18290 2 Franklin Electric Submersible Motor User Guide M1311_60_Hz_AIM_Catalog Manual
18184 2 Franklin Electric Submersible Motor Control User Guide 18184_2_Franklin Electric Submersible Motor Control User Guide 18184_2_Franklin Electric Submersible Motor Control User Guide pdf pumpproducts
User Manual: Pump 18290 2 Franklin Electric Submersible Motor User Guide
Open the PDF directly: View PDF .
Page Count: 80
Download | |
Open PDF In Browser | View PDF |
SUBMERSIBLE MOTORS !PPLICATION s )NSTALLATION s -AINTENANCE FRANKLIN ELECTRIC 2011 AIM MANUAL (Z 3INGLE 0HASE AND 4HREE 0HASE -OTORS ATTENTION! IMPORTANT INFORMATION FOR INSTALLERS OF THIS EQUIPMENT! THIS EQUIPMENT IS INTENDED FOR INSTALLATION BY TECHNICALLY QUALIFIED PERSONNEL. FAILURE TO INSTALL IT IN COMPLIANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES, AND WITHIN FRANKLIN ELECTRIC RECOMMENDATIONS, MAY RESULT IN ELECTRICAL SHOCK OR FIRE HAZARD, UNSATISFACTORY PERFORMANCE, AND EQUIPMENT FAILURE. FRANKLIN INSTALLATION INFORMATION IS AVAILABLE FROM PUMP MANUFACTURERS AND DISTRIBUTORS, AND DIRECTLY FROM FRANKLIN ELECTRIC. CALL FRANKLIN TOLL FREE 800-348-2420 FOR INFORMATION. WARNING SERIOUS OR FATAL ELECTRICAL SHOCK MAY RESULT FROM FAILURE TO CONNECT THE MOTOR, CONTROL ENCLOSURES, METAL PLUMBING, AND ALL OTHER METAL NEAR THE MOTOR OR CABLE, TO THE POWER SUPPLY GROUND TERMINAL USING WIRE NO SMALLER THAN MOTOR CABLE WIRES. TO REDUCE RISK OF ELECTRICAL SHOCK, DISCONNECT POWER BEFORE WORKING ON OR AROUND THE WATER SYSTEM. DO NOT USE MOTOR IN SWIMMING AREAS. ATTENTION! INFORMATIONS IMPORTANTES POUR L’INSTALLATEUR DE CET EQUIPEMENT. CET EQUIPEMENT DOIT ETRE INTALLE PAR UN TECHNICIEN QUALIFIE. SI L’INSTALLATION N’EST PAS CONFORME AUX LOIS NATIONALES OU LOCALES AINSI QU’AUX RECOMMANDATIONS DE FRANKLIN ELECTRIC, UN CHOC ELECTRIQUE, LE FEU, UNE PERFORMANCE NON ACCEPTABLE, VOIRE MEME LE NON-FONCTIONNEMENT PEUVENT SURVENIR. UN GUIDE D’INSTALLATION DE FRANKLIN ELECTRIC EST DISPONIBLE CHEZ LES MANUFACTURIERS DE POMPES, LES DISTRIBUTEURS, OU DIRECTEMENT CHEZ FRANKLIN. POUR DE PLUS AMPLES RENSEIGNEMENTS, APPELEZ SANS FRAIS LE 800-348-2420. AVERTISSEMENT UN CHOC ELECTRIQUE SERIEUX OU MEME MORTEL EST POSSIBLE, SI L’ON NEGLIGE DE CONNECTER LE MOTEUR, LA PLOMBERIE METALLIQUE, BOITES DE CONTROLE ET TOUT METAL PROCHE DU MOTEUR A UN CABLE ALLANT VERS UNE ALIMENTATION D’ENERGIE AVEC BORNE DE MISE A LA TERRE UTILISANT AU MOINS LE MEME CALIBRE QUE LES FILS DU MOTEUR. POUR REDUIRE LE RISQUE DE CHOC ELECTRIQUE. COUPER LE COURANT AVANT DE TRAVAILLER PRES OU SUR LE SYSTEM D’EAU. NE PAS UTILISER CE MOTEUR DANS UNE ZONE DE BAIGNADE. ATENCION! INFORMACION PARA EL INSTALADOR DE ESTE EQUIPO. PARA LA INSTALACION DE ESTE EQUIPO, SE REQUIERE DE PERSONAL TECNICO CALIFICADO. EL NO CUMPLIR CON LAS NORMAS ELECTRICAS NACIONALES Y LOCALES, ASI COMO CON LAS RECOMENDACIONES DE FRANKLIN ELECTRIC DURANTE SU INSTALACION, PUEDE OCASIONAR, UN CHOQUE ELECTRICO, PELIGRO DE UN INCENDIO, OPERACION DEFECTUOSA E INCLUSO LA DESCOMPOSTURA DEL EQUIPO. LOS MANUALES DE INSTALACION Y PUESTA EN MARCHA DE LOS EQUIPOS, ESTAN DISPONIBLES CON LOS DISTRIBUIDORES, FABRICANTES DE BOMBAS O DIRECTAMENTE CON FRANKLIN ELECTRIC. PUEDE LLAMAR GRATUITAMENTE PARA MAYOR INFORMACION AL TELEFONO 800-348-2420. ADVERTENCIA PUEDE OCURRIR UN CHOQUE ELECTRICO, SERIO O FATAL DEBIDO A UNA ERRONEA CONECCION DEL MOTOR, DE LOS TABLEROS ELECTRICOS, DE LA TUBERIA, DE CUALQUIER OTRA PARTE METALICA QUE ESTA CERCA DEL MOTOR O POR NO UTILIZAR UN CABLE PARA TIERRA DE CALIBRE IGUAL O MAYOR AL DE LA ALIMENTACION. PARA REDUCIR EL RIESGO DE CHOQUE ELECTRIC, DESCONECTAR LA ALIMENTACION ELECTRICA ANTES DE INICIAR A TRABAJAR EN EL SISTEMA HIDRAULICO. NO UTILIZAR ESTE MOTOR EN ALBERCAS O AREAS EN DONDE SE PRACTIQUE NATACION. Commitment to Quality Franklin Electric is committed to provide customers with defect free products through our program of continuous improvement. Quality shall, in every case, take precedence over quantity. 35"-%23)",% -/4/23 (Z 3INGLE 0HASE AND 4HREE 0HASE !PPLICATION s )NSTALLATION s -AINTENANCE -ANUAL The submersible motor is a reliable, efficient and troublefree means of powering a pump. Its needs for a long operational life are simple. They are: 1. A suitable operating environment 2. An adequate supply of electricity 3. An adequate flow of cooling water over the motor 4. An appropriate pump load All considerations of application, installation, and maintenance of submersible motors relating to these four areas are presented in this manual. Franklin Electric’s web page, www.franklin-electric.com, should be checked for the latest updates. Contents Application !LL -OTORS Storage ................................................................................ 3 Frequency of Starts ............................................................. 3 Mounting Position ................................................................ 3 Transformer Capacity ........................................................... 4 Effects of Torque .................................................................. 4 Use of Engine Driven Generators ........................................ 5 Use of Check Valves ............................................................ 5 Well Diameters, Casing, Top Feeding, Screens ................... 6 Water Temperature and Flow ............................................... 6 Flow Inducer Sleeve ............................................................ 6 Head Loss Past Motor ......................................................... 7 Hot Water Applications ..................................................... 7-8 Drawdown Seals .................................................................. 9 Grounding Control Boxes and Panels .................................. 9 Grounding Surge Arrestors .................................................. 9 Control Box and Panel Environment .................................... 9 Equipment Grounding .......................................................... 9 3INGLE 0HASE -OTORS 3-Wire Control Boxes ......................................................... 10 2-Wire Motor Solid State Controls ..................................... 10 QD Relays (Solid State) ..................................................... 10 Cable Selection 2-Wire or 3-Wire ...................................... 11 Two Different Cable Sizes .................................................. 12 Single-Phase Motor Specifications .................................... 13 Single-Phase Motor Fuse Sizing ....................................... 14 Auxiliary Running Capacitors............................................. 15 Buck-Boost Transformers ................................................... 15 4HREE 0HASE -OTORS Cable Selection - 60 °C Three-Wire.............................. 16-17 Cable Selection - 60 °C Six-Wire ....................................... 18 Cable Selection - 75 °C Three-Wire.............................. 19-20 Cable Selection - 75 °C Six-Wire ....................................... 21 Three-Phase Motor Specifications................................ 22-28 Overload Protection ...................................................... 29-31 Submersible Pump Installation Checklist (No. 3656) Submersible Motor Installation Record (No. 2207) Submersible Booster Installation Record (No. 3655) SubMonitor ........................................................................ 32 Power Factor Correction .................................................... 32 Three-Phase Starter Diagrams .......................................... 33 Three-Phase Power Unbalance ......................................... 34 Rotation and Current Unbalance ....................................... 34 Three-Phase Motor Lead Identification.............................. 35 Phase Converters .............................................................. 35 Reduced Voltage Starters .................................................. 36 Inline Booster Pump Systems....................................... 36-39 Variable Speed Operation ............................................. 40-41 )NSTALLATION !LL -OTORS Submersible Motors - Dimensions ..................................... 42 Tightening Lead Connector Jam Nut ................................. 43 Pump to Motor Coupling .................................................... 43 Pump to Motor Assembly ................................................... 43 Shaft Height and Free End Play ........................................ 43 Submersible Leads and Cables ......................................... 43 -AINTENANCE !LL -OTORS System Troubleshooting ................................................ 44-45 Preliminary Tests................................................................ 46 Insulation Resistance......................................................... 47 Resistance of Drop Cable .................................................. 47 3INGLE 0HASE -OTORS AND #ONTROLS Identification of Cables ...................................................... 48 Single-Phase Control Boxes .............................................. 48 Ohmmeter Tests................................................................. 49 QD Control Box Parts ........................................................ 50 Integral hp Control Box Parts ........................................ 51-52 Control Box Wiring Diagrams ........................................ 53-57 %LECTRONIC 0RODUCTS Pumptec-Plus Troubleshooting During Installation ............ 58 Pumptec-Plus Troubleshooting After Installation ............... 59 QD Pumptec and Pumptec Troubleshooting ...................... 60 SubDrive/MonoDrive Troubleshooting........................... 61-62 SubMonitor Troubleshooting .............................................. 63 Subtrol-Plus Troubleshooting ........................................ 64-65 !00,)#!4)/. !LL -OTORS 3TORAGE Franklin Electric submersible motors are a waterlubricated design. The fill solution consists of a mixture of deionized water and Propylene Glycol (a non-toxic antifreeze). The solution will prevent damage from freezing in temperatures to -40 °F (-40 °C); motors should be stored in areas that do not go below this temperature. The solution will partially freeze below 27 °F (-3 °C), but no damage occurs. Repeated freezing and thawing should be avoided to prevent possible loss of fill solution. There may be an interchange of fill solution with well water during operation. Care must be taken with motors removed from wells during freezing conditions to prevent damage. When the storage temperature does not exceed 100 °F (37 °C), storage time should be limited to two years. Where temperatures reach 100° to 130 °F, storage time should be limited to one year. Loss of a few drops of liquid will not damage the motor as an excess amount is provided, and the filter check valve will allow lost liquid to be replaced by filtered well water upon installation. If there is reason to believe there has been a considerable amount of leakage, consult the factory for checking procedures. &REQUENCY OF 3TARTS The average number of starts per day over a period of months or years influences the life of a submersible pumping system. Excessive cycling affects the life of control components such as pressure switches, starters, relays and capacitors. Rapid cycling can also cause motor spline damage, bearing damage, and motor overheating. All these conditions can lead to reduced motor life. The pump size, tank size and other controls should be selected to keep the starts per day as low as practical for longest life. The maximum number of starts per 24-hour period is shown in table 3. Motors should run a minimum of one minute to dissipate heat build up from starting current. Six inch and larger motors should have a minimum of 15 minutes between starts or starting attempts. Table 3 Number of Starts MOTOR RATING MAXIMUM STARTS PER 24 HR PERIOD HP KW SINGLE-PHASE THREE-PHASE Up to 0.75 Up to 0.55 300 300 1 thru 5.5 0.75 thru 4 100 300 7.5 thru 30 5.5 thru 22 50 100* 40 and over 30 and over - 100 * Keeping starts per day within the recommended numbers provides the best system life. However, when used with a properly configured Reduced Voltage Starter (RVS) or Variable Frequency Drive (VFD), 7.5 thru 30 hp three-phase motors can be started up to 200 times per 24 hour period. -OUNTING 0OSITION Franklin submersible motors are designed primarily for operation in the vertical, shaft-up position. During acceleration, the pump thrust increases as its output head increases. In cases where the pump head stays below its normal operating range during startup and full speed condition, the pump may create upward thrust. This creates upward thrust on the motor upthrust bearing. This is an acceptable operation for short periods at each start, but running continuously with upthrust will cause excessive wear on the upthrust bearing. With certain additional restrictions as listed in this section and the Inline Booster Pump Systems sections of this manual, motors are also suitable for operation in positions 3 from shaft-up to shaft-horizontal. As the mounting position becomes further from vertical and closer to horizontal, the probability of shortened thrust bearing life increases. For normal motor life expectancy with motor positions other than shaft-up, follow these recommendations: 1. Minimize the frequency of starts, preferably to fewer than 10 per 24-hour period. Six and eight inch motors should have a minimum of 20 minutes between starts or starting attempts 2. Do not use in systems which can run even for short periods at full speed without thrust toward the motor. !00,)#!4)/. !LL -OTORS 4RANSFORMER #APACITY 3INGLE 0HASE OR 4HREE 0HASE Distribution transformers must be adequately sized to satisfy the kVA requirements of the submersible motor. When transformers are too small to supply the load, there is a reduction in voltage to the motor. Table 4 references the motor horsepower rating, singlephase and three-phase, total effective kVA required, and the smallest transformer required for open or closed three-phase systems. Open systems require larger transformers since only two transformers are used. Other loads would add directly to the kVA sizing requirements of the transformer bank. Table 4 Transformer Capacity MOTOR RATING HP SMALLEST KVA RATING-EACH TRANSFORMER TOTAL EFFECTIVE KVA REQUIRED KW OPEN WYE OR DELTA 2- TRANSFORMERS CLOSED WYE OR DELTA 3- TRANSFORMERS 1.5 1.1 3 2 1 2 1.5 4 2 1.5 3 2.2 5 3 2 5 3.7 7.5 5 3 7.5 5.5 10 7.5 5 10 7.5 15 10 5 7.5 15 11 20 15 20 15 25 15 10 25 18.5 30 20 10 30 22 40 25 15 40 30 50 30 20 50 37 60 35 20 60 45 75 40 25 75 55 90 50 30 100 75 120 65 40 125 93 150 85 50 175 100 60 150 110 175 130 200 115 70 200 150 230 130 75 NOTE: Standard kVA ratings are shown. If power company experience and practice allows transformer loading higher than standard, higher loading values may be used to meet total effective kVA required, provided correct voltage and balance is maintained. %FFECTS OF 4ORQUE During starting of a submersible pump, the torque developed by the motor must be supported through the pump, delivery pipe or other supports. Most pumps rotate in the direction which causes unscrewing torque on right-handed threaded pipe or pump stages. All threaded joints, pumps and other parts of the pump support system must be capable of withstanding the maximum torque repeatedly without loosening or breaking. Unscrewing joints will break electrical cable and may cause loss of the pump-motor unit. To safely withstand maximum unscrewing torques with a minimum safety factor of 1.5, tightening all threaded joints to at least 10 lb-ft per motor horsepower is recommended (table 4A). It may be necessary to tack or strap weld pipe joints on high horsepower pumps, especially at shallower settings. Table 4A Torque Required (Examples) MOTOR RATING HP KW MINIMUM SAFE TORQUE-LOAD 1 hp & Less 0.75 kW & Less 10 lb-ft 20 hp 15 kW 200 lb-ft 75 hp 55 kW 750 lb-ft 200 hp 150 kW 2000 lb-ft 4 !00,)#!4)/. !LL -OTORS 5SE OF %NGINE $RIVEN 'ENERATORS 3INGLE 0HASE OR 4HREE 0HASE Table 5 lists minimum generator sizes based on typical 80 °C rise continuous duty generators, with 35% maximum voltage dip during starting, for Franklin’s threewire motors, single- or three-phase. This is a general chart. The generator manufacturer should be consulted whenever possible, especially on larger sizes. There are two types of generators available: externally and internally regulated. Most are externally regulated. They use an external voltage regulator that senses the output voltage. As the voltage dips at motor start-up, the regulator increases the output voltage of the generator. Internally regulated (self-excited) generators have an extra winding in the generator stator. The extra winding senses the output current to automatically adjust the output voltage. Generators must be sized to deliver at least 65% of the rated voltage during starting to ensure adequate starting torque. Besides sizing, generator frequency is important as the motor speed varies with the frequency (Hz). Due to pump affinity laws, a pump running at 1 to 2 Hz below motor nameplate frequency design will not meet its performance curve. Conversely, a pump running at 1 to 2 Hz above may trip overloads. Generator Operation Always start the generator before the motor is started and always stop the motor before the generator is shut down. The motor thrust bearing may be damaged if the generator is allowed to coast down with the motor running. This same condition occurs when the generator is allowed to run out of fuel. Follow generator manufacturer’s recommendations for de-rating at higher elevations or using natural gas. Table 5 Engine Driven Generators NOTE: This chart applies to 3-wire or 3-phase motors. For best starting of 2-wire motors, the minimum generator rating is 50% higher than shown. MOTOR RATING HP KW 1/3 1/2 3/4 1 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 200 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 93 110 130 150 MINIMUM RATING OF GENERATOR EXTERNALLY REGULATED INTERNALLY REGULATED KW KVA KW KVA 1.5 1.9 1.2 1.5 2 2.5 1.5 1.9 3 3.8 2 2.5 4 5.0 2.5 3.13 5 6.25 3 3.8 7.5 9.4 4 5 10 12.5 5 6.25 15 18.75 7.5 9.4 20 25.0 10 12.5 30 37.5 15 18.75 40 50 20 25 60 75 25 31 75 94 30 37.50 100 125 40 50 100 125 50 62.5 150 188 60 75 175 220 75 94 250 313 100 125 300 375 150 188 375 469 175 219 450 563 200 250 525 656 250 313 600 750 275 344 WARNING: To prevent accidental electrocution, automatic or manual transfer switches must be used any time a generator is used as standby or back up on power lines. Contact power company for use and approval. 5SE OF #HECK 6ALVES It is recommended that one or more check valves always be used in submersible pump installations. If the pump does not have a built-in check valve, a line check valve should be installed in the discharge line within 25 feet of the pump and below the draw down level of the water supply. For deeper settings, check valves should be installed per the manufacturer’s recommendations. More than one check valve may be required, but more than the recommended number of check valves should not be used. hammer and upthrust. Any of these can lead to early pump or motor failure. NOTE: Only positive sealing check valves should be used in submersible installations. Although drilling the check valves or using drain-back check valves may prevent back spinning, they create upthrust and water hammer problems. Swing type check valves are not acceptable and should never be used with submersible motors/pumps. Swing type check valves have a slower reaction time which can cause water hammer (see next page). Internal pump check valves or spring loaded check valves close quickly and help eliminate water hammer. A. Backspin - With no check valve or a failed check valve, the water in the drop pipe and the water in the system can flow down the discharge pipe when the motor stops. This can cause the pump to rotate in a reverse direction. If the motor is started while it is backspinning, an excessive force is placed across the pump-motor assembly that can cause impeller damage, motor or pump shaft breakage, excessive bearing wear, etc. Check valves are used to hold pressure in the system when the pump stops. They also prevent backspin, water B. Upthrust - With no check valve, a leaking check valve, or drilled check valve, the unit starts under 5 !00,)#!4)/. !LL -OTORS a zero head condition. This causes an uplifting or upthrust on the impeller-shaft assembly in the pump. This upward movement carries across the pumpmotor coupling and creates an upthrust condition in the motor. Repeated upthrust can cause premature failure of both the pump and the motor. the discharge piping. On the next pump start, water moving at very high velocity fills the void and strikes the closed check valve and the stationary water in the pipe above it, causing a hydraulic shock. This shock can split pipes, break joints and damage the pump and/or motor. Water hammer can often be heard or felt. When discovered, the system should be shut down and the pump installer contacted to correct the problem. C. Water Hammer - If the lowest check valve is more than 30 feet above the standing (lowest static) water level, or a lower check valve leaks and the check valve above holds, a vacuum is created in 7ELLS n ,ARGE $IAMETER 5NCASED 4OP &EEDING AND 3CREENED 3ECTIONS Franklin Electric submersible motors are designed to operate with a cooling flow of water over and around the full length of the motor. s 7ELL DIAMETER IS TOO LARGE TO MEET TABLE flow requirements. If the pump installation does not provide the minimum flow shown in table 6, a flow inducer sleeve (flow sleeve) must be used. The conditions requiring a flow sleeve are: s 0UMP IS IN A ROCK WELL OR BELOW THE WELL CASING s 0UMP IS IN AN OPEN BODY OF WATER s 4HE WELL IS hTOP FEEDINGv AKA CASCADING s 0UMP IS SET IN OR BELOW SCREENS OR PERFORATIONS 7ATER 4EMPERATURE AND &LOW Franklin Electric’s standard submersible motors, except Hi-Temp designs (see note below), are designed to operate up to maximum service factor horsepower in water up to 86 °F (30 °C). A flow of 0.25 ft/s for 4" motors rated 3 hp and higher, and 0.5 ft/s for 6" and 8" motors is required for proper cooling. Table 6 shows minimum flow rates, in gpm, for various well diameters and motor sizes. Table 6 Required Cooling Flow MINIMUM GPM REQUIRED FOR MOTOR COOLING IN WATER UP TO 86 °F (30 °C). If a standard motor is operated in water over 86 °F (30 °C), water flow past the motor must be increased to maintain safe motor operating temperatures. See HOT WATER APPLICATIONS on page 7. NOTE: Franklin Electric offers a line of Hi-Temp motors designed to operate in water at higher temperatures or lower flow conditions. Consult factory for details. CASING OR SLEEVE ID INCHES (MM) 4" MOTOR (3-10 HP) 0.25 FT/S GPM (L/M) 6" MOTOR 0.50 FT/S GPM (L/M) 8" MOTOR 0.50 FT/S GPM (L/M) 4 (102) 1.2 (4.5) - - 5 (127) 7 (26.5) - - 6 (152) 13 (49) 9 (34) - 7 (178) 20 (76) 25 (95) - 8 (203) 30 (114) 45 (170) 10 (40) 10 (254) 50 (189) 90 (340) 55 (210) 12 (305) 80 (303) 140 (530) 110 (420) 14 (356) 110 (416) 200 (760) 170 (645) 16 (406) 150 (568) 280 (1060) 245 (930) 0.25 ft/s = 7.62 cm/sec 0.50 ft/s = 15.24 cm/sec 1 inch = 2.54 cm &LOW )NDUCER 3LEEVE If the flow rate is less than specified, then a flow inducer sleeve must be used. A flow sleeve is always required in an open body of water. FIG. 1 shows a typical flow inducer sleeve construction. WORM GEAR CLAMPS SAW CUTS INTAKE NOTCH OUT FOR CABLE GUARD EXAMPLE: A 6" motor and pump that delivers 60 gpm will be installed in a 10" well. FLOW INDUCER SLEEVE From table 6, 90 gpm would be required to maintain proper cooling. In this case adding an 8" or smaller flow sleeve provides the required cooling. SUBMERSIBLE MOTOR LOCK NUTS INSIDE SLEEVE BOTTOM END VIEW CENTERING BOLT FIG. 1 CENTERING BOLTS MUST BE LOCATED ON MOTOR CASTING. DO NOT LOCATE ON STATOR SHELL. CENTERING BOLT HOLE (3 REQUIRED) 6 !00,)#!4)/. !LL -OTORS (EAD ,OSS &ROM &LOW 0AST -OTOR Table 7 lists the approximate head loss due to flow between an average length motor and smooth casing or flow inducer sleeve. Table 7 Head Loss in Feet (Meters) at Various Flow Rates 4" 4" 4" 6" 6" 6" 8" 8" CASING ID IN INCHES (MM) 4 (102) 5 (127) 6 (152) 6 (152) 7 (178) 8 (203) 8.1 (206) 10 (254) Flow Rate in gpm (l/m) MOTOR DIAMETER 25 (95) 0.3 (.09) 50 (189) 1.2 (.37) 100 (378) 4.7 (1.4) 150 (568) 10.2 (3.1) 0.3 (.09) 1.7 (.52) 0.6 (.18) 0.2 (.06) 3.7 (1.1) 200 (757) 1.1 (.34) 0.4 (.12) 6.3 (1.9) 0.5 (.15) 6.8 (2.1) 250 (946) 1.8 (.55) 0.7 (.21) 9.6 (2.9) 0.8 (.24) 10.4 (3.2) 300 (1136) 2.5 (.75) 1.0 (.30) 13.6 (4.1) 1.2 (.37) 0.2 (.06) 14.6 (4.5) 23.7 (7.2) 2.0 (.61) 0.4 (.12) 24.6 (7.5) 500 (1893) 3.1 (.94) 0.7 (.21) 37.3 (11.4) 0.6 (0.2) 600 (2271) 4.4 (1.3) 1.0 (.30) 52.2 (15.9) 0.8 (0.3) 400 (1514) 800 (3028) 1.5 (0.5) 1000 (3785) 2.4 (0.7) (OT 7ATER !PPLICATIONS 3TANDARD -OTORS Franklin Electric offers a line of Hi-Temp motors which are designed to operate in water with various temperatures up to 194 °F (90 °C) without increased flow. When a standard pump-motor operates in water hotter than 86 °F (30 °C), a flow rate of at least 3 ft/s is required. When selecting the motor to drive a pump in over 86 °F (30 °C) water, the motor horsepower must be de-rated per the following procedure. 