Air

Package Heat Pump
RQNL/RQPL Series

Rheem Commercial Classic® Series
Package Heat Pump

RQNL- High Efficiency 13-SEER Series
Nominal Sizes 2-4 Tons [7.03-14.07 kW]

RQPL- High Efficiency 14-SEER Series
Nominal Sizes 2-4 Tons [7.03-14.07 kW]

(14 SEER ONLY)

“Proper sizing and installation of equipment is critical to achieve
optimal performance. Ask your Contractor for details or visit
www.energystar.gov.”

FORM NO. P11-791

Air

Table of Contents
RQNL/RQPL Series

TABLE OF CONTENTS
Unit Features & Benefits ..................................................................................3-4
Model Number Identification ..............................................................................5
Options ............................................................................................................6
General Data
RQNL- Series ..............................................................................................7-8
RQPL- Series ............................................................................................9-11
General Data Notes ..........................................................................................12
Gross Systems Performance Data
RQNL- Series ..........................................................................................13-17
RQPL- Series ..........................................................................................18-23
Indoor Airflow Performance
RQNL- Series ..........................................................................................24-25
RQPL- Series ..........................................................................................26-27
Electrical Data
RQNL- Series................................................................................................28
RQPL- Series................................................................................................28
Electric Heater Kits......................................................................................29-31
Dimensional Data ........................................................................................32-33
Typical Installations ..........................................................................................34
Accessories ................................................................................................35-43
Wiring Diagrams ..........................................................................................44-48
Limited Warranty ..............................................................................................52

2

Air

Unit Features & Benefits
RQNL/RQPL Series

Package Heat Pump Features:
5

(Not Shown)

4

3

Air

Unit Features & Benefits
RQNL/RQPL Series

Features Below Correspond to Photos on Page 3
1. All models feature Scroll® compressors for maximum
efficiency and quiet operation. This unit contains a
special scroll compressor that is designed specifically
to operate with R-410A Refrigerants and polyolester
(POE) oils. The compressor is hermetically sealed and
incorporates internal high temperature motor overload
protection and durable insulation on the motor windings.
It is externally mounted on rubber grommets to reduce
vibration and noise.
2. Louvered condenser compartment for protecting the
coil against yard hazards and/or weather extremes.
3. One-piece top with a deep flange to help keep water
out of the unit.
4. Supply and return air openings feature a one-inch tall
flange to prevent water migration into the ductwork.
5. Access panels have “weep holes” and channels to
further help manage water run-off.
6. Side and down discharge options available on all
models. (Shipped Downflow Standard).

9. Condenser and evaporator coils feature enhanced fins
for better heat transfer and rifled copper tubing for
greater efficiency.
10. Supplemental electric heat strips up to 15 kW are
available (field or factory installed) for periods of
extreme cold temperatures. Single point wiring makes
installation even easier.
11. All units feature an internal trap on the condensate
line eliminating the need for installing an on-site
external trap.
12. Easily accessible control box. Package heat pump
utilizes demand defrost control which monitors the
outdoor ambient temperature, outdoor coil temperature, and compressor run-time to determine when a
defrost cycle is required.
13. Thermal Expansion Valve standard on all models for
superior superheat control, reliability, and energy
efficiency at all operating conditions.
14. Filter Drier Standard on all models (not shown).

7. Easily accessible blower section complete with slideout blower.

15. Rugged Baserail for improved installation and
handling.

8. Refrigerant connections are conveniently located for
easy service diagnostics. Low pressure/loss of charge
protection is standard on all models.

16. Reversing valve directs flow of refrigerant and
reverses the refrigerant flow when heating is required.

4

Air

Model Number Identification
RQNL/RQPL Series

R Q N L — B024 J K 000 X X X
Factory Installed Options
(See Next Page)
Heating Capacity (Factory Installed)
000 = No Resistance Heat
005 = 05 KW Resistance Heat (018-030)
010 = 10 KW Resistance Heat (024-048)
015 = 15 KW Resistance Heat (036-048)
Drive Package
K = Direct Drive
Electrical Designation
J = 208-230V—1PH—60 Hz
C = 208-230V—3PH—60 Hz
Cooling Capacity (BTUH) [kW]
B024 = 24,000 [7.03]
B025 = 24,000 [7.03]
B030 = 30,000 [8.79]
B036 = 36,000 [10.55]
B042 = 42,000 [12.31]
B048 = 48,000 [14.07]
Design Series
L = R-410A
Efficiency Designation
N = 13 SEER High Efficiency
P = 14 SEER High Efficiency
Product Classification
Q = Package Heat Pump
Tradebrand
R = Rheem

[ ] Designates Metric Conversions

5

Air

Options
RQNL/RQPL Series

Instructions for Factory Installed Option(s) Selection
Note: Two characters following the model number will be utilized to designate a factory-installed option or
combination of options. If no factory option(s) is required, nothing follows the model number.
Step 1. After a basic rooftop model is selected, choose a two-character option code from the FACTORY
INSTALLED OPTION SELECTION TABLE.

FACTORY INSTALLED OPTION CODES
Option
Code
AA
AKA
Example: RQNL-B036JK000XX (where XX is factory installed option)
Example: No Options
RQNL-B036JK000
Example: Options with Sideflow
RQNL-B036JK000AKA
Note: Factory installed economizer is not available on these models.

6

Side Flow
No Option
x

General Data
RQNL Series

Air

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]
Model RQNL- Series
Cooling Performance1
Gross Cooling Capacity Btu [kW]
EER/SEER2

B024JK

B030JK

B036CK

B036JK

24,400 [7.15]
11/13

29,000 [8.5]
11/13

36,200 [10.61]
11/13

CONTINUED
36,200 [10.61]
11/13

800/800 [378/378]
23,600 [6.91]

1000/1000 [472/472]
27,800 [8.15]

1200/1250 [566/590]
35,000 [10.26]

1200/1250 [566/590]
35,000 [10.26]

17,600 [5.16]
6,000 [1.76]

20,800 [6.09]
7,000 [2.05]

26,000 [7.62]
9,000 [2.64]

26,000 [7.62]
9,000 [2.64]

2.15

2.53

3.18

3.18

23,600 [6.91]
2.02/3.4
13,000 [3.81]

28,200 [8.26]
2.45/3.4
16,000 [4.69]

34,000 [9.96]
2.86/3.5
19,500 [5.71]

34,000 [9.96]
2.86/3.5
19,500 [5.71]

1.9/2

2.26/2.1

2.61/2.2

2.61/2.2

7.7

7.7

7.7

7.7

1/Scroll
76

1/Scroll
76

1/Scroll
76

1/Scroll
76

Louvered

Louvered

Louvered

Louvered

Rifled
0.375 [9.5]
14.51 [1.35]
1 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
1 / 22 [9]

Rifled
0.375 [9.5]
11.2 [1.04]
2 / 22 [9]

Rifled
0.375 [9.5]
11.2 [1.04]
2 / 22 [9]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type
Tube Type
Tube Size in. [mm]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

5.54 [0.51]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

Direct/1

Direct/1

Direct/1

Direct/1

CFM [L/s]

2700 [1274]

2700 [1274]

2700 [1274]

2700 [1274]

No. Motors/HP

1 at 1/5 HP

1 at 1/5 HP

1 at 1/5 HP

1 at 1/5 HP

1075

1075

1075

1075

FC Centrifugal
1/9x7 [228.6x177.8]
Direct/2

FC Centrifugal
1/10x9 [254x228.6]
Direct/3

FC Centrifugal
1/10x9 [254x228.6]
Direct/1

FC Centrifugal
1/10x9 [254x228.6]
Direct/1

Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)4
Heating Input Btu [kW] Rating
System Power KW/COP
Low Temp. Btuh [kW] Rating
System Power KW/COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil—Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]

Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds

Motor RPM
Indoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter—Type
Furnished

1

1

1

1

1/4

1/2

1/3

1/3

1075

1075

1075

1075

48
Field Supplied

48
Field Supplied

48
Field Supplied

48
Field Supplied

No

No

No

No

(1)1x20x20 [25x508x508]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

Refrigerant Charge Oz. [g]

98 [2778]

108 [3062]

146 [4139]

146 [4139]

Weights
Net Weight lbs. [kg]

391 [177]

444 [201]

471 [214]

468 [212]

401 [182]

455 [206]

482 [219]

479 [217]

(No.) Size Recommended in. [mm]

Ship Weight lbs. [kg]
See Page 12 for Notes.

[ ] Designates Metric Conversions

7

Air

General Data
RQNL Series

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]
Model RQNL- Series

B042CK

B042JK

B048CK

B048JK

43,500 [12.75]
11/13

43,500 [12.75]
11/13

49,000 [14.36]
11/13

49,000 [14.36]
11/13

1400/1400 [661/661]
42,500 [12.45]

1400/1400 [661/661]
42,500 [12.45]

1600/1600 [755/755]
47,500 [13.92]

1600/1600 [755/755]
47,500 [13.92]

31,500 [9.23]
11,000 [3.22]

31,500 [9.23]
11,000 [3.22]

36,000 [10.55]
11,500 [3.37]

36,000 [10.55]
11,500 [3.37]

3.86

3.86

4.31

4.31

41,500 [12.16]
3.65/3.4
24,200 [7.09]

41,500 [12.16]
3.65/3.4
24,200 [7.09]

46,000 [13.48]
3.89/3.4
26,600 [7.79]

46,000 [13.48]
3.89/3.4
26,600 [7.79]

3.43/2.08

3.43/2.08

3.57/2.2

3.57/2.2

7.7

7.7

7.7

7.7

1/Scroll
76

1/Scroll
76

1/Scroll
78

1/Scroll
78

Louvered

Louvered

Louvered

Louvered

Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type
Tube Type
Tube Size in. [mm]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

Direct/1

Direct/1

Direct/1

Direct/1

CFM [L/s]

3300 [1557]

3300 [1557]

3000 [1416]

3000 [1416]

No. Motors/HP

1 at 1/3 HP

1 at 1/3 HP

1 at 1/3 HP

1 at 1/3 HP

1075

1075

1075

1075

FC Centrifugal
1/10x9 [254x228.6]
Direct/2

FC Centrifugal
1/10x9 [254x228.6]
Direct/2

FC Centrifugal
1/10x9 [254x228.6]
Direct/2

FC Centrifugal
1/10x9 [254x228.6]
Direct/2

Cooling Performance1
Gross Cooling Capacity Btu [kW]
EER/SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)4
Heating Input Btu [kW] Rating
System Power KW/COP
Low Temp. Btuh [kW] Rating
System Power KW/COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil—Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]

Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds

Motor RPM
Indoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter—Type
Furnished

1

1

1

1

3/4

3/4

3/4

3/4

1075

1075

1075

1075

48
Field Supplied

48
Field Supplied

48
Field Supplied

48
Field Supplied

No

No

No

No

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

Refrigerant Charge Oz. [g]

176 [4990]

176 [4990]

183 [5188]

183 [5188]

Weights
Net Weight lbs. [kg]

508 [230]

505 [229]

500 [227]

510 [231]

519 [235]

516 [234]

511 [232]

521 [236]

(No.) Size Recommended in. [mm]

Ship Weight lbs. [kg]
See Page 12 for Notes.

8

[ ] Designates Metric Conversions

General Data
RQPL Series

Air

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]
Model RQPL- Series
Cooling Performance1
Gross Cooling Capacity Btu [kW]
EER/SEER2

B024JK

B025JK

B030JK

B036CK

25,000 [7.32]
11.8/14

24,400 [7.15]
12/14

29,800 [8.73]
12/14

CONTINUED
36,800 [10.78]
12/14

800/850 [378/401]
24,400 [7.15]

800/850 [378/401]
23,800 [6.97]

1000/1050 [472/495]
29,200 [8.56]

1200/1250 [566/590]
36,000 [10.55]

18,900 [5.54]
5,500 [1.61]

17,800 [5.22]
6,000 [1.76]

23,000 [6.74]
6,200 [1.82]

27,000 [7.91]
9,000 [2.64]

2.06

1.98

2.43

3

23,800 [6.97]
1.94/3.5
13,800 [4.04]

23,600 [6.91]
1.88/3.7
12,900 [3.78]

27,800 [8.15]
2.27/3.6
15,500 [4.54]

33,200 [9.73]
2.73/3.6
18,000 [5.27]

1.78/2.2

1.7/2.24

2.07/2.2

2.5/2.2

8

8

8

8

1/Scroll
76

1/Scroll
76

1/Scroll
76

1/Scroll
76

Louvered

Louvered

Louvered

Louvered

Rifled
0.375 [9.5]
14.51 [1.35]
1 / 22 [9]

Rifled
0.375 [9.5]
14.51 [1.35]
1 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
1 / 22 [9]

Rifled
0.375 [9.5]
11.2 [1.04]
2 / 22 [9]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type
Tube Type
Tube Size in. [mm]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

5.54 [0.51]

5.54 [0.51]

7.39 [0.69]

7.39 [0.69]

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

Direct/1

Direct/1

Direct/1

Direct/1

CFM [L/s]

2700 [1274]

2700 [1274]

2700 [1274]

2700 [1274]

No. Motors/HP

1 at 1/5 HP

1 at 1/3 HP

1 at 1/5 HP

1 at 1/5 HP

1075

869

1075

1075

FC Centrifugal
1/9x7 [228.6x177.8]
Direct/2

FC Centrifugal
1/9x7 [229x178]
Direct/2

FC Centrifugal
1/10x9 [254x228.6]
Direct/3

FC Centrifugal
1/10x9 [254x228.6]
Direct/3

Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)4
Heating Input Btu [kW] Rating
System Power KW/COP
Low Temp. Btuh [kW] Rating
System Power KW/COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil—Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]

Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds

Motor RPM
Indoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter—Type
Furnished

1

1

1

1

1/3

1/3

1/2

1/2

1050

1050

1050

1075

48
Field Supplied

48
Field Supplied

48
Field Supplied

48
Field Supplied

No

No

No

No

(1)1x20x20 [25x508x508]

(1)1x20x20 [25x508x508]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

Refrigerant Charge Oz. [g]

98 [2778]

98 [2778]

108 [3062]

146 [4139]

Weights
Net Weight lbs. [kg]

391 [177]

391 [177]

444 [201]

471 [214]

401 [182]

401 [182]

455 [206]

482 [219]

(No.) Size Recommended in. [mm]

Ship Weight lbs. [kg]
See Page 12 for Notes.

[ ] Designates Metric Conversions

9

Air

General Data
RQPL Series

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]
Model RQPL- Series
Cooling Performance1
Gross Cooling Capacity Btu [kW]
EER/SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)4
Heating Input Btu [kW] Rating
System Power KW/COP
Low Temp. Btuh [kW] Rating
System Power KW/COP
HSPF (Btu/Watts-hr)

B036JK

B042CK

B042JK

B048CK

36,800 [10.78]
12/14

43,500 [12.75]
11.3/14

43,500 [12.75]
11.3/14

CONTINUED
49,000 [14.36]
11.5/14

1200/1250 [566/590]
36,000 [10.55]

1400/1400 [661/661]
42,500 [12.45]

1400/1400 [661/661]
42,500 [12.45]

1600/1600 [755/755]
47,500 [13.92]

27,000 [7.91]
9,000 [2.64]

31,500 [9.23]
11,000 [3.22]

31,500 [9.23]
11,000 [3.22]

36,000 [10.55]
11,500 [3.37]

3

3.85

3.85

4.26

33,200 [9.73]
2.73/3.6
18,000 [5.27]

41,500 [12.16]
3.65/3.4
24,200 [7.09]

41,500 [12.16]
3.65/3.4
24,200 [7.09]

46,000 [13.48]
3.89/3.45
26,600 [7.79]

2.5/2.2

3.43/2.08

3.43/2.08

3.57/2.2

8

8

8

8

1/Scroll
76

1/Scroll
76

1/Scroll
76

1/Scroll
78

Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil—Fin Type

Louvered

Louvered

Louvered

Louvered

Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]

Rifled
0.375 [9.5]
11.2 [1.04]
2 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Refrigerant Control

TX Valves

TX Valves

TX Valves

TX Valves

Indoor Coil—Fin Type
Tube Type
Tube Size in. [mm]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

Louvered
Rifled
0.375 [9.5]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

7.39 [0.69]

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

1/22 [558.8]

Direct/1

Direct/1

Direct/1

Direct/1

CFM [L/s]

2700 [1274]

3300 [1557]

3300 [1557]

3000 [1416]

No. Motors/HP

1 at 1/5 HP

1 at 1/3 HP

1 at 1/3 HP

1 at 1/3 HP

1075

1075

1075

1075

FC Centrifugal
1/10x9 [254x228.6]
Direct/3

FC Centrifugal
1/10x9 [254x228.6]
Direct/2

FC Centrifugal
1/10x9 [254x228.6]
Direct/2

FC Centrifugal
1/10x9 [254x228.6]
Direct/2

Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds

Motor RPM
Indoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter—Type
Furnished

1

1

1

1

1/2

3/4

3/4

3/4

1050

1075

1075

1075

48
Field Supplied

48
Field Supplied

48
Field Supplied

48
Field Supplied

No

No

No

No

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

(1)1x24x24 [25x610x610]

Refrigerant Charge Oz. [g]

146 [4139]

176 [4990]

176 [4990]

183 [5188]

Weights
Net Weight lbs. [kg]

468 [212]

508 [230]

505 [229]

500 [227]

479 [217]

519 [235]

516 [234]

511 [232]

(No.) Size Recommended in. [mm]

Ship Weight lbs. [kg]
See Page 12 for Notes.

10

[ ] Designates Metric Conversions

Air

General Data
RQPL Series

NOMINAL SIZES 2-4 TONS [7.03-14.07 kW]
Model RQPL- Series
Cooling Performance1
Gross Cooling Capacity Btu [kW]
EER/SEER2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
Heating Performance (Heat Pumps)4
Heating Input Btu [kW] Rating
System Power KW/COP
Low Temp. Btuh [kW] Rating
System Power KW/COP
HSPF (Btu/Watts-hr)

B048JK
49,000 [14.36]
11.5/14
1600/1600 [755/755]
47,500 [13.92]
36,000 [10.55]
11,500 [3.37]
4.26
46,000 [13.48]
3.89/3.45
26,600 [7.79]
3.57/2.2
8

Compressor
No./Type
Outdoor Sound Rating (dB)3
Outdoor Coil—Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]

1/Scroll
78
Louvered
Rifled
0.375 [9.5]
16.32 [1.52]
2 / 22 [9]

Refrigerant Control

TX Valves

Indoor Coil—Fin Type
Tube Type
Tube Size in. [mm]

Louvered
Rifled
0.375 [9.5]

Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds

7.39 [0.69]
2 / 15 [6]
TX Valves
1/1 [25.4]
Propeller
1/22 [558.8]
Direct/1

CFM [L/s]

3000 [1416]

No. Motors/HP

1 at 1/3 HP

Motor RPM
Indoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter—Type
Furnished
(No.) Size Recommended in. [mm]

1075
FC Centrifugal
1/10x9 [254x228.6]
Direct/2
1
3/4
1075
48
Field Supplied
No
(1)1x24x24 [25x610x610]

Refrigerant Charge Oz. [g]

183 [5188]

Weights
Net Weight lbs. [kg]

510 [231]

Ship Weight lbs. [kg]
See Page 12 for Notes.

521 [236]
[ ] Designates Metric Conversions

11

Air

General Data Notes
RQNL/RQPL Series

NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does
not include the effect of fan motor heat. AHRI capacity is net and includes the effect of fan motor heat. Units are
suitable for operation in CFM range shown in airflow tables. Units are certified in accordance with the Unitary Air
Conditioner Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
4. Heating Performance is rated at 47° F ambient, 70° F entering dry bulb for High Temp rating and 17° F ambient, 70° F
entering dry bulb for Low Temp rating. Performance ratings do include the effect of fan motor heat.

