Nexus 1450
®

Cyber Secure Energy Panel Meter with Advanced Power Quality & Multiport Communication

Nexus® 1450 Meter

Metering and Communication

www.electroind.com

w
Ne•

Multilevel Cyber Secure Encrypted Configuration

• Advanced Web Server with Waveform
Analysis Tools

P40N+ Remote Multifunction Display

Advanced Power Quality Analysis
• Class A IEC 61000-4-30 Edition 3 Power
Quality Measurements
• IEC 61000-4-15 Flicker Measurements

• Up to 1024 Samples per Cycle-based Measurements

• IEC 61000-4-7 Harmonic Measurements

• 0.06% Energy Accuracy Over Wide Dynamic
Measurement Range

• EN 50160 Power Quality Reports
• New CORE™ Logging Architecture

• Highly Accurate and Stable Measurements Using
Multi-Gain™ Sensing

• Easy-install Transducer and Separate Display

• 6 Available Communication Ports, Including
Modbus and DNP 3.0 Protocols

• Direct Physical Retrofit to Nexus® 125X Series Meter/
Transducer with Greater Functionality

• Two Independent Ethernet Ports, with Unique
IP Addressing

• Separate 3 Line LED Displays

Electro Industries/GaugeTech™
The Leader in Power Monitoring and Smart Grid Solutions™

Introduction
Electro Industries’ Nexus® 1450 meter is a powerful energy meter that
provides accurate electrical energy measurements and offers advanced
capabilities for power quality analysis and determining electrical power
reliability. The meter is a transducer base with a separate display. The
transducer base retrofits to existing Electro Industries’ Nexus® 1250 and
1252 meters. The Nexus® 1450 meter is ideal for existing switchboard
panels, since it can be installed without cutting panel doors. The separate
display mounts into existing analog meter knockouts.
The Nexus® 1450 meter is protected with a multi-level Cyber Secure
configuration with 10 highly secure encrypted user IDs and passwords
that help prevent tampering and hacking of your power system data. The
meter's built in WebView™ Energy Dashboard allows you to analyze
metering data without needing software. You can navigate easily through
multiple webpage views and get detailed information on energy usage and
power quality: view real time data, analyze stored history logs, view alarms
and waveform records.

Multi-Gain™ Sensing Provides
Superior Accuracy
The Nexus® 1450 meter utilizes EIG’s latest measurement-sensing
technology - Multi-Gain™. Multi-Gain™ technology uses two
sensors on the current inputs - a high gain sensor and a lower gain
sensor. Each sensor simultaneously measures the current signal coming
from the external current transformers. The meter’s intelligent processing
looks at the signal level and determines the optimal sensing circuit for the
highest accuracy measurement. With this technique, the meter has 0.06%
accuracy throughout an extended measurement range, which is a defining
trait of Nexus® Series meters.
The meter’s standard pickup range starts as low as 1 mA, and high
accuracy is attained at 25 mA. Multi-Gain™ metrology allows the same
meter to be used on both 5 A secondary and 1 A secondary CTs. The
meter should maintain high accuracy measurement throughout its
installed life. Refer to the accuracy chart on the next page, for details.

With 6 simultaneously operating communication ports, the meter is a
communication hub to multiple software systems. The Nexus® 1450
meter has 4 serial ports that speak Modbus and DNP 3.0 protocols. It also
has two independent Ethernet ports, consisting of a 10/100BaseT copper
RJ45 connector and an ST Terminated 100Base FX Fiber Optic Ethernet
port. Each Ethernet port has a unique IP address. Through the meter's 6
ports, a user is able to communicate to multiple computer-based
systems, providing data to entities throughout an enterprise.
The meter also excels at measuring power quality, including waveform
recording and IEC 61000-4-7, IEC 61000-4-15, and IEC 61000-4-30
Class A compliance. The Nexus® 1450 meter lets you look at the
reliability of the electrical power circuit to determine causes of faults,
voltage surges and sags, and harmonics.

