Powerwave Technologies 5JS0071 Multi Carrier RF Power Amplifier User Manual
Powerwave Technologies Inc Multi Carrier RF Power Amplifier Users Manual
Users Manual
G3L-850-135 Multi-Carrier Power Amplifier Service and Installation Manual 044-05117 December 2004 044-05117 © 2004 Powerwave Technologies Incorporated. All rights reserved. Powerwave Technologies, and the Powerwave logo are registered trademarks Powerwave Technologies, Inc. reserves the right to make changes to the documentation and equipment, including but not limited to component substitution and circuitry changes. Changes that impact this manual may subsequently be incorporated in a later revision of this manual. This Powerwave product is designed to operate within the Normal Operating (typical operating) ranges or conditions specified in this document. Operation of this equipment beyond the specified ranges in this document may cause (1) spurious emissions that violate regulatory requirements; (2) the equipment to be automatically removed from service when maximum thresholds are exceeded; or (3) the equipment to not perform in accordance with its specifications. It is the Operator's responsibility to ensure this equipment is properly installed and operated within Powerwave operating specifications to obtain proper performance from the equipment and to comply with regulatory requirements. ii Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Warnings, Cautions, and Notes Warnings, cautions, and notes are found throughout this manual. The associated icons in warnings and cautions are used to quickly identify a potential condition that could result in the consequences described below if precautions are not taken. Notes clarify and provide additional information to assist the user. This warning symbol means danger. You are in a situation that could cause WARNING bodily injury. Before you work on any equipment, be aware of the hazards involved with electrical and RF circuitry and be familiar with standard practices for preventing accidents. CAUTIO This caution symbol means reader, be careful. In this situation, the user might do something that could result in equipment damage or loss of data. This note symbol means reader, take note. Notes contain helpful suggestions or Note references to material not covered in the document. Procedures are not contained in notes. 044-05117 Revision Record Revision Record ii Revision Letter Date of Entry Reason for Change December, 2004 Original version of product Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Table of Contents Chapter No. Chapter 1 1-1 1-2 1-3 1-4 1-5 1-5.1 1-5.1.1 1-5.1.2 1-5.1.3 Installation 2-1 Operating Instructions 3-1 Introduction................................................................................................................... 3-1 Controls and Indicators ................................................................................................ 3-1 RESET Switch .............................................................................................................. 3-1 LED Status Indicator and RESET/On/Off Toggle Switch............................................. 3-1 RJ-11 PC Interface ....................................................................................................... 3-2 Initial Start-Up and Operating Procedures ................................................................... 3-2 Chapter 4 4-1 4-2 4-3 4-4 4-4.1 4-4.2 4-4.3 4-4.4 4-4.5 4-5 4-6 4-7 1-1 Introduction................................................................................................................... 2-1 Site Survey ................................................................................................................... 2-1 Electrical Service Recommendations........................................................................... 2-1 Air Conditioning ............................................................................................................ 2-2 Unpacking and Inspection ............................................................................................ 2-3 Installation Instructions................................................................................................. 2-4 Installing the Amplifier into the Subrack ....................................................................... 2-4 Amplifier Module Power, Alarm, Control, and RF Connector....................................... 2-5 Chapter 3 3-1 3-2 3-2.1 3-2.2 3-2.3 3-3 General Description Page Introduction................................................................................................................... 1-1 General Description...................................................................................................... 1-1 Functional and Physical Specifications ........................................................................ 1-2 Ordering Information .................................................................................................... 1-5 General Safety.............................................................................................................. 1-6 Lifting Standards........................................................................................................... 1-6 Power Plant .................................................................................................................. 1-6 Electronic Modules ....................................................................................................... 1-6 Electrostatic Discharge................................................................................................. 1-6 Chapter 2 2-1 2-2 2-3 2-4 2-5 2-6 2-6.1 2-6.2 Title Principles of Operation 4-1 Introduction................................................................................................................... 4-1 RF Input Signal............................................................................................................. 4-1 RF Output Load ............................................................................................................ 4-1 Functional Description.................................................................................................. 4-1 Preamplifier .................................................................................................................. 4-2 Main and Error Amplifiers............................................................................................. 4-2 Alarm Monitoring and Control....................................................................................... 4-2 First and Second Loop Control Circuits ....................................................................... 4-3 Pilot Tone Generator .................................................................................................... 4-3 Amplifier Module Cooling ............................................................................................. 4-3 Power Distribution ........................................................................................................ 4-3 Amplifier Alarms ........................................................................................................... 4-4 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier iii 044-05117 Chapter 5 5-1 5-2 5-3 5-4 5-4.1 5-4.2 5-4.3 5-4.4 5-5 5-5.1 5-5.2 Maintenance 5-1 Introduction................................................................................................................... 5-1 Periodic Maintenance................................................................................................... 5-1 Test Equipment Required For Test .............................................................................. 