Manual Control Unit SLVA 4Kplus Installation Directions
2016-10-27
: Pdf 609574-Installationsheet 609574-InstallationSheet B6 unilog
Open the PDF directly: View PDF
.
Page Count: 36
| Download | |
| Open PDF In Browser | View PDF |
FACTORY AUTOMATION MANUAL SLVA-4Kplus CONTROL UNIT Part No. 109008 2012-03 Date of issue With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the "Elektrotechnik und Elektroindustrie (ZVEI) e.V." including the supplementary clause: "Erweiterter Eigentumsvorbehalt". SLVA-4Kplus Control unit Table of contents 1 Intended use ............................................................................................ 6 2 Product description ................................................................................ 7 2.1 2.2 2.3 2.4 2.5 2.5.1 2.5.2 2.5.3 2.5.4 2.6 2.6.1 2.6.2 2.6.3 2.7 Product features ....................................................................................................... 7 Components of the light barrier safety system .......................................................... 7 Connections on the SLVA-4Kplus ............................................................................. 9 Fuses ...................................................................................................................... 10 Operating modes .................................................................................................... 10 Setting the operating mode ..................................................................................... 10 Start-up/restart interlock .......................................................................................... 11 Relay monitor .......................................................................................................... 11 Emergency-Stop ..................................................................................................... 12 Indicator lights ......................................................................................................... 13 Internal control unit indicator lights .......................................................................... 13 External indicator lights ........................................................................................... 13 Light barrier and light grid indicators ....................................................................... 14 Test ......................................................................................................................... 14 3 Arrangement and combination of light barriers and light grids ....... 15 4 Installation/removal of the control unit ............................................... 19 5 Installation ............................................................................................. 19 6 Commissioning ...................................................................................... 22 7 Technical data ....................................................................................... 24 Date of issue 12.3.12 Part No. 109008 5.1 5.2 5.3 5.4 5.5 5.5.1 5.5.2 5.5.3 5.5.4 6.1 6.2 6.3 6.4 6.5 6.6 6.7 7.1 7.2 7.3 7.4 SLA light barriers and SLP light grids ...................................................................... 19 Emergency-Stop circuit ........................................................................................... 19 Indicator lights ......................................................................................................... 19 Safety outputs ......................................................................................................... 20 User check lists ....................................................................................................... 20 Before installation ................................................................................................... 20 After installation ...................................................................................................... 21 Commissioning ....................................................................................................... 21 Periodic check ........................................................................................................ 21 Adjustment .............................................................................................................. 22 Checking the detection capability ........................................................................... 22 Checking the start-up/restart interlock and start-up enable ..................................... 22 Checking the test input ........................................................................................... 22 Checking the relay monitor ..................................................................................... 22 Checking the static Emergency-Stop ...................................................................... 23 Checking the pulsed Emergency-Stop .................................................................... 23 General specifications ............................................................................................ 24 Electrical data ......................................................................................................... 24 Other data ............................................................................................................... 25 Dimensions ............................................................................................................. 26 3 SLVA-4Kplus Control unit 7.5 Curves and diagrams ...............................................................................................26 8 Periodic checks ..................................................................................... 27 9 Fault elimination .................................................................................... 27 10 Circuit examples .................................................................................... 29 11 Ordering information ............................................................................. 32 12 Guarantee conditions ............................................................................ 33 13 Glossary ................................................................................................. 33 14 14.1 14.2 Standards ............................................................................................... 