PowerLogic® ION7550 / ION7650 Energy & Power Quality Meter Installation Guide December 2007 PowerLogic ION7550 / ION7650 Installation Guide Danger This symbol indicates the presence of dangerous voltage within and outside the product enclosure that may constitute a risk of electric shock, serious injury or death to persons if proper precautions are not followed. Caution This symbol alerts the user to the presence of hazards that may cause minor or moderate injury to persons, damage to property or damage to the device itself, if proper precautions are not followed. Note This symbol directs the user’s attention to important installation, operating and maintenance instructions. Installation Considerations Installation and maintenance of the PowerLogic ION7550 / ION7650 meter should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. The meter must be installed in accordance with all local and national electrical codes. DANGER Failure to observe the following instructions may result in severe injury or death. During normal operation of the ION7550 / ION7650 meter, hazardous voltages are present on its termi- nal strips, and throughout the connected potential transformer (PT), current transformer (CT), digital (status) input, control power and external I/O circuits. PT and CT secondary circuits are capable of generating lethal voltages and currents with their primary circuit energized. Follow standard safety precautions while performing any installation or service work (i.e. removing PT fuses, shorting CT secondaries, etc.). The terminal strips on the meter base should not be user-accessible after installation. Do not use digital output devices for primary protection functions. These include applications where the devices perform energy limiting functions or provide protection of people from injury. Do not use the ION7550 / ION7650 in situations where failure of the devices can cause injury or death, or cause sufficient energy to be released that can start a fire. The meter can be used for secondary protection functions. Do not HIPOT/Dielectric test the digital (status) inputs, digital outputs, or communications terminals. Refer to the label on the ION7550 / ION7650 meter for the maximum voltage level the device can withstand. CAUTION Observe the following instructions, or permanent damage to the meter may occur. The ION7550 / ION7650 meter offers a range of hardware options that affect input ratings. The ION7550 / ION7650 meter’s serial number label lists all equipped options. Applying current levels incom- patible with the current inputs will permanently damage the meter. This document provides installation instructions applicable to each hardware option. The ION7550 / ION7650 meter’s chassis ground must be properly connected to the switchgear earth ground for the noise and surge protection circuitry to function correctly. Failure to do so will void the warranty. Terminal screw torque: Barrier-type (current, voltage, and relay terminal screws: 1.35 Nm (1.00 ft-lbf) max. Captured-wire type (digital inputs/outputs, communications, power supply: 0.90 Nm (0.66 ft.lbf) max. FCC Notice This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. © 2007 Schneider Electric. All rights reserved. 3 PowerLogic ION7550 / ION7650 Installation Guide This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. The Ringer Equivalence Number (REN) for the ION7550 / ION7650 optional internal modem is 0.6. Connection to the ION7550 / ION7650 internal modem should be made via an FCC Part 68 compliant telephone cord (not supplied). The ION7550 / ION7650 cannot be used on a public coin phone service or party line services. Network Compatibility Notice for the Internal Modem The internal modem in meters equipped with this option is compatible with the telephone systems of most countries in the world. Use in some countries may require modification of the internal modem’s initialization strings. If problems using the modem on your phone system occur, please contact Schneider Electric Technical Support. Standards Compliance CSA: Certified to CAN/ Certified to CSA C22.2 No.1010-1 UL 3111 Made by Power Measurement Ltd. PowerLogic, ION, ION Enterprise, MeterM@il, WebMeter and Modbus are either trademarks or registered trademarks of Schneider Electric. Covered by one or more of the following patents: U.S. Patent No's 7010438, 7006934, 6990395, 6988182, 6988025, 6983211, 6961641, 6957158, 6944555, 6871150, 6853978, 6825776, 6813571, 6798191, 6798190, 6792364, 6792337, 6751562, 6745138, 6737855, 6694270, 6687627, 6671654, 6671635, 6615147, 6611922, 6611773, 6563697, 6493644, 6397155, 6236949, 6186842, 6185508, 6000034, 5995911, 5828576, 5736847, 5650936, D505087, D459259, D458863, D443541, D439535, D435471, D432934, D429655, D427533. 