Siemens S5 135U 155U Users Manual 135U/155U

S5-135U155U to the manual 6d40d426-09fc-49c4-a38f-a40c545584f5

2015-02-05

: Siemens Siemens-S5-135U-155U-Users-Manual-410326 siemens-s5-135u-155u-users-manual-410326 siemens pdf

Open the PDF directly: View PDF PDF.
Page Count: 560

DownloadSiemens Siemens-S5-135U-155U-Users-Manual- S5-135U/155U  Siemens-s5-135u-155u-users-manual
Open PDF In BrowserView PDF
Contents
Notes on Using this Manual
and on the CE Symbol

1

Centralized and Distributed
Configuration of a Programmable Controller

2

Installation Guidelines

3

Central Controllers and
Expansion Units
Power Supply Units

4

CPUs, Memory Cards,
Memory Submodules,
Interface Submodules

5

Multiprocessor Operation/
Coordinators

6

Interface Modules

7

Digital Input/Output Modules

8

Analog Input/Output Modules

9

SIMATIC
S5-135U/155U

System Manual

This manual has the
order number:

6ES5998-0SH21

Monitoring Module

10

Connector Assignments

11

Appendices
Appendix

A

Guidelines for Handling
Electrostatically-Sensitive
Devices (ESD)

B

Index
12/98
C79000-G8576-C199
Release 06

Safety Guidelines

!

#$. ()0' *)/$). )*/$ . 2#$# 4*0 .#*0' *. -1 /* ).0- 4*0- *2) + -.*)' .! /4 . 2 '' . /*
+-*/ / /# +-*0/ ) *)) /  ,0$+( )/ # . )*/$ . - #$"#'$"#/  $) /# ()0' 4  2-)$)"
/-$)"' ) - (-&  . !*''*2. *-$)" /* /# ' 1 ' *! )" -

Warning
$)$/ ./#/  /# . 1 - + -.*)' $)%0-4 *- .0./)/$' +-*+ -/4 (" ) - .0'/ $! +-*+ - +- 0/$*). )*/ /& )

Note
-2.4*0- // )/$*) /* +-/$0'-'4 $(+*-/)/ $)!*-(/$*) *) /# +-*0/ #)'$)" /# +-*0/ *- /*  +-/$0'+-/ *! /# *0( )//$*)

Qualified Personnel

#  1$ .4./ ( (4 *)'4  . / 0+ ) *+ -/  $) *)%0)/$*) 2$/# /#$. ()0'
)'4    .#*0'  ''*2  /* $)./'' ) 2*-& *) /#$. ,0$+( )/ 0'$!$  + -.*).  !$)  . + -.*). 2#* - 0/#*-$5  /* *(($..$*) /* "-*0) ) /* /" $-0$/. ,0$+( )/ ) .4.6
/ (. $) *-) 2$/# ./'$.#  .! /4 +-/$ . ) ./)-.

Correct Usage

!

*/ /# !*''*2$)"

Warning
#$.  1$ ) $/. *(+*) )/. (4 *)'4  0.  !*- /# ++'$/$*).  .-$  $) /# /'*" *- /# / #)$'
 .-$+/$*) ) *)'4 $) *)) /$*) 2$/#  1$ . *- *(+*) )/. !-*( */# - ()0!/0- -. 2#$# #1  )
++-*1  *- - *(( )  4 $ ( ).
#$. +-*0/ ) *)'4 !0)/$*) *-- /'4 ) .! '4 $! $/ $. /-).+*-/  ./*-  . / 0+ ) $)./''  *-- /'4 )
*+ -/  ) ($)/$)  . - *(( ) 

!

!
Trademarks

Caution
	  
 	  ! 

)" - *! 3+'*.$*) $! // -4 $. $)*-- /'4 - +'   +' *)'4 2$/# .( *- ,0$1' )/ /4+
- *(( )  4 /# ()0!/0- - 
$.+*. *! 0.  // -$ . *-$)" /* /# ()0!/0- -. $)./-0/$*).

Warning

   
  
		 
 		    	   
 6



	R ) 	 R ) 	 
R - - "$./ -  /- (-&. *!  
#$- +-/$ . 0.$)" !*- /# $- *2) +0-+*. . )4 */# - )( . $) /#$. *0( )/ 2#$# - ! - /* /- (-&. ($"#/
$)!-$)" 0+*) /# -$"#/. *! /# /- (-& *2) -.

