NOTICE TO INSTALLER: Instructions must remain with installation.
Your Peace of Mind is Our Top Priority
Product information presented
here reflects conditions at time
of publication. Consult factory
regarding discrepancies or
inconsistencies.
OR
LE F
T HO E
N
E
V
TION
VALV
ICE:
NOT CHECK ION SEC E 3
G
T
A
U
CA
NP
#3 IN ND #4 O
E
E
A
S
OW
BEL

Section: 6.10.072
FM2562
0113
Supersedes
1111

®

®

MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624

visit our web site:
www.zoeller.com
DATE INSTALLED:
MODEL NUMBER:

PREASSEMBLED SUMP PUMP SYSTEM WITH BATTERY BACKUP
MODEL 507 - 12V DC BATTERY BACKUP SYSTEM
WITH 120V AC POWERED SUMP PUMP
MODEL WM49, M53 or M98

INSTALLATION INSTRUCTIONS

SEE BELOW FOR
LIST OF CAUTIONS

SEE BELOW FOR
LIST OF WARNINGS
1. Make certain that the receptacle is within the reach of the pump’s power supply cord.
Do not use primary pump circuit. DO NOT USE AN EXTENSION CORD. Extension
cords that are too long or too light do not deliver sufficient voltage to the pump motor.
But, more important, they could present a safety hazard if the insulation were to
become damaged or the connection end were to fall into the sump.
2. Make sure the pump electrical supply circuit is equipped with fuses or circuit breakers
of proper capacity. A separate branch circuit is recommended, sized according to
the “National Electrical Code” for the current shown on the pump nameplate.
3. Testing for ground. As a safety measure, each electrical outlet should be checked for
ground using an Underwriters Laboratory Listed circuit analyzer which will indicate
if the power, neutral and ground wires are correctly connected to your outlet. If they
are not, call a qualified licensed electrician.
4. For Added Safety. Pumping and other equipment with a 3-prong grounded plug must
be connected to a 3-prong grounded receptacle. For added safety the receptacle
may be protected with a ground-fault circuit interrupter. When a pump needs to be
connected in a watertight junction box, the plug can be removed and spliced to the
supply cable with proper grounding. For added safety this circuit may be protected
by a ground-fault circuit interrupter. The complete installation must comply with the
National Electrical Code and all applicable local codes and ordinances.
5. FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS POWER
SOURCE BEFORE HANDLING. Single phase pumps are supplied with a 3-prong
grounded plug to help protect you against the possibility of electrical shock. DO
NOT UNDER ANY CIRCUMSTANCES REMOVE THE GROUND PIN. The 3-prong
plug must be inserted into a mating 3-prong grounded receptacle. If the installation
does not have such a receptacle, it must be changed to the proper type, wired and
grounded in accordance with the National Electrical Code and all applicable local
codes and ordinances.
6. The tank is to be vented in accordance with local plumbing code. Pumps must be
installed in accordance with the National Electrical Code and all applicable local codes
and ordinances. Pumps are not to be installed in locations classified as hazardous
in accordance with National Electrical Code, ANSI/NFPA 70.
7.
“Risk of electrical shock” Do not remove power supply cord and strain relief
or connect conduit directly to the pump.
8. Installation and servicing of electrical circuits and hardware should be performed by
a qualified licensed electrician.
9. Pump installation and servicing should be performed by a qualified person.
10. Risk of electric shock - These pumps have not been investigated for use in swimming
pool and marine areas.
11. According to the state of California (Prop 65), this product contains chemicals known
to the state of California to cause cancer and birth defects or other reproductive harm.
12. It is the owner’s responsibility to check the battery and battery connection at least
once a month. Batteries contain acid and caution must be taken when handling.

1. Check to be sure your power source is capable of handling the voltage requirements
of the motor, as indicated on the pump name plate.
2. The installation of automatic pumps with variable level float switches or nonautomatic pumps using auxiliary variable level float switches is the responsibility of
the installing party and care should be taken that the tethered float switch will
not hang up on the pump apparatus or pit peculiarities and is secured so that the
pump will shut off. It is recommended to use rigid piping and fittings and the pit
be 18" or larger in diameter.
3. Information - vent hole purpose. It is necessary that all submersible sump, effluent,
and sewage pumps capable of handling various sizes of solid waste be of the
bottom intake design to reduce clogging and seal failures. If a check valve is
incorporated in the installation, a vent hole (approx. 3/16") must be drilled in the
discharge pipe below the check valve and pit cover to purge the unit of trapped
air. Trapped air is caused by agitation and/or a dry basin. Vent hole should be
checked periodically for clogging. The 50 Series pumps have a vent located in
the pump housing opposite the float, adjacent to a housing lug, but an additional
vent hole is recommended. If you choose not to drill a vent hole, be sure the
pump case and impeller is covered with liquid before connecting the pipe to the
check valve and no inlet carries air to the pump intake. NOTE: THE HOLE
MUST ALSO BE BELOW THE BASIN COVER AND CLEANED PERIODICALLY.
Water stream will be visible from this hole during pump run periods.
4. Pump should be checked frequently for debris and/or build up which may interfere
with the float “on” or “off” position. Repair and service should be performed by
Zoeller Pump Company Authorized Service Station only.
5. Dewatering and effluent sump pumps are not designed for use in pits handling
raw sewage.
6. Maximum operating temperature must not exceed 104ºF (40ºC).
7. Do not operate a pump in an application where the Total Dynamic Head is less
than the minimum Total Dynamic Head listed on the Pump Performance Curves.
8. For indoor use only.
9. DC emergency pumps are designed for handling clear water. Do not use in septic
tanks to pump effluent or sewage pits to pump sewage.
10. Repair and service of your DC backup system should be performed by an
authorized service station.
11. The installation of DC automatic backup pumps requires the use of a variable level
float switch for operation. It is the responsibility of the installing party, to ensure
that the float switch will not hang up on the pump apparatus or pit peculiarities and
is secured so the pump will turn “on” and “off”. It is recommended that the pit be
18" in diameter or larger to accommodate both a primary and a DC backup pump.
NOTE: Pumps with the “UL” mark and pumps with the “US” mark are tested to UL Standard UL778.
CSA Certified pumps are certified to CSA Standard C22.2 No. 108.
Refer to Warranty on page 2.

© Copyright 2013 Zoeller Co. All rights reserved.

