Brochure
100349-Attachment 100349-Attachment 100349-Attachment 753573 Batch6 unilog cesco-content
2014-05-16
: Pdf 83556-Brochure 83556-Brochure 753573 Batch3 unilog
Open the PDF directly: View PDF .
Page Count: 2
®
SPECIFICATIONS
ORDERING INFO
OPTIONS
MULTIWAY INTERFACE (3X)
• Interfacesw/otherunitsfor3-wayor
additionalcongurations
• Onlyavailableonsingleon/offversion
DIMMING (D)
• Enablesusercontrolof0-10VDC
dimmableballasts
COLOR (mustbespecied)
• White,Ivory,Gray,LightAlmond
• Wallplateprovided
LOW TEMP/HIGH HUMIDITY (LT)
• Deviceelectronicsarecoatedfor
corrosionresistance
•Operatesdownto-40ºF/C
Blank = 1 Switch / Auto-On Blank = None Blank = None WH = White Blank = Standard
SA = 1 Switch / Manual On 3X = 3-Way D = Dimming IV = Ivory LT = Low Temp
2P = 2 Switches (Pole 1 Manual / Pole 2 Auto) Operation GY = Gray
2P 2SA = 2 Switches (Both Poles Manual) AL = Light Almond
The Push-Button SwitchPod (sPODM) Series of
low voltage wall stations interface with standard
Sensor Switch occupancy sensors and power
packs in order to implement a wide range
of single and bi-level switching applications.
These switch devices provide an elegant and
cost effective way of deploying bi-level lighting
control that meet energy and building codes
without having to source special sensors or
power packs.
Commonly required by building codes (such as
California Title 24), bi-level lighting control is
an easy and convenient method of delivering
extra energy savings without inconveniencing
the occupants. The most common bi-level
conguration requires one lighting load to be
switched on automatically when occupancy is detected by an occupancy sensor, while a
second lighting load can be turned on manually by the occupant if desired. Both loads can then
be turned off manually or via the occupancy sensor timing out. Sensors with photocells can
also be congured with SwitchPods in order to add override off capabilities.
SwitchPods are all single gang decorator style devices available as single or dual switch units.
Versions are also available that work in 3-way applications and/or have a 0-10 VDC dimming
output. Units defaulted to dual manual-on operation are also available. For digital solutions
to bi-level lighting applications, nLight-enabled wall stations (WallPods), power packs, and
sensors are necessary.
SWITCHPOD • SENSOR INTERFACE SWITCH •
MANUAL/AUTO ON • LOW VOLTAGE • PUSH-BUTTON
sPODM
FEATURES
Enables Standard Occupancy Sensors
to be used for Manual On Operation
Alternative Usage as Override Switch
for Auto-On Applicaitons
Single Gang Decorator Style w/
either 1 or 2 On/Off Switches
Soft-Click Push-Buttons
Programmable w/o Removing
Switch Plate
Optional Dual Manual On Operation
Optional 3-Way Operation
Optional 0-10 VDC Dimming Control
PHYSICAL SPECS
SIZE (not including ground strap)
2.74” H x 1.68” W x 1.63” D
(6.96 cm x 4.27 cm x 4.14 cm)
WEIGHT 2 oz
MOUNTING Single Gang Switch Box or
Low Voltage Ring
COLOR White, Ivory, Gray, & Lt. Almond
ELECTRICAL SPECS
OPERATING VOLTAGE
12-24 VAC/VDC
CURRENT 5 mA
DIMMING LOAD
Sinks < 20mA;
~40 Ballasts @ .5mA each
WIRES (all 20 AWG)
sPODM (SA): 4
sPODM 2P (2SA): 6
sPODM (SA) 3X: 6
sPODM (SA) D: 5
sPODM (SA) 3X D: 7
RECOMMENDED POWER PACK
PP20
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
OTHER
Class 2 Low Voltage
Title 24 System Device
5 Year Warranty
Assembled in the U.S.A.
sPODM [# OF SWITCHES/DEFAULT ON OPER.] [3-WAY]* [DIMMING]* [COLOR] [TEMP/HUMIDTY]
# OF SWITCHES/DEFAULT ON OPER. 3-WAY* DIMMING* COLOR TEMP/HUMIDTY
*Not available with 2 switch (2P) versions
ON
OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON / OFF
ON
OFF
ON
OFF
1
2
OPERATION / WIRING INFORMATION
STANDARD (SPODM / SPODM SA)
RED - Power (12-24 VAC/VDC)
BLACK - Common
WHITE - Occupancy Sensor Input
WHITE w/ BLUE STRIPE - Output to Relay
note: Default output functionality (Manual On vs.
