Rockwell Sonicrafter Devicenet 1771 Sdn Users Manual 6.5.132, PLC 5 Scanner User

2015-02-06

: Rockwell-Sonicrafter Rockwell-Sonicrafter-Devicenet-1771-Sdn-Users-Manual-524685 rockwell-sonicrafter-devicenet-1771-sdn-users-manual-524685 rockwell-sonicrafter pdf

Open the PDF directly: View PDF PDF.
Page Count: 139 [warning: Documents this large are best viewed by clicking the View PDF Link!]

PLC-5 DeviceNet
Scanner Module
1771-SDN
User Manual
Important User Information
Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this control
equipment must satisfy themselves that all necessary steps have been
taken to assure that each application and use meets all performance and
safety requirements, including any applicable laws, regulations, codes and
standards.
The illustrations, charts, sample programs and layout examples shown in
this guide are intended solely for purposes of example. Since there are
many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability (to
include intellectual property liability) for actual use based upon the
examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application,
Installation and Maintenance of Solid-State Control (available from your
local Allen-Bradley office), describes some important differences between
solid-state equipment and electromechanical devices that should be taken
into consideration when applying products such as those described in this
publication.
Reproduction of the contents of this copyrighted publication, in whole or
part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety
considerations:
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
Allen-Bradley, Data Highway Plus, and PLC-5 are trademarks of Rockwell Automation.
ControlNet is a trademark of ControlNet International, Ltd.
DeviceNet is a trademark of Open DeviceNet Vendor Association (ODVA), Inc.
Ethernet is a trademark of Digital Equipment Corporation, Intel, and Xerox Corporation.
RSLinx, RSLogix 5, and RSNetWorx are trademarks of Rockwell Software.
Windows 95/98 and Windows NT are trademarks of Microsoft Corporation.
ATTENTION
!
Identifies information about practices or
circumstances that can lead to personal injury or
death, property damage or economic loss
IMPORTANT Identifies information that is critical for successful
application and understanding of the product.
European Communities (EC)
Directive Compliance
If this product has the CE mark it is approved for installation within
the European Union and EEA regions. It has been designed and tested
to meet the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC
Electromagnetic Compatibility (EMC) by applying the following
standards, in whole or in part, documented in a technical construction
file:
EN 50081-2 EMC — Generic Emission Standard, Part 2 —
Industrial Environment
EN 50082-2 EMC — Generic Immunity Standard, Part 2 —
Industrial Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low
Voltage, by applying the safety requirements of EN 61131-2
Programmable Controllers, Part 2 - Equipment Requirements and
Tests. For specific information required by EN 61131-2, see the
appropriate sections in this publication, as well as the Allen-Bradley
publication Industrial Automation Wiring and Grounding Guidelines
For Noise Immunity, publication 1770-4.1.
This equipment is classified as open equipment and must be mounted
in an enclosure during operation to provide safety protection.
1Publication 1771-6.5.132 - June 2000
Preface
About This User Manual
Introduction
This user manual is designed to provide you enough information to
get a small example application up and running. Use this manual if
you are knowledgeable about DeviceNet and PLC-5 products, but
may not have used the products in conjunction. The information
provided is a base; modify or expand the examples to suit your
particular needs.
The manual contains instructions on configuring a DeviceNet network
using RSLinx and RSNetWorx for DeviceNet software. It also describes
how to use the PLC-5 pass-through feature to communicate with the
DeviceNet network for adjustment and tuning of network devices via
other networks, including:
ControlNet
Ethernet
Data Highway Plus (DH+)
The example application demonstrates how to perform control on
DeviceNet using a PLC-5 processor and the 1771-SDN module. You
use RSLogix 5 programming software to create a ladder logic program
to control a photoeye and a RediSTATION.
IMPORTANT This User manual should be used in conjunction
with the 1771-SDN DeviceNet Scanner Module
Installation Instructions, publication 1771-5.14. The
Installation Instructions contain important
information on configuring your scanner.
Publication 1771-6.5.132 - June 2000
P-2 About This User Manual
Contents
This user manual contains the following chapters:
Audience
This manual is intended for control engineers and technicians who are
installing, programming, and maintaining a control system that
includes a PLC-5 processor communicating on a DeviceNet network
through a 1771-SDN module.
We assume that you:
are developing a DeviceNet network using a PLC-5 processor in
conjunction with the 1771–SDN scanner module
know each of your device’s I/O parameters and requirements
understand PLC-5 processor programming and operation
are experienced with the Microsoft® Windows environment
are familiar with RSNetWorx for DeviceNet software
2
1
3
Planning Your
Configuration
go to Chapter 2
4Configuring the
DeviceNet Network
go to Chapter 4
Configuring DeviceNet
From Another Network
go to Chapter 5
5
Before You Begin
go to Chapter 1
Setting Up the
Hardware
go to Chapter 3
Creating and Running
the Application Program
go to Chapter 6
6
7Troubleshooting
go to Chapter 7
Publication 1771-6.5.132 - June 2000
About This User Manual P-3
The Example Application
This manual describes how to set up an example application. The
manual provides examples of each step of the setup, with references
to other manuals for more details.
System Components
We used the following devices and software for the example
application. For your own application, substitute your own devices to
fit your needs. The recommended configurations in this user manual
will help you set up the test system and get it working. Your eventual
configuration will depend on your application.
Note: If you use different software or fimware versions of these
products some of your screens may appear slightly different from
those shown in the example.
Product Name Catalog Number Series Revision
Qty Hardware
1PLC-5C processor(1) 1785-L20C15, -L40C15, -L80C15 - -
1 1771 Universal I/O chassis 1771-A1B, -A2B, -A3B, -A3B1,
-A4B
B-
1 DeviceNet Scanner module 1771-SDN/B B -
1Ethernet Interface module(2) 1785-ENET - -
1 DeviceNet Quad-Tap 1492-DN3TW - -
1 RediSTATION operator interface module 2705-TxDN1x42x-xxxx - -
1 Series 9000 Photoeye 42GNP-9000 or equivalent
1 DeviceNet RS-232 interface module 1770-KFD - -
1 RS-232 cables 1787-RSCABL/A (PC to 1770-KFD) - -
- DeviceNet dropline or trunkline
cables, as needed
1787-PCABL, -TCABL, -MCABL - -
1 24V Power Supply Regulated 24VDC, 8A - -
1 PC IBM-compatible
Windows 95/98, NT 4.0
Software
RSLogix 5 9324-RL5300xxx - 3.22
RSNetWorx for DeviceNet 9357-DNETL3 - 2.11
RSLinx 9355-WABxxx - 2.10
(1) The minimum requirement for the processor is that it support block transfer instructions.
A ControlNet version of the Processor is required if interfacing the DeviceNet network and a ControlNet network (see chapters 5 and 6).
(2) Required if interfacing the DeviceNet network and an Ethernet network. See chapters 5 and 6.
Publication 1771-6.5.132 - June 2000
P-4 About This User Manual
Common Techniques
Used in This Manual
The following conventions are used throughout this manual:
Bulleted lists provide information, not procedural steps.
Numbered lists provide sequential steps.
Information in bold contained within text identifies menu
windows, or screen options, screen names and areas of the
screen, such as dialog boxes, status bars, radio buttons and
parameters.
TIP This symbol identifies helpful tips.
A definition box defines terms that may be
unfamiliar to you.
Screen captures are pictures of the software’s
actual screens. The names of screen buttons and
fields are often in bold in the text of a
procedure. Pictures of keys represent the actual
keys you press.
The “MORE” icon is placed beside any
paragraph that references sources of additional
information outside of this document.
This is a definition
box. When a word is
bold within the text
of a paragraph, a
definition box will
appear in the left
margin to further
define the text.
More
Publication 1771-6.5.132 - June 2000
About This User Manual P-5
Where to Find
More Information
Refer to the following publications as needed for additional help
when setting up and using your DeviceNet network:
More
For information about See this publication Publication Number
the 1771-SDN DeviceNet scanner 1771-SDN Scanner Module Installation Instructions 1771-5.14
the PLC-5 processor ControlNet PLC-5 Programmable Controllers User Manual
Phase 1.5
1785-6.5.22
PLC-5 Instruction Set Reference Manual 1785-6.1
1785-PLC-5 Programmable Controllers Quick Reference 1785-7.1
the1785-ENET Ethernet interface module PLC-5 Ethernet Interface Module User Manual 1785-6.5.19
the 1771 I/O chassis Universal I/O Chassis 1771-2.210
the 1770-KFD communication module DeviceNet RS-232 Interface Module Installation Instructions 1770-5.6
a 1784-PCD communication card NetLinx DeviceNet Communication Card Installation Instructions 1784-5.29
a 1784-PCID or 1784-PCIDS card DeviceNet PCI Communication Interface Card Installation 1784-5.31
the RediSTATION RediSTATION Operator Interface User Manual 2705-804
the 9000 Series photoeye {refer to the information that came with your photoeye} n/a
DeviceNet DeviceNet System Overview DN-2.5
DeviceNet Design Manual (online) DNET-AT-001A-EN
connecting the DeviceNet network DeviceNet Cable Planning and Installation Manual DN-6.7.2
DeviceNet Cable Planning and Installation Release Note 1 DN-6.7.2-RN1
RSLinx software RSLinx Lite User’s Guide 9399-WAB32LUG
RSLogix 5 software Getting Results With RSLogix 5 9399-RL53GR
RSNetWorx for DeviceNet software DeviceNet Demo CD 9398-DNETDEMO
terms and definitions Allen-Bradley Industrial Automation Glossary AG-7.1
TIP Many of the above are available online from the
Automation Bookstore:
http://www.theautomationbookstore.com.
TIP For more information about Rockwell Software
products, visit the Rockwell Software internet site:
http://www.software.rockwell.com.
Publication 1771-6.5.132 - June 2000
P-6 About This User Manual
Terminology
This term Means
Bridge The scanner module’s support of explicit message transfer.
Change of State A type of I/O data communication. The scanner module can send and
receive data with slave devices that have the change of state feature. Data
is sent whenever a data change occurs. Data is updated at the rate of the
heartbeat.
Communication
Module
The 1771-SDN scanner module or the 1770-KFD module.
Cyclic A type of I/O data communication. The scanner module can send and
receive data with slave devices that have the cyclic feature. Data is only
sent at a user-configurable rate.
EDS Electronic Data Sheet. A vendor-supplied template that specifies how
information is displayed as well as what is an appropriate entry (value).
Explicit
Messaging
A type of messaging used for lower priority tasks, such as configuration
and data monitoring.
Heartbeat Rate Devices that are configured for change of state data can also send a
“heartbeat” signal to indicate proper operation.
Host Platform The computer that hosts the 1771-SDN scanner module.
I/O An abbreviation for “input and output”.
Implicit
Messaging
The type of messaging used for high priority I/O control data; e.g., change
of state, cyclic, polled, or strobed.
Input Data Data produced by a DeviceNet device and collected by the scanner module
for a host platform to read.
MAC ID The network address of a DeviceNet node.
Network The DeviceNet network or the RSNetWorx for DeviceNet software
representation of the network.
Node Hardware that is assigned a single address on the network (also referred
to as device).
Offline When the PC communication scanner is not communicating on the
network.
Online When the PC communication scanner is configured and enabled to
communicate on the network.
Output Data Data produced by a host platform that is written to the scanner module’s
memory. This data is sent by the scanner module to DeviceNet devices.
PC Abbreviation for an IBM® compatible personal-computer.
Polled A type of input/output-data communication. A polled message solicits a
response from a single, specified device on the network (a point-to-point
transfer of data).
Record The node address and channel-specific memory assigned in the scanner
module’s non-volatile storage for a node in the scanlist.
Rx An abbreviation for “receive”.
Scanlist The list of devices (nodes) with which the scanner is configured to
exchange I/O data.
Scanner The function of the 1771-SDN scanner module to support the exchange of
I/O with slave modules.
Slave Mode The scanner module is in slave mode when it is placed in another scanner
module’s scanlist as a slave device.
Strobed A type of I/O data communication. A strobed message solicits a response
from each strobed device (a multicast transfer). It is a 64-bit message that
contains one bit for each device on the network.
Tx An abbreviation for “transmit”.
Publication 1771-6.5.132 - June 2000
About This User Manual P-7
Rockwell Automation
Support
Rockwell Automation offers support services worldwide, with over 75
sales/support offices, 512 authorized distributors, and 260 authorized
systems integrators located throughout the United States alone, plus
Rockwell Automation representatives in every major country in the
world.
Local Product Support
Contact your local Rockwell Automation representative for:
sales and order support
product technical training
warranty support
support service agreements
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance,
call your local Rockwell Automation representative, or call Rockwell
directly at: 1 440 646-6800.
For presales support, call 1 440 646-3NET.
You can obtain technical assistance online from the following
Rockwell Automation WEB sites:
www.ab.com/mem/technotes/kbhome.html (knowledge base)
www.ab.com/networks/eds (electronic data sheets)
Your Questions or Comments about This Manual
If you find a problem with this manual, please notify us of it on the
enclosed Publication Problem Report (at the back of this manual).
If you have any suggestions about how we can make this manual
more useful to you, please contact us at the following address:
Rockwell Automation, Allen-Bradley Company, Inc.
