551692 1 Grundfos SQ Series Brochure
: Pump 551692 1 Grundfos Sq Series Brochure 551692_1_Grundfos SQ Series Brochure pdf
Open the PDF directly: View PDF .
Page Count: 64
Download | |
Open PDF In Browser | View PDF |
GRUNDFOS DATA BOOKLET SQ, SQE, SQE-NE, CU331SP SQ, SQE, SQE-NE, CU331SP Table of contents 1. 2. Product introduction 3 Features and benefits Identification 3 5 Applications 6 SQ with pressure switch and pressure tank Constant-pressure control with CU 301 - residential water supply Constant-pressure control with CU 301 - irrigation Maintaining a constant water table Emptying or filling a tank Pumping from one tank to another Setting of operating parameters SQE with manual speed control 6 8 9 10 11 12 13 3. Performance range 14 4. Installation 15 Sizing and selection 16 System sizing guide 16 5. 6. 7. 8. 9. Cable sizing 17 Cable sizing chart 17 SQ curve charts 18 5 SQ, SQE 10 SQ, SQE 15 SQ, SQE 22 SQ, SQE 30 SQ, SQE 10 SQE-NE 22 SQE-NE 18 19 20 21 22 23 24 Technical data 25 Electrical data Operating conditions Motor data Dimensions and weights 25 25 26 27 Construction 28 Materials of construction Material specification 28 29 10. Control units CU 301 CU 300 2 7 30 30 33 11. CU331SP variable frequency drive Features Applications System components Identification CU331SP product range CU331SP performance range CU331SP sizing CU331SP operation CU331SP installation CU331SP electrical connection CU331SP technical data CU331SP curve charts 12. Accessories CU331SP Constant Pressure Drive Kits (with sensor) CU 301 Constant Pressure System CU 300 Status Box & R100 SQ, SQE flow sleeves 13. Further product documentation WebCAPS WinCAPS 37 37 37 37 38 39 39 39 40 44 45 51 53 59 59 59 59 59 60 60 61 SQ, SQE, SQE-NE, CU331SP 1 3-inch SQ, SQE submersible well pumps for 3-inch and larger wells SQ, SQE pumps are suitable for both continuous and intermittent operation for a variety of applications: • Domestic water supply • light commercial • irrigation • tank applications. Features and benefits SQ, SQE pumps offer these features: • • • • • • • Dry-run protection high efficiency pump and motor protection against up-thrust soft-start over-voltage and under-voltage protection over-temperature protection high starting torque. Product introduction 1. Product introduction The "Smart Motor" communicates via the CU301 status box through the power leads. It is not necessary to run any additional wires down the well. Communication with the pump provides Constant Pressure Control and the highly useful ability to change the pump performance while the pump is installed in the well. Like the SQ motor, this is also a 2wire motor designed for single-phase operation. Dry-running protection The pumps are protected against dry running. A value of Pcut-out ensures cut-out of the pump in case of lack of water in the borehole thus preventing a burnout of the motor. Pcut-out is factory-set both for the SQ and SQE, SQENE pumps. H Q • Constant pressure control • variable speed • electronic control and communication. P P1 P cut-out cut-out Q SQ, SQE pumps feature an innovative motor design incorporating permanent-magnet technology. By combining permanent-magnet motors and a Grundfos micro-frequency converter, we are able to deliver unmatched performance and the ability to control and communicate with the pump in ways never before possible. A few of the features that result from this combined technology are Constant Pressure Control, Soft-Start, and Integrated Dry-Run Protection, but these are just a few of the features these pumps offer. SQ pump models operate at a constant speed much like today’s conventional pumps. The difference is that SQ delivers the benefits of an electronically controlled permanent-magnet motor that cannot be achieved with a conventional induction motor. Fig. 1 Pcut-out curve High pump efficiency The hydraulic pump components are polyamide reinforced with 30 % glass fiber. The hydraulic design provides for high pump efficiency resulting in low energy consumption and therefore low energy costs. High motor efficiency The motors are based on a permanent magnet rotor (PM motor) featuring high efficiency within a wide load range. Eta [%] 70 SQ.3 MS 65 Conventional Conventional3-ph. 3 ph SQ pumps are available for single-phase power; a simple 2-wire design makes installation easy. 60 Conventional Conventional1-ph. 1 ph SQE pumps are equipped with a Grundfos "Smart Motor." Like the SQ models, SQ pumps have a high efficiency permanent-magnet motor — but we add the ability to communicate. 50 55 45 200 Fig. 2 250 300 350 400 450 500 550 P2 [W] TM01 2698 2298 SQ, SQE innovative motor technology TM01 2751 2298 Additionally, SQE pumps offer these advantages: Efficiency curves of Grundfos SQ motor versus conventional motors 3 SQ, SQE, SQE-NE, CU331SP 1 Overvoltage and undervoltage protection The pump design features "floating" impellers (not fastened to the shaft). Each impeller has its own tungsten carbide/ceramic bearing. The construction and materials ensure high wear resistance to sand for long product life. Overvoltage and undervoltage may occur in case of unstable voltage supply. TM01 3141 3498 Product introduction Wear resistance Fig. 3 The pump will cut out if the voltage falls below 150 V or rises above 315 V. The motor is automatically cut in again when the voltage again falls within the permissible voltage range. Therefore no extra protection relay is needed. Overload protection Example of Grundfos floating impeller Protection against upthrust Starting up a pump with a very low counter pressure involves the risk of the entire impeller stack being lifted, also called upthrust. Upthrust may cause breakdown of both pump and motor. SQ, SQE, SQE-NE motors are fitted with a top bearing protecting both pump and motor against upthrust, thus preventing breakdown during the critical start-up phase. Excellent starting capabilities The integrated electronic unit of the motor features soft starting. Soft start reduces the starting current and thus gives the pump a smooth and steady acceleration. The soft starter minimizes the risk of wear on the pump and prevents overloading of the mains during start-up. The excellent starting capabilities are a result of the high locked-rotor torque of the permanent magnet motor together with the few pump stages. The high starting reliability also applies in case of low voltage supply. Exposure of the pump to heavy load causes the current consumption to rise. The motor will automatically compensate for this by reducing the speed to 3000 rpm. Further overload will lead to stop. If the rotor is being prevented from rotating, this will automatically be detected and the power supply will be cut out. Consequently, no extra motor protection is needed. Overtemperature protection A permanent magnet motor gives off very little heat to its surroundings. In combination with an efficient internal circulation system leading the heat away from the rotor, stator and bearings, this ensures optimum operating conditions for the motor. As an extra protection, the electronic unit has a built-in temperature sensor. When the temperature rises too high, the motor is cut out; when the temperature has dropped, the motor is automatically cut in again. Reliability The motors are built for high reliability and feature: • Tungsten carbide / ceramic bearings • thrust bearings protecting against downthrust Current [A] • product life time equal to conventional AC motors. Variable speed Soft start 3 Soft-start feature Time [s] TM01 3479 4198 DOL (direct-on-line starting) Fig. 4 The integrated protection of all motors prevents damage to the motor in case the voltage moves outside the permissible voltage range. The SQE motor enables continuously variable speed control from 3,000 to 10,700 rpm. The pump can be set to operate in any duty point in the range between the 3,000 and 10,700 rpm performance curves of the pump. Consequently, the pump performance can be adapted to any specific requirement. The variable speed control facility requires the use of the CU 300 or CU 301 control unit. For the calculation of pump speed, the program "SQE Speed Calculation" is available on CD-ROM as an accessory. 4 SQ, SQE, SQE-NE, CU331SP 1 Product introduction Identification Type key example SQ, SQE, SQE-NE 10 SQ E 05 - 160 N E Rated gallons per minute Basic version (without communication) Electronic communication Horsepower Total Dynamic Head in (ft) at rated flow Stainless steel 316 Environmental, PVDF impellers 5 SQ, SQE, SQE-NE, CU331SP 2 Applications 2. Applications SQ with pressure switch and pressure tank SQ is ideally suited for domestic water supply in single- family dwellings or summer homes which are not connected to municipal waterworks. SQ is easy to install and operate. 17 1 2 3 4 12 14 17 18 20 21 22 30 31 4 12 14 20 18 21 17 Pump, SQ Cable Cable clips Pressure tank Pressure switch Pressure gauge Isolating valve Tap Mains switch Mains connection Riser pipe Safety cable Wire clamp 31 22 Recommended min. 20 inches (0.5 m) 2 3 30 TM01 2447 1798 31 1 Min. 20 inches (0.5 m) Fig. 5 Application example: SQ with pressure switch and pressure tank Pos. Part 1 2 3 4 12 14 20 30 31 6 Pump Cable Cable clips Pressure tank Pressure switch Pressure gauge Mains switch Safety cable Wire clamp Type SQ No. of units Product number Unit price Total price SQ, SQE, SQE-NE, CU331SP 2 Applications Constant-pressure control with CU 301 - residential water supply When the pressure in the tank is 7 psi (0.5 bar) below setpoint, the pump will start. The pump will run until the pressure is 7 psi (0.5 bar) above setpoint. This way of operation is called on/off operation. The system maintains a constant pressure within the maximum pump performance in spite of a varying water consumption. The pressure is registered by the pressure sensor and transmitted to the CU 301. The CU 301 adjusts the pump performance accordingly. At a flow higher than approximately 1 gpm (0.18 m3/h), the pressure will drop quickly and the pump will start immediately and maintain a constant pressure. Function When a tap is opened the pressure in the tank will start to drop. At a flow lower than approximately 1 gpm (0.18 m3/h), the pressure will drop slowly. During operation, the CU 301 will regulate the pump speed to maintain a constant pressure. If there is no consumption, the pump will boost the pressure to 7 psi (0.5 bar) above setpoint and stop after a few seconds. 