Schweitzer Engineering Laboratories 900FT50 SEL-FT50 User Manual FT50 FR12 IM 20170317

Schweitzer Engineering Laboratories, Inc. SEL-FT50 FT50 FR12 IM 20170317

User Manual

Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemAccelerate Tripping, Speed Up Restoration, and Improve Safety on Distribution FeedersMajor Features and BenefitsThe SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System speeds up distribution-protection schemes by detecting and transmitting distribution feeder fault information to recloser controls or relays. Install the SEL-FT50 Fault Transmitters on laterals, branches, and the main line to broadcast fault status to one or more SEL-FR12 Fault Receivers. The SEL-FR12 communicates the fault data through MIRRORED BITS® communications to a relay or recloser control within 6 ms.➤Real-Time Distribution Fault Detection. Identify the faulted line segment with fault detection and low-latency communication while a fault is still active; for use in protection schemes.➤Enhanced Protection. Make real-time changes to the protection strategy based on information from the faulted distribution-line segment.➤Improved Selectivity. Trip a main feeder or branch recloser only when necessary. Avoid unnecessary entire-feeder outages.➤Customized Reclosing Strategies. Block or enable reclosing for specific line segments.➤Improved Power Quality, Reduced System Stress, Limited Equipment Damage, and Enhanced Safety. Leverage faulted feeder status to better coordinate between protective elements, leading to faster trip times.➤Easy Operation. Configure the fault transmitters and receiver without additional software.➤No Batteries. Power the SEL-FT50 directly from the line because batteries are not necessary.➤Easy Installation. Install the SEL-FT50 on live lines by using familiar line tools and techniques.➤Flexible Integration. Install the SEL-FT50/SEL-FR12 system in an existing relay protection system.SEL-FT50/SEL-FR12Fault Transmitter and Receiver System
2SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317Functional OverviewFunctional OverviewThe SEL-FT50/SEL-FR12 system consists of as many as twelve SEL-FT50 Fault Transmitters and one SEL-FR12 Fault Receiver. The SEL-FT50 is mounted on distribution conductors with voltages as high as 38 kV. The SEL-FR12 is mounted in a recloser control cabinet or in a substation control house.When one or more SEL-FT50 Fault Transmitters detect a fault, they send a wireless signal to the SEL-FR12. The SEL-FR12 transfers the received signal to the recloser control or relay via MIRRORED BITS communications in as little as 6 ms. The recloser control uses the fault information to make protection or relay decisions.To monitor the health of the system, the SEL-FT50 Fault Transmitters periodically send communication link-check messages to the SEL-FR12 to indicate their status.System OverviewFigure 1 provides an overview of the SEL-FT50/SEL-FR12 system and illustrates how to apply it across a distribution power system.Serial Port MIRRORED BITSEncoder12-ChannelReceiverSEL-FR12 Fault ReceiverReceiveMIRRORED BITS OutputOverhead ConductorSEL-FT50 Fault TransmitterSignal andEnergy HarvestFaultSenseLink-CheckTimerPowerCircuitRadioTransmit
3Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSystem OverviewFigure 1 SEL-FT50/SEL-FR12 SystemThe SEL-FT50/SEL-FR12 system components are easy to use, and they contain many powerful and innovative features. Use programmable logic in the SEL-651R or in connected relays to incorporate the new protection capabilities and achieve the benefits shown in Figure 1.Figure 2 SEL-FT50 OverviewEach SEL-FT50 mounts onto and monitors the line current on one phase. When a fault occurs, the SEL-FT50 transmits a high-speed wireless signal to influence protection decisions. Control (DIP) switches inside the transmitter allow easy selection of unit and Network IDs. No batteries are needed because the SEL-FT50 is powered by the line current.Protective DeviceSEL-651RSEL-FR12SEL-FT50MIRRORED BITSDistributionSystemCollection ProtectionLogic•  Collect wireless      signals simultaneously     from as many as 12     fault transmitters •  Monitor as many as 4     three-phase branchesSEL-FT-50/SEL-FR12System Benefits•  Speed up protection•  Improve power quality•  Protect equipment•  Enhance safetyHot stick loopCurrent transformerTwistlock housing for setting accessOmnidirectional antenna for the radio transmitterSpring for secure installationConductor stopLeft control (DIP)switch bankSW 1–4 Unit IDSW 5–8 Network IDRight control (DIP)switch bankSW 6–8 fault pickup
4SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317System OverviewFigure 3 SEL-FR12 OverviewThe SEL-FR12 collects wireless signals simultaneously from as many as 12 SEL-FT50 Fault Transmitters (enough for 4 three-phase installations). The SEL-FR12 reports faults to a relay or recloser control in less than 6 ms via MIRRORED BITS. The SEL-FR12 HMI contains 29 LEDs and 1 pushbutton, as shown in Figure 3.➤The ENABLED LED illuminates green when the SEL-FR12 is turned on and operational.➤The 12 FAULT LEDs (red, one per Unit ID) illuminate after the SEL-FR12 receives a Fault message from the associated SEL-FT50. These LEDs have a latching behavior so that once set, they remain on until reset by the TARGET RESET pushbutton or via MIRRORED BITS command.➤The 12 LINK LEDs (green, one per Unit ID) have a tristate operation:➢LINK LEDs are initially off when the SEL-FR12 is turned on or after it receives a clear link status command via MIRRORED BITS. ➢LINK LEDs illuminate when the SEL-FR12 receives consecutive Link messages or one Fault message from the associated SEL-FT50. These LEDs have a delayed dropout behavior. Once illuminated, they remain illuminated as long as Link signals are periodically received.➢LINK LEDs begin to flash after one minute elapses without receipt of a Link message for the associated Unit ID. When Link or Fault signals resume, the LINK LED stops flashing and stays illuminated once again.ENABLEDLEDFAULT and LINKstatus LEDsMIRRORED BITSstatus LEDsTARGET RESETpushbuttonSerial port(DB-9 connector)Power supplyinput (9–30 Vdc)Control (DIP) switches to select:  •  Network ID—SW 1–4  •  Baud rate—SW 5–6  •   MIRRORED BITS TX and RX ID—SW 7–10  •  Near/distant SEL-FT50—SW 11–14Radio antennaBNC connectorGrounding lug
5Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemApplication Examples➤The ROK, TX, RX (green), and LOOP (red) LEDs indicate MIRRORED BITS status and activity. The ROK LED illuminates when MIRRORED BITS data exchange is successful.➤The TARGET RESET pushbutton resets the FAULT LEDs. Press and hold the pushbutton to illuminate all HMI LEDs (lamp test function).                      Application ExamplesCollect Fault Information From Remote BranchesA traditional recloser control or substation circuit breaker must be coordinated with the other protective devices on a distribution feeder, including fuses on downstream line segments. On the sample feeder in Figure 4, the recloser control or substation relay cannot distinguish one segment from another.Figure 4 Typical Recloser VisibilityThe SEL-FT50/SEL-FR12 system offers increased visibility to a recloser control by providing fault status from locations as far away as two miles. Figure 5 illustrates how this allows the recloser control to see faults on individual branches, including locations where it is not economically feasible to install a relay or recloser. Each SEL-FT50 label in Figure 5 represents three SEL-FT50 Fault Transmitters, one per phase.Table 1 Target and Status LED DefinitionsLED (Color) Off Flashing On Reset MethodsFAULT (red) target No fault signal has been received from the corresponding Unit ID since the last reset.Not applicable. The SEL-FR12 received a fault signal from the cor-responding Unit ID since the last reset.Manual—resets via the TARGET RESET pushbutton.Remote—resets via MIR-RORED BITS.LINK (green) status The SEL-FR12 has not detected an SEL-FT50 with the corresponding Unit ID since initializa-tion.This learning feature keeps unused LINK LEDs turned off.The SEL-FR12 is not presently receiving sig-nals from the previously learned Unit ID, indicat-ing that an SEL-FT50 is not harvesting energy during low-current condi-tions or an outage.The SEL-FR12 has received signals from the corresponding Unit ID within the last minute, indicating that the SEL-FT50 is receiving minimum radio link active current.Automatic—learning mode resets automatically after the SEL-FR12 turns on.Remote—resets via MIR-RORED BITS.R????
6SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317Application ExamplesFigure 5 Recloser Communication With Fault TransmittersEach SEL-FT50 monitors line current and instantly transmits a wireless signal when an overcurrent (fault) condition occurs. The companion SEL-FR12 receives and aggregates fault data from as many as 12 SEL-FT50 Fault Transmitters. Upon detecting a fault indication signal, the SEL-FR12 communicates the fault information to the host SEL-651R recloser control, or other SEL protective relay, by using MIRRORED BITS communications.The SEL-FT50/SEL-FR12 system allows the protective relay or recloser control to make intelligent decisions by using high-speed fault information from remote locations.Improve Fuse CoordinationIn a radial distribution system, there are two main schemes that control fuse coordination: fuse-saving and fuse-blowing (also called trip-saving). Each of these schemes has shortcomings that you can address with the SEL-FT50/SEL-FR12 system.Figure 6 gives a representation of a typical time-overcurrent coordination graph.RWirelessSEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FR12SEL-651R-2
7Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemApplication ExamplesFigure 6 Example Time-Overcurrent Element CoordinationFuse-Blowing Scheme Shortcomings For a radial distribution system, the goal of the fuse-blowing scheme is to minimize the number of customers exposed to an interruption. The scheme accomplishes this by allowing a fuse to clear a given fault. The recloser only trips for faults that are not protected by a fuse. This scheme is sometimes called a trip-saving or fuse-blowing scheme because the recloser only trips when absolutely necessary.Refer to Figure 6 for the recloser control time-overcurrent element slow curve (shown in red). This curve must coordinate with the highest-rated fuse size present on the system, which is shown in green. An intentional coordination margin allows for prefault load and variances in fuse construction.For faults on sections of the feeder that are not fuse-protected, the recloser must still implement this intentional coordination margin. The recloser control cannot determine which downstream branch the fault is on and assumes that the fault will be cleared by a fuse. Figure 7 shows an example of a main line feeder and a fused lateral without a fuse. For a fault on the main line, the recloser control will wait before using the slow curve to clear the fault (see Figure 6). For a fault on the main line, the recloser control delays tripping unnecessarily because there is no fuse present.Figure 7 Fault on Unfused Tap Recloser ControlFast CurveRecloser ControlSlow CurveFuse-Melting CurveFuse-Clearing Curve0.010.1110100100Current (A)1,0001,000Time (s)R
8SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317Application ExamplesImprove Fuse-Blowing Schemes With the Fault Transmitter and Receiver SystemWith the SEL-FT50/SEL-FR12 system installed as shown in Figure 8, the recloser control receives an indication whenever a fault is on the unfused branch. With this information, if a fault occurs on the unfused line section, the recloser control can trip instantaneously instead of waiting for the fuse delay.In Figure 8, the unfused tap is monitored by a set of SEL-FT50 Fault Transmitters (one for each phase), one SEL-FR12, and one SEL-651R. The SEL-FR12 is connected to the SEL-651R via a serial port.Figure 8 SEL-FT50 on Unfused Tap When using the SEL-FT50/SEL-FR12 system, the SEL-651R knows when a fault occurs on the unfused tap because one or more of the SEL-FT50 Fault Transmitters detect the fault current and send the fault status to the SEL-FR12, which then conveys the information to the recloser control.The SEL-651R settings replace or modify the curve behavior while the fault is happening. In the example fault shown in Figure 8, the recloser control enables the recloser control fast curve (see Figure 6). Compare this to when a fault is on the same unfused line section but the recloser control does not know it. The recloser trips after a delay. Based on the coordination curves in Figure 6, for a 1000 A fault, using the SEL-FT50/SEL-FR12 system to trip on the fast curve instead of the slow curve reduces the fault clearing time by 400 ms. Fuse-Saving Combined With Fuse-Blowing SchemesThe fundamental choice in distribution-line protection is between fuse-saving and fuse-blowing. For a given fault, designers either favor blowing fuses and disrupting as few customers as possible, or tripping the recloser and interrupting the fault without blowing any fuses. Each method has its advantages, but the protection planner has to pick one or the other.Using the SEL-FT50/SEL-FR12 system, design smart protection that switches from fuse-saving to fuse-blowing, or vice versa without interruption. You get the fuse-saving or fuse-blowing benefits you want while eliminating any drawbacks.The following two example applications show how a single protective zone using the SEL-FT50/SEL-FR12 system allows both fuse-saving and fuse-blowing schemes in service.Example 1: Switchover Without Interruption From a Fuse-Blowing Scheme to a Fuse-Saving SchemeIn this switchover scheme, utilities have the option to tailor protection for specific line segments with different characteristics. If the SEL-FT50 declares that a fault is present on a candidate line section, the scheme enables fuse-saving while the fault is in progress. For other faulted line segments, the fuse-blowing scheme works as intended.RSEL-FR12SEL-651R-2When the fault is on the unfused branch, the recloser trips without fuse-coordination delay.SEL-FT50
9Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemApplication ExamplesExample 2: Switchover Without Interruption From a Fuse-Saving Scheme to a Fuse-Blowing SchemeIn this switchover scheme, the SEL-FT50/SEL-FR12 system is used to indicate which line section contains a fault. However, the fuse-saving scheme is the default operating mode. When the SEL-FT50 declares that a fault is present on a candidate line section, the scheme enables fuse-blowing while the fault is in progress. For other faulted line segments, the fuse-saving scheme works as intended.Improve Feeder Cable First-Span ProtectionThe SEL-FT50/SEL-FR12 system improves first-span feeder cable protection. Feeder cables are often used for substation egress, eliminating overhead line clutter and improving working safety. These feeder cables radiate from a substation, continuing for a few feet to one mile. These cables are usually terminated on a riser pole and then connected to the overhead conductors.To protect cable sections, some utilities use instantaneous overcurrent elements with pickup levels set to cover the entire cable length, plus some margin that overreaches onto a portion of the overhead line. In these applications, a high-current fault causes an instantaneous trip with no reclosing permitted.While this approach protects equipment, it also often causes an unnecessary permanent outage when the fault is on the portion of the overhead line where available fault levels are still very high. The majority of overhead faults are caused by temporary events and are far more likely to occur than underground faults. By not reclosing for close-in overhead faults, the entire feeder suffers a permanent outage that could have been avoided.To improve the first-span feeder cable protection, use a set of three SEL-FT50 Fault Transmitters to monitor the first span of overhead line, as shown in Figure 9. When an overhead fault occurs, the relay instantaneous element trips the recloser or feeder breaker, but reclosing is allowed when the SEL-FT50 signals that the fault is on the overhead portion of the feeder. This simple modification of an existing scheme improves system availability. This application extends to any line that transitions between overhead and underground lines. Knowing whether a fault is on an overhead or underground section of a feeder helps when coordinating reclosing and protection schemes.Figure 9 Feeder Cable Egress Protection With EnhancementsSEL-FR12RelayBreakerSubstation busSubstationUndergroundfeeder cableWirelessRiser pole Overhead conductorSEL-FT50
10SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317Safety InformationTripping the Right Recloser FasterYou can protect a distribution feeder with multiple reclosers. In a radial system, to optimize selectivity, users want the recloser closest to the fault to operate for that fault. For this reason, reclosers at the end of the distribution line are set to trip first and the close-in reclosers are set to delay their tripping. Figure 10 shows a fault in Zone R1. In a conventional protection design, assuming the reclosers use a fuse-blowing scheme, R1 clears this fault, but only after it gives Zones R2, R3, and R4 a chance to operate. This situation results in a long fault duration that stresses the system and impacts the power quality on other substation loads.Figure 10 Radial Distribution Line With Multiple ReclosersFix this problem by using an SEL-FT50/SEL-FR12 system. In Figure 10, the SEL-FT50 detects the fault and immediately transmits the information to the SEL-FR12, which then sends this information to the recloser control at R1. Because R1 knows that the fault is in its zone, it trips without waiting for the downstream reclosers, avoiding the unnecessary coordination delay.Safety InformationRegulatory InformationThe SEL-FT50 is approved for use only with specific output power configurations that have been tested and approved. Modifications to the SEL-FT50, the SEL-FR12, the antenna system, and the power output that have not been explicitly specified by the manufacturer are not permitted and may render the radio noncompliant with applicable regulatory authorities. The radio equipment described in this manual emits radio frequency energy. Professional installation is required.This equipment has been tested and found to comply with the limits for Class A digital devices, pursuant to FCC Part 15 Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and radiates radio frequency energy, and if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communication. Operation of this equipment in a residential environment is likely to cause harmful interference, in which case the user will be required to correct the interference at his/her own expense.R1SEL-FR12SEL-651R-2R2 R3 R4SEL-FT50CAUTIONAlthough the power level is low, concentrated energy from a directional antenna may pose a health hazard. Do not allow users to come closer than 23 cm (9 in) to the transmitter when it is operating.DANGERInstall fault transmitters and sensors in accordance with normal safe operating procedures. These instructions are not intended to replace or supersede existing safety or operating requirements. Only trained qualified personnel with knowledge of high voltage safety should install or operate fault transmitters.
11Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSafety InformationDangers, Warnings, and CautionsThis manual uses three kinds of hazard statements, defined as follows:Safety Symbols The following symbols apply to this device.                     Safety Marks The following statements apply to this device.                     This device complies with Industry Canada license-exempt RSS stan-dard(s). Operation is subject to the fol-lowing two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de brouillage ; (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en com-promettre le fonctionnement.DANGERIndicates an imminently hazardous situation that, if not avoided, will result in death or serious injury.WARNINGIndicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.CAUTIONIndicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury or equipment damage.                     CAUTIONRefer to accompanying documents.ATTENTIONSe reporter à la documentation.                      Protective earth (ground) Terre de protection                      Direct current Courant continu                      Instruction manual Manuel d’instructionsDANGERDisconnect or de-energize all external connections before opening this device. Contact with hazardous voltages and currents inside this device can cause electrical shock resulting in injury or death.DANGERDébrancher tous les raccordements externes avant d’ouvrir cet appareil. Tout contact avec des tensions ou courants internes à l’appareil peut causer un choc électrique pouvant entraîner des blessures ou la mort.DANGERContact with instrument terminals can cause electrical shock that can result in injury or death.DANGERTout contact avec les bornes de l’appareil peut causer un choc électrique pouvant entraîner des blessuers ou la mort.WARNINGUse of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment.AVERTISSEMENTL’utilisation de cet appareil suivant des procédures différentes de celles indiquées dans ce manuel peut désarmer les dispositifs de protection d’opérateur normalement actifs sur cet équipement.WARNINGHave only qualified personnel service this equipment. If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage.AVERTISSEMENTSeules des personnes qualifiées peuvent travailler sur cet appareil. Si vous n’êtes pas qualifiés pour ce travail, vous pourriez vous blesser avec d’autres personnes ou endommager l’équipement.
12SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317System InstallationSystem InstallationSEL-FR12 The SEL-FR12 uses two 10-position control (DIP) switches to set the wireless network identification (Network ID) of the associated SEL-FT50 Fault Transmitters, the baud rate and addresses for the MIRRORED BITS serial communications port, and the separate receiver gain values for the SEL-FT50 Fault Transmitters.The control (DIP) switch assignments are listed on the SEL-FR12 enclosure. The switch positions are labeled 1 through 20, but only 1 through 14 are used.Physical InstallationInstall the SEL-FR12 first for easier commissioning when you install the SEL-FT50 Fault Transmitters.For simplest installation, place the SEL-FR12 inside the recloser control cabinet, powered by the 12 Vdc auxiliary power supply of the SEL-651R. However, it can be installed with any device that communicates through MIRRORED BITS. The SEL-FR12 must be connected to an antenna that is outside the recloser control cabinet and can connect to a coaxial cable run with proper grounding and lightning protection devices. The antenna is typically mounted higher up on the pole in a safe location. The appropriate antenna type is site-specific. Perform a path study before choosing the antenna.The SEL-FR12 serial port connects to one of the serial ports of the SEL-651R that are configured for SEL MIRRORED BITS communications. This connection allows the SEL-FR12 to share the received fault with the recloser control. The programmable logic of the recloser control is configured to incorporate the received data as part of the protection or control decisions.Installation details differ slightly for SEL-FR12 Fault Receivers placed in substations.Refer to the SEL Radios Accessories Guide on the SEL website for a complete list of radio accessories offered by SEL.Mounting the SEL-FR12Use the accessory kit hardware to mount the SEL-FR12 in the recloser control cabinet. When ordered as an accessory to the SEL-651R, the unit comes pre-installed without wiring as part of the cabinet.Chassis Ground and Power ConnectionConnect the rear-panel grounding terminal (labeled with the ground symbol) to a rack frame ground or main station ground for proper safety and WARNINGDo not perform any procedures or adjustments that this instruction manual does not describe.AVERTISSEMENTNe pas appliquer une procédure ou un ajustement qui n’est pas décrit explicitement dans ce manuel d’instruction.CAUTIONEquipment components are sensitive to electrostatic discharge (ESD). Undetectable permanent damage can result if you do not use proper ESD procedures. Ground yourself, your work surface, and this equipment before removing any cover from this equipment. If your facility is not equipped to work with these components, contact SEL about returning this device and related SEL equipment for service.ATTENTIONLes composants de cet équipement sont sensibles aux décharges électrostatiques (DES). Des dommages permanents non-décelables peuvent résulter de l’absence de précautions contre les DES. Raccordez-vous correctement à la terre, ainsi que la surface de travail et l’appareil avant d’en retirer un panneau. Si vous n’êtes pas équipés pour travailler avec ce type de composants, contacter SEL afin de retourner l’appareil pour un service en usine.
13Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSystem Installationperformance. Use 4 mm2 (12 AWG) or heavier wire of less than 2 meters (6.6 feet) for this connection. Make the ground connection before making the power connections.Connect the power harness to a fused 12 V auxiliary power supply terminal on the SEL-651R, paying attention to polarity.If possible, turn on the SEL-FR12 and verify that the ENABLED LED illuminates. Turn it off before continuing.Connect the Serial PortUse a short cable, such as the SEL-C272, to connect the serial output of the SEL-FR12 to the recloser control or relay serial port that has been configured for MIRRORED BITS operation.Turn on the SEL-FR12 and verify that the ROK LED illuminates. If ROK does not assert, check the SEL-FR12 MIRRORED BITS Speed and Address switches and compare them with the MIRRORED BITS port settings of the host device. Turn it off before continuing.Feed Lines The feed line used with the antenna is important. Use coaxial cables that have low attenuation and are rated for outdoor use. Keep the feed line as short as possible to minimize signal loss between the radio and antenna. RG8X or LMR-400 coaxial cables are preferred. If longer lengths or less cable loss is desired for the radio link, then you can use a larger cable, such as a 7/8-inch HELIAX. Table 2 lists the signal losses for the indicated lengths of each cable type.Antenna System Ground Antenna system grounding is not included in the scope of this manual. Please consult a radio systems engineer or other professional for advice on ground-system design, and read AG2014-36, Radio System Lightning Protection Best Practices, which can be found on the SEL website. A well-designed system will minimize equipment damage and risk of electric shock to personnel.Setting Network IDTo enable multiple wireless fault transmitter and fault receiver systems to operate in close proximity, both the SEL-FT50 and SEL-FR12 feature a Network ID selection (1–16). See Figure 11 for an example of two networks.The SEL-FR12 will only receive transmissions from SEL-FT50 Fault Transmitters that match its Network ID.Each SEL-FT50 contain configuration switches to select one of sixteen network identification numbers. The SEL-FR12 also has Network ID Table 2 Length vs. Loss in Coaxial Cables at 900 MHzCable Type Characteristic Impedance3.05 Meters(10 Feet)12.24 Meters(50 Feet)30.48 Meters(100 Feet)91.44 Meters(300 Feet)RG-8X(SEL-C964, SEL-C975)50 :0.70 dB 3.50 dB 7.0 dB Unacceptable lossLMR-400(SEL-C966, SEL-C968)50 :0.39 dB 1.95 dB 3.90 dB Unacceptable loss7/8-inch HELIAX(SEL-C978)50 :Do not use 0.64 dB 1.28 dB 3.84 dB
14SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317System Installationconfiguration switches and will only accept received SEL-FT50 messages that have a matching Network ID.For example, if three distribution feeders emanate from one substation, each with their own SEL-FT50/SEL-FR12 system, these systems operate independently if they have unique Network IDs.Figure 11 Two-Network ExampleOnce you have determined the Network ID to be used, set control switches to the appropriate positions, as shown in Figure 12.Figure 12 Network ID Switch SelectionSerial Port SettingsConfigure the desired serial port baud rate through use of the control switch positions.For best performance, choose the highest speed that matches the available MIRRORED BITS speed on the connected device. Set the transmit address (TX_ADD) of the SEL-FR12 to match the receive address of the connected device. Set the receive address (RX_ADD) of the SEL-FR12 to match the receive transmit of the connected device. Figure 13 outlines the control switch settings. Do not set the TX and RX addresses of each device to the same number because the SEL-FR12 detects a loopback condition when it receives its own transmit address in the MIRRORED BITS message. When the SEL-FR12 detects loopback, the LOOP LED illuminates and the ROK LED extinguishes.SEL-FR12SEL-FR12SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50SEL-FT50Network ID 01 Network ID 04Network ID 01 Network ID 04Unique Network IDs isolate system operation010203040506010203040506
15Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSystem InstallationFigure 13 Serial Port Settings SelectionSetting Near/Distant SEL-FT50For three-phase installations, the SEL-FT50 Fault Transmitters are installed in groups of three, and the received signal strength from all members of a trio is identical. The received signal strength between multiple trios is usually different because of path differences. To accommodate the range of reception signal strengths, an attenuation setting is provided for each trio. See Table 3 for trio assignments.NOTE: There is no transmitter power adjustment selection in the SEL-FT50.  The appropriate attenuation setting for each trio is based on the distance between the trio and the SEL-FR12.Figure 14 Trio Attenuation Switch SelectionConnecting the SEL-FR12 to Other SEL DevicesThe SEL-FR12 uses the MB8 MIRRORED BITS protocol. The following examples give sample configurations for SEL devices that operate with the SEL-FR12. For each of these examples, select BAUD = 38400, RX_ADD = 2, and TX_ADD = 1 on the SEL-FR12. Only the minimum settings required are shown. Consult the appropriate instruction manual to ensure proper settings for your particular MIRRORED BITS application.Table 3 Trio AssignmentsNode (Three-Phase) Unit ID Assignments at Each Location Trio Number1 1, 2, 3 12 4, 5, 6 23 7, 8, 9 34 10, 11, 12 4
16SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317System InstallationSEL-351, SEL-751 Relays, SEL-351R, and SEL-651R Recloser ControlsPROTO = MB8A*SPEED = 38400TXID = 2RXID = 1* = MB8A or MB8B may be usedSEL-451 RelayPROTO= MBA*SPEED = 38400MBT = NTX_ID = 2TX MODE = PSTOPBIT = 2RX_ID = 1MBNUM = 8* = MBA or MBB may be usedSEL-2505/SEL-2506 Remote I/O ModuleSPEED = 38400RX_ADD = 1TX_ADD = 2MIRRORED BITS Interface and MessagesThe SEL-FR12 communicates with a host device (protective relay or recloser control) through use of SEL MIRRORED BITS communications. The connection requires one serial port on the host device. The SEL-FR12 supports four port speeds: 9.6, 19.2, 38.4, and 115.2 kbps. By default, the messages have the formats listed in Table 4.The default command set is ideal for applications where SEL-FT50 Fault Transmitters are installed in trios and individual unit information is not needed. For other applications, the SEL-FR12 supports two additional MIRRORED BITS command sets.The command sets listed in Table 6 and Table 7 provide conditional responses. Program the SEL-651R logic to evaluate the expression RMB1 OR RMB2. When true, the remaining bits RMB3–RMB8 contain FAULT data; otherwise, they contain LINK data.Table 5 defines the Trio FAULT and Trio LINK bits.Table 4 Default Command Set—SEL-FR12 MIRRORED BITS Data Message ContentsRequired SEL-651R Transmit MIRRORED BITS (SELOGIC Equations) for Default ModeTMB1 TMB2 TMB3 TMB4 TMB5 TMB6 TMB7 TMB80 0 0 0 0 0 Clear link state in SEL-FR12Target reset on SEL-FR12 HMISEL-651R Received MIRRORED BITS (Relay Word bits)RMB1 RMB2 RMB3 RMB4 RMB5 RMB6 RMB RMB8Trio 1 FAULT Trio 2 FAULT Trio 3 FAULT Trio 4 FAULT Trio 1 LINK Trio 2 LINK Trio 3 LINK Trio 4 LINK
17Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSystem InstallationThe TMB1–TMB6 entries in Table 6 and Table 7 indicate the required TMB states to select the Default Set or Command Set 2 or 3. Any other bit combinations force the SEL-FR12 to return all zeros and cause it to ignore TMB7 and TMB8 commands.The Trio 1 LINK, Trio 2 LINK, Trio 3 LINK, and Trip 4 LINK bit logic ignores SEL-FT50 Fault Transmitters that have not been installed or detected. For example, if SEL-FT50 Fault Transmitters with Unit IDs 4 and 5 are installed, but there is no Unit ID 6, LINK 6 never asserts. The equation for the Trio 2 LINK is reduced to LINK 4 AND LINK 5.Table 5 Definition of FAULT and LINK BitsBit Label DefinitionLINK u u = Unit ID 1–12SEL-FR12 is receiving messages from SEL-FT50 Fault Transmitters. Asserts whenever SEL-FR12 LINK LED u is solidly illuminated.Trio 