WC14
14"Wall Commander®
revision 7/19/11 • kim_wc14_spec_.pdf
Approvals:
Specifications Housing and Lens
The complete housing fastens to a mounting plate with keyhole slots freeing both hands for securing
and wiring. Access to field splice is through back of housing.
For UP and UP/DOWN model: One-piece die-cast, low copper (<0.6% Cu) aluminum
alloy. Lens (Up model) and top lens (Up/Down model) is flat F" thick tempered glass
mounted flush with top of housing for water run off, and is silicone sealed.
For DOWN model: Two-piece die-cast, low copper (<0.6% Cu) aluminum alloy. Top of
housing is closed with a die-cast plate with cooling fins to dissipate heat. The top plate is
secured by fasteners and sealed with silicone gasketing around the perimeter.
Access Door (UP model): One-piece die-cast, low copper (<0.6% Cu) aluminum alloy with integral
stainless steel pin hinges. Two stainless steel thumb latches secure the frame to the housing.
Lens Frame (DOWN and UP/DOWN model): One-piece die-cast, low copper (<0.6% Cu)
aluminum alloy with integral stainless steel pin hinges. Two stainless steel thumb latches secure
the frame to the housing. Sealing is provided by a one-piece molded silicone gasket between the
glass lens and the reflector flange. Clear flat lens is F" thick tempered glass secured to lens frame
with retainer clips.
Reflector Module
All sockets are procelain medium base rated 4KV. All models are factory prewired with
quick-disconnect plug for mating to the ballast module.
For all models: Specular Alzak®optical segments rigidly mounted within a die-cast aluminum
enclosure that attaches to the housing by stainless steel hinge and latches. The Wall Grazer and
Spot systems include black louver vanes that run parallel to the lamp arc for controlling the hot
spot directly behind the luminaire, and the spill light into the atmosphere.
Electrical Module: High power factor ballasts are mounted to a rigid aluminum tray
and secured to the housing with screws and key hole slots. Factory prewired with
quick-disconnect plugs for mating to the reflector module and incoming leads.
Mounting Plate: Mounting plate attaches directly to any standard 4" junction box. All mounting
plates are die-cast aluminum with reinforced ribs. Two studs are provided in each plate with
flange nuts to allow luminaire mounting by key hole slots. Sealant must be applied (by others)
between mounting plate and mounting surface to ensure a dry junction box.
Finish/Color: Finish is Super TGIC thermoset polyester powder coat paint, 2.5 mil nominal
thickness, applied over a titanated zirconium conversion coating; A.S.T.M. 2500 hour salt spray
test endurance rating. Standard colors are Black, Dark Bronze, Light Gray, Stealth Gray,
Platinum Silver, or White. Custom colors are available.
CAUTION: Fixtures must be grounded in accordance with national, state and/or local electrical
codes. Failure to do so may result in serious personal injury.
Date:
Page: 1 of 5
19"
(482.6 mm)
12N"
(319.1 mm)
13C"
(339.7 mm)
5N"
(141.3 mm)
Bottom
Front
Back
Side
Top
2D"
(66.7 mm)
to J-box
center
5N"
(141.3 mm)
Type:
Job:
Catalog number:
© 2011 KIM LIGHTING INC. • P.O. BOX 60080, CITY OF INDUSTRY, CA 91716-0080 • TEL: 626/968-5666 • FAX: 626/369-2695
///
Fixture Electrical Module Finish Options
See pages 3-4
See page 2
1Suitable for wet locations
KIM LIGHTING RESERVES THE RIGHT TO CHANGE SPECIFICATIONS WITHOUT NOTICE.
Listings and Ratings
UL cUL 15981CE 25C Ambient
IP66 Rated
50 to 150 watt
Medium Base Lamps
WC14 Mounting Plate
Attaches directly to any
standard 4" J-box (by others)
5"
(127.0 mm) 11D"
(295.3 mm)
Reset Form
WC14
14"Wall Commander®
revision 7/19/11 • kim_wc14_spec_.pdf
Page: 2 of 5
Type:
Job:
Standard Features
© 2011 KIM LIGHTING INC. • P.O. BOX 60080, CITY OF INDUSTRY, CA 91716-0080 • TEL: 626/968-5666 • FAX: 626/369-2695
1For colored up light ray beam, contact factory.
2 Primary grazer or primary spot optics supplied when specified with the ray option. Secondary grazer or secondary spot optics supplied when specified in all other
up/down combination configurations
Refer to the Kim Lighting Wall Commander Catalog for a complete matrix of available configurations.
