6ES72141AG400XB0

2016-01-18

: Pdf 6Es72141Ag400Xb0 6ES72141AG400XB0 Siemen DataSheet

Open the PDF directly: View PDF PDF.
Page Count: 1

Download6ES72141AG400XB0
Open PDF In BrowserView PDF
Data sheet

6ES7214-1AG40-0XB0
SIMATIC S7-1200, CPU 1214C, COMPACT CPU, DC/DC/DC,
ONBOARD I/O: 14 DI 24V DC; 10 DO 24 V DC; 2 AI 0 - 10V DC,
POWER SUPPLY: DC 20.4 - 28.8 V DC, PROGRAM/DATA
MEMORY: 100 KB

General information
Product type designation

CPU 1214C DC/DC/DC

Firmware version

V4.1

Engineering with
● Programming package

STEP 7 V13 SP1 or higher

Display
with display

No

Supply voltage
Rated value (DC)
● 24 V DC

Yes

permissible range, lower limit (DC)

20.4 V

permissible range, upper limit (DC)

28.8 V

Reverse polarity protection

Yes

Load voltage L+
● Rated value (DC)

24 V

● permissible range, lower limit (DC)

20.4 V

● permissible range, upper limit (DC)

28.8 V

6ES7214-1AG40-0XB0
Page 1/8

18.01.2016

Changes preserved
© Copyright Siemens AG

Input current
Current consumption (rated value)

500 mA; CPU only

Current consumption, max.

1 500 mA; CPU with all expansion modules

Inrush current, max.

12 A; at 28.8 V

Encoder supply
24 V encoder supply
● 24 V

L+ minus 4 V DC min.

Output current
for backplane bus (5 V DC), max.

1 600 mA; Max. 5 V DC for SM and CM

Power loss
Power loss, typ.

12 W

Memory
Type of memory

RAM

Work memory
● integrated

100 kbyte

● expandable

No

Load memory
● integrated

4 Mbyte

● Plug-in (SIMATIC Memory Card), max.

with SIMATIC memory card

Backup
● present

Yes; maintenance-free

● without battery

Yes

CPU processing times
for bit operations, typ.

0.085 µs; / instruction

for word operations, typ.

1.7 µs; / instruction

for floating point arithmetic, typ.

2.3 µs; / instruction

CPU-blocks
Number of blocks (total)

DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used

OB
● Number, max.

Limited only by RAM for code

Data areas and their retentivity
retentive data area in total (incl. times, counters,
flags), max.

10 kbyte

Flag
● Number, max.

8 kbyte; Size of bit memory address area

Local data
● per priority class, max.

16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2
to 26: 6 KB

6ES7214-1AG40-0XB0
Page 2/8

18.01.2016

Changes preserved
© Copyright Siemens AG

Address area
Process image
● Inputs, adjustable

1 kbyte

● Outputs, adjustable

1 kbyte

Hardware configuration
Number of modules per system, max.

3 comm. modules, 1 signal board, 8 signal modules

Time of day
Clock
● Hardware clock (real-time clock)

Yes

● Backup time

480 h; Typical

● Deviation per day, max.

60 s/month at 25 °C

Digital inputs
Number of digital inputs
● of which inputs usable for technological
functions

14; Integrated
6; HSC (High Speed Counting)

integrated channels (DI)

14

m/p-reading

Yes

Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max.

14

Input voltage
● Rated value (DC)

24 V

● for signal "0"

5 V DC at 1 mA

● for signal "1"

15 VDC at 2.5 mA

Input delay (for rated value of input voltage)
for standard inputs
— parameterizable

0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four

— at "0" to "1", min.

0.2 ms

— at "0" to "1", max.

12.8 ms

for interrupt inputs
— parameterizable

Yes

for counter/technological functions
— parameterizable

Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80
kHz & 3 @ 30 kHz

Cable length
● shielded, max.

500 m; 50 m for technological functions

● unshielded, max.

300 m; For technological functions: No

Digital outputs
Number of digital outputs
● of which high-speed outputs

6ES7214-1AG40-0XB0
Page 3/8

10
4; 100 kHz Pulse Train Output

18.01.2016

Changes preserved
© Copyright Siemens AG

integrated channels (DO)

10

Limitation of inductive shutdown voltage to

L+ (-48 V)

Switching capacity of the outputs
● with resistive load, max.

0.5 A

● on lamp load, max.

5 W

Output voltage
● for signal "0", max.

0.1 V; with 10 kOhm load

● for signal "1", min.

20 V

Output current
● for signal "1" rated value

0.5 A

● for signal "0" residual current, max.

0.1 mA

Output delay with resistive load
● "0" to "1", max.

1 µs

● "1" to "0", max.

5 µs

Switching frequency
● of the pulse outputs, with resistive load, max.

100 kHz

Cable length
● shielded, max.

500 m

● unshielded, max.

150 m

Analog inputs
Number of analog inputs

2

integrated channels (AI)

2; 0 to 10V

Input ranges
● Voltage

Yes

Input ranges (rated values), voltages
● 0 to +10 V

Yes

● Input resistance (0 to 10 V)

≥100k ohms

Cable length
● shielded, max.

100 m; twisted and shielded

Analog outputs
Number of analog outputs

0

Analog value generation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign),
max.