Copyright E Siemens AG 1993 All rights reserved

Disclaimer of Liability

The reproduction, transmission or use of this document or its
contents is not permitted without express written authority.
Offenders will be liable for damages. All rights, including rights
created by patent grant or registration of a utility model or design, are
reserved.

We have checked the contents of this manual for agreement with the
hardware and software described. Since deviations cannot be
precluded entirely, we cannot guarantee full agreement. However,
the data in this manual are reviewed regularly and any necessary
corrections included in subsequent editions. Suggestions for
improvement are welcomed.

$ ( ). 
Bereich Automatisierungs- und Antriebstechnik
Geaschaeftsgebiet Industrie Automatisierungssysteme
Postfach 4848, D-90327 Nuernberg

Siemens Aktiengesellschaft

E Siemens AG 1993
0% / /* #)" 2$/#*0/ +-$*- )*/$ 
6ES5998-0SH21

C7-633, C7-634 Control Systems

Contents
1

2

3

Notes on Using this Manual and on the CE Symbol . . . . . . . . . . . . . . . . . . . . . . .

1-1

Notes on Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-1

Notes on the CE Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-4

Notes for Machine Manufacturers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-6

Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-7

Centralized and Distributed Configuration of a Programmable Controller . . .

2-1

2.1

Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2

2.2
2.2.1
2.2.2

Centralized and Distributed Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing a PLC with Centralized Configuration . . . . . . . . . . . . . . . . . . . . . .
Installing a PLC with Distributed Configuration . . . . . . . . . . . . . . . . . . . . . . .

2-3
2-4
2-5

2.3

Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-6

Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-1

3.1
3.1.1
3.1.2

Principles of Installation of Systems for EMC . . . . . . . . . . . . . . . . . . . . . . . .
Overview of Possible Types of Interference . . . . . . . . . . . . . . . . . . . . . . . . .
The Most Important Basic Rules for Ensuring EMC . . . . . . . . . . . . . . . . . .

3-2
3-2
3-6

3.2
3.2.1

Installation of Programmable Controllers for EMC . . . . . . . . . . . . . . . . . . . .
Basic Rules for Assembling and Grounding the Inactive Metal
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example of Cabinet Assembly for EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example of Rack and Wall Mounting for EMC . . . . . . . . . . . . . . . . . . . . . . .

3-8

3.2.2
3.2.3
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5

3-8
3-9
3-11

Wiring of Programmable Controllers for EMC . . . . . . . . . . . . . . . . . . . . . . .
Routing of Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Equipotential Bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shielding of Cables and Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Measures for Interference-Free Operation . . . . . . . . . . . . . . . . . . .
Checklist for the Electromagnetically Compatible Installation
of Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-19

3.4
3.4.1
3.4.2
3.4.3

Power Supplies for Programmable Controllers and I/Os . . . . . . . . . . . . . .
Power Supplies for Control Systems with SIMATIC S5 . . . . . . . . . . . . . . .
Connecting the Programmable Controller and Load Power . . . . . . . . . . . .
Connecting Non-Floating or Floating Modules . . . . . . . . . . . . . . . . . . . . . . .

3-20
3-20
3-21
3-26

3.5
3.5.1
3.5.2

Interference-Free
Interface Circuits
Interference-Free
Interference-Free

Installation of Centralized and Distributed
................................................
Installation of Centralized Interface Circuits . . . . . . . . .
Installation of Distributed Interface Circuits . . . . . . . . . .

3-28
3-28
3-28

3.6

Interference-Free Connection of Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-30

System Manual
C79000-G8576-C199-06

3-12
3-12
3-14
3-15
3-17

iii

Contents

3.6.1

4

5

iv

3.6.2

Interference-Free Connection of a Monitor to the CP of the S5
Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shielding and Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3-30
3-31

3.7
3.7.1
3.7.2
3.7.3
3.7.4
3.7.5

Selection and Installation of Cabinets with SIMATIC S5 . . . . . . . . . . . . . . .
Types of Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clearances in Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removal of Power Dissipation from Cabinets . . . . . . . . . . . . . . . . . . . . . . . .
Examples for Determining the Type of Cabinet . . . . . . . . . . . . . . . . . . . . . .
Determining the Power Dissipation of Modules . . . . . . . . . . . . . . . . . . . . . .

