Remeha Avanta Plus Gas 210 Technical Information
2015-05-27
: Remeha-Avanta-Plus Remeha-Avanta-Plus-Gas-210-Technical-Information-724294 remeha-avanta-plus-gas-210-technical-information-724294 remeha-avanta-plus pdf
Open the PDF directly: View PDF
.
Page Count: 72
| Download | |
| Open PDF In Browser | View PDF |
English EN GAS 210 ECO PRO High efficiency Low NOX gas boiler Types: 210-80 210-120 210-160 210-200 Technical information 114494-04 Table of contents GAS 210 ECO PRO Table of contents Preface 6 1. EC declaration 7 2. Introduction 2.1 Pictograms used 2.2 Important instructions 8 8 8 3. Safety 9 4. Installation 4.1 Scope of delivery and installation 4.2 Dimensions 4.3 Installation and service clearances 10 10 11 12 5. Water-side connections 5.1.1 Condensed water discharge 5.1.2 Water treatment 5.1.3 Pressure relief valve 5.1.4 Circulation pump 5.1.5 Water flow 13 13 13 14 14 14 6. Gas-side connections 6.1 Gas connection 6.2 Gas pressure 6.3 Gas/air ratio control 15 15 15 15 7. Connecting the flue gas discharge and air supply 7.1 General 7.2 Conventional open flue installation 7.2.1 Possible lengths for the flue gas discharge pipe 7.3 Room sealed installation 7.3.1 Possible lengths for the air supply and flue gas discharge 7.3.2 Discharge in different pressure areas 7.3.3 Connection of flue gas discharge and choice of material 7.3.4 Air supply connection and choice of material 7.3.5 Additional Directives 16 16 16 17 18 18 20 21 21 21 8. Control and electrical connections 8.1 General 8.1.1 Boiler control 8.1.2 Modulating controls general 8.1.3 Modulating room control 8.1.4 Modulating weather-compensated control rematic® 8.1.5 Modulating cascade controller MC4 8.2 Electrical specifications 8.2.1 Mains voltage 8.2.2 Control box 8.2.3 Fuse ratings 8.3 Electrical connection options 8.3.1 Connection options of standard control unit (PCU-01) 8.3.2 On/off control (OT) 8.3.3 Modulating controls (OT) 8.3.4 External interlock (BL) 8.3.5 Input release (RL) 8.3.6 Circulation pump (Pump) 8.3.7Connecting a PC 22 22 22 22 22 22 23 23 23 23 24 24 24 24 24 24 25 25 25 2 114494-03 GAS 210 ECO PRO Table of contents 8.3.8 Connection options for the PCB - SCU - X01 8.4 Connection options for the optional 0 - 10 V control PCB (IF-01) 8.4.1 Connection status (Nc) 8.4.2 OTm connection 8.4.3 Analogue input (0 - 10 V) 8.4.4 Analogue output (0 - 10 V) 8.5 Connection options of the optional expanded control/protection PCB (SCU-S01) 8.5.1 Flue gas damper control (FgV) 8.5.2 Hydraulic valve control (HdV) 8.5.3 External gas valve control (EgV) 8.5.4 Operation signal and failure signal (Nc / No) 8.5.5 Water pressure sensor (Wps) 8.5.6 Outside temperature sensor (Tout) 8.5.7 Minimum gas pressure switch (Gps) 8.5.8 Gas leakage control (VPS; only for 210- 160 and 210- 200 boilers) 8.5.9 Wiring diagram 25 26 26 26 27 27 28 28 28 28 28 28 29 29 29 30 9 Commissioning 9.1 Control panel 9.1.1 Normal start-up procedure 9.1.2 Fault during start-up procedure 9.1.3 Reading current values 9.1.3.1 Status and sub status 9.1.4 Adjusting the boiler to the system 9.1.5 Changing parameters at user level (without access code) 9.1.6 Changing parameters at service level (with access code) 9.1.7 Resetting factory settings 9.1.8 Setting manual operation ( symbol) 9.2 Commissioning 9.3 Taking the boiler out of operation 9.3.1 Boiler with frost protection, out of operation for a long time 9.3.2 Boiler without frost protection, out of operation for a long time 31 31 31 32 33 34 34 35 35 38 39 39 42 42 42 10. Inspection and maintenance 10.1 General 10.2 Combustion check of the boiler 10.2.1 Corrective maintenance 10.2.2 Cleaning the fan 10.2.3 Cleaning the heat exchanger (flue gas side) 10.2.4 Cleaning the burner 10.3 Cleaning the trap 10.4 Checking the ignition electrode 10.5 Checking for leaks 10.6 Checking water pressure 10.7 Putting boiler back into operation 43 43 43 43 44 46 47 48 48 48 48 48 11. Control stops and faults 11.1 General 11.2 Control stops and faults 11.3 Control stop codes 11.4 Fault codes 11.5 Control stop - and fault memory 11.5.1 Reading faults 11.5.2 Deleting control stops or faults 49 49 49 49 51 54 55 55 114494-03 3 Table of contents GAS 210 ECO PRO 12. Service parts 12.1 General 12.2 Exploded view 56 56 57 13. Regulations 13.1 General 13.2 Standards 13.3 Remeha factory test 13.4 Supplementary guidelines 58 58 58 58 59 14. Technical specifications 14.1 Technical data 60 60 15. Efficiency data and gas inspection labels 15.1 Unit usable efficiency (HR efficiency) 15.2 Water-side efficiency 15.3 Zero-load losses 15.4 Description of specifications 15.5 Accessories 15.6 Services 15.7 Type of unit 15.8 Operating principle 15.9 Boiler Control 15.9.1 Temperature control 15.9.2 Low water level protection 15.9.3 Maximum protection 15.9.4 Frost protection 61 61 61 61 61 62 62 63 64 64 64 64 65 65 16. Application data 16.1 General 16.2 Air and flue gas application options 16.3 Hydraulic application options 16.4 Cascade application 16.5 Control options 16.6 Gas application options 66 66 66 66 66 69 69 17. Checklists (records) 17.1 Checklist for commissioning (Commissioning record) 17.2 Checklist for annual inspection (inspection record) 17.3 Checklist for maintenance (maintenance record) 70 70 70 71 4 114494-03 GAS 210 ECO PRO 114494-03 Table of contents 5 Preface GAS 210 ECO PRO Preface Preface This technical information , which contains a lot of practical information about the Remeha Gas 210 ECO PRO, a High efficiency central heating unit, is mainly intended for installers. It contains important instructions for safe and trouble-free operation of the boiler before commissioning and during operation. Read these instructions carefully before putting the boiler into operation, familiarise yourself with its control functions, operation and strictly observe the instructions given. Failure to do so may invalidate warranty or prevent the boiler from operating. The boiler is available in the following types: - Gas 210 ECO PRO 80 (3 sections; 87 kW) - Gas 210 ECO PRO 120 (4 sections; 120 kW) - Gas 210 ECO PRO 160 (5 sections; 166 kW) - Gas 210 ECO PRO 200 (6 sections; 200 kW) The installation, commissioning, inspection and servicing of the boiler must be carried out by a competent Corgi registered engineer who holds valid A.C.S. certification and in accordance with current gas safety (installation and use) regulations, the building regulations and all other relevant codes of practice. All electrical work must be carried out by a competent engineer and to be installed in accordance with the current IEE regulations. If you have any questions, require an engineer to call on site, or if you need more information about specific subjects relating to this boiler, or it's installation please do not hesitate to contact our technical help line 0118 978 3434. When contacting Broag with a problem on the boiler, please have available the boiler type, Serial No (located on the bottom of the casing), and the symptoms or fault code (the fault code is a series of flashing digits in the display panel). The data published in these technical instructions is based on the latest information (at date of publication) and may be subject to revisions. We reserve the right to continuous development in both design and manufacture, therefore any changes to the materials or technology employed may not be retrospective nor may we be obliged to adjust earlier supplies accordingly. 6 114494-03 GAS 210 ECO PRO 1. EC declaration 1. EC declaration EC - DECLARATION OF CONFORMITY Manufacturer : Remeha B.V. Address : Kanaal Zuid 110 City, Country : Postbus 32, NL-7300 AA Apeldoorn, Holland - this is to declare that the following product(s) : Remeha Gas 210 ECO PRO is/are in conformity with the following EEC-directives: EEC- Directive: 90/396/EEC tested and examined to the following norms: EN 656 A1(2006), EN 15417(2006) 15240(2006) 92/42/EEC 73/23/EEC DIN EN 50165(2001), EN 50165(1997 + A1: 2001) DIN EN 60335-1(2003), EN 60335-1(2002) 07 89/336/EEC EN 55014-1(2000+A1:2001), 55014-2(1997+A1:2001) EN 61000-3-2(2000+A2:2005), 61000-3-3(1995+A1:2001) 97/23/EEC (article 3, sub 3) Apeldoorn, aug. 2007 W.F. Tijhuis Approval manager 114494-03 7 2. Introduction GAS 210 ECO PRO 2. Introduction 2.1 Pictograms used The following pictograms are used in this document to emphasise certain instructions. This is in order to increase your personal safety and to safeguard the technical reliability of the boiler. The pictograms used are: Useful advice. Important instruction for carrying out an action. Possible risk of bodily injury or material damage to boiler, building or environment. Possible risk of electrical shocks. Serious bodily injury may occur. 2.2 Important instructions The boiler must be installed in a frost-free area. Work on the boiler Installation, commissioning, maintenance and repair work may only be carried out by suitably qualified specialist installers in accordance with the applicable national and local standards and guidelines.Always disconnect the mains supply and close the main gas cock when working on the boiler. Check the entire system for leaks after maintenance and servicing work. Casing panels may only be removed for maintenance and servicing purposes. Refit all panels on completion of maintenance and servicing work. Instruction and warning labels on the boiler must never be removed or covered and must be clearly legible throughout the entire service life of the boiler. Replace damaged or illegible instruction and warning labels immediately. Generally applicable safety instructions related to accident prevention must be consulted in addition to the information supplied in this technical documentation. Boiler modifications Modifications to the boiler require the written approval of Broag. Keep this document near to the installation. 8 114494-03 GAS 210 ECO PRO 3. Safety 3. Safety Adhere strictly to the specific safety instructions. Can you smell gas? Proceed as follows: • do not smoke and avoid fire and sparks • do not operate electrical switches. • close the gas cock. • open doors and windows. • trace possible leaks and seal them off. • if the leak is upstream of the gas meter, notify National Gas Emergency Service tel: 0800 1110999. Can you smell flue or combustion gases? Proceed as follows: • isolate the mains power supply from the boiler. • open doors and windows. • trace possible leaks and seal them off. 114494-03 9 4. Installation GAS 210 ECO PRO 4. Installation 4.1 Scope of delivery and installation The boiler is supplied fully assembled and protected. The boiler is placed on a pallet (70 x 130 cm, 145 cm high), which can be transported with a pallet truck, hand truck, forklift truck or 4-wheel transport boards. The packaging passes through all standard doors (minimum width of 74.5 cm). The boiler is installed as follows: - Position the pallet with the boiler in the boiler room; - Remove the fixing bands and all other packaging (some components are packaged in the polystyrene cap); - Lift the boiler from the pallet; - Slide the boiler into the required position, using the recessed handles in the boiler base; - Cover the boiler and do not operate it whilst dust creating construction processes or insulation to the pipe work etc. are carried out in the plant room. 10 114494-03 GAS 210 ECO PRO 4. Installation 125 4.2 Dimensions 140 140 61 121 1070 61 152 316 1200 1272 305 A 160 1190 450 114492LTAL21H001b fig. 01 Elevation drawings Connection É Flow Gas 210 ECO PRO 80/120/160 1¼” male thread Gas 210 ECO PRO 200 1½” male thread (fit supplied adapter 1¼” > 1½”) Ê Return 1¼” male thread 1½” male thread (fit supplied adapter 1¼” > 1½”) Gas connection 1¼” male thread 1¼” male thread Ò Condensate drain Ø 32 mm external Ø 32 mm external Ð Combustion air supply Ø 150 mm Ø 150 mm Ñ Flue gas outlet Dimension “A” Ø 150 mm 1309 mm 1¼” male thread Ø 150 mm 1324 mm 1¼” male thread Ì Second return (option) 114494-03 11 4. Installation GAS 210 ECO PRO 4.3 Installation and service clearances Clearance of at least 60 cm is required at the front of the boiler. However, we recommend a clearance of 1 m. We recommend a clearance of at least 40 cm above the boiler control panel, at least 5 cm on the left side and at least 25 cm on the right side in connection with condensed water discharge. Install a gas cock in the immediate vicinity of/above the boiler. 1 2 1490 250 50 1190 250 250 600 1050 600 1050 3 4 2100 450 1890 450 600 450 1190 250 1190 50 250 1690 1190 450 250 600 1690 1190 450 1190 450 50 2930 114492LTAL21H002a fig. 02 12 Boiler room installation options 114494-03 GAS 210 ECO PRO 5. Water-side connections 5. Water-side connections 5.1.1 Condensed water discharge Discharge the condensed water directly into a foul water drain. In view of the acidity level of condensate (pH between 3 and 5), only use plastic material for the discharge pipe. After assembly, fill the trap with clean water. Make an open connection with the drain. The discharge pipe must slope down by at least 30 mm/m. Condensed water must not be discharged into gutters or rain water down pipes. 