Multi-Gain™ Metrology allows the Nexus® 1450 meter to have
highly repeatable and stable measurements throughout range
2

Typical accuracy charts

Meter Accuracy Specification
Measurement
Measurement
Voltage L-N
Voltage L-N
Voltage L-L
Voltage L-L
Current
Current
Neutral Current
Neutral Current
Frequency
Frequency
Watts
Watts
Watt-hour*
Watt-hour*
VAR
VAR
VARh
VARh
VA
VA
Power Factor
Power Factor
THD
THD

0.04% of reading
0.04% of reading
0.04% of reading
0.04% of reading
0.04% of reading
0.04% of reading
0.1%
0.1%
0.004 Hz
0.004 Hz
0.06% of reading
0.06% of reading
0.06% of reading
0.06% of reading
0.15% of reading
0.15% of reading
0.15% of reading
0.15% of reading
0.06% of reading
0.06% of reading
0.15% of reading
0.15% of reading
2.5% of reading
2.5% of reading

Advanced Energy Meter for
Primary Loads
The Nexus® 1450 unit is an electrical energy meter designed to be used
for any important application. In addition to highly accurate energy
measurement, the meter features:
•

Full 4 quadrant metering.

•

Max/Min recording with timestamp.

•

Extensive logging with 8 logs of programmable
historical profiles.

•

Built-in CORE™ log for web trending.

•

Transformer and Line Loss compensation: for both iron and
copper, and total substation losses.

*(0.025 A to 20 A at PF=1); full accuracy specifications are given in the
Nexus® 1450 Meter Installation and Operation Manual.

•

CT and PT compensation: to correct instrument
transformer errors.

Precision Crystal Time Reference:

•

Coincidental readings: e.g., PF or VARs at time of Peak Demand.

•

Load aggregation/universal metering: pulse inputs can be used
to aggregate or accumulate different loads. Utility commodities
such as gas and water can also be accumulated.

The Nexus® 1450 meter is equipped with an internal clock crystal
accurate to 3.5 PPM over the full operating temperature range and 5 PPM
at over ten years of use. This highly accurate trimmed clock design
allows users to maintain accurate time when running on crystal
synchronization. The meter's clock crystal will drift less than 6 seconds
per month from (0-40) °C.
Additional time sync methods include:
•

Modbus time sync.

•

IRIG-B time sync.

•

DNP 3.0 time sync.

•

SNTP time sync.

On-board Time of Use Measurements:
The Nexus® 1450 meter uses a perpetual Time of Use (TOU) calendar
that only needs to be set up once. The TOU implementation allows the
user to set up multiple tariffs to meet any contractual obligations. It also
allows the user to customize any energy parameter for TOU. The 16
available TOU registers can be configured not only for TOU built-in energy
readings, but also for any stored data from pulses or other readings that
need TOU functionality.
•

Up to four seasons - seasons can be customized.

•

Flexible billing periods/rates/holidays/schedules setup.

•

Cumulative and continuous cumulative demand are available.

Easily Configure Almost any Time of Use Usage Profile
3

Data Logging and Internal Storage
The Nexus® 1450 meter provides advanced capabilities for storing
measured values over time, for trending and analysis. The meter has up
to 4 GB of memory, with up to 1.2 GB allocated exclusively to logging
and user storage, and is preconfigured to store its core measurements (in
the CORE™ log) every 15 minutes, without any user intervention. Core
measurements include 142 different values. Additionally, a user is able to
configure up to 8 historical logs. All logs work with a FIFO buffer and roll
over when filled. The following logs are available:
•

Trending Log: The meter supports up to eight historical,
trending logs of 64 data channels per log, acting as a traditional
load profile recorder with up to 8 separate logs.

•

System Events Security Log: This anti-tampering log
records all events in the meter, with an associated timestamp.
The unit records:

•

Limit Log: The Limit/Alarm log can be set to record on high
and low conditions for up to 32 user programmable limits.

•

Input Status Change Log: This log supplies
information on the state of the meter’s internal digital inputs.