34 Construction and equipping of protective equipment ...............................................34 Use and installation of protective equipment ...........................................................34 Introduction! These operating instructions provide information on the intended use of the product and are intended to prevent the occurrence of dangerous situations. They must be read and applied by all persons involved in the application, installation, operation, servicing, repair and inspection of the product. This product can only fulfil the purpose for which it is intended if it is installed, operated, serviced, repaired and inspected in accordance with the information provided by Pepperl+Fuchs. The guarantee provided by Pepperl+Fuchs for this product is rendered null and void if the product is not installed, operated, serviced, repaired and inspected in accordance with the information provided by Pepperl+Fuchs. Before the selection and use of the product, an evaluation must be undertaken to determine that it is suitable for the envisaged application. Pepperl+Fuchs has no control over the selection and use of the product. Our liability is therefore restricted to the intrinsic quality of the product. The product must be regularly inspected and serviced by specialist personnel. The results of such inspections and servicing operations are to be recorded. Only original Pepperl+Fuchs parts are to be used when effecting repairs. This equipment contains assemblies that are electrostatically sensitive. Opening of the equipment for the purpose of servicing and repair work must be undertaken by specialist personnel. Electrostatic discharges due to unprotected contact with the assemblies must 4 12.3.12 The statements above do not replace the clauses relating to guarantees and liability in the Pepperl+Fuchs general terms and conditions of sale and supply. Date of issue Repair work on the product, which has not been carried out by Pepperl+Fuchs, is outside the control of Pepperl+Fuchs. Our liability is therefore restricted to those repairs that have been carried out by Pepperl+Fuchs. Part No. 109008 Modifications to the equipment or components and the use of defective or incomplete equipment or components are not permitted. Repair work on equipment or components carried out other than by Pepperl+Fuchs must only be undertaken in proper workshop facilities. Such workshop facilities are responsible for acquiring the latest technical information on the equipment and components from Pepperl+Fuchs. SLVA-4Kplus Control unit be avoided. The destruction of components caused by an electrostatic discharge will render the guarantee null and void! The right is reserved to make technical changes. Symbols In this manual important notes for operation and safety when using the control unit SLVA4Kplus are distinguished by symbols. The meaning of the symbols are: Recommendation for the user Attending these notes the insallation procedure and the use of the control unit SLVA-4Kplus will be lightened. Indication of dangerous circumstances or a direct danger. Non observance may lead to damage to property, or to severe or fatal injury. Date of issue 12.3.12 Part No. 109008 We reserve the right to alter specifications at any time and without notice. 5 SLVA-4Kplus Control unit Intended use 1 Intended use The SLVA-4K system, comprising the SLA light barriers or the SLP light grids and the control unit SLVA-4Kplus, must only be used for the intended purpose, i.e., as a non-contact electro-sensitive protection device (ESPD) for the prevention of access to danger points and areas. If the system is used for a purpose other than that intended, its function may not be guaranteed. When operating the equipment the relevant safety regulations, standards and specifications are to be observed and the specific requirements of the specific application must be considered. The SLVA-4Kplus is a control unit for a safety light barrier system with 1 to 4 single-pass light barriers of type BWS (Non-contact electro-sensitive protection device) category 4 (ISO 13849-1) and type 4 (EN 61496-1), which can be used for the prevention of access to danger points and areas. A complete light barrier safety system consists of: • 1-4 single-pass light barriers (transmitters and receivers), • the SLVA-4Kplus control unit and optionally • a 2-channel monitoring system (for example for Emergency-Stop switches) Each transmitter generates a light beam, which is detected by an associated receiver. Any interruption of the light beam is detected by the control unit, which opens the contacts of the output relay, thus in turn enabling secondary switching devices to initiate methods of preventing the danger of movement into the protected area. Date of issue 12.3.12 Part No. 109008 In constructing a BWS of type 4, only the permitted light barriers of type SLA and light grids of type SLP may be connected to SLVA-4Kplus control unit. The light barriers and light grids cannot be operated without the control unit. 6 SLVA-4Kplus Control unit Product description 2 2.1 Product description Product features • Self-monitoring • Modular construction • Monitored relay outputs (EDM, external device monitor) • Can be operated with and without start-up/restart interlock • Selectable relay monitor • Diagnostic indication for ease of fault location • Control unit to protection class IP20/NEMA 1 for installation in a control cabinet or in a housing with a protection class of at least IP54/NEMA 3 • Up to four protective beams • Red transmitted light for simple alignment • Stability control indication on the light barrier receivers and on the control unit • Monitored connection of 2-channel safety circuit (EMERGENCY-STOP circuit) 2.2 Components of the light barrier safety system The system is represented schematically in figure 2.1 and figure 2.2. The control unit generates the required supply voltages for the light barriers. The control electronics drives the light barrier transmitters and evaluates the signals coming from the receivers. A safetyaligned microprocessor control permanently monitors the light barrier functions. Two positive-action relays provide the switch-off signal when a light beam is broken. The switching time of the relays is monitored to ensure that the maximum switching time is not exceeded. The SLVA-4Kplus can be used in various operating modes, i.e. the functions: • Start-up/Restart interlock • Relay monitor • Monitoring of 2-channel safety circuits. These can also be activated by the user, either singly, or in combination. Signal outputs for the conditions: • Ready for start/fault condition • Safety outputs switched-off enable a system message to be provided to a location appropriate to the respective safety device. Date of issue 12.3.12 Part No. 109008 • Safety outputs switched-on 7 SLVA-4Kplus Control unit Product description Voltage supply OSSD-outputs Status signals Test input Transmitter 1 Receiver 1 Transmitter 2 Receiver 2 Channel 3 Transmitter 3 Receiver 3 Channel 4 Transmitter 4 Receiver 4 Channel 1 SLVA-4Kplus Channel 2 Restart input Fig. 2.1: Light barrier safety system with SLVA-4Kplus Voltage supply OSSD-outputs Status signals Test input Channel 1 SLVA-4Kplus Channel 2 Transmitter 1 Receiver 1 Transmitter 2 Receiver 2 Channel 3 Channel 4 Restart input Light barrier safety system with EMERGENCY-STOP switch Date of issue 12.3.12 Part No. 109008 Fig. 2.2: 8 SLVA-4Kplus Control unit Product description 2.3 Connections on the SLVA-4Kplus The connection of the light barriers and light grids to the control unit is by means of terminals. The control unit connections are shown in figure 2.3. + red - green 1 2 TEST 3 4 RESTART 5 6 GN RD 7 8 24V 9 R1 10 11 R2 12 13 14 15 16 24V R3 R4 C YE OSSDs ON OFF 12345678 OSSD1 OSSD2 RELAY MONITOR POWER 17 18 19 20 21 24 V AC/DC Version -2528 24 V AC 115 V AC 230 V AC Date of issue 12.3.12 Part No. 109008 Fig. 2.3: 22 23 24 T1 25 T2 26 27 T3 28 29 T4 30 31 32 N.C. contact ext. relay Control unit connections Terminal Function 1-2 Normally-open contact for test and fault elimination; has to be closed, unless the test or fault elimination is started by switching the power supply off and then on again - see section 9. 