5.1.2 Water treatment • Use untreated tap water only to fill the CH system. • The pH value of the system water must be between 7 and 9. • Where inhibitors are being used, please refer to Broag recommendations in this section and follow the manufactures instructions given. If used correctly water treatment can improve the boilers efficiency and increase the anticipated life expectancy of the boiler. For further information a special document “Remeha water quality regulations” is available from Broag. The regulations mentioned in this document must be followed. As most systems contain a variety of metals, it is considered good practice to provide some form of water treatment in order to prevent or reduce the following: • Metallic corrosion • Formation of scale and sludge • Microbiological contamination • Chemical changes in the untreated system water All scale deposits, however small, will reduce the efficiency of the boiler and should be prevented. Suitable chemicals and their use should be discussed with a specialist water treatment company prior to carrying out any work (environmental aspects, health aspects). The specification of the system and manufacturers recommendations must be taken into account, along with the age and condition of the system. New systems should be flushed thoroughly to BS 7593(1992) to remove all traces of flux, debris, grease and metal swarf generated during installation. Care to be taken with old systems to ensure any black metallic iron oxide sludge and other corrosive residues are removed, again by power flushing, ensuring that the system is drained completely from all low points. Please ensure that the new boiler plant is not in circuit when the flushing takes place, especially if cleansing chemicals are used to assist the process. 114494-03 13 5. Water-side connections GAS 210 ECO PRO It is important to check the inhibitor concentration after installation, system modifications, filling the system and every service in accordance with these instructions. For the correct dosage and the suitability of inhibitors for use with our boilers and for further information on water treatment or system cleaning we advise direct contact with either of the following companies: ‘Copal ®’ manufactured by: Fernox, Cookson Electronics Forsyth Road Sheerwater Woking Surrey GU21 5RZ Tel No: 01483 793200 Fax No: 01483 793201 Email: sales@fernox.com Website: www.fernox.com or: Sentinal ‘X100®’ manufactured by: Sentinel Performance Solutions The Heath Business & Technical Park Runcorn Cheshire, WA7 4QX Tel No: 0800 389 4670 Fax No: 0800 389 4677 Email: info.uk@sentinel-solutions.net Website: www.sentinel-solutions.net 5.1.3 Pressure relief valve Install an pressure relief valve in the system, in accordance with NEN 3028, between any valves and the boiler and in the flow pipe within 0.5 m of the boiler. 5.1.4 Circulation pump P (%) The boiler is equipped with a pump switch to connect an external circulation pump. This pump is run once every 24 hours to prevent sticking (24 hour pump operation). Only on/off pumps can be controlled. For connections, see Section 8.3.6. The hydraulic resistance for the various output options of the boiler is as follows: V Boiler type D 0 10 20 30 35 40 210-80 210-120 210-160 210-200 Hydraulic resistance at Hydraulic resistance at a dT a dT of 20°C of 10°C mbar kPa mbar kPa 165 16,5 545 54,5 135 13,5 446 44,6 170 17,0 562 56,2 180 18,0 595 59,5 ∆T (°C) 114492LTAL21H031 fig. 03 Output control characteristic V = full load D = part load 14 P = heat output ∆T = temperature difference 5.1.5 Water flow The maximum temperature difference between flow and return, and the maximum rate of rise of the flow temperature and boiler block temperature are limited by the boiler's modulating controls. As a result, the boiler is virtually unaffected by low water flow. However for a continuous supply of heat, the boiler requires a minimum flow of 30 % of the nominal flow at the relevant design temperatures. 114494-03 GAS 210 ECO PRO 6. Gas-side connections 6. Gas-side connections 6.1 Gas connection The boiler is suitable for use with natural gas and propane* category II2H3P. For other types of natural gas, consult our Technical department. All gas appliances must, by law, be installed by competent persons (e.g. Corgi). Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to ensure that the law is complied with. The gas connection is at the top of the boiler. We recommend installing a gas filter in the gas supply pipe to avoid pollution of the gas multiblock. The gas filter's resistance must not be so high that the minimum inlet gas pressure can no longer be achieved. * Refer to Broag for using propane. 6.2 Gas pressure 3+4 L 5+6 L The boiler has been factory set and tested by Remeha to natural gas (G20) - with an inlet pressure of 17 mbar. The boiler is suitable for 17 - 30 mbar inlet gas pressure. For propane (LPG), an inlet pressure of 37 - 50 mbar is required. 114492LTAL21H003a fig. 04 Gas multiblocks 6.3 Gas/air ratio control The boiler has a zero governor gas valve. This gas valve maintains the ratio between the gas and air quantities in the burner at a constant level under variable loads. This ensures clean and reliable combustion and high efficiency across the entire load range. 114494-03 15 7. Connecting the flue gas discharge and air supply GAS 210 ECO PRO 7. Connecting the flue gas discharge and air supply 7.1 General The Remeha Gas 210 PRO is suitable for conventional room ventilated or room sealed operation. Specify at the time of ordering if the boiler is to be supplied for room sealed operation. In that case, the boiler will be supplied with a purpose-designed room sealed terminal, air supply connection and some accessories. The air supply connection should rest on the heat exchanger underneath the boiler casing after removing the standard perforated air inlet cover. Horizontal components in the flue gas discharge system should slope towards the boiler. Horizontal components in the air supply system should slope towards the supply opening. Room sealed terminals should comply with the national requirements for both horizontal and vertical outlet constructions. Care should be taken when siting flue exit positions as a vapour plume will be visible when the boiler is operational (flue gas temperature will be less than 80°C resulting in the water vapour condensing out on contact with the air). Classification due to discharging flue gases The boiler is approved according to CE with classification: Type B23: Conventional room ventilated appliance without draft diverter. Air supply from boiler room; flue gas discharge on roof. Type B23P: Conventional room ventilated boiler without draft diverter. Air supply from boiler room: flue gas discharge on roof, metal flue gas discharge with CE symbol, meets pressure class P1. Type C13: Room sealed boiler, connected to combined wall outlet. Type C33: Room sealed appliance, connected to combined roof outlet. Type C43: Room sealed appliance in cascade configuration, connected via two ducts to a common duct system serving more than one appliance. Type C53: Room sealed appliance, connected to separate ducts for the air supply and flue gas discharge, terminated in zones of different pressure. Type C63: Room sealed appliance, supplied without the terminal or the air supply and flue gas discharge ducts. Type C83: Room sealed appliance, connected to separate air supply and flue gas discharge duct, with flue gas discharge duct always in underpressure. 7.2 Conventional open flue installation The open flue version extracts the necessary combustion air from the plant room or compartment. A table showing the maximum discharge lengths can be found in Section 7.2.1. 16 114494-03 GAS 210 ECO PRO 7. Connecting the flue gas discharge and air supply • The air supply opening must stay open. • The installation area or boiler room must be equipped with the necessary combustion air supply openings. These openings must not be obstructed or shut off. • The combustion air supply must be free of dust and chemically aggressive agents (such as trichloroethylene or halogenated hydrocarbons), as used in aerosol cans, certain types of adhesive, certain solvents and cleaning agents, and paint, etc. 7.2.1 Possible lengths for the flue gas discharge pipe Conventional room ventilated, type B23 according to CE. Maximum permitted flue gas discharge lengths (L) in m Boiler type D (mm) Free discharge 100 18 210-80 110 35 130 + 210-120 110 130 150 20 48 + 210-160 130 150 180 22 45 + 210-200 130 150 180 14 31 + table 01 Flue gas discharge table for the open version + = Lengths up to 50m possible. For longer lengths, consult our Technical department When flue gas discharge pipes with diameters other than 150 mm are used, an adapter is required: Ø150/100mm, Ø150/110mm, Ø150/130mm or Ø150/180mm. fig. 05 Piping for the conventional room ventilated For each additional 90° or 45° bend, the pipe length must be reduced by the amount shown in table 02. D in mm Ø Ø Ø Ø Ø 100 110 130 150 180 table 02 114494-03 R=½D R=½D R=D R=D R=D 90° bend 4.9 5.4 1.8 2.1 2.5 length in m 45° bend 1.4 5.1 1.0 1.2 1.4 Metres to be deducted per bend 17 7. Connecting the flue gas discharge and air supply GAS 210 ECO PRO 7.3 Room sealed installation The room sealed installation is based on the use of an air supply pipe connected directly to the boiler. This increases the number of installation options within a building, while the discharge location is subject to less stringent requirements because the air supply and flue gas discharge can be incorporated in the same pressure field. Additional ventilation will be required to the room/compartment in accordance with BS 6644-2005 (compartment ventilation). In addition, air from outside is usually cleaner, which has a beneficial effect on the boiler service life. An air supply and flue gas discharge table for the enclosed version of the boiler can be found in table 03. For discharge in two different pressure fields, see Section 7.3.2. The boilers can be installed on a flue dilution system, but must have a total flue break to avoid boiler controls being affected by the flue dilution fan pressures. For full details please contact Broag. 7.3.1 Possible lengths for the air supply and flue gas discharge Room sealed appliance, type C33 according to CE. Maximum acceptable flue gas discharge/air supply pipe lengths (L) in m Calculated with Boiler Pipe Ø D concentric roof feedModel (mm) [m] through Dnominal (mm) 100 100 8 130 130 + 210-80 130 150 + 150 150 + 210-120 100 130 130 150 100 130 150 150 3 22 25 + 210-160 130 150 180 150 150 150 11 22 130 150 180 130 150 150 4 13 + 210-200 + table 03 Air supply and flue gas discharge table for the enclosed version 0021H7900017 fig. 06 18 += Lengths up to 30m possible. For longer lengths, consult our Technical department Piping for the room sealed appliance 114494-03 GAS 210 ECO PRO 7. Connecting the flue gas discharge and air supply When air supply and flue gas discharge pipes with diameters other than 150 mm are used, adapters are required: Ø150/100mm, Ø150/110mm, Ø150/130mm or Ø150/180mm and, for connection to our standard combined vertical roof feed-through sets, also Ø180/150mm, Ø130/150mm or Ø110/150mm. For each additional 90° or 45° bend, the pipe length must be reduced by the amount shown in table 04. D in mm Ø Ø Ø Ø Ø 100 110 130 150 180 table 04 90° bend R=½D R=½D R=D R=D R=D length in m 4.9 5.4 1.8 2.1 2.5 45° bend 1.4 5.1 1.0 1.2 1.4 Metres to be deducted per bend For enclosed versions, combined vertical roof feed-through sets are available, as well as sealing plates for flat roofs, in accordance with the following drawings. Please consult our Technical department for this option. Epoxy layer Int Int Ext Ext Ext Ext fig. 07 Vertical roof feed-through for room sealed operation Pdf dakdoorvoer 114494-03 19 7. Connecting the flue gas discharge and air supply GAS 210 ECO PRO 7.3.2 Discharge in different pressure areas For installations where supply and discharge points are in two different pressure zones CLV system please contact Broag Technical Dept. for further details and advice. The maximum acceptable height difference between combustion air supply and flue gas discharge is 36 m and the maximum acceptable length of the air supply and flue gas discharge combined is shown in table 05. fig. 08 Discharge in different pressure areas Maximum permitted flue gas discharge and air supply pipe lengths Boiler model D in mm L in m 210-80 150 36 210-120 150 36 210-160 150 23 210-200 150 11 table 05 Air supply and flue gas discharge table for 'simplified CLV system' 20 114494-03 GAS 210 ECO PRO 7. Connecting the flue gas discharge and air supply 7.3.3 Connection of flue gas discharge and choice of material Connecting the flue gas discharge: Remove the cap from the flue gas discharge opening Ñ; • Fit the flue gas discharge pipes seamlessly together. • Seams and joints must be airtight and watertight or fit seamlessly. • Horizontal parts must be oriented towards the boiler at a gradient (min. 5 cm per metre). • Connect the pipes stress-free. • Flue gas discharge pipes longer than 2 m must be fixed separately and must not rest on the boiler. Flue gas discharge: Material: Rigid single walled: stainless steel (316), aluminium or plastic (to comply with building regulations). Flexible: stainless steel (316). Construction: all joints and seams should be gastight and watertight with the horizontal runs graded towards the boiler (min. discharge 5 cm per meter) to allow condensate free drainage to the boiler. Flue gas discharges longer than 2 meters must be supported independently and may not rest on the boiler. The flue outlet should terminate with reduction cone and bird guard only (chinamans hat or GLC type terminals etc. should not be used). 7.3.4 Air supply connection and choice of material Connecting air supply: Remove air supply grille from the air supply opening Ð; • Fit the air supply pipes seamlessly together. • Seams and joints must be airtight and watertight or fit seamlessly. • Horizontal parts must be oriented towards the discharge at a gradient (min. 5 cm per metre). • Connect the pipes stress-free. Air supply: Material: Single walled, rigid or flexible: aluminium, stainless steel and plastic (to comply with building regulations). Air supply ducts longer than 2 meters must be supported independently and may not rest on the boiler air inlet. Care must be taken to ensure that if water is able to enter the duct it will run away from the boiler air inlet connection or supply a suitable train c/w water seal trap. 7.3.5 Additional Directives Please refer to the manufacturer’s instructions for the material in question when installing the flue gas discharge and air supply materials. If the flue gas discharge and air supply materials are not installed according to the instructions (e.g. they are not leakproof, not clamped in place etc.), this may cause hazardous situations and/or result in bodily injury. After assembly, check at least all flue gas and air–carrying parts for tightness. 