RDI Technology XASC04 Artemis Ceiling Mounted LED Stairwell Fixture User Manual

RDI Technology (Shenzhen) Co., Ltd. Artemis Ceiling Mounted LED Stairwell Fixture

User Manual

ArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuideXeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.com1LowOccupancyFixture XLStairwellFixtureXSBasicFixtureXB
Pleasereadtheseinstructionscarefully,andkeepthemforfuturereference.2XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comIMPORTANT SAFEGUARDSWhen using electrical equipment, basic safety precautions should always be followed including the following:a) READ AND FOLLOW ALL SAFETY INSTRUCTIONS.b) Do not use outdoors.c) Do not let power supply cords touch hot surfaces.d) Do not mount near gas or electric heaters.e) Use caution when servicing batteries.  Battery acid can cause burns to skin and eyes.  If acid is spilled on skin or in eyes, flush acid with fresh water and contact a physician immediately.f) Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.g) The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.h) Do not use this equipment for other than intended use.SAVE THESE INSTRUCTIONSArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuide
PARTS&TOOLSREQUIRED:ArtemisStairwellFixture WireNutsFlatBladeScrewdriver(NotProvided)WARNING:Turnpoweroffatcircuitbreakerorfusebox.Donotrelyonawallswitchalonetoturnoffpower.Failuretodosomaycauseashockhazardanddamagethiselectronicfixture!3DrillandMasonryDrillBits(Notprovided)PhillipsScrewdriver(NotProvided)XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comAnchors&MountingHardware(NotProvided)Note:Ensurecompliancewithlocalcodesandordinances.ArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuide
4StepDescription Image1Removethefixturefromthepackagingandmakesureithasarrivedingoodcondition.Placethefixtureonaflatsurfaceandremovetwoscrewswhichsecuretheback‐boxtothelightengine(locatedoneithersideofthefixtureinthemiddleandjustbehindthelens).2Useastraightslotscrewdriverandgentlyprythesheetmetalawayfromthelightengine.Thereisanotchdesignedintothebackboxforthispurpose.Thiswillreleasetheprimarylightenginefromthebackbox(white).3Carefullyremovetheprimarylightengineandsetitnexttothebackbox.Therearetwoconnectorsthatmustbedisconnected.Thelargerofthetwoconnectorsisforthemotionsensorarray.Thesmallerconnectorpowersthelightengine.4Afterremovingtheexistingfixturefromtheceiling,positionthenewbackboxwhereyouwantit.Usingtheprovidedopenings,securethebackboxtotheimbeddedjunctionbox(ifpoweriscominginfromthebackofthefixture).Checkthealignmentofthebackboxandthensecuretheendsofthefixtureusingtheprovidedholes.AnanchororTapconisrecommended,ensuringthatthisiscompliantwithlocalcodesandordinances.Note:Usewashersasspacersiftheceilingisnotflat.Notdoingsocanresultinawarpingofthebackbox,makingitdifficulttosnapintheprimarylightengine.5Ifinstallinganemergencyback‐upbattery,usaPhilipsscrewdrivertoremovethebatteryholdingfixtureclosesttothedriver.InstallationXeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuide4
StepDescription Image6Feedthebatteryconnectorthroughtheopeninginthebatteryholderyoujustremoved.Placetheotherendofthebatteryinthecorrespondingholder.UseaPhilipsheadscrewdriverandre‐installthebatteryholder.Plugthewhiteconnectorcomingoutofthebatteryintothemattingconnectorinsidethebackbox.7Ifpoweriscomingintothefixtureviaanelectricalconduit(flexorrigid),useoneoftheknockoutsateitherendofthefixture.Makesuretheproperstrainreliefsareusedtofullycomplywithlocalcodesorordinances.8Hookupthethreeincomingpowerwirestothethreewireswithinthebackbox.Usetheprovidedwirenutsorsimilarproductstoensurethesafetyoftheinstallation.9Holdthelightengineclosetothebackboxmountedtotheceilingandpluginthetwoconnectors(sensorarrayandpowerforthelightengine).10Snapthelightengineintothebackbox,beingverycarefulnottopinchanywires.Youmayneedtoprybackthemetalofthebackboxslightlytofacilitatethisstep.Oncethelightengineissnappedintothebackboxre‐installtothetwoscrewsintoeithersideofthefixture.5Note:Ifareplacementbatteryisneeded,thepartnumberisasfollows:XAP‐0039XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuideInstallation(cont.)
