Rotork Controls P3W-001 Pakscan 3 Wireless Field Control Unit User Manual Manual pt2
Rotork Controls Ltd Pakscan 3 Wireless Field Control Unit Manual pt2
Contents
- 1. Manual pt1
- 2. Manual pt2
- 3. Antenna Information
Manual pt2
P3 - Pakscan Master Station Technical Manual Publication PUB059-002-00 Issue 05/12 P3 - Pakscan Master Station Technical Manual KNOW YOUR MASTER STATION These modules not fitted on single master stations Optional Optional Current Loop Current Loop Module Module Optional Optional Key Switch and Wireless Wireless LTD Module Module Module A side P3 CPU Main Module Pakscan P3 Wireless IIE Loop Keyswitch IIE Loop Comms PS700 rotork rotork CPU/PSU PS720 rotork rotork Option 1 Port A Port B PS720 PS721 rotork rotork rotork Switch Option 2 Port 3 Port 4 rotork CPU/PSU Current Loop Connection Terminals (Single Master Only) Status Pri/Stby Power Alarm Port 1 Port 2 Host Comms Serial Ports for B master station Current Loop Connection Terminals Host Ethernet Ports for B master station Port 3 Port 4 12345 Power Connector Option 1 PS710 Host Comms Serial Ports for A master station Alarm and ESD Host Ethernet Terminals Ports for A Connection to master station wireless module Pakscan PS730 Option 2 CЄ Port 2 Main Chassis 2 of 134 Auto Port B PS721 Port 1 Standby Port A Status Pri/Stby Power Alarm P3 Wireless Comms Standby PS710 B side P3 CPU Main Module View from below Publication PUB059-002-00 Alarm and ESD Terminals 12345 Power Connector Issue 05/12 Contents CONTENTS: KNOW YOUR MASTER STATION .............................................................................2 TABLE OF FIGURES:.................................................................................................5 INTRODUCTION .........................................................................................................7 1. MOUNTING AND CONNECTING THE MASTER STATION ..............................9 1.1 Mechanical Fixing ................................................................................................................ 9 1.2 Host Serial Communications Connections ....................................................................... 12 1.3 Ethernet Communications Connections ........................................................................... 12 1.4 Power Connector and Fuses ............................................................................................. 12 1.5 Alarm and Hardwired ESD Connector ............................................................................... 13 1.6 Current Loop Connections ................................................................................................ 13 1.7 Wireless Coordinator Connections ................................................................................... 14 1.8 Wireless Repeater and WMA AC Power Connections ...................................................... 15 1.9 WMA (Wireless Modbus Adapter) 24VDC Connections.................................................... 16 1.10 WMA (Wireless Modbus Adapter) Modbus Connections................................................ 16 1.11 Setting up the Wireless Repeater and WMA ................................................................... 17 1.12 Front Panel LEDs ............................................................................................................. 20 2. THE FIELD CURRENT LOOP NETWORK.......................................................21 2.1 Loop Checks....................................................................................................................... 22 2.2 Connecting Up.................................................................................................................... 23 3. THE FIELD WIRELESS NETWORK.................................................................25 3.1 Wireless Site Survey .......................................................................................................... 26 3.2 Wireless Specification ....................................................................................................... 26 3.3 Connecting Up.................................................................................................................... 26 4. CONFIGURING SERIAL COMMUNICATIONS ................................................29 4.1 Setting Port 1 and 2 for RS-232 or RS-485 ........................................................................ 29 5. CONFIGURING ETHERNET COMMUNICATIONS ..........................................33 5.1 Default Ethernet Settings ................................................................................................... 34 5.2 Ethernet Security................................................................................................................ 35 6. SETTING UP THE MASTER STATION BY THE KEYPAD ..............................37 6.1 Using the Keypad ............................................................................................................... 37 6.2 The Screen Display ............................................................................................................ 38 6.3 Setting the Current Loop Option Module Parameters ...................................................... 39 Issue 05/12 Publication PUB059-002-00 3 of 134 P3 - Pakscan Master Station Technical Manual 6.4 Setting the Wireless Option Module Parameters .............................................................. 43 6.5 Setting the Master Host Communications Parameters..................................................... 45 6.6 The Other Settings ............................................................................................................. 47 6.6.1 Security .......................................................................................................... 47 6.6.2 ESD ............................................................................................................... 47 6.6.3 Date and Time................................................................................................ 47 6.6.4 Master Station Parameters ............................................................................. 48 7. INTERNAL WEB PAGES .................................................................................49 7.1 7.2 7.3 7.4 Making an Internet / Intranet Connection .......................................................................... 49 Connecting a Computer Directly to the Master Station .................................................... 50 Adjusting the Network Settings of the Computer ............................................................. 50 Web Page Structure ........................................................................................................... 52 7.4.1 User Levels .................................................................................................... 52 7.4.2 Overview of Web Page Layout........................................................................ 52 7.5 The Web Pages in Detail .................................................................................................... 54 7.5.1 Log In Screen ................................................................................................. 54 7.5.2 Master Station ................................................................................................ 55 7.5.3 View Configuration ......................................................................................... 57 7.5.4 System Diagnostics ........................................................................................ 58 7.5.5 Master Station Data Logger [ms datalogger] ................................................... 60 7.5.6 Master Station Host Analyser [host analyser] .................................................. 62 7.5.7 Pakscan 2 Loop Diagnostics [diagnostics] ...................................................... 63 7.5.8 Pakscan Wireless Diagnostics [diagnostics] .................................................... 66 7.5.9 Pakscan 2 Loop Option Module Event Logger [Event Log] .............................. 68 7.5.10 Pakscan Wireless Option Module Event Logger [Event Log] ........................... 69 7.5.11 FCU Menu...................................................................................................... 70 7.5.12 FCU Control – IQ / IQT Actuator ..................................................................... 71 7.5.13 FCU Control - Integral Actuator (2-wire loop only) ........................................... 80 7.5.14 FCU Control - General Purpose Field Control Unit (2-wire loop only) .............. 84 7.5.15 Admin............................................................................................................. 88 7.5.16 Users ............................................................................................................. 88 7.5.17 Master station Configuration ........................................................................... 91 7.5.18 Host Port Configuration ................................................................................ 100 7.5.19 Alarms.......................................................................................................... 105 7.5.20 Time............................................................................................................. 107 7.5.21 General ........................................................................................................ 108 7.5.22 Network ........................................................................................................ 109 7.6 Setting Up the Master station Configuration Using the Web Pages .............................. 111 7.6.1 Masterstation Config - Modbus Address ....................................................... 111 7.6.2 Masterstation Config - Pakscan 2 Current loop option ................................... 111 7.6.3 Masterstation Config - Pakscan 3 Wireless option......................................... 112 7.6.4 Host port settings ......................................................................................... 112 7.6.5 Network IP address settings ......................................................................... 113 8. MAKING THE SYSTEM WORK ..................................................................... 115 8.1 Commissioning the Wired System .................................................................................. 115 8.2 Commissioning the Wireless network............................................................................. 116 4 of 134 Publication PUB059-002-00 Issue 05/12 Contents 8.3 Monitoring and Controlling the Actuators from the HMI or web pages ......................... 117 9. LONG TERM DATALOGGER (LTD) .............................................................. 119 9.1 Removing the memory card and copying data ............................................................... 120 9.2 Viewing the data with the LTD Viewer software .............................................................. 122 9.2.1 Messages..................................................................................................... 123 9.2.2 Messages – Filter Options ............................................................................ 123 9.2.3 Reports ........................................................................................................ 126 9.2.4 FCU Data ..................................................................................................... 127 10. RESETTING THE MASTER STATION TO DEFAULT VALUES.................... 128 10. REPLACING THE P3 MASTER STATION BATTERY ................................... 130 GENERAL SAFETY INFORMATION ...................................................................... 131 TABLE OF FIGURES: Fig 1: The Pakscan 3 Single Master Station – option: Current loop ............................................7 Fig 2: The Pakscan 3 Hot Standby Master Station - option: Current loop ...................................7 Fig 3: The Pakscan 3 Single Master Station – option: Wireless..................................................8 Fig 4: The Pakscan 3 Hot Standby Master Station – option: Wireless ........................................8 Fig 5: The Pakscan 3 Wireless master station coordinator – PS722...........................................8 Fig 6: Pakscan 3 surface mounting dimensions. ........................................................................9 Fig 7: Pakscan 3, 19-inch rack mounting dimensions............................................................... 10 Fig 8: View below the Pakscan P3 master station showing the Connectors ............................. 10 Fig 9: Wireless co-ordinator WMA and Repeater mounting details ........................................... 11 Fig 10: Serial Communication connections ................................................................................ 12 Fig 11: PS710 CPU module connector terminal functions .......................................................... 13 Fig 12: PS720/PS730/PS731/PS732 Current Loop connections ................................................ 13 Fig 13: PS721 to PS722 connections (Master station to Wireless Coordinator) .......................... 