1 LINK Logical AND of the link status from the installed SEL-FT50 Fault Transmitters with Unit IDs 1, 2, and 3Trio 2 LINK Logical AND of the link status from the installed SEL-FT50 Fault Transmitters with Unit IDs 4, 5, and 6Trio 3 LINK Logical AND of the link status from the installed SEL-FT50 Fault Transmitters with Unit IDs 7, 8, and 9Trio 4 LINK Logical AND of the link status from the installed SEL-FT50 Fault Transmitters with Unit IDs 10, 11, and 12FAULT u u = Unit ID 1–12Asserts for 116 ms when the SEL-FR12 receives a fault message from the SEL-FT50 and deasserts thereafter; this bit is not latched (this dif-fers from the SEL-FR12 FAULT LEDs, which are latched until reset). Trio 1 FAULT Logical OR of the fault state from Unit IDs 1, 2, and 3Trio 2 FAULT Logical OR of the fault state from Unit IDs 4, 5, and 6Trio 3 FAULT Logical OR of the fault state from Unit IDs 7, 8, and 9Trio 4 FAULT Logical OR of the fault state from Unit IDs 10, 11, and 12Table 6 Detailed Command Set 2—SEL-FR12 MIRRORED BITS Data Message ContentsRequired SEL-651R Transmit MIRRORED BITS (SELOGIC Equations) for Detailed Command Set (2)TMB1 TMB2 TMB3 TMB4 TMB5 TMB6 TMB7 TMB80 0 1 0 0 0 Clear link state in SEL-FR12Target reset on SEL-FR12 HMI SEL-651R Received MIRRORED BITS (Relay Word bits)RMB1 RMB2 RMB3 RMB4 RMB5 RMB6 RMB7 RMB8Response During Normal Conditions (No Fault on Trio 1 or Trio 2)Trio 1 FAULT = 0Trio 2 FAULT = 0LINK 1 LINK 2 LINK 3 LINK 4 LINK 5 LINK 6Response During FAULT Indication (One or Both Trio 1 FAULT, Trio 2 FAULT Asserted)Trio 1 FAULT Trio 2 FAULT FAULT 1 FAULT 2 FAULT 3 FAULT 4 FAULT 5 FAULT 6
18SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317System InstallationAccess 12 Individual LINK and FAULT BitsCommand Set 2 provides the individual status of Unit IDs 1–6 and Command Set 3 provides it for Unit IDs 7–12. However, there is no command set that provides all 12 individual status points at one time.For applications that require more than six individual LINK u or FAULT u bits, set the SEL-651R to alternately request Command Set 2 and Command Set 3. Achieve this by operating TMB4 from a SELOGIC timer, changing state automatically (refer to the top sections of Table 6 and Table 7). Configure further SELOGIC to qualify and decode the RMB data, and store the result in the appropriate SELOGIC variables for use in control functions or for system logging in the Sequential Events Recorder.Temporarily Disable SEL-FR12 MIRRORED BITS ResponsesFor commissioning purposes, it may be necessary to disable the MIRRORED BITS data that the SEL-FR12 is transmitting. In the SEL-651R, set TMB1–TMB8 = 0, with the exception of setting TMB4 = 1. This has no effect on the SEL-FR12 front-panel LED operation.SEL-FT50Settings and ConfigurationThe SEL-FT50 uses two internal eight-position switch banks to configure the Unit ID, the Network ID, and the Fault Pickup current level.To begin, open the SEL-FT50 by twisting the bottom counter-clockwise. On the inside of the device, you will see the two banks of switches. The switch positions are labeled 1 through 8 on each of the two switch banks. The switch selections are outlined on a label on the interior of the device, as shown in Figure 15. Table 7 Detailed Command Set 3—SEL-FR12 MIRRORED BITS Data Message ContentsRequired SEL-651R Transmit MIRRORED BITS (SELOGIC Equations) for Detailed Command Set (2)TMB1 TMB2 TMB3 TMB4 TMB5 TMB6 TMB7 TMB80 0 1 1 0 0 Clear link state in SEL-FR12Target reset on SEL-FR12 HMISEL-651R Received MIRRORED BITS (Relay Word bits)RMB1 RMB2 RMB3 RMB4 RMB5 RMB6 RMB7 RMB8Response During Normal Conditions (No Fault on Trio 3 or Trio 4)Trio 3 FAULT = 0Trio 4 FAULT = 0LINK 7 LINK 8 LINK 9 LINK 10 LINK 11 LINK 12Response During FAULT Indication (One or Both Trio 3 FAULT, Trio 4 FAULT Asserted)Trio 3 FAULT Trio 4 FAULT FAULT 7 FAULT 8 FAULT 9 FAULT 10 FAULT 11 FAULT 12
19Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSystem InstallationFigure 15 Switch Selections LabelsSetting the Unit IDThe SEL-FR12 Fault Receiver receives wireless signals from as many as 12 SEL-FT50 Fault Transmitters on the same network, defined by the Network ID selection in the SEL-FT50/SEL-FR12 system.To allow the SEL-FR12 to distinguish which fault transmitter has sent a message, each SEL-FT50 transmits a Unit ID field as part of the message (the Unit ID is a number from 1 to 12).The following lists the requirements when planning the Unit IDs to use in a system:➤Unit IDs cannot be duplicated on the network.➤Not all Unit IDs need to be present.➤Unit IDs should be grouped in three-phase locations as trios (see Table 3).➤Single-phase and two-phase applications are possible in specific situations.➤Unit IDs should be marked on the system record for later installation and commissioning work.➤Each SEL-FT50 Unit ID is configurable and is selected by the Unit ID control switches inside the housing. Setting the Network IDConfigure your SEL-FT50 Fault Transmitters to communicate on the same network as your SEL-FR12 by giving both devices the same Network ID. Devices with different Network IDs cannot communicate.Setting Fault PickupThe topic of power system coordination is outside the scope of this guide. An overcurrent element must supervise SEL-FT50 data when used in trip decisions or other operations affecting protection. Choose an SEL-FT50 Fault Pickup to be at or below the upstream protective device (e.g., recloser control) supervising the overcurrent pickup setting (expressed in primary amperes).Because the SEL-FT50 measurement accuracy is not as accurate as a relay, take care when choosing your fault pickup settings. The measurement accuracy for each trip threshold is spelled out in the specifications section.
20SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317System InstallationFollow the guidelines in the following table to ensure the right pickup levels while avoiding false pickups.This selection method guarantees that the SEL-FT50 picks up for any fault that the protective device element can see. This setting method will perform well in locations where fault current is much higher than load current.The protection planner must consider the load current range on the distribution system at each node, combined with the SEL-FT50 accuracy rating at currents below the fault pickup. High load current levels may result in false assertion of the SEL-FT50 fault detector. In most cases, this is acceptable because the supervising overcurrent element will not assert. However, the more frequent a load condition is mistaken for a fault, and the longer each instance persists, the higher the chance of the SEL-FT50 missing an actual fault. To avoid this situation, consider selecting the SEL-FT50 Fault Pickup setting to be one step higher.Field InstallationWireless ConsiderationsRadio Path. Spread-spectrum radios operating in the 900-MHz band are limited by line-of-sight. Obstructions in the line-of-sight will impact the performance of the radio, because the strongest radio signal is communicated directly along the radio line-of-sight. The line-of-sight between two antennas is shaped like an ellipse (called the Fresnel zone). The point exactly halfway between the two antennas is the widest part of the ellipse, as shown in Figure 16. At 900 MHz and 304.8 m (1000 ft) apart, the Fresnel zone is 4.9 m (16 ft) in diameter. At 32 km (20 mi) apart, it is 51.8 m (170 ft) in diameter. Anything within the Fresnel zone will obstruct and reduce signal strength and availability (the ground, buildings, vegetation, etc.). Table 9 depicts the maximum Fresnel zone diameter and path loss for some typical path distances.Table 8 Fault Pickup Accuracy ConsiderationsFault Pickup Level Host Relay Pickup Setting Load Behind FT5050A > 75A < 25A100A > 130A < 70A200A > 260A < 140A400A > 480A < 320A600A > 720A < 480A800A > 960A < 640A1000A > 1200A < 800A1200A > 1440A < 960ANOTE: The SEL-FT50 current measurement circuitry is not as precise as a protective relay overcurrent element. Refer to Specifications on page 25 for fault pickup accuracy, response characteristics, and device ratings.
21Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSystem InstallationFigure 16 Fresnel ZoneThe formula used to calculate the widest distance of the Fresnel zone is as follows:where:b = radius of the Fresnel zone in metersd = distance between transmitter and receiver in kilometersf = frequency transmitted in GHzObstructions in the Fresnel zone may also cause multipath interference because of reflective or refractive signals that may arrive at the receiver out of phase with the desired signal. The Fresnel zone should be at least 60 percent clear of obstructions for reliable radio communications. Large objects outside the Fresnel zone can also cause reflections that can affect reliable radio operation.Fade Margin. The fade margin determines the allowable signal loss between the transmitter and receiver. The fade margin is a function of system gains (transmitter power, receiver sensitivity, and antenna gain) and system losses (free-space loss, losses because of Earth’s curvature, and coaxial cable loss). Variations in temperature and humidity of the atmosphere along with elevation cause the signals to bend more or bend less, resulting in fading at the receiver. The longer the path, the more likely deep fades will occur, requiring a greater fade margin. The formula to calculate free-space loss is shown below.Free-Space Loss = 92.4 + 20log(f) + 20log(d) dBwhere: f = frequency in GHzd = distance in kmRegional conditions also impact the probability of signal fade. Generally, mountainous terrain is more favorable, while tropical areas and those near large bodies of water are less favorable. Perform a site survey before installing the SEL-FT50 Fault Transmitters to obtain the fade margin. A fade margin of 10 dB yields adequate performance for noncritical communications links Table 9 900-MHz Fresnel Zone RadiusDistance Between Antennas (d) Fresnel Zone Radius (b) Free-Space Loss (dB)304.8 m (1000 ft) 4.9 m (16 ft) 811.6 km (1 mi) 11.6 m (38 ft) 968 km (5 mi) 25.9 m (85 ft) 11016 km (10 mi) 36.6 m (120 ft) 116dbb 17.32 d 4f e=
22SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317System Installationwhile a fade margin of 15 dB yields good radio performance for critical communications links.Site Survey. A line-of-sight path provides the most reliable transmission in all cases. As the distance increases, the need for a clear path becomes more critical in creating a reliable, available radio link. If you have a clear line-of-sight to the other location without obstructions to the Fresnel zone (see Radio Path on page 20) then a path study is generally not needed. Longer distances may require a path study, a visual path inspection, and a spectrum analysis of the area to give a good indication of how high the antenna needs to be and how good the radio link will be.Radio Interference. The SEL-FT50 shares frequency spectrum with other services and FCC Part 15 (unlicensed) devices in ITU Region 2 (North, Central, and South America). Error-free communication may not be achievable in a given location and some level of interference should be expected. For a given fault, the SEL-FT50 sends four consecutive messages. This mitigates the effect of radio interference by increasing the odds that a fault indication will be communicated successfully during situations with poor channel conditions. Physical InstallationInstall the SEL-FT50 on a distribution line by using an industry-standard hot stick.Step 1. Use a hot stick to grasp the hook eye on the side of the SEL-FT50, and place the device on the line so that the opening hangs over the line.Figure 17 Positioning the SEL-FT50Step 2. Apply slight downward and sideways pressure until the device is closed around the line.The spring mechanism should be pushed in, so that it wraps around the line. Figure 18 SEL-FT50 Installation Position
23Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemDimensionsStep 3. Apply slight upward pressure until the device is secured around the line as shown in Figure 19.Figure 19 SEL-FT50 Secure on the LineStep 4. Use the hot stick to adjust the transmitter orientation so that it is directly vertical. This is important to ensure the best propagation characteristics for the internal antenna. DimensionsFigure 20 SEL-FT50 Dimensions5.71(145.03)5.83(148.08)2.47(62.74)4.75(120.55)
24SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317DimensionsFigure 21 SEL-FR12 Dimensions
25Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemSpecificationsSpecifications                     ComplianceDesigned and manufactured under an ISO 9001 certified quality management system.GeneralOperating Temperature–40° to +85°C (–40° to +185°F)Storage Temperature–40° to +85°C (–40° to +185°F)Operating EnvironmentPollution Degree: 2Relative Humidity: 5–95%, noncondensingMaximum Altitude: 2000 mIngress Protection (SEL-FT50)IP67Clamp Range (SEL-FT50)7.6 mm to 27.9 mm (0.3 in to 1.1 in)DimensionsSEL-FT50: 145 mm diameter x 148 mm height(5.71 in. diameter x 5.83 in. height)SEL-FR12: 44 mm x 243 mm x 117 mm (1.73 in x 9.57 in x 4.61 in)WeightSEL-FT50: 0.6 kg (1.3 lb)SystemPower System Frequency Range45–65 HzCurrent Pickup LevelNote: Units are individually configurable.50, 100, 200, 400, 600, 800, 1000, 1200 AFault Detection Accuracy50 A Threshold: 50%100 A, 200 A Threshold: 30%400 A Threshold and Above: 20%Maximum Voltage38 kV (L-L)PowerSEL-FT50 Minimum Radio Link Active Current15 ASEL-FR12 Power RequirementsVoltage: 9–30 VdcPower Consumption: < 2 WRadio SystemFrequency Band902–928 MHz ISM bandSEL-FT50TX Power: 700 mW (28 dBm)SEL-FR12Number of Channels: 12Antenna Connector: BNC, 50 :RX Sensitivity: –100 dBm at 1% error rateSerial Protocol: MIRRORED BITS communicationsSerial Port: 9600, 19200, 38400, 115200 bpsModulationFSKTypical Range4 miles with 20 dB of interference/fade margin
26SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317Appendix A: Manual VersionsAppendix A: Manual VersionsInstruction Manual The date code at the bottom of each page of this manual reflects the creation or revision date.Table 10 lists the instruction manual versions and revision descriptions. The most recent instruction manual version is listed first.Table 10 Instruction Manual Revision HistoryDate Code Summary of Revisions20170317 ➤Initial version.