3-4 Normally-open contact for start-up/restart enable; has to be closed. The contact remains open when the control unit is operating in the mode without a start-up/restart inhibit. 5-6 Direct connection of LED for indication of output relay status (Optionally available with relay contacts) - see section 2.6.2. 7-14 Connections for light barrier receiver, or the Emergency-Stop circuits - see section 5. 15-16 Connection for start-up readiness/fault status indicator light - see section 2.6.2. 17-18 Power supply connection: Arbitrary polarity for direct voltage supply. 19-22 Safety relay switch outputs (OSSD), zero potential contacts for machine control. 23-24 Relay monitor: Only connected when the function relay monitor is used see section 2.5.3. 25-32 Connections for light barrier transmitter - see section 5. Table 2.1: Terminal assignment 9 SLVA-4Kplus Control unit Product description 2.4 Fuses The OSSD control unit outputs are fused. Before replacing a fuse, the control unit must be isolated from the power supply. All fuses are located inside the control unit and are not accessible from outside. In order to replace a fuse, the lower terminal strip must be removed. Output Switch output, N.O. 1 (19-20) Switch output, N.O. 2 (21-22) Value T 2,0 A T 2,0 A Plan view Left Right, adjacent Table 2.2: Fuse assignment and values. 2.5 Operating modes 2.5.1 Setting the operating mode The operating mode is factory-set to match the order code. However, the user can change the operating mode. Following a change in the operating mode, the selected setting must always be checked for correct operation before the system is enabled. On the SLVA-4Kplus the operating mode is set by means of DIP switches. The DIP switches are accessed by removing the transparent cover from the top of the control unit. For each setting, two DIP switches are set at the stated positions. 2+6 3+7 4+8 Operating mode without start-up/restart interlock with start-up/restart interlock without relay monitor (EDM) with relay monitor (EDM) Light barriers on channels 3 and 4 Emergency-Stop on channels 3 and 4 Emergency-Stop static Emergency-Stop pulsed Table 2.3: DIP switches In order to set the DIP switches, a suitable screwdriver is used to remove the transparent cover. The cover is replaced after setting the switches. If the DIP switches are actuated during operation, the control unit switches to the safe condition (Outputs switched-off) and the 7-segment indicator displays a P. In addition, output 15/16 flashes (Ready for startup). 10 12.3.12 1 +5 Position OFF ON OFF ON OFF ON OFF ON Date of issue Switch Part No. 109008 The table shows the operating modes that can be selected. SLVA-4Kplus Control unit Product description The safety device must be checked after every change of the DIP switch settings (see Section 6). Changes to the settings in accordance with table 2.3 must be marked in the appropriate boxes on the type label. 2.5.2 Start-up/restart interlock The start-up/restart interlock prevents the dangerous motion from switching on again of its own accord after the protected area has been entered. The switch for the start-up/restart inhibit should be located such that it can be seen from the area of danger and yet it is not possible for it to be actuated from within this area. In order to switch the plant/machinery on again, the start-up/restart enable (Terminals 34) must be actuated for 0.05 s ... 1 s. The dynamic enable serves to provide protection against static faults in the start-up enable circuit. The devices are supplied with on or off-switched start-up/restart inhibit. The product type plate is marked to identify this feature. Any change made to this setting using the DIP switches must be marked in the appropriate fields on the product type plate. 2.5.3 Relay monitor The relay monitor provides a monitoring function via the SLVA-4Kplus for externally connected relays (or protection devices / contactors). The wiring of the relay monitor is illustrated in figure 2.4. Any number of normally-closed contacts of any number of relays can be connected in series. In the figure, K1 and K2 are positive-action relays. The normally-closed contacts K1K and K2K (control contacts) must ensure a secure contact at 24 V / 5 mA. Attachable auxiliary contacts or the contacts of auxiliary relays normally satisfy this requirement. Date of issue 12.3.12 Part No. 109008 A surge withstand capability of 6 kV between the control contacts and other contacts, which carry critical voltages, must be guaranteed by the relay manufacturer. The relay operating circuit must be protected with a fuse having a maximum nominal value of 60 % of the load rating of the relay contacts, in order to prevent welding of the contacts. The relays are monitored with a delay of 200 ms after the switching operation. If the new switching state has not been achieved after 200 ms, the SLVA-4Kplus assumes an inhibit state and fault F is indicated on the diagnostic display. The devices are supplied with either a connect or disconnect relay monitor. This function is indicated on the type label. Any modification to this setting using the DIP switches must be marked in the appropriate box on the type label. 11 SLVA-4Kplus Control unit Product description SLVA-4Kplus 5 19 6 21 7 20 8 22 3 23 9 24 K1K K2K K1 Fig. 2.4: K2 Relay monitor 2.5.4 Emergency-Stop In the Emergency-Stop operating mode, the two channels of an Emergency-Stop circuit are connected in place of the light barriers 3 and 4. There are two versions of this arrangement: 1. Static operation: Both channels switch the 24 V static voltage to the receiver inputs of light barriers 3 and 4. Due to the resulting loss of the cross-circuit monitoring, the two channels of the Emergency-Stop circuit must either be laid in separate cables or in a common mechanically-protected cable. The current loading of the Emergency-Stop circuit is approx. 10 mA. 2. Pulse operation: The two channels switch a connection between the transmitter outputs of light barriers 3 and 4, on the one hand, and on the other hand between the receiver inputs of light barriers 3 and 4. Due to the existing short-circuit and cross-circuit monitoring, the protected laying of the Emergency-Stop circuit is not necessary. The mean current loading of the Emergency-Stop circuit is very low, so that the Emergency-Stop switches that are used for zero-current switching are suitable. Date of issue 12.3.12 The Emergency-Stop would also function in the DIP switch settings XX00 XX00 and XX01 XX01, however, in this case there is no simultaneity monitoring (not permissible)! Therefore, if a pulsed Emergency-Stop is used, care must be taken to ensure that the DIP switches remain in the settings XX11 XX11! Part No. 109008 If Emergency-Stop switches are attached, the start up/restart interlock mode must be activated to prevent a start up/restart, when unlocking the Emergency-Stop switches (EN 418). 