Powerware® 5140 Rack-Mount UPS
Product Snapshot
Rating: 6000 VA/
6000 Watts
Voltage: 200-240 Vac
Frequency: 50/60 Hz
Configuration: 6U rack-mount
for standard
19-inch racks

T

o meet the power protection needs of

In addition to its exceptional power rating
and size, the Powerware 5140 also

F e a ture s

applications, Powerware Corporation

incorporates Advanced Battery

A

(formerly Exide Electronics) proudly intro-

Management (ABM™) which assures

Power Factor Corrected (PFC) design
protects more equipment

duces the Powerware 5140 Rack-Mount

reliability and improves performance by

A

uninterruptible power system (UPS). The

doubling battery service life, optimizing

6U rack height conserves valuable
rack space

Powerware 5140 is powerful and flexible

recharge time, and providing up to a 60-

A

enough to respond to the demands of

day notice of the end of useful battery life.

Advanced Battery Management
(ABM™) doubles battery service life

A

Buck and Boost voltage
regulation with pure sine
wave output

A

Extended Battery Modules (EBMs)
prolong run times

A

Modular design eases setup and
service

A

Load Segments (separate receptacle
groups) enable scheduled shutdowns
and maximize run time for
critical devices

A

Hot-Swappable batteries and Manual
Bypass Switch simplify service

A

Backed by 10-Year Pro-rated
Warranty (U.S. and Canada)

rapidly expanding rack-based

virtually any Enterprise computing
network.

The Powerware 5140 utilizes multiple
receptacle groups, called Load Segments,

The Powerware 5140 is designed with a

which can be pre-configured to shutdown

unity power factor rating, meaning it is

peripherals first to effectively triple battery

ideally suited to meet the requirements of

run times for the most critical equipment.

today's Power Factor Corrected (PFC)

Extended Battery Modules (EBMs) are also

loads. With proven and reliable technology,

available to extend run times, and to

it delivers up to a third more power than

preserve data integrity, the Powerware

traditionally rated UPSs while still

5140 is bundled with award-winning

occupying only 6U (10.5 inches) of

LanSafe III and FailSafe III power

valuable rack space.

management software.

Technical Specifications1
Advanced Battery Management (ABM™) Technology Doubles Battery Service Life
The lead-acid batteries typically used in a
UPS are considered viable as long as they
can maintain backup times of at least half
that of new batteries. The illustration to the
right shows that batteries that are constantly
trickle charged (as are virtually all other UPS
batteries on the market today) reach the end
of their useful life in less than half the time
of batteries charged using ABM. ABM uses a
patented three-stage charging technique that
not only doubles battery service life, but

Data based upon tests performed by an independent battery manufacturer.

also optimizes battery recharge time and
provides up to a 60-day advanced notification of pending end of useful battery life.

ELECTRICAL INPUT

C O M M U N I C AT I O N S

Voltage

200, 208, 220, 230, & 240 Vac user-selectable;
see Model Selection Guide for default settings

Serial Ports

Normal Voltage
Range

±20% of nominal voltage without using batteries

Extended Voltage
Range

160-288V without using batteries (set via front panel)

Frequency

50/60 Hz, ±3 Hz (+5/-3 Hz with extended voltage range)

Connection

Hardwired

Efficiency

96%

ELECTRICAL OUTPUT

User LEDs
LCD
LCD Languages
Front Panel Buttons
Communications
Cable

(2) Serial communication ports for use with power
management software and installable option cards,
including ConnectUPS SLC-EM SNMP Adapter and the
Port Expander Card
Normal Operation (green), On Battery (yellow),
On Bypass (yellow), and Alarm (red)
Two-line LCD with three button control
Danish, Dutch, English, French, German, Spanish,
Italian, and Japanese
On, Off, and Alarm Silence/Self Test
6-foot communication cable included

Power Out

6000 VA/6000 Watts

E N V I R O N M E N TA L A N D S A F E T Y

Voltage Range
(online)

±10% of nominal voltage

Operating
Temperature

Voltage Range
(on battery)

±5% of nominal voltage

Transit Temperature -20°C to 55°C

Wave Form
(on battery)

Sine Wave

Frequency

Same as input (±0.5% during battery operation)

