548036 2 Zoeller Simplex Control Panel Installation

548037 2 Zoeller Simplex Control Panel Installation 548037_2_Zoeller Simplex Control Panel Installation

548035 2 Zoeller Simplex Control Panel Installation 548035_2_Zoeller Simplex Control Panel Installation

548033 2 Zoeller Simplex Control Panel Installation 548033_2_Zoeller Simplex Control Panel Installation

548038 2 Zoeller Simplex Control Panel Installation 548038_2_Zoeller Simplex Control Panel Installation

548044 2 Zoeller Simplex Control Panel Installation 548044_2_Zoeller Simplex Control Panel Installation

: Pump 548036 2 Zoeller Simplex Control Panel Installation 548036_2_Zoeller Simplex Control Panel Installation pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

© Copyright 2016 Zoeller® Co. All rights reserved.
Model 10-1037
C
R
L
U
US LISTED
An Electrical Control Panel is used on a Simplex pump application where automatic electrical cycling of the pump is desired for added protection in
residential or commercial applications. A Control Panel is required for all systems using a nonautomatic pump. The built-in alarm system, a standard
feature, will activate when the water level becomes unusually high. All electrical systems must be installed by a qualied electrician and according
to the National Electrical Code. (See Section 430-71 though 430-113, plus any others that apply.)
SECTION: 2.50.030
FM1596
1216
Supersedes
0714
ELECTRICAL CONTROL PANELS - FOR SIMPLEX INSTALLATIONS
Simplex
Control Panel
SINGLE PHASE CONTROL PANEL FEATURES
115-208-230 Volts
Dead front panel
Clear inner door (10-0125 only)
Includes (3) 20 ft. control oat switches
Equipment disconnect (10-0125 only)
Motor contactor (all models except 10-1019 and 10-1023)
NEMA 4X watertight enclosure with lockable latch
Top-mounted alarm light
Alarm horn provides audio warning of alarm condition
(83 to 85 decibel rating)
Pump run indicator light
Horn silence and alarm test toggle switches
HOA switch
Complete installation instructions included
Lockable latch
2 year warranty
Dry auxiliary contact (not available in Plug-In Panels)
SINGLE PHASE SIMPLEX PLUG-IN CONTROL PANEL
115 V model 10-1019 or 230 V model 10-1023
NEMA 4X enclosure with hinged cover
Receptacle for use with piggyback pump switch
Alarm horn (83 to 85 decibel rating)
Terminal strip
Horn silence switch to turn alarm on or off
Alarm oat only
SINGLE PHASE SIMPLEX PUMP CONTROL/ALARM SYSTEM
Model # Volts Amp Range Float Switches Included Features
* 10-0125 Branch Circuit Protection provided by the installing electrician.
10-1019 115 V 0-15 Alarm Float Only Plug-In
10-1023 230 V 0-15 Alarm Float Only Plug-In
10-1036 115V, 208-230 V 0-7 Three-20’ Control Floats Circuit Breaker Disconnect
10-1037 115V, 208-230 V 7-15 Three-20’ Control Floats Circuit Breaker Disconnect
10-1038 115V, 208-230 V 15-20 Three-20’ Control Floats Circuit Breaker Disconnect
10-0125* 115V, 208-230 V 0-20 Three-20’ Control Floats Equipment Disconnect
Simplex
Plug-In
Panel
Model 10-1019
NOTE: 600 and X600 Series
single phase pumps require
special panels that include
start components. See Se-
lection Guide FM1228 and
FM1705 for correct panel
selection.
NOTE: All variable level oat
switches in this section are
mechanically activated and
do not contain mercury.
C
R
L
U
US LISTED
Product information presented
here reects conditions at time
of publication. Consult factory
regarding discrepancies or
inconsistencies.
MAIL TO: P.O. BOX 16347 • Louisville, KY 40256-0347
SHIP TO: 3649 Cane Run Road • Louisville, KY 40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
visit our web site:
www.zoeller.com
®
Your Peace of Mind is Our Top Priority
®
© Copyright 2016 Zoeller® Co. All rights reserved.
THREE PHASE SIMPLEX CONTROL PANEL FEATURES
208-230-460-575 Volts
NEMA 4X - watertight enclosure with lockable latch
Hand-off toggle switch
Green pump run light
Alarm test & silence switches
Red alarm beacon and audible alarm for a high water condition
(83 to 85 decibel rating)
Motor protection switch with overload protection
Magnetic starter
Numbered terminal strip for connecting pumps and variable level oat switches
Dry auxiliary contacts for remote alarm devices
Three oat operation (oats not included - See FM0526)
The use of off-the-shelf components provide for relatively easy eld
maintenance and repair
2-year warranty
Three Phase -
Dead Front Cover
PUMP POWER SUPPLY
CONTROL & ALARM
POWER SUPPLY
NOTE: ALARM - CONTROL
CIRCUIT SHOULD BE
SEPARATE FROM
PUMP POWER
2" OR 3" DISCHARGE PIPE
FLOOR FLANGE
ZOELLER FIBERGLASS
OR POLYETHYLENE BASIN
ZOELLER FLOAT SWITCH
ZOELLER SEWAGE PUMP
SIMPLEX CONTROL PANEL
ZOELLER UNICHCEK
CHECK VALVE (2" OR 3")
4" HUB INLET
"ALARM" LEVEL SET
ABOVE "ON" FLOAT AND
BELOW INLET.
"ON" LEVEL PUMP OPERATION
IS EACH CYCLE MAXIMIZED
BASED ON DEPTH AND VOLUME
MINIMUM "OFF" LEVEL
DISCONNECT
OF BASIN
(SINGLE PHASE ONLY)
(SINGLE PHASE ONLY)
5"
ALARM LIGHT
SK1734
SEQUENCE OF OPERATION FOR SIMPLEX PANEL
1. Operation can begin after the following:
- Correct voltage is supplied to panel
- A good ground is supplied to panel
- Pump is connected correctly to panel
- Panel circuit breaker is closed
- Floats are installed properly
- Overload protection is adjusted to pump nameplate amps
- Pump HOA Switch is set to “Auto”
2. When the “Stop” and “Start” oats are closed the Pump will energize
and the External Pump Run Light will illuminate. The Pump will remain
operational until the “Stop” oat opens.
3. In the event the liquid level continues to rise the “Alarm” oat will be
closed. When the “Alarm” oat is closed the following will occur: - The
External High Water Light will illuminate
- The Audible High Water Horn will sound
- The Auxiliary Dry Contacts will close
4. The Audible High Water Horn can be silenced by pressing the
Alarm Silence Button. When the “Alarm” oat is opened the
External High Water Light, Audible High Water Horn and Dry
Auxiliary Contacts will be reset.
*A three phase panel has a multi-tap transformer with secondary
fusing.
CAUTION
All electrical systems must be installed by a quali-
ed licensed electrician according to the National Electrical Code.
(See section 430-71 through 430-113 plus any others that apply)
Refer to FM1228 and FM1705 for correct selection of Simplex
Panels.
THREE PHASE SIMPLEX PUMP CONTROL PANELS
MODEL # DIMENSIONS VOLTS AMP RANGE
10-1074 12 X 10 X 6 208/230/460 1.0 - 1.6
10-1076 12 X 10 X 6 208/230/460 1.6 - 2.5
10-1078 12 X 10 X 6 208/230/460 2.5 - 4.0
10-1080 12 X 10 X 6 208/230/460 4.0 - 6.3
10-1082 12 X 10 X 6 208/230/460 6.0 - 10.0
10-1083 12 X 10 X 6 208/230/460 9.0 - 14.0
10-1084 12 X 10 X 6 208/230/460 13.0 - 18.0
10-1086 12 X 10 X 6 208/230/460 17.0 - 23.0
10-1132 12 X 10 X 6 575 1.6 - 2.5
10-1134 12 X 10 X 6 575 2.5 - 4.0
10-1136 12 X 10 X 6 575 4.0 - 6.3
C
R
L
U
US LISTED