1 2 3 4 5 10 14 18 21 22 30 31 Pump, SQE Cable Cable clips Pressure tank, 2 gal (8 liters) Control unit, CU 301 Pressure sensor, 0 - 120 psi (0 - 6 bar) Pressure gauge Tap Mains connection Riser pipe Safety cable Wire clamp TM03 3429 0406 Recommended min. 20 inches (0.5 m) Min. 20 inches (0.5 m) Fig. 6 Application example: Constant-pressure control with CU 301 - residential water supply Pos. Part 1 2 3 4 5 10 14 30 31 Pump Cable Cable clips Pressure tank Control unit Pressure sensor Pressure gauge Safety cable Wire clamp Type No. of units Product number Unit price Total price SQE 2 gal (8 liters) CU 301 0 - 120 psi (0 - 6 bar) 7 SQ, SQE, SQE-NE, CU331SP 2 Applications Constant-pressure control with CU 301 - irrigation tank is 7 psi (0.5 bar) below setpoint, the pump will start. The pump will run until the pressure is 7 psi (0.5 bar) above setpoint. This way of operation is called on/off operation. The system maintains a constant pressure within the maximum pump performance in spite of a varying water consumption. The pressure is registered by means of the pressure sensor and transmitted to the CU 301. The CU 301 adjusts the pump performance accordingly. At a flow higher than approximately 1 gpm (0.18 m3/h), the pressure will drop quickly and the pump will start immediately and maintain a constant pressure. Function During operation, the CU 301 will regulate the pump speed to maintain a constant pressure. If there is no consumption, the pump will boost the pressure to 7 psi (0.5 bar) above setpoint and stop after a few seconds. When the sprinkler system is started, the pressure in the tank will start to drop. At a flow lower than approximately 1 gpm (0.18 m3/h), the pressure will drop slowly. When the pressure in the 1 2 3 4 5 10 14 18 21 22 30 31 Pump, SQE Cable Cable clips Pressure tank 2 gal (8 liter) Control unit, CU 301 Pressure sensor, 0 - 120 psi (0-6 bar) Pressure gauge Sprinkler system Mains connection Riser pipe Safety cable Wire clamp TM03 3428 2810 Recommended min. 20 inches (0.5 m) Min. 20 inches (0.5 m) Fig. 7 Application example: Constant-pressure control with CU 301 - irrigation Pos. Part 1 2 3 4 5 10 14 30 31 8 Pump Cable Cable clips Pressure tank Control unit Pressure sensor Pressure gauge Safety cable Wire clamp Type SQE 2 gal (8 liter) CU 301 0 - 120 psi (0 - 6 bar) No. of units Product number Unit price Total price SQ, SQE, SQE-NE, CU331SP 2 A constant water table can be maintained by adjusting pump performance. It may be important to maintain a constant water table, e.g. in connection with keeping out the groundwater on a building site or water remediation projects. The example shows how to maintain a constant water table by adjusting pump performance. Sensors Level Description 5 R100 R100 Warning (max.) Desired level 1 2 3 5 11 21 22 29 30 31 29 31 Reaction Level sensor (pos. 11) Warning (min.) 21 Applications Maintaining a constant water table Too high water level. Possible cause: Insufficient pump capacity. The water level which should be maintained. Too low water level. Possible cause: Too high pump capacity. Alarm relay operates. Alarm relay operates. Pump, SQE Cable Cable clips Control unit, CU 300 Level sensor Mains connection Riser pipe Remote control, R100 Safety cable Wire clamp Warning (max.) 22 2 Desired level 3 Warning (min.) 30 Recommended min. 20 inches (0.5 m) 31 11 TM01 2459 2810 1 Min. 0.5 m Fig. 8 Pos. 1 Application example: Maintaining a constant water table Part Type Pump SQE 2 Cable 3 Cable clips 5 Control unit 11 Level sensor 29 Remote control 30 Safety cable 31 Wire clamp No. of units Product number Unit price Total price CU 300 R100 9 SQ, SQE, SQE-NE, CU331SP 2 Applications Emptying or filling a tank The SQE pump with CU 300 is ideal for emptying or filling a tank. 5 R100 R100 21 5 29 2 R100 R100 21 3 29 22 Max. (start) 27 11 1 Min. (stop) Recommended min. 20 inches (0.5 m) 11 22 2 Recommended min. 20 inches (0.5 m) 3 30 31 Fig. 9 Pos. 10 Pump, SQE Cable Cable clips Control unit, CU 300 Level sensor Mains connection Riser pipe Flow sleeve with strainer and supporting brackets Remote control, R100 Safety cable Wire clamp 1 Min. 20 inches (0.5 m) Application example: Emptying or filling a tank Part Type 1 Pump SQE 2 Cable 3 Cable clips 5 Control unit 11 Level sensor 22 Riser pipe 27 Flow sleeve with strainer and supporting brackets 29 Remote control 30 Safety cable 31 Wire clamp CU 300 R100 No. of units Product number Unit price Total price TM01 8649 4801 1 2 3 5 11 21 22 27 29 30 31 SQ, SQE, SQE-NE, CU331SP 2 The SQE pump is ideal for pumping water from one tank to another. Applications Pumping from one tank to another Sensors Level Light indication on CU 300 Description Level sensor (pos. 11, tank at top) Green indicator light When the water has reached in on/off button is this level, the pump stops. flashing. Green indicator light When the water has dropped in on/off button is to this level, the pump starts. permanently on. Max. (stop) Min. (start) Level sensor (pos. 11, tank at bottom) Green indicator light When the water has reached in on/off button is this level, the pump starts. on. Green indicator light When the water has dropped in on/off button is to this level, the pump stops. flashing. Max. (start) Min. (stop) 5 R100 R100 29 21 Max. (stop) 22 Min. (start) 11 1 2 3 5 11 21 22 27 29 Pump, SQE Cable Cable clips Control unit, CU 300 Level sensor Mains connection Riser pipe Flow sleeve with strainer and supporting brackets Remote control, R100 3 2 11 TM01 2454 4801 Max. (start) 27 Min. (stop) 1 Recommended min. 20 inches (0.5 m) Fig. 10 Application example: Pumping from one tank to another Pos. Part Type 1 Pump SQE 2 Cable 3 Cable clips 5 Control unit 11 Level sensor 27 Flow sleeve with strainer and supporting brackets 29 Remote control No. of units Product number Unit price Total price CU 300 R100 11 SQ, SQE, SQE-NE, CU331SP 2 Applications Setting of operating parameters Using the R100 and the CU 300 enables change of the motor speed and thereby setting of the pump to a specific performance. Dry-running protection The software program "SQE Speed Calculation" has been developed for the calculation of the speed in order to obtain the required flow rate and head. If the speed of the SQE pump is reduced by more than 1000 rpm, the Pcut-out value must be readjusted by means of the CU 300 and R100. The value Pcut-out, ensuring dry-running protection, is factory-set for the SQE pump. CU 300 R100 Note: The SQE pump must not be started until the pump has been completely submerged below the water table. However, the change of the motor speed can be made even if the pump is not submerged. TM01 8650 4801 SQE Fig. 11 Application example: Workshop setting of operating parameters Part Type Pump SQE Remote control Control unit SQE Speed Calculation program 12 R100 CU 300 No. of units Product number Unit price Total price SQ, SQE, SQE-NE, CU331SP 2 Functioning and benefits Manual speed control of the SQE pumps is possible by means of R100 and an SPP 1 potentiometer. This application is especially suitable for sampling from groundwater monitoring wells. The monitoring well is purged at high speed and the sample is taken at a low speed (quiet flow). For contaminated groundwater the SQE-NE type range is recommended. In case frequent sampling is required, dedicated installation of the pump is recommended, thus eliminating wear caused by frequent assembly and dismantling the installation. 5 Applications SQE with manual speed control Furthermore, dedicated installations saves the costs of assembling and dismantling the installation. Important: Through dedicated installation the transfer of contamination from one monitoring well to another is avoided. Dry-running protection The value Pcut out, ensuring dry-running protection, is factory-set for the SQE pump. If the speed of the pump is reduced more than 1,000 rpm, the value of Pcut out must be readjusted by means of CU 300 and R100. 1 2 3 5 21 22 30 31 32 32 21 SQE pump Cable Cable clips Control unit, CU 300 Mains connection Riser pipe Stainless-steel safety cable Stainless-steel wire clamps, 2 per lifting eye Potentiometer, SPP 1 22 Recommended min. 20 inches (0.5 m) 2 3 30 31 TM01 9028 4801 1 Min. 20 inches (0.5 m) Fig. 12 Application example: Sampling/manual speed control of SQE Pos. 1 2 3 5 22 30 31 32 Part Type Pump Cable Cable clips Control unit Riser pipe Stainless-steel safety cable Wire clamps Potentiometer SQE No. of units Product number Unit price Total price CU 300 2 per lifting eye SPP 1 13 SQ, SQE, SQE-NE, CU331SP 3 Performance range 3. Performance range H [m] H [ft] SQ SQE SQE-NE 800 200 ISO 9906 Annex A 600 400 100 90 300 80 70 60 200 50 150 40 30 100 30 SQ, SQE 5 SQ, SQE 60 22 SQ, SQE, SQE-NE 20 15 SQ, SQE 10 SQ, SQE, SQE-NE 80 40 10 0 0 14 4 8 12 2 16 20 4 24 28 6 32 36 8 Q [US GPM] Q [m³/h] TM02 9975 2010 30 SQ, SQE, SQE-NE, CU331SP 4 Installation 4. Installation The SQ and SQE, SQE-NE may be installed vertically, horizontally or in any position in between. Note: The pump must not fall below the horizontal level in relation to the motor. The following features ensure simple installation of the pump: • Built-in check valve with spring • low weight ensuring user-friendly handling • installation in 3" or larger boreholes • only on/off switch is needed, which means that no extra motor starter / starter box is necessary. For horizontal installation a flow sleeve is recommended in order to: • ensure sufficient flow velocity past the motor and thus provide sufficient cooling • prevent motor and electronic unit from being buried in sand or mud. Not allowed TM01 1375 1498 Allowed Fig. 13 SQE installation 15 SQ, SQE, SQE-NE, CU331SP 5 Sizing and selection 5. Sizing and selection System sizing guide Step 1 Calculate minimum head requirements at no flow conditions: Hmax (required) = dynamic head + system pressure (in feet) + above grade elevation + friction loss Step 2 Select pump from chart as follows: • Choose model family based on the desired flow rate (i.e. 15SQE for a flow rate of 15 gpm) • Select the first model with a value in Column 2 greater than the Hmax calculated in Step 1 (For example: the choice for a 22 gpm model with an Hmax of 140 ft would be the 22SQE-160). • Double check your selection in the performance curves; see 7. SQ curve charts on p. 18. System sizing matrix 16 Head @ rated gpm @ 10700 rpm max. speed TDH [feet] TDH [feet] 5SQE-90 11 86 5SQE-140 17 131 5SQE-180 22 177 5SQE-230 28 222 5SQE-270 34 270 5SQE-320 39 315 5SQE-360 45 360 5SQE-410 51 405 5SQE-450 56 450 10SQE-110 12 105 10SQE-160 17 164 10SQE-200 23 215 10SQE-240 29 267 10SQE-290 34 328 10SQE-330 40 390 15SQE-70 10 75 15SQE-110 14 123 15SQE-150 19 164 15SQE-180 24 205 15SQE-220 29 246 15SQE-250 33 287 15SQE-290 38 328 22SQE-40 5 36 22SQE-80 9 77 22SQE-120 14 117 22SQE-160 18 159 22SQE-190 23 200 22SQE-220 27 240 30SQE-40 5 33 30SQE-90 11 82 30SQE-130 16 126 Pump curve at 3,000 rpm Fig. 14 Recommended sizing Note: All calculated head requirements must lie between the selected pump models minimum and maximum speed curves. TM01 8547 0400 Shutoff head (0 gpm) @ 3000 rpm min. speed Pump curve at 10,700 ft Max. head at no flow Column 2 Max. head at rated flow Pump type Model B Column 1 SQ, SQE, SQE-NE, CU331SP 6 Cable sizing 6. Cable sizing Cable sizing chart Motor rating Copper wire size (AWG) Volts Hp Amps 14 12 10 8 6 4 2 115 0.5 12 140 220 360 550 880 1390 2260 — 230 0.5 5.2 640 1000 1660 2250 4060 — 230 0.75 8.4 400 620 1030 1580 2510 3970 — 230 1 11.2 300 460 770 1190 1890 2980 4850 230 1.5 12 280 430 720 1110 1760 2780 4530 Cable length in feet. Note: shaded values do not apply when using a CU 301 as its max. recommended cable length is 650 ft. 17 SQ, SQE, SQE-NE, CU331SP 7 SQ curve charts 7. SQ curve charts 5 SQ, SQE H [m] 250 H [ft] 800 5 SQ 5 SQE -450 ISO 9906 Annex A -410 700 200 -360 600 -320 150 500 -270 -230 400 100 -180 300 -140 200 -90 50 100 0 0 0 H [m] 1 2 3 4 5 6 Q [US GPM] 2 3 4 5 6 Q [US GPM] H [ft] 24 4 16 2 8 0 0 NPSH 0 0.0 18 1 0.4 0.8 1.2 1.6 Q [m³/h] TM04 7463 2010 6 SQ, SQE, SQE-NE, CU331SP 7 H [m] H [ft] 10 SQ 10 SQE 550 160 SQ curve charts 10 SQ, SQE ISO 9906 Annex A -330 500 140 120 450 -290 400 -240 350 100 -200 300 80 60 250 -160 200 -110 150 40 100 20 0 50 0 0 H [m] 8 1 2 3 4 5 6 7 8 9 10 11 12 13 Q [US GPM] 3 4 5 6 7 8 9 10 11 12 13 Q [US GPM] H [ft] 30 20 0 10 NPSH 0 0 0.0 1 2 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 Q [m³/h] TM04 7464 2010 4 19 SQ, SQE, SQE-NE, CU331SP 7 SQ curve charts 15 SQ, SQE H [m] H [ft] 500 15 SQ 15 SQE -290 ISO 9906 Annex A 450 -250 120 400 -220 350 -180 300 80 -150 250 200 -110 150 40 -70 100 50 0 0 0 H [m] 8 2 4 6 8 10 12 14 16 18 Q [US GPM] 4 6 8 10 12 14 16 18 Q [US GPM] H [ft] 30 20 0 10 NPSH 0 0 0 20 2 1 2 3 4 Q [m³/h] TM04 7465 2010 4 SQ, SQE, SQE-NE, CU331SP 7 H [m] H [ft] 22 SQ 22 SQE 360 ISO 9906 Annex A -220 100 SQ curve charts 22 SQ, SQE 320 -190 280 80 240 60 -160 200 -120 160 40 120 -80 80 20 -40 40 0 0 0 H [m] 8 4 8 12 16 20 24 28 Q [US GPM] 8 12 16 20 24 28 Q [US GPM] H [ft] 30 20 0 10 NPSH 0 0 0 4 2 4 6 Q [m³/h] TM04 7466 2010 4 21 SQ, SQE, SQE-NE, CU331SP 7 SQ curve charts 30 SQ, SQE H [m] H [ft] 30 SQ 30 SQE 220 60 ISO 9906 Annex A -130 200 180 50 160 140 -90 40 120 30 100 80 20 10 -40 60 40 20 0 0 0 H [m] 8 4 8 12 16 20 24 28 32 36 Q [US GPM] 8 12 16 20 24 28 32 36 Q [US GPM] H [ft] 30 20 0 10 NPSH 0 0 0 22 4 2 4 6 8 Q [m³/h] TM04 7467 2010 4 SQ, SQE, SQE-NE, CU331SP 7 H [m] H [ft] SQ curve charts 10 SQE-NE 10 SQE - NE 550 ISO 9906 Annex A 160 -340 500 140 120 450 -300 400 -260 350 100 -220 300 80 60 -180 250 200 -140 150 -100 40 100 20 50 0 0 0 H [m] 2 4 6 8 10 12 Q [US GPM] 2 4 6 8 10 12 Q [US GPM] H [ft] 30 8 20 0 10 NPSH 0 0 0 1 2 3 Q [m³/h] TM04 7468 2010 4 23 SQ, SQE, SQE-NE, CU331SP 7 SQ curve charts 22 SQE-NE H [m] H [ft] 22 SQE - NE 100 ISO 9906 Annex A 320 -210 280 80 -180 240 60 -140 200 160 -110 40 120 -80 80 20 -40 40 0 0 0 H [m] 4 8 12 16 20 24 28 Q [US GPM] 8 12 16 20 24 28 Q [US GPM] H [ft] 24 6 16 4 8 0 0 NPSH 0 0 24 4 2 4 6 Q [m³/h] TM04 7469 2010 2 SQ, SQE, SQE-NE, CU331SP 8 Technical data 8. Technical data Electrical data Supply voltage: 1x200-240V +6%/-10%, 50/60 Hz, PE 1x100-115V +6%/-10%, 50/60 Hz, PE Operation via generator: As a minimum, the generator output must be equal to the motor P1[kw] + 10% Starting current: The motor starting current is equal to the highest value stated on the motor nameplate Starting: Soft Start Run-up time: Maximum: 2 seconds Motor protection: Motor is protected against: – Dry running – overvoltage – undervoltage – overload – overtemperature. Power factor: PF=1 Motor cable: 3 wire, 14AWG XLPE, 5 ft Motor liquid: Type SML 2 pH Values: SQ and SQE: 5 to 9 SQE-NE: 2 to 13 Liquid temperature: The temperature of the pumped liquid must not exceed 86 °F (30 °C) Note: If liquids with a viscosity higher than that of water are to be pumped, please contact Grundfos. Control units CU 300 and CU 301 Voltage: 1 x 100-240 V – 10 %/+ 6 %, 50/60 Hz, PE Power consumption: 5W Current consumption: Maximum 130 mA Enclosure class: IP 55 Ambient temperature: During operation: –22 °F to +122 °F (–30 °C to +50 °C) During storage: –22 °F to 140 °F ( –30 °C to +60 °C) Relative air humidity: 95 %. Pump cable: Maximum length between CU 300 or CU 301 and pump: 650 ft (198 m) Back-up fuse: Maximum: 16 A Radio noise: CU 300 and CU 301 comply with EMC Directive 89/336/EEC. Approved according to the standards EN 55014 and EN 55014-2 Marking: CE, cUL (CU 301) Load: Max. 100 mA Operating conditions Minimum ambient fluid temperature: +34 °F (+1 °C) Maximum ambient fluid temperature: +86 °F (+30 °C) Well diameter: 3-inch or larger Installation depth (maximum): 500 feet below static water level Storage conditions Minimum ambient temperature: –4 °F (–20 °C) Maximum ambient temperature: +140 °F (+60 °F) Frost protection: If the pump has to be stored after use, it must be stored at a frost-free location, or it must be ensured that the motor liquid is frost-proof. 25 SQ, SQE, SQE-NE, CU331SP 8 Technical data Motor data Full load amps Pump type 26 Hp Overload amps 230V 115V 230V 115V Min. well diameter Voltage Discharge 5SQE05-90 1/2 230V / 115V 2.1 4.2 5 11 3" 1" NPT 5SQE05-140 1/2 230V / 115V 2.9 6.0 5 11 3" 1" NPT 5SQE05-180 1/2 230V / 115V 3.7 7.7 5 11 3" 1" NPT 5SQE07-230 3/4 230V 4.6 - 8 - 3" 1" NPT 5SQE07-270 3/4 230V 5.3 - 8 - 3" 1" NPT 5SQE07-320 3/4 230V 6.2 - 8 - 3" 1" NPT 5SQE10-360 1 230V 7.2 - 11 - 3" 1" NPT 5SQE10-410 1 230V 8.1 - 11 - 3" 1" NPT 5SQE15-450 1 1/2 230V 9.2 - 12 - 3" 1" NPT 10SQE05-110 1/2 230V / 115V 2.9 6.1 5 11 3" 1 1/4" NPT 10SQE05-160 1/2 230V / 115V 4.1 8.6 8 11 3" 1 1/4" NPT 10SQE07-200 3/4 230V 5.3 - 8 - 3" 1 1/4" NPT 10SQE7-240 3/4 230V 6.0 - 8 - 3" 1 1/4" NPT - 10SQE10-290 1 230V 7.7 - 11 10SQE15-330 1 1/2 230V 8.9 - 12 3" 1 1/4" NPT 3" 1 1/4" NPT 15SQE05-70 1/2 230V / 115V 2.9 6.0 5 11 3" 1 1/4" NPT 15SQE05-110 1/2 230V / 115V 4.0 8.3 5 11 3" 1 1/4" NPT 15SQE07-150 3/4 230V 5.1 - 8 - 3" 1 1/4" NPT 15SQE07-180 3/4 230V 6.2 - 8 - 3" 1 1/4" NPT 15SQE10-220 1 230V 7.4 - 11 - 3" 1 1/4" NPT 15SQE10-250 1 230V 8.4 - 11 - 3" 1 1/4" NPT 15SQE15-290 1 1/2 230V 9.7 - 12 - 3" 1 1/4" NPT 22SQE05-40 1/2 230V / 115V 1.9 3.9 5 - 3" 1 1/2" NPT 22SQE05-80 1/2 230V / 115V 3.4 7.2 5 - 3" 1 1/2" NPT 22SQE07-120 3/4 230V 4.9 - 8 - 3" 1 1/2" NPT 22SQE10-160 1 230V 6.4 - 8 - 3" 1 1/2" NPT 22SQE10-190 1 230V 7.9 - 11 - 3" 1 1/2" NPT 22SQE15-220 1 1/2 230V 9.5 - 12 - 3" 1 1/2" NPT 30SQE05-40 1/2 230V / 115V 2.8 5.7 5 - 3" 1 1/2" NPT 30SQE07-90 3/4 230V 5.2 - 8 - 3" 1 1/2" NPT 30SQE10-130 1 230V 7.6 - 11 - 3" 1 1/2" NPT SQ, SQE, SQE-NE, CU331SP 8 Technical data Dimensions and weights SQ, SQE Model Hp Motor size Discharge size Dimensions in inches A B C D E Approx. ship. wt. 5SQ/SQE05-90 1/2 3" 1" NPT 30.4 19.8 10.6 2.6 2.9 5SQ/SQE05-140 1/2 3" 1" NPT 30.4 19.8 10.6 2.6 2.9 12 12 5SQ/SQE05-180 1/2 3" 1" NPT 31.5 19.8 11.6 2.6 2.9 12 5SQ/SQE07-230 3/4 3" 1" NPT 33.6 19.8 13.7 2.6 2.9 13 5SQ/SQE07-270 3/4 3" 1" NPT 33.6 19.8 13.7 2.6 2.9 13 5SQ/SQE07-320 3/4 3" 1" NPT 34.6 19.8 14.8 2.6 2.9 13 5SQ/SQE10-360 1 3" 1" NPT 38.2 21.3 16.9 2.6 2.9 16 5SQ/SQE10-410 1 3" 1" NPT 38.2 21.3 16.9 2.6 2.9 16 5SQ/SQE15-450 1 1/2 3" 1" NPT 39.3 21.3 18.0 2.6 2.9 16 10SQ/SQE05-110 1/2 3" 1 1/4" NPT 30.4 19.8 10.6 2.6 2.9 12 10SQ/SQE05-160 1/2 3" 1 1/4" NPT 30.4 19.8 10.6 2.6 2.9 12 10SQ/SQE07-200 3/4 3" 1 1/4" NPT 31.5 19.8 11.6 2.6 2.9 13 10SQ/SQE07-260 3/4 3" 1 1/4" NPT 33.6 19.8 13.7 2.6 2.9 13 10SQ/SQE10-290 1 3" 1 1/4" NPT 35.0 21.3 13.7 2.6 2.9 16 10SQ/SQE15-330 1 1/2 3" 1 1/4" NPT 36.14 21.3 14.8 2.6 2.9 16 15SQ/SQE05-70 1/2 3" 1 1/4" NPT 30.4 19.8 10.6 2.6 2.9 12 15SQ/SQE05-110 1/2 3" 1 1/4" NPT 30.4 19.8 10.6 2.6 2.9 12 15SQ/SQE07-150 3/4 3" 1 1/4" NPT 31.5 19.8 11.6 2.6 2.9 13 15SQ/SQE07-180 3/4 3" 1 1/4" NPT 33.6 19.8 13.7 2.6 2.9 13 15SQ/SQE10-220 1 3" 1 1/4" NPT 35.0 21.3 13.7 2.6 2.9 16 15SQ/SQE10-250 1 3" 1 1/4" NPT 36.1 21.3 14.8 2.6 2.9 16 15SQ/SQE10-290 1 1/2 3" 1 1/4" NPT 38.2 21.3 16.9 2.6 2.9 16 22SQ/SQE05-40 1/2 3" 1 1/2" NPT 30.4 19.8 10.6 2.6 2.9 12 22SQ/SQE05-80 1/2 3" 1 1/2" NPT 30.4 19.8 10.6 2.6 2.9 12 22SQ/SQE07-120 3/4 3" 1 1/2" NPT 31.5 19.8 11.6 2.6 2.9 13 22SQ/SQE10-160 1 3" 1 1/2" NPT 33.6 19.8 13.7 2.6 2.9 13 22SQ/SQE10-190 1 3" 1 1/2" NPT 38.2 21.3 16.9 2.6 2.9 16 22SQ/SQE15-220 1 1/2 3" 1 1/2" NPT 38.2 21.3 16.9 2.6 2.9 16 30SQ/SQE05-40 1/2 3" 1 1/2" NPT 30.4 19.8 10.6 2.6 2.9 12 30SQ/SQE07-90 3/4 3" 1 1/2" NPT 30.4 19.8 10.6 2.6 2.9 13 30SQ/SQE10-130 1 3" 1 1/2" NPT 35.0 21.3 13.7 2.6 2.9 13 10SQE-05-100NE 1/2 3" 1 1/4" NPT 30.4 19.8 10.6 2.6 2.9 12 10SQE-05-140NE 1/2 3" 1 1/4" NPT 30.4 19.8 10.6 2.6 2.9 12 10SQE-05-180NE 3/4 3" 1 1/4" NPT 31.5 19.8 11.6 2.6 2.9 13 10SQE-07-220NE 3/4 3" 1 1/4" NPT 33.6 19.8 13.7 2.6 2.9 13 10SQE-10-260NE 1 3" 1 1/4" NPT 35.0 21.3 13.7 2.6 2.9 16 10SQE-10-300NE 1 3" 1 1/4" NPT 36.1 21.3 14.8 2.6 2.9 16 10SQE-10-340NE 1 3" 1 1/4" NPT 38.2 21.3 16.9 2.6 2.9 16 22SQE05-40NE 1/2 3" 1 1/2" NPT 30.4 19.8 10.6 2.6 2.9 12 22SQE05-80NE 1/2 3" 1 1/2" NPT 30.4 19.8 10.6 2.6 2.9 12 22SQE07-110NE 3/4 3" 1 1/2" NPT 31.5 19.8 11.6 2.6 2.9 13 22SQE07-140NE 3/4 3" 1 1/2" NPT 33.6 19.8 13.7 2.6 2.9 13 22SQE10-180NE 1 3" 1 1/2" NPT 38.2 21.3 16.9 2.6 2.9 16 22SQE10-210NE 1 3" 1 1/2" NPT 38.2 21.3 16.9 2.6 2.9 16 SQE-NE 27 SQ, SQE, SQE-NE, CU331SP 9 Construction 9. Construction Materials of construction SQE-NE Component Splined shaft Component Splined shaft Valve casing Polyamide Valve casing PVDF Discharge chamber 304 stainless steel Discharge chamber 316 stainless steel Valve guide Polyamide O-ring FPM rubber Valve spring 316LN stainless steel Valve cone PVDF Valve cone Polyamide Valve seat FPM rubber Valve seat NBR rubber Top chamber PVDF O-ring NBR rubber Empty chamber PVDF Lock ring 310 stainless steel Top bearing FPM rubber Top bearing NBR rubber Neck ring PVDF Top chamber Polyamide Lock ring 316 stainless steel Guide vanes Polyamide Guide vanes PVDF Impeller Polyamide w/ tungsten carbide bearings Bottom chamber PVDF Polyamide Impeller w/ tungsten carbide bearing PVDF Bottom chamber Neck ring TPU / PBT Suction interconnector PVDF Bearing Aluminum oxide Ring 316 stainless steel Suction interconnector Polyamide Ring 304 stainless steel Shaft w/coupling Sintered steel 316 stainless steel Pump sleeve 304 stainless steel Cable guard 316 stainless steel Pressure equalization cone Polyamide Cable guard screws 316 stainless steel Spacer Polyamide Pressure equalization cone PVDF Sand trap 316 stainless steel Valve spring 316 stainless steel Shaft w/coupling 304 stainless steel Pump sleeve 316 stainless steel Cable guard 304 stainless steel Valve guide PVDF Spacer 316 stainless steel Discharge sizes: 1" NPT 5 SQ/SQE 1 1/4" NPT 10 - 15 SQ/SQE 1 1/2" NPT 22-30 SQ/SQE 28 TM04 7522 2110 SQ, SQE SQ, SQE, SQE-NE, CU331SP 9 Construction Material specification Pump Pos. Component Material DIN W-Nr. SQ/SQE AISI DIN W-Nr. SQ/-NE AISI 1.4301 304 1.4401 316 1a 1 Valve casing Polyamide 1a Discharge chamber Stainless steel 70 1d O-ring NBR rubber 39 2 Valve cup Polyamide 3 Valve seat NBR rubber 2 4a Empty chamber Polyamide 3 6 Top bearing NBR rubber 7 Neck ring TPU / PBT 7a Lock ring Stainless spring steel 7b Neck ring retainer Polyamide 9b Chamber top Polyamide 9c Chamber bottom Polyamide 13 Impeller with tungsten carbide bearing Polyamide 14 14a 55 1 1.4301 310 1.4401 18b 316 1d 7a 6 64 18 4a 14 Suction inter-connector Polyamide 14a Ring Stainless steel 1.4301 304 1.4401 316 16 Shaft with coupling Stainless steel 1.4301 304 1.4401 316 18 Cable guard Stainless steel 1.4301 304 1.4401 316 18a 18b Screws for cable guard Stainless steel 1.4301 316 1.4401 316 30 Cone for pressure equalization Polyamide 32 Guide vanes Polyamide 39 Spring Stainless spring steel 1.4406 316LN 1.4406 316LN 55 Pump sleeve Stainless steel 1.4301 304 1.4401 316 64 Priming screw Polyamide 70 Valve guide Polyamide 86 Lip seal ring NBR rubber 87 Cone for pressure equalization complete Polyamide / NBR rubber Sintered steel 30 87 9b 86 32 13 16 18a 9c 7 7b 222a 225 232 224 205 Motor 201 DIN W-Nr. SQ-SQE AISI DIN W-Nr. SQE-NE AISI Stainless steel 1.4301 304 1.4401 316 1.4301 304 1.4401 316 Component Stator Material 202 Rotor Stainless steel 202a Stop ring PP 202b Filter Polyester 203 Thrust bearing Carbon 205 Radial bearing Ceramic tungsten carbine 220 Motor cable with plug EPR 222a Filling plug MS 3: NBR MSE 3: FKM 224 O-ring FKM 225 Top cover PPS Shaft seal MS 3: NBR MSE 3: FKM Motor liquid SML-2 232 202a 202b 201 202 220 203 TM01 2745 2010 Pos. 29 SQ, SQE, SQE-NE, CU331SP 10 Control units 10. Control units CU 301 6 The CU 301 is a control and communication unit developed especially for the SQE submersible pumps in constant-pressure applications. 1 2 3 4 bar 5.0 4.5 4.0 The CU 301 control unit provides: 3.5 3.0 2.5 R100 R 100 • two-way communication with the SQE pumps • possibility of adjusting the pressure 5 • alarm indication (LED) when service is needed • possibility of starting, stopping and resetting the pump simply by means of a push-button TM03 3426 0406 2.0 • Full control of the SQE pumps Fig. 15 CU 301 control unit • configuration with R100 remote control. The CU 301 communicates with the pump via mains borne signalling (Power Line Communication), meaning that no extra cables are required between the CU 301 and the pump. 1. Pump running indicator 2. System pressure setting 3. System ON/OFF 4. Button lock indicator 5. Dry-running indicator Operating relay entry Power supply entry Pressure sensor entry Submersible drop cable entry TM02 3427 0406 The CU 301 features the following indications (see drawing in right column): Fig. 16 CU 301 entry ports 6. Service needed in case of: bar 5.0 4.5 4.0 3.5 3.0 2.5 2.0 • External signal input for pressure sensor • connection to an operating relay for indication of pump operation. Optional R100 remote control Wireless infrared remote control of the CU 301 is possible by means of the R100. Using the R100, it is possible to monitor and change the operating parameters, see the R100 menu structure on page 31. The R100 is a valuable tool in case fault finding is required. 30 Fig. 17 CU 301 dimensions 4.49 in. (114 mm) TM03 3003 2010 The CU 301 incorporates: 9.13 in. (232 mm) 7.68 in. (195 mm) – – no contact to pump – overvoltage – undervoltage – speed reduction – overtemperature – overload – sensor defective. SQ, SQE, SQE-NE, CU331SP 10 Control units R100 menu structure for CU 301 control unit Start Setting Contrast Light 0. General 1. Operation USB version only 2. Status 3. Installation 1.1 2.1 3.1 1.2 2.2 3.2 1.3 2.3 3.3 1.4 2.4 3.4 1.5 2.5 3.5 1.6 2.6 3.6 1.7 3.7 1.8 3.8 3.9 Note: This menu is an example, not the factory setting. 3.10 31 SQ, SQE, SQE-NE, CU331SP 10 Control units R100 menus for CU 301 0. General 1. Operation 1.1 Setpoint setting 1.2 Selection of operating mode 1.3 Alarm indication. 2. Status The indication of: 2.1 Actual operating mode 2.2 Actual pressure 2.3 Actual motor speed 2.4 Actual motor temperature 2.5 Actual power input and accumulated motor power consumption 2.6 Accumulated number of operating hours and accumulated number of starts. 3.Installation 3.1 Sensor parameters 3.2 Choice of sensor 3.3 Setting of maximum pressure setpoint 3.4 Setting of automatic restart time 3.5 Setting of the dry-running stop limit 3.6 Setting of the maximum motor speed 3.7 Setting of the cut-in motor speed 3.8 Activating or deactivating the on/off-button and the buttons for system pressure setting on the CU 301 3.9 Indication of pump operation 3.10 Allocation of identification number. 32 SQ, SQE, SQE-NE, CU331SP 10 LED alarm indication On/Off button with red and green indicator lights The CU 300 control unit provides: R100 • Flexible pump control based on various sensor inputs • two-way communication with the SQE pumps • alarm indication of pump operation by LED’s on the front IR communication TM01 2760 4801 The CU 300 is a control and communication unit developed especially for the SQE submersible pumps for control applications other than constant pressure. Control units CU 300 Fig. 18 CU 300 control unit with R100 • possibility of starting, stopping and resetting the pump simply by means of a push-button • communication with R100 remote control. Fieldbus entry The following alarms can be indicated by the CU 300: • No contact Power supply entry Submersible drop cable entry • overvoltage • undervoltage Sensor entries TM01 2761 4801 Extra cable entries The CU 300 communicates with the pump via mains borne signalling (Power Line Communication), meaning that no extra cables are required between the CU 300 and the pump. Fig. 19 CU 300 control unit, external entry ports • dry running 9.14 in. (232 mm) • speed reduction 4.49 in. (114 mm) • overtemperature The CU 300 incorporates: • External signal input for two analog sensors and one digital sensor • relay output for external alarm indication • control according to the signals received, e.g. of flow, pressure, water level and conductivity. TM01 2781 2010 • sensor alarm. 7.68 in. (195 mm) • overload Fig. 20 CU 300 dimensions R100 remote control Wireless infrared remote control of the CU 300 is possible by means of the R100. Using the R100, it is possible to monitor and change the operating parameters, see the R100 menu structure on page 34. The R100 is a valuable tool in case fault finding is required. 33 SQ, SQE, SQE-NE, CU331SP 10 Control units R100 menu structure for the CU 300 Start Setting Contrast Light 0. General USB version only 1. Operation 2. Status 3. Limits 4.1 1.1 2.1 1.2 2.2 3.2 4.2 1.3 2.3 3.3 4.3 1.4 2.4 3.4 4.4 1.5 2.5 3.5 4.5 1.6 2.6 3.6 4.6 1.7 2.7 3.7 4.7 1.8 2.8 3.8 4.8 2.9 3.9 4.9 3.10 4.10 Note: This menu is an example, not the factory setting. 3.1 3.11 3.12 34 4. Installation SQ, SQE, SQE-NE, CU331SP 4. 4.1 Installation Selection of controller — open loop, closed loop 4.2 Setting of external setpoint 4.3 Setting of automatic restart time 0. General 1. 1.1 Operation Setpoint setting 1.2 Selection of operating mode 4.4 Allocation of individual start delays 1.3 Alarm indication. 4.5 Setting of the stop and run times for the dewatering function 4.6 Setting of the dry-running stop limit 4.7 Activating or deactivating the dry-running protection 4.8 Setting of the maximum motor speed 4.9 Activating or deactivating the on/off-button on the CU 300 2. Status The indication of: 2.1 Actual operating mode 2.2 Actual and external setpoint 2.3 Actual motor temperature 2.4 Actual motor speed 2.5 Actual power input and accumulated motor power consumption 2.6 Accumulated number of operating hours and accumulated number of starts 2.7 Actual values of sensors 1 and 2, respectively 2.8 Actual values of the digital input 2.9 Accumulated flow, and the power used to pump. Control units R100 menus for CU 300 10 4.10 Allocation of ID number where more than one CU 300 is installed. R100 offers the possibility of making a number of settings. 3. Limits The setting of: 3.1 Sensor 1 parameters 3.2 Min. and max. stop limits of sensor 1 3.3 Min. and max. warning limits of sensor 1 3.4 Min. and max. alarm limits of sensor 1 3.5 Sensor 2 parameters 3.6 Min. and max. stop limits of sensor 2 3.7 Min. and max. warning limits of sensor 2 3.8 Min. and max. alarm limits of sensor 2 3.9 Filling or emptying 3.10 Setting of the function of the digital sensor connected to the digital input 3.11 The setting of the water quantity stop limit and the setting of the sensor to detect water quantity 3.12 The setting of the temperature warning limits of the motor electronics. 35 SQ, SQE, SQE-NE, CU331SP 10 Control units Examples of R100 displays Accumulated number of operating hours and number of starts Menu OPERATION Setpoint setting 1.1 From factory, the pump is set to maximum speed, 10,700 rpm. R100 makes it possible to reduce the pump speed by changing the setpoint. The speed can be set to 3,000 - 10,700 rpm, at 100 rpm intervals. The unit of the setpoint is automatically changed according to the unit of the sensor connected to sensor input 1. Example: Sensor input 1 is connected to a pressure sensor using the unit feet (ft) and the range 0-60. Consequently, the setpoint of display 1.1 can be set to between 0-60 ft. 2.6 The number of operating hours and the number of starts are values accumulated from the time of installation and they cannot be reset. Both values are stored in the motor electronics, and they are kept even if the CU 300 is replaced. The number of operating hours is registered every two hours of continuous operation. Menu LIMITS Sensor 1 Menu STATUS The displays appearing in this menu are status displays only. It is not possible to change settings in this menu. Accumulated flow 3.1 The setting of sensor 1. Depending on the type of sensor, the following settings can be made: • Sensor outputs: – (not active), 0-10 V, 2-10 V, 0-20 mA, 4-20 mA • setting range unit: m3/h, m, %, gpm, ft • sensor minimum value: 0-249 (0, 1, 2, 3.....249) 2.9 In display 2.9, the water quantity (m3)* pumped is shown. The value shown is the accumulated flow registered by the sensor selected in display 3.11. The power used to pump 1 m3 is shown in the display as energy per m3 (kWh/m3). It is possible to read the status of the accumulated flow and energy per m3 at any time. *Water quantity in units of gpm can be chosen. 36 • sensor maximum value: 1-250 (1, 2, 3, 4.....250). SQ, SQE, SQE-NE, CU331SP 11 Features User interface The user interface offers these possibilities: • Local operation via a control panel with graphic display where the menu structure is based on the well-known system from Grundfos E-pumps. • Monitoring of operating status via indicator lights and signal relays. • Display of alarm or warning and logging of the last five alarms and warnings. Functions Control mode: Constant pressure The CU331SP has only one control mode, Constant pressure. The pressure is kept constant, independently of the flow rate. CU331SP variable frequency drive 11. CU331SP variable frequency drive Applications For 4" or larger wells. Main applications: • • • • Domestic and light commercial water supply irrigation livestock watering water transfer. System components • Compact, efficient, and reliable variable frequency drive • rugged stainless steel pump end and proven, reliable, 3-phase motor • pressure sensor • diaphragm tank (sold separately). Start-up guide TM05 5801 4012 The CU331SP has a start-up guide, which is launched at the first power up. Parameters are set manually on the basis of the installation. The start-up guide can be repeated, if necessary. Thanks to the start-up guide, the installer can quickly set a few parameters and put the CU331SP into operation. Direction of rotation test During start-up, the CU331SP automatically tests and sets the correct direction of rotation without changing the cable connections. The direction of rotation test can be performed manually if it fails for any reason. Fig. 21 CU331SP variable frequency drive and sensor Dry-running protection To protect the pump, the CU331SP will automatically set up dry-run protection so that water shortage can be detected. The dry-run alarm will automatically reset 30 minutes after the alarm is declared. Low-flow stop function The low-flow stop function is used for changing between on/off operation at low flow rate and continuous operation at high flow rate. The low-flow stop function protects the pump and saves energy. 37 SQ, SQE, SQE-NE, CU331SP 11 CU331SP variable frequency drive Identification Nameplate TM05 6001 4012 The CU331SP can be identified by means of the nameplate. An example is shown below. Fig. 22 Example of nameplate Key Text Description T/C: Prod.no: CU-331 (product name) Product number (98370280) Serial number (000201H462) The last four digits indicate the production date. In this case, 46 is the week, and 2 is the year 2012. Typical shaft power on the motor Supply voltage, frequency and maximum input current. Motor voltage, frequency and maximum output current. The maximum output frequency usually depends on the pump type. Enclosure class Maximum ambient temperature S/N: 3.0 hp IN: OUT: Type 12 / IP55 Tamb. 38 SQ, SQE, SQE-NE, CU331SP 11 Enclosure type Indoor Outdoor NEMA Type 12 Type 4X Hp Input Ph Input volts 2 1 200 - 240 3 1 200 - 240 5 1 200 - 240 2 1 200 - 240 3 1 200 - 240 5 1 200 - 240 CU331SP variable frequency drive CU331SP product range CU331SP performance range H [ft] 2000 1500 5 Hp 1000 800 3 Hp 600 500 2 Hp 400 300 SQE 200 150 100 60 50 40 2 4 6 8 10 20 40 60 80 100 Q [US GPM] TM05 6380 5012 2 Hp 80 CU331SP sizing Step 1 Calculate maximum head requirements at rated flow conditions: Hmax=dynamic head + system psi (in feet) + friction loss + above grade elevation. Step 2 Select pump from performance curves as follows: Select a model in which the calculated value of Hmax is within the maximum performance curve of the pump. Refer to section CU331SP curve charts on page 53. Step 3 Select the CU331SP that corresponds to the correct motor Hp and enclosure type. 39 SQ, SQE, SQE-NE, CU331SP 11 CU331SP variable frequency drive CU331SP operation Menu structure The CU331SP has a start-up guide, which is launched at the first power up. After the start-up guide, the CU331SP has a menu structure divided into four main menus: 0. GENERAL gives access to the start-up guide for the general setting of the CU331SP. 1. OPERATION enables the setting of setpoint and resetting of alarms. It is also possible to see the latest five warnings and alarms. 2. STATUS shows the status of the CU331SP and the pump. It is not possible to change or set values. 3. INSTALLATION gives access to available parameters. 40 SQ, SQE, SQE-NE, CU331SP 11 START-UP GUIDE 1/11 2/11 0. GENERAL 1. OPERATION 2. STATUS CU331SP variable frequency drive CU331SP menu overview 3. INSTALLATION 0.1 1.1 2.1 3.1 0.2 1.2 2.2 3.2 1.3 2.3 3.3 1.4 2.4 3.4 1.5 - 1.9 2.5 3.5 3/11-7/11 Automatic or manual setting of the direction of rotation 8/11 2.6 9/11-10/11 Automatic setting of Stop and Dry-run functions 11/11 1.10-1.14 2.7 2.11 2.12 Fig. 23 Menu overview 41 SQ, SQE, SQE-NE, CU331SP 11 Constant pressure with stop function These operating modes can be selected with the CU331SP: • Normal • Stop • Min. • Max. The operating modes can be set without changing the setpoint setting. The outlet pressure is kept constant at high flow rate (Q > Qmin). On/off operation at low flow rate. See fig. 25. Hset Normal The pump operates in constant pressure mode. Qmin Stop The pump has been stopped by user. Fig. 25 Constant pressure with stop function Min. curve The pump is running at a set minimum speed value. See fig. 24. For instance, this operating mode can be used during periods with a very small flow requirement. Max. curve The setpoint can be set or changed during operation using the setpoint display in the "OPERATION" menu shown below. It is not necessary to run the start guide to change the setpoint. TM03 8813 2507 Max. Fig. 24 Min. and max. curves Control mode The CU331SP has been developed specifically to operate submersible pumps in Constant Pressure mode. This Closed-Loop control mode uses an analog pressure transducer to provide pressure feedback to the drive. 42 The pump is controlled according to a constant pressure measured after the pump.This means that the pump offers a constant pressure in the Q-range of Qmin to Qmax, represented by the horizontal line in the QH diagram. Setting the setpoint by means of the OPERATION menu The pump is running at a set maximum speed value. Min. Qmax TM03 8807 3307 CU331SP TM03 8477 2507 CU331SP variable frequency drive Operating modes Low flow and stop functions The pump will check the flow regularly by reducing the speed for a short time. If there is no or only a small change in pressure, this means that there is low flow. The speed will be increased until the stop pressure (actual setpoint + 0.5 x ΔH) is reached and the pump will stop after a few moments. The pump will restart at the latest when the pressure has fallen to the start pressure (actual setpoint - 0.5 x ΔH). SQ, SQE, SQE-NE, CU331SP 11 Operating conditions for the stop function It is only possible to use the stop function if the system incorporates a pressure sensor, a non-return valve and a diaphragm tank. The non-return valve must always be installed before the pressure sensor. Diaphragm tank Pressure sensor CU331SP variable frequency drive Automatic setting The CU331SP automatically tests and sets the correct direction of rotation without changing the cable connections. Automatic setting requires a sensor. This test is not suitable for all pump types and will in certain cases not be able to determine for certainty the correct direction of rotation. In these cases, the CU331SP changes over to manual setting where the direction of rotation is determined on the basis of the installer’s observations. Manual setting when the direction of rotation is not visible The correct direction of rotation is set manually without changing the cable connections. This requires that it is possible to observe the head or flow rate. Status functions TM05 5804 4012 Pump with non return valve Fig. 26 Position of the pressure sensor and diaphragm tank Diaphragm tank The stop function requires a diaphragm tank of a certain minimum size. The tank must be installed as close as possible after the pump and the precharge pressure must be 0.7 x actual setpoint. Recommended diaphragm tank size: Rated flow of pump [gpm (m3/h)] Typical diaphragm tank size [gal (l)] 0-26 (0-6) 27-105 (7-24) 2 (7.5) 4 (15.1) If a diaphragm tank of the above size is installed in the system, the factory setting of ΔH is the correct setting. If the tank installed is too small, the pump will start and stop too often. The CU331SP shows the following data: • power consumption • operating hours • measured value • speed • input power • motor current. The status