•

Power Quality Log: This log captures power quality
events, such as surges and sags, and lets you view and analyze
the data through power quality graphs, such as the ITI CBEMA
Curve and SEMI F47 standards. See the next page for more
power quality reporting information.

•     Resets.
•     Programming changes.
•     Password access changes.
•     Time changes.
•     Power up/down.
•     Change of Firmware.

Chart of Memory for Logging
Log Type

V1 Record
Size

Days

V2 Record
Size

Days

System Events

16384

CORE™ Log*

16384

163

32768

327

Log 1**

16384

163

32768

327

Log 2**

16384

163

32768

327

Log 3**

16384

163

32768

327

Log 4**

16384

163

32768

327

Log 5**

16384

163

32768

327

Log 6**

16384

163

32768

327

Log 7**

16384

163

32768

327

Log 8**

16384

163

32768

327

Digital Input

16384

32768

Limits/Alarms

16384

32768

Power Quality

16384

32768

Waveforms***

For 512 samples per cycle, 1
second waveform recording at 60
Hz: 682 records.

For 1024 samples per cycle, 1
second waveform recording at
60 Hz: 341 records.

32768

* The CORE™ log automatically records readings for 142 parameters at the logging interval.
The default interval is 15 minutes. Days are based on approximately 100 records per day.
** Logs 1 - 8 are user-assignable and allow 64 parameters per log. Days are based on
approximately 100 records per day.

4

*** The number of waveform records depends on the sampling rate and the length of waveform recording. V1 offers up to 512 samples per cycle recording and V2 offers up to 1024
samples per cycle recording.

Power Quality Measurements
Critical sensitive equipment and over utilized distribution systems need to
be monitored for proactive system reliability improvements. By measuring
power quality indices such as voltage anomalies, harmonics, flicker,
imbalances and many other conditions, you are able to quantify your
system reliability. Recording waveform events on sags and swells,
including peak and duration of the event, with microsecond resolution,
will facilitate forensic engineering analysis of harmful events in your
power system. The Nexus® 1450 meter is designed to the highest
standards for power quality, including IEC 61000-4-7, IEC 61000-4-15
and IEC 61000-4-30 Class A.

IEC 61000-4-7 Harmonics:
•

View harmonic magnitudes to the 511th order for each voltage
and current channel, using EIG's Log Viewer software.

•

Harmonic magnitudes and phase angles in real time are resolved
to the 127th order.

•

Obtain THD, TDD, and K-Factor.

•

Conduct power quality analysis at the high end of the harmonic
magnitude spectrum.

IEC 61000-4-30 Class A Reporting:
•

•

Supporting the most stringent international power quality
standards, the Nexus® 1450 meter offers full reporting of power
quality conditions using the IEC 61000-4-30 Class A
methodology.
Operates on both 230 volt/50 Hz and 120 volt/60 Hz.

Limits/Alarms:
The Nexus® 1450 meter lets you set multiple programmable limits for
any measured value and for conditions set up in a Boolean logic tree. This
feature will record events based on threshold settings. Limits can be used
with timers and logic to trigger control events.

IEC 61000-4-15 Flicker Measurement:
•

The Nexus® 1450 meter measures Flicker in compliance with
the IEC 61000-4-15 Class A standard.

•

Operates on both 230 volt/50 Hz and 120 volt/60 Hz.

5

Waveform Recording:
The Nexus® 1450 meter offers waveform recording at a sampling rate of
up to 1024 samples/cycle. The meter can be programmed to record
waveforms on multiple power quality events, such as surges and/or sags.
16-bit A/D conversion provides precise waveform resolution. Both voltage
and current recording offer pre and post-event analysis. Fault recording
offers 8 times full-scale capture capability. Both hardware and software
triggers are available.
The waveforms can be viewed either through Communicator EXT™
software or on the meter's built-in web browser, or they can be
downloaded to third party software for analysis. By analyzing the
waveforms, the nature and source of power quality anomalies can be
determined, and steps can be taken to remedy the situation.