Fixture
Cat. No. designates WC14
fixture with:
s= Up Light Distribution
t= Down Light Distribution
n/a = not available
Type II Type III Type IV Primary and
Secondary
Grazers
Primary and
Secondary
Spots
Asymmetric Flood Ray
Primary Primary
UP ONLY sType II sType III sType IV sGrazer sSpot sAsymmetric Flood sRay
WC14U2 WC14U3 WC14U4 WC14UG WC14US n/a n/a
Primary Primary
DOWN ONLY tType II tType III tType IV tGrazer tSpot tAsymmetricFlood tRay
WC14D2 WC14D3 WC14D4 WC14DG WC14DS n/a n/a
Secondary Secondary
UP / DOWN sType II sType III sType IV sGrazer sSpot sAsymmetric Flood sRay1,2
tType II n/a n/a n/a WC14UGD2 WC14USD2 WC14UFD2 WC14URD2
tType III n/a n/a n/a WC14UGD3 WC14USD3 WC14UFD3 WC14URD3
tType IV n/a n/a n/a WC14UGD4 WC14USD4 WC14UFD4 WC14URD4
Secondary
tGrazer2WC14U2DG WC14U3DG WC14U4DG WC14UGDG WC14USDG WC14UFDG WC14URDG
Secondary
tSpot2WC14U2DS WC14U3DS WC14U4DS WC14UGDS WC14USDS WC14UFDS WC14URDS
tAsymmetric WC14U2DF WC14U3DF WC14U4DF WC14UGDF WC14USDF WC14UFDF WC14URDF
Flood
Electrical Module
Finish
Super TGIC powder coat paint
over a titanated zirconium
conversion coating.
Cat. Nos. for Electrical Modules available:
WC14
14"Wall Commander®
revision 7/19/11 • kim_wc14_spec_.pdf
Page: 3 of 5
Type:
Job:
Standard Features
© 2011 KIM LIGHTING INC. • P.O. BOX 60080, CITY OF INDUSTRY, CA 91716-0080 • TEL: 626/968-5666 • FAX: 626/369-2695
Lamp Lamp Line
Watts Type Volts
150 PMH 277
Pulse Start Metal Halide
50PMH120 70PMH120 100PMH120 150PMH120
50PMH20870PMH208100PMH208150PMH208
50PMH240 70PMH240 100PMH240 150PMH240
50PMH277 70PMH277 100PMH277 150PMH277
50PMH347 70PMH347 100PMH347 150PMH347
70PMH4803100PMH4803150PMH4803
Lamp ED-17, Clear T6 ED-17, Clear ED-17, Clear T6 ED-17, Clear
Socket Medium Base G-12 Medium Base Medium Base G12 Medium Base
ANSI Ballast M-148 / M-110 M-143 / M-98 M-140 / M-90 M-142 / M102
High Pressure Sodium
70HPS120 100HPS120 150HPS120
70HPS208100HPS208150HPS208
70HPS240 100HPS240 150HPS240
70HPS277 100HPS277 150HPS277
70HPS347 100HPS347 150HPS347
70HPS4803100HPS4803150HPS4803
Lamp ED-17, Clear ED-17, Clear ED-17, Clear
Socket Medium Base Medium Base Medium Base
ANSI Ballast S-62 S-54 S-55
PMH=Pulse Start Metal Halide PL = Compact Fluorescent
HPS=High Pressure Sodium Triple Tube
IF = Induction Fluorescent
Compact Fluorescent Triple Tube Induction Fluor.
42PL120157PL1201, 2, 4 55IF1204
42PL208157PL2081, 2, 4 55IF2084
42PL240157PL2401, 2, 4 55IF2404
42PL277157PL2771, 2, 4 55IF2774
Lamp Coated Coated Induction Fluor.
Socket GX24q-4 Base GX24q-5 Base
ANSI Ballast
1Multiple CFL lamp configurations (ie, two 42W lamps) are possible with certain optical systems. Consult factory for details.
2Remote battery pack and test switch available for 57W CFL lamps - consult factory. “EM” option not available with 55W IF lamps.
3480 volt with medium base lamp sockets may require approval by the local building code authority.
4For Type II, Type III, or Type IV fixtures only. Up or down.
NOTE: Lamp and electrical data supplied for reference purposes only. All initial lumen values shown may vary from one manufacturer to another. Consult lamp
manufacturer’s data for exact lumen and life data.
CAUTION: All manufacturers of metal halide lamps recommend turning them off for 15 minutes once per week when under continuous operation. This will
reduce the risk of arc tube rupture at end of life. Also, color temperature may differ between manufacturers of metal halide lamps. See lamp manufacturers’
specification sheets.