LIMITED WARRANTY
Manufacturer warrants, to the purchaser and subsequent owner during
the warranty period, every new product to be free from defects in material
and workmanship under normal use and service, when properly used and
maintained, for a period of three years from date of purchase by the end
user. Parts that fail within the warranty period, that inspections determine
to be defective in material or workmanship, will be repaired, replaced or
remanufactured at Manufacturer's option, provided however, that by so doing we
will not be obligated to replace an entire assembly, the entire mechanism or the
complete unit. No allowance will be made for shipping charges, damages, labor
or other charges that may occur due to product failure, repair or replacement.
This warranty does not apply to and there shall be no warranty for any material
or product that has been disassembled without prior approval of Manufacturer,
subjected to misuse, misapplication, neglect, alteration, accident or act of
God; that has not been installed, operated or maintained in accordance with
Manufacturer's installation instructions; that has been exposed to outside
substances including but not limited to the following: sand, gravel, cement,
mud, tar, hydrocarbons, hydrocarbon derivatives (oil, gasoline, solvents,
etc.), or other abrasive or corrosive substances, wash towels or feminine
sanitary products, etc. in all pumping applications. The warranty set out in

the paragraph above is in lieu of all other warranties expressed or implied; and
we do not authorize any representative or other person to assume for us any
other liability in connection with our products.
Contact Manufacturer at, 3649 Cane Run Road, Louisville, Kentucky 40211,
Attention: Product Support Department to obtain any needed repair or
replacement of part(s) or additional information pertaining to our warranty.
MANUFACTURER EXPRESSLY DISCLAIMS LIABILITY FOR SPECIAL,
CONSEQUENTIAL OR INCIDENTAL DAMAGES OR BREACH OF
EXPRESSED OR IMPLIED WARRANTY; AND ANY IMPLIED WARRANTY
OF FITNESS FOR A PARTICULAR PURPOSE AND OF MERCHANTABILITY
SHALL BE LIMITED TO THE DURATION OF THE EXPRESSED WARRANTY.
Some states do not allow limitations on the duration of an implied warranty,
so the above limitation may not apply to you. Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you.
This warranty gives you specific legal rights and you may also have other rights
which vary from state to state.

In those instances where damages are incurred as a result of an alleged pump failure,
the Homeowner must retain possession of the pump for investigation purposes.

DESCRIPTION
The DC emergency pump is designed as a backup to your primary sump pump during unexpected power outages or primary pump failure. The DC
pump, electronic controls and all the parts required for installation are included except the battery which is supplied by the user. The system is designed
for installation in sumps with minimum of 18" diameter and 24" deep. For 18" x 22" applications, consult factory.

BATTERY SELECTION
The DC emergency pump system requires a good quality, 12 volt battery to obtain maximum pumping time during a power outage. A deep-cycle, 12
volt, 105 amp-hour marine battery or larger is recommended and will provide approximately 7½ hours of continuous pumping time in a sump pump
installation with 8' of head pressure. In most installations the pump runs intermittently and the battery life is extended accordingly. Batteries with top
terminals are recommended for ease of installation. These batteries contain acid and proper precaution must be taken when handling. Maximum battery size 12½" Length x 7" Width x 9½" Height.

THE AQUANOT ® BATTERY
There are millions of batteries manufactured each year, so it is impossible to guarantee consistent quality. A defective battery will never become fully
charged and may damage the charging circuits of the Control. It is for this reason that Zoeller offers its own line of batteries. We offer both a Water/
Acid Deep-Cycle Battery which can run the pump continuously for over 7½ hours, and a Maintenance-Free AGM Battery, which will power the pump for
over 3½ hours. These times are based on continuous pumping at 10' of static head. Actual times will vary depending on static head, volume of water
entering the pit, and the condition of the battery.
Follow these recommendations:
• Use a B.C.I. size 27 deep-cycle battery, 175 minute reserve capacity, or larger
• Do NOT use a “maintenance-free” battery unless it is a Gel-filled or AGM battery
• Replace your battery every 3 years
• Do not let corrosion build up on the battery terminals
• Do not place your battery on a concrete floor where it will discharge faster
• To check specific gravity, follow the instructions on a hydrometer (not applicable for Gel or AGM batteries)
PROTECT YOUR WARRANTY:
• Water level in batteries must be checked once a month (not applicable for Gel or AGM batteries)

© Copyright 2013 Zoeller Co. All rights reserved.
2

EASY DO'S & DON'TS FOR INSTALLING A SUMP PUMP
1. DO read thoroughly all installation material provided with the system.

6. DO install a union in the discharge line.
2. DO inspect system for any visible damage caused by shipping. Contact 		 DO NOT use a discharge pipe smaller than the pump discharge.
dealer if system appears to be damaged.
7. DO NOT use a sump pump as a trench or excavation pump, or for pumping
sewage, gasoline, or other hazardous liquids.
3. DO clean all debris from the sump. Be sure that the pump will have a hard,
flat surface beneath it. DO NOT install on sand, gravel or dirt.
8. DO test system immediately after installation to be sure that the system is
working properly.
4. DO be sure that the sump is large enough to allow proper clearance for the
level control switch(es) to operate properly.
9. DO cover sump with an adequate sump cover.

5. DO Always Disconnect Pump From Power Source Before Handling.
		 DO always connect to a separately protected and properly grounded circuit.
		 DO NOT ever cut, splice, or damage power cord (Only splice in a watertight
junction box).
		 DO NOT carry or lift pump by its power cord.
		 DO NOT use an extension cord with a sump pump.

10. DO review all applicable local and national codes and verify that the installation
conforms to each of them.
11. DO consult manufacturer for clarifications or questions.
12. DO inspect and test system for proper operations at least every three months.

RECOMMENDED INSTALLATION FOR ALL APPLICATIONS
1.	Electrical wiring and protection must be in accordance with National		
Electrical Code and any other applicable state and local electrical 		
requirements.

7. Basin must be clean and free of debris after installation.

2.	All installations require a basin cover to prevent debris from falling into
the basin and to prevent accidental injury.

9. Gas tight seals required to contain gases and odors.

3.	Securely tape or clamp power cord to discharge pipe, clear of the float
mechanism(s).
4. Use full-size discharge pipe.

8.	Gate Valve or Ball Valve to be supplied by installer and installed
according to any and all codes.
10.	Vent gases and odors to the atmosphere through vent pipe.
11. 	 Install Zoeller Pump Stand (Model 10-2421) under pump to
provide a settling basin.

5.	Basin must be in accordance with applicable codes and specifications.
6.	Pump must be level and float mechanism(s) clear of sides of basin
before starting pump. Float switch may be repositioned as needed.

PERFORMANCE
The DC pump performance with fully charged 12V battery
Discharge Feet of Head

5

10

15

17.5

Flow Gal. per min.