Control and Information Group
Technical Communication
1 Allen-Bradley Drive
Mayfield Heights, OH 44124-6118
Publication 1771-6.5.132 - June 2000
P-8 About This User Manual
iPublication 1771-6.5.132 - June 2000
Table of Contents
Chapter 1
Before You Begin
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
What You Need to Know . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
What Your 1771-SDN Module Does . . . . . . . . . . . . . . . . . . . . 1-2
Address Density and Discrete I/O . . . . . . . . . . . . . . . . . . . . . . 1-4
Communicating with Your Devices . . . . . . . . . . . . . . . . . . . . . 1-6
Communicating with Your PLC-5 Processor. . . . . . . . . . . . . . . 1-7
What 1771-SDN Module Data Tables Are and What They Do . . 1-8
The Scanner Configuration Table (SCT) . . . . . . . . . . . . . . . 1-8
The Scanlist Table (SLT) . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
RSNetWorx Software as a Configuration Tool . . . . . . . . . . . . . 1-9
RSNetWorx for DeviceNet Configuration Screen Map . . . . 1-10
What’s Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Chapter 2
Planning Your Configuration and
Data Mapping Your Devices
What You Need to Know . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Beginning the Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
The Example Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Example Network Devices . . . . . . . . . . . . . . . . . . . . . . . . 2-2
RediSTATION Operator Interface Data Mapping. . . . . . . . . 2-4
Mapping RediSTATION Input Data
for a Block Transfer Read . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Mapping RediSTATION Output Data
for a Block Transfer Write . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Photoeye Input Data Mapping. . . . . . . . . . . . . . . . . . . . . . 2-7
Mapping Photoeye Input Data for a Block Transfer Read . . 2-8
What’s Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Chapter 3
Hardware Setup
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Installing the 1770-KFD Interface Module . . . . . . . . . . . . . . . . 3-1
Installing the PLC-5 Processor . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Setting the I/O Chassis Backplane Switches . . . . . . . . . . . . 3-2
Going Online to the PLC-5 Processor. . . . . . . . . . . . . . . . . 3-3
Installing the 1785-ENET Ethernet Module. . . . . . . . . . . . . . . . 3-5
Installing the 1771-SDN Scanner Module . . . . . . . . . . . . . . . . . 3-7
Setting the Channel 1 Data Rate
and Node Address Switches . . . . . . . . . . . . . . . . . . . . . . . 3-8
Setting the I/O Chassis Addressing Node Switches . . . . . . . 3-8
Installing the Scanner Module in the Chassis . . . . . . . . . . . 3-9
Connecting the Scanner to the DeviceNet Network . . . . . 3-10
Installing the RediSTATION Operator Interface . . . . . . . . . . . 3-11
Installing the Series 9000 Photoeye . . . . . . . . . . . . . . . . . . . . 3-12
How Your Example System Will Look. . . . . . . . . . . . . . . . . . 3-13
What’s Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Publication 1771-6.5.132 - June 2000
Table of Contents ii
Chapter 4
Configuring the
DeviceNet Network
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Installing the Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Using RSLinx to Configure the DeviceNet Driver . . . . . . . . . . . 4-2
Using RSNetWorx for DeviceNet to Configure the Scanlist . . . . 4-4
Setting Up an Online Connection . . . . . . . . . . . . . . . . . . . 4-4
Setting the 1771-SDN Node Address . . . . . . . . . . . . . . . . . 4-6
Configuring the I/O Devices . . . . . . . . . . . . . . . . . . . . . . . 4-9
Verifying the Photoeye Configuration. . . . . . . . . . . . . 4-12
Verifying the RediSTATION Configuration . . . . . . . . . 4-13
AutoMapping the Devices into the Scanlist . . . . . . . . . 4-14
Download the Configuration to the Scanner . . . . . . . . 4-17
What’s Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
Chapter 5
Communicating with DeviceNet
from Another Network
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Where to Find More Information. . . . . . . . . . . . . . . . . . . . . . . 5-2
Communicating with DeviceNet from a ControlNet Network . . 5-3
Configuring the DeviceNet Pass-Through Driver. . . . . . . . . 5-3
Communicating with the DeviceNet Network. . . . . . . . . . . 5-6
Communicating with DeviceNet from an Ethernet Network. . . 5-9
Configuring the Ethernet to PLC-5 Communications Driver . 5-9
Configuring the DeviceNet Pass-Through Driver. . . . . . . . 5-12
Communicating with the DeviceNet Network. . . . . . . . . . 5-15
Communicating with DeviceNet from a DH+ Network . . . . . 5-18
Configuring the DeviceNet Pass-Through Driver. . . . . . . . 5-18
Communicating with the DeviceNet Network. . . . . . . . . . 5-21
What’s Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
Chapter 6
Creating and Running the Example
Application Program
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Installing the Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Creating the Example Application Program . . . . . . . . . . . . . . . 6-2
Downloading and Running the Program . . . . . . . . . . . . . . . . . 6-6
Downloading and Running the Program
via a ControlNet Network . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Testing the Example Program . . . . . . . . . . . . . . . . . . . 6-8
Downloading and Running the Program
via an Ethernet Network . . . . . . . . . . . . . . . . . . . . . . . . . . 6-9
Testing the Example Program . . . . . . . . . . . . . . . . . . 6-11
Downloading and Running the Program
via a DH+ Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12
Testing the Example Program . . . . . . . . . . . . . . . . . . 6-14
What’s Next? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-14
Publication 1771-6.5.132 - June 2000
Table of Contents iii
Chapter 7
Troubleshooting
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Module Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Network Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Node/Error Code Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Appendix A
1785-ENET Module
Channel Configuration
Configuring the Communications Channel. . . . . . . . . . . . . . . . A-1
Appendix B
Installing and Configuring the
ControlNet Communications
Driver
Installing the 1784-KTCX15 Communication Interface Card . . . B-1
Configuring the 1784-KTCX15 Communications Driver . . . . B-2
Appendix C
Installing and Configuring the
DH+ Communications Driver
Installing the 1784-KTX Communication Interface Card . . . . . . C-1
Configuring the 1784-KTX Communications Driver . . . . . . . . . C-2
Appendix D
Data Map Example
Example Input Mapping Scheme. . . . . . . . . . . . . . . . . . . . . . D-1
Example Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Example Framework . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
Input Data Table Formats . . . . . . . . . . . . . . . . . . . . . . . . D-3
Example Output Mapping Scheme . . . . . . . . . . . . . . . . . . . . D-6
Example Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . D-6
Example Framework . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-6
Output Data Table Formats . . . . . . . . . . . . . . . . . . . . . . . D-7
Index
Publication 1771-6.5.132 - June 2000
Table of Contents iv
1Publication 1771-6.5.132 - June 2000
Chapter
1
Before You Begin
What This Chapter Contains
This chapter provides an overview of communication between a
PLC-5 processor and DeviceNet devices via a 1771-SDN module. The
data tables and the RSNetWorx for DeviceNet screens and windows
used to configure the data tables are also described.
The following table identifies what this chapter contains and where to
find specific information.
What You Need to Know
Before configuring your 1771-SDN scanner module, you must
understand:
the data exchange between the PLC -5 processor and DeviceNet
devices through the 1771-SDN module
user-configurable 1771-SDN module data tables
the role of RSNetWorx for DeviceNet software
For information about See page
What You Need to Know 1-1
What Your 1771-SDN Module Does 1-2
Communicating with Your Devices 1-6
What 1771-SDN Module Data Tables Are and What They Do 1-8
The Scanner Configuration Table (SCT) 1-8
The Scanlist Table (SLT) 1-8
RSNetWorx Software as a Configuration Tool 1-9
RSNetWorx for DeviceNet Configuration Screen Map 1-10
Publication 1771-6.5.132 - June 2000
1-2 Before You Begin
What Your 1771-SDN
Module Does
In a typical configuration, the 1771-SDN module acts as an interface
between DeviceNet devices and the PLC-5 processor.
The 1771-SDN module communicates with DeviceNet devices over
the network to:
read inputs from a device
write outputs to a device
download configuration data
monitor a device’s operational status
The 1771-SDN module communicates with the processor in the form
of Block Transfers (BT) and/or Discrete I/O (DIO). Information
exchanged includes:
device I/O data
status information
configuration data
1770-KFD PC
Communication
Module
PC with RSNetWorx
for DeviceNet software
Series 9000
Photoeye RediSTATION
1305 Drive
FLEX I/O Rack
DeviceNet
Devices
DeviceNet Network
PLC-5
Processor
1771-SDN
Scanner module
1771 I/O
Chassis
Publication 1771-6.5.132 - June 2000
Before You Begin 1-3
A processor to I/O DeviceNet configuration is shown in the following
figure. See the referenced chapters for more information.
Configure SDN module (Chapter 4)
Mapping Table (Chapters 2 and 4)
Input
Device Output
Device
Input Data from
Device to SDN
(Chapter 2)
Output Write by
Processor (Chapter 2)
DeviceNet Network
Output Data to Devices
from SDN (Chapter 2)
Input Read by Processor (Chapter 2) Processor to I/O
PC running
RSNetWorx
for DeviceNet
Publication 1771-6.5.132 - June 2000
1-4 Before You Begin
The 1771-SDN scanner module can also be used to bridge a
DeviceNet network with another network.
Address Density
and Discrete I/O
You can use three addressing methods with your 1771-SDN scanner
module. The number of discrete I/O bits you have available for data
transfer is affected by the addressing mode selected.
Configuring Devices and Data Collection on
Higher-Level Networks Via PLC-5/SDN
Target Device to
be configured Source Device
to collect data
Configuration of device
using RSNetWorx
(Chapters 4 & 5)
DeviceNet Network
Laptop PC
running
RSNetWorx
ControlNet, DH+, or Ethernet Network
Collection of status
or alarm data
(Chapter 6)
SDN scanner
module
Industrial
workstation
running RSView
Addressing Mode Discrete Inputs Discrete Outputs
2-slot 0 bits 0 bits
1-slot 8 bits 8 bits
1/2-slot 24 bits 24 bits
Publication 1771-6.5.132 - June 2000
Before You Begin 1-5
The concept described below applies to both input and output data
tables. For example, when using your 1771-SDN in 1-slot addressing
mode, you have eight bits of discrete input and eight bits of output
available.
The address density is set via dip switches on the 1771-SDN module
and 1771 chassis. For more information about setting your module’s
address density with switches, refer to the 1771-SDN Scanner Module
Installation Instructions, publication 1771-5.14. For more information
about 1771-module addressing, refer to chapter 3 and to your PLC
programmable controller system-level installation manual and design
manual.
In the scanner’s input and output data tables, there is one byte of memory that is
reserved for communication between the processor and the scanner.
Processor-specific responses from the scanner are read by the processor in this byte
of the input data table. Scanner-specific instructions are written to this byte of the
output data table.
In 2-slot addressing mode, the only memory that would have
been available for discrete data transfer (8 bits) is taken up by
scanner/processor communication.
0 bits for discrete data transfer 2-slot addressing
8 bits for discrete data transfer 1-slot addressing
24 bits for discrete data transfer 1/2-slot addressing
In 1-slot addressing mode, there are 16 bits: eight bits for
scanner/processor communication, and eight bits for discrete
data transfer.
In 1/2-slot addressing mode, there are 32 bits: eight bits used for
scanner/processor communication, and 24 bits for discrete data
transfer.
= bits reserved for 1771-SDN and
processor communication
= bits available for discrete
data transfer
More
Publication 1771-6.5.132 - June 2000
1-6 Before You Begin
Communicating with
Your Devices
The 1771-SDN module communicates with a device via
strobe,
poll,
change of state,
and/or
cyclic
messages. It uses these messages to solicit
data from or deliver data to each device. Data received from the devices,
or input data, is organized by the 1771-SDN module and made available
to the processor. Data received from your PLC-5 processor, or output data,
is organized in the 1771-SDN module and sent on to your devices.
IMPORTANT
Throughout this document,
input
and
output
are defined
from the PLC-5 processor’s point of view. Output is data
sent from the PLC-5 processor
to
a device. Input is data
collected by the PLC-5 processor
from
a device.
All data sent and received on a DeviceNet network is in
byte lengths. A device may, for example, produce only
two bits of input information. Nevertheless, since the
minimum data size on a DeviceNet network is one byte,
two bits of information are included in the byte of data
produced by the device. In this example (only two bits of
input information), the upper six bits are insignificant.
A strobe message is a
multicast transfer of data
(which is 64 bits in length)
sent by the 1771-SDN
module that solicits a
response from each strobed
slave device. There is one bit
for each of the possible 64
node addresses. The devices
respond with their data,
which can be as much as 8
bytes.
A poll message is a
point-to-point transfer of
data (0-255 bytes) sent by
the 1771-SDN module that
solicits a response from a
single device. The device
responds with its input data
(0-255 bytes).
A change of state message
is a transfer of data sent
whenever a data change
occurs. A user-configurable
heartbeat rate can also be
set to allow devices to
indicate proper operation
during intervals between
data changes. This does not
solicit response data, but
may receive an acknowledge
message.
A cyclic message is sent only
at a user-configurable rate,
such as every 10 ms.
1771-SDN Scanner Module DeviceNet Devices
Input Data Storage
Input Data From
DeviceNet Devices
E
Y
X
Y
Y
Data from a single device can
be mapped to separate
1771-SDN module memory
locations. For example,
“On/Off” values can be mapped
to one location, diagnostic
values to another, etc. This is
known as “map segmenting”.
This concept is illustrated by
byte A, stored separately as
segments A1 and A2.
Output Data Storage
Output Data To
DeviceNet Devices
Byte
,
0
1
2
3
4
5
6
Z
Y
Y
Y
output from
the PLC-5
processor
B
A1
C
D
A2
E
E
input from the
devices to the
PLC-5 processor
B
C
D
X
Z
A1 A2
Y
Publication 1771-6.5.132 - June 2000
Before You Begin 1-7
Communicating with Your
PLC-5 Processor
Your processor communicates with the 1771-SDN scanner module via
block transfer reads, block transfer writes, and DIO transfers.
Input data, gathered from the network’s devices, is organized within
the 1771-SDN and made available for the processor to “read”.
The 1771-SDN module does not send data to your processor.
Data transferred between the module and the processor must be
initiated by the processor. Output data is sent, or “written”, to the
scanner by your processor. This data is organized in the 1771-SDN
module, which in turn passes the data on to your scanned devices via
strobe, poll, change of state, or cyclic messages.
A block transfer read (BTR) is
a block transfer of data from
the 1771-SDN module to the
PLC processor. The processor
is
reading
the data collected
by the 1771-SDN module
(i.e., DeviceNet input data).
A block transfer write (BTW)
is a block transfer of data
from the PLC processor to
the 1771-SDN module. The
processor is
writing
the data
to the 1771-SDN’s memory
(i.e., DeviceNet output data).
PLC-5 Processor 1771-SDN Scanner
B
A1
C
D
A2
E
E
X
Y
Y
Z
Y
Y
C
D
A2
X
Z
Y
Y
Y
Y
Discrete Input Image
Block Transfer Data File
A1
B
E
E
Internal Input
Data Storage
I/O Map
Input from
the devices
Discrete Output Image
Block Transfer Data File
Internal
Output Data
I/O Map
Discrete I/O
Transfer
Block
Transfer
Write
Discrete I/O
Transfer
Block
Transfer
Read
Output to
the devices
Publication 1771-6.5.132 - June 2000
1-8 Before You Begin
What 1771-SDN Module
Data Tables Are and What
They Do
To manage the flow of data between your processor and the network
devices, the 1771-SDN module uses the following data tables.
1771-SDN Module Configuration Table
Scanlist Table
Device Input Data Table
Device Output Data Table
Device Idle Table
Device Failure Table
You can configure two of these data tables through RSNetWorx
software. These two tables are stored in the 1771-SDN module’s
non-volatile memory and used to construct all other data tables:
Scanner Configuration Table (SCT)
Scanlist Table (SLT)
The Scanner Configuration Table (SCT)
The SCT controls basic information your 1771-SDN module needs to
function on your DeviceNet network. It tells your 1771-SDN module:
if it can transmit and receive input and output data
how long it waits after each scan before it scans the devices
again
when to send out its poll messages
The Scanlist Table (SLT)
The SLT supports I/O updating for each of your devices on the
network. It also makes it possible for your 1771-SDN module to make
device data available to your processor. The SLT tells your 1771-SDN
module:
which device node addresses to scan
how to scan each device (strobe, poll, change of state, cyclic or
any valid combination)
how often to scan your devices
Publication 1771-6.5.132 - June 2000
Before You Begin 1-9
exactly where in each device’s total data to find the desired data
the size of the input data/output data
exactly where to map the input or output data for your
processor to read or write
RSNetWorx Software as a
Configuration Tool
RSNetWorx for DeviceNet software is used to configure the 1771-SDN
module’s data tables. This software tool connects to the 1771-SDN
module over the DeviceNet network via a PC RS–232 interface
(1770–KFD module), or PC Card (1784-PCD, -PCID, or PCIDS).
User
Configured
Tables
Data In This Table RSNetWorx Configuration
Screen
SCT basic operation
module parameters
interscan delay
background poll ratio
1771-SDN Module Configuration
SLT device-specific
identification data
Scanlist Editor (SLE)
data transfer method
transmit/receive data size
Edit Device I/O Parameters
input and output data
source and destination
locations
These values can be configured
automatically through the
AutoMap function or manually
through the Data Table Map.
