Dlt Trf Psg

2018-08-28

: Pdf Dlt Trf Psg dlt_trf_psg psg products dual-lite

Open the PDF directly: View PDF PDF.
Page Count: 2

INVERTERS
AC output provides full lumen output for emergency lighting loads in commercial or
industrial applications
Compatible with any lighting load including incandescent, HID, fluorescent
and LED lamps
Painted steel enclosure and double conversion online operation
Maintenance-free batteries with fully automatic solid state charger
Form C contact closure points standard on all models
24 hour recharge time
Temperature range: 20°C to 30°C (68°F to 86°F)
OSHPD seismic qualification on 65 - 125KVA sizes
UL 924 Listed
MODEL
TRF
OUTPUT
VOLTAGE
208 208VAC
4803480VAC
INPUT
VOLTAGE
208¹208VAC
480 480VAC
INPUT
CONDUCTOR
33 Wire
424 Wire
CAPACITY
10
10KVA/9KW
15
15KVA/13KW
20
20KVA/18KW
30
30KVA/27KW
40
40KVA/36KW
50
50KVA/45KW
60
60KVA/54KW
65
65KVA/58KW
80
80KVA/72KW
100
100KVA/90KW
125
125KVA/112KW
OPTIONS6,7
ASNMP/Web Card
BSNMP/Web Card & Env. Sensor
CTop Entry Cabinet
DSNMP Card & Top Entry Cabinet
ESNMP Card, Env. Sensor &
Top Entry Cabinet
FACTORY STARTUPS REQUIRED4
FST-1 Factory Start-Up 10 - 30kVA
FST-2 Factory Start-Up 40 - 80kVA
FST-3 Factory Start-Up > 80kVA
ACCESSORIES
TRF-RSP-1 Remote Status Panel 10-60kVA
TRF-RSP-2 Remote Status Panel 65-125kVA
TRF-SFK-1 Seismic Mounting 10-40kVA
TRF-SFK-2 Seismic Mounting 50-60kVA
1 Only available with 208VAC output voltage.
2 Only available with 480VAC output voltage (all capacities), and with 208 VAC input voltage on 10KVA through 65KVA capacities
3 Only available with 480VAC input voltage.
4 Start-up must be performed by an Authorized Service Center within 6 months of shipment to maintain battery warranty.
5 Batteries must be connected to an energized charging circuit within 90 days from date of shipment or warranty is void.
6 Alternate run times and 50Hz models available on request; consult factory.
7 SNMP/web card: Internal SNMP Card allows inverter management acrosss a LAN using any of the main network communication protocols. - TCP/IP, HTTP and network interface (SNMP).
SNMP/Web Card & Env. Sensor: SNMP card with an environmental sensor module that senses temperature, humidity and smoke and displays it via SNMP.
Top Entry Cabinet: Provides additional compartments to allow for top conduit entry.
FEATURES
TRF
Three-Phase Systems - 10KVA to 125KVA
ELECTRONICS
Uninterruptible "no break" transfer
Microprocessor controlled pulse width modulation (PWM) using IGBT technology
Transient surge, LVD, short-circuit, current limiting, overload and brown-out protection
Self-test diagnostic circuitry
True sine wave output; optional runtime available
Digital controls with graphic user interface with LED indicators and audible alarm system
Load power factor range of 0.9 leading to 0.5 lagging without derating (may not exceed KVA rating)
Internal power factor of 0.90 to yield KW rating
ORDERING INFORMATION
CABINET CONFIGURATIONS
Cabinet Congurations
Conguration A Conguration B Conguration C Conguration D Conguration E Conguration F
Conguration G Conguration H Conguration I
Conguration J Conguration K Conguration L
Cabinet Congurations
Conguration A Conguration B Conguration C Conguration D Conguration E Conguration F
Conguration G Conguration H Conguration I
Conguration J Conguration K Conguration L
Cabinet Congurations
Conguration A Conguration B Conguration C Conguration D Conguration E Conguration F
Conguration G Conguration H Conguration I
Conguration J Conguration K Conguration L
Cabinet Congurations
Conguration A Conguration B Conguration C Conguration D Conguration E Conguration F
Conguration G Conguration H Conguration I
Conguration J Conguration K Conguration L
Cabinet Congurations
