7kW

®

7kW

CorePower™ System

Residential Standby Generators
Air-Cooled Gas Engine
1 of 5

Power Rating
Model 005837-0 (Composite Polymer) - 7 kW 60Hz

INCLUDES:
• Digital LED Controller
• Automatic Transfer Switch
with Built-In Priority Load Center
• Composite All Weather Enclosure
• Sound Attenuated Enclosure
• External Main Circuit Breaker
• Flexible Fuel Line Connector
• Composite Mounting Pad
• Natural Gas or LP Gas Operation
• 2 Year Limited Warranty
• UL 2200 Listed

FEATURES
¡	
INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of
GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it
doesn’t stop there. Total commitment to component testing, reliability
testing, environmental testing, destruction and life testing, plus testing
to applicable CSA, NEMA, EGSA, and other standards, allows you to
choose GENERAC POWER SYSTEMS with the confidence that these
systems will provide superior performance.
¡

 OREPOWER™: Offers an extreme value for those who desire automatic
C
backup power at the most affordable price.

¡

TEST CRITERIA:
 PROTOTYPE TESTED

 NEMA MG1-22 EVALUATION

 SYSTEM TORSIONAL TESTED

 MOTOR STARTING ABILITY

¡	
SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION.
This state-of-the-art power maximizing regulation system is standard on
all Generac models. It provides optimized FAST RESPONSE to changing
load conditions and MAXIMUM MOTOR STARTING CAPABILITY by
electronically torque-matching the surge loads to the engine.

¡	
SINGLE SOURCE SERVICE RESPONSE from Generac’s dealer network
provides parts and service know-how for the entire unit, from the engine
to the smallest electronic component.

¡	
G ENERAC TRANSFER SWITCHES. Long life and reliability are
synonymous with GENERAC POWER SYSTEMS. One reason for this
confidence is that the GENERAC product line includes its own transfer
systems and controls for total system compatibility.

7kW

®

CorePower™ System - 7 kW

features and benefits

Engine

2 of 5

•Generac OHV engine

A durable, reliable powertrain for maximum power output.

•Cast iron cylinder walls

Rigid construction and added durability provide long engine life.

•Electronic ignition/spark advance

These features combine to assure smooth, quick starting every time.

•Pressurized filtration system

Better performance, less maintenance and significantly longer engine life.

•Low oil pressure shutdown system

Superior shutdown protection prevents catastrophic engine damage due to low oil.

•High temperature shutdown

Prevents damage due to overheating.

•Spin-on automotive type oil filter

Captures and collects harmful impurities with easy serviceability.

Generator
•Revolving field

Allows for a smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.

•Displaced phase excitation

Maximizes motor starting capability.

•Automatic voltage regulation

Regulates the output voltage to ±5% prevents damaging voltage spikes.

•UL 2200 Listed

For your safety.

Transfer Switch
•Fully Automatic

Transfers your vital electrical loads to the energized source of power.

•Remote Mounting

Mounts near your existing distribution panel for simple, low cost installation.

•Flush mountable

Can be installed between studs like a standard electrical panel.

•UL Listed

For your safety.

Controls
•Auto/Off/Manual switch

Selects the operating mode.

•Utility voltage sensing

Constantly monitors utility voltage, setpoints 60% dropout, 80% pick-up, of standard voltage.

•Utility interrupt delay

Prevents nuisance start-ups of the engine, adjustable 10-30 seconds.

•Engine warm-up

Ensures engine is ready to assume the load, setpoint approximately 5 seconds.

•Engine cool-down

Allows engine to cool prior to shutdown, setpoint approximately 1 minute.

•Seven day exerciser

Operates engine to prevent oil seal drying and damage between power outages.

•Timed Trickle Battery charger

Maintains battery charge level to ensure starting.

•Main Line Circuit Breaker

Protects generator from overload.

Unit
•Weather protective enclosure

Ensures protection against mother nature. Tool-less removal of roof and sides.
Three lift-out panels for easy access to all routine maintenance items. Composite polymer enclosure will not rust
and is ideal for harsh and coastal installations.

•Enclosed critical grade muffler

Quiet, critical grade muffler is mounted inside the unit to prevent injuries.

•Small, compact, attractive

Makes for an easy, eye appealing installation.

•SAE

Sound attenuated enclosure ensures quiet operation.

Installation System
•1’ Flexible Fuel Line Connector

Easy Installation.

specifications

CorePower™ System - 7 kW

7kW

®

Generator
Model

005837-0

Rated Maximum Continuous Power Capacity (LP)
Rated Maximum Continuous Power Capacity (NG)
Rated Voltage
Rated Maximum Continuous Load Current – 240 Volts
Main Line Circuit Breaker
Phase
Number of Rotor Poles
Rated AC Frequency
Power Factor
Battery Requirement (not included)
Unit Weight (Pounds/Kilos)
Dimensions (L x W x H) inches [mm]
Sound output in dB(A) at 23 ft. with generator operating at normal load

7,000 Watts*
6,000 Watts*
240
29.1 / 25
30 Amp
1
2
60Hz
1
Group 26R 12 Volts and
350 Cold-cranking Amperes Minimum
250/113.4
24.4 x 30.2 x 33 [618.5 x 767.5 x 837]
67

Engine
Type of Engine
Number of Cylinders
Displacement
Cylinder Block
Valve Arrangement
Ignition System
Governor System
Starter
Oil Capacity Including Filter
Operating RPM
Fuel Consumption
Natural Gas

