For Three Phase and Single Phase MP200
Metering Systems
TM

www.electroind.com

ENCMP200

Pre-wired Multipoint Metering Solution
Ready for Installation

• For Retrofit Meter Solutions

• Pre-Wired and Configured

• Extends Switchgear Capability

• Nema Type 1 Rated Enclosure

• Optional BACnet®* or LonWorks®* • Eliminates Wiring and Installation
Communication Protocols
Errors
Electro Industries/GaugeTech

The Leader in Power Monitoring and Smart Grid Solutions

MP200 in ENCLOSURE INFORMATION
TM

Description
EIG's MP200TM in enclosure lets you
expand your switchgear capability and/or
easily meter circuits without expensive and
time-consuming redesign. Simply mount
the enclosure in any convenient location,
next to your switchgear or on a wall, and
you are ready to go with no downtime.
Using the MP200TM in enclosure allows
you to meter up to 24 single phase or 8
three phase loads and send the data with
a variety of communication protocols.

This is a perfect solution for a retrofit
where there is no metering compartment
available. The meter comes standard with
a NEMA 1 rated enclosure and is factory
wired with the meter installed. Standard
equipment includes voltage fuses and
shorting blocks for current transformers.
The system will work directly with 120/208
and 277/480 Volt power systems.

Color
Touchscreen
Display

The enclosure can be ordered with either
the three phase MP200TM-Y or the single
phase MP200TM-S meter. Optional CTs are
available for each circuit. The CTs can be
ordered as either split core or solid core
depending on the needs of the installation.
Optional ProtoCom and ProtoCom-Lon
modules offer BACnet®* and LonWorks®*
communication, enabling the MP200TM in

enclosure to fit seamlessly into existing
Building Automation System applications.
The unit is equipped with either a 3.5" or
5.7" color touchscreen display to make
data reading simple and easy. The display
provides extensive circuit data for every
load, including circuit analysis.

MP200 in ENCLOSURE LAYOUT
TM

CT Connections
UL Listing

Key Lock

2

CT Shorting Blocks

Optional Protocol
Additions

Fused Voltage
Inputs

Neutral
Connection

SHARK®MP200

METER ASSEMBLY

DIMENSIONAL DRAWINGS

7.35in
[18.69cm]
20.00in
[50.80cm]

6.60in
[16.76cm]

20.00in
[50.80cm]

20.00in
[50.80cm]

20.00in
[50.8cm]

MP200 in Enclosure
Top Dimensions
TM

MP200 in Enclosure
Front Dimensions

MP200 in Enclosure
Side Dimensions

TM

TM

MOUNTING DRAWINGS
2.500

2.500

15.000

1.250

1.250

36

0.4

0.4

TM

17.690

MP200 in Enclosure
Mounting Dimensions

17.690

36

0.3

12

12

0.3
1.060

1.060
2.500

15.000

2.500

3

WIRING DIAGRAMS

LINE
V3

V2

LINE

CT SHORTING BLOCK

V1

.

V2

N
WHITE

.
.

CURRENT A HI

BLACK

CURRENT A LO

WHITE

CURRENT B HI

BLACK

CURRENT B LO

WHITE

CURRENT C HI

BLACK

CURRENT C LO

.

V1

.

CT SHORTING BLOCK

N
WHITE

.
TO MP200 CURRENT INPUTS

.

CURRENT 1 HI

BLACK

CURRENT 1 LO

WHITE

CURRENT 2 HI

BLACK

CURRENT 2 LO

.
TO MP200 CURRENT INPUTS

.

.

ONLY ONE 3 PHASE CIRCUIT IS SHOWN.
DUPLICATE IT FOR ADDITIONAL CIRCUITS.

.
ONLY ONE CIRCUIT IS SHOWN.
DUPLICATE FOR ADDITIONAL CIRCUITS.

.

.

GND

GND
FUSE BLOCK

FUSE BLOCK
L+

.

V1

UNIT POWER L +

.

VOLTAGE A
TO MP200 VOLTAGE/ POWER INPUTS

.
.
.

V2

VOLTAGE B

V3

VOLTAGE C

UNIT POWER L +

L+

V1

VOLTAGE A

V2

VOLTAGE B

TO MP200 VOLTAGE/ POWER INPUTS

.

VOLTAGE C

N

.

NEUTRAL

.

N

NEUTRAL

LOAD

LOAD

Single Phase Wiring for
MP200 -S

Three Phase Wiring for
MP200 -Y
TM

TM

Ordering Information
MP200 in Enclosure
TM

All fields must be filled in to create a valid part number.
Model
Option
Numbers:
Example:

ENCMP200

Current Configuration

-

MP200 Metering
System in Nema 1
Enclosure

Y
Y
Three Phase
WYE
S
Single Phase
ONLY

-

Frequency

60
50
50HZ
60
60HZ

Current Class

-

10

V-Switch Pack

-

V2

-

V1
Transducer

10
10 Amp
Secondary
2
2 Amp
Secondary

Communication

V2
Basic Logger
V3
Advanced Logger

WIFI
X
RS485 Only
(Modbus®)*
WIFI
Ethernet and
WiFi
(Modbus®)*

-

Display

MDSN

Add-on Protocol

-

MDSN
3.5" Display
MDLN
5.7" Display

ProtoCom
X
No Add-on
Protocol
ProtoCom
BACnet®*
ProtoCom-Lon
LonWorks®*

Optional Available Current Transformers
Solid Core Transformers

Split Core Transformers

WIFI Antenna (Required for WIFI)

100/5 : EI-2DARL-101

100/5 : EI-1SP-100-00

ANTI8769 - Remote mounted WiFi Antenna for

200/5 : EI-2DARL-201

200/5 : EI-1SP-200-00

mounting on outside of enclosure.

400/5 : EI-5ARL-401

400/5 : EI-WC-400-RA05
Specifics are available online at the EIG website.
www.electroind.com

*LonWorks® is a registered trademark of Echelon Corp. Modbus® is a registered trademark of Schneider Electric, licensed to the Modus Organization,
Inc. BACnet® is a registered trademark of ASHRAE. MP200TM is a trademark of Electro Industries/GaugeTech.

Electro Industries/GaugeTech

1800 Shames Drive • Westbury, NY 11590
1- 877-EIMETER (1- 877-346-3837) • E-Mail: sales@electroind.com
Tel: 516-334-0870 • Web Site: www.electroind.com • Fax: 516-338-4741

4

E180702 061914 V.1.01



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : Electro Industries
Create Date                     : 2014:06:25 14:10:47-04:00
Modify Date                     : 2014:06:25 15:00:20-04:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2014:06:25 15:00:20-04:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:e86c76e3-a409-4256-ba01-21e73bc69e67
Original Document ID            : adobe:docid:indd:5546d5a8-555a-11e0-a36c-f7b30d6f168b
Document ID                     : xmp.id:7C6BA6EB93FCE311B17D86F340C0D938
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:7A6BA6EB93FCE311B17D86F340C0D938
Derived From Document ID        : xmp.did:6E11CFCBDCFBE311AAE3D555A0153AD3
Derived From Original Document ID: adobe:docid:indd:5546d5a8-555a-11e0-a36c-f7b30d6f168b
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2014:06:25 14:10:47-04:00
Format                          : application/pdf
Title                           : MP200 in Enclosure Brochure V.1.01
Creator                         : Electro Industries
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 4
EXIF Metadata provided by EXIF.tools

Navigation menu