9300 Series Power Meter
User’s Guide

DANGER
ElectricaI equipment contains hazardous voltages and high speed
moving parts.
Can cause death, serious injury or property damage.
See safety instruction contained herein. Restrict use to qualified personnel.

The use of unauthorized parts in the repair of the equipment
or tampering by unqualified personnel will result in dangerous
conditions that can cause death, serious injury or property
damage.
IMPORTANT
The information contained herein is general in nature and not
intended for specific application purposes. It does not relieve
the user of responsibility to use sound practices in application, installation, operation, and maintenance of the
equipment purchased. Siemens reserves the right to make
changes at any time without notice or obligations. Should a
conflict arise between the general information contained in
this publication and the contents of drawings or supplementary material or both, the latter shall take precedence.
QUALIFIED PERSONNEL
For the purposes of this manual and product labels, "qualified
personnel" is one who is familiar with the installation,
construction, or operation of the equipment and the hazards
involved. In addition, s/he has the following qualifications:
(a) is trained and authorized to energize, de-energize,
clear, ground, and tag circuits and equipment in accordance
with established safety practices.
(b) is trained in the proper care and use of protective gear
equipment such as rubber gloves, hard hat, safety glasses or
face shields, flash clothing, etc., in accordance with established safety procedures
(c) is trained in rendering first aid.
SUMMARY
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible
contingency to be met in connection with installation, operation, or maintenance. Should further information be
desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to the local the sales office.
THE CONTENTS OF THIS INSTRUCTION MANUAL SHALL NOT BECOME PART OF OR MODIFY ANY PRIOR OR
EXISTING AGREEMENT, COMMITMENT OR RELATIONSHIP. THE SALES CONTRACT CONTAINS ALL OBLIGATIONS OF SIEMENS ENERGY & AUTOMATION, INC. THE WARRANTY CONTAINED IN THE CONTRACT
BETWEEN THE PARTIES IS THE SOLE WARRANTY OF SIEMENS ENERGY & AUTOMATION, INC.
ACCESS, ISGS, Isolated Multi-Drop, S7-I/O, SBwin, SAMMS-LV, SAMMS-MV,SEAbus,SIEServe, Static Trip III,
Wisdom, and WinPM are trademark, Sensitrip and Sentron are registered trademarks of Siemens Energy &
Automation, Inc. SIEMENS is a registered trademark and Windows is a trademark of Microsoft Corporation. ION
is a registered trademark of Power Measurement. All other product names mentioned herein are used for identification purposes only and may be the trademarks or registered trademarks of their respective companies.

Notices
Danger
This symbol indicates the presence of dangerous voltage within and
outside the product enclosure that may constitute a risk of electric
shock, serious injury or death to persons if proper precautions are not
followed.
Caution
This symbol alerts the user to the presence of hazards that may cause
minor or moderate injury to persons, damage to property or damage
to the device itself, if proper precautions are not followed.
Note
This symbol directs the user’s attention to important installation,
operating and maintenance instructions.

Installation Considerations
Installation and maintenance of the 9300 Series meter should only be performed by
qualified, competent personnel that have appropriate training and experience
with high voltage and current devices. The meter must be installed in accordance
with all Local and National Electrical Codes.

DANGER
Failure to observe the following instructions may result in severe injury or death.

During normal operation of the 9300 Series meter, hazardous voltages are
present on its terminal strips, and throughout the connected potential
transformer (PT), current transformer (CT), digital (status) input, control power
and external I/O circuits. PT and CT secondary circuits are capable of generating
lethal voltages and currents with their primary circuit energized. Follow
standard safety precautions while performing any installation or service work
(i.e. removing PT fuses, shorting CT secondaries, etc).
The terminal strips on the meter base should not be user-accessible after
installation.
Do not use digital output devices for primary protection functions. These
include applications where the devices perform energy limiting functions or
provide protection of people from injury. Do not use the 9300 Series in
situations where failure of the devices can cause injury or death, or cause
sufficient energy to be released that can start a fire. The meter can be used for
secondary protection functions.
Do not HIPOT/Dielectric test the digital (status) inputs, digital outputs, or
communications terminals. Refer to the label on the 9300 Series meter for the
maximum voltage level the device can withstand.

CAUTION
Observe the following instructions, or permanent damage to the meter may occur.

The 9300 Series meter offers a range of hardware options that affect input
ratings. The 9300 Series meter’s serial number label lists all equipped options.
Applying current levels incompatible with the current inputs will permanently
damage the meter. This document provides installation instructions applicable
to each hardware option.
The 9300 Series meter’s chassis ground must be properly connected to the
switchgear earth ground for the noise and surge protection circuitry to function
correctly. Failure to do so will void the warranty.
Terminal screw torque: Barrier-type (current, voltage, and relay terminal screws:
1.35 Nm (1.00 ft-lbf) max. Captured-wire type (digital inputs/outputs,
communications, power supply: 0.90 Nm (0.66 ft.lbf) max.

FCC Notice
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his
own expense. The Ringer Equivalence Number (REN) for the 9300 Series optional
internal modem is 0.6. Connection to the 9300 Series internal modem should be
made via an FCC Part 68 compliant telephone cord (not supplied). The 9300 Series
cannot be used on a public coin phone service or party line services.

Network Compatibility Notice for the Internal Modem
The internal modem in meters equipped with this option is compatible with the
telephone systems of most countries in the world, with the exception of Australia
and New Zealand. Use in some countries may require modification of the internal
modem’s initialization strings. If problems using the modem on your phone
system occur, please contact Siemens Customer Service

Standards Compliance

CSA: Certified to CAN/ Certified to
CSA C22.2 No.1010-1 UL 3111

CE: approved

Contents
Chapter 1

Introduction
9300 Series Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
The ACCESS Meter in an Enterprise Energy Management System . . . . . . . . 14
Data Display and Analysis Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Communications Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Digital and Analog I/O Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
The Meter is Factory-Configured and Ready to Operate . . . . . . . . . . . . . . . . . . . . 17
Meter Firmware Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Ethernet Card Firmware Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Using this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Getting More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Chapter 2

Using the Front Panel
Displaying Data with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Front Panel Display Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Default Front Panel Display Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Configuring the Meter with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . 27
The Front Panel’s Setup Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Clear Functions Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Quick Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Advanced Meter Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Display Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Screen Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Nameplate Info Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Security Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Diagnostic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Custom Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Before Customizing the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Chapter 3

Default Meter Functionality
Default Meter Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Communications Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Power Quality Setup (9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Data Logging Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Setpoint Configuration (9330 and 9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Meter Clock Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Demand Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Factory Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

49
50
52
53

Third Party Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Using the Modbus RTU Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Using the Modbus/TCP Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Using the DNP 3.0 Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Using the Profibus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Restoring the Factory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

Chapter 4

Using ACCESS Software
WinPM.Net Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
WinPM.Net: Management Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Configuring Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
WinPM.Net: Vista . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Displaying Data with Vista . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Customizing the Vista Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
WinPM.Net: Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Basics of ION Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Designer’s Main Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Viewing Real-time Data in Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Changing Setup Registers with Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Customizing Frameworks in Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
WinPM.Net: Reporter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Pre-configured Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Report Creation and Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
ION Setup Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Configuring Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Basic Meter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Displaying Data with ION Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

Chapter 5

Features and Applications
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
RS-485 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Optical Port Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Internal Modem Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Profibus Connections (9300) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Internet Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
WebMeter and MeterM@il . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
WebReach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

Telnet and Hyperterminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

Digital and Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Specifying a Port In an ION Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Using the Onboard Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Using the Onboard Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Using the Optional Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Using the Optional Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Data and Event Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Data Logging (9330 and 9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Event Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Logging and Recording Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Meter Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Standard Meter Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Residual Current Calculation (I4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Alerting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Alerting ION Software via the Alarm Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Alerting via an Alphanumeric Pager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Alerting via a Numeric Pager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Alerting via Email (9330 and 9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134

Chapter 6

Revenue Metering
9300 Series Revenue Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Revenue Meter Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Revenue Meter Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Differences between Standard and Revenue Models . . . . . . . . . . . . . . . . . . . . . . 136
Revenue Meter Energy Register Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Additional Revenue Metering Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Security Mechanisms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Anti-Tamper Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Password Protected Min/Max Register Resets . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Hardware-based Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Configuring the Revenue Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Before Disassembling the Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Inserting the Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
CT & PT Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

Chapter 7

Hardware Reference
Standard Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Communications Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
COM1 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

COM 2 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COM 3 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Profibus Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Internal Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

147
148
148
149
150
151

I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Options and Retrofits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Terminal Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Remote Modular Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Switchboard Case . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Relay Expansion Board (Grayhill Rack) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
TRAN Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165

1

Introduction
The 9300 Series intelligent metering and control devices are typically used in
enterprise energy management systems such as feeder monitoring and
submetering, and offer unmatched value, functionality, and ease of use. These
meters interface to WinPM.Net software or other automation systems for fast
information sharing and analysis. The 9300 meter is an ideal analog meter
replacement with a multitude of power and energy measurements, analog and
digital I/O, communication ports, and industry-standard protocols. The 9330
meter adds on-board data storage, alarms, and an optional modem. The 9350
meter is further augmented by more sophisticated power quality analysis and a
call-back-on-alarm feature.

In This Chapter
9300 Series Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
The ACCESS Meter in an Enterprise Energy Management System . . . . . . . . 14
Data Display and Analysis Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Communications Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Digital and Analog I/O Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
The Meter is Factory-Configured and Ready to Operate . . . . . . . . . . . . . . . . . . . . 17
Meter Firmware Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Ethernet Card Firmware Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Using this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Getting More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

9300 Series Meters

9300 Series User’s Guide

9300 Series Meters
The 9300 Series meters are intelligent metering and control devices suited to a wide
range of applications. The meters can be used as stand-alone devices, but their
extensive capabilities are fully realized when used as part of an enterprise energy
management (EEM) system.
EEM systems give energy suppliers, service providers, and large industrial and
commercial energy consumers the tools to meet all the challenges and
opportunities of the new energy environment. EEM systems use real-time
information and control to directly address a broad range of requirements
throughout the power delivery chain and across an entire enterprise. These
systems offer an integrated solution to managing new billing structures,
distributed generation, energy purchasing, energy cost control, operational
efficiency, and power quality and reliability.
ION® technology uniquely delivers the benefits of enterprise energy management
through an efficient, economical, and scalable architecture using web-enabled
software and intelligent metering and control devices. ACCESS systems place
intelligence everywhere its needed, delivering information and control to
everyone that needs it, wherever they are. This gives all parties the necessary
information to make the best energy decisions, and the control to act on them.
Systems can span widely dispersed geographic locations and multiple points
within each site. A single, shared system delivers a broad range of functionality
that can satisfy the needs of many different groups within an enterprise, while
integrating seamlessly with existing systems.

Page 12

Chapter 1 - Introduction

9300 Series User’s Guide

9300 Series Meters

WinPM.Net™ is a powerful web-ready software suite that can process, analyze,
store, and share information from across your entire organization. Its
compatibility and flexibility means you can introduce individual components, at a
pace you decide, while maintaining your original investments. You can access
information and alarms from any workstation, pager, PDA, or cell phone locally or
around the world, in the format you require. You can also perform coordinated
load and equipment control functions, either manually or automatically. ACCESS
software collects data automatically from ACCESS meters and third-party devices,
so you can manage a single site or a global network of devices. ACCESS software
and hardware products reduce cost of installation and ownership by leverage
existing corporate networks and popular networking technologies, including
serial, wireless, modem, Ethernet and Internet links.
A wide selection of ACCESS intelligent metering and control devices are available,
with choices to meet the specific needs of various key points within an enterprise.
Devices offer a range of high accuracy metering, power quality and reliability
analysis, data and event logging, alarming, control and communications.
This manual discusses the use of all 9300 Series meters. Throughout the manual,
the term “meter” generally refers to all meter models. All differences between the
models, such as a feature specific to one model, are indicated with the appropriate
model number.
The 9300 Series meters can be used effectively in numerous supply side and demand
side operations. Some common meter applications are:
Revenue Metering
Substation Automation
Replacement of Analog Transducers
Commercial/Industrial Metering
Demand Monitoring
Genset Applications
Universal Metering (9330 and 9350)
Utility Sub-Metering (9330 and 9350)
These are just a few of the many possibilities. Contact Siemens Customer Service
if you would like assistance with your application.

Chapter 1 - Introduction

Page 13

The ACCESS Meter in an Enterprise Energy Management System

9300 Series User’s Guide

The ACCESS Meter in an Enterprise Energy Management
System
Applications that include the meter typically require additional equipment.
Display and analysis software tools are almost always used to manage, interpret
and distribute the data measured or logged by a meter. There are usually a variety
of tools used, and often these tools are connected using different communications
standards and protocols. In many cases, a meter must also provide control
capabilities and device-level data sharing.
The meter can adapt to many situations. Advanced communications allow data to
be shared simultaneously across multiple networks, built-in I/O provides
monitoring and control capabilities, and a variety of display and analysis tools can
be used to monitor your power system.
Power System Connections

Internet Connectivity

Protocols

Phase voltage and phase current
from Wye, Delta or single-phase
power systems.

- MeterM@il
- WebMeter

- ION
- Modbus RTU
- DNP V3.00
- Profibus (9300)

Data Analysis Tools
- WinPM.Net Software
- 3rd-Party tools

Corporate Network

I/O

Communications

- Energy Pulses
- Breaker Closures
- Digital Signals
- Analog Transducers

- RS-485
- Optical Infrared
- 10 Base-T Ethernet
- 33.6 kbps internal modem
- Profibus port (9300)

On-Site Data Display
- Remote Modular Display
Remote Data Display
- Vista
- WebReach

Data Display and Analysis Tools
Not only does the meter’s front panel allow meter configuration and data display,
but the meter also integrates seamlessly with display and analysis software
available from Siemens. WinPM.Net software is the network and device
configuration software that also lets you analyze and monitor your system and
produce reports for any department in an organization. Furthermore, you can use
data acquired by the meter in a variety of third-party systems. ACCESS software
is designed to make use of all the available advanced capabilities.

Page 14

Chapter 1 - Introduction

9300 Series User’s Guide

Data Display and Analysis Tools

The Front Panel
Local monitoring and standalone applications are facilitated by the meter’s front
panel interface. The front panel combines real-time display features as well as
device configuration functions.

The Remote Modular Display
The Remote Modular Display (RMD) can be added to an existing 9300 SeriesTRAN (Transducer) model to facilitate local monitoring and standalone
applications. The 9300 Series Basic Model provides an integrated front panel
display.
Both the front panel and RMD combine real-time display features with limited
device configuration functions. When used in combination with an WinPM.Net
system, the display provides an interface for field personnel.

WebMeter® Embedded Web Server Feature
An on-board web server combined with an Ethernet port provides quick and easy
access to real-time energy and basic power quality information without special
software: this is WebMeter functionality. The built-in web pages display a range of
energy and basic power quality information through the web-enabled device;
these pages even support basic meter configuration tasks.

MeterM@il® Internal E-Mail Server Feature
Configure the meter to automatically email high-priority alarm notifications or
scheduled system-status update messages to anyone, anywhere within the facility
or around the world. Specify the type of event that triggers an email alert, such as
power quality disturbances or logged data at any pre-determined interval, and
have your ACCESS software administrator program the meter to respond with a
MeterM@il message when these events occur. MeterM@il messages can be
received like any email message over a workstation, cell phone, pager, or PDA.

XML Compatibility
The meters can exchange information using industry-standard XML format. This
simple machine-readable format supports easy integration with custom reporting,
spreadsheet, database, and other applications.

WinPM.Net Software
The complete WinPM.Net software package enables the meter to be part of a fully
networked information system with other meters and local and wide-area
computer networks. WinPM.Net is recommended for all power monitoring
systems where advanced analysis and control capabilities are required.
WinPM.Net provides tools for managing your power monitoring network,
logging data, analyzing real-time and logged data, generating power system
reports, and creating custom functionality at the meter level.

Chapter 1 - Introduction

Page 15

Communications Protocols

9300 Series User’s Guide

WinPM.Net also offers two ways to remotely view information through a web
browser: WebReach and Microsoft Terminal Services.
WebReach only requires an URL to display a meter’s real-time data and select
views of historical and waveform data from a web browser; there is no client
machine configuration. WebReach is a data display application; there is no
control functionality available through it.
Microsoft Terminal Services enable full WinPM.Net functionality, including
control features. Some client machine configuration is required.

ION Setup™ Software
ION Setup is a meter configuration tool designed specifically to configure and test
meters. ION Setup offers an intuitive graphical interface for performing basic
meter setup, installing templates into meters, viewing real-time and reset
accumulated values, verifying meter calibration and measurements, and setting
up advanced security.

Communications Protocols
The 9300 Series meter can be integrated into various industry-standard
networks. Data that is measured by the unit can be made available to other devices
using ACCESS, Modbus, and DNP V3.00 (9330 and 9350) protocols. The 9300
meter also has the option available to communicate using the Profibus protocol.
You can also configure the meter to import data from devices on these networks.
With these advanced communications functions, the power of the meter can be
utilized in most existing power monitoring systems. Any data display and analysis
software that works with Modbus or DNP devices will also function with the 9300
Series meter.
The standard meter has one infrared port and one or two RS-485 communications
ports (the 9300 has one, the 9330 and 9350 have two). These ports are capable of
data rates up to 19,200 bps. The infrared port on the front panel is compatible with
an ANSI C12.13 Type II magnetic optical communications coupler. It can be used
to communicate real-time measurements via ACCESS, Modbus, or DNP protocols.
The RS-485 and infrared ports can communicate simultaneously. Ordering options
can include a 10Base-T Ethernet port, a 33.6 kbps internal modem, and a Profibus
port, depending on the model type of your 9300 Series meter.

Digital and Analog I/O Options
The 9300 Series meter offers a variety of analog and digital I/O combinations. I/O
connections to the meter are made via captured-wire terminals on the meter. The
analog I/O option can be specified for any 9300 Series meter, allowing you to
monitor a wide range of conditions, such as flow rates, device cycles (RPM), fuel
levels, oil pressures and transformer temperatures. You can output energy pulses
to an RTU or perform equipment control operations.

Page 16

Chapter 1 - Introduction

9300 Series User’s Guide

The Meter is Factory-Configured and Ready to Operate

Digital Outputs
All 9300 Series meters have four programmable digital output ports. These are
suitable for pulsing or controlling relays. The Infrared Data Port and/or a rear
panel LED can also be used for energy pulsing.

Status Inputs
Four optically isolated digital inputs on the 9330 and 9350 meters can monitor
status, count transducer pulses, breaker trips and pulses from any external “volts
free” dry contact.

Analog Inputs/Outputs
Any meter in the 9300 Series can be equipped with an optional analog I/O card
featuring:
4 analog inputs accepting 0–1mA or 0–20mA, (scalable to 4-20mA)
4 analog outputs accepting 0–1mA or 0–20mA, (scalable to 4-20mA)

NOTE
When equipped with analog I/O, TRAN base units cannot be ordered with a remote display (RMD).

REB Option
Adding the Relay Expansion Board (REB) option can enhance the functionality of
the onboard digital outputs. The REB option includes a four-position Grayhill
module rack and a 100-240VAC to 5VDC power supply. Grayhill modules are
ordered separately.

The Meter is Factory-Configured and Ready to Operate
Although the 9300 Series meter is fully customizable, it is shipped from the factory
with many functions pre-configured. Once installation and basic setup are
performed, all of the basic measurements and energy calculations are ready to
operate, right out of the box. Many users will find that the factory configuration
will serve their purposes without performing any additional configuration.

Chapter 1 - Introduction

Page 17

Meter Firmware Revision History

9300 Series User’s Guide

Meter Firmware Revision History
9300 Models
Firmware
Version

Release Date

Firmware Enhancements

V250

June 2000

Rev B Hardware Initial Release
Improved communications performance
Four Calibration Pulsers added
Harmonic update times improved

V265

March 2001

Analog I/O supported
New Calibration procedure

V271

July 2002

Adds Web Server capabilities when combined with ETH73V272 firmware

9330 Models
Firmware
Version

Release Date

Firmware Enhancements

V250

June 2000

Rev B Hardware Initial Release
Improved communications performance
Adds 4 Calibration Pulser modules to template
Harmonic update times improved

V265

March 2001

Analog I/O supported.
New Calibration procedure

V271

July 2002

Adds Web Server capabilities when combined with ETH73V272 firmware

V272

September 2002

Maintenance Release

V273

September 2002

Maintenance Release

9350 Models
Firmware
Version

Release Date

Firmware Enhancements

V265

March 2001

Analog I/O supported
New Calibration procedure

V271

July 2002

Adds Web Server capabilities when combined with ETH73V272 firmware, MeterM@il (data logs)
and alerts.

V272

September 2002

Maintenance Release

V273

September 2002

Maintenance Release

V274

November 2002

Maintenance Release

Page 18

Chapter 1 - Introduction

9300 Series User’s Guide

Ethernet Card Firmware Revision History

Ethernet Card Firmware Revision History
Firmware
Version

Release Date

Firmware Enhancements

V102

June 2000

Maintenance release (support for Rev B hardware)

V270

September 2001

MeterM@il support added (with 9330V270 firmware)
Modbus TCP support added

V272

July 2002

Adds Web Server capabilities when combined with 9300 Series V271 firmware, MeterM@il (data
logs) for the 9330 and 9350, and alerts for the 9350

Chapter 1 - Introduction

Page 19

Using this Guide

9300 Series User’s Guide

Using this Guide
This User’s Guide is directed at three types of user: the typical user or operator, the
system administrator, and the advanced user. You might not fit into any of these
groups directly, or perhaps you are both an operator and an administrator. These
classifications are intended to make this guide easier to navigate with respect to
which information is appropriate to your needs.
Typical User or Operator
Most users simply want to display the data provided by the factory-configured
meter. These users want fast access to data through the front panel, ACCESS
software, or a third-party protocol such as Modbus or DNP.
System Administrator or Manager
Some users need to make minor adjustments so that their meters “fit” their power
systems: data recording intervals, demand sub-intervals and other parameters
may need to be set before the meter’s setup is complete. These users will use the
front panel, or ACCESS software to change settings in the device’s operating
software. (WinPM.Net is highly recommended.)
Advanced User or Systems Integrator
Advanced users may want to make use of the flexibility and power provided by
the device’s operating software. These users will need to become familiar with the
ION Architecture, and the ACCESS software tools used to customize the device’s
operation.

Before You Can Use this Guide
By the time you are ready to use this guide, your meter should be installed, basic
setup should have been performed, and communications/basic operation should
have been verified. If the unit is not yet installed and operational, refer to the 9300
Series Installation Guide shipped with the meter.

Getting More Information
Additional information is available from Siemens. Check our web site at
www.sea.siemens.com, contact your local Siemens representative, or contact
Siemens directly (contact information is provided on the first page of this
document). Documents that are related to the installation, operation and
application of the meter are as follows:
Installation Guide
This brief instructional manual is shipped with each meter. It details the mounting,
wiring and basic setup of the device.
ION Programmer’s Reference
This online reference contains detailed descriptions of all of the modules in each
ACCESS meter.

Page 20

Chapter 1 - Introduction

9300 Series User’s Guide

Getting More Information

WinPM.Net Getting Started Guide
This guide explains the installation and configuration of the WinPM.Net software
suite.
Online WinPM.Net Help
Each WinPM.Net software component has an in-depth online help system.
Application Notes
Online application notes offer detailed, high-level descriptions of real-world
situations, where Siemens’s ACCESS devices and ACCESS software provide
beneficial solutions.

Chapter 1 - Introduction

Page 21

Getting More Information

Page 22

9300 Series User’s Guide

Chapter 1 - Introduction

2

Using The Front Panel
The meter’s front panel is used for both display and configuration purposes. The
liquid crystal display (LCD) screen and the numerous selection, navigation, and
configuration buttons allow quick access to basic meter configuration provided by
special setup screens. The front panel also provides access to the settings of many
other meter functions, such as customizing the type of data the meter displays.

In This Chapter
Displaying Data with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Front Panel Display Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Default Front Panel Display Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Configuring the Meter with the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . 27
The Front Panel’s Setup Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Clear Functions Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Quick Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Advanced Meter Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Display Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Screen Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Nameplate Info Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Security Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Diagnostic Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Custom Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Before Customizing the Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Displaying Data with the Front Panel

9300 Series User’s Guide

Displaying Data with the Front Panel
The front panel provides a detailed graphics and text display for the meter. The
front panel is configured at the factory with eight displays showing some of the
more commonly used power system values measured by the device (refer to
“Default Front Panel Display Screens”). A Remote Modular Display (RMD) can be
added to an existing TRAN meter to provide a front panel display.

Measurements are
displayed here.

Use the arrow buttons
to scroll through data
display screens.

Optical (Infrared)
port

Press the round button to
access the Setup menu
or make a selection.

Button Functions
Press the Up/Down arrow buttons to scroll through the data display screens. You
do not require password authorization to view these screens. The round button,
when pressed, provides access to the Setup menu. Use the front panel’s three
buttons to navigate this menu, and enter settings into the meter. For more
information on setting up the meter using the front panel, refer to “Configuring the
Meter with the Front Panel” on page 27.

Front Panel Display Resolution
When displaying numeric values, the front panel display screen can show up to
nine digits of resolution. This nine digit resolution is available when the display
screen is set to display one parameter. Any multi-parameter screen displays up to
five digits of resolution.
If you require more digit resolution than is available, use ACCESS software to
display data. If a value is too large to be displayed on your display screen (i.e.
greater than 99,999 on a two parameter screen), the front panel uses an abbreviated
engineering notation with standard metric prefixes to indicate the magnitude of
the reading. The following table provides some examples:

Page 24

Front Panel Display

Value

124K0

124,000

124M0

124,000,000

1G240

1, 240, 000, 000

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Default Front Panel Display Screens

Numeric values are displayed in base units; voltages are displayed in volts, while
current is displayed in amps. The following values, however, are displayed in kilo
units rather than base units since kilo is the most frequently used value range:
kW
kVA
kVAR
When viewing these parameters with the front panel, remember that the values are
already multiplied by 1000. For example, the reading below indicates
120,000 kilowatts, not 120,000 watts.
kW total

120K0

INVLD and N/A Messages
If the front panel is unable to read a numeric or status value from the meter, it will
display either INVLD or N/A in place of the value. INVLD indicates that the value
received cannot be displayed because it is too large (above 9G999). N/A appears if
the register is not available.

Default Front Panel Display Screens
The meter’s eight default data displays are as follows:

Chapter 2 - Using The Front Panel

Display 1 (kWh net)

Display 5 (Power)

Net Energy

Total Power (true, reactive,
and apparent), Power Factor.

Display 2 (kWh swd / mx)

Display 6 (Frequency)

Present Interval and Maximum
Sliding Window Demand

Frequency

Display 3 (Volts)

Display 7 (V-THD)

Per-phase and average
line-to-line voltage

Per-phase Voltage
Total Harmonic Distortion

Page 25

Default Front Panel Display Screens

9300 Series User’s Guide

Display 4 (Amps)

Display 8 (I-THD)

Per-phase and
average current

Per-phase Current
Total Harmonic Distortion

NOTE
Your default data display screens will differ if the meter is in Fixed mode (refer to “Display Mode” on
page 34), or if your meter has custom displays.

Page 26

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Configuring the Meter with the Front Panel

Configuring the Meter with the Front Panel
The front panel provides meter setup capability at the meter’s installed location.
All of the meter’s setup registers can be configured moving through menus on the
front panel’s screen (ION module links cannot be modified using the front panel).
The front panel also provides quick access to parameter reset for common
cumulative parameters.

The Front Panel’s Setup Menus
To access the front panel’s device configuration functions, press the round button.
The Setup menu appears listing the meter’s front panel setup options:
Setup Option

Description

Clear Functions

Resets Min/Max, Sliding Window Demand, Energy, Thermal Demand, Peak
Demand Registers, Harmonics Min/Max, Status Counters, Manual Waveform
Capture, and Disturbance Counts.

Quick Setup

Changes settings in the Communications, Power Meter, and Sag/Swell modules.

Adv Meter
Setup

Provides access to all the modules in the meter.

Display Setup

Customizes the appearance of the display screen.

Screen Setup

Customizes the style and values appearing on the display screens.

Nameplate Info

Displays information about the device.

Security

Allows you to modify your password. See “Front Panel Password Security” on
page 28.

Diagnostics

Screens to aid in troubleshooting; refer to “Diagnostic Menu” on page 35.

Accessing the Setup Menus
The three buttons are used to navigate the on-screen menus and edit setup
registers. While the device is displaying data, the Up/Down buttons scroll through
the different display screens. Press the round button at this time to access the Setup
menu.

Navigating Menus
Each menu has a title displayed at the top of the display screen and menu items
displayed below the title. Use the arrow buttons to scroll through the menu items.
To select an item that is highlighted, press the round button. To return to the
previous screen, select RETURN. Return to the data display screens by repeatedly
selecting RETURN.

Chapter 2 - Using The Front Panel

Page 27

Clear Functions Menu

9300 Series User’s Guide

Editing Registers
To edit the value of a register, navigate the registers using the arrow keys until the
register you want is highlighted, then press the round button. The register appears
in one of two ways: as a number, or as an option selected from a menu. Once you
have entered the password (if required), a YES or NO verification screen appears
showing the new value of the register. Select YES to change the value of the setup
register; select NO to return to the previous screen without changing the value.
Numeric Registers
Use the arrow buttons to change the value of the digit above the
cursor.
Change the position of the cursor by holding down an arrow key for about one
second. Holding the up arrow button moves the cursor left one position, and
holding the right arrow button moves the cursor right one position. Once you have
the value you want, press the round button.
Enumerated Registers
Some registers are displayed as a menu of options. The current value of the register
will be displayed in the list with an asterix (*) on either side of it. Use the arrow
buttons to highlight the setting you want, and press the round button.

Front Panel Password Security
The password is required when you make a change to a register through the front
panel. Once you have entered a valid password, you can make multiple register
changes. The password is factory set at ‘00000’ (5 zeros). Press the round button
when you have entered the correct front panel password. If you need to change the
password, refer to the section “Security Menu” on page 35.

