Ruggedcom Rsg2100 Users Manual Datasheet_Rev2U
RSG2100 to the manual 0bf61bf7-818f-4718-aa2b-672029748710
2015-02-06
: Ruggedcom Ruggedcom-Rsg2100-Users-Manual-525616 ruggedcom-rsg2100-users-manual-525616 ruggedcom pdf
Open the PDF directly: View PDF .
Page Count: 10
Download | |
Open PDF In Browser | View PDF |
RuggedSwitchTM RSG2100 eRSTP eRSTP 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports eRSTP eRSTP ZPL TM Zero-Packet-Loss™ eRSTP eRSTP eRSTP eRSTP eRSTP The RuggedSwitch™ RSG2100 is an industrially hardened, fully managed, modular, Ethernet switch specifically designed to operate reliably in electrically harsh and climatically demanding utility substation and industrial environments. The RSG2100's superior ruggedized hardware design coupled with the embedded Rugged Operating System (ROS™) provides improved system reliability and advanced cyber security and networking features making it ideally suited for creating secure Ethernet networks for missioncritical, real-time, control applications. The RSG2100's modular flexibility offers 10BaseFL /100BaseFX /1000BaseX fiber and 10/100/1000BaseTX copper port combinations. Optional front or rear mount connectors make the RSG2100 highly versatile for any application and can support multiple fiber connectors (ST, MTRJ, LC, SC) without loss of port density. The RSG2100 is packaged in a rugged galvanized steel enclosure with industrial grade DIN, panel, or 19" rack-mount mounting options. Features and Benefits Ethernet Ports .up to 3-Gigabit Ethernet ports - copper and/or fiber .up to 16-Fast Ethernet ports - copper and/or fiber .2 port modules for tremendous flexibility .Non-blocking, store and forward switching .Supports many types of fiber (Multimode, singlemode, bi-directional single strand) .Long haul optics allow Gigabit distances up to 70km .Multiple connector types (ST, MTRJ, LC, SC) Cyber Security Features .Multi-level user passwords .SSH/SSL encryption .Enable/disable ports, MAC based port security .Port based network access control (802.1x) .VLAN (802.1q ) to segregate and secure network traffic .Radius centralized password management .SNMPv3 encrypted authentication and access security RuggedRated TM for Reliability in Harsh Environments .Immunity to EMI and heavy electrical surges . Zero-Packet-Loss™ Technology . Meets IEEE 1613 Class 2 (electric utility substations) . Exceeds IEC 61850-3 (electric utility substations) . Exceeds IEC 61800-3 (variable speed drive systems) . Exceeds IEC 61000-6-2 (generic industrial) . Exceeds NEMA TS-2 (traffic control equipment) .-40 to +85°C operating temperature (no fans) .Conformal coated printed circuit boards (optional) .18 AWG galvanized steel enclosure .Hazardous Location Certification: Class 1 Division 2 Rugged Operating System (ROSTM) Features .Simple plug and play operation - automatic learning, negotiation, and crossover detection .RSTP (802.1w) and Enhanced Rapid Spanning Tree (eRSTP™) network fault recovery (<5ms) .Quality of Service (802.1p) for real-time traffic .VLAN (802.1q) with double tagging and GVRP support .Link aggregation (802.3ad) .IGMP Snooping for multicast filtering .Port Rate Limiting and Broadcast Storm Limiting .Port configuration, status, statistics, mirroring, security .Loss of link management on fiber ports .SNTP time synchronization (client and server) .Industrial automation features (eg. Modbus) Management Tools .Web-based, Telnet, CLI management interfaces .SNMP v1/v2/v3 .Remote Monitoring (RMON) .Rich set of diagnostics with logging and alarms Universal Power Supply Options .Fully integrated, dual-redundant (optional) power supplies .Universal high voltage range: 88-300VDC or 85-264VAC .Popular low voltage ranges: 24VDC(9-36VDC), 48VDC (36-72VDC) .Screw or pluggable terminal blocks available .Terminal blocks for reliable