1. Using table 7A, determine pump gpm required for different well or sleeve diameters. If necessary, add a flow sleeve to obtain at least 3 ft/s flow rate. 7 Table 7A Minimum gpm (l/m) Required for 3 ft/s (.91 m/sec) Flow Rate CASING OR SLEEVE ID 4" HIGH THRUST MOTOR 6" MOTOR GPM (L/M) 52 (197) 150 (568) 8" MOTOR INCHES (MM) GPM (L/M) 4 (102) 15 (57) GPM (L/M) 5 (127) 80 (303) 6 (152) 160 (606) 7 (178) 8 (203) 260 (984) 60 (227) 10 (254) 520 (1970) 330 (1250) 12 (305) 650 (2460) 14 (356) 1020 (3860) 16 (406) 1460 (5530) Continued on next page !00,)#!4)/. !LL -OTORS 2. Determine pump horsepower required from the pump manufacturer’s curve. Brake Horsepower 6 EXAMPLE 5 A B 4 C 3 2 1 0 0 5 10 15 20 25 30 35 40 45 50 Gallons Per Minute FIG. 2 MANUFACTURER’S PUMP CURVE Table 8 Heat Factor Multiplier at 3 ft/s (.91 m/sec) Flow Rate 3. Multiply the pump horsepower required by the heat factor multiplier from table 8. MAXIMUM WATER TEMPERATURE 1/3 - 5 HP .25 - 3.7 KW 7 1/2 - 30 HP 5.5 - 22 KW OVER 30 HP OVER 22 KW 140 °F (60 °C) 1.25 1.62 2.00 131 °F (55 °C) 1.11 1.32 1.62 122 °F (50 °C) 1.00 1.14 1.32 113 °F (45 °C) 1.00 1.00 1.14 104 °F (40 °C) 1.00 1.00 1.00 95 °F (35 °C) 1.00 1.00 1.00 Table 8A Service Factor Horsepower 4. Select a rated hp motor on table 8A whose Service Factor Horsepower is at least the value calculated in Item 3. (OT 7ATER !PPLICATIONS HP KW SFHP HP KW SFHP HP KW SFHP HP KW SFHP 1/3 0.25 0.58 3 2.2 3.45 25 18.5 28.75 100 75 115.00 1/2 0.37 0.80 5 3.7 5.75 30 22.0 34.50 125 93 143.75 3/4 0.55 1.12 7.5 5.5 8.62 40 30.0 46.00 150 110 172.50 1 0.75 1.40 10 7.5 11.50 50 37.0 57.50 175 130 201.25 1.5 1.10 1.95 15 11.0 17.25 60 45.0 69.00 200 150 230.00 2 1.50 2.50 20 15.0 23.00 75 55.0 86.25 %XAMPLE EXAMPLE: A 6" pump end requiring 39 hp input will pump 124 °F water in an 8" well at a delivery rate of 140 gpm. From table 7A, a 6" flow sleeve will be required to increase the flow rate to at least 3 ft/s. Using table 8, the 1.62 heat factor multiplier is selected because the hp required is over 30 hp and water temperature is above 122 °F. Multiply 39 hp x 1.62 (multiplier), which equals 63.2 hp. This is the minimum rated service factor horsepower usable at 39 hp in 124 °F. Using table 8A, select a motor with a rated service factor horsepower above 63.2 hp. A 60 hp motor has a service factor horsepower of 69, so a 60 hp motor may be used. 8 !00,)#!4)/. !LL -OTORS $RAWDOWN 3EALS Allowable motor temperature is based on atmospheric PRESSURE OR HIGHER SURROUNDING THE MOTOR h$RAWDOWN SEALS v WHICH SEAL THE WELL TO THE PUMP ABOVE ITS INTAKE to maximize delivery, are not recommended, since the suction created can be lower than atmospheric pressure. 'ROUNDING #ONTROL "OXES AND 0ANELS The National Electrical Code requires that the control box or panel-grounding terminal always be connected to supply ground. If the circuit has no grounding conductor and no metal conduit from the box to supply panel, use a wire at least as large as line conductors and connect as required by the National Electrical Code, from the grounding terminal to the electrical supply ground. WARNING: Failure to ground the control frame can result in a serious or fatal electrical shock hazard. 'ROUNDING 3URGE !RRESTORS An above ground surge arrestor must be grounded, metal to metal, all the way to the lowest draw down water strata for the surge arrestor to be effective. GROUNDING THE ARRESTOR TO THE SUPPLY GROUND OR TO A DRIVEN GROUND ROD PROVIDES LITTLE OR NO SURGE PROTECTION FOR THE MOTOR. #ONTROL "OX 0UMPTEC 0RODUCTS AND 0ANEL %NVIRONMENT Franklin Electric control boxes, Pumptec products and three-phase panels meet UL requirements for NEMA Type 3R enclosures. They are suitable for indoor and outdoor applications within temperatures of +14 °F (-10 °C) to 122 °F (50 °C). Operating control boxes below +14 °F can cause reduced starting torque and loss of overload protection when overloads are located in control boxes. Control boxes, Pumptec products and three-phase panels should never be mounted in direct sunlight or high temperature locations. This will cause shortened capacitor life (where applicable) and unnecessary tripping of overload protectors. A ventilated enclosure painted white to reflect heat is recommended for an outdoor, high temperature location. A damp well pit, or other humid location, accelerates component failure from corrosion. Control boxes with voltage relays are designed for vertical upright mounting only. Mounting in other positions will affect the operation of the relay. %QUIPMENT 'ROUNDING WARNING: Serious or fatal electrical shock may result from failure to connect the motor, control enclosures, metal plumbing and all other metal near the motor or cable to the power supply ground terminal using wire no smaller than motor cable wires. The primary purpose of grounding the metal drop pipe and/or metal well casing in an installation is safety. It is done to limit the voltage between nonelectrical (exposed metal) parts of the system and ground, thus minimizing dangerous shock hazards. Using wire at least the size of the motor cable wires provides adequate current-carrying capability for any ground fault that might occur. It also provides a low resistance path to ground, ensuring that the current to ground will be large enough to trip any overcurrent device designed to detect faults (such as a ground fault circuit interrupter, or GFCI). Normally, the ground wire to the motor would provide the 9 primary path back to the power supply ground for any ground fault. There are conditions, however, where the ground wire connection could become compromised. One such example would be the case where the water in the well is abnormally corrosive or aggressive. In this example, a grounded metal drop pipe or casing would then become the primary path to ground. However, the many installations that now use plastic drop pipes and/or casings require further steps to be taken for safety purposes, so that the water column itself does not become the conductive path to ground. When an installation has abnormally corrosive water AND the drop pipe or casing is plastic, Franklin Electric recommends the use of a GFCI with a 10 mA set-point. In this case, the motor ground wire should be routed through the current-sensing device along with the motor power leads. Wired this way, the GFCI will trip only when a ground fault has occurred AND the motor ground wire is no longer functional. !00,)#!4)/. 3INGLE 0HASE -OTORS 7IRE #ONTROL "OXES Single-phase three-wire submersible motors require the use of control boxes. Operation of motors without control boxes or with incorrect boxes can result in motor failure and voids warranty. Control boxes contain starting capacitors, a starting relay, and, in some sizes, overload protectors, running capacitors and contactors. Ratings through 1 hp may use either a Franklin Electric solid state QD or a potential (voltage) type starting relay, while larger ratings use potential relays. Potential (Voltage) Relays Potential relays have normally closed contacts. When power is applied, both start and main motor windings are energized, and the motor starts. At this instant, the voltage across the start winding is relatively low and not enough to open the contacts of the relay. As the motor accelerates, the increasing voltage across the start winding (and the relay coil) opens the relay contacts. This opens the starting circuit and the motor continues to run on the main winding alone, or the main plus run capacitor circuit. After the motor is started the relay contacts remain open. CAUTION: The control box and motor are two pieces of one assembly. Be certain that the control box and motor hp and voltage match. Since a motor is designed to operate with a control box from the same manufacturer, we can promise warranty coverage only when a Franklin control box is used with a Franklin motor. 7IRE -OTOR 3OLID 3TATE #ONTROLS BIAC Switch Operation When power is applied the bi-metal switch contacts are closed, so the triac is conducting and energizes the start winding. As rpm increases, the voltage in the sensor coil generates heat in the bi-metal strip, causing the bi-metal strip to bend and open the switch circuit. This removes the starting winding and the motor continues to run on the main winding alone. to restart the motor before the starting switch has reset, the motor may not start; however, there will be current in the main winding until the overload protector interrupts the circuit. The time for the protector to reset is longer than the reset of the starting switch. Therefore, the start switch will have closed and the motor will operate. Approximately 5 seconds after power is removed from the motor, the bi-metal strip cools sufficiently to return to its closed position and the motor is ready for the next start cycle. A waterlogged tank will cause fast cycling. When a waterlogged condition does occur, the user will be alerted to the problem during the off time (overload reset time) since the pressure will drop drastically. When the waterlogged tank condition is detected, the condition should be corrected to prevent nuisance tripping of the overload protector. Rapid Cycling Bound Pump (Sandlocked) The BIAC starting switch will reset within approximately 5 seconds after the motor is stopped. If an attempt is made CAUTION: Restarting the motor within 5 seconds after power is removed may cause the motor overload to trip. When the motor is not free to turn, as with a sandlocked PUMP THE ")!# SWITCH CREATES A hREVERSE IMPACT TORQUEv IN THE MOTOR IN EITHER DIRECTION 7HEN THE SAND IS dislodged, the motor will start and operate in the correct direction. 1$ 2ELAYS 3OLID 3TATE There are two elements in the relay: a reed switch and a triac. The reed switch consists of two tiny rectangular blade-type contacts, which bend under magnetic flux. It is hermetically sealed in glass and is located within a coil, which conducts line current. When power is supplied to the control box, the main winding current passing through the coil immediately closes the reed switch contacts. This turns on the triac, which supplies voltage to the start winding, thus starting the motor. Once the motor is started, the operation of the QD relay is an interaction between the triac, the reed switch and the motor windings. The solid state switch senses motor speed through the changing phase relationship between start winding current and line current. As the motor approaches running speed, the phase angle between the start current and the line current becomes nearly in phase. At this point, the reed switch contacts open, turning off the triac. This removes voltage from the start winding and the motor continues to run on the main winding only. With the reed switch contacts open and the triac turned off, the QD relay is ready for the next starting cycle. 10 !00,)#!4)/. 3INGLE 0HASE -OTORS OR 7IRE #ABLE (Z (Service Entrance to Motor - Maximum Length In Feet) 60 °C Table 11 MOTOR RATING 60 °C INSULATION - AWG COPPER WIRE SIZE VOLTS HP KW 14 12 10 8 6 4 3 2 1 0 00 000 0000 115 1/2 .37 100 160 250 390 620 960 1190 1460 1780 2160 2630 3140 3770 1/2 .37 400 650 1020 1610 2510 3880 4810 5880 7170 8720 3/4 .55 300 480 760 1200 1870 2890 3580 4370 5330 6470 7870 1 .75 250 400 630 990 1540 2380 2960 3610 4410 5360 6520 1.5 1.1 190 310 480 770 1200 1870 2320 2850 3500 4280 5240 2 1.5 150 250 390 620 970 1530 1910 2360 2930 3620 4480 3 2.2 120 190 300 470 750 1190 1490 1850 2320 2890 3610 5 3.7 0 0 180 280 450 710 890 1110 1390 1740 2170 2680 7.5 5.5 0 0 0 200 310 490 610 750 930 1140 1410 1720 10 7.5 0 0 0 0 250 390 490 600 750 930 1160 1430 1760 15 11 0 0 0 0 170 270 340 430 530 660 820 1020 1260 230 75 °C Table 11A MOTOR RATING 75 °C INSULATION - AWG COPPER WIRE SIZE VOLTS HP KW 14 12 10 8 6 4 3 2 1 0 00 000 0000 115 1/2 .37 100 160 250 390 620 960 1190 1460 1780 2160 2630 3140 3770 1/2 .37 400 650 1020 1610 2510 3880 4810 5880 7170 8720 3/4 .55 300 480 760 1200 1870 2890 3580 4370 5330 6470 7870 9380 1 .75 250 400 630 990 1540 2380 2960 3610 4410 5360 6520 7780 9350 1.5 1.1 190 310 480 770 1200 1870 2320 2850 3500 4280 5240 6300 7620 2 1.5 150 250 390 620 970 1530 1910 2360 2930 3620 4480 5470 6700 3 2.2 120 190 300 470 750 1190 1490 1850 2320 2890 3610 4470 5550 5 3.7 0 110 180 280 450 710 890 1110 1390 1740 2170 2680 3330 7.5 5.5 0 0 120 200 310 490 610 750 930 1140 1410 1720 2100 10 7.5 0 0 0 160 250 390 490 600 750 930 1160 1430 1760 15 11 0 0 0 0 170 270 340 430 530 660 820 1020 1260 230 1 Foot = .3048 Meter Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors 60 °C or 75 °C in free air or water, not in magnetic enclosures, conduit or direct buried. Lengths NOT in bold meet the NEC ampacity requirements for either individual conductors or jacketed 60 °C or 75 °C cable and can be in conduit or direct buried. Flat molded and web/ribbon cable are considered jacketed cable. The portion of the total cable length, which is between the supply and single-phase control box with a line contactor, should not exceed 25% of total maximum allowable to ensure reliable contactor operation. Singlephase control boxes without line contactors may be connected at any point in the total cable length. Tables 11 & 11A are based on copper wire. If aluminum wire is used, it must be two sizes larger than copper wire and oxidation inhibitors must be used on connections. If any other cable is used, the NEC and local codes should be observed. EXAMPLE: If tables 11 & 11A call for #12 copper wire, #10 aluminum wire would be required. Cable lengths in tables 11 & 11A allow for a 5% voltage drop running at maximum nameplate amperes. If 3% voltage drop is desired, multiply table 11 and 11A lengths by 0.6 to get maximum cable length. Contact Franklin Electric for 90 °C cable lengths. See pages 15, 49, and 50 for applications using 230 V motors on 208 V power systems. 11 !00,)#!4)/. 3INGLE 0HASE -OTORS 4WO OR -ORE $IFFERENT #ABLE 3IZES #AN "E 5SED Depending on the installation, any number of combinations of cable may be used. occurs in this wire. This leaves us 46.7% (1.00 - 0.533 = 0.467) of some other wire size to use in the remaining FEET hDOWN HOLEv WIRE RUN For example, in a replacement/upgrade installation, the well already has 160 feet of buried #10 cable between the service entrance and the wellhead. A new 3 hp, 230-volt, single-phase motor is being installed to replace a smaller motor. The question is: Since there is already 160 feet of #10 AWG installed, what size cable is required in the well with a 3 hp, 230-volt, single-phase motor setting at 310 feet? The table shows #8 AWG copper wire is good for 470 feet. Using the formula again, 310 feet (used) ÷ 470 feet (allowed) = 0.660; adding this to the 0.533 determined earlier; 0.533 + 0.660 = 1.193. This combination is greater than 1.00, so the voltage drop will not meet US National Electrical Code recommendations. Tables 11 & 11A show #6 AWG copper wire is good for 750 feet. Using the formula, 310 ÷ 750 = 0.413, and using these numbers, 0.533 + 0.413 = 0.946, we find this is less than 1.00 and will meet the NEC recommended voltage drop. From tables 11 & 11A, a 3 hp motor can use up to 300 feet of #10 AWG cable. The application has 160 feet of #10 AWG copper wire installed. This works for two, three or more combinations of wire and it does not matter which size wire comes first in the installation. Using the formula below, 160 feet (actual) ÷ 300 feet (max allowable) is equal to 0.533. This means 53.3% (0.533 x 100) of the allowable voltage drop or loss, which is allowed between the service entrance and the motor, Formula: Actual Length Max Allowed + Actual Length Max Allowed = 1.00 EXAMPLE: 3 hp, 230-Volt, Single-Phase Motor 310 ft #6 AWG (41.3% of allowable cable) 160 ft #10 AWG (53.3% of allowable cable) FIG. 3 3 hp, 230 V Single-Phase Motor 12 !00,)#!4)/. 3INGLE 0HASE -OTORS Table 13 Single-Phase Motor Specifications (60 Hz) 3450 rpm FULL LOAD MAXIMUM LOAD (2) WATTS AMPS 12.0 960 6.0 960 8.0 1310 10.4 1600 13.1 2280 Y12.0 B12.0 960 R0 Y6.0 B6.0 960 R0 Y8.0 B8.0 1310 R0 10.4 10.4 1600 R0 HP KW VOLTS HZ S.F. 244504 244505 244507 244508 244309 1/2 1/2 3/4 1 1.5 0.37 0.37 0.55 0.75 1.1 115 230 230 230 230 60 60 60 60 60 1.6 1.6 1.5 1.4 1.3 214504 1/2 0.37 115 60 1.6 214505 1/2 0.37 230 60 1.6 214507 3/4 0.55 230 60 1.5 214508 1 0.75 230 60 1.4 214505 1/2 0.37 230 60 1.6 Y3.6 B3.7 R2.0 655 Y4.3 B4.0 R2.0 214507 3/4 0.55 230 60 1.5 Y4.9 B5.0 R3.2 925 214508 1 0.75 230 60 1.4 Y6.0 B5.7 R3.4 1160 214508 W/11.5 CB 1 0.75 230 60 1.4 224300 1.5 1.1 230 60 1.3 224301 2 1.5 230 60 1.25 224302 (3) 3 2.2 230 60 1.15 224303 (4) 5 3.7 230 60 1.15 226110 (5) 5 3.7 230 60 1.15 226111 7.5 5.5 230 60 1.15 226112 10 7.5 230 60 1.15 226113 15 11 230 60 1.15 6" 4" 3-WIRE 4" 3-WIRE W/CRC CB 4" 3-WIRE TYPE 4" 2-WIRE RATING MOTOR MODEL PREFIX (2) AMPS 10.0 5.0 6.8 8.2 10.6 Y10.0 B10.0 R0 Y5.0 B5.0 R0 Y6.8 B6.8 R0 Y8.2 B8.2 R0 Y6.6 B6.6 R1.3 Y10.0 B9.9 R1.3 Y10.0 B9.3 R2.6 Y14.0 B11.2 R6.1 Y23.0 B15.9 R11.0 Y23.0 B14.3 R10.8 Y36.5 B34.4 R5.5 Y44.0 B39.5 R9.3 Y62.0 B52.0 R17.5 (1) Main winding - yellow to black Start winding - yellow to red (2) Y = Yellow lead - line amps B = Black lead - main winding amps R = Red lead - start or auxiliary winding amps (3) Control Boxes date coded 02C and older have 35 MFD run capacitors. Current values should be Y14.0 @ FL and Y17.0 @ Max Load. B12.2 B14.5 R4.7 R4.5 WATTS 670 670 940 1210 1770 670 670 940 1210 1130 1620 2025 3000 4830 4910 7300 9800 13900 WINDING (1) RES. IN OHMS M=MAIN RES. S=START RES. 1.0-1.3 4.2-5.2 3.0-3.6 2.2-2.7 1.5-2.1 EFFICIENCY % POWER FACTOR % S.F. F.L. S.F. 62 62 64 65 64 56 56 59 62 63 73 73 74 74 83 M1.0-1.3 S4.1-5.1 62 56 M4.2-5.2 S16.7-20.5 62 M3.0-3.6 S10.7-13.1 F.L. LOCKED ROTOR AMPS KVA CODE 58 58 62 63 76 64.4 32.2 40.7 48.7 66.2 R R N N M 73 58 50.5 M 56 73 58 23 M 64 59 74 62 34.2 M M2.2-2.7 S9.9-12.1 65 62 74 63 41.8 L 890 M4.2-5.2 S16.7-20.5 67 57 90 81 23 M Y5.7 B5.2 R3.1 1220 M3.0-3.6 S10.7-13.1 69 60 92 84 34.2 M Y7.1 B6.2 R3.3 1490 M2.2-2.7 S9.9-12.1 70 64 92 86 41.8 L 1500 M2.2-2.7 S9.9-12.1 70 66 82 72 43 L 2080 M1.7-2.1 S7.5-9.2 70 69 85 79 51.4 J 2555 M1.8-2.3 S5.5-7.2 73 74 95 94 53.1 G 3400 M1.1-1.4 S4.0-4.8 75 75 99 99 83.4 H 5500 M.71-.82 S1.8-2.2 78 77 100 100 129 G 5570 M.55-.68 S1.3-1.7 77 76 100 99 99 E 8800 M.36-.50 S.88-1.1 73 74 91 90 165 F 11300 M.27-.33 S.80-.99 76 77 96 96 204 E 16200 M.17-.22 S.68-.93 79 80 97 98 303 E Y8.0 B7.9 R1.3 Y11.5 B11.0 R1.3 Y13.2 B11.9 R2.6 Y17.0 B12.6 R6.0 Y27.5 B19.1 R10.8 Y27.5 B17.4 R10.5 Y42.1 B40.5 R5.4 Y51.0 B47.5 R8.9 Y75.0 B62.5 R16.9 (4) Control Boxes date coded 01M and older have 60 MFD run capacitors and the current values on a 4" motor will be Y23.0 @ FL - Y27.5 @ Max Load. B19.1 B23.2 R8.0 R7.8 (5) Control Boxes date coded 01M and older have 60 MFD run capacitors and the current values on a 6" motor will be Y23.0 @ FL -Y27.5 @ Max Load. B18.2 B23.2 R8.0 R7.8 Performance is typical, not guaranteed, at specified voltages and specified capacitor values. Performance at voltage ratings not shown is similar, except amps vary inversely with voltage. 13 !00,)#!4)/. 3INGLE 0HASE -OTORS Table 14 Single-Phase Motor Fuse Sizing 4" 3-WIRE W/CRC CB 4" 3-WIRE 4" 2-WIRE TYPE MOTOR MODEL PREFIX CIRCUIT BREAKERS OR FUSE AMPS (MAXIMUM PER NEC) (TYPICAL SUBMERSIBLE) HP KW VOLTS STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER 244504 1/2 0.37 115 35 20 30 30 15 30 244505 1/2 0.37 230 20 10 15 15 8 15 244507 3/4 0.55 230 25 15 20 20 10 20 244508 1 0.75 230 30 20 25 25 11 25 244309 1.5 1.1 230 35 20 30 35 15 30 214504 1/2 0.37 115 35 20 30 30 15 30 214505 1/2 0.37 230 20 10 15 15 8 15 214507 3/4 0.55 230 25 15 20 20 10 20 214508 1 0.75 230 30 20 25 25 11 25 214505 1/2 0.37 230 20 10 15 15 8 15 214507 3/4 0.55 230 25 15 20 20 10 20 214508 1 0.75 230 30 20 25 25 11 25 1 0.75 230 30 20 25 25 11 25 224300 1.5 1.1 230 35 20 30 30 15 30 224301 2 1.5 230 30 20 25 30 15 25 224302 3 2.2 230 45 30 40 45 20 40 224303 5 3.7 230 80 45 60 70 30 60 226110 5 3.7 230 80 45 60 70 30 60 226111 7.5 5.5 230 125 70 100 110 50 100 226112 10 7.5 230 150 80 125 150 60 125 226113 15 11 230 200 125 175 200 90 175 214508 W/ 1-1.5 CB 6" 4" 3-WIRE CIRCUIT BREAKERS OR FUSE AMPS RATING 14 !00,)#!4)/. 3INGLE 0HASE -OTORS !UXILIARY 2UNNING #APACITORS !DDED CAPACITORS MUST BE CONNECTED ACROSS h2EDv AND h"LACKv CONTROL BOX TERMINALS IN PARALLEL WITH ANY EXISTING running capacitors. The additional capacitor(s) should be mounted in an auxiliary box. The values of additional running capacitors most likely to reduce noise are given below. The tabulation gives the max. S.F. amps normally in each lead with the added capacitor. Although motor amps decrease when auxiliary run capacitance is added, the load on the motor does not. If a motor is overloaded with normal capacitance, it still will be overloaded with auxiliary run capacitance, even though motor amps may be within nameplate values. Table 15 Auxiliary Capacitor Sizing MOTOR RATING NORMAL RUNNING CAPACITOR(S) AUXILIARY RUNNING CAPACITORS FOR NOISE REDUCTION MAXIMUM AMPS WITH RUN CAP HP VOLTS MFD MFD MIN. VOLTS FRANKLIN PART YELLOW BLACK RED 1/2 115 0 60(1) 370 TWO 155327101 8.4 7.0 4.0 1/2 0 15(1) 370 ONE 155328101 4.2 3.5 2.0 3/4 0 20(1) 370 ONE 155328103 5.8 5.0 2.5 7.1 5.6 3.4 1 0 25(1) 370 ONE EA. 155328101 155328102 1.5 10 20 370 ONE 155328103 9.3 7.5 4.4 20 10 370 ONE 155328102 11.2 9.2 3.8 45 NONE 370 17.0 12.6 6.0 80 NONE 370 2 230 3 5 7.5 45 45 370 ONE EA. 155327101 155328101 10 70 30 370 ONE 155327101 15 135 NONE 27.5 19.1 10.8 37.0 32.0 11.3 49.0 42.0 13.0 75.0 62.5 16.9 (1) Do not add running capacitors to 1/3 through 1 hp control boxes, which use solid state switches or QD relays. Adding capacitors will cause switch failure. If the control box is converted to use a voltage relay, the specified running capacitance can be added. "UCK "OOST 4RANSFORMERS wide range of voltage boost or buck are published by transformer manufacturers, the following table shows Franklin’s recommendations. The table, based on boosting the voltage 10%, shows the minimum rated transformer kVA needed and the common standard transformer kVA. When the available power supply voltage is not within the proper range, a buck-boost transformer is often used to adjust voltage to match the motor. The most common usage on submersible motors is boosting a 208 volt supply to use a standard 230 volt single-phase submersible motor and control. While tables to give a Table 15A Buck-Boost Transformer Sizing MOTOR HP 1/3 1/2 3/4 1 1.5 2 3 5 7.5 10 15 LOAD KVA 1.02 1.36 1.84 2.21 2.65 3.04 3.91 6.33 9.66 11.70 16.60 MINIMUM XFMR KVA 0.11 0.14 0.19 0.22 0.27 0.31 0.40 0.64 0.97 1.20 1.70 STANDARD XFMR KVA 0.25 0.25 0.25 0.25 0.50 0.50 0.50 0.75 1.00 1.50 2.00 Buck-Boost transformers are power transformers, not control transformers. They may also be used to lower voltage when the available power supply voltage is too high. 15 !00,)#!4)/. 