Liquid Propane

cu.ft./hr.
1/2 Load
Full Load
ft3/hr (gal/hr)
1/2 Load
Full Load

GENERAC OHV
1
432cc
Aluminum w/Cast Iron Sleeve
Overhead Valve
Solid-state w/Magneto
Mechanical
12 Vdc
Approx. 1.1 Qts./1.0L
3,600

83 (2.4)
146 (4.1)
37.1 (1.02)
47.6 (1.31)

Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG)

Controls
Digital LED Indicators
Mode Switch
-Auto
-Off
-Manual/Test (start)
Engine Start Sequence
Engine Warm-up
Engine Cool-Down
Starter Lock-out
2.5 Amp Timed Trickle Battery Charger
Automatic Voltage Regulator w/Overvoltage Protection
Automatic Low Oil Pressure Shutdown
Overspeed Shutdown
High Temperature Shutdown
Overcrank Protection
Safety Fuse

Simple user interface for ease of operation
Automatic Start on Utility failure. 7 day exerciser
Stops unit. Power is removed. Control and charger still operate.
Start with starter control, unit stays on. If utility fails, transfer to load takes place,
Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
5 seconds
1 minute
Starter cannot re-engage until 5 sec. after engine has stopped.
Standard
Standard
Standard
Standard, 72Hz
Standard
Standard
Standard

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F). Sound output ratings from certain points on the generator
subject to change based on installation parameters.

3 of 5

7kW

®

Transfer Switch Features
4 of 5

transfer switch

CorePower™ System - 7 kW

• Electrically operated, mechanically-held
contacts for fast, positive connections.
• Rated for all classes of load, 100%
equipment rated, both inductive and
resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• NEMA 1 (indoor rated) enclosure is standard.
• Flush mountable

Model

005837-0

No. of Poles
Current Rating (amps)
Voltage Rating (VAC)
Utility Voltage Monitor (fixed) (Function of Digital LED
Controller)
-Pick-up
-Dropout
Return to Utility (Function of Digital LED Controller)
Exerciser weekly for 12 minutes (Function of Digital LED
Controller)
UL Listed
Total of Pre-wired Circuits
No. 15A 120V
No. 20A 120V
No. 20A 240V
No. 30A 240V
No. 40A 240V
No. 50A 240V
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts

2
50
250
80%
60%
approx. 15 sec.
Standard
Standard
8
5
1
1
-

10,000
25/11.3

Weight (Pounds/Kilos)

W2

Dimensions

Mechanical Dimensions (in inches/mm)
Height
Width
Current
No. of
Rating
Poles
H1
H2
W1
W2
50 UL Listed
2
18.5 in
23 in
10.5 in 15.38 in
470 mm 584 mm 267 mm 391 mm
Terminal Wire Ranges
ATS Rated Amps
Switch Terminal
50A 2-Pole UL
1 x 1/0-12

Depth

®

3.4 in
86 mm

H2
H1

Neutral Lug/Stud
1 x 3/8-16 Stud

Ground Lug
1 x 2/0-14
D
W1

available accessories

CorePower™ System - 7 kW

Model #

Product

Discription

5819

26R Wet Cell Battery

Every standby generator requires a battery to start the system. Generac offers the
recommended 26R wet cell battery for use with all air-cooled standby product.

5865

Cold Weather Kit

The CorePower cold weather kit is recommended for CorePower units installed in
regions where the temperature regularly falls below 32° F.

6003

Scheduled Maintenance Kit

Generac's scheduled maintenance kits provide all the hardware necessary to
perform complete routine maintenance on a Generac automatic standby generator.

dimensions
Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Generac dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.

837
[32.95]

®

618.5
[24.35]

FRONT VIEW

®

76.2 [3.0]
PEA GRAVEL
MINIMUM

767.5
[30.22]

RIGHT SIDE VIEW

Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2012 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186720SBY-J Printed in U.S.A. 10/26/12

7kW

®

5 of 5



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Encryption                      : Standard V4.4 (128-bit)
User Access                     : Print, Modify, Copy, Annotate, Fill forms, Extract, Print high-res
Create Date                     : 2012:11:06 13:24:36-06:00
Creator                         : Adobe InDesign CS6 (Windows)
Modify Date                     : 2013:01:08 10:24:21-06:00
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Instance ID                     : uuid:144eb0d2-23b5-4b58-8315-250bc8327c0f
Original Document ID            : adobe:docid:indd:d32fe439-0e78-11de-8989-9b78f80736fb
Document ID                     : xmp.id:E5816B5D4728E211B6F5D816E9DA4124
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:48F802FEAE1FE211AC86B8F03CEADD5D
Derived From Document ID        : xmp.did:55E9ADCE811FE211AA85B628F0D3E470
Derived From Original Document ID: adobe:docid:indd:d32fe439-0e78-11de-8989-9b78f80736fb
Derived From Rendition Class    : default
History Action                  : converted
History Parameters              : from application/x-indesign to application/pdf
History Software Agent          : Adobe InDesign CS6 (Windows)
History Changed                 : /
History When                    : 2012:11:06 13:24:36-06:00
Metadata Date                   : 2013:01:08 10:24:21-06:00
Creator Tool                    : Adobe InDesign CS6 (Windows)
Format                          : application/pdf
Producer                        : Adobe PDF Library 10.0.1
Trapped                         : False
Page Count                      : 5
EXIF Metadata provided by EXIF.tools

Navigation menu