RUGGEDCOM maintenance free connections .CSA/UL 60950 safety approved to +85°C www.RuggedCom.com ISO 9001:2000 CERTIFIED RuggedSwitchTM RSG2100 1 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports RuggedSwitch™ RSG2100 Modularity: 10 available slots Up to 16 Fast Ethernet ports & 3 Gigabit ports Dual and single port modules Modularity (8x2) Mounting Options Panel/Din Rail 19” Rack Mount Front or Rear Mount Modular HMI: Gigabit Port Types: Fast Ethernet Ports Types: up to 16 Fast Ethernet Ports up to 3 Gigabit Ethernet Ports virtually any mix of fiber or 10/100/1000 TX RJ45 Front or Rear Mount 1000SX Multimode copper desired 10/100TX RJ45 1000LX Singlemode 10FL Multimode Pluggable Optics (SFP) 100FX Multimode SC, ST, LC and MTRJ 100FX Singlemode Integrated Power Supply Universal high-voltage range: 88-300VDC or 85-264VAC Popular low voltage DC ranges: 24VDC (9-36VDC), 48VDC (36-59VDC) True Dual Redundant Parallel Load Sharing (Optional) Critical Alarm Relay Operating Temperature -40oC to +85oC No Fans Form-C contact ratings: Max Voltage 250VAC,125VDC Max Current 2A@250VAC, 0.15A@125VDC, 2A@30VDC Screw or pluggable terminal blocks available www.RuggedCom.com RuggedSwitchTM RSG2100 2 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports ROSTM Features Cyber Security Cyber security is an urgent issue in many industries where advanced automation and communications networks play a crucial role in mission critical applications and where high reliability is of paramount importance. Key ROS™ features that address security issues at the local area network level include: .Passwords - Multi-level user passwords secures switch against unauthorized configuration .SSH / SSL - Extends capability of password protection to add encryption of passwords and data as they cross the network .Enable / Disable Ports - Capability to disable ports so that traffic can not pass .802.1q VLAN - Provides the ability to logically segregate traffic between predefined ports on switches .MAC Based Port Security - The ability to secure ports on a switch so only specific Devices / MAC addresses can communicate via that port .802.1x Port Based Network Access Control - The ability to lock down ports on a switch so that only authorized clients can communicate via this port .Radius - Provides centralized password management .SNMPv3 - encrypted authentication and access security The ROS™ cyber security features are included to help address the various industry specific security standards such as NERC CIP, ISA S99, AGA 12, IEC 62443, ISO 17799:2005 and PCSRF SPP-ICS. Enhanced Rapid Spanning Tree Protocol (eRSTP™) RuggedCom eRSTP allows the creation of fault-tolerant ring and mesh Ethernet networks that incorporate redundant links that are 'pruned' to prevent loops. eRSTP yields worst-case fault recovery1 of 5ms times the 'bridge diameter' and allows rings of up to 80 switches. For example, a ring of ten switches will have fault recovery times under 50ms. eRSTP implements both STP and RSTP to ensure interoperability with commercial switches unlike other proprietary 'ring' solutions. Quality of Service (IEEE 802.1p) Some networking applications such as real-time control or VoIP (voice over IP) require predictable arrival times for Ethernet frames. Switches can introduce latency in times of heavy network traffic due to the internal queues that buffer frames and then transmit on a first come first serve basis. ROS™ supports 'Class of Service' in accordance with IEEE 802.1p that allows time critical traffic to jump ahead to the front of the queue thus minimizing latency and reducing jitter to allow such demanding applications to operate correctly. ROS™ allows priority classification by port, tags, MAC address, and IP type of service (TOS). www.RuggedCom.com A configurable "weighted fair