Albatros2
Zone controler
User Manual OEM

Edition 1.0
Controller series A
CE1U2353en01a
22. November 2006

RVS46..
AVS75..
AVS37..
QAA75..
QAA78..
QAA55..

Building Technologies
HVAC Products

2/26
Siemens Schweiz AG
HVAC Products

User Manual OEM

CE1U2353en01a
22. November 2006

Table of contents
1

Overview of OEM settings ............................................................................... 4

2

The settings in detail...................................................................................... 15

2.1

Operator section ............................................................................................ 15
Operation and display.................................................................................... 15

2.2

Heating circuits .............................................................................................. 15
mixing valve control ....................................................................................... 15

2.3

Domestic hot water........................................................................................ 16
Setpoints........................................................................................................ 16
Release ......................................................................................................... 16

2.4

Pump H1/H2 .................................................................................................. 17
pump H1 ........................................................................................................ 17

2.5

Primary controller / system pump .................................................................. 17
flow temperature setpoint limitations ............................................................. 17
mixing valve control ....................................................................................... 18

2.6

DHW storage tank ......................................................................................... 19
Release ......................................................................................................... 19
Charging control ............................................................................................ 19
Charging time limitation ................................................................................. 20
Discharging protection................................................................................... 20
Overtemperature protection........................................................................... 21
DHW push ..................................................................................................... 21

2.7

Configuration ................................................................................................. 21
Building and room model............................................................................... 21
Parameters .................................................................................................... 22

2.8

LPB................................................................................................................ 22
Error / maintenance / alarms ......................................................................... 22
Range of action of changeover...................................................................... 22

2.9

Error............................................................................................................... 23
History 1...10 ................................................................................................. 23

2.10

Diagnostics consumers ................................................................................. 23
Heating circuit 1, heating circuit 2, heating circuit P ..................................... 23

3/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Table of contents

CE1U2353en01a
22. November 2006

1

Overview of OEM settings

The table below shows all available settings up to the heating engineer level. However,
certain operating lines may be hidden, depending on the type of unit.

Max

Unit

O = OEM

Minimum

Function

User level

Operating line

Time of day and date
1
E Hours/minutes
2
E Day/month
3
E Year
5
F Start of summertime
6
F End of summertime
Operator section
20
E Language

F = heating engineer

Default value

E = enduser
I = commissioning
BZ = operating line

Legend

25.03
25.10

00:00
01.01
2004
01.01
01.01

23:59
31.12
2099
31.12
31.12

hh:mm
dd.mm
yyyy
dd.mm
dd.mm

German

-

Temporarily

-

Off

-

Off

-

German ¦ …

22

F

Info
Temporarily ¦ Permanently

26

F

Operation lock
Off ¦ On

27

F

Programming lock
Off ¦ On

30

O

Data:read

No

No ¦ Yes

31

O

Data:write

No

No ¦ Yes

40

I

Used as

Room unit 1

-

Heating circuit 1

-

Commonly with HC1

-

Commonly with HC1

-

Heating circuit 1

-

Room unit 1 ¦ Room unit 2 ¦ Operator unit ¦Service unit

42

I

assignment room unit 1
Heating circuit 1 ¦ Heating circuits 1 and 2

44

I

Operation HC2
Commonly with HC1 ¦ Independently

46

I

Operation HCP
Commonly with HC1 ¦ Independently

48

I

Action occupancy button
None ¦ Heating circuit 1 ¦ Heating circuit 2 ¦ Commonly

54
F
70
F
Wireless
120
I

Readjustment room sensor
Software version

0.0
-

Binding

No

-3
0

3
99.9

°C
-

No ¦ Yes

121

I

Test mode

Off

Off ¦ On

130

I

Room unit 1

-

-

-

-

-

-

-

-

Missing ¦ Ready ¦ No reception ¦ Change batt

131

I

Room unit 2
Missing ¦ Ready ¦ No reception ¦ Change batt

132

I

Outside sensor
Missing ¦ Ready ¦ No reception ¦ Change batt

133

I

Repeater
Missing ¦ Ready ¦ No reception

4/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Default value
-

Unit

Function
Operator unit

Max

User level
I

Minimum

Operating line
134

-

-

-

No

-

Mo - Su

-

Missing ¦ Ready ¦ No reception ¦ Change batt

135

I

Service unit
Missing ¦ Ready ¦ No reception ¦ Change batt

138

I

Delete all devices
No ¦ Yes

Time prog heating circuit 1
500
E Preselection
Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su

501
502
503
504
505
506
516

E
E
E
E
E
E
E

1st phase on
1st phase off
2st phase on
2st phase off
3st phase on
3st phase off
Default values

6:00
22:00
24:00
24:00
24:00
24:00
No

00:00
00:00
00:00
00:00
00:00
00:00

24:00
24:00
24:00
24:00
24:00
24:00

hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
-

No ¦ Yes

Time prog heating circuit 2
520
E Preselection

Mo - Su

-

Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su

521
522
523
524
525
526
536

E
E
E
E
E
E
E

1st phase on
1st phase off
2st phase on
2st phase off
3st phase on
3st phase off
Default values

6:00
22:00
24:00
24:00
24:00
24:00
No

00:00
00:00
00:00
00:00
00:00
00:00

24:00
24:00
24:00
24:00
24:00
24:00

hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
-

No ¦ Yes

Time program 3 / HCP
540
E Preselection

Mo - Su

-

Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su

541
542
543
544
545
546
556

E
E
E
E
E
E
E

1st phase on
1st phase off
2st phase on
2st phase off
3st phase on
3st phase off
Default values

