1_COUV.fm Page 1 Mardi, 2. avril 2002 6:21 18

Guide de programmation
Programming Manual
Programmieranleitung
Guía de programación
Guida programmazione

Altivar 58
Telemecanique
Terminal d'exploitation
Display Module
Bedienterminal
Terminal de explotación
Terminale di esercizio

VW3-A58101

GP_ATV58_DE.fm Page 149 Mardi, 2. avril 2002 6:01 18

Menü "Belegung der Eingänge/Ausgänge"

Bei bestimmten Neuzuordnungen erscheinen neue Einstellparameter, deren Abgleich Sie im Menü
"Steuerung", "Antrieb" oder "Fehlerbehandlung" nicht vergessen sollten:
E/A

Zuordnung

Einstellparameter

LI

-SP

-Drehzahl

Str (Menü Steuerung)

LI

FST

Schnellhalt

dCF (Menü Antrieb)

LI

RST

Fehlerreset

rSt (Menü Fehlerbehandlung)

AI

SFB

Tachogenerator

Sdd (Menü Fehlerbehandlung)

A+, A-,
B+, B-

SAI

Summensollwert

PGt, PLS (Menü Antrieb)

A+, A-,
B+, B-

RGI

Istwert Geber

PGt, PLS (Menü Antrieb)

DEUTSCH
149

GP_ATV58_DE.fm Page 150 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Inkompatibilitäten von Funktionen

Momentenbegrenzung über LI

Momentenbegrenzung über AI3

Drehzahlregelung mit
Tachogenerator oder Encoder

Vorwahlfrequenzen

Schrittbetrieb

Schnellhalt

Freier Auslauf

➞

Bremsung durch Einspeisung
von Gleichstrom

Umschalten der Sollwerte

+/- Drehzahl

PI-Regler

Sollwertsummierung

Bremsung durch Einspeisung
von Gleichstrom

Die Auswahl der Anwendungsfunktionen ist durch die Unvereinbarkeit bestimmter Funktionen untereinander
begrenzt. Die nicht in dieser Tabelle aufgeführten Funktionen sind frei von derartigen Einschränkungen.

Sollwertsummierung
PI-Regler

➞

Umschalten der Sollwerte

➞

Freier Auslauf

➞

DEUTSCH

+/- Drehzahl

Schnellhalt
Vorwahlfrequenzen

➞

➞

Schrittbetrieb

➞
➞

Drehzahlregelung mit
Tachogenerator oder Encoder
Momentenbegrenzung über AI3
Momentenbegrenzung über LI

Unvereinbare Funktionen
Vereinbare Funktionen
Gegenstandslos
Vorrangfunktionen (Funktionen, die nicht gleichzeitig aktiviert werden können):

➞

➞

Die durch den Pfeil angegebene Funktion besitzt den Vorrang gegenüber der anderen.

Die Anhaltefunktionen (z. B. Schnellhalt, DC-Bremsung) besitzen den Vorrang gegenüber den Fahrbefehlen.
Die Funktionen Frequenzvorwahl und Jog besitzen den Vorrang gegenüber den Analogsollwerten.

150

GP_ATV58_DE.fm Page 151 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Anwendungsfunktionen der Logikeingänge
Drehrichtung: Rechtslauf / Linkslauf
Für Anwendungen, die Motorbetrieb in beiden Drehrichtungen erfordern, kann die Funktion "Linkslauf"
verwendet werden.
2-Draht-Steuerung
Der Fahrbefehl (Rechtslauf oder Linkslauf) und das Anhalten werden über denselben Logikeingang gesteuert.
Der Zustand (logisch 1 oder 0) beziehungsweise die Zustandsänderung werden ausgewertet (siehe
Menüpunkt "Typ 2-Draht-Steuerung").
3-Draht-Steuerung
Der Fahrbefehl (Rechtslauf oder Linkslauf) und das Anhalten werden über 2 verschiedene Logikeingänge
gesteuert.
LI1 ist immer der Anhaltefunktion zugeordnet. Das Anhalten wird durch das Öffnen erreicht (logisch 0).
Der Impuls des Eingangs "Betrieb" wird bis zum Öffnen des Eingangs "Anhalten" gespeichert.
Bei einem Einschalten oder einem manuellen oder automatischen Reset einer Störung kann der Motor erst
nach einem Rücksetzen der Befehle "Rechtslauf", "Linkslauf", "Anhalten über DC-Bremsung" mit Spannung
versorgt werden.

Wenn ein Logikeingang dieser Funktion zugeordnet ist, kann das Umschalten der Rampe nur über diesen
Eingang erfolgen.
Schrittbetrieb ”JOG”: Impuls bei Betrieb mit niedriger Frequenz
Wenn der JOG-Befehl vor dem Fahrbefehl aktiviert wird, beträgt die Rampenzeit 0,1 s - unabhängig von den
Einstellungen der Parameter ACC, dEC, AC2 und dE2. Wenn der JOG-Befehl nach dem Fahrbefehl aktiviert
wird, werden die eingestellten Rampenzeiten verwendet.
Über das Menü Einstellung zugängliche Parameter:
- JOG-Frequenz
- Verzögerung (minimale Zeit zwischen 2 “JOG”-Befehlen).

151

DEUTSCH

Umschalten der Rampe: Erste Rampe : ACC, DEC ; Zweite Rampe : AC2, DE2
Es bestehen 2 Aktivierungsmöglichkeiten:
- Aktivierung eines Logikeingangs LIx
- Überschreiten eines einstellbaren Frequenzschwellwertes.

GP_ATV58_DE.fm Page 152 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

+/- Drehzahl: 2 Betriebsarten sind verfügbar.
1 Verwendung von Tastern mit einfacher Betätigung: Zwei Logikeingänge sind zusätzlich zu der oder den
Drehrichtungen erforderlich.
Der mit “+ Drehzahl” belegte Eingang erhöht die Drehzahl, der mit “- Drehzahl” belegte Eingang verringert
die Drehzahl.
Diese Funktion gibt Zugriff auf den Parameter "Sollw-Speich" im Menü "Steuerung".
2 Verwendung von Tastern mit doppelten Kontakten: Nur ein Logikeingang, der "+ Drehzahl" zugeordnet ist,
ist erforderlich.
+ Drehzahl/ - Drehzahl mit Tastern mit doppelten Kontakten:
Beschreibung: 1 Taster, der zweifach gedrückt werden kann, für jede Drehrichtung.
Jedes Betätigen schließt einen Normalkontakt.
Losgelassen
(- Drehzahl)

Erstes Drücken
(Drehzahl halten)

Zweites Drücken
(+ Drehzahl)

Taster Rechtslauf

–

a

a und b

Taster Linkslauf

–

c

c und d

DEUTSCH

Anschlußbeispiel:

Steuerklemmenleiste ATV58

LI1 LIx LIy

LI1 : Rechtslauf
LIx : Linkslauf
LIy : schneller

+ 24

b
a

d

c

Motorfrequenz

LSP
0
LSP

Rechtslauf
Kontakt 2
Kontakt 1
0

b
a

a

b
a

a

a

a

a

Linkslauf
Kontakt 2
Kontakt 1
0

d
c

c

Diese Version von "+/- Drehzahl" ist mit der 3-Draht-Steuerung nicht vereinbar. In diesem Fall wird die
Funktion "- Drehzahl" automatisch dem Logikeingang mit dem nächsthöheren Wert (Beispiel: LI3 (+ Drehzahl),
LI4 (- Drehzahl)) zugeordnet.
In beiden Anwendungsfällen wird die maximale Drehzahl über die an den Analogeingängen
anliegenden Sollwerte vorgegeben.

152

GP_ATV58_DE.fm Page 153 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Vorwahlfrequenzen
Es können 2, 4 oder 8 Frequenzen vorgewählt werden, die jeweils 1, 2, oder 3 Logikeingänge benötigen.
Die folgende Reihenfolge der Zuordnungen muß eingehalten werden: PS2 (LIx), dann PS4 (LIy), dann PS8
(LIz).
2 Vorwahlfrequenzen

4 Vorwahlfrequenzen

8 Vorwahlfrequenzen

Zuordnen: LIx zu PS2

Zuordnen: LIx zu PS2, dann
LIy zu PS4

Zuordnen: LIx zu PS2
LIy zu PS4, dann LIz zu PS8

LIx

LIy

LIx

LIz

LIy

LIx

0

LSP+Sollwert

Frequenzsollwert

0

0

LSP+Sollwert

Frequenzsollwert

0

0

0

LSP+Sollwert

Frequenzsollwert

1

HSP

0

1

SP2

0

0

1

SP2

1

0

SP3

0

1

0

SP3

1

1

HSP

0

1

1

SP4

1

0

0

SP5

1

0

1

SP6

1

1

0

SP7

1

1

1

HSP

DEUTSCH

Um die Zuordnung der Logikeingänge aufzuheben, muß folgende Reihenfolge eingehalten werden:
PS8 (LIz), dann PS4 (LIy), dann PS2 (LIx).
Umschalten des Sollwerts
Umschalten von zwei Sollwerten (Sollwert an AI1 und Sollwert an AI2) durch Befehl am Logikeingang.
Diese Funktion ordnet automatisch AI2 dem Frequenzsollwert 2 zu
Verdrahtung
LI x + 24

COM

AI 1

+10

AI 2

Kontakt offen, Sollwert = AI2
Kontakt geschlossen, Sollwert = AI1
0-20mA
4-20mA

Anhalten im freien Auslauf
Anhalten des Motors ausschließlich über das Lastmoment, die Spannungsversorgung des Motors ist
unterbrochen.
Das Anhalten im Freilauf wird durch das Öffnen des Logikeingangs (logisch 0) erreicht.
Anhalten durch Einspeisung von Gleichstrom
Anhalten über Gleichstrombremsung durch Aktivierung des Logikeingangs (logisch 1).
Schnellhalt
Gebremstes Anhalten mit verringerter Auslaufzeit. Eingabe des Reduktionsquotienten im Menü "Antrieb".
Schnellhalt durch Öffnen des Logikeingangs (logisch 0).

153

GP_ATV58_DE.fm Page 154 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Umschalten der Motoren
Abwechselnder Betrieb von zwei Motoren unterschiedlicher Leistung.
Für die Umschaltung der Motoren ist im Umrichterausgang eine geeignete Steuerung vorzusehen.
Umschaltung nur im Stillstand bei verriegeltem Umrichter. Von der Umschaltung betroffene Parameter:
- Ie motor
- Bremsabfallstrom
- I DC-Bremsung
Der thermische Schutz wird für den zweiten Motor nicht durchgeführt.
Parameter: Verhältnis der Motorleistungen PCC im Menü "Antrieb".
Zweite Drehmomentbegrenzung
Verringerung des maximalen Motormoments, wenn der Logikeingang aktiviert ist.
Parameter: tL2 im Menü "Einstellung".
Fehlerreset
Zwei Arten des Rücksetzens sind möglich: Teilreset oder Globalreset (Parameter rSt im Menü "Fehlerbehandlung").

DEUTSCH

Teilreset (rSt = RSP):
Ermöglicht das Löschen der gespeicherten Störung und das erneute Freigeben des Umrichters, wenn die
Ursache der Störung verschwunden ist.
Von einem teilweisen Löschen betroffene Störungen:
- Überspannung Netz
- Überspannung DC-Bus
- Ausfall Motorphase
- Ausreißen der Last

- Störung Kommunikation
- Überlast Motor
- Verlust 4-20 mA
- externe Störung

- Überhitzung Motor
- Störung serielle Schnittstelle
- Überhitzung Umrichter
- Rückführung fehlt

Globalreset (rSt = RSG):
Unterdrückung (erzwungener Betrieb) aller Störungen außer Kurzschluß Motor, während der
zugeordnete Logikeingang geschlossen ist.
Vor-Ort-Steuerung
Ermöglicht das Umschalten von der Steuerung über serielle Schnittstelle oder Feldbus auf einen lokalen
Modus (Steuerung über Klemmenleiste oder Terminal).
Motormessung
Der Übergang auf 1 des zugeordneten Logikeingangs löst eine Motormessung aus, ebenso wie der Parameter
tUn des Menüs "Antrieb".
ACHTUNG: Die Motormessung wird nur dann ausgeführt, wenn zuvor kein Befehl aktiv ist. Wenn ein
Logikeingang mit der Funktion "Freier Auslauf" oder "Schnellhalt" belegt ist, muß dieser Eingang
gesetzt werden (inverse Logik).
Anwendung: Beispielsweise bei der Umschaltung der Motoren.
Auto-Manu PI, PI-Vorwahl-Sollwerte: Siehe Funktion PI (Seite 155)
Drehmomentbegrenzung über AI
Diese Funktion ist nur anwählbar wenn der Analogeingang AI3 auf Drehmomentbegrenzung eingestellt ist.
Wenn keiner der LI auf "TL2: zweite Drehmomentbegrenzung" eingestellt ist: Drehmomentbegrenzung direkt
über AI3.Wenn ein LI auf "TL2: zweite Drehmomentbegrenzung" eingestellt ist:
Wenn LI auf logisch 0: Drehmomentbegrenzung über tLi
Wenn LI auf logisch 1: Drehmomentbegrenzung über AI3
Externer Fehler
Der Übergang auf 1 des zugeordneten Logikeingangs löst das Anhalten des Motors (je nach Konfiguration des
Parameters Stt Stop Type im Menü Antrieb) und die Verriegelung des Umrichters mit der Störung EPF ext.
Fehler aus.
154

GP_ATV58_DE.fm Page 155 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Anwendungsfunktionen der Analogeingänge
Der Eingang AI1 ist immer der Frequenzsollwert.

Belegung von AI2 und AI3
Summe Frequenzsollwert: Die an AI2 und AI3 anliegenden Sollwerte können zu AI1 addiert werden.
Tachorückführung: (Nur für AI3 bei vorhandener Optionskarte E/A-Erweiterung):
Ermöglicht eine Drehzahlkorrektur über den Istwert des Tachogenerators.
Ein externer Spannungsteiler ist für die Anpassung der Spannung des Tachogenerators erforder-lich. Die
maximale Spannung muß zwischen 5 und 9 V liegen. Genauer Abgleich über Parameter dtS (Menü
"Einstellung").
Auswertung PTC-Fühler: (Nur für AI3 bei vorhandener Optionskarte E/A-Erweiterung).
Ermöglicht einen direkten Schutz des Motors durch Anschluß der in den Motorwicklungen integrierten PTCFühler am Analogeingang AI3.
Kenndaten der PTC-Fühler:
Gesamtwiderstand der Fühlerschaltung bei 20 °C = 750 W.

Warnung: Die Funktion PI-Regler ist aktiv, wenn ein Eingang AI dem PI-Istwert zugeordnet ist. Diese
Zuordnung zu AI ist erst möglich, wenn zuvor die mit PI unvereinbaren Funktionen gesperrt wurden (voir
page 150).

PI-Sollwert

+
-

PI-Istwert

PSP

TiefpaßFilter

FBS
10

Umkehrung
PI-Regler

PI-Regler

PIC
X±1

RPG
RIG

Rampe
wenn PSP = 0
X

ACC
dEC
Sollwert

Rampe
wenn PSP > 0

AC2
dE2

Auto
Manu

Multiplikator
Fahrbefehl

Manueller Sollwert

Auto / Manu

ACC
dEC
Rampe

Auto / Manu: Diese Funktion ist nur zugänglich, wenn die Funktion PI aktiviert ist und eine Optionskarte E/A
Erweiterung mit Analogeingang vorhanden ist.
Ermöglicht über den Logikeingang LI die Umschaltung des Betriebs auf Frequenzregelung, wenn LIx = 0
(manueller Sollwert an AI3), und auf PI-Regelung, wenn LIx = 1 (auto).
155

DEUTSCH

PI-Regler: Ermöglicht die Regelung eines Prozesses mit einem Sollwert und einem von einem Geber
übermittelten Istwert. Mit der PI-Funktion sind alle Rampen linear, auch wenn sie anders konfiguriert sind.
Mit dem PI-Regler lässt sich folgendes realisieren:
- Anpassung des Istwerts über FbS.
- Durchführung einer umgekehrten PI-Korrektur (PIC).
- Regelung des P- und I-Anteils (RPG und RIG).
- Zuweisung eines Analogausgangs für PI-Sollwert, PI-Istwert und PI-Abweichung.
- Anwendung einer Rampe zum Aufbau der Wirkung des PI-Reglers (AC2) beim Anlaufen, wenn PSP > 0.
Wenn PSP = 0, sind die aktiven Rampen ACC / dEC. Beim Anhalten wird immer die Rampe dEC
verwendet.
Die Motordrehzahl ist zwischen LSP und HSP begrenzt.

GP_ATV58_DE.fm Page 156 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Vorwahl-Sollwerte:
2 oder 4 Vorwahl-Sollwerte erfordern jeweils die Verwendung von 1 oder 2 Logikeingängen:

LIx

2 Vorwahl-Sollwerte

4 Vorwahl-Sollwerte

Zuordnen: LIx zu Pr2

Zuordnen: LIx zu Pr2, dann LIy zu Pr4

Sollwert

0

Analogsollwert

1

Max. Prozeß (= 10 V)

LIy

LIx

0

0

Sollwert
Analogsollwert

0

1

PI2 (regelbar)

1

0

PI3 (regelbar)

1

1

Max. Prozeß (= 10 V)

Momentenbegrenzung: (Nur mit einer Optionskarte E/A-Erweiterung mit Analogeingang AI3)
Das an AI3 anliegende Signal wirkt linear auf die interne Drehmomentbegrenzung (Parameter TLI des Menüs
"Antrieb"):
- Wenn AI3 = 0V : Begrenzung = TLI x 0 = 0
- Wenn AI3 = 10 V : Begrenzung = TLI.
Anwendungen: Korrektur des Drehmoments, des Antriebs…

Anwendungsfunktionen des Gebereingangs:
DEUTSCH

(Nur mit einer Optionskarte E/A-Erweiterung mit Gebereingang)
Drehzahlregelung: Ermöglicht eine Drehzahlkorrektur über Inkrementalgeber oder Impulsgeber (siehe die mit
der Karte gelieferte Dokumentation).
Frequenz-Summensollwert: Der sich aus dem Gebereingang ergebende Sollwert bildet eine Summe mit AI1
(siehe die mit der Karte gelieferte Dokumentation).
Anwendungen:
- Synchronisierung der Frequenz mehrerer Umrichter. Der Parameter PLS im Menü "Antrieb" ermöglicht
die Einstellung des Verhältnisses der Drehzahl eines Motors zu der eines anderen.
- Sollwert über Impulsgeber.

156

GP_ATV58_DE.fm Page 157 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Anwendungsfunktionen der Logikausgänge
Relais R2, statischer Ausgang LO (mit E/A-Karte)
Steuerung Motorschütz (OCC): zuordenbar zu R2 oder LO
Ansteuerung eines Schützes zwischen Umrichter und Motor. Der Anzug des Schützes erfolgt bei Vorliegen
eines Fahrbefehls. Das Abfallen des Schützes erfolgt, wenn kein Strom mehr im Motor fließt.
Wenn eine Funktion "Gleichstrombremsung" konfiguriert wird, sollte sie im Stillstand nicht zu lange
weiter aktiv sein, da das Schütz erst am Ende der Bremsung abfällt.
Umrichter in Betrieb (RUN) : zuordenbar zu R2 oder LO
Der Logikausgang wird gesetzt, wenn der Motor vom Umrichter gespeist wird (Strom vorhanden), oder wenn
ein Fahrbefehl mit einem Sollwert Null vorliegt.
Frequenzschwellwert erreicht (FTA) : zuordenbar zu R2 oder LO
Der Logikausgang wird gesetzt, wenn die Motorfrequenz größer oder gleich dem über Ftd im Menü Einstellung
eingestellten Frequenzschwellwert ist.
2. Frequenzschwellwert erreicht (F2A) : zuordenbar zu R2 oder LO
Der Logikausgang wird gesetzt, wenn die Motorfrequenz größer oder gleich dem über F2d im Menü
Einstellung eingestellten Frequenzschwellwert ist.
Sollwert erreicht (SRA): zuordenbar zu R2 oder LO
Der Logikausgang wird gesetzt, wenn die Motorfrequenz gleich dem Sollwert ist.

Stromschwellwert erreicht (CTA): zuordenbar zu R2 oder LO
Der Logikausgang wird gesetzt, wenn der Motorstrom größer oder gleich dem im Menü "Einstellung"
vorgegebenen Stromschwellwert Ctd ist.
Thermischer Zustand erreicht (TSA) : zuordenbar zu R2 oder LO
Der Logikausgang wird gesetzt, wenn der thermische Motorzustand größer oder gleich dem im Menü
"Einstellung" vorgegebenen Schwellwert ttd des thermischen Zustands ist.
Thermischer Zustand Umrichter erreicht (TAD): zuordenbar zu R2 oder LO
Der Logikausgang ist auf logisch 1, wenn der thermische Umrichterzustand größer oder gleich dem über dtd
im Menü Einstellung eingestellten Schwellwert des thermischen Zustands ist.
Bremssteuerung (BLC) : ausschließlich zuordenbar zu Relais R2
Ansteuerung einer elektromagnetischen Bremse über den Umrichter bei Hubanwendungen. Bei Horizontalbewegungen die Funktion “Umrichter in Betrieb“ verwenden.
Motorfrequenz

T = feste Verzögerungszeit (nicht
einstellbar)

Sollwert

Zugängliche Parameter im Menü
"Einstellung":
- Bremsabfallfrequenz (brL)
- Bremsabfallverzögerung (brt)
- Bremsanzugsverzögerung (bEt)
- Bremsabfallstrom (Ibn)
- Bremsanzugsfrequenz (bEn)

Zustand Bremse
1
0
Relais R2
1
0
Anziehen oder Abfallen
1
0
T

brt

bEt

157

DEUTSCH

Große Frequenz erreicht (FLA): zuordenbar zu R2 oder LO
Der Logikausgang wird gesetzt, wenn die Motorfrequenz gleich HSP ist.

GP_ATV58_DE.fm Page 158 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Empfohlene Einstellung der Bremssteuerung bei einer vertikalen Hubanwendung:
1 Bremsabfallfrequenz (brL), Lüftung der bremse:
Die Bremsabfallfrequenz auf folgenden Wert einstellen: Nennschlupf multipliziert mit der Nennfrequenz in
Hz (sn x fs).
( ns – nr )
Berechnung : s = ---------------------n
ns
- ns = Synchrondrehzahl in U / min.
(bei einem Netz 50 Hz: ns = 3000 U/min bei einem Motor mit 1 Polpaar, 1500 U/min bei einem Motor mit 2
Polpaaren, 1000 U/min bei einem Motor mit 3 Polpaaren und 750 U/min bei einem Motor mit 4 Polpaaren,
bei einem Netz 60 Hz: ns = 3600 U/min bei einem Motor mit 1 Polpaar, 1800 U/min bei einem Motor mit 2
Polpaaren, 1200 U/min bei einem Motor mit 3 Polpaaren und 900 U/min bei einem Motor mit 4 Polpaaren).
- ns = Nenndrehzahl bei Nennmoment in U/min. Die auf den Motor gestempelte Drehzahl übernehmenr.
Abfallfrequenz = sn • fs.
- sn = zuvor berechneter Schlupf.
- fs = Nennfrequenz des Motors gemäß Typenschild (i. A. 50 Hz oder 60 Hz).
Beispiel: bei einem Motor mit 2 Polpaaren, gestempelt für 1430 U/min, Netz 50 Hz.
sn = (1500 - 1430) / 1500 = 0.0466.
Bremsabfallfrequenz = 0.0466 x 50 = 2.4 Hz

DEUTSCH

2 Bremsabfallstrom (Ibr), Lüftung der bremse:
Den Bremsabfallstrom auf den Nennstrom gemäß Typenschild des Motors einstellen.
Anmerkung zu den Punkten 1 und 2: Die angegebenen Werte (Abfallstrom und Abfallfrequenz) entsprechen
theoretischen Werten. Wenn bei Tests das Drehmoment mit den theoretischen Werten nicht ausreichend
ist, sollte der Bremsabfallstrom auf dem Nennstrom des Motors bleiben und die Bremsabfallfrequenz
abgesenkt werden (bis zu 2/3 des Nennschlupfs). Wenn auch dann das Ergebnis noch nicht zufriedenstellend ist, wieder zu den theoretischen Werten zurückkehren und den Bremsabfallstrom erhöhen (der
maximale Wert wird durch den Umrichter vorgegeben) und die Bremsabfallfrequenz schrittweise erhöhen.
3 Hochlaufzeit:
Für Hubanwendungen empfehlen wir die Einstellung der Hochlauframpen auf einen Wert größer 0.5
Sekunden. Überprüfen, daß der Umrichter nicht in Strombegrenzung übergeht.
Dieselbe Empfehlung gilt auch für die Auslaufzeit.
Bitte beachten: Bei einer Hubbewegung muß ein Bremswiderstand verwendet werden und es ist zu
gewährleisten, daß die gewählten Einstellungen und Konfigurationen zu keinem Sturz oder Verlust der
Kontrolle über die angehobene Last führen kann.
4 Verzögerung des Bremsabfalls (brt), Lüftung der bremse:
In Abhängigkeit des Bremsentyps einstellen. Dies ist die erforderliche Zeit, die die mechanische Bremse
zum Öffnen benötigt.
5 Anzugsfrequenz der Bremse (bEn):
Den 2fachen Wert des Nennschlupfs einstellen (in unserem Beispiel 2 x 2.4 = 4.8 Hz). Anschließend in
Abhängigkeit des erzielten Ergebnisses einstellen.
6 Verzögerung des Anziehens der Bremse (bEt):
In Abhängigkeit des Bremsentyps einstellen. Dies ist die erforderliche Zeit, die die mechanische Bremse
zum Anziehen benötigt.
Verlust 4-20 mA (APL) zuordenbar zu R2 oder LO
Der Logikausgang ist auf logisch 1, wenn das Signal am Eingang 4-20 mA unter 2 mA ist.

158

GP_ATV58_DE.fm Page 159 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

Anwendungsfunktionen des Analogausgangs AO und AO1
Die Analogausgänge AO und AO1 sind Stromausgänge, von AOL (mA) bis AOH (mA),
• AOL und AOH sind konfigurierbar von 0 bis 20 mA.
Beispiele AOL - AOH :

0 - 20 mA
4 - 20 mA
20 - 4 mA

Motorstrom (OCR) : Abbild des im Motor fließenden Effektivstroms.
• AOH entspricht dem doppelten Nennstrom des Umrichters.
• AOL entspricht dem Strom Null.
Motorfrequenz (OFR) : Abbild der vom Umrichter geschätzten Motorfrequenz.
• AOH entspricht der maximalen Frequenz (Parameter tFr).
• AOL entspricht Frequenz Null.
Ausgang Rampe (ORP) : Abbild der Frequenz am Ausgang der Rampe.
• AOH entspricht der maximalen Frequenz (Parameter tFr).
• AOL entspricht Frequenz Null.

DEUTSCH

Motormoment (TRQ) : Abbild des Motormoments.
• AOH entspricht dem doppelten Nennmoment des Motors.
• AOL entspricht Drehmoment Null.
Motormoment mit Vorzeichen (STQ) : Abbild des Motormoments und seiner Richtung:
• AOL entspricht einem Bremsmoment = doppeltes Nennmoment
• AOH entspricht einem Motormoment = doppeltes Nennmoment.
• AOH + AOL entspricht Drehmoment Null.
2
Rampe mit Vorzeichen (ORS) : Abbild der Frequenz am Ausgang der Rampe und ihrer Richtung.
• AOL entspricht der maximalen Frequenz (Parameter tFr) bei Linkslauf.
• AOH entspricht der maximalen Frequenz (Parameter tFr) bei Rechtslauf.
• AOH + AOL entspricht Frequenz Null
2
PI-Sollwert (OPS) : Abbild des Sollwerts des PI-Reglers.
• AOL entspricht dem minimalen Sollwert.
• AOH entspricht dem maximalen Sollwert.
PI-Istwert (OPF) : Abbild des Istwerts des PI-Reglers.
• AOL entspricht dem minimalen Istwert.
• AOH entspricht dem maximalen Istwert.

159

GP_ATV58_DE.fm Page 160 Mardi, 2. avril 2002 6:01 18

Funktionen der konfigurierbaren Ein-/Ausgänge

PI-Abweichung (OPE) : Abbild der Abweichung des PI-Reglers in % des Bereiches des Fühlers (max.
Istwert - min. Istwert).
• AOL entspricht dem maximalen Fehler < 0.
• AOH entspricht dem minimalen Fehler > 0.
• AOH + AOL entspricht einem Fehler 0 (OPE=0).
2
PI-Integral (OPI) : Abbild des Integrals der Abweichung des PI-Reglers.
• AOL bedeutet Integral Null
• AOH bedeutet Integral gesättigt
Motorleistung (OPR) : Abbild der vom Motor aufgenommenen Leistung.
• AOL entspricht 0 % der Nennleistung des Motors.
• AOH entspricht 200 % der Nennleistung des Motors.
Motorerwärmung (THR) : Abbild des thermischen Zustands des Motors (berechnet).
• AOL entspricht 0 %.
• AOH entspricht 200 %.

DEUTSCH

Erwärmung Umrichter (THD) : Abbild des thermischen Zustands des Umrichters.
• AOL entspricht 0 %.
• AOH entspricht 200 %.

160

GP_ATV58_DE.fm Page 161 Mardi, 2. avril 2002 6:01 18

Menü "Fehlerbehandlung"

Dieses Menü ist zugänglich in Position
des Programmierschalters (Niveau 2).
Veränderungen können nur im Stillstand bei verriegeltem Umrichter ausgeführt werden.
Code

Beschreibung

Werks-einstellung

Atr

Aut Neustart

Nein

rSt

Fehlerreset

RSP

Diese Funktion ist zugänglich, wenn der Fehlerreset einem Logikeingang zugeordnet ist.
2 Auswahlen möglich: Teilreset (RSP), Globalreset (RSG) Durch einen Teilreset betroffene
Störungen (rSt = RSP)
- Überspannung Netz
- Überspannung DC-Bus
- Überhitzung Motor
- Verlust 4-20 mA
- Motorüberlast
- Ausreißen der Last
- Motorphase fehlt
- Überhitzung Umrichter
- Störung serielle Schnittstelle
- Externe Störung
- Störung Kommunikation
- Rückführung fehlt
Durch einen Globalreset betroffene Störungen (rSt = RSG): alle Störungen. Der Globalreset
bedeutet eine Unterdrückung aller Störungen außer Kurzschluß (erzwungener Betrieb).
Um rSt = RSG zu konfigurieren:
1 - RSG anzeigen
2 - auf die Taste "ENT" drücken
3 - der Umrichter zeigt "vgl. prog.-Anl." an
4 - auf ▲ dann auf ▼ ,anschließend auf "ENT" drücken

OPL

Mot-ph fehlt

Ja

Aktivierung der Motorphasenüberwachung (nicht verwenden bei Installation eines Schützes
zwischen Umrichter und Motor). Auswahl: Ja / Nein

IPL

Netzph fehlt

Ja

Aktivierung der Netzphasenüberwachung (nicht verwenden bei direkter Speisung über
Gleichstromzwischenkreis und bei einphasiger Speisung eines dreiphasigen Umrichters ATV58•
U72M2, U90M2 oder D12M2). Auswahl: Ja / Nein
Diese Störung existiert nicht bei den Typen ATV58•U09M2, U18M2, U29M2 und U41M2.

161

DEUTSCH

Diese Funktion ermöglicht einen automatischen Wiederanlauf des Umrichters, wenn die Störung
verschwunden ist (Auswahl Ja/Nein). Ein automatischer Wiederanlauf ist nach folgenden
Störungen möglich:
- Überspannung Netz
- Überspannung Gleichstromzwischenkreis
- Externe Störung
- Motorphase fehlt
- Störung serielle Schnittstelle
- Störung Kommunikation
- Verlust Sollwert 4-20 mA
- Motorüberlast (Bedingung: Thermischer Zustand des Motors unter 100 %)
- Überhitzung Umrichter (Bedingung: Thermischer Zustand Umrichter unter 70 % abgesunken)
- Überhitzung Motor (Bedingung: Widerstand der Fühler unter 1500 Ω abgesunken)
Wenn diese Funktion aktiviert ist, bleibt das Störmelderelais R1 nach dem Auftreten einer oder
mehrerer dieser Störungen angezogen: der Umrichter führt alle 30 s einen Anlaufversuch durch. Es
werden maximal 6 Versuche durchgeführt, solange der Umrichter nicht anlaufen kann (Andauern
der Störung). Wenn alle 6 Versuche fehlgeschlagen sind, bleibt der Umrichter definitiv verriegelt,
das Störmelderelais fällt ab, bis durch ein Abschalten der Spannung das Relais reaktiviert wird.
Für diese Funktion muß eine geeignete Steuerung vorgesehen werden, und es muß
gewährleistet sein, daß das plötzliche Wiederanlaufen keine Gefahr für Personen oder
Gegenstände darstellt.

GP_ATV58_DE.fm Page 162 Mardi, 2. avril 2002 6:01 18

Menü "Fehlerbehandlung"

Code

Beschreibung

Werks-einstellung

tHt

Therm Schutz

ACL

Definiert die Art des indirekten, durch den Umrichter realisierten Thermoschutzes des Motors.
Wenn PTC-Fühler an den Umrichter angeschlossen sind, ist diese Funktion nicht verfügbar.
Kein thermischer Schutz: N0: Keiner
Motor selbstgekühlt (ACL): Reduzierung des Moments in Abhängigkeit der Frequenz.
Motor fremdgekühlt (FCL): Keine Reduzierung des Moments in Abhängigkeit der Frequenz.

LFL

Verl. 4-20 mA

Nein

Auswertung der Störung "Verl. Sollwert 4-20 mA". Diese Störung kann nur konfiguriert werden,
wenn die Parameter Sollwert min/max AI2 (CrL u. CrH) über 3 mA liegen, oder wenn CrL>CrH.
- Nein : Kein Fehler
- Ja : Fehler sofort
- STT: Halt entsprechend Parameter STT, ohne Fehler, Wiederanlauf auf das zurückgekehrte
Signal
- LSF: Halt nach Parameter STT, danach Fehler
- LFF: Gezwungen auf die Rückzugsdrehzahl, geregelt über den Parameter LFF
- RLS : Erhaltung der erreichten Drehzahl während Verlust 4-20 mA, ohne Fehler,
Wiedereinfangen des zurückgekehrten Signals

LFF

Vorg.-Frequ.4-20

0

DEUTSCH

Vorgabefrequenz bei Verlust Sollwert 4-20 mA. Einstellung von 0 bis HSP.

FLr

Einf im Lauf

Nein

Einfangen im Lauf nach folgenden Ereignissen:
- Netzausfall oder Ausschalten.
- Reset der Störungen oder automatischer Wiederanlauf.
- Anhalten im Freilauf oder über DC-Bremsung mit Logikeingang.
- ungesteuerte Unterbrechung vor dem Umrichter.
Auswahl: Ja / Nein
Wenn Relais R2 mit der Funktion Bremslogik belegt wird, bleibt der Parameter FLr auf Nein
verriegelt.

StP

Gef.Auslauf

Nein

Geführter Auslauf bei Ausfall einer Netzphase. Diese Funktion ist nur dann aktivierbar, wenn IPL
auf "Nein" gesetzt wurde. Wenn IPL = Ja, StP in Position "Nein" belassen. Mögliche Auswahlen:
Nein: Verriegeln bei Netzausfall.
MMS: Umax DC-Bus: Die Steuerspannung wird durch Energierückspeisung vom Motor in den
Zwischenkreis bis zum Auftreten der Störung USF (Unterspannung) aufrechterhalten.
FRP: Auf Rampe; Auslaufzeit je nach programmierter Rampe dEC oder dE2 bis zum Stillstand oder
Eintreten der Störung USF (Unterspannung). Diese Funktion existiert nicht bei ATV58•U09M2,
U18M2, U29M2, U41M2

Sdd

Ausreißerk.

Nein

Diese Funktion ist zugänglich, wenn eine Rückführung über Tachogenerator oder über
Impulsgenerator programmiert ist. Bei Freigabe der Funktion sperrt sie den Umrichter, wenn ein
Nichteinhalten der Drehzahl entdeckt wird (Unterschied zw. Statorfrequenz und gemessener
Drehzahl).
Auswahl: Ja / Nein.

EPL

162

Ext. Fehler
Ja
Definiert den Haltvorgang nach einem externen Fehler:
- Ja: sofortige Verriegelung in Fehlerzustand.
- LSF:Stop+Fehler: Haltvorgang entsprechend dem Parameter Stt (Menü Antrieb) und
nachfolgende Verriegelung in Fehlerzustand.

GP_ATV58_DE.fm Page 163 Mardi, 2. avril 2002 6:01 18

Menü "Konf-Datei"

Dieses Menü ist zugänglich in Position
des Programmierschalters (Niveau 2).
Die Aktionen können nur im Stillstand bei verriegeltem Umrichter durchgeführt werden.
Das Terminal kann 4 Konfigurationsdateien speichern.
Code

Beschreibung

Werks-einstellung

F1S
F2S
F3S
F4S

Zust Datei 1
Zust Datei 2
Zust Datei 3
Zust Datei 4
Zeigt den Zustand der entsprechenden Datei an.
Mögliche Zustände:
FRE: Datei frei (Zustand bei Auslieferung des Terminals)
EnG: In dieser Konfigurationsdatei wurde bereits eine Konfiguration
gespeichert

FRE
FRE
FRE
FRE

FOt

Aktion

NO

DEUTSCH

Auswahl der mit den Konfigurationsdateien auszuführenden Aktionen.
Mögliche Aktionen:
NO: keine Aktion (standardmäßiger Wert bei jedem neuen Anschluß des
Terminals am Umrichter)
STR: Speichern der Konfiguration des Umrichters in einer Datei des
Terminals.
REC: Übertragung des Inhalts einer Datei zum Umrichter
Ini: Rückkehr des Umrichters zu den Werkseinstellungen
Die Rückkehr zu den Werkseinstellungen hebt alle Ihre
Einstellungen und Ihre Konfiguration auf.

Vorgehensweise
Aktion Ini, STR oder REC auswählen, Bestätigung mit ENT.
1 Wenn Aktion = STR:
Anzeige der Dateinummern. Eine Datei über ▲ oder ▼ auswählen und mit "ENT" bestätigen.
2 Wenn Aktion = REC:
Anzeige der Dateinummern. Eine Datei über ▲ oder ▼ auswählen und mit "ENT" bestätigen.
- Auf der Anzeige erscheint:

CHG

VERDRAHTUNG OK?

ENT

Überprüfen, daß die Verdrahtung mit der Konfiguration der Datei vereinbar ist.
Mit "ESC" abbrechen oder mit "ENT" bestätigen
- Die Anzeige fordert darauf eine zweite Bestätigung, die mit "ENT" erteilt oder mit "ESC" verweigert
werden muß.
3 Wenn Aktion = InI:
Bestätigung mit "ENT"
- Auf der Anzeige erscheint:

CHG

VERDRAHTUNG OK?

ENT

Überprüfen, daß die Verdrahtung mit der Werkskonfiguration vereinbar ist.
Mit "ESC" abbrechen oder mit "ENT" bestätigen.
- Die Anzeige fordert darauf eine zweite Bestätigung, die mit "ENT" erteilt oder mit "ESC" verweigert
werden muß.
Am Ende jeder Aktion kehrt die Anzeige zum Parameter "Aktion" und "NO" zurück.

163

GP_ATV58_DE.fm Page 164 Mardi, 2. avril 2002 6:01 18

Menü "Konf-Datei"

Menü Konf-Datei (Fortsetzung)
Code

Beschreibung

COd

Code
Zugriffscode

Die Konfiguration des Umrichters kann über einen Zugriffscode (COd) geschützt werden
ACHTUNG: Dieser Parameter ist mit Vorsicht zu verwenden. Er kann den Zugang zu allen Parametern
sperren. Jede Veränderung des Wertes dieses Parameters muß sorgfältig notiert und aufgezeichnet
werden.
Der Wert des Codes wird über vier Ziffern angegeben. Die letzte Ziffer gibt dabei das Zugriffsniveau an, zu
dem weiterhin ein freier Zugang möglich sein soll.

8888
Diese Ziffer gibt das zulässige
Zugriffsniveau an, ohne Eingabe eines korrekten Codes.

DEUTSCH

Der Zugriff auf die Menüs in Abhängigkeit des Programmierschalters auf der Rückseite des Terminals ist
immer aktiviert, allerdings in den durch diesen Code gesetzten Grenzen.
Der Wert 0000 (Werkseinstellung) schränkt den Zugriff nicht ein.
Die nachstehende Tabelle definiert den Zugriff auf die Menüs in Abhängigkeit der letzten Ziffer des Codes.
Letzte Ziffer des Codes
Menü

Zugriff gesperrt

Anzeige

Änderung

Einstellungen

0 (außer 0000)
und 9

1

2

Niveau 2:
Einstellungen, Makrokonfig., Antrieb, Steuerung,
Belegung E/A, Fehlerbehandlung, Konf-Datei
(außer Code), Kommunikation (wenn Karte
vorhanden)

0 (außer 0000)
und 9

3

4

Applikation (wenn Karte vorhanden)

0 (außer 0000)
und 9

5

6

Niveau 2 und Applikation (wenn Karte vorhanden)

0 (außer 0000)
und 9

7

8

Angaben zum Zugriff auf das Menü Applikation finden Sie in der Dokumentation der Applikationskarte.
Die Änderung des Codes erfolgt über die Tasten ▲ und ▼.
Wenn ein falscher Code eingegeben wird, wird er durch die Anzeige der folgenden Meldung zurückgewiesen:

COd

Falscher Code

Nach Drücken auf die Taste ENT oder ESC der Tastatur wird der angezeigte Wert des Parameters Code zu
0000: Das Zugriffsniveau bleibt unverändert. Die Aktion muß erneut durchgeführt werden.
Um Zugriff auf die durch den Code geschützten Menüs zu erhalten, muß zunächst dieser Code eingegeben
werden, der jederzeit im Menü Konf-Datei zugänglich ist.
164

GP_ATV58_DE.fm Page 165 Mardi, 2. avril 2002 6:01 18

Menüs "Kommunikation" und "Applikation" /
Bedienungsunterstützung / Wartung
Menü "Kommunikation"
Dieses Menü wird nur angezeigt, wenn eine Kommunikationskarte installiert ist. Es ist im Niveau 2 (Position
des Programmierschalters) zugänglich. Eine Konfiguration ist nur im Stillstand bei verriegeltem Umrichter möglich.
Informationen für den Einsatz mit einer optionalen Kommunikationskarte finden Sie in der mit der jeweiligen
Karte ausgelieferten Dokumentation.
Informationen zum Einsatz der Kommunikation über die serielle Schnittstelle RS485 des Basisgerätes finden
Sie in der mit der Anschaltbaugruppe RS485 gelieferten Dokumentation.

Menü "Applikation"
Dieses Menü wird nur angezeigt, wenn eine Karte “Applikation Kunde“ installiert ist. Es ist im Niveau 2
(Position
des Programmierschalters) zugänglich. Eine Konfiguration ist nur im Stillstand bei verriegeltem
Umrichter möglich.
Weitere Informationen finden Sie in der mit dieser Karte ausgelieferten Dokumentation.

Bedienungsunterstützung
Siehe die Anzeige-LEDs im Kapitel "Allgemeines".

Wartung

ACHTUNG: Die Gleichspannung an den Klemmen + und - oder PA und PB kann je nach Netzspannung
bis zu 900 V erreichen.
Wenn bei Inbetriebnahme oder Bedienung Unregelmäßigkeiten auftreten, muß zunächst überprüft werden,
daß die Empfehlungen zur Aufstellung, Montage und zu den Anschlüssen beachtet wurden.
Weitere Informationen finden Sie in der Bedienungsanleitung des Altivar-58-Basisgerätes.

Wartung
Der Altivar 58 benötigt keine vorbeugende Wartung. Dennoch empfehlen wir, in regelmäßigen Abständen
folgende Überprüfungen durchzuführen:
- Den Zustand und das Anzugsmoment der Anschlüsse überprüfen.
- Überprüfen, daß sich die Temperatur in der Nähe des Gerätes in einem akzeptablen Bereich bewegt und
daß die Belüftung wirksam ist (mittlere Lebensdauer der Lüfter: 3 bis 5 Jahre je nach Einsatzbedingungen).
- Gegebenenfalls den Umrichter von Staub befreien.

Wartungsunterstützung
Die erste festgestellte Störung wird gespeichert und auf dem Display des Terminals angezeigt: Der Umrichter
verriegelt sich, die rote LED leuchtet und das Sicherheitsrelais R1 fällt ab.

Löschen von Störungen
Die Spannungsversorgung des Umrichters beim Auftreten von Störungen, die ein Wiederein-schalten nicht
zulassen, unterbrechen.
Die Ursache der Störung suchen und diese beheben.
Die Spannungsversorgung wiederherstellen: Wenn der Fehler verschwunden ist, wird er daraufhin gelöscht.
In bestimmten Fällen kann nach Verschwinden der Störung ein automatischer Wiederanlauf erfolgen, falls
diese Funktion programmiert wurde.
165

DEUTSCH

Vor jedem Eingriff in den Umrichter die Spannungsversorgung unterbrechen und das
Entladen der Zwischenkreiskondensatoren abwarten (etwa 3 Minuten): Erlöschen der grünen
LED auf der Vorderseite des Umrichters.

GP_ATV58_DE.fm Page 166 Mardi, 2. avril 2002 6:01 18

Wartung

DEUTSCH

Angezeigte Störung Wahrscheinliche Ursache

Maßnahme, Behebung

PHF
NETZPHASE FEHLT

• Umrichter fehlerhaft versorgt oder
• den Leistungsanschluß und die
Sicherungen geschmolzen
Sicherungen überprüfen
• Kurzausfall einer Phase
• wieder einschalten
• Betrieb an einphasigem Netz bei einem • die Störung "Netzphase fehlt" (Code
ATV58•U72M2, U90M2 oder D12M2
IPL) mit "Nein" konfigurieren, Menü
(dreiphasig)
"Fehlerbeh"

USF
UNTERSPANNUNG

• Netzspannung zu niedrig
• vorübergehender Spanngsabfall
• Lastwiderstand beschädigt

• Netzspannung überprüfen

OSF
ÜBERSPANNUNG

• Netzspannung zu hoch

• Netzspannung überprüfen

OHF
ÜBERHITZUNG ATV

• Temperatur des Kühlkörpers zu hoch
(tHd>118 %)

• Belastung des Motors, Belüftung des
Umrichters überprüfen und das
Abkühlen abwarten, um wieder
einschalten zu können

OLF
MOTORÜBERLAST

• Thermisches Auslösen bei längerer
Überlast (tHr>118 %)

• die Einstellung des Thermoschutzes
und die Belastung des Motors
überprüfen
• ein Wiedereinschalten ist nach etwa 7
Minuten möglich

ObF
ZU STARKE BREMSG

• Zu starke Bremsung oder antreibende
Last
• Überspannung Netz im Betrieb

• Auslaufzeit erhöhen, gegebenenfalls
einen Bremswiderstand einbauen
• Überwachen auf eventuelle
Überspannung im Netz

OPF
MOTORPHASE FEHLT

• Unterbrechung einer Phase am
Umrichterausgang

• Überwachen Motorphase und
Verbindung Motorschütz (falls
vorhanden)
• Bei der Makrokonfiguration
Motorabgang ist zu beachten, daß
Relais R2 auf Motorschütz konfiguriert
ist

LFF
VERLUST 4-20mA

• Verlust des Sollwerts 4-20 mA an
Eingang AI2

• die Anschlüsse der Sollwertschaltungen überprüfen

OCF
ÜBERSTROM

• Rampe zu kurz
• Massenträgheit oder Last zu hoch
• Mechanische Blockierung

• Einstellungen überprüfen
• Dimensionierung Motor/Umrichter/Last
überprüfen
• Zustand der Mechanik überprüfen

SCF
Kurzschluß Motor

• Kurzschluß oder Erdschluß am
Umrichterausgang

• die Anschlußkabel und die Isolierung
des Motors bei abgeklemmtem
Umrichter prüfen. Die Transistorenbrücke des Umrichters prüfen

CrF
LADESCHÜTZ

• Störung der Steuerung des Lastrelais
• Lastwiderstand beschädigt

• den Anschluß im Umrichter und den
Lastwiderstand prüfen

SLF
FEHLER RS485

• Fehlerhafter Anschluß am
Terminalstecker des Umrichters

• Anschluß am Terminalstecker des
Umrichters prüfen

166

• Lastwiderstand austauschen

GP_ATV58_DE.fm Page 167 Mardi, 2. avril 2002 6:01 18

Wartung

Angezeigte Störung Wahrscheinliche Ursache

Maßnahme, Behebung

• Motortemperatur zu hoch (PTC-Fühler) • Belüftung des Motors, Umgebungstemperatur und Belastung des Motors
prüfen
• die Art der verwendeten Fühler prüfen

tSF
FEHLER MOTOR-PTC

• Fehlerhafter Anschluß der Fühler am
Umrichter

• den Anschluß der Fühler am Umrichter
prüfen
• die Fühler prüfen

EEF
EEPROM-FEHLER

• Fehler beim Speichern auf EEPROM

• die Spannungsversorgung des
Umrichters unterbrechen und wieder
einschalten

InF
INTERNER FEHLER

• Interne Störung
• Fehlerhafter Anschluß

• den Anschluß im Umrichter prüfen

EPF
EXTERNER FEHLER

• Störung ausgelöst durch ein externes
Gerät

• das Gerät prüfen, das die Störung
verursacht hat u. wieder einschalten

SPF
Überdrehzahl

• Drehzahlrückführung fehlt

• Anschluß und mechanische Ankopplung
des Drehzahlgebers prüfen

AnF
LAST AUSGERISSEN

• Nichteinhaltung der Rampe
• Drehzahl umgekehrt wie Sollwert

• Einstellung und Verkabelung der
Drehzahlrückführung prüfen
• die Eignung der Einstellungen bezogen
auf die Last prüfen
• die Dimensionierung von Motor und
Umrichter sowie die eventuelle Notwendigkeit eines Bremswiderstandes prüfen

SOF
Rückführg fehlt

• Instabilität
• Zu stark antreibende Last

• Einstellungen und Parameter prüfen
• einen Bremswiderstand einbauen
• die Dimensionierung Motor/Umrichter/
Last prüfen

CnF
EXT.KOM.-FEHLER

• Kommunikationsstörung am Feldbus

• den Anschluß des Netzes am Umrichter
prüfen
• Time Out überprüfen

ILF
INT.KOM.-FEHLER

• Kommunikationsstörung zwischen
Optionskarte und Steuerkarte

• den Anschluß der Optionskarte auf der
Steuerkarte prüfen

CFF

Fehler wahrscheinlich beim Austauschen
einer Karte:
• Ändern der Baugröße der Leistungskarte,
• Ändern des Typs der Optionskarte oder
Installation einer Optionskarte, wenn
zuvor keine Karte vorhanden war und die
Makrokonfig. gleich CUS ist,
• Entfernung der Optionskarte,
• Gespeicherte Konfiguration inkohärent.
Bei Drücken auf ENT erscheint die
Meldung: WKSEINST? ENT/ESC

• die Hardware-Konfiguration des
Umrichters prüfen (Leistungskarte,
weitere Karten)
• die Spannungsversorgung des
Umrichters unterbrechen und wieder
einschalten
• die Konfiguration in einer
Konfigurationsdatei der Konsole
speichern
• auf ENT drücken, um zu den
Werkseinstellungen zurückzukehren

FEHL TYP-ERK>ENT
FEHL. OPT->ENT

KEINE OPT->ENT
CHECKSUMF.->ENT

CFI
FEHLER KONFIG.

• Die über die serielle Schnittstelle an
• die zuvor gesendete Konfiguration
den Umrichter gesendete Konfiguration
prüfen
ist inkohärent
• eine kohärente Konfiguration senden

167

DEUTSCH

OtF
ÜBERHITZUNG MOT.

GP_ATV58_DE.fm Page 168 Mardi, 2. avril 2002 6:01 18

Wartung

Bei keiner Funktion, ohne daß eine Störung angezeigt wird
Anzeige

Wahrscheinliche Ursache

Maßnahme, Behebung

Kein Code,
LEDs erloschen

• Keine Spannungsversorgung

• Spannungsversorgung des Umrichters
prüfen

Kein Code,
grüne LED
leuchtet, rote LED
erloschen oder
leuchtet

• Terminal außer Betrieb

• Terminal austauschen

DEUTSCH

rdY
• Umrichter im Online-Modus, mit
grüne LED leuchtet
Kommunikationskarte oder
Anschaltbaugruppe RS 485.
• Einem Eingang LI ist "Freier Auslauf"
oder "Schnellhalt" zugeordnet, und
dieser Eingang ist nicht unter
Spannung.
Diese Anhaltevorgänge werden durch
eine Unterbrechung des Eingangs
gesteuert.

168

• LI4 für Vor-Ort-Betrieb parametrieren
und dies anschließend über LI4
bestätigen.
• Den Eingang mit 24 V verbinden, um
das Anhalten aufzuheben.

GP_ATV58_DE.fm Page 169 Mardi, 2. avril 2002 6:01 18

Merkblatt Konfiguration und Einstellungen

Umrichter Typ ATV58 ............ Anzeige rEF : ....................................... (Menü "Identifikation")
Kundenspezifische Bezeichnung: ........................................................
Optionskarte : Nein y Ja y : Typ .........................................................
Zugriffscode: Nein y Ja y : .................................................................
Konfiguration in der Konf-Datei Nr. ............................ des Bedienterminals
Makrokonfiguration: ..............................................................................
Zur Konfiguration CUS : Sonder , Belegung der Eingänge / Ausgänge:
Basisgerät
LI 1 :
LI 2 :
LI 3 :
LI 4 :
AI 1 :
AI 2 :

Logikeingänge

Analogeingänge
Gebereingang
Relais
Logikausgang
Analogausgang

Optionskarte
LI 5 :
LI 6 :

AI 3 :
AI3 :

R2 :
LO :
AO :

AO1

Menü "Einstellungen":
Werkseinstellg
3s
3s
0 Hz
50/60 Hz
20 %
20 %
je nach Typ
je nach Typ
0,5 s
0,5 ItH
5s
5s
0 Hz
0 Hz
0 Hz
0
1
100 %
100 %
20 %
10 Hz
15 Hz
20 Hz
25 Hz
30 Hz

Kundeneinstellg (1)
s
s
Hz
Hz
%
%
A
A
s
A
s
s
Hz
Hz
Hz
s
%
%
%
Hz
Hz
Hz
Hz
Hz

Code
SP7
JOG
JGt
brL
Ibr
brt
bEn
bEt
FFt
bIP
rPG
rIG
FbS
PIC
dtS
Ctd
ttd
tL2
PSP
PI2
PI3
dtd
Ftd
F2d

Werkseinstellg
35 Hz
10 Hz
0,5 s
0 Hz
0A
0s
0 Hz
0s
50/60 Hz
Nein
1
1/s
1
Nein
1
1,36 In
100 %
200 %
0s
30 %
60 %
105 %
50/60 Hz
50/60 Hz

Kundeneinstellg (1)
Hz
Hz
s
Hz
A
s
Hz
s
Hz

/s

A
%
%
s
%
%
%
Hz
Hz

(1) ”keine” angeben, wenn der Parameter fehlt.
169

DEUTSCH

Code
ACC
dEC
LSP
HSP
FLG
StA
ItH
IdC
tdC
SdC
AC2
dE2
JPF
JF2
JF3
tLS
USC
UFr
SLP
PFL
SP2
SP3
SP4
SP5
SP6

GP_ATV58_DE.fm Page 170 Mardi, 2. avril 2002 6:01 18

Merkblatt Konfiguration und Einstellungen

Menü "Antrieb":
Code
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt

Werkseinstellg
je nach Typ
50/60 Hz
je nach Typ
je nach Typ
je nach Typ
Nein
60/72 Hz
Nein
Nein
Nein
0 Hz
STN

Kundeneinstellg (1)
V
Hz
A
rpm

Hz

Code
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Werkseinstellg
LIN
4
200 %
1,36 In
Ja
1
LF
je nach Typ
Ja
Nein
DET
1024

Kundeneinstellg (1)
Hz

Code
AOH
Str
LCC
PSt
Add
tbr
rPr

Werkseinstellg
20 mA
Nein
Nein
Ja
0
19200
Nein

Kundeneinstellg (1)
mA

Code
LFF
FLr
StP
Sdd
EPL

Werkseinstellg
0 Hz
Nein
Nein
Ja
Ja

Kundeneinstellg (1)
Hz

%
A

kHz

(1) ”keine” angeben, wenn der Parameter fehlt.

DEUTSCH

Menü "Steuerung":
Code
tCC
tCt
rIn
bSP
CrL
CrH
AOL

Werkseinstellg
2W
LEL
Nein
Nein
4 mA
20 mA
0 mA

Kundeneinstellg (1)

mA
mA
mA

(1) ”keine” angeben, wenn der Parameter fehlt.

Menü "Fehlerbehandlung":
Code
Atr
rSt
OPL
IPL
tHt
LFL

Werkseinstellg
Nein
RSP
Ja
Ja
ACL
Nein

Kundeneinstellg (1)

(1) ”keine” angeben, wenn der Parameter fehlt.

170

GP_ATV58_DE.fm Page 171 Mardi, 2. avril 2002 6:01 18

Zusammenfassung der Menüs

Menü "Sprache"
Bezeichnung
English
Français
Deutsch
Español
Italiano

Menü 2 - "Einstellung" (Fortsetzung)
Code
LnG
LnG
LnG
LnG
LnG

Menü "Makrokonfig."
Bezeichnung
Hdg : Fördertech.
GEn : Allg. Anw.
VT : Var. Moment

Code
CFG
CFG
CFG

Menü 1 - "Betrieb"
Code
--FrH
rFr
SPd
LCr
USP
OPr
ULn
tHr
tHd
LFt
LFr
APH
rtH

Menü 2 - "Einstellung"
Bezeichnung
Sollfrequenz
Hochlaufzeit
Auslaufzeit
Hochlaufz. 2
Auslaufz. 2
Kleine Freq.
Große Freq.
Verstärkung
Dämpfung

- Hz
- s
- s
- s
- s
- Hz
- Hz
- %
- %

Code
LFr
ACC
dEC
AC2
dE2
LSP
HSP
FLG
StA

Code
ItH
IdC
tdC
SdC
JPF
JF2
JF3
USC
tLS
UFr
SLP
SP2
SP3
SP4
SP5
SP6
SP7
Ctd
JOG
JGt
tL2
PFL
rPG
rIG
FbS
PIC
brL
Ibr
brt
bEn
bEt
FFt
bIP
dtS
Ftd
F2d
ttd
PSP
PI2
PI3
dtd

DEUTSCH

Bezeichnung
Zustand ATV
Sollfrequenz
Motorfrequ.
Motor-Drehz
Motorstrom
Geschw Masch
Motorleistg
Netzspannung
Motorerwärmg
Erwärmg ATV
Fehlersp.
Sollfrequenz
Energieaufn.
Betriebszeit

Bezeichnung
I Thermisch - A
I DC-Bremsg - A
T DC-Bremsg - s
I DC-Bremsg - A
F-Ausblendg - Hz
F-Ausblendg2 - Hz
F-Ausblendg3 - Hz
Koeff. Masch
T Kleine Fr. - s
IR-Kompens. - %
Schlupfkomp. - %
Vorwahlfreq2 - Hz
Vorwahlfreq3 - Hz
Vorwahlfreq4 - Hz
Vorwahlfreq5 - Hz
Vorwahlfreq6- Hz
Vorwahlfreq7- Hz
Jog-Frequenz- Hz
Jog-Pause
- s
Momentbegr.2- %
U/f-Kennl. - %
P-Anteil PI
I-Anteil PI - /s
Faktor Istw.
Umkehr PI
F-Schwelle - Hz
F Br.-Abfall- Hz
I Br.-Abfall- A
T Br.-Abfall- s
F Bremsanzug- Hz
T Bremsanzug- s
Schw.Ausl.NST- Hz
Bremsstartim
Faktor Tacho
F-Schwelle2 - Hz
I-Schwelle A
T-Schwelle %
PI Filt Ist – s
PI Sollw.2
- %
PI Sollw.3
- %
U.Temperatur

171

GP_ATV58_DE.fm Page 172 Mardi, 2. avril 2002 6:01 18

Zusammenfassung der Menüs

DEUTSCH

Menü 3 - "Antrieb"
Bezeichnung
Ue Motor
- V
Fnenn Motor - Hz
Ie Motor
- A
Nenndrehzahl - rpm
Cos Phi Mot
Motormessung
Max-Frequenz - Hz
Energiespar
Imax=f (fmot)
Anp Auslaufz
F Rampe 2
- Hz
Typ Anhalten
Typ Rampe
K Schn.-halt
Momentbegr. - %
Begr.-Strom A
Auto GS-Br.
Faktor Pmot
Typ F-Takt
Taktfrequenz- kHz
Geräuscharm
Sondermotor
Typ Impulsg
Impulse/Umdr

Menü 5 - "Belegung E/A"
Code
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Menü 4 - "Steuerung"
Bezeichnung
2/3-Draht?
Typ 2-Draht
Nur pos. Sum
SW-Begr./Unterdrück.
Min Wert AI2- mA
Max Wert AI2- mA
Min Wert AO - mA
Max Wert AO - mA
Sollw-Speich
Vor-Ort-St.
Vorrang STOP
Adresse ATV
BdRate RS485
Reset Zähler

172

Code
tCC
tCt
rIn
bSP
CrL
CrH
AOL
AOH
Str
LCC
PSt
Add
tbr
rPr

Bezeichnung
Belegung LI2
Belegung LI3
Belegung LI4
Belegung LI5
Belegung LI6
NO:keine
RV :Linkslauf
RP2:Umsch. Rampe
JOG:Tippbetrieb
+SP:Schneller
-SP:Langsamer
PS2: 2 Festfreq.
PS4: 4 Festfreq.
PS8: 8 Festfreq.
RFC:Umsch. Sollw.
NST:Freier Ausl.
DCI:DC-Bremsung
FST: Schnellhalt
CHP: Umsch Mot.
TL2:Momentbegr.2
FLO:Vor-Ort-Bet.
RST:Fehlerreset
ATN:Motormessung
PAU:PI Aut/Man
PR2:2Sollw. PI
PR4:4Sollw. PI
TLA:Moment-Begr.
EDD:Ext.Fehl
Belegung R2
Belegung LO
NO:keine
RUN: In Betrieb
OCC:Motorschütz
FTA:F-Schwelle
FLA:Große F err.
CTA:I-Schwelle
SRA:F-Soll err.
TSA:T-Schwelle
BLC: Bremslogik
APL:Verl. 4-20 mA
F2A:Freq.-Schw.2 err.
tAd:Temp. Alarm

Code
L12
L13
L14
L15
L16

r2
LO

GP_ATV58_DE.fm Page 173 Mardi, 2. avril 2002 6:01 18

Zusammenfassung der Menüs

Menü 5 - "Belegung E/A" (Fortsetzung) Menü 6 -"Fehlerbeh."
Code
AI2
AI3

AI3

Bezeichnung
Aut Neustart
Fehlerreset
Mot-ph fehlt
Netzph fehlt
Therm Schutz
Verl. 4-20 mA
Vorg.-Frequ.4-20
Einf im Lauf
Gef. Auslauf
Ausreißerk.
Ext. Fehler

Code
Atr
rSt
OPL
IPL
tHt
LFL
LFF
FLr
StP
Sdd
EPL

Menü 7 - "Konf-Datei"
AO

Bezeichnung
Zust Datei
Zust Datei
Zust Datei
Zust Datei
Aktion
Code

1
2
3
4

Code
FI5
F25
F35
F45
FOt
COd

DEUTSCH

Bezeichnung
Belegung AI2
Belegung AI3
NO:keine
FR2:F-Soll. 2
SAI:Sum. Sollw.
PIF:PI-Istwert
PIM:Man.Sollw.PI
SFB:Tacho-Signal
PTC:Motor-PTC
ATL:Momentbegr.
Belegung AI3(Geber)
NO:keine
SAI:Sum. Sollw.
RGI:Istwert Geber
Belegung AO
NO:keine
OCR:Motorstrom
OFR:Mot-frequenz
ORP:Ausg. Rampe
TRQ:Motormoment
STQ:Moment m. Vorz.
ORS:Rampe m. Vorz.
OPS:Sollw. PIPI
OPF:Istwert PI
OPE:Abweichg PI
OPI:Integral PI
OPR:Motorleistg
THR:Motorerwärmg
THD:Erwärmg Umr.

Menü 8 - "Kommunikation"
Siehe die mit der Kommunikationskarte
gelieferte Dokumentation.

Menü 8 - "Applikation"
Siehe die mit der Applikationskarte
gelieferte Dokumentation.

173

GP_ATV58_DE.fm Page 174 Mardi, 2. avril 2002 6:01 18

DEUTSCH

Stichwortverzeichnis

Funktion

Menü

Seite

+/- Drehzahl

Belegung E/A

146-149-152

Adresse serielle Schnittstelle

Steuerung

145

Analogeingang AI2

Steuerung

144

Auslaufzeit

Einstellung - Antrieb

132-140

Autom. Anpassung Auslauframpe

Antrieb

140

Automatischer Wiederanlauf

Fehlerbeh.

161

Begrenzg Zeit bei niedriger Frequenz

Einstellung

133

Bremslogik

Einstellung - Belegung E/A

136-147-148-157-158

DC-Bremsung

Einstellung - Antrieb

133-135-141

Drehmomentbegrenzungen

Einstellung - Antrieb - Belegung E/A

135-137-146-146-148-154

Drehzahlregler mit Encoder

Antrieb - Belegung E/A

142-147-148-156

Drehzahlregler mit Tacho

Einstellung - Belegung E/A

137-147-148-155

Einfangen im Lauf

Fehlerbeh.

162

Energiesparfunktion

Antrieb

139

Frequenzausblendung

Einstellung

133

Geführter Auslauf

Belegung E/A - Fehlerbeh.

146-162

Hochlaufzeit

Einstellung - Antrieb

132-140

Konfigurierbare Ausgänge

Steuerung - Belegung E/A

145-147-148-157-158-159

Konfigurierbare Eingänge

Belegung E/A

146-147-148

Motormessung

Antrieb - Belegung E/A

139-146-154

Motorschütz

Belegung E/A

146-153

Motorumschaltung

Antrieb - Belegung E/A

141-146-154

PI-Regler

Einstellung - Belegung E/A

137-147-148-155

PTC-Fühler

Belegung E/A

147-155

Rampenumschaltung

Einstellung - Antrieb - Belegung E/A

132-140-146-148-151

Reset der Störungen

Belegung E/A - Fehlerbeh.

146-149-154-161

Schrittbetrieb (JOG)

Einstellung - Belegung E/A

135-136-146-148-151

Sollwertspeicherung

Steuerung

145

Sollwertumschaltung

Belegung E/A

147-157

Standardmoment / starkes Moment

Identifizierung (rEF)

129

Steuerung 2 Draht / 3 Draht

Steuerung

143-151

Strombegrenzung

Antrieb

140-141

Taktfrequenz

Antrieb

141

Thermischer Motorschutz

Einstellung - Belegung E/A - Fehlerbeh.

132-138-147-148-162

Vor-Ort-Betrieb

Steuerung - Belegung E/A

146-154

Vorrang Stop

Steuerung

145

Vorwahlfrequenzen

Einstellung - Belegung E/A

134-136-146-148-153

Werkseinstellung / Speichern

Konf-Datei

163

Zugriffscode

Konf-Datei

164

174

GP_ATV58_DE.fm Page 175 Mardi, 2. avril 2002 6:01 18

DEUTSCH
175

GP_ATV58_Page2-ES.fm Page 176 Mardi, 2. avril 2002 6:20 18

Advertencia
Este documento sirve de referencia para la utilización del
Altivar 58 únicamente:
- con el terminal de explotación VW3A58101,
- ocasionalmente, con una tarjeta de extensión de entradas/salidas VW3A58201 o VW3A58202.
Algunos modos, MENÚS y funcionamientos, se pueden
modificar siempre y cuando el variador posea otras opciones. Consulte la documentación relativa a cada una
de dichas opciones.

ESPAÑOL

Desde la aparición del Altivar 58 en el mercado, se han
incorporado nuevas funciones que se contemplan en
este documento. Es posible utilizarlas con los primeros
variadores, aunque, en estos aparatos, pueden faltar algunos de los parámetros que describe el documento.
Para la instalación, conexión, puesta en servicio y manipulación, consulte la guía de explotación del Altivar 58 y
la guía de explotación de la tarjeta de opcional de extensión de entradas/salidas.

176

Indice

Presentación __________________________________________________________________ 178
Consejos prácticos / puesta en servicio mínima _______________________________________ 181
Desbloqueo de menús antes de la programación ______________________________________ 182
Acceso a los menús _____________________________________________________________ 183
Acceso a los menús - Inicio de la programación _______________________________________ 184
Macro-configuraciones ___________________________________________________________ 185
Identificación Variador ___________________________________________________________ 187
Menú Supervisión ______________________________________________________________ 188
Menú ajustes __________________________________________________________________ 190
Menú accionamiento ____________________________________________________________ 197
Menú control __________________________________________________________________ 201
Menú asignación de entradas/salidas _______________________________________________ 204
Funciones de aplicaciones de entradas/salidas configurables ____________________________ 208
Menú defectos _________________________________________________________________ 219
Menú archivo __________________________________________________________________ 221
Menús comunicación y aplicación/asistencia a la explotación/mantenimiento ________________ 223
Mantenimiento _________________________________________________________________ 224
Memorización de configuración y ajustes ____________________________________________ 227
Resumen de menús _____________________________________________________________ 229
Índice ________________________________________________________________________ 232

ESPAÑOL
177

GP_ATV58_ES.fm Page 178 Mardi, 2. avril 2002 6:05 18

Presentación

El terminal de explotación VW3A58101 se entrega con los variadores ATV58••••M2 y ATV58••••N4.
Los variadores ATV58••••••Z se entregan sin terminal. Éste se puede solicitar por separado.

Montaje del terminal en el variador:
Para montar el terminal en un variador ATV58••••••Z, retire, en primer lugar, la trampilla de protección.

POWE
R
FAUL z
T

POWE
R
FAUL z
T

ESC
FWD
REV

ENT
RUN

STOP
RESET

El terminal de explotación se puede conectar y desconectar en tensión. Si el terminal se desconecta mientras
el control del variador es validado por el terminal, entonces el variador se bloquea con fallo SLF.

ESPAÑOL

Montaje remoto del terminal:
Utilice el conjunto de referencia VW3A58103 que incluye 1 cable con conectores y las piezas necesarias para
el montaje en la puerta del armario, así como las instrucciones de montaje.

Señalización en la parte delantera del Altivar
Otros LED: señaliz. de estado con tarjetas opcionales comunicación.

POWER z

LED verde POWER

encendido: Altivar en tensión

FAULT

LED rojo FAULT

• encendido: Altivar en fallo.
• parpadeante: Altivar bloqueado tras pulsar la tecla
"STOP" del terminal o tras un cambio de
configuración. El motor sólo puede ser alimentado
tras la reinicialización previa de las órdenes
"adelante", "atrás", "parada por inyección".

178

GP_ATV58_ES.fm Page 179 Mardi, 2. avril 2002 6:05 18

Presentación
☞ Antes de poner el Altivar en tensión y antes de utilizar el terminal:
Desenclave y abra la tapa del Altivar para acceder al
conmutador de 50/60 Hz 1 situado en la tarjeta de control.
Si se presenta una tarjeta opcional, el conmutador sigue
siendo accesible a través de ésta.
Sitúe el conmutador en posición 50 ó 60 Hz según
corresponda a su motor.
Punto de funcionamiento preajustado:

1
o
50 Hz

60 Hz

Posición 50 Hz (ajuste en fábrica):
- 230 V 50 Hz para ATV 58••••M2
- 400 V 50 Hz para ATV 58••••N4
Posición 60 Hz :
- 230 V 60 Hz para ATV 58••••M2
- 460 V 60 Hz para ATV 58••••N4

El terminal de explotación permite:
- la visualización de la identificación del variador, de magnitudes eléctricas, de parámetros
de explotación o de fallos,
- la toma de ajustes y de configuración del Altivar,
- el control local desde el teclado del terminal,
- la memorización y la llamada de configuración en una memoria no volátil del terminal.

☞ Retorno a los ajustes de fábrica:

179

ESPAÑOL

- apague el variador,
- desenclave y abra la tapa del Altivar para acceder al conmutador 50/60 Hz 1 de la tarjeta de control. Si
existe una tarjeta opcional, el conmutador sigue siendo accesible a través de la misma,
- cambie de posición el conmutador 50/60 Hz 1 de la tarjeta de control,
- conecte el variador,
- apague el variador,
- vuelva a poner el conmutador 50/60 Hz 1 de la tarjeta de control en su posición inicial (frecuencia
nominal del motor), conecte el variador, que recupera su configuración de fábrica.

GP_ATV58_ES.fm Page 180 Mardi, 2. avril 2002 6:05 18

Presentación

Vista de la parte delantera

LOC

PROG

ESC
ENT
FWD
REV

RUN

Utilización de las teclas y significado de los mensajes
 Ú
Piloto parpadeante:
indica el sentido de rotación seleccionado
Piloto fijo:
indica el sentido de rotación del motor
LOC
Indica el modo de CONTROL por la consola
PROG Aparece en modo de puesta servicio y programac.
Piloto parpadeante:
indica la modificación de un valor no memorizado
Pantalla 4 caracteres:
muestra valores numéricos y códigos
Una línea de 16 caracteres:
visualización de mensajes

STOP
RESET

Desplazamiento por los MENÚS o por los parámetros, y ajuste de un valor.
ESC

Retorno al menú anterior, o abandono de un ajuste en curso y retorno al valor original.

ENT

Selección de un menú, validación con memorización de elección o de ajuste.

Si se selecciona el CONTROL desde el terminal:

ESPAÑOL

FWD
REV

RUN
STOP
RESET

Invierte el sentido de rotación.
Orden de inicio de rotación del motor.
Orden de parada del motor o rearranque del fallo. La función "STOP" de la tecla se puede
inhibir en programación (menú "CONTROL").

