Single phase, duplex alternating pump control with override.
The Model 122 control panel is designed to alternately control two 120, 208, or 240 VAC single phase pumps in water and sewage
installations. The alternating action equalizes pump wear. In addition to the alternating pump control, this system provides override
control should either pump fail. If an alarm condition occurs, an alarm switch activates the audio/visual alarm system. Common
applications include pump chambers, sump pump basins, irrigation systems and lift stations.
MODEL 122 Control Panel
1. Enclosure measures 10 X 10 X 6 inches (25.4 X 25.4 X 15.24 cm).
Choice of NEMA 1 (steel for indoor use), or NEMA 4X (ultraviolet stabilized
thermoplastic with removable mounting feet for outdoor or indoor use).
Note: Options selected may increase enclosure size and change component
layout.
2. Magnetic Motor Contactors control pumps by switching electrical lines.
3. HOA Switches for manual pump control (mounted on circuit board).
4. Control Circuit Board provides pump control and alternation.
5. Green pump Run Indicator Lights (mounted on circuit board).
6. Circuit Breakers (optional) provide pump disconnect and branch circuit
protection.
7. Ground Lugs
8. Float Status Indicator Lights (mounted on circuit board).
9. Control and Alarm Power Indicator Lights (mounted on circuit board)
10. Auxiliary Alarm Contact, form C (mounted on circuit board).
NOTE: Schematic is located inside the panel on enclosure cover.
STANDARD ALARM PACKAGE
11. Red Alarm Beacon provides 360° visual check of alarm condition.
Note: NEMA 1 style utilizes a door mounted indicator in lieu of a beacon.
12. Alarm Horn provides audio warning of alarm condition (83 to 85 decibel
rating).
Note: NEMA 1 style utilizes an internally mounted buzzer in lieu of horn.
13. Exterior Alarm Test/Normal/Silence Switch allows horn and light to be tested
and horn to be silenced in an alarm condition. Alarm automatically resets once
alarm condition is cleared.
14. Horn Silence Relay (mounted on circuit board).
NOTE: other options available.
FEATURES
n
Entire control system (panel and switches) is UL Listed to meet and/or
exceed industry safety standards
n
Dual safety certication for the United States and Canada
n
Standard package includes three 20' SJE SignalMaster® control
switches
n
Complete with step-by-step installation instructions
n
Five-year limited warranty
PANEL COMPONENTS
PO Box 1708, Detroit Lakes, MN 56502
1-888-DIAL-SJE • 1-218-847-1317
1-218-847-4617 Fax
email: customer.service@sjerhombus.com
www.sjerhombus.com
SEE BACKSIDE FOR COMPLETE LISTING OF AVAILABLE OPTIONS.
SEE PRICE BOOK FOR LIST PRICE. B.41
Model Shown 1221W114X6A
4panel cover
11
1
3
8
12
14
5
10
9
2
7
13
6
7
9500066B © SJE-Rhombus 12/16
1A Red beacon only / no audio
(must select "0" for alarm package)
1C Horn only / no visual
(must select "0" for alarm package)
HH 3A Alarm asher
H3B Manual alarm reset
H4A Redundant off
(select Option 4D if oats included)
4B Red redundant off indicator & alarm
(must select Option 4A also)
4D Redundant off oat
(must select 4A option) (select 17 option)
H5A Thermal cutout/heat sensor auto reset
(for pumps w/thermal switch leads)
H5E Seal failure circuit & red indicator (2 wire)
6A Auxiliary alarm contact, form C
(included as standard)
H 8A Elapsed time meter
H
8C
Event (cycle) counter
H 9_A Pump overload
specify amperage after number 9 followed by letter "A". ..
Example: 912A = 12 amp pump.
H 0-25 FLA
H 25-30 FLA
10E Lockable latch - NEMA 4X
10E Lockable latch - NEMA 1
H 10F Lightning arrestor (select pump circuit breaker)
HH10K Anti-condensation heater
11C NEMA 1 alarm panel
11D NEMA 4X alarm panel
H 14B
Main disconnect (rotary style, mounted through door, non-fused,
padlockable in the OFF-position, door interlock in the ON-position)
(must select circuit breaker)
H 0-20 FLA (total of both pumps)
H 20-60 FLA (total of both pumps)
16A 10' cord in lieu of 20' (per oat)
16B 15' cord in lieu of 20' (per oat)
16C 30' cord in lieu of 20' (per oat)
16D 40' cord in lieu of 20' (per oat)
17A SJE SignalMaster® / pipe clamp l (per oat)
17B SJE SignalMaster® / externally weighted l (per oat)
17C Sensor Float® / internally weighted s (per oat)
17D Sensor Float® / externally weighted s (per oat)
17E Sensor Float® Mini / pipe clamp s (per oat)
17F Sensor Float® Mini / externally weighted s (per oat)
17J Sensor Float® / pipe clamp s (per oat)
19B Lead lag selector switch
19F Fourth oat to separate alarm function from lag
19T TOA (Test/Off/Automatic) switches and pump run lights
through door mounted
19U HOA (Hand/Off/Automatic) switches and pump run lights
through door mounted
19X Door mounted pump run indicator
l Mechanically-activated s Mercury-activated
122 1 W 9 0 4 H 6A 8AC 17A
CODE DESCRIPTION
CODE DESCRIPTION
SAMPLE
122
ENCLOSURE UPSIZE
If you selected one or more of the H options, or two HH options
H
B.42
6A
MODEL
Alarm Package
Enclosure Rating
Starting Device
Pump Full Load Amps
Pump Disconnect
Float Switch Application
Options: Auxiliary alarm contact, form C,
Elapsed time meter, event (cycle) counter,
SJE SignalMaster® / pipe clamp
MODEL 122
ALARM PACKAGE
0 = select options or no alarm package
1 = alarm package (includes test/normal/silence switch, fuse, red light, & horn)
ENCLOSURE RATING
I = Indoor, NEMA 1 (metal)
W = Weatherproof, NEMA 4X (engineered thermoplastic)
STARTING DEVICE
1 = magnetic motor contactor 120/208/240V
9 = magnetic motor contactor 120V only
PUMP FULL LOAD AMPS
0 = 0-7 FLA
1 = 7-15 FLA
2 = 15-20 FLA
3 = 20-30 FLA
PUMP DISCONNECTS
0 = no pump disconnect
4 = circuit breaker 120V (select STARTING DEVICE option 9 above)
120/208/240V (select STARTING DEVICE option 1 above)
FLOAT SWITCH APPLICATION
H or L = pump down or pump up (select 17 option)
X = no oats
OPTIONS Listed below
If additional features are required, call the factory for a quote on an Engineered Custom control panel.