6:00
22:00
24:00
24:00
24:00
24:00
No

00:00
00:00
00:00
00:00
00:00
00:00

24:00
24:00
24:00
24:00
24:00
24:00

hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
-

No ¦ Yes

Time program 4 / DHW
560
E Preselection

Mo - Su

-

Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa
¦Su

561
562
563
564
565
566

E
E
E
E
E
E

1st phase on
1st phase off
2st phase on
2st phase off
3st phase on
3st phase off

6:00
22:00
24:00
24:00
24:00
24:00

00:00
00:00
00:00
00:00
00:00
00:00

24:00
24:00
24:00
24:00
24:00
24:00

hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
hh:mm
5/26

Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

-

Periode 1

-

Unit

No

Max

Default values

Minimum

Default value

User level
E

Function

Operating line
576

No ¦ Yes

Holidays heating circuit 1
641
E Preselection
Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8

642
643
648

E
E
E

Start
End
Operating level

--.-01.01
--.-01.01
Frost protection

31.12
31.12

dd.mm
dd.mm
-

Frost protection ¦ Reduced

Holidays heating circuit 2
651
E Preselection

Periode 1

-

Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8

652
653
658

E
E
E

Start
End
Operating level

--.-01.01
--.-01.01
Frost protection

31.12
31.12

dd.mm
dd.mm
-

Frost protection ¦ Reduced

Holidays heating circuit P
661
E Preselection

Periode 1

-

Period 1 ¦ Period 2 ¦ Period 3¦ Period 4¦ Period 5¦ Period
6¦ Period 7¦ Period 8

662
663
668

E
E
E

Start
End
Operating level

--.-01.01
--.-01.01
Frost protection

31.12
31.12

dd.mm
dd.mm
-

20.0
16
10.0
35.0
1.50
0.0
Off

BZ 712
BZ 714
4
BZ 710
0.10
-4.5

BZ 716
BZ 710
BZ 712
35
4.00
4.5

°C
°C
°C
°C
°C
-

18
−−−/8
-3
− − − / -10
8
8
80
BZ 740
20
−−−/0
−−−
− − − / 0.5
5
−−−/0
Down to reduced setpoint

30
10
BZ 741
95
100
4
20

°C
°C
°C
°C
%
°C
°C
-

0
0
−−−
-15
On

0
0
− − − / -30
-30

360
360
10
BZ 800

min
min
°C
°C
-

10

0

50

°C

Frost protection ¦ Reduced

Heating circuit 1
710
E Comfort cooling setpoint
712
E Reduced setpoint
714
E Frost protection setpoint
716
F Comfort setpoint max
720
E Heating curve slope
721
F Heating curve displacement
726
F Heating curve adaption
Off ¦ On

730
732
740
741
750
760
770
780

E
F
I
I
F
F
F
F

Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
Room influence
Room temp limitation
Boost heating
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint

790
791
800
801
820

F
F
F
F
F

Optimum start control max
Optimum stop control max
Reduced setp increase start
Reduced setp increase end
Overtemp prot pump circuit

830

F

Mixing valve boost

Off ¦ On

6/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Default value

3-position

Unit

Function
Actuator:type

Max

User level
F

Minimum

Operating line
832

-

2-position ¦ 3-position

833
834
835
836
850

F
F
O
O
I

Switching differential 2-pos
Actuator: running time
Mixing valve Xp
Mixing valve Tn
Floor curing function

2
120
32
120
Off

0
30
1
10

20
873
100
873

°C
s
°C
s
-

95

°C

BZ 1012
BZ 1014
4
BZ 1010
0.10
-4.5

BZ 1016
BZ 1010
BZ 1012
35
4.00
4.5

°C
°C
°C
°C
°C
-

18
−−−/8
-3
− − − / -10
8
8
80
BZ 1040
20
−−−/0
−−−
− − − / 0.5
5
−−−/0
Down to reduced setpoint

30
10
BZ 1041
95
100
4
20

°C
°C
°C
°C
%
°C
°C
-

0
0
−−−
-15
On

360
360
10
BZ 1100

min
min
°C
°C
-

10
0
3-position

50

°C
-

2
120
32
120
Off

20
873
100
873

°C
s
°C
s
-

Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually

851
861

I
F

Floor curing setp manually
Excess heat draw

25
0
Always

Off ¦ Heating mode ¦ Always

872

F

With prim contr/system pump

Yes

No ¦ Yes

900

I

Optg mode changeover

Protection

Protection ¦ Recuced

Heating circuit 2
1010 E Comfort cooling setpoint
1012 E Reduced setpoint
1014 E Frost protection setpoint
1016 F Comfort setpoint max
1020 E Heating curve slope
1021 F Heating curve displacement
1026 F Heating curve adaption

20.0
16
10.0
35.0
1.50
0.0
Off

Off ¦ On

1030
1032
1040
1041
1050
1060
1070
1080

E
F
I
I
F
F
F
F

Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
Room influence
Room temp limitation
Boost heating
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint

1090
1091
1100
1101
1120

F
F
F
F
F

Optimum start control max
Optimum stop control max
Reduced setp increase start
Reduced setp increase end
Overtemp prot pump circuit

1130
1132

F
F

Mixing valve boost
Actuator:type

1133
1134
1135
1136
1150

F
F
O
O
F

Switching differential 2-pos
Actuator: running time
Mixing valve Xp
Mixing valve Tn
Floor curing function

