Rixson Checkmate Series S 99 826, 926, 626, 726 Installation Instructions 80 9399 0102 015
User Manual: Rixson Checkmate Series - s 99-826, 99-926, 99-626, 99-726 Installation Instructions Installation Instructions
Open the PDF directly: View PDF .
Page Count: 4
Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. 80-9399-0102-015 (07-14)
ASSA ABLOY
RIXSON®
1
ASSA ABLOY
RIXSON®Installation Instructions
Door Holder and Releasing Device
WITH and WITHOUT
Integral Smoke Detector
An incorrectly installed or improperly
adjusted door closer can cause property
damage or personal injury. These instructions
should be followed to avoid the possibility
of misapplication or misadjustment.
CAUTION
®
Checkmate Series
99-626/99-826 (with detector)
99-726/99-926 (without detector)
Models
Hinge (Pull) Side of
Door Application
Stop (Push) Side of
Door Application
99-826
99-926
99-626
99-726
99-826 PULL SIDE
illustrated
RH – Right Hand Door
LHR – Left Hand Reverse
99-826 PULL SIDE
illustrated
LH – Left Hand Door
RHR – Right Hand Reverse
Components:
®
NOTES: - For wiring of 99-626/99-826 models, see "Checkmate "
"Wiring Instructions" No. 80-9399-0103-015 (07-14)
Push (Stop) Side
Pull (Hinge) Side
99-926 Hook-Up Box
99-826/99-926 Track
99-626/99-726 Track
99-726 Hook-Up Box
99-626 Hook-Up Box
Smoke
Detector
99-826 Hook-Up Box
Smoke
Detector
9/32” (7 mm);
3/8” (9.5 mm) dia. x
3/8” (9.5 mm) deep on
door opposite to closer
Standard
Optional
Through-bolts and
grommet-nuts
All
Preparation for Fasteners
Door or Frame
Fasteners Drill-Sizes
Self-Drilling Screw
Wood 3/16” (4.30 mm)
Pilot hole required
1/4” - 20 machine
screw Metal Drill: #7 (0.201” dia.)
Tap: 1/4” - 20
Sleeve nuts and
bolts
Hollow
Metal
9/32” (7 mm) through;
3/8” (9.5 mm) door face
opposite to closer
Aluminum
or Wood
3/8” (9.5 mm) through
Aluminum
or Metal No drill required
NOTE:
For special applications a separate door and frame
preparation template is packed with these instructions.
Use this instruction sheet for installation sequence and
closer adjustments only.
Use of an auxiliary door stop is always recommended.
Unit must be mounted on interior of building in dry
environment, maximum humidity of 95%.
See NFPA70 for wiring requirements and NFPA72 for alarm
system requirements.
99-726 PUSH SIDE
illustrated
RH – Right Hand Door
LHR – Left Hand Reverse
99-726 PUSHL SIDE
illustrated
LH – Left Hand Door
RHR – Right Hand Reverse
Hinge Edge of Door
Hinge Edge of Door
Adjusting
Rod
Arm Bracket
& Tube
Adjusting
Screw
Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. 80-9399-0102-015 (07-14)
ASSA ABLOY
RIXSON®
2
2
1
Parts
3
Hinge (Pull) Side Application
Right Hand Shown
Mark and Drill Holes
Installation Sequence
19
(483)
3-5/8
(92)
A
B
7-1/4
(184) 2-1/2
(64)
C
L
Power Track
99-926
99-826
31-1/16
(788)
34-11/16
(881)
Dim. "A”
32-1/8
(816)
35-3/4
(908)
Dim. "B”
Hold Open Angle
(Between 85° and 110° only)
A
Lock into
hold-open
C Open door to
desired angle
BD
Use holes
that align
in arms
7/8 (22) Conduit
hole for concealed
wiring only
1/2
(13)
99-826 / 99-926 Series
4
Self-Drilling
Screw Wood
(see Note)
No drill required
3-16” (4.3mm)
Drill #7 (.201” dia)
Tap 1/4”-20
Metal
Fasteners Door or
Frame Drill Sizes
Preparation for Fasteners
Note: Wood doors/frames MUST have pilot
hole when using Self-Drilling Screws.
1/4”-20
machine screw
Aluminum
or Metal
3/4
(19)
1-7/16
(37)
1-1/4
(32)
A
C
After installed,
bend out tabs
to secure.
