.6 152.4 4.1 4.8 4.1

7.81/ 7.81/ 3.38/ 3.19/ 7.50/ 4.00/ 0.38/
198.4 198.4 85.9 81.0 190.5 101.6 9.7

0.25/
6.4

3.00/ 5.50/ 2.25/ 5.50/ 0.44/ 6.00/ 6.00/ 0.19/ 0.19/ 0.19/
DTX-060603
76.2 139.7 57.2 139.7 11.2 152.4 152.4 4.8 4.8 4.8

7.81/ 7.81/ 4.41/ 4.22/ 7.50/ 4.00/ 0.38/
198.4 198.4 112.0 107.2 190.5 101.6 9.7

0.25/
6.4

4.00/ 5.50/ 3.25/ 5.50/ 0.44/ 6.00/ 6.00/ 0.22/ 0.19/ 0.22/
DTX-060604
101.6 139.7 82.6 139.7 11.2 152.4 152.4 5.6 4.8 5.6

7.81/ 7.81/ 6.41/ 6.22/ 7.50/ 4.00/ 0.38/
198.4 198.4 162.8 158.0 190.5 101.6 9.7

0.25/
6.4

6.00/ 5.50/ 6.25/ 5.50/ 0.44/ 6.00/ 6.00/ 0.19/ 0.19/ 0.19/
DTX-060606
152.4 139.7 158.8 139.7 11.2 152.4 152.4 4.8 4.8 4.8

5.81/ 9.81/ 3.44/ 3.19/ 5.50/ 5.00/ 0.38/
147.6 249.2 87.4 81.0 139.7 127.0 9.7

0.25/
6.4

3.00/ 7.50/ 2.25/ 3.50/ 0.47/ 4.00/ 8.00/ 0.19/ 0.25/ 0.19/
DTX-080403
76.2 190.5 57.2 88.9 11.9 101.6 203.2 4.8 6.4 4.8

5.81/ 9.81/ 4.44/ 4.19/ 5.50/ 5.00/ 0.38/
147.6 249.2 112.8 106.4 139.7 127.0 9.7

0.25/
6.4

4.00/ 7.50/ 3.25/ 3.50/ 0.47/ 4.00/ 8.00/ 0.19/ 0.25/ 0.19/
DTX-080404
6.4 4.8
101.6 190.5 82.6 88.9 11.9 101.6 203.2 4.8

7.81/ 9.81/ 3.47/ 3.22/ 7.63/ 5.00/ 0.38/
198.4 249.2 88.1 81.8 193.8 127.0 9.7

0.25/
6.4

3.00/ 7.50/ 2.25/ 5.50/ 0.50/ 6.00/ 8.00/ 0.22/ 0.25/ 0.22/
DTX-080603
76.2 190.5 57.2 139.7 12.7 152.4 203.2 5.6 6.4 5.6

7.81/ 9.81/ 4.47/ 4.22/ 7.63/ 5.00/ 0.38/
198.4 249.2 113.5 107.2 193.8 127.0 9.7

0.25/
6.4

4.00/ 7.50/ 3.25/ 5.50/ 0.50/ 6.00/ 8.00/ 0.22/ 0.25/ 0.22/
DTX-080404
101.6 190.5 82.6 139.7 12.7 152.4 203.2 5.6 6.4 5.6

7.81/ 9.81/ 6.47/ 6.22/ 7.63/ 5.00/ 0.38/
198.4 249.2 164.3 158.0 193.8 127.0 9.7

0.25/
6.4

6.00/ 7.50/ 5.25/ 5.50/ 0.50/ 6.00/ 8.00/ 0.22/ 0.25/ 0.22/
DTX-080606
152.4 190.5 133.4 139.7 12.7 152.4 203.2 5.6 6.4 5.6

616

B

Z

Side View

Mounting
Enclosure

Overall Enclosure
A

K

L

3.50/ 2.31/ 3.50/ 0.44/ 4.00/ 4.00/ 0.16/ 0.19/ 0.16/
DTX-040403
88.9 58.7 88.9 11.2 101.6 101.6 4.1 4.8 4.1

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DTX Series Junction Box Dimensions
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.

Outside Flange Dimensional Data in Inches/Millimeters
Useable
Conduit Area

C
D
M

A
E-MTG

Useable
Conduit Area

S
Opening

P

X

M
X

B

K

L

F
MTG

T
Opening

L/2
G
Dia.

Front View

C

D

E

F

Mounting
Thickness Depth
G

J

Y

N
End View

Conduit Area
L

M

N

P

Section View

Clear
Opening

Wall Thickness

S

X

T

Y

Z

Catalog
Number

9.81/
249.2

9.81/
249.2

4.47/ 4.22/ 9.63/ 5.00/ 0.38/
113.5 107.2 244.6 127.0 9.7

0.25/
6.4

4.00/ 7.50/ 3.25/ 7.50/ 0.50/ 8.00/ 8.00/ 0.22/ 0.25/ 0.22/
DTX-080804
101.6 190.5 82.6 190.5 12.7 203.2 203.2 5.6 6.4 5.6

9.81/
249.2

9.81/
249.2

6.47/ 6.22/ 9.63/ 5.00/ 0.38/
164.3 158.0 244.6 127.0 9.7

0.25/
6.4

6.00/ 7.50/ 5.25/ 7.50/ 0.50/ 8.00/ 8.00/ 0.22/ 0.25/ 0.22/
DTX-080806
152.4 190.5 133.4 190.5 12.7 203.2 203.2 5.6 6.4 5.6

9.81/
249.2

9.81/
249.2

8.47/ 8.22/ 9.63/ 5.00/ 0.38/
215.1 208.8 244.6 127.0 9.7

0.25/
6.4

8.00/ 7.38/ 7.25/ 7.38/ 0.50/ 8.00/ 8.00/ 0.22/ 0.25/ 0.22/
DTX-080808
203.2 187.5 184.2 187.5 12.7 203.2 203.2 5.6 6.4 5.6

7.81/ 11.81/
198.4 300.0

4.47/ 4.22/ 7.63/ 7.00/ 0.38/
113.5 107.2 193.8 177.8 9.7

0.25/
6.4

4.00/ 9.50/ 3.25/ 5.50/ 0.50/ 6.00/ 10.00/ 0.22/ 0.25/ 0.22/
DTX-010604
101.6 241.3 82.6 139.7 12.7 152.4 254.0 5.6 6.4 5.6

7.81/ 11.81/
198.4 300.0

6.47/ 6.22/ 7.63/ 7.00/ 0.38/
164.3 158.0 193.8 177.8 9.7

0.25/
6.4

6.00/ 9.50/ 5.25/ 5.50/ 0.50/ 6.00/ 10.00/ 0.22/ 0.25/ 0.22/
DTX-100606
152.4 241.3 133.4 139.7 12.7 152.4 254.0 5.6 6.4 5.6

10.06/ 12.81/ 40.53/ 4.25/ 90.75/ 7.00/ 0.38/
255.5 325.4 1029.5 108.0 2305.1 177.8 9.7

0.25/
6.4

4.00/ 9.50/ 3.25/ 7.50/ 0.50/ 8.00/ 10.00/ 0.25/ 0.28/ 0.25/
DTX-100804
101.6 241.3 82.6 190.5 12.7 203.2 254.0 6.4 7.1 6.4

10.06/ 120.06/ 8.47/ 6.25/ 90.75/ 7.00/ 0.38/
255.5 3049.5 215.1 158.8 2305.1 177.8 9.7

0.25/
6.4

6.00/ 9.50/ 5.25/ 7.50/ 0.50/ 8.00/ 10.00/ 0.25/ 0.28/ 0.25/
DTX-100806
152.4 241.3 133.4 190.5 12.7 203.2 254.0 6.4 7.1 6.4

10.06/ 120.06/ 80.53/ 8.25/ 90.75/ 7.00/ 0.38/
255.5 3049.5 2045.5 209.6 2305.1 177.8 9.7

0.25/
6.4

8.00/ 9.38/ 7.25/ 7.38/ 0.50/ 8.00/ 10.00/ 0.25/ 0.28/ 0.25/
DTX-100808
203.2 238.3 184.2 187.5 12.7 203.2 254.0 6.4 7.1 6.4

10.06/ 120.06/ 40.53/ 4.25/ 11.63/ 7.00/ 0.38/
255.5 3049.5 1029.5 108.0 295.4 177.8 9.7

0.25/
6.4

4.00/ 9.50/ 3.25/ 9.50/ 0.50/ 10.00/ 10.00/ 0.25/ 0.28/ 0.25/
DTX-101004
101.6 241.3 82.6 241.3 12.7 254.0 254.0 6.4 7.1 6.4

10.06/ 120.06/ 60.53/ 6.25/ 11.63/ 7.00/ 0.38/
255.5 3049.5 1537.5 158.8 295.4 177.8 9.7

0.25/
6.4

6.00/ 9.50/ 5.25/ 9.50/ 0.50/ 10.00/ 10.00/ 0.25/ 0.28/ 0.25/
DTX-101006
152.4 241.3 133.4 241.3 12.7 254.0 254.0 6.4 7.1 6.4

12.06/ 120.06/ 80.53/ 8.25/ 11.63/ 7.00/ 0.38/
306.3 3049.5 2045.5 209.6 295.4 177.8 9.7

0.25/
6.4

8.00/ 9.38/ 7.25/ 9.38/ 0.50/ 10.00/ 10.00/ 0.25/ 0.28/ 0.25/
DTX-101008
203.2 238.3 184.2 238.3 12.7 254.0 254.0 6.4 7.1 6.4

6.06/ 140.06/ 4.50/ 4.25/ 5.38/ 8.00/ 0.38/
153.9 3557.5 114.3 108.0 136.7 203.2 9.7

0.25/
6.4

4.00/ 11.50/ 3.25/ 3.50/ 0.50/ 4.00/ 12.00/ 0.25/ 0.25/ 0.25/
DTX-120404
101.6 292.1 82.6 88.9 12.7 101.6 304.8 6.4 6.4 6.4

8.06/ 140.06/ 40.53/ 4.25/ 8.38/ 8.00/ 0.44/
204.7 3557.5 1029.5 108.0 212.9 203.2 11.2

0.38/
9.7

4.00/ 11.50/ 3.25/ 5.50/ 0.50/ 6.00/ 12.00/ 0.25/ 0.28/ 0.25/
DTX-120604
101.6 292.1 82.6 139.7 12.7 152.4 304.8 6.4 7.1 6.4

8.06/ 140.06/ 60.53/ 6.25/ 8.38/ 8.00/ 0.44/
204.7 3557.5 1537.5 158.8 212.9 203.2 11.2

0.38/
9.7

6.00/ 11.50/ 5.25/ 5.50/ 0.50/ 6.00/ 12.00/ 0.25/ 0.28/ 0.25/
DTX-120606
152.4 292.1 133.4 139.7 12.7 152.4 304.8 6.4 7.1 6.4

617

Enclosures and Junction Boxes: Hazardous Junction Boxes

B

Enclosures and Junction Boxes

A

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

K

P

J
N/2
Front View
Less Cover

Side View
Mounting
Enclosure

Overall Enclosure

Z

DTX Series Junction Box Dimensions
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Outside Flange Dimensional Data in Inches/Millimeters

A
10.06/
255.5
10.06/
255.5
10.06/
255.5
12.06/
306.3
12.06/
306.3
12.06/
306.3
14.06/
357.1
14.06/
357.1
14.06/
357.1
14.06/
357.1
14.06/
357.1
14.06/
357.1
10.06/
255.5
10.06/
255.5
10.06/
255.5
16.63/
422.4
16.63/
422.4
16.63/
422.4
14.63/
371.6
14.63/
371.6
14.63/
371.6
18.63/
473.2
8.09/
205.5
10.09/
256.3
10.09/
256.3
14.63/
371.6
14.63/
371.6
14.63/
371.6
14.63/
371.6
14.63/
371.6
14.63/
371.6

618

Overall Enclosure
B
C
14.06/ 4.53/
357.1 115.0
14.06/ 6.53/
357.1 165.9
14.06/ 8.53/
357.1 216.7
14.06/ 4.53/
357.1 115.0
14.06/ 6.53/
357.1 165.9
14.06/ 8.53/
357.1 216.7
14.06/ 4.56/
357.1 115.8
14.06/ 6.56/
357.1 166.6
14.06/ 7.63/
357.1 193.8
14.06/ 8.63/
357.1 219.2
14.06/ 10.63/
357.1 270.0
14.06/ 12.63/
357.1 320.8
16.06/ 4.53/
407.9 115.0
16.06/ 6.53/
407.9 165.9
16.06/ 8.53/
407.9 216.7
16.63/ 6.59/
422.4 167.4
16.63/ 8.59/
422.4 218.2
16.63/ 10.59/
422.4 269.0
18.63/ 4.59/
473.2 116.6
18.63/ 6.59/
473.2 167.4
18.63/ 8.59/
473.2 218.2
18.63/ 6.63/
473.2 168.4
20.09/ 6.59/
510.3 167.4
20.09/ 4.59/
510.3 116.6
20.09/ 6.59/
510.3 167.4
20.63/ 4.56/
524.0 115.8
20.63/ 6.59/
524.0 167.4
20.63/ 8.63/
524.0 219.2
20.63/ 10.63/
524.0 270.0
20.63/ 12.63/
524.0 320.8
20.63/ 18.66/
524.0 474.0

D
4.25/
108.0
6.25/
158.8
8.25/
209.6
4.25/
108.0
6.25/
158.8
8.25/
209.6
4.25/
108.0
6.25/
158.8
7.31/
185.7
8.31/
211.1
10.31/
261.9
12.31/
312.7
4.25/
108.0
6.25/
158.8
8.25/
209.6
6.28/
159.5
8.28/
210.3
10.28/
261.1
4.28/
108.7
6.28/
159.5
8.28/
210.3
6.31/
160.3
6.28/
159.5
4.28/
108.7
6.28/
159.5
4.25/
108.0
6.28/
159.5
8.31/
211.1
10.31/
261.9
12.31/
312.7
18.34/
465.8