3-33
3-34
3-34
3-37
3-38
3-39

Central Controllers and Expansion Units Power Supply Units . . . . . . . . . . . . .

4-1

4.1
4.1.1
4.1.2
4.1.3
4.1.4
4.1.5

S5-135U/155U Central Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Repair Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-2
4-2
4-6
4-10
4-12
4-13

4.2
4.2.1
4.2.2
4.2.3

Expansion Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description of the Expansion Units . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Expansion Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications of the Expansion Units . . . . . . . . . . . . . . . . . . . . .

4-15
4-16
4-18
4-18

4.3
4.3.1
4.3.2
4.3.3
4.3.4
4.3.5
4.3.6

Power Supply Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting and Connecting the Power Supply Unit . . . . . . . . . . . . . . . . . . . . . .
Fault Indications/Fault Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance and Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description of Internal Sequences in the Power Supply Unit . . . . . . . . . . .
Technical Specifications of the Power Supply Units . . . . . . . . . . . . . . . . . .

4-19
4-19
4-23
4-36
4-40
4-49
4-51

4.4
4.4.1
4.4.2
4.4.3
4.4.4
4.4.5
4.4.6

6ES5 955-3NA12 Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Power Supply Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-57
4-57
4-60
4-63
4-64
4-66
4-68

4.5
4.5.1
4.5.2
4.5.3

Fan Submodules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting and Connecting the Fan Submodule . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4-70
4-70
4-72
4-74

CPUs, Memory Cards, Memory Submodules, Interface Submodules . . . . . . . .

5-1

5.1
5.1.1
5.1.2
5.1.3
5.1.4

CPU 948B -3UA13 or CPU 948B -3UA23 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interfaces of the CPU 948 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-2
5-2
5-3
5-13
5-15

5.2
5.2.1
5.2.2

CPU 948 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-17
5-17
5-18

System Manual
C79000-G8576-C199-06

Contents

5.2.3
5.2.4

Interfaces of the CPU 948 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-27
5-28

5.3
5.3.1
5.3.2
5.3.3

CPU 928B -3UB21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-30
5-30
5-33
5-40

5.4
5.4.1
5.4.2
5.4.3

CPU 928B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-42
5-42
5-45
5-52

5.5
5.5.1
5.5.2
5.5.3

CPU 928 -3UA21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-54
5-54
5-56
5-61

5.6
5.6.1
5.6.2
5.6.3

CPU 928 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-62
5-62
5-64
5-70

5.7
5.7.1
5.7.2
5.7.3

CPU 922 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-71
5-71
5-73
5-79

5.8
5.8.1
5.8.2
5.8.3

374 Flash EPROM Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-80
5-80
5-80
5-81

5.9
5.9.1
5.9.2
5.9.3

376 Memory Submodules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-82
5-82
5-82
5-83

5.10
5.10.1
5.10.2
5.10.3
5.10.4

377 Memory Submodules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RAM Submodules with Battery Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-84
5-84
5-84
5-85
5-90

5.11
5.11.1
5.11.2
5.11.3
5.11.4
5.11.5
5.11.6
5.11.7

Interface Submodules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing and Removing the Interface Submodules . . . . . . . . . . . . . . . . . . .
PG Submodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V.24 Submodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TTY Submodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS422 A/485 Submodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SINEC L1 Submodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications of the Interface Submodules . . . . . . . . . . . . . . . .

5-92
5-93
5-95
5-99
5-106
5-112
5-118
5-122

System Manual
C79000-G8576-C199-06

v

Contents

6

7

8

vi

Multiprocessor Operation/Coordinators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-1

6.1

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-2

6.2

Starting the Multiprocessor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-3

6.3

Coordinator Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-13

6.4
6.4.1
6.4.2

923A Coordinator Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings on the Coordinator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-15
6-15
6-17

6.5
6.5.1
6.5.2

923C Coordinator Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings on the Coordinator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6-18
6-18
6-23

6.6

Technical Specifications of the Coordinators . . . . . . . . . . . . . . . . . . . . . . . .

6-28

Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-1

7.1
7.1.1
7.1.2

The 300 and 312 Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indicators and Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes/Jumper Assignments of the IM 300 . . . . . . . . . . . . . . . . . . . . . . . . . .