114494-03 21 8. Control and electrical connections GAS 210 ECO PRO 8. Control and electrical connections 8.1 General The boiler is equipped with electronic control and safety equipment with ionisation flame protection. The advanced boiler control (abc®), is a microprocessor that protects and controls the boiler. The boiler is fully prewired; all external connections are made on the terminal strips. Connect the boiler to the mains supply in accordance with the local electricity supplier's instructions and IEE regulations. 8.1.1 Boiler control The heat output of the Remeha Gas 210 ECO PRO can be controlled as follows: - Modulating, where the output modulates between the minimum and maximum values on the basis of the flow temperature defined by the modulating controller. - On/off control, where the heat output modulates between the minimum and maximum values on the basis of the flow temperature set in the unit. This can be combined with an outside sensor so that the internal heating curve is used. - Analogue control (0-10 V), where the heat output or temperature is controlled by a 0‑10 V signal, see Section 8.4.4. Only possible with optional 0 - 10 V control PCB (IF-01). 8.1.2 Modulating controls general The modulating nature of the boiler is used to maximum effect with a modulating controller based on room and/or outside temperatures. If the controller demands heat, the boiler supplies the heat output. If the controller demands a flow temperature, the boiler modulates to this value. This increases the number of operating hours and drastically reduces the number of starts. Combined with the fixed gas/air mixture, this results in greater efficiency. Various types of modulating controls can be connected, including the following: - Modulating room control, see Section 8.1.3; - Modulating weather-compensated control see Section 8.1.4; - Modulating cascade control, see Section 8.1.5. 8.1.3 Modulating room control The boiler is set up for communication via the OpenTherm protocol. Modulating controllers can be connected according to the OpenTherm protocol, e.g. the Remeha iSense. The controller is mounted in a reference area. Connection is made with a two-core cable to the On/off - OT terminals of terminal strip X6 (not polarity sensitive). 8.1.4 Modulating weather-compensated control rematic® The following optional controller can be supplied by Broag-Remeha. The controller is supplied with a connection adapter and interface that are built into the boiler. The connections for this feature are fully pre-wired. 22 114494-03 GAS 210 ECO PRO 8. Control and electrical connections rematic® 2945 C3 K In addition to the weather-compensated boiler pre-control, this controller provides optimum start, dual zone weather compensation and priority DHW (if required). Fit the controller in the boiler. Connection takes place using the supplied rematic® adapter and the supplied interface that can be integrated in the control panel. Refer to the relevant controller documentation for detailed information. 8.1.5 Modulating cascade controller MC4 The Remeha Celcia MC4 cascade controller is suitable for the modulated control of 2 to 4 Remeha Gas 210 PRO boilers in cascade. This controller is wall-mounted and communicates according the OpenTherm protocol. We recommend using our Celcia MC4 modulating cascade controller in conjunction with the iSenseTime/ Weather compensation controller. Refer to the relevant controller documentation for detailed information. iSense with MC4 will only control up to 4 boilers in cascade 8.2 Electrical specifications 8.2.1 Mains voltage The boiler is suitable for a 230 V-50 Hz supply with live/neutral/ earth (the control is phase/neutral sensitive). Other connection values are only acceptable if an isolating transformer is installed. Connect the mains lead (not supplied) to the 230 V terminal strip. 8.2.2 Control box 230Vac, 50Hz, F6.3AT L N Mains voltage : 230 V/50 Hz Power consumption at: stand-by/low load/full load: - 210-80 : 4 / 36 / 125 W - 210-120 : 4 / 37 / 193 W - 210-160 : 4 / 53 / 206 W - 210-200 : 4 / 54 / 317 W Safety time: 3.5 s Anti-hunting time: Adaptive 1 - 10 minutes. Pump post-circulation time: adjustable between 0 and 98 minutes or continuous (= 99 minutes), set by default to 3 minutes Max. power consumption of external pump: 300 VA. 8.2.3 Fuse ratings 114492LTAL21H004a fig. 09 Connect mains lead 114494-03 The 230 V terminal strip contains the fuse F - 6.3 AT. This is a general fuse for all connected components. The control unit contains the fuse F1 - 1.6 AT. This is a fuse for the mains voltage of the control unit, gas multiblock and ignition, excluding pump. 23 8. Control and electrical connections GAS 210 ECO PRO 8.3 Electrical connection options The boiler has several control, protection and regulation connection options. The standard control PCB (PCU-01) can for example be expanded with: • an optional 0 - 10 V control PCB (available as an accessory IF-01); • and/or the optional expanded control/protection PCB (available as an accessory SCU-SO1). To install or access these PCBs, the plastic cap must be removed from the control panel. The required external connections are made on these (optional) PCBs. The various connection options are detailed in the following sections. 8.3.1 Connection options of standard control unit (PCU-01) Connected on the standard control unit (PCU-01) is the safety unit (SU) connected, which protects the boiler. 2 1 4x 8.3.2 On/off control (OT) The boiler is suitable for connection to a ‘volt free’ on/off controller. Connect the controller to the On/off - OT terminals of terminal strip X6 (not polarity sensitive). 8.3.3 Modulating controls (OT) The boiler is set up for communication via the OpenTherm protocol. Modulating controllers can be connected. Connection is made with a two-core cable to the On/off - OT terminals of terminal strip X6 (it does not matter which wire is connected to which cable clamp). 8.3.4 External interlock (BL) X4 X3 NL BL BL OT X5 OT 1.6 AT Mains F1 on/of X2 Pump N L Pump N L SU The boiler has an external interlock switch, so that the boiler can be shutdown in the event that this switch is not made. This input can be used in combination with a flue gas thermostat (available as an accessory). This input relates to the BL terminals of terminal strip X6. Remove the wire bridge before using the input. The input's behaviour depends on the parameter 33 setting: 1 = Normal shutdown; 2 = Shutdown without frost-protection (= default); 3 = Lock out. RL X11 X10 X9 X11 X10 X9 X6 X8 X7 RL PCU-01 X1 114492LTAL21H005e fig. 10 Standard control PCB (PCU-01) with safety unit (SU) 24 114494-03 GAS 210 ECO PRO 8. Control and electrical connections 1.6 AT X5 The boiler is also equipped with an input release so that the burner can be released/shutdown. This input can be used in combination with the limit switches on flue gas throttle valves, hydraulic control valves, safety interlocks, etc. This input relates to the RL terminals of terminal strip X6. N L Mains F1 8.3.5 Input release (RL) Pump N L Pump N L X4 X3 X2 PCU-01 X10 X9 X7 X8 ww w. re Recom 8.3.6 Circulation pump (Pump) RL BL X11 X6 BL X9 OT X10 on/of X11 OT RL X1 A pump with the following specifications can be connected: - On/off pump with a mains voltage of 230 VAC (50 Hz) and 300 VA (maximum). me ha Connect the pump to the Pump terminals of terminal strip X4. The post-circulation time of the circulation pump at the end of a heat demand can be set according to requirements by means of a program option at user level, see Section 9.1.6. .co m 8.3.7 Connecting a PC T000058 fig. 11 Using the optional Recom interface package a PC can be connected to the X7 “telephone connector”. Using the Recom software you can load, change and download various boiler settings and readings. See the user instructions supplied with the software. Connecting a PC 8.3.8 Connection options for the PCB - SCU - X01 X3 0 1 9 7 8 0 1 5 6 7 8 Status Nc C No Nc C No 9 4 2 3 X2a X4 5 6 SCU-X01 The PCB - SCU - X01 is equipped with two potential-free outputs that have a capacity of max. 230 VAC/5 A reactive/2 A inductive (cos 0.6). It also has two rotary switches with ten positions. See the table below for the rotary switch settings. 4 Status Nc C No Nc C No 2 3 X2 T002747-A Nr 0 Description Alarm Standby C-NO Active C-NC 114494-03 1 2 3 4 5 6 7 8 9 Burning Burning inverted Burning low Burning high Service report CHmode DWHmode CHpump C-NC C-NO C-NC C-NO C-NO NA NA NA C-NO C-NO C-NC C-NO C-NC C-NC NA NA NA C-NC Alarm inverted = fail safe 25 8. Control and electrical connections GAS 210 ECO PRO 8.4 Connection options for 0 - 10 V control PCB (IF-01) 8.4.1 Connection status (Nc) If the boiler locks out, a relay is de-energised and the alarm can be transmitted via a potential-free contact (maximum 230 V, 1 A) on terminals Nc and C of terminal strip X4. 8.4.2 OTm connection IF-01 X1 X4 0 + 0 + OTm Nc C No X5 0-10 0-10 % OTm 0 + 0 + 2 Status 1 Nc C No The interface uses OpenTherm to communicate with the boiler control. The OTm connection on terminal strip X5 must therefore be connected to the OpenTherm OT input of the boiler control. 114492LTAL21H006a fig. 12 26 Jumper 2 114494-03 GAS 210 ECO PRO 8. Control and electrical connections 8.4.3 Analogue input (0 - 10 V) 2 2 1 2% This control can be based on temperature or heat output (optional). The two controls are described briefly below. Connect the 0 - 10 V signal to the interface input for analogue control. Analogue temperature-based control () The 0-10 V signal controls the boiler flow temperature between 0°C and 100°C. This control modulates on the basis of flow temperature, where the heat output varies between the minimum and maximum values on the basis of the set point flow temperature calculated by the controller. Jumper (2) on the interface is used to select either temperature () or boiler output (%) control. 114492LTAL21H023a fig. 13 Jumper 2 Jumper 2 table 06 Input signal [V] Temperature [°C] Description 0 - 1,5 0 - 15 Boiler off 1,5 - 1,8 15 - 18 Hysteresis 1,8 - 10 18 -100 Desired temperature Analog input signal for temperature Analogue output-based control (%) The 0-10 V signal controls the boiler output between 0% and 100%, where the minimum and maximum values are limited. The minimum output is linked to the boiler's modulation depth. This control is output modulated, where the output varies between the minimum and maximum values on the basis of the value defined by the controller. Jumper 2 Ingput signal Boiler output Description [V] [%] 0 - 2,0* 0 - 20 Boiler off 2,0 - 2,2* 20 - 22 Hysteresis % 2,0* - 10 20 -100 Desired boiler output * Dependent on the minimum modulation dept (fan rotation speeds settings, pre set 20%) table 07 Analogue input signal for boiler output 8.4.4 Analogue output (0 - 10 V) If this feedback message is received, temperature or heat output can be selected. The two are described briefly below. 1 1 1 2% Jumper (1) on the interface is used to select either temperature () or boiler output (%). Jumper 1 114492LTAL21H024a fig. 14 Jumper 1 114494-03 Output signal [V] 0,5 1- 10 Temperature [°C] 10 - 100 Description Alarm Delivered temperature table 08 Analogue output signal for temperature 27 8. Control and electrical connections GAS 210 ECO PRO Jumper Output signal Boiler output 1 [V] [%] 0 0 - 15 0,5 15 - 18 % 2,0* - 10 20 - 100 * Dependent on the minimum modulation dept tings, pre set 20%) table 09 Description Boiler off Alarm Delivered boiler output (fan rotation speeds set- Analogue output signal for boiler output 8.5 Connection options of the optional expanded control/protection PCB (SCU-SO1) 8.5.1 Flue gas damper control (FgV) In a cascade configuration, a flue gas damper (available as an accessory) prevents flue gases from being discharged through a non-operating boiler, with flue gas cascade. Therefore, the boiler is suitable for flue gas overpressure systems. Consult our Technical department. Connect the flue gas damper to the FgV terminals of terminal strip X3. Also fit this flue gas damper if flue gases flow back when the boiler is in stand-by mode. The running time of the flue gas damper must be programmed with parameter 29. 8.5.2 Hydraulic valve control (HdV) FgV N L FgV N L F1 HdV N L HdV N L X3 4 AT X1 EgV N L EgV N L 8.5.3 External gas valve control (EgV) Status SCU-S01 Wps O S + O S + Tout GPS VPS Tout Nc C No NcC No X4 If there is a heat demand, an alternating voltage of 230 V 1 A (maximum) becomes available on the EgV terminals of terminal strip X3 to control an external gas valve. The voltage is switched off when the gas multiblock on the boiler closes. 8.5.4 Operation signal and failure signal (Nc / No) X5 GPS VPS X2 114492LTAL21H007c fig. 15 In a cascade configuration, a hydraulic valve prevents heat loss when the boiler is not running. Connect the hydraulic valve to the HdV terminals of terminal strip X3. The running time of the hydraulic valve must be programmed with parameter 28. Expanded control/protection PCB (SCU-SO1). The alarm or operation signal is selected using the relevant parameter 25, see Section 9.1.6. If the boiler is operational, the alarm or operation signal can be switched via a potential-free contact (maximum of 230 V, 1 A) on the No and C terminals of terminal strip X4. If the boiler locks out, the alarm can be transmitted via a potential-free contact (maximum 230 V, 1 A) on terminals No and C of terminal strip X4. 