0
0
− − − / -30
-30

Off ¦ On

2-position ¦ 3-position

0
30
1
10

Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually

7/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Default value

25
0
Always

1172

F

With prim contr/system pump

Unit

Function
Floor curing setp manually
Excess heat draw

Max

User level
F
F

Minimum

Operating line
1151
1161

95

°C

Off ¦ Heating mode ¦ Always

Yes

No ¦ Yes

1200

I

Optg mode changeover

Protection

Protection ¦ Recuced

Heating circuit P
1300 E Operating mode

Automatic

-

Protection ¦ Automatic ¦ Reduced ¦ Comfort

1310
1312
1314
1316
1320
1321
1326

E
E
E
F
E
F
F

1330
1332
1340
1341
1350
1360
1370
1380

E
F
F
F
F
F
F
F

Comfort cooling setpoint
Reduced setpoint
Frost protection setpoint
Comfort setpoint max
Heating curve slope
Heating curve displacement
Heating curve adaption

20.0
16
10.0
35.0
1.50
0.0
Off

BZ 1012
BZ 1014
4
BZ 1010
0.10
-4.5

BZ 1016
BZ 1010
BZ 1012
35
4.00
4.5

°C
°C
°C
°C
°C
-

18
−−−/8
-3
− − − / -10
8
8
80
BZ 1040
20
−−−/0
−−−
− − − / 0.5
5
−−−/0
Down to reduced setpoint

30
10
BZ 1041
95
100
4
20

°C
°C
°C
°C
%
°C
°C
-

0
0
−−−
-15
On

360
360
10
BZ 1100

min
min
°C
°C
-

Off ¦ On

Summer/winter heating limit
24-hour heating limit
Flow temp setpoint min
Flow temp setpoint max
Room influence
Room temp limitation
Boost heating
Quick setback
Off ¦ Down to reduced setpoint ¦ Down to frost prot
setpoint

1390
1391
1400
1401
1420

F
F
F
F
F

Optimum start control max
Optimum stop control max
Reduced setp increase start
Reduced setp increase end
Overtemp prot pump circuit

0
0
− − − / -30
-30

Off ¦ On

1450

I

Floor curing function

Off

-

Off ¦ Functional heating ¦ Curing heating ¦
Functional/curing heating¦ Manually

1451
1455
1456
1461

I
F
F
F

Floor curing setp manually
Floor curing setp current
Floor curing day current
Excess heat draw

25
0
0
0
0
0
Always

95
95
32

°C
°C
°C

BZ 1614 OEM
BZ 1610
80

°C
°C
°C
-

Off ¦ Heating mode ¦ Always

1172

F

With prim contr/system pump

Yes

No ¦ Yes

1500

I

Optg mode changeover

Protection

Protection ¦ Recuced

Domestic hot water
1610 E Nominal setpoint
1612 F Reduced setpoint
1614 O Nominal setpoint max
1620 I
Release

55
BZ 1612
40
8
65
8
Time programs HCs

24h/day ¦ Time programs HCs ¦ Time program 4/DHW
8/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Default value

MC shifting, PC absolute

Unit

Function
Charging priority

Max

User level
I

Minimum

Operating line
1630

-

Fixed weekday

-

Absolute ¦ Shifting ¦ None ¦ MC shifting, PC absolute

1640

F

Legionella function
Off ¦ Periodically ¦ Fixed weekday

1641
1642

F
F

Legionella funct periodically
Legionella funct weekday

3
1
Montag

7

Days

−−−
65
30
On

23:50
95
360

hh:mm
°C
min
-

Monday ¦ Tuesday ¦ Wednesday ¦ Thursday ¦ Friday ¦
Saturday ¦ Sunday

1644
1645
1646
1647

F
F
F
F

1660

F

Legionella funct time
Legionella funct setpoint
Legionella funct duration
Legionella funct circ pump

− − − / 00:00
55
− − − / 10

Off ¦ On

Release of the circulating pump

DHW release

-

On

-

Time program 3/HCP ¦ DHW release ¦ Time program
4/DHW

1661

F

Circulating pump cycling
Off ¦ On

1663 F Circulaton setpoint
Pump H1/H2
2008 O H1 DHW charging priority

45

8

80

°C

Yes

No ¦ Yes

2010

F

H1 Excess heat draw

On

Off ¦ On

2014

F

H1 prim contr/system pump

Yes

-

No ¦ Yes

2033

O

H2 DHW charging priority

Yes

No ¦ Yes

2035

F

H2 Excess heat draw

On

Off ¦ On

2039

F

H2 prim contr/system pump

Yes

-

No ¦ Yes

Primary controller / system pump
2110 O Flow temp setpoint min
2111 O Flow temp setpoint max
2130 O Mixing valve boost
2132 O Actuator:type

8
8
80
8
10
0
3-position

95
95
50

°C
°C
°C

2-position ¦ 3-position

2133
2134
2135
2136
Solar
3810
3811
3812
3830
3831
3840
3850
3860

O
O
O
O

Switching differential 2-pos
Actuator: running time
Mixing valve Xp
Mixing valve Tn

2
120
32
120

0
30
1
10

20
873
100
873

°C
°C
°C
°C

F
F
F
F
F
F
F
F

Temp diff on
Temp diff off
Charg temp min DHW st tank
Collector start function
Min run time collector pump
Collector frost protection
Collector overtemp prot
Evaporation heat carrier