12

Air

Gross Systems Performance Data
RQNL Series

COOLING PERFORMANCE DATA—RQNL-024
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

880 [415]
.17

71°F [21.7°C]
800 [378]
.15

720 [340]
.13

880 [415]
.17

67°F [19.4°C]
800 [378]
.15

720 [340]
.13

880 [415]
.17

63°F [17.2°C]
800 [378]
.15

720 [340]
.13

Total BTUH [kW]
75
Sens BTUH [kW]
[23.9]
Power

29.4 [8.62]
18.2 [5.33]
1.5

28.9 [8.47]
17.4 [5.10]
1.5

28.3 [8.29]
16.6 [4.86]
1.5

28.1 [8.24]
21.0 [6.15]
1.5

27.6 [8.09]
20.1 [5.89]
1.5

27.1 [7.94]
19.1 [5.60]
1.5

27.1 [7.94]
22.3 [6.54]
1.5

26.6 [7.80]
21.3 [6.24]
1.5

26.1 [7.65]
20.3 [5.95]
1.5

Total BTUH [kW]
80
Sens BTUH [kW]
[26.7]
Power

29.2 [8.56]
18.0 [5.28]
1.6

28.6 [8.38]
17.2 [5.04]
1.6

28.1 [8.24]
16.4 [4.81]
1.6

27.8 [8.15]
20.8 [6.10]
1.6

27.3 [8.00]
19.8 [5.80]
1.6

26.8 [7.85]
18.9 [5.54]
1.6

26.8 [7.85]
22.1 [6.48]
1.6

26.4 [7.74]
21.1 [6.18]
1.6

25.9 [7.59]
20.1 [5.89]
1.6

Total BTUH [kW]
85
Sens BTUH [kW]
[29.4]
Power

28.5 [8.35]
17.6 [5.16]
1.7

28.0 [8.21]
16.8 [4.92]
1.7

27.5 [8.06]
16.0 [4.69]
1.7

27.2 [7.97]
20.4 [5.98]
1.7

26.7 [7.83]
19.5 [5.71]
1.7

26.2 [7.68]
18.6 [5.45]
1.7

26.2 [7.68]
21.7 [6.36]
1.7

25.7 [7.53]
20.7 [6.07]
1.7

25.2 [7.39]
19.7 [5.77]
1.7

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

27.5 [8.06]
17.1 [5.01]
1.8

27.0 [7.91]
16.3 [4.78]
1.8

26.5 [7.77]
15.6 [4.57]
1.8

26.1 [7.65]
19.9 [5.83]
1.8

25.7 [7.53]
19.0 [5.57]
1.8

25.2 [7.39]
18.1 [5.30]
1.8

25.2 [7.39]
21.2 [6.21]
1.8

24.7 [7.24]
20.2 [5.92]
1.8

24.3 [7.12]
19.3 [5.66]
1.8

26.2 [7.68]
16.5 [4.84]
1.9

25.8 [7.56]
15.8 [4.63]
1.9

25.3 [7.41]
15.0 [4.40]
1.9

24.9 [7.30]
19.3 [5.66]
1.9

24.5 [7.18]
18.5 [5.42]
1.9

24.0 [7.03]
17.6 [5.16]
1.9

23.9 [7.00]
20.6 [6.04]
1.9

23.5 [6.89]
19.7 [5.77]
1.9

23.1 [6.77]
18.8 [5.51]
1.9

24.9 [7.30]
15.9 [4.66]
2.0

24.4 [7.15]
15.2 [4.45]
2.0

24.0 [7.03]
14.5 [4.25]
2.0

23.5 [6.89]
18.7 [5.48]
2.0

23.1 [6.77]
17.9 [5.25]
2.0

22.7 [6.65]
17.0 [4.98]
2.0

22.5 [6.59]
20.0 [5.86]
2.0

22.1 [6.48]
19.1 [5.60]
2.0

21.7 [6.36]
18.2 [5.33]
2.0

Total BTUH [kW]
105
Sens BTUH [kW]
[40.6]
Power

23.5 [6.89]
15.2 [4.45]
2.1

23.1 [6.77]
14.5 [4.25]
2.1

22.7 [6.65]
13.9 [4.07]
2.1

22.2 [6.51]
18.0 [5.28]
2.1

21.8 [6.39]
17.2 [5.04]
2.1

21.4 [6.27]
16.4 [4.81]
2.1

21.2 [6.21]
19.3 [5.66]
2.1

20.8 [6.10]
18.5 [5.42]
2.1

20.4 [5.98]
17.6 [5.16]
2.1

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power

22.2 [6.51]
14.6 [4.28]
2.2
21.1 [6.18]
14.0 [4.10]
2.3

21.8 [6.39]
14.0 [4.10]
2.2
20.7 [6.07]
13.4 [3.93]
2.3

21.4 [6.27]
13.3 [3.90]
2.2
20.3 [5.95]
12.8 [3.75]
2.3

20.9 [6.13]
17.4 [5.10]
2.2
19.8 [5.80]
16.9 [4.95]
2.3

20.5 [6.01]
16.7 [4.89]
2.2
19.4 [5.69]
16.1 [4.72]
2.3

20.1 [5.89]
15.9 [4.66]
2.2
19.0 [5.57]
15.4 [4.51]
2.3

19.9 [5.83]
18.7 [5.48]
2.2
18.8 [5.51]
18.1 [5.30]
2.3

19.5 [5.71]
17.9 [5.25]
2.2
18.4 [5.39]
17.3 [5.07]
2.3

19.2 [5.63]
17.0 [4.98]
2.2
18.1 [5.30]
16.5 [4.84]
2.3

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNL-024
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

880 [415]

60°F [15.5°C]
800 [378]

720 [340]

880 [415]

70°F [21.1°C]
800 [378]

720 [340]

880 [415]

80°F [26.7°C]
800 [378]

720 [340]

8.3 [2.43]
1.4
10.0 [2.93]
1.4
11.6 [3.40]
1.4
13.2 [3.87]
1.4
14.9 [4.37]
1.5
16.5 [4.84]
1.5
18.1 [5.30]
1.5
19.8 [5.80]
1.5
21.4 [6.27]
1.5
23.0 [6.74]
1.6
24.7 [7.24]
1.6

8.3 [2.43]
1.4
9.9 [2.90]
1.4
11.5 [3.37]
1.4
13.1 [3.84]
1.5
14.8 [4.34]
1.5
16.4 [4.81]
1.5
18.0 [5.28]
1.5
19.6 [5.74]
1.5
21.3 [6.24]
1.6
22.9 [6.71]
1.6
24.5 [7.18]
1.6

8.2 [2.40]
1.4
9.8 [2.87]
1.4
11.4 [3.34]
1.5
13.0 [3.81]
1.5
14.7 [4.31]
1.5
16.3 [4.78]
1.5
17.9 [5.25]
1.5
19.5 [5.71]
1.6
21.1 [6.18]
1.6
22.7 [6.65]
1.6
24.3 [7.12]
1.6

7.4 [2.17]
1.6
9.1 [2.67]
1.6
10.7 [3.14]
1.6
12.3 [3.60]
1.6
14.0 [4.10]
1.6
15.6 [4.57]
1.7
17.2 [5.04]
1.7
18.9 [5.54]
1.7
20.5 [6.01]
1.7
22.1 [6.48]
1.7
23.8 [6.98]
1.8

7.4 [2.17]
1.6
9.0 [2.64]
1.6
10.6 [3.11]
1.6
12.3 [3.60]
1.6
13.9 [4.07]
1.7
15.5 [4.54]
1.7
17.1 [5.01]
1.7
18.7 [5.48]
1.7
20.4 [5.98]
1.7
22.0 [6.45]
1.8
23.6 [6.92]
1.8

7.3 [2.14]
1.6
9.0 [2.64]
1.6
10.6 [3.11]
1.6
12.2 [3.58]
1.7
13.8 [4.04]
1.7
15.4 [4.51]
1.7
17.0 [4.98]
1.7
18.6 [5.45]
1.7
20.2 [5.92]
1.8
21.8 [6.39]
1.8
23.4 [6.86]
1.8

6.0 [1.76]
1.8
7.6 [2.23]
1.8
9.3 [2.73]
1.8
10.9 [3.19]
1.9
12.5 [3.66]
1.9
14.2 [4.16]
1.9
15.8 [4.63]
1.9
17.4 [5.10]
1.9
19.1 [5.60]
2.0
20.7 [6.07]
2.0
22.3 [6.54]
2.0

6.0 [1.76]
1.8
7.6 [2.23]
1.8
9.2 [2.70]
1.9
10.8 [3.17]
1.9
12.5 [3.66]
1.9
14.1 [4.13]
1.9
15.7 [4.60]
2.0
17.3 [5.07]
2.0
18.9 [5.54]
2.0
20.6 [6.04]
2.0
22.2 [6.51]
2.0

5.9 [1.73]
1.9
7.5 [2.20]
1.9
9.1 [2.67]
1.9
10.8 [3.17]
1.9
12.4 [3.63]
1.9
14.0 [4.10]
2.0
15.6 [4.57]
2.0
17.2 [5.04]
2.0
18.8 [5.51]
2.0
20.4 [5.98]
2.0
22.0 [6.45]
2.1

[ ] Designates Metric Conversions

13

Air

Gross Systems Performance Data
RQNL Series

COOLING PERFORMANCE DATA—RQNL-030
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1000 [472]
.18

900 [425]
.16

1100 [519]
.02

67°F [19.4°C]
1000 [472]
.18

900 [425]
.16

1100 [519]
.02

63°F [17.2°C]
1000 [472
.18

900 [425]
.16

Total BTUH [kW] 36.1 [10.58]
75
Sens BTUH [kW] 22.0 [6.45]
[23.9]
1.9
Power

35.4 [10.37]
21.0 [6.15]
1.9

34.8 [10.20]
20.0 [5.86]
1.8

34.1 [9.99]
25.3 [7.41]
1.8

33.4 [9.79]
24.2 [7.09]
1.8

32.8 [9.61]
23.0 [6.74]
1.8

32.7 [9.58]
26.7 [7.83]
1.9

32.1 [9.41]
25.5 [7.47]
1.9

31.5 [9.23]
24.3 [7.12]
1.8

Total BTUH [kW] 34.9 [10.23]
80
Sens BTUH [kW] 21.4 [6.27]
[26.7]
2.0
Power

34.3 [10.05]
20.4 [5.98]
1.9

33.6 [9.85]
19.5 [5.71]
1.9

32.9 [9.64]
24.7 [7.24]
1.9

32.3 [9.47]
23.6 [6.92]
1.9

31.7 [9.29]
22.5 [6.59]
1.9

31.5 [9.23]
26.1 [7.65]
2.0

31.0 [9.09]
25.0 [7.33]
1.9

30.4 [8.91]
23.8 [6.98]
1.9

Total BTUH [kW] 33.8 [9.91]
85
Sens BTUH [kW] 20.8 [6.10]
[29.4]
2.1
Power

33.2 [9.73]
19.9 [5.83]
2.0

32.6 [9.55]
19.0 [5.57]
2.0

31.8 [9.32]
24.1 [7.06]
2.0

31.2 [9.14]
23.0 [6.74]
2.0

30.6 [8.97]
22.0 [6.45]
2.0

30.4 [8.91]
25.5 [7.47]
2.1

29.8 [8.73]
24.4 [7.15]
2.0

29.3 [8.59]
23.3 [6.83]
2.0

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

32.6 [9.55]
20.2 [5.92]
2.2

32.0 [9.38]
19.3 [5.66]
2.1

31.5 [9.23]
18.4 [5.39]
2.1

30.6 [8.97]
23.5 [6.89]
2.1

30.1 [8.82]
22.5 [6.59]
2.1

29.5 [8.65]
21.4 [6.27]
2.1

29.3 [8.59]
25.0 [7.33]
2.2

28.7 [8.41]
23.9 [7.00]
2.1

28.2 [8.26]
22.7 [6.65]
2.1

31.5 [9.23]
19.7 [5.77]
2.2

30.9 [9.06]
18.8 [5.51]
2.2

30.4 [8.91]
17.9 [5.25]
2.2

29.5 [8.65]
23.0 [6.74]
2.2

29.0 [8.50]
22.0 [6.45]
2.2

28.4 [8.32]
20.9 [6.13]
2.2

28.1 [8.24]
24.4 [7.15]
2.2

27.6 [8.09]
23.3 [6.83]
2.2

27.1 [7.94]
22.2 [6.51]
2.2

30.3 [8.88]
19.2 [5.63]
2.3

29.8 [8.73]
18.3 [5.36]
2.3

29.3 [8.59]
17.4 [5.10]
2.3

28.3 [8.29]
22.4 [6.56]
2.3

27.8 [8.15]
21.4 [6.27]
2.3

27.3 [8.00]
20.4 [5.98]
2.3

27.0 [7.91]
23.9 [7.00]
2.3

26.5 [7.77]
22.8 [6.68]
2.3

26.0 [7.62]
21.7 [6.36]
2.3

Total BTUH [kW] 29.2 [8.56]
105
Sens BTUH [kW] 18.6 [5.45]
[40.6]
2.4
Power

28.6 [8.38]
17.8 [5.22]
2.4

28.1 [8.24]
16.9 [4.95]
2.4

27.2 [7.97]
21.9 [6.42]
2.4

26.7 [7.83]
20.9 [6.13]
2.4

26.2 [7.68]
19.9 [5.83]
2.4

25.8 [7.56]
23.3 [6.83]
2.4

25.3 [7.41]
22.3 [6.54]
2.4

24.9 [7.30]
21.3 [6.24]
2.4

27.4 [8.03]
17.3 [5.07]
2.5
26.1 [7.65]
16.7 [4.89]
2.6

26.9 [7.88]
16.5 [4.84]
2.5
25.7 [7.53]
15.9 [4.66]
2.6

25.9 [7.59]
21.4 [6.27]
2.5
24.6 [7.21]
20.8 [6.10]
2.6

25.5 [7.47]
20.4 [5.98]
2.5
24.2 [7.09]
19.9 [5.83]
2.6

25.0 [7.33]
19.5 [5.71]
2.5
23.7 [6.95]
19.0 [5.57]
2.5

24.6 [7.21]
22.8 [6.68]
2.5
23.3 [6.83]
22.2 [6.51]
2.6

24.1 [7.06]
21.8 [6.39]
2.5
22.8 [6.68]
21.2 [6.21]
2.6

23.7 [6.95]
20.8 [6.10]
2.5
22.4 [6.56]
20.3 [5.95]
2.6

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1100 [519]
.02

27.9 [8.18]
18.1 [5.30]
2.5
26.6 [7.80]
17.5 [5.13]
2.6

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNL-030
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

14

1100 [519]

60°F [15.5°C]
1000 [472]

900 [425]

1100 [519]

70°F [21.1°C]
1000 [472]

900 [425]

1100 [519]

80°F [26.7°C]
1000 [472

900 [425]

9.3 [2.73]
1.6
11.3 [3.31]
1.6
13.2 [3.87]
1.6
15.1 [4.43]
1.7
17.0 [4.98]
1.7
18.9 [5.54]
1.7
20.9 [6.13]
1.8
22.8 [6.68]
1.8
24.7 [7.24]
1.8
26.6 [7.80]
1.9
28.6 [8.38]
1.9

9.3 [2.73]
1.6
11.2 [3.28]
1.6
13.1 [3.84]
1.7
15.0 [4.40]
1.7
16.9 [4.95]
1.7
18.8 [5.51]
1.8
20.7 [6.07]
1.8
22.6 [6.62]
1.8
24.5 [7.18]
1.8
26.4 [7.74]
1.9
28.4 [8.32]
1.9

9.2 [2.70]
1.6
11.1 [3.25]
1.6
13.0 [3.81]
1.7
14.9 [4.37]
1.7
16.8 [4.92]
1.7
18.7 [5.48]
1.8
20.6 [6.04]
1.8
22.5 [6.59]
1.8
24.4 [7.15]
1.9
26.3 [7.71]
1.9
28.2 [8.26]
1.9

7.8 [2.29]
1.8
9.7 [2.84]
1.8
11.6 [3.40]
1.9
13.5 [3.96]
1.9
15.5 [4.54]
1.9
17.4 [5.10]
1.9
19.3 [5.66]
2.0
21.2 [6.21]
2.0
23.2 [6.80]
2.0
25.1 [7.36]
2.1
27.0 [7.91]
2.1

7.7 [2.26]
1.8
9.6 [2.81]
1.8
11.5 [3.37]
1.9
13.5 [3.96]
1.9
15.4 [4.51]
1.9
17.3 [5.07]
2.0
19.2 [5.63]
2.0
21.1 [6.18]
2.0
23.0 [6.74]
2.1
24.9 [7.30]
2.1
26.8 [7.85]
2.1

7.7 [2.26]
1.8
9.6 [2.81]
1.9
11.5 [3.37]
1.9
13.4 [3.93]
1.9
15.3 [4.48]
2.0
17.1 [5.01]
2.0
19.0 [5.57]
2.0
20.9 [6.13]
2.1
22.8 [6.68]
2.1
24.7 [7.24]
2.1
26.6 [7.80]
2.1

6.4 [1.88]
2.0
8.3 [2.43]
2.0
10.2 [2.99]
2.1
12.1 [3.55]
2.1
14.0 [4.10]
2.1
16.0 [4.69]
2.2
17.9 [5.25]
2.2
19.8 [5.80]
2.2
21.7 [6.36]
2.3
23.7 [6.95]
2.3
25.6 [7.50]
2.3

6.3 [1.85]
2.0
8.2 [2.40]
2.1
10.1 [2.96]
2.1
12.0 [3.52]
2.1
13.9 [4.07]
2.2
15.9 [4.66]
2.2
17.8 [5.22]
2.2
19.7 [5.77]
2.3
21.6 [6.33]
2.3
23.5 [6.89]
2.3
25.4 [7.44]
2.4

6.3 [1.85]
2.1
8.2 [2.40]
2.1
10.1 [2.96]
2.1
12.0 [3.52]
2.2
13.8 [4.04]
2.2
15.7 [4.60]
2.2
17.6 [5.16]
2.3
19.5 [5.71]
2.3
21.4 [6.27]
2.3
23.3 [6.83]
2.3
25.2 [7.39]
2.4

[ ] Designates Metric Conversions

Air

Gross Systems Performance Data
RQNL Series

COOLING PERFORMANCE DATA—RQNL-036
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1250 [590]
.19

1120 [528]
.17

1380 [651]
.21

67°F [19.4°C]
1250 [590]
.19

1120 [528]
.17

1380 [651]
.21

63°F [17.2°C]
1250 [590]
.19

1120 [528]
.17

Total BTUH [kW] 44.5 [13.04]
75
Sens BTUH [kW] 27.2 [7.97]
[23.9]
2.3
Power

43.7 [12.81]
26.0 [7.62]
2.3

42.9 [12.57]
24.8 [7.27]
2.2

42.5 [12.46]
31.3 [9.17]
2.3

41.7 [12.22]
29.9 [8.76]
2.2

40.9 [11.99]
28.5 [8.35]
2.2

41.3 [12.10]
33.7 [9.88]
2.2

40.6 [11.90]
32.2 [9.44]
2.2

39.8 [11.66]
30.7 [9.00]
2.2

Total BTUH [kW] 43.4 [12.72]
80
Sens BTUH [kW] 26.6 [7.80]
[26.7]
2.4
Power

42.6 [12.48]
25.4 [7.44]
2.4

41.8 [12.25]
24.2 [7.09]
2.4

41.3 [12.10]
30.7 [9.00]
2.4

40.6 [11.90]
29.3 [8.59]
2.4

39.9 [11.69]
27.9 [8.18]
2.4

40.2 [11.78]
33.0 [9.67]
2.4

39.5 [11.58]
31.6 [9.26]
2.4

38.8 [11.37]
30.1 [8.82]
2.3

Total BTUH [kW] 42.1 [12.34]
85
Sens BTUH [kW] 26.0 [7.62]
[29.4]
2.6
Power

41.3 [12.10]
24.8 [7.27]
2.5

40.6 [11.90]
23.6 [6.92]
2.5

40.0 [11.72]
30.0 [8.79]
2.5

39.3 [11.52]
28.7 [8.41]
2.5

38.6 [11.31]
27.3 [8.00]
2.5

38.9 [11.40]
32.4 [9.50]
2.5

38.2 [11.20]
30.9 [9.06]
2.5

37.5 [10.99]
29.5 [8.65]
2.5

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

40.6 [11.90]
25.3 [7.41]
2.7

39.9 [11.69]
24.1 [7.06]
2.7

39.1 [11.46]
23.0 [6.74]
2.7

38.5 [11.28]
29.3 [8.59]
2.7

37.9 [11.11]
28.0 [8.21]
2.7

37.2 [10.90]
26.7 [7.83]
2.6

37.4 [10.96]
31.7 [9.29]
2.7

36.7 [10.76]
30.3 [8.88]
2.6

36.1 [10.58]
28.8 [8.44]
2.6

39.0 [11.43]
24.5 [7.18]
2.9

38.3 [11.22]
23.4 [6.86]
2.8

37.6 [11.02]
22.3 [6.54]
2.8

36.9 [10.81]
28.6 [8.38]
2.8

36.3 [10.64]
27.3 [8.00]
2.8

35.6 [10.43]
26.0 [7.62]
2.8

35.8 [10.49]
30.9 [9.06]
2.8

35.2 [10.32]
29.6 [8.67]
2.8

34.5 [10.11]
28.2 [8.26]
2.8

37.3 [10.93]
23.7 [6.95]
3.0

36.7 [10.76]
22.7 [6.65]
3.0

36.0 [10.55]
21.6 [6.33]
2.9

35.3 [10.35]
27.8 [8.15]
3.0

34.6 [10.14]
26.5 [7.77]
2.9

34.0 [9.96]
25.3 [7.41]
2.9

34.1 [9.99]
30.2 [8.85]
3.0

33.5 [9.82]
28.8 [8.44]
2.9

32.9 [9.64]
27.5 [8.06]
2.9

Total BTUH [kW] 35.6 [10.43]
105
Sens BTUH [kW] 22.9 [6.71]
[40.6]
3.1
Power

35.0 [10.26]
21.9 [6.42]
3.1

34.4 [10.08]
20.9 [6.13]
3.1

33.6 [9.85]
27.0 [7.91]
3.1

33.0 [9.67]
25.8 [7.56]
3.1

32.4 [9.50]
24.6 [7.21]
3.1

32.4 [9.50]
29.4 [8.62]
3.1

31.9 [9.35]
28.1 [8.24]
3.1

31.3 [9.17]
26.7 [7.83]
3.0

33.4 [9.79]
21.1 [6.18]
3.3
31.8 [9.32]
20.3 [5.95]
3.4

32.7 [9.58]
20.1 [5.89]
3.2
31.2 [9.14]
19.4 [5.69]
3.4

31.9 [9.35]
26.2 [7.68]
3.3
30.3 [8.88]
25.3 [7.41]
3.4

31.3 [9.17]
25.0 [7.33]
3.2
29.8 [8.73]
24.2 [7.09]
3.4

30.8 [9.03]
23.8 [6.98]
3.2
29.2 [8.56]
23.1 [6.77]
3.3

30.8 [9.03]
28.5 [8.35]
3.2
29.2 [8.56]
27.7 [8.12]
3.4

30.2 [8.85]
27.3 [8.00]
3.2
28.6 [8.38]
26.5 [7.77]
3.4

29.7 [8.70]
26.0 [7.62]
3.2
28.1 [8.24]
25.2 [7.39]
3.3

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1380 [651]
.21

34.0 [9.96]
22.1 [6.48]
3.3
32.4 [9.50]
21.3 [6.24]
3.4

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNL-036
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