5-1 Amplifier Performance Test.......................................................................................... 5-2 Amplifier Spurious Emissions Test:.............................................................................. 5-2 Gain Test:..................................................................................................................... 5-3 Input Return Loss: ........................................................................................................ 5-4 Test Data Sheet ........................................................................................................... 5-5 Return For Service Procedures.................................................................................... 5-6 Obtaining An RMA........................................................................................................ 5-6 Repackaging For Shipment.......................................................................................... 5-6 Appendix A Abbreviations and Acronyms Appendix 2 General Site Survey Form List of Figures Figure No. Figure Title Page Figure 1-1. Model G3L-850-135 Amplifier Front Isometric View.................................................. 1-3 Figure 1-2. Model G3L-850-135 Amplifier Rear Isometric View .................................................. 1-3 Figure 1-3. Model G3L-850-135 Amplifier Side View................................................................... 1-4 Figure 1-4. Model G3L-850-135 Amplifier Bottom View............................................................... 1-4 Figure 1-5. Model G3L-850-135 Amplifier Front Panel ................................................................ 1-5 Figure 2-1. Power Switch Functions and Unlocking/Locking Thumbscrews ............................... 2-5 Figure 2-2. DC and Logic Connector (Male, on Rear of G3L-850-135 Amplifier Module)........... 2-5 Figure 3-1. G3L-850-135 Controls and Indicators........................................................................ 3-1 Figure 4-1. Functional Block Diagram .......................................................................................... 4-2 Figure 5-1. Amplifier Test Setup Diagram – Configuration A ....................................................... 5-3 Figure 5-2. Amplifier Test Setup – Configuration B..................................................................... 5-4 iv Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 List of Tables Table No. Table Title Page Table 1-1. General Operating Parameters ................................................................................... 1-1 Table 1-2. G3L-850-135 Amplifier Specifications......................................................................... 1-2 Table 1-3. Major System Components ........................................................................................ 1-5 Table 2-1. Sample of DC Cable Ratings ...................................................................................... 2-1 Table 2-2. 4-Way Combining Averaged DC Current Load........................................................... 2-2 Table 2-3. 4-In/4-Out Non-combining Averaged DC Current Load .............................................. 2-2 Table 2-4. 4-Way Combining Averaged Heat Loading................................................................. 2-3 Table 2-5. 4-In/4-Out Non-combining Averaged Heat Loading.................................................... 2-3 Table 2-6. G3L-850-135 Amplifier Combo Connector Specifications .......................................... 2-6 Table 3-1. Status Indicator Colors and Status.............................................................................. 3-2 Table 4-1. G3L-850-135 Alarm States.......................................................................................... 4-4 Table 5-1. Periodic Maintenance.................................................................................................. 5-1 Table 5-2. Test Equipment Required............................................................................................ 5-2 Table 5-3. Amplifier Performance Data ........................................................................................ 5-5 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 This Page Intentionally Blank vi Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Chapter 1 1-1 General Description Introduction This manual contains information and procedures for installation and servicing of Powerwave’s G3L-850-135 Amplifier. The manual is organized into two chapters as follows: Chapter 1 General Description Chapter 4 Principles of Operation Chapter 2 Installation Chapter 5 Maintenance Chapter 3 Operating Instruction Appendix A Glossary of Terms 1-2 General Description The G3L-850-135 Power Amplifier, shown in Figure 1-1 - Figure 1-5, operates in the 25 MHz frequency band from 869 MHz to 894 MHz with an instantaneous bandwidth of less than 25 MHz. The instantaneous bandwidth is the maximum frequency band in which any two or more signals can occupy .The amplifier’s instantaneous bandwidth is set automatically and does not require any manual setup. The amplifier is modular in design. Table 1-1 gives additional essential operating specifications. Table 1-1. General Operating Parameters Characteristic Performance Remarks Operating Frequency Band 869 MHz to 894 MHz Instantaneous Bandwidth 25MHz Gain 63 dB Spurious Performance ITU-R SM329-9, Category A Non-carrier related Receive Band Noise -98 dBm/Hz In RX channels associated with RF input terminated into 50 Ω. Supply Voltage 21 Vdc to 30 Vdc Nominal +27 Vdc. Degraded mode of operation at less than 26 Vdc. Heat Output 3,074 BTU At full rated power GSM (up to 12 carriers) or GSM 11.21 EDGE +GSM (up to 4 carriers for each) TS 25.141 Carrier Types 3GPP2 C.S0010-B WCDMA (up to 4 carriers) Storage Temperature -40 - +85 °C Ambient Temperature -33 - + 50 °C Altitude -50 - +4,000 m Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 1-1 044-05117 1-3 Functional and Physical Specifications Electrical, mechanical, and environmental specifications for the G3L-850-135 amplifier are listed in Table 1-2. Table 1-2. G3L-850-135 Amplifier Specifications Frequency Range Minimum Channel Spacing Total Maximum Input Power Total Output Power Intermodulation Distortion and In-Band Spurious: RF Gain at 869 to 894 MHz Gain Flatness: Gain Variation Over Temperature: Output Protection: Input Port Return Loss: Out of Band Spurious: Duty Cycle: DC Input Power: Operating Temperature: Storage Temperature: Operating Humidity: Storage Humidity: RF Input / Output / Status / Alarm / Control / DC Input Connectors: Maintenance Port Switches Indicators: STATUS Dimensions: Weight: Note 1-2 869-894 MHz; 25 MHz bandwidth (lowest to highest transmitted frequency) 1 to 8 GSM carriers -12.21 dBm @ 135 Watts (to achieve rated power); -11.91 dBm max. -6.0 dBm or greater causes input overdrive shutdown. 135 Watts (7GSM and 1EDGE) @27Vdc 120 Watts (GSM/EDGE) @26Vdc to 30Vdc 110 Watts (W-CDMA) @26Vdc to 30Vdc -65 dBc (Min) @ +26 to +28 Vdc @ 135 Watts; 600 KHz channel spacing within 25 MHz bandwidth* 63 dB ±1 dB ±0.5 dB @ 27 Vdc ±1 Vdc ±0.5 dB from 26 Vdc to 28 Vdc over -20° to +50° C Mismatch protected Equal to or greater than 14dB Better than -60 dBc, +26 Vdc to +28 Vdc Continuous +27 Vdc ± 1 Vdc, 34.1 Amps typical, 36 Amps max @ 135 Watts; operational range +21.0 Vdc to 30 Vdc amplifier will disable at < 20.5 Vdc or > +30.5 Vdc. -33 ºC. to +50 ºC. -40 ºC. to +85 ºC. 5 % to 95 % relative humidity (non-condensing) 5 % to 95 % relative humidity (non-condensing) 21-Pin D-Subminiature combo connector RJ-11, RS-232 signaling (for factory use only) Reset/On/Off Switch LED; Green (normal), Yellow (minor alarm), Red (critical alarm) 35.46 cm wide, 9.56 cm high, 45.0 cm deep (including handles) 12.97 kg This Powerwave product is designed to operate within the normal operating (typical operating) ranges or conditions specified in this document. Operation of this equipment beyond the specified ranges may cause (1) spurious emissions that violate regulatory requirements; (2) the equipment to be automatically removed from service when maximum thresholds are exceeded; or (3) the equipment to not perform in accordance with its specifications. It is the operator's responsibility to ensure this equipment is properly installed and operated within Powerwave operating specifications to obtain proper performance from the equipment and to comply with regulatory requirements. Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Figure 1-1. Model G3L-850-135 Amplifier Front Isometric View Figure 1-2. Model G3L-850-135 Amplifier Rear Isometric View Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 1-3 044-05117 Figure 1-3. Model G3L-850-135 Amplifier Side View Figure 1-4. Model G3L-850-135 Amplifier Bottom View 1-4 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Figure 1-5. Model G3L-850-135 Amplifier Front Panel 1-4 Ordering Information Table 1-3 lists major system component numbers and descriptions for use in ordering amplifiers or components. Table 1-3. Major System Components Model Number Description G3L-850-135 135-Watt Amplifier, +27 Vdc *MCR41927-1-4 4-way Combining Amplifier Subrack *MCR41928-4-4 4-In/4-Out Non-combining Amplifier Subrack *MCR41970-4-4 4-In/4-Out N+1 Non-combining Amplifier Subrack *Amplifier subracks sold and described separately Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 1-5 044-05117 1-5 General Safety This paragraph describes safety practices when handling certain components. 1-5.1 Lifting Standards The handling of the power amplifier cabinet and its subassemblies involves heavy lifting. Various methods of lifting must be employed to safely and properly install this equipment. The following web site addresses are provided as references to OSHA personnel lifting guidelines: http://www.osha.gov/SLTC/etools/electricalcontractors/materials/heavy.html http://www.cdc.gov/niosh/pdfs/94-110.pdf Lifting of heavier modules may require two people in awkward work environments, whereas only one person might otherwise be able to safely lift the module. Be aware of the environmental impact on lifting and twisting while moving heavier materials. The Amplifier weighs 12.97 kg (28.5 lb) and can normally be lifted by one person. 1-5.1.1 Power Plant Only qualified electricians, certified to work on high voltages (176 to 264 Vac; 150 A), should perform installation and maintenance to the cabinet and rectifier inputs. Failure to follow safe practices may result in equipment damage, personal injury or death. Never remove bare DC power wires from equipment or allow bare DC voltage wires to dangle freely in the cabinet. Prior to removal of equipment that necessitates dangling of DC wires, disconnect DC power at the LVD and turn the rectifiers off. Verify with a voltmeter that DC power is removed prior to disconnecting equipment. Refer to NEC Article 810, for clearances from power and lightning conductors, mounting, and grounding. 1-5.1.2 Electronic Modules Electronic modules should be turned off before removal, when an on/off switch is provided. For example, the amplifier module draws up to 26 amperes of current with no RF energy applied. Failure to turn the amplifier module off before removal will cause arching between the amplifier module and the amplifier subrack, resulting in damage to both pieces of equipment. RF energy should be turned off before removal or installation of RF cables. Failure to RF energy may result in equipment damage or personal injury. Electronic modules should be turned off before removal or installation of electronic interconnecting cables. 1-5.1.3 Electrostatic Discharge The power amplifier cabinet contains modules and components that are sensitive to static electricity. Two Electrostatic Discharge (ESD) service points are incorporated in the cabinet frame. One service point is located in the interior front electronics compartment about half way down the right hand vertical rail. The other service point is located in the interior rear electronics compartment about half way down the left hand vertical rail. ESD protective devices must be properly worn and connected to one of the cabinet ESD service points by technicians and installers during the performance of maintenance activities. 1-6 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Chapter 2 2-1 Installation Introduction This chapter contains unpacking, inspection, and installation instructions for the G3L-850-135 Multi-Carrier Power Amplifier (MCPA). It is important that the licensee perform the following tasks correctly. Carefully read all material in this chapter prior to equipment unpacking or installation. Also, read and review the operating procedures in chapter 3 prior to installing the equipment. If applicable, carefully review the government and local codes as they apply to your installation. 2-2 Site Survey Powerwave Technologies recommends that site surveys be performed by qualified individuals or firms prior to equipment ordering or installation. Performing a detailed site survey reduces or eliminates installation and turn-up delays caused by oversights. Pay particular attention to power plant capacity, air conditioning needs, and RF/DC cabling/breaker requirements. 2-3 Electrical Service Recommendations Powerwave Technologies recommends that proper AC line conditioning and surge suppression be provided on the primary AC input to the +27 Vdc power source. Install all electrical service in accordance with applicable local codes and good engineering practice. Give special consideration to lightning protection of all systems, given the vulnerability of most transmitter sites to lightning. Lightning arrestors are recommended in the service entrance. Straight, short ground runs are recommended. The electrical service must be well grounded. The information in Table 2-1 is provided as a guideline. Follow the appropriate standards in the National Electrical Code (NEC) and codes for your area, and observe the cable manufacturer’s recommendations for proper cable selection. Table 2-1. Sample of DC Cable Ratings Copper mm 3 Cond. In Raceway Aluminum Single Conductor In Free Air 3 Cond. In Raceway 90°C 110°C Single Conductor In Free Air 90°C 110°C 90°C 110°C 125°C 200°C 90°C 110°C 125°C 200°C 25 30 30 40 40 45 -- -- -- -- -- -- 30 35 40 50 50 55 25 25 30 40 40 45 40 45 55 65 70 75 30 35 45 50 55 60 55 60 75 85 90 100 40 45 55 65 70 80 13 70 80 100 120 125 135 55 60 80 95 100 105 21 95 105 135 160 170 180 75 80 105 125 135 140 34 125 135 185 210 225 240 100 105 140 165 175 185 42 145 160 215 245 265 280 110 125 165 190 205 220 53 165 190 250 285 305 325 130 150 190 220 240 255 Based on ambient temperature of 30°C (86°F) 100% Load Factor Source: Industrial Electric Wire & Cable Inc., Technical Guide Vol. 4M 11/99, Table III Suggested Ampacities - All Types of Insulations; Based on National Electric Code Each amplifier system should have its own circuit breaker, so a failure in one does not shut off the whole installation. Circuit breakers should be capable of handling the anticipated inrush current, in a load center with a master switch. Powerwave recommends that a 50 A circuit Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 2-1 044-05117 breaker be installed in the power distribution unit for each amplifier. DC wire smaller than 8 mm2 90°C copper should not be installed. Each amplifier should have its own DC cable pair. Refer to Table 2-1. According to the laws of probability used to formulate Erlang tables, rarely are all channels transmitting at the same time. We can use Erlang tables to predict typical maximum current usage. Table 2-2 and Table 2-3 describe the current load (at 120 Watts typical) for a 3 sector (70%), 2 sector (80%) and omni (90%) site in two different configurations. Based on table 2-2, a 600-ampere power plant may suffice in a macro-cell site, whereas, a 200-ampere or smaller power plant may be adequate in a micro-cell site, based on the equipment configuration. Battery backup or UPS systems should be installed in remote sites or in sites that experience brownout conditions or generator switchovers. Adding this equipment should eliminate the need for site visits by technicians after brownouts or power outages. Battery backup systems also provide excellent DC filtering as a side benefit. Table 2-2. 