Rts Kgatx0101400 Users Manual 0G1622 Rev0
KGATX0101400 to the manual fffd27ed-5620-4fcf-aa62-9a98225364d1
2015-02-06
: Rts Rts-Kgatx0101400-Users-Manual-525552 rts-kgatx0101400-users-manual-525552 rts pdf
Open the PDF directly: View PDF .
Page Count: 16
Download | |
Open PDF In Browser | View PDF |
RTS Automatic Transfer Switch 400A, 120/240V, Single-phase Model No.: KGATX0101400 TECHNICAL MANUAL A new standard of reliability This manual should remain with the unit. Important Safety Instructions Also read the instructions and information on tags, decals, and labels that may equipment. be affixed to the transfer switch. Replace any decal or label that is no longer legible. Read the following information carefully before attempting to install, operate or service this shall be by means of suitable transfer equipment so as to isolate the electric system utility from utility distribution system when the generator is operating (Article 701 Legally Required DANGER! Connection of a generator to an electrical system normally supplied by an electric Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these means may result in damage to generator and may result in injury or death to utility workers due to backfeed of electrical energy. The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the transfer switch unsafe. Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instruction about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. The definitions are as follows: DANGER After this heading, read instructions that, if not strictly complied with, will result in personal injury or property damage. After this heading, read instructions that, if not strictly complied with, may result in personal injury or property damage. After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property. NOTE: After this heading, read explanatory statements that require special emphasis. These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the service are essential to preventing accidents. Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows: symbol points out important safety infor This mation that, if not followed, could endanger personal safety and/or property of others. symbol points out potential explosion This hazard. This symbol points out potential fire hazard. symbol points out potential electrical shock This hazard. GENERAL HAZARDS • Any AC generator that is used for backup power if a NORMAL (UTILITY) power source failure occurs, must be isolated from the NORMAL (UTILITY) power source by means of an approved transfer switch. Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers, due to backfeed of electrical energy. • Improper or unauthorized installation, operation, service or repair of the equipment is extremely dangerous and may result in death, serious personal injury, or damage to equipment and/or personal property. • Extremely high and dangerous power voltages are present inside an installed transfer switch. Any contact with high voltage terminals, contacts or wires will result in extremely hazardous, and possibly LETHAL, electric shock. DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF. • Competent, qualified personnel should install, operate and service this equipment. Adhere strictly to local, state and national electrical and building codes. When using this equipment, comply with regulations the National Electrical Code (NEC), CSA Standard; C22.1 Canadian Electric Code and Occupational Safety and Health Administration (OSHA) have established. • Never handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT. Table of Contents • Because jewelry conducts electricity, wearing it may cause dangerous electrical shock. Remove all jewelry (such as rings, watches, bracelets, etc.) before working on this equipment. • If work must be done on this equipment while standing on metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats. • Never work on this equipment while physically or mentally fatigued. • Keep the transfer switch enclosure door closed and bolted at all times. Only qualified personnel should be permitted access to the switch interior. • In case of an accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor but AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help. • When an automatic transfer switch is installed for a standby generator set, the generator engine may crank and start at any time without warning. To avoid possible injury that might be caused by such sudden start-ups, the system’s automatic start circuit must be disabled before working on or around the generator or transfer switch. Turn the generator’s AUTO/OFF/MANUAL switch to OFF. Turn the generator’s main circuit breaker OFF. Then place a “DO NOT OPERATE” tag on the transfer switch and on the generator. Remove the Negative (Neg) or (–) battery cable. Safety Rules .........................................Inside Front Cover Section 1 — General Information ...................................2 1.1 Introduction............................................................. 