1380 [651]

60°F [15.5°C]
1250 [590]

1120 [528]

1380 [651]

70°F [21.1°C]
1250 [590]

1120 [528]

1380 [651]

80°F [26.7°C]
1250 [590]

1120 [528]

11.9 [3.49]
1.8
14.4 [4.22]
1.9
16.8 [4.92]
1.9
19.3 [5.66]
1.9
21.7 [6.36]
2.0
24.2 [7.09]
2.0
26.7 [7.83]
2.1
29.1 [8.53]
2.1
31.6 [9.26]
2.1
34.0 [9.96]
2.2
36.5 [10.70]
2.2

11.9 [3.49]
1.8
14.3 [4.19]
1.9
16.7 [4.89]
1.9
19.2 [5.63]
2.0
21.6 [6.33]
2.0
24.0 [7.03]
2.0
26.5 [7.77]
2.1
28.9 [8.47]
2.1
31.3 [9.17]
2.2
33.8 [9.91]
2.2
36.2 [10.61]
2.2

11.8 [3.46]
1.9
14.2 [4.16]
1.9
16.6 [4.86]
1.9
19.0 [5.57]
2.0
21.4 [6.27]
2.0
23.9 [7.00]
2.1
26.3 [7.71]
2.1
28.7 [8.41]
2.2
31.1 [9.11]
2.2
33.5 [9.82]
2.2
35.9 [10.52]
2.3

9.9 [2.90]
2.1
12.4 [3.63]
2.1
14.8 [4.34]
2.2
17.3 [5.07]
2.2
19.7 [5.77]
2.2
22.2 [6.51]
2.3
24.6 [7.21]
2.3
27.1 [7.94]
2.4
29.5 [8.65]
2.4
32.0 [9.38]
2.4
34.4 [10.08]
2.5

9.8 [2.87]
2.1
12.3 [3.60]
2.1
14.7 [4.31]
2.2
17.1 [5.01]
2.2
19.6 [5.74]
2.3
22.0 [6.45]
2.3
24.4 [7.15]
2.3
26.9 [7.88]
2.4
29.3 [8.59]
2.4
31.7 [9.29]
2.5
34.2 [10.02]
2.5

9.8 [2.87]
2.1
12.2 [3.58]
2.2
14.6 [4.28]
2.2
17.0 [4.98]
2.2
19.4 [5.69]
2.3
21.8 [6.39]
2.3
24.3 [7.12]
2.4
26.7 [7.83]
2.4
29.1 [8.53]
2.5
31.5 [9.23]
2.5
33.9 [9.94]
2.5

8.5 [2.49]
2.4
11.0 [3.22]
2.4
13.4 [3.93]
2.4
15.9 [4.66]
2.5
18.3 [5.36]
2.5
20.8 [6.10]
2.6
23.2 [6.80]
2.6
25.7 [7.53]
2.6
28.1 [8.24]
2.7
30.6 [8.97]
2.7
33.0 [9.67]
2.8

8.5 [2.49]
2.4
10.9 [3.19]
2.4
13.3 [3.90]
2.5
15.8 [4.63]
2.5
18.2 [5.33]
2.6
20.6 [6.04]
2.6
23.1 [6.77]
2.6
25.5 [7.47]
2.7
27.9 [8.18]
2.7
30.4 [8.91]
2.8
32.8 [9.61]
2.8

8.4 [2.46]
2.4
10.8 [3.17]
2.5
13.2 [3.87]
2.5
15.7 [4.60]
2.5
18.1 [5.30]
2.6
20.5 [6.01]
2.6
22.9 [6.71]
2.7
25.3 [7.41]
2.7
27.7 [8.12]
2.8
30.2 [8.85]
2.8
32.6 [9.55]
2.8

[ ] Designates Metric Conversions

15

Air

Gross Systems Performance Data
RQNL Series

COOLING PERFORMANCE DATA—RQNL-042
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1400 [661]
.15

1260 [595]
.14

1540 [727]
.17

67°F [19.4°C]
1400 [661]
.15

1260 [595]
.14

1540 [727]
.17

63°F [17.2°C]
1400 [661]
.15

1260 [595]
.14

Total BTUH [kW] 53.9 [15.80]
75
Sens BTUH [kW] 32.2 [9.44]
[23.9]
2.9
Power

52.9 [15.50]
30.7 [9.00]
2.9

51.9 [15.21]
29.3 [8.59]
2.9

50.9 [14.92]
37.1 [10.87]
2.9

50.0 [14.65]
35.5 [10.40]
2.9

49.1 [14.39]
33.8 [9.91]
2.9

48.1 [14.10]
39.3 [11.52]
2.9

47.3 [13.86]
37.5 [10.99]
2.9

46.4 [13.60]
35.8 [10.49]
2.9

Total BTUH [kW] 52.0 [15.24]
80
Sens BTUH [kW] 31.3 [9.17]
[26.7]
3.1
Power

51.0 [14.95]
29.9 [8.76]
3.1

50.1 [14.68]
28.5 [8.35]
3.1

49.0 [14.36]
36.3 [10.64]
3.1

48.1 [14.10]
34.7 [10.17]
3.1

47.2 [13.83]
33.0 [9.67]
3.1

46.2 [13.54]
38.4 [11.25]
3.1

45.4 [13.31]
36.7 [10.76]
3.1

44.6 [13.07]
35.0 [10.26]
3.0

Total BTUH [kW] 50.3 [14.74]
85
Sens BTUH [kW] 30.5 [8.94]
[29.4]
3.3
Power

49.4 [14.48]
29.2 [8.56]
3.3

48.5 [14.21]
27.8 [8.15]
3.2

47.3 [13.86]
35.5 [10.40]
3.3

46.5 [13.63]
33.9 [9.94]
3.2

45.6 [13.36]
32.3 [9.47]
3.2

44.6 [13.07]
37.6 [11.02]
3.3

43.8 [12.84]
35.9 [10.52]
3.2

43.0 [12.60]
34.3 [10.05]
3.2

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

48.7 [14.27]
29.8 [8.73]
3.4

47.9 [14.04]
28.4 [8.32]
3.4

47.0 [13.77]
27.1 [7.94]
3.4

45.8 [13.42]
34.7 [10.17]
3.4

44.9 [13.16]
33.2 [9.73]
3.4

44.1 [12.92]
31.6 [9.26]
3.4

43.0 [12.60]
36.8 [10.79]
3.4

42.2 [12.37]
35.2 [10.32]
3.4

41.5 [12.16]
33.6 [9.85]
3.4

47.2 [13.83]
29.0 [8.50]
3.6

46.4 [13.60]
27.7 [8.12]
3.6

45.5 [13.33]
26.4 [7.74]
3.6

44.2 [12.95]
34.0 [9.96]
3.6

43.4 [12.72]
32.4 [9.50]
3.6

42.7 [12.51]
30.9 [9.06]
3.6

41.5 [12.16]
36.1 [10.58]
3.6

40.7 [11.93]
34.5 [10.11]
3.6

40.0 [11.72]
32.9 [9.64]
3.5

45.6 [13.36]
28.2 [8.26]
3.8

44.8 [13.13]
26.9 [7.88]
3.8

44.0 [12.90]
25.7 [7.53]
3.7

42.6 [12.48]
33.2 [9.73]
3.8

41.9 [12.28]
31.7 [9.29]
3.7

41.1 [12.05]
30.2 [8.85]
3.7

39.9 [11.69]
35.3 [10.35]
3.8

39.2 [11.49]
33.7 [9.88]
3.7

38.5 [11.28]
32.1 [9.41]
3.7

Total BTUH [kW] 43.8 [12.84]
105
Sens BTUH [kW] 27.4 [8.03]
[40.6]
4.0
Power

43.0 [12.60]
26.1 [7.65]
3.9

42.3 [12.40]
24.9 [7.30]
3.9

40.8 [11.96]
32.3 [9.47]
3.9

40.1 [11.75]
30.9 [9.06]
3.9

39.4 [11.55]
29.4 [8.62]
3.9

38.1 [11.17]
34.4 [10.08]
3.9

37.4 [10.96]
32.9 [9.64]
3.9

36.7 [10.76]
31.4 [9.20]
3.9

41.0 [12.02]
25.2 [7.39]
4.1
38.6 [11.31]
24.2 [7.09]
4.3

40.2 [11.78]
24.1 [7.06]
4.1
37.9 [11.11]
23.1 [6.77]
4.2

38.8 [11.37]
31.4 [9.20]
4.1
36.3 [10.64]
30.3 [8.88]
4.3

38.1 [11.17]
30.0 [8.79]
4.1
35.6 [10.43]
29.0 [8.50]
4.2

37.4 [10.96]
28.6 [8.38]
4.0
35.0 [10.26]
27.6 [8.09]
4.2

36.0 [10.55]
33.5 [9.82]
4.1
33.5 [9.82]
32.4 [9.50]
4.3

35.4 [10.37]
32.0 [9.38]
4.1
32.9 [9.64]
31.0 [9.09]
4.2

34.7 [10.17]
30.5 [8.94]
4.0
32.3 [9.47]
29.5 [8.65]
4.2

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1540 [727]
.17

41.7 [12.22]
26.4 [7.74]
4.1
39.3 [11.52]
25.4 [7.44]
4.3

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNL-042
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

16

1540 [727]

60°F [15.5°C]
1400 [661]

1260 [595]

1540 [727]

70°F [21.1°C]
1400 [661]

1260 [595]

1540 [727]

80°F [26.7°C]
1400 [661]

1260 [595]

13.9 [4.07]
2.6
16.9 [4.95]
2.6
20.0 [5.86]
2.6
23.0 [6.74]
2.7
26.0 [7.62]
2.7
29.0 [8.50]
2.8
32.0 [9.38]
2.8
35.1 [10.29]
2.8
38.1 [11.17]
2.9
41.1 [12.05]
2.9
44.1 [12.92]
2.9

13.8 [4.04]
2.6
16.8 [4.92]
2.6
19.8 [5.80]
2.7
22.8 [6.68]
2.7
25.8 [7.56]
2.7
28.8 [8.44]
2.8
31.8 [9.32]
2.8
34.8 [10.20]
2.9
37.8 [11.08]
2.9
40.8 [11.96]
2.9
43.8 [12.84]
3.0

13.7 [4.02]
2.6
16.7 [4.89]
2.7
19.7 [5.77]
2.7
22.6 [6.62]
2.7
25.6 [7.50]
2.8
28.6 [8.38]
2.8
31.6 [9.26]
2.9
34.6 [10.14]
2.9
37.5 [10.99]
2.9
40.5 [11.87]
3.0
43.5 [12.75]
3.0

12.9 [3.78]
3.0
16.0 [4.69]
3.0
19.0 [5.57]
3.1
22.0 [6.45]
3.1
25.0 [7.33]
3.1
28.0 [8.21]
3.2
31.1 [9.11]
3.2
34.1 [9.99]
3.2
37.1 [10.87]
3.3
40.1 [11.75]
3.3
43.1 [12.63]
3.4

12.8 [3.75]
3.0
15.8 [4.63]
3.1
18.8 [5.51]
3.1
21.8 [6.39]
3.1
24.8 [7.27]
3.2
27.8 [8.15]
3.2
30.8 [9.03]
3.2
33.8 [9.91]
3.3
36.8 [10.79]
3.3
39.8 [11.66]
3.4
42.8 [12.54]
3.4

12.8 [3.75]
3.1
15.7 [4.60]
3.1
18.7 [5.48]
3.1
21.7 [6.36]
3.2
24.7 [7.24]
3.2
27.6 [8.09]
3.3
30.6 [8.97]
3.3
33.6 [9.85]
3.3
36.6 [10.73]
3.4
39.6 [11.61]
3.4
42.5 [12.46]
3.4

11.2 [3.28]
3.3
14.2 [4.16]
3.4
17.3 [5.07]
3.4
20.3 [5.95]
3.5
23.3 [6.83]
3.5
26.3 [7.71]
3.5
29.3 [8.59]
3.6
32.4 [9.50]
3.6
35.4 [10.37]
3.6
38.4 [11.25]
3.7
41.4 [12.13]
3.7

11.1 [3.25]
3.4
14.1 [4.13]
3.4
17.1 [5.01]
3.5
20.1 [5.89]
3.5
23.1 [6.77]
3.5
26.1 [7.65]
3.6
29.1 [8.53]
3.6
32.1 [9.41]
3.6
35.1 [10.29]
3.7
38.1 [11.17]
3.7
41.1 [12.05]
3.8

11.1 [3.25]
3.4
14.0 [4.10]
3.5
17.0 [4.98]
3.5
20.0 [5.86]
3.5
23.0 [6.74]
3.6
25.9 [7.59]
3.6
28.9 [8.47]
3.7
31.9 [9.35]
3.7
34.9 [10.23]
3.7
37.9 [11.11]
3.8
40.8 [11.96]
3.8

[ ] Designates Metric Conversions

Air

Gross Systems Performance Data
RQNL Series

COOLING PERFORMANCE DATA—RQNL-048
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1600 [755]
.13

1440 [680]
.11

1760 [831]
.15

67°F [19.4°C]
1600 [755]
.13

1440 [680]
.11

1760 [831]
.15

63°F [17.2°C]
1600 [755]
.13

1440 [680]
.11

Total BTUH [kW] 60.4 [17.70]
75
Sens BTUH [kW] 37.4 [10.96]
[23.9]
3.2
Power

59.3 [17.38]
35.7 [10.46]
3.2

58.3 [17.09]
34.1 [9.99]
3.2

57.1 [16.73]
42.7 [12.51]
3.2

56.1 [16.44]
40.8 [11.96]
3.2

55.0 [16.12]
38.9 [11.40]
3.1

54.5 [15.97]
45.0 [13.19]
3.2

53.5 [15.68]
43.0 [12.60]
3.1

52.5 [15.39]
41.0 [12.02]
3.1

Total BTUH [kW] 58.8 [17.23]
80
Sens BTUH [kW] 36.6 [10.73]
[26.7]
3.4
Power

57.8 [16.94]
35.0 [10.26]
3.4

56.7 [16.62]
33.3 [9.76]
3.3

55.5 [16.27]
41.9 [12.28]
3.4

54.5 [15.97]
40.0 [11.72]
3.4

53.5 [15.68]
38.2 [11.20]
3.3

52.9 [15.50]
44.2 [12.95]
3.4

51.9 [15.21]
42.2 [12.37]
3.3

51.0 [14.95]
40.3 [11.81]
3.3

Total BTUH [kW] 57.0 [16.71]
85
Sens BTUH [kW] 35.7 [10.46]
[29.4]
3.6
Power

56.0 [16.41]
34.1 [9.99]
3.6

55.0 [16.12]
32.5 [9.52]
3.5

53.7 [15.74]
41.0 [12.02]
3.6

52.7 [15.44]
39.2 [11.49]
3.5

51.8 [15.18]
37.3 [10.93]
3.5

51.1 [14.98]
43.3 [12.69]
3.5

50.2 [14.71]
41.4 [12.13]
3.5

49.3 [14.45]
39.4 [11.55]
3.5

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

55.1 [16.15]
34.8 [10.20]
3.8

54.1 [15.86]
33.2 [9.73]
3.7

53.1 [15.56]
31.7 [9.29]
3.7

51.7 [15.15]
40.1 [11.75]
3.8

50.8 [14.89]
38.3 [11.22]
3.7

49.9 [14.62]
36.5 [10.70]
3.7

49.1 [14.39]
42.4 [12.43]
3.7

48.3 [14.16]
40.5 [11.87]
3.7

47.4 [13.89]
38.6 [11.31]
3.7

53.1 [15.56]
33.8 [9.91]
4.0

52.1 [15.27]
32.3 [9.47]
3.9

51.2 [15.01]
30.8 [9.03]
3.9

49.8 [14.59]
39.1 [11.46]
3.9

48.9 [14.33]
37.4 [10.96]
3.9

48.0 [14.07]
35.6 [10.43]
3.9

47.2 [13.83]
41.4 [12.13]
3.9

46.3 [13.57]
39.6 [11.61]
3.9

45.5 [13.33]
37.7 [11.05]
3.9

51.1 [14.98]
32.9 [9.64]
4.2

50.2 [14.71]
31.4 [9.20]
4.1

49.3 [14.45]
29.9 [8.76]
4.1

47.8 [14.01]
38.2 [11.20]
4.1

46.9 [13.75]
36.5 [10.70]
4.1

46.1 [13.51]
34.8 [10.20]
4.1

45.2 [13.25]
40.5 [11.87]
4.1

44.4 [13.01]
38.7 [11.34]
4.1

43.6 [12.78]
36.9 [10.81]
4.0

Total BTUH [kW] 49.3 [14.45]
105
Sens BTUH [kW] 32.0 [9.38]
[40.6]
4.3
Power

48.4 [14.18]
30.6 [8.97]
4.3

47.5 [13.92]
29.2 [8.56]
4.3

46.0 [13.48]
37.3 [10.93]
4.3

45.1 [13.22]
35.7 [10.46]
4.3

44.3 [12.98]
34.0 [9.96]
4.2

43.4 [12.72]
39.6 [11.61]
4.3

42.6 [12.48]
37.9 [11.11]
4.3

41.8 [12.25]
36.1 [10.58]
4.2

46.8 [13.72]
29.9 [8.76]
4.5
45.5 [13.33]
29.3 [8.59]
4.7

45.9 [13.45]
28.5 [8.35]
4.5
44.6 [13.07]
27.9 [8.18]
4.6

44.3 [12.98]
36.6 [10.73]
4.5
43.0 [12.60]
36.0 [10.55]
4.7

43.5 [12.75]
34.9 [10.23]
4.5
42.2 [12.37]
34.4 [10.08]
4.7

42.7 [12.51]
33.3 [9.76]
4.4
41.4 [12.13]
32.8 [9.61]
4.6

41.7 [12.22]
38.9 [11.40]
4.5
40.4 [11.84]
38.3 [11.22]
4.7

41.0 [12.02]
37.1 [10.87]
4.4
39.6 [11.61]
36.6 [10.73]
4.6

40.2 [11.78]
35.4 [10.37]
4.4
38.9 [11.40]
34.8 [10.20]
4.6

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1760 [831]
.15

47.6 [13.95]
31.3 [9.17]
4.5
46.3 [13.57]
30.7 [9.00]
4.7

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQNL-048
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

1760 [831]

60°F [15.5°C]
1600 [755]

1440 [680]

1760 [831]

70°F [21.1°C]
1600 [755]

1440 [680]

1760 [831]

80°F [26.7°C]
1600 [755]

1440 [680]

16.9 [4.95]
2.6
20.1 [5.89]
2.6
23.2 [6.80]
2.7
26.4 [7.74]
2.7
29.5 [8.65]
2.8
32.7 [9.58]
2.8
35.9 [10.52]
2.9
39.0 [11.43]
2.9
42.2 [12.37]
3.0
45.3 [13.28]
3.0
48.5 [14.21]
3.1

16.8 [4.92]
2.6
19.9 [5.83]
2.6
23.1 [6.77]
2.7
26.2 [7.68]
2.8
29.3 [8.59]
2.8
32.5 [9.52]
2.9
35.6 [10.43]
2.9
38.7 [11.34]
3.0
41.9 [12.28]
3.0
45.0 [13.19]
3.1
48.1 [14.10]
3.1

16.7 [4.89]
2.6
19.8 [5.80]
2.7
22.9 [6.71]
2.7
26.0 [7.62]
2.8
29.1 [8.53]
2.8
32.2 [9.44]
2.9
35.4 [10.37]
2.9
38.5 [11.28]
3.0
41.6 [12.19]
3.1
44.7 [13.10]
3.1
47.8 [14.01]
3.2

15.4 [4.51]
3.0
18.6 [5.45]
3.0
21.8 [6.39]
3.1
24.9 [7.30]
3.1
28.1 [8.24]
3.2
31.2 [9.14]
3.2
34.4 [10.08]
3.3
37.5 [10.99]
3.3
40.7 [11.93]
3.4
43.9 [12.87]
3.4
47.0 [13.77]
3.5