Cyber Secured Configuration
Protects Meter from Tampering:
•

Highly Secure Encrypted Passwords - 128 Bit AES Encryption.

•

10 User IDs and Passwords - Up to 30 Characters.

•

Password Fail Timeouts Eliminate Brute Force Hacking.

•

4 Roles with Customized User Access.

•

Physical Seals and Lock-outs to Prevent Hacking or Tampering.

V-Switch™ Key technology
The Nexus® 1450 meter is equipped with V-Switch™ key upgrade
technology that lets you upgrade meter functionality even after
installation. This means you can purchase what you need now and then
upgrade whenever you need the additional features. Following are the
available V-Switch™ keys:
Nexus® 1450 Features

V1 (Basic)

V2 (Advanced)

Voltage, Current, etc.

P

P

THD and Harmonics

P

P

Time of Use

P

P

Waveform Recording

P

P

Sampling Rate

512

1024

Basic Measurements

Power Quality Measurements

Phasor Analysis:
Communicator EXT™ software lets you view the phase angles and
symmetrical components for voltage and current, helping you analyze
electrical system problems.

Flicker

P

P

IEC 61000-4-30 Class A

S

A

EN 50160 Reporting

P

P

Storage
CORE™ Log

P

P

Custom Historical Logs

P

P

PQ Log

P

P

Waveform Log

P

P

Limit Log

P

P

Digital Input Log

P

P

Memory for logging

512 MB*

1200 MB*

Serial

P

P

Modbus over Serial

P

P

DNP 3.0 over Serial

P

P

RJ45 Ethernet

P

P

Fiber Ethernet

P

P

Modbus over Ethernet

P

P

DNP 3.0 over Ethernet

P

P

Communication

* The unit has 4000 MB flash memory installed, for longer reliable life.
Some of the memory is allocated to wear-leveling and system use.
6

Advanced Communication

Standard I/O

The Nexus® 1450 meter is equipped with extensive communication
capabilities that allow it to speak with many different SCADA or other
communication systems, simultaneously. The meter has 6
communication ports as a standard offering. These ports include 4 serial
ports and 2 Ethernet-based communication ports.  The Ethernet ports
include an ST terminated fiber optic port and an RJ45 port. Both ports use
separate IP addresses, so that they can run on simultaneous redundant
networks.

8 Built-in Digital Status Inputs:

Details of Ports:

VAUX Input:

•

6 standard Com ports.

•

4 serial ports - RS485 (one of the ports is RS485/
RS232 selectable).

•

2 independent Ethernet ports - RJ45 and Fiber Optic.

•

Modbus RTU, Modbus ASCII, Modbus TCP/IP, DNP 3.0
Level 2 communication.

•
•

•

•

Inputs automatically sense whether the circuit is
externally wetted.

•

If externally wetted, input up to 150 V DC is accepted.

•

If internally wetted, the meter supplies the necessary voltage for
the control application.

•

Two Standard Pulse Outputs:
•

Solid State, form-A, 35
ohm max on resistance.

•

120 mA continuous, 350
mA max for 10 ms.

•

Peak voltage: 350 V DC.

All ports can be communicating simultaneously.
Ports 3 and 4 can be used as Master ports to control up to 4 I/O
modules each.

Neutral to ground or aux voltage readings for synchronizing
schemes, for example, obtaining the frequency, magnitude, and
phase angle on both sides of a switch or between generator and
bus voltage.

•

Switching rate max: 10/s.

•

Support pulse-counting
applications.

Each Ethernet port can be assigned a separate IP address.

The Nexus® 1450 meter is a direct physical retrofit to
Nexus® 1250 and 1252 meters.
7

Revenue Seal
The Nexus® 1450 meter is lockable to prevent physical tampering. The
following items are part of the meter's security:

Digital Inputs:
•

8DI1: 8 Digital Status Inputs Wet/Dry.

•

Auto-Detect Up to 300 V DC.

Digital Dry Contact Relay Outputs:

•

Demand and programming Reset button seal.