Interscan delay is the time between
I/O scans (polled and strobed). It is
the time the 1771-SDN module will
wait between the last poll message
request and the start of the next scan
cycle.
Background poll ratio sets the
frequency of poll messages to a
device in relation to the number of
I/O scans. For example, if the ratio
is set at 10, that device will be
polled once every 10 scans.
TIP RSNetWorx for DeviceNet software can also
communicate with the 1771-SDN module via a
ControlNet, Ethernet, or Data Highway Plus network.
See chapter 5.
Publication 1771-6.5.132 - June 2000
1-10 Before You Begin
The configuration screen map below shows the RSNetWorx for
DeviceNet screens used to configure the 1771-SDN module and the
navigation paths between them. The use of these screens is described
in Chapter 4.
RSNetWorx for DeviceNet Configuration Screen Map
The main RSNetWorx for DeviceNet screen.
To automatically map input
devices, select the Input tab
and click on the AutoMap
button.
To automatically map output
devices, select the Output tab
and click on the AutoMap
button.
To access the scanlist,
click on the Scanlist tab.
To edit a devices I/O parameters,
double-click on the device in
To access the 1771-SDN scanner Module,
double-click on the 1771-SDN icon.
To download the scanlist, click on
the Download to Scanner button.
To browse the network,
click on the Online button
and select the driver.
the scanlist.
Publication 1771-6.5.132 - June 2000
Before You Begin 1-11
What’s Next?
The remaining sections of this manual provide the following
information:
Chapter 2 covers the configuration process planning stage
through a data mapping example.
Chapter 3 describes the hardware setup for the example
application.
Chapter 4 covers configuration of the DeviceNet network using
RSNetWorx for DeviceNet software.
Chapter 5 describes how to communicate with a DeviceNet
network from another network.
Chapter 6 describes how to create, download, and run the
example application program.
Chapter 7 covers the diagnostics provided for troubleshooting
the 1771-SDN module.
Publication 1771-6.5.132 - June 2000
1-12 Before You Begin
1Publication 1771-6.5.132 - June 2000
Chapter
2
Planning Your Configuration and Data
Mapping Your Devices
This chapter introduces questions you should ask before configuring
your 1771-SDN Scanner. In addition, it presents an example DeviceNet
network and I/O data mapping scheme for a photoeye and a
RediSTATION operator interface module. The following table
identifies what this chapter covers and where to find specific
information.
What You Need to Know
To map data via your 1771-SDN Scanner module, you must
understand:
your network requirements
how input data is mapped
how output data is mapped
Beginning the Process
Planning before configuring your 1771-SDN module helps make sure
that you can:
use your memory and bandwidth efficiently
cater to device-specific needs and requirements
give priority to critical I/O transfers
leave room for expansion
For information about See page
What You Need to Know 2-1
Beginning the Process 2-1
The Example Network 2-2
Example Network Devices 2-2
Photoeye Input Data Mapping 2-7
Mapping Photoeye Input Data for a Block Transfer Read 2-8
RediSTATION Operator Interface Data Mapping 2-4
Mapping RediSTATION Input Data for a Block Transfer Read 2-5
Mapping RediSTATION Output Data for a Block Transfer Write 2-6
Publication 1771-6.5.132 - June 2000
2-2 Planning Your Configuration and Data Mapping Your Devices
A very important question to answer is “what is on your network?”
You should be familiar with each device’s:
communication requirements
I/O importance and size
frequency of message delivery
You should also ask “how might this network appear in the future?” At
this point in your planning, it is advantageous for you to have some
idea of how the network could be expanded. I/O data mapping can
be performed automatically by the RSNetWorx software. But when
mapping your I/O, you also have the opportunity to allot room for
future I/O. This can save time and effort in the future.
For example, RSNetWorx will automatically map the devices as
efficiently as possible, but the result is that multiple devices may share
the same word location in memory. However, you can also have the
system map the devices such that no two devices share the same
memory location by selecting the “Dword align” option when
performing automapping. You can manually map the devices if you
need to assign them to specific memory locations.
For details refer to the Help screens provided by the RSNetWorx for
DeviceNet software. Additional support can be found at the Rockwell
Software website: http://www.software.rockwell.com.
The Example Network
The following example illustrates a data mapping plan for a
DeviceNet network. Note that even if the mapping is performed
automatically by the RSNetWorx software, you must know where the
devices are mapped in order to use them in your network.
Example Network Devices
This example network has the following devices:
a PC running RSNetWorx for DeviceNet software
a 1771-SDN Scanner module interfacing a PLC-5 processor with
DeviceNet
a Series 9000 photoelectric sensor (strobed)
a RediSTATION operator interface (polled)
Publication 1771-6.5.132 - June 2000
Planning Your Configuration and Data Mapping Your Devices 2-3
The system you will set up is shown below:
IMPORTANT In the following example, output is data sent to a
device from a controller. Input is data collected from
a device by a controller.
DeviceNet Network
PC running Windows NT
or Windows 95/98,
containing RSNetWorx for
DeviceNet software
Series 9000
Photoelectric
Sensor
RediSTATION
Operator Interface
1771-SDN and PLC-5
in 1771 I/O Chassis
Node 7
Node 9
Node 62
1770-KFD
Communication
Module
Node 0
* See note below
IMPORTANT Each end of the DeviceNet trunk cable must be
properly terminated with a resistor. Refer to the
DeviceNet Cable Planning and Installation Manual,
publication DN-6.7.2 for detailed information.
Publication 1771-6.5.132 - June 2000
2-4 Planning Your Configuration and Data Mapping Your Devices
RediSTATION Operator Interface Data Mapping
The RediSTATION has both inputs and outputs that must be mapped.
The input byte is mapped to the 1771-SDN module’s block transfer
read data table and then to the PLC-5 processor’s input data file. The
output byte is mapped to the 1771-SDN module’s block transfer write
data table and then to the PLC-5 processor’s output data file.
The mapping procedure, using RSNetWorx for DeviceNet software, is
described on pages 4-14 to 4-17.
In the RediSTATION’s bits for the red and green buttons and the
indicator light status bit:
1 = ON
0 = OFF
RediSTATION operator interface
Two input bits from the RediSTATION will
be mapped: bit 1 for the green Start button
and bit 0 for the red Stop button.
Bit 4 of the input byte indicates if the bulb
is missing.
Indicator light
green start light
red start light
1 byte
input
output
1 byte
The RediSTATION
operator interface
produces one byte of
input data and uses one
byte of output data. L
start bit (green button)
stop bit
(red button)
status bit for
indicator light
One output bit for the RediSTATION’s
indicator light (on/off) will be mapped.
76543210
76543210
G R
Publication 1771-6.5.132 - June 2000
Planning Your Configuration and Data Mapping Your Devices 2-5
Mapping RediSTATION Input Data for a Block Transfer Read
The RediSTATION operator interface’s input byte is mapped to the
scanner’s block transfer read data table through a 62 word BTR. In this
example, we use data file N9:0.
1
2
The bits for the RediSTATION
operator interfacess red and green
buttons are mapped into the
1771-SDN Scanners BTR data
table.
What’s Happening?
The BTR data table is then
transferred via a BTR to the PLC-5
processor’s input data file.
Important: The 1771-SDN module only
makes the data file available for the
processor to read. The 1771-SDN does
not move the data file to the processor.
R = bit for red button (STOP)
G = bit for green button (START)
N9:0 0000 0000 0000 0000
N9:1 0000 0000 0000 00GR
N9:2 0000 0000 0000 0000
N9:3 0000 0000 0000 0000
N9:5 0000 0000 0000 0000
Word 0
Word 1
Word 2
Word 3
Word 4
Word 61
The red STOP button from the
RediSTATION appears in the PLC-5
processor’s input file at address N9:1/0.
N9:4 0000 0000 0000 0000
RediSTATION Input Byte
= unused bits
1
1771-SDN Scanner Block Transfer Read Data Table
1 byte G R
2
G R
1 This mapping is based upon the example in chapter 4.
The mapping for your system may be different.
PLC-5 Processor
Input Data File1
reserved for module status word
= bits reserved for module
status word
Note: This example uses
1-slot addressing.
N9:61 0000 0000 0000 0000
Example: The green START button from
the RediSTATION appears in the PLC-5
processor’s input file at address N9:1/1.
Publication 1771-6.5.132 - June 2000
2-6 Planning Your Configuration and Data Mapping Your Devices
Mapping RediSTATION Output Data for a Block Transfer Write
The RediSTATION operator interface’s output byte is mapped to the
1771-SDN module’s block transfer write data table. Within the output
byte is bit 0 for the indicator light. The PLC-5’s output data file is
transferred by the processor application to turn the light on or off. In
this example, we use N10 for the output data file.
1start/stop station node address 7
L = bit for the station
indicator light
2
The PLC-5 processor’s output
data file containing the indicator
light bit for the RediSTATION is
transferred via a BTW to the
1771-SDN Scanners BTW data
table.
What’s Happening?
The BTW data table is then sent
to the RediSTATION via a polled
message from which the
RediSTATION receives its
indicator light bit.
= unused bits
2
RediSTATION Output
1 byte L
1
Example: The RediSTATION’s indicator light (L) is taken
from N10:1/0 in the PLC-5 processor’s output data file.
1 This mapping is based upon the example in chapter 4.
The actual mapping for your system may be different.
= bits reserved for module
status word
Word 0
Word 1
Word 2
Word 3
Word 4
Word 61
1771-SDN Scanner Block Transfer Write Data Table
L
reserved for module status word
N10:0 0000 0000 0000 0000
N10:1 0000 0000 0000 000L
N10:2 0000 0000 0000 0000
N10:3 0000 0000 0000 0000
N10:5 0000 0000 0000 0000
N10:4 0000 0000 0000 0000
PLC-5 Processor
Output Data File1
N10:61 0000 0000 0000 0000
Note: This example uses
1-slot addressing.
Publication 1771-6.5.132 - June 2000
Planning Your Configuration and Data Mapping Your Devices 2-7
Photoeye Input Data Mapping
The photoelectric sensor (photoeye) inputs are mapped to the
1771-SDN module’s block transfer read data table and then to the
PLC-5 processor’s input data file. The procedure for doing this using
RSNetWorx for DeviceNet software is described on pages 4-14 to 4-17.
The photoeye has no outputs to map.
Series 9000 Photoeye
Two input bits from the photoeye
will be mapped: the status bit
and the data bit.
The photoeye produces
one byte of input data in
response to the strobe
message.
input
status
bit
1 byte S D data
bit
76543210
Publication 1771-6.5.132 - June 2000
2-8 Planning Your Configuration and Data Mapping Your Devices
Mapping Photoeye Input Data for a Block Transfer Read
The photoeye’s input byte is mapped to the scanner’s block transfer
read data table through a 62 word BTR. In this example, we use data
file N9.
What’s Happening?
Important: The 1771-SDN module only
makes the data available for the
processor to read. The 1771-SDN
module does not move the data to the
processor.
= unused bits
1
Photoeye Input Byte
1 byte
1
2
The status and data bits from
the photoeye are mapped into
the 1771-SDN Scanner’s BTR
data table.
The BTR data table is then
transferred via a BTR to the
PLC-5 processor’s input data
file.
S D
2
1 This mapping is based upon the example in chapter 4.
The actual mapping for your system may be different.
Note: This example uses
1-slot addressing.
Word 0
Word 1
Word 2
Word 3
Word 4
Word 61
1771-SDN Scanner Block Transfer Read Data Table
S D
= bits reserved for module
status word
N9:0 0000 0000 0000 0000
N9:1 0000 00SD 0000 0000
N9:2 0000 0000 0000 0000
N9:3 0000 0000 0000 0000
N9:5 0000 0000 0000 0000
N9:4 0000 0000 0000 0000
PLC-5 Processor
Input Data File1
N9:61 0000 0000 0000 0000
Example: The Status bit from the photoeye appears in the PLC-5
processor’s integer file at address N9:1/9.
The Data bit from the photoeye appears in the PLC-5 processor’s
integer file at address N9:1/8.
reserved for module status word
RediSTATION
Publication 1771-6.5.132 - June 2000
Planning Your Configuration and Data Mapping Your Devices 2-9
What’s Next?
Chapter 3 describes how to set up the system hardware for the
example application.
Publication 1771-6.5.132 - June 2000
2-10 Planning Your Configuration and Data Mapping Your Devices
1Publication 1771-6.5.132 - June 2000
Chapter
3
Hardware Setup
What This Chapter Contains
This chapter describes how to set up the hardware for the example
application. The following table describes what this chapter contains
and where to find specific information.
Installing the 1770-KFD
Interface Module
Connect the RS-232 connector on the 1770-KFD interface module to
one of the serial ports on your PC workstation (e.g., COM1). Connect
the DeviceNet connector on the 1770-KFD module to a DeviceNet
drop or trunk cable. You can make this connection in several ways;
for example, using a DeviceNet Quad Tap (#1492-DN3TW), as shown
on page 3-13.
For detailed directions on how to install the 1770-KFD interface
module, see the DeviceNet RS-232 Interface Module Installation
Instructions, publication 1770-5.6.
For information about See page
Installing the 1770-KFD Interface Module 3-1
Installing the PLC-5 Processor 3-2
Setting the I/O Chassis Backplane Switches 3-2
Going Online to the PLC-5 Processor 3-3
Installing the 1785-ENET Ethernet Module 3-5
Installing the 1771-SDN Scanner Module 3-7
Setting the Channel 1 Data Rate and Node Address Switches 3-8
Setting the I/O Chassis Addressing Node Switches 3-8
Installing the Scanner Module in the Chassis 3-9
Connecting the Scanner to the DeviceNet Network 3-10
Installing the RediSTATION Operator Interface 3-11
Installing the Series 9000 Photoeye 3-12
How Your Example System Will Look 3-13
to PC COM 1
1770-KFD RS-232
Interface Module
DeviceNet
Dropline or
Trunk Cable
More
Publication 1771-6.5.132 - June 2000
3-2 Hardware Setup
Installing the PLC-5
Processor
Refer to the following figure while installing your PLC-5 processor.
Setting the I/O Chassis Backplane Switches
Set the backplane switches in the 1771 I/O chassis for 1-slot
addressing for the example application. To do this, put switch 4 in the
OFF position and switch 5 in the ON position.
Switches Addressing
45
OFF OFF 2 - slot
OFF ON 1 - slot
ON OFF 1/2 - slot
ON ON Not Allowed
For information on setting the other backplane switches
for your system, refer to the ControlNet PLC-5
Programmable Controllers User Manual Phase 1.5,
publication 1785-6.5.22.
Card Guides
Battery
Battery
Battery
PLC-5/40C Processor
Lift Ejector Tab
Locking Bar
Connector
Cover
ControlNet Node Address Switches
PLC-5C Processor and 1771 I/O Chassis
DH+ Address
Switches
(on back)
12345678
O
N
O
FF
1771 I/O Chassis
ON
OFF
More
Publication 1771-6.5.132 - June 2000
Hardware Setup 3-3
Going Online to the PLC-5 Processor
You cannot go online to the PLC-5 processor over DeviceNet. In order
to download and run the example application program in chapter 6
you must use the processor’s RS-232 connector, or download and run
the program via another network.