Clear Functions Menu
The CLEAR FUNCTIONS menu allows you to reset cumulative parameters. To access
the Clear Functions screen, press the round button while the meter is displaying
data; scroll down the Setup menu and select CLEAR FUNCTIONS.
Peak Demand Reset
The following Demand parameters are reset when you select PEAK DMD RSET:
Maximum and Minimum Rolling (Sliding Window) Demand (kW, kVAR, kVA)
Maximum and Minimum Thermal Demand (kW, kVAR, kVA)
Min/Max Reset
The minimum and the maximum values for each the following parameters are reset
when you select MNMX RSET:

Page 28

Phase and average Current

Frequency

Line-to-line voltages

PF lead and PF lag

Line-to-neutral voltages

Total kW, kVAR, kVA

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Clear Functions Menu

Sliding Window Demand Reset
These Sliding Window Demand values are reset when SWDEMAND RSET is selected:
Average Current (I avg) SWD

kW SWD

kVAR SWD

kVA SWD

Thermal Demand Reset
The following Thermal Demand parameters are reset when TDEMAND RSET is
selected:
Average Current TD

kW TD

kVAR TD

kVA TD

Manual Waveform Trigger
Select this menu item to capture your per-phase current and voltage waveforms.
Harmonics Min/Max Reset
The following Harmonics Parameters are reset when HARM MNMX RSET is selected:
Current Total HD (Ia, Ib, Ic)
Voltage Total HD (Va, Vb, Vc)
Energy Reset
The following energy parameters are reset when ENERGY RSET is selected:
kWh import, export, total and net
kVAh
kVARh import, export, total and net
Status Counters
Each of the four Status Counters that monitor the number of times each Status
input changes are reset when S COUNT RSET is selected.
Disturbance Counter Reset
Resets the counter in the Sag / Swell module that keeps track of how many Sags or
Swells are detected by the meter.

Chapter 2 - Using The Front Panel

Page 29

Quick Setup Menu

9300 Series User’s Guide

Quick Setup Menu
Select QUICK SETUP from the Setup menu to access to the Power Meter module and
the Communications module settings. These settings are all configured when the
meter is initially put into service — typically you will not need to change these
settings once the meter is operational.
Comm 1, Comm 2, and Infrared Comm Menus
The setup registers for the three serial Communication modules are as follows:

1

Register

Default Value

Description

CM1 Unit ID

Factory Set 1

The communications ID for COM 1

CM1 Baud Rate

9600

The baud rate of the COM 1 port

CM1 Protocol

ION

The communications protocol for COM 1

CM2 Unit ID

Factory Set 1

The communications ID for COM 2

CM2 Baud Rate

9600

The baud rate of the COM 2 port

CM2 Protocol

ION

The communications protocol for COM 2

IR1 Unit ID

Factory Set 1

The communications ID for the Infrared port

IR1 Baud Rate

9600

The baud rate of the Infrared port

IR1 Protocol

ION

The communications protocol for the Infrared port

The factory set Unit ID is based on the serial number of the meter.

Refer to the online ION Programmer’s Reference for details on each Communications
module’s additional registers and their default settings.
Profibus Comm Menu (9300)
In addition to the existing communications ports available on the 9300 meter, the
9300-Profibus option is equipped with a Profibus port capable of operating at baud
rates up to 12 Mbps. You must configure the 9300-Profibus before the meter can
provide power system data to the Profibus network.
The Comm 4 Profibus Communications module has one setting: PB Address. The
default value of this register is 126. Use the front panel to configure this setting to
a unique PB Address on your Profibus network.

Page 30

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Quick Setup Menu

Ethernet Menu
The Ethernet module controls the meter’s optional 10Base-T port. Configuring the
Ethernet module registers incorrectly can cause network disruptions. The
following settings can be accessed through the Ethernet Menu:
Setup Register

Function

IP Address

Sets the IP Address for the meter

Subnet Mask

Used if subnetting applies to your network – see your network
administrator

Gateway

Used in multiple network configurations – see your network
administrator

SMTP Server 1

Sets the IP Address for the SMTP Mail Server that is configured to
forward mail from the meter to the final destination

SMTP Connection Timeout

1

Webserver Config Access
1

Sets the minimum time that the meter waits for a connection to an
SMTP server
Enables configuration of meter with a web browser

Settings available for 9330 and 9350 meters with MeterM@il.

Typically your network administrator will provide you with the appropriate IP
address for the meter. The Subnet Mask and Gateway settings are required if you
have communications between multiple Ethernet networks, and if subnetting is
implemented. The SMTP Server and SMTP Connection Timeout settings are
required for MeterM@il (9330 and 9350 meters). Webserver Config Access allows you
to enable/disable configuration of your meter with a web browser.
Power Meter Menu
Select POWER METER from the Quick Setup menu to access the following settings:

Chapter 2 - Using The Front Panel

Register

Default Value

Description

PM1 Volts Mode

4W-WYE

The power system’s configuration – WYE, DELTA, etc.

PM1 PT Prim

347

The Potential Transformer’s primary winding voltage rating.

PM1 PT Sec

347

The Potential Transformer’s secondary winding voltage rating.

PM1 CT Prim

5

The Current Transformer’s primary winding current rating.

PM1 CT Sec

5

The Current Transformer’s secondary winding current rating.

PM1 V1 Polarity

NORMAL

The polarity of the Potential Transformer on V1.

PM1 V2 Polarity

NORMAL

The polarity of the Potential Transformer on V2.

PM1 V3 Polarity

NORMAL

The polarity of the Potential Transformer on V3.

PM1 I1 Polarity

NORMAL

The polarity of the Current Transformer on I1.

PM1 I2 Polarity

NORMAL

The polarity of the Current Transformer on I2.

PM1 I3 Polarity

NORMAL

The polarity of the Current Transformer on I3.

Page 31

Advanced Meter Setup Menu

9300 Series User’s Guide

The remaining Power Meter module setup options and their default values are
given in the online ION Programmer’s Reference. In most cases you can leave them
at their default settings and the meter will function properly.
Sag/Swell Module Settings (9350)
You must set the Sag/Swell module’s Nom Volts setup register to a voltage that
represents the nominal voltage for your power system (for example, 120). If the
Sag/Swell module’s Nom Volts setup register is set to zero, all Sag/Swell module
functions are disabled.

CAUTION
The Nom Volts setup register MUST be set to your primary power system voltage, or the Power Quality
features of the 9350 meter will not properly function.

.

Register

Default

Description

Swell Lim 1

106

The limit a monitored voltage must exceed in order for the meter to
classify it as an overvoltage condition.

88

The limit a monitored voltage must fall below in order for the meter
to classify it as an undervoltage condition.

0

The primary power system voltage (line-to-line voltage for Delta
systems, and line-to-neutral voltage for Wye systems).

Sag Lim

1

Nom Volts 2
1

The ANSI C84.1 1989 standard recommends a temporary overvoltage limit of 106% for Range B
voltage levels, and a temporary undervoltage limit of 88% for load voltages and 92% for the service
entrance.

2

The primary power system voltage is sometimes different than the PT Primary setup register value; i.e.
when the PT Primary is used to indicate winding ratio rather than primary voltage.

Advanced Meter Setup Menu
The Advanced Meter Setup menu provides access to the setup registers of every ION
module in the meter. To access this menu screen, select ADV METER SETUP from the
Setup menu. Follow this procedure to access a setup register:
1.

From the Feature Manager screen, select the module’s type.

2.

Select the module you want to configure from the list of available modules.

3.

From the list of the module’s setup registers, select the one you want to
configure.

4.

Edit the value of the register (see “Editing Registers” on page 3–28).

You may be prompted to enter your password (see “Front Panel Password
Security” on page 3–28). Select YES to the next prompt to change the value of the
register. Select NO if you want to leave the screen without making any changes.
Refer to the online ION Programmer’s Reference for complete details on each setup
register’s function.

Page 32

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Display Setup Menu

Display Setup Menu
When you select DISPLAY SETUP from the Setup menu, you get these settings:
Display Setup Option

Default

Description

AutoScroll

0 s (Disabled)

Time between automatic display screen advance.

Contrast

mid

The display screen’s contrast level.

Backlight Time

1800 seconds

Time before display screen backlight automatically
turns off.

Update Rate

4s

Period between data display refreshes.

Display Mode

Programmable

Custom or Factory configured display screen option.

Auto Scroll
Auto Scroll activates each of the enabled display screens in sequence. By default,
the Auto Scroll is disabled. Use the arrow buttons to specify the number of seconds
that each screen is displayed before it flips to the next display screen, then press
the round button to set the value. Any screens that have been disabled will not
appear when Auto Scroll is enabled. Set the numeric value to zero (the default
value) to disable auto scrolling.

Contrast
To change the contrast of the front panel’s display, select CONTRAST. Press an
arrow button once, and the display screen’s contrast slowly changes. Press an
arrow button to stop the process. Press the round button when you are satisfied
with the contrast level.

NOTE
Contrast can be adjusted from any screen by holding down the round button for more than ten seconds.
Release the round button when the contrast is at a suitable level.

Backlight Timeout
This setting changes the amount of time the front panel’s backlight stays on when
the front panel is idle. The backlight has a limited lifespan; to prolong it, you
should only have back-lighting on when you are actively using the front panel.
Select BACKLIGHT TIMEOUT, then use the front panel’s buttons to change the
amount of time in seconds that the backlight stays on after a button is pressed.

Update Rate
The update rate specifies how frequently data on the display screen is refreshed.
You may find the values are being updated too frequently, or that the data shown
on screen lags too far behind the actual values. The default update rate is four
seconds; use the front panel’s buttons to change the update rate to suit your needs.

Chapter 2 - Using The Front Panel

Page 33

Screen Setup Menu

9300 Series User’s Guide

Display Mode
There are two display modes: PROGRAMMABLE MODE and FIXED MODE. The default
is programmable mode, which provides eight data display screens which can be
configured to meet your requirements (see “Custom Front Panel Displays”). Fixed
Mode displays four screens, each with large characters in the display, easily visible
from a distance. The four fixed mode screens display Average Volts, Average
Amps, kW total, and PF total. You cannot customize the fixed mode displays.

Screen Setup Menu
The SCREEN SETUP menu screen allows you to change the data displayed on the
eight display screens. From the SELECT SETUP menu, select SCREEN SETUP. The list
of display titles appear that correspond to each of the eight display screens (see
“Default Front Panel Display Screens”). The screen number with an asterix (*)
beside it indicates the active display (the screen displayed before you entered
SELECT SETUP). Select the screen you want to change, and press the round button.
Two settings appear, VALUES and STYLE, that allow you to specify which
measurements to display.
Style = One Parameter

Style
The STYLE setting defines the number of parameters on each screen. This setting
has five options for each display screen: ONE PARAMETER, TWO PARAMETER, THREE
PARAMETER, FOUR PARAMETER, and DISABLED. Select the number of values you
want to display (the fewer values you select for display, the larger the
measurement will appear on the display screen).

Style = Four Parameter

If you select a large style (for example, one value) for a display screen that is
already set to display more than one value, the front panel warns you with a
message, and displays only the first value — the links to the undisplayable values
are severed and have to be reprogrammed.

Values
The VALUES setting specifies which of the device’s measurements are displayed on
each display screen. When you change the value displayed on a screen, you are
presented with a complete list of the meter’s measurements. Using the lists of
modules provided, select the values you want to have displayed on that display
screen.
The number of VALUES you can select is a function of the STYLE setting. You cannot
select more values than the style is set to display.

Page 34

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Nameplate Info Menu

Nameplate Info Menu
Select NAMEPLATE INFO to display information about the various options of the
device, such as:
manufacturer

approvals

meter type and class

serial number

service type

accuracy rating

voltage and current input ratings

acceptable operating temperature

auxiliary power

battery life

operating frequency

configured demand settings

transformer ratios

three custom text lines written into
the meter’s Factory module

meter firmware revision
digital output information

Security Menu
When any changes are made to the meter via the front panel, the meter prompts
for a user password. The password prevents unauthorized tampering with your
meter’s configuration. Depending on site security, you may want to modify the
user password from the default to protect your configuration. The default
password is 00000 and can be set to a maximum numeric value of 60000.
Changing the User Password
1.

Select SECURITY from the Setup menu.

2.

You will see that the screen displays 00000. Enter the current password. If you
have not previously changed your password, the default is 00000.

3.

Choose MODIFY PASSWORD to alter your password (the FACTORY USE ONLY
option is for factory purposes and is not accessible).

4.

Enter your new numeric password.

5.

Select YES to accept your new password. You will be returned to the Setup menu.

Diagnostic Menu
The DIAGNOSTIC menu is accessed from the Setup menu; you can view per-phase
voltage and current harmonics screens, verify communications, verify the digital
I/O, and check the meter’s local time.

Chapter 2 - Using The Front Panel

Page 35

Diagnostic Menu

9300 Series User’s Guide

Harmonics Diagnostics
Select HARMONICS from the Diagnostics menu to view per-phase voltage and
current harmonics to the 31st harmonic. The following is an example of a
harmonics display:

Press and hold the up and down buttons to move the cursor to the harmonic of
interest. The percentage of the fundamental is also displayed.
Communications Diagnostics
The Communications diagnostic screen has a different screens according to the
communications options on your meter.
The RS-485 diagnostic screen shows three boxes labelled COM 1, COM 2 (ETH if
the meter has the optional Ethernet card) and COM 3. The following screen is an
example of Ethernet (COM 2) communication:

COM1 ETH COM3
R

T

R

T

R

T

COM 1 and COM 2 refer to the communications ports on the back panel of the
meter. As there are is no COM2 port on the 9300 meter, the COM2 box never
appears active. The COM 3 box verifies communication through the Infrared
port on the front panel (IR1).
The Ethernet diagnostic screen displays text similar to what you see in the table
below - each label appears with a value next to it. The table explains the meaning
of each possible value.

Page 36

Label

Possible Values

Description

ETH73 Version

see description

Displays the Ethernet meter’s firmware version (e.g. v270)

ETH73 in UPG

YES, NO

YES means the meter is currently being upgraded

ETH73 Setup

N/A, Rec’d

N/A means the Setup/options on the meter have not been
transmitted
Rec’d means the Setup/options have been received

EtherGate

YES, NO

YES means EtherGate is supported (9330 and 9350)
NO means EtherGate is not supported (9300)

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Diagnostic Menu

The Ethernet Connection diagnostic screen displays text similar to what you see
in the table below - each label appears with a value next to it. The table explains
the meaning of each possible value.
Label

Possible Values

Description

# Power Ups

see description

Displays the number of times the Ethernet card has power
cycled
The type of Ethernet connection:
N/A indicates no connection
ION indicates ION over Ethernet
Modbus indicates either Modbus RTU over Ethernet or Modbus
TCP

Connection

N/A, ION,
Modbus

# WEB Reqs

see description

Displays the number of received WEB Page requests

# MeterM@il

see description

Displays the number MeterM@ils sent

I/O Diagnostics
The I/O diagnostics mode verifies the operation of the digital inputs/outputs you
may have connected to the device and, if you ordered the analog I/O option, allows
you to monitor the Analog Input or Analog Output ports on your meter. analog
inputs/outputs. The following diagnostic screens are available:
Digital Ins – This screen displays the four digital input values as seen at the low
level.
Digital Outs – This screen displays the four digital input values as seen at the
low level.
Analog Ins – This screen displays the four analog inputs’s values as seen at each
Analog Input module’s output register.
Analog Outs – This screen displays the four analog outputs’s values as seen at
each Analog Output module’s output register.
Troubleshooting Diagnostics
There are three troubleshooting diagnostic screens available. They are as follows:
kiloWatts – This screen shows per-phase and total kiloWatts.
Volts – This screens shows line to neutral and average volts.
Power Factor – This screen shows signed per-phase and total power factor.
Date/Time Screen
For the 9330 and 9350 meters, this screen displays the time and date from the
device’s internal clock.
For the 9300 meter, this screen displays the time passed sent during a time sync.
The 9300 meter does not increment its internal clock while the meter is powereddown.

Chapter 2 - Using The Front Panel

Page 37

Custom Front Panel Displays

9300 Series User’s Guide

Custom Front Panel Displays
Custom front panel displays can be created showing any data the meter measures
or calculates. Each display screen can be configured to display any measurements
you require. You can also adjust the size of the characters in each screen so you can
easily read the device’s display from farther away.
There are only eight display screens available for configuration. Since all eight of
the front panel’s screen displays are factory-configured, an existing display must
be changed if you want a custom display. Refer to “Default Front Panel Display
Screens” on page 25 and/or “Display Configuration” on page 50 for details on the
eight default display screens.
The technical note Custom Front Panel Displays has complete details for
personalizing your meter’s display screens.

Before Customizing the Front Panel
In order for the customized screens to be displayed in the front panel’s display, the
meter’s Display Mode must be properly set. Ensure that the Display Options
module’s Display Mode setup register is set to PROGRAMMABLE. This is the default
setting. If it is required, you can use the meter’s front panel or ACCESS software to
set this register.

Customizing Displays Using the Front Panel
The SCREEN SETUP menu screen allows you to change the data displayed on the
eight display screens using the front panel (see “Screen Setup Menu” on page 34).

Customizing Displays Using Designer
The front panel display of the 9300 Series is controlled by the Display modules and
Display Options modules. Refer to the ION Programmer’s Reference for detailed
descriptions of the Display module and the Display Options module. Refer to
“ION Enterprise: Designer” on page 83 for details on using Designer.
Display Module
A Display module controls which values are displayed on a display screen, and
how these values are presented. Up to four parameters can be linked to a Display
module — these parameters appear on the display screen when the module is
activated.

Page 38

Chapter 2 - Using The Front Panel

9300 Series User’s Guide

Before Customizing the Front Panel

Links to a Display module can be made using Designer or the front panel. Each
Display module has one setup register, Display Type, which sets the number of
parameters that the display screen will show.

Power Meter
module

kW tot
kVAR tot
kVA tot
PF sign tot

Display
Module 5
Source 1
Source 2
Source 3
Source 4

kWh net

Display
Module 1

Source 1

The Display Type setup register has five options: ONE PARAMETER, TWO
PARAMETER, THREE PARAMETER, FOUR PARAMETER, AND DISABLED. The number of
inputs for the Display module should match the Display Type setup register.
If you select a Display Type with more parameters than are currently linked to the
Display module, the display screen will show any unavailable inputs as N/A. If a
Display Type is selected which has fewer parameters than are linked to the
module, the Display module will only display the Display Type number, and will
break any links to parameters that it cannot display.
For example, if you have a display screen with four parameters, and you select a
Display Type of One Parameter, the first parameter is displayed and the other three
links to the ION Display module are severed.
Display Options Module
The Display Options module controls data display settings such as backlight
timeout, automatic display scrolling, parameter update rate, and display mode.
Settings in the Display Options modules are global, and affect all of the front panel
display screens. Refer to “Display Configuration” on page 50 for the Display
Options module’s default setup register settings.

Chapter 2 - Using The Front Panel

Page 39

Before Customizing the Front Panel

Page 40

9300 Series User’s Guide

Chapter 2 - Using The Front Panel

3

Default Meter Functionality
The information provided in this chapter corresponds to factory-configured
ACCESS devices. If you have a custom framework, some of the default settings
may differ for your configuration.

In This Chapter
Default Meter Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Communications Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Power Quality Setup (9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Data Logging Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Setpoint Configuration (9330 and 9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Meter Clock Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Display Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Demand Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Factory Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Third Party Protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Using the Modbus RTU Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Using the Modbus/TCP Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Using the DNP 3.0 Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Using the Profibus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Restoring the Factory Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

Default Meter Functionality

9300 Series User’s Guide

Default Meter Functionality
To learn more about the ION modules in your meter, refer to the ION Device
Templates at www.pwrm.com. ION Device Templates list all of the ION modules
available in the current version of your meter, and the total number of each
module. ION Device Templates also show the ranges or options available for each
module’s setup registers.

Basic Setup
Basic configuration of the meter is provided by the Power Meter module. The
Power Meter module is the main connection between the power system
measurements and all other ION modules in the device. This module reports the
values for all voltage, current and power measurements.
The Power Meter module’s setup registers describe details of the power system
being monitored. Many of the Power Meter module’s setup registers are
configured when the meter is initially put into service, although the device will not
operate properly until Volts mode and PT and CT ratios are set. Some registers
may need to be changed to refine the device’s operation.
The functions of the setup registers in the Power Meter module are as follows:
Setup Register

Function

Defaults

Volts Mode 1

The power system’s configuration – WYE, DELTA, Single, etc

4W-WYE

The Potential Transformer’s primary winding rating for V1, V2
and V3

120

PT Sec 1

The Potential Transformer’s secondary winding rating for V1, V2
and V3

120

CT Prim 1

The Current Transformer’s primary winding rating for I1, I2 and I3

5

CT Sec 1

The Current Transformer’s secondary winding rating for I1, I2
and I3

5

Vn Polarity

The polarity of the Potential Transformer on Vn

Normal

In Polarity

The polarity of the Current Transformer on In

Normal

Phase Order

The expected rotation of the voltage phases (ABC or ACB)

ABC

Phase Lbls

The phase label format assigned to the outputs (ABC, RST, XYZ,
RYB, RWB or 123)

ABC

PT Prim

1

1

The registers are typically set when the device is commissioned. Changing the values of these registers
while the device is in service is not recommended.

Once basic setup is performed (i.e. the PT/CT and Volts Mode settings), the meter
operates properly. Typically there is no need to make further changes to the Power
Meter module’s setup registers.

Page 42

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Communications Setup

Communications Setup
Communication settings are typically configured when the ACCESS meter is
initially put into service. Each communications port on a meter is controlled by a
single Communications module. The modules’ setup registers define the
parameters used for each port, so parameters do vary according to the type of
communications channel selected (i.e. RS-232, RS-485, Modem, Infrared, Ethernet).
Module Name

Settings

Comm 1

COM1 RS-485 port and internal modem

Comm 2 2

COM2 RS-485 port or EtherGate

Infrared Comm

COM3 Optical port

Ethernet Comm

10Base-T Ethernet port

Profibus Comm

4

3

1

port

Profibus Communications port

1

For 9330 / 9350 meters with an optional modem, COM1 is hardwired for ModemGate.

2

COM2

3

For 9330 / 9350 meters with an optional Ethernet card, COM2 is hardwired for EtherGate.

is not available for the 9300 meter.

4 Available for the 9300 meter.

A communications channel must be configured before you can use ACCESS
software (i.e. Vista or Designer). Altering the settings of the channel that is in use
causes a loss of communications with the meter. Refer to the online ION
Programmer’s Reference for complete details on all the Communications module
setup registers.
Communications
Module

Comm 1
Comm 2
Infrared Comm

Comm 1

Setup Register

Description

Default

Baud Rate

Sets the communications speed, in bits/second for the serial port

9600

RTS Delay

Sets the RTS Delay for the serial communications port

0

Unit ID

Sets the Unit ID of the communications port

Unit ID is based on
the serial number 1

Protocol

Sets the communications protocol for the communications port

ION

Modem Init 2

Sets the modem’s initialization string

AT&F

IP Address

Sets the IP Address of the meter

None

Subnet Mask

Sets the Subnet Mask setting for the Ethernet Port

None

Gateway

Sets the Ethernet Gateway setting for the Ethernet Port

None

SMTP Server 3

Sets the IP Address for the SMTP Mail Server that is configured to
forward mail from the meter to the final destination

None

SMTP Connection
Timeout 3

Sets the time that the meter will wait when establishing a
connection to an SMTP Server

None

PB Address

Sets the Profibus Address

126

Ethernet

Profibus Comm

Chapter 3 - Default Meter Functionality

1

The factory set Unit ID for this port is based on the serial number of the meter. For example: Serial
number: PA-0009A263-10; Unit ID: 9263.

2

Setting for the 9330 and 9350 meters.

Page 43

Power Quality Setup (9350)

9300 Series User’s Guide

3

MeterM@il settings for 9330 and 9350 meters.

Modem Initialization String
The setup register labeled ModemInit is available for 9330 and 9350 meters with
internal modems, and defines the initialization string for the internal modem (by
default, the modem is factory configured to answer on one ring). You should not
require changes to the ModemInit string for normal operation. If you require
advanced modem functionality, you can customize the ModemInit register with a
string up to 47 characters long.

CAUTION
The ModemInit string is automatically sent to the internal modem when the ModemInit setup register is
changed, when the meter is powered up, or when the baud rate of the modem’s Communications
module is changed.

Communications Protocols
By default, all COM ports are configured to use the ACCESS protocol. If you want
to make use of Modbus RTU, DNP 3.00, or GPS configurations, you need to
configure Protocol setup register the Communications module that controls the
port you want to use.

NOTE
The Factory Protocol is reserved for the use by Siemens Customer Service.

Power Quality Setup (9350)
For the 9350 meter, power quality parameters can be set up using the Sag/Swell
module. The Sag/Swell module monitors applicable phase voltages for temporary
undervoltages and overvoltages (i.e. CBEMA Type 2 and Type 3 disturbances).
Once a disturbance is detected, magnitude and duration data is captured by the
Sag/Swell module, and is passed to a data recording framework.

Page 44

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Data Logging Setup

Sag/Swell Module Settings
Setup Register

Function

Default

Swell Lim

The magnitude above which a voltage deviation is considered
a swell

106

Sag Lim

The magnitude below which a voltage deviation is considered a sag

88

Nom Volts

The nominal power system voltage

01

EvPriority

The priority assigned to Sag/Swell module events (0 to 255; 255 is
highest)

200

1

The primary power system voltage is sometimes different than the PT Primary setup register value; i.e.
when the PT Primary is used to indicate winding ratio rather than
primary voltage.

Nom Volts must be set to enable Power Quality functions. Most applications are
served by the default values entered into the module’s registers, but if you want to
fine-tune Sag/Swell detection, try adjusting the Swell Lim and Sag Lim values.

NOTE
If the Sag/Swell module’s Nom Volts setup register is set to zero, all Power Quality functions of the 9350
meter are disabled. That is why Nom Volts is typically set when the meter is put into service. If Nom Volts
has not been set, enter a value for your power system’s nominal voltage (for example, 120, 277 or 347).

Data Logging Setup
The data recording frameworks contain Data Recorder modules, Waveform
Recorder modules, and Periodic Timer modules. Data Recorder and Waveform
Recorder modules are responsible for logging the power system data. The Periodic
Timer modules control the recording frequency of the recorder modules to which
they are linked.

Default Logging Capacity
The following table summarizes the default recording depths and recording
intervals of the various Data recorders and Waveform recorders in the meter.

Chapter 3 - Default Meter Functionality

Log

Depth

Interval

Historic Log

930

900 seconds (15 minutes)

Waveform recording (waveform recorders)

3

Triggered on demand

Report Generator Log (EgyDmd Log)

930

900 seconds (15 minutes)

Sag/Swell Log (9350 only)

100

Triggered on demand

Event Log (Event Log Controller module)

50

Triggered on demand

Page 45

Data Logging Setup

9300 Series User’s Guide

Procedures for changing the logging depth and the frequency of logging are
discussed in the following sections: “Changing the Frequency of Logging” on
page 47 and “Changing the Log Depths” on page 47.

Default Logging Configuration
The standard configuration of the meter includes data recorders that log various
power system data such as energy and demand, or the average power system
quantity used over a period of time (Historic Mean Log). The 9350 also logs sags
and swells in voltage.
Revenue Logging
For the revenue meter option, Data Recorder #1 is locked, so channels must be
specified prior to the meter being sealed. Refer to RMICAN Ordering Sheet on our
website for your particular meter.
For compatibility with the UTS MV-90 billing software, Data Recorder #1 must be
configured as a 16-channel recorder.
Historical Data Logging
One Data Recorder module, the Historic Mean Log, logs the following output
register values by default:
Hist Mean Log
Vll avg mean

Vln avg mean

I avg mean

kW tot mean

kVAR tot mean

kVA tot mean

PF sign mean

Freq mean

V unbal mean

I unbal mean

V1 THD mean

V2 THD mean

V3 THD mean

I1 THD mean

I2 THD mean

I3 THD mean

WinPM.Net Reporting
One recorder is configured to provide power system data for the Reporter
software. This recorder is labeled Egy Dmd Log. If any input links to this module
are changed, Reporter will not be able to create reports from the device’s logs. If
you use the Reporter software, do not change the parameters that are logged in the
Egy Dmd Log.

Page 46

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Data Logging Setup

Sag/Swell Logging (9350 only)
The meter logs the following output register values:
Sag/Swell Log
SS1 DistDur

SS1 DistV1Min

SS1 DistV1Max

SS1 DistV2Min

SS1 DistV2Max

SS1 DistV3Min

SS1 DistV3Max

SS1 DistNominal

Changing the Frequency of Logging
The two Periodic Timer modules that control the frequency of different data
recording are as follows:
“EgyDmd Log” Trg controls the frequency of logging for the Energy and
Demand Log (this log is used for generating reports using Reporter).
“Hist Log Trg” controls the frequency of Historic Data logging.
Change the value in the Period setup register to change the frequency of data
logging (Period values are specified in seconds). Do not change the Sync Mode
setup register.

Changing the Log Depths
Change the value in the Depth setup register to increase the number of records
stored in the recorder. The RecordMode setup register controls how the Data
Recorder will overwrite old records; refer to the Data Recorder module description
in the online ION Programmer’s Reference before changing this setup register.

Changing Waveform Recording
The Waveform Recorder modules do not require changes to their default settings.
If you want to change the format of the recorded waveforms, refer to the
Waveform Recorder module description in the online ION Programmer’s Reference.