Connections

Receptacles or hardwired; see Model Selection Guide

Max Current

29A at 208 Vac; 26A at 230 Vac

Output Protection

Resettable circuit breakers

B AT T E R Y

10°C to 40°C (25°C for optimal performance)

Storage Temperature 0°C to 25°C
Humidity (Operation) 20 to 80% (noncondensing)
Humidity
(Non-operating)

5 to 95%

Operating Altitude

0 to 10,000 feet (non-operating: 0 to 30,000 feet)

Audible Noise

55 dBA at 1 meter

Safety Markings

UL, CSA, NOM. Models PW5140 6000i and
PW5140 6000 HW also CE and VDE

Safety
Certifications

UL1778; CSA22.2 No.107.1,No.107.2,No.950; CB
Bulletin No.86AI; EN50091-1; EN60950;
EMKO-TSE207/95; NOM-019-SCFI-1993

Type

Maintenance-free, sealed, valve-regulated lead-acid
(VRLA), (28), 12V 5 AH

Extended Batteries

Maximum of 2 Extended Battery Modules (EBMs)

Backup Time

See Battery Run Times table

EMC Markings

FCC-A; CISPR-A; VCCI

Recharge Time

<3 hours to 80% usable capacity

Immunity

IEC 801-2, IEC 801-3, IEC 801-4, IEC 801-5

Extended Battery
Recharge Time

<10 hours to 80% usable capacity

Surge Suppression

Conforms to IEEE 587B and ANSI C62.41

REPO Port

Meets NEC code 645-11 intent and UL requirements

1. Due to continuing product improvement programs, specifications are subject to
change without notice.

Powerware 5140 Features
Load Segments
Load Segments are groups of receptacles that can be independently controlled via the front
panel LCD interface and/or LanSafe III/FailSafe III, which is bundled with the Powerware
5140. Load Segments provide extended battery run times and flexible management of the
UPS. The five Load Segments of model PW5140 6000i are outlined below.

Unity Power
Factor Rating
What does unity power factor rating mean?
Quite simply, it means that the watt rating of the
UPS is equal to its VA rating. Traditionally,
UPSs have been designed, built, and sold with a

Load Segments divide the
Powerware 5140 into five
virtual UPSs

power factor rating of approximately 0.6 to 0.7.
For example, a 1000 VA UPS could supply a
Shut down Load Segments
to decrease load and
extend backup time for
other Load Segments

Reboot a locked up server
by turning a Load Segment
off and on

maximum of 600 to 700 watts. Historically, this
0.7 power factor was appropriate for the
majority of computer loads the UPS was
intended to support since most computers
demanded power at a 0.7 power factor.
Today, however, a large percentage of high-end
computers, utilize Power Factor Corrected
(PFC) power supplies, which have a power

Front Panel Display

factor of approximately 1.0. Take a look at the
configuration below:
Equipment

Load:
Watts

Load:
VA

(3) Servers*

3300

3366

(2) Workstations*

1000

1020

(1) Color Monitor

200

300

Total

4500

4686

LCD Status Screen
Menu Navigation
Keys
Bypass LED

UPS On Battery

Alarm LED

Power On (Normal)

*Equipment with PFC power supplies.

On

Off

Alarm Silence/
Self-Test

To support this load, you need to select a
UPS with a rating that meets or exceeds both

Extended Battery Modules (EBMs)

the watt and VA demand shown above.

To extend battery backup times, you can connect up to two EBMs. Each EBM occupies

A traditionally rated 5000 VA/3750 watt UPS

3U (5.25 inches) of rack space.

without a unity power factor rating cannot be
used. The Powerware 5140, on the other
You can hot-swap both the
standard batteries and EBMs
without powering down the
connected load. This makes it
possible to extend the life of
the UPS without returning the
unit for service.

hand, has capacity to spare.

