Robinair High Performance Vacuum Pump 15401 Users Manual

2015-02-06

: Robinair Robinair-High-Performance-Vacuum-Pump-15401-Users-Manual-524645 robinair-high-performance-vacuum-pump-15401-users-manual-524645 robinair pdf

Open the PDF directly: View PDF PDF.
Page Count: 8

DownloadRobinair Robinair-High-Performance-Vacuum-Pump-15401-Users-Manual-  Robinair-high-performance-vacuum-pump-15401-users-manual
Open PDF In BrowserView PDF
High Performance Vacuum Pump
Model 15401/15601/15603/15605
Operating Manual.......................................... 2

Bombas de Vacío de Alto Rendimiento
Modelo 15401/15601/15603
Manuel del Operador..................................... 8

Pompe à Vide à Haut Rendement

Modèle 15401/15601/15603
Manuel d’utilisation...................................... 16

Hochleistungs-Vakuumpumpe

Modelle 15401/15601/15603
Bedienungsanleitung................................... 24

Table of contents
Robinair® high performance
vacuum pumps......................................................2
Pump components................................................3
Warnings ..............................................................3
Before using your vacuum pump........................... 4
To use the gas ballast feature............................... 5
To shut down your pump after use........................ 5
To maintain your high vacuum pump..................... 5
	

Vacuum pump oil..............................................5

	

Cleaning your pump.........................................5

	

Operating Manual

	

Oil change procedure....................................... 5
Motor lubrication ..............................................5

Troubleshooting guide...........................................6
Failure to start.......................................................6
	
	

Oil leakage........................................................6
Failure to pull a good vacuum.......................... 6

Pump specifications..............................................6
Replacement parts................................................7
Warranty coverage................................................7
	

Out of warranty.................................................7

For use on A/C-R systems
using CFCs, HCFCs and HFCs
in conjunction with mineral oil,
ester oil, alkylbenzene oil and
PAG oil as lubricants. Not for
use with ammonia or lithium
bromide systems. Not for use
with flammable refrigerants.

Robinair® high performance
vacuum pumps
Congratulations on purchasing one of Robinair’s
top quality vacuum pumps. Your pump has been
engineered specifically for air conditioning and
refrigeration service, and is built with Robinair’s
proven offset rotary vane for fast, thorough
evacuation.
You’ll appreciate these key features . . .
Iso-ValveTM

Allows the pump to be shut off while still connected to
the A/C-R system, which is handy for checking rate
of rise. With the valve handle in the OPEN position,
the pump is open to the system being evacuated.
In the CLOSE position, the pump is isolated from
the system. This minimizes pump oil pulled into
the pumping module, making start-up easier and
reducing wear and tear on the pump components.
High vacuum rating

The two-stage, offset rotary vane design provides
powerful, quiet, high vacuum capability and ensures
moisture removal, while the high pumping capacity
reduces evacuation time.
Lifetime filtration

The intake filter prevents foreign matter from entering
the pumping chamber, and an internal exhaust filter
separates oil vapor from the exhaust flow.
Directed exhaust

The exhaust is expelled through the handle to direct it
away from the service technician.
Gas ballast

A precise amount of atmospheric air is introduced
into the pump, preventing condensation of moisture
vapor and helping maintain the purity of the pump oil.
By using the gas ballast, the pump operates more
efficiently and pump life is extended.
Sure-grip handle

The one-piece, molded handle makes it easy to carry
the pump to and from job sites, and the handle stays
cool to the touch during operation.
Compact design

The pump measures approximately 40 cm long, while
aluminum housing and offset rotary vanes keep the
pump weight low, making it easy to carry.

2

12

11

1
2
3
4

10

5

8
7

Pump Components	

	 1.	 Intake Fitting
	 2.	 Gas Ballast Valve	
  (located beside handle base)
	 3.	 Oil Fill Port
	 4.	 Sight Glass
	 5.	 Die-Cast Aluminum Housing
	 6.	 Oil Drain
	 7.	 Molded Polycarbonate Base
	 8.	 Iso-ValveTM
	 	   (isolates the pump from the system)
	 9.	 High Torque Motor
	10.	 Power Switch
	11.	 Through-the-Handle Exhaust
	12.	 Sure-Grip Handle

6

Warnings
Wear goggles when working with
refrigerants. Contact with refrigerants
may cause injury.

Incorrect use or connections may
cause electrical shock. Study and
follow the instructions carefully. and
take precautions to avoid electrical
shock hazards. All associated devices
must be grounded before energizing
circuits.
The normal operating temperature
will cause certain external portions of
the pump to be hot to the touch. Do
not touch the pump housing or motor
during operation.