4-Way Combining Averaged DC Current Load Amplifier Power No. Of 3-Sector (70%) 2-Sector (80%) 1-Sector (90%) Amplifiers Averaged Current Averaged Current Averaged Current 120 12 *348 A 120 *232 A 120 *116 A 120 *29 A * typical, based on given % of output power) *254 A *127 A *32 A *130 A *33 A 100% Typical 409 A 273 A 136 A 34 A Table 2-3. 4-In/4-Out Non-combining Averaged DC Current Load Amplifier Power No. Of 3-Sector (70%) 2-Sector (80%) 1-Sector (90%) Amplifiers Averaged Current Averaged Current Averaged Current 120 *99 A 120 *87 A 120 *58 A 120 *29 A * typical, based on given % of output power) 2-4 *95 A *63 A *32 A *65 A *33 A 100% Typical *114 A *102 A *68 A *34 A Air Conditioning Each G3L-850-135 amplifier generates 3,074 BTUs of heat at full 135-Watt power. A 1-ton air conditioner offsets 12,000 BTU’s of heat. The G3L-850-135 amplifier is designed to operate within the extended low temperature and high temperature environments defined in table 1-2. In keeping with Paragraph 2-3, Table 2-4 and Table 2-5 describe the heat load (at 120 Watts typical) for a 3-sector (70%), 2-sector (80%), omni (90%), and typical (100%) site. Perform a site survey to determine actual air conditioning needs. 2-2 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Table 2-4. 4-Way Combining Averaged Heat Loading Amplifier Power 120 120 120 120 No. Of Amplifiers 3-Sector (70%) Averaged BTU/hour 2-Sector (80%) Averaged BTU/hour 28,791 19,194 9,597 2,399 20,638 10,319 2,580 12 1-Sector (90%) Averaged BTU/hour 100% Typical BTU/Hour 32,793 21,862 10,931 2,733 10,514 2,629 * typical, based on given % of output power Table 2-5. 4-In/4-Out Non-combining Averaged Heat Loading Amplifier Power 120 120 120 120 No. Of Amplifiers 3-Sector (70%) Averaged BTU/hour 2-Sector (80%) Averaged BTU/hour 9,585 7,198 4,799 2,399 7,739 5,160 2,580 1-Sector (90%) Averaged BTU/hour 100% Typical BTU/Hour 5,257 2,629 10,585 8,198 5,465 2,733 * typical, based on given % of output power 2-5 Unpacking and Inspection This equipment has been operated, tested, and calibrated at the factory. Only in the event of severe shocks or other mistreatment should any substantial readjustment be required. Carefully unpack each piece of equipment after it has reached the installation site and is approximately in place. Carefully open the several amplifier system containers and remove the contents. Inventory all items to ensure all needed materials have been delivered. Retain all packing material to support any claim of shipping damage or for use in the event that the equipment must be returned to the factory. Exercise care in handling equipment during inspection to prevent damage CAUTION caused by rough or careless handling. Some components are heavy. Follow the guidelines set forth in Paragraph 1-5.1 when lifting heavy components. Visually inspect the Amplifier for damage that may have occurred during shipment. Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extraneous packing material in the connectors or fans. Inspect male connectors on modules and harnesses for bent connector pins. Perform the following steps: 1. Visually inspect the MCPA for damage that may have occurred during shipment. 2. Check for evidence of water damage, bent or warped chassis, loose screws or nuts, or extraneous packing material in the connector(s). Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 2-3 044-05117 CAUTION Before applying power, make sure that all connectors are secure. Make sure that the input and output are properly terminated at 50 ohms. Do not operate the system without a load attached. Refer to Table 1-2 for input power requirements. Excessive input power may damage the equipment. If the equipment is damaged: • The carrier is your first area of recourse. • A claim should be filed with the carrier once the extent of any damage is assessed. We cannot stress too strongly the importance of IMMEDIATE careful inspection of the equipment and the subsequent IMMEDIATE filing of the necessary claims against the carrier, if necessary. If the equipment is damaged and must be returned to the factory: • Please write or phone for return authorization. • Powerwave may not accept returns without a return authorization. 2-6 Installation Instructions Install the G3L-850-135 amplifier as follows: WARNING Turn off external primary DC power before connecting DC power cables. 2-6.1 Installing the Amplifier into the Subrack 1. For each Amplifier: a. Inspect the 21WA4 male combo connector on the rear of each amplifier. Verify that all pins are straight, no pins are recessed, packing material is removed, and that the alignment shield is not bent. b. Set the amplifier power Reset/On/Off switch to “Off” (down position) as shown in Figure 2-1. CAUTION Note Do not slam or force the amplifier into the subrack. This may cause the pins on the 21-D sub connector of the amplifier to become recessed or broken. Non-combining subracks are typically sector specific; ensure the amplifier is installed to support the appropriate sector. c. With the thumbscrews in the unlock position, install the amplifier(s) into the subrack. There are no slot priorities in a combining subrack, so all slots function equally. To secure the amplifier(s) in the subrack, turn the top and bottom thumbscrews to the lock position as shown in Figure 2-1. WARNING Check your work before applying DC voltage to the amplifier. Make certain all connections are tight and correct. 2-4 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 2. Measure primary DC input voltage. DC input voltage should be +27 Vdc ±1.0 Vdc. If the DC input voltage is above or below the limits, call and consult an electrician before you turn on your amplifier system. Refer to Chapter 3 for initial turn-on and checkout procedures. Unlock Position Lock Position 3-Position Switch: Reset (Up) On (Middle) Off (Down) Figure 2-1. Power Switch Functions and Unlocking/Locking Thumbscrews 2-6.2 Amplifier Module Power, Alarm, Control, and RF Connector The power, alarm, control, and RF connections on the amplifier are made through a 21WA4 male connector, located on the rear of the amplifier. Pins are listed and described in Table 2-6. Alarms are interpreted by the amplifier subrack and reported to the base station as a system level alarm. A1 2 3 4 5 6 7 8 9 A3 A2 A4 10 11 12 13 14 15 16 17 Figure 2-2. DC and Logic Connector (Male, on Rear of G3L-850-135 Amplifier Module) Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 2-5 044-05117 Table 2-6. G3L-850-135 Amplifier Combo Connector Specifications 21WA4 Connector Description 2-6 Pins/Signal Names A1 RF Input (Coaxial Contact) A2 +27 Vdc (Power Contact) A3 Ground (Power Contact) A4 RF Output (Coaxial Contact) TX H (RS-485) 10 System Reset TTL TX L (RS-485) 11 NC GND 12 NC RX H (RS-485) 13 AMP AO RX L (RS-485) 14 AMP A1 GND 15 AMP A2 MOD_DET 16 NC Summary Fault 17 MCPA Temp DC (On/Off) Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Chapter 3 3-1 Operating Instructions Introduction This chapter contains a description of the G3L-850-135 Multi-Carrier Power Amplifier (MCPA) controls, indicators, and initial start-up and operating procedures. 3-2 Controls and Indicators The controls and indicators for the G3L-850-135 Power Amplifier consist of the primary power RESET toggle switch, the LED STATUS indicator, and the RJ-11 PC Interface as shown in Figure 3-1. 