2 1.2 Equipment Description ........................................... 2 1.3 Transfer Switch Data Label ..................................... 2 1.4 Transfer Switch Enclosure ...................................... 2 1.5 Safe Use of Transfer Switch .................................... 2 Section 2 — Installation ....................................................3 2.1 Introduction to Installation ...................................... 3 2.2 Unpacking ............................................................... 3 2.3 Mounting ................................................................. 3 2.4 Connecting Power Source and Load Lines ............... 3 2.4.1 2-Pole Mechanism ......................................... 3 2.5 Connecting Start Circuit Wires ................................ 4 2.6 Auxiliary Contacts.................................................... 4 Section 3 — Operation.......................................................4 3.1 Functional Tests & Adjustments .............................. 4 3.2 Manual Operation .................................................... 5 3.2.1 Close to Normal Source Side ........................ 5 3.2.2 Close to Emergency Source Side ................... 6 3.2.3 Return to Normal Source Side ...................... 6 3.3 Voltage Checks......................................................... 6 3.3.1 Utility Voltage Checks .................................... 6 3.3.2 Generator Voltage Checks.............................. 6 3.4 Generator Tests Under Load ................................... 7 Section 4 – Installation Diagram ....................................8 Section 5 – Electrical Data ...............................................9 Section 6 – Exploded Views & Parts Lists ..................12 Section 7 – Warranty ...................................... Back Cover 1 Section 1 — General Information RTS “W” Type Transfer Switch 1.1 INTRODUCTION This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect application, or improper procedures. Every effort has been expended to make sure that the contents of this manual are both accurate and current. The manufacturer reserves the right to change, alter or otherwise improve the product at any time without prior notice. 1.2 EQUIPMENT DESCRIPTION The automatic transfer switch is used for transferring critical electrical loads from a UTILITY (NORMAL) power source to an EMERGENCY (GNERATOR) power source. The transfer switch prevents electrical feedback between the UTILITY and EMERGENCY sources. For that reason, electrical codes require a transfer switch in all standby electric system installations. When the transfer switch is connected to the engine generator control panel, the control panel constantly monitors the UTILITY voltage and controls the operation of the transfer switch. Should the UTILITY voltage drop below a preset value, and remain at this low voltage for a preset amount of time, the generator cranks and starts. After the generator starts, the transfer switch transfers the load circuits to the generator, the generator then supplies the loads. When UTILITY returns above a preset level the load is transferred back to the UTILITY and the generator shuts down. 1.3 TRANSFER SWITCH DATA LABEL A DATA LABEL is permanently affixed to the transfer switch enclosure. Use this transfer switch only with the specific limits shown on the DATA LABEL and on other decals and labels that may be affixed to the switch. This will prevent damage to equipment and property. When requesting information or ordering parts for this equipment, make sure to include all information from the DATA LABEL. Record the Model and Serial numbers in the space provided below for future reference. MODEL # SERIAL # 1.4 TRANSFER SWITCH ENCLOSURE The standard switch enclosure is a National Electrical Manufacturer’s Association (NEMA) and UL 3R type. UL and NEMA 3R type enclosures primarily provide a degree of protection against falling rain and sleet; undamaged by the formation of ice on the enclosure. 