information can be shown in the display. Power consumption The value of the power consumption is an accumulated value calculated from the pump’s startup date and cannot be reset. No additional sensor is required. Operating hours The value of operating hours is an accumulated value calculated from the pump’s startup date and cannot be reset. No additional sensor is required. Measured value Sensor display will show the actual pressure as received from the pressure transducer. Speed Display will show the motor speed in RPM's (calculated). Input power Setting the direction of rotation The start-up guide is started the first time the CU331SP is connected to supply voltage. Then while going through the start-up guide, the CU331SP tests and sets the correct direction of rotation without changing the cable connections to the motor. The correct direction of rotation can be set in these ways: • automatic setting. • manual setting when the direction of rotation is not visible. Display will show the power consumption in kW. Motor current Display will show the actual motor current being used. Logging functions Alarm and warning log The latest five alarms and five warnings are logged with a timestamp corresponding to the power-on time after the fault has occurred. The alarm and warning log can be shown directly on the display. See section Warning and alarm list. 43 SQ, SQE, SQE-NE, CU331SP 11 CU331SP variable frequency drive Signal relays The table shows the function of the signal relays. Type Function Relay 1 • Pump running Relay 2 • Alarm Accessory bag Fig. 27 Terminals for signal relays (normal state, not activated) Terminal C1 NO 1 NC1 Function C2 NO 2 NC2 Common Normally open contact Normally closed contact CU331SP installation Mechanical installation TM05 5990 4012 TM03 8801 3407 See also fig. 27. Fig. 28 CU331SP packaging Space requirements and air circulation CU331SP units can be mounted side by side, but as a sufficient air circulation is required for cooling these requirements must be met: • Sufficient free space above and below the CU331SP • Ambient temperature up to 122°F (50 °C) • Hang the CU331SP directly on the wall, or fit it with a back plate. See fig. 29. The individual CU331SP cabinet sizes are characterized by their enclosures. The table in section CU331SP technical data shows the relationship of enclosure class and enclosure type. Reception and storage Transportation and unpacking The CU331SP must only be unpacked at the installation site to prevent damage during the transport to the site. The packaging contains accessory bag(s), documentation and the unit itself. See fig. 28. TM03 8859 2607 Check on receipt that the packaging is intact, and the unit is complete. In case of damage during transport, contact the transport company to file a claim. Note that the CU331SP is delivered in a packaging which is not suitable for outdoor storage. Fig. 29 CU331SP hung directly on the wall or fitted with a back plate Required free space above and below the CU331SP: Enclosure Space [in (mm)] B1 7.9 (200) For information about enclosure, see section Enclosure. Mounting The CU331SP must be mounted securely on a firm surface. Ensure that screws are sized appropriately for the weight of the CU331SP (approximately 60 lbs) and anchored securely to the mounting surface. 1. Mark and drill holes. See fig. 30; also see section Main dimensions and weight. 2. Fit the screws, but leave loose. Mount the CU331SP, and tighten the four screws. 44 SQ, SQE, SQE-NE, CU331SP 11 a a Fig. 30 Drilling holes for mounting Motor protection TM03 8860 2607 b CU331SP variable frequency drive The total leakage current of all the electrical equipment in the installation must be taken into account. During start and in asymmetrical supply systems, the leakage current can be higher than normal and may cause the ELCB to trip. b The motor requires no external motor protection. The CU331SP protects the motor against thermal overloading and blocking. Protection against overcurrent The CU331SP has an internal overcurrent protection for overload protection on the motor output. Protection against mains voltage transients CU331SP electrical connection Ensure the correct grounding and protection procedures are used for the installation. Before the electrical installation, ensure that the power supply and other voltage inputs are switched off. Electrical protection Protection against electric shock, indirect contact The leakage current to ground exceeds 3.5 mA, and a reinforced ground connection is required. Protective conductors must always have a yellow/ green (PE) or yellow/green/blue (PEN) color marking. Instructions according to EN IEC 61800-5-1: • The CU331SP must be stationary, installed permanently and connected permanently to the mains supply. • The ground connection must be carried out with duplicate protective conductors or with a single reinforced protective conductor with a cross-section of minimum AWG 7 (10 mm2). The CU331SP is protected against mains voltage transients according to EN 61800-3, second environment. Mains and motor connection The supply voltage and frequency are marked on the CU331SP nameplate. Make sure that the CU331SP is suitable for the power supply of the installation site. The maximum output voltage of the CU331SP is equal to the input. Example: if the supply voltage is rated at 208V choose a 208V motor for operation. Mains switch A mains switch can be installed before the CU331SP according to local regulations. See fig. 32. Wiring diagram The wires in the terminal box must be as short as possible. Excepted from this is the ground wire, which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry. The CU331SP and the supply system must be protected against short-circuit. Grundfos requires that the back-up fuses are used for protection against short-circuit. The CU331SP offers complete short-circuit protection in case of a short-circuit on the motor output. TM05 5867 3912 Protection against short-circuit, fuses Fig. 32 CU331SP wiring diagram Additional protection The leakage current to ground exceeds 3.5 mA. If the CU331SP is connected to an electrical installation where an earth leakage circuit breaker (ELCB) is used as additional protection, the circuit breaker must be of a type marked with the following symbols: Terminal 91 (L1) 92 (L2) 95/99 (PE) Function Single-phase supply Ground connection For single-phase connection, use L1 and L2. ELCB Fig. 31 Circuit breaker type B 45 SQ, SQE, SQE-NE, CU331SP 11 CU331SP variable frequency drive Mains connection Check that mains voltage and frequency correspond to the values on the nameplate of the CU331SP and the motor. 1. Connect the ground wire to terminal 95 (PE). See fig. 33. 2. Connect the power leads to the terminals 91 (L1), 92 (L2). 3. Fix the mains cable with a cable clamp. The cable screen must be exposed and in physical contact with the mounting plate and clamp 11.1 Connecting the signal terminals As a precaution, signal cables must be separated from other groups by reinforced insulation in their entire lengths. If no external on/off switch is connected, short-circuit terminals 18 and 20 using a short wire. Connect the signal cables according to the guidelines for good practice to ensure EMC-correct installation. See section EMC-correct installation. • Use screened signal cables with a conductor crosssection of min. AWG 20 (0.5 mm2) and max. AWG 16 (1.5 mm2). • Use a 3-conductor screened bus cable in new systems. Minimum connection, signal terminal CU331SP drive is usable with 3-phase input power by connecting leads to 91 (L1), 92 (L2), and 93 (L3). Motor connection The motor cable must be screened for the CU331SP to meet EMC requirements. TM03 9020 2807 1. Connect the ground wire to terminal 99 (PE). See fig. 34. 2. Connect the motor leads to the terminals 96 (U), 97 (V), 98 (W). 3. Fix the screened cable with a cable clamp. Fig. 34 Motor connection 46 Jumper wire Fig. 35 Required minimum connection, signal terminal TM03 9057 3207 Fig. 33 Mains connection GND Start/stop Operation is only possible when the terminals 18 and 20 are connected, for instance by means of an external on/off switch or a short wire. SQ, SQE, SQE-NE, CU331SP Terminal key 0/4-20 mA RS-485 A Terminals Sensor 1 Terminal Type Function 12 +24 V out Supply to sensor 18 DI 1 Digital input, start/stop 20 GND Common frame for digital inputs 55 GND Common frame for analog inputs 54 AI 2 Sensor input, sensor 1, 0/4-20 mA 61 RS-485 GND Y GENIbus, frame 68 RS-485 A GENIbus, signal A (+) 69 RS-485 B GENIbus, signal B (-) The RS-485 screen must be connected to frame. Access to signal terminals All signal terminals are behind the terminal cover of the CU331SP front. Remove the terminal cover as shown in fig. 39. TM05 5802 3913 GND Start/stop +24 V out GND Switch position must be changed to "I" prior to startup RS-485 B RS-485 GND Y CU331SP variable frequency drive 11 Jumper wire TM03 9004 2807 TM05 6776 5112 Fig. 36 Wiring diagram for CU331SP Fig. 39 Access to signal terminals Fig. 37 Sensor wiring diagram Setting the analog input 54 The contact A54 is positioned behind the control panel and is used for setting the signal type of the analog input. The factory setting of the inputs is voltage signal "U". This setting must be changed to "I" prior to starting the CU331SP. Be sure the power supply is switched off. TM03 9025 2807 Remove the control panel to set the contact. See fig. 38. A54 U I TM05 5803 3912 Fig. 40 Signal terminals Fig. 38 Setting contact A54 to current signal "I" 47 SQ, SQE, SQE-NE, CU331SP 11 Fig. 41 Fitting the conductor into the signal terminal TM03 8801 2507 C2 NC 2 NO 2 C1 NC 1 As a precaution, signal cables must be separated from other groups by reinforced insulation in their entire lengths. NO 1 Connecting the signal relays 1. Remove the insulation at a length of 0.35 to 0.40 inches (9 to 10 mm). 