Mounting
Enclosure
E
F
10.38/ 8.00/
263.7 203.2
10.38/ 8.00/
263.7 203.2
10.38/ 8.00/
263.7 203.2
12.38/ 8.00/
314.5 203.2
12.38/ 8.00/
314.5 203.2
12.38/ 8.00/
314.5 203.2
14.38/ 8.00/
365.3 203.2
14.38/ 8.00/
365.3 203.2
14.38/ 8.00/
365.3 203.2
14.38/ 8.00/
365.3 203.2
14.38/ 8.00/
365.3 203.2
14.38/ 8.00/
365.3 203.2
10.38/ 10.00/
263.7 254.0
10.38/ 10.00/
263.7 254.0
10.38/ 10.00/
263.7 254.0
16.50/ 10.00/
419.1 254.0
16.50/ 10.00/
419.1 254.0
16.50/ 10.00/
419.1 254.0
14.50/ 12.00/
368.3 304.8
14.50/ 12.00/
368.3 304.8
14.50/ 12.00/
368.3 304.8
18.50/ 12.00/
469.9 304.8
8.50/ 13.00/
215.9 330.2
10.50/ 13.00/
266.7 330.2
10.50/ 13.00/
266.7 330.2
14.38/ 13.00/
365.3 330.2
14.38/ 13.00/
365.3 330.2
14.38/ 13.00/
365.3 330.2
14.38/ 13.00/
365.3 330.2
14.38/ 13.00/
365.3 330.2
14.38/ 13.00/
365.3 330.2

G
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9
0.43/
10.9

Mounting
Thickness
J
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7

Depth
K
4.00/
101.6
6.00/
152.4
8.00/
203.2
4.00/
101.6
6.00/
152.4
8.00/
203.2
4.00/
101.6
5.00/
127.0
7.00/
177.8
8.00/
203.2
10.00/
254.0
12.00/
304.8
4.00/
101.6
6.00/
152.4
8.00/
203.2
6.00/
152.4
8.00/
203.2
10.00/
254.0
4.00/
101.6
6.00/
152.4
8.00/
203.2
6.00/
152.4
6.00/
152.4
4.00/
101.6
6.00/
152.4
4.00/
101.6
6.00/
152.4
8.00/
203.2
10.00/
254.0
12.00/
304.8
18.00/
457.2

L
11.50/
292.1
11.50/
292.1
11.38/
289.1
11.50/
292.1
11.50/
292.1
11.50/
292.1
11.38/
289.1
11.50/
292.1
11.38/
289.1
11.38/
289.1
11.25/
285.8
11.25/
285.8
13.25/
336.6
13.25/
336.6
13.13/
333.5
13.25/
336.6
13.25/
336.6
13.00/
330.2
15.25/
387.4
15.25/
387.4
15.00/
381.0
15.25/
387.4
17.25/
438.2
17.25/
438.2
17.25/
438.2
17.25/
438.2
17.25/
438.2
17.00/
431.8
17.00/
431.8
16.88/
428.8
16.75/
425.5

Conduit Area
M
N
3.25/ 7.50/
82.6 190.5
5.25/ 7.50/
113.4 190.5
7.25/ 7.38/
184.2 187.5
3.25/ 9.50/
82.6 241.3
5.25/ 9.50/
113.4 241.3
7.25/ 9.38/
184.2 238.3
3.19/ 11.50/
81.0 292.1
5.19/ 11.50/
131.8 292.1
6.19/ 11.38/
157.2 289.1
7.19/ 11.38/
182.6 289.1
9.19/ 11.25/
233.4 285.8
11.19/ 11.25/
284.2 285.8
3.00/ 7.25/
76.2 184.2
5.00/ 7.25/
127.0 184.2
7.00/ 7.13/
177.8 181.1
4.94/ 13.25/
125.5 336.6
6.94/ 13.25/
176.3 336.6
8.94/ 13.00/
227.1 330.2
2.94/ 11.25/
74.7 285.8
4.94/ 11.25/
125.5 285.8
6.94/ 11.00/
176.3 279.4
4.94/ 15.25/
125.5 387.4
4.94/ 5.25/
125.5 133.4
2.94/ 7.25/
74.7 184.2
4.94/ 7.25/
125.5 184.2
2.94/ 11.25/
74.7 285.8
4.94/ 11.25/
125.5 285.8
6.94/ 11.00/
176.3 279.4
6.94/ 11.00/
176.3 279.4
10.94/ 10.88/
277.9 276.4
16.94/ 10.75/
430.3 273.1

P
0.50/
12.7
0.50/
12.7
0.50/
12.7
0.50/
12.7
0.50/
12.7
0.50/
12.7
0.50/
12.7
0.50/
12.7
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.63/
16.0
0.63/
16.0
0.63/
16.0
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.63/
16.0
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.75/
19.1

Clear
Opening
S
T
8.00/ 12.00/
203.2 304.8
8.00/ 12.00/
203.2 304.8
8.00/ 12.00/
203.2 304.8
10.00/ 12.00/
254.0 304.8
10.00/ 12.00/
254.0 304.8
10.00/ 12.00/
254.0 304.8
12.00/ 12.00/
304.8 304.8
12.00/ 12.00/
304.8 304.8
12.00/ 12.00/
304.8 304.8
12.00/ 12.00/
304.8 304.8
12.00/ 12.00/
304.8 304.8
12.00/ 12.00/
304.8 304.8
8.00/ 14.00/
203.2 355.6
8.00/ 14.00/
203.2 355.6
8.00/ 14.00/
203.2 355.6
14.00/ 14.00/
355.6 355.6
14.00/ 14.00/
355.6 355.6
14.00/ 14.00/
355.6 355.6
12.00/ 16.00/
304.8 406.4
12.00/ 16.00/
304.8 406.4
12.00/ 16.00/
304.8 406.4
16.00/ 16.00/
406.4 406.4
6.00/ 18.00/
152.4 457.2
8.00/ 18.00/
203.2 457.2
8.00/ 18.00/
203.2 457.2
12.00/ 18.00/
304.8 457.2
12.00/ 18.00/
304.8 457.2
12.00/ 18.00/
304.8 457.2
12.00/ 18.00/
304.8 457.2
12.00/ 18.00/
304.8 457.2
12.00/ 18.00/
304.8 457.2

Wall Thickness
X
Y
Z
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.31/ 0.25/
6.4
7.9
6.4
0.25/ 0.31/ 0.25/
6.4
7.9
6.4
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.25/ 0.28/ 0.25/
6.4
7.1
6.4
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.25/ 0.31/ 0.25/
6.4
7.9
6.4
0.28/ 0.31/ 0.28/
7.1
7.9
7.1
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.34/ 0.31/ 0.34/
8.6
7.9
8.6

Catalog
Number
DTX-120804
DTX-120806
DTX-120808
DTX-121004
DTX-121006
DTX-121008
DTX-121204
DTX-121206
DTX-121207
DTX-121208
DTX-121210
DTX-121212
DTX-140804
DTX-140806
DTX-140808
DTX-141406
DTX-141408
DTX-141410
DTX-161204
DTX-161206
DTX-161208
DTX-161606
DTX-180606
DTX-180804
DTX-180806
DTX-181204
DTX-181206
DTX-181208
DTX-181210
DTX-181212
DTX-181218

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

DTX Series Junction Box Dimensions
Dust-Ignitionproof, Watertight

Cast iron box and cover for surface mounting. Cast aluminum box and cover for surface mounting.

Outside Flange Dimensional Data in Inches/Millimeters

G
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2
0.56/
14.2

Mounting
Thickness
J
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7
0.38/
9.7

Depth
K
6.00/
152.4
8.00/
203.2
10.00/
254
12.00/
304.8
6.00/
152.4
8.00/
203.2
12.00/
304.8
6.00/
152.4
8.00/
203.2
10.00/
254
12.00/
304.8
18.00/
457.2
6.00/
152.4
8.00/
203.2
10.00/
254
12.00/
304.8
12.00/
304.8
12.00/
304.8
10.00/
254
10.00/
254
12.00/
304.8
18.00/
457.2
8.00/
203.2
8.00/
203.2
12.00/
304.8
18.00/
457.2
8.00/
203.2
10.00/
254
12.00/
304.8
18.00/
457.2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

L
17.25/
438.2
17.25/
438.2
17.00/
431.8
17.00/
431.8
23.25/
590.6
23.25/
590.6
23.00/
584.2
23.25/
590.6
23.25/
590.6
23.00/
584.2
23.00/
584.2
23.00/
584.2
23.25/
590.6
23.25/
590.6
23.00/
584.2
23.00/
584.2
27.00/
685.8
27.00/
685.8
29.25/
743
29.25/
743
29.25/
743
29.00/
736.6
35.25/
819.2
35.25/
819.2
36.00/
914.4
36.00/
914.4
36.00/
914.4
35.00/
889
36.00/
914.4
34.88/
886

Conduit Area
M
N
4.94/ 17.25/
125.5 438.2
6.94/ 17.25/
176.3 438.2
8.94/ 17.00/
227.1 431.8
10.94/ 17.00/
277.9 431.8
4.94/ 11.25/
125.5 285.8
6.94/ 11.25/
176.3 285.8
10.94/ 11.00/
277.9 279.4
4.88/ 17.25/
124
438.2
6.88/ 17.25/
174.8 438.2
8.88/ 17.00/
225.6 431.8
10.88/ 17.00/
276.4 431.8
16.88/ 17.00/
428.8 431.8
4.88/ 23.25/
124
590.6
6.88/ 23.25/
174.8 590.6
8.88/ 23.00/
225.6 584.2
10.88/ 23.00/
276.4 584.2
10.88/ 11.00/
276.4 279.4
10.88/ 11.00/
276.4 279.4
8.88/ 23.25/
225.6 590.6
8.88/ 23.25/
225.6 590.6
10.88/ 23.25/
276.4 590.6
16.88/ 23.00/
428.8 584.2
4.88/ 17.25/
124
438.2
6.88/ 17.25/
174.8 438.2
10.88/ 17.00/
276.4 431.8
16.88/ 17.00/
428.8 431.8
6.75/ 36.00/
171.5 914.4
8.75/ 36.00/
222.3 914.4
10.75/ 36.00/
273.1 914.4
16.75/ 34.88/
425.5
886

P
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.69/
17.5
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.75/
19.1
0.81/
20.6
0.81/
20.6
0.81/
20.6
0.81/
20.6

Clear
Opening
S
T
18.00/ 18.00/
457.2 457.2
18.00/ 18.00/
457.2 457.2
18.00/ 18.00/
457.2 457.2
18.00/ 18.00/
457.2 457.2
12.00/ 24.00/
304.8 609.6
12.00/ 24.00/
304.8 609.6
12.00/ 24.00/
304.8 609.6
18.00/ 24.00/
457.2 609.6
18.00/ 24.00/
457.2 609.6
18.00/ 24.00/
457.2 609.6
18.00/ 24.00/
457.2 609.6
18.00/ 24.00/
457.2 609.6
24.00/ 24.00/
609.6 609.6
24.00/ 24.00/
609.6 609.6
24.00/ 24.00/
609.6 609.6
24.00/ 24.00/
609.6 609.6
12.00/ 28.00/
304.8 711.2
12.00/ 28.00/
304.8 711.2
24.00/ 30.00/
609.6 762
24.00/ 30.00/
609.6 762
24.00/ 30.00/
609.6 762
24.00/ 30.00/
609.6 762
18.00/ 36.00/
457.2 914.4
18.00/ 36.00/
457.2 914.4
18.00/ 36.00/
457.2 914.4
18.00/ 36.00/
457.2 914.4
36.00/ 36.00/
914.4 914.4
36.00/ 36.00/
914.4 914.4
36.00/ 36.00/
914.4 914.4
36.00/ 36.00/
914.4 914.4

Wall Thickness
X
Y
Z
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.31/ 0.31/ 0.31/
7.9
7.9
7.9
0.34/ 0.38/ 0.34/
8.6
9.7
8.6
0.34/ 0.38/ 0.34/
8.6
9.7
8.6
0.34/ 0.38/ 0.34/
8.6
9.7
8.6
0.34/ 0.38/ 0.34/
8.6
9.7
8.6
0.34/ 0.38/ 0.34/
8.6
9.7
8.6
0.34/ 0.38/ 0.34/
8.6
9.7
8.6
0.34/ 0.38/ 0.34/
8.6
9.7
8.6
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.34/ 0.34/ 0.34/
8.6
8.6
8.6
0.34/ 0.34/ 0.34/
8.6
8.6
8.6
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.38/ 0.38/ 0.38/
9.7
9.7
9.7
0.44/ 0.44/ 0.44/
11.2
11.2
11.2
0.44/ 0.44/ 0.44/
11.2
11.2
11.2
0.44/ 0.44/ 0.44/
11.2
11.2
11.2
0.44/ 0.44/ 0.44/
11.2
11.2
11.2

Catalog
Number
DTX-181806
DTX-181808
DTX-181810
DTX-181812
DTX-241206
DTX-241208
DTX-241212
DTX-241806
DTX-241808
DTX-241810
DTX-241812
DTX-241818
DTX-242406
DTX-242408
DTX-242410
DTX-242412
DTX-281208
DTX-281212
DTX-302408
DTX-302410
DTX-302412
DTX-302418
DTX-361806
DTX-361808
DTX-361812
DTX-361818
DTX-363608
DTX-363610
DTX-363612
DTX-363618

619

Enclosures and Junction Boxes: Hazardous Junction Boxes

D
6.31/
160.3
8.31/
211.1
12.31/
312.7
12.31/
312.7
6.31/
160.3
8.31/
211.1
12.31/
312.7
6.34/
161
8.34/
211.8
10.34/
262.6
12.34/
313.4
18.34/
465.8
6.34/
161
8.34/
211.8
10.38/
263.7
12.38/
314.5
12.34/
313.4
12.34/
313.4
8.38/
212.9
10.38/
263.7
12.38/
314.5
18.38/
466.9
6.38/
162.1
8.38/
212.9
12.38/
314.5
18.38/
466.9
8.88/
225.6
10.88/
276.4
12.88/
327.2
18.88/
479.6

