SPECIAL APPLICATIONS POWER SUPPLY
INSTALLATION INSTRUCTIONS
MODEL 602RF
SECURITY DOOR CONTROLS
801 Avenida Acaso, Camarillo, Ca. 93012
(805) 494-0622 • Fax: (805) 494-8861
www.sdcsecurity.com • E-mail: service@sdcsecurity.com
POWER SUPPLY SPECIFICATIONS
Input Voltage: 115/230 VAC @ 60hz
Input Current: 0.8 amps Max.
Output Voltage: 12/24VDC (Special Applications)
Burglary Use:
Output Voltage Ranges:
12 V Operation: 9.2 – 12.0 VDC
24 V Operation: 21.2 – 24.0 VDC
Output Current: 1.0 amps
Ripple Voltage: 0.05 Volts Max
Battery Charger Max Current: 0.25 amps
Maximum recommended battery size: 4ah
(Replace batteries every three years)
To determine standby battery capacity, refer to
Batter Discharge table (INST-BDT).
Compatible UL listed Fire Devices:
Smoke detector manufactured by ESL, Model 521B,
521BXT with Model 506 module.
Suitable Uses:
Electric Lock Power Supply
Access Control Power Supply
Burglar Alarm System Power Supply
Fire Protective Signaling Service
NOT INTENDED TO POWER A LOCAL
BURGLAR ALARM INDICATING DEVICE.
TEST UNIT YEARLY
COMPONENT LOCATIONS
STANDARD BOX
POWER
SUPPLY
BOARD
CONTROL
MODULE
CONTROL
MODULE
BATTERY 1
4ah
BATTERY 2
4ah
MAIN SYSTEM ON-OFF
OR
FIRE PANEL CONNECTION
Fire Panel
Contact (N/C)
Master ON/OFF
Switch (N/C)
+_
C
Figure C
C
+_
Min. Switch
OR
Contact Ratings
100mA @ 30vdc
MODEL 602RF
AC Voltage
Input
AC Voltage
Input
Manuel
Reset
Battery Input
Terminals
Voltage Output
Terminals
System
Status LED
Yellow = System OK
Red = No AC Input
Green = No DC Output
12VDC
+_
12VDC
+_
JUMPER SET
FOR 24 VDC
+
-
JUMPER SET
FOR 12 VDC
12VDC
+_
+
-
NOTE:
Power limited cable
must maintain a 1/4”
or more spacing from
battery cables or
primary power wires.
_
Battery
+Power limited
Class 2 output
602RF
High voltage
Input
+ - + -
C
Wire Routing
12 Volt Mode Battery
Connections
24 Volt Mode Battery
Connections
P:\INSTALLATION INST\Power Supplies\INST-602RF-CUL.vsd Rev B 04-13
SPECIAL APPLICATIONS POWER SUPPLY
INSTALLATION INSTRUCTIONS
MODEL 602RF-CUL
801 Avenida Acaso, Camarillo, Ca. 93012
(805) 494-0622 • Fax: (805) 494-8861
www.sdcsecurity.com • E-mail: service@sdcsecurity.com
POWER SUPPLY SPECIFICATIONS
Input Voltage: 115 VAC @ 60hz
Input Current: 0.8 amps Max.
Output Voltage: 12/24VDC (Special Applications)
Burglary Use:
Output Voltage Ranges:
12 V Operation: 9.2 – 12.0 VDC
24 V Operation: 21.2 – 24.0 VDC
Output Current: 1.0 amps
Ripple Voltage: 0.05 Volts Max.
Battery Charger Max. Current: 0.25 amps
Maximum recommended battery size: 4ah
Recommended Battery: SDC Model RB12V4
(Replace batteries every 3 years)
To determine standby battery capacity refer to
Battery Discharge Table (INST-BDT).
Suitable Uses:
Electric Lock Power Supply
Access Control Power Supply
TEST UNIT ANNUALLY
BATTERY 1
4ah
POWER
SUPPLY
BOARD
BATTERY 1
4ah
COMPONENT LOCATIONS
STANDARD BOX
CONTROL
MODULE
CONTROL
MODULE
MODEL 602RF-CUL
AC VOLTAGE
INPUT
VOLTAGE SELECT
SWITCHES
BATTERY INPUT
TERMINALS
MANUAL
RESET SYSTEM STATUS
YELLOW – SYSTEM OK
RED – ON BATTERY PWR
GREEN – NO DC OUTPUT
VOLTAGE OUTPUT
TERMINALS
COVER
BATTERY MONITOR LEDS
GRN = AC
RED = BATTERIES
ORG = NO/LO BATTERY
MAIN SYSTEM ON-OFF Min. Switch or
Contact Ratings
100mA @ 30VDC
+_CMaster ON/OFF
Switch (N/C)
12VDC
+_+_
12VDC
+_+_
24 Volt Mode Battery
Connections
Monitor Board
12VDC
+_+_
+_
12 Volt Mode Battery
Connections
Monitor Board
Note: Power limited
cable must maintain a
1/4” or more of spacing
from battery cables or
primary power wires.
602RF-CUL
Battery
+C
_
HIGH
VOLTAGE
INPUT
POWER LIMITED
CLASS 2 OUTPUT
+_
+_+_
+_