Intended Use:
Largest in the Litepak product family, the LNC4 is designed
for perimeter illumination for safety, security and identity.
Replaces up to 400w HID luminaires one-for-one replace-
ment covering existing installation footprint. No uplight and
lower glare lenses offer neighbor friendly lighting at typical
mounting heights of 15-25’. Units have protective polyester
powder coat finish for long lasting appearance. Ideal for
schools, factories, hospitals, warehouses and retail applica-
tions. Energy efficient LEDs provide 70%+ energy savings
with little to no maintenance when compared to traditional
light sources. Battery backup option for meeting path of
egress requirements.
Construction:
Die-cast aluminum housing protects components and
provides an architectural appearance. Casting thermally
conducts LED heat to optimize performance and long life.
Powder paint finish provides durability in outdoor environ-
ments. Four 1/2” conduit entries (top, bottom, and sides)
provided for surface conduit.
Electrical:
120-277, 347 and 480 voltage, 50/60Hz, 0-10V
dimming drivers. Electronic driver. 10 kA surge
protection (parallel); Automatically takes fixture
off-line when device is consumed. Ambient oper
ating temperature -40°C to 40°C.
Lenses:
• Zero uplight distributions using individual acrylic
LED optics provide IES type II, III and IV distributions
CS - Frosted acrylic diffuser option for reduced glare
CSU - Frosted acrylic diffuser for inverted “up”
mounting applications (lens required
LED(s) CCT:
3000K, 4000K and 5000K CCT nominal with
70 CRI. 36 and 44 LED configurations available,
see page 2 for electrical and photometric data
Lumen Maintenance:
L96 at 25,000 hrs (Projected per IESNA TM-21-11), see
table on page 2 for all values
Installation:
Quick-mount adapter with gasket seal provides easy
installation to wall or to recessed junction box (4” square
junction box). Fixture attaches by two Allen-head hidden
fasteners for tamper resistance. Designed for direct j-box
mount or conduit feed on all four sides in single SKU.
Options/Controls
Button photocontrol for dusk to dawn energy savings
7-pin photo-receptacle available for twist lock
photocell and controls by others
Occupancy sensor options available for complete
on/off and dimming control
Integral Battery Backup provides emergency path of
egress lighting for the required 90 minutes
SiteSync pre-commisioned wireless controls (with
or without sensor)
• In addition, the LNC4 can be specified with
SiteSync wireless control system for reduction in energy
and maintenance cost while optimizing light quality 24/7.
See ordering information or visit
www. hubbelllighting.com/sitesync for more details.
Listings
• DesignLights Consortium® (DLC) qualified.
Please refer to the DLC website for specific
product qualifications at www.designlights.org
• Listed to UL1598 and CSAC22.2#250.0-24
for wet locations. IP65 Assembly. IDA Approved
(3000K configurations)
Warranty:
Five year limited warranty (for more information visit: http://
www.hubbelllighting.com/resources/warranty/
SPECIFICATIONS
LITEPAK
SERIES
LNC4
Hubbell Outdoor Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000
Due to our continued efforts to improve our products, product specifications are subject to change without notice.
© 2016 HUBBELL OUTDOOR LIGHTING, All Rights ReservedFor more information visit our website: www.hubbelloutdoor.com • Printed in USA LNC4-SPEC SEPTEMBER 15, 2017 9:45 AM
Cat.#
Approvals
Job Type
With Diffuser
PRODUCT IMAGE(S)
Catalog
Number
G.W(kg)/
CTN
Carton Dimensions Carton Qty.
per Master
Pack
Length
Inch (cm)
Width
Inch (cm)
Height
Inch (cm)
LNC4-36L 27.0 (12.2) 19.7 (50) 13 (33) 13 (33) 1
LNC4-44L
SHIPPING INFORMATION
1 Must specify voltage (battery backup 120 or 277V only, SiteSync 120, 277 or 347V only)
2 Factory install only. Not available with SCP or SWPM sensor/control options
3 Must order minimum of one remote control to program dimming settings, 0-10V fully adjustable dimming with
automatic daylight calibration and different time delay settings, 120-277V only.
4 PCU option not applicable, included in sensor. Must specify sensor height (8F = up to 8ft, 20F = up to 20ft)
5 Accepts standard 3, 5, and 7-Pin ANSI controls (by others). Not available with PCU, SWP or SWPM control options
6 36L-650mA version only. Not available with SWP or SWPM control options.
7 Must specify group and zone information at time or order. See www.hubbelllighting.com/products/sitesync for further details.
8 Specify time delay; dimming level and mounting height
*3000K and warmer CCTs only
A
B
D
E
C
17.2
(436mm)
8.9
(226mm)
6.5
(165mm)
10.5
(266mm)
9.9
(251mm)
A B C D E Weight
17.2” 10.5” 9.9” 6.5” 8.9” 27 lbs.