7-2
7-4
7-5

7.2
7.2.1
7.2.2

The 301 and 310 Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indicators and Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes/Jumper Assignments of the IM 301 . . . . . . . . . . . . . . . . . . . . . . . . . .

7-9
7-10
7-11

7.3
7.3.1
7.3.2
7.3.3

The 304 and 314 Interface Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Indicators and Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes/Jumper Assignments of the IM 304 . . . . . . . . . . . . . . . . . . . . . . . . . .
Modes/Jumper Assignments of the IM 314 . . . . . . . . . . . . . . . . . . . . . . . . . .

7-13
7-14
7-15
7-17

7.4
7.4.1
7.4.2

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 721 Connecting Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 7602 Terminator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7-20
7-20
7-22

Digital Input/Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-1

8.1
8.1.1
8.1.2
8.1.3
8.1.4

Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function of the Enable Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Features of the 432 Digital Input Module . . . . . . . . . . . . . . . . . . . . .
Special Features of the DI/DQ 482 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-2
8-4
8-5
8-8
8-12

8.2
8.2.1
8.2.2
8.2.3
8.2.4
8.2.5

8-14
8-14
8-18
8-20
8-21

8.2.6
8.2.7

Installation and Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting the Module Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Inserting Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marking of Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Signal Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection of Outputs in Parallel and Switching On
the Load via a Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Short-Circuit Protection and Fusing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Arc-Quenching for Inductive Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-22
8-24
8-25

8.3

Common Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8-28

8.4
8.4.1
8.4.2

Specification Sheets for the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 420-4UA13/4UA14 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . .
6ES5 430-4UA13/4UA14 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . .

8-30
8-30
8-32

System Manual
C79000-G8576-C199-06

Contents

8.4.3
8.4.4
8.4.5
8.4.6
8.4.7
8.4.8
8.4.9
8.4.10
8.4.11
8.4.12
8.4.13
8.4.14
8.4.15
8.4.16
8.4.17
8.4.18
8.4.19
9

6ES5 431-4UA12 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 432-4UA12 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 434-4UA12 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 435-4UA12 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 436-4UA12 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 436-4UB12 Digital Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 441-4UA13/4UA14 Digital Output Module . . . . . . . . . . . . . . . . . . . . .
6ES5 451-4UA13/4UA14 Digital Output Module . . . . . . . . . . . . . . . . . . . . .
6ES5 453-4UA12 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 454-4UA13/4UA14 Digital Output Module . . . . . . . . . . . . . . . . . . . . .
6ES5 455-4UA12 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 456-4UA12 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 456-4UB12 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 457-4UA12 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 458-4UA12 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 458-4UC11 Digital Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6ES5 482-4UA11 Digital Input/Output Module . . . . . . . . . . . . . . . . . . . . . . .

8-34
8-36
8-39
8-42
8-44
8-46
8-48
8-50
8-52
8-54
8-56
8-58
8-60
8-62
8-64
8-67
8-69

Analog Input/Output Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-1

9.1

Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-2

9.2

Common Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-3

9.3
9.3.1
9.3.2
9.3.3
9.3.4
9.3.5
9.3.6
9.3.7
9.3.8
9.3.9
9.3.10
9.3.11
9.3.12
9.3.13
9.3.14
9.3.15

The 460 Analog Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function of the Enable Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Features of the 460 Analog Input Module . . . . . . . . . . . . . . . . . . . .
Setting the Module Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Inserting Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marking of Modules and Front Connectors . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Signal Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection of Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting a Compensating Box for Thermal E.M.F. Measurement . . . .
Connecting Resistance Thermometers in the Standard Pt 100 Range . .
Connecting Resistance Thermometers in the Extended Pt 100 Range . .
Broken Wire Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measured-Value Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-4
9-4
9-4
9-8
9-10
9-13
9-15
9-16
9-17
9-19
9-20
9-21
9-22
9-23
9-24
9-29

9.4
9.4.1
9.4.2
9.4.3
9.4.4
9.4.5
9.4.6
9.4.7
9.4.8
9.4.9

The 463 Analog Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function of the Enable Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Features of the 463 Analog Input Module . . . . . . . . . . . . . . . . . . . .
Setting the Module Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Inserting Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marking of Modules and Front Connectors . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Signal Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measured-Value Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-35
9-35
9-35
9-39
9-39
9-42
9-44
9-45
9-46
9-47

9.5
9.5.1
9.5.2

The 465 Analog Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function of the Enable Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-50
9-50
9-50