Mounting
Enclosure
E
F
20.63/ 13.00/
524 330.2
20.63/ 13.00/
524 330.2
20.63/ 13.00/
524 330.2
20.63/ 13.00/
524 330.2
14.63/ 19.00/
371.6 482.6
14.63/ 19.00/
371.6 482.6
14.63/ 19.00/
371.6 482.6
20.63/ 19.00/
524 482.6
20.63/ 19.00/
524 482.6
20.63/ 19.00/
524 482.6
20.63/ 19.00/
524 482.6
20.63/ 19.00/
524 482.6
26.88/ 19.00/
682.8 482.6
26.88/ 19.00/
682.8 482.6
26.88/ 19.00/
682.8 482.6
26.88/ 19.00/
682.8 482.6
14.75/ 22.00/
374.7 558.8
14.75/ 22.00/
374.7 558.8
26.88/ 24.00/
682.8 609.6
26.88/ 24.00/
682.8 609.6
26.88/ 24.00/
682.8 609.6
26.88/ 24.00/
682.8 609.6
20.88/ 30.00/
530.4 762
20.88/ 30.00/
530.4 762
20.88/ 30.00/
530.4 762
20.88/ 30.00/
530.4 762
38.88/ 30.00/
987.6 762
38.88/ 30.00/
987.6 762
38.88/ 30.00/
987.6 762
38.88/ 30.00/
987.6 762

Enclosures and Junction Boxes

A
20.69/
525.5
20.69/
525.5
20.69/
525.5
20.69/
525.5
15.19/
385.8
15.19/
385.8
15.19/
385.8
21.19/
538.2
21.19/
538.2
21.19/
538.2
21.19/
538.2
21.19/
538.2
27.19/
690.6
27.19/
690.6
27.19/
690.6
27.19/
690.6
15.19/
385.8
15.19/
385.8
27.25/
692.2
27.25/
692.2
27.25/
692.2
27.25/
692.2
21.25/
539.8
21.25/
539.8
21.25/
539.8
21.25/
539.8
39.00/
990.6
39.00/
990.6
39.00/
990.6
39.00/
990.6

Overall Enclosure
B
C
20.69/ 6.63/
525.5 168.4
20.69/ 8.63/
525.5 219.2
20.69/ 10.63/
525.5
270
20.69/ 1.63/
525.5 41.4
27.19/ 6.63/
690.6 168.4
27.19/ 8.63/
690.6 219.2
27.19/ 12.63/
690.6 320.8
27.19/ 6.72/
690.6 170.7
27.19/ 8.72/
690.6 221.5
27.19/ 10.72/
690.6 272.3
27.19/ 12.72/
690.6 323.1
27.19/ 18.72/
690.6 475.5
27.19/ 6.72/
690.6 170.7
27.19/ 8.72/
690.6 221.5
27.19/ 10.75/
690.6 273.1
27.19/ 1.75/
690.6 44.5
31.19/ 12.69/
792.2 322.3
31.19/ 12.69/
792.2 322.3
33.25/ 8.75/
844.6 222.3
33.25/ 10.75/
844.6 273.1
33.25/ 12.75/
844.6 323.9
33.25/ 18.75/
844.6 476.3
39.25/ 6.75/
997
171.5
39.25/ 8.75/
997
222.3
39.25/ 12.75/
997
323.9
39.25/ 18.75/
997
476.3
39.00/ 8.88/
990.6 225.6
39.00/ 10.88/
990.6 276.4
39.00/ 12.88/
990.6 327.2
39.00/ 18.88/
990.6 479.6

XP Series Junction Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof
Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2, Groups IIC, IIB + H2
Class II, Division 1 and 2, Groups E, F, G
Class III
CSA Enclosure Type 3R
EMR Canada

Applications
•	 Protection and control of electrical apparatus in hazardous
environments, either indoors or outdoors.
•	 Designed for Class I, Zone I areas where flammable gases or
vapors are present either continuously or intermittently or under
abnormal circumstances.
•	 Used as a junction, splice or pull box.
•	 Ideal where number and size or conductors require a large
volume enclosure.

Features
•	 Removable hinged cover gives unobstructed access to
enclosure.
•	 Installation is easy with keyhole mounting lugs to simplify
mounting.

Standard Materials
•	 Enclosure and cover: copperfree (4/10 of 1% max) aluminum
•	 Cover bolts and fasteners: stainless steel

Standard Finishes
•	 Gray baked epoxy

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Options and Accessories
•	
•	
•	
•	
•	
•	
•	

Breather and drain, add suffix -B.
Ferrous alloy, add suffix -F.
Mounting pan, add suffix -P.
Quad lead cover bolts, add suffix -QB.
Right hand hinge, add suffix -RH.
Enclosure Type 4X, add suffix -4X.
For custom terminal blocks, windows and operator controls,
contact your local representative.

Certifications and Compliances
•	 CSA Standard: C22.2 No. 25, C22.2 No. 30
•	 CSA Certified: 013017

Related Products
•	 For control panels, see Distribution Equipment section.

V CSA Certification Only.

620

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

XP Series Junction Boxes V

CSA Certification Only. Explosionproof, Dust-Ignitionproof
Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2, Groups IIC, IIB + H2
Class II, Division 1 and 2, Groups E, F, G
Class III
CSA Enclosure Type 3R
EMR Canada

Enclosure
Type

W

Inside in Inches/Millimeters
L

H

Aluminum
Weight Lb/Kg

Catalog
Number

XPA

20.00/508

12.01/305

5.00/127

79/36

XP201205

XPA

20.00/508

12.01/305

7.99/203

93/42

XP201208

XPB

28.00/711

12.01/305

5.00/127

97/44

XP281205

XPB

28.00/711

12.01/305

7.99/203

119/54

XP281208

XPC

36.97/939

12.01/305

5.00/127

148/67

XP371205

XPC

36.97/939

12.01/305

7.99/203

176/80

XP371208

XPE

42.01/1067

15.98/406

5.00/127

227/103

XP421605

Dimensions in Inches/Millimeters

Enclosures and Junction Boxes

Conduit Area
Flat Surface

Inside

Size

A

B

C1

C2

D

E

F1

F2

H

J

XPA

15.5/400

23.5/600

7.62/190

10.5/270

11.81/300

10.63/270

5.12/130

7.87/200

18.11/460

2.99/76
2.99/76

XPB

15.5/400

31.5/800

7.62/190

10.5/270

11.81/300

27.95/710

5.12/130

7.87/200

25.98/660

XPC

15.5/400

40.5/1030

7.62/190

10.5/270

11.81/300

37.01/940

5.12/130

7.87/200

35.04/890

2.99/76

XPE

19.5/500

45.5/1150

7.62/190

—­

16.14/410 42.13/1070

5.12/130

­­­—

40.16/1020

2.99/76

V CSA Certification Only.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

621

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosure
Outside

XP Series Junction Box Drilling and Tapping V
CSA Certification Only. Explosionproof, Dust-Ignitionproof
Class I, Division 1 and 2, Groups B, C, D
Class I, Zone 1 and 2, Groups IIC, IIB + H2
Class II, Division 1 and 2, Groups E, F, G
Class III
CSA Enclosure Type 3R
EMR Canada

Instructions for conduit entries
To specify your drilling and tapping requirements for the junction boxes:
1. Choose the letter to indicate the size of desired conduit entry (Table 1).
2. Select the number to specify the location of conduit opening (Table 2).
3. Add the combined letter and number to the end of the junction box catalog number: Example: XP201208-C6-D8-A18.
Notes:
1. Be sure to indicate the spacing requirements, otherwise holes will be centred and evenly spaced.
2. Specific conduit openings must be located from the box centerline and from outside mounting surface of the box to the conduit centerline.
Table 1— Drilling and Tapping for Conduit

Enclosures and Junction Boxes: Hazardous Junction Boxes

Enclosures and Junction Boxes

Outlet Conduit
Code Size (In)

4

3-1/2

3

Minimum Spacing for Conduit Centres in Inches/Millimeters
2-1/2
2
1-1/2
1-1/4

1

3/4

A

1/2

4.50/114.3 4.25/108.0 4.00/101.6 3.63/92.1

3.13/79.4

2.81/71.4

2.63/66.7

2.25/57.2

2.13/54.0

B

3/4

4.50/114.3 4.25/108.0 4.00/101.6 3.63/92.2

3.13/79.4

2.81/71.4

2.63/66.7

2.25/57.2

2.13/54.0

C

1

4.88/123.8 4.50/114.3 4.13/104.8 3.75/95.3

3.25/82.6

3.00/76.2

2.81/71.4

2.38/60.3

D

1-1/4 5.00/127.0 4.75/120.7 4.50/114.3 4.13/104.8 3.63/92.2

3.31/84.1

3.13/79.4

E

1-1/2 5.25/133.4 4.94/125.4 4.63/117.5 4.31/109.5 3.81/96.8

3.25/82.6

F
G

2

1/2
2.13/54.0

5.75/146.1 5.38/136.5 5.00/127.0 4.63/117.5 4.13/104.8

2-1/2 6.13/155.6 5.75/146.1 5.31/134.9 5.13/130.2

H

3

6.25/158.8 6.0/152.4

5.75/146.1

Conduit
Size
(Inches)

Number of threads
per inch

Min. Wall Thickness
for 5 thread engagement
in Inches/Millimeters

1/2 and 3/4

14

0.375/9.525

1-2

11-1/2

0.4375/11.1125

2-1/2 - 4

8

0.625/15.875

Table 2 — Spacing and Location of Conduit Entries

Conduit Entry Limitations
Maximum Conduit Size
Ends

3” NPT

Sides

2” NPT

V CSA Certification Only.

622

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

W Series Cast Junction Box Options

Boxes Available for Raintight, Watertight, or Submersible Applications

This table shows the optional items available on the different types of enclosures shown in this section. When not furnished as standard
equipment the cost must be added to the base price of the box.
Lettering on Covers can be furnished. These are usually engraved letters and can be applied to the cover of any type box.

Options *

Slip Holes
Drill & Tap Holes
Bosses Only
Drilled & Tapped Boss
Mtg. Lugs
Mtg. Buttons
Mtg. Plates*
Hinges
Drain & Breather
Hasp (for padlock)

WYS







NA

NA

WYL







NA

NA

WYF







NA

NA

The following information should be given on all box orders:

Type of Enclosure
WYU
WYR














NA

NA

NA


WYT







NA
NA
NA

WY58E
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

WYC







S
NA
NA

WYNY
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA

sizes. If more threads are required, please order a Bossed, Drilled
and Tapped hole.
Bossed Drilled and Tapped Holes — These are holes threaded
through the box wall and a boss (or pad) which has been added
at the location of the conduit entrance to provide added wall
thickness for additional thread engagement (5 threads standard).
Mounting Lugs — Provided on all surface mounted boxes over 100
in3 /1.6dm3 of internal volume to meet NEC Section 314.23(E).
Boxes 100 in3 /1.6dm3 or less may be supported by two or more
conduits threaded into the enclosure, or by optional mounting
lugs. All mounting lugs will be located on the long sides of the
box, unless otherwise specified. Refer to following pages for
dimensional data.
Mounting Buttons — For mounting equipment off the back of
the box; can be furnished located on standard centers and
blind D and T for 1∕4” - 20 screws. If special mounting button
arrangement is required, furnish a sketch showing layout
including the size of the mounting screws. Please use the drilling
template provided on following pages.
Covers — Other than standard, must be specified if required.

XXXX

CAST-IN OR ENGRAVED LETTERS

SLIP HOLE - ASH
BOSSED, DRILLED AND
TAPPED HOLE - ABDT

DRILLED AND TAPPED HOLE - ADT

MOUNTING BUTTONS - A-MBT
MOUNTING LUGS - A-ML

Wall Thickness and Maximum Conduit Size
Conduit Size
Number of
Inches
Threads Per Inch
3∕8
18
1∕2 to 3∕4
14
1 to 2
11-1∕2
2-1∕2 to 4
8

Wall Thickness Required in/mm
3-1∕2 Threads
5 Threads
0.28/7.1
0.88∕22.2 ‡
0.25/6.4
0.38/9.5
0.31/7.9
0.44/11.1
0.44/11.1
0.63/15.9

‡ 1∕4” minimum wall thickness must be provided.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

623

Enclosures and Junction Boxes

Catalog Number and Inside Dimensions — (L x W x D) should be
specified.
Sketch — Show size and location of conduit entrances in sketch
similar to Drilling Template, Fig. 2. Tables on following pages give
recommended spacing between conduits and minimum distance
from corner and back of box. When spacings are not specified,
they will be located at our discretion.
Slip Holes — These are clearance holes for conduit. No threads
provided. Conduits are usually fastened in slip holes by means
of locknuts and bushings. Standard locknut spacings must be
allowed between the conduits.
Drilled and Tapped Holes — These are threaded holes provided
in the enclosure wall into which the conduit is screwed. To meet
UL requirements, they must conform to the following:
•	 Enclosures for use in Non-hazardous Locations must have a wall
thickness of not less than 1/4” at the tapped holes for the conduit
and there shall not be less than 3-1/2 threads in the metal.
•	 Compare the wall thickness shown in the listing of these
enclosures with the chart at right to determine the number of
threads which the box wall will provide for the various conduit

WYW







S



Enclosures and Junction Boxes: Ordinary Location Junction Boxes

 – Available option at additional charge.
S – Furnished as standard equipment at no additional charge
NA – Not permitted on this type of enclosure by NEMA and Underwriters Laboratories, Inc. standards and specifications, or basic construction of box will not
allow or require this item.
* See ordering details on Options and Ordering Information pages.

W Series Cast Junction Box Options

Boxes Available for Raintight, Watertight, or Submersible Applications

Drilling and Tapping

Combination Drain and Breather Fittings

Applies to: Types WYS, WYL, WYF, WYW-T, WYT, WYC, WYU, WYR.