8
4
−−−
−−−
60
−−−
−−−
−−−

BZ 3811
0
−−−/8
−−−/5
5
− − − / -20
− − − / 30
− − − / 60

40
BZ 3812
95
60
120
5
200
200

°C
°C
°C
min
s
°C
°C
°C

9/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Max

Unit

Minimum

Default value

Function

User level

Operating line

DHW storage tank
5010 O Charging

16
0
With B3/B31

30

°C

5
0
150
− − − / 10
Automatic

20
600

°C
min

80
90
60
Off

BZ 5051 OEM
95
95

°C
°C
°C
-

Several times / day

Once/day ¦ Several times/day

5020
5022

F
F

Increase of the flow temperature setpoint
Type of charging

5024
5030
5040

O
O
O

Switching diff
Charging time limitation
Discharging protection

5050
5051
5055
5056

F
O
F
F

Charging temp max
Storage tank temp max
Recooling temp
Recooling heat gen/HCs

5057

F

Recooling collector

With B3 ¦ With B3/B31 ¦ With B3, legio B3/B31

Off ¦ Always ¦ Automatically

8
8
8

Off ¦ On

Off

-

Substitute

-

DHW release

-

DHW sensor

-

Off ¦ Summer ¦ Always

5060

F

Electric immersion heater:operating mode
Substitute ¦ Summer ¦ Always

5061

F

Electric immersion heater:release
24h/day ¦ DHW release¦ Time program4/ DHW

5062

F

El immersion heater control
External thermostat ¦ DHW sensor

5070

O

Automatic push

On

Off ¦ On

5085

F

Excess heat draw

On

-

Off ¦ On

5092

F

With prim contr/system pump

No

No ¦ Yes

5093

F

With solar integration

Yes

No ¦ Yes

Configuration
5710 I
Heating circuit 1

On

-

On

-

Sensors

-

charging pump

-

None

-

None

-

None

-

Off ¦ On

5715

I

Heating circuit 2
Off ¦ On

5730

I

DHW sensor B3
Sensor ¦ Thermostat

5731

I

DHW controlling element Q3
None ¦ Charging pump ¦ Diverting valve

5890

I

Relay output QX1
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14

5930

I

Sensor input BX1
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39

5931

I

Sensor input BX2
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39

10/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Function input H1
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦
Error/alarm message ¦ Min flow temp setpoint ¦ Excess
heat discharge

5951

I

Contact type H1

Unit

Max

Minimum

Default value

User level
I

Function

Operating line
5950

Optg mode change
HCs+DHW

-

NO contact

-

NC ¦ NO

5952
5954
5956
5960

I
I
I
I

Min flow temp setpoint H1
Heat request 10V H1
Pressure value 3.5V H1
Function input H2
Optg mode change HCs+DHW ¦ Optg mode changeover
HCs ¦ Optg mode changeover HC1 ¦ Optg mode
changeover HC2 ¦ Optg mode changeover HCP ¦ Heat
generation lock ¦ Error/alarm message ¦ Min flow temp
setpoint ¦ Heat request ¦ Pressure measurement

5961

I

Contact type H2

70
8
100
5
5.0
0.0
Optg mode change
HCs+DHW

120
130
10.0

NO contact

°C
°C
bar
-

-

NC ¦ NO

5962
6014

I
I

Min flow temp setpoint H2
Function mixing group 1

70
8
Heating circuit

120

°C
-

Heating circuit ¦ Prim contr/system pump

6020

I

Function extension module 1

No function

-

No function

-

None ¦ Multi-functional ¦ Heating circuit ¦ Solar DHW ¦
Prim contr/system pump

6021

I

Function extension module 2
None ¦ Multi-functional ¦ Heating circuit ¦ Solar DHW ¦
Prim contr/system pump

6097

F

Sensor type collector

NTC

NTC 10k ¦ Platinum 1000

6030

I

Relay output QX21

None

-

None

-

None

-

None

-

None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14

6031

I

Relay output QX22
None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦
Collector pump Q5 ¦ H1 pump Q15 ¦ Alarm output K10 ¦
2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22
¦ 2nd pump speed HCP Q23 ¦ Heat circuit pump HCP
Q20 ¦ H2 pump ¦ Q18 primary pump Q14

6040

I

Sensor input Bx21
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39

6041

I

Sensor input BX22
None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ DHW
circulation sensor B39

Sensor type collector

6097

NTC

NTC 10k ¦ Platinum 1000

6098
6100
6110
6112
6120

F
F
F
O
F

Readjustm collector sensor
Readjustm outside sensor
Time constant building
Gradient room model
Frost protection plant

0
0.0
15
60
On

-20
-3.0
0
0

20
3.0
50
300

°C
°C
h
min/°C
-

Off ¦ On

6200

I

Saving sensors

No

-

No ¦ Yes
11/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Default value
No

Unit

Function
Save parameters

Max

User level
O

Minimum

Operating line
6204

No ¦ Yes

6205

F

Reset to default parameters

No

-

No ¦ Yes

6212
6215
6217
6220
6222
LPB
6600
6601
6604

I
I
I
F
O

Check no heat source 1
Check no storage tank
Check no heating circuits
Software version
Device hours run