queuing" algorithm controls how frames are emptied from the queues. VLAN (IEEE 802.1q) Virtual local area networks (VLAN) allow the segregation of a physical network into separate logical networks with independent broadcast domains. A measure of security is provided since hosts can only access other hosts on the same VLAN and traffic storms are isolated. ROS™ supports 802.1q tagged Ethernet frames and VLAN trunks. Port based classification allows legacy devices to be assigned to the correct VLAN. GVRP support is also provided to simplify the configuration of the switches on the VLAN. Link Aggregation (802.3ad) The link aggregation feature provides the ability to aggregate several Ethernet ports into one logical link (port trunk) with higher bandwidth. This provides an inexpensive way to set up a high speed backbone to improve network bandwidth. This feature is also known as "port trunking", "port bundling", "port teaming", and "ethernet trunk". IGMP Snooping ROS uses IGMP snooping (Internet Group Management Protocol v1&v2) to intelligently forward or filter multicast traffic streams (e.g. MPEG video) to or from hosts on the network. This reduces the load on network trunks and prevents packets from being received on hosts that are not involved. ROS™ has a very powerful implementation of IGMP snooping that: .Can be enabled on a per VLAN basis. .Detects and filters all multicast streams regardless of whether subscribers exist. .Supports "router-less" operation by supporting an "active" mode. .Restores traffic streams immediately after an RSTP topology change. SNMP (Simple Network Management Protocol) SNMP provides a standardized method for network management stations the ability to interrogate devices from different vendors. SNMP versions supported by ROS™ are v1, v2c, and v3. SNMPv3 in particular provides security features (such as authentication, privacy, and access control) not present in earlier SNMP versions. ROS™ also supports numerous standard MIBs (Management Information Base) allowing for easy integration with any network management system (NMS). 1 eRSTP fault recovery times may be approximated as follows: For 100 Mbps, fault recovery performance is <5ms/hop For 1,000 Mbps, fault recovery performance is <5ms/hop + 20ms RuggedSwitchTM RSG2100 3 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports ROSTM Features SNMP (Simple Network Management Protocol) (cont’d) A feature of SNMP supported by ROS™ is the ability to generate "traps" upon system events. A NMS can record traps from multiple devices providing a powerful network troubleshooting tool. RuggedVueTM is RuggedCom's NMS that provides graphical visualization of the network and is fully integrated with all RuggedCom products. Port Configuration and Status ROS™ allows individual ports to be 'hard' configured for speed, duplex, auto-negotiation, flow control and more. This allows proper connection with devices that do not negotiate or have unusual settings. Detailed status of ports with alarm and SNMP trap on link problems aid greatly in system troubleshooting. SNTP (Simple Network Time Protocol) SNTP automatically synchronizes the internal clock of all ROS™ devices on the network. This allows for correlation of time stamped events for troubleshooting. Port Statistics and RMON (Remote Monitoring) ROS™ provides continuously updating statistics per port that provide both ingress and egress packet and byte counters as well as detailed error figures. Also provided is full support for the RMON statistics, history, alarms, and event groups. RMON allows for very sophisticated data collection, analysis and detection of traffic patterns. SCADA and Industrial Automation ROS™ contains features that optimize network performance and simplify switch management based on the unique requirements found in SCADA and industrial