14 Fig 14: Power module for Wireless Repeater and WMA. ........................................................... 15 Fig 15: PS721 to PS722 connections (Master station to Wireless Coordinator) .......................... 16 Fig 16: Wireless Repeater and WMA database ......................................................................... 18 Fig 17: Wireless Repeater and WMA database ......................................................................... 19 Fig 18: CPU LEDs (Light Emitting Diodes) ................................................................................ 20 Fig 19: Pakscan P3 Wired Network ........................................................................................... 21 Fig 20: Pakscan P3 Current Wired Loop System Block Diagram (hot standby master station).......... 23 Fig 21: Pakscan P3 Current Wired Loop System Block Diagram (single master station) ................... 24 Fig 22: A typical P3 wireless network ........................................................................................ 25 Fig 23: Pakscan P3 Wireless network Block Diagram (hot standby master station) .................... 27 Fig 24: Pakscan P3 Chassis, CPU and Key Switch modules removed....................................... 29 Fig 25: Port Function Switches shown in RS-232 position ......................................................... 30 Fig 26: Port Termination Switches shown in Off position............................................................ 30 Fig 27: Cross connection switch settings on the backplane behind the Switch Module ............... 31 Fig 28: Hot Standby Serial Communications.............................................................................. 32 Fig 29: Hot Standby Ethernet Communications ......................................................................... 33 Fig 30: Hot Standby, Dual Redundant Ethernet Communications .............................................. 34 Fig 31: Pakscan P3 Main module connection to laptop and keypad detail .................................. 37 Fig 32: Connecting a Laptop to the Pakscan P3 Main Module ................................................... 50 Issue 05/12 Publication PUB059-002-00 5 of 134 P3 - Pakscan Master Station Technical Manual Fig 33: Fig 34: Fig 35: Fig 36: Fig 37: Fig 38: Fig 39: Fig 40: Fig 41: Fig 42: Fig 43: Fig 44: Fig 45: Fig 46: Fig 47: Fig 48: Fig 49: Fig 50: Fig 51: Fig 52: Fig 53: Fig 54: Fig 55: Fig 56: Fig 57: Fig 58: Fig 59: Fig 60: Fig 61: Fig 62: Fig 63: Fig 64: Fig 65: Fig 66: Fig 67: Fig 68: Fig 69: Fig 70: Fig 71: Fig 72: Fig 73: Fig 74: Fig 75: Fig 76: Fig 77: Fig 78: Fig 79: Fig 80: Fig 81: Fig 82: Fig 83: Fig 84: 6 of 134 Changing the Network Connections TCP/IP Properties – Windows XP .......................... 51 Web Page Menu Layout ................................................................................................ 53 Web page Log In Screen ............................................................................................... 54 Web page Header Navigation ........................................................................................ 54 Master Station Overview web page and Option 1 data, if a Wireless module is fitted ...... 55 System Configuration Overview web page ..................................................................... 57 System Diagnostics web page wired only and option 1 data, if wireless fitted................. 58 Master Station Data Logger pop-up ............................................................................... 60 Close up of Master Station Data Logger Information ...................................................... 60 Saving the master station log file ................................................................................... 61 Host Analyser pop-up .................................................................................................... 62 Pakscan 2 Loop Diagnostics web page ......................................................................... 63 Pakscan Wireless Diagnostics web page ....................................................................... 66 Wired Option Module Event Logger pop-up ................................................................... 68 Wireless Option Module Event Logger pop-up ............................................................... 69 FCU Menu web page .................................................................................................... 70 IQ and IQT actuator FCU Control web pages................................................................. 71 Wired IQ / IQT Parameters pop-up ................................................................................ 72 Wired IQ / IQT Alarms pop-up ....................................................................................... 73 Wired and Wireless IQ / IQT Torque Profile pop-up ....................................................... 73 Wired IQ / IQT FCU Event Log pop-up .......................................................................... 74 Wireless IQ / IQT Parameters pop-up ............................................................................ 75 Wireless IQ / IQT Alarms pop-up ................................................................................... 76 Wireless IQ / IQT FCU Event Log pop-up ...................................................................... 77 Wireless IQ / IQT Downloads pop-up ............................................................................. 78 Wireless Neighbour tables pop-up ................................................................................. 78 Q actuator FCU Control Web page ................................................................................ 80 Q Parameters pop-up .................................................................................................... 81 Q Alarms pop-up ........................................................................................................... 82 Q FCU Event Log pop-up .............................................................................................. 82 GPFCU Control web page ............................................................................................. 84 GPFCU Parameters pop-up .......................................................................................... 85 GPFCU Alarms pop-up.................................................................................................. 86 GPFCU Event Log pop-up ............................................................................................. 86 Administrator Level........................................................................................................ 88 Users web page ............................................................................................................ 88 Add User web page ....................................................................................................... 89 Modify User web page ................................................................................................... 90 Master station configuration web page: General Settings ............................................... 91 Web page Field unit distribution bar............................................................................... 95 Master station configuration web page: Pakscan 2 Loop ................................................ 96 Master station configuration web page: Pakscan 3 Wireless .......................................... 98 Host Port Configuration web page ............................................................................... 100 Modbus Message Generator web page ....................................................................... 103 Modbus Message Example web page ......................................................................... 104 Alarm Reporting Set up web page ............................................................................... 105 Time Settings web page .............................................................................................. 107 General web page ....................................................................................................... 108 Ethernet Network Settings web page ........................................................................... 109 Detailed Actuator Condition HMI pages ....................................................................... 117 Hot standby master station with Long Term Datalogger (LTD) ..................................... 119 Front view of the LTD .................................................................................................. 120 Publication PUB059-002-00 Issue 05/12 Introduction This manual relates to Pakscan 3 Master Stations fitted with PS720 Current Loop modules and/or the PS721 and PS722 Wireless modules INTRODUCTION Pakscan 3 is a complete field network control system from Rotork. With the addition of a wireless network the user now has the choice of proven current loop technology of the Pakscan IIE system or the flexibility of a meshed wireless network. This manual provides a guide to setting up the Pakscan master station, the loop communications, wireless communications, and the host connections for the most commonly found applications. Most types of Rotork actuator can be connected to a Pakscan current loop provided they are fitted with the necessary field unit. Information on the respective actuator field units can be found in the appropriate manuals. In this guide, the type of actuator is not considered, though reference is made to both the Integral and IQ actuator types of field unit. The type of field unit does not affect the setting up of the system. The IQ and IQT range of actuator integrate fully with the wireless network. Other actuators or devices can be added to the system using a Wireless Modbus Adaptor (WMA). Pakscan 3 master stations are delivered either as loose items for mounting by the user, or contained in an enclosure provided by Rotork. The master station will generally be either a single unit, or a hot standby pair. Pakscan IIE Loop Standby Port A PS710 rotork rotork CPU/PSU Status Pri/Stby Power Alarm PS700 Port 1 Port B PS720 rotork rotork rotork Option 1 Option 2 CЄ Port 2 Switch Option 2 Option 1 Port 1 CPU/PSU Port 2 Fig 1: The Pakscan 3 Single Master Station – option: Current loop Pakscan IIE Loop Standby PS700 rotork rotork CPU/PSU Port 1 Port 2 Auto Port B Port B PS720 PS730 PS720 PS710 rotork rotork rotork rotork rotork Option 1 Option 2 CЄ Pakscan Port A Status Pri/Stby Power Alarm IIE Loop Standby Port A PS710 Keyswitch Switch Option 2 Option 1 rotork CPU/PSU Status Pri/Stby Power Alarm Port 1 Port 2 Fig 2: The Pakscan 3 Hot Standby Master Station - option: Current loop Issue 05/12 Publication PUB059-002-00 7 of 134 P3 - Pakscan Master Station Technical Manual A master station fitted with the wired network only requires the PS720 module that fits in to the back plane. A master station fitted with wireless requires a module to be fitted to the back plane (in option 1) and connected to this module, a coordinator module (PS722). Pakscan P3 Wireless Comms PS710 CPU/PSU PS700 rotork rotork Status Pri/Stby Power Alarm PS721 rotork Option 1 Port 1 rotork Option 2 CЄ Port 2 rotork Switch Fig 3: The Pakscan 3 Single Master Station – option: Wireless Pakscan P3 PS700 rotork rotork CPU/PS Port Port Pakscan Comms PS710 P3 Comms Statu Pri/Stb Pow Alar Keyswit PS721 Aut PS730 rotork rotork Option Option CЄ rotork Switc PS720 PS721 rotork rotork Option Option PS710 rotork CPU/PS Statu Pri/Stb Pow Alar Port Port Fig 4: The Pakscan 3 Hot Standby Master Station – option: Wireless Fig 5: The Pakscan 3 Wireless master station coordinator – PS722. One required for single channel master stations, two for hot standby master stations. The repeater (a device for extending the range of wireless) and the WMA look identical to this. 8 of 134 Publication PUB059-002-00 Issue 05/12 1. Mounting and Connecting the Master Station 1. MOUNTING AND CONNECTING THE MASTER STATION Before mounting the master station, set the communications link switches, as discussed in section 3. The Pakscan 3 master station (single or hot standby) provides front access for all the user connections, including power feed and the field network connections – either loop wires to the Current Loop module (PS720) or network connection to the Wireless coordinator (PS721 and PS722). The host communication links use plug in D-type connectors for the serial communications and RJ45 connections for the Ethernet links. The field wiring for the current loop, wireless coordinator and the master station alarms are taken to screw terminals on plug in connectors that are fitted from below their appropriate module. Power wiring is connected using an IEC connector in the bottom of the master station module PS710. Two connections are required for a hot standby system. Serial communications (RS-232 or RS-485) plug into 9 way female D-type connectors on the front of the mounting chassis. Ethernet connections use RJ45 connectors on the bottom of the master station module PS710. The connector on the front is intended for connection to a service laptop computer. 