3-2.1 RESET Switch The RESET Switch, located on the front panel, has three positions, each with its own function. • The momentary up position resets fault indications and returns the Amplifier to normal operation if a critical or hard fault does not prevent such operation. When the switch is released, it automatically returns to the middle position. • The middle position allows normal operation. If no critical faults are present, the Amplifier operates normally. • The down position is used to turn the amplifier off. The Amplifier remains disabled until the switch is manually returned to the middle position. RJ-11 PC Interface Reset/On/Off Toggle Switch Multi-Colored LED Status Indicator Figure 3-1. G3L-850-135 Controls and Indicators 3-2.2 LED Status Indicator and RESET/On/Off Toggle Switch The status indicator, located on the front panel, is a single, tri-color LED. Status is indicated by a combination of color and intermittent/steady operation. The LED has tri-color capability: red, yellow, and green. The LED’s blinking frequency is 0.5-1 Hz with a duty cycle of 45-55%. The LED indicates the status of the MCPA as listed in Table 3-1. Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 3-1 044-05117 Table 3-1. Status Indicator Colors and Status Control/Indicator STATUS (Multicolored LED Indicator) Description LED Color MCPA Status Green (solid) RF enabled, Reset/On/Off switch set to On (middle position). Green (blinking) Standby. Yellow (solid) Minor* alarm - APC function enabled. Red (solid) Major* alarm – Critical fault present. If present on only one amplifier, amplifier replacement required. If present on all amplifiers in a subrack, a fault exists in the subrack or in the RF load attached to the subrack. Red/Yellow (alternating) Downloading. Do not interrupt power. Toggle Switch positions RESET (Up) Amplifier in RESET mode. LED indicates Boot mode, then turns solid green. On (Middle) Amplifier enabled. LED indicates solid green Off (Down) Amplifier disabled. LED Indicates solid red. * See Table 4-1 for an explanation of major and minor alarms. 3-2.3 RJ-11 PC Interface The RJ-11 PC Interface connector, located on the Front Panel, is for updating the amplifier’s firmware, and is for factory use only. 3-3 Initial Start-Up and Operating Procedures To perform the initial start-up, proceed as follows: 1. For each Amplifier: a. Verify that all input and output cables are properly connected. Caution Before applying power, make sure that the input and output of the amplifier are properly terminated at 50 ohms. Do not operate the amplifier without a load attached. Refer to table 1-2 for input power requirements. Excessive input power may damage the MCPA. Note The amplifiers must be warmed up for a minimum of 5 minutes prior to setting power levels. Failure to properly warm the amplifiers may result in lower output power, once the amplifiers reach operating temperature. b. Turn on the supply that provides +27 Vdc to the amplifier. 3-2 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 c. Place the power 3-position (Reset/On/Off) switch on the amplifier front panel to the On (middle) position. 2. Allow the amplifiers to warm up for at least 5 minutes before taking power readings. Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 3-3 044-05117 This Page Intentionally Blank 3-4 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Chapter 4 4-1 Principles of Operation Introduction This chapter contains a functional description of the G3L-850-135 Multi-Carrier Power Amplifier (MCPA). 4-2 RF Input Signal The maximum input power for all carrier frequencies to the amplifier should not exceed the limits specified in Table 1-2 4-3 RF Output Load For good power transfer to the RF load, the load impedance should be as closely matched to the output impedance of the amplifier as possible. A VSWR of less than 1.5:1 across the working band of frequencies is satisfactory. If the amplifier is operated into a filter, it maintains its distortion characteristics outside the signal band even if the VSWR is infinite. A parasitic signal of less than one-watt incident on the output will not cause distortion at a higher level than the normal forward distortion (i.e. -65 dBc). 4-4 Functional Description The Multi-Carrier Power Amplifier (MCPA) is a linear, feedforward amplifier that operates in the frequency band from 869 MHz to 894 MHz with an instantaneous bandwidth of less than 25 MHz (refer to Table 1-2 for amplifier specifications). The instantaneous bandwidth is the maximum frequency band that a set of two or more signals can occupy .The amplifier’s instantaneous bandwidth is set automatically and does not require any manual setup. The amplifier provides a gain of 63 dB. Typical outputs for different carrier types are specified in Table 1-2. Each amplifier is a self-contained module and is functionally independent of any other MCPA in a system. The amplifiers are designed for parallel operation to achieve a high peak power output. Each MCPA has an alarm board that monitors the amplifier performance. If a failure or fault occurs in an MCPA, it is transmitted to a subrack system via the D-sub 21WA4 connector located at the rear of the module. The subrack reports all alarms to the host system. Continuously comparing active paths with passive references, and correcting for small variations through RF feedback controls maintain constant gain. All gain variations, for example those due to temperature, are reduced to the passive reference variations. Refer to Figure 4-1 for the amplifier functional block diagram. The amplifier consists of the following major functional blocks: • Preamplifier • Main amplifier • Error amplifier • Alarm monitoring and control • First and second loop control circuits • Pilot tone generator Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 4-1 044-05117 Figure 4-1. Functional Block Diagram 4-4.1 Preamplifier The RF carriers are applied to the input port of the amplifier, where they are fed to the preamplifier stage. The preamplifier provides two stages of class-A mode-amplification. The output of the preamplifier is then split into two paths, one to the main amplifier and one to the error amplifier. 4-4.2 Main and Error Amplifiers The main amplifier provides the balance of gain and power (refer to Table 1-1 for amplifier specifications). The main amplifier employs class AB amplification for maximum efficiency. The error amplifier and feed forward loops are used to correct signal distortion introduced by nonlinearity in the class AB main amplifier. The error amplifier operates in class A mode. The RF signal from the preamp is coupled to an attenuator and phase shifter in the first feed-forward loop where it is phase shifted by 180 degrees and amplified in the pre-main amplifier. The output from the pre-main amplifier is fed to the class AB main amplifier. The signal output from the main amplifier is sampled using a coupler, and the sample signal is combined with the main input signal and input to the second feed-forward loop. The error signal is attenuated, phase shifted 180 degrees, then fed to the error amplifier where it is amplified to a level identical to the sample output from the main amplifier. The output from the error amplifier is then coupled back and added to the output from the main amplifier. The control loops continuously make adjustments to cancel out any distortion in the final output signals. 4-4.3 Alarm Monitoring and Control The alarm logic controls the +5 Vdc bias voltage that shuts down the amplifier. During routine operation, all normal variations are automatically compensated for by the feed-forward loop control. However, when large variations occur beyond the adjustment range of the loop control, a 4-2 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 loop fault occurs. When this happens, an alarm indicator is illuminated on the front panel of the subrack. The fault is transmitted back to an external summary module via the external alarm interface connection on the front panel of the subrack. 