RF300 system planning 4.6 EMC Directives Prevention of interference by optimum configuration Good interference suppression can be achieved by installing SIMATIC PLCs on conducting mounting plates (unpainted). When setting up the control cabinet, interference can be prevented easily by observing certain guidelines. Power components (transformers, drive units, load power supply units) should be arranged separately from the control components (relay control unit, SIMATIC S7). As a rule: ⢠The effect of the interference decreases as the distance between the interference source and interference sink increases. ⢠The interference can be further decreased by installing grounded shielding plates. ⢠The load connections and power cables should be installed separately from the signal cables with a minimum clearance of 10 cm. 3RZHUVXSSO\ &&(8 6KLHOG SODWH 'ULYH Figure 4-24 Prevention of interference by optimum configuration SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 4-51 RF300 system planning 4.6 EMC Directives Filtering of the supply voltage External interference from the mains can be prevented by installing line filters. Correct installation is extremely important, in addition to appropriate dimensioning. It is essential that the line filter is mounted directly at the cabinet inlet. As a result, interference is filtered promptly at the inlet, and is not conducted through the cabinet. &RUUHFW ,QFRUUHFW /LQHILOWHU ,V /LQHILOWHU ,V ,F LQWHUIHUHQFHFXUUHQW Figure 4-25 4-52 Filtering of the supply voltage SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 RF300 system planning 4.6 EMC Directives 4.6.6 Prevention of interference sources A high level of immunity to interference can be achieved by avoiding interference sources. All switched inductances are frequent sources of interference in plants. Suppression of inductance Relays, contactors, etc. generate interference voltages and must therefore be suppressed using one of the circuits below. Even with small relays, interference voltages of up to 800 V occur on 24 V coils, and interference voltages of several kV occur on 230 V coils when the coil is switched. The use of freewheeling diodes or RC circuits prevents interference voltages and thus stray interference on conductors installed parallel to the coil conductor. 5HOD\FRLOV 9DOYHV &RQWDFWRUV %UDNHV Figure 4-26 Suppression of inductance Note All coils in the cabinet should be suppressed. The valves and motor brakes are frequently forgotten. Fluorescent lamps in the control cabinet should be tested in particular. SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 4-53 RF300 system planning 4.6 EMC Directives 4.6.7 Equipotential bonding Potential differences between different parts of a plant can arise due to the different design of the plant components and different voltage levels. If the plant components are connected across signal cables, transient currents flow across the signal cables. These transient currents can corrupt the signals. Proper equipotential bonding is thus essential. ⢠The equipotential bonding conductor must have a sufficiently large cross section (at least 10 mm2). ⢠The distance between the signal cable and the associated equipotential bonding conductor must be as small as possible (antenna effect). ⢠A fine-strand conductor must be used (better high-frequency conductivity). ⢠When connecting the equipotential bonding conductors to the centralized equipotential bonding strip (EBS), the power components and non-power components must be combined. ⢠The equipotential bonding conductors of the separate modules must lead directly to the equipotential bonding strip. &DELQHW &DELQHW 3RZHUVXSSO\ 'HYLFH ,QFRUUHFW 'HYLFH 'HYLFH 3/& ,QFRUUHFW (%6 'ULYH Figure 4-27 Equipotential bonding (EBS = Equipotential bonding strip) The better the equipotential bonding in a plant, the smaller the chance of interference due to fluctuations in potential. Equipotential bonding should not be confused with protective earthing of a plant. Protective earthing prevents the occurrence of excessive shock voltages in the event of equipment faults whereas equipotential bonding prevents the occurrence of differences in potential. 4-54 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 RF300 system planning 4.6 EMC Directives 4.6.8 Cable shielding Signal cables must be shielded in order to prevent coupling of interference. The best shielding is achieved by installing the cables in steel tubes. However, this is only necessary if the signal cable is routed through an environment prone to particular interference. It is usually adequate to use cables with braided shields. In either case, however, correct connection is vital for effective shielding. Note An unconnected or incorrectly connected shield has no shielding effect. As a rule: ⢠For analog signal cables, the shield should be connected at one end on the receiver side ⢠For digital signals, the shield should be connected to the enclosure at both ends ⢠Since interference signals are frequently within the HF range (> 10 kHz), a large-area HFproof shield contact is necessary Figure 4-28 Cable shielding SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 4-55 RF300 system planning 4.6 EMC Directives The shielding bus should be connected to the control cabinet enclosure in a manner allowing good conductance (large-area contact) and must be situated as close as possible to the cable inlet. The cable insulation must be removed and the cable clamped to the shielding bus (high-frequency clamp) or secured using cable ties. Care should be taken to ensure that the connection allows good conductance. Cable tie 5HPRYHSDLQW Figure 4-29 Connection of shielding bus The shielding bus must be connected to the PE busbar. If shielded cables have to be interrupted, the shield must be continued via the corresponding connector housing. Only suitable connectors may be used for this purpose. 