1.1 Mechanical Fixing Room should be left around the module for all the connections and cables, allowing for a suitable bending radius on each lead. Power wiring should be suitably fused or protected with miniature circuit breakers (MCBs) external to the master station. The master station may be mounted on a flat surface using the mounting brackets provided. Also, the extension brackets allow it to be mounted in a 19-inch rack. In either case it should be located in a way that permits easy access to the pushbuttons and easy viewing of the display panel(s). 482 All dimensions in mm 467 140 438 Pakscan IIE Loop 45 Standby 178 88 Port A Port B Status PS710 PS700 rotork rotork CPU/PSU Port 1 Port 2 Pri/Stby Power Alarm PS720 rotork rotork Option 1 Option 2 CЄ rotork Switch Option 2 Option 1 CPU/PSU Port 1 Port 2 4 holes 6.5 Allow 30 mm minimum space for cabling Fig 6: Pakscan 3 surface mounting dimensions. (Both single and hot standby master stations may be surface mounted) Issue 05/12 Publication PUB059-002-00 9 of 134 P3 - Pakscan Master Station Technical Manual All dimensions in mm 482 140 133 466 Pakscan 38 IIE Loop Key switc h Standby 178 102 CPU/PSU Port 1 Port 2 PS700 rotork rotork AutoB PS730 Status Option 2 Switch Option 2 Pri/Stby PS710 PS720 rotork rotork rotork rotork rotork CЄ Port B PS720 Option 1 4 slots 6.5 Pakscan Port A Port B Status Pri/Stby Power Alarm Standby Port A PS710 IIE Loop Option 1 Power Alarm rotork CPU/PSU Port 1 Port 2 Allow 30 mm minimum space for cabling Fig 7: Pakscan 3, 19-inch rack mounting dimensions. (Both single and hot standby master stations can be panel or rack mounted) Ethernet Ports Hard Wired ESD Serial Ports Wireless Current module Loop (Single) Port 3 Port 4 (Hot Standby) 12345 123456 IEC Power Connector Fuses Fig 8: View below the Pakscan P3 master station showing the Connectors (The B side connections are similar) 10 of 134 Publication PUB059-002-00 Issue 05/12 1. Mounting and Connecting the Master Station Wireless installations will include a Wireless Coordinator and may include Wireless Repeaters and Wireless Modbus Adaptor. These units are identical with regards to mechanical fixing. Dimensions in mm, Module weight: 4,400g Fig 9: Wireless co-ordinator WMA and Repeater mounting details The Wireless Coordinator, Wireless Repeater and Wireless modbus Adaptor may be located in Hazardous locations. If this is the case, please refer to the Hazardous Area notes in the General Safety Information section at the back of this manual. Issue 05/12 Publication PUB059-002-00 11 of 134 P3 - Pakscan Master Station Technical Manual 1.2 Host Serial Communications Connections The serial data connections are via the D-type connectors below each master station PS710 on the main chassis. They are labelled Port 1 and Port 2 on both the A and B (left and right) sides of the assembly. All the connectors are 9 way female and they may be set for RS-485 (2-wire) or RS-232 use. On hot standby systems they can be cross coupled to provide seamless communication when the systems change over. The pin-out connections are shown below. Fig 10: Serial Communication connections With RS-485 it is possible to arrange a multi-drop data highway for the serial communications, whilst RS-232 must be single point communications. 1.3 Ethernet Communications Connections Each Pakscan P3 CPU module (master station module) has 2 x RJ45 Ethernet connectors for the two host communication ports (accessed from below) marked Port 3 and Port 4. A third RJ45 connector is located on the front of each module. This is provided to allow a portable computer (laptop) to be connected for diagnostic and set up purposes. Standard Ethernet patch cables can be used with these connectors. All Ethernet cables must be screened, and of good quality. Many screened Ethernet cables of low quality have questionable screening efficacy. 1.4 Power Connector and Fuses Each Pakscan P3 CPU module has its own internal power supply. A standard IEC connector is provided to allow the mains power (85 to 263V AC – 47 to 63 Hz) to be connected from below the module. The mains IEC socket also includes the two fuses for the system, which must only be replaced with the same and rating 250V 1A 5x20mm anti-surge fuses. For the 24V DC version, a three pin removable screw terminal connector is provided. There is no internal fuse. 12 of 134 Publication PUB059-002-00 Issue 05/12 1. Mounting and Connecting the Master Station 1.5 Alarm and Hardwired ESD Connector There is a removable screw terminal connector in each Pakscan P3 CPU module for the connection of ESD hard-wired inputs and for connection to the internal alarm relay contacts, when required. On most systems these terminals will not be used; in which case a hard-wired link between pins 4 and 5 must be fitted, this is usually fitted by the factory. Alarm Emergency Shutdown PS710 CONNECTOR Fig 11: Terminal Function Alarm (common) Alarm (normally closed) Alarm (normally open) Emergency Shutdown Emergency Shutdown PS710 CPU module connector terminal functions Note the relay is shown in the ‘alarm active’ or ‘power removed’ position. The Alarm relay will activate if there are any alarm conditions in any field unit or the master station. This alarm will not prevent operation of the master station. 1.6 Current Loop Connections A connector is located in the bottom of the key switch module on hot standby Pakscan 3 systems for the connection of the current loop to the field mounted actuators. On single P3 master stations the connector beneath the current loop module itself should be used. Source B Source A PS720/PS730 CONNECTOR Fig 12: Issue 05/12 Port B IN Port B OUT Screen Port A IN Port A OUT Screen Terminal Function Port B In Port B Out Port B Screen Port A In Port A Out Port A Screen PS720/PS730/PS731/PS732 Current Loop connections Publication PUB059-002-00 13 of 134 P3 - Pakscan Master Station Technical Manual 1.7 Wireless Coordinator Connections A connector is located in the bottom of the (PS721) wireless option module to connect to the Wireless coordinator (PS722). The connection between these should be made using a shielded network cable with 3 pairs of wires – each pair to be twisted. Suitable cable conforms to the specification for RS-422 networks. This cable can be up to 200m long so that the coordinator may be mounted, for example, on the roof of the building containing the master station. The Communications cable and appropriate glands for the Wireless coordinator will need to be sourced locally, according to site requirements. Connect the Communications cable as shown below, noting that the connections are NOT all one to one. WIRELESS OPTION MODULE 24V PS721 0V Supply 0 V DC 8 Supply 24 V DC 7 Tx Shield/Gnd 6 RS422 Tx -ve 5 RS422 Tx +ve 4 WIRELESS COORDINATOR MODULE Scr/ Rx PS722 Gnd -ve Tx 6 2 Rx Scr/ Tx +ve +ve 1 Gnd -ve 4 Rx Shield/Gnd 3 RS422 Rx -ve 2 RS422 Rx +ve 1 200m maximum Fig 13: 14 of 134 PS721 to PS722 connections (Master station to Wireless Coordinator) Publication PUB059-002-00 Issue 05/12 1. Mounting and Connecting the Master Station 1.8 Wireless Repeater and WMA AC Power Connections The Wireless Repeater and the WMA will contain a power module for the appropriate power supply requested by the user. The power module is mounted the base half of the module with the wireless module in the other half, the modules will be connected together by an interconnecting loom, connected to SK1 on the power module and SK3A on the wireless module. The mains AC connections are made to the power module connections SK6 and SK5, shown in the Figure below. SK15, a flying lead, will be fitted to the appropriate tapping for the power supply that the customer has indicated will be used. Fitting to the posts labelled W, X, Y and Z selects the correct voltage. This should be checked for correct fitment before power is applied. Power should only be applied with the module fully assembled i.e. the base and the cover connected together with the bolts supplied. Cable glands used must be appropriate to the classification of the area. The Power cable and appropriate glands for the Wireless coordinator will need to be sourced locally, according to site requirements. Fig 14: Issue 05/12 Power module for Wireless Repeater and WMA. Publication PUB059-002-00 15 of 134 P3 - Pakscan Master Station Technical Manual 1.9 WMA (Wireless Modbus Adapter) 24VDC Connections The WMA may be powered from the Modbus device to which it is connected, assuming the device has the appropriate DC supply available. Under this circumstance the interconnection cable between the device and the WMA should contain 2 shielded pairs, one for power supply and one for the communication signal. The distance between the Modbus device and the WMA should not exceed 10 meters in this case. The power connection on the WMA are pins 7 (+ve) and 8 (0volts) of SK3A. 1.10 WMA (Wireless Modbus Adapter) Modbus Connections The WMA connects to a Modbus RTU device enabling a Modbus host to connect through the Pakscan wireless system to the Modbus device. The connection between the Modbus device and the WMA should be made using a shielded network cable with 1 twisted pair of wires. Suitable cable conforms to the specification for RS-485 networks. This cable length will depend on the baud rate chosen for communications. The Communications cable and appropriate glands for the Wireless coordinator will need to be sourced locally, according to site requirements. Connect the Communications cable as shown below, SK3A is used on the WMA. WIRELESS MODBUS ADAPTOR (WMA) MODBUS DEVICE Shield/Gnd RS485 (B) RS485 (A) Fig 15: 16 of 134 RS485 (B) 2 RS485 (A) Scr/ 1 Gnd PS721 to PS722 connections (Master station to Wireless Coordinator) Publication PUB059-002-00 Issue 05/12 1. Mounting and Connecting the Master Station 1.11 Setting up the Wireless Repeater and WMA The Wireless Repeater requires the PAN ID (Personal Area Network Identification number) and RF Channel to be set up for the network to which it is attached. The WMA also requires these parameters and its Modbus communication parameters to be set up. This is achieved using the Modbus interface that is available on both modules. The Modbus physical connections are detailed in the previous section ‘WMA (Wireless Modbus Adapter) Modbus Connections’. For the purpose of configuration, these connections can be temporary, for example, it may be more convenient to make the configuration changes in a workshop before installation on site. For both devices it is likely that configuration is only required once, therefore after installation there should be no need to access the Modbus connections again on the Wireless repeater. During configuration in a workshop environment, the 2 halves of the module can be separated, such that the Wireless module is disconnected from its power supply module. The wireless module can then be powered, separately, using a 24VDC source as described in the previous section ‘WMA (Wireless Modbus Adapter) 24VDC Connections’. For making configuration changes to the Repeater or WMA, there is a fixed Modbus address of 248. The Wireless Repeater, ONLY requires the PAN ID and RF Channel to be set up, whereas the WMA also requires the Modbus communication parameters (baud rate and parity) to be set up, as appropriate for communicating to the Modbus slave device it is to be connected to. The Modbus slave device address is not required to be set up within the WMA, as the WMA will automatically scan for attached devices using the baud rate and parity set. Up to 10 slave Modbus devices can be connected to the WMA, each device will require a unique Modbus address, within the range 201 to 247. The address must be unique for the host device to be able to access it. Within the master station configuration pages, the Modbus addresses used for the devices fitted to the WMAs are required to be selected. See section 7.5.17 master station configuration. Changes to RF communication parameters will take place immediately. Changes to modbus communication parameters will take effect after a power cycle and will apply to the Wireless Repeater and WMA when configuring in the future as well as when the WMA communicates to its Modbus device. Issue 05/12 Publication PUB059-002-00 17 of 134 P3 - Pakscan Master Station Technical Manual The principle of operation of the WMA is shown in the diagram below Fig 16: 18 of 134 Wireless Repeater and WMA database Publication PUB059-002-00 Issue 05/12 1. Mounting and Connecting the Master Station The following parameters can be configured when addressing the unit using the configuration Modbus address of 248: Modbus Modbus Register Function code 100 03, 04, 06, 16 Description Range PAN ID 102 03, 04, 06, 16 RF Channel 104 03, 04 0000 – FFFFhex (0 – 65535) 16 – 25dec (channel 16 to Channel 25) 201-247dec 200 03, 04, 06, 16 WMA: Lowest Modbus Address of device (s) connected to the WMA, if no device is found this will default to 247 Repeater: Address of the repeater, required to be set up for the device to appear in the master station for status info – must be unique in the network Modbus Baud rate 201 03, 04, 06, 16 RS485 Parity 03, 04, 06, 16 Fig 17: Default Value DA15 hex 22 Read / Write? R/W 247 RO 301 R/W (9600) R/W (None) R/W R/W 301-315dec Value 1 to 5: 1–9600 / 2–19200 3–38400 / 4–57600 5-115200 Value 1 to 5: 1–None / 2-Odd 3-Even Wireless Repeater and WMA database The baud rate of communications between the WMA and the Device should be set to a value faster that the host will communicate to the master station. Issue 05/12 Publication PUB059-002-00 19 of 134 P3 - Pakscan Master Station Technical Manual 1.12 Front Panel LEDs There are four Light Emitting Diodes (LEDs) on the front panel of the CPU module, in the bottom righthand corner. These are fitted to show if a unit is powered-up, which unit is in Primary or Standby mode and whether there are any errors or alarms. Fig 18: CPU LEDs (Light Emitting Diodes) On power-up, there is a sequence of colour changes and flashes from the LEDs, which take almost a minute to complete and confirms that all parts of the system are operating correctly: The Status LED sequence is: off > amber > flashing green > steady green. The Pri/Stdby LED sequence is: off > green > off > amber > steady green (amber for standby). The Power LED sequence is: off > amber > green > green > steady green. The Alarm LED sequence is: off > red > off > red > off. The Status LED will show steady red if communications with the host is lost over Ethernet, or there is a communications error between the master station and a field unit. The LED shows flashing green only during the power-up sequence. The LED shows steady green to confirm that all applications are running after power-up is completed. The Pri/Stdby LED will show steady green if it is a singe unit or if it is the Primary unit of a hot standby pair. The LED will show steady amber if it is the Standby unit in a hot standby pair. The Power LED is off when there is no power and steady green when power is present. It only shows amber during the power-up sequence. The Alarm LED will show steady red if there are any alarm conditions in any field unit or the master station. This alarm will not prevent operation of the master station. 