User´s Guide: BNI EIP 502 105 R015 / 508 EN Manual
User Manual: Pdf
Open the PDF directly: View PDF .
Page Count: 54
Download | |
Open PDF In Browser | View PDF |
BNI EIP-502-105-R015 BNI EIP-508-105-R015 EtherNet/IP™ IP67 modules User's Guide Table of Contents 1 Notes 1.1. Structure of the guide 1.2. Typographical Conventions Enumerations Actions Syntax Cross-references 1.3. Symbols 1.4. Abbreviations 1.5. Deviating views 3 3 3 3 3 3 3 3 3 3 2 Safety 2.1. Intended Use 2.3. General Safety Notes 2.4. Resistance to Aggressive Substances Dangerous Voltage 4 4 4 4 4 3 First Steps 3.1. Module Overview 3.2. Mechanical Connection 3.3. Electrical Connection Power Supply Grounding Ethernet IP Interface I/O Port IO-Link Port Port 5 5 6 6 6 6 6 7 7 7 4 Technical Data 4.1. Dimensions 4.2. Mechanical Data 4.3. Operating Conditions 4.4. Electrical Data 4.5. Ethernet 4.6. Function Indicators Module Status Port 8 8 8 8 8 9 9 9 10 5 Integration 5.1. Integration in Rockwell RS Logix 5000 5.2. Address Specifications 5.3. Data Configuration 5.4. Configuration Data Module Configuration BNI EIP-502-105-XXX Module Configuration BNI EIP-508-105-XXX Module Configuration BNI EIP-507-005-Z040, BNI EIP-527-005-Z040 Module Configuration BNI EIP-508-XXX-XXXX-C06 IO-Link Port Configuration Cycle Settings Validation Settings Parameter Server Upload Flag on the IO-Link Device 11 11 15 15 15 16 16 16 16 17 18 18 19 19 6 Configuration via Explicit Messages QuickConnect Rockwell Automation Products that are Compatible with QuickConnect www.balluff.com 20 20 21 1 Balluff Network Interface EtherNet/IP™ Example with Rockwell Components PLC Program Fault State Enable/Disable Fault State Fault State Action IO-Link Device Parameterization Read IO-Link Parameter Write IO-Link Parameter 22 23 26 26 26 27 27 29 7 Process Data 7.1. Process Data Inputs Standard Input Data IO-Link Input Data 7.2. Process Data Outputs Standard Output Data IO-Link Output Data 30 30 30 31 32 32 32 8 Display 8.1. General 8.2. Address Specifications 8.3. Control and Display 8.4. Display Information 8.5. Design and Symbols 8.6. Startup 8.7. Main Menu 8.8. IP Setup 8.9. Network Config 8.10. Edit mode 8.11. Module Information 8.12. General Information 33 33 33 33 33 34 34 34 35 35 36 37 37 9 Web Server 9.1. General 9.2. Navigation / Info 9.3. Login/Logout 9.4. "Home" dialog 9.5. "Ports" dialog No appropriate IODD uploaded Appropriate IODD uploaded 9.6. "IODD" dialog 9.7. "Config" dialog 9.8. "Log" dialog 38 38 39 40 41 43 43 44 46 47 49 10 Appendix 10.1. Scope of Delivery 10.2. Order Number 10.3. Ordering Information 51 51 51 51 Notes www.balluff.com 52 2 1 Notes 1.1. Structure of the guide This guide is arranged so that one chapter builds upon the other. Chapter 2: Basic safety instructions Chapter 3: Main steps for installing the device ……… 1.2. Typographical Conventions The following typographical conventions are used in this manual. Enumerations Enumeration is shown in the form of bulleted lists. • Entry 1, • Entry 2 Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated by an arrow. Action instruction 1. Result of action. Action instruction 2. Actions can also be indicated as numbers in parentheses. (1) Step 1 (2) Step 2 Syntax Numbers: Decimal numbers are shown without additional information (e.g. 123), Hexadecimal numbers are shown with the additional indicator hex (e.g., 00 hex) or the prefix "0x" (e.g., 0x00). Cross-references Cross-references indicate where additional information on the topic is located. 1.3. Symbols Note This symbol indicates general notes. Attention! This symbol indicates a security notice which most be observed. 1.4. Abbreviations BNI I EIP EMC FE O 1.5. Deviating views Product views and illustrations in this manual may differ from the actual product. They are intended only as illustrative material. www.balluff.com Balluff Network Interface Standard input port EtherNet/IP™ Electromagnetic compatibility Function ground Standard output port 3 Balluff Network Interface EtherNet/IP™ 2 Safety 2.1. Intended Use 2.2. Installation and Startup 2.3. General Safety Notes 2.4. Resistance to Aggressive Substances Dangerous Voltage The BNI EIP-… is a decentralized IO-Link, input and output module for connecting to the EtherNet/IP™ network. Attention! Installation and startup are to be performed by trained technical personnel only. Skilled specialists are people who are familiar with the work such as installation and the operation of the product and have the necessary qualifications for these tasks. Any damage resulting from unauthorized tampering or improper use shall void warranty and liability claims against the manufacturer. The operator is responsible for ensuring that the valid safety and accident prevention regulations are observed in specific individual cases. Commissioning and inspection Before commissioning, carefully read the User's Guide. The system must not be used in applications in which the safety of persons depends on the function of the device. Intended use Warranty and liability claims against the manufacturer shall be rendered void by damage from: • Unauthorized tampering • Improper use • Use, installation or handling contrary to the instructions provided in this User's Guide. Obligations of the owner/operator The device is a piece of equipment in accordance with EMC Class A. This device can produce RF noise. The owner/operator must take appropriate precautionary measures against this for its use. The device may be used only with a power supply approved for this. Only approved cables may be connected. Malfunctions In the event of defects and device malfunctions that cannot be rectified, the device must be taken out of operation