Operating Manual

9

NOTICE: Airborne Noise Emissions

This equipment has been tested for airborne noise emission per
the Council Directive for Machinery (89/392/EEC) Section 1.7.4
Instructions — Essential Health and Safety Requirements.
Sound levels do not exceed 80dB(A) actual value.

116292  Rev. F  June 18, 2013

3

Before using your vacuum pump
In all cases, motors are designed for operating
voltages plus or minus 10% of the normal rating
(see SPECIFICATIONS).

Operating Manual

	 1.	 Verify the voltage and frequency at the outlet
match the specifications on the pump motor
decal. Verify the ON / OFF switch is in the
OFF position before you plug the pump
into an outlet. Verify the gas ballast valve is
closed. Remove and discard the exhaust plug
from the end of the pump’s handle.
	 2.	 The pump is shipped without oil in the
reservoir. Before starting the pump, fill with
oil. Remove the OIL FILL cap (black plastic
plug directly in front of the handle), and add
oil until the oil just shows in the bottom of the
sight glass. The approximate oil capacity of
the pump is 375 milliliters.

	 3.	 Replace the OIL FILL cap and remove the cap
from one of the inlet ports. Turn the Iso-Valve
to OPEN. Turn the motor switch ON. When
the pump runs smoothly, turn the Iso-Valve
to CLOSED and replace the cap on the inlet
port. This may take from two to 30 seconds,
depending on the ambient temperature. After
the pump runs for approximately one minute,
check the sight glass for correct oil level —
oil should be even with the sight glass OIL
LEVEL line. Add more oil if necessary.
When the pump is running, the oil level
should be even with the line on the sight
glass. Underfilling will result in poor vacuum
performance. Overfilling can result in oil
blowing from the exhaust.

Your pump is now ready to evacuate air
conditioning and refrigeration systems. Follow
normal service procedures and the A/C-R
manufacturer’s instructions for connections to the
system.

CAUTION! Before connecting the vacuum pump
to an A/C-R system, remove refrigerant from the
system in an accepted manner. Damage to the
pump may occur if evacuation is started while
the system is under high pressure. Robinair
recommends use of our Refrigerant Recovery
and Recycling equipment.
Wiring Instructions:

This vacuum pump features dual voltage ranges.
Before operating the pump, read and follow these
rewiring instructions (if necessary) to be sure your
pump is wired for the appropriate voltage.  
CAUTION! Unplug the unit before
beginning any service work. Incorrect
use or connections can cause electrical
shock. Only qualified personnel should
perform service work.
This vacuum pump is factory wired for a high
voltage range of 220 to 250 volts. To wire the
switch for a low voltage range of 110 volts to 115
volts, follow these steps:  

	 1.	 Disconnect the unit from the AC power source.
	 2.	 Loosen the screws on the plate at the rear of
the motor, and carefully move the plate aside
to clear the opening.
	 3.	 Disconnect the leads and reconnect for low
voltage, following the diagram and chart.
(High voltage connections are also shown if
you want to rewire in the future.)
	 4.	 Verify connections are secure and there
are no short circuits. Verify the grounding
connector is correctly connected.

	 5.	 Re-install the plate on the rear of motor with
the screws which were loosened in Step 2.
IMPORTANT: Check for short circuits using a
continuity tester before reconnecting to the AC
power source.

NOTE: EXTERNAL POWER LEADS ARE ALWAYS
CONNECTED TO TERMINALS 1 AND 4.

	
	
	
	
	

— EMERSON —
INTERNAL VOLTAGE CONNECTION
MOTOR	
LOW	
HIGH
LEAD	
VOLTAGE	
VOLTAGE
BROWN	
3	
6
WHITE	
4	
3
BLACK	
2	
3
INST0350

4

General Electric Motors

Emerson Motors

To maintain the high vacuum
pump

Moisture from the A/C-R system that is carried
into the pump as a vapor tends to condense into
a liquid and combine with the vacuum pump oil.
When moisture contaminates the pump oil, it
reduces the pump’s ability to reach its ultimate
deep vacuum level.