20 of 134 Publication PUB059-002-00 Issue 05/12 2. The Field Current Loop Network 2. THE FIELD CURRENT LOOP NETWORK The Pakscan current loop field network must be correctly cabled and connected to the master station. The values of the field loop resistance and capacitance must be known to determine the loop speed that can be used. If these are not known then the LOWEST loop speed must be set in each actuator and the master station to ensure good field network connectivity. Port A OUT = Term'l 5 IN = Term'l 4 Port B IN = Term'l 1 OUT = Term'l 2 Up to 240 actuators per loop Current loop - up to 20 km Fig 19: Issue 05/12 Pakscan P3 Wired Network Publication PUB059-002-00 21 of 134 P3 - Pakscan Master Station Technical Manual 2.1 Loop Checks The most common errors in installing the system occur on the field wiring. Loop Continuity With all the field units connected, but none of them powered up, check the continuity of the 2 cores of the Pakscan loop cable. Measure and record the resistance of each core. These measurements will be useful as they can be compared with future measurements to determine if cable resistance has changed significantly or not, this may help identify a cable fault. Cable resistance (R) is the sum of the resistance of both cores. Screen Continuity Screen continuity must be continuous between each end of the loop. Ensure the screen is either connected to a signal earth bar at only one point or to terminals on the loop driver plug; pin 3 connects directly to the enclosure earth and pin 6 connects to the enclosure earth via an internal capacitor, preventing an earth loop. Both screens must be connected to the terminals provided on the loop driver, so as to ensure the product meets the European Directive on EMC. Cable Capacitance The capacitance (C) between the cores of the cable is critical to system performance. Too high a capacitance for the selected loop baud rate will result in poor communications, or even communication failure. If a suitable meter is available, measure and record the capacitance between the cable cores. Maximum Loop Speed The cable resistance must not exceed 500 Ohms (250 Ohms per core) and the total capacitance must not exceed the maximum value for each communication speed. In addition to cable capacitance, each field unit adds a small amount of capacitance to the loop which must also be considered when determining maximum loop speed. Use the measured resistance and capacitance values from the above tests to determine which loop speed should be used. Baud Rate 110 300 600 1200 2400 R max (ohms) C max (F) 500 500 500 500 500 4.5 2.1 1.54 0.6 0.3 Each field unit will add a capacitance of 2.2nF The C max figure given is the maximum value for the network capacitance including the field unit capacitance. Test Equipment A good quality multimeter with capacitance test facility is adequate for testing loop resistance and capacitance. Under no circumstances should any high voltage test equipment be used such as insulation Megga testers when any part of the cable loop is connected to either the master station or actuators. The high test voltages generated by such equipment may damage the Pakscan components. 22 of 134 Publication PUB059-002-00 Issue 05/12 2. The Field Current Loop Network 2.2 Connecting Up Once the checks are complete, connect the Loop Cables to the PS730 Key switch module on a hot standby system or the PS720 Current Loop module on a single system. The Pakscan loop should look like figure 15. Check the loop wiring complies with this drawing and then proceed to Section 8.1 for commissioning instructions. MAINS SUPPLY L N E P3 MASTER STATION ‘A’ POWER SUPPLY PORT 1 PORT 2 PS710 MODULE (PROCESSORS AND DISPLAY) WIRE A SIDE EMERGENCY SHUTDOWN IN SERIES WITH B SIDE Note: 4 and 5 swap over ALARM EMERGENCY SHUTDOWN PS720 MODULE (CURRENT LOOP CONTROLLER) PORT 3 PORT 4 Actuator Terminals A C B SCR 6 Screen 5 Port A OUT 4 Port A IN SIGNAL EARTH BAR If there is a signal earth bar, connect the screen on one side only to the bar. 3 Screen 2 Port B OUT 1 Port A IN Actuator Terminals A C B SCR PS730 KEY SWITCH MODULE SCR B C A Actuator Terminals PORT 4 PS720 MODULE (CURRENT LOOP CONTROLLER) PORT 3 PORT 2 PORT 1 PS710 MODULE (PROCESSORS AND DISPLAY) POWER SUPPLY P3 MASTER STATION ‘B’ ALARM Fig 20: Pakscan P3 Current Wired Loop System Block Diagram (hot standby master station) L N E MAINS SUPPLY Note: If there is no hard-wired ESD requirement a shorting link must be fitted across pin 4 and 5 on both side A and side B of the PS710 modules Issue 05/12 Publication PUB059-002-00 23 of 134 P3 - Pakscan Master Station Technical Manual MAINS SUPPLY L N E POWER SUPPLY PORT 1 PORT 2 PORT 3 PORT 4 P3 MASTER STATION ‘A’ PS710 MODULE (PROCESSORS AND DISPLAY) 2 ALARM EMERGENCY SHUTDOWN PS720 MODULE (CURRENT LOOP CONTROLLER) Actuator Terminals A C B SCR 6 Screen 5 Port A OUT 4 Port A IN Actuator Terminals A C B SCR SIGNAL EARTH BAR If there is a signal earth bar, connect the screen on one side only to the bar. Screen 2 Port B OUT 1 Port A IN SCR B C A Actuator Terminals Fig 21: Pakscan P3 Current Wired Loop System Block Diagram (single master station) Note: If there is no hard-wired ESD requirement a shorting link must be fitted across pin 4 and 5 of the PS710 module 24 of 134 Publication PUB059-002-00 Issue 05/12 3. The Field Wireless Network 3. THE FIELD WIRELESS NETWORK A Pakscan wireless network will contain a master station with a PS721 module fitted to its back plane (2 for hot standby). Each of these will connect to a PS722 Wireless coordinator module. The coordinator module is the device that controls and organises the wireless network. For an actuator to be connected on the network it must have a wireless actuator module. The IQ and IQT range of actuators fully integrate into the wireless system. Other devices can be integrated into the system using a Wireless to Modbus adaptor (WMA). The WMA can be attached to any device that has a Modbus interface on it. The host then uses the master station and the wireless network as a transport layer only to send Modbus messages that are directed to a Modbus device. A network may also require a number of repeaters to overcome wireless dead spots or to ensure a redundant path to all devices. Fig 22: A typical P3 wireless network Up to 60 devices can be connected in a wireless network. The distances between each node in the network is recommended to be no more than: Indoors: 30 metres Outside: 100 metres In practice, it has been found that these distances can be extended, but a site survey is required to confirm this. Each device is able to route messages onto the next device. By this method, the range of the network is increased. It is recommended to have no more than 7 ‘hops’ from the master station to the final device. A ‘hop’ is where a message routes through a wireless device to get to the destination device. Issue 05/12 Publication PUB059-002-00 25 of 134 P3 - Pakscan Master Station Technical Manual 3.1 Wireless Site Survey The first step in setting up a wireless network will be a Wireless Site Survey, which would be performed by Rotork Personnel. This will establish the suitability of the site for a wireless network. The survey will establish the levels of background wireless signals within the spectrum of the 2.4 GHz band used for the P3 wireless network and also the potential strength of the wireless signals between the actuator and coordinator locations. This will aid in positioning the coordinator and in deciding upon the need for repeaters. As a result of the survey, one or more, channels within the band will be found to be suitable for the network. All devices on the network will be shipped with a default channel set. 3.2 Wireless Specification Network Based on: Maximum Wireless devices: Frequency: Operating Range: Network Structure: Channels available: Security: Power: IEEE 82.15.4, DSSS (Direct Sequence Spread Spectrum). 60. 2.4GHz band. 30m indoors, 100m outside. Mesh. 16. AES and anti-spoofing. 10mW default, potential for 100mW if the location allows. 3.3 Connecting Up The IQ and IQT actuators fitted with a wireless module will only require mains power connections and the appropriate glands for the environment to be connected to them. Where a WMA is supplied, power is required to be provided by the user and the user must also provide the necessary cable and glands between the WMA and the device to which it is attached. A repeater also only requires a power cable and glands supplied by the user. The power required for the Repeater and WMA will be indicated on the serial label. Figure 17 shows the master station block diagram. The site survey will have indicated the appropriate position to locate the coordinator(s) and any repeaters. Once all the equipment is in place, the user can then proceed to Section 8.2 for commissioning instructions. 26 of 134 Publication PUB059-002-00 Issue 05/12 3. The Field Wireless Network Fig 23: Pakscan P3 Wireless network Block Diagram (hot standby master station) Note: If there is no hard-wired ESD requirement a shorting link must be fitted across pin 4 and 5 on both side A and side B of the PS710 modules. Issue 05/12 Publication PUB059-002-00 27 of 134 P3 - Pakscan Master Station Technical Manual (This page is intentionally blank) 28 of 134 Publication PUB059-002-00 Issue 05/12 4. Configuring Serial Communications 4. CONFIGURING SERIAL COMMUNICATIONS The Pakscan 3 CPU module has two serial ports. Each of these is configurable for RS-232 or RS-485. Most hot standby systems will probably require two RS-485 connections in a seamless redundant configuration. Single systems may use RS-232 or RS-485. 