2. Insert a screwdriver with a tip of maximum 0.015 X 0.1 in (0.4 X 2.5 mm) into the square hole. 3. Insert the conductor into the corresponding round hole. Remove the screwdriver. The conductor is now fixed in the terminal. TM03 9026 2807 CU331SP variable frequency drive Fitting the conductor Fig. 42 Terminals for signal relays (normal state, not activated) Terminal C1 NO 1 NC 1 C2 NO 2 NC 2 Function Common Normally open contact Normally closed contact Signal relay TM03 9008 2807 The signal relays on the CU331SP are predefined as follows: Relay 1: Pump running Relay 2: Alarm Fig. 43 Terminals for relay connection 48 SQ, SQE, SQE-NE, CU331SP EMC-correct installation RFI filters This section gives guidelines for good practice when installing the CU331SP. Follow these guidelines to meet EN 61800-3, first environment. • Use only motor and signal cables with a braided metal screen in applications without output filter. • There are no special requirements to supply cables, apart from local requirements. • Leave the screen as close to the connecting terminals as possible. See fig. 44. • Avoid terminating the screen by twisting the ends. See fig. 45. Use cable clamps or EMC screwed cable entries instead. • Connect the screen to frame at both ends for both motor and signal cables. If the controller has no cable clamps, connect only the screen to the CU331SP. • Avoid unscreened motor and signal cables in electrical cabinets with variable frequency drives. • Make the motor cable as short as possible in applications without output filter to limit the noise level and minimize leakage currents. • Screws for frame connections must always be tightened whether a cable is connected or not. • Keep main cables, motor cables and signal cables separated in the installation, if possible. Other installation methods may give similar EMC results if the above guidelines for good practice are followed. To meet the EMC requirements, the CU331SP comes with the following types of built-in radio frequency interference filter (RFI). Voltage Typical shaft power P2 RFI filter type 1 x 200-240 V * 1.5 - 10 hp C1 *Single-phase input - three-phase output. Description of RFI filter types C1: For use in domestic areas. RFI filter types are according to EN61800-3 Control panel The on/off button on the control panel does not disconnect the CU331SP from the power supply and must therefore not be used as a safety switch. The On/Off button has the highest priority. In "Off" condition, pump operation is not possible. On/ Off The control panel is used for local setting of the CU331SP. The functions available are preset in the CU331SP. TM02 1325 0901 CUE CU On/ Off > On OK Off > - > Alarm + Fig. 45 Do not twist the screen ends TM03 8719 2507 > Fig. 44 Example of stripped cable with screen TM03 8812 2507 CU331SP variable frequency drive 11 Fig. 46 Control panel of the CU331SP Line disturbance and transient protection To protect itself from AC line voltage disturbances, the CU331SP monitors the input power supply and interrupts drive operation in the event of phase loss or imbalance. Transients on the AC line are suppressed by MOVs as well as zener diodes for extreme transients. The CU331SP meets VDE 0160 (European standard - 2.3 x line voltage for 1.3 msec) for transient protection. Editing buttons Button Function On/ Off Makes the pump ready for operation/starts and stops the pump. OK Saves changed values, resets alarms and expands the value field. + - Changes values in the value field. 49 SQ, SQE, SQE-NE, CU331SP 11 CU331SP variable frequency drive Navigating buttons Button > > > > Function Displays, general terms Figures 47 and 48 show the general terms of the display. Navigates from one menu to another. When the menu is changed, the display shown will always be the top display of the new menu. Display name Navigates up and down in the individual menu. Value field Adjusting the display contrast Press OK and + for darker display. Press OK and - for brighter display. Current display / total number Button lock Fig. 47 Example of display in the start-up guide To lock the buttons on the panel press and hold the up and down arrows simultaneously. Indicator lights Display name The operating condition of the pump is indicated by the indicator lights on the front of the control panel. See fig. 46. The table shows the function of the indicator lights. Value field Display number, menu name The pump is running or has been stopped by a stop function. Off (orange) The pump has been stopped with the on/off button. Alarm (red) Indicates an alarm or a warning. Fig. 48 Example of display in the user menu Warning and alarm list Status Code and display text ● Operating Resetting mode 1 Too high leakage current 2 Mains phase failure ● Stop Aut. 3 External fault ● Stop Man. ● 16 Other fault 32 Overvoltage 40 Undervoltage ● ● Man. Stop Aut. Stop Man. - Aut. Stop Aut. - Aut. ● Stop Aut. ● ● 49 Overload Stop ● ● 48 Overload ● ● Stop Aut. Stop Man. Stop Aut. - Aut. ● Stop Aut. 57 Dry running ● Stop Aut. Too high CU331SP 64 temperature ● Stop Aut. ● 1) Aut. ● 1) Aut. ● Stop Aut. 55 Overload 89 Sensor 1 outside range Setpoint signal outside 96 range 155 Inrush fault 241 Motor phase failure 50 Locked alarm If flashing, the pump has been stopped by the user (CU331SP menu), external start/stop or bus. Alarm On (green) Function Warning Indicator light ● ● - Aut. Stop Aut. 1) In case of an alarm, the CU331SP will change the operating mode depending on the pump type. 2) Warning is reset in display 3.20. SQ, SQE, SQE-NE, CU331SP 11 CU331SP technical data CU331SP variable frequency drive Terminal tightening torques Tightening torque [ft-lb] Enclosure Enclosure All CU331SP enclosures are size B1. The enclosure rating can be either IP 55 / TYPE 12 or IP 66 / TYPE 4X. Main dimensions and weight B1 Mains Motor Earth Relay 1.3 1.3 2.2 0.4 Cable length Maximum length, screened motor cable 500 ft (152 m) Maximum length, unscreened motor cable 1000 ft (305 m) Maximum length, signal cable 1000 ft (305 m) Fuses and cable cross-section Always comply with national and local regulations as to cable cross-sections. TM03 9002 2807 Cable cross-section to signal terminals Maximum cable cross-section to signal terminals, rigid conductor AWG 14 Maximum cable cross-section to signal terminals, flexible conductor AWG 18 Minimum cable cross-section to signal terminals AWG 20 Non-UL fuses and conductor crosssection to mains and motor Fig. 49 Enclosure B1 1) The dimensions are maximum height, width and depth. Enclosure Height [in] Width [in] A a B b C 17.9 9.5 8.3 10.2 Screw holes [in] c d e f Weight [lbs] 0.47 0.75 0.35 0.35 50.7 2 3 5 40 40 80 gG gG gG 1) Maximum conductor cross section1 [AWG] [mm2] 7 7 7 10 10 10 Screened motor cable, unscreened supply cable. UL fuses and conductor cross-section to mains and motor 5-95 % RH Ambient temperature Max. 122 °F (50 °C) Average ambient temperature over 24 hours Max. 113 °F (45 °C) Minimum ambient temperature at full operation 32 °F (0 °C) Minimum ambient temperature at reduced operation 14 °F (-10 °C) Temperature during storage and transportation -13 to 150 °F (-25 to 65 °C) Storage duration Fuse type Typical shaft Maximum Bussmann power P2 fuse size RK1 Surroundings Relative humidity Maximum fuse size [A] Depth [in] 18.9 B1 Typical shaft power P2 [Hp] Max. 6 months Maximum altitude above sea level without performance reduction 3280 ft (1000 m) Maximum altitude above sea level with performance reduction 9840 ft (3000 m) The CU331SP comes in a packaging which is not suitable for outdoor storage. 1) [Hp] [A] 2 3 5 40 40 80 Maximum conductor cross section1 [AWG} KTN-R40 KTN-R40 KTN-R80 7 7 7 Screened motor cable, unscreened supply cable. Inputs and outputs Mains supply (L1, L2) Supply voltage 200-240 V ± 10 % Supply frequency 60 Hz Maximum temporary imbalance between phases 3 % of rated value Leakage current to earth > 3.5 mA Number of cut-ins Max. 1 time/min. Do not use the power supply for switching the CU331SP on and off. 51 SQ, SQE, SQE-NE, CU331SP 11 CU331SP variable frequency drive Motor output (U, V, W) Analog input 0-100 % 1) Output voltage Output frequency Switching on output 1) Not recommended Current range 0-20, 4-20 mA Input resistance, Ri Maximum current Approx. 200 Ω RS-485 GENIbus connection Maximum fault, terminals 53, 54 68 (A), 69 (B), 61 GND (Y) 1) 30 mA 0.5 % of full scale The factory setting is voltage signal "U". The RS-485 circuit is functionally separated from other central circuits and galvanically separated from the supply voltage (PELV). All analog inputs are galvanically separated from the supply voltage (PELV) and other high-voltage terminals. Digital inputs Sound pressure level Terminal number 18 Voltage level 0-24 VDC Voltage level, open contact > 19 VDC Voltage level, closed contact < 14 VDC Maximum voltage on input Input resistance, Ri 28 VDC Approx. 4 kΩ All digital inputs are galvanically separated from the supply voltage (PELV) and other high-voltage terminals. Signal relays Relay 01, terminal number 1 (C), 2 (NO), 3 (NC) Relay 02, terminal number 4 (C), 5 (NO), 6 (NC) Maximum terminal load (AC-1) 1) Maximum terminal load (AC-15) 1) Maximum terminal load (DC-1) 1) Minimum terminal load 1) C 240 VAC, 2 A 240 VAC, 0.2 A 50 VDC, 1 A 24 V DC 10 mA 24 V AC 20 mA IEC 60947, parts 4 and 5. Common NO Normally open NC Normally closed The relay contacts are galvanically separated from other circuits by reinforced insulation (PELV). 