4HREE 0HASE -OTORS Table 16 Three-Phase 60 °C Cable, 60 Hz (Service Entrance to Motor) Maximum Length in Feet MOTOR RATING VOLTS 200 V 60 Hz ThreePhase 3 - Lead 230 V 60 Hz ThreePhase 3 - Lead 380 V 60 Hz ThreePhase 3 - Lead 60 °C INSULATION - AWG COPPER WIRE SIZE HP KW 14 12 10 8 6 4 3 1/2 0.37 710 1140 1800 2840 4420 3/4 0.55 510 810 1280 2030 3160 1 0.75 430 690 1080 1710 1.5 1.1 310 500 790 1260 2670 4140 5140 1960 3050 2 1.5 240 390 610 3780 970 1520 2360 3 2.2 180 290 470 740 1160 1810 5 3.7 110 170 280 440 690 5.5 0 0 200 310 7.5 10 7.5 0 0 0 15 11 0 0 20 15 0 25 18.5 30 60 °C MCM COPPER WIRE SIZE 2 1 0 00 000 0000 250 2940 3610 4430 5420 2250 2760 3390 4130 1080 1350 1660 2040 490 770 960 1180 230 370 570 720 0 160 250 390 0 0 0 190 0 0 0 0 22 0 0 0 1/2 0.37 930 1490 3/4 0.55 670 300 350 400 500 2490 3050 3670 4440 5030 1450 1770 2170 2600 3150 3560 880 1090 1330 1640 1970 2390 2720 490 600 740 910 1110 1340 3100 3480 3800 4420 1630 1850 2100 2350 2570 300 380 460 570 700 860 2980 1050 1270 1440 1650 1850 2020 0 240 300 370 460 570 2360 700 840 1030 1170 1330 1500 1640 0 0 0 250 310 380 470 1900 580 700 850 970 1110 1250 1360 2350 3700 5760 8910 1590 1080 1700 2580 4190 6490 8060 9860 910 1430 2260 3520 5460 6780 8290 1 0.75 560 1.5 1.1 420 670 1060 1670 2610 4050 5030 6160 7530 9170 2 1.5 320 510 810 1280 2010 3130 3890 4770 5860 7170 3 2.2 240 390 620 990 1540 2400 2980 3660 4480 5470 6690 8020 9680 5 3.7 140 230 370 590 920 1430 1790 2190 2690 3290 4030 4850 5870 6650 7560 8460 9220 7.5 5.5 0 160 260 420 650 1020 1270 1560 1920 2340 2870 3440 4160 4710 5340 5970 6500 7510 10 7.5 0 0 190 310 490 760 950 1170 1440 1760 2160 2610 3160 3590 4100 4600 5020 5840 15 11 0 0 0 210 330 520 650 800 980 1200 1470 1780 2150 2440 2780 3110 3400 3940 20 15 0 0 0 0 250 400 500 610 760 930 1140 1380 1680 1910 2180 2450 2680 3120 25 18.5 0 0 0 0 0 320 400 500 610 750 920 1120 1360 1540 1760 1980 2160 2520 0 0 260 330 410 510 620 760 930 1130 1280 1470 1650 1800 2110 8830 8780 30 22 0 0 0 1/2 0.37 2690 4290 6730 3/4 0.55 2000 3190 5010 7860 1 0.75 1620 2580 4060 6390 9980 1.5 1.1 1230 1970 3100 4890 7630 2 1.5 870 1390 2180 3450 5400 8380 3 2.2 680 1090 1710 2690 4200 6500 8020 9830 5 3.7 400 640 1010 1590 2490 3870 4780 5870 7230 7.5 5.5 270 440 690 1090 1710 2640 3260 4000 4930 6010 7290 8780 10 7.5 200 320 510 800 1250 1930 2380 2910 3570 4330 5230 6260 7390 8280 9340 15 11 0 0 370 590 920 1430 1770 2170 2690 3290 4000 4840 5770 6520 7430 8250 8990 20 15 0 0 0 440 700 1090 1350 1670 2060 2530 3090 3760 4500 5110 5840 6510 7120 8190 25 18.5 0 0 0 360 570 880 1100 1350 1670 2050 2510 3040 3640 4130 4720 5250 5740 6590 30 22 0 0 0 0 470 730 910 1120 1380 1700 2080 2520 3020 3430 3920 4360 4770 5490 40 30 0 0 0 0 0 530 660 820 1010 1240 1520 1840 2200 2500 2850 3170 3470 3990 50 37 0 0 0 0 0 0 540 660 820 1000 1220 1480 1770 2010 2290 2550 2780 3190 60 45 0 0 0 0 0 0 0 560 690 850 1030 1250 1500 1700 1940 2150 2350 2700 75 55 0 0 0 0 0 0 0 0 570 700 860 1050 1270 1440 1660 1850 2030 2350 100 75 0 0 0 0 0 0 0 0 0 510 630 760 910 1030 1180 1310 1430 1650 125 93 0 0 0 0 0 0 0 0 0 0 0 620 740 840 950 1060 1160 1330 150 110 0 0 0 0 0 0 0 0 0 0 0 0 620 700 790 880 960 1090 175 130 0 0 0 0 0 0 0 0 0 0 0 0 0 650 750 840 920 1070 200 150 0 0 0 0 0 0 0 0 0 0 0 0 0 0 630 700 760 880 Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details. Continued on next page 16 !00,)#!4)/. 4HREE 0HASE -OTORS 60 °C Table 17 Three-Phase 60 °C Cable (Continued) MOTOR RATING VOLTS KW 14 12 10 2 1 00 000 1/2 0.37 3770 6020 9460 3/4 0.55 2730 4350 6850 0.75 2300 3670 5770 9070 1.1 1700 2710 4270 6730 2 1.5 1300 2070 3270 5150 8050 3 2.2 1000 1600 2520 3970 6200 5 3.7 590 950 1500 2360 3700 5750 7.5 5.5 420 680 1070 1690 2640 10 7.5 310 500 790 1250 1960 4100 5100 6260 7680 3050 3800 4680 15 11 0 340 540 850 5750 7050 1340 2090 2600 3200 3930 20 15 0 0 410 650 1030 1610 2000 2470 3040 4810 5900 7110 3730 4580 25 18.5 0 0 0 530 830 1300 1620 1990 5530 2450 3010 3700 30 22 0 0 0 430 680 1070 1330 4470 5430 1640 2030 2490 3060 3700 40 30 0 0 0 0 500 790 980 1210 1490 1830 2250 2710 50 37 0 0 0 0 0 640 800 980 1210 1480 1810 60 45 0 0 0 0 0 540 670 830 1020 1250 75 55 0 0 0 0 0 0 0 680 840 100 75 0 0 0 0 0 0 0 0 125 93 0 0 0 0 0 0 0 150 110 0 0 0 0 0 0 130 0 0 0 0 0 200 150 0 0 0 0 0 1/2 0.37 5900 9410 3/4 0.55 4270 6810 1 0.75 3630 5800 9120 1.5 1.1 2620 4180 6580 2 1.5 2030 3250 5110 8060 3 2.2 1580 2530 3980 6270 5 3.7 920 1480 2330 3680 5750 7.5 5.5 660 1060 1680 2650 4150 10 7.5 490 780 1240 1950 15 11 330 530 850 1340 20 15 0 410 650 25 18.5 0 0 30 22 0 40 30 50 1.5 175 575 V 60 Hz ThreePhase 3 - Lead 60 8 6 4 MCM COPPER WIRE SIZE 3 1 460 V 60 Hz ThreePhase 3 - Lead 60 °C INSULATION - AWG COPPER WIRE SIZE HP 0 0000 250 300 350 400 500 4500 5130 5860 3290 3730 4250 2190 2650 3010 1540 1850 2240 2540 3420 3830 4180 4850 2890 3240 3540 1030 1260 1520 1850 4100 2100 2400 2700 2950 620 760 940 1130 3440 1380 1560 1790 2010 2190 0 0 0 740 2550 890 1000 1220 1390 1560 1700 0 0 0 0 1960 0 760 920 1050 1190 1340 1460 0 0 0 0 1690 0 0 0 810 930 1060 1190 1300 0 0 0 1510 0 0 0 0 0 810 920 1030 1130 1310 3060 4770 5940 2090 3260 4060 1030 1610 2520 3140 520 830 1300 2030 2530 3860 4760 5830 3110 3840 0 430 680 1070 1670 4710 2080 2560 3160 0 0 0 500 790 3880 4770 5780 7030 8000 1240 1540 1900 2330 2860 3510 4230 5140 37 0 0 0 0 5830 640 1000 1250 1540 1890 2310 2840 3420 4140 45 0 0 0 4700 5340 5990 6530 7580 0 0 850 1060 1300 1600 1960 2400 2890 3500 3970 4520 5070 5530 0 6410 0 0 0 690 860 1060 1310 1600 1970 2380 2890 3290 3750 5220 4610 5370 75 55 0 100 75 0 0 0 0 0 0 0 790 970 1190 1460 1770 2150 2440 2790 3140 3430 3990 125 93 0 0 0 0 0 0 0 0 770 950 1160 1400 1690 1920 2180 2440 2650 3070 150 110 0 0 0 0 0 0 0 0 0 800 990 1190 1440 1630 1860 2080 2270 2640 175 130 0 0 0 0 0 0 0 0 0 0 870 1050 1270 1450 1650 1860 2030 2360 200 150 0 0 0 0 0 0 0 0 0 0 0 1110 1260 1440 1620 1760 2050 920 Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See 11 for additional details. 17 Continued on next page !00,)#!4)/. 4HREE 0HASE -OTORS 60 °C Table 18 Three-Phase 60 °C Cable (Continued) MOTOR RATING VOLTS HP KW 5 3.7 200 V 7.5 5.5 60 Hz 10 7.5 Three15 11 Phase 20 15 6 - Lead 25 18.5 Y-D 30 22 5 3.7 230 V 7.5 5.5 60 Hz 10 7.5 Three15 11 Phase 20 15 6 - Lead 25 18.5 Y-D 30 22 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 380 V 30 22 60 Hz 40 30 ThreePhase 50 37 6 - Lead 60 45 Y-D 75 55 100 75 125 93 150 110 175 130 200 150 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 460 V 30 22 60 Hz 40 30 ThreePhase 50 37 6 - Lead 60 45 Y-D 75 55 100 75 125 93 150 110 175 130 200 150 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 575 V 30 22 60 Hz 40 30 ThreePhase 50 37 6 - Lead 60 45 Y-D 75 55 100 75 125 93 150 110 175 130 200 150 14 12 10 8 160 110 80 0 0 0 0 210 150 110 0 0 0 0 600 400 300 210 160 0 0 0 0 0 0 0 0 0 0 0 880 630 460 310 230 190 0 0 0 0 0 0 0 0 0 0 1380 990 730 490 370 300 240 0 0 0 0 0 0 0 0 0 250 180 130 0 0 0 0 340 240 180 0 0 0 0 960 660 480 340 260 210 0 0 0 0 0 0 0 0 0 0 1420 1020 750 510 380 310 250 0 0 0 0 0 0 0 0 0 2220 1590 1170 790 610 490 400 300 0 0 0 0 0 0 0 0 420 300 210 140 0 0 0 550 390 280 190 140 0 0 1510 1030 760 550 410 330 270 0 0 0 0 0 0 0 0 0 2250 1600 1180 810 610 490 410 300 0 0 0 0 0 0 0 0 3490 2520 1860 1270 970 780 645 480 380 0 0 0 0 0 0 0 660 460 340 240 170 140 0 880 630 460 310 230 190 150 2380 1630 1200 880 660 540 430 320 250 0 0 0 0 0 0 0 3540 2530 1870 1270 970 790 640 480 370 320 0 0 0 0 0 0 5520 3970 2920 2010 1540 1240 1020 750 590 500 420 0 0 0 0 0 60 °C INSULATION - AWG COPPER WIRE SIZE 6 4 3 2 1 1030 730 550 370 280 220 180 1380 970 730 490 370 300 240 3730 2560 1870 1380 1050 850 700 510 400 340 0 0 0 0 0 0 5550 3960 2940 2010 1540 1240 1020 750 590 500 420 0 0 0 0 0 8620 6220 4590 3130 2410 1950 1600 1180 960 790 660 400 0 0 0 0 MCM COPPER WIRE SIZE 300 350 400 0 00 000 0000 250 3060 2170 1630 1110 850 690 570 4030 2880 2160 1470 1140 910 760 3730 2650 1990 1360 1050 850 700 4930 3510 2640 1800 1390 1120 930 4570 3250 2460 1660 1290 1050 870 6040 4300 3240 2200 1710 1380 1140 5500 3900 2950 2010 1570 1260 1050 7270 5160 3910 2670 2070 1680 1390 6660 4720 3580 2440 1900 1540 1270 8800 6240 4740 3220 2520 2040 1690 7540 5340 4080 2770 2160 1750 1450 9970 7060 5380 3660 2860 2310 1920 4650 3150 2470 1990 1660 5220 3520 2770 2250 1870 5700 3850 3030 2460 2040 6630 4470 3540 2850 2380 8010 6150 4170 3270 2640 2200 8950 6900 4660 3670 2970 2470 9750 7530 5100 4020 3240 2700 8760 5910 4680 3780 3160 7390 5350 4030 3090 2500 2070 1510 1230 1030 855 640 490 420 360 0 9010 6490 4930 3790 3070 2550 1860 1500 1270 1050 760 600 510 440 0 7840 6000 4630 3760 3120 2280 1830 1540 1290 940 730 620 540 480 9390 7260 5640 4560 3780 2760 2220 1870 1570 1140 930 750 660 580 8650 6750 5460 4530 3300 2650 2250 1900 1360 1110 930 780 690 9780 7660 6190 5140 3750 3010 2550 2160 1540 1260 1050 970 790 4260 7080 5880 4270 3430 2910 2490 1770 1420 1180 1120 940 9760 7870 6540 4750 3820 3220 2770 1960 1590 1320 1260 1050 8610 7150 5200 4170 3520 3040 2140 1740 1440 1380 1140 9880 8230 5980 4780 4050 3520 2470 1990 1630 1600 1320 9390 7020 4800 3700 2980 2460 1810 1470 1240 1020 760 590 510 0 0 8620 5890 4560 3670 3040 2230 1810 1530 1260 930 730 630 550 0 7210 5590 4510 3730 2740 2220 1870 1540 1140 880 770 680 590 8850 6870 5550 4590 3370 2710 2310 1890 1410 1110 950 830 730 8290 6700 5550 4060 3280 2770 2280 1690 1330 1140 1000 880 8140 6750 4930 3970 3360 2770 2070 1500 1380 1220 1070 7690 5590 4510 3810 3150 2340 1830 1570 1390 1210 8790 6370 5130 4330 3600 2680 2080 1790 1580 1380 5740 4860 4050 3010 2340 2000 1780 1550 6270 5310 4420 3280 2550 2180 1950 1690 7270 6150 5160 3820 2940 2530 2270 1970 5790 4660 3840 2850 2310 1950 1590 1180 920 800 700 0 7140 5760 4740 3490 2830 2400 1960 1450 1150 990 860 760 8740 7060 5820 4290 3460 2940 2400 1780 1420 1210 1060 930 7150 5260 4260 3600 2950 2190 1740 1480 1300 1140 8670 6340 5130 4330 3570 2650 2100 1780 1570 1370 7710 6210 5250 4330 3220 2530 2160 1910 1670 8740 7050 5950 4930 3660 2880 2450 2170 1890 8010 6780 5620 4180 3270 2790 2480 2160 8980 7600 6330 4710 3660 3120 2780 2420 9790 8290 6910 5140 3970 3410 3040 2640 9610 8050 5980 4600 3950 3540 3070 1620 1150 850 580 450 360 294 2140 1530 1140 780 600 480 390 5800 3960 2890 2140 1630 1320 1090 790 630 540 450 0 0 0 0 0 8620 6150 4570 3130 2410 1950 1600 1180 960 810 660 500 0 0 0 0 2020 1440 1080 730 570 450 370 2680 1900 1420 970 750 600 490 7170 4890 3570 2650 2020 1650 1360 990 810 660 550 420 0 0 0 0 2490 1770 1320 900 690 550 460 3280 2340 1750 1200 910 750 610 8800 6000 4360 3250 2500 2020 1680 1230 990 840 690 520 400 0 0 0 7650 5700 3900 3000 2430 1990 1470 1200 1000 810 610 470 0 0 0 7150 4890 3780 3040 2500 1860 1500 1270 1030 780 600 0 0 0 8910 6090 4710 3790 3120 2310 1870 1590 1290 960 740 650 0 0 500 Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details. 18 !00,)#!4)/. 4HREE 0HASE -OTORS Table 19 Three-Phase 75 °C Cable, 60 Hz (Service Entrance to Motor) Maximum Length in Feet MOTOR RATING VOLTS 200 V 60 Hz ThreePhase 3 - Lead 230 V 60 Hz ThreePhase 3 - Lead 380 V 60 Hz ThreePhase 3 - Lead 75 °C INSULATION - AWG COPPER WIRE SIZE HP KW 14 12 10 8 6 1/2 0.37 710 1140 1800 2840 4420 3/4 0.55 510 810 1280 2030 3160 690 1080 1710 4 3 75 °C MCM COPPER WIRE SIZE 2 1 0 00 000 0000 250 300 350 400 500 1 0.75 430 2670 4140 5140 1.5 1.1 310 500 790 1260 1960 3050 3780 2 1.5 240 390 610 970 1520 2360 2940 3610 4430 5420 3 2.2 180 290 470 740 1160 1810 2250 2760 3390 4130 5 3.7 110 170 280 440 690 1080 1350 1660 2040 2490 3050 3670 4440 5030 7.5 5.5 0 0 200 310 490 770 960 1180 1450 1770 2170 2600 3150 3560 10 7.5 0 0 150 230 370 570 720 880 1090 1330 1640 1970 2390 2720 3100 3480 3800 4420 15 11 0 0 0 160 250 390 490 600 740 910 1110 1340 1630 1850 2100 2350 2570 2980 20 15 0 0 0 0 190 300 380 460 570 700 860 1050 1270 1440 1650 1850 2020 2360 25 18.5 0 0 0 0 0 240 300 370 460 570 700 840 1030 1170 1330 1500 1640 1900 30 22 0 0 0 0 0 200 250 310 380 470 580 700 850 970 1110 1250 1360 1590 1/2 0.37 930 1490 2350 3700 5760 8910 3/4 0.55 670 1080 1700 2580 4190 6490 8060 9860 1 0.75 560 910 1430 2260 3520 5460 6780 8290 1.5 1.1 420 670 1060 1670 2610 4050 5030 6160 7530 9170 2 1.5 320 510 810 1280 2010 3130 3890 4770 5860 7170 8780 2.2 240 390 620 990 1540 2400 2980 3660 4480 5470 6690 8020 9680 230 370 590 920 1430 1790 2190 2690 3290 4030 4850 3 5 3.7 140 5870 6650 7560 8460 9220 7.5 5.5 0 160 260 420 650 1020 1270 1560 1920 2340 2870 3440 4160 4710 5340 5970 6500 7510 10 7.5 0 0 190 310 490 760 950 1170 1440 1760 2160 2610 3160 3590 4100 4600 5020 5840 15 11 0 0 0 210 330 520 650 800 980 1200 1470 1780 2150 2440 2780 3110 3400 3940 20 15 0 0 0 160 250 400 500 610 760 930 1140 1380 1680 1910 2180 2450 2680 3120 25 18.5 0 0 0 0 200 320 400 500 610 750 920 1120 1360 1540 1760 1980 2160 2520 30 22 0 0 0 0 0 260 330 410 510 620 760 930 1130 1280 1470 1650 1800 2110 1/2 0.37 2690 4290 6730 3/4 0.55 2000 3190 5010 7860 1 0.75 1620 2580 4060 6390 9980 1.5 1.1 1230 1970 3100 4890 7630 2 1.5 870 1390 2180 3450 5400 8380 3 2.2 680 1090 1710 2690 4200 6500 8020 9830 5 3.7 400 640 1010 1590 2490 3870 4780 5870 7230 8830 7.5 5.5 270 440 690 1090 1710 2640 3260 4000 4930 6010 7290 8780 10 7.5 200 320 510 800 1250 1930 2380 2910 3570 4330 5230 6260 7390 8280 9340 11 0 0 370 590 920 1430 1770 2170 2690 3290 4000 4840 5770 6520 7430 8250 8990 15 0 0 280 440 700 1090 1350 1670 2060 2530 3090 3760 4500 5110 2840 6510 7120 8190 25 18.5 0 0 0 360 570 880 1100 1350 1670 2050 2510 3040 3640 4130 4720 5250 5740 6590 30 22 0 0 0 290 470 730 910 1120 1380 1700 2080 2520 3020 3430 3920 4360 4770 5490 40 30 0 0 0 0 0 530 660 820 1010 1240 1520 1840 2200 2500 2850 3170 3470 3990 50 37 0 0 0 0 0 440 540 660 820 1000 1220 1480 1770 2010 2290 2550 2780 3190 60 45 0 0 0 0 0 370 460 560 690 850 1030 1250 1500 1700 1940 2150 2350 2700 75 55 0 0 0 0 0 0 0 460 570 700 860 1050 1270 1440 1660 1850 2030 2350 100 75 0 0 0 0 0 0 0 0 420 510 630 760 910 1030 1180 1310 1430 1650 125 93 0 0 0 0 0 0 0 0 0 0 510 620 740 840 950 1060 1160 1330 150 110 0 0 0 0 0 0 0 0 0 0 0 520 620 700 790 880 960 1090 175 130 0 0 0 0 0 0 0 0 0 0 0 0 560 650 750 840 920 1070 200 150 0 0 0 0 0 0 0 0 0 0 0 0 0 550 630 700 760 880 15 20 Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details. 19 Continued on next page !00,)#!4)/. 4HREE 0HASE -OTORS 75 °C Table 20 Three-Phase 75 °C Cable (Continued) MOTOR RATING VOLTS 460 V 60 Hz ThreePhase 3 - Lead KW 14 12 10 1/2 0.37 3770 6020 9460 3/4 0.55 2730 4350 6850 3670 8 6 4 3 2 1 MCM COPPER WIRE SIZE 0 00 000 0000 250 300 350 400 500 1 0.75 2300 5770 9070 1.5 1.1 1700 2710 4270 6730 2 1.5 1300 2070 3270 5150 8050 3 2.2 1000 1600 2520 3970 6200 5 3.7 590 950 1500 2360 3700 5750 7.5 5.5 420 680 1070 1690 2640 4100 5100 6260 7680 10 7.5 310 500 790 1250 1960 3050 3800 4680 5750 15 11 0 340 540 850 1340 2090 2600 3200 3930 4810 5900 7110 20 15 0 0 410 650 1030 1610 2000 2470 3040 3730 4580 5530 25 18.5 0 0 330 530 830 1300 1620 1990 2450 3010 3700 4470 5430 30 22 0 0 270 430 680 1070 1330 1640 2030 2490 3060 3700 4500 5130 5860 40 30 0 0 0 320 500 790 980 1210 1490 1830 2250 2710 3290 3730 4250 50 37 0 0 0 0 410 640 800 980 1210 1480 1810 2190 2650 3010 3420 3830 4180 4850 60 45 0 0 0 0 0 540 670 830 1020 1250 1540 1850 2240 2540 2890 3240 3540 4100 75 55 0 0 0 0 0 440 550 680 840 1030 1260 1520 1850 2100 2400 2700 2950 3440 100 75 0 0 0 0 0 0 0 500 620 760 940 1130 1380 1560 1790 2010 2190 2550 93 0 0 0 0 0 0 0 0 0 600 740 890 1000 1220 1390 1560 1700 1960 110 0 0 0 0 0 0 0 0 0 0 630 760 920 1050 1190 1340 1460 1690 175 130 0 0 0 0 0 0 0 0 0 0 0 670 810 930 1060 1190 1300 1510 200 150 0 0 0 0 0 0 0 0 0 0 0 590 710 810 920 1030 1130 1310 1/2 0.37 5900 9410 3/4 0.55 4270 6810 1 0.75 3630 5800 9120 1.5 1.1 2620 4180 6580 2 1.5 2030 3250 5110 8060 3 2.2 1580 2530 3980 6270 5 3.7 920 1480 2330 3680 5750 7.5 5.5 660 1060 1680 2650 4150 10 7.5 490 780 1240 1950 3060 4770 5940 15 11 330 530 850 1340 2090 3260 4060 20 15 0 410 650 1030 1610 2520 3140 3860 4760 5830 25 18.5 0 0 520 830 1300 2030 2530 3110 3840 4710 30 22 0 0 430 680 1070 1670 2080 2560 3160 3880 4770 5780 7030 8000 30 0 0 0 500 790 1240 1540 1900 2330 2860 3510 4230 5140 5830 37 0 0 0 410 640 1000 1250 1540 1890 2310 2840 3420 4140 4700 5340 5990 6530 7580 60 45 0 0 0 0 540 850 1060 1300 1600 1960 2400 2890 3500 3970 4520 5070 5530 6410 75 55 0 0 0 0 0 690 860 1060 1310 1600 1970 2380 2890 3290 3750 5220 4610 5370 100 75 0 0 0 0 0 0 640 790 970 1190 1460 1770 2150 2440 2790 3140 3430 3990 125 93 0 0 0 0 0 0 0 630 770 950 1160 1400 1690 1920 2180 2440 2650 3070 150 110 0 0 0 0 0 0 0 0 660 800 990 1190 1440 1630 1860 2080 2270 2640 175 130 0 0 0 0 0 0 0 0 0 700 870 1050 1270 1450 1650 1860 2030 2360 200 150 0 0 0 0 0 0 0 0 0 0 760 920 1110 1260 1440 1620 1760 2050 125 150 575 V 60 Hz ThreePhase 3 - Lead 75 °C INSULATION - AWG COPPER WIRE SIZE HP 40 50 7050 Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details. Continued on next page 20 !00,)#!4)/. 4HREE 0HASE -OTORS 75 °C Table 21 Three-Phase 75 °C Cable (Continued) MOTOR RATING VOLTS HP KW 5 3.7 200 V 7.5 5.5 60 Hz 10 7.5 Three15 11 Phase 20 15 6 - Lead 25 18.5 Y-D 30 22 5 3.7 230 V 7.5 5.5 60 Hz 10 7.5 Three15 11 Phase 20 15 6 - Lead 25 18.5 Y-D 30 22 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 380 V 30 22 60 Hz 40 30 ThreePhase 50 37 6 - Lead 60 45 Y-D 75 55 100 75 125 93 150 110 175 130 200 150 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 460 V 30 22 60 Hz 40 30 ThreePhase 50 37 6 - Lead 60 45 Y-D 75 55 100 75 125 93 150 110 175 130 200 150 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 575 V 30 22 60 Hz 40 30 ThreePhase 50 37 6 - Lead 60 45 Y-D 75 55 100 75 125 93 150 110 175 130 200 150 14 12 10 8 160 110 80 0 0 0 0 210 150 110 0 0 0 0 600 400 300 210 160 0 0 0 0 0 0 0 0 0 0 0 880 630 460 310 230 190 0 0 0 0 0 0 0 0 0 0 1380 990 730 490 370 300 240 0 0 0 0 0 0 0 0 0 250 180 130 0 0 0 0 340 240 180 130 0 0 0 960 660 480 340 260 210 0 0 0 0 0 0 0 0 0 0 1420 1020 750 510 380 310 250 0 0 0 0 0 0 0 0 0 2220 1590 1170 790 610 490 400 300 0 0 0 0 0 0 0 0 420 300 210 140 120 0 0 550 390 280 190 140 120 0 1510 1030 760 550 410 330 270 210 0 0 0 0 0 0 0 0 2250 1600 1180 810 610 490 410 300 250 0 0 0 0 0 0 0 3490 2520 1860 1270 970 780 645 480 380 330 0 0 0 0 0 0 660 460 340 240 170 140 120 880 630 460 310 230 190 150 2380 1630 1200 880 660 540 430 320 250 0 0 0 0 0 0 0 3540 2530 1870 1270 970 790 640 480 370 320 0 0 0 0 0 0 5520 3970 2920 2010 1540 1240 1020 750 590 500 420 0 0 0 0 0 75 °C INSULATION - AWG COPPER WIRE SIZE 6 4 3 2 1 1030 730 550 370 280 220 180 1380 970 730 490 370 300 240 3730 2560 1870 1380 1050 850 700 510 400 340 290 0 0 0 0 0 5550 3960 2940 2010 1540 1240 1020 750 590 500 420 310 0 0 0 0 8620 6220 4590 3130 2410 1950 1600 1180 960 790 660 400 0 0 0 0 0 00 000 0000 250 3060 2170 1630 1110 850 690 570 4030 2880 2160 1470 1140 910 760 3730 2650 1990 1360 1050 850 700 4930 3510 2640 1800 1390 1120 930 4570 3250 2460 1660 1290 1050 870 6040 4300 3240 2200 1710 1380 1140 5500 3900 2950 2010 1570 1260 1050 7270 5160 3910 2670 2070 1680 1390 6660 4720 3580 2440 1900 1540 1270 8800 6240 4740 3220 2520 2040 1690 7540 5340 4080 2770 2160 1750 1450 9970 7060 5380 3660 2860 2310 1920 7390 5350 4030 3090 2500 2070 1510 1230 1030 855 640 490 420 360 0 9010 6490 4930 3790 3070 2550 1860 1500 1270 1050 760 600 510 440 410 7840 6000 4630 3760 3120 2280 1830 1540 1290 940 730 620 540 480 9390 7260 5640 4560 3780 2760 2220 1870 1570 1140 930 750 660 580 8650 6750 5460 4530 3300 2650 2250 1900 1360 1110 930 780 690 9390 7020 4800 3700 2980 2460 1810 1470 1240 1020 760 590 510 450 0 8620 5890 4560 3670 3040 2230 1810 1530 1260 930 730 630 550 480 7210 5590 4510 3730 2740 2220 1870 1540 1140 880 770 680 590 8850 6870 5550 4590 3370 2710 2310 1890 1410 1110 950 830 730 8290 6700 5550 4060 3280 2770 2280 1690 1330 1140 1000 880 5790 4660 3840 2850 2310 1950 1590 1180 920 800 700 610 7140 5760 4740 3490 2830 2400 1960 1450 1150 990 860 760 8740 7060 5820 4290 3460 2940 2400 1780 1420 1210 1060 930 7150 5260 4260 3600 2950 2190 1740 1480 1300 1140 8670 6340 5130 4330 3570 2650 2100 1780 1570 1370 1620 1150 850 580 450 360 294 2140 1530 1140 780 600 480 390 5800 3960 2890 2140 1630 1320 1090 790 630 540 450 340 0 0 0 0 8620 6150 4570 3130 2410 1950 1600 1180 960 810 660 500 390 0 0 0 2020 1440 1080 730 570 450 370 2680 1900 1420 970 750 600 490 7170 4890 3570 2650 2020 1650 1360 990 810 660 550 420 340 0 0 0 2490 1770 1320 900 690 550 460 3280 2340 1750 1200 910 750 610 8800 6000 4360 3250 2500 2020 1680 1230 990 840 690 520 400 350 0 0 7650 5700 3900 3000 2430 1990 1470 1200 1000 810 610 470 420 0 0 7150 4890 3780 3040 2500 1860 1500 1270 1030 780 600 520 0 0 8910 6090 4710 3790 3120 2310 1870 1590 1290 960 740 650 570 500 MCM COPPER WIRE SIZE 300 350 400 500 4650 3150 2470 1990 1660 5220 3520 2770 2250 1870 5700 3850 3030 2460 2040 6630 4470 3540 2850 2380 8010 6150 4170 3270 2640 2200 8950 6900 4660 3670 2970 2470 9750 7530 5100 4020 3240 2700 8760 5910 4680 3780 3160 9780 7660 6190 5140 3750 3010 2550 2160 1540 1260 1050 970 790 4260 7080 5880 4270 3430 2910 2490 1770 1420 1180 1120 940 9760 7870 6540 4750 3820 3220 2770 1960 1590 1320 1260 1050 8610 7150 5200 4170 3520 3040 2140 1740 1440 1380 1140 9880 8230 5980 4780 4050 3520 2470 1990 1630 1600 1320 8140 6750 4930 3970 3360 2770 2070 1500 1380 1220 1070 7690 5590 4510 3810 3150 2340 1830 1570 1390 1210 8790 6370 5130 4330 3600 2680 2080 1790 1580 1380 5740 4860 4050 3010 2340 2000 1780 1550 6270 5310 4420 3280 2550 2180 1950 1690 7270 6150 5160 3820 2940 2530 2270 1970 7710 6210 5250 4330 3220 2530 2160 1910 1670 8740 7050 5950 4930 3660 2880 2450 2170 1890 8010 6780 5620 4180 3270 2790 2480 2160 8980 7600 6330 4710 3660 3120 2780 2420 9790 8290 6910 5140 3970 3410 3040 2640 9610 8050 5980 4600 3950 3540 3070 Lengths in BOLD only meet the US National Electrical Code ampacity requirements for individual conductors in free air or water. Lengths NOT in bold meet NEC ampacity requirements for either individual conductors or jacketed cable. See page 11 for additional details. 21 !00,)#!4)/. 4HREE 0HASE -OTORS Table 22 Three-Phase Motor Specifications (60 Hz) 3450 rpm TYPE 4" MOTOR MODEL PREFIX MAXIMUM LOAD VOLTS HZ S.F. AMPS WATTS AMPS WATTS LINE TO LINE RESISTANCE OHMS S.F. F.L. LOCKED ROTOR AMPS 234501 200 60 1.6 2.8 585 3.4 860 6.6-8.4 70 64 17.5 N 234511 230 60 1.6 2.4 585 2.9 860 9.5-10.9 70 64 15.2 N 380 60 1.6 1.4 585 2.1 860 23.2-28.6 70 64 9.2 N 234521 460 60 1.6 1.2 585 1.5 860 38.4-44.1 70 64 7.6 N 234531 575 60 1.6 1.0 585 1.2 860 58.0-71.0 70 64 6.1 N 234502 200 60 1.5 3.6 810 4.4 1150 4.6-5.9 73 69 24.6 N 234512 230 60 1.5 3.1 810 3.8 1150 6.8-7.8 73 69 21.4 N 380 60 1.5 1.9 810 2.5 1150 16.6-20.3 73 69 13 N 234522 460 60 1.5 1.6 810 1.9 1150 27.2-30.9 73 69 10.7 N 234532 575 60 1.5 1.3 810 1.6 1150 41.5-50.7 73 69 8.6 N 234503 200 60 1.4 4.5 1070 5.4 1440 3.8-4.5 72 70 30.9 M 234541 234542 RATING HP 1/2 3/4 KW 0.37 0.55 234513 234543 1 0.75 FULL LOAD EFFICIENCY % KVA CODE 230 60 1.4 3.9 1070 4.7 1440 4.9-5.6 72 70 26.9 M 380 60 1.4 2.3 1070 2.8 1440 12.2-14.9 72 70 16.3 M 234523 460 60 1.4 2 1070 2.4 1440 19.9-23.0 72 70 13.5 M 234533 575 60 1.4 1.6 1070 1.9 1440 30.1-36.7 72 70 10.8 M 234504 200 60 1.3 5.8 1460 6.8 1890 2.5-3.0 76 76 38.2 K 234514 230 60 1.3 5 1460 5.9 1890 3.2-4.0 76 76 33.2 K 234544 1.5 1.1 234524 380 60 1.3 3 1460 3.6 1890 8.5-10.4 76 76 20.1 K 460 60 1.3 2.5 1460 3.1 1890 13.0-16.0 76 76 16.6 K 234534 575 60 1.3 2 1460 2.4 1890 20.3-25.0 76 76 13.3 K 234305 200 60 1.25 7.7 1960 9.3 2430 1.8-2.4 76 76 50.3 K 234315 234345 2 1.5 230 60 1.25 6.7 1960 8.1 2430 2.3-3.0 76 76 45.0 K 380 60 1.25 4.1 1960 4.9 2430 6.6-8.2 76 76 26.6 K 234325 460 60 1.25 3.4 1960 4.1 2430 9.2-12.0 76 76 22.5 K 234335 575 60 1.25 2.7 1960 3.2 2430 14.6-18.7 76 76 17.8 K 234306 200 60 1.15 10.9 2920 12.5 3360 1.3-1.7 77 77 69.5 K 234316 230 60 1.15 9.5 2920 10.9 3360 1.8-2.2 77 77 60.3 K 380 60 1.15 5.8 2920 6.6 3360 4.7-6.0 77 77 37.5 K 460 60 1.15 4.8 2920 5.5 3360 7.2-8.8 77 77 31.0 K 234346 3 2.2 234326 234336 575 60 1.15 3.8 2920 4.4 3360 11.4-13.9 77 77 25.1 K 234307 200 60 1.15 18.3 4800 20.5 5500 .68-.83 78 78 116 K 234317 234347 5 3.7 230 60 1.15 15.9 4800 17.8 5500 .91-1.1 78 78 102 K 380 60 1.15 9.6 4800 10.8 5500 2.6-3.2 78 78 60.2 K 234327 460 60 1.15 8.0 4800 8.9 5500 3.6-4.4 78 78 53.7 K 234337 575 60 1.15 6.4 4800 7.1 5500 5.6-6.9 78 78 41.8 K 234308 200 60 1.15 26.5 7150 30.5 8200 .43-.53 78 78 177 K 234318 230 60 1.15 23.0 7150 26.4 8200 .60-.73 78 78 152 K 234348 7.5 5.5 234328 380 60 1.15 13.9 7150 16.0 8200 1.6-2.0 78 78 92.7 K 460 60 1.15 11.5 7150 13.2 8200 2.3-2.8 78 78 83.8 K 234338 575 60 1.15 9.2 7150 10.6 8200 3.6-4.5 78 78 64.6 K 234549 380 60 1.15 19.3 10000 21.0 11400 1.2-1.6 75 75 140 L 460 60 1.15 15.9 10000 17.3 11400 1.8-2.3 75 75 116.0 L 575 60 1.15 12.5 10000 13.6 11400 2.8-3.5 75 75 92.8 L 234595 234598 10 7.5 22 !00,)#!4)/. 