200 Installation
30-3001-786 Rev H
Mechanical
2.75
(70)
Power Connection
200ac 200dc
Use care when attaching power
wiring (AC or DC) to these connectors.
They are not to be used as a strain relief.
The connectors cannot withstand
excessive bending or flexing.
!
+
24 VDC
230V
115V
SETTING 115V
230V
SETTING
6.5
(165)
6.67
(170)
ENCLOSED-CLASS
MOUNTING DIMENSIONS
7.5
(191)
8.5
(216)
8.0
(203)
+
-
SHLD
5
RD TD
+
-
SHLD
4
RD TD
+
-
SHLD
3
RD TD
+
-
SHLD
2
RD TD
+
-
SHLD
1
RD TD
(INPUT)
POWER
BAUD RATE
76800
SPARE
38400
19200
9600
2400
1200
300
1 2 3 4 5 6 7
8
RD TDRS-485
RS-232
7.625
(194)
0.33 (8) 4.870
(124)
0.19 (5)
5.5
(140)
OPEN-CLASS *
MOUNTING DIMENSIONS
* OPEN-CLASS MOUNTING:
This equipment is intended for field installation within a UL-listed enclosure.
115/230 VAC ~
50/60 HZ, 3 VA
L
N
LINE VOLTAGE
SELECTOR 115V
USE COPPER CONDUCTORS ONLY
GREEN
EARTH GROUND
BLACK
HOT
WHITE
NEUTRAL
AC
MAINS
USE GROUND STUDS PROVIDED
INSIDE CHASSIS FOR EARTH GROUND USE GROUND STUDS PROVIDED
INSIDE CHASSIS FOR EARTH GROUND
UL864 SMOKE CONTROL NOTICE
In UL864 Installations (Smoke Control),
this cabinet must be surface mounted only.
+ V
- V
24 V ---
1.0 W
USE COPPER CONDUCTORS ONLY
Signal Connection
BLACK
SHIELD
+
-
SHLD
1
RD TD
(INPUT)
NETWORK ACTIVITY
INDICATORS
RS485
RS485
WHITE
RS485 Connections
RS232 Connections
200
RS485
4000 ft (max.)
1219 m (max.)
RS485
4000 ft (max.)
1219 m (max.)
RS485
4000 ft (max.)
1219 m (max.)
RS485
4000 ft (max.)
1219 m (max.)
1
(INPUT)
2 3 4 5
RS485
RS232
Wiring Rules
High voltage AC Power wiring should be routed to the conduit
opening nearest the AC power terminals.
Do not bundle or route AC Power wiring with low voltage input or
output wiring.
Be absolutely certain that your installation complies with all aspects
of the National Electric Code, NFPA 70. Be especially sure that
your system is properly grounded.
Cable Recommendations:
RS-485: 22-24 AWG blanced, twisted-pair cable with braided shield
Building Ground Requirements
Be sure that all equipment from Schneider Electric is grounded to true earth
ground. True Earth ground protects the equipment from transients and other
power surges in the area. Special studs are pressed into the inside of the
chassis for use as a ground connection.
We cannot guarantee that the controller system will operate as documented
without a properly grounded installation.
An example of a sub-standard ground is a galvanized steel cold water pipe.
As the pipe corrodes, it does not act as a true ground. The corrosion acts
as an insulator, raising the potential of the pipe with respect to the ground.
Communications Baud Rate
BAUD RATE
76800
SPARE
38400
19200
9600
2400
1200
300
1 2 34567
8
To select a baud rate, slide the
appropriate switch to the right.
Warning: Only one switch may be
activated at a time. If no switch is
selected unit will not operate.
All connected network rates must
be the same.
InfiNet I speed is limited to 19200
PIN 1: CHASSIS GROUND PIN 7: SIGNAL GROUND
PIN 2: TRANSMIT DATA PIN 9: +12VDC @ 25mA
PIN 3: RECEIVE DATA PIN 10: -12VDC @ 25mA
PIN 4: ENABLE PIN 20: ENABLE
1
POWER
System Indicators/Controls
POWER indicates that the proper power is
applied to the unit.
© 2010 Schneider Electric, All Rights Reserved.
Schneider Electric - One High Street - North Andover MA USA 01845
Note: These
circuits are
Supervised.
Caution: Earth ground ( ) must be
connected to avoid module damage.
!