6KLHOGWXUQHGXSVLGHGRZQ WKURXJKrDQG FRQQHFWHGWRFRQQHFWRU KRXVLQJ 5XEEHUVOHHYH Figure 4-30 Interruption of shielded cables If intermediate connectors, which do not have a suitable shield connection, are used, the shield must be continued by fixing cable clamps at the point of interruption. This ensures a large-area, HF-conducting contact. 4-56 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5 Readers 5.1 5.1 Overview The reader ensures inductive communication with the transponders, and handles the serial connection to the communication modules/interface modules and 8xIQ-Sense module. Communication between the transponder and reader takes place over inductive alternating fields. The transmittable data volume between reader and transponder depends on: ⢠the speed at which the transponder moves through the transmission window of the reader. ⢠the length of the transmission window. ⢠the transponder type (FRAM, EEPROM). SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-1 Readers 5.2 RF310R with IQ-Sense interface 5.2 5.2.1 5.2 RF310R with IQ-Sense interface Features Reader RF310R Features Design (1) IQ-Sense interface (2) Operating indicator 5.2.2 Identification tasks on small assembly lines in harsh industrial environments Read/write distance to transponder max. 30 mm Data transmission rate ⢠⢠Read: approx. 50 bytes/s Write: approx. 40 bytes/s Display elements of the RF310R reader with IQ-Sense interface Table 5-1 5.2.3 Field of application Display elements of the reader Color Meaning Green Operating voltage available yellow Transponder present red Errors Ensuring reliable data exchange The "center point" of the transponder must be situated within the transmission window. 5-2 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.2 RF310R with IQ-Sense interface 5.2.4 Metal-free area The RF310R can be flush-mounted in metal. Please allow for a possible reduction in the field data values. 6,0$7,& 5)5 Figure 5-1 Metal-free area for RF310R To avoid any impact on the field data, the distance a should be ⼠20 mm. 5.2.5 Minimum distance between RF310R readers 6,0$7,& 5)5 0LQLPXPGLVWDQFHEHWZHHQ5)5DQG5)5 ' ุPP 6,0$7,& 5)5 Figure 5-2 6,0$7,& 5)5 Minimum distance between RF310R readers SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-3 Readers 5.2 RF310R with IQ-Sense interface 5.2.6 Technical data for RF310R reader with IQ-Sense interface Table 5-2 5-4 Technical data for RF310R reader with IQ-Sense interface Inductive interface to the transponder Transmission frequency for power/data 13.56 MHz Interface to SIMATIC S7-300 Required master module RFID channels (RF310R) Mixed operation with other profiles IQ-Sense, 2-wire non-polarized 8-IQ-Sense (6ES7 338-7XF00-0AB0) max. 2 per master module, max. 4 Opto-BEROs, 1x SIMATIC RF310R Cable length between reader and communication module Max. 50 m (unshielded cable) Read/write distances of reader See RF310R field data Minimum distance between two RF310R readers ⼠400 mm Data transfer rate for read/write device Reading Writing Approx. 50 bytes/s Approx. 40 bytes/s Passing speed Reading Writing Approx. 0.8 m/s (2 bytes) Approx. 0.8 m/s (2 bytes) Function Read, write, initialize transponder Multi-tag no Voltage supply via IQ-Sense master module 24 V DC Display elements 2-color LED (operating voltage, presence, error) Plug connector M12 (4-pin) Enclosure Dimensions (in mm) Color Material 55 x 75 x 30 (without M12 enclosure connector) Anthracite Plastic PA 12 Fixing 4 x M5 screws Ambient temperature during operations during transport and storage -25°C to +70°C -40°C to +85°C Degree of protection to EN 60529 Shock to EN 60 721-3-7 Class 7 M2 Overall shock response spectrum, Type II Vibration to EN 60 721-3-7 Class 7M2 IP65 50 g 1 g (9 to 200 Hz) 1.5 g (200 to 500 Hz) Weight Approx. 200 g MTBF (Mean Time Between Failures) in years 153,5 Approvals Radio to R&TTE guidelines EN 300 330, EN 301 489, CE, FCC SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.2 RF310R with IQ-Sense interface 5.2.7 FCC information Siemens SIMATIC RF300 with IQ-Sense interface FCC ID: NXW-RF310R-IQ This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. 5.2.8 Ordering data of RF310R with IQ-Sense interface RF310R Order No. With IQ-Sense interface for ET 200M to SIMATIC S7-300 IP65, -25° to +70°C, 71 x 75 x 30 (L x W x H in mm), with integrated antenna, max. limit distance: 30 mm (depending on transponder) 6GT2801-0AA00 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-5 Readers 5.2 RF310R with IQ-Sense interface Dimension drawing 5.2.9 6,0$7,& 5)5 Figure 5-3 5-6 Dimension drawing for RF310R SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.3 RF310R with RS 422 interface 5.3 5.3.1 5.3 RF310R with RS 422 interface Features Reader RF310R Features Structure (1) RS 422 interface (2) Operating indicator 5.3.2 Identification tasks on small assembly lines in harsh industrial environments Read/write distance to transponder max. 30 mm Data transmission rate ⢠⢠Read: approx. 