High Performance Vacuum Pump
Model 15401/15601/15603/15605
Operating Manual .........................................2
Bombas de Vacío de Alto Rendimiento
Modelo 15401/15601/15603
Manuel del Operador ....................................8
Pompe à Vide à Haut Rendement
Modèle 15401/15601/15603
Manuel d’utilisation .....................................16
Hochleistungs-Vakuumpumpe
Modelle 15401/15601/15603
Bedienungsanleitung ..................................24
Table of contents
Robinair® high performance
vacuum pumps .....................................................2
Pump components................................................3
Warnings .............................................................3
Before using your vacuum pump ..........................4
To use the gas ballast feature...............................5
To shut down your pump after use .......................5
To maintain your high vacuum pump ....................5
Vacuum pump oil .............................................5
Oil change procedure ......................................5
Cleaning your pump.........................................5
Motor lubrication .............................................5
Troubleshooting guide ..........................................6
Failure to start.......................................................6
Oil leakage .......................................................6
Failure to pull a good vacuum..........................6
Pump specications..............................................6
Replacement parts ...............................................7
Warranty coverage ...............................................7
Out of warranty ................................................7
Operating Manual
2
Robinair® high performance
vacuum pumps
Congratulations on purchasing one of Robinair’s
top quality vacuum pumps. Your pump has been
engineered specically for air conditioning and
refrigeration service, and is built with Robinair’s
proven offset rotary vane for fast, thorough
evacuation.
You’ll appreciate these key features . . .
Iso-ValveTM
Allows the pump to be shut off while still connected to
the A/C-R system, which is handy for checking rate
of rise. With the valve handle in the OPEN position,
the pump is open to the system being evacuated.
In the CLOSE position, the pump is isolated from
the system. This minimizes pump oil pulled into
the pumping module, making start-up easier and
reducing wear and tear on the pump components.
High vacuum rating
The two-stage, offset rotary vane design provides
powerful, quiet, high vacuum capability and ensures
moisture removal, while the high pumping capacity
reduces evacuation time.
Lifetime ltration
The intake lter prevents foreign matter from entering
the pumping chamber, and an internal exhaust lter
separates oil vapor from the exhaust ow.
Directed exhaust
The exhaust is expelled through the handle to direct it
away from the service technician.
Gas ballast
A precise amount of atmospheric air is introduced
into the pump, preventing condensation of moisture
vapor and helping maintain the purity of the pump oil.
By using the gas ballast, the pump operates more
efciently and pump life is extended.
Sure-grip handle
The one-piece, molded handle makes it easy to carry
the pump to and from job sites, and the handle stays
cool to the touch during operation.
Compact design
The pump measures approximately 40 cm long, while
aluminum housing and offset rotary vanes keep the
pump weight low, making it easy to carry.
For use on A/C-R systems
using CFCs, HCFCs and HFCs
in conjunction with mineral oil,
ester oil, alkylbenzene oil and
PAG oil as lubricants. Not for
use with ammonia or lithium
bromide systems. Not for use
with ammable refrigerants.
Operating Manual
3
Pump Components
1.IntakeFitting
2.GasBallastValve
(locatedbesidehandlebase)
3.OilFillPort
4.SightGlass
5.Die-CastAluminumHousing
6.OilDrain
7.MoldedPolycarbonateBase
8.Iso-ValveTM
(isolatesthepumpfromthesystem)
9.HighTorqueMotor
10.PowerSwitch
11.Through-the-HandleExhaust
12.Sure-GripHandle
Warnings
Wear goggles when working with
refrigerants. Contact with refrigerants
may cause injury.
Incorrect use or connections may
cause electrical shock. Study and
follow the instructions carefully. and
take precautions to avoid electrical
shock hazards. All associated devices
must be grounded before energizing
circuits.
The normal operating temperature
will cause certain external portions of
the pump to be hot to the touch. Do
not touch the pump housing or motor
during operation.