Conguration A Conguration B Conguration C Conguration D Conguration E Conguration F
Conguration G Conguration H Conguration I
Conguration J Conguration K Conguration L
Configuration A Configuration B Configuration C Configuration D
Configuration E Configuration F Configuration G Configuration H Configuration I
Configuration J Configuration K Configuration L
INVERTERS
UPS
Rating AC Voltage AC Current Battery Recommended OCPD Mechanical Data
kVA/kW Input
(VAC)
Output
(VAC)
Bypass
(VAC)
Input
Nom
(A)
Input
Max
(A)
Output
Nom
(A)
Nom.
(VDC)
Discharge
(A) Input Output DC No. of
Cab.
Cab.
Config.
Width
(in)
Depth
(in)
Height
(in)
Weight
(lbs)
Heat Dis.
(BTU/hr)
10/9 208V 208Y/120V 208V 27.8 33.4 27.8 432 26.5 45 35 35 2 A 49.2 35.6 72.4 2,351 3200
10/9 208Y/120V 208Y/120V 208/120V 27.1 32.6 27.8 432 26.5 40 35 35 2 A 49.2 35.6 72.4 2,171 2400
10/9 480V 208Y/120V 480V 12.1 14.5 27.8 432 26.5 20 35 35 2 A 49.2 35.6 72.4 2,381 3200
10/9 480V 480Y/277V 480V 12.2 14.7 12.0 432 26.9 20 15 35 2 A 49.2 35.6 72.4 2,481 3700
10/9 480Y/277V 480Y/277V 480/277V 12.1 14.5 12.0 432 26.9 20 15 35 2 A 49.2 35.6 72.4 2,371 3400
15/13 208V 208Y/120V 208V 41.7 50.1 41.6 432 39.8 70 60 50 2 B 59.1 34.5 78.7 3,439 4800
15/13 208Y/120V 208Y/120V 208/120V 40.7 48.8 41.6 432 39.8 60 60 50 2 B 59.1 34.5 78.7 3,189 3500
15/13 480V 208Y/120V 480V 18.1 21.7 41.6 432 39.8 30 60 50 2 B 59.1 34.5 78.7 3,439 4800
15/13 480V 480Y/277V 480V 18.4 22.0 18.0 432 40.4 30 25 60 2 B 59.1 34.5 78.7 3,639 5600
15/13 480Y/277V 480Y/277V 480/277V 18.2 21.8 18.0 432 40.4 30 25 60 2 B 59.1 34.5 78.7 3,589 5000
20/18 208V 208/120V 208V 55.7 66.8 55.5 432 53.1 90 70 70 2 C 63.1 34.5 78.7 4319 6400
20/18 208Y/120V 208Y/120V 208/120V 54.3 65.1 55.5 432 53.1 80 70 70 2 C 63.1 34.5 78.7 4,089 4700
20/18 480V 208Y/120V 480V 24.1 28.9 55.5 432 53.1 35 70 70 2 C 63.1 34.5 78.7 4,389 6400
20/18 480V 480Y/277V 480V 24.5 29.4 24.1 432 53.9 40 30 70 2 C 63.1 34.5 78.7 4,619 7400
20/18 480Y/277V 480Y/277V 480/277V 24.2 29.1 24.1 432 53.9 40 30 70 2 C 63.1 34.5 78.7 4,549 6700
30/27 208V 208Y/120V 208V 83.5 100.2 83.3 432 79.6 125 110 100 3 D 99.1 34.5 78.7 6,509 9500
30/27 208Y/120V 208Y/120V 208/120V 81.4 97.7 83.3 432 79.6 125 110 100 3 D 99.1 34.5 78.7 6,079 7000
30/27 480V 208Y/120V 480V 36.2 43.4 83.3 432 79.6 60 110 100 3 D 99.1 34.5 78.7 6,509 9500
30/27 480V 480Y/277V 480V 36.7 44.1 36.1 432 80.8 60 50 110 3 D 99.1 34.5 78.7 6,774 11100
30/27 480Y/277V 480Y/277V 480/277V 36.4 43.6 36.1 432 80.8 60 50 110 3 D 99.1 34.5 78.7 6,609 10000
40/36 208V 208Y/120V 208V 111.3 133.6 111.0 432 106.2 175 150 150 3 E 103.1 34.5 78.7 7,953 12700
40/36 208Y/120V 208Y/120V 208/120V 108.5 130.2 111.0 432 106.2 175 150 150 3 E 103.1 34.5 78.7 7,519 9300
40/36 480V 208Y/120V 480V 48.2 57.9 111.0 432 106.2 70 150 150 3 E 103.1 34.5 78.7 7,969 12700
40/36 480V 480Y/277V 480V 49.0 58.8 48.1 432 107.8 80 70 150 3 E 103.1 34.5 78.7 8,239 14700
40/36 480Y/277V 480Y/277V 480/277V 48.5 58.2 48.1 432 107.8 80 70 150 3 E 103.1 34.5 78.7 8,059 13300
50/45 208V 208Y/120V 208V 147.1 176.5 138.8 432 132.7 225 175 175 3 F 106.4 34.3 78.7 9,621 25500
50/45 208Y/120V 208Y/120V 208/120V 143.4 172.0 138.8 432 132.7 225 175 175 3 F 106.4 34.3 78.7 9,041 21000
50/45 480V 208Y/120V 480V 63.7 76.5 138.8 432 132.7 100 175 175 3 F 106.4 34.3 78.7 9,451 25500
50/45 480V 480Y/277V 480V 65.4 78.4 60.1 432 136.1 100 80 175 3 F 106.4 34.3 78.7 9,861 30100
50/45 480Y/277V 480Y/277V 480/277V 65.4 78.4 60.1 432 136.1 100 80 175 3 F 106.4 34.3 78.7 9,861 30100
60/54 208V 208Y/120V 208V 170.6 204.8 166.5 432 159.3 250 225 200 3 F 106.4 34.3 78.7 9,599 23500
60/54 208Y/120V 208Y/120V 208/120V 166.4 199.7 166.5 432 159.3 250 225 200 3 F 106.4 34.3 78.7 9,041 18300
60/54 480V 208Y/120V 480V 73.9 88.7 166.5 432 159.3 110 225 200 3 F 106.4 34.3 78.7 9,601 23500