automation applications. Features such as Modbus TCP management for retrieval of switch data using the ubiquitous Modbus protocol and DHCP Option 82, a Rockwell Automation ODVA requirement for IP address assignment based on the location of the end device, provide capabilities not found in typical "commercial" or "office grade" Ethernet switches. Port Based Network Access Control (802.1x) ROS™ supports the IEEE 802.1x standard that defines a mechanism for port-based network access control which provides a means of authenticating and authorizing devices attached to LAN ports. Port Rate Limiting ROS™ supports configurable rate limiting per port to limit unicast and multicast traffic. This can be essential to managing precious network bandwidth for service providers. It also provides edge security for denial of service (DOS) attacks. Broadcast Storm Filtering Broadcast storms wreak havoc on a network and can cause attached devices to malfunction. This could be disastrous on a network with mission critical equipment. ROS™ limits this by filtering broadcast frames with a user-defined threshold. Loss of Link Management Some intelligent electronic devices (IEDs) have dual fiber optic ports with automatic failover to a backup port should the primary fail. ROS™ ensures this mechanism works reliably under all failure modes by appropriately disabling link signals when required. ROS™ also flushes learned MAC addresses to ensure the failover occurs quickly. Port Mirroring ROS™ can be configured to duplicate all traffic on one port to a designated mirror port. When combined with a network analyzer, this can be a powerful troubleshooting tool. www.RuggedCom.com Event Logging and Alarms ROS™ records all significant events to a non-volatile system log allowing forensic troubleshooting. Events include link failure and recovery, unauthorized access, broadcast storm detection, and self-test diagnostics among others. Alarms provide a snapshot of recent events that have yet to be acknowledged by the network administrator. An external hardware relay is de-energized during the presence of critical alarms allowing an external controller to react if desired. HTML Web Browser and Telnet User Interfaces ROS™ provides a simple, intuitive user interface for configuration and monitoring via a standard graphical web browser or via Telnet. All system parameters include detailed on-line help to make setup a breeze. ROS™ , presents a common look and feel and standardized configuration process allowing easy migration to other RuggedCom managed products. Configuration via ASCII Text File All configuration parameters are stored in an ASCII formatted text file that can easily be transferred via TFTP or Xmodem. The configuration file can be saved for backup purposes and easily manipulated by a text editor. The same text file can be downloaded to the switch at a later date in order to re-configure or restore a previous configuration. Command Line Interface (CLI) A command line interface can be used in conjunction with remote shell to automate data retrieval, configuration updates, and firmware upgrades. A powerful SQL-like capability allows expert users the ability to selectively retrieve or manipulate any parameters the device has to offer. RuggedSwitchTM RSG2100 4 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports EMI and Environmental Type Tests IEC 61850-3 EMI TYPE TESTS TEST Description IEC 61000-4-2 ESD IEC 61000-4-3 Radiated RFI Test Levels Enclosure Contact Enclosure Air Enclosure ports Signal ports IEC 61000-4-4 +/- 8kV +/- 15kV 20 V/m Severity Levels 4 4 x +/- 4kV @ 2.5kHz x D.C. Power ports +/- 4kV 4 A.C. Power ports +/- 4kV 4 Earth ground ports 3 +/- 4kV 4 +/- 4kV line-to-earth, +/- 2kV line-to-line +/- 2kV line-to-earth, +/- 1kV line-to-line +/- 4kV line-to-earth, +/- 2kV