System Manual
C79000-G8576-C199-06

vii

Contents

10

viii

9.5.3
9.5.4
9.5.5
9.5.6
9.5.7
9.5.8
9.5.9
9.5.10
9.5.11
9.5.12
9.5.13

Special Features of the 465 Analog Input Module . . . . . . . . . . . . . . . . . . . .
Setting the Module Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Inserting Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marking of Modules and Front Connectors . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Signal Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting a Compensating Box for Thermal E.M.F. Measurement . . . .
Connecting Resistance Thermometers to the 465 Analog Input Module .
Broken Wire Signal for Resistance Thermometers . . . . . . . . . . . . . . . . . . .
Connecting Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Measured-Value Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-54
9-56
9-59
9-61
9-62
9-63
9-64
9-66
9-67
9-68
9-72

9.6
9.6.1
9.6.2
9.6.3
9.6.4
9.6.5
9.6.6
9.6.7
9.6.8
9.6.9

The 466 Analog Input Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Features of the 466 Analog Input Module . . . . . . . . . . . . . . . . . . . .
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Inserting Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marking of Modules and Front Connectors . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Signal Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting Sensors to the 466 Analog Input Module . . . . . . . . . . . . . . . . .
Measured-Value Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-77
9-77
9-77
9-77
9-84
9-86
9-87
9-88
9-91
9-95

9.7
9.7.1
9.7.2
9.7.3
9.7.4
9.7.5
9.7.6
9.7.7
9.7.8
9.7.9
9.7.10

The 470 Analog Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function of the Enable Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special Features of the 470 Analog Output Module . . . . . . . . . . . . . . . . . .
Setting the Module Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Inserting Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Marking of Modules and Front Connectors . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Signal Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting Loads to the 470 Analog Output Module . . . . . . . . . . . . . . . . .
Measured-Value Representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-98
9-98
9-98
9-102
9-102
9-105
9-107
9-108
9-109
9-111
9-112

Monitoring Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-1

10.1
10.1.1
10.1.2
10.1.3
10.1.4
10.1.5

Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mode of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-2
10-2
10-3
10-3
10-4
10-5

10.2
10.2.1
10.2.2
10.2.3
10.2.4
10.2.5

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Possible Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing and Inserting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the RESET Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switch Positions of the Relay Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10-6
10-6
10-6
10-7
10-7
10-7

10.3
10.3.1
10.3.2
10.3.3

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-8
Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-10
Setting the Address Switches S1, S2, S3, S4 . . . . . . . . . . . . . . . . . . . . . . . 10-12
Setting the Switch S5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-13

System Manual
C79000-G8576-C199-06

Contents

10.4

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-14

10.5

Address Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-16

11

Connector Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

11-1

A

Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A-1

B

Guidelines for Handling Electrostatically Sensitive Devices (ESD) . . . . . . . . .

B-1

B.1

What is ESD? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-2

B.2

Electrostatic Charging of Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B-3

B.3

General Protective Measures Against Electrostatic Discharge Damage .

B-4

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-1

System Manual
C79000-G8576-C199-06

ix

Contents

x

System Manual
C79000-G8576-C199-06

1

Notes on Using this Manual
and on the CE Symbol
Notes on Using this Manual

The S5-135U/155U PLC is a member of the family of SIMATIC S5
programmable (logic) controllers. The controller can be used in single and in
multiprocessor operation with up to four CPUs. In multiprocessor operation,
each CPU processes its individual user program independently of the other
CPUs (multicomputing).

CPUs Available

The following are available as CPUs:

for fast word and binary signal processing especially
fast double-word and floating point processing and for
large programs with a high storage requirement;
programming in STEP 5.
When you use a CPU 948 you have an S5-155U PLC.

CPU 948

CPU 928B

for fast word and binary signal processing and for
communication; programming in STEP 5.

CPU 928

for fast binary signal processing and for word
processing; programming in STEP 5.

CPU 922
(R processor)

Slots

System Manual
C79000-G8576-C199-06

for word processing (computing controlling
monitoring signaling); programming in STEP 5.