•

Two physical meter seal locations.

•

•

Lockable cover for voltage and current inputs.

4RO1: 4 Relay Outputs, 5 A, 250 V AC/30 V DC, Form-C
Latching.

•

Ordering: Up to 4 Digital Dry Contact Relay Outputs.

•

All seals, other than Demand/programming, are sold separately.

•

Two standard test pulses for Wh and VARh testing.

Digital Solid State Pulse Outputs:
•

4PO1: 4 Solid State Pulse Outputs, Form A or C KYZ pulses.

•

Maximum Pulse Speed: 20 pulses per second.

•

Ordering: Up to 4 Digital Solid State Pulse Output modules.

I/O Module Accessories:

Optional I/O Modules
Analog Outputs:

•

PSIO: Power supply for up to 4 additional I/O modules. This
accessory may be needed when using 3 or more displays and/or
modules.

•

MBIO: Mounting bracket for external I/O modules. Must be
ordered with external I/O module (required).

Optional Display:
•

Optional multifunction LED Master display, P40N+, supplies
visual display of meter readings; also used as a Master volt
display.

•

Optional Slave displays P41N+ (Ampere display) and P43N+
(Power display) can be daisy-chained.

•

1mAON4/1mAON8: 4 or 8 Analog
Outputs, 0±1 mA, self-powered, scalable, bidirectional.

•

20mAON4/20mAON8: 4 or 8 Analog Outputs, 4-20 mA,
self-powered, scalable.

•

Wiring: Common Mode.

•

Display connects to any RS485 port.

•

Accuracy: 0.1% of Full Scale.

•

Calibration: Self-calibrating.

•

P40N+ offers USB connection to a PC for direct data download
of readings.

•

Scaling: Programmable.

•

Ordering: Up to 4 Analog Output modules.

Analog Inputs:

8

•

8AI1: 8 Analog Inputs, 0±1 mA.

•

8AI2: 8 Analog Inputs, 4-20 mA.

•

8AI3: 8 Analog Inputs, 0±5 V DC.

•

8AI4: 8 Analog Inputs, 0±10 V DC.

•

Wiring: Common Mode.

•

Accuracy: 0.25% of Full Scale.

•

Scaling: Programmable.

•

Ordering: Up to 4 Analog Input modules.

Use existing installed P40N+ Series displays and I/O from your
1250/1252 installation.

WebView™ Energy Dashboard
Built-in Energy Dashboard Allows You to Analyze
Metering Data Without Needing Software:
The Nexus® 1450 meter utilizes a unique HTML 5-based web server. This
new web server acts as an Energy Dashboard, allowing the user to view
real time data, as well as to analyze stored historical logs, alarms, and
waveform records. The WebView™ Energy Dashboard is built on a
responsive architecture, so that it will work properly on hand held browserbased devices, such as tablets and phones.

Energy Screen

Using the WebView™ Energy Dashboard, the user is able to navigate
easily through multiple webpage views, getting detailed information on
energy usage and power quality:
•

Real time voltage and current readings and detailed charts, so
that the user can see energy use over time.

•

Energy usage, quadrant energy charts and trending.

•

Waveform event records, including zoom and pan.

•

Status of digital inputs.

•

Phasor diagram.

•

Flicker readings, including PST and PLT.

•

Detailed information for accumulators and aggregators.

•

Meter information and diagnostic webpages for meter health
and status.

•

View data directly from the meter's web viewer.