NOTICE: Airborne Noise Emissions
This equipment has been tested for airborne noise emission per
the Council Directive for Machinery (89/392/EEC) Section 1.7.4
Instructions — Essential Health and Safety Requirements.
Sound levels do not exceed 80dB(A) actual value.
1
2
3
4
5
6
7
8
9
10
11
12
116292Rev.FJune18,2013
Inallcases,motorsaredesignedforoperating
voltagesplusorminus10%ofthenormalrating
(seeSPECIFICATIONS).
1.Verifythevoltageandfrequencyattheoutlet
matchthespecicationsonthepumpmotor
decal.VerifytheON/OFFswitchisinthe
OFFpositionbeforeyouplugthepump
intoanoutlet.Verifythegasballastvalveis
closed.Removeanddiscardtheexhaustplug
fromtheendofthepump’shandle.
2.Thepumpisshippedwithoutoilinthe
reservoir.Beforestartingthepump,llwith
oil.RemovetheOILFILLcap(blackplastic
plugdirectlyinfrontofthehandle),andadd
oiluntiltheoiljustshowsinthebottomofthe
sightglass.Theapproximateoilcapacityof
thepumpis375milliliters.
3.ReplacetheOILFILLcapandremovethecap
fromoneoftheinletports.TurntheIso-Valve
toOPEN.TurnthemotorswitchON.When
thepumprunssmoothly,turntheIso-Valve
toCLOSEDandreplacethecapontheinlet
port.Thismaytakefromtwoto30seconds,
dependingontheambienttemperature.After
thepumprunsforapproximatelyoneminute,
checkthesightglassforcorrectoillevel—
oilshouldbeevenwiththesightglassOIL
LEVELline.Addmoreoilifnecessary.
Whenthepumpisrunning,theoillevel
shouldbeevenwiththelineonthesight
glass.Underllingwillresultinpoorvacuum
performance.Overllingcanresultinoil
blowingfromtheexhaust.
Yourpumpisnowreadytoevacuateair
conditioningandrefrigerationsystems.Follow
normalserviceproceduresandtheA/C-R
manufacturer’sinstructionsforconnectionstothe
system.
Before using your vacuum pump
Operating Manual
4
Emerson MotorsGeneral Electric Motors
CAUTION! Before connecting the vacuum pump
to an A/C-R system, remove refrigerant from the
system in an accepted manner. Damage to the
pump may occur if evacuation is started while
the system is under high pressure. Robinair
recommends use of our Refrigerant Recovery
and Recycling equipment.
Wiring Instructions:
Thisvacuumpumpfeaturesdualvoltageranges.
Beforeoperatingthepump,readandfollowthese
rewiringinstructions(ifnecessary)tobesureyour
pumpiswiredfortheappropriatevoltage.
CAUTION! Unplug the unit before
beginning any service work. Incorrect
use or connections can cause electrical
shock. Only qualied personnel should
perform service work.
Thisvacuumpumpisfactorywiredforahigh
voltagerangeof220to250volts.Towirethe
switchforalowvoltagerangeof110voltsto115
volts,followthesesteps:
1.
DisconnecttheunitfromtheACpowersource.
2.Loosenthescrewsontheplateattherearof
themotor,andcarefullymovetheplateaside
tocleartheopening.
3.Disconnecttheleadsandreconnectforlow
voltage,followingthediagramandchart.
(Highvoltageconnectionsarealsoshownif
youwanttorewireinthefuture.)
4.Verifyconnectionsaresecureandthere
arenoshortcircuits.Verifythegrounding
connectoriscorrectlyconnected.
5.Re-installtheplateontherearofmotorwith
thescrewswhichwereloosenedinStep2.
IMPORTANT: Checkforshortcircuitsusinga
continuitytesterbeforereconnectingtotheAC
powersource.