1.5 SAFE USE OF TRANSFER SWITCH Before installing, operating or servicing this equipment, read the SAFETY RULES (inside front cover) carefully. Comply strictly with all SAFETY RULES to prevent accidents and/or damage to the equipment. The manufacturer recommends a copy of the SAFETY RULES are made and posted near the transfer switch. Also, be sure to read all instructions and information found on tags, labels and decals affixed to the equipment. Two publications that outline the safe use of transfer switches are the following: • NFPA 70; National Electrical Code • UL 1008, STANDARD FOR SAFETY-AUTOMATIC TRANSFER SWITCHES NOTE: It is essential to use the latest version of any standard to ensure correct and current information. 2 Section 2 — Installation RTS “W” Type Transfer Switch 2.1 INTRODUCTION TO INSTALLATION This equipment has been wired and tested at the factory. Installing the switch includes the following procedures: • Mounting the enclosure. • Connecting utility and generator power source leads. • Connecting the load leads. • Connecting any auxiliary contact (if needed) • Installing/connecting any options and accessories. • Testing functions. 2.2 2.4.1 2-POLE MECHANISM These switches (Figure 2.1) are used with a single phase system, when the single phase NEUTRAL line is to be connected to a Neutral Lug and is not to be switched. Figure 2.1 — Typical 2-Pole Transfer Mechanism (400 Amp Shown) UNPACKING Carefully unpack the transfer switch. Inspect closely for any damage that might have occurred during shipment. The purchaser must file with the carrier any claims for loss or damage incurred while in transit. Check that all packing material is completely removed from the switch prior to installation. 2.3 MOUNTING Mounting dimensions for the transfer switch enclosure are in this manual. Enclosures are typically wallmounted. See the “Mounting Dimensions” drawing. transfer switches carefully when install Handle ing. Do not drop the switch. Protect the switch against impact at all times, and against construction grit and metal chips. Never install a transfer switch that has been damaged. Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure. To prevent switch distortion, level all mounting points. If necessary, use washers behind mounting holes to level the unit. 2.4 CONNECTING POWER SOURCE AND LOAD LINES DANGER sure to turn OFF both the UTILITY Make (Normal) and EMERGENCY (Standby generator) power supplies before trying to connect power source and load lines to the transfer switch. Supply voltages are extremely high and dangerous. Contact with such high voltage power supply lines causes extremely hazardous, possibly lethal, electrical shock. Wiring diagrams and electrical schematics are provided in this manual. Power source and load connections are made at the transfer mechanism, inside the switch enclosure. Solderless, screw-type terminal lugs are standard. The conductor size range is as follows: Switch Rating Wire Range 400A (1) #4-600 MCM or (2) 1/0-250 MCM Conductor sizes must be adequate to handle the maximum current to which they will be subjected; based on the 75°C column of tables, charts, etc. used to size conductors. The installation must comply fully with all applicable codes, standards and regulations. Before connecting wiring cables to terminals, remove any surface oxides from the cable ends with a wire brush. All power cables should enter the switch next to transfer mechanism terminals. If ALUMINUM conductors are used, apply corrosion inhibitor to conductors. Tighten terminal lugs to the torque values as noted on the decal located on the inside of the door. After tightening terminal lugs, carefully wipe away any excess corrosion inhibitor. All power cables should enter the switch next to the transfer mechanism terminals. 3 Section 3 — Operation RTS “W” Type Transfer Switch NOTE: Use a torque wrench to tighten the conductors, being sure not to overtighten, or damage to the switch base could occur. If undertightened, a loose connection would result, causing excess heat which could damage the switch base. Connect power source load conductors to clearly marked transfer mechanism terminal lugs as follows Auxiliary Contacts are rated 10 amps at 125 or 250 volts AC. DO NOT EXCEED THE RATED VOLTAGE AND CURRENT OF THE CONTACTS. Figure 2.3 – Auxiliary Contacts 1. Connect UTILITY (NORMAL) power source cables to switch terminals N1, N2, (N3). 