60/54 480V 480Y/277V 480V 75.1 90.1 72.2 432 161.7 110 100 225 3 F 106.4 34.3 78.7 10,167 26600
60/54 480Y/277V 480Y/277V 480/277V 74.3 89.2 72.2 432 161.7 110 100 225 3 F 106.4 34.3 78.7 10,173 24500
65/58 208V 208Y/120V 208V 180.5 209.0 180.4 480 159.5 300 225 160 4 J 137 33.5 78.7 12,539 15683
65/58 480V 480/277V 480V 78.2 89.0 78.2 480 159.5 125 125 160 4 J 137 33.5 78.7 11,909 15833
65/58 480V 208Y/120V 480V 78.2 89.0 180.4 480 159.5 125 225 160 4 J 137 33.5 78.7 11,909 15683
65/58 480Y/277V 480Y/277V 480/277V 78.2 89.0 78.2 480 159.5 125 100 160 3 G 103.6 33.5 78.7 10,439 15033
80/72 208V 208Y/120V 208V 222.2 256.0 222.1 480 196.4 350 300 200 5 K 173 33.5 78.7 17,009 19300
80/72 480V 480/277V 480V 96.3 109.0 96.2 480 196.4 150 150 200 5 K 173 33.5 78.7 16,379 19300
80/72 480V 208Y/120V 480V 96.3 109.0 222.1 480 196.4 150 300 200 5 K 173 33.5 78.7 16,739 19300
80/72 480Y/277V 480Y/277V 480/277V 96.3 109.0 96.2 480 196.4 150 125 200 4 H 139.6 33.5 78.7 14,909 18500
100/90 208V 208Y/120V 208V 277.6 317.0 277.6 480 235.8 400 350 250 5 K 173 33.5 78.7 17,119 24120
100/90 480V 480/277V 480V 120.3 136.0 120.3 480 235.8 175 175 250 5 K 173 33.5 78.7 16,489 24120
100/90 480V 208Y/120V 480V 120.3 136.0 277.6 480 235.8 175 350 250 5 K 173 33.5 78.7 16,489 24120
100/90 480Y/277V 480Y/277V 480/277V 120.3 136.0 120.3 480 235.8 175 150 250 4 H 139.6 33.5 78.7 15,019 23120
125/112 208V 208Y/120V 208V 347.1 360.0 347.0 480 294.8 450 450 300 6 L 209 33.5 78.7 21,722 30150
125/112 480V 480/277V 480V 150.4 160.0 150.4 480 294.8 200 200 300 6 L 209 33.5 78.7 21,092 30150
125/112 480V 208Y/120V 480V 150.4 160.0 347.0 480 294.8 200 450 300 6 L 209 33.5 78.7 21,092 30150
125/112 480Y/277V 480Y/277V 480/277V 150.4 160.0 150.4 480 294.8 200 200 300 5 I 175.6 33.5 78.7 19,622 28900
NOTES FOR SITE PLANNING DATA:
1. Input and bypass cables must be run in separate conduit from output cables.
2. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors
are recommended. Neutral conductors to be sized for full capacity per NEC 310-15(B)(4)
References are per NEC 2008.
3. Wiring requirements:
AC Input: 3-phase, 3-wire plus ground or 3-phase, 4-wire plus ground
AC Output: 3-phase, 3-wire plus ground or 3-phase, 4-wire plus ground
4. All wiring is to be in accordance with national and local electrical codes.
5. Minimum cabinet access clearance: 3 ft. (0.9m) front, ; 18” (457mm) overhead for up to
65kVA systems and 24” (610mm) overhead for >65kVA systems; 8” (203mm) rear for up to
65kVA systems and 24”(610mm) rear for >65kVA systems.
6. Top or bottom cable entry through removable access plates. Punch plate to suit conduit size
then replace.
7. Control wiring and power wiring must be run in separate conduit.
ADDITIONAL NOTES:
If site configuration includes a back-up emergency generator, it is recommended
that the engine generator set be properly sized and equipped for
a UPS application. Generator options would typically include an
isochronous
governor
(generator frequency regulation) and a UPS
compatible regulator (generator voltage regulation). Consult generator
manufacturer for required generator options and sizing.
8. Dimensions are system dimensions including UPS, battery cabinets and transformer
cabinets (if any).; Transformer cabinets are front access
9. Weights are system weights including UPS, battery cabinets and transformer cabinets
(if any).; Transformer cabinets are front access.
10. Heat dissipation includes UPS , battery and transformer cabinet.
11. Recommended AC input external overcurrent protection is based on 80% rated
devices and maximum input current limit settings.
TRF
Three Phase Central Lighting Inverters – 10KVA to 125KVA
SPECIFICATIONS

Navigation menu