— EMERSON —
INTERNAL VOLTAGE CONNECTION
MOTOR LOW HIGH
LEAD VOLTAGE VOLTAGE
BROWN 3 6
WHITE 4 3
BLACK 2 3
INST0350
NOTE: EXTERNAL POWER LEADS ARE ALWAYS
CONNECTED TO TERMINALS 1 AND 4.
Operating Manual
To use the gas
ballast feature
MoisturefromtheA/C-Rsystemthatiscarried
intothepumpasavaportendstocondenseinto
aliquidandcombinewiththevacuumpumpoil.
Whenmoisturecontaminatesthepumpoil,it
reducesthepump’sabilitytoreachitsultimate
deepvacuumlevel.
Thegasballastvalvepurgesasmallamountof
atmosphericairthroughtheexhaustchamber.
Thisextravolumeofairmixeswiththevaporfrom
therefrigerantsystemtopreventcondensation
andtohelpexhaustmoistureintheformofvapor
fromthepump.
Tousethegasballast,startthepumpandopen
thegasballastvalveuntilthesystemhasreached
approximately1000-3000microns.Closethe
valvetoallowthepumptopulldowntoitsultimate
vacuumlevel.(Thegasballastvalveislocated
besidethehandle,oppositetheinlettting.)
Thegasballastvalvemaybeopenedorclosedat
anytimeduringpumpoperation.Itisfullyopenat
twoturnscounterclockwise.
NOTE: Robinair recommends the use of a
thermistor vacuum gauge to most accurately
measure vacuum levels.
5
To maintain the high vacuum
pump
Formaximumperformance,Robinairrecommends
changingvacuumpumpoilaftereachuse.
Vacuum pump oil
Theconditionandtypeofoilusedinanyhighvacuum
pump are extremely important in determining the
ultimateattainablevacuum.Robinairrecommends
the use of our Premium High Vacuum Pump Oil.
Thisoilhasbeenspecicallyblendedtomaintain
maximumviscosityatnormalrunningtemperatures
andtoimprovecoldweatherstarts.
OurPremiumHighVacuumPumpOilisavailable
inquartorgalloncontainers.Orderbypart
number:
13203—Quart(shipped12quartspercase)
13204—Gallon(shipped4gallonspercase)
Oil change procedure
1.Besurethepumpiswarmedup.
2.RemovetheOILDRAINcap.Drain
contaminatedoilintoasuitablecontainerand
disposeofcorrectly.Oilcanbeforcedfrom
thepumpbyopeningtheinletandpartially
blockingtheexhaustwithaclothwhilethe
pumpisrunning.Donotoperatethepumpfor
morethan20secondsusingthismethod.
3.Whentheowofoilhasstopped,tiltthe
pumpforwardtodrainresidualoil.
4.ReplacetheOILDRAINcap.Removethe
OILFILLcap,andllthereservoirwithnew
vacuumpumpoiluntiltheoiljustshowsatthe
bottomofthesightglass.Theapproximateoil
capacityofthepumpis375milliliters.
5.Verifytheinletportsarecapped.TurnON
thepump,andallowittorunforoneminute.
Checktheoillevel.Iftheoilisbelowthesight
glassOILLEVELline,addoilslowly(withthe
pumprunning)untiltheoilreachestheOIL
LEVELline.ReplacetheOILFILLcap,cap
theinlet,andtightenthedraincap.
6.Iftheoilisbadlycontaminated,youmayneed
toushthepump.Toush,removethepump
draincapandstartthepump.Slowlypoura
smallquantityofnewpumpoilthroughtheoil
llinlet.
Repeatthisprocedureasrequireduntilthe
contaminationisremoved.ReplacetheOIL
DRAINcapandrellthereservoirtothe
correctlevelusingfreshpumpoil(Step4).
Cleaning the pump
Useonlysoapandwatertocleanthe
pump.Donotusecommercialcleanersthat
containdegreasingagentsthatcandamage
polycarbonates.Thepumphandleandbaseare
madeofLexan,oneofthetoughestpolycarbonate
plasticsavailable.However,itissensitiveto
degreasingagents.