Auto-On) is determined by model number, but
re-congurable using push-button sequence
3-WAY OPTION (3X OPTION)
YELLOW - Remote Switch I/O
YELLOW w/ BLACK STRIPE - Remote Switch I/O
DIMMING OPTION (D OPTION)
VIOLET - 0-10 VDC Output (wire to VIOLET on
0-10 VDC dimmable ballast)
2P BUTTONS CONTROLS
- top two buttons always
control the Pole 1 Output
- bottom two buttons always
control the Pole 2 Output
2P OPTION (SPODM 2P / SPODM 2P 2SA)
WHITE - Pole 1 Occupancy Sensor Input
WHITE w/ BLUE STRIPE - Pole 1 Output to Relay
BLUE - Pole 2 Occupancy Sensor Input
BLUE w/ WHITE STRIPE - Pole 2 Output to Relay
note: Default output functionality (Manual On vs.
Auto-On) is determined by model number, but
re-congurable using push-button sequence
TYPICAL CONFIGURATIONS (note: 3 conductor 18AWG wire is recommended for all wiring)
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a period of 60
months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material Authorization number
and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied warranties
(including the implied warranties of merchantability and tness for use) and under no circumstances shall Sensor Switch, Inc. be liable
for any incidental or consequential property damages or losses.
TS-SPOD-002A
Revised 1.31.14 © 2014 Sensor Switch
BI-LEVEL (MANUAL ON / AUTO ON) SOLUTION
w/ OCCUPANCY SENSOR: 1 GANG
BI-LEVEL (AUTO-ON / MANUAL ON) SOLUTION
w/ OCCUPANCY SENSOR: 2 GANG
3-WAY MANUAL ON SOLUTION w/ OCCUPANCY SENSOR
BLK
RED
BLU
BLU
BLU
BLU
WHT
BLK/ORN
BLK
WHT
RED
WHT / BLU STRIPE
BLU / WHT STRIPE
Bi-Level Solution w/ Occupancy Sensor: 1-gang
RED
BLK
WHT
RED
BLK
N
H
sPODM 2P
WHT
WHT
BLU
PP20 SP20
MANUAL
ON LOAD
AUTO ON
LOAD
Class 1 Connections
A1
SP20
PP20
BLK
RED
BLU
BLU
BLU
WHT
BLK/ORN
BLK
WHT
RED
WHT / BLU STRIPE
RED
WHT
WHT
WHT / BLU STRIPE
BLK
RED
BLK
WHT
RED
BLK
N
H
sPODM
sPODM SA
WHT
Class 1 Connections
A2
Bi-Level Solution w/ Occupancy Sensor: 2-gang
AUTO ON
LOAD
BLU
H
MANUAL
ON LOAD
WHT
WHT
WHT / BLU
BLK REDBLK RED
WHT
sPODM SA 3X
YEL
WHT / BLU STRIPE
YEL
YEL / BLK STRIPE
YEL / BLK STRIPE
BLK
RED
BLK
RED
sPODM SA 3X
A4
PP20
Class 1 Connections
3-Way Manual On Solution w/ Occupancy Sensor: 1-gang
BLU
BLU
WHTWHT
BLK / ORN
N
H
LOAD
Note: If sensor also has dimming output, connect sensor VIO wire
to SPODM and ballast VIO wire. Lowest output level always takes
precedence.
1. Enter programming mode by pressing & holding upper most button until LED ashes rapidly. Release button.
2. Enter the On Mode function by pressing button twice.
3. The current On Mode setting will then be fed out in a sequence of LED ashes as indicated in the table below (e.g., one ash for Auto-
On). To change the setting, proceed to step 4 before sequence repeats 10 times.
4. At any time while the switch is ashing back the current On Mode setting, interrupt it by pressing button the number of times for the new
desired On Mode setting as indicated in the table below (e.g., press twice for Manual On). Switch will begin to ash back new setting as
conrmation.
5. Next, while the switch is ashing back new setting, interrupt it by pressing and holding button until LED ashes rapidly. Release button.
6. As nal conrmation and activation of the new setting, press button two times.
7. LED will ash twice indicating acceptance of new setting. If two ashes are not seen, repeat 7 step process.
Note: To exit programming mode without saving, wait for blink back sequence to repeat 10 times then return to step 1.
Function
Number
Function
Name
Settings (*indicates default setting)
Setting Number Pole 1 Pole 2 (2P devices only)
2 On Mode
1 Auto-On Manual On
2 Manual On Auto-On
3 (2P devices only) Manual On Manual On
4 (2P devices only) Auto-On Auto-On
PROGRAMMING INSTRUCTIONS
WHT
BLK RED
BLK
WHT VIO
WHT / BLU STRIPE
VIO
BLK
RED
sPODM SA D
A4
PP20
Class 1 Connections
3-Way Manual On Solution w/ Occupancy Sensor: 1-gang
BLU
BLU
WHTWHT
BLK / ORN
N
H
0-10 VDC
BALLAST
GRY
RED
If sensor also has dimming output, connect sensor VIO wire to SPODM and ballast VIO wire
MANUAL ON w/ DIMMING & OCCUPANCY SENSOR
(PLEASE READ ALL 7 STEPS BEFORE PROGRAMMING)
Note: SPODM (SA) 3X D units should only be used in 3-way applications with SPODM (SA)
3X units (non-dimming) as dimming levels are not communicated between devices.