Domestic Hot Water Recirculation Systems
Application, Selection & Installation Guide
Effective Date: 01/31/06
Printed in USA
Water Circulation
Pumps & Circulators
©Taco Catalog # 100-41
Supersedes: New
Use at 40%, Centered (In place of “Do it Once. Do it right” on Catalog Sheets) NOTE: Remove Hydronic Components & Systems
e-smart™ is our way of helping you quickly identify our most resource-saving products.
The Problem:
Waiting for Hot Water
It’s a common problem: turn on the faucet or shower for hot
water, then wait for it to arrive. In fact, the wait can be up to
two minutes in larger homes with multiple bathrooms and
long runs of pipe between the plumbing fixtures and the water
heater! With a Taco Domestic Hot Water Recirculation
System in place, there’s no more wait. Instant hot water!
Waiting Means Wasting
Waiting for hot water sends millions of gallons of cooled
water down the drain each year. In fact, an average family
of four wastes up to 14,000 gallons of water each year waiting
for hot water.* Water conservation is so important that
many US states and municipalities routinely impose water-
ing bans and offer rebate incentives to help conserve this
natural resource. *Source: Dept. of Energy study.
Estimated Annual Water Savings
Energy Down The Drain
Of course, all that “waiting water” contains some heat energy
(BTU’s), even if it’s only room temperature. Wasting those
Domestic Hot Water Recirculation
BTU’s and starting over with fresh, cold water to heat up
requires even more heat energy. So in addition to wasting
water, millions of BTU’s and energy dollars are wasted, too.
The Solution:
Install a Domestic Hot Water Recirculation System
The Taco Plumb n’ Plug® Recirculation System is specifically
designed for:
• Instant hot water comfort
• Water savings
• Energy savings
How a Domestic Hot Water Recirculation System Works
A standard DHW system requires a dedicated return line
from the furthest fixture back to the water heater. The re-
turn line is connected to a tee at the tank drain valve or to
the tank’s cold water supply line. A Taco Plumb n’ Plug® re-
circulation pump with an optional Integral Flow Check (IFC®)
is installed on the return line and controlled by a timer or
temperature Aquastat. The spring-loaded IFC® prevents
gravity circulation during off-cycles. The timer turns on the
pump at preset intervals, usually during peak use periods in
the early morning and late afternoon. An optional Aquastat
operates the pump to keep hot water in the line within a
set range (95°F–115°F). All supply and return lines should
be insulated for maximum energy savings.
Required Components
• Taco Plumb n’ Plug® Circulator with optional IFC®
• Isolation valves - to isolate the pump for future service
• Flow check valve - to prevent gravity flow
• Purge Valve - to remove air from system piping
• Timer control - 24-hour analog or 7-day digital timer
• Aquastat - to control temp between 95°F-115°F (opt.)
• Pipe insulation - to maximize energy savings
Features & Benefits:
Plumb n’ Plug Circulators
• Removable stainless steel cartridge - contains all moving parts
• Patented, removable Integral Flow Check (IFC®) option
• Bronze construction
• 1⁄2” & 3⁄4” sweat, 3⁄4” npt, union or flanged connections
• Pre-wired power cord
• Pre-wired 24-hour analog or 7-day programmable timer
• Durable Noryl® impeller
• Ceramic shaft, carbon bearings
• Quiet running, low power consumption
• Low maintenance, unmatched reliability
• UL Listed
Pipe
Type
Hot Water
Supply
Length (ft.)
100
150
200
250
300
100
150
200
250
300
Pipe
Water Volume
(gallons)
Daily Water
Volume Wasted
(gallons)*
12
18
24
30
36
25
37
50
62
75
Annual Water
Volume Saved
(gallons)
4,400
6,600
8,800
11,000
13,200
9,200
13,700
18,300
23,000
27,500
* Assume average of 10 cycles per day.
1/2” Copper
Type “L”
1.2
per 100’
3/4” Copper
Type “L”
2.5
per 100’
Noryl® is a registered trademark of General Electric Company.
1.
Typical Installation & Piping
One-Story with 1 Water Heater One-Story with 2 Water Heaters
Multi-Story with 1 Water Heater Multi-Story with 2 Water Heaters
Recirculation Piping with Storage
Water Heater & Mixing Valve
Indirect
Water
Heater
Boiler
Cold Water Supply
Hot Water
Supply
TubShowerSink
Dish
Washer
Clothes
Washer
Hot
Water
Return
TACO Plumb N’ Plug
Circulator
Recirculation Piping
with Indirect Water Heater
2.