0

0
0
0
0
0

I
F
F

Device address
Segment address
Bus power supply function

1
0
0
0
Automatic

199999
199999
199999
99.9
500 000

h

16
14

-

Off ¦ Automatically

6605

F

Bus power supply state

On

-

Off ¦ On

6610

O

Display system messages

Yes

No ¦ Yes

6612

O

Alarm delay

No

No ¦ Yes

6620

O

Action changeover functions

System

-

Local

-

All heating circuits in the
system
Autonomous

-

Segment ¦ System

6621

F

Summer changeover
Locally¦ Centrally

6625

F

DHW assignment
Local HCs ¦ All HCs in segment ¦ All HCs in system

6640

I

Clock mode

-

Autonomously ¦ Slave without remote ¦ Slave with
remote setting ¦ Master

6650
Error
6710

F

Outside temp source

0

I

Reset:alarm relay

No

0

239

-

No ¦ Yes

6740
6741
6800
6802
6804
6806
6808
6810
6812
6814

F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F

Flow temp 1 alarm
Flow temp 2 alarm
History 1
Error code 1
History 2
Error code 1
History 3
Error code 1
History 4
Error code 1
History 5
Error code 1
History 6
Error code 6
History 7
Error code 7
History 8
Error code 8

−−−
−−−
-

− − − / 10
− − − / 10

240
240

min
min

0

255

-

0

255

-

0

255

-

0

255

-

0

255

-

0

255

-

0

255

-

0

255

-

12/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

No

Unit

History 9
Error code 9
History 10
Error code 10
Reset history

Max

F
F
F
F
O

Minimum

Default value

6820

Function

6818

User level

Operating line
6816

0

255

-

0

255

-

No ¦ Yes

Maintenance/service
7140 E manual control

Off

-

Off ¦ On

7150 I
Simulation outside temp
7170 I
Telephone customer service
Input/output test
7700 I
Relay test

-

-50.0

50

No test

°C
-

No test ¦ Everything off ¦ DHW pump Q3 ¦ Heating circuit
pump Q2 ¦ Heat circ mix valve op Y1 ¦ Heat circ mix
valve cl Y2 ¦ Relay output QX1 ¦ Relay output QX21
module 1 ¦ Relay output QX22 module 1 ¦ Relay output
QX23 module 1¦ Relay output QX21 module 2 ¦ Relay
output QX22 module 2 ¦ Relay output QX23module 2

7730
7732
7750
7820
7821
7830
7831
7832
7833
7841

I
I
I
I
I
I
I
I
I
I

Outside temp B9
Flow temp B1
DHW temp B3
Sensor temp BX1
Sensor temp BX2
Sensor temp BX21 module 1
Sensor temp BX22 module 1
Sensor temp BX21 module 2
Sensor temp BX22 module 2
Contact state H1

0
0
0
0
Open

-50.0
0.0
0.0
-28.0
-28.0
-28
-28
-28
-28

50
140
140
350
350
350
350
350
350

°C
°C
°C
°C
°C
°C
°C
°C
°C
-

Open ¦ Closed

7846

I

Contact state H2

Open

-

-

-

Open ¦ Closed

Status:
8000 I
State heating circuit 1
8001 I
State heating circuit 2
8002 I
State heating circuit P
8003 I
State DHW
8007 I
State solar
Diagnostics heat source
8510 I
Collector temp 1
8511 I
Collector temp 1 max
8512 I
Collector temp 1 min
8513 I
dT collector 1/DHW
8514 I
dT collector 1/buffer
8530 F Hours run solar yield
8531 F Hours run collect overtemp
Diagnostics consumers
8700 I
Outside temperature
8703 I
Outside temp attenuated
8704 I
Composite outside temperature

0
0
-

-28.0
-28.0
-28.0
-28.0
-28.0
0
0

350
350
350
350
350
65535
65535

°C
°C
°C
°C
°C
h
h

-

-50.0
-50.0
-50.0

50.0
50.0
50.0

°C
°C
°C
13/26

Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

Default value
-

Unit

Function
Heating circuit pump Q2

Max

User level
I

Minimum

Operating line
8730

-

-

-

-

-

Off ¦ On

8731

I

Heat circ mix valve op Y1
Off ¦ On

8732

I

Heat circ mix valve cl Y2
Off ¦ On

8740
8741
8742
8743
8744
8760

I
I
O
I
I
I

8761

I

Room temp 1
Room setpoint 1
Room temp 1 model
Flow temp 1
Flow temp setpoint 1
Heating circuit pump Q6

-

0.0
4.0
0.0
0.0
0.0

50.0
35.0
50.0
140.0
140.0

°C
°C
°C
°C
°C
-

Off ¦ On

Heat circ mix valve op Y5

-

-

-

-

Off ¦ On

8762

I

Heat circ mix valve cl Y6
Off ¦ On

8770
8771
8772
8773
8774
8800
8801
8802
8803
8820

I
I
O
I
I
I
I
O
I
I

8830
8831
8832
8835
8930
8931
8950
8951
9000
9001
9031

I
I
I
I
I
I
I
I
I
I
I

9050

I

Room temp 2
Room setpoint 2
Room temp 2 model
Flow temp 2
Flow temp setpoint 2
Room temp P
Room setpoint P
Room temp P model
Flow temp setpoint P
DHW pump Q3

-

0.0
4.0
0.0
0.0
0.0
0.0
4.0
0.0
0.0

50.0
35.0
50.0
140.0
140.0
50.0
35.0
50.0
140.0

°C
°C
°C
°C
°C
°C
°C
°C
°C
-

-

0.0
8.0
0.0
0.0
0.0
0.0
0.0
0.0
5.0
5.0

140.0
80.0
140.0
140.0
140.0
140.0
140.0
140.0
130.0
130.0

°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
-

Off ¦ On

DHW temp 1
DHW temp setpoint
DHW temp 2
DHW circulation temp
Primary controller temp
Primary controller setpoint
Common flow temp
Common flow temperature setpoint
Flow temp setpoint H1
Flow temp setpoint H2
Relay output QX1
Off ¦ On

Relay output QX21 module 1

-

-

-

-

-

-

-

-

-

-

-

-

Off ¦ On

9051

I

Relay output QX22 module 1
Off ¦ On

9052

I

Relay output QX23 module 1
Off ¦ On

9053

I

Relay output QX21 module 2
Off ¦ On

9054

I

Relay output QX22 module 2
Off ¦ On

9055

I

Relay output QX23 module 2
Off ¦ On

14/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
Overview of OEM settings

CE1U2353en01a
22. November 2006

2

The settings in detail

2.1 Operator section
Operation and display
Line no.

Operating line

30

Data:read
No
Yes

31

Data:write
No
Yes

Data:read

The setting data of all operating levels are copied from the controller to the memory of
the operator unit. This means that previous data in the operator unit will be overwritten.