Powerware® 5140 Model Selection Guide
MODEL
NUMBER

POWER OUT
(VA/W AT T )

I N P U T /O U T P U T
V O LTA G E (V A C )

FREQUENCY
(H Z )

INPUT
CONNECTION

PW5140 6000i

6000/6000

208/2302

50/603

Hardwired

PW5140 6000

6000/6000

208/2302

50/603

Hardwired

PW5140 6000 HW
Options

6000/6000

208/2302

50/603

Hardwired

PW5140 BATT

–

–

–

PW5140 PDU7

250/250

120

PW5119 MK23

–

–

OUTPUT
R E C E P TA C L E S
(12) IEC-320, C13 &
(3) IEC-320, C194
(2) L6-30R &
(2) IEC-3205
Hardwired &
(2) IEC-3205

60

Custom
Adapter
Custom
Adapter

(2) 5-15R

–

–

–

–

DIMENSIONS
(H X W X D) 1
10.5 x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm
10.5 x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm
10.5 x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm
5.25 x 17.25 x 22.5 in
13.3 x 43.8 x 57.2 cm
1.98 x 19.28 x 9.90 in
5.03 x 48.97 x 25.15 cm
Adjustable; fits
standard 19-inch rack

WEIGHT
(KG/LB)
136/3006
136/3006
136/3006

81.6/180
8.6/19
4.5/10

1. 19-inch wide front panel with a 17.25-inch wide chassis; depth does not include front panel (.5 inches) 2. 208/230 Vac auto-sensing default. User-selectable via
LCD interface for 200, 208, 220, 230, and 240 Vac. 3. Automatic frequency synchronization. 4. Divided into 5 Load Segments. 5. Divided into 2 Load Segments;
IEC-320 receptacles are used to connect optional PW5140 PDU. 6. Shipping weight is 325 pounds (147 kg). 7. Sidewall design occupies 0U of rack space.

B AT T E R Y R U N T I M E S
LOAD
1000 Watts
2000 Watts
3000 Watts
4000 Watts
5000 Watts
6000 Watts

S TA N D A R D

ONE ADDITIONAL

TWO ADDITIONAL

B AT T E R I E S
1 hour 2 minutes
28 minutes
18 minutes
12 minutes
8 minutes
6 minutes

E X T E N D E D B AT T E R Y M O D U L E
2 hours 24 minutes
1 hour 6 minutes
40 minutes
28 minutes
21 minutes
18 minutes

E X T E N D E D B AT T E R Y M O D U L E S
3 hours 56 minutes
1 hour 47 minutes
1 hour 6 minutes
47 minutes
36 minutes
28 minutes

This table provides typical information. Battery times are approximate and may vary with equipment, configuration, disk access, battery use, temperature, etc.

R E A R PA N E L S

PW5140 6000i

PW5140 6000 HW

PW5140 6000

A (2) I N S TA L L A B L E O P T I O N S L O T S

E HARDWIRE INPUT

I

B (2) C O M M U N I C AT I O N P O R T S

F LOAD SEGMENT 1

J LOAD SEGMENT 5

LOAD SEGMENT 4

C M A N U A L B Y PA S S S W I T C H

G LOAD SEGMENT 2

K CIRCUIT BREAKER(S)

D REPO P O R T

H LOAD SEGMENT 3

L IEC-320 R E C E P TA C L E S
M HARDWIRE OUTPUT

Powerware Corporation
Corporate Headquarters

Latin America/Caribbean

China and North Asia

8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.877.797.9273 (PWRWARE)
or 919.872.3020
Fax: 1.800.753.9433
or 919.870.3411
E-mail: info@powerware.com
www.powerware.com

Europe/Middle East/Africa

Australia and South Pacific

Southeast Asia

Canada

Revision 5140FXA 7/99
Reprint 7/99

Sunrise, FL: 954.835.1180

Berkshire, England: 44.1753.606700
Singapore: 65.861.9877

Hong Kong: 852.2745.6682
Sydney, Australia: 61.2.9878.5000
Toronto, Ontario: 416.798.0112

FOR

PDU C O N N E C T I O N



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.1
Linearized                      : No
Page Count                      : 4
Create Date                     : 1999:07:26 14:14:34
Producer                        : Acrobat Distiller 3.01 for Power Macintosh
Creator                         : QuarkXPressª 4.03: LaserWriter 8 8.5.1
Author                          : mdeeb
Title                           : _PW5140_.799
EXIF Metadata provided by EXIF.tools

Navigation menu