Chapter 6 provides examples of downloading and running the
application program via ControlNet, Ethernet, and Data Highway Plus
networks. Chapter 5 provides examples of configuring the DeviceNet
network over these networks.
To go online to the PLC-5 processor via ControlNet:
1. Set the PLC-5C ControlNet node address using the two 10-digit
rotary switches on top of the PLC-5C module.
For the example application we used node address 16.
2. Connect the PLC-5C’s ControlNet port to the ControlNet network.
See Appendix B for information on installing and configuring the
ControlNet driver. See the ControlNet 1.5 PLC-5 Programmable
Controller User Manual, publication 1785-6.5.22, for further
information.
ControlNet PLC-5C processor’s NET address = 16
30
40
50
60
70
80
90
00
10 20 3
4
5
6
7
8
9
0
1 2
30
40
50
60
70
80
90
00
10 20
More
Publication 1771-6.5.132 - June 2000
3-4 Hardware Setup
To go online to the PLC-5 processor via Data Highway Plus:
1. Define the DH+ station address of channel 1A by setting switch
assembly SW-1 on the back of the processor. For the example
application we used address 1. (Set switch 4 in the up position, and
switches 1, 2, 3, 5, and 6 in the down position.)
2. Set the baud rate to 57.6 Kbaud by placing switch 7 in the up
position.
See Appendix C for information on installing and configuring the Data
Highway Plus driver.
TIP See the information on the side of the processor if
you want to use another address.
back view of processor
up
down
side view
Switch 7 in the “up” position.
Switch 4 in the “up” position
More
Publication 1771-6.5.132 - June 2000
Hardware Setup 3-5
Installing the 1785-ENET
Ethernet Module
To go online to the PLC-5 processor via Ethernet, you must install a
1785-ENET module in the 1771 I/O chassis.
The Ethernet module is shipped with a 58-pin connector header that
attaches to the PLC-5 processor.
1. Attach the connector header to the PLC-5 processor.
2. Use the captive screws to connect the interface module to the
processor.
Status Indicator
Transmit Indicator
External Transceiver
Fuse
Channel 3A:
15-pin AUI
Connector Port
IMPORTANT Make sure you carefully align the pins and holes
before you press the connector header into the
processor. If you improperly align them, you will
bend the connector header pins when you press
them together. Do not use excessive force on the
connector header when seating it into the processor.
You do not need to key the connector.
Push the exposed pins
into the holes on the
PLC-5 processor.
Attach the interface
module to this end.
Connector
Header
Publication 1771-6.5.132 - June 2000
3-6 Hardware Setup
3. Insert the interface module/processor combination in the left-most
slot of the 1771 I/O chassis.
4. Assign an IP address to the interface module.
5. Configure channel 3A for Ethernet communication.
You can configure the communication channel using BOOTP
software or your PLC-5 programming software. See Appendix A for
information on configuring the communication channel using
RSLogix 5 programming software.
For more information, see the PLC-5 Ethernet Interface Module User
Manual, publication 1785-6.5.19.
Be sure power to the
1771 I/O chassis is OFF.
!
TIP Rockwell Automation offers a BOOTP tool on
http://www.ab.com
More
Publication 1771-6.5.132 - June 2000
Hardware Setup 3-7
Installing the 1771-SDN
Scanner Module
Refer to the following figure as you install the 1771-SDN module.
Module Status Indicator - indicates
whether the device has power and is
functioning properly.
MODULE
STATUS
RESET
CHANNEL 1
NETWORK
STATUS
NODE/
ERROR CODE
DeviceNet
CHANNEL 2
DeviceNet
NETWORK
STATUS
NODE/
ERROR CODE
Channel 1 Status Indicator - gives
diagnostic indications for Channel 1.
Node Address and Status Display -
displays numeric codes that indicate
scanner node address, status and/or
errors for Channel 1.
DeviceNet Port 1 - use the color-coded
header to wire your module.
Channel 2 Status Indicator - gives
diagnostic indications for Channel 2.
Node Address and Status Display -
displays numeric codes that indicate
scanner node address, status and/or
errors for Channel 2.
DeviceNet Port 2 - use the color-coded
header to wire your module.
Reset Button - resets your module.
= ON = 1
= OFF = 0
Multi-position Switches - use to set the data rate, chassis
addressing mode, and scanner node address for each channel.
Data Rate
Switch Settings
Chassis Address
Switch Settings
Channel 1 & 2
Node Address Switch Settings
Left Side of Module
= ON = 1
= OFF = 0
12345678 12345678 12345678
ON ON
ON
Allen-Bradley
1771-SDN
Publication 1771-6.5.132 - June 2000
3-8 Hardware Setup
Setting the Channel 1 Data Rate and Node Address Switches
1. Locate the switchbank labeled “Channel 1” on the left side of the
module.
2. Set the DeviceNet Data Rate for Channel 1 to 500K baud for the
example application by setting switch 1 to an ON (“1”) position
and switch 2 to an OFF (“0”) position.
3. Set the DeviceNet node address for Channel 1 to node 0 for the
example application by setting switches 3 through 8 to the OFF
(“0”) position.
Setting the I/O Chassis Addressing Node Switches
Set the I/O chassis addressing mode to 1-slot for the example
application.
1. Locate the switchbank labeled “Configuration” on the left side of
the module.
2. Set switch 7 to an OFF (“0”) position and switch 8 to an ON (“1”)
position.
TIP Refer to the table on the left side of the module to
set the channel to a different node address. The
address range is 0 to 63.
IMPORTANT The node address setting must not conflict with the
node address of any other device on the network.
Note that channel 2 is not used for the example
application.
IMPORTANT Make sure switches 1 through 6 in the Configuration
switchbank always remain in the OFF (“0”) position.
IMPORTANT The chassis addressing mode setting for the 1771 I/O
chassis (page 3-2) must match the I/O chassis
address setting of the scanner. If the switches do not
match, data will be lost in the data transfer between
the PLC-5 processor and the scanner module.
Channel 1
= ON = 1
= OFF = 0
12345678
ON
= ON = 1
= OFF = 0
Configuration
12345678
ON
Publication 1771-6.5.132 - June 2000
Hardware Setup 3-9
Installing the Scanner Module in the Chassis
1. Select a slot for the 1771-SDN module in the chassis. You may use
any slot except the leftmost slot, which is reserved for the PLC-5
processor. For the example application, we installed the scanner in
slot 1.
2. Insert the 1771-SDN Scanner module into the slot.
Apply firm, even pressure to seat the module in the I/O chassis
backplane connectors.
ATTENTION
!
Do not install the 1771-SDN Scanner Module with the
chassis power supply on. Turn off the chassis power
supply. You will disrupt backplane communication
and may damage your module.
Publication 1771-6.5.132 - June 2000
3-10 Hardware Setup
Connecting the Scanner to the DeviceNet Network
To connect to the DeviceNet network:
1. Connect the DeviceNet drop line to the linear plug provided with
the scanner. Match the wire insulation colors to the colors shown
on the label.
2. Locate the DeviceNet port connector for Channel 1 on the front of
the module.
3. Insert the linear plug into the five-pin header for Channel 1.
ATTENTION
!
Do not wire your module with power applied to
your network. You may short circuit your network or
disrupt communication.
MODULE
STATUS
RESET
CHANNEL 1
NETWORK
STATUS
NODE/
ERROR CODE
Device
Net
CHANNEL 2
Device
Net
NETWORK
STATUS
NODE/
ERROR CODE
Front of
Scanner
Module
Module label shows
wiring color scheme
RED
WHITE
BARE
BLUE
BLACK
Dedicated DeviceNet
Drop Line
Channel 1 Port
Connector
Publication 1771-6.5.132 - June 2000
Hardware Setup 3-11
Installing the RediSTATION
Operator Interface
Begin installing the RediSTATION by removing the six screws
fastening the cover and setting the DIP switches inside as follows:
See Chapter 2 of the RediSTATION Operator Interface User Manual,
publication 2705-804, for complete information about setting the DIP
switches to configure the node address, data rate, output flash rate,
and output fault state.
Refer to the following illustration as you connect the RediSTATION to
the network.
Set this position To this value:
1
2
3
4
5
6
1On
1On
1 On (node
0 Off address1)
0Off
0Off
7
8
0 Off (data
1On rate
2)
9
10
0Off
0Off
1The DeviceNet address is 000111 (node 7).
2The data rate is 10 (500k bps).
The output fault rate is 0 (outputs turned off).
The output flash rate is 0 (outputs tuned off).
More
DeviceNet Cable
The DeviceNet cable connects directly
to the mini connector on the top of the
RediSTATION enclosure or through the
conduit opening (open style).
TIP You do not need to
disconnect incoming
power from the
DeviceNet network
before connecting
the RediSTATION.
mini
connector
open
style
Publication 1771-6.5.132 - June 2000
3-12 Hardware Setup
Installing the
Series 9000 Photoeye
Connect the photoeye to the network and configure the photoeye as
follows:
Node Address: 9
Operating Mode: Light Operate (default)
Baud Rate: 500 kb
For detailed directions, see the instructions that came with your
photoeye.
Programming
Pushbutton
Sensitivity
Adjustment
Yellow - Output
Green - Margin
Red/Green - Status
Top View of Series 9000 Photoeye
More
Publication 1771-6.5.132 - June 2000
Hardware Setup 3-13
How Your Example
System Will Look
When you have finished installing all the devices, your example
system should look similar to the one shown below:
What’s Next?
The next step is to configure the 1771-SDN module and perform I/O
data mapping using RSNetWorx for DeviceNet software.
Series 9000
Photoelectric
Sensor
RediSTATION
Operator Interface
PLC-5 Processor with 1771-SDN
module in 1771 I/O chassis
Node 7
Node 9
Node 62
1770-KFD
Communication
Module
Node 0
24V
PC Serial
Port 1492-DN3TW
Quad Tap
PC running Windows NT
or Windows 95/98,
containing RSNetWorx for
DeviceNet software
IMPORTANT Make sure each end of your DeviceNet trunk cable
is properly terminated with a resistor. Refer to the
DeviceNet Cable Planning and Installation Manual,
publication DN-6.7.2 for detailed information.
Publication 1771-6.5.132 - June 2000
3-14 Hardware Setup
1Publication 1771-6.5.132 - June 2000
Chapter
4
Configuring the DeviceNet Network
What This Chapter Contains
This chapter describes how to configure the DeviceNet network using
RSLinx and RSNetWorx for DeviceNet software. The following table
describes what this chapter contains and where to find specific
information.
Installing the Software
Install the RSLinx and RSNetWorx software.
1. Insert the CD in the CD-ROM drive.
Note: The CD-ROM supports Windows Autorun. Once inserted into
the CD-ROM drive, if you have Autorun configured, the installation
will automatically start at the first setup screen.
If Autorun is not configured for your CD-ROM drive, go to step 2.
2. From the Start menu, choose Run.
You will see the Run pop-up window.
3. Type d:/setup (if it doesn’t appear automatically), where d: is your
CD-ROM driver letter.
4. Click on OK.
You see the progress bar, followed by the welcome screen.
For information about See page
Installing the Software 4-1
Using RSLinx to Configure the DeviceNet Driver 4-2
Using RSNetWorx for DeviceNet to Configure the Scanlist 4-4
Setting Up an Online Connection 4-4
Setting the 1771-SDN Node Address 4-6
Configuring the I/O Devices 4-9
Verifying the Photoeye Configuration 4-12
Verifying the RediSTATION Configuration 4-13
AutoMapping the Devices into the Scanlist 4-14
Publication 1771-6.5.132 - June 2000
4-2 Configuring the DeviceNet Network
Using RSLinx to Configure
the DeviceNet Driver
After you install the software, you use RSLinx to configure your
DeviceNet driver and RSNetWorx for DeviceNet to configure the
network.
1. Start the RSLinx software.
2. From the Communications menu, select Configure Drivers. The
Configure Drivers window will appear.
3. From the list of Available Drivers, select DeviceNet Drivers and
click on Add/New.
You will see the following list of drivers:
4. Select the Allen-Bradley 1770-KFD driver.
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-3
The Allen-Bradley 1770-KFD Driver Configuration window will
appear.
5. Configure the driver using the example above as a guide and click
on OK. The software will take a few seconds to configure the
driver. When it is done the following prompt will appear:
6. Select the default driver name 1770-KFD-1 and click on OK.
7. Close RSLinx.
You will use the driver you just configured to browse and configure
the network with RSNetWorx for DeviceNet.
Your driver setup will vary according to your system
setup (COM port, Data Rate, Node Address). Choose
the appropriate settings for your system. We set the
DeviceNet Port Setup Data Rate to 500K for the
example application.
Publication 1771-6.5.132 - June 2000
4-4 Configuring the DeviceNet Network
Using RSNetWorx for
DeviceNet to Configure
the Scanlist
Setting Up an Online Connection
Follow the procedure below to set up an online connection to the
DeviceNet network using the 1770-KFD driver.
1. Start RSNetWorx.
2. From the File menu, select New.
If you have RSNetWorx for ControlNet installed on your computer
you may see the following window. Otherwise, proceed to step 4.
3. Highlight DeviceNet Configuration and click on OK.
4. Click on the Online button on the toolbar.
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-5
The Browse for network window will appear. You will see the
drivers you have configured on your system.
5. Select the 1770-KFD-1, DeviceNet driver and click on OK.
You will be prompted to upload or download devices before going
online.
6. Click on OK to go online and upload the network.
RSNetWorx for DeviceNet will begin browsing for network devices.
When the software is finished browsing, the network displayed on
your screen should look similar to the one shown below.
Publication 1771-6.5.132 - June 2000
4-6 Configuring the DeviceNet Network
Setting the 1771-SDN Node Address
Once the devices are uploaded, their node addresses appear to the
right of their icons. For the example application, the 1771-SDN
scanner module should have a node address of “0” (or “00”). If you
need to change a module’s node address, use the following
procedure.
If “00” appears to the right of the 1771-SDN icon and you do not need
to change the node address or baud rate of any device, skip the
remainder of this section and go to “Configuring the I/O Devices” on
page 4-9.
TIP RSNetWorx for DeviceNet performs a one-shot
browse when you go online or choose the browse
feature. The software will poll for devices once and
display the results. If a node which was online later
goes offline, there will be no “live” indication in
RSNetWorx. You must manually perform a browse to
detect the missing node.
To perform the browse, press the button.
TIP You can use this procedure to change the node
address of other devices on the network (e.g., the
Photoeye). You can also change the network data
rate (baud rate) of some devices. Power must be
cycled for baud rate changes to take effect.
IMPORTANT The network must not be active when performing
node commissioning on the 1771-SDN module. Make
sure the processor is in Program mode.
(Note that this applies only to the 1771-SDN. You
may commission other devices with the processor in
Run mode.)
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-7
To change the node address of a device perform the following steps:
1. From the Tools menu select Node Commissioning.
2. Click on the Browse button.
You will see the Device Selection window.
3. Select the 1770-KFD-1 driver.
Publication 1771-6.5.132 - June 2000
4-8 Configuring the DeviceNet Network
The devices on the network will appear in the right panel.