15.3 [4.48]
3.0
18.5 [5.42]
3.0
21.6 [6.33]
3.1
24.7 [7.24]
3.2
27.9 [8.18]
3.2
31.0 [9.09]
3.3
34.1 [9.99]
3.3
37.3 [10.93]
3.4
40.4 [11.84]
3.4
43.6 [12.78]
3.5
46.7 [13.69]
3.5

15.2 [4.45]
3.0
18.3 [5.36]
3.1
21.5 [6.30]
3.1
24.6 [7.21]
3.2
27.7 [8.12]
3.2
30.8 [9.03]
3.3
33.9 [9.94]
3.4
37.0 [10.84]
3.4
40.1 [11.75]
3.5
43.2 [12.66]
3.5
46.4 [13.60]
3.6

14.4 [4.22]
3.4
17.6 [5.16]
3.5
20.7 [6.07]
3.5
23.9 [7.00]
3.6
27.1 [7.94]
3.6
30.2 [8.85]
3.7
33.4 [9.79]
3.7
36.5 [10.70]
3.8
39.7 [11.63]
3.8
42.8 [12.54]
3.9
46.0 [13.48]
3.9

14.3 [4.19]
3.5
17.5 [5.13]
3.5
20.6 [6.04]
3.6
23.7 [6.95]
3.6
26.9 [7.88]
3.7
30.0 [8.79]
3.7
33.1 [9.70]
3.8
36.3 [10.64]
3.8
39.4 [11.55]
3.9
42.5 [12.46]
3.9
45.7 [13.39]
4.0

14.2 [4.16]
3.5
17.3 [5.07]
3.5
20.4 [5.98]
3.6
23.6 [6.92]
3.7
26.7 [7.83]
3.7
29.8 [8.73]
3.8
32.9 [9.64]
3.8
36.0 [10.55]
3.9
39.1 [11.46]
3.9
42.2 [12.37]
4.0
45.3 [13.28]
4.0

[ ] Designates Metric Conversions

17

Air

Gross Systems Performance Data
RQPL Series

COOLING PERFORMANCE DATA—RQPL-024
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

940 [444]
.15

71°F [21.7°C]
850 [401]
.13

760 [359]
.11

940 [444]
.15

67°F [19.4°C]
850 [401]
.13

760 [359]
.11

940 [444]
.15

63°F [17.2°C]
850 [401]
.13

760 [359]
.11

Total BTUH [kW]
75
Sens BTUH [kW]
[23.9]
Power

29.9 [8.76]
19.2 [5.63]
1.5

29.4 [8.62]
18.4 [5.39]
1.5

28.8 [8.44]
17.5 [5.13]
1.5

28.6 [8.38]
22.0 [6.45]
1.5

28.0 [8.21]
21.0 [6.15]
1.5

27.5 [8.06]
20.1 [5.89]
1.5

27.6 [8.09]
23.3 [6.83]
1.5

27.1 [7.94]
22.3 [6.54]
1.5

26.6 [7.80]
21.2 [6.21]
1.5

Total BTUH [kW]
80
Sens BTUH [kW]
[26.7]
Power

29.7 [8.70]
19.0 [5.57]
1.6

29.1 [8.53]
18.1 [5.30]
1.6

28.6 [8.38]
17.3 [5.07]
1.6

28.3 [8.29]
21.8 [6.39]
1.6

27.8 [8.15]
20.8 [6.10]
1.6

27.3 [8.00]
19.9 [5.83]
1.6

27.3 [8.00]
23.1 [6.77]
1.6

26.8 [7.85]
22.1 [6.48]
1.6

26.4 [7.74]
21.0 [6.15]
1.6

Total BTUH [kW]
85
Sens BTUH [kW]
[29.4]
Power

29.0 [8.50]
18.6 [5.45]
1.7

28.5 [8.35]
17.8 [5.22]
1.7

27.9 [8.18]
16.9 [4.95]
1.7

27.6 [8.09]
21.4 [6.27]
1.7

27.2 [7.97]
20.5 [6.01]
1.7

26.7 [7.83]
19.5 [5.71]
1.7

26.7 [7.83]
22.7 [6.65]
1.7

26.2 [7.68]
21.7 [6.36]
1.7

25.7 [7.53]
20.7 [6.07]
1.7

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

28.0 [8.21]
18.1 [5.30]
1.8

27.5 [8.06]
17.3 [5.07]
1.8

27.0 [7.91]
16.5 [4.84]
1.8

26.6 [7.80]
20.9 [6.13]
1.8

26.2 [7.68]
20.0 [5.86]
1.8

25.7 [7.53]
19.1 [5.60]
1.8

25.6 [7.50]
22.2 [6.51]
1.8

25.2 [7.39]
21.2 [6.21]
1.8

24.7 [7.24]
20.2 [5.92]
1.8

26.7 [7.83]
17.5 [5.13]
1.9

26.3 [7.71]
16.7 [4.89]
1.9

25.8 [7.56]
16.0 [4.69]
1.9

25.4 [7.44]
20.4 [5.98]
1.9

24.9 [7.30]
19.4 [5.69]
1.9

24.5 [7.18]
18.5 [5.42]
1.9

24.4 [7.15]
21.6 [6.33]
1.9

24.0 [7.03]
20.7 [6.07]
1.9

23.5 [6.89]
19.7 [5.77]
1.9

25.4 [7.44]
16.9 [4.95]
2.0

24.9 [7.30]
16.1 [4.72]
2.0

24.5 [7.18]
15.4 [4.51]
2.0

24.0 [7.03]
19.7 [5.77]
2.0

23.6 [6.92]
18.8 [5.51]
2.0

23.2 [6.80]
18.0 [5.28]
2.0

23.0 [6.74]
21.0 [6.15]
2.0

22.6 [6.62]
20.1 [5.89]
2.0

22.2 [6.51]
19.1 [5.60]
2.0

Total BTUH [kW]
105
Sens BTUH [kW]
[40.6]
Power

24.0 [7.03]
16.3 [4.78]
2.1

23.6 [6.92]
15.5 [4.54]
2.1

23.1 [6.77]
14.8 [4.34]
2.1

22.6 [6.62]
19.1 [5.60]
2.1

22.2 [6.51]
18.2 [5.33]
2.1

21.8 [6.39]
17.4 [5.10]
2.1

21.7 [6.36]
20.4 [5.98]
2.1

21.3 [6.24]
19.5 [5.71]
2.1

20.9 [6.13]
18.5 [5.42]
2.1

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power

22.7 [6.65]
15.6 [4.57]
2.2
21.6 [6.33]
15.1 [4.43]
2.3

22.3 [6.54]
14.9 [4.37]
2.2
21.2 [6.21]
14.4 [4.22]
2.3

21.9 [6.42]
14.2 [4.16]
2.2
20.8 [6.10]
13.7 [4.02]
2.3

21.4 [6.27]
18.5 [5.42]
2.2
20.2 [5.92]
17.9 [5.25]
2.3

21.0 [6.15]
17.6 [5.16]
2.2
19.9 [5.83]
17.1 [5.01]
2.3

20.6 [6.04]
16.8 [4.92]
2.2
19.5 [5.71]
16.3 [4.78]
2.3

20.4 [5.98]
19.7 [5.77]
2.2
19.3 [5.66]
19.2 [5.63]
2.3

20.0 [5.86]
18.9 [5.54]
2.2
18.9 [5.54]
18.3 [5.36]
2.3

19.6 [5.74]
18.0 [5.28]
2.2
18.6 [5.45]
17.5 [5.13]
2.3

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-024
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

18

940 [444]

60°F [15.5°C]
850 [401]

760 [359]

940 [444]

70°F [21.1°C]
850 [401]

760 [359]

940 [444]

80°F [26.7°C]
850 [401]

760 [359]

8.9 [2.61]
1.4
10.5 [3.08]
1.4
12.1 [3.55]
1.4
13.8 [4.04]
1.5
15.4 [4.51]
1.5
17.1 [5.01]
1.5
18.7 [5.48]
1.5
20.3 [5.95]
1.5
22.0 [6.45]
1.6
23.6 [6.92]
1.6
25.2 [7.39]
1.6

8.8 [2.58]
1.4
10.4 [3.05]
1.4
12.1 [3.55]
1.5
13.7 [4.02]
1.5
15.3 [4.48]
1.5
16.9 [4.95]
1.5
18.6 [5.45]
1.5
20.2 [5.92]
1.6
21.8 [6.39]
1.6
23.4 [6.86]
1.6
25.1 [7.36]
1.6

8.7 [2.55]
1.4
10.4 [3.05]
1.5
12.0 [3.52]
1.5
13.6 [3.99]
1.5
15.2 [4.45]
1.5
16.8 [4.92]
1.5
18.4 [5.39]
1.6
20.0 [5.86]
1.6
21.7 [6.36]
1.6
23.3 [6.83]
1.6
24.9 [7.30]
1.6

8.0 [2.34]
1.6
9.6 [2.81]
1.6
11.3 [3.31]
1.6
12.9 [3.78]
1.6
14.5 [4.25]
1.7
16.2 [4.75]
1.7
17.8 [5.22]
1.7
19.4 [5.69]
1.7
21.1 [6.18]
1.7
22.7 [6.65]
1.8
24.4 [7.15]
1.8

7.9 [2.32]
1.6
9.6 [2.81]
1.6
11.2 [3.28]
1.6
12.8 [3.75]
1.7
14.4 [4.22]
1.7
16.1 [4.72]
1.7
17.7 [5.19]
1.7
19.3 [5.66]
1.7
20.9 [6.13]
1.8
22.6 [6.62]
1.8
24.2 [7.09]
1.8

7.9 [2.32]
1.6
9.5 [2.78]
1.6
11.1 [3.25]
1.7
12.7 [3.72]
1.7
14.3 [4.19]
1.7
15.9 [4.66]
1.7
17.6 [5.16]
1.7
19.2 [5.63]
1.8
20.8 [6.10]
1.8
22.4 [6.56]
1.8
24.0 [7.03]
1.8

6.5 [1.90]
1.8
8.2 [2.40]
1.8
9.8 [2.87]
1.9
11.5 [3.37]
1.9
13.1 [3.84]
1.9
14.7 [4.31]
1.9
16.4 [4.81]
1.9
18.0 [5.28]
2.0
19.6 [5.74]
2.0
21.3 [6.24]
2.0
22.9 [6.71]
2.0

6.5 [1.90]
1.8
8.1 [2.37]
1.9
9.8 [2.87]
1.9
11.4 [3.34]
1.9
13.0 [3.81]
1.9
14.6 [4.28]
1.9
16.3 [4.78]
2.0
17.9 [5.25]
2.0
19.5 [5.71]
2.0
21.1 [6.18]
2.0
22.8 [6.68]
2.0

6.5 [1.90]
1.9
8.1 [2.37]
1.9
9.7 [2.84]
1.9
11.3 [3.31]
1.9
12.9 [3.78]
1.9
14.5 [4.25]
2.0
16.1 [4.72]
2.0
17.8 [5.22]
2.0
19.4 [5.69]
2.0
21.0 [6.15]
2.1
22.6 [6.62]
2.1

[ ] Designates Metric Conversions

Air

Gross Systems Performance Data
RQPL Series

COOLING PERFORMANCE DATA—RQPL-025
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

930 [439]
.15

71°F [21.7°C]
850 [401]
.17

760 [359]
.19

930 [439]
.15

67°F [19.4°C]
850 [401]
.17

760 [359]
.19

930 [439]
.15

63°F [17.2°C]
850 [401]
.17

760 [359]
.19

Total BTUH [kW]
75
Sens BTUH [kW]
[23.9]
Power

30.4 [8.9]
18.8 [5.5]
1.5

29.9 [8.8]
17.5 [5.1]
1.4

29.3 [8.6]
16.1 [4.7]
1.4

28.5 [8.4]
22.1 [6.5]
1.5

28.0 [8.2]
20.7 [6.1]
1.5

27.5 [8.1]
19.2 [5.6]
1.4

26.8 [7.9]
24.4 [7.2]
1.5

26.4 [7.7]
23.0 [6.8]
1.5

25.9 [7.6]
21.4 [6.3]
1.4

Total BTUH [kW]
80
Sens BTUH [kW]
[26.7]
Power

29.6 [8.7]
18.2 [5.3]
1.5

29.1 [8.5]
16.9 [5.0]
1.5

28.5 [8.4]
15.5 [4.6]
1.5

27.7 [8.1]
21.5 [6.3]
1.5

27.2 [8.0]
20.1 [5.9]
1.5

26.7 [7.8]
18.6 [5.5]
1.5

26.0 [7.6]
23.8 [7.0]
1.6

25.6 [7.5]
22.4 [6.6]
1.5

25.1 [7.4]
20.8 [6.1]
1.5

Total BTUH [kW]
85
Sens BTUH [kW]
[29.4]
Power

28.7 [8.4]
17.5 [5.1]
1.6

28.2 [8.3]
16.3 [4.8]
1.6

27.6 [8.1]
14.9 [4.4]
1.6

26.8 [7.9]
20.9 [6.1]
1.6

26.3 [7.7]
19.5 [5.7]
1.6

25.8 [7.6]
18.1 [5.3]
1.6

25.1 [7.4]
23.2 [6.8]
1.6

24.7 [7.2]
21.8 [6.4]
1.6

24.2 [7.1]
20.2 [5.9]
1.6

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

27.7 [8.1]
16.9 [5.0]
1.7

27.2 [8.0]
15.7 [4.6]
1.7

26.7 [7.8]
14.4 [4.2]
1.7

25.8 [7.6]
20.3 [6.0]
1.7

25.4 [7.4]
19.0 [5.6]
1.7

24.9 [7.3]
17.6 [5.2]
1.7

24.1 [7.1]
22.4 [6.6]
1.7

23.7 [6.9]
21.1 [6.2]
1.7

23.3 [6.8]
19.7 [5.8]
1.7

26.7 [7.8]
16.3 [4.8]
1.8

26.2 [7.7]
15.1 [4.4]
1.8

25.7 [7.5]
13.9 [4.1]
1.8

24.8 [7.3]
19.6 [5.8]
1.8

24.4 [7.2]
18.4 [5.4]
1.8

23.9 [7.0]
17.0 [5.0]
1.8

23.1 [6.8]
21.9 [6.4]
1.8

22.7 [6.7]
20.6 [6.0]
1.8

22.3 [6.5]
19.2 [5.6]
1.8

25.6 [7.5]
15.8 [4.6]
1.9

25.2 [7.4]
14.7 [4.3]
1.9

24.7 [7.2]
13.5 [4.0]
1.9

23.7 [6.9]
19.0 [5.6]
1.9

23.3 [6.8]
17.8 [5.2]
1.9

22.9 [6.7]
16.5 [4.8]
1.9

22.0 [6.4]
21.3 [6.3]
1.9

21.7 [6.4]
20.1 [5.9]
1.9

21.3 [6.2]
18.7 [5.5]
1.9

Total BTUH [kW]
105
Sens BTUH [kW]
[40.6]
Power

24.5 [7.2]
15.2 [4.5]
2.0

24.1 [7.1]
14.2 [4.2]
2.0

23.6 [6.9]
13.0 [3.8]
2.0

22.6 [6.6]
18.5 [5.4]
2.0

22.2 [6.5]
17.3 [5.1]
2.0

21.8 [6.4]
16.1 [4.7]
2.0

20.9 [6.1]
20.8 [6.1]
2.0

20.6 [6.0]
19.6 [5.8]
2.0

20.2 [5.9]
18.3 [5.4]
2.0

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power

23.3 [6.8]
14.7 [4.3]
2.2
22.1 [6.5]
14.2 [4.2]
2.3

22.9 [6.7]
13.7 [4.0]
2.1
21.7 [6.4]
13.2 [3.9]
2.3

22.5 [6.6]
12.6 [3.7]
2.1
21.3 [6.2]
12.2 [3.6]
2.2

21.4 [6.3]
18.0 [5.3]
2.2
20.2 [5.9]
17.5 [5.1]
2.3

21.0 [6.2]
16.8 [4.9]
2.1
19.8 [5.8]
16.4 [4.8]
2.3

20.6 [6.0]
15.6 [4.6]
2.1
19.4 [5.7]
15.2 [4.5]
2.2

19.7 [5.8]
19.7 [5.8]
2.2
18.5 [5.4]
18.5 [5.4]
2.3

19.4 [5.7]
19.1 [5.6]
2.1
18.2 [5.3]
18.2 [5.3]
2.3

19.0 [5.6]
17.8 [5.2]
2.1
17.8 [5.2]
17.4 [5.1]
2.2

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-025
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F]
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

930 [439]

60°F [15.5°C]
850 [401]

760 [359]

930 [439]

70°F [21.1°C]
850 [401]

760 [359]

930 [439]

80°F [26.7°C]
850 [401]

760 [359]

7.3 [2.1]
1.2
9.1 [2.7]
1.3
11.0 [3.2]
1.3
12.8 [3.8]
1.3
14.6 [4.3]
1.4
16.5 [4.8]
1.4
18.3 [5.4]
1.4
20.1 [5.9]
1.4
22.0 [6.4]
1.5
23.8 [7.0]
1.5
25.7 [7.5]
1.5

7.2 [2.1]
1.3
9.1 [2.7]
1.3
10.9 [3.2]
1.3
12.7 [3.7]
1.3
14.5 [4.2]
1.4
16.4 [4.8]
1.4
18.2 [5.3]
1.4
20.0 [5.9]
1.5
21.8 [6.4]
1.5
23.7 [6.9]
1.5
25.5 [7.5]
1.6

7.2 [2.1]
1.3
9.0 [2.6]
1.3
10.8 [3.2]
1.3
12.6 [3.7]
1.4
14.4 [4.2]
1.4
16.2 [4.7]
1.4
18.0 [5.3]
1.4
19.9 [5.8]
1.5
21.7 [6.4]
1.5
23.5 [6.9]
1.5
25.3 [7.4]
1.6

5.9 [1.7]
1.4
7.8 [2.3]
1.4
9.6 [2.8]
1.5
11.4 [3.3]
1.5
13.3 [3.9]
1.5
15.1 [4.4]
1.6
17.0 [5.0]
1.6
18.8 [5.5]
1.6
20.6 [6.0]
1.6
22.5 [6.6]
1.7
24.3 [7.1]
1.7

5.9 [1.7]
1.4
7.7 [2.3]
1.5
9.5 [2.8]
1.5
11.4 [3.3]
1.5
13.2 [3.9]
1.6
15.0 [4.4]
1.6
16.8 [4.9]
1.6
18.7 [5.5]
1.6
20.5 [6.0]
1.7
22.3 [6.5]
1.7
24.1 [7.1]
1.7

5.9 [1.7]
1.4
7.7 [2.3]
1.5
9.5 [2.8]
1.5
11.3 [3.3]
1.5
13.1 [3.8]
1.6
14.9 [4.4]
1.6
16.7 [4.9]
1.6
18.5 [5.4]
1.7
20.3 [5.9]
1.7
22.1 [6.5]
1.7
23.9 [7.0]
1.8

4.6 [1.3]
1.6
6.4 [1.9]
1.6
8.2 [2.4]
1.7
10.1 [3.0]
1.7
11.9 [3.5]
1.7
13.8 [4.0]
1.7
15.6 [4.6]
1.8
17.4 [5.1]
1.8
19.3 [5.7]
1.8
21.1 [6.2]
1.9
22.9 [6.7]
1.9

4.5 [1.3]
1.6
6.4 [1.9]
1.6
8.2 [2.4]
1.7
10.0 [2.9]
1.7
11.8 [3.5]
1.7
13.7 [4.0]
1.8
15.5 [4.5]
1.8
17.3 [5.1]
1.8
19.1 [5.6]
1.9
21.0 [6.2]
1.9
22.8 [6.7]
1.9

4.5 [1.3]
1.6
6.3 [1.8]
1.7
8.1 [2.4]
1.7
9.9 [2.9]
1.7
11.8 [3.5]
1.8
13.6 [4.0]
1.8
15.4 [4.5]
1.8
17.2 [5.0]
1.8
19.0 [5.6]
1.9
20.8 [6.1]
1.9
22.6 [6.6]
1.9

[ ] Designates Metric Conversions

19

Air

Gross Systems Performance Data
RQPL Series

COOLING PERFORMANCE DATA—RQPL-030
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1050 [496]
.13