3100 bytes/s Write: approx. 3100 bytes/s Display elements of the RF310R reader with RS 422 interface Table 5-3 5.3.3 Field of application Display elements of the reader Color Meaning Green Operating voltage available yellow Transponder present red Errors Ensuring reliable data exchange The "center point" of the transponder must be situated within the transmission window. SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-7 Readers 5.3 RF310R with RS 422 interface 5.3.4 Metal-free area The RF310R can be flush-mounted in metal. Please allow for a possible reduction in the field data values. 6,0$7,& 5)5 Figure 5-4 Metal-free area for RF310R To avoid any impact on the field data, the distance a should be ⼠20 mm. 5.3.5 Minimum distance between RF310R readers 6,0$7,& 5)5 0LQLPXPGLVWDQFHEHWZHHQ5)5DQG5)5 ' ุPP 6,0$7,& 5)5 Figure 5-5 5-8 6,0$7,& 5)5 Minimum distance between RF310R readers SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.3 RF310R with RS 422 interface 5.3.6 Technical data of the RF310R reader with RS 422 interface Table 5-4 Technical data of the RF310R reader with RS 422 interface Inductive interface to the transponder Transmission frequency for power/data 13.56 MHz Antenna Integrated Interface to communication module RS 422 (3964R protocol) Baud rate 19200 baud, 57600 baud, 115200 baud Cable length between reader and communication module Max. 120 m Read/write distances of reader See RF310R field data Minimum distance between two RF310R readers ⼠400 mm Maximum data transfer rate from reader to transponder (Tag) Reading Writing Approx. 3100 bytes/s Approx. 3100 bytes/s Data cable length max. 1000 m (shielded cable) Functions Initialize/read/write transponder Scan status and diagnostics information Switch antenna on/off Repeat command Scan transponder serial numbers Voltage supply 24 V DC, 30 mA typ. Display elements 2-color LED (operating voltage, presence, error) Plug connector M12 (8-pin) Enclosure Dimensions (in mm) Color Material 55 x 75 x 30 (without M12 device connector) Anthracite Plastic PA 12 Fixing 4 x M5 screws Ambient temperature during operations during transport and storage -25 °C to +70 °C -40 °C to +85 °C Degree of protection to EN 60529 IP65 Shock to EN 60 721-3-7 Class 7 M2 Overall shock response spectrum, Type II Vibration to EN 60 721-3-7 Class 7 M2 50 g 1 g (9 to 200 Hz) 1.5 g (200 to 500 Hz) Weight Approx. 200 g MTBF (Mean Time Between Failures) in years 169,9 Approvals Radio to R&TTE guidelines EN 300 330, EN 301489, CE, FCC SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-9 Readers 5.3 RF310R with RS 422 interface 5.3.7 FCC information Siemens SIMATIC RF310R with RS 422 interface FCC ID: NXW-RF310R This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. 5.3.8 5-10 Ordering data for RF310R with RS 422 interface RF310R Order No. With RS 422 interface (3964R) for ASM 475/452/456/473 (S7-300, PROFIBUS) IP 65, -25 °C to +70 °C, 55 x 75 x 30 (L x B x H in mm), with integrated antenna, max. limit distance 30 mm (depending on transponder type) 6GT2801-1AA10 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.3 RF310R with RS 422 interface Dimension drawing 5.3.9 Figure 5-6 6,0$7,& 5)5 Dimension drawing for RF310R SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-11 Readers 5.4 RF340R 5.4 5.4.1 5.4 RF340R Features Reader RF340R Features Design (1) RS 422 interface (2) Operating indicator Read/write distance to transponder max. 60 mm Data transmission rate ⢠⢠Read: approx. 3,100 bytes/s Write: approx. 3,100 bytes/s Display elements of the RF340R reader Table 5-5 5.4.3 Identification tasks on assembly lines in harsh industrial environments 5.4.2 Application Display elements of the reader Color Meaning Green Operating voltage available yellow Transponder present red Errors Ensuring reliable data exchange The "center point" of the transponder must be situated within the transmission window. 5-12 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.4 RF340R 5.4.4 Metal-free area The RF340R can be flush-mounted in metal. Please allow for a possible reduction in the field data values. 6,0$7,& 5)5 Figure 5-7 Metal-free area for RF340R To avoid any impact on the field data, the distance a should be ⼠20 mm. 5.4.5 Minimum distance between RF340R readers 5)5 0LQLPXPGLVWDQFHIURP5)5WR5)5 ' ุPP 5)5 Figure 5-8 5)5 Minimum distance between RF340R readers SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-13 Readers 5.4 RF340R 5.4.6 Technical data of the RF340R reader Table 5-6 5-14 Technical data of the RF340R reader Inductive interface to the transponder Transmission frequency for power/data 13.56 MHz Antenna Integrated Interface to communication module RS 422 (3964R protocol) Baud rate 19200 baud, 57600 baud, 115200 baud Cable length between reader and communication module Max. 120 m Read/write distances of reader See RF340R field data Minimum distance between two RF340R readers ⼠500 mm Maximum data transfer rate reader - transponder (tag) Reading Writing Approx. 3100 bytes/s Approx. 