4. Select the device from the right panel and click on OK.
You will see the Node Commissioning window with the current
settings for the device. Your window will look similar to the one
shown below.
5. In the New Device Settings: Node Address box, enter the new
node address (e.g., a 0 as shown above).
6. Click on Apply.
7. Click on Exit to close the window.
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-9
Configuring the I/O Devices
Next you must add the RediSTATION and the photoeye to the
1771-SDN’s scanlist, configure and/or verify their parameters, and map
them to the PLC-5 processor’s memory.
1. Double-click on the 1771-SDN module icon.
The following window will appear:
2. Select the Module tab.
Publication 1771-6.5.132 - June 2000
4-10 Configuring the DeviceNet Network
You will be prompted to upload or download the configuration.
3. Click on Upload.
After uploading the Module page will appear:
4. Make sure the 1771-SDN module’s Rack and Group numbers are
correct. We used Rack 0, Group 1 for the example application.
5. Select the Scanlist tab.
TIP We used the Module Defaults for the other settings.
For an explanation of the other settings (Import
and Export, PLC Interface Address, etc.) click on
the Help button.
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-11
The Scanlist page will appear with the RediSTATION and the
photoeye in the list of Available Devices.
6. For this example, uncheck the Automap on Add box, as shown
above. You will do this mapping later.
7. Click on the double arrow button to add the photoeye and
RediSTATION to the Scanlist.
The photoeye and the RediSTATION will appear in the Scanlist in
the right panel.
8. Click on OK.
Publication 1771-6.5.132 - June 2000
4-12 Configuring the DeviceNet Network
You will be prompted to download the changes to the device (i.e.,
the scanner).
9. Click on Yes.
Verifying the Photoeye Configuration
1. Double-click on the 1771-SDN module icon and again select the
Scanlist tab.
2. Double-click on the photoeye in the Scanlist.
IMPORTANT The PLC-5 processor must be in Program mode to
download the scanlist to the 1771-SDN module.
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-13
The Edit I/O Parameters window will appear for the photoeye.
The I/O parameters define the configuration for the device in terms
of how much and what data the device will exchange with the
1771-SDN module. By default, the photoeye will send 1 byte when
it receives a strobe request. Recall from chapter 3 that the output of
the photoeye will be returned in bit 0 of that byte.
3. Verify that the photoeye parameters are set as shown above. Make
any changes as necessary and click on OK.
4. Close the Edit I/O Parameters window for the photoeye.
Verifying the RediSTATION Configuration
1. Double-click on the RediSTATION in the Scanlist window. The
Edit I/O Parameters window will appear for the RediSTATION.
2. Make sure that the Polled box is checked and that the Rx Size and
Tx Size are each 1 byte.
Publication 1771-6.5.132 - June 2000
4-14 Configuring the DeviceNet Network
3. Click on OK if you made any changes and close the Edit I/O
Parameters window for the RediSTATION.
4. Click on OK again. You will be prompted to download the changes
to the 1771-SDN module.
5. Click on Yes to download the new configuration.
AutoMapping the Devices into the Scanlist
Follow the procedure below to automatically map the photoeye and
RediSTATION to the PLC-5 processor.
1. Double-click on the 1771-SDN module icon and select the Input
tab. You will see the following window.
2. Highlight the RediSTATION and the photoeye as shown above and
click on the AutoMap button.
TIP If you want to know how to map the devices
manually, click on the Help button at the bottom of
the screen and select “Map device input data
manually”.
There are six available blocks.
Block Xfer 62 is the default.
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-15
The resulting device mapping will appear in the lower panel of the
window:
In this example, the input byte from the RediSTATION will appear
in the PLC-5 processor in file N9, word 1, as bits 0-7. Recall from
chapter 2 that the START button is bit 1 and the STOP button is bit
0. Therefore, the addresses for the RediSTATION inputs are:
START N9:1.1
STOP N9:1.0
The input byte from the photoeye will appear in the PLC-5
processor in file N9, word 1, as bits 8-15. Recall from chapter 3 that
the input bit is bit 0. Therefore, the address of the photoeye input
bit is:
N9:1.8
3. Note the addresses assigned to the START and STOP buttons
and the photoeye in your system. You will enter these addresses
in the example ladder program.
RediSTATION
inputs
Photoeye
inputs
File N9,
Word 1
Note: The source address is actually
determined by the block transfer
instruction in the ladder logic. See
chapter 6.
Publication 1771-6.5.132 - June 2000
4-16 Configuring the DeviceNet Network
4. Select the Output tab.
Highlight the RediSTATION as shown above and click on the
AutoMap button. The mapping of the RediSTATION will appear in
the lower panel.
In this example, the output to the RediSTATION appears in the
PLC-5 processor in file N10, word 1, as the lower byte (bits 0-7).
Recall from chapter 3 that the indicator light is output bit 0.
Therefore, the address for the RediSTATION’s indicator light is:
N10:1.0
5. Note the address assigned to this output in your system. You
will enter this address in the example ladder logic program.
After mapping the
RediSTATION output
address will appear
here.
File N10,
Word 1
Note: The destination address is
actually determined by the block
transfer instruction in the ladder
logic. See chapter 6.
Publication 1771-6.5.132 - June 2000
Configuring the DeviceNet Network 4-17
Download the Configuration to the Scanner
1. Click on the Scanlist tab and then on the Download to Scanner
button.
You will see this window:
2. Select Channel A (default).
Note: Both channels will download.
3. Select All Records.
4. Click on the Download button to download the configuration to
the 1771-SDN scanner module.
5. Click on the OK button to complete the DeviceNet scanner
configuration.
6. Select the Save as option from the File menu, and save the
DeviceNet configuration, using an appropriate name, e.g.,
1771-SDN.dnt.
7. Close the RSNetWorx for DeviceNet software.
What’s Next?
The next chapter describes how to configure the DeviceNet network
remotely from other networks: Ethernet, ControlNet, and Data
Highway Plus.
Publication 1771-6.5.132 - June 2000
4-18 Configuring the DeviceNet Network
1Publication 1771-6.5.132 - June 2000
Chapter
5
Communicating with DeviceNet
from Another Network
What This Chapter Contains
This chapter describes how to communicate with the DeviceNet
network from another network, using the PLC-5 “pass-through”
feature. This feature can be used to adjust and fine tune the nodes on
your network. Examples are provided for communicating from a
ControlNet network, an Ethernet network, and a Data Highway Plus
network.
You must have previously set up the network you will use to
communicate with the DeviceNet network and have installed and
configured the appropriate drivers and interface hardware. The 1771
I/O chassis used for these examples was set up with the following
hardware mapping:
ATTENTION
!
The pass-through feature is not intended to replace a
1770-KFD, PCD, PCID, or PCIDS connection to the
network:
Pass-through is intended only for fine tuning and
adjustment of your network devices. Do not
attempt to configure your entire network using a
pass-through driver, or a time-out may occur.
The pass-through method is not suitable for real
time monitoring of your network devices.
IMPORTANT To use the pass-through feature you must have the
following versions of the RSLinx software and
1771-SDN module firmware:
Module Rack Group Slot IP Address
PLC-5C/1785-ENET 0 0 0 130.130.130.2
1771-SDN 0 1 0 n/a
Component Software/Firmware Version
RSLinx software 2.10 or higher
1771-SDN module 4.003 or higher
Publication 1771-6.5.132 - June 2000
5-2 Communicating with DeviceNet from Another Network
The following table describes what this chapter contains and where to
find specific information.
Where to Find
More Information
Refer to the following publications for information on configuring
other networks:
For information about See page
Where to Find More Information 5-2
Communicating with DeviceNet from a ControlNet Network 5-3
Communicating with DeviceNet from an Ethernet Network 5-9
Communicating with DeviceNet from a DH+ Network 5-18
More
For information about: See this publication: Publication number:
the ControlNet PLC-5 processor ControlNet PLC-5 Programmable Controllers User Manual 1785-6.5.22
the Ethernet interface module PLC-5 Ethernet Interface Module User Manual 1785-6.5.19
TCP/IP protocol and networking in general Comer, Douglas E.,
Internetworking with TCP-IP, Volume 1:
Protocols and Architecture
, 2nd ed. Englewood Cliffs,
N.J.:Prentice-Hall, 1995. ISBN 0-13-216987-8.
n/a
Tannebaum, Andrew S.
Computer Networks
, 2nd ed. Englewood
Cliffs, N.J.: Prentice-Hall, 1989. ISBN 0-13-162959-
X
.
n/a
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-3
Communicating with
DeviceNet from a
ControlNet Network
Before performing this example the ControlNet network must be
configured and running. A ControlNet processor (PLC-5C) is required.
In this example the PLC-5C processor is configured as ControlNet
node 16. Use your own ControlNet PLC-5C processor’s configuration
when performing this example.
Configuring the DeviceNet Pass-Through Driver
Before you can communicate with the 1771-SDN module via the
ControlNet network, you must first configure the DeviceNet
pass-through driver (1771-SDNPT) with a ControlNet port. RSLinx,
version 2.10 or higher, is required.
To configure the ControlNet pass-through driver perform the
following steps:
1. Start RSLinx.
2. From the Communications menu, select Configure Drivers.
3. From the list of Available Driver Types select DeviceNet Drivers
and click on Add/New.
Publication 1771-6.5.132 - June 2000
5-4 Communicating with DeviceNet from Another Network
You will see the following list of drivers.
4. Select the Allen-Bradley 1771-SDNPT driver. The Driver
Configuration window will appear.
5. Select a pass-through port to be configured from the pull-down list,
e.g., Port 1.
6. Expand your installed ControlNet driver (AB_KTC-1 in the
example) and highlight your PLC-5C processor.
7. Select the 1771-SDN Backplane Address Configuration. We
used the following configuration for the example application.
8. Select the DeviceNet Channel (Channel 1 for the example
application).
Rack 0
Group 1
Slot 0
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-5
9. Click on OK.
You will see the following warning:
10. Verify that the routing information is accurate and click on the Yes
button.
You will be prompted to choose a name for the driver.
11. Enter an appropriate driver name (e.g., 1771-SDNPT-1) and click
on the OK button.
The new driver will be added to the Configured Drivers in
RSLinx. (Your list will contain the drivers you have configured.)
12. Close or Minimize RSLinx.
Publication 1771-6.5.132 - June 2000
5-6 Communicating with DeviceNet from Another Network
Communicating with the DeviceNet Network
Once you have the ControlNet pass-through driver configured, you
can use RSNetWorx for DeviceNet to communicate with the DeviceNet
network via the ControlNet network.
Perform the following steps:
1. Start RSNetWorx.
2. From the File menu, select New.
If you have RSNetWorx for ControlNet installed on your computer
you may see the following window. Otherwise, proceed to step 4.
3. Select DeviceNet Configuration and click on OK.
4. Click on the Online button on the toolbar.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-7
The Browse for network window will appear. You will see the
drivers you have configured on your system.
5. Highlight your DeviceNet pass-through driver (1771-SDNPT-1
above) and click on OK.
You will receive the following prompt:
6. Click on OK to upload the devices. RSNetWorx for DeviceNet will
begin browsing for network devices.
ATTENTION
!
Performing a pass-through browse via the
ControlNet network will take longer than browsing
using the 1770-KFD DeviceNet driver as described in
chapter 4.
Note that due to the time required, the pass-through
method is not suitable for configuring a network nor
for real time monitoring of your network devices.
Publication 1771-6.5.132 - June 2000
5-8 Communicating with DeviceNet from Another Network
When RSNetWorx for DeviceNet is finished browsing, the network
displayed on your screen should look similar to the one shown
below.
You are now communicating with the DeviceNet network via the
ControlNet network. See pages 4-6 to 4-17 of this manual for
examples of how to use RSNetWorx for DeviceNet to adjust network
parameters.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-9
Communicating with
DeviceNet from an Ethernet
Network
Before performing this example the Ethernet network must be
configured and running. A 1785-ENET module must be installed on
the PLC-5 processor and connected to the network.
See the PLC-5 Ethernet Interface Module User Manual (publication
1785-6.5.19) for more information.
Establishing Ethernet pass-through communications involves four
main steps:
1. You use RSLinx to configure the Ethernet to PLC-5 driver. This
procedure is described on pages 5-9 to 5-11.
2. You configure the 1785-ENET module’s communications channel
and download the configuration to the PLC-5 processor. This can
be done using RSLogix 5 software when you create the example
ladder program. The Ethernet channel configuration is described in
Appendix A.
3. You use RSLinx to configure the DeviceNet pass-through driver to
communicate with the 1771-SDN module via the Ethernet network.
This procedure is described on pages 5-12 to 5-15.
4. You use the pass-through driver with RSNetWorx for DeviceNet
software to adjust and tune your DeviceNet network. This
procedure is described on pages 5-15 to 5-17.
Configuring the Ethernet to PLC-5 Communications Driver
To communicate with your PLC-5 processor over an Ethernet network
you must configure the Ethernet to PLC-5 driver. Perform the
following steps to configure the driver using RSLinx software.
1. Start RSLinx.
More
Publication 1771-6.5.132 - June 2000
5-10 Communicating with DeviceNet from Another Network
2. From the Communications menu, select Configure Drivers.
3. From the list of Available Driver Types, select the Ethernet to
PLC-5/SLC-5/5820-EI driver and click on Add New.
You will be prompted to choose a name for the new driver.
4. Enter an appropriate driver name (e.g., AB_ETH-1) and click on
the OK button.
The Configure driver for Ethernet to PLC-5/SLC-5/5820-EI
window will open.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-11
5. In the IP address or hostname field, enter the IP address of the
PLC-5 processor (130.130.130.2 in this example).
6. Click on the Accept button. Then click on OK.
The new driver will be added to the list of Configured Drivers in
RSLinx. (Your list will contain the drivers you have configured.)
IMPORTANT You must configure the PLC-5’s communications
using BOOTP software or your PLC-5 programming
software (e.g., RSLogix 5) before you will be able to
communicate with the PLC-5 using this Ethernet
address. See Appendix A for information on
configuring the PLC-5’s communications using
RSLogix 5.
Publication 1771-6.5.132 - June 2000
5-12 Communicating with DeviceNet from Another Network
Configuring the DeviceNet Pass-Through Driver
Before you can communicate with the 1771-SDN module via the
Ethernet network, you must configure the DeviceNet pass-through
driver (1771-SDNPT). RSLinx, version 2.10 or higher, is required.
Connect your 1785-ENET module to your Ethernet network. Then
perform the following steps.
1. Start RSLinx.
2. From the Communications menu, select Configure Drivers.
3. From the list of Available Driver Types select DeviceNet Drivers
and click on Add/New.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-13
You will see the following list of drivers.
4. Select the Allen-Bradley 1771-SDNPT driver.
The Allen-Bradley 1771-SDNPT Driver Configuration window
will open.
5. Select a pass-through port to be configured from the pull-down list,
e.g., Port 2.
6. Expand your Ethernet driver (AB_ETH-1) and highlight your PLC-5
processor.
Publication 1771-6.5.132 - June 2000
5-14 Communicating with DeviceNet from Another Network
7. Select the 1771-SDN Backplane Address Configuration. We
used the following configuration for the example application.
8. Select the DeviceNet channel (Channel 1 for the example
application).
