Raypak Raytherm 0180B Users Manual 6000.59 New RP2100
0042B to the manual 13de2bcb-7177-4e20-8003-08c58addd641
2015-02-02
: Raypak Raypak-Raytherm-0180B-Users-Manual-443482 raypak-raytherm-0180b-users-manual-443482 raypak pdf
Open the PDF directly: View PDF .
Page Count: 40
Download | |
Open PDF In Browser | View PDF |
INSTALLATION & OPERATING INSTRUCTIONS Raytherm™ Residential Boilers Models 0042B, 0066B, 0090B 0135B & 0180B – Type H WARNING: If these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or death. FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire. WHAT TO DO IF YOU SMELL GAS: • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference. CATALOG NO. 2100.50AB Effective: 09-02-09 Replaces: 12-26-07 P/N 240488 Rev. 29 Rev. 29 reflects the following: Changes to: Note on Page 8, text on Page 10, Item 7 on Page 11, mounting instructions on Page 12 2 CONTENTS WARNINGS Pay Attention to These Terms RECEIVING EQUIPMENT GENERAL SPECIFICATIONS INSTALLATION Code Requirements Mounting Base Clearance Requirements Combustion/Ventilation Air Venting Connections Vent Damper Installation Location VENT DAMPER WIRING DIAGRAM Gas Supply Connections Gas Pressure Water Connections & System Piping Electrical Wiring WIRING DIAGRAMS SERVICING PROCEDURES General Location of Controls SEQUENCE OF OPERATION Intermittent Ignition Device (IID) START-UP PROCEDURES Lighting the Boiler For Standing Pilot Models Filling the System Checking the Circulator For Standing Pilot Models with Robertshaw Gas Valve, 2-stage Operation (Models 90, 13 & 180) To Turn Off Gas to the Boiler (Models 90, 135 & 180) For Automatic Ignition Models For Intermittent Ignition (IID) with Honeywell or Robertshaw Gas Valve (All Models) To Turn Off Gas to the Boiler Shut-down Procedure Testing the Ignition afety Shut-off Safe Shut-down Tests Inspection Procedures REPAIR PROCEDURES Tube Cleaning Procedure Heat Exchanger Removal Heat Exchanger Re-assembly Combustion Chamber Removal TROUBLESHOOTING Adjustment & Replacement of Components Replacement Parts WARRANTY 4 4 5 5 7 7 7 7 8 9 11 14 15 15 15 18 19 26 26 26 26 27 27 27 27 27 28 28 28 29 29 29 30 30 31 32 32 32 3 33 33 34 36 37 38 WARNINGS Pay Attention to These Terms DANGER: WARNING: CAUTION: NOTE: Indicates the presence of immediate hazards which will cause severe personal injury, death or substantial property damage if ignored. Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored. Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored. Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards. DANGER: Make sure the gas on which the heater will operate is the same type as that specified on the heater rating plate. WARNING: To minimize the possibility of improper operation, serious personal injury, fire, or damage to the heater: WARNING—CALIFORNIA PROPOSITION 65: This product contains chemicals known to the State of California to cause cancer, birth defects or other reproductive harm. • • WARNING: This unit contains refractory ceramic fiber (RCF) insulation in the combustion chamber. RCF, as manufactured, does not contain respirable crystalline silica. However, following sustained exposure to very high temperatures (>2192F), the RCF can transform into crystalline silica (cristabolite). The International Agency for Research on Cancer (IARC) has classified the inhalation of crystalline silica (cristabolite) as carcinogenic to humans. Always keep the area around the heater free of combustible materials, gasoline, and other flammable liquids and vapors. Heater should never be covered or have any blockage to the flow of fresh air to the heater. WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water. WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the heater. Instead, shut off the gas supply at a location external to the heater. When removing the burners or heat exchangers, take precautions to avoid creating airborne dust and avoid inhaling airborne fibers. When cleaning spills, use wet sweeping or High Efficiency Particulate Air (HEPA) filtered vacuum to minimize airborne dust. Use feasible engineering controls such as local exhaust ventilation or dust collecting systems to minimize airborne dust. Wear appropriate personal protective equipment including gloves, safety glasses with side shields, and appropriate NIOSH certified respiratory protection, to avoid inhalation of airborne dust and airborne fiber particles. NOTE: These instructions are provided to ensure the proper installation and operation of Raypak boilers. Should questions arise regarding the specifications, installation, operation or servicing of these boilers, we suggest that the local Sales representative or the factory be consulted. 4 RECEIVING EQUIPMENT GENERAL SPECIFICATIONS On receipt of your equipment, visually check for external damage to the carton. If the carton is damaged, it is suggested that a note be made on the Bill of Lading when signing for the equipment. Raytherm hydronic boilers are design certified and tested under the requirements of the latest edition of the American National Standard, ANSI Z21.13/CSA 4.9. Each boiler has been constructed and pressure tested in accordance with the requirements of Section IV of the American Society of Mechanical Engineers Code, and factory fire tested. Remove the boiler from the carton, and if it is damaged, report the damage to the carrier immediately. Be sure that you receive the number of packages indicated on the Bill of Lading. Claims for shortages and damages must be filed with carrier by consignee. These boilers are designed for indoor installation with a built-in drafthood, and a built-in sub-base for combustible flooring. Models are available with standing pilot, or with an intermittent ignition device (IID). Purchased parts are subject to replacement only under the manufacturer's warranty. Debits for defective replacement parts will not be accepted and defective parts will be replaced in kind only per our standard warranties. These boilers are equipped with the following components: water circulation pump, pressure relief valve, temperature/pressure gauge, adjustable high limit switch, drain valve, fast response temperature sensor, 40 VA transformer, pump relay, vent thermal switch, flame roll-out switch, and redundant combination gas valve. Two-stage gas valve (50% firing on first stage) is standard on models H-0090, H-0135 and H-0180. When ordering parts, you must specify Model and Serial Number of the boiler. When ordering under warranty conditions, you must also specify date of installation. Raypak recommends that this manual be reviewed thoroughly before installing the boiler. If there are any questions which this manual does not answer, please contact your local Raypak representative. The automatic ignition models and some standing pilot models are provided with a plug-in connector that is compatible with the Honeywell D80D vent damper. Similar type vent dampers made by other manufacturers, and design certified by a nationally-recognized testing agency, under the ANSI Z21.66 standard, may also be used. Follow the installation instructions furnished with the vent damper package. The plug-in connector can also be used with power venters. Refer to the specific installation instructions supplied by the power vent manufacturer. 