Vista de la parte posteriory

Conector:
- para conexión directa del terminal al variador
- para utilización a distancia. El terminal se puede conectar
mediante un cable que se suministra con VW3A58103.
Conmutador de bloqueo de acceso :

180

- posición

: Ajuste y configuración no accesibles

- posición

: Ajuste accesible

- posición

: Ajuste y configuración accesibles

GP_ATV58_ES.fm Page 181 Mardi, 2. avril 2002 6:05 18

Consejos prácticos / puesta en servicio mínima

Consejos prácticos:
Prepare su programación haciendo un borrador en las hojas de memorización de configuración y ajustes que
se adjuntan al final de este documento.
La programación del Altivar 58 se ve facilitada por unos selectores y bloqueos internos. Para mayor
comodidad, le recomendamos que acceda a los MENÚS en el siguiente orden. No es obligatorio seguir
todos los pasos para todos los casos.
↓ IDIOMA
MACRO-CONFIG
DENTIFICACIÓN
CONTROL (si CONTROL 3 hilos exclusivamente)
AFECTACIÓN E/S
CONTROL
ACCIONAMIENTO
DEFECTOS
↓ COMUNICACIÓN o APLICACIÓN si se utiliza una tarjeta
AJUSTES
ATENCIÓN: Es necesario asegurarse de que las funciones programadas son compatibles con el
esquema de cableado utilizado. Concretamente, el ATV 58E necesita dicha comprobación en caso
de que se modifique la configuración de fábrica. En caso de necesidad, modifique también el
esquema.

Puesta en servicio mínima:
Este proceso se puede utilizar:
- en las aplicaciones simples en las que el ajuste de fábrica del variador es aproprado,
- en fases de montaje en las que es necesario hacer rotar el motor provisionalmente antes
completamente con la puesta en servicio.

de terminar

Proceso :

2 Asegúrese de que la macro-configuración de fábrica es apropiada y, si no es el caso, modifíquela en el
menú «Macro-config».
3 En el caso de los variadores de potencia superior a 7,5 kW en 200/240 V y 15 kW en 380/500 V para
aplicaciones de "par estándar", configure la potencia por medio del menú «IDENTIFICACIÓN».
4 Compruebe que el esquema de cableado es compatible con la macro-configuración de forma que quede
garantizada la seguridad necesaria y, en caso contrario, modifique el esquema.
5 Compruebe en el menú «ACCIONAMIENTO» que los parámetros de fábrica son compatibles con los
inscritos en la placa del motor y, en caso contrario, modifíquelos.
6 En el menú «ACCIONAMIENTO» realice un Auto Ajuste.
7 Si es necesario ajuste los parámetros del menú «AJUSTES» (rampas, I Térmica, etc...).

181

ESPAÑOL

1 Siga las recomendaciones de la guía de explotación que acompaña al variador, y ajuste el conmutador 50/
60 Hz a la frecuencia nominal del motor.

GP_ATV58_ES.fm Page 182 Mardi, 2. avril 2002 6:05 18

Desbloqueo de menús antes de la programación

Nivel de acceso/Modo de utilización
La posición del conmutador de bloqueo ofrece tres niveles de acceso a los MENÚS en función de el grado de
utilización de la máquina. El acceso a los MENÚS también se puede bloquear mediante un código de acceso
(véase menú ARCHIVO).
Posición
-

Visualización: se utiliza durante las fases de explotación.

Menú IDIOMA: Selecciona el Idioma de diálogo.
Menú MACRO-CONFIG: Visualiza la macro-configuración.
Menú IDENTIFICACIÓN: Visualiza la tensión y la potencia del variador.
Menú SUPERVISIÓN: Visualiza magnitudes eléctricas, la fase de funcionamiento o un fallo.

Posición

Visualización y ajustes: se utiliza durante las fases de puesta en servicio.

- Podrá ejecutar todas las operaciones posibles en el nivel 0.
- Menú AJUSTES: Ajusta el conjunto de los parámetros accesibles del motor en rotación.

ESPAÑOL

Posición

Acceso total: se utiliza durante las fases de programación.

- Podrá ejecutar todas las operaciones posibles en los niveles 0 y 1.
- Menú MACRO-CONFIG: Cambia la macro-configuración.
- Menú IDENTIFICACIÓN: Permite modificar la potencia, en "par estándar" o "alto par", para los calibres
a los que concierne este parámetro.
- Menú ACCIONAMIENTO: Ajusta las prestaciones del conjunto moto-variador.
- Menú CONTROL: Configura el control del variador mediante los borneros, el terminal o la conexión serie
RS485 que se incluye en el equipo.
- Menú AFECTACIÓN E/S: Cambia la asignación de las entradas/salidas.
- Menú DEFECTOS: Configura las protecciones del motor y del variador, y el comportamiento que se debe
seguir en caso de que se produzca algún fallo.
- Menú ARCHIVO: Memoriza, llama configuraciones del variador memorizadas en el terminal, regresa a
los ajustes de fábrica o protege la configuración actual.
- Menú COMUNICACIÓN, si se instala una tarjeta de comunicación: Ajusta los parámetros de un
Protocolo de comunicación.
- Menú APLICACIÓN, si se instala una tarjeta de «aplicación cliente». Consulte la documentación relativa
a dicha tarjeta.

182

GP_ATV58_ES.fm Page 183 Mardi, 2. avril 2002 6:05 18

Acceso a los menús

El número de menús accesibles va en función de la posición del conmutador de bloqueo.
Cada menú consta de diversos parámetros.
Puestas en
tensión siguientes

1ª puesta
en tensión

LnG

LANGUAGE

ESC

CFG

MACRO-CONFIG

rEF

Identificación

0.37 kW 200/240 V

SUP

1-DISPLAY

SEt

2-ADJUST

drC

3-DRIVE

CtL

5-I/O

ESPAÑOL

4-CONTROL

La indicación PROG
se visualiza en
el terminal

I-O
FLt

6-FAULT

FLS

7-FILES

accesible solamente si la
tarjeta «aplicación cliente»
esta instalada

APP

8-APPLICATION

SL

8-COMMUNICATION

accesible solamente si
la tarjeta Protocolo está
instalada

ATENCIÓN: Si se programa previamente un código de acceso, determinados menús pueden hacerse no
modificables e incluso invisibles. En este caso, consulte el apartado titulado “menú ARCHIVO” para introducir
el código de acceso.

183

GP_ATV58_ES.fm Page 184 Mardi, 2. avril 2002 6:05 18

Acceso a los menús - Inicio de la programación

Idioma:
Este menú es accesible independientemente de la posición del conmutador y se puede modificar en parada
o en marcha.
Ejemplo:
ENT

LnG

LnG

LANGUAGE

English

LnG

Italiano

Retorno a la elección
previamente memorizada

Memorización
de la nueva elección

ESC

ENT

ESC

LnG

Italiano

LnG

English

Elección posible: Inglés (ajuste de fábrica), Francés, Alemán, Español, Italiano.

Inicio de la programación:

ESPAÑOL

El inicio es siempre idéntico, con 1 ó 2 niveles:
• 1 nivel: véase el ejemplo “Idioma“ arribaDisminución
• 2 niveles: véase el ejemplo “rampa de Aceleración“ abajo.
ENT

SEt

ENT

ACC

Acceleration

2.ADJUST

3.0

s

Acceleration

Aumento

ESC

s

(o

Disminución)

3.1

Acceleration

ESC

Retorno al valor
precedente

ENT

ESC

3.1

Acceleration

184

s

Memorización
del nuevo
valor

s

3.0

Acceleration

s

GP_ATV58_ES.fm Page 185 Mardi, 2. avril 2002 6:05 18

Macro-configuraciones

Este parámetro se puede visualizar siempre pero sólo se modifica en modo programación (conmutador de
bloqueo en posición
) y en paro, con el variador bloqueado.
Permite realizar la configuración automática de una tarea. Hay tres tareas disponibles.
- Manutención (Hdg)
- Par variable para las aplicaciones de bombas y ventiladores (VT)
- Uso general (GEn)
Una macro-configuración asigna automáticamente entradas/salidas y parámetros, poniendo, de este modo,
en servicio las funciones que necesita la aplicación. Los parámetros vinculados a las funciones programadas
están disponibles.
Ajuste de fábrica: Manutención
Variador:
Asignaciones de entradas/salidas en función de la macro-configuración

Hdg: Manutención

GEn: Uso General

VT: Par Variable

Entrada lógica LI1

giro adelante

giro adelante

giro adelante

Entrada lógica LI2

giro atrás

giro atrás

giro atrás

Entrada lógica LI3

2 velocidades presel.

marcha paso a paso

conmutación referencia

Entrada lógica LI4

4 velocidades presel.

parada libre (1)

frenado por inyección

Entrada ana. AI1

ref. sumadora

ref. sumadora

ref. velocidad 1

Entrada ana. AI2

ref. sumadora

ref. sumadora

ref. velocidad 2

Relé R1

fallo variador

fallo variador

fallo variador

Relé R2

contr. contact. ag. abajo

est. térmico mot. alcan.

consigna frec. alcan.

Salida ana. AO1

frecuencia motor

frecuencia motor

frecuencia motor

Tarjetas de extensión:

Hdg: Manutención

GEn: Uso General

Entrada lógica LI5

8 velocidades presel.

borrado fallo

VT: Par Variable
parada libre (1)

Entrada lógica LI6

borrado fallo

limitación de par

conmutación de rampa

Entrada ana. AI3
o
Entradas A, A+, B, B+

ref. sumadora

ref. sumadora

retorno regulador PI (2)

retorno velocidad

retorno velocidad

retorno velocidad

Salida lógica LO

umbral corriente alcan.

contr. contact. ag. abajo

máx. veloc. alcan.

Salida ana. AO

corriente motor

corriente motor

corriente motor

(1) Para arrancar, la entrada lógica debe estar conectada a +24 V (función activa a 0).
(2) Desasigne AI3 si el retorno PI no está cableado.
ATENCIÓN: Asegúrese de que la macro-configuración programada es compatible con el
esquema de cableado utilizado. Concretamente, el ATV 58E suministrado necesita esta
comprobación si se modifica la configuración de fábrica. En caso de necesidad, modifique también
el esquema.

185

ESPAÑOL

Asignaciones de entradas/salidas en función de la macro-configuración

GP_ATV58_ES.fm Page 186 Mardi, 2. avril 2002 6:05 18

Macro-configuraciones

La modificación de la macro-configuración necesita una doble confirmación, ya que ésta implica las
asignaciones automáticas de las funciones y la recuperación de los ajustes de fábrica. Aparece la
siguiente pantalla:

CHG

CABLEADO OK?

ENT

ENT para validar la modificación
ESC para retornar a la configuración anterior

Personalización de la configuración:
La configuración del variador se puede personalizar cambiando la asignación de las entradas/salidas en el
menú AFECTACIÓN E/S accesible en modo programación (conmutador de bloqueo en posición
).
Dicha personalización hace que varíe el valor de la macro-configuración visualizada:
visualización de

CFG

ESPAÑOL

CUS:Personalizar

186

GP_ATV58_ES.fm Page 187 Mardi, 2. avril 2002 6:05 18

Identificación Variador

Identificación Variador
Este parámetro se puede visualizar siempre. Indica la potencia y la tensión del variador que aparecen
marcadas en la etiqueta de identificación.

rEF

La potencia se visualiza en kW si el conmutador de 50/60 Hz del
variador se encuentra en la posición de 50 Hz, y en HP, si se encuentra
en la posición de 60 Hz.

0.37 kW 200/240 V

Variadores de potencia superior a 7,5 kW en 200/240 V y 15 kW en 380/500 V:
Su potencia varía si la aplicación es de par estándar o de alto par. Los variadores se suministran con la
configuración de fábrica de "alto par". La configuración de "par estándar" puede obtenerse de la siguiente
manera:

ENT rEF Intermitente
22 kW

rEF

22 kW

380/500 V

rEF Intermitente

rEF
380/500 V

+30 kW

rEF
380/500 V

o ESC

ESC

ENT

+30 kW

rEF
380/500 V

+30 kW

rEF
380/500 V

ESC

En la aplicación de "par estándar", el signo + precede a la potencia en kW.
La recuperación de la configuración de "alto par" se realiza mediante el mismo proceso.
La configuración de "par estándar" o "alto par" preconfigura los "ajustes de fábrica" de ciertos parámetros:

Por tanto, el cambio de una configuración de par a otra implica la recuperación de los ajustes
de fábrica de todos sus parámetros.

187

ESPAÑOL

• menú accionamiento: UnS, nCr, nSP, COS, tUn
• menú ajustes: ItH, IdC.

GP_ATV58_ES.fm Page 188 Mardi, 2. avril 2002 6:05 18

Menú Supervisión

Menú supervisión (elección del parámetro visualizado en funcionamiento)
Los siguientes parámetros son accesibles independientemente de la posición del conmutador, ya se
encuentre parado o en marcha.

Unidad

Cód.

Función

--rdY
rUn
ACC
dEC
CLI
dCb
nSt
Obr

Estado var.
–
Estado del variador : indica un fallo o la fase de funcionamiento del motor:
rdY = variador listo,
rUn = motor en régimen establecido u orden de marcha presente y referencia nula,
ACC = en Aceleración,
dEC = en Deceleración,
CLI = en limitación de corriente,
dCb = en frenado por inyección,
nSt = en CONTROL de parada libre,
Obr = frenado adaptando la rampa de Deceleración (véase el menú “accionamiento“).

FrH

Ref. Frec.

Hz

Referencia frecuencia

rFr

Frec. Salida

Hz

Frecuencia de salida aplicada al motor

SPd

Veloc. Motor

rpm

Velocidad del motor estimada por el variador

LCr

Int. Motor

USP

Vel accion

A

Corriente del motor
–

ESPAÑOL

Velocidad de la máquina estimada por el variador. Es proporcional a rFr, según un coeficiente USC
ajustable desde el menú ajustes.
Permite visualizar un valor que corresponda a la aplicación (por ejemplo, metros/segundo).
Atención, si USP es superior a 9999, el valor visualizado se divide por 1000.

OPr

Pot. salida

%

Potencia suministrada por el motor, estimada por el variador.
100% corresponde a la potencia nominal.

ULn

Tensión red

V

Tensión de la red

tHr

Themp. Motor

%

Est. térmico: 100% corresponde al estado térmico nominal del motor. Por encima del 118%, el
variador se desconecta en fallo OLF (Sobrecarga Motor)

tHd

Themp. Var.

%

Est. térmico del variador: 100% corresponde al estado térmico nominal del variador. Por encima del
118%, el variador se desconecta en fallo OHF (sobretemp. variador). Se puede volver a conectar
por debajo del 70%.

LFt

Ultimo fallo
Visualiza el último fallo aparecido.

188

–

GP_ATV58_ES.fm Page 189 Mardi, 2. avril 2002 6:05 18

Menú Supervisión

Cód.

Función

Unidad

LFr

Ref. Frec.

Hz

Este parámetro de ajuste aparece en lugar del parámetro FrH cuando el CONTROL del variador por
la consola está activo:
parámetro LCC del menú CONTROL.

APH

Consumo

Wh o MWh

Energía consumidakWh o MWh

rtH

Tiempo marcha

h

Tiempo de funcionamiento continuo (motor en tensión), en horas.

ESPAÑOL
189

GP_ATV58_ES.fm Page 190 Mardi, 2. avril 2002 6:05 18

Menú ajustes

Este menú es accesible en las posiciones
y
del conmutador. La modificación de los
parámetros de ajuste se puede realizar en paro o en funcionamiento. Asegúrese de que los cambios
durante el funcionamiento no son peligrosos; realícelos preferentemente en paro.
La lista de parámetros de ajuste consta de una parte fija y de otra variable que varía en función:
- de la macro-configuración elegida
- de la presencia o no de una tarjeta extensión de entradas/salidas
- de reasignaciones de las entradas/salidas
Los siguientes parámetros son accesibles en todas las macro-configuraciones.
Cód.

Descripción

LFr

Ref. Fre c.

- Hz

Rango de ajuste

Ajuste de fábrica

LSP a HSP

–

Aparece cuando el control del variador desde el terminal se activa: parámetro LCC del menú control

ACC
dEC

Aceleración - s
Deceleración - s

0,05 a 999,9
0,05 a 999,9

3s
3s

Tiempo de rampas de Aceleración y de Deceleración
Definidos para pasar de 0 a la frecuencia nominal del motor (FrS)

AC2
dE2

Aceleración2 - s
Decelerac2
- s

0,05 a 999,9
0,05 a 999,9

5s
5s

2º tiempo de la rampa de Aceleración
2º tiempo de la rampa de Deceleración
Estos parámetros son accesibles si el umbral de conmutación de rampa (parámetro Frt) es distinto
de 0 Hz o si se asigna una entrada lógica a la conmutación de rampa.

LSP

Veloc.Mínima- Hz

0 a HSP

0 Hz

LSP a tFr

50 / 60 Hz en función del
conmutador

Mínima velocidad

HSP

Veloc.Máxima- Hz

Máxima velocidad: asegúrese de que este ajuste conviene al motor y a la aplicación.

ESPAÑOL

FLG

Ganancia

- %

0 a 100

20

Ganancia de bucle frecuencia: permite adaptar la rapidez de los transitorios de velocidad de la
máquina en función de la cinemática.
Para máquinas con fuerte par resistente o inercia considerable a ciclos rápidos, aumente
progresivamente la Ganancia.

StA

Estabilidad

- %

0 a 100

20

Permite adaptar la espera del régimen establecido tras un transitorio de velocidad en función de la
cinemática de la máquina.
Aumente progresivamente la Estabilidad para eliminar los excesos de velocidad.

ItH

I Térmica

- A

0,25 a 1,36 In (1)

Según calibre variador

Corriente utilizada para la protección térmica del motor. Ajuste ItH a la intensidad nominal que figura
en la placa de características del motor.
(1) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de alto par.

190

GP_ATV58_ES.fm Page 191 Mardi, 2. avril 2002 6:05 18

Menú ajustes

Cód.

Descripción

tdC

I Inyecc

- s

Rango de ajuste

Ajuste de fábrica

0 a 30 s Cont

0,5 s

Tiempo de frenado por inyección de corriente continua.
Si se aumenta por encima de 30 s, se visualiza "Cont", Inyección de corriente permanente.
La corriente de inyección se equipara a SdC al cabo de 30 segundos.

SdC

Icc en pared - A

0,1 a 1,36 In (1)

Según calibre variador

Intensidad de la corriente de frenado por inyección que se aplica al cabo de 30 segundos si
tdC = Cont.
Compruebe que el motor admite esta corriente sin exceso de calentamiento.

JPF

Frec. Oculta.-Hz

0 a HSP

0 Hz

Frecuencia oculta: se prohibe un funcionamiento prolongado en un rango de frecuencia de +/2,5 Hz alrededor de JPF. Esta función permite eliminar una velocidad crítica que provoque una
resonancia.

JF2

Frec.Ocult2 - Hz

0 a HSP

0 Hz

2ª frecuencia oculta: misma función que JPF, para un 2º valor de frecuencia.

JF3

Frec.Ocult3 - Hz

0 a HSP

0 Hz

3ª frecuencia oculta: misma función que JPF, para un 3er valor de frecuencia.

USC

Coef.accion

0,01 a 100

1

Coeficiente que se aplica al parámetro rFr (frecuencia de salida que se aplica al motor) permite
visualizar la velocidad de la máquina por medio del parámetro USP
USP = rFr x USC

tLS

Temp.Vel.Mín - s

0 a 999.9

0 (sin limitación de tiempo)

(1) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de alto par.

191

ESPAÑOL

Tiempo de funcionamiento a mín. velocidad.
Sigue a un funcionamiento en LSP durante el tiempo definido, la parada del motor se solicita
automáticamente. El motor arranca si la referencia de frecuencia es superior a LSP y si siempre
hay una orden de marcha presente.
Atención, el valor 0 corresponde a un tiempo no limitado

GP_ATV58_ES.fm Page 192 Mardi, 2. avril 2002 6:05 18

Menú ajustes

Los siguientes parámetros son accesibles en la macro-configuración ‘manutención’
Cód.

Descripción

UFr

Comp. RI

- %

Rango de ajuste

Ajuste de fábrica

0 a 150% ó 0 a 800%

100%

Permite ajustar el valor por defecto o tomado durante el Auto Ajuste.
El rango de ajuste llega al 800% si el parámetro SPC (M.especiales) del menú accionamiento es
“Sí”.

SLP

Comp.Desliza - %

0 a 150%

100%

Permite ajustar la compensación de deslizamiento alrededor del valor fijado por la velocidad
nominal del motor.

SP2

Vel.Presel.2- Hz

LSP a HSP

10 Hz

LSP a HSP

15 Hz

LSP a HSP

20 Hz

LSP a HSP

25 Hz

LSP a HSP

30 Hz

LSP a HSP

35 Hz

0 a 1.36 In (1)

1.36 In (1)

2 ª velocidad preseleccionada

SP3

Vel.Presel.3- Hz
3ª velocidad preseleccionada

SP4

Vel.Presel.4- Hz
4ª velocidad preseleccionada

SP5

Vel.Presel.5- Hz
5ª velocidad preseleccionada

SP6

Vel.Presel.6- Hz
6ª velocidad preseleccionada

SP7

Vel.Presel.7- Hz
7ª velocidad preseleccionada

Ctd

Int.Alcanza

- A

ESPAÑOL

Umbral de corriente por el que la salida lógica, o el relé, pasa al estado 1
(1) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de "alto par".

192

GP_ATV58_ES.fm Page 193 Mardi, 2. avril 2002 6:05 18

Menú ajustes

Los siguientes parámetros son accesibles en macro-configuración "uso general"
Cód.

UFr

Descripción

Comp. RI

- %

Rango de ajuste

Ajuste de fábrica

0 a 150% ó 0 a 800%

100%

Permite ajustar el valor por defecto o tomado durante el Auto Ajuste.
El rango de ajuste llega al 800% si el parámetro SPC (M.especiales) del menú accionamiento es
“Sí”.

SLP

Comp.Desliza - %

0 a 150%

100%

Permite ajustar la compensación de deslizamiento alrededor del valor fijado por la velocidad
nominal del motor.

JOG

Jog (Hz)

- Hz

0 a 10 Hz

10 Hz

Frecuencia de funcionamiento en marcha paso a paso.

JGt

Tempo JOG

- s

0a2s

0.5 s

Tiempo de inhabilitación del orden de marcha entre dos marchas paso a paso consecutivas

tL2

Limit. par 2 - %

0 a 200% (1)

200%

Segundo nivel de limitación de par activado por una entrada lógica.

Los siguientes parámetros son accesibles en macro-configuración "par variable"
Cód. Descripción
IdC I Inyecc

- A

Rango de ajuste

Ajuste de fábrica

0,10 a 1,36 In (2)

Según calibre variador

Intensidad de la corriente de frenado por inyección de corriente continua.
Al cabo de 30 segundos, la cresta de la corriente de inyección se limita a 0,5 Ith si su ajuste es
superior.

PFL

Perfil U/f

- %

0 a 100%

20%

Permite ajustar el perfil cuadrático cuando la función economía de energía se inhibe.

Los parámetros sombreados aparecen si se instala una tarjeta de extensión de E/S.

193

ESPAÑOL

(1) 100% corresponde al par nominal de un motor de una potencia igual a la asociada a un variador para
aplicaciones de alto par.
(2) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de "alto par".

GP_ATV58_ES.fm Page 194 Mardi, 2. avril 2002 6:05 18

Menú ajustes

Los siguientes parámetros pueden ser accesibles después de reasignar entradas/salidas del producto básico.
Cód.

Descripción

Rango de ajuste

Ajuste de fábrica

AC2

Aceleración 2- s

0.05 a 999.9

5s

2º tiempo de la rampa de aceleración

dE2

Decelerac 2

- s

0.05 a 999.9

5s

2º tiempo de la rampa de deceleración
Estos parámetros son accesibles si el umbral de conmutación de rampa (parámetro Frt) es distinto
de 0 Hz o si se asigna una entrada lógica a la conmutación de rampa.

IdC

I Inyecc

- A

0,10 a 1,36 In (1)

Según calibre variador

Intensidad de la corriente de frenado por inyección de corriente continua
Este parámetro es accesible si se asigna una entrada lógica a la parada por inyección de corriente.
Al cabo de 30 segundos, la cresta de la corriente de inyección se limita a 0,5 Ith si su ajuste es
superior.

SP2

Vel.Presel.2- Hz

LSP a HSP

10 Hz

LSP a HSP

15 Hz

LSP a HSP

20 Hz

LSP a HSP

25 Hz

LSP a HSP

30 Hz

LSP a HSP

35 Hz

0 a 10 Hz

10 Hz

2ª velocidad preseleccionada

SP3

Vel.Presel.3- Hz
3ª velocidad preseleccionada

SP4

Vel.Presel.4- Hz
4ª velocidad preseleccionada

SP5

Vel.Presel.5- Hz
5ª velocidad preseleccionada

SP6

Vel.Presel.6- Hz
6ª velocidad preseleccionada

ESPAÑOL

SP7

Vel.Presel.7- Hz
7ª velocidad preseleccionada

JOG

Jog (Hz)

- Hz

Frecuencia de funcionamiento en marcha paso a paso

JGt

Tempo JOG

- s

0a2s

0,5 s

Tiempo de inhabilitación de orden de marcha entre dos marchas paso a paso consecutivas

brL

AperFren(Hz)- Hz

0 a 10 Hz

0 Hz

0 a 1,36 In(1)

0A

0a5s

0s

0 a LSP

0 Hz

0a5s

0s

Frecuencia de apertura de freno

Ibr

AperFren(I)

- A

Corriente de apertura de freno

brt

AperFren(t)

- s

Tiempo de apertura de freno

bEn

CierFren(Hz)- Hz
Frecuencia de cierre del freno

bEt

CierFren(t) - Hz
Tiempo de cierre del freno

(1) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de "alto par".
194

GP_ATV58_ES.fm Page 195 Mardi, 2. avril 2002 6:05 18

Menú ajustes

Cód.

FFt

Descripción

Rango de ajuste

Ajuste de fábrica

UmbralActivNST-Hz

0 a HSP

0 Hz

Umbral de activación de parada de la ruedalibre: por solicitud de parada en rampa o de parada rápida,
el tipo de parada seleccionado se activa hasta que la velocidad desciende por debajo de este umbral.
Por debajo del umbral, la parada de la rueda libre se activa. Es posible acceder a este parámetro si el
relé R2 no está asignado a la función BLC: lógica de freno, y si el tipo de parada está en "rampa" o
"rápida" en el menú accionamiento.

bIP

Imp. Aper. Fre

no-SÍ

no

Impulso de apertura de freno
SÍ : el par durante la apuertura del freno siempre es en sentido FW (adelante) con independencia
del sentido solicitado.
Compruebe que el sentido del par motor en control FW (adelante) corresponde con el sentido
de subida de la carga; si es necessario, invierta las dos fases del motor.
no : durante la apuerta del freno, el par corresponde con el sentido de rotación solicitado.

dtS

Coef.Ret.DT

1a2

1

Coeficiente multiplicador de retorno asociado a la función dinamo tacométrica:
dtS =

rPG

9
tensión dinamo velocidad máx. HSP

Gan.Prop(PI)

0.01 a 100

1

Ganancia proporcional del regulador PI

rIG

Gan.Int (PI)

0.01 a 100 /s

1/s

Ganancia integral del regulador PI

FbS

Coef.Ret PI

1 a 100

1

Coeficiente multiplicador de retorno PI

PIC

PI inverso

No - Sí

No

ESPAÑOL

Inversión del sentido de corrección del regulador PI
No : normal
Sí : inverso

Ftd

Frec Alcanza- Hz

LSP a HSP

50/60 Hz

Umbral de frecuencia del motor por encima del cual la salida lógica pasa a 1

F2d

Det.Frec.2

- Hz

LSP a HSP

50/60 Hz

2ª umbral de frecuencia: misma función que Ftd, para un 2ª valor de frecuencia

Ctd

Int.Alcanza

- A

0 a 1,36 In (1)

1,36 In (1)

Umbral de corriente por encima del cual la salida lógica o el relé pasa a estado 1

ttd

Temp.Alcanza - %

0 a 118%

100%

Umbral del estado térmico del motor por encima del cual la salida lógica o el relé pasa al estado 1

tL2

Limit. par 2 - %

0 a 200% (2)

200%

Segundo nivel de limitación de par activado por una entrada lógica
(1) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de "alto par".
(2) 100% corresponde al par nominal de un motor de una potencia igual a la asociada al variador para
aplicaciones de "alto par".
Los parámetros sombreados aparecen si se instala una tarjeta de extensión de E/S.
195

GP_ATV58_ES.fm Page 196 Mardi, 2. avril 2002 6:05 18

Menú ajustes

Cód.

Descripción

PSP

Filtro PI

- s

Rango de ajuste

Ajuste de fábrica

0,0 a 10,0

0s

Permite de ajustar la constante de tiempo del filtro del retorno PI

PI2

2 cons. PI

- %

0 a 100 %

30 %

2ª consigna preseleccionada del PI, cuando una entrada lógica a sido afectada a la función de 4
consignas de PI preseleccionadas.
100 % = máx. proceso
0 % = mín. proceso

PI3

3 cons. PI

- %

0 a 100 %

60 %

3ª consigna preseleccionada del PI, cuando una entrada lógica a sido afectada a la función de 4
consignas de PI preseleccionadas.
100 % = máx. proceso
0 % = mín. proceso

dtd

Umb. Tér. var.

0 a 118 %

105 %

ESPAÑOL

Nivel del estado térmico variador a partir del cual la salida lógica o el relé pasa a 1.

196

GP_ATV58_ES.fm Page 197 Mardi, 2. avril 2002 6:05 18

Menú accionamiento

Este menú es accesible en posición
del conmutador.
Los parámetros sólo se pueden modificar en parada, con el variador bloqueado.
La optimización de las prestaciones de accionamiento se obtiene:
- introduciendo en el menú accionamiento los valores de la placa descriptiva,
- ejecutando un Auto Ajuste (en un motor asíncrono estándar).
En caso de uso de motores especiales (motores en paralelo, motores de freno con rotor cónico o derivación
de flujo, motores síncronos o asíncronos, motores asíncronos con rotor resistente):
- Seleccione la macro-configuración “Hdg : Manutención” o la macro-configuración “GEn : Uso General”
- Configure, en el menú accionamiento, el parámetro M.especiales “SPC” en “Sí”
- Ajuste, en el menú ajuste, el parámetro Comp. RI “UFr” para obtener un funcionamiento satisfactorio.
Cód.

Descripción

Rango de ajuste

Ajuste de fábrica

UnS

U Nom. Motor - V

200 a 240 V
200 a 500 V

230 V (2)
400/460V (2)

Tensión nominal del motor que marca la placa descriptiva
El rango de ajuste depende del modelo de variador:
ATV58••••M2
ATV58••••N4

FrS

F Nom.Motor - Hz

10 a 500 Hz

50/60Hz (2)

Frecuencia nominal del motor que marca la placa descriptiva

nCr

I Nom. Motor - A

0,25 a 1,36 In (1)

según calibre variador

Corriente nominal del motor que marca la placa descriptiva

nSP

Vel.NomMotor-rpm

0 a 9999 rpm

según calibre variador

Velocidad nominal del motor que marca la placa descriptiva

COS

CosPhiMot

0,5 a 1

según calibre variador

Coseno Fi del motor que marca la placa descriptiva

tUn

Auto Ajuste

No - Sí

No

tFr

Frec.Máxima - Hz

10 a 500 Hz

60/72 Hz (2)

Frecuencia máxima de salida.
El valor máx. va en función de la frecuencia de corte
Ver parámetro SFR (menú accionamiento)

nLd

Eco Energía

No-Sí

Sí

Optimiza el rendimiento del motor.
Accesible solamente en macro-configuración par variable
(1) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de "alto par".
(2) según posición del conmutador 50/60 Hz.

197

ESPAÑOL

Permite realizar un Auto Ajuste del CONTROL del motor después de posicionar este parámetro en
“Sí”. Una vez en Auto Ajuste hecho el parámetro pasa automáticamente a “hecho”, o “no“ en caso
de fallo.
Atención: el autoajuste sólo se lleva a cabo si no se acciona ningún control. Si se asigna una función
de "parada en rueda libre" o "parada rápida" a una entrada lógica, es necesario poner dicha entrada
a 1 (activa a 0).

GP_ATV58_ES.fm Page 198 Mardi, 2. avril 2002 6:05 18

Menú accionamiento

Cód.

Descripción

Rango de ajuste

Ajuste de fábrica

Fdb

Adapt. lim I

No-Sí

No

Adaptación de la corriente de limitación en función de la frecuencia de salida.
Este parámetro sólo aparece en la macro-configuración de "par variable" VT (aplicaciones de
ventilación en las que la curva de carga evoluciona en función de la densidad del gas).

brA

AdaptRampDec

No-Sí

No

La activación de esta función permite aumentar automáticamente el tiempo de deceleración, si éste
se ha ajustado con un valor demasiado bajo considerando la inercia de la carga y evitando, así, el
paso a fallo ObF. Esta función puede ser incompatible con un posicionamiento en rampa y con la
utilización de una resistencia de frenado.
El ajuste en fábrica depende de la macro-configuración utilizada: no en manutención, Sí para par
variable y uso general.
Si el relé R2 se asigna a la función lógica de freno, el parámetro brA permanece bloqueado en no.

Frt

F.ConmRamp2 - Hz

0 a HSP

0 Hz

Frecuencia de comunicación de rampa.
Cuando la frecuencia de salida llega a ser superior a Frt, los tiempos de rampa que se tienen en
cuenta son AC2 y dE2.

Stt

Tipo de parada

STN - FST - NST - DCI

STN

Tipo de parada.
Mediante solicitud de parada, el tipo de parada se activa hasta el umbral FFt (menú Ajustes).
Por debajo del umbral, la parada se realiza en rueda libre.
STN: en rampa
FST: parada rápida
NST: parada en rueda libre
DCI: parada por inyección de corriente continua.
No es posible acceder a este parámetro si el relé R2 está asignado a la función BLC: lógica de
freno.

rPt

Tipo Rampa

LIN - S - U

LIN

ESPAÑOL

Define la altura de las rampas de aceleración y de Deceleración.
LIN : lineal S : en S U : en U
f (Hz)

f (Hz)

GV

GV

El coeficiente de redondeo es fijo,
t2 = 0,6 x t1
t1 = tiempo de rampa ajustado.

Rampas en S
0

t

t2

0

t

t2

t1

t1

f (Hz)

f (Hz)

GV

GV

El coeficiente de redondeo es fijo,
t2 = 0,5 x t1
t1 = tiempo de rampa ajustado.

Rampas en U

0
t2

t

t1

dCF

Reducir Dec.

0
t2

t

t1

1 a 10

4

Coeficiente de reducción del tiempo de rampa de deceleración cuando se activa la función parada
rápida.

198

GP_ATV58_ES.fm Page 199 Mardi, 2. avril 2002 6:05 18

Menú accionamiento

Cód.

Descripción

tLI

Limit. par

_ %

Rango de ajuste

Ajuste de fábrica

0 a 200% (1)

200%

La limitación de par permite limitar el par máximo del motor.

CLI

Lim.Corr.Int - A

0 a 1,36 In (2)

1,36 In

La limitación de corriente permite limitar el calentamiento del motor.

AdC

Iny CC Autom

No - Sí

Sí

Permite desactivar el frenado por inyección de corriente automáticamente en la parada.

PCC

Reducir Pot.

0,2 a 1

1

Define la relación entre la potencia nominal del variador y el motor de menor potencia cuando se
asigna una entrada lógica a la función de conmutación de motores.
Tipo
Modulado
SFt
LF-HF1-HF2
LF
Permite seleccionar una frecuencia de corte de baja (LF) o alta frecuencia (HF1 o HF2). El tipo de
corte HF1 se destina a las APLICACIONES con factor débil de marcha sin desclasificación del
variador. Si el estado térmico del variador supera el 95 %, la frecuencia pasa automáticamente a
2 ó 4 kHz según calibre variador. Cuando el estado térmico del variador desciende al 70%, la
frecuencia de corte elegida se restablece. El tipo de HF2 se destina a las APLICACIONES con
factor fuerte de marcha con desclasificación del variador de un calibre: los parámetros de
accionamiento se ponen automáticamente a escala (limitación de par, corriente térmica...).
La modificación de este parámetro implica la recuperación de los ajustes de fábrica
de los siguientes parámetros:
• nCr, CLI, Sfr, nrd (menú Accionamiento)
• ItH, IdC, Ibr, Ctd (menú Ajustes).

SFr

Frec. Corte -kHz

0,5-1-2-4-8-12-16 kHz

según calibre variador

Permite seleccionar la frecuencia de corte. El rango de ajuste depende del parámetro SFt.
Si SFt = LF : 0,5 a 2 ó 4 kHz según calibre variador
Si SFt = HF1 o HF2 : 2 ó 4 a 16 kHz según calibre variador
La frecuencia máxima de funcionamiento (tFr) se limita según la frecuencia de corte:

nrd

Reducc.ruido

0.5
62

1
125

2
250
No - Sí

4
500

8
500

12
500

ESPAÑOL

SFr(kHz)
tFr (Hz)

16
500

(3)

Esta función modula de forma aleatoria la frecuencia de corte para reducir el ruido del motor.

SPC

M.especiales

No-Sí-PSM

No

Esta función, cuando está en "Sí", amplía el rango de ajuste del parámetro UFr del menú ajuste
para permitir la adaptación de los motores especiales mencionados al inicio del capítulo. Accesible
sólo en las macro-configuraciones "Manutención" y "Uso general".
Para PSM: inhibe la detección de Perdida Fase Motor "OPF" (especialmente útil para motores
pequeños).
No: motor normal
Sí: motor especial
PSM: motor pequeño
(1) 100% corresponde al par nominal de un motor de potencia igual a la asociada al variador para aplicaciones
de "alto par".
(2) In corresponde a la corriente nominal del variador que se indica en el catálogo y en la etiqueta descriptiva
del variador para aplicaciones de "alto par".
(3) Sí si SFt = LF, No si SFt = HF1 o HF2

199

GP_ATV58_ES.fm Page 200 Mardi, 2. avril 2002 6:05 18

Menú accionamiento

Cód.

Descripción

Rango de ajuste

Ajuste de fábrica

PGt

Tipo encoder

INC-DET

DET

Define el tipo de sensor utilizado al instalar una tarjeta E/S de retorno del encoder:
INC: encoder Incremental (A, A+, B, B+ están cableados)
DET: Detector (sólo A está cableado)

PLS

No Pulsos

1 a 1024

1024

Define el número de pulsos por vuelta del sensor.

ESPAÑOL

Los parámetros sombreados aparecen si se instala una tarjeta de extensión de E/S.

200

GP_ATV58_ES.fm Page 201 Mardi, 2. avril 2002 6:05 18

Menú control

Este menú es accesible en posición
con el variador bloqueado.

del conmutador. Los parámetros sólo se pueden modificar en paro,

Cód.

Descripción

Rango de ajuste

Ajuste de fábrica

tCC

Conf. Bornero

2W- 3W (2 hilos-3 hilos)

2W

Configuración del control bornero: control 2 hilos ó 3 hilos.
La modificación de este parámetro necesita una confirmac. doble ya que conlleva una
reasignación de las entradas lógicas. Entre el control 2 hilos y el control 3 hilos, las
asignaciones de las entradas lógicas se desplazan una entrada. La asig. de LI3 2 hilos se
transforma en la asignación de LI4 en control 3 hilos. En control 3 hilos, las entradas LI1 y LI2 no
son reasignables.
E/S

Manutención

Uso general

LI1

STOP

STOP

Par variable
STOP

LI2

RUN giro adelante

RUN giro adelante

RUN giro adelante

LI3

RUN Giro Atrás

RUN Giro Atrás

RUN Giro Atrás

LI4

2 veloc. presel.

marcha paso a paso

Conmut. de ref.

LI5

4 veloc. presel.

parada libre

frenado por inyección

LI6

8 veloc. presel.

borrado fallos

parada libre

Las entradas/salidas sombreadas son accesibles si se instala una tarjeta de extensión de E/S.
control 3 hilos (control por pulsos: basta un pulso para el control del arranque). Esta elección inhibe
la función "arranque automático"
Ejemplo de cableado :
Bornero control ATV58
LI1 : stop
24 V LI1 LI2 LIx
LI2 : adelante
LIx : atrás

ESPAÑOL

Esta elección sólo aparece si se configura el CONTROL de 2 hilos.
Cód.

tCt

Descripción

Rango de ajuste

Ajuste de fábrica

Tipo 2 hilos

LEL-TRN-PFo

LEL

Define el tipo de CONTROL 2 hilos:
- función del estado de las entradas lógicas (LEL: Nivel)
- función de un cambio de estado de las entradas lógicas (TRN: Flanco)
- función del estado de las entradas lógicas con giro adelante siempre prioritario sobre el giro
atrás (PFo: Prior.FW)
Ejemplo de cableado :
Bornero control ATV58
LI1 : giro adelante
24 V LI1 LIx
LIx : giro atrás

Los parámetros sombreados aparecen si se instala una tarjeta de extensión de E/S.

201

GP_ATV58_ES.fm Page 202 Mardi, 2. avril 2002 9:33 21

Menú control

Cód.

Descripción

Rango de ajuste

Ajuste de fábrica

rln

Inhibic. RV

No - Sí

No

• Inhibición de la marcha en sentido inverso al controlado por las entradas lógicas, aunque la
inversión corresponda a una petición de una función sumadora o de regulación.
• Inhibición de la marcha atrás si la orden procede de la tecla FWD/REV del terminal.

bSP

scalon/Huec

No
BNS: Hueco de velocidad
BLS: Escalon de velocidad

No

Gestión del funcionamiento a baja velocidad:
F : frecuencia motor

F : frecuencia motor

HSP

HSP
No
LSP

LSP
Referencia

0

0

Hueco de
velocidad (BNS)
Referencia
100 %

100 %
F : frecuencia motor
HSP
Escalon de
velocidad (BLS)

LSP

Referencia

0

100 %

CrL
CrH

Ref.Min. AI2- mA
Ref.Máx. AI2- mA

0 a 20 mA
4 a 20 mA

4 mA
20 mA

ESPAÑOL

Valores mínimos y máximos del señal en la entrada AI2.
Estos dos parámetros permiten definir la señal en AI2. Entre otras, hace posible configurar la
entrada por una señal 0-20 mA, 4-20 mA, 20-4mA ...

Frecuencia
HSP

LSP
0

202

CrL

CrH

2
20 AI
(mA)

GP_ATV58_ES.fm Page 203 Mardi, 2. avril 2002 6:05 18

Menú control

Cód.

Descripción

Rango de ajuste

AOL
AOH

Val.Míni AO - mA
Val.Máxi AO - mA

0 a 20 mA
0 mA
0 a 20 mA
20 mA
Valores mínimo y máximo del señal de las salidas lógicas AO y AO1
(1).
Estos dos parámetros permiten definir la señal de salida de AO y
AO1. p.e: 0-20 mA, 4-20 mA, 20-4mA ...

Parametro
Máx

AO (mA)

0
AOL

Str

Ajuste de fábrica

Mem.Consigna

AOH

20

NO-RAM-EEP

NO

Asociada a la función +rápido/-rápido, esta función permite memorizar la consigna:
cuando desaparecen las órdenes de marcha (memorización en RAM) o cuando la red de
alimentación desaparece (memorización en EEPROM)
En el siguiente arranque, la consigna velocidad es la última consigna memorizada.

LCC

Ctrl Consola

No-Sí

No

Permite activar el CONTROL del variador por el terminal. Las teclas STOP/RESET, RUN y FWD/
REV están activas. La consigna velocidad viene dada por el parámetro LFr. Sólo las órdenes
parada libre, rápida y por inyección, permanecen activas en el bornero. Si la conexión variador/
terminal se interrumpe, el variador se bloquea en fallo SLF.

PSt

Prior. STOP

No-Sí

Sí

Add

Direcc. Var.

0 a 31

0

Dirección del variador cuando es controlado por la conexión de la toma terminal (sin terminal de
explotación y terminal de programación)

tbr

BdRate RS485

9600-19200

19200

Velocidad de transmisión mediante el enlace serie RS485 en bits/segundo (se tiene en cuenta en
la siguiente puesta en tensión).
Si tbr ≠ 19200, ya no se puede utilizar el terminal. Para que el terminal esté otra vez
activo, configure de nuevo tbr en 19200 por el enlace serie o efectúe un retorno a los
ajustes de fábrica (véase la página 179).

rPr

Borrar Cont.

No-APH-RTH

No

Puesta a cero de los kWh o del tiempo de funcionamiento.
No
APH: puesta a cero de los kWh
RTH: puesta a cero del tiempo de funcionamiento
La confirmación de la orden de puesta a cero se realiza a través de "ENT".
Las acciones de APH y RTH son inmediatas, a continuación el parámetro vuelve automáticamente
a No.
(1) La salida analógica AO aparece si se instala una tarjeta de extensión de E/S.

203

ESPAÑOL

Esta función otorga la prioridad a la tecla STOP sea cual sea el canal de control (bornero o bus de
terreno).
Para pasar el parámetro PSt a "no":
1 - visualice "no"
2 - pulse la tecla "ENT"
3 - el variador muestra "Ver guía program"
4 - pulse ▲ y a continuación ▼ y seguidamente "ENT"
Para las aplicaciones con "proceso" continuo, se aconseja desactivar la tecla (ajuste en "no")

GP_ATV58_ES.fm Page 204 Mardi, 2. avril 2002 6:05 18

Menú asignación de entradas/salidas

Este menú es accesible en la posición
del conmutador.
Las asignaciones sólo pueden modificarse con el variador en parada y bloqueado.
Cód.

Función

LI2

Afectac.

LI2

Vease el cuadro resumen y la descripción de las funciones.
Las entradas y salidas que figuran en el menú dependen de las tarjetas de E/S que estén instaladas en el
variador y de las elecciones previamente realizadas en el menú control.
Las configuraciones de "fábrica" están preasignadas en la macro-configuración seleccionada.

Cuadro resumen de asignaciones de las entradas lógicas (sin las opciones de 2 hilos/3 hilos).
Tarjetas opcionales de extensión de E/S

2 entradas lógicas LI5-LI6

Variador sin opciones
(No asignada)

X

RV :Giro atrás

(Marcha atrás)

X

(Conmutación de rampa)

X

RP2:Conm. Rampa
JOG:Avance JOG
+SP:+ Velocidad
-SP:- Velocidad

(Marcha paso a paso)

X

(Más rápido)

X

(Menos rápido)

X

PS2:2 Veloc.Pres

(2 velocidades preseleccionadas)

X

PS4:4 Veloc.Pres

(4 velocidades preseleccionadas)

X

PS8:8 Veloc.Pres

(8 velocidades preseleccionadas)

X

(Conmutación de referencias)

X

RFC:Conm. Refer

ESPAÑOL

3 entradas lógicas LI2 a LI4

NO:No asignada

NST:Parada Libre

(Parada en "rueda libre")

X

DCI:Inyecc. c.c.

(Parada por inyección)

X

(Parada rápida)

X

FST:ParadaRápid
CHP:Conm. Motores

(Conmutación de motores)

X

TL2:Limit. Par 2

(Segunda limitación de par)

X

FLO:Forzar Loc.

(Forzado local)

X

RST:ResetDefect

(Eliminación de fallos)

X

ATN:Auto Ajuste

(Autoajuste)

X

PAU:AutoManu PI

(Auto - manual PI) Si una AI = PIF

X

PR2:2 cons.

PI

(2 consignas PI preseleccionadas) Si una AI = PIF

X

PR4:4 cons.

PI

(4 consignas PI preseleccionadas) Si una AI = PIF

X

TLA:Limit. de Par
EDD:Fallo Ext.

(Limitación de par mediante AI) Si una AI = ATL

X

(Fallo externo)

X

ATENCIÓN: Si se asigna una entrada lógica a "Parada en rueda libre" o a "Parada rápida", el
arranque sólo es posible si se conecta esta entrada a +24 V, ya que estas funciones de parada se
activan con las entradas en estado 0.

204

GP_ATV58_ES.fm Page 205 Mardi, 2. avril 2002 6:05 18

Menú asignación de entradas/salidas

Cuadro resumen de asignaciones de las entradas analógicas y del codificador
Tarjetas opcionales de extensión de E/S

Variador sin opciones

SAI:Ref. Suma.
PIF:Retorno PI
PIM:Cons. Man. PI
SFB:Retorno DT

(No asignada)

X

(Referencia de velocidad 2)
Si una LI = RFC

X

(Referencia sumatoria)

X

(Retorno del regulador Pl)

X

(Consigna de velocidad manual PI)
Si una AI = PIF y una LI = PAU

RGI:Retorno GI

X

X

X

X

X
X

(Dinamo tacométrica)

X

(Sondas PTC)

X

(Limitación de par)

X

PTC:Sonda PTC
ATL:Lim.Par

Entrada de
codificador
A+, A-, B+,
B- (1)

Entrada
analógica
AI2

NO:No asignada
FR2:Ref. Vel. 2

Entrada
analógica
AI3

(Retorno de codificador o detector)

X

(1) Nota: El menú asignación de la entrada del codificador A+, A-, B+, B- se denomina "Afectación AI3".
ATENCIÓN: Si el relé R2 se asigna a la función "lógica de freno", AI3 se asigna automáticamente
en ajuste de fábrica al Retorno DT, si la tarjeta está presente. No obstante, es posible reasignar AI3.

Cuadro resumen de asignaciones de las salidas lógicas
Salida lógica
LO

Variador sin opciones

NO:No asignada

Relé R2
(No asignada)

X

X

(Variador en marcha)

X

X

OCC:Ctrl.Contact.

(Control de contactor aguas abajo)

X

X

FTA:Frec. Alcanza

(Umbral de frecuencia alcanzado)

X

X

(HSP alcanzada)

X

X

(Umbral de corriente alcanzado)

X

X

(Referencia de frecuencia alcanzada)

X

X

(Umbral térmico motor alcanzado)

X

X

RUN:En marcha

FLA:HSP. Alcanza
CTA:I Alcanzada
SRA:Réf. Fre. Alca
TSA:T(°C) Alcanz
BLC:LógicaFreno

(Lógica de freno)

X

(Pérdida de referencia 4 / 20 mA)

X

X

F2A:Umbral F2 Alc

(2º umbral de frecuencia 4 / 20 mA)

X

X

TAD: Est. Tér. var

(Umbral térmico variador alcanzado)

X

X

APL:Pérdida 4-20 mA

205

ESPAÑOL

Tarjetas opcionales de extensión de E/S

GP_ATV58_ES.fm Page 206 Mardi, 2. avril 2002 6:05 18

Menú asignación de entradas/salidas

Cuadro resumen de asignaciones de las salidas analógicas
Tarjetas opcionales de extensión de E/S

Salida analógica AO

Variador sin opciones

Salida analógica AO1

NO:No asignada

(No asignada)

X

OCR:Int.Motor

(Corriente del motor)

X

OFR:Frec. Motor

(Velocidad del motor)

X

ORP:SalidaRampa

(Salida rampa)

X

(Par motor)

X

(Par motor con signo)

X

TRQ:Par Motor
STQ:Asig. de par
ORS:Rampa señal.
OPS:Cons. PI

(Salida rampa con signo)

X

(Salida de consigna PI) Si una AI = PIF

X

(Salida retorno PI) Si una AI = PIF

X

OPF:Retorno PI
OPE:Error PI

(Salida de error PI) Si una AI = PIF

X

OPI:Integral PI

(Salida integral PI) Si una AI = PIF

X

OPR:Pot. Salida

(Potencia del motor)

X

THR:Temp. Motor

(Estado térmico del motor)

X

(Estado térmico del variador)

X

THD:Temp. Var.

Después de reasignar las entradas/salidas, los parámetros vinculados a la función aparecen
automáticamente en los menús y en la macro-configuración con la indicación "CUS: personaliz.".
Ciertas reasignaciones añaden nuevos parámetros que deben tenerse en cuenta en el menú ajustes:

ESPAÑOL

E/S

Asignaciones

Parámetros que deben ajustarse

Conmutación de rampa

AC2 dE2

JOG

Marcha Paso a Paso

JOG JGt

PS4

4 velocidades preseleccionadas

SP2-SP3

PS8

8 velocidades preseleccionadas

SP4-SP5-SP6-SP7

DCI

Parada por inyección

IdC

LI

TL2

Segunda limitación de par

tL2

LI

PR4

4 consignas PI preseleccionadas

PI2-PI3

AI

PIF

Retorno del regulador Pl

rPG-rIG-PIC-rdG-rED-PrGPSr-PSP-PLr-PLb

LI

RP2

LI
LI
LI
LI

AI

SFB

Dinamo tacométrica

dtS

R2

BLC

Lógica de freno

Ibr-brt-bEn-bEt-brL-bIP

LO/R2

FTA

Umbral de frecuencia alcanzado

Ftd

LO/R2

CTA

Umbral de corriente alcanzado

Ctd

LO/R2

TSA

Umbral térmico motor alcanzado

ttd

LO/R2

F2A

2º umbral de frecuencia alcanzado

F2d

LO/R2

TAD

Umbral térmico variador alcanzado

dtd

206

GP_ATV58_ES.fm Page 207 Mardi, 2. avril 2002 6:05 18

Menú asignación de entradas/salidas

Ciertas reasignaciones añaden nuevos parámetros que deben tenerse en cuenta en los menún control,
accionamiento o defectos:
E/S

Asignaciones

Parámetros que deben ajustarse

LI

-SP

Menos rápido

Str (menú control)

LI

FST

Parada rápida

dCF (menú accionamiento)

LI

RST

Eliminación de fallos

rSt (menú defectos)

AI

SFB

Dinamo tacométrica

Sdd (menú defectos)

A+, A-,
B+, B-

SAI

Referencia sumatoria

PGt, PLS (menú accionamiento)

A+, A-,
B+, B-

RGI

Retorno GI

PGt, PLS (menú accionamiento)

ESPAÑOL
207

GP_ATV58_ES.fm Page 208 Mardi, 2. avril 2002 6:05 18

Funciones de aplicaciones de entradas/salidas
configurables
Tabla de compatibilidades entre funciones

Limitación del par por LI

Limitación del par por AI3

Ajuste de velocidad con
dinamo tacométrica o encoder

Velocidades presel.

Marcha Paso a Paso

Parada rápida

Parada libre

➞

Frenado por inyección
de corriente continua

Conmutación de referencias

Más rápido/menos rápido

REgulador PI

Entradas sumadoras

Frenado por inyección
de corriente continua

La elección de las funciones de aplicación puede verse limitada por la incompatibilidad de ciertas funciones
entre sí. Las funciones que no aparecen en la tabla no sufren ninguna incompatibilidad.

Entradas sumadores
Regulador PI

➞

Más rápido/menos rápido
Conmutación de referencias
Parada rueda libre

➞

➞

Parada rápida
Marcha Paso a Paso

ESPAÑOL

➞

➞

Velocidades preseleccionadas

➞
➞

Ajuste de velocidad con
dinamo tacométrica o encoder
Limitación del par por AI3
Limitación del par por LI

Funciones incompatibles
Funciones compatibles
Sin objeto
Funciones prioritarias (funciones que no se pueden activar a la vez):

➞

➞

La función señalada por al flecha tiene prioridad sobre la otra.

Las funciones de parada son prioritarias sobre las órdenes de marcha.
Las consignas de velocidad por orden lógica son prioritarias sobre las consignas analógicas.

208

GP_ATV58_ES.fm Page 209 Mardi, 2. avril 2002 6:05 18

Funciones de aplicaciones de entradas/salidas
configurables
Funciones de las aplicaciones de las entradas lógicas
Sentido de marcha: adelante/atrás
La marcha hacia atrás se puede eliminar en caso de aplicación en un sólo sentido de rotación del motor
CONTROL 2 hilos
La marcha (adelante o atrás) y la parada son controladas por la misma entrada lógica. Se toma en cuenta el
estado 1 (marcha) ó 0 (parada), o el cambio (véase el menú tipo de control 2 hilos).
CONTROL 3 hilos
La marcha (adelante o atrás) y la parada son controladas por 2 entradas lógicas diferentes.
LI1 siempre se asigna a la función parada. La parada se obtiene con la apertura (estado 0).
El pulso en la entrada marcha se memoriza hasta la apertura de la entrada parada.
Cuando se produce una puesta en tensión o una reinicialización de fallo manual o automática, el motor sólo
se puede alimentar hasta la reinicialización previa de las órdenes "adelante, "atrás", "parada por inyección".
Conmutación de rampa: 1ª rampa: ACC, DEC ; 2ª rampa: AC2, DE2
Se pueden dar 2 casos de activación:
- activación de una entrada lógica LIx
- detección de un umbral de frecuencia ajustable.
Si se asigna una entrada lógica a la función, sólo se puede realizar la conmutación de rampa desde dicha
entrada.
Marcha Paso a Paso ”JOG”: Pulso de marcha a pequeña velocidad
Si se cierra el contacto JOG y a continuación se acciona el sentido de marcha, la aceleración es 0,1 s, sean
cuales sean los ajustes ACC, dEC, AC2, dE2. Si se cierra el contacto de sentido y a continuación se acciona
el contacto JOG, entonces se utilizan las rampas ajustadas.

ESPAÑOL

Parámetros accesibles en el menú ajuste:
- velocidad JOG
- Inhabilitación temporizada de orden de marcha entre dos órdenes de marcha consecutivas (tiempo
mínino entre 2 controles “JOG”).

209

GP_ATV58_ES.fm Page 210 Mardi, 2. avril 2002 9:35 21

Funciones de aplicaciones de entradas/salidas
configurables
Más rápido/menos rápido: Existen 2 tipos de funcionamiento.
1 Uso de botones por simple acción: se necesitan dos entradas lógicas además de uno o varios sentidos de
marcha.
La entrada asignada al control “más rápido” aumenta la velocidad, la entrada asignada al control “menos
rápido” disminuye la velocidad.
Esta función permite el acceso al parámetro de memorización de consigna Str del menú control.
2 Uso de botones por doble acción: sólo es necesaria 1 entrada lógica asignada al más rápido.
Más rápido/menos rápido con botones de doble acción:
Descripción: 1 botón de doble acción para cada sentido de rotación.
Cada acción cierra un contacto seco.
Reposo
(menos rápido)

1ª acción
(velocidad mantenida)

2 ª acción
(más rápido)

botón giro adelante

–

a

ayb

botón giro atrás

–

c

cyd

Ejemplo de cableado:
LI1 : giro adelante
LIx : giro atrás
LIy : más rápido

Bornero control ATV58
LI1 LIx LIy
+ 24

b
a

d

c

Frecuencia
motor

ESPAÑOL

LSP
0
LSP
Adelante
2a acci—n
1a acci—n
0
Atr‡s
2a acci—n
1a acci—n
0

b
a a a

b
a

a

a

a

c

d
c

Este tipo de más rápido/menos rápido es incompatible con el CONTROL de 3 hilos. En este caso, la función
menos rápido se asigna de forma automática a la entrada lógica de índice superior (ejemplo: LI3 (más rápido),
LI4 (menos rápido)).
En los dos casos la velocidad máxima viene determinada por las consignas aplicadas a las entradas
analógicas. Conecte por ejemplo AI1 a +10V.

210

GP_ATV58_ES.fm Page 211 Mardi, 2. avril 2002 9:35 21

Funciones de aplicaciones de entradas/salidas
configurables
Velocidades preseleccionadas
Se pueden preseleccionar 2,4 u 8 velocidades, que necesitan respectivamente 1, 2, ó 3 entradas lógicas.
Se debe respetar el siguiente orden de asignación: PS2 (LIx), PS4 (LIy) y PS8 (LIz) por último.

LIx

2 velocidades
preseleccionadas

4 velocidades preseleccionadas

8 velocidades preseleccionadas

Asignar: LIx a PS2

Asignar: LIx a PS2 y,
LIy a PS4

Asignar: LIx a PS2
LIy a PS4, y LIz a PS8

LIy

LIx

LIz

LIy

LIx

0

LSP+consigna

referencia veloc.

0

0

LSP+consigna

referencia veloc.

0

0

0

LSP+consigna

referencia veloc.

1

HSP

0

1

SP2

0

0

1

SP2

1

0

SP3

0

1

0

SP3

1

1

HSP

0

1

1

SP4

1

0

0

SP5

1

0

1

SP6

1

1

0

SP7

1

1

1

HSP

Para resasignar las entradas lógicas se debe respetar el siguiente orden: PS8 (LIz), PS4 (LIy) y PS2 (LIx).
Conmutación de referencia
Conmutación de dos referencias (referencia en AI1 y referencia en AI2) por orden de entrada lógica.
Esta función asigna automáticamente AI2 a la referencia de velocidad 2
Esquema de conexión

LI x + 24 COM

AI 1

+10

AI 2
ESPAÑOL

0-20mA
4-20mA

Contacto abierto, referencia= AI2
Contacto cerrado, referencia= AI1

Parada rueda libre
Provoca la parada del motor por el par resistente solamente, la alimentación del motor se interrumpe.
La parada libre se consigue al abrir la entrada lógica (estado 0).
Parada por inyección de corriente continua
La parada por inyección se consigue al cerrar la entrada lógica (estado 1).
Parada rápida
Parada de frenado con el tiempo de curva de Deceleración reducido por un coeficiente de reducción dCF que
aparece en el menú de accionamiento.
La parada rápida se consigue al abrir la entrada lógica (estado 0).

211

GP_ATV58_ES.fm Page 212 Mardi, 2. avril 2002 9:35 21

Funciones de aplicaciones de entradas/salidas
configurables
Conmutación de motores
Esta función permite que un mismo variador alimente sucesivamente a dos motores de potencias diferentes,
asegurando la conmutación mediante una secuencia apropiada a la salida del variador. La conmutación debe
hacerse con el motor parado, con el variador bloqueado. Los siguientes parámetros internos se conmutan
automáticamente en un orden lógico:
- corriente nominal del motor
- corriente de inyección

- corriente de apertura de freno

Esta función inhibe automáticamente la protección térmica del segundo motor.
Parámetro accesible: Relación de potencias de motores PCC en el menú accionamiento.
Segunda limitación de par
Reducción del par máximo del motor cuando la entrada lógica está activa.
Parámetro tL2 en el menú ajuste.
Reinicialización de fallo
Hay dos tipos de reinicialización: parcial o general (parámetro rSt del menú "defectos").
Reinicialización parcial (rSt = RSP):
Permite borrar un fallo memorizado y volver a arrancar el variador si desaparece la causa del fallo.
Fallos a los que afecta el borrado parcial:
-

sobretensión red
sobretensión bus continuo
corte fase motor
pérdida de la carga

-

defecto de comunicación
sobrecarga Motor
falloCorte4-20mA
fallo externo

-

sobreTemp.Motor
fallo conexión serie
sobretemp. variador
sobrevelocidad

ESPAÑOL

Reinicialización general (rSt = RSG):
Se trata de la inhibición (operación forzada) de todos los fallos excepto del SCF (Cortocirc. mot.)
mientras que la entrada lógica asignada está cerrada.
Forzado local
Permite pasar de un modo de control de línea (conexión serie) a un modo local (control desde el bornero o
desde el terminal).
Autoajuste
El paso a 1 de la entrada lógica asignada dispara un autoajuste, al igual que el parámetro tUn del menú
"accionamiento".
ATENCIÓN: el autoajuste sólo tiene lugar si no se acciona ningún mando. Si se asigna una función
"parada en rueda libre" o "parada rápida" a una entrada lógica, es necesario poner la entrada a 1
(activa a 0).
Aplicación: Para la conmutación de motores, por ejemplo.
Auto-manu PI, consigna PI preseleccionadas: Ver función PI (página 213)
Limitación de par mediante AI
Esta función no es accesible si la entrada analógica AI3 no está asignada a limitación de par. Si no hay una
LI configurada en “TL2: segunda limitación de par”, la limitación está directamente dada por AI3.
Si una entrada lógica está configurada en “TL2: segunda limitación de par” :
- Cuando la entrada está a 0, la limitación viene dada por tLi
- Cuando la entrada esta a 1, la limitación viene dada por AI3
Fallo externo
El paso a 1 de la entrada lógica asignada inicia la parada del motor (según la configuración del parámetro
Stt Tipo Parada del menú Accionamiento), el bloqueo del variador por fallo EPF Fallo Ext..

212

GP_ATV58_ES.fm Page 213 Mardi, 2. avril 2002 9:35 21

Funciones de aplicaciones de entradas/salidas
configurables
Funciones de aplicación de las entradas analógicas
La entrada AI1 es siempre referencia de velocidad.

Asignación de AI2 y AI3
Referencia de velocidad sumadora: Las consignas de frecuencia que se derivan de AI2 y AI3 se pueden
sumar a AI1.
Ajuste de velocidad con dinamo tacométrica: (Asignación a AI3 solamente con una tarjeta de extensión
de E/S con entrada analógica): permite corregir la velocidad mediante el retorno dinamo tacométrico.
Se necesita un puente divisor exterior para adaptar la corriente de la dinamo tacométrica. La corriente máxima
debe estar comprendida entre 5 y 9 V. A continuación se consigue un ajuste exacto gracias al ajuste del
parámetro dtS que se encuentra disponible en el menú ajuste.
Tratamiento sonda PTC: (sólo con una tarjeta de extensión de E/S con entrada analógica). Permite la
protección térmica directa del motor mediante la conexión de las sondas PTC del bobinado del motor a la
entrada analógica AI3 .
Características de las sondas PTC:
Resistencia total de la sonda del circuito a 20 °C = 750 Ω.
Regulador PI: Permite regular un proceso con una referencia y un retorno procedente de un captador. Con
la función PI, todas las rampas son lineales aunque se configuren de otra forma.
Con el regulador PI, es posible:
- adaptar el retorno por FbS;
- realizar una corrección inversa de PI;
- ajustar las ganancias proporcional e integral (RPG y RIG);
- asignar una salida analógica a la consigna PI, el retorno PI y el error PI;
- aplicar una rampa de establecimiento de la acción del PI (AC2) en el arranque si PSP > 0.
Si PSP = 0 las rampas activas son ACC/dEC. En la parada, la rampa dEC se utiliza siempre.
La velocidad del motor está limitada entre LSP y HSP.
Atención: La función de regulador PI se activa cuando se asigna una entrada AI al retorno PI. Esta asignación
a AI sólo es posible después de cancelar las funciones incompatibles con PI (voir page 208).

Retorno
PI
PSP

+
FBS
10

Filtro de Multiplicador
paso bajo

Consigna manual
Auto / manu

Inversion
PI

Regulador
PI

PIC
X±1

RPG
RIG

Rampa
si PSP = 0
X

Rampa
si PSP > 0

ESPAÑOL

Consigna
PI

AC2
dE2

ACC
dEC

Referencia
Auto
Manu

Orden de marcha
ACC
dEC
Rampa

Auto/manu: Sólo se puede acceder a esta función si la función PI esta activada, y requiere una tarjeta de
extensión de E/S con entrada analógica
Permite mediante la entrada lógica LI, conmutar la marcha en regulación de velocidad si LIx = 0 (consigna
manual en AI3), y la regulación PI si LIx = 1 (auto).

213

GP_ATV58_ES.fm Page 214 Mardi, 2. avril 2002 6:05 18

Funciones de aplicaciones de entradas/salidas
configurables
Consignas preseleccionadas
2 ó 4 consignas preseleccionadas requieren respectivamente la utilización de 1 ó 2 entradas lógicas:

LIx

2 consignas preseleccionadas

4 consignas preseleccionadas

Asignar : LIx a Pr2

Asignar : LIx a Pr2 y a continuación, LIy a Pr4

Referencia

0

Consigna analógica

1

Máx. proceso (= 10 V)

LIy

LIx

0

0

Referencia
Consigna analógica

0

1

PI2 (ajustable)

1

0

PI3 (ajustable)

1

1

Máx. proceso (= 10 V)

Limitación de par: (Sólo con una tarjeta de extensión de E/S con entrada analógica AI3)
La señal que se aplica a AI3 actúa linealmente sobre la limitación de par interno (parámetro TLI del menú
"accionamiento"):
- Si AI3 = 0V: limitación = TLI x 0 = 0
- Si AI3 = 10 V: limitación = TLI
Aplicaciones: Corrección de par, de tracción…

Funciones de aplicaciones de la entrada del encoder:
(sólo con una tarjeta de extensión de E/S con entrada de encoder)
Ajuste de velocidad: Permite corregir la velocidad mediante un encoder incremental o detector. (Consulte la
documentación de la tarjeta).

ESPAÑOL

Referencia de velocidad sumadora: La consigna obtenida en la entrada del encoder se añade a AI1.
(Consulte la documentación de la tarjeta).
Aplicaciones:
- Sincronización de velocidad de varios variadores. El parámetro PLS del menú "accionamiento" permite
ajustar la relación de la velocidad de un motor con respecto a otro.
- Consigna mediante generador de impulsos.

214

GP_ATV58_ES.fm Page 215 Mardi, 2. avril 2002 6:05 18

Funciones de aplicaciones de entradas/salidas
configurables
Funciones de aplicación de las salidas lógicas
Relé R2, salida estática LO (con tarjeta de extensión de E/S)
Control contactor aguas abajo (OCC): asignable a R2 o LO
Permite el CONTROL de un contactor de bucle (colocado entre el variador y el motor) desde el variador. La
petición de cierre del contactor se realiza al aparecer una orden de marcha. La apertura del contactor se
solicita cuando no queda corriente en el motor.
Si se configura una función de frenado por inyección de corriente continua, no se debe hacer actuar
demasiado tiempo en parada, ya que esto haría que el contactor no se abriese hasta el final del frenado.
Variador en marcha (RUN): asignable a R2 o LO
La salida lógica está en estado 1 si el variador alimenta al motor (presencia de corriente), o si se presenta una
orden de marcha con una referencia negativa.
Umbral de frecuencia alcanzada (FTA): asignable a R2 o LO
La salida lógica está en estado 1 si la frecuencia del motor es mayor o igual que el umbral de frecuencia
predeterminado por Ftd en el menú ajuste.
2º umbral de frecuencia alcanzado (F2A): asignable a R2 o LO
La salida lógica está en estado 1 si la frecuencia del motor es superior o igual al umbral de frecuencia ajustado
por F2d en el menú de ajustes.
Consigna alcanzada (SRA): asignable a R2 o LO
La salida lógica está en estado 1 si la frecuencia del motor es igual al valor de la consigna.
Máxima velocidad alcanzada (FLA): asignable a R2 o LO
La salida lógica está en estado 1 si la frecuencia del motor es igual a HSP.
Umbral de corriente alcanzada (CTA): asignable a R2 o LO
La salida lógica está en estado 1 si la corriente del motor es mayor o igual que el umbral de corriente
predeterminada por Ctd en el menú ajuste.

Estado térmico del variador alcanzado (TAD) : asignable a R2 o LO
La salida lógica está en estado 1 si el estado térmico del variador es mayor o igual que el umbral de estado
térmico predeterminado por dtd en el menú ajuste.
Control de freno (BLC): asignable exclusivamente al relé R2
Permite que el variador controle un freno electromagnético en aplicaciones de apertura vertical. Para frenar
los movimientos horizontales utilícese la función “variador en marcha“.
Velocidad motor

T = temporización no ajustable
Ajustes accesibles en el menú ajuste:
- frecuencia de apertura de freno
(brL)
- temporización de apertura de freno
(brt)
- temporización de cierre de freno
(bEt)
- corriente de apertura de freno (Ibn)
- frecuencia de cierre de freno (bEn)

Consigna

Estado freno
1
0
Relé R2
1
0
Subida o bajada
1
0
T

brt

bEt

215

ESPAÑOL

Estado térmico del motor alcanzado (TSA): asignable a R2 o LO
La salida lógica está en estado 1 si el estado térmico del motor es mayor o igual que el umbral de estado
térmico predeterminado por ttd en el menú ajuste.

GP_ATV58_ES.fm Page 216 Mardi, 2. avril 2002 6:05 18

Funciones de aplicaciones de entradas/salidas
configurables
Recomendación para el ajuste del control de freno para una aplicación de apertura vertical:
1 Frecuencia de apertura del freno (brL):
Ajuste la frecuencia de apertura del freno al valor: deslizamiento nominal multiplicado por la frecuencia
nominal en Hz (s x FS).
Ns – Nr )
Modo de cálculo: deslizam. = (-----------------------Ns

- Ns = velocidad de sincronismo en tr / mn.
(para una red de 50 Hz: Ns = 3000 tr/mn para un motor de 1 par de polos, 1500 tr/mn para un motor de 2
pares de polos, 1000 tr/mn para un motor de 3 pares de polos y 750 tr/mn para un motor de 4 pares de
polos,
para una red de 60 Hz: Ns = 3600 tr/mn para un motor de 1 par de polos, 1800 tr/mn para un motor de 2
pares de polos, 1200 tr/mn para un motor de 3 pares de polos y 900 tr/mn para un motor 4 pares de polos).
- Nr = velocidad nominal al par nominal en tr/mn. Tome la velocidad de la placa del motor.
Frecuencia de apertura= s x Fs.
- s = deslizamiento previamente calculado.
- Fs = frecuencia nominal motor (indicada en la placa del motor).
Ejemplo: para motor de 2 pares de polos, marcado en placa con 1430 tr/mn, red de 50 Hz.
s = (1500 - 1430) / 1500 = 0,0466.
Frecuencia de apertura de freno = 0,0466 x 50 = 2,4 Hz
2 Corriente de apertura del freno (Ibr):
Ajuste la corriente de apertura de freno a la corriente nominal marcada en la placa del motor.