Changing the Parameters that are Logged
The meter’s factory configuration logs a comprehensive set of energy, power and
harmonics parameters. You cannot change which parameters are logged by
configuring a setup register. Adding or deleting a log’s parameters is an advanced
procedure, as it requires changes to the links between modules.
The software “Using Designer software” section of Using WinPM.Net describes
adding and deleting links between modules. Once you are comfortable editing
module links, change logged parameters by linking the output registers you want
logged to the inputs of an ION Data Recorder module.

Chapter 3 - Default Meter Functionality

Page 47

Setpoint Configuration (9330 and 9350)

9300 Series User’s Guide

Setpoint Configuration (9330 and 9350)
Setpoints provide extensive control, secondary protection and analysis capabilities
by allowing you to initiate an action in response to a specific condition. Some
possible applications for the Setpoint module include: demand control, power
quality monitoring, fault detection, activating alarms, and gated logging functions.
For the 9330 and 9350 meters, the Setpoint modules monitor certain ‘over’ and
‘under’ conditions for sliding window demand, current, voltage and power factor.
Module Label

Description

Over kW swd

Monitors over conditions for kW swd on the SD1 Sliding Window Demand
module

Under VII avg

Monitors under conditions on the VII avg output for the Power Meter module

Over I avg

Monitors over conditions on the I avg output for the Power Meter module

Under PF sign

Monitors under conditions on the PF sign tot output for the Power Meter module

Setpoint Module Settings
There is no need to change any of the Setpoint modules’ setup registers for normal
operation of the meter.
Default
Setup Register

Function
Over kW swd

Under VII avg

Over I avg

Under PF sign

High Limit

The limit that a source input must exceed
for an over condition to start

1,000,000,000

0

1,000,000,000

0

Low Limit

The limit that a source input must exceed
for an under condition to start

1,000,000,000

0

1,000,000,000

0

SusUntlON

Amount of time an input must be out of
range for an over/under condition to start

0

0

0

0

SusUntlOFF

Amount of time an input must be back in
range for an over/under condition to end

0

0

0

0

Input Mode

This register specifies how the value of the
source input is interpreted

Signed

Signed

Signed

Absolute

Eval Mode

Determines how the High Limit and Low
Limit setup registers are interpreted

GreaterThan

LessThan

GreaterThan

LessThan

EvPriority

The priority assigned to a Setpoint event (0
to 255; 255 is highest)

128

128

128

128

Page 48

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Meter Clock Configuration

Fine Tuning Over Condition Monitoring
If you want to fine-tune over condition monitoring, the only setup registers you
should change are SusUntlON and SusUntlOFF.
SusUntlON determines how long the modules wait after an over condition is
detected before reporting it. This gives the monitored value a short period to
correct itself before the event is registered with the module, so that very brief over
conditions are ignored. Similarly, SusUntlOFF is the amount of time a normal
value must be present before the module considers normal operation to be
restored. Both SusUntlON and SusUntlOFF values are entered in seconds (the
default value for both is 30 seconds).
Refer to the online ION Programmer’s Reference for more information about the
Relative Setpoint module.

Meter Clock Configuration
The Clock module controls the meter’s internal clock which provides timestamps
for data logged by the device. The clock needs to be configured properly to ensure
that logged data has accurate timestamp information. The Clock module also
receives the time synchronization signals sent to it by the workstation running
ION software, updating the device’s clock when required.
The setup registers in the Clock module specify timezone and Daylight Savings
Time (DST) parameters and time synchronization functions.
Setup Register

Function

Default

TZ Offset

The timezone the device is in, relative to Greenwich Mean Time

0

DST Start

Date and time when DST begins

0

DST End

Date and time when DST ends

86,400

DST Offset

The amount of time the clock is changed when DST begins or ends

0

Time Sync Source

The communications port that receives time sync signals

COM1

Time Sync Type

The type of time sync signal (Local or Universal time)

UTC

Clock Source

Specifies the clock’s time synchronization signal source (line frequency, communications signals, or
internal crystal)

Internal

NOTE
When modifying setup registers of the Clock module, use the Format option to convert between UNIX and
conventional time. Refer to the description of the Clock module in the online ION Programmer’s
Reference for more details.

Refer to the technical note Time Synchronization and Timekeeping for further details
on using the meter’s time synchronization functions.

Chapter 3 - Default Meter Functionality

Page 49

Display Configuration

9300 Series User’s Guide

Display Configuration
The meter’s front panel display is controlled by two types of ION modules: the
Display Options module and Display modules. Display modules determine the
form and content of each display screen, and the Display Options module controls
options such as decimal format, daylight savings time display, and backlight
timeout.
There are eight display screens which are all factory-configured. (An existing
display must be changed if you want a custom display.) The default displays are
as follows:
Display Number

Display Title

Parameters shown

Display #1

kWh net

kWh net

Display #2

kWh swd / mx

kWh swd, kWh swd mx

Display #3

Volts

Va, Vb, Vc

Display #4

Amps

Ia, Ib, Ic

Display #5

Power

kW tot, kVAR tot, kVA tot, PF sign tot

Display #6

Frequency

Freq

Display #7

V-THD

V1 Total HD, V2 Total HD, V3 Total HD

Display #8

I-THD

I1 Total HD, I2 Total HD, I3 Total HD

Display Options Module Settings
The Display Options module contains setup registers that hold data display
settings such as contrast level and backlight timeout. Settings in the Display
Options modules are global, and affect the entire set of front panel display screens.
Setup Register

Function

Default

Autoscroll

Sets the number seconds that each screen is displayed before it flips to the next display
screen. Set to DISABLED to turn-off AutoScroll.

Disabled

Backlight Timeout

Sets the time that the front panel’s backlight stays on after the last press of a front
panel button.

1,800

Display Update Time

Sets the period between data display refreshes

4

Display Mode

Sets the display to show the four fixed mode display screens, or the eight programmable
display screens.

Programmable

Page 50

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Display Configuration

Display Module Settings
The Display module’s setup registers determine the format that the Source data
will take on the front panel display. Depending on the display screen type, you can
use up to four Source links to a single Display module. Display modules have the
following setup registers:
Setup Register

Function

Screen Type

Determines the display format (see table below)

The number of parameters you can have linked to the Source inputs depends on the
value of the Screen Type setup register. The supported options for the setup register
and the number of allowable Source inputs for each Screen Type setting are
described below.
Screen Type Setting

Max Source inputs

One Parameter

1

Two Parameter

2

Three Parameter

3

Four Parameter

4

Display Description

Displays one to four values. The fewer
the values, the larger the values appear
on the display screen.

Changing the Parameters that are Displayed
The meter’s default display configuration shows a comprehensive set of
parameters. Changing these parameters requires that you alter the links between
various ION modules. Complete details on configuring the front panel displays
are provided in the Custom Front Panel Displays technical note.

Chapter 3 - Default Meter Functionality

Page 51

Demand Setup

9300 Series User’s Guide

Demand Setup
The demand modules (both Thermal Demand modules and Sliding Window
Demand modules) are configured to calculate the average current demand and
kW, kVAR and kVA demand. The setup registers in the demand modules define
time intervals for demand calculations, setting the sensitivity of the module’s
operation.
Sliding Window Demand Module Settings
Sliding Window Demand is often referred to as Rolling Block Demand. To
compute sliding window demand values, the Sliding Window Demand module
uses the sliding window averaging (or rolling interval) technique which divides
the demand interval into sub-intervals. The demand is measured electronically
based on the average load level over the most recent set of sub-intervals. This
method offers better response time than fixed interval methods.
Setup Register

Function

Default

Sub Intvl

The time, in seconds, in the sliding window demand sub-interval

900

#SubIntvls

The number of sub-intervals in the sliding window

1

Pred Resp

The speed of Predicted Demand calculations; use higher values for
faster prediction (70 to 99 recommended)

70

Thermal Demand Module Settings
The Thermal Demand module calculates thermal demand over a specified length
of time. It uses a method which is equivalent to thermal averaging. For thermal
averaging, the traditional demand indicator responds to heating of a thermal
element in a Watt-Hour meter. You can adjust the Thermal Demand module's
calculation to mimic this technique by changing the Time Const and Interval setup
parameters.

Page 52

Setup Register

Function

Default

Interval

The time, in seconds, in the thermal demand interval

900

Time Const

The sensitivity to changes in the source signal; higher values
provide faster response time (common values are 63 and 90)

90

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Factory Information

Factory Information
The Factory module displays firmware version, serial number and other device
information in read-only setup registers (read-only registers can be viewed but not
changed).
Factory Module Settings
The device information provided is as follows:
Setup Register

Description

Device Type

A device type identifier (“7300” for the 9300)

Compliance

A statement of whether the device is ION compliant or not

Options

Shows model number of meter

Revision

The meter’s firmware version

Serial Num

The meter’s serial number

ION Version

The ION version supported by the device

Template

The name of the factory default template (framework) installed on the device

Nom Freq

The expected frequency of the power system being monitored

The Factory module also contains numerous read-only setup registers that hold
the calibration constants used at the factory.
How to TAG Your Meter
Three setup registers are provided for you to enter your company name and other
text information you want stored in the device. These configurable setup registers
are as follows:
Owner - This is a text register for storing user information (e.g. company name);
it can be up to 255 characters in length.
Tag 1 - This is a text register for storing user information (e.g. device location); it
can be up to 15 characters in length.
Tag 2 - This is a text register for storing user information (e.g. device number or
identifier); it can be up to 15 characters in length.

Chapter 3 - Default Meter Functionality

Page 53

Third Party Protocols

9300 Series User’s Guide

Third Party Protocols
Modbus and DNP modules are factory configured and do not require basic
configuration changes. Changing the factory configuration is an advanced setup
procedure that requires an understanding of the protocol, as well as an
understanding of the meter’s internal operation.
Refer to the technical notes DNP 3.0 and ION Technology and Modbus and ION
Technology for the appropriate list of protocol parameters available.

NOTE
The meter can also be configured to receive data through Modbus or DNP 3.0, though there is no factoryconfigured framework for receiving data through these protocols. An 9300 Series meter can receive data
if the meter writes to hard-coded registers.
For details on configuring your network for receiving data via Modbus or DNP 3.0, refer to the DNP Slave
Import module descriptions in ION Programmer’s Reference and the 9300 Series Modbus protocol
documents, as well as the technical notes DNP 3.0 and ION Technology and Modbus and ION
Technology.

Communications Protocol Configuration
In order to use the factory Modbus or DNP configuration you must first configure
the communications channel you want to use. By default all communications ports
are configured to use the ACCESS protocol. Choose the 3rd-party protocol you
want from the list of available protocols in the Communications module’s Protocol
setup register.

NOTE
Modbus RTU is available on each of the meter’s communications ports, and multiple ports can
communicate using Modbus simultaneously. Only a single port can use the DNP 3.00 protocol at any
one time.

The meter is factory configured to provide advanced interoperability support. The
meter is readily incorporated into third party power monitoring systems. This
section describes how to communicate with the meter via Modbus RTU, Profibus,
and DNP 3.0 protocols.

Using the Modbus RTU Protocol
The meter can make any real-time data available through the Modbus RTU
protocol. Modbus Master devices connected to the 9300 can access this data.
Modbus Master devices can also write data into 9300’s module registers, making
device configuration changes or initializing control actions.

Page 54

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Using the Modbus RTU Protocol

Factory Modbus Configuration for the 9300 Series Meter
The 9300 Series meter makes data available to Modbus devices using four Modbus
Slave modules. These modules are linked to other modules in the meter that
provide energy, power and demand data. Once a communications channel is
configured to use Modbus RTU protocol (refer to “Communications Setup” in
Chapter 3), the data is available to Modbus Master devices.

communications port is set
to Modbus RTU protocol

measured data is linked
to Modbus module’s input

Power Meter
Module

Vln a

Modbus Slave
Module

40011

Modbus module outputs
data in Modbus format

data is available to
Modbus Master devices

ION Meter

As the data available through the Modbus Slave modules is in a specific format,
knowledge of the Modbus protocol and an understanding of the settings used in
the meter are required to interpret the data provided.
Changing the Modbus Configuration
If the factory Modbus configuration does not suit your needs, the existing Modbus
Slave modules can be relinked to other parameters that you want to access through
Modbus. There are ten Modbus Slave modules available in the 9300 Series meter,
so you can create more modules to make other parameters available to Modbus
Master devices.
If your Modbus Master device requires data in a format different than that
provided by the factory Modbus configuration, you can edit the setup registers in
the Modbus Slave modules. These setup registers specify the Modbus format,
scaling and base address settings. Refer to the ION Programmer’s Reference for
complete details on Modbus Slave module functionality.

NOTE
Refer to the Modbus 7300 Series protocol document for complete details on the Modbus implementation
in the 9300 Series of meters.

Modbus Slave Module Settings
The settings in the Modbus Slave module setup registers are shown in the tables
below. Refer to the Modbus Slave module description in the ION Programmer’s
Reference for complete details of each setup register’s function and options.
Refer to the Modicon Modbus Protocol document for additional details on the
Modbus implementation in the 9300 Series meter.

Chapter 3 - Default Meter Functionality

Page 55

Using the Modbus RTU Protocol

9300 Series User’s Guide

Modbus Slave Module #1

Modbus Slave Module #2

Setup Register

Setting

Setup Register

Setting

Format

unsigned 16-bit

Format

signed 32-bit

Base Address

40011

Base Address

40027

Scaling

YES

Scaling

YES

In Zero

0

In Zero

-214748364

In Full

6553

In Full

214748364

Out Zero

0

Out Zero

-2147483640

Out Full

65530

Out Full

2147483640

Modbus Slave Module #3

Modbus Slave Module #4

Setup Register

Setting

Setup Register

Setting

Format

signed 32-bit

Format

signed 32-bit M10K

Base Address

40059

Base Address

40089

Scaling

YES

Scaling

NO

In Zero

-214748364

In Full

214748364

Out Zero

-2147483640

Out Full

2147483640

Modbus Slave Module Parameter Mapping
The following tables show which measurements are provided by each of the four
Modbus Slave modules. The source for each measurement is shown (“Source ION
Module”) so that you can easily delete parameters if you want to access different
data. Note that the Modbus Register remains the same if you link a different
parameter into one of the Modbus Slave module inputs (i.e. any value you link to
Modbus Slave module #1, Source Input #1 will use Modbus Register 40011).
Modbus Slave Module #1 Links
Measurement

Label

Source ION Module

Modbus Module and Input Number

Modbus Register

L-N Voltage Phase A

Vln a

Power Meter

Modbus Slave #1 – Source Input #1

40011

L-N Voltage Phase B

Vln b

Power Meter

Modbus Slave #1 – Source Input #2

40012

L-N Voltage Phase C

Vln c

Power Meter

Modbus Slave #1 – Source Input #3

40013

Average L-N Voltage

Vln avg

Power Meter

Modbus Slave #1 – Source Input #4

40014

L-L Voltage AB

Vll ab

Power Meter

Modbus Slave #1 – Source Input #5

40015

L-L Voltage BC

Vll bc

Power Meter

Modbus Slave #1 – Source Input #6

40016

L-L Voltage CA

Vll ca

Power Meter

Modbus Slave #1 – Source Input #7

40017

Page 56

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Using the Modbus RTU Protocol

Measurement

Label

Source ION Module

Modbus Module and Input Number

Modbus Register

Average L-L Voltage

Vll avg

Power Meter

Modbus Slave #1 – Source Input #8

40018

Phase A Current

Ia

Power Meter

Modbus Slave #1 – Source Input #9

40019

Phase B Current

Ib

Power Meter

Modbus Slave #1 – Source Input #10

40020

Phase C Current

Ic

Power Meter

Modbus Slave #1 – Source Input #11

40021

Average Current

I avg

Power Meter

Modbus Slave #1 – Source Input #12

40022

Voltage Unbalance

V unbal

Power Meter

Modbus Slave #1 – Source Input #13

40023

Current Unbalance

I unbal

Power Meter

Modbus Slave #1 – Source Input #14

40024

Line Frequency

Freq

Power Meter

Modbus Slave #1 – Source Input #15

40025

L-N Voltage Phase A

Vln a

Power Meter

Modbus Slave #1 – Source Input #1

40011

Modbus Slave Module #2 Links
Measurement

Label

Source ION Module

Modbus Module and Input Number

Modbus Register

Phase A kW

kW a

Power Meter

Modbus Slave #2 – Source Input #1

40027-40028

Phase B kW

kW b

Power Meter

Modbus Slave #2 – Source Input #2

40029-40030

Phase C kW

kW c

Power Meter

Modbus Slave #2 – Source Input #3

40031-40032

Total kW

kW tot

Power Meter

Modbus Slave #2 – Source Input #4

40033-40034

Phase A kVAR

kVAR a

Power Meter

Modbus Slave #2 – Source Input #5

40035-40036

Phase B kVAR

kVAR b

Power Meter

Modbus Slave #2 – Source Input #6

40037-40038

Phase C kVAR

kVAR c

Power Meter

Modbus Slave #2 – Source Input #7

40039-40040

Total kVAR

kVAR tot

Power Meter

Modbus Slave #2 – Source Input #8

40041-40042

Phase A kVA

kVA a

Power Meter

Modbus Slave #2 – Source Input #9

40043-40044

Phase B kVA

kVA b

Power Meter

Modbus Slave #2 – Source Input #10

40045-40046

Phase V kVA

kVA c

Power Meter

Modbus Slave #2 – Source Input #11

40047-40048

Total kVA

kVA tot

Power Meter

Modbus Slave #2 – Source Input #12

40049-40050

Phase A signed PF

PF sign a

Power Meter

Modbus Slave #2 – Source Input #13

40051-40052

Phase B signed PF

PF sign b

Power Meter

Modbus Slave #2 – Source Input #14

40053-40054

Phase C signed PF

PF sign c

Power Meter

Modbus Slave #2 – Source Input #15

40055-40056

Modbus Slave Module #3 Links
Measurement

Label

Source ION Module

Modbus Module and Input Number

Modbus Register

kW Thermal Dmd

kW td

Thermal Demand

Modbus Slave #3 – Source Input #1

40059-40060

kVAR Thermal Dmd

kVAR td

Thermal Demand

Modbus Slave #3 – Source Input #2

40061-40062

kVA Thermal Dmd

kVA td

Thermal Demand

Modbus Slave #3 – Source Input #3

40063-40064

Max kW Th Dmd

kW td mx

Maximum

Modbus Slave #3 – Source Input #4

40065-40066

Chapter 3 - Default Meter Functionality

Page 57

Using the Modbus RTU Protocol

9300 Series User’s Guide

Measurement

Label

Source ION Module

Modbus Module and Input Number

Modbus Register

Max kVAR Th Dmd

kVAR td mx

Maximum

Modbus Slave #3 – Source Input #5

40067-40068

Max kVA Th Dmd

kVA td mx

Maximum

Modbus Slave #3 – Source Input #6

40069-40070

Max Avg L-N Voltage

Vln avg mx

Maximum

Modbus Slave #3 – Source Input #7

40071-40072

Max Average Current

I avg mx

Maximum

Modbus Slave #3 – Source Input #8

40073-40074

Maximum Total kW

kW tot mx

Maximum

Modbus Slave #3 – Source Input #9

40075-40076

Maximum Total kVAR

kVAR tot mx

Maximum

Modbus Slave #3 – Source Input #10

40077-40078

Maximum Total kVA

kVA tot mx

Maximum

Modbus Slave #3 – Source Input #11

40079-40080

Maximum Frequency

Freq mx

Maximum

Modbus Slave #3 – Source Input #12

40081-40082

Min Avg L-N Voltage

Vln avg mn

Minimum

Modbus Slave #3 – Source Input #13

40083-40084

Min Average Current

I avg mn

Minimum

Modbus Slave #3 – Source Input #14

40085-40086

Minimum Frequency

Freq mn

Minimum

Modbus Slave #3 – Source Input #15

40087-40088

Modbus Slave Module #4 Links
Measurement

Label

Source ION Module

Modbus Module and Input Number

Modbus Register

Imported kWh

kWh imp

Integrator

Modbus Slave #4 – Source Input #1

40089-40090

Exported kWh

kWh exp

Integrator

Modbus Slave #4 – Source Input #2

40091-40092

Total kWh

kWh tot

Integrator

Modbus Slave #4 – Source Input #3

40093-40094

Net kWh

kWh net

Integrator

Modbus Slave #4 – Source Input #4

40095-40096

Imported kVARh

kVARh imp

Integrator

Modbus Slave #4 – Source Input #5

40097-40098

Exported kVARh

kVARh exp

Integrator

Modbus Slave #4 – Source Input #6

40099-40100

Total kVARh

kVARh tot

Integrator

Modbus Slave #4 – Source Input #7

40101-40102

Net kVARh

kVARh net

Integrator

Modbus Slave #4 – Source Input #8

40103-40104

Total kVAh

kVAh

Integrator

Modbus Slave #4 – Source Input #9

40105-40106

Max Phase A Voltage THD

V1 THD max

Maximum

Modbus Slave #4 – Source Input #10

40107-40108

Max Phase B Voltage THD

V2 THD max

Maximum

Modbus Slave #4 – Source Input #11

40109-40110

Max Phase C Voltage THD

V3 THD max

Maximum

Modbus Slave #4 – Source Input #12

40111-40112

Max Phase A Current THD

I1 THD max

Maximum

Modbus Slave #4 – Source Input #13

40113-40114

Max Phase B Current THD

I2 THD max

Maximum

Modbus Slave #4 – Source Input #14

40115-40116

Max Phase C Current THD

I3 THD max

Maximum

Modbus Slave #4 – Source Input #15

40117-40118

Importing Data using Modbus RTU
It is possible to bring data into the 9300 Series meter using Modbus. Various ION
registers can be written by Modbus Master devices by correlating the Modbus
register number with the address of the ION register you want to write. When a
Modbus register is written with a value, the corresponding ION register will be
written, provided the Modbus RTU protocol is active on the communications
channel that connects the Modbus Master to the 9300 Series meter.

Page 58

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Using the Modbus/TCP Protocol

You can use the Modbus RTU protocol to write values into ION external numeric,
pulse and Boolean modules, allowing you to enable, disable and reset meter
functions. You can also use Modbus to change setup register values in various ION
modules to configure the meter’s operation.
All of the information required to write to ION registers through Modbus is
available in 9300 & 9330 Modicon Modbus Protocol, available on the Technical
Documentation CD, or by request from Siemens.

Using the Modbus/TCP Protocol
Modbus/TCP is the newest open Modbus protocol variant (formerly called
MBAP). It defines the packet structure and connection port (port 502) for the
industry standard TCP/IP protocol. The structure of Modbus/TCP is very similar
to the Modbus RTU packet except that it has an extra six-byte header and does not
use the cyclic redundancy check (CRC). Some of the newest ION firmware now
supports Modbus/TCP for direct communications with the meter.
Modbus/TCP retains the Modbus RTU limit of 256 bytes to a packet. It is suggested
that higher through-put is possible if this limitation is removed. This variant is
called Enhanced Modbus/TCP but, so far, few devices have moved to support it.
Another variant, that has yet to gain popularity, is from the Semiconductor
Equipment and Materials International (SEMI) trade association. The Generic
Sensor-Bus Sub-Committee created the Sensor/Actuator Network Standard (SEMI
E54-0997).

Modbus TCP Communications
You can now communicate to the meter via Modicon® Modbus TCP (formerly
called MBAP). Your meter must have the optional Ethernet port.
Connect to socket 502.

Etherne

t

Connect to socket 502

Meter with optional
Ethernet port

Be aware that you cannot form an EtherGate connection to the Modbus TCP
network.

Chapter 3 - Default Meter Functionality

Page 59

Using the DNP 3.0 Protocol

9300 Series User’s Guide

Using the DNP 3.0 Protocol
The Distributed Network Protocol Version 3.00 (DNP 3.0) is an open protocol used
in the electric utility industry for communications and interoperability among
substation computers, RTUs, IEDs, and Master Stations. The 9300 can be
integrated into a DNP network using the DNP Slave Import, Export and Options
modules.

NOTE
Complete DNP documentation is available through the DNP User’s Group (on the web at www.dnp.org).
This documentation describes DNP 3.0 Transport Functions, the Application Layer Protocol, the Data
Object Library, Data Link Layer Protocol Description, and the Subset Definitions.

Factory DNP 3.0 Configuration for the 9330 and 9350
The meter’s factory configuration makes various parameters available through
DNP 3.0. There is no factory-configured functionality for importing DNP 3.0 data
into the meter. ION modules are linked to DNP Slave Export modules which
convert the ION data into the appropriate DNP objects. These objects are available
through the meter’s communications port that is configured to use the DNP 3.0
protocol. The DNP Options module sets global options for all of the DNP Slave
Export modules.

DNP Options
Module

measured data is linked
to DNP module’s input

Power Meter
Module

Vln a

DNP Options module
sets global options
for all DNP modules

DNP Export
Module

data is available
to DNP devices

DNP objects

DNP module outputs
data as DNP objects

communications port is
set to DNP 3.0 protocol

ION Meter

Changing the DNP Configuration
If the factory DNP configuration does not suit your needs, the existing DNP Slave
Export modules can be relinked to other parameters that you want to access
through DNP. Alternately you can add additional DNP Slave Export modules and
link the desired ION parameters to them. There are 16 DNP Slave Export modules
available on the 9330 and 9350; of these, 14 are used by the factory configuration.

NOTE
Only one port per 9330 or 9350 can be used with DNP 3.0.

Page 60

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Using the DNP 3.0 Protocol

If your DNP network requires data in a format different than that provided by the
factory DNP configuration, you can edit the setup registers in the DNP Slave
Export modules and the DNP Options module. Do not make any changes to the
DNP Options module’s setup registers unless you understand the effects each
change will cause. Refer to the ION Programmer’s Reference for complete details on
DNP Slave Export and DNP Slave Options module function.
As DNP 3.0 is a very complex protocol, an in-depth understanding of DNP 3.0 is
required to interpret the settings in the DNP Options module and the DNP Slave
Export modules. It is beyond the scope of this meter’s User’s Guide to describe
DNP; consult the DNP User’s Group or other resources to learn more about the
protocol.

DNP Slave Export Module Settings
The 14 factory-configured DNP Slave Export modules are configured as shown in
the following table.
Setup Register

Setting

BasePoint

Varies – each analog input or binary counter has a different BasePoint

StaticObj

11 modules are Analog Input; three are Binary Counter

EventObj

Disable Event Objects

Deadband

0

FrozStaObj

Disable Frozen Static Objects

FrozEvtObj

Disable Frozen Event Objects

EventClass

Class 1

Scaling

OFF (excluding Unbalx10 and Freqx10 which are ON)

IONZero

0

IONFull

0 (1000 for Unbalx10 and 100 for Freqx10)

DNPZero

0

DNPFull

0 (10000 for Unbalx10 and 1000 for Freqx10)

Some setup register settings vary for different modules. Specifically, BasePoint
differs for each module within a group (Analog Input and Binary Counter are
groups), and StaticObj is set to Analog Input for the 11 analog input points and
Binary Counter for the three binary counter points. (StatObj defines the type of
DNP object the module provides when the Master polls it.)
In addition, Scaling is OFF for all but two modules. The only modules that apply
scaling are the Analog Input points that provide Voltage and Current Unbalance
data (labeled Unbalx10) and Frequency data (Labeled Freqx10). These modules
apply x10 scaling.

Chapter 3 - Default Meter Functionality

Page 61

Using the DNP 3.0 Protocol

9300 Series User’s Guide

DNP Options Module Settings
The DNP Options module provides global settings that affect all DNP Slave Export
and DNP Slave Import modules. The default settings in this module are shown in
the following table.
Setup Register

Setting

Function

BinInStatic

Single-bit Binary Input

Variant for Binary Input Static objects

BinInEvents

Binary Input Change w/o time

Variant for Binary Input Event objects

BinInEvDepth

100

Maximum number of Binary Input Events that can be stored

BinCntStatic

16-bit Binary Counter w/o flag

Variant for Binary Counter Static objects

FrzCntStatic

16-bit Frozen Counter w/o flag

Variant for Frozen Counter Static objects

FrzCntEvents

16-bit Frozen Counter Event w/o time

Variant for Frozen Counter Event objects

FrzCntEvDepth

100

Max number of Frozen Counter Events that can be stored

CntChangeEvents

16-bit Counter Change Event w/o time

Variant for Counter Change Event objects

CntChangeEvDepth

100

Max number of Counter Change Events that can be stored

AIStatic

16-bit Analog Input w/o flag

Variant for Analog Input Static objects

FrzAIStatic

16-bit Frozen Analog Input w/o flag

Variant for Frozen Analog Input Static objects

FrzAIEvents

16-bit Frozen Analog Event w/o time

Variant for Frozen Analog Input Event objects

FrzAIEvDepth

100

Max number of Frozen Analog Input Events that can be stored

AIChangeEvents

16-bit Analog Input Change Event w/o time

Variant for Analog Input Change Event objects

AIChangeEvDepth

200

Max number of Analog Input Change Events that can be stored

AOStatic

16-bit Analog Output Status

Variant for Analog Output Block objects

SelectTimeout

10

Select Before Operate timeout period (in seconds)

TimeSynchPeriod

86400

Time (in seconds) between IED requests for time syncs

ALFragSize

2048

Max application layer message size (in octets) that IED can send

DLAck

Never

When device requests data link layer acknowledgements

DLTimeout

2

How long the data link layer waits for acknowledgement from Master

DLNumRetries

0

How many times a data link layer packet is re-sent after failing

Importing Data using DNP 3.0
Data can be imported into the 9330 and 9350 from a DNP Master device. DNP
Slave Import modules are used to take a DNP analog or binary output object and
map it into an ION numeric or Boolean register. Refer to the ION Programmer’s
Reference for detailed module descriptions.