8.5.5 Water pressure sensor (Wps) The water pressure sensor (available as an accessory) shuts the boiler down when the minimum water pressure (0.8 bar) is reached. To activate the water pressure sensor, a minimum pressure must be set with parameter 26 (factory setting 0 = off, see Section 9.1.6.) The pump does not run during this shutdown. 28 114494-03 GAS 210 ECO PRO 8. Control and electrical connections Connect the water pressure sensor to the Wps terminals of terminal strip X5. 0 = Earth or neutral of the power supply S = Signal or output from the sensor + = Supply voltage 8.5.6 Outside temperature sensor (Tout) To take advantage of the boiler's modulating operation during the entire heating season, a Remeha outside temperature sensor (available as an accessory) can be used in combination with an on/off control or connection. Connect the on/off control or connection to the On/off terminals of terminal strip X6 on the standard control PCB (PCU-01) and the outside temperature sensor to the Tout terminals of terminal strip X5 on the optional expanded control/protection PCB (SCU-SO1). The unit modulates with a heat demand from the controller or because of a connection to a flow temperature corresponding to the outside temperature (see heating curve graph). Fitting the outside temperature sensor Fit the external sensor, protected against direct sunlight, to the north or north-west of the building, at a height of at least 2.5 metres from ground level. Do not fit the outside temperature sensor near windows, doors, ventilation grills and extractors, etc. 80 3 60 2 F 40 20 -15 1 0 10 20 114492LTAL21H025b fig. 16 Heating curve graph F = factory setting Heating curve setting The maximum flow temperature setting is also the setting for the ‘top’ of the heating curve, i.e. the required flow temperature for an outside temperature of ‑15°C. The baseline of the heating curve is also adjustable and can be changed at service level, see Section 9.1.6. A linear relationship exists between the outside temperatures mentioned and the corresponding flow temperatures. 8.5.7 Minimum gas pressure switch (Gps) The minimum gas pressure (available as an accessory) switch shuts the boiler down if the inlet gas pressure becomes too low. Connect the minimum gas pressure switch to the Gps terminals of terminal strip X5. The presence of the gas pressure switch must be activated using parameter 27 in the setting mode (see Section 9.1.6). 8.5.8 G as leakage control (VPS; only for 210- 160 and 210- 200 boilers) The gas leakage control checks and controls the safety valves on the gas block via a VPS system. The test takes place when the boiler starts. In the event of a leak in the gas block, the boiler will lock out. Connect the gas leakage control to the VPS terminals of terminal strip X5. The presence of a gas leakage control must be entered using parameter 31, see Section 9.1.6. 114494-03 29 9. Commissioning GAS 210 ECO PRO 8.5.9 Wiring diagram PRIMARY CONTROL UNIT - PCU-01 X01 X02 X03 X04 Pump Mains 1 2 3 1 2 3 4 1 2 3 1 2 3 GY SAFETY UNIT - SU-01 BK BL BL BR BL PE-4 GN/YW GN/YW BL On / Off 1 2 3 X07 RL 4 5 1 PC BK BL BL GN/YW X21 3 1 2 3 BL BR X51 GN/YW BR 1 2 PE-11 BR GN/YW X55 1 SCU-X01 X01 X03 X04 0-10V IF-01 SU-01 PCU-01 X01 PRIMARY CONTROL UNIT - PCU-01 X50 X02 X03 X09 X10 1 2 3 4 1.....6 X11 1 2 3 5 4 6 7 10 8 9 X01 PCU-01 X03 X04 BR YW RD OR X05 X91 1 5 X05 4 WH 2 OR BK BL BR/ GL/ WH WH Fan X02 SCU-S01 X06 P Flow temp. CORD COLORS BL BLUE BL/WH BLUE/WHITE BR BROWN BR/WH BROWN/WHITE YW YELLOW GN/YW GREEN/YELLOW YW/WH YELLOW/WHITE GN GREEN GY GREY OR ORANGE RD RED WH WHITE BK BLACK BK/WH BLACK/WHITE BL/ BK/ WH WH WH GN X04 X07 2 3 Fan Boiler switch on / off N L Power supply 230V,50Hz X02a SCU-X01/ X02 SCU-S01 SU-01 GN/YW BL X50 X05 X11 X10 X09 X08 X235 14 13 12 BR PE-1 1 2 Elektrode X04 GN/YW BL Safety shut-off Safety shut-off valve1 valve 2 PE-12 Ignition transformer PE-7 BK 6 7 5 GN/YW DISPLAY BL 6.3AT GY 2 1 10 BK GN/YW BL X235 11 9 8 10 X08 6 T PE-2 PE-5 X06 OT GN/ YW N L BR PE-6 X05 1.....6 PE-2 1.....6 1 2 3 Nc C No Status 1 2 3 Nc C No Status X03 X04 X02 X02a Return Heat exch. temp. temp. Flue gas pressure switch PSU (Parameter storage unit) SECONDARY CONTROL UNIT - SCU-X01 BL GN/YW N L GN/YW N L N L Wps Tout Gps VPs 2 4 6 8 BK + - + - 0-10V 0-10V Status X05 X04 OTm Nc C No IF-01 30 1 2 3 1 3 2 1.....6 X01 X01 X02 1 2 3 Fgv 4 5 6 Hdv X03 7 8 9 Egv 1 2 3 Nc C No Status X04 1 3 5 7 9 O S + X05 SECONDARY CONTROL UNIT - SCU-S01 (OPTION) T002609-04-C 114494-03 GAS 210 ECO PRO 9. Commissioning 9 Commissioning 9.1 Control panel The boiler's control panel contains four function keys, a menu key, a service engineers key, an on/off switch and a display. 1 2 8 Bar 3 4 5 6 7 114492LTAL21H008a fig. 17 1 2 3 4 = = = = Control panel Display [Menu] key [Service engineers] key [Escape] or [reset] key 5 6 7 8 = = = = [Central heating temperature] or [-] key [+] key [enter] key or [Service] indicator On/off switch The display has four positions and several symbols and provides information about the operating status of the boiler and any faults. Numbers, dots and/or letters may be shown. The symbols in the display above the function keys indicate what the function of the relevant keys is at that moment. If no key is pressed for three minutes, the display lighting switches off and only the and symbols are displayed. Press any key; the current boiler status and the current operating code appear on the display. This is always displayed in the event of a fault. 9.1.1 Normal start-up procedure Switch on the mains supply to the boiler; the Gas 210 ECO PRO will perform the start-up program. The following will appear in succession in the display: - a short display test, whereby all of the display's segments are visible; fXx software version alternating with 1; pXx parameter version; - Afterwards (depending on the operating status), the following may appear on the display: N : L (flashes) : live and nutral wires are wrongly connected; change wires on the 230V terminal strip! 114494-03 31 9. Commissioning GAS 210 ECO PRO With a heat demand: 1 Boiler starts 2 Burner starts 3 Central heating operation; briefly in part load then in full load When a heat demand ceases: 5 Burner stops 6 Boiler stops 0 Stand-by mode table 10 Normal operation 9.1.2 Fault during start-up procedure If nothing appears on the display, check: - the connection of the mains lead; - the main fuse in the instrument box (F = 6.3 AT, 230 V); - the fuse on the control unit (F1 = 1.6 AT, 230 V); - the mains voltage. • A fault code in the display is recognised as follows: the fault symbol appears and the fault code flashes underneath it; • The meaning of this fault code can be found in the fault table, see Section 11.2. • If possible, solve the fault first. • Press the RESET key for 3 seconds to restart the Gas 210 ECO PRO. If the display does not show RESET but SERVICE, the boiler must be switched off and switched on again after 10 seconds before the fault can be reset. 32 114494-03 GAS 210 ECO PRO 9. Commissioning 9.1.3 Reading current values The following current values can be read in the ‘information menu’ - 5t = Status - 5u = Sub status - t1 = flow temperature [°C]; - t2 = return temperature [°C]; - t4 = outside temperature [°C]; (only if outside sensor is connected) - t6 = boiler block temperature [°C]; - 5p = internal set point [°C]; - fl = ionisation current [uA]; - f = fan rotation speed [rpm]; - pr = water pressure [mbar]; - p = relative output supplied [%]; bar % 114492LTAL21H009c fig. 18 Reading current values 114494-03 The current values can be read as follows: • Press the key, the symbol will then flash, confirm with the key; • Press the [+] key again so that 5t appears alternating with 3, the actual status; • Press the [+] key again so that 5u appears alternating with , the actual sub status; • Press the [+] key again so that t1 appears, alternating with, for example, 60°C, the actual flow temperature; • Press the [+] key repeatedly so that the remaining temperatures also appear; • Press the [+] key again so that 5p appears, alternating with, for example, 88°C, an internal set point; • Press the [+] key again so that fl appears alternating with, for example, u, the actual ionisation current; • Press the [+] key again so that ñf appears alternating with, for example, 3000 (rpm), the actual fan rotation speed; • Press the [+] key again until pr appears alternating and, for example, 3.0 bar, the actual water pressure (if no water pressure sensor is connected, --.- bar appears); • Press the [+] key again until p appears and, for example, 78 %, the actual modulation percentage; • Press the [+] key again, the read-out cycle starts again with 5t, etc; • Press the key twice to return to the display with the current operating status. 33 9. Commissioning GAS 210 ECO PRO 9.1.3.1 Status and sub status In the ‘information menu’ the following status and sub status numbers are displayed: Number 0 1 2 3 5 6 8 9 table 11 Status 5t Status Stand-by mode Number 0 1 2 Boiler starts (heat demand) 3 4 10 11 12 13 14 Burner starts 15 16 17 18 19 20 30 31 32 33 34 Burning on central heating operation 35 36 37 38 40 41 42 Burner stop 43 44 45 60 61 Boiler stop (end of heat demand) 62 63 0 Control stop 1 Shutdown xx Settings at service level Sub status 5u Sub status Stand-by mode Anti-hunting Open hydraulic valve Start pump Wait for the correct temperatures for burner start Open external gas valve Fan running Open flue gas damper Pre-ventilation Wait for release signal Burner on VPS gas leakage control For ignition Main ignition Flame detection Intermediate ventilation Temperature control Limited temperature control (∆T safety) Output control Increase protection level 1 (control modulation) Increase protection level 2 (part load) Increase protection level 3 (shut down) Modulate up for flame control Stabilisation time Cold start Burner off Post ventilation Fan running Close flue gas damper Stop fan Close the external gas valve Pump post circulation Pump off Close hydraulic valve Start anti-hunting Wait for burner start Anti-hunting Shutdown xx 9.1.4 Adjusting the boiler to the system The boiler's control parameters are set to the most common central heating systems. With these settings, practically all central heating systems will work well. However, the user or the installer can optimise the parameters as he/she wishes. 34 114494-03 GAS 210 ECO PRO 9. Commissioning 9.1.5 Changing parameters at user level (without access code) 2x The following settings can be changed at user level: p1 = F low temperature set point [°C], adjustable between 20 and 90°C; p2 = Pump post-circulation time 0..98 mins, 99 is continuous; p3 = B oiler control; central heating on/off. 0 = Central heating off 1 = Central heating on (= factory setting) p4 = D isplay options 0 = Simple display 1 = Comprehensive display 2=D isplay automatically goes to simple after three minutes (factory setting) * Consult our Technical department for further information and demands on the system. 2x fig. 19 Changing parameters 114492LTAL21H021b The parameters can be changed at user level as follows: 1. Press the -key several times until the symbol flashes in the menu bar; 2. Select the users menu using the -key, p1 appears (the 1 flashes); 3. Press the [+]-key; p2 appears (the 2 flashes); 3. Press the -key again; 3 (min) appears and flashes: (factory setting); 4. Change the value by pressing the [-] -key or the [+] -key, in this case for example to 15 min, with the [+] -key; 5. Confirm the value with the -key, p2 appears (the 2 flashes); 6. Press the - key twice, the boiler enters the current operating status. The p1 to p4 settings can be changed in the same way as p2. 9.1.6 Changing parameters at service level (with access code) To prevent undesired settings, some parameter settings can only be changed after the special access code 12 is entered. This code may only be used by qualified installers. The following settings can be changed at user and service levels: 114494-03 35 9. Commissioning May also be changed by users Codes in display GAS 210 ECO PRO Description 1 Flow temperature set point 2 Pump post-circulation time 3 Boiler control 4 Display 17 Maximum speed central heating (natural gas) Minimum speed 18 central heating and hot water (natural gas) 19 Starting speed (natural gas) 20 Maximum flow temperature CH 21 Can only be changed by the installer 22 23 24 25 26 27 Setting range and possible explanation 20 - 90°C 0 – 98 minutes 99 = continuous 0 = Central heating off 1 = Central heating on 0 = Simple display 1 = Comprehensive display 2 = Display automatically goes to simple 10 - 70 x 100 rpm 10 - 40 x 100 rpm Do not change * 21080 Factory setting 210- 210- 210120 160 200 80 3 1 2 51 64 48 57 12 13 10 12 10 - 40 x 100 rpm Do not change * 17 20 - 90°C 90 0 - 30°C (only with external sensor) 20 0 - 90°C (only with external sensor) 20 -30 - 0°C (only with external sensor) - 15 -30 - 0°C (only with external sensor) - 10 Base point heating curve outside temperature Baseline of flow temperature heating curve Outside temperature climate point heating curve Outside temperature for frost protection Fault relay function (available as an accessory) Minimum water pressure (available as an accessory) 0 = Operation signal 1 = Alarm signal 1 - 60:10 bar (only with water pressure sensor) 0 = off Minimum gas pressure check (available as an accessory) 0 = Off 1 = On (only with a minimum gas pressure sensor) Hydraulic valve running time (available as an accessory) Flue gas damper running time 29 (available as an accessory) 28 30 31 32 33 34 Ad df and dU 0 = no waiting time 1 – 255 s (only if connected) 0 = no waiting time 1 – 255 s (only if connected) 0 = no waiting time Maximum time for release 1 – 255 s (only if connected) VPS gas leakage control 0 = off (available as an accessory) 1 = on (only with leakage control) 0 = Off Mains detection phase 1 = On 1 = Normal shutdown External interlock function 2 = Shutdown without frost-protection (available as an accessory) 3 = Lock out 0 = °C / bar Display units 1 = °F / psi Do not modify Automatic detection of optional 0 = No hardware 1 = Yes, once The type plate states the value of Resetting factory settings dF (X) and dU (Y); setting these values resets the factory settings. 