940 [444]
.11

1160 [547]
.15

67°F [19.4°C]
1050 [496]
.13

940 [444]
.11

1160 [547]
.15

63°F [17.2°C]
1050 [496]
.13

940 [444]
.11

Total BTUH [kW] 36.9 [10.81]
75
Sens BTUH [kW] 23.7 [6.95]
[23.9]
1.9
Power

36.2 [10.61]
22.6 [6.62]
1.9

35.5 [10.40]
21.5 [6.30]
1.9

34.9 [10.23]
26.9 [7.88]
1.9

34.2 [10.02]
25.7 [7.53]
1.9

33.6 [9.85]
24.5 [7.18]
1.9

33.5 [9.82]
28.4 [8.32]
1.9

32.9 [9.64]
27.1 [7.94]
1.9

32.3 [9.47]
25.8 [7.56]
1.9

Total BTUH [kW] 35.7 [10.46]
80
Sens BTUH [kW] 23.1 [6.77]
[26.7]
2.0
Power

35.1 [10.29]
22.0 [6.45]
2.0

34.4 [10.08]
21.0 [6.15]
2.0

33.7 [9.88]
26.3 [7.71]
2.0

33.1 [9.70]
25.2 [7.39]
2.0

32.5 [9.52]
24.0 [7.03]
2.0

32.3 [9.47]
27.8 [8.15]
2.0

31.8 [9.32]
26.5 [7.77]
2.0

31.2 [9.14]
25.3 [7.41]
2.0

Total BTUH [kW] 34.6 [10.14]
85
Sens BTUH [kW] 22.5 [6.59]
[29.4]
2.1
Power

33.9 [9.94]
21.5 [6.30]
2.1

33.3 [9.76]
20.5 [6.01]
2.1

32.6 [9.55]
25.8 [7.56]
2.1

32.0 [9.38]
24.6 [7.21]
2.1

31.4 [9.20]
23.5 [6.89]
2.1

31.2 [9.14]
27.2 [7.97]
2.1

30.6 [8.97]
26.0 [7.62]
2.1

30.1 [8.82]
24.8 [7.27]
2.1

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

33.4 [9.79]
21.9 [6.42]
2.2

32.8 [9.61]
20.9 [6.13]
2.2

32.2 [9.44]
20.0 [5.86]
2.2

31.4 [9.20]
25.2 [7.39]
2.2

30.9 [9.06]
24.1 [7.06]
2.2

30.3 [8.88]
23.0 [6.74]
2.2

30.1 [8.82]
26.6 [7.80]
2.2

29.5 [8.65]
25.4 [7.44]
2.2

29.0 [8.50]
24.3 [7.12]
2.2

32.3 [9.47]
21.4 [6.27]
2.3

31.7 [9.29]
20.4 [5.98]
2.3

31.1 [9.11]
19.5 [5.71]
2.3

30.3 [8.88]
24.7 [7.24]
2.3

29.8 [8.73]
23.6 [6.92]
2.3

29.2 [8.56]
22.5 [6.59]
2.2

28.9 [8.47]
26.1 [7.65]
2.3

28.4 [8.32]
24.9 [7.30]
2.3

27.9 [8.18]
23.8 [6.98]
2.3

31.1 [9.11]
20.8 [6.10]
2.4

30.6 [8.97]
19.9 [5.83]
2.4

30.0 [8.79]
19.0 [5.57]
2.4

29.1 [8.53]
24.1 [7.06]
2.4

28.6 [8.38]
23.0 [6.74]
2.4

28.1 [8.24]
22.0 [6.45]
2.3

27.8 [8.15]
25.5 [7.47]
2.4

27.3 [8.00]
24.4 [7.15]
2.4

26.8 [7.85]
23.3 [6.83]
2.4

Total BTUH [kW] 30.0 [8.79]
105
Sens BTUH [kW] 20.3 [5.95]
[40.6]
2.5
Power

29.4 [8.62]
19.4 [5.69]
2.5

28.9 [8.47]
18.5 [5.42]
2.5

28.0 [8.21]
23.6 [6.92]
2.5

27.5 [8.06]
22.5 [6.59]
2.5

27.0 [7.91]
21.5 [6.30]
2.4

26.6 [7.80]
25.0 [7.33]
2.5

26.1 [7.65]
23.9 [7.00]
2.5

25.6 [7.50]
22.8 [6.68]
2.5

28.2 [8.26]
18.8 [5.51]
2.6
26.9 [7.88]
18.3 [5.36]
2.7

27.7 [8.12]
18.0 [5.28]
2.6
26.4 [7.74]
17.5 [5.13]
2.7

26.7 [7.83]
23.0 [6.74]
2.6
25.4 [7.44]
22.5 [6.59]
2.7

26.2 [7.68]
22.0 [6.45]
2.6
25.0 [7.33]
21.5 [6.30]
2.6

25.8 [7.56]
21.0 [6.15]
2.5
24.5 [7.18]
20.5 [6.01]
2.6

25.4 [7.44]
24.4 [7.15]
2.6
24.1 [7.06]
23.9 [7.00]
2.7

24.9 [7.30]
23.4 [6.86]
2.6
23.6 [6.92]
22.8 [6.68]
2.7

24.5 [7.18]
22.3 [6.54]
2.6
23.2 [6.80]
21.8 [6.39]
2.7

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1160 [547]
.15

28.7 [8.41]
19.7 [5.77]
2.6
27.4 [8.03]
19.2 [5.63]
2.7

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-030
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

20

1160 [547]

60°F [15.5°C]
1050 [496]

940 [444]

1160 [547]

70°F [21.1°C]
1050 [496]

940 [444]

1160 [547]

80°F [26.7°C]
1050 [496]

940 [444]

9.5 [2.78]
1.6
11.5 [3.37]
1.6
13.4 [3.93]
1.6
15.3 [4.48]
1.7
17.2 [5.04]
1.7
19.2 [5.63]
1.7
21.1 [6.18]
1.8
23.0 [6.74]
1.8
24.9 [7.30]
1.8
26.9 [7.88]
1.9
28.8 [8.44]
1.9

9.5 [2.78]
1.6
11.4 [3.34]
1.6
13.3 [3.90]
1.7
15.2 [4.45]
1.7
17.1 [5.01]
1.7
19.0 [5.57]
1.8
20.9 [6.13]
1.8
22.8 [6.68]
1.8
24.8 [7.27]
1.8
26.7 [7.83]
1.9
28.6 [8.38]
1.9

9.4 [2.75]
1.6
11.3 [3.31]
1.6
13.2 [3.87]
1.7
15.1 [4.43]
1.7
17.0 [4.98]
1.7
18.9 [5.54]
1.8
20.8 [6.10]
1.8
22.7 [6.65]
1.8
24.6 [7.21]
1.9
26.5 [7.77]
1.9
28.4 [8.32]
1.9

8.0 [2.34]
1.8
19.9 [2.90]
1.8
11.8 [3.46]
1.9
13.8 [4.04]
1.9
15.7 [4.60]
1.9
17.6 [5.16]
1.9
19.5 [5.71]
2.0
21.5 [6.30]
2.0
23.4 [6.86]
2.0
25.3 [7.41]
2.1
27.2 [7.97]
2.1

7.9 [2.32]
1.8
19.8 [2.87]
1.8
11.8 [3.46]
1.9
13.7 [4.02]
1.9
15.6 [4.57]
1.9
17.5 [5.13]
2.0
19.4 [5.69]
2.0
21.3 [6.24]
2.0
23.2 [6.80]
2.1
25.1 [7.36]
2.1
27.0 [7.91]
2.1

7.9 [2.32]
1.8
19.8 [2.87]
1.9
11.7 [3.43]
1.9
13.6 [3.99]
1.9
15.5 [4.54]
2.0
17.4 [5.10]
2.0
19.3 [5.66]
2.0
21.2 [6.21]
2.1
23.0 [6.74]
2.1
24.9 [7.30]
2.1
26.8 [7.85]
2.2

6.6 [1.93]
2.0
18.5 [2.49]
2.0
10.4 [3.05]
2.1
12.3 [3.60]
2.1
14.3 [4.19]
2.1
16.2 [4.75]
2.2
18.1 [5.30]
2.2
20.0 [5.86]
2.2
22.0 [6.45]
2.3
23.9 [7.00]
2.3
25.8 [7.56]
2.3

6.5 [1.90]
2.0
18.4 [2.46]
2.1
10.3 [3.02]
2.1
12.3 [3.60]
2.1
14.2 [4.16]
2.2
16.1 [4.72]
2.2
18.0 [5.28]
2.2
19.9 [5.83]
2.3
21.8 [6.39]
2.3
23.7 [6.95]
2.3
25.6 [7.50]
2.4

6.5 [1.90]
2.1
18.4 [2.46]
2.1
10.3 [3.02]
2.1
12.2 [3.58]
2.2
14.1 [4.13]
2.2
16.0 [4.69]
2.2
17.9 [5.25]
2.3
19.7 [5.77]
2.3
21.6 [6.33]
2.3
23.5 [6.89]
2.4
25.4 [7.44]
2.4

[ ] Designates Metric Conversions

Air

Gross Systems Performance Data
RQPL Series

COOLING PERFORMANCE DATA—RQPL-036
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1250 [590]
.19

1120 [528]
.17

1380 [651]
.21

67°F [19.4°C]
1250 [590]
.19

1120 [528]
.17

1380 [651]
.21

63°F [17.2°C]
1250 [590]
.19

1120 [528]
.17

Total BTUH [kW] 45.0 [13.19]
75
Sens BTUH [kW] 27.7 [8.12]
[23.9]
2.3
Power

44.2 [12.95]
26.5 [7.77]
2.2

43.4 [12.72]
25.3 [7.41]
2.2

42.9 [12.57]
31.8 [9.32]
2.2

42.2 [12.37]
30.4 [8.91]
2.2

41.4 [12.13]
28.9 [8.47]
2.2

41.8 [12.25]
34.2 [10.02]
2.2

41.0 [12.02]
32.6 [9.55]
2.2

40.3 [11.81]
31.1 [9.11]
2.2

Total BTUH [kW] 43.9 [12.87]
80
Sens BTUH [kW] 27.1 [7.94]
[26.7]
2.4
Power

43.1 [12.63]
25.9 [7.59]
2.4

42.3 [12.40]
24.7 [7.24]
2.4

41.8 [12.25]
31.2 [9.14]
2.4

41.1 [12.05]
29.8 [8.73]
2.4

40.3 [11.81]
28.4 [8.32]
2.3

40.7 [11.93]
33.5 [9.82]
2.4

39.9 [11.69]
32.0 [9.38]
2.3

39.2 [11.49]
30.5 [8.94]
2.3

Total BTUH [kW] 42.6 [12.48]
85
Sens BTUH [kW] 26.5 [7.77]
[29.4]
2.5
Power

41.8 [12.25]
25.3 [7.41]
2.5

41.0 [12.02]
24.1 [7.06]
2.5

40.5 [11.87]
30.5 [8.94]
2.5

39.8 [11.66]
29.1 [8.53]
2.5

39.1 [11.46]
27.8 [8.15]
2.5

39.4 [11.55]
32.9 [9.64]
2.5

38.7 [11.34]
31.4 [9.20]
2.5

37.9 [11.11]
29.9 [8.76]
2.5

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

41.1 [12.05]
25.7 [7.53]
2.7

40.3 [11.81]
24.6 [7.21]
2.7

39.6 [11.61]
23.5 [6.89]
2.6

39.0 [11.43]
29.8 [8.73]
2.7

38.3 [11.22]
28.5 [8.35]
2.6

37.6 [11.02]
27.1 [7.94]
2.6

37.9 [11.11]
32.2 [9.44]
2.6

37.2 [10.90]
30.7 [9.00]
2.6

36.5 [10.70]
29.3 [8.59]
2.6

39.5 [11.58]
25.0 [7.33]
2.8

38.8 [11.37]
23.9 [7.00]
2.8

38.1 [11.17]
22.8 [6.68]
2.8

37.4 [10.96]
29.1 [8.53]
2.8

36.8 [10.79]
27.8 [8.15]
2.8

36.1 [10.58]
26.5 [7.77]
2.8

36.3 [10.64]
31.4 [9.20]
2.8

35.6 [10.43]
30.0 [8.79]
2.8

35.0 [10.26]
28.6 [8.38]
2.7

37.8 [11.08]
24.2 [7.09]
3.0

37.1 [10.87]
23.2 [6.80]
2.9

36.5 [10.70]
22.1 [6.48]
2.9

35.8 [10.49]
28.3 [8.29]
2.9

35.1 [10.29]
27.0 [7.91]
2.9

34.5 [10.11]
25.8 [7.56]
2.9

34.6 [10.14]
30.7 [9.00]
2.9

34.0 [9.96]
29.3 [8.59]
2.9

33.4 [9.79]
27.9 [8.18]
2.9

Total BTUH [kW] 36.1 [10.58]
105
Sens BTUH [kW] 23.4 [6.86]
[40.6]
3.1
Power

35.5 [10.40]
22.4 [6.56]
3.1

34.8 [10.20]
21.3 [6.24]
3.1

34.1 [9.99]
27.5 [8.06]
3.1

33.5 [9.82]
26.3 [7.71]
3.1

32.8 [9.61]
25.0 [7.33]
3.0

32.9 [9.64]
29.9 [8.76]
3.1

32.3 [9.47]
28.5 [8.35]
3.0

31.7 [9.29]
27.2 [7.97]
3.0

33.8 [9.91]
21.6 [6.33]
3.2
32.2 [9.44]
20.8 [6.10]
3.4

33.2 [9.73]
20.6 [6.04]
3.2
31.7 [9.29]
19.8 [5.80]
3.3

32.4 [9.50]
26.7 [7.83]
3.2
30.8 [9.03]
25.8 [7.56]
3.4

31.8 [9.32]
25.5 [7.47]
3.2
30.2 [8.85]
24.7 [7.24]
3.3

31.2 [9.14]
24.3 [7.12]
3.2
29.7 [8.70]
23.5 [6.89]
3.3

31.2 [9.14]
29.0 [8.50]
3.2
29.6 [8.67]
28.2 [8.26]
3.4

30.7 [9.00]
27.7 [8.12]
3.2
29.1 [8.53]
26.9 [7.88]
3.3

30.1 [8.82]
26.4 [7.74]
3.2
28.6 [8.38]
25.7 [7.53]
3.3

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1380 [651]
.21

34.4 [10.08]
22.6 [6.62]
3.3
32.8 [9.61]
21.8 [6.39]
3.4

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-036
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

1380 [651]

60°F [15.5°C]
1250 [590]

1120 [528]

1380 [651]

70°F [21.1°C]
1250 [590]

1120 [528]

1380 [651]

80°F [26.7°C]
1250 [590]

1120 [528]

11.7 [3.43]
1.8
14.1 [4.13]
1.9
16.6 [4.86]
1.9
19.0 [5.57]
2.0
21.5 [6.30]
2.0
23.9 [7.00]
2.0
26.4 [7.74]
2.1
28.8 [8.44]
2.1
31.3 [9.17]
2.2
33.7 [9.88]
2.2
36.2 [10.61]
2.2

11.6 [3.40]
1.9
14.0 [4.10]
1.9
16.5 [4.84]
1.9
18.9 [5.54]
2.0
21.3 [6.24]
2.0
23.8 [6.98]
2.1
26.2 [7.68]
.1
28.6 [8.38]
2.1
31.1 [9.11]
2.2
33.5 [9.82]
2.2
35.9 [10.52]
2.3

11.5 [3.37]
1.9
13.9 [4.07]
1.9
16.3 [4.78]
2.0
18.8 [5.51]
2.0
21.2 [6.21]
2.1
23.6 [6.92]
2.1
26.0 [7.62]
2.1
28.4 [8.32]
2.2
30.8 [9.03]
2.2
33.3 [9.76]
2.3
35.7 [10.46]
2.3

9.6 [2.81]
2.1
12.1 [3.55]
2.1
14.5 [4.25]
2.2
17.0 [4.98]
2.2
19.4 [5.69]
2.3
21.9 [6.42]
2.3
24.3 [7.12]
2.3
26.8 [7.85]
2.4
29.2 [8.56]
2.4
31.7 [9.29]
2.5
34.1 [9.99]
2.5

9.6 [2.81]
2.1
12.0 [3.52]
2.2
14.4 [4.22]
2.2
16.9 [4.95]
2.2
19.3 [5.66]
2.3
21.7 [6.36]
2.3
24.2 [7.09]
2.4
26.6 [7.80]
2.4
29.0 [8.50]
2.4
31.5 [9.23]
2.5
33.9 [9.94]
2.5

9.5 [2.78]
2.1
11.9 [3.49]
2.2
14.3 [4.19]
2.2
16.7 [4.89]
2.3
19.2 [5.63]
2.3
21.6 [6.33]
2.4
24.0 [7.03]
2.4
26.4 [7.74]
2.4
28.8 [8.44]
2.5
31.2 [9.14]
2.5
33.7 [9.88]
2.6

8.3 [2.43]
2.4
10.7 [3.14]
2.4
13.2 [3.87]
2.5
15.6 [4.57]
2.5
18.1 [5.30]
2.5
20.5 [6.01]
2.6
23.0 [6.74]
2.6
25.4 [7.44]
2.7
27.9 [8.18]
2.7
30.3 [8.88]
2.8
32.8 [9.61]
2.8

8.2 [2.40]
2.4
10.6 [3.11]
2.5
13.1 [3.84]
2.5
15.5 [4.54]
2.5
17.9 [5.25]
2.6
20.4 [5.98]
2.6
22.8 [6.68]
2.7
25.2 [7.39]
2.7
27.7 [8.12]
2.7
30.1 [8.82]
2.8
32.5 [9.52]
2.8

8.1 [2.37]
2.4
10.6 [3.11]
2.5
13.0 [3.81]
2.5
15.4 [4.51]
2.6
17.8 [5.22]
2.6
20.2 [5.92]
2.7
22.6 [6.62]
2.7
25.1 [7.36]
2.7
27.5 [8.06]
2.8
29.9 [8.76]
2.8
32.3 [9.47]
2.9

[ ] Designates Metric Conversions

21

Air

Gross Systems Performance Data
RQPL Series

COOLING PERFORMANCE DATA—RQPL-042
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1400 [661]
.15

1260 [595]
.14

1540 [727]
.17

67°F [19.4°C]
1400 [661]
.15

1260 [595]
.14

1540 [727]
.17

63°F [17.2°C]
1400 [661]
.15

1260 [595]
.14

Total BTUH [kW] 53.9 [5.80]
75
Sens BTUH [kW] 32.2 [9.44]
[23.9]
2.9
Power

52.9 [15.50]
30.7 [9.00]
2.9

51.9 [15.21]
29.3 [8.59]
2.9

50.9 [14.92]
37.1 [10.87]
2.9

50.0 [14.65]
35.5 [10.40]
2.9

49.1 [14.39]
33.8 [9.91]
2.9

48.1 [14.10]
39.3 [11.52]
2.9

47.3 [13.86]
37.5 [10.99]
2.9

46.4 [13.60]
35.8 [10.49]
2.9

Total BTUH [kW] 52.0 [15.24]
80
Sens BTUH [kW] 31.3 [9.17]
[26.7]
3.1
Power

51.0 [14.95]
29.9 [8.76]
3.1

50.1 [14.68]
28.5 [8.35]
3.1

49.0 [14.36]
36.3 [10.64]
3.1

48.1 [14.10]
34.7 [10.17]
3.1

47.2 [13.83]
33.0 [9.67]
3.0

46.2 [13.54]
38.4 [11.25]
3.1

45.4 [13.31]
36.7 [10.76]
3.1

44.6 [13.07]
35.0 [10.26]
3.0

Total BTUH [kW] 50.3 [14.74]
85
Sens BTUH [kW] 30.5 [8.94]
[29.4]
3.3
Power

49.4 [14.48]
29.2 [8.56]
3.2

48.5 [14.21]
27.8 [8.15]
3.2

47.3 [13.86]
35.5 [10.40]
3.3

46.5 [13.63]
33.9 [9.94]
3.2

45.6 [13.36]
32.3 [9.47]
3.2

44.6 [13.07]
37.6 [11.02]
3.2

43.8 [12.84]
35.9 [10.52]
3.2

43.0 [12.60]
34.3 [10.05]
3.2

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

48.7 [14.27]
29.8 [8.73]
3.4

47.9 [14.04]
28.4 [8.32]
3.4

47.0 [13.77]
27.1 [7.94]
3.4

45.8 [13.42]
34.7 [10.17]
3.4

44.9 [13.16]
33.2 [9.73]
3.4

44.1 [12.92]
31.6 [9.26]
3.4

43.0 [12.60]
36.8 [10.79]
3.4

42.2 [12.37]
35.2 [10.32]
3.4

41.5 [12.16]
33.6 [9.85]
3.4

47.2 [13.83]
29.0 [8.50]
3.6

46.4 [13.60]
27.7 [8.12]
3.6

45.5 [13.33]
26.4 [7.74]
3.5

44.2 [12.95]
34.0 [9.96]
3.6

43.4 [12.72]
32.4 [9.50]
3.6

42.7 [12.51]
30.9 [9.06]
3.5

41.5 [12.16]
36.1 [10.58]
3.6

40.7 [11.93]
34.5 [10.11]
3.6

40.0 [11.72]
32.9 [9.64]
3.5

45.6 [13.36]
28.2 [8.26]
3.8

44.8 [13.13]
26.9 [7.88]
3.7

44.0 [12.90]
25.7 [7.53]
3.7

42.6 [12.48]
33.2 [9.73]
3.8

41.9 [12.28]
31.7 [9.29]
3.7

41.1 [12.05]
30.2 [8.85]
3.7

39.9 [11.69]
35.3 [10.35]
3.7

39.2 [11.49]
33.7 [9.88]
3.7

38.5 [11.28]
32.1 [9.41]
3.7

Total BTUH [kW] 43.8 [12.84]
105
Sens BTUH [kW] 27.4 [8.03]
[40.6]
3.9
Power

43.0 [12.60]
26.1 [7.65]
3.9

42.3 [12.40]
24.9 [7.30]
3.9

40.8 [11.96]
32.3 [9.47]
3.9

40.1 [11.75]
30.9 [9.06]
3.9

39.4 [11.55]
29.4 [8.62]
3.9

38.1 [11.17]
34.4 [10.08]
3.9

37.4 [10.96]
32.9 [9.64]
3.9

36.7 [10.76]
31.4 [9.20]
3.9

41.0 [12.02]
25.2 [7.39]
4.1
38.6 [11.31]
24.2 [7.09]
4.2

40.2 [11.78]
24.1 [7.06]
4.0
37.9 [11.11]
23.1 [6.77]
4.2

38.8 [11.37]
31.4 [9.20]
4.1
36.3 [10.64]
30.3 [8.88]
4.3

38.1 [11.17]
30.0 [8.79]
4.1
35.6 [10.43]
29.0 [8.50]
4.2

37.4 [10.96]
28.6 [8.38]
4.0
35.0 [10.26]
27.6 [8.09]
4.2

36.0 [10.55]
33.5 [9.82]
4.1
33.5 [9.82]
32.4 [9.50]
4.3

35.4 [10.37]
32.0 [9.38]
4.1
32.9 [9.64]
31.0 [9.09]
4.2

34.7 [10.17]
30.5 [8.94]
4.0
32.3 [9.47]
29.5 [8.65]
4.2

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1540 [727]
.17

41.7 [12.22]
26.4 [7.74]
4.1
39.3 [11.52]
25.4 [7.44]
4.3

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-042
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