4.1 Setting Port 1 and 2 for RS-232 or RS-485 The chassis has DIP switches behind the PS710 CPU module for setting the type of serial port that is presented at the port connectors. Select RS-485 Termination Select Function Port Terminations Off 1 Off 2 CPU Feedback for Cross Connection On On IIE Loop IIE Loop Standby Port A RS232 Port 1 Port 2 PS700 rotork Fig 24: Port 1 Port 2 Port Terminations Off 1 Off 2 Port B rotork rotork Option 1 RS232 RS485 Port 1 Port B Port 2 Port 2 PS720 Port 2 rotork rotork Not Cross Cross Connected Connected Option 2 CЄ On On Port A Port 1 Port 1 PS720 CPU/PSU Select RS-485 Termination Standby Port 1 Port 2 Only Only RS485 Port 1 Port 2 Select Function Select RS-485 Cross Connection Switch Option 2 Option 1 CPU/PSU Port 1 Port 2 Pakscan P3 Chassis, CPU and Key Switch modules removed The switches on the backplane behind the PS710 CPU Module are used to set Port 1 and Port 2 parameters. Issue 05/12 Publication PUB059-002-00 29 of 134 P3 - Pakscan Master Station Technical Manual Port Function RS-232 Fig 25: RS-485 Port 1 Two DIP switches allow each port to be selected between RS232 and RS-485. For RS-485 slide the appropriate Port switches to the right, for RS-232 they should be on the left. Port 2 Each of the two ports may be set independently. Port Function Switches shown in RS-232 position RS-485 Termination Resistors Two DIP switches are used to connect end-of-line termination and biasing resistors to the RS-485 highway. All RS-485 network highways must be terminated at both ends of the highway, in this case, at the host controller and at the master station. Only RS-485 highways need termination and biasing resistors. If a CPU port is configured for RS-232, it must never be terminated. Each port can be terminated independently. Each CPU module serial port sits on an independent highway and should be terminated independently. So, if ports 1 & 2 on a CPU module are both being used for redundant RS-485 communications to a Host controller, then each port may need to be terminated and biased. However, where more than one CPU Module sits on the same RS-485 highway, then only the one furthest from the host controller needs the biasing and termination resistors to be enabled. +5V 1k Off On Data + 120 Data Off On 1k Gnd Fig 26: 30 of 134 Port Termination Switches shown in Off position Publication PUB059-002-00 Issue 05/12 4. Configuring Serial Communications Cross Connection switches The cross connection switches, found on the backplane behind the PS710 CPU Module, are used to cross connect the serial RS-485 connections. They are only applicable for a hot standby system and should ONLY be set as cross connected for a port that has been selected as RS-485. Fig 27: Cross connection switch settings on the backplane behind the Switch Module The switches are shown in the Factory Default positions (Hot Standby). Port 1 is set to Cross-Connected for RS-485 Serial communications. Port 2 is set to Not CrossConnected for RS-232 Serial Communications. The feedback switch positions must reflect the Cross-Connection settings for Port 1 and Port 2. These switches are used, by the master station CPU, to indicate to the user (via the HMI or web pages) the position of the cross-connect switches. Issue 05/12 Publication PUB059-002-00 31 of 134 P3 - Pakscan Master Station Technical Manual Typical Serial Host connections to the P3 master station and appropriate switch settings: Hot Standby RS-485 communications Communications between the Host and the master stations uses the Modbus protocol. Because the Master A is cross-connected to Master B, they both share the same Modbus address. The standby action must then be set to passive. Thus, the host can have two-way communications with the Primary (Main ) module and the Standby module will only listen to the messages. Hot Standby RS-232 Communications With RS-232, communications between the Host and Hot Standby master station must be point-topoint. Multi-drop connection is not allowed, so separate cables must be run from the Host to each side of the master station. Also, the Cross-Connect switch must be set to Not Cross-Connect. The standby action must be set to active, so that the Host has full communications with Master A and Master B. Note: only actuator commands sent to the Primary CPU Module will be actioned. Hot Standby dual Host RS-232 or RS-485 communications P o r t 2 s e t to N o t C r o s s - C o n n e c t PS 710 P o rt 1 P o rt 2 PS 710 P o rt 1 P o rt 2 Host H ost R S -2 3 2 o r R S -4 8 5 Fully dual-redundant system. Port 2 set to RS-232 or RS-485 to match Host communication Fig 28: 32 of 134 Hot Standby Serial Communications Publication PUB059-002-00 Issue 05/12 5. Configuring Ethernet Communications 5. CONFIGURING ETHERNET COMMUNICATIONS Pakscan 3 master stations come complete with two Ethernet ports for connection to host systems. A third Ethernet port is also available for connection to a computer for configuration purposes. The master station is ready to use with Ethernet and Modbus TCP protocol for the host to access data and control the actuators on the field network. The IP address is factory set to the default value and can be changed during set up of the master station. The Pakscan master station defaults to the same IP address on both ports, and can use the same address on the A and B master stations. It is possible to change the IP address on either master station, but ports 3 and 4 of each CPU Module always have the same address. Hot Standby Ethernet communications Port 2 set to Not Cross-Connect Port 3 or 4 PS 710 Port 1 Port 2 Host Host Port 3 or 4 PS 710 Port 1 Port 2 Ethernet Ethernet Ethernet comms between Hosts and master station are made using Port 3 or Port 4. The CrossConnect switches can be in either position, or set appropriately for any additional serial comms. In this case, with two Hosts, Standby must be set to Active. The IP address of Master A and Master B can be set to be the same or different, with Standby Active. Where an Ethernet switch is used to connect a Host to the hot standby master station and the IP address is set the same for Master A and B, then Standby must be set to Passive. Fig 29: Hot Standby Ethernet Communications Hot Standby Redundant Host, Redundant Ethernet communications Issue 05/12 Publication PUB059-002-00 33 of 134 P3 - Pakscan Master Station Technical Manual Fig 30: Hot Standby, Dual Redundant Ethernet Communications For full Ethernet communications redundancy, use two Hosts and two managed Ethernet switches. Managed Ethernet switches with rapid spanning tree protocol are required. This type of switch is able to prevent Ethernet Storms, where messages are re-circulated continuously. Ethernet communications between Hosts and master station are made using Port 3 and Port 4. In this case, with two Hosts, Standby must be set to Passive. The IP addresses of Master A and Master B can be set to be the same with Standby Passive, or different, with Standby Active. The Pakscan P3 master station defaults to the same IP address on all ports. It is possible to change the IP address for Master A and Master B independently, but all ports for each master will have the same address. In a hot standby system, if the Copy IP Settings option is selected, both sides of the master station will have the same IP address. 5.1 Default Ethernet Settings The default Ethernet parameters set in each Pakscan 3 CPU Module are given below: DHCP Default IP address Default Subnet mask Standby Action Static 10 200 255 255 255 Passive Note: changes to the IP address, Subnet Mask or clock settings will cause a re-boot of the CPU module. 34 of 134 Publication PUB059-002-00 Issue 05/12 5. Configuring Ethernet Communications 5.2 Ethernet Security When connecting the master station to an Ethernet network, care should be taken to consider security of the master station. There are a number of Ethernet services available in the master station and, where appropriate, the user should ensure that the Ethernet infrastructure is able to protect the master station from unwanted access to a service. Transmission Control Protocol (TCP) and Internet Protocol (IP) are the core protocols utilised in Local Area Networks (LANs) and computer networking. Within these networks a ‘port’ is an endpoint to a logical connection – not to be confused with the physical port! The port number in this case refers to the type of port. For example, port 80 is used for HTTP web page traffic. The ports that are available at the master station are: Port description Telnet FTP HTTP HTTPS Modbus/TCP Port number 23 21 80 443 502, 50003, 50004, 50005, 50006, 50007, 50008 and 50009 Ethernet products, like routers, can prevent other Ethernet equipment on the same LAN from accessing certain services in the master station. If web page access were not required, the most secure set up would be to prevent all but Modbus traffic entering the master station. Issue 05/12 Publication PUB059-002-00 35 of 134 P3 - Pakscan Master Station Technical Manual (This page is intentionally blank) 36 of 134 Publication PUB059-002-00 Issue 05/12 6. Setting Up the Master Station by the Keypad 6. SETTING UP THE MASTER STATION BY THE KEYPAD The Pakscan 3 master station CPU module has a full colour display and 5 button input pad. All the settings for the performance of the master station, the Option module fitted and the Field Network can be made using these facilities. The keypad and screen also allows every connected actuator to be interrogated and its status monitored. Finally, the actuators and valves can be moved using these facilities. Alternatively, a computer with an Internet browser facility can be used with the internal web server pages. These pages allow the whole system to be set up and modified. In addition, they allow the connected actuators to be viewed and controlled. Pakscan Keypad Detail Display BACK ENTER Keypad NEXT Ethernet Set up Port PS710 rotork Status Pri/Stby Power Alarm Ethernet cable Fig 31: Pakscan P3 Main module connection to laptop and keypad detail 6.1 Using the Keypad The keypad controls the movement through the display screens and the movement within each screen, as well as the ability to input data or requests. (Left) and (Right) arrow keys Allow active items within a page display to be highlighted. If the item is selected and a numeric input is needed, then these keys increase or decrease the number. ENTER Selects a highlighted element on the screen or completes the entry of information. BACK and NEXT BACK moves up one level in the menu of the displays, returning to the previous screen viewed. NEXT only functions if there is more data to show than fits on the screen. When there is additional data, a small arrow is shown on the right side of the screen. It points down () for NEXT and up () for BACK to operate. Issue 05/12 Publication PUB059-002-00 37 of 134 P3 - Pakscan Master Station Technical Manual 6.2 The Screen Display The opening, or top screen display shows the network status and three icons (four icons, if keypad ESD is enabled – see below). Menu Section Network Information Current Status Selected Icon Highlighted Selected Icon Function Menu Location The Diagnostics icon (Magnifying Glass) will have a black square around it. The position of the square indicates the part of the menu that will be accessed if the ENTER key is pressed. The highlighted icon can be changed by pressing the arrow buttons ( or ) to scroll round them. The bottom bar shows the selected function as a text message. BACK ENTER NEXT Diagnostics Menus Field Unit Menus Settings Menus ESD control - only visible when “Keypad ESD” is enabled Highlight the Spanner icon for ‘Settings’; then press ENTER. The menu location changes to A3 and the ‘Settings’ menu screen appears with the ‘Host’ icon selected. BACK ENTER NEXT This screen also contains the icons used for access to all the other setting menus. 38 of 134 Host Option Module Security ESD Date/Time M/S Publication PUB059-002-00 Issue 05/12 6. Setting Up the Master Station by the Keypad 6.3 Setting the Current Loop Option Module Parameters On the ‘Settings’ menu, select the Option Module Icon by pressing the right arrow key () followed by the ENTER key. BACK ENTER NEXT The Option choice screen appears where the module to be set can be selected. Firstly we need to ensure that the field units are correctly assigned to the field network chosen. The selection box by the ‘Option 1’ text should be highlighted by pressing the right arrow key twice (). BACK ENTER NEXT Pressing ENTER enables changes to be made using the left () or right () arrow key, press the ENTER key to make a change to the value. This box will increment in steps of 60. In a wired only network all available field units should be allocated to the Pakscan 2 module. Once the number is correct, press ENTER once more BACK BACK ENTER ENTER NEXT NEXT To make changes to the Pakscan 2 Current Loop module settings, highlight Option 2 by using the left () or right () arrow key. BACK ENTER NEXT Issue 05/12 Publication PUB059-002-00 39 of 134 P3 - Pakscan Master Station Technical Manual Pressing ENTER brings the next choice for the setting. This time select ‘Loop Settings’ by once more using the right arrow key (). BACK BACK ENTER ENTER NEXT NEXT The Loop Settings screen is split over two pages, as indicated by the small arrow () on the right side of the screen, so the NEXT and BACK buttons are used to jump between the two. BACK BACK ENTER ENTER NEXT NEXT Once a setting box is highlighted, by using the left () or right () arrow key, press the ENTER key to make a change to the value. This will make the security screen appear for the PIN number entry. The default value for the system security requires a PIN to be entered before any settings can be changed. This setting can be altered from the Security Setting menu. BACK BACK ENTER ENTER NEXT NEXT The default PIN number is 0000. To enter a PIN, or accept the number, press ENTER and the first digit will flash. The value can be changed by using the left or right arrow keys ( or ). Once the number is correct, press ENTER once more. When all 4 digits of the PIN are entered correctly, select the OK button with the arrow keys ( or ). BACK BACK ENTER ENTER NEXT NEXT Press ENTER and the screen will return to the settings screen and the Current Speed will be highlighted. Press ENTER once more to select this parameter and the current value begins to flash. 