Page 62

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Using the Profibus Protocol

Using the Profibus Protocol
Those 9300 meters ordered with the optional Profibus port are suitable to provide
many real-time power system measurements to a Profibus network. Profibus
Master devices connected to the 9300-Profibus can access this data. Refer to the
9300 & 9330 Profibus Protocol Document for complete details on the Profibus
implementation in the 9300.
Factory Profibus Configuration for the 9300
The 9300-Profibus makes data available to Profibus devices using 12 Profibus
Slave Export modules. These modules are linked to other modules in the 9300 that
provide energy, power and demand data through the Profibus Commun-ications
module. As the data available through the Profibus Slave Export modules is in a
specific format, knowledge of the Profibus protocol and an understanding of the
settings used in the 9300 are required to interpret the data provided.
Changing the Profibus Configuration
If the factory Profibus configuration does not suit your needs, link the unused
parameters in the existing Profibus Slave Export modules. If you require more
changes, you will have to relink these modules to other parameters.

Profibus Slave Export Module Parameter Mapping
The following tables detail the measurements provided by 12 Profibus modules.
The “Source ION Module” is shown so that you can easily unlink parameters if
you want to access different data. To change scaling refer to the Profibus Slave
Export module description in the ION Programmer’s Reference.

Chapter 3 - Default Meter Functionality

Page 63

Using the Profibus Protocol

9300 Series User’s Guide

Profibus Slave Export Module 1 (Scaling x10)

Profibus Slave Export Module 2 (Scaling x10)

Source ION Module

Measurement

ION Label

Source ION Module

Measurement

ION Label

Power Meter

Volts line to neutral A

Vln a

Power Meter

Volts line to line AB

Vll ab

Power Meter

Volts line to neutral B

Vln b

Power Meter

Volts line to line BC

Vll bc

Power Meter

Volts line to neutral C

Vln c

Power Meter

Volts line to line CA

Vll ca

Power Meter

Volts l-n average

Vln avg

Power Meter

Volts l-l average

Vll avg

Maximum #4

Vln avg Maximum

Vln mx

Maximum #8

Vll avg MAX

Vll avg mx

Maximum #31

kVAR Tot Th. Dmd max

kVAR td mx

Maximum #32

kVA Tot Th. Dmd MAX

kVA td mx

Profibus Slave Export Module 3 (Scaling x10)

Profibus Slave Export Module 4 (Scaling x10)

Source ION Module

Measurement

ION Label

Source ION Module

Measurement

ION Label

Power Meter

Current Phase A

Ia

Power Meter

kW phase A

kW a

Power Meter

Current Phase B

Ib

Power Meter

kW phase B

kW b

Power Meter

Current Phase C

Ic

Power Meter

kW phase C

kW c

Power Meter

Average Current

I avg

Power Meter

kW Total

kW tot

Maximum #13

Max. Average Current

I avg mx

Thermal Demand #1

kW Total Th.Demand

kW td

Minimum #13

Min. Average Current

I avg mn

Maximum #30

kW Total Th. Dem. Max

kW td mx

Profibus Slave Export Module 5 (Scaling x10)

Profibus Slave Export Module 6 (Scaling x10)

Source ION Module

Measurement

ION Label

Source ION Module

Measurement

ION Label

Power Meter

kVAR phase A

kVAR a

Power Meter

kVA phase A

kVA a

Power Meter

kVAR phase B

kVAR b

Power Meter

kVA phase B

kVA b

Power Meter

kVAR phase C

kVAR c

Power Meter

kVA phase C

kVA c

Power Meter

kVAR Total

kVAR tot

Power Meter

kVA Total

kVA tot

Th. Demand #2

kVAR Total Th. Demand

kVAR td

Th. Demand #3

kVA Total Th. Demand

kVA td

Maximum #31

kVAR Tot Th. Dmd max

kVAR td mx

Maximum #32

kVA Tot Th. Dmd MAX

kVA td mx

Profibus Slave Export Module 7 (Scaling x10)

Profibus Slave Export Module 8 (Scaling x100)

Source ION Module

Measurement

ION Label

Source ION Module

Measurement

ION Label

Power Meter

Power Factor phase A

PF a

Power Meter

Volts unbalanced

V unbal

Power Meter

Power Factor phase B

PF b

Power Meter

Current unbalanced

C unbal

Power Meter

Power Factor phase C

PF c

Power Meter

Line Frequency

Freq

Power Meter

Power Factor Total

PF sign tot

Maximum #21

Line Frequency max

Freq mx

Minimum #22

Power Factor Lead min

PF lead mn

Minimum #21

Line Frequency min

Freq mn

Minimum #23

Power Factor Lag min

PF lag mn

---

Not used

---

Page 64

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Using the Profibus Protocol

Profibus Slave Export Module 9 (No Scaling)

Profibus Slave Export Module 10 (No Scaling)

Source ION Module

Measurement

ION Label

Source ION Module

Measurement

ION Label

Integrator #3

kW hour Total

kWh tot

Integrator #1

kW hour Import

kWh imp

Integrator #7

kVAR hour Total

kVARh tot

Integrator #2

kW hour Export

kWh exp

Integrator #9

kVA hour

kVAh tot

Integrator #4

kW hour Net

kWh net

---

Not used

---

Integrator #5

kVAR hour Import

kVARh imp

---

Not used

---

Integrator #6

kVAR hour Export

kVARh exp

---

Not used

---

Integrator #8

kVAR hour Net

kVARh net

Profibus Slave Export Module 11 (Scaling x10)

Profibus Slave Export Module 12 (Scaling x100)

Source ION Module

Measurement

ION Label

Source ION Module

Measurement

ION Label

S W Demand #1

kW Sliding Demand

kW swd

Power Meter

kVA phase A

kVA a

S W Demand #1

kW Predicted Demand

kW swd pred

Power Meter

kVA phase B

kVA b

Maximum #27

kW Sliding Demand max

kW swd mx

Power Meter

kVA phase C

kVA c

Minimum #27

kW Sliding Demand min

kw swd mn

Power Meter

kVA Total

kVA tot

---

Not used

---

Thermal Demand #3

kVA Total Th. Demand

kVA td

---

Not used

---

Maximum #32

kVA Tot Th. Dmd MAX

kVA td mx

Chapter 3 - Default Meter Functionality

Page 65

Restoring the Factory Configuration

9300 Series User’s Guide

Restoring the Factory Configuration
If you have made changes to the default functionality and want to return to the
factory configuration, you can e-initialize the factory configuration in the meter
through Designer. The basic setup of the device can be retained, so the meter does
not need to be taken out of service for a long period of time.

NOTE
If you restore the factory configuration, all custom features you created are lost.

To restore the factory configuration:
1.

Display the meter’s main Configuration screen in Designer.

2.

Choose Select All from the Edit menu, then press Delete on your keyboard.
The confirmation dialog box appears explaining that some modules will not be
deleted (core modules cannot be deleted — scroll down in the dialog to see that
various standard modules will be deleted).

3.

Click OK on the confirmation dialog box.
After a brief wait the modules are deleted, and the main meter Configuration
screen is blank except for the Frameworks folder in the Advanced Setup area.
(The Frameworks folder contains the folder of Core modules which cannot be
deleted.)

4.

Choose Select All from the Edit menu to select the Frameworks folder. This
selects all subfolders and modules within the folder.

5.

Choose Paste from Framework in the Edit menu, and select the appropriate .fwn
file from the folder \WinPM.Net\config\fmwk\nd\ and click OK.
Ensure that the chosen .fwn file includes the following in the filename:
The model name of the meter you are restoring (i.e. 7300, 7330 or 7350)
The base firmware version (e.g. v250, v265, etc.)
For example, if you are restoring an 9300 with a V252 firmware version, you
could select the file “7300_v250_FAC-4WYE_V2.1.0.0.0.fwn”. Although this file
was designed for V250, the framework is also used for V252, because v250 is the
base firmware version upon which v252 is built. (For details about framework
files, contact Customer Service.)

6.

Click Open. The Paste Summary window appears.

7.

Click on the first module, scroll down to the last module, hold the Shift key and
click on the last module. This selects all of the modules.

8.

While holding the Shift key, click on the check box to the left of the module name
so you see a lock icon with a green checkmark.

9.

Check “Maintain external inputs” and click OK on the confirmation dialog box.
A message appears indicating that Designer is pasting modules. All modules are
selected when the paste is complete. Click anywhere in the background of the
node diagram to deselect all of the modules.

Page 66

Chapter 3 - Default Meter Functionality

9300 Series User’s Guide

Restoring the Factory Configuration

10. Click the Power Meter shortcut in the Basic Configuration area to select it. Once
selected, click Reset in the Designer toolbar, or select Reset from the Edit menu.
This reverts the Power Meter to the settings it had before you deleted any
modules (retaining the basic setup you previously had).
11. Choose Send & Save from the File menu. The factory configuration is now
restored (any custom functionality you created is removed).

Chapter 3 - Default Meter Functionality

Page 67

Restoring the Factory Configuration

Page 68

9300 Series User’s Guide

Chapter 3 - Default Meter Functionality

4

Using ACCESS Software
ACCESS software encompasses a variety of programs that enhance the
functionality and usability of your ACCESS devices. ACCESS software can collect
data via serial, wireless, modem, or Ethernet links, so you can manage a single site
or global network of devices. WinPM.Net is a software suit with applications for
displaying data, configuring ACCESS meters, and much more. ION Setup is a
stand-alone program that greatly simplifies meter configuration.
This chapter recognizes the various ACCESS software programs available to you,
providing instructions on each program’s use. Details on where to find more in
depth information on a program’s operation are included in that program’s
introduction.

In This Chapter
WinPM.Net Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
WinPM.Net: Management Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Configuring Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
WinPM.Net: Vista . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Displaying Data with Vista . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Customizing the Vista Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
WinPM.Net: Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Basics of ION Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Designer’s Main Configuration Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Viewing Real-time Data in Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Changing Setup Registers with Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Customizing Frameworks in Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
WinPM.Net: Reporter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Pre-configured Reports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Report Creation and Generation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
ION Setup Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Configuring Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Basic Meter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Displaying Data with ION Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

WinPM.Net Software

9300 Series User’s Guide

WinPM.Net Software
WinPM.Net software offers control capabilities and comprehensive power quality
and reliability analysis. It is a powerful software suite that can process, analyze,
store, and share data across your entire enterprise. The fully networked clientserver information system allows you to access data from any workstation, locally
or around the world, in the format you need. With WinPM.Net you can manage an
intelligent ACCESS metering network, monitoring and controlling individual
devices, analyzing data, and deciding on new courses of action.
WinPM.Net software has four main components, each with their own user
interfaces. These applications are the Management Console, Vista, Designer, and
Reporter.
If you require more information on WinPM.Net software than is presented here,
refer to the online WinPM.Net Help or the WinPM.Net Getting Started Guide.

Software Security
The software security system limits how you can use ACCESS software to view
meter data and send configuration changes to ACCESS meters. A valid user
account and password are required to log on to any ACCESS software application.
Each access level, or authority, that is specified for a user account defines the types
of operations available in each application, so you may not necessarily be allowed
to view or configure meter information if your authority is too low.
WinPM.Net provides two default software security settings: guest and supervisor.
Both of these default security settings use 0 (zero) for the password, and enable the
highest level of authority which allows complete control of the system.

NOTE
Since both the software and the meter use password security, you may need to enter the software
password, meter password, or both depending on the function you are performing.

Page 70

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

WinPM.Net: Management Console

WinPM.Net: Management Console
The Management Console is responsible for building your network. You build
your power-monitoring network to reflect the way your physical communications
network is wired so that WinPM.Net software can communicate with your
devices. The network is created using servers, sites, devices, and modems. These
network components must be configured in the Management Console before you
can use the other WinPM.Net applications.

Title Bar
System
Setup Pane

Network
Component
Icon

Display
Window

The following is a brief description of each network component. To learn how to
configure these components, refer to the “Configuring Communications” section
of this chapter.
Servers
A server is a computer in an WinPM.Net system running administrative software
that controls access to the network and its resources, such as ION devices, and
provides resources to computers functioning as workstations on the network. A
server runs service components that create communication and software links
between ACCESS systems components, and it creates links into the ACCESS
database, too.
Computers with primary and secondary WinPM.Net installations are servers, as
they have the communication software (services) installed. A primary server
contains all software components and the database; a secondary server contains
software but references the primary server for program files and database
information. Both server types connect directly to ACCESS devices via serial,
Ethernet, or modem links, but there can be only one primary server on a network.
When you install WinPM.Net, the Primary Server must be installed before any
Secondary server or Client computers.

Chapter 4 - Using ACCESS Software

Page 71

WinPM.Net: Management Console

9300 Series User’s Guide

Sites
A site in an WinPM.Net system contains one or more intelligent devices that share a
common communications link. There are three different types of sites, based on the
type of communications medium each uses. The site types are as follows:
Direct (Serial) Site - a direct-connected RS-232 or RS-485 network
Modem Site - a remote serial site connected by a modem
Ethernet Gateway Site - a gateway that transfers data between an Ethernet
device and an RS-485 chain of connected devices

NOTE
You are not required to create a site for an Ethernet Device, unless you intend to use the device as an
Ethernet Gateway Site.

Depending on the site type, devices belonging to a site may be at different physical
locations.
Devices
Devices refer to intelligent devices (basic energy meters, multi-function
monitoring/analysis/control devices, intelligent relays, etc.) that can be connected
to an WinPM.Net network serially, via Ethernet, or through a gateway.
Serial Devices belong to Direct Sites or Modem Sites, so they communicate using
modem, RS-232, or RS-485 connections. Before these types of devices can be added
to the network, they require the prior configuration of a Direct Site or Modem Site.
Ethernet Devices are those that are directly connected to an Ethernet network. You
are not required to create a site for an Ethernet Device, unless you intend to use the
device as an Ethernet Gateway Site. Furthermore, you can manually connect and
disconnect your Ethernet Devices from the Management Console.
Dialout Modems
A Dialout Modem is the modem that a server computer uses to communicate with
a remote modem at a Modem Site.
Connection Schedules
Connection schedules are programmed routines for a server to regularly connect
to and disconnect from Modem Sites and their associated ACCESS (or other)
devices. If so desired, you can also create connection schedules from Direct Sites
and Ethernet Devices/Ethernet Gateway Sites.

Page 72

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Configuring Communications

Configuring Communications
Before you can talk to the devices on your network, you need to configure
communications within the Management Console. Essentially, this means adding
one or more sites and then adding the devices associated with each site. If you
create a modem site, then you also need to add and configure a dialout modem.
There may be instances where you want to add a new server (either another
computer or third-party gateway); the computer running the WinPM.Net software
is considered a server and is listed in the Server section.
Adding a new Server, Site, Device or Dialout Modem
1.

Click the appropriate network component icon (Servers, Sites, Devices,
Dialout Modems) in the System Setup pane. The title bar reflects your
selection.

2.

Right-click in the display window, select New and the type of Server, Site,
Device. If you are configuring a modem you only have one New option.

3.

Configure the item using the drop-down list boxes and manually entering
values where required.

4.

Right click in the Properties dialog box to access Advanced Properties. You can
use the drop-down list boxes or manually enter new values as required.

5.

Click OK when you are done.

The process of adding network components to the Management Console is the
same for each component — the difference lies in how you configure the
components. When the Properties dialog appears for the component you added,
the fields for which you are required to provide information are highlighted in red.
For example, the illustration below shows the required fields when adding a new
Ethernet device:
Although Group has
a drop down list box,
you are not restricted
to the values in the
list. If you want to
create a new group,
simply type its name
in the value field.
Other drop down list
boxes restrict you to
the values in the list.

The Properties dialog has different required fields depending on which component
you are adding:
For a Direct Site you specify the serial port (COM1, COM2, etc.) on the server
computer where the serial device (or network of serial devices) is connected.
You must specify the server computer that communicates with the direct site.
For a Modem Site you provide information about the modem at the (remote)
modem site: baud rate, modem telephone number, etc. You also specify the
server computer that communicates with the modem site.

Chapter 4 - Using ACCESS Software

Page 73

Configuring Communications

9300 Series User’s Guide

For an Ethernet Gateway Site, you specify the Ethernet device acting as the
gateway and the TCP/IP port to which the serial device, or network of serial
devices, is connected. Before you can add an Ethernet Gateway Site, an Ethernet
Device must be added and configured first.
For a Serial Device you provide the device type, the unit ID, and the site to
which the meter is connected. Before you can add serial devices, a Serial or
Modem Site must be added and configured first.
For an Ethernet Device you specify the type of meter, the meter’s IP address,
and the server computer that communicates with the Ethernet device.
For a Dialout Modem, you provide the modem type, the computer that
communicates over the modem channel, and the serial port used on the
computer.
For a Computer (Server) you specify the machine’s computer name.
For a 3rd-Party Gateway (Server), you specify the name of the network host, the
IP address of the gateway device, and the computer that communicates through
the Ethernet gate
Complete details on working with the Management Console are available in the
WinPM.Net Getting Started guide, or the online WinPM.Net Help.

Page 74

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

WinPM.Net: Vista

WinPM.Net: Vista
Vista is a display, analysis, and control application. It is the main user interface to
the WinPM.Net system. Vista presents a graphical view of your power system,
allowing you to view real-time data from power meters or historical data from the
WinPM.Net database. It simplifies the tasks of managing your power system and
transcends a number of physical device boundaries, so you can retrieve, store, and
display data from any device in your system through a unified interface. Vista
reports on the status of your power system components, informing you of alarm
conditions and providing you with control capabilities for initiating intelligent
device functions or actuating field machinery.

Displaying Data with Vista
A standard set of Vista User Diagrams display real-time and logged data for
various power system parameters. Interactive objects are provided on the
diagrams that allow operators with appropriate authority to enable and disable
logging functions and reset cumulative parameters.
A network diagram uses links to default user diagrams to display data from each
device in your system. When you generate a network diagram, Vista automatically
locates all devices in your system and displays them.
Generating a network diagram in Vista
1.

Select Generate Network Diagram from the File menu.
The Network Diagram initially looks like this:

Menu bar
Toolbar

Vista
Grouping
Object

2.

Click the appropriate grouping object. These are labelled according to the
device’s “Group” value in the Management Console.

NOTE
If you have Show Toolbox selected in the Options menu, you must double-click diagram objects and icons
instead of single clicking them.

Chapter 4 - Using ACCESS Software

Page 75

Displaying Data with Vista

9300 Series User’s Guide

This opens a new window showing all of the installed meters. Each meter
appears with an icon that represents its type and a label reflecting the name you
configured in the Management Console.

Meter icons
(representing
configured
devices in the
Management
Console)

3.

Click a meter icon to open its main default diagram.

Each meter has a set of default diagrams that show the results of various real-time
measurements and calculations that are being performed. Links to data,
waveform, and event logs are also provided (if the meter supports logging).
You should now be able to navigate through the various diagrams and view realtime and logged data.
Displaying Data if the Software is not Fully Configured
If WinPM.Net has been installed and configured using the recommended
guidelines in the WinPM.Net Getting Started guide, the standard Vista user
diagrams automatically display real-time data from your meter.
If you are unable to display data from your meter in Vista, contact your
WinPM.Net software administrator, or refer to the WinPM.Net Getting Started
guide before continuing with this User’s Guide.

Page 76

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Displaying Data with Vista

Vista Diagram Elements
Each Vista diagram shows the name of the meter, the time on the meter’s clock,
and the type of meter. The main diagrams also provide buttons that let you jump
to other diagrams. Jump to another diagram by clicking any of the buttons near the
top right-hand corner (as illustrated in the Volts/Amps diagram below).

Click any of these
buttons (grouping
objects) to jump to other
diagrams.

Click this button
to return to the
Network
Diagram.

Events and Alarms
are available
through the Event
Log viewer.

This numeric object
shows real-time data.

Logged data is
available through
these data log
viewer objects.

This grouping object
leads to Long-Term
Min/Max data.

Click this control object
to enable/disable
historic data logging.

Most measurements appear on-screen in Vista numeric objects.
Some ON/OFF quantities, such as the status of a setpoint, may appear as status
objects.
To view another screen or diagram, click on a grouping object. Grouping objects
may be in the form of buttons, folders, meter icons, etc.
To return to the previous diagram, use the
use the File > Up One Level menu item.

button on the Vista toolbar, or

Level 3 WinPM.Net authority is required to use control objects.
Logged data (such as snapshot, interval and waveform data) can be accessed by
clicking the associated the data log viewer icon, which looks like this
To view a record of events and alarms for the active user diagram,
click

— the event log viewer icon.

To view records of high-priority events and alarms for your entire system, select
the global event log viewer from the View pull-down menu.

Chapter 4 - Using ACCESS Software

Page 77

Displaying Data with Vista

9300 Series User’s Guide

Summary of Data Provided in Vista
The standard set of Vista diagrams included with WinPM.Net display a variety of
data measured by the factory-configured meter. Some of the diagrams include
grouping windows that display additional data. The following section
summarizes the data, and interactive control functions provided.
Real-Time Measurements
The Real-Time diagram includes a simple power system illustration that shows
various real-time parameters. The diagram also includes links to a min/max
parameter display. The measurements you see in Vista depend on the Volts Mode
setting in your Power Meter module; here are some you may see:
Line-to-neutral voltages, line-to-line voltages, average L-N and L-L voltages and
voltage unbalance level
Phase currents and average current, or total current
Phase kW, total kW, kVAR and kVA
Frequency and signed power factor
Min/max display of each of the above parameters
All logged meter events
Trend logs of voltage, current, power, frequency and power factor
Long-term Min/Max
Double-click the Long-term Min/Max object to see a Vista grouping window
showing min/max values for line-to-line and line-to-neutral voltages, voltage
unbalance, phase currents, power values (kVA, kVAR and kW), frequency, and
power factor. Level 3 WinPM.Net authority is required to reset the min/max
values.
To return to the real-time diagram, use the
the File pulldown and select Up One Level.

button on the Vista toolbar; or use

Min/max values are valid from the time the meter was powered up, or valid from
the time the last reset was performed.
Historic Data Logging Enable
The Log Server must be running to view historical data. Historic data logging is
enabled by default. Level 3 WinPM.Net authority is required to use the enable
control object. The control object indicates the logging enable status: the switch is
in the up position (1) when logging is enabled, and down (0) when logging is
disabled.
Power Quality Data
The Power Quality diagram shows voltage disturbance and harmonics details. The
voltage disturbance display counts sag/swell and transient events, and provides
links to a sequence-of-events log and a CBEMA plot. The diagram includes a
trigger for manual waveform recording, and control objects for enabling/disabling
power quality event recording.

Page 78

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Displaying Data with Vista

The harmonics measurement display shows total harmonic distortion for each
phase of voltage and current. Links to harmonics min/max and harmonics
trending displays are provided, and a control object is included for enabling/
disabling harmonics logging
Voltage Disturbance Counter Reset
Level 3 WinPM.Net authority is required to reset the power quality event
counter, the manual waveform trigger, and the control objects.
Disturbance Details
The Log Server must be running to view the CBEMA plot or sequence-of-events
data.
Long-term Min/Max
Double-click the Long-term Min/Max object to see a Vista grouping window
showing min/max values for phase voltage and current THD.
Level 3 WinPM.Net authority is required to reset the min/max values.
Harmonics Measurements
Total Harmonics Distortion (THD) is displayed as a percentage of the
fundamental.
Harmonics Trending
The Log Server must be running to view the logged harmonics data.
Harmonics data logging is enabled by default.
Level 3 WinPM.Net authority is required to use the control object.
The control object indicates the logging enable status: the switch is in the up
position (1) when logging is enabled, and down (0) when logging is disabled.
Setpoints
The Setpoints diagram uses setpoints to monitor kW demand, over current and
under average voltage and power factor levels. Vista annunciates warnings if any of
the values exceed specified limits. Users with Level 3 WinPM.Net authority can
define the setpoint limits.
Monitoring of kW demand, phase current and voltage unbalance conditions,
with annunciation when user-specified upper limit is exceeded
Real-time display of kW demand, phase current and voltage unbalance
Over kW Sliding Window Demand Monitoring
Over kW demand monitoring is disabled by default. Level 3 WinPM.Net authority
is required to enable this monitoring. The status will read NOT AVAILABLE when
monitoring is disabled.

Chapter 4 - Using ACCESS Software

Page 79

Displaying Data with Vista

9300 Series User’s Guide

Energy & Demand Calculations
The Energy & Demand diagram shows the real-time sliding window demand for
kW, kVA and kVAR, and the real-time energy values kWh net, kVARh net and
kVAh. Peak demand is displayed for kW, kVAR and kVA, and a link to a demand
profile trend is provided. Control objects for enabling/disabling demand logging
and resetting energy and demand values are also included.
Real-time and peak kW, kVAR and kVA sliding window demand
Real-time net kWh, net kVARh and kVAh energy values
Trend log of all of the above parameters, plus power factor lead and lag,
imported, exported and net energy
Demand, Energy and Peak Demand Reset
Level 3 WinPM.Net authority is required to reset these values.
Demand Profile Trending
The Log Server must be running to view the energy and demand log. Energy and
demand logging is enabled by default. Level 3 WinPM.Net authority is required to
use the enable control object. The control object indicates the logging enable status:
the switch is in the up position (1) when logging is enabled, and down (0) when
logging is disabled.
Over Average Current Monitoring
Over current monitoring is disabled by default. Level 3 WinPM.Net authority is
required to enable this monitoring. Each status reads “Not Available” when
monitoring is disabled.
Under Average Voltage Line-to-Line Monitoring
Over voltage monitoring is disabled by default. Level 3 WinPM.Net authority is
required to enable this monitoring. The status reads “Not Available” when
monitoring is disabled.
Under Power Factor Monitoring
Under power factor monitoring is disabled by default. Level 3 WinPM.Net
authority is required to enable this monitoring. The status reads “Not Available”
when monitoring is disabled.
Digital Inputs
The Digital Inputs diagram monitors the four status inputs on the 9300. The status
of each input (ON or OFF), and the number of times the status has changed is
displayed. The status change counter can be reset.
Monitoring of the 9300 meter’s four on-board status inputs
Status change counter for each input
Status
The 9300 meter’s status inputs are de-energized when the meter is powered-up, so
each status will initially be OFF.
Reset
Level 3 WinPM.Net authority is required to reset the status counter.

Page 80

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Customizing the Vista Interface

Customizing the Vista Interface
Standard Vista diagrams show much of the data that the factory-configured meter
measures and calculates. However, the factory-configured meter can provide
additional data that is not presented by default with these display tools. This data
can be added to the standard Vista diagrams by placing addition diagram objects
on them; or, you can create new user diagrams to display any additional data you
want.
Vista cannot be used to customize data displays on the ACCESS meters
themselves.

NOTE
Level 5 ACCESS software authority (Supervisor) is required to create and configure new Vista diagrams.
If you do not have Level 5 password authority, contact your ACCESS software administrator for assistance.

Diagram Objects in a User Diagram
Diagram objects provide the interface to ION registers in your network, and to
DDE values from other applications. Each diagram object displays a single piece
of information from somewhere in your power-monitoring network; for example,
a single numeric object displays numeric data from a single source.
If your account has permission to edit user diagrams, the following diagram
objects are represented by icons in a floating toolbox.

If this toolbox is not available in Vista, yet you have the proper permissions to edit
user diagrams, you must select Options > Show Toolbox from the Vista menu. A
check mark next to the option indicates that it has been selected.
To place a diagram object, simply click, drag and drop the object you want from
the toolbox onto the current Vista display window. Once you have added the
diagram object, right-click the icon to specify the actions you want it to perform.
Complete details on configuring diagram objects and creating Vista User
Diagrams are in the online WinPM.Net Help.

Chapter 4 - Using ACCESS Software

Page 81

Customizing the Vista Interface

9300 Series User’s Guide

Custom Appearance of a User Diagram
You can customize the appearance and configuration of any window within a user
diagram. You can alter a window's font or background color, or configure window
properties such as background image, real-time and logged data links, doubleclick action, and stale data settings.
To make one or more of these changes, right-click anywhere in the background of
a user diagram. A menu appears with three selections:

Choosing Default Font or Background Color allows you to customize the area
implied by the selection. Choosing Properties brings up the Window Properties
Configuration box, which offers five groups of options: Image, Log Server, Node,
Action and Stale Data. Complete details on these options are found in the online
WinPM.Net Help.

Page 82

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

WinPM.Net: Designer

WinPM.Net: Designer
Designer is an application for advanced users who know the nature of ION
architecture, specifically the nature of frameworks. A framework is a number of
ION modules arranged (linked) to perform a specific function or number of
functions. Designer allows you to customize current frameworks by adding,
deleting, or re-linking ION modules, and it allows you to create entirely new
frameworks. Although it can be used to perform basic setup, such as changing an
ION module’s setup register, it is recommended that you only use Designer for
framework customization and creation.

NOTE
In most cases, you will be able to achieve the functionality you want by changing the settings in an existing
module’s setup registers. For this operation it is recommended that you use ION Setup.

Basics of ION Architecture
Before you begin altering the meter’s operation, it is advisable to familiarize
yourself with the basics of how the device operates. Understanding the basics of
the ION architecture will help you understand how to make different types of
configuration changes.
The ION architecture applies the principles of object-oriented software design to
the creation of functionality inside your devices. The object-oriented structure
allows you to connect different discrete objects (called ION modules) in different
ways to define how information is accessed, transferred, and manipulated inside
the device and across the power monitoring network.
Each ACCESS device contains a number of ION modules that perform specific
functions. The ION modules are linked together to create frameworks or
framework templates, defining multiple operations and logical pathways for
power system information. The basic structure of an ION module is the same for
each module type, making it easy to use new features once the basics are
understood.

Chapter 4 - Using ACCESS Software

Page 83

Basics of ION Architecture

9300 Series User’s Guide

ION Modules
The ION module is the basic building block of the ACCESS device’s operating
software. A module can be considered as a “function box”: it receives data from its
inputs, makes decisions based on the settings in its setup registers, and then makes
data available at its output registers. All functionality provided by an ACCESS
device can be considered in terms of its modules and the linkages between them.