and protected against unauthorized use. Intended use is ensured only when the housing is fully installed. Attention! The BNI modules always have good chemical and oil resistance. When used in aggressive media (such as chemicals, oils, lubricants and coolants, each in a high concentration (i.e. too little water content)), the material must first be checked for resistance in the particular application. No defect claims may be asserted in the event of a failure or damage to the BNI modules caused by such aggressive media. Attention! Before working on the device, switch off its power supply. Note In the interest of continuous improvement of the product, Balluff GmbH reserves the right to change the technical data of the product and the content of these instructions at any time without notice. www.balluff.com 4 3 First Steps 3.1. Module Overview 17 1 2 16 3 4 15 5 14 6 7 13 8 12 9 11 10 1 Figure – Overview: BNI EIP-508-105-R015 1 2 3 4 5 6 7 8 9 www.balluff.com Mounting hole EtherNet/IP™ port 2 Display Power supply, input Status LED: communication / module Port 08 / 09 (IO-Link, standard I/O) Pin/port LED: signal status Port 10 / 11 (IO-Link, standard I/O) Port 12 / 13 (IO-Link, standard I/O) 10 11 12 13 14 15 16 17 Port 14 / 15 (IO-Link, standard I/O) Port 06 / 07 (IO-Link, standard I/O) Port 04 / 05 (IO-Link, standard I/O) Port 02 / 03 (IO-Link, standard I/O) Port 00 / 01 (IO-Link, standard I/O) Power supply, output EtherNet/IP™ port 1 Ground connection 5 Balluff Network Interface EtherNet/IP™ 3 First Steps 3.2. Mechanical Connection The module is secured by means of two M6 screws and two washers. Insulation support is available separately. 3.3. Electrical Connection Power Supply IN 7/8”, male Pin Function 1 +24 V Actuator supply 2 +24 V Module / sensor supply 3 OUT 0V 4 Description GND module / sensor and actuator supply 7/8” female Note Where possible, use a separate power source to supply the sensor/bus and actuator with power. Total current < 9 A The total current of all modules must not exceed 9 A even in the case of series connection of the actuator supply. Grounding Note The functional ground connection between housing and machine must have a low impedance and be as short as possible. Ethernet IP Interface www.balluff.com M12, D-coded, female Pin 1 2 3 4 Tx+ Rx+ TxRx- Function Transmit Data + Receive Data + Transmit Data Receive Data - 6 3 First Steps I/O Port M12, A-coded, female Pin 1 2 3 4 5 Function +24 V, 200 mA Input/output 2A GND Input/output 2A FE Note For the digital sensor inputs, refer to guideline on inputs EN 61131-2, Type 2. Note The total current of the module must not exceed 9 A. Note Unused I/O ports must be provided with cover caps to comply with degree of protection IP67. IO-Link Port M12, A-coded, female Pin 1 2 3 4 5 Function +24 V, 1.6 A Input/output 2A GND IO-Link/input/output 2A n.a. Port BNI EIP-502-105-R015 BNI EIP-508-105-R015 www.balluff.com Port 00/01, 02/03, 08/09, 10/11 04/05, 06/07, 12/13, 14/15 IN / OUT IN / OUT / IO-Link IN / OUT / IO-Link 7 Balluff Network Interface EtherNet/IP™ 4 Technical Data 4.1. Dimensions 4.2. Mechanical Data 4.3. Operating Conditions 4.4. Electrical Data www.balluff.com Housing material Plastic housing, resistant (Fortron 6165 A6 black) Enclosure rating per IEC 60529 IP 67 (only when plugged-in and threaded-in) Supply voltage 7/8" 4-pin, connector / female Input ports / output ports M12, A-coded (8x female) Dimensions (W x H x D in mm) 68 x 226 x 42.9 Type of mounting Screw mounting with 2 mounting holes Ground strap installation M4 Weight Approx. 670 gr. Operating temperature Ta Storage temperature -5 °C ... 70 °C -25 °C ... 70 °C EMC - Immunity - Emission EMC Directive 2004/108/EEC - EN 61000-6-2 - EN 61000-6-4 Shock/vibration EN 60068-2-6, EN 60068-2-27 EN 60068-2-29, EN 60068-2-64 Supply voltage 18...30.2 V DC, in accordance with EN 61131-2 Ripple < 1% Input current at 24 V 130 mA 8 4 Technical Data 4.5. Ethernet Ethernet IP port 2 x 10Base/100Base Tx Connection for Ethernet IP port M12, D-coded, female Cable types in accordance with IEEE 802.3 Shielded, twisted pair min. STP CAT 5/ STP CAT 5e Data transmission rate 10/100 Mbps Max. cable length 100 m Flow control Half-duplex/full-duplex (IEEE 802.33x pause) 4.6. Function Indicators Status LEDs Port LEDs Module Status LED UA US Mod Netw ork 100 LNK www.balluff.com Display Green Red, flashing Red Green Red, flashing Green, flashing Green Red, flashing Red-green, flashing Off Green, flashing Green Red, flashing Red-green, flashing Off Yellow Green Description Output power OK Low output power (< 18V) No output power (< 11V) Input power OK Low input power (< 18V) Incorrect or no configuration of the module Module is working Fixed bus clock is not possible Initial sequence Module has no IP address Module has IP, but no connection established Connection established Connection timeout Initial sequence Bus clock: 10 Mbps Bus clock: 100 Mbps Data transfer 9 Balluff Network Interface EtherNet/IP™ 4 Technical Data Port Each port has two bicolored LEDs for displaying the I/O statuses. IO-Link port I/O port Display www.balluff.com Status Description Off I/O status The status of the input or output pins is 0 Yellow Red, flashing Red I/O status The status of the input or output pins is 1 Short-circuit Short-circuit between pin 1 and 3 Short-circuit Short-circuit at dedicated pin Green Green, flashing Green, rapidly flashing Red Red, flashing quickly IO-Link IO-Link communication active IO-Link No IO-Link communication IO-Link IO-Link pre-operate during data storage Short-circuit Short-circuit at pin 4 Validation failed / Data storage failed / Wrong device for data storage IO-Link 10 5 Integration 