23

15

5

Shut-off Head

The DC controller is equipped with a 10 amp charger for maintaining the battery in a ready state and recharging the battery after use when AC power
is restored. Time for recharge depends upon the amount of power consumed by the pumping cycle during the AC power interruption. The pump may
go back to the ready run position in a very short period of time. A completely drained battery may require up to 24 hours for full recharge. If after 24
hours of charging the battery has not reached 6 volts, the alarm will sound and not reset until the battery is brought up to a voltage of 6.5-7.0 volts.

IMPORTANT NOTICE: Some insurance policies, both commercial and residential, extend coverage for damages incurred by product failure. You will need to
have possession of the product to support your claim in most cases. Zoeller Pump Co. will exchange the unit or refund the original purchase price once the claim
is settled with the insurer in the case where you need to retain possession of the product to support a damage claim you submit to your insurance company.

© Copyright 2013 Zoeller Co. All rights reserved.
3

© Copyright 2013 Zoeller Co. All rights reserved.
4

PUMP DISCHARGE

WEEP HOLE PROVIDED

CHECK VALVE

SEE DETAIL "A"

BATTERY BOX

CHARGER OUTLET

FIGURE 1

(SCALE: 4X)

DETAIL "A"

VERIFY WEEP HOLE IS
VISIBLE. (SEE PUMP
INSTALLATION INSTRUCTIONS)

1"MIN.

(MUST BE INSTALLED
ON TWO SEPARATE
CIRCUITS.)

SK2750

IMPORTANT: OFF LEVEL OF
FLOAT ASSEMBLY MUST BE
1"MIN. ABOVE CENTER OF TEE.
(SEE INSTALLATION NOTE 3.)

PRIMARY PUMP OUTLET

DC PUMP PLUMBED IN LINE WITH SUBMERSIBLE PUMP

TYPICAL INSTALLATION

FIGURE 2
SK2752

For Installation, Maintenance, Troubleshooting and Service Checklist, please refer to
the corresponding Pump Installation Manual and Replacement Parts List.

EXPLODED VIEW OF PUMP SYSTEM

INSTALLATION
1. The preferred method of installation for backup pumps is shown in figure 1.
The installation kit includes one check valve for installing with the backup
pump discharging into the primary pump outlet pipe. An additional check
valve is incorporated in the discharge of the backup pump.
2. Select location for battery and control charger. Control charger must be
within 6' of a 115V wall outlet and within 6' of pump and basin. Connect to
a separate circuit, different than the primary pump.
3. Make certain the float switch clamp is tight on the pipe to avoid slippage.
Use electrical tape below the clamp to help prevent the clamp from moving.
Ensure that the “off” level of the float is 1" min. above the discharge tee of
the DC backup pump (see figure 1). Position pumps in the sump and move
float up and down, making sure of free movement without interference from
any obstructions inside the sump or lid. Very shallow sumps may require
some adjustment to avoid overfilling or backing up of water into the sump
inlet. The float switch can be moved on the discharge pipe or the rubber
stops can be adjusted as necessary. Cut extra float rod length below lower
float stop to prevent debris from interfering with float operation (see figure 2).

5. Connect the leads from the control charger to the battery terminals. Red
pos. (+) lead to positive terminal and black neg. (-) lead to negative battery
terminal. Upon proper connection, test alarm will sound. Press alarm
reset to silence. This indicates proper charger to battery connection.
Correct battery hook up is essential for operation of the
system. Use nuts supplied with battery and eyelet connectors on battery
wire leads. The positive terminal is the larger stud, 3/8" diameter. The
smaller stud, 5/16" diameter is the negative terminal. Apply grease to the
terminals to help prevent corrosion.
6. Connect the black lead from the pump to the negative (-) battery terminal.
Connect the white or red lead from the pump to the white lead from the
switch. This connection is made at the fuse installed on the switch wire
(see figure 3). Connect the black lead from the switch to the positive (+)
battery terminal.
7. Connect the blue sensor wire to the sensor connector (figure 3).
8. Close battery box and secure cover. Carpeted or wood barrier between
the battery case and the floor is recommended.

4. Install DC control charger (see figure 3) by using the wall bracket and 9. Plug the control power cord into the 115V wall outlet. The primary sump
anchors provided. If more convenient, the control charger may be set on
pump and the control box should be on separate circuits.
a nearby shelf or ledge. The control charger should be located 3 or 4 ft.
10.
Reconnect power to primary sump pump.
above the sump. To reduce noise from vibration, it is recommended that
the charger be anchored with the wall bracket provided.

INITIAL START-UP AND OPERATION
1. Test the installation for leaks by running water into the sump allowing for
normal operation of the primary pump.
2. Check the control charger. The “red” power on light will be lit when the unit
is plugged into the 115V wall outlet. The “yellow/green” light will indicate
the condition of the battery.
3. Disconnect primary pump before touching any component in the sump pit.
4. Lift float switch. The DC backup pump will run and the alarm will sound.
Lower float switch immediately after pump has started running. Pump is
running dry during initial check out for several seconds.
Continuous dry running may cause overheating and damage the pump
seals. Upon release of the float switch, the pump will shut off. Press the
reset button to turn the alarm off.

5. Complete the final testing of your installation by disconnecting the power
to the primary pump and the control charger by removing the plugs from
the 115V wall outlets. Run water into the sump until the DC backup pump
is activated by the float switch. Check all connections for leaks.
6. Push alarm reset switch when pump is running. This will silence the alarm.
The pump will continue to run.
7. Reconnect the control charger and your primary pump to the AC wall outlets.
The primary pump should come on and lower the water level in the sump
back to the normal operating level and shut off. Both primary and backup
systems are now ready for use.
8. The battery charged and charging LED’s will alternate during normal
charging operation.

MAINTENANCE
1.

Inspect and test the system for proper operations at least every 3 months.
(a) Red power on indicator light should be “on” indicating AC
power is on.
(b) Unplug primary pump and the control charger from power supply.
(c) Fill sump with water to the “on” level for the DC pump. Allow
pump to run a few minutes.
(d) The alarm will sound approximately 5 seconds after the pump
starts to run.
(e) Push alarm reset switch. The alarm will go “off”.
(f) Pump will shut off after water level is lowered and the float drops
to the off position.

2.

Plug the control charger and the primary pump into the wall outlet.
(a)		T he primary pump will come on and lower the water to the
			normal operating level and shut off.
(b)		The “yellow” charging light should be on. The charger is replacing
the energy consumed during the test. The “green” light will come
on after the charger has replaced the energy consumed during
the test.
3.