1 0 0 0 0 0 0 0 2 0 0 X Y table 12 Settings at service level * Change this parameter when converting to flue gas cascade and LPG gas (please refer to Broag). 36 114494-03 GAS 210 ECO PRO 9. Commissioning 4x • The parameters at service level may only be changed by a qualified installer. • Changing the factory settings can result in incorrect operation of the Gas 210 ECO PRO. The parameters can be changed at service level as follows: 1. Press the -key several times until the symbol flashes in the menu bar; 2. Select the installers menu using the -key, appears in the display; 3. Use the [-] -key or [+] -key to set installers code 0012; 4. Confirm with the -key; appears; 5. Press the -key again; value 80°C appears (factory setting); 6. Lower the value, for example to 60°C, with the [-] key; 7. Confirm the value with the -key; appears; 8. Set other parameters where required by selecting them with the [-] -key or [+] -key; 9. Press the - key twice, the boiler becomes operational. Gas 210 ECO PRO also returns to operation if no keys are pressed for 10 minutes. fig. 20 Setting service code 114494-03 114492LTAL21H018b 37 9. Commissioning GAS 210 ECO PRO 9.1.7 Resetting factory settings 4x • Press the -key several times until the symbol flashes in the menu bar; • Select the installers menu using the -key, appears in the display; • Use the [-] -key or [+] -key to set installers code 0012; • Confirm with the -key; appears; • Press the [+] -key several times, df X appears; • By default, the current value X for dF appears on the display; as a check, compare this with the value of X on the type plate; enter the value of X on the type plate with the [-] key or the [+] key. • Press the key again, dU Y appears; • By default, the current value Y for dU appears on the display; as a check, compare this with the value of Y on the type plate; enter the value of Y on the type plate with the [-] key or the [+] key. • Press the key to confirm the values; the factory settings have been reset. 114492LTAL21H010a fig. 21 38 Resetting factory setting 114494-03 GAS 210 ECO PRO 9. Commissioning 9.1.8 Setting manual operation ( symbol) 3x In some cases, it may be necessary to set the boiler to manual operation, for example when the controller has not yet been connected. The boiler can be set to automatic or manual operation under the symbol. Do this as follows: • Press the -key several times until the symbol flashes in the menu bar; • Press the -key once, either the minimum flow temperature or AUt) (only if an external sensor has been connected) will appear in the display; the flow temperature is determined by the internal heating curve; • or 20°C (minimum flow temperature) will appear in the display; • Press the [+] -key to increase this value in manual operation temporarily; • Confirm with the -key; • The boiler is now set to manual operation; • Press the -key twice to exit manual operation; the boiler enters operating status. Manual operation keeps active after power breakdown. 114492LTAL21H019a fig. 22 Setting manual operation 9.2 Commissioning Ensure that the boiler is disconnected from the power supply. 1. Remove front panel. 2. Open the main gas cock. 3. Check the electrical connections including earth. 4. Fill the boiler and the system with water (minimum pressure 0.8 bar). 5. Vent the system. 6. Fill the trap with clean water. 7. Check the flue gas discharge connection and air supply connection. 8. Vent the gas pipe (only vent pipework from gas isolation valve). 9. Open the gas cock in the gas pipe to the boiler. 10. Check the gas connection for leakage. 11. Switch on the mains supply to the boiler. 12. Adjust the boiler and any external controls to heat demand. 13. The boiler now starts to run. 114494-03 39 9. Commissioning GAS 210 ECO PRO Operation can now be monitored via the code window: With a heat demand: 1 Boiler starts 2 Burner starts 3 Central heating operation; briefly in part load then in full load When a heat demand ceases: 5 Burner stops 6 Boiler stops 0 Stand-by mode 15 Check and, if necessary, correct the gas/air ratio control setting. Perform the check at full load and minimum load for all boiler models. Only perform settings for the 210-80 and 210-120 models at minimum load. Perform settings for the 210-160 and 210-200 models at full load and minimum load. An electronic CO2 or O2 meter is required for checking and adjustment purposes. Check that the opening around the probe is properly sealed when meas urements are taken. 1 2 CO2 3 = full load T000239-C fig. 23 Setting values CO2 Boiler type 210-80 210-120 210-160 210-200 table 13 Boiler type 210-80 210-120 210-160 210-200 15.a Set full load: press the key, the symbol appears in the menu bar; if h3 appears in the display, full load has been set. 15.b Now measure the CO2 percentage and compare it with the values in table 13. If the CO2% level deviates from these values, set the CO2 percentage using the screw under the cap of the V2 coil on the gas block (this can only be adjusted on the 210-160 and 210-200 models). Check the flame through the inspection glass (at full load): the flame must not blow off and the burner's surface must not be red hot. Checking and setting values O2/CO2 for natural gas (H) at full load Control Setting marControl O2 Fan speed (rpm) CO2 margin gin margin % % % % % Full load h:3 5100 6400 4800 5700 8.8 8.8 8.8 8.8 ± ± ± ± 0.7 0.7 0.5 0.5 n/a n/a ± 0.3 ± 0.3 5.2 5.2 5.2 5.2 Checking and setting values O2/CO2 for natural gas (front housing removed) ± ± ± ± 1.3 1.3 0.9 0.9 Checking and setting values O2/CO2 for natural gas (H) at minimum load Control Setting marControl O2 Fan speed (rpm) CO2 margin gin margin % % % % % Minimum load L:3 1200 1300 1000 1200 9.3 9.3 9.3 9.3 ± ± ± ± 0.5 0.5 0.5 0.5 ± ± ± ± 0.3 0.3 0.3 0.3 4.3 4.3 4.3 4.3 ± ± ± ± 0.9 0.9 0.9 0.9 Setting margin % n/a n/a ± 0.5 ± 0.5 Setting margin % ± ± ± ± 0.5 0.5 0.5 0.5 table 14 Checking and setting values O2/CO2 for natural gas (front housing removed) 40 114494-03 GAS 210 ECO PRO 9. Commissioning 1 15.c Set minimum load: press the [-] -key and, when l 3 appears in the display, minimum load has been set. 15.d After minimum output has been reached, check the CO2 percentage and compare it with the value in table 14. If the CO2% level deviates from these values, set the CO2 percentage using the correction screw of the pressure controller on the gas block (for the 210-80 and 210-120 models, adjustments are only made at minimum load). 3 CO2 2 = minimum load T001791-B fig. 24 Setting values CO2 for 210-160 and 210-200 1 CO2 CO2 The boiler is supplied with a number of basic settings. burner control - modulating on the basis of flow temperature maximum flow temperature - 80°C If other values are required: see Section 9.1.6. 15.e Remove measuring equipment and seal measuring points. 16. Check gas leakage control (VPS if installed = available as an accessory): Then set the gas leakage control pressure switch to a switch pressure equal to 50% of the inlet pressure. Check that the measured inlet pressure is not the (higher) closing pressure. 17. Press the ‘reset’ key to reset the boiler to 'user level'. 18. Heat the system up to roughly 80°C if possible and switch the boiler off. 19. Vent the system and check the water pressure. 20. The boiler is now ready for operation. 21. Set the boiler control to the required values and write down the connected type of gas on the boiler type plate: e.g. G20 – 25 mbar. 22. Switch the boiler on. 2 114492LTAL21H020a fig. 25 Setting values CO2 for 210-80 and 210- 120 (only minimum load) Gas / Gaz / Gáz H (G20) ø 8.4 mm 8. 4 If the CO2% with the 210-80 and 210-120 still deviates on full load: - adjust part load (see point 15.c and 15.d) - check full load (see point 15.b) ; if the CO2% deviation is still too large; - check the size and placing of the restrictor (natural gas; 8.4 mm) The following operating modes are now available: 23.a Modulating operation: The heat output of the boiler modulates on the basis of the flow temperature demanded by the modulating controller, see ‘Note’ in point 22 and Section 8.1.2. 23.b On/off operation: the boiler modulates between minimum and maximum heat output on the basis of the flow temperature set in the boiler, see Section 8.3.2. 114492LTAL21H027 fig. 26 Check size and positioning of restrictor 114494-03 41 9. Commissioning GAS 210 ECO PRO 9.3 Taking the boiler out of operation The boiler must be switched off for maintenance or repair work. If the central heating system is not going to be used for a long time (for example, during holidays in frost-free periods), it is advisable to put the boiler out of operation. 9.3.1 Boiler with frost protection, out of operation for a long time • Set the controller low, for example to 10°C; The Gas 210 ECO PRO will now only come into operation to protect itself against freezing, (= depending on parameter 33, see table 11). To prevent radiators and the system from freezing in rooms where there is a risk of frost (e.g. garage or storage room), a frost thermostat can be connected to the boiler. The boiler will then keep the radiators in that room warm. This frost protection does not work if the boiler is out of operation. 9.3.2 Boiler without frost protection, out of operation for a long time • Isolate the mains power supply from the boiler; • Close the boiler gas cock. Drain the boiler and central heating system if you are not going to use your home or the building for a long time and there is a chance of frost. 42 114494-03 GAS 210 ECO PRO 10. Inspection and maintenance 10. Inspection and maintenance 10.1 General The boiler is virtually maintenance free; it only has to be inspected once a year and only if necessary be serviced/cleaned. The annual inspection of the boiler includes: - combustion check of the boiler (the fan draws in the combustion air through the venturi. Clean the fan, venturi and burner if there are irregularities); - cleaning the trap; - checking the ignition electrode; - leakage check (water, flue gas and gas); - water pressure check. 10.2 Combustion check of the boiler Combustion is checked by measuring the O2/CO2 percentage in the flue gas discharge duct. To do this, heat the boiler to a water temperature of approx. 70°C. The measurements must meet the values set in table 13. The flue gas temperature can also be measured at the measuring point in the flue gas discharge duct. If the flue gas temperature exceeds the return temperature by more than 30°C, this can indicate that the heat exchanger is dirty. If these checks show that combustion in the boiler or heat transmission is no longer optimum, corrective maintenance must be carried out in accordance with the instructions in Sections 10.2.1 to 10.2.4. 10.2.1 Corrective maintenance This should include cleaning the fan, venturi, the heat exchanger and the burner. These parts must be cleaned in succession. A service kit which contains gaskets and most used parts for maintenance is available as an accessory. Work on the boiler Disconnect the mains supply, close the main gas cock and allow the boiler to cool down before working on the boiler. 114494-03 43 10. Inspection and maintenance GAS 210 ECO PRO 10.2.2 Cleaning the fan 3 230 V 1 2 6 4 5 7 For the 210-80 and 210-120 versions: Remove the electrical connections from the fan. 1. Unscrew the union nut under the gas multiblock (pay attention to the sealing). 2. Remove the bolts from the outlet side of the fan. 3. Remove the fan, including venturi and gas multiblock. 4. Remove the bolts on the inlet side of the fan. 5. Detach the venturi from the fan. 6. Clean the fan with a plastic brush. 7. Remove loose dust from the fan. 8. Re-attach the venturi to the fan. 9. Detach the air silencing tube from the venturi. 10. Clean the venturi with a plastic brush. 11. Refit all removed components; check the correct positioning of the gasket ring between fan and venturi. 8 9 12 10 11 13 230 V 15 14 114492LTAL21H028b fig. 27 44 Cleaning the fan 210-80 and 210-120 114494-03 GAS 210 ECO PRO 10. Inspection and maintenance 3 1 2 4 For the 210-160 and 210-200 versions: 1. Remove the electrical connections from the fan. 2. Remove the bolts that fix the venturi on the fan. 3. Remove the bolts and the nuts from the outlet side of the fan. 4. Remove the fan (pay attention to the sealing). 5. Clean the fan with a plastic brush. 6. Remove loose dust from the fan. 7. Detach the air silencing tube from the venturi. 8. Clean the venturi with a plastic brush. 9. Refit all removed components; check the correct positioning of the gasket ring between fan and venturi. 5 6 7 8 11 10 9 114492LTAL21H029b fig. 28 Cleaning the fan 210-160 and 210-200 114494-03 45 10. Inspection and maintenance GAS 210 ECO PRO 5/6 leden 10.2.3 Cleaning the heat exchanger (flue gas side) 1 Caution: The sealing between the inspection hatch and heat exchanger may stick, as may the sealing between the burner and heat exchanger Prevent the sealing from tearing. Damaged or hardened sealing must always be replaced. 1. Remove the nuts from the inspection hatch at the front of the heat exchanger. 2. Take the inspection hatch off the heat exchanger. 3. Clean the heat exchanger with special cleaning tool (available as an accessory) or compressed air. 4. Clean the condensate collector by removing the plug (in front of the flue gas discharge pipe) and rinsing the collector with water. 