ION Module
Output 1
Input 1
Input 2

INPUT REGISTERS
are connected to the output
registers of other modules;
data flows into them.

Output 2

OUTPUT REGISTERS
hold the result of the
module’s operation–
this data is available to
other ION modules.

SETUP REGISTERS
control how the module
processes data

Modules are linked together to create powerful functions. For example, the
framework below consists of four modules that, when combined, trigger a
waveform recording in response to an over-voltage condition.

Power Meter
Module

Voltage on phase A
is measured

Vln a

Setpoint
Module

Trigger

Setpoint goes ON when
Vln a exceeds a limit and
outputs a trigger pulse

One-Shot Timer
Module

Trigger

One-Shot Timer waits for
a specified period then
outputs a trigger pulse

Waveform Recorder
Module

Waveform log

Waveform is recorded
and stored in the log file

Module Linking Restrictions
The maximum number of modules that can be linked in a row is 25. This is referred
to as the framework’s depth. Modules that branch off or branch into the chain do
not affect the depth, and there is no restriction on the number of branches you can
have in a framework.
Another restriction concerns “circular” linking of modules. You cannot link a
module’s output register to its own input or to the input of any module that
precedes it in the chain. This protects you from creating infinite loops that can
waste system resources.
The one exception to this rule is the Feedback module, which makes circular
linkages possible (refer to the ION Programmer’s Reference).

Page 84

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Basics of ION Architecture

Sequence of ION Module Execution
ION modules always execute in the order of the data flow (in the example below,
from 1 to 4). This logical execution order is maintained even if you created the
framework from back to front.
1

1

3

4

2

ION modules may execute simultaneously if they do not depend on each other for
data (such as both ION modules labelled 1). Conversely, ION module 3 will not
execute until both ION modules 1 and ION module 2 have executed.

ION Registers
Each module has one or more output registers, and most modules have Setup
registers. (A module’s inputs are links to the output registers on other modules.)
There are different types of registers, each classified by the type of data they accept.
When you want to change a module’s configuration, you must supply the type of
data that is appropriate for the register you are configuring. The configuration
tools prevent you from entering the wrong type of data into a register, but they do
not prevent you from entering the wrong value.
The ‘NOT AVAILABLE’ Value
An ION module that requires a link to one or more of its inputs, but has no such
links created, does not contain any values in its output registers. Instead, its output
registers are set to NOT AVAILABLE. In addition, if a module has an input that is
invalid (for example, a line-to-neutral measurement for a 3-wire Delta system) its
output register is also set to NOT AVAILABLE. The NOT AVAILABLE value helps to
distinguish between cases where a register contains a value like 0 or OFF, and cases
where there is actually no value stored.

NOTE
The NOT AVAILABLE value appears in Vista objects that are linked to ION modules with output registers
that are NOT AVAILABLE. The front panel of the meter displays values that are NOT AVAILABLE as dashes (–).

If the inputs of a module are NOT AVAILABLE, its output registers are also NOT
AVAILABLE. The NOT AVAILABLE value propagates through all linked modules.
(The NOT AVAILABLE value propagates through linked Arithmetic modules
differently - refer to the ION Arithmetic module description in the ION
Programmer’s Reference.)

Chapter 4 - Using ACCESS Software

Page 85

Basics of ION Architecture

9300 Series User’s Guide

ION Configuration Changes and Module Security
When you make configuration changes to an ACCESS device you are either
changing a value in a module’s setup register (basic configuration) or you are
changing the linkage between two or more modules (advanced customization).
Certain parts of the meter’s operating software are protected against deletion and
tampering, specifically core ION modules, fixed module links, persistent ION
modules, and locked ION modules. Visit Power Measurement’s web site
(www.pwrm.com) for a complete listing of these module types for your meter.
Core Modules
Core ION modules are fundamental to basic device or software node operation.
You cannot create or delete core modules, and in some cases, you cannot configure
them. Those ION modules classed as Core modules are the same in every device
or software node, though not all devices and software nodes support all the Core
modules. The following are examples of Core Modules: Power Meter module,
Communications module, Display Options module, and the Factory Module.
Fixed Module Links
Several of the linkages between core modules are fixed; they are required for the
basic operation of the device. A fixed link cannot be removed. A core module with
fixed links can still be linked to other modules.
Persistent Modules
Persistent ION modules are similar to Core modules, as they are core to the
operation of the device and cannot be created or deleted. These ION modules are
protected, because they are factory-configured to provide important external
control functions. Many External Pulse modules are Persistent ION modules.

CAUTION
Persistent modules can be overwritten in Designer. When pasting a default framework onto a meter, use
lock-paste on the Persistent modules. Do not free-paste. A list of Persistent modules is available on the
Library page of Siemens's web site, under "ION Device Templates".

Locked Modules
Locked modules provide security for revenue meters. This type of module security
only applies to ACCESS meters with the revenue-lock enabled (RM) order option.
Furthermore, there are varying degrees to locked module security: Fully Locked,
Writable Locked, and Front Panel Locked. Fully Locked security is designed to
protect the revenue related functions within the meter; they cannot be modified in
any way. (Fully Locked modules have their values written via internal meter
methods, as the meter makes calculations based on its voltage and current inputs.)
Writable Locked security allows you to trigger or change the state of the ION
module, but you cannot delete it, link to it, or change its label. Front Panel Locked
security prevents registers from being altered remotely via software; you must use
the ACCESS meter’s front panel to make any modifications to these registers.

NOTE
Depending on the meter family, there may be different types of module security. Rev_write_state_lookup
means the module cannot be modified in any way, and Rev_destroy_lookup means the module cannot
be deleted.

Page 86

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Designer’s Main Configuration Screen

Designer’s Main Configuration Screen
If the software has been properly configured, the main screen of the meter’s node
diagram appears each time that you open a meter in Designer. If the ACCESS
software has not yet been configured, refer to the Getting Started Guide, or contact
your network administrator. The different types of device functions are grouped
together on the Designer screen, so you can quickly access the types of settings you
want to change.

ION modules appear on the
main Designer screen,
grouped by the functions
they perform. Right-click a
module to access its Setup
registers.

Folder icons indicate that
additional ION modules are
available. Double-click on
the folder to view them.

Status Bar

Once you have logged on to Designer and opened the meter’s node diagram, you
can begin configuring ION modules. Designer displays two types of objects on the
main configuration screen: ION modules and grouping objects (also called
folders).
A folder in Designer indicates that additional modules are available. Double-click
on a folder to access the modules contained inside it. In some cases a folder will
contain additional folders — continue double-clicking on the folders until you
reach the appropriate ION module.

Chapter 4 - Using ACCESS Software

Page 87

Viewing Real-time Data in Designer

9300 Series User’s Guide

Viewing Real-time Data in Designer
You can view the real-time values of output registers in Designer. This is useful
when you are linking these outputs to other modules. However, it is
recommended that you use Vista as your main data display application.
To view real-time data of output registers:
1.

Click Options > Show Toolbox on the Designer menu.

2.

Find the ION module you want, press the Shift key and click the output register.
The following example shows how the real-time data for the output is
displayed:

Changing Setup Registers with Designer
If you are familiar with the nature of ION architecture and comfortable using
Designer, you can use the application to modify ION modules’ setup registers.

NOTE
It is recommended that you use the Setup Assistant in the ION Setup software to configure an ION
module’s setup registers. The Setup Assistant is a user interface that provides access to the setup registers
for a meter. (Refer to the ION Setup section for more details.)

Page 88

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Changing Setup Registers with Designer

To configure ION module setup registers with Designer:
1.

Right-click near the module’s center. The ION Module Setup dialog box
appears, showing a list of setup registers available for configuration:

The list of available Setup
registers appears here.
Select a Setup register,
then click Modify... (or
double click on the Setup
register name).

2.

Highlight the Setup register you want to configure, and click Modify.... A
Modify Register dialog box appears.

A drop down list of option
appears when you click
on the arrow because this
setup register is of the
enumerated type.

Make the change to the register’s setting here. As there are different types of data
held in setup registers, there are different Modify Register dialog boxes. The
Modify Register dialog box may require that you choose an option from a list or
enter a numeric value.
A format option is available when modifying Numeric Bounded setup registers.
Clicking Format causes a “Formatted Numeric Value” window to appear:

Chapter 4 - Using ACCESS Software

Page 89

Customizing Frameworks in Designer

9300 Series User’s Guide

Use the Interval Format area if the setting you are changing requires intervals.
Use the Date/Time Format area if the setting you are changing requires specific
dates (such as those needed used in the Clock module). Click OK when you have
the desired setting for the time interval or date.
3.

Click OK when you are satisfied with your configuration changes.

Complete details about the Setup registers of every ION module are provided in
the ION Programmer’s Reference. Details about the Setup Areas on the main screen
of the node diagram can be found in the Default Functionality chapter.

Customizing Frameworks in Designer
To create custom functions, ION modules are linked together and then configured.
Linking ION modules is relatively straightforward: output registers on one
module are linked to the input registers of subsequent modules. Data flows from
the output register on the first module to the input registers on a second module.
Each module that receives data makes decisions and processes the data based on
its setup registers’ settings. Once the data has been processed, a module makes the
data available at its output registers. These output registers can then be linked to
the inputs of other modules, and so on.
Most ION modules perform simple, discrete functions. The combination of
modules linked together creates a more powerful functionality. Multiple modules
linked together can be referred to as a framework. Since a device’s operation can
be separated into the specific, smaller functions performed by the modules,
creating specialized functionality is simple if you understand the operation of the
component pieces.

CAUTION
The meter is factory-configured for optimal operation. You should not make any changes to its operating
software unless you are familiar with the ION architecture, you know specifically what you want to
accomplish, and you understand the effects of the changes you intend to make.

If you need to customize your meter’s operation, you will need to create new ION
modules, configure their settings, and in some cases link them to other modules.
Designer provides a graphical view of your meter’s internal operation, making
these tasks simple. If you require more information on Designer than is presented
in these pages, refer to the ION Programmer’s Reference or online WinPM.Net Help
for complete usage details.

Page 90

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Customizing Frameworks in Designer

Creating New Modules
To add a module, locate its icon in the Designer toolbox, press and hold the left
mouse button over the icon, and drag it onto the node diagram. Once you release
the mouse button, the module becomes part of the diagram and is ready to be
configured and linked.
Choosing the Module
The Designer toolbox displays icons for all the meter’s available module types. If
the toolbox is not displayed, choose Show Toolbox from the Options menu to make
it appear.
As you drag the mouse over the icons in the toolbox, the status bar at the bottom
of the Designer window displays the module type.
Each ION module available to a
meter appears in the toolbox.

Creating the Module
Follow these steps to create an ION module in the meter:
1.

On the ION Modules toolbox, press the mouse button down on top of the icon
of the module you want to create, and drag it onto the node diagram. As you
drag the icon, the cursor changes shape to indicate you are placing an object.

2.

Release the mouse button to place the module in the diagram. When you release
the mouse button, Designer places a pending module icon into the diagram
(pending modules appear with a dashed outline).

3.

Once you have configured the node to your liking, choose Send & Save from the
File menu to download the configuration to the node. The dashed outline is
replaced with a solid outline, indicating that your changes have been saved.
After a Send & Save, ION modules that are offline (or inactive) appear with a red
border. This can mean that the ION module’s setup is incomplete. Refer to the
online WinPM.Net Help for more details.

The web site has information about the setup register defaults a module contains
when it is initially created, as well as the ranges or options each setup register
supports.

Deleting Modules
To delete a module, select it by clicking its icon, then press the Delete key. Use
caution when deleting modules – any dependant modules will be affected.
Designer informs you of dependant modules if they exist on the same node.

Linking Modules
Module linking involves clicking on one module’s output register symbol,
choosing the output register you want to link, then clicking the input of a second
module and selecting the input to link to. This operation can be performed in
reverse – you can start with one module’s input and link to another module’s
output register if desired.

Chapter 4 - Using ACCESS Software

Page 91

Customizing Frameworks in Designer

9300 Series User’s Guide

You can link modules that reside on different nodes, provided that you are linking
between software nodes, or from a meter to a software node. You cannot link
modules between meters. The following section describes how to link modules
that reside on the same node. Refer to the ION Programmer’s Reference or the online
WinPM.Net Help for instructions if you want to link modules that reside on
different nodes.
Follow the steps below to link modules on the meter:
1.

Accessing module outputs

Click on the
symbol on the right side of the module icon to list a module’s
output registers. (To list the module’s setup registers, hold the CTRL key while
clicking on the
symbol.) In most cases, a pop-up menu appears and lists
the available registers. If the module has many registers, a dialog box appears
instead.

or

The cursor looks like this when
a linking operation is in
progress:

2.

Click on the register you want to select. In the case of the dialog box, double-click
on an output register, or choose the register and click Select.

3.

Drag the cursor towards the module to which you want to link; the cursor
changes and a dotted line follows it across the node diagram. This indicates you
are in the process of creating a link. The dotted line also shows where the
connecting line will appear in the node diagram once the link is made.
If you link to a module that is in a different window than the original module
(either in a different node diagram or grouping window), the dotted line
disappears, but the cursor still indicates that a link is in progress.

4.
Accessing module inputs

Click on the module icon’s left
symbol to display the module’s inputs. In
most cases, a pop-up menu appears and lists the module’s inputs. (If there are a
large number of inputs, a dialog box similar to the More Output Registers dialog
box appears instead.) Inputs that are a different class than the selected output
register are grayed out to indicate that you cannot select them.
If the input is already linked, the register label it is linked to is displayed beside
the input. If you select the input, the existing link is overwritten.

5.

Choose the input you want from the pop-up or dialog box.
If the two modules are in the same window, the dotted line remains on the
screen to show the link between the modules.

6.

Page 92

Save the changes you made to the node. When you save the line changes from a
dotted line to a thin black line to indicate that the link is now programmed on
the node.

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Customizing Frameworks in Designer

The linking procedure described in the preceding steps can also be performed in
reverse order. You can select a module’s input first and then link it to another
module’s output register.

Editing Existing Frameworks
If you are comfortable with the ACCESS software and the meter’s configuration,
you can make changes to the existing frameworks to customize operation. Any
edits you make to the existing frameworks alter the device’s operation — be sure
you understand what effect your changes will have before proceeding.
Checking an Output Register’s “Owner”
Using Designer, right-click a module’s output register to view its linkages, referred
to as “owners”. A dialog box appears showing all of the inputs that are linked to
that output register. With this information you can determine what changes will
result to the framework by deleting the links to the parameter. Note that links to
inputs on other nodes are not shown in this dialog box.

CAUTION
Viewing owners by right-clicking a module's output register will only show you module linkages on the
same node. Any links to modules on different nodes will not be shown. If links to modules on other nodes
may exist, always check the links at a module’s inputs.

Deleting the Link at a Module’s Input
You can also check the links at a module’s input. Using Designer, right-click on the
input symbol on a module to view a dialog box listing each of the inputs and the
output registers they are linked to. You can unlink inputs from within this dialog
box as well.
Replacing a Link
You do not need to unlink a module’s input before linking a different output
register to it. If you link an output register to an input that is already linked, the
existing link is overwritten.

Chapter 4 - Using ACCESS Software

Page 93

WinPM.Net: Reporter

9300 Series User’s Guide

WinPM.Net: Reporter
Reporter is a database reporting application. It lets you define, generate, and
manage comprehensive reports based on the data in your database. Reporter
retrieves data from the Relational Database Management System (RDBMS), and
processes it into a finished report in Microsoft Excel format. There are a number of
pre-configured reports available, including Power Quality, Load Profile, Energy
and Demand, and EN50160 reports. You can also generate custom reports that
incorporate virtually any data stored in the RDBMS and perform further analysis
using Excel’s advanced mathematical and graphical functions.
After you’ve designed custom reports and configured the Excel workbooks,
reports are updated automatically, either in response to a power system event, or
following a specified schedule. You can also configure reports to automatically
email selected recipients after updating.

NOTE
The Report View Manager, a component of the Reporter, can be used on its own to create custom
database views for use with other third party reporting packages. Advanced knowledge of database
operation may be required to use the Report View Manager with third-party applications. Refer to the
online WinPM.Net Help for details on the Report View Manager.

Pre-configured Reports
When you start Reporter, the main Reporter screen appears with a list of
pre-configured reports. The most commonly accessed reports are the Energy and
Demand report, the Load Profile report, and the Power Quality report. There are
also 2 reports related to the European EN50160 power quality standards.
Time of Use Schedule
used for Energy and
Demand reports.
This is not to be
confused with the
Time of Use Module

Page 94

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Pre-configured Reports

Energy and Demand
This report is designed to generate and display details about energy consumption
and peak demand levels over a given time period. It uses a Time of Use Schedule
(TOU) to reference the metered data against an energy provider’s tariff schedule.
The first step in creating an Energy and Demand report is to preconfigure the TOU
schedule that will be applied to the metered data. If you do not require a time of
use schedule, you can create a mock schedule with only one time period defined.
Use the EgyDmd Log as a query item.

Load Profile
This report generates a graphical representation of demand, or load levels, over a
given time frame. The profile is a characterization of peak loads that can be used
to determine and limit demand peaks which could lead to financial penalties for
energy consumers, or could signal a need for additional generation or the
introduction of load control programs for energy suppliers.
The Load Profile report also uses the EgyDmd Log as a query item, but it does not
use a TOU schedule.

Power Quality
This report summarizes the number and severity of sags and swells over a given
time range, and graphically represents the waveform captures of each individual
event for further analysis.
The Power Quality report is slightly different than the other two report types mainly in its requirements for different data log sources. The Power Quality report
requires a combination of the Sag/Swell Log and Waveform Log.

EN50160
EN50160 is a general power quality standard used by energy suppliers and energy
consumers in European countries. The report is a summary of the multiple pass/
fail results of the evaluation methods outlined in the standard.
The following logs are used for the EN50160_General report:
EN50160 Vlt Dp1 to EN50160 Vlt Dp5
EN50160 Ovrvlt1 to EN50160 Ovrvlt3
EN50160 Frq/Mg, EN50160 Flicker, EN50160 Intrp, EN50160 Hrm Vlt, EN50160
Ihm Vlt, and EN50160 Vunbal
All fourteen of the above logs must be added to each EN50160_General report.
EN50160 MSignal is the log used for the EN50160_Mains_Signal report.

NOTE
The 73xx Series meters do not support EN50160 compliance. Although you see them as viable selections
in Reporter, the 73xx Series meters do not have the logs needed to create EN50160 reports.

Chapter 4 - Using ACCESS Software

Page 95

Report Creation and Generation

9300 Series User’s Guide

Report Creation and Generation
These steps are used for creating all report types. Be sure to know which log(s) you
use for the report you are creating.

NOTE
If you are creating an Energy and Demand report, complete the steps under “Creating a Time of Use
Schedule” (following “Creating a Report”) before you procede with creating your report.

Creating a Report
1.

Start Reporter.

2.

Select the report type you want and click Copy.
The pre-configured reports include some basic programing to simplify the
customization process. It is recommended that you create a copy prior to
making changes, leaving the default report unmodified.

3.

Click the Properties button (while your copy is selected). The Report Properties
dialog box appears.
On the General tab, it is recommended that you change the default report name
to distinguish it from other reports you may create.

4.

Click New from within the Database Queries section. The Database Query
Properties dialog box appears.

5.

Select your DSN (Data Source Name). This is the name of your database file or
archive.

6.

Select the appropriate Log file(s) for the report. Click OK to close the Database
Query Properties dialog box.

7.

Click on the Distribution tab and select the appropriate checkbox.
You may need to provide more information, such as a destination folder or
email address, depending on your distribution method.

8.

Make any changes you require on the Advanced tab and write any information
you desire on the Notes tab.

9.

Save your new report template.

Generating the Report
1.

Select your report from the list.

2.

Click Generate.

The Report Generator extracts the requested information from the database,
applies the TOU (if required), and displays the report in Microsoft Excel. Larger
reports with many queries may take a few minutes to complete.

NOTE
If you selected the checkbox for Interactive Date Range on the Advanced tab, you are prompted to select
the date range within the Interactive Date Range screen.

Page 96

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Report Creation and Generation

Creating a Time of Use Schedule
1.

Start Reporter and select the TOU tab.

2.

Select the Sample file, then click copy to duplicate it.
All of the pre-configured samples include some basic programing to simplify
customization. It is generally best to create a copy of the samples before making
changes, and leave the sample in its default state.

NOTE
Be aware that the NEW button creates a completely new report or TOU schedule with no default
configuration. Use this option to create completely customized reports.

3.

Select your new copy and click Properties to configure it.
Examples of the changes you may want to make to the TOU schedule are as
follows:
Rename the TOU Schedule using the appropriate field.
Modify On Peak and Off Peak charges using the appropriate field.
Add a 'Shoulder Period' which is often called a 'Partial Peak' (see below).
Change the Holidays to an appropriate country (see below).

4.

Save the new TOU configuration when configuration is complete.

Adding a Shoulder Period
1.

Highlight the Off Peak period by left clicking on it, select New.

2.

Rename your new tariff period (i.e. Partial Peak).

3.

Modify the time period by left clicking the plus sign, selecting the time period
and changing the time within the left window.

4.

You will also have to modify the time period within the On Peak and/or Off Peak
intervals to ensure that there is no overlap (i.e. if your new 'Partial Peak' period
is between 6:00 and 8:00 PM, then you will have to change your 'Off Peak' period
to 8:00 PM to End Of Day).

Changing Which Days are Holidays
1.

Select the Off Peak period.

2.

Left-click 'All Day, Canada Holidays' and select a different country from the
window on the left.

3.

Add or remove holiday dates as required.

CAUTION
Double check to make certain that there are no gaps and no overlapping date or time ranges.
The TOU schedule should not be confused with the Time of Use Module used by billing applications.

Once you have completed configuring the TOU schedule, you are ready to create
the actual Energy and Demand report.

Chapter 4 - Using ACCESS Software

Page 97

ION Setup Software

9300 Series User’s Guide

ION Setup Software
ION Setup is a software solution that allows basic configuration and control
capabilities for your power monitoring devices. ION Setup can also display realtime and diagnostic data for your networked devices.
When starting ION Setup, you have the option to enter network mode or single
device mode at the logon screen. Network mode allows you to add multiple sites
and meters to your network, organize your meters into logical groups, and
configure each site and meter individually. The single device mode, however,
allows you to connect to only one meter and make changes to its configuration or
view its data.
Refer to the documentation on you ION Setup CD or visit the Siemens website for
complete details on ION Setup.

Configuring Communications
With ION Setup, you first create one or more communication sites: the site defines
the communication method. You then add devices to a site, followed by grouping
the devices in a logical manner according to your needs (e.g. by common function
or physical location).

These are the
types of sites
available

You can group
meters from
different sites

NOTE
You must be logged on to ION Setup in network mode in order to add a site, group, or device.

Page 98

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Configuring Communications

Sites, Groups, and Meters
You can create a network of items within ION Setup so that the next time you want
to upgrade a meter’s firmware or make any configuration changes, the meter is
easy to find and your communication setup is ready.
Sites refers to a communication method. For example, you need separate sites for
Ethernet, Serial or Modem types of communication. A site can have many
connected devices. You can also have one meter that is connected to two or more
sites provided that the meter has the capability.
A group is an optional feature that lets you define a logical grouping of meters. For
example, you can have a group of meters for power quality monitoring, or you can
have a group of meters defined by location. Groups are always attached to the
System icon. Devices within each group are attached to both the group and a
communications site (sites are connected to the workstation).
You can add a meter to a communication site or a group. When you add a meter
to a group, it is automatically attached to the appropriate communication site.
However, when you delete a meter from a group, the meter remains attached to
the communication site.
Adding a Site, Group or Meter
1.

Close any open windows to return to the Network Viewer screen. Do one of
the following:
From the toolbar, click the Insert An Item button, or
From the Insert menu, choose Item, or
Right-click anywhere on the screen to display the shortcut menu, and then
click Insert Item.
The New Network Item dialog box appears (see illustration in step 2).

2.

Chapter 4 - Using ACCESS Software

Click the item (Group, Site or Meter) that you want to add. In the Attach To: box,
select where you want to attach the item.

Page 99

Configuring Communications

9300 Series User’s Guide

3.

Click OK. A dialog box for the appropriate item appears. Depending on the
item, there may be multiple tabs each with numerous options for configuration:
When you add a new site, the dialog displays three tabs: General, Timings,
and Polling. If you are adding a modem or gateway site, there is a fourth tab
labelled Remote Info.

When you add a new group, the dialog box has only one tab labelled
General. On this tab, you can change the name of your newly created group.

When you add a new meter, the dialog box displays three tabs: General,
Display, and Tools.

Page 100

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Basic Meter Configuration

Basic Meter Configuration
The Setup Assistant is a user interface that contains relevant instructions to help
guide you through common setup requirements for your ACCESS meter. After
you have added a device to ION Setup in network mode, or connected using single
device mode, the Setup Assistant appears in the right pane. Double-click the Setup
Assistant to access the setup dialog box.

The Setup Assistant is accessible in both single device mode and network mode.
The Setup Screens on the left let you access different setup tabs on the right. It is
from these setup tabs that you can configure a meter’s setup registers.
Changing a setup register
1.

Highlight the Setup Screen you want and select the desired tab where
applicable.

Important notices may be
included in the description
box. Read them carefully
before proceeding with
your configuration
changes.

Chapter 4 - Using ACCESS Software

Page 101

Displaying Data with ION Setup

9300 Series User’s Guide

2.

Highlight the setup register you want to edit in the register window.

3.

Click the Edit button.
(A window may appear, asking for the meter’s password. This only occurs for
meter’s with advanced meter security. Type the meter’s password and click
OK.)
A window appears where you can edit the register value.

Depending on the register class, you either select a value from a drop-down list
or enter the new value manually in the field provided.
4.

Make your selection from the drop-down list or enter a new value. Click OK. The
setup register changes immediately.

Displaying Data with ION Setup
You can use ION Setup to display real-time or diagnostic data from any meter that
you have added to the software.
Displaying real-time data

Page 102

1.

Select Data Screens from the View menu (or click

on the toolbar).

2.

Click the device icon from which you want to view real-time data.

3.

Double-click the icon for the screen you want to display (the screens in the right
pane of the ION Setup window).

4.

Click the desired tab to display its contents if there is more than one tab in the
display screen.

Chapter 4 - Using ACCESS Software

9300 Series User’s Guide

Displaying Data with ION Setup

Displaying diagnostics data
1.

Select a site or device icon from the left pane.

2.

Select Diagnostics from the Tools menu (or click

on the toolbar).

The Communication tab displays information about the meter’s communication
status, message information, message timing, and packet frames. Clicking the
Reset button sets all values to zero.

The General tab display information about the meter, such as the meter type, the
firmware version, serial number, communications, and available memory.

Chapter 4 - Using ACCESS Software

Page 103

Displaying Data with ION Setup

Page 104

9300 Series User’s Guide

Chapter 4 - Using ACCESS Software

5

Features and Applications
The 9300 Series meters offer a range of capabilities for enterprise energy
management applications such as feeder monitoring and submetering.
Comprehensive analog and digital I/O, multiple communication ports, industrystandard protocols, and precision time synchronization compliment the meters’
ability to integrate with your energy management and SCADA systems.

In This Chapter
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
RS-485 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Optical Port Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Internal Modem Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Profibus Connections (9300) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Internet Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
WebMeter and MeterM@il . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
WebReach . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Telnet and Hyperterminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Digital and Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Specifying a Port In an ION Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Using the Onboard Digital Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Using the Onboard Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Using the Optional Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Using the Optional Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Data and Event Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Data Logging (9330 and 9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Event Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Logging and Recording Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Meter Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Standard Meter Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Residual Current Calculation (I4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Alerting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Alerting ION Software via the Alarm Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Alerting via an Alphanumeric Pager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Alerting via a Numeric Pager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Alerting via Email (9330 and 9350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134

Communications

9300 Series User’s Guide

Communications
This section describes the meter communications media types and communications
applications. The diagram below shows the 9300 Series meter communication ports
with a brief description of how each port is used.
COM 3:
Optical serial connection

NOTE

All 9300 Series meters provide COM 3, an
optical (infrared) port. The optical port
(located on the front of the meter) is used for
serial communications, and supports these
protocols: ION, Modbus RTU, or DNP (9330
/ 9350). The port can also be used for
energy pulsing.
The meter’s internal modem
communicates to the server
computer over the telephone
network.

The Profibus meter option for the 9300 uses
special COM connections.

Ethernet connection
M

DM

COM1 COM2

All 9300 Series meters support the optional
Ethernet card. An Ethernet connection
supports ION, Modbus RTU, or Modbus/TCP
protocols.

COM 1:
RS-485 serial connection or ModemGate

COM 2:
RS-485 serial connection or EtherGate

All 9300 Series meters provide COM 1: an
RS-485 serial communications port that
supports these protocols: ION, Modbus
RTU, or DNP (9330 / 9350).
9330 and 9350 meters with an internal
modem can use the ModemGate protocol
on COM 1, allowing the meter’s internal
modem to communicate with the meter, the
WinPM.Net server computer, and any
devices that are wired to the meter’s COM 1
port.

The 9330 or 9350 meter provides COM 2.
If your meter has an Ethernet card, then
COM 2 functions as an Ethernet gateway
(EtherGate) — EtherGate transfers data
directly between an Ethernet network and
any devices that are wired to the meter’s
COM 2 port. If there is no Ethernet card,
then COM 2 functions as a serial
communications RS-485 port, and supports
ION, Modbus RTU, or DNP protocols.