12 SLVA-4Kplus Control unit Product description 2.6 Indicator lights 2.6.1 Internal control unit indicator lights The functions of the control unit indicator lights are shown in table 2.4. The digital display indicates the operating and fault conditions of the BWS (see Section 9). A fault condition is indicated when the decimal point on the 7 segment display flashes. The LEDs R1-R4 (yellow) indicate the reception status of the connected light barriers or of the connected Emergency-Stop circuit. The OSSD LED (ON = green, OFF = red) indicates the status of the safety outputs (OSSDs). LED red green yellow 7-Segment indicator OSSD outputs OFF OSSD outputs ON Indicator for channels (1-4) On = Light beam free or Emerg.-Stop On Flashing = Light beam free, stability control inadequate Off = Light beam broken or Emerg.-Stop circuit switched off Protected area clear, OSSD ON (Run light) (symbol elements light in turn, clockwise) Protected area obstructed Protected area clear, OSSD OFF, Ready for start-up System fault DIP switch setting incorrect Short-circuit, transmitter connection Fault, simultaneity condition Emergency-Stop channel Date of issue 12.3.12 Part No. 109008 Fault in an external relay DIP switches being set Table 2.4: Control unit indicator lights 2.6.2 External indicator lights The external indicator lights have to be connected to the control unit by the operator. These are not included in the delivery package. The external start-up readiness indicator light must be clearly visible. 13 SLVA-4Kplus Control unit Product description Start-up readiness indicator light: • Installation - see Section 5 • ON status (yellow): System waiting to be enabled • OFF status: protected area clear, OSSD On or protected area obstructed, OSSD Off • Status indicator flashing: Control unit in the fault condition or operating mode is set. • see Section 7.1 for connection values, indicator outputs. Indicator light for the output relay: 2 indications, red and green, for the output relay status (OSSD). Standard version with direct LED control, optional relay output with changeover contact (Centre contact on terminal 15). • • • • For installation, see Section 5. ON status (green): Output relay On ON status (red): Output relay Off See Section 7.1 for connection values, indicator outputs. 2.6.3 Light barrier and light grid indicators Each receiver has an LED that signals the receiver status. Indications are given of light beam broken (Indicator dark) and light beam unbroken. Incorrect alignment of the light barrier is also indicated. Type SLA5 SLA5S SLA20 SLA25 SLA40 SLP red yellow not avail- dark able lit dark green dark dark lit dark not available flashing lit SLA28 lit dark flashing lit dark dark dark lit dark Meaning Light beam broken Light beam unbroken, stability control inadequate Light beam unbroken Light beam broken Light beam unbroken, stability control inadequate Light beam unbroken The SLP has an additional red LED, near the connector cap, as a power supply indicator. Light beam broken Light beam unbroken, stability control inadequate Light beam unbroken The input test causes the system to execute a system reset, followed by a restart. The complete switching system is tested, including the safety outputs. The same effect is achieved if the power supply is switched off for at least 1s. The wiring of the connection is not absolutely necessary. The system reset is used to accept failure conditions on the unit and to check the switching capability of the safety outputs. 14 12.3.12 Test Date of issue 2.7 Part No. 109008 Table 2.5: Light barrier indicator lights SLVA-4Kplus Control unit Arrangement and combination of light barriers and light grids 3 Arrangement and combination of light barriers and light grids Light barriers of the SLA type and light grids of the type SLP are through beam photoelectric sensors, generally consisting of a transmitter and a receiver. Together with the SLVA4-Kplus control unit they form a BWS of Type 4 (EN 61496-1) or Category 4 (ISO 13849-1). Up to 4 light barriers or light beams can be connected to one control unit. SLA light barriers and SLP light grids connected to the same control unit do not subject one another to mutual interference. Light barriers and grids that are connected to different control units should be arranged such that the transmitters of one group of light barriers do not irradiate the receivers of the other group of light barriers, so that mutual interference is avoided. Light barriers type SLA and SLP light grids that are approved for connection to SLVA system control units can be mixed arbitrarily, provided that the transmitters and receivers are of the same type. Further data can be obtained from the respective technical information on the light barriers and light grids. The SLA light barriers and SLP light grids must only be connected to control units in the SLVA family. In addition to the differences in range and housing construction, the light barriers and light grids also differ in respect of their electrical connections. The light barriers have either a fixed cable connection, a plug connection or are provided with a terminal compartment, into which the user inserts and attaches the cable connections. The connections that have to be made are shown in figure 3.1 and figure 3.2. The SLP light grids are fitted with a terminal compartment. Date of issue 12.3.12 Part No. 109008 The SLP light grids are suitable for access security functions with 2-4 protective beams. The distances between the protective beams are as prescribed in ISO 13855. The wiring between the control unit and the transmitter/receiver is shown in Figure 6. 15 SLVA-4Kplus Control unit Arrangement and combination of light barriers and light grids 3 1 2 3 TEST 4 RESTART 5 6 GN RD 7 8 9 10 24V R1 R2 11 12 13 14 24V R3 R4 OSSDs 16 C YE 4 4 1 3 4 1 3 4 1 Receiver Receiver OSSD1 18 19 OSSD2 20 21 RELAY MONITOR T1 22 23 24 T2 25 26 T3 27 28 Transmitter 4 Transmitter 3 Transmitter 2 Transmitter 1 T4 29 30 31 32 4 3 Fig. 3.1: 2 TEST 3 4 RESTART 4 3 4 3 4 3 Connection of light barriers with terminal compartment connections (e.g. SLA28) and with plug connection (e.g. SLA5(s)/92, SLA40/92 SLA28/104). Caution: On transmitter type SLA20, connect terminal 2 in place of terminal 4. 