line-to-line 4 3 4 Signal ports 10V 3 Burst (Fast Transient) IEC 61000-4-5 Signal ports D.C. Power ports A.C. Power ports Surge IEC 61000-4-6 D.C Power ports 10V 3 A.C. Power ports 10V 3 Earth ground ports 3 Enclosure ports 10V Induced (Conducted) RFI IEC 61000-4-8 Magnetic Field D.C. Power ports 3 40 A/m continuous, 1000 A/m for 1 s N/A 30% for 0.1s, 60% for 0.1s, 100% for 0.05s N/A 30% for 1 period, 60% for 50 periods N/A 100% for 5 periods, 100% for 50 periods 2 2.5kV common, 1kV diff. mode@1MHz 2.5kV common, 1kV diff. mode@1MHz 2.5kV common, 1kV diff. mode@1MHz 30V Continuous, 300V for 1s 30V Continuous, 300V for 1s 10% 2kVac (Fail-Safe Relay output) 2kVac 2kVac 5kV (Fail-Safe Relay output) 5kV 5kV N/A IEC 61000-4-29 Voltage Dips & Interrupts A.C. Power ports IEC 61000-4-11 IEC 61000-4-12 Damped Oscillatory IEC 61000-4-16 Mains Frequency Voltage IEC 61000-4-17 Ripple on D.C. Power Supply IEC 60255-5 Dielectric Strength IEC 60255-5 H.V. Impulse Signal ports D.C. Power ports A.C. Power ports Signal ports D.C. Power ports D.C. Power ports Signal ports D.C. Power ports A.C. Power ports Signal ports D.C. Power ports A.C. Power ports 3 3 3 4 4 3 N/A N/A N/A N/A N/A N/A IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS Test Description IEEE C37.90.3 ESD IEEE C37.90.2 Radiated RFI IEEE C37.90.1 Fast Transient IEEE C37.90.1 Oscillatory IEEE C37.90 H.V. Impulse IEEE C37.90 Dielectric Strength Enclosure Contact Enclosure Air Enclosure ports Signal ports D.C. Power ports A.C. Power ports Earth ground ports3 Signal ports D.C. Power ports A.C. Power ports Signal ports D.C. Power ports A.C. Power ports Signal ports D.C. Power ports A.C. Power ports Test Levels +/- 8kV +/- 15kV 35 V/m +/- 4kV @ 2.5kHz +/- 4kV +/- 4kV +/- 4kV 2.5kV common mode @1MHz 2.5kV common, 1kV diff. mode@1MHz 2.5kV common, 1kV diff. mode@1MHz 5kV (Fail-Safe Relay output) 5kV 5kV 2kVac 2kVac 2kVac Severity Levels N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A Environmental Type Tests Notes: Test IEC 60068-2-1 Description Cold Temperature Test Ad Test Levels -40°C, 16 Hours Severity Levels N/A IEC 60068-2-2 Dry Heat Test Bd +85°C, 16 Hours N/A N/A Class 2 Class 2 IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db 95% (non-condensing), 55°C , 6 cycles IEC 60255-21-1 IEC 60255-21-2 Vibration Shock Tests Fc Tests Ea 2g @ (10 - 150) Hz 30g @ 11mS 1. Only applicable to functional earth connections separated from the safety earth connection. 2. Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high, ( e.g. shipboard application and for severe transportation conditions") www.RuggedCom.com RuggedSwitchTM RSG2100 5 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports Technical Specifications Power Supply .Power Consumption: 28W Max .24VDC: 9-36 VDC, 1.2A .48VDC: 36-72 VDC, 0.6A .HI Voltage AC/DC: 88-300VDC or 85-264VAC Critical Alarm Relay .Form-C contact ratings: Max Voltage 250VAC,125VDC Max Current 2A@250VAC, 0.15A @125VDC, 2A@30VDC Physical .Height: 4.42cm / 1.74" .Width: 46.48cm / 18.3" .Depth: 31.5cm / 12.4" .Weight: 5.2kg / 11.5 lbs .Ingress Protection: IP40 (1mm objects) .Enclosure: 18 AWG galvanized steel enclosure .Mounting: DIN rail or panel mounted Switch Properties .Switching method: Store & Forward .Switching latency: 7 us .Switching bandwidth: 9.2 Gbps .MAC addresses: 8192 .MAC address table size: 64kbytes .Priority Queues: 4 .Frame buffer memory: 2 Mbit .VLANs: 4094 .IGMP multicast groups: 256 .Port rate limiting .No head of line blocking Approvals .ISO: Designed and manufactured using a ISO9001: 2000 certified quality program .CE Marking .Emissions: FCC Part 15 (Class A), EN55022 (CISPR22 Class A) .Safety: cCSAus (Compliant with CSA C22.2 No. 60950, UL 60950, EN60950) .Laser Eye Safety (FDA/CDRH): Complies with 21 CFR Chapter1, Subchapter J. Warranty .5 Years - Applicable to design and manufacturing related product defects. Network Management .HTTP graphical web-based .SNMP v1, v2c, v3 .Telnet, VT100 .Command Line Interface (CLI) www.RuggedCom.com EMI Immunity and Environmental Compliance .IEC 61000-6-2 Industrial (Generic) .IEC 61800-3 Industrial (Variable Speed Drive Systems) .IEC 61850-3 Electric Utility Substations .IEEE 1613 Electric Utility Substations .NEMA TS 2 Traffic Control Equipment IEEE Compliance .802.3-10BaseT .802.3u-100BaseTX, 100BaseFX .802.3x-Flow Control .802.3z-1000BaseLX .802.3ab-1000BaseTX .802.3ad-Link Aggregation .802.1d-MAC Bridges .802.1d-Spanning Tree Protocol .802.1p-Class of Service .802.1q-VLAN Tagging .802.1w-Rapid Spanning Tree Protocol .802.1x-Port Based Network Access Control IETF RFC Compliance .RFC768-UDP .RFC783-TFTP .RFC791-IP .RFC792-ICMP .RFC793-TCP .RFC826-ARP .RFC854-Telnet .RFC894-IP over Ethernet .RFC1112-IGMP v1 .RFC1519-CIDR .RFC1541-DHCP (client) .RFC2030-SNTP .RFC2068-HTTP .RFC2236-IGMP v2 .RFC2284-EAP .RFC2475-Differentiated Services .RFC2865-Radius .RFC3414-SNMPv3-USM .RFC3415-SNMPv3-VACM IETF SNMP MIBS .RFC1493-BRIDGE-MIB .RFC1907-SNMPv2-MIB .RFC2012-TCP-MIB .RFC2013-UDP-MIB .RFC2578-SNMPv2-SMI .RFC2579-SNMPv2-TC .RFC2819-RMON-MIB .RFC2863-IF-MIB .draft-ietf-bridge-rstpmib-03-BRIDGE-MIB .draft-ietf-bridge-bridgemib-smiv2-03-RSTP-MIB .IANAifType-MIB RuggedSwitchTM RSG2100 6 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports Dimensions www.RuggedCom.com RuggedSwitchTM RSG2100 7 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports Mounting Options Slot 1 Slot 3 Slot 5 Slot 7 Slot 9 Slot 2 Slot 4 Slot 6 Slot 8 Slot 10 www.RuggedCom.com RuggedSwitchTM RSG2100 8 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports Order Codes RSG2100 -______ -______ -____ -____ -____ -____ -____ -____ -____ -____ -____ -____ -____ -_____ Main Mount PS1 PS2 S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 Slot 1 Slot 3 Slot 5 Slot 7 Slot 9 Slot 2 Slot 4 Slot 6 Slot 8 Slot 10 Main: Ethernet and Power Connectors .R = Ethernet on rear; LED panel on front; power connector on rear .F = Ethernet on front; LED panel on front; power connector on rear . B = Ethernet on rear; LED panel on top; power connector on rear . T = Ethernet on front; LED panel on top; power connector on rear Mount: Mounting Options . RM = 19" Rack Mount Kit . DP = DIN and Panel Mount Kit . RD = 19" Rack, DIN, and Panel Mount Kit . 00 = No Mounting Option PS1 and PS2: Power Supply 1 and 2 . 24 = 24VDC (9-36VDC), screw terminal block . 48 = 48VDC (36-72VDC), screw terminal block . HI = 88-300VDC or 85-264VAC, screw terminal block . 24P = 24VDC (9-36VDC), pluggable terminal block . 48P = 48VDC (36-72VDC), pluggable terminal block . HIP = 88-300VDC or 85-264VAC, pluggable terminal block . XX = No Power Supply (PS2 Only) S1, S2, S3, S4, S7, S8, S9 and S10: Ethernet Modules for Slots 1, 2, 3, 4, 7, 8, 9 and 10 . XXXX = Empty . TX01 = 2 x 10/100Tx RJ45 FL01 = 2 x 10FL - Multimode, 850nm, ST . FX01 = 2 x 100FX - Multimode, 1300nm, ST . FX02 = 2 x 100FX - Multimode, 1300nm, SC . FX11 = 2 x 100FX – Multimode, 1300nm, LC . FX03 = 2 x 100FX - Multimode, 1300nm, MTRJ . FX04 = 2 x 100FX - Singlemode, 1310nm, ST, 20km . FX05 = 2 x 100FX - Singlemode, 1310nm, SC, 20km . FX06 = 2 x 100FX - Singlemode, 1310nm, LC, 20km . FX07 = 2 x 100FX - Singlemode, 1310nm, SC, 50km . FX08 = 2 x 100FX - Singlemode, 1310nm, LC, 50km . FX09 = 2 x 100FX - Singlemode, 1310nm, SC, 90km . FX10 = 2 x 100FX - Singlemode, 1310nm, LC, 90km S5: Gigabit Ethernet Modules for slot 5 .XXXX = Empty .CG01 = 2 x 10/100/1000Tx RJ45 .FG01 = 2 x 1000SX - Multimode, 850nm, LC, 500m .FG02 = 2 x 1000LX - Singlemode, 1310nm, SC connectors, 10km .FG03 = 2 x 1000LX - Singlemode, 1310nm, LC connectors, 10km .FG04 = 2 x 1000LX - Singlemode, 1310nm, SC connectors, 