The 9300 Series meter has numerous communication possibilities depending on
your ordering preferences. However, not all communications options are available
to each model. The standard meter has two or three serial communication ports:
an RS-485 port on COM 1, another RS-485 port on COM 2, and an Infrared port on
COM 3. Optional ports can include an internal modem, a 10 Base-T Ethernet
communication port, or a Profibus port. The table outlines the communication
(COM) ports for each 9300 Series meter. Information regarding Profibus —
available only on the 9300 meter - can be found in its sections.
COM 1

COM 2

COM 3

Ethernet

EtherGate

Modem

ModemGate

9300
9330
9350

Page 106

Chapter 5 - Features and Applications

9300 Series User’s Guide

RS-485 Connections

RS-485 Connections
Refer to the “Hardware Reference” chapter for the 9300 Series RS-485
specifications. The communication card is designed with optical coupling that
provides full isolation between the RS-485 communication lines and the meter
internal circuitry. This circuitry provides protection from common mode voltages
and incorrect connections. All inputs pass the ANSI/IEEE C37.90-1989 surge
withstand and fast transient tests.
The communications terminal strip on the rear of the meter shows two
communication ports: COM 1 and COM 2. (The COM 2 port is not available on the
9300.) Up to 32 devices can be connected on a single RS-485 bus. Use a good quality
shielded twisted pair cable for each RS-485 bus, AWG 22 (0.5 mm2) or larger. The
overall length of the RS-485 cable connecting all devices cannot exceed 4000 ft.
(1219 m). The RS-485 bus may be configured in straight-line or loop topologies.
Straight Line Topology
RS-485

COM

SH + -

SHLD

+

SHLD

+

SHLD

+

Termination

RT Resistor

RS-232 to
RS-485
Converter

+
-

D

L
SH

SHLD

+

SHLD

+

SHLD

+
RT

Loop Topology
RS-485

COM

SH + -

SHLD

RS-232 to
RS-485
Converter

+

SHLD

+

SHLD

+

SHLD

Termination
Block

+
-

LD

SH

SHLD

+

SHLD

+

SHLD

+

General Bus Wiring Considerations
Devices connected on the bus, including the meter, converter(s) and other
instrumentation, must be wired as follows:
The shield of each segment of the RS-485 cable must be connected to ground at
one end only.
Isolate cables as much as possible from sources of electrical noise.
Use an intermediate terminal strip to connect each device to the bus. This allows
for easy removal of a device for servicing if necessary.

Chapter 5 - Features and Applications

Page 107

Optical Port Connections

9300 Series User’s Guide

Install a ¼ Watt termination resistor (RT) between the (+) and (-) terminals of the
device at each end point of a straight-line bus. The resistor should match the
nominal impedance of the RS-485 cable (typically 120 ohms – consult the
manufacturer’s documentation for the cable’s impedance value).

CAUTION
Do not connect ground to the shield at both ends of a segment. Doing so allows ground loop currents to
flow in the shield, passing noise into the communications cable.

RS-485 Connection Methods to Avoid
Any Device connection that causes a branch in the main RS-485 bus should be
avoided. This includes star and tee (T) methods. These wiring methods cause signal
reflections that may cause interference. At any connection point on the RS-485 bus,
no more than two cables should be connected. This includes connection points on
instruments, converters, and terminal strips. Following this guideline ensures that
both star and tee connections are avoided.

Avoid
3-way “Star”
connection point

Avoid
3-way “T”
connection point

Optical Port Connections
Refer to the “Hardware Reference” chapter for the optical port specifications.
The optical (infrared) port on the meter’s front panel is compatible with an ANSI
C12.13 Type II magnetic optical communications coupler. The optical magnetic
coupler is purchased separately. Contact your supplier for a list of recommended
opto-couplers.
The optical port can communicate real-time measurements to a laptop or similar
device via ION, Modbus RTU, or DNP 3.0 (9330 and 9350). The port can also be used
for infrared energy pulsing.

Page 108

Chapter 5 - Features and Applications

9300 Series User’s Guide

Optical Port Connections

Meter Setup for Optical Port Communications
To communicate real-time measurements through the infrared port, you must
configure the Infrared Comm communications module. The Baud Rate, Unit ID,
and Protocol setup registers must properly match your system and can be set using
the meter’s front panel or ACCESS software. Once you have completed the
device’s configuration, connect the Type II compatible optical magnetic coupler to
the front panel. (The optical magnetic coupler is purchased separately.)
Configuring the Infrared Comm Module through the Front Panel
1. From the SELECT SETUP menu, choose QUICK SETUP > INFRARED COMM > IR1
PROTOCOL > INFRARED I/O.
2.

Configure the INFRARED COMM communications module Baud Rate, Unit ID, and
Protocol setup registers to match your communications system.

Configuring the Infrared Comm Module with Designer
In order to configure the Infrared Comm communications module with Designer,
you must use the Management Console to:
Add the meter (that will be used for optical port communications) to your
WinPM.Net system.
Add a direct (serial) site with the RtsCts disabled.
Launch Designer and configure the Infrared Comm communications module
settings.
Adding a Meter and Direct (Serial) Site to your WinPM.Net Network
In the Management Console, add the meter that you will use for optical
communications and a direct site to your WinPM.Net network. Describe how your
serial device is wired and other communications information on the options
screens.
On the Direct Site Options screen:
Select the server computer that will communicate with the serial device.
Select the server computer serial port where the optical coupler is connected.
Disable RtsCts.
Server computer that
communicates with the
remote modem
Port on the server computer
where the optical coupler is
connected
RtsCts disabled for
Infrared communications.

Configuring the Infrared Comm Communications Module in Designer
Launch Designer and configure the Infrared Comm communications module Baud
Rate, Unit ID, and Protocol setup registers to match your communications system.

Chapter 5 - Features and Applications

Page 109

Ethernet Connections

9300 Series User’s Guide

Optical Port Setup for Energy Pulsing
To configure the optical (infrared) port for energy pulsing, you must set the
Infrared Comm communications module Protocol register to INFRARED I/O. Use the
meter’s front panel or ACCESS software to set the IR pulsing.
Setting the IR Pulsing using the Front Panel
1.

From the SELECT SETUP menu, choose QUICK SETUP > INFRARED COMM > IR1
PROTOCOL > INFRARED I/O.

2.

Choose SELECT SETUP > ADV METER SETUP > CALIBRATION PULSER MODULES.

3.

Select the module you wish to use for pulsing (kWh Pulse, for example).

4.

Choose the Port setup register from the menu provided, then select IR LED.

Setting the IR Pulsing using Designer
1.

Set the Infrared Comm communications module’s Protocol setup register to
I/O.

INFRARED

2.

Send and Save the configuration change to the device.

3.

Set the Port setting of any Pulser module to IR LED.

4.

Send and Save.

NOTE
In order to use the optical port for energy pulsing, it cannot be used for communications at the same time.

Ethernet Connections
Refer to the “Hardware Reference” chapter for the Ethernet port specifications.

Etherne

t

10Base-T Ethernet connections are made via the RJ45 modular port on the left side
of the unit. Use high quality Category 3 or 5 UTP (CAT 5 unshielded twisted pair
recommended) cable with a male RJ45 modular connector for connection to the
10Base-T port. The meter’s optional 10Base-T Ethernet port is capable of data rates
up to 10Mbps, and supports ION, Modbus RTU, and Modbus/TCP protocols.
The meter supports a single connection at a time to one of these three IP Service
Ports: ION, Modbus/TCP, or Modbus RTU. WebMeter is accessible at the same
time, as are connections to Ethergate and MeterM@il as long as these features are
available on your meter.

Page 110

Chapter 5 - Features and Applications

9300 Series User’s Guide

Ethernet Connections

Meter Setup for Ethernet Communications
To enable communications through the meter’s Ethernet port, you must configure
the Ethernet communications module. The IP Address, Subnet Mask, Gateway,
SMTP Server and SMTP Connection Timeout setup registers must properly match
your system and can be set through the meter’s front panel, or with Designer
software.
Configuring the Ethernet Module through the Front Panel
1.

From the SELECT SETUP menu, choose QUICK SETUP > ETHERNET.

2.

Configure the ETHERNET communications module IP Address, Subnet Mask,
Gateway, SMTP Server and SMTP Connection Timeout setup registers to match
your communications system.

Configuring the Ethernet Module via Designer
After you have wired your meter to the Ethernet network and performed basic
setup, add the meter to your WinPM.Net network using the Management Console.
(It is not necessary/possible to add an Ethernet site.)
Adding an Ethernet Device to your WinPM.Net Network
In the Management Console, the Ethernet Device Options screen appears when you
add an Ethernet device (meter). Use this screen to describe your meter Ethernet
address and other communications information. Be sure to include:
The server computer that will communicate with the Ethernet device.
The Ethernet device TCP/IP address.

Meter TCP/IP Address
Server computer that
communicates with the
Ethernet device

Configuring the Ethernet Communications Module in Designer
To enable communications through the Ethernet port, you must configure the
Ethernet communications module. Launch Designer and configure the IP Address,
Subnet Mask, Gateway, SMTP Server and SMTP Connection Timeout registers to
match your system.

Chapter 5 - Features and Applications

Page 111

Ethernet Connections

9300 Series User’s Guide

The EtherGate Protocol
EtherGate is a powerful communications tool that lets you communicate to a meter
and through a meter simultaneously. When a meter installed on the Ethernet
network has EtherGate enabled, a master device (such as a workstation running
ION Enterprise software) can communicate to the meter, as well as through the
meter to a serial network of devices wired to the meter’s COM 2 port.
EtherGate is only available for the 9330 and 9350 meters, and it is only configurable
on the COM 2 port. (Port 7802 is used for EtherGate communications.)

9330 or 9350
with Ethernet
Port

EtherGate connections do
not connect a workstation
with WinPM.Net (or other
master device) to COM 2

Workstation with
WinPM.Net is located on
the Ethernet LAN

Ethern

et

Each device on the RS-485
loop must have a unique
Unit ID and operate at the
same baud rate.

Once you have the chain of serial devices installed, use Designer or the meter’s
front panel to change the COM 1 or COM 2 Protocol setting to EtherGate. The
transfer of data between protocols is then handled automatically.
The Devices list in the Management Console appears as follows:
The devices that reside on the RS-485
loop connected to the 9350.

The 9350 appears in the
Devices list, because it
must be configured as an
Ethernet device before you
can configure it as an
Ethernet Gateway Site.
The Gateway Site - set the IP Service Port to
7802 for COM 2. The number following the
IP Service Port number is the device’s unique
Unit ID.
From the Type heading in the
Sites window, you can see the
9350 has been configured as
an Ethernet Gateway Site.

Refer to the EtherGate technical note for complete details on configuring your
meter for EtherGate.

Page 112

Chapter 5 - Features and Applications

9300 Series User’s Guide

Internal Modem Connections

Internal Modem Connections
This option is only available on the 9330 and 9350 meters.
Refer to the “Hardware Reference” chapter for internal modem specifications.

Teleph
o

ne Ne
twor

k

Connection to the internal modem is made via the RJ-11 jack, or two captured wire
connectors, located on the right side of the meter. Connect the meter to the
telephone network with an FCC Part 68 compliant telephone cord (that has two
male RJ-11 plugs). If you have the captured wire connector option, connect the
meter to the telephone system with the (bare wire to RJ-11) cable provided. If you
have the CTR-21 compliant internal modem option, you may also require an
adaptor to interface with your regional telephone jack.
The meter with an internal modem uses the modem to communicate to a master
device (e.g. server computer with WinPM.Net software) over the telephone
network.

Meter Setup for Modem Communications
To enable communications through the meter’s internal modem, you must
configure the Comm 1 Communications module. The Baud Rate, Unit ID, and
Protocol setup registers must properly match your system, and the initialization
string for the internal modem must be set up using the ModemInit register.

ModemInit Setup Register
The ModemInit string register defines the initialization string for the internal
modem, with a maximum of 47 characters.
Edit the ModemInit register and enter the initialization string desired. The string is
sent to the modem as soon as you download the COM 1 module. Note that the
string is also sent to the modem whenever the meter is powered up, or whenever
the baud rate in the Comm 1 Communications module is changed.
Any changes to the Modem Init or Baud Rate setup registers while the modem is
online will cause the modem to disconnect from the phone line.

Chapter 5 - Features and Applications

Page 113

Internal Modem Connections

9300 Series User’s Guide

Modem Initialization String Examples
The modem supports various commands in the initialization string. The examples
below are for use when the modem is used to receive incoming calls.
1.

Enter the following string to force the modem to use the 1200 bps Bell 212A
quick-connect (this ensures the modem will answer incoming calls and
connect within nine seconds):
AT&F0 +MS=69,0,1200,1200 \N0 S0=1

2.

This string will set the modem back to its default state of connecting with the
fastest possible baud rate between modems:
AT&F0 S0=1

For any initialization string, it is recommended that the &F0 be at the beginning of
the string.
After the meter is installed, and the internal modem is connected to the telephone
network, the Comm 1 module can be configured; use the meter’s front panel or
with Designer software. To learn how to connect the internal modem to the
telephone network, consult your meter’s Basic Setup and Installation Instructions.

NOTE
To learn what AT Commands are compatible with your meter, consult the technical note Modem AT

Commands.

Configuring the Comm 1 Module through the Front Panel
1.

From the SELECT SETUP menu, choose QUICK SETUP > COMM 1.

2.

Configure the COMM 1 communications module Baud Rate, Unit ID, and Protocol
setup registers to match your communications system.

3.

Configure the initialization string for the internal modem using the ModemInit
register. Refer to “ModemInit Setup Register” on page 113.

Configuring the Comm 1 Module via Designer
Before you can configure the Comm 1 module in Designer you must add the meter
(with the internal modem) and a modem site to your WinPM.Net network.
Adding a Meter and a Modem Site to your WinPM.Net Network
In the Management Console, add the meter with the internal modem, and a
modem site to your WinPM.Net network. Describe how your remote modem is
wired and other communications information on the options screens.
On the Modem Site Options screen, be sure to include:
The server computer that will communicate with the remote modem.
Either before or after adding the Modem Site, you must add a dialout modem
to the server computer. The server computer dialout modem communicates to
the modem at the modem site. Refer to the WinPM.Net Getting Started guide to
learn how to add a dialout modem.
The remote modem telephone number.

Page 114

Chapter 5 - Features and Applications

9300 Series User’s Guide

Internal Modem Connections

Remote modem telephone
number
Server computer that
communicates with the
remote modem. Ensure that
the server computer dialout
modem is configured.

Configuring the Comm 1 Communications Module in Designer
Launch Designer, and configure the Comm 1 communications module Baud Rate,
Unit ID, and Protocol setup registers to match your communications system.
Configure the initialization string for the internal modem using the ModemInit
register. Refer to “ModemInit Setup Register” on page 113.

The ModemGate Protocol
The ModemGate feature creates a communications connection between the
telephone network and an RS-485 serial network of devices (loop or straight-line
topology). When you specify the protocol for the meter’s COM 1 port as
MODEMGATE, all data received by the meter’s internal modem is automatically
transferred to the serial network.
ModemGate is only available for the 9330 and 9350 meters, and it is only
configurable on the COM 1 port.

Workstation with
WinPM.Net and
modem

Teleph
o

ne Ne
two

rk

Meter with an
internal modem.
The serial network
is connected to
COM 1.

Each device on the RS-485 loop,
including the gateway meter’s internal
modem, must have a unique Unit ID
number.
All serial devices must operate at the
same baud rate as the gateway meter.

Chapter 5 - Features and Applications

Page 115

Profibus Connections (9300)

9300 Series User’s Guide

Wire an RS-485 connection between one or more meters and COM 1 of the
9330 or 9350 meter according to the wiring guidelines presented in the Installation
and Basic Setup Guide.

The 9350 with internal modem

The RS-485 device network
connected to the meter with
the internal modem.
The same RS-485 serial
protocol must be selected
for connections to multiple
devices along the same bus.

The Modem Site

Refer to the ModemGate technical note for complete details on configuring your
meter for ModemGate.

Profibus Connections (9300)
NOTE
The Profibus Master file (.GSD file) is included on a floppy disk with the meter. This file must be installed
on your Profibus Masters before the meter can communicate with the Profibus network.

The optional Profibus port on the meter is capable of operating baud rates up to 12
Mbps. Profibus Connections to the meter are made via the nine-pin connector on
the rear of the unit. Plug your Profibus connector from the network into this
connector.

Profibus Female Connector
(located on meter)
5

1

9

Page 116

6

Pin Number

Profibus Function

1

N/A

2

N/A

3

B-line

4

RTS

5

Isolated GND

6

Isolated Vcc

7

N/A

8

A-line

9

N/A

Chapter 5 - Features and Applications

9300 Series User’s Guide

Internet Connectivity

Internet Connectivity
ACCESS meters provide Internet connectivity so you can receive meter emails, view
realtime data, and configure your system through a web browser from anywhere in
the world. Your ACCESS meter provides the following internet connectivity
options:
MeterM@il® feature (receive data logs and email alerts from the meter)
WebMeter® feature (onboard web server allows you to view real-time data and
configure the meter through a web browser)
WebReach (view WinPM.Net system information through a web browser)

WebMeter and MeterM@il
The WebMeter feature provides real-time data display and system configuration
of a meter over the Internet. The MeterM@il feature lets meters automatically
transmit data by email to anyone, anytime, anywhere.
All 9300 Series meters provide WebMeter capability. 9330 and 9350 meters also
support MeterM@il. The table below illustrates the features supported by different
9300 Series meters. The following sections provide WebMeter and MeterM@il
details.
WebMeter

Datalog Email

Email Alerts

9300
9330
9350

NOTE
To enable WebMeter and MeterM@il features, the meter must have firmware v271 or later and an
Ethernet card with firmware ETH73v271 or later. Firmware can be downloaded from
www.sea.siemens.com. Refer to the technical note Upgrading ION Device Firmware to learn how to
upgrade device firmware.

ACCESS WebMeter Feature
WebMeter-enabled meters have an on-board web server. Built-in web pages
display certain energy and basic power quality information and also support basic
meter configuration tasks. A meter with the WebMeter feature can be connected to
your corporate Ethernet network like any other network device, and you can
access it with a standard web browser like Internet Explorer.
Refer to the technical note WebMeter Internal Web Server Feature to learn how to:
view your WebMeter data on the Internet
configure your WebMeter-enabled meter

Chapter 5 - Features and Applications

Page 117

WebReach

9300 Series User’s Guide

set up your network for the WebMeter feature
enable/disable web browser configuration of the meter (for 9300 Series meters,
web browser configuration of the meter is enabled by default)

ACCESS MeterM@il Feature (9330 and 9350)
The MeterM@il feature allows your meter to send data logs as email attachments
to a workstation, pager, cell phone, or PDA. In addition to the log export function,
your meter can send email alerts.
Refer to the technical note ACCESS MeterM@il Internal Email Server Feature to learn
how to:
view MeterM@il data
set up your network for the MeterM@il feature
configure your meter to use the MeterM@il feature
set up the meter for your SMTP Server
set up the MeterM@il feature to send alerts
set up the MeterM@il feature to send data logs

WebReach
WebReach allows you to remotely view WinPM.Net information through a web
browser. WebReach requires a simple URL and no client machine configuration so
you have the flexibility to view your data from a web browser anywhere in the
world. With WebReach, you can view real-time data and select views of historical/
waveform data. Currently, no configuration or control functions are available
through WebReach. Refer to the online WinPM.Net Help for more details on
WebReach.

Telnet and Hyperterminal
You can access certain Ethernet settings and statistics through a telnet application
such as Microsoft Telnet. Similarly, you can use Windows HyperTerminal to access
certain meter module settings. Use the following guidelines to determine which
application you should use to access your meter:
If your meter is connected to an Ethernet network, use a telnet application such
as Microsoft Telnet.
If your meter is connected serially or through a modem to your workstation, use
a terminal application such as Windows HyperTerminal.
You can access certain Power Meter module and Factory module settings from
both a Telnet session and HyperTerminal session. Both sessions also let you
configure Factory module setup registers for Current Probe Input applications.
Additionally, a Telnet session lets you view ethernet statistics and access certain
Ethernet communications module settings.

Page 118

Chapter 5 - Features and Applications

9300 Series User’s Guide

Telnet and Hyperterminal

Refer to the technical note Telnet and HyperTerminal Access for the appropriate
application’s menu options and connection instructions.

Chapter 5 - Features and Applications

Page 119

Digital and Analog I/O

9300 Series User’s Guide

Digital and Analog I/O
Digital and analog I/O ports on ION meters let you bring a variety of data into a
common system, thereby simplifying data gathering. The 9300 Series offers
numerous digital and analog I/O combinations.
All series meters provide four digital (relay) output ports, one infrared data port,
and one configurable LED output. The digital outputs are used as status outputs
or for relay control. The infrared port can be used as a communications port, or it
can be configured as a digital output for energy pulsing applications. The LED (L1)
is used for energy pulsing. The 9330 and the 9350 meters also provide four digital
(status) inputs. These optically isolated digital inputs can monitor status, count
transducer pulses, breaker trips and pulses from any external "volts free" dry
contact.

NOTE
The LED (L1) is preconfigured for kWh pulsing, but it can be easily reconfigured to perform kVAh pulsing,
kVARh pulsing or any other digital output function.

There is also an analog I/O option - four analog inputs and four analog outputs that can be specified for any 9300 Series meter. These allow you to monitor a wide
range of conditions, such as device cycles (RPM), flow rates, fuel levels, oil
pressures and transformer temperatures. You can output energy pulses to an RTU
or perform equipment control operations.
An optional external relay board (the REB option) is available with four external
relays that connect to the onboard digital outputs. Several different types of digital
output devices are available for use with the external relay board; refer to
www.sea.siemens.com for the External I/O Output Device Part Summary.
Refer to the technical note Digital and Analog I/O for more information regarding
digital and analog inputs and outputs than is provided in this User’s Guide.

Specifying a Port In an ION Module
The Digital Output, Digital Input (9330 and 9350), Analog Output, Analog Input,
Pulser, and Calibration Pulser modules have Port setup registers that allow you to
specify which port handles the outgoing or incoming signals. To assign a port to
one of these modules, simply modify the Port setup register by picking a port from
the enumerated list. This can be done with both Designer and ION Setup.
Be aware that the enumerated list only displays those ports that are not yet
assigned to another module. For example, the meter’s default configuration has
port L1 assigned to Calibration Pulser module “kWh imp LED.” If you create a
new Calibration module and modify its Port setup register, port L1 does not
appear in the list of available ports. To make a port available, you must locate the
module controlling it and set the module’s Port setup register to NOT USED (or
delete the module entirely). The port now appears in the list of available ports.

Page 120

Chapter 5 - Features and Applications

9300 Series User’s Guide

Specifying a Port In an ION Module

NOTE
The IR LED capability is not available until you set the IR1 PROTOCOL register in the IR Comm module to
INFRARED I/O.

The following table describes the ports that can be configured (in the Digital
Output, Pulser, Digital Input, Analog Input, Analog Output, and Calibration
Pulser modules) to handle outgoing or incoming signals.
All 9300 Series meters (9300, 9330 and 9350) have these digital output ports and
optional analog input/output ports
Output Port Names

Description

Port D1

Digital Output port 1

Port D2

Digital Output port 2

Port D3

Digital Output port 3

Port D4

Digital Output port 4

L1

LED Output

IR LED

Infrared LED Output

Port AO1

Analog Output port 1

Port AO2

Analog Output port 2

Port AO3

Analog Output port 3

Port AO4

Analog Output port 4

Input Port Names

Description

Port AI1

Analog Input port 1

Port AI2

Analog Input port 2

Port AI3

Analog Input port 3

Port AI4

Analog Input port 4

9330 and 9350 meters also include the following digital (status) input ports

Chapter 5 - Features and Applications

Input Port Names

Description

Port S1

Status Input port 1

Port S2

Status Input port 2

Port S3

Status Input port 3

Port S4

Status Input port 4

Page 121

Using the Onboard Digital Outputs

9300 Series User’s Guide

Using the Onboard Digital Outputs
The four digital output ports are located on the rear of the meter. ION Digital
Output, Calibration Pulser, or Pulser modules control the function of the digital
output ports. These modules define the characteristics of outgoing signals and can
act as intermediaries between the hardware port and the other modules in the
meter. Digital Output ports can be used to control relays or send status signals.
You configure Digital Output, Calibration Pulser, and Pulser modules by
specifying to which hardware port they send signals. You are also responsible for
the settings that define the type of pulses the modules send. Once you have
configured the modules, they can be controlled by other ION modules that
provide trigger outputs.
The following table summarizes the settings for these modules.
ION Module

Calibration Pulser
Module

Digital
Output
Module

Pulser Module

Setup Registers

Available Settings

Default

Description

Port

D1 to D4 or NOT USED

NOT USED

Specifies the output hardware channel

Pulse Width

numeric

0.05

Pulse Width, in seconds

Kt

0.01 to 1 x 109

1.8 Wh

Specifies Watts per pulse

Output Mode

Pulse, KYZ

Pulse

Sets the type of output

Int Mode

Forward, Reverse, Absolute, Net

Forward

Specifies the integration

Port

As above

NOT USED

See above

Pulse Width

numeric

0

Pulse Width, in seconds
(set to 0 for continuous pulse)

Polarity

Fixed at NON-INVERTING

NON-Inverting

Specifies non-inverted pulse

EvLog Mode

LOG ON or LOG OFF

LOG OFF

Specifies to store state changes in the
Event Log

Port

As above

NOT USED

See above

PulseWidth

numeric

1

Pulse width, in seconds

OutputMode

PULSE or KYZ

PULSE

Specifies full pulse or KYZ

Polarity

Fixed at NON-INVERTING

NON-Inverting

Specifies non-inverted pulse

NOTE
Remember that if the port you want to use does not appear in the Port setup register’s list, then that port
is in use by another module. You must edit the Port setup register of the module using the port, setting it
to NOT USED, if you want the port to be available to other modules.

Page 122

Chapter 5 - Features and Applications

9300 Series User’s Guide

Using the Onboard Digital Outputs

Energy Pulsing
Five Calibration Pulser modules are preconfigured at the factory for energy
pulsing applications. One of these modules is programmed to send kWh pulses to
the LED on the back of the meter. The remaining four (configured for imported/
exported kWh and kVARh pulsing) can be configured to send energy pulses to any
digital output port. Edit the appropriate Calibration Pulser or Pulser module’s Port
setup register, and set it to the port you want to send the signal through (D1, D2,
D3 or D4, or IR1).

LED Energy Pulsing
The LED port (L1) controls the LED on the back of the meter. This port is used for
kWh pulsing by default; LED 1 on the back of the meter pulses every 1.8 Wh. If you
wish to configure the LED for other energy pulsing applications (i.e. kVAh, kVARh),
you must first disable the default kWh pulsing. Use the front panel to disable kWh
pulsing as follows:
1.

From the SELECT SETUP menu, choose ADV METER SETUP > CALIBRATION
PULSER MODULES > KWH IMP LED, and highlight the Port setup register and
press the round button.

2.

From the list of available ports, select NOT USED.

These steps remove control of the L1 LED from the kWh IMP LED module. You
can also disable the kWh pulsing using Designer. Select the kWh imp LED
Calibration Pulser module and disable L1 by setting the Port setup register to NOT
USED.
Configuring Other Energy Pulsing Applications
Now that you have the L1 port free to assign a pulse to, you can assign other Pulser,
Digital Output, or Calibration Pulser modules to it. Using the front panel, assign a
Pulser module as follows:
1.

From SELECT SETUP choose ADV METER SETUP, then select the new module type
and the module you wish to use for pulsing the LED.

2.

Scroll down and select the Port (e.g. PU2) setup register, then choose L1.

You can also configure LED energy pulsing from Designer. Select the Digital
Output, Pulser, or Calibration Pulser module you wish to use and set its Port setup
register to L1.

Using the Relay Expansion Board (REB Option)
The REB option (Relay Expansion Board) allows for custom digital output
applications using specific Grayhill relay units. The REB option provides four slots
where you can plug Grayhill digital output hardware modules. There are nine
Grayhill hardware modules of varying functionality available. The relays are
purchased separately.
As with onboard digital outputs, the Pulser, Calibration Pulser, and Digital Output
modules can be used to control the functions of the external relays. Set the
module’s Port setup register to the digital output port (D1 to D4) that the relay is
connected to.

Chapter 5 - Features and Applications

Page 123

Using the Onboard Digital Inputs

9300 Series User’s Guide

Using the Onboard Digital Inputs
The 9330 and the 9350 meters’ four onboard digital (status) inputs can be used for
monitoring external contacts or pulse counting applications. These inputs can be
used for dry contact sensing, but they cannot be used for voltage sensing
applications.
The function of each digital input is controlled by the Digital Input modules S1
through S4. These modules are preconfigured at the factory, together with four
Counter modules for counting status changes, and an External Pulse module for
resetting the Counter modules.
The four Digital Input modules are factory configured as follows (refer to the
online ION Programmer’s Reference for complete details on module function):
Setup Register

Factory Setting

Input Mode

Pulse (complete pulse as opposed to KYZ transition pulse)

Event Log Mode

Log Off (status changes are not logged)

Polarity

Inverting (hardware signal is inverted)

Debounce

0.010 (mechanical contact bounce, in seconds)

Port

S1 to S4 (specifies which hardware port the module controls)

Once you have connected the status inputs to the field equipment they are going
to monitor, check the meter’s Digital Input modules to ensure they are configured
appropriately.

Using the Optional Analog Inputs
The four optional Analog Input ports allow you to monitor a wide range of
conditions, such as device cycles (RPM), flow rates, fuel levels, oil pressures and
transformer temperatures. Both types of Analog Inputs (either 0-20mA or 0-1mA)
are suitable for monitoring DC signals from transducers in your system. Analog
Input modules control the analog input ports.
You use Designer to create and configure Analog Input modules. Set the Analog
Input module’s Port setup register to the appropriate analog input port on the rear
of the meter. Link the Analog Input module’s ScaledValu output to another module
or framework for analysis.

NOTE
Your meter’s default template may already have a framework of pre-configured Analog Input and Analog
Output modules.

