SECURITY DOOR CONTROLS
801 Avenida Acaso, Camarillo, Ca. 93012
(805) 494-0622 • Fax: (805) 494-8861
www.sdcsecurity.com • E-mail: service@sdcsecurity.com

SPECIAL APPLICATIONS POWER SUPPLY
INSTALLATION INSTRUCTIONS
MODEL 602RF

COMPONENT LOCATIONS
MODEL 602RF
CONTROL
MODULE

AC Voltage
Input

POWER
SUPPLY
BOARD

CONTROL
MODULE

BATTERY 1
4ah

BATTERY 2
4ah

STANDARD BOX
AC Voltage
Input
Manuel
Reset

MAIN SYSTEM ON-OFF
OR
FIRE PANEL CONNECTION

System
Status LED

+ _

Yellow = System OK
Red = No AC Input
Green = No DC Output
Battery Input
Terminals

Voltage Output
Terminals

+

_

C

Master ON/OFF
Switch (N/C)

C

Fire Panel
Contact (N/C)

Min. Switch
OR
Contact Ratings
100mA @ 30vdc

Figure C
Input Voltage: 115/230 VAC @ 60hz
Input Current: 0.8 amps Max.

POWER SUPPLY SPECIFICATIONS
JUMPER SET
FOR 24 VDC

JUMPER SET
FOR 12 VDC

Output Voltage: 12/24VDC (Special Applications)
Burglary Use:
Output Voltage Ranges:
12 V Operation: 9.2 – 12.0 VDC
24 V Operation: 21.2 – 24.0 VDC
Output Current: 1.0 amps
Ripple Voltage: 0.05 Volts Max

+
-

+
-

Battery Charger Max Current: 0.25 amps
Maximum recommended battery size: 4ah
(Replace batteries every three years)

_

+

12VDC

12VDC
To determine standby battery capacity, refer to
Batter Discharge table (INST-BDT).

12 Volt Mode Battery
Connections

Compatible UL listed Fire Devices:
Smoke detector manufactured by ESL, Model 521B,
521BXT with Model 506 module.

602RF

+- + -

_

+
Battery

TEST UNIT YEARLY
Rev F

01-12

12VDC

High voltage
Input

Wire Routing

NOT INTENDED TO POWER A LOCAL
BURGLAR ALARM INDICATING DEVICE.

_

+

24 Volt Mode Battery
Connections

Suitable Uses:
Electric Lock Power Supply
Access Control Power Supply
Burglar Alarm System Power Supply
Fire Protective Signaling Service

P:\INSTALLATION INST\Power Supplies\INST-602RF.vsd

_

+

C

NOTE:
Power limited cable
must maintain a 1/4”
or more spacing from
battery cables or
primary power wires.
Power limited
Class 2 output

SPECIAL APPLICATIONS POWER SUPPLY
INSTALLATION INSTRUCTIONS

801 Avenida Acaso, Camarillo, Ca. 93012
(805) 494-0622 • Fax: (805) 494-8861
www.sdcsecurity.com • E-mail: service@sdcsecurity.com

MODEL 602RF-CUL

COMPONENT LOCATIONS

MODEL 602RF-CUL

CONTROL
MODULE

POWER
SUPPLY
BOARD

CONTROL
MODULE

AC VOLTAGE
INPUT

BATTERY 1
4ah

BATTERY 1
4ah

STANDARD BOX

BATTERY MONITOR LEDS
GRN = AC
RED = BATTERIES
ORG = NO/LO BATTERY

VOLTAGE SELECT
SWITCHES
MANUAL
RESET

COVER

SYSTEM STATUS
YELLOW – SYSTEM OK
RED – ON BATTERY PWR
GREEN – NO DC OUTPUT

Min. Switch or
Contact Ratings
100mA @ 30VDC

MAIN SYSTEM ON-OFF

BATTERY INPUT
TERMINALS

VOLTAGE OUTPUT
TERMINALS

_

+

Master ON/OFF
Switch (N/C)

C

POWER SUPPLY SPECIFICATIONS
Input Voltage: 115 VAC @ 60hz
Input Current: 0.8 amps Max.
+

Output Voltage: 12/24VDC (Special Applications)
Burglary Use:
Output Voltage Ranges:
12 V Operation: 9.2 – 12.0 VDC
24 V Operation: 21.2 – 24.0 VDC
Output Current: 1.0 amps
Ripple Voltage: 0.05 Volts Max.

Monitor Board
_
_
+

_

+

12VDC

_

+

_

12VDC

24 Volt Mode Battery
Connections

12 Volt Mode Battery
Connections
HIGH
VOLTAGE
INPUT

To determine standby battery capacity refer to
Battery Discharge Table (INST-BDT).
602RF-CUL

+_ +_

Suitable Uses:
Electric Lock Power Supply
Access Control Power Supply

+

+

P:\INSTALLATION INST\Power Supplies\INST-602RF-CUL.vsd

Monitor
_
_ Board
+

+

12VDC

Battery Charger Max. Current: 0.25 amps
Maximum recommended battery size: 4ah
Recommended Battery: SDC Model RB12V4
(Replace batteries every 3 years)

TEST UNIT ANNUALLY

+

_

Battery

Rev B

04-13

_

+

_

C

Note: Power limited
cable must maintain a
1/4” or more of spacing
from battery cables or
primary power wires.

POWER LIMITED
CLASS 2 OUTPUT



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Author                          : sdc-12
Create Date                     : 2005:12:23 08:50:56-08:00
Modify Date                     : 2013:04:19 12:18:54-07:00
XMP Toolkit                     : Adobe XMP Core 5.2-c001 63.139439, 2010/09/27-13:37:26
Metadata Date                   : 2013:04:19 12:18:54-07:00
Creator Tool                    : PScript5.dll Version 5.2
Format                          : application/pdf
Title                           : INST-602RF.qxd
Creator                         : sdc-12
Document ID                     : uuid:896a6ba8-9431-4577-8fa7-1d721aa24cb1
Instance ID                     : uuid:74e2ee42-f1b1-ca43-a6e5-3ea746de6d96
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Page Count                      : 2
EXIF Metadata provided by EXIF.tools

Navigation menu