You can combine the CPUs arbitrarily at the CPU slots in the central
controller:
CPU

Slot Requirement

CPU 948/CPU 928B/CPU 928

2 slots

CPU 922/CPU 928-3UA21/
CPU 928B-3UB21
CPU 948B-3UA13/ -3UA23

1 slot

1-1

Notes on Using this Manual and on the CE Symbol

How the Manual is
Organized

Given as a guide in the following are pointers on how this manual is
organized; they will assist you when using your S5-135U/155U
programmable controller.
At the start of this manual you will find the “Safety-Related Guidelines”
and the “ESD Guidelines.” You must observe these to the letter and
follow them during the entire time you are working with the
S5-135U/155U PLC. If your PLC requires repair, you must observe the
Repair Guidelines in Section 4.1.4.
Chapter 3 contains the Installation Guidelines with information on
interference-free installation of the S5-135U/155U PLC.
Which of the remaining chapters of this manual you may require when
working with your PLC will depend on the extent of your automation task
and on the configuration of your PLC.
For a basic configuration in single-processor operation without expansion
units, you will need the following chapters:
Chapter 4 describes the central controller (CC) in Section 4.1. Described
are the technical features, installation, startup and maintenance of the CC.
Section 4.3 describes the power supply units. You will find a separate
description of the 6ES5 955-3NA12 power supply unit in Section 4.5.
Both sections describe the installation and startup as well as the necessary
maintenance on the power supply units. The 24 V/4 A load power supply
is described in Section 4.4.
Chapter 5 contains the instructions for the individual CPUs. Described
here are the technical features, installation and startup of the individual
CPUs. The various methods of operating the CPUs are also described, as
are the CPU statuses where they can be directly indicated by the LEDs on
the module. If you use memory submodules or memory cards (CPU 948),
you can look up the necessary information in Sections 5.7 to 5.9.
Chapter 8 and Chapter 9 describe the digital and analog I/O modules.
Described here are the installation, wiring and operation of these
modules. Individual I/O modules exhibit specific features which are
discussed in separate chapters.
To configure your PLC with expansion units (EUs) you will need the
following chapters:
Chapter 2 shows how you can configure a PLC with expansion units in a
centralized or distributed arrangement.
Described in Chapter 4, Section 4.2, are the EU 183U, EU 184U, EU
185U and EU 187U. Those EUs which operate with their own power
supply unit are described in Section 4.3.
Chapter 7 describes the interface modules (IMs) which serve for data
communication between central controllers and expansion units.

1-2

System Manual
C79000-G8576-C199-06

Notes on Using this Manual and on the CE Symbol

To operate two or more CPUs in multiprocessor mode in your PLC, you will
need Chapter 6.
Chapter 6 describes multiprocessor operation. This chapter contains all
the measures you must take for startup of the PLC in multiprocessor
operation. Described in Sections 6.5 and 6.6 are the 923C and 923A
coordinators.
In Chapter 11 are the connector assignments of the individual modules and
subracks.
The Appendix contains the ordering data for the products described in this
manual, references to further reading and the index of keywords in this
manual.

System Manual
C79000-G8576-C199-06

1-3

Notes on Using this Manual and on the CE Symbol

Notes on the CE Symbol

EC Directive on
EMC 89/336/EEC

The following applies to the SIMATIC products described in this manual:
Products which carry the CE symbol fulfil the requirements for the EC
Directive 89/336/EEC on “electromagnetic compatibility.”
The EC declarations of conformity and the documentation relating to this are
available to the authorities concerned, according to the above EC Directive,
Article 10 (2), from:
Siemens Aktiengesellschaft
Automation Group
A&D AS E48
Postfach 1963
D-92209 Amberg
Products which do not carry the CE symbol meet the requirements and
standards given in this manual under the respective “Technical
Specifications” sections.

Fields of
Application

For SIMATIC S5, the following fields of application apply according to this
CE symbol:

Field of Application

Requirement for
Emitted Interference

Industry

EN 50081-2: 1993

Noise Immunity
EN 50082-2: 1995

Observing the
Installation
Guidelines

The installation guidelines and safety-related guidelines given in this manual
must be observed during startup and when operating SIMATIC S5 devices.
Moreover, the following rules must be observed when using certain modules.

Installing the
Devices

Programmable controllers of the type SIMATIC S5-135U/S5-155U must be
installed in metal cabinets according to these installation guidelines.

Working on
Cabinets

To protect the modules from static discharge, the user must discharge his
body’s electrostatic charge before opening a cabinet.

1-4

System Manual
C79000-G8576-C199-06

Notes on Using this Manual and on the CE Symbol

Notes on
Individual Modules

Additional measures are required when using the following modules.