5 6 GN RD 7 8 9 10 24V R1 R2 11 12 13 14 15 16 24V R3 R4 C YE OSSDs BU BK BN BU BK BN BU BK BN BU BK BN Receiver Receiver Receiver Receiver Transmitter 4 Transmitter 3 Transmitter 2 Transmitter 1 12345678 SLVA-4Kplus ON OFF POWER 17 3 Receiver SLVA-4Kplus ON OFF 1 1 Receiver 12345678 POWER 17 15 18 OSSD1 19 20 OSSD2 21 22 RELAY MONITOR T1 23 24 25 T2 26 27 T3 28 29 T4 30 31 32 BK BU BK BU BK BU BK BK=black, BU=blue, BN=brown Connection of light barriers with fixed cable (e.g. SLA5(S), SLA40) Date of issue Fig. 3.2: 12.3.12 Part No. 109008 BU 16 SLVA-4Kplus Control unit Arrangement and combination of light barriers and light grids GN R4 R3 R2 R1 + U 1 2 TEST 3 4 RESTART 5 6 GN RD 7 8 9 10 24V R1 R2 11 12 13 14 15 16 24V R3 R4 C YE OSSDs 12345678 SLVA-4Kplus ON OFF OSSD1 17 SLP-Receiver 18 19 20 OSSD2 21 RELAY MONITOR T1 22 23 24 25 T2 26 27 T3 28 29 SLP-Emitter T4 30 31 32 GN Fig. 3.3: T4 T3 T2 T1 Connection of SLP light grid The light barriers must be installed in such a way, that it is not possible to gain access to the danger area by by-passing the light barrier. In other words, it must not be possible to: • Crawl under the lowest beam. • Reach over the highest beam. • Step through between two beams. Part No. 109008 Danger area Minimum distance S Date of issue 12.3.12 Transmitter SLA (SLP) Receiver SLA (SLP) Protected area Fig. 3.4: Minimum distance, protective beam(s) The light barriers should be installed in such a way that they can be adjusted. 17 SLVA-4Kplus Control unit Arrangement and combination of light barriers and light grids Calculation of the minimum distance from the danger area is in accordance with the relevant specifications and standards. In accordance with ISO 13855, the minimum distance is calculated from the formula: S=K·T+C where: S = Minimum safety distance in mm (Separation between the boundary of the danger area and the boundary of the protected area) K = Approach speed constant in mm/s T = Total response time in s, T=t1+t2 t1 = Response time of the protective device (40 ms) t2 = Response time of the machine C = Additional distance in mm. This distance depends on how far a person can enter into the danger area before the safety device is actuated. For access security: S = K · T + 850 mm In accordance with ISO 13855, the following heights are recommended for the individual beams: No. of beams 2 3 4 Height above the reference plane (mm) 400, 900 300, 700, 1100 300, 600, 900, 1200 Table 3.1: Installation heights Care should be taken that there are no reflecting objects within the transmitter or receiver lobes, which could cause reflections around an obstacle (see EN 61496-1). Reflecting object outside of the light beams area Minimum distance a 5˚ Transmitter Receiver Part No. 109008 5˚ Reflection around obstacle Date of issue Fig. 3.5: 12.3.12 Obstacle 18 SLVA-4Kplus Control unit Installation/removal of the control unit 4 Installation/removal of the control unit In order to install the control unit, a standard 35 mm rail to DIN EN 50022-35 is fixed to the base on which the installation is to be made. A plastic profile and spring-loaded latching device are provided on the underside of the control unit. The control unit is positioned with its underside on one edge of the standard rail and then pushed on to the latching device. To remove the control unit, the latching device is pulled back with a screwdriver to allow the unit to be extracted. Sufficient space must be allowed above the screw terminals to enable a screwdriver to be inserted. 5 Installation 5.1 SLA light barriers and SLP light grids The transmitters are connected to terminal pairs 25-26 (S1), 27-28 (S2), 29-30 (S3) and 31-32 (S4) in accordance with the colour coding. Likewise, the receivers are connected to terminals 7-8-9 (E1), 7-8-10 (E2), 11-12-13 (E3) and 11-12-14 (E4) in accordance with the colour coding. The length of the connection cable between the light barriers and the control unit must not exceed 50 m. The cable for connecting the light barriers is specified in Section 7.2. If less than 4 light barrier channels are to be operated, the channel that is not used must be replaced by a jumper, for which a length of up to 3 m is permissible. Light barrier channel to be replaced 1 2 3 4 Jumper between 25-9 27-10 29-13 31-14 Table 5.1: Jumpering of unused light barrier channels 5.2 Emergency-Stop circuit For Emergency-Stop operation, the Emergency-Stop circuit is to be connected to the control unit in accordance with figure 10.1 or figure 10.3. Date of issue 12.3.12 Part No. 109008 In the case of a static Emergency-Stop, the cabling of the EmergencyStop circuit is to be provided with protection. 5.3 Indicator lights A green/red indicator light is to be connected to the output 5/6. The output is to be laid out so that an anti-parallel circuit for a green and a red LED can be connected without series resistors, in which a current of approx. 9 mA flows. Appropriate circuitry must be provided if heavier current indicator lights are required. The output data is provided in section 7.1. For operation with a start-up interlock (Restart), an easily visible yellow indicator light must 19 SLVA-4Kplus Control unit Installation be connected to output 15/16. This indicator light signals to the operator that the start-up enable has to be activated to switch the system on. It is a zero-potential output, therefore the indicator light must be supplied from an external power source. In the SLVA-4KPlus-2528 option, the output 5/6 is controlled by a relay, whose common contact is connected to terminal 15, so that heavier current indicator lights can be connected. The circuit is illustrated in figure 10.4. The indicator light circuits are protected internally by a 2.5 A automatic fuse that can be reset. 5.4 Safety outputs The safety outputs (OSSDs) 19-22 are zero-potential, normally-open contacts, without cross-circuit monitoring. Connection to the system is achieved with a protected cable or to protect from short circuit by an apropriate wiring. The withstand voltage must be adequate to provide safe isolation. In the case of an inductive load, the output contacts must be protected against the increased loading by RC combinations or free-wheeling diodes. The circuitry must be provided by the user. Note that when using free-wheeling diodes, the contact release time of the connected relays or contactors should be increased. If DC loads are switched with the outputs, the permissible switching capacity stated in section 7 should be noted. When interconnecting the control unit in the machine safety control system, the factors considered should take account of the instructions in EN 61496-1 (Interface connection of the BWS series-connected control elements). 5.5 User check lists 5.5.1 Before installation • Have the related standards been taken into account? (See Section 14) • Are the SLVA4-Kplus control unit and the light barriers/light grids of the prescribed type available in the appropriate quantities? • Are jumper cables available for the unused channels? • Is the SLVA4-Kplus suitable for the required operating voltage (Note type label)? • Will the SLVA4-Kplus be installed into a control cabinet or built into a housing with a protection class of at least IP54/NEMA 3? • In the case of a relay monitor: Is the necessary safe isolation between the normally closed control contact and other contacts, in accordance with overvoltage category 4 (EN 50178), guaranteed by the relay or contactor manufacturer? 