ESPAÑOL

Advierta que en los puntos 1 y 2: los valores indicados (corriente de apertura y frecuencia de apertura)
corresponden a los valores teóricos. Si durante las pruebas, el par es insuficiente con los valores teóricos:
mantenga la corriente de apertura de freno en la corriente nominal del motor y baje la frecuencia de apertura
de freno (hasta 2/3 del deslizamiento nominal). Si el resultado no es satisfactorio, vuelva a los valores
teóricos, aumente a continuación la corriente de apertura de freno (el variador impone el valor máximo) y
aumente por último la frecuencia de apertura de freno progresivamente.
3 Tiempo de Aceleración:
Para las aplicaciones de apertura, es aconsejable ajustar las curvas de Aceleración de más de 0,5
segundos. Asegúrese de que el variador no pase a limitación de corriente.
Téngase en cuenta la misma recomendación que para la Deceleración.
Advertencia: para un movimiento de apertura, se deberá utilizar una resistencia de frenado y habrá que
asegurarse de que los ajustes y las configuraciones elegidas no pueden provocar ni la caída ni el "no
control" de la carga elevada.
4 Temporización de apertura del freno (brt):
Ajústese en función del tipo de freno. Es el tiempo que necesita el freno mecánico para abrirse.
5 Frecuencia de cierre del freno (bEn):
Ajústese a 2 veces el deslizamiento nominal (en nuestro ejemplo 2 x 2,4 = 4,8 Hz). Ajústese a continuación
en función del resultado.
6 Temporización de cierre del freno (bEt):
Ajústese en función del tipo de freno. Es el tiempo que necesita el freno mecánico para cerrarse.
Pérdida 4-20 mA (APL) asignable a R2 o LO
La salida lógica está en 1 si la señal de la entrada 4-20 mA es inferior a 2 mA.

216

GP_ATV58_ES.fm Page 217 Mardi, 2. avril 2002 6:05 18

Funciones de aplicaciones de entradas/salidas
configurables
Funciones de aplicación de la salida analógica AO y AO1
Las salidas analógicas AO y AO1 son salidas en corriente, de AOL (mA) a AOH (mA).
• AOL y AOH pueden configurarse entre 0 y 20 mA.
Ejemplos AOL - AOH : 0 - 20 mA
4 - 20 mA
20 - 4 mA
Corriente del motor (Código OCR): proporciona la imagen de la corriente eficaz del motor.
• AOH corresponde a 2 veces la corriente nominal del variador.
• AOL corresponde a la corriente nula.
Frecuencia del motor (Código OFR): ofrece la frecuencia del motor estimada por el variador.
• AOH corresponde a la frecuencia máxima (parámetro tFr).
• AOL corresponde a la frecuencia nula.
Salida rampa (Código ORP): ofrece la imagen de la frecuencia en la salida de la rampa.
• AOH corresponde a la frecuencia máxima (parámetro tFr).
• AOL corresponde a la frecuencia nula.
Par motor (Código TRQ): ofrece la imagen del par del motor en valor absoluto.
• AOH corresponde a dos veces el par nominal del motor.
• AOL corresponde al par nulo.
Par motor con signo (código STQ): ofrece la imagen del par motor y su sentido:
• AOL corresponde a un par de frenado = 2 veces el par nominal.
• AOH corresponde a un par motor = 2 veces el par nominal
• AOH + AOL corresponde a un par nulo.
2

Consigna PI (código OPS): proporciona la imagen de la consigna del regulador PI.
• AOL corresponde a la consigna mínima.
• AOH corresponde a la consigna máxima.
Retorno PI (código OPF): proporciona la imagen del retorno del regulador PI.
• AOL corresponde al retorno mínimo.
• AOH corresponde al retorno máximo.

217

ESPAÑOL

Rampa con signo (código ORS): proporciona la imagen de la frecuencia en la salida de la rampa y su
sentido.
• AOL corresponde a la frecuencia máxima (parámetro tFr) en marcha atrás.
• AOL corresponde a la frecuencia máxima (parámetro tFr) en marcha adelante.
• AOH + AOL corresponde a una frecuencia nula
2

GP_ATV58_ES.fm Page 218 Mardi, 2. avril 2002 6:05 18

Funciones de aplicaciones de entradas/salidas
configurables
Error PI (código OPE): proporciona la imagen de error del regulador PI en % del intervalo del captador
(retorno máx. - retorno mín.).
• AOL corresponde al error máximo < 0.
• AOH corresponde al error máximo > 0.
• AOH + AOL corresponde a un error nulo (OPE = 0).
2
Integral PI (código OPI): proporciona la imagen de la integral del error del regulador PI.
• AOL corresponde a una integral nula.
• AOH corresponde a una integral saturada.
Potencia del motor (código OPR): proporciona la imagen de la potencia absorbida por el motor.
• AOL corresponde al 0% de la potencia nominal del motor.
• AOH corresponde al 200% de la potencia nominal del motor.
Estado térmico del motor (código THR): proporciona la imagen del estado térmico del motor, calculado.
• AOL corresponde a 0%.
• AOH corresponde a 200%.

ESPAÑOL

Estado térmico del variador (código THD): proporciona la imagen del estado térmico del variador.
• AOL corresponde a 0%.
• AOH corresponde a 200%.

218

GP_ATV58_ES.fm Page 219 Mardi, 2. avril 2002 6:05 18

Menú defectos

Este menú es accesible en posición
del conmutador.
Sólo se pueden realizar los cambios en paro, con el variador bloqueado.
Cód.

Descripción

Ajuste en fábrica

Atr

Rearr.Automa

No

Esta función permite el rearranque automático del variador cuando el error ha desaparecido
(selección Sí/No).
Se puede realizar el rearranque después de los siguientes fallos:
- Sobretensión red
- Sobretensión bus DC
- fallo externo
- corte fase motor
- fallo conexión en serie
- fallo de comunicación
- corte 4-20 mA
- Sobrecarga motor (condición: estado térmico motor inferior al 100%)
- sobretemp. variador (condición: estado térmico variador inferior al70%)
- SobreTemp.motor (condición: estado de las sondas inferior a 1 500 Ohmios)
Cuando la función esta activada, después de la aparición de uno o varios de estos fallos, el relé R1
permanece cerrado: el variador realiza un intento de arranque cada 30 s. Se efectúa un máximo de
6 intentos mientras el arrancador no pueda arrancar (presencia del fallo). Si fracasan los 6 intentos,
el variador se bloquea definitivamente y se abre el relé de fallo. Para rearmar el aparato, es
necesario apagarlo.
Esta función necesita que la secuencia asociada se mantenga, y hay que asegurarse de
que el rearranque intempestivo no presente ningún peligro humano o material.

rSt

Tipo Reset

RSP

Esta función es accesible si la reinicialización de los fallos se asigna a una entrada lógica.
2 posibles elecc.: reset parciall (RSP), reset total (RSG)
Fallos afectados por un reset parcial (rSt = RSP)
- sobretensión bus contin.
- fallo Corte 4-20mA
- pérdida de la carga
- sobretemp. variador
- fallo externo
- sobrevelocidad

ESPAÑOL

- sobretensión red
- sobreTemp.Motor
- sobrecarga Motor
- corte fase motor
- fallo conexión en serie
- fallo comunicación

Fallos afectados por un reset general (rSt = RSG):
todos los fallos. El reset general provoca la inhibición de todos los fallos (marcha forzada).
Para configurar St = RSG :
1 - visualice RSG
2 - pulse la tecla "ENT"
3 - el variador visualiza"Ver guía program"
4 - pulse ▲ a continuación ▼ y finalmente pulse "ENT"

OPL

CorteFaseMot

Sí

Permite actualizar el fallo de corte de fase motor. (Eliminación del fallo en caso de utilización de un
interruptor entre el variador y el motor).
Elección Sí/No

IPL

CorteFaseVar

Sí

Permite validar el fallo de corte de fase de red.
Eliminación del fallo en caso de alimentación directa por un bus continuo y en caso de alimentación
de un variador trifásico ATV58• U72M2, U90M2 o D12M2 monofásico). Elección Sí/No
Este fallo no existe en los ATV58•U09M2, U18M2, U29M2 y U41M2

219

GP_ATV58_ES.fm Page 220 Mardi, 2. avril 2002 6:05 18

Menú defectos

Cód.

Descripción

Ajuste en fábrica

tHt

TipoProtTérm

ACL

Define el tipo de protección térmica indirecta del motor que realiza el variador. Si se conectan
sondas PTC al variador, no es posible realizar dicha función.
Sin protección térmica: N0: Ninguno
Motor Auto-ventilado (ACL): el variador considera una desclasificación en función de la frecuencia
de rotación.
Motor moto-ventilado (FCL): el variador no considera una desclasificación en función de la
frecuencia de rotación.

LFL

FalloCorte4-20mA

No

Permite la validación del fallo de corte 4-20 mA.
Este fallo sólo se puede configurar si los parámetros ref. mín./máx. AI2 (CrL y CrH)) superan los 3
mA o si CrL>CrH.
- No : Ningún fallo
- Si : Fallo inmediato
- STT: parada según el parámetro STT, sin fallo, re-arranque al retorno de la señal
- LSF: parada según el parámetro STT, dando el fallo al fin de la parada.
- LFF: forzado a la velocidad fijada por el parámetro LFF
- RLS: mantiene la velocidad alcanzada a partir del corte 4-20 mA, sin fallo, re-arranque al
retorno de señal

LFF

Fall.ret.vel

0

Velocidad de secuencia en caso de pérdida de referencia 4-20 mA.
Ajuste de 0 a HSP.

ESPAÑOL

FLr

Cazar Vuelo

No

Permite validar un rearranque sin brusquedad cuando se produce:
- corte de red o simple desconexión.
- reinicialización de fallos o rearranque automático.
- parada libre o parada por inyección con entrada lógica.
- corte no controlado antes del variador.
Elección Sí/No
Si se asigna el relé R2 a la función lógica de freno el parámetro FLr se bloquea en no.

StP

Paro Control

No

Parada controlada en un corte de fase de red. Esta función sólo es operativa si el parámetro IPL
se posiciona en No. Si IPL está en Sí, mantenga StP en posición No. Posibles elecciones:
No: bloqueo al interrumpirse la red.
MMS: Mant. Bus DC: el control del variador se mantiene en tensión mediante la energía cinética
restituida por las inercias hasta que aparece el fallo USF (Subtensión)
FRP: En rampa: Deceleración según la rampa programada dEC o dE2 hasta la parada o la
aparición de fallo USF (Subtensión). Este funcionamientos no existe en ATV58•U09M2, U18M2,
U29M2 y U41M2

Sdd

PérdidaCarga

Sí

Esta función es accesible si se programa un retorno mediante dinamo tacométrica o generador de
impulsos. Validada, permite bloquear el variador, si se detecta un no seguimiento de velocidad
(diferencia entre la frecuencia del estator y la velocidad medida).
Elección Sí/No.

EPL

220

Fallo Ext.
Sí
Configure el parada en Fallo externo:
- Sí: bloqueo del variador en fallo inmediate.
- LSF:Parada+fallo: parada según el parámetro Stt(Menú accionamiento) a continuación
bloqueo en fallo.

GP_ATV58_ES.fm Page 221 Mardi, 2. avril 2002 6:05 18

Menú archivo

Este menú es accesible en posición
del conmutador.
Las Operaciones sólo se pueden realizar en parada, con el variador bloqueado.
El terminal permite almacenar 4 archivos que contienen las configuraciones del variador.
Cód.

Descripción

Ajuste en fábrica

F1S
F2S
F3S
F4S

EstadoArch. 1
EstadoArch. 2
EstadoArch. 3
EstadoArch. 4
Visualiza el estado del archivo correspondiente.
Estados posibles:
FRE: Archivo libre (Estado al entregar el terminal)
EnG: Hay una configuración ya memorizada en dicho archivo

FRE
FRE
FRE
FRE

FOt

Operación

NO

Selecciona la Operación que se va a realizar en los archivos.
Operaciones posibles:
NO: Operación no solicitada (valor por defecto en cada nueva conexión del
terminal al variador)
STR: Operación de memorización de la configuración del variador en un archivo
del terminal
REC: transfer. del contenido de un arch. hacia el var.
Ini: retorno del variador a los ajustes de fábrica
El retorno al ajuste de fábrica anula los demás ajustes y la
configuración.

Modo operativo
Seleccione STR, REC o InI y pulse "ENT".
1 Si Operación = STR:
Visualización de los números de archivos. Seleccione un archivo por medio de ▲ o ▼ y acepte con "ENT".

- la pantalla muestra:

CHG

CABLEADO OK?

ENT

Compruebe que el cableado es compatible con la configuración del archivo.
Cancele con "ESC" o acepte con "ENT"
- la pantalla solicita una nueva confirmación: acepte con "ENT" o cancele con "ESC".
3 Si Operación = InI :
Acepte con "ENT"
- la pantalla muestra:

CHG

CABLEADO OK?

ENT

Compruebe que el cableado es compatible con la configuración de fábrica.
Cancele con "ESC" o acepte con "ENT".
- la pantalla solicita una nueva confirmación: acepte con "ENT" o cancele con "ESC".
Al final de cada operación, la pantalla vuelve al parámetro "Operación" en "NO".

221

ESPAÑOL

2 Si Operación = REC
Visualización de los números de archivos. Seleccione un archivo por medio de ▲ o ▼ y acepte con "ENT".

GP_ATV58_ES.fm Page 222 Mardi, 2. avril 2002 6:05 18

Menú archivo

Menú ARCHIVO (continuación)
Cód.

Descripción

COd

Password
Código confidencial (contraseña)

La configuración del variador se puede proteger mediante un password (COd).
ATENCIÓN: ESTE PARÁMETRO SE DEBE UTILIZAR CON PRECAUCIÓN. PUEDE PROHIBIR EL
ACCESO AL CONJUNTO DE PARÁMETROS. CUALQUIER MODIFICACIÓN DEL VALOR DEL
PARÁMETRO SE DEBE GUARDAR CELOSAMENTE.
El valor del código viene determinado por cuatro cifras. La primera fija el nivel de accesibilidad que se desee
dejar libre.

8888
esta cifra proporciona el nivel
de acceso autorizado, sin código correcto.
El acceso a los MENÚS en función del conmutador de acceso situado en la cara delantera del terminal esté
siempre operativo dentro de los límites autorizados por el código.
El valor del código 0000 (ajuste en fábrica) no limita el acceso.
La siguiente tabla define el acceso a los MENÚS en función de la última cifra del código.

ESPAÑOL

Última cifra del código
MENÚ

Acceso
bloqueado

Visualización

Modificación

Ajustes

0 salvo 0000 y 9

1

2

Nivel 2:
Ajustes, Macro-config, Accionamiento, control,
afectación E/S, Defectos, archivo (excepto
código), comunicación (si hay tarjeta)

0 salvo 0000 y 9

3

4

Aplicación (si hay tarjeta)

0 salvo 0000 y 9

5

6

Nivel 2 y aplicación (si hay tarjeta)

0 salvo 0000 y 9

7

8

Para acceder al menú APLICACIÓN, consulte la documentación de la tarjeta de aplicación.
El cambio de código se realiza con las teclas ▲ y ▼ .
Si se introduce un Password erróneo, éste se rechaza mediante la visualización del mensaje:

COd

Password Fault

Pulse a continuación las teclas ENT o ESC. El valor visualizado del parámetro Código se transforma en 0000.
El nivel de acceso no se altera. La Operación se debe repetir.
Para acceder a los menús protegidos mediante una contraseña, es necesario introducir previamente dicho
código que siempre está accesible en el menú archivo.

222

GP_ATV58_ES.fm Page 223 Mardi, 2. avril 2002 6:05 18

Menús comunicación y aplicación/asistencia a la
explotación/mantenimiento
Menú comunicación
Este menú se visualiza sólo si hay una tarjeta comunicación instalada. Es accesible en
la posición
del conmutador. Sólo se puede configurar en paro, con el variador bloqueado.
Para utilizarlo con una tarjeta opcional de comunicación, véase el documento que se entrega con dicha tarjeta.
Para utilizar la comunicación mediante la conexión RS485 del producto básico, véase el documento que se
entrega con el kit de conexión RS485.

Menú aplicación
Este menú sólo se visualiza si se instala una tarjeta “aplicación cliente“. Es accesible en la posición
conmutador. Sólo se puede configurar en paro, con el variador bloqueado.
Véase la documentación que se entrega con la tarjeta.

del

Asistencia a la explotación
Véanse los indicadores de señalización en el apartado "Presentación".

Mantenimiento
Antes de manipular el variador, desconecte la alimentación y espere que se descarguen los
condensadores (3 minutos aproximadamente): se apaga el LED verde de la cara delantera del
variador.
ATENCIÓN: la tensión continua en los bornes + y - o PA y PB puede alcanzar los 900 V según sea la
tensión de la red.

En caso de anomalía durante la puesta en servicio o la explotación, asegúrese de que se han respetado
todas las recomendaciones referentes al entorno, al montaje y a las conexiones. Consulte la guía de
explotación del Altivar.

El Altivar 58 no necesita mantenimiento preventivo. Sin embargo, es aconsejable, periódicamente:
- comprobar el estado y el ajuste de las conexiones.
- asegurarse de que la temperatura cercana al aparato se mantiene a un nivel aceptable, y que la
ventilación es correcta (vida media de los ventiladores: 3 a 5 años según las condiciones de explotación).
- quitar el polvo al variador en caso de necesidad.

Asistencia al mantenimiento
El primer fallo detectado se memoriza y se visualiza en la pantalla del terminal: el variador se bloquea, el LED
rojo se enciende y el relé de seguridad R1 se dispara.

Borrado del fallo
Desconecte la alimentación del variador en caso de que se produzca un fallo que impida volver arrancar.
Busque el motivo del fallo para eliminarlo.
Restablecimiento de la alimentación: borra el fallo en caso de que éste haya desaparecido.
En determinados casos, se puede producir un rearranque automático al desaparecer el fallo, siempre y
cuando esta función se haya programado previamente.

223

ESPAÑOL

Mantenimiento

GP_ATV58_ES.fm Page 224 Mardi, 2. avril 2002 6:05 18

ESPAÑOL

Mantenimiento

Fallo visualizado

Causa probable

Proceso, solución

PHF
PérdidaFase Var

• variador mal alimentado o fusión de
fusibles
• corte de una fase
• uso en red monofásica de un
ATV58•U72M2, U90M2 o D12M2
(trifásico)

• compruebe la conexión potencia y los
fusibles
• rearranque
• configurar el valor "CorteFaseVar"
(código IPL) a "No", en elmenú
DEFECTOS

USF
Subtensión

• red sin potencia suficiente
• bajada de tensión temporal
• resistencia de carga defectuosa

• compruebe la tensión de red

OSF
Sobretensión

• red con tensión demasiado elevada

• compruebe la tensión de la red

OHF
SobreTemp. Var

• temp. radiador muy elevada
(tHd>118 %)

• controle la carga del motor, la
ventilación del variador y espere a que
se enfríe antes de rearrancar

OLF
Sobrecarga Motor

• desconexión térmica por sobrecarga
prolongada (tHr>118 %)

• compruebe el ajuste de la protección
térmica, controle la carga del motor.
• pasados 7 minutos es posible
rearrancar.

ObF
Frenado Excesivo

• frenado demasiado brusco o carga de
accionamiento
• Subtensión red en funcionamiento

• aumente el tiempo de deceleración,
añada una resistencia de frenado si es
necesario.
• verificar las eventuales subtensiones
de red

• cambie la resistencia de carga

OPF
• corte de fase a la salida del variador
PérdidaFase Motor

• verificar las conexiones del motor y del
cierre del contactor aguas abajo (si
existe).
• si se utiliza un arranque motor en la
macro configuración, verificar que la
configuración de R2 es control
contactor.

LFF
• corte de la consigna 4-20mA en la
FalloCorte 4-20mA
entrada AI2

• compruebe la conexión de los circuitos
de consigna

OCF
Sobreintensidad

• rampa demasiado corta
• inercia o carga demasiado alta
• bloqueo mecánico

• compruebe los ajustes
• compruebe el dimensionamientomotor/
variador/carga
• compruebe estado mecánica

SCF
Cortocirc. mot

• corto circuito o conexión a tierra a la
salida del variador

• compruebe cables de conexión
variador desconectado e aisla- del
motor. Compruebe el puente de
transistores del variador.

CrF
Fallo Circ.Carga

• fallo de CONTROL del relé de carga
• resistencia de carga deteriorada

• compruebe la conéctica del variador y
la resistencia de carga

SLF
Fallo CorteRS485

• mala conexión al puerto de
comunicación

• compruebe la conexión al puerto de
comunicación

OtF
SobreTemp.Motor

• temperatura motor demasiado elevada • compruebe la ventilación del, motor, la
(sondas PTC)
temperatura ambiente, controle la
carga del motor.
• compruebe el tipo de sondas utilizadas.

224

GP_ATV58_ES.fm Page 225 Mardi, 2. avril 2002 6:05 18

Mantenimiento

Fallo visualizado

Causa probable

tSF
Fallo

• mala conexión de las sondas al variador • compruebe la conexión de las sondas
al variador
• compruebe las sondas

sonda PTC

Proceso, solución

• error de memorización en EEPROM

• interrumpa la alimentación del variador
y rearranque.

InF
Fallo Interno

• fallo interno
• fallo de conexión

• compruebe la conéctica en el variador.

EPF
Fallo Externo

• fallo originado por un componente
externo

• compruebe el componente que provocó
el fallo y rearranque

SPF
Retorno vel.

• ausencia de retorno de velocidad

• compruebe la conexión y el
acoplamiento mecánico del sensor de
velocidad

AnF
Pérdida de carga

• no continuidad de rampa
• velocidad inversa a la consigna

• compruebe el ajuste y cableado del
retorno de velocidad.
• compruebe la adecuación de los
ajustes con respecto a la carga.
• compruebe el dimensionamiento motovariador y la necesidad de una
resistencia de frenado.

SOF
Sobrevelocidad

• inestabilidad
• carga accionam. muy elevada

• compruebe ajustes y parámetros
• añada una resistencia de frenado
• compruebe el dimensionamiento motor/
variador/carga

CnF
Fallo Com. Red

• fallo de comunicación en el bus de
terreno

• compruebe la conexión de la red al
variador
• compruebe el Time Out.

ILF
FalloCom.Interna

• fallo de comunicación entre la tarjeta
opcional y la tarjeta de control

• comprobar la conexión de la tarjeta
opcional a la tarjeta de control.

CFF

Posible error durante un cambio de
tarjeta:
• cambio del calibre de tarjeta potencia,
• cambio del tipo de tarjeta opcional o
instalación de una tarjeta opcional si
no la tenía antes y si la Macro-config
es CUS,
• pérdida de tarjeta opcional,
• configuración memorizada
incoherente.
Al pulsar ENT Donde aparece el
mensaje :
AjsFábrica? ENT/ESC

• compruebe la configuración material
del variador (tarjeta potencia entre
otras).
• interrumpa la alimentación del variador
y rearranque después.
• memorice la configuración en un
archivo de la consola.
• pulse ENT para regresar a los ajustes
de fábrica.

• la configuración enviada al variador
mediante la conexión serie es
incoherente

• compruebe la configuración
previamente enviada.
• envíe una configuración coherente.

FalloCalibre-ENT
Fallo Opción-ENT

Pérdida Opc.-ENT
CKS. EEPROM-ENT

CFI
Fallo Configurac

225

ESPAÑOL

EEF
Fallo Eeprom

GP_ATV58_ES.fm Page 226 Mardi, 2. avril 2002 6:05 18

Mantenimiento

Caso de no funcionamiento sin visualización de fallo
Causa probable

Proceso, solución

Ningún código,
pilotos apagados.

• Sin alimentación.

• Comprobar la alimentación del
variador.

Ningún código,
piloto verde
encendido, piloto
rojo apagado o
encendido

• Terminal HS.

• Cambiar el terminal.

rdY
piloto verde
encendido

• Variador en modo de línea, con tarjeta • Parametrar LI4 en forzado local y a
de comunicación o kit RS 485.
continuación validar el forzado con LI4.
• Se ha asignado una entrada LI a
• Conectar la entrada al 24 V para anular
"Parada rueda libre" o "Parada rápida",
la validación de la parada.
pero la entrada no está en tensión.
Estas paradas se controlan mediante
corte de la entrada.

ESPAÑOL

Fallo visualizado

226

GP_ATV58_ES.fm Page 227 Mardi, 2. avril 2002 6:05 18

Memorización de configuración y ajustes

Variador referencia ATV58 ............ Visualización de rEF : ..........................
N° identificación cliente opcional : ................................................................
Tarjeta opcional : no y Sí y : referencia ......................................................
Código de acceso: no y Sí y : ....................................................................
Configuración en el archivo n° ............................ del terminal de explotación
Macro-configuración : ....................................................................................
Para configuración CUS: Personalizar , asignación de las entradas/salidas:
ALTIVAR
LI 1 :
LI 2 :
LI 3 :
LI 4 :
AI 1 :
AI 2 :

Entradas lógicas

Entradas analógicas
Entrada encoder
Relé
Salida lógica
Salida analógica

Tarjeta opcional
LI 5 :
LI 6 :

AI 3 :
AI3 :

R2 :
LO :
AO :

AO1 :

Parámetros de ajuste:
Ajuste fábrica
3s
3s
0 Hz
50 / 60 Hz
20 %
20 %
Según modelo
Según modelo
0,5 s
0,5 ItH
5s
5s
0 Hz
0 Hz
0 Hz
0
1
100 %
100 %
20 %
10 Hz
15 Hz
20 Hz
25 Hz
30 Hz

Ajuste Cliente (1)
s
s
Hz
Hz
%
%
A
A
s
A
s
s
Hz
Hz
Hz
s
%
%
%
Hz
Hz
Hz
Hz
Hz

Cód.
SP7
JOG
JGt
brL
Ibr
brt
bEn
bEt
FFt
bIP
rPG
rIG
FbS
PIC
dtS
Ctd
ttd
tL2
PSP
PI2
PI3
dtd
Ftd
F2d

Ajuste fábrica
35 Hz
10 Hz
0,5 s
0 Hz
0A
0s
0 Hz
0s
50/60 Hz
non
1
1/s
1
no
1
1,36 In
100 %
200 %
0s
30 %
60 %
105 %
50/60 Hz
50/60 Hz

Ajuste Cliente (1)
Hz
Hz
s
Hz
A
s
Hz
s
Hz

ESPAÑOL

Cód.
ACC
dEC
LSP
HSP
FLG
StA
ItH
IdC
tdC
SdC
AC2
dE2
JPF
JF2
JF3
tLS
USC
UFr
SLP
PFL
SP2
SP3
SP4
SP5
SP6

/s

A
%
%
s
%
%
%
Hz
Hz

(1) indique ”nulo” cuando el parámetro esté ausente.
227

GP_ATV58_ES.fm Page 228 Mardi, 2. avril 2002 6:05 18

Memorización de configuración y ajustes

Parámetros del menú accionamiento:
Cód.
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt

Ajuste fábrica
según modelo
50 / 60 Hz
según modelo
según modelo
según modelo
no
60 / 72 Hz
no
no
no
0 Hz
STN

Ajuste Cliente (1)
V
Hz
A
rpm

Hz

Cód.
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Ajuste fábrica
LIN
4
200 %
1,36 In
Sí
1
LF
según modelo
Sí
no
DET
1024

Ajuste Cliente (1)
Hz

Cód.
AOH
Str
LCC
PSt
Add
tbr
rPr

Ajuste fábrica
20 mA
No
no
Sí
0
19200
No

Ajuste Cliente (1)
mA

Cód.
LFF
FLr
StP
Sdd
EPL

Ajuste fábrica
0 Hz
no
no
Sí
Sí

Ajuste Cliente (1)
Hz

%
A

kHz

(1) indique ”nulo” cuando el parámetro esté ausente.

Parámetros del menú CONTROL:

ESPAÑOL

Cód.
tCC
tCt
rIn
bSP
CrL
CrH
AOL

Ajuste fábrica
2W
LEL
no
no
4 mA
20 mA
0 mA

Ajuste Cliente (1)

mA
mA
mA

(1) indique ”nulo” cuando el parámetro esté ausente.

Paramètres menu défauts :
Cód.
Atr
rSt
OPL
IPL
tHt
LFL

Ajuste fábrica
no
RSP
Sí
Sí
ACL
no

Ajuste Cliente (1)

(1) indique ”nulo” cuando el parámetro esté ausente.

228

GP_ATV58_ES.fm Page 229 Mardi, 2. avril 2002 6:05 18

Resumen de menús

Menú Idioma
Leyenda
English
Français
Deutsch
Español
Italiano

Menú 2 - AJUSTES (cont.)
Cód.
LnG
LnG
LnG
LnG
LnG

Menú Macro-config
Leyenda
Hdg : Manutención
GEn : Uso General
VT : Par Variable

Cód.
CFG
CFG
CF

Menú 1 - SUPERVISIÓN
Cód.
--FrH
rFr
SPd
LCr
USP
OPr
ULn
tHr
tHd
LFt
LFr
APH
rtH

Menú 2 - AJUSTES
Leyenda
Ref. Frec. - Hz
Aceleración s
Deceleración - s
Aceleración2 - s
Decelerac2
- s
Veloc.Mínima - Hz
Veloc.Máxima - Hz
Ganancia
- %
Estabilidad
- %

Cód.
LFr
ACC
dEC
AC2
dE2
LSP
HSP
FLG
StA

Cód.
ItH
IdC
tdC
SdC
JPF
JF2
JF3
USC
tLS
UFr
SLP
SP2
SP3
SP4
SP5
SP6
SP7
Ctd
JOG
JGt
tL2
PFL
rPG
rIG
FbS
PIC
brL
Ibr
brt
bEn
bEt
FFt
bIP
dtS
Ftd
F2d
ttd
PSP
PI2
PI3
dtd

ESPAÑOL

Leyenda
Estado Var.
Ref. Frec.
Frec. Salida
Veloc. Motor
Int. Motor
Vel. accion
Pot. salida
Tensión red
Temp. Motor
Temp. Var.
ultimo fallo
Ref. Frec.
Consumo
Tiempo marcha

Leyenda
I Térmica A
I Inyecc
A
TiempoInyeccs
Icc en pared - A
Frec.Oculta.- Hz
Frec Ocult2- Hz
Freq Ocult3- Hz
Coef. accion
Temp.Vel.Mín - s
Comp. RI %
Comp.Desliza - %
Vel.Presel.2- Hz
Vel.Presel.3- Hz
Vel.Presel.4- Hz
Vel.Presel.5- Hz
Vel.Presel.6- Hz
Vel.Presel.7- Hz
Int.Alcanza - A
Jog (Hz)
- Hz
Tempo JOG
- s
Limit. par 2 - %
Perfil U/f
- %
Gan.Prop(PI)
Gan.Int (PI) -/s
Coef.Ret PI
PI inverso
AperFren(Hz)- Hz
AperFren(I)A
AperFren(t)s
CierFren(Hz)- Hz
CierFren(t)s
UmbralActiv NST- Hz
Imp. Aper. Fre
Coef.Ret.DT
Frec Alcanza- Hz
Det. Frec.2 - Hz
Temp.Alcanza- %
Filtro PI
- s
2 cons. PI
- %
3 cons. PI
- %
Umb. Tér. var.

229

GP_ATV58_ES.fm Page 230 Mardi, 2. avril 2002 6:05 18

Resumen de menús

Menú 3 - ACCIONAMIENTO

ESPAÑOL

Leyenda
U Nom. Motor - V
F Nom.MotorHz
I Nom. Motor - A
Vel.NomMotor- rpm
CosPhiMotor
Auto Ajuste
Frec.Máxima - Hz
Eco Energía
Adapt. lim I
AdaptRampDec
F.ConmRamp2 - Hz
Tipo de parada
Tipo rampa
Reducir Dec.
Limit par %
Lim.Corr.IntA
Iny CC Autom
Reducir Pot.
TipoModulado
Frec. Corte - kHz
Reducc.ruido
M.especiales
Tipo encoder
NoPulsos

Cód.
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Menú 4 - CONTROL
Leyenda
Conf.Bornero
Tipo 2 hilos
Inhibic. RV
Escalon/Huec
Ref.Mín. AI2- mA
Ref.Máx. AI2- mA
Val.min AO - mA
Val.max AO - mA
Mem.Consigna
Ctrl Consola
Prior. STOP
Direcc.Var.
BdRate RS485
Borrar Cont.

230

Cód.
tCC
tCt
rIn
bSP
CrL
CrH
AOL
AOH
Str
LCC
PSt
Add
tbr
rPr

Menú 5 - AFECTACIÓN E/S
Leyenda
Afectac LI2
Afectac LI3
Afectac LI4
Afectac LI5
Afectac LI6
NO:NO Afectado
RV :Giro Atrás
RP2:Conm.Rampa
JOG:Avance JOG
+SP: + Velocidad
-SP: - Velocidad
PS2: 2 Veloc.Pres
PS4: 4 Veloc.Pres
PS8: 8 Veloc.Pres
RFC:Conm.Refer
NST:Parada Libre
DCI:Inyecc. c.c.
FST:ParadaRápida
CHP:Commut Mot.
TL2:Limit. par 2
FLO:Forzar Local
RST:ResetDefect
ATN:Auto ajuste
PAU:AutoManu PI
PR2:2 cons. PI
PR4:4 cons. PI
TLA:Limit. de Par
EDD:Fallo Ext.
Affect R2
Affect LO
NO:No asignada
RUN:En marcha
OCC:Ctrl.Contact.
FTA:Frec. Alcanza
FLA:HSP. Alcanza
CTA:I Alcanzada
SRA:Réf. Fre. Alca
TSA:T(°C) Alcanz
BLC:LógicaFreno
APL:Pérdida 4-20 mA
F2A:Umbral F2 Alc
TAD: Est. Tér. var

Cód.
L12
L13
L14
L15
L16

r2
LO

GP_ATV58_ES.fm Page 231 Mardi, 2. avril 2002 6:05 18

Resumen de menús

Menú 5 - AFECTACIÓN E/S (cont.)
Cód.
AI2
AI3

AI3

Menú 6 - DEFECTOS
Leyenda
Rearr.Automa
Tipo Reset
CorteFaseMot
CorteFaseVar
TipoProtTérm
FalloCorte4-20mA
Fall.ret.vel
Cazar Vuelo
Paro Control
PérdidaCarga
Fallo Ext.

Cód.
Atr
rSt
OPL
IPL
tHt
LFL
LFF
FLr
StP
Sdd
EPL

Menú 7 - ARCHIVO
AO

Leyenda
Estado Arch.
Estado Arch.
Estado Arch.
Estado Arch.
Operación
Password

1
2
3
4

Cód.
FI5
F25
F35
F45
FOt
COd

Menú 8 - COMUNICACIÓN
Consulte la documentación suministrada
con la tarjeta comunicación.

ESPAÑOL

Leyenda
Affect AI2
Affect AI3
NO:NO Afectado
FR2:Ref. Vel. 2
SAI:Ref.Suma.
PIF:Retorno PI
PIM:Cons. Man. PI
SFB:Retorno DT
PTC:Sondas PTC
ATL:Lim. de par
Afectac. AI3(codif.)
NO:NO Afectado
SAI:Réf. Sommat.
RGI:Retour GI
Afectac. AO
NO:NO Afectado
OCR: Int. Motor
OFR:Frec.Motor
ORP:Salida Rampa
TRQ:Par Motor
STQ:Asig de par
ORS:Rampa señal.
OPS:Cons. PI
OPF:Retorno PI
OPE:Error PI
OPI:Integral PI
OPR:Pot. Salida
THR:Temp. Motor
THD:Temp. Var.

Menú 8 - APLICACIÓN
Consulte la documentación suministrada
con la tarjeta aplicación.

231

GP_ATV58_ES.fm Page 232 Mardi, 2. avril 2002 6:05 18

ESPAÑOL

Índice

Función

Menú

Aceleración

AJUSTES - ACCIONAMIENTO

Páginas
190-198

Adaptación automática de rampa

ACCIONAMIENTO

198

Ajuste en fábrica/Memorización

ARCHIVO

221

Atrap. Auto. (cazar al vuelo)

DEFECTOS

220

Auto Ajuste

ACCIONAMIENTO - AFECTACIÓN E/S

197-204-212

Bucle de velocidad con codific.

ACCIONAMIENTO - AFECTACIÓN E/S

195-205-205-206

Bucle de velocidad con dinamo

AJUSTES - AFECTACIÓN E/S

195-205-206-213

Código confidencial

ARCHIVO

222

Conmutación de motores

ACCIONAMIENTO - AFECTACIÓN E/S

199-204-212

Conmutación de rampas

AJUSTES - ACCIONAMIENTO - AFECT. E/S

190-198-204-206-209

Conmutación de referencias

AFECTACIÓN E/S

204-211

Contactor aguas abajo

AFECTACIÓN E/S

205-215

Control 2 hilos/3 hilos

CONTROL

201-209

Deceleración

AJUSTES - ACCIONAMIENTO

190-198

Dirección conexión serie

CONTROL

203

Economía de energía

ACCIONAMIENTO

197

Entrada analógica AI2

CONTROL

202

Entradas configurables

AFECTACIÓN E/S

204-205-206

Forzado modo local

CONTROL - AFECTACIÓN E/S

204-212

Frecuencia de corte

ACCIONAMIENTO

199

Frecuencia oculta

AJUSTES

191

Frenado por inyección

AJUSTES - ACCIONAMIENTO

191-193-199

Lim. tiempo velocidad baja

AJUSTES

191

Limitación de corriente

ACCIONAMIENTO

198-199

Limitaciones de par

AJUSTES - ACCIONAMIENTO - AFECT. E/S

193-195-199-204-206-212

Lógica de freno

AJUSTES - AFECTACIÓN E/S

194-205-206-215-216

Más rápido/menos rápido

AFECTACIÓN E/S

204-207-210

Memorización de consigna

CONTROL

203

Par estándar/alto par

IDENTIFICACIÓN (rEF)

187

Parada controlada

AFECTACIÓN E/S - DEFECTOS

204-220

Paso a paso (JOG)

AJUSTES - AFECTACIÓN E/S

193-194-204-206-209

Prioridad stop

CONTROL

203

Protección térmica motor

AJUSTES - AFECTACIÓN E/S - DEFECTOS

190-196-205-206-220

Rearranque automático

DEFECTOS

219

Regulador PI

AJUSTES - AFECTACIÓN E/S

195-205-206-213

Reinicialización de fallos

AFECTACIÓN E/S - DEFECTOS

204-207-212-219

Salidas configurables

CONTROL - AFECTACIÓN E/S

203-205-206-215-216-217

Sondas PTC

AFECTACIÓN E/S

205-213

Velocidades preseleccionadas

AJUSTES - AFECTACIÓN E/S

192-194-204-206-211

232

GP_ATV58_ES.fm Page 233 Mardi, 2. avril 2002 6:05 18

ESPAÑOL
233

GP_ATV58_Page2-IT.fm Page 234 Mardi, 2. avril 2002 6:21 18

Attenzione
Questo manuale riguarda l'impiego dei variatori Altivar 58
esclusivamente con:
- terminale di esercizio VW3A58101,
- eventuale scheda di estensione ingressi/uscite
VW3A58201 o VW3A58202.
Alcuni modi di funzionamento e menu possono essere
modificati se il variatore è dotato di altre opzioni. Consultare la documentazione relativa ad ogni specifica opzione.
Rispetto a quando è stata introdotta sul mercato, la gamma dei variatori Altivar 58 ora in commercio è dotata di
funzioni supplementari. Questo manuale tiene conto
delle modifiche apportate. Può essere tuttavia utilizzata
anche per i primi variatori, ma in questo caso si troveranno le descrizioni di parametri assenti dai primi modelli di
variatori.

ITALIANO

Per l’installazione, il collegamento, la messa in servizio e
la manutenzione, consultare la guida all'impiego dell’Altivar 58 e la guida all'impiego dell'eventuale scheda di estensione ingressi/uscite.

234

Indice

Presentazione _________________________________________________________________ 236
Consigli pratici / messa in servizio minima ____________________________________________ 239
Sblocco dei menu prima della programmazione _______________________________________ 240
Accesso ai menu _______________________________________________________________ 241
Accesso ai menu - Principio di programmazione _______________________________________ 242
Le Macro-configurazioni __________________________________________________________ 243
Identificazione Variatore __________________________________________________________ 245
Menu Visualizzazione ___________________________________________________________ 246
Menu Regolazioni ______________________________________________________________ 248
Menu Controllo _________________________________________________________________ 255
Menu Comando ________________________________________________________________ 259
Menu Configurazione degli ingressi / uscite ___________________________________________ 262
Funzioni configurabili degli ingressi e uscite __________________________________________ 266
Menu Difetti ___________________________________________________________________ 277
Menu File _____________________________________________________________________ 279
Menu Comunicazione e Applicazione/Assistenza in esercizio/Manutenzione _________________ 281
Manutenzione __________________________________________________________________ 282
Memorizzazione configurazione e regolazioni _________________________________________ 285
Sintesi dei menu ________________________________________________________________ 287
Indice ________________________________________________________________________ 290

ITALIANO
235

GP_ATV58_IT.fm Page 236 Mardi, 2. avril 2002 5:51 17

Presentazione

Il terminale di esercizio VW3A58101 è fornito con i variatori ATV58••••M2 e ATV58••••N4.
I variatori ATV58••••••Z sono forniti senza terminale che può tuttavia essere ordinato a parte.

Montaggio del terminale sul variatore:
Per montare il terminale su un variatore ATV58••••••Z, togliere per prima cosa la mascherina di protezione.

POWE
R
FAUL z
T

POWE
R
FAUL z
T

ESC
FWD
REV

ENT
RUN

STOP
RESET

Il terminale di esercizio può essere collegato e scollegato sotto tensione. Se si scollega il terminale dopo aver
validato il comando del variatore mediante terminale, il variatore si blocca segnalando un difetto SLF.

Montaggio a distanza del terminale:
Utilizzare il kit VW3A58103, comprendente 1 cavo dotato di connettori, gli elementi necessari al montaggio
sulla porta dell'armadio e le istruzioni di montaggio.

Visualizzazione sul lato frontale dell'Altivar

ITALIANO

Altri LED, visualizzazione stato variatore con schede opzioni comunicazione.

POWER z

LED verde POWER

acceso: Altivar sotto tensione

FAULT

LED rosso FAULT

• acceso: Altivar in difetto
• lampeggiante: Altivar bloccato in seguito a
pressione del tasto "STOP" del terminale o ad una
modifica della configurazione. Il motore potrà in tal
caso essere alimentato solo in seguito ad un reset
dei comandi "marcia avanti", "marcia indietro",
"arresto con iniezione di corrente".

236

GP_ATV58_IT.fm Page 237 Mardi, 2. avril 2002 5:51 17

Presentazione
☞ Prima di alimentare l’Altivar e di utilizzare il terminale:
Sbloccare ed aprire il coperchio di protezione dell’Altivar in
modo da poter accedere al commutatore 50/60 Hz 1 della
scheda di controllo. Se è presente una scheda opzionale il
commutatore resta accessibile attraverso quest'ultima.
Posizionare il commutatore su 50 o 60 Hz a seconda della
frequenza nominale del motore.
Punto di funzionamento preregolato:

1
o
50 Hz

60 Hz

Posizione 50 Hz (regolazione di base):
- 230 V 50 Hz per ATV-58••••M2
- 400 V 50 Hz per ATV-58••••N4
Posizione 60 Hz:
- 230 V 60 Hz per ATV-58••••M2
- 460 V 60 Hz per ATV-58••••N4

Il terminale di esercizio consente:
- la visualizzazione dell'identificazione del variatore, delle grandezze elettriche, dei parametri
di esercizio o dei difetti,
- la ripresa delle regolazioni e della configurazione dell’Altivar,
- il comando in locale mediante tastiera,
- la memorizzazione ed il richiamo della configurazione in una memoria non volatile del terminale.

☞ Ritorno alle regolazioni di base:
- spegnere il variatore,
- sbloccare ed aprire il coperchio di protezione dell’Altivar in modo da poter accedere al commutatore 50/
60 Hz 1 della scheda di controllo. Se é presente una scheda opzionale il commutatore resta accessibile
attraverso quest’ultima,
- cambiare la posizione del commutatore 50/60 Hz 1 della scheda di controllo,
- alimentare il variatore,
- spegnare il variatore,
- rimettere il commutatore 50/60 Hz 1 della scheda di controllo alla sua posizione iniziale (frequenza
nominale motore),
- alimentare il variatore, quest’ultimo riprenderà la sua configurazione di base.

ITALIANO
237

GP_ATV58_IT.fm Page 238 Mardi, 2. avril 2002 5:51 17

Presentazione

Vista lato anteriore

LOC

PROG

ESC
ENT
FWD
REV

Utilizzo dei tasti e significato delle visualizzazioni
 Ú
Segnalazione lampeggiante:
iindica il senso di rotazione selezionato
Segnalazione fissa:
iindica il senso di rotazione del motore
LOC
Indica il comando in locale mediante consolle
PROG Appare in modo messa in servizio e programmazione
Segnalazione lampeggiante:
iindica una modifica di valore non memorizzata
Display 4 caratteri:
visualizzazione di valori numerici e codici
Una riga da 16 caratteri:
visualizzazione in chiaro dei messaggi

STOP
RESET

RUN

Spostamento all'interno di menu o di parametri di regolazione di un valore.
ESC

Ritorno al menu precedente o uscita da una regolazione in corso e ritorno
al valore originale.

ENT

Selezione di un menu, convalida con memorizzazione di una scelta o di una regolazione.

Se è selezionato il comando mediante terminale:
FWD
REV

RUN
STOP
RESET

Inversione del senso di rotazione.
Ordine di messa in moto del motore.
Ordine di arresto del motore o reset in seguito a difetto. La funzione "STOP" del tasto può
essere inibita mediante programmazione (menu "COMANDO").

ITALIANO

Vista lato posteriore

Connettore:
- per il collegamento diretto del terminale al variatore
- per impiego a distanza, il terminale può essere collegato
con un cavo fornito con il kit VW3A58103
Commutatore di blocco accesso:

238

- posizione

: Regolazione e configurazione non accessibili

- posizione

: Regolazione accessibile

- posizione

: Regolazione e configurazione accessibili

GP_ATV58_IT.fm Page 239 Mardi, 2. avril 2002 5:51 17

Consigli pratici / messa in servizio minima

Consigli pratici:
Preparare per prima cosa la programmazione completando le schede riportate al fondo del manuale con i dati
di memorizzazione della configurazione e delle regolazioni.
La programmazione dell'Altivar 58 è assistita. Per poter usufruire di queste facilitazioni consigliamo di
accedere ai menu nell'ordine qui di seguito indicato. Ricordiamo che in ogni caso non è obbligatorio
seguire tutte le fasi.
↓ LINGUA
MACRO-CONFIG
IDENTIFICAZIONE
COMANDO (solo in caso di comando a 3 fili)
CONFIGURAZIONE I/U
COMANDO
CONTROLLO
DIFETTI
↓ COMUNICAZIONE o APPLICAZIONE nel caso in cui si utilizzi una scheda
REGOLAZIONI
ATTENZIONE: Occorre accertarsi che le funzioni programmate siano compatibili con lo schema di
collegamento utilizzato. Questa verifica è necessaria in particolare per l’ATV-58E in caso di modifica
della configurazione di base; se necessario modificare anche lo schema di collegamento.

Messa in servizio minima:
Questa procedura può essere utilizzata:
- nelle applicazioni semplici o quando vanno bene le regolazioni di base del variatore,
- nelle fasi di montaggio in cui è necessario far girare il motore provvisoriamente prima di effettuare la
messa in opera completa.

Procedura:
1 Seguire le istruzioni della guida all'impiego fornita con il variatore, posizionando naturalmente il
commutatore 50/60 Hz sulla frequenza nominale del motore.
2 Accertarsi che la macro-configurazione di base vada bene; in caso contrario modificarla all'interno del
menu «MACRO-CONFIG».
3 Per i variatori di potenza superiore a 7,5 kW a 200/240 V e 15 kW a 380/500 V in applicazione "coppia
standard", configurare la potenza nel menu «IDENTIFICAZIONE».
4 Verificare che lo schema di cablaggio sia compatibile con la macro-configurazione in modo tale da
garantire la sicurezza necessaria; in caso contrario modificare lo schema.

ITALIANO

5 Verificare nel menu «CONTROLLO» che i parametri di base siano compatibili con quelli riportati sulla
targhetta del motore; in caso contrario modificarli.
6 Effettuare un autotuning nel menu «CONTROLLO».
7 Se necessario regolare i parametri del menu «REGOLAZIONI» (rampe, I termica, ecc...).

239

GP_ATV58_IT.fm Page 240 Mardi, 2. avril 2002 5:51 17

Sblocco dei menu prima della programmazione

Livello di accesso / Modo d'impiego
La posizione del commutatore di blocco offre tre livelli di accesso ai menu in funzione dell'impiego della vostra
macchina. L'accesso ai menu può ugualmente essere bloccato con un codice di accesso (vedere menu files).
Posizione
-

Visualizzazione: utilizzare nelle fasi di esercizio.

Menu LINGUA: L'operatore può selezionare la lingua di dialogo.
Menu MACRO-CONFIG: L'operatore può visualizzare la macro-configurazione.
Menu IDENTIFICAZIONE: L'operatore può visualizzare la tensione e la potenza del variatore.
Menu VISUALIZZAZIONE: L'operatore può visualizzare delle grandezze elettriche, la fase di
funzionamento o un difetto.

Posizione

Visualizzazione e regolazioni: utilizzare nelle fasi di messa in servizio.

- L'operatore può effettuare tutte le operazioni possibili al livello 0.
- Menu REGOLAZIONI: L'operatore può regolare tutti i parametri accessibili con il motore in funzione.
Posizione

Accesso totale: utilizzare nelle fasi di programmazione.

ITALIANO

- L'operatore può effettuare tutte le operazioni possibili ai livelli 0 e 1.
- Menu MACRO-CONFIG: L'operatore può modificare la macro configurazione.
- Menu IDENTIFICAZIONE: L'operatore può modificare la potenza in "coppia standard" o "forte coppia",
per i calibri interessati da questo parametro.
- Menu CONTROLLO: L'operatore può regolare le prestazioni dell'insieme motore-variatore.
- Menu COMANDO: L'operatore può configurare il comando del variatore: mediante morsettiere, terminale
o collegamento seriale RS485 integrato.
- Menu CONFIGURAZIONE I/O: L'operatore può modificare la configurazione degli ingressi/uscite.
- Menu DIFETTI: L'operatore può configurare le protezioni motore e variatore ed il comportamento in caso
di difetto.
- Menu FILE: L'operatore può memorizzare, richiamare delle configurazioni variatore memorizzate nel
terminale, tornare alle regolazioni di base o proteggere la configurazione effettuata.
- Menu COMUNICAZIONE, l'operatore può, nel caso in cui sia installata una scheda di comunicazione,
regolare i parametri di un protocollo di comunicazione.
- Menu APPLICAZIONE, nel caso in cui sia installata una scheda «applicazione cliente». Consultare la
documentazione specifica relativa alla scheda in oggetto.

240

GP_ATV58_IT.fm Page 241 Mardi, 2. avril 2002 5:51 17

Accesso ai menu

Il numero di menu accessibili dipende dalla posizione del commutatore di blocco.
Ogni menu è composto da parametri.
1a messa
sotto tensione

LINGUA

Messe sotto tensione
successive

LnG

ESC

CFG

MACRO-CONFIG

rEF

Identificazione

0.37 kW 200/240 V

SUP

1-VISUALIZZAZIONE

SEt

2-REGOLAZIONI

drC

3-CONTROLLO

CtL

4-COMANDO

L’indicazione PROG è
visualizzata
a terminale

I-O

5-CONFIGURAZIONE I/O

FLt

6-DIFETTI

accessibile solo con scheda
«applicazione cliente»
installata

FLS

APP

8-APPLICAZIONE

ITALIANO

7-FILE

SL

8-COMUNICAZIONE

accessibile solo
con scheda protocollo
installata

ATTENZIONE: Se in precedenza è stato programmato un codice di accesso è possibile rendere inaccessibili
o anche invisibili alcuni menu. In questo caso consultare il capitolo “menu FILE” per inserire il codice di
accesso.

241

GP_ATV58_IT.fm Page 242 Mardi, 2. avril 2002 5:51 17

Accesso ai menu - Principio di programmazione

Lingua:
Questo menu è accessibile qualunque sia la posizione del commutatore e può essere modificato con variatore
fermo o in funzione.
Esempio:
ENT

LINGUA

LnG

LnG

English

LnG

Italiano

Ritorno alla selezione
precedentemente memorizzata

Memorizzazione
nuova selezione

ESC

ENT

ESC

LnG

LnG

Italiano

English

Selezione possibile: Inglese (regolazione base), Francese, Tedesco, Spagnolo, Italiano.

Principio di programmazione:
Il principio è sempre lo stesso, con 1 o 2 livelli:
• 1 livello: vedere l’esempio “lingua“ sopra riportato.
• 2 livelli: vedere l’esempio “rampa di accelerazione“ sopra riportato.
ENT

SEt

ENT

ACC

Accelerazione

2.REGOLAZIONI

3.0

s

Accelerazione

Aumento

ESC

s

(o Diminuzione)

ITALIANO

3.1

Accelerazione

ESC

Memorizzazione
del nuovo valore

Ritorno al valore
precedente

ENT

ESC

3.1

Accelerazione

242

s

s

3.0

Accelerazione

s

GP_ATV58_IT.fm Page 243 Mardi, 2. avril 2002 5:51 17

Le Macro-configurazioni

Questo parametro può essere sempre visualizzato ma è modificabile solo in modo programmazione
(commutatore di blocco in posizione
) e con motore fermo, variatore bloccato.
Consente la configurazione automatica di un'applicazione. Sono disponibili tre applicazioni.
- Movimentazione (Hdg)
- Coppia variabile per le applicazioni pompe e ventilatori (VT)
- Uso generale (GEn)
Una macro-configurazione configura automaticamente gli ingressi/uscite e i parametri, mettendo quindi in
servizio le funzioni necessarie all'applicazione. I parametri collegati alle funzioni programmate sono disponibili.

Regolazione di base: Movimentazione
Variatore:
Configurazione degli ingressi / uscite in funzione della macro-configurazione
Hdg: Movimentazione

GEn: Uso gen.

Ingresso logico LI1

marcia avanti

marcia avanti

VT: C. Variabile
marcia avanti

Ingresso logico LI2

marcia indietro

marcia indietro

marcia indietro

Ingresso logico LI3

2 velocità presel.

marcia passo-passo

commutazione riferim.

Ingresso logico LI4

4 velocità presel.

arresto ruota libera (1)

frenatura con iniez. cc

Ingresso anal. AI1

rif. sommatore

rif. sommatore

rif. velocità 1

Ingresso anal. AI2

rif. sommatore

rif. sommatore

rif. velocità 2

Relè R1

difetto variatore

difetto variatore

difetto variatore

Relè R2

Com. contatt. a valle

stato term. mot. ragg.

valore frequenza ragg.

Uscita anal. AO1

frequenza motore

frequenza motore

frequenza motore

Schede estensione:
Configurazione degli ingressi / uscite in funzione della macro-configurazione
GEn: Uso gen.

8 velocità presel.

reset difetto

VT : C. Variabile
arresto ruota libera (1)

Ingresso logico LI6

reset difetto

limitazione di coppia

commutazione rampa

Ingresso anal. AI3
o
Ingressi A, A+, B, B+

rif. sommatore

rif. sommatore

ritorno regolatore PI

ritorno velocità

ritorno velocità

ritorno velocità

Uscita logica LO

soglia corrente ragg.

Com. contatt. a valle

grande velocità ragg.

Uscita anal. AO

frequenza motore

frequenza motore

frequenza motore

ITALIANO

Hdg: Movimentazione
Ingresso logico LI5

(1) Per avviare, l'ingresso logico deve essere collegato al + 24 V (funzione attiva a 0)
ATTENZIONE: Occorre accertarsi che la macro-configurazione programmata sia compatibile
con lo schema di collegamento utilizzato. Questa verifica è necessaria in particolare per l’ATV58E equipaggiato, in caso di modifica della configurazione di base; se necessario modificare anche
lo schema di collegamento.

243

GP_ATV58_IT.fm Page 244 Mardi, 2. avril 2002 5:51 17

Le Macro-configurazioni

La modifica della macro-configurazione richiede una doppia conferma da parte dell'operatore dal
momento che implica configurazioni automatiche di alcune funzioni ed un ritorno alla regolazione di
base.
Il display visualizza la seguente videata:

CHG

VALIDARE?

ENT/ESC

ENT per confermare la modifica
ESC per tornare alla configurazione precedente

Personalizzazione della configurazione:
La configurazione del variatore può essere personalizzata modificando la configurazione degli ingressi/uscite
all'interno del menu Configurazione I/O accessibile in modo programmazione (commutatore di blocco in
posizione
).
Questo comporta la modifica del valore della macro-configurazione visualizzato:
visualizzazione di

CFG

ITALIANO

CUS:Personalizzata

244

GP_ATV58_IT.fm Page 245 Mardi, 2. avril 2002 5:51 17

Identificazione Variatore

Identificazione Variatore
Questo parametro è sempre visualizzabile. Indica la potenza e la tensione del variatore riportate sulla targhetta
segnaletica.

rEF

La potenza è indicata in kW se il commutatore 50/60 Hz del variatore è
su 50 Hz, e in HP se è su 60 Hz.

0.37 kW 200/240 V

Caso specifico dei variatori di potenza superiore a 7,5 kW a 200/240 V e 15 kW a 380/500 V:
La potenza di questi variatori è diversa a seconda che l'applicazione sia a coppia standard o a forte coppia. I
variatori sono forniti con configurazione di base a "forte coppia". La configurazione "coppia standard" si ottiene
nel modo seguente:

ENT

22 kW

rEF

rEF lampeggia
22 kW

380/500 V

rEF lampeggia

rEF
380/500 V

+30 kW

rEF
380/500 V

o ESC

ESC

ENT

+30 kW

rEF
380/500 V

+30 kW

rEF
380/500 V

ESC

In applicazione "coppia standard" il segno + precede la potenza indicata in kW.
Per tornare alla configurazione "forte coppia" ripetere lo stesso procedimento.
La configurazione "coppia standard" o "forte coppia" preconfigura la "regolazione di base" di alcuni parametri:
• menu controllo: UnS, nCr, nSP, COS, tUn
• menu regolazione: ItH, IdC
Il passaggio dalla configurazione "coppia standard" alla configurazione "forte coppia" o
viceversa, comporta un ritorno alla regolazione di base di tutti i parametri sopra indicati.

ITALIANO
245

GP_ATV58_IT.fm Page 246 Mardi, 2. avril 2002 5:51 17

Menu Visualizzazione

Menu Visualizzazione (scelta del parametro visualizzato in funzionamento)
I seguenti parametri sono accessibili con commutatore in qualsiasi posizione, con motore fermo o in funzione.
Cod.

--rdY
rUn
ACC
dEC
CLI
dCb
nSt
Obr
FrH

Descrizione

Unità

Stato var.

–

Stato del variatore: indica un difetto, o la fase di funzionamento del motore:
rdY = variatore pronto,
rUn = motore a regime stabilito o ordine di marcia presente e riferimento nullo,
ACC = accelerazione,
dEC = decelerazione,
CLI = limitazione di corrente,
dCb = frenatura con iniez. cc,
nSt = comando di arresto a ruota libera,
Obr = frenatura con adattamento della rampa di decelerazione
(vedere il menu "controllo").

Rif. Freq

Hz

Riferimento frequenza

rFr

Freq. Uscita

Hz

Frequenza di uscita applicata al motore

SPd

Velocità mot.

rpm

Velocità motore stimata dal variatore

LCr

Corrente mot.

A

Corrente motore

USP

Vel.Macchina

–

Velocità macchina stimata dal variatore. È proporzionale a rFr, in base ad un coefficiente USC
regolabile nel menu regolazione.
Questo consente di visualizzare un valore corrispondente all'applicazione (metri/secondo, ad
esempio).
Attenzione: se USP è maggiore di 9999 il valore visualizzato viene diviso per 1000.

OPr

Pot.Uscita

%

Potenza fornita dal motore, stimata dal variatore. 100 % corrisponde alla potenza nominale.

ULn

Tens. rete

V

Tensione rete

ITALIANO

tHr

Term. mot.

%

Stato termico: 100% corrisponde allo stato termico nominale del motore. Oltre il 118%, si verifica un
difetto variatore OLF (soraccarico motore)

tHd

Term. var.

%

Stato termico del variatore: 100% corrisponde allo stato termico nominale del variatore. Oltre il
118%, si verifica un difetto variatore OHF (surriscaldamento variatore). Può essere rimesso in
funzione al di sotto del 70 %.

LFt

Ultimo dif.
Visualizza l'ultimo difetto rilevato.

246

–

GP_ATV58_IT.fm Page 247 Mardi, 2. avril 2002 5:51 17

Menu Visualizzazione

Cod.

Funzione

Unità

LFr

Rif. Freq.

Hz

Questo parametro di regolazione appare al posto del parametro FrH quando viene attivato il
comando variatore mediante consolle: parametro LCC del menu comando.

APH

Consumo

kWh o MWh

Energia consumata

rtH

Tempo marcia

h

Tempo di funzionamento continuo (motore in tensione), en heures.

ITALIANO
247

GP_ATV58_IT.fm Page 248 Mardi, 2. avril 2002 5:51 17

Menu Regolazioni

Questo menu è accessibile con commutatore in posizione
e
. I parametri di regolazione
possono essere modificati con motore fermo O in funzione. Accertarsi tuttavia che i cambiamenti
effettuati in fase di funzionamento non siano pericolosi; si consiglia di effettuare le modifiche
preferibilmente a motore fermo.
La lista dei parametri di regolazione si compone di una parte fissa e di una parte variabile che evolve in
funzione:
- della macro-configurazione scelta
- della presenza o meno di una scheda di estensione ingressi/uscite
- di riconfigurazioni degli ingressi/uscite
I seguenti parametri sono accessibili in tutte le macro-configurazioni.
Cod.

Descrizione

LFr

Rif. Freq.

- Hz

Campo di regolazione

Regolazione base

da LSP a HSP

–

Appare quando viene attivato il comando variatore mediante terminale: parametro LCC del menu
comando

ACC
dEC

Accelerazione - s
Decelerazione - s

0,05 ÷ 999,9
0,05 ÷ 999,9

3s
3s

Tempi delle rampe di’accelerazione e di decelerazione
Definiti per passare da 0 alla frequenza nominale motore (FrS)

AC2
dE2

Accel. 2
Decel. 2

-

s
s

0,05 ÷ 999,9
0,05 ÷ 999,9

5s
5s

2o tempo della rampa di accelerazione
2o tempo della rampa di decelerazione
Parametri accessibili se la soglia di commutazione della rampa (parametro Frt) è diversa da 0 Hz
o se un ingresso logico è assegnato alla commutazione della rampa.

LSP

Piccola vel.- Hz

da 0 a HSP

0 Hz

da LSP a tFr

50 / 60 Hz in funzione del
commutatore

Piccola velocità

HSP

Grande vel. - Hz

Grande velocità: accertarsi che questa regolazione sia adatta al motore e all'applicazione.

FLG

Guadagno

- %

da 0 a 100

20

Guadagno anello frequenza: consente di regolare la rapidità dei transitori di velocità della macchina
in funzione della cinematica. Per le macchine a forte coppia resistente o inerzia importante, a cicli
rapidi, aumentare progressivamente il guadagno.

ITALIANO

StA

Stabilità

- %

da 0 a 100

20

Consente di adattare il raggiungimento del regime stabilito dopo un transitorio di velocità in funzione
della cinematica della macchina. Aumentare progressivamente la stabilità per eliminare la
sovravelocità.

ItH

I Termica

- A

0,25 ÷ 1,36 In (1)

In base al calibro del variatore

Corrente utilizzata per la protezione termica del motore. Regolare ItH all’intensità nominale letta
sulla targhetta del motore.
(1) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targhetta del variatore in
applicazione forte coppia.

248

GP_ATV58_IT.fm Page 249 Mardi, 2. avril 2002 5:51 17

Menu Regolazioni

Cod.

Descrizione

tdC

T Iniez.DC-

s

Campo di regolazione

Regolaz. di base

0 ÷ 30 s Cont

0,5 s

Tempo di frenatura con iniezione di corrente continua all'arresto. Se è regolato sopra i 30 s, viene
visualizzato "Cont", Iniezione dicorrente permanente all'arresto. Trascorsi i 30 secondi la corrente
d'iniezione diventa uguale a SdC.

SdC

I arresto DC

-

A

0,1 ÷ 1,36 In (1)

In base al calibro variat.

Intensità della corrente di frenatura mediante iniezione di cc applicata trascorsi i 30 secondi se
tdC = Cont.
Accertarsi che questa intensità di corrente non surriscaldi il motore.

JPF

Freq Masch.- Hz

da 0 a HSP

0 Hz

Frequenza mascherata: impedisce un funzionamento prolungato in un campo di frequenza di +/2,5Hz vicino a JPF. Questa funzione consente di eliminare una velocità critica che provoca una
risonanza.

JF2

Freq. Masch. 2 - Hz

da 0 a HSP

0 Hz

2 a frequenza mascherata: stessa funzione di JPF, per un secondo valore di frequenza.

JF3

Freq. Masch. 3 - Hz

da 0 a HSP

0 Hz

3 a frequenza mascherata: stessa funzione di JPF, per un terzo valore di frequenza.

USC

Coeff.Macchina

da 0,01 a 100

1

Coefficiente applicato al parametro rFr (frequenza di uscita applicata al motore) che consente la
visualizzazione della velocità macchina attraverso il parametro USP USP = rFr x USC

tLS

Tempo LSP

-

s

da 0 a 999.9

0 (nessuna limitazione di
tempo)

Tempo di funzionamento a piccola velocità. In seguito al funzionamento a LSP per il tempo stabilito,
l’arresto del motore è richiesto automaticamente. Il motore riparte se il riferimento frequenza è
superiore a LSP e è sempre presente un ordine di marcia. Attenzione, il valore 0 corrisponde ad un
tempo non limitato.
(1) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targhetta del variatore in
applicazione forte coppia.

ITALIANO
249

GP_ATV58_IT.fm Page 250 Mardi, 2. avril 2002 5:51 17

Menu Regolazioni

I seguenti parametri sono accessibili in macro-configurazione ‘movimentazione’
Cod.

Descrizione

UFr

Compens. RI -

%

Campo di regolazione

Regolaz. di base

da 0 a 150% o da 0 a 800%

100%

Consente di regolare il valore di default o misurato durante l'ultimo autotuning. Il campo di
regolazione è esteso a 800% se il parametro SPC (motore speciale) del menu controllo è “si”.

SLP

Comp.Scorr. -

%

da 0 a 150%

100%

Consente di regolare la compensazione di scorrimento attorno al valore fissato dalla velocità
nominale motore.

SP2

Vel.Presel.2- Hz

LSP ÷ HSP

10 Hz

LSP ÷ HSP

15 Hz

LSP ÷ HSP

20 Hz

LSP ÷ HSP

25 Hz

LSP ÷ HSP

30 Hz

LSP ÷ HSP

35 Hz

0.25 ÷ 1.36 In (1)

1.36 In (1)

2 a velocità preselezionata

SP3

Vit.Présél.3- Hz
3 a velocità preselezionata

SP4

Vel.Presel.4- Hz
4a

SP5

velocità preselezionata

Vel.Presel.5- Hz
5 a velocità preselezionata

SP6

Vel.Presel.6- Hz
6 a velocità preselezionata

SP7

Vel.Presel.7- Hz
7 a velocità preselezionata

Ctd

Rilevamento I-A

Soglia di corrente al di là della quale l'uscita logica, o il relè passa a 1

ITALIANO

(1) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targa del variatore, in
applicazione "forte coppia".

250

GP_ATV58_IT.fm Page 251 Mardi, 2. avril 2002 5:51 17

Menu Regolazioni

I seguenti parametri sono accessibili in macro-configurazione ‘uso generale’
Cod.

UFr

Descrizione

Compens. RI -

%

Campo di regolaz.

Regolaz. di base

da 0 a 150% o da 0 a 800%

100%

Consente di regolare il valore di default o misurato nell'autotuning. Il campo di regolazione è esteso
a 800% se il parametro SPC (motore speciale) del menu controllo è "si".

SLP

Comp.Scorr. -

%

da 0 a 150%

100%

Consente di regolare la compensazione di scorrimento intorno al valore fissato dalla velocità
nominale motore.

JOG

Freq. Jog

- Hz

da 0 a 10 Hz

10 Hz

Frequenza di funzionamento in marcia passo-passo

JGt

Tempo JOG

-

s

da 0 a 2 s

0.5 s

Temporizzazione di anti-ripetizione tra due comandi di marcia passo-passo consecutivi

tL2

Lim. Coppia 2- %

da 0 a 200% (1)

200%

Secondo livello di limitazione della coppia attivata da un ingresso logico
I seguenti parametri sono accessibili in macro-configurazione ‘coppia variabile’
Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

IdC

I Iniez. DC - A

da 0,10 a 1,36 In (2)

In base al calibro variatore

Intensità della corrente di frenatura con iniezione di corrente continua. Questo parametro è accessibile
se un ingresso logico è assegnato all'arresto mediante iniezione di corrente. Trascorsi i 30 secondi la
corrente di iniezione è limitata automaticamente a 0,5 Ith se regolata ad un valore superiore

PFL

Profilo U/f

- %

da 0 a 100%

20%

Consente di regolare la legge di alimentazione quadratica quando la funzione risparmio energetico
è stata inibita
(1) 100% corrisponde alla coppia nominale di un motore di potenza pari a quella associata al variatore in
applicazione forte coppia.
(2) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targa del variatore, in
applicazione "forte coppia".
I parametri su fondo grigio compaiono solo se è installata una scheda di estensione ingressi/uscite.

ITALIANO
251

GP_ATV58_IT.fm Page 252 Mardi, 2. avril 2002 5:51 17

Menu Regolazioni

È possibile accedere ai seguenti parametri in seguito alla riconfigurazione degli ingressi/uscite del prodotto base.
Cod.

Descrizione

AC2

Accel. 2

-

s

Campo di regolaz.

Regolaz. di base

0.05 ÷ 999.9

5s

2a tempo della rampa di accelerazione

dE2

Decel. 2

-

s

0.05 ÷ 999.9

5s

2a

tempo della rampa di decelerazione. Parametri accessibili se la soglia di commutazione della
rampa (parametro Frt) è diversa da 0 Hz o se un ingresso logico è assegnato alla commutazione
della rampa.

IdC

I Iniez. DC

-

A

0,10 ÷ 1,36 In (1)

In base al calibro & variatore

Intensità della corrente di frenatura mediante iniezione di corrente continua. Parametro accessibile
se un ingresso logico è assegnato all'arresto mediante iniezione di corrente. Trascorsi i 30 secondi
la corrente di iniezione è limitata automaticamente a 0,5 Ith se regolata ad un valore superiore.

SP2

Vel.Presel.2- Hz
2a

SP3

LSP ÷ HSP

10 Hz

LSP ÷ HSP

15 Hz

LSP ÷ HSP

20 Hz

LSP ÷ HSP

25 Hz

LSP ÷ HSP

30 Hz

LSP ÷ HSP

35 Hz

da 0 a 10 Hz

10 Hz

velocità preselezionata

Vel.Presel.3- Hz
3a velocità preselezionata

SP4

Vel.Presel.4- Hz
4a velocità preselezionata

SP5

Vel.Presel.5- Hz
5a velocità preselezionata

SP6

Vel.Presel.6- Hz
6a

SP7

velocità preselezionata

Vel.Presel.7- Hz
7a velocità preselezionata

JOG

Freq. Jog

- Hz

Frequenza di funzionamento in marcia passo-passo

JGt

Tempo JOG

-

s

da 0 a 2 s

0.5 s

Temporizzazione d'anti-ripetizione tra due comandi consecutivi di marcia passo-passo

brL

F.Apert.Freno Hz

da 0 a 10 Hz

0 Hz

0 ÷ 1,36 In(1)

0A

da 0 a 5 s

0s

da 0 a LSP

0 Hz

da 0 a 5 s

0s

ITALIANO

Frequenza di apertura del freno

Ibr

I Apert.Freno-

A

Corrente di apertura del freno

brt

T.Apert.Freno-

s

Tempo di apertura del freno

bEn

F.Chius.Freno- Hz
Frequenza di chiusura del freno

bEt

T.Chius.Freno- Hz
Tempo di chiusura del freno

(1) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targa del variatore, in
applicazione "forte coppia".

252

GP_ATV58_IT.fm Page 253 Mardi, 2. avril 2002 5:51 17

Menu Regolazioni

Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

FFt

Sogliaint NST- Hz

da 0 a HSP

0 Hz

Soglia di intervento arresto ruota libera: in caso di comando di arresto su rampa o di arresto rapido il tipo
di arresto selezionato rimane attivo fino a quando la velocità torna al di sotto di questa soglia. Al di sotto
di tale soglia viene attivato l’arresto a ruota libera. Parametro accessibile se il relè è attivato. Parametro
accessibile se il relè R2 non è assegnato alla funzione BLC : logica di comando freno e se il tipo di
arresto è posizionato su "rampa" o "rapido" nel menu di controllo.

bIP

Imp. Liv. Freno

no-SI

no

Impulso di apertura del freno
SI : la coppia durante il tempo di apertura del freno è sempre nel senso FW (avanti) qualunque sia
il senso di rotazione richiesto
Verificare che il senso della coppia motore in comando FW (avanti) corrisponda al verso di
salita del carico; se necessario invertire le due fasi del motore.
no : la coppia durante il tempo di apertura del freno è sempre nel senso di rotazione richiesto

dtS

Coeff. Rit. DT

da 1 a 2

1

Coefficiente moltiplicatore associato alla funzione ritorno dinamo tachimetrica:
dtS =

rPG

9
tensione dinamo a velocità max

Guad. Prop.PI

0.01 ÷ 100

1

Guadagno proporzionale del regolatore PI

rIG

Guad. Int. PI

0.01 ÷ 100 /s

1 /s

Guadagno integrale del regolatore PI

FbS

Coeff. Rit. PI

1 ÷ 100

1

Coefficiente moltiplicatore del ritorno PI

PIC

Inversione PI

no - si

no

Inversione del senso di correzione del regolatore PI
no: normale
si: inverso

Ftd

Rilev.Freq. - Hz

LSP ÷ HSP

50/60 Hz

Soglia di frequenza motore oltre la quale l'uscita logica passa a 1

F2d

Dèt.Frèq.2 I

- Hz

LSP ÷ HSP

50/60 Hz

2 e seuil de fréquence : même fonction que Ftd, pour une 2 e valeur de fréquence

Ctd

Rilevam. I -

A

da 0 a 1.36 In (1)

1.36 In (1)

ttd

Rilev.Term.