A shielded signal cable is required for the following modules:
Order Number

Module

6ES5 432-4UA12

Digital input module 432

6ES5 453-4UA12

Digital output module 453-4

6ES5 457-4UA12

Digital output module 457-4

6ES5 482-4UA12

Digital I/O module 482-4 for IP 257

A filter (SIFI C B841213-C-B30 or equivalent) is required in the 230 V AC load voltage supply
for the following modules:
Order Number

Module

6ES5 436-4UA12

Digital input module 436-4

6ES5 436-4UB12

Digital input module 436-4

6ES5 456-4UA12

Digital output module 456-4

6ES5 456-4UB12

Digital output module 456-4

A filter (SIFI C, B841213-C-B30 or equivalent) is required in the 24 V DC load voltage supply
for the following modules:
Order Number

Module

6ES5 261-4UA11

Proportioning module IP 261

6ES5 432-4UA12

Digital input module 432

6ES5 453-4UA12

Digital output module 453-4

6ES5 457-4UA12

Digital output module 457-4

6ES5 465-4UA12

Analog input module 465-4

6ES5 470-4UB12

Analog output module 470-4

System Manual
C79000-G8576-C199-06

1-5

Notes on Using this Manual and on the CE Symbol

Notes for Machine Manufacturers

Introduction

The SIMATIC programmable controller is not a machine in the sense of the
EC Directive on machines. Therefore, there is no declaration of conformity
for SIMATIC as regards the EC Directive 89/392/EEC on machines.

EC Directive
89/392/EEC on
Machines

The EC Directive 89/392/EEC on machines controls machine requirements.
Here, a machine is understood to be the entire sum of devices or parts
involved (see also EN 292-1, paragraph 3.1).
SIMATIC is part of the electrical equipment for a machine and must
therefore be included in the procedure for checking conformity by the
machine manufacturer.

Electrical
Equipment for
Machines to EN
60204

EN 60204-1
Para. 4

The EN 60204-1 standard (machine safety, general requirements for the
electrical equipment for machines) applies to the electrical equipment for
machines.
The following table should help you with the declaration of conformity and
shows which criteria apply to EN 60204-1 (as at June 1993) for SIMATIC.
Subject/Criterion
General requirements

Remarks
Requirements are fulfilled if the machines are
assembled/installed according to the
installation guidelines.
See also the explanations on the previous
pages.

Para. 11.2

Digital I/O interfaces

Requirements are fulfilled.

Para. 12.3

Programmable equipment

Requirements are fulfilled if the machines are
installed in lockable cabinets to protect them
from memory modifications by unauthorized
persons.

Para. 20.4

Voltage tests

Requirements are fulfilled.

1-6

System Manual
C79000-G8576-C199-06

Notes on Using this Manual and on the CE Symbol

Safety Notes
Risks Involved in the Use of So-Called SIMATIC-Compatible Modules of
Non-Siemens Manufacture
“The manufacturer of a product (SIMATIC in this case) is under the general
obligation to give warning of possible risks attached to his product. This
obligation has been extended in recent court rulings to include parts supplied
by other vendors. Accordingly, the manufacturer is obliged to observe and
recognize such hazards as may arise when a product is combined with
products of other manufacture.
For this reason, we feel obliged to warn our customers who use SIMATIC
products not to install so-called SIMATIC-compatible modules of other
manufacture in the form of replacement or add-on modules in SIMATIC
systems.
Our products undergo a strict quality assurance procedure. We have no
knowledge as to whether outside manufacturers of so-called
SIMATIC-compatible modules have any quality assurance at all or one that is
nearly equivalent to ours. These so-called SIMATIC-compatible modules are
not marketed in agreement with Siemens; we have never recommended the
use of so-called SIMATIC-compatible modules of other manufacture. The
advertising of these other manufacturers for so-called SIMATIC-compatible
modules wrongly creates the impression that the subject advertised in
periodicals, catalogs, or at exhibitions had been agreed with us. Where
so-called SIMATIC-compatible modules of non-Siemens manufacture are
combined with our SIMATIC automation systems, we have a case of our
product being used contrary to recommendations. Because of the variety of
applications of our SIMATIC automation systems and the large number of
these products marketed worldwide, we cannot give a concrete description
specifically analyzing the hazards created by these so-called
SIMATIC-compatible modules. It is beyond the manufacturer’s capabilities
to have all these so-called SIMATIC-compatible modules checked for their
effect on our SIMATIC products. If the use of so-called SIMATIC-compatible
modules leads to defects in a SIMATIC automation system, no warranty for
such systems will be given by Siemens.
In the event of product liability damages due to the use of so-called
SIMATIC-compatible modules, Siemens are not liable since we took timely
action in warning users of the potential hazards involved in so-called
SIMATIC-compatible modules.”