4HREE 0HASE -OTORS Table 23 Three-Phase Motor Fuse Sizing TYPE 4" MOTOR MODEL PREFIX CIRCUIT BREAKERS OR FUSE AMPS (MAXIMUM PER NEC) (TYPICAL SUBMERSIBLE) VOLTS STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER 234501 200 234511 230 10 5 8 10 4 15 8 4.5 6 8 4 15 380 5 2.5 4 5 2 15 234521 460 4 2.25 3 4 2 15 234531 575 3 1.8 3 3 1.4 15 234502 200 15 7 10 12 5 15 234512 230 10 5.6 8 10 5 15 380 6 3.5 5 6 3 15 234522 460 5 2.8 4 5 3 15 234532 575 4 2.5 4 4 1.8 15 234503 200 15 8 15 15 6 15 234513 230 15 7 10 12 6 15 380 8 4.5 8 8 4 15 234523 460 6 3.5 5 6 3 15 234533 575 5 2.8 4 5 2.5 15 234504 200 20 12 15 20 8 15 234514 230 15 9 15 15 8 15 380 10 5.6 8 10 4 15 234524 460 8 4.5 8 8 4 15 234534 575 6 3.5 5 6 3 15 234305 200 25 15 20 25 11 20 234315 230 25 12 20 25 10 20 380 15 8 15 15 6 15 234325 460 15 6 10 11 5 15 234335 575 10 5 8 10 4 15 234306 200 35 20 30 35 15 30 234316 230 30 17.5 25 30 12 25 380 20 12 15 20 8 15 234326 460 15 9 15 15 6 15 234336 575 15 7 10 11 5 15 234307 200 60 35 50 60 25 50 234317 230 50 30 40 45 20 40 380 30 17.5 25 30 12 25 234327 460 25 15 20 25 10 20 234337 575 20 12 20 20 8 20 234308 200 90 50 70 80 35 70 234318 230 80 45 60 70 30 60 380 45 25 40 40 20 40 234328 460 40 25 30 35 15 30 234338 575 30 17.5 25 30 12 25 234349 380 70 40 60 60 25 60 234329 460 60 30 45 50 25 45 234339 575 45 25 35 40 20 35 380 70 35 60 60 25 60 234595 460 60 30 45 50 25 45 234598 575 45 25 35 40 20 35 234541 234542 234543 234544 234345 234346 234347 234348 234549 23 CIRCUIT BREAKERS OR FUSE AMPS RATING HP 1/2 3/4 1 1.5 2 3 5 7.5 10 KW 0.37 0.55 0.75 1.1 1.5 2.2 3.7 5.5 7.5 !00,)#!4)/. 4HREE 0HASE -OTORS Table 24 Three-Phase Motor Specifications (60 Hz) 3450 rpm TYPE 6" STD. MOTOR MODEL PREFIX MAXIMUM LOAD VOLTS HZ S.F. AMPS WATTS AMPS WATTS LINE TO LINE RESISTANCE OHMS 236650 200 60 1.15 17.5 4700 20.0 5400 .77-.93 79 79 99 H 236600 230 60 1.15 15 4700 17.6 5400 1.0-1.2 79 79 86 H 236660 RATING HP 5 KW 3.7 236610 FULL LOAD EFFICIENCY % S.F. F.L. LOCKED ROTOR AMPS KVA CODE 380 60 1.15 9.1 4700 10.7 5400 2.6-3.2 79 79 52 H 460 60 1.15 7.5 4700 8.8 5400 3.9-4.8 79 79 43 H 236620 575 60 1.15 6 4700 7.1 5400 6.3-7.7 79 79 34 H 236651 200 60 1.15 25.1 7000 28.3 8000 .43-.53 80 80 150 H 236601 236661 7.5 5.5 230 60 1.15 21.8 7000 24.6 8000 .64-.78 80 80 130 H 380 60 1.15 13.4 7000 15 8000 1.6-2.1 80 80 79 H 236611 460 60 1.15 10.9 7000 12.3 8000 2.4-2.9 80 80 65 H 236621 575 60 1.15 8.7 7000 9.8 8000 3.7-4.6 80 80 52 H 236652 200 60 1.15 32.7 9400 37 10800 .37-.45 79 79 198 H 236602 230 60 1.15 28.4 9400 32.2 10800 .47-.57 79 79 172 H 236662 10 7.5 236612 380 60 1.15 17.6 9400 19.6 10800 1.2-1.5 79 79 104 H 460 60 1.15 14.2 9400 16.1 10800 1.9-2.4 79 79 86 H 236622 575 60 1.15 11.4 9400 12.9 10800 3.0-3.7 79 79 69 H 236653 200 60 1.15 47.8 13700 54.4 15800 .24-.29 81 81 306 H 236603 236663 15 11 230 60 1.15 41.6 13700 47.4 15800 .28-.35 81 81 266 H 380 60 1.15 25.8 13700 28.9 15800 .77-.95 81 81 161 H 236613 460 60 1.15 20.8 13700 23.7 15800 1.1-1.4 81 81 133 H 236623 575 60 1.15 16.6 13700 19 15800 1.8-2.3 81 81 106 H 236654 200 60 1.15 61.9 18100 69.7 20900 .16-.20 82 82 416 J 236604 230 60 1.15 53.8 18100 60.6 20900 .22-.26 82 82 362 J 236664 20 15 236614 380 60 1.15 33 18100 37.3 20900 .55-.68 82 82 219 J 460 60 1.15 26.9 18100 30.3 20900 .8-1.0 82 82 181 J 236624 575 60 1.15 21.5 18100 24.2 20900 1.3-1.6 82 82 145 J 236655 200 60 1.15 77.1 22500 86.3 25700 .12-.15 83 83 552 J J 236605 236665 25 18.5 236615 230 60 1.15 67 22500 75 25700 .15-.19 83 83 480 380 60 1.15 41 22500 46 25700 .46-.56 83 83 291 J 460 60 1.15 33.5 22500 37.5 25700 .63-.77 83 83 240 J 236625 575 60 1.15 26.8 22500 30 25700 1.0-1.3 83 83 192 J 236656 200 60 1.15 90.9 26900 104 31100 .09-.11 83 83 653 J 236606 236666 30 22 230 60 1.15 79 26900 90.4 31100 .14-.17 83 83 568 J 380 60 1.15 48.8 26900 55.4 31100 .35-.43 83 83 317 J 236616 460 60 1.15 39.5 26900 45.2 31100 .52-.64 83 83 284 J 236626 575 60 1.15 31.6 26900 36.2 31100 .78-.95 83 83 227 J 236667 236617 40 30 380 60 1.15 66.5 35600 74.6 42400 .26-.33 83 83 481 J 460 60 1.15 54.9 35600 61.6 42400 .34-.42 83 83 397 J 236627 575 60 1.15 42.8 35600 49.6 42400 .52-.64 83 83 318 H 236668 380 60 1.15 83.5 45100 95 52200 .21-.25 82 83 501 H 236618 460 60 1.15 67.7 45100 77 52200 .25-.32 82 83 414 H 236628 575 60 1.15 54.2 45100 61.6 52200 .40-.49 82 83 331 H 276668 50 37 276618 380 60 1.15 82.4 45100 94.5 52200 .21 - .25 82 83 501 H 460 60 1.15 68.1 45100 78.1 52200 .25 - .32 82 83 414 H 276628 575 60 1.15 54.5 45100 62.5 52200 .40 - .49 82 83 331 H 236669 380 60 1.15 98.7 53500 111 61700 .15-.18 84 84 627 H 236619 460 60 1.15 80.5 53500 91 61700 .22-.27 84 84 518 H 236629 575 60 1.15 64.4 53500 72.8 61700 .35-.39 84 84 414 H 276669 60 45 380 60 1.15 98.1 53500 111.8 61700 .15 - .18 84 84 627 H 276619 460 60 1.15 81.0 53500 92.3 61700 .22 - .27 84 84 518 H 276629 575 60 1.15 64.8 53500 73.9 61700 .35 - .39 84 84 414 H Model numbers above are for three-lead motors. Six-lead motors with different model numbers have the same running performance, but when Wye connected for starting have locked rotor amps 33% of the values shown. Six-lead individual phase resistance = table X 1.5. 24 !00,)#!4)/. 4HREE 0HASE -OTORS Table 25 6” Three-Phase Motor Specifications (60 Hz) 3450 rpm TYPE 6" HITEMP 90 °C MOTOR MODEL PREFIX MAXIMUM LOAD VOLTS HZ S.F. AMPS WATTS AMPS WATTS LINE TO LINE RESISTANCE OHMS 276650 200 60 1.15 17.2 5200 19.8 5800 .53 - .65 73 72 124 K 276600 230 60 1.15 15.0 5200 17.2 5800 .68 - .84 73 72 108 K 276660 RATING HP 5 KW 3.7 276610 FULL LOAD EFFICIENCY % S.F. F.L. LOCKED ROTOR AMPS KVA CODE 380 60 1.15 9.1 5200 10.4 5800 2.0 - 2.4 73 72 66.0 K 460 60 1.15 7.5 5200 8.6 5800 2.8 - 3.4 73 72 54.0 K 276620 575 60 1.15 6.0 5200 6.9 5800 4.7 - 5.7 73 72 43.0 K 276651 200 60 1.15 24.8 7400 28.3 8400 .30 - .37 77 76 193 K 276601 276661 7.5 5.5 230 60 1.15 21.6 7400 24.6 8400 .41 - .50 77 76 168 K 380 60 1.15 13.1 7400 14.9 8400 1.1 - 1.4 77 76 102 K 276611 460 60 1.15 10.8 7400 12.3 8400 1.7 - 2.0 77 76 84.0 K 276621 575 60 1.15 8.6 7400 9.9 8400 2.6 - 3.2 77 76 67.0 K 276652 200 60 1.15 32.0 9400 36.3 10700 .21 - .26 80 79 274 L 276602 230 60 1.15 27.8 9400 31.6 10700 .28 - .35 80 79 238 L 276662 10 7.5 276612 380 60 1.15 16.8 9400 19.2 10700 .80 - .98 80 79 144 L 460 60 1.15 13.9 9400 15.8 10700 1.2 - 1.4 80 79 119 L 276622 575 60 1.15 11.1 9400 12.7 10700 1.8 - 2.2 80 79 95.0 L 276653 200 60 1.15 48.5 14000 54.5 15900 .15 - .19 81 80 407 L 276603 276663 15 11 230 60 1.15 42.2 14000 47.4 15900 .19 - .24 81 80 354 L 380 60 1.15 25.5 14000 28.7 15900 .52 - .65 81 80 214 L 276613 460 60 1.15 21.1 14000 23.7 15900 .78 - .96 81 80 177 L 276623 575 60 1.15 16.9 14000 19.0 15900 1.2 - 1.4 81 80 142 L 276654 200 60 1.15 64.9 18600 73.6 21300 .10 - .12 80 80 481 K 276604 230 60 1.15 56.4 18600 64.0 21300 .14 - .18 80 80 418 K 276664 20 15 276614 380 60 1.15 34.1 18600 38.8 21300 .41 - .51 80 80 253 K 460 60 1.15 28.2 18600 32.0 21300 .58 - .72 80 80 209 K K 276624 575 60 1.15 22.6 18600 25.6 21300 .93 - 1.15 80 80 167 276655 200 60 1.15 80.0 22600 90.6 25800 .09 - .11 83 82 665 L 276605 230 60 1.15 69.6 22600 78.8 25800 .11 - .14 83 82 578 L 380 60 1.15 42.1 22600 47.7 25800 .27 - .34 83 82 350 L 460 60 1.15 34.8 22600 39.4 25800 .41 - .51 83 82 289 L 276665 25 18.5 276615 276625 575 60 1.15 27.8 22600 31.6 25800 .70 - .86 83 82 231 L 276656 200 60 1.15 95.0 28000 108.6 31900 .07 - .09 81 80 736 K 276606 276666 30 22 230 60 1.15 82.6 28000 94.4 31900 .09 - .12 81 80 640 K 380 60 1.15 50.0 28000 57.2 31900 .23 - .29 81 80 387 K 276616 460 60 1.15 41.3 28000 47.2 31900 .34 - .42 81 80 320 K 276626 575 60 1.15 33.0 28000 37.8 31900 .52 - .65 81 80 256 K 276667 276617 276627 40 30 380 60 1.15 67.2 35900 76.0 42400 .18 - .23 84 83 545 L 460 60 1.15 55.4 35900 62.8 42400 .23 - .29 84 83 450 L 575 60 1.15 45.2 35900 50.2 42400 .34 - .43 84 83 360 L Model numbers above are for three-lead motors. Six-lead motors with different model numbers have the same running performance, but when Wye connected for starting have locked rotor amps 33% of the values shown. Six-lead individual phase resistance = table X 1.5. 25 !00,)#!4)/. 4HREE 0HASE -OTORS Table 26 Three-Phase Motor Fuse Sizing TYPE 6" STD. & HITEMP MOTOR MODEL PREFIX 236650 236600 236660 236610 236620 236651 236601 236661 236611 236621 236652 236602 276650 276600 276660 276610 276620 276651 276601 276661 276611 276621 276652 276602 236662 236612 236622 236653 236603 236663 236613 236623 236654 236604 236664 236614 236624 236655 236605 236665 236615 236625 236656 236606 236666 236616 236626 236667 236617 236627 236668 236618 236628 236669 236619 236629 276662 276612 276622 276653 276603 276663 276613 276623 276654 276604 276664 276614 276624 276655 276605 276665 276615 276625 276656 276606 276666 276616 276626 276667 276617 276627 276668 276618 276628 276669 276619 276629 CIRCUIT BREAKERS OR FUSE AMPS CIRCUIT BREAKERS OR FUSE AMPS (MAXIMUM PER NEC) (TYPICAL SUBMERSIBLE) RATING HP KW 5 3.7 7.5 5.5 10 7.5 15 11 20 15 25 18.5 30 22 40 30 50 37 60 45 VOLTS STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER 200 230 380 460 575 200 230 380 460 575 200 230 60 45 30 25 20 80 70 45 35 30 100 90 35 30 17.5 15 12 45 40 25 20 17.5 60 50 45 40 25 20 15 70 60 35 30 25 90 80 50 45 30 25 20 80 70 40 35 25 100 90 25 20 12 10 8 35 30 20 15 11 45 40 45 40 25 20 15 70 60 35 30 25 90 80 380 460 575 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 380 460 575 380 460 575 380 460 575 60 45 35 150 150 80 70 60 200 175 100 90 70 250 225 125 110 90 300 250 150 125 100 200 175 150 250 225 175 300 250 200 35 25 20 90 80 50 40 30 110 100 60 50 40 150 125 80 60 50 175 150 90 70 60 125 100 80 150 125 100 175 150 125 45 40 30 125 110 70 60 45 175 150 90 70 60 200 175 110 90 70 250 225 125 110 90 175 150 110 225 175 150 250 225 175 50 45 35 150 125 80 60 50 175 175 100 80 70 225 200 125 100 80 300 250 150 125 100 200 175 125 250 200 175 300 250 200 25 20 15 60 60 35 30 25 80 70 45 35 30 100 90 50 45 35 125 100 60 50 40 90 70 60 110 90 70 125 100 80 45 40 30 125 110 70 60 45 175 150 90 70 60 200 175 110 90 70 250 200 125 100 80 175 150 110 225 175 150 250 225 175 26 !00,)#!4)/. 4HREE 0HASE -OTORS Table 27 Three-Phase Motor Specifications (60 Hz) 3525 rpm TYPE 8" STD. MOTOR MODEL PREFIX 239660 239600 239610 239661 239601 239611 239662 239602 239612 239663 239603 239613 239664 239604 239614 239165 239105 239115 239166 239106 239116 239167 239107 239117 239168 239108 239118 HP KW 40 30 50 37 60 45 75 55 100 75 125 93 150 110 175 130 200 150 MAXIMUM LOAD VOLTS HZ S.F. AMPS KILOWATTS AMPS KILOWATTS LINE TO LINE RESISTANCE OHMS 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 64 53 42 79 64 51 92 76 61 114 94 76 153 126 101 202 167 134 235 194 155 265 219 175 298 246 197 35 35 35 43 43 43 52 52 52 64 64 64 85 85 85 109 109 109 128 128 128 150 150 150 169 169 169 72 60 48 88 73 59 104 86 69 130 107 86 172 142 114 228 188 151 266 219 176 302 249 200 342 282 226 40 40 40 49 49 49 60 60 60 73.5 73.5 73.5 97.5 97.5 97.5 125 125 125 146 146 146 173 173 173 194 194 194 .16-.20 .24-.30 .39-.49 .12-.16 .18-.22 .28-.34 .09-.11 .14-.17 .22-.28 .06-.09 .10-.13 .16-.21 .05-.06 .07-.09 .11-.13 .03-.04 .05-.07 .08-.11 .02-.03 .04-.05 .06-.08 .02-.04 .04-.05 .06-.08 .02-.03 .03-.05 .05-.07 RATING FULL LOAD EFFICIENCY % S.F. 86 86 86 87 87 87 88 88 88 88 88 88 89 89 89 87 87 87 88 88 88 88 88 88 88 88 88 F.L. LOCKED ROTOR AMPS KVA CODE 86 86 86 87 87 87 87 87 87 88 88 88 89 89 89 86 86 86 87 87 87 88 88 88 88 88 88 479 396 317 656 542 434 797 658 526 1046 864 691 1466 1211 969 1596 1318 1054 1961 1620 1296 1991 1645 1316 2270 1875 1500 J J J K K K K K K L L L L L L K K K K K K J J J J J J KVA CODE M M M M M M N N N L L L M M M L L L K K K Table 27A 8” Three-Phase Motor Specifications (60 Hz) 3525 rpm TYPE 8" HITEMP MOTOR MODEL PREFIX 279160 279100 279110 279161 279101 279111 279162 279102 279112 279163 279103 279113 279164 279104 279114 279165 279105 279115 279166 279106 279116 HP KW 40 30 50 37 60 45 75 56 100 75 125 93 150 110 MAXIMUM LOAD VOLTS HZ S.F. AMPS KILOWATTS AMPS KILOWATTS LINE TO LINE RESISTANCE OHMS 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 1.15 69.6 57.5 46.0 84.3 69.6 55.7 98.4 81.3 65.0 125 100 80 159 131 105 195 161 129 235 194 155 38 38 38 47 47 47 55 55 55 68 68 68 88 88 88 109 109 109 133 133 133 78.7 65.0 52.0 95.4 78.8 63.0 112 92.1 73.7 141 114 92 181 149 119 223 184 148 269 222 178 43 43 43 53 53 53 62 62 62 77 77 77 100 100 100 125 125 125 151 151 151 .11 - .14 .16 - .19 .25 - .31 .07 - .09 .11 - .14 .18 - .22 .06 - .07 .09 - .11 .13 - .16 .05 - .06 .07 - .09 .11 - .14 .04 - .05 .05 - .07 .08 - .10 .03 - .04 .04 - .06 .07 - .09 .02 - .03 .03 - .05 .05 - .07 RATING FULL LOAD EFFICIENCY % S.F. F.L. LOCKED ROTOR AMPS 79 79 79 81 81 81 83 83 83 83 83 83 86 86 86 86 86 86 85 85 85 78 78 78 80 80 80 82 82 82 82 82 82 85 85 85 85 85 85 84 84 84 616 509 407 832 687 550 1081 893 715 1175 922 738 1508 1246 997 1793 1481 1185 2012 1662 1330 Model numbers above are for three-lead motors. Six-lead motors with different model numbers have the same running performance, but when Wye connected for starting have locked rotor amps 33% of the values shown. Six-lead individual phase resistance = table X 1.5. 27 !00,)#!4)/. 4HREE 0HASE -OTORS Table 28 Three-Phase Motor Fuse Sizing TYPE 8" STD. MOTOR MODEL PREFIX 239660 239600 239610 239661 239601 239611 239662 239602 239612 239663 239603 239613 239664 239604 239614 239165 239105 239115 239166 239106 239116 239167 239107 239117 239168 239108 239118 CIRCUIT BREAKERS OR FUSE AMPS RATING HP KW 40 30 50 37 60 45 75 55 100 75 125 93 150 110 175 130 200 150 CIRCUIT BREAKERS OR FUSE AMPS (MAXIMUM PER NEC) (TYPICAL SUBMERSIBLE) VOLTS STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER 380 460 575 380 460 575 380 460 575 380 460 575 380 200 175 150 250 200 175 300 250 200 350 300 250 500 125 100 80 150 125 90 175 150 110 200 175 150 275 175 150 110 200 175 150 250 200 175 300 250 200 400 200 175 125 225 200 150 300 225 175 350 300 225 450 80 70 60 100 80 70 125 100 80 150 125 100 200 175 150 110 200 175 150 250 200 175 300 250 200 400 460 575 380 460 575 380 460 575 380 460 575 380 460 575 400 350 700 500 450 800 600 500 800 700 600 1000 800 600 225 200 400 300 250 450 350 300 500 400 350 600 450 350 350 300 600 450 350 600 500 400 700 600 450 800 700 500 400 300 600 500 400 700 600 450 800 700 600 1000 800 600 175 125 250 225 175 300 250 200 350 300 225 400 350 250 350 300 600 450 350 600 500 400 700 600 450 800 700 500 Table 28A 8” Three-Phase Motor Fuse Sizing TYPE 8" HITEMP MOTOR MODEL PREFIX 279160 279100 279110 279161 279101 279111 279162 279102 279112 279163 279103 279113 279164 279104 279114 279165 279105 279115 279166 279106 279116 CIRCUIT BREAKERS OR FUSE AMPS RATING HP KW 40 30 50 37 60 45 75 56 100 75 125 93 150 110 CIRCUIT BREAKERS OR FUSE AMPS (MAXIMUM PER NEC) (TYPICAL SUBMERSIBLE) VOLTS STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER STANDARD FUSE DUAL ELEMENT TIME DELAY FUSE CIRCUIT BREAKER 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 225 175 150 250 200 175 300 275 200 400 300 275 500 400 350 700 500 450 800 600 500 125 110 90 150 125 100 175 150 125 200 175 150 300 250 200 400 300 250 450 350 300 175 150 125 225 175 150 250 225 175 350 275 225 450 350 300 600 450 350 600 500 400 200 175 125 225 200 150 300 250 175 350 300 225 450 400 300 600 500 400 700 600 450 90 70 60 110 90 70 125 100 80 150 125 100 200 175 125 250 225 175 300 250 200 175 150 125 225 175 150 250 225 175 350 275 225 450 350 300 600 450 350 600 500 400 28 !00,)#!4)/. 4HREE 0HASE -OTORS /VERLOAD 0ROTECTION OF 4HREE 0HASE 3UBMERSIBLE -OTORS The characteristics of submersible motors are different than standard motors and special overload protection is required. All heaters and amp settings shown are based on total line amps. When determining amperage settings or making heater selections for a six-lead motor with a Wye-Delta starter, divide motor amps by 1.732. If the motor is locked, the overload protection must trip within 10 seconds to protect the motor windings. Subtrol/ SubMonitor, a Franklin-approved adjustable overload relay, or a Franklin-approved fixed heater must be used. Pages 29, 30 and 31 list the correct selection and settings for some manufacturers. Approval for other manufacturers’ types not listed may be requested by calling Franklin’s Submersible Service Hotline at 800-348-2420. Fixed heater overloads must be the ambient-compensated quick-trip type to maintain protection at high and low air temperatures. Refer to notes on page 30. Table 29 - 60 Hz 4" Motors HP KW 1/2 0.37 3/4 0.55 1 0.75 1.5 1.1 2 1.5 3 2.2 5 3.7 7.5 5.5 10 7.5 29 VOLTS NEMA STARTER SIZE 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 200 230 380 460 575 380 460 575 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 0 0 0 00 00 0 0 0 0 0 1 1 0 0 0 1 1 1 1 1 1 1 1 HEATERS FOR OVERLOAD RELAYS FURNAS (NOTE 1) K31 K28 K22 K34 K32 K27 K23 K21 K37 K36 K28 K26 K23 K42 K39 K32 K29 K26 K50 K49 K36 K33 K29 K55 K52 K41 K37 K34 K62 K61 K52 K49 K42 K68 K67 K58 K55 K52 K62 K60 K56 G.E. (NOTE 2) L380A L343A L211A L174A L510A L420A L282A L211A L193A L618A L561A L310A L282A L211A L750A L680A L420A L343A L282A L111B L910A L561A L463A L380A L147B L122B L750A L618A L510A L241B L199B L122B L100B L825A L332B L293B L181B L147B L122B L241B L199B L165B ADJUSTABLE RELAYS (NOTE 3) SET 3.2 2.7 1.7 1.4 1.2 4.1 3.5 2.3 1.8 1.5 5.0 4.4 2.6 2.2 1.8 6.3 5.5 3.3 2.8 2.2 8.6 7.5 4.6 3.8 3.0 11.6 10.1 6.1 5.1 4.1 19.1 16.6 10.0 8.3 6.6 28.4 24.6 14.9 12.3 9.9 19.5 16.1 12.9 #LASS 0ROTECTION 2EQUIRED MAX. 3.4 2.9 1.8 1.5 1.3 4.4 3.8 2.5 1.9 1.6 5.4 4.7 2.8 2.4 1.9 6.8 5.9 3.6 3.0 2.4 9.3 8.1 4.9 4.1 3.2 12.5 10.9 6.6 5.5 4.4 20.5 17.8 10.8 8.9 7.1 30.5 26.4 16.0 13.2 10.6 21.0 17.3 13.6 !00,)#!4)/. 4HREE 0HASE -OTORS Table 30 - 60 Hz 6" Standard & Hi-Temp Motors HP 5 7.5 10 15 20 25 30 40 50 60 KW 3.7 5.5 7.5 11 15 18.5 22 30 37 45 VOLTS NEMA STARTER SIZE 200 230 HEATERS FOR OVERLOAD RELAYS ADJUSTABLE RELAYS (NOTE 3) FURNAS (NOTE 1) G.E. (NOTE 2) SET 1 K61 L220B 17.6 19.1 1 K61 L199B 15.4 16.6 10.1 MAX. 380 0 K52 L122B 9.4 460 0 K49 L100B 7.7 8.3 575 0 K42 L825A 6.1 6.6 200 1 K67 L322B 26.3 28.3 230 1 K64 L293B 22.9 24.6 380 1 K57 L165B 13.9 14.9 460 1 K54 L147B 11.4 12.3 575 1 K52 L111B 9.1 9.8 200 2(1) K72 L426B 34.4 37.0 230 2(1) K70 L390B 29.9 32.2 380 1 K61 L220B 18.1 19.5 460 1 K58 L181B 15.0 16.1 575 1 K55 L147B 12.0 12.9 200 3(1) K76 L650B 50.7 54.5 230 2 K75 L520B 44.1 47.4 380 2(1) K68 L322B 26.7 28.7 460 2(1) K64 L265B 22.0 23.7 575 2(1) K61 L220B 17.7 19.0 200 3 K78 L787B 64.8 69.7 230 3(1) K77 L710B 56.4 60.6 380 2 K72 L426B 34.1 36.7 460 2 K69 L352B 28.2 30.3 575 2 K64 L393B 22.7 24.4 200 3 K86 L107C 80.3 86.3 230 3 K83 L866B 69.8 75.0 380 2 K74 L520B 42.2 45.4 460 2 K72 L426B 34.9 37.5 575 2 K69 L352B 27.9 30.0 200 4(1) K88 L126C 96.7 104.0 230 3 K87 L107C 84.1 90.4 380 3(1) K76 L650B 50.9 54.7 460 3(1) K74 L520B 42.0 45.2 575 3(1) K72 L390B 33.7 36.2 380 3 K83 L866B 69.8 75.0 460 3 K77 L710B 57.7 62.0 575 3 K74 L593B 46.1 49.6 380 3 K87 L107C 86.7 93.2 460 3 K83 L950B 71.6 77.0 575 3 K77 L710B 57.3 61.6 380 4(1) K89 L126C 102.5 110.2 460 4(1) K87 L107C 84.6 91.0 575 4(1) K78 L866B 67.7 72.8 Footnotes for Tables 29, 30, and 31 NOTE 1: Furnas intermediate sizes between NEMA starter sizes apply where (1) is shown in tables, size 1.75 replacing 2, 2.5 replacing 3, 3.5 replacing 4, and 4.5 replacing 5. Heaters were selected from Catalog 294, table 332 and table 632 (starter size 00, size B). Size 4 starters are heater type 4 (JG). Starters using these heater tables include classes 14, 17 and 18 (inNOVA), classes 36 and 37 (reduced voltage), and classes 87, 88 and 89 (pump and motor control centers). Overload relay adjustments should be set no higher than 100% unless necessary to stop nuisance tripping with measured amps in all lines below nameplate maximum. Heater selections for class 16 starters (Magnetic Definite Purpose) will be furnished upon request. NOTE 2: General Electric heaters are type CR123 usable only on type CR124 overload relays and were selected from Catalog GEP-126OJ, page 184. Adjustment should be set no higher than 100%, unless necessary to stop nuisance tripping with measured amps in all lines below nameplate maximum. NOTE 3: Adjustable overload relay amp settings apply to approved types listed. Relay adjustment should be set at the specified SET amps. Only if tripping occurs with amps in all lines measured to be within nameplate maximum amps should the setting be increased, not to exceed the MAX value shown. NOTE 4: Heaters shown for ratings requiring NEMA size 5 or 6 starters are all used with current transformers per manufacturer standards. Adjustable relays may or may not use current transformers depending on design. 30 !00,)#!4)/. 4HREE 0HASE -OTORS Table 31 - 60 Hz 8" Motors MOTOR MODEL PREFIX 239660 239600 239610 239661 239601 239611 239662 239602 239612 239663 239603 239613 239664 239604 239614 239165 239105 239115 239166 239106 239116 239167 239107 239117 239168 239108 239118 HP KW 40 30 50 37 60 45 75 55 100 75 125 93 150 110 175 130 200 150 NEMA VOLTS STARTER SIZE 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 3 3 3 3 3 3 4(1) 4(1) 4(1) 4 4(1) 4(1) 5(1) 4 4 5 5(1) 5(1) 5 5(1) 5(1) 6 5 5 6 5 5 Table 31A - 60 Hz 8" Hi-Temp 75°C Motors HEATERS FOR OVERLOAD RELAYS FURNAS (NOTE 1) K78 K77 K73 K86 K78 K77 K89 K86 K78 K92 K89 K85 K28 K92 K90 K32 K29 K26 K32 K28 K26 K33 K31 K27 K33 K32 G.E. (NOTE 2) L866B L710B L520B L107C L866B L710B L126C L107C L787B L142C L126C L950C L100B L155C L142C L135B L111B L825A L147B L122B L100B L147B L111B L165B L135B ADJUSTABLE RELAYS (NOTE 3) SET 68 56 45 81 68 56 101 83 64 121 100 79 168 134 108 207 176 140 248 206 165 270 233 186 316 266 213 MAX. 73 60 48 87 73 60 108 89 69 130 107 85 181 144 116 223 189 150 267 221 177 290 250 200 340 286 229 MOTOR MODEL PREFIX 279160 279100 279110 279161 279101 279111 279162 279102 279112 279163 279103 279113 279164 279104 279114 279165 279105 279115 279166 279106 279116 HP KW 40 30 50 37 60 45 75 56 100 75 125 93 150 110 NEMA VOLTS STARTER SIZE 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 380 460 575 3 3 3 3 3 3 4(1) 4(1) 4(1) 4 4(1) 4(1) 5(1) 5(1) 4 5 5(1) 5(1) 5 5(1) 5(1) HEATERS FOR OVERLOAD RELAYS FURNAS (NOTE 1) K83 K77 K74 K87 K83 K77 K89 K87 K78 K92 K89 K87 K28 K26 K90 K32 K29 K26 K32 K28 G.E. (NOTE 2) L866B L710B L593B L107C L866B L710B L126C L107C L866B L155C L126C L950C L100B L825A L142C L135B L111B L825A L147B L122B L100B ADJUSTABLE RELAYS (NOTE 3) SET 73 60 48 89 73 59 104 86 69 131 106 86 168 139 111 207 171 138 250 206 166 MAX. 79 65 52 95 79 63 112 92 74 141 114 92 181 149 119 223 184 148 269 222 178 Note: Other relay types from these and other manufacturers may or may not provide acceptable protection, and they should not be used without approval of Franklin Electric. Some approved types may only be available for part of the listed motor ratings. When relays are used with current transformers, relay setting is the specified amps divided by the transformer ratio. Recommended Adjustable Overload Relays Advance Controls: MDR3 Overload Lovato: RC9, RC22, RC80, RF9, RF25 & RF95 AEG Series: B17S, B27S, B27-2 Matsushita: FKT-15N, 15GN, 15E, 15GE, FT-15N, FHT-15N ABB Type: RVH 40, RVH65, RVP160, T25DU, T25CT, TA25DU Mitsubishi: ET, TH-K12ABKP, TH-K20KF, TH-K20KP, TH-K20TAKF, TH-K60KF, TH-K60TAKF AGUT: MT03, R1K1, R1L0, R1L3, TE set Class 5 Allen Bradley: Bulletin 193, SMP-Class 10 only Automatic Switch Types: DQ, LR1-D, LR1-F, LR2 Class 10 Benshaw: RSD6 (Class 10) Soft Start Bharita C-H: MC 305 ANA 3 Clipsal: 6CTR, 6MTR Cutler-Hammer: C316F, C316P, C316S, C310-set at 6 sec max, Advantage Class10 Fanal Types: K7 or K7D through K400 Franklin Electric: Subtrol-Plus, SubMonitor Fuji Types: TR-OQ, TR-OQH, TR-2NQ, TR- 3NQ, TR-4NQ, TR-6NQ, RCa 3737-ICQ & ICQH Furnas Types: US15 48AG & 48BG, 958L, ESP100-Class 10 only, 3RB10-Class 10 General Electric: CR4G, CR7G, RT*1, RT*2, RTF3, RT*4, CR324X-Class 10 only Kasuga: RU Set Operating Time Code = 10 & time setting 6 sec max Klockner-Moeller Types: ZOO, Z1, Z4, PKZM1, PKZM3 & PKZ2 31 Omron: K2CM Set Operating Timing Code = 10 & time setting 6 sec max, SE-KP24E time setting 6 sec max Riken: PM1, PM3 Samwha: EOCRS Set for Class 5, EOCR-ST, EOCR-SE, EOCR-AT time setting 6 sec max Siemens Types: 3UA50, -52, -54, -55, -58, -59, -60, -61, -62, -66, -68, -70, 3VUI3, 3VE, 3UB (Class 5) Sprecher and Schuh Types: CT, CT1, CTA 1, CT3K, CT3-12 thru CT3-42, KTA3, CEF1 & CET3 set at 6 sec max, CEP 7 Class 10, CT4, 6, & 7, CT3, KT7 Square D/Telemecanique: Class 9065 Types: TD, TE, TF, TG, TJ, TK, TR, TJE &TJF (Class 10), LR1-D, LR1-F, LR2 Class 10, Types 18A, 32A, SS-Class 10, SR-Class 10 and 63-A-LB Series. Integral 18,32,63, GV2-L, GV2-M, GV2-P, GV3-M (1.6-10 amp only) LR9D, SF Class 10, ST Class 10, LT6 (Class 5 or 10), LRD (Class 10), Motor Logic (Class10) Toshiba Type: 2E RC820, set at 8 sec max. WEG: RW2 Westinghouse Types: FT13, FT23, FT33, FT43, K7D, K27D, K67D, Advantage (Class 10), MOR, IQ500 (Class 5) Westmaster: OLWROO and OLWTOO suffix D thru P 35"-%23)",% 05-0 )NSTALLATION #HECK ,IST 1. Motor Inspection A. Verify that the model, hp or kW, voltage, phase and hertz on the motor nameplate match the installation requirements. B. Check that the motor lead assembly is not damaged. C. Measure insulation resistance using a 500 or 1000 volt DC megohmmeter from each lead wire to the motor frame. Resistance should be at least 200 megohms without drop cable. D. Keep a record of motor model number, hp or kW, voltage, and serial number (S/N). (S/N is stamped in shell above the nameplate. A typical example, S/N 07A18 01-0123) 2. Pump Inspection A. Check that the pump rating matches the motor. B. Check for pump damage and verify that the pump shaft turns freely. 