5. Now refit all removed components. 5/6 leden 2 3 4 5/6 leden 3 6 5 114492LTAL21H013a fig. 29 46 Cleaning heat exchanger 114494-03 GAS 210 ECO PRO 10. Inspection and maintenance 10.2.4 Cleaning the burner 2 3 1 1 2 1. Dismantle the burner. 2. Check burner visually and if necessary clean carefully with air (e.g. compressed air at between 2 and 5 bar, nozzle - burner distance approx. 1 cm). 3. Now refit all removed components. Ensure that cables do not come into contact with hot boiler parts! 4 1cm 5 2-5 bar 6 8 8 7 6 114492LTAL21H014a fig. 30 Cleaning burner 114494-03 47 10. Inspection and maintenance GAS 210 ECO PRO 10.3 Cleaning the trap Remove the trap from the boiler and clean it. Fill the trap with fresh water and fit it. 10.4 Checking the ignition electrode Check the ignition electrode adjustment (between 3 and 4 mm) and replace electrode if necessary (including sealing). Also check the electrode's porcelain for hairline fractures because this may cause spark-over. 3 ... 4 mm 114492LTAL21H030 fig. 31 Check the ignition electrode 10.5 Checking for leaks Check for water, flue gas and gas leaks. 10.6 Checking water pressure The water pressure must be a minimum of 0.8 bar. The water pressure also depends on the height of the central heating system above the boiler (static pressure, 1 bar = 10 m high). It is recommended to fill the system to approx. 0.8 bar above this static pressure. 10.7 Putting boiler back into operation 1. Open the gas cock in the gas pipe to the boiler. 2. Switch on the mains supply to the boiler. 3. Adjust the boiler and any external controls to heat demand. 4. Perform another flue gas analysis (see Section 9.2 and adjust if necessary. 48 114494-03 GAS 210 ECO PRO 11. Faults 11. Control stops and faults 11.1 General The boiler is fitted with an advanced control unit. The heart of the control is a microprocessor, the abc®, which both protects and controls the boiler. 11.2 Control stops and faults Control stop: The control stop is a (temporary) boiler operating mode due to an abnormal situation. The boiler switches to the neutral position so that it can return to a normal state. The display then shows the shutdown status (with code 9) again. The boiler control unit will, at first, try several times to start the boiler again. The boiler shall operate again when the causes of the control stop have been removed. Fault: If the shutdown condition still exists even after various automatic control unit start attempts have been made or if a non-reproducible phenomenon has arisen, the boiler switches to fault mode (also known as lock-out). The boiler can only resume operation if the cause of the fault is rectified and the ‘RESET button’ is pressed 11.3 Control stop codes The boiler display will show code 9. The control stop codes can be read out as follows: • Push the - key, and then the - key; • The display shows = 9; • Push the [+]- key one time; the display shows 5u and the control stop code. The boiler shall start automatically when the causes of the control stop have been removed. 114494-03 49 11. Faults Code 5u GAS 210 ECO PRO Description 0 Parameter fault 1 Maximum flow temperature exceeded 3 4 Maximum heat exchanger temperature exceeded Maximum heat exchanger temperature increase exceeded Possible cause Check/solution • Reset dF and dU • Reset with RECOM PC • No flow or insufficient flow Check: • Flow and/or reason for heat demand • No flow or insufficient flow during heat demand Check: • Flow (direction, pump, valves) • That the system has been correctly bled • Temperature sensors for deviations • Water pressure in the system • Whether the heat exchanger is dirty • No flow or insufficient flow • Sensor fault Check: • Flow (direction, pump, valves) • That the system has been correctly bled • Temperature sensors for deviations • Water pressure in the system • Whether the heat exchanger is dirty 5 Maximum difference between heat exchanger and return temperature exceeded • No flow or insufficient flow during heat demand • Sensor fault Check: • Flow (direction, pump, valves) • That the system has been correctly bled • Temperature sensors for deviations • Water pressure in the system • Whether the heat exchanger is dirty 6 Maximum difference between heat exchanger and flow temperature exceeded • No flow or insufficient flow during heat demand • Sensor fault Check: • Flow (direction, pump, valves) • That the system has been correctly bled • Temperature sensors for deviations • Water pressure in the system • Whether the heat exchanger is dirty 8 Waiting time release signal drift • External cause • Incorrectly set parameter • Bad connection • Remove external cause • Check the parameter • Check the connection 9 Phase and neutral of mains supply mixed up • Mains supply incorrectly wired • Floating or 2-phase system • Reconnect phase and neutral • Set parameter 32 to 0 10 Shutdown interlock active • External cause • Incorrectly set parameter • Bad connection • Remove external cause • Check the parameter • Check the connection 11 • External cause Shutdown interlock active or frost • Incorrectly set parameter protection active • Bad connection • Remove external cause • Check the parameter • Check the connection 13 • BUS connection inadequate or Communication fault with SCU (= non-existent • SCU PCB not present optional PCB) (any longer) in boiler • Reconnect • Carry out automatic detection 14 Water pressure too low • Water pressure non-existent or too low • Incorrect water pressure parameter adjustment • Water leakage Check: • Water pressure in the system • Minimum water pressure • That hydraulic pressure sensor is properly installed /connected Gas pressure too low • No flow or insufficient flow • Incorrect GPS switch adjustment • Wiring defect or switch faulty Check: • That the gas cock is fully opened • That there is adequate gas pressure • That the GPS switch is properly installed • Replace the GPS switch if necessary Configuration fault or SU not recognised • Incorrect SU PCB for this boiler • Replace SU PCB 15 16 * 50 114494-03 GAS 210 ECO PRO 11. Faults Code 5u Description Possible cause Check/solution 17 * Configuration fault or default parameters table incorrect • PCU-01 unit parameters incorrect • Replace PCU-01 unit 18 * Configuration fault or parameter storage unit (PSU) not recognised • Incorrect PSU PCB for this boiler • Replace PSU PCB 19 * Configuration fault or dF-dU parameters unknown 20 * Configuration procedure active • Standard briefly activated following boiler switch-on • No action Communication fault with SU-01 • Bad connection • Check that the PCB is inserted in the correct connector No flame during operation • No ionisation current Check: • That the gas cock is fully opened • That the gas pressure is sufficient • That the gas block is appropriately adjusted and working correctly • Whether the air supply or flue gas discharge are blocked • The flue gas circulation; inspect the flue gas discharge system for installation faults and the heat exchanger for leaks 24 VPS test failed Check: • That the gas cock is fully opened • That the gas pressure is sufficient • Gas pressure non-existent or • That the VPS switch is properly too low installed • Faulty gas valve • Whether the gas valve is leaking or in • Incorrect adjustment of the VPS the open position switch • That the wiring is OK; mix up of the V1 • Wiring fault and V2 plugs • Faulty VPS switch • The adjustment of the VPS switch • Replace the VPS switch if necessary • Replace the gas valve if necessary 25 Internal fault SU-01 21 22 • Add/check dF and dU • Replace SU-01 * These lock-outs are not stored in the failure memory. table 15 Control stop codes 11.4 Fault codes The boiler displays the fault codes as follows: é 12 (the display shows the symbol and the fault code flashes). The meaning of the fault codes can be found in the fault table, see table 16. In the event of faults, proceed as follows: • Note the fault code. The fault code is needed to find the cause of the fault quickly and correctly and for any support from our Customer Care Department. 114494-03 51 11. Faults GAS 210 ECO PRO • Press the “RESET- key” for 2 seconds. If the fault code continues to appear, look for the cause in the following fault table and rectify the fault. If the display does not show RESET but SERVICE, the boiler must be switched off and switched on again after 10 seconds before the fault can be reset. Fault code Description Possible cause Check/solution E:00 Storage unit parameter not found • Bad connection • Check the cable bundle E:01 Safety parameters not in order • Bad connection • Check the cable bundle E:02 Heat exchanger temperature sensor short circuited E:03 Heat exchanger temperature sensor open circuit • • • • • • Bad connection Defective sensor Sensor not correctly mounted Bad connection Defective sensor Sensor not correctly mounted • • • • • • E:04 Heat exchanger temperature exceeded below normal range Bad connection Defective sensor Sensor not correctly mounted No or to little flow E:05 Heat exchanger temperature exceeded above normal range (high limit thermostat) • • • • • Check the cable bundle • Replace the sensor if necessary Check: • flow (direction, pump, valves) • if system has been correctly bled • temperature sensors for deviations • if sensor is correctly mounted • water pressure in the system • if heat exchanger is dirty E:06 Return temperature sensor short circuited E:07 Return temperature sensor open circuit • • • • • • Bad connection Defective sensor Sensor not correctly mounted Bad connection Defective sensor Sensor not correctly mounted E:08 Return temperature exceeded below normal range • • • • Bad connection Defective sensor Sensor not correctly mounted No or to little flow E:09 E:10 E:11 52 Return temperature exceeded above normal range • Defective sensor Too great a difference between heat exchanger and • No or to little flow • Sensor not correctly mounted return temperature Check the cable bundle Replace the sensor if necessary Check if sensor is correctly mounted Check the cable bundle Replace the sensor if necessary Check if sensor is correctly mounted • Check the cable bundle • Replace the sensor if necessary • Check if sensor is correctly mounted • Check the cable bundle • Replace the sensor if necessary • Check if sensor is correctly mounted • Check the cable bundle • Replace the sensor if necessary Check: • flow (direction, pump, valves) • if system has been correctly bled • temperature sensors for deviations • if sensor is correctly mounted • water pressure in the system • if heat exchanger is dirty • • Replace the sensor if necessary Check: • flow (direction, pump, valves) • if system has been correctly bled • temperature sensors for deviations • water pressure in the system • if heat exchanger is dirty • if sensor is correctly mounted 114494-03 GAS 210 ECO PRO Fault code Description E:12 Trap protection activated E:14 5 failed burner starts E:15 5 failed gas leakage controls E:16 False flame signal E:17 Gas valve control fault E:32 Flow temperature sensor short circuited 114494-03 11. Faults Possible cause Check/solution • Check the cable bundle • Check that the trap is not empty; top up if necessary • Bad connection • Blockage in flue gas discharge/RGA • Pressure in flue gas discharge duct covered is (was) too high • Cascade valve does not open • air supply obstructed • Trap is blocked • Heat exchanger is dirty • check the air supply Check: - connection between ignition cable and transformer - electrode distance, this must be 3 to 4 mm - breakdown to earth • No ignition spark - condition of the burner set (burner set/electrode seal) - earthing - bad actuation on SU board Check: - is the gas cock opened? - is the inlet gas pressure sufficient? - is the gas pipe vented? - correct gas block operation and • Ignition spark, but no flame adjustment? - is the air supply or flue gas discharge blocked? - condition of cable bundle to gas block - bad actuation on SU board Check: - condition of the electrode and earthing - condition of cable bundle between ignition • Flame, but insufficient ionisation cable and transformer - if gas cock is fully opened - if the gas pressure is sufficient • Is the gas cock opened? • Is the gas pressure sufficient? • Are the VPS switches correctly fitted? • Defective gas valve • Gas valve is leaking or is stuck in the • No or to little gas pressure open position. • VPS switch wrongly adjusted • Is the wiring in order, plugs V1, V2 not • Bad connection mixed up? • Defective sensor • Check the VPS settings • Sensor not correctly mounted • Replace the sensor if necessary • Check if sensor is correctly mounted • Burner glows as a result of a high CO2 percentage (adjust CO2). • Ionisation current has been meas• Check the ignition/ionisation electrode ured, while there may not be a flame • Gas valve is leaking or is stuck in the • Defective ignition transformer open position. • Replace ignition transformer • Bad connection • Check the cable bundle • Defective gas valve • Replace the gas valve if necessary • Check the cable bundle • Bad connection • Replace the sensor if necessary • Defective sensor • Check if sensor is correctly mounted • Sensor not correctly mounted 53 11. Faults GAS 210 ECO PRO Fault code Description Possible cause Check/solution E:33 Flow temperature sensor open circuit • Bad connection • Defective sensor • Sensor not correctly mounted E:34 Fan fault • Bad connection • Defective fan Flow and return swopped • • • • Flame loss occurs 5 times • Ionisation current drops out • Check the cable bundle • Replace the sensor if necessary • Check if sensor is correctly mounted • Fault in fan cabling • Defect in fan • (Too) much draught over boiler, so that the fan starts to rotate Check: - flow direction - temperature sensors for deviations • Replace the sensor if necessary • Inlet gas pressure sufficient? Inlet gas pressure controller in order? • Correct gas block operation and adjustment? • Blockage in air supply or flue gas discharge? • Flue gas circulation, check flue gas system for installation faults and the heat exchanger for possible leaks • Check SU board is correctly inserted in the connector on the PCU-01 E:35 Defective sensor Wrong flow direction Bad sensor connection Sensor not correctly mounted E:36 E:37 Communication fault with SU • Bad connection board E:38 Communication fault with SCU board (optional) E:39 table 16 • Bad connection • External cause Shutdown input in locked-out • Incorrectly set parameter mode • Bad connection • Check the cable bundle • Remove external cause • Check the parameter • Check the cable bundle Fault codes 11.5 Control stop - and fault memory The boiler control unit has a control stop and fault memory. This stores the last 16 control stops and the last 16 faults that have occurred. With each fault, the following data is saved: - B or E = control stop or fault code - = Number of times that the fault has occurred in succession - hr = Burner operating hours since time of fault - 5t = status - 5u = sub status - t1 = flow temperature [°C]; - t2 = return temperature [°C]; - t4 = outside temperature [°C]; - t6 = boiler block temperature [°C]; - 5p = internal set point [°C]; - fl = ionisation current [uA]; - f = fan rotation speed [rpm]; - pr = water pressure [mbar]; - p = relative output supplied [%]; 54 114494-03 GAS 210 ECO PRO 12. Service parts 11.5.1 Reading faults 5x • Press the -key several times until the symbol flashes in the menu bar; • Press the key; B xx will flash in the display, together with the number of shutdowns that have been memorised; • Press the [+] or [-] key to select either the control stops B or faults Er. • Press the key; B xx will flash in the display, together with the number of shutdowns that have been memorised; • Press the [+] or [-] -key to go forwards or backwards in the list of faults. • Press the -key to take a closer look at the fault. Press the [+] or [-] -key to view the following information: b12 (shut down code b with fault number e.g. 12); (number of with the 'number of times that the fault has occurred’ as number); hr = 2 (burner operating hours since time of fault) ; (status code) ; 5u (sub status); t180 (temperature t1, the flow temperature 80 when the fault occurred); t270 (temperature t2, the return temperature 70 when the fault occurred); • Press the -key to stop the cycle, B xx will appear flashing in the display with the number of the last fault; • Press the [+] or [-] -key to view any subsequent fault information. t/m t/m 2x 2x 114492LTAL21H015a fig. 32 Reading faults or control stops 11.5.2 Deleting control stops or faults The last message in the list in the display is (or b with shutdowns) • Press the -key; the display will show: 0 • Press the [+] -key to set the parameter to 1. • Press the -key ; the fault memory is cleared • Press the - key twice to exit the fault memory. With faultfinding, retrieving the operating status when the fault occurred can contribute to faster rectification of the cause. fig. 33 Deleting faults 114494-03 55 12. Service parts GAS 210 ECO PRO 12. Service parts 12.1 General If it is ascertained during the annual inspection or maintenance work that a part in the boiler must be replaced, use only original parts or parts and materials recommended by Broag. Send the part to be replaced to Broag. Always send a fully completed return form as well, see example. In this way, Broag can handle its guarantee obligations faster and more efficiently. Your reference Date Customer Name Address Zip code / city Telephone Contact person Job number Part. no. Description Boiler serial nr.* Model Installation date Problem desReference cription t able 17 Return form sample * This data can be found on the boiler type plate; the type plate is stuck to the top of the boiler's right side panel. 56 114494-03 GAS 210 ECO PRO 12. Service parts 12.2 Exploded view 210-80 210-120 210-160 210-200 210-200 210-80 210-120 210-160 210-200 210-200 210-80 210-120 210-160 210-200 114492EVAL21H001b fig. 34 Exploded view 114494-03 57 13. Regulations GAS 210 ECO PRO 13. Regulations 13.1 General The Remeha Gas 210 ECO PRO is a high efficiency, floor standing central heating boiler, suitable for use with all types of natural gas; it recovers both perceptible and latent heat from flue gases. The units are inspected on the basis of the essential requirements in the following directives: - Gas Appliances Directive no. 90/396/EEC - Efficiency Requirements Directive no. 92/42/EEC - EMC Directive no. 89/336/EEC - Low Voltage Directive no. 73/23/EEC - Pressure Equipment Directive no. 97/23/EEC, article 3, sub. 3 CE identification number: 0085BS0132 NOx class: 5 NOx identification number: BS004 13.2 Standards The following instructions must be adhered to when the Remeha Gas 210 ECO PRO is installed: - Gas Safety (Installation and Use) Regulations 1998 (as amended). In addition to the above regulations, this boiler must be installed in compliance with: - Current I.E.E. Regulations for electrical installations - Local building regulations - The Building Standards (Scotland) - (Consolidation) Regulations - by-laws of the local water undertaking - Health and Safety Document No 635 'The Electricity at Work Regulations 1989'. It should also be in accordance with the relevant recommendations in the current edition of the following British Standards and Codes of Practice, viz. BS 6644, BS 5978 Part 1 & 2, BS 5449, BS 5446, BS 6798, BS 6891 and BG DM2. 13.3 Remeha factory test Before leaving the factory, every Remeha boiler is optimally set and tested for: - electrical safety; - CO2 adjustment; - hot water operation; - water tightness; - gas tightness; - control unit parameters. 58 114494-03 GAS 210 ECO PRO 13. Regulations 13.4 Supplementary guidelines In addition to the regulations and guidelines mentioned in Section 13.2, the supplementary guidelines in this documentation must also be followed. Supplements or subsequent regulations and guidelines in existence at the time of installation shall apply to all regulations and guidelines mentioned in this Installation and Service manual. The Remeha Gas 210 ECO PRO is a CE certified boiler and must not be modified or installed in any way contrary to these "Installation and Maintenance Instructions". Manufacturers Instructions must NOT be taken as overriding statutory obligations. 114494-03 59 14. Technical specifications GAS 210 ECO PRO 14. Technical specifications 14.1 Technical data Boiler type Gas 210 ECO PRO Unit 210-80 210-120 210-160 210-200 3 4 5 6 General Number of sections Input control Nominal output (80/60°) Pn Nominal output (50/30°) Pn Nominal input gross caloric value (GCV/Hs) Qn Nominal input net caloric value (NCV/Hi) Qn Gas and flue gas side Category Inlet gas pressure natural gas Gas consumption natural gas min max NOX emission per year (BREEAM) (EN 15420) Residual fan pressure Flue gas quantity Modulating, 0-10 V or on/off min max min max min max min max min max Type classification with respect to flue gas discharge Central heating side kW kW kW kW kW kW kW kW 16 87 18 93 19 99 17 89 22 120 24 129 26 137 23 123 - II2H3P mbar 17 - 30 29 166 33 179 34 189 31 170 39 200 44 217 46 228 41 205 m03/h m03/h 1.8 9.4 2.4 13.0 3.3 18.0 4.3 21.7 mg/kWh 33 35 38 37 Pa 130 130 130 130 kg/h kg/h 27.2 149.7 36.7 206.9 49.5 286.0 65.5 344.9 - B23, B23P, C13, C33, C43, C53, C63, C83 High limit temperature °C 110 Operating temperature range °C 20 - 90 Minimum water working pressure bar 0.8 Maximum water working pressure PMS bar 6 Water content litres 12 16 20 24 Hydraulic resistance at dT = 20° mbar (kPa) 165 (16.5) 135 (13.5) 170 (17) 180 (18) 4 125 4 193 4 206 4 317 165 188 Electrical Mains voltage Input power (without pump) Insulation class V/Hz min max Watt Watt 230/50 IP 20 Other Weight excluding water Noise level at a distance of 1 m from the boiler (enclosed version) Environment temperature Colour of casing table 18 60 kg dB(A) 115 135 ≤ 59 °C 0 - 40 RAL 2002 (red)/7037 (grey) Technical data 114494-03 GAS 210 ECO PRO 15. Efficiency data and gas inspection labels 15. Efficiency data and gas inspection labels 15.1 Unit usable efficiency (HR efficiency) Up to 108.6 with respect to Hi at TReturn = 30°C. 15.2 Water-side efficiency a. Up to 98.4% with respect to Hi at full load at an average water temperature of 70°C (80/60°C). b. Up to 105.7% with respect to Hi at full load an average water temperature of 40°C (50/30°C). 15.3 Zero-load losses Approx. 0.21% with respect to Hi at an average water temperature of 45°C. 15.4 Description of specifications High efficiency gas boiler Inspected for compliance with the essential requirements of the Gas Appliances Directive, Efficiency Directive, Low Voltage Directive and EMC Directive. - Boiler conforms to Pressure Equipment Directive (article 3, sub. 3). - Modulating (18 - 100%) or 0-10V or on/off control is optional. - Hydraulic efficiency up to 98.4% at full load (with respect to Hi) at 80/60°C and up to 105.7% (with respect to Hi) at 50/30°C. - Suitable for use with II2H3P - Annual NOX emissions < 62 mg/kWh, or < 35 ppm at O2 = 0% (NOx - class 5). - Average boiler housing noise level at 1 m distance around boiler ≤ 59 dBA - Heat exchanger made of cast aluminium sections. - Cylindrical, stainless steel, premix burner with metal fibre cover. - Air supply fan. - Flue gas pressure difference switch. - Temperature control: adjustable between 20 - 90°. - Low water level protection using temperature sensors. - Gas/air mixing system (venture). - Gas multiblock (210-80 + 210-120 ;230V) (210-160 + 210-200; 30 RAC) - Electronic control and protection equipment: 230 V. - Fan; 230V - Pump switch: on/off 230 V max. 300 VA. - Frost protection. - Filling and drain cock. - Trap. - Suitable for both room ventilated and room sealed versions. - Sheet steel casing, off the ground. - Plastic condensate collector. - Boiler equipped with closed air box. - Boiler fully pre-wired with built-on control box. - Installation option for boiler controllers. - Suitable for OpenTherm controllers. - Supplied with internal heating curve. - Well laid-out instrument panel with LCD display. - Menu-controlled microprocessor boiler control with operating and servicing diagnostics. 114494-03 61 15. Efficiency data and gas inspection labels GAS 210 ECO PRO Available in 4 types: 210 -80: 87 kW nominal output at 80/60°C 210-120: 120 kW nominal output at 80/60°C 210-160: 166 kW nominal output at 80/60°C 210-200: 200 kW nominal output at 80/60°C 15.5 Accessories - Modulating rematic® weather compensators. - OpenTherm weather compensators (iSense), also for cascade configurations (Celcia MC4). - Air supply filter (only for use with “open flue”). - Concentric wall and roof feed-through connections. - Second return connection (for CT circuit). - Thermostat pocket - Cleaning tools. - Service case. - Recom communication set with CD-ROM, interface and wiring. - Interfaces for communication with various controllers, see Section 8.4.3. - 0 - 10 V control PCB (IF-01). - Expanded control/protection PCB (SCU-S01). - Outside temperature sensor* (only possible in combination with SCU-S01 PCB). - Flue gas temperature switch* (only possible in combination with SCU-S01 PCB). - Minimum gas pressure switch* (only possible in combination with SCU-S01 PCB). - Water pressure sensor* (only possible in combination with SCUS01 PCB). - Motorised flue gas discharge valve* for cascade configurations and to prevent flue gas from flowing back (only possible in combination with SCU-S01 PCB). - Gas leakage control* (for the 166 and 200 kW boilers), only possible in combination with SCU-S01 PCB. * Only one PCB (SCU-S01) board is needed for one or all of these options. 15.6 Services The following services can be supplied by Broag: - Initial commissioning. - Warranty support. - Access to list of Broag trained and approved service companies. Please contact our Technical department for further information on certified maintenance and inspections. 62 114494-03 GAS 210 ECO PRO 15. Efficiency data and gas inspection labels 15.7 Type of unit 30 29 28 27 26 1 25 2 24 3 23 4 22 5 21 6 20 7 19 8 18 9 17 10 16 11 15 12 14 13 114492LTAL21H016b fig. 35 Cross-section 1. Flue gas discharge 2. O2/CO2 measuring point 3. Air box 4. Control panel 5. Burner 6. Heat exchanger 7. Inspection hatch 8. Inspectionhatch for condensate collector 9.Ignition pin 10. Boiler heath exchanger sensor 114494-03 11. Return temperature sensor 12. Condensate collector 13. Condensate trap 14. Air silencing tube 15. Filling and drain cock 16. Water pressure switch (option) 17. Gas multiblock 18. Venturi 19. Fan 20.Mixing tube 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. Flue gas switch Flow temperature sensor On/off Gas connection Return connection Flow connection Thermostat pocket Display Combustion air supply Facility for built-in weather compensator 63 15. Efficiency data and gas inspection labels GAS 210 ECO PRO 15.8 Operating principle The inlet side of the fan is fitted with a venturi, where air and gas are mixed according to a fixed ratio. When there is a heat demand, the fan will pre-vent. The fan draws in the combustion air, which is mixed with the gas to optimum effect in the venturi. The fan moves the homogenous gas/air mixture through to the burner. The mixture is then ignited by the combined ignition and ionisation electrode, which also monitors the flame. Combustion then takes place. Following combustion, the hot flue gases pass through the cast aluminium heat exchanger. Here, the flue gases release their heat to the heating water in the heat exchanger. The heat output of the boiler is controlled on the basis of the settings and the prevailing water temperatures that are measured by the temperature sensors. With flue gas temperatures below dew point (approx. 