20 12.3.12 • Is there sufficient space above the screw terminals of the SLVA4-Kplus for installation and removal? Date of issue • Has the control unit been supplied with the correct setting for start-up/restart interlock and relay monitor (see type label)? Part No. 109008 • Has the overvoltage category required in accordance with EN 50178 been achieved in respect of voltages from the output connections and power supply connections to other connections? SLVA-4Kplus Control unit Installation 5.5.2 After installation • Are all the light barriers/light grids correctly connected? • Have the unused channels been bridged? • Is there a red/green LED in a visible position to indicate the status of the outputs, or has the prescribed red/green indicator light been provided by an alternative means? • For start-up/restart interlock: - Is the restart input connected? - Is the test input connected? - Is there a clearly visible yellow indicator light to signal start-up readiness? • For relay monitor: - Is the relay monitor input connected to at least 2 positive-action N.C. relays in series? - Are the operating contacts of the external relays protected against contact welding by a suitable fuse? • Are the light barriers arranged in such a way that it is not possible to access the danger area by avoiding them? • Have the light barriers been adjusted? • Emergency-Stop circuit, static operation: Has attention been paid to the fact that the cable between the Emergency-Stop switch and the switching device must be protected, or that the two Emergency-Stop channels must be laid in separate cables? • Emergency-Stop circuits, pulse operation: Has attention been paid to the fact that the Emergency-Stop switch must be suitable for switching smaller loads (see Section 7.1)? 5.5.3 Commissioning • Has each beam of the safety device been checked after installation for effective detection, using a test piece of the prescribed diameter? • Has the start-up/restart interlock (if activated) been checked for correct function? • In case of attached Emergency-Stop-switches, is the start-up/restart interlock mode activated? • Has the relay monitor (if activated) been checked for correct function? • Have the Emergency-Stop circuits (if activated) been checked for correct function? • Has the set operating mode been entered on the supplementary label? • Is the protected area penetrated at least once each day of operation, the system switched on and the contact test/fault enable activated? • Is the effectiveness of the Emergency-Stop circuits checked at the prescribed distances? Date of issue 12.3.12 Part No. 109008 5.5.4 Periodic check 21 SLVA-4Kplus Control unit Commissioning 6 Commissioning After the installation of the system, commissioning is initiated by switching on the power supply. 6.1 Adjustment Adjustment is simplified by the visible red light of the light barrier transmitter. The adjustment commences at the transmitter: The transmitter light spot is adjusted to the position occupied by the receiver. In executing this, the visible red light is either observed directly at the receiver by looking into the transmitter (not dangerous!) or after positioning a retroreflector at the position of the receiver, observed from the transmitter side. It should be noted that the eye must be positioned close to the light beam axis. If this is not possible, a deflecting mirror can be used as an aid in making the adjustment. After adjusting the transmitter, the receiver is adjusted such that its indicator lights signal unbroken light beams with adequate stability control (see section 2.6.3). 6.2 Checking the detection capability • Remove all objects from the paths of the beams. • Using the test rod prescribed for the light barriers, break the light beams one after the other. • Ascertain whether the output relays switch off as required and the output relay indicator changes from green to red. Also check that the broken beam is indicated at the control unit by the extinguishing of the associated reception indicator on the control unit. 6.3 Checking the start-up/restart interlock and start-up enable • Break one beam and then leave all the beams unobstructed. • The output relays must remain inhibited, due to the existing start-up interlock and the yellow start-up readiness indicator light must come on. • Operate the restart button. • The output relays must switch-on and the start-up readiness indicator must go out. 6.4 Checking the test input • Remove all objects from the light beam paths. • If a start-up interlock is in effect, operate the start-up enable. • The output relays must switch-on. • The output relays must switch-off during the actuation. 6.5 Checking the relay monitor • Disconnect the leads from connections 23 or 24. Part No. 109008 • Actuate Test. • Reconnect the leads. 22 Date of issue • Note the SLVA4-Kplus digital indicator. If .F is displayed, the relay monitor is active. 12.3.12 • Switch on the SLVA4-Kplus. SLVA-4Kplus Control unit Commissioning 6.6 Checking the static Emergency-Stop Switch on all Emergency-Stop switches, make sure all the light beams are unobstructed and enable the start-up. The safety outputs must then be in the switched-on state. Operate an Emergency-Stop switch. The safety outputs must then be in the switched-off state and the control unit digital indicator must not display a fault. This check must be repeated for all Emergency-Stop switches on the Emergency-Stop circuit. 6.7 Checking the pulsed Emergency-Stop The check is carried out in the same way as for the static Emergency-Stop. Date of issue 12.3.12 Part No. 109008 For the pulsed Emergency-Stop an additional check must be made to ensure that the DIP switches occupy the positions XX11 XX11! 23 SLVA-4Kplus Control unit Technical data 7 Technical data 7.1 General specifications Approvals Tests Safety type Performance Level Safety Integrity Level (SIL) Category Marking 7.2 TÜV, cNRTLus EN IEC 61496; EN ISO 13849; EN 55022 The specified standards refer on the respective current version of the normative documents 4 (EN IEC 61496) PL e (EN ISO 13849) SIL 3 (EN IEC 61508) Cat. 4 (EN ISO 13849) CE Electrical data Supply voltage: 230 VAC version: 115 VAC version: 24 VDC version: 24 V AC/DC version, option 2528 Current consumption: 230 V AC (-15%, +10%), 48 Hz ... 62 Hz 115 V AC (-15%, +10%), 48 Hz ... 62 Hz 24 V DC (-15%, +15%) 24 V AC/DC (-10%, +10%) 230 VAC version: 115 VAC version: 24 VDC version: 24 V AC/DC version, option 2528 Power consumption: 50 mA 100 mA 220 mA 220 mA 230 VAC version: 115 VAC version: 24 VDC version: 24 V AC/DC version, option 2528 Rating: 13 W 13 W 7W 7W 230 VAC version: 115 VAC version: 24 VDC version: 24 V AC/DC version, option 2528 Response time: Activation current and voltage for potentialfree control contacts Activation time for start-up enable(restart) and error enable (reset) Relay monitor: Switching voltage: Switching current: Detection of maloperation: Emergency-Stop circuits: II (IEC 61140) II (IEC 61140) III (IEC 61140) III (IEC 61140) 40 ms 8 mA / 24 V 24 24 V DC continuous or 12 V DC pulsed operation 10 mA 2 s after switch over Part No. 109008 12.3.12 Actuation current: Indication of maloperation: 24 V DC 10 mA 200 ms after switch over Date of issue Switching voltage: 0.05 s .... 