3. Pump/Motor Assembly A. If not yet assembled, check that pump and motor mounting faces are free from dirt, debris and uneven paint thickness. B. Pumps and motors over 5 hp should be assembled in the vertical position to prevent stress on pump brackets and shafts. Assemble the pump and motor together so their mounting faces are in contact and then tighten assembly bolts or nuts evenly to manufacturer specifications. C. If accessible, check that the pump shaft turns freely. D. Assemble the pump lead guard over the motor leads. Do not cut or pinch lead wires during assembly or installation. 4. Power Supply and Controls A. Verify that the power supply voltage, Hertz, and kVA capacity match motor requirements. B. Verify control box hp and voltage matches motor (3-wire only). C. Check that the electrical installation and controls meet all safety regulations and match the motor requirements, including fuse or circuit breaker size and motor overload protection. Connect all metal plumbing and electrical enclosures to the power supply ground to prevent shock hazard. Comply with national and local codes. 5. Lightning and Surge Protection A. Use properly rated surge (lightning) arrestors on all submersible pump installations. Motors 5 hp and SMALLER WHICH ARE MARKED h%QUIPPED WITH ,IGHTNING !RRESTORSv CONTAIN INTERNAL ARRESTORS B. Ground all above ground arrestors with copper wire directly to the motor frame, or to metal drop pipe or casing which reaches below the well pumping level. Connecting to a ground rod does not provide good surge protection. 6. Electrical Drop Cable A. Use submersible cable sized in accordance with local regulations and the cable charts. See pages 11 and 16-21. Ground motor per national and local codes. B. Include a ground wire to the motor and surge protection, connected to the power supply ground if required by codes. Always ground any pump operated outside a drilled well. 7. Motor Cooling A. Ensure at all times that the installation provides adequate motor cooling; see page 6 for details. Form No. 3656 11/09 © 2009 Franklin Electric Co., Inc. 35"-%23)",% 05-0 )NSTALLATION #HECK ,IST 8. Pump/Motor Installation A. Splice motor leads to supply cable using electrical grade solder or compression connectors, and carefully insulate each splice with watertight tape or adhesive-lined shrink tubing, as shown in motor or pump installation data. B. Support the cable to the delivery pipe every 10 feet (3 meters) with straps or tape strong enough to prevent sagging. Use padding between cable and any metal straps. C. A check valve in the delivery pipe is recommended. More than one check valve may be required, depending on valve rating and pump setting; see page 5 for details. D. Assemble all pipe joints as tightly as practical, to prevent unscrewing from motor torque. Torque should be at least 10 pound feet per hp (2 meter-KG per kW). E. Set the pump far enough below the lowest pumping level to assure the pump inlet will always have at least the Net Positive Suction Head (NPSH) specified by the pump manufacturer. Pump should be at least 10 feet (3 meters) from the bottom of the well to allow for sediment build up. F. Check insulation resistance as pump/motor assembly is lowered into the well. Resistance may drop gradually as more cable enters the water, but any sudden drop indicates possible cable, splice or motor lead damage; see page 45. 9. After Installation A. Check all electrical and water line connections and parts before starting the pump. B. Start the pump and check motor amps and pump delivery. If normal, continue to run the pump until delivery is clear. If three-phase pump delivery is low, it may be running backward. Rotation may be reversed (with power off) by interchanging any two motor lead connections to the power supply. C. Check three-phase motors for current balance within 5% of average, using motor manufacturer instructions Imbalance over 5% will cause higher motor temperatures and may cause overload trip, vibration, and reduced life. D. Verify that starting, running and stopping cause no significant vibration or hydraulic shocks. E. After at least 15 minutes running time, verify that pump output, electrical input, pumping level, and other characteristics are stable and as specified. Date _____________________ Filled In By _________________________________________________________________ Notes _______________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ ____________________________________________________________________________________________________ Form No. 3656 11/09 © 2009 Franklin Electric Co., Inc. 2-! .UMBER 35"-%23)",% -/4/2 ).34!,,!4)/. 2%#/2$ &ORM 0AGE +%9 $%!,%2 $)342)"54/2 ).34!,,%2 %.$ 53%2 Name: _________________________ Name: _________________________ Name: _________________________ City: ___________________________ City: ___________________________ City: ___________________________ State: ___________ Zip: __________ State: ___________ Zip: __________ State: ___________ Zip: __________ °F Well ID or GPS: __________ ___________ ______________________ Water Temperature: _____________ °C Application/Water Use (e.g. potable water, irrigation, municipal, fountain, etc.): ___________________________________ Yes Date Installed (mm/yy): _____________ Date Failed (mm/yy):_____________ Motor Position Shaft-Up: Hrs. Operating Cycle: ON Time Per Start _____ Mins. Time OFF Between Stop & Restart _____ Hrs. No Mins. -/4/2 Model: ______________________ Serial Number: __________________________ Date Code (if updated): __________ -/4/2 /6%2,/!$ System Typical Operating Current: _______________ Amps @ _______________ Volts Overload: FE SubMonitor Input Amps _______ D3 Attached Yes No Fault Settings Attached Yes No Other Manufacturer Model: _______________________ Dial Set at: __________ or Heater# __________ NEMA Class: Power to Motor by: 10 20 Full Volt Starter 30 Ambient Compensated: VFD 05-0 Yes No Soft Starter VFD or Soft Starter Mfr. & Model: ___________________ 7%,, $!4! (All measurements from well head down.) Manufacturer:_________________________ Casing Diameter ______________________ in Model: ______________________________ Drop Pipe Diameter ____________________ in Stages:______________________________ Number of Sticks of Drop Pipe _____________ Design Rating: _______ gpm @ _______ ft TDH Static Water Level _____________________ ft Horsepower Required by Pump End: ___________ Drawdown (pumping) Water Level _________ ft Actual Pump Delivery: _______ gpm @ _______ psi Spring Assist Check Valves: (Measured from Well Head Down) What Controls When System Runs & Stops: _________________________________________ (e.g. pressure, level, flow, manual on/off, timer, time clock etc.) #1 ______ #2______ #3 ______ #4______ ft Solid Drilled Poppet Break-Off Plug Pump Inlet Setting ____________________ ft Flow Sleeve No Yes, Dia. _________ in Case Ends ___________________________ ft 9/52 .!-% $!4% ____________________________ / ___________ Form No. 2207 v6 05/11 © 2009 Franklin Electric Co., Inc. Well Screen Perforated Casing #1 from ____to____ft & #2 from ____to____ft Well Depth ___________________________ ft 2-! .UMBER 35"-%23)",% -/4/2 ).34!,,!4)/. 2%#/2$ &ORM 0AGE 42!.3&/2-%23 Number of Transformers: Two Transformer #1: __________ kVA Three Transformers Supply Motor Only: Transformer #2: __________ kVA Yes No Unsure Transformer #3: __________ kVA 0/7%2 #!",%3 '2/5.$ 7)2% Service Entrance to Pump Control Panel: 1 Length: __________ ft. & Gauge: __________ AWG/MCM Material: Copper Aluminum Temperature Rating of Cable: Construction: 60C 75C 90C Jacketed Individual Conductors Web Twisted 125C or Insulation Type: ________________ (e.g. THHN) Pump Control Panel to Motor: 2 Length: __________ ft. & Gauge: __________ AWG/MCM Material: Copper Aluminum Temperature Rating of Cable: Construction: 60C 75C 90C Jacketed Individual Conductors Web Twisted 125C or Insulation Type: ________________ (e.g. THHN) Ground Wire Size: From Control Panel to Motor: __________ AWG/MCM 3 Control Grounded to (mark all that apply): Well Head Metal Casing Motor Driven Rod Power Supply ).#/-).' 6/,4!'% 25..).' !-03 #522%.4 "!,!.#% No Load L1-L2 ______ L2-L3 ______ L1-L3 ______ Full Load Full Load L1-L2 ______ L2-L3 ______ L1-L3 ______ % Unbalance: ______ L1 ________ L2 ________ L3 ________ #/.42/, 0!.%, 1 Pump Panel Manufacturer/Fabricator: _______________________________________________________________ Short Circuit Protection - Fuses or Circuit Breaker Option #1 - Fuse 2 Manufacturer: __________________ Model: __________________ Rating: ____________ Amps Type: Time-Delay Standard Option #2 - Circuit Breaker Manufacturer: __________________ Model: __________________ Rating: ___________ Amps Setting: _________ Starter - Full Voltage, Reduced Voltage, Soft-Starter or VFD (Variable Frequency Drive) Option #1 - Full Voltage Manufacturer: __________________ Model: ________________ Size: ____________ Contacts: NEMA IEC Option #2 - Reduced Voltage Manufacturer: __________________ Model: __________________ Ramp Time to Full Voltage: _____________ sec. 3 Option #3 - Soft-Starter or VFD Manufacturer: __________________ Model: __________________ Max. Continuous Amp Output Rating: _________ Min. Setting: ____________ Hz & GPM: ____________ Start Ramp Time to 30 Hz: ________ sec. Special Output Filter Purchased: Yes Stop Mode: Max. Setting: ____________ Hz & GPM: ____________ Power Off Coast 30-0 Hz Ramp ________ sec. No Output Filter Manufacturer: ______________________ Model: ______________________ % Reactance: _________ 4 Surge Arrestor: No Yes, Manufacturer: ____________________ Model: ____________________ Form No. 2207 v6 05/11 © 2009 Franklin Electric Co., Inc. 35"-%23)",% -/4/2 "OOSTER )NSTALLATION 2ECORD 2-! .UMBER Date ______ /______/_______ Filled In By ______________________________________ ).34!,,!4)/. Owner/User ________________________________________________ Telephone (______) ____________________ Address ____________________________________________City _______________ State ______ Zip ___________ Installation Site, If Different _________________________________________________________________________ Contact ___________________________________________________ Telephone (______) ____________________ System Application________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ System Manufactured By_____________________________Model ________________ Serial No. ________________ System Supplied By_________________________________ City _________________ State ______ Zip __________ )S THIS A h(%2/v SYSTEM 0( Yes No -/4/2 Model No. _______________ Serial No. _______________ Date Code ______ Horsepower ______ Voltage ______ Slinger Removed? Yes Motor Fill Solution Standard Single-Phase Three-Phase Diameter ______ in. No Check Valve Plug Removed? Yes No DI Water Model No. _____________ Serial No. _____________ Date Code ______ 05-0 Manufacturer _______________ Model _______________ Serial No. _______________ Stages ______ Diameter ________ Flow Rate Of ________ gpm At ______TDH Booster Case Internal Diameter ________ Material _______________ #/.42/,3 !.$ 02/4%#4)6% $%6)#%3 SubMonitor? Yes No If Yes, Warranty Registration No._______________________________________ If Yes, Overload Set? Underload Sets? VFD or Reduced Voltage Starter? Yes Yes Yes No ______ Set At _________________________ No ______ Set At _________________________ No If Yes, Type __________________________________________ Mfr. ______________Setting ________% Full Voltage In ________sec Pump Panel? Yes No If Yes, Mfr. ______________________________Size _______________________ Magnetic Starter/Contactor Mfr. ___________________________ Model __________________Size_______________ Heaters Mfr. _____________________ No. ____________ If Adjustable Set At ________________________________ Fuses Mfr. ____________________ Size ___________ Type ______________________________________________ Lightning/Surge Arrestor Mfr. ________________________ Model __________________________________________ Controls Are Grounded to __________________ with No. ________Wire Inlet Pressure Control Yes No If Yes, Mfr.________ Model _______ Setting _____ psi Delay ____ sec Inlet Flow Control Yes No If Yes, Mfr.________ Model _______ Setting _____ gpm Delay ____ sec Outlet Pressure Control Yes No If Yes, Mfr.________ Model _______ Setting _____ psi Delay ____ sec Outlet Flow Control Yes No If Yes, Mfr.________ Model _______ Setting _____ gpm Delay ____ sec Water Temperature Control Yes No If Yes, Mfr.________ Model ________________________ Delay ____ sec Set At ________ °F or ______ °C Located _____________________________________ Form No. 3655 11/09 © 2009 Franklin Electric Co., Inc. 35"-%23)",% -/4/2 "OOSTER )NSTALLATION 2ECORD ).35,!4)/. #(%#+ Initial Megs: Motor & Lead Only Black (T1/U1)_________ Yellow (T2/V1)________ Red (T3/W1)_________ Installed Megs: Motor, Lead, & Cable Black (T1/U1)_________ Yellow (T2/V1)________ Red (T3/W1)_________ 6/,4!'% 4/ -/4/2 Non-Operating: B-Y (T1/U1 - T2/V1)_____ Y-R (T2/V1 - T3/W1)_____ R-B (T3/W1 - T1/U1)_____ At Rated Flow of __________gpm B-Y (T1/U1 - T2/V1)_____ Y-R (T2/V1 - T3/W1)_____ R-B (T3/W1 - T1/U1)_____ At Open Flow ____________gpm B-Y (T1/U1 - T2/V1)_____ Y-R (T2/V1 - T3/W1)_____ R-B (T3/W1 - T1/U1)_____ !-03 4/ -/4/2 At Rated Flow of __________gpm Black (T1/U1)_________ Yellow (T2/V1)________ Red (T3/W1)_________ At Open Flow ____________gpm Black (T1/U1)_________ Yellow (T2/V1)________ Red (T3/W1)_________ At Shut Off* Black (T1/U1)_________ Yellow (T2/V1)________ Red (T3/W1)_________ *Do NOT run at Shut Off more than two (2) minutes. Inlet Pressure __________psi Outlet Pressure __________psi Water Temperature _______ °F or _______ °C If you have any questions or problems, call the Franklin Electric Toll-Free Hot Line: 1-800-348-2420 Comments: _____________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ 0,%!3% 3+%4#( 4(% 3934%- Form No. 3655 11/09 © 2009 Franklin Electric Co., Inc. !00,)#!4)/. 4HREE 0HASE -OTORS 3UB-ONITOR 4HREE 0HASE 0ROTECTION Applications SubMonitor is designed to protect 3-phase pumps/ motors with service factor amp ratings (SFA) from 5 to 350 A (approx. 3 to 200 hp). Current, voltage, and motor temperature are monitored using all three legs and allows the user to set up the SubMonitor quickly and easily. Protects Against s s s s 5NDER/VERLOAD 5NDER/VERVOLTAGE #URRENT 5NBALANCE /VERHEATED -OTOR (if equipped with Subtrol Heat Sensor) s &ALSE 3TART #HATTERING s 0HASE 2EVERSAL 0OWER &ACTOR #ORRECTION In some installations, power supply limitations make it necessary or desirable to increase the power factor of a submersible motor. The table lists the capacitive kVAR required to increase the power factor of large Franklin three-phase submersible motors to the approximate values shown at maximum input loading. Capacitors must be connected on the line side of the overload relay, or overload protection will be lost. Table 32 kVAR Required 60 Hz MOTOR HP 5 KVAR REQUIRED FOR PF OF: KW 0.90 0.95 1.00 3.7 1.2 2.1 4.0 7.5 5.5 1.7 3.1 6.0 10 7.5 1.5 3.3 7.0 15 11 2.2 4.7 10.0 20 15 1.7 5.0 12.0 25 18.5 2.1 6.2 15.0 30 22 2.5 7.4 18.0 40 30 4.5 11.0 24.0 7.1 15.0 32.0 50 37 60 45 8.4 18.0 38.0 75 55 6.3 18.0 43.0 100 75 11.0 27.0 60.0 125 93 17.0 36.0 77.0 150 110 20.0 42.0 90.0 175 130 9.6 36.0 93.0 200 150 16.0 46.0 110.0 Values listed are total required (not per phase). 32 !00,)#!4)/. 4HREE 0HASE -OTORS 4HREE 0HASE 3TARTER $IAGRAMS Three-phase combination magnetic starters have two distinct circuits: a power circuit and a control circuit. The power circuit consists of a circuit breaker or fused line switch, contacts, and overload heaters connecting incoming power lines L1, L2, L3 and the three-phase motor. The control circuit consists of the magnetic coil, overload contacts and a control device such as a pressure switch. When the control device contacts are closed, current flows through the magnetic contactor coil, the contacts close, and power is applied to the motor. Hand-Off-Auto switches, start timers, level controls and other control devices may also be in series in the control circuit. L1 L3 L2 Line Voltage Control This is the most common type of control encountered. Since the coil is connected directly across the power lines L1 and L2, the coil must match the line voltage. PRESSURE SWITCH OR OTHER CONTROL DEVICE FUSES O.L. CONTACTS COIL CONTACTS OVERLOAD HEATERS AND/OR SUBTROL PLUS MOTOR L1 Low Voltage Transformer Control This control is used when it is desirable to operate push buttons or other control devices at some voltage lower than the motor voltage. The transformer primary must match the line voltage and the coil voltage must match the secondary voltage of the transformer. L2 FIG. 7 L3 PRESSURE SWITCH OR OTHER CONTROL DEVICE FUSES O.L. CONTACTS COIL FUSE TRANSFORMER CONTACTS OVERLOAD HEATERS AND/OR SUBTROL PLUS MOTOR L1 External Voltage Controls Control of a power circuit by a lower circuit voltage can also be obtained by connecting to a separate control voltage source. The coil rating must match the control voltage source, such as 115 or 24 volts. L2 FIG. 8 L3 PRESSURE SWITCH OR OTHER CONTROL DEVICE FUSES O.L. CONTACTS COIL CONTACTS OVERLOAD HEATER AND/OR SUBTROL DEVICE MOTOR 33 FIG. 9 TO SEPARATE CONTROL VOLTAGE SOURCE !00,)#!4)/. 4HREE 0HASE -OTORS 4HREE 0HASE 0OWER 5NBALANCE A full three-phase supply is recommended for all threephase motors, consisting of three individual transformers OR ONE THREE PHASE TRANSFORMER 3O CALLED hOPENv DELTA or Wye connections using only two transformers can be used, but are more likely to cause problems, such as FIG. 10 FULL THREE-PHASE poor performance, overload tripping or early motor failure due to current unbalance. Transformer rating should be no smaller than listed in table 4 for supply power to the motor alone. FIG. 11 OPEN DELTA #HECKING AND #ORRECTING 2OTATION AND #URRENT 5NBALANCE 1. Establish correct motor rotation by running the motor in both directions. Normal rotation is CCW viewing the shaft end. Rotation can be changed by interchanging any two of the three motor leads. The rotation that gives the most water flow is typically the correct rotation. 2. After correct rotation has been established, check the current in each of the three motor leads and calculate the current unbalance as explained in 3 below. If the current unbalance is 2% or less, leave the leads as connected. If the current unbalance is more than 2%, current readings should be checked on each leg using each of three possible hook-ups. Roll the motor leads across the starter in the same direction to prevent motor reversal. 3. To calculate percent of current unbalance: A. Add the three line amps values together. D. Determine the difference between this amp value (furthest from average) and the average. E. Divide the difference by the average. Multiply the result by 100 to determine percent of unbalance. 4. Current unbalance should not exceed 5% at max amp load or 10% at rated input load. If the unbalance cannot be corrected by rolling leads, the source of the unbalance must be located and corrected. If, on the three possible hookups, the leg farthest from the average stays on the same power lead, most of the UNBALANCE IS COMING FROM THE hPOWER SIDEv OF THE system. If the reading farthest from average moves with the same motor lead, the primary source of UNBALANCE IS ON THE hMOTOR SIDEv OF THE STARTER )N THIS instance, consider a damaged cable, leaking splice, poor connection, or faulty motor winding. Phase designation of leads for CCW rotation viewing shaft end. To reverse rotation, interchange any two leads. B. Divide the sum by three, yielding average current. 0HASE OR h!v "LACK 4 OR 5 C. Pick the amp value which is furthest from the average current (either high or low). 0HASE OR h"v 9ELLOW 4 OR 6 0HASE OR h#v 2ED 4 OR 7 NOTICE: Phase 1, 2 and 3 may not be L1, L2 and L3. 1st Hook Up L1 L2 L3 2nd Hook Up L1 L2 L3 3rd Hook Up L1 L2 L3 supply starter T2 T1 T1 T3 T3 T3 T2 T2 T1 motor EXAMPLE: T1 = 51 amps T3 = 50 amps T2 = 50 amps T2 = 46 amps T1 = 49 amps T3 = 48 amps + T2 = 51 amps + T3 = 53 amps + T1 = 52 amps Total = 150 amps Total = 150 amps Total = 150 amps 150 = 50 amps 3 150 = 50 amps 3 150 = 50 amps 3 50 - 46 = 4 amps 50 - 49 = 1 amp 50 - 48 = 2 amps 4 = 0.08 or 8% 50 1 = 0.02 or 2% 50 2 = 0.04 or 4% 50 34 !00,)#!4)/. 4HREE 0HASE -OTORS 4HREE 0HASE -OTOR ,EAD )DENTIlCATION Line Connections — Six-Lead Motors T5-V2 (YELLOW) WARNING: When installing 6-lead motors extra care must be used to ensure lead identification at the surface. Leads must be marked and connected per diagram. Motor leads are not connected red to red, yellow to yellow, etc. CHECK VALVE OR PIPE PLUG ON RIGHT SIDE FACING MOTOR SHAFT T6-W2 (RED) T4-U2 (BLACK) T2-V1 (YELLOW) T1-U1 (BLACK) T3-W1 (RED) LEADS LOCATED HERE ONLY FOR 3 LEAD (DOL) MOTORS 90° Lead Spacing Connections for across-the-line starting, running, and any reduced voltage starting except WYE-DELTA type starters. L1 T1 U1 L2 T6 W2 T2 V1 L3 T4 U2 T3 W1 T5 V2 WYE-DELTA starters connect the motor as shown below during starting, then change to the running connection shown at the left. L1 L2 L3 T1 U1 T2 V1 T3 W1 T4 U2 T5 V2 T6 W2 Each motor lead is numbered with two markers, one near each end. To reverse rotation, interchange any two line connections. 0HASE #ONVERTERS There are a number of different types of phase converters available. Each generates three-phase power from a single-phase power line. In all phase converters, the voltage balance is critical to current balance. Although some phase converters may be well balanced at one point on the system-operating curve, submersible pumping systems often operate at differing points on the curve as water levels and operating pressures fluctuate. Other converters may be well balanced at varying loads, but their output may vary widely with fluctuations in the input voltage. The following guidelines have been established for submersible installations to be warrantable when used with a phase converter. 35 1. Limit pump loading to rated horsepower. Do not load into motor service factor. 2. Maintain at least 3 ft/s flow past the motor. Use a flow sleeve when necessary. 3. Use time delay fuses or circuit breakers in pump panel. Standard fuses or circuit breakers do not provide secondary motor protection. 4. SubMonitor may be used with electro mechanical type phase converters, however special connections are required. Consult SubMonitor Manual for connections of receiver and lightning arrestor. 5. SubMonitor will not work with electronic solid state phase converters. 6. Current unbalance must not exceed 10%. !00,)#!4)/. 