Standard Models
Submittal Data Information
HP
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/40
1/25
1/25
Voltage
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
Amps
0.43
0.43
0.43
0.43
0.52
0.52
0.52
0.52
0.84
0.84
24 Hr Analog
Timer
003-BC4-PNP
003-B4-PNP
003-BT4-PNP
003-BC4-1PNP
006-BC4-PNP
006-B4-PNP
006-BT4-PNP
006-BC4-1PNP
---
---
---
---
7 Day Digital
Timer
003-BC4-8PNP
003-B4-2PNP
003-BT4-2PNP
003-BC4-9PNP
006-BC4-4PNP
006-B4-2PNP
006-BT4-2PNP
006-BC4-5PNP
Line Cord
Only
003-BC4-4PNP
003-B4-1PNP
003-BT4-1PNP
003-BC4-5PNP
006-BC4-2PNP
006-B4-1PNP
006-BT4-3PNP
006-BC4-3PNP
---
---
Standard
Model #
003-BC4
003-B4
003-BT4
003-BC4-1
006-BC4
006-B4
006-BT4
006-BC4-1
008-BC6
008-BF6
System
Connection
1/2” Sweat
3/4” Sweat
3/4” NPT
Union
1/2” Sweat
3/4” Sweat
3/4” NPT
Union
3/4” Sweat
Flanged
Plumb n’ Plug® (PNP) Pre-Wired Models
Integral Flow Check (IFC) Models
HP Voltage
Amps
24 Hr Analog
Timer
--- ---
--- ---
7 Day Digital
Timer
Line Cord
Only
Standard
Model #
System
Connection
Plumb n’ Plug® (PNP) Pre-Wired Models
1/40
1/40
1/40
1/40
1/40
1/40
1/25
1/25
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
115/60/1
0.43
0.43
0.43
0.52
0.52
0.52
0.84
0.84
003-BC4-3PNP
003-BC4-2PNP
003-B4-3PNP
006-BC7-1PNP
006-BC7-PNP
006-B7-PNP
003-BC4-11PNP
003-BC4-10PNP
003-B4-4PNP
006-BC7-5PNP
006-BC7-4PNP
006-B7-1PNP
003-BC4-7PNP
003-BC4-6PNP
---
006-BC7-3PNP
006-BC7-2PNP
---
---
---
003-BC4-IIFC
003-BC4-IFC
003-B4-2IFC
006-BC7-1IFC
006-BC7-IFC
006-B7-IFC
008-BC6-IFC
008-BF6-IFC
1/2” Sweat
3/4” Sweat
Union
1/2” Sweat
3/4” Sweat
Union
3/4” Sweat
Flanged
Domestic Hot Water Circulator Accessories
Unions
Half Unions
Shut-Off Unions
System
Connection
1/2”
3/4”
1/2”
3/4”
Sweat
110-558
110-559
258-3
258-4
NPT
110-556
110-557
258-1
258-2
Freedom
Flange
Shut-Off
Bronze
System
Connection
1/2”
3/4”
1/2”
3/4”
Sweat
242-2
243-2
110-522BSF
110-523BSF
NPT
242-1
243-1
---
110-251BF
Plumb n’ Plug
Accesories
Analog Timer Kit
Digital Timer Kit
Aquastat
Model #
265-1
265-3
563-2
Half
Unions
Shut-off
Unions
Freedom Flange
265-1
Analog
Timer 265-3
Digital
Timer
Shut-off Freedom Flange
563-2
Aquastat
3.
Choosing the Correct
Circulator for the Job
Pump Selection Charts
This information is provided as a guide only. Larger models are available. For larger systems, consult your local Taco representative.
Find the table below that best describes the design you plan to use. Select the pump model based on the supply and return pipe length,
size and pump options. Do not oversize the pump or high velocity noise and erosion corrosion of system piping may result.
Model #
003
006
008
003-IFC*
006-IFC*
008-IFC*
Supply Pipe
Maximum Length (ft.)
50
150
275
50
125
250
Total Maximum Pipe
Length (ft.)
100
300
550
100
250
500
* With Integral Flow Check
1/2" Supply & 1/2" Return Lines
003
006
008
003-IFC*
006-IFC*
008-IFC*
350
900
1,450
350
750
1,350
700
1,800
2,900
700
1,500
2,700
* With Integral Flow Check
Model # Supply Pipe
Maximum Length (ft.)
Total Maximum Pipe
Length (ft.)
3/4" Supply & 3/4" Return Lines
Model #
003
006
008
003-IFC*
006-IFC*
008-IFC*
Supply Pipe
Maximum Length (ft.)
100
275
450
100
275
425
Total Maximum Pipe
Length (ft.)
200
550
900
200
550
850
* With Integral Flow Check
3/4" Supply & 1/2" Return Lines
Model #
003
006
008
003-IFC*
006-IFC*
008-IFC*
Supply Pipe
Maximum Length (ft.)
125
325
525
130
275
500
Total Maximum Pipe
Length (ft.)
250
650
1,050
260
550
1,000
* With Integral Flow Check
1" Supply & 1/2" Return Lines
1/2" Supply & 1/2" Return Lines 3/4" Supply & 3/4" Return Lines
3/4" Supply & 1/2" Return Lines 1" Supply & 1/2" Return Lines
Assumptions:
Flow = 1 GPM
Max. Velocity = 3 ft./sec.
Allowances have been added for pressure drop
of other typical system components
Type L Copper Tubing
Supply & Return Piping are equal in length
1" Supply & 3/4" Return Lines
Performance Field Information - 60 Hz
Model #
003
006
003-IFC*
006-IFC*
Supply Pipe
Maximum Length (ft.)