%

da 0 a 118%

ITALIANO

Soglia di corrente oltre la quale l'uscita logica o il relè passa a 1
100%

Soglia dello stato termico motore oltre la quale l'uscita logica o il relè passa a 1

tL2

Lim. Coppia 2 - %

da 0 a 200% (2)

200%

Secondo livello di limitazione coppia attivato da un ingresso logico
(1) 100% corrisponde alla coppia nominale di un motore di potenza pari a quella associata al variatore in
applicazione forte coppia.
(2) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targa del variatore, in
applicazione "forte coppia".
I parametri su fondo grigio compaiono solo se è installata una scheda di estensione ingressi/uscite.
253

GP_ATV58_IT.fm Page 254 Mardi, 2. avril 2002 5:51 17

Menu Regolazioni

Cod.

Descrizione

PSP

Filtro PI

- s

Campo di regolaz.

Regolaz. di base

da 0,0 a 10,0

0s

Permette di regolare la costante di tempo del filtro sul ritorno PI

PI2

Rif. PI2

- %

da 0 a 100 %

30 %

2a riferimento preselezionato del regolatore PI, quando un ingresso logico è stato assegnato alla
funzione 4 riferimenti PI preselezionati..
100 % = max processo 0 % = min processo

PI3

Rif. PI3

- %

da 0 a 100 %

60 %

3a riferimento preselezionato del regolatore PI, quando un ingresso logico è stato assegnato alla
funzione 4 riferimenti PI preselezionati
100 % = max processo
0 % = min processo

dtd

Rilev. Term. var.

da 0 a 118 %

105 %

ITALIANO

Soglia dello stato termico del variatore al di là della quale l’uscita logica o il relè passa a 1.

254

GP_ATV58_IT.fm Page 255 Mardi, 2. avril 2002 5:51 17

Menu Controllo

Questo menu è accessibile con commutatore in posizione
.
I parametri possono essere modificati solo a motore fermo, variatore bloccato.
L’ottimizzazione delle prestazioni di controllo si ottiene:
- inserendo nel menu di controllo i valori indicati sulla targa del motore,
- avviando un auto-tuning (su un motore asincrono standard).
In caso d’impiego di motori speciali (motori in parallelo, motori a rotore conico o a derivazione di flusso,
motori sincroni o asincroni sincronizzati, motori asincroni a rotore resistente):
- Selezionare la macro-configurazione “Hdg: Movimentazione” o la macro-configurazione “GEn: Uso gen.”
- Configurare nel menu controllo il parametro Motore speciale “SPC” selezionando “si”.
- Nel menu regolazione impostare il parametro Compens. RI “UFr” per ottenere un funzionamento
soddisfacente.
Cod.

Descrizione

UnS

U Nom. Mot. -

V

Campo di regolaz.

Regolaz. di base

200 ÷ 240 V
200 ÷ 500 V

230 V (2)
400/460V (2)

Tensione nominale motore indicata sulla targa del motore. Il campo di regolazione dipende dal
modello di variatore:
ATV58••••M2
ATV58••••N4

FrS

Freq.Nom.Mot- Hz

da 10 a 500 Hz

50/60Hz (2)

Frequenza nominale motore indicata sulla targa del motore

nCr

I Nom. Mot

-

A

da 0.25 a 1.36 In (1)

in base al calibro variatore

Corrente nominale motore indicata sulla targa del motore

nSP

Vel.Nom.Mot -rpm

da 0 a 9999 rpm

in base al calibro variatore

Velocità nominale motore indicata sulla targa del motore

COS

Cos Phi Mot

da 0.5 a 1

in base al calibro variatore

Coseno Phi motore indicato sulal targa del motore

tUn

Auto-tuning

no - si

no

Consente di autoregolare il comando del motore dopo aver impostato questo parametro su “si”.
Una volta effettuato l'auto-tuning il parametro torna automaticamente su “eseguito”, o visualizza “no“
in caso di difetto.
Attenzione: l'auto-tuning si effettua solo se non è azionato alcun comando . Se ad un ingresso logico
è assegnata una funzione "arresto ruota libera" o "arresto rapido", è necessario mettere a 1
l'ingresso (attivo a 0).

tFr

Freq. Max

- Hz

40 ÷ 500 Hz

60/72Hz (2)

nLd

Risp. Energet.

no-si

ITALIANO

Frequenza massima di uscita. Il valore max dipende dalla frequenza di commutazione.
si

Ottimizza il rendimento del motore.
Accessibile solo in macro-configurazione coppia variabile.
(1) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targa del variatore, in
applicazione "forte coppia".
(2) in base alla posiz. del commutat. 50/60Hz

255

GP_ATV58_IT.fm Page 256 Mardi, 2. avril 2002 5:51 17

Menu Controllo

Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

Fdb

Adatt. I lim.

no-si

no

Adattamento della corrente di limitazione in funzione della frequenza di uscita.
Parametro che appare solo in macro-configurazione coppia variabile" VT (applicazioni di
ventilazione in cui la curva di carico evolve in funzione della densità del gas).

brA

Adatt.Rampa Dec.

no-si

no

L’attivazione di questa funzione consente di aumentare automaticamente il tempo di decelerazione,
se questo è stato impostato su un valore troppo basso tenuto conto dell'inerzia del carico, evitando
in tal modo il verificarsi del difetto ObF.
Questa funzione può essere incompatibile con un posizionamento su rampa e con l'utilizzo di una
resistenza di frenatura.
La regolazione di base dipende dalla macro-configurazione utilizzata: no in movimentazione, si per
coppia variabile e uso generale.
Se il relè R2 è assegnato alla funzione logica freno, il parametro brA resta bloccato in posizione no.

Frt

F.Comm.Rampa2- Hz

da 0 a HSP

0 Hz

Frequenza di commutazione rampa. Quando la frequenza di uscita supera Frt, i tempi di rampa
acquisiti sono AC2 e dE2.

Stt

Tipo arresto

STN - FST - NST - DCI

STN

Tipo di arresto.
Al comando di arresto il tipo di arresto viene attivato fino alla soglia FFt (menu regolazione). Al di
sotto della soglia l’arresto avviene a ruota libera.
STN: su rampa
FST: arresto rapido
NST: arresto ruota libera
DCI: arresto mediante iniezione di corrente continua.
Parametro accessibile solo se il relè R2 è assegnato alla funzione BLC: logica di comando freno.

rPt

Tipo Rampa

LIN - S - U

LIN

Definisce il funzionamento delle rampe di accelerazione e di decelerazione.
LIN: lineare S: a S U: a U
f (Hz)

f (Hz)

GV

GV

Il coefficiente di arrotondamento
è fisso con t2 = 0,6 x t1 e
con t1 = tempo di rampa regolato.

Rampe a S
0

t

t2

0

ITALIANO

t

t2

t1

t1

f (Hz)

f (Hz)

GV

GV

Il coefficiente di arrotondamento
è fisso con t2 = 0,5 x t1 e
con t1 = tempo di rampa regolato.

Rampe a U

0
t2

t

0

t1

dCF

Coeff.RampaDEC

t2

t

t1

da 1 a 10

4

Coefficiente di riduzione del tempo della rampa di decelerazione quando è attiva la funzione arresto
rapido.

256

GP_ATV58_IT.fm Page 257 Mardi, 2. avril 2002 5:51 17

Menu Controllo

Cod.

Descrizione

tLI

Lim. Coppia

_ %

Campo di regolaz.

Regolaz. di base

da 0 a 200% (1)

200%

La limitazione di coppia consente di limitare la coppia massima del motore.

CLI

ILim.interna - A

0 ÷ 1,36 In (2)

1,36 In

La limitazione di corrente consente di limitare il riscaldamento del motore.

AdC

Iniez. DC Auto

no-si

si

Consente di disattivare la frenatura mediante iniezione di corrente automatica all'arresto

PCC

Coeff. P mot.

da 0.2 a 1

1

Definisce il rapporto tra la potenza nominale del variatore ed il motore di potenza minore quando un
ingresso logico è assegnato alla funzione di commutazione dei motori.
Tipo
Commut.
SFt
LF-HF1-HF2
LF
Consente di selezionare una commutazione a bassa (LF) o alta frequenza (HF1 o HF2).
La commutazione HF1 è destinata alle applicazioni a fattore di marcia ridotto senza declassamento
del variatore. Se lo stato termico del variatore supera il 95 %, la frequenza passa automaticamente
a 2 o 4 kHz a seconda del calibro del variatore. Quando lo stato termico del variatore ridiscende al
70 %, viene ripristinata la frequenza di commutazione scelta. La commutazione HF2 è destinata alle
applicazioni a fattore di marcia elevato con declassamento del variatore di un calibro: i parametri di
controllo vengono messi in scala automaticamente (limitazione di coppia, corrente termica, ecc...).
La modifica di questo parametro provoca il ritorno dei parametri alla regolazione di
base:
• nCr, CLI, Sfr, nrd (menu Controllo)
• ItH, IdC, Ibr, Ctd (menu Regolazioni)

SFr

Freq.Commut.kHz

0.5-1-2-4-8-12-16 kHz

In base al calibro variatore

Consente di selezionare la frequenza di commutazione. Il campo di regolazione dipende dal
parametro SFt.
Se SFt = LF: da 0,5 a 2 o 4 kHz in base al calibro del variatore
Se SFt = HF1 o HF2: da 2 o 4 a 16 kHz in base al calibro del variatore
La frequenza massima di funzionamento (tFr) è limitata in base alla frequenza di commutazione:

nrd

SFr(kHz)

0.5

1

2

4

8

12

16

tFr (Hz)

62

125

250

500

500

500

500

Riduz. Rumore

no-si

(3)

Questa funzione modula in modo aleatorio la frequenza di taglio per ridurre il rumore motore

SPC

Motore Speciale

no-si-PSM

no

(1) 100% corrisponde alla coppia nominale di un motore di potenza pari a quella associata al variatore in
applicazione forte coppia.
(2) In corrisponde alla corrente nominale variatore indicata nel catalogo e sulla targa del variatore, in
applicazione "forte coppia".
(3) si se SFt = LF, no se SFt = HF1 oppure HF2

257

ITALIANO

Questa funzione impostata su SI estende la gamma di regolazione del parametro UFr del menu
regolazione per permetterne l’adattamento ai motori speciali indicati all’inizio del capitolo.
PSM: inibisce la funzione di rilevamento "Interruzione a valle non controllata" (utile soprattutto per
i motori di piccolo calibro).
No: motore normale
Si: motore speciale
PSM: motore di piccolo calibro

GP_ATV58_IT.fm Page 258 Mardi, 2. avril 2002 5:51 17

Menu Controllo

Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

PGt

Tipo di GI

INC-DET

DET

Definisce il tipo di trasduttore utilizzato in caso d'installazione di una scheda I/O ritorno encoder:
INC: encoder incrementale (A, A+, B, B+ sono collegati)
DET: sensore (solo A è collegato)

PLS

N° Impulsi

da 1 a 1024

1024

Definisce il numero d’impulsi/giro del trasduttore.

ITALIANO

I parametri su fondo grigio compaiono solo se è installata una scheda di estensione ingressi/uscite

258

GP_ATV58_IT.fm Page 259 Mardi, 2. avril 2002 5:51 17

Menu Comando

Queso menu è accessibile con commutatore in posizione
motore fermo, variatore bloccato.

I parametri possono essere modificati solo con

Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

tCC

Conf. Morsett.

2W- 3W (2 fili - 3 fili)

2W

Configurazione del comando morsettiera: comando 2 fili o 3 fili.
La modifica di questo parametro richiede una doppia conferma dal momento che provoca
una riconfigurazione degli ingressi logici. Tra il comando 2 fili ed il comando 3 fili, le
configurazioni degli ingressi logici sono scalate di un ingresso. La configurazione di LI3 a 2
fili diventa la configurazione di LI4 in comando a 3 fili. In comando a 3 fili, gli ingressi LI1 e LI2 non
sono riconfigurabili.
E/S

Movimentazione

Uso generale

LI1

STOP

STOP

Coppia variabile
STOP

LI2

RUN avanti

RUN avanti

RUN avanti

LI3

RUN indietro

RUN indietro

RUN indietro

LI4

2 velocità presel

marcia passo-passo

Commut. di rif.

LI5

4 velocità presel.

arresto ruota libera

frenat. con iniez. cc

LI6

8 velocità presel.

reset difetti

arresto ruota libera

Gli ingressi/uscite su fondo grigio sono accessibili solo nel caso in cui sia installata una scheda I/O.
Comando 3 fili (Comando ad impulsi: un impulso è sufficiente a comandare l'avviamento). Questa
selezione disattiva la funzione "riavviamento automatico".
Esempio di collegamento:
Morsettiera di controllo ATV58
LI1 : stop
24 V LI1 LI2 LIx
LI2 : marcia avanti
LIx : marcia indietro

Questa possiblità di selezione appare solo in caso di configurazione comando a 2 fili.
Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

tCt

Tipo 2 fili

LEL-TRN-PFo

LEL

I parametri su fondo grigio compaiono solo se è installata una scheda di estensione ingressi/uscite.

259

ITALIANO

Definisce il tipo di comando a 2 fili:
- in funzione dello stato degli ingressi logici (LEL: Rilevam. Liv.)
- in funzione di un cambiamento di stato degli ingressi logici (TRN: Rilevam. Tras.)
- in funzione dello stato degli ingressi logici con marcia avanti sempre prioritaria sulla marcia
indietro (PFo: Priorit. FW)
Esempio di cablaggio:
Morsettiera controllo ATV58
LI1 : marcia avanti
24 V LI1 LIx
LIx : marcia indietro

GP_ATV58_IT.fm Page 260 Mardi, 2. avril 2002 5:51 17

Menu Comando

Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

rln

Inib. RV

no-si

no

• Inibizione della marcia in senso inverso rispetto al senso comandato dagli ingressi logici, anche se
l'inversione è richiesta da una funzione sommatore o regolazione
• Inibizione della marcia indietro nel caso in cui questa sia comandata con il tasto FWD/REV del
terminale

bSP

Livell./Azzer.

no
BNS:Azzeram.
BLS:Livell.

no

Gestione del funzionamento a bassa velocità:
F : frequenza motore

F : frequenza motore

HSP

HSP
No

LSP

LSP
Riferimento

0

0

Azzeramento
(BNS)
Riferimento
100 %

100 %
F : frequenza motore
HSP
Livellamento
(BLS)

LSP

Riferimento

0

100 %

CrL
CrH

Rif.Min. AI2 - mA
Rif.Max AI2 - mA

0 ÷ 20 mA
4 ÷ 20 mA

4 mA
20 mA

Valore min. del segnale sull’ingresso AI2
Valore max del segnale sull’ingresso AI2 Questi due parametri consentono di definire il segnale
trasmesso su AI2. Tra le altre, possibilità di configurare l’ingresso per un segnale 0-20 mA, 4-20 mA,
20-4mA ...
Frequenza

ITALIANO

HSP

LSP
0
CrL

260

CrH

20

AI 2
(mA)

GP_ATV58_IT.fm Page 261 Mardi, 2. avril 2002 5:51 17

Menu Comando

Cod.

Descrizione

Campo di regolaz.

Regolaz. di base

AOL
AOH

Val.Min. AO - mA
Val.Max AO - mA

0 ÷ 20 mA
0 ÷ 20 mA

0 mA
20 mA

Valore minimo del segnale sull'uscita AO e AO1 (1)
Valore massimo del segnale sull'uscitaAO
Questi due parametri consentono di definire il segnale di uscita su
AO e AO1.
Es.: 0-20 mA, 4-20 mA, 20-4mA ...

Parametro
Max

AO (mA)

0
AOL

Str

AOH

Mem.Riferimento

20

NO-RAM-EEP

NO

Associata alla funzione +veloce/-veloce questa funzione consente di memorizzare il valore
impostato: alla scomparsa dei comandi di marcia (memorizzazione in RAM) o in caso d'interruzione
della rete di alimentazione (memorizz. in EEPROM) All'avviamento successivo il riferimento di
velocità è l'ultimo valore memorizzato.

LCC

Com.Terminale

No-Si

No

Consente di attivare il comando del variatore mediante terminale. I tasti STOP/RESET, RUN e
FWD/REV sono attivi. Il riferimento di velocità è dato dal parametro LFr. Solo gli ordini di arresto
ruota libera, arresto rapido e arresto con iniezione di cc restano attivi da morsettiera. Se il
collegamento variatore/terminale viene interrotto, il variatore si blocca in difetto SLF.

PSt

Prior. STOP

No-Si

Si

Questa funzione dà priorità al tasto STOP qualunque sia il canale di comando (morsettiera o bus di
campo).
Per impostare il parametro PSt su "no":
1 - visualizzare "no"
2 - premere il tasto "ENT"
3 - il variatore visualizza "Vedere manuale"
4 - premere su ▲ quindi su ▼ e infine il tasto "ENT"
Per le applicazioni con "processi" continui si consiglia di disattivare il tasto (regolazione su "no")

Add

Indirizzo Var.

da 0 a 31

0

Indirizzo del variatore quando questo è comandato tramite collegamento della presa terminale
(eccetto terminale di esercizio e terminale di programmazione)

tbr

Reset cpts

No-APH-RTH

No

Azzeramento (reset) dei kWh o del tempo di funzionamento.
No
APH: reset dei kWh
RTH: reset del tempo di funzionamento.
Confermare il comando di reset con il tasto "ENT".
Le azioni di APH e RTH sono immediate, quindi il parametro torna automaticamente in posizione No
(1) L’uscita AO appare solo se é installata una scheda di estensione I/O.
261

ITALIANO

rPr

BdRate RS485
9600-19200
19200
Velocità di trasmissione tramite collegamento seriale RS485 (elaborazione alla messa sotto tensione
successiva)
9600 bit/secondo
19200 bit/secondo
Se tbr ≠ 19200, l ’utilizzo del terminale non è più possibile . Per riattivare nuovamente
il terminale riconfigurare tbr a 19200 tramite collegamento seriale o ripristinare le
preregolazioni di base ( vedere pagina 5 ).

GP_ATV58_IT.fm Page 262 Mardi, 2. avril 2002 5:51 17

Menu Configurazione degli ingressi / uscite

Questo menu è accessibile con commutatore in posizione
.
Le configurazioni possono essere modificate solo con motore fermo e variatore bloccato.
Cod.

Descrizione

LI2

Config.

LI2

Vedere tabella riassuntiva e descrizione delle funzioni.
Gli ingressi e uscite proposti nel menu dipendono dalle evtuali schede I/O installate nel variatore, oltre che dalle
scelte effettuate all'interno del menu comando.
Le configurazioni ”base” sonono preassegnate dalla macro-configurazione selezionata.

Tabella riassuntiva delle configurazioni degli ingressi (tranne scelta comando 2 fili / 3 fili)
Schede opzionali estensione I / O

2 ingressi logici LI5-LI6

Variatore senza opzioni

NO:Non configur.
RV: Indietro

(Non configurata)

X

(Marcia indietro)

X

RP2:Comm. Rampa

(Commutazione rampa)

X

JOG:JOG Impuls.

(Marcia passo-passo)

X

+SP: + veloce

(Più veloce)

X

-SP: - Veloce

(Meno veloce)

X

PS2: 2Vel.Presel.

(2 velocità preselezionate)

X

PS4: 4Vel.Presel.

(4 velocità preselezionate)

X

PS8: 8Vel.Presel.

(8 velocità preselezionate)

X

RFC:Commut. Rif.

(Commutazione riferimenti)

X

(Arresto ruota libera)

X

(Arresto con iniezione cc)

X

FST:Arr. rapido

(Arresto rapido)

X

CHP:Commut Mot.

(Commutazione motori)

X

TL2:Lim.Coppia 2

(Seconda limitazione di coppia)

X

FLO:Forzat. Loc.

(Forzatura locale)

X

RST:Reset Difetti

(Reset dei difetti)

X

NST:StpRuotaLibera
DCI:Arr.Iniez.DC

ITALIANO

3 ingressi logici da LI2 a LI4

ATN:Auto-tuning
PAU:AutoMan PI
PR2:2Rif.

PI

PR4:4Rif.

PI

(Auto-tuning)

X

(Auto - man PI) Se unAI = PIF

X

(2 riferimenti PI preselezionati) Se un AI = PIF

X

(4 riferimenti PI preselezionati) Se un AI = PIF

X

TLA:LimitCoppia

(Limitazione di coppia tramite AI) Se un AI = ATL

X

EDD:Dif.esterno

(difetto esterno)

X

ATTENZIONE: Se un ingresso logico è assegnato alla funzione "Arresto ruota libera" o "Arresto
rapido" l’avviamento può avvenire solamente collegando l’ingresso al +24V, dal momento che le
funzioni di arresto sono attive solo quando gli ingressi sono a 0.

262

GP_ATV58_IT.fm Page 263 Mardi, 2. avril 2002 5:51 17

Menu Configurazione degli ingressi / uscite

Tabella riassuntiva delle configurazioni degli ingressi analogici e encoder
Schede opzionali estensione I / O

Variatore senza opzioni

SAI:Rif. Sommat.

Ingresso
encoder (1)
A+, A-,
B+, B-

X

X

X

Ingresso
analogico
AI2

NO:Non config.
FR2:Rif. Vel. 2

Ingresso
analogico
AI3

(Non configurata)

X

(Riferimento velocità 2)
Se une LI = RFC

X

(Riferimento sommatore)

X

X

PIF:Ritorno PI

(Ritorno del regolatore Pl)

X

X

PIM:Rif Man PI

(Riferimento velocità manuale PI)
Se une AI = PIF e une LI = PAU

SFB:Ritorno DT

(Dinamo tachimetrica)

X

(Sonde PTC)

X

ATL:Lim.Coppia

(Limitazione di coppia)

X

RGI:Ritorno GI

(Ritorno encoder o rilevatore)

PTC:Sonde PTC

X

X

(1) NB: Il menu di configurazione dell'ingresso encoder A+, A-, B+, B- è il menu "Configurazione AI3".
ATTENZIONE: Se il relè R2 è assegnato alla funzione "logica freno", AI3 è assegnato
automaticamente in regolazione base al Ritorno DT, sempre che sia installata la scheda. Resta
comunque possibile riconfigurare AI3.

Tabella riassuntiva delle configurazioni delle uscite logiche
Scheda opzionale estensione I / O

Uscita
logica LO

Variatore senza scheda opzionale

NO:Non config.

Relè R2
X

X

X

X

OCC:Cdo Contatt.

(Comando contattore a valle)

X

X

FTA:Soglia F.Ragg.

(Soglia frequenza raggiunta)

X

X

(HSP raggiunta)

X

X

(Soglia corrente raggiunta)

X

X

FLA:HSP Raggiunta
CTA:Soglia I Ragg.
SRA:Rif.Vel.Ragg.
TSA:SogliaTerm.Ragg.

BLC:Logica Freno
APL:Inter.4-20 mA
F2A:Soglia F2 rag.
tAd:All.ter.var.

(Riferimento frequenza raggiunta)

X

X

(Soglia termica reggiunta)

X

X

(Logica freno)

X

(Interruzione 4 / 20 mA)

X

X

(2 °soglia di frequenza raggiunta)

X

X

(Soglia termica variatore raggiunta)

X

X

ITALIANO

(Non configurata)
(Variatore in marcia)

RUN:Var.In Marcia

263

GP_ATV58_IT.fm Page 264 Mardi, 2. avril 2002 5:51 17

Menu Configurazione degli ingressi / uscite

Tabella riassuntiva delle configurazioni delle uscite analogiche
Scheda opzionale estensione I / O

Uscita analogico AO

Variatore senza scheda opzionale

Uscita analogico AO1

NO:Non config.

(Non configurata)

X

OCR:Corrente Mot.

(Corrente motore)

X

OFR:Freq. Mot.

(Velocità motore)

X

(Uscita rampa)

X

(Coppia motore)

X

STQ:Coppia con segno

(Coppia motore con segno)

X

ORS:Rampa con segno

(Uscita rampa con segno)

X

(Uscita PI) Se un ingresso AI = PIF

X

ORP:Uscita Rampa
TRQ:Coppia mot.

OPS:Rif PI
OPF:Ritorno PI

(Uscita ritorno PI) Se un ingresso AI = PIF

X

OPE:Errore PI

(Uscita errore PI) Se un ingresso AI = PIF

X

OPI:Integ PI

(Uscita integrale PI) Se un ingresso AI = PIF

X

(Potenza motore)

X

(Stato termico motore)

X

(Stato termico variatore)

X

OPR:Potenza Motore
THR:Stato Motore
THD:Stato Var.

In seguito alla riconfigurazione di un ingresso/uscita, i parametri legati alla funzione appaiono
automaticamente all'interno dei menu e la macro-configurazione indica “CUS: personalizzata“.
Alcune riconfigurazioni mostrano nuovi parametri di regolazione che non bisogna tralasciare di
regolare nel menu regolazione:

ITALIANO

I/O

Configurazioni

Parametri da regolare

Commutazione di rampa

AC2 dE2

JOG

Marcia passo-passo

JOG JGt

PS4

4 velocità preselezionate

SP2-SP3

LI

PS8

8 velocità preselezionate

SP4-SP5-SP6-SP7

LI

DCI

Arresto con iniezione di cc

IdC

LI

TL2

Seconda limitazione di coppia

tL2

LI

PR4

4 consignes PI présélectionnées

PI2-PI3

AI

PIF

Regolatore PI

rPG-rIG-PIC-rdG-rED-PrGPSr-PSP-PLr-PLb

LI

RP2

LI
LI

AI

SFB

Dinamo tachimetrica

dtS

R2

BLC

Logica freno

Ibr-brt-bEn-bEt-brL-bIP

LO/R2

FTA

Soglia Frequenza raggiunta

Ftd

LO/R2

CTA

Soglia Corrente raggiunta

Ctd

LO/R2

TSA

Soglia Termica raggiunta

ttd

LO/R2

F2A

2 e seuil Fréquence atteint

F2d

LO/R2

TAD

Seuil Thermique variateur atteint

dtd

264

GP_ATV58_IT.fm Page 265 Mardi, 2. avril 2002 5:51 17

Menu Configurazione degli ingressi / uscite

Alcune riconfigurazioni mostrano nuovi parametri che non bisogna tralasciare di regolare nel menu
comando, controllo o difetto:
I/O

Configurazioni

Parametri da regolare

LI

-SP

Meno veloce

Str (menu comando)

LI

FST

Arresto rapido

dCF (menu controllo)

LI

RST

Reset difetti

rSt (menu difetti)

AI

SFB

Dinamo tachimetrica

Sdd (menu difetti)

A+, A-,
B+, B-

SAI

Riferimento sommatore

PGt, PLS (menu controllo)

A+, A-,
B+, B-

RGI

Ritorno GI

PGt, PLS (menu controllo)

ITALIANO
265

GP_ATV58_IT.fm Page 266 Mardi, 2. avril 2002 5:51 17

Funzioni configurabili degli ingressi e uscite
Tabella di compatibilità delle funzioni

Limitazione di coppia mediante LI

Limitazione di coppia mediante AI3

Regolazione di velocità con
dinamo tachimetrica o encoder

Velocità preselezionate

Marcia passo-passo

Arresto rapido

Arresto ruota libera

➞

Frenatura con iniezione
di corrente continua

Commutazione dei riferimenti

Più veloce / meno veloce

Regolatore PI

Ingressi sommatori

Frenatura con iniezione
di corrente continua

La scelta delle funzioni da configurare può essere limitata dall'incompatibilità di alcune funzioni tra loro. Le
funzioni non presenti in questa tabella non sono oggetto di incompatibilità.

Ingressi sommatori
Regolatore PI

➞

Più veloce / meno veloce
Commutazione dei riferimenti
Arresto ruota libera

➞

➞

Arresto rapido
Marcia passo-passo

➞

➞

Velocità preselezionate

➞
➞

Regolazione di velocità con
dinamo tachimetrica o encoder
Limitazione di coppia mediante AI3
Limitazione di coppia mediante LI

Funzioni incompatibili

Non previsto
Funzioni prioritarie (funzioni che non possono essere attive contemporaneamente):

➞

➞

ITALIANO

Funzioni compatibili

La funzione indicata dalla punta della freccia ha priorità sull'altra.

Le funzioni di arresto hanno priorità sugli ordini di marcia.
I riferimenti di velocità mediante ordine logico hanno priorità sui riferimenti analogici.

266

GP_ATV58_IT.fm Page 267 Mardi, 2. avril 2002 5:51 17

Funzioni configurabili degli ingressi e uscite
Funzioni degli ingressi logici
Senso di marcia: avanti / indietro
La marcia indietro può essere eliminata in caso di applicazioni ad un solo senso di rotazione del motore.
Comando a 2 fili:
La marcia (avanti o indietro) e l’arresto sono comandati dallo stesso ingresso logico, dal momento che viene
tenuto conto dello stato a 1 (marcia) o a 0 (arresto), o del cambiamento di stato (vedere menu comando a 2 fili).
Comando a 3 fili:
La marcia (avanti o indietro) e l’arresto sono comandati da 2 ingressi logici diversi.
LI1 è sempre assegnato alla funzione di arresto. L’arresto è ottenuto all'apertura (stato 0).
L’impulso sull’ingresso marcia viene memorizzato fino all'apertura dell’ingresso arresto.
Alla messa sotto tensione o in caso di reset manuale o automatico dei difetti, il motore può essere alimentato
solo dopo in seguito al reset dei comandi "avanti", "indietro", "arresto con iniezione di cc".
Commutazione di rampa: 1a rampa: ACC, DEC ; 2a rampa: AC2, DE2
Sono possibili 2 casi di attivazione:
- mediante attivazione di un ingresso logico LIx
- mediante rilevamento di una soglia di frequenza regolabile
Se un ingresso logico è assegnato alla funzione, la commutazione di rampa può avvenire solo su questo
ingresso.
Marcia passo-passo ”JOG”: Impulso di marcia a piccola velocità
Se il contatto JOG è chiuso e viene azionato il contatto del senso di marcia, la rampa è di 0,1 s con qualsiasi
regolazione ACC, dEC, AC2, dE2. Se il contatto di senso di marcia è chiuso e viene azionato il contatto JOG,
sono le rampe regolate ad essere utilizzate.
Parametri accessibili nel menu regolazione:
- velocità JOG
- temporizzazione di anti-ripetizione (tempo min. tra 2 comandi “JOG”)

ITALIANO
267

GP_ATV58_IT.fm Page 268 Mardi, 2. avril 2002 5:51 17

Funzioni configurabili degli ingressi e uscite
Più veloce / meno veloce: sono possibili 2 tipi di funzionamento.
1 Utilizzo di pulsanti ad azione singola: sono necessari due ingressi logici oltre al o ai sensi di marcia.
L’ingresso assegnato al comando "più veloce” aumenta la velocità, mentre l’ingresso assegnato al comando
“meno veloce” riduce la velocità.
Questa funzione consente di accedere al parametro memorizzazione riferimento Str nel menu Comando.
2 Utilizzo di pulsanti a doppia azione: è necessario solo un ingresso logico assegnato al comando più veloce.
Più veloce / meno veloce con pulsanti a doppia azione:
Descrizione: 1 pulsante a doppia azione per ogni senso di rotazione.
Ad ogni pressione del pulsante viene chiuso un contatto pulito.
Rilasciato
(meno veloce)

1a pressione
(velocità mantenuta)

2a pressione
(più veloce)

pulsante marcia avanti

–

a

aeb

pulsante marcia indietro

–

c

ced

Esempio di collegamento:
LI1 : marcia avanti
LIx : marcia indietro
LIy : più veloce

Morsettiera controllo ATV58
LI1 LIx LIy
+ 24

b
a

d

c

Frequenza
motore

ITALIANO

LSP
0
LSP
Marcia avanti
2¡ pressione pulsante
1¡ pressione pulsante
0
Marcia indietro
2¡ pressione pulsante
1¡ pressione pulsante
0

b
b
a a a a

a

a

a

c

d
c

Questo tipo di funzione più veloce/meno veloce è incompatibile con il comando a 3 fili. In questo caso la
funzione meno veloce è assegnata automaticamente all’ingresso logico d’indice superiore (esempio: LI3 (più
veloce), LI4 (meno veloce)).
In entrambi i casi d'impiego la velocità massima è data dai valori applicati agli ingressi analogici.
Collegare ad esempio AI1 al +10V.

268

GP_ATV58_IT.fm Page 269 Mardi, 2. avril 2002 9:42 21

Funzioni configurabili degli ingressi e uscite
Velocità preselezionate
È possibile preselezionare 2,4 o 8 velocità, che richiedono rispettivamente 1, 2, o 3 ingressi logici.
L’ordine delle configurazioni che è necessario rispettare è il seguente: PS2 (LIx), quindi PS4 (LIy), e infine PS8
(LIz).
2 velocità preselezionate

4 velocità preselezionate

8 velocità preselezionate

Configurare: LIx a PS2

Configurare: LIx a PS2 quindi
LIy a PS4

Configurare: LIx a PS2
LIy a PS4, e infine LIz a PS8

LIx

LIy

LIx

LIz

LIy

LIx

0

LSP+riferimento

riferimento velocità

0

0

riferimento velocità
LSP+riferimento

0

0

0

riferimento velocità
LSP+riferimento

1

HSP

0

1

SP2

0

0

1

SP2

1

0

SP3

0

1

0

SP3

1

1

HSP

0

1

1

SP4

1

0

0

SP5

1

0

1

SP6

1

1

0

SP7

1

1

1

HSP

Per disattivare gli ingressi logici, deve è necessario rispettare l'ordine seguente: PS8 (LIz), quindi PS4 (LIy) e
infine PS2 (LIx).
Commutazione dei riferimenti:
Commutazione di due riferimenti (riferimento in AI1 e riferimento in AI2) mediante ordine su ingresso logico.
Questa funzione assegna automaticamente AI2 al riferimento velocità 2.
Schema di collegamento

LI x + 24 COM

AI 1

+10

AI 2

0-20mA
4-20mA

Contatto aperto, riferimento = AI2
Contatto chiuso, riferimento = AI1

Arresto ruota libera
L’arresto del motore è funzione solo della coppia resistente, con interruzione dell'alimentazione del motore.
L’arresto ruota libera si ottiene all'apertura dell’ingresso logico (stato 0).

Arresto rapido:
Arresto frenato con tempo della rampa di decelerazione ridotto in base ad un coefficiente di riduzione dCF che
appare nel menu controllo.
L’arresto rapido si ottiene all'apertura dell’ingresso logico (stato 0).

269

ITALIANO

Arresto mediante iniezione di corrente continua
L’arresto mediante iniezione di cc si ottiene alla chiusura dell'ingresso logico (stato 1).

GP_ATV58_IT.fm Page 270 Lundi, 8. avril 2002 4:53 16

Funzioni configurabili degli ingressi e uscite
Commutazione dei motori
Questa funzione consente di alimentare in successione due motori di potenze diverse; la commutazione è
garantita da una sequenza appropriata in uscita dal variatore. La commutazione deve avvenire a motore fermo
e variatore bloccato. I seguenti parametri interni sono commutati automaticamente mediante ordine logico:
- corrente nominale motore
- corrente di iniezione

- corrente di apertura del freno

Questa funzione annulla automaticamente la protezione termica del secondo motore.
Parametro accessibile: Rapporto delle potenze motore PCC nel menu controllo.
Seconda limitazione di coppia
Riduzione della coppia massima del motore con ingresso logico attivo.
Parametro tL2 nel menu regolazione.
Reset difetto
Sono disponibili due tipi di reset: parziale o generale (parametro rSt del menu "difetti").
Reset parziale (rSt = RSP):
Consente di cancellare il difetto memorizzato e di riarmare il variatore se la causa del difetto è scomparsa.
Difetti cancellabili con reset parziale:
-

sovratensione rete
sovratensione bus continuo
interruzione fase motore
trascinamento del carico

-

difetto comunicazione
sovraccarico motore
interruzione 4-20mA
difetto esterno

-

surriscaldamento motore
difetto collegam. seriale
surriscaldamento variatore
sovravelocità

Reset generale (rSt = RSG):
Si tratta di un'inibizione (marcia forzata) di tutti i difetti ad eccezione del difetto SCF (cortocircuito
motore) durante la chiusura dell'ingresso logico configurato.
Forzatura locale
Consente di passare da un modo di comando in linea (collegamento seriale) ad un modo di comando locale
(comando mediante morsettiera o terminale).
Auto-tuning
Il passaggio a 1 dell'ingresso logico configurato attiva un auto-tuning, come il parametro tUn del menu
"controllo".
Attenzione: l'auto-tuning può essere effettuato solo se non è azionato alcun comando. Se ad un
ingresso logico è assegnata una funzione "arresto ruota libera" o "arresto rapido" occorre mettere
l'ingresso a 1 (attivo a 0).
Applicazione: Ad esempio in caso di commutazione dei motori.

ITALIANO

Auto-man PI, riferimenti PI preselezionati: Vedere funzione regolatore PI (pagina 39)
Limitazione di coppia tramite ingresso AI
Questa funzione è accessibile solo se l’ingresso analogico AI3 è assegnato alla funzione limitazione di coppia.
Se non esiste alcun ingresso logico LI impostato su "TL2 : seconda limitazione di coppia", la limitazione è data
direttamente dall’ingresso analogico AI3.
Se un ingresso logico è impostato su "TL2 : seconda limitazione di coppia " :
Quando l’ingresso è a 0, la limitazione è data da tLi.
Quando l’ingresso è a 1, la limitazione è data tion da AI3.
Difetto esterno
Il passaggio a 1 dell’ingresso logico configurato attiva l’arresto del motore (in base alla configurazione del
parametro LSF Stop+dif del menu Controllo) e il blocco del variatore in difetto EPF difetto esterno.

270

GP_ATV58_IT.fm Page 271 Lundi, 8. avril 2002 4:44 16

Funzioni configurabili degli ingressi e uscite
Funzioni configurabili degli ingressi analogici
L’ingresso AI1 è sempre assegnato al riferimento velocità.

Configurazione di AI2 e AI3
Riferimento velocità sommatore: I riferimenti di frequenza di AI2 e AI3 possono essere sommate a AI1.
Regolazione della velocità con dinamo tachimetrica: (Configurazione su AI3 solo con una scheda
estensione I/O con ingresso analogico): consente una correzione della velocità con ritorno dinamo
tachimetrica. Per adattare la tensione della dinamo tachimetrica è necessario un partitore esterno. La tensione
massima deve essere compresa tra 5 e 9 V. Una regolazione precisa si ottiene mediante regolazione del
parametro dtS disponibile nel menu regolazione.
Trattamento sonda PTC: (solo con una scheda di estensione I/O con ingresso analogico). Consente una
protezione termica diretta del motore collegando sull’ingresso analogico AI3 le sonde PTC inserite negli
avvolgimenti del motore.
Caratteristiche delle sonde PTC:
Resistenza totale del circuito sonda a 20 °C = 750 Ω.
Regolatore PI: Consente di regolare un processo con un riferimento e un ritorno dato da un trasduttore. Con
la funzione PI, le rampe sono tutte lineari, anche se configurate in modo diverso.
Con il regolatore PI, è possibile:
- Adattare il ritorno con FbS.
- Effettuare una correzione di PI inverso.
- Regolare i guadagni proporzionale ed integrale (RPG e RIG).
- Assegnare un’uscita analogica al riferimento PI, il ritorno PI e l’errore PI.
- Applicare una rampa di esecuzione dell’azione del PI (AC2) all’avviamento se PSP > 0.
Se PSP = 0 le rampe attive sono ACC / dEC. All’arresto la rampa dEC è sempre utilizzata.
La velocità motore è limitata tra LSP e HSP.
Nota : La funzione regolatore PI è attiva se un ingresso AI è configurato a ritorno PI. Questa configurazione
su AI è possibile solo dopo annullamento delle funzioni incompatibili con PI (vedere pagina 34).

Riferimento
PI

+
-

Ritorno
PI

PSP

FBS
10

Inversione
PI

Regolatore
PI

PIC
X±1

RPG
RIG

Rampa
se PSP = 0
X

ACC
dEC
Riferimento

Rampa
se PSP > 0

AC2
dE2

Auto
Man

Filtro
Moltiplicatore
passa basso
Ordine di marcia

Auto / man

ITALIANO

Riferimento manuale

ACC
dEC
Rampa

271

GP_ATV58_IT.fm Page 272 Lundi, 8. avril 2002 4:44 16

Funzioni configurabili degli ingressi e uscite
Auto / Man :
Questa funzione è accessibile solo se è attiva la funzione PI e richiede una scheda di estensione I/O con
ingresso analogico.
Consente la commutazione della marcia in regolazione velocità tramite ingresso logico se LI si LIx = 0
(riferimento manuale su AI3) e la regolazione PI se LIx = 1 (auto).
Riferimenti preselezionati:
2 o 4 riferimenti preselezionati richiedono rispettivamente l’utilizzo di 1 o 2 ingressi logici:

LIx

2 riferimenti selezionati

4 riferimenti selezionati

Configurare: da LIx a Pr2

Configurare: da LIx a Pr2 quindi, da LIy a Pr4
LIy

LIx

0

Riferimento analogico

Riferimento

0

0

Riferimento
Riferimento analogico

1

Max processo (= 10 V)

0

1

PI2 (regolabile)

1

0

PI3 (regolabile)

1

1

Max processo (= 10 V)

Limitazione di coppia: (Solo con una scheda di estensione I/U con ingresso analogico AI3)
Il segnale applicato su AI3 agisce in modo lineare sulla limitazione di coppia interna (parametro TLI del menu
"controllo") :
- Se AI3 = 0V : limitazione = TLI x 0 = 0
- Se AI3 = 10 V : limitazione = TLI.
Applicazini : Correzione di coppia, di trazione

Funzioni dell’ingresso encoder:
(Solo con una scheda di estensione I/U con ingresso encoder)
Regolazione velocità: Permette una correzione della velocità mediante encoder incrementale o rilevatore.
(Vedere documentazione fornita con la scheda).

ITALIANO

Riferimento velocità sommatrice: Il riferimento emesso dall’ingresso encoder è sommato con AI1.
(Vedere documentazione fornita con la scheda)
Applicazioni :
- Sincronizzazione in velocità di più variatori. Il parametro PLS del menu "controllo" permette di regolare il
rapporto della velocità di un motore rispetto ad un altro.
- Riferimento con generatore d'impulsi.

272

GP_ATV58_IT.fm Page 273 Mardi, 2. avril 2002 5:51 17

Funzioni configurabili degli ingressi e uscite
Funzioni configurabili delle uscite logiche
Relè R2, uscita statica LO (con scheda di estensione I/O)
Comando contattore a valle (OCC): configurabile a R2 o LO
Consente il comando di un contattore (situato tra il variatore ed il motore) mediante variatore. L'ordine di
chiusura del contattore avviene alla comparsa di un ordine di marcia. L'apertura del contattore avviene quando
nel motore non è più presente corrente.
Se è configurata una funzione di frenatura mediante iniezione di corrente continua, non farla
funzionare troppo a lungo all'arresto, dal momento che il contattore si aprirà solo a frenatura
terminata.

Variatore in marcia (RUN): configurabile a R2 o LO
L'uscita logica è a 1 se il motore è alimentato dal variatore (presenza di corrente), o se è presente un ordine
di marcia con riferimento nullo.
Soglia di frequenza raggiunta (FTA): configurabile a R2 o LO
L'uscita logica è a 1 se la frequenza motore è superiore o uguale alla soglia di frequenza regolata mediante
Ftd nel menu regolazione.
2 a soglia di frequenza raggiunta (F2A): configurabile a R2 o LO
L’uscita logica è a 1 se la frequenza motore è superiore o uguale alla soglia di frequenza regolata tramite
il parametro F2d nel menu regolazione.

Riferimento raggiunto (SRA): configurabile a R2 o LO
L'uscita logica è a 1 se la frequenza motore è uguale al valore di riferimento.
Grande velocità raggiunta (FLA): configurabile a R2 o LO
L'uscita logica è a 1 se la frequenza motore è uguale a HSP.
Soglia di corrente raggiunta (CTA): configurabile a R2 o LO
L'uscita logica è a 1 se la corrente motore è superiore o uguale alla soglia di corrente regolata mediante Ctd
nel menu regolazione.
Stato termico raggiunto (TSA): configurabile a R2 o LO
L'uscita logica è a 1 se lo stato termico motore è superiore o uguale alla soglia dello stato termico regolata
mediante ttd nel menu regolazione.
Stato termico variatore raggiunto (TAD): configurabile a R2 o LO
L’uscita logica è a 1 se lo stato termico variatore è superiore o uguale alla soglia dello stato termico regolata
tramite il parametro dtd nel menu regolazione.

Comando freno (BLC): configurabile solo al relè R2
Consente la gestione di un freno elettromagnetico mediante il variatore, per le applicazioni di sollevamento
verticale. Per i freni dei movimenti orizzontali utilizzare la funzione “variatore in marcia“.
Velocità motore

Stato freno
1
0
Relè R2
1
0
Apertura o chiusura freno
1
0
T

brt

bEt

273

ITALIANO

T = temporizzazione non regolabile
Regolazioni accessibili nel menu
regolazione:
- frequenza di apertura freno (brL)
- temporizzazione di apertura freno
(brt)
- temporizzazione di chiusura freno
(bEt)
- corrente di apertura freno (Ibn)
- frequenza di chiusura freno (bEn)

Riferimento

GP_ATV58_IT.fm Page 274 Mardi, 2. avril 2002 5:51 17

Funzioni configurabili degli ingressi e uscite
Consigli per la regolazione del comando freno, per applicazioni di sollevamento verticale:
1 Frequenza di apertura freno (brL):
Regolare la frequenza di apertura del freno al valore: scorrimento nominale moltiplicato per la frequenza
nominale in Hz (g x FS).
( Ns – Nr )
Ns

Calcolo dello scorrimento: = ------------------------- Ns = velocità di sincronizzazione in giri/min.
(per una rete 50 Hz: Ns = 3000 giri/min. per un motore a 1 coppia di poli, 1500 giri/min. per un motore a 2
coppie di poli, 1000 giri/min. per un motore a 3 coppie di poli e 750 giri/min. per un motore a 4 coppie di poli,
per una rete 60 Hz: Ns = 3600 giri/min. per un motore a 1 coppia di poli, 1800 giri/min. per un motore a 2
coppie di poli, 1200 giri/min. per un motore a 3 coppie di poli e 900 giri/min. per un motore a 4 coppie di poli).
- Nr = velocità nominale alla coppia nominale in giri/min.; prendere la velocità indicata sulla targa del motore.
Frequenza di apertura freno = g x Fs.
- g = scorrimento precedentemente calcolato.
- Fs = frequenza nominale motore (indicata sulla targa motore).
Esempio: per motore a 2 coppie di poli, con 1430 giri/min., rete 50 Hz.
g = (1500 - 1430) / 1500 = 0.0466.
Frequenza di apertura freno = 0.0466 x 50 = 2.4 Hz
2 Corrente di apertura del freno (Ibr):
Regolare la corrente di apertura del freno alla corrente nominale indicata sulla targa del motore.
Nota sui punti 1 e 2: i valori indicati (corrente di apertura e frequenza di apertura) corrispondono a valori
teorici. Se, al momento delle prove, la coppia è insufficiente rispetto ai valori teorici indicati: mantenere la
corrente di apertura del freno alla corrente nominale motore e ridurre la frequenza di apertura del freno (fino
a 2/3 dello scorrimento nominale). Se il risultato non sarà ancora soddisfacente tornare ai valori teorici,
quindi aumentare la corrente di apertura del freno (il valore massimo è imposto dal variatore) e aumentare
progressivamente la frequenza di apertura del freno.
3 Tempo di accelerazione:
Per le applicazioni di sollevamento consigliamo di impostare rampe di accelerazine superiori a 0.5 secondi.
Assicurarsi che il variatore non passi in limitazione di corrente.
Stessa raccomandazione per le rampe di decelerazione.
Attenzione: per un movimento di sollevamento occorre utilizzare una resistenza di frenatura accertandosi
inoltre che le regolazioni e configurazioni scelte non provochino una caduta o il mancato controllo del carico
sollevato.

ITALIANO

4 Temporizzazione di apertura del freno (brt):
Regolare questo parametro in funzione del tipo di freno; si tratta del tempo necessario all'apertura del freno
meccanico.
5 Frequenza di chiusura del freno (bEn):
Regolare a 2 volte lo scorrimento nominale (nell'esempio sopra riportato: 2 x 2.4 = 4.8 Hz). Quindi effettuare
la regolazione in funzione del risultato ottenuto.
6 Temporizzazione di chiusura del freno (bEt):
Regolare questo parametro in funzione del tipo di freno; si tratta del tempo necessario alla chiusura del freno
meccanico.
Interruzione 4-20 mA (APL) configurabile a R2 o LO
L’uscita logica è a 1 seil segnale sull’ingresso 4-20 mA è inferiore a 2 mA.

274

GP_ATV58_IT.fm Page 275 Mardi, 2. avril 2002 5:51 17

Funzioni configurabili degli ingressi
e delle uscite
Funzioni configurate dell'uscita analogica AO
L'uscita analogica AO è un'uscita in corrente, da AOL (mA) a AOH (mA),
• con AOL e AOH configurabili da 0 a 20 mA.
Esempi AOL - AOH :

0 - 20 mA
4 - 20 mA
20 - 4 mA

Corrente motore (Codice OCR): fornisce l'immagine della corrente efficace del motore.
• AOH corrisponde al doppio della corrente nominale del variatore.
• AOL corrisponde alla corrente nulla.
Frequenza motore (Codice OFR): fornisce la frequenza motore stimata dal variatore.
• AOH corrisponde alla frequenza massima (parametro tFr).
• AOL corrisponde alla frequenza nulla.
Uscita rampa (Codice ORP): fornisce l’immagine della frequenza in uscita dalla rampa.
• AOH corrisponde alla frequenza massima (parametro tFr).
• AOL corrisponde alla frequenza nulla.
Coppia motore (Codice TRQ): fornisce l’immagine della coppia motore in valore assoluto.
• AOH corrisponde al doppio della coppia nominale motore.
• AOL corrisponde alla coppia nulla.
Coppia motore con segno (Codice STQ): fornisce l'immagine dell coppia motore con il senso:
• AOL corrisponde ad una coppia di frenatura = 2 volte la coppia nominale.
• AOH corrisponde ad una coppia motore = 2 volte la coppia nominale.
• AOH + AOL corrisponde alla coppia nulla.
2
Rampa con segno (codice ORS) : fornisce l’immagine della frequenza in uscita dalla rampa e il suo senso.
• AOL corrisponde alla frequenza massima (parametro tFr) in marcia indietro.
• AOH corrisponde alla frequenza massima (parametro tFr) in marcia avanti.
• AOH + AOL corrisponde alla frequenza nulla.
2
RIferimento PI (codice OPS): fornisce l’immagine del riferimento del regolatore PI.
• AOL corrisponde al riferimento min.
• AOH corrisponde al riferimento max.

275

ITALIANO

Ritorno PI (codice OPF) : fornsice l’immagine del ritorno del regolatore PI.
• AOL corrisponde al ritorno min.
• AOH corrisponde al ritorno max.
•
Errore PI (codice OPE) : fornisce l’immagine dell’errore del regolatore PI in % della gamma del sensore
(ritorno max - ritorno min).
• AOL corrisponde all’errore massimo < 0.
• AOH corrisponde all’errore massimo > 0.
• AOH + AOL corrisponde ad un errore nullo (OPE = 0).
2

GP_ATV58_IT.fm Page 276 Mardi, 2. avril 2002 9:47 21

Funzioni degli ingressi e delle uscite configurabili
Integrale PI (codice OPI): fornisce l’immagine dell’integrale dell’errore del regolatore PI.
• AOL corrisponde ad un’integrale nulla.
• AOH corrisponde ad un’integrale satura.
Potenza Motore (codice OPR): fornisce l’immagine della potenza assorbita dal motore.
• AOL corrisponde allo 0 % della potenza nominale del motore.
• AOH corrisponde al 200 % della potenza nominale del motore.
Stato termico motore (codice THR): fornisce l’immagine dello stato termico del motore calcolato.
• AOL corrisponde allo 0 %.
• AOH corrisponde al 200 %.

ITALIANO

Stato termico variatore (codice THD): fornisce l’immagine dello stato termico del variatore.
• AOL corrisponde allo 0 %.
• AOH corrisponde al 200 %.

276

GP_ATV58_IT.fm Page 277 Lundi, 8. avril 2002 4:48 16

Menu Difetti

Questo menu è accessibile con commutatore in posizione
.
Le modifiche possono essere effettuate solo a motore fermo e variatore bloccato.
Cod.

Descrizione

Regolaz. di base

Atr

Riavv. Auto

No

Questa funzione consente un riavviamento automatico del variatore in caso di scomparsa del difetto
(scelta Si/No). È possibile effettuare un riavviamento automatico dopo i seguenti difetti:
- sovratensione rete
- sovratensione bus DC
- difetto esterno
- interruzione fase motore
- difetto collegamento seriale
- difetto comunicazione
- interruzione riferimento 4-20 mA
- sovraccarico motore (condizione: stato termicoinferiore al 100 %)
- surriscaldamento variatore (condizione: stato termico variatore inferiore al 70 %)
- Surriscaldamento motore (condizione: resistenza delle sonde inferiore a 1500 Ohm)
Quando la funzione è attivata in seguito ad arresto il relè R1 resta chiuso su uno o più difetti: il
variatore effettua un tentativo di avviamento ogni 30 s. Vengono effettuati 6 tentativi al massimo
fino a quando il variatore sarà in grado di ripartire . Se tutti e 6 i tentativi non hanno esito positivo il
variatore resta definitivamente bloccato con apertura del relè di difetto, fino al riarmo mediante
messa fuori tensione.
Questa funzione richiede che sia mantenuta la sequenza associata. Occorre inoltre
accertarsi che un riavviamento intempestivo non presenti un pericolo per le persone
e le cose.

rSt

Tipo Reset

RSP

Questa funzione è accessibile se il reset dei difetti è assegnato ad un ingresso logico. 2 scelte
possibili: reset parziale (RSP), reset totale (RSG)
Difetti cancellabili con un reset parziale (rSt = RSP)
- sovratensione rete
- sovratens. bus continuo
- surriscaldamento motore
- perte 4-20mA
- sovraccarico motore
- trascinamento del carico
- interruzione fase motore
- surriscaldam. variatore
- difetto collegam. seriale
- difetto esterno
- difetto comunicazione
- sovravelocità

OPL

Interruzione Fase Mot

ITALIANO

Difetti cancellabili con un reset generale (rSt = RSG): tutti i difetti. Il reset generale è infatti
un'inibizione di tutti i difetti (marcia forzata).
Per configurare rSt = RSG:
1 visualizzare RSG
2 premere il tasto "ENT"
3 il variatore visualizza "Vedere manuale"
4 premere su ▲ quindi su ▼ e infine su "ENT"
Si

Consente di convalidare il difetto di interruzione fase motore. (Eliminazione del difetto in caso
d'impiego di un contattore tra il variatore ed il motore). Scelta Si / No

IPL

Interruzione Fase rete

Si

Consente di convalidare il difetto di interruzione fase rete. (Eliminazione del difetto in caso di
alimentazione diretta con bus continuo e in caso di alimentazione di un variatore trifase ATV58•
U72M2, U90M2 o D12M2 in monofase). Scelta Si / No
Questo difetto non esiste sui variatori ATV58•U09M2, U18M2, U29M2 e U41M2.

277

GP_ATV58_IT.fm Page 278 Mardi, 2. avril 2002 5:51 17

Menu Difetti

Cod.

Descrizione

Regolaz. di base

tHt

Tipo Prot. Term.

ACL

Definisce il tipo di protezione termica motore indiretta effettuata dal variatore. Se al variatore sono
collegate delle sonde PTC, questa funzione non è disponibile. Nessuna protezione termica:
N0: Nessuna
Motore autoventilato (ACL): il variatore tiene conto di un declassamento in funzione della frequenza
di rotazione.Motore motoventilato (FCL): il variatore non tiene conto di un declassamento in
funzione della frequenza di rotazione.

LFL

Interruzione 4-20mA

No

Consente di convalidare il difetto di interruzione rif. 4-20 mA.
Questo difetto è configurabile solo se i parametri riferim. min./max AI2 (CrL e CrH)) sono superiori
a 3 mA. Scelta Si / No. Si CrL>CrH, LFL è bloccato su Si.
- No : nessuno difetto
- Si : difetto immediato
- STT : arresto secondo il parametro STT, nessuno difetto, riavviamento al ritorno del segnale
- LSF : arresto secondo il parametro STT e quindi diffeto al fine dell’arresto
- LFF : forzatura alla velocità di ripristino regolata dal parametro LFF
- RLS : mantenimento della velocità raggiunta fino alla comparsa dell interruzione 4-20 mA,
nessuno difetto, riavviamento al ritorno del segnale.

LFF

Vit.Def.4-20

0

Velocità di ripristino in caso di interruzione di riferimento 4-20 mA.
Regabile di 0 da HSP.

FLr

Ripresa al Volo

No

Consente di convalidare un riavviamento senza sbalzi dopo i seguenti eventi:
- interruzione rete o semplice messa fuori tensione.
- reset dei difetti o riavviamento automatico.
- arresto ruota libera o arresto con iniezione su ingresso logico.
- interruzione non controllata a valle del variatore.
Scelta Si / No
Se il relè R2 è assegnato alla funzione logica freno il parametro FLr resta bloccato su no.

ITALIANO

StP

Arresto Interr. Rete

No

Arresto controllato in caso di interruzione di fase rete. Questa funzione è attiva solo se il parametro
IPL è impostato su No. Se IPL è su Si, lasciare StP in posizione No. Scelte possibili:
No: blocco in caso di interruzione della rete.
MMS: Mant. Bus DC: il controllo del variatore è mantenuto sotto tensione dall'energia cineticas
restituita dall'inerzia del carico, fino alla comparsa del difetto USF (sotto tensione)
FRP: Su rampa: decelerazione in base alla rampa programmata dEC o dE2 fino all'arresto o alla
comparsa difetto USF (sotto tensione). Funzione non presente sui variatori ATV58•U09M2, U18M2,
U29M2 e U41M2.

Sdd

Cont. Anti Rotaz.

Si

Questa funzione è accessibile se è programmato un ritorno con dinamo tachimetrica o generatore
d’impulsi. Se convalidata consente di bloccare il variatore nel caso in cui venga rilevata una
differenza tra la frequenza statorica e la velocità misurata.
Scelta Si / No.

EPL

278

Difetto esterno
Si
Configura l’arresto in caso di difetto esterno:
- Si: blocco in difetto immediato
- LSF:Stop+Dif.: arresto secondo il parametro SSt(Menu Controllo) e quindi blocco in difetto.

GP_ATV58_IT.fm Page 279 Mardi, 2. avril 2002 5:51 17

Menu File

Questo menu è accessibile con commutatore in posizione
.
Le operazioni sono possibili solo con motore fermo e variatore bloccato.
Il terminale consente di memorizzare 4 files contenenti le configurazioni del variatore.
Cod.

Descrizione

F1S
F2S
F3S
F4S

Stato
Stato
Stato
Stato

File
File
File
File

Regolaz. di base

1
2
3
4

FRE
FRE
FRE
FRE

Consente di visualizzare lo stato del file corrispondente.
Stati possibili:
FRE: file libero (Stato alla consegna del terminale)
EnG: Una configurazione è già stata memorizzata in questo file

FOt

Operazione

NO

Consente di selezionare l'operazione da effettuare sui files.
Operazioni possibili:
NO: nessuna operazione richiesta (valore di default ad ogni nuovo collegamento del terminale al
variatore)
STR: operazione di memorizzazione della configurazione del variatore in un file del terminale
REC: trasferimento del contenuto di un file al variatore
Ini: ritorno del variatore alle regolazioni di base
Il ripristino della regolazione di base annulerà tutte le regolazioni e configurazioni
effettuate.

Come procedere
Selezionare STR, REC o InI e premere il tasto "ENT".
1 Se Operazione = STR:
Il display visualizza dei numeri di file. Selezionare un file con ▲ o ▼ e confermare con "ENT".
2 Se Operazione = REC:
Il display visualizza dei numeri di file. Selezionare un file con ▲ o ▼ e confermare con "ENT".
- il display visualizza

CHG

VALIDARE?

ENT/ESC

Verificare che il collegamento sia compatibile con la configurazione del file.
Annullare con "ESC" o confermare con "ENT".
- il display chiede quindi una seconda conferma da convalidare premendo "ENT" o annullare con "ESC".
3 Se Operazione = InI:
Validazione con "ENT"

CHG

VALIDARE?

ENT/ESC

Verificare che il collegamento sia compatibile con la configurazione di base.
Annullare con "ESC" o confermare con "ENT".
- il display chiede quindi una seconda conferma da convalidare premendo "ENT" o annullare con "ESC".
Al termine di ogni operazione il display visualizza nuovamente il parametro "Operazione" in "NO".

279

ITALIANO

- il display visualizza:

GP_ATV58_IT.fm Page 280 Mardi, 2. avril 2002 5:51 17

Menu File

Menu File (segue)
Cod.

Descrizione

COd

Cod. Conf.
Codice confidenziale

La configurazione del variatore può essere protetta con un Codice confidenziale (COd).
ATTENZIONE: QUESTO PARAMETRO DEVE ESSERE UTILIZZATO CON PARTICOLARE ATTENZIONE
POICHÈ PUÒ IMPEDIRE L'ACCESSO ALL'INSIEME DEI PARAMETRI. QUALSIASI MODIFICA
APPORTATA DEVE ESSERE ACCURATAMENTE ANNOTATA E REGISTRATA.
Il codice è composto da quattro cifre, l'ultima delle quali consente di fissare il livello che si decide di lasciare
libero, a cui è possibile cioè accedere senza inserire il codice esatto.

8888
questa cifra indica il livello di accesso autorizzato,
senza inserimento del codice corretto.
L’accessibilità ai menu in funzione del commutatore di blocco accesso situato sul lato posteriore del terminale
è sempre operativa, nei limiti consentiti dal codice confidenziale.
Il Codice 0000 (regolazione di base) non implica limitazioni di accesso.
La tabella qui di seguito indica l'accessibilità ai menu in funzione dell'ultima cifra del codice.
Ultima cifra del codice
Menu

Accesso bloccato

Visualizzazione

Modifica

Regolazioni

0 tranne 0000 e 9

1

2

Livello 2 :
Regolazioni, Macro-config, Controllo,
Comando, Configurazione I/O, Difetti,
File (tranne codice),
Comunicazione (solo con scheda installata)

0 tranne 0000 e 9

3

4

Applicazione (solo con scheda installata)

0 tranne 0000 e 9

5

6

Livello 2 e Applicazione (solo con scheda
installata)

0 tranne 0000 e 9

7

8

ITALIANO

Per accedere al menu APPLICAZIONE, consultare la documentazione della scheda applicazione.
La modifica del codice si effettua con i tasti ▲ o ▼ .
Se viene inserito un codice errato il display visualizza il seguente messaggio:

COd

Codice inesatto

Dopo aver premuto i tasti ENT o ESC della tastiera, il valore visualizzato del parametro Codice diventa 0000:
il livello di accessibilità resta invariato. L’operazione deve essere ripetuta.
Per accedere ai menu protetti dai codici confidenziali, occorre per prima cosa inserire il codice esatto che resta
sempre accessibile nel menu File.

280

GP_ATV58_IT.fm Page 281 Mardi, 2. avril 2002 5:51 17

Menu Comunicazione e Applicazione/Assistenza in
esercizio/Manutenzione
Menu Comunicazione
Questo menu viene visualizzato solo se è installata una scheda comunicazione. È accessibile con
commutatore in posizione
. La configurazione è possibile solo con motore fermo e variatore bloccato.
Per l’utilizzo con una scheda di comunicazione opzionale, consultare la documentazione fornita con la scheda
stessa.
Per l’utilizzo della comunicazione con collegamento RS485 del prodotto base, consultare la documentazione
fornita con il kit di connessione RS485.

Menu Applicazione
Questo menu viene visualizzato solo se è installata una scheda "applicazione cliente". È accessibile con
commutatore in posizione
. La configurazione è possibile solo con motore fermo e variatore bloccato.
Consultare la documentazione fornita con la scheda.

Assistenza in esercizio
Vedere le spie di segnalazione riportate nel paragrafo "Presentazione".

Manutenzione
Prima di effettuare qualsiasi intervento sul variatore, interrompere l’alimentazione ed
attendere la scarica dei condensatori (3 minuti circa): spegnimento del LED verde sul lato
anteriore del variatore.
ATTENZIONE: la tensione continua ai morsetti + e - o PA e PB può raggiungere 900 V in base alla
tensione della rete.
In caso di anomalia alla messa in servizio o in esercizio, accertarsi per prima cosa che siano stati osservati
con cura i consigli relativi alle condizioni ambientali, al montaggio e ai collegamenti. Consultare la guida
all'impiego dell’Altivar.

Manutenzione
L’Altivar 58 non richiede interventi di manutenzione preventiva. Si consiglia tuttavia, ad intervalli regolari, di:
- verificare lo stato e il serraggio delle connessioni,
- assicurarsi che la temperatura vicino all'apparechio resti ad un livello accettabile e che la ventilazione sia
efficace (durata media dei ventilatori: da 3 a 5 anni in base alle condizioni d'impiego),
- se necessario spolverare il variatore.

Il primo difetto rilevato viene memorizzato e visualizzato sul display del terminale: il variatore si blocca, il LED
rosso si accende ed il relè di sicurezza R1 interviene.

Reset del difetto
Interrompere l’alimentazione del variatore in caso di difetto non riarmabile.
Cercare la causa del difetto per eliminarla.
Ripristinare l’alimentazione: questo consente di resettare il difetto se questo è scomparso.
In alcuni casi può verificarsi un riavviamento automatico in seguito ala scomparsa del difetto, se la funzione è
stata precedentemente programmata.

281

ITALIANO

Assistenza alla manutenzione

GP_ATV58_IT.fm Page 282 Mardi, 2. avril 2002 5:51 17

ITALIANO

Manutenzione

Difetto visualizzato

Causa possibile

Procedura, rimedio

PHF
INTERRUZIONE
FASE RETE

• variatore mal alimentato o intervento
fusibili
• interruz. improvvisa di una fase
• utilizzo su rete monofase di un
variatore ATV58•U72M2, U90M2 o di
un D12M2 (trifase)

• verificare il collegamento potenza e i
fusibili
• riarmare
• configurare il difetto "Int. Fase rete"
(codice IPL) su "No", nel menu DIFETTI

USF
SOTTO TENSIONE

• rete troppo bassa
• abbassam.di tensione passeggero
• resistenza di carico usurata

• verificare la tensione di rete

OSF
SOVRATENSIONE

• rete troppo alta

• verificare la tensione di rete

OHF
SURRISCALDAMENTO
VAR

• temperatura radiatore troppo elevata
(tHd>118 %)

• controllare il carico del motore, la
ventilazione del variatore e attendere il
raffreddamento per riarmare

OLF
SOVRACCARICO MOT

• sganciamento termico per sovraccarico • verificare le regolazione della
protezione termica, controllare il carico
prolungato (tHr>118 %)
del motore.
• il riarmo è possibile dopo 7 minuti circa.

ObF
FRENATURA ECC

• frenatura troppo brusca o carico
trascinante
• surtension réseau en fonctionnement

• aumentare il tempo di decelerazione, e
se necessario aggiungere una
resistenza di frenatura.
• Verificare le eventuali sovratensioni
rete

OPF
INTERRUZIONE
FASE MOT

• interruzione di una fase in uscita
variatore

• verificare i collegamenti del motore et la
fermeture du contacteur aval (s’il existe)
• se si utilizza una partenza motore in
macro configurazione, verificare che la
configurazione del relè R2 sia in
contattore a valle.

LFF
INTERRUZIONE
4-20mA

• interruzione del riferim. 4-20mA
sull’ingresso AI2

• verificare il collegamento dei circuiti di
comando

OCF
SOVRACORRENTE

• rampa troppo corta
• inerzia o carico troppo forte
• blocco meccanico

• verificare le regolazioni
• verificare il dimensionamento motore/
variatore/carico
• verificare lo stato della meccanica

SCF
CORTOCIRCUITO
MOT

• cortocircuito o messa a terra in uscita
variatore

• verificare i cavi di collegamento
variatore scollegato e l’isolamento del
motore. Verificare il partitore a transistor
del variatore.

CrF
RELE CARICO

• difetto di comando del relè di carica
• resistenza di carica usurata

• verificare i collegamenti all'interno del
variatore e la resistenza di carica

SLF
INTERRUZIONE
RS485

• collegamento non corretto sulla presa
terminale del variatore

• verificare il collegamento sulla presa
terminale del variatore

282

• sostituire la resistenza di carica

GP_ATV58_IT.fm Page 283 Mardi, 2. avril 2002 5:51 17

Manutenzione

Difetto visualizzato

Causa possibile

Procedura, rimedio

OtF
SURRISCALDAMENTO
MOT

• temperatura motore troppo elevata
(sonde CTP)

• verificare la ventilazione motore, la
temperatura ambiente, controllare il
carico del motore
• verificare il tipo di sonde utilizzate

tSF
DIF. SONDA PTC

• collegamento errato delle sonde al
variatore

• verificare il collegamento delle sonde al
variatore
• verificare le sonde

EEF
DIFETTO EEPROM

• errore di memorizzazione in memoria
EEPROM

• interrompere l’alimentazione del
variatore e riarmare

InF
DIFETTO INTERNO

• difetto interno
• difetto di collegamento

• verificare i collegamenti del variatore

EPF
DIFETTO ESTERNO

• difetto provocato da un organo esterno • verificare l'organo che ha provocato il
difetto e riarmare

SPF
INTERRUZIONE
RIT. VEL.

• assenza di ritorno velocità

• verificare il collegamento e
l'accoppiamento meccanico del
rilevatore di velocità

AnF
ANTIROTAZIONE

• rampa non seguita
• velocità inversa al riferimento

• verificare la regolazione e il cablaggio
del ritorno velocità
• verificare l'adeguamento delle
regolazioni al carico
• verificare il dimensionamento motorevariatore e l'eventuale necessità di una
resistenza di frenatura

SOF
SOVRAVELOCITA'

• instabilità
• carico trascinante troppo forte

• verificare le regolazioni e i parametri
• aggiungere una resistenza di frenatura
• verificare il dimensionamento motore/
variatore/carico

CnF
DIF. RETE COM

• difetto di comunicazione sul bus di
campo

• verificare il collegamento della rete al
variatore
• verificare il time-out
• verificare il collegamento scheda
opzionale alla scheda controllo

CFF

• verificare la configurazione del variatore
(scheda potenza e altre)
• interrompere l’alimentazione del
variatore quindi riarmare
• memorizzare la configurazione in un file
del terminale
• premere ENT per ripristinare le
regolazioni di base

ERR. CALIBRO-ENT
ERR. OPZIONE-ENT

OPZ. NON PRESENTE-ENT
CONTR. EEPROM-ENT

CFI
DIF. CONFIG

Probabile errore nella sostituzione della
scheda:
• modifica del calibro della scheda
potenza
• modifica del tipo di scheda opzionale o
installazione di una scheda opzionale
prima non presente e se la
macroconfigurazione è CUS
• scheda opzionale non presente
• configurazione memorizzata
incoerente
Premendo il tasto ENT apparirà il messaggio:
RgLBase? ENT/ESC

• la configurazione trasmessa al variatore • verificare la configurazione
con collegamento seriale è incoerente
precedentemente trasmessa
• trasmettere una configurazione
coerente.
283

ITALIANO

ILF
• difetto di comunicazione tra la scheda
DIF. COM. INTERNA
opzionale e la scheda controllo

GP_ATV58_IT.fm Page 284 Mardi, 2. avril 2002 5:51 17

Manutenzione

Casi di mal funzionamento senza visualizzazione dei difetti
Causa possibile

Procedura,rimedio

Nessun codice
visualizzato, led
spenti.

• Manca alimentazione

• Verificare l’alimentazione del variatore

Nessun codice
visualizzato,
led verde acceso,
led rosso spento o
acceso

• Terminale HS

• Sostituire il terminale

rdY
led verde acceso

• Variatore in linea, con scheda
• Parametrizzare LI4 in forzatura locale
comunicazione o kit RS 485
quindi forzare a +24V LI4
• Un ingresso LI é configurato in "Arresto • Portare l'ingresso a 24 V per disabilitare
ruota libera" o "Arresto rapido", e
l’arresto
questo ingresso non é alimentato
Questi arresti lavorano in sicurezza
positiva (LI=+24 V)

ITALIANO

Difetto visualizzato

284

GP_ATV58_IT.fm Page 285 Mardi, 2. avril 2002 5:51 17

Memorizzazione configurazione e regolazioni

Riferimento variatore ATV58 ............ Display rif : ..............................................
Eventuale n° di identificazione cliente : ..............................................................
Scheda estensione : no y si y : riferimento ......................................................
Codice di accesso : no y si y : .........................................................................
Configurazione nel file n° ............................ del terminale di esercizio
Macro configuratione : .......................................................................................
Per configurazione CUS: personalizzata , configurazione degli ingressi / uscite :
ALTIVAR
LI 1 :
LI 2 :
LI 3 :
LI 4 :
AI 1 :
AI 2 :

Ingressi logici

Ingressi analogici
Ingressi encoder
Relé
Uscite logiche
Uscite analogiche

Scheda opzionale
LI 5 :
LI 6 :

AI 3 :
AI3 :

R2 :
LO :
AO :

AO1 :

Parametri di regolazione:
Regolazioni di base
3s
3s
0 Hz
50 / 60 Hz
20 %
20 %
In base al modello
In base al modello
0,5 s
0,5 ItH
5s
5s
0 Hz
0 Hz
0 Hz
0
1
100 %
100 %
20 %
10 Hz
15 Hz
20 Hz
25 Hz
30 Hz

Regolazioni cliente (1)
s
s
Hz
Hz
%
%
A
A
s
A
s
s
Hz
Hz
Hz
s
%
%
%
Hz
Hz
Hz
Hz
Hz

Cod.
SP7
JOG
JGt
brL
Ibr
brt
bEn
bEt
FFt
bIP
rPG
rIG
FbS
PIC
dtS
Ctd
ttd
tL2
PSP
PI2
PI3
dtd
Ftd
F2d

Regolazioni di base
35 Hz
10 Hz
0,5 s
0 Hz
0A
0s
0 Hz
0s
50/60 Hz
no
1
1/s
1
no
1
1,36 In
100 %
200%
0s
30 %
60 %
105 %
50/60 Hz
50/60 Hz

Regolazioni cliente (1)
Hz
Hz
s
Hz
A
s
Hz
s
Hz

/s

ITALIANO

Cod.
ACC
dEC
LSP
HSP
FLG
StA
ItH
IdC
tdC
SdC
AC2
dE2
JPF
JF2
JF3
tLS
USC
UFr
SLP
PFL
SP2
SP3
SP4
SP5
SP6

A
%
%
s
%
%
%
Hz
Hz

(1) indicare ”nullo” in mancanza del parametro.
285

GP_ATV58_IT.fm Page 286 Mardi, 2. avril 2002 5:51 17

Memorizzazione configurazione e regolazioni

Parametri menu esercizio:
Cod.
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt

Regolazioni di base
In base al modello
50 / 60 Hz
In base al modello
In base al modello
In base al modello
no
60 / 72 Hz
no
no
non
0 Hz
STN

Regolazioni cliente (1)
V
Hz
A
rpm

Hz

Cod.
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Regolazioni di base
LIN
4
200%
1,36 In
si
1
LF
In base al modello
si
no
DET
1024

Regolazioni cliente (1)
Hz

Cod.
AOH
Str
LCC
PSt
Add
tbr
rPr

Regolazioni di base
20 mA
No
non
si
0
19200
No

Regolazioni cliente (1)
mA

Cod.
LFF
FLr
StP
Sdd
EPL

Regolazioni di base
0 Hz
no
no
si
si

Regolazioni cliente (1)
Hz

%
A

kHz

(1 indicare ”nullo” in mancanza del parametro.