For maximum performance, Robinair recommends
changing vacuum pump oil after each use.
Vacuum pump oil
The condition and type of oil used in any high vacuum
pump are extremely important in determining the
ultimate attainable vacuum. Robinair recommends
the use of our Premium High Vacuum Pump Oil.
This oil has been specifically blended to maintain
maximum viscosity at normal running temperatures
and to improve cold weather starts.
Our Premium High Vacuum Pump Oil is available
in quart or gallon containers. Order by part
number:
	13203 — Quart (shipped 12 quarts per case)
	13204 — Gallon (shipped 4 gallons per case)
Oil change procedure
	 1.	 Be sure the pump is warmed up.
	 2.	 Remove the OIL DRAIN cap. Drain
contaminated oil into a suitable container and
dispose of correctly. Oil can be forced from
the pump by opening the inlet and partially
blocking the exhaust with a cloth while the
pump is running. Do not operate the pump for
more than 20 seconds using this method.
	 3.	 When the flow of oil has stopped, tilt the
pump forward to drain residual oil.
	 4.	 Replace the OIL DRAIN cap. Remove the
OIL FILL cap, and fill the reservoir with new
vacuum pump oil until the oil just shows at the
bottom of the sight glass. The approximate oil
capacity of the pump is 375 milliliters.
	 5.	 Verify the inlet ports are capped. Turn ON
the pump, and allow it to run for one minute.
Check the oil level. If the oil is below the sight
glass OIL LEVEL line, add oil slowly (with the
pump running) until the oil reaches the OIL
LEVEL line. Replace the OIL FILL cap, cap
the inlet, and tighten the drain cap.
	 6.	 If the oil is badly contaminated, you may need
to flush the pump. To flush, remove the pump
drain cap and start the pump. Slowly pour a
small quantity of new pump oil through the oil
fill inlet.
Repeat this procedure as required until the
contamination is removed. Replace the OIL
DRAIN cap and refill the reservoir to the
correct level using fresh pump oil (Step 4).
Cleaning the pump
Use only soap and water to clean the
pump. Do not use commercial cleaners that
contain degreasing agents that can damage
polycarbonates. The pump handle and base are
made of Lexan, one of the toughest polycarbonate
plastics available. However, it is sensitive to
degreasing agents.
*Lexan is a registered trademark of General
Electric
Motor lubrication
After three years of normal service or one year
of heavy-duty service, add motor oil. Use electric
motor oil or SAE 10 oil.

The gas ballast valve purges a small amount of
atmospheric air through the exhaust chamber.
This extra volume of air mixes with the vapor from
the refrigerant system to prevent condensation
and to help exhaust moisture in the form of vapor
from the pump.

To use the gas ballast, start the pump and open
the gas ballast valve until the system has reached
approximately 1000‑3000 microns. Close the
valve to allow the pump to pull down to its ultimate
vacuum level. (The gas ballast valve is located
beside the handle, opposite the inlet fitting.)
The gas ballast valve may be opened or closed at
any time during pump operation. It is fully open at
two turns counterclockwise.
NOTE: Robinair recommends the use of a
thermistor vacuum gauge to most accurately
measure vacuum levels.

To shut down the
pump after use
To help prolong pump life and promote easy starting, follow these procedures for shutdown:
	 1.	 Close the manifold valve between the pump
and the system.
	 2.	 Turn the Iso-Valve to the CLOSED position.
	 3.	 Remove the hose from the pump inlet.

	 4.	 Turn the pump power switch to OFF, then
return the Iso-Valve to the OPEN position for
a few seconds to relieve any vacuum inside
the pump.
	 5.	 Cap the inlet port to prevent any contamination or loose particles from entering the port.

Operating Manual

To use the gas
ballast feature

5

Troubleshooting guide

Pump Specifications

This pump has been designed for dependable
use and long life. If something should go wrong,
however, the following guide will help you get the
pump back into service as quickly as possible.

Frequency Range..................................... 50-60 Hz

If disassembly of the pump is required, please
check your warranty. The warranty may be voided
by misuse or customer tampering that results in
the pump being inoperable.

Operating Manual

Failure to start

Check line voltage. Robinair pumps are designed
to start at +10% line voltage (loaded) at 0oC. At
extremes, however, switching between the start
and run windings may occur. When starting the
pump in cold temperatures, verify the Iso-Valve
and inlet port are open to free air.
Oil leakage

	 1.	 Verify the oil is not a residual accumulation
from spillage, etc.

	 2.	 If leakage exists, the module cover gasket
or the shaft seal may need replacing.
Follow the instructions supplied with the
seal replacement kit, part number 15367. If
leakage exists in the area of the drain plug,
reseal the plug using a commercial pipe
thread sealer.
Failure to pull a good vacuum

	 1.	 Verify the Iso-Valve on the pump is in the
OPEN position, and the gas ballast knob is
tightly sealed.

	 2.	 Verify the vacuum gauge and all connections
are in good conditon and leak-free. Confirm
leakage by monitoring the vacuum with a
thermistor gauge while applying vacuum
pump oil at connections or suspected leak
points. Vacuum will improve briefly while the
oil is sealing the leak.
	 3.	 Be sure the pump oil is clean. A badly
contaminated pump may require several oil
flushes. See OIL CHANGE PROCEDURE.