436 mm 266 mm 251 mm 165 mm 226 mm 12.3 kg
DIMENSIONS
Fixture Weight: 27 pounds
A
B
D
E
C
17.2
(436mm)
8.9
(226mm)
6.5
(165mm)
10.5
(266mm)
9.9
(251mm)
ORDERING INFORMATION – CONFIGURABLE (ORDERING EXAMPLE: LNC4-36L3K-105-3-U-BL-PCU-CS)
LNC4
FAMILY
LNC4 Large
Litepak
Wallpack
NUMBER
OF LEDS
36L 36LED
44L 44LED
IES
DISTRIBUTION
2Type II
3Type III
4Type IV
OPTIONS
F1Fusing (must
specify voltage per
footnote)
CS Frosted acrylic
diffuser
CSU2Frosted acrylic
diffuser required
for inverted fixture
installations
(Factory install
only see page 3)
E1,6 Integral battery
backup rated for
0°C.
EH1,6 Integral battery
backup with heater
rated for -30°C.
VOLTAGE
U120V-277V
1120V1
2208V1
3240V1
4277V1
5480V1
F347V1
FINISH
DB Bronze
BL Black
WH White
GR Gray
PS Platinum
CC Custom
Color
CONTROL OPTIONS
PCU Universal Button PC
7PR57-pin photocell
receptacle
SCP3,4 Programmable
occupancy sensor
SWP1,7 SiteSync
pre-commisioned
SWPM1,4,7,8 SiteSync pre-
commisioned w/
occupancy sensor
Occupancy Sensor
7-Pin PCR Receptacle
Conduit Entry
CERTIFICATIONS/LISTINGS
REPLACEMENT PART/ACCESSORIES,
CATALOG NUMBER
DESCRIPTION
LNC4-CS
Frosted acrylic diffuser reduces surface brightness and glare with a roughly 20% lumen reduction
SCP-REMOTE
*
Remote control for SCP option. Order at least one per project to program and control fixtures
SWUSB*
SiteSync loaded on USB flash drive (Windows based only)
SWTAB*
SiteSync Windows Tablet
SWBRG*
SiteSync Wireless Bridge Node
Must order minimum of one remote control to program dimming settings,
0-10V fully adjustable dimming with automatic daylight calibration and
different time delay settings, 120V or 277V only
** When ordering with SiteSync, one of the following interface
options must be chosen an ordered separately. Each option contains
the SiteSync License, GUI and Bridge Node.
+ If needed, an additional Bridge Node can be ordered.
CCT
3K 3000K
4K 4000K
5K 5000K
DRIVE
CURRENT
035 350mA
065 650mA
105 1150mA
ELECTRICAL DATA
5K (5000K nominal, 70 CRI)
4K (4000K nominal, 70 CRI)
3K (3000K nominal, 70 CRI)
# OF
DRIVE
CURRENT
SYSTEM
WATTS
DIST.
TYPE
LUMENS
LPW
1
B
U
G
LUMENS
LPW
1
B
U
G
LUMENS
LPW
1
B
U
G
N/A
N/A
E
671
N/A
657
N/A
591
N/A
36
350mA
40.3
2
4,529
112
1
0
1
4,593
114
1
0
1
4,269
106
1
0
1
3
4,718
117
1
0
1
4,631
115
1
0
1
4,305
107
1
0
1
4
4,441
110
1
0
2
4,502
112
1
0
2
4,186
104
1
0
2
44 49.3
2
5,536
112
1
0
2
5,613
114
1
0
2
5,218
106
1
0
1
3
5,766
117
1
0
2
5,656
115
1
0
2
5,262
107
1
0
1
4
5,427
110
1
0
2
5,503
112
1
0
2
5,116
104
1
0
2
36
650mA
80
2
7,627
95.3
2
0
2
7,440
93.0
2
0
2
6,756
84.4
2
0
2
3
7,590
94.9
1
0
2
7,404
92.5
1
0
2
6,723
84.0
1
0
2
4
7,611
95.1
1
0
3
7,424
92.8
1
0
3
6,742
84.3
1
0
3
44 96
2
9,094 94.7 202 9,221 96.0 2 0 2 8,572 89.3 2 0 2
3
9,472
98.7
2
0
2
9,298
96.9
1
0
2
8,644
90.0
1
0
2
4
8,916
92.9
1
0
3
9,040
94.2
1
0
3
8,405
87.6
1
0
3
36
1150mA
140
2
11,911
86.6
2
0
2
11,619
84.5
2
0
2
10,551
76.7
2
0
2
3
11,853 90.2 202 11,563 88.0 2 0 2 10,500 79.9 2 0 2
4
11,886
84.9
1
0
3
11,595
82.8
1
0
3
10,529
75.2
1
0
3
44 170
2
14,202 83.6 203 14,400 84.7 3 0 3 13,387 78.7 2 0 2
3
14,793
87.0
2
0
3
14,521
88.2
2
0
3
13,499
82.0
2
0
3
4
13,924
81.9
2
0
3
14,118
83.0
2
0
3
13,127
77.2
2
0
3
Lumen values are from photometric tests performed in accordance with IESNA LM-79-08. Data is considered to be representative of the configurations shown. Actual performance may differ as a result of end-user environment and application.