4 © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide PowerLogic ION7550 / ION7650 Models Integrated Display Model Comes with front optical port. TRAN (transducer) Model The TRAN model has no display. Available Options Option ION7550 Form Factor Current Inputs Integ. Display TRAN 5 MB memory 10 MB memory Up to 256 sampling rate Standard Standard (RS-232, 1 Amp Ethernet RJ45 Ethernet Fiber Modem (5 Amp) Power Supply COM RS-485, optical) Standard Low Voltage DC Model Form Factor Current Inputs Integ. Display Same as ION7550 TRAN 5 MB memory Power Supply 10 MB memory Same as Up to 512 ION7550 sampling rate (standard) 1024 sampling rate (optional) EN50160 compliance IEC61000-4-30 Class A compliance ION7650 COM Same as ION7550 I/O Standard (8 digital inputs, 3 Form C relays, 4 Form A outputs) Extra 8 digital inputs Four 0-1mA analog inputs Four 0-20 mA analog inputs Four -1 to 1mA analog outputs Four 0-20 mA analog outputs I/O Same as ION7550 Security Standard1 RMANSI2 Security Same as ION7550 Notes 1 Standard = password protected, no locking or sealing. 2 RMANSI = ANSI C12.16 approved revenue meter; meets ANSI C12.20 class 0.2 accuracy standards. © 2007 Schneider Electric. All rights reserved. 5 PowerLogic ION7550 / ION7650 Installation Guide Before You Begin Before installing the meter, familiarize yourself with the steps in this guide and read the safety precautions presented on the “Installation Considerations” page. DANGER Do not power up the meter until the current and voltage wiring is completed. Recommended Tools Phillips screwdriver Precision flat-head screwdriver Wire cutters / stripper Meter Overview Meter Front Meter Back Voltage and Current Inputs Digital Inputs Softkeys ESC Button Optical Port Navigation Buttons Analog Outputs I/O Expansion Card Power Supply Operational LEDs Analog Inputs PROG/SELECT Button Communications Card Form C Digital Outputs Digital Inputs Ground Terminal Form A Digital Outputs Front Panel Button Functions PROG PROG/SELECT: Press the PROG/SELECT (program or select) button to enter Setup mode. In Setup mode, press the PROG/SELECT button to accept changes. Press the ESC (Escape) button to return to a higher menu or discontinue a configuration change. ESC: ESC Press the UP / DOWN arrow buttons to highlight menu items, or increment / decrement numbers. NAVIGATION: Press the LEFT or RIGHT arrow buttons to move to an adjacent digit. SOFTKEY: Press a SOFTKEY button to select the parameter that you want to configure from the sub-menus. 6 © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide Unit Dimensions Basic Model — Rear View Basic Model — Front View © 2007 Schneider Electric. All rights reserved. Basic Model — Side View 7 PowerLogic ION7550 / ION7650 Installation Guide Step 1: Mount the Meter Environmental Specifications Mounting Location Operating Range Display Operating Range Storage Range Relative Humidity Range Indoor use -20 to +70ºC (-4 to +158ºF) Standard Power Supply -20 to +50ºC (-4 to +122ºF) Low Voltage DC Power Supply No formation of ice -20 to +70ºC (-4 to +158ºF) -40 to +85ºC (-40 to +185ºF) 5 to 95% non-condensing Meter Battery Considerations The meter’s battery life expectancy depends on both temperature and the amount of time the meter is without power. For typical installations, the battery should last 20 years or more. If the meter is not powered, the battery will last a minimum of 7 years at room temperature. Integrated Display Model 1. Fit the meter into the DIN standard 192 cutout (186 mm by 186 mm). 2. Slide the four brackets into their slots on the back of the meter and secure using the four Phillips head screws. Do not overtighten. Screw DIN 192 Cutout Bracket Step 2: Wire the Ground Terminal Connect the terminal to a good earth ground with a 2.1 mm2 (14 AWG) wire. Ensure that the terminal nut is tightened down securely onto the ground wire. Do not use metal door hinges as a grounding point. 