3100 bytes/s Data cable length max. 1000 m (shielded cable) Functions Initialize/read/write transponder Scan status and diagnostics information Switch antenna on/off Repeat command Scan transponder serial numbers Voltage supply 24 V DC, 110 mA typ. Display elements 2-color LED (operating voltage, presence, error) Plug connector M12 (8-pin) Enclosure Dimensions (in mm) Color Material 75 x 75 x 40 (without M12 device connector) Anthracite Plastic PA 12 Fixing 2 x M5 screws Ambient temperature during operations during transport and storage -25 °C to +70 °C -40 °C to +85 °C Degree of protection to EN 60529 IP65 Shock to EN 60 721-3-7 Class 7 M2 Overall shock response spectrum, Type II Vibration to EN 60 721-3-7 Class 7 M2 50 g 1 g (9 to 200 Hz) 1.5 g (200 to 500 Hz) Weight Approx. 250 g MTBF (Mean Time Between Failures) in years 140,3 Approvals Radio to R&TTE guidelines EN 300 330, EN 301489, CE, FCC SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.4 RF340R 5.4.7 FCC information Siemens SIMATIC RF340R FCC ID: NXW-RF340R This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. 5.4.8 Ordering data for RF340R Product description Order No. Reader RF340R With RS 422 interface (3964R) for ASM 475/452/473 (S7-300, PROFIBUS); IP65; -25 °C ⌠+70 C, dimensions 75 x 91 x 41 (L x W x H in mm); with integrated antenna; max. limit distance 65 mm (depending on transponder) 6GT2801-2AA10 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-15 Readers 5.4 RF340R Dimension drawing 5.4.9 Figure 5-9 5-16 Dimension drawing for RF340R SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.5 RF350R 5.5 5.5.1 5.5 RF350R Features Reader RF350R Features Design (1) RS 422 interface (2) Operating indicator (3) Antenna connection 5.5.2 Identification tasks in assembly lines in harsh industrial environments; for external antennas (ANT 1, ANT 18, ANT 30) Interfaces with which the RF350R reader can be operated ASM 452, ASM 456, ASM 473, ASM 475 Read/write distance to transponder max. 60 mm Data transmission rate ⢠⢠Read: approx. 3,100 bytes/s Write: approx. 3,100 bytes/s Display elements of the RF350R reader Table 5-7 5.5.3 Application Display elements of the reader Color Meaning Green Operating voltage available yellow Transponder present red Errors Ensuring reliable data exchange The "center point" of the transponder must be situated within the transmission window. SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-17 Readers 5.5 RF350R 5.5.4 Metal-free area The RF350R reader does not have an internal antenna. Operation is not affected by mounting on metal or flush-mounting in metal. For information about the metal-free area required by the external antennas, refer to the corresponding section of the chapter Antennas. 5.5.5 Technical data of the RF350R reader Table 5-8 Technical data of the RF350R reader Inductive interface to the transponder Transmission frequency for power/data 5-18 13.56 MHz Antenna External, plug-in MOBY E antennas ANT 1, ANT 18 or ANT 30 Interface to communication module RS 422 (3964R protocol) Baud rate 19200 baud, 57600 baud, 115 baud Cable length between reader and communication module Max. 120 m Read/write distances of reader See field data Minimum distance between two antennas See field data Maximum data transfer rate reader - transponder (tag) Reading Writing Approx. 3100 bytes/s Approx. 3100 bytes/s Data cable length max. 1000 m (shielded cable) Functions Initialize/read/write transponder Scan status and diagnostics information Switch antenna on/off Repeat command Scan transponder serial numbers Voltage supply 24 V DC, 110 mA typ. Display elements 2-color LED (operating voltage, presence, error) Plug connector M12 (8-pin); M8 (4-pin) for antenna Enclosure Dimensions (in mm) Color Material 75 x 75 x 40 (without M12 device connector) Anthracite Plastic PA 12 Fixing 2 x M5 screws Ambient temperature during operations during transport and storage -25 °C to +70 °C -40 °C to +85 °C Degree of protection to EN 60529 IP65 Shock to EN 60 721-3-7 Class 7 M2 Overall shock response spectrum, Type II Vibration to EN 60 721-3-7 Class 7 M2 50 g 1 g (9 to 200 Hz) 1.5 g (200 to 500 Hz) Weight Approx. 250 g MTBF (Mean Time Between Failures) in years 140,3 Approvals Radio to R&TTE guidelines EN 300 330, EN 301489, CE, FCC SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.5 RF350R 5.5.6 FCC information Siemens SIMATIC RF350R FCC ID: NXW-RF350R This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. 5.5.7 Ordering data for RF350R Product description Order No. Reader RF350R With RS 422 interface (3964R) for ASM 475/452/473 (S7-300, PROFIBUS); IP65; - 25 °C ⌠+70 C, dimensions 75 x 75 x 40 (L x W x H in mm); for plug-in antennas from the MOBY E product range; max. limit distance 65 mm (depending on transponder) 6GT2801-4AA10 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-19 Readers 5.5 RF350R Dimension drawing 5.5.8 Figure 5-10 5-20 RF350R dimension drawing SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.5 RF350R 5.5.9 Antennas 5.5.9.1 Features You can use the following plug-in antennas from the MOBY E product spectrum for the RF350R reader: Limit distance Sg in mm 1) Dimensions (L x B x H) in mm Suitable for dynamic operation MOBY E ANT 1 to 60 75 x 75 x 20 Yes MOBY E ANT 18 to 13 Ă M18 x 50 no MOBY E ANT 30 to 22 Ă M30 x 58 no Antenna Product photo 1) depending on the transponder used SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-21 Readers 5.5 RF350R ANT 1 The ANT 1 is an antenna in the mid performance range and can be used to the customer's advantage in production and assembly lines due to its manageable housing shape. The antenna dimensions make it possible to read/write large quantities of data dynamically from/to the tag during operation. The antenna cable can be connected at the reader end. ANT 