22

1540 [727]

60°F [15.5°C]
1400 [661]

1260 [595]

1540 [727]

70°F [21.1°C]
1400 [661]

1260 [595]

1540 [727]

80°F [26.7°C]
1400 [661]

1260 [595]

13.9 [4.07]
2.6
16.9 [4.95]
2.6
20.0 [5.86]
2.6
23.0 [6.74]
2.7
26.0 [7.62]
2.7
29.0 [8.50]
2.8
32.0 [9.38]
2.8
35.1 [10.29]
2.8
38.1 [11.17]
2.9
41.1 [12.05]
2.9
44.1 [12.92]
2.9

13.8 [4.04]
2.6
16.8 [4.92]
2.6
19.8 [5.80]
2.7
22.8 [6.68]
2.7
25.8 [7.56]
2.7
28.8 [8.44]
2.8
31.8 [9.32]
2.8
34.8 [10.20]
2.9
37.8 [11.08]
2.9
40.8 [11.96]
2.9
43.8 [12.84]
3.0

13.7 [4.02]
2.6
16.7 [4.89]
2.7
19.7 [5.77]
2.7
22.6 [6.62]
2.7
25.6 [7.50]
2.8
28.6 [8.38]
2.8
31.6 [9.26]
2.9
34.6 [10.14]
2.9
37.5 [10.99]
2.9
40.5 [11.87]
3.0
43.5 [12.75]
3.0

12.9 [3.78]
3.0
16.0 [4.69]
3.0
19.0 [5.57]
3.1
22.0 [6.45]
3.1
25.0 [7.33]
3.1
28.0 [8.21]
3.2
31.1 [9.11]
3.2
34.1 [9.99]
3.2
37.1 [10.87]
3.3
40.1 [11.75]
3.3
43.1 [12.63]
3.4

12.8 [3.75]
3.0
15.8 [4.63]
3.1
18.8 [5.51]
3.1
21.8 [6.39]
3.1
24.8 [7.27]
3.2
27.8 [8.15]
3.2
30.8 [9.03]
3.2
33.8 [9.91]
3.3
36.8 [10.79]
3.3
39.8 [11.66]
3.4
42.8 [12.54]
3.4

12.8 [3.75]
3.1
15.7 [4.60]
3.1
18.7 [5.48]
3.1
21.7 [6.36]
3.2
24.7 [7.24]
3.2
27.6 [8.09]
3.3
30.6 [8.97]
3.3
33.6 [9.85]
3.3
36.6 [10.73]
3.4
39.5 [11.58]
3.4
42.5 [12.46]
3.4

11.2 [3.28]
3.3
14.2 [4.16]
3.4
17.3 [5.07]
3.4
20.3 [5.95]
3.5
23.3 [6.83]
3.5
26.3 [7.71]
3.5
29.3 [8.59]
3.6
32.4 [9.50]
3.6
35.4 [10.37]
3.6
38.4 [11.25]
3.7
41.4 [12.13]
3.7

11.1 [3.25]
3.4
14.1 [4.13]
3.4
17.1 [5.01]
3.5
20.1 [5.89]
3.5
23.1 [6.77]
3.5
26.1 [7.65]
3.6
29.1 [8.53]
3.6
32.1 [9.41]
3.6
35.1 [10.29]
3.7
38.1 [11.17]
3.7
41.1 [12.05]
3.8

11.1 [3.25]
3.4
14.0 [4.10]
3.5
17.0 [4.98]
3.5
20.0 [5.86]
3.5
23.0 [6.74]
3.6
25.9 [7.59]
3.6
28.9 [8.47]
3.7
31.9 [9.35]
3.7
34.9 [10.23]
3.7
37.9 [11.11]
3.8
40.8 [11.96]
3.8

[ ] Designates Metric Conversions

Air

Gross Systems Performance Data
RQPL Series

COOLING PERFORMANCE DATA—RQPL-048
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀
wbE
CFM [L/s]
DR ➀

O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E

71°F [21.7°C]
1600 [755]
.13

1440 [680]
.11

1760 [831]
.15

67°F [19.4°C]
1600 [755]
.13

1440 [680]
.11

1760 [831]
.15

63°F [17.2°C]
1600 [755]
.13

1440 [680]
.11

Total BTUH [kW] 60.4 [17.70]
75
Sens BTUH [kW] 37.4 [10.96]
[23.9]
3.2
Power

59.3 [17.38]
35.7 [10.46]
3.1

58.3 [17.09]
34.1 [9.99]
3.1

57.1 [16.73]
42.7 [12.51]
3.1

56.1 [16.44]
40.8 [11.96]
3.1

55.0 [16.12]
38.9 [11.40]
3.1

54.5 [15.97]
45.0 [13.19]
3.1

53.5 [15.68]
43.0 [12.60]
3.1

52.5 [15.39]
41.0 [12.02]
3.1

Total BTUH [kW] 58.8 [17.23]
80
Sens BTUH [kW] 36.6 [10.73]
[26.7]
3.4
Power

57.8 [16.94]
35.0 [10.26]
3.3

56.7 [16.62]
33.3 [9.76]
3.3

55.5 [16.27]
41.9 [12.28]
3.3

54.5 [15.97]
40.0 [11.72]
3.3

53.5 [15.68]
38.2 [11.20]
3.3

52.9 [15.50]
44.2 [12.95]
3.3

51.9 [15.21]
42.2 [12.37]
3.3

51.0 [14.95]
40.3 [11.81]
3.2

Total BTUH [kW] 57.0 [16.71]
85
Sens BTUH [kW] 35.7 [10.46]
[29.4]
3.5
Power

56.0 [16.41]
34.1 [9.99]
3.5

55.0 [16.12]
32.5 [9.52]
3.5

53.7 [15.74]
41.0 [12.02]
3.5

52.7 [15.44]
39.2 [11.49]
3.5

51.8 [15.18]
37.3 [10.93]
3.5

51.1 [14.98]
43.3 [12.69]
3.5

50.2 [14.71]
41.4 [12.13]
3.5

49.3 [14.45]
39.4 [11.55]
3.4

Total BTUH [kW]
90
Sens BTUH [kW]
[32.2]
Power
Total BTUH [kW]
95
Sens BTUH [kW]
[35]
Power
Total BTUH [kW]
100
Sens BTUH [kW]
[37.8]
Power

55.1 [16.15]
34.8 [10.20]
3.7

54.1 [15.86]
33.2 [9.73]
3.7

53.1 [15.56]
31.7 [9.29]
3.7

51.7 [15.15]
40.1 [11.75]
3.7

50.8 [14.89]
38.3 [11.22]
3.7

49.9 [14.62]
36.5 [10.70]
3.6

49.1 [14.39]
42.4 [12.43]
3.7

48.3 [14.16]
40.5 [11.87]
3.6

47.4 [13.89]
38.6 [11.31]
3.6

53.1 [15.56]
33.8 [9.91]
3.9

52.1 [15.27]
32.3 [9.47]
3.9

51.2 [15.01]
30.8 [9.03]
3.9

49.8 [14.59]
39.1 [11.46]
3.9

48.9 [14.33]
37.4 [10.96]
3.9

48.0 [14.07]
35.6 [10.43]
3.8

47.2 [13.83]
41.4 [12.13]
3.9

46.3 [13.57]
39.6 [11.61]
3.8

45.5 [13.33]
37.7 [11.05]
3.8

51.1 [14.98]
32.9 [9.64]
4.1

50.2 [14.71]
31.4 [9.20]
4.1

49.3 [14.45]
29.9 [8.76]
4.0

47.8 [14.01]
38.2 [11.20]
4.1

46.9 [13.75]
36.5 [10.70]
4.0

46.1 [13.51]
34.8 [10.20]
4.0

45.2 [13.25]
40.5 [11.87]
4.1

44.4 [13.01]
38.7 [11.34]
4.0

43.6 [12.78]
36.9 [10.81]
4.0

Total BTUH [kW] 49.3 [14.45]
105
Sens BTUH [kW] 32.0 [9.38]
[40.6]
4.3
Power

48.4 [14.18]
30.6 [8.97]
4.3

47.5 [13.92]
29.2 [8.56]
4.2

46.0 [13.48]
37.3 [10.93]
4.3

45.1 [13.22]
35.7 [10.46]
4.2

44.3 [12.98]
34.0 [9.96]
4.2

43.4 [12.72]
39.6 [11.61]
4.2

42.6 [12.48]
37.9 [11.11]
4.2

41.8 [12.25]
36.1 [10.58]
4.2

46.8 [13.72]
29.9 [8.76]
4.4
45.5 [13.33]
29.3 [8.59]
4.6

45.9 [13.45]
28.5 [8.35]
4.4
44.6 [13.07]
27.9 [8.18]
4.6

44.3 [12.98]
36.6 [10.73]
4.5
43.0 [12.60]
36.0 [10.55]
4.6

43.5 [12.75]
34.9 [10.23]
4.4
42.2 [12.37]
34.4 [10.08]
4.6

42.7 [12.51]
33.3 [9.76]
4.4
41.4 [12.13]
32.8 [9.61]
4.6

41.7 [12.22]
38.9 [11.40]
4.4
40.4 [11.84]
38.3 [11.22]
4.6

41.0 [12.02]
37.1 [10.87]
4.4
39.6 [11.61]
36.6 [10.73]
4.6

40.2 [11.78]
35.4 [10.37]
4.4
38.9 [11.40]
34.8 [10.20]
4.5

Total BTUH [kW]
110
Sens BTUH [kW]
°F [43.3] Power
[°C]
Total BTUH [kW]
115
Sens BTUH [kW]
[46.1]
Power
DR —Depression ratio
dbE —Entering air dry bulb
wbE —Entering air wet bulb

1760 [831]
.15

47.6 [13.95]
31.3 [9.17]
4.5
46.3 [13.57]
30.7 [9.00]
4.7

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input

NOTES:
➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible capacity
from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

HEATING PERFORMANCE DATA—RQPL-048
IDB
CFM [L/s]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]

0
[-17.8]
5
[-15]
10
[-12.2]
15
[-9.4]
20
[-6.7]
25
[-3.9]
30
[-1.1]
35
[1.7]
40
[4.4]
45
[7.2]
50
[10]

Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power
Total BTUH [kW]
Power

IDB—Indoor air dry bulb

1760 [831]

60°F [15.5°C]
1600 [755]

1440 [680]

1760 [831]

70°F [21.1°C]
1600 [755]

1440 [680]

1760 [831]

80°F [26.7°C]
1600 [755]

1440 [680]

16.9 [4.95]
2.6
20.1 [5.89]
2.6
23.2 [6.80]
2.7
26.4 [7.74]
2.7
29.5 [8.65]
2.8
32.7 [9.58]
2.8
35.9 [10.52]
2.9
39.0 [11.43]
2.9
42.2 [12.37]
3.0
45.3 [13.28]
3.0
48.5 [14.21]
3.1

16.8 [4.92]
2.6
19.9 [5.83]
2.6
23.1 [6.77]
2.7
26.2 [7.68]
2.8
29.3 [8.59]
2.8
32.5 [9.52]
2.9
35.6 [10.43]
2.9
38.7 [11.34]
3.0
41.9 [12.28]
3.0
45.0 [13.19]
3.1
48.1 [14.10]
3.1

16.7 [4.89]
2.6
19.8 [5.80]
2.7
22.9 [6.71]
2.7
26.0 [7.62]
2.8
29.1 [8.53]
2.8
32.2 [9.44]
2.9
35.4 [10.37]
2.9
38.5 [11.28]
3.0
41.6 [12.19]
3.1
44.7 [13.10]
3.1
47.8 [14.01]
3.2

15.4 [4.51]
3.0
18.6 [5.45]
3.0
21.8 [6.39]
3.1
24.9 [7.30]
3.1
28.1 [8.24]
3.2
31.2 [9.14]
3.2
34.4 [10.08]
3.3
37.5 [10.99]
3.3
40.7 [11.93]
3.4
43.9 [12.87]
3.4
47.0 [13.77]
3.5

15.3 [4.48]
3.0
18.5 [5.42]
3.0
21.6 [6.33]
3.1
24.7 [7.24]
3.2
27.9 [8.18]
3.2
31.0 [9.09]
3.3
34.1 [9.99]
3.3
37.3 [10.93]
3.4
40.4 [11.84]
3.4
43.6 [12.78]
3.5
46.7 [13.69]
3.5

15.2 [4.45]
3.0
18.3 [5.36]
3.1
21.5 [6.30]
3.1
24.6 [7.21]
3.2
27.7 [8.12]
3.2
30.8 [9.03]
3.3
33.9 [9.94]
3.4
37.0 [10.84]
3.4
40.1 [11.75]
3.5
43.2 [12.66]
3.5
46.4 [13.60]
3.6

14.4 [4.22]
3.4
17.6 [5.16]
3.5
20.7 [6.07]
3.5
23.9 [7.00]
3.6
27.1 [7.94]
3.6
30.2 [8.85]
3.7
33.4 [9.79]
3.7
36.5 [10.70]
3.8
39.7 [11.63]
3.8
42.8 [12.54]
3.9
46.0 [13.48]
3.9

14.3 [4.19]
3.5
17.5 [5.13]
3.5
20.6 [6.04]
3.6
23.7 [6.95]
3.6
26.9 [7.88]
3.7
30.0 [8.79]
3.7
33.1 [9.70]
3.8
36.3 [10.64]
3.8
39.4 [11.55]
3.9
42.5 [12.46]
3.9
45.7 [13.39]
4.0

14.2 [4.16]
3.5
17.3 [5.07]
3.5
20.4 [5.98]
3.6
23.6 [6.92]
3.7
26.7 [7.83]
3.7
29.8 [8.73]
3.8
32.9 [9.64]
3.8
36.0 [10.55]
3.9
39.1 [11.46]
3.9
42.2 [12.37]
4.0
45.3 [13.28]
4.0

[ ] Designates Metric Conversions

23

24

High

Low

Low

Low
(Tap 1)

Low
(Tap 1)

2.0
[7.03]

2.5
[8.79]

3.0
[10.55]

3.5
[12.31]

4.0
[14.07]

1350 CFM/1700 CFM
[496/802 L/s]

1225 CFM/1575 CFM
[578/743 L/s]

1050 CFM/1350 CFM
[496/637 L/s]

875 CFM/1125 CFM
[413/531 L/s]

700 CFM/900 CFM
[271/319 L/s]

Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
1/3 HP [248]
1 Speed
(PSC Motor)

10x9 Blower
1/2 HP [372]
2 Speed
(PSC Motor)

9x7 Blower
1/4 HP [186]
2 Speed
(PSC Motor)

Blower Size/
Motor
HP [W] &
# of Speeds

High
(Tap 2)

Low
(Tap 1)

High
(Tap 2)

Low
(Tap 1)

High

High

Medium

Low

High

Low

Motor
Speed

[ ] Designates Metric Conversions

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
CFM [L/s]
600 [283]
800 [378]
Pressure Drop—Inches W.C. [kPa]
.00
.01 [.002]

NOTE: Effect of electric heat strip on airflow performance is negligible.

Motor
Speed
from
Factory

Nominal
Cooling
Capacity
Tons [kW]
0.1 [.02]

292
1076 [508]

CFM

1514 [715]
895
538

CFM
RPM
Watts

0.2 [.05]

454

1000 [472]
.02 [.005]

966

1770 [835]

CFM
RPM

390

Watts

923

1675 [791]

CFM
RPM

321

Watts

870

1559 [736]

CFM
RPM

268

Watts

824

RPM

1455 [687]

CFM
Watts

352

355

1200 [566]
.03 [.007]

466

989

1751 [826]

401

944

1658 [782]

327

893

1530 [722]

280

856

1431 [675]

805

785

RPM

1201 [567]

514

930

1461 [690]

415

810

1197 [565]

349

775

1059 [500]

278

965

861 [406]

214

785

657 [310]

Watts

1222 [577]

423

CFM

765

RPM

1222 [577]

Watts

CFM

356

940

RPM
Watts
730

898 [424]

CFM

RPM

221

Watts

695

RPM

675 [319]

Watts

CFM

INDOOR AIRFLOW PERFORMANCE—208 VOLTS

1400 [661]
.05 [.012]

473

1018

1706 [805]

412

979

1610 [760]

338

932

1488 [702]

288

889

1396 [659]

346

830

1173 [554]

493

965

1415 [668]

407

855

1179 [556]

341

820

1032 [487]

266

995

822 [388]

203

870

634 [299]

0.3 [.07]

1600 [775]
.07 [.017]

486

1050

1672 [789]

425

1013

1580 [746]

351

968

1454 [686]

303

931

1360 [642]

340

870

1137 [537]

473

985

1370 [647]

397

890

1162 [548]

331

865

996 [470]

253

1020

777 [367]

191

905

602 [284]

0.4 [.10]

490

1078

1624 [766]

433

1045

1535 [724]

364

1007

1417 [669]

311

968

1315 [621]

331

905

1090 [514]

454

1005

1322 [624]

386

920

1137 [537]

320

905

950 [448]

239

1045

721 [340]

171

940

560 [264]

0.5 [.12]

External Static Pressure—Inches W.C. [kPa]
Side Discharge—Wet Coil
0.6 [.15]

481

1100

1555 [734]

440

1077

1491 [704]

371

1036

1375 [649]

325

1009

1285 [606]

320

950

1030 [486]

434

1025

1266 [597]

370

960

1097 [518]

305

940

896 [423]

221

1070

651 [307]

163

980

505 [238]

0.7 [.17]

460

1115

1463 [690]

432

1098

1422 [671]

381

1072

1336 [631]

331

1041

1241 [586]

306

990

954 [450]

412

1045

1197 [565]

351

995

1033 [488]

287

975

832 [393]

199

1090

562 [265]

149

1020

435 [205]

Air
Indoor Airflow Performance
RQNL Series

High

Low

High

Low
(Tap 1)

Low
(Tap 1)

2.0
[7.03]

2.5
[8.79]

3.0
[10.55]

3.5
[12.31]

4.0
[14.07]

1350 CFM/1700 CFM
[496/802 L/s]

1225 CFM/1575 CFM
[578/743 L/s]

1050 CFM/1350 CFM
[496/637 L/s]

875 CFM/1125 CFM
[413/531 L/s]

700 CFM/900 CFM
[271/319 L/s]

Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
1/3 HP [249]
1 Speed
(PSC Motor)

10x9 Blower
1/2 HP [373]
3 Speed
(PSC Motor)

9x7 Blower
1/4 HP [186]
2 Speed
(PSC Motor)

Blower Size/
Motor
HP [W] &
# of Speeds

High
(Tap 2)

Low
(Tap 1)

High
(Tap 2)

Low
(Tap 1)

High

High

Medium

Low

High

Low

Motor
Speed

[ ] Designates Metric Conversions

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
CFM [L/s]
600 [283]
800 [378]
Pressure Drop—Inches W.C. [kPa]
.00
.01 [.002]

NOTE: Effect of electric heat strip on airflow performance is negligible.