8 © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide Step 3: Wire the Digital I/O and Analog I/O Form C Digital Outputs: Mechanical Relays R1 - R3 Internal Form C Mechanical Relay R11 R13 R12 R11 R12 R13 R21 Type Contacts Wire Connector Voltage Rating Rated Load @ Rated Voltage Max. Voltage MOV Protection Max. Load @ Max. Voltage Turn-On Time Isolation Turn-Off Time Form C (R1, R2, R3) K (common), Y (NO), Z (NC) Use wiring that is appropriate for the application Ring or split ring connector 250 VAC / 30 VDC Resistive: 10 A (AC/DC) Inductive (PF=0.4): 7.5 A (AC) / 5 A (DC) 380 VAC / 125 VDC between K and NO/NC 300 V max. between NO and NC 3 A (AC) / 0.2 A (DC) 15 ms max. 5,000 VAC for 60 s 5 ms max. No load = 10,000,000 operations Rated voltage and load = 100,000 operations ½ cycle or 1 s Lifetime Update time Meter NO NC K Mechanical relays should always be protected by external fuses Load Alarm Lamp External Supply Form A Digital Outputs: Solid State Relays D1 - D4 Form A (D1, D2, D3, D4) Wire 1.3 to 0.1 mm2 (16 to 28 AWG) Continuous or pulse 30 VDC 80 mA per channel Optically isolated; max. 5,000 V RMS isolation (UL-E91231) ½ cycle or 1 s Signal Type Max. Load Voltage Max. Load Current Isolation Scan Time Meter D1 - + _ + 1.8 Wh + D2 - + D3 _ _ D3 - + + + _ DIGITAL OUTPUTS D4 - + D2 _ _ + D1 + + Internal Form A Solid State Relay Type D1 _ _ + External Relays External Supply 30VDC max D4 output is factory-configured to pulse once every 1.8 Wh for Class 20 meters, or once every 0.18 Wh for Class 2 meters (for calibration testing purposes). © 2007 Schneider Electric. All rights reserved. 9 PowerLogic ION7550 / ION7650 Installation Guide Digital Inputs: S1 - S8 DIGITAL INPUTS S C O M S S 8 7 S 6 S S 5 4 S 3 S 2 S 1 Type Application Self-excited (internal 30 VDC supply) Dry contact sensing, or with external excitation Wire 1.3 to 0.1 mm2 (16 to 28 AWG) 1 ms 20 pulses per second 1 ms ½ cycle (after timing resolution) max. 200 VDC for 10s 130 VDC continuous Min. Pulse Width Max. Pulse Rate Timing Resolution Updated Isolation to Ground Max. External Voltage Internal Excitation External Excitation Meter Meter _ _ S7 + + _ + S7 _ S8 + 30 VDC + SCOM _ Opticallycoupled switch S8 30 VDC + + _ _ SCOM Opticallycoupled switch External Supply 130 VDC max Digital Inputs (Meter Ordering Option): DI1 - DI8 Type Application Self excited (internal 30 VDC supply) Dry contact sensing, or with external excitation Wire Min. Pulse Width Max. Pulse Rate Timing Resolution Updated Isolation to Ground Max. External Voltage 1.3 to 0.1 mm2 (16 to 28 AWG) 20 ms 25 pulses per second 2 ms ½ cycle (after timing resolution) 750 VDC 50 VDC continuous Internal Excitation Meter External Excitation Meter Opticallycoupled switch Opticallycoupled switch External Supply 50 VDC max 10 © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide Analog Inputs (Meter Ordering Option): AI1 to AI4 AI3 AI3 Captured wire connector Wire 1.3 to 0.1 mm2 (16 to 28 AWG) DC current Signal Type + - AI4 Type AI2 AI1 Available Options 0 to 20 mA (scalable 4-20 mA) or 0 to 1 mA Input Impedance Accuracy Update Rate Isolation to Ground Isolation Impedance 24 Ω (0-20 mA option) or 475 Ω (0-1 mA option) +/– 0.3% of full scale 1s 750 V max 400 kΩ (channel/channel) Thermocoupler mA mV Voltage-toCurrent Transducer Meter + AI1 - Example application: temperature sensing NOTE Do not connect the analog inputs of the I/O card to the analog outputs on the same I/O card. Analog Outputs (Meter Ordering Option): AO1 to AO4 AO3 OUT COM Type Captured wire connector Wire 1.3 to 0.1 mm2 (16 to 28 AWG) DC current 0 to 20 mA (scalable 4-20 mA) or -1 to 1 mA (scalable 0-1 mA) 500 Ω (0-20 mA option) or 10 kΩ (-1 to 1 mA option) +/– 0.30% of full scale ½ cycle or 1 s min. 1 cycle for measurement + ½ cycle for ION + 1 s delay for hardware 750 V Signal Type Available Options Driving Capability AO4 A03 A02 AO1 Accuracy Update Rate Latency Isolation to Ground Meter Analog Meter + OUT AO1 Example application: driving an analog meter with the DC current output COM NOTE Do not connect the analog outputs of the I/O card to the analog inputs on the same I/O card. © 2007 Schneider Electric. All rights reserved. 11 PowerLogic ION7550 / ION7650 Installation Guide Step 4: Wire the Voltage and Current Inputs V1 V2 V3 V4 Vref I11 I12 I21 3~ VOLTAGE INPUTS I22 I31 I32 I41 I42 I51 I52 3~ CURRENT INPUTS Voltage Inputs Connector Type Ring or split ring connector Wire Gauge 3.3 to 2.1 mm2 (12 to 14 AWG) 347 V L-N RMS /600 V L-L RMS 1200 V L-N peak 1500 VAC RMS continuous 2500 VAC RMS at 60 Hz for 60 s 5 MΩ/phase (phase - Vref) Rated Inputs Fault Capture Overload Dielectric Withstand Input Impedance Current Inputs: Class 20 Current Inputs (5A Option) Connector Type Wire Gauge Input Rating Starting Current Fault Capture Max. Voltage Overload Dielectric Withstand Burden Impedance Ring or split ring connector 5.3 to 3.3 mm2 (10 to 12 AWG): Use 8.4 mm2 (8 AWG) for 10-20 A applications 5 A, 10 A, and/or 20 A RMS 0.005 A RMS 70 A peak 600 V RMS (CAT III IEC61010-1) 500 A RMS for 1 s, non-recurring 2500 VAC RMS at 60 Hz for 60 s 0.05 VA per phase (at 5 A) 0.002 Ω per phase Current Inputs: Class 2 Current Inputs (1A Option) Connector Type Ring or split ring connector Wire Gauge 5.3 to 3.3 mm2 (10 to 12 AWG) 1 A, 2 A, 5 A, and/or 10 A RMS 0.001 A RMS 17.5 A peak 600 V RMS (CAT III IEC61010-1) 50 A RMS for 1s, non-recurring 2500 VAC RMS at 60 Hz for 60 s 0.015 VA per phase (at 1 A) 0.015 Ω per phase Input Rating Starting Current Fault Capture Max. Voltage Overload Dielectric Withstand Burden Impedance NOTE The appropriate Volts Mode setting is included with each wiring diagram. Refer to Step 8 to learn how to configure Volts Mode on the meter. 