1 s SLVA-4Kplus Control unit Technical data OSSD-outputs, isolated relays outputs at clamps 19 to 21: Switching voltage AC/DC: Switching current AC: Switching current DC: Switching frequency: fusing: Outputs for indicators: Output for indicator "OSSD", isolated relays outputs between clamps 5 and 6, option 2528 only Switching voltage AC/DC: Switching current AC: fusing: notice: Outputs for LED-indicators between clamps 5 and 6 Voltage: Current: 7.3 20 V AC/DC ... 230 V AC/DC 0.01 A ... 2 A see load limit curve Maximum 1/s fuse T2A 24 V AC/DC 0.01 A ... 1.5 A Polyfuse (re-settable) Supply via clamp 15 max. 5 V max. 10 mA Other data Ambient conditions: Operating temperature: Storage temperature: rel humidity, uncondensed: Wiring: connection: conductor cross section: Weight: Housing material: Protection class: notice Length of the connection cable: terminal clamps with terminal screws litz wire with sleeve, max. 1.5 mm² 900 g Polycarbonate / UL-94 V-0 IP 20 / NEMA 1 mounting in a switch cabinet or enclosure with rating IP54/NEMA 3 or better is demanded max. 50 m max. 100 m Date of issue 12.3.12 Part No. 109008 between control unit and light barriers: between control unit and system: 0 ºC ... 50 ºC -20 ºC ... 75 ºC max. 95 % (at temperatures between 20 °C and 50 °C) 25 SLVA-4Kplus Control unit Technical data 7.4 Dimensions 70 152 73.2 118.2 Fig. 7.1: 7.5 Dimensions Curves and diagrams Current [A] 8 6 4 3 2 1 0.8 0.6 0.4 0.3 0.2 2 0 50 100 150 200 250 Voltage [V DC] 1) inductive load, L/R = 40 ms 2) ohmic load Load limit curves with direct current across the outputs Date of issue Fig. 7.2: 12.3.12 0.1 Part No. 109008 1 26 SLVA-4Kplus Control unit Periodic checks 8 Periodic checks The periodic check is a check of the output relay. This must be carried out if there is uncertainty that - Penetration of the protected area takes place at least once daily - Or that the device is not switched-on once per operating day. The check is carried out as follows: 1. Clear the protected area and enable start-up. 2. Penetrate the protected area by breaking any one beam and observe the indicator on the control unit or the external indicator light. These must change from green to red. 3. If the BWS does not enter a fault condition, the check is complete. If a fault condition is indicated, the fault must be eliminated and the check repeated. 9 Fault elimination In all cases, faults in the system cause the system to switch to the safe condition. Most faults cause the system to enter a fault condition, which is identified by a fault code to assist in isolating the fault. Output 15/16 generates a clock signal of approx. 1 Hz when the system enters a fault condition. This signal can be used to provide a fault indication remote from the control unit. Several faults, which have their origin outside the control unit, do not generate a fault indication. If a fault occurs, the operator activates the fault enable and then checks whether the system runs again. If the system does not restart, an attempt should be made to return to normal operation by switching the power supply off and then on again. Under high-frequency fields which exceed a field strength of 10 V/m, the outputs of the SLVA-4Kplus may switch to the safe state. Date of issue 12.3.12 Part No. 109008 The following table lists a number of fault situations in which self-help is possible. 27 SLVA-4Kplus Control unit Fault elimination Fault No indicator lights come on any of the components in the system. External protected area indicator (5-6) does not light. Start-up readiness indicator (1516) does not operate. Start-up enable does not function. Operator action Check power supply. Check installation and indicator lights. Check installation. Check whether the indicator lights E1-E4 light. If they do not, then a beam has been interrupted. If the start-up readiness indicator is indicating, the restart input connection should be checked. Fault 2 is indicated. Check the transmitter installation. Fault F is indicated. Check relay; check connection between relay and relay monitor. The protected area is not clear: 0 is Check on the control unit (E1-E4) to see if a indicated. beam is broken. Readjust if necessary. Emergency-Stop operating mode activated: Emergency-Stop circuit is open, or pulse operation is wired-in and static Emergency-Stop selected via operating mode. The beam is still not clear after Check receiver installation. adjustment. One output cannot be switched. Check the fuses on terminals 20-21 and 22-23 with start-up enabled and replace if necessary. Check installation. Fault E is indicated. Either short-circuit of a receiver to +UB or interference from another light barrier. Fault E is indicated/EmergencyThe Emergency-Stop operating mode is wired-in, Stop operating mode set but pulse operation is selected via the operating mode setting. Fault E is indicated Internal fault. Switch-off and then on again or activate test. If there is no short-circuit on the receiver leads, send the unit for repair. Date of issue 12.3.12 Part No. 109008 Table 9.1: Fault elimination 28 Date of issue 12.3.12 Part No. 109008 K1G Power contactor Fig. 10.1: K2G Indicator circuit contacts K1B K2B Make contacts 1 2 3 4 5 6 7 bk bu bk bu bk bu bk in GND in GND in GND in bu GND bn +24 V bk out bu GND bn +24 V bk out bu GND bn +24 V bk out bu GND bn +24 V bk out 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Restart GND Operating voltage +24V out Operating voltage Test OSSD1 +24V out OSSD1 Start- up enable OSSD2 Indicator gn OSSD2 Indicator rd +24V out GND out Relay monitor +24V out Sender 1 Receiver 1 GND out Receiver 2 Transmitter 2 GND out GND out +24V out Transmitter 3 Receiver 3 GND out Receiver 4 Transmitter 4 Start- up readyness GND out Start- up readyness 10 bu 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 SLVA-4Kplus Control unit Circuit examples Circuit examples The figure 10.1 shows a circuit with 4 light barriers, start-up/restart interlock and relay monitor. In this example, the SLA5 is used as a light barrier. The DIP switches are set to 1100 1100. gn rd ye Test SLA5-R SLA5-T K1A Power contactor K2A ON 8 Power circuit Connection schematic for operation with 4 light barriers, start-up /restart inhibit and relay monitor. 29 Date of issue 12.3.12 Part No. 109008 The circuitry for connections 20-25 is not shown in this diagram Fig. 10.2: 30 1 2 3 4 5 6 7 bk bu bk in GND in bu GND bn +24 V bk out bu GND bn +24 V bk out 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Restart GND Operating voltage +24V out Operating voltage Test OSSD1 +24V out OSSD1 Start- up enable OSSD2 Indicator gn OSSD2 Indicator rd +24V out GND out Relay monitor +24V out Transmitter 1 Receiver 1 GND out Receiver 2 Transmitter 2 GND out GND out +24V out Transmitter 3 Receiver 3 GND out Receiver 4 Transmitter 4 Start- up readyness GND out Start- up readyness rd bu 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 SLVA-4Kplus Control unit Circuit examples The figure 10.1 shows a connection schematic for a static Emergency-Stop. In this scheme, the Emergency-Stop cable must be protected. The DIP switches are set to XX10 XX10. gn EMERGENCYSTOP Test ye SLA5-R SLA5-T ON 8 Connection schematic for operation with 2 light barriers and static Emergency-Stop. SLVA-4Kplus Control unit Circuit examples The figure 