Motor
Speed
from
Factory

Nominal
Cooling
Capacity
Tons [kW]
0.1 [.02]

315
1206 [569]

CFM

1641 [774]
980
589

CFM
RPM
Watts

0.2 [.05]

440

1000 [472]
.02 [.005]

955

1748 [825]

CFM
RPM

404

Watts

931

1692 [799]

CFM
RPM

317

Watts

867

1550 [732]

CFM
RPM

276

Watts

831

RPM

1467 [692]

CFM
Watts

419

428

1200 [566]
.03 [.007]

446

978

1718 [811]

409

950

1661 [784]

323

890

1520 [717]

282

854

1439 [679]

875

835

RPM

1357 [640]

565

1000

1577 [744]

498

900

1368 [646]

406

815

1182 [558]

303

1015

922 [435]

242

870

751 [354]

Watts

1391 [656]

498

CFM

865

RPM

1411 [666]

Watts

CFM

419

990

RPM
Watts
760

946 [446]

CFM

RPM

253

Watts

825

RPM

771 [364]

Watts

CFM

INDOOR AIRFLOW PERFORMANCE—230 VOLTS

1400 [661]
.05 [.012]

462

1010

1686 [796]

424

982

1633 [771]

339

930

1486 [701]

297

894

1408 [665]

406

915

1312 [619]

543

1020

1515 [715]

481

935

1327 [626]

394

870

1157 [546]

288

1035

882 [416]

230

910

725 [342]

0.3 [.07]

1600 [775]
.07 [.017]

475

1043

1647 [777]

434

1018

1589 [750]

355

974

1449 [684]

307

932

1360 [642]

392

940

1258 [594]

523

1035

1455 [687]

464

970

1285 [606]

381

910

1128 [532]

273

1055

830 [392]

217

950

691 [326]

0.4 [.10]

484

1073

1616 [763]

450

1054

1560 [736]

362

1003

1407 [664]

319

972

1331 [628]

378

965

1201 [567]

503

1050

1393 [657]

447

1000

1238 [584]

368

950

1091 [515]

257

1070

769 [363]

204

985

645 [304]

0.5 [.12]

External Static Pressure—Inches W.C. [kPa]
Side Discharge—Wet Coil
0.6 [.15]

473

1096

1543 [728]

453

1082

1512 [714]

377

1039

1382 [652]

326

1005

1287 [607]

365

985

1145 [540]

481

1065

1329 [627]

431

1020

1183 [558]

353

975

1044 [493]

241

1085

701 [331]

189

1010

584 [276]

0.7 [.17]

459

1111

1472 [695]

443

1103

1442 [681]

385

1073

1337 [631]

341

1042

1259 [594]

355

1000

1093 [516]

456

1080

1262 [596]

391

1035

1116 [527]

334

1000

983 [464]

226

1100

630 [297]

181

1030

546 [258]

Air
Indoor Airflow Performance
RQNL Series

25

26

High
(Tap 1)

Low
(Tap 1)

Low
(Tap 1)

Low
(Tap 1)

Low
(Tap 1)

2.0
[7.03]

2.5
[8.79]

3.0
[10.55]

3.5
[12.31]

4.0
[14.07]

1350 CFM/1700 CFM
[496/802 L/s]

1225 CFM/1575 CFM
[578/743 L/s]

1050 CFM/1350 CFM
[496/637 L/s]

875 CFM/1125 CFM
[413/531 L/s]

700 CFM/900 CFM
[271/319 L/s]

Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
1/2 HP [372]
3 Speed
(X13 Motor)

10x9 Blower
1/2 HP [372]
3 Speed
(X13 Motor)

9x7 Blower
1/3 HP [249]
3 Speed
(X13 Motor)

Blower Size/
Motor
HP [W] &
# of Speeds

High
(Tap 2)

Low
(Tap 1)

High
(Tap 2)

Low
(Tap 1)

High
(Tap 3)

Medium
(Tap 2)

Low
(Tap 1)

High
(Tap 3)

Medium
(Tap 2)

Low
(Tap 1)

High
(Tap 2)

Low
(Tap 1)

Motor
Speed

[ ] Designates Metric Conversions

0.1 [.02]

454

1000 [472]
.02 [.005]

966

1770 [835]

CFM
RPM

390

Watts

923

1675 [791]

CFM
RPM

321

Watts

870

1559 [736]

CFM
RPM

268

Watts

824

RPM

1455 [687]

CFM
Watts

280

1200 [566]
.03 [.007]

466

989

1751 [826]

401

944

1658 [782]

327

893

1530 [722]

280

856

1431 [675]

898

268

1357 [640]

864

1396 [659]

CFM

242

850

RPM

233

1292 [610]

208

819

Watts

820

RPM
Watts

1307 [617]

200

CFM

784

RPM

1247 [589]

CFM
Watts

210
1220 [576]

826

206

1213 [572]

796

1252 [591]

CFM

177

785

1132 [534]

145

749

1034 [488]

177

971

887 [419]

147

818

RPM

167

0.2 [.05]
818 [386]

Watts

744

RPM
Watts

1165 [550]

143

CFM

719

1067 [504]

CFM
RPM

173

Watts

934

914 [431]

CFM
RPM

145

Watts

892

RPM

847 [400]

Watts

CFM

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
CFM [L/s]
600 [283]
800 [378]
Pressure Drop—Inches W.C. [kPa]
.00
.01 [.002]

NOTE: Effect of electric heat strip on airflow performance is negligible.

Motor
Speed
from
Factory

Nominal
Cooling
Capacity
Tons [kW]

INDOOR AIRFLOW PERFORMANCE—208 VOLTS

473

1018

0.4 [.10]

486

1050

1672 [789]

425

1013

1580 [746]

351

968

1454 [686]

303

931

1360 [642]

292

942

1286 [607]

255

918

1214 [573]

224

890

1143 [539]

225

893

1137 [537]

191

864

1051 [496]

159

819

957 [452]

186

1053

824 [389]

157

765

765 [361]

1400 [661]
.05 [.012]

1706 [805]

412

979

1610 [760]

338

932

1488 [702]

288

889

1396 [659]

288

920

1334 [630]

248

889

1238 [584]

219

863

1178 [556]

219

868

1166 [550]

188

833

1091 [515]

155

791

992 [468]

185

1024

853 [403]

156

788

788 [372]

0.3 [.07]

1600 [775]
.07 [.017]

490

1078

1624 [766]

433

1045

1535 [724]

364

1007

1417 [669]

311

968

1315 [621]

299

976

1253 [591]

262

944

1170 [552]

233

932

1099 [519]

234

934

1099 [519]

202

905

1009 [476]

169

876

912 [430]

188

1083

793 [374]

164

737

737 [348]

0.5 [.12]

481

1100

1555 [734]

440

1077

1491 [704]

371

1036

1375 [649]

325

1009

1285 [606]

304

1010

1207 [570]

268

981

1135 [536]

236

957

1064 [502]

245

982

1046 [494]

206

951

959 [453]

182

952

820 [387]

192

1121

762 [360]

167

695

695 [328]

0.6 [.15]

External Static Pressure—Inches W.C. [kPa]
Side Discharge—Wet Coil
0.7 [.17]

460

1115

1463 [690]

432

1098

1422 [671]

381

1072

1336 [631]

331

1041

1241 [586]

310

1043

1163 [549]

277

1028

1087 [513]

246

1012

998 [471]

248

1026

986 [465]

217

1020

855 [404]

185

983

778 [367]

185

1135

717 [338]

167

659

659 [311]

0.8 [.20]

316

1089

1103 [521]

284

1087

989 [467]

256

1075

904 [427]

256

1086

892 [421]

351

1053

819 [387]

192

1024

729 [344]

164

1155

602 [284]

155

581

581 [274]

Air
Indoor Airflow Performance
RQPL Series

Low
(Tap 1)

Low
(Tap 1)

Low
(Tap 1)

Low
(Tap 1)

Low
(Tap 1)

2.0
[7.03]

2.5
[8.79]

3.0
[10.55]

3.5
[12.31]

4.0
[14.07]

1350 CFM/1700 CFM
[496/802 L/s]

1225 CFM/1575 CFM
[578/743 L/s]

1050 CFM/1350 CFM
[496/637 L/s]

875 CFM/1125 CFM
[413/531 L/s]

700 CFM/900 CFM
[271/319 L/s]

Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
3/4 HP [559]
2 Speed
(X13 Motor)

10x9 Blower
1/2 HP [372]
3 Speed
(X13 Motor)

10x9 Blower
1/2 HP [372]
3 Speed
(X13 Motor)

9x7 Blower
1/3 HP [249]
3 Speed
(X13 Motor)

Blower Size/
Motor
HP [W] &
# of Speeds

High
(Tap 2)

Low
(Tap 1)

High
(Tap 2)

Low
(Tap 1)

High
(Tap 3)

Medium
(Tap 2)

Low
(Tap 1)

High
(Tap 3)

Medium
(Tap 2)

Low
(Tap 1)

High
(Tap 2)

Low
(Tap 1)

Motor
Speed

27

[ ] Designates Metric Conversions

0.1 [.02]

440

1000 [472]
.02 [.005]

955

1748 [825]

CFM
RPM

404

Watts

931

1692 [799]

CFM
RPM

317

Watts

867

1550 [732]

CFM
RPM

276

Watts

831

RPM

1467 [692]

CFM
Watts

290

1200 [566]
.03 [.007]

446

978

1718 [811]

409

950

1661 [784]

323

890

1520 [717]

282

854

1439 [679]

898

285

1379 [651]

874

1416 [668]

CFM

249

867

RPM

239

1298 [613]

217

829

Watts

821

RPM
Watts

1336 [631]

210

CFM

802

RPM

1258 [594]

CFM
Watts

217
1215 [573]

836

212

1223 [577]

797

1271 [600]

CFM

182

799

1124 [530]

148

753

1041 [491]

184

988

888 [419]

159

953

RPM

176

0.2 [.05]
834 [394]

Watts

762

RPM
Watts

1187 [560]

144

CFM

715

1076 [508]

CFM
RPM

181

Watts

953

918 [433]

CFM
RPM

151

Watts

889

RPM

862 [407]

Watts

CFM

DOWN DISCHARGE PRESSURE DROP (ADD TO EXTERNAL STATIC PRESSURE)
CFM [L/s]
600 [283]
800 [378]
Pressure Drop—Inches W.C. [kPa]
.00
.01 [.002]

NOTE: Effect of electric heat strip on airflow performance is negligible.

Motor
Speed
from
Factory

Nominal
Cooling
Capacity
Tons [kW]

INDOOR AIRFLOW PERFORMANCE—230 VOLTS

462

1010

0.4 [.10]

475

1043

1647 [777]

434

1018

1589 [750]

355

974

1449 [684]

307

932

1360 [642]

304

952

1292 [610]

262

920

1229 [580]

230

894

1160 [547]

231

905

1137 [537]

196

859

1071 [505]

169

825

970 [458]

198

1060

838 [395]

166

1018

781 [369]

1400 [661]
.05 [.012]

1686 [796]

424

982

1633 [771]

339

930

1486 [701]

297

894

1408 [665]

299

933

1342 [633]

259

903

1259 [594]

225

861

1200 [566]

227

878

1169 [552]

191

832

1096 [517]

157

787

1017 [480]

194

1032

874 [412]

162

974

819 [387]

0.3 [.07]

1600 [775]
.07 [.017]

484

1073

1616 [778]

450

1054

1560 [736]

362

1003

1407 [664]

319

972

1331 [628]

314

993

1275 [602]

275

957

1198 [565]

239

933

1130 [533]

241

939

1104 [521]

209

914

1024 [483]

175

877

928 [438]

200

1091

819 [387]

173

1065

761 [359]

0.5 [.12]

473

1096

1543 [779]

453

1082

1512 [714]

377

1039

1382 [652]

326

1005

1287 [607]

322

1011

1240 [585]

279

993

1160 [547]

245

971

1082 [511]

247

974

1071 [505]

212

940

987 [466]

187

946

852 [402]

204

1126

781 [369]

176

1101

729 [344]

0.6 [.15]

External Static Pressure—Inches W.C. [kPa]
Side Discharge—Wet Coil
0.7 [.17]

459

1111

1472 [780]

443

1103

1442 [681]

385

1073

1337 [631]

341

1042

1259 [594]

328

1060

1200 [566]

290

1038

1116 [527]

259

1020

1026 [484]

257

1026

1015 [479]

227

1021

896 [423]

198

1005

785 [370]

189

1146

711 [336]

180

1133

695 [328]

0.8 [.20]

337

1091

1168 [551]

299

1071

1071 [505]

268

1077

954 [450]

270

1089

934 [441]

235

1059

852 [402]

202

1032

745 [352]

168

1157

616 [291]

165

1156

606 [286]

Air
Indoor Airflow Performance
RQPL Series

Air

Electrical Data
RQNL/RQPL Series

Unit Information

ELECTRICAL DATA – RQNL- SERIES
-B024JK

-B030JK

-B036CK

-B036JK

-B042CK

-B042JK

-B048CK

-B048JK

Unit Operating
Voltage Range

187-253

187-253

187-253

187-253

187-253

187-253

187-253

187-253

Minimum Circuit Ampacity

19/19

22/22

17/17

24/24

25/25

33/33

26/26

37/37

25/25

25/25

20/20

25/25

30/30

35/35

30/30

40/40

30/30

35/35

25/25

40/40

35/35

50/50

35/35

50/50

1
208/230
1
2
3450
12.8/12.8
58.3/58.3
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/4
1.5
2.4

1
208/230
1
2 1/2
3450
14.1/14.1
73/73
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/2
2.4
5.1

1
208/230
3
3
3450
10.4/10.4
88/88
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/3
1.7
2.5

1
208/230
1
3
3450
16.7/16.7
79/79
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/3
1.7
2.5

1
208/230
3
3 1/2
3450
13.1/13.1
83.1/83.1
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

1
208/230
1
3 1/2
3450
19.9/19.9
109/109
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

1
208/230
3
4
3450
13.7/13.7
83.1/83.1
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

1
208/230
1
4
3450
23.8/23.8
117/117
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

Evaporator Fan Condenser Motor Compressor Motor

Minimum Overcurrent
Protection Device Size
Maximum Overcurrent
Protection Device Size
No.
Volts
Phase
HP
RPM
Amps (RLA)
Amps (LRA)
No.
Volts
Phase
HP
Amps (FLA)
Amps (LRA)
No.
Volts
Phase
HP
Amps (FLA)
Amps (LRA)

Unit Information

ELECTRICAL DATA – RQPL- SERIES
-B024JK

B025JK

-B030JK

-B036CK

-B036JK

-B042CK

-B042JK

-B048CK

-B048JK

Unit Operating
Voltage Range

187-253

187-253

187-253

187-253

187-253

187-253

187-253

187-253

187-253

Minimum Circuit Ampacity

21/21

21/21

24/24

19/19

27/27

25/25

33/33

26/26

37/37

25/25

25/25

25/25

20/20

30/30

30/30

35/35

30/30

40/40

30/30

30/30

35/35

25/25

40/40

35/35

50/50

35/35

50/50

1
208/230
1
2
3450
12.8/12.8
58.3/58.3
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/3
2.8
0

1
208/230
1
2
3450
12.8/12.8
58.3/58.3
1
208/230
1
1/3
1.3/1.3
0/0
1
208/230
1
1/3
2.8/2.8
0/0

1
208/230
1
2 1/2
3450
14.1/14.1
73/73
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/2
4.1
0

1
208/230
3
3
3450
10.4/10.4
88/88
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/2
4.1
0

1
208/230
1
3
3450
16.7/16.7
79/79
1
208/230
1
1/5
1.3
2.2
1
208/230
1
1/2
4.1
0

1
208/230
3
3 1/2
3450
13.1/13.1
83.1/83.1
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

1
208/230
1
3 1/2
3450
19.9/19.9
109/109
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

1
208/230
3
4
3450
13.7/13.7
83.1/83.1
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

1
208/230
1
4
3450
23.8/23.8
117/117
1
208/230
1
1/3
2
3.9
1
208/230
1
3/4
6
0

Evaporator Fan Condenser Motor Compressor Motor

Minimum Overcurrent
Protection Device Size
Maximum Overcurrent
Protection Device Size
No.
Volts
Phase
HP
RPM
Amps (RLA)
Amps (LRA)
No.
Volts
Phase
HP
Amps (FLA)
Amps (LRA)
No.
Volts
Phase
HP
Amps (FLA)
Amps (LRA)

1. Horsepower Per Compressor.
2. Amp Draw Per Motor. Multiply Value By Number of Motors to Determine Total Amps.

28

Air

Unit Model Application

Electric Heater Kits
RQNL/RQPL Series

Electric Heater Kit Models
RXQJ-A05J (208-240 volt, 1-ph, 5kW)
RXQJ-A10J (208-240 volt, 1-ph, 10kW)

RQNL/RQPL-B024JK & RQPL-B025JK

RXQJ-A05J (208-240 volt, 1-ph, 5kW)
RXQJ-A10J (208-240 volt, 1-ph, 10kW)
RXQJ-A10J (208-240 volt, 1-ph, 10kW)
RXQJ-A15J (208-240 volt, 1-ph, 15kW)

RQNL/RQPL-B030JK
RQNL/RQPL-B036JK

RXQJ-10J (208-240 volt, 1-ph, 10kW)

RQNL/RQPL-B042JK

RXQJ-15J (208-240 volt, 1-ph, 15kW)
RXQJ-10J (208-240 volt, 1-ph, 10kW)
RXQJ-15J (208-240 volt, 1-ph, 15kW)
RXQJ-A10C (208-240 volt, 3-ph, 10kW)
RXQJ-A15C (208-240 volt, 3-ph, 15kW)

RQNL/RQPL-B048JK

RQNL/RQPL-B036CK

RXQJ-A10C (208-240 volt, 3-ph, 10kW)

RQNL/RQPL-B042CK

RXQJ-A15C (208-240 volt, 3-ph, 15kW)
RXQJ-A10C (208-240 volt, 3-ph, 10kW)
RXQJ-A15C (208-240 volt, 3-ph, 15kW)

RQNL/RQPL-B048CK

WARNING
ONLY ELECTRIC HEATER KITS SUPPLIED BY THIS MANUFACTURER AS DESCRIBED IN THIS PUBLICATION HAVE
BEEN DESIGNED, TESTED, AND EVALUATED BY A NATIONALLY RECOGNIZED SAFETY TESTING AGENCY FOR USE
WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED
ELECTRIC HEATERS INSTALLED WITHIN THIS UNIT MAY
CAUSE HAZARDOUS CONDITIONS RESULTING IN PROPERTY DAMAGE, FIRE, BODILY INJURY OR DEATH.

29

30

B048CK

B042CK

B036CK

Unit
Model
No.
RQNL-

B048JK

B042JK

B036JK

B030JK

B024JK

Unit
Model
No.
RQNL-

No Heat
A10C
A15C
No Heat
A10C
A15C
No Heat
A10C
A15C

—
1
2
—
1
2
—
2
2
—
2
2
—
2
2

No. of
Sequence
Steps
—
3.6/4.8
7.2/9.6
—
3.6/4.8
7.2/9.6
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

12.28/16.38
24.56/32.75

—
12.28/16.38
24.56/32.75

—
17.3/20.0
34.6/40.0
—
17.3/20.0
34.6/40.0
—
34.6/40.0
51.9/60.0
—
34.6/40.0
51.9/60.0
—
34.6/40.0
51.9/60.0

Rated
Heater
Heater
Heater kW
KBTU/Hr
Amp.
@ 208-240 V @ 208-240 V @ 208-240 V
19/19
41/44
62/69
22/22
43/47
65/72
24/24
68/74
89/99
33/33
77/83
98/108
37/37
80/87
102/112

Unit Min. Ckt.
Ampacity
@ 208-240 V
Min./Max.
@ 208 V
30/30
45/50
70/70
35/35
50/50
70/80
40/40
70/80
90/100
50/50
80/90
100/110
50/50
90/90
110/125

Min./Max.
@ 240 V
30/30
45/50
70/70
35/35
50/50
70/80
40/40
70/80
90/100
50/50
80/90
100/110
50/50
90/90
110/125

Over Current
Protective Device Size

Heat Pump

—
22/25
44/50
—
22/25
44/50
—
44/50
65/75
—
44/50
65/75
—
44/50
65/75

Min. Ckt.
Ampacity
208/240V
—
25/25
45/50
—
25/25
45/50
—
45/50
70/80
—
45/50
70/80
—
45/50
70/80

Max. Fuse
Size
208/240V

Heater Kit

19/19
—
—
22/22
—
—
24/24
—
—
33/33
—
—
37/37
—
—

Min. Circuit
Ampacity
208-240 V
Min./Max.
@ 208 V
30/30
—
—
35/35
—
—
40/40
—
—
50/50
—
—
50/50
—
—

—
3
3
—
3
3
—
3
3

—
3
3
—
3
3
—
3
3

No. of
Sequence
Steps
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

—
20.0/23.1
30.1/34.7
—
20.0/23.1
30.1/34.7
—
20.0/23.1
30.1/34.7

Rated
Heater
Heater
Heater kW
KBTU/Hr
Amp.
@ 208-240 V @ 208-240 V @ 208-240 V

Heater Kit

17/17
42/45
54/60
25/25
50/54
63/68
26/26
51/55
63/69

Unit Min. Ckt.
Ampacity
@ 208-240 V

Single Power Supply For Both Unit and Heater Kit

Min./Max.
@ 208 V
25/25
45/45
60/60
35/35
50/60
70/70
35/35
60/60
70/70

Min./Max.
@ 240 V
25/25
45/45
60/60
35/35
50/60
70/70
35/35
60/60
70/70

Over Current
Protective Device Size

Heat Pump

—
25/29
38/44
—
25/29
38/44
—
25/29
38/44

Min. Ckt.
Ampacity
208/240V

—
25/30
40/45
—
25/30
40/45
—
25/30
40/45

Max. Fuse
Size
208/240V

Heater Kit

17/17
—
—
25/25
—
—
26/26
—
—

Min. Circuit
Ampacity
208-240 V

Min./Max.
@ 208 V
25/25
—
—
35/35
—
—
35/35
—
—

Min./Max.
@ 240 V
25/25
—
—
35/35
—
—
35/35
—
—

Over Current
Protective Device Size

Heat Pump

Separate Power Supply For Both Unit and Heater Kit

Min./Max.
@ 240 V
30/30
—
—
35/35
—
—
40/40
—
—
50/50
—
—
50/50
—
—

Over Current
Protective Device Size

Heat Pump

Separate Power Supply For Both Unit and Heater Kit

208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION

—
1
2
—
1
2
—
2
3
—
2
3
—
2
3

RXQJNo. of
Heater Kit
Elements
Nominal kW

No Heat
A05J
A10J
No Heat
A05J
A10J
No Heat
A10J
A15J
No Heat
B10J
B15J
No Heat
B10J
B15J