Parametri menu comando:
Cod.
tCC
tCt
rIn
bSP
CrL
CrH
AOL

Regolazioni di base
2W
LEL
no
no
4 mA
20 mA
0 mA

Regolazioni cliente (1)

mA
mA
mA

(1 indicare ”nullo” in mancanza del parametro.

ITALIANO

Parametri menu difetti:
Cod.
Atr
rSt
OPL
IPL
tHt
LFL

Regolazioni di base
no
RSP
si
si
ACL
no

Regolazioni cliente (1)

(1) indicare ”nullo” in mancanza del parametro.

286

GP_ATV58_IT.fm Page 287 Mardi, 2. avril 2002 5:51 17

Sintesi dei menu

Menu LINGUA
Funzione
English
Français
Deutsch
Español
Italiano

Menu 2 - REGOLAZIONI (segue)
Codice
LnG
LnG
LnG
LnG
LnG

Menu MACRO-CONFIG
Funzione
Hdg : Manutenzione
GEn : Uso Gen.
VT : C. Variabile

Codice
CFG
CFG
CF

Menu 1 - VISUALIZZAZIONI
Funzione
Stato var.
Rif. Freq
Freq. Uscita
Vitesse mot.
Velocità mot.
Vel. macchina
Potenza uscita
U rete
Term. mot.
Term. var.
Ultimo dif.
Rif. Freq.
Consumo
Tempo di marcia

Codice
--FrH
rFr
SPd
LCr
USP
OPr
ULn
tHr
tHd
LFt
LFr
APH
rtH

Menu 2 - REGOLAZIONI
Codice
LFr
ACC
dEC
AC2
dE2
LSP
HSP
FLG
StA

Codice
ItH
IdC
tdC
SdC
JPF
JF2
JF3
USC
tLS
UFr
SLP
SP2
SP3
SP4
SP5
SP6
SP7
Ctd
JOG
JGt
tL2
PFL
rPG
rIG
FbS
PIC
brL
Ibr
brt
bEn
bEt
FFt
bIP
dtS
Ftd
F2d
ttd
PSP
PI2
PI3
dtd

ITALIANO

Funzione
Rif. Freq. - Hz
Accelerazione - s
Decelerazione - s
Accel. 2
- s
Decel. 2
- s
Piccola vel. - Hz
Grande vel. - Hz
Guadagno
- %
Stabilità - %

Funzione
I Thermica - A
I Iniez. DC - A
Tempo Ini.DC- s
I arresto DC - A
Fréq mascher.- Hz
Fréq mascher2- Hz
Fréq mascher3- Hz
Coef. Macchina
Tempo LSP
- s
Compens. RI - %
Comp.Scorr. - %
Vel.Presel.2- Hz
Vel.Presel.3- Hz
Vel.Presel.4- Hz
Vel.Presel.5- Hz
Vel.Presel.6- Hz
Vel.Presel.7- Hz
Rilevamento I - A
Freq. Jog
- Hz
Tempo JOG
- s
Lim. Coppia 2- %
Profilo U/f
- %
Guadagno Prop.PI
Guadagno Int.PI - /s
Coef. Rit. PI
Inversione PI
F.AperturaFreno- Hz
I AperturaFreno- A
T.AperturaFreno- s
F.Chius.Freno- Hz
T.Chius.Freno- s
Soglia int. NST- Hz
Imp.Apert.Freno
Coef. Rit. DT
Rilev.Freq - Hz
Rilev. Freq.2 - Hz
Rilev.Term- %
Filtro PI
- s
Rif. PI2
- %
Rif. PI3
- %
Rilev. Term. var.

287

GP_ATV58_IT.fm Page 288 Mardi, 2. avril 2002 5:51 17

Sintesi dei menu

Menu 3 - CONTROLLO
Funzione
U Nom. Mot. - V
Freq.Nom.Mot- Hz
I Nom. Mot - A
Vel.Nom.Mot -rpm
Cos Phi Mot
Auto tuning
Freq. Max
- Hz
Risparmio Energetico
Adatt. I lim
AdattRampDec
F.Com.Rampa2- Hz
Tipo arresto
Tipo Rampa
Coef.RampaDEC
Lim. Coppia - %
ILim.interna- A
Iniez. DC Auto
Coef. P mot.
Type Commutaz.
Fréq.Commutaz.-kHz
Riduzione rumore
Moteur Spécial
Tipo di GI
N. Impulsi

Codice
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

ITALIANO

Menu 4 - COMANDO
Funzione
Conf. Morsett.
Tipo 2 fili
Inibiz. RV
Livell./Epiet
Rif.Min AI2- mA
Rif.Maxi AI2- mA
Val.Min AO - mA
Val.Maxi AO - mA
Mem.Riferim.
Com.Terminale
Prior. STOP
Indirizzo Var.
BdRate RS485
Reset cpts

288

Codice
tCC
tCt
rIn
bSP
CrL
CrH
AOL
AOH
Str
LCC
PSt
Add
tbr
rPr

Menu 5 - CONFIGURAZIONE I/O
Funzione
Config LI2
Config LI3
Config LI4
Config LI5
Config LI6
NO:Non config
RV :Indietro
RP2:Comm. Rampa
JOG:JOG Impuls.
+SP: + veloce
-SP: - veloce
PS2: 2Vel.Presel
PS4: 4Vel.Presel
PS8: 8Vel.Presel
RFC:Commut. Rif.
NST:StpRuotsLibera
DCI:ArrestoIniez.DC
FST:Arresto Rapido
CHP:Commut Mot.
TL2:Lim.Coppia 2
FLO:Forzatura Loc.
RST:Reset Difetti
ATN:Auto tuning
PAU:AutoMan PI
PR2:2RIF.
PI
PR4:4RIF.
PI
TLA:LimitCoppia
EDD:Dif.esterno
Config R2
Config LO
NO:Non config
RUN: Var.InMarcia
OCC:Cdo Contatt.
FTA:Soglia F. Rag.
FLA:HSP Raggiunta
CTA:Soglia I rag.
SRA:Rif. Vel.Rag.
TSA:SogliaTerm.Ragg
BLC:LogicaFreno
APL:Interruzione 4-20mA
F2A:Soglia F2 Ragg
TAD:All.ter.var.

Codice
L12
L13
L14
L15
L16

r2
LO

GP_ATV58_IT.fm Page 289 Mardi, 2. avril 2002 5:51 17

Sintesi dei menu

Menu 5 - CONFIGURAZIONE I/O (segue)
Funzione
Config AI2
Config AI3
NO:Non config
FR2:Rif. Vel. 2
SAI:Rif. Sommat.
PIF:Retorno PI
PIM:Rif Man PI
SFB:Ritorno DT
PTC:Sonde PTC
ATL:Lim. Coppia
Config AI3(encoder)
NO:Non config
SAI:Rif. Sommat.
RGI:Ritorno GI
Config AO
NO:Non config
OCR:Corrente Mot.
OFR:Freq. Mot.
ORP:Uscita Rampa
TRQ:Coppia mot.
STQ:Coppia con segno
ORS:Rampa con segno
OPS:Conf. PI
OPF:Ritorno PI
OPE:Errore PI
OPI:Integ PI
OPR:Pot Motore
tHR:Stato TerMotore
tHD:Stato TerVar.

Codice
AI2
AI3

AI3

Menu 6 - DIFETTI
Funzione
Riavv. Autom.
Tipo Reset
Interr. fase Mot
Interr. fase rete
Tipo Prot. Term.
Interr. 4-20mA
Vel.Rotazione.4-20
Ripresa al volo
Arresto inter. rete
Cont Anti-Rot
Dif.esterno.

Codice
Atr
rSt
OPL
IPL
tHt
LFL
LFF
FLr
StP
Sdd
EPL

Menu 7 - FILE
AO

Funzione
Stato file
Stato file
Stato file
Stato file
Operazione
Cod. Conf.

1
2
3
4

Codice
FI5
F25
F35
F45
FOt
COd

Menu 8 - COMUNICAZIONE
Consultare la documentazione fornita
con la scheda di communicazione

Menu 8 - APPLICAZIONE
Consultare la documentazione fornita
con la scheda di applicazione

ITALIANO
289

GP_ATV58_IT.fm Page 290 Mardi, 2. avril 2002 5:51 17

ITALIANO

Indice

Funzione

Menu

Accelerazione

REGOLAZIONI-CONTROLLO

248-256

Adattamento automatico rampa

CONTROLLO

256

Anello di velocità con dinamo

REGOLAZIONI - CONFIGURAZIONE I/O

253-263-264-271

Anello di velocità con encoder

CONTROLLO - CONFIGURAZIONE I/O

258-263-264-272

Arresto controllo

CONFIGURAZIONE I/O - DIFETTI

262-278

Auto tuning

CONTROLLO - CONFIGURAZIONE I/O

255-262-270

Codice confidenziale

FILE

280

Comando 2fili/3fili

COMANDO

259-267

Commutazione dei motore

CONTROLLO - CONFIGURAZIONE I/O

257-262-270

Commutazione dei riferimenti

CONFIGURAZIONE I/O

262-269

Commutazione di rampa

REGOLAZIONI - CONTROLLO - CONFIG. I/O

248-256-262-264-267

Contattore a valle

CONFIGURAZIONEI/O

263-273

Coppia standard / forte coppia

IDENTIFICAZIONE (rIF)

245

Decelerazione

REGOLAZIONI - CONTROLLO

248-256

Entrata analogica AI2

COMANDO

260

Forzatura modo locale

COMANDO - CONFIGURAZIONE I/O

262-270

Frenatura mediante iniezione

REGOLAZIONI - CONTROLLO

249-251-257

Frequenza di commutazione

CONTROLLO

257

Frequenze mascherate

REGOLAZIONI

249

Indirizzo collegamento seriale

COMANDO

261

Ingressi configurabili

CONFIGURAZIONE I/O

262-263-264

Limitaz.tempo di velocità bassa

REGOLAZIONI

249

Limitazione di coppia

REGOLAZIONI - CONTROLLO - CONFIG. I/O

251-253-257-262-264270

Limitazione di corrente

CONTROLLO

256-257

Logica freno

REGOLAZIONI - CONFIGURAZIONE I/O

252-263-264-273-274

Memorizzazione riferimento

COMANDO

261

Passo-passo (JOG)

REGOLAZIONI - CONFIGURAZIONE I/O

251-252-262-264-267

Pliù veloce / meno veloce

CONFIGURAZIONE I/O

262-265-268

Priorità stop

COMANDO

261

Protezione termica motore

REGOLAZIONI - CONFIG. I/O - DEFAUTS

248-254-263-264-278

Regolaore PI

REGOLAZIONI- CONFIGURAZIONE I/O

253-263-264-271

Regolazione base / Memorizzazione

FILE

279

Reset dei difetti

CONFIGURAZIONE I/O - DIFETTI

262-265-270-277

Riaviamento automatico

DIFETTI

277

Ripresa auto. (ripresa al volo)

DIFETTI

278

Risparmio energetico

CONTROLLO

255

Sonde PTC

CONFIGURAZIONE I/O

263-271

Uscite configurabili

COMANDO - CONFIGURAZIONE I/O

261-263-264-273-274275

Velocità preselezionate

REGOLAZIONI - CONFIGURAZIONE I/O

250-252-262-264-269

290

Pagine

GP_ATV58_IT.fm Page 291 Mardi, 2. avril 2002 5:51 17

ITALIANO
291

ITALIANO

GP_ATV58_IT.fm Page 292 Mardi, 2. avril 2002 5:51 17

292

4_COUV.fm Page 155 Mardi, 2. avril 2002 6:22 18

VVDED397047

W9 1493589 01 13 A06

82475

2002-04

GP_ATV58_Page1.fm Page 1 Mardi, 2. avril 2002 6:18 18

Altvar 58

FRANÇAIS

Terminal d’exploitation

Page 2

Bedienterminal

Seite 118

Terminale di esercizio

Pagina 234

ITALIANO

Página 176

ESPAÑOL

Terminal de explotación

DEUTSCH

Page 60

ENGLISH

Display Module

1

FRANÇAIS

GP_ATV58_Page2-FR.fm Page 2 Mardi, 2. avril 2002 6:20 18

Avertissement
Ce document concerne l’utilisation de l’Altivar 58 avec
exclusivement :
- le terminal d’exploitation VW3A58101,
- éventuellement une carte extension d’entrées/sorties
VW3A58201 ou VW3A58202.
Certains modes, menus et fonctionnement peuvent être
modifiés si le variateur est équipé d’autres options. Consulter la documentation propre à chacune de ces options.
Depuis le début de sa commercialisation l'Altivar 58 a
bénéficié de fonctionnalités supplémentaires. Ce document tient compte de ces adjonctions. Son utilisation
avec les premiers appareils reste opérationnelle, mais
dans ce cas il est normal d'y voir décrits des paramètres
absents de ces variateurs.
Pour l’installation, le raccordement, la mise en service et
la maintenance, consulter le guide d’exploitation de l’Altivar 58 et le guide d’exploitation de la carte extension
d’entrées/sorties éventuelle.

2

Sommaire

Présentation _____________________________________________________________________ 4
Conseils pratiques / mise en service minimale __________________________________________ 7
Déverrouillage des menus avant programmation ________________________________________ 8
Accès aux menus _________________________________________________________________ 9
Accès aux menus - Principe de la programmation _______________________________________ 10
Les Macro-configurations __________________________________________________________ 11
Identification Variateur ____________________________________________________________ 13
Menu Surveillance _______________________________________________________________ 14

FRANÇAIS

Menu Réglages _________________________________________________________________ 16
Menu Entraînement ______________________________________________________________ 23
Menu Commande ________________________________________________________________ 27
Menu Affectation des entrées / sorties ________________________________________________ 30
Fonctions d’applications des entrées et sorties configurables ______________________________ 34
Menu Défauts ___________________________________________________________________ 45
Menu Fichier ___________________________________________________________________ 47
Menus Communication et Application/Assistance en exploitation/Maintenance ________________ 49
Maintenance ____________________________________________________________________ 50
Mémorisation configuration et réglages _______________________________________________ 53
Synthèse des menus _____________________________________________________________ 55
Index _________________________________________________________________________ 58

3

GP_ATV58_FR.fm Page 4 Mardi, 2. avril 2002 5:54 17

Présentation

Le terminal d’exploitation VW3A58101 est livré avec les variateurs ATV58••••M2 et ATV58••••N4.
Les variateurs ATV58••••••Z sont livrés sans terminal. Celui-ci peut être commandé séparément.

Montage du terminal sur le variateur :
FRANÇAIS

Pour monter le terminal sur un variateur ATV58••••••Z, ôter préalablement la trappe de protection.

POWE
R
FAUL z
T

POWE
R
FAUL z
T

ESC
FWD
REV

ENT
RUN

STOP
RESET

Le terminal d’exploitation peut être connecté et déconnecté sous tension. Si le terminal est déconnecté alors
que la commande du variateur par le terminal est validée, le variateur se verrouille en défaut SLF.

Montage déporté du terminal :
Utiliser l’ensemble référence VW3A58103, comprenant 1 câble avec connecteurs, les pièces nécessaires au
montage sur porte d’armoire et la notice de montage.

Signalisation en face avant de l'Altivar
Autres DEL, signalisation d’état avec cartes options communication.

4

POWER z

DEL verte POWER

allumée : Altivar sous tension

FAULT

DEL rouge FAULT

• allumée : Altivar en défaut
• clignotante : Altivar verrouillé suite à l’action de la
touche "STOP" du terminal ou suite à un
changement de configuration. Le moteur ne peut
alors être alimenté qu’après une remise à zéro
préalable des ordres "avant", "arrière", "arrêt par
injection".

GP_ATV58_FR.fm Page 5 Mardi, 2. avril 2002 5:54 17

Présentation
☞ Avant de mettre l’Altivar sous tension et avant d’utiliser le terminal :

Point de fonctionnement préréglé :

1
ou
50 Hz

60 Hz

Position 50 Hz (réglage usine) :
- 230 V 50 Hz pour ATV-58••••M2
- 400 V 50 Hz pour ATV-58••••N4
Position 60 Hz :
- 230 V 60 Hz pour ATV-58••••M2
- 460 V 60 Hz pour ATV-58••••N4

Le terminal d’exploitation permet :
- la visualisation de l’identification variateur, de grandeurs électriques, des paramètres d’exploitation ou
des défauts,
- la reprise des réglages et de la configuration de l’Altivar,
- la commande locale par le clavier,
- la mémorisation et le rappel de configuration dans une mémoire non volatile du terminal.

☞ Retour aux réglages usine :
- éteindre le variateur,
- déverrouiller et ouvrir le capot de l’Altivar de manière à accéder au commutateur 50/60 Hz 1 de la carte
contrôle. Si une carte option est présente, le commutateur reste accessible au travers de celle-ci,
- changer de position le commutateur 50/60 Hz 1 de la carte contrôle,
- mettre le variateur sous-tension,
- éteindre le variateur,
- remettre le commutateur 50/60 Hz 1 de la carte contrôle à sa position initiale (fréquence nominale moteur),
- mettre le variateur sous-tension, celui-ci reprend sa configuration usine.

5

FRANÇAIS

Déverrouiller et ouvrir le capot de l’Altivar de manière à
accéder au commutateur 50/60 Hz 1 de la carte contrôle. Si
une carte option est présente, le commutateur reste
accessible au travers de celle-ci.
Positionner le commutateur dans la position 50 ou 60 Hz
correspondant à votre moteur.

GP_ATV58_FR.fm Page 6 Mardi, 2. avril 2002 5:54 17

Présentation

Vue face avant

FRANÇAIS

LOC

PROG

ESC
ENT
FWD
REV

RUN

Utilisation des touches et signification des affichages
 Ú
Signalisation clignotante :
indique le sens de rotation sélectionné
Signalisation fixe :
indique le sens de rotation du moteur
LOC
Indique le mode de commande par la console
PROG Apparaît en mode mise en service et programmation
Signalisation clignotante :
indique une modification de valeur non mémorisée
Afficheur 4 caractères :
affichage de valeurs numériques et de codes
Une ligne de 16 caractères :
affichage en clair des messages

STOP
RESET

Déplacement dans les menus ou les paramètres et réglage d’une valeur.
ESC

Retour au menu précédent, ou abandon d’un réglage en cours et retour à la valeur d’origine.

ENT

Sélection d’un menu, validation avec mémorisation d’un choix ou d’un réglage.

Si la commande par le terminal est sélectionnée :
FWD
REV

RUN
STOP
RESET

Inverse le sens de rotation.
Ordre de mise en rotation du moteur.
Ordre d’arrêt du moteur ou réarmement du défaut. La fonction "STOP" de la touche peut
être inhibée par programmation (menu "COMMANDE").

Vue face arrière

Connecteur :
- pour le raccordement direct du terminal au variateur
- pour utilisation à distance, le terminal peut être raccordé par un
câble fourni dans l’ensemble VW3A58103.
Commutateur de verrouillage d’accès :

6

- position

: Réglage et configuration non accessibles

- position

: Réglage accessible

- position

: Réglage et configuration accessibles

GP_ATV58_FR.fm Page 7 Mardi, 2. avril 2002 5:54 17

Conseils pratiques / mise en service minimale

Conseils pratiques :
Préparez d'abord votre programmation en remplissant les feuilles de mémorisation de configuration et
réglages (à la fin de ce document).

ATTENTION : Il faut s’assurer que les fonctions programmées soient compatibles avec le schéma
de câblage utilisé. En particulier, l’ATV-58E équipé nécessite cette vérification en cas de
modification de la configuration usine; modifier aussi le schéma si nécessaire.

Mise en service minimale :
Cette procédure peut être utilisée :
- dans les applications simples où les réglages usine du variateur conviennent,
- dans des phases de montage où il est nécessaire de faire tourner le moteur provisoirement avant
d’effectuer la mise en œuvre complète.

Procédure :
1 Suivre les recommandations du guide d’exploitation fourni avec le variateur, notamment en positionnant le
commutateur 50/60 Hz sur la fréquence nominale du moteur.
2 S’assurer que la macro-configuration usine convient, et dans le cas contraire la changer dans le menu
«MACRO-CONFIG».
3 Pour les variateurs de puissances supérieures à 7,5 kW en 200/240 V et 15 kW en 380/500 V en application
"couple standard", configurer la puissance dans le menu «IDENTIFICATION».
4 Vérifier que le schéma de câblage est compatible avec la macro-configuration de façon à assurer toute
la sécurité nécessaire, dans le cas contraire modifier le schéma.
5 Vérifier dans le menu «ENTRAINEMENT» que les paramètres usine soient compatibles avec ceux inscrits
sur la plaque signalétique du moteur, dans le cas contraire les modifier.
6 Dans le menu «ENTRAINEMENT» effectuer un autoréglage.
7 Si nécessaire ajuster les paramètres du menu «REGLAGES» (rampes, I thermique, etc...).

7

FRANÇAIS

La programmation de l'Altivar 58 est facilitée par des aiguillages et verrouillages internes. Afin de bénéficier
pleinement de ce confort, nous vous recommandons d'accéder aux menus dans l'ordre suivant. Toutes les
étapes ne sont pas obligatoires dans tous les cas.
↓ LANGUE
MACRO-CONFIG
IDENTIFICATION
COMMANDE (si commande 3 fils seulement)
AFFECTATION I/O
COMMANDE
ENTRAINEMENT
DEFAUTS
↓ COMMUNICATION ou APPLICATION si une carte est utilisée
REGLAGES

GP_ATV58_FR.fm Page 8 Mardi, 2. avril 2002 5:54 17

Déverrouillage des menus avant programmation

Niveau d’accès / Mode d’utilisation

FRANÇAIS

La position du commutateur de verrouillage offre trois niveaux d’accès aux menus en fonction de la phase
d’utilisation de votre machine. L'accès aux menus peut également être verrouillé par un code d'accès (voir
menu fichiers).
Position
-

Visualisation : utiliser pendant les phases d’exploitation.

Menu LANGUE : Vous pouvez sélectionner la langue de dialogue.
Menu MACRO-CONFIG : Vous pouvez visualiser la macro-configuration.
Menu IDENTIFICATION : Vous pouvez visualiser la tension et la puissance du variateur.
Menu SURVEILLANCE : Vous pouvez visualiser des grandeurs électriques, la phase de fonctionnement
ou un défaut.

Position

Visualisation et réglages : utiliser pendant les phases de mise en service.

- Vous pouvez exécuter toutes les opérations possibles en niveau 0.
- Menu REGLAGES : Vous pouvez régler l’ensemble des paramètres accessibles moteur en rotation.
Position

Accès total : utiliser pendant les phases de programmation.

- Vous pouvez exécuter toutes les opérations possibles en niveaux 0 et 1.
- Menu MACRO-CONFIG : Vous pouvez changer la macro-configuration.
- Menu IDENTIFICATION : Vous pouvez changer la puissance en "couple standard" ou "fort couple", pour
les calibres concernés par ce paramètre.
- Menu ENTRAINEMENT : Vous pouvez ajuster les performances de l’ensemble moto variateur.
- Menu COMMANDE : Vous pouvez configurer la commande du variateur : par les borniers, par le terminal
ou par la liaison série RS485 intégrée.
- Menu AFFECTATION I/O : Vous pouvez changer l’affectation des entrées/sorties.
- Menu DEFAUTS : Vous pouvez configurer les protections moteur et variateur et le comportement en cas
de défaut.
- Menu FICHIER : Vous pouvez mémoriser, rappeler des configurations variateur mémorisées dans le
terminal, retourner aux réglages usine ou protéger votre configuration.
- Menu COMMUNICATION, si une carte de communication est installée : Vous pouvez régler les
paramètres d’un protocole de communication.
- Menu APPLICATION, si une carte «application client» est installée. Consulter la documentation
spécifique à cette carte.

8

GP_ATV58_FR.fm Page 9 Mardi, 2. avril 2002 8:32 20

Accès aux menus

Le nombre de menus accessibles est fonction de la position du commutateur de verrouillage.
Chaque menu est composé de paramètres.
Mises sous tension
suivantes

1 re mise
sous tension

FRANÇAIS

LANGUE

LnG

-5+

CFG

MACRO-CONFIG

rEF

Identification

0.37 kW 200/240 V

SUP

1-SURVEILLANCE

SEt

2-REGLAGES

drC

3-ENTRAINEMENT

CtL

4-COMMANDE

L’indication PROG est
affichée sur
le terminal

I-O

5-AFFECTATION I/O

FLt

6-DEFAUTS

FLS

7-FICHIER

accessible uniquement si la
carte «application client» est
installée

APP

8-APPLICATION

SL

8-COMMUNICATION

accessible uniquement
si la carte protocole est
installée

ATTENTION : Si un code d’accès a été précédemment programmé, certains menus peuvent être rendus non
modifiables, voire même invisibles. Dans ce cas reportez-vous au chapitre “menu FICHIER” pour entrer le
code d’accès.

9

GP_ATV58_FR.fm Page 10 Mardi, 2. avril 2002 5:54 17

Accès aux menus - Principe de la programmation

Langue :
Ce menu est accessible quelle que soit la position du commutateur, il est modifiable à l’arrêt ou en marche.

FRANÇAIS

Exemple :
ENT

LANGUE

LnG

LnG

English

LnG

Italiano

Retour au choix
précédemment mémorisé

Mémorisation
du nouveau choix

ESC

ENT

ESC

LnG

LnG

Italiano

English

Choix possible : Anglais (réglage usine), Français, Allemand, Espagnol, Italien.

Principe de la programmation :
Le principe est toujours le même, avec 1 ou 2 niveaux :
• 1 niveau : voir l’exemple “langue“ ci-dessus.
• 2 niveaux : voir l’exemple “rampe d’accélération“ ci-dessous.
ENT

SEt

ENT

ACC

Accélération

2.REGLAGES

3.0

s

Accélération

Augmentation

ESC

s

(ou

Diminution)

3.1

Accélération

ESC

Retour à la valeur
précédente

ENT

ESC

3.1

Accélération

10

s

Mémorisation
de la nouvelle
valeur

s

3.0

Accélération

s

GP_ATV58_FR.fm Page 11 Mardi, 2. avril 2002 5:54 17

Les Macro-configurations

Ce paramètre est toujours visualisable mais n’est modifiable qu’en mode programmation (commutateur de
verrouillage en position
) et à l’arrêt, variateur verrouillé.

Une macro-configuration affecte automatiquement les entrées/sorties et des paramètres, mettant alors en
service les fonctions nécessaires à l’application. Les paramètres liés aux fonctions programmées sont
disponibles.

Réglage usine : Manutention
Variateur :
Affectations des entrées / sorties en fonction de la macro-configuration
Hdg : Manutention

GEn : Usage Gén.

VT : C. Variable

Entrée logique LI1

sens avant

sens avant

sens avant

Entrée logique LI2

sens arrière

sens arrière

sens arrière

Entrée logique LI3

2 vitesses présél.

marche pas à pas

commutation référence

Entrée logique LI4

4 vitesses présél.

arrêt roue libre (1)

freinage par injection

Entrée ana. AI1

réf. sommatrice

réf. sommatrice

réf. vitesse 1

Entrée ana. AI2

réf. sommatrice

réf. sommatrice

réf. vitesse 2

Relais R1

défaut variateur

défaut variateur

défaut variateur

Relais R2

Cde contacteur aval

état thermique mot. att

consigne fréq. att

Sortie ana. AO1

fréquence moteur

fréquence moteur

fréquence moteur

Cartes extensions :
Affectations des entrées / sorties en fonction de la macro-configuration
Hdg : Manutention

GEn : Usage Gén.

Entrée logique LI5

8 vitesses présél.

effacement défaut

VT : C. Variable
arrêt roue libre (1)

Entrée logique LI6

effacement défaut

limitation de couple

commutation de rampe

Entrée ana. AI3
ou
Entrées A, A+, B, B+

réf. sommatrice

réf. sommatrice

NO

retour vitesse

retour vitesse

retour vitesse

Sortie logique LO

seuil courant atteint

Cde contacteur aval

grande vitesse atteinte

Sortie ana. AO

courant moteur

courant moteur

courant moteur

(1) Pour démarrer, l'entrée logique doit être reliée au + 24 V (fonction active à 0)
ATTENTION : Il faut s’assurer que la macro-configuration programmée est compatible avec
le schéma de câblage utilisé. En particulier, l’ATV-58E équipé nécessite cette vérification en cas
de modification de la configuration usine; modifier aussi le schéma si nécessaire.

11

FRANÇAIS

Il permet une configuration automatique à un métier. Trois métiers sont disponibles.
- Manutention (Hdg)
- Couple variable pour les applications pompes et ventilateurs (VT)
- Usage général (GEn)

GP_ATV58_FR.fm Page 12 Mardi, 2. avril 2002 5:54 17

Les Macro-configurations

FRANÇAIS

La modification de la macro-configuration nécessite une double confirmation car elle entraîne des
affectations automatiques de fonctions et un retour au réglage usine.
Affichage de l’écran suivant :

CHG

CABLAGE OK?

ENT

ENT pour valider la modification
ESC pour retourner à la configuration précédente

Personnalisation de la configuration :
La configuration du variateur peut être personnalisée en changeant l’affectation des entrées/sorties dans le
menu Affectation I/O accessible en mode programmation (commutateur de verrouillage en position
).
Cette personnalisation modifie la valeur de la macro-configuration affichée :
affichage de

CFG

CUS:Personnalisé

12

GP_ATV58_FR.fm Page 13 Mardi, 2. avril 2002 5:54 17

Identification Variateur

Identification Variateur
Ce paramètre est toujours visualisable. Il indique la puissance et la tension du variateur indiquées sur
l’étiquette signalétique.
L'affichage de la puissance est en kW si le commutateur 50/60 Hz du
variateur est sur 50 Hz, et en HP s'il est sur 60 Hz.

Cas des variateurs de puissances supérieures à 7,5 kW en 200/240 V et 15 kW en 380/500 V :
Leur puissance est différente selon l'application à couple standard ou à fort couple. Les variateurs sont livrés
en configuration usine à "fort couple". La configuration "couple standard" s'obtient de la manière suivante :

ENT

22 kW

rEF

rEF clignote
22 kW

380/500 V

rEF clignote

rEF
380/500 V

+30 kW

rEF
380/500 V

ou ESC

ESC

ENT

+30 kW

rEF
380/500 V

+30 kW

rEF
380/500 V

ESC

En application à "couple standard" le signe + précède la puissance en kW.
Le retour à la configuration "fort couple" s'effectue selon le même processus.
La configuration "couple standard" ou "fort couple" préconfigure le "réglage usine" de certains paramètres :
• menu "Entraînement" : UnS, nCr, nSP, COS, tUn
• menu "Réglages" : ItH, IdC.
Le passage de l'une à l'autre de ces configurations de couple entraîne donc un retour aux
réglages usine de tous ces paramètres.

13

FRANÇAIS

rEF

0.37 kW 200/240 V

GP_ATV58_FR.fm Page 14 Mardi, 2. avril 2002 5:54 17

Menu Surveillance

Menu Surveillance (choix du paramètre affiché en fonctionnement)
Les paramètres suivants sont accessibles quelle que soit la position du commutateur, à l’arrêt ou en marche.

FRANÇAIS

Code

--rdY
rUn
ACC
dEC
CLI
dCb
nSt
Obr
FrH

Fonction

Unité

Etat var.

–

Etat du variateur : indique un défaut, ou la phase de fonctionnement du moteur :
rdY = variateur prêt,
rUn = moteur en régime établi ou ordre de marche présent et référence nulle,
ACC = en accélération,
dEC = en décélération,
CLI = en limitation de courant,
dCb = en freinage par injection,
nSt = en commande d’arrêt roue libre,
Obr = freinage en adaptant la rampe de décélération (voir le menu "entraînement").

Réf. Fréq

Hz

Référence fréquence

rFr

Fréq. Sortie

Hz

Fréquence de sortie appliquée au moteur

SPd

Vitesse mot.

rpm

Vitesse moteur estimée par le variateur

LCr

Courant mot.

A

Courant moteur

USP

Vit.Machine

–

Vitesse machine estimée par le variateur. Elle est proportionnelle à rFr, suivant un coefficient USC
ajustable dans le menu "Réglages". Cela permet l'affichage d'une valeur correspondant à
l'application (mètres / seconde par exemple). Attention, si USP devient supérieure à 9999 l'affichage
est divisé par 1000.

OPr

Puiss.Sortie

%

Puissance fournie par le moteur, estimée par le variateur. 100 % correspond à la puissance
nominale.

ULn

U réseau

V

Tension réseau

tHr

Therm. mot.

%

Etat thermique : 100% correspond à l’état thermique nominal du moteur. Au-delà de 118%, le
variateur déclenche en défaut OLF (surcharge moteur)

tHd

Therm. var.

%

Etat thermique du variateur : 100% correspond à l’état thermique nominal du variateur. Au-delà de
118%, le variateur déclenche en défaut OHF (surchauffe variateur). Il est réenclenchable en dessous
de 70 %.

LFt

Dernier déf.
Affiche le dernier défaut apparu.

14

–

GP_ATV58_FR.fm Page 15 Mardi, 2. avril 2002 5:54 17

Menu Surveillance

Code

Fonction

Unité

LFr

Ref. Fréq.

Hz

Ce paramètre de réglage apparaît à la place du paramètre FrH lorsque la commande variateur par
la console est activée : paramètre LCC du menu commande.

Consommation

kWh ou MWh

Energie consommée.

rtH

Temps marche

h

Temps de fonctionnement continu (moteur sous tension), en heures.

15

FRANÇAIS

APH

GP_ATV58_FR.fm Page 16 Mardi, 2. avril 2002 5:54 17

FRANÇAIS

Menu Réglages

Ce menu est accessible dans les positions
et
du commutateur. La modification des
paramètres de réglage est possible à l’arrêt OU en fonctionnement. S’assurer que les changements en
cours de fonctionnement sont sans danger; les effectuer de préférence à l’arrêt.
La liste des paramètres de réglages est composée d’une partie fixe, et d’une partie évolutive qui varie
en fonction :
- de la macro-configuration choisie
- de la présence ou non d’une carte extension entrées/sorties
- de réaffectations d’entrées/sorties
Les paramètres suivants sont accessibles dans toutes les macro-configurations.
Code

Description

LFr

Réf. Fréq.

- Hz

Plage de réglage

Réglage usine

LSP à HSP

–

Apparaît lorsque la commande variateur par le terminal est activée : paramètre LCC du menu
commande

ACC
dEC

Accélération - s
Décélération - s

0,05 à 999,9
0,05 à 999,9

3s
3s

Temps des rampes d’accélération et de décélération. Définis pour aller de 0 à la fréquence
nominale moteur (FrS)

AC2
dE2

Accél. 2
Décél. 2

- s
- s

0,05 à 999,9
0,05 à 999,9

5s
5s

2e temps de la rampe d’accélération
2e temps de la rampe de décélération
Ces paramètres sont accessibles si le seuil de commutation de rampe (paramètre Frt) est différent
de 0 Hz ou si une entrée logique est affectée à la commutation de rampe.

LSP

Petite vit.

- Hz

0 à HSP

0 Hz

- Hz

LSP à tFr

50 / 60 Hz en fonction du
commutateur

Petite vitesse

HSP

Grande vit.

Grande vitesse : s’assurer que ce réglage convient au moteur et à l’application.

FLG

Gain

- %

0 à 100

20

Gain de boucle fréquence : permet d’adapter la rapidité des transitoires de vitesse de la machine
en fonction de la cinématique. Pour les machines à fort couple résistant ou inertie importante, à
cycles rapides, augmenter progressivement le gain.

StA

Stabilité

- %

0 à 100

20

Permet d’adapter l’atteinte du régime établi après un transitoire de vitesse en fonction de la
cinématique de la machine. Augmenter progressivement la stabilité pour supprimer les
dépassements en vitesse.

ItH

I Thermique

- A

0,25 à 1,36 In (1)

Selon calibre variateur

Courant utilisé pour la protection thermique moteur. Régler ItH à l’intensité nominale lue sur la
plaque signalétique moteur.
(1) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur en application à fort couple.

16

GP_ATV58_FR.fm Page 17 Mardi, 2. avril 2002 5:54 17

Menu Réglages

Code

Description

tdC

Temps Inj.DC-

s

Plage de réglage

Réglage usine

0 à 30 s Cont

0,5 s

SdC

I arrêt DC

-

A

0,1 à 1,36 In (1)

Selon calibre variateur

Intensité du courant de freinage par injection appliqué au bout de 30 secondes si tdC = Cont.
S'assurer que le moteur supporte ce courant sans surchauffe.

JPF

Fréq Occult.- Hz

0 à HSP

0 Hz

Fréquence occultée : interdit un fonctionnement prolongé sur une plage de fréquence de +/-2,5 Hz
autour de JPF. Cette fonction permet de supprimer une vitesse critique qui entraîne une résonance.

JF2

Fréq.Occult2- Hz

0 à HSP

0 Hz

2 e fréquence occultée : même fonction que JPF, pour une 2 e valeur de fréquence.

JF3

Fréq.Occult3- Hz

0 à HSP

0 Hz

3 e fréquence occultée : même fonction que JPF, pour une 3 e valeur de fréquence

USC

Coef.Machine

0,01 à 100

1

Coefficient appliqué au paramètre rFr (fréquence de sortie appliquée au moteur) permettant
l'affichage de la vitesse machine par le paramètre USP
USP = rFr x USC

tLS

Temps LSP

-

s

0 à 999.9

0 (pas de limitation de temps)

Temps de fonctionnement en petite vitesse. Suite à un fonctionnement en LSP pendant le temps
défini, l’arrêt du moteur est demandé automatiquement. Le moteur redémarre si la référence
fréquence est supérieure à LSP et si un ordre de marche est toujours présent. Attention, la valeur
0 correspond à un temps non limité
(1) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur en application à fort couple.

17

FRANÇAIS

Temps de freinage par injection de courant continu. Si on augmente au-delà de 30 s, affichage de
"Cont", Injection de courant permanente. Le courant d'injection devient égal à SdC au bout de 30
secondes.

GP_ATV58_FR.fm Page 18 Mardi, 2. avril 2002 5:54 17

Menu Réglages

FRANÇAIS

Les paramètres suivants sont accessibles en macro-configuration ‘manutention’
Code

Description

UFr

Compens. RI -

%

Plage de réglage

Réglage usine

0 à 150% ou 0 à 800%

100%

Permet d’ajuster la valeur par défaut ou mesurée lors de l’autoréglage. La plage de réglage est
étendue à 800 % si le paramètre SPC (moteur spécial) du menu entraînement est “oui”.

SLP

Comp.Gliss. -

%

0 à 150%

100%

Permet d’ajuster la compensation de glissement autour de la valeur fixée par la vitesse nominale
moteur.

SP2

Vit.Présél.2- Hz

LSP à HSP

10 Hz

LSP à HSP

15 Hz

LSP à HSP

20 Hz

LSP à HSP

25 Hz

LSP à HSP

30 Hz

LSP à HSP

35 Hz

0 à 1.36 In (1)

1.36 In (1)

2 e vitesse présélectionnée

SP3

Vit.Présél.3- Hz
3 e vitesse présélectionnée

SP4

Vit.Présél.4- Hz
e

4 vitesse présélectionnée

SP5

Vit.Présél.5- Hz
5 e vitesse présélectionnée

SP6

Vit.Présél.6- Hz
6 e vitesse présélectionnée

SP7

Vit.Présél.7- Hz
7 e vitesse présélectionnée

Ctd

Détection I -

A

Seuil de courant au-delà duquel la sortie logique, ou le relais passe à l’état 1
(1) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur, en application à "fort couple"

18

GP_ATV58_FR.fm Page 19 Mardi, 2. avril 2002 5:54 17

Menu Réglages

Les paramètres suivants sont accessibles en macro-configuration ‘usage général’
Code

UFr

Description

Compens. RI -

%

Plage de réglage

Réglage usine

0 à 150% ou 0 à 800%

100%

SLP

Comp.Gliss. -

%

0 à 150%

FRANÇAIS

Permet d’ajuster la valeur par défaut ou mesurée lors de l’autoréglage. La plage de réglage est
étendue à 800% si le paramètre SPC (moteur spécial) du menu entraînement est "oui".
100%

Permet d’ajuster la compensation de glissement autour de la valeur fixée par la vitesse nominale
moteur.

JOG

Fréq. Jog

- Hz

0 à 10 Hz

10 Hz

Fréquence de fonctionnement en marche pas à pas.

JGt

Tempo JOG

-

s

0à2s

0.5 s

Temporisation d’anti-pianotage entre deux marches pas à pas consécutives

tL2

Lim. Couple 2- %

0 à 200% (1)

200%

Deuxième niveau de limitation de couple activé par une entrée logique
Les paramètres suivants sont accessibles en macro-configuration ‘couple variable’
Code

IdC

Description

I Inj. DC

- A

Plage de réglage

Réglage usine

0,10 à 1,36 In (2)

Selon calibre variateur

Intensité du courant de freinage par injection de courant continu. Au bout de 30 secondes le courant
d'injection est écrêté à 0,5 Ith s'il est réglé à une valeur supérieure.

PFL

Profil U/f

- %

0 à 100%

20%

Permet d’ajuster la loi d’alimentation quadratique lorsque la fonction économie d’énergie a été
inhibée.
(1) 100% correspond au couple nominal d’un moteur d’une puissance égale à celle associée au variateur en
application à fort couple.
(2) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur, en application à "fort couple".
Les paramètres grisés apparaissent si une carte extension entrées/sorties est installée.

19

GP_ATV58_FR.fm Page 20 Mardi, 2. avril 2002 5:54 17

Menu Réglages

Les paramètres suivants peuvent être accessibles suite à une réaffectation des entrées/sorties du produit de base.
Code

Description

AC2

Accél. 2

-

s

Plage de réglage

Réglage usine

0.05 à 999.9

5s

FRANÇAIS

2 e temps de la rampe d’accélération

dE2

Décél. 2

-

s

0.05 à 999.9

5s

2e

temps de la rampe de décélération. Ces paramètres sont accessibles si le seuil de commutation
de rampe (paramètre Frt) est différent de 0 Hz ou si une entrée logique est affectée à la
commutation de rampe.

IdC

I Inj. DC

-

A

0,10 à 1,36 In (1)

Selon calibre variateur

Intensité du courant de freinage par injection de courant continu. Ce paramètre est accessible si
une entrée logique est affectée à l’arrêt par injection de courant. Au bout de 30 secondes le courant
d'injection est écrêté à 0,5 Ith s'il est réglé à une valeur supérieure.

SP2

Vit.Présél.2- Hz
2e

SP3

LSP à HSP

10 Hz

LSP à HSP

15 Hz

LSP à HSP

20 Hz

LSP à HSP

25 Hz

LSP à HSP

30 Hz

LSP à HSP

35 Hz

0 à 10 Hz

10 Hz

vitesse présélectionnée

Vit.Présél.3- Hz
3 e vitesse présélectionnée

SP4

Vit.Présél.4- Hz
4 e vitesse présélectionnée

SP5

Vit.Présél.5- Hz
5 e vitesse présélectionnée

SP6

Vit.Présél.6- Hz
6e

SP7

vitesse présélectionnée

Vit.Présél.7- Hz
7 e vitesse présélectionnée

JOG

Freq. Jog

- Hz

Fréquence de fonctionnement en marche pas à pas

JGt

Tempo JOG

-

s

0à2s

0.5 s

Temporisation d’anti-pianotage entre deux marches pas à pas consécutives

brL

F.LevéeFrein- Hz

0 à 10 Hz

0 Hz

0 à 1,36 In(1)

0A

0à5s

0s

0 à LSP

0 Hz

0à5s

0s

Fréquence de levée de frein

Ibr

I levéeFrein-

A

Courant de levée de frein

brt

T.levéeFrein-

s

Temps de levée de frein

bEn

F.Ferm.Frein- Hz
Fréquence de fermeture du frein

bEt

T.Ferm.Frein- Hz
Temps de fermeture du frein

(1) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur en application à "fort couple".

20

GP_ATV58_FR.fm Page 21 Mardi, 2. avril 2002 5:54 17

Menu Réglages

Code

Description

Plage de réglage

Réglage usine

FFt

SeuilDéc NST- Hz

0 à HSP

0 Hz

bIP

Imp. Lev. Frein

non-OUI

non

Impulsion de levée de frein
OUI : le couple pendant la levée du frein est toujours dans le sens FW (avant) quel que soit le sens
demandé.
Vérifier que le sens du couple moteur en commande FW (avant) correspond au sens de
montée de la charge, inverser si nécessaire 2 phases du moteur.
non : le couple pendant la levée du frein est dans le sens de rotation demandé.

dtS

Coef. Ret. DT

1à2

1

Coefficient mutiplicateur du retour associé à la fonction dynamo tachymétrique :
dtS =

rPG

9
tension dynamo à vitesse maxi

Gain Prop.PI

0.01 à 100

1

Gain proportionnel du régulateur PI

rIG

Gain

Int. PI

0.01 à 100 /s

1/s

1 à 100

1

Gain intégral du régulateur PI

FbS

Coef. Ret. PI

Coefficient mutiplicateur du retour PI

PIC

Inversion PI

non - oui

non

Inversion du sens de correction du régulateur PI
non : normal
oui : inverse

Ftd

Détect.Fréq - Hz

LSP à HSP

50/60 Hz

Seuil de fréquence moteur au-delà duquel la sortie logique passe à l’état 1

F2d

Dét.Fréq.2

- Hz

LSP à HSP

50/60 Hz

2 e seuil de fréquence : même fonction que Ftd, pour une 2 e valeur de fréquence

Ctd

Détection I -

A

0 à 1.36 In (1)

1.36 In (1)

Seuil de courant au-delà duquel la sortie logique ou le relais passe à l’état 1

ttd

Détect.Therm-

%

0 à 118%

100%

Seuil de l’état thermique moteur au-delà duquel la sortie logique ou le relais passe à l’état 1

tL2

Lim.Couple 2 - %

0 à 200% (2)

200%

Deuxième niveau de limitation de couple activé par une entrée logique
(1) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur en application à "fort couple".
(2) 100% correspond au couple nominal d’un moteur d’une puissance égale à celle associée au variateur en
application à "fort couple".
Les paramètres grisés apparaissent si une carte extension entrées/sorties est installée.

21

FRANÇAIS

Seuil de déclenchement d'arrêt roue libre : sur demande d'arrêt sur rampe ou d'arrêt rapide, le type
d'arrêt sélectionné est activé jusqu'à ce que la vitesse descende sous ce seuil. En dessous de ce seuil
l'arrêt roue libre est activé. Paramètre accessible si le relais R2 n'est pas affecté à la fonction BLC :
logique de frein, et si le typed'arrêt est positionné sur "rampe" ou "rapide" dans le menu entraînement.

GP_ATV58_FR.fm Page 22 Mardi, 2. avril 2002 5:54 17

Menu Réglages

Code

Description

PSP

Filtre PI

- s

Plage de réglage

Réglage usine

0,0 à 10,0

0s

FRANÇAIS

Permet de régler la constante de temps du filtre sur le retour PI

PI2

Cons. PI2

- %

0 à 100 %

30 %

2 ème consigne présélectionnée du PI, lorsqu'une entrée logique a été affectée à la fonction 4
consignes PI présélectionnées.
100 % = maxi process
0 % = mini process

PI3

Cons. PI3

- %

0 à 100 %

60 %

3 ème consigne présélectionnée du PI, lorsqu'une entrée logique a été affectée à la fonction 4
consignes PI présélectionnées.
100 % = maxi process
0 % = mini process

dtd

Dét. Th. var.

0 à 118 %

105 %

Seuil de l'état thermique variateur au delà duquel la sortie logique ou le relais passe à 1.

22

GP_ATV58_FR.fm Page 23 Mardi, 2. avril 2002 5:54 17

Menu Entraînement

Ce menu est accessible dans la position
du commutateur.
Les paramètres ne sont modifiables qu’à l’arrêt, variateur verrouillé.
L’optimisation des performances d’entraînement est obtenue :
- en entrant les valeurs lues sur la plaque signalétique dans le menu entraînement,
- en déclenchant un auto-réglage (sur un moteur asynchrone standard).

Code

Description

UnS

U Nom. Mot. -

V

Plage de réglage

Réglage usine

200 à 240 V
200 à 500 V

230 V (2)
400/460V (2)

Tension nominale moteur lue sur la plaque signalétique. La plage de réglage dépend du modèle de
variateur :
ATV58••••M2
ATV58••••N4

FrS

Fréq.Nom.Mot- Hz

10 à 500 Hz

50/60Hz (2)

Fréquence nominale moteur lue sur la plaque signalétique

nCr

I Nom. Mot

-

A

0.25 à 1.36 In (1)

selon calibre variateur

Courant nominal moteur lu sur la plaque signalétique

nSP

Vit.Nom.Mot -rpm

0 à 9999 rpm

selon calibre variateur

Vitesse nominale moteur lue sur la plaque signalétique.

COS

Cos Phi Mot

0.5 à 1

selon calibre variateur

Cosinus Phi moteur lu sur la plaque signalétique.

tUn

Auto réglage

non - oui

non

Permet d’effectuer un autoréglage de la commande du moteur après positionnement de ce
paramètre sur “oui”. Une fois l’autoréglage fait le paramètre repasse automatiquement sur “fait”, ou
“non“ en cas de défaut.
Attention : l'autoréglage s'effectue seulement si aucune commande n'est actionnée. Si une fonction
"arrêt roue libre" ou "arrêt rapide" est affectée à une entrée logique, il faut mettre cette entrée à 1
(active à 0).

tFr

Fréq. Max

- Hz

10 à 500 Hz

60/72Hz (2)

Fréquence maximale de sortie. La valeur maxi est fonction de la fréquence de découpage. Voir
paramètre SFR (menu entraînement)

nLd

Eco Energie

non-oui

oui

Optimise le rendement moteur.
Accessible uniquement en macro-configuration couple variable.
(1) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur en application à "fort couple".
(2) selon position du commutateur 50/60 Hz

23

FRANÇAIS

Cas d’utilisation de moteurs spéciaux (moteurs en parallèle, moteurs freins à rotor conique ou à dérivation
de flux, moteurs synchrones ou asynchrones synchronisés, moteurs asynchrones à rotor résistant) :
- Sélectionner la macro-configuration “Hdg : Manutention” ou la macro-configuration “GEn : Usage Gén.”
- Configurer dans le menu entraînement le paramètre Moteur spécial “SPC” sur “oui”.
- Ajuster dans le menu "Réglages" le paramètre Compens. RI “UFr” pour obtenir un fonctionnement
satisfaisant.

GP_ATV58_FR.fm Page 24 Mardi, 2. avril 2002 5:54 17

FRANÇAIS

Menu Entraînement

Code

Description

Plage de réglage

Réglage usine

Fdb

Adapt. I lim

non-oui

non

Adaptation du courant de limitation en fonction de la fréquence de sortie. Ce paramètre n'apparaît
que dans la macro-configuration "couple variable" VT (applications de ventilation où la courbe de
charge évolue en fonction de la densité du gaz).

brA

AdaptRampDec

non-oui

non

L’activation de cette fonction permet d’augmenter automatiquement le temps de décélération, si
celui-ci a été réglé à une valeur trop faible compte tenu de l’inertie de la charge, évitant ainsi le
passage en défaut ObF. Cette fonction peut être incompatible avec un positionnement sur rampe
et avec l’utilisation d’une résistance de freinage. Le réglage usine dépend de la macro-configuration
utilisée : non en manutention, oui pour couple variable et usage général. Si le relais R2 est affecté
à la fonction logique de frein, le paramètre brA reste verrouillé sur non.

Frt

F.Com.Rampe2- Hz

0 à HSP

0 Hz

Fréquence de commutation de rampe. Lorsque la fréquence de sortie devient supérieure à Frt, les
temps de rampe pris en compte sont AC2 et dE2.

Stt

Type arrêt

STN - FST - NST - DCI

STN

Type d'arrêt.
Sur demande d'arrêt, le type d'arrêt est activé jusqu'au seuil FFt (menu "Réglages"). En dessous du
seuil l'arrêt se fait en roue libre.
STN : sur rampe
FST : arrêt rapide
NST : arrêt roue libre
DCI : arrêt par injection de courant continu.
Ce paramètre n'est pas accessible si le relais R2 est affecté à la fonction BLC : logique de frein.

rPt

Type Rampe

LIN - S - U

LIN

Définit l’allure des rampes d’accélération et de décélération.
LIN : linéaire S : en S U : en U
f (Hz)

f (Hz)

GV

GV

Le coefficient d'arrondi est fixe,
avec t2 = 0,6 x t1 avec t1 = temps
de rampe réglé.

Rampes en S
0

t

t2

0

t

t2

t1

t1

f (Hz)

f (Hz)

GV

GV

Le coefficient d'arrondi est fixe,
avec t2 = 0,5 x t1 avec t1 = temps
de rampe réglé.

Rampes en U

0
t2

t

t1

dCF

Coef.RampDEC

0
t2

t

t1

1 à 10

4

Coefficient de réduction du temps de rampe de décélération lorsque la fonction arrêt rapide est
active.

24

GP_ATV58_FR.fm Page 25 Mardi, 2. avril 2002 5:54 17

Menu Entraînement

Code

Description

tLI

Lim. Couple

_ %

Plage de réglage

Réglage usine

0 à 200% (1)

200%

La limitation de couple permet de limiter le couple maximal moteur.

ILim.interne - A

0 à 1,36 In (2)

1,36 In

FRANÇAIS

CLI

La limitation de courant permet de limiter l'échauffement du moteur.

AdC

Inj. DC Auto

non-oui

oui

Permet de désactiver le freinage par injection de courant automatique à l’arrêt.

PCC

Coef. P mot.

0.2 à 1

1

Définit le rapport entre la puissance nominale du variateur et le moteur de plus faible puissance
lorsqu’une entrée logique est affectée à la fonction commutation de moteurs.
Type
Découp.
SFt
LF-HF1-HF2
LF
Permet de sélectionner un découpage basse (LF) ou haute fréquence (HF1 ou HF2). Le type de
découpage HF1 est destiné aux applications à faible facteur de marche sans déclassement du
variateur. Si l’état thermique du variateur dépasse 95 %, la fréquence passe automatiquement à 2
ou 4 kHz selon calibre variateur. Lorsque l'état thermique du variateur redescend à 70 %, la
fréquence de découpage choisie est rétablie. Le type de découpage HF2 est destiné aux
applications à fort facteur de marche avec déclassement du variateur d'un calibre : les paramètres
d’entraînement sont automatiquement mis à l’échelle (limitation de couple, courant thermique...).
La modification de ce paramètre entraîne un retour aux réglages usine des
paramètres:
• nCr, CLI, Sfr, nrd (menu Entraînement)
• ItH, IdC, Ibr, Ctd (menu Réglages).

SFr

Fréq.Découp.-kHz

0.5-1-2-4-8-12-16 kHz

Selon calibre variateur

Permet de sélectionner la fréquence de découpage. La plage de réglage dépend du paramètre SFt.
Si SFt = LF : 0,5 à 2 ou 4 kHz selon calibre variateur
Si SFt = HF1 ou HF2 : 2 ou 4 à 16 kHz selon calibre variateur
La fréquence maximale de fonctionnement (tFr) est limitée suivant la fréquence de découpage :

nrd

SFr(kHz)

0.5

1

2

4

8

12

16

tFr (Hz)

62

125

250

500

500

500

500

Réduct. Bruit

non-oui

(3)

Cette fonction module de façon aléatoire la fréquence de découpage pour réduire le bruit moteur.

SPC

Moteur Spécial

non-oui-PSM

non

Cette fonction pour oui étend la plage de réglage du paramètre UFr du menu "Réglages" pour
permettre l’adaptation aux moteurs spéciaux cités en tête de ce chapitre.
Pour PSM : elle inhibe la détection de "Coupure aval non contrôlée" (utile notamment pour les petits
moteurs).
Non : moteur normal
Oui : moteur spécial
PSM : petit moteur
(1) 100% correspond au couple nominal d’un moteur d’une puissance égale à celle associée au variateur en
application à "fort couple".
(2) In correspond au courant nominal variateur indiqué dans le catalogue et sur l’étiquette signalétique du
variateur en application à "fort couple".
(3) oui si SFt = LF, non si SFt = HF1 ou HF2

25

GP_ATV58_FR.fm Page 26 Mardi, 2. avril 2002 5:54 17

FRANÇAIS

Menu Entraînement

Code

Description

Plage de réglage

Réglage usine

PGt

Type de GI

INC-DET

DET

Définit le type de capteur utilisé lorsqu’une carte E/S retour codeur est installée :
INC : codeur incrémental (A, A+, B, B+ sont câblés)
DET : détecteur (seul A est câblé)

PLS

Nb. Impulsion

1 à 1024

1024

Définit le nombre d’impulsions par tour du capteur.
Les paramètres grisés apparaissent si une carte extension entrées/sorties est installée.

26

GP_ATV58_FR.fm Page 27 Mardi, 2. avril 2002 5:54 17

Menu Commande

Ce menu est accessible dans la position
variateur verrouillé.

du commutateur. Les paramètres ne sont modifiables qu’à l’arrêt,

Code

Description

Plage de réglage

Réglage usine

tCC

Conf. Bornier

2W- 3W (2 fils - 3 fils)

2W

E/S

Manutention

Usage général

LI1

STOP

STOP

Couple variable
STOP

LI2

RUN sens avant

RUN sens avant

RUN sens avant

LI3

RUN sens arrière

RUN sens arrière

RUN sens arrière

LI4

2 vitesses présél.

marche pas à pas

Commut. de réf.

LI5

4 vitesses présél.

arrêt roue libre

freinage par injection

LI6

8 vitesses présél.

effacement défauts

arrêt roue libre

Les entrées/sorties grisées sont accessibles si une carte extension E/S est installée.
Commande 3 fils (Commande par impulsions : une impulsion suffit pour commander le démarrage).
Ce choix inhibe la fonction "redémarrage automatique".
Exemple de câblage :
Bornier contrôle ATV58
LI1 : stop
24 V LI1 LI2 LIx
LI2 : avant
LIx : arrière

Ce choix n’apparaît que si la commande 2 fils est configurée.
Code

Description

Plage de réglage

Réglage usine

tCt

Type 2 fils

LEL-TRN-PFo

LEL

Définit le type de commande 2 fils :
- fonction de l’état des entrées logiques (LEL : Détect. Niv.)
- fonction d’un changement d’état des entrées logiques (TRN : Détect. Trans.)
- fonction de l’état des entrées logiques avec sens avant toujours prioritaire sur le sens arrière
(PFo : Priorit. FW)
Exemple de câblage :
Bornier contrôle ATV58
LI1 : sens avant
24 V LI1 LIx
LIx : sens arrière

Les paramètres grisés apparaissent si une carte extension entrées/sorties est installée.

27

FRANÇAIS

Configuration de la commande bornier : commande 2 fils ou 3 fils.
La modification de ce paramètre nécessite une double confirmation car elle entraîne une
réaffectation des entrées logiques. Entre la commande 2 fils et la commande 3 fils, les
affectations des entrées logiques sont décalées d’une entrée. L’affectation de LI3 en 2 fils
devient l’affectation de LI4 en commande 3 fils. En commande 3 fils, les entrées LI1 et LI2 ne sont
pas réaffectables.

GP_ATV58_FR.fm Page 28 Mardi, 2. avril 2002 9:00 21

FRANÇAIS

Menu Commande

Code

Description

Plage de réglage

Réglage usine

rln

Inhib. RV

non - oui

non

• Inhibition de la marche en sens inverse du sens commandé par les entrées logiques, même si
cette inversion est demandée par une fonction sommation ou régulation.
• Inhibition du sens arrière s'il est commandé par la touche FWD/REV du terminal.

bSP

Ecrêt./Epiet

non
BNS:Epiétage
BLS:Ecrêtage

non

Gestion du fonctionnement en basse vitesse :

F : frŽquence moteur

F : frŽquence moteur

HSP

HSP
Non

LSP
0
F : frŽquence moteur

RŽfŽrence
100 %

LSP
0

Epietage
(BNS)
RŽfŽrence
100 %

HSP
EcrŽtage
(BLS)

LSP

RŽfŽrence
100 %

0
CrL
CrH

Réf.Mini AI2 - mA
Réf.Maxi AI2 - mA

0 à 20 mA
4 à 20 mA

4 mA
20 mA

Valeurs minimale et maximale du signal sur l’entrée AI2.
Ces deux paramètres permettent de définir le signal envoyé sur AI2. Entre autres, possibilité de
configurer l’entrée pour un signal 0-20 mA, 4-20 mA, 20-4mA ...

FrŽquence
HSP

LSP
0

28

CrL

CrH

2
20 AI
(mA)

GP_ATV58_FR.fm Page 29 Mardi, 2. avril 2002 5:54 17

Menu Commande

Code

Description

Plage de réglage

Réglage usine

AOL
AOH

Val.Mini AO - mA
Val.Maxi AO - mA

0 à 20 mA
0 à 20 mA

0 mA
20 mA

AO (mA)

0
AOL

Str

Mém.Consigne

AOH

20

NO-RAM-EEP

NO

Associée à la fonction +vite/-vite, cette fonction permet de mémoriser la consigne : lorsque les
ordres de marche disparaissent (mémorisation en RAM) ou lorsque le réseau d’alimentation
disparaît (mémorisation en EEPROM). Sur le démarrage suivant, la consigne vitesse est la dernière
consigne mémorisée.

LCC

Com.Terminal

Non-Oui

Non

Permet d’activer la commande du variateur par le terminal. Les touches STOP/RESET, RUN et
FWD/REV sont actives. La consigne vitesse est donnée par le paramètre LFr. Seuls les ordres arrêt
roue libre, arrêt rapide et arrêt par injection restent actifs au bornier. Si la liaison variateur/terminal
est coupée, le variateur se verrouille en défaut SLF.

PSt

Prior. STOP

Non-Oui

Oui

Cette fonction donne la priorité à la touche STOP quel que soit le canal de commande (bornier ou
bus de terrain).
Pour passer le paramètre PSt sur "non" :
1 - afficher "non"
2 - appuyer sur la touche "ENT"
3 - le variateur affiche "Voir manuel"
4 - appuyer sur ▲ puis sur ▼ puis sur "ENT"
Pour les applications avec "process" continus, il est conseillé de rendre la touche inactive (réglage
sur "non")

Add

Adresse Var.

0 à 31

0

Adresse du variateur lorsqu’il est piloté par la liaison de la prise terminal (hors terminal
d’exploitation et terminal de programmation)

tbr

BdRate RS485

9600-19200

19200

Vitesse de transmission par la liaison série RS485 en bits par seconde (prise en compte à la
prochaine mise sous tension).
Si tbr ≠ 19200, l’utilisation du terminal n’est plus possible. Pour rendre le terminal de
nouveau actif, reconfigurer tbr à 19200 par la liaison série ou effectuer un retour aux
réglages usine (voir page 5).

rPr

Reset cpts

Non-APH-RTH

Non

Remise à zéro des kWh ou du temps de fonctionnement.
Non
APH : remise à zéro des kWh
RTH : remise à zéro du temps de fonctionnement.
Une confirmation de l'ordre de remise à zéro est à faire par "ENT".
Les actions de APH et RTH sont immédiates, puis le paramètre revient automatiquement à Non.
(1) La sortie AO apparait si une carte extension entrée / sortie est installée.

29

FRANÇAIS

Valeurs minimale et maximale du signal sur les sorties AO et AO1 (1).
Ces deux paramètres permettent de définir le signal de sortie sur
AO et AO1. Ex. : 0-20 mA, 4-20 mA, 20-4mA ...

Paramètre
Maxi

GP_ATV58_FR.fm Page 30 Mardi, 2. avril 2002 5:54 17

Menu Affectation des entrées / sorties

FRANÇAIS

Ce menu est accessible dans la position
du commutateur.
Les affectations ne sont modifiables qu’à l’arrêt, variateur verrouillé.
Code

Fonction

LI2

Affect

LI2

Voir tableau récapitulatif et description des fonctions.
Les entrées et sorties proposées dans le menu dépendent des cartes E/S éventuellement installées dans le
variateur, ainsi que des choix préalablement faits dans le menu commande.
Les configurations ”usine” sont préaffectées par la macro-configuration sélectionnée.

Tableau récapitulatif des affectations des entrées logiques (hors choix 2 fils / 3 fils)
Cartes options extension E / S

2 entrées logiques LI5-LI6

Variateur sans option

NO:Non affectée
RV :Sens arrière

3 entrées logiques LI2 à LI4
(Non affectée)

X

(Marche arrière)

X

RP2:Comm. Rampe

(Commutation de rampe)

X

JOG:JOG Impuls.

(Marche pas à pas)

X

+SP: + vite

(Plus vite)

X

-SP: - Vite

(Moins vite)

X

PS2: 2Vit.Présél

(2 vitesses présélectionnées)

X

PS4: 4Vit.Présél

(4 vitesses présélectionnées)

X

PS8: 8Vit.Présél

(8 vitesses présélectionnées)

X

RFC:Commut. Réf.

(Commutation de références)

X

NST:StpRoueLibre

(Arrêt roue libre)

X

DCI:Arrêt Inj.DC

(Arrêt par injection)

X

(Arrêt rapide)

X

(Commutation de moteurs)

X

FST:Arrêt Rapide
CHP:Commut Mot.
TL2:Lim.Couple 2

(Seconde limitation de couple)

X

FLO:Forçage Loc.

(Forçage local)

X

(Effacement des défauts)

X

(Autoréglage)

X

RST:Raz Défauts
ATN:Auto Réglage
PAU:AutoManu PI

(Auto - manu PI) Si une AI = PIF

X
X

PR2:2Cons.

PI

(2 consignes PI présélectionnées) Si une AI = PIF

PR4:4Cons.

PI

(4 consignes PI présélectionnées) Si une AI = PIF

X

TLA:LimitCouple

(Limitation de couple par AI) Si une AI = ATL

X

EDD:Déf.externe

(défaut externe)

X

ATTENTION : Si une entrée logique est affectée à "Arrêt roue libre" ou "Arrêt rapide" le démarrage
ne peut s'effectuer qu'en reliant cette entrée au +24V, car ces fonctions d'arrêt sont actives à l'état
0 des entrées.

30

GP_ATV58_FR.fm Page 31 Mardi, 2. avril 2002 5:54 17

Menu Affectation des entrées / sorties

Tableau récapitulatif des affectations des entrées analogiques et codeur
Cartes options extension E / S

Entrée
codeur A+,
A-, B+, B(1)

X

X

X

Entrée
analogique
AI2

NO:Non affectée

(Non affectée)

X

FR2:Réf. Vit. 2

(Référence vitesse 2)
Si une LI = RFC

X

SAI:Réf. Sommat.

(Référence sommatrice)

X

X

PIF:Retour PI

(Retour du régulateur Pl)

X

X

PIM:Cons Man PI

(Consigne vitesse manuelle PI)
Si une AI = PIF et une LI = PAU

SFB:Retour DT
PTC:Sondes PTC
ATL:Lim.Couple
RGI:Retour GI

FRANÇAIS

Variateur sans option

Entrée
analogique
AI3

X

(Dynamo tachymétrique)

X

(Sondes PTC)

X

(Limitation de couple)

X

(Retour codeur ou détecteur)

X

(1) NB : Le menu d'affectation de l'entrée codeur A+, A-, B+, B- est intitulé "Affectation AI3".
ATTENTION : Si le relais R2 est affecté à la fonction "logique de frein", AI3 est automatiquement
affecté en réglage usine au Retour DT, si la carte est présente. La réaffectation de AI3 reste
néanmoins possible.

Tableau récapitulatif des affectations des sorties logiques
Carte option extension E / S

Sortie
logique LO

Variateur sans option

NO:Non affectée

Relais R2
(Non affectée)

X

X

RUN:Var.EnMarche

(Variateur en marche)

X

X

OCC:Cde Contact.

(Commande contacteur aval)

X

X

FTA:Seuil F. Att.

(Seuil fréquence atteint)

X

X

FLA:HSP Atteinte

(HSP atteinte)

X

X

CTA:Seuil I Att.

(Seuil courant atteint)

X

X

SRA:Réf. Vit.Att.

(Référence fréquence atteinte)

X

X

TSA:Seuil Th.Att

(Seuil thermique moteur atteint)

X

X

(Logique de frein)

X

BLC:LogiqueFrein
APL:Perte 4-20 mA

(perte référence 4 / 20 mA)

X

X

F2A:Seuil F2 Att

(2 e seuil fréquence atteint)

X

X

(Seuil thermique variateur atteint)

X

X

TAD:Alarm.th.var.

31

GP_ATV58_FR.fm Page 32 Mardi, 2. avril 2002 5:54 17

Menu Affectation des entrées / sorties

Tableau récapitulatif des affectations de la sortie analogique
Carte option extension E / S

Sortie analogique AO

Variateur sans option

Sortie analogique AO1

FRANÇAIS

NO:Non affectée

(Non affectée)

X

OCR:Courant Mot.

(Courant moteur)

X

OFR:Fréq. Mot.

(Vitesse moteur)

X

(Sortie rampe)

X

(Couple moteur)

X

STQ:Couple signé

(Couple moteur signé)

X

ORS:RampeSignée

(Sortie rampe signée)

X

ORP:Sortie Rampe
TRQ:Couple mot.

OPS:Cons PI

(Sortie consigne PI) Si une AI = PIF

X

OPF:Retour PI

(Sortie retour PI) Si une AI = PIF

X

OPE:Erreur PI

(Sortie erreur PI) Si une AI = PIF

X

OPI:Intég PI

(Sortie intégrale PI) Si une AI = PIF

X

(Puissance moteur)

X

(Etat thermique moteur)

X

(Etat thermique variateur)

X

OPR:Puis Moteur
THR:Eth Moteur
THD:Eth Var.

Après une réaffectation d’entrées/sorties, les paramètres liés à la fonction apparaissent
automatiquement dans les menus et la macro-configuration indique “CUS : personnalisée“. Certaines
réaffectations font apparaître de nouveaux paramètres de réglages qu’il ne faut pas oublier d’ajuster
dans le menu "Réglages" :
E /S

Affectations

Paramètres à régler

Commutation de rampe

AC2 dE2

JOG

Marche pas à pas

JOG JGt

PS4

4 vitesses présélectionnées

SP2-SP3

LI

PS8

8 vitesses présélectionnées

SP4-SP5-SP6-SP7

LI

DCI

Arrêt par injection

IdC

LI

TL2

Seconde limitation de couple

tL2

LI

PR4

4 consignes PI présélectionnées

PI2-PI3

AI

PIF

Retour du régulateur PI

rPG-rIG-PIC-rdG-rED-PrGPSr-PSP-PLr-PLb

LI

RP2

LI
LI

AI

SFB

Dynamo tachymétrique

dtS

R2

BLC

Logique de frein

Ibr-brt-bEn-bEt-brL-bIP

LO/R2

FTA

Seuil Fréquence atteint

Ftd

LO/R2

CTA

Seuil Courant atteint

Ctd

LO/R2

TSA

Seuil Thermique moteur atteint

ttd

LO/R2

F2A

2 e seuil Fréquence atteint

F2d

LO/R2

TAD

Seuil Thermique variateur atteint

dtd

32

GP_ATV58_FR.fm Page 33 Mardi, 2. avril 2002 5:54 17

Menu Affectation des entrées / sorties

Certaines réaffectations font apparaître de nouveaux paramètres qu’il ne faut pas oublier d’ajuster
dans le menu commande, entraînement ou défaut :
E /S

Affectations

Paramètres à régler

-SP

Moins vite

Str (menu commande)

FST

Arrêt rapide

dCF (menu entraînement)

LI

RST

Effacement des défauts

rSt (menu défauts)

AI

SFB

Dynamo tachymétrique

Sdd (menu défauts)

A+, A-,
B+, B-

SAI

Référence sommatrice

PGt, PLS (menu entraînement)

A+, A-,
B+, B-

RGI

Retour GI

PGt, PLS (menu entraînement)

FRANÇAIS

LI
LI

33

GP_ATV58_FR.fm Page 34 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables
Tableau de compatibilité des fonctions

Limitation couple par LI

Limitation couple par AI3

Régulation de vitesse avec
dynamo tachymétrique ou codeur

Vitesses présélectionnées

Marche Pas à Pas

Arrêt rapide

Arrêt roue libre

➞

Freinage par injection
de courant continu

Commutation de références

Plus vite / moins vite

Régulateur PI

Entrées sommatrices

Freinage par injection
de courant continu

FRANÇAIS

Le choix des fonctions d’application peut être limité par l’incompatibilité de certaines fonctions entre elles. Les
fonctions qui ne sont pas listées dans ce tableau ne font l’objet d’aucune incompatibilité.

Entrées sommatrices
Régulateur PI

➞

Plus vite / moins vite
Commutation de références

➞

➞

Arrêt roue libre
Arrêt rapide
Marche Pas à Pas

➞

➞

Vitesses présélectionnées

➞
➞

Régulation de vitesse avec
dynamo tachymétrique ou codeur
Limitation couple par AI3
Limitation couple par LI

Fonctions incompatibles
Fonctions compatibles
Sans objet
Fonctions prioritaires (fonctions qui ne peuvent être actives en même temps) :

➞

➞

La fonction indiquée par la flèche est prioritaire sur l’autre.