40 of 134 Publication PUB059-002-00 Issue 05/12 6. Setting Up the Master Station by the Keypad BACK BACK ENTER ENTER NEXT NEXT Use the arrow keys ( or ) to change the value shown until the desired figure appears, then press ENTER and the new value will be set. The arrow keys can be used to navigate to other settings, and the NEXT button goes to the Loop Test screen and Loop Reset function. Set the loop performance parameters in accordance with the data recorded earlier. Make sure the loop speed is compatible with the setting for the loop capacitance. Set the highest field unit address parameter equal to the actual highest address. Doubling can be set to ‘On’ if the loop performance is not fast enough. It has the effect of halving the time to collect data from the field units. This feature will only operate if the loop is functioning correctly with “loopbacks off”. IQ DV Convert should be set to ‘On’ if analogue position control is being used on the IQ / IQT actuators on the network. Data Retain set to ‘Off’ clears all the field unit data if communication is lost. Some host systems want the data to be retained, in which case set the parameter to ‘On’. Once the parameters are all set, leave this part of the setting menu to ensure the new values are loaded. Use the BACK button to return to the Host Settings page, and then ENTER to select the Host Settings menu. BACK BACK ENTER ENTER NEXT NEXT Make alterations to the host protocol settings and Alarm linkage, if required, in a similar manner to altering the loop performance parameters described earlier. The PIN will need to be entered if no keys are operated for approximately 5 minutes from the last PIN entry. Where the two serial ports are being used by the same host system it is advisable to ‘Link’ the alarms so that both ports always report exactly the same alarm data. Issue 05/12 Publication PUB059-002-00 41 of 134 P3 - Pakscan Master Station Technical Manual When the settings are as required, use the BACK key to return to the top Settings menu. BACK ENTER NEXT 42 of 134 Publication PUB059-002-00 Issue 05/12 6. Setting Up the Master Station by the Keypad 6.4 Setting the Wireless Option Module Parameters On the ‘Settings’ menu, select the Option Module Icon by pressing the right arrow key () followed by the ENTER key. BACK ENTER NEXT The Option choice screen appears where the module to be set can be selected. The Pakscan Wireless is always in the Option 1 slot and this is highlighted as the page is entered. BACK ENTER NEXT The Wireless network Settings screen is split over two pages, as indicated by the small arrow () on the right side of the screen, so the NEXT and BACK buttons are used to jump between the two. BACK BACK ENTER ENTER NEXT NEXT Once a setting box is highlighted, by using the left () or right () arrow key, press the ENTER key to make a change to the value. This will make the security screen appear for the PIN number entry. The default value for the system security requires a PIN to be entered before any settings can be changed. This setting can be altered from the Security Setting menu. BACK BACK ENTER ENTER NEXT NEXT The default PIN number is 0000. To enter a PIN, or accept the number, press ENTER and the first digit will flash. The value can be changed by using the left or right arrow keys ( or ). Once the number is correct, press ENTER once more. When all 4 digits of the PIN are entered correctly, select the OK button with the arrow keys ( or ). Issue 05/12 Publication PUB059-002-00 43 of 134 P3 - Pakscan Master Station Technical Manual BACK ENTER NEXT Press ENTER and the screen will return to the settings screen and the Lowest FCU addr. will be highlighted. Press ENTER once more to select this parameter and the current value begins to flash. Use the arrow keys ( or ) to change the value shown until the desired figure appears, then press ENTER and the new value will be set. The arrow keys can be used to navigate to other settings, and the NEXT button goes to the second setting page and the Network Reset function. Set Lowest FCU addr. to the lowest address used for a Wireless field device. This will be where the addressing starts from. Set the Num of FCU to the actual number of Field units in the network. The field units will be numbered from the lowest FCU address contiguously for the Number for field units fitted. Set the PAN ID to a value different from the default. This should be noted as this needs to be set in all the individual field units. Data Retain set to ‘Off’ clears all the field unit data if communication is lost. Some host systems want the data to be retained, in which case set the parameter to ‘On’. Set the AES key to something different from the default. This should be noted as this needs to be set in all the individual field units. The most suitable channel for the system will have been selected during the site survey. This setting should be set to that value. Set the number of repeaters used in the system - repeaters may be required in the system to ensure redundancy or for improved communications. The network can be reset from the second page. This will need to be done if network changes have been made and these are required to be uploaded to all field units. Note that changes to network parameters will only be loaded to those devices currently communicating on the network. When the settings are as required, use the BACK key to return to the top Settings menu. BACK ENTER NEXT 44 of 134 Publication PUB059-002-00 Issue 05/12 6. Setting Up the Master Station by the Keypad 6.5 Setting the Master Host Communications Parameters Select the Host icon using the arrow keys ( or ) and press ENTER. The Host Settings menu choices screen appears. BACK ENTER NEXT Select ‘Ethernet Settings’ using the arrow keys ( or ) and press Enter once more. The Ethernet settings screen appears, note that there are two pages to the menu as indicated by the small arrow () on the right side of the screen. BACK BACK ENTER ENTER NEXT NEXT Use the NEXT button to move to the second page, the BACK button returns to the first page. BACK ENTER NEXT It is usually only necessary to change the IP address and Netmask to match the requirements of the network connected to the master station. When making any change it will be necessary to enter the PIN number for the master station as shown in the previous section. To return to the previous Host Settings screen, press BACK and then select the Serial Settings using the arrow keys ( or ) and press ENTER. The communications port speed (default 9600), and parity are changed here. BACK BACK ENTER ENTER NEXT NEXT Issue 05/12 Publication PUB059-002-00 45 of 134 P3 - Pakscan Master Station Technical Manual The port type is determined by the DIP switch settings on the main chassis behind the PS710 CPU module and the setting is reflected in the message on the screen. If the port is set to RS-485 and cross connected, the description changes to show these settings. This is particularly useful when determining the settings already in place. Select the option to be changed by using the arrow keys ( or ), then ENTER (the PIN screen may appear before a change can be made). Once the PIN is entered, the value of the parameter can be altered by the arrow keys ( or ). The speed can be varied from 2400 to 115,200 and the parity may be Odd, Even, Zero or None. Once the value is as required, press ENTER to set the value. When the parameters are all as required, press BACK to return to the Host Settings screen, then select the Modbus Address using the arrow keys ( or ) and press ENTER. BACK BACK ENTER ENTER NEXT NEXT The Pakscan 3 Modbus address is for accessing the Wireless database. The Pakscan 2 Modbus address is for accessing the Wired (current loop) database. The Pakscan 2 and Pakscan 3 Modbus addresses MUST NOT be the same value. The Modbus address for the communication to the actuators on the Pakscan 2 current loop (via the module in option 2 slot) is altered in the lower window. It is recommended that this is altered to a value other than the generic Modbus default address of 247 and the master Station defaults to ensure that any new stations introduced do not conflict with this address. Do not change unless a Pakscan 3 option module is fitted Change this address for communication with the actuators connected to the current loop module The address is changed by first selecting it with the arrow keys, then pressing ENTER (if the PIN requires entry the prompt page then appears). Use the arrow keys to change the number to the new value, and then press ENTER once more. The new address becomes active once the screen has been changed to a new one. The Pakscan 3 wireless Modbus address is modified in the same way. 46 of 134 Publication PUB059-002-00 Issue 05/12 6. Setting Up the Master Station by the Keypad Once the settings are as required, use the BACK key to return to the top Settings menu. BACK ENTER NEXT 6.6 The Other Settings There are menus for setting all the parameters of the system. These are more fully explained in the system manual and, in general, the default settings will allow most systems to operate with reasonable success. 6.6.1 Security Security is used for setting the PIN number to be used, plus the actions permitted from the keypad and the serial ports via the Interlocks. The Security setting default requires a PIN for adjusting the settings for system performance, but not for issuing actuator commands. Interlocking controls the serial communications that are permitted to operate the actuators. The default grants permission to all the serial ports and the Ethernet ports, but prevents the web page facility from moving the valves. The default PIN = 0000. 6.6.2 ESD The default condition is to disable all the possible Emergency Shut Down routes. ESD can be enabled from the serial ports, Ethernet ports, Web page, hard-wired input or keypad on an individual actuator selection basis. If this ESD function is not required, ensure that a shorting link is fitted across pins 4 and 5 of the PS710 CPU module connector. 6.6.3 Date and Time The date and time, plus the use of an NTP server are set from this menu. The time stamp is used for the logging facility. Issue 05/12 Publication PUB059-002-00 47 of 134 P3 - Pakscan Master Station Technical Manual 6.6.4 Master Station Parameters The master station parameters include the Tag for the master station and the setting for data transferred between the two CPU modules on a hot standby system along with several other parameters. Most of the default settings are suitable on most systems, though there is one particular set of parameters that must be correctly set in the case of hot standby systems. The Serial Ports should appear as Passive if the Cross Connect DIP switch is set to ‘cross connect’. If the port is set to RS-485 highway and is being used on a multi-drop highway it must be set to passive. If it is not shown correctly it probably means the DIP switch is incorrectly set. Remember, the default setting is Standby Active. 48 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages 7. INTERNAL WEB PAGES The master station includes a set of web pages that may be remotely accessed via Ethernet. They can be used for setting up the system, examining the system for any faults or alarms and also for controlling the actuators on the network (provided the Interlock permission is set to allow this feature). If the master station is connected to an Ethernet Network it will act as a web server and any computer within that network can connect to the master station. The master station can also be configured and the field network set up by using these web pages. The host system or computer connected via the Ethernet Network or directly will need a web browser such as Internet Explorer to access the master station web pages. 7.1 Making an Internet / Intranet Connection Connect the master station to an Ethernet host as described in section 5, or connect via a suitable router to the internet / intranet. A computer can be connected directly to the master station using the configuration port. Start the browser and enter the IP address of the master station. The default address is 10.200.1.1, so the address is http://10.200.1.1. The browser will then access the master station and bring up the opening page of the master station. In order to log in as a verified user, enter a user name of admin and a password of admin. (The default password should be altered as soon as convenient to prevent unauthorised access to the system.) Default IP address 10 . 200 . 1 . 1 Default User admin Default Password admin Once entry to the web pages has been made, if no changes to the display or information is made for a few minutes, the system will automatically log out and the user/password must be re-entered. Issue 05/12 Publication PUB059-002-00 49 of 134 P3 - Pakscan Master Station Technical Manual 7.2 Connecting a Computer Directly to the Master Station The simplest direct connection to the master station is by using the Ethernet port on the front of the CPU module. A standard Ethernet patch cable or crossover cable can be used to link the two directly. A permanent connection can also be made directly to one of the underside connectors (port 3 or 4). In order to establish a connection it is probably necessary to adjust the settings of the computer’s Internet connection. Fig 32: Connecting a Laptop to the Pakscan P3 Main Module 7.3 Adjusting the Network Settings of the Computer Ensure that nothing is connected to the Ethernet port of the computer. Open the Control Panel and select Network Connections (XP) or Network and Sharing Centre (Windows 7). Select Change Adaptor settings (Windows 7 only). In the ‘Network Connections’ window, double-click on the appropriate ‘LAN or High Speed Internet’ icon and the ‘Local Area Connection Status’ window will open. Click on the ‘Properties’ button, and a second window will open. Select ‘Internet Protocol TCP/IP’ (‘Internet Protocol Version 4 (TCP/IPv4)’ for Windows 7) and click on the ‘Properties’ button in this window. The ‘Internet Protocol TCP/IP Properties’ window will open. Next, change the setting to force the computer to adopt a fixed IP address and enter an address of 10.200.1.3 and a subnet mask of 255.255.255.0. Click on the ‘OK’ button and the window will close. 