4HREE 0HASE -OTORS 2EDUCED 6OLTAGE 3TARTERS All Franklin three-phase submersible motors are suitable for full-voltage starting. Under this condition the motor speed goes from zero to full speed within a half second or less. The motor current goes from zero to locked rotor amps, then drops to running amps at full speed. This may dim lights, cause momentary voltage dips to other electrical equipment, and shock power distribution transformers. In some cases the power companies may require reduced-voltage starters to limit this voltage dip. There are also times when reduced-voltage starters may be desirable to reduce motor starting torque thus reducing the stress on shafts, couplings, and discharge piping. Reduced-voltage starters also slow the rapid acceleration of the water on start-up to help control upthrust and water hammer. Reduced-voltage starters may not be required if the maximum recommended cable length is used. With maximum recommended cable length there is a 5% voltage drop in the cable at running amps, resulting in about 20% reduction in starting current and about 36% reduction in starting torque compared to having rated voltage at the motor. This may be enough reduction in starting current so that reduced-voltage starters are not required. Three-Lead Motors: Autotransformer or solid-state reduced-voltage starters may be used for soft-starting standard three-phase motors. When autotransformer starters are used, the motor should be supplied with at least 55% of rated voltage to ensure adequate starting torque. Most autotransformer starters have 65% and 80% taps. Setting the taps on these starters depends on the percentage of the maximum allowable cable length used in the system. If the cable length is less than 50% of the maximum allowable, either the 65% or the 80% taps may be used. When the cable length is more than 50% of allowable, the 80% tap should be used. Six-Lead Motors: Wye-Delta starters are used with six-lead Wye-Delta motors. All Franklin 6" and 8" three-phase motors are available in six-lead Wye-Delta construction. Consult the factory for details and availability. Part winding starters are not compatible with Franklin Electric submersible motors and should not be used. Wye-Delta starters of the open-transition type, which momentarily interrupt power during the starting cycle, are not recommended. Closed-transition starters have no interruption of power during the start cycle and can be used with satisfactory results. Reduced-voltage starters have adjustable settings for acceleration ramp time, typically preset at 30 seconds. They must be adjusted so the motor is at full voltage within THREE SECONDS MAXIMUM to prevent excessive radial and thrust bearing wear. If Subtrol-Plus or SubMonitor is used the acceleration time must be set to TWO SECONDS MAXIMUM due to the 3 second reaction time of the Subtrol-Plus or SubMonitor. Solid-state starters AKA soft starts may not be compatible with Subtrol-Plus/SubMonitor. However, in some cases a bypass contactor has been used. Consult the factory for details. During shutdown, Franklin Electric’s recommendation is for the power to be removed, allowing the pump/motor to coast down. Stopping the motor by ramping down the voltage is possible, but should be limited to three (3) seconds maximum. )NLINE "OOSTER 0UMP 3YSTEMS Franklin Electric offers three different types of motors for non-vertical applications. 1. The Booster motors are specifically designed for booster applications. They are the “Best Choice” for sealed Reverse Osmosis applications. These motors are the result of two years of focused development and bring additional value and durability to booster module systems. These motors are only available to OEMs or Distributors who have demonstrated capability in Booster Module systems design and operation and adhere to Franklin’s Application Manual requirements. 2. The Hi-Temp motors have many of the internal design features of the Booster motor. It’s additional length allows for higher temperature handling and the Sand Fighter sealing system provides greater abrasion resistance. One or both of these conditions Continued on next page are often experienced in open atmosphere applications such as lakes, ponds, etc. 3. The Standard Vertical Water Well (40-125 hp) motors can be adapted to non-vertical applications when applied per the below guidelines. However, they will be more sensitive to application variances than the other two designs. All of the above motors must be applied per the guidelines listed below. In addition, for all applications where the motor is applied in a sealed system, a Submersible Motor Booster Installation Record (Form 3655) or its equivalent must be completed at startup and received by Franklin Electric within 60 days. A sealed system is one where the motor and pump intake are mounted in a sleeve and the water feeding the pump intake is not open to the atmosphere. 36 !00,)#!4)/. 4HREE 0HASE -OTORS )NLINE "OOSTER 0UMP 3YSTEMS CONTINUED water must be done by an approved Franklin service shop or representative using a vacuum fill system per Franklin’s Motor Service Manual instruction. The motor shell then must be permanently stamped with a D closely behind the Serial Number. Design And Operational Requirements 1. Non-Vertical Operation: Vertical Shaft-up (0°) to Horizontal (90°) operation is acceptable as long as THE PUMP TRANSMITS hDOWN THRUSTv TO THE MOTOR WITHIN 3 seconds after start-up and continuously during operation. However, it is best practice to provide a positive slope whenever it is possible, even if it is only a few degrees. 3. Motor Support Points: A minimum of two support points are required on the motor. One in the motor/ pump flange connection area and one in the bottom end of the motor area. The motor castings, not the shell area, are recommended as support points. If the support is a full length support and/or has bands in the shell area, they must not restrict heat transfer or deform the shell. Derating Factor for Motors That Must Have Their Factory Fill Replaced With Deionized Water 8" Encapsulated Motor 1.8 1.75 1.7 Pump Load Multiplier 2. Motor, Sleeve, and Pump Support System: The booster sleeve ID must be sized according to the motor cooling and pump NPSHR requirements. The support system must support the motor’s weight, prevent motor rotation and keep the motor and pump aligned. The support system must also allow for thermal axial expansion of the motor without creating binding forces. The maximum pressure that can be applied to the motor internal components during the removal of the factory fill solution is 7 psi (0.5 bar.) 1.65 1.6 1.55 1.5 1.45 1.4 1.35 1.3 1.25 1.2 1.15 1.1 1.05 1 1.00 Service Factor 1.15 Service Factor 40 35 30 (50Hz) (60Hz) 25 20 15 10 Feed Water Temperature (°C) FIG. 12 Determine maximum Feed Water Temperature that will be experienced in this application. If the feed water exceeds the maximum ambient of the motor, both the DI water derating and a hot water application derating must be applied. 4. Motor Support Material and Design: The support system shall not create any areas of cavitation or other areas of reduced flow less than the minimum rate required by this manual. They should also be designed to minimize turbulence and vibration and provide stable alignment. The support materials and locations must not inhibit the heat transfer away from the motor. First: 5. Motor and Pump Alignment: The maximum allowable misalignment between the motor, pump, and pump discharge is 0.025 inch per 12 inches of length (2 mm per 1000 mm of length). This must be measured in both directions along the assembly using the motor/pump flange connection as the starting point. The booster sleeve and support system must be rigid enough to maintain this alignment during assembly, shipping, operation and maintenance. Third: Multiply the Pump Load Requirement times the pump load multiplier number indicated on the vertical axis to determine the Minimum Motor Nameplate Rating. Fourth: Select a motor with a nameplate equal or higher than the above calculated value. 6. The best motor lubrication and heat resistance is obtained with the factory based propylene glycol fill solution. Only when an application MUST HAVE deionized (DI) water should the factory fill solution be replaced. When a deionized water fill is required, the motor must be derated as indicated on the below chart. The exchange of the motor fill solution to DI 37 Second: Determine the Pump Load Multiplier from the appropriate Service Factor curve. (Typical 1.15 Service Factor is for 60 Hz ratings &1.00 Service Factor for 50 Hz ratings). 7. Motor Alterations - Sand Slinger & Check Valve Plug: /N v AND v MOTORS THE RUBBER SAND SLINGER located on the shaft must be removed. If a pipe plug is covering the check valve, it must be removed. The special Booster motor already has these modifications. 8. Frequency of Starts: Fewer than 10 starts per 24-hour period are recommended. Allow at least 20 minutes between shutdown and start-up of the motor. Continued on next page !00,)#!4)/. 4HREE 0HASE -OTORS )NLINE "OOSTER 0UMP 3YSTEMS CONTINUED 9. Controls-Soft Starters and VFDs: Reduced voltage starters and variable speed drives (inverter drives) may be used with Franklin three-phase submersible motors to reduce starting current, upthrust, and mechanical stress during start-up. The guidelines for their use with submersible motors are different than with normal air cooled motor applications. Refer to the Franklin Electric Application, Installation and Maintenance (AIM) Manual Reduced Voltage Starters section or Variable Speed Submersible Pump Operation, Inverter Drives sections for specific details including required filtering. Franklin Cable Chart tables 16-21. (Notice: wire size, wire rating and insulation temperature rating must be known when determining its suitability to operate in air or conduit. Typically, for a given size and rating, as the insulation temperature rating increases its ability to operate in air or conduit also increases.) 13. Check Valves: Spring-loaded check valves must be used on start-up to minimize motor upthrusting, water hammer, or in multiple booster (parallel) applications to prevent reverse flow. 14. Pressure Relief Valves: A pressure relief valve is required and must be selected to ensure that, as the pump approaches shut-off, it never reaches the point that the motor will not have adequate cooling flow past it. 10. Motor Overload Protection: Submersible motors require properly sized ambient compensated Class 10 quick-trip overloads per Franklin’s AIM Manual guidelines to protect the motor. Class 20 or higher overloads are NOT acceptable. Franklin’s SubMonitor is strongly recommended for all large submersibles since it is capable of sensing motor heat without any additional wiring to the motor. Applications using Soft Starters with a SubMonitor require a start-up bypass - consult the factory for details. SubMonitor can not be used in applications using a VFD control. 15. System Purge (Can Flooding): An air bleeder valve must be installed on the booster sleeve so that flooding may be accomplished prior to booster startup. Once flooding is complete, the booster should be started and brought up to operating pressure as quickly as possible to minimize the duration of an upthrust condition. At no time should air be allowed to gather in the booster sleeve because this will prevent proper cooling of the motor and permanently damage it. 11. Motor Surge Protection: Properly sized, grounded and dedicated motor surge arrestors must be installed in the supply line of the booster module as close to the motor as possible. This is required on all systems including those using soft-starters and variable speed drives (inverter drives). 16. System Flush – Must Not Spin Pump: Applications may utilize a low flow flushing operation. Flow through the booster sleeve must not spin the pump impellers and the motor shaft. If spinning takes place, the bearing system will be permanently damaged and the motor life shortened. Consult the booster pump manufacturer for maximum flow rate through the pump when the motor is not energized. 12. Wiring: Franklin’s lead assemblies are only sized for submerged operation in water to the motor nameplate maximum ambient temperature and may overheat and cause failure or serious injury if operated in air. Any wiring not submerged must meet applicable national and local wiring codes and Table 38 Franklin Cable chart (See 12. Wiring) CABLE TEMP. RATING (°C) 75 90 125 MOTOR NAMEPLATE RATED AMPS FULL LOAD #10 AWG IN AIR IN CONDUIT #8 AWG IN AIR IN CONDUIT #6 AWG IN AIR #4 AWG IN CONDUIT IN AIR #2 AWG IN CONDUIT IN AIR IN CONDUIT 3-LEAD (DOL) 40A 28A 56A 40A 76A 52A 100A 68A 136A 92A 3,(+@¬ 69A 48A 97A 69A 132A 90A 173A 118A 236A 159A 3-LEAD (DOL) 44A 32A 64A 44A 84A 60A 112A 76A 152A 104A 3,(+@¬ 76A 55A 111A 76A 145A 104A 194A 132A 263A 180A 3-LEAD (DOL) 66A 46A 77A 53A 109A 75A 153A 105A 195A 134A 3,(+@¬ 114A 80A 133A 91A 188A 130A 265A 181A 337A 232A Based on 30 °C maximum ambient with cable length of 100 feet or less. Continued on next page 38 !00,)#!4)/. 4HREE 0HASE -OTORS )NLINE "OOSTER 0UMP 3YSTEMS CONTINUED 17. Open Atmosphere Booster Pump Systems: When an open booster is placed in a lake, tank, etc. that is open to atmospheric pressure, the water level must provide sufficient head pressure to allow the pump to operate above its NPSHR requirement at all times and all seasons. Adequate inlet pressure must be provided prior to booster start-up. Even during these 10 seconds the pressure must remain positive and be higher than the NPSHR (Net Positive Suction Head Requirement) of the pump. PSIG is the actual value displayed on a pressure gauge in the system piping. PSIG is the pressure above the atmospheric conditions. If at any time these pressure requirements are not being met, the motor must be de-energized immediately to prevent permanent damage to the motor. Once the motor is damaged, it is usually not immediately noticeable, but progresses and results in a premature motor failure weeks or months after the damage occurred. Four Continuous Monitoring System Requirements for Sealed Booster Systems. 1. 2. 39 Water Temperature: Feed water on each booster must be continuously monitored and not allowed to exceed the motor nameplate maximum ambient temperature at any time. IF THE INLET TEMPERATURE EXCEEDS THE MOTOR NAMEPLATE MAXIMUM AMBIENT TEMPERATURE, THE SYSTEM MUST SHUTDOWN IMMEDIATELY TO PREVENT PERMANENT MOTOR DAMAGE. If feed water temperatures are expected to be above the allowable temperature, the motor must be derated. See Franklin’s AIM Manual Hot Water Applications section for derating guidelines. (The high temperature feed water derating is in addition to the exchange to DI water derating if the motor factory fill solution was exchanged to DI water.) Inlet Pressure: The inlet pressure on each booster module must be continuously monitored. It must always be positive and higher than the NPSHR (Net Positive Suction Head Requirement) of the pump. A minimum of 20 PSIG (1.38 Bar) is required at all times, except for 10 seconds or less when the motor is starting and the system is coming up to pressure. Motors that will be exposed to pressure in excess of 500 psi (34.47 Bar) must undergo special high pressure testing. Consult factory for details and availability. 3. Discharge Flow: The flow rate for each pump must not be allowed to drop below the motor minimum cooling flow requirement. IF THE MOTOR MINIMUM COOLING FLOW REQUIREMENT IS NOT BEING MET FOR MORE THAN 10 SECONDS, THE SYSTEM MUST BE SHUT DOWN IMMEDIATELY TO PREVENT PERMANENT MOTOR DAMAGE. 4. Discharge Pressure: The discharge pressure must be monitored to ensure that a downthrust load toward the motor is present within 3 seconds after start-up and continuously during operation. IF THE MOTOR DISCHARGE PRESSURE IS NOT ADEQUATE TO MEET THIS REQUIREMENT, THE SYSTEM MUST BE SHUT DOWN IMMEDIATELY TO PREVENT PERMANENT MOTOR DAMAGE. !00,)#!4)/. 4HREE 0HASE -OTORS 6ARIABLE &REQUENCY $RIVE 3UBMERSIBLE -OTOR 2EQUIREMENTS Franklin Electric’s three-phase, encapsulated submersible motors can be used with variable frequency drives (VFD) when applied within the guidelines below. All three-phase, encapsulated submersible motors must have the VFD sized based on the motor’s nameplate maximum amps, not horsepower. The continuous rated amps of the VFD must be equal to or greater than the motor’s nameplate maximum amps or warranty will be void. Franklin Electric’s single-phase, 2- and 3-wire, encapsulated submersible motors can only be used with the appropriate Franklin constant pressure controller. Franklin Electric’s submersible motor Application Installation Maintenance (AIM) manual should be checked for the latest guidelines and can be found online at www.franklin-electric.com. WARNING: There is a potential shock hazard from contact with and/or touching the insulated cables connected to the variable frequency drive output anytime the motor has energy applied. /UTPUT &ILTER 2EQUIREMENT 4EST Franklin Electric has a line of VFDs that are specifically designed for Franklin application systems. These VFDs are used in the MonoDrive and SubDrive constant pressure systems. Franklin drive systems have the required additional output filtering installed; however, the SubDrive HPX does not. 4YPES OF /UTPUT &ILTERS A resistor-inductor-capacitor (RLC) filter has both a high pass filter & a low pass filter section and are considered the best practice, but a high pass reactor filter is also acceptable. Filters should be recommended by the drive manufacturer; for the correct recommendations provide them with answers to all five of the items below. 2%15)2%$ )4%-3 &/2 02/0%2 6&$ &),4%2 3):).' (1) VFD model (2) Carrier frequency setting (3) Motor nameplate voltage (4) Motor nameplate max amps (5) Cable length from the drive output terminals to the motor )NPUT #URRENT -OTOR /VERLOAD 0ROTECTION ./4)#%: An incoming power supply or line-side filter for the drive does not replace the need for additional output filters. s -OTOR INPUT CURRENT SHOULD BE SET AT THE SYSTEMS typical operating current when running at nameplate rated voltage and frequency (Hz). !N OUTPUT lLTER IS REQUIRED IF THE ANSWER IS YES TO ONE OR BOTH OF THE ITEMS BELOW s -OTOR OVERLOAD PROTECTION SHOULD BE SET TO TRIP AT 115% of the system’s typical operating current. #1 - Is the VFD’s pulse width modulation (PWM) voltage rise-time (dV/dt) more than 500 Volts per micro-second (500 V/µ-second)? #2 - Is the motor nameplate voltage more than 379 Volts and is the cable from drive-to-motor more than 50 ft (15.2 m)? ./4)#% More than 99% of the drives applied on water well submersible motors will require the purchase of additional output filtering based on question #1. Output filters can be expensive. However, when needed, it is required for the motor to be considered for warranty. Make sure this item is not overlooked when quoting a job. s -OTOR OVERLOAD PROTECTION MUST TRIP EQUAL TO or faster than NEMA Class 10 motor overload curve requirements. -OTOR -AXIMUM ,OAD ,IMITS s 4HE SYSTEM MUST NEVER OPERATE IN EXCESS OF THE MOTOR nameplate maximum amps. s /N (Z MOTORS NAMEPLATE AMPS ARE MAXIMUM amps as these motors have a 1.0 service factor. PWM dV/dt value can be defined as: the rate at which voltage is changing with time or how fast the voltage is accelerating. This information can be supplied by the drive manufacturer or the manufacturer’s drive specification sheet. The dV/dt value cannot be measured with typical field equipment, even when using a true-RMS voltage/amperage multi-meter. 40 !00,)#!4)/. 4HREE 0HASE -OTORS 6ARIABLE &REQUENCY $RIVE 3UBMERSIBLE -OTOR 2EQUIREMENTS -OTOR /PERATING (ERTZ #OOLING 2EQUIREMENTS 5NDERLOAD 3ETTINGS s 3TANDARD PRACTICE FOR LARGE 6&$ INSTALLATIONS IS TO LIMIT the operation to 60 Hz max. Operating at greater than 60 Hz requires special system design considerations. s 4HE MOTOR MUST NEVER OPERATE BELOW (Z 4HIS IS the minimum speed required to provide correct bearing lubrication. s 4HE MOTORS OPERATING SPEED MUST ALWAYS OPERATE so the minimum water flow requirements of 0.5 ft/sec for 6-inch & 8-inch motors and 0.25 ft/sec for 4-inch motors is supplied. s 4HE MOTOR UNDERLOAD PROTECTION IS NORMALLY SET TO trip at 80% of the system’s typical operating current. However, the underload trip point must be selected so that minimum flow requirements are always met. 3TARTING 3TOPPING 2AMP 3ETTINGS s 4HE MOTOR MUST REACH OR PASS THE (Z OPERATING speed within 1 second of the motor being energized. If this does not occur, the motor bearings will be damaged and the motor life reduced. s 4HE BEST STOPPING METHOD IS TO TURN POWER off followed by a natural coast to stop. s ! CONTROLLED STOP FROM (Z TO (Z IS ALLOWED IF THE time does not exceed 1 second. $RIVE #ARRIER &REQUENCY s 4HE CARRIER FREQUENCY IS SET IN THE lELD 4HE DRIVE typically has a selectable range between 2k and 12k Hz. The higher the carrier wave frequency setting, the greater the voltage spikes; the lower the carrier wave frequency setting, the rougher/poorer the shape of the power curve. s 4HE CARRIER FREQUENCY SHOULD BE SET WITHIN THE RANGE of 4k to 5k Hz for encapsulated submersible motors. !PPLICATION &UNCTION 3ETTING s )F THE 6&$ HAS A SETTING OF CENTRIFUGAL PUMP OR propeller fan it should be used. s #ENTRIFUGAL PUMPS AND FANS HAVE SIMILAR load characteristics. 41 6&$ &REQUENCY OF 3TARTS s +EEPING THE STARTS PER DAY WITHIN THE RECOMMENDED numbers shown in the frequency of starts section of the AIM manual provides the best system life. However, since in-rush current is typically reduced when used with a properly configured VFD, large 3-phase submersible motors can be started more frequently. In all cases a minimum of 7 minutes must be allowed between a power off and the next restart attempt or consecutive restart attempts. .%-! -' !BOVE 'ROUND -OTOR 3TANDARD #OMMENTS s &RANKLIN %LECTRIC ENCAPSULATED SUBMERSIBLE MOTORS are not declared inverter duty motors by NEMA MG1 standards. The reason is NEMA MG1 standard part 31 does not include a section covering encapsulated winding designs. s &RANKLIN SUBMERSIBLE MOTORS CAN BE USED WITH 6&$S without problems or warranty concerns providing Franklin's Application Installation Maintenance (AIM) manual guidelines are followed. See Franklin's on-line AIM manual for the latest guidelines. ).34!,,!4)/. !LL -OTORS v 3UPER 3TAINLESS $IMENSIONS v (IGH 4HRUST $IMENSIONS 3TANDARD 7ATER 7ELL 3TANDARD 7ATER 7ELL 0.030" R MAX 14 TOOTH 24/48" DIAMETRAL PITCH 0.50" MIN. FULL SPLINE 1.48" MAX 0.030" R MAX 1.508" 1.498" 5/16" - 24 UNF-2A MOUNTING STUDS 1.508" 1.498" 5/16" - 24 UNF-2A MOUNTING STUDS 0.97" 0.79" 0.161" MAX LEAD BOSS HEIGHT 14 TOOTH 24/48" DIAMETRAL PITCH 0.50" MIN. FULL SPLINE 1.48" MAX 1.09" 0.91" 0.161" MAX LEAD BOSS HEIGHT 3.75" DIA. 3.75" DIA. L* L* v $IMENSIONS v $IMENSIONS 3TANDARD 7ATER 7ELL 3TANDARD 7ATER 7ELL 15 TOOTH 16/32" DIAMETRAL PITCH .94" MIN. FULL SPLINE 3.000" 2.997" 1.0000" DIA. 0.9995" 2.875" 2.869" 0.250" 0.240" 0.75" 1/2" - 20 UNF-2B MOUNTING HOLES CHECK VALVE L* 23 TOOTH 16/32" DIAMETRAL PITCH 5.000" 4.997" 1.69" MIN FULL SPLINE 4.000" 3.990" SHAFT DIA 1.5000" 1.4990" 1.06" 0.94" 23 TOOTH 16/32" DIAMETRAL PITCH 0.240" 5.130" 5.120" M8 x 1.25 6G GROUND SCREW 7.70" DIA MAX L* 1.69" MIN FULL SPLINE 4.000" 3.990" SHAFT DIA 1.5000" 1.4990" 1.06" 0.94" CHECK VALVE WATER WELL MODELS PIPE PLUG STAINLESS STEEL MODELS 5.000" 4.997" 0.240" 5.130" 5.120" CHECK VALVE MOUNTING HOLES CLEARANCE FOR 5/8" BOLTS M8 x 1.25 6G GROUND SCREW 7.70" DIA MAX L* 5.44" DIA. 6.25" 7.00" FINNED 2.75" FINNED 40 to 100 hp 125 to 200 hp * Motor lengths and shipping weights are available on Franklin Electric’s web site (www.franklin-electric.com) or by calling Franklin’s submersible hotline (800-348-2420). 42 ).34!,,!4)/. !LL -OTORS 4IGHTENING -OTOR ,EAD #ONNECTOR *AM .UT 4" Motors with Jam Nut: 15 to 20 ft-lb (20 to 27 Nm) 4" Motors with 2 Screw Clamp Plate: 35 to 45 in-lb (4.0 to 5.1 Nm) 6" Motors: 40 to 50 ft-lb (54 to 68 Nm) 8" Motors with 1-3/16" to 1-5/8" Jam Nut: 50 to 60 ft-lb (68 to 81 Nm) 8" Motors with 4 Screw Clamp Plate: Apply increasing torque to the screws equally in a criss-cross pattern until 80 to 90 in-lb (9.0 to 10.2 Nm) is reached. Jam nut tightening torques recommended for field assembly are shown. Rubber compression set within the first few hours after assembly may reduce the jam nut torque. This is a normal condition which does not indicate reduced seal effectiveness. Retightening is not required, but is permissible and recommended if original torque was questionable. 0UMP TO -OTOR #OUPLING 0UMP TO -OTOR !SSEMBLY Assemble coupling with non-toxic FDA approved waterproof grease such as Mobile FM102, Texaco CYGNUS2661, or approved equivalent. This prevents abrasives from entering the spline area and prolongs spline life. After assembling the motor to the pump, torque mounting fasteners to the following: A motor lead assembly should not be reused. A new lead assembly should be used whenever one is removed from the motor, because rubber set and possible damage from removal may prevent proper resealing of the old lead. All motors returned for warranty consideration must have the lead returned with the motor. 4" Pump and Motor: 10 lb-ft (14 Nm) 6" Pump and Motor: 50 lb-ft (68 Nm) 8" Pump and Motor: 120 lb-ft (163 Nm) 3HAFT (EIGHT AND &REE %ND 0LAY Table 42 MOTOR NORMAL SHAFT HEIGHT FREE END PLAY DIMENSION SHAFT HEIGHT MIN. MAX. 38.30 mm 38.05 0.010" 0.25 mm 0.045" 1.14 mm 4" 1 1/2" 38.1 mm 1.508" 1.498" 6" 2 7/8" 73.0 mm 2.875" 2.869" 73.02 mm 72.88 0.030" 0.76 mm 0.050" 1.27 mm 8" TYPE 1 4" 101.6 mm 4.000" 3.990" 101.60 mm 101.35 0.008" 0.20 mm 0.032" 0.81 mm 8" TYPE 2.1 4" 101.6 mm 4.000" 3.990" 101.60 mm 101.35 0.030" 0.76 mm 0.080" 2.03 mm If the height, measured from the pump-mounting surface of the motor, is low and/or end play exceeds the limit, the motor thrust bearing is possibly damaged, and should be replaced. 