18 The ANT 18 is designed for use in small assembly lines. Due to its small, compact construction, the antenna can be easily positioned for any application using two plastic nuts (included in the package). The antenna cable can be connected at the reader end. With the RF320T and RF340T tags, communication with the data storage unit is only possible in static mode. ANT 30 The ANT 30 is designed for use in small assembly lines. In comparison to ANT 18, the maximum write/read distance is approximately 60 % larger. Due to its compact construction, the antenna can be easily positioned for any application using two plastic nuts (included in the package). The antenna cable can be connected at the reader end. With the RF320T, RF340T and RF350T tags, communication with the data storage unit is only possible in static mode. 5-22 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.5 RF350R 5.5.9.2 Ensuring reliable data exchange The "center point" of the transponder must be situated within the transmission window. 5.5.9.3 Metal-free area The antennas ANT1, ANT18 and ANT30 can be flush-mounted on metal. Please allow for a possible reduction in the field data values. 0HWDOIUHHDUHDIRUIOXVKPRXQWLQJ a = 40 mm 0HWDO h > 20 mm h > 20 mm QRWDPHWDOOLFEDVH Metal-free area for ANT 1 D PP E PP 02%<( $17 0HWDOIUHHDUHDIRU IOXVKPRXQWLQJ 1RWH ,IWKHPHWDOIUHHDUHDLVQRW REVHUYHGWKHOLPLWDQGRSHUDWLQJ GLVWDQFHVDUHUHGXFHG Figure 5-12 Figure 5-11 $17 Metal-free area for ANT 18 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-23 Readers 5.5 RF350R 02%<( $17 D PP E PP 6LGHYLHZ 3ODQYLHZ Figure 5-13 5-24 Metal-free area for ANT 30 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.5 RF350R 5.5.9.4 Minimum distance between antennas 'D $17 $17 'E B PP 'D ! B PP 'E ! $17 7KHUHDGHUHOHFWURQLFVFDQEH PRXQWHGGLUHFWO\DORQJVLGHHDFKRWKHU Figure 5-14 Minimum distance for ANT 1 Figure 5-15 Minimum distance for ANT 18 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-25 Readers 5.5 RF350R Figure 5-16 5-26 Minimum distance for ANT 30 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Readers 5.5 RF350R 5.5.9.5 Technical data for antennas Table 5-9 Technical data for antennas ANT1, ANT18 and ANT30 Antenna ANT1 ANT18 ANT30 Read/write distance antenna to transponder (Sg) max 100 mm 15 mm 24 mm Enclosure dimensions in mm 75 x 75 x 20 (L x W x H) M18 x 1.0 x 55 (Ă x thread x L) M30 x 1.5 x 58 (Ă x thread x L) Color Anthracite Pale turquoise Material Plastic PA 12 Plastic Krastin Plug connection 4-pin (pins on antenna side) Antenna cable lengths 3m Type of protection to EN 60529 IP 67 Shock-resistant acc. to EN 60721-3-7, Class 7M2 50 g 1) Vibration-resistant to EN 60721-3-7, Class 7M2 20 g ( 3 to 500 Hz) 1) Attachment of the antenna 2 x M5 screws Ambient temperature ⢠During operation ⢠Transport and storage ⢠⢠MTBF (at +40 °C) 2,5 x 105 hours Approx. weight 80 g IP 67 (at the front) 2 plastic nuts M18 x 2 plastic nuts M30 x 1.0 1.5 -25 °C to +70 °C -40 °C to +85 °C 120 g 150 g 1) Warning: The values for shock and vibration are maximum values and must not be applied continuously. 5.5.9.6 Ordering data for antennas Product description Order No. MOBY E, ANT 1 6GT2398-1CB00 MOBY E, ANT 18 6GT2398-1CA00 MOBY E, ANT 30 6GT2398-1CD00 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 5-27 Readers 5.5 RF350R Dimension drawings for antennas 5.5.9.7 &DEOHOHQJWKP 0LQLPXPEHQGLQJ UDGLXV 20 mm $17FDQEHFRQQHFWHG DWUHDGHUHQG Figure 5-17 Dimension drawing for ANT 1 $QWHQQDHQG 0 )LQHWKUHDGSLWFK &DEOHOHQJWKP 0LQLPXPEHQGLQJ UDGLXV PP $17FDQEHFRQQHFWHG DWUHDGHUHQG Dimension drawing for ANT 18 &DEOHOHQJWKP 0LQLPXPEHQGLQJ UDGLXV PP $QWHQQDKHDG $17FDQEHFRQQHFWHG DWUHDGHUHQG 5-28 $QWHQQDHQG 0 )LQHWKUHDGSLWFK Figure 5-19 $17 6LGHYLHZRI DQWHQQDKHDG $QWHQQDKHDG Figure 5-18 02%<( 02%<( $17 6LGHYLHZRI DQWHQQDKHDG Dimension drawing for ANT 30 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6 Transponders 6.1 6.1 Overview Transponders consist predominantly of logic, FRAM and/or EEPROM. If a transponder moves into the transmission window of the reader, the necessary power for all of the circuit components is generated and monitored by the power supply unit. The pulse-coded information is prepared in such a way that it can be processed further as pure digital signals. The handling of data, including check routines, is performed by the logic, which also manages the various memories. 6.2 6.2.1 6.2 RF320T Features Transponder RF320T Features Application Memory Identification tasks on small assembly lines in harsh industrial environments Read-only area (4 bytes UID) User data area (20 bytes) Read/write range See section Field data Mounting on metal Not possible Recommended distance from metal ⼠20 mm SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-1 Transponders 6.2 RF320T 6.2.2 Metal-free area Mounting of RF320T on metal Direct mounting of the RF320T on metal is not allowed. The following figures show the minimum distance between the RF320T and metal: K!PP 'DWDPHPRU\ 0HWDO 1RQPHWDO Figure 6-1 Mounting of an RF320T on metal with spacer Flush-mounting of RF320T in metal 0HWDO K!PP 'DWDPHPRU\ 1RQPHWDO D!PP Figure 6-2 Flush-mounting of RF320T in metal with spacer At lower values, the field data change significantly, resulting in a reduced range. 6-2 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.2 RF320T 6.2.3 Technical data Table 6-1 Technical data for RF320T Memory size 20 bytes EEPROM (r/w), 4 bytes UID (ro) Memory organization Byte-oriented access, write protection possible in 4-byte blocks MTBF (Mean Time Between Failures) in years 1871 Read cycles Unlimited Write cycles, min. 50 000 at ⤠40 °C, typical > 100 000 Data retention time > 10 years (at < +40 °C) Read/write distance max. 18 mm (see field data) Energy source Inductive power transmission Shock/vibration-resistant to EN 60721-3-7, Class 7 M3 100 g/20 g Torsion and bending load not permissible Fixing Adhesive/M3 screws Recommended spacing from metal > 20 mm Degree of protection per EN 60529 ⢠Housing ⢠Dimensions ⢠Color/material Button ⢠à 27 mm x 4 mm ⢠Black/epoxy resin Ambient temperature ⢠During operation ⢠Storage and transport ⢠⢠Weight Approx. 5 g IP67/IPX9K -25 to +85 °C -40 to +125 °C Note All the technical data listed are typical data and are applicable for an ambient temperature of between 0 C and +50°C and a metal-free environment. 6.2.4 Ordering data Transponder RF320T Order number: Transponder RF320T, button, 20 byte EEPROM, IP 67, -25 °C to +85 °C, d = 27 mm x 4 mm 6GT2800-1CA00 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-3 Transponders 6.2 RF320T 6.2.5 Dimension drawing Dimensions of the device Dimensions in millimeters 6-4 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.3 RF340T 6.3 6.3.1 6.3 RF340T Features Transponder RF340T Features Application Memory Identification tasks on small assembly lines in harsh industrial environments Read-only area (4 bytes UID) Read/write memory (8 KB) OTP 1) memory (20 bytes) Read/write range See section Field data Mounting on metal Direct mounting on metal is possible. 1) OTP: (One Time Programmable) SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-5 Transponders 6.3 RF340T 6.3.2 Metal-free area Direct mounting of the RF340T on metal is permitted. Mounting of RF340T on metal 0HWDO Figure 6-3 Mounting of RF340T on metal Flush-mounting of RF340T in metal: 0HWDO Figure 6-4 Flush-mounting of RF340T in metal The standard value for a is ⼠20 mm. At lower values, the field data change significantly, resulting in a reduction in the range. 6-6 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.3 RF340T 6.3.3 Technical data Table 6-2 Technical data for RF340T Memory size 8 KB Memory organization Blocks of 8 bits / 1 byte Memory configuration ⢠Serial number (UID) ⢠Application memory ⢠OPT memory ⢠⢠⢠4-byte (fixed code) 8189 bytes r/w 20-byte OTP 1) memory Storage technology FRAM / EEPROM MTBF (Mean Time Between Failures) in years 1201 Write cycles, at +40°C Virtually unlimited (>1010) Read cycles Unlimited Transmission rate ⢠Read ⢠Write with RS 422 reader: with IQ-Sense reader: Approx. 0.3 ms / byte approx. 0.3 ms / byte Approx. 20 ms / byte approx. 25 ms / byte Data retention > 10 years Read/write distance 0 to max. 60 mm (depends on reader used) Multitag capability max. 4 transponders Recommended spacing from metal can be directly mounted on metal Power supply Inductive, without battery Degree of protection to EN 60529 Shock to EN 60721-3-7 Vibration to EN 60721-3-7 Torsion and bending load IP68/IPX9K 50 g 20 g Not permitted permanently Housing dimensions Color Material Fixing 48 x 25 x 15 mm (L x W x H) Anthracite PA12 2 screws (M3) Ambient temperature ⢠During operation ⢠Storage and transport -25°C to +85°C -40°C to +85°C Weight Approx. 25 g 1) OTP: (One Time Programmable) 6.3.4 Ordering data Transponder RF340T Order number: Transponder RF340T, 8 KB FRAM, IP 68, -25 °C to +85 °C, 48 x 25 x 15 mm (L x W x H) 6GT2800-4BB00 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-7 Transponders 6.3 RF340T 6.3.5 Dimension drawing 6,(0(16 6,0$7,& 5)7 Dimensions of the device  Dimensions in millimeters 6-8 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.4 RF350T 6.4 6.4.1 6.4 RF350T Features Transponder RF350T Features Application Memory Identification tasks on small assembly lines in harsh industrial environments Read-only area (4 bytes UID) Read/write memory (32 KB) OTP 1) memory (20 bytes) Read/write range See section Field data Mounting on metal Direct mounting on metal is possible. 1) OTP: (One Time Programmable) SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-9 Transponders 6.4 RF350T 6.4.2 Metal-free area Direct mounting of the RF350T on metal is permitted. Mounting of RF350T on metal Figure 6-5 Mounting of RF350T on metal Flush-mounting of RF350T in metal: Figure 6-6 RF350T flush-mounted in metal The standard value for a is ⼠20 mm. At lower values, the field data change significantly, resulting in a reduction in the range. 6-10 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.4 RF350T 6.4.3 Technical data Table 6-3 Technical data for RF350T Memory size 32 KB Memory organization Blocks of 8 bits / 1 byte Memory configuration ⢠Serial number (UID) ⢠Application memory ⢠OTP 1) memory ⢠⢠⢠4-byte (fixed code) 32765 bytes r/w 20 bytes Storage technology FRAM / EEPROM MTBF (Mean Time Between Failures) in years 1201 Write cycles, at +40°C Virtually unlimited (>1010) Read cycles Practically unlimited (>1010) Transmission rate ⢠read ⢠Write with RS 422 reader: with IQ-Sense reader: Approx. 0.3 ms / byte approx. 0.3 ms / byte Approx. 20 ms / byte approx. 