50 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages Fig 33: Changing the Network Connections TCP/IP Properties – Windows XP Click OK on the ‘Local Area Connection Properties’ window and then close the status window. Finally, close the ‘Network Connections’ window and the Control Panel. It may be necessary to reboot the computer to be sure that the new settings take effect correctly. Connect the cable between the computer and the Pakscan master station. Start the browser and enter the IP address of the master station. The default address is 10.200.1.1, so set the address to http://10.200.1.1. The browser will then access the master station and bring up the opening page of the master station. In order to log in as a verified user, enter the username of admin and the password admin. Note: If the IP address of the master station has been changed from the defaults, then the settings above will not work and will have to be modified to suit the actual settings. Issue 05/12 Publication PUB059-002-00 51 of 134 P3 - Pakscan Master Station Technical Manual 7.4 Web Page Structure The web pages have three access levels, each requiring a password with the correct level set. A user enters the web server with a particular degree of access to the functions of the server and the master station. 7.4.1 User Levels Access Level Lowest level Highest Level Function Read Allows access to read master station status and settings, plus the option module status and settings, plus the actuator and field unit status on the option module network. No commands or alterations to the system are permitted. Write As for read access with the addition of the ability to issue network commands, swap masters and command actuators on the option module network to change position. Administrator As for the two lower levels plus the ability to configure the master station, option modules and all system settings. Set and remove user names and passwords; set alarm reporting parameters, change system addresses and test system communications. The Administrator level sets all other user names and passwords. As soon as the system is set up the default password should be changed. Make sure all changes made to log in details are recorded. 7.4.2 Overview of Web Page Layout The web pages are organised using a menu structure with the primary menu on the top of each page. Within a page there are other controls for parameter alteration or to reveal extended information on the topic of the particular page. Navigation between the pages is by selecting another topic on the main menu. If there is no activity with the mouse to change the display or update the information or selection for a few minutes, the system automatically logs out the user. The username and password must be reentered to continue using the pages. 52 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages Log In Master Station View Configuration System Diagnostics Master Station Log Host Analyser Option Diagnostics Network Diagnostics Option Event Log FCU Menu FCU Admin* Users Master Station and Option Configuration Host Ports Alarms Time General Network * requires Admin level log in Fig 34: Web Page Menu Layout Issue 05/12 Publication PUB059-002-00 53 of 134 P3 - Pakscan Master Station Technical Manual 7.5 The Web Pages in Detail 7.5.1 Fig 35: Log In Screen Web page Log In Screen The first screen is the Log In screen on which the user must enter a Username and Password. Username - a case sensitive identification for an individual or group used to give access to the system. User names are listed for administrators to see on the ‘Add User’ page. Password - the case sensitive confirmation required before a username is accepted by the system. Passwords are not listed on any page in the system and cannot be retrieved, even at the administrator level. Select the box with the mouse and enter the appropriate name or password, then click on the login button. The system will move to the next page if the login is accepted. If it fails, the data is cleared from the boxes and must be re-entered correctly in both boxes before access is granted. The default user name is admin and default password is admin. The password should be altered as soon as convenient to prevent unauthorised access to the system. User name and access level. Log out when finished by clicking here (changes to red when selected). Menu of available screens to visit (changes to blue when selected) for Read and Write access levels Fig 36: 54 of 134 Web page Header Navigation Publication PUB059-002-00 Issue 05/12 7. Internal Web pages 7.5.2 Master Station Site Name Tag Name Status Option Module 1 Option Module 2 Status Controls Fig 37: Master Station Overview web page and Option 1 data, if a Wireless module is fitted This screen is accessible to Read, Write and Administrator user levels. This screen reports the current status of the master station and the option modules fitted. The picture shows the master station, single or hot standby version. The green, orange and red lights show the condition of the associated parameter. Greyed out text and lights are not applicable or else in a safe (normal) condition. Master station CPU Module Site name : The name of the site where the system is located, as entered during configuration. Tag name : The master station tag, as entered during configuration. Status Location A/B Issue 05/12 : Indicates the CPU module currently in communication over the Ethernet. Publication PUB059-002-00 55 of 134 P3 - Pakscan Master Station Technical Manual Primary/Standby Module Health ESD Presence Redundancy Option Other Master Station health Alarm : Shows the condition of the CPU with regard to controlling the option modules. The Primary CPU is in control. A Standby CPU is prepared to become the Primary and take control if the partner unit fails. : Indicates the absence (green light) or presence (red light) of a fault on the CPU. : Shows a yellow light if an Emergency Shut Down signal is active. : Shows a green light if there is a partner module fitted. : Indicates the absence (green light) or presence (red light) of a fault on the partner CPU. : Indicates the presence of an alarm (red light) somewhere on the system. Option 1 and Option 2 - Show the type of Option module fitted, either: Pakscan 2 Loop Option Module Loopback in : A blue light shows whilst the master station is reconfiguring the loop. Progress Loopback in Use : A yellow light shows when the master station has detected a loopback fault on the system. Auto Loopback : If a fault occurs on the network and an automatic reconfiguration of the occurred loop occurs, then a yellow light is shown here. Common Field : A red light shows if any field unit on the network has an alarm bit present. Unit Alarm Common : A red light shows if any actuator on the network is unavailable due to its Actuator Alarm monitor relay having tripped. ESD Active : If there is an Emergency Shut Down signal present on the system a red light shows. Pakscan 3 Wireless Option Module Configuration in : A blue light shows whilst the master station is reconfiguring the network. Progress : A Green light shows when the master station has detected NO faults in Network Healthy the network and it is healthy. Field Unit Alarm : A Red light shows when the master station has detected an alarm on any of the field units. Field unit Comms : A Red light shows when the master station has detected a fail communications failure to a field unit. ESD Active : If there is any Emergency Shut Down signal present for that network on the system a red light shows. Controls - Not Available for Read level users Network ESD : Click here to issue an ESD to all actuators connected to both option modules. The resulting action will depend on the individual actuator settings. A confirmation screen appears to verify or cancel the instruction before the action occurs. Changeover : Only applicable to hot standby systems. Click this button to make the Master master station CPU in control; change from A to B or B to A. 56 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages 7.5.3 Fig 38: View Configuration System Configuration Overview web page This screen is accessible to Read, Write and Administrator user levels. The screen shows the settings for the control of the option module networks and the CPU control capability, software fitted and various options selected. All of these settings can be modified elsewhere, but only by users with Administrator level access. There are no controls on this page. The settings are explained in the Master Station Configuration page section. Issue 05/12 Publication PUB059-002-00 57 of 134 P3 - Pakscan Master Station Technical Manual 7.5.4 System Diagnostics Master Station CPU Status Controls Option Module 1 Controls Option Module 2 Controls Fig 39: System Diagnostics web page wired only and option 1 data, if wireless fitted This screen is accessible to Read, Write and Administrator user levels. The System Diagnostics screen shows an overview of the status of the fitted modules and also provides access to further information. Master Station Diagnostics Module Health : A green light shows if the module is operating correctly, changes to red if there is a fault. Primary/Standby : Indicates which module is being accessed. A green light indicates Primary, a yellow light indicates Standby and a red light indicates a fault. Redundancy : Shows a green light if there is a partner module fitted. Option Other Master : Indicates the absence (green light) or presence (red light) of a fault on the Station Health partner CPU. Host port 1 : Indicates when there is serial communication taking place on activity communications port 1. Host port 2 : Indicates when there is serial communication taking place on activity communications port 2. Modbus/TCP : Indicates when Ethernet control using Modbus/TCP is present on either activity Ethernet port. 58 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages Controls - Available to all user levels ms datalogger : Reveals a pop-up showing a log of the activity on the master station and the source of requests or commands received. See section 7.5.5 for details. host analyser : Reveals a pop-up with the data logger data and the additional controls required for using the inbuilt data analyser for commands and data sent to the host system. See section 7.5.6. Option 1 Diagnostics Pakscan wireless network Option Health Shows module type and status, or ‘Not Fitted’ when there is nothing in the slot. Shows a green light when healthy and a red light if there is a fault on the module. Option 2 Diagnostics Pakscan 2 Loop : Shows module type and status, or ‘Not Fitted’ when there is nothing in the slot. Option Health : Shows a green light when healthy and a red light if there is a fault on the module. Controls - Available (when module fitted) to all user levels diagnostics : Reveals the diagnostic page for the option module fitted. See section 7.5.7 Pakscan 2 Loop and section 7.5.8 Pakscan Wireless. event log : Shows the option module event recorder. See section 7.5.9 Pakscan 2 Loop and section 7.5.10 Pakscan Wireless. Issue 05/12 Publication PUB059-002-00 59 of 134 P3 - Pakscan Master Station Technical Manual 7.5.5 Master Station Data Logger [ms datalogger] Close pop-up Master Station Events Controls Fig 40: Master Station Data Logger pop-up This screen is accessible to Read, Write and Administrator user levels. The data logger displays Modbus instructions received by the master station to carry out commands such Alarm Accept or commands to move a valve. Each event is prefixed by a date and time and they are listed in time order. They are followed by the source from which the command originated. Once full the log rolls over and rewrites over the oldest events, the log is 1Mbyte in size. Date and Time Fig 41: Modbus Message Message Source / Address Close up of Master Station Data Logger Information Date and Time Formatted Day/Month/Year or Month / Day / Year. Modbus Message Standard Modbus RTU format for all ‘write’ messages. Message Source and Address Display : Keypad on the master station CPU. Ethernet : Ethernet input and IP address of the source. RTU : Serial port 1 (RTU 1) or serial port 2 (RTU 2). Webpages : Web page Log In name and IP address. 