INSTALLATION INSTRUCTIONS
E600 SERIES MAGNETIC LOCK
The E600 Series magnetic lock is mounted to the underside of the header, on the stop side of the
door. An inswing mounting kit (optional) can be used when mounting on the hinge side of the
door.

Interlocking
Mounting Plate
Quick Mount
Interlocking
Mounting Assembly

Frame

Mounting Screws
Armature

Outswing

Electrical Instructions:
Use properly fused U. L. Listed Power Supply

Electrical Specifications:
Do not install a diode in parallel with any magnetic lock. A diode
will cause a delay when releasing the door and residual magnetism
to occur.

Dual Voltage

12 or 24VDC

Power Consumption
Although SDC recommends the use of a DC power supply, a
transformer with an adjacent mounted full wave bridge rectifier
may be used. A significant drop will occur when using a full wave
bridge rectifier.

500mA@12VDC
250mA@24VDC

DS Door Status Sensor SPDT, 500mA@30VDC
LS Lock Status Sensor SPDT, 2A@30VDC

Any low voltage condition will cause erratic operation of the
optional board sensor.
When using a full wave bridge rectifier all access controls and/or
release contacts must be located between the magnetic lock and rectifier
to ensure quick release.
P:\INSTALLATION INST\Electromagnetic Locks\EXCEL\INST-E600.vsd

REV A

07-10

Page 1

Any suggestions or comments to this instruction or
product are welcome. Please contact us through
our website or email engineer@sdcsecurity.com

1. Inspect the frame header to determine if mounting accessories are required (refer to page 4).
2. Fold template as indicated on dotted line. For single doors locate template against the door and header on the
lock jamb side of the frame.
3. Mark and drill holes as indicated by the template.

STEPS 2 & 3

4. Mount armature to door.

STEP 4

5. Install mounting plate to header with the interlock detail away from the door side of the stop.
Loosely fasten screws through adjustment slot as shown. Assure that the mounting plate and
armature line up properly, then tighten down ALL mounting screws.

STEP 5

P:\INSTALLATION INST\Electromagnetic Locks\EXCEL\INST-E600.vsd

REV A

07-10

Page 2

6. Holding the magnet housing at each end, engage the entire length of the interlock detail, by pushing towards the
door. Tap with a soft hammer to ensure proper alignment and engagement.
CAUTION: The lock body must be held in place until secured with mounting screws. Secure socket head
screws provided inside the housing at each end. Start screws into threads carefully to avoid stripping the
threads. Check alignment and tighten screws. Pull wires through frame, mounting plate and magnet housing

STEP 6

7. Select jumper position for 12VDC or 24VDC. Connect power to magnetic lock.
1

Lock Status
Switch

4

Door Position Sensor (Reed switch)
NC
COM
RED (open with door closed)
BLACK
GREEN (closed with door closed)
NO

5

NO C NC

2 3

+ -

Power
Supply

LED
24VDC

Voltage Jumper

12VDC

A RED LED INDICATES
ENERGIZED & UNSECURED
(GREEN=ENERGIZED & SECURE)

+
A/C
MAINS

POWER
SUPPLY

-

12VDC
or
24VDC

SWITCH or ACCESS CONTROL

8. Test operation. When all is operating properly, tighten
all screws as shown. Install anti-tamper plugs over socket head
screws using a soft hammer to avoid damage to the housing.

P:\INSTALLATION INST\Electromagnetic Locks\EXCEL\INST-E600.vsd

REV A

07-10

Page 3

MOUNTING ACCESSORIES:
STOP FILLER PLATE
EF02
Inches: 10.5" L x 0.5" H x 0.75" D
mm: 266 L x 12.7 H x 19 D
May be field cut for use with E600

GLASS DOOR ARMATURE BRACKET
E6U
For use with Model E600 Series
Field adjustable for glass thickness

ANGLE BRACKET
E12L
Inches: 10.5" L x 0.5" H x 0.75" D
mm: 266 L x 12.7 H x 19 D
May be field cut for use with E600

TOP JAMB MOUNTING BRACKET
E6Z
For use with Model E600 Series

ADJUSTABLE ANGLE BRACKET
E6A
For use with Model E600 Series

Supplied Mounting Hardware

To maintain surface plating from corrosion:
Do not touch the lock face with your hands.
Clean lock face with Scotch-Brite pad by 3M (do not use sandpaper).
Apply a thin film of rust inhibitor (LPS-3) on lock face.
Repeat application on armature plate.

P:\INSTALLATION INST\Electromagnetic Locks\EXCEL\INST-E600.vsd

REV A

07-10

Page 4



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
XMP Toolkit                     : 3.1-702
Create Date                     : 2010:07:16 11:07Z
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2010:11:22 11:03:15-08:00
Metadata Date                   : 2010:11:22 11:03:15-08:00
Format                          : application/pdf
Creator                         : sdc-36
Title                           : Visio-INST-E600.vsd
Producer                        : GPL Ghostscript 8.15
Document ID                     : uuid:878644ce-a9c9-4975-9c2c-5adfad0182e2
Instance ID                     : uuid:3955cabd-f1cc-4ec0-b5ba-43e00b0603fb
Page Count                      : 4
Author                          : sdc-36
EXIF Metadata provided by EXIF.tools

Navigation menu