*Lexan is a registered trademark of General
Electric
Motor lubrication
Afterthreeyearsofnormalserviceoroneyear
ofheavy-dutyservice,addmotoroil.Useelectric
motoroilorSAE10oil.
To shut down the
pump after use
Tohelpprolongpumplifeandpromoteeasystart-
ing,followtheseproceduresforshutdown:
1.Closethemanifoldvalvebetweenthepump
andthesystem.
2.TurntheIso-ValvetotheCLOSEDposition.
3.Removethehosefromthepumpinlet.
4.TurnthepumppowerswitchtoOFF,then
returntheIso-ValvetotheOPENpositionfor
afewsecondstorelieveanyvacuuminside
thepump.
5.Captheinletporttopreventanycontamina-
tionorlooseparticlesfromenteringtheport.
Troubleshooting guide
Thispumphasbeendesignedfordependable
useandlonglife.Ifsomethingshouldgowrong,
however,thefollowingguidewillhelpyougetthe
pumpbackintoserviceasquicklyaspossible.
Ifdisassemblyofthepumpisrequired,please
checkyourwarranty.Thewarrantymaybevoided
bymisuseorcustomertamperingthatresultsin
thepumpbeinginoperable.
Failure to start
Checklinevoltage.Robinairpumpsaredesigned
tostartat+10%linevoltage(loaded)at0oC.At
extremes,however,switchingbetweenthestart
andrunwindingsmayoccur.Whenstartingthe
pumpincoldtemperatures,verifytheIso-Valve
andinletportareopentofreeair.
Oilleakage
1.Verifytheoilisnotaresidualaccumulation
fromspillage,etc.
2.Ifleakageexists,themodulecovergasket
ortheshaftsealmayneedreplacing.
Followtheinstructionssuppliedwiththe
sealreplacementkit,partnumber15367.If
leakageexistsintheareaofthedrainplug,
resealtheplugusingacommercialpipe
threadsealer.
Failure to pull a good vacuum
1.VerifytheIso-Valveonthepumpisinthe
OPENposition,andthegasballastknobis
tightlysealed.
2.Verifythevacuumgaugeandallconnections
areingoodconditonandleak-free.Conrm
leakagebymonitoringthevacuumwitha
thermistorgaugewhileapplyingvacuum
pumpoilatconnectionsorsuspectedleak
points.Vacuumwillimprovebrieywhilethe
oilissealingtheleak.
3.Besurethepumpoilisclean.Abadly
contaminatedpumpmayrequireseveraloil
ushes.SeeOILCHANGEPROCEDURE.
4.Verifytheoilisatthecorrectlevel.For
maximumpumpoperation,theoilmustbe
evenwiththeOILLEVELlineonthesight
glasswhenthepumpisrunning.SeeOIL
CHANGEPROCEDURE.Donotoverll.
Operatingtemperaturescausetheoilto
expand,soitwillappearatahigherlevelthan
whenthepumpisnotrunning.Tocheckthe
oillevel,startthepumpwiththeinletcapped.
Checktheoillevelinthesightglass.Addoilif
necessary.