52 54 A54 = "I" 1) Current signal Output voltage in % of supply voltage. Terminal number Terminal number 0-60 Hz The sound pressure of the CU331SP is maximum 70 dB(A). The sound pressure level of a motor controlled by a Variable frequency drive may be higher than that of a corresponding motor which is not controlled by a variable frequency drive. SQ, SQE, SQE-NE, CU331SP 11 280 260 240 220 200 180 160 140 120 100 80 60 40 20 0 55 Hz 40 Hz 30 Hz 600 160 1 2 3 4 0.5 5 6 7 Q [US GPM] 1.0 Q [m³/h] 60 Hz 55 Hz 700 650 180 600 50 Hz 550 45 Hz 500 140 450 120 400 40 Hz 350 35 Hz 300 80 250 60 200 0 30 Hz 150 100 50 0 0 120 400 2 3 0.5 4 5 6 1.0 7 8 9 10 Q [US GPM] 1.5 Q [m³/h] H [ft] 550 16S20-18 60 Hz 160 500 55 Hz 50 Hz 140 450 120 400 55 Hz 50 Hz 500 450 1 0.0 10S20-27 7S20-32 60 Hz 750 200 H [m] 550 140 100 800 20 700 180 240 40 750 650 850 100 35 Hz H [ft] 200 260 160 45 Hz 0.0 220 H [ft] 900 220 50 Hz 0 H [m] 5S20-39ds 60 Hz H [m] TM05 6411 5012 300 H [ft] 1050 1000 950 900 850 800 750 700 650 600 550 500 450 400 350 300 250 200 150 100 50 0 TM05 6410 5012 H [m] 320 CU331SP variable frequency drive CU331SP curve charts 350 100 45 Hz 45 Hz 300 350 40 Hz 80 35 Hz 60 250 40 Hz 200 35 Hz 150 30 Hz 300 250 60 200 40 30 Hz 40 150 100 100 0 20 50 0 0 0 2 4 1 6 8 10 12 14 Q [US GPM] 2 Q [m³/h] TM05 6412 5012 20 0 50 0 0 0 2 4 1 6 8 10 12 14 16 18 20 22 Q [US GPM] 2 3 Q [m³/h] TM05 6413 5012 80 53 SQ, SQE, SQE-NE, CU331SP 11 90 340 70 60 60 320 55 300 50 55 Hz 280 80 25S20-11 60 Hz 260 45 240 40 220 35 45 Hz 180 50 40 30 160 40 Hz 140 120 20 10 H [ft] 40 130 80 70 35 Hz 5 4 6 Q [m³/h] TM05 6414 5012 2 12 16 20 24 28 32 36 Q [US GPM] 120 H [ft] 30 100 4 6 8 10 Q [m³/h] 75S20-3 60 Hz 55 Hz 80 70 50 Hz 60 45 Hz 70 15 40 Hz 50 50 40 Hz 40 35 Hz 10 30 Hz 35 Hz 30 30 Hz 30 20 5 20 10 0 10 20 30 40 50 60 70 80 90 Q [US GPM] 5 10 15 Q [m³/h] TM05 6416 5012 0 0 54 2 20 80 10 0 5 10 15 20 25 30 35 40 45 50 55 60 Q [US GPM] 50 Hz 40 5 0 H [m] 25 60 10 10 0 45 Hz 15 20 90 100 90 20 30 Hz 0 55 Hz 110 60 0 60S20-4 60 Hz 35 25 40 Hz 25 40 30 0 30 100 90 10 8 45 Hz 110 50 4 50 Hz 130 120 15 0 H [m] 150 30 Hz 40 0 55 Hz 160 20 20 0 180 170 35 Hz 60 40S20-7 190 30 100 80 60 Hz 140 50 Hz 200 H [ft] 200 TM05 6415 5012 100 H [m] H [ft] 0 0 0 0 10 20 30 40 50 60 70 80 90 100 Q [US GPM] 5 10 15 Q [m³/h] TM05 6417 5012 CU331SP variable frequency drive H [m] SQ, SQE, SQE-NE, CU331SP 1300 5S30-48ds 60 Hz 300 280 1200 350 1100 300 55 Hz 1000 50 Hz 250 200 800 700 40 Hz 500 0 300 35 Hz 30 Hz 80 250 30 Hz 60 200 150 40 0 1 2 0.5 4 5 6 7 Q [US GPM] 1.0 Q [m³/h] 400 60 40 55 Hz 120 50 Hz 100 45 Hz 80 8 1 10 12 14 Q [US GPM] 2 Q [m³/h] H [ft] 25S30-15 60 Hz 400 55 Hz 50 Hz 320 280 45 Hz 240 350 40 Hz 60 35 Hz 250 200 40 30 Hz 150 20 40 Hz 200 160 35 Hz 120 30 Hz 80 40 50 0 0 0 2 4 1 6 8 10 12 14 16 18 20 22 Q [US GPM] 2 3 Q [m³/h] TM05 6420 5012 0 6 360 100 20 4 480 300 80 2 440 500 120 0 140 550 450 50 0 16S30-24 60 Hz 100 0 H [m] 700 140 100 3 H [ft] 600 40 Hz 350 300 0 180 160 140 20 650 45 Hz 550 500 450 100 200 50 Hz 650 600 100 200 750 700 120 0.0 220 750 35 Hz 0 H [m] 55 Hz 400 TM05 6418 5012 50 800 160 400 100 240 180 45 Hz 600 150 900 850 200 10S30-34 60 Hz 950 260 220 900 H [ft] 1000 CU331SP variable frequency drive 400 H [m] TM05 6419 5012 H [ft] 0 0 0 0 4 8 2 12 16 20 24 28 32 36 Q [US GPM] 4 6 Q [m³/h] TM05 6421 5012 H [m] 11 55 SQ, SQE, SQE-NE, CU331SP 11 80 260 H [m] 40S30-9 60 Hz 50 240 45 70 220 60 55 Hz 50 200 50 Hz 35 160 30 45 Hz 40 25 40 Hz 20 100 35 Hz 80 20 10 15 30 Hz 10 40 5 20 0 0 H [m] 50 45 35 30 20 15 170 5 4 6 8 10 Q [m³/h] 100 45 Hz 80 40 Hz 70 60 35 Hz 50 30 Hz 30 20 0 400 130 120 300 50 Hz 110 5 10 15 Q [m³/h] 10S50-48ds 60 Hz 1300 1200 350 55 Hz 10 20 30 40 50 60 70 80 90 Q [US GPM] H [ft] 1400 150 55 Hz 1100 1000 50 Hz 900 100 250 45 Hz 80 200 40 Hz 70 60 800 45 Hz 700 40 Hz 600 150 35 Hz 50 500 35 Hz 400 30 Hz 100 30 50 20 30 Hz 300 200 100 0 10 20 30 40 50 60 70 80 90 100 Q [US GPM] 5 10 15 Q [m³/h] TM05 6424 5012 0 0 56 50 Hz 110 0 10 0 120 0 75S30-5 60 Hz 160 40 10 2 0 H [m] 90 25 5 10 15 20 25 30 35 40 45 50 55 60 Q [US GPM] H [ft] 140 40 55 Hz 130 10 0 TM05 6422 5012 0 150 40 60 60S30-5 60 Hz 160 90 140 120 30 170 140 40 180 H [ft] TM05 6423 5012 H [ft] 0 0 0 0 2 4 1 6 8 10 12 14 Q [US GPM] 2 Q [m³/h] TM05 6425 5012 CU331SP variable frequency drive H [m] SQ, SQE, SQE-NE, CU331SP 350 300 200 150 55 Hz 300 1300 50 50 Hz 250 1100 1000 45 Hz 200 800 150 600 35 Hz 500 100 30 Hz 300 50 200 2 4 0 800 220 180 600 2 Q [m³/h] 120 400 55 Hz 60 200 90 80 70 45 Hz 60 35 Hz 300 30 Hz 200 0 2 4 H [ft] 360 6 8 10 12 14 16 18 20 22 Q [US GPM] 1 2 3 40S50-12 60 Hz 340 Q [m³/h] 320 300 55 Hz 260 50 Hz 240 220 200 45 Hz 180 50 40 Hz 40 35 Hz 30 30 Hz 20 150 10 0 0 4 8 2 12 16 20 24 28 32 36 Q [US GPM] 4 6 Q [m³/h] TM05 6428 5012 50 0 160 40 Hz 140 35 Hz 120 100 30 Hz 80 100 0 400 0 50 Hz 300 250 40 Hz 500 280 350 80 45 Hz 0 100 500 450 20 0 H [m] 110 25S50-26 60 Hz 550 140 40 1 10 12 14 Q [US GPM] 700 650 100 8 750 200 160 6 TM05 6426 5012 0 240 700 100 0 H [ft] 50 Hz 800 40 Hz 700 H [m] 55 Hz 600 100 0 1000 900 1200 400 100 60 Hz 1100 1500 900 250 16S50-38 1200 350 1400 400 10S50-58 60 Hz 1600 CU331SP variable frequency drive 450 1700 H [ft] TM05 6427 5012 500 H [m] H [ft] 0 60 40 20 0 0 0 5 10 15 20 25 30 35 40 45 50 55 60 Q [US GPM] 2 4 6 8 10 Q [m³/h] TM05 6429 5012 H [m] 11 57 SQ, SQE, SQE-NE, CU331SP 11 110 100 90 80 70 60 50 40 30 20 10 0 55 Hz 60 90 300 50 45 Hz 40 70 60 40 30 35 Hz 20 30 Hz 10 5 10 15 20 25 30 35 40 45 50 55 60 Q [US GPM] 2 4 6 8 10 Q [m³/h] 60S50-9 60 Hz 10 0 80 35 Hz 60 30 Hz 40 0 10 20 30 40 50 60 70 80 90 Q [US GPM] 0 H [m] H [ft] 80 260 5 10 15 Q [m³/h] 75S50-8 60 Hz 70 55 Hz 60 220 50 Hz 200 55 Hz 220 240 200 50 Hz 180 50 160 45 Hz 45 Hz 160 40 140 30 35 Hz 100 140 120 40 Hz 40 Hz 100 35 Hz 80 30 Hz 20 60 40 10 30 Hz 60 40 20 0 10 20 30 40 50 60 70 80 90 Q [US GPM] 5 10 15 Q [m³/h] TM05 6432 5012 0 0 58 40 Hz 100 0 20 0 45 Hz 240 260 80 20 140 20 120 30 50 Hz 160 40 Hz 180 50 55 Hz 120 280 80 200 180 50 Hz 0 H [ft] 60S50-7 60 Hz 220 0 H [m] 240 70 TM05 6431 5012 120 40S50-15 60 Hz H [ft] 0 0 0 0 10 20 30 40 50 60 70 80 90 100 Q [US GPM] 5 10 15 Q [m³/h] TM05 6433 5012 130 H [m] H [ft] 440 420 400 380 360 340 320 300 280 260 240 220 200 180 160 140 120 100 80 60 40 20 0 TM05 6430 5012 CU331SP variable frequency drive H [m] SQ, SQE, SQE-NE, CU331SP 12 Accessories 12. Accessories CU331SP Constant Pressure Drive Kits (with sensor) Enclosure type NEMA Indoor Type 12 Type 4X Input Ph Input volts Product number Approx. ship wt. [lbs] 2 1 200 - 240 98370277 60 3 1 200 - 240 98370280 60 5 1 200 - 240 98370304 60 2 1 200 - 240 98370279 60 3 1 200 - 240 98370301 60 5 1 200 - 240 98370305 60 TM05 5801 4012 Outdoor Hp CU 301 Constant Pressure System Description Product number 96438895 TM04 7509 2110 Constant Pressure Kit (CU 301 and Transducer) CU 300 Status Box & R100 Description Product number CU300 Status Box 96422776 TM04 7508 2110 Description Product number R100 (for wireless infrared communication with the CU 301 / CU 300) 96615297 SQ, SQE flow sleeves Description 100 ø90 max. ø100 210 250 50 550 50 Product number 98148594 TM01 3292 3798 SQ, SQE flow sleeve, complete 88 650 59 SQ, SQE, SQE-NE, CU331SP 13 Further product documentation 13. Further product documentation WebCAPS WebCAPS is a Web-based Computer Aided Product Selection program available on www.grundfos.com. WebCAPS contains detailed information on more than 185,000 Grundfos products in more than 20 languages. In WebCAPS, all information is divided into 6 sections: • Catalog • Literature • Service • Sizing • Replacement • CAD drawings. Catalog This section is based on fields of application and pump types, and contains • technical data • curves (QH, Eta, P1, P2, etc) which can be adapted to the density and viscosity of the pumped liquid and show the number of pumps in operation • product photos • dimensional drawings • wiring diagrams • quotation texts, etc. Literature In this section you can access all the latest documents of a given pump, such as • product guides • installation and operating instructions • service documentation, such as Service kit catalog and Service kit instructions • quick guides • product brochures, etc. Service This section contains an easy-to-use interactive service catalog. Here you can find and identify service parts of both existing and discontinued Grundfos pumps. Furthermore, this section contains service videos showing you how to replace service parts. 60 SQ, SQE, SQE-NE, CU331SP Sizing 0 Further product documentation 13 1 This section is based on different fields of application and installation examples, and gives easy step-by-step instructions in how to • select the most suitable and efficient pump for your installation • carry out advanced calculations based on energy consumption, payback periods, load profiles, life cycle costs, etc. • analyse your selected pump via the built-in life cycle cost tool • determine the flow velocity in wastewater applications, etc. Replacement In this section you find a guide to selecting and comparing replacement data of an installed pump in order to replace the pump with a more efficient Grundfos pump. The section contains replacement data of a wide range of pumps produced by other manufacturers than Grundfos. Based on an easy step-by-step guide, you can compare Grundfos pumps with the one you have installed on your site. When you have specified the installed pump, the guide will suggest a number of Grundfos pumps which can improve both comfort and efficiency. CAD drawings In this section it is possible to download 2-dimensional (2D) and 3-dimensional (3D) CAD drawings of most Grundfos pumps. These formats are available in WebCAPS: 2-dimensional drawings: • .dxf, wireframe drawings • .dwg, wireframe drawings. 3-dimensional drawings: • .dwg, wireframe drawings (without surfaces) • .stp, solid drawings (with surfaces) • .eprt, E-drawings. WinCAPS WinCAPS is a Windows-based Computer Aided Product Selection program containing detailed information on more than 185,000 Grundfos products in more than 20 languages. The program contains the same features and functions as WebCAPS, but is an ideal solution if no Internet connection is available. WinCAPS is available on CD-ROM and updated once a year. Fig. 50 WinCAPS CD-ROM 61 62 63 © Copyright Grundfos Holding A/S 98440904 0313 ECM: - GRUNDFOS Pumps Corporation 17100 West 118th Terrace Olathe, Kansas 66061 Phone: +1-913-227-3400 Telefax: +1-913-227-3500 GRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Canada Phone: +1-905 829 9533 Telefax: +1-905 829 9512 Bombas GRUNDFOS de Mexico S.A. de C.V. Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto Apodaca, N.L. Mexico 66600 Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010 The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. L-SQ-PG-001
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes Create Date : 2013:03:01 16:26:06Z Creator : FrameMaker 10.0 Modify Date : 2013:03:01 16:31:31+01:00 Language : en XMP Toolkit : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26 Format : application/pdf Title : untitled Creator Tool : FrameMaker 10.0 Metadata Date : 2013:03:01 16:31:31+01:00 Producer : Acrobat Distiller 10.0.0 (Windows) Document ID : uuid:19d655b1-ffe8-4cd2-abed-230fb4e3bb1b Instance ID : uuid:c51af276-0262-4b0a-afb5-b11c27332a98 Page Mode : UseOutlines Page Count : 64EXIF Metadata provided by EXIF.tools