2. Connect EMERGENCY (STANDBY) source power cables to transfer switch terminals E1, E2, (E3). 3. Connect customer LOAD leads to switch terminals T1, T2, (T3). 4. Connect neutral conductors of UTILITY, EMERGENCY and customer LOAD to the neutral block. Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes. Side views shown in Utility position Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits. 2.5 CONNECTING START CIRCUIT WIRES Control system interconnections consist of UTILITY 1 and 2, and leads 23 and 194. Control system interconnection leads must be run in a conduit that is separate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below: MAXIMUM WIRE LENGTH 460 feet (140m) 461 to 730 feet (223m) 731 to 1,160 feet (354m) 1,161 to 1,850 feet (565m) 2.6 RECOMMENDED WIRE SIZE No. 18 AWG. No. 16 AWG. No. 14 AWG. No. 12 AWG. AUXILIARY CONTACTS If desired, there are Auxiliary Contacts on the transfer switch to operate customer accessories, remote advisory lights, or remote annunciator devices. A suitable power source must be connected to the COMMON (C) terminal. See Figure 2.3. Contact operation is shown in the following chart: Common to Normally Open Common to Normally Closed 4 Switch Position Utility Standby Open Closed Closed Open 3.1 FUNCTIONAL TESTS AND ADJUSTMENTS Following transfer switch installation and interconnection, inspect the entire installation carefully. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regulations. When absolutely certain the installation is proper and correct, complete a functional test of the system. functional tests in the exact order pre Perform sented in this manual, or damage to the switch could be done. IMPORTANT: Before proceeding with functional tests, read and make sure you understand all instructions and information in this section. Also read the information and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation. Section 3 — Operation RTS “W” Type Transfer Switch 3.2 MANUAL OPERATION DANGER NOT manually transfer under load. Do Disconnect transfer switch from all power sources by approved means, such as a main circuit breaker(s). A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically. To check manual operation, proceed as follows: 1. Turn the generator’s AUTO/OFF/MANUAL switch to OFF. 2. Turn OFF both UTILITY and EMERGENCY power supplies to the transfer switch, with whatever means provided (such as the main line circuit breakers). 3. Note position of transfer mechanism main contacts by observing display windows in “A” and “B” in Figure 3.1 on page 6 as follows: • Window “A” ON, Window “B” OFF - LOAD terminals (T1, T2, T3) are connected to utility terminals (N1, N2, N3). • Window “A” OFF, Window “B” ON - LOAD terminals (T1, T2, T3) are connected to emergency terminals (E1, E2, E3). not use excessive force when operating the Do transfer switch manually or the manual handle could be damaged. 3.2.1 CLOSE TO NORMAL SOURCE SIDE Before proceeding, verify the position of the switch by observing window “A” in Figure 3.1. If window “A” reads “ON”, the contacts are closed in the normal position, no further action is required. If it reads “OFF”, proceed with Step 1. Step 1: With the handle attached to the actuating shaft, move handle in the direction of the arrow on the switch cover until it stops — DO NOT FORCE. Release handle slowly to allow the spring in the switch box to relax. “ON” now appears in Window “A” and “OFF” appears in Window “B”. Figure 3.1 — Actuating Transfer Switch 5 Section 3 — Operation RTS “W” Type Transfer Switch 3.2.2 CLOSE TO EMERGENCY SOURCE SIDE 3.3.2 GENERATOR VOLTAGE CHECKS Before proceeding, verify the position of the switch by observing window “B” in Figure 3.1. If window “B” reads “ON”, the contacts are closed in the EMERGENCY (STANDBY) position. No further action is required. If it reads “OFF”, proceed with Step 1. 1. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL position. The generator should crank and start. 2. Let the generator stabilize and warm up at noload for at least five minutes. 