Data sheet 6AG1332-1SH52-7AA0
SIPLUS LOGO! POWER 24V 4A
SIPLUS LOGO! POWER 24V 4 A FOR MEDIAL STRESS -40...+70
DEGR C BASED-ON 6EP1332-1SH52 .STABILIZED POWER
SUPPLY INPUT: AC (110-300 V DC) OUTPUT: 24 V/
Input
Input 1-phase AC or DC
Rated voltage value Vin rated 100...240V
Voltage range AC 85...264V
Input voltage
● at DC 110...300V
Wide-range input Yes
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Mains buffering at Iout rated, min. 40ms; at Vin = 187 V
Rated line frequency 50...60Hz
Rated line range 47...63Hz
Input current
● at rated input voltage 120 V 1.95A
● at rated input voltage 230 V 0.97A
Switch-on current limiting (+25 °C), max. 30A
I²t, max. 2.5A²·s
Built-in incoming fuse internal
Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 16 A characteristic
B or from 10 A characteristic C
6AG1332-1SH52-7AA0 Changes preserved
Page 1/
4
25.12.2015 © Copyright Siemens AG
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24V
Total tolerance, static ± 3%
Static mains compensation, approx. 0.1%
Static load balancing, approx. 1.5%
Residual ripple peak-peak, max. 200mV
Residual ripple peak-peak, typ. 30mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 300mV
Spikes peak-peak, typ. (bandwidth: 20 MHz) 60mV
Adjustment range 22.2...26.4V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer
Status display Green LED for output voltage OK
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 0.5s
Voltage rise, typ. 15ms
Rated current value Iout rated 4A
Current range 0...4A
● Note +55 ... +70 °C: Derating 2%/K
Active power supplied typical 96W
Parallel switching for enhanced performance Yes
Numbers of parallel switchable units for enhanced
performance
2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 89%
Power loss at Vout rated, Iout rated, approx. 12W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %),
max.
0.2%
Dynamic load smoothing (Iout: 10/90/10 %), Uout ±
typ.
1.5%
Load step setting time 10 to 90%, typ. 1ms
Load step setting time 90 to 10%, typ. 1ms
Protection and monitoring
Output overvoltage protection Yes, according to EN 60950-1
Current limitation, typ. 5.2A
Property of the output Short-circuit proof Yes
Short-circuit protection Constant current characteristic
Enduring short circuit current RMS value
● maximum 7.9A
Overload/short-circuit indicator -
6AG1332-1SH52-7AA0 Changes preserved
Page 2/
4
25.12.2015 © Copyright Siemens AG
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN
50178
Protection class Class II (without protective conductor)
CE mark Yes
UL/CSA approval No
Certificate of suitability IECEx No
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation -40...+70°C
— Note with natural convection
● during transport -40...+85°C
● during storage -40...+85°C
Ambient condition relating to ambient temperature -
air pressure - installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m);
Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500
m); Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ...
+5000 m)
Relative humidity with condensation maximum 100%; Relative humidity, incl. condensation / frost permitted (no
commissioning under condensation conditions)
Resistance to biologically active substances
conformity acc. to EN 60721-3-3
Yes; Conformity with EN 60721-3-3, Class 3B2 mold, fungus and
dry rot spores (with the excepion of fauna). The supplied
connector covers must remain on the unused interfaces during
operation!
Resistance to chemically active substances
conformity acc. to EN 60721-3-3
Yes; Conformity with EN 60721-3-3, Class 3C4 incl. salt spray
according to EN 60068-2-52 (degree of severity 3). The supplied
connector covers must remain on the unused interfaces during
operation!
Resistance to mechanically active substances
conformity acc. to EN 60721-3-3
Yes; Conformity with EN 60721-3-3, Class 3S4 incl. Sand, dust.
The supplied connector covers must remain on the unused
interfaces during operation!
Mechanics
Connection technology screw-type terminals
Connections
● Supply input L, N: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely
stranded
● Output +, -: 2 screw terminals each for 0.5 ... 2.5 mm²
● Auxiliary -
Width of the enclosure 90mm
6AG1332-1SH52-7AA0 Changes preserved
Page 3/
4
25.12.2015 © Copyright Siemens AG
Height of the enclosure 90mm
Depth of the enclosure 55mm
Weight, approx. 0.34kg
Product feature of the enclosure housing for side-by-
side mounting
Yes
Installation Snaps onto DIN rail EN 60715 35x7.5/15
Other information Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)
6AG1332-1SH52-7AA0 Changes preserved
Page 4/
4
25.12.2015 © Copyright Siemens AG