5.1. Integration in Rockwell RS Logix 5000 Here you see an example of how the module can be integrated into a Rockwell RS Logix 5000: First go offline Right-click Ethernet (on the correct scanner card) Select a new module www.balluff.com 11 Balluff Network Interface EtherNet/IP™ 5 Integration Then select the general Ethernet module as the ETHERNET module in the communication path Now enter a user-defined tag name to select the general format Data-SINT, to enter the IP address of the module and to enter the correct connection parameters. www.balluff.com 12 5 Integration The new module and corresponding controller tags are generated automatically. Then download the configuration www.balluff.com 13 Balluff Network Interface EtherNet/IP™ 5 Integration When the download is done, you can observe and control the tags using the Controller Tags option. Make sure you select the correct tag name, which you configured beforehand. The input, output and configuration data for this is described on the following pages. You can use these tags for the programming, too. www.balluff.com 14 5 Integration 5.2. Address Specifications These settings are factory-set. IP-Adresse: 192.168.1.1 Subnetmaske: 255.255.255.0 Gatewayadresse: 192.168.1.1 5.3. Data Configuration Please enter the following values in the control system. They describe the data sizes of the input, output and configuration data. Instanc ID Input Output CONFIG 5.4. Configuration Data 100 101 102 502 200 134 98 508 392 262 194 Data length 507 196 130 98 527 196 128 98 508-C06 128 86 0 The following tables show an allocation of the configuration data sequence. The standard values specified below describe a configuration with the IO-Link function at Pin 4 and standard I/O functions at Pin 2 and 4 of each port. The input and output functions of the configured standard I/O ports are set via the process data. BNI EIP-502-105-XXXX, BNI EIP-507-005-Z040, BNI EIP-527-005-Z040 Slot 1 2 3 4 5 Byte 0…1 2…25 26…49 50…73 74…97 Module part Module IO-Link port 0 IO-Link port 1 IO-Link port 2 IO-Link port 3 Description General configuration for the entire module Configuration of IO-Link port 0 Configuration of IO-Link port 1 Configuration of IO-Link port 2 Configuration of IO-Link port 3 BNI EIP-508-105-XXXX Byte 0…1 2…25 26…49 50…73 74…97 98…121 122…145 146…169 170…193 Slot 1 2 3 4 5 6 7 8 9 Module part Module IO-Link port 0 IO-Link port 1 IO-Link port 2 IO-Link port 3 IO-Link port 4 IO-Link port 5 IO-Link port 6 IO-Link port 7 Description General configuration for the entire module Configuration of IO-Link port 0 Configuration of IO-Link port 1 Configuration of IO-Link port 2 Configuration of IO-Link port 3 Configuration of IO-Link port 4 Configuration of IO-Link port 5 Configuration of IO-Link port 6 Configuration of IO-Link port 7 Note The BNI EIP-508-XXX-XXXX-C06 has no configuration data. These are fixed and can not be changed. www.balluff.com 15 Balluff Network Interface EtherNet/IP™ Module Configuration BNI EIP-508-105XXX Module Configuration BNI EIP-507-005Z040, BNI EIP527-005-Z040 www.balluff.com 6 5 4 Description 3 2 1 0 P3 P2 - - 1 P7 P6 - - 7 6 5 4 Description 3 2 1 0 P3 P2 P1 P0 1 P7 P6 P5 P4 0 Port function 0x00: Standard I/O 0x01: IO-Link Bit 0 1 Module Configuration BNI EIP-508-XXXXXXX-C06 Bit 7 0 Byte Module Configuration BNI EIP-502-105XXX Byte Integration Byte 5 Port function 0x00: Standard I/O 0x01: IO-Link Bit 7 6 P3 5 4 Description 3 P2 2 P1 Reserved 1 0 P0 Port function 0x00: Standard I/O 0x01: IO-Link The IO-Link ports are always activated. 16 Integration IO-Link Port Configuration Byte 5 2 6 Basic 5 4 Description 3 2 Time 3 Validation type 4 5 6 7 8 9 … 24 Vendor ID 1 Vendor ID 2 Device ID 1 Device ID 2 Device ID 3 Serial number 1 … Serial number 16 25 … www.balluff.com Bit 7 1 0 Cycle time Validation type 0 No validation 1 compatible (VID + DID) 2 Identical (VID + DID + SerNum) Vendor ID Device ID Serial number Parameter server 0x8X Enable 0x0X Disable Parameter server 0x40 Delete 0xX1 Enable upload 0xX2 Disable download The data of the other IO-Link ports is structured identically and described in the following. For the BNI EIP-508-xxx-xxxx-C06 these data are not adjustable. 17 Balluff Network Interface EtherNet/IP™ Cycle Settings This parameter can be used to influence the IO-Link communication speed. Calculated using the multiplier and the time base, the IO-Link cycle time can be increased. The time base is described in Table B3. The multiplier is entered in decimal form from 0…63. Bit 7 6 Time base 5 4 Description 3 2 1 Multiplier 0 Bit 0 to 5: Multiplier These bits contain a 6-bit multiplier for the calculation of MasterCycleTime or MinCycle Time. Permissible values for the multiplier are 0 to 63. Bit 6 to 7: Time Base These bits specify the time base for the calculation of MasterCycleTime or MinCycleTime. Possible values of MasterCycleTime and MiniCycleTime Time base encoding Time base value 00 01 0.1 ms 0.4 ms 10 1.6 ms Calculation Multiplier x time base 6.4 ms + multiplier x time base 32.0 ms + multiplier x time base Cycle time 0.4 ms to 6.3 ms 6.4 ms to 31.6 ms 32.0 ms to 132.8 ms 11 Reserved Reserved Reserved NOTE: The value 0.4 results from the minimum possible transmission time according to A.3.7. Validation Settings www.balluff.com No validation: validation deactivated, every device will be accepted. Compatibility: manufacturer ID and device ID are compared to the IO-Link device data. Identity: manufacturer ID and device ID and serial number are compared to the IO-Link device data. The IO-Link communication is only started if there is a match. 