Page 124

Chapter 5 - Features and Applications

9300 Series User’s Guide

Using the Optional Analog Outputs

The settings for Analog Input modules are as follows:

1

Setup
Registers

Available Settings

Creation
Default

Description

Port

Not Used
I/O Exp AI1 to
I/O Exp AI4

Not Used

The input hardware channel

Full Scale

-1 x 109 to 1 x 109

1

Defines what value appears in the ScaledValu
output register when the highest possible value
from the hardware is applied

Zero Scale 1

-1 x 109 to 1 x 109

0

Defines what value appears in the ScaledValu
output register when the lowest possible value
from the hardware is applied

An arbitrary input value can be treated as the Zero Scale (i.e. a 4-20mA input is capable of generating
a 0 to X output).

Using the Optional Analog Outputs
The four optional Analog Output ports can output energy pulses to an RTU or
perform equipment control operations. Both types of Analog Output (either 020mA or 0-1mA) can deliver a continuous DC signal. Analog Output modules
control these hardware ports.
You use ION Designer to create and configure these ION modules. Create an
Analog Output module for each output port you are going to use, and link their
Source input to a value you want to reflect through the analog outputs. Alter the
setup registers as required:
Setup
Registers

Available Settings

Creation
Default

Description

Port

Not Used
I/O AO1 to
I/O AO4 inclusive

Not Used

The output hardware channel

Full Scale

-1 x 109 to 1 x 109

1

Defines what value appears in the ScaledValu
output register when the highest possible value
from the hardware is applied

Zero Scale

-1 x 109 to 1 x 109

0

Defines what value appears in the ScaledValu
output register when the lowest possible value
from the hardware is applied

Setting Zero Scale for 4 to 20mA Outputs
If you want your 9300 meter’s 0 to 20 mA analog output ports to operate as 4 to 20
mA outputs (i.e. delivers a 4 mA current with a zero Source input value to the
Analog Output module), use the following formula:
Zero Scale = - 0.25 * Full Scale
For example, with a Full Scale value of 100, your Zero Scale setting would be -25.

Chapter 5 - Features and Applications

Page 125

Data and Event Logging

9300 Series User’s Guide

Data and Event Logging
The meter includes powerful data logging (9330 and 9350 meters only) and event
recording capabilities. Data and event logs recorded by the meter are prioritized
and stored onboard. Data is retrieved periodically by the WinPM.Net software Log
Server (or other third party application).
If you use WinPM.Net software, all retrieved data from your system is stored in an
ODBC-compliant database. The information in the database can be viewed and
analyzed using WinPM.Net software applications such as Vista (for viewing), or
Reporter (for organizing and presenting data).

Data Logging (9330 and 9350)
The standard configuration of the meter includes data recorders that log various
power system data such as energy and demand, or the average power system
quantity used over a period of time (Historic Mean Log). The 9350 also logs sags
and swells in voltage.
Reporting
The Data Recorder module labeled EGY DMD LOG is configured to provide power
system data for Reporter software to create reports from the device’s logs. If any
input links to this module are changed, Reporter will not be able to create reports.
If you use the Reporter software, do not change the parameters that are logged in
the Egy Dmd Log.
Revenue Logging
For the revenue meter option, Data Recorder #1 is locked, so channels must be
specified prior to the meter being sealed. Refer to RMICAN Ordering Sheet on our
website for your particular meter.

NOTE
For compatibility with the UTS MV-90 billing software, Data Recorder #1 must be configured as a 16channel recorder.

To learn more about the data recorder modules in your meter, refer to ION Device
Templates at www.sea.siemens.com. ION Device Templates located at
www.sea.siemens.com lists all of the ION modules available in the current version
of your meter, and the total number of each module. ION Device Templates also
shows the ranges or options available for each module’s setup registers.

Changing Parameters that are Logged
The factory-configured meter logs a comprehensive set of parameters. Adding or
deleting log parameters is an advanced procedure that requires changing links
between modules using Designer software.
Once you are comfortable editing module links, change logged parameters by
linking the output registers you want logged to the inputs of an ION Data
Recorder module.

Page 126

Chapter 5 - Features and Applications

9300 Series User’s Guide

Event Logging

Event Logging
Events produced by the various ION modules in the meter are prioritized and
grouped to facilitate custom logging. Each event has a priority group number
assigned to it, based on its type and severity.

ION Event Priority Groups
Some event groups are preset with a Priority Number as shown in the table below.
You can also define your own priority number for some modules. Priority
numbers from 128-191 appear in the global even log viewer in WinPM.Net
software. Priority numbers from 192-255 are logged, initiate a beep and cause the
window to flash. You can customize these responses to display messages or
perform netsend messages, for example.
The Event Log Controller module allows you to set a priority cutoff for event
logging. Any events with a priority number greater than the cutoff value are
logged, and events with lower priorities are discarded. Refer to the individual
module descriptions and the Event Log Controller module description in the
online ION Programmer’s Reference for more details.
Event Group

Description

Priority
Number

Reset

Module reset or resynchronized

5

Setup Change

Module setup changes

10

Input Register Change

Inputs of certain modules change value

15

I/O State Change

I/O state changes (i.e. relay closes)

20

Information

Module produces important user information

25

Warning

Module produces a warning

30

Failure

A failure has occurred

255

External ION Events
Some events are not produced by a specific module; they are generated internally
by the meter. These events and their associated priority levels are as follows:.
Event Group

Description

Priority
Number

Warning

Factory initialize performed

30

Firmware upgrade performed
Memory upgrade performed
Device power-up
Device power-down
Failure

Chapter 5 - Features and Applications

Communications fail to allocate required memory

255

Page 127

Logging and Recording Capacity

9300 Series User’s Guide

Logging and Recording Capacity
Data and Event Logging (9330 and 9350)
The standard memory capacity for both meters is 304 kilobytes of non-volatile
memory. This is enough memory to log 16 parameters every 15 minutes for 30 days.
However, by default the meter is set for a log depth of 930, which is enough for 9
days. Use the following equation to help determine different variations on this
example:
each record consumes = ((number of parameters * 6) + 8)

Waveform Recording (9350)
The meter can simultaneously capture events on all channels to a maximum of 48
cycles each. To calculate the waveform memory usage use the following formula:
waveform memory usage = (2*(number of samples per cycle) + 10)*(number of
cycles in waveform) + 30
See the following table.

1

Format

Memory Usage

Page Usage

16 x 22

1024 x M1

1xM

16 x 48

2048 x M

2xM

16 x 72

3072 x M

3xM

16 x 96

4096 x M

4xM

32 x 12

1024 x M

1xM

32 x 26

2048 x M

2xM

32 x 40

3072 x M

3xM

32 x 54

4096 x M

4xM

64 x 14

2048 x M

2xM

64 x 28

4096 x M

4xM

128 x 14

4096 x M

4xM

M = Recorder depth

NOTE
Round up to the next kilobyte (1024 bytes) after each of the above calculations.

Page 128

Chapter 5 - Features and Applications

9300 Series User’s Guide

Time Synchronization

Time Synchronization
Time synchronization lets you synchronize the internal clocks of all networked
meters and devices. Once synchronized, all data logs have timestamps that are
relative to a uniform time base. This allows you to achieve precise sequence-ofevents and power quality analyses. To synchronize clocks, use ACCESS software
to broadcast time signals across the network.
Refer to the technical note Time Synchronization and Timekeeping for more
information on implementing time synchronization for your system.
Enabling or Customizing Time Synchronization
1.

Launch the Management Console.

2.

From the System Setup Pane, select Sites or Devices.
Select Sites if you want to customize a particular serial, modem, or Ethernet
Gateway site.
Select Devices if you want to customize an individual Ethernet device.

3.

Right-click in the main window and select Properties.

4.

Right-click inside the display window and select Advanced Properties.

The fields for enabling or customizing time synchronization are shown below.

These fields appear in
the Devices Advanced
Properties screen for
Ethernet devices. Serial
devices are configured
via the Serial Site
advanced properties.

Use these fields on the Site Advanced
Properties screen to enable time
synchronization or set custom
intervals for any device in any Serial
Site or Ethernet Gateway Site.

The Property Description area explains the purpose for each field. The default time
synchronization interval of 3,600 seconds (displayed in milliseconds) is acceptable
for most ION installations.

NOTE
You need appropriate permissions to configure the meters on your network. Refer to the technical note
ION Security for details on software and meter security.

Chapter 5 - Features and Applications

Page 129

Meter Security

9300 Series User’s Guide

Meter Security
The meter’s security settings allow you to configure the meter through the front
panel, with ACCESS software, or with the optional embedded web server.
Standard meter security
Anytime you make configuration changes to your meter, either through the front
panel or with ION software, you must enter a password.
Anti-tamper sealing
Your revenue meter can be protected by anti-tamper sealing.
Software security
ACCESS software security brings access-level security to the meter. With ACCESS
software, you can configure multiple users with different passwords and specify
access rights. For example, one user may have view-only rights, while another user
may have meter configuration rights. ACCESS software security only applies to
users who are accessing the meter via ION software.
For more information on meter security, refer to the ION Security technical note in
Appendix A.

Standard Meter Security
Standard meter security lets you configure the meter through the front panel or
with communications software using a meter password.
This section describes password security options available from the front panel of
the meter. Step-by-step instructions are given to help you enter, or change the
meter password and disable (enable) the password security check on the front
panel of the meter.

Entering the Password through the Front Panel
The first time you make a change to any setting you are presented with the
Password display. The factory configured password is zero (0). The password
prevents unauthorized tampering with your meter’s configuration. Depending on
site security, you may want to modify the user password from the default to
protect your configuration. The default password is “00000” and can be set to a
maximum numeric value of 60000.

Page 130

Chapter 5 - Features and Applications

9300 Series User’s Guide

Residual Current Calculation (I4)

Changing the Meter Password
1.

Select SECURITY from the Setup menu.

2.

You will see that the screen displays 00000. Enter the current password. If you
have not previously changed your password, the default is 00000.

3.

Choose MODIFY PASSWORD to alter your password (the FACTORY USE ONLY
option is for factory purposes and is not accessible).

4.

Enter your new numeric password.
To change the value of the highlighted digit use the Up and Down arrow
buttons.
To change the position of the cursor one space to the left, hold the Up arrow
button for about one second.
To change the position of the cursor one space to the right, hold the Down
arrow button for about one second.

5.

Select YES to accept your new password. You will be returned to the Setup
menu.

Residual Current Calculation (I4)
The Power Meter module provides an output register labeled “I4” which holds the
residual current value, derived from the three phase current measurements. As
such, I4 represents the ground fault current, or the current flow in the neutral or
ground conductor.
This quantity is only available when the meter's Volts Mode is set to 4-WIRE WYE. If
the Power Meter module is set to any other Volts Mode, the I4 output will read NOT
AVAILABLE.

Chapter 5 - Features and Applications

Page 131

Alerting

9300 Series User’s Guide

Alerting
The purpose of an ION alert system is to send an email or to contact a modem, fax,
pager, or software in the event of a user-specified condition. These conditions can
be changes in relays or power quality problems including surges, sags, swells and
outages. With ION alarm notification, you can automatically advise key people of
problems allowing quick remedial action, or notify ACCESS software so logs can
be uploaded from the site that initiated the alert.
The Alert module sends an alert whenever its Trigger input is pulsed. You can
connect this input to any module that produces a pulse output. You can use
modules that monitor alarm conditions such as changes in relay status and power
quality problems. For example, you can connect the Trigger input to the output of
a Setpoint module, thereby allowing the Alert module to send an alert when the
setpoint condition is reached.
The Alert module delivers these types of alerts:
Numeric Pager
Alphanumeric Pager
PEGASYS (for alerts to PEGASYS software)
ION Alert (for alerts to WinPM.Net software)
ASCII
Email
Selection between modes is made with the Alert module Alert Type setup register.
The Alert module requires access to either a modem (a dedicated modem or a
modem handling a loop of meters) or Ethernet (for the Alert module email
capabilities).
Alerting is briefly described in the following section. For detailed information
about alerting, including how to build a framework to send alerts, refer to the Alert
module description in the online ION Programmer’s Reference.

Alerting ION Software via the Alarm Server
NOTE
For detailed information about sending alerts to WinPM.Net software via the Alarm Server, refer to the
WinPM.Net online help.

The Alarm Server can run on any ACCESS software Primary or Secondary server.
The server computer should have a dedicated phone line and modem. Modems at
remote sites are programmed to dial the server's phone number when a priority
event occurs. The Alarm Server monitors the phone line and waits for the remote
sites to annunciate events. The most common use of the Alarm Server is to handle
Remote Site Event Notification.

Page 132

Chapter 5 - Features and Applications

9300 Series User’s Guide

Alerting ION Software via the Alarm Server

Remote Site Event Notification
Server or LAN

Dedicated Alarm
Server Modem

Alarm Server.exe

Connection
Manager

1. Remote Site
informs the
Alarm Server
that a priority
message exists

Modem Site

2. Server
computer
receives the
alarm

Any Dialout
Modem

3. Communication
Services contact
the modem site
and retrieve
priority messages

The Alarm Server uses a series of command line arguments to specify the actions
it takes when a priority event is reported. These commands must be entered on the
computer that is running the Alarm Server utility. Typically the Alarm Server is
configured to launch the Connection Manager, which dials up the remote site and
retrieves the logs from the devices. The Alarm Server can also be configured to
launch other applications. A series of parameter switches are added to the
command line to pass information about the event to the application that is
launched.
Configuring the Alarm Server
The Alarm Server should have a dedicated phone line, modem, and COM port to
avoid conflicts with other ACCESS software components.
The modem used by the Alarm Server is not configured with the Management
Console– only dialout modems are configured in the Management Console. The
Alarm Server's executable, alarmsrv.exe, is typically located in
\\Siemens\WinPM.Net\SYSTEM\bin. You can run the Alarm Server in a console
window, or you can define a shortcut icon that includes all of the command line
arguments required.
Alarm Server Command Line Arguments
Refer to the WinPM.Net online help for a list of command lines that the Alarm
Server supports.

Chapter 5 - Features and Applications

Page 133

Alerting via an Alphanumeric Pager

9300 Series User’s Guide

Alerting via an Alphanumeric Pager
NOTE
For detailed information about building a framework for alerting via an alphanumeric pager, refer to the
Alert module description in the online ION Programmer’s Reference.

If an alphanumeric pager is specified as the destination address in the Alert
module, then an alphanumeric paging service, such as BC Tel Mobility, receives a
message from the ION meter.
Once the modem at the paging service is contacted, the ION meter transmits the
following information:
Pager identification number
Local time (year, month, date, hours, minutes, seconds)
Remote site identification
Priority of the alarm
Alert message, with text strings and realtime measured values
To include a module’s Source input in the message, reference the message string by
using the form %Vn, where n is the Source input number. In the following Message
register setting, the kWtot value is %V1. The string includes Source input 1 which
would be the kWtot register from the Power Meter module.
The destination register contains your modem access number for the paging
service provider and is what is dialed out first. The Pager Num register is the pager
access number that is provided by your paging company.

Alerting via a Numeric Pager
NOTE
For detailed information about building a framework for alerting via a numeric pager, refer to the Alert
module description in the online ION Programmer’s Reference.

If a numeric pager is specified as the destination address in the Alert module, then
a numeric paging service receives a message from the ION meter. Due to the
inherent limitations in numeric paging, the ION meter can only send a string of
digits to the paging service. The Alert module then waits a specified time,
determined by the number of commas inserted after the phone number in the Pager
Num setup register. Finally, the Alert module dials the message digital string.
There are two important factors to consider when setting up the Alert module for
numeric paging. First, be sure to specify a string of digits that is meaningful to you,
such as a coded message. Second, be aware that there is no way to assure that a
message has been successfully transmitted. Instead, there may be a busy signal or
an answering machine may take the call. The number of commas you add to your
dial string is an estimate of how long the modem at the remote site waits before it
transmits numbers.

Page 134

Chapter 5 - Features and Applications

9300 Series User’s Guide

Alerting via Email (9330 and 9350)

NOTE
In the following destination-setting example: 1-250-555-666,,,,,999#, the pager number is 1-250-555666 and the message string that displays on the pager is 999. You may need to insert 9,,, before the
destination number if the line you are using is not a direct line. In this case the destination number is
9,,1-250-555-666,,999#

Alerting via Email (9330 and 9350)
NOTE
For detailed information about setting up your network and building a framework for meter email
(MeterM@il) alerts, refer to the technical note ION MeterM@il.

If email is specified as the destination address in the Alert module then an email
message is sent to any address you specify. You can only set one email address per
Alert module. If you want to send an alert to more than one email address you
need to create a group — be sure your email server is configured to send email to
groups via SMTP (Simple Message Transport Protocol).
Follow the steps below to send email alerts from your meter. Note that your meter
must support emailing (with a correctly configured SMTP server):
1.

Create an Alert module.

2.

Configure these Alert module setup registers as indicated:
Message – type in the text of the alert to be emailed.
Destination – type in the destination email address.
Type – select Email.
Com Port – select Ethernet.
Location – type in a custom string; this is optional, and appears in the email.
Email From – type in an address that you want the email to appear from. This
may be required as some SMTP servers only accept emails from valid
addresses.

Chapter 5 - Features and Applications

3.

Create an ION module that will produce a pulse on its Trigger output when the
exceptional event occurs (for example, a Setpoint module pulses its Trigger
output when the setpoint condition is reached).

4.

Link the Alert module’s Trigger input to the Trigger output of the module created
in step 3.

5.

Send and save. When the Trigger input is pulsed, the Alert module establishes
communications with the SMTP mail server, and emails the alert message.

Page 135

Alerting via Email (9330 and 9350)

Page 136

9300 Series User’s Guide

Chapter 5 - Features and Applications

6

Revenue Metering
This chapter provides an overview of the 9300 Series revenue meters.

In This Chapter
9300 Series Revenue Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Revenue Meter Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Revenue Meter Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Differences between Standard and Revenue Models . . . . . . . . . . . . . . . . . . . . . . 136
Revenue Meter Energy Register Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Additional Revenue Metering Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Security Mechanisms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Anti-Tamper Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Password Protected Min/Max Register Resets . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Hardware-based Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Configuring the Revenue Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Before Disassembling the Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Inserting the Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
CT & PT Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

9300 Series Revenue Meters

9300 Series User’s Guide

9300 Series Revenue Meters
The fundamental functions of a revenue meter are to provide measurements that
are within industry-accepted limits for accuracy over a defined range of operating
conditions and to provide adequate protection against unauthorized alteration of
these measured quantities. International and national standards define industryaccepted accuracy limits. National and utility-based standards regulate protection
against unauthorized alteration of measured quantities.

Revenue Meter Models
Two revenue meter models are available; each model is designated by the
certification it holds.
Model

Certification Achievement

Current Inputs

Revenue Metering
Security Systems

RMICAN
(unsealed)

Canadian Revenue Metering Standards

Rated for 0.1 Amps
to 10 Amps AC

Enabled

RMANSI
(unsealed)

Complies with the accuracy
requirements of the ANSI C12.16
Revenue Metering Standard

Rated for 0.1 Amps
to 10 Amps AC

Enabled

Revenue Meter Options
The RMSEAL option provides a factory installed anti-tamper mechanical seal on
the base unit. This option is only available with the RMICAN meter model.

Differences between Standard and Revenue Models
The revenue meter differs from the standard (non-revenue) meter – additional
modules for revenue calculations and new energy output register labels have been
added to the revenue meter firmware.

Revenue Meter Energy Register Labels
The revenue and non-revenue meters differ in how they label energy flow:
standard (non-revenue) meters use the terms “imported” and “exported” energy,
whereas the revenue meters use the terms “delivered” and “received” energy.

Page 138

Chapter 6 - Revenue Metering

9300 Series User’s Guide

Security Mechanisms

Power Provider / Utility

Power Consumer

LINE
V1

LOAD
I11

I12 Delivered
Received

Imported

V1

I11

I12

Exported

Revenue Model

Regular Model

The revenue meter’s energy output register labels follow the revenue metering
terminology; the energy labels for kVAh, kVARh and kWh are different from the
non-revenue devices as follows:
imp is del

tot is del+rec

exp is rec

net is del-rec

For example, the meter’s output register kVARh tot will be kVARh del+rec in the
revenue meter model.

Additional Revenue Metering Modules
There are additional modules incorporated into the template of the revenue meter.
Some of these modules are used in the calculation and logging of both V2h and I2h
(used for transformer and line loss compensation).

Security Mechanisms
To meet Government regulations and Utility security requirements, the revenue
meter incorporates three types of security systems:
a traditional anti-tamper mechanical seal on the meter base unit
a password-based security system that permits password protected minimum/
maximum resets (for example, Sliding Window Demand reset)
a hardware-based security system that prevents modification of revenue
quantities after the meter is sealed

Chapter 6 - Revenue Metering

Page 139

Security Mechanisms

9300 Series User’s Guide

Anti-Tamper Seals
The revenue meter incorporates one or two sealing cans through which traditional
lead/wire seals can be inserted. When utilized, these lead/wire seals effectively
prevent unauthorized personnel from gaining access to meter internals. These seals
are provided with the meter, and are installed as follows:
1.

Place the sealing can over one of the rear panel corner holes and insert the
screw into the hole through the sealing can.

2.

Insert the ball bearing into the sealing can over the head of the screw. Install the
wire through the two holes in the sealing can.

3.

Twist the wire and crimp the lead-sealing tab onto the wire.

Password Protected Min/Max Register Resets
The meter front panel incorporates a password that must be entered in order to
reset any of the minimum/maximum register values. The password must therefore
be used to reset peak demand register values.

Hardware-based Security
The revenue meter is equipped with a comprehensive security system that provides
protection against unauthorized alteration or tampering of revenue-related
quantities. This security system locks all revenue-related ION modules, ION links
and ION setup-registers. Basic meter configuration parameters including volts
mode (service-type), PT ratio, and CT ratio are locked. These locks are automatically
enabled (at the factory) for all sealed revenue meters. Typical values that are
protected include:
kWh, kVARh, kVAh delivered, received, del-rec, del+rec
kW, kVAR, kVA Thermal and Sliding Window demand min and max values
Digital Outputs controlling the energy pulsing applications
All Power system settings, including PT an CT ratios
A two-pin jumper block is used to enable and disable the hardware security as
described in the next section.

Page 140

Chapter 6 - Revenue Metering

9300 Series User’s Guide

Configuring the Revenue Meter

Configuring the Revenue Meter
When enabled, the revenue meter security system prevents unauthorized
alteration of revenue-related quantities. By default, all revenue meters are shipped
from the factory with the security system enabled. You can temporarily disable the
security to configure your revenue meter. This is done by removing the meter’s
back plate, and placing a jumper into the meter.

Before Disassembling the Meter
Before attempting to remove the back plate of the revenue meter, ensure that the
device is protected against static-electric discharge. To prevent damage to the unit,
wear an anti-static wrist strap at all times.

DANGER
During normal operation of the 7350 ION, hazardous voltages are present which can cause severe injury
or death. These voltages are present on the terminal strips of the device and throughout the connected
potential transformer (PT), current transformer (CT), status input, relay, and control power circuits.
Installation and servicing should be performed only by qualified, properly trained personnel.

1.

Open all PT fuses (or direct voltage input fuses) and close all CT shorting
blocks.

2.

Turn off all power to the revenue meter and disconnect the Line and Neutral (or
DC power) wires from the Supply Power inputs to the unit.

3.

Disconnect all other wiring (or power off all other circuits) that may present
potentially hazardous voltage levels to the unit, such as connections to the relay
outputs.

4.

Ensure that all cables still connected to the revenue meter are NOT live.

Inserting the Key
In order to configure the revenue meter, ensure that adequate safety precautions
have been exercised as above.

CAUTION
The components inside the 7350 ION-RM are extremely sensitive to electro-static discharge. To prevent
damage to the unit, wear an anti-static wrist strap at all times when working inside the unit. Failure to use
proper equipment during servicing will void the 7350 ION-RM warranty.

Chapter 6 - Revenue Metering

1.

Remove the thumbscrews and retainer bars from the unit.

2.

Remove the anti-tamper wire seal and four screws on the rear panel.

3.

Slide out the rear plate of the device to reveal the unit’s circuit board panels.

4.

Locate the two-pin jumper header labeled “J1” on the communications card.

Page 141

Configuring the Revenue Meter

9300 Series User’s Guide

5.

Place the jumper block on to the J1 two-pin header (this disables the hardware
based security). Slide the rear plate back into the device and replace the four
screws onto the real panel. Apply Control power to the revenue meter.

6.

Configure the meter (e.g. Volts mode, PT and CT ratios, Pulse outputs).

7.

Remove control power from the revenue meter.

8.

Slide the rear plate out and remove the jumper block from the two-pin header to
re-enable the hardware-based security.

9.

Replace the rear plate and re-apply the anti-tamper seals.

CT & PT Selection
Consult your local Revenue Metering authorities to obtain standards for CT and
PT selection for revenue metering applications in your region.

Page 142

Chapter 6 - Revenue Metering

7

Hardware Reference
This chapter is intended to provide quick, at-a-glance, technical specifications for
the more common hardware features of the 9300 Series meter. Not all
specifications are included. All specifications are subject to change without notice.
For the most recent information see the 9300 Series Meter Datasheet.

In This Chapter
Standard Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Communications Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
COM1 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
COM 2 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
COM 3 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Profibus Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Internal Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Options and Retrofits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Terminal Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Remote Modular Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Switchboard Case . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Relay Expansion Board (Grayhill Rack) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
TRAN Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165

Standard Model

9300 Series User’s Guide

Standard Model
Rear View of Meter

Current Inputs
see page 156

SHORTING BLOCK or TEST BLOCK

Dry Contacts / Switches
31
22
21

32

Ports

12

11

Communications
see page 145

Digital Ports
see page 153
S1 S2 S3 S4

C

V+ (Max. 30V)
RS-485 bus

L1

Relays

VREF

+

L2

D4 D3 D2 D1 C
DIGITAL PORTS

V1

V2

V3

SH +
COM1

N

SH +
COM2

L

G

+
Voltage Inputs
see page 155

Power Supply
see page 155

+
+

Page 144

Chapter 7 - Hardware Reference

9300 Series User’s Guide

General Specifications

General Specifications
Environmental Conditions
To operate properly and effectively, environmental conditions should fall within
the guidelines listed below.

Chapter 7 - Hardware Reference

Environmental Condition

Acceptable Range

Operating Temperature

Base Unit: -20°C (-4°F) to 60°C (140°F)

Storage Temperature

-30°C (-22°F) to +85°C (185°F)

Relative Humidity

5% to 95% RH non-condensing

Altitude

Less than 2,000m (6,100ft) above sea level

Page 145

Unit Dimensions

9300 Series User’s Guide

Unit Dimensions
Basic Model Dimensions

96mm
(3.78")

96mm (3.78")

86 mm
(3.39")

162.2 mm (6.39")

Ethernet Port Location
72.8 mm (2.87“)
16.8 mm (0.66“)
14.2 mm (0.56“)

57.4 mm (2.26“)

Internal Modem Port Location
14.3 mm (0.56“)

13.4 mm (0.53“)

30.8 mm (1.21“)

33.8 mm (1.33“)

Page 146

Chapter 7 - Hardware Reference

9300 Series User’s Guide

Communications Specifications

Communications Specifications
Rear View of Meter

Ethernet

Modem
RJ11

RJ45

M

DM

FCC part 68 compliant
telephone cord

COM1 COM2

Category 3
or 5 UTP

Captured-wire
connectors

22 AWG shielded,
twisted pair

RS-485

NOTE
The Profibus meter option on the 9300 meter does not use a COM port.

The following table indicates which COM ports are available for each model.
Model

COM1

COM2

COM3

Ethernet

EtherGate

Modem

ModemGate

9300
9330
9350

Chapter 7 - Hardware Reference

Page 147

COM1 Port

9300 Series User’s Guide

Co-existing Hardware Options on the Meter
These are the hardware ordering options that can (and cannot) exist together on
the same meter.
Profibus
Profibus

Ethernet

Modem

Digital
Inputs

Digital
Outputs

Analog I/O

No

Yes

No

Yes

No

Yes

Yes

Yes

No

Yes

Yes

Yes

Yes

Yes

Ethernet

No

Modem

Yes

Yes

Digital Inputs

No

Yes

Yes

Analog I/O

No

No

Yes

Yes

Yes

COM1 Port
COM1 is used for RS-485 communications. If you have the ModemGate option on
your meter, COM1 will automatically be set to ModemGate, not RS-485.

NOTE
The internal modem option is hardwired to COM1. If you are using ModemGate, then any meter with an
internal modem that will reside on the serial loop must connect to the serial loop using COM2. If COM1
is used, then the two modems (gated meter internal modem and serially looped meter internal modem)
conflict during communication.

RS-485 Connections
RS-485

COM

SH +
+ -SH

RS-485 connections are made via the captured-wire connectors on the rear of the
meter. Devices can be connected in series using RS-485 (see diagram to the left). Be
sure not to ground the wires at both ends.
The specifications for RS-485 communications are as follows:

Page 148

Specification

Value

Baud Rates

Up to 19,200 bps (default is 9,600 bps)

Duplex

Half

Supported Protocols

ION (default), Modbus RTU, DNP 3.0, EtherGate (COM2), ModemGate
(COM1), and Factory

Isolation

Optical isolation from all other inputs and outputs

Chapter 7 - Hardware Reference

9300 Series User’s Guide

COM 2 Port

Connections

1

Specification

Description

Cable Type

Good quality shielded twisted pair cable, AWG 22 or larger.

Max. Cable Length

4,000 ft. (1,219 m) 1

Max. number of devices per bus

32

The lengths of all (+ and –) cable segments must be counted including those that connect devices to
terminal blocks.

Terminal connections on the meter are marked as follows:
Marking

Terminal Function

SH

RS-485 Shield (electrically connected to chassis ground)

+

RS-485 Data Plus

-

RS-485 Data Minus

COM 2 Port
COM 2 is used for RS-485 communications and can be configured as an EtherGate.