5 Model No. Input MBH Heating Capacity MBH Net I=B=R Rating H-0042 42 35 30 H-0090 90 74 64 H-0066 66 H-0135 54 135 H-0180 47 109 180 95 148 129 Piping Connections Water NPT Gas NPT 1 in. 1/2 in. A B C K Vent Dia. 1 in. 1/2 in. 11 in. 5 3/4 in. 5 1/2 in. 4 in. 1 in. 1/2 in. 11 in. 5 3/4 in. 5 3/4 in. 5 in. 1 1/4 in. 11 in. 1/2 in. 1 1/4 in. 18 in. 1/2 in. 18 in. 5 3/4 in. 5 3/4 in. 6 1/4 in. 5 in. 6 1/4 in. 6 1/4 in. 6 in. 8 in. 7 in. Table A: Specifications B AUTOMATIC VENT DAMPER (FIELD INSTALLED) OUTLET K 31/8 C INLET 1 4 /2 16 117/8 6 3/4 NPT PIPE TO DRAIN MIN 1 33 /4 19 THERMOSTAT CONN (ELECTRICAL CONN ON OTHER SIDE) A 1 22 /8 Fig. 1: Dimensions 6 1 3 /4 1 26 /2 GAS CONN 1 18 12 /2 5 INSTALLATION Code Requirements Installation must be in accordance with local codes, or in the absence of local codes, with the latest editions of the National Fuel Gas Code, ANSI Z223.1, and the National Electrical Code, ANSI/NFPA 70. In Canada, installations must conform with the current CSA B149 and the Canadian Electrical Code Part 1 CSA C22.2 No.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Boilers, CSD-1. Mounting Base Boiler should be mounted on a level surface. Each boiler is designed with a built-in sub-base approved for mounting the boiler on combustible flooring. Boiler must NOT be installed on carpet. Fig. 2: Mounting Base In addition, the boiler shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replacement, etc.) Clearance Requirements 1. Minimum clearances from combustible materials are listed in Table B below. NOTE: This boiler should be located in an area where water leakage will not result in damage to the area adjacent to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict air flow. Model No. 0042 0066 0090 0135 0180 2. A front clearance of at least 24" is recommended for adequate service of burner-tray and controls. Floor Front Back Right Left Top Comb. 4 in. 6 in. 6 in. 6 in. 16 in. Comb. Alcove 6 in. 6 in. 6 in. 16 in. Table B: Minimum Clearances From Combustible Materials 7 Flue Vent 6 in. 6 in. 3. Except for carpeted flooring, boilers are certified for installation on combustible floors. One opening shall be within 12" of the top, and the other opening within 12" of the floor. If additional gas appliances are installed in the same space, the total input of all gas appliances installed in the same space, must be considered in the calculation. Refer to the latest edition of the National Fuel Gas Code for additional requirements. 4. For un-insulated hot water pipes, maintain a 2" clearance, or consult local authority having jurisdiction. Combustion/Ventilation Air WARNING: Air supply to the boiler room must not be affected by mechanical exhaust vents located in other parts of the house, such as kitchen or bathroom fans, or attic blowers. Mechanical exhaust vents may create a negative pressure condition in the boiler room that can become a hazard of asphyxiation, explosion or fire. CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the boiler. Measures must be taken to prevent the entry of corrosive chemical fumes to the combustion and ventilation air supply. Such chemicals include, but are not limited to, chlorinated and/or fluorinated hydrocarbons such as found in refrigerants, aerosol propellants, drycleaning fluids, degreasers, and paint removers. Other harmful elements may come from bleaches, air fresheners, or mastics. Vapors from these types of products can form corrosive acid compounds when burned in a gas flame. The resulting acid condensate can damage or substantially reduce the life of the heater. It may be necessary to provide outside air directly to the heater in order to avoid this problem. Fig. 3: Location of Openings for Combustion/Ventilation Air NOTE: If louvers, grills or screens are used on the openings, obtain the net free area requirements from their supplier or manufacturer. If the design free area of a louver is not known nor available, it shall be assumed that wood louvers will have 20-25 percent free area and metal louvers will have 60-75 percent free area as specified in the National Fuel Gas Code. 1. The boiler must be provided with adequate supply of air for proper combustion and ventilation in accordance with the latest edition of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes. 3. If the boiler room is located against an outside wall and air openings can communicate directly with the outdoors, the two openings on the outside wall must each have a net free area as shown in Table D. 2. Models 0042 and 0066 only: When the boiler is installed in a confined space such as a utility room or closet where all air is supplied from inside the building, the boiler room must be provided with two openings, each one having a minimum net free area, in square inches as shown in Table C. Model No. 0042 0066 Model No. Sq. in. of Free Area 0066 18 0042 0090 Sq. in. of Free Area 0135 70 0180 Table C: Minimum Net Free Area 12 24 35 45 Table D: Minimum Net Free Area 8 Location of the openings is the same as in the previous case - that is, within 12" of the top, and within 12" of the bottom of the enclosure. If horizontal ducts are used, the area must be doubled and the duct area shall not be less than the area of the openings they connect, and in no case shall the smallest dimension be less than 3". The discharge opening must be a minimum of two (2) feet vertically from the roof surface and at least two (2) feet higher than any part of the building within ten (10) feet. Vent stack shall be at least five (5) feet in vertical height above the drafthood outlet. The vent cap location shall have a minimum clearance of four (4) feet horizontally from, and in no case above or below, unless a 4-foot horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment. Venting Connections These boilers have built-in drafthoods. Vent piping the same size or larger than the drafthood outlet is recommended; however, when the total vent height (drafthood outlet to vent terminal) is at least ten (10) feet, the vent pipe size may be reduced by one size only as specified in the latest edition of the National Fuel Gas Code, ANSI Z223.1. The weight of the vent stack or chimney must not rest on the boiler's drafthood. Support must be provided in compliance with applicable codes. The boiler top and drafthood must be readily removable for maintenance and inspection. Vent pipe should be adequately supported to maintain proper clearances from combustible construction. As much as possible, avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal runs, the vent pipe must have a minimum of 1/4 inch per foot rise and should be supported at not less than five foot intervals. Maximum vent connector horizontal length shall be 1-1/2 feet (18 inches) for each inch of connector diameter as shown in Table E. Vent Connector Diameter (in.) Max. Horizontal Length (ft) 0066, 0090 5 7.5 0135 6 9 0180 7 10.5 Model No. 0042 4 Type "B" double-wall (or equivalent) vent pipe is recommended. However, single-wall metal vent pipe may be used as specified in the latest edition of the National Flue Gas Code ANSI Z223.1. Listed Cap Lowest Discharge Opening Listed Gas Vent 6 X 12 Roof Pitch is X/12 H - Minimum Height from Roof to Lowest Discharge Opening Table E: Maximum Horizontal Length of Vent Pipe Gas vents supported only by the flashing and extending above the roof more than five feet should be securely guyed or braced to withstand snow and wind loads. We recommend use of insulated vent pipe spacer through the roofs and walls. Refer to Table F for detailed information Fig. 4: Minimum Height from Roof to Lowest Discharge Opening For protection against rain or blockage by snow, the vent pipe must terminate with a listed vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z223.1. 9 Roof Pitch (X/12) H (Min. ft) 6/12 to 7/12 1.25 Over 8/12 to 9/12 2 Flat to 6/12 Over 7/12 to 8/12 Over 9/12 to 10/12 1 1.5 3.25 Over 12/12 to 14/12 5 Over 14/12 to 16/12 Over 16/12 to 18/12 Over 18/12 to 20/12 Over 20/12 to 21/12 Refer to Fig. 4 for graphical reference For connections to gas vents or chimneys, vent installations shall be in accordance with the Venting of Equipment section of the National Fuel Gas Code, ANSI Z223.1, or applicable provisions of the local building codes. 2.5 Over 10/12 to 11/12 Over 11/12 to 12/12 WARNING: These boilers must not be connected into any portion of mechanical draft systems operating under positive pressure. To do so may cause the flue products to be discharged into the living space causing serious health injury. 4 Common Vents 6 Manifolds that connect more than one boiler to a common chimney must be sized to handle the combined load. Consult available guides for proper sizing of the manifold and the chimney. At no time should the area be less than the area of the largest outlet. 7 7.5 8 Table F: Minimum Height from Roof to Lowest Discharge Opening Fig. 6: Common Venting Fig. 5: Minimum Venting Measurements 10 Vent Damper Installation Location At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation. The vent damper supplied with each boiler must be located in the vent so that it serves only the appliance for which it is intended. 1. Seal any unused openings in the common venting system. If improperly installed, a hazardous condition, such as an explosion or carbon monoxide poisoning, could result. Make certain that it is mounted in an accessible location at least 6 in. (152.4 mm) from any combustible material or the heat exchanger and that the position indicator is in a visible location. 2. Visually inspect the venting system for proper size and horizontal pitch and make sure there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. The vent damper must be installed at the appliance drafthood, and without modification of the drafthood. 3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers. To connect the vent damper wiring to the boiler wiring, connect the damper circuit plug to the boiler circuit plug. 4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously. 5. Test for spillage at the drafthood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe to visually check spillage. 6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use. 7. Any improper operation of the common venting system should be corrected so that the installation conforms with the latest edition of the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code, ANSI Z 223.1 and CSA - B149. Fig. 7: Vent Damper Location WARNING: Carefully read and follow the installation instructions furnished with the vent damper package. Failure to follow these instructions can cause asphyxiation, explosion or fire. 11 Mounting On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the side of the vent. The vent damper is set up for a continuous pilot system. If the vent damper is installed on a system with an Intermittent Pilot, the energy savings of the vent damper can be improved by plugging the hole in the vent damper blade using the knockout plug provided in the parts envelope. Hole in Vent Damper Blade Closed Position Fig. 10: D80D General Wiring Diagram Install the vent damper to service only the single appliance for which it is intended. If improperly installed, a hazardous condition, such as an explosion or carbon monoxide poisoning, could result. Vent Damper Operation DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a hazardous condition. For safe, efficient operation, the vent damper and all flue-product-carrying areas of the appliance must be checked annually, with particular attention given to deterioration from corrosion or other sources. Fig. 8: Vent Damper Check vent damper operation as follows: 1. When the boiler is off, check that the vent damper position indicator points to the closed position (see Fig. 11). Damper Position Indicator Fig. 9: Installing The Vent Damper in Horizontal & Vertical Vents Damper Open 12 Damper Closed Fig. 11: Vent Damper Position Indicator NOTE: To place vent damper in the open position to allow burner operation: Turn the power off. Turn the damper blade to fully open position (arrow facing same direction as vent pipe). Turn power on. 24 2. Turn the thermostat or controller up to call for heat and check that the vent damper indicator points to the open position, as shown in Fig. 11. 2 4 3 Abbreviation 2 SC R1 End Switch TR GV TH J JUMPER Description ES SS2 SS2 ES SS 1 Relay N/C Safety Switch N/O Safety Switch Transformer, 120/24V High Limit 24V Gas Valve Thermostat, Heating, Low Voltage Jumper Table G: Legend for Figures 12 & 13 4 HL TR 120 VAC 60Hz L L 1 2 R Damper Motor SS1 R1 GV 24 VAC 2 M R 3 HL GV Fig. 13: Ladder Diagram HL 2 1 M R 1 J SS Flair Damper M SS ES The vent damper must be inspected at least once a year by a trained, experienced service technician. The name of the person who originally installed your vent damper is shown on the installation label. Damper must be in open position when boiler main burners are operating. SC AC R TH 3. Turn the thermostat or controller down again and check that the vent damper position indicator returns to the closed position. R2 V TH Note: Circuit shown with damper in closed position, no call for heat. Fig. 12: System Schematic 13 VENT DAMPER 14 Model 1/2 in. Pipe No. Nat. Pro. 0042 125 350 0090 30 80 0066 0135 0180 60 15 160 40 20 3/4 in. Pipe Nat. Pro. 175 460 60 150 500 125 35 1 in. Pipe Nat. Pro. 300 400 90 115 200 450 300 1 1/4 in. Pipe Nat. Pro. 425 Table H: Maximum Equivalent Pipe Length (Feet) Gas Supply Connections NOTE: Do not use teflon tape on gas line pipe thread. A flexible sealant suitable for use with Natural and Propane gases is recommended. The inlet gas connection of the boiler gas valve is 1/2". Provide an adequate gas piping supply line no smaller than 1/2", according to Table H above. These boilers are also certified to operate on propane gas, when equipped with the combination gas valve and orifices (pilot and main burners) sized for propane gas. Gas piping must have a sediment trap ahead of the boiler gas controls, and a manual shut-off valve located outside the jacket. All gas piping should be tested after installation in accordance with local codes. Manual Valve Gas Pressure The gas valve is provided with pressure taps to measure gas pressure upstream of the gas valve and downstream which is the same as the manifold pressure. Union Gas Type Sediment Trap Natural Gas Valve Propane Must be Supplied by Installer Fig. 14: Sediment Trap CAUTION: The boiler and its manual shut-off valve must be disconnected from the gas supply during any pressure testing of that system at test pressures in excess of 1/2 psi (3.45 kPa). Dissipate test pressure in the gas supply line before reconnecting the boiler and its manual shut-off valve to gas supply line. FAILURE TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. OVER PRESSURED GAS VALVES ARE NOT COVERED BY WARRANTY. The boiler and its gas connections shall be leak tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use open flame. Inches WC Min. Inches WC Max. Regulator Setting 12.0 13.0 11.0 7.0 10.5 3.5 Table I: Minimum and Maximum Gas Pressure Water Connections & System Piping The pipe size for water connections is shown on page 6. Typical piping systems are shown on pages 17 to 19. 15 This boiler is supplied with a circulator and built-in bypass as standard to ensure the required minimum water flow in the boiler. The bypass on models H-0135 and H-0180 is provided with an adjustable valve that is factory-set in the full open position. The handle is shipped loose. The full open position is appropriate for most systems, and ensures adequate flow through the boiler. Systems with multiple zones may require an additional circulator. Consult manufacturer's data for valve pressure drops. When an indirect water heating system is used, it is recommended that a separate circulator be installed to meet the required flow and pressure drop conditions of the indirect water heater. If system flow is inadequate, (indicated by excessive temperature drop through the system) the bypass valve can be throttled slightly. Care must be taken against over-throttling which may lead to inadequate flow through the boiler and boiler harmonics (a humming sound from the heat exchanger). We recommend that the make-up water from the cold water line have a check valve, gate valve, and feedwater regulator set at 12 psi. Install unions and gate or ball valves at inlet and outlet connections at the boiler to facilitate servicing. If adequate system flow cannot be obtained without causing harmonics, an additional pump is required. The factory-mounted circulator will provide adequate water flow for systems designed at a 20°F temperature drop, and system pressure drop or head not exceeding that which is shown in Table J. Model No. System Flow (gpm) Max. System Head (ft/WC) H-0066 5.3 8.5 H-0042 H-0090 H-0135 H-0180 3.5 7.3 11.0 14.6 Table J: System Pressure Drop The pressure relief valve is mounted on the boiler and must be piped to a drain. We recommend that all high points be vented and that purge valves be installed. A boiler installed above radiation level must be provided with a low water cut-off device. See page 27 for wiring hook-up. The boiler, when used in connection with a refrigeration system, must be installed so that the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler. 8.0 6.5 The boiler piping system of a hot water heating boiler, that is connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 10.0 7.0 When the total system head exceeds the available head pressures, a primary/secondary pumping system is recommended. A diaphragm expansion tank should be installed in the return line. A typical 8"-diameter expansion tank can be used on models H-0042, and H-0066, and an 11"diameter expansion tank can be used on models H-0090, H-0135 and H-0180. Consult tank manufacturer for correct sizing. The minimum boiler operating temperature should be 105°F. When operating at low temperature applications, ∆T (temperature rise) must be 20°F or less. Propylene glycol solution is commonly used in the heating system when freeze protection is required. This will affect the system design and pump performance. As a rule of thumb, 50% solution of propylene glycol will require the system flow (gpm) to increase by 14%, and the system head (ft/WC) by 23% in order to maintain the same heat transfer load. 16 Piping Diagrams Air Vent Air Scoop Feed Valve Diaphragm Expansion Tank Pipe Pressure Relief Valve to Drain Cold Water Inlet Heating Units Fig. 15: Single-Zone Piping 12” Max. Air Vent Air Scoop Feed Valve Circulators Diaphragm Expansion Tank Pipe Pressure Relief Valve to Drain Cold Water Inlet Heating Units Fig. 16: Multiple Zones with Circulators 17 Electrical Wiring The room thermostat should be installed in accordance with the manufacturer's instructions. The thermostat heat anticipator should be set at 1.0 ampere (automatic ignition) and 0.60 ampere (standing pilot) for single- zone installations. For multi-zone applications, the heat anticipator setting should be based on the ampere load in the thermostat circuit. The electrical power supply requirement for these boilers is 120 VAC, 60 Hz. Field wiring connections and electrical grounding must comply with the local codes, or in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFPA 70. NOTE: If it is necessary to replace any of the original wiring, it must be replaced with 105°C wire or its equivalent, except 150°C black wire must be replaced with 150°C wire or its equivalent. See Fig. 19 for 150°C wire indication. Provide a separate fused circuit from the main electrical panel to the boiler, and a disconnecting means within sight of the boiler. Remove the control box cover and make the power supply connections in the field wiring compartment. (See general location of controls drawing on page 28). The pump is supplied and factory-wired to operate with the boiler. The "TH" wire leads are for the room thermostat or zone valve connections. 18 Wiring Diagrams 19 20 21 Fig. 17: Single-Zone Taco Valve NOTE: Maximum three (3) zone valves per one (1) 40 VA transformer. Fig. 18: Dual-Zone Taco Valve NOTE: Maximum five (5) zone valves per one (1) 40 VA Transformer. Fig. 19: Dual-Zone Honeywell Valve 22 NOTE: Check VA rating of each relay coil. Total load must not exceed VA rating of transformer. Fig. 20: System with Three (3) Zone Pumps Fig. 21: Power Vent System with Zone Valve 23 Fig. 22: Primary/Secondary Pumping System Honeywell Zone Valve Note: Low water cut-off (LWCO) and system switch supplied by others. Fig. 23: Standing Pilot with Low Water Cut-off Device 24 Note: Low water cut-off (LWCO) and system switch supplied by others. Fig. 24: IID Units with Low Water Cut-off Device 25 SERVICING PROCEDURES SEQUENCE OF OPERATION General Location of Controls Intermittent Ignition Device (IID) Boilers equipped with the IID system will automatically light the pilot burner first and then the main burner, each time there is a call for heat from the room thermostat. Whenever the room thermostat is calling for heat, the circulator supplied with the boiler will be energized and should be running. 2-Stage Controller Relay The ignition control module will also be energized to initiate the pilot ignition by opening the first main valve (pilot). At the same time, the electronic spark generator in the module produces a high-voltage spark output that lights the pilot burner. If the pilot burner does not light, the module will not energize the second main valve and the burners will not light. FastIgnition Module Response Temperature (Auto Ignition Only) Sensor Ignition spark continues only until the timed trial for ignition period ends. Then, the module goes into safety shutdown or lockout. Lockout de-energizes the first main valve operator and closes the first main (pilot) valve in the gas control, stopping pilot gas flow. The ignition control system must be reset by setting the thermostat below room temperature for one minute or by turning off power to the module for one minute. Fig. 25: Control Box Component Locations Models 135 & 180 CIRCULATOR VENT SENSOR BYPASS VALVE (MODELS 135 & 180 ONLY) When the pilot flame is established, flame rectification circuit is completed between the sensor and burner ground. The flame sensing circuit in the module detects the flame current, shuts off the spark generator and energizes the second main valve operator which opens the second main valve. This allows gas to flow to the burners where it is ignited by the pilot burner flame. BYPASS LINE TEMPERATURE AND PRESSURE GAUGE 2-STAGED CONTROLLER (MODEL 90 ONLY) PRESSURE RELIEF VALVE RELAY ADJUSTABLE HIGH LIMIT When the thermostat is satisfied, the valve operators are de-energized shutting off the pilot and main burners, and also the circulator. FIELD WIRING COMPARTMENT FAST RESPONSE TEMPERATURE SENSOR IGNITION MODULE (AUTO IGNITION ONLY) TRANSFORMER ROLL-OUT SENSOR GAS VALVE Fig. 26: Component Locations 26 START-UP PROCEDURES Filling the System Flush system before putting into operation to ensure that foreign material does not damage pump seals. Fill system with water. Purge all air from the system using purge valve sequence. After system is purged of air, lower system pressure. Open valves for normal system operation, fill system through feed pressure regulator to minimum 12 psi. Manually open air vent on the compression tank until water appears, then close vent. Lighting the Boiler Safe-lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the boiler underwent tests specified in the latest edition of the ANSI-Z21.13/CSA 4.9 Standard. On multiple-zone systems, purge each zone separately. Isolate the other zones while one zone is being purged of air. CAUTION: Propane gas is heavier than air and sinks to the ground. Exercise extreme care in lighting boiler in confined areas. Checking the Circulator For Standing Pilot Models Before lighting the boiler and after system is filled, make sure that circulator is operating properly. Manual gas valve should be off. By adjusting the wall thermostat to the maximum setting, circulator should run immediately and allow water to flow through the boiler and the entire system. WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This boiler has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. NOTE: Circulator motor supplied with the boiler does not require lubrication. B. BEFORE LIGHTING Smell all around the boiler area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. CAUTION: In case of a prolonged power failure during freezing weather conditions, boiler and piping system must be drained completely to avoid possible damage to the heating system. WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electric switch; • Do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. C. Use only your hand to push in, move or turn the gas control knob or lever. Never use tools. If the knob or lever will not push in, move or turn by hand, don't try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water. 27 For Standing Pilot Models with Robertshaw Gas Valve, 2-stage Operation (Models 90, 135 & 180) 1. 2. 3. 4. *If lever does not spring back to "PILOT" position when released, stop and immediately call your service technician or gas supplier. *If the pilot does not stay lit after several tries, move the gas control lever to "OFF" and call your service technician or gas supplier. 9. Stand to the side of the boiler and move the gas control lever counter-clockwise to "ON". 10. Turn on all electrical power to the boiler. 11. Set the thermostat to the desired setting. STOP! Read the safety information. Set the thermostat to the lowest setting. Turn off all electrical power to the boiler. Push in and move gas control lever counterclockwise to "OFF" position. To Turn Off Gas to the Boiler (Models 90, 135 & 180) GAS CONTROL LEVER SHOWN IN "OFF" POSITION 1. Set the thermostat to the lowest setting. 2. Turn off all electrical power to the boiler 3. Push in and move gas control lever counterclockwise to "OFF" position. Do not force. GAS INLET For Automatic Ignition Models Fig. 27: Gas Valve Please read carefully and understand the following safety information before operating the boiler. NOTE: Lever cannot be moved from "ON" to "OFF" unless lever is pushed in slightly. Do not force. WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. 5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the label affixed to the unit. If you don't smell gas, go to the next step. 6. Locate pilot mounted on the right side of the burner tray, and right of first burner. A. This boiler is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand; or this boiler may not have a pilot and is equipped with a hot surface ignition device which automatically lights the burners. Do not try to light the burners by hand. B. BEFORE OPERATING smell all around the boiler area for gas. Be sure to smell next to the floor because some gases are heavier than air and will settle on the floor. HONEYWELL PILOT WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electrical switch. • Do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. ROBERTSHAW PILOT Fig. 28: Pilots 7. Move control lever clockwise to "SET" position and immediately light pilot with a match. 8. Hold lever in "SET" position for 1/2 minute after pilot is lit. Release lever, and it will spring back to "PILOT" position. Pilot should remain lit. If it goes out, repeat steps 4 through 8. C. Use only your hand to push in, move or turn the gas control knob or lever. Never use tools. If the knob or lever will not push in, move or turn by hand don't try to repair it, call a qualified service 28 technician. Force or attempted repair may result in a fire or explosion. GAS CONTROL KNOB SHOWN IN "OFF" POSITION D. Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water. GAS INLET For Intermittent Ignition (IID) with Honeywell or Robertshaw Gas Valve (All Models) 1. 2. 3. 4. ROBERTSHAW (All Models) Fig. 30: Robertshaw Gas Valve STOP! Read the previous safety information. Set the thermostat to the lowest setting. Turn off all electrical power to the appliance. This boiler is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. 8. Turn on all electrical power to the boiler. 9. Set thermostat to desired setting. 10. If the boiler will not operate, follow the instructions "To Turn Off Gas To Boiler" and call your service technician or gas supplier. To Turn Off Gas to the Boiler GAS CONTROL KNOB SHOWN IN"OFF" POSITION 1. Set the thermostat at the lowest setting. 2. Turn off all electrical power to the boiler if service is to be performed. 3. For Honeywell valve: Turn gas control knob clockwise to "Off". Make sure knob rest against stop. For Robertshaw valve: Push in and move gas control lever to "Off" position. GASINLET HONEYWELL (Models 30 - 90) Fig. 29: Honeywell Gas Valve 5. For Honeywell valve: Turn gas control knob clockwise to "Off". For Robertshaw valve: Push in and move gas control lever to "Off" position. 6. Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the label affixed to the front of the unit. If you don't smell gas, go to the next step. 7. For Honeywell valve: turn gas control counterclockwise to "On". For Robertshaw valve: Move gas control lever to "On" position. HONEYWELL PILOT Fig. 31: Honeywell Pilot Shut-down Procedure To prevent freeze damage to the heating system, it is recommended that the following system shut-down procedure be performed. 1. Set the room thermostat to "OFF" or the lowest setting. 2. Turn off all electrical switches to the boiler. 29 3. Turn off all gas valves supplying gas to the boiler. Refer to operating instruction label on the boiler. 4. Shut-off the water supply to the boiler piping system loop. 5. Open drain valve on the boiler to remove water from the boiler and the piping circuits. e. Replace pilot adjustment cover screw, then follow the lighting instructions to get boiler ready for operation. For Automatic Ignition Systems Intermittent Ignition (IID) NOTE: It may be necessary to open the purge valves and/ or manual air vents to facilitate complete drainage of water from the heating system. 1. Turn on power to the ignition systems and turn gas supply off at the gas valve. 2. Check ignition module as follows: a. Set the thermostat or controller above room temperature to call for heat. b. Watch for continuous spark at the pilot burner. c. Time the spark operation. Time must be within the lockout timing period (15 or 90 seconds). d. Turn thermostat down to end call for heat and wait 60 seconds on lockout models before beginning step 3. 3. Turn on gas supply. 4. Set thermostat or controller above room temperature to call for heat. 5. Systems should start as follows: a. Spark will turn on and pilot gas valve will open at once. Pilot burner should ignite after gas reaches the pilot burner. b. Spark ignition should cut-off when pilot flame is established. c. Main gas valve should open and main burner should ignite after gas reaches the burner port. CAUTION: Should overheating occur or the gas supply fails to shut-off, DO NOT turn off or disconnect the electrical supply to the pump. Instead, shut-off the gas supply at a location external to the boiler. Failure to observe this precaution may aggravate the overheated condition resulting in possible damage to the boiler and injury to the user. Testing the Ignition Safety Shut-off The ignition system safety shut-off must be tested by conducting the following tests: For Standing Pilot Systems 1. With the main burners on, remove the pilot adjustment cover screw. NOTE: There is no pilot adjustment cover on Robertshaw 7200 gas valve. Safe Shut-down Tests 2. Insert a small slot screw driver and turn the adjustment screw clockwise until pilot flame goes out. Note and count number of turns made. 3. Gas valve will shut-off main burners after about three (3) minutes. If the gas valve will not shut-off, follow the instructions "To Turn Off Gas To Boiler" and call service technician or your gas supplier. 4. Return pilot adjustment screw counter-clockwise , using the same number of turns as in step (b). Limit Action With the burner operating, lower the high limit setting to simulate an overheated boiler. Normal shutdown should occur. Restore the normal limit setting, and the burner should restart. Flame Failure 1 2 3 With burner operating, close the manual fuel valves to simulate a flame failure. System should lock out after safety switch timing (15 seconds). After the safety switch has cooled, open the manual valves (relight standing pilots) and reset the safety switch; the burner should restart. S E T PILOT P I ADJ L O T O N O F F PILOT KEY Pilot Adjustment Fig. 32: Robertshaw 7200 Gas Valve (Models 90, 135, 180) 30 Inspection Procedures *3. *4. *5. *6. Inspect pilot and main burner flame and firing rate. Inspect and operate all controls and gas valve. Visually inspect system for water leaks. Inspect oil pump motor and bearing assembly, if oil cups are provided. 7. Check flow switch paddle. 8. Clean room air intake openings to ensure adequate flow of combustion and ventilation air. 9. Keep boiler area clear and free from combustible materials, gasoline, and other flammable vapors and liquids. Burners Clean main burners and air louvers of dust, lint and debris. Keep boiler area clear and free from combustibles and flammable liquids. Do not obstruct the flow of combustion and ventilation air. Make visual check of burner and pilot flame. Yellow flame indicates clogging of air openings. Lifting or blowing flame indicates high gas pressure. Low flame indicates low gas pressure. *Should be checked monthly. (Takes approximately 15 minutes). Low Water Cut-Off (When Installed) The low water cut-off automatically shuts down burner whenever water level drops below probe. 90 second time delay prevents premature lockout due to temporary conditions such as power failure or air pockets. Flush float type devices at beginning of each heating season. Procedure for Cleaning Flue Gas Passageways NOTE: Modulating burner flame varies in height from approximately 1/4" at low fire to approximately 4" in high fire. Fig. 33: Main Burner Flame Soot will clog areas behind fins and eventually cause tube failure. Any sign of soot at base of burners or around outer jacket indicates a need for cleaning. 1. Lift off drafthood and flue collector by removing bolts and screws. 2. Remove "V" baffles from heat exchanger. 3. Remove burner tray, see Burner Tray Removal. 4. Take garden hose and wash heat exchanger, making sure soot is removed from between fins. (Avoid excessive water against refractory). 5. Reassemble; when boiler is fired, some steam will form from wet refractory. This is normal. NOTE: In extreme cases it may be necessary to remove the heat exchanger completely for cleaning. The simplest method is steam cleaning at a local car wash. DO NOT WIRE BRUSH! Fig. 34: Pilot Burner Flame (Standing Pilot Units) Inspection Schedule To be performed the first and third month after initial start up and then on an annual basis. If problems are found, refer to Troubleshooting Guide for additional directions. 1. Remove top of boiler and inspect heat exchanger for soot and examine venting system. 2. Remove rear header and inspect for scale deposits. CAUTION: Soot is combustible, so exercise extreme care. 31 REPAIR PROCEDURES Burner Tray Removal 1. Shut-off power and gas supply to the boiler. Disconnect union(s) and pilot tubing when present; then loosen and remove burner hold-down screws. 2. Disconnect wires at gas valve and slide burner tray out. Tube Cleaning Procedure (Typical) Establish a regular inspection schedule, the frequency of which depends on the local water condition and severity of service. Do not let the tubes clog up solidly. Clean out deposits over 1/16" in thickness. Main Burner and Orifice Removal 1. Remove screws and burner hold-down bracket. To clean the tubes, remove the heat exchanger, ream tubes and immerse heat exchanger in non-inhibited de-scale solvent. NOTE: If the heat exchanger is sooted badly, the burner hold-down bracket and spacer can become distorted from direct flame impingement and this usually necessitates replacement of these parts. Heat Exchanger Removal 1. Shut water, gas and electricity off, close valves, relieve pressure and remove relief valve. Remove front inspection panel. 2. Lift burners from slotted spacer and slide from orifices. Clean with a wire brush. 3. Orifices usually do not need to be replaced. To clean, run either copper wire or wood through orifice. Do not enlarge hole. To remove orifice, use a socket wrench and remove the manifold. DO NOT over-tighten when reinstalling. 2. Remove top holding screws. 3. Remove draft diverter, lift and remove top and flue collector on stack type models. 4. Loosen bolts and disconnect flange nuts on inlet/outlet header, loosen union(s) at gas pipe, and slide boiler away from piping until studs clear the heater. 5. Lift heat exchanger straight up using caution not to damage refractory. RAYPAK TUBE CLEANING KIT Extension Pieces (5) Auger with Carbide Tip 5/8" - PN 052871F 7/8" - PN 052870F Fig. 35: Raypak Tube Cleaning Kit 32 Wire Brush Heat Exchanger Re-assembly 9. Install flue collector, jacket top and inspection panels. Install top holding screws. Install draft diverter and vent piping if so equipped. 1. Heat exchanger water header O-rings should be replaced with new ones. 10. If gas piping was disconnected, reconnect gas piping system and check for leakage using a soap solution. 2. Install in/out and return water headers and install header retainer nuts and torque nuts evenly. 11. Check for correct water pressure and water level in the system. Make sure that system pump operates immediately on the call for heat. The system is ready for operation. 3. Replace "V" baffles. 4. Install thermostat sensing bulbs in header wells and replace bulb retaining clips. 12. Within two (2) days of start-up, recheck all air vents and expansion tank levels. 5. Install inlet and return pipes in water headers using pipe thread sealant. Combustion Chamber Removal 6. Install water pressure relief valve, flow switch, and low water cut-off devices if so equipped. To remove combustion chamber panels, you must first remove the heat exchanger. Remove combustion chamber panels individually. 7. Open water supply and return shut-off valves. Fill boiler and water piping system with water. Check boiler and piping system for leaks at full line pressure. Run system circulating pump for a minimum of 1/2 hour with boiler shut off. 8. Shut down entire system and vent all radiation units and high points in system piping. Check all strainers for debris. Expansion tank water level should be at the 1/4 mark and the balance of the tank filled with air (when using Air-X-Tank). Fig. 36: Combustion Chamber Panels—Top View 33 TROUBLESHOOTING These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not qualified shall not attempt to install this equipment nor attempt repairs according to these instructions. PROBLEM 1)When room thermostat is turned on, boiler does not operate. CAUSES 1) No power to the boiler. SOLUTIONS 1) Check circuit breakers, disconnect switch. Make sure power is on. 2) Defective room thermostat or disconnected wire in thermostat circuit. 2) Check continuity on thermostat and wiring circuit. Replace thermostat, or repair wiring connections. 3) Check secondary voltage. If no 24V, replace transformer. 4) Check relay coil or contacts. Replace as required. 5) Replace pump. 3) Defective transformer. 4) Defective pump relay. 5)Defective pump. 2)When room thermostat is calling for heat, pump is on, but burners will not turn on. 1)For standing pilot models, pilot burner not lighted. 2)If pilot burner will not stay lighted, thermocouple or gas valve may be defective. 3) Gas knob in "Pilot" position. 4) For automatic ignition models, gas valve knob is in "OFF" position. 5)Vent switch is open. 6) Roll-out switch is open. 7) High limit is open. 8) Fast Response Temperature Sensor probe is defective. 9) Fast Response Temperature sensor board is defective. 34 1) Light pilot burner. (Follow lighting instructions on rating plate.) 2) Check thermocouple MV generation. If less than 25MV (open circuit), replace thermocouple. If between 2535 MV, replace gas valve. 3) Turn knob to "ON" position. 4) Turn gas knob to "ON". If ignition module locks out, reset by interrupting power to boiler. 5) Check for blockage of venting system or disconnected vent piping. After problem is corrected push button to reset, or replace single-use type vent switch. 6) Check for blockage of flue or sooted heat exchanger. After problem is corrected push button to reset or replace single use type roll-out switch. 7) Setting may be too low. Check water flow and adjust setting to obtain 2030°F temperature rise. 8) Red LED on circuit board will be ON to indicate a loose sensor connection or a shorted sensor. Check terminal connectors or replace sensor as required. NOTE: Red LED will also be ON if sensor temperature exceeds 300°F or drops below - 20°F. It will turn OFF when sensor temperature returns to the proper range. Yellow LED will be ON if temperature exceeds 240°F. It will turn off when sensor temperature falls below 180°F. When either Red or Yellow LED is ON, boiler will be shut down. 9)Check voltage across output and common terminals. If no 24V is present, replace board. 3) Pilot Outage. (Standing pilot models) 4) Yellow lazy flame. 10) Defective ignition module or defective gas valve. 10) Before module goes into a lock-out, check voltage across MV and MV/ PV. If no 24V is present, replace module. If 24V is present, replace gas valve. 1) Too low or too high gas pressures. 2) Restricted pilot. 3) Weak thermocouple. 1) Adjust inlet gas pressure as shown on rating plate. 2) Clean pilot orifice. 3) Replace thermocouple. 1) Too low gas pressure. 1) Adjust manifold pressure as shown 2) Restricted burner intake ports. 3) Restricted gas line. 5) Sooting 1) Insufficient combustion air. 2) Improper venting. 3) Severe yellow burner flames. 35 on rating plate. 2) Clean burners free of debris or insects. 3) Clean gas line or increase gas line piping. 1) Refer to installation instructions regarding combustion air requirements. 2) Refer to installations instructions. 3) See yellow flame section above. Adjustment & Replacement of Components Flame Roll-out Switch Replacement DANGER—SHOCK HAZARD: Make sure electrical power to the boiler is disconnected to avoid potential serious injury or damage to components. 1. Shut-off electrical power and gas supply to the boiler. 2. Remove gas piping to gas valve inlet. 3. Disconnect wiring connections, pilot tubing (when present). 4. Remove screws (2) holding the burner tray. 5. Slide burner tray out. 6. Remove gas valve bracket screws and bracket. 7. Unscrew gas valve from gas pipe. 8. Reverse above procedure to re-install. Shut-off electrical power to the boiler. Remove wiring connections to switch. Remove the screws (2). Reverse above procedure to re-install. 1. Shut-off electrical power to the boiler. 2. Remove control cover screws and open control compartment. 3. Disconnect wiring connections to module. 4. Remove screws (2) holding module. 5. Reverse above procedure to re-install. Transformer Replacement 1. Shut-off electrical power and gas supply to the boiler. 2. Disconnect gas piping to gas valve. 3. Disconnect wiring connections to gas valve. 4. Remove screws (2) holding the burner tray. 5. Slide burner tray out. 6. Remove screw holding pilot lighter tube. 7. Remove screws (2) holding pilot bracket on the burner tray. 8. Disconnect thermocouple and pilot tubing from the gas valve. 9. Remove pilot burner from pilot bracket. 10. Remove pilot orifice and blow away lint or dirt. Clean with wire or small brush. NOTE: Make sure pilot orifice is clear, but do not enlarge the hole. 11. Reverse above procedure to re-install. Orifice 1. 2. 3. 4. Ignition Module Replacement Pilot Burner Cleaning or Replacement (Standing Pilot) Air Opening Shut-off electrical power to the boiler. Remove wiring connections to switch. Remove screws (2) holding the switch. Reverse above procedure to re-install. Vent Thermal Switch Replacement Gas Valve Replacement Pilot 1. 2. 3. 4. 1. Shut-off electrical power to the boiler. 2. Remove control cover screws and open control compartment. 3. Disconnect wiring connections from transformer leads. 4. Remove screws (2) holding transformer. 5. Reverse above procedure to re-install. Pump Relay Replacement 1. Shut-off electrical power to the boiler. 2. Remove control cover screws and open control compartment. 3. Disconnect wiring to the relay. 4. Remove screws (2) holding relay. 5. Reverse above procedure to re-install. High Limit Control Pilot 1. Shut-off electrical power to the boiler. 2. Remove control cover screws and open control compartment. 3. The control is factory set at 180°F. To adjust setting, use a small screw driver and turn dial clockwise to lower the temperature or counterclockwise to raise the setting. 4. To replace the limit control, disconnect the wiring connections. 5. Remove screws (2) holding the limit control. 6. Remove upper access panel. Orifice Fig. 37: Pilots, Honeywell (Left) and Robertshaw (Right) 36 2-Stage Controller (Models 90, 135 & 180) 7. Remove the wedge or retaining clip holding the sensing bulb in the control well in the in/out header. 8. Pull out the sensing bulb carefully from the control well. 9. Remove the limit control with capillary from unit. 10. Reverse above procedure to re-install. 1. Shut-off electrical power to the boiler. 2. Remove control cover screws and open control compartment. 3. The control is factory set at 160°F. To adjust to another setting, use a small screw driver and turn dial clockwise to lower the temperature or counterclockwise to raise the setting. 4. To replace the stage controller, disconnect the wiring connections. 5. Remove screws (2) holding the staged controller. 6. Remove upper access panel. 7. Remove the wedge or retaining clip holding the sensing bulb in the control well in the in/ out header. 8. Pull out the sensing bulb carefully from the control well. 9. Remove the stage control with capillary from unit. 10. Reverse above procedure to re-install. Fast-Response Temperature Sensor Module Replacement 1. Shut-off electrical power to the boiler. 2. Remove control cover screws and open control compartment. 3. Disconnect wiring to the board. 4. Carefully pull out the control board from the nylon pin supports. Reverse above procedure to re-install. Fast-Response Temperature Sensor Probe Replacement Replacement Parts List 1. Shut-off electrical power to the boiler. 2. Shut-off water supply to the boiler and open drain valve to remove water to the sensor probe level. 3. Remove control cover screws and open control compartment. 4. Disconnect wire leads from control board. 5. Remove upper access panel. 6. Remove sensor probe from in/out header. 7. Reverse above procedure to re-install. NOTE: To supply the correct part it is important that you supply the model number, serial number and type of gas when applicable. Any part returned for replacement under standard company warranties must be properly tagged with Raypak return parts tag, completely filled in with the heater serial number, model number etc., and shipped to Raypak freight prepaid. Circulator Replacement 1. Shut-off electrical power to the boiler. 2. Shut-off water supply and open drain valve to remove water in the piping at the pump level. If determined defective by Raypak and within warranty, the part will be returned in kind or equal substitution, freight collect. Credit will not be issued. CAUTION: To avoid damage to electrical components, keep water from getting into the control compartments and gas valve. RAYPAK, INC. 2151 Eastman Avenue Oxnard, CA 93030 3. Disconnect wiring and conduit connections to the pump. 4. Disconnect the bypass tube connections to the inlet flange. 5. Remove the nuts and bolts at the inlet and outlet flanges. Remove old gaskets. 6. Remove the pump. 7. Reverse the above procedure to re-install. Use new gaskets and make sure they are seated properly when tightening the nuts and bolts. 37 LIMITED PARTS WARRANTY RESIDENTIAL HEATING BOILERS MODELS 42 TO 180 Catalog No.: 1910.10H Effective: 01-01-04 Replaces: 05-15-03 SCOPE: Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this boiler which are actually manufactured by Raypak will be free from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this Warranty. Labor charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty but are the owner’s responsibility. ANY PART MANUFACTURED BY RAYPAK: One (1) year warranty from date of boiler installation, or eighteen (18) months from date of factory shipment based on Raypak’s records, whichever comes first. SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. THIS WARRANTY WILL BE VOID IF THE BOILER RATING PLATE IS ALTERED OR REMOVED. HEAT EXCHANGER WARRANTY: Second through tenth years from date of installation, Raypak warrants that the copper and cast iron waterway are free from defects in material and workmanship. If any of these parts are found defective Raypak will replace or repair free of charge subject to conditions listed under “Scope” above. Eleventh through twentieth years from date of installation, Raypak warrants that the copper and cast iron waterways are free from defects in material and workmanship. If any of these parts are found defective Raypak will replace the original parts and payment of a proportionate charge equal to 1/120th of the list price of such parts, at the time the warranty claim is made, for each month, or portion there of, beyond the tenth year. ADDITIONAL WARRANTY EXCLUSIONS: This warranty does not cover failures or malfunctions resulting from: 1. Failure to properly install, operate or maintain the boiler in accordance with our printed instructions provided; 2. Abuse, alteration, accident, fire, flood and the like; 3. Sediment or lime buildup, freezing, or other conditions causing inadequate water circulation; 4. High velocity flow exceeding boiler design rates; 5. Failure of connected systems devices, such as pump or controller; 6. Use of non-factory authorized accessories or other components in conjunction with the boiler system; 7. Failure to eliminate air from, or replenish water in, the connected water system; 8. Chemical contamination of combustion air or use of chemical additives to water; 9. Boilers installed in buildings other that one- or two-family dwellings. PARTS REPLACEMENT: Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested, with transportation charges prepaid, and all applicable warranty conditions satisfied. The replacement part will be warranted for only the unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts manufactured by others, but Raypak will apply any such warranty as may be provided by the parts manufacturers. TO MAKE WARRANTY CLAIM: Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the problem. The installer must then notify a Raypak distributor for instructions regarding the claim. If neither the installer nor the distributor is available, contact Service Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 or call (805) 278-5300. In all cases proper authorization must first be received from Raypak before replacement of any part. EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY: This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak’s behalf. THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITY AND THE SOLE REMEDY AGAINST RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL BE AS PROVIDED IN THIS WARRANTY. IT IS AGREED THAT RAYPAK SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN CONTRACT, TORT, NEGLIGENCE OR OTHERWISE, FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL, DAMAGE, INCLUDING DAMAGE FROM WATER LEAKAGE. Some states do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental or consequential damages. So the above limitation or exclusion may not apply to you. This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We suggest that you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on the date of manufacture plus thirty (30) days. _____________________________________________________ Name of Owner _____________________________________________________ Address _____________________________________________________ ______________________________________________ Name of Installer ______________________________________________ Address ______________________________________________ _____________________________________________________ Model No. ______________________________________________ Serial No. Date of Installation_____________________________________ Date of Initial Operation___________________________ RAYPAK, INC. • 2151 Eastman Avenue • Oxnard, CA 93030 • (805) 278-5300 • Fax (800) 872-9725 • www.raypak.com P/N: 240419 38 39 www.raypak.com Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468 Litho in U.S.A.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : No Page Count : 40 X Press Private : %%DocumentProcessColors: Cyan Magenta Yellow Black.%%EndComments Creator : QuarkXPress(R) 7.5 Producer : QuarkXPress(R) 7.5 Create Date : 2009:09:09 09:46:07 Modify Date : 2009:09:09 09:46:07 Title : 6000.59 - New RP2100.qxdEXIF Metadata provided by EXIF.tools