3UBMERSIBLE ,EADS AND #ABLES A common question is why motor leads are smaller than specified in Franklin’s cable charts. The leads are considered a part of the motor and actually are a connection between the large supply wire and the motor winding. The motor leads are short and there is virtually no voltage drop across the lead. In addition, the lead assemblies operate under water, while at least part of the supply cable must operate in air. Lead assemblies running under water operate cooler. 43 CAUTION: Lead assemblies on submersible motors are suitable only for use in water and may overheat and cause failure if operated in air. -!).4%.!.#% !LL -OTORS 3YSTEM 4ROUBLESHOOTING Motor Does Not Start POSSIBLE CAUSE CHECKING PROCEDURES CORRECTIVE ACTION A. No power or incorrect voltage. Check voltage at line terminals. The voltage must be ± 10% of rated voltage. Contact power company if voltage is incorrect. B. Fuses blown or circuit breakers tripped. Check fuses for recommended size and check for loose, dirty or corroded connections in fuse receptacle. Check for tripped circuit breakers. Replace with proper fuse or reset circuit breakers. C. Defective pressure switch. Check voltage at contact points. Improper contact of switch points can cause voltage less than line voltage. Replace pressure switch or clean points. D. Control box malfunction. For detailed procedure, see pages 48-56. Repair or replace. E. Defective wiring. Check for loose or corroded connections or defective wiring Correct faulty wiring or connections. F. Bound pump. Check for misalignment between pump and motor or a sand bound pump. Amp readings will be 3 to 6 times higher than normal until the overload trips Pull pump and correct problem. Run new installation until the water clears G. Defective cable or motor. For detailed procedure, see pages 46 & 47. Repair or replace. A. Pressure switch. Check setting on pressure switch and examine for defects. Reset limit or replace switch. B. Check valve - stuck open. Damaged or defective check valve will not hold pressure. Replace if defective. C. Waterlogged tank. Check air charge Clean or replace. D. Leak in system. Check system for leaks. Replace damaged pipes or repair leaks. Motor Starts Too Often 44 -!).4%.!.#% !LL -OTORS 3YSTEM 4ROUBLESHOOTING Motor Runs Continuously POSSIBLE CAUSE CHECKING PROCEDURES CORRECTIVE ACTION A. Pressure switch. Check switch for welded contacts. Check switch adjustments. Clean contacts, replace switch, or adjust setting. B. Low water level in well. Pump may exceed well capacity. Shut off pump, wait for well to recover. Check static and drawdown level from well head. Throttle pump output or reset pump to lower level. Do not lower if sand may clog pump. C. Leak in system. Check system for leaks. Replace damaged pipes or repair leaks. D. Worn pump. Symptoms of worn pump are similar to those of drop pipe leak or low water level in well. Reduce pressure switch setting, if pump shuts off worn parts may be the fault. Pull pump and replace worn parts. E. Loose coupling or broken motor shaft. Check for loose coupling or damaged shaft. Replace worn or damaged parts. F. Pump screen blocked. Check for clogged intake screen. Clean screen and reset pump depth. G. Check valve stuck closed. Check operation of check valve. Replace if defective. H. Control box malfunction. See pages 47-55 for single-phase. Repair or replace. Motor Runs But Overload Protector Trips A. Incorrect voltage. Using voltmeter, check the line terminals. Voltage must be within ± 10% of rated voltage. Contact power company if voltage is incorrect. B. Overheated protectors. Direct sunlight or other heat source can raise control box temperature causing protectors to trip. The box must not be hot to touch. Shade box, provide ventilation or move box away from source. C. Defective control box. For detailed procedures, see pages 47-55. Repair or replace. D. Defective motor or cable. For detailed procedures, see pages 45 & 46. Repair or replace. E. Worn pump or motor. Check running current, see tables 13, 22, 24 & 27. Replace pump and/or motor. 45 -!).4%.!.#% !LL -OTORS Table 45 Preliminary Tests - All Sizes Single- and Three-Phase TEST PROCEDURE WHAT IT MEANS 1. Open master breaker and disconnect all leads from control box or pressure switch (QD type control, remove lid) to avoid electric shock hazard and damage to the meter. 1. If the ohms value is normal (table 46), the motor is not grounded and the cable insulation is not damaged. 2. If the ohms value is below normal, either the windings are grounded or the cable insulation is damaged. Check the cable at the well seal as the insulation is sometimes damaged by being pinched. 2. Use a megohmmeter or set the scale lever to R X 100K on an ohmmeter. Zero the meter. Insulation Resistance 3. Connect one meter lead to any one of the motor leads and the other lead to the metal drop pipe. If the drop pipe is plastic, connect the meter lead to ground. Winding Resistance 1. Open master breaker and disconnect all leads from control box or pressure switch (QD type control, remove lid) to avoid electric shock hazard and damage to the meter. 1. If all ohms values are normal (tables 13, 22, 24 & 27), the motor windings are neither shorted nor open, and the cable colors are correct 2. Set the scale lever to R X 1 for values under 10 ohms. For values over 10 ohms, set the scale lever to R X 10. hZEROv THE OHMMETER 2. If any one value is less than normal, the motor is shorted. 3. If any one ohm value is greater than normal, the winding or the cable is open, or there is a poor cable joint or connection. 3. On 3-wire motors measure the resistance of yellow to black (main winding) and yellow to red (start winding). On 2-wire motors: measure the resistance from line-to-line. 4. If some ohms values are greater than normal and some less on single-phase motors, the leads are mixed. See page 46 to verify cable colors. Three-phase motors: measure the resistance line-to-line for all three combinations. ATTACH THIS LEAD TO WELL CASING OR DISCHARGE PIPE L1 TO POWER SUPPLY { L2 GROUND L1 L2 POWER MUST BE SHUT OFF R Y CONNECT THIS LEAD TO GROUND B L1 L2 R B RED RED YELLOW YELLOW BLACK BLACK BLACK YELLOW RED GROUND { TO PUMP TO POWER SUPPLY { GROUND L1 L2 BLACK YELLOW RED GROUND POWER MUST BE SHUT OFF MEGGER OR OHMMETER SET AT R X 100K FIG. 13 Y { TO PUMP OHMMETER SET AT R X 1 FIG. 14 46 -!).4%.!.#% !LL -OTORS )NSULATION 2ESISTANCE 2EADINGS Table 46 Normal ohm and Megohm Values Between All Leads and Ground CONDITION OF MOTOR AND LEADS OHMS VALUE MEGOHM VALUE A new motor (without drop cable). 200,000,000 (or more) 200.0 (or more) A used motor which can be reinstalled in well. 10,000,000 (or more) 10.0 (or more) 2,000,000 (or more) 2.0 (or more) 500,000 - 2,000,000 0.50 - 2.0 Less than 500,000 Less than .50 MOTOR IN WELL. READINGS ARE FOR DROP CABLE PLUS MOTOR. New motor. Motor in good condition. Insulation damage, locate and repair. Insulation resistance varies very little with rating. Motors of all hp, voltage, and phase rating have similar values of insulation resistance. The table above is based on readings taken with a megohm meter with a 500 VDC output. Readings may vary using a lower voltage ohmmeter, consult Franklin Electric if readings are in question. 2ESISTANCE OF $ROP #ABLE OHMS The values below are for copper conductors. If aluminum conductor drop cable is used, the resistance will be higher. To determine the actual resistance of the aluminum drop cable, divide the ohm readings from this chart by 0.61. This chart shows total resistance of cable from control to motor and back. Winding Resistance Measuring The winding resistance measured at the motor should fall within the values in tables 13, 22, 24 & 27. When measured through the drop cable, the resistance of the drop cable must be subtracted from the ohmmeter readings to get the winding resistance of the motor. See table below. Table 46A DC Resistance in ohms per 100 ft of Wire (Two conductors) @ 50 °F 47 AWG OR MCM WIRE SIZE (COPPER) 14 12 10 8 6 4 3 2 OHMS 0.544 0.338 0.214 0.135 0.082 0.052 0.041 0.032 1 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 0.026 0.021 0.017 0.013 0.010 0.0088 0.0073 0.0063 0.0056 0.0044 0.0037 0.0032 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS )DENTIlCATION /F #ABLES 7HEN #OLOR #ODE )S 5NKNOWN (Single-Phase 3-Wire Units) If the colors on the individual drop cables cannot be found with an ohmmeter, measure: Cable 1 to Cable 2 Cable 2 to Cable 3 Cable 3 to Cable 1 Find the highest resistance reading. The lead not used in the highest reading is the yellow lead. Use the yellow lead and each of the other two leads to get two readings: Highest is the red lead. Lowest is the black lead. EXAMPLE: The ohmmeter readings were: Cable 1 to Cable 2 - 6 ohms Cable 2 to Cable 3 - 2 ohms Cable 3 to Cable 1 - 4 ohms The lead not used in the highest reading (6 ohms) was Cable 3—Yellow From the yellow lead, the highest reading (4 ohms) was To Cable 1—Red From the yellow lead, the lowest reading (2 ohms) was To Cable 2—Black 3INGLE 0HASE #ONTROL "OXES Checking and Repairing Procedures (Power On) WARNING: Power must be on for these tests. Do not touch any live parts. A. VOLTAGE MEASUREMENTS Step 1. Motor Off 1. Measure voltage at L1 and L2 of pressure switch or line contactor. 2. Voltage Reading: Should be ± 10% of motor rating. Step 2. Motor Running 1. Measure voltage at load side of pressure switch or line contactor with pump running. 2. Voltage Reading: Should remain the same except for slight dip on starting. Excessive voltage drop can be caused by loose connections, bad contacts, ground faults, or inadequate power supply. 3. Relay chatter is caused by low voltage or ground faults. B. CURRENT (AMP) MEASUREMENTS 1. Measure current on all motor leads. 2. Amp Reading: Current in red lead should momentarily be high, then drop within one second to values in table 13. This verifies relay or solid state relay operation. Current in black and yellow leads should not exceed values in table 13. 3. Relay or switch failures will cause red lead current to remain high and overload tripping. 4. Open run capacitor(s) will cause amps to be higher than normal in the black and yellow motor leads and lower than normal in the red motor lead. 5. A bound pump will cause locked rotor amps and overloading tripping. 6. Low amps may be caused by pump running at shutoff, worn pump, or stripped splines. 7. Failed start capacitor or open switch/relay are indicated if the red lead current is not momentarily high at starting. CAUTION: The tests in this manual for components such as capacitors, relays, and QD switches should be regarded as indicative and not as conclusive. For example, a capacitor may test good (not open, not shorted) but may have lost some of its capacitance and may no longer be able to perform its function. 48 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS /HMMETER 4ESTS QD, Solid State Control Box (Power Off) A. START CAPACITOR AND RUN CAPACITOR IF APPLICABLE (CRC) 1. Meter Setting: R x 1,000. 2. Connections: Capacitor terminals. 3. Correct meter reading: Pointer should swing toward zero, then back to infinity. B. Q.D. (BLUE) RELAY Step 1. Triac Test 1. Meter setting: R x 1,000. C. POTENTIAL (VOLTAGE) RELAY Step 1. Coil Test 1. Meter setting: R x 1,000. 2. Connections: #2 & #5. 3. Correct meter readings: For 115 Volt Boxes: 0.7-1.8 (700 to 1,800 ohms). For 230 Volt Boxes: 4.5-7.0 (4,500 to 7,000 ohms). 2. Connections: Cap and B terminal. Step 2. Contact Test 3. Correct meter reading: Infinity for all models. 1. Meter setting: R x 1. Step 2. Coil Test 2. Connections: #1 & #2. 1. Meter Setting: R x 1. 3. Correct meter reading: Zero for all models. 2. Connections: L1 and B. 3. Correct meter reading: Zero ohms for all models. /HMMETER 4ESTS Integral Horsepower Control Box (Power Off) A. OVERLOADS (Push Reset Buttons to make sure contacts are closed.) 1. Meter Setting: R x 1. 2. Connections: Overload terminals. 3. Correct meter reading: Less than 0.5 ohms. B. CAPACITOR (Disconnect leads from one side of each capacitor before checking.) 1. Meter Setting: R x 1,000. 2. Connections: Capacitor terminals. 3. Correct meter reading: Pointer should swing toward zero, then drift back to infinity, except for capacitors with resistors which will drift back to 15,000 ohms. C. POTENTIAL (VOLTAGE) RELAY Step 1. Coil Test 1. Meter setting: R x 1,000. 2. Connections: #2 & #5. Step 2. Contact Test 1. Meter Setting: R x 1. 2. Connections: #1 & #2. 3. Correct meter reading: Zero ohms for all models. D. CONTACTOR Step 1. Coil 1. Meter setting: R x 100 2. Connections: Coil terminals 3. Correct meter reading: 1.8-14.0 (180 to 1,400 ohms) Step 2. Contacts 1. Meter Setting: R X 1 2. Connections: L1 & T1 or L2 & T2 3. Manually close contacts 4. Correct meter reading: Zero ohms 3. Correct meter readings: 4.5-7.0 (4,500 to 7,000 ohms) for all models. CAUTION: The tests in this manual for components such as capacitors, relays, and QD switches should be regarded as indicative and not as conclusive. For example, a capacitor may test good (not open, not shorted) but may have lost some of its capacitance and may no longer be able to perform its function. 49 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS Table 49 QD Control Box Parts 60 Hz HP 1/3 1/2 3/4 1 CONTROL BOX MODEL NUMBER VOLTS QD (BLUE) RELAY START CAPACITOR MFD VOLTS 115 280 102 4915 223 415 905 275 464 125 159-191 110 230 280 103 4915 223 415 901 275 464 126 43-53 220 115 280 104 4915 223 415 906 275 464 201 250-300 125 230 280 105 4915 223 415 902 275 464 105 59-71 220 230 282 405 5015 (CRC) 223 415 912 275 464 126 43-53 220 230 280 107 4915 223 415 903 275 464 118 86-103 220 230 282 407 5015 (CRC) 223 415 913 275 464 105 59-71 220 230 280 108 4915 223 415 904 275 464 113 105-126 220 230 282 408 5015 (CRC) 223 415 914 275 464 118 86-103 220 Table 49A QD Capacitor Replacement Kits RUN CAPACITOR MFD VOLTS 156 362 101 15 370 156 362 102 23 370 156 362 102 23 370 Table 49B Overload Kits 60 Hz CAPACITOR NUMBER KIT HP VOLTS KIT (1) 275 464 105 305 207 905 1/3 115 305 100 901 275 464 113 305 207 913 1/3 230 305 100 902 275 464 118 305 207 918 1/2 115 305 100 903 275 464 125 305 207 925 1/2 230 305 100 904 275 464 126 305 207 926 3/4 230 305 100 905 275 464 201 305 207 951 1 230 305 100 906 156 362 101 305 203 907 156 362 102 305 203 908 (1) For Control Boxes with model numbers that end with 4915. Table 49C QD Relay Replacement Kits QD RELAY NUMBER KIT 223 415 901 305 101 901 223 415 902 305 101 902 223 415 903 305 101 903 223 415 904 305 101 904 223 415 905 305 101 905 223 415 906 305 101 906 223 415 912 (CRC) 305 105 901 223 415 913 (CRC) 305 105 902 223 415 914 (CRC) 305 105 903 FOOTNOTES: (1) Control boxes supplied with QD Relays are designed to operate on 230-volt systems. For 208-volt systems or where line voltage is between 200 volts and 210 volts use the next larger cable size, or use a boost transformer to raise the voltage. (2) Voltage relays kits for 115-volts (305 102 901) and 230-volts (305 102 902) will replace current, voltage or QD Relays, and solid state switches. 50 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS Table 50 Integral Horsepower Control Box Parts 60 Hz MOTOR SIZE 4" MOTOR RATING HP 1 - 1.5 STANDARD CAPACITORS CONTROL BOX (1) MODEL NO. PART NO. (2) MFD. VOLTS QTY. OVERLOAD (2) PART NO. RELAY (3) PART NO. 282 300 8110 (See Note 5) 275 464 113 S 155 328 102 R 105-126 10 220 370 1 1 275 411 107 155 031 102 282 300 8110 (See Note 5) 275 464 113 S 155 328 101 R 105-126 15 220 370 1 1 275 411 114 S 275 411 113 M 155 031 102 282 300 8610 275 464 113 S 155 328 101 R 105-126 15 220 370 1 1 None (See Note 4) 155 031 102 4" 2 STANDARD 282 301 8110 275 464 113 S 155 328 103 R 105-126 20 220 370 1 1 275 411 117 S 275 411 113 M 155 031 102 4" 2 DELUXE 282 301 8310 275 464 113 S 155 328 103 R 105-126 20 220 370 1 1 275 411 117 S 275 411 113 M 155 031 102 4" 3 STANDARD 282 302 8110 275 463 123 S 155 327 109 R 208-250 45 220 370 1 1 275 411 118 S 275 411 115 M 155 031 102 4" 3 DELUXE 282 302 8310 275 463 123 S 155 327 109 R 208-250 45 220 370 1 1 275 411 118 S 275 411 115 M 155 031 102 4" & 6" 5 STANDARD 282 113 8110 275 468 119 S 155 327 114 R 270-324 40 330 370 1 2 275 411 119 S 275 406 102 M 155 031 601 4" & 6" 5 DELUXE 282 113 9310 275 468 119 S 155 327 114 R 270-324 40 330 370 1 2 275 411 119 S 275 406 102 M 155 031 601 6" 7.5 STANDARD 282 201 9210 275 468 119 S 275 468 118 S 155 327 109 R 270-324 216-259 45 330 330 370 1 1 1 275 411 102 S 275 406 122 M 155 031 601 6" 7.5 DELUXE 282 201 9310 275 468 119 S 275 468 118 S 155 327 109 R 270-324 216-259 45 330 330 370 1 1 1 275 411 102 S 275 406 121 M 155 031 601 6" 10 STANDARD 282 202 9210 275 468 119 S 275468 120 S 155 327 102 R 270-324 350-420 35 330 330 370 1 1 2 275 406 103 S 155 409 101 M 155 031 601 282 202 9230 130-154 216-259 270-324 35 330 330 330 370 1 1 1 2 155 031 601 6" 275 463 120 S 275 468 118 S 275 468 119 S 155 327 102 R 275 406 103 S 10 STANDARD 282 202 9310 275 468 119 S 275468 120 S 155 327 102 R 270-324 350-420 35 330 330 370 1 1 2 282 202 9330 275 463 120 S 275 468 118 S 275 468 119 S 155 327 102 R 130-154 216-259 270-324 35 330 330 330 370 1 1 1 2 155 409 101 M 350-420 45 330 370 2 3 CONTACTOR (2) PART NO. 155 325 102 L 155 325 102 L 155 326 101 L 155 326 102 L 155 409 101 M 275 406 103 S 155 409 101 M 155 031 601 155 326 102 L 275 406 103 S 155 031 601 155 326 102 L 275 406 103 S 155 409 102 M 155 031 601 155 429 101 L 275 406 103 S 155 031 601 155 429 101 L 155 031 601 2 required 155 429 101 L 6" 10 DELUXE 6" 10 DELUXE 6" 15 DELUXE 282 203 9310 275 468 120 S 155 327 109 R 6" 15 DELUXE 282 203 9330 275 463 122 S 275 468 119 S 155 327 109 R 161-193 270-324 45 330 330 370 1 2 3 155 409 102 M 6" 15 X-LARGE 282 203 9621 275 468 120 S 155 327 109 R 350-420 45 330 370 2 3 275 406 103 S 155 409 102 M FOOTNOTES: (1) Lightning arrestors 150 814 902 are suitable for all control boxes. (2) S = Start, M = Main, L = Line, R = Run Deluxe = Control box with line contactor. (3) For 208-volt systems or where line voltage is between 200 volts and 210 volts, a low voltage relay is required. On 3 hp and smaller control boxes use relay part 155 031 103 in place of 155 031 102 and use the next larger cable size than specified in the 230-volt table. On 5 hp and larger use relay 155 031 602 in place of 155 031 601 and next larger wire. Boost transformers per page 15 are an alternative to special relays and cable. (4) Control box model 282 300 8610 is designed for use with motors having internal overload protectors. If used with a 1.5 hp motor manufactured prior to date code 06H18, Overload/Capacitor Kit 305 388 901 is required. (5) Control box model 282 300 8110 with date code 11C19 (March 2011) and newer contain 15 MFD run capacitor and both start and run overloads. This box is designed for use with any Franklin 1.5 hp motor. 51 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS Table 51 Integral hp Capacitor Replacement Kits CAPACITOR NUMBER KIT 275 463 120 305 206 920 275 463 122 305 206 922 275 463 123 305 206 923 275 464 113 305 207 913 275 468 118 305 208 918 275 468 119 305 208 919 275 468 120 305 208 920 155 327 101 305 203 901 155 327 102 305 203 902 155 327 109 305 203 909 155 327 114 305 203 914 155 328 101 305 204 901 155 328 102 305 204 902 155 328 103 305 204 903 Table 51A Integral hp Overload Replacement Kits OVERLOAD NUMBER KIT 275 406 102 305 214 902 275 406 103 305 214 903 275 406 121 305 214 921 275 406 122 305 214 922 275 411 102 305 215 902 275 411 107 305 215 907 275 411 108 305 215 908 275 411 113 305 215 913 275 411 114 305 215 914 275 411 115 305 215 915 275 411 117 305 215 917 275 411 118 305 215 918 275 411 119 305 215 919 Table 51B Integral hp Voltage Relay Replacement Kits RELAY NUMBER KIT 155 031 102 305 213 902 155 031 103 305 213 903 155 031 601 305 213 961 155 031 602 305 213 962 Table 51C Integral hp Contactor Replacement Kits CONTACTOR KIT 155 325 102 305 226 902 155 326 101 305 347 903 155 326 102 305 347 902 155 429 101 305 347 901 FOOTNOTES: (1) The following kit number changes were made for number consistency purposes only. Parts in the kit did not change. 305 206 922 was 305 206 912 305 206 923 was 305 206 911 305 213 962 was 305 213 904 305 226 902 was 305 226 901 52 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS #ONTROL "OX 7IRING $IAGRAMS GND QD RELAY BLUE YELLOW Y (MOTOR LEADS) ORANGE R (START) BLUE L1 RED BLACK 53 Y (MOTOR LEADS) L1 QD RELAY CAP B L2 1/3 - 1 hp QD RELAY 280 10_ 4915 Sixth digit depends on hp (LINE LEADS) RED B (MAIN) GREEN YELLOW R (START) L2 (LINE LEADS) BLUE GREEN START CAPACITOR B (MAIN) CAPACITOR RED L1 BLACK B RUN CAPACITOR GREEN GND GND ORANGE CAP L1 GND GREEN 1/2 - 1 hp CRC QD RELAY 282 40_ 5015 Sixth digit depends on hp -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS START CAPACITOR RUN CAPACITOR BLK BLK RED ORG YEL 5 RELAY GROUND LEAD L1 BLK RED RED 2 YEL 1 YEL BLK RED L2 YEL BLK LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. 3 BLU 1 2 OVERLOAD GROUND TO LEAD MOTOR 1 - 1.5 hp 282 300 8110 (Date Codes 11C19 & Older) START CAPACITOR RUN CAPACITOR RUN CAPACITOR START CAPACITOR BLK RED BLK BLK ORG RED ORG 5 YEL 2 RED RELAY 1 YEL 5 RELAY L1 GROUND LEAD MAIN OVERLOAD BLK 1 3 LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. BLK 1 3 BLK START OVERLOAD 1 - 1.5 hp 282 300 8110 (Date Codes 11C19 & Newer) GROUND LEAD L1 RED BLK BLK YEL GROUND LEAD YEL BLK RED YEL BLU LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. L2 RED 2 RED YEL 1 YEL BLK RED L2 YEL BLK BLK GROUND TO MOTOR LEAD TO MOTOR 1 - 1.5 hp 282 300 8610 54 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS START CAPACITOR RUN CAPACITOR START CAPACITOR RUN CAPACITOR BLK BLK L2 L1 ORG T1 YEL 2 RED ORG YEL T2 RELAY 1 BLK RED YEL COIL 5 BLK YEL LINE CONTACTOR BLK RED YEL 5 RELAY RED 2 1 BLU BLK YEL LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. 1 MAIN OVERLOAD BLK 1 3 BLK 3 SW L1 GROUND LEAD GROUND LEAD START OVERLOAD TO MOTOR LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER TO PRESSURE OR OTHER CONTROL SWITCH 2 hp STANDARD 282 301 8110 BLK YEL BLK RED L2 3 1 1 GROUND LEAD 3 START OVERLOAD MAIN OVERLOAD TO MOTOR 2 hp DELUXE 282 301 8310 START CAPACITOR RUN CAPACITOR RED YEL BLK YEL BLK RED L2 BLU L1 GROUND LEAD RED YEL BLK BLK START CAPACITOR RUN CAPACITOR BLK BLK L2 L1 BLK RED ORG T1 ORG YEL T2 YEL RELAY YEL GROUND LEAD BLK BLU BLK 1 1 2 2 BLK START OVERLOAD 3 hp STANDARD 282 302 8110 55 RED YEL BLK RED YEL GROUND LEAD TO MOTOR LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER TO PRESSURE OR OTHER CONTROL SWITCH SW L1 L2 YEL BLK RED BLU L2 BLK YEL L1 GROUND LEAD RED 2 RED 1 BLK BLK BLK RED 2 MAIN OVERLOAD YEL 5 RELAY LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. BLK RED YEL COIL 5 1 BLK YEL LINE CONTACTOR 2 1 MAIN OVERLOAD 3 hp DELUXE 282 302 8310 1 2 GROUND LEAD START TO OVERLOAD MOTOR -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS START CAPACITOR START CAPACITOR BLK BLK RUN CAPACITOR RUN CAPACITOR BLK BLK RED BLK RED RED T1 L1 YEL 5 BLK BLK RED 2 LINE CONTACTOR COIL COIL BLK RELAY 1 T2 L2 YEL YEL 5 YEL YEL ORG ORG BLK RED RELAY L1 YEL L2 GROUND LEAD RED BLK L1 SW L2 BLK RED YEL BLK RED YEL GROUND LEAD RED 2 1 YEL RED BLK BLK 1 2 2 1 START OVERLOAD MAIN OVERLOAD GROUND TO LEAD MOTOR LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER 5 hp STANDARD 282 113 8110 TO PRESSURE OR OTHER CONTROL SWITCH BLK BLU BLU LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. BLK YEL 1 2 1 2 START OVERLOAD MAIN OVERLOAD GROUND TO LEAD MOTOR 5 hp DELUXE 282 113 8310 or 282 113 9310 START CAPACITOR START CAPACITOR ORG BLK RUN CAPACITOR BLK START CAPACITOR BLK BLK BLK START CAPACITOR RED RED ORG YEL RELAY ORG 1 T1 L1 RED YEL 5 ORG 2 LINE CONTACTOR COIL COIL YEL 5 YEL T2 L2 RUN CAPACITOR BLK YEL RELAY 1 RED 2 BLK SURGE ARRESTOR YEL L2 SW L1 GROUND LEAD BLK BLK 3 1 1 2 MAIN OVERLOAD START OVERLOAD 7.5 hp STANDARD 282 201 9210 GROUND LEAD TO MOTOR LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER L2 YEL RED YEL RED BLK RED BLK YEL BLU LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. L1 RED BLK BLU GROUND LEAD BLK YEL SURGE ARRESTOR TO PRESSURE OR OTHER CONTROL SWITCH 2 3 1 1 BLK BLK MAIN OVERLOAD START OVERLOAD GROUND LEAD TO MOTOR 7.5 hp DELUXE 282 201 9310 56 -!).4%.!.