25km .FG05 = 2 x 1000LX - Singlemode, 1310nm, LC connectors, 25km .FG50 = 2 x 1000LX SFP - Blank (no optical transceiver) .FG51 = 2 x 1000SX SFP - Multimode, 850nm, LC, 500m .FG52 = 2 x 1000LX SFP - Singlemode, 1310nm, LC, 10km .FG53 = 2 x 1000LX SFP - Singlemode, 1310nm, LC, 25km .FG54 = 2 x 1000LX SFP - Singlemode, 1550nm, LC, 70km .FG70 = 2 x 1000LX GBIC - Blank (no optical transceiver) .FG71 = 2 x 1000LX GBIC - Singlemode, 1310nm, SC, 10km .FG72 = 2 x 1000LX GBIC - Singlemode, 1310nm, SC, 25km .FG73 = 2 x 1000LX GBIC - Singlemode, 1550nm, SC, 70km S6: Gigabit Ethernet Modules for slot 6 .XXXXX = Empty .1CG01 = 1 x 10/100/1000Tx RJ45 .1FG01 = 1 x 1000SX - Multimode, 850nm, LC, 500m .1FG02 = 1 x 1000LX - Singlemode, 1310nm, SC connectors, 10km .1FG03 = 1 x 1000LX - Singlemode, 1310nm, LC connectors, 10km .1FG04 = 1 x 1000LX - Singlemode, 1310nm, SC connectors, 25km .1FG05 = 1 x 1000LX - Singlemode, 1310nm, LC connectors, 25km .1FG50 = 1 x 1000SX SFP - Blank (no optical transceiver) .1FG51 = 1 x 1000SX SFP - Multimode, 850nm, LC, 500m .1FG52 = 1 x 1000LX SFP - Singlemode, 1310nm, LC,10km .1FG53 = 1 x 1000LX SFP - Singlemode, 1310nm, LC, 25km .1FG54 = 1 x 1000LX SFP - Singlemode, 1550nm, LC, 70km (2) .1FG70 = 1 x 1000LX GBIC - Blank (no optical transceiver) .1FG71 = 1 x 1000LX GBIC - Singlemode, 1310nm, SC, 10km .1FG72 = 1 x 1000LX GBIC - Singlemode, 1310nm, SC, 25km .1FG73 = 1 x 1000LX GBIC - Singlemode, 1550nm, SC, 70km (2) NOTES: 1 Distance ratings are typical but will depend on type of cabling, number of connectors and splices. 2 These transceivers have an operating temperature range of -20 °C to +85°C. All other transceivers have an operating temperature range of -40°C to +85°C Example Order Codes: RSG2100-R-RM-24-48-TX01-TX01-XXXX-XXXX-XXXXXXXXX-XXXX-XXXX-XXXX-XXXX 19” Rack mounted, 24VDC power supply, 48VDC power supply, 4 10/100 RJ45 Ethernet Ports, with Ethernet ports on the rear RSG2100-F-RM-48-48-TX01-TX01-FX01-FX01-XXXX-XXXXXXXXX-XXXX-XXXX-XXXX 19” Rack mounted, 48VDC power supply, 48VDC, 4 10/100 RJ45 Ethernet Ports, 4 100FX (Multi Mode 1310nm Fiber) Ethernet ports, with Ethernet ports on the front www.RuggedCom.com RSG2100-R-RM-HI-HI-TX01-TX01-FX01-FX01-FG02XXXXX-FX01-FX01-FX01-FX01 19” Rack mounted, HI power supply, HI power supply, 4 10/100 RJ45 Ethernet Ports, 12 100FX (Multi Mode 1350nm Fiber) Ethernet ports, 2 1000LX (Gigabit) Ethernet ports, with Ethernet ports on the front Accessories/Options 82-01-0002 - Conformal Coating 41-11-0011 - Cable support brackets 43-10-0007 - Power cable (North America three prong connector -> beau) RuggedSwitchTM RSG2100 9 RuggedSwitchTM RSG2100 19-Port Modular Managed Ethernet Switch with Gigabit Uplink Ports RuggedCom Inc. 30 Whitmore Road Woodbridge, Ontario, Canada L4L 7Z4 Tel: (905) 856-5288 Fax: (905) 856-1995 Toll Free: (888) 264-0006 Technical Support Center: (866) 922-7975 or (954) 922-7975 © 2007 RuggedCom Inc. RuggedSwitch is a trademark of RuggedCom Inc. Ethernet is a trademark of the Xerox Corporation. Patent Pending All specifications in this document are subject to change without notice. Rev 2-U www.RuggedCom.com For additional information on our products and services, please visit our web site at: www.ruggedcom.com RuggedSwitchTM RSG2100 10
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.4 Linearized : Yes XMP Toolkit : 3.1-701 Producer : Acrobat Distiller 7.0.5 (Windows) Create Date : 2008:03:12 12:17:45-04:00 Creator Tool : PScript5.dll Version 5.2.2 Modify Date : 2008:03:12 12:17:45-04:00 Format : application/pdf Creator : jamieblakeley Title : RSG2100 Datasheet_Rev2U:RSG2100 Datasheet_Rev2K.qxd.qxd Document ID : uuid:70e90d59-0ce3-49f7-bc0f-2e907e0b28e5 Instance ID : uuid:79dc055e-6cfa-47a9-a012-555244cdeaff Page Count : 10 Author : jamieblakeleyEXIF Metadata provided by EXIF.tools