Data:write

With the exception of the data listed below, the setting data of all operating levels are
transferred from the memory of the operator unit to the connected controller. Previous
setting data in the controller will be overwritten.
The following data will not be overwritten:
Line no.

3
130
131
132
133
134
135
138
516
536
556
576
6222
6600
6601
6650

Operating line

Year
Room unit 1
Room unit 2
Outside sensor
Repeater
Operator unit
Service unit
Delete all devices
default values
default values
default values
default values
Device hours run
device address
Segment address
Outside temp source

2.2 Heating circuits
mixing valve control
HC1

835
836

Line no.
HC2 HC3P

1135
1136

Operating line

Mixing valve Xp
Mixing valve Tn

Mixing valve Xp

The proportional band defines within which change of the control variable ∆x (∆T of the
flow) the whole correcting span y (valve travel) is traversed.
The smaller the proportional band, the greater the change of the manipulated variable
∆y at a given change of the controlled variable ∆x.

Mixing valve Tn

The integral action time is the period of time the controller’s I-part would require to
produce the same change of the manipulated variable as the P-part
15/26

Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

An adjustment of the integral action time changes the valve’s rate of response.
The longer the integral action time Tn, the slower the response of the controlled
system.

2392Z08

y

1
Xp

t

Tn
x
t

@

2.3 Domestic hot water
Setpoints
Line no.

Operating line

1614

Nominal setpoint max

This operating line is used to limit the “Nominal setpoint“ (operating line 1610) at the
top.
Release
Line no.

Operating line

1620

Release
24h/day
Time programs HCs
Time program 4 / DHW

24h/day
The DHW temperature is constantly maintained at the nominal DHW setpoint,
independent of any time programs.

2371Z18

Example:

0

6

12

18

24

h

Time programs HCs
The DHW setpoint is switched between the nominal DHW setpoint and the reduced
DHW setpoint according to the heating circuits’ time programs. The first switch-on point
of each period is shifted forward in time by one hour.

16/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

2377Z16

Example:

0

5 6

12

16 17

h

24

Time program 4 / DHW
For DHW heating, time switch program 4 of the local controller is used. The set
switching times of that program are used to switch between the nominal DHW setpoint
and the reduced DHW setpoint. This way, the DHW is heated independently of the
heating circuits.

2373Z24

Example:

0

6

12

18

24

h

2.4 Pump H1/H2
pump H1
Line no.
H1
H2

2008 2033

Operating line

H1/H2 DHW charging priority
Off ¦ On

H1/H2 DHW charging
priority

When using this setting, the connected pump H1/H2 can be excluded from / included in
the effect of DHW charging priority.
In the case of a ventilation system, for example, it is thus possible to ensure a constant
supply of heat with no impact from DHW charging priority.

2.5 Primary controller / system pump
flow temperature setpoint limitations
Line no.

Operating line

2110
2111

Flow temp setpoint min
Flow temp setpoint max

Using this limitation, a temperature range for the flow temperature setpoint can be
defined. If the requested flow temperature setpoint reaches the relevant limit and the
heat request increases or decreases, the flow temperature setpoint will be maintained
at the maximum or minimum limit.

17/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

TVmax

max
TVw

2358Z09

TV

akt
TVmin
min
0

10

TVw
TVmax
Tvmin

20

30

40

50

60

70

80

90

100 °C

Current flow temperature setpoint
Flow temperature setpoint maximum
Flow temp setpoint min

mixing valve control
Line no.

Operating line

2130
2132
2133
2134
2135
2136

Mixing valve boost
Actuatortype
Switching differential 2-pos
Actuator running time
Mixing valve Xp
Mixing valve Tn

Mixing valve boost

For mixing, the actual value of the boiler flow temperature must be higher than the
required setpoint of the mixing valve flow temperature since otherwise that temperature
cannot be controlled. The controller generates the boiler temperature setpoint based on
the increase set here and the current flow temperature setpoint.

Actuator:type

Selection of the type of actuator determines the way the control action impacts the type
of mixing valve actuator used.

Switching differential 2pos

For the 2-position actuator, the 2-position switching differential must also be adapted.
This is not required when using 3-position actuators.

Actuator: running time

Setting the actuator running time for the mixing valve used.

Mixing valve Xp

The proportional band defines within which change of the control variable ∆x (∆T of the
flow) the whole correcting span y (valve travel) is traversed.
The smaller the proportional band, the greater the change of the manipulated variable
∆y at a given change of the controlled variable ∆x.

Mixing valve Tn

The integral action time is the period of time the controller’s I-part would require to
produce the same change of the manipulated variable as the P-part
An adjustment of the integral action time changes the valve’s rate of response.
The longer the integral action time Tn, the slower the response of the controlled
system.