9. Click on OK.
You will see the following warning:
10. Verify that the routing information is accurate and click on the Yes
button.
You will be prompted to enter a name for the driver.
11. Enter an appropriate driver name (e.g., 1771-SDNPT-2) and click
on the OK button.
Rack 0
Group 1
Slot 0
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-15
The new driver will be added to the list of Configured Drivers in
RSLinx. (Your list will contain the drivers you have configured.)
12. Close or Minimize RSLinx.
Communicating with the DeviceNet Network
Once you have the Ethernet pass-through driver configured, you can
use RSNetWorx for DeviceNet to communicate with the DeviceNet
network via the Ethernet network.
Perform the following steps:
1. Start RSNetWorx.
Publication 1771-6.5.132 - June 2000
5-16 Communicating with DeviceNet from Another Network
2. From the File menu, select New.
If you have RSNetWorx for ControlNet installed on your computer
you may see the following window. Otherwise, proceed to step 4.
3. Select DeviceNet Configuration and click on OK.
4. Click on the Online button on the toolbar.
The Browse for network window will appear. You will see the
drivers you have configured on your system.
5. Highlight the 1771-SDNPT-2, DeviceNet driver and click on OK.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-17
You will receive the following prompt:
6. Click on OK to upload the devices. RSNetWorx for DeviceNet will
begin browsing for network devices.
When RSNetWorx for DeviceNet is finished browsing, the network
displayed on your screen should look similar to the one shown
below.
You are now communicating with the DeviceNet network via the
Ethernet network. See pages 4-6 to 4-17 of this manual for
examples of how to use RSNetWorx for DeviceNet to adjust
network parameters.
ATTENTION
!
Performing a pass-through browse via the Ethernet
network will take longer than browsing using the
1770-KFD DeviceNet driver as described in
chapter 4.
Note that due to the time required, the pass-through
method is not suitable for configuring a network nor
for real time monitoring of your network devices.
Publication 1771-6.5.132 - June 2000
5-18 Communicating with DeviceNet from Another Network
Communicating with
DeviceNet from a DH+
Network
Before performing this example the DH+ network must be configured
and running. In this example, the PLC-5 processor’s DH+ channel A is
configured as node 1. Use your own DH+ configuration when
performing this example.
Configuring the DeviceNet Pass-Through Driver
Before you can communicate with the 1771-SDN module via a DH+
network, you must first configure the DeviceNet pass-through driver
(1771-SDNPT) with a DH+ port. RSLinx, version 2.10 or higher, is
required.
Perform the following steps.
1. Start RSLinx.
2. From the Communications menu, select Configure Drivers.
The Configure Drivers window will appear.
3. Select DeviceNet Drivers from the Available Driver Types
pull-down list and click on Add/New.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-19
You will see the following list of drivers.
4. Select the Allen-Bradley 1771-SDNPT driver.
The Driver Configuration window will appear.
5. Select a pass-through port to be configured from the pull-down list,
e.g., Port 3.
6. Expand your DH+ driver (AB_KT-1 above) and highlight the PLC-5
processor.
7. Select the 1771-SDN Backplane Address Configuration. We
used the following configuration for the example application.
8. Select the DeviceNet Channel (Channel 1 for the example
application).
Rack 0
Group 1
Slot 0
Publication 1771-6.5.132 - June 2000
5-20 Communicating with DeviceNet from Another Network
9. Click on OK.
You will see the following warning:
10. Verify that the routing information is accurate and click on the Yes
button.
You will be prompted to enter a name for the driver.
11. Enter an appropriate driver name (e.g., 1771-SDNPT-3) and click
on the OK button.
The new driver will be added to the Configured Drivers in
RSLinx. (Your list will contain the drivers you have configured.)
12. Close or Minimize RSLinx.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-21
Communicating with the DeviceNet Network
Once you have the DH+ pass-through driver configured, you can use
RSNetWorx for DeviceNet to communicate with the DeviceNet
network via the DH+ network.
Perform the following steps:
1. Start RSNetWorx.
2. From the File menu, select New.
If you have RSNetWorx for ControlNet installed on your computer
you may see the following window. Otherwise, proceed to step 4.
3. Select DeviceNet Configuration and click on OK.
4. Click on the Online button on the toolbar.
Publication 1771-6.5.132 - June 2000
5-22 Communicating with DeviceNet from Another Network
The Browse for network window will appear. You will see the
drivers you have configured on your system.
5. Highlight the 1771-SDNPT-3 driver and click on OK.
You will receive the following prompt:
6. Click on OK to upload the devices. RSNetWorx for DeviceNet will
begin browsing for network devices.
ATTENTION
!
Performing a pass-through browse via the DH+
network will take longer than browsing using the
1770-KFD DeviceNet driver as described in
chapter 4.
Note that due to the time required, the pass-through
method is not suitable for configuring a network nor
for real time monitoring of your network devices.
Publication 1771-6.5.132 - June 2000
Communicating with DeviceNet from Another Network 5-23
When RSNetWorx for DeviceNet is finished browsing, the network
displayed on your screen should look similar to the one shown
below.
You are now online to the DeviceNet network via the Data Highway
Plus network. See pages 4-6 to 4-17 of this manual for examples of
how to use RSNetWorx for DeviceNet to adjust network parameters.
What’s Next?
The next chapter describes how to create and run the example
application program to test the DeviceNet Network.
Publication 1771-6.5.132 - June 2000
5-24 Communicating with DeviceNet from Another Network
1Publication 1771-6.5.132 - June 2000
Chapter
6
Creating and Running the Example
Application Program
What This Chapter Contains
This chapter describes the procedure to create, download, and run an
example ladder logic program to test the DeviceNet network. When
the program is put into Run mode, pressing the START button on the
network’s RediSTATION will cause the red indicator light to come on
and stay on until the STOP button is pressed. Passing an object in
front of the photoeye will increment a counter.
This chapter provides examples of downloading and running the
program over ControlNet, Ethernet, and Data Highway Plus networks.
You cannot directly communicate with the PLC-5 processor over the
DeviceNet network.
The 1771 I/O chassis used for these examples was set up with the
following hardware:
The following table describes what this chapter contains and where to
find specific information.
For more information, see Getting Results With RSLogix 5, Rockwell
Software publication 9399-RL53GR.
Module Rack Group Slot IP Address
PLC-5/1785-ENET 0 0 0 130.130.130.2
1771-SDN 0 1 0 n/a
For information about See page
Installing the Software 6-2
Creating the Example Application Program 6-2
Downloading and Running the Program 6-6
Downloading and Running the Program via a ControlNet Network 6-6
Downloading and Running the Program via an Ethernet Network 6-9
Downloading and Running the Program via a DH+ Network 6-12
More
Publication 1771-6.5.132 - June 2000
6-2 Creating and Running the Example Application Program
Installing the Software
Install the RSLogix 5 software.
1. Insert the CD in the CD-ROM drive.
Note: The CD-ROM supports Windows Autorun. Once inserted into
the CD-ROM drive, if you have Autorun configured, the installation
will automatically start at the first setup screen.
If Autorun is not configured for your CD-ROM drive, go to step 2.
2. From the Start menu, choose Run.
You will see the Run pop-up window.
3. Type d:/setup (if it doesn’t appear automatically), where d: is your
CD-ROM driver letter.
4. Click on OK.
You see the progress bar, followed by the welcome screen.
Creating the Example
Application Program
Perform the following steps to create the example application
program.
1. Start RSLogix 5.
2. From the File menu select New.
Publication 1771-6.5.132 - June 2000
Creating and Running the Example Application Program 6-3
The Select Processor Type window will open.
3. Enter the following information and click on OK.
In this field Select or Enter
Processor Name DNET_PLC
Platform ControlNet
Processor (Select your processor type)
Series (Select your processor’s series)
Revision (Enter revision letter)
Driver (Select a Driver)(1)
(1) You can use the Who Active button to select your communications driver. This is described in the
“Downloading” sections of this chapter.
Processor Node (Enter the Processor Node)(1)
TIP Ignore any prompts or warnings you receive
about specifying ControlNet project files. That is
not necessary for this example.
Publication 1771-6.5.132 - June 2000
6-4 Creating and Running the Example Application Program
4. Enter the following ladder program.
5. Save the program using an appropriate name, e.g., “DNET_PLC”.
Input data file mapped
by RSNetWorx for DeviceNet
Output data file mapped
by RSNetWorx for DeviceNet
RediSTATION Start bit
RediSTATION Stop bit
RediSTATION Indicator Light bit
Photoeye input bit
Length of 62 specifies the first
data block. See the Automapping
Length of 62 specifies the first
data block. See the Automapping
example in chapter 4.
example in chapter 4.
Publication 1771-6.5.132 - June 2000
Creating and Running the Example Application Program 6-5
See the 1771-SDN DeviceNet Scanner Module Installation Instructions
(publication 1771-5.14) for more information on using the scanner
module command register.
IMPORTANT The first word of the BTW downloaded from the
PLC-5 to block 62 is reserved as the scanner module
command register. You must set bit 0 of the
command register to “1” to place the scanner’s
DeviceNet Channel 1 in run mode. You can do this
by double-clicking on file N10 in the project window
and manually setting N10:0, bit 0 to “1” as shown
below.
Note: Set bit 2 to place Channel 2 in run mode.
More
Publication 1771-6.5.132 - June 2000
6-6 Creating and Running the Example Application Program
Downloading and Running
the Program
The remaining sections of this chapter provide examples of
downloading and running the program via the following networks:
ControlNet (page 6-6)
Ethernet (page 6-9)
Data Highway Plus (page 6-12)
Downloading and Running the Program via a ControlNet Network
Follow the procedure below to download and run the example
program via a ControlNet network.
1. Click on the RSLogix 5 Comms menu and select System
Communications.
2. Click on the Who Active button.
Publication 1771-6.5.132 - June 2000
Creating and Running the Example Application Program 6-7
RSLinx will open. You will see a window similar to the one below,
displaying your system’s driver configuration.
3. Expand the tree under your ControlNet driver and highlight the
PLC-5 processor as shown above. Click on OK.
4. Click on the Download button.
You will be asked if you want to proceed with the Download. You
will see a message similar to the one below.
5. Click on Yes to download the program.
You may be prompted to keep the existing online ControlNet
configuration.
6. Click on Yes. The program will be downloaded to the processor.
Publication 1771-6.5.132 - June 2000
6-8 Creating and Running the Example Application Program
Testing the Example Program
1. After the download is complete, go online and put the PLC-5
processor in Run mode.
2. Press and release the START button on the RediSTATION. The red
light should turn on. On your screen, you should see rung 1 in
your ladder program being energized as you press the button.
3. Pass your hand back and forth over the photoeye several times. On
your screen you should see the counter incrementing.
4. Press and release the STOP button on the RediSTATION. The red
light should turn off. On your screen, you should see rung 2 in
your ladder program being energized as you press the button.
This completes the ControlNet example.
Publication 1771-6.5.132 - June 2000
Creating and Running the Example Application Program 6-9
Downloading and Running the Program via an Ethernet Network
Follow the procedure below to download and run the example
program via an Ethernet network.
1. Click on the RSLogix 5 Comms menu and select System
Communications.
2. Click on the Who Active button.
IMPORTANT The Ethernet configuration must be downloaded to
the PLC-5 processor before performing this example.
See Appendix A.
Publication 1771-6.5.132 - June 2000
6-10 Creating and Running the Example Application Program
RSLinx will open. You will see a window similar to the one below,
displaying your system’s driver configuration.
3. Expand the tree under your Ethernet driver and highlight the PLC-5
processor as shown above. Click on OK.
4. Click on the Download button.
You will be asked if you want to proceed with the Download. You
will see a message similar to the one below.
5. Click on Yes to download the program.
You may be prompted to keep the existing online ControlNet
configuration.
6. Click on Yes. The program will be downloaded to the processor.
Publication 1771-6.5.132 - June 2000
Creating and Running the Example Application Program 6-11
Testing the Example Program
1. After the download is complete, go online and put the PLC-5
processor in Run mode.
2. Press and release the START button on the RediSTATION. The red
light should turn on. On your screen, you should see rung 1 in
your ladder program being energized as you press the button.
3. Pass your hand back and forth over the photoeye several times. On
your screen you should see the counter incrementing.
4. Press and release the STOP button on the RediSTATION. The red
light should turn off. On your screen, you should see rung 2 in
your ladder program being energized as you press the button.
This completes the Ethernet example.
Publication 1771-6.5.132 - June 2000
6-12 Creating and Running the Example Application Program
Downloading and Running the Program via a DH+ Network
Follow the procedure below to download and run the example
program via a DH+ network.
1. Click on the RSLogix 5 Comms menu and select System
Communications.
2. Click on the Who Active button.
RSLinx will open. You will see a window similar to the one below,
displaying your system’s driver configuration.
3. Expand the tree under your DH+ driver and highlight the PLC-5
processor as shown above. Click on OK.
Publication 1771-6.5.132 - June 2000
Creating and Running the Example Application Program 6-13
4. Click on the Download button.
You will be asked if you want to proceed with the Download. You
will see a message similar to the one below.
5. Click on Yes to download the program.
You may be prompted to keep the existing online ControlNet
configuration.
6. Click on Yes. The program will be downloaded to the processor.
Publication 1771-6.5.132 - June 2000
6-14 Creating and Running the Example Application Program
Testing the Example Program
1. After the download is complete, go online and put the PLC-5
processor in Run mode.
2. Press and release the START button on the RediSTATION. The red
light should turn on. On your screen, you should see rung 1 in
your ladder program being energized as you press the button.
3. Pass your hand back and forth over the photoeye several times. On
your screen you should see the counter incrementing.
4. Press and release the STOP button on the RediSTATION. The red
light should turn off. On your screen, you should see rung 2 in
your ladder program being energized as you press the button.
This completes the Data Highway Plus example.
What’s Next?
This concludes the example applications. The following chapter
describes how the diagnostic indicators on the 1771-SDN module can
be used for troubleshooting.
1Publication 1771-6.5.132 - June 2000
Chapter
7
Troubleshooting
What This Chapter Contains
This chapter describes the diagnostics provided by the LED diagnostic
indicators on the 1771-SDN module’s front panel.
Module Status Indicator
The bicolor (green/red) Module Status LED indicates whether the
1771-SDN module has power and is functioning properly.
For information about the See page
Module Status Indicator 7-1
Network Status Indicator 7-2
Node/Error Code Indicator 7-2
Module Status Indicator
If the indicator
is
Then Take this action
Off There is no power applied to the
module.
Verify power connections and
apply power.
Green The module is operating normally. No action required.
Flashing Green The module is not configured. Configure the module.
Flashing Red There is an invalid configuration. Verify DIP switch settings. Check
configuration setup.
Red The module has an unrecoverable
fault.
Replace the module.
Module Status
Indicator
Network Status
Indicator
op Part of Module
Publication 1771-6.5.132 - June 2000
7-2 Troubleshooting
Network Status Indicator
Each of the channels (1 and 2) on the 1771-SDN Scanner module has
a bicolor (green/red) network status indicator that provides
troubleshooting information about the channel’s communication links.
Node/Error Code Indicator
Each channel also has a Node/Error Code indicator that displays
numeric codes providing diagnostic information. The display flashes
at approximately one second intervals, depending on network traffic.