12 © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide 4-Wire Wye, 3-Element, Direct Connection Diagram LOAD LINE Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source I4 Optional 347 V L-N / 600 V L-L max. VOLTS MODE = 4W-Wye 4-Wire Wye, 3-Element, 3 PTs Connection Diagram LOAD LINE Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source I4 Optional Use PTs for voltages over 347 V L-N / 600 V L-L. Wye (Star) wiring for PT primaries and secondaries. VOLTS MODE = 4W-Wye 4-Wire Wye, 2½-Element, 2 PTs Connection LOAD LINE Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source I4 Optional Phase B voltage (V2) displayed by meter is derived from phase A and phase C, not measured. V2 will display a value even if no voltage is present on Phase B. V2 values are only accurate for balanced loads. VOLTS MODE = 3W-Wye © 2007 Schneider Electric. All rights reserved. 13 PowerLogic ION7550 / ION7650 Installation Guide 3-Wire Solid-Grounded Wye, 3-Element, Direct Connection LOAD LINE Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source When the common or star point of a 3-wire Wye system is grounded, the meter may be connected directly without using PTs, provided that the phase voltages are within the meter’s range. VOLTS MODE = 4W-Wye 3-Wire Delta, 2½-Element, Direct Connection LOAD LINE A B C Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source 2A 3A Do not connect V1 V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52 G L / + N/- 600 V L-L max. VOLTS MODE = Delta 3-Wire Delta, 2-Element 2 PTs & 2 CTs LOAD LINE A B C Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source 3A 2A V1 V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52 G L / + N/- Use PTs for voltages over 600 V L-L. VOLTS MODE = Delta 14 © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide 3-Wire Delta, 2½-Element, 2 PTs & 3 CTs LOAD LINE A B C Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source 3A 2A V1 V2 V3 V4 Vref I11 I12 I21 I22 I31 I32 I41 I42 I51 I52 G L / + N/- Use PTs for voltages over 600 V L-L VOLTS MODE = Delta Single Phase Connection Diagram LOAD LINE Fuse for N/- terminal required if its supply source is ungrounded Connect G terminal to ground for AC power source I4 Optional 277 V L-N / 554 V L-L max. Use PTs for higher voltages. VOLTS MODE = Single Using Potential Transformers System Mode Wye Single Phase Delta Voltage Range 120 V L-N or 208 V L-L 277 V L-N or 480 V L-L 347 V L-N or 600 V L-L over 347 V L-N or 600 V L-L 120 V L-N or 240 V L-L 277 V L-N or 554 V L-L over 277 V L-N or 554 V L-L up to 600 V L-L over 600 V L-L © 2007 Schneider Electric. All rights reserved. Requires PTs no no no yes no no yes no yes 15 PowerLogic ION7550 / ION7650 Installation Guide Step 5: Wire the Communications RS-232 Connections (COM1) DB9 Null Modem Wiring Diagram DTE (computer) Specification DTE (meter) Meter Connected to Computer Connector Type Wire Maximum Cable Length Data Rate Isolation Duplex Compliance Null modem cable pinout Pin 3 - Transmit Data - Pin 2 Pin 2 - Receive Data - Pin 3 Pin 7 - Request to Send- Pin 8 Pin 8 - Clear to Send- Pin 7 Pin 5 - Signal Ground- Pin 5 Pin 6 - Data Set Ready- Pin 4 Pin 4 - Data Terminal Ready- Pin 6 Meter Connected to External Modem DB9 female end for mating with male connector on the meter Null modem RS-232 cable Straight-through RS-232 cable 15.2 m (50 ft) 300 – 115,200 bps Optical Full ANSI/IEEE C37.90.1-2002 surge withstand and fast transient tests RS-485 Connections (COM1 and COM2) SH – + RS-485 Shield (electrically connected to chassis ground) RS-485 Data Minus RS-485 Data Plus Connector Type Wire Maximum Cable Length Data Rate Maximum Devices (per bus) Isolation Duplex Connect SH at one end only Compliance Captured wire Shielded twisted pair RS-485 cable, 0.33 mm2 (22 AWG) or larger 1219 m (4000 ft) total for entire bus 300 – 115,200 bps 32 Optical Half ANSI/IEEE C37.90.1-2002 surge withstand and fast transient tests Infrared Connections (COM4) Interface Location Data Rate Duplex 16 ANSI C12.18 Type II optical port Front of meter 1,200 – 19,200 bps Half © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide Ethernet Connections (if equipped) 10BASE-T / 100BASE-TX Pin 1: Transmit Data + Pin 2: Transmit Data Pin 3: Receive Data + Pin 6: Receive Data - Wire Type Connector Type Maximum Length High quality Category 5 or 6 unshielded twisted pair cable RJ45 modular 100 m (328 ft) IEEE 802.3 10/100BASE-T for 10/100 Mbps base band CSMA/CD Type LANs Data Rate 10/100 Mbps Isolation Transformer isolated to 1500 V RMS Max. Connections Allowed 4 simultaneous (32 via Modbus TCP/IP) 100BASE-FX (Fiber) 62.5/125 or 50/125 micrometer multimode fiber optic cable Connector Type SC 2000 m (6562 ft) full duplex Maximum Length 400 m (1312 ft) half duplex Data Rate 100 Mbps Isolation Optical Wire Type SC type fiber cable Ethernet TCP/IP Service Ports Protocol Only one EtherGate connection per port is allowed at a time Port 7700 7701 502 7801 7802 20,000 25 (configurable) ION Modbus RTU Modbus TCP EtherGate (COM1) EtherGate (COM2) DNP TCP SMTP Internal Modem Connection (COM3 if equipped) Pin 3: Ring Pin 4: Tip Connector Type Wire Type Data Rate Error Correction Data Compression © 2007 Schneider Electric. All rights reserved. RJ11 FCC Part 68 compliant telephone cord (two male RJ11 ends) 300 bps – 56 kbps V.42 LAPM, MNP 2-4, V.44 V.42 bis/MNP 5 17 PowerLogic ION7550 / ION7650 Installation Guide Step 6: Wire the Power Supply Specification G L+ N_ Standard Power Supply Type Captured wire connector Wire 3.3-2.1 mm2 (12-14 AWG) Low Voltage DC 2.1-0.8 mm2 (14-18 AWG) 85-240 VAC ±10% (47-63 Hz), 20-60 VDC ±10% or 110-300 VDC ±10% Dielectric Withstand 2500 VAC RMS at 60 Hz for 60s Burden 35 VA max. (15 VA typical) 18 W max. (12 W typical) Ride-through 100 ms (6 cycles at 60 Hz) min. None Rated Inputs Step 7: Power Up the Meter 1. Ensure the ground wire is securely connected on both ends. 2. Ensure the meter’s power supply voltage is within the allowed range. 3. Power up the meter. Step 8: Set Up the Meter Using the Front Panel The following Setup screens are available for meter configuration via the front panel: BASIC SETUP COM1 SETUP COM2 SETUP COM3 SETUP COM4 SETUP NETWORK SETUP PQ SETUP FORMAT SETUP DISPLAY SETUP TIME SETUP SECURITY SETUP METER RESETS Use the PROG/SELECT, ESC, softkeys and arrow buttons to configure settings. The following example shows Volts Mode setup using the meter front panel. Press Press Press Press Press Press PROG/SELECT to enter Setup Mode from Display Mode. 18 Press Use arrow buttons to move up and down in list. Press PROG/SELECT to select Basic Setup. Use arrow buttons to move up and down in list. Press PROG/SELECT to select PT/CT Setup. Press Mode softkey. Use arrow buttons to move up and down in list. Press PROG/SELECT to select Delta. © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide Password A password is required for all front panel configuration changes and to enter the Security Setup menu. The password is set to 0 (zero) in the factory. The front panel only prompts you for the meter password once, before you make your first configuration change. You can disable the password via the Security Setup menu. Selecting the Front Panel Language Meters are shipped with English as the default front panel language. To select another language: 1. Press PROG/SELECT and the right arrow buttons, hold for two seconds then release. 2. Scroll through the language list and select the language you want. 3. Press PROG/SELECT to confirm. You can also access this setting via the Display Setup menu. NOTE The meter only communicates to software in English. © 2007 Schneider Electric. All rights reserved. 19 PowerLogic ION7550 / ION7650 Installation Guide Front Panel Setup Menu Settings The following table lists all settings that can be configured via the front panel. BASIC SETUP Menu Setting Description Default VOLTS MODE 4W-WYE PT PRIMARY The Potential Transformer’s primary 1 to 999,999.99 winding voltage rating 120.00 PT SECONDARY The Potential Transformer’s secondary winding voltage rating 1 to 999,999.99 120.00 CT PRIMARY The Current Transformer’s primary winding current rating 1 to 999,999.99 5.00 CT SECONDARY The Current Transformer’s secondary winding current rating 1 to 999,999.99 5.00 V4 PRIMARY The Potential Transformer’s primary 1 to 999,999.99 winding voltage rating on V4 120.00 V4 SECONDARY The Potential Transformer’s secondary winding voltage rating on V4 1 to 999,999.99 120.00 I4 PRIMARY The Current Transformer’s primary winding current rating on I4 1 to 999,999.99 5.00 I4 SECONDARY The Current Transformer’s secondary winding current rating on I4 1 to 999,999.99 5.00 I5 PRIMARY The Current Transformer’s primary winding current rating on I5 1 to 999,999.99 5.00 I5 SECONDARY The Current Transformer’s secondary winding current rating on I5 1 to 999,999.99 5.00 V NOMINAL The V1, V2 and V3 nominal voltage 1.000 to 999,999.000 used