18 5 Integration Parameter Server Enable: data management functions enabled, parameter data and identification data of the IO-Link device are stored permanently. Disable: data management functions disabled, stored parameter data and identification data of the IO-Link device remain stored. Deleted: data management functions disabled, stored parameter data and identification data of the IO-Link device are deleted. Enable upload: If only the upload is enabled, the master always starts an upload of the parameter data. In this case, the upload is independent of the upload flag of the IO-Link device. If no data is stored in the Master Port, an upload likewise takes place. (e.g. after deleting the data or before the first data upload) Enable download: If only the download is enabled, the master always starts a download of the parameter data. In this case, the download is likewise independent of the upload flag of the IO-Link device. If no data is stored in the Master Port, however, an upload takes place first. (e.g. after deleting the data or before the first data upload) Enable upload and download: If the upload and download are enabled, different parameter sets are distinguished depending on the upload flag of the IO-Link device. If no parameter data is stored in the IO-Link master port, an initial upload takes place. (e.g. after deleting the data or before the first data upload) If the upload flag is set on the IO-Link device, an upload of the parameter data always takes place. If no upload flag is set and parameter data has already been stored, a download of the parameter data always takes place. Note After the upload of the parameter data, the vendor ID and device ID of the connected IO-Link device are also still saved until the data records are deleted. When the connected IO-Link device is started, a validation takes place. Thus, only an IO-Link device of the same type can be used for the data management. If an IO-Link device of a different type is to be used, the contents of the parameter server must be deleted. The data storage is supported only by IO-Link devices with IO-Link Revision 1.1. Upload Flag on the IO-Link Device The upload flag is needed to overwrite already saved data in the parameter server with new parameter data of the same IO-Link device. To enable the upload flag of an IO-Link device, the data value 0x05 must be entered in the index 0x02, subindex 0. (For information about configuration via IO-Link, refer to the "Web Server" chapter under "Device Properties" or the "Configuration via Explicit Messages" chapter under "IO-Link Device Parameterization") www.balluff.com 19 Balluff Network Interface EtherNet/IP™ 6 Configuration via Explicit Messages QuickConnect The QuickConnect function makes it faster to boot up and integrate the BNI EIP-50x-105X015 modules. Enabling QuickConnect automatically takes over all necessary port properties on the module: Static IP address Ports at 100 Mbps full-duplex Auto-negotiation disabled Auto MDI-X disabled Prepared for linear topology You can configure QuickConnect via the following class instance attribute of the explicit messages: Class 245 (0xF5) Instance 1 (0x01) Attribute 12 (0x0C) Value 0: disabled (default) 1: enabled Note For QuickConnect to be enabled, ACD (Address Conflict Detection) must also be enabled. This is switched on by default. The ACD can be reviewed and changed using the following class instance attributes of the explicit messages: Class 245 (0xF5) www.balluff.com Instance 1 (0x01) Attribute 10 (0x0A) Value 0: disabled 1: enabled(default) 20 6 Configuration via Explicit Messages Rockwell Automation Products that are Compatible with QuickConnect Source: Allen-Bradley Ethernet/IP QuickConnect Application Technique Page 13 www.balluff.com 21 Balluff Network Interface EtherNet/IP™ 6 Configuration via Explicit Messages Example with Rockwell Components Source: Allen-Bradley Ethernet/IP QuickConnect Application Technique, Page 12 Please also note the following: www.balluff.com Direct connection between PLC and QuickConnect slave with crossover cable Slave-to-slave connection using patch cable For setting up the topology, only the linear topology with a maximum of 20 modules on the tool side is permitted. If needed, only one managed switch may be used between the PLC and Ethernet/IP slave. To trigger the QuickConnect sequence, an electrical lock signal is required that reads in the supply voltage of the QuickConnect slaves via the controller. 22 6 Configuration via Explicit Messages PLC Program Source: Allen-Bradley Ethernet/IP QuickConnect Application Technique, Page 29 www.balluff.com 23 Balluff Network Interface EtherNet/IP™ 6 Configuration via Explicit Messages Source: Allen-Bradley Ethernet/IP QuickConnect Application Technique, Page 30 www.balluff.com 24 6 Configuration via Explicit Messages Source: Allen-Bradley Ethernet/IP QuickConnect Application Technique, Page 31 www.balluff.com 25 Balluff Network Interface EtherNet/IP™ 6 Configuration via Explicit Messages Source: Allen-Bradley Ethernet/IP QuickConnect Application Technique, Page 32 Fault State A safe state that the port is to take on in the case of a loss of bus communication can be predefined for each output on the port pins. The fault state settings can be configured using the following class instance attributes of the explicit messages. Enable/Disable Fault State Class 9 (0x09) Instance 1–m Attribute 6 Value 0: Fault state disabled 1: Fault state enabled Fault State Action Class 9 (0x09) Instance 1–m Attribute 5 Value 0: Output on 1: Hold last state m: Number of outputs Note The fault state settings are stored only temporarily in the module. They are deleted after a power reset. To ensure a long-term fault state configuration, the configuration has to be programmed via the PLC so that the settings are transferred to the module again when the system is restarted. www.balluff.com 26 6 Configuration via Explicit Messages IO-Link Device Parameterization There are two options for configuring an IO-Link device connected to the IO-Link port. Configuration via the web server refer to the "Web Server" chapter under "Device Properties" Configuration via explicit messages The following example describes how Rockwell RSLogix 5000 devices can be used to configure an IO-Link device via explicit messages. For this purpose, the "MSG" components in the PLC program are used. Read IO-Link Parameter Service Code 0x32 Class 0x96 Instance 1-n Attribute 0x03 (Read Parameter) n: Number of ports Source Length must correspond to at least the read parameters, but a larger value can also be entered. (In this example, 100 bytes) As the Source Element (Write) and as the Destination Element (Read), create one SINT[100] array each and select the first line[0]. www.balluff.com 27 Balluff Network Interface EtherNet/IP™ 6 Configuration via Explicit Messages In the Source Element Array (Write), enter which index is to be read. In this example, this is index 0x4E. Destination Array (Read) shows the read-out value. In case of a configuration error, the error code is likewise displayed there. In the "Communication" window, you have to select the Ethernet module on which the configuration is to take place. www.balluff.com 28 6 Configuration via Explicit Messages Write IO-Link Parameter Service Code 0x32 Class 0x96 Instance 1-n Attribute 0x02 (Write Parameter) n: Number of the ports Source Element and Destination Element are to be selected so they are identical to the previous example, "Read IO-Link parameter". The Source Length must be exactly the same length as the parameter data to be written. In this example, index 0x4E, subindex 0, value 0x02 is written in Source Element Array (Write). In case of a configuration error, an error code appears in Destination Element Array (Read). In the "Communication" window, you likewise have to select the Ethernet module on which the configuration is to take place. Note The explicit messages functions are implemented in accordance with the Volume 1: Common Industrial Protocol Specification and Volume 2: Ethernet/IP Adaption of CIP. www.balluff.com 29 Balluff Network Interface EtherNet/IP™ Process Data 7.1. Process Data Inputs Standard Input Data www.balluff.com The input data size is 200 bytes. Take a look at the tables below for the allocation of the process data inputs. BNI EIP-502-105-R015 Byte Module part 0…7 Standard I/O ports 8…55 IO-Link port 1 56…103 IO-Link port 2 104…151 IO-Link port 3 152…199 IO-Link port 4 Description Process data inputs at the standard inputs Process data inputs at IO-Link port 1 Process data inputs at IO-Link port 2 Process data inputs at IO-Link port 3 Process data inputs at IO-Link port 4 BNI EIP-508-105-R015 Byte Module part 0…7 Standard I/O ports 8…55 IO-Link Port 0 56…103 IO-Link port 1 104…151 IO-Link port 2 152…199 IO-Link port 3 200…247 IO-Link port 4 248…295 IO-Link port 5 296…343 IO-Link port 6 344…391 IO-Link port 7 Description Process data inputs at the standard inputs Process data inputs at IO-Link port 0 Process data inputs at IO-Link port 1 Process data inputs at IO-Link port 2 Process data inputs at IO-Link port 3 Process data inputs at IO-Link port 4 Process data inputs at IO-Link port 5 Process data inputs at IO-Link port 6 Process data inputs at IO-Link port 7 BNI EIP-502-105-R015 and BNI EIP-508-105-R015 Byte 7 7 6 5 4 3 2 1 0 0 I32 I34 I22 I24 I12 I14 I02 I04 1 I72 I74 I62 I64 I52 I54 I42 I44 Bit 2 S3 S2 S1 3 S7 S6 S5 S0 S4 4 O32 O34 O22 O24 O12 O14 O02 O04 5 O72 O74 O62 O64 O52 O54 O42 O44 6 0 0 0 0 0 NA PS PA 7 0 0 0 0 0 0 0 0 Description Input data I04 Input at port 0, pin 4 The result is 0 only if the port is configured as an IO-Link port. Short-circuit status Short-circuit between pin 1 and 3 at the registered port Overload status O04 Overload at port 0, pin 4 Only if the port is configured as an output. Status of the power supply NV: No actuator power supply PS: Power supply for sensor PA: Power supply for actuator Reserved 30 7 Process Data BNI EIP-502-105-R015 and BNI EIP-508-105-R015 Byte IO-Link Input Data Bit 7 6 5 4 3 2 1 8 … 39 0 0 0 0 0 0 DC IOL 41 SC 0 0 0 0 PDI DF VF 55 … www.balluff.com IO-Link port 0 input data 40 42 43 44 45 46 47 48 49 50 51 52 53 54 Description 0 Mode Vendor ID 1 Vendor ID 2 Device ID 1 Device ID 2 Device ID 3 Type Event code high Event code low Type Event code high Event code low Type Event code high IO-Link status IOL: Port in IO-Link mode DC: Device connected 0: Reserved IO-Link error VF: Validation failed SC: IO-Link short-circuit DF: Data storage validation failed PDI: Process data invalid Vendor ID Device ID 0 Mode: 0: Reserved 1: Event single shot 2: Event disappears Mode 0 3: Event appears Event 2 Type: 0: Reserved Mode 0 1: Notification Event 3 2: Warning Event code low 3: Error The data of the other IO-Link ports are structured identically and described in the following. Event 1 31 Balluff Network Interface EtherNet/IP™ 7 Process Data 7.2. Process Data Outputs Standard Output Data IO-Link Output Data The output data size is 134 bytes. Take a look at the tables below for the allocation of the process data outputs. BNI EIP-502-105-R015 Byte Module part 0…5 Standard I/O ports 6…37 IO-Link port 1 38…69 IO-Link port 2 70…101 IO-Link port 3 102…133 IO-Link port 4 Description Process data outputs at the standard inputs Process data outputs at IO-Link port 1 Process data outputs at IO-Link port 2 Process data outputs at IO-Link port 3 Process data outputs at