D
See Page 4 for
wiring instructions.
2
1
F
G
B
E
Solenoid wire
coiled inside
end of track
Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. 80-9399-0102-015 (07-14)
ASSA ABLOY
RIXSON®
3
3
Parts
Stop (Push) Side Application
2
Mark and Drill Holes
Installation Sequence
A
D
E
Power Track
PTO
PTDO
30-9/16
(776)
34-3/16
(868)
Dim. "A”
31-11/16
(805)
35-5/16
(897)
Dim. "B”
F
See Page 4 for
wiring instructions.
B
C
99-626 / 99-726 Series
4
Hold Open Angle
(Between 85° and 110° only)
A
Lock into
hold-open
C Open door to
desired angle
BD
Use holes
that align
in arms
Self-Drilling
Screw Wood
(see Note)
No drill required
3-16” (4.3mm)
Drill #7 (.201” dia)
Tap 1/4”-20
Metal
Fasteners Door or
Frame Drill Sizes
Preparation for Fasteners
Note: Wood doors/frames MUST have pilot
hole when using Self-Drilling Screws.
1/4”-20
machine screw
Aluminum
or Metal
1
2
1
Left Hand Shown
12
(305)
3-1/8
(79)
A
B
C
L19
(486) 1
(25)
1-1/8 (29) hole
for Conduit
Bottom of Frame Stop
2-3/4
(70)
1/2
(13)
5-1/8
(130)
2-1/2
(64)
Solenoid wire
coiled inside
end of track
Copyright © 2009, 2014 Yale Security Inc., an ASSA ABLOY Group company. All rights reserved.
Reproduction in whole or in part without the express written permission of Yale Security Inc. is prohibited. 80-9399-0102-015 (07-14)
ASSA ABLOY
RIXSON®
4
3000 Highway 74 East • Monroe, NC 28112
Tel: (800)- 5670457-
www.r ixson.com
ASSA ABLOY
RIXSON®
99-726 / 99-926 Support Unit Wiring Diagram
(24VAC/DC Input)
99-726 / 99-926 Support Unit Wiring Diagram
(120VAC Input)
(Do not use a 120VAC 99-726 / 99-926 unit when power is
supplied from a 99-626 / 99-826 unit)
2-Pin Jumper SOL
1
2
3
4
3
2
1
24VAC/DC Circuit Board 4-Pin
Jumper
2-Pin Jumper SOL
1
2
3
4
3
2
1
120VAC Circuit Board 4-Pin
Jumper
Test Switch
Header for Solenoid
Connection
Openings for surface
wiring shown Fuse
125V / 1/2A
Terminal Strip for
Power Input Connection Test Switch
Openings for surface
or concealed wiring
Terminal Strip for
Power Input Connection
ELECTRICAL DATA
NOTES:
Maximum wire size is 14AWG.
All wiring and connections use standard wiring practice conforming with
local wiring codes.
For 99-626/99-826
Models:
Refer to Wiring Instructions
No. 80-9399-0103-015 (02-09)
for making wiring connections.
Earth
(+)
(-)
Earth
(+)
(-)
Input
Power
Input
Power
120VAC 24VAC 24VDC
Voltage
Current
120V 24V 24V
132V Max
102V Min
26.4V Max
20.4V Min
26.4V Max
20.4V Min
.036 Amps .059 Amps .074 Amps
Detector
26.4V Max
20.4V Min
0.034 Amps
24V
Header for Solenoid
Connection
Fuse
125V / 1/2A
Cont.:
increase the releasing force by turning the screw
accessible thru the end cap of the track using the
9/64” hex wrench provided.
Again, open door to the hold-open position.
Depress “Test Switch” button on the hook-up
board...door should close. If arm does not
release, see previous step.
IMPORTANT:
Remove solenoid wire from end of track before
installing track to frame. Do not pinch or crimp wire.
Once track and hook-up box are installed, solenoid
wire must be plugged into Header on circuit board
shown above.
After making all wiring connections:
Turn power to unit “ON”. (On Master (99-626 /
99-826) unit only, red LED should illuminate once
every 15 sec.).
Track’s hold open force is preset at the factory.
Open door to hold-open position. Manually pull
door out of hold-open and release...door should
close. If arm does not release from hold-open,