for harmonics calculations 120.00 V4 NOMINAL The V4 nominal voltage used for harmonics calculations 1.000 to 999,999.000 120.00 Va POLARITY The polarity of the Potential Transformer on Va Normal or Inverted Normal Vb POLARITY The polarity of the Potential Transformer on Vb Normal or Inverted Normal Vc POLARITY The polarity of the Potential Transformer on Vc Normal or Inverted Normal V4 POLARITY The polarity of the Potential Transformer on V4 Normal or Inverted Normal Ia POLARITY The polarity of the Current Transformer on Ia Normal or Inverted Normal Ib POLARITY The polarity of the Current Transformer on Ib Normal or Inverted Normal Ic POLARITY The polarity of the Current Transformer on Ic Normal or Inverted Normal I4 POLARITY The polarity of the Current Transformer on I4 Normal or Inverted Normal I5 POLARITY The polarity of the Current Transformer on I5 Normal or Inverted Normal CURRENT PROBE The type of current probes being TYPE used with the meter 20 Range (Values) The power system’s configuration – 4W-WYE, DELTA, 3W-WYE, WYE, DELTA, etc. SINGLE, DEMO Factory Default, User Defined 1, Factory or User Defined 2 Default © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide COM1 SETUP Menu Setting Description COM2 SETUP COM3 SETUP Default PROTOCOL The communications protocol BAUD RATE The data rate, in bits per second 3001, 1200, 2400, 4800, 9600, 19,200 19200, 38400, 57600, 115200 TRAN DELAY The transmit delay in seconds 0 to 1 UNIT ID Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number 0.010 From serial number2 SERIAL PORT Parity and stop bits for the port 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1 MODE Hardware mode for the port RS232 or RS485 RS232 RTS + DELAY or RTS/CTS RTS + DELAY Specifies the handshake mode FLOW CONTROL when COM1 is set to RS232 COM4 SETUP Range (Values) ION, Modbus RTU, Modbus Master, DNP V3.00, ION GPS:Truetime/Datum,GPS: Arbiter, GPS:Arbiter-Vorne, Factory, Ethergate, ModemGate RS485 BIAS Turns on biasing when Mastering on the RS-485 bus ON or OFF OFF PROTOCOL The communications protocol See COM1 protocol ION The data rate, in bits per second 3001, 1200, 2400, 4800, 9600, 19,200 0 to 1 0.010 BAUD RATE 19200, 38400, 57600, 115200 TRAN DELAY The transmit delay in seconds UNIT ID Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number SERIAL PORT Parity and stop bits for the port 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1 RS485 BIAS Turns on biasing when Mastering on the RS-485 bus ON or OFF OFF PROTOCOL The communications protocol ION, Modbus RTU, Modbus Master, DNP V3.00, GPS:Truetime/Datum,GPS: Arbiter, GPS:Arbiter-Vorne, Factory ION BAUD RATE The data rate, in bits per second 3001, 1200, 2400, 4800, 9600, 19,200 19200, 38400, 57600, 115200 TRAN DELAY The transmit delay in seconds 0 to 1 UNIT ID Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number 102 ANSWER HR RINGS The number of rings during defined 0 to 255 answer hours 1 NON-ANSWER HR RINGS The number of rings during defined 0 to 255 non-answer hours 5 101 0.010 PROTOCOL The communications protocol ION, Modbus RTU, DNP V3.00, Factory BAUD RATE The data rate, in bits per second 1200, 2400, 4800, 9600, 19200 9600 TRAN DELAY The transmit delay in seconds 0 to 1 0.010 UNIT ID Every meter on an RS-485 network 1 to 9999 must have a unique Unit ID number SERIAL PORT Parity and stop bits for the port © 2007 Schneider Electric. All rights reserved. ION 103 8N1, 8N2, 8E1, 8E2, 8O1, 8O2 8N1 21 PowerLogic ION7550 / ION7650 Installation Guide NETWORK SETUP Menu Setting Description PQ SETUP FORMAT SETUP Default IP ADDRESS Sets the IP address for the meter SUBNET MASK Used if subnetting applies to your network 000.000.000.000 to 999.999.999.999 255.240.0.0 GATEWAY Used in multiple network configurations 000.000.000.000 to 999.999.999.999 0.0.0.0 DNS PRIMARY Sets the address for the primary DNS Server that is configured to resolve domain names 000.000.000.000 to 999.999.999.999 none DNS SECONDARY Sets the address for the secondary DNS Server that is configured to resolve domain names 000.000.000.000 to 999.999.999.999 none 10/100BT CONFIG Sets the BASE-T Ethernet max. link speed and duplexing Auto, 10BT half, 10BT full, 100BTX half, 100BTX full Auto Full Duplex or Half Duplex Full Duplex 100BFX CONFIG Sets the Fiber Ethernet duplexing 22 Range (Values) 000.000.000.000 to 999.999.999.999 varies3 SNMP SERVER Determines whether SNMP protocol Enabled or Disabled is enabled on the meter or not Disabled SWELL LIMIT Specifies the magnitude above which an input must rise for a swell 100 to 1000 to be recorded 106 SAG LIMIT Specifies the magnitude below which an input must fall for a sag to 0 to 