Historical Log Screen

Voltage Screen
Phasor Screen

Waveform Recording Screen
Sample of watt and VAR trending over webpage
9

Dimensional Drawings

Nexus® 1450 Meter Base
10.70 in [27.19 cm]
2X 3.35 in [8.51 cm]

2.80 in [7.12 cm]

2X 4.00 in [10.16 cm]

2.56 in [6.51 cm]

6.25 in [15.88 cm]

6.74 in [17.12 cm]

Without
Sealed Cover

3.35 in [8.51 cm]
3.74 in [9.51 cm]

4X 0.22 in [0.56 cm] THROUGH-SLOT FOR #10 SCREW

Nexus® 1450 Meter
Front Dimensions

With
Sealed Cover

Nexus® 1450 Meter
Side Dimensions

Nexus® LED Display
1.79 in
[4.55 cm]
3.37 in
[8.57 cm]
1.68 in
[4.28 cm]

5.25 in
[13.34 cm]

1 in
[2.54 cm]

5.25 in
[13.34 cm]

4X 0.20 in
[0.50 cm]

1.07 in
[2.77 cm]

3.37 in
[8.57 cm]

4.00 in
[10.16 cm]

P40N+ Back
Dimensions

P40N+ Front
Dimensions

P40N+
Side Dimensions

Note 1: Mounting and I/O Module details are available in the Nexus® 1450 Meter Installation and Operation Manual.
Note 2: P41N+ and P43N+ displays utilize the same dimensions.
10

Wiring Diagrams

LINE

LINE

A B C N

A B C N

SHORTING SWITCH OR
TEST BLOCK
SHORTING SWITCH OR
TEST BLOCK
HI
HI
LO
HI

Ic

LO
CTs

HI

Ib

LO

EARTH GROUND

EARTH GROUND

In

Ic

LO

Ib

LO

Ia

LO

HI

CTs

HI

HI

Ia

EARTH
GROUND

FUSES

LO

Vc

FUSES
Vc

EARTH GROUND

PTs

Vb

Vb
Va
Vref
Vaux

Va
AUXILIARY VOLTAGE

NFUSE

L+

POWER SUPPLY
(DEPENDENT ON EQUIPPED SUPPLY OPTION)

Vref

A B C N

Vaux

EARTH
GROUND

AUXILIARY VOLTAGE

A B C N

NFUSE

LOAD

L+

POWER SUPPLY
(DEPENDENT ON EQUIPPED SUPPLY OPTION)

LOAD

4-Wire Wye, 3 Element Direct Voltage with 4 CTs

4-Wire Wye, 3 Element with 3 PTs and 3 CTs

LINE

LINE

A B C

A B C N

SHORTING SWITCH OR
TEST BLOCK

SHORTING SWITCH OR
TEST BLOCK

Ic

LO

CTs

EARTH GROUND

EARTH GROUND

HI

HI

Ic

LO

Ib

LO

HI
CTs

HI

Ia

LO

HI

Ia

LO
EARTH GROUND

FUSES

FUSES
Vc

PTs

Vc
EARTH GROUND

Vb
Va
Va

NFUSE

L+

POWER SUPPLY
(DEPENDENT ON EQUIPPED SUPPLY OPTION)

Vref

A B C

Vaux

AUXILIARY VOLTAGE

EARTH
GROUND

N-

LOAD

3 Wire, 2 Element Delta Direct Voltage with 2 CTs
Important: The Potential between A, B, C and GROUND
must be less than 347 V AC.

FUSE

L+

POWER SUPPLY
(DEPENDENT ON EQUIPPED SUPPLY OPTION)

A B C N
LOAD

3 Phase, 4 Wire 2.5-Element with 2 PTs, 3 CTs

Additional wiring diagrams for the meter are available in the Nexus® 1450 Meter Installation and Operation Manual.
11

Specifications
•

•

(20 to 720) V AC

Accuracy Ratings:

•

Pickup voltage: 5 V AC

•

Isolation:
•

•

Voltage Inputs isolated to 2500 V AC

Current Input Range:

•

•

Supports Class 2 and Class 20 in
one input configuration

•

Programmable to any CT ratio

•

Fault current recording to +/- 80 A peak

•

Pick-up current: 1 mA

•

100 A for 10 seconds

•

300 A for 3 seconds

•

500 A for 1 second

•

Voltage Inputs: 5 Mohms per
voltage input
Current Inputs: 0.028 VA per phase max
at 20 A
(42.5–69.5) Hz

Environmental:
•
•

Energy measurement accuracy at 0.06%
(0.025 A to 20 A at PF=1)

Total shipping weight: approx. 5 lbs
(2.2 kgs)

•

Full accuracy specifications available in
Nexus® 1450 meter User Manual

Shipping container dimensions: 14" x10"
x6" (35.6cm x 25.4cm x 15.2cm)

•

Displays and I/O modules ship in
separate containers.

Time clock: 3.5 ppm for
(-25 to +70) °C - less than 10 seconds
drift per month on crystal sync; 2.0 ppm
Typical from 0 to +40 °C - less than 6
seconds per month drift

•

1 Second - High Accuracy readings

•

1 Cycle - Fast Update readings

•

Customizable high-speed readings update rate from 2 to 20 cycles RMS

•

D2 Option: (96-276) V @ 50/60 Hz
or DC

•

D Option: (18-60) V DC

•

Burden: 20 VA max w/o I/O or display;
40 VA max with I/O and display

Operating temp: (-25 to +70) °C
Storage temp: (-40 to +70) °C

Compliance:

•

Baud rate up to 115200 bps

•

Programmable parity and stop bits

•

Serial Communication protocols:
Modbus ASCII/RTU, DNP 3.0

•

IEC 62052-11 General requirements,
tests and test conditions - Metering
equipment

•

IEC 62053-22  Particular Requirements Static meters for active energy (Classes
0,2 S and 0,5 S)

•

IEC 62053-23, Static meters for reactive
energy (Classes 2 and 3)

•

IEEE 519 Recommended Practices and
Requirements for Harmonic Control in
Electrical Power Systems

•

REACH Regulation (EC) No 1907/2006

•

UL Listed

•

ANSI C12.1 Electric Meters Code For
Electricity Metering

•

ANSI C12.20  Electricity Meters 0.2 and
0.5 Accuracy Classes

External I/O Modules:

•

ANSI (IEEE) C37.90.1 (Surge Withstand)

•

1mAON4: 4 Analog Outputs, 0±1 mA

ANSI C62.41 (Burst)

•

1mAON8: 8 Analog Outputs, 0±1 mA

IEC 60068-2-1 Environmental Testing:
Test A: Cold

•

20mAON4: 4 Analog Outputs, 4-20 mA

•

20mAON8: 8 Analog Outputs, 4-20 mA

•

IEC 60068-2-2 Environmental Testing:
Test B: Dry Heat

•

8AI1: 8 Analog Inputs, 0±1 mA

•

IEC 60068-2-30 Environmental Testing:
Test Db: Damp heat, cycle (12h + 12h
cycle)

•

8AI2: 8 Analog Inputs, 4-20 mA

•

8AI3: 8 Analog Inputs, 0±5 VDC

•

8AI4: 8 Analog Inputs, 0±10 VDC

IEC 61000-4-2 Electromagnetic compatibility (EMC). Testing and measurement
techniques. Electrostatic discharge
immunity test

•

4RO1: 4 Relay Outputs

•

4PO1: 4 Solid State Pulse Outputs

•

8DI1: 8 Digital Status Inputs

IEC 61000-4-3 Electromagnetic
compatibility (EMC). Radiated,radiofrequency, electromagnetic field
immunity test

•

PSIO: Power Supply for up to 4
additional I/O modules

•

MBIO: I/O mounting bracket (must be
ordered with external I/O module)

•

•

•

RJ45 Ethernet port 10/100BaseT

Protection Class: IP30

•

Fiber Optic port 100Base FX

Measurement Method:

•

4 RS485 ports

•

Up to 1024 samples per cycle
(programmable)

•

RS232 port (shared)

•

16 Bit A/D resolution – multiple
simultaneous converters

•

RS485 Serial ports have 18 V DC
output for I/O

•

IEC 61000-4-4 Electrical fast transient/
burst immunity test

•

Optional P40N+ display offers USB
Type B communication

•

IEC 61000-4-5 Surge immunity test

•

IEC 61000-4-6 Immunity to conducted

Multi-Gain™ sensing method

IEC 61000-4-30 Power quality
measurement methods

EU Directive 2011/65/EU (RoHS 2
Directive)