	 4.	 Verify the oil is at the correct level. For
maximum pump operation, the oil must be
even with the OIL LEVEL line on the sight
glass when the pump is running. See OIL
CHANGE PROCEDURE. Do not overfill.
Operating temperatures cause the oil to
expand, so it will appear at a higher level than
when the pump is not running. To check the
oil level, start the pump with the inlet capped.
Check the oil level in the sight glass. Add oil if
necessary.

Model 15401

Free Air Displacement..........................4 cfm/60 Hz
	 . ................................................. 94 l/m @ 50 Hz
	 . ............................................... 113 l/m @ 60 Hz
Stages...................................................................2
Motor Speed..............................1425 rpm @ 50 Hz
	 . ............................................1725 rpm @ 60 Hz

Voltage Range.......................................110V–115V
	 . ....................................................... 220V–250V
Factory Micron Rating........................... 15 microns

Approximate Oil Capacity............................. 400 ml

Weight............................................................ 13 kg

Width........................................................ 14.29 cm

Height......................................................... 24.6 cm
Length........................................................... 40 cm

Intake..................................... 1/4" and 1/2" SAE MFL
Min. Starting Temp. (at 90% voltage)................ 0oC

Motor Size............. 0.25kW (1/3 HP) Capacitor Start

Operating Temp............................................... 68oC
Models 15601/15603/15605

Frequency Range..................................... 50-60 Hz

Free Air Displacement..........................6 cfm/60 Hz
	 . ............................................... 142 l/m @ 50 Hz
	 . ............................................... 170 l/m @ 60 Hz
Stages...................................................................2
Motor Speed..............................1425 rpm @ 50 Hz
	 . ............................................1725 rpm @ 60 Hz

Voltage Range.......................................110V–115V
	 . ....................................................... 220V–250V
Factory Micron Rating........................... 15 microns

Approximate Oil Capacity............................. 400 ml

Weight............................................................ 13 kg

Width........................................................ 14.29 cm

Height......................................................... 24.6 cm
Length........................................................... 42 cm

Intake..............................1/4", 3/8", and 1/2" SAE MFL
Min. Starting Temp. (at 90% voltage)................ 0oC
Motor Size............ 0.25 kW (1/3 HP) Capacitor Start

Operating Temp............................................... 68oC

Notes:
	 1.	 All motors are internally protected (automatic
reset).
	 2.	 Operating temperatures are typical for normal
operating conditions.
	 3.	 Model 15603 has a bipolar side grounded plug.
	 4.	 Models 15405 & 15605 have Australian plugs.
Because of ongoing product improvements, we reserve the right to
change design, specifications, or materials without notice.

6

11

12

9
9

8
9

7
13

6
14

5

4

15

INST0026

17

2

1

Replacement parts

Warranty coverage

			 15605/
			 15601/
Part	
Item	 15401	 15603

Robinair vacuum pumps are warranted against
defects in material and workmanship for one year
of normal use from the date of purchase. See your
distributor for warranty details.

Oil Drain Cap (6)	

Oil Drain Kit	
(includes Item No. 1)	

1	

40572	 40572

2	

13193	 13193

Module Cover Kit	
(includes Nos. 2, 4, and 5)	 3	
Oil Fill Cap 	
(includes No. 7)	
Intake Fitting	
(includes No. 9)	

Intake Cap (1 ea.)
1/4", 3/8", 1/2" SAE MFL	
Vent Bolt 	
(includes o-rings)	

15337	 15337

4	

15371	 15371

8	

15364	 555124

9	

555133	 555133

Handle, Power Cord	
and Switch Assembly	

11	

15338	 15338

12	

15466	 15466

Coupling	

14	

13192	 13192

Motor	

Iso-Valve

TM

Assembly	

Base and Foot Assembly	

13	
15	

16	

Pump Assembly, less motor	
(includes No. 3 and 6)	
17	
Seal Replacement Kit	
(not shown)	

	
--	

Out of warranty

A pump which is no longer covered by the oneyear warranty period and which fails to operate
properly should be returned to the distributor
with a full written explanation of the problem. The
distributor may suggest returning the pump to the
factory. Before returning an out-of-warranty pump,
review all maintenance procedures to avoid an unnecessary return. Replacement parts are available
for doing your own service.

Operating Manual

16

3

15465	 15465
15368	 15368

15369	 15369

15547	 15548
15367	 15367

7

%

Call our Toll-Free
Technical Support Line at

800-822-5561

in the continental U.S. and Canada
or visit our website
www.robinair.com

In all other locations, contact your local distributor. To help us serve you better,
be prepared to provide the model number, serial number, and date of purchase of
your unit.
To validate your warranty, complete the warranty card attached to your unit and
return it within ten days from date of purchase.

NATIONWIDE NETWORK OF AUTHORIZED SERVICE CENTERS

If your unit needs repairs or replacement parts, contact the service center in your
area. For help in locating a service center, call the toll-free technical support line,
or visit our website.
Due to ongoing product improvements, we reserve the right
to change design, specifications, and materials without notice.

BOSCH AUTOMOTIVE SERVICE SOLUTIONS
655 EISENHOWER DRIVE
OWATONNA, MN 55060 USA
TECHNICAL SERVICES: 1-800-822-5561
FAX: 1-866-259-1241
CUSTOMER SERVICE: 1-800-533-6127
FAX: 1-800-283-8665
WEB SITE: WWW.ROBINAIR.COM

116292 Rev. F June 18, 2013	

© Bosch Automotive Service Solutions



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : Yes
Create Date                     : 2013:06:24 14:47:47-05:00
Creator                         : Adobe InDesign CS4 (6.0.6)
Modify Date                     : 2013:06:24 14:59:33-05:00
Has XFA                         : No
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Instance ID                     : uuid:3683d3d9-7bf7-f74a-b350-2fcac9fe77dd
Document ID                     : adobe:docid:indd:6c8b6574-2f71-11e0-ada9-c5fc1a5081f7
Original Document ID            : adobe:docid:indd:6c8b6574-2f71-11e0-ada9-c5fc1a5081f7
Rendition Class                 : proof:pdf
Derived From Instance ID        : cf3c9696-2ede-11e0-ad70-8c1dc69d6431
Derived From Document ID        : adobe:docid:indd:78f691bf-2ece-11e0-ad70-8c1dc69d6431
History Action                  : saved, saved, saved, saved
History Instance ID             : xmp.iid:078011740720681197A5E6713C9C2685, xmp.iid:088011740720681197A5E6713C9C2685, xmp.iid:098011740720681197A5E6713C9C2685, xmp.iid:FA7F117407206811AFFDE6DFECD39CCC
History When                    : 2013:06:18 09:29:28-05:00, 2013:06:18 09:29:28-05:00, 2013:06:18 09:44:45-05:00, 2013:06:24 14:42:57-05:00
History Software Agent          : Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0, Adobe InDesign 6.0
History Changed                 : /, /metadata, /, /
Manifest Link Form              : ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream, ReferenceStream
Manifest Placed X Resolution    : 600.00, 600.00, 600.00, 600.00, 600.00, 600.00, 600.00, 600.00
Manifest Placed Y Resolution    : 600.00, 600.00, 600.00, 600.00, 600.00, 600.00, 600.00, 600.00
Manifest Placed Resolution Unit : Inches, Inches, Inches, Inches, Inches, Inches, Inches, Inches
Manifest Reference Instance ID  : uuid:8EE1A1BBE1D5DE119532DCE6D7248607, uuid:A562FF4BEBD4DE119AE989F4C439B092, uuid:8EE1A1BBE1D5DE119532DCE6D7248607, uuid:A562FF4BEBD4DE119AE989F4C439B092, uuid:8EE1A1BBE1D5DE119532DCE6D7248607, uuid:A562FF4BEBD4DE119AE989F4C439B092, uuid:8EE1A1BBE1D5DE119532DCE6D7248607, uuid:A562FF4BEBD4DE119AE989F4C439B092
Manifest Reference Document ID  : uuid:8DE1A1BBE1D5DE119532DCE6D7248607, uuid:A462FF4BEBD4DE119AE989F4C439B092, uuid:8DE1A1BBE1D5DE119532DCE6D7248607, uuid:A462FF4BEBD4DE119AE989F4C439B092, uuid:8DE1A1BBE1D5DE119532DCE6D7248607, uuid:A462FF4BEBD4DE119AE989F4C439B092, uuid:8DE1A1BBE1D5DE119532DCE6D7248607, uuid:A462FF4BEBD4DE119AE989F4C439B092
Metadata Date                   : 2013:06:24 14:59:33-05:00
Creator Tool                    : Adobe InDesign CS4 (6.0.6)
Thumbnail Format                : JPEG
Thumbnail Width                 : 256
Thumbnail Height                : 256
Thumbnail Image                 : (Binary data 12259 bytes, use -b option to extract)
Doc Change Count                : 92
Format                          : application/pdf
Producer                        : Adobe PDF Library 9.0
Trapped                         : False
Page Count                      : 8
EXIF Metadata provided by EXIF.tools

Navigation menu