25 ms / byte Data retention > 10 years Read/write distance 0 to max. 60 mm (depends on reader used) Multitag capability max. 4 transponders Recommended spacing from metal can be directly mounted on metal Power supply Inductive, without battery Degree of protection to EN 60529 Shock to EN 60721-3-7 Vibration to EN 60721-3-7 Torsion and bending load IP68 50 g 20 g Not permitted permanently Housing dimensions Color Material Fixing 50 x 50 x 20 mm (L x W x H) Anthracite PA12 2 screws M4 Ambient temperature ⢠During operation ⢠Storage and transport -25°C to +85°C -40°C to +85°C Weight Approx. 25 g 1) OTP: (One Time Programmable) 6.4.4 Ordering data RF350T Order number: 32 KB FRAM (read/write) + 4 byte EEPROM (read only), IP 68, -25 °C to +85 °C, dimensions 50 x 50 x 20 (LxWxH in mm) 6GT2800-5BD00 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-11 Transponders 6.4 RF350T 6.4.5 Dimension drawing Dimension drawing of RF350T transponder )L[LQJIUDPH 7UDQVSRQGHU ,QVWDOODWLRQGLDJUDP 7KHWUDQVSRQGHUFDQEHPRXQWHGDVVKRZQZLWK WKHIL[LQJIUDPH Figure 6-7 6-12 RF350T dimension drawing SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.5 RF360T 6.5 6.5.1 6.5 RF360T Features Transponder RF360T Features Application Memory Identification tasks on small assembly lines in harsh industrial environments Read-only area (4 bytes UID) Read/write memory (8 KB) OTP 1) memory (20 bytes) Read/write range See section Field data Mounting on metal Not possible; recommended distance from metal ⼠20 mm 1) OTP. (One Time Programmable) SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-13 Transponders 6.5 RF360T 6.5.2 Metal-free area Direct mounting of the RF360T on metal is not allowed. A distance ⼠20 mm is recommended. This can be achieved using the spacer 6GT2190-0AA00 in combination with the fixing pocket 6GT2190-0AB00. Mounting of RF360T on metal 'DWDVWRUDJHXQLW 0HWDO 1RQPHWDO Figure 6-8 Mounting of RF360T with spacer The standard value for h is ⼠20 mm. Flush-mounting of RF360T in metal: 'DWDVWRUDJHXQLW 0HWDO 1RQPHWDO Figure 6-9 Flush-mounting of RF360T with spacer The standard value for a is ⼠20 mm. At lower values, the field data change significantly, resulting in a reduction in the range. 6-14 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.5 RF360T Dimensions of spacer and fixing pocket for RF360T 'LPHQVLRQVNHWFK )L[LQJSRFNHW*7$% 6SDFHU*7$$ (DUV +ROGLQJNQREV  +ROGLQJFOLS 0DWHULDO3$   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r Figure 6-10 7KHWUDQVSRQGHULVLQVHUWHGLQWRWKH IL[LQJSRFNHW7KHHDUVDUHPRYHGE\ rDQGLQVHUWHGLQWRWKHVSDFHU7KH IL[LQJSRFNHWPXVWEH DOLJQHGVXFKWKDWLWFRYHUV WKHWUDQVSRQGHU VHH)LJXUH /RFNLQJ LVDXWRPDWLF Dimensions of spacer and fixing pocket for RF360T SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-15 Transponders 6.5 RF360T 6.5.3 Technical data Table 6-4 Technical data for RF360T Memory size 8 KB Memory organization Blocks of 8 bits / 1 byte Memory configuration ⢠Serial number (UID) ⢠Application memory ⢠OTP 1) memory ⢠⢠⢠4-byte (fixed code) 8189 bytes r/w 20 bytes Storage technology FRAM / EEPROM MTBF (Mean Time Between Failures) in years 1201 Write cycles, at +40°C Virtually unlimited (>1010) Read cycles Practically unlimited (>1010) Transmission rate ⢠Read ⢠Write with RS 422 reader: with IQ-Sense reader: Approx. 0.3 ms / byte approx. 0.3 ms / byte Approx. 20 ms / byte approx. 25 ms / byte Data retention > 10 years Read/write distance 0 to max. 60 mm (depends on reader used) Multitag capability max. 4 transponders Recommended spacing from metal ⼠20 mm; e.g. using spacer 6GT2190-0AA00 in conjunction with fixing pocket 6GT2190-0AB00 Power supply Inductive, without battery Degree of protection to EN 60529 Shock to EN 60721-3-7 Vibration to EN 60721-3-7 Torsion and bending load IP67 50 g 20 g Not permitted permanently Housing dimensions Color Material Fixing 85.8 x 54.8 x 2.5 mm (L x W x H) Anthracite PA12 2 screws (M3) or with fixing pocket 6GT21900AB00 Ambient temperature ⢠During operation ⢠Storage and transport -25°C to +75°C -40°C to +85°C Weight Approx. 25 g 1) OTP: (One Time Programmable) 6.5.4 6-16 Ordering data RF360T Order number 8 KB FRAM (read/write) + 4 byte EEPROM (read only), IP 67, -25 °C to +75 °C, dimensions 85.8 x 54.8 x 2.5 (LxWxH in mm) 6GT2800-4AC00 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.5 RF360T 6.5.5 Dimension drawing Dimension drawing of RF360T transponder 5 Figure 6-11 Dimensions of RF360T SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-17 Transponders 6.6 Memory configuration of the RF300 tags 6.6 6.6 Memory configuration of the RF300 tags ))) E\WHV 8,' UHDGRQO\ ))) 5)7 5)7 5)7 5)7 )) E\WHV 273 QRWZLWK ,46HQVH 8VHUDUHD UHDGZULWH ((3520 )) . 5)7 )) ))& )) )) )) PD[ EORFNVRI E\WHVHDFK ))& 3K\VLFDOO\LGHQWLFDOPHPRU\ :KHQWKH273DUHDLVXVHGWKH FRUUHVSRQGLQJXVHUDUHD )) )) FDQQRORQJHUEHPRGLILHG UHDGRQO\ 8VHUDUHD UHDGZULWH )5$0 ))& 5)7 5)7 Figure 6-12 . Memory configuration of the RF300 tags The memory configuration of an RF300 tag always comprises an EEPROM memory that has 20 bytes for user data (read/write) and a 4 byte unique serial number (UID, read only). For reasons of standardization, the UID is transferred as an 8 byte value through a read command to address FFF0 with a length of 8. The unused 4 high bytes are filled with zeros. A high-speed FRAM memory (read/write) is available as an option. Depending on the tag type, this is 8 KB (0-1FFC) or 32 KB (0-7FFC) in size. The EEPROM memory area (address FF00-FF13) can also be used as a so-called "OTP" memory (One Time Programmable). The 5 block addresses FF80, FF84, FF88, FF8C and FF90 are used for this purpose. A write command to this block address with a valid length (4, 8, 12, 16, 20 depending on the block address) protects the written data from subsequent overwriting. Notice This operation is not reversible. 