2392Z08

y

1
Xp

t

Tn
x
t

18/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

@

2.6 DHW storage tank
Release
Line no.

Operating line

5010

Charging
Once / day
Several times / day

Charging

Selection of charging “Once/day“ or “Several times/day” is active only if DHW release is
set according to the time programs of the heating circuits.
Once / day
Release of DHW charging is given 2.5 hours before the first heat request fom the
heating circuit is received. Then, the reduced DHW setpoint applies for the whole day.

Heizprogramm
Time
program

Einmal
Once
perpro
day Tag

DHW
release
TWW-Freigabe

2.5h

In the case of continuous heating (with no setback periods), release of DHW charging
is given at 0:00. The same rule also applies if the first request for heat from the heating
circuit is received before 02:30. If a request for heat is delivered at midnight, DHW
charging is released after the first setback period, but no earlier than 2.5 hours before
midnight.
Day
Tag11

Day
Tag2 2

Day 33
Tag

Day
Tag4 4

Time
program
Heizprogramm

DHW
release
TWW-Freigabe

2.5h

0:00

24:00

2.5h

2.5h

22:00
2.5h

Several times / day
When selecting “Several times/day“, release of DHW charging is put forward in time by
1 hour against the periods of time the heating circuit calls for heat, and is then
maintained during these periods of time.
Heizprogramm
Time
program
Several times
perTag
Mehrmals
pro
day

DHW
release
TWW-Freigabe

1h

1h

Charging control

Switching diff

Line no.

Operating line

5024

Switching diff

If the DHW temperature is lower than the current setpoint minus the switching
differential set here, DHW charging will be started.
DHW charging will be terminated when the temperature reaches the current setpoint.

19/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

When DHW heating is released for the first time in a 24-hour period, forced charging
will be initiated. DHW charging is also started when the DHW temperature lies within
the switching differential, provided it does not lie less than 1 K below the setpoint.
Charging time limitation

Charging time limitation

Line no.

Operating line

5030

Charging time limitation

During DHW charging, space heating may obtain no or too little energy, depending on
the selected charging priority (operating line 1630) and the type of hydraulic circuit. For
this reason, it is often practical to set a time limit to DHW charging.
--Charging time limitation is deactivated. The DHW is heated up to the nominal setpoint,
even if space heating temporarily obtains too little heat.
10 – 600
DHW charging is stopped after the set period of time in minutes and then locked for the
same time before it is resumed. During this period of time, the heat produced by the
boiler is made available for space heating. This cycle is repeated until the nominal
DHW setpoint is reached.
When space heating is switched off (summer operation, Eco function, etc.), DHW
charging will not be stopped, independent of the selected setting.

Discharging protection

Discharging protection

Line no.

Operating line

5040

Discharging protection

This function ensures that the DHW charging pump (Q3) will be activated only when the
boiler temperature is sufficiently high.
•

With sensor
The charging pump will be activated only when the boiler temperature reaches the
level of the DHW temperature plus half the charging boost. If, during charging, the
boiler temperature drops to a level below the DHW temperature plus 1/8 the
charging boost, the charging pump will be deactivated again. If 2 DHW sensors are
parameterized for DHW charging, the lower temperature is used for the discharging
protection function (usually sensor B31).

•

With thermostat
The charging pump will be activated only when the boiler temperature lies above
the nominal DHW setpoint. If, during charging, the boiler temperature drops below
the nominal DHW temperature minus the DHW switching differential, the charging
pump will be deactivated again.

Off
Function is deactivated.
Always
The function is always active.
Automatic
The function is active only if the heat source is unable to deliver heat, or is not available
(fault, heat generation lock).

20/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

Overtemperature protection

Storage tank temp max

Line no.

Operating line

5051

Storage tank temp max

If the storage tank reaches the maximum storage tank temperature set here, the
collector pump will be deactivated. It will be released again when the storage tank
temperature drops 1 °C below the maximum storage tank temperature.
The protective collector overtemperature function can reactivate the collector pump
until the storage tank’ s safety temperature is reached.
T
TSpMax

TSp
L

2354Z10

1°C

1
0
t

TSpMax
TSp
L

Storage tank temp max (operating line 5051)
Actual value of the storage tank temperature
Storage tank charging: 1 = on, 0 = off

DHW push
Line no.

Operating line

5070

Automatic push
Off
On

Automatic push

The DHW push can be triggered either manually or automatically.
With the DHW push, the DHW is heated up once until the nominal setpoint is reached.
Off
The DHW push must be triggered manually.
On
If the DHW temperature falls below the reduced setpoint (operating line 1612) by at
least 2 switching differentials (operating line 5024), one-time charging to the nominal
DHW setpoint (operating line 1610) will take place again.
The automatic DHW push only works when the DHW operating mode is activated.

2.7 Configuration
Building and room model

Gradient room model

Line no.

Operating line

6112

Gradient room model

The room model gradient gives the period of time in minutes room heating needs to
raise the temperature by 1 °C. The setting made applies to all circuits.

21/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

The setting is used to calculate the fictive room temperature of rooms that have no
room temperature sensor installed (operating lines 8742, 8772, and 8802).
Parameters
Line no.

Operating line

6204

Save parameters

.
The current parameter settings can be saved as new standard settings. Exempted from
this are the following operating pages: Time of day and date, operator section, wireless,
and all time programs, as well as the number of operating hours and the different
counters.
Important:
With this process, the factory settings will be overwritten and can no longer be
retrieved!

Device hours run

Line no.

Operating line

6222

Device hours run

This indicates the total number of operating hours since the controller was first
commissioned.