PERFORMANCE DATA
Hubbell Outdoor Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000
Due to our continued efforts to improve our products, product specifications are subject to change without notice.
© 2016 HUBBELL OUTDOOR LIGHTING, All Rights ReservedFor more information visit our website: www.hubbelloutdoor.com • Printed in USA LNC4-SPEC SEPTEMBER 15, 2017 9:45 AM
Catalog Number Wattage Number of LEDs Voltage Dist. Type Lumens LPW CCT Weight lbs. (Kg) Number of Drivers LED Currentt
LNC4-36L-4K 124.6 36
120-277 4
10,754 86.3
4000°K
27.0 (12.2) 2 1050mA
LNC4-44L-4K 152.6 44 13,477 88.3
LNC4-44L-5K 152.1 44 13,342 87.7 5000°K
LNC4-44L-4K-7PR 152.6 44 13,477 88.3 4000°K
LNC4-44L-4K-SCP 152.6 44 13,477 88.3
ORDERING INFORMATION – STOCKED VERSIONS (ORDERING EXAMPLE: LNC4-44L-4K)
Configurable Versions
# oF
LEDS
Drive Current
(mA)
Input
Voltage
Current
(Amps)
System
Power
36
STD. (1050)mA
120
1.03
124
277
0.45
124
44
120
1.27
152
277
0.55
152
Stocked Versions
# oF LEDS
Drive Current (mA)
Input Voltage
Current (Amps)
System Power
36
350mA
120
0.34
40
277
0.15
40
347
0.12
40
480
0.08
40
44
120
0.41
49
277
0.18
49
347
0.14
49
480
0.10
49
36
650mA
120
0.66
80
277
0.29
80
347
0.23
80
480
0.17
80
44
120
0.80
96
277
0.35
96
347
0.28
96
480
0.20
96
36
1150mA
120
1.17
140
277
0.51
140
347
0.40
140
480
0.29
140
44
120
1.42
170
277
0.61
170
347
0.49
170
480
0.35
170
Catalog Number Description HCS System
NXOFM-1R1D-UNV On-fixture Module (7-pin), On / Off / Dim, Daylight Sensor
with HubbNET Radio and Bluetooth® Radio, 120-480VAC
NX Distributed
Intelligence™
WIR-RME-L On-fixture Module (7-pin or 5-pin), On / Off / Dim, Daylight
Sensor with wiSCAPE Radio, 110-480VAC
wiSCAPE™
Lighting Control
For additional information related to these accessories please visit www.hubbellcontrolsolutions.com. Options provided for use with
integrated sensor, please view specification sheet ordering information table for details.
Hubbell Control Solutions - Accessories (sold separately)
SCP - Programmable Occupancy Sensor
CSU – INVERTED MOUNTING OPTION
(Requires Factory Installed lens option)
Sensor offers greater control and energy savings with SCP program-
mable sensor with adjustable delay and dimming levels (Factory
default is 10%)
Visit: http://www.hubbelllighting.com/solutions/controls/
for control application information
TYPE IV (Foward throw): LNC4-36L-5K-105-4-UTYPE III: LNC4-36L-5K-105-3TYPE II: LNC4-36L-5K-105-2
PHOTOMETRICS
Inverted mounting capabilities for uplighting
applications. Specially designed frosted acrylic
diffuser option softens output, improves
uniformity and protects LED lenses.
7PR-7-PIN RECEPTACLE
(Photocontrol and Wireless Controls by Others)
Standard NEMA 7-Pin receptacle for twist lock
photocell or wireless controls (by others).
SWP & SWPM - SiteSync
SiteSync Lighting Control is available
from our most popular brands in
a broad range of award-winning
product families.
Precommissioned SiteSync Ordering Information:
When ordering a fixture with the SiteSync lighting control option, additional information will be required
to complete the order. The SiteSync Commissioning Form or alternate schedule information must
be completed. This form includes Project locations Group information, and Operating schedules. For
more detailed information please visit www.HubbellLighting.com/proudcts/sitesync or contact Hubbell
Lighting tech support at (800) 345-4928.
SiteSync fixtures with occupancy sensor (SWPM) require the mounting height of the fixture selection
of the lens.
Examples: LNC4-36L4k-105-3-U-DB-SWP SiteSync only
LNC4-36L4k-105-3-U-DB-SWPM-20F SiteSync with Motion Control
11
11
22’
33’
44’ 33’ 22’ 1111 22’ 33’ 44’
11
22’
33’
2fc
.1fc
.5fc
1fc
11' Mounting Height
Hubbell Outdoor Lighting • 701 Millennium Boulevard • Greenville, SC 29607 • Phone: 864-678-1000
Due to our continued efforts to improve our products, product specifications are subject to change without notice.
© 2016 HUBBELL OUTDOOR LIGHTING, All Rights ReservedFor more information visit our website: www.hubbelloutdoor.com • Printed in USA LNC4-SPEC SEPTEMBER 15, 2017 9:45 AM
Provides Life Safety Code average illuminance of 1.0 fc. Assumes open
space with no obstructions.
Diagrams for illustration purposes only, please consult factory for application layout.
PHOTOMETRICS - BATTERY BACKUP E & EH EMERGENCY BATTERY BACKUP
24 High Power LEDs generate up to 7,600
lumens in Normal Mode and use 4 LEDs for up
to 700 lumens in emergency mode.
Mounting Height 20ft
HUBBELL OUTDOOR
LNC4-36L-5K-105-2-U
Large LNC4 Litepak
C-70-CRI
Horizontal Footcandles
Scale: 1 Inch = 20 Ft.
Light Loss Factor = 1.00
Lumens Per Lamp = N.A. (absolute photometry)
Luminaire Lumens = 11911
Mounting Height = 20.00 Ft
Maximum Calculated Value = 5.95 Fc
Arrangement: Single
Photometric Toolbox Professional Edition - Copyright 2002-2011 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations.
Results derived from content of manufacturers photometric file.
HUBBELL OUTDOOR
LNC4-36L-5K-105-3-U
Large LNC4 Litepak
C-70-CRI
Horizontal Footcandles
Scale: 1 Inch = 20 Ft.
Light Loss Factor = 1.00
Lumens Per Lamp = N.A. (absolute photometry)
Luminaire Lumens = 11853
Mounting Height = 20.00 Ft
Maximum Calculated Value = 4.39 Fc
Arrangement: Single
Photometric Toolbox Professional Edition - Copyright 2002-2011 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations.
Results derived from content of manufacturers photometric file.
HUBBELL OUTDOOR
LNC4-36L-5K-105-4-U
Large LNC4 Litepak
C-70-CRI
Horizontal Footcandles
Scale: 1 Inch = 20 Ft.
Light Loss Factor = 1.00
Lumens Per Lamp = N.A. (absolute photometry)
Luminaire Lumens = 11887
Mounting Height = 20.00 Ft
Maximum Calculated Value = 7.48 Fc
Arrangement: Single
Photometric Toolbox Professional Edition - Copyright 2002-2011 by Lighting Analysts, Inc.
Calculations based on published IES Methods and recommendations.
Results derived from content of manufacturers photometric file.
2fc
1fc
.5fc .25fc
40' 40' 40' 40'
0' 0' 0' 0'
20' 20' 20' 20'
20' 20' 20' 20'
60' 60' 60' 60'
80' 80' 80' 80'
2fc
1fc
.5fc
.25fc
2fc
1fc
.5fc
.25fc
20' 20' 20'20' 20' 20'40' 40' 40'40' 40' 40'60' 60' 60'60' 60' 60'0' 0' 0'
LUMINAIRE AMBIENT TEMPERATURE FACTOR (LATF)
PROJECTED LUMEN MAINTENANCE
AMBIENT TEMPERATURE
LUMEN MULTIPLIER
0˚ C
32˚ F
1.02
10˚ C
50˚ F
1.01
20˚ C
68˚ F
1.00
25˚ C
77˚ F
1.00
30˚ C
86˚ F
1.00
40˚ C
104˚ F
0.99
Use these factors to determine relative lumen output for average ambient
temperatures from 0-40°C (32-104°F).
OPERATING HOURS
Ambient
Temp.
0
25,000
50,000
TM-21-111
L96 60,000
100,000
L70
(hours)
25°C / 77°F 1.00 0.96 0.92 0.91 0.85 223,000
40°C / 104°F 1.00 0.94 0.89 0.87 0.80 159,000
1. Projected per IESNA TM-21-11 * (Nichia 219B, 700mA, 85°C Ts, 10,000hrs)
Data references the extrapolated performance projections for the LNC-12LU-5K base model in a 40°C
ambient, based on 10,000 hours of LED testing per IESNA LM-80-08.