The following table summarizes the meanings of the numeric codes.
Network Status Indicator
If the indicator is Then Which indicates Take this action
Off The device has no power or the
channel is disabled for
communication due to a bus off
condition, loss of network power, or
it has been intentionally disabled.
The channel is disabled for DeviceNet
communication.
Power-up the module, provide network
power to the channel, and be sure the
channel is enabled in both the module
configuration table and the module
command word.
Green Normal operation. All slave devices in the scanlist table
are communicating normally with the
module.
None.
Flashing Green The two-digit numeric display for the
channel indicates an error code that
provides more information about the
condition of the channel.
The channel is enabled but no
communication is occurring.
Configure the scanlist table for the
channel to add devices.
Flashing Red The two-digit numeric display for the
channel displays an error code that
provides more information about the
condition of the channel.
At least one of the slave devices in the
module’s scanlist table has failed to
communicate with the module.
The network has faulted.
Examine the failed device and the
scanlist table for accuracy.
Red The communications channel has
failed. The two digit numeric display
for the channel displays an error
code that provides more information
about the condition of the channel.
The module may be defective. Reset the module. If failures continue,
replace module.
Numeric Display Code Summary
Numeric
Code
Description Take this action
0 - 63 Normal operation. The numeric code is
the 1771-SDN’s node address on the
DeviceNet network.
None.
70 Module failed Duplicate Node Address
check.
Change the module node address to
another available one. The node address
you selected is already in use on that
channel.
71 Illegal data in scanlist table (node
number alternately flashes).
Reconfigure the scanlist table and
remove any illegal data.
72 Slave device stopped communicating
(node number alternately flashes).
Inspect the field devices and verify
connections.
Top of Module
Node/Error Code Indicator
Publication 1771-6.5.132 - June 2000
Troubleshooting 7-3
73 Device’s identity information does not
match electronic key in scanlist table
entry (node number alternately
flashes).
Verify that the correct device is at this
node number. Make sure that the device
at the flashing node address matches
the desired electronic key (vendor,
product code, product type).
74 Data overrun on port detected. Modify your configuration and check for
invalid data. Check network
communication traffic.
75 No scanlist is active in the module. Enter a scanlist.
76 No direct network traffic for module
detected.
None. The module hears other network
communication.
77 Data size expected by the device does
not match scanlist entry (node number
alternately flashes).
Reconfigure your module for the correct
transmit and receive data size.
78 Slave device in scanlist table does not
exist (node number alternately
flashes).
Add the device to the network, or delete
the scanlist entry for that device.
79 Module has failed to transmit a
message.
Make sure that your module is
connected to a valid network. Check for
disconnected cables. Verify baud rate.
80 Module is in IDLE mode. Put PLC-5 in RUN mode. Enable RUN bit
in module command register.
81 Module is in FAULT mode. Check ladder program for cause of fault
bits.
82 Error detected in sequence of
fragmented I/O messages from device
(node number alternately flashes).
Check scanlist table entry for slave
device to make sure that input and
output data lengths are correct. Check
slave device configuration.
83 Slave device is returning error
responses when module attempts to
communicate with it (node number
alternately flashes).
Check accuracy of scanlist table entry.
Check slave device configuration. Slave
device may be in another master’s
scanlist. Reboot slave device.
84 Module is initializing the DeviceNet
channel.
None. This code clears itself once
module attempts to initialize all slave
devices on the channel.
85 Data size larger than 255 bytes (node
number alternately flashes).
Configure the device for a smaller data
size.
86 Device is producing zero length data
(idle state) while channel is in Run
Mode.
Check device configuration and slave
node status.
88 This is not an error. At power-up and
reset, the module displays all 14
segments of the node address and
status display LEDs.
None.
90 User has disabled communication port. Reconfigure your module. Check the
disable bit in the Module Command
Register.
Numeric Display Code Summary
Numeric
Code
Description Take this action
Publication 1771-6.5.132 - June 2000
7-4 Troubleshooting
91 Bus-off condition detected on comm
port. Module is detecting
communication errors.
Check DeviceNet connections and
physical media integrity. Check system
for failed slave devices or other possible
sources of network interference.
92 No network power detected on comm
port.
Provide network power. Make sure that
module drop cable is providing network
power to module comm port.
95 Application FLASH update in progress. None. Do not disconnect the module
while application FLASH is in progress.
You will lose any existing data in the
module’s memory.
97 Module halted by user command. Check ladder program for cause of fault
bits.
98 Unrecoverable firmware failure. Service or replace your module.
99 Unrecoverable hardware failure. Service or replace your module.
Numeric Display Code Summary
Numeric
Code
Description Take this action
1Publication 1771-6.5.132 - June 2000
Appendix
A
1785-ENET Module Channel Configuration
Configuring the
Communications Channel
Before you can communicate with the PLC-5 processor over an
Ethernet network, you must configure the 1785-ENET module’s
Ethernet communications channel and download the configuration to
the PLC-5 processor. The following example describes how to do this
using RSLogix 5 software.
1. Select Channel Configuration under the Controller folder in the
Project window.
The Edit Channel Properties window will open.
Publication 1771-6.5.132 - June 2000
A-2 1785-ENET Module Channel Configuration
2. Select the Channel 3A tab.
3. Select Ethernet as the Channel Type.
4. Uncheck the BOOTP Enabled box to disable BOOTP.
5. Enter the IP Address you want to assign to the PLC-5 processor
(e.g., 130.130.130.2).
6. Download the configuration to the processor, using a
communications driver that was previously configured, (e.g,
ControlNet or DH+). See chapter 6 for examples of downloading
to the PLC-5 using these drivers.
1Publication 1771-6.5.132 - June 2000
Appendix
B
Installing and Configuring the ControlNet
Communications Driver
The examples using ControlNet in this manual were performed with a
1784-KTCX15 communication interface card installed in the personal
computer that was used as a programming terminal. This appendix
describes how to install and configure the 1784-KTCX15 card.
Installing the 1784-KTCX15
Communication Interface
Card
Perform the following steps to install the 1784-KTCX15 card in your
personal computer.
1. Set the card’s base memory address location on switches S1 and S2.
2. Set the card’s base I/O space address location on switch S3.
For detailed information on
installing the 1784-KTCX15, refer
to the ControlNet Communication
Interface Card Installation
Instructions, publication number
1784-5.33.
More
D000:0000
Front of Switches
Factory-set address
(recommended setting)
up (1)
S2 S1
down (0)
Front View Side View
down (0)
up (1)
Front View Side View
down (0)
up (1)
up (1)
down (0)
S3
240h shown
(adjust for your system)
Front of Switches
Publication 1771-6.5.132 - June 2000
B-2 Installing and Configuring the ControlNet Communications Driver
These settings depend on the devices installed on your computer.
We used the following addresses:
When deciding which addresses to use, remember that each card in
your computer must have a unique base memory address and a
unique base I/O space memory address. If another card in the host
computer is using one or both of the selected addresses, you must
change the card’s switch settings to an available address.
3. Insert the card in a vacant 16- or 32-bit ISA/EISA expansion slot.
Configuring the 1784-KTCX15 Communications Driver
After installing the card in the computer, you must run RSLinx to
configure the driver.
1. Start RSLinx.
2. Select Configure Drivers from the Communications menu.
The following window will appear:
3. Select the Allen-Bradley 1784-KT/KTC(X) device from the
pull-down list and click on Add/New.
Base I/O Space Address 240
Base Memory Address D000:000 (factory default)
TIP Consult with your IT/PC support group to find out
if it is necessary to change any of your computer’s
memory address or IRQ settings.
Publication 1771-6.5.132 - June 2000
Installing and Configuring the ControlNet Communications Driver B-3
4. When prompted for a name for the new driver, select the default
name assigned by the system, i.e., AB_KTC-1.
The Configure Device window will appear:
5. Enter the following configuration:
6. Click on OK to save your settings.
7. Close RSLinx.
Station Name ABKTC
Net. Address 17(1)
(1) This is an unscheduled device. For maximum efficiency,
set its address higher than the highest scheduled
address on your network.
Interrupt None
I/O Base 240(2)
(2) Modify as necessary for your system.
Mem. Address D000( 2 )
Publication 1771-6.5.132 - June 2000
B-4 Installing and Configuring the ControlNet Communications Driver
1Publication 1771-6.5.132 - June 2000
Appendix
C
Installing and Configuring the DH+
Communications Driver
The examples using Data Highway Plus (DH+) in this manual were
performed with a 1784-KTX communication interface card installed in
the personal computer that was used as the programming terminal.
This appendix describes how to install and configure the 1784-KTX
card.
Installing the 1784-KTX
Communication Interface
Card
Perform the following steps to install the 1784-KTX card in your
personal computer. Refer to the following figure.
1. Set the interrupt jumpers on the communication card (IRQ5 in this
example).
2. Set the switches on the card (D700 in this example).
3. Insert the communication interface card into a vacant 16-bit ISA or
EISA expansion slot and tighten the screw to secure the card.
For more information, see the
KTX Communication Interface
Card User Manual, publication
number 1784-6.5.22.
More
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
3
4
5
7
9
10
11
12
15
CH2 CH1
D7
KTX Card
CH1
SW3 SW4
(shown in IRQ5 position)
SW3 SW4
Channel 1 Address
shown in D700:
position
Publication 1771-6.5.132 - June 2000
C-2 Installing and Configuring the DH+ Communications Driver
Configuring the 1784-KTX
Communications Driver
After installing the card in the computer, you must run RSLinx to
configure the communications driver.
1. Start the RSLinx software.
2. From the Communications menu select Configure Drivers.
The Configure Drivers window will appear:
3. From the list of Available Drivers, select the
1784-KT/KTX(D)/PKTX(D) driver from the pull-down list and
click on Add/New.
4. When prompted for a name for the new driver, select the default
name assigned by the system, AB_KT-1.
The device’s configuration window will open:
Publication 1771-6.5.132 - June 2000
Installing and Configuring the DH+ Communications Driver C-3
5. Enter the following configuration:
6. Click on OK to save your settings.
7. Close RSLinx.
Device Type KTX(D)
Network DH+
Station Name RSLinx
Station Number 0
Board Address D700
Interrupt(1)
(1) Must match switch settings on card
None
DH+ Speed 57.6K
Publication 1771-6.5.132 - June 2000
C-4 Installing and Configuring the DH+ Communications Driver
1Publication 1771-6.5.132 - June 2000
Appendix
D
Data Map Example
This appendix describes a basic mapping example that connects two
DeviceNet networks (channels A and B of the 1771-SDN scanner) to
62 simple sensor-type devices. Each device sends one data byte that
contains one data bit and one status bit.
These are given in response to a strobe message. With channel A
only, the scanner maps this data to the discrete I/O table if it is
available; otherwise, the data is mapped to block transfer locations.
See the 1771-SDN DeviceNet Scanner Installation Instructions (pub.
no. 1771-5.14) for details on using block transfer read and write
operations to communicate between your PLC-5 processor and
1771-SDN scanner.
Example Input
Mapping Scheme
This example’s input mapping scheme is a simplified and fixed map
of discrete input data and status bits for DeviceNet devices. It is
mapped to discrete inputs and the device input data table. An
example for each slot-addressing mode is given.
Example Characteristics
strobe is used to query DeviceNet devices
poll is disabled
Devicenet A and B ports are connected to separate networks
the input data bit is fixed and occupies the lowest-order bit in
the lowest-order byte of the strobe (bit #0)
one bit of status data is accepted from each node responding to
the strobe
the status data bit is fixed and occupies the next lowest-order bit
in the next lowest-order byte (after the input data bit) of the
strobe (i.e., bit #1)
input and status data bits accepted from each node are mapped
to discrete inputs and the device input data table of the scanner
input and status data bits accepted from each node are fixed and
predefined
More
Publication 1771-6.5.132 - June 2000
D-2 Data Map Example
Example Framework
Based on the backplane addressing mode and the scanner’s block
transfer support, the following number of discrete inputs are
supported.
This example adheres to the following structure:
only one master scanner can own a device; there may, however,
be multiple masters on a network
interface nodes (KFDs, PCDs, etc.) should be assigned node
numbers 62, 61, 60, etc.
node number 63 should always be left available to add a new
default device
address 0 is normally used for the scanner. Scanners in
multi-scanner networks are numbered 0, 1, 2, etc.
the first word in the device input data table contains the module
command word (this is applicable under any mapping scheme)
input data and status bits received from nodes 1-62 on channel
A are mapped to both the discrete inputs and the device input
data table
no discrete inputs are used for channel B
the device input data table is segmented
one word for the module status word
four words each for channel A and B devices’ input data bits
four words each for channel A and B devices’ status data bits
Addressing Mode Discrete Inputs
2-slot 0
1-slot 8
1/2-slot 24
Publication 1771-6.5.132 - June 2000
Data Map Example D-3
Input Data Table Formats
The manner in which bits are mapped to the input data table depends
on the address density used. The following example is a 2-slot
configuration. Note that discrete mapping is not possible in 2-slot mode.
node #1 1 byte
S D
node #2 1 byte
S D
node #1 1 byte
S D
node #2 1 byte
S D
Channel A
Channel B
to node #62
to node #62
Module Status
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
15 0
2D 1D
79
95
143
159
206
222
270
81 80
2D 1D
145 144
2S 1S
208 207
2S 1S
Input Data Bits from Channel A Devices
bits 16-79
bits 80-143
Input Data Bits from Channel B Devices
bits 144-206
Status Bits from Channel A Devices
Status Bits from Channel B Devices
bits 207-270
word 0
word 1
word 2
word 3
word 4
word 5
word 6
word 7
word 8
word 9
word 10
word 11
word 12
word 13
word 14
word 15
word 16
Bit numbering in the data table is right
to left, beginning with zero.
Note: 1 word = 2 bytes
1 byte = 8 bits
Each devices status and data bits are mapped into
the device input data table. Data bits from devices
on channel A are mapped into the first four words
after the module status word in ascending,
numeric order according to the device’s node
address. For example, node #1 is mapped then
node #2, #3, #4, and so on.
Input data bits from channel B as well as status
bits from channels A and B are mapped into
similar four-word groups. These bits are also
ordered by node address in ascending numeric
order.
Device Input
208 207
2S 1S
Note:
D = data bit
S = status bit
1D & 1S = data and
status bits for node #1
2D & 2S = data and
status bits for node #2
Publication 1771-6.5.132 - June 2000
D-4 Data Map Example
In 1-slot addressing mode eight bits are available for discrete input
mapping, as shown below.
node #1 1 byte
S D
node #2 1 byte
S D
node #1 1 byte
S D
node #2 1 byte
S D
Channel A
Channel B
to node #62
to node #62
Module Status
39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24
15 0
79
95
143
159
206
222
270
81 80
2D 1D
145 144
2S 1S
208 207
2S 1S
Input Data Bits from Channel A Devices
bits 24-79
bits 80-143
Input Data Bits from Channel B Devices
bits 144-206
Status Bits from Channel A Devices
Status Bits from Channel B Devices
bits 207-270
word 0
word 1
word 2
word 3
word 4
word 5
word 6
word 7
word 8
word 9
word 10
word 11
word 12
word 13
word 14
word 15
word 16
Bit numbering in the data table is right
to left, beginning with zero.