Les fonctions d’arrêt sont prioritaires sur les ordres de marches.
Les consignes de vitesse par ordre logique sont prioritaires sur les consignes analogiques.

34

GP_ATV58_FR.fm Page 35 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables
Fonctions d’application des entrées logiques
Sens de marche : avant / arrière
La marche arrière peut être supprimée dans le cas d’applications à un seul sens de rotation moteur.

Commande 3 fils
La marche (avant ou arrière) et l’arrêt sont commandés par 2 entrées logiques différentes.
LI1 est toujours affectée à la fonction arrêt. L’arrêt est obtenu à l’ouverture (état 0).
L’impulsion sur l’entrée marche est mémorisée jusqu’à ouverture de l’entrée arrêt.
Lors d'une mise sous tension ou d'une remise à zéro de défaut manuelle ou automatique, le moteur ne peut
être alimenté qu'après une remise à zéro préalable des ordres "avant", "arrière", "arrêt par injection".
Commutation de rampe : 1re rampe : ACC, DEC ; 2e rampe : AC2, DE2
2 cas d’activation sont possibles :
- par activation d’une entrée logique LIx
- par détection d’un seuil de fréquence réglable.
Si une entrée logique est affectée à la fonction, la commutation de rampe ne peut s’effectuer que par cette
entrée.
Marche Pas à Pas ”JOG” : Impulsion de marche en petite vitesse
Si le contact JOG est fermé puis le contact de sens de marche actionné, la rampe est de 0,1 s quels que soient
les réglages ACC, dEC, AC2, dE2. Si le contact de sens est fermé puis le contact JOG actionné, ce sont les
rampes réglées qui sont utilisées.
Paramètres accessibles dans le menu "Réglages" :
- vitesse JOG
- temporisation d’anti-pianotage (temps mini entre 2 commandes “JOG”).

35

FRANÇAIS

Commande 2 fils
La marche (avant ou arrière) et l’arrêt sont commandés par la même entrée logique, c’est l’état 1 (marche) ou
0 (arrêt), ou le changement d’état qui est pris en compte (voir menu type de commande 2 fils).

GP_ATV58_FR.fm Page 36 Mardi, 2. avril 2002 8:55 20

Fonctions d’applications des entrées et sorties
configurables

FRANÇAIS

Plus vite / moins vite : 2 types de fonctionnement sont disponibles.
1 Utilisation de boutons simple action : deux entrées logiques sont nécessaires en plus du ou des sens de
marche.
L’entrée affectée à la commande “plus vite” augmente la vitesse, l’entrée affectée à la commande “moins
vite” diminue la vitesse.
Cette fonction donne accès au paramètre mémorisation de consigne Str dans le menu Commande.
2 Utilisation de boutons double action : seule une entrée logique affectée à plus vite est nécessaire.
Plus vite / moins vite avec boutons double action :
Descriptif : 1 bouton double enfoncement pour chaque sens de rotation.
Chaque enfoncement ferme un contact sec.
Relaché
(moins vite)

1er enfoncement
(vitesse maintenue)

2ème enfoncement
(plus vite)

bouton sens avant

–

a

a et b

bouton sens arrière

–

c

c et d

Exemple de câblage :
LI1 : sens avant
LIx : sens arrière
LIy : plus vite

Bornier contrôle ATV58
LI1 LIx LIy
+ 24

b
a

d

c

FrŽquence
moteur
LSP
0
LSP
Avant
2 e enfoncement
1er enfoncement
0
Arrire
2 e enfoncement
1er enfoncement
0

b
a a a

b
a

a

a

a

c

d
c

Ce type de plus vite/moins vite est incompatible avec la commande 3 fils. Dans ce cas, la fonction moins vite
est automatiquement affectée à l’entrée logique d’indice supérieur (exemple : LI3 (plus vite), LI4 (moins vite)).
Dans les deux cas d’utilisation la vitesse max. est donnée par les consignes appliquées sur les entrées
analogiques. Relier par exemple AI1 au +10V.

36

GP_ATV58_FR.fm Page 37 Mardi, 2. avril 2002 9:03 21

Fonctions d’applications des entrées et sorties
configurables
Vitesses présélectionnées
2,4 ou 8 vitesses peuvent être présélectionnées, nécessitant respectivement 1, 2, ou 3 entrées logiques.
L’ordre des affectations à respecter est le suivant : PS2 (LIx), puis PS4 (LIy), puis PS8 (LIz).
4 vitesses présélectionnées

8 vitesses présélectionnées

Affecter : LIx à PS2

Affecter : LIx à PS2 puis,
LIy à PS4

Affecter : LIx à PS2
LIy à PS4, puis LIz à PS8

LIx

LIy

LIx

LIz

LIy

LIx

0

LSP+consigne

référence vitesse

0

0

LSP+consigne

référence vitesse

0

0

0

LSP+consigne

1

HSP

0

1

SP2

0

0

1

SP2

1

0

SP3

0

1

0

SP3

1

1

HSP

0

1

1

SP4

1

0

0

SP5

1

0

1

SP6

1

1

0

SP7

1

1

1

HSP

FRANÇAIS

2 vitesses présélectionnées

référence vitesse

Pour désaffecter les entrées logiques, l’ordre suivant doit être respecté : PS8 (LIz), puis PS4 (LIy), puis PS2
(LIx).
Commutation de référence
Commutation de deux références (référence en AI1 et référence en AI2) par ordre sur entrée logique.
Cette fonction affecte automatiquement AI2 à référence vitesse 2
Schéma de raccordement

LI x + 24 COM

AI 1

+10

AI 2

0-20mA
4-20mA

Contact ouvert, référence = AI2
Contact fermé, référence = AI1

Arrêt roue libre
Provoque l’arrêt du moteur par le couple résistant seulement, l'alimentation du moteur est coupée.
L’arrêt roue libre est obtenu à l’ouverture de l’entrée logique (état 0).
Arrêt par injection de courant continu
L’arrêt par injection est obtenu à la fermeture de l’entrée logique (état 1).
Arrêt rapide
Arrêt freiné avec le temps de rampe de décélération réduit par un coefficient de réduction dCF qui apparaît
dans le menu entraînement.
L’arrêt rapide est obtenu à l’ouverture de l’entrée logique (état 0).

37

GP_ATV58_FR.fm Page 38 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables

FRANÇAIS

Commutation de moteurs
Cette fonction permet d’alimenter successivement par le même variateur deux moteurs de puissances
différentes, la commutation étant assurée par une séquence appropriée en sortie du variateur. La commutation
doit être faite moteur à l’arrêt, variateur verrouillé. Les paramètres internes suivants sont automatiquement
commutés par l’ordre logique :
- courant nominal moteur
- courant d’injection

- courant de levée de frein

Cette fonction inhibe automatiquement la protection thermique du second moteur.
Paramètre accessible : Rapport des puissances moteurs PCC dans le menu entraînement.
Seconde limitation de couple
Réduction du couple maximal du moteur lorsque l’entrée logique est active.
Paramètre tL2 dans le menu "Réglages".
Remise à zéro défaut
Deux types de remise à zéro sont disponibles : partielle ou générale (paramètre rSt du menu "défauts").
Remise à zéro partielle (rSt = RSP) :
Permet l’effacement du défaut mémorisé et le réarmement du variateur si la cause du défaut a disparu.
Défauts concernés par un effacement partiel :
-

surtension réseau
surtension bus continu
perte phase moteur
dévirage de la charge

-

défaut communication
surcharge moteur
perte 4-20mA
défaut externe

-

surchauffe moteur
défaut liaison série
surchauffe variateur
survitesse

Remise à zéro générale (rSt = RSG) :
Il s'agit d'une inhibition (marche forcée) de tous les défauts sauf SCF (court-circuit moteur) pendant que
l'entrée logique affectée est fermée.
Forçage local
Permet de passer d’un mode de commande ligne (liaison série) à un mode local (commande par le bornier ou
par le terminal).
Autoréglage
Le passage à 1 de l'entrée logique affectée déclenche un autoréglage, comme le paramètre tUn du menu
"entraînement".
Attention : l'autoréglage s'effectue seulement si aucune commande n'est actionnée. Si une fonction
"arrêt roue libre" ou "arrêt rapide" est affectée à une entrée logique, il faut mettre cette entrée à 1
(active à 0).
Application : En cas de commutation de moteurs par exemple.
Auto-manu PI, consigne PI présélectionnées : Voir fonction PI (page 39)
Limitation de couple par AI
Cette fonction n'est accessible que si l'entrée analogique AI3 est affectée à la limitation de couple.
S'il n'y a pas de LI configurée sur "TL2 : seconde limitation de couple", la limitation est directement donnée par
AI3.
Si une entrée logique est configurée sur "TL2 : seconde limitation de couple" :
Lorsque l'entrée vaut 0, la limitation est donnée par tLi.
Lorsque l'entrée vaut 1, la limitation est donnée par AI3.
Défaut externe
Le passage à 1 de l'entrée logique affectée déclenche l’arrêt du moteur (selon la configuration du paramètre
LSF Stop+def du menu Entrainement), le verrouillage du variateur en défaut EPF défaut externe.

38

GP_ATV58_FR.fm Page 39 Mardi, 2. avril 2002 9:05 21

Fonctions d’applications des entrées et sorties
configurables
Fonctions d’application des entrées analogiques
L’entrée AI1 est toujours la référence vitesse.

Affectation de AI2 et AI3

Régulation de vitesse avec dynamo tachymétrique : (Affectation sur AI3 seulement avec une carte
extension E/S avec entrée analogique) : permet une correction de vitesse par retour dynamo tachymétrique.
Un pont diviseur extérieur est nécessaire pour adapter la tension de la dynamo tachymétrique. La tension
maximale doit être entre 5 et 9 V. Un réglage précis est ensuite obtenu par réglage du paramètre dtS
disponible dans le menu "Réglages".
Traitement sonde PTC : (seulement avec une carte extension E/S avec entrée analogique). Permet une
protection thermique directe du moteur en connectant sur l’entrée analogique AI3 les sondes PTC noyées
dans les bobinages du moteur.
Caractéristiques des sondes PTC :
Résistance totale du circuit sonde à 20 °C = 750 W.
Régulateur PI : Permet de réguler un processus avec une référence et un retour donné par un capteur. Avec
la fonction PI, les rampes sont toutes linéaires, même si elles sont configurées différemment.
Avec le régulateur PI, il est possible de :
- Adapter le retour par FbS.
- Faire une correction de PI inverse.
- Régler les gains proportionnel et intégral (RPG et RIG).
- Attribuer une sortie analogique pour la consigne PI, le retour PI et l'erreur PI.
- Appliquer une rampe d'établissement de l'action du PI (AC2) au démarrage si PSP > 0.
Si PSP = 0 les rampes actives sont ACC / dEC. A l'arrêt la rampe dEC est toujours utilisée.
La vitesse moteur est limitée entre LSP et HSP.
Nota : La fonction régulateur PI est active si une entrée AI est affectée à retour PI. Cette affectation sur AI
n’est possible qu’après dévalidation des fonctions incompatibles avec PI (voir page 34).

Consigne
PI
Retour
PI

+
PSP

FBS
10

Filtre Multiplicateur
passe bas

Consigne manuelle
Auto / manu

Inversion
PI

RŽgulateur
PI

PIC
X±1

RPG
RIG

Rampe
si PSP = 0
X

Rampe
si PSP > 0

AC2
dE2

ACC
dEC

RŽfŽrence
Auto
Manu

Ordre de marche
ACC
dEC
Rampe

39

FRANÇAIS

Référence vitesse sommatrice : Les consignes de fréquence issues de AI2 et AI3 peuvent être sommées
avec AI1.

GP_ATV58_FR.fm Page 40 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables

FRANÇAIS

Auto / Manu : Cette fonction n’est accessible que si la fonction PI est activée, et nécessite une carte extension
E/S avec entrée analogique
• Permet par entrée logique LI, la commutation de la marche en régulation de vitesse si LIx = 0 (consigne
manuelle sur AI3), et la régulation PI si LIx = 1 (auto).
Consignes présélectionnées :
2 ou 4 consignes présélectionnées nécessitent respectivement l'utilisation de 1 ou 2 entrées logiques :

LIx

2 consignes présélectionnées

4 consignes présélectionnées

Affecter : LIx à Pr2

Affecter : LIx à Pr2 puis, LIy à Pr4

Référence

0

Consigne analogique

1

Max process (= 10 V)

LIy

LIx

0

0

Référence
Consigne analogique

0

1

PI2 (réglable)

1

0

PI3 (réglable)

1

1

Max process (= 10 V)

Limitation de couple : (Seulement avec une carte extension E/S avec entrée analogique AI3)
Le signal appliqué sur AI3 agit de façon linéaire sur la limitation de couple interne (paramètre TLI du menu
"entraînement") :
- Si AI3 = 0V : limitation = TLI x 0 = 0
- Si AI3 = 10 V : limitation = TLI.
Applications : Correction de couple, de traction…

Fonctions d’applications de l'entrée codeur :
(seulement avec une carte extension E/S avec entrée codeur)
Régulation de vitesse : Permet une correction de vitesse par codeur incrémental ou détecteur. (Voir
documentation fournie avec la carte).
Référence vitesse sommatrice : La consigne issue de l'entrée codeur est sommée avec AI1. (voir
documentation fournie avec la carte)
Applications :
- Synchronisation en vitesse de plusieurs variateurs. Le paramètre PLS du menu "entraînement" permet
d'ajuster le rapport de la vitesse d'un moteur par rapport à un autre.
- Consigne par générateur d'impulsions.

40

GP_ATV58_FR.fm Page 41 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables
Fonctions d’application des sorties logiques

Variateur en marche (RUN) : affectable à R2 ou LO
La sortie logique est à l’état 1 si le moteur est alimenté par le variateur (présence de courant), ou si un ordre
de marche est présent avec une référence nulle.
Seuil de fréquence atteint (FTA) : affectable à R2 ou LO
La sortie logique est à l’état 1 si la fréquence moteur est supérieure ou égale au seuil de fréquence réglé par
Ftd dans le menu "Réglages".
2 ème seuil de fréquence atteint (F2A) : affectable à R2 ou LO
La sortie logique est à l’état 1 si la fréquence moteur est supérieure ou égale au seuil de fréquence réglé par
F2d dans le menu "Réglages".
Consigne atteinte (SRA): affectable à R2 ou LO
La sortie logique est à l’état 1 si la fréquence moteur est égale à la valeur de la consigne.
Grande vitesse atteinte (FLA): affectable à R2 ou LO
La sortie logique est à l’état 1 si la fréquence moteur est égale à HSP.
Seuil de courant atteint (CTA): affectable à R2 ou LO
La sortie logique est à l’état 1 si le courant moteur est supérieur ou égal au seuil de courant réglé par Ctd dans
le menu "Réglages".
Etat thermique moteur atteint (TSA) : affectable à R2 ou LO
La sortie logique est à l’état 1 si l’état thermique moteur est supérieur ou égal au seuil de l’état thermique réglé
par ttd dans le menu "Réglages".
Etat thermique variateur atteint (TAD) : affectable à R2 ou LO
La sortie logique est à l’état 1 si l’état thermique variateur est supérieur ou égal au seuil de l’état thermique
réglé par dtd dans le menu "Réglages".
Commande de frein (BLC) : affectable uniquement au relais R2
Permet la gestion d’un frein électro-magnétique par le variateur, pour les applications de levage vertical. Pour
les freins des mouvements horizontaux, utiliser la fonction “variateur en marche“.
Vitesse moteur

T = temporisation non réglable
Réglages accessibles dans le menu
"Réglages" :
- fréquence de levée de frein (brL)
- temporisation de levée de frein
(brt)
- temporisation de fermeture de frein
(bEt)
- courant de levée de frein (Ibn)
- fréquence de fermeture de frein
(bEn)

Consigne

Etat frein
1
0
Relais R2
1
0
Montée ou descente
1
0
T

brt

bEt

41

FRANÇAIS

Relais R2, sortie statique LO (avec carte extension E/S)
Commande contacteur aval (OCC): affectable à R2 ou LO
Permet la commande d’un contacteur de boucle (situé entre le variateur et le moteur) par le variateur. La
demande de fermeture du contacteur se fait sur apparition d’un ordre de marche. L’ouverture du contacteur
est demandée lorsqu’il n’y a plus de courant dans le moteur.
Si une fonction freinage par injection de courant continu est configurée, ne pas la faire agir trop
longtemps à l’arrêt, car le contacteur ne s’ouvrira qu’à la fin du freinage.

GP_ATV58_FR.fm Page 42 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables
Recommandation de réglages de la commande de frein, pour une application levage vertical :
1 Fréquence de levée du frein (brL) :
Ajuster la fréquence de levée du frein à la valeur : glissement nominal multiplié par la fréquence nominale
en Hz (g x FS).

FRANÇAIS

Ns – Nr )
Mode de calcul : glissement = (-----------------------Ns

- Ns = vitesse de synchronisme en tr/mn.
(pour un réseau 50 Hz : Ns = 3000 tr/mn pour un moteur 1 paire de pôles, 1500 tr/mn pour un moteur 2
paires de pôles, 1000 tr/mn pour un moteur 3 paires de pôles et 750 tr/mn pour un moteur 4 paires de pôles,
pour un réseau 60 Hz : Ns = 3600 tr/mn pour un moteur 1 paire de pôles, 1800 tr/mn pour un moteur 2 paires
de pôles, 1200 tr/mn pour un moteur 3 paires de pôles et 900 tr/mn pour un moteur 4 paires de pôles).
- Nr = vitesse nominale au couple nominal en tr/mn, prendre la vitesse plaquée sur le moteur.
Fréquence de levée = g x Fs.
- g = glissement calculé précédemment.
- Fs = fréquence nominale moteur (indiquée sur la plaque moteur).
Exemple : pour moteur 2 paires de pôles, plaqué 1430 tr/mn, réseau 50 Hz.
g = (1500 - 1430) / 1500 = 0.0466.
Fréquence de levée de frein = 0.0466 x 50 = 2.4 Hz
2 Courant de levée du frein (Ibr) :
Ajuster le courant de levée de frein au courant nominal plaqué sur le moteur.
Remarque sur les points 1 et 2 : les valeurs indiquées (courant de levée et fréquence de levée)
correspondent aux valeurs théoriques. Si lors des essais, le couple est insuffisant avec les valeurs
théoriques : conserver le courant de levée de frein au courant nominal moteur et baisser la fréquence de
levée de frein (jusqu’à 2/3 du glissement nominal). Si le résultat n’est toujours pas satisfaisant, revenir aux
valeurs théoriques puis augmenter le courant de levée de frein (la valeur maximale est imposée par le
variateur) et augmenter la fréquence de levée de frein de manière progressive.
3 Temps d’accélération :
Pour les applications levage, nous vous conseillons de régler des rampes d’accélération supérieures à 0.5
secondes. S’assurer que le variateur ne passe pas en limitation de courant.
Même recommandation pour la décélération.
Rappel : pour un mouvement de levage, une résistance de freinage devra être utilisée et il faudra s’assurer
que les réglages et configurations choisis ne peuvent entraîner une chute ou un non contrôle de la charge
soulevée.
4 Temporisation de levée du frein (brt) :
Ajuster en fonction du type de frein, c’est le temps nécessaire au frein mécanique pour s’ouvrir.
5 Fréquence de fermeture du frein (bEn) :
Ajuster à 2 fois le glissement nominal (dans notre exemple 2 x 2.4 = 4.8 Hz). Puis ajuster en fonction du
résultat.
6 Temporisation de fermeture du frein (bEt) :
Ajuster en fonction du type de frein, c’est le temps nécessaire au frein mécanique pour se fermer.
Perte 4-20 mA (APL) affectable à R2 ou LO
La sortie logique est à 1 si le signal sur l'entrée 4-20 mA est inférieur à 2 mA.

42

GP_ATV58_FR.fm Page 43 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables
Fonctions d’application de la sortie analogique AO et AO1
Les sorties analogiques AO et AO1 sont des sorties en courant, de AOL (mA) à AOH (mA),
• AOL et AOH étant configurables de 0 à 20 mA.

FRANÇAIS

Exemples AOL - AOH : 0 - 20 mA
4 - 20 mA
20 - 4 mA
Courant moteur (code OCR) : fournit l’image du courant efficace moteur.
• AOH correspond à 2 fois le courant nominal du variateur.
• AOL correspond à courant nul.
Fréquence moteur (Code OFR) : fournit la fréquence moteur estimée par le variateur.
• AOH correspond à la fréquence maximale (paramètre tFr).
• AOL correspond à fréquence nulle.
Sortie rampe (Code ORP) : fournit l’image de la fréquence en sortie de la rampe.
• AOH correspond à la fréquence maximale (paramètre tFr).
• AOL correspond à fréquence nulle.
Couple moteur (Code TRQ) : fournit l’image du couple moteur en valeur absolue.
• AOH correspond à deux fois le couple nominal moteur.
• AOL correspond à couple nul.
Couple moteur signé (code STQ) : fournit l'image du couple moteur et son sens :
• AOL correspond à un couple de freinage = 2 fois le couple nominal.
• AOH correspond à un couple moteur = 2 fois le couple nominal.
• AOH + AOL correspond à couple nul.
2
Rampe signée (code ORS) : fournit l’image de la fréquence en sortie de la rampe et son sens.
• AOL correspond à la fréquence maximale (paramètre tFr) dans le sens arrière.
• AOH correspond à la fréquence maximale (paramètre tFr) dans le sens avant.
• AOH + AOL correspond à une fréquence nulle
2
Consigne PI (code OPS) : fournit l’image de la consigne du régulateur PI.
• AOL correspond à la consigne mini.
• AOH correspond à la consigne maxi.
Retour PI (code OPF) : fournit l’image du retour du régulateur PI.
• AOL correspond au retour mini.
• AOH correspond au retour maxi.
Erreur PI (code OPE) : fournit l’image de l’erreur du régulateur PI en % de la plage du capteur (retour maxi
- retour mini).
• AOL correspond à l'erreur maximale < 0.
• AOH correspond à l'erreur maximale > 0.
• AOH + AOL correspond à une erreur nulle (OPE = 0).
2

43

GP_ATV58_FR.fm Page 44 Mardi, 2. avril 2002 5:54 17

Fonctions d’applications des entrées et sorties
configurables

FRANÇAIS

Intégrale PI (code OPI) : fournit l’image de l’intégrale de l’erreur du régulateur PI.
• AOL correspond à une intégrale nulle.
• AOH correspond à une intégrale saturée.
Puissance Moteur (code OPR) : fournit l’image de la puissance absorbée par le moteur.
• AOL correspond à 0 % de la puissance nominale du moteur.
• AOH correspond à 200 % de la puissance nominale du moteur.
Etat thermique Moteur (code THR) : fournit l’image de l’état thermique du moteur, calculé.
• AOL correspond à 0 %.
• AOH correspond à 200 %.
Etat thermique Variateur (code THD) : fournit l’image de l’état thermique du variateur.
• AOL correspond à 0 %.
• AOH correspond à 200 %.

44

GP_ATV58_FR.fm Page 45 Mardi, 2. avril 2002 5:54 17

Menu Défauts

Ce menu est accessible dans la position
du commutateur.
Les modifications ne peuvent être effectuées qu’à l’arrêt, variateur verrouillé.
Code

Description

Réglage usine

Atr

Redém. Auto

Non

rSt

Type Reset

RSP

Cette fonction est accessible si la remise à zéro des défauts est affectée à une entrée logique. 2
choix possibles : reset partiel (RSP), reset total (RSG)
Défauts concernés par un reset partiel (rSt = RSP)
- surtension réseau
- surtension bus continu
- surcharge moteur
- perte 4-20mA
- surchauffe moteur
- dévirage de la charge
- perte phase moteur
- surchauffe variateur
- défaut liaison série
- défaut externe
- défaut communication
- survitesse
Défauts concernés par un reset général (rSt = RSG) : tous les défauts. Le reset général est en fait
une inhibition de tous les défauts (marche forcée).
Pour configurer rSt = RSG :
1 afficher RSG
2 appuyer sur la touche "ENT"
3 le variateur affiche "Voir manuel"
4 appuyer sur ▲ puis sur ▼ puis sur "ENT"

OPL

Perte Ph Mot

Oui

Permet la validation du défaut perte de phase moteur. (Suppression du défaut en cas d’utilisation
d’un interrupteur entre le variateur et le moteur). Choix Oui / Non

IPL

Perte Ph rés

Oui

Permet la validation du défaut perte phase réseau. (Suppression du défaut en cas d’alimentation
directe par un bus continu et en cas d'alimentation d'un variateur triphasé ATV58• U72M2, U90M2
ou D12M2 en monophasé). Choix Oui / Non
Ce défaut n’existe pas sur les ATV58•U09M2, U18M2, U29M2 et U41M2.

45

FRANÇAIS

Cette fonction permet un redémarrage automatique du variateur si le défaut a disparu (choix Oui/
Non). Un redémarrage automatique est possible après les défauts suivants :
- surtension réseau
- surtension bus DC
- défaut externe
- perte phase moteur
- défaut liaison série
- défaut communicaton
- perte référence 4-20 mA
- surcharge moteur (condition : état thermique moteur inférieur à 100 %)
- surchauffe variateur (condition : état thermique variateur inférieur à 70 %)
- surchauffe moteur (condion : résistance des sondes inférieure à 1 500 Ohms)
Lorsque la fonction est activée, suite à l’apparition de un ou plusieurs de ces défauts, le relais
R1reste fermé : le variateur effectue une tentative de démarrage toutes les 30 s. Un maximum de
6 tentatives sont effectuées tant que le variateur ne peut démarrer (présence du défaut) . Si toutes
les 6 ont échoué, le variateur reste verrouillé définitivement avec ouverture du relais de défaut,
jusqu’à réarmement par mise hors tension.
Cette fonction nécessite que la séquence associée soit maintenue, et il faut s’assurer que
le redémarrage intempestif ne présente aucun danger humain ou matériel.

GP_ATV58_FR.fm Page 46 Mardi, 2. avril 2002 5:54 17

FRANÇAIS

Menu Défauts

Code

Description

Réglage usine

tHt

Typ Prot Therm

ACL

Définit le type de protection thermique moteur indirecte effectuée par le variateur. Si des sondes
PTC sont connectées au variateur, cette fonction n’est pas disponible. Pas de protection thermique:
N0 : Aucune
Moteur autoventilé (ACL) : le variateur tient compte d’un déclassement en fonction de la fréquence
de rotation. Moteur motoventilé (FCL) : le variateur ne tient pas compte d’un déclassement en
fonction de la fréquence de rotation.

LFL

Perte 4-20mA

Non

Permet la validation du défaut perte référence 4-20 mA.
Ce défaut n’est configurable que si les paramètres référence mini/maxi AI2 (CrL et CrH)) sont
supérieurs à 3 mA ou si CrL>CrH.
- Non : pas de défaut
- Oui : défaut immédiat
- STT : arrêt selon le paramètre STT, sans défaut, rédémarrage au retour du signal
- LSF : arrêt selon le paramètre STT, puis défaut à la fin de l'arrêt
- LFF : forçage à la vitesse de repli réglée par le paramètre LFF
- RLS : maintien de la vitesse atteinte lors de l'apparition de la perte 4-20 mA, sans défaut,
redémarrage au retour du signal.

LFF

Vit.Def.4-20

0

Vitesse de repli en cas de perte référence 4-20 mA.
Réglage de 0 à HSP.

FLr

Reprise Volée

Non

Permet la validation d’un redémarrage sans à-coup après les évènements suivants :
- coupure réseau ou simple mise hors tension.
- remise à zéro des défauts ou redémarrage automatique.
- arrêt roue libre ou arrêt par injection avec entrée logique.
- coupure non contrôlée en aval du variateur.
Choix Oui / Non
Si le relais R2 est affecté à la fonction logique de frein le paramètre FLr reste verrouillé sur non.

StP

Arrêt Coup Rés

Non

Arrêt contrôlé sur une perte de phase réseau. Cette fonction n'est opérationnelle que si le paramètre
IPL est positionné sur Non. Si IPL est sur Oui, laisser StP en position Non. Choix possibles :
Non : verrouillage sur coupure réseau.
MMS : Maint. Bus DC : le contrôle du variateur est maintenu sous tension par l'énergie cinétique
restituée par les inerties, jusqu'à apparition du défaut USF (sous tension)
FRP : Sur rampe : décélération suivant la rampe programmée dEC ou dE2 jusqu'à l'arrêt ou
l'apparition du défaut USF (sous tension). Ce fonctionnement n'existe pas sur ATV58•U09M2,
U18M2, U29M2 et U41M2

Sdd

Cont Anti-Dév

Oui

Cette fonction est accessible si un retour par dynamo tachymétrique ou par générateur d’impulsions
est programmé. Validée, elle permet de verrouiller le variateur, si un non suivi de vitesse est détecté
(différence entre la fréquence statorique et la vitesse mesurée).
Choix Oui / Non.

EPL

46

Défaut externe
Oui
Configure l’arrêt sur défaut externe:
- Oui: verrouillage en défaut immédiat
- LSF Stop+def: arrêt selon le paramètre Stt (Menu Entraînement) puis verrouillage en défaut

GP_ATV58_FR.fm Page 47 Mardi, 2. avril 2002 5:54 17

Menu Fichier

Ce menu est accessible dans la position
du commutateur.
Les opérations ne sont possibles qu’à l’arrêt, variateur verrouillé.
Le terminal permet de stocker 4 fichiers contenant des configurations variateur.
Description

Etat
Etat
Etat
Etat

Fich.
Fich.
Fich.
Fich.

Réglage usine

1
2
3
4

FRANÇAIS

Code

F1S
F2S
F3S
F4S

FRE
FRE
FRE
FRE

Permet de visualiser l’état du fichier correspondant.
Etats possibles :
FRE : fichier libre (Etat à la livraison du terminal)
EnG : Une configuration a déjà été mémorisée dans ce fichier

FOt

Opération

NO

Permet la sélection de l’opération à réaliser sur les fichiers.
Opérations possibles :
NO : pas d’opération demandée (valeur par défaut à chaque nouvelle connexion du terminal sur le
variateur)
STR : opération de mémorisation de la configuration du variateur dans un fichier du terminal
REC : transfert du contenu d’un fichier vers le variateur
Ini : retour du variateur aux réglages usine
Le retour aux réglages usine annulera tous vos réglages et votre configuration.

Mode opératoire
Sélectionner STR, REC ou InI et appuyer sur "ENT".
1 Si Opération = STR :
Affichage des numéros de fichiers. Sélectionner un fichier par ▲ ou ▼ et valider par "ENT".
2 Si Opération = REC :
Affichage des numéros de fichiers. Sélectionner un fichier par ▲ ou ▼ et valider par "ENT".
- l'afficheur indique :

CHG

CABLAGE OK?

ENT

Vérifier que le câblage est compatible avec la configuration du fichier.
Annuler par "ESC" ou valider par "ENT"
- l'afficheur demande alors une seconde confirmation à valider par "ENT" ou annuler par "ESC".
3 Si Opération = InI :
Validation par "ENT"
- l'afficheur indique :

CHG

CABLAGE OK?

ENT

Vérifier que le câblage est compatible avec la configuration usine.
Annuler par "ESC" ou valider par "ENT".
- l'afficheur demande alors une seconde confirmation à valider par "ENT" ou annuler par "ESC".
A la fin de chaque opération l'afficheur revient au paramètre "Opération" en "NO"

47

GP_ATV58_FR.fm Page 48 Mardi, 2. avril 2002 5:54 17

Menu Fichier

Menu Fichiers (suite)
Code

Description

COd

Code Conf.

FRANÇAIS

Code confidentiel
La configuration du variateur peut être protégée par un Code confidentiel (COd)
ATTENTION : CE PARAMETRE EST A UTILISER AVEC PRECAUTIONS. IL PEUT INTERDIR L’ACCES A
L’ENSEMBLE DES PARAMETRES. TOUTE MODIFICATION DE LA VALEUR DE CE PARAMETRE DOIT
ETRE PRECAUTIONNEUSEMENT NOTEE ET ENREGISTREE.
La valeur du code est donnée par quatre chiffres, dont le dernier permet de fixer le niveau d’accessibilité que
l’on souhaite laisser libre.

8888
ce chiffre donne le niveau
d’accès autorisé, sans code correct.
L’accessibilité aux menus en fonction du commutateur de verrouillage d’accès situé sur la face arrière du
terminal est toujours opérationnelle, dans les limites autorisées par le code.
La valeur de Code 0000 (réglage usine) ne limite pas l’accès.
Le tableau ci-dessous définit l’accessibilité aux menus en fonction du dernier chiffre du code.
Dernier chiffre du code
Menus

Accès verrouillé

Visualisation

Modification

Réglages

0 sauf 0000 et 9

1

2

Niveau 2 :
Réglages, Macro-config, Entraînement,
Commande, Affectation I/O, Défauts,
Fichier (sauf code),
Communication (si carte présente)

0 sauf 0000 et 9

3

4

Application (si carte présente)

0 sauf 0000 et 9

5

6

Niveau 2 et Application (si carte présente)

0 sauf 0000 et 9

7

8

Pour l'accessibilité au menu APPLICATION, consulter la documentation de la carte application.
La modification du code s’effectue par les touches ▲ et ▼ .
Si un code incorrect est entré, il est refusé avec affichage du message :

COd

Code incorrect

Après appui sur la touche ENT ou ESC du clavier, la valeur affichée du paramètre Code devient 0000 : le
niveau d’accessibilité reste inchangé. L’opération doit être reconduite.
Pour accéder aux menus protégés par le code d’accès, il faut préalablement entrer ce code qui reste toujours
accessible dans le menu Fichier.

48

GP_ATV58_FR.fm Page 49 Mardi, 2. avril 2002 5:54 17

Menus Communication et Application/Assistance en
exploitation/Maintenance
Menu Communication
Ce menu n’est affiché que si une carte communication est installée. Il est accessible dans
la position
du commutateur. La configuration n’est possible qu’à l’arrêt, variateur verrouillé.
Pour l’utilisation avec une carte option communication, se reporter au document fourni avec cette carte.

Menu Application
Ce menu n’est affiché que si une carte "application client" est installée. Il est accessible dans la position
du commutateur. La configuration n’est possible qu’à l’arrêt, variateur verrouillé.
Se reporter au document fourni avec la carte.

Assistance en exploitation
Voir les voyants de signalisation au paragraphe "Présentation".

Maintenance
Avant toute intervention dans le variateur, couper l’alimentation et attendre la décharge des
condensateurs (environ 3 minutes) : extinction de la Del verte située en face avant du
variateur.
ATTENTION : la tension continue aux bornes + et - ou PA et PB peut atteindre 900 V suivant la tension
réseau.
En cas d’anomalie à la mise en service ou en exploitation, s’assurer tout d’abord que les recommandations
relatives à l’environnement, au montage et aux raccordements ont été respectées. Consulter le guide
d’exploitation de l’Altivar.

Entretien
L’Altivar 58 ne nécessite pas d’entretien préventif. Il est néanmoins conseillé à intervalles réguliers de :
- vérifier l’état et le serrage des connexions,
- s’assurer que la température au voisinage de l’appareil reste à un niveau acceptable et que la ventilation
reste efficace (durée de vie moyenne des ventilateurs : 3 à 5 ans selon les conditions d’exploitation),
- dépoussiérer le variateur si nécessaire.

Assistance à la maintenance
Le premier défaut détecté est mémorisé et affiché sur l’écran du terminal : le variateur se verrouille, la Del
rouge s’allume, et le relais de sécurité R1 déclenche.

Effacement du défaut
Couper l’alimentation du variateur en cas de défaut non réarmable.
Rechercher la cause du défaut pour l’éliminer.
Rétablir l’alimentation : ceci a pour effet d’effacer le défaut si celui-ci a disparu.
Dans certains cas, il peut y avoir redémarrage automatique après disparition du défaut, si cette fonction a été
programmée.

49

FRANÇAIS

Pour l’utilisation de la communication par la liaison RS485 du produit de base, se reporter au document fourni
avec le kit de connexion RS485.

GP_ATV58_FR.fm Page 50 Mardi, 2. avril 2002 5:54 17

FRANÇAIS

Maintenance

Défaut affiché

Cause probable

PHF
COUPURE PH. RES

• variateur mal alimenté ou fusion de
• vérifier le raccordement puissance et
fusibles
les fusibles
• coupure fugitive d’une phase
• réarmer
• utilisation sur réseau monophasé
• configurer le défaut "Perte Ph rés"
d'un ATV58•U72M2, U90M2 ou D12M2
(code IPL) en "Non", dans le menu
(triphasé)
DEFAUTS

USF
SOUS TENSION

• réseau trop faible
• baisse de tension passagère
• résistance de charge détériorée

• vérifier la tension réseau

OSF
SURTENSION

• réseau trop fort

• vérifier la tension réseau

OHF
SURCHAUFFE VAR

• température radiateur trop élevée
(tHd>118 %)

• contrôler la charge du moteur, la
ventilation du variateur et attendre le
refroidissement pour réarmer

OLF
SURCHARGE MOT

• déclenchement thermique par
surcharge prolongée (tHr>118 %)

• vérifier le réglage de la protection
thermique, contrôler la charge du
moteur
• le réarmement est possible après 7
minutes environ

ObF
FREINAGE EXC

• freinage trop brutal ou charge
entraînante
• surtension réseau en fonctionnement

• augmenter le temps de décélération,
adjoindre une résistance de freinage si
nécessaire
• Vérifier les éventuelles surtensions
réseau

OPF
COUPURE PH. MOT

• coupure d’une phase en sortie variateur • vérifier les raccordements du moteur et
la fermeture du contacteur aval (s’il
existe)
• si utilisation d’un départ moteur en
macro configuration, vérifier que la
configuration du relaisR2 est en
contacteur aval.

LFF
PERTE 4-20mA

• perte de la consigne 4-20mA sur
l’entrée AI2

• vérifier le raccordement des circuits de
consigne

OCF
SURINTENSITE

• rampe trop courte
• inertie ou charge trop forte
• blocage mécanique

• vérifier les réglages
• vérifier le dimensionnement moteur/
variateur/charge
• vérifier l'état de la mécanique

SCF
COURTCIRCUIT MOT

• court-circuit ou mise à la terre en sortie • vérifier les câbles de liaison variateur
variateur
débranché, et l’isolement du moteur.
Vérifier le pont à transistor du variateur.

CrF
RELAIS CHARGE

• défaut de commande du relais de
charge
• résistance de charge détériorée

• vérifier la connectique dans le variateur
et la résistance de charge

SLF
COUPURE RS485

• mauvais raccordement sur la prise
terminal du variateur

• vérifier le raccordement sur la prise
terminal du variateur

50

Procédure, remède

• changer la résistance de charge

GP_ATV58_FR.fm Page 51 Mardi, 2. avril 2002 5:54 17

Maintenance

Cause probable

Procédure, remède

OtF
SURCHAUFFE MOT

• température moteur trop élevée
(sondes CTP)

• vérifier la ventilation du moteur, la
température ambiante, contrôler la
charge du moteur.
• vérifier le type de sondes utilisées.

tSF
DEF. SONDE PTC

• mauvaise connexion des sondes au
variateur

• vérifier le reccordement des sondes au
variateur
• vérifier les sondes

EEF
DEFAUT EEPROM

• erreur de mémorisation en EEPROM

• couper l’alimentation du variateur et
réarmer.

InF
DEFAUT INTERNE

• défaut interne
• défaut de connectique

• vérifier la connectique dans le variateur.

EPF
DEFAUT EXTERNE

• défaut déclenché par un organe externe • vérifier l’organe qui a causé le défaut et
réarmer

SPF
COUPURE RET. VIT

• absence de retour vitesse

• vérifier le raccordement et
l'accouplement mécanique du capteur
de vitesse

AnF
DEVIRAGE

• non suivi de rampe
• vitesse inverse à la consigne

• vérifier le réglage et le câblage du
retour vitesse.
• vérifier l’adéquation des réglages par
rapport à la charge.
• vérifier le dimensionnement
motovariateur et la nécessité éventuelle
d'une résistance de freinage.

SOF
SURVITESSE

• instabilité
• charge entraînante trop forte

• vérifier les réglages et paramètres
• ajouter une résistance de freinage
vérifier le dimensionnement moteur/
variateur/charge

CnF
DEF. RESEAU COM

• défaut de communication sur le bus de • vérifier la connexion du réseau au
terrain
variateur
• vérifier le time-out.

ILF
DEF. COM. INTERN

• défaut de communication entre la carte • vérifier la connexion de la carte option
option et la carte contrôle
sur la carte contrôle.

CFF

Erreur probablement lors d’un
changement de carte :
• changement du calibre de carte
puissance,
• changement du type de carte option
ou installation d'une carte option s'il n'y
en avait pas auparavant et si la macroconfig est CUS,
• carte option ôtée,
• configuration mémorisée incohérente.
L’appui sur ENT fait apparaître le
message :
RgLUsine? ENT/ESC

• vérifier la configuration matérielle du
variateur (carte puissance, autres)
• couper l’alimentation du variateur puis
réarmer.
• mémoriser la configuration dans un
fichier de la console.
• appuyer sur ENT pour retourner aux
réglages usine

• la configuration envoyée au variateur
par liaison série est incohérente

• vérifier la configuration précédemment
envoyée
• envoyer une configuration cohérente.

ERR. CALIBRE-ENT
ERR. OPTION-ENT

OPT. RETIREE-ENT
CKS. EEPROM-ENT

CFI
DEF. CONFIG

51

FRANÇAIS

Défaut affiché

GP_ATV58_FR.fm Page 52 Mardi, 2. avril 2002 5:54 17

Maintenance

FRANÇAIS

Cas de non fonctionnement sans affichage de défaut
Affichage

Cause probable

Procédure, remède

Aucun code,
voyants éteints.

• Pas d'alimentation.

• Vérifier l'alimentation du variateur.

Aucun code,
voyant vert allumé,
voyant rouge éteint
ou allumé

• Terminal HS.

• Changer le terminal.

rdY
voyant vert allumé

• Variateur en mode ligne, avec carte
• Paramètrer LI4 en forçage local puis
communication ou kit RS 485.
valider ce forçage par LI4.
• Une entrée LI est affectée à "Arrêt roue • Relier l'entrée au 24 V pour dévalider
libre" ou "Arrêt rapide", et cette entrée
l'arrêt.
n'est pas sous tension.
Ces arrêts sont commandés par
coupure de l'entrée.

52

GP_ATV58_FR.fm Page 53 Mardi, 2. avril 2002 5:54 17

Mémorisation configuration et réglages

Variateur référence ATV58 ............ Affichage rEF : .....................................
N° identification client éventuel : ..................................................................
Carte option : non y oui y : référence .........................................................

FRANÇAIS

Code d’accès : non y oui y : .......................................................................
Configuration dans le fichier n° ............................ du terminal d’exploitation
Macro configuration : ....................................................................................
Pour configuration CUS : personnalisée , affectation des entrées / sorties :
ALTIVAR
LI 1 :
LI 2 :
LI 3 :
LI 4 :
AI 1 :
AI 2 :

Entrées logiques

Entrées analogiques
Entrée codeur
Relais
Sortie logique
Sortie analogique

Carte option
LI 5 :
LI 6 :

AI 3 :
AI3 :

R2 :
LO :
AO :

AO1 :

Paramètres de réglage :
Code
ACC
dEC
LSP
HSP
FLG
StA
ItH
IdC
tdC
SdC
AC2
dE2
JPF
JF2
JF3
tLS
USC
UFr
SLP
PFL
SP2
SP3
SP4
SP5
SP6

Réglage usine
3s
3s
0 Hz
50 / 60 Hz
20 %
20 %
Selon modèle
Selon modèle
0,5 s
0,5 ItH
5s
5s
0 Hz
0 Hz
0 Hz
0
1
100 %
100 %
20 %
10 Hz
15 Hz
20 Hz
25 Hz
30 Hz

Réglage Client (1)
s
s
Hz
Hz
%
%
A
A
s
A
s
s
Hz
Hz
Hz
s
%
%
%
Hz
Hz
Hz
Hz
Hz

Code
SP7
JOG
JGt
brL
Ibr
brt
bEn
bEt
FFt
bIP
rPG
rIG
FbS
PIC
dtS
Ctd
ttd
tL2
PSP
PI2
PI3
dtd
Ftd
F2d

Réglage usine
35 Hz
10 Hz
0,5 s
0 Hz
0A
0s
0 Hz
0s
50/60 Hz
non
1
1/s
1
non
1
1,36 In
100 %
200%
0s
30 %
60 %
105 %
50/60 Hz
50/60 Hz

Réglage Client (1)
Hz
Hz
s
Hz
A
s
Hz
s
Hz

/s

A
%
%
s
%
%
%
Hz
Hz

(1) indiquer ”néant” lorsque le paramètre est absent.
53

GP_ATV58_FR.fm Page 54 Mardi, 2. avril 2002 5:54 17

Mémorisation configuration et réglages

FRANÇAIS

Paramètres menu entraînement :
Code
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt

Réglage usine
selon modèle
50 / 60 Hz
selon modèle
selon modèle
selon modèle
non
60 / 72 Hz
non
non
non
0 Hz
STN

Réglage Client (1)
V
Hz
A
rpm

Hz

Code
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Réglage usine
LIN
4
200%
1,36 In
oui
1
LF
selon modèle
oui
non
DET
1024

Réglage Client (1)
Hz

Code
AOH
Str
LCC
PSt
Add
tbr
rPr

Réglage usine
20 mA
No
non
oui
0
19200
Non

Réglage Client (1)
mA

Code
LFF
FLr
StP
Sdd
EPL

Réglage usine
0 Hz
non
non
oui
oui

Réglage Client (1)
Hz

%
A

kHz

(1) indiquer ”néant” lorsque le paramètre est absent.

Paramètres menu commande :
Code
tCC
tCt
rIn
bSP
CrL
CrH
AOL

Réglage usine
2W
LEL
non
non
4 mA
20 mA
0 mA

Réglage Client (1)

mA
mA
mA

(1) indiquer ”néant” lorsque le paramètre est absent.

Paramètres menu défauts :
Code
Atr
rSt
OPL
IPL
tHt
LFL

Réglage usine
non
RSP
oui
oui
ACL
non

Réglage Client (1)

(1) indiquer ”néant” lorsque le paramètre est absent.

54

GP_ATV58_FR.fm Page 55 Mardi, 2. avril 2002 5:54 17

Synthèse des menus

Menu LANGUE

Menu 2 - REGLAGES (suite)
Code
LnG
LnG
LnG
LnG
LnG

Menu MACRO-CONFIG
Libellé
Hdg : Manutention
GEn : Usage Gén.
VT : C. Variable

Code
CFG
CFG
CF

Menu 1 - SURVEILLANCE
Libellé
Etat var.
Réf. Fréq
Fréq. Sortie
Vitesse mot.
Courant mot.
Vit. machine
Puiss. Sortie
U réseau
Therm. mot.
Therm. var.
Dernier déf.
Réf. Fréq.
Consommation
Temps marche

Code
--FrH
rFr
SPd
LCr
USP
OPr
ULn
tHr
tHd
LFt
LFr
APH
rtH

Menu 2 - REGLAGES
Libellé
Réf. Fréq. - Hz
Accélération - s
Décélération - s
Accél. 2
- s
Décél. 2
- s
Petite vit. - Hz
Grande vit. - Hz
Gain
- %
Stabilité
- %

Code
LFr
ACC
dEC
AC2
dE2
LSP
HSP
FLG
StA

Libellé
I Thermique - A
I Inj. DC
- A
Temps Inj.DC- s
I arrêt DC - A
Fréq Occult.- Hz
Fréq Occult2- Hz
Fréq Occult3- Hz
Coef. Machine
Temps LSP
- s
Compens. RI - %
Comp.Gliss. - %
Vit.Présél.2- Hz
Vit.Présél.3- Hz
Vit.Présél.4- Hz
Vit.Présél.5- Hz
Vit.Présél.6- Hz
Vit.Présél.7- Hz
Détection I - A
Fréq. Jog
- Hz
Tempo JOG
- s
Lim. Couple 2- %
Profil U/f
- %
Gain Prop.PI
Gain Int.PI - /s
Coef. Ret. PI
Inversion PI
F.LevéeFrein- Hz
I levéeFrein- A
T.levéeFrein- s
F.Ferm.Frein- Hz
T.Ferm.Frein- s
SeuilDéc NST- Hz
Imp.Lev.Frein
Coef. Ret. DT
Détect.Fréq - Hz
Dét. Freq.2 - Hz
Détect.Therm- %
Filtre PI
- s
Cons. PI2
- %
Cons. PI3
- %
Dét. Th. var.

Code
ItH
IdC
tdC
SdC
JPF
JF2
JF3
USC
tLS
UFr
SLP
SP2
SP3
SP4
SP5
SP6
SP7
Ctd
JOG
JGt
tL2
PFL
rPG
rIG
FbS
PIC
brL
Ibr
brt
bEn
bEt
FFt
bIP
dtS
Ftd
F2d
ttd
PSP
PI2
PI3
dtd

FRANÇAIS

Libellé
English
Français
Deutsch
Español
Italiano

55

GP_ATV58_FR.fm Page 56 Mardi, 2. avril 2002 5:54 17

Synthèse des menus

FRANÇAIS

Menu 3 - ENTRAINEMENT
Libellé
U Nom. Mot. - V
Fréq.Nom.Mot- Hz
Nom. Mot - A
Vit.Nom.Mot -rpm
Cos Phi Mot
Auto réglage
Fréq. Max
- Hz
Eco Energie
Adapt. I lim
AdaptRampDec
F.Com.Rampe2- Hz
Type arrêt
Type Rampe
Coef.RampDEC
Lim. Couple - %
ILim.interne- A
Inj. DC Auto
Coef. P mot.
Type Découp.
Fréq.Découp.-kHz
Réduct. Bruit
Moteur Spécial
Type de GI
Nb. Impulsion

Code
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Menu 4 - COMMANDE
Libellé
Conf. Bornier
Type 2 fils
Inhibit. RV
Ecrêt/Epiet
Ref.Mini AI2Ref.Maxi AI2Val.Mini AO Val.Maxi AO Mém.Consigne
Com.Terminal
Prior. STOP
Adresse Var.
BdRate RS485
Reset cpts

56

mA
mA
mA
mA

Code
tCC
tCt
rIn
bSP
CrL
CrH
AOL
AOH
Str
LCC
PSt
Add
tbr
rPr

Menu 5 - AFFECTATION I/O
Libellé
Affect LI2
Affect LI3
Affect LI4
Affect LI5
Affect LI6
NO:Non affectée
RV :Sens arrière
RP2:Comm. Rampe
JOG:JOG Impuls.
+SP: + vite
-SP: - vite
PS2: 2Vit.Présél
PS4: 4Vit.Présél
PS8: 8Vit.Présél
RFC:Commut. Réf.
NST:StpRoueLibre
DCI:Arrêt Inj.DC
FST:Arrêt Rapide
CHP:Commut Mot.
TL2:Lim.Couple 2
FLO:Forçage Loc.
RST:Raz Défauts
ATN:Auto réglage
PAU:AutoManu PI
PR2:2Cons.
PI
PR4:4Cons.
PI
TLA:LimitCouple
EDD:Déf.externe
Affect R2
Affect LO
NO:Non affectée
RUN: Var.EnMarche
OCC:Cde Contact.
FTA:Seuil F. Att.
FLA:HSP Atteinte
CTA:Seuil I Att.
SRA:Réf. Vit.Att.
TSA:Seuil Th.Att
BLC:LogiqueFrein
APL:Perte 4-20mA
F2A:Seuil F2 Att
TAD:Alarm.th.var.

Code
L12
L13
L14
L15
L16

r2
LO

GP_ATV58_FR.fm Page 57 Mardi, 2. avril 2002 5:54 17

Synthèse des menus

Menu 5 - AFFECTATION I/O (suite)
Code
AI2
AI3

AI3

Menu 6 - DEFAUTS
Libellé
Redém. Auto
Type Reset
Perte Ph Mot
Perte Ph rés
Typ Prot Therm
Perte 4-20mA
Vit.Def.4-20
Reprise Volée
Arrêt Coup Rés
Cont Anti-Dév
Défaut externe

Code
Atr
rSt
OPL
IPL
tHt
LFL
LFF
FLr
StP
Sdd
EPL

FRANÇAIS

Libellé
Affect AI2
Affect AI3
NO:Non affectée
FR2:Réf. Vit. 2
SAI:Réf. Sommat.
PIF:Retour PI
PIM:Cons Man PI
SFB:Retour DT
PTC:Sondes PTC
ATL:Lim. Couple
Affect AI3(codeur)
NO:Non affectée
SAI:Réf. Sommat.
RGI:Retour GI
Affect AO
NO:Non affectée
OCR:Courant Mot.
OFR:Fréq. Mot.
ORP:Sortie Rampe
TRQ:Couple mot.
STQ:Couple signé
ORS:Rampe signé
OPS:Cons. PI
OPF:Retour PI
OPE:Erreur PI
OPI:Integ PI
OPR:Puis Moteur
tHR:Eth Moteur
tHD:Eth Var.

Menu 7 - FICHIER
AO

Libellé
Etat Fich.
Etat Fich.
Etat Fich.
Etat Fich.
Opération
Code Conf.

1
2
3
4

Code
FI5
F25
F35
F45
FOt
COd

Menu 8 - COMMUNICATION
Consulter la documentation fournie
avec la carte communication.

Menu 8 - APPLICATION
Consulter la documentation fournie
avec la carte application.

57

GP_ATV58_FR.fm Page 58 Mardi, 2. avril 2002 5:54 17

FRANÇAIS

Index

Fonction

Menus

Accélération

REGLAGES - ENTRAINEMENT

16-24

Adaptation automatique de rampe

ENTRAINEMENT

24

Adresse liaison série

COMMANDE

29

Arrêt contrôlé

AFFECTATION I/O - DEFAUTS

30-46

Auto réglage

ENTRAINEMENT - AFFECTATION I/O

23-30-38

Boucle de vitesse avec codeur

ENTRAINEMENT - AFFECTATION I/O

26-31-32-40

Boucle de vitesse avec dynamo

REGLAGES - AFFECTATION I/O

21-31-32-39

Code confidentiel

FICHIER

48

Commande 2fils/3fils

COMMANDE

27-35

Commutation de moteurs

ENTRAINEMENT - AFFECTATION I/O

25-30-38

Commutation de rampes

REGLAGES - ENTRAINEMENT - AFFECT. I/O

16-24-30-32-35

Commutation de références

AFFECTATION I/O

30-37

Contacteur aval

AFFECTATION I/O

31-41

Couple standard / fort couple

IDENTIFICATION (rEF)

13

Décélération

REGLAGES - ENTRAINEMENT

16-24

Economie d’énergie

ENTRAINEMENT

23

Entrée analogique AI2

COMMANDE

28

Entrées configurables

AFFECTATION I/O

30-31-32

Forçage mode local

COMMANDE - AFFECTATION I/O

30-38

Freinage par injection

REGLAGES - ENTRAINEMENT

17-19-25

Fréquence de découpage

ENTRAINEMENT

25

Fréquences occultées

REGLAGES

17

Limitations de couple

REGLAGES - ENTRAINEMENT - AFFECT. I/O

19-21-25-30-32-38

Limitation de courant

ENTRAINEMENT

24-25

Limitation temps de vitesse basse

REGLAGES

17

Logique de frein

REGLAGES - AFFECTATION I/O

20-31-32-41-42

Mémorisation de consigne

COMMANDE

29

Pas à pas (JOG)

REGLAGES - AFFECTATION I/O

19-20-30-32-35

Plus vite / moins vite

AFFECTATION I/O

30-33-36

Priorité stop

COMMANDE

29

Protection thermique moteur

REGLAGES - AFFECTATION I/O - DEFAUTS

16-22-31-32-46

Rattrap. auto. (reprise à la volée)

DEFAUTS

46

Redémarrage automatique

DEFAUTS

45

Réglage usine / Mémorisation

FICHIER

47

Régulateur PI

REGLAGES - AFFECTATION I/O

21-31-32-39

Remise à zéro des défauts

AFFECTATION I/O - DEFAUTS

30-33-38-45

Sondes PTC

AFFECTATION I/O

31-39

Sorties configurables

COMMANDE - AFFECTATION I/O

29-31-32-41-42-43

Vitesses présélectionnées

REGLAGES - AFFECTATION I/O

18-20-30-32-37

58

Pages

GP_ATV58_FR.fm Page 59 Mardi, 2. avril 2002 5:54 17

FRANÇAIS
59

GP_ATV58_Page2-EN.fm Page 60 Mardi, 2. avril 2002 6:19 18

Warning

ENGLISH

This document relates to use of the Altivar 58 exclusively
with :
- the VW3A58101 display module
- a VW3A58201 or VW3A58202 I/O extension card if applicable.
Some modes, menus and types of operation can be modified if the speed controller is equipped with other options. Please refer to the relevant documentation for each
of these options.
Since it was first commercialised, the Altivar 58 has had
additional functions included. This document can be used
with earlier devices, but parameters described here may
be missing from those speed controllers.
For installation, connection, setup and maintenance instructions, please refer to the Altivar 58 and the I/O extension card User's Manuals as required.
Informationen zu Installation, Anschluß, Inbetrieb-nahme
und Wartung finden Sie im technischen Heft des Altivar
58-Basisgerätes und gegebenen-falls im Bedienungshandbuch der Optionskarte E/A Erweiterung.

60

Contents

Introduction ____________________________________________________________________ 62
Practical Advice / Minimum Setup ___________________________________________________ 65
Unlocking Menus Before Programming _______________________________________________ 66
Access to Menus ________________________________________________________________ 67
Access to Menus - Programming Principle ____________________________________________ 68
Macro-Configurations _____________________________________________________________ 69
Drive Identification _______________________________________________________________ 71
Display Menu ___________________________________________________________________ 72
Adjust Menu ____________________________________________________________________ 74
Drive Menu _____________________________________________________________________ 81
Control Menu ___________________________________________________________________ 85
I/O Menu ______________________________________________________________________ 88
Configurable I/O Application Functions _______________________________________________ 92
Fault Menu ____________________________________________________________________ 103

ENGLISH

Files Menu ____________________________________________________________________ 105
Communication and Application Menus / Assistance During Operation / Maintenance _________ 107
Maintenance ___________________________________________________________________ 108
Saving the Configuration and Settings _______________________________________________ 111
Summary of Menus _____________________________________________________________ 113
Index ________________________________________________________________________ 116

61

GP_ATV58_EN.fm Page 62 Mardi, 2. avril 2002 6:09 18

Introduction

The VW3A58101 display module is supplied with ATV58••••M2 and ATV58••••N4 speed controllers.
ATV58••••••Z speed controllers are supplied without a display module. This can be ordered separately.
Installing the display module on the speed controller :

ENGLISH

The protective cover should be removed before installing the display module on an ATV58••••••Z speed
controller.

POWE
R
FAUL z
T

POWE
R
FAUL z
T

ESC
FWD
REV

ENT
RUN

STOP
RESET

The display module must be connected and disconnected with the power off. If the display module is
disconnected when control of the speed controller via the display module is enabled, the speed controller locks
in fault mode SLF.

Installing the display module remotely :
Use the kit, reference VW3A58103, comprising 1 cable with connectors, the parts required for mounting on an
enclosure door and the installation guide.

Signaling on the front panel of the Altivar
Other LEDs, indicating status with communication option cards.

POWER z

Green LED POWER

on : Altivar powered up

FAULT

Red LED FAULT

• on : Altivar faulty
• flashing : Altivar locked once the "STOP" key has
been pressed on the display module or after a
change to the configuration. The motor can then
only be supplied with power after resetting prior to
the "forward", "reverse", and "injection stop"
commands.

62

GP_ATV58_EN.fm Page 63 Mardi, 2. avril 2002 6:09 18

Introduction
☞ Before switching the Altivar on and before using the display module :
Unlock and open the cover of the Altivar to access the 50/
60 Hz selector switch 1 on the control card. If an option
card is present, the selector switch can be accessed
through it.
Position the selector switch on 50 or 60 Hz, whichever
corresponds to your motor.
Preset operating point :

1
or
50 Hz

60 Hz

ENGLISH

50 Hz position (factory setting) :
- 230 V 50 Hz for ATV58••••M2
- 400 V 50 Hz for ATV58••••N4
60 Hz position :
- 230 V 60 Hz for ATV58••••M2
- 460 V 60 Hz for ATV58••••N4

The display module is used for :
-

Displaying the drive identification, electrical values, operating or fault parameters
Altering the Altivar settings and configuration
Operating in local control mode via the keypad
Saving and restoring the configuration in a non-volatile memory in the display module

☞ Return to factory settings:
- Switch off the drive
- Unlock and open the Altivar cover in order to access the 50/60 Hz switch 1 on the control card. If an
option card is present, the selector switch can be accessed through it.
- Change the position of the 50/60 Hz switch 1 on the control card
- Switch on the drive
- Switch off the drive
- Reset the 50/60 Hz switch 1 on the control card to its initial position (nominal motor frequency)
Switch on the drive, and it reverts to its factory configuration.

63

GP_ATV58_EN.fm Page 64 Mardi, 2. avril 2002 6:09 18

Introduction

Front panel

LOC

PROG

ESC
ENT
ENGLISH

FWD
REV

RUN

Use of keys and meaning of displays
 Ú
Flashing :
indicates the selected direction of rotation
Steady :
indicates the direction of motor rotation
LOC
Indicates control via the display module
PROG Appears in setup and programming mode
Flashing :
indicates that a value has been modified but not saved
4-character display :
displays numeric values and codes
One line of 16 characters :
displays messages in plain text

STOP
RESET

Scroll through menus or parameters and set a value
ESC

Return to the previous menu or abort the current adjustment and return to the original value

ENT

Select a menu, confirm and save a selection or setting

If control via the display module is selected :
FWD
REV

RUN
STOP
RESET

Reverse the direction of rotation
Command to start the motor running
Command to stop the motor or reset the fault. The key's "STOP" function can be inhibited
via the program ("CONTROL" menu).

Rear view

Connector :
- for direct connection of the display module to the speed
controller
- for remote operation, the display module can be connected via
a cable provided in the VW3A58103 kit..
Access locking switch :

64

- position

: Settings and configuration not accessible

- position

: Settings accessible

- position

: Settings and configuration accessible

GP_ATV58_EN.fm Page 65 Mardi, 2. avril 2002 6:09 18

Practical Advice / Minimum Setup

Practical advice :
Before starting your programming, first fill in the configuration and settings record tables (at the end of this
document).
Programming the Altivar 58 is made easier by the use of internal sequence selections and interlocks. In order
to maximize this ease of use, we recommend that you access the menus in the following order. Not all steps
are essential in every case.

↓

ENGLISH

↓

LANGUAGE
MACRO-CONFIG
IDENTIFICATION
CONTROL (for 3-wire control only)
I/O
CONTROL
DRIVE
FAULT
COMMUNICATION or APPLICATION if a card is used
ADJUST
CAUTION : The user must ensure that the programmed functions are compatible with the wiring
diagram used. This check is particularly important on the ready-assembled ATV58E if the factory
configuration is modified; the diagram may also require modification.

Minimum setup :
This procedure can be used :
- in simple applications where the speed controller factory settings are suitable
- in installation phases where it is necessary to rotate the motor experimentally before undertaking a full
installation

Procedure :
1 Follow the recommendations in the User's Manual supplied with the speed controller, most importantly
setting the 50/60 Hz selector switch to the nominal frequency of the motor.
2 Ensure that the factory macro-configuration is suitable, otherwise change it in the «MACRO-CONFIG»
menu.
3 For speed controllers with power ratings greater than 7.5 kW at 200/240 V and 15 kW at 380/500 V in
"standard torque" applications, configure the power in the «IDENTIFICATION» menu.
4 To ensure the required level of safety, check that the wiring diagram is compatible with the macroconfiguration, otherwise modify the diagram.
5 Check in the «DRIVE» menu that the factory parameters are compatible with those given on the motor
rating plate, otherwise modify them.
6 In the «DRIVE» menu, perform an auto tune.
7 If necessary, adjust the parameters in the «ADJUST» menu (ramps, thermal current, etc).

65

GP_ATV58_EN.fm Page 66 Mardi, 2. avril 2002 6:09 18

Unlocking Menus Before Programming

Level of access / Operating mode
The position of the selector switch offers three levels of access to the menus according to the operating phase
of your machine. Access to the menus can also be locked using an access code (see the Files menu).
Position
-

LANGUAGE menu : To select the dialog language
MACRO-CONFIG menu : To display the macro-configuration
IDENTIFICATION menu : To display the speed controller voltage and power
DISPLAY menu : To display the electrical values, the operating phase or a fault

Position

ENGLISH

Display : use during operating phases

Display and settings : use during setup phases

- To perform all the operations which are possible in level 0
- ADJUST menu : To set all the parameters which can be accessed while the motor is rotating
Position

Total unlock : use during programming phases

- To perform all the operations which are possible in levels 0 and 1
- MACRO-CONFIG menu : To change the macro-configuration.
- IDENTIFICATION menu : To change the power in "standard torque" or "high torque" mode, for the ratings
governed by this parameter.
- DRIVE menu : To adjust the performance of the motor-speed controller unit
- CONTROL menu : To configure control of the speed controller, for control via the terminals, the display
module or the integrated RS485 serial link
- I/O menu : To change the I/O assignment
- FAULT menu : To configure the motor and speed controller protection and behavior in the event of a fault
- FILES menu : To save and restore the speed controller configurations stored in the display module, return
to the factory settings or protect your configuration
- COMMUNICATION menu, if a communication card is installed : To adjust the parameters of a
communication protocol
- APPLICATION menu, if a «client application» card is installed. Please refer to the documentation specific
to this card.

66

GP_ATV58_EN.fm Page 67 Mardi, 2. avril 2002 6:09 18

Access to Menus

The number of menus which can be accessed depends on the position of the access locking switch.
Each menu is made up of a number of parameters.
Subsequent
power-ups

Initial
power-up

LnG

LANGUAGE

ESC

CFG

MACRO-CONFIG

ENGLISH

rEF

Identification

0.37 kW 200/240 V

SUP

1-DISPLAY

SEt

2-ADJUST

drC

3-DRIVE

CtL

4-CONTROL

5-I/O

The PROG
indication is
displayed on
the display module

I-O
FLt

6-FAULT

FLS

7-FILES

can only be accessed if the
"client application" card is
installed

APP

8-APPLICATION

SL

8-COMMUNICATION

can only be accessed if
the protocol card is
installed

CAUTION : If an access code has already been programmed, it may be impossible to modify some menus,
these may not even be visible. In this case, see the section entitled “FILES menu” explaining how to enter the
access code.
67

GP_ATV58_EN.fm Page 68 Mardi, 2. avril 2002 6:09 18

Access to Menus - Programming Principle

Language :
This menu can be accessed whatever position the access switch is in, and can be modified in stop or run mode.
Example :
ENT

LnG

LnG

LANGUAGE

English

LnG

ENGLISH

Italiano

Return to the previously
saved selection

Save the new
selection

ESC

ENT

ESC

LnG

Italiano

LnG

English

Possible selections : English (factory setting), French, German, Spanish, Italian.

Programming principle :
The principle is always the same, with 1 or 2 levels :
• 1 level : see the “language” example above.
• 2 levels : see the “acceleration ramp” example below.
ENT

SEt

ENT

ACC

Accélération

2.REGLAGES

3.0

s

Accélération

Increase

ESC

s

(or

Decrease)

3.1

Accélération

ESC

Save
the new value

Return to
the previous value

ENT

ESC

3.1

Accélération

68

s

s

3.0

Accélération

s

GP_ATV58_EN.fm Page 69 Mardi, 2. avril 2002 6:09 18

Macro-Configurations

This parameter can always be displayed but can only be modified in programming mode (access switch in
position
) and in stop mode with the speed controller locked.
It can be used to automatically configure an application-specific function. Three application-specific functions
are available.
- Handling (Hdg)
- Variable torque for pump and fan applications (VT)
- General use (GEn)
A macro-configuration automatically assigns the I/O and parameters, activating the functions required for the
application. The parameters related to the programmed functions are available.

Factory setting : Handling
Speed controller :

ENGLISH

I/O assignment according to the macro-configuration

Hdg : Handling

GEn : Gen Use.

VT : Var. Torque

Logic input LI1

forward

forward

forward

Logic input LI2

reverse

reverse

reverse

Logic input LI3

2 preset speeds

jog operation

reference switching

Logic input LI4

4 preset speeds

freewheel stop (1)

injection braking

Analog input AI1

summing ref.

summing ref.

speed ref. 1

Analog input AI2

summing ref.

summing ref.

speed ref. 2

Relay R1

controller fault

controller fault

controller fault

Relay R2

downstr. contactor ctrl

mot. therm. state
reached

freq. setpoint reached

Analog output AO1

motor frequency

motor frequency

motor frequency

Extension cards :
I/O assignment according to the macro-configuration

Hdg : Handling

GEn : Gen Use.

Logic input LI5

8 preset speeds

clear fault

VT : Var. Torque
freewheel stop (1)

Logic input LI6

clear fault

limit torque

ramp switching

Analog input AI3
or
Inputs A, A+, B, B+

summing ref.

summing ref.

NO

speed feedback

speed feedback

speed feedback

Logic output LO

current thresh reached

downstr. contactor ctrl

high speed reached

Analog output AO

Motor current

Motor current

Motor current

(1) In order to start, the logic input must be linked to the + 24 V (function active at 0).
CAUTION : Ensure that the programmed macro-configuration is compatible with the wiring
diagram used. This check is particularly important on the ready-assembled ATV58E if the factory
configuration is modified; the diagram may also require modification.

69

GP_ATV58_EN.fm Page 70 Mardi, 2. avril 2002 6:09 18

Macro-Configurations

Modification of the macro-configuration requires double confirmation as it results in automatic
assignment of functions and a return to factory settings.
The following screen is displayed :

CHG

WIRING OK?

ENT

ENT to confirm the modification
ESC to return to the previous configuration

Customizing the configuration :
The configuration of the speed controller can be customized by changing the I/O assignment in the I/O menu
which can be accessed in programming mode (access switch in position
).
This customization modifies the displayed macro-configuration value :
is displayed.

CFG

ENGLISH

CUS:Customize

70

GP_ATV58_EN.fm Page 71 Mardi, 2. avril 2002 6:09 18

Drive Identification

Drive identification
This parameter can always be displayed. It indicates the speed controller power and voltage as indicated on
the identification label.

rEF

0.37 kW 200/240 V

The power is displayed in kW if the 50/60 Hz selector switch on the speed controller
is set to 50 Hz, and in HP if it is set to 60 Hz.

For speed controllers rated above 7.5 kW at 200/240 V and 15 kW at 380/500 V :
The rating is different according to whether it is a standard torque or high torque application. The speed
controllers are supplied factory set at "high torque". "Standard torque" configuration is obtained in the following
way :

22 kW

rEF

rEF flashes
22 kW

380/500 V

ENGLISH

ENT

rEF flashes

rEF
380/500 V

+30 kW

rEF
380/500 V

ou ESC

ESC

ENT

+30 kW

rEF
380/500 V

+30 kW

rEF
380/500 V

ESC

In "standard torque" applications the + sign precedes the power in kW.
To return to "high torque" configuration, perform the same procedure.
"Standard torque" or "high torque" configuration preconfigures the "factory setting" of certain parameters :
• Drive menu : UnS, nCr, nSP, COS, tUn
• Adjust menu : ItH, IdC.
Changing from one to the other of these torque configurations therefore results in all these
parameters returning to factory settings.

71

GP_ATV58_EN.fm Page 72 Mardi, 2. avril 2002 6:09 18

Display Menu

Display menu (selection of parameter displayed during operation)
The following parameters can be accessed whatever position the access switch is in, in stop or run mode.
Code

ENGLISH

--rdY
rUn
ACC
dEC
CLI
dCb
nSt
Obr
FrH

Function

Unit

Var. State

–

State of the speed controller : indicates a fault or the motor operating phase :
rdY = speed controller ready,
rUn = motor in steady state or run command present and zero reference,
ACC = accelerating,
dEC = decelerating,
CLI = current limit,
dCb = injection braking,
nSt = freewheel stop control,
Obr = braking by adapting the deceleration ramp (see the “drive” menu).

Freq. Ref.

Hz

Frequency reference

rFr

Output Freq.

Hz

Output frequency applied to the motor

SPd

Motor Speed

rpm

Motor speed estimated by the speed controller

LCr

MotorCurrent

A

Motor current

USP

Mach. speed

–

Machine speed estimated by the speed controller. This is proportional to rFr, according to a
coefficient USC which can be regulated in the adjust menu. Displays a value corresponding to the
application (metres / second, for example). Caution, if USP becomes greater than 9999 the display
isdivided by 1000.

OPr

Output power

%

Power supplied by the motor, estimated by the controller.
100 % corresponds to nominal power.

ULn

MainsVoltage

V

Line voltage

tHr

MotorThermal

%

Thermal state : 100% corresponds to the nominal thermal state of the motor. Above 118%, the
speed controller triggers an OLF fault (motor overload)

tHd

DriveThermal

%

Thermal state of the speed controller : 100% corresponds to the nominal thermal state of the speed
controller. Above 118%, the speed controller triggers an OHF fault (speed controller overheating).
It can be reset below 70 %.

LFt

Last Fault
Displays the last fault which occurred.

72

–

GP_ATV58_EN.fm Page 73 Mardi, 2. avril 2002 6:09 18

Display Menu

Code

Function

Unit

LFr

Freq. Ref.

Hz

This adjustment parameter appears instead of the FrH parameter when the speed controller control
via the display module is activated : LCC parameter in the control menu.

APH

Consumption

kWh or MWh

Energy consumed.

rtH

Run time

hrs

Continuous operating time (motor powered up) in hours.

ENGLISH
73

GP_ATV58_EN.fm Page 74 Mardi, 2. avril 2002 6:09 18

Adjust Menu

This menu can be accessed when the switch is in positions
and
. Adjustment parameters
can be modified in stop mode OR during operation. Ensure that any changes made during
operation are not dangerous; changes should preferably be made in stop mode.
The list of adjustment parameters is made up of a fixed and a changeable part which varies according to :
- the selected macro-configuration
- the presence of an I/O extension card
- the reassignment of I/O
The following parameters can always be accessed in all the macro-configurations.
Code

Description

LFr

Freq. Ref.