#% 3INGLE 0HASE -OTORS #ONTROLS START CAPACITOR START CAPACITOR START CAPACITOR BLK BLK ORG ORG BLK ORG BLK ORG START CAPACITOR BLK START CAPACITOR RED RED RED BLK RED RUN CAPACITOR YEL YEL T2 L2 LINE CONTACTOR BLK BLK COIL COIL BLK YEL 5 RED 2 RELAY 1 BLK RED YEL RED RED GROUND LEAD 1 2 MAIN OVERLOAD GROUND LEAD START OVERLOAD TO MOTOR LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER 10 hp STANDARD 282 202 9210 or 282 202 9230 RUN CAPACITOR G RED L2 YEL BLK TO PRESSURE OR OTHER CONTROL SWITCH 1 MAIN OVERLOAD START OVERLOAD GROUND TO LEAD MOTOR RUN CAPACITOR BLK RED RED RED T2 COIL SURGE ARRESTOR COIL T2 1 2 2 LINE CONTACTOR L1 COIL T1 YEL 5 ORG BLK T1 L1 BLK COIL 1 5 RELAY RELAY L2 YEL BLK 5 YEL L2 BLK YEL BLK 2 START CAPACITOR BLK BLK OR L1 SW 10 hp DELUXE 282 202 9230 or 282 202 9330 START CAPACITOR BLK SW BLK BLK BLK START CAPACITOR SURGE ARRESTOR YEL BLK LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER, AND OTHER CONTROL IF USED. YEL L2 BLK L1 RED 2 YEL SURGE ARRESTOR GROUND LEAD YEL 5 ORG 1 BLK T1 L1 RELAY ORG RUN CAPACITOR BLK BLK BLK START CAPACITOR RELAY 1 RED 2 L2 L1 GROUND LEAD SURGE ARRESTOR RED SW GROUND LEAD YEL BLK 1 TO PRESSURE OR OTHER CONTROL SWITCH MAIN OVERLOAD BLK 2 START OVERLOAD GROUND TO LEAD MOTOR 15 hp DELUXE 282 203 9310 or 282 203 9330 57 B R Y RED L2 BLK BLK LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER L1 SW SW SW LINE POWER FROM TWO POLE FUSED SWITCH OR CIRCUIT BREAKER 1 2 TO PRESSURE OR OTHER CONTROL SWITCH MAIN OVERLOAD START OVERLOAD 15 hp X-LARGE 282 203 9621 GROUND LEAD TO MOTOR -!).4%.!.#% %LECTRONIC 0RODUCTS Pumptec-Plus Pumptec-Plus is a pump/motor protection device designed to work on any 230 V single-phase induction motor (PSC, CSCR, CSIR, and split phase) ranging in size from 1/2 to 5 horsepower. Pumptec-Plus uses a micro-computer to continuously monitor motor power and line voltage to provide protection against dry well, water logged tank, high and low voltage and mud or sand clogging. Pumptec-Plus – Troubleshooting During Installation SYMPTOM POSSIBLE CAUSE SOLUTION Unit Appears Dead (No Lights) No Power to Unit Check wiring. Power supply voltage should be applied to L1 and L2 terminals of the Pumptec-Plus. In some installations the pressure switch or other control devices is wired to the input of the Pumptec-Plus. Make sure this switch is closed. Unit Needs to Be Calibrated Pumptec-Plus is calibrated at the factory so that it will overload on most pump systems when the unit is first installed. This overload condition is a reminder that the PumptecPlus unit requires calibration before use. See step 7 of the installation instructions. Miscalibrated Pumptec-Plus should be calibrated on a full recovery well with the maximum water flow. Flow restrictors are not recommended. 2-Wire Motor Step C of the calibration instructions indicate that a flashing green light condition will occur 2 to 3 seconds after taking the SNAPSHOT of the motor load. On some two-wire motors the yellow light will flash instead of the green light. Press and release the reset button. The green should start flashing. Flashing Yellow Light Flashing Yellow Light During Calibration Power Interruption During the installation of Pumptec-Plus power may be switched on and off several times. If power is cycled more than four times within a minute Pumptec-Plus will trip on rapid cycle. Press and release the reset button to restart the unit. Float Switch A bobbing float switch may cause the unit to detect a rapid cycle condition on any motor or an overload condition on two-wire motors. Try to reduce water splashing or use a different switch. Flashing Red and Yellow Lights High Line Voltage Flashing Red Light Unloaded Generator Low Line Voltage The line voltage is over 253 volts. Check line voltage. Report high line voltage to the power company. If you are using a generator the line voltage may become too high when the generator unloads. Pumptec-Plus will not allow the motor to turn on again until the line voltage returns to normal. Overvoltage trips will also occur if line frequency drops too far below 60 Hz. The line voltage is below 207 volts. Check line voltage. Loose Connections Check for loose connections which may cause voltage drops. Loaded Generator If you are using a generator the line voltage may become too low when the generator loads. Pumptec-Plus will trip on undervoltage if the generator voltage drops below 207 volts for more than 2.5 seconds. Undervoltage trips will also occur if the line frequency rises too far above 60 Hz. Solid Red Light 58 -!).4%.!.#% %LECTRONIC 0RODUCTS Pumptec-Plus Pumptec-Plus - Troubleshooting SYMPTOM After Installation POSSIBLE CAUSE SOLUTION Dry Well Wait for the automatic restart timer to time out. During the time out period the well should recover and fill with water. If the automatic reset timer is set to the manual position, then the reset button must be pressed to reactivate the unit. Blocked Intake Solid Yellow Light Blocked Discharge Remove blockage in plumbing. Check Valve Stuck Replace check valve. Broken Shaft Replace broken parts. Severe Rapid Cycling Worn Pump Yellow Flashing Light Float Switch A bobbing float switch can cause two-wire motors to stall. Arrange plumbing to avoid splashing water. Replace float switch. Ground Fault Check insulation resistance on motor and control box cable. Loose Connections High Line Voltage Rapid Cycle The line voltage is below 207 volts. Pumptec-Plus will try to restart the motor every two minutes until line voltage is normal. Check for excessive voltage drops in the system electrical connections (i.e. circuit breakers, fuse clips, pressure switch, and Pumptec-Plus L1 and L2 terminals). Repair connections. The line voltage is over 253 volts. Check line voltage. Report high line voltage to the power company. The most common cause for the rapid cycle condition is a waterlogged tank. Check for a ruptured bladder in the water tank. Check the air volume control or snifter valve for proper operation. Check setting on the pressure switch and examine for defects. Leaky Well System Replace damaged pipes or repair leaks. Stuck Check Valve Failed valve will not hold pressure. Replace valve. Float Switch 59 Replace worn pump parts and recalibrate. Repair or replace motor. Pump may be sand or mud locked. Solid Red Light Flashing Red and Yellow Lights Machine gun rapid cycling can cause an underload condition. See flashing red and yellow lights section below. Stalled Motor Low Line Voltage Flashing Red Light Clear or replace pump intake screen. Press and release the reset button to restart the unit. A bobbing float switch may cause the unit to detect a rapid cycle condition on any motor or an overload condition on 2-wire motors. Try to reduce water splashing or use a different switch. -!).4%.!.#% %LECTRONIC 0RODUCTS 1$ 0UMPTEC AND 0UMPTEC QD Pumptec and Pumptec are load sensing devices that monitor the load on submersible pumps/motors. If the load drops below a preset level for a minimum of 4 seconds the QD Pumptec or the Pumptec will shut off the motor. The QD Pumptec is designed and calibrated expressly for use on Franklin Electric 230 V 3-wire motors (1/3 to 1 hp.) The QD Pumptec must be installed in QD relay boxes. The Pumptec is designed for use on Franklin Electric 2- and 3-wire motors (1/3 to 1.5 hp) 115 and 230 V. The Pumptec is not designed for jet pumps. QD Pumptec & Pumptec – Troubleshooting SYMPTOM CHECKS OR SOLUTION A. Is the voltage less than 90% of nameplate rating? B. Are the pump and motor correctly matched? If the QD Pumptec or Pumptec trips in about 4 seconds with some water delivery. C. Is the QD Pumptec or Pumptec wired correctly? For the Pumptec check the wiring diagram and pay special attention to the positioning of the power lead (230 V or 115 V). D. For QD Pumptec is your system 230 V 60 Hz or 220 V 50 Hz? A. The pump may be airlocked. If there ia a check valve on top of the pump, put another section of pipe between the pump and the check valve. If the QD Pumptec or Pumptec trips in about 4 seconds with no water delivery. B. The pump may be out of water. C. Check the valve settings. The pump may be dead-heading. D. Pump or motor shaft may be broken. E. Motor overload may be tripped. Check the motor current (amperage). If the QD Pumptec or Pumptec will not timeout and reset. A. Check switch position on side of circuit board on Pumptec. QD Pumptec check timer position on top/front of unit. Make sure the switch is not between settings. B. If the reset time switch is set to manual reset (position 0), QD Pumptec and Pumptec will not reset (turn power off for 5 sec. then back on to reset). A. Check voltage. B. Check wiring. If your pump/motor will not run at all. C. Remove the QD Pumptec from the control box. Reconnect wires in box to original state. If motor does not run the problem is not QD Pumptec. Bypass Pumptec by connecting L2 and motor lead with jumper. Motor should run. If not, the problem is not Pumptec. D. On Pumptec only check that Pumptec is installed between the control switch and the motor. A. Be sure you have a Franklin motor. B. Check wiring connections. On Pumptec is lead power (230 V or 115 V) connected to correct terminal? Is motor lead connected to correct terminal? C. Check for ground fault in the motor and excessive friction in the pump. If your QD Pumptec or Pumptec will not trip when the pump breaks suction. $ 4HE WELL MAY BE hGULPINGv ENOUGH WATER TO KEEP QD Pumptec or Pumptec from tripping. It may be necessary to adjust the QD Pumptec or the Pumptec for these extreme applications. Call the Franklin Electric Service Hotline at 800-348-2420 for information. E. On Pumptec applications does the control box have a run capacitor? If so, Pumptec will not trip. (Except for Franklin 1.5 hp motors). A. Check for low voltage. If your QD Pumptec or Pumptec chatters when running. B. Check for waterlogged tank. Rapid cycling for any reason can cause the QD Pumptec or the Pumptec relay to chatter. C. On Pumptec make sure the L2 and motor wires are installed correctly. If they are reversed, the unit can chatter. 60 -!).4%.!.#% %LECTRONIC 0RODUCTS 3UB$RIVE7 -ONO$RIVE -ONO$RIVE 84 The Franklin Electric SubDrive/MonoDrive Constant Pressure controller is a variable-speed drive that delivers water at a constant pressure. WARNING: Serious or fatal electrical shock may result from failure to connect the motor, SubDrive/MonoDrive Controller, metal plumbing and all other metal near the motor or cable to the power supply ground terminal using wire no smaller than motor cable wires. To reduce the risk of electrical shock, disconnect power before working on or around the water system. Capacitors inside the SubDrive/MonoDrive Controller can still hold a lethal voltage even after power has been removed. Allow 10 minutes for dangerous internal voltage to discharge. Do not use motor in swimming areas. 61 -!).4%.!.#% %LECTRONIC 0RODUCTS 3UB$RIVE7 -ONO$RIVE -ONO$RIVE 84 SubDrive/MonoDrive Troubleshooting 3HOULD AN APPLICATION OR SYSTEM PROBLEM OCCUR BUILT IN DIAGNOSTICS WILL PROTECT THE SYSTEM 4HE h&!5,4v LIGHT OR DIGITAL display on the front of the SubDrive/MonoDrive Controller will flash a given number of times or display a number indicating the nature of the fault. In some cases, the system will shut itself off until corrective action is taken. Fault codes and their corrective actions are listed below. See SubDrive/MonoDrive Installation Manual for installation data. NUMBER OF FLASHES OR DIGITAL DISPLAY 1 FAULT MOTOR UNDERLOAD POSSIBLE CAUSE CORRECTIVE ACTION - Overpumped well - Broken shaft or coupling - Blocked screen, worn pump - Air/gas locked pump - SubDrive not set properly for pump end - Frequency near maximum with less than 65% of expected load, 42% if $)0 IS hONv - System is drawing down to pump inlet (out of water) (IGH STATIC LIGHT LOADING PUMP RESET $)0 SWITCH TO hONv FOR LESS sensitivity if not out of water - Check pump rotation (SubDrive only) reconnect if necessary for proper rotation - Air/gas locked pump - if possible, set deeper in well to reduce - Verify DIP switches are set properly - Low line voltage - Misconnected input leads - Line voltage low, less than approximately 150 VAC (normal operating range = 190 to 260 VAC) - Check incoming power connections and correct or tighten if necessary - Correct incoming voltage - check circuit breaker or fuses, contact power company 2 UNDERVOLTAGE 3 LOCKED PUMP - Motor and/or pump misalignment - Dragging motor and/or pump - Abrasives in pump - Amperage above SFL at 10 Hz - Remove and repair or replace as required INCORRECTLY WIRED - MonoDrive only - Wrong resistance values on main and start - Wrong resistance on DC test at start - Check wiring, check motor size and DIP switch setting, adjust or repair as needed OPEN CIRCUIT - Loose connection - Defective motor or drop cable - Wrong motor - Open reading on DC test at start. - Check drop cable and motor resistance, tighten output connections, repair OR REPLACE AS NECESSARY USE hDRYv MOTOR TO CHECK DRIVE FUNCTIONS IF DRIVE will not run and exhibits underload fault replace drive SHORT CIRCUIT - When fault is indicated immediately after power-up, short circuit due to loose connection, defective cable, splice or motor - Amperage exceeded 50 amps on DC test at start or max amps during running - Incorrect output wiring, phase to phase short, phase to ground short in wiring or motor - If fault is present after resetting and removing motor leads, replace drive - When fault is indicated while motor is running, over current due to loose debris trapped in pump - Check pump - High ambient temperature - Direct sunlight - Obstruction of airflow - Drive heat sink has exceeded max rated temperature, needs to drop below 85 °C to restart - Fan blocked or inoperable, ambient above 125 °F, direct sunlight, air flow blocked - Replace fan or relocate drive as necessary - Improper pre-charge - Valve closing too fast - Pressure setting too close to relief valve rating - Reset the pre-charge pressure to 70% of sensor setting. Reduce pressure setting well below relief valve rating. Use next size larger pressure tank. - Verify valve operation is within manufacturer’s specifications. - Reduce system pressure setting to a value less than pressure relief rating. - A fault was found internal to drive - Unit may require replacement. Contact your supplier. - Wrong hp/voltage - Internal fault - Verify motor hp and voltage - Unit may require replacement. Contact your supplier. 4 (MonoDrive & MonoDriveXT only) 5 6 OVER CURRENT 7 8 (SubDrive300 only) RAPID 9 (SubDrive2W only) OVERHEATED DRIVE OVER PRESSURE INTERNAL FAULT OVER RANGE (Values outside normal operating range) 62 -!).4%.!.#% %LECTRONIC 0RODUCTS 3UB-ONITOR SubMonitor Troubleshooting FAULT MESSAGE SF Amps Set Too High Phase Reversal PROBLEM/CONDITION SF Amps setting above 359 Amps. Motor SF Amps not entered. Reversed incoming voltage phase sequence. Incoming power problem. Normal line current. Wrong SF Max Amps setting. Low line current. Over pumping well. Clogged pump intake. Closed valve. Loose pump impeller. Broken shaft or coupling. Phase loss. Normal line current. Wrong SF Max Amps setting. High line current. High or low line voltage. Ground fault. Pump or motor dragging. Motor stalled or bound pump. Motor temperature sensor has detected excess motor temperature. High or low line voltage. Motor is overloaded. Excessive current unbalance. Poor motor cooling. High water temperature. Excessive electrical noise (VFD in close proximity). Current difference between any two legs exceeds programmed setting. Phase loss. Unbalanced power supply. Open Delta transformer. Line voltage exceeds programmed setting. Unstable power supply. Line voltage below programmed setting. Poor connection in motor power circuit. Unstable or weak power supply. Power has been interrupted too many times in a 10 second period. Chattering contacts. Loose connections in motor power circuit. Arcing contacts. Underload Overload Overheat Unbalance Overvoltage Undervoltage False Starts 63 POSSIBLE CAUSE Continued on next page -!).4%.!.#% %LECTRONIC 0RODUCTS 3UBTROL 0LUS /BSOLETE 3EE 3UB-ONITOR Subtrol-Plus - Troubleshooting After Installation SYMPTOM Subtrol-Plus Dead POSSIBLE CAUSE OR SOLUTION When the Subtrol-Plus reset button is depressed and released, all indicator lights should flash. If line voltage is correct at the Subtrol-Plus L1, L2, L3 terminals and the reset button does not cause lights to flash, Subtrol-Plus receiver is malfunctioning. Green Off Time Light Flashes The green light will flash and not allow operation unless both sensor coils are plugged into the receiver. If both are properly connected and it still flashes, the sensor coil or the receiver is faulty. An ohmmeter check between the two center terminals of each sensor coil connected should read less than 1 ohm, or coil is faulty. If both coils check good, receiver is faulty. Green Off Time Light On The green light is on and the Subtrol-Plus requires the specified off time before the pump can be restarted after having been turned off. If the green light is on except as described, the receiver is faulty. Note that a power interruption when the motor is running will initiate the delay function. Overheat Light On This is a normal protective function which turns off the pump when the motor reaches maximum safe temperatures. Check that amps are within the nameplate maximum on all three lines, and that the motor has proper water flow past it. If overheat trip occurs without apparent motor overheating, it may be the result of an arcing connection somewhere in the circuit or extreme noise interference on the power lines. Check with the power company or Franklin Electric. A true motor overheat trip will require at least five minutes for a motor started cold. If trips do not conform to this characteristic, suspect arcing connections, power line noise, ground fault, or SCR variable speed control equipment. Overload Light On This is a normal protective function, protecting against an overload or locked pump. Check the amps in all lines through a complete pumping cycle, and monitor whether low or unbalanced voltage may be causing high amps at particular times. If overload trip occurs without high amps, it may be caused by a faulty rating insert, receiver, or sensor coil. Recheck that the insert rating matches the motor. If it is correct, carefully remove it from the receiver by alternately lifting sides with a knife blade or thin screwdriver, and make sure it has no pins bent over. If the insert is correct and its pins are okay, replace receiver and/or sensor coils. This is a normal protective function. A. Make sure the rating insert is correct for the motor. Underload Light On B. Adjusting the underload setting as described to allow the desired range of operating conditions. Note that a DECREASE in underload setting is required to allow loading without trip. C. Check for drop in amps and delivery just before trip, indicating pump breaking suction, and for unbalanced line current. D. With the power turned off, recheck motor lead resistance to ground. A grounded lead can cause underload trip. 64 -!).4%.!.#% %LECTRONIC 0RODUCTS 3UBTROL 0LUS /BSOLETE 3EE 3UB-ONITOR Subtrol-Plus - Troubleshooting After Installation (Continued) SYMPTOM Tripped Light On Control Circuit Fuse Blows Contactor Will Not Close POSSIBLE CAUSE OR SOLUTION Whenever the pump is off as a result of Subtrol-Plus protective function, the red tripped light is on. A steady light indicates the Subtrol-Plus will automatically allow the pump to restart as described, and a flashing light indicates repeated trips, requiring manual reset before the pump can be restarted. Any other red light operation indicates a faulty receiver. One-half voltage on 460 V will cause tripped light on. With power turned off, check for a shorted contactor coil or a grounded control circuit lead. The coil resistance should be at least 10 ohms and the circuit resistance to panel frame over 1 megohm. A standard or delay-type 2 amp fuse should be used. If proper voltage is at the control coil terminals when controls are operated to turn the pump on, but the contactor does not close, turn off power and replace the coil. If there is no voltage at the coil, trace the control circuit to determine if the fault is in the Subtrol-Plus receiver, fuse, wiring, or panel operating switches. This tracing can be done by first connecting a voltmeter at the coil terminals, and then moving the meter connections step by step along each circuit to the power source, to determine at which component the voltage is lost. With the Subtrol-Plus receiver powered up, with all leads disconnected from the control terminals and with an ohmmeter set at RX10, measure the resistance between the control terminals. It should measure 100 to 400 ohms. Depress and hold in the reset button. The resistance between the control terminals should measure close to infinity. 65 Contactor Hums or Chatters Check that coil voltage is within 10% of rated voltage. If voltage is correct and matches line voltage, turn off power and remove the contactor magnetic assembly and check for wear, corrosion, and dirt. If voltage is erratic or lower than line voltage, trace the control circuit for faults similar to the previous item, but looking for a major drop in voltage rather than its complete loss. Contactor Opens When Start Switch is Released Check that the small interlocks switch on the side of the contactor closes when the contactor closes. If the switch or circuit is open, the contactor will not stay closed when the selector switch is in HAND position. Contactor Closes But Motor Doesn’t Run Turn off power. Check the contactor contacts for dirt, corrosion, and proper closing when the contactor is closed by hand. Signal Circuit Terminals Do Not Energize With the Subtrol-Plus receiver powered up and all leads disconnected from the signal terminals, with an 0hmmeter set at RX10, measure the resistance between the signal terminals. Resistance should measure close to infinite. Depress and hold in the reset button. The resistance between the signal terminals should measure 100 to 400 ohms. !)- -!.5!, !BBREVIATIONS A Amp or amperage MCM Thousand Circular Mils AWG American Wire Gauge mm Millimeter BJT Bipolar Junction Transistor MOV Metal Oxide Varister °C Degree Celsius NEC National Electrical Code CB Control Box NEMA CRC Capacitor Run Control National Electrical Manufacturer Association DI Deionized Nm Newton Meter Dv/dt Rise Time of the Voltage NPSH Net Positive Suction Head EFF Efficiency OD Outside Diameter °F Degree Fahrenheit OL Overload FDA Federal Drug Administration PF Power Factor FL Full Load psi Pounds per Square Inch ft Foot PWM Pulse Width Modulation ft-lb Foot Pound QD Quick Disconnect ft/s Feet per Second R Resistance GFCI Ground Fault Circuit Interrupter RMA Return Material Authorization gpm Gallon per Minute RMS Root Mean Squared HERO High Efficiency Reverse Osmosis rpm Revolutions per Minute hp Horsepower SF Service Factor Hz Hertz SFhp Service Factor Horsepower ID Inside Diameter S/N Serial Number IGBT Insulated Gate Bipolar Transistor TDH Total Dynamic Head in Inch UNF Fine Thread kVA Kilovolt Amp V Voltage kVAR Kilovolt Amp Rating VAC Voltage Alternating Current kW Kilowatt (1000 watts) VDC Voltage Direct Current L1, L2, L3 Line One, Line Two, Line Three VFD Variable Frequency Drive lb-ft Pound Feet W Watts L/min Liter per Minute XFMR Transformer mA Milliamp Y-D Wye-Delta max Maximum 1 ohms 66 !)- -!.5!, .OTES !)- -!.5!, .OTES !)- -!.5!, .OTES !)- -!.5!, .OTES TOLL FREE HELP FROM A FRIEND nääÎ{nÓ{ÓäÊUÊÓÈänÓÇx£äÓÊv>Ý® Phone Franklin’s toll free SERVICE HOTLINE for answers to your pump and motor installation questions. When you call, a Franklin expert will offer assistance in troubleshooting and provide immediate answers to your system application questions. Technical support is also available online. Visit our website at: ÜÜÜ°vÀ>iiVÌÀV°V The Company You Trust Deep Down M1311 07.11
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes Apple Keywords : Author : Brown, Tyler Create Date : 2011:08:05 17:23:56Z Modify Date : 2014:06:09 11:34:21-04:00 Subject : XMP Toolkit : Adobe XMP Core 5.4-c005 78.147326, 2012/08/23-13:03:03 Creator Tool : Preview Metadata Date : 2014:06:09 11:34:21-04:00 Format : application/pdf Description : Creator : Brown, Tyler Title : M1311_60_Hz_AIM_Catalog Keywords : Producer : Mac OS X 10.6.6 Quartz PDFContext Document ID : uuid:61bbdb03-36bf-3e4e-abb5-b14e49466fd6 Instance ID : uuid:769ae075-ec28-4486-b371-0f67305fbc5e Page Count : 80EXIF Metadata provided by EXIF.tools