D and T and installation included.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Catalog Number
Conduit
Size
Inches
3∕8

Boss for 4
Threads and
Tapping
ABDT-38

Size (Inches)
3∕8

Catalog Number
AMDB-38

1∕2

AMDB-50

Drilling Only
Slip Hole
ASH-38

Drilling &
Tapping
No Boss
ADT-38

Boss Only 5
Threads
without Hole
ABWH-38

1∕2

ASH-50

ADT-50

ABWH-50

ABDT-50

3∕4

ASH-75

ADT-75

ABWH-75

ABDT-75

Quantity Per Box
1

Catalog Number
A1-MBT

Interior Mounting Buttons

1

ASH-100

ADT-100

ABWH-100

ABDT-100

2

A2-MBT

1-1∕4

ASH-125

ADT-125

ABWH-125

ABDT-125

3

A3-MBT

1-1∕2

ASH-150

ADT-150

ABWH-150

ABDT-150

4

A4-MBT

2

ASH-200

ADT-200

ABWH-200

ABDT-200

2-1∕2

ASH-250

ADT-250

ABWH-250

ABDT-250

3

ASH-300

ADT-300

ABWH-300

ABDT-300

3-1∕2

ASH-350

ADT-350

ABWH-350

ABDT-350

4

ASH-400

ADT-400

ABWH-400

ABDT-400

Wire Capacity
Al-Cu Tinned Copper
#14-4 AWG

Catalog Number
AGK-04

4-1∕2

ASH-450

ADT-450

ABWH-450

ABDT-450

8-1/0 AWG

AGK-10

5

ASH-500

ADT-500

ABWH-500

ABDT-500

6 AWG-250kcmil

AGK-25

6

ASH-600

ADT-600

ABWH-600

ABDT-600

Grounding Kits

Hinges
Type
Stainless Steel

Box Size in Inches/Millimeters
Up to 12 x 12/304.8 x 304.8

Number of Hinges Per Set
2

Catalog Number
AHNG-22SS

Butt Type

Up to 18 x 18/457.2 x 457.2

2

AHNG-23SS

For WYU Boxes

Larger than 18 x 18/457.2 x 457.2

3

AHNG-33SS

Hasps

Letters Engraved on Box Covers

Hot dip galvanized steel (lock not Included).

Box Size in Inches/Millimeters
Up to 12” x 12” / 304.8 x 304.8
Larger than 12” x 12”/ 304.8 x 304.8

Catalog Number
AHSP-13SG
AHSP-15SG

Description
Up to 10 letters, one line
Up to 20 letters, two lines

Catalog Number
Engraved
Raised
AENGRAVE-1 ARAISED-1
AENGRAVE-2 ARAISED-2

Optional Mounting Lugs with Bolt Holes †
Maximum Box Size — L x W in in/mm
Sizes up to 6” x 4”/
152.4 x 101.6
Sizes 6” x 6” to 12” x 4”/
152.4 x 152.4 up to 304.8 x 101.6
Sizes 12” x 6” up to 18” x 16”
304.8 x 152.4 up to 457.2 x 406.4
Sizes 18” x 18” and larger/
457.2 x 457.2 and larger

No. of Lugs
2
4
2
4
2

Catalog
Number
A2-ML-0604
A4-ML-0604
A2-ML-1204
A4-ML-1204
A2-ML-1816

4

A4-ML-1816

4

A4-ML-3636

† Mounting lugs are standard equipment on surface mounted boxes over 100 in3/1.6 dm3 of internal volume at no additional charge.

624

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

W Series Cast Junction Box Ordering Information

Boxes Available for Raintight, Watertight, or Submersible Applications

Minimum Recommended Spacing Between Conduit Openings
Allowance made for clearance over locknuts and bushings.

When unions are used, additional space must be allowed. Table shows minimum distances between conduit opening centerlines in various
size combinations. For example, if 1-1/2” and 3/4” openings are to be drilled and tapped into one side of box, the minimum spacing between
centerlines would be 2.13"/54.1mm.

Size of
Conduit

3-1/2

3

2-1/2

2

1-1/2

1-1/4

1

3/4

1/2

1/2

3.63/
92.2

3.38/
85.9

3.00/
76.2

2.63/
66.8

2.38/
60.5

2.00/
50.8

1.88/
47.8

1.75/
44.5

1.63/
41.4

1.50/
38.1

3/4

3.75/
95.3

3.50/
88.9

3.13/
79.5

2.75/
69.9

2.50/
63.5

2.13/
54.1

2.00/
50.8

1.88/
47.8

1.75/
44.5

1

4.00/
101.6

3.63/
92.2

3.25/
82.6

3.00/
76.2

2.63/
66.8

2.38/
60.5

2.25/
57.2

2.00/
50.8

1-1/4

4.13/
104.9

3.88/
98.6

3.50/
88.9

3.13/
79.5

2.88/
73.2

2.50/
63.5

2.38/
60.5

1-1/2

4.25/
108.0

4.00/
101.6

3.63/
92.2

3.25/
82.6

3.00/
76.2

2.63/
66.8

2

4.63/
117.6

4.25/
108.0

3.88/
98.6

3.63/
92.2

3.25/
82.6

2-1/2

4.88/
124.0

4.63/
117.6

4.25/
108.0

3.88/
98.6

3

5.38/
136.7

5.00/
101.6

4.63/
117.6

3-1/2

5.63/
143.0

5.25/
133.4

4

5.88/
149.4

Locknut Diameter

1.13/
28.7

1.38/
35.1

1.75/
44.5

2.25/
57.2

2.56/
65.0

3.19/
81.0

3.50/
88.9

4.19/
106.4

4.75/
120.7

5.38/
136.7

BBU Bushing Diameter

1.06/
26.9

1.31/
33.3

1.56/
39.6

1.94/
49.3

2.19/
55.6

2.69/
68.3

3.19/
81.0

3.88/
98.6

4.38/
111.3

4.88/
124.0

BU Bushing Diameter

1.13/
28.7

1.25/
31.8

1.63/
41.4

2.06/
52.3

2.31/
58.7

2.94/
74.7

3.25/
82.3

3.88/
98.6

4.56/
115.8

5.06/
128.5

UNY/UNF® Union

1.50/
38.1

1.75/
44.5

2.00/
50.8

2.81/
71.4

3.06/
77.7

3.75/
95.3

4.94/
125.5

5.44/
138.2

5.94/
150.9

6.50/
165.1

Conduit Diameter

0.88/
22.4

1.06/
26.9

1.38/
35.1

1.69/
42.9

1.94/
49.3

2.38/
60.5

2.88/
73.2

3.50/
88.9

4.00/
101.6

4.50/
114.3

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

625

Enclosures and Junction Boxes

4

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Space Between Centers of Conduit Inches/Millimeters

W Series Cast Junction Box Ordering Information

Boxes Available for Raintight, Watertight, or Submersible Applications

Figure 2
Drilling template on page following page can be copied and used
to transmit information regarding conduit entries, mounting lugs,
mounting plates, or any other options or specifications. The view
is looking into the box with sides laid down. Doors are hinged on
the right side, when required, which is the length, when no other
instructions are given. Unless otherwise specified, all openings
will be located in centerline of walls and evenly spaced.

Width “W”
12”

Enclosures and Junction Boxes

(1) 11/2” D & T
with Boss

Top

31/4”

CL
1 3 /4 ”

15/8”
2”

3”

When optional Mounting Buttons are ordered, dimensions
for spacing MUST be given, otherwise will be spaced per our
discretion.

11/2”
1 1 /2 ”

Back
CL

18”

Length “L”

8”

(4) Mounting Buttons
Tapped Blind For
1
/4 — 20 UNC - 2B

4”

Left

Side

Right

1 5 /8 ”

CL

Side

13/4” CL
CL

6”

Depth “D”

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

(2) 2” D & T
with Boss

(2) 2” Slip
Holes

31/4”

Bottom
CL

Minimum Allowable Spacing from Back and Sides
Allowance made for clearance over locknuts and bushings.

Types WYS, WYL,
WYW, WYT and WYC

Types WYF, WYR,
WYU and WY58E

Conduit
Size

1/2”

3/4”

1”

1-1/4”

1-1/2”

2”

2-1/2”

3”

3-1/2”

4”

Dimension A
in/mm

1.25/
31.8

1.38/
35.1

1.63/
41.4

1.88/
47.8

2.00/
50.8

2.38/
60.5

2.63/
66.8

3.00/
76.2

3.25/
82.6

3.63/
92.2

Dimension B
in/mm

1.00/
25.4

1.00/
25.4

1.13/
28.7

1.38/
35.1

1.50/
38.1

1.75/
44.5

2.13/
54.1

2.50/
63.5

2.88/
73.2

3.13/
79.5

626

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

W Series Cast Junction Box Drilling Template
Boxes Available for Raintight, Watertight, or Submersible Applications

For copier reproduction or computer scanning. Please send to your local representative for quotation or order confirmation.

Company Name
Shipping Address
Distributor

Account Number

Purchase Order No.

Part Number

Purchase Order Date

Quantity

Internal Order No.

Req No.

Mark Box

Additional
Specifications

Customer Signature

Drawing No.

Gasket Data
Neoprene

Yes

No





Drilling Data *
Slip-Hole Only

Yes

No

Drilled and Tapped







Drilled and Tapped
with Boss



Boss Only



Mounting Lug Data
Required

Yes

No

Standard Spacing









Special Spacing:
Locate on Templete







Boss Only





If X and K dimensions are not indicated, factory will locate.
Dim X = Distance from centerline to center of conduit opening.
Dim K = Distance from mounting surface to center of conduit opening.
Check which type of entry is required: bossed drill and tap or slip hole.

Looking into Box — Sides Laid Down

Looking Cover

All dimensions are from INSIDE of box.

CL

CL

Back
of
Box

C
L

C
L

C
L

C
L

C
L

Cover
of
Box

C
L

Cover
of
Box

C
L

Length

Back
of
Box

C
L

Width

Length

CL

Width

Right Side

Left Side

C
L

Right Side

Depth

CL

CL

Depth

Left Side

Depth

CL

Top

Enclosures and Junction Boxes

Depth

Top

All dimensions are from INSIDE of box.

C
L
K

K

X

X

Bottom

Bottom

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Print Name

627

W Series Cast Box Mounting Lug Data

Boxes Available for Raintight, Watertight, or Submersible Applications

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

For Cast Iron and Cast Aluminum Boxes.

The dimensions listed in these tables are approximate and may vary as much as 0.25”/6.4 mm in any direction. If closer tolerances are required or if other
locations of the mounting lugs are desired, specify on the order or drawing.

Types WYS, WYL, WYW, WYU, and WYW-T
Box Size in
Inches/Millimeters
L
x
W
4.00/101.6
5.00/127.0
6.00/152.4
6.00/152.4
7.00/177.8
8.00/203.2
8.00/203.2
8.00/203.2
9.00/228.6
10.00/254.0
10.00/254.0
10.00/254.0
10.00/254.0
10.00/254.0
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
14.00/355.6
14.00/355.6
14.00/355.6
15.00/381.0
15.00/381.0
15.00/381.0
15.00/381.0
16.00/406.4
16.00/406.4

628

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

4.00/101.6
5.00/127.0
4.00/101.6
6.00/152.4
5.00/127.0
4.00/101.6
6.00/152.4
8.00/203.2
6.00/152.4
4.00/101.6
5.00/127.0
6.00/152.4
8.00/203.2
10.00/254.0
4.00/101.6
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
8.00/203.2
10.00/254.0
14.00/355.6
6.00/152.4
8.00/203.2
9.00/228.6
10.00/254.0
4.00/101.6
10.00/254.0

Dimension in
Inches/Millimeters
A
B
3.00/76.2
4.00/101.6
5.00/127.0
4.00/101.6
5.00/127.0
5.00/127.0
5.00/127.0
5.00/127.0
6.00/152.4
7.00/177.8
7.00/177.8
7.00/177.8
7.00/177.8
7.00/177.8
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
10.00/254.0
10.00/254.0
10.00/254.0
11.00/279.4
11.00/279.4
11.00/279.4
11.00/279.4
12.00/304.8
12.00/304.8

5.38/136.7
6.50/165.1
5.38/136.7
7.63/193.8
6.50/165.1
5.63/143.0
7.63/193.8
9.75/247.7
7.63/193.8
5.63/143.0
6.63/168.4
7.75/196.9
9.75/247.7
11.75/298.5
5.63/143.0
8.50/215.9
10.50/266.7
12.50/317.5
14.50/368.3
10.50/266.7
12.50/317.5
16.50/419.1
8.38/212.9
10.63/270.0
11.50/292.1
12.50/317.5
6.50/165.1
12.50/317.5

Types WYS, WYL, WYW, WYU, and WYW-T
Bolt Hole
Diameter
in/mm
D
0.31/7.9
0.31/7.9
0.31/7.9
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2

Box Size in
Inches/Millimeters
L
x
W
16.00/406.4
16.00/406.4
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
20.00/508.0
20.00/508.0
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
24.00/609.6
28.00/711.2
30.00/762.0
30.00/762.0
30.00/762.0
34.00/863.6
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4
36.00/914.4
48.00/1219.2

x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Dimension in
Inches/Millimeters
A
B

12.00/304.8 12.00/304.8
16.00/406.4 12.00/304.8
6.00/152.4 13.00/330.2
8.00/203.2 13.00/330.2
12.00/304.8 13.00/330.2
14.00/355.6 13.00/330.2
16.00/406.4 13.00/330.2
18.00/457.2 13.00/330.2
10.00/254.0 15.00/381.0
20.00/508.0 15.00/381.0
8.00/203.2 19.00/482.6
12.00/304.8 19.00/482.6
16.00/406.4 19.00/482.6
18.00/457.2 19.00/482.6
20.00/508.0 19.00/482.6
24.00/609.6 19.00/482.6
12.00/304.8 22.00/558.8
8.00/203.2 24.00/609.6
18.00/457.2 24.00/609.6
24.00/609.6 24.00/609.6
30.00/762.0 28.00/711.2
6.00/152.4 30.00/762.0
12.00/304.8 30.00/762.0
18.00/457.2 30.00/762.0
24.00/609.6 30.00/762.0
30.00/762.0 30.00/762.0
36.00/914.4 30.00/762.0
6.00/152.4 42.00/1066.8

14.50/368.3
18.50/469.9
8.50/215.9
10.50/266.7
14.50/368.3
16.63/422.4
18.63/473.2
20.88/530.4
12.63/320.8
22.63/574.8
10.75/273.1
14.75/374.7
18.75/476.3
20.75/527.1
22.75/577.9
26.88/682.8
14.88/378.0
10.75/273.1
21.00/533.4
14.88/378.0
32.88/835.2
8.63/219.2
14.88/378.0
21.00/533.4
26.88/682.8
32.88/835.2
38.88/987.6
8.63/219.2

Bolt Hole
Diameter
in in/mm
D
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.56/14.2
0.56/14.2
0.56/14.2
0.28/7.1
0.28/7.1
0.28/7.1
0.28/7.1
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

W Series Cast Box Mounting Lug Data

Boxes Available for Raintight, Watertight, or Submersible Applications
For Cast Iron and Cast Aluminum Boxes.

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

The dimensions listed in these tables are approximate and may vary as much
as 0.25”/6.4 mm in any direction. If closer tolerances are required or if other
locations of the mounting lugs are desired, specify on the order or drawing.

Types WYF and WYR
Box Size in
Inches/Millimeters
L
x
W
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

4.00/101.6
5.00/127.0
4.00/101.6
6.00/152.4
4.00/101.6
6.00/152.4
8.00/203.2
6.00/152.4
8.00/203.2
10.00/254.0
4.00/101.6
6.00/152.4
8.00/203.2
10.00/254.0
12.00/304.8
8.00/203.2
14.00/355.6
12.00/304.8
16.00/406.4
6.00/152.4
8.00/203.2
12.00/304.8
18.00/457.2
12.00/304.8
18.00/457.2
24.00/609.6
12.00/304.8
24.00/609.6
18.00/457.2
24.00/609.6
36.00/914.4

3.00/76.2
4.00/101.6
5.00/127.0
4.00/101.6
5.00/127.0
5.00/127.0
5.00/127.0
7.00/177.8
7.00/177.8
7.00/177.8
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
8.00/203.2
10.00/254.0
10.00/254.0
12.00/304.8
12.00/304.8
13.00/330.2
13.00/330.2
13.00/330.2
13.00/330.2
19.00/482.6
19.00/482.6
19.00/482.6
22.00/558.8
24.00/609.6
30.00/762.0
30.00/762.0
30.00/762.0

5.38/136.7
6.38/162.1
5.38/136.7
7.50/190.5
5.50/139.7
7.63/193.8
9.63/244.6
7.63/193.8
9.75/247.7
11.63/295.4
5.63/143.0
8.38/212.9
10.38/263.7
12.38/314.5
14.38/365.3
10.38/263.7
16.50/419.1
14.50/368.3
18.50/469.9
8.50/215.9
10.50/266.7
14.38/365.3
20.63/524.0
14.63/371.6
20.63/524.0
26.88/682.8
14.75/374.7
26.88/682.8
20.88/530.4
26.88/682.8
38.88/987.6

Bolt Hole
Diameter
in in/mm
D
0.31/7.9
0.31/7.9
0.31/7.9
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.38/9.7
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.44/11.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2
0.56/14.2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes

4.00/101.6
5.00/127.0
6.00/152.4
6.00/152.4
8.00/203.2
8.00/203.2
8.00/203.2
10.00/254.0
10.00/254.0
10.00/254.0
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
12.00/304.8
14.00/355.6
14.00/355.6
16.00/406.4
16.00/406.4
18.00/457.2
18.00/457.2
18.00/457.2
18.00/457.2
24.00/609.6
24.00/609.6
24.00/609.6
28.00/711.2
30.00/762.0
36.00/914.4
36.00/914.4
36.00/914.4

Dimension in
Inches/Millimeters
A
B

629

W Series Junction Box Mounting Plate Information

Boxes Available for Raintight, Watertight, or Submersible Applications
For Cast Iron and Cast Aluminum Boxes.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Mounting plates are used for mounting equipment up off the back of an enclosure. Steel Plates
are all 0.13”/3.3mm thick hot dip galvanized material. Aluminum plates are 0.13”/3.3 mm thick
material up to and including 12 x 12” / 304.8 x 304.8 mm size. All larger sizes are constructed of
0.19”/4.8mm thick aluminum plate.
Select mounting plates based on inside length and width of box. Order as a separate item
immediately following the catalog number of the box as follows:
Example: 	Line 1	
WYS-080804
	
Line 2	
WYM-0808-2
For mounting plates in smaller boxes than listed, use similar catalog number logic. Example:
A steel mounting plate for a WYF-040403 box would be WYM-0404-1. Pricing will be based
upon a WYM-0808-1 price.
The catalog numbers shown in the table below include the mounting buttons.
Inside Length &
Width of Junction
Box in in/mm
8 x 8/
203.2 x 203.2

10 x 8/
254.0 x 203.2

10 x 10/
254.0 x 254.0

12 x 8/
304.8 x 203.2

12 x 10/
304.8 x 254.0

12 x 12/
304.8 x 304.8

14 x 8
355.6 x 203.2

14 x 14/
355.6 x 355.6

16 x 8/
406.4 x 203.2

630

Catalog Number – Steel Plates
For use in Types
For use in Types
WYF & WYR
WYS, WYL & WYW
Junction Boxes
Junction Boxes

Catalog Number – Aluminum Plates
For use in Types
For use in Types
WYF & WYR
WYS, WYL & WYW
Junction Boxes
Junction Boxes

WYM-0808-1

WYM-0808-1A

Dimension in Inches/Millimeters
Style
1

WYM-0808-2
WYM-1008-1

WYM-0808-2A
WYM-1008-1A
1

WYM-1008-2
WYM-1010-1

WYM-1008-2A
WYM-1010-1A
1

WYM-1010-2
WYM-1208-1

WYM-1010-2A
WYM-1208-1A
1

WYM-1208-2
WYM-1210-1

WYM-1208-2A
WYM-1210-1A
1

WYM-1210-2
WYM-1212-1

WYM-1210-2A
WYM-1212-1A
1

WYM-1212-2
WYM-1408-1

WYM-1212-2A
WYM-1408-1A
1

WYM-1408-2
WYM-1414-1

WYM-1408-2A
WYM-1414-1A
1

WYM-1414-2
WYM-1608-1

WYM-1414-2A
WYM-1608-1A
1

WYM-1608-2

WYM-1608-2A

L
6.75/
171.5
6.00/
152.4
8.75/
222.3
8.00/
203.2
8.75/
222.3
8.00/
203.2
10.75/
273.1
10.00/
254.0
10.75/
273.1
10.00/
254.0
10.75/
273.1
10.00/
254.0
12.75/
323.9
12.00/
304.8
12.75/
323.9
12.00/
304.8
14.75/
374.7
12.00/
304.8

W
6.75/
171.5
6.00/
152.4
6.75/
171.5
6.00/
152.4
8.75/
222.3
8.00/
203.2
6.75/
171.5
6.00/
152.4
8.75/
222.3
8.00/
203.2
10.75/
273.1
10.00/
254.0
6.75/
171.5
6.00/
152.4
12.75/
323.9
12.00/
304.8
6.75/
171.5
6.00/
152.4

A
6.00/
152.4
5.25/
133.4
8.00/
203.2
7.25/
184.2
8.00/
203.2
7.25/
184.2
10.00/
254.0
9.25/
235.0
10.00/
254.0
9.25/
235.0
10.00/
254.0
9.25/
235.0
12.00/
304.8
11.25/
285.5
12.00/
304.8
11.25/
285.5
14.00/
355.6
11.25/
285.5

B
6.00/
152.4
5.25/
133.4
8.00/
203.2
5.25/
133.4
8.00/
203.2
7.25/
184.2
6.00/
152.4
5.25/
133.4
8.00/
203.2
5.25/
133.4
10.00/
254.0
9.25/
235.0
6.00/
152.4
5.25/
133.4
12.00/
304.8
11.25/
285.5
6.00/
152.4
5.25/
133.4

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

W Series Junction Box Mounting Plate Information

Boxes Available for Raintight, Watertight, or Submersible Applications
For Cast Iron and Cast Aluminum Boxes. Continued from preceding page.

Mounting plates are used for mounting equipment up off the back of an enclosure. Steel Plates
are all 0.13”/3.3mm thick hot dip galvanized material. Aluminum plates are 0.13”/3.3 mm thick
material up to and including 12 x 12” / 304.8 x 304.8 mm size. All larger sizes are constructed of
0.19”/4.8mm thick aluminum plate.

For mounting plates in smaller boxes than listed, use similar catalog number logic. Example:
A steel mounting plate for a WYF-040403 box would be WYM-0404-1. Pricing will be based
upon a WYM-0808-1 price.
The catalog numbers shown in the table below include the mounting buttons.
Inside Length &
Width of Junction
Box in in/mm
16 x 12/
406.4 x 304.8

16 x 16/
406.4 x 406.4

18 x 8/
457.2 x 203.2

18 x 12/
457.2 x 304.8

18 x 14/
457.2 x 355.6
18 x 16/
457.2 x 406.4
18 x 18/
457.2 x 457.2

20 x 10/
508.0 x 254.0

Catalog Number – Aluminum Plates
For use in Types
For use in Types
WYF & WYR
WYS, WYL & WYW
Junction Boxes
Junction Boxes

WYM-1612-1

WYM-1612-1A

Dimension in Inches/Millimeters
Style
1

WYM-1612-2
WYM-1616-1

WYM-1612-2A
WYM-1616-1A
1

WYM-1616-2
WYM-1808-1

WYM-1616-2A
WYM-1808-1A
1

WYM-1808-2
WYM-1810-1

WYM-1808-2A
WYM-1810-1A
1

WYM-1810-2
WYM-1812-1

WYM-1818-2A
WYM-1812-1A
1

WYM-1812-2
WYM-1814-1

WYM-1812-2A
WYM-1814-1A
1

WYM-1814-2

WYM-1814-2A

—

—
WYM-1816-2

WYM-1818-1

WYM-1816-2A

1

WYM-1818-1A
1
WYM-1818-2

WYM-2010-1

WYM-1818-2A
WYM-2010-1A
1

WYM-2020-2

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYM-2020-2A

L
14.75/
374.7
14.00/
355.6
14.75/
374.7
14.00/
355.6
16.75/
171.5
16.00/
152.4
16.75/
171.5
16.00/
152.4
16.75/
171.5
16.00/
152.4
16.75/
171.5
16.00/
152.4
—
16.00/
152.4
16.75/
171.5
16.00/
152.4
18.75/
222.3
18.00/
203.2

W
10.75/
273.1
10.00/
254.0
14.75/
374.7
14.00/
355.6
6.75/
171.5
6.00/
152.4
8.75/
222.3
8.00/
203.2
10.75/
273.1
10.00/
254.0
12.75/
323.9
12.00/
304.8
—
14.00/
355.6
16.75/
171.5
16.00/
152.4
8.75/
222.3
8.00/
203.2

A
14.00/
355.6
13.25/
336.6
14.00/
355.6
13.25/
336.6
16.00/
152.4
15.25/
133.4
16.00/
152.4
15.25/
133.4
16.00/
152.4
15.25/
133.4
16.00/
152.4
15.25/
133.4
—
15.25/
133.4
16.00/
152.4
15.25/
133.4
18.00/
203.2
17.25/
184.2

B
10.00/
254.0
9.25/
235.0
14.00/
355.6
13.25/
336.6
6.00/
152.4
5.25/
133.4
8.00/
203.2
7.25/
184.2
10.00/
254.0
9.25/
235.0
12.00/
304.8
11.25/
285.5
—
13.25/
336.6
16.00/
152.4
15.25/
133.4
8.00/
203.2
7.25/
184.2

631

Enclosures and Junction Boxes

18 x 10/
457.2 x 254.0

Catalog Number – Steel Plates
For use in Types
For use in Types
WYF & WYR
WYS, WYL & WYW
Junction Boxes
Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Select mounting plates based on inside length and width of box. Order as a separate item
immediately following the catalog number of the box as follows:
Example: 	Line 1	
WYS-080804
	
Line 2	
WYM-0808-2

W Series Junction Box Mounting Plate Information

Boxes Available for Raintight, Watertight, or Submersible Applications
For Cast Iron and Cast Aluminum Boxes. Continued from preceding page.

Mounting plates are used for mounting equipment up off the back of an enclosure.
Steel Plates are all 0.13”/3.3mm thick hot dip galvanized material. Aluminum plates
are 0.13”/3.3mm thick material up to and including 12 x 12” / 304.8 x 304.8 mm size.
All larger sizes are constructed of 0.19”/4.8mm thick aluminum plate.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Select mounting plates based on inside length and width of box. Order as a
separate item immediately following the Catalog Number of the box as follows:
Example:
WYS-080804

WYM-0808-2

The catalog numbers shown in the table below include the mounting buttons.

Inside Length &
Width of Junction
Box in in/mm

Catalog Number – Steel Plates
For use in Types
For use in Types
WYF & WYR
WYS, WYL & WYW
Junction Boxes
Junction Boxes

Catalog Number – Aluminum Plates
For use in Types
For use in Types
WYF & WYR
WYS, WYL & WYW
Junction Boxes
Junction Boxes

Dimension in Inches/Millimeters
Style

L

W

A

B

WYM-2412-1A

2

21.75/
552.5

9.75/
247.7

21.00/
533.4

9.00/
228.6

WYM-2418-1A

WYM-2418-1A

2

21.75/
552.5

15.75/
400.1

21.00/
533.4

15.00/
381.0

WYM-2424-1

WYM-2424-1A

WYM-2424-1A

3

21.75/
552.5

21.75/
552.5

21.00/
533.4

21.00/
533.4

WYM-2812-1

WYM-2812-1

WYM-2812-1A

WYM-2812-1A

2

25.75/
654.1

9.75/
247.7

25.00/
635.0

9.00/
228.6

30.00 x 12.00/
762.0 x 304.8

WYM-3012-1

WYM-3012-1

WYM-3012-1A

WYM-3012-1A

2

27.75/
704.9

9.75/
247.7

27.00/
685.8

9.00/
228.6

30.00 x 18.00/
762.0 x 457.2

WYM-3018-1

WYM-3018-1

WYM-3018-1A

WYM-3018-1A

2

27.75/
704.9

15 .75/
400.1

27.00/
685.8

15.00/
381.0

30.00 x 24.00/
762.0 x 609.6

WYM-3024-1

WYM-3024-1

WYM-3024-1A

WYM-3024-1A

3

27.75/
704.9

21.75/
552.5

27.00/
685.8

21.00/
533.4

36.00 x 12.00/
914.4 x 304.8

WYM-3612-1

WYM-3612-1

WYM-3612-1A

WYM-3612-1A

2

33.75/
857.3

9.75/
247.7

33.00/
838.2

9.00/
228.6

36.00 x 18.00/
914.4 x 457.2

WYM-3618-1

WYM-3618-1

WYM-3618-1A

WYM-3618-1A

2

33.75/
857.3

15.75/
400.1

33.00/
838.2

15.00/
381.0

36.00 x 24.00/
914.4 x 609.6

WYM-3624-1

WYM-3624-1

WYM-3624-1A

WYM-3624-1A

3

33.75/
857.3

21.75/
552.5

33.00/
838.2

21.00/
533.4

36.00 x 30.00/
914.4 x 762.0

WYM-3630-1

WYM-3630-1

WYM-3630-1A

WYM-3630-1A

3

33.75/
857.3

27.75/
704.9

33.00/
838.2

27.00/
685.8

36.00 x 36.00/
914.4 x 914.4

WYM-3636-1

WYM-3636-1

WYM-3636-1A

WYM-3636-1A

3

33.75/
857.3

33.75/
857.3

33.00/
838.2

33.00/
838.2

24.00 x 12.00/
609.6 x 304.8

WYM-2412-1

WYM-2412-1

WYM-2412-1A

24.00 x 18.00/
609.6 x 457.2

WYM-2418-1

WYM-2418-1

24.00 x 24.00/
609.6 x 609.6

WYM-2424-1

28.00 x 12.00/
711.2 x 304.8

632

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYS Type Unflanged Junction or Pull Boxes
W Series: Raintight, Watertight

Cast Iron or Aluminum Box For Surface Mounting.
NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Applications
•	 These boxes are general purpose enclosures suitable for use
indoors or outdoors.

Features

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

•	 Mounting lugs are standard on boxes over 100 in3/1.6dm3
internal volume, and optional on boxes 100 in3/1.6dm3 or less.
See Options and Ordering Information pages for additional
information and ordering instructions.
•	 Type WYS boxes have a post in each corner and allowances
must be made for them when conduit entrances are to be
located close to a corner.
•	 Neoprene gasket, attached to cover.
•	 Suitable for a variety of applications.
•	 Wide selection of sizes and locations for drilled-and-tapped and
slip-hole conduit entrances.
•	 Choice of locations for blind tapped holes in interior mounting
buttons (optional).

Standard Materials
•	 Box and cover: cast iron
•	 Gasket: neoprene
•	 Screws: stainless steel cover

Standard Finishes
•	 Box and cover: hot dip galvanized

Options
•	 Available in aluminum. Add suffix -A to catalog number.
•	 For additional options see Options and Ordering Information
pages.

Certifications and Compliances
UL Standard: UL 514A, UL 50, UL 50E
UL Listed: E110234
CSA Standard: C22.2 No. 40
CSA Certified: 001472

Enclosures and Junction Boxes

•	
•	
•	
•	

† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

633

WYS Type Unflanged Junction or Pull Boxes
W Series: Raintight, Watertight

Cast Iron or Aluminum Box For Surface Mounting.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Iron
Catalog Number

Approximate Wall
Thickness *in/mm

L

Inside Dimensions Inches/Millimeters
x
W
x

WYS-040404 †

0.19/4.8

4.00/101.6

x

4.00/101.6

x

4.00/101.6

WYS-060404 †

0.19/4.8

6.00/152.4

x

4.00/101.6

x

4.00/101.6

D

WYS-060604

0.19/4.8

6.00/152.4

x

6.00/152.4

x

4.00/101.6

WYS-060606

0.25/6.4

6.00/152.4

x

6.00/152.4

x

6.00/152.4

WYS-080404

0.22/5.6

8.00/203.2

x

4.00/101.6

x

4.00/101.6

WYS-080604

0.22/5.6

8.00/203.2

x

6.00/152.4

x

4.00/101.6

WYS-080606

0.25/6.4

8.00/203.2

x

6.00/152.4

x

6.00/152.4

WYS-080804

0.22/5.6

8.00/203.2

x

8.00/203.2

x

4.00/101.6

WYS-080806

0.25/6.4

8.00/203.2

x

8.00/203.2

x

6.00/152.4

WYS-080808

0.94/23.9

8.00/203.2

x

8.00/203.2

x

8.00/203.2

WYS-100604

0.22/5.6

10.00/254.0

x

6.00/152.4

x

4.00/101.6

WYS-100606

0.28/7.1

10.00/254.0

x

6.00/152.4

x

6.00/152.4

WYS-100806

0.28/7.1

10.00/254.0

x

8.00/203.2

x

6.00/152.4

WYS-101004

0.22/5.6

10.00/254.0

x

10.00/254.0

x

4.00/101.6

WYS-101006

0.25/6.4

10.00/254.0

x

10.00/254.0

x

6.00/152.4

WYS-120804

0.22/5.6

12.00/304.8

x

8.00/203.2

x

4.00/101.6

WYS-120806

0.28/7.1

12.00/304.8

x

8.00/203.2

x

6.00/152.4

WYS-120808

0.94/23.9

12.00/304.8

x

8.00/203.2

x

8.00/203.2

WYS-121206

0.28/7.1

12.00/304.8

x

12.00/304.8

x

6.00/152.4

WYS-121208

0.94/23.9

12.00/304.8

x

12.00/304.8

x

8.00/203.2

WYS-121212

0.38/9.7

12.00/304.8

x

12.00/304.8

x

12.00/304.8

WYS-161208

0.94/23.9

16.00/406.4

x

12.00/304.8

x

8.00/203.2

WYS-180806

0.28/7.1

18.00/457.2

x

8.00/203.2

x

6.00/152.4

WYS-181206

0.28/7.1

18.00/457.2

x

12.00/304.8

x

6.00/152.4

WYS-181210

0.38/9.7

18.00/457.2

x

12.00/304.8

x

10.00/254.0

WYS-181806

0.94/23.9

18.00/457.2

x

18.00/457.2

x

6.00/152.4

WYS-181808

0.34/8.6

18.00/457.2

x

18.00/457.2

x

8.00/203.2

WYS-181812

0.44/11.2

18.00/457.2

x

18.00/457.2

x

12.00/304.8

* Measured 2.00”/50.8 mm up from back of box.
† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.

634

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYL Type Overlapping Cover Boxes
W Series: Watertight, Raintight

Cast Iron or Aluminum Box for Surface Mounting.
NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Applications
•	 These overlapping cover boxes are listed by Underwriters
Laboratories, Inc. as Type 4 †.
•	 They are suitable for use outdoors, or where they would be
subjected to rain, dripping or splashing of water.

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Features
•	 Mounting lugs are standard on boxes over 100 in3/1.6dm3
internal volume, and optional on boxes 100 in3/1.6dm3 or less.
See Options and Ordering Information pages for additional
information and ordering instructions.
•	 Type WYL boxes have a post in each corner and allowances
must be made for them when conduit entrances are to be
located close to a corner.
•	 Flat, neoprene gasket attached to cover.
•	 Wide selection of sizes and locations for drilled-and-tapped and
slip-hole conduit entrances.
•	 Choices of locations for blind tapped holes in interior mounting
buttons (optional).

Standard Materials
•	 Box and cover: cast iron
•	 Gasket: neoprene
•	 Screws: stainless steel cover

Standard Finishes
•	 Box and cover: hot dip galvanized

Options
•	 Available in aluminum. Add suffix -A to catalog number.
•	 For additional options see Options and Ordering Information
pages.

Certifications and Compliances
UL Standard: UL 514A, UL 50, UL 50E
UL Listed: E110234
CSA Standard: C22.2 No. 40
CSA Certified: 001472

Enclosures and Junction Boxes

•	
•	
•	
•	

† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

635

WYL Type Overlapping Cover Boxes
W Series: Watertight, Raintight

Cast Iron or Aluminum Box for Surface Mounting.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Iron
Catalog Number

Approximate Wall
Thickness * in/mm

L

Inside Dimensions Inches/Millimeters
x
W
x

WYL-040404 †

0.19/4.8

4.00/101.6

x

4.00/101.6

x

4.00/101.6

WYL-060404 †

0.19/4.8

6.00/152.4

x

4.00/101.6

x

4.00/101.6

D

WYL-060604

0.19/4.8

6.00/152.4

x

6.00/152.4

x

4.00/101.6

WYL-060606

0.25/6.4

6.00/152.4

x

6.00/152.4

x

6.00/152.4

WYL-080404

0.22/5.6

8.00/203.2

x

4.00/101.6

x

4.00/101.6

WYL-080604

0.22/5.6

8.00/203.2

x

6.00/152.4

x

4.00/101.6

WYL-080606

0.25/6.4

8.00/203.2

x

6.00/152.4

x

6.00/152.4

WYL-080804

0.22/5.6

8.00/203.2

x

8.00/203.2

x

4.00/101.6

WYL-080806

0.25/6.4

8.00/203.2

x

8.00/203.2

x

6.00/152.4

WYL-080808

0.31/7.9

8.00/203.2

x

8.00/203.2

x

8.00/203.2

WYL-100604

0.22/5.6

10.00/254.0

x

6.00/152.4

x

4.00/101.6

WYL-100606

0.28/7.1

10.00/254.0

x

6.00/152.4

x

6.00/152.4

WYL-100806

0.28/7.1

10.00/254.0

x

8.00/203.2

x

6.00/152.4

WYL-101004

0.22/5.6

10.00/254.0

x

10.00/254.0

x

4.00/101.6

WYL-101006

0.25/6.4

10.00/254.0

x

10.00/254.0

x

6.00/152.4

WYL-120804

0.22/5.6

12.00/304.8

x

8.00/203.2

x

4.00/101.6

WYL-120806

0.28/7.1

12.00/304.8

x

8.00/203.2

x

6.00/152.4

WYL-120808

0.31/7.9

12.00/304.8

x

8.00/203.2

x

8.00/203.2

WYL-121206

0.28/7.1

12.00/304.8

x

12.00/304.8

x

6.00/152.4

WYL-121208

0.31/7.9

12.00/304.8

x

12.00/304.8

x

8.00/203.2

WYL-121212

0.38/9.7

12.00/304.8

x

12.00/304.8

x

12.00/304.8

WYL-161208

0.31/7.9

16.00/406.4

x

12.00/304.8

x

8.00/203.2

WYL-180806

0.28/7.1

18.00/457.2

x

8.00/203.2

x

6.00/152.4

WYL-181206

0.28/7.1

18.00/457.2

x

12.00/304.8

x

6.00/152.4

WYL-181210

0.38/9.7

18.00/457.2

x

12.00/304.8

x

10.00/254.0

WYL-181806

0.31/7.9

18.00/457.2

x

18.00/457.2

x

6.00/152.4

WYL-181808

0.34/8.6

18.00/457.2

x

18.00/457.2

x

8.00/203.2

WYL-181812

0.44/11.2

18.00/457.2

x

18.00/457.2

x

12.00/304.8

WYL-241208

0.31/7.9

24.00/609.6

x

12.00/304.8

x

8.00/203.2

WYL-241812

0.44/11.2

24.00/609.6

x

18.00/457.2

x

12.00/304.8

WYL-242412

0.44/11.2

24.00/609.6

x

24.00/609.6

x

12.00/304.8

WYL-281208

0.38/9.7

28.00/711.2

x

12.00/304.8

x

8.00/203.2

WYL-361212

0.34/8.6

36.00/914.4

x

12.00/304.8

x

12.00/304.8

WYL-362412

0.44/11.2

36.00/914.4

x

24.00/609.6

x

12.00/304.8

WYL-363612

0.44/11.2

36.00/914.4

x

36.00/914.4

x

12.00/304.8

* Measured 2.00”/50.8 mm up from back of box.
† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.

636

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYW Type Hinged Cover Boxes

W Series: Watertight, Raintight, Dust Tight
Cast Iron or Aluminum Box for Surface Mounting.
NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Applications
•	 These hinged cover boxes make ideal enclosures where
equipment within the box has to be inspected frequently or easy
access is required.
•	 The hinges are adjusted at the factory for proper gasket
pressure, but can be readjusted in the field.

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Features
•	 Mounting lugs are standard on boxes over 100 in3/1.6dm3
internal volume, and optional on boxes 100 in3/1.6dm3 or less.
See Options and Ordering Information pages for additional
information and ordering instructions.
•	 Hinges are always located on the long side of the box and
unless otherwise specified on the right side.
•	 Hinged cover for easy access to wiring for inspection and
maintenance.
•	 Three-rivet anchoring of hinges and bolt/wing nut fasteners.
•	 Type WYW Boxes have a post in each corner and allowances
must be made for them when conduit entrances are to be
located close to a corner.
•	 Flat, neoprene gasket attached to cover.
•	 Wide selection of sizes and locations for drilled-and-tapped and
slip-hole conduit entrances.
•	 Choices of locations for blind tapped holes in interior mounting
buttons (optional).

Standard Materials
•	 Box and cover: cast iron
•	 Gasket: neoprene
•	 Screws: stainless steel cover

Standard Finishes
•	 Box and cover: hot dip galvanized

Options

Enclosures and Junction Boxes

•	 Available in aluminum. Add suffix -A to catalog number.
•	 For additional options see Options and Ordering Information
pages.

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 514A, UL 50, UL 50E
UL Listed: E110234
CSA Standard: C22.2 No. 40
CSA Certified: 001472

† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

637

WYW Type Hinged Cover Boxes

W Series: Watertight, Raintight, Dust Tight
Cast Iron or Aluminum Box for Surface Mounting.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Inside Dimensions Inches/Millimeters
x
W
x

Iron
Catalog Number

Approximate Wall
Thickness * in/mm

L

WYW-060404 †

0.19/4.8

6.00/152.4

x

4.00/101.6

x

4.00/101.6

WYW-060604

0.19/4.8

6.00/152.4

x

6.00/152.4

x

4.00/101.6

WYW-060606

0.25/6.4

6.00/152.4

x

6.00/152.4

x

6.00/152.4

WYW-080404

0.22/5.6

8.00/203.2

x

4.00/101.6

x

4.00/101.6

WYW-080604

0.22/5.6

8.00/203.2

x

6.00/152.4

x

4.00/101.6

WYW-080606

0.25/6.4

8.00/203.2

x

6.00/152.4

x

6.00/152.4

WYW-080804

0.22/5.6

8.00/203.2

x

8.00/203.2

x

4.00/101.6

WYW-080806

0.25/6.4

8.00/203.2

x

8.00/203.2

x

6.00/152.4

WYW-080808

0.31/7.9

8.00/203.2

x

8.00/203.2

x

8.00/203.2

WYW-100604

0.22/5.6

10.00/254.0

x

6.00/152.4

x

4.00/101.6

WYW-100606

0.28/7.1

10.00/254.0

x

6.00/152.4

x

6.00/152.4

WYW-100806

0.28/7.1

10.00/254.0

x

8.00/203.2

x

6.00/152.4

WYW-101004

0.22/5.6

10.00/254.0

x

10.00/254.0

x

4.00/101.6

WYW-101006

0.25/6.4

10.00/254.0

x

10.00/254.0

x

6.00/152.4

WYW-120804

0.22/5.6

12.00/304.8

x

8.00/203.2

x

4.00/101.6

WYW-120806

0.28/7.1

12.00/304.8

x

8.00/203.2

x

6.00/152.4

WYW-120808

0.31/7.9

12.00/304.8

x

8.00/203.2

x

8.00/203.2

WYW-121206

0.28/7.1

12.00/304.8

x

12.00/304.8

x

6.00/152.4

WYW-121208

0.31/7.9

12.00/304.8

x

12.00/304.8

x

8.00/203.2

WYW-121212

0.38/9.7

12.00/304.8

x

12.00/304.8

x

12.00/304.8

WYW-161208

0.31/7.9

16.00/406.4

x

12.00/304.8

x

8.00/203.2

WYW-180806

0.28/7.1

18.00/457.2

x

8.00/203.2

x

6.00/152.4

WYW-181206

0.28/7.1

18.00/457.2

x

12.00/304.8

x

6.00/152.4

WYW-181210

0.38/9.7

18.00/457.2

x

12.00/304.8

x

10.00/254.0

WYW-181806

0.31/7.9

18.00/457.2

x

18.00/457.2

x

6.00/152.4

WYW-181808

0.34/8.6

18.00/457.2

x

18.00/457.2

x

8.00/203.2

WYW-181812

0.44/11.2

18.00/457.2

x

18.00/457.2

x

12.00/304.8

WYW-241208

0.31/7.9

24.00/609.6

x

12.00/304.8

x

8.00/203.2

WYW-241812

0.44/11.2

24.00/609.6

x

18.00/457.2

x

12.00/304.8

WYW-242412

0.44/11.2

24.00/609.6

x

24.00/609.6

x

12.00/304.8

WYW-281208

0.38/9.7

28.00/711.2

x

12.00/304.8

x

8 .00/203.2

WYW-361212

0.34/8.6

36.00/914.4

x

12.00/304.8

x

12.00/304.8

WYW-362412

0.44/11.2

36.00/914.4

x

24.00/609.6

x

12.00/304.8

WYW-363612

0.44/11.2

36.00/914.4

x

36.00/914.4

x

12.00/304.8

D

* Measured 2.00”/50.8 mm up from back of box.
† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.

638

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYF Type Flat Flanged Boxes

W Series: Submersible ‡, Watertight, Raintight, Dust Tight
Cast Iron or Aluminum Box for Surface Mounting.

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 6 ‡, 6P ‡,
12, 12K, 13

Applications
•	 These boxes have been listed by Underwriters Laboratories, Inc.
as a Type 4 † enclosure.
•	 They are also suitable for use indoors or outdoors where they
would be subjected to splashing water, seepage of water, falling
or hose directed water and severe external condensation. †

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Features
•	 Mounting lugs are standard on boxes over 100 in3/1.6dm3
internal volume, and optional on boxes 100 in3/1.6dm3 or less.
See Options and Ordering Information pages for additional
information and ordering instructions.
•	 Wide flange provides greater contact between gasketed cover
and box.
•	 Enclosed and gasketed construction – neoprene gasket
attached to cover.
•	 Flange ground before galvanizing.
•	 Choices of locations for blind tapped holes in interior mounting
buttons (optional).

Standard Materials
•	 Box and cover: cast iron
•	 Gasket: neoprene
•	 Screws: stainless steel cover

Standard Finishes
•	 Box and cover: hot dip galvanized

Options
The ridge on the underside of
the cover assures a good seal.

Enclosures and Junction Boxes

•	 Available in aluminum. Add suffix -A to catalog number.
•	 For additional options see Options and Ordering Information
pages.
•	 Submersible Applications ‡
— These boxes can be tested to withstand occasional
submersion under a 6 foot/1.83 meter head of water for 30
minutes (NEMA 6 requirements). Add suffix -SUB6 to catalog
number.
— These boxes can be tested to withstand Prolonged
submersion under a 6 foot/1.83 meter head of water for 24
hours (NEMA 6P requirements). Add suffix -SUB6P to catalog
number.
— These boxes can be tested to withstand submersion up to a
20-foot head of water. Add suffix -SUB___ to catalog number,
filling in the blank space with the number of feet from 7 up to
20, followed by -P if prolonged submersion is required.
— All WYF-SUB enclosures are subject to a price addition on
application and must have:
1. Mounting lugs
2. Bossed, drilled, and tapped conduit entrances (ABDT
series)

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 514A, UL 50, UL 50E
UL Listed: E110234
CSA Standard: C22.2 No. 40
CSA Certified: 001472

† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.
‡ Intended for indoor or outdoor use primarily to provide a degree of protection against hose-directed water and the entry of water during temporary submersion
at a limited depth; and to be undamaged by the formation of ice on the enclosure.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

639

WYF Type Flat Flanged Boxes

W Series: Submersible ‡, Watertight, Raintight, Dust Tight
Cast Iron or Aluminum Box for Surface Mounting.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 6 ‡, 6P ‡,
12, 12K, 13

Inside Dimensions Inches/Millimeters
x
W
x

Iron
Catalog Number

Approximate Wall
Thickness * in/mm

L

WYF-040404 †

0.16/4.1

4.00/101.6

x

4.00/101.6

x

4.00/101.6

WYF-060404 †

0.16/4.1

6.00/152.4

x

4.00/101.6

x

4.00/101.6

WYF-060604

0.22/5.6

6.00/152.4

x

6.00/152.4

x

4.00/101.6

WYF-060606

0.22/5.6

6.00/152.4

x

6.00/152.4

x

6.00/152.4

D

WYF-080404

0.19/4.8

8.00/203.2

x

4.00/101.6

x

4.00/101.6

WYF-080606

0.22/5.6

8.00/203.2

x

6.00/152.4

x

6.00/152.4

WYF-080804

0.22/5.6

8.00/203.2

x

8.00/203.2

x

4.00/101.6

WYF-080806

0.25/6.4

8.00/203.2

x

8.00/203.2

x

6.00/152.4

WYF-080808

0.25/6.4

8.00/203.2

x

8.00/203.2

x

8.00/203.2

WYF-100606

0.22/5.6

10.00/254.0

x

6.00/152.4

x

6.00/152.4

WYF-100806

0.25/6.4

10.00/254.0

x

8.00/203.2

x

6.00/152.4

WYF-101004

0.25/6.4

10.00/254.0

x

10.00/254.0

x

4.00/101.6

WYF-101006

0.25/6.4

10.00/254.0

x

10.00/254.0

x

6.00/152.4

WYF-120804

0.25/6.4

12.00/304.8

x

8.00/203.2

x

4.00/101.6

WYF-120806

0.25/6.4

12.00/304.8

x

8.00/203.2

x

6.00/152.4

WYF-120808

0.25/6.4

12.00/304.8

x

8.00/203.2

x

8.00/203.2

WYF-121206

0.25/6.4

12.00/304.8

x

12.00/304.8

x

6.00/152.4

WYF-121208

0.31/7.9

12.00/304.8

x

12.00/304.8

x

8.00/203.2

WYF-121212

0.31/7.9

12.00/304.8

x

12.00/304.8

x

12.00/304.8

WYF-161004

0.28/7.1

16.00/406.4

x

10.00/254.0

x

4.00/101.6

WYF-161208

0.28/7.1

16.00/406.4

x

12.00/304.8

x

8.00/203.2

WYF-180806

0.28/7.1

18.00/457.2

x

8.00/203.2

x

6.00/152.4

WYF-181206

0.28/7.1

18.00/457.2

x

12.00/304.8

x

6.00/152.4

WYF-181210

0.31/7.9

18.00/457.2

x

12.00/304.8

x

10.00/254.0

WYF-181806

0.31/7.9

18.00/457.2

x

18.00/457.2

x

6.00/152.4

WYF-181812

0.31/7.9

18.00/457.2

x

18.00/457.2

x

12.00/304.8

WYF-241208

0.31/7.9

24.00/609.6

x

12.00/304.8

x

8.00/203.2

WYF-241812

0.34/8.6

24.00/609.6

x

18.00/457.2

x

12.00/304.8

WYF-242412

0.38/9.7

24.00/609.6

x

24.00/609.6

x

12.00/304.8

WYF-281208

0.38/8.6

28.00/711.2

x

12.00/304.8

x

8.00/203.2

WYF-361812

0.38/8.6

36.00/914.4

x

18.00/457.2

x

12.00/304.8

WYF-363612

0.44/11.2

36.00/914.4

x

36.00/914.4

x

12.00/304.8

* Measured 2.00”/50.8 mm up from back of box.
† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.
‡ Intended for indoor or outdoor use primarily to provide a degree of protection against hose-directed water and the entry of water during temporary submersion
at a limited depth; and to be undamaged by the formation of ice on the enclosure.

640

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYU Type Inside Flanged Recessed Cover Boxes
W Series: Raintight, Dust Tight
Cast Iron Box for Flush Mounting.

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 5, 12, 12K, 13

Applications
•	 Recessed cover boxes designed for flush mounting in masonry.
•	 They are furnished with a plain cover as shown but can be
supplied with steel checkered plate covers suitable for foot
traffic (see options).

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Features
•	 Flat, neoprene gasket attached to cover.
•	 Wide selection of sizes and locations for drilled-and-tapped and
slip-hole conduit entrances.
•	 Choices of locations for blind tapped holes in interior mounting
buttons (optional).

Standard Materials
•	 Box and cover: cast iron
•	 Gasket: neoprene
•	 Screws: stainless steel cover

Installation in Masonry

Standard Finishes
•	 Box and cover: hot dip galvanized

Options
•	 Available in aluminum. Add suffix -A to catalog number.
•	 Steel checkered plate covers suitable for pedestrian traffic add
suffix -CS.
•	 See optional hinges below.
•	 For additional options see Options and Ordering Information
pages.
Iron
Catalog Number

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 514A, UL 50, UL 50E
UL Listed: E110234
CSA Standard: C22.2 No. 40
CSA Certified: 001472
Inside Dimensions Inches/Millimeters
x
W
x

Approximate Wall
Thickness * in/mm

L

WYU-040404

0.16/4.1

4.00/101.6

x

4.00/101.6

x

4.00/101.6

WYU-060604

0.22/5.6

6.00/152.4

x

6.00/152.4

x

4.00/101.6

WYU-060606

0.22/5.6

6.00/152.4

x

6.00/152.4

x

6.00/152.4

WYU-080804

0.25/6.4

8.00/203.2

x

8.00/203.2

x

4.00/101.6

WYU-080806

0.25/6.4

8.00/203.2

x

8.00/203.2

x

6.00/152.4

WYU-100806

0.25/6.4

10.00/254.0

x

8.00/203.2

x

6.00/152.4

WYU-101006

0.25/6.4

10.00/254.0

x

10.00/254.0

x

6.00/152.4

WYU-120806

0.25/6.4

12.00/304.8

x

8.00/203.2

x

6.00/152.4

WYU-121206

0.25/6.4

12.00/304.8

x

12.00/304.8

x

6.00/152.4

WYU-121212

0.31/7.9

12.00/304.8

x

12.00/304.8

x

12.00/304.8

WYU-161208

0.28/7.1

16.00/406.4

x

12.00/304.8

x

8.00/203.2

WYU-181210

0.28/7.1

18.00/457.2

x

12.00/304.8

x

10.00/254.0

D

Enclosures and Junction Boxes

Optional Hinges (Stainless Steel, Butt Type)
Catalog Number

Hinges Per Set

Box Size

AHNG-22SS

0.16/4.1

Up to 12” x 12”/304.8 x 304.8 mm

AHNG-23SS

0.22/5.6

Up to 18” x 18”/457.2 x 457.2 mm

AHNG-33SS

0.22/5.6

Larger than 18” x 18”/457.2 x 457.2mm

* Measured 2.00”/50.8 mm up from back of box.
† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

641

WYR Outside Flanged Recessed Cover Boxes
W Series: Watertight, Raintight, Dust Tight
Cast Iron Box for Flush Mounting.