ControlPanelForStairwell(XS)FixturesFloorX1DialSwitch:Thisdialissettoindicatetheflooraparticularfixtureisbeinginstalledon.Ifthefixtureisbeinginstalledonthe4thfloor,thisdialwouldbesetto“4”.Ifthefixtureisbeinginstalledonthe23rdfloorthisdialwouldbesetto“3”,etc.StairwellDialSwitch:Somebuildingshavemorethanonestairwell.Thisswitchhelpstokeepfixturesinonestairwellfromtalkingtofixturesinanotherstairwell.Ifyouhaveonestairwell,useasmallstraightslotscrewdriverandsetthedialto“1”.Formultiplestairwellswithinabuilding,setthedialaccordingly.Timer:Oncethefixtureseesmotionwithinthestairwellitwillimmediatelyilluminatetofullintensity.Asmallscrewdriverisusedtoadjustthe“Timer”.ThisTimeradjuststhelengthoftimethatthefixtureremainsonatfullpowerpriortoreturningtothe“DIM”setting.TurningtheTimerallthewaytotheleft(counterclockwise)willkeepthefixtureonathighpowerforonly10‐seconds.TurningtheTimerallthewaytotheright(clockwise)willkeepthelightsonatfullpowerfor5‐minutesafterthesensorseesitslastmotion.Thetimecanalsobesetanywherebetween10‐secondsand5‐minutesbypositioningtheTimeraccordingly.StatusIndicatorLED:Thisisabi‐coloredLED(RedorGreen).ThisLEDprovidestheoperatorwiththecurrentsystemstatus.Seethetableonthenextpageforadetaileddescriptionofthevariousindications.Self‐Diagnostic:Periodicallyit’sagoodideafortheoperatorstopushtheSelf‐Diagnosticbuttontorunthebuilt‐intestingprogram.ResultsoftheSelf‐Diagnostictestarereportedonthe“DIAG”LEDIndicator.Seethetableonthenextpageforadetaileddescriptionoftheindications.Self‐DiagnosticStatusLED:Thisisabi‐coloredLEDs(RedorGreen).ThisLEDprovidetheoperatorwiththeself‐diagnosticteststatusandresults.Seethetableonthenextpageforadetaileddescriptionoftheindications.6FloorX10DialSwitch:Thisdialissettoindicatetheflooraparticularfixtureisbeinginstalledon.Ifthefixtureisbeinginstalledonfloors1‐ 9,thisdialwouldbesetto“0”.Ifthefixtureisbeinginstalledonfloors10– 19,thisdialwouldbesetto“1”.Ifitisbeinginstalledonfloors20– 29,thisdialwouldbesetto“2”,etc.EXAMPLE#1:Ifafixtureisbeinginstalledinthesecondstairwellofabuildingonthe17th floor,thedialindicatorswouldbesetlikethis:217.EXAMPLE#2:Ifafixtureisbeinginstalledinabuildingwithonlyonestairwellonthelandingbetweenfloors5and6,thedialindicatorswouldbesetlikethis:105.NOTE:Landingsbetweenfloorsshouldhavethesamedialsettingsasthefloorjustbelowit…i.e.Afixtureinstalledonalandingbetweenfloors2and3shouldhavethesamedialsettingsasthefixtureonfloor2.XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuideSTAIRWELLX10FLOORX1 DIMHILOWPOWERHILOW“DIM”Settingcontrolsthelightlevelwhenthestairwellisun‐occupied.“POWER”Settingcontrolsthelightlevelwhenthestairwellisoccupied.STAIRWELLX10FLOORX1TESTDIAG.STATUS
ControlPanelForLowOccupancy(XL)FixturesAreaX1DialSwitch:Thisdialissettoindicatethefloororareaaparticularfixtureisbeinginstalledon.Ifthefixtureisbeinginstalledonthe4thfloor,thisdialwouldbesetto“4”.Ifthefixtureisbeinginstalledonthe23rdfloorthisdialwouldbesetto“3”,etc.ZoneDialSwitch:Somefacilitieshavemorethanonebuildingorareastoilluminate.Thisswitchhelpstokeepfixturesinonebuildingorareafromtalkingtofixturesinadjoiningbuildingsorareas.Ifyou’reonlyilluminatingonearea,useasmallstraightslotscrewdriverandsetthedialto“1”.Formultiplebuildingsorareassetthedialaccordingly.Timer:Oncethefixtureseesmotionwithinanareaitwillimmediatelyilluminatetofullintensity.Asmallscrewdriverisusedtoadjustthe“Timer”.ThisTimeradjuststhelengthoftimethatthefixtureremainsonatfullpowerpriortoreturningtothe“DIM”setting.TurningtheTimerallthewaytotheleft(counterclockwise)willkeepthefixtureonathighpowerforonly10‐seconds.TurningtheTimerallthewaytotheright(clockwise)willkeepthelightsonatfullpowerfor5‐minutesafterthesensorseesitslastmotion.Thetimecanalsobesetanywherebetween5‐secondsand10‐minutesbypositioningtheTimeraccordingly.StatusIndicatorLED:Thisisabi‐coloredLED(RedorGreen).ThisLEDprovidestheoperatorwiththecurrentsystemstatus.Seethetableonthenextpageforadetaileddescriptionofthevariousindications.Self‐Diagnostic:Periodicallyit’sagoodideafortheoperatorstopushtheSelf‐Diagnosticbuttontorunthebuilt‐intestingprogram.ResultsoftheSelf‐Diagnostictestarereportedonthe“DIAG”LEDIndicator.Seethetableonthenextpageforadetaileddescriptionoftheindications.Self‐DiagnosticStatusLED:Thisisabi‐coloredLEDs(RedorGreen).ThisLEDprovidetheoperatorwiththeself‐diagnosticteststatusandresults.Seethetableonthenextpageforadetaileddescriptionoftheindications.7AreaX10DialSwitch:Thisdialissettoindicatethefloororareaaparticularfixtureisbeinginstalledon.Ifthefixturesarebeinginstalledonfloors1‐ 9,thisdialwouldbesetto“0”.Ifthefixtureisbeinginstalledonfloors10– 19,thisdialwouldbesetto“1”.Ifitisbeinginstalledonfloors20– 29,thisdialwouldbesetto“2”,etc.EXAMPLE#1:Ifafixtureisbeinginstalledinthesecondstairwellofabuildingonthe17th floor,thedialindicatorswouldbesetlikethis:217.EXAMPLE#2:Ifafixtureisbeinginstalledinabuildingwithonlyonestairwellonthelandingbetweenfloors5and6,thedialindicatorswouldbesetlikethis:105.NOTE:Landingsbetweenfloorsshouldhavethesamedialsettingsasthefloorjustbelowit…i.e.Afixtureinstalledonalandingbetweenfloors2and3shouldhavethesamedialsettingsasthefixtureonfloor2.XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuideZONEX10AREAX1 DIMHILOWOFFPOWERHILOW“DIM”Settingcontrolsthelightlevelwhenthestairwellisun‐occupied.“POWER”Settingcontrolsthelightlevelwhenthestairwellisoccupied.XLZONEX10AREAX1TESTDIAG.STATUS
ControlPanelLEDIndicatorMessageInterpretation“OnlyForFixtures(XS&XL)withBatteryBack‐Up”DiagnosticLEDFunction DiagnosticLEDDiagnosticFAILED RED:OnDiagnosticPASSED GREEN:OnDiagnosticin PROGRESS Alternate FlashingbetweenREDandGREENTobeincompliancewithNFPALifeSafetyCode101,endusersmustperforma30‐secondmonthlyfunctionaltestanda90‐minuteannualtest.The30‐secondmonthlytestisdonebypressingtheDiagnosticTestButtononthecontrolpanel.A30‐secondself‐diagnostictestisbuiltintotheprogrammingofthisunit.After30‐secondstheresultswillbedisplayedasindicatedinthetablebelow.Toconducttheannualtest,powershouldbesecuredtothestairwellfixturesexternally(i.e.thecircuitbreaker).Attheendof90minutesthefixturesshouldstillbeprovidingadequateilluminationthroughtheintegratedbatteryback‐upsystemwithinthisfixture(ifsoequipped).Thetestitselfandtheresultsshouldberecordedandthisrecordmaintainedbytheenduser.ThetablebelowexplainswhattheDiagnosticLEDIndicator(DIAG)means:StatusLEDFunction StatusLEDACPowerGood,BatteryCharged GREEN:OnACPowerGood,BatteryCharging GREEN:FlashingACPowerOff,BatteryGood RED:OnAC PowerOff,BatteryLow RED:FlashingBatteryFAULT Alternate FlashingbetweenREDandGREENOncethefixturehasbeenproperlysecuredtotheceilingandpowered,twoIndicatorLEDscanbeseenonthecontrolpanelonthesideofthefixture.Theonetotheleft(whenlookingatthecontrolpanel)istheDiagnosticLEDIndicator.TheonetotherightistheStatusLEDIndicator.TheseLEDsarebi‐colored,meaningtheycanbe2differentcolors,inthiscaseRED orGREEN.ThetablebelowexplainswhattheStatusLEDIndicatormeans:8Note:Forfulldetailsrelatedtoperiodictestingofstairwellfixtures,seeNFPA101(00),Sec7.9.3.XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuideorXLZONEX10AREAX1orXLZONEX10AREAX1STAIRWELLX10FLOORX1TESTDIAG.STATUSTESTDIAG.STATUSXLZONEX10AREAX1STAIRWELLX10FLOORX1TESTDIAG.STATUSTESTDIAG.STATUS