- Hz

Adjustment range

Factory setting

LSP to HSP

–

Appears when control via the display module is activated : LCC parameter in the control menu

ENGLISH

ACC
dEC

Acceleration - s
Deceleration - s

0.05 to 999.9
0.05 to 999.9

3s
3s

Acceleration and deceleration ramp times. Ranges 0 to motor nominal frequency (FrS)

AC2
dE2

Accelerate 2 - s
Decelerate 2 - s

0.05 to 999.9
0.05 to 999.9

5s
5s

2nd acceleration ramp
2nd deceleration ramp
These parameters can be accessed if the ramp switching threshold (parameter Frt) is other than 0
Hz or if a logic input is assigned to ramp switching.

LSP

Low Speed

- Hz

0 to HSP

0 Hz

- Hz

LSP to tFr

50 / 60 Hz
acc. to the switch

Low speed

HSP

High Speed

High speed : ensure that this setting is correct for the motor and the application.

FLG

Gain

- %

0 to 100

20

Frequency loop gain : used to adapt the rapidity of the machine speed transients according to the
dynamics.
For high resistive torque, high inertia or fast cycle machines, increase the gain gradually.

StA

Stability

- %

0 to 100

20

Used to adapt the return to steady state after a speed transient according to the dynamics of the
machine.Gradually increase the stability to avoid any overspeed.

ItH

ThermCurrent - A

0.25 to 1.36 In (1)

According to controller rating

Current used for motor thermal protection. Set ItH to the nominal current on the motor rating plate.

tdC

DC Inj. Time - s

0 to 30 s Cont

0.5 s

DC injection braking time.
If this is increased to more than 30 s, "Cont" is displayed, permanent DC injection.
The injection becomes equal to SdC after 30 seconds.
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for high torque applications.

74

GP_ATV58_EN.fm Page 75 Mardi, 2. avril 2002 6:09 18

Adjust Menu

Code

SdC

Description

Adjustment range

Factory setting

DC stop.curr - A

0.1 to 1.36 In (1)

Acc. to contr. rating

Injection braking current applied after 30 seconds if tdC = Cont.
Check that motor will withstand this curr. without overheating

JPF

Jump Freq.

- Hz

0 to HSP

0 Hz

Skip frequency : prohibits prolonged operation over a frequency range of +/-2.5 Hz around JPF. This
function can be used to prevent a critical speed which causes resonance.

JF2

Jump Freq.2 - Hz

0 to HSP

0 Hz

Second skip frequency: Same function as JPF, for a second frequency value

Jump Freq.3 - Hz

0 to HSP

0 Hz

Third skip frequency: Same function as JPF, for a third frequency value

USC

Machine Coef.

0.01 to 100

1

Coefficient applied to parameter rFr (output frequency applied to the motor), the machine speed is
displayed via parameter USP
USP = rFr x USC

tLS

LSP Time

- s

0 to 999.9

0 (no time limit)

Operating time at low speed. After operating at LSP for a given time, the motor is stopped
automatically. The motor restarts if the frequency reference is greater than LSP and if a run
command is still present.
Caution : value 0 corresponds to an unlimited time
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for high torque applications.

75

ENGLISH

JF3

GP_ATV58_EN.fm Page 76 Mardi, 2. avril 2002 6:09 18

Adjust Menu

The following parameters can be accessed in the ‘handling’ macro-configuration
Code

Description

UFr

IR Compens.

- %

Adjustment range

Factory setting

0 to 150% or 0 to 800%

100%

Used to adjust the default value or the value measured during auto-tuning. The adjustment range is
extended to 800% if the SPC parameter (special motor) is set to “Yes” in the drive menu.

SLP

Slip Comp.

- %

0 to 150%

100%

Used to adjust the slip compensation value fixed by the motor nominal speed.

SP2

Preset Sp.2 - Hz

LSP to HSP

10 Hz

LSP to HSP

15 Hz

LSP to HSP

20 Hz

LSP to HSP

25 Hz

LSP to HSP

30 Hz

LSP to HSP

35 Hz

0 to 1.36 In (1)

1.36 In (1)

2nd preset speed

SP3

Preset Sp.3 - Hz

ENGLISH

3rd preset speed

SP4

Preset Sp.4 - Hz
4th preset speed

SP5

Preset Sp.5 - Hz
5th preset speed

SP6

Preset Sp.6 - Hz
6th preset speed

SP7

Preset Sp.7 - Hz
7th preset speed

Ctd

Curr.Lev.Att - A

Current threshold above which the logic output or the relay changes to 1
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.

76

GP_ATV58_EN.fm Page 77 Mardi, 2. avril 2002 6:09 18

Adjust Menu

The following parameters can be accessed in the ‘general use’ macro-configuration
Code

UFr

Description

IR Compens.

- %

Adjustment range

Factory setting

0 to 150% or 0 to 800%

100%

Used to adjust the default value or the measured value during auto-tuning.
The adjustment range is extended to 800% if the SPC parameter (special motor) is set to “Yes” in
the drive menu.

SLP

Slip Comp.

- %

0 to 150%

100%

Used to adjust the slip compensation value fixed by the motor nominal speed.

JOG

Jog Freq.

- Hz

0 to 10 Hz

10 Hz

0 to 2 s

0.5 s

Jog frequency

JGt

JOG Delay

- s

ENGLISH

Anti-repeat delay between two consecutive jog operations

tL2

Trq.Limit 2

- %

0 to 200% (1)

200%

Second torque limit level activated by a logic input
The following parameters can be accessed in the ‘variable torque’ macro-configuration
Code

IdC

Description

DC Inj.curr

- A

Adjustment range

Factory setting

0.10 to 1.36 In (2)

Acc. to controller rating

DC injection braking current.
After 30 seconds the injection current is peak limited to 0.5 Ith if it is set at a higher value

PFL

U/f Profile

- %

0 to 100%

20%

Used to adjust the quadratic power supply ratio when the energy saving function has been inhibited
(1) 100% corresponds to the nominal torque of a motor with a power rating equal to that associated with the
speed controller in high torque applications.
(2) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
Parameters in gray boxes appear if an I/O extension card is installed

77

GP_ATV58_EN.fm Page 78 Mardi, 2. avril 2002 6:09 18

Adjust Menu

The following parameters can be accessed once the I/O have been reassigned on the basic product.
Code

Description

AC2

Accel. 2

-

s

Adjustment range

Factory setting

0.05 to 999.9

5s

0.05 to 999.9

5s

2nd acceleration ramp

dE2

Decel. 2

-

s

2nd deceleration ramp
These parameters can be accessed if the ramp switching time (parameter Frt) is other than 0 Hz or
if a logic input is assigned to ramp switching.

IdC

DC Inj.curr -

A

0.10 to 1.36 In (1)

Acc. to controller rating

ENGLISH

DC injection braking current
This parameter can be accessed if a logic input is assigned to DC injection stopping.
After 30 seconds the injection current is peak limited to 0.5 Ith if it is set at a higher value

SP2

Preset Sp.2 - Hz

LSP to HSP

10 Hz

LSP to HSP

15 Hz

LSP to HSP

20 Hz

LSP to HSP

25 Hz

LSP to HSP

30 Hz

LSP to HSP

35 Hz

0 to 10 Hz

10 Hz

0 to 2 s

0.5 s

2nd preset speed

SP3

Preset Sp.3 - Hz
3rd preset speed

SP4

Preset Sp.4 - Hz
4th preset speed

SP5

Preset Sp.5 - Hz
5th preset speed

SP6

Preset Sp.6 - Hz
6th preset speed

SP7

Preset Sp.7 - Hz
7th preset speed

JOG

Jog Freq.

- Hz

Jog frequency

JGt

JOG Delay

-

s

Anti-BrkLgSeqFlwd delay between two consecutive jog operations

brL

BrReleaseLev- Hz

0 to 10 Hz

0 Hz

0 to 1.36In(1)

0A

0 to 5 s

0s

0 to LSP

0 Hz

0 to 5 s

0s

Brake release frequency

Ibr

BrRelease I -

A

Brake release current

brt

BrReleasTime-

s

Brake release time

bEn

BrEngage Lev- Hz
Brake engage frequency

bEt

BrEngageTime- Hz
Brake engage time

(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.

78

GP_ATV58_EN.fm Page 79 Mardi, 2. avril 2002 6:09 18

Adjust Menu

Code

Description

Adjustment range

Factory setting

FFt

TripThreshNST-Hz

0 to HSP

0 Hz

Freewheel stop trip threshold: When a stop on ramp or fast stop is requested, the type of stop
selected is activated until the speed falls below this threshold. Below this threshold, freewheel stop
is activated. This parameter can only be accessed if the R2 relay is not assigned to the “BLC: Brake
Logic” function, and if an “on ramp” or “fast” type stop has been selected in the drive menu.

bIP

Brake impul.

No - Yes

No

dtS

Tacho Coeff.

1 to 2

1

Multiplication coefficient of the feedback associated with tachogenerator function :
dtS =

rPG

9
tacho voltage at HSP HSP

PI Prop.Gain

0.01 to 100

1

Proportional gain of the PI regulator

rIG

PI Int.Gain

0.01 to 100/s

1/s

1 to 100

1

Integral gain of the PI regulator

FbS

PI Coeff.

PI feedback multiplication coefficient

PIC

PI Inversion

No - Yes

No

Reversal of the direction of correction of the PI regulator
no : normal
yes : reverse

Ftd

Freq.Lev.Att- Hz

LSP to HSP

50/60 Hz

Motor frequency threshold above which the logic output changes to 1

F2d

Freq.Lev.2

- Hz

LSP to HSP

50/60 Hz

Same function as Ftd, for a second frequency value

Ctd

Curr.Lev.Att-

A

0 to 1.36 In (1)

1.36 In (1)

Current threshold above which the logic output or the relay changes to 1

ttd

ThermLev.Att-

%

0 to 118%

100%

Motor thermal state threshold above which the logic output or the relay changes to 1

tL2

Trq.Limit 2

- %

0 to 200% (2)

200%

Second torque limit level activated by a logic input
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
(2) 100% corresponds to the nominal torque of a motor with a power rating equal to that associated with the
speed controller for "high torque" applications.
Parameters in gray boxes appear if an I/O extension card is installed
79

ENGLISH

Brake release pulse
Yes : While the brake is released the torque is always in the FW (foward) control corresponds to the
direction, regardless of the direction requested.
Check that the motor torque direction for FW (foward) control corresponds to the direction of
increase in load; if necessary reverse 2 motor phases.
no : while the brake is released the torque is in the requested direction of rotation.

GP_ATV58_EN.fm Page 80 Mardi, 2. avril 2002 6:09 18

Adjust Menu

Code

Description

PSP

PI Filter

- s

Adjustment range

Factory setting

0,0 à 10,0

0s

Adjusts the time constant of the filter on the return PI

PI2

PI Preset 2

- %

0 à 100 %

30 %

2nd preset reference of PI when a logic input has been assigned to 4 preset speeds.
100 % = maxi process
0 % = mini process

PI3

PI Preset 3

- %

0 à 100 %

60 %

ENGLISH

3rd preset reference of PI when a logic input has been assigned to 4 preset speeds.
100 % = maxi process
0 % = mini process

dtd

ATV Th. fault

0 à 118 %

105 %

Level of drive thermal state above which the logic output or relay change to state 1.

80

GP_ATV58_EN.fm Page 81 Mardi, 2. avril 2002 6:09 18

Drive Menu

This menu can be accessed when the switch is in position
.
The parameters can only be modified in stop mode with the speed controller locked.
Drive performance can be optimized by :
- entering the values given on the rating plate in the drive menu
- performing an auto-tune operation (on a standard asynchronous motor)
When using special motors (motors connected in parallel, tapered rotor brake motors, synchronous or
synchronized asynchronous motors, rheostatic rotor asynchronous motors) :
- Select the “Hdg : Handling” or the “GEn : General Use” macro-configuration.
- Set the “SPC” Special motor parameter to “Yes” in the drive menu.
- Adjust the “UFr” IR compensation parameter in the adjust menu to obtain satisfactory operation.

Description

Adjustment range

Factory setting

Nom.Mot.Volt - V

200 to 240V
200 to 500 V

230 V (2)
400/460V (2)

ENGLISH

Code

UnS

Nominal motor voltage given on the rating plate
The adjustment range depends on the speed controller model :
ATV58••••M2
ATV58••••N4

FrS

Nom.Mot.Freq- Hz

10 to 500 Hz

50/60Hz (2)

Nominal motor frequency given on the rating plate

nCr

Nom.Mot.Curr - A

0.25 to 1.36 In (1)

acc. to controller rating

Nominal motor current given on the rating plate

nSP

Nom.MotSpeed-rpm

0 to 9999 rpm

acc. to controller rating

Nominal motor speed given on the rating plate

COS

Mot. Cos Phi

0.5 to 1

acc. to controller rating

Motor Cos Phi given on the rating plate

tUn

Auto Tuning

No - Yes

No

Used to auto-tune motor control once this parameter has been set to “Yes”.
Once auto-tuning is complete, the parameter automatically returns to “Done”, or to “No” in the event
of a fault.
Caution : auto-tuning is only performed if no command has been activated. If a "freewheel stop" or
"fast stop" function is assigned to a logic input, this input must be set to 1 (active at 0).

tFr

Max. Freq.

- Hz

10 to 500 Hz

60/72Hz (2)

Maximum output frequency.
The maximum value is a function of the switching frequency. See SFR parameter (drive menu).

nLd

Energy Eco

No-Yes

Yes

Optimizes motor efficiency.
Can only be accessed in the variable torque macro-configuration.
(1) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
(2) according to position of 50/60Hz switch.

81

GP_ATV58_EN.fm Page 82 Mardi, 2. avril 2002 6:09 18

Drive Menu

Code

Description

Adjustment range

Factory setting

Fdb

I lim. Adapt

No-Yes

No

Adaptation of the current limit according to the output frequency.
This parameter only appears in the "variable torque" VT macro-configuration (ventilation
applications where the load curve changes according to the density of the gas).

brA

DecRampAdapt

No-Yes

No

ENGLISH

Activation of this function is used to increase the deceleration time automatically if this has been set
to too low a value for the inertia of the load, thus avoiding an ObF fault.
This function may be incompatible with positioning on a ramp and with the use of a braking resistor.
The factory setting depends on the macro-configuration used :
No for handling, Yes for variable torque and general use.
If relay R2 is assigned to the brake sequence function, the parameter brA remains locked on No.

Frt

SwitchRamp2- Hz

0 to HSP

0 Hz

Ramp switching frequency.
Once the output frequency exceeds Frt, the ramp times taken into account are AC2 and dE2.

Stt

Type of stop

STN - FST - NST - DCI

STN

Type of stop:
When a stop is requested, the type of stop is activated until the Ftt threshold (adjust menu) is
reached.
Below this threshold, freewheel stop is activated.
Stn: On ramp
Fst: Fast stop
Nst: Freewheel stop
Dci: DC injection stop
This parameter cannot be accessed if the R2 relay is assigned to the “BLC: Brake Logic” function.

rPt

Ramp Type

LIN - S - U

LIN

Defines the shape of the acceleration and deceleration ramps.
LIN : linear S : S-shape ramp U : U-shape ramp
f (Hz)

f (Hz)

GV

GV

The curve coefficient is fixed,
with t2 = 0.6 x t1
with t1 = set ramp time.

S-shape ramps
0

0

t

t2

t

t2

t1

t1

f (Hz)

f (Hz)

GV

GV

The curve coefficient is fixed,
with t2 = 0.5 x t1
with t1 = set ramp time.

U-shape ramps

0
t2

t

t1

dCF

DecRAmpCoeff

0
t2

t

t1

1 to 10

4

Deceleration ramp time reduction coefficient when the fast stop function is active.

82

GP_ATV58_EN.fm Page 83 Mardi, 2. avril 2002 6:09 18

Drive Menu

Code

Description

tLI

Trq.Limit

_ %

Adjustment range

Factory setting

0 to 200% (1)

200%

The torque limit is used to limit the maximum motor torque.

CLI

nt. I Lim -

A

0 to 1.36 In (2)

1.36 In

The current limit is used to limit motor overheating.

AdC

Auto DC Inj.

No-Yes

Yes

Used to deactivate automatic DC injection braking on stopping.

PCC

Motor P Coef

0.2 to 1

1

Defines the relationship between the speed controller nominal power and a less powerful motor
when a logic input has been assigned to the motor switching function.

Sw Freq. Type

LF-HF1-HF2

LF

Used to select a low switching frequency (LF) or a high switching frequency (HF1 or HF2). HF1
switching is designed for applications with a low load factor without derating the speed controller. If
the thermal state of the speed controller exceeds 95 %, the frequency automatically changes to 2
or 4 kHz depending on the speed controller rating. When the thermal state of the speed controller
drops back to 70 %, the selected switching frequency is re-established. HF2 switching is designed
for applications with a high load factor with derating of the speed controller by one rating : the drive
parameters are scaled automatically (torque limit, thermal current, etc).
Modifying this parameter results in the following parameters returning to factory
settings :
• nCr, CLI, Sfr, nrd (Drive menu)
• ItH, IdC, Ibr, Ctd (Adjust menu).

SFr

Sw Freq. -

kHz

0.5-1-2-4-8-12-16 kHz

acc. to controller rating

Used to select the switching frequency. The adjustment range depends on the SFt parameter.
If SFt = LF : 0.5 to 2 or 4 kHz acc. to the controller rating
If SFt = HF1 or HF2 : 2 or 4 to 16 kHz acc. to the controller rating
The maximum operating frequency (tFr) is limited according to the switching frequency :

nrd

SFr(kHz)

0.5

1

2

4

8

12

16

tFr (Hz)

62

125

250

500

500

500

500

Noise Reduct

No-Yes

(3)

This function modulates the switching frequency randomly to reduce motor noise.

SPC

Special motor

No-Yes

No

This function with "yes" extends the adjustment range for the UFr parameter in the adjust menu for
adaptation to the special motors mentioned at the start of this section. Can only be accessed in the
"Handling" and "General use" macro-configurations.
NO : normal motor
YES : special motor
PSM : small motor
(1) 100% corresponds to the nominal torque of a motor with a power rating equal to that associated with the
speed controller for "high torque" applications.
(2) In corresponds to the speed controller nominal current indicated in the catalog and on the speed controller
identification label for "high torque" applications.
(3) Yes if SFt = LF, No if SFt = HF1 or HF2

83

ENGLISH

SFt

GP_ATV58_EN.fm Page 84 Mardi, 2. avril 2002 6:09 18

Drive Menu

Code

Description

Adjustment range

Factory setting

PGt

PG Type

INC-DET

DET

Defines the type of sensor used when an encoder feedback I/O card is installed :
INC : incremental encoder (A, A+, B, B+ are hard-wired)
DET : detector (only A is hard-wired)

PLS

Num. Pulses

1 to 1024

11

Defines the number of pulses for one rotation of the encoder.

ENGLISH

Parameters in gray boxes appear if an I/O extension card is installed

84

GP_ATV58_EN.fm Page 85 Mardi, 2. avril 2002 6:09 18

Control Menu

This menu can be accessed when the switch is in position
mode with the speed controller locked.

. The parameters can only be modified in stop

Code

Description

Adjustment range

Factory setting

tCC

TermStripCon

2W- 3W (2-wire/ 3-wire)

2W

Configuration of terminal control : 2-wire or 3-wire control.
Modification of this parameter requires double confirmation as it results in reassignment of
the logic inputs. By changing from 2-wire control to 3-wire control, the logic input assignments
are shifted by one input. The LI3 assignment in 2-wire control becomes the LI4 assignment
in 3-wire control. In 3-wire control, inputs LI1 and LI2 cannot be reassigned.
Handling
STOP
RUN forward
RUN reverse
2 preset speeds
4 preset speeds
8 preset speeds

General use
STOP
RUN forward
RUN reverse
jog operation
freewheel stop
clear faults

Variable torque
STOP
RUN forward
RUN reverse
ref. switching
injection braking
freewheel stop

ENGLISH

I/O
LI1
LI2
LI3
LI4
LI5
LI6

The I/O with a gray background can be accessed if an I/O extension card has been installed.
3-wire control (pulse control : one pulse is sufficient to control start-up). This option inhibits the
"automatic restart" function.
Wiring example :
ATV58 control terminals
LI1 : stop
24 V LI1 LI2 LIx
LI2 : forward
LIx : reverse

This option only appears if 2-wire control is configured.
Code

Description

Adjustment range

Factory setting

tCt

Type 2 Wire

LEL-TRN-PFo

LEL

Defines 2-wire control :
- according to the state of the logic inputs (LEL : 2-wire)
- according to a change in state of the logic inputs (TRN : 2-wire trans.)
- according to the state of the logic inputs with forward always having priority over reverse
(PFo : Priorit. FW)
Wiring example :
ATV58 control terminals
LI1 : forward
24 V LI1 LIx
LIx : reverse

Parameters in gray boxes appear if an I/O extension card is installed

85

GP_ATV58_EN.fm Page 86 Mardi, 2. avril 2002 9:13 21

Control Menu

Code

Description

Adjustment range

Factory setting

rln

RV Inhib.

No - Yes

No

• Inhibition of operation in the opposite direction to that controlled by the logic inputs, even if this
reversal is required by a summing or process control function.
• Inhibition of reverse if it is controlled by the FWD/REV key on the display module.

bSP

deadb./pedst

No
BNS:Pedestal
BLS:Deadband

No

ENGLISH

Management of operation at low speed :

F : motor frequency

F : motor frequency

HSP

HSP
No

LSP

Reference
100 %

0

LSP
0

Pedestal
(BNS)
Reference
100 %

F : motor frequency
HSP
Deadband
(BLS)

LSP

Reference
100 %

0

CrL
CrH

AI2 min Ref.- mA
AI2 Max. Ref- mA

0 to 20 mA
4 to 20 mA

4 mA
20 mA

Minimum and maximum value of the signal on input AI2.
These two parameters are used to define the signal sent to AI2. There are several configuration
possibilities, one of which is to configure the input for a 0-20 mA, 4-20 mA, 20-4mA, etc signal.

Frequency
HSP

LSP
0

86

CrL

CrH

2
20 AI
(mA)

GP_ATV58_EN.fm Page 87 Mardi, 2. avril 2002 6:09 18

Control Menu

Code

Description

Adjustment range

Factory setting

AOL
AOH

AO Min. Val- mA
AO Max. Val- mA

0 to 20 mA
0 to 20 mA

0 mA
20 mA

Min. and max. value of the signal on output AO and AO1 (1).
These two parameters are used to define the output signal on AO
and AO1.
Eg. : 0-20 mA, 4-20 mA, 20-4mA, etc

Parameter
Max

AO (mA)

0
AOL

Str

AOH

Save Ref.

20

NO-RAM-EEP

NO

LCC

Keypad Comm.

No-Yes

ENGLISH

Associated with the +/- speed function, this function is used to save the reference :
when the run commands disappear (save in RAM) or when the line supply disappears (save in
EEPROM)
On the next start-up, the speed reference is the last reference saved.
No

Used to activate speed controller control via the display module. The STOP/RESET, RUN and
FWD/REV keys are active. The speed reference is given by the parameter LFr. Only the freewheel
stop, fast stop and DC injection stop commands remain active at the terminals. If the speed
controller / display module connection is cut, the speed controller locks in an SLF fault.

PSt

STOP Priorit

No-Yes

Yes

This function gives priority to the STOP key irrespective of the control channel (terminals or
fieldbus).
To set the PSt parameter to "No" :
1 - Display "No".
2 - Press the "ENT" key.
3 - The speed controller displays "See manual"
4 - Press ▲ then ▼ then "ENT".
For applications with continuous processes, it is advisable to configure the key as inactive (set to
"No").

Add

DriveAddress

0 to 31

0

Address of the speed controller when it is controlled via the display module port (with the display
module and programming terminal removed)

tbr

BdRate RS485

9600-19200

19200

Transmission speed via the RS485 serial link (effective on the next power-up)
9600 bps
19200 bps
If tbr ≠ 19200, the terminal can no longer be used. To reactivate the terminal,
reconfigure tbr as 19200 via the serial link or revert to factory settings (see page 63).

rPr

Reset counters

No-APH-RTH

No

KWh or operating time reset to 0
No: No
APH: KWh reset to 0
RTH: Operating time reset to 0
APH and RTH are active immediately. The parameter then automatically returns to NO.
Press “ENT” to confirm the reset to 0 command.
(1) Analog output AO appear if an I/O extension card is installed
87

GP_ATV58_EN.fm Page 88 Mardi, 2. avril 2002 6:09 18

I/O Menu

This menu can be accessed when the switch is in position
.
The assignments can only be modified in stop mode with the speed controller locked.
Code

Function

LI2

LI2 Assign.
See the summary table and description of the functions

The inputs and outputs available in the menu depend on the I/O cards installed (if any) in the speed controller,
as well as the selections made previously in the control menu.
The “factory” configurations are preassigned by the selected macro-configuration.

Summary table of the configurable input assignments (exc. 2-wire / 3-wire option)
ENGLISH

I/O extension option cards

2 logic inputs LI5-LI6

Speed controller without option

NO:Not assigned
RV :Reverse

3 logic inputs LI2 to LI4
(Not assigned)

X

(Run reverse)

X

(Ramp switching)

X

(Jog operation)

X

+SP: + Speed

(+ speed)

X

-SP: - Speed

(- speed)

X

PS2: 2 Preset SP

(2 preset speeds)

X

PS4: 4 Preset SP

(4 preset speeds)

X

PS8: 8 Preset SP

(8 preset speeds)

X

(Reference switching)

X

(Freewheel stop)

X

(Injection stop)

X

RP2:Switch Ramp2
JOG

RFC:Auto/manu
NST:Freewhl Stop
DCI:DC inject.
FST:Fast stop
CHP:Multi. Motor

(Fast stop)

X

(Motor switching)

X

TL2:Trq.Limit 2

(Second torque limit)

X

FLO:Forced Local

(Forced local mode)

X

(Clearing faults)

X

RST:Fault Reset
ATN:Auto-tune
PAU:PI Auto/Manu
PR2:PI 2 Preset
PR2:PI 4 Preset
TLA:Torque limit
EDD:Ext flt.

(Auto-tuning)

X

(PI Auto/Manu) If one AI = PIF

X

(2 preset PI setpoints) If one AI = PIF

X

(4 preset PI setpoints) If one AI = PIF

X

(Torque limitation by AI) If one AI = ATL

X

(external fault)

X

CAUTION: If a logic input is assigned to "Freewheel stop" or "Fast stop", start-up can only be
performed by linking this input to the +24V, as these stop functions are active when inputs are at
state 0.

88

GP_ATV58_EN.fm Page 89 Mardi, 2. avril 2002 6:09 18

I/O Menu

Summary table of the configurable input and encoder assignment
I/O extension option cards

Speed controller without option

NO:Not assigned
FR2:Speed Ref2
SAI:Summed Ref.

Encoder
input (1)
A+, A-,
B+, B-

X

X

X

Analog input
AI2
(Not assigned)

X

(Speed reference 2)
If one LI = RFC

X
X

X

X

X

(Manual PI speed reference)
If one AI = PIF and one LI = PAU

X

SFB:Tacho feedbk

(Tachogenerator)

X

PTC:Therm.Sensor

(PTC probes)

X

(Torque limit)

X

ATL:Torque Lim.
RGI:PG feedbk

(Encoder or sensor feedback)

ENGLISH

(Summing reference)
(Pl regulator feedback)

PIF:PI Regulator
PIM:PI Man.ref.

Analog input
AI3

X

(1) NB : The menu for assigning encoder input A+, A-, B+, B- is called "Assign AI3".
CAUTION : If relay R2 is assigned to the "brake sequence" function, AI3 is automatically assigned in
the factory setting to Tacho Feedback, if the card is present. However, it is still possible to reassign
AI3.

Summary table for configurable outputs
I/O extension option card

Logic output
LO

Speed controller without option

NO:Not assigned
RUN:DriveRunning
OCC:OutputCont.

Relay R2
(Not assigned)

X

X

(Speed controller running)

X

X

(Downstream contactor control)

X

X

FTA:Freq Attain.

(Threshold freq. reached)

X

X

FLA:HSP Attained

(HSP reached)

X

X

(Current threshold reached)

X

X

SRA:FRH Attained

(Frequency reference reached)

X

X

TSA:MtrTherm Lvl

(Motor thermal threshold reached)

X

X

(Brake sequence)

X

CTA:I Attained

BLC:Brk Logic
APL:4-20 mA loss
F2A:F2 Attained
TAD:ATV th. Alarm

(Loss of 4-20 mA signal)

X

X

(Second frequency threshold reached)

X

X

(Drive thermal threshold reached)

X

X

89

GP_ATV58_EN.fm Page 90 Mardi, 2. avril 2002 6:09 18

I/O Menu

Table of the analogue output assignments
I/O extension
option cards

Analog output AO

ENGLISH

Speed controller without option

Analog output AO1

NO :Not assigned

(Not assigned)

X

OCR:Motor Curr.

(Motor current)

X

OFR:Motor Freq

(Motor speed)

X

ORP:Output ramp

(Ramp output)

X

TRQ:Motor torque

(Motor torque)

X

STQ:Signed Torq.

(Signed motor torque)

X

ORS:Signed ramp

(Signed ramp output)

X

OPS:PI ref.
OPF:PI Feedback

(PI setpoint output) If one AI = PIF

X

(PI feedback output) If one AI = PIF

X

(PI error output) If one AI = PIF

X

OPE:PI Error
OPI:PI Integral

(PI integral output) If one AI = PIF

X

OPR:Motor power

(Motor power)

X

THR:Motor Thermal

(Motor thermal state)

X

THD:Drive Thermal

(Drive thermal state)

X

Once the I/O have been reassigned, the parameters related to the function automatically appear in the
menus, and the macro-configuration indicates “CUS : Customize”.
Some reassignments result in new adjustment parameters which the user must not forget to set in the
adjust menu :
I/O

Assignments

Parameters to set

Ramp switching

AC2 dE2

JOG

Jog operation

JOG JGt

PS4

4 preset speeds

SP2-SP3

LI

PS8

8 preset speeds

SP4-SP5-SP6-SP7

LI

DCI

Injection stop

IdC

LI

TL2

Second torque limit

tL2

LI

PR4

4 preset PI setpoints

PI2-PI3

AI

PIF

PI regulator

rPG-rIG-PIC-rdG-rED-PrGPSr-PSP-PLr-PLb

LI

RP2

LI
LI

AI

SFB

Tachogenerator

dtS

R2

BLC

Brake sequence

Ibr-brt-bEn-bEt-brL-bIP

LO/R2

FTA

Frequency threshold reached

Ftd

LO/R2

CTA

Current threshold reached

Ctd

LO/R2

TSA

Motor thermal threshold reached

ttd

LO/R2

F2A

2 nd frequency threshold reached

F2d

LO/R2

TAD

Drive thermal threshold reached

dtd

90

GP_ATV58_EN.fm Page 91 Mardi, 2. avril 2002 6:09 18

I/O Menu

Some reassignments result in new adjustment parameters being added which the user must configure
in the control, drive or fault menu :
I/O

Assignments

Parameters to set

LI

-SP

- speed

Str (control menu)

LI

FST

Fast stop

dCF (drive menu)

LI

RST

Fault reset

rSt (fault menu)

AI

SFB

Tachogenerator

Sdd (fault menu)

A+, A-,
B+, B-

SAI

Summing reference

PGt, PLS (drive menu)

A+, A-,
B+, B-

RGI

PG Feedback

PGt, PLS (drive menu)

ENGLISH
91

GP_ATV58_EN.fm Page 92 Mardi, 2. avril 2002 6:09 18

Configurable I/O Application Functions

Function compatibility table

Summing inputs
PI regulator

➞

+ / - speed
Reference switching

➞

➞

Freewheel stop
Fast stop
Preset speeds

➞

➞

Jog operation

➞
➞

Speed regulation with
tachogenerator or encoder
Torque limitation via AI3
Torque limitation via LI

Incompatible functions
Compatible functions
Not applicable
Priority functions (functions which cannot be active simultaneously) :

➞

➞

The function indicated by the arrow has priority over the other.

Stop functions have priority over run commands.
Speed references via logic command have priority over analog setpoints.

92

Torque limitation via LI

Torque limitation via AI3

Speed regulation with
tachogenerator or encoder

Preset speeds

Jog operation

Fast stop

Freewheel stop

Reference switching

+ / - speed

PI regulator

Summing inputs

DC injection
braking
DC injection
braking

➞

ENGLISH

The choice of application functions may be limited by incompatibility between certain functions. Functions
which are not listed in this table are fully compatible.

GP_ATV58_EN.fm Page 93 Mardi, 2. avril 2002 6:09 18

Configurable I/O Application Functions

Logic input application functions
Operating direction : forward / reverse
Reverse operation can be disabled for applications requiring only a single direction of motor rotation.
2-wire control
Run and stop are controlled by the same logic input, for which state 1 (run) or 0 (stop), or a change in state is
taken into account (see the 2-wire control menu).
3-wire control
Run and stop are controlled by 2 different logic inputs. LI1 is always assigned to the stop function. A stop is
obtained on opening (state 0).
The pulse on the run input is stored until the stop input opens.

Ramp switching : 1st ramp : ACC, DEC ; 2nd ramp : AC2, DE2
Two types of activation are possible :
activation of logic input LIx
detection of an adjustable frequency threshold
If a logic input is assigned to the function, ramp switching can only be performed by this input.
Step by step operation (“JOG”) : Low speed operation pulse
If the JOG contact is closed and then the operating direction contact is actuated, the ramp is 0.1 s irrespective
of the ACC, dEC, AC2, dE2 settings. If the direction contact is closed and the JOG contact is then actuated,
the configured ramps are used.
Parameters which can be accessed in the adjust menu :
- JOG speed
- anti-repeat delay (minimum time between 2 “JOG” commands).

93

ENGLISH

During power-up or manual or automatic fault resetting, the motor can only be supplied with power after a reset
prior to the “forward”, “reverse”, and “injection stop” commands.

GP_ATV58_EN.fm Page 94 Mardi, 2. avril 2002 9:15 21

Configurable I/O Application Functions

+ / - speed : 2 types of operation are available
1 Use of single action buttons : two logic inputs are required in addition to the operating direction(s). The input
assigned to the “+ speed” command increases the speed, the input assigned to the “- speed” command
decreases the speed.
This function accesses the Str save reference parameter in the Control menu.
2 Use of double action buttons : only one logic input assigned to + speed is required.
+ / - speed with double action buttons :

ENGLISH

Description : 1 button pressed twice for each direction of rotation.
Each action closes a volt-free contact.
Release (- speed)

Press 1 (speed
maintained)

Press 2 (+ speed)

forward button

–

a

a and b

reversebutton

–

c

c and d

Wiring example :

ATV58 control terminals
LI1 LIx LIy
+ 24

LI1 : forward
LIx : reverse
LIy : + speed

b
a

d

c

Motor
frequency
LSP
0
LSP
Forward
Press 2
Press 1
0
Reverse
Press 2
Press 1
0

b
a a a

b
a

a

a

a

c

d
c

This type of +/- speed is incompatible with 3-wire control. In this case, the - speed function is automatically
assigned to the logic input with the highest index (for example : LI3 (+ speed), LI4 (- speed)).
In both cases of operation, the maximum speed is given by the references applied to the analog inputs.
For example, connect AI1 to +10V.

94

GP_ATV58_EN.fm Page 95 Mardi, 2. avril 2002 9:18 21

Configurable I/O Application Functions

Preset speeds
2, 4 or 8 speeds can be preset, requiring 1, 2, or 3 logic inputs respectively.
The following order of assignments must be observed : PS2 (LIx), then PS4 (LIy), then PS8 (LIz).
2 preset speeds

4 preset speeds

8 preset speeds

Assign : LIx to PS2

Assign : LIx to PS2 then,
LIy to PS4

Assignr : LIx to PS2
LIy to PS4, then LIz to PS8

speed reference

LIy

LIx

speed reference

LIz

LIy

LIx

speed reference

0

LSP+reference

0

0

LSP+reference

0

0

0

LSP+reference

1

HSP

0

1

SP2

0

0

1

SP2

1

0

SP3

0

1

0

SP3

1

1

HSP

0

1

1

SP4

1

0

0

SP5

1

0

1

SP6

1

1

0

SP7

1

1

1

HSP

ENGLISH

LIx

To unassign the logic inputs, the following order must be observed : PS8 (LIz), then PS4 (LIy), then PS2 (LIx).
Reference switching
Switching of two references (AI1 reference and AI2 reference) by logic input command.
This function automatically assigns AI2 to speed reference 2.
Connection diagram

LI x + 24 COM

AI 1

+10

AI 2

0-20mA
4-20mA

Open contact, reference = AI2
Closed contact, reference = AI1

Freewheel stop
Causes the motor to stop using the resistive torque only. The motor power supply is cut.
A freewheel stop is obtained when the logic input opens (state 0).
DC injection stop
An injection stop is obtained when the logic input closes (state 1).
Fast stop
Braked stop with the deceleration ramp time reduced by a reduction factor dCF which appears in the drive
menu.
A fast stop is obtained when the logic input opens (state 0).

95

GP_ATV58_EN.fm Page 96 Mardi, 2. avril 2002 6:09 18

Configurable I/O Application Functions

Motor switching
This function is used to switch between two motors with different power ratings using the same speed
controller. An appropriate sequence must be installed on the speed controller output. Switching is carried out
with the motor stopped and the speed controller locked. The following internal parameters are automatically
switched by the logic command :
- nominal motor current
- injection current

- brake release current

This function automatically inhibits thermal protection of the second motor.
Accessible parameter : Motor power ratio (PCC) in the drive menu.

ENGLISH

Second torque limit
Reduction of the maximum motor torque when the logic input is active.
Parameter tL2 in the adjust menu.
Fault reset
Two types of reset are available : partial or general (rSt parameter in the "fault" menu).
Partial reset (rSt = RSP) :
Used to clear the stored fault and reset the speed controller if the cause of the fault has disappeared.
Faults affected by partial clearing :
-

line overvoltage
DC bus overvoltage
motor phase loss
overhauling

-

communication fault
motor overload
loss of 4-20mA
external fault

-

motor overheating
serial link fault
speed controller overheating
overspeed

General reset (rSt = RSG) :
This inhibits all faults (forced operation) except SCF (motor short-circuit) while the assigned logic input
is closed.
Forced local mode
Used to switch between line control mode (serial link) and local mode (controlled via the terminals or via the
display module).
Auto-tuning
When the assigned logic input changes to 1 an auto-tuning operation is triggered, in the same way as
parameter tUn in the "drive" menu.
Caution : Auto-tuning is only performed if no command has been activated. If a "freewheel stop" or "fast stop"
function is assigned to a logic input, this input must be set to 1 (active at 0).
Application : When switching motors, for example.
Auto-man PI, preset PI setpoints : PI operation (see page 97)
Torque limitation by AI
This function is only accessible if the analogue input AI3 is assigned to torque limit. If there is not a logic input
configured on TL2 : second torque limit, the limit is directly given by AI3.
If a logic input is configured on TL2 second torque limit.
- When the input is 0 the limit is given by tLi
- When the input is 1 the limit is given by AI3
External fault
When the assigned logic input changes to 1, the motor stops (according to the configuration of the LSF
Stop+flt parameter in the Drive menu), and the drive locks in EPF external fault fault mode.
96

GP_ATV58_EN.fm Page 97 Mardi, 2. avril 2002 9:24 21

Configurable I/O Application Functions

Analog input application functions
Input AI1 is always the speed reference.

Assignment of AI2 and AI3
Summing speed reference : The frequency setpoints given by AI2 and AI3 can be summed with AI1.
Speed regulation with tachogenerator : (Assignment on AI3 only with an I/O extension card with analog
input)
An external divider bridge is required to adapt the voltage of the tachogenerator. The maximum voltage must
be between 5 and 9 V. A precise setting is then obtained by setting the dtS parameter available in the adjust
menu.

PI regulator: Used to regulate a process with a reference and a feedback given by a sensor. In PI mode the
ramps are all linear, even if they are configured differently.
With the PI regulator, it is possible to:
- Adapt the feedback via FbS.
- Correct PI inversion.
- Adjust the proportional and integral gain (RPG and RIG).
- Assign an analog output for the PI reference, PI feedback and PI error.
- Apply a ramp to establish the action of the PI (AC2) on start-up if PSP > 0.
If PSP = 0 the active ramps are ACC/dEC. The dEC ramp is always used when stopping.
The motor speed is limited to between LSP and HSP.
Note: PI regulator mode is active if an AI input is assigned to PI feedback. This AI assignment can only be
made after disabling any functions incompatible with PI (voir page 92).

PI
setpoint

+

PI
feedback PSP

FBS
10

Low-pass Multiplieur
filter

Manual setpoint
Auto / man

PI
reversal

PI
regulator

PIC
X±1

RPG
RIG

Ramp
if PSP = 0
X

Ramp
if PSP > 0

AC2
dE2

ACC
dEC

Reference
Auto
Man

Run command
ACC
dEC
Ramp

Auto/Man: This function can only be accessed when the PI function is active, and requires an I/O extension
card with analog input
Via logic input LI, this is used to switch operation to speed regulation if LIx = 0 (manual reference on AI3), and
PI regulation if LIx = 1 (auto).
97

ENGLISH

PTC probe processing : (only with an I/O extension card with analog input). Used for the direct thermal
protection of the motor by connecting the PTC probes in the motor windings to analog input AI3.
PTC probe characteristics :
Total resistance of the probe circuit at 20 °C = 750 W.

GP_ATV58_EN.fm Page 98 Mardi, 2. avril 2002 6:09 18

Configurable I/O Application Functions

Analog input application functions
Preset setpoints:
2 or 4 preset setpoints require the use of 1 or 2 logic inputs respectively:

ENGLISH

LIx

2 preset setpoints

4 preset setpoints

Assign: LIx to Pr2

Assign: LIx to Pr2 then, LIy to Pr4

Reference

0

Analog reference

1

Process max (= 10 V)

LIy

LIx

0

0

Reference
Analog reference

0

1

PI2 (adjustable)

1

0

PI3 (adjustable)

1

1

Process max (= 10 V)

Torque limit : (Only with an I/O extension card with analog input AI3)
The signal applied at AI3 operates in a linear fashion on the internal torque limit (parameter TLI in the "drive
menu") :
- If AI3 = 0V : limit = TLI x 0 = 0
- If AI3 = 10 V : limit = TLI.
Applications : Torque or traction correction, etc.

Encoder input application functions :
(Only with an I/O extension card with encoder input)
Speed regulation : Is used for speed correction using an incremental encoder or sensor.
(See documentation supplied with the card).
Summing speed reference : The setpoint from the encoder input is summed with AI1. (See documentation
supplied with the card)
Applications :
- Synchronization of the speed of a number of speed controllers. Parameter PLS in the "drive" menu is
used to adjust the speed ratio of one motor in relation to that of another.
- Setpoint via encoder.

98

GP_ATV58_EN.fm Page 99 Lundi, 8. avril 2002 3:36 15

Configurable I/O Application Functions

Logic output application functions
Relay R2, LO solid state output (with I/O extension card)
Downstream contactor control (OCC): can be assigned to R2 or LO
Enables the speed controller to control an output contactor (located between the speed controller and the
motor). The request to close the contactor is made when a run command appears. The request to open the
contactor is made when there is no more current in the motor.
If a DC injection braking function is configured, it should not be left operating too long in stop mode,
as the contactor only opens at the end of braking.
Speed controller running (RUN) : can be assigned to R2 or LO
The logic output is at state 1 if the motor power supply is provided by the speed controller (current present), or
if a run command is present with a zero reference.

Setpoint reached (SRA): can be assigned to R2 or LO
The logic output is at state 1 if the motor frequency is equal to the setpoint value.
High speed reached (FLA): can be assigned to R2 or LO
The logic output is at state 1 if the motor frequency is equal to HSP.
Current threshold reached (CTA): can be assigned to R2 or LO
The logic output is at state 1 if the motor current is greater than or equal to the current threshold set by Ctd in
the adjust menu.
Motor thermal state reached (TSA) : can be assigned to R2 or LO
The logic output is at state 1 if the motor thermal state is greater than or equal to the thermal state threshold
set by ttd in the adjust menu.
Drive thermal state reached (TAD) : can be assigned to R2 or LO
The logic output is at state 1 if the drive thermal state is greater than or equal to the thermal state threshold set
by dtd in the adjust menu.
Brake sequence (BLC) : can only be assigned to relay R2
Used to control an electromagnetic brake by the speed controller, for vertical lifting applications. For brakes
used for horizontal movement, use the “speed controller running“ function.
Motor speed
Setpoint

Brake status
1
0

T = non-adjustable time delay
Settings which can be accessed in the
adjust menu :
- brake release frequency (brL)
- brake release delay (brt)
- brake engage delay (bEt)
- brake release current (Ibn)
- brake engage frequency (bEn)

R2 relay
1
0
Up or down
1

99

ENGLISH

Frequency threshold reached (FTA) : can be assigned to R2 or LO
The logic output is at state 1 if the motor frequency is greater than or equal to the frequency threshold set by
Ftd in the adjust menu.

GP_ATV58_EN.fm Page 100 Mardi, 2. avril 2002 6:09 18

Configurable I/O Application Functions

Recommended settings for brake control, for a vertical lifting application :
1 Brake release frequency (brL) :
Set the brake release frequency to the value of the nominal slip multiplied by the nominal frequency in Hz
(g x FS).
Ns – Nr )
Calculation method : slip = (------------------------

ENGLISH

Ns

Ns = synchronous speed in rpm.
(for 50 Hz supply : Ns = 3000 rpm for a motor with 1 pair of poles, 1500 rpm for a motor with 2 pairs of poles,
1000 rpm for a motor with 3 pairs of poles and 750 rpm for a motor with 4 pairs of poles,
for 60 Hz supply : Ns = 3600 rpm for a motor with 1 pair of poles, 1800 rpm for a motor with 2 pairs of poles,
1200 rpm for a motor with 3 pairs of poles and 900 rpm for a motor with 4 pairs of poles).
- Nr = nominal speed at nominal torque in rpm, use the speed indicated on the motor rating plate.
Release frequency = g x Fs.
- g = slip calculated previously
- Fs = nominal motor frequency (indicated on the motor rating plate)
Example : for a motor with 2 pairs of poles, 1430 rpm given on plate, 50 Hz supply.
g = (1500 - 1430) / 1500 = 0.0466
Brake release frequency = 0.0466 x 50 = 2.4 Hz
2 Brake release current (Ibr) :
Adjust the brake release current to the nominal current indicated on the motor.
Note regarding points 1 and 2 : the values indicated (release current and release frequency) correspond to
theoretical values. If during testing, the torque is insufficient using these theoretical values, retain the brake
release current at the nominal motor current and lower the brake release frequency (up to 2/3 of the nominal
slip). If the result is still not satisfactory, return to the theoretical values then increase the brake release
current (the maximum value is imposed by the speed controller) and increase the brake release frequency
gradually.
3 Acceleration time :
For lifting applications, it is advisable to set the acceleration ramps to more than 0.5 seconds. Ensure that
the speed controller does not exceed the current limit.
The same recommendation applies for deceleration.
Note : for a lifting movement, a braking resistor should be used. Ensure that the settings and configurations
selected cannot cause a drop or a loss of control of the lifted load.
4 Brake release delay (brt) :
Adjust according to the type of brake. It is the time required for the mechanical brake to open.
5 Brake engage frequency (bEn) :
Set to twice the nominal slip (in our example 2 x 2.4 = 4.8 Hz). Then adjust according to the result.
6 Brake engage delay (bEt) :
Adjust according to the type of brake. It is the time required for the mechanical brake to close.
Loss of 4-20 mA signal (APL), can be assigned to R2 or L0
The logic output is set to 1 if the signal on the 4-20 mA input is less than 2 mA.

100

GP_ATV58_EN.fm Page 101 Mardi, 2. avril 2002 6:09 18

Configurable I/O Application Functions

AO and AO1 analog output application functions
The analogue outputs AO and AO1 are the output currents of AOL (mA) and AOH (mA),
• AOL and AOH being configurable from 0 to 20 mA.
Examples AOL - AOH : 0 - 20 mA
4 - 20 mA
20 - 4 mA
Motor current (Code OCR) : the image of the motor rms current.
• AOH corresponds to twice the nominal speed controller current.
• AOL corresponds to zero current.

ENGLISH

Motor frequency (Code OFR) : the motor frequency estimated by the speed controller.
• AOH corresponds to the maximum frequency (parameter tFr).
• AOL corresponds to zero frequency.
Ramp output (Code ORP) : the image of the ramp output frequency.
• AOH corresponds to the maximum frequency (parameter tFr).
• AOL corresponds to zero frequency.
Motor torque (Code TRQ) : the image of the motor torque as an absolute value.
• AOH corresponds to twice the nominal motor torque.
• AOL corresponds to zero torque.
Signed motor torque (Code STQ) : the image of the motor torque and direction :
• AOL corresponds to a braking torque = twice the nominal torque
• AOH corresponds to a motor torque = twice the nominal torque.
• AOH + AOL corresponds to zero torque.
2
Signed ramp (Code ORS): the image of the ramp output frequency and direction.
• AOL corresponds to the maximum frequency (parameter tFr) in the reverse direction.
• AOH corresponds to the maximum frequency (parameter tFr) in the forward direction.
• AOH + AOL corresponds to zero frequency.
2
PI setpoint (Code OPS): the image of the PI regulator setpoint
• AOL corresponds to the minimum setpoint.
• AOH corresponds to the maximum setpoint.
PI feedback (Code OPF): the image of the PI regulator feedback
• AOL corresponds to the minimum feedback.
• AOH corresponds to the maximum feedback.
PI error (Code OPE) : the image of the PI regulator error as a % of the sensor range (maximum feedback
– minimum feedback)
• AOL corresponds to the maximum error < 0
• AOH corresponds to the maximum error >0
• AOH + AOL corresponds to null error (OPE = 0)
2

101

GP_ATV58_EN.fm Page 102 Mardi, 2. avril 2002 6:09 18

Configurable I/O Application Functions

PI intégral (Code OPI) : the image of the PI regulator error integral.
• AOL corresponds to a null integral
• AOH corresponds to a saturated integral
Motor power (Code OPR) : the image of the power drawn by the motor.
• AOL corresponds to 0 % of the motor nominal power.
• AOH corresponds to 200 % of the motor nominal power.
Motor thermal state (Code THD) : the image of the calculated motor thermal power.
• AOL corresponds to 0 %.
• AOH corresponds to 200 %.

ENGLISH

Drive thermal state (Code THD) : the image of the drive thermal power.
• AOL corresponds to 0 %.
• AOH corresponds to 200 %.

102

GP_ATV58_EN.fm Page 103 Mardi, 2. avril 2002 6:09 18

Fault Menu

This menu can be accessed when the switch is in position
.
Modifications can only be made in stop mode with the speed controller locked.
Code

Description

Factory setting

Atr

Auto Restart

No

rSt

Reset Type

RSP

This function can be accessed if the fault reset is assigned to a logic input.
2 possible options : partial reset (RSP), general reset (RSG)
Faults affected by a partial reset (rSt = RSP)
- line overvoltage
- DC bus overvoltage
- motor overheating
- loss of 4-20mA
- motor overload
- overhauling
- motor phase loss
- speed controller overheating
- serial link fault
- external fault
- communication fault
- overspeed
Faults affected by a general reset (rSt = RSG) : all faults. The general reset actually inhibits all the
faults (forced operation).
To configure rSt = RSG :
1 Display RSG.
2 Press the "ENT" key.
3 The speed controller displays "See manual".
4 Press ▲ then ▼ then "ENT".

OPL

OutPhaseLoss

Yes

Used to enable the motor phase loss fault.
(Fault is disabled if an isolator is used between the speed controller and the motor).
Yes / No options

IPL

InPhseLoss

Yes

Used to enable the line phase loss fault.
(Fault is disabled if there is a direct power supply via a DC bus, or a single phase supply to an
ATV58•U72M2, U90M2, D12M2
Yes / No options
This fault does not exist on the ATV58•U09M2, U18M2, U29M2 and U41M2.

103

ENGLISH

This function is used to restart the speed controller automatically if a fault has disappeared (Yes/No
option). Automatic restarting is possible after the following faults :
- line overvoltage
- DC bus overvoltage
- external fault
- motor phase loss
- serial link fault
- communication fault
- loss of 4-20 mA reference
- motor overload (condition : motor thermal state less than 100 %)
speed controller overheating (condition : speed controller thermal state less than 70 %)
- motor overheating (condition : resistance of probes less than 1,500 Ohms)
When the function is activated, following appearance of one or more of these faults, the R1 relay
stays closed: the drive attempts to start every 30 s. A maximum of 6 attempts are made with the
drive unable to start (fault present). If all 6 fail, the drive remains locked definitively with the fault relay
open, until it is reset by being switched off.
This function requires the associated sequence to be maintained. Ensure that accidental
restarting will not pose any danger to either equipment or personnel.

GP_ATV58_EN.fm Page 104 Mardi, 2. avril 2002 6:09 18

Fault Menu

Code

Description

Factory setting

tHt

ThermProType

ACL

Defines the type of indirect motor thermal protection provided by the speed controller. If the PTC
probes are connected to the speed controller, this function is not available. No thermal protection :
NO: No Prot.
Self-cooled motor (ACL) : the speed controller takes account of a derating depending on the rotation
frequency.
Force-cooled motor (FCL) : the speed controller does not take account of a derating depending on
the rotation frequency.

LFL

LossFollower

No

ENGLISH

Used to enable the loss of 4-20 mA reference fault.
This fault can only be configured if the min/max AI2 ref. parameters (CrL and CrH) are greater than
3 mA, or if CrL>CrH,
- No : no fault.
- Yes : immediate fault.
- STT : stop according to the parameter STT, without a fault restart on the return of the signal.
- LSF : stop according to the parameter STT, drive shows a fault after stopping.
- LFF : Force the speed to the value set by LFF.
- RLS : maintain the speed reached when the 4-20mA disappeared without a fault, restart on
the return of the signal.

LFF

Flt. Speed 4-20

0

Fallback speed in the event of the loss of the 4-20mA signal. Can be adjusted from 0 to HSP.

FLr

Catch On Fly

No

Used to enable a smooth restart after one of the following events :
- loss of line supply or simple power off
- fault reset or automatic restart.
- freewheel stop or injection stop with logic input
- uncontrolled loss downstream of the speed controller
Yes / No options.
If relay R2 is assigned to the brake sequence function, the FLr parameter remains locked on No.

StP

Cont. Stop

No

Controlled stop on a line phase loss. This function is only operational if parameter IPL is set to No.
If IPL is set to Yes, leave StP in position No. Possible choices :
No : locking on loss of line supply
MMS : Maintain DC Bus : voltage for the speed controller control is maintained by the kinetic energy
restored by the inertia, until the USF fault (undervoltage) occurs
FRP : Follow ramp : deceleration following the programmed dEC or dE2 ramp until a stop or until
the USF fault (undervoltage) occurs. This operation does not exist on ATV58•U09M2, U18M2,
U29M2 and U41M2.

Sdd

RampNotFoll

Yes

This function can be accessed if feedback via tachogenerator or pulse generator is programmed.
When enabled, it is used to lock the speed controller, if a speed error is detected (difference
between the stator frequency and the measured speed). Yes / No options.

EPL

104

External fault
Yes
Defines the type of stop on externel fault:
- Yes: immediate fault
- LSF Stop+flt: stop according to the Stt parameter, then fault at the end of stopping

GP_ATV58_EN.fm Page 105 Mardi, 2. avril 2002 6:09 18

Files Menu

This menu can be accessed when the switch is in position
.
The operations are only possible in stop mode with the speed controller locked.
The display module is used to store 4 files containing the speed controller configurations.
Code

Description

Factory setting

F1S
F2S
F3S
F4S

File
File
File
File

FRE
FRE
FRE
FRE

1
2
3
4

State
State
State
State

Used to display the state of the corresponding file.
Possible states :
FRE : file free (state when display module is delivered)
EnG : A configuration has already been saved in this file

Operat.Type

NO

Used to select the operation to be performed on the files.
Possible operations :
NO : no operation requested (default value on each new connection of the display module to the
speed controller)
STR : operation to save the speed controller configuration in a file on the display module
REC : transfer of the content of a file to the speed controller
Ini : return of the speed controller to factory settings
A return to the factory settings cancels all your settings and your configuration.

Operating mode
Select STR, REC or InI and press "ENT".
1 If Operation = STR :
The file numbers are displayed. Select a file using ▲ or ▼ and confirm with "ENT".
2 If Operation = REC :
The file numbers are displayed. Select a file using ▲ or ▼ and confirm with "ENT".
- The display indicates :

CHG

WIRING OK?

ENT

Check that the wiring is compatible with the file configuration.
Cancel with "ESC" or confirm with "ENT"
- The display then requests a second confirmation using "ENT" or cancelation using "ESC".
3 If Operation = InI :
Confirm with "ENT"
- The display indicates :

CHG

WIRING OK?

ENT

Check that the wiring is compatible with the factory configuration.
Cancel with "ESC" or confirm with "ENT".
- The display then requests a second confirmation using "ENT" or cancelation using "ESC".
At the end of each operation the display returns to the "Operation" parameter, set to "NO"

105

ENGLISH

FOt

GP_ATV58_EN.fm Page 106 Mardi, 2. avril 2002 6:09 18

Files Menu

Files menu (continued)
Code

Description

COd

Password
Confidential code

The speed controller configuration can be protected by a password (COd).

ENGLISH

CAUTION : THIS PARAMETER SHOULD BE USED WITH CAUTION. IT MAY PREVENT ACCESS TO ALL
PARAMETERS. ANY MODIFICATION TO THE VALUE OF THIS PARAMETER MUST BE CAREFULLY
NOTED AND SAVED.
The code value is given by four figures, the last of which is used to define the level of accessibility required by
the user.

8888
This figure gives the access level
permitted, without having the correct code.
Access to the menus according to the position of the access locking switch on the rear of the display module
is always operational, within the limits authorized by the code.
The value Code 0000 (factory setting) does not restrict access.
The table below defines access to the menus according to the last figure in the code.
Last figure in the code
Menus

Access locked

Display

Adjust

0 exc. 0000 and 9

1

Modification
2

Level 2 :
Adjust, Macro-config, Drive, Control, I/O, Fault,
File (excluding code),
Communication (if card present)

0 exc. 0000 and 9

3

4

Application (if card present)

0 exc. 0000 and 9

5

6

Level 2 and Application (if card present)

0 exc. 0000 and 9

7

8

For access to the APPLICATION menu, refer to the application card documentation.
The code is modified using the ▲ and ▼ keys.
If an incorrect code is entered, it is refused and the following message is displayed :

COd

Password Fault

After pressing the ENT or ESC key on the keypad, the value displayed for the Code parameter changes to
0000 : the level of accessibility does not change. The operation should be repeated.
To access menus protected by the access code the user must first enter this code which can always be
accessed in the Files menu.

106

GP_ATV58_EN.fm Page 107 Mardi, 2. avril 2002 6:09 18

Communication and Application Menus / Assistance
During Operation / Maintenance
Communication menu
This menu is only displayed if a communication card is installed. It can be accessed when the switch is in
position
. Configuration is only possible in stop mode with the speed controller locked.
For use with a communication option card, refer to the document provided with this card.
For communication via the RS485 link on the basic product, refer to the document provided with the RS485
connection kit.

Application menu
This menu is only displayed if a “client application“ card is installed. It can be accessed when the switch is in
position
. Configuration is only possible in stop mode with the speed controller locked. Refer to the
document provided with the card.

ENGLISH

Assistance during operation
See the indicator lamps explained in the “Introduction”.

Maintenance
Before working on the speed controller, switch off the power supply and wait for the
capacitors to discharge (approximately 3 minutes) : the green LED on the front panel of the
speed controller is no longer illuminated.
CAUTION : the DC voltage at the + and - terminals or PA and PB terminals may reach 900 V depending
on the line voltage.
If a problem arises during setup or operation, ensure that the recommendations relating to the environment,
mounting and connections have been observed. Refer to the Altivar User's Manual.

Servicing
The Altivar 58 does not require any preventive maintenance. It is nevertheless advisable to perform the
following regularly :
- check the condition and tightness of connections
- ensure that the temperature around the unit remains at an acceptable level, and that ventilation is
effective (average service life of fans : 3 to 5 years depending on the operating conditions)
- remove any dust from the speed controller

Assistance with maintenance
The first fault detected is stored and displayed on the display module screen : the speed controller locks, the
red LED lights, and fault relay R1 trips.

Clearing the fault
Cut the power supply to the speed controller in the event of a non-resettable fault.
Locate the cause of the fault in order to eliminate it.
Reconnect the power supply : this clears the fault if it has disappeared.
In some cases, there may be an automatic restart once the fault has disappeared, if this function has been
programmed.

107

GP_ATV58_EN.fm Page 108 Mardi, 2. avril 2002 6:09 18

ENGLISH

Maintenance

Fault displayed

Probable cause

PHF
Mains Phase Loss

• speed controller incorrectly supplied or • check the power connection and the fuses
fuses blown
• reset
• transient fault on one phase
• configure the "In Phase Loss" (code
• use on a single phase supply of an
IPL) fault to "No", in the FAULT menu
ATV58•U72M2, U90M2 or a D12M2
(3-phase)

USF
Undervoltage

• line supply too low
• transient voltage dip
• damaged load resistor

• check the line voltage

OSF
Overvoltage

• line supply too high

• check the line voltage

OHF
Drive Overheat

• heatsink temperature too high
(tHd>118 %)

• monitor the motor load, the speed
controller ventilation and wait for it to
cool down before resetting

OLF
Mot Overload

• thermal trip due to prolonged overload
(tHr>118 %)

• check the thermal protection setting,
monitor the motor load
• a reset will be possible after approximately
7 minutes

ObF
Overbraking

• braking too sudden or driving load
• supply overvoltage during operation

• increase the deceleration time, add a
braking resistor if necessary
• check the possible supply overvoltage

OPF
Motor Phase Loss

• one phase cut at the speed controller
output

• Check the motor connections and the
operation of the output contactor (if fitted)
• If a motor starter is used in macro
configuration, check the configuration of
the relay R2 and the output contactor

LFF
Loss Follower

• loss of the 4-20mA setpoint on input AI2 • check the connection of the setpoint
circuits

OCF
Overcurrent

• ramp too short
• inertia or load too high
• mechanical locking

• check the settings
• check the size of the motor/speed
controller/load
• check the state of the mechanism

SCF
Short Circuit

• short-circuit or grounding at the speed
controller output

• check the connection cables with the
speed controller disconnected, and the
motor insulation. Check the speed
controller transistor bridge

CrF
Precharge Fault

• load relay control fault
• damaged load resistor

• check the connectors in the speed
controller and the load resistor

SLF
Serial Link Flt

• incorrect connection on the speed
controller terminal port

• check the connection on the speed
controller terminal port

OtF
Motor Overheat

• motor temperature too high (PTC
probes)

• check the motor ventilation and the ambient temperature, monitor the motor load
• check the type of probes used

tSF
PTC Therm Sensor

• incorrect connection of probes to the
speed controller

• check the connection of the probes to
the speed controller
• check the probes

108

Procedure, remedy

• change the load resistor

GP_ATV58_EN.fm Page 109 Mardi, 2. avril 2002 6:09 18

Maintenance

Probable cause

Procedure, remedy

EEF
EEprom Fault

• error saving in EEPROM

• cut the power supply to the speed
controller and reset

InF
Internal Fault

• internal fault
• connector fault

• check the connectors in the speed
controller

EPF
External Fault

• fault triggered by an external device

• check the device which has caused the
fault and reset

SPF
Sp. Feedbk. Loss

• no speed feedback

• check the connection and the
mechanical coupling of the speed
sensor

AnF
Load Veer. Flt

• non-following of ramp
speed inverse to the setpoint

• check the speed feedback setting and
wiring
• check the suitability of the settings for
the load
• check the size of the motor - speed
controller and the possible need for a
braking resistor

SOF
Overspeed

• instability
driving load too high

• check the settings and the parameters
add a braking resistor
• check the size of the motor/speed
controller/load

CnF
Network Fault

• communication fault on the fieldbus

• check the network connection to the
speed controller
• check the time-out

ILF
Int. Comm. Flt

• communication fault between the option • check the connection of the option card
card and the control card
to the control card

CFF

Error probably caused when changing
the card :
• change of rating of the power card
• change of the type of option card or
installation of an option card if there
was not one already and if the macroconfiguration is CUS
• option card removed
• inconsistent configuration saved

Rating Fault-ENT
Option Fault-ENT

Opt. Missing-ENT
CKS Fault - ENT

• check the hardware configuration of the
speed controller (power card, others)
• cut the power supply to the speed
controller then reset
• save the configuration in a file on the
display module
• press ENT to return to the factory
settings

The following message appears when
ENT is pressed :
Fact.Set? ENT/ESC

CFI
Config. Fault

• inconsistent configuration sent to speed • check the configuration sent previously
controller via serial link
• send a consistent configuration

109

ENGLISH

Fault displayed

GP_ATV58_EN.fm Page 110 Mardi, 2. avril 2002 6:09 18

Maintenance

Malfunction with no fault display
Display

Probable cause

Procedure, remedy

No code, LEDs not
illuminated

• No power supply

• Check power supply to speed controller

No code, green
• Display module defective
LED illuminated,
red LED illuminated
or not illuminated

ENGLISH

rdY
green LED
illuminated

110

• Change the display module

• Speed controller in line mode with
• Set parameter LI4 to forced local mode
communication card or RS485 kit
then use LI4 to confirm this forced
• An LI input is assigned to “Freewheel
mode.
stop” or “Fast stop”, and this input is not • Connect the input to 24 V to disable the
switched on.
stop.
These stops are controlled by loss of
the input.

GP_ATV58_EN.fm Page 111 Mardi, 2. avril 2002 6:09 18

Saving the Configuration and Settings

Speed controller reference ATV58 ............ Display rEF : ........................
Client identification number (if applicable) :
Option card : No y Yes y : reference ..........................................
Access code : No y Yes y : ........................................................
Configuration in file no. ............... on the display module
Macro-configuration : ..................................................................
For CUS : Customize configuration, assign the I/O as follows :
ALTIVAR
LI 1 :
LI 2 :
LI 3 :
LI 4 :
AI 1 :
AI 2 :

Logic inputs

Encoder input
Relay
Logic output
Analog output

AI 3 :

ENGLISH

Analog inputs

Option card
LI 5 :
LI 6 :

AI3 :
R2 :
LO :
AO :

AO1 :

Adjustment parameters :
Code
ACC
dEC
LSP
HSP
FLG
StA
ItH
IdC
tdC
SdC
AC2
dE2
JPF
JF2
JF3
tLS
USC
UFr
SLP
PFL
SP2
SP3
SP4
SP5
SP6

Factory setting
3s
3s
0 Hz
50 / 60 Hz
20 %
20 %
acc. to model
acc. to model
0.5 s
0.5 ItH
5s
5s
0 Hz
0 Hz
0 Hz
0
1
100 %
100 %
20 %
10 Hz
15 Hz
20 Hz
25 Hz
30 Hz

Client setting (1)
s
s
Hz
Hz
%
%
A
A
s
A
s
s
Hz
Hz
Hz
s
%
%
%
Hz
Hz
Hz
Hz
Hz

Code
SP7
JOG
JGt
brL
Ibr
brt
bEn
bEt
FFt
bIP
rPG
rIG
FbS
PIC
dtS
Ctd
ttd
tL2
PSP
PI2
PI3
dtd
Ftd
F2d

Factory setting
35 Hz
10 Hz
0,5 s
0 Hz
0A
0s
0 Hz
0s
50/60 Hz
no
1
1/s
1
no
1
1.36 In
100 %
200%
0s
30 %
60 %
105 %
50/60 Hz
50/60 Hz

Client setting (1)
Hz
Hz
s
Hz
A
s
Hz
s
Hz

/s

A
%
%
s
%
%
%
Hz
Hz

(1) leave blank when the parameter is missing
111

GP_ATV58_EN.fm Page 112 Mardi, 2. avril 2002 6:09 18

Saving the Configuration and Settings

ENGLISH

Drive menu parameters :
Code
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt

Factory setting
acc. to model
50 / 60 Hz
acc. to model
acc. to model
acc. to model
no
60 / 72 Hz
no
no
no
0 Hz
STN

Client setting (1)
V
Hz
A
rpm

Hz

Code
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

Factory setting
LIN
4
200%
1.36 In
yes
1
LF
acc. to model
yes
no
DET
1024

Client setting (1)
Hz

Code
AOH
Str
LCC
PSt
Add
tbr
rPr

Factory setting
20 mA
no
no
yes
0
19200
no

Client setting (1)
mA

Code
LFF
FLr
StP
Sdd
EPL

Factory setting
0 Hz
no
no
yes
yes

Client setting (1)
Hz

%
A

kHz

(1) leave blank when the parameter is missing

Control menu parameters :
Code
tCC
tCt
rIn
bSP
CrL
CrH
AOL

Factory setting
2W
LEL
no
no
4 mA
20 mA
0 mA

Client setting (1)

mA
mA
mA

(1) leave blank when the parameter is missing

Fault menu parameters :
Code
Atr
rSt
OPL
IPL
tHt
LFL

Factory setting
no
RSP
yes
yes
ACL
no

Client setting (1)

(1) leave blank when the parameter is missing

112

GP_ATV58_EN.fm Page 113 Mardi, 2. avril 2002 6:09 18

Summary of Menus

LANGUAGE menu
Label
English
Français
Deutsch
Español
Italiano

2 - ADJUST menu (continued)
Code
LnG
LnG
LnG
LnG
LnG

MACRO-CONFIG menu
Code
CFG
CFG
CFG

1 - DISPLAY menu
Label
Var. State
Freq. Ref.
Output Freq.
Motor Speed
MotorCurrent
Machine Spd.
Output Power
MainsVoltage
MotorThermal
DriveThermal
Last Fault
Freq. Ref.
Consumption
Run time

Code
--FrH
rFr
SPd
LCr
USP
OPr
ULn
tHr
tHd
LFt
LFr
APH
rtH

2 - ADJUST menu
Label
Freq. Ref.
Acceleration
Deceleration
Accelerate 2
Decelerate 2
Low Speed
High Speed
Gain
Stability

- Hz
- s
- s
- s
- s
- Hz
- Hz
- %
- %

Code
LFr
ACC
dEC
AC2
dE2
LSP
HSP
FLG
StA

Code
ItH
IdC
tdC
SdC
JPF
JF2
JF3
USC
tLS
UFr
SLP
SP2
SP3
SP4
SP5
SP6
SP7
Ctd
JOG
JGt
tL2
PFL
rPG
rIG
FbS
PIC
brL
Ibr
brt
bEn
bEt
FFt
bIP
dtS
Ftd
F2d
ttd
PSP
PI2
PI3
dtd

ENGLISH

Label
Hdg : Handling
GEn : General Use
VT : Var. Torque

Label
ThermCurrent - A
DC Inj.Curr. - A
DC Inj. Time - s
DC Stop Curr.- A
Jump Freq.
- Hz
Jump Freq.2
- Hz
Jump Freq.3
- Hz
Machine Coef.
LSP Time
- s
IR Compens.
- %
Slip Comp.
- %
Preset Sp.2
- Hz
Preset Sp.3
- Hz
Preset Sp.4
- Hz
Preset Sp.5
- Hz
Preset Sp.6
- Hz
Preset Sp.7
- Hz
Curr.Lev.Att - A
Jog Freq.
- Hz
JOG Delay
- s
Trq.Limit 2
- %
V/f Profile
- %
PI Prop. Gain
PI Int. Gain - /s
PI Coeff.
PI Inversion
BrReleaseLev - Hz
BrRelease I
- A
BrReleasTime - s
BrEngage Lev - Hz
BrEngageTime - s
Trip Thresh NST-Hz
Brake impul.
Tacho Coeff.
Freq.Lev.Att - Hz
Freq.Lev.2
- Hz
ThermLev.Att - %
PI Filter
- s
PI Preset 2 - %
PI Preset 3 - %
ATV Th. fault

113

GP_ATV58_EN.fm Page 114 Mardi, 2. avril 2002 6:09 18

Summary of Menus

ENGLISH

3 - DRIVE menu
Label
Nom.Mot.Volt
Nom.Mot.Freq
Nom.Mot.Curr
Nom.MotSpeed
Mot. Cos Phi
Auto Tuning
Max. Freq.
Energy Eco
I lim Adapt.
DecRampAdapt
SwitchRamp2
Type of stop
Ramp Type
DECRampCoeff
Trq.Limit
Int. I Lim
Auto DC Inj.
Motor P Coef
Sw Freq. Type
Sw Freq
Noise Reduct
Sp'l Motor
PG Type
Num. Pulses

5 - I/O menu

- V
- Hz
- A
-rpm

- Hz

- Hz

-

%
A

-kHz

Code
UnS
FrS
nCr
nSP
COS
tUn
tFr
nLd
Fdb
brA
Frt
Stt
rPt
dCF
tLI
CLI
AdC
PCC
SFt
SFr
nrd
SPC
PGt
PLS

4 - CONTROL menu
Label
TermStripCon
Type 2 Wire
RV Inhibit.
deadb./pedst
AI2 min Ref. AI2 Max Ref
Min Val. AO
Max Val. AO
Save Ref.
Keypad Comm.
Stop Priorit
DriveAddress
BdRate RS485
Reset counters

114

mA
mA
mA
mA

Code
tCC
tCt
rIn
bSP
CrL
CrH
AOL
AOH
Str
LCC
PSt
Add
tbr
rPr

Label
LI2 Assign.
LI3 Assign.
LI4 Assign.
LI5 Assign.
LI6 Assign.
NO :Not assigned
RV :Reverse
RP2:Switch ramp2
JOG:JOG
+SP: + Speed
-SP: - Speed
PS2: 2 preset SP
PS4: 4 preset SP
PS8: 8 preset SP
RFC:Auto/manu
NST:Freewhl Stop
DCI:DC inject.
FST:Fast stop
CHP:Multi. Motor
TL2:Trq.Limit 2
FLO:Forced Local
RST:Fault Reset
ATN:Auto-tune
PAU:PI Auto/Manu
PR2:PI 2 Preset
PR4:PI 4 Preset
TLA:Torque limit
EDD:Ext flt.
R2 Assign.
LO Assign.
NO:Not assigned
RUN:DriveRunning
OCC:OutputCont.
FTA:Freq Attain.
FLA:HSP Attained
CTA:I Attained
SRA:FRH Attained
TSA:MtrTherm Lvl
BLC:Brk Logic
APL:4-20 mA loss
F2A:F2 Attained
TAD:Alarm.th.var.