10 bit

● Integration time, parameterizable

Yes

● Conversion time (per channel)

625 µs

Encoder
Connectable encoders
● 2-wire sensor

6ES7214-1AG40-0XB0
Page 4/8

Yes

18.01.2016

Changes preserved
© Copyright Siemens AG

1. Interface
Interface type

PROFINET

Physics

Ethernet

Isolated

Yes

automatic detection of transmission rate

Yes

Autonegotiation

Yes

Autocrossing

Yes

Functionality
● PROFINET IO Controller

Yes

● PROFINET IO Device

Yes

● Open IE communication

Yes

● Web server

Yes

PROFINET IO Controller
● Transmission rate, max.

100 Mbit/s

Services
— Number of connectable IO Devices, max.

16

PROFINET IO Device
Services
— Shared device

Yes

— Number of IO Controllers with shared
device, max.

2

Protocols
Supports protocol for PROFINET IO

Yes

PROFIBUS

Yes; CM 1243-5 required

AS-Interface

Yes

Protocols (Ethernet)
● TCP/IP

Yes

Further protocols
● MODBUS

Yes

Communication functions
S7 communication
● supported

Yes

● as server

Yes

● as client

Yes

Open IE communication
● TCP/IP

Yes

● ISO-on-TCP (RFC1006)

Yes

● UDP

Yes

Web server
● supported

Yes

● User-defined websites

Yes

6ES7214-1AG40-0XB0
Page 5/8

18.01.2016

Changes preserved
© Copyright Siemens AG

Number of connections
● overall

16; dynamically

Test commissioning functions
Status/control
● Status/control variable

Yes

● Variables

Inputs/outputs, memory bits, DBs, distributed I/Os, timers,
counters

Forcing
● Forcing

Yes

Diagnostic buffer
● present

Yes

Traces
● Number of configurable Traces

2; Up to 512 KB of data per trace are possible

Integrated Functions
Number of counters

6

Counting frequency (counter) max.

100 kHz

Frequency meter

Yes

controlled positioning

Yes

Number of position-controlled positioning axes, max.

8

Number of positioning axes via pulse-direction
interface

4; With integrated DO

PID controller

Yes

Number of alarm inputs

4

Number of pulse outputs

4

Limit frequency (pulse)

100 kHz

Potential separation
Potential separation digital inputs
● Potential separation digital inputs

500V AC for 1 minute

● between the channels, in groups of

1

Potential separation digital outputs
● Potential separation digital outputs

Yes

● between the channels

No

● between the channels, in groups of

1

EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of
static electricity acc. to IEC 61000-4-2

Yes

— Test voltage at air discharge

8 kV

— Test voltage at contact discharge

6 kV

Interference immunity to cable-borne interference

6ES7214-1AG40-0XB0
Page 6/8

18.01.2016

Changes preserved
© Copyright Siemens AG

● Interference immunity on supply lines acc. to
IEC 61000-4-4

Yes

● Interference immunity on signal cables acc. to
IEC 61000-4-4

Yes

Interference immunity against voltage surge
● on the supply lines acc. to IEC 61000-4-5

Yes

Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency
radiation acc. to IEC 61000-4-6

Yes

Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas

Yes; Group 1

● Limit class B, for use in residential areas

Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011

Degree and class of protection
Degree of protection acc. to EN 60529
● IP20

Yes

Standards, approvals, certificates
CE mark

Yes

UL approval

Yes

cULus

Yes

FM approval

Yes

RCM (formerly C-TICK)

Yes

Marine approval
● Marine approval

Yes

Ambient conditions
Free fall
● Drop height, max. (in packaging)

0.3 m; five times, in dispatch package

Ambient temperature during operation
● min.

-20 °C

● max.

60 °C; Number of simultaneously activated inputs or outputs 7 or
5 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 14 or
10 at 55 °C horizontal or 45 °C vertical

● horizontal installation, min.

-20 °C

● horizontal installation, max.

60 °C

● vertical installation, min.

-20 °C

● vertical installation, max.

50 °C

Ambient temperature during storage/transportation
● min.

-40 °C

● max.

70 °C

Air pressure acc. to IEC 60068-2-13
● Storage/transport, min.

660 hPa

● Storage/transport, max.

1 080 hPa

6ES7214-1AG40-0XB0
Page 7/8

18.01.2016

Changes preserved
© Copyright Siemens AG

● permissible operating height

-1000 to 2000 m

Relative humidity
● permissible range (without condensation) at 25
°C

95 %

Vibrations
● Vibrations

2G wall mounting, 1G DIN rail

● Operation, tested according to IEC 60068-2-6

Yes

Shock test
● tested according to IEC 60068-2-27

Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak
value), duration 11 ms

Extended ambient conditions
Pollutant concentrations
— SO2 at RH < 60% without condensation

S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free

Configuration
Programming
Programming language
— LAD

Yes

— FBD

Yes

— SCL

Yes

Cycle time monitoring
● adjustable

Yes

Dimensions
Width

110 mm

Height

100 mm

Depth

75 mm

Weights
Weight, approx.

415 g

last modified:

13.01.2016

6ES7214-1AG40-0XB0
Page 8/8

18.01.2016

Changes preserved
© Copyright Siemens AG