“DIMandPOWER”SettingsForArtemisFixtures9XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuideThereareverystringentilluminationregulationsgoverningfixturesintendedforuseinstairwells.Xeleum’sXSArtemisfixturesarespecificallydesigntosurpasstheserequirements,andhavebeenvalidatedwith3rd partytestingandcertification.Assuch,neitherthePOWER(occupied)andDIM(un‐occupied)settingscanbeturnedoff.Thisensurestheproperilluminationrequiredtobecompliantwithregulatoryrequirements.Fornon‐stairwellapplications,Xeleum’sArtemisXLseriesoffersseveraldifferentPOWERandDIMsettingsallowingfullcustomizationforcustomerspecificapplication.Asmall“slideswitch”isprovidedinthewindowundertheDIMandPOWERlabelsonthecontrolpanel.Thesecanbesetwithafingerorasmallscrewdriver.POWERandDIMSettings:DIMSettingsfortheXL(non‐stairwellversion):The“DIM”settingcontrolsthelightlevelwhentheareabeingilluminatedis“unoccupied”.Therearethreedifferentoptionsforthissetting…HI – Thissettingprovidesabout50%ofthefixturesfullilluminationcapabilitywhentheareabeingilluminatedisunoccupied.LOW – Thissettingprovidesabout10%ofthefixturesfullilluminationcapabilitywhentheareabeingilluminatedisunoccupied.OFF – Thissettingturnsthefixturecompletelyoffwhentheareabeingilluminatedisunoccupied.Note:Theremaystillbeaslightglowcomingfromthefixtureinthissetting.Thisisrelatedtothechargingandmemoryfeaturesofthisfixture.POWERSettings:The“POWER”settingcontrolsthelightlevelwhentheareaisbeingilluminatedafterthefixture’sPIRsensorhasidentifiedmovementwithinthespace(occupied)…HI–Thissettingprovides100%powerorabout4200lumensformaximumilluminationwithinthespacebeingilluminated.LOW‐ Thissettingprovidesabout75%powerorabout3200lumenswithinthespacebeingilluminated.Thissettingprovidesanadditional25%energysavingsascomparedtotheHIsetting.SlideSwitchSTAIRWELLX10FLOORX1TESTDIAG.STATUSDIAG.STATUSTESTZONEX10AREAX1
Caution:10XeleumLighting,LLC.333NorthBedfordRd.MountKisco,NY10549*Phone954‐617‐8170*Fax954‐571‐9777*www.xeleum.comArtemisSeriesofLowOccupancyLEDCeilingMountedFixtures(IncludingStairwells)Installation&OperationGuideCet appareil est conforme àlaPartie 15desrèglements delaFCCetauxnormes RSSdel’Industrie duCanada.Sonfonctionnement est soumis auxdeux conditionssuivantes :(1)cet appareil nedoit pascauserdesinterférences nuisibles,et(2)cet appareil doit acceptertoute interférence reçue,ycompris lesinterférencesquipeuvent provoquer unfonctionnement indésirable.Lefabricantn'est pasresponsable destoutes interférences radioou télévision causées pardesmodificationsnonautorisées apportées àcet appareil.Detelles modificationspeuvent empêcher l’utilisateur d’utiliserl'appareil.ThisdevicecomplieswithPart15oftheFCCrulesandIndustryCanadalicense‐exemptRSSstandard(s).Operationissubjecttothefollowingtwoconditions:(1)thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptanyinterferencereceived,includinginterferencethatmaycauseundesiredoperation.ThemanufacturerisnotresponsibleforanyradioorTVinterferencecausedbyunauthorizedmodificationsorchangetothisequipment.Suchmodificationsorchangecouldvoidtheuser’sauthoritytooperatetheequipment.Leprésent émetteur radio(identifierledispositif parsonnuméro decertificationou sonnuméro demodèle s'ilfaitpartie dumatériel decatégorie II)aété approuvé parIndustrie Canadapourfonctionner aveclestypesd'antenne énumérés ci‐dessous etayant ungainadmissiblemaximal.Lestypesd'antenne noninclus danscette liste,etdont legainest supérieur augainmaximalindiqué,sont strictement interdits pourl'exploitationdel'émetteur.Thisradiotransmitter(identifythedevicebycertificationnumberormodelnumberifCategoryII)hasbeenapprovedbyIndustryCanadatooperatewiththeantennatypeslistedbelowwiththemaximumpermissiblegainindicated.Antennatypesnotincludedinthislist,havingagaingreaterthanthemaximumgainindicatedforthattype,arestrictlyprohibitedforusewiththisdevice.Max.AntennaGain(dBi)3dBiAntennaType MonopoleantennaWithRP SMAconnector