600
1,500
1,200
2,500
Total Maximum Pipe
Length (ft.)
1,200
3,000
1,200
2,500
* With Integral Flow Check
1" Supply & 3/4" Return Lines
DOMESTIC WATER RECIRCULATION MODELS (STD)
FLOW - M 3/H
FLOW - GPM
TOTAL HEAD — FEET
TOTAL HEAD — METERS
TOTAL HEAD — FEET
TOTAL HEAD — METERS
FLOW - M 3/H
0.0
20
18
16
14
12
10
8
6
4
2
0
20
18
16
14
12
10
8
6
4
2
0
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
1.00.5 1.5 2.0 2.5 3.0 3.5 4.0 4.5
0 42 6 8 10 12 14 16 18 20
FLOW - GPM
0 42 6 8 10 12 14 16 18 20
0.0 1.00.5 1.5 2.0 2.5 3.0 3.5 4.0 4.5
DOMESTIC WATER RECIRCULATION MODELS (IFC)
003
006
008
003-IFC
006-IFC
008-IFC
1
2
3
1
2
3
1
2
3
1
2
3
4.
"On-Demand" Systems
for New or Retrofit Installations
Using the existing cold water line as the return line,
the D’MAND® System is ideal for both new and retrofit
installations. Typically installed at the furthest fixture from
the water heater, D’MAND® fits out of the way, under any
bathroom vanity. Connections are made from the hot and
cold lines to the suction and discharge side of the pump
using adapter tees and stainless flex lines provided. When
hot water is needed, the pump is activated by pressing a
starter button, runs only long enough to supply hot water
to the fixture and then automatically stops. This prevents
hot water from entering the cold line. A spring-loaded
Integral Flow-Check valve (IFC®) prevents cold water from
entering the hot line. Optional wireless RF or motion
sensor starters are also available.
Domestic Hot Water Recirculation
Ideal for Tankless Water Heaters
Features and Benefits of the Taco D’MAND® System
• Instant Hot Water Comfort
• Maximum Water & Energy Savings
• 24 Hour "On-Demand" operation
• Maintenance free circulator - unmatched reliability
• Removable stainless steel cartridge - contains all moving parts
• UL, IAPMO listed
• Patented D’MAND® electronics control board
• Integral Flow-Check (IFC
®
) to prevent thermo-siphoning or gravity flow
• Pre-wired power cord and integral temperature sensor
• Adapter tees & stainless steel flex lines included
• RF wireless remote or motion sensor starter-optional
Tank Type
Water
Heater
Water
Heater
Tank
Tankless
Water
Heater
Tankless
Water
Heater
CITY WATER SUPPLY COLD WATER LINE
CITY WATER SUPPLY COLD WATER LINE
HOT WATER LINE
HOT WATER LINE
RETURN LINE
Remote
Activation
Remote
Activation
Remote
Activation
Remote
Activation
Hot
Water
Supply
Valve
Cold
Water
Supply
Valve
Hot
Water
Supply
Valve
Cold
Water
Supply
Valve
Remote
Activation
Motion Sensor or
Starter Button
Activation
Motion Sensor or
Starter Button
Activation
D’MAND
®
System
Electronic
Controls
Heat
Sensor
Remote
Receiver
D’MAND
®
System
Electronic
Controls
Heat
Sensor Remote
Receiver
Hot
Water
Supply
Valve
Cold
Water
Supply
Valve
5.
Model
554-1
554-2
554-3
554-4 Motion Sensor Kit
D‘Mand System Accessories
Description
RF Remote Transmitter/Reciever Kit
RF Individual Remote Transmitter Button
Hardwired Individual Starter Button Round
D'MAND® System Accessories
Sizing Your D'MAND
®
System
Size of Home
Small
Medium
Large/Commerical
Total length of
Pipe (ft)
50
100
Over100
Tank Type Water Heater
Model
006-DM-PK
008-DM-PK
0011-DM-PK
Tank Type Water Heater
Size of Home
Small / Medium
Large/Commerical
Total length of
Pipe (ft)
<60
60+
Tankless Water Heater
Model
008-DM-PK
0011-DM-PK
Tankless Water Heater
Standard Piping:
Recirculation Piping:
Size of Home
Small
Medium
Large/Commerical
Total Length
of Pipe (ft.)
100
200
200 +
Re-Circ Tank Type Water Heater
Model
006-DM
008-DM
0011-DM
Performance Field Information - 60 Hz
FLOW-GPM
0 1 2 3 4 5 6 7 8 9 10
TEEF-DAEH LATOT
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
FLOW-M3/ H
0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25
SRETEM-DAEH LATOT
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
006-DM-PK
008-DM-PK
0011-DM-PK
1
2
3
1
3
D’MAND SYSTEM MODELS
2
Tank Type Water Heater
Size of Home
Small / Medium
Large/Commerical
Sq. Ft.
<2500
2500+
ReCirc Tankless Water Heater
Model
008-DM
0011-DM
Tankless Water Heater
RF Wireless
Starter Kit
Motion
Sensor
6.
Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com