4-4.4 First and Second Loop Control Circuits The primary function of the first loop is to amplify the carrier signals and isolate an error signal for the second loop. The primary function of the second loop is to amplify the error signal to cancel out spurious products developed in the main amplifier. The input signal is amplified by a preamplifier and fed to a coupler and delay line. The signal from the coupler is fed to the attenuator and phase shifter in the first loop. The first loop control section phase shifts the main input signals by 180 degrees and constantly monitors the output for correct phase and gain. The second loop control section obtains a sample of the distortion added to the output signals by the main amplifiers. The signal is phase shifted 180 degrees, then fed to the error amplifier where it is amplified to the same power level as the input sample. The signal is then coupled to the error signal of the main amplifier output. The final output is monitored by the second loop and adjusted to ensure that the signal distortion and intermodulation distortion (IMD) on the final output is cancelled out. 4-4.5 Pilot Tone Generator A Pilot Tone is an internally generated signal, who’s precise frequency, phase, and amplitude is known. The basic idea of injecting a pilot tone is that if the pilot signal is suppressed at the amplifier output, then the distortion created by the main amplifier is also suppressed. To accomplish this, the pilot tone signal is injected into the first loop and then detected at the feedforward output of the second loop. The pilot tone is coupled off of the main amplifier, thus creating a second pilot tone, attenuated and phase shifted 180 degrees to be used as the reference. This second pilot tone is then amplified in the error amplifier and mixed with the signals from the main signal path. Ideally, the two pilot tones, both amplified, should cancel each other out. If they do not cancel each other out, as determined by an output detector, the information is fed back to control the gain and phase of both the main and error amplifier paths such that the output distortion is minimized. 4-5 Amplifier Module Cooling The amplifier is cooled by forced air flowing over its heat sink, which is provided by external fans mounted on the MCPA subrack. The fans are field replaceable. Each amplifier, when properly cooled, maintains the amplifier within the specified operating temperature range. Six inches of free space are required at both the front and rear panels of the subrack to allow adequate air volume to circulate over the heat sinks. 4-6 Power Distribution Primary DC power for the amplifier is provided by the host system. The amplifier module has a DC/DC converter and voltage regulator that converts the +27 Vdc to +15 Vdc, +5 Vdc, and -5 Vdc for internal use. Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 4-3 044-05117 4-7 Amplifier Alarms Causes for MCPA alarms are given in Table 4-1. Conditions external to the amplifier should be investigated before replacing the amplifier, particularly if more than one amplifier exhibits a critical alarm. Alarm conditions are reported to the amplifier subrack via RS-485 or TTL interfaces. Other than the front panel LEDs (described in chapter 3), there are no other visual aids for the technician. Table 4-1. G3L-850-135 Alarm States Major Alarm - Causes MCPA RF section to be disabled Amplifier Alarm Output Overpower Automatic Power Control (APC) Input Overdrive Definition Amplifier Mode Disable the MCPA immediately if the output Major power is >2 dB over rated power. Enabled if the output power is > 50 dBm Note: If the MCPA cannot compensate the gain to maintain compliance, the Output Overpower or Input Overdrive Faults will protect the MCPA. Disable the MCPA immediately if the input RF power is > -6.0 dBm High Sensor temperature is > Temperature +88° C Minor Minor Alarm - Does not cause MCPA RF section to be disabled Auto-Recovery Event/Fault Log No auto recovery. Requires Records output manual reset. Output power overpower event after must be decreased to < 2 system disabled dB over rated power. Amplifier auto-recovers when the output power drops below the rated maximum output power. Records APC event and auto-recovery event if auto-recovery successful Major No auto recovery. Requires manual reset. Input power must be decreased to < -6.6 dBm. Records input overdrive event, system disable event, each auto recovery event* Major Amplifier auto-recovers when the sensor temperature drops to < +73° C. Records over temperature event, system disable event, each auto recovery event, (Yellow LED display) Reflected Power Reverse RF output power is > +47.8 dBm for a Major duration of 1-minute No auto-recovery. Requires manual reset. Reverse Records high reflected power must be < 50% of the power event, each auto recovery event* maximum rated forward output power. High Voltage Disable the MCPA immediately if the supply DC voltage > +30.5 Vdc Major Auto-recovery when the supply voltage drops to < +30.0 Vdc Records supply DC fault event, system disable event, each auto recovery event* Low Voltage Disable the MCPA immediately if the supply DC voltage < +20.5 Vdc Major Auto-recovery when the supply voltage increases to > +24 Vdc Records low voltage event, system disable event, each auto recovery event* 4-4 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Major Alarm - Causes MCPA RF section to be disabled Amplifier Alarm Definition Amplifier Mode Minor Alarm - Does not cause MCPA RF section to be disabled Auto-Recovery Event/Fault Log Loop converges. Tries to auto recover 10 times before permanent shut down. 2 minutes and 5 seconds for each try. Records internal DC fault event, system disable event, each auto recovery event* Records internal DC fail event, system disable event, each auto recovery event* Loop Fail Loop convergence fail Internal DC Fail Minor Internal voltages fail or out (no LED of range display) Auto-recovery once the voltage is within the range. No shutdown until Linearization alarm occurs. Device Fail Minor One or more output power (no LED devices fail display) No auto-recovery. No Records device fault shutdown until Linearization event alarm occurs. Major Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 4-5 044-05117 This Page Intentionally Blank 4-6 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Chapter 5 5-1 Maintenance Introduction This chapter contains periodic maintenance and performance test procedures for the G3L-850-135 Multi-Carrier Power Amplifier (MCPA). Check your sales order and equipment warranty before attempting to service or Note repair the unit. Do not break the seals on equipment under warranty or the warranty will be null and void. Do not return equipment for warranty or repair service until proper shipping instructions are received from the factory. 5-2 Periodic Maintenance Periodic maintenance requirements and the intervals at which the tasks should be performed are listed in Table 5-1. Table 5-1. Periodic Maintenance Task Inspection: Interval Action 12 Months Inspect signal and power cables for frayed insulation. Check RF connectors to ensure that they are tight. Performance Tests 12 Months Perform annual test per paragraph 5-4. Clean Fans/Heat Sinks 3 Months Inspect for debris. Remove dust with a soft cloth/brush or vacuum cleaner. Cables and Connectors 5-3 Test Equipment Required For Test Test equipment required to test the amplifier is listed in Table 5-2. Equivalent test equipment may be substituted for any item, keeping in mind that a thermistor type power meter is required. Note All RF test equipment required must be calibrated to 0.05 dB resolutions. Any deviation from the nominal attenuation must be accounted for and factored into all output readings. Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 5-1 044-05117 Table 5-2. Test Equipment Required Nomenclature Manufactu rer Model Signal Generator Agilent 8656B 20 dB Attenuator, 250 Watt Bird 20 dB Attenuator, 20 Watt (2 each) Bird Tenuline Spectrum Analyzer Agilent 8560E Coax Directional Coupler Agilent 778D Power Meter / Sensor Agilent 437B / 8481A Arbitrary Waveform Generator Sony AWG2021 Network Analyzer Agilent 8753C * Any Equipment substitutions should have equivalent specifications. 5-4 Amplifier Performance Test Performance testing should be conducted every 12 months to ensure that the amplifier system meets the operational specifications listed in Table 5-3. Also verify system performance after any amplifier module is replaced in the field. The test equipment required to perform the testing is listed in Table 5-2, and the test setup is shown in Table 5-1. Note The frequencies used in this test are typical for an amplifier with a 25 MHz band from 869 MHz to 894 MHz. Select evenly spaced F1, F2, F3, and F4 frequencies that cover the instantaneous bandwidth of your system. To check amplifier performance, proceed as follows: WARNING Do not apply any RF signals to the amplifier input until instructed to do so. Ensure that the correct amount of attenuation is used between the amplifier RF CAUTIO connections and the test equipment to prevent overdrive of the amplifier or the test equipment. 5-4.1 Amplifier Spurious Emissions Test: 1. Connect the test equipment as shown in Figure 5-1. 2. Configure the signal source to produce four frequencies evenly spaced across the instantaneous bandwidth to be used for the amplifier under test. 3. Adjust the output of the signal source to excite the amplifier to its rated output. 4. Use the spectrum analyzer to measure the spurious emissions performance. 5. Record test data in Table 5-3. Verify that the data are within the specifications shown in Table 1-2. 6. Reduce the output of the signal source to minimum. 5-2 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 7. Switch off the Main Power Switch on the amplifier under test. 20 dB Directional Coupler 27 Vdc Power Meter HP 437B 30 dB Attn RF Out G3L-850-135 PYTHON MultiChannel Power Amplifier Gain = 63 dB Output = 135 W = +51.3 dBm 250 W High Pwr RF In +1.3 dBm* Sensor Head 8482A Power Meter HP 8648 A Signal Source 20 dB Directional Coupler 30 dB Attn Spectrum Analyzer HP 8560 E 20 W Sensor Head 8482A INPUT TEST CONFIGURATION 04-0262B-A +1.3 dBm* * Example. Ensure that sufficient attenuation is present between the amplifier output and your test equipment to avoid overdrive or damage. Refer to test equipment specifications. Figure 5-1. Amplifier Test Setup Diagram – Configuration A 5-4.2 Gain Test: 1. Disconnect: a. Spectrum analyzer b. Signal source. c. Power Meter and Sensor Head. 2. Connect the network analyzer as shown in Figure 5-2. 3. Set network analyzer as follows: a. Power output to -11 dBm max. b. Frequency start to 869 MHz. c. Frequency stop to 894 MHz. d. Normalize the network analyzer for gain and return loss. 4. Switch on the amplifier under test, and ensure that the STATUS switch is in the center position. 5. Check the amplifier gain across the band from 869 MHz to 894 MHz. Gain should be as specified in Table 1-2. Record test data in Table 5-3. Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 5-3 044-05117 27 Vdc RF Out G3L-850-135 PYTHON MultiChannel Power Amplifier Gain = 63 dB Output = 135 W = +51.3 dBm 250 W RF In 40 dB Attn HP 8753 D Network Analyzer PORT 1 PORT 2 +1.3 dBm* TEST CONFIGURATION * Example. Ensure that sufficient attenuation is present between the amplifier output and your test equipment to avoid overdrive or damage. Refer to test equipment specifications. 04-0263B-A Figure 5-2. Amplifier Test Setup – Configuration B 5-4.3 Input Return Loss: 1. Retain the test configuration shown in Figure 5-2. 2. Read and record the S11 return loss measurement on network analyzer. Record test data in Table 5-3. 3. Switch off the amplifier under test. 4. Disconnect the test equipment. 5-4 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 5-4.4 Test Data Sheet Record the amplifier’s performance test data below. MODULE S/N DATE Test Conditions: Load and Source Impedance: 50 Ohms VSWR: < 1.5:1 Supply Voltage: +27 Vdc ±0.1 Vdc Table 5-3. Amplifier Performance Data Test Specification RF Gain Min Max Data Vcc = 27 Vdc PO = See table 1-4 62.5.0 dB 63.5 dB Freq. = 869 – 894 MHz Spurious Emissions Vcc = 27 Vdc PO = See table 1-2 -62 dBc 869 – 894 MHz Band Gain Flatness Vcc = 27 Vdc PO = See table 1-2 ±0.5 dB 869 – 894 MHz Band Input Return Vcc = 27 Vdc Loss PO = See table 1-2 - 16 dB 869 – 894 MHz Band PASS FAIL Tested by Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 5-5 044-05117 5-5 Return For Service Procedures When returning products to Powerwave, the following procedures will ensure optimum response. 5-5.1 Obtaining An RMA A Return Material Authorization (RMA) number must be obtained prior to returning equipment to the factory for service. Please contact our Repair Department at (714) 466-1000 to obtain this number, or FAX your request to (714) 466-5800. Failure to obtain this RMA number may result in delays in receiving repair service. 5-5.2 Repackaging For Shipment To ensure safe shipment of the amplifier, it is recommended that the original package designed for shipping the amplifier be reused. If it is not available, contact Powerwave’s Customer Service Department for packing materials. 5-6 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Appendix A Abbreviations and Acronyms Below is a list of the abbreviations and acronyms used in the industry. Abbreviation/ Acronym Definition ACLR Adjacent Channel Leakage Power Ratio ACP Adjacent Channel Power A/D Analog-to-Digital Conversion ADC {Analog-to-Digital Converter {Automatic Data Collection AM Amplitude Modulation AMPS Advanced Mobile Phone System ANSI American National Standards Institute APC Automatic Power Control APTT Analog Push To Talk ASG Applications Support Group ASIC Application Specific Integrated Circuit ATE Automatic (Automated) Test Equipment ATP Acceptance Test Procedure ATTEN Attenuator BER Beyond Economical Repair BOM Bill Of Materials BPF Band Pass Filter BS Base Station BTS Base Transceiver Station (System) BW BandWidth °C Degrees Celsius CAD Computer Aided Design CCA {Circuit Card Assembly CCW Counter ClockWise CDMA Code Division Multiple Access CDPD Cellular Digital Packet Data CTRL Control CW {ClockWise Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier A-1 044-05117 Abbreviation/ Acronym Definition {Continuous Wave dB deciBels dBc Referenced to a carrier level dBm Reference to one milliwatt dBw Reference to one watt DIN Deutsches Insitut für Normung eV DLNA Duplexer Low Noise Amplifier DPTT Digital Push To Talk DQPSK Differential Quadrature Phase Shift Keyed DSP Digital Signal Processing DUT Device Under Test ECD Estimated Completion Date ECM Electronic Counter Measure EDGE Enhanced Data for GSM Evolution EEPROM Electrically-Erasable Programmable Read-Only Memory EIA Electronic Industries Association EMC ElectroMagnetic Compatibility EMI ElectroMagnetic Interference EPROM {Electrically Programmable Read-Only Memory {Erasable Programmable Read-Only Memory ESD ElectroStatic Discharge ESG Electronic Signal Generator ETDMA Extended Time Division Multiple Access ETSI European Telecommunications Standard Institute EUT Equipment Under Test FAR Failure Analysis Report FCC Federal Communications Commission FDMA Frequency Division Multiple Access FET Field Effect Transistor FHMA Frequency Hopping Multiple Access FM Frequency Modulation FRU Field Replaceable Unit FSK Frequency Shift Key