IO-Link port 4 BNI EIP-508-105-R015 Byte Module part 0…5 Standard I/O ports 6…37 IO-Link Port 0 38…69 IO-Link port 1 70…101 IO-Link port 2 102…133 IO-Link port 3 134…165 IO-Link port 4 166…197 IO-Link port 5 198…229 IO-Link port 6 230…261 IO-Link port 7 Description Process data outputs at the standard inputs Process data output at IO-Link port 0 Process data output at IO-Link port 1 Process data output at IO-Link port 2 Process data output at IO-Link port 3 Process data output at IO-Link port 4 Process data output at IO-Link port 5 Process data output at IO-Link port 6 Process data output at IO-Link port 7 Byte 6 5 4 3 2 1 0 0 O32 O34 O22 O24 O12 O14 O02 O04 1 O72 O74 O62 O64 O52 O54 O42 O44 2 R32 R34 R22 R24 R12 R14 R02 R04 3 R72 R74 R62 R64 R52 R54 R42 R44 4 0 0 0 0 0 0 0 0 5 0 0 0 0 0 DL GO RO 7 6 5 4 3 2 1 0 Byte 6…37 … www.balluff.com Bit 7 Bit Description Output data O04 Output at port 0, pin 4 To use this function at an IOLink port, the port has to be configured as an output. Restart Restart of the output after a short-circuit is detected Reserved Display control system DL: Display disabled / PLC lock GO: Green display LED illuminates RO: Red display LED illuminates Description IO-Link port 0 output data The data of the other IO-Link ports are structured identically and described in the following. 32 8 Display 8.1. General With the implemented display, the address is output directly to the devices BNI EIP… The following address types are possible: • IP address • Subnet mask • Gateway address Each address is composed of 4 octets. The display also shows information about the hardware and firmware update. The display has a locking function that can be enabled from the control panel. If the lock is set, no more editing can be done (see bit layout, Chapter 6.2 Standard output data). 8.2. Address Specifications IP address: Subnet mask: Gateway address: 8.3. Control and Display 192.168.1.1 255.255.255.0 192.168.1.1 6 IP SN GW S 5 ↑ 3 4 1 Display 2 Arrow key 3 Octet cursor 8.4. Display Information 2 1 0 1 2 3 4 Address type cursor 5 "Set" key 6 LED Cursor for selecting the address type Cursor for selecting the address type IP SN IP GW 3 2 1 0 Cursor for selecting the octet IP: IP address SN: Subnet address GW: Gateway address www.balluff.com 3: First octet 2: Second octet 1: Third octet 0: Fourth octet 33 Balluff Network Interface EtherNet/IP™ 8 Display 8.5. Design and Symbols In the following flow charts, some symbols are used to describe the display functionality: Current status Switch S Condition: Briefly press the Set key S Condition: Press and hold the Set key (at least 3 seconds) Condition: Briefly press the arrow key 8.6. Startup BALLUFF BALLUFF BNI EIP-508105-R015 Module name VERSION HW: 1.0 SW: 1.0 Hardware and firmware update IP 192 . 168 . 015 . 005 Current IP Subnet 255 . 255 . 255 . 000 Current subnet mask e Gateway 000 . 000 . 000 . 000 Current gateway address 8.7. Main Menu Standard view 4th octet of the IP address 007 S Network Config Menu: Network Config … S Menu: IP Setup S IP SETUP … S Menu: Module Information • • www.balluff.com MODULE INFO … Press the Set key briefly to scroll through the main menu. Press the arrow key to open the menu. 34 8 Display 8.8. IP Setup X STATIC DHCP FACTORYSETTING IP editing mode S S S STATIC DHCP X FACTORYSETTING S STATIC X DHCP FACTORYSETTING X STATIC DHCP FACTORYSETTING Editing mode • • Press and hold the Set key to call up the editing mode. The preferred value is configured by briefly pressing the arrow key. 8.9. Network Config IP 192.168. 015.005 S S 168 S 192 • • • • • • www.balluff.com S 000 S 255 S 255 S 255 Gateway 000.000. 000.000 S S Editing mode Programming mode 005 015 S Editing mode Programming mode Editing mode Programming mode S Subnet 255.255. 255.000 000 S 000 S S 000 S 000 Press and hold the Set key to call up the editing mode. The preferred value is configured by briefly pressing the arrow key. Press and hold the arrow key to call up the fast program mode. Briefly pressing the Set key saves the entered value and scrolls to the next octet. The 4th octet represents the beginning of the editing process. The completely entered address is saved by briefly pressing the Set key when editing the first octet. The entered value appears right afterwards in the IP overview display. Manual changes to IP, subnet or gateway lead to an automatic change of the IP setup to "static". 35 Balluff Network Interface EtherNet/IP™ 8 Display 8.10. Edit mode • • • • • In the Network Configuration menu, select IP / Subnet or Gateway Address. Press the set button long to switch to edit mode. Press the arrow key briefly to change the number. Press the Set button briefly to move to the next position. After the last digit, press the set button briefly to move to the next octet of the address or to accept the new number after the last octet. Note The module has to be restarted to work with the new configuration. www.balluff.com 36 8 Display 8.11. Module Information BNI EIP-508105-R015 • • 8.12. General Information • • • • • • • • Version SW: x.x HW: x.x MAC ID XX : XX : XX : XX : XX : XX Briefly pressing the arrow key allows scrolling through the "Module information" menu. The product name, module updates and Mac-ID are displayed as information. Press and hold the arrow key to scroll quickly in editing mode. If no key is pressed for 10 seconds, the view reverts to the standard display (4th octet of the IP address). Changes that have not been saved will be lost. Differences between the new configuration and the configuration with which the module works are indicated by an unequal sign. In this case, the screen switches to the standard display after 5 seconds. The