60 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages Controls - Available to all user levels Print : Prints the logger data to a printer attached to the computer. Save : Saves the logger data to a file on the computer. The saved file is of the type cmdlog.log and can be opened in the Notepad on the computer. It can also be imported into a spreadsheet, such as Excel, for analysis as required. Refresh : Updates the screen with any new data. Fig 42: Saving the master station log file Issue 05/12 Publication PUB059-002-00 61 of 134 P3 - Pakscan Master Station Technical Manual 7.5.6 Master Station Host Analyser [host analyser] Close pop-up Analyser Events Controls Fig 43: Host Analyser pop-up This screen may be used by Administrator user level only. The Host Analyser is a real time system analyser that can be used with either a Modbus RTU serial data control source, acting through one of the serial data ports (Port 1 or 2), or a Modbus TCP Ethernet control source, acting through the Ethernet ports. The analyser will record up to 100 messages (requests and responses) on the data line between the two points. It is especially useful for debugging a host control system to ensure that messages are correctly formatted and that the required control or data points are being accessed. In particular, the use of correct offsets in the Modbus protocol can be checked. Controls - Available to Administrator user level RTU1 : Selects Serial Port 1 host input. RTU2 : Selects Serial Port 2 host input. ETH : Selects the Ethernet port host input (all Ethernet ports are monitored). Print : Prints the analyser data to a printer attached to the computer. Save : Saves the analyser data to a file on the computer. Refresh : Updates the screen with any new data. 62 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages 7.5.7 Pakscan 2 Loop Diagnostics [diagnostics] Network Information Controls Network FCU Map Fig 44: Pakscan 2 Loop Diagnostics web page This screen is accessible to Read, Write and Administrator user levels. The Pakscan 2 Loop Diagnostics screen gives diagnostic information on the 2-wire loop option module and the network connected to it. The top part of the screen shows the information about the option module itself, whilst the lower part shows the loop map. This is the order in which the field units on the 2-wire loop are connected. It also shows the device type and tag name for each address and position. Issue 05/12 Publication PUB059-002-00 63 of 134 P3 - Pakscan Master Station Technical Manual Network Diagnostics No. Of Devices On Network No. Of FCUs Found Configuration Status : This is the number of field units that are expected to be located on the network. It is the highest address that the network will scan up to when locating field units. All field units need to be consecutively addressed, and there should be no gaps in the addresses. : This is the total number of field units located on the network. If all the field units are powered on and connected, then the number will equal the No. Of Devices On The Network above. : This field shows any fault that exists on the network cabling and the stages passed through as network configuration takes place. During configuration the following sequence can be displayed 1. Wait for Loopbacks 1 (first wait for loopbacks to come on) 2. Find FCUs on Port A (finding FCUs on port A) 3. Test Loop (testing for complete loop) 4. Find FCUs on Port B (finding FCUs on port B) 5. Wait for Loopbacks 2 (second wait for loopbacks to come on) 6. Loopbacks off on A (removing loopbacks from port A) 7. Loopbacks off on B (removing loopbacks from port B) (The normal sequence for a fault-free loop would be 1, 2 and 3. A sequence for a break in the loop, anywhere except at port A or port B, would be 1 to 7. Some of the phases may be very quick, particularly at higher baud rates, and so may not be seen on the browser display. Whilst the configuration is taking place, the master station web page shows ‘Loopback in Progress’ and a blue light on the Option module. If the configuration process detects a fault on the loop and switches on the loopback circuits of two field units, the master station web page shows ‘Loopback in Use’ and illuminates the yellow light. Last Network Reset Initiated By 64 of 134 : The loop can be reconfigured for a number of reasons and this field will show the cause of the last reset/reconfigure that occurred. The possible reasons are: Power on Reset - loop configured because the master station powered up. Fault Found - fault detected on the loop whilst it was running without loopbacks present. Fault Found A - fault detected on the A side of broken loop whilst running with loopbacks on. Fault Found B - fault detected on the B side of broken loop whilst running with loopbacks on. Reset Command - loop Reconfigure command entered from keypad or serial port. Return wire fault - fault detected in the return current path whilst the loop was running at double speed. Doubling failed - fault detected after loop assumed double speed. Publication PUB059-002-00 Issue 05/12 7. Internal Web pages Network Fault Type : This field shows the type of fault detected that caused the loopback to occur, or an addressing fault on the field units. The types are: Zero Address Address too High xx Same Address xx Loop Open Circuit Loop Short Circuit - a field unit has been found with an address of zero. - a field unit has been found with an address higher than that set up within the master station; xx is the address. - two field units found with the same address; xx is the address. - an open-circuit fault found on the loop. - a short-circuit fault found on the loop. If two field units are found with the same address, or there is an address outside the range of addresses expected (as set by No. of Devices on Network), the network will continue to operate and miss out the faulty field units. Loop Baud Rate : Shows the current speed selected. The speed can be 110, 300, 600, 1200, or 2400 baud. No. Of FCUs On Side A : This is the total number of field units connected to the option module Port A and communicating via Port A. No. Of FCUs On Side B : This is the total number of field units connected to the option module Port B and communicating via Port B. Port B is only used if there is a loopback present on the network. Controls - Available to all user levels Reset network : Causes the option module to reconfigure the 2-wire network. This should be used after a loop fault has been corrected. Network Map The map shows the order in which the field units have been identified and found by the option module during the last loop reconfiguration process (reset). Each time the loop is reconfigured the map is regenerated and repopulated. Any field unit that is not powered-up at the time of reconfiguration will be absent from the map. Position Address Failures Issue 05/12 : The position in the loop. Number 1 is nearest to Port A. : The address of the field unit. : Shows a count of communication errors with the field unit. The count has a range of 0 to 255, after which it rolls around to zero and it increments for every communication error. The system will only announce a ‘Comms failure’ when 3 successive tries have failed to locate the field unit. This counter therefore reflects the communications condition and can be used as an indicator of the health of the field unit to assess the probability of failure in the future. Publication PUB059-002-00 65 of 134 P3 - Pakscan Master Station Technical Manual Type Tag Name 7.5.8 : The type of field unit depends on the actuator and function required. Current types are IQ - IQ or IQT actuator Integral - Non IQ actuator Flowpak - Flowpak actuator GPFCU - GP - General Purpose Field Unit GPFCU - Act - General Purpose in Actuator mode IQA - IQ Analogue card ROMpak - ROMpak actuator : The associated identification Tag assigned to this field unit. Pakscan Wireless Diagnostics [diagnostics] Network Information Controls Fig 45: Pakscan Wireless Diagnostics web page This screen is accessible to Read, Write and Administrator user levels. The Pakscan Wireless Diagnostics screen gives diagnostic information on the wireless option module and the network connected to it. 66 of 134 No of Devices On Network This is the number of wireless field units that are expected to be located on the network. This is set up in the master station configuration web page. No of FCUs found This is the total number of field units found on the network. If all the field units are powered on and able to communicate, the number will equal the number expected on the network. Wireless repeater nodes expected This is the number of wireless repeater modules that are expected to be located on the network. This is set up in the master station configuration web page. Wireless repeater nodes found This is the total number of wireless repeater nodes found on the network. If all the repeater nodes are powered on and able to communicate, the number will equal the number expected on the Publication PUB059-002-00 Issue 05/12 7. Internal Web pages network. During configuration of the wireless network the network goes through various stages as indicated below. Some of the stages can be quite quick and therefore may not be seen: Uninitialised. Initialised / starting up. Detecting field units. Building map of field units. Detecting field units complete. Obtaining initial field unit data. Field unit data collection complete. Network Ready to run. Master station updating RF parameters. After a reset network command is sent from the web page, the normal sequence seen would be: Initialised / starting up, Detecting Complete, Obtaining initial Data, Data collection complete, Ready to run. ‘Ready to run’ is the normal state of a good network. Configuration Status Last Network Reset Initialised By This field indicates the cause of the last reset, this can either be due to a power cycle (value will be 00), as a result of receiving a reset network command, due to a parameter change causing the Coordinator to reset or due to a Radio communications parameter change. Network Fault Type This field indicates any faults on the network. Faults reported can be: Wireless coordinator fault. Insufficient wireless neighbours for the coordinator or the field units, the intention is always to have at least 2 neighbours. RF parameter change failed. Duplicate field unit address detected. Issue 05/12 Publication PUB059-002-00 67 of 134 P3 - Pakscan Master Station Technical Manual 7.5.9 Pakscan 2 Loop Option Module Event Logger [Event Log] Close pop-up Event Log Controls Fig 46: Wired Option Module Event Logger pop-up This screen is accessible to Read, Write and Administrator user levels. The event logger shows the last occurrence of the listed events and, in the case of an ESD, where the signal originated. Controls - Available to all user levels Print : Prints the logger data to a printer attached to the computer. Save : Saves the logger data to a file on the computer. Refresh : Updates the screen with any new data. 68 of 134 Publication PUB059-002-00 Issue 05/12 7. Internal Web pages 7.5.10 Pakscan Wireless Option Module Event Logger [Event Log] Close pop-up Event Log Controls Fig 47: Wireless Option Module Event Logger pop-up This screen is accessible to Read, Write and Administrator user levels. The event logger shows the last occurrence of the listed events. In the case of an ESD, where the ESD signal originated is reported. In the case of the last field unit comms fail, it also indicates which field unit lost communications. Controls - Available to all user levels Print : Prints the logger data to a printer attached to the computer. Save : Saves the logger data to a file on the computer. Refresh : Updates the screen with any new data. Issue 05/12 Publication PUB059-002-00 69 of 134 P3 - Pakscan Master Station Technical Manual 7.5.11 FCU Menu Network Information Controls Fig 48: FCU Menu web page This screen is accessible to Read, Write and Administrator user levels. The FCU Menu lists all the field units in address order (which may not be the same as the order in which they are connected together on the wired loop). For each address, the Tag name and Type of field unit is listed. Field unit types are described in section 7.5.7. The Network column shows which option module network each actuator is connected to; this will be Pakscan 2 for the 2-wire loop option module and Wireless for the wireless option. The next two columns show critical alarm conditions that will prevent remote control of the actuator. An Alarm present will generally prevent operation, whilst Comms Fail indicates that the actuator is no longer in communication with the field network. The final column has Navigation controls to the individual FCU screens. Controls - Available to all user levels FCU Control : Click here to show the selected FCU individual control panel web page. The different types of devices each have different screens and only the relevant data and controls for each type are included on the screen, together with a picture identifying the type of device. When not in communication the screen may still be visited, but the actuator picture will have a large red cross over it to show that a problem exists. 70 of 134 Publication PUB059-002-00 Issue 05/12
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.5 Linearized : Yes Page Count : 70 XMP Toolkit : XMP toolkit 2.9.1-13, framework 1.6 About : uuid:1d18709a-6c49-41f0-8d0f-1936d5639514 Modify Date : 2012:10:24 14:23:04+01:00 Create Date : 2012:10:24 14:22:47+01:00 Metadata Date : 2012:10:24 14:23:04+01:00 Document ID : uuid:5111c5f8-c57c-4f8b-9d54-506e9a2f5cdc Format : application/pdf Producer : doPDF Ver 7.3 Build 382 (Windows 7 Enterprise Edition (SP 1) - Version: 6.1.7601 (x64))EXIF Metadata provided by EXIF.tools