55°, the temperature at which the water vapour in the flue gases starts to condense), the water vapour in the flue gases will condense in the lower part of the heat exchanger. The heat released during this condensation process (called latent heat or heat of condensation) is also transferred to the heating water. The condensed water is discharged through a trap. The flue gases flow through the condensate collector and are discharged via the flue gas discharge pipe. The advanced control system of the boiler, the abc®, guarantees extremely reliable heat supplies. This means that the boiler responds quickly and efficiently to negative environmental influences (such as hydraulic flow problems, air flow problems, etc.). If problems of this kind occur, the boiler will not lock out, but initially modulate down and, depending on the nature of the problem, switch off temporarily (shutdown or control stop) and try again after a pre-determined time. Providing the situation is not hazardous, the boiler will always continue to attempt to provide heat. For a continuous supply of heat, the boiler requires a minimum flow of 30 % of the nominal flow at the relevant design temperatures. The boiler can be equipped with a second return for CT circuit (available as an accessory). The second return can contribute additional efficiency if the installation includes different temperature groups. 15.9 Boiler Control 15.9.1 Temperature control The Remeha Gas 210 ECO PRO is equipped with electronic temperature control based on flow, return and boiler block temperature sensors. The flow temperature is adjustable between 20 and 90°C (factory setting 80°C). 15.9.2 Low water level protection The Remeha Gas 210 ECO PRO is equipped with low water protection based on temperature difference measurements and temperature increase measurements. 64 114494-03 GAS 210 ECO PRO 15. Efficiency data and gas inspection labels 15.9.3 Maximum protection The maximum protection switches the unit off if the water temperature is too high (110°C) and interlocks it on the control box. Once the fault has been remedied, the unit can be reset using the resetkey. 15.9.4 Frost protection The unit must be installed in a frost-free area to prevent freezing of the condensate drain pipe. If the temperature of the heating water drops too much, the built-in unit protection activates. 114494-03 65 16. Application data GAS 210 ECO PRO 16. Application data 16.1 General The boiler is suitable for a wide range of applications. The boiler offers numerous flue gas, hydraulic, gas and control application options, but, at the same time, is not complicated to install. This and its moderate dimensions, low noise levels and cascade options mean the boiler can be installed almost anywhere (for general legal requirements, see Section 13.2). 16.2 Air and flue gas application options The choice of versions (open or closed combustion air supply) provides excellent siting flexibility for the boiler. A motorised flue gas discharge valve is available as an accessory and is used for overpressure flue gas cascade arrangements. The boiler is equipped with an enclosed housing that also serves as an air box. An air filter and connection set are available for situations in which the boiler has to be commissioned during the construction phase or has to operate in a heavily polluted environment (this only applies to room ventilated versions). Direct connection to structural ducts is not acceptable because of condensation, see Chapter 7 for instructions and flue gas discharge tables. 16.3 Hydraulic application options The advanced boiler control (abc®) and relatively low hydraulic resistance ensures that the boiler can be used in virtually any hydraulic system. 16.4 Cascade application The boiler is also suited for configuration in a cascade. For overpressure flue gas cascade arrangements, use our motorised flue gas discharge valve (available as an accessory). This prevents flue gas from flowing back to boilers that are not in operation. As a result of the narrow width and depth of the boiler, a heat output of 400 kW (2 x Gas 210- 200) can be provided in a floor area of just under 1.2 m2. A floor area of less than 3 m2 is sufficient to include room for service and maintenance. If necessary, consult our Technical department. 66 114494-03 GAS 210 ECO PRO fig. 36 1. 2. 3. 4. 5. 6. 7. 16. Application data Example of a hydraulic diagram cascade configuration modulating cascade controller pump safety valve outside temperature sensor non return valve expansion vessel manual seal 114494-03 8. automatic air vent 9. pressure-free distributor (not supplied by Remeha, see table 19 for dimensions) 10. drain cock 11. system pump 12. expansion vessel system 13. flow temperature sensor 67 16. Application data GAS 210 ECO PRO B fig. 37 The following table shows the minimum dimensions for the various pipes and for the low loss header based on a dT design of 20°. The boiler has a no built-in pump. I Illustration of low loss header B = boiler side I = installation side Output kW 80 120 160 200 240 280 320 360 400 440 480 520 560 600 640 table 19 68 Rate of flow Q m3/h 3.4 5.2 6.9 8.6 10.3 12.0 13.8 15.5 17.2 18.9 20.6 22.4 24.1 25.8 27.5 d int. inch 1¼ 2 2 2½ 2½ 2½ 2½ 2½ 2½ 3 3 3 3 3 3 D Ø or D square inch 3 (DN 80) 4 (DN 100) 4 (DN 100) 5 (DN 125) 5 (DN 125) 6 (DN 150) 6 (DN 150) 6 (DN 150) 8 (DN 200) 8 (DN 200) 8 (DN 200) 8 (DN 200) 8 (DN 200) 8 (DN 200) 10 (DN 250) mm 70 90 100 110 120 130 140 150 160 170 170 180 190 190 200 H A B mm 280 350 350 440 440 440 440 440 440 540 540 540 540 540 540 mm 370 465 465 580 580 580 580 580 580 720 720 720 720 720 720 mm 510 630 630 770 770 770 770 770 770 900 900 900 900 900 900 Low loss header dimensions 114494-03 GAS 210 ECO PRO 16. Application data 16.5 Control options The following types of control can be used for the boiler: - as a single boiler or in a cascade with modulating controllers based on room and/or outside temperature - on/off controllers, using the boiler's internal heating curve if necessary (in combination with outside temperature sensor) - high/low controllers - analogue signals (0-10 V) for control based on output or flow temperature. For further details, see Section 8.4.3 16.6 Gas application options The boiler is suitable for use with natural gas category II2H3P. For further data, see Chapter 6. 114494-03 69 17. Checklists (records) GAS 210 ECO PRO 17. Checklists (records) 17.1 Checklist for commissioning (Commissioning record) Commissioning work, see Section 9.2 1. Fill the central heating system with water. Check the water pressure in the central heating system. 2. Fill trap with water. 3. Vent central heating system 4. Check circulation pump operation 5. Check water-side connections for tightness 6. Check type of gas offered (Does the type of gas offered correspond to the type of gas for which the boiler is suited?) 7. Check the gas supply pressure 8. Check gas meter capacity 9. Check the gas tightness of the connections and the gas pipes 10. Vent gas supply pipe 11. Check electrical connections 12. Air supply and flue gas discharge connections checked 13. Check function and operational status of the boiler 14. Check whether the gas/air ratio control is correct 15. Measuring equipment removed and cap refitted on flue gas measuring point 16. Refit boiler front housing again in the proper manner 17. Write type of gas on the boiler type plate 18. Set room thermostat or boiler control to desired value 19. Instruct user and hand over the necessary documents 20. Confirmation of commissioning Measured value or confirmation O O O O O O Natural gas G20/G25/propane Wobbe index …….kWh/m3 O O O O O O O O O O O O O Date: (Company name, signature of engineer) table 20 Commissioning record 17.2 Checklist for annual inspection (inspection record) Inspection work, see Chapter 10. Confirmation and date 1. Water pressure checked 2. Air supply and flue gas discharge connections checked 3. Ignition electrode checked 4. Combustion checked 5. Heat exchanger (central heating) checked 6. Check the venturi for corrosion 7. Confirmation of inspection (signature of engineer) table 21 Inspection record 70 114494-03 GAS 210 ECO PRO 17. Checklists (records) 17.3 Checklist for maintenance (maintenance record) Maintenance work (see Section 10) Confirmation and date 1. Ignition electrode checked 2. Heat exchanger (central heating) cleaned 3. Combustion checked 4. Water pressure checked 5. Air supply and flue gas discharge connections checked 6. Check the venturi for corrosion 7. Burner checked 8. Confirmation of maintenance (signature of engineer) table 22 114494-03 Maintenance record 71 Remeha Commercial Innovation House 3 Oaklands Business Centre Oaklands Park Wokingham RG41 2FD Tel: +44 118 9783434 Fax: +44 118 9786977 Internet: www.remeha.co.uk E-mail: boilers@remeha.co.uk © Copyright All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions furnisched by us remain our property and may not be multiplied without our prior consent in writing. 04112014 114494
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes XMP Toolkit : 3.1-702 Create Date : 2014:11:04 10:58:23+01:00 Metadata Date : 2015:02:12 11:22:24Z Modify Date : 2015:02:12 11:22:24Z Creator Tool : Adobe InDesign CS5 (7.0) Page Image Page Number : 1, 2 Page Image Format : JPEG, JPEG Page Image Width : 256, 256 Page Image Height : 256, 256 Page Image : (Binary data 7689 bytes, use -b option to extract), (Binary data 10946 bytes, use -b option to extract) Document ID : xmp.did:C202D4BFE228E21180BCABAEA8D5D30B Instance ID : uuid:acb06252-a422-4018-8d47-d081a15b25ae Original Document ID : adobe:docid:indd:1bfbe69d-2d25-11df-aac4-a580e4ecbfe0 Rendition Class : proof:pdf Derived From Instance ID : xmp.iid:67349DBFE228E21180BCABAEA8D5D30B Derived From Document ID : xmp.did:02C8A111DC28E2119D82D2F77C16489F Derived From Original Document ID: adobe:docid:indd:1bfbe69d-2d25-11df-aac4-a580e4ecbfe0 Derived From Rendition Class : default History Action : saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved, saved History Instance ID : xmp.iid:3853232D8F33E011A707C57733950640, xmp.iid:3953232D8F33E011A707C57733950640, xmp.iid:3A53232D8F33E011A707C57733950640, xmp.iid:13007B009033E011A707C57733950640, xmp.iid:662436634997E011BE76B234B6AC6EC9, xmp.iid:19D957A04C22E1119B02C82E63462DEF, xmp.iid:1F0A7E304D22E11182A0B8B78CFC75FB, xmp.iid:DEA72FE25622E111AE57A4C83CA91689, xmp.iid:0917D5591727E111946E823F043B4750, xmp.iid:813246E01927E11189DDF4DF2C899CC8, xmp.iid:4EF469BD1B27E11189DDF4DF2C899CC8, xmp.iid:F9C472F91D27E1119DD5AE1CBBD1B43C, xmp.iid:1679EEC3993BE1119720A38EE0A16ECE, xmp.iid:4B099CFBC53DE11196DECDC32C094BCA, xmp.iid:A97CA78AE340E111B9A9B70B7EFEEB10, xmp.iid:56C90FBC8C42E111A8AF9B4B5AE2A7E9, xmp.iid:58D4D8168D42E111A8AF9B4B5AE2A7E9, xmp.iid:F0D2AB7F4F43E111AEBBC27D5FDB9325, xmp.iid:A7A196075043E1118A89F0F5CF21D537, xmp.iid:EF484183EE52E1119378D374FD8A1EC6, xmp.iid:C898E12E0595E11196F9C0AA8EDFC4A8, xmp.iid:CEF22FEA0695E11196F9C0AA8EDFC4A8, xmp.iid:CFF22FEA0695E11196F9C0AA8EDFC4A8, xmp.iid:27A660290795E11196F9C0AA8EDFC4A8, xmp.iid:C6F76A690A95E111BC97C52537FEE052, xmp.iid:CE56086351FEE11181328269ACB85223, xmp.iid:B2BF9503DC28E2119D82D2F77C16489F, xmp.iid:B3BF9503DC28E2119D82D2F77C16489F, xmp.iid:02C8A111DC28E2119D82D2F77C16489F, xmp.iid:A40286A5E228E211B9BCDAF3C7E6BC94, xmp.iid:67349DBFE228E21180BCABAEA8D5D30B, xmp.iid:C202D4BFE228E21180BCABAEA8D5D30B, xmp.iid:C21A8227125BE211B110C74381B5C5DB, xmp.iid:8EE7D944125BE211B110C74381B5C5DB, xmp.iid:6C2432554661E211818EB2E8899BC5AD, xmp.iid:A4F4F76C4661E211818EB2E8899BC5AD, xmp.iid:0AF9F1160764E411823DDA102566D27A, xmp.iid:0A97D8410864E411B31484B3F3ABCB52, xmp.iid:54A4DB410864E411B31484B3F3ABCB52, xmp.iid:FF3E4B810864E41192BCB29D8A2AF56B, xmp.iid:003F4B810864E41192BCB29D8A2AF56B, xmp.iid:C55CE9AC0864E411A3A399BF2C15999D, xmp.iid:04B9EACC0864E411A3A399BF2C15999D, xmp.iid:06E79BF80864E411A3A399BF2C15999D, xmp.iid:716CFB170964E4119C9B8E0B2DBCF1A0 History When : 2011:02:08 15:25:06+01:00, 2011:02:08 15:25:06+01:00, 2011:02:08 15:29:36+01:00, 2011:02:08 15:30:39+01:00, 2011:06:15 14:18:10+02:00, 2011:12:09 11:01:32+01:00, 2011:12:09 11:05:35+01:00, 2011:12:09 12:14:58+01:00, 2011:12:15 13:22:47+01:00, 2011:12:15 13:40:51+01:00, 2011:12:15 13:54:12+01:00, 2011:12:15 14:10:11+01:00, 2012:01:10 15:46:01+01:00, 2012:01:13 10:08:16+01:00, 2012:01:17 09:17:25+01:00, 2012:01:19 12:01:04+01:00, 2012:01:19 12:02:54+01:00, 2012:01:20 11:15:15+01:00, 2012:01:20 11:19:03+01:00, 2012:02:09 08:21:18+01:00, 2012:05:03 11:49:10+02:00, 2012:05:03 12:01:33+02:00, 2012:05:03 12:01:55+02:00, 2012:05:03 12:02:58+02:00, 2012:05:03 12:26:35+02:00, 2012:09:14 11:49:53+02:00, 2012:11:07 14:06:59+01:00, 2012:11:07 14:07:22+01:00, 2012:11:07 14:07:22+01:00, 2012:11:07 14:54:27+01:00, 2012:11:07 14:55:11+01:00, 2012:11:07 14:55:12+01:00, 2013:01:10 11:40:30+01:00, 2013:01:10 11:41:19+01:00, 2013:01:18 09:09:08+01:00, 2013:01:18 09:09:47+01:00, 2014:11:04 10:43:54+01:00, 2014:11:04 10:52:15+01:00, 2014:11:04 10:52:15+01:00, 2014:11:04 10:54:01+01:00, 2014:11:04 10:54:01+01:00, 2014:11:04 10:55:15+01:00, 2014:11:04 10:56:08+01:00, 2014:11:04 10:57:22+01:00, 2014:11:04 10:58:14+01:00 History Software Agent : Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0, Adobe InDesign 7.0 History Changed : /;/metadata, /metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata, /metadata, /;/metadata, /metadata, /;/metadata, /;/metadata, /;/metadata, /;/metadata Doc Change Count : 485 Format : application/pdf Producer : Adobe PDF Library 9.9 Trapped : False Page Count : 72 Creator : Adobe InDesign CS5 (7.0)EXIF Metadata provided by EXIF.tools