Pump Specications
Model 15401
FrequencyRange.................................... 50-60Hz
FreeAirDisplacement.........................4cfm/60Hz
..................................................94l/m@50Hz
................................................ 113l/m@60Hz
Stages..................................................................2
MotorSpeed.............................1425rpm@50Hz
.............................................1725rpm@60Hz
VoltageRange......................................110V–115V
........................................................ 220V–250V
FactoryMicronRating.......................... 15microns
ApproximateOilCapacity............................ 400ml
Weight........................................................... 13kg
Width....................................................... 14.29cm
Height........................................................ 24.6cm
Length........................................................... 40cm
Intake.................................... 1/4"and1/2"SAEMFL
Min.StartingTemp.(at90%voltage)............... 0oC
MotorSize............0.25kW(1/3HP)CapacitorStart
OperatingTemp.............................................. 68oC
Models 15601/15603/15605
FrequencyRange.................................... 50-60Hz
FreeAirDisplacement.........................6cfm/60Hz
................................................142l/m@50Hz
................................................170l/m@60Hz
Stages..................................................................2
MotorSpeed.............................1425rpm@50Hz
.............................................1725rpm@60Hz
VoltageRange......................................110V–115V
........................................................ 220V–250V
FactoryMicronRating.......................... 15microns
ApproximateOilCapacity............................ 400ml
Weight........................................................... 13kg
Width....................................................... 14.29cm
Height........................................................ 24.6cm
Length........................................................... 42cm
Intake.............................1/4",3/8",and1/2"SAEMFL
Min.StartingTemp.(at90%voltage)............... 0oC
MotorSize...........0.25kW(1/3HP)CapacitorStart
OperatingTemp.............................................. 68oC
Notes:
1. All motors are internally protected (automatic
reset).
2. Operating temperatures are typical for normal
operating conditions.
3. Model 15603 has a bipolar side grounded plug.
4. Models 15405 & 15605 have Australian plugs.
Because of ongoing product improvements, we reserve the right to
change design, specications, or materials without notice.
Operating Manual
6
Operating Manual
7
INST0026 1
2
3
4
5
6
7
9
8
9
11
12
13
14
16
15
17
Replacement parts
15605/
15601/
Part Item 15401 15603
OilDrainCap(6) 1 40572 40572
OilDrainKit
(includesItemNo.1) 2 13193 13193
ModuleCoverKit
(includesNos.2,4,and5) 3 15337 15337
OilFillCap
(includesNo.7) 4 15371 15371
IntakeFitting
(includesNo.9) 8 15364 555124
IntakeCap(1ea.)
1/4",3/8",1/2"SAEMFL 9 555133 555133
VentBolt
(includeso-rings) 11 15338 15338
Handle,PowerCord
andSwitchAssembly 12 15466 15466
Motor 13 15465 15465
Coupling 14 13192 13192
Iso-ValveTMAssembly 15 15368 15368
BaseandFootAssembly 16 15369 15369
PumpAssembly,lessmotor
(includesNo.3and6) 17 15547 15548
SealReplacementKit
(notshown) -- 15367 15367
Warranty coverage
Robinairvacuumpumpsarewarrantedagainst
defectsinmaterialandworkmanshipforoneyear
ofnormalusefromthedateofpurchase.Seeyour
distributorforwarrantydetails.
Out of warranty
Apumpwhichisnolongercoveredbytheone-
yearwarrantyperiodandwhichfailstooperate
properlyshouldbereturnedtothedistributor
withafullwrittenexplanationoftheproblem.The
distributormaysuggestreturningthepumptothe
factory.Beforereturninganout-of-warrantypump,
reviewallmaintenanceprocedurestoavoidanun-
necessaryreturn.Replacementpartsareavailable
fordoingyourownservice.
9
116292 Rev. F June 18, 2013 © Bosch Automotive Service Solutions
BOSCH AUTOMOTIVE SERVICE SOLUTIONS
655 EISENHOWER DRIVE
OWATONNA, MN 55060 USA
TECHNICAL SERVICES: 1-800-822-5561
FAX: 1-866-259-1241
CUSTOMER SERVICE: 1-800-533-6127
FAX: 1-800-283-8665
WEB SITE: WWW.ROBINAIR.COM
Call our Toll-Free
Technical Support Line at
800-822-5561
in the continental U.S. and Canada
or visit our website
www.robinair.com
In all other locations, contact your local distributor. To help us serve you better,
be prepared to provide the model number, serial number, and date of purchase of
your unit.
To validate your warranty, complete the warranty card attached to your unit and
return it within ten days from date of purchase.
NATIONWIDE NETWORK OF AUTHORIZED SERVICE CENTERS