Humidity: Up to 95% RH
non-condensing

•

•

•

Ethernet: Modbus TCP, DNP 3.0, SNTP,
HTTP, and HTTPS

•

IEC 61000-4-7 General guide on
harmonics and interharmonic
measurements and instrumentation

EU Directive 2014/32/EU (Measuring
Instruments Directive)

•

•

•

•

•

Communication:

Frequency Range:
•

•

Control Power Requirements:

Burden:
•

True RMS

Update Rate:

Current Input Withstand
Capability (at 23 °C):

disturbances, induced by radiofrequency fields

Shipping:

Voltage Input Range:

•

Note: Please see the Nexus® 1450 meter
Installation and Operation Manual for
comprehensive specifications.

Ordering Information
Nexus® Base
Meter

-

Option
Numbers:
Example:

-

Control
Power

-

Frequency
Range

-

Accessories
-

Virtual
Switch

Software
COMEXT4P1Y

-

Nexus 1450

D2

60

V1

Nexus®
1450 Meter

D2
Universal (96-276) V @
50/60 Hz or DC

60
60 Hz

V1
Standard Nexus® 1450 Meter
512 MB memory logging /
512 s/c

D
(18-60) V DC

50
50 Hz

V2
V1 + 1200 MB
memory logging / 1024 s/c

1800 Shames Drive, Westbury, NY 11590   1-877-EIMETER (1-877-346-3837)  
Tel: 516-334-0870   Fax: 516-338-4741   Email: sales@electroind.com
www.electroind.com

Electro Industries/GaugeTech™

The Leader in Power Monitoring and Smart Grid Solutions™

Displays
P40N+
P41N+
P43N+

Multifunction LED Display/Master
Amp Display Slave
Watt/VAR/PF Display Slave

I/O Modules
1mAON4
1mAON8
20mAON4
20mAON8
8AI1
8AI2
8AI3
8AI4
4RO1
4PO1
8DI1
PSIO
*MBIO
E171103

Nexus® 1450
web page:

Communicator EXT 4.0
Software for Windows
Single-Computer License (One
Year)

4 Analog Outputs, 0±1 mA
8 Analog Outputs, 0±1 mA
4 Analog Outputs, 4-20 mA
8 Analog Outputs, 4-20 mA
8 Analog Inputs, 0±1 mA
8 Analog Inputs, 4-20 mA
8 Analog Inputs, 0±5 V DC
8 Analog Inputs, 0±10 V DC
4 Relay Outputs
4 Solid State Pulse Outputs
8 Digital Status Inputs
Power Supply for Additional
I/O Modules
I/O Mounting Bracket
DIN Rail Mount Kit for Nexus®
1450 meter

Accessories Note:
* Must be ordered with an external I/O module.

E171702  010918  V.1.02



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Author                          : Electro Industries
Create Date                     : 2018:01:10 14:22:25-05:00
Modify Date                     : 2018:01:10 15:47:39-05:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2018:01:10 15:47:39-05:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Instance ID                     : uuid:0216a356-c111-40ee-8ff9-f179a1658d05
Original Document ID            : adobe:docid:indd:16dc73aa-227d-11e0-a17f-bf3b56d83edc
Document ID                     : xmp.id:49B04A783BF6E711B5879292A1BC5FA9
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:44E5DE2C3BF6E711B5879292A1BC5FA9
Derived From Document ID        : xmp.did:8809E14B25F6E711B5879292A1BC5FA9
Derived From Original Document ID: adobe:docid:indd:16dc73aa-227d-11e0-a17f-bf3b56d83edc
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2018:01:10 14:22:25-05:00
Format                          : application/pdf
Title                           : Nexus 1450 Meter Brochure V.1.02
Creator                         : Electro Industries
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 12
EXIF Metadata provided by EXIF.tools

Navigation menu