10.3 shows a connection schematic for a pulsed Emergency-Stop. In this scheme, mechanical protection of the Emergency-Stop cable is not necessary. The Emergency-Stop switch must be suitable for the switching of low currents. The DIP switches are set to XX11 XX11. The pulsed Emergency-Stop likewise functions in the DIP switch settings XX00 XX00 and XX01 XX01. However, simultaneity of the channels is not monitored. Therefore a short-circuit in one channel is then not covered, e.g. from SLVA4-Kplus connection15 to SLVA4-Kplus connection 31! gn rd ye Restart The circuitry for connections 20-25 is not shown in this diagram bu GND bn +24 V bk out SLA5-R 1 2 3 4 5 7 in GND 6 bk bu in bk bu GND SLA5-T 8 ON Connection schematic for operation with 2 light barriers and pulsed Emergency-Stop. Date of issue 12.3.12 Part No. 109008 Fig. 10.3: bu GND bn +24 V bk out EMERGENCYSTOP 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Operating voltage +24V out Operating voltage Test OSSD1 +24V out OSSD1 Start- up enable OSSD2 Indicator gn OSSD2 Indicator rd +24V out GND out Relay monitor +24V out Transmitter 1 Receiver 1 GND out Receiver 2 Transmitter 2 GND out GND out +24V out Transmitter 3 Receiver 3 GND out Receiver 4 Transmitter 4 Start- up readyness GND out Start- up readyness 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Test 31 SLVA-4Kplus Control unit Ordering information The figure 10.4 shows a connection schematic for the SLVA4-Kplus 2528, that has a relay output in place of the LED control circuit. Other details have been omitted. rd ye 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Operating voltage +24V out Operating voltage Test OSSD1 +24V out OSSD1 Start- up enable OSSD2 Indicator gn OSSD2 Indicator rd +24V out GND out Relay monitor +24V out Transmitter 1 Receiver 1 GND out Receiver 2 Transmitter 2 GND out GND out +24V out Transmitter 3 Receiver 3 GND out Receiver 4 Transmitter 4 Start- up readyness GND out Start- up readyness 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 gn Fig. 10.4: 11 Connection schematic for the SLVA4-Kplus 2528 Ordering information SLVA4-Kplus Power supply Order numbers AWS RM AWS & RM 24 V DC SLVA-4Kplus 24VDC SLVA-4Kplus 24VDC-RI SLVA-4Kplus 24VDC-RM SLVA-4Kplus 24VDC-RI,RM 115 V AC SLVA-4Kplus 115VAC SLVA-4Kplus 115VAC-RI SLVA-4Kplus 115VAC-RM SLVA-4Kplus 115VAC-RI,RM 230 V AC SLVA-4Kplus 230VAC SLVA-4Kplus 230VAC-RI SLVA-4Kplus 230VAC-RM SLVA-4Kplus 230VAC-RI,RM Date of issue 12.3.12 Part No. 109008 Without AWS & RM 32 SLVA-4Kplus Control unit Guarantee conditions SLVA-4KPlus-2528 Version with relay contacts for OSSD indication in place of LED initiation (Terminals 5, 6 and 15)) Power supply Order numbers 24 V AC/DC SLVA-4Kplus-2528 24VAC/DC 115 V AC SLVA-4Kplus-2528 115VAC 230 V AC SLVA-4Kplus-2528 230VAC The operating modes AWS, RM and Emergency-Stop channels have to be set by the user. The factory setting on delivery is AWS switched-on. 12 Guarantee conditions The guarantee period for the SLVA4-Kplus control unit is 12 months, in accordance with the general conditions of supply of the ZVEI. Repairs must only be carried out by the manufacturer. Interference or modification of the unit is not permitted. Such action will lead to invalidation of the guarantee. Glossary OSSD Output signal switching device BWS Non tactile protection device AWS Start-up/restart interlock RM Relay monitor Date of issue 12.3.12 Part No. 109008 13 33 SLVA-4Kplus Control unit Standards 14 Standards The relevant laws and standards apply to the use of photoelectric protective devices. There are differences depending on the area of use. The following regulations are relevant within the EU and Germany. 14.1 Construction and equipping of protective equipment IEC 61496-1 Safety of machinery. Electro-sensitive protective equipment IEC 61508, Functional safety of EEPE safety-related systems DIN V VDE0801 Principles for computers in systems with safety tasks DIN EN 62061 Safety of machinery - Functional safety of safety-related electrical, electronic and programmable electronic control systems IEC 50178 Electronic equipment for use in power installations DIN IEC 68 Electrical engineering; basic environmental testing procedures DIN EN 60204-1 Safety of machinery - electrical equipment of machines DIN EN 61140 Protection against electric shock - common aspects for installations and equipment (IEC 61140:2001 and A1:2004, modified) DIN EN 60664-1 Coordination of the insulation of electronic equipment in low-voltage systems Part 1: Principles, requirements and tests (IEC 60664-1:2007) DIN EN 60068-1:199503 Environmental testing - Part 1: General matters and guidance Directive 98/37/EC, from 29.12.2009 Directive 2006/42/EC Machinery Directive EN ISO 12100 Safety of machinery - electrical equipment of industrial machines EN ISO 13849-1 Safety of machinery - safety relevant parts of controls- part 1: General design principles DIN CLC/TS 62046, preliminary standard, 2005-09 Safety of machinery - Use of protective equipment to recognize the presence of people (IEC/TS 62046:2004) Safety of machinery - The positioning of protective equipment with respect to approach speeds of parts of the human body EN999/EN ISO 13855 Safety of machinery - The positioning of protective equipment with respect to approach speeds of parts of the human body ZH1/597 Safety rules for non-contact protective equipment on powered equipment EN ISO 13857 Safety of machinery - Safety distances to prevent hazard zones being reached by upper and lower limbs Date of issue 12.3.12 In addition to the stipulations listed there may be other applicable standards for special machinery and applications that should be considered. Part No. 109008 14.2 Use and installation of protective equipment 34 Part No. 109008 2012-03 Date of issue With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship" FABRIKAUTOMATION – SENSING YOUR NEEDS Zentrale weltweit Pepperl+Fuchs GmbH 68307 Mannheim · Deutschland Tel. +49 621 776-0 E-Mail: info@de.pepperl-fuchs.com Zentrale USA Pepperl+Fuchs Inc. Twinsburg, Ohio 44087 · USA Tel. +1 330 4253555 E-Mail: sales@us.pepperl-fuchs.com Zentrale Asien Pepperl+Fuchs Pte Ltd. Singapur 139942 Tel. +65 67799091 E-Mail: sales@sg.pepperl-fuchs.com www.pepperl-fuchs.com Änderungen vorbehalten Copyright PEPPERL+FUCHS • Printed in Germany DOCT-0183A 109008 03/2012
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : No Encryption : Standard V4.4 (128-bit) User Access : Print, Annotate, Fill forms, Extract, Print high-res Author : DM Create Date : 2012:03:12 09:57:14Z Modify Date : 2012:03:12 15:37:49+01:00 Subject : Control unit Has XFA : No XMP Toolkit : Adobe XMP Core 4.2.1-c043 52.372728, 2009/01/18-15:08:04 Creator Tool : FrameMaker 7.2 Metadata Date : 2012:03:12 15:37:49+01:00 Format : application/pdf Description : Control unit Title : Manual Control unit SLVA-4Kplus Creator : DM, Pepperl+Fuchs GmbH Producer : Acrobat Distiller 9.5.0 (Windows) Document ID : uuid:ef45f311-5f6b-4484-aee7-5c0d3e2d50b1 Instance ID : uuid:5c0a8091-a167-48c9-8687-7f0cfa39729a Page Mode : UseOutlines Page Count : 36EXIF Metadata provided by EXIF.tools