Battery should be agitated gently every 3 months.
Battery acid is dangerous. Take proper safety precautions. Do not
splash the acid. Add distilled water to battery when necessary per
battery manufacturer's instructions.

© Copyright 2013 Zoeller Co. All rights reserved.
5

EXPLODED VIEW - DC PUMP
FIGURE 3
CLAMP
15 AMP FUSE

FLOAT SWITCH

WHITE LEAD
TO DC PUMP

DC BACK-UP PUMP

BLACK LEAD
TO POSITIVE

DC CONTROL BOX
BLUE LEAD
TO FLOAT SWITCH

WHITE OR
RED LEAD
TO FLOAT
SPLICER

BLACK WITH RED
TRACER TO POSITIVE

BLACK LEAD
TO NEGATIVE

12 VOLT
MARINE BATTERY
SUPPLIED BY USER

BATTERY BOX

FIG. 5

BLACK LEAD
TO NEGATIVE

SK2501

All installations must comply with all applicable electrical and plumbing codes, including, but not limited to, National Electrical
Code, local, regional, and/or state plumbing codes, etc. Not intended for use in hazardous locations.

CHECKLIST
MODEL
ITEM

DESCRIPTION

507-A

QTY

9/10
thru
Current

1

Pump, 12V DC with terminals

1

017198

2

Battery box

1

10-0764

3

DC control charger with terminals

1

011323

4

“Off”/”On” float switch

1

017197

5

Check valve

1

019768

6

Hose coupling and clamps

1

019857

7

Pump, M98/115V (507-0011)

Pump, M53/115V (507-0008)

53-0001
1

Pump, WM49/115V (507-0009)

98-0001
49-0005

8

1-1/2" PVC pipe tee

1

005645

9

1-1/2" X 2-1/8" long pipe

1

150197

10

1-1/2" X 8-3/4" long pipe

1

010619

11

Hardware pack (507)

1

017196

© Copyright 2013 Zoeller Co. All rights reserved.
6

TROUBLESHOOTING INFORMATION
1.

Charging and charged LED’s alternate frequently.
(a) This is normal.

2.

DC Pump won’t run.
(a) Check 15 amp fuse in line from pump to switch (see fig. 4). If fuse
is blown, replace with 15 amp Littelfuse type 3AG, series 311.
(b) Check for proper connections.
(c) Check all wire terminal points. Clean if required.
(d) Check for low battery. Service battery if required.

3.

Pump runs but pumps very little or no water.
(a) Check for low battery. Battery will recharge if Red power “on”
light indicates power has been restored and the float switch is
in the off position.
(b) If immediate usage is required, remove and replace dead
battery with a full recharged battery.
(c) Due to varying conditions the pump may continue to run on a
low battery without sufficient power to remove water. Pump will
not stop running until battery is completely discharged.
(d)
Weak batteries can be recharged but may
not store sufficient energy for full service. A weak recharged
battery can only be detected by reduced pumping time or by
checking each cell with a hydrometer. If your emergency pump
system is used frequently the battery should be checked by a
qualified battery dealer.

4.

Pump cycles too frequently.
(a) Check positions of rubber stops on float rod.
(b) Adjust upper rubber float stop as required. Recommended for
standard installation.

5.

Float switch in “on” position. Pump won’t run.
(a) Remove pump. Check for obstruction in pump preventing
impeller from rotating.

6.

Pump runs, but pumps water intermittently.
(a) Pump is air locking. Check flow of water incoming to sump. If
water is entering the sump at a high velocity creating a turbulent
condition, a mixture of air and water may cause a complete
or partial air lock and reduce or stop the flow of water in the
discharge pipe.
(b) Baffle the incoming stream of water to reduce turbulence.
Diverting water stream against wall of basin usually corrects an
air lock problem.

7.

Water level stays high. DC Pump continues to run.
(a) Battery is low.
(b) If power has been restored and water in sump remains high
check primary pump. Service if required.
(c) After several hours the battery will be restored to full charge.

8.

Alarm sounds during battery recharge cycle.
(a) Push alarm reset (max. 3 times). If condition persists, replace
battery.
(b) To silence alarm if alarm will not reset, unplug the charger from
115V wall outlet, then disconnect the black lead from charger on
negative (-) battery post. Check battery. Replace if necessary.
Reconnect and refer to Installation (step 7).

Service Checklist
ELECTRICAL PRECAUTIONS- Before servicing a pump, always shut off the main power breaker and then unplug the pump - making
sure you are wearing insulated protective sole shoes and not standing in water. Under flooded conditions, contact your local electric company or a
qualified licensed electrician for disconnecting electrical service prior to pump removal.
Submersible pumps contain oils which becomes pressurized and hot under operating conditions - allow 2½ hours after disconnecting before
attempting service.
CONDITION

COMMON CAUSES

A.

Pump will not start or run.

Check fuse, low voltage, overload open, open or incorrect wiring, open switch, impeller or seal bound mechanically, motor
or wiring shorted. Float assembly held down. Switch, damaged or out of adjustment.

B.

Motor overheats and trips
overload or blows fuse.

Incorrect voltage, negative head (discharge open lower than normal) impeller or seal bound mechanically, motor shorted.

C. Pump starts and stops too often.

Float switch tether length too short, check valve stuck open, or none installed in long distance line, overload open, bidding,
sump pit too small.

D. Pump will not shut off.

Debris under float assembly, float bound by basin sides or other, switch, damaged or out of adjustment.

E.

Pump operates but delivers little
or no water.

Check inlet, strainer housing, discharge pipe, and vent holes for obstructions. Discharge head exceeds pump capacity.
Low or incorrect voltage. Incoming water containing air or causing air to enter pumping chamber. Incorrect motor rotation.
(3 phase pumps only)

F.

Drop in head and/or capacity
after a period of use.

Increased pipe friction, clogged line or check valve. Abrasive material and adverse chemicals could possibly deteriorate
impeller and pump housing. Check line. Remove base and inspect.

G. If tank or fittings leak.

Carefully tighten pipe joints (use pipe dope) and screws. Check gasket location, tighten lid evenly. Do not over tighten
fittings or screws.

If the above checklist does not uncover the problem, consult the factory - Do not attempt to service or otherwise disassemble pump. Service must be
performed by Zoeller Authorized Service Stations. Go to www.zoellerpumps.com/service stations to find the Authorized Service Station in your area.

© Copyright 2013 Zoeller Co. All rights reserved.
7

FLOAT SWITCH

CONTROL CHARGER
ALARM RESET
POWER ON
"RED"

INDICATOR
"CHARGING-YELLOW"
"CHARGED-GREEN"

BLACK LEAD TO
NEG. BATTERY TERMINAL

LOCKING PIN MUST BE
INSTALLED UNDER FLOAT
ROD IN THIS LOCATION.

BLUE LEAD TO
FLOAT SWITCH

NON-GROUNDED
POWER CORD

BLACK WITH RED TRACER
TO POS. BATTERY TERMINAL

FIGURE 4

FIG. 4

sk2503

FIGURE 5

sk1424

CARBON MONOXIDE DETECTORS
Whether you have a “Basement Sentry®” Backup Pump System, or a competitive brand, all use batteries that give off gaseous by-products when charging.
Some of these by-products can produce a rotten egg odor. Also, some of these by-products can cause a CO detector to falsely activate. In order to help
prevent false activation, Zoeller Company recommends moving the battery as far apart from the CO detector as possible or, if necessary, vent the battery to the
exterior. Zoeller Company provides the previous statements only as guidelines to help prevent false activation of the CO detector. In no way are they meant
to supersede the instructions that accompany the detector nor do they supersede advice from the CO detector manufacturer.
If the audible alarm associated with your CO detector is activated, we recommend the following actions:
1)

Take immediate action for personal safety as recommended in the CO detector literature.

2)

Contact the appropriate agency to determine if the CO is being produced by your furnace, water heater, or any other device which uses natural gas.

3)

If you are certain that no CO is being produced, then a charging battery may be producing gaseous by-products which are causing the CO detector
to activate. Contact the manufacturer and ask for recommendations as to what can be done to prevent the alarm activation.

®

MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624

Your Peace of Mind is Our Top Priority ®
© Copyright 2013 Zoeller Co. All rights reserved.
8

visit our web site:
www.zoeller.com



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.0-c060 61.134777, 2010/02/12-17:32:00
Create Date                     : 2013:01:08 14:47:29-05:00
Modify Date                     : 2013:01:08 14:47:36-05:00
Metadata Date                   : 2013:01:08 14:47:36-05:00
Creator Tool                    : Adobe InDesign CS5 (7.0.4)
Page Image Page Number          : 1, 2
Page Image Format               : JPEG, JPEG
Page Image Width                : 256, 256
Page Image Height               : 256, 256
Page Image                      : (Binary data 12104 bytes, use -b option to extract), (Binary data 9399 bytes, use -b option to extract)
Version ID                      : 1
Instance ID                     : uuid:0d4d55c1-8da9-4479-ae97-462d39aaa944
Document ID                     : xmp.did:B428AC5A3845E2119CD4C8995DD54543
Original Document ID            : adobe:docid:indd:974c0857-2061-11de-9e97-88b9e4061213
Rendition Class                 : proof:pdf
Derived From Instance ID        : xmp.iid:B7E29D5A3845E2119CD4C8995DD54543
Derived From Document ID        : xmp.did:9FCF20BA1A15E1119445FC7F49631350
Derived From Original Document ID: adobe:docid:indd:974c0857-2061-11de-9e97-88b9e4061213
Derived From Version ID         : 1
Derived From Rendition Class    : default
History Action                  : saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved
History Instance ID             : xmp.iid:E4C3E7C53CBBDF11AB2786A4324566EC, xmp.iid:364DF1C53CBBDF11AB2786A4324566EC, xmp.iid:374DF1C53CBBDF11AB2786A4324566EC, xmp.iid:384DF1C53CBBDF11AB2786A4324566EC, xmp.iid:4AF18E0B43BBDF11AB2786A4324566EC, xmp.iid:4BF18E0B43BBDF11AB2786A4324566EC, xmp.iid:AF33B3AF43BBDF11AB2786A4324566EC, xmp.iid:B033B3AF43BBDF11AB2786A4324566EC, xmp.iid:92F5CD5E44BBDF11AB2786A4324566EC, xmp.iid:93F5CD5E44BBDF11AB2786A4324566EC, xmp.iid:F59F9F5646BBDF11AB2786A4324566EC, xmp.iid:F69F9F5646BBDF11AB2786A4324566EC, xmp.iid:F79F9F5646BBDF11AB2786A4324566EC, xmp.iid:F89F9F5646BBDF11AB2786A4324566EC, xmp.iid:D4D0867547BBDF11AB2786A4324566EC, xmp.iid:D5D0867547BBDF11AB2786A4324566EC, xmp.iid:9E76412C48BBDF11AB2786A4324566EC, xmp.iid:9F76412C48BBDF11AB2786A4324566EC, xmp.iid:44DC80FD4FBBDF11AB2786A4324566EC, xmp.iid:45DC80FD4FBBDF11AB2786A4324566EC, xmp.iid:F56B977350BBDF11AB2786A4324566EC, xmp.iid:F66B977350BBDF11AB2786A4324566EC, xmp.iid:6A99D67552BBDF11AB2786A4324566EC, xmp.iid:6B99D67552BBDF11AB2786A4324566EC, xmp.iid:7DA773E055BBDF11AB2786A4324566EC, xmp.iid:7EA773E055BBDF11AB2786A4324566EC, xmp.iid:BAB1564557BBDF11AB2786A4324566EC, xmp.iid:DFCC5D4557BBDF11AB2786A4324566EC, xmp.iid:75F99CCE5ABBDF11AB2786A4324566EC, xmp.iid:76F99CCE5ABBDF11AB2786A4324566EC, xmp.iid:EA65248362BBDF11AB2786A4324566EC, xmp.iid:EB65248362BBDF11AB2786A4324566EC, xmp.iid:F05743256EBBDF11AB2786A4324566EC, xmp.iid:F15743256EBBDF11AB2786A4324566EC, xmp.iid:B9B3569271BBDF11AB2786A4324566EC, xmp.iid:E6D85D9271BBDF11AB2786A4324566EC, xmp.iid:30F3A5F272BBDF11AB2786A4324566EC, xmp.iid:31F3A5F272BBDF11AB2786A4324566EC, xmp.iid:ED14EA1ED7BCDF1194CAD78E6932D450, xmp.iid:EE14EA1ED7BCDF1194CAD78E6932D450, xmp.iid:5B8F1837D8BCDF1194CAD78E6932D450, xmp.iid:5C8F1837D8BCDF1194CAD78E6932D450, xmp.iid:41ADD1B5D8BCDF1194CAD78E6932D450, xmp.iid:42ADD1B5D8BCDF1194CAD78E6932D450, xmp.iid:D811B026D9BCDF1194CAD78E6932D450, xmp.iid:D911B026D9BCDF1194CAD78E6932D450, xmp.iid:8BD2BD06EBBCDF1194CAD78E6932D450, xmp.iid:8CD2BD06EBBCDF1194CAD78E6932D450, xmp.iid:CA69D4B4ECBCDF1194CAD78E6932D450, xmp.iid:CB69D4B4ECBCDF1194CAD78E6932D450, xmp.iid:8FA2DF498AC1DF11A718FF2EAC0680D0, xmp.iid:90A2DF498AC1DF11A718FF2EAC0680D0, xmp.iid:34C516398DC1DF11A718FF2EAC0680D0, xmp.iid:35C516398DC1DF11A718FF2EAC0680D0, xmp.iid:78EA0CA18DC1DF11A718FF2EAC0680D0, xmp.iid:79EA0CA18DC1DF11A718FF2EAC0680D0, xmp.iid:7AEA0CA18DC1DF11A718FF2EAC0680D0, xmp.iid:2F6BD14390C1DF11A718FF2EAC0680D0, xmp.iid:DBA20E2791C1DF11A718FF2EAC0680D0, xmp.iid:DCA20E2791C1DF11A718FF2EAC0680D0, xmp.iid:80BB165992C1DF11A718FF2EAC0680D0, xmp.iid:81BB165992C1DF11A718FF2EAC0680D0, xmp.iid:6EA2D2AE94C1DF11A718FF2EAC0680D0, xmp.iid:6FA2D2AE94C1DF11A718FF2EAC0680D0, xmp.iid:70A2D2AE94C1DF11A718FF2EAC0680D0, xmp.iid:E45A1CD695C1DF11A718FF2EAC0680D0, xmp.iid:F26253F195C1DF11A718FF2EAC0680D0, xmp.iid:91B9ECF795C1DF11A718FF2EAC0680D0, xmp.iid:92B9ECF795C1DF11A718FF2EAC0680D0, xmp.iid:F453E40798C1DF11A718FF2EAC0680D0, xmp.iid:F553E40798C1DF11A718FF2EAC0680D0, xmp.iid:B5BB7F1399C1DF11A718FF2EAC0680D0, xmp.iid:4D7F841399C1DF11A718FF2EAC0680D0, xmp.iid:095D786F99C1DF11A718FF2EAC0680D0, xmp.iid:0A5D786F99C1DF11A718FF2EAC0680D0, xmp.iid:3001F3B39CC1DF11A718FF2EAC0680D0, xmp.iid:3101F3B39CC1DF11A718FF2EAC0680D0, xmp.iid:7F05C78A9DC1DF11A718FF2EAC0680D0, xmp.iid:8005C78A9DC1DF11A718FF2EAC0680D0, xmp.iid:8105C78A9DC1DF11A718FF2EAC0680D0, xmp.iid:54FA9A529EC1DF11A718FF2EAC0680D0, xmp.iid:922970749EC1DF11A718FF2EAC0680D0, xmp.iid:932970749EC1DF11A718FF2EAC0680D0, xmp.iid:942970749EC1DF11A718FF2EAC0680D0, xmp.iid:952970749EC1DF11A718FF2EAC0680D0, xmp.iid:962970749EC1DF11A718FF2EAC0680D0, xmp.iid:972970749EC1DF11A718FF2EAC0680