WARNING: Fixtures must be installed and grounded in accordance with national, state and/or local electrical codes. Failure to do so may result in serious personal
injury. For lamp/ballast information outside of the U.S.A. and Canada, please consult our local Kim representative. Lamps by others.
5Custom colors subject to additional charges, minimum quantities and extended lead times.
Consult representative. Custom color description:
Color: Black Dark Bronze Light Gray Stealth GrayPlatinum Silver White Custom Color5
Cat. No.: BL DB LG SG PS WH CC
Wire Guard
Cat. No. WC14WG
No Option
Fusing
Cat. No. (see right)
No Option
WC14
14"Wall Commander®
revision 7/19/11 • kim_wc14_spec_.pdf
Page: 4 of 5
Type:
Job:
Optional Features
Factory installed inside housing with fully gasketed sensor
on side wall.
F" clear convex vacuum formed non-yellowing Lexan®
enclosure with gasket. Mounts over lens to predrilled door
frame holes.
NOTE: Catalog number is for one enclosure. Order
2 enclsoures for both up and down distributions
For use with all WC14 fixtures, UP or DOWN. 11 ga.
(.12"dia.) BB Wire. (.75
"
sq. welded mesh pattern.) Finish is
Super TGIC thermoset polyester powder coat paint, over
zinc plated wireform. Finished to match the fixture. Only
available with flat lens applications.
NOTE: Catalog number is for one wire guard. Order 2 wire
guards for both up and down distributions.
WG14 = 11C" x 10J" x 1K" deep
Photocell Control
Cat. No. (see right)
No Option
© 2011 KIM LIGHTING INC. • P.O. BOX 60080, CITY OF INDUSTRY, CA 91716-0080 • TEL: 626/968-5666 • FAX: 626/369-2695
Lexan®non-yellowing
enclosure
Cat. No. WC14LS
No Option
Cat. No. Line Volts:
A-30 120V
A-31 208V
A-32 240V
Cat. No. Line Volts:
A-33 277V
A-34 480V
A-35 347V
Photocell
Control
Wire Guard
Single Fuse
Lexan®
Enclosure
Quartz Standby
Cat. No. QS
No Option
Integral electronic device energizes a T-4 mini-can socket
during initial lamp start-up or after a power interruption.
De-energizes prior to HID lamp reaching full brightness.
T-4 halogen lamp by others; 100W maximum. Quartz Standby
High temperaure fuse holders factory installed inside the
fixture housing. Fuse is included.
Line Volts: 120V 208V 240V 277V 347V 480V
Cat. No.: SF DF DF SF SF DF
Houseside Shield
Cat. No. HS
No Option
Up or down shield for Type II, III, and IV area optics only.
Combination louver shield and black end-panel for
reflector. Factory installed to reflector module. Reduces light
toward wall.
CAUTION: Do not use the houseside shield option
with the grazer or spot as it will interfere with the
light distribution.
Houseside Shield
Base Socket
Cat. No. G12
No Option
Available for 70W and 150W Pulse Start Metal Halide
lamps only.
Emergency Battery
Back-up
Cat. No. EM
No Option
WC14
14"Wall Commander®
revision 7/19/11 • kim_wc14_spec_.pdf
Page: 5 of 5
Type:
Job:
© 2011 KIM LIGHTING INC. • P.O. BOX 60080, CITY OF INDUSTRY, CA 91716-0080 • TEL: 626/968-5666 • FAX: 626/369-2695
Optional Features
Internal battery pack provides 90 minutes of
supplemental light at 750 lamp lumens on 42 watt
compact fluorescent lamps only.
Remote mounted battery pack also available for 57W
CFL - consult factory.
Direct Conduit Entries
Cat. No. DCE
No Option
Two conduit locations provided on the housing, (1)
on the side wall and (1) on top of housing for
L" conduit clearance.
L" conduit holes
battery back-up
Color Ray Kits
Each color ray kit includes
(5) glass tile pieces,
except for the multi-color
kit which includes (5) of
each color plus (5) clear,
(30 pieces total).
Color: Amber Blue Green Red Yellow Multi-Color
Cat. No.: CRA CRB CRG CRR CRY CRM
Single or multi-color ray kits available.
NOTE: Ray colors and distributions may vary with reflector types, sources, and color
temperatures. Not recommended for all lamp types. Contact factory for more information.
Easy and Flexible Field Installation: Simply arrange the color glass tiles into the slide
channel and replace the retaining pin. Secure the reflector assembly back into the housing
and latch the lens frame shut.
Wall Commander
reflector assembly
with ray option

Navigation menu