2.8 LPB
Error / maintenance / alarms
Line no.

Operating line

6610
6612
6620

Display system messages
Alarm delay
Action changeover functions
Segment
System

Display system messages

This setting enables system messages transmitted via LPB to be suppressed at the
connected operator unit.

Alarm delay

Delivery of the alarm to the OCI can be delayed in the basic unit by setting a delay.
This ensures that unnecessary notifications of a service center resulting from short-time
errors (e.g. temperature limiter cut out, communication error) can be prevented.
It is to be noted, however, that errors occurring for a short period of time, and
reoccurring constantly and rapidly, will also be filtered.

Range of action of changeover
The range of action of central changeover can be defined.
This applies to the following types of limitation:
• Optg mode changeover
• Summer changeover (when selecting ”Central“ on setting line 6621)
Entries:
• Segment: Changeover takes place with all controllers in the same segment.
• System: Changeover takes place with all controllers in the entire system (in all
segments). The controller must be located in segment 0!

22/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

2.9 Error
History 1...10
Line no.

Operating line

6820

Reset history
No
Yes

Reset history

The error history with the last 10 errors will be deleted.

2.10 Diagnostics consumers
Heating circuit 1,
heating circuit 2,
heating circuit P

Room temperature 1 / 2 /
P model

Line no.

Operating line

8742
8772
8802

Room temp 1 model
Room temp 2 model
Room temp P model

The room model calculates a fictive room temperature for rooms that have no room
temperature sensor. The value calculated for each heating circuit is indicated on these
operating lines.
This allows boost heating, quick setback and optimum start and stop control to be
implemented with no need for using a room temperature sensor.
The calculation takes into account the attenuated outside temperature (operating line
8703), the room model gradient (operating line 6112) for switching to a higher setpoint,
and the building’s time constant (operating line 6110) for switching to a lower setpoint.

23/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
The settings in detail

CE1U2353en01a
22. November 2006

Index
A
action changeover functions......................................22
attenuated outside temperature ................................23
Automatic push..........................................................21
B
building’s time constant .............................................23
C
charging DHW ...........................................................19
Charging time limitation.............................................20
copy settings .............................................................15
D
Data:read...................................................................15
Data:write ..................................................................15
Device hours run .......................................................22
DHW charging ...........................................................19
DHW push .................................................................21
DHW switching differential ........................................19
E
error reset..................................................................23
F
flow temp setpoint max..............................................17
flow temp setpoint min...............................................17
G
Gradient room model...........................................21, 23
H
history reset...............................................................23
hours run device........................................................22
I
integral action time ..............................................16, 18

L
limitation of charging time......................................... 20
M
maximum nominal setpoint....................................... 16
model room temperature 1 / 2 / P............................. 23
N
Nominal setpoint max ............................................... 16
O
once / day ................................................................. 19
Optimum start control ............................................... 23
optimum stop control ................................................ 23
P
proportional band................................................ 15, 18
push.......................................................................... 21
Q
quick setback / boost heating ................................... 23
R
reset
error history ......................................................... 23
room model gradient................................................. 21
room temperature model 1 / 2 / P............................. 23
S
Save parameters ...................................................... 22
Saving parameter settings........................................ 22
several times / day.................................................... 19
Summer changeover ................................................ 22
switching differential DHW........................................ 19

24/26
Siemens Schweiz AG
HVAC Products

Benutzerhandbuch
2 The settings in detail

CE1U2354de01a
22. November 2006

3

Proof of change

All changes since the last issue (see front side) are registered in the original document
(Winwordfile) with the Winwordfunktion " Highlight ".
To make these passages visible, go forward with the following key combination:
Show: Ctrl+Shift+?’
Hide: Ctrl+Shift+`
Or put the same functionality about the following Winword menu:
Menu: [Tools] - [Optionen]
Option: [Highlight]
In the Printfile (PDF) the change proof is not evident.’

25/26
Siemens Schweiz AG
HVAC Products

User Manual OEM

CE1U2353en01a
22. November 2006

Siemens Schweiz AG
Siemens Switzerland Ltd
Building Technologies Group / HVAC Products
Gubelstrasse 22
CH -6301 Zug
Tel. +41 41-724 24 24
Fax +41 41-724 35 22
www.sbt.siemens.com

© 2005-2006 Siemens Building Technologies AG
Subject to alteration

26/26
Siemens Schweiz AG
HVAC Products

User Manual OEM
3 Proof of change

CE1U2353en01a
22. November 2006



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.5
Linearized                      : No
Page Count                      : 26
Signing Authority               : Schaub Thomas
Signing Date                    : 2006:11:22 14:44:15+01:00
Signing Reason                  : I am the author of this document
Modification Permissions        : Fill forms, Create page templates, Sign
Has XFA                         : No
XMP Toolkit                     : XMP toolkit 2.9.1-14, framework 1.6
About                           : uuid:936d01f9-4be7-4df7-8d17-a72413b6163a
Producer                        : Acrobat Distiller 6.0.1 (Windows)
Create Date                     : 2006:11:22 14:19:30+01:00
Creator Tool                    : PScript5.dll Version 5.2.2
Modify Date                     : 2006:11:23 15:17:38+01:00
Metadata Date                   : 2006:11:23 15:17:38+01:00
Document ID                     : uuid:0904b819-78d4-4678-a1d4-8321ba238951
Format                          : application/pdf
Creator                         : schaubt
Title                           : Microsoft Word - 012_Albatros2_U2353en_01a.doc
Author                          : schaubt
EXIF Metadata provided by EXIF.tools

Navigation menu