Vigirex Ground Fault Relays
2014-11-11
: Pdf 59155-Attachment 59155-Attachment 785901 Batch12 unilog
Open the PDF directly: View PDF
Page Count: 52
- Please Note
- Section 1—Introduction
- Section 2—Vigirex Ground-fault Relays System Overview
- Introduction
- Operation
- Vigirex ground-fault relays are not designed to protect people as defined by UL 943 Class A. Vigi...
- Testing Locally or Remotely, With or Without Tripping
- Benefits to the Equipment User
- Table 1: Benefits for the End-Use Customer
- How can manufacturers be sure equipment has this benefit?
- Benefits to the manufacturer of equipment (OEM)
- Table 2: Benefits for the OEM
- Selection Criteria for Relays
- Mounting / Packaging—RH10M, RH21M, RH99M, and RH10P, RH21P, RH99P
- Control Voltage
- Time Delays
- Sensitivity (Tripping Threshold)
- Manual or Automatic Reset
- Selection Criteria for Sensors
- Closed Toroid Sensors
- Split Toroid Sensors
- Rectangular Sensors
- Table 3: Vigirex Ground-Fault Relays (UL 1053)
- Table 4: Sensors for Vigirex Ground-Fault Relays
- Section 3—Relay Characteristics
- Optimum Continuity of Service
- The Vigirex range of ground-fault relays offers multiple setting possibilities that may be used t...
- Provisions to minimize downtime of the Vigirex relay include:
- The Vigirex relays trip between 80% and 100% of their tripping threshold (IDn) thus increasing im...
- A range of power supplies is available, including a low voltage unit for operation from AC or DC ...
- Additional standard functions are available to make the protection as dependable as possible:
- Vigirex relays are not affected by micro-outages lasting less than 60 ms. The maximum break time ...
- Vigirex relays continuously monitor the power supply, relay / sensor link and internal electronic...
- The Vigirex relay can be manually tested as part of a maintenance routine. This procedure can be ...
- Either method can be used locally (with front-panel push buttons) or remotely via the Test and Re...
- If a Vigirex relay with a 30 mA setting is used to shunt trip a Schneider Electric / Square D Com...
- The electronic design of the Vigirex relay provides several functions to minimize outages and eli...
- The inverse-time tripping curve of the Vigirex relays (see Figure 3) affects performance in two b...
- Also, when circuits are energized, the inverse-time tripping curve avoids nuisance tripping due t...
- Vigirex devices use rms measurements for the zero-sequence currents. This is the means to:
- Frequency filtering by Vigirex residual current relays ensures maximum protection against insulat...
- Frequency converters (e.g. variable-speed drives) generate significant levels of high-frequency l...
- Vigirex relays are designed to optimize immunity to:
- To ensure optimal immunity, Vigirex relays are tested in compliance with the following standards:
- The high immunity levels of Vigirex relays ensure optimum safety without nuisance tripping.
- According to the National Electrical Code (NEC), a test is required after installation to check c...
- The purpose of the test is to check:
- Whatever the test mode, a reset clears the fault stored in memory and resets the LEDs and the rel...
- During acceptance of a switchboard or other electrical equipment and prior to dielectric testing,...
- Vigirex relays are supplied with a plug-in connector for easy and secure connection and disconnec...
- The Vigirex relays can be mounted in a variety of ways:
- Plug in connectors allow easy and secure disconnection of control panel for switchboard acceptanc...
- DIN-format Vigirex relays can be equipped with toroids from 1–2 in. (30–50 mm) in diameter.
- —
- Section 4—Sensors
- Section 5—Coordination
- Section 6—Application of Vigirex ground-fault Relays
- Introduction to Equipment Ground-fault Protection
- Installation in Equipment by the End-User
- Installation in Equipment by the OEM
- Distribution Applications in Addition to NEC Requirements at Main Service
- Alarming / Monitoring Applications
- Identifying the Right Applications
- Consequences of an Insulation Fault
- Introduction to Electrical Systems
- Applications
- TN-S Grounding System
- Electrical Shock Hazard
- Vigirex relays are NOT UL Listed to comply with UL standards for people protection.
- Wiring Diagrams—RH10, RH21, and RH99
- Wiring for Optimum Continuity of Service (with Shunt Trip)
- Wiring for Optimum Safety (with Undervoltage Release)
- Connection of Test and Remote Reset Functions
- Connection of RH10, RH21, and RH99 Power Supply
- Section 7—Vigirex Relays and Sensors Installation and Dimensions
- Possible Installation Positions
- Relay Mounting Possibilities
- Dimensions–RH10M, RH21M, and RH99M
- Dimensions—RH10P, RH21P, and RH99P
- Connection (Relays and Sensors)
- Sensor Mounting
- Figure 33: TA30, PA50, IA80, or MA120 on DIN Rail Using Supplied Accessories
- Figure 34: TA30, PA50, IA80, MA120, SA 200 GOA, or POA on a Plate or Bracket
- Figure 35: TA30 and PA50 Clipped on the Back of the Relay
- Figure 36: IA80, MA120, SA200, and GA300 Tied to Cables
- Figure 37: Rectangular Sensors Tied to Cables
- Figure 38: Rectangular Sensors on Bars with Chocks
- Conductor Installation Guidelines
- Connection of Rectangular Sensors and Conductor Layout
- Connection Between Vigirex Relays and Sensors
- Section 8—Definitions
- Coordination
- Direct Contact
- Double Insulation
- Earth Leakage
- EMC / EM
- Earth (Ground)
- Equipotential Bonding
- Exposed Conductive Part
- Fault (Electrical)
- Fault Voltage
- Ground Electrode
- Ground-Fault Current
- Ground-Fault Protection (GFP)
- Ground-Leakage Current
- Grounding Resistance
- Indirect Contact
- Insulation Voltage
- Intentional Leakage Current
- Isolated System
- IT
- Leakage Current
- Live Conductor
- National Electrical Code (NEC)
- Natural Leakage Current
- People Protection Devices
- Pickup Current (Residual Operating Current) (IDn)
- Protective Ground Conductor (PE)
- RFI
- RFI Filter
- RMS
- Residual Current
- Residual Current Device (RCD)
- Residual Operating Current IDn
- Sensor
- Service Voltage
- TN
- TN-S
- TT
- Time Delay
- Touch Voltage
- UL 943
- UL 1053
- Zero-Sequence Current