27Date Code 20170317 Instruction Manual SEL-FT50/SEL-FR12 Fault Transmitter and Receiver SystemAppendix B: Two Branch ApplicationAppendix B: Two Branch ApplicationTwo Branch ApplicationThis application has two three-phase branches, A and B, as shown in Figure 22. Branch B has a fuse and uses a fuse-blowing scheme, while Branch A does not. When a fault occurs on Branch A, the recloser operates to clear the fault. In traditional protection schemes, those without the SEL-FT50/SEL-FR12 system, the time-inverse overcurrent curves of the SEL-651R recloser control are set above the fuse-clearing curve, resulting in longer tripping times for faults on Branch A. Use the SEL-FT50/SEL-FR12 system to improve this protection scheme.Figure 22 SEL-FT50/SEL-FR12 System Protection SchemeInsert a set of three SEL-FT50 Fault Transmitters on each branch, one per phase. The SEL-FR12 connects to the SEL-651R with an SEL-C272 serial cable. In this example, the load current of Branch A is 200 A, and the load current of Branch B is 100 A. The 51 element pickup of the SEL-651R is set above 200 percent of the load current. In this example, the fuse size is 140 T, the SEL-651R 51 element pickup is 550 A, and the settings from Table 11 apply.This settings example uses Network ID = 3, and the fault current pickup threshold is set above the load current and below the pickup.The Network ID of the SEL-FR12 matches the Network ID of the SEL-FT50 Fault Transmitters. Table 12 assumes that the distances of the SEL-FT50 Fault Transmitters are farther than 300 m (1000 ft). See Table 13 for the settings of the SEL-651R and Table 14 for the SEL-651R transmit MIRRORED BITS settings.RSEL-FR12SEL-651R-2SEL-FT50SEL-FT50123456ABTable 11 Settings for the SEL-FT50 Fault TransmittersSEL-FT50 BranchUnit IDControl (DIP) Switch PositionsNetwork IDControl (DIP) Switch PositionsPickup ThresholdControl (DIP) Switch Positions1 A 1—(0000) 3—(0010) 400 A—(011)2 A 2—(0001) 3—(0010) 400 A—(011)3 A 3—(0010) 3—(0010) 400 A—(011)4 B 4—(0011) 3—(0010) 200 A—(010)5 B 5—(0100) 3—(0010) 200 A—(010)6 B 6—(0101) 3—(0010) 200 A—(010)
28SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 20170317Appendix B: Two Branch ApplicationWith these settings, Branch B operates using a fuse-blowing scheme where the fuse clears faults on the branch, while Branch A operates separately, tripping much faster because the protection does not wait for a fuse-coordination delay.Table 12 Settings for the SEL-FR12Network ID BAUD RX_ADD TX_ADD Trio 1 Distance Trio 2 Distance Trio 3 Distance Trio 4 Distance3—(0010) 38400 1 2 > 300 m (1000 ft) > 300 m (1000 ft) > 300 m (1000 ft) > 300 m (1000 ft)Table 13  SEL-651R SettingsPROTO SPEED TXID RXIDMB8A or MB8B 38400 1 2Table 14 SEL-651R Transmit MIRRORED BITS SettingsTMB1A TMB2A TMB3A TMB4A TMB5A TMB6A TMB7A TMB8A Comments0 0 0 0 0 0 0 TRGTR The TARGET RESET pushbutton of the SEL-651R resets the latched FAULT LEDs of the SEL-FR12.
SEL-FT50/SEL-FR12 Fault Transmitter and Receiver System Instruction Manual Date Code 2017031729 Appendix B: Two Branch Application© 2017 by Schweitzer Engineering Laboratories, Inc. All rights reserved.All brand or product names appearing in this document are the trademark or regis-tered trademark of their respective holders. No SEL trademarks may be used with-out written permission. SEL products appearing in this document may be covered byU.S. and Foreign patents.Schweitzer Engineering Laboratories, Inc. reserves all rights and benefits affordedunder federal and international copyright and patent laws in its products, includingwithout limitation software, firmware, and documentation.The information in this document is provided for informational use only and is sub-ject  to  change  without  notice.  Schweitzer  Engineering  Laboratories,  Inc.  hasapproved only the English language document.This product is covered by the standard SEL 10-year warranty. For warranty details,visit selinc.com or contact your customer service representative. *PMFR12-01*2350 NE Hopkins Court • Pullman, WA 99163-5603 U.S.A.Tel: +1.509.332.1890 • Fax: +1.509.332.7990selinc.com • info@selinc.com