RXQJNo. of
Heater Kit
Elements
Nominal kW

Heater Kit

Single Power Supply For Both Unit and Heater Kit

208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Air
Electric Heater Kits
RQNL Series

B048CK

B042CK

B036CK

Unit
Model
No.
RQPL-

B048JK

B042JK

B036JK

B030JK

B024JK
B025JK

Unit
Model
No.
RQPL-

No Heat
A10C
A15C
No Heat
A10C
A15C
No Heat
A10C
A15C

—
1
2
—
1
2
—
2
2
—
2
2
—
2
2

No. of
Sequence
Steps
—
3.6/4.8
7.2/9.6
—
3.6/4.8
7.2/9.6
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

12.28/16.38
24.56/32.75

—
12.28/16.38
24.56/32.75

—
17.3/20.0
34.6/40.0
—
17.3/20.0
34.6/40.0
—
34.6/40.0
51.9/60.0
—
34.6/40.0
51.9/60.0
—
34.6/40.0
51.9/60.0

Rated
Heater
Heater
Heater kW
KBTU/Hr
Amp.
@ 208-240 V @ 208-240 V @ 208-240 V
21/21
42/46
64/71
24/24
45/49
67/74
27/27
70/77
92/102
33/33
77/83
98/108
37/37
80/87
102/112

Unit Min. Ckt.
Ampacity
@ 208-240 V
Min./Max.
@ 208 V
30/30
50/50
70/80
35/35
50/50
70/80
40/40
70/80
100/110
50/50
80/90
100/110
50/50
90/90
110/125

Min./Max.
@ 240 V
30/30
50/50
70/80
35/35
50/50
70/80
40/40
70/80
100/110
50/50
80/90
100/110
50/50
90/90
110/125

Over Current
Protective Device Size

Heat Pump

—
22/25
44/50
—
22/25
44/50
—
44/50
65/75
—
44/50
65/75
—
44/50
65/75

Min. Ckt.
Ampacity
208/240V
—
25/25
45/50
—
25/25
45/50
—
45/50
70/80
—
45/50
70/80
—
45/50
70/80

Max. Fuse
Size
208/240V

Heater Kit

21/21
—
—
24/24
—
—
27/27
—
—
33/33
—
—
37/37
—
—

Min. Circuit
Ampacity
208-240 V
Min./Max.
@ 208 V
30/30
—
—
35/35
—
—
40/40
—
—
50/50
—
—
50/50
—
—

—
3
3
—
3
3
—
3
3

—
3
3
—
3
3
—
3
3

No. of
Sequence
Steps
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
—
7.2/9.6
10.8/14.4
24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

24.56/32.75
36.84/49.13

—
20.0/23.1
30.1/34.7
—
20.0/23.1
30.1/34.7
—
20.0/23.1
30.1/34.7

Rated
Heater
Heater
Heater kW
KBTU/Hr
Amp.
@ 208-240 V @ 208-240 V @ 208-240 V

Heater Kit

19/19
44/48
57/62
25/25
50/54
63/68
26/26
51/55
63/69

Unit Min. Ckt.
Ampacity
@ 208-240 V

Single Power Supply For Both Unit and Heater Kit

Min./Max.
@ 208 V
25/25
45/50
60/70
35/35
50/60
70/70
35/35
60/60
70/70

Min./Max.
@ 240 V
25/25
45/50
60/70
35/35
50/60
70/70
35/35
60/60
70/70

Over Current
Protective Device Size

Heat Pump

—
25/29
38/44
—
25/29
38/44
—
25/29
38/44

Min. Ckt.
Ampacity
208/240V

—
25/30
40/45
—
25/30
40/45
—
25/30
40/45

Max. Fuse
Size
208/240V

Heater Kit

19/19
—
—
25/25
—
—
26/26
—
—

Min. Circuit
Ampacity
208-240 V

Min./Max.
@ 208 V
25/25
—
—
35/35
—
—
35/35
—
—

Min./Max.
@ 240 V
25/25
—
—
35/35
—
—
35/35
—
—

Over Current
Protective Device Size

Heat Pump

Separate Power Supply For Both Unit and Heater Kit

Min./Max.
@ 240 V
30/30
—
—
35/35
—
—
40/40
—
—
50/50
—
—
50/50
—
—

Over Current
Protective Device Size

Heat Pump

Separate Power Supply For Both Unit and Heater Kit

208-240 VOLT, THREE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION

—
1
2
—
1
2
—
2
3
—
2
3
—
2
3

RXQJNo. of
Heater Kit
Elements
Nominal kW

No Heat
A05J
A10J
No Heat
A05J
A10J
No Heat
A10J
A15J
No Heat
B10J
B15J
No Heat
B10J
B15J

RXQJNo. of
Heater Kit
Elements
Nominal kW

Heater Kit

Single Power Supply For Both Unit and Heater Kit

208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION

Air
Electric Heater Kits
RQPL Series

31

Air

Dimensional Data
RQNL/RQPL Series

OUTDOOR FAN GRILLE
AND COMPRESSOR ACCESS

CONTROL
ACCESS PANEL

FILTER ACCESS
PANEL (FOR
UNIT MOUNTED
FILTER ACCESSORY)

LIQUID PRESSURE
SERVICE PORT

OUTDOOR COIL
PROTECTIVE GRILLE

30% 2%

SUCTION PRESSURE
SERVICE PORT

21% 2%

THREADED PVC CONDENSATE
DRAIN CONNECTION (3/4" [19.05 mm] N.P.T.)
THERMOSTAT WIRING
ENTRANCE

29% 2%

ELECTRICAL POWER
ENTRANCE

CORNER WEIGHTS
% OF TOTAL
UNIT WEIGHT

20% 2%

SIDE RETURN
DUCT OPENING
BLOWER/
EVAPORATOR
ACCESS PANEL

TOP VIEW

SIDE SUPPLY
DUCT OPENING

BOTTOM VIEW
451/16"
[1145 mm]
INSIDE

19

47 /32"
[1209 mm]

13/16"
[30 mm]
TYP.

11/2"
[38 mm]
TYP.

BOTTOM
RETURN
DUCT
OPENING
5013/16"
[1290 mm]

497/16"
[1256 mm]
INSIDE

BOTTOM
SUPPLY
DUCT
OPENING

141/4"
[362 mm]
TYP.

199/16"
[497 mm]

OUTDOOR FAN
GRILLE &
COMPRESSOR ACCESS

[ ] Designates Metric Conversions

32

313/16"
[97 mm]

45/16"
[95 mm]

153/8"
[391 mm]

33/16"
[97 mm]

Dimensional Data
RQNL/RQPL Series

Air

SIDE VIEW

SIDE VIEW
OUTDOOR
COIL PROTECTIVE
GRILLE

FILTER ACCESS PANEL (FOR UNIT
MOUNTED FILTER ACCESSORY)

THERMOSTAT
WIRE ENTRANCE

11/8"
[28.6 mm]

255/16"
[643 mm]

103/16"
[259 mm]
51/16"
[129 mm]

43/4"
[121 mm]

ELECTRICAL
POWER
ENTRANCE

527/16"
[1332 mm]

BLOWER/
EVAPORATOR
ACCESS PANEL

BACK VIEW

FRONT VIEW

CONTROL
ACCESS PANEL
47/8"
[124 mm]

SIDE SUPPLY
DUCT OPENING

LIQUID
PRESSURE
SERVICE PORT

133/4"
[349 mm]

75/16"
[186 mm]

57/16" [138 mm]
21/2" [63.5 mm]
81/2"
[216 mm]
TYP.

2211/16"
[576 mm]

47/16"
[113 mm]

471/2"
[1207 mm]

THREADED PVC
CONDENSATED DRAIN
CONNECTION (3/4 N.P.T.)

15"
[381 mm]

143/16"
[360 mm]
TYP.
191/8"
[486 mm]

SIDE RETURN
DUCT OPENING

SHOWN WITH DUCT COVERS REMOVED.
SUCTION PRESSURE
SERVICE PORT

IMPORTANT:
INSTALLATION MUST NOT
INTERFERE WITH DRAINAGE
OPENINGS IN BOTTOM OF
UNIT UNDER OUTDOOR COIL.

Model Number

Height “A”

B024, B025

3515/16

B030, B036,
B042, B048

41

IMPORTANT:
UNIT MUST BE LEVEL TO
PREVENT WATER MIGRATION.

[ ] Designates Metric Conversions

33

Air

Typical Installations
RQNL/RQPL Series

[ ] Designates Metric Conversions

34

Air

Accessories
RQNL/RQPL Series

ACCESSORY EQUIPMENT
Accessory
Description
Thermostats

Model
Application
RQNL-/RQPL-

Accessory
Model No.
See Thermostat Specification Sheet (T11-001)

Roofcurb

RQNL-/RQPL-

RXQG-AAA14 (14" [356 mm] Height)
RXQG-AAA24 (24" [610 mm] Height)

Supply & Return Diffusers

RQNL-/RQPL-

RXRN-BD15

Economizers (Downflow Only)

RQNL-/RQPL-

Economizers (Sideflow Only)

RQNL-/RQPL-

Fresh Air Damper

RQNL-/RQPL-

AXRF-FAB1 (Motorized-35%)
AXRF-FAA1 (Fixed-35%)

Rectangular to Round Transition (Downflow)

RQNL-/RQPL-

RXMC-CA02 (16" [406 mm] Ducts)
RXMC-CA03 (18" [457 mm] Ducts)

Filter Kit
High Pressure Control
Outdoor Thermostat

RQNL-/RQPLRQNL-/RQPLRQNL-/RQPL-

RXRY-B01
RXAB-D01
RXPT-A01

Low Amient Control

RQNL-/RQPL-

RXPZ-G01

Duct Adapter Sideflow Square to Round Transition
Lift Kit

RQNL-/RQPLRQNL-/RQPL-

AXMC-BA01
RXML-A01

AXRE-CAA30 (3 Position)
AXRD-CAM10 (Fully Modulating)
AXRD-CCM10 (Fully Modulating)
AXRE-CCA30 (3 Position)

COMMON SUPPLY/RETURN
CONCENTRIC AIR DIFFUSER

SUPPLY/RETURN DIFFUSER

NOTE: The location of the combination supply and return diffuser should
not exceed 10 feet [3.05 m] above the floor level for units @ 1000 CFM
[472 L/s] or less and 12 [3.66 m] to 14 feet [4.27 m] above the floor level
for units with CFM greater than 1000 [472 L/s]. If the diffuser is installed
with a greater distance than recommended above, the supply air may
become stratified above the required comfort area causing uncomfortable conditions.

AIRFLOW/PRESSURE DROP
INFORMATION (INCHES W.C. [kPa])
Designed to convert a side by side or an over and under arrangement into a concentric distribution of air. The diffuser is flush
mounted, completely insulated, assembled, and internally baffled
to provide four way supply air distribution with a center return. To
make the assembly complete and ready to fit into a 2' [0.61 m] x
4' [1.22 m] suspended ceiling grid, the diffuser includes
adjustable supply louvers, hanging rings, anti-sweat gasket, and
round flanges for use with flexible ducts.

Approximate CFM [L/s]-Supply Air
1300 [614] 1575 [743] 1800 [850] 2200 [1038]
Plenum & Supply/Return Duct .07 [.017] .10 [.024] .12 [.030] .17 [.042]
Diffuser
.09 [.022] .13 [.032] .16 [.040] .24 [.060]
Economizer
.06 [.015] .09 [.022] .11 [.027] .17 [.042]
Accessory

SUPPLY AIR/PERFORMANCE
Model No.
RXRNBD15

Diameter
Inches [mm]
16 [406]

Shipping Wt.
Lbs. [kg]
90 [40.82]

Dimension A
Inches [mm]
201/2 [521]

Diffuser Airflow CFM [L/s]
800 [378]-1200 [566]
1600 [755]-2000 [944]

Range of Throw Ft. [m]
14 [4.27]-16 [4.88]
18 [5.49]-28 [8.53]
[ ] Designates Metric Conversions

35

Air

Accessories
RQNL/RQPL Series

THERMOSTATS
200-Series *
Programmable

300-Series *
Deluxe
Programmable

400-Series *

Special Applications/
Programmable

* Photos are representative. Actual models may vary.

For detailed thermostat match-up information,
see specification sheet form number T11-001.

36

500-Series *

Communicating/
Programmable

Air

Accessories
RQNL/RQPL Series

DUCT ADAPTERS
RECTANGULAR TO ROUND
TRANSITIONS (DOWNFLOW)

RXMC-CA02

RXMC-CA03

[ ] Designates Metric Conversions

37

Air

Accessories
RQNL/RQPL Series

FRESH AIR DAMPER FOR USE ON
RQNL-/RQPL- SERIES
AXRF-FAA1 (Fixed - 0-35%)
The 0-35% manual outside Air Damper is designed to replace
the unit return air duct cover. No drilling or damper assembly is
required. The amount of outside air (0-35%) is controlled by simply adjusting the side damper.
AXRF-FAB1 (Motorized - 0-35%)
The 0-35% motorized outside Air Damper is designed to replace
the unit return air duct cover. No drilling or damper assembly is
required. The control motor opens the adjustable slide damper
when the unit blower motor is energized.

ECONOMIZERS
AXRE-CAA30 (3 Position) and
AXRD-CAM10 (Fully Modulating) for
RQNL-/RQPL- Series
Downflow Application
AXRE-CAA30 (3 Position)
Provided with enthalpy control, and
mixed air sensor. Settings include
fully open, fully closed and adjustable
mid point.
AXRD-CAM10 (Fully Modulating)
Provided with enthalpy control, mixed
air sensor and minimum position potentiometer for proportioning (modulating)
the amount of fresh air.

[ ] Designates Metric Conversions

38

Air

Accessories
RQNL/RQPL Series

ECONOMIZERS
AXRD-CCM10 (Fully Modulating) and
AXRE-CCA30 (3 Position)
Horizontal Application
AXRD-CCM10 (Fully Modulating)
Provided with enthalpy control, mixed
air sensor and minimum position potentiometer for proportioning (modulating)
the amount of fresh air.
AXRE-CCA30 (3-Position)
Has outdoor air sensor, minimum position
potentiometer, and mixed air sensor to
provide three damper positions.
[ ] Designates Metric Conversions

39

Air

Accessories
RQNL/RQPL Series

FILTER KIT INSTALLATION
RXRY-B01
For use in either vertical
or horizontal discharge.

Minimum
Airflow
510 [241]
680 [321]
850 [401]
1020 [481]
1190 [562]
1275 [602]
1700 [802]

CFM [L/s]
Nominal
Airflow
600 [283]
800 [378]
1000 [472]
1200 [566]
1400 [661]
1500 [708]
2000 [944]

[ ] Designates Metric Conversions

40

Maximum
Airflow
660 [311]
880 [415]
1100 [519]
1320 [623]
1540 [727]
1650 [779]
2200 [1039]

Airflow Pressure Drop, Inches W.C. [kPa]
CFM [L/s]
1" Filter
2" Filter
500 [236]
.02 [.0050]
.03 [.0075]
600 [283]
.02 [.0050]
.03 [.0075]
700 [330]
.03 [.0075]
.04 [.0010]
800 [378]
.04 [.0010]
.05 [.0124]
900 [425]
.05 [.0124]
.06 [.0149]
1000 [472]
.07 [.0174]
.08 [.0199]
1100 [519]
.08 [.0199]
.09 [.0224]
1200 [566]
.10 [.0249]
.12 [.0299]
1300 [614]
.13 [.0324]
.15 [.0373]
1400 [661]
.16 [.0398]
.19 [.0473]
1500 [708]
.19 [.0473]
.21 [.0523]
1600 [755]
.20 [.0498]
.23 [.0572]
1700 [802]
.21 [.0523]
.24 [.0598]
1800 [850]
.22 [.0548]
.25 [.0623]
1900 [897]
.24 [.0598]
.27 [.0672]
2000 [944]
.26 [.0647]
.29 [.0722]

Air

Accessories
RQNL/RQPL Series

DUCT ADAPTER SIDEFLOW
SQUARE TO ROUND TRANSITION
AXMC-BA01
Adapts the side rectangular supply and return openings to 14"
[356 mm] diameter round openings. Adapters provided with
same finish as unit and also provided with thermal insulation.
[ ] Designates Metric Conversions

41

Air

Accessories
RQNL/RQPL Series

Roofcurb (Sloped)
RXQG-AAA14 & RXQG-AAA24
for RQNL-/RQPL- Series

RXQG-AAA14
(14" [356 mm] High)

Note: Heat pump models must
use sloped curbs.
Hinged corners make
for fast, easy set-up.

RXQG-AAA24
(24" [610 mm] High)

Packaged Heat Pump
Roofcurb Installation (Sloped)
OUTDOOR FAN GRILLE�
AND COMPRESSOR ACCESS

OUTDOOR COIL�
PROTECTIVE GRILLE

5"�
[127 mm]

IMPORTANT: UNIT MUST BE LEVEL TO �
PREVENT WATER MIGRATION

LIQUID PRESSURE�
SERVICE PORT
SUCTION PRESSURE�
SERVICE PORT

207/8"
[530.2 mm]

THREADED PVC CONDENSATE�
DRAIN CONNECTION (3/4" [19.05 mm] N.P.T.)

CONTROL�
ACCESS PANEL

[ ] Designates Metric Conversions

42

Air

Accessories
RQNL/RQPL Series

ROOFCURB ADAPTERS
Fabricated from galvanized steel to adapt the New cabinet to the old style curb. All are furnished with a New gasket.
OLD MODEL PACKAGE
HEAT PUMP

OLD CURB MODEL

SMALL CABINET
(11/2-2 TON) [5.28-7.03 kW]
RPNCRPND-

20 SERIES

RXPA-CA20

MEDIUM CABINET
(21/2-3 TON) [8.79-10.55 kW]
RPNCRPND-

21 SERIES

RXPA-CA21

EXTRA LARGE CABINET
(31/2-5 TON) [12.31-17.58 kW]
RPNCRPND-

23 SERIES

RXPA-CA23

NEW MODEL TO OLD MODEL
ROOFCURB ADAPTER

NEW MODEL PACKAGE
HEAT PUMP

ONLY 1 CABINET SIZE—
ALL MODELS
RXPX-BACCA20
RXPX-BACCA21
RXPX-BCCCA23

RQNL-/
RQPL-

[ ] Designates Metric Conversions

43

Air

44

Wiring Diagrams
RQNL Series

Air

Wiring Diagrams
RQNL Series

45

Air

46

Wiring Diagrams
RQNL Series

Air

Wiring Diagrams
RQNL Series

47

Air

48

Wiring Diagrams
RQNL Series

Air

Limited Warranty
RQNL/RQPL Series

BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM
YOUR RETAILER.

GENERAL TERMS OF LIMITED WARRANTY*
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
periods stated, in accordance with the terms of the limited
warranty.
*For Complete Details of the Limited Warranty, Including Applicable
Terms and Conditions, See Your Local Installer or Contact the
Manufacturer for a Copy.

Conditional Parts (Registration Required)
1 Phase, Residential Applications ..................Ten (10) Years
Compressor
1 Phase, Residential Applications...................Ten (10) Years
1 & 3 Phase, Commercial Applications ...........Five (5) Years
Parts
1 & 3 Phase, Commercial Applications .............One (1) Year

49

Air

50

Notes
RQNL/RQPL Series

Air

Notes
RQNL/RQPL Series

51

The new degree of comfort.™

In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.
Rheem Heating, Cooling & Water Heating • P.O. Box 17010
Fort Smith, Arkansas 72917 • www.rheem.com

Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1
Brampton, Ontario • L6Y 0P5

PRINTED IN U.S.A 02/12 QG FORM NO. P11-791



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Create Date                     : 2012:02:20 16:42:58-06:00
Modify Date                     : 2012:02:24 16:47:51-06:00
Has XFA                         : No
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Metadata Date                   : 2012:02:24 16:47:51-06:00
Producer                        : Acrobat Distiller 9.5.0 (Macintosh)
Format                          : application/pdf
Title                           : untitled
Document ID                     : uuid:b372a69f-72be-f54e-ac5e-8cbd73879b22
Instance ID                     : uuid:029ccd5a-17a2-44a5-a98e-48160b7bb26d
Page Count                      : 52
EXIF Metadata provided by EXIF.tools

Navigation menu