In 1-slot addressing, the first eight bits
after the module status word are used for
the input image table. This table is for
discrete input bits. Data bits for node
addresses 1-8 are mapped to this area in
ascending numeric order according to
node address.
Device Input
208 207
2S 1S
N
ote: 1 wor
d
= 2
b
ytes
1 byte = 8 bits
Input Image Table
23 22 21 20 19 18 17 16
2D 1D
(for discrete input data bits)
Note:
D = data bit
S = status bit
1D & 1S = data and
status bits for node #1
2D & 2S = data and
status bits for node #2
Publication 1771-6.5.132 - June 2000
Data Map Example D-5
In 1/2-slot addressing 24 bits are available for discrete input mapping,
as shown below.
node #1 1 byte
S D
node #2 1 byte
S D
node #1 1 byte
S D
node #2 1 byte
S D
Channel A
Channel B
to node #62
to node #62
Module Status
55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40
15 0
79
95
143
159
206
222
270
81 80
2D 1D
145 144
2S 1S
208 207
2S 1S
Input Data Bits from Channel A Devices
bits 40-79
bits 80-143
Input Data Bits from Channel B Devices
bits 144-206
Status Bits from Channel A Devices
Status Bits from Channel B Devices
bits 207-270
word 0
word 1
word 2
word 3
word 4
word 5
word 6
word 7
word 8
word 9
word 10
word 11
word 12
word 13
word 14
word 15
word 16
Bit numbering in the data table is right
to left, beginning with zero.
In 1/2-slot addressing, the first 24 bits after the
module status word are used for the input
image table. This table is for discrete input bits.
Data bits for channel A node addresses 1-24 are
mapped to this area in ascending numeric order
according to node address
Device Input
Note:
D = data bit
S = status bit
1D & 1S = data and
status bits for node #1
2D & 2S = data and
status bits for node #2
208 207
2S 1S
N
ote: 1 wor
d
= 2
b
ytes
1 byte = 8 bits
Input Image Table
23 22 21 20 19 18 17 16
2D 1D
(for discrete input data bits)
39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24
Publication 1771-6.5.132 - June 2000
D-6 Data Map Example
Example Output
Mapping Scheme
This example’s output mapping scheme is a simplified and fixed map
of the discrete outputs and data from the device output data table to
DeviceNet devices.
Devices present in the default database are strobed only; therefore,
the output data map bits are mapped into each network’s strobe
message. If the discrete table is available, it serves as a source for the
strobe bits; otherwise, the source is found in block transfer locations.
Example Characteristics
strobe is used to send output to the DeviceNet devices
poll is disabled
DeviceNet A and B ports are connected to separate networks
one output data bit each is sent to nodes 1-62 on channel A
the output data bits are embedded in the 8 byte (64 bit) data
portion of the DeviceNet strobe message
the output bit string source within the strobe message is divided
across the discrete outputs (if any) assigned to the scanner and
the device output data table
Example Framework
Based on the backplane addressing mode and the scanner’s block
transfer support, the following number of discrete outputs are
supported:
This example adheres to the following structure:
when a 1771-SDN scanner is running this configuration, there
cannot be any other 1771-SDN scanner on that network
DeviceNet devices may reside only at nodes 1-62
address 0 must be used for the scanner
the first word in the device output data table contains the
module command word (this is applicable under any mapping
scheme)
output bits intended for nodes 1-62 on channel A are mapped to
both the discrete outputs and the device output data table
no discrete outputs are used for channel B
Addressing Mode Discrete Outputs
2-slot 0
1-slot 8
1/2-slot 24
Publication 1771-6.5.132 - June 2000
Data Map Example D-7
Output Data Table Formats
The following illustrates an output data mapping scheme example for
a scanner in 2-slot addressing mode.
Module Status
31
15 0
79
95
125
N45
143
80
N1
word 0
word 1
word 2
word 3
word 4
word 5
word 6
word 7
word 8
In 2-slot addressing mode, the output bits
for channel A and channel B devices are
written to the scanner’s output data table.
The bits are stored in ascending numeric
order, according to node address. The
mapping begins with channel A devices at
bit 16 of the table.
There are 64 possible node addresses per
network. Channel A devices fill the first
four words (after the module status word).
Channel B devices fill the last four words
of the table.
Note: 1 word = 2 bytes
1 byte = 8 bits 16
N1
bit number
node number
N1 = node #1
16
N1
Output Data Strobe Message channel A
Output Data Strobe Message channel B
63 - - - - - - - - - - - - - - - - - - - - - - - - - 23 - - - - - - - - - - - - - - - 1 0
N23 N1
63 - - - - - - - - - - - 45 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1 0
N45 N1
Bit numbering in the data table is
right to left, beginning with zero.
Each node’s output bit is mapped to a bit number in the
strobe message that directly corresponds to that
particular node’s MAC ID. For example, the output bit
for node #23 is mapped to strobe bit #23.
Bit numbering in the data table is
right to left, beginning with zero.
Channel B
Channel A
The scanner takes the output bits from its
output data table and organizes them into a
strobe message. The strobe message
contains one bit for each node address,
0-63. In default mode, the scanner is node
63; therefore, this bit is empty. The scanner
sends a separate strobe message to each
network, via channel A and channel B.
39
N23
Publication 1771-6.5.132 - June 2000
D-8 Data Map Example
The following is an output data mapping scheme example for a
scanner in 1-slot addressing mode.
Module Status
39
15 0
79
95
125
N45
143
80
N1
word 0
word 1
word 2
word 3
word 4
word 5
word 6
word 7
word 8
In 1-slot addressing mode, eight bits of the
output data table are used for the output
image table. The image table is for
discrete output bits. In the default mode,
the processor writes the output bits of the
first eight nodes to the output image table
via DIO. The output bits from the remaining
nodes are written to the output data table.
Note that the output image table begins
with bit #16, where the output bit for node
#1 (MAC ID 1) is written. The output data
table now begins with bit #40, where the
output bit for node #25 (MAC ID 25) is
written.
Note: 1 word = 2 bytes
1 byte = 8 bits
Output Image Table
23 22 21 20 19 18 17 16
N1
(for discrete output data bits)
16
N1
bit number
node number
N1 = node #1
24
N9
Output Data Strobe Message channel A
Output Data Strobe Message channel B
63 - - - - - - - - - - - - - - - - - - - - - - - - - 23 - - - - - - - - - - - - - - - 1 0
N23 N1
63 - - - - - - - - - - - 45 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1 0
N45 N1
Bit numbering in the data table is
right to left, beginning with zero.
Each node’s output bit is mapped to a bit number in the
strobe message that directly corresponds to that
particular node’s MAC ID. For example, the output bit
for node #23 is mapped to strobe bit #23.
Bit numbering in the data table is
right to left, beginning with zero.
Channel B
Channel A
The scanner takes the output bits from its
output data table and organizes them into a
strobe message. The strobe message
contains one bit for each node address,
0-63. In default mode, the scanner is node
0; therefore, this bit is empty. The scanner
sends a separate strobe message to each
network, via channel A and channel B.
Publication 1771-6.5.132 - June 2000
Data Map Example D-9
The following is an output data mapping scheme example for a
scanner in 1/2-slot addressing mode.
Module Status
55
15 0
79
95
125
N45
143
80
N1
word 0
word 1
word 2
word 3
word 4
word 5
word 6
word 7
word 8
In 1/2-slot addressing mode, 24 bits of the
output data table are used for the output
image table. The image table is for
discrete output bits. In the default mode,
the processor writes the output bits of the
first 24 nodes to the output image table via
DIO. The output bits from the remaining
nodes are written to the output data table.
Note that the output image table begins
with bit #16, where the output bit for node
#1 (MAC ID 1) is written. The output data
table now begins with bit #40, where the
output bit for node #25 (MAC ID 25) is
written.
The scanner takes the output bits from its
output data table and organizes them into
a strobe message. The strobe message
contains one bit for each node address,
0-63. In default mode, the scanner is node
0; therefore, this bit is empty. The scanner
sends a separate strobe message to each
network, via channel A and channel B.
Note: 1 word = 2 bytes
1 byte = 8 bits
Output Image Table
23 22 21 20 19 18 17 16
N1
(for discrete output data bits)
39 38 37 36 35 34 33 32
N23
31 30 29 28 27 26 25 24
16
N1
bit number
node number
N1 = node #1
40
N25
Output Data Strobe Message channel A
Output Data Strobe Message channel B
63 - - - - - - - - - - - - - - - - - - - - - - - - - 23 - - - - - - - - - - - - - - - 1 0
N23 N1
63 - - - - - - - - - - - 45 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 1 0
N45 N1
Bit numbering in the data table is
right to left, beginning with zero.
Each node’s output bit is mapped to a bit number in the
strobe message that directly corresponds to that
particular node’s MAC ID. For example, the output bit
for node #23 is mapped to strobe bit #23.
Bit numbering in the data table is
right to left, beginning with zero.
Channel B
Channel A
Publication 1771-6.5.132 - June 2000
D-10 Data Map Example
Publication 1771-6.5.132 - June 2000
Index
A
about this user manual P-1 to P-7
audience P-2
automapping 4-14 to 4-17
B
before you begin 1-1 to 1-11
block transfer read 2-5, 2-8
block transfer read (BTR) 1-7
block transfer write 2-6
block transfer write (BTW) 1-7
C
change of state message 1-6
common techniques used in this manual P-4
communicating with DeviceNet from another network
5-1 to 5-23
ControlNet 5-3 to 5-8
pass-through driver 5-3 to 5-5
Data Highway Plus (DH+) 5-18 to 5-23
pass-through driver 5-18 to 5-20
Ethernet 5-9 to 5-17
Ethernet PLC-5 driver 5-9 to 5-11
pass-through driver 5-12 to 5-15
where to find more information 5-2
configuring the DeviceNet network 4-1 to 4-17
automapping 4-14 to 4-17
I/O devices 4-9 to 4-17
photoeye 4-12 to 4-13
photoeye 4-12 to 4-17
verifying photoeye configuration 4-12
RediSTATION 4-13 to 4-17
verifying RediSTATION configuration 4-13 to 4-14
scanlist configuration 4-9 to 4-17
setting the 1771-SDN node address 4-6 to 4-8
setting up an online connection 4-4 to 4-6
software installation 4-1
using RSLinx 4-2 to 4-3
using RSNetworx for DeviceNet 4-4 to 4-17
cyclic message 1-6
D
data map example D-1 to D-10
example input mapping scheme D-1 to D-5
example characteristics D-1
example framework D-2
input data table formats D-3 to D-5
example output mapping scheme D-6 to D-9
example characteristics D-6
example framework D-6
output data table formats D-7 to D-9
data mapping your devices 2-1 to 2-9
photoeye input data mapping 2-7 to 2-8
block transfer read 2-8
RediSTATION data mapping 2-4 to 2-9
block transfer read 2-5
block transfer write 2-6
data tables
scanlist table (SLT) 1-8
scanner configuration table (SCT) 1-8
DeviceNet driver 1770-KFD
configuring 4-2 to 4-3
E
ENET module channel configuration A-1 to A-2
example application
example network 2-2 to 2-9, 3-13
system components P-3
example application program 6-1 to 6-14
creating the program 6-2 to 6-4
downloading and running the program 6-6 to 6-14
via ControlNet 6-6 to 6-8
via Data Highway Plus 6-12 to 6-14
via Ethernet 6-9 to 6-11
installing the software 6-2
G
going online to the PLC-5 processor 3-3 to 3-6
via ControlNet 3-3, 6-6 to 6-8
via Data Highway Plus 3-4, 6-12 to 6-14
via Ethernet 3-5 to 3-6, 6-9 to 6-11
H
hardware setup 3-1 to 3-13
1770-KFD module 3-1
1771-SDN module 3-7 to 3-10
connecting to the network 3-10
installing in the chassis 3-9
setting data rate & node address switches 3-8
setting I/O chassis address switches 3-8
1785-ENET Ethernet module 3-5 to 3-6
photoeye 3-12
PLC-5 processor 3-2
RediSTATION 3-11
Publication 1771-6.5.132 - June 2000
2 Index
setting the I/O chassis backplane switches 3-2
help
Rockwell Automation support P-7
how your network will look 3-13
I
input data definition 1-6
input data file 2-5, 2-8
installation
see
hardware setup
Installing and configuring ControlNet communications
driver B-1 to B-3
1784-KTCX15 card B-1 to B-2
configuring communications B-2 to B-3
installing and configuring DH+ driver C-1 to C-3
1784-KTX card C-1
configuring communications C-2 to C-3
L
ladder logic program
see
example application program
O
output data definition 1-6
output data file 2-6
P
pass-through driver
see
communicating with DeviceNet from another
network
photoeye
data mapping 2-7 to 2-8
installation 3-12
scanlist configuration 4-12 to 4-17
planning your configuration 2-1 to 2-9
beginning the process 2-1
what you need to know 2-1
poll message 1-6
Q
questions or comments about manual P-7
R
RediSTATION
data mapping 2-4 to 2-9
DIP switch setting 3-11
installation 3-11
scanlist configuration 4-13 to 4-17
Rockwell Automation support P-7
RSLinx
configuring the DeviceNet driver 4-2 to 4-3
installation 4-1
RSLogix5 software installation 6-2
RSNetWorx
installation 4-1
RSNetWorx for DeviceNet
as a configuration tool 1-9
configuration screen map 1-10
configuring the DeviceNet network 4-4 to 4-17
S
scanlist configuration 4-9 to 4-17
scanner module data tables 1-8 to 1-9
scanner module functions 1-2
software installation 4-1
support and technical assistance P-7
system components P-3
T
terminology P-6
troubleshooting 7-1 to 7-4
module status indicator 7-1
network status indicator 7-2
node/error code indicator 7-2 to 7-4
typical network configuration 1-2
W
what you need to know 1-1
what your 1771-SDN module does 1-2 to 1-6
where to find more information P-5
Publication 1771-6.5.132 - June 2000 955134-57
Allen-Bradley
Publication Problem Report
If you find a problem with our documentation, please complete and return this form.
Pub. Name PLC-5 DeviceNet Scanner Module User Manual
Cat. No. 1771-SDN Pub. No. 1771-6.5.132 Pub. Date June 2000 Part No. 955134-57
Check Problem(s) Type: Describe Problem(s) Internal Use Only
Technical Accuracy t e xt illustration
Completeness procedure/step illustration definition info in manual
What information is missing? example guideline feature (accessibility)
explanation other info not in
Clarity
What is unclear?
Sequence
What is not in the right order?
Other Comments
Use back for more comments.
Your Name Location/Phone
Return to: Marketing Communications, Allen-Bradley., 1 Allen-Bradley Drive, Mayfield Hts., OH 44124-6118Phone: (440) 646-3176
FAX: (440) 646-4320
Other Comments
PLEASE FOLD HERE
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
BUSINESS REPLY MAIL
FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE
1 ALLEN BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
()
PLEASE REMOVE
Publication 1771-6.5.132 - June 2000 2PN 955134-57
Supersedes Publication 1771-6.5.118 - May 1997 © 2000 Rockwell International Corporation. Printed in the U.S.A.
Back Cover
PLC-5 DeviceNet Scanner Module User Manua
l

Navigation menu