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Applications
•	 These recessed cover boxes are listed by Underwriters’
Laboratories, Inc. as Type 4.
•	 They are suitable for use outdoors where they would be
subjected to rain or dripping or splashing of water.
•	 This type of box is designed especially for flush mounting
in walls or floors or can be used for surface mounting using
optional mounting lugs.

Features
•	 Flat, neoprene gasket attached to cover.
•	 Wide box flange permits greater contact between gasket and box.
•	 Wide selection of sizes and locations for drilled-and-tapped and
slip-hole conduit entrances.
•	 Choices of locations for blind tapped holes in interior mounting
buttons (optional).

Standard Materials
•	 Box and cover: cast iron
•	 Gasket: neoprene
•	 Screws: stainless steel cover

Standard Finishes
•	 Box and cover: hot dip galvanized

Installation in
Masonry

Options
•	 Available in aluminum. Add suffix -A to catalog number.
•	 Steel checkered plate covers suitable for pedestrian traffic add
suffix -CS.
•	 Steel checkered covers suitable for vehicular traffic (H-25
loading) add suffix -CSV.
•	 For additional options see Options and Ordering Information
pages.

Certifications and Compliances
•	
•	
•	
•	

UL Standard: UL 514A, UL 50, UL 50E
UL Listed: E110234
CSA Standard: C22.2 No. 40
CSA Certified: 001472

† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.

642

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYR Outside Flanged Recessed Cover Boxes
W Series: Watertight, Raintight, Dust Tight
Cast Iron Box for Flush Mounting.

NEMA/CSA Type 1, 2, 3, 3R †, 3S †, 4 †, 5, 12,
12K, 13

Iron
Catalog Number

Approximate Wall
Thickness * in/mm

L

Inside Dimensions Inches/Millimeters
x
W
x

WYR-040404

0.16/4.1

4.00/101.6

x

4.00/101.6

x

4.00/101.6

WYR-060404

0.16/4.1

6.00/152.4

x

4.00/101.6

x

4.00/101.6

D

0.22/5.6

6.00/152.4

x

6.00/152.4

x

4 4.00/101.6

0.22/5.6

6.00/152.4

x

6.00/152.4

x

6.00/152.4

WYR-080404

0.19/4.8

8.00/203.2

x

4.00/101.6

x

4.00/101.6

WYR-080604

0.22/5.6

8.00/203.2

x

6.00/152.4

x

4.00/101.6

WYR-080804

0.25/6.4

8.00/203.2

x

8.00/203.2

x

4.00/101.6

WYR-080806

0.25/6.4

8.00/203.2

x

8.00/203.2

x

6.00/152.4

WYR-080808

0.25/6.4

8.00/203.2

x

8.00/203.2

x

8.00/203.2

WYR-100606

0.22/5.6

10.00/254.0

x

6.00/152.4

x

6.00/152.4

WYR-100806

0.25/6.4

10.00/254.0

x

8.00/203.2

x

6.00/152.4

WYR-101004

0.25/6.4

10.00/254.0

x

10.00/254.0

x

4.00/101.6

WYR-101006

0.25/6.4

10.00/254.0

x

10.00/254.0

x

6.00/152.4

WYR-120804

0.25/6.4

12.00/304.8

x

8.00/203.2

x

4.00/101.6

WYR-120806

0.25/6.4

12.00/304.8

x

8.00/203.2

x

6.00/152.4

WYR-120808

0.25/6.4

12.00/304.8

x

8.00/203.2

x

8.00/203.2

WYR-121206

0.25/6.4

12.00/304.8

x

12.00/304.8

x

6.00/152.4

WYR-121208

0.31/7.9

12.00/304.8

x

12.00/304.8

x

8.00/203.2

0.31/7.9

12.00/304.8

x

12.00/304.8

x

12.00/304.8

0.25/6.4

14.00/355.6

x

8.00/203.2

x

6.00/152.4

WYR-161208

0.28/7.1

16.00/406.4

x

12.00/304.8

x

8.00/203.2

WYR-180806

0.28/7.1

18.00/457.2

x

8.00/203.2

x

6.00/152.4

WYR-181206

0.28/7.1

18.00/457.2

x

12.00/304.8

x

6.00/152.4

WYR-181210

0.31/7.9

18.00/457.2

x

12.00/304.8

x

10.00/254.0

WYR-181806

0.31/7.9

18.00/457.2

x

18.00/457.2

x

6.00/152.4

WYR-181812

0.31/7.9

18.00/457.2

x

18.00/457.2

x

12.00/304.8

WYR-241208

0.31/7.9

24.00/609.6

x

12.00/304.8

x

8.00/203.2

WYR-241812

0.34/8.6

24.00/609.6

x

18.00/457.2

x

12.00/304.8

WYR-242412

0.38/9.7

24.00/609.6

x

24.00/609.6

x

12.00/304.8

WYR-361812

0.38/9.7

36.00/914.4

x

18.00/457.2

x

12.00/304.8

WYR-362412

0.41/10.4

36.00/914.4

x

24.00/609.6

x

12.00/304.8

WYR-363612

0.44/11.2

36.00/914.4

x

36.00/914.4

x

12.00/304.8

Enclosures and Junction Boxes

WYR-121212
WYR-140806

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

WYR-060604
WYR-060606

* Measured 2.00”/50.8 mm up from back of box.
† Mounting lugs are optional. For watertight and raintight external mounting means must be provided. Specify mounting lugs.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

643

WYT Type Checkered Cover Sidewalk Boxes
W Series: Weatherproof
Cast Iron Box for Flush Mounting.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Applications
•	 These boxes are specially designed to be mounted in sidewalks
and other flat concrete surfaces. Their checkered covers are
made to withstand pedestrian traffic.
•	 The flanges and covers are interchangeable to permit
replacement without disturbing the box or conduit system.
•	 Heavy checkered steel covers can be furnished which will
accommodate vehicular traffic (see Options and Ordering
Information pages).

Features
•	 Type WYT boxes have a post in each corner and allowances
must be made for them, when conduit entrances are to be
located close to a corner.
•	 Cross ribbed, heavy duty cover with pry bar slots.
•	 Checkered cover provides non-slip surface.
•	 Flat, neoprene gasket, attached to cover.
•	 Wide selection of locations for drilled and tapped and slip hole
conduit entrances.
•	 Choice of locations for blind tapped holes in interior mounting
buttons (optional).

Standard Materials
•	 Box and cover: cast iron
•	 Gasket: neoprene
•	 Screws: stainless steel cover

Standard Finishes
•	 Box and cover: hot dip galvanized

Options
•	 Available in aluminum. Add suffix -A to catalog number.
•	 Steel checkered covers suitable for vehicular traffic H-25
loading, add suffix -CSV.
•	 Engraved lettering on cover per specifications.
•	 For additional options see Options and Ordering Information
pages.

Inside Dimensions Inches/Millimeters
x
W
x

Iron
Catalog Number

Approximate Wall
Thickness * in/mm

L

WYT-060604

0.25/6.4

6.00/152.4

x

6.00/152.4

x

4.00/101.6

WYT-080604

0.25/6.4

8.00/203.2

x

6.00/152.4

x

4.00/101.6

WYT-080804

0.25/6.4

8.00/203.2

x

8.00/203.2

x

4.00/101.6

WYT-080806

0.25/6.4

8.00/203.2

x

8.00/203.2

x

6.00/152.4

WYT-080808

0.25/6.4

8.00/203.2

x

8.00/203.2

x

8.00/203.2

WYT-120808

0.31/7.9

12.00/304.8

x

8.00/203.2

x

8.00/203.2

WYT-121206

0.31/7.9

12.00/304.8

x

12.00/304.8

x

6.00/152.4

WYT-121208

0.38/9.7

12.00/304.8

x

12.00/304.8

x

8.00/203.2

WYT-121212

0.38/9.7

12.00/304.8

x

12.00/304.8

x

12.00/304.8

WYT-181206

0.38/9.7

18.00/457.2

x

12.00/304.8

x

6.00/152.4

WYT-241208

0.38/9.7

24.00/609.6

x

12.00/304.8

x

8.00/203.2

D

* Measured 2.00”/50.8 mm up from back of box.

644

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYC Type Box with Hinged Door and Trim Cabinet
W Series: Weatherproof

Cast Iron Box for Flush Mounting in Walls.

Applications
•	 They are used exterior building walls, bridge construction,
underpasses and approaches.
•	 They may house time switches, relays or other types of equipment.

Features

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

•	 These boxes have ornamental trim for flush mounting in
concrete or stone structures.
•	 Type WYC boxes have a post in each corner and allowances
must be made for them, when conduit entrances are to be
located close to a corner.

Standard Materials
•	
•	
•	
•	
•	

Box: cast iron
Trim/door: cast iron
Gasket: neoprene and polyurethane
Hinges: steel, non-removable
Cylinder lock: brass with two keys

Standard Finishes
•	 Box: hot dip galvanized
•	 Trim/Door: hot dip galvanized
•	 Hinges: zinc plated

Options
•	 Lettering cast on cover per specifications at price addition.
•	 Cast bronze trim/door available at price addition. Add suffix -B.
•	 For additional options see Options and Ordering Information
pages.

Approximate Wall
Thickness * in/mm

L

WYC-060604

0.25/6.4

6.00/152.4

x

WYC-080808

0.25/6.4

8.00/203.2

WYC-121206

0.31/7.9

12.00/304.8

WYC-121208

0.38/9.7

12.00/304.8

Enclosures and Junction Boxes

Inside Dimensions Inches/Millimeters
x
W
x

Iron
Catalog Number

D

6.00/152.4

x

4.00/101.6

x

8.00/203.2

x

8.00/203.2

x

12.00/304.8

x

6.00/152.4

x

12.00/304.8

x

8.00/203.2

* Measured 2.00”/50.8 mm up from back of box.
Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

645

WY58E Type Checkered Cover Sidewalk Topping Box
W Series: Weatherproof
Cast Iron Box for Flush Mounting.

Applications
•	 These open-bottom boxes are designed to top off an underlying
concrete pull box.
•	 The construction details of the cover and flange are the same as
those of a Type WYT.
•	 Frame and cover are interchangeable and may be replaced if
damaged without disturbing the rest of the system.
•	 Checkered cover provides non-slip surface for pedestrian traffic.
•	 Cross-ribbed checkered cover with pry bar slots.
•	 Cover secures to frame with recessed stainless steel hex head
cap screws.
•	 Flat, neoprene gasket, attached to cover.
•	 Wide selection of locations for drilled and tapped and slip hole
conduit entrances.

Standard Materials
•	 Box, flange and cover: cast iron
•	 Neoprene gasket
•	 Screws: stainless steel

Standard Finishes
•	 Box and cover: hot dip galvanized

Options
•	 Engraved lettering on cover per specifications.

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

Features

Iron
Catalog Number

Approximate Wall
Thickness * in/mm

L

Inside Dimensions Inches/Millimeters
x
W
x

D

WY58E-1212

0.38/9.7

12.00/304.8

x

12.00/304.8

x

5.00/127.0

WY58E-1812

0.38/9.7

18.00/457.2

x

12.00/304.8

x

5.00/127.0

WY58E-2412

0.38/9.7

24.00/609.6

x

12.00/304.8

x

5.00/127.0

WY58E-2418

0.38/9.7

24.00/609.6

x

18.00/457.2

x

5.00/127.0

WY58E-2424

0.38/9.7

24.00/609.6

x

24.00/609.6

x

5.00/127.0

WY58E-3018

0.38/9.7

30.00/762.0

x

18.00/457.2

x

5.00/127.0

WY58E-3618

0.38/9.7

36.00/914.4

x

18.00/457.2

x

5.00/127.0

WY58E-3624

0.38/9.7

36.00/914.4

x

24.00/609.6

x

5.00/127.0

WY58E-3636

0.38/9.7

36.00/914.4

x

36.00/914.4

x

5.00/127.0

WY58E-4224

0.38/9.7

42.00/1066.8

x

24.00/609.6

x

5.00/127.0

* Measured 2.00”/50.8 mm up from back of box.

646

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

WYNY Type Checkered Cover Roadway Topping Box
W Series: Weatherproof

Cast Iron Box for Flush Mounting.

Applications
•	 These open-bottom boxes are designed to top off concrete
pull boxes.
•	 Units designed to withstand vehicular traffic, H-20 loading.

Features

Enclosures and Junction Boxes: Ordinary Location Junction Boxes

•	 Design of these boxes is similar to the type WY58E except box
and flange are one piece and cover is of cast steel or ductile iron.
•	 Cross-ribbed checkered cover with pry bar slots.

Standard Materials
•	
•	
•	
•	

Box: cast iron
Cover: cast steel or ductile iron
Gasket: neoprene
Screws: stainless steel cover

Standard Finishes
•	 Box and cover: hot dip galvanized

Options
•	 Engraved lettering on cover per specifications.

Approximate Wall
Thickness * in/mm

L

WYNY-1812-DIV

0.38/9.7

18.00/457.2

x

12.00/304.8

x

5.50/139.7

WYNY-2418-DIV

0.38/9.7

24.00/609.6

x

18.00/457.2

x

5.50/139.7

WYNY-3018-DIV

0.38/9.7

30.00/762.0

x

18.00/457.2

x

5.50/139.7

WYNY-3618-DIV

0.38/9.7

36.00/914.4

x

18.00/457.2

x

5.50/139.7

WYNY-3624-DIV

0.38/9.7

36.00/914.4

x

24.00/609.6

x

5.50/139.7

WYNY-4824-DIV

0.38/9.7

48.00/1219.2

x

24.00/609.6

x

5.50/139.7

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.
© September 2010

Enclosures and Junction Boxes

Inside Dimensions Inches/Millimeters
x
W
x

Iron
Catalog Number

D

647

Enclosures and Junction Boxes

Enclosures and Junction Boxes: Notes

Notes

648

Visit our website at www.appletonelec.com or contact us at (800) 621-1506.