6-18 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Transponders 6.6 Memory configuration of the RF300 tags Note The OTP area cannot be used for the IQ-Sense reader variant. When the OTP area is used, it must also be ensured that the blocks are write-protected starting from Block 0consecutively. Examples: 3 blocks (with write command), Block 0, 1, 2 (FF80, length = 12): valid 2 blocks (consecutive), Block 0 (FF80, length =4), Block 1 (FF84, length = 4): valid 2 blocks (consecutive), Block 0 (FF80, length =4), Block 2 (FF88, length = 4): Invalid 1 Block, Block 4 (FF90, length = 4): Invalid The EEPROM user memory (address FF00-FF13, or FF80-FF90) requires significantly more time for writing (approx. 11 ms/byte) than the high-speed FRAM memory. For time-critical applications with a write function, it is therefore recommended that FRAM tags are used (e.g. RF340T, RF350T, RF360T). SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 6-19 Transponders 6.6 Memory configuration of the RF300 tags 6-20 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Communication modules 7.1 7.1.1 7.1 8xIQ-Sense Features Field of application The 8xIQ-Sense module is the link between the RF310R with 8xIQ-Sense interface and SIEMENS S7-300 and functions in the same manner as the communication module (interface module). It can be operated centrally in an S7-300 or decentrally in an ET200M. Figure 7-1 8xIQ-Sense interface module SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 7-1 Communication modules 7.1 8xIQ-Sense 7.1.2 Indicators Status displays The 8xIQ-Sense module has the following LEDs: A green LED, which has no function for RFID devices, and a red SF LED (system fault LED), which indicates the diagnostic state of the module. LEDs 60 [,46HQVH 6) Labeling LED status Meaning Green 0âŚ7 LED per channel Has no function here Red Illuminate Module fault, sensor fault, active teach-in operation, external auxiliary voltage missing SF No fault or no active teach-in Not illuminate operation ; ;)$% 7-2 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Communication modules 7.1 8xIQ-Sense 7.1.3 Configuration Centralized configuration with SIMATIC S7-300 [,46HQVH 2WKHUPRGXOHVIURPWKH6UDQJH LQFOXGLQJ[,46HQVH 6 $60FKDQQHO 5HDGHU 5HDGHU 6,0$7,& 6,0$7,& 5)5 5)5 6,0$7,& 6,0$7,& 5)7 5)7 7UDQVSRQGHU Figure 7-2 5HDGHUZLWK[,46HQVH LQWHUIDFH 7UDQVSRQGHU RF310R reader with 8xIQ-Sense interface Distributed configuration with ET 200M [,46HQVH 2WKHUPRGXOHVIURPWKH6UDQJH LQFOXGLQJ[,46HQVH (70 $60FKDQQHO 5HDGHU 5HDGHU 6,0$7,& 6,0$7,& 5)5 5)5 6,0$7,& 6,0$7,& 5)7 5)7 7UDQVSRQGHU Figure 7-3 5HDGHUZLWK[,46HQVH LQWHUIDFH 7UDQVSRQGHU RF310R reader with 8xIQ-Sense interface SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 7-3 Communication modules 7.1 8xIQ-Sense Pin assignment of RF310R with IQ-Sense interface Table 7-1 Pin assignment of RF310R with IQ-Sense interface Pin Pin, device end, 4-pin M12 Assignment IQ-Sense Not assigned IQ-Sense Not assigned Configuration of connecting cable from 8xIQ-Sense to RF310R 5HDGHUVLGH ,46HQVHVLGH EURZQ 6/*FRQQHFWRU 0VRFNHW EOXH PD[P Figure 7-4 7-4 Cable and pin assignment of RF300 with IQ-Sense SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 Communication modules 7.1 8xIQ-Sense 7.1.4 Addressing The address range of the 8xIQ-Sense module is 16 bytes I/O. This is independent of the choice of channel profiles on the connected device (i.e. the IQ profile IDs in HW Config). Access to memory areas A direct association exists between the number of the channel to which the IQ-Sense device is connected (terminal) and the input and output data area of the module. Based on the address range, the following addresses can be used to access the memory areas: Address = module initial address + (channel no. x 2) SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618 7-5 Communication modules 7.1 8xIQ-Sense Example Module initial address = 280 I/O address for channel 3: 286 &KDQQHODGGUHVVHV LQH[DPSOH 7HUPLQDO 5)5 0 ,46HQVHGHYLFH ,46HQVHGHYLFH ,46HQVHGHYLFH ,46HQVHGHYLFH 0 ಌ 0 0 ಌ 0 0 ಌ )URQW GRRULQWHULRU &KDQQHOQR IRU,46HQVHGHYLFHV / ,4 FKDQQHO FKDQQHO FKDQQHO FKDQQHO FKDQQHO FKDQQHO FKDQQHO FKDQQHO 0 0 ಌ IRU5) ,4 ,4 ,4 5)5 ,46HQVHGHYLFH ,46HQVHGHYLFH ,46HQVHGHYLFH 0 0 ಌ 0 0 ಌ 0 0 ಌ ,46HQVHGHYLFH 0 0 ಌ ,4 ,4 ,4 ,4 Figure 7-5 8xIQ-Sense module: Assignment of terminal pair to memory area Note A maximum of two read/write devices can be operated! Each read/write device uses channel numbers 0 to 3 or 4 to 7. 7-6 SIMATIC RF300 System Manual, Release 04/2006, J31069 D0166-U001-A2-7618
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.3 Linearized : No Modify Date : 2006:06:14 08:40:38+02:00 Create Date : 2006:05:16 07:28:20+02:00 Author : A&D SE EM MS Keywords : J31069, D0166-U001-A2-7618;, Release, 04/2006 Subject : System Manual Page Count : 60 Page Mode : UseOutlines XMP Toolkit : XMP toolkit 2.9.1-14, framework 1.6 About : uuid:01c37a4f-8d7f-4c39-b74b-cb7a92217af4 Producer : Acrobat Distiller 6.0.1 (Windows) Creator Tool : Acrobat PDFMaker 6.0 für Word Metadata Date : 2006:05:16 12:42:29+02:00 Document ID : uuid:dd2bc528-c004-4a31-a8f2-5e2d3fd880c3 Format : application/pdf Title : RFID-Systeme SIMATIC RF300 Creator : A&D SE EM MS Description : System ManualEXIF Metadata provided by EXIF.tools