display flashes in editing mode. The display flickers in fast scroll mode. If the module receives a single ping, the word "Ping" appears on the display for a couple of seconds. Then the previous display returns. You can exit ping mode sooner by briefly pressing the Set key. If the module receives two or more pings, the word "Ping" appears on the display. You can exit the display only by briefly pressing the Set key. Then the display before the ping returns. The LED function of the display LEDs can be set in a user-specific manner by setting several bits in the process data outputs. (see bit layout, standard output data) The plc lock function can also be used by setting a bit in the process data outputs. (see bit layout, standard output data) Note You cannot select editing mode in the display if the plc lock is set in the process data inputs by a bit (see bit layout, standard output data) www.balluff.com 37 Balluff Network Interface EtherNet/IP™ 9 Web Server 9.1. General The BNI fieldbus module contains an integrated web server for retrieving detailed device information and for configuring the device. To use the web interface you must first ensure that the module has been correctly integrated into your network. In addition the IP subnet of the BNI module must be accessible from the PC on which the browser is running. Please use Internet Explorer 10 or newer as the browser; older versions may result in display problems. For open a connection with the web server, enter the IP address of the module in the address line of the browser. The homepage then appears with the essential device information. www.balluff.com 38 9 Web Server 9.2. Navigation / Info The navigation bar is located in the upper area of the window, which allows you to switch between the various dialogs of the web interface. To do this click on the corresponding icon. When the "Info" tab is selected the following overview appears: The "BALLUFF" logo at upper right links to the international Balluff homepage. www.balluff.com 39 Balluff Network Interface EtherNet/IP™ 9 Web Server 9.3. Login/Logout To make configuration settings on the fieldbus module using the web interface, you must first log in. Functionalities which cannot be used without logging in are indicated by the grayed out buttons. The default password is: BNI PNT-XXX-XXX-XXXX BNI EIP-XXX-XXX-XXXX BNI ECT-XXX-XXX-XXXX "BNIPNT“ "BNIEIP“ "BNIECT“ The password cannot be changed! After successfully logging in the dialogs are shown as follows: Use the "Logout" button to log out again. After 5 minutes of no interaction with the Webserver the user is automatically logged out. Note For security reasons the fieldbus module shows only one login at a time with configuration access. Reading (without logging in) is however possible from multiple PCs at the same time on the fieldbus module. www.balluff.com 40 9 Web Server 9.4. "Home" dialog Under "Home" you are given the essential information about the fieldbus itself and its network activity. You are also shown whether the configuration block was enabled by the controller (PLC). Information is also shown about the current process data and the status of the module via the corresponding LEDs. After selecting "LED Legend" a Help dialog appears which explains the meaning of the LEDs. If an IO-Link device is connected to one of the configured IO-Link terminals, some of the device data will be displayed in addition to the module data in the form of a link. After selecting one of these links the corresponding device dialog is opened. www.balluff.com 41 Balluff Network Interface EtherNet/IP™ 9 Web Server PNT: EIP: www.balluff.com 42 9 Web Server 9.5. "Ports" dialog The "Ports" dialog displays information and process data for the connected IO-Link devices. Select the desired IO-Link Port in the image of the fieldbus module on the right side to see the device data. Note The IO-Link device data are only displayed if the port is also configured as an IO-Link port! No appropriate IODD uploaded It is possible to read and write the configuration parameters of the IO-Link device via the "Parameters" option. The parameter indexes and subindexes of the IO-Link device are described in the corresponding separate user's guide (and follow the IO-Link conventions). Under "Events" you can see whether a diagnostic event from the IO-Link device exists. Under "Parameter Server Content" you can view the content of the parameter server if parameter data is stored on the parameter server. "Ports" dialog with direct parameter access www.balluff.com 43 Balluff Network Interface EtherNet/IP™ 9 Web Server Appropriate IODD uploaded If an IODD appropriate to the IO-Link device connected to the currently selected port has been uploaded (see "Dialog "IODD"), the normal dialog for "Process Data" and "Parameters" is not displayed, but rather an expanded dialog. Information from the IODD of the device is used so that the data can be better understood. Thus in the following screenshot not only are the input data of the distance sensor displayed as a hex number, but also interpreted and labeled under "Input". Since the sensor has no parameters, none are displayed. Dialog "Ports“: IODD interpretation and device image www.balluff.com 44 9 Web Server If the IODD of the IO-Link device on the currently selected port has parameters, these are shown in table format (see following screenshot). In this example the parameters for the Balluff Smart Light are shown. The Smart Light is a signal light which can be used in three different modes. These modes can be set using an IO-Link parameter. The parameter values and associated texts are stored in the IODD. This means "Operation Mode" can be