Siemens 110 Users Manual RDG100 140 160 Operating Instructions

140 1801_a6v10355400[1]

160 to the manual a8674e13-cd7d-4c73-b0d8-e5a2505c497a

2015-02-05

: Siemens Siemens-110-Users-Manual-410622 siemens-110-users-manual-410622 siemens pdf

Open the PDF directly: View PDF PDF.
Page Count: 2

s
Operating Instructions
RDG100/110/140/160
RDG – the electronic room thermostat that allows you to set the ideal room temperature you want.
The thermostat satisfies your individual needs in all operating modes: Comfort, Economy and
Protection. The fan operates either in Automatic mode or at the selected speed when using Manual
mode. You can either rely on the factory settings or make adjustments that suit your individual needs.
Main display Operating mode
Room
temperature Heating mode
Room temperature in
degrees Celsius Electric heater on
Room temperature in
degrees Fahrenheit
Cooling mode
Button lock active Comfort
Alert indicator Economy
Condensation in the
room
Protection mode:
Protection against
frost
Temporary timer
function active Indicator for
selecting mode
Additional user
information
Operating mode
button Fan mode
Fan mode button Automatic
Rotary knob Manual:
Low / medium / high
Changing the room temperature
The room temperature setpoint can be ad
j
usted with the rotar
y
knob when
Comfort mode is active
Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to
decrease the current room temperature setpoint for Comfort mode
The setting range is from 5...40 °C, unless limited by parameters P09 and P10 (for parameter
settings, see reverse side).
Adjusting the fan speed
Press the fan mode button until the desired fan mode is reached
In Automatic mode , the fan speed is automaticall
y
selected b
y
the thermostat
dependin
g
on the setpoint and the actual room temperature. When the room
temperature reaches the setpoint, the fan stops (factory setting) or runs at low
speed (P15).
In Manual mode, the fan operates independentl
y
and alwa
y
s runs at the same
speed: Low / medium / high
Note:
If desired,
y
ou can chan
g
e the fan mode selector option via P03: Manuall
y
onl
y
, or manuall
y
includin
g
Protection mode. Use P15 to set the fan speed in dead zone.
Selecting Comfort mode
Press the operating mode button until symbol appears, indicatin
g
that
Comfort mode is selected
In Comfort mode, the thermostat maintains the setpoint which can be read
j
usted
with the rotary knob
Selecting Protection mode
Press the operating mode button until symbol appears, indicatin
g
that
Protection mode is selected
In Protection mode, the plant stops operatin
g
. If the room temperature falls
below 8 °C, heating is switched on however to protect the room against frost
The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer: Frost protection: ____________ ˚C Heat protection: ______________˚C
Selecting Economy mode
In Economy mode, the room temperature is maintained at a lower or hi
g
her setpoint, thus savin
g
energy and money.
When selecting Economy, make sure that parameter P02 is set to 2
Press the operating mode button until symbol appears
You can chan
g
e the preselected setpoint b
y
ad
j
ustin
g
parameters P11 and P12
(for parameter settings, see reverse side)
Important: The setpoint for Economy can be set to OFF. This means that the thermostat is deactivated!
Risk of frost, i.e. no protective heating or cooling function is provided!
Energy saving tips without sacrificing comfort:
• Air out rooms for short periods of time only, but properly, with the windows wide open
• Never allow the room temperature to exceed 21 °C through heating, and to fall below 25.5 °C through cooling
Button lock
To lock or unlock the buttons manuall
y
, press and hold the fan mode button for
3 seconds. The buttons are locked or unlocked in this manner if P14 is set to 2
If P14 is set to 1, the thermostat automaticall
locks the buttons 10 seconds after
the last adjustment
Temporary timer for extended presence or absence
The Comfort and Economy modes can be temporarily extended by 0.5 to 9.5 hours using the temporary
timer.
1. To set the temporar
y
timer, press and hold the operatin
g
mode button for maximum 3 seconds.
While holding the button, turn the rotary knob clockwise or counterclockwise as required.
a) Turn the rotary knob clockwise to extend Comfort mode.
Display: 0....+9:30
b) Turn the rotary knob counterclockwise to extend Economy mode.
Display: 0....-9:30
2. Release the operating mode button and the mode is temporarily changed, indicated by .
After the temporary timer has elapsed, the thermostat will resume operation in the operatin
g
mode
that was active before:
Extended Comfort mode New operating mode = Economy
Extended Economy mode New operating mode = Comfort
If Economy cannot be selected via the operating mode button (P022), Protection mode will be
used for extended absence instead!
The temporary timer function is aborted whenever a new setting is made
Note:
Extended Comfort mode is also possible when an external contact such as a keycard switch or central time clock is active
To enable this function, the time for the extended period must be set via parameter P68.
Changing from heating to cooling mode
Depending on the type of plant, the changeover from heating to cooling (or vice
versa) is made either automatically by a changeover sensor or a remote change-
over switch, or manually by pressing the operating mode button (see parameter
P01)
To select cooling or heating manually (P01=2), press the operating mode button
until the desired mode appears
With automatic changeover or continuous heating / cooling, symbols /
indicate that the system currently operates in heating or cooling mode
With manual changeover, symbol appears, indicating that the system currently
operates in heating or cooling mode
Control parameters
If you want to change control parameters, proceed as follows:
1. Press both buttons simultaneously for at least 3 seconds.
2. Release them and, within 2 seconds, press the right button again for 3 seconds.
The display shows P01.
3. Select the required parameter by turning the rotary knob.
4. Press button (OK). The current value of the selected parameter starts blinkin
g
and can be
changed by turning the rotary knob.
5. Press button (OK) to confirm the adjusted value, or (Esc) to cancel the change.
If you wish to adjust additional parameters, repeat steps 3 through 5, or press (Esc) to leave the
parameter setting mode.
Parameter list
No. Parameter name Default value Setting range Adj.
P01 Control sequence 2-pipe / 2-
stage:
1 = cooling only
4-pipe:
4 = H and C
0 = heating only
1 = cooling only
2 = H/C changeover, manually
3 = H/C changeover, auto
4 = heating and cooling
P02 Mode selection via operating
mode button
1
1 = Comfort / Protection mode
2 = Comfort / Economy /
Protection mode
P03 Mode selection via fan mode
button
0 0 = Auto / Manual
1 = Manual
2 = Auto / Manual /
Protection mode
P04 Selection of °C or °F 0 0 = °C
1 = °F
P05 Sensor calibration 0.0 K – 3…3 K
P06 Standard temperature display 0 0 = Room temperature
1 = Setpoint
P07 Additional display information 0 0 = --- (no display)
1 = ˚C and ˚F
P08 Comfort basic setpoint 21 °C 5…40 °C
P09 Minimum setpoint limitation in
Comfort mode
5 °C 5…40 °C
P10 Maximum setpoint limitation in
Comfort mode
35 °C 5…40 °C
P11 Setpoint for heating in Economy
mode (WheatEco)
15 °C OFF, 5 °C…WcoolEco
P12 Setpoint for cooling in Economy
mode (WcoolEco)
30 °C OFF, WheatEco…40°C
P13 Electric heater in cooling mode ON OFF = Disabled
ON = Enabled
P14 Button lock 0 0 = Disabled
1 = Automatic
2 = Manual
P15 Fan speed in dead zone
(Comfort mode)
0 0 = Disabled
1 = Stage 1 (H or C)
2 = Stage 1 (Cooling only)
The control parameters displayed depend on the DIP switch settings made
Siemens Switzerland Ltd
Subject to change
B3181.1en
21 Oct 2011

Navigation menu