RS-485 Connections
The specifications for RS-485 communications on COM 2 are the same as those for
COM 1.

NOTE
On 9330 and 9350 meters with the Ethernet card, COM2 is hardwired for EtherGate only, and cannot
be used for serial communication.

Chapter 7 - Hardware Reference

Page 149

COM 3 Port

9300 Series User’s Guide

COM 3 Port
COM 3 is reserved for the optical (infrared) port.

Infrared Connection
Specifications for the optical port are as follows:

1

Specification

Value

Baud Rate

Up to 19,200 bps (default is 9,600 bps)

Duplex

Half

Operating Distance

less than 1 meter (3 feet) 1

Optical Range

±15° (minimum), ±30° (maximum)

Supported Protocols

ION, Modbus RTU, DNP 3.0, FACTORY (default is ION)

Compatibility

ANSI C12.13 Type II magnetic optical communications coupler

No physical connection is required to use the infrared port. Any device with an IRDA-compliant port
that is positioned within the operating distance and optical range specified above can receive data.

Ethernet Port
10Base-T Ethernet connections are made via the RJ45 modular port on the left side
of the unit.

Pin 1: Transmit Data +
Pin 2: Transmit Data Pin 3: Receive Data +
Pin 6: Receive Data -

1 2 3 4 5 6 7 8

RJ45

Description

Cable Type

High quality Category 3 or 5 UTP (CAT 5 unshielded twisted pair
recommended) cable

Cable Ends

Male RJ45 modular connector for connection to the 10Base-T port

Specifications for the Ethernet ports are as follows:

1

Page 150

Specification

Specification

Value

Type (10 Base-T)

IEEE 802.3 10Base-T for 10 Mbps base band CSMA/CD LANs

Data Rate

10 Mbps

Supported Protocols

ION, Modbus RTU 1, Modbus/TCP 1

Isolation

Transformer isolated to 1,500 VAC RMS

The unit ID for Modbus RTU and Modbus/TCP over Ethernet is 100.

Chapter 7 - Hardware Reference

9300 Series User’s Guide

Profibus Port

IP Service Ports
Connect to the following TCP/IP Service Ports for communications over Ethernet.

1

Protocol

TCP/IP Port

ION

7700

Modbus RTU

7701

Modbus/TCP

502

EtherGate 1

7802

EtherGate communications are available only through COM2. This feature is available only on
9330 and 9350 meters.

Profibus Port
This option is offered exclusively on the 9300 meter.

LEDs (DE and PWR)

Profibus female
connector.
PROFIBUS

DE
PWR

NOTE
The Profibus Master file (.GSD file) is included on a floppy disk with the meter. This file must be installed
on your Profibus Masters before the meter can communicate with the Profibus network.

The optional Profibus port on the meter is capable of operating baud rates up to 12
Mbps. Profibus Connections to the meter are made via the nine-pin connector on
the rear of the unit. Plug your Profibus connector from the network into this
connector.

Chapter 7 - Hardware Reference

Page 151

Internal Modem

9300 Series User’s Guide

Profibus Female Connector
(located on meter)
5

1

9

6

Pin Number

Profibus Function

1

N/A

2

N/A

3

B-line

4

RTS

5

Isolated GND

6

Isolated Vcc

7

N/A

8

A-line

9

N/A

Internal Modem

Pin 3: Ring
Pin 4: Tip

1 2 3 4 5 6

RJ11

Connection to the internal modem is made via the RJ-11 jack, or two captured wire
connectors, located on the right side of the meter. Connect the meter to the
telephone network with an FCC Part 68 compliant telephone cord (that has two
male RJ-11 plugs).
If you have the captured wire connector option, connect the meter to the telephone
system with the (bare wire to RJ-11) cable provided. If you have the CTR-21
compliant internal modem option, you may also require an adaptor to interface
with your regional telephone jack.

1

Page 152

Specification

Value

Baud Rate

300 to 33,600 bps 1

Error Correction

V.42 LAPM, MNP 2-4, MNP 10

Data Compression

V.42 bis/MNP 5

Interface

RJ11 (Tip & Ring)

Government
Approvals

FCC Modem: FCC P68 (USA), Industry Canada CS-03 (CAN)
CE Modem: CTR-21 (Austria, Belgium, Denmark, Finland, France,
Germany, Greece, Iceland, Ireland, Italy, Luxemburg, Netherlands,
Norway, Portugal, Spain, Sweden, Switzerland, UK)

The baud rate used between connected modems is independent of the baud rate used for
communication between the modem and the 9300 Series meter.
Higher data rates can be achieved if data compression is enabled in the modem.

Chapter 7 - Hardware Reference

9300 Series User’s Guide

LEDs

LEDs
All LEDs are found on the backplate of the meter, except the two Ethernet LEDs,
which are found on the left side (if you are facing front of meter).
LED

Color

Function

L1

Red

Pulses once for every 1.8 Wh of energy measured

L2

Red

Blinks slowly to indicate CPU operation. It blinks rapidly to indicate communications through one of its
serial ports 1

Ethernet LINK

Yellow 2

Remains on while an Ethernet carrier is present; if this LED is off, the Ethernet connection cannot be
established

Ethernet ACTIVITY

Yellow 2

Blinks to indicate Ethernet traffic

Profibus DE

Yellow

Indicates communications between the Profibus Master and the meter have been established

Profibus PWR

Red

Shows that the meter is powered

Chapter 7 - Hardware Reference

1

If the L2 LED does not blink once the meter is installed, contact Siemens Customer Service.

2

One or both of the Ethernet LED colors may differ from the standard yellow.

Page 153

I/O Connections

9300 Series User’s Guide

I/O Connections
Use a wire size that is appropriate for your application and complies with local
electrical codes.

Digital Outputs
The meter provides four digital output ports that are suitable for controlling external
relays. The digital outputs can deliver a continuous signal or pulse.
Description

Specification

Output Type

Form A Solid State

Outputs

D1, D2, D3, D4

Wire

28 to 16 AWG (0.1 to 1.3 mm2)

Connector Type

Captured wire

Signal Type

Continuous or pulse

Max. Load Voltage

30 V

Max. Forward Current

80 mA

Isolation

Optical

Digital Outputs

C

V+ (maximum 30V)
Relays

D1
Internal Circuit

D2
C (+)

D3
D1

D4

CAUTION
Only use Siemens approved external relays with the meter digital outputs. Contact Siemens for complete
information regarding relay specifications and applications.

Page 154

Chapter 7 - Hardware Reference

9300 Series User’s Guide

I/O Connections

Digital Inputs
The meter supports four digital inputs. These can be used for monitoring the
condition of an external contact, or for pulse counting applications.
Description

Specification

Input Type

Self-excited (internal 30 VDC supply)

Inputs

S1, S2, S3, S4

Application

Dry contact sensing, or with external excitation.

Wire

28 to 16 AWG (0.1 to 1.3 mm2)

Connector Type

Captured wire

Max. Pulse Width

25 pulses per second

Digital Inputs
S1

Optically coupled
solid state relay
30 VDC
Internal
Supply

External Dry
Contacts

S2

R

S1

S3

C (+)

S4

Polarity
for SSR
Contact
shown.

Internal Circuit

C

Analog Inputs
Two types of analog input ports are available when you order a meter (refer to
your meter’s label to determine what type you ordered):
0-20 mA (scalable to
4-20 mA) Option

Specification

Chapter 7 - Hardware Reference

0-1 mA Option

Input Impedance

25 Ω

475 Ω

Maximum Source
Impedance

500 Ω

10 kΩ

Accuracy

±0.3% of full-scale

Inputs

AI1, AI2, AI3, AI4

Connectors

Phoenix captured-wire

Update Rate

1 Hz

Channel to Channel
Isolation

None

Max. Common Mode
Voltage

30 V

Standards Compliance

IEC 61000-4-4 fast transient test with capacitive clamp (4 kVp-p@2.5
kHz for 1 min)

Page 155

I/O Connections

9300 Series User’s Guide

ANALOG INPUT PORTS
+ AI1 -

Analog Source
(Voltage / Current)

Out
In

+
_

Analog Outputs
This ordering option provides four analog outputs. Two varieties are available:
0-20 mA (scalable to
4-20 mA) Option

Specification

0-1 mA Option

Max. Load Drive Capability

500 Ω

Accuracy

±0.3% of full-scale

Outputs

A1, A2, A3, A4

Connectors

Phoenix captured-wire

Channel to Channel
Isolation

None

Max. Common Mode
Voltage

30 V

Standards Compliance

IEC 61000-4-4 fast transient test with capacitive clamp (4 kVpp@2.5 kHz for 1 min)

10 kΩ

NOTE
There is one common terminal for all of the Analog Outputs.

Page 156

Chapter 7 - Hardware Reference

9300 Series User’s Guide

Electrical Specifications

Electrical Specifications
Power Supply

1

Specification

Description

Supply Voltage

Standard AC: 95 - 240 VAC (+/- 10%), 47-440 Hz
Standard DC:120 - 310 VDC (+/- 10%)
Option: 20 - 60 VDC (+/- 10%)

Supply Current

Standard: 0.2 Amp (12W)
Option: 0.6 Amp (12W) 1

Connector Type

Captured wire

Wire Type

AWG 16 to AWG 14

Protection

2A slow blow fuse

1

If a standard display unit is used.

Voltage Inputs
Specification

Value

Operating Range

3 phase: 50 to 347 Volts RMS (L-N) and 87 to 600 Volts RMS (L-L)
Single phase: 50 to 300 Volts RMS (L-N) and 100 to 600 Volts RMS (L-L)

Steady-State Rating

0 to 347 Volts RMS

Overload Rating

1,500 VAC RMS (continuous) and 3,250 VAC RMS (one second,
non-recurring)

Input Impedance

>2 MΩ

Phase Voltage
Connector Type

Ring or spade

Phase Voltage
Wire Type

AWG 14 to 12 wire

Phase Voltage Sense
Lead Protection

Use breakers or fuses at their source

CAUTION
Phasing and polarity of the AC voltage inputs and their relationship is critical to the correct operation of
the unit.

Chapter 7 - Hardware Reference

Page 157

Electrical Specifications

9300 Series User’s Guide

Potential Transformers
Specification

Description

Use of PTs

Required for all systems with voltage levels greater than those above

Secondary Rating

50 to 347 VAC +25% is required

CAUTION
In cases where PTs are required, the secondaries should be fused.

Current Inputs
Specification

Value

Overload

20 Amps continuous, 500 Amps for 1 second, non-recurring

Burden

0.0625 VA @ 10 Amps

Phase Current Wire Type

AWG 14 to 12 wire

Starting Current

2 mA

Current Transformers

1

Page 158

Specification

Value

Primary Rating

Equal to the current rating of the power feed protection device

Burden Rating

>3 VA 1

Secondary Rating

5 Amp nominal, 10 Amp full-scale

The CT burden rating must exceed the combined burden of the meter, plus cabling, plus any other
connected devices.

Chapter 7 - Hardware Reference

9300 Series User’s Guide

Options and Retrofits

Options and Retrofits
Terminal Cover
This option ensures that the terminal strips on the meter’s base are not accessible
after installation.

DANGER
During normal operation of the meter, hazardous voltages are present which can cause severe injury or
death. Only qualified, properly trained personnel should perform installation and servicing.

1.

Turn off all power to the meter.

2.

Open all PT fuses (or direct voltage input fuses). Close all CT shorting blocks.

3.

Ensure that all cables still connected to the meter are NOT live.

4.

Unscrew the four corner screws (T10 TORX) from the rear of the unit.

5.

Screw in the four spacers (stand-offs).

6.

Fasten the Terminal Strip Cover with the four screws (T10 TORX) and washers
supplied.

CAUTION
The spacers have a maximum torque rating of 1.35 Nm. Do not over tighten the screws.

7.

Close the PT fuses (or direct voltage input fuses), and open the CT shorting
blocks.

8.

Turn on power to the meter and verify the correct operation of the unit.

Installation Diagram

Spacer

Washer

Screw

Rear of Meter

Chapter 7 - Hardware Reference

Terminal Cover

Page 159

Remote Modular Display

9300 Series User’s Guide

Remote Modular Display
The remote modular display (RMD) connects to the TRAN meter as shown:

4x 6mm (0.25”) mounting
slots. Mount flush to any
flat surface.

DISPLAY

1

Specification

Description

Connector Type

DB25

Wire Type

1.8 m cable 1

Only use cable supplied by Siemens to connect the remote display unit.

RMD Dimensions

96mm
(3.78")

96mm (3.78")

86mm
(3.39")

37.2mm
(1.47")

Switchboard Case
The meter is available in the switchboard-case ordering/retrofit option.
Switchboard meters can be plugged into the S1 (General Electric) or the FT21
(ABB) switchboard case.

Page 160

Chapter 7 - Hardware Reference

9300 Series User’s Guide

Switchboard Case

Installation Instructions
CAUTION
Installation and maintenance of the switchboard meter should only be performed by qualified personnel
who have appropriate training and experience with high voltage and high current devices.

If the switchboard case is included with your meter, draw the meter chassis out of
the case to facilitate its installation into the mounting hole. Installing and setting
up the switchboard meter is summarized in the following steps.
1.

Review the unit’s dimensions and prepare a mounting hole for the
switchboard case. If you are retrofitting your switchboard meter into an
existing case, you may have to drill or punch a 29mm (1.13”) round hole in the
back of the case to accommodate communications, I/O, and/or auxiliary power
wiring.

NOTE
For retrofitting S1 style switchboard cases, a pre-drilled backplate is included. To use it, remove the
backplate from the old switchboard case and replace it with the supplied backplate.

2.

Place the supplied 29mm (1.13”) nylon bushing into the drilled hole if desired.
Refer to “Unit Dimensions” on page 161.

3.

Place the switchboard case into the prepared mounting hole. Attach the
mounting screws.

4.

Wire the phase voltages and currents to the terminal posts on the rear of the case.

5.

Read the warning label on the green captured-wire plug.

6.

Connect any communications, I/O, and/or auxiliary power wiring to the meter.
For the P24 power supply option, ensure that the auxiliary power cable is
powered off.
Pass all wiring through the switchboard case using the round hole in back.
Connect the communications and I/O wiring to the meter; for the P24 power
supply option, also connect the auxiliary power cable to the meter’s power
supply terminals.
Slide the meter chassis into position while feeding the excess wiring
through the hole in the rear of the switchboard case, making sure none of
the wires are pinched.
Secure the meter by locking the two chassis levers into position.
Wire any external communications and I/O; for the P24 power supply
option, connect the other end of the auxiliary power cable to an external
dedicated 20 to 60VDC source that is powered down.

7.

Connect the ribbon cable to the back of the display on the case cover.

8.

Energize the meter as follows:
For the P24 power supply option, power up the auxiliary power
(20 to 60VDC) source.

Chapter 7 - Hardware Reference

Page 161

Switchboard Case

9300 Series User’s Guide

For the standard option, the meter is powered up when the voltage inputs
are applied in the next step.
9.

Apply the current and voltage inputs:
For S1 style switchboard meters, insert the connection plug into the slot at
the bottom of the meter.
For FT21 style switchboard meters, push the shorting switches up.

10. Place the case cover into position and tighten the thumbscrew(s).
11. Perform basic setup and verify the meter’s operation: refer to the meter’s
Installation and Basic Setup Instructions manual for details.

Suggested Mounting Hole Dimensions
S1 Case HoleFT21 Case Hole
149mm (5.87")
141mm (5.55")

156mm (6.14")
146mm (5.75")

246mm (9.69")

230mm (9.06")

210mm (8.27")

111mm (4.37")

Page 162

Chapter 7 - Hardware Reference

9300 Series User’s Guide

Switchboard Case

Unit Dimensions
S1 Case
142mm
(5.59") 42mm
(1.65")

34mm
(1.34")

29mm
(1.13")
206mm
(8.11")
239mm
(9.39")
99mm
(3.89")
75mm
(2.96")

49mm
(1.92")
176mm
(6.91")

157mm
(6.19")

56mm
(2.19")

172mm
(6.77")

FT21 Case
145mm
(5.69")

105mm
(4.14")

47mm
(1.84")

226mm
(8.89")

265mm
(10.42")

113mm
(4.45")

163mm
(6.43")

Chapter 7 - Hardware Reference

43mm
(1.69")
51mm
(2.00")

152mm
(6.00")

169mm
(6.65")

Page 163

Switchboard Case

9300 Series User’s Guide

The arrows in the diagram below indicate where the grounding posts are located
(on the back of the switchboard meter):

P24 Power Supply Option

Page 164

1.

Connect the auxiliary power cable to the meter’s power supply terminals.

2.

Connect the other end of the cable to an external dedicated 20 to 60VDC source
that is powered down.

3.

Energize the meter by powering up the dedicated 20 to 60VDC source.

Chapter 7 - Hardware Reference

9300 Series User’s Guide

Relay Expansion Board (Grayhill Rack)

Relay Expansion Board (Grayhill Rack)
The optional relay extension board allows for custom digital output applications
using specific Grayhill modules. This option includes a 4-position Grayhill module
rack and one of two power supplies:
a 100-240 VAC/110-370 VDC to 5 VDC power supply
a 20-60 VDC to 5 VDC power supply

D4 control module (module 4)
D3 control module (module 3)
D2 control module (module 2)
D1 control module (module 1)
Wire sizes will vary depending on application

B AC OUTPUT Y AC INPUT
R DC OUTPUT W DC INPUT

These numbers indicate
which Grayhill module is
controlled by D1 to D4.

2

3

4

1

Grayhill Rack
part # 70GRCK4R
1

AWG 20 to AWG 16

2

3

4

5

6

7

8

9

+5 VDC
output

Power Supply

NOTE
The meter’s digital outputs can be wired directly (without the use of the Grayhill rack), as long as the
external power supply you use does not exceed 30 VDC/80 mA.

Chapter 7 - Hardware Reference

Page 165

Analog I/O

9300 Series User’s Guide

Wiring for Modules with Manual Override
The following wiring scheme must be used when the relay extension board
contains Grayhill modules with the manual override feature.

2

1

3

4

5

6

7

8

9

91 Ω
91 Ω
91 Ω

+ 5 VDC
output

AWG 20 to AWG 16

91 Ω (¼W 5%)

Power Supply

DIGITAL PORTS

DANGER
In this configuration, the outputs of the Grayhill modules with manual override will switch state on
power up.

Analog I/O
The following diagram shows the additional connections required for the analog
I/O ordering option.

32

31

22

ANALOG INPUTS
+ AI1 -

+ AI2 -

+ AI3 -

21

12

ANALOG OUTPUTS
A1 A2 A3 A4

+ AI4 -

C

2

AWG 24 to 18 (0.2 to 0.8 mm ) recommended.
Wire sizes will vary depending on application
Analog Input connections
from external transducers:
0 to 20mA or 0 to 1mA

Page 166

Analog output connections
to analog transducers
0 to 20mA: 500 Ω load Max
0 to 1mA: 10k Ω load Max

Chapter 7 - Hardware Reference

9300 Series User’s Guide

TRAN Model

TRAN Model
The 9300 TRAN is a meter with no display. All specifications are the same as for
standard 9330, except the following.

Unit Dimensions
TRAN Model Dimensions

86mm
(3.39")

60mm
(2.36")

6mm
(0.24")

Chapter 7 - Hardware Reference

100mm (3.94")

164.5 mm (6.48”)

Page 167

Unit Dimensions

Page 168

9300 Series User’s Guide

Chapter 7 - Hardware Reference

I N DE X
...............

I
A
Advanced Meter Setup menu 32
alarm server 131
command line arguments 132
configuring 132
Alert module 131
alerting 106
remote site event notification 132
via alphanumeric pager 133
via email 134
via numeric pager 133
Analog Input module 119
analog inputs
using the optional 123
Analog Output module 119
analog outputs
using the optional 124
ANSI 32, 107, 108
Auto Scroll 33

B
backlight timeout 33
before you can use this guide 21
bus wiring 107
buttons 24

C
Calibration Pulser module 119
Clear Functions menu 28
disturbance counter reset 29
energy reset 29
harmonics min/max reset 29
manual waveform trigger 29
min/max reset 28
peak demand reset 28
sliding window reset 29
status counters 29
thermal demand reset 29
COM1 146
COM2 147
RS-485 147
COM3 148
Comm 1 module 114
common applications 13
communications 106
adding components 73

channel 43
COM1 146
COM2 147
COM3 148
diagnostic 36
in ION Setup 98
in ION software 73
infrared 148
specifications 148
internal modem 150
optical (see infrared)
protocol configuration 54
protocols 16
RS-485 146
setup 43
specifications 145
Communications module 30
configuration changes
in ION modules 86
configuration tools 43
Connection Manager 132
connections
ethernet 110
optical port 108
Profibus 116
RS-485 107
control objects 77
current inputs 156
current transformers 156
custom front panel displays 38

D
data
digital inputs 80
display and analysis tools 14
displaying diagnostics in ION Setup 103
displaying if software not configured 76
displaying with ION Setup 102
displaying with RMD 15
displaying with Vista 15
energy and demand 80
historical logging 46, 78
logging 45, 125
long-term min/max 78
output registers 88
peak demand reset 80
power quality 78

real-time 78, 88
data and event logging
changing logged parameters 125
Data Recorder module 45, 125
date 37
default meter functionality 42
demand setup 52
Designer 109
changing setup registers 88
configuring setup registers 89
creating new modules 91
customizing frameworks 90
deleting modules 91
editing existing frameworks 93
linking modules 91
main configuration screen 87
replacing input links 93
viewing real-time data 88
devices
ethernet 72
serial 72
Diagnostic menu 35
displaying the date/time 37
using the communications diagnostic 36
using the I/O diagnostic 37
viewing the Harmonics diagnostic 36
diagnostics
troubleshooting 37
diagram objects 81
dialout modems 72
Digital Input module 119
digital inputs 80
reset 80
status 80
using the onboard 123
Digital Output module 119
Display Setup menu 33
adjusting backlight timeout 33
adjusting contrast 33
adjusting update rate 33
setting display mode 34
using the Auto Scroll feature 33
displays
contrast 33
custom front panel 38
disturbance counter reset 29
DNP 3.0 60
changing configuration 60
export module settings 61
factory configuration 60
importing data 62
options settings 62

E
EEM 12
EN50160 95
energy and demand 80
demand profile trending 80
peak demand reset 80
energy pulsing 122
energy reset 29
entering the password 129
environmental conditions 143
EtherGate 112
ethernet 31
connection diagnostic screen 37
connections 110
diagnostic screen 36
port 148
Ethernet communications module 111
Event Log Controller module 126
event log viewer 77
event priority groups 126
external events 126

F
factory configuration 17
restoring 66
factory information 53
Factory module 53
fixed module links 86
frameworks 66, 84, 133
cautions 90
customizing 90
customizing in Designer 90
deleting an input link 93
front panel
accessing front panel setup menus 27
configuring the meter using 27
default display screens 25
display resolution 24
displaying data with 24
invalid and N/A messages 25
navigating setup menus 27
password security 28
security 35
using buttons 24

G
global event log viewer 77
Grayhill 163
grouping objects 77

H
harmonics
diagnostics 36

min/max reset 29
Hyperterminal 118

I
I/O 119
analog diagram 164
analog inputs 153
analog outputs 154
diagnostic mode 37
digital inputs 16, 153
digital outputs 152
onboard
digital outputs 121
options 16
infrared 108
energy pulsing 110
Infrared Comm module 109
Input/Output (see I/O)
interface
customizing in Vista 81
internal modem 113, 150
internet connectivity 117
ION architecture
core modules 86
modules 84
ION Enterprise 131
core modules 86
fixed module links 86
locked modules 86
modules 84
persistent modules 86
Reporter 94
reporting 46
security 70
ION events 126
ION MeterMail 31, 117
ION modules 84
core 86
creating new 91
customizing frameworks 90
deleting 91
deleting an input link 93
depth 84
editing existing frameworks 93
fixed links 86
linking 91
linking restrictions 84
locked 86
persistent 86
registers 85
replacing input links 93
security 86
sequence of execution 85
specifying a port 119

ION registers 85
not available values 85
ION Setup 98
changing a setup register 101
configuring communications 98
displaying data 102
displaying diagnostics data 103
Setup Assistant 101
sites, groups and meters 99
ION software
adding components 73
adding network components 73
configuring communication 73
core modules 86
fixed module links 86
ION Setup 98
locked modules 86
modules 84
persistent modules 86
security 70
ION WebMeter 117
IR pulsing 110

L
LED
energy pulsing 122
LED indicators 151
load profile 95
locked modules 86
logging
capacity 127
changing parameters 47
changing the frequency 46
changing the log depths 47
data 125
default configuration 45
event 126
historical 46
revenue 45, 125
loop topology 107

M
Management Console 71
adding network components in 73
configuring network components 71
properties dialog 73
manual waveform trigger 29
MeterMail 15, 31, 110, 117
min/max reset 28
Modbus 54, 59, 110
changing configuration 55
factory configuration 55
importing data 58
module settings 55

Slave parameter map 56
Modbus Slave module 55
modem
dialout 72
initialization string 113
modem initialization string 44
ModemGate 113
module security 86
MV-90 46, 125

Slave parameter map 63
protocols 44
DNP 3.0 60
Modbus RTU 54
Modbus TCP 59
ModemGate 115
Profibus 63
third party 54
Pulser module 119

N

Q

nameplate 35
Nameplate Info menu 35
network components
devices 72
dialout modem 72
servers 71
sites 72
network diagrams
generating in Vista 75
numeric objects 77

Quick Setup menu 30
using the Comm menus 30
using the Ethernet menu 31
using the Power Meter menu 31
using the Profibus Comm menu 30

O
optical port
connections 108
options
Relay Expansion Board (REB) 163
terminal cover 157
output registers
owner 93
real-time data 88

P
passwords 28, 129
changing on meter 130
peak demand reset 28
Periodic Timer module 46
persistent modules 86
ports
specifying 119
potential transformers 156
Power Meter module 31, 32, 42, 130
power quality data 78
disturbance details 79
harmonics measurements 79
long-term min/max 79
setup 44
voltage disturbance counter reset 79
power supply 155
Profibus 30, 63, 116
changing configuration 63
factory configuration 63
ports 149

R
real-time measurements
historic data enable 78
recording capacity 127
registers
editing using the front panel 28
enumerated 28
numeric 28
relay expansion board
wiring 164
Relay Expansion Board (REB) 122, 163
Relay Extension Board (REB) 17
Remote Modular Display (RMD) 15, 24
installation instructions 159
mounting dimensions 160
P24 power supply option 162
specifications 158
Reporter 94
EN50160 95
pre-configured reports 94
report creation and generation 96
reporting 125
reports
adding a shoulder period 97
changing which days are holidays 97
creation and generation 96
EN50160 95
energy and demand 95
generating 96
load profile 95
pre-configured 95
time of use schedules 97
residual current calculation 130
revenue logging 125
Revenue Meters (RM) 135
configuring 139
CT & PT selection 140

models 136
security mechanisms 137
standard versus RM models 136
RS-485
connection methods to avoid 108
connections 107
diagnostic screen 36
specifications 146

S
Sag/Swell module 32, 44
Screen Setup menu 34
style setting 34
values setting 34
security
default settings 70
entering password 129
front panel 28
in modules 86
meter 70
software 70
standard meter 129
Security menu 35
changing the User password 35
Setpoint module 48
setpoints 79
configuring 48
over average current 80
over kW sliding demand 79
under average line-line voltage 80
under power factor monitoring 80
Setup Assistant
in ION Setup 101
setup registers
changing 88
changing in ION Setup 101
configuring with Designer 89
sites
direct 72
ethernet gateway 72
modem 72
Sliding Window Demand module 52
sliding window reset 29
SMTP 31
specifications
current inputs 156
current transformers 156
potential transformers 156
power supply 155
voltage inputs 155
standard meter security 129
status counters 29
status objects 77
straight line topology 107

T
TAG 53
Telnet 118
Thermal Demand module 52
thermal demand reset 29
time 37
time synchronization 128
TRAN 24
unit dimensions 165
troubleshooting
diagnostic screens 37

U
unit dimensions 144
update rate 33
user diagram
custom appearance 82
using this guide 21

V
Vista
control objects 77
customizing the interface 81
diagram elements 77
diagram objects 81
displaying data 75
event log viewer 77
generating a network diagram 75
grouping objects 77
long-term min/max 78
numeric objects 77
real-time diagram 78
real-time measurements 78
status objects 77
summary of data provided 78
voltage inputs 155

W
waveforms
changing recording 47
WebMeter 15, 117
WebMeters 110
WebReach 118
WebServers Config access 31

X
XML 15

Z
zero scale
setting for 4 to 20mA outputs 124

Siemens Energy & Automation, Inc.
Power Management Technologies
3333 Old Milton Parkway
Alpharetta, GA 30005

For Nearest Sales Office
1.800.964.4114

© Siemens Energy & Automation, Inc.

Windows is a trademark and Microsoft is a registered
trademark of Microsoft Corporation.
All others are of Siemens AG.

Siemens is a registered trademark of Siemens AG.
Specifications are subject to change without notice.

www.sea.siemens.com
sales/salesoffices.html

For More Information Visit

www.sea.siemens.com/access
Order No. 70000-0177-01
PDF 0800 Printed in the U.S.A.



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.3
Linearized                      : Yes
Modify Date                     : 2003:07:31 10:25:41Z
Create Date                     : 2003:07:30 09:17:25Z
Page Count                      : 176
Creation Date                   : 2003:07:30 09:17:25Z
Mod Date                        : 2003:07:31 10:25:41Z
Producer                        : Acrobat Distiller 5.0.5 (Windows)
Author                          : cesart
Metadata Date                   : 2003:07:31 10:25:41Z
Creator                         : cesart
Title                           : 9300 Series User’s Guide
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu