THERM-X-TROL®
THERMAL EXPANSION ABSORBERS
The Best Solution for
Controlling Thermal Expansion
As Seen On
2
THERM-X-TROL® Expansion Tanks ......... 2
What is Thermal Expansion? .................... 2
THERM-X-TROL®: The Market Leader ..... 3
Pressure Increase in Closed Piping System 4
Precise Sizing Procedure ......................... 5
ASME Thermal-X-Trol® ............................. 6
Non-ASME Thermal-X-Trol® ..................... 7
Quick Sizing .............................................. 8
Table of Contents
THERM-X-TROL® Expansion Tanks
What Is Thermal Expansion?
With modern plumbing codes mandating backflow prevention,
thermal expansion can cause pressure buildup in domestic water
systems. When demand is put upon a potable water system,
hot water is drawn from the water heater. Cold water from the
supply line enters the water heater
to replenish it. The cold water is
heated to replace the hot water
used. With the installation of a
backflow preventer, check valve
or pressure reducing valve on the
supply line, the water heater and
the system piping form a closed
plumbing system under pressure.
As the water is heated, thermal
expansion occurs. Pressure increases until the relief valve opens
and the expanded water spills from the water heater. This spillage
results in wasted energy and a potential safety hazard. (See
Diagram 1)
Closed Potable Hot Water System
without THERM-X-TROL®
Backflow preventer, pressure reducing valve or other one-way device
causes expanded (heated) water to build pressure causing the relief valve to
open resulting in…
Wasted energy
Shortened water heater life
Wasted municipal water and sewer dollars
Potential safety hazard
The THERM-X-TROL® is designed to eliminate this problem by providing
control of maximum pressures at a level below the relief valve setting. It also
provides an additional space in the system to accommodate the increased
volume of water created by thermal expansion, returning it to the system
when hot water delivery is demanded. Maximum pressure is kept well
below the relief valve setting by the THERM-X-TROL®, with its pre-charged
air cushion that is separated from system water. The relief valve does not
open, therefore spillage is eliminated (Diagram 2).
Closed Potable Hot Water System
with THERM-X-TROL®
Expanded (heated) water is absorbed by THERM-X-TROL® which means…
Water heater and fixtures are protected
Eliminates energy and water waste, saving money
No dangerous pressure build up in the system
Relief valves will not open
Potential safety hazard reduced
Unsafe pressure increases
without THERM-X-TROL®
Fixture
Closed
SPILL
Cold Water Supply
Backflow Preventor
Diagram 1
Backflow
Preventor
THERM-X-TROL®
Cold Water Supply
3
THERM-X-TROL®: The Market Leader
#1 choice of Professional Installers
Safest and most cost effective way to control
Thermal Expansion
Easy to install
The innovator of Thermal Expansion Control in
Closed Potable Hot Water Systems
Broadest line of sizes and models
Recognized Industry leader in Quality, Design,
Manufacturing, Delivery and Service
Extensive Network of Plumbing & Heating
Distributors
First to obtain NSF/ANSI 61, IAPMO, SBCCI & City
of Los Angeles listings
First to offer 5 year limited warranty
Deep Drawn Steel Domes for
maximum strength & pressure rating
Rigid Polypropylene Liner for
corrosion resistant reservoir
Butyl diaphragm for long life
expectancy
Diaphragm Hoop Ring mechanically
grooved for permanent air-tight seal
Welded Steel Construction
Welded Air Charge Fitting with
protective plastic cap for corrosion
resistance and maximum air-tight seal
Product Features
High-grade connector
Pressure Increase in Closed Piping System
4
P
R
E
S
S
U
R
E
P
S
I
G
0
100
200
300
400
500
600
65 70 75 80 85 90 95 100
TEMPERATURE - °F
WATER
Precise Sizing Procedure - For Special Applications
The procedure for sizing the Therm-X-Trol® for
any application depends on four (4) vital pieces of
information:
1. ASME or non-ASME requirement
2 Calculated thermally expanded water volume
3. Minimum water pressure experienced at the tank
location
4. Maximum water pressure allowable at the tank
location
The tank required for any application can be sized with
the following equation:
Tv = Design Pressure Factor X expanded water
Where Tv is the total Thermal-X-Trol® volume required
in gallons.
Example: A 240 gallon water heater with a 150°F aquastat
setting is installed with a 125 psi maximum pressure
requirement. For a static supply line pressure of 60
psi, what Therm-X-Trol® model is required for critical
protection?
Critical Sizing AMTROL® Therm-X-Trol®
1. Total Water Heater Volume (Gallons)
2. Water Expansion Factor (Table I)
3. Calculate Expanded Water (Gallons)
(Line 1 x Line 2)
4. Design Pressure Factor (Table II)
5. Therm-X-Trol Volume Required (Gallons)
(Line 3 x Line 4)
6. Select Therm-X-Trol® Model (pg. 6 & 7)
Critical Sizing AMTROL® Therm-X-Trol®: EXAMPLE
1. Total Water Heater Volume (Gallons) 240
2. Water Expansion Factor (Table I) 0.0179
3. Calculate Expanded Water (Gallons) 4.3
(Line 1 x Line 2) = (240 x .0179)
4. Design Pressure Factor (Table II) 2.1
5. Therm-X-Trol Volume Required (Gallons) 9.0
(Line 3 x Line 4) = (4.3 x 2.1)
6. Select Therm-X-Trol® Model (pg. 6 & 7) ST-25V
ST30V-C
Note: The Therm-X-Trol® air pressure should be equal to static line pressure.
TABLE I Expansion Factor
Operating (Design) Expansion Factor*
Temperature of (Percentage of Water
Water Heater (Tank) Volume Increase)
100˚F 0.0062 0.6%
120˚F 0.0100 1.0%
130˚F 0.0124 1.2%
140˚F 0.0150 1.5%
150˚F 0.0179 1.8%
160˚F 0.0209 2.0%
170˚F 0.0242 2.4%
180˚F 0.0276 2.8%
* Based on the initial temperature of 40˚F
TABLE II Design Pressure Factor: DPF
Maximum Line Design
Allowable Pressure Pressure
Pressure psi Factor (DPF)
40 1.9
50 2.3
100 60 2.9
70 3.8
80 5.7
40 1.6
50 1.9
125 60 2.1
70 2.5
80 3.1
40 1.5
50 1.6
150 60 1.8
70 2.1
80 2.4
For conditions not shown in table, use equation:
DPF= Max. Allow. Pressure + 14.7
Max. Allow. Pressure - Line Pressure
5
6
ASME THERM-X-TROL®
THERM-X-TROL® ASME Specifications
Model Max. Working Total Volume Maximum Diameter Height System Ship Weight
No. Pressure (PSIG) (Gals.) Acceptance Factor (A) (B) Connection (lbs)
ST-5-C 150 2.1 .42 10” 10 3/8 3/4” NPT 21
ST-12-C 150 6.4 .50 12” 15 5/8 3/4NPT 26
ST-20V-C 150 8.0 .40 12” 19 1/2 3/4” NPT 41
ST-30V-C 150 14.0 .64 16 1/4 19 1/8 3/4” NPT 84
ST-42V-C 150 17.5 .64 16 1/4 24 1/4 3/4” NPT 90
ST-60V-C 150 25.0 .45 16 1/4 34” 3/4” NPT 96
ST-70V-C 150 34.0 .33 16 1/4 45 3/4 3/4” NPT 123
ST-80V-C 150 53.0 .64 24” 40 1/2 1 1/4” NPT 229
ST-120V-C 150 66.0 .51 24” 47 3/4 1 1/4NPT 258
ST-180V-C 150 77.0 .44 24” 52 5/8 1 1/4NPT 288
ST-210V-C 150 90.0 .38 24” 60” 1 1/4” NPT 318
ST-447-C 125 53.0 .65 24” 45 1/4 2” NPT 263
ST-448-C 125 80.0 .65 24” 59 1/8 2” NPT 308
ST-449-C 125 106.0 .65 24” 73 1/8 2” NPT 353
ST-450-C 125 132.0 .65 24” 86 5/8 2” NPT 391
ST-451-C 125 158.0 .65 30” 73 1/4 2” NPT 508
ST-452-C 125 211.0 .65 30” 91” 2” NPT 760
ST-453-C 125 264.0 .65 36” 85 5/8 3” NPT 810
ST-454-C 125 317.0 .65 36” 98” 3” NPT 914
ST-455-C 125 370.0 .65 36” 110 3/8 3” NPT 1,018
ST-456-C 125 422.0 .65 48” 81 7/8 3” NPT 1,655
ST-457-C 125 528.0 .65 48” 97 1/4 3” NPT 1,925
Maximum Allowable Working Temperature: ST-5-C through ST-210V-C: 200°F; ST-447-C through ST-457-C: 240°F Standard Factory Precharge: 55 PSIG.
Code Applications
Commercial Water Heaters
Laundromats
Hospitals and Nursing Homes
Car Washes
Dishwashers
Plant Washrooms
Hotels and Motels
Restaurants
Schools and Dormitories
Other Applications as Required by Code
A
B
A
B
ST-5-C, ST-12-C
A
B
ST-20V-C to ST-70V-C
ST-80V-C to ST-210V-C ST-447-C to ST-457-C
7
Non-ASME THERM-X-TROL®
A
B
A
B
ST-5, ST-8, ST-12
ST-25V through ST-210V
General Usage
Residential Water Heaters
Office Buildings
Apartment Buildings
Dormitories
Elderly Housing
Extended Care Facilities
Condominiums/Multiple Residential
Food Service
Laundromats
Hospitals
Other General-Use Hot Water Systems
THERM-X-TROL® Non-ASME Specifications
Model Total Volume Maximum Diameter Height System Ship Weight
No. (Gals.) Acceptance Factor (A) (B) Connection (lbs)
ST-5 2.0 .45 8” 12 5/8 3/4NPT 5
ST-8 3.2 .45 9” 15” 3/4NPT 7
ST-12 4.4 .55 11” 15” 3/4NPT 9
ST-25V 10.3 1.0 15 3/8 19 1/4 3/4NPT 23
ST-30V 14.0 .81 15 3/8 23 7/8 3/4” NPT 25
ST-42V 20.0 .57 15 3/8 31 5/8 3/4” NPT 33
ST-60V 34.0 .35 22” 29 5/8 1 1/4NPT 61
ST-80V 44.0 .77 22” 36” 1 1/4” NPT 69
ST-180V 62.0 .55 22” 46 3/4 1 1/4NPT 92
ST-200V 81.0 .41 22” 56 3/8 1 1/4NPT 103
ST-210V 86.0 .54 26” 47 1/4 1 1/4NPT 123
ST-451 158.0 .65 73 1/4 30” 2” NPT 508
ST-452 211.0 .65 91” 30” 2” NPT 760
ST-453 264.0 .65 85 5/8 36” 3” NPT 810
ST-454 317.0 .65 98” 36” 3” NPT 914
ST-455 370.0 .65 110 3/8 36” 3” NPT 1,018
ST-456 422.0 .65 81 7/8 48” 3” NPT 1,655
ST-457 528.0 .65 97 1/4 48” 3” NPT 1,925
Maximum Working Pressure: 150 PSI. All Models listed by NSF 61 (excluding ST-451 – ST-457); Maximum Allowable Working Temperature: ST-5 through
ST-210V: 200°F; ST-451 through ST-457: 240°F; Standard Factory Precharge: 40 PSIG (ST-5 – ST-210V); 55 PSIG (ST-451 – ST-457)
THERM-X-TROL®
THERM-X-TROL®
The THERM-X-TROL® from AMTROL is designed to protect domestic
water heaters from the effects of thermal expansion. Installation is
easy; just tee it into the cold water inlet (before the water heater) as
shown in Diagram 3.
THERM-X-TROL®
Quick-Sizing Chart
Sizing Charts are based on 40°F incoming
water temperature and a 150 psi T & P
safety relief valve.
If your Plumbing Code requires a Backflow
Preventer,Check Valve or Pressure Reducing Valve...
You Need a THERM-X-TROL® on Every Job!
MC# 4090 (06/09) ©2009 AMTROL Inc.
Printed in USA
The AMTROL® logo, AMTROL and Therm-X-Trol are registered trademarks of AMTROL Inc. and its affiliates in the US and elsewhere. AMTROL Inc. and it’s subsidiaries reserve the right to alter designs and specifications without prior notice.
Corporate Headquarters
1400 Division Road, West Warwick, RI USA 02893
Telephone: 401-884-6300 Fax: 401-884-5276
AMTROL Canada, Ltd.
275 Shoemaker Street, Kitchener, Ontario N2E 3B3
Telephone: 519-478-1138 Fax: 519-748-4231
www.amtrol.com
Hot Water
BFP, Check or PRV
Expanded
Water
CWS
Outer
Steel Shell
Rigid
Polypropylene
Liner
Heavy Duty
Butyl Diaphragm
Diagram 3
Water
Heater
T & P
Va lve
Always adjust THERM-X-TROL®
pre-charge to equal city water
supply pressure.
* For multiple heater, use the total volume of the heaters
plus any storage tanks.
** Therm-X-Trol Precharge must be set to equal Static
Supply Pressure prior to installation.