read out and displayed ("Read" and "Read All" buttons) or written to the device ("Write" button). If subindexes have no buttons they cannot be individually processed but rather only the entire index at once. Note Each changed value must be individually written by clicking on the "Write" button! "Ports" dialog: Parameter list of an IO-Link device with uploaded IODD www.balluff.com 45 Balluff Network Interface EtherNet/IP™ 9 Web Server 9.6. "IODD" dialog Using this dialog you can transfer IODDs (device description files for IO-Link devices) and the associated device images to the fieldbus module, so that a detailed representation of the connected IO-Link devices in the "Ports" dialog is possible. When IO-Link devices are connected and IO-Link ports are activated, the dialog shows a table with information about the IO-Link devices. The fieldbus module file system supports only device names in "8+3" format, i.e. with a restricted name length. Since IODD files are generally published with a long file name, these must be renamed and given a shorter naming scheme on the PC before uploading to the fieldbus module. For this a help setting is provided in the dialog, with the associated required IODD file name for the currently connected IO-Link devices shown in the bottom section of the list (column IODD Filename). Image files without IODD can also be uploaded; the images are still displayed in the "Ports" dialog. Using the "Delete" button you can delete IODDs and device images from the fieldbus when needed. Note Before selecting the IODD it must be renamed on the PC to the file name which is shown in the table in the "IODD Filename" column! www.balluff.com 46 9 Web Server 9.7. "Config" dialog The configuration page enables configuration of the module. You can change both the module information texts and the port configuration. The "Set Ports" action is not permanently stored in the device and is lost after the next reboot or reset. PNT / ECT: www.balluff.com 47 Balluff Network Interface EtherNet/IP™ 9 Web Server EIP: The parameter set “Module Configuration” on the left side is used by clicking "Save Configuration" and permanently stored in the device. The "Reboot" button reboots the device as if the power to the module had been turned off and on again. Clicking on "Factory Reset" deletes the configuration and log files saved in the device and then performs a reboot, so that the device is restored to the default factory configuration as on delivery. www.balluff.com 48 9 Web Server 9.8. "Log" dialog This dialog provides general service information about the device as well as a logging function. The upper table (see screenshot below) contains important information for all service inquiries. Note If you have a detailed question about a specific situation, send us a screenshot of this Website or print the site as a PDF. Logging shows events which have occurred in chronological order. This provides a tool for detailed troubleshooting in equipment. www.balluff.com 49 Balluff Network Interface EtherNet/IP™ 9 Web Server Events are classified using the "Severity“ column: Internal Error (Emergency, Alert, Critical) The fieldbus module has detected a fault in itself (hardware or software) which should not occur during normal operation. If this happens, the module must be serviced or replaced. External Error (Error, Warning) The fieldbus module has detected what may be a non-permissible event which is affecting the module from the outside. The system may require troubleshooting. Event (Informational, Notice) The fieldbus module has detected an important normal operating event and reports it. These may include for example configuration actions over the web interface and other configuration interfaces which are also recorded. Clicking on "Set Module Time” sends the current browser time to the fieldbus module but does not permanently store it. After a reset, reboot or loss of power the time begins to run again from the year 2000. Clicking on "Update Log” refreshes the display, and "Clear Log” deletes all entries. The log entries are stored in a ring buffer. www.balluff.com 50 10 Appendix 10.1. Scope of Delivery The BNI EIP comprises the following elements: • IO-Link block • 4x M12 dummy plugs • Ground strap • M4x6 screw • 20 informational signs 10.2. Order Number BNI EIP-50x-105-R015 Balluff Network Interface Ethernet IP Functions 502 = IP 67 IO-Link master module, 4 IO-Link ports 508 = IP 67 IO-Link master module, 8 IO-Link ports Versions 105 = display version, 2-port switch Mechanical version R015 = plastic housing, resistant (Fortron 6165 A6 black) Data transmission: 2 x M12x1 internal thread Power supply: 7/8" external thread, 7/8" internal thread Sensor connections: 8 x M12x1 internal thread 10.3. Ordering Information www.balluff.com Product order code BNI EIP-502-105-R015 BNI EIP-508-105-R015 Order code BNI008Z BNI008M 51 Notes www.balluff.com 52 Balluff GmbH Schurwaldstrasse 9 D-73765 Neuhausen a.d.F. Germany Phone +49 7158 173-0 Fax +49 7158 5010 www.balluff.com balluff@balluff.de No. 922508-726 E 04.124053 Edition D17 Replaces Edition B17 Subject to modification www.balluff.com 53
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : No Page Count : 54 Language : de-DE Tagged PDF : Yes XMP Toolkit : 3.1-701 Producer : Microsoft® Word 2016 Title : User´s Guide: BNI EIP-502-105-R015 / BNI EIP-508-105-R015 EN Creator : Claudia Exner Creator Tool : Microsoft® Word 2016 Create Date : 2017:05:02 14:49:02+02:00 Modify Date : 2017:05:02 14:49:02+02:00 Document ID : uuid:88346884-F3E9-4C57-9E5A-F4CC15F12436 Instance ID : uuid:88346884-F3E9-4C57-9E5A-F4CC15F12436 Author : Claudia ExnerEXIF Metadata provided by EXIF.tools