Code
L12
L13
L14
L15
L16

r2
LO

GP_ATV58_EN.fm Page 115 Mardi, 2. avril 2002 6:09 18

Summary of Menus

5 - I/O menu (continued)
Code
AI2
AI3

AI3

6 - FAULT menu
Label
Auto Restart
Reset Type
OutPhaseLoss
InPhaseLoss
ThermProType
LossFollower
Flt. Speed 4-20
Catch On Fly
Cont. Stop
RampNotFoll
External fault

Code
Atr
rSt
OPL
IPL
tHt
LFL
LFF
FLr
StP
Sdd
EPL

ENGLISH

Label
AI2 Assign.
AI3 Assign.
NO:Not assigned
FR2:Speed Ref2
SAI:Summed Ref.
PIF:PI regulator
PIM:PI Man.ref.
SFB:Tacho feedbk
PTC:Therm.Sensor
ATL:Torque limit
AI3Assign(encoder)
NO:Not assigned
SAI:Summed ref.
RGI:PG feedbk
AO Assign.
NO:Not assigned
OCR:Motor Curr.
OFR:Motor Freq.
ORP:Ramp Output
TRQ:Motor torque
STQ:Signed torque
ORS:Signed ramp
OPS:PI ref.
OPF:PI Feedback
OPE:PI Error
OPI:PI Integral
OPR:Motor power
tHR:Motor Thermal
tHD:Drive Thermal

7 - FILES menu
AO

Label
File 1 State
File 2 State
File 3 State
File 4 State
Operat.Type
Conf. Code

Code
FI5
F25
F35
F45
FOt
COd

8 - COMMUNICATION menu
Refer to the documentation provided
with the communication card.

8 - APPLICATION menu
Refer to the documentation provided
with the application card.

115

GP_ATV58_EN.fm Page 116 Mardi, 2. avril 2002 6:09 18

ENGLISH

Index

Function

Menus

Pages

+ / - speed

I/O

88-91-94

2/3-wire control

CONTROL

85-93

Acceleration

ADJUST - DRIVE

74-82-

Analog input AI2

CONTROL

86

Auto catching (flying restart)

FAULT

104

Auto tuning

DRIVE - I/O

81-88-96

Automatic ramp adaptation

DRIVE

82

Automatic restart

FAULT

103

Brake sequence

ADJUST - I/O

78-89-90-99

Confidential code

FILES

106

Configurable inputs

I/O

88-89-90

Configurable outputs

CONTROL - I/O

87-89-90-99-100-101

Controlled stop

I/O - FAULT

88-104

Current limit

DRIVE

82-83

Deceleration

ADJUST - DRIVE

74-82

Downstream contactor

I/O

89-99

Energy saving

DRIVE

81

Factory setting / Save

FILE

105

Fault reset

I/O - FAULT

88-91-96-103

Forced local mode

CONTROL - I/O

88-96

Injection braking

ADJUST - DRIVE

74-77-78-83

Low speed limit time

ADJUST

75-

Motor switching

DRIVE - I/O

83-88-96

Motor thermal protection

ADJUST - I/O - FAULT

74-80-89-90-104

PI regulator

ADJUST - I/O

79-89-90-97

Preset speeds

ADJUST - I/O

76-78-88-90-95

PTC probes

I/O

89-97

Ramp switching

ADJUST - DRIVE - I/O

74-82-88-90-93

Reference switching

I/O

88-95

Save reference

CONTROL

87

Serial link address

CONTROL

87

Skip frequency

ADJUST

75-

Speed loop with encoder

DRIVE - I/O

84-89-90-98

Speed loop with tacho

ADJUST - I/O

79-89-90-97

Standard torque / high torque

DRIVE IDENTIFICATION (rEF)

71-

Step by step (JOG)

ADJUST - I/O

77-78-88-90-93

Stop priority

CONTROL

87

Switching frequency

DRIVE

83

Torque limits

ADJUST - DRIVE - I/O

77-79-83-88-90-96

116

GP_ATV58_EN.fm Page 117 Mardi, 2. avril 2002 6:09 18

ENGLISH
117

GP_ATV58_Page2-DE.fm Page 118 Mardi, 2. avril 2002 6:18 18

Achtung
Dieses Dokument beinhaltet die Programmier-anleitung
für das Altivar 58-Basisgerät bei Verwendung ausschließlich folgender Module:
- dem Bedienterminal VW3A58101,
- eventuell einer Optionskarte E/A Erweiterung
VW3A58201 oder VW3A58202.

DEUTSCH

Die Verwendung anderer Optionsmodule kann zu Änderungen in den Menüs führen. Entsprechende Angaben
hierzu sind in der jeweiligen Moduldokumentation enthalten.
Seit seiner Markteinführung wurde der Altivar 58 mit
zusätzlichen Funktionen ausgestattet, die in dieser Programmieranleitung Berücksichtigung finden. Dieses
Handbuch kann auch mit den ersten Geräten eingesetzt
werden, dabei ist es jedoch normal, daß auch Parameter
beschrieben werden, die es bei diesen Geräten noch
nicht gibt.
Alle Beschreibungen dieses Handbuches beziehen sich
auf Bedienterminals der Version V2.1, die mit Steuerkarten der Version V2.4 eingesetzt werden. Bei Verwendung
eines älteren Terminals und/oder einer älteren Steuerkarte können die Menüs einen anderen Inhalt haben.

118

Inhalt

Allgemeines ___________________________________________________________________ 120
Praktische Hinweise / Schnellinbetriebnahme _________________________________________ 123
Freigabe der Menüs vor der Programmierung _________________________________________ 124
Zugriff auf die Menüs ____________________________________________________________ 125
Zugriff auf die Menüs - Prinzip der Programmierung ____________________________________ 126
Makrokonfigurationen ____________________________________________________________ 127
Identifizierung Umrichter _________________________________________________________ 129
Menü Betrieb __________________________________________________________________ 130
Menü "Einstellung" ______________________________________________________________ 132
Menü "Antrieb" _________________________________________________________________ 139
Menü "Steuerung" ______________________________________________________________ 143
Menü "Belegung der Eingänge/Ausgänge" ___________________________________________ 146
Funktionen der konfigurierbaren Ein-/Ausgänge _______________________________________ 150
Menü "Fehlerbehandlung" ________________________________________________________ 161
Menü "Konf-Datei" ______________________________________________________________ 163
Menüs "Kommunikation" und "Applikation" / Bedienungsunterstützung / Wartung _____________ 165
Wartung ______________________________________________________________________ 166
Merkblatt Konfiguration und Einstellungen ____________________________________________ 169
Zusammenfassung der Menüs _____________________________________________________ 171
Stichwortverzeichnis ____________________________________________________________ 174

DEUTSCH
119

GP_ATV58_DE.fm Page 120 Mardi, 2. avril 2002 6:01 18

Allgemeines

Das Bedienterminal VW3A58101 wird mit den Umrichtern ATV58••••M2 und ATV58••••N4 geliefert.
Die Umrichter ATV58••••••Z werden ohne dieses Terminal ausgeliefert. Es kann jedoch getrennt bestellt
werden.

Montage des Terminals auf dem Umrichter:
Um das Bedienterminal auf einem Umrichter des Typs ATV58••••••Z zu montieren, muß zunächst die
Schutzklappe abgenommen werden.

POWE
R
FAUL z
T

POWE
R
FAUL z
T

ESC

DEUTSCH

FWD
REV

ENT
RUN

STOP
RESET

Das Bedienterminal kann unter Spannung angeschlossen und wieder abgenommen werden. Wenn das
Terminal abgenommen wird, während der Umrichter über das Terminal angesteuert wird, verriegelt sich der
Umrichter mit der Störung SLF.

Fernbedienbausatz:
Den Montagesatz (Typ VW3A58103), bestehend aus 1 Kabel mit Steckverbindern, den für die Montage auf
einer Schaltschranktür notwendigen Teilen und Montageanleitung verwenden.

Signalisierung auf der Vorderseite des Altivar
Weitere LEDs, Zustandsanzeigen bei Verwendung von Optionskarten für die
Kommunikation.

POWER z

grüne LED POWER

leuchtet: Altivar 58 unter Spannung

FAULT

rote LED FAULT

• leuchtet: Altivar 58 in Störung
• blinkt: Altivar 58 verriegelt nach Betätigung der
Taste "STOP" des Terminals oder in Folge einer
Konfigurationsänderung. Der Motor kann in diesem
Fall erst nach einer Unterbrechung der Befehle
"Rechtslauf", "Linkslauf", "Anhalten über
Gleichstrom-bremsung" gestartet werden.

120

GP_ATV58_DE.fm Page 121 Mardi, 2. avril 2002 6:01 18

Allgemeines
☞ Vor dem Einschalten des Altivar und vor Verwendung des Terminals:
Die Abdeckklappe des Altivar 58 entriegeln und öffnen, so daß
ein Zugriff auf den Schalter 50/60 Hz 1 der Steuerkarte
möglich ist. Wenn eine Optionskarte eingebaut ist, bleibt der
Schalter weiterhin zugänglich.
Den Schalter in der Position 50 oder 60 Hz je nach
Motorfrequenz positio-nieren.

1

Voreingestellter Betriebspunkt:

od.
50 Hz 60 Hz

Position 50 Hz (Werkseinstellung):
- 230 V 50 Hz bei ATV 58••••M2
- 400 V 50 Hz bei ATV 58••••N4
Position 60 Hz:
- 230 V 60 Hz bei ATV 58••••M2
- 460 V 60 Hz bei ATV 58••••N4

Das Bedienterminal bietet folgende Möglichkeiten:
DEUTSCH

- Anzeige der Identifizierung des Umrichters, von elektrischen Größen, Bedienparametern oder
Störungen,
- Änderung der Parametrierung und der Konfiguration des Altivar,
- lokale Steuerung über die Tastatur,
- Speicherung und das Aufrufen von Konfigurationsdateien im bzw. aus dem EEPROM-Speicher des
Terminals.

☞ Rückkehr zu den Werkseinstellungen:
- den Umrichter ausschalten,
- die Abdeckklappe des Altivar entriegeln und öffnen, so dass ein Zugriff auf den Schalter 50/60 Hz 1 der
Steuerkarte möglich ist. Wenn eine Optionskarte vorhanden ist, bleibt der Schalter über diese Karte
zugänglich,
- die Stellung des Schalters 50/60 Hz 1 der Steuerkarte ändern,
- den Umrichter einschalten,
- den Umrichter ausschalten,
- den Schalter 50/60 Hz 1 der Steuerkarte wieder in seine Ausgangsstellung bringen (Nennfrequenz des
Motors), den Umrichter einschalten, dieser befindet sich wieder in seiner Werkskonfiguration.

121

GP_ATV58_DE.fm Page 122 Mardi, 2. avril 2002 6:01 18

Allgemeines

Ansicht Vorderseite

LOC

PROG

ESC
ENT
FWD
REV

STOP
RESET

RUN

Verwendung der Tasten und Bedeutung der Anzeigen
 Ú
blinkende Anzeige:
gibt die gewählte Drehrichtung an
feste Anzeige:
gibt die Drehrichtung des Motors an
LOC
Ansteuerung über das Terminal
PROG Erscheint im Modus Inbetriebnahme und
Programmierung
blinkende Anzeige: gibt eine Veränderung eines
nicht gespeicherten Wertes an
4-stellige Anzeige:
Anzeige der numerischen Werte und der Codes
Eine Zeile mit 16 Zeichen:
Anzeige der Meldungen im Klartext

DEUTSCH

Bewegung innerhalb der Menüs oder Parameter und Einstellung eines Wertes.
ESC

Zurück zum vorhergehenden Menü oder Verlassen einer noch nicht abgeschlossenen
Einstellung und Rückkehr zum Ausgangswert.

ENT

Auswahl eines Menüs, Speichern einer Auswahl oder einer Einstellung.

Bei Auswahl der Steuerung über das Terminal:
FWD
REV

RUN
STOP
RESET

Drehrichtungsumkehr.
Fahrbefehl.
Anhaltebefehl für den Motor oder Rücksetzen der Störung. Die Funktion "STOP" der Taste
kann über Programmierung gesperrt werden (Menü "Steuerung").

Ansicht Rückseite

Stecker:
- für den direkten Anschluß des Terminals am Umrichter
- bei räumlich getrennter Montage kann das Terminal über ein mit
dem Fernbedienbausatz VW3A58103 geliefertes Kabel
angeschlossen werden.
Programmierschalter:

122

- position

: Kein Zugriff auf Parametrierung und Konfiguration

- position

: Zugriff auf Parametrierung

- position

: Zugriff auf Parametrierung und Konfiguration

GP_ATV58_DE.fm Page 123 Mardi, 2. avril 2002 6:01 18

Praktische Hinweise / Schnellinbetriebnahme

Praktische Hinweise:
Bereiten Sie zunächst Ihre Programmierung vor, indem Sie die Blätter für die Aufzeichnung von Konfiguration
und Parametrierung (am Ende dieses Dokumentes) ausfüllen.
Die Programmierung des Altivar 58 wird durch Verzweigungen und interne Sperren erleichtert. Um diese
Vorteile voll ausnutzen zu können, empfehlen wir Ihnen, auf die Menüs in folgender Reihenfolge zuzugreifen.
Nicht alle angegebenen Schritte sind in jedem Fall obligatorisch.
↓ Sprache
Makrokonfiguration
Identifikation
Steuerung (nur bei 3-Draht-Steuerung)
Belegung E/A
Steuerung
Antrieb
Fehlerbehandlung
↓ Kommunikation oder Applikation (wenn eine entsprechende Karte eingesetzt wird)
Einstellung
HINWEIS : Es muß überprüft werden, daß die programmierten Funktionen mit der jeweiligen
Verdrahtung vereinbar sind. Insbesondere ist diese Überprüfung bei der Ausführung ATV 58E•••••
nach einer Veränderung der Konfiguration erforderlich. In diesem Fall muß auch gegebenenfalls die
Verdrahtung geändert werden.

Dieses Verfahren kann in folgenden Fällen verwendet werden:
- bei einfachen Anwendungen, bei denen die Werkseinstellungen des Umrichters geeignet sind,
- während der Montage des Umrichters, falls es erforderlich ist, den Motor provisorisch drehen zu lassen,
bevor die vollständige Inbetriebnahme ausgeführt wird.

Vorgehensweise:
1 Die Empfehlungen der mit dem Umrichter gelieferten Bedienungsanleitung beachten. Insbesondere gilt dies
für die Einstellung des Schalters 50/60 Hz auf die Motomennfrequenz.
2 Überprüfen, ob die werkseitig eingestellte Makrokonfiguration "Hdg: Fördertech." geeignet ist. Sollte dies
nicht der Fall sein, kann sie im Menü "Makrokonfig." geändert werden.
3 Bei folgenden Umrichtern muß ggf. im Menü "Identifikation" die maximal zulässige Überlast konfiguriert
werden:
- Leistungen ab 11 kW bei Umrichtern für 208-230 V-Netze
- Leistungen ab 18,5 kW bei Umrichtern für 380-500 V-Netze
4 Überprüfen, ob die Verdrahtung mit der Makrokonfiguration vereinbar ist, so daß die erforderliche
Sicherheit gewährleistet ist. Im entgegengesetzten Fall die Verdrahtung verändern.
5 Im Menü "Antrieb" überprüfen, ob die werkseitig eingestellten Parameter mit den auf dem Leistungsschild
des Motors gestempelten Werten vereinbar sind. Ist dies nicht der Fall, müssen die Parameter verändert
werden.
6 Unbedingt im Menü "Antrieb" eine Motormessung durchführen.
7 Gegebenenfalls die Parameter des Menüs "Einstellung" (Rampen, I Thermisch, usw.) einstellen.

123

DEUTSCH

Schnellinbetriebnahme:

GP_ATV58_DE.fm Page 124 Mardi, 2. avril 2002 6:01 18

Freigabe der Menüs vor der Programmierung

Zugriffsniveau / Verriegelung
Die Position des Programmierschalters bietet in Abhängigkeit von der Betriebsphase Ihrer Maschine drei
Zugriffsniveaus auf die Menüs. Der Zugriff auf die Menüs kann auch über einen Zugriffscode gesperrt werden
(siehe Menü Konf-Datei).
Position
-

(Niveau 0, Anzeige): während des Betriebs verwenden.

Menü Sprache: Auswahl der Dialogsprache.
Menü Makrokonfig.: Anzeige der Makrokonfiguration.
Menü Identifikation: Anzeige der Statusmeldungen des Umrichters.
Menü Betrieb: Anzeige von elektrischen Größen und Störungen

Position

(Niveau 1, Anzeige und Parametrierung): Während der Inbetriebnahme verwenden.

- Ausführung aller in Niveau 0 möglichen Aktionen.
- Menü Einstellung: Einstellung aller bei drehendem Motor verfügbaren Parameter.

DEUTSCH

Position

(Niveau 2, Allgemeiner Zugriff): Während der Programmierung verwenden.

- Ausführung aller in Niveau 0 und 1 möglichen Aktionen.
- Menü Makrokonfig.: Änderung der Makrokonfiguration.
- Menü Identifikation: Einstellung der Dauerleistung des Umrichters in Abhängigkeit der zulässigen
Überlast.
- Menü Antrieb: Anpassung der Dynamik und des Regelverhaltens von Motor und Umrichter.
- Menü Steuerung: Konfiguration der Steuerung des Umrichters (über Klemmenleisten, Terminal und die
integrierte serielle Schnittstelle).
- Menü Belegung E/A: Änderung der Belegung der Eingänge/Ausgänge.
- Menü Fehlerbehandlung: Konfiguration der Schutzvorrichtungen für Motor und Umrichter sowie des
Verhaltens im Störungsfall.
- Menü Konf-Datei: Rückkehr zu Werkseinstellungen, Speicherung von Konfigurationen im EEPROM des
Bedienterminals, Laden von Konfigurationen aus dem EEPROM, Eingabe eines Codes zur Verriegelung
der Konfigurationsfunktionen.
- Menü Kommunikation (nur bei Installation einer Kommunikationskarte): Einstellung der Parameter des
jeweiligen Kommunikationsprotokolls.
- Menü Applikation (nur bei Installation einer Karte "Applikation Kunde"): Weitere Informationen in der
spezifischen Dokumentation dieser Karte.

124

GP_ATV58_DE.fm Page 125 Mardi, 2. avril 2002 6:01 18

Zugriff auf die Menüs

Die Anzahl der erreichbaren Menüs hängt von der Stellung des Programmierschalters auf der Rückseite des
Terminals ab.
Jedes Menü besteht aus einzelnen Parametern.
Folgende
Inbetriebnahmen

Erste
Inbetriebnahme

LANGUE

LnG

ESC

CFG

MACRO-KONFIG

rEF

Identifizierung

0.37 kW 200/240 V

SUP

1-BETRIEB

DEUTSCH

SEt

2-EINSTELLUNG

drC

3-ANTRIEB

CtL

4-STEUERUNG

Die Anzeige PROG
erscheint auf
dem Terminal

I-O

5-BELEGUNG E/A

FLt

6-FEHLERBEH.

FLS

7-KONF-DATEI

Zugriff nur möglich, wenn die
Karte "Applikation Kunde"
installiert ist

APP

8-APPLIKATION

SL

8-KOMMUNIKATION

Zugriff nur möglich,
wenn die Karte
"Protokoll" installiert ist

ACHTUNG: Wenn zuvor ein Zugriffscode programmiert wurde, können bestimmte Menüs nicht veränderbar
oder sogar unsichtbar sein. Im Kapitel “Menü Konfigurationsdatei” finden Sie Informationen zur Eingabe des
Zugriffscodes.
125

GP_ATV58_DE.fm Page 126 Mardi, 2. avril 2002 6:01 18

Zugriff auf die Menüs - Prinzip der Programmierung

Sprache:
Dieses Menü ist unabhängig von der Stellung des Schalters erreichbar. Eine Veränderung ist sowohl im
Stillstand als auch während des Betriebs möglich.
Beispiel:
ENT

LANGUE

LnG

LnG

English

LnG

Deutsch

Zurück zur bisher
gespeicherten Auswahl

Speichern der
neuen Auswahl

ESC

ENT

ESC

LnG

DEUTSCH

Deutsch

LnG

English

Mögliche Dialogsprachen: Englisch (Werkseinstellung), Französisch, Deutsch, Spanisch, Italienisch.

Prinzip der Programmierung:
Das Programmierprinzip ist immer identisch:
• Niveau 1: siehe oben Beispiel “Sprache“.
• Niveau 2: siehe unten Beispiel “Hochlauframpe“.
ENT

SEt

ENT

ACC

Hochlaufzeit

2.EINSTELLUNG

3.0

s

Hochlaufzeit

s

Erhöhen

ESC

(oder Verringern)

3.1

Hochlaufzeit

ESC

Speichern des
neuen Wertes

Zurück zum
bisherigen Wert

ENT

ESC

3.1

Hochlaufzeit

126

s

s

3.0

Hochlaufzeit

s

GP_ATV58_DE.fm Page 127 Mardi, 2. avril 2002 6:01 18

Makrokonfigurationen

Die Makrokonfiguration kann immer angezeigt werden. Eine Veränderung ist jedoch nur im
Programmiermodus (Niveau 2, Programmierschalter in Position
) im Stillstand bei verriegeltem Umrichter
möglich.
Die Makrokonfiguration ermöglicht eine automatische Voreinstellung für ein bestimmtes Anwendungsgebiet.
Drei Anwendungsgebiete stehen zur Wahl.
- Fördertechnik (Hdg), (Werkseinstellung)
- Variables Drehmoment bei Pumpen- und Lüfteranwendungen (VT)
- Allgemeine Anwendung (GEn)
Eine Makrokonfiguration ordnet automatisch die Eingänge/Ausgänge und die Parameter zu und aktiviert dabei
die für die Anwendung erforderlichen Funktionen. Die mit den programmierten Funktionen verknüpften
Parameter sind zugänglich.
Umrichter:
Belegungen der Eingänge / Ausgänge in Abhängigkeit der Makrokonfiguration

Hdg : Fördertech.

GEn : Allg. Anw.

VT : Var. Moment

Rechtslauf

Rechtslauf

Rechtslauf

Logikeingang LI2

Linkslauf

Linkslauf

Linkslauf

Logikeingang LI3

2 Vorwahlfrequenzen

Schrittbetrieb (Jog)

Umschalten Sollwert

Logikeingang LI4

4 Vorwahlfrequenzen

Freier Auslauf (1)

Gleichstrombremsung

Analogeingang AI1

Frequenzsollwert

Frequenzsollwert

Frequenzsollwert 1

Analogeingang AI2

Frequenzsollw. (Sum.)

Frequenzsollw. (Sum.)

Frequenzsollwert 2

Relais R1

Störung

Störung

Störung

Relais R2

Steuerung Motorschütz

Therm. Zust. Mot. err.

Sollfrequenz erreicht

Analogausgang AO1

Motorfrequenz

Motorfrequenz

Motorfrequenz

DEUTSCH

Logikeingang LI1

Bei vorhandener Optionskarte E/A-Erweiterung:
Belegungen der Eingänge / Ausgänge in Abhängigkeit der Makrokonfiguration

Hdg : Fördertech.

GEn : Allg. Anw.

VT : Var. Moment

Logikeingang LI5

8 Vorwahlfrequenzen

Löschen Störung

Freier Auslauf (1)

Logikeingang LI6

Löschen Störung

Momentbegrenzung

Umschalten Rampe

Analogeingang. AI3
oder
Eingänge A, A+, B, B+

Summensollwert

Summensollwert

Istwert PI-Regler (2)

Drehzahlrückführung (2)

Drehzahlrückführung (2)

Drehzahlrückführung (2)

Logikausgang LO

Stromschwellwert err.

Strg Motorschütz

große Drehzahl erreicht

Analogausgang AO

Motorstrom

Motorstrom

Motorstrom

(1) Für den Anlauf muß der Logikeingang an + 24 V (aktive Funktion auf 0) angeschlossen sein.
(2) Belegung des Eingangs aufheben, wenn der PI-Istwert bzw. die Drehzahlrückführung nicht
verkabelt ist.
HINWEIS: Es muß überprüft werden, daß die programmierten Funktionen mit der jeweiligen
Verdrahtung vereinbar sind. Insbesondere ist diese Überprüfung bei der Ausführung ATV 58E•••••
nach einer Veränderung der Konfiguration erforderlich. In diesem Fall muß auch gegebenenfalls die
Verdrahtung geändert werden.

127

GP_ATV58_DE.fm Page 128 Mardi, 2. avril 2002 6:01 18

Makrokonfigurationen

Bei einer Veränderung der Makrokonfiguration ist eine doppelte Bestätigung erforderlich, da sie die
automatische Zuordnung von Funktionen und eine Rückkehr zu den Werkseinstellungen nach sich
zieht.
Anzeige des folgenden Textes auf dem Display:

CHG

VERDRAHTUNG OK?

ENT, um die Änderung zu bestätigen
ESC, um zur bisherigen Konfiguration zurückzukehren

ENT

Anpassung der Konfiguration:
Die Konfiguration kann durch Ändern der Zuordnung der Eingänge/Ausgänge im Menü "Belegung E/A"
angepaßt werden (Niveau 2, Programmierschalter in Position

).

Diese Anpassung ändert den Code der angezeigten Makrokonfiguration:
Anzeige von

CFG

DEUTSCH

CUS:Sonder

128

GP_ATV58_DE.fm Page 129 Mardi, 2. avril 2002 6:01 18

Identifizierung Umrichter

Identifizierung Umrichter
Diese Anzeige ist jederzeit zugänglich. Sie gibt die auf das Typenschild gestempelte Leistung und Spannung
des Umrichters an.

rEF

Die Anzeige der Leistung erfolgt in kW, wenn der Schalter 50/60 Hz des
Umrichters auf 50 Hz steht und in HP, wenn er auf 60 Hz steht.

0.37 kW 200/240 V

Einstellung der Dauerleistung:
Nur bei folgenden Umrichtern möglich:
- Leistung ab 11 kW bei Umrichtern für 208-230 V-Netz.
- Leistung ab 18,5 kW bei Umrichtern für 380-500 V-Netz.
Die Dauerleistung ist je nach der Applikation bei normaler bzw. hoher Überlast unterschiedlich. Die Umrichter
werden mit der Werkseinstellung "hohe Überlast" ausgeliefert. Die Konfiguration "normale Überlast" wird wie
folgt eingestellt:

ENT

22 kW

rEF

rEF blinkt
22 kW

380/500 V

rEF blinkt

rEF
380/500 V

+30 kW

rEF
380/500 V

DEUTSCH

oder ESC

ESC

ENT

+30 kW

rEF
380/500 V

+30 kW

rEF
380/500 V

ESC

Bei einer Applikation mit "normaler Überlast" steht das Vorzeichen "+" vor der Leistungsangabe.
Die Rückkehr zur Konfiguration "starkes Drehmoment" erfolgt nach demselben Verfahren.
Die Konfiguration "normale bzw. hohe Überlast" stellt eine Vorkonfiguration der Werkseinstellung bestimmter
Parameter dar:
• Menü "Antrieb": UnS, nCr, nSP, COS, tUn
• Menü "Einstellung": ItH, IdC.
Das Umschalten zwischen diesen beiden Drehmoment-Konfigurationen führt also bei diesen
Parametern zu einer Rückkehr zu den Werkseinstellungen.

129

GP_ATV58_DE.fm Page 130 Mardi, 2. avril 2002 6:01 18

Menü Betrieb

Menü Betrieb (Auswahl des während des Betriebs angezeigten Parameters)
Auf folgende Parameter ist unabhängig von der Position des Programmierschalters sowohl im Stillstand, als
auch während des Betriebs ein Zugriff möglich.

Einheit

Code

Funktion

--rdY
rUn
ACC
dEC
CLI
dCb
nSt
Obr

Zustand Umr
–
Zustand des Umrichters: Gibt eine Störung oder die Betriebsphase des Motors an.
rdY = Umrichter betriebsbereit,
rUn = In Betrieb,
ACC = Hochlauf,
dEC = Auslauf,
CLI = Strombegrenzung,
dCb = Gleichstrombremsung,
nSt = Anhalten im Freilauf,
Obr = Bremsung unter Anpassung der Auslauframpe (Siehe Menü “Antrieb“).

FrH

Sollfrequenz

Hz

Sollfrequenz

rFr

Motorfrequ.

Hz

Am Motor anliegende Frequenz

DEUTSCH

SPd

Motor-Drehz

1/min

Vom Umrichter geschätzte Motordrehzahl

LCr

Motorstrom

USP

Geschw Masch

A

Motorstrom
–

Vom Umrichter geschätzte Geschwindigkeit der Maschine. Sie ist proportional zu rFr, entsprechend
dem im Menü "Einstellung regelbaren Faktor USC. Dadurch kann ein der Anwendung
entsprechender Wert angezeigt werden (z. B. Meter/Sekunde).
Achtung, wenn USP über 9999 liegt, wird die Anzeige durch 1000 geteilt.

OPr

Motorleistg

%

Vom Umrichter geschätzte Wellenleistung des Motors.
100 % entspricht der Nennleistung.

ULn

Netzspannung

V

Netzspannung

tHr

Motorerwärmg

%

Thermischer Zustand: 100% entspricht dem Nennwert der Motorerwärmung. Über 118% löst der
Umrichter die Störung OLF (Motorüberlast) aus

tHd

Erwärmg Umr

%

Thermischer Zustand des Umrichters: 100% entspricht der Nennerwärmung des Umrichters. Über
118% löst der Umrichter die Störung OHF (Überhitzung Umrichter) aus. Wenn der Wert unter 70 %
absinkt, kann er wieder eingeschaltet werden.

LFt

Fehlersp.
Zeigt die letzte aufgetretene Störung an.

130

–

GP_ATV58_DE.fm Page 131 Mardi, 2. avril 2002 6:01 18

Menü Betrieb

Code

Funktion

Einheit

LFr

Sollfrequenz

Hz

Dieser Einstellparameter erscheint an Stelle des Parameters FrH, wenn die Steuerung des
Umrichters über die Konsole aktiviert ist: Parameter LCC in Menü "Steuerung".

APH

Energieaufn.

kWh oder MWh

Aufgenommene Energie.

rtH

Betriebszeit

h

Kontinuierliche Betriebszeit (Motor unter Spannung) in Stunden.

DEUTSCH
131

GP_ATV58_DE.fm Page 132 Mardi, 2. avril 2002 6:01 18

Menü "Einstellung"

Dieses Menü ist in den Positionen
und
des Programmierschalters (Niveau 1 und 2)
zugänglich. Die Veränderung der Einstellparameter ist sowohl im Stillstand, als auch während des
Betriebs möglich. Überprüfen, daß die während des Betriebs vorgenommenen Änderungen gefahrlos
sind. Änderungen sollten vorzugsweise im Stillstand erfolgen.
Die Liste der Einstellparameter besteht aus einem festen Teil und einem variablen Teil, der sich ändert in
Abhängigkeit von:
- der gewählten Makrokonfiguration
- dem Vorhandensein einer Erweiterungskarte Eingänge/Ausgänge
- der Neuzuordnung von Eingängen/Ausgängen
Auf folgende Parameter kann in allen Makrokonfigurationen zugegriffen werden.
Code

Beschreibung

Einstell-bereich

Werks-einstellung

LFr

Sollfrequenz- Hz

LSP bis HSP

–

Erscheint, wenn die Steuerung des Umrichters über das Terminal aktiviert ist: Parameter LCC in
Menü Steuerung

ACC
dEC

Hochlaufzeit - s
Auslaufzeit - s

0,05 bis 999,9
0,05 bis 999,9

3s
3s

Zeit der Hochlauf- und Auslauframpen. Definiert für einen Bereich von 0 bis zur Nennfrequenz des
Motors (FrS)

DEUTSCH

AC2
dE2

Hochlaufz. 2Auslaufz. 2 -

s
s

0,05 bis 999,9
0,05 bis 999,9

5s
5s

2. Hochlauframpe
2. Auslauframpe
Ein Zugriff auf diese Parameter ist möglich, wenn der Schaltschwellwert der Rampe (Parameter Frt)
ungleich 0 Hz ist oder wenn ein Logikeingang dem Umschalten der Rampe zugeordnet ist.

LSP

Kleine Freq.- Hz

0 bis HSP

0 Hz

LSP bis tFr

50 / 60 Hz in Abhängigkeit des
Schalters

Kleine Frequenz

HSP

Große Freq. - Hz

Große Frequenz: Überprüfen, daß die Einstellung mit Motor und Anwendung vereinbar ist.

FLG

Verstärkung -

%

0 bis 100

20

Verstärkung des Frequenzreglers: ermöglicht die Anpassung der Geschwindigkeit von
Sollwertsprüngen. Bei Maschinen mit starkem Gegenmoment oder großem
Massenträgheitsmoment mit schnellen Zyklen die Verstärkung schrittweise erhöhen.

StA

Dämpfung

-

%

0 bis 100

20

Ermöglicht die Verringerung von Überschwingern nach Sollwertsprüngen.
Die Dämpfung schrittweise erhöhen, um Überschwinger zu unterdrücken.

ItH

I Thermisch -

A

0,25 bis 1,36 In (1)

je nach Umrichter

Strom für den thermischen Schutz des Motors. ItH auf den vom Typenschild abgelesenen
Bemessungsbetriebsstrom einstellen.
(1) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit starkem Drehmoment.

132

GP_ATV58_DE.fm Page 133 Mardi, 2. avril 2002 6:01 18

Menü "Einstellung"

Code

Beschreibung

Einstell-bereich

Werks-einstellung

tdC

T DC-Bremsung- s

0 bis 30s Cont

0,5 s

Bremsdauer bei Gleichstrombremsung. Wird der Wert über 30 s erhöht, erscheint die Anzeige
"Cont", (permanente Einspeisung, solange Fahrbefehl aktiv).
Der Strom wird automatisch eingestellt, nach 30 s wird SdC verwendet.

SdC

I DC-Bremsg -

A

0,1 bis 1,36 In (1)

je nach Umrichter

Stärke des Bremsstroms nach einer Bremsdauer von über 30 Sekunden (tdC = Cont.).
Überprüfen, daß der Motor diesem Strom ohne Überhitzen standhält

JPF

F-Ausblendg - Hz

0 bis HSP

0 Hz

Frequenzausblendung: läßt den stationären Betrieb in einem Frequenzbereich von +/-2,5 Hz um
JPF nicht zu. Mit dieser Funktion kann eine kritische Frequenz unterdrückt werden, die eine
Resonanz auslösen könnte.

JF2

F-Ausblendg2- Hz

0 bis HSP

0 Hz

2. Frequenzausblendung: Funktion identisch zu JPF, für einen 2. Frequenzwert.

JF3

F-Ausblendg3- Hz

0 bis HSP

0 Hz

3. Frequenzausblendung: Funktion identisch zu JPF, für einen 3. Frequenzwert

USC

Koeff.Masch

0,01 bis 100

1

tLS

T Kleine Fr. - s

0 bis 999.9

0 (keine Zeitbe-grenzung)

Betriebszeit bei kleiner Frequenz. Nach einem Betrieb in LSP während der definierten Zeit wird der
Motor automatisch angehalten. Der Motor läuft wieder an, wenn der Frequenzsollwert über LSP
liegt.
Achtung: Der Wert 0 entspricht einer unbegrenzten Zeit.
(1) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit starkem Drehmoment.

133

DEUTSCH

Auf den Parameter rFr Motorfrequenz angewandter Faktor.
Ermöglicht die Anzeige der Maschinengeschwindigkeit über den Parameter USP. USP = rFr x USC

GP_ATV58_DE.fm Page 134 Mardi, 2. avril 2002 6:01 18

Menü "Einstellung"

Die folgenden Parameter sind in der Makrokonfiguration "Fördertech" zugänglich.
Code

Beschreibung

UFr

IR-Kompens. -

%

Einstell-bereich

Werks-einstellung

0 bis 150 % oder
0 bis 800 %

100 %

Ermöglicht die Einstellung des standardmäßigen oder gemessenen Wertes. Der Einstellbereich wird
auf 800 % ausgedehnt, wenn Parameter SPC (Sondermotor) von Menü Antrieb gleich “Ja” ist.

SLP

Schlupfkomp. - %

0 bis 150 %

100 %

Anpassung der durch Eingabe der Motornenndrehzahl festgelegten Schlupfkompensation (vgl.
Menü "Antrieb").

SP2

Vorwahlfreq2- Hz

LSP bis HSP

10 Hz

LSP bis HSP

15 Hz

LSP bis HSP

20 Hz

LSP bis HSP

25 Hz

LSP bis HSP

30 Hz

LSP bis HSP

35 Hz

0 bis 1.36 In (1)

1.36 In (1)

2. Vorwahlfrequenz

SP3

Vorwahlfreq3- Hz
3. Vorwahlfrequenz

SP4

Vorwahlfreq4- Hz
4. Vorwahlfrequenz

SP5

Vorwahlfreq5- Hz

DEUTSCH

5. Vorwahlfrequenz

SP6

Vorwahlfreq6- Hz
6. Vorwahlfrequenz

SP7

Vorwahlfreq7- Hz
7. Vorwahlfrequenz

Ctd

I-Schwelle -

A

Stromschwellwert, ab dem der Logikausgang od. das Relais nach log. 1 übergeht.
(1) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit "starkem Drehmoment"

134

GP_ATV58_DE.fm Page 135 Mardi, 2. avril 2002 6:01 18

Menü "Einstellung"

Die folgenden Parameter sind in der Makrokonfiguration "Allgemeine Anwendung" zugänglich
Code

UFr

Beschreibung

IR-Kompens. -

%

Einstell-bereich

Werks-einstellung

0 bis 150 % oder 0 bis 800 %

100 %

Ermöglicht die Einstellung des standardmäßigen oder gemessenen Wertes. Der Einstellbereich wird
auf 800 % ausgedehnt, wenn Parameter SPC (Sondermotor) von Menü Antrieb gleich “Ja” ist.

SLP

Schlupfkomp. - %

0 bis 150 %

100 %

Anpassung der durch Eingabe der Motornenndrehzahl festgelegten Schlupfkompensation (vgl.
Menü "Antrieb").

JOG

Jog-Frequenz -Hz

0 bis 10 Hz

10 Hz

0 bis 2 s

0.5 s

Frequenz bei Schrittbetrieb.

JGt

Jog-Pause

-

s

Verzögerung zum Entprellen bei zwei aufeinanderfolgenden Jog-Befehlen

tL2

Momentbegr.2 - %

0 bis 200 % (1)

200 %

2. Drehmomentbegrenzung, wird über einen Logikeingang aktiviert
Die folgenden Parameter sind in der Makrokonfiguration "Variables Drehmoment" zugänglich
Beschreibung

Einstell-bereich

Werks-einstellung

IdC

I DC-Bremsung - A

0,10 bis 1,36 In (1)

Je nach Baugröße des Umrichters

Stärke des Bremsstroms bei Gleichstrombremsung über Logikeingang. Nach Ablauf von 30 Sekunden wird des Einspeisestrom auf 0,5 Ith begrenzt, falls er auf einen höheren Wert eingestellt ist.

PFL

U/f-Kennl.

-

%

0 bis 100 %

20 %

Ermöglicht die Anpassung der quadratischen U/f-Kennlinie, wenn die Funktion "Energiesparen"
inaktiv ist.
(1) 100 % entspricht dem Nennmoment eines Motors, dessen Leistung mit der des Umrichters bei Anwendung
mit "starkem Drehmoment" identisch ist.
(2) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit "starkem Drehmoment"
Die grau hinterlegten Parameter sind nur bei installierter Optionskarte E/A-Erweiterung zugänglich.

135

DEUTSCH

Code

GP_ATV58_DE.fm Page 136 Mardi, 2. avril 2002 6:01 18

Menü "Einstellung"

Die folgenden Parameter können nach einer Neubelegung der Eingänge/Ausgänge des Basisgerätes zugänglich
sein.
Code

Beschreibung

Einstell-bereich

Werks-einstellung

AC2

Hochlaufz. 2 - s

0.05 bis 999.9

5s

0.05 bis 999.9

5s

2. Hochlauframpe

dE2

Auslaufz. 2 - s

2. Auslauframpe
Ein Zugriff auf diese Parameter ist möglich, wenn der Schaltschwellwert der Rampe (Parameter Frt)
ungleich 0 Hz ist oder wenn ein Logikeingang dem Umschalten der Rampe zugeordnet ist.

IdC

I DC-Bremsung - A

0,10 bis 1,36 In (1)

Je nach Umrichter

Stärke des Bremsstroms bei Gleichstrombremsung. Dieser Parameter ist zugänglich, wenn ein
Logikeingang mit dem Anhalten über Gleichstrombremsung belegt ist. Nach Ablauf von 30 Sekunden wird der Einspeisestrom auf 0,5 Ith begrenzt, falls er auf einen höheren Wert eingestellt ist.

SP2

Vorwahlfreq2- Hz

LSP bis HSP

10 Hz

LSP bis HSP

15 Hz

LSP bis HSP

20 Hz

LSP bis HSP

25 Hz

LSP bis HSP

30 Hz

LSP bis HSP

35 Hz

0 bis 10 Hz

10 Hz

0 bis 2 s

0.5 s

2. Vorwahlfrequenz

SP3

Vorwahlfreq3- Hz
3. Vorwahlfrequenz

DEUTSCH

SP4

Vorwahlfreq4- Hz
4. Vorwahlfrequenz

SP5

Vorwahlfreq5- Hz
5. Vorwahlfrequenz

SP6

Vorwahlfreq6- Hz
6 . Vorwahlfrequenz

SP7

Vorwahlfreq7- Hz
7 . Vorwahlfrequenz

JOG

Jog-Frequenz- Hz
Frequenz bei Schrittbetrieb

JGt

JOG-Pause

-

s

Verzögerung zum Entprellen zwischen 2 aufeinanderfolgenden Jog-Befehlen

brL

F Bremsanzug- Hz

0 bis 10 Hz

0 Hz

Bremsabfallfrequenz, Lüftung Bremse

Ibr

I Bremsanzug-

A

0 bis 1,36 In(1)

0A

Bremsabfallstrom, Lüftung Bremse

brt

T Bremsanzug-

s

0 bis 5 s

0s

0 bis LSP

0 Hz

0 bis 5 s

0s

Bremsabfallzeit, Lüftung Bremse

bEn

F Br.-Abfall- Hz
Bremsanzugsfrequenz

bEt

T Br.-Abfall- Hz
Bremsanzugszeit

(1) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit "starkem Drehmoment".
136

GP_ATV58_DE.fm Page 137 Mardi, 2. avril 2002 6:01 18

Menü "Einstellung"

Code

Beschreibung

Einstell-bereich

Werks-einstellung

FFt

Schw.Ausl.NST-Hz

0 bis HSP

0 Hz

Auslöseschwellwert für Anhalten im Freilauf: bei Anforderung Anhalten über Rampe oder Schnellhalt; der
gewählte Anhaltemodus ist aktiviert, bis die Drehzahl unter diesen Schwellwert abfällt. Unterhalb dieses
Schwellwertes ist das Anhalten im Freilauf aktiviert. Dieser Parameter ist zugänglich, wenn Relais R2
nicht mit der Funktion BLC (Bremslogik) belegt ist, und wenn der Anhaltemodus im Menü "Antrieb" auf
"Rampe" oder "Schnellhalt" eingestellt ist

bIP

Bremsstartim

Nein-JA

Nein

Stromimpulsion bei Bremsefreigabe
Ja : Das Drehmoment beim Bremsabfall ist immer in Richtung FW (Rechtslauf), unabhängig von der
angeforderten Richtung.
Überprüfen, daß die Richtungdes Motordrehmoments bei Anforderung FW (Rechtslauf) der
Richtung des Lastanstiegs entspricht, gegebenenfalls 2 phasen des Motors umbkehren.
Nein : das Drehmoment während des Bremsabfalls ist der angeforderten Drehrichtung.

dtS

Faktor Tacho

1 bis 2

1

Der Funktion Tachogenerator zugeordneter Multiplikationsfaktor der Rückführung:
dtS =

rPG

9
Spanng Tacho bei max. Frequenz HSP

P-Anteil PI

1

0.01 - 100 /s

1/s

1 bis 100

1

Nein - Ja

Nein

DEUTSCH

0.01 bis 100

P-Anteil des PI-Reglers

rIG

I-Anteil PI
I-Anteil des PI-Reglers

FbS

Faktor Istw.
Multiplikationsfaktor für PI-Regler

PIC

Umkehr PI

Invertierung des PI-Regler-Ausgangssignals
Nein: normal
Ja: umgekehrt

Ftd

F-Schwelle - Hz

LSP bis HSP

50/60 Hz

Schwellwert der Motorfrequenz, ab dem der Logikausgang auf logisch 1 übergeht

F2d

F-Schwelle2- Hz

LSP bis HSP

50/60 Hz

2. Schwellwert der Motorfrequenz, identisch zu Ftd, für einen 2. Frequenzwert

Ctd

I-Schwelle -

A

0 bis 1.36 In (1)

1.36 In (1)

Stromschwellwert, ab dem der Logikausgang oder das Relais auf log. 1 übergeht

ttd

T-Schwelle-

%

0 bis 118 %

100 %

Schwellwert des thermischen Motorzustands, ab dem der Logikausgang oder das Relais auf logisch
1 übergeht

tL2

Momentbegr.2- %

0 bis 200 % (2)

200 %

2. Drehmomentbegrenzung, aktiviert über einen Logikeingang
(1) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit "starkem Drehmoment".
(2) 100 % entspricht dem Nennmoment eines Motors, dessen Leistung mit der des Umrichters bei Anwendung
mit "starkem Drehmoment" identisch ist.
Die grau hinterlegten Parameter sind nur bei installierter Optionskarte E/A-Erweiterung zugänglich.
137

GP_ATV58_DE.fm Page 138 Mardi, 2. avril 2002 6:01 18

Menü "Einstellung"

Code

Beschreibung

PSP

PI Filt Ist

– s

Einstell-bereich

Werks-einstellung

0,0 bis 10,0

0s

Einstellung der Zeitkonstante des Filters für die Rückführung PI

PI2

PI Sollw.2

- %

0 bis 100 %

30 %

Sollwert 2 voreingestellt auf PI, wenn ein digitaler Eingang auf Funktion 4 PI-Sollwert eingestellt ist.
100% = maxi Prozess
0% = mini Prozess

PI3

PI Sollw.3

- %

0 bis 100 %

60 %

Sollwert 3 voreingestellt auf PI, wenn ein digitaler Eingang auf Funktion 4 PI-Sollwert eingestellt ist.
100% = maxi Prozess
0% = mini Prozess

dtd

U.Temperatur

0 bis 118 %

105 %

DEUTSCH

Schwelle Thermischer Zustand Umrichter, über der der Logikausgang oder das Ausgangsrelais auf
logisch 1 übergeht.

138

GP_ATV58_DE.fm Page 139 Mardi, 2. avril 2002 6:01 18

Menü "Antrieb"

Dieses Menü ist nur im Niveau 2 zugänglich (Programmierschalter in Position
).
Die Parameter können nur im Stillstand bei verriegeltem Umrichter verändert werden.
Eine Optimierung der Antriebsleistungen wird wie folgt erreicht:
- durch Eingabe der auf dem Typenschild abgelesenen Werte im Menü "Antrieb",
- durch Auslösen einer Motormessung (nur bei Standardmotor).
Einsatz mit Sondermotoren (parallelgeschaltete Motoren, Verschiebeankermotoren, Reluktanzmotoren,
Schleifringläufer):
- Die Makrokonfiguration “Hdg: Fördertech.” oder “Gen: Allg. Anw.” auswählen.
- Im Menü "Antrieb" den Parameter Sondermotor (SPC) auf “Ja” einstellen.
- Im Menü "Einstellung" den Parameter IR-Kompens. (UFr) so einstellen, daß sich ein zufriedenstellender
Betrieb ergibt.
Code

Beschreibung

UnS

Ue Motor -

V

Einstell- bereich

Werks-einstellung

200 bis 240 V
200 bis 500 V

230 V (2)
400/460 V (2)

Vom Typenschild abgelesene Nennspannung des Motors. Der Einstellbereich hängt vom
Umrichtertyp ab:
ATV58••••M2
ATV58••••N4

FrS

Fnenn Motor-

Hz

10 bis 500 Hz

50/60 Hz (2)

Vom Typenschild abgelesene Nennfrequenz des Motors

Ie Motor

-

A

0.25 bis 1.36 In (1)

DEUTSCH

nCr

je nach Umrichter

Vom Typenschild abgelesener Nennstrom des Motors

nSP

Nenndrehzahl-rpm

0 bis 9999 1/min

je nach Umrichter

Vom Typenschild abgelesene Nenndrehzahl des Motors

COS

Cos Phi Mot

0.5 bis 1

je nach Umrichter

Vom Typenschild abgelesener Leistungsfaktor des Motors

tUn

Motormessung

Nein - Ja Fertig

Nein

Durch Setzen dieses Parameters auf "Ja" kann eine Motormessung der Motorsteuerung
durchgeführt werden. Nachdem die Motormessung ausgeführt wurde, stellt sich der Parameter
automatisch auf “Fertig” oder bei einer Störung auf “Nein“ zurück.
Achtung: Die Motormessung erfolgt nur, wenn zuvor kein Befehl erteilt wurde. Wenn die Funktion
"Freier Auslauf" oder "Schnellhalt" einem Logikeingang zugeordnet wurde, muß dieser Eingang
gesetzt werden (Eingang auf 0 aktiv)

tFr

Max-Frequenz- Hz

10 bis 500 Hz

60/72 Hz (2)

Maximale Ausgangsfrequenz.
Der maximale Wert hängt von der Taktfrequenz ab.
Siehe Parameter SFR (Menü Antrieb).

nLd

Energiespar

Nein-Ja

Ja

Optimiert den Wirkungsgrad des Antriebs.
Nur zugänglich in der Makrokonfiguration "Variables Moment".
(1) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit "starkem Drehmoment".
(2) je nach Position des Schalters 50/60 Hz

139

GP_ATV58_DE.fm Page 140 Mardi, 2. avril 2002 6:01 18

Menü "Antrieb"

Code

Beschreibung

Einstell- bereich

Werks-einstellung

Fdb

Imax=f (fmot)

Nein-Ja

Nein

Temperaturabhängige Strombegrenzung. Dieser Parameter erscheint nur in der
Makrokonfiguration "Variables Moment" (VT).

brA

Anp Auslaufz

Nein-Ja

Nein

Durch Aktivierung dieser Funktion erhöht sich automatisch die Auslaufzeit, wenn diese auf einen zu
niedrigen Wert eingestellt wurde. Somit läßt sich das Eintreten der Störung ObF vermeiden.
Diese Funktion sollte bei vorhandenem Bremswiderstand nicht aktiviert werden. Die
Werkseinstellung hängt von der verwendeten Makrokonfiguration ab: Nein bei "Fördertech.", Ja bei
"Variables Moment" und "Allgemeine Anwendung". Wenn Relais R2 der Funktion Bremslogik
zugeordnet ist, kann die Funktion nicht aktiviert werden.

Frt

F Rampe 2- Hz

0 bis HSP

0 Hz

Frequenzschwelle für Rampenumschaltung. Wenn die Ausgangsfrequenz Frt überschreitet, sind
die berücksichtigten Rampenzeiten AC2 und dE2.

DEUTSCH

Stt

Typ Anhalten

STN - FST - NST - DCI

STN

Anhaltemodus.
Bei Anhaltebefehl ist der Anhaltemodus bis zum Schwellwert FFt (Menü "Einstellung") aktiviert.
Unterhalb dieses Schwellwerts erfolgt das Anhalten im Freilauf.
STN : über Rampe
FST : Schnellhalt
NST : Freier Auslauf
DCI : Anhalten über Einspeisung von Gleichstrom.
Dieser Parameter ist nicht zugänglich, wenn Relais R2 mit der Funktion BLC (Bremslogik) belegt ist.

rPt

Typ Rampe

LIN - S - U

LIN

Definiert den Verlauf der Hochlaufund der Auslauframpen.
LIN : linear S : S-förmig U : U-förmig
f (Hz)

f (Hz)

GV

GV

Der Rundungsfaktor ist fest,
wobei t2 = 0,6 x t1
und t1 = eingestellte Rampenzeit.

S-förmig Rampen
0

0

t

t2

t

t2

t1

t1

f (Hz)

f (Hz)

GV

GV

Der Rundungsfaktor ist fest,
wobei t2 = 0,5 x t1
und t1 = eingestellte Rampenzeit.

U-förmig Rampen

0
t2

t

t1

dCF

K Schn.-halt

0
t2

t

t1

1 bis 10

4

Quotient zur Verkürzung der Auslauframpe, wenn die Funktion Schnellhalt aktiviert ist.

140

GP_ATV58_DE.fm Page 141 Mardi, 2. avril 2002 6:01 18

Menü "Antrieb"

Code

Beschreibung

tLI

Momentbegr

_ %

Einstell- bereich

Werks-einstellung

0 bis 200 % (1)

200 %

Mit der Funktion Momentbegrenzung kann das max. Motormoment begrenzt werden.

CLI

Begr.Strom -

A

0 bis 1,36 In (2)

1,36 In

Mit dem Begrenzungsstrom kann die Erwärmung des Motors begrenzt werden.

AdC

Auto GS-Br.

Nein-Ja

Ja

Bremsung bei automatischer Einspeisung von Strom im Stillstand.

PCC

Faktor P mot.

0.2 bis 1

1

Definiert das Verhältnis zwischen Nennleistung des Umrichters und dem Motor mit der kleineren
Leistung, wenn ein Logikeingang der Funktion "Umschaltung Motor" zugeordnet wurde.
Typ
F-Takt
SFt
LF-HF1-HF2
LF

SFr

Taktfrequenz-kHz

0.5-1-2-4-8-12-16 kHz

je nach Umrichter (1)

Auswahl der Taktfrequenz. Der Einstellbereich hängt vom Parameter SFt ab.
Wenn SFt = LF: 0,5 bis 2 oder 4 kHz je nach Baugröße Umrichter
Wenn SFt = HF1 oder HF2: 2 oder 4 bis 16 kHz je nach Baugröße Umrichter
Die max. Betriebsfrequenz (tFr) ist je nach Taktfrequenz begrenzt:
SFr(kHz)
tFr (Hz)

nrd

Geräuscharm

0.5
62

1
125

2
250
Nein-Ja

4
500

8
500

12
500

16
500

(3)

Zufallsgesteuerte Modulation der Taktfrequenz, um das Motorgeräusch zu verringern.

SPC

Sondermotor

Nein-Ja-PSM

Nein

Ja: Erweiterung des Einstellbereichs von Parameter UFr (Menü "Einstellung") zur Anpassung an
Sondermotoren. Zugang in den Makrokonfigurationen "Fördertech." und "Allgemeine Anwendung".
PSM: sperrt die Entdeckung von "Nicht gesteuerte Abschaltung hinter dem Umrichter" (sinnvoll vor
allem bei kleinen Motoren).
Nein: normaler Motor
Ja: Sondermotor
PSM: kleiner Motor
(1) 100 % entspricht dem Nennmoment eines Motors, dessen Leistung mit der des Umrichters bei Anwendung
mit "starkem Drehmoment" identisch ist.
(2) In entspricht dem im Katalog und auf dem Typenschild des Umrichters angegebenen Bemessungsbetriebsstrom des Umrichters bei Anwendung mit "starkem Drehmoment".
(3) Ja si SFt = LF, Nein si SFt = HF1 oder HF2

141

DEUTSCH

Einstellbereich der Taktfrequenz:
LF - niedrige Taktfrequenz
HF1/HF2 - Hohe Taktfrequenz
HF1 - niedrige Einschaltdauer, ohne Deklassierung des Umrichters. Erreicht die Umrichtererwärmung 95 %, wird die Taktfrequenz je nach Umrichter auf 2 bzw. 4 kHz umgeschaltet. Unterhalb
von 70 % wird die ursprüngliche Taktfrequenz wiederhergestellt.
HF2 - hohe Einschaltdauer, automatische Deklassierung des Umrichters um eine Typenleistung.
Die Änderung dieses Parameters führt zu einer Rückkehr zu den Werkseinstellungen
der Parameter:
• nCr, CLI, Sfr, nrd (Menü "Antrieb")
• ItH, IdC, Ibr, Ctd (Menü "Einstellung").

GP_ATV58_DE.fm Page 142 Mardi, 2. avril 2002 6:01 18

Menü "Antrieb"

Code

Beschreibung

Einstell- bereich

Werks-einstellung

PGt

Typ Impulsg

INC-DET

DET

Typ des verwendeten Impulsgebers, wenn eine Karte E/A Istwert-Geber installiert ist: INC:
Inkrementalgeber (A, A+, B, B+ sind verdrahtet)
DET: Impulsgeber (nur A ist verdrahtet)

PLS

Impulse/Umdr

1 bis 1024

1024

Anzahl der Impulse pro Umdrehung des Gebers.

DEUTSCH

Die grau hinterlegten Parameter sind nur bei installierter Optionskarte E/A-Erweiterung zugänglich.

142

GP_ATV58_DE.fm Page 143 Mardi, 2. avril 2002 6:01 18

Menü "Steuerung"

Dieses Menü ist in Niveau 2 (Position
des Programmierschalters) zugänglich. Die Parameter können nur
im Stillstand bei verriegeltem Umrichter verändert werden.
Code

Beschreibung

Einstell- bereich

Werks-einstellung

tCC

2/3-Draht

2 W- 3 W (2 - 3 Drähte)

2W

Typ der Steuerung über die Klemmenleiste: 2- oder 3-Draht-Steuerung.
Bei Veränderung dieses Parameters ist eine doppelte Bestätigung erforderlich, da er eine
Neuzuordnung der Logikeingänge nach sich zieht. Beim Übergang von 2- auf 3-DrahtSteuerung werden die Zuordnungen der Logikeingänge um einen Eingang verschoben.
Die Zuordnung von LI3 bei 2 Drähten wird zur Zuordnung von LI4 bei 3 Drähten. Bei 3-DrahtSteuerung können die Eingänge LI1 und LI2 nicht neu zugeordnet werden.
Werkseinstellung der Logikeingänge bei 3-Draht-Steuerung:
E/A

Fördertech.

Allgem. Anwendung

LI1

STOP

STOP

Variables Moment
STOP

LI2

RUN Rechtslauf

RUN Rechtslauf

RUN Rechtslauf

LI3

RUN Linkslauf

RUN Linkslauf

RUN Linkslauf

LI4

2 Vorwahlfrequ.

Schrittbetrieb

Sollw. Umschaltung

LI5

4 Vorwahlfrequ.

Anhalten Freilauf

Gleichstrombremsung

24 V LI1 LI2 LIx

LI1 : Stop
LI2 : Rechtslauf
LIx : Linkslauf

Diese Auswahl erscheint nur, wenn 2-Draht-Steuerung konfiguriert wurde.
Code

Beschreibung

Einstell- bereich

Werks-einstellung

tCt

Typ 2-Draht?

LEL-TRN-PFo

LEL

Typ der 2-Draht-Steuerung:
- Zustand der Logikeingänge (LEL = Niveau)
- Zustandsänderung der Logikeingänge (TRN = Flanke)
- Zustand der Logikeingänge, Rechtslauf immer prioritär gegenüber Linkslauf (PFo = Vorrang
RL)
Anschlußbeispiel :
Steuerklemmenleiste ATV58
LI1 : Rechtslauf
LIx : Linkslauf

24 V LI1 LIx

Die grau hinterlegten Parameter sind nur bei installierter Optionskarte E/A-Erweiterung zugänglich.

143

DEUTSCH

LI6
8 Vorwahlfrequ.
Löschen Störungen
Freier Auslauf
Die grau hinterlegten Eingänge/Ausgänge sind zugänglich, wenn eine Optionskarte E/A-Erweiterung
installiert wurde.
3-Draht-Steuerung (Steuerung über Impulse: ein Impuls reicht aus, um das Anlaufen zu
veranlassen). Diese Auswahl sperrt die Funktion "Automatischer Wiederanlauf".
Anschlußbeispiel:
Steuerklemmenleiste ATV58

GP_ATV58_DE.fm Page 144 Mardi, 2. avril 2002 6:01 18

Menü "Steuerung"

Code

Beschreibung

Einstell- bereich

Werks-einstellung

rln

Nur pos. Sum

Nein - Ja

Nein

• Eine Drehrichtungsumkehr kommt nur über den Fahrbefehl zustande, nicht über gesteuerten
Richtung, selbst wenn diese negative Summensollwerte bzw. Ausgangssignale des PI-Reglers.
• Unterdrückung Drehrichtungsumkehr über FWD/REV-Taste des Terminals.

bSP

fLSP
f0

Nein
BNS: f0
BLS: fLSP

Nein

Betriebsart unterhalb der kleinen Frequenz (LSP) :
F : Motorfrequenz

F : Motorfrequenz

HSP

HSP
Nein

LSP

LSP
Sollwert

0

0

Sollwertunterdrückung
(BNS)
Sollwert
100 %

100 %
F : Motorfrequenz

DEUTSCH

HSP
Sollwertbegrenzung
(BLS)

LSP

Sollwert

0

100 %

CrL
CrH

Min Wert AI2- mA
Max Wert AI2- mA

0 bis 20 mA
4 bis 20 mA

4 mA
20 mA

Minimaler und Maximaler Signalwert auf dem Eingang AI2.
Diese beiden Parameter definieren das Signal auf AI2. Beispiel : 0-20 mA, 4-20 mA, 20-4mA …
Frequenz
HSP

LSP
0
CrL

144

CrH

20

AI 2
(mA)

GP_ATV58_DE.fm Page 145 Mardi, 2. avril 2002 6:01 18

Menü "Steuerung"

Code

Beschreibung

Einstell- bereich

Werks-einstellung

AOL
AOH

Min Wert AO- mA
Max Wert AO- mA

0 bis 20 mA
0 bis 20 mA

0 mA
20 mA

Minimaler und Maximaler Signalwert auf dem Ausgang AO und
AO1 (1).
Diese beiden Parameter definieren das Signal auf AO und AO1.
Beispiel : 0-20 mA, 4-20 mA, 20-4mA …

Parameter
Max

AO (mA)

0
AOL

Str

Sollw-Speich

AOH

20

NO-RAM-EEP

NO

Bei Verwendung der Funktion "+/- Drehzahl" kann der Sollwert für den nächsten Fahrbefehl
gespeichert werden:
- RAM bei Fahrbefehlunterbrechung
- EEPROM bei Spannungsunterbrechung.

LCC

Vor-Ort-St.

Nein - Ja

Nein

PSt

Vorrang STOP

Nein - Ja

Ja

Vorrang der STOP-Taste unabhängig vom Befehlskanal (Klemmenleiste oder Feldbus).
Um den Parameter PSt auf "Nein" zu stellen:
1 - "Nein" anzeigen
2 - auf die Taste "ENT" drücken
3 - der Umrichter zeigt "Vgl. Prog.-Anl." an
4 - ▲ , dann ▼ , anschließend "ENT" betätigen.
Bei Anwendungen mit kontinuierlichen Prozeßabläufen sollte die Taste deaktiviert werden
(Einstellung auf "Nein")

Add

Adresse ATV

0 bis 31

0

Adresse des Umrischters, wenn er über die Schnittstelle des Terminalsteckers gesteuert wird
(außer bei Bedienterminal und Programmierterminal)

tbr

BdRate RS485

9600-19200

19200

Übertragungsgeschwindigkeit über die serielle Schnittstelle RS485 in Bit/Sekunde
(Berücksichtigung erfolgt beim nächsten Einschalten).
Wenn tbr ≠ 19200, kann das Terminal nicht mehr verwendet werden. Um das Terminal
zu reaktivieren, muss tbr über die serielle Schnittstelle wieder auf 19200 konfiguriert
oder eine Rückkehr zu den Werkseinstellungen ausgeführt werden (siehe Seite 121).

rPr

Reset Zähler

Nein-APH-RTH

Nein

Rücksetzen der kWh oder der Betriebszeit auf Null.
Nein
APH : Rücksetzen der kWh auf Null
RTH : Rücksetzen der Betriebszeit auf Null.
Eine Bestätigung des Reset-Befehls muß über "ENT" erfolgen.
Die Ausführung von APH und RTH erfolgt unmittelbar, der Parameter stellt sich anschließend
automatisch auf Nein zurück.
(1) Den Analogausgang AO gibt es, wenn eine E/A-Erweiterungskarte installiert ist.

145

DEUTSCH

Steuerung des Umrichters über das Terminal. Die Tasten STOP/RESET, RUN und FW/REV sind
aktiviert. Der Frequenzsollwert wird über den Parameter LFr vorgegeben. Nur die Befehle Anhalten
im Freilauf, Schnellhalt und Anhalten über DC-Bremsung bleiben an der Klemmenleiste aktiviert.
Wenn die Verbindung Umrichter / Terminal unterbrochen wird, verriegelt sich der Umrichter mit der
Störung SLF.

GP_ATV58_DE.fm Page 146 Mardi, 2. avril 2002 6:01 18

Menü "Belegung der Eingänge/Ausgänge"

Dieses Menü ist in der Position
des Programmierschalters zugänglich.
Die Belegungen können nur im Stillstand bei verriegeltem Umrichter verändert werden.
Code

Funktion

LI2

Belegung

LI2

Siehe Übersichtstabelle und Beschreibung der Funktionen.
Die in diesem Menü vorhandenen Ein- und Ausgänge hängen von den gegebenenfalls im Umrichter
installierten E/A-Karten sowie von der zuvor im Menü "Steuerung" getroffenen Auswahl ab.
Die werkseitigen Konfigurationen sind von der gewählten Makrokonfiguration vorab belegt.

Übersichtstabelle der Zuordnungen der Logikeingänge (außer Auswahl 2 Draht / 3 Draht)
Optionskarten Erweiterung E / A

2 Logikeingänge LI5-LI6

Umrichter ohne Optionsmodul

NO:Nicht belegt
RV :Linkslauf
RP2:Umschaltg. Rampe
JOG:JOG Schrittb.

DEUTSCH

+SP: + Drehzahl
-SP: - Drehzahl

3 Logikeingänge LI2 bis LI4
(Nicht belegt)

X

(Linkslauf)

X

(Umschalten der Rampe)

X

(Schrittbetrieb)

X

(+Drehzahl)

X

(-Drehzahl)

X

PS2: 2Vorw.-Frequ.

(2 Vorwahlfrequenzen)

X

PS4: 4Vorw.-Frequ.

(4 Vorwahlfrequenzen)

X

(8 Vorwahlfrequenzen)

X

(Umschalten der Sollwerte)

X

PS8: 8Vorw.-Frequ.
RFC:Umsch. Sollw.
NST:Freier Auslauf
DCI:DC-Aufschaltung
FST:Schnellhalt

(Anhalten im Freilauf)

X

(Anhalten über DC-Bremsung)

X

(Schnellhalt)

X

CHP:Umsch. Motor

(Umschalten der Motoren)

X

TL2:Moment-Begr. 2

(2. Momentenbegrenzung)

X

(Vor-Ort-Betätigung)

X

FLO:Vor-Ort-Betrieb
RST:Reset Fehler

(Löschen der Störungen)

X

ATN:Motormessung

(Motormessung)

X

PAU:PI Aut/Man

(Auto-manu PI) wenn ein AI = PIF

X

PR2:2Sollw.

PI

(2 PI-Vorwahl-Sollwerte) wenn ein AI = PIF

X

PR4:4Sollw.

PI

(4 PI-Vorwahl-Sollwerte) wenn ein AI = PIF

X

TLA:Moment-Begr.

(Momentenbegrenzung über AI) wenn ein AI = ATL

X

(externer Fehler)

X

EDD:Ext.Fehl

ACHTUNG: Wenn ein Logikeingang mit "Freier Auslauf" oder "Schnellhalt" belegt ist, kann ein
Anlauf nur erfolgen, wenn dieser Eingang an +24V angeschlossen wird, da diese Anhaltefunktionen
bei logisch 0 der Eingänge aktiv sind.

146

GP_ATV58_DE.fm Page 147 Mardi, 2. avril 2002 6:01 18

Menü "Belegung der Eingänge/Ausgänge"

Übersichtstabelle der Zuordnungen der Analogeingänge und der Gebereingänge
Optionskarten Erweiterung E / A

Umrichter ohne Optionsmodul

NO:Nicht belegt
FR2:F-Soll 2
SAI:Sum. Sollw.
PIF:PI-Istwert

Analogeingang
AI3

GeberEingang A+,
A-, B+, B(1)

X

X

X

X

Analogeingang AI2
(Nicht belegt)

X

(Frequenzsollwert 2)
wenn ein LI=RFC

X

(Summensollwert)

X

(Istwert des Pl-Reglers)

X

X

PIM:Man.Sollw.PI

(Manueller Frequenzsollwert PI)
wenn ein AI=PI ond ein LI=PAU

X

SFB:Tacho-Signal

(Tachogenerator)

X

PTC:Motor-PTC
ATL:Momentbegr.
RGI:Istwert Geber

(PTC-Fühler)

X

(Momentenbegrenzung)

X

(Istwert Geber od. Impulsgeber)

X

ACHTUNG: Wenn Relais R2 mit der Funktion "Bremslogik" belegt ist, wird AI3 in Werkseinstellung
automatisch mit der Tachorückführung belegt, falls eine E/A-Karte installiert ist. Die Neubelegung
von AI3 bleibt dennoch möglich.

Übersichtstabelle der Zuordnungen der Logikausgänge
Optionskarte Erweiterung E / A

Logikausgang
LO

Umrichter ohne Optionsmodul

NO:Nicht belegt
RUN:In Betrieb
OCC:Motorschütz
FTA:Freq.-Schw. err.
FLA:HSP erreicht
CTA:I-Schwelle err.
SRA:F-Soll erreicht
TSA:T-Schw. erreicht
BLC:Bremssteuerung
APL:Verl. 4-20 mA
F2A:Freq.-Schw.2 err.

tAd:Temp. Alarm

Relais R2
(Nicht belegt)

X

X

(Umrichter in Betrieb)

X

X

(Steuerung über Motorschütz)

X

X

(Frequenzschwellwert erreicht)

X

X

(HSP erreicht)

X

X

(Stromschwellwert erreicht)

X

X

(Sollfrequenz erreicht)

X

X

(Schwelle Thermischer Zustand Motor erreicht)

X

X

(Bremssteuerung)

X

(Verlust Sollwert 4 / 20 mA)

X

X

(2. Frequenzschwellwert erreicht)

X

X

(Schwelle Thermischer Zustand Umrichter erreicht)

X

X

147

DEUTSCH

(1) Achtung: Das Menü zur Belegung des Gebereingangs A+, A-, B+, B- heißt "Belegung AI3".

GP_ATV58_DE.fm Page 148 Mardi, 2. avril 2002 6:01 18

Menü "Belegung der Eingänge/Ausgänge"

Übersichtstabelle der Zuordnungen des Analogausgangs
Optionskarte Erweiterung E / A

Analogausgang AO

Umrichter ohne Optionsmodul

Analogausgang AO1

NO:Nicht belegt

(Nicht belegt)

OCR:Motorstrom

(Motorstrom)

X

(Motorfrequenz)

X

ORP:Ausg. Rampe

(Ausgang Rampe)

X

TRQ:Motormoment

(Motormoment)

X

(Motormoment mit Vorzeichen)

X

OFR:Motorfrequenz

STQ:Moment m. Vorz.
ORS:Rampe m. Vorz.

(Ausgang Rampe mit Vorzeichen)

X

OPS:Sollw. PI

(Ausgang PI-Sollwert) wenn ein AI = PIF

X

OPF:Istwert PI

(Ausgang PI-Istwert) wenn ein AI = PIF

X

OPE:Abweichg PI

(Ausgang PI-Abweichung) wenn ein AI = PIF

X

OPI:Integral PI

(Ausgang PI-Integral) wenn ein AI = PIF

X

(Motorleistung)

X

OPR:Motorleistg

DEUTSCH

X

THR:Motorerwärmg

(Thermischer Zustand des Motors)

X

THD:Erwärmg Umr.

(Thermischer Zustand Umrichter)

X

Nach einer Neuzuordnung der Eingänge/Ausgänge erscheinen die mit der Funktion verknüpften
Parameter automatisch in den Menüs, als Makrokonfiguration wird "Anwender" angezeigt. Bei
bestimmten Neuzuordnungen erscheinen neue Einstellparameter, deren Abgleich Sie im Menü
"Einstellung" nicht vergessen sollten:
E/A

Zuordnung

Einstellparameter

Umschalten der Rampe

AC2 dE2

JOG

Schrittbetrieb

JOG JGt

PS4

4 Vorwahlfrequenzen

SP2-SP3

PS8

8 Vorwahlfrequenzen

SP4-SP5-SP6-SP7

DCI

Anhalten über DC-Bremsung

IdC

LI

TL2

Zweite Momentenbegrenzung

tL2

LI

PR4

4 PI-Vorwahl-Sollwerte

PI2-PI3

AI

PIF

Istwert des PI-Reglers

rPG-rIG-PIC-rdG-rEDPrG-PSr-PSP-PLr-PLb

LI

RP2

LI
LI
LI
LI

AI

SFB

Tachogenerator

dtS

R2

BLC

Bremssteuerung

Ibr-brt-bEn-bEt-brL-bIP

LO/R2

FTA

Frequenzschwellwert erreicht

Ftd

LO/R2

CTA

Stromschwellwert erreicht

Ctd

LO/R2

TSA

Schwelle Thermischer Zustand Motor erreicht

ttd

LO/R2

F2A

2. Frequenzschwellwert erreicht

F2d

LO/R2

TAD

Schwelle Thermischer Zustand Umrichter erreicht

dtd

148



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Create Date                     : 2002:05:02 13:54:36Z
Modify Date                     : 2002:05:02 15:59:32+02:00
Page Count                      : 294
Creation Date                   : 2002:05:02 13:54:36Z
Mod Date                        : 2002:05:02 15:59:32+02:00
Producer                        : Acrobat Distiller 5.0.2 (Macintosh)
Author                          : FARRIS Daniel
Metadata Date                   : 2002:05:02 15:59:32+02:00
Creator                         : FARRIS Daniel
Title                           : 1_COUV.fm
EXIF Metadata provided by EXIF.tools

Navigation menu