3. Set the generator's main circuit breaker (CB1) to its ON or CLOSED position. Step 1: With the handle attached to the actuating shaft, move the handle in the direction of the arrow on the switch cover until it stops - DO NOT FORCE. Release handle slowly to allow the spring in the switch box to relax. “OFF” now appears in Window “A” and “ON” appears in Window “B”. 3.2.3 RETURN TO NORMAL SOURCE SIDE Manually actuate switch to return Window “A” to the “ON” position. 3.3 VOLTAGE CHECKS 3.3.1 UTILITY VOLTAGE CHECKS 1. Turn ON the UTILITY power supply to the transfer switch with whatever means provided (such as the UTILITY maim line circuit breaker). DANGER WITH CAUTION. THE TRANSFER PROCEED SWITCH IS NOW ELECTRICALLY HOT. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY HAZARDOUS AND POSSIBLY FATAL ELECTRICAL SHOCK. 2. With an accurate AC voltmeter, check for correct voltage. Single-phase utility supply: Measure across ATS terminal lugs N1 and N2; N1 to NEUTRAL and N2 to NEUTRAL. DANGER TO TURN OFF THE UTILITY SUPPLY FAILURE BEFORE WORKING ON THE UTILITY CONNECTIONS OF THE ATS WILL RESULT IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK. 5. When certain that UTILITY supply voltage is correct and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch. 6 DANGER WITH CAUTION. GENERATOR PROCEED OUTPUT VOLTAGE IS NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK. 4. With an accurate AC voltmeter and frequency meter, check the no-load, voltage and frequency. Single-phase generator supply: Measure across ATS terminal lugs E1 to E2; E1 to NEUTRAL and E2 to NEUTRAL. a. b. c. d. Frequency ....................................... 60-62 Hz Terminals E1 to E2 ........................ 240-246 VAC Terminals E1 to NEUTRAL............. 120-123 VAC Terminals E2 to NEUTRAL............. 120-123 VAC 5. When certain that UTILITY supply voltage is correct and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch. 6. Set the generator’s main circuit breaker (CB1) to its OFF or OPEN position. 7. Set the AUTO/OFF/MANUAL switch to the OFF position to shut down the generator. NOTE: Do NOT proceed until generator AC output voltage and frequency are correct and within stated limits. If the no-load voltage is correct but noload frequency is incorrect, the engine governed speed probably requires adjustment. If no-load frequency is correct but voltage is not, the voltage regulator may require adjustment. Section 3 — Operation RTS “W” Type Transfer Switch 3.4 GENERATOR TESTS UNDER LOAD 1. Set the generator's main circuit breaker to its OFF or OPEN position. 2. Manually actuate the transfer switch main contacts to their EMERGENCY (STANDBY) position. Refer to “Manual Operation” section. 3. To start the generator, set the AUTO/OFF/MANUAL switch to MANUAL. When engine starts, let it stabilize for a few minutes. 4. Turn the generator's main circuit breaker to the ON or CLOSED position. The generator now powers all LOAD circuits. Check generator operation under load as follows: • Turn ON electrical loads to the full rated wattage/amperage capacity of the generator. DO NOT OVERLOAD. • With maximum rated load applied, check voltage and frequency across transfer switch terminals E1 and E2. Voltage should be greater than 200 volts (208VAC system) or 230 volts (240VAC system); frequency should be greater than 59 Hz. • Let the generator run under rated load for at least 30 minutes. With unit running, listen for unusual noises, vibration, overheating, etc., that might indicate a problem. 5. When checkout under load is complete, set main circuit breaker of the generator to the OFF or OPEN position. 6. Let the generator run at no-load for several minutes. Then, shut down by setting the AUTO/OFF/ MANUAL switch to its OFF position. 7. Move the switch's main contacts back to the UTILITY position. For example, load connected to utility power supply. Refer to “Manual Operation”. Handle and operating lever of transfer switch should be in down position. 8. Turn on the utility power supply to transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads. 9. Set the generator's AUTO/OFF/MANUAL switch to its AUTO position. The system is now set for fully automatic operation. 