100 be recorded 88 CHANGE CRITERIA Specifies the amount by which an input must change during a 0 to 100 disturbance to be considered a new sub-disturbance 10 NOMINAL VOLTAGE4 Specifies the nominal voltage of the 0 to 1,000,000 power system 0 EVENT PRIORITY Assigns a priority level to sag/swell events 0 to 255 200 DIGIT GROUP Specifies symbols used to delimit thousands & decimal place holder 1000.0 or 1,000.0 or 1000,0 1000.0 VOLTS DECIMAL Number of decimal places displayed for voltages 1. to 123456789.XXX 1.XX CURRNT DECIMAL Number of decimal places displayed for currents 1. to 123456789.XXX 1.XXX POWER DECIMAL Number of decimal places 1. to 123456789.XXX displayed for power measurements 1.XXX MEAS SYMBOL Specifies the convention used for displaying measurements IEEE or IEC IEEE PHASE LABEL Specifies how phases are labelled ABC, RST, XYZ, RYB, RWB, 123 ABC PF SIGN Specifies the power factor sign convention used IEEE or IEC IEEE PF SYMBOL Sets how power factor is labelled (LD = leading/LG = lagging) LD/LG, +/-, CAP/IND LD/LG DATE FORMAT Specifies how dates are displayed MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD MM/DD/ YYYY TIME FORMAT Specifies whether time is displayed 12 H or 24 H in 12 hour or 24 hour clock format 24 H DISPLAY DST Specifies whether or not DST is displayed Yes Yes or No © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide Menu Setting Description SECURITY SETUP TIME SETUP DISPLAY SETUP UPDATE RATE Range (Values) Default Sets when the display updates 1 to 6 (seconds) 1 CONTRAST Higher numbers are sharper 0 to 9 7 DELTA VECTORS Specifies how vector diagrams are displayed when in Delta mode System or Instrument System LANGUAGE Specifies the language used on the meter’s front panel English, Spanish, French, Russian English TZ OFFSET Sets the time zone of the meter’s location, relative to UTC - 12:00 to +13:00 +00:00 DST OFFSET Sets the daylight savings time offset -3:00 to +3:00 of the meter’s location +00:00 SYNC SOURCE Sets the port to receive time synchronization signals Ethernet, COM1, COM2, COM3, COM4 COM1 SYNC TYPE Specifies whether time sync signals are received in local time or UTC Local Time or UTC UTC CLOCK SOURCE Specifies time sync source Internal, Line Freq or COMM Line Freq LOCAL DATE Sets the local date Same as Date Format setting LOCAL TIME Sets the local time PASSWORD Sets the meter password 00000000 to 99999999 00000000 ENABLED Enables or disables meter security Yes or No No WEB CONFIG Enables or disables web browser configuration of the meter Enabled or Disabled Enabled WEB ACTIVE Enables or disables internal web server on the meter Yes or No Yes 1 A baud rate of 300 bps is only intended for paging applications. 2 Serial number = PA-0302B222-01, Unit ID = 2222 3 Default IP ADDRESS = 172.16.xxx.xxx, where the last two bytes (decimal) match the last two bytes of the meter’s MAC address (hex). 4 NOMINAL VOLTAGE must be set to your system’s nominal voltage to activate the meter’s power quality features. Step 9: Verify Meter Operation The LEDs on the back of the meter flash during communications. LED Color Function Ethernet 100 (Speed) Green Off = link at 10 Mb, On = link at 100 Mb Ethernet TX Green Blinking indicates Ethernet transmission Ethernet RX/LINK Green On = link up, Off = link down Blinking indicates Ethernet reception Modem DCD Green Indicates a carrier signal is detected (active connection to the modem) Modem RI Green Indicates a ring is detected by the modem COM3 (Modem) TX Yellow Indicates serial transmission on COM3 COM3 (Modem) RX Yellow Indicates serial reception on COM3 COM2 TX Yellow Indicates serial transmission on COM2 COM2 RX Yellow Indicates serial reception on COM2 COM1 TX Yellow Indicates serial transmission on COM1 COM1 RX Yellow Indicates serial reception on COM1 © 2007 Schneider Electric. All rights reserved. 23 PowerLogic ION7550 / ION7650 Installation Guide The LEDs on the front panel indicate the following: Top (green) LED indicates the meter is operational. The light should always remain on when the meter is in service. Middle (red) LED is a watt-hour pulser. During normal operations this LED should blink intermittently as the meter measures power. Watt-hour pulsing Bottom (red) LED is user programmable. It can be used for Alarm notification. See the ION7550 / ION7650 User Guide for more information. Front Panel Phasor Diagrams You can also view the meter’s phasor diagram in real time. Use the Phasor Viewer available in PowerLogic ION Setup v2.1 and later (free download from the PowerLogic website) to verify your meter’s wiring. See the ION Setup online help for details. NOTE The following DELTA phasor diagrams are represented in System mode view. DELTA phasors for UNITY Power Factor (resistive load) Applicable Volts Mode = DELTA VBC VCA IC IB IA ACB Rotation ABC Rotation VAB IB IA VAB IC VBC 24 VCA © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide WYE - ABC Rotation Applicable Volts Mode = 4W-WYE and 3W-WYE IB VA IA Q1: Lagging PF (-) VC IC Rotation Rotation Reactive Power VC +kVAR Q2: Leading PF (+) VA IB IC VB IA VB Active Power Active Power +kW -kW Q3: Lagging PF (-) Q4: Leading PF (+) VC VC -kVAR VB IC Rotation VA Reactive Power Rotation IB IA IA IC VA VB IB WYE - ACB Rotation Applicable Volts Mode = 4W-WYE and 3W-WYE IC VA IA Q1: Lagging PF (-) VB IB Rotation Rotation Reactive Power VB +kVAR Q2: Leading PF (+) VA IC IB VC IA VC Active Power Active Power +kW -kW Q3: Lagging PF (-) Q4: Leading PF (+) VB VB IB © 2007 Schneider Electric. All rights reserved. -kVAR VC Rotation VA Reactive Power Rotation IC IA IB IA VA IC VC 25 PowerLogic ION7550 / ION7650 Installation Guide 2 Element (3Wire) DELTA - ABC Rotation Applicable Volts Mode = DELTA VCA IB VAB IA Q1: Lagging PF (-) VCA IC Rotation Rotation Reactive Power +kVAR Q2: Leading PF (+) IB VAB IC IA VBC VBC Active Power Active Power +kW -kW Q3: Lagging PF (-) Q4: Leading PF (+) VCA VCA IA IC -kVAR IC VBC IA Rotation IB Reactive Power Rotation VAB VAB IB VBC 2 Element (3Wire) DELTA - ACB Rotation Applicable Volts Mode = DELTA IB VAB Q1: Lagging PF (-) VBC IB Rotation Rotation IC Reactive Power +kVAR Q2: Leading PF (+) VBC VAB IA IC IA VCA VCA Active Power Active Power +kW -kW Q3: Lagging PF (-) Q4: Leading PF (+) VBC VBC IA VAB VCA 26 -kVAR IB Reactive Power Rotation IA Rotation IC VAB IB IC VCA © 2007 Schneider Electric. All rights reserved. PowerLogic ION7550 / ION7650 Installation Guide Step 10: View Meter Data Use the softkeys to select which data to display. Use the left and right arrow buttons to scroll through the available display screens. Display Screens Softkey V,I,PF Volts Amps Power Energy1 Demand1 Pk Dmd1 V Bar, I Bar, P Bar Summary1, Summary2 D Inputs DI - I/O D-Output Anlg - I/O Phasors Name Plt Events Setpoint Energy2 Demand2 Pk Dmd2 THD V1 Harm, V2 Harm,... I1 Harm, I2 Harm,... TOU TOU Egy TOU Dmd1 & TOU Dmd2 *PQ Freq *PQ Vmag1 *PQ Vmag2 *PQ Flk1 *PQ Flk2 *PQ Vdist *PQ Vunb *PQ Vhrm1 *PQ Vhrm2 V-Trend, I-Trend, P-Trend * Contents Volts, Amps, Power Factor Volts Amps Total Power Energy delivered Demand delivered Peak Demand delivered Voltage, Current and Power Bar Graphs Volts/Amps Summary, Power Summary Digital Inputs Digital I/O on expansion I/O card Digital Outputs Analog In and Out Phasors Nameplate information Events Setpoint status Energy received Demand received Peak Demand received Volts and Amps Total Harmonic Distortion V1, V2, V3, V4 harmonics I1, I2, I3, I4, I5 harmonics Time Of Use Active Rate / Season TOU Energy delivered TOU Peak Demand 1 and 2 Power Quality Power Frequency PQ Supply Voltage 1 PQ Supply Voltage 2 PQ Flicker 1 PQ Flicker 2 PQ Voltage Disturbance PQ Voltage Unbalance PQ Voltage Harmonics 1 PQ Voltage Harmonics 2 Voltage, Current, Power Trends Additional display screens for ION7650 meters with EN50160 option. © 2007 Schneider Electric. All rights reserved. 27 PowerLogic ION7550 / ION7650 with WebMeter and MeterM@il Installation Guide For further assistance please contact us at: Schneider Electric Power Monitoring and Control 2195 Keating Cross Road Saanichton, BC Canada V8M 2A5 Tel: 1-250-652-7100 295 Tech Park Drive, Suite 100 Lavergne, TN 37086 USA Tel: 1-615-287-3400 Electropole (38 EQI) 31, rue Pierre Mendès France F - 38050 Grenoble Cédex 9 Tel : + 33 (0) 4 76 57 60 60 Getting technical support: Contact your local Schneider Electric sales representative for assistance or go to the www.powerlogic.com website. PowerLogic, ION, ION Enterprise, MeterM@il, WebMeter and Modbus are either trademarks or registered trademarks of Schneider Electric. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 70002-0247-10 © 2007 Schneider Electric. All rights reserved. 12/2007
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : No Page Mode : UseOutlines XMP Toolkit : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39 Producer : Acrobat Distiller 8.0.0 (Windows) Creator Tool : FrameMaker 7.1 Modify Date : 2007:12:10 10:39-08:00 Create Date : 2007:12:10 10:31:11Z Metadata Date : 2007:12:10 10:39-08:00 Format : application/pdf Title : PowerLogic ION7550 / ION7650 Installation Guide Creator : Schneider Electric Document ID : uuid:905f310e-337b-49c7-8f48-6922ce5746cd Instance ID : uuid:3186533f-5433-40ac-9094-e4019f35bcaa Has XFA : No Page Count : 28 Author : Schneider ElectricEXIF Metadata provided by EXIF.tools