Catalog #
Project
Comments
Prepared by
Type
Date
203 Cooper Circle P: 800-553-3879
Peachtree City, GA 30269 F: 800-954-7016
www.coopercontrol.com
Specifications:
Electrical Ratings:
Input: (120/277 VAC-SP20-MV), (347 VAC-
SP15-347), (220-240 VAC-SP20-240), 50/60 Hz
operation. Contacts are isolated and may be used to
control low voltage circuits.
Output: 15 VDC 125mA to operate up to five
Greengate sensors
Control: Connecting the 22 AWG red and blue control
leads to each other will close the relay contacts
Ballast Compatibility: Compatible with magnetic and
electronic ballasts
NOTE: The life of some compact fluorescent
lamps (CFLs) is shortened by frequent automatic or
manual switching. Check with the CFL and ballast
manufacturer to determine effects of cycling.
Operating Environment:
• Temperature: 32°F to 104°F (0°C to 40°C)
• Relative humidity: less than 95%, non-condensing
• For indoor use only
Housing: Medium impact injection molded housing.
ABS resin complies with UL 94V-0. Plenum rated for
external junction box mounting, with Teflon coated
leads.
Motor Load: 1 HP 120-240 VAC; 2 HP 250 VAC
Size: 2 15/16” x 2 7/16” x 1 11/16”
Mounting: Mounts to the side of a 4" square box via
1/2" knockout
SP15 & SP20,
Heavy Duty
Switchpacks
Overview
Switchpacks provide 15 VDC operating voltage to all low voltage, 15 VDC
occupancy sensors and daylighting controllers. A single switchpack can provide
power for up to five sensors. Up to ten switchpacks can be connected to one
sensor for control of multiple circuits. Isolated contacts may also be used to control
HVAC, contactors, motors, etc.
Description/Operation
The switchpack has two main components: a transformer and one high current
relay. The transformer has a primary line voltage input and a secondary low voltage
output. The low voltage output, 15 VDC, provides operating power to connected
low voltage Greengate occupancy sensors. When an occupancy sensor detects
motion, it electrically closes an internal circuit, pulling up the control signal between
the sensor and the switchpack. This signals the switchpack to close its high current
relay, turning the connected load on.
Ordering
Can be easily mounted on or in a
4"sq. junction box, via ½” in nipple
Available for 120, 220, 240, 277
& 347 VAC operation
Application
The switchpack is designed to work with low voltage sensors which require
switchpacks. It cannot be used with sensors designed for use with any other
low voltage relay systems. Consult sensor spec sheets for other sensor relay
combinations.
Catalog # Ratings TungstenBallast Output
120/277 VAC, 50/60 Hz
347 VAC, 50/60 Hz
220-240 VAC, 50/60 Hz
20A
15A
20A
15A, 120V
NR
NR
15 VDC, 125mA
15 VDC, 125mA
15 VDC, 125mA
Motor (HP)
1HP-120V, 2HP-250V
NR
NR
SP20-MV
SP15-347
SP20-240
•Replacesseparatetransformers
and relays
•Zero-crossingcircuitprovides
increased durability, especially with
today’s high inrush loads
•Capableofswitchingupto20Amps
•SuitableforPlenumuse
•RatedforBallast,TungstenandMotor
Loads
UL, CSA listed
ACC131666
www.coopercontrol.com
203 Cooper Circle, Peachtree City, GA 30269
P: 800-553-3879 F: 800-954-7016
Cooper Controls, Greengate, Novitas, Yes Box, PCI Lighting Control Systems, VisionTouch, VisionSwitch,
MicroSet, Digita, ControlKeeper, LiteKeeper, TracKeeper, IntelliRelay are valuable trademarks of Cooper
Industries in the U.S and other countries. You are not permitted to use Cooper Trademarks without the
prior written consent of Cooper Industries.
All connections are made via pigtails with twist-on
wire connectors.
NOTE: Connect either the orange or black supply
lead to the power source, depending upon the power
requirements. Cap the unused lead.
Wiring Diagrams SP15 & SP20, Heavy Duty Switchpacks
LOAD
BLUE
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
**HOT
WHITE
BLUE
SWITCH-
PACK
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, LOAD
TURNS ON.
2. LOAD TURNS OFF, WHEN SENSOR
TIMES OUT.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
TO ADDITIONAL SENSORS.
MAXIMUM 5 SENSORS PER SWITCHPACK.
TO ADDITIONAL SWITCHPACKS.
MAXIMUM 10 SWITCHPACKS PER SENSOR.
BLACK (COMMON)
BLUE (CONTROL)
RED (10-30 VDC)
BLACK (COMMON)
BLUE (CONTROL)
RED (15 VDC)
Standard Configuration
LOAD "B"
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
**HOT
WHITE
BLUE
SWITCH-
PACK
BLACK (COMMON)
BLUE (CONTROL)
RED (10-30VDC)
BLACK (COMMON)
BLUE (CONTROL)
RED (15 VDC)
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, LOADS
TURN ON.
2. LOADS TURN OFF, WHEN SENSOR
TIMES OUT.
3. SWITCHES CAN BE USED TO TURN
LOADS ON OR OFF.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
TO ADDITIONAL SENSORS.
MAXIMUM 5 SENSORS PER SWITCHPACK.
LOAD "A"
BLUE
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
**HOT
WHITE
BLUE
SWITCH-
PACK
BLACK (COMMON)
BLUE (CONTROL)
RED (15 VDC )
BLUE
2 Circuits, 1 Sensor
Three Way Switching
LOAD "A"
BLUE
NEUTRAL
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
**HOT
WHITE
BLUE
SWITCH-
PACK
BLACK (COMMON)
BLUE (CONTROL)
RED (10-30 VDC)
BLACK (COMMON)
BLUE (CONTROL)
RED (15 VDC)
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, LOADS
TURN ON.
2. LOADS TURN OFF, WHEN SENSOR
TIMES OUT.
3. SWITCHES CAN BE USED TO TURN
LOADS ON OR OFF.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
TO ADDITIONAL SENSORS.
MAXIMUM 5 SENSORS PER SWITCHPACK.
LOAD "B"
HOT
BLUE
NEUTRAL
HOT
**USE BLACK LEAD FOR 120 VAC.
USE ORANGE LEAD FOR 277 VAC.
CAP UNUSED LEAD.
LINE
**HOT
WHITE
BLUE
SWITCH-
PACK
BLACK (COMMON)
BLUE (CONTROL)
RED (10-30 VDC)
BLACK (COMMON)
BLUE (CONTROL)
RED (15 VDC)
AUTOMATIC MODE OPERATION:
1. WHEN SENSOR ACTIVATES, LOAD
TURNS ON.
2. LOAD TURNS OFF, WHEN SENSOR
TIMES OUT.
3. SWITCHES CAN BE USED TO TURN
LOADS ON OR OFF.
RECOMMENDED WIRE:
18-3 AWG STRANDED WIRE SHIELDED OR
NON/SHIELDED
TO ADDITIONAL SENSORS.
MAXIMUM 5 SENSORS PER SWITCHPACK.
LOAD
THREE-WAY SWITCHES
WALL BOX 1WALL BOX 2
A/B Switching
Mounting