7 8 TRIPLE EKO SUITABLE FOR 1", 1.25" & 1.50" CONDUIT 3 PLACES 254mm[10.0"] 917mm[36.1"] 609.6mm[24.0"] 487mm[19.2"] MOUNTING HOLES: Ø6.35mm[Ø0.25"] 4-PLACES 60.8mm[2.4"] 794mm[31.3"] 61.3mm[2.4"] Section 4 — Installation Diagram RTS “W” Type Transfer Switch Installation Diagram – Drawing No. 0F6401 Section 5 — Electrical Data RTS “W” Type Transfer Switch Interconnection Diagram - Drawing No. 0G1944 9 Section 5 — Electrical Data RTS “W” Type Transfer Switch Wiring Diagram/Schematic – Drawing No. 0D3819-A TR F1 1 126 N1A 7 N1 N1A F2 N2 N2A N2A 126 N1A A1 B1 T1 205 T2 LS1 2 3 5 6 LS3 6 RED TR 9 N2A WHITE C 1 E1 LS2 A2 4 GTS B2 E1 E2 N2A B LEGEND 23 23 TR C - CONTACTOR ACTUATING COIL GTS - TRANSFER SWITCH CONTACTOR TR - RELAY, TRANSFER TS - TERMINAL STRIP (CUSTOMER CONNECTION) LS1,LS2,LS3 - LIMIT SWITCHES, ACTUATOR F1,F2 - FUSE 5A SENSING A 194 NOTES: ALL CONTACTS SHOWN WITH TRANSFER SWITCH IN UTILITY POSITION. 10 194 Section 5 — Electrical Data RTS “W” Type Transfer Switch Wiring Diagram/Schematic – Drawing No. 0D3819-A N2A N2A N1A N1A N1 N2 E1 E2 T1 T2 GTS N1A T2 T1 B2 B1 A2 A1 N2A E2 N2A 205 N2A E1 126 N1A TR N1A 126 205 A 7 B 9 N2A N1A 1 3 194 23 205 E1 23 194 N1A N2A N1A N2A N1A 23 194 F1 F2 N1 N2 23 194 194 23 UTILITY 2 UTILITY 1 TS 11 Section 6 — Exploded Views and Parts List RTS “W” Type Transfer Switch 400 A Switch Assembly – Drawing No. 0G1510$ 12 Section 6 — Exploded Views and Parts List RTS “W” Type Transfer Switch 400 A Switch Assembly – Drawing No. 0G1510$ ITEM PART NO. 1 2 3 4 5 6 7 8 9 (2) 10 11 12 (2) 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 (1) 34 35 36 37 (2) 38 39 40 41 42 43 0D7294 0A7822 026902 0C7907J 024526 057329 027482 022097 0C8275 0D2806 090388 0A1495 063617 047411 0A1661 0F4034 0F5935 0F5939 0C8308 0C2262 0F6165 0G1520 064101 0F5940 087680 063378 064761 063321 073590A 0D3587 067210A 0A9457 0D4545 0F6129 081221 0A8261 022473 048850 0F6273A 022129 091472 091472A 067989 QTY. 1 6 5 2 1 1 1 9 4 1 3 6 1 2 2 1 1 1 2 1 2 1 6 1 1 4 4 1 2 1 1 1 1 1 1 6 6 1 1 1 2' 2' 2 DESCRIPTION XFER SW-W 400A600V2P LUG, SLDLSS 600/250-1/0X1/4-28 SCREW TAPTITE #8-32X1/4 BP COVER LUG 2P 400AMP SCREW HHTT 5/16-18 X 3/4 CZ LUG, SOLDERLESS 350-#6X13/32 AL/CU WASHER SHAKEPROOF EXT 5/16 STEEL WASHER LOCK M6-1/4 SCREW PPHM DSEMS M4-.7 X 10 ZNC FUSEBLOCK 30A 600V 2POS W/SQ SCREW TAPTITE M6-1.0 X 12 MM SCREW TAPTITE M4-.7 X 10 MM RELAY PNL 12VDC DPDT 10A@240VA SCREW HHC M6-1.0 X 16 G8.8 RIVET, POP ASSY. NEUTRAL BLOCK 300/400A RTS 3R ENCLOSURE 24X36X10 COVER TRANSFER SWITCH DECAL TERMINAL SHOCK HAZARD DECAL TERMINAL STRIP WASHER, NYLON DECAL,DATA XFER SW 400A,240V NUT HEX FL WHIZ 3/8-16 SUBPLATE,100A TS 3R 480V NUT WING M6-1.0 HOLDER CABLE TIE TIE WRAP UL 5.6" X .10" NATL HANDLE TRANSFER SWITCH 1-400A FUSE 5A X BSS HLDR73591 DECAL,FUSE REPLACEMENT DECAL GROUND LUG DECAL NEUTRAL DECAL MANUAL OPERATION DECAL, TEST SEQUENCE DECAL, UL NAMEPLATE SCREW, HHCS 1/4-28 X 5/8" WASHER, FLAT 1/4-6M ZINC BLOCK TERM 20A 5 X 6 X 1100V HARNESS 400A 2 POLE RTS (NOT SHOWN) WASHER LOCK M8-5/16 DUCT WIRING 1X1.5 COVER WIRE DUCT 1 IN NUT HEX FL WHIZ M8-1.25 (1) CENTER DECAL ON INSIDE OF THE COVER (ITEM #18) (2) ITEMS INCLUDED WITH HARNESS 13 Section 8 — Warranty RTS “W” Type Transfer Switch CARRIER WARRANTY/SERVICE Carrier will warrant that from the date of purchase, our transfer switch will be free from defects in material and workmanship for the items and periods set forth in the warranty statement found in the owners manual of the Carrier generator that this transfer switch will be utilized with. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Carrier Dealer. THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, CARRIER MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. CARRIER’S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL CARRIER BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF CARRIER’S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to you. This warranty gives you specific legal rights. You also may have other rights that vary from state to state. Part No. 0G1622 Rev. A (12/15/06) Catalog No. OMKGATD,XNS400-03 Printed in U.S.A.
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : Yes XMP Toolkit : 3.1-702 Producer : Acrobat Distiller 7.0.5 (Windows) Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2006:12:05 14:36:23-06:00 Create Date : 2006:07:18 10:52:40-05:00 Metadata Date : 2006:12:05 14:36:23-06:00 Format : application/pdf Title : 0G1622 rev0.indd Creator : bpeterso Document ID : uuid:d617ca70-c281-418e-ac06-1ad262666cf0 Instance ID : uuid:aa78ea2e-69cb-4023-8f87-f559fc902e52 Page Count : 16 Author : bpetersoEXIF Metadata provided by EXIF.tools