D0, xmp.iid:982970749EC1DF11A718FF2EAC0680D0, xmp.iid:992970749EC1DF11A718FF2EAC0680D0, xmp.iid:E2C138C8A2C1DF11A718FF2EAC0680D0, xmp.iid:E3C138C8A2C1DF11A718FF2EAC0680D0, xmp.iid:72FE5A5CE2C4DF118692FF0D51935BEB, xmp.iid:73FE5A5CE2C4DF118692FF0D51935BEB, xmp.iid:74FE5A5CE2C4DF118692FF0D51935BEB, xmp.iid:249F26A5E2C4DF118692FF0D51935BEB, xmp.iid:5A025A50F0CBDF118733A89F3063F826, xmp.iid:5B025A50F0CBDF118733A89F3063F826, xmp.iid:222A5E25F2CBDF118733A89F3063F826, xmp.iid:232A5E25F2CBDF118733A89F3063F826, xmp.iid:EEF7196CF2CBDF118733A89F3063F826, xmp.iid:EFF7196CF2CBDF118733A89F3063F826, xmp.iid:A34E556276D0DF11878BCBB08EE9C791, xmp.iid:A44E556276D0DF11878BCBB08EE9C791, xmp.iid:41E105BA76D0DF11878BCBB08EE9C791, xmp.iid:42E105BA76D0DF11878BCBB08EE9C791, xmp.iid:31B6BD4477D0DF11878BCBB08EE9C791, xmp.iid:32B6BD4477D0DF11878BCBB08EE9C791, xmp.iid:04BD3BCD78D0DF11878BCBB08EE9C791, xmp.iid:05BD3BCD78D0DF11878BCBB08EE9C791, xmp.iid:B9FB7FF578D0DF11878BCBB08EE9C791, xmp.iid:BAFB7FF578D0DF11878BCBB08EE9C791, xmp.iid:8DAD6D3E79D0DF11878BCBB08EE9C791, xmp.iid:8EAD6D3E79D0DF11878BCBB08EE9C791, xmp.iid:9009B48141D1DF11AEEAD5A6D7194B49, xmp.iid:9109B48141D1DF11AEEAD5A6D7194B49, xmp.iid:9209B48141D1DF11AEEAD5A6D7194B49, xmp.iid:9309B48141D1DF11AEEAD5A6D7194B49, xmp.iid:38C4607442D1DF11AEEAD5A6D7194B49, xmp.iid:39C4607442D1DF11AEEAD5A6D7194B49, xmp.iid:3AC4607442D1DF11AEEAD5A6D7194B49, xmp.iid:3BC4607442D1DF11AEEAD5A6D7194B49, xmp.iid:DE9248B467D1DF11AEEAD5A6D7194B49, xmp.iid:DF9248B467D1DF11AEEAD5A6D7194B49, xmp.iid:E09248B467D1DF11AEEAD5A6D7194B49, xmp.iid:E19248B467D1DF11AEEAD5A6D7194B49, xmp.iid:B2B675FB69D1DF11AEEAD5A6D7194B49, xmp.iid:B3B675FB69D1DF11AEEAD5A6D7194B49, xmp.iid:2D68910C6AD1DF11AEEAD5A6D7194B49, xmp.iid:2E68910C6AD1DF11AEEAD5A6D7194B49, xmp.iid:3368910C6AD1DF11AEEAD5A6D7194B49, xmp.iid:4CC0FA977BD1DF11AEEAD5A6D7194B49, xmp.iid:C4086C6635D5DF119ABC9DBE8DBFD17A, xmp.iid:A442866635D5DF119ABC9DBE8DBFD17A, xmp.iid:A542866635D5DF119ABC9DBE8DBFD17A, xmp.iid:A642866635D5DF119ABC9DBE8DBFD17A, xmp.iid:053A316E3902E011ADAE81572876D131, xmp.iid:80ED188C3902E011ADAE81572876D131, xmp.iid:81ED188C3902E011ADAE81572876D131, xmp.iid:82ED188C3902E011ADAE81572876D131, xmp.iid:55F6CFE03A02E011ADAE81572876D131, xmp.iid:56F6CFE03A02E011ADAE81572876D131, xmp.iid:DD3BB4043B02E011ADAE81572876D131, xmp.iid:DE3BB4043B02E011ADAE81572876D131, xmp.iid:A6DD2D0C3D02E011ADAE81572876D131, xmp.iid:A7DD2D0C3D02E011ADAE81572876D131, xmp.iid:A8DD2D0C3D02E011ADAE81572876D131, xmp.iid:A9DD2D0C3D02E011ADAE81572876D131, xmp.iid:C30C6A95CB02E011A04597C2674A7A75, xmp.iid:C40C6A95CB02E011A04597C2674A7A75, xmp.iid:DE163DAACB02E011A04597C2674A7A75, xmp.iid:DF163DAACB02E011A04597C2674A7A75, xmp.iid:E970FDEBCB02E011A04597C2674A7A75, xmp.iid:EA70FDEBCB02E011A04597C2674A7A75, xmp.iid:8BB44709CC02E011A04597C2674A7A75, xmp.iid:8CB44709CC02E011A04597C2674A7A75, xmp.iid:8DB44709CC02E011A04597C2674A7A75, xmp.iid:8EB44709CC02E011A04597C2674A7A75, xmp.iid:66C54079CC02E011A04597C2674A7A75, xmp.iid:67C54079CC02E011A04597C2674A7A75, xmp.iid:0B48F30FCD02E011A04597C2674A7A75, xmp.iid:0C48F30FCD02E011A04597C2674A7A75, xmp.iid:D5DEB196C518E011B08280EF5664F705, xmp.iid:0154C796C518E011B08280EF5664F705, xmp.iid:396A94AFC518E011B08280EF5664F705, xmp.iid:3A6A94AFC518E011B08280EF5664F705, xmp.iid:3B6A94AFC518E011B08280EF5664F705, xmp.iid:3C6A94AFC518E011B08280EF5664F705, xmp.iid:AB37EF9C1315E1119445FC7F49631350, xmp.iid:9FCF20BA1A15E1119445FC7F49631350, xmp.iid:50FC5EE31A15E1119445FC7F49631350, xmp.iid:BE10ECFE1A15E1119445FC7F49631350, xmp.iid:BF10ECFE1A15E1119445FC7F49631350, xmp.iid:B469B1951E15E1119445FC7F49631350, xmp.iid:7FC1F38E3045E2118B63ED62763BBA95, xmp.iid:6DC98E983045E2118B63ED62763BBA95, xmp.iid:6EC98E983045E2118B63ED62763BBA95, xmp.iid:07211E663145E2118B63ED62763BBA95, xmp.iid:598EBE613245E2118B63ED62763BBA95, xmp.iid:BFBA16E73345E2118B63ED62763BBA95, xmp.iid:B7E29D5A3845E2119CD4C8995DD54543, xmp.iid:B428AC5A3845E2119CD4C8995DD54543, xmp.iid:52A3EF7A3E45E2119CD4C8995DD54543, xmp.iid:385DA16F3F45E2119CD4C8995DD54543, xmp.iid:EAF479FB3F45E2119CD4C8995DD54543, xmp.iid:880272034045E2119CD4C8995DD54543, xmp.iid:890272034045E2119CD4C8995DD54543, xmp.iid:900272034045E2119CD4C8995DD54543, xmp.iid:6F52A27C244AE211B647D3E1968AB1DD, xmp.iid:8D00CA1F254AE211B647D3E1968AB1DD, xmp.iid:99895A33CC59E211895AAF6547828390