modulation GHz Gigahertz GMSK Gaussian Minimum Shift Keying GOLAY See GSC GSC Golay Sequential Code A-2 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Abbreviation/ Acronym Definition GSM Global System for Mobile Communications HPF High Pass Filter HW Hardware Hz Hertz IAW In Accordance With IC Integrated Circuit IMD InterModulation Distortion IRL Input Return Loss IS-54 Interim Standard 54 for TDMA IS-95 Interim Standard 95 for CDMA ISDN Integrated Services Digital Network ISM Industrial, Scientific and Medical unlicensed frequency bands ISO {International Organization for Standardization {ISOlator kHz Kilohertz LDA Linear Discrete Amplifier (Class A or AB) LGL Lower Guardband Limit LMR Land Mobile Radio LMS Land Mobile Systems LNA Low Noise Amplifier LO Local Oscillator LPA Linear Power Amplifier LPF Low Pass Filter LSL Lower Specification Limit LVD Low Voltage Disconnect MC MultiChannel MCA MultiChannel Amplifier MCPA {MultiCarrier Power Amplifier {MultiChannel Power Amplifier MCR MultiChannel Rack MFRM {Multiple Frequency Radio Mobile {Multifunction Frequency Radio Modulation MHz Megahertz MSO Master Switch Office MTBF Mean Time Between Failures MTSO Master Telephone Switch Office MU Measurement Uncertainty Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier A-3 044-05117 Abbreviation/ Acronym Definition M&TE Measuring and Test Equipment NAMPS Narrow Analog Mobile Phone System NIOSH National Institute for Occupational Safety and Health NIST National Institute for Standards and Technology NMT Nordic Mobile Telephone NVM NonVolatile Memory OEM Original Equipment Manufacturer OFDM Orthogonal Frequency Division Multiplexing OMS Operational Method Sheet OOB Out Of Box O/P Output OSHA Occupational Safety and Health Administration PA Power Amplifier PAF Powerwave Amplifier Frame PAR Peak to Average Ration PCB Printed Circuit Board PCMCIA Personal Computer Memory Card International Association PCN Personal Communications Network PCS {Personal Communications Services {Personal Communication System(s) PDA Personal Digital Assistant PEP Peak Envelope Power PF PicoFarads PHS Personal Handyphone System – Japan PLC Product Life Cycle PLL Phase Locked Loop PM {Phase Modulation {Preventive Maintenance PMR Peak to Minimum Ratio PO Purchase Order PPM Parts Per Million PSC {PCS Single Channel {Product Serialization Code PSTN Public Switched Telephone Network PTI Powerwave Technologies, Inc. PTT Push To Talk PWAV PowerWAVe A-4 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Abbreviation/ Acronym Definition QA Quality Assurance QAM Quadrature Amplitude Modulation RBW Resolution BandWidth RF Radio Frequency RFI Radio Frequency Interference RFQ Request For Quotation RFS RF Solutions RFSU RF Switching Unit RGO Return Goods Order RH Relative Humidity RL Return Loss RMA {Rack-Mounted Amplifier {Return Material Authorization RMP Reliability Monitoring Plan (Procedure) RMS Root Mean Square RSS Root Sum Square Rx Receive, Receiver SCHPA Single-Channel High Power Amplifier SCPA Single Channel Power Amplifier SIM System Interface Module SMA SubMiniature Type A (coaxial connector) SMT Surface Mount Technology SN Serial Number SO System Outage SOE Sequence of Events SW SoftWare TBC To Be Confirmed TBD To Be Determined (To Be Defined) TCXO Temperature Controlled crystal Oscillator TD {Temperature Drift {Temporary Deviation TDMA Time Division Multiple Access TRU Transmit Receive Unit TRX Transceiver (Transmit / Receiver) Unit Tx Transmit, Transmitter UAI Use As Is Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier A-5 044-05117 Abbreviation/ Acronym Definition UART Universal Asynchronous Receiver Transmitter UCL Upper Control Limit UCLR Upper Control Limit for Range UGL Upper Guardband Limit UL Underwriters Laboratories UMTS Universal Mobile Telecommunications System UNL Unit Nominal Level URG Unit Reference Gain USL Upper Specification Limit UUT Unit Under Test VADJ Voltage ADJust (signal name frequently found on schematic or block diagrams) VBW Video BandWidth VCO Voltage Controlled Oscillator VFWD Voltage ForWarD (signal name frequently found on schematic or block diagrams) VREFL Voltage REFLected (signal name frequently found on schematic or block diagrams) VSWR Voltage Standing Wave Ratio VVA Voltage Variable Attenuator WCDMA Wideband Code Division Multiple Access XMT Transmit XMTR Transmitter A-6 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 Appendix 2 General Site Survey Form Name of Operator: Brand Name: Date: Info Source: Tel: Tel: Your Name: Email: BTS Sectors(S) To Be Equipped: Type / Supplier: Downlink Frequencies in use MHz to MHz. Uplink Frequencies in use MHz to MHz. Ant 0 Signals BCCH present? TRXn Ant 1 Signals BCCH sometimes present? TRXn Plans to add additional TRX during trial? Feedline Size: Length , dB Loss estimate For existing sites: BTS jumper from BTS top to feedline on tower: Shelter exit on up tower: Jumper to antenna: Overall feedline loss estimate from BTS to Antenna ____________________________dB Jumpers From power amplifier cabinet to feedline for tower required: Length , Connector Type , and Gender Location On Roof Near Antenna? On Ground? Type of raised platform? Adequate space including ½ meter min jumper bend radius at power amplifier left side? Is a structural analysis needed? Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier A2-1 044-05117 Network Link Budget RF carrier power (each TRX) at BTS top connector (in dBm)? Desired RF carrier power (each TRX) at power amplifier cabinet output connector (in dBm)? Current system uplink and downlink balance or difference? Is discontinuous transmit (DTX) feature used? Power AC Voltage available for power amplifier at site: Amps Vac; Singe Phase or Three Phase? (circle one) Main Panel or Sub Panel? (circle one) Required RF Jumpers (8x8x8 configuration) 9 pieces Type N male to Type N male, ½” Heliax jumper - BTS top to power amplifier cabinet input Length: 6 pieces 7/16 DIN male to 7/16 DIN male, ½” Heliax jumper - power amplifier cabinet output to antenna feedline Length: Other? (Type & Length) Required Cables (non-RF) AC wiring from panel to power amplifier cabinet. Length: Interconnecting alarm wire and connection. Length: Ground bus wiring and attachment. Length: Host is Responsible for • Installing power mains panel • Contractor management of cabinet mounting, installation and coax seal weatherproofing. • Location preparation: structural analysis, platform installation, building code conformance, site security Photos Required • BTS top connection • BTS front inside showing TRX unit and number of TRX • Wide view of BTS and proposed power amplifier cabinet location in same photo • Proposed power amplifier cabinet location shown with a 1 meter long ruler in view nearby A2-2 Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier 044-05117 • Existing feedline cable to antenna (where power amplifier cabinet output will connect to) • Power mains circuit breaker panel (shows adequate capacity for breakers) • Misc. pictures showing tower and site access. Installation and Service Manual - G3L-850-135 Multi-Carrier Power Amplifier A2-3 044-05117 This Page Left Blank 044-05117 Corporate Headquarters Powerwave Technologies, Inc. 1801 East St. Andrew Place Santa Ana, CA 92705 USA Tel: 714-466-1000 Fax: 714-466-5800 www.powerwave.com Main European Office Antennvägen 6 SE-187 80 Täby Sweden Tel: +46 8 540 822 00 Fax: +46 8 540 823 40 Hong Kong Office 23 F Tai Yau Building 181 Johnston Road Wanchai, Hong Kong Tel: +852 2512 6123 Fax: +852 2575 4860 ©Copyright October 2004, Powerwave Technologies, Inc. All Rights reserved. Powerwave, Powerwave Technologies, The Power in Wireless and the Powerwave logo are registered trademarks of Powerwave Technologies, Inc.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Warning : Invalid xref tableEXIF Metadata provided by EXIF.tools