History When                    : 2010:09:08 07:32:33-04:00, 2010:09:08 07:32:33-04:00, 2010:09:08 08:06:40-04:00, 2010:09:08 08:06:40-04:00, 2010:09:08 08:17:27-04:00, 2010:09:08 08:17:27-04:00, 2010:09:08 08:22:02-04:00, 2010:09:08 08:22:02-04:00, 2010:09:08 08:26:56-04:00, 2010:09:08 08:26:56-04:00, 2010:09:08 08:41:01-04:00, 2010:09:08 08:41:01-04:00, 2010:09:08 08:47:40-04:00, 2010:09:08 08:47:40-04:00, 2010:09:08 08:49:03-04:00, 2010:09:08 08:49:03-04:00, 2010:09:08 08:54:09-04:00, 2010:09:08 08:54:09-04:00, 2010:09:08 09:50:07-04:00, 2010:09:08 09:50:07-04:00, 2010:09:08 09:53:25-04:00, 2010:09:08 09:53:25-04:00, 2010:09:08 10:07:48-04:00, 2010:09:08 10:07:48-04:00, 2010:09:08 10:32:15-04:00, 2010:09:08 10:32:15-04:00, 2010:09:08 10:42:14-04:00, 2010:09:08 10:42:14-04:00, 2010:09:08 11:07:33-04:00, 2010:09:08 11:07:33-04:00, 2010:09:08 12:02:42-04:00, 2010:09:08 12:02:42-04:00, 2010:09:08 13:25:59-04:00, 2010:09:08 13:25:59-04:00, 2010:09:08 13:50:30-04:00, 2010:09:08 13:50:30-04:00, 2010:09:08 14:00:21-04:00, 2010:09:08 14:00:21-04:00, 2010:09:10 08:29:56-04:00, 2010:09:10 08:29:56-04:00, 2010:09:10 08:37:46-04:00, 2010:09:10 08:37:46-04:00, 2010:09:10 08:41:19-04:00, 2010:09:10 08:41:19-04:00, 2010:09:10 08:44:28-04:00, 2010:09:10 08:44:28-04:00, 2010:09:10 10:52:26-04:00, 2010:09:10 10:52:26-04:00, 2010:09:10 11:04:27-04:00, 2010:09:10 11:04:27-04:00, 2010:09:16 08:02:33-04:00, 2010:09:16 08:02:33-04:00, 2010:09:16 08:23:33-04:00, 2010:09:16 08:23:33-04:00, 2010:09:16 08:26:28-04:00, 2010:09:16 08:26:28-04:00, 2010:09:16 08:45:20-04:00, 2010:09:16 08:45:20-04:00, 2010:09:16 08:51:41-04:00, 2010:09:16 08:51:41-04:00, 2010:09:16 09:00:14-04:00, 2010:09:16 09:00:14-04:00, 2010:09:16 09:16:57-04:00, 2010:09:16 09:16:57-04:00, 2010:09:16 09:25:13-04:00, 2010:09:16 09:25:13-04:00, 2010:09:16 09:25:58-04:00, 2010:09:16 09:26:09-04:00, 2010:09:16 09:26:09-04:00, 2010:09:16 09:40:55-04:00, 2010:09:16 09:40:55-04:00, 2010:09:16 09:48:24-04:00, 2010:09:16 09:48:24-04:00, 2010:09:16 09:50:58-04:00, 2010:09:16 09:50:58-04:00, 2010:09:16 10:14:22-04:00, 2010:09:16 10:14:22-04:00, 2010:09:16 10:20:22-04:00, 2010:09:16 10:20:22-04:00, 2010:09:16 10:25:57-04:00, 2010:09:16 10:25:57-04:00, 2010:09:16 10:26:54-04:00, 2010:09:16 10:26:54-04:00, 2010:09:16 10:39:14-04:00, 2010:09:16 10:39:14-04:00, 2010:09:16 10:40:54-04:00, 2010:09:16 10:40:54-04:00, 2010:09:16 10:51:17-04:00, 2010:09:16 10:51:17-04:00, 2010:09:16 10:57:53-04:00, 2010:09:16 10:57:53-04:00, 2010:09:20 14:10:33-04:00, 2010:09:20 14:10:33-04:00, 2010:09:20 14:12:35-04:00, 2010:09:20 14:12:35-04:00, 2010:09:29 13:38:04-04:00, 2010:09:29 13:38:04-04:00, 2010:09:29 13:51:11-04:00, 2010:09:29 13:51:11-04:00, 2010:09:29 13:57:33-04:00, 2010:09:29 13:57:33-04:00, 2010:10:05 07:47:51-04:00, 2010:10:05 07:47:51-04:00, 2010:10:05 07:50:19-04:00, 2010:10:05 07:50:19-04:00, 2010:10:05 07:54:11-04:00, 2010:10:05 07:54:11-04:00, 2010:10:05 08:05:10-04:00, 2010:10:05 08:05:10-04:00, 2010:10:05 08:06:17-04:00, 2010:10:05 08:06:17-04:00, 2010:10:05 08:08:20-04:00, 2010:10:05 08:08:20-04:00, 2010:10:06 08:01:52-04:00, 2010:10:06 08:01:52-04:00, 2010:10:06 08:02:56-04:00, 2010:10:06 08:02:56-04:00, 2010:10:06 08:08:39-04:00, 2010:10:06 08:08:39-04:00, 2010:10:06 08:11:43-04:00, 2010:10:06 08:11:43-04:00, 2010:10:06 12:35:18-04:00, 2010:10:06 12:35:18-04:00, 2010:10:06 12:44:09-04:00, 2010:10:06 12:44:09-04:00, 2010:10:06 12:51:36-04:00, 2010:10:06 12:51:36-04:00, 2010:10:06 13:14:12-04:00, 2010:10:06 13:14:12-04:00, 2010:10:06 14:57:40-04:00, 2010:10:06 14:57:40-04:00, 2010:10:11 08:45:17-04:00, 2010:10:11 08:45:17-04:00, 2010:10:11 08:45:57-04:00, 2010:10:11 08:45:57-04:00, 2010:12:07 14:38:20-05:00, 2010:12:07 14:38:20-05:00, 2010:12:07 14:39:44-05:00, 2010:12:07 14:39:44-05:00, 2010:12:07 14:47:52-05:00, 2010:12:07 14:47:52-05:00, 2010:12:07 14:48:52-05:00, 2010:12:07 14:48:52-05:00, 2010:12:07 15:03:24-05:00, 2010:12:07 15:03:24-05:00, 2010:12:07 15:13:02-05:00, 2010:12:07 15:13:02-05:00, 2010:12:08 08:03:42-05:00, 2010:12:08 08:03:42-05:00, 2010:12:08 08:04:17-05:00, 2010:12:08 08:04:17-05:00, 2010:12:08 08:06:08-05:00, 2010:12:08 08:06:08-05:00, 2010:12:08 08:06:57-05:00, 2010:12:08 08:06:57-05:00, 2010:12:08 08:09:15-05:00, 2010:12:08 08:09:15-05:00, 2010:12:08 08:10:05-05:00, 2010:12:08 08:10:05-05:00, 2010:12:08 08:14:18-05:00, 2010:12:08 08:14:18-05:00, 2011:01:05 07:16:13-05:00, 2011:01:05 07:16:13-05:00, 2011:01:05 07:16:55-05:00, 2011:01:05 07:16:55-05:00, 2011:01:05 08:06:52-05:00, 2011:01:05 08:06:52-05:00, 2011:11:22 10:00:33-05:00, 2011:11:22 10:00:33-05:00, 2011:11:22 10:01:42-05:00, 2011:11:22 10:02:28-05:00, 2011:11:22 10:07:32-05:00, 2011:11:22 10:28:10-05:00, 2012:12:13 09:22:43-05:00, 2012:12:13 09:22:59-05:00, 2012:12:13 09:28:25-05:00, 2012:12:13 09:28:44-05:00, 2012:12:13 09:35:46-05:00, 2012:12:13 09:46:39-05:00, 2012:12:13 10:18:31-05:00, 2012:12:13 10:18:31-05:00, 2012:12:13 11:02:22-05:00, 2012:12:13 11:09:13-05:00, 2012:12:13 11:13:07-05:00, 2012:12:13 11:13:21-05:00, 2012:12:13 11:17:48-05:00, 2012:12:13 12:53:17-05:00, 2012:12:19 16:38:54-05:00, 2012:12:19 16:43:28-05:00, 2013:01:08 14:47:14-05:00
History Software Agent          : Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0
History Changed                 : /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /metadata, /;/metadata, /;/metadata, /metadata, /metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /metadata, /metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata
Doc Change Count                : 1908
Format                          : application/pdf
Producer                        : Adobe PDF Library 9.9
Trapped                         : False
Page Count                      : 8
Creator                         : Adobe InDesign CS5 (7.0.4)
EXIF Metadata provided by EXIF.tools

Navigation menu