System Manual
C79000-G8576-C199-06

1-7

Notes on Using this Manual and on the CE Symbol

1-8

System Manual
C79000-G8576-C199-06

2
Centralized and Distributed Configuration
of a Programmable Controller
This chapter contains an overview of the methods of configuring an
S5-135U/155U PLC. You will find a description of the types of
communication between a central controller and the expansion units, and an
overview of the interface modules required for the different types of
communication.

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Contents

Page

2.1

Application

2-2

2.2

Centralized and Distributed Configuration

2-3

2.3

Examples

2-6

2-1

Centralized and Distributed Configuration of a Programmable Controller

2.1

Application
The S5-135U/155U programmable controllers comprise a central controller
(CC) and, if required, one or more expansion units (EUs). You need EUs
when there are insufficient slots in the CC for the modules to be used.
Various interface modules (IMs) are available for communication between
the CC and the EUs and between the EUs. It is therefore possible to install an
EU or EUs in the immediate vicinity of the CC (centralized configuration) or
at some distance (distributed configuration). A combination of both types of
configuration is also possible by connecting additional EUs in a centralized
configuration with a distributed EU (see Figure 2-5).
This is clarified on the following pages.

2-2

System Manual
C79000-G8576-C199-06

Centralized and Distributed Configuration of a Programmable Controller

2.2

Centralized and Distributed Configuration
You can install a PLC in centralized or distributed configuration according to
your application.
IF ...

THEN ...

you wish to position the modules as closely as
possible to the CC and can accept longer cable runs to
the process,

choose the
centralized
configuration

you wish to position the I/O modules as closely as
possible to the process and can accept longer cable
runs to the CC,

choose the
distributed
configuration

With the centralized configuration, you can install the CC and EUs in the
same cabinet or in adjacent cabinets. Data transmission is parallel. Shown in
the following figure is a centralized configuration.

EU

EU

CC

Load Power Supply

Figure 2-1

System Manual
C79000-G8576-C199-06

Centralized Configuration

2-3

Centralized and Distributed Configuration of a Programmable Controller

With the distributed configuration, a distinction is made between parallel and
serial communication. The main features of these types of communication
are as follows:

2.2.1

S Parallel

fast data transmission line length of up to 600 m

S Serial

slower data transmission line length of up to 3000 m

Installing a PLC with Centralized Configuration
The following table shows which interface modules and connecting cables
can be used for connecting the various expansion units to the CC in a
centralized configuration.

Interface Module
in the CC

Expansion Unit

Interface Module
in the EU

Connecting Cable
Max. Distance

IM 300-3
6ES5 300-3AB11

EU 183U
EU 185U
(I/O mod. only)

IM 312-3 2)
6ES5 312-3AB11

fixed to the IM 312 module
0.5 m; 0.95 m

IM 301-3 1)
6ES5 301-3AB13

EU 183U
EU 185U
(I/O mod. only)

IM 312-3 2)
6ES5 312-3AB31

fixed to the IM 312 module
0.5 m; 0.95 m

IM 300-5
6ES5 300-5CA11

EU 184U
EU 187U

IM 312-5
6ES5 312-5CA11

fixed to the IM 312 module
0.5 m; 1.5 m

IM 301-5 1)
6ES5 301-5CA12

EU 184U
EU 187U

IM 312-5
6ES5 312-5CA21

fixed to the IM 312 module
0.5 m; 1.5 m

IM 300-5
6ES5 300-5LB11

ER 701-1

IM 306
6ES5 306-7LA11

6ES5 705-0xxxx
0.5 m to 2,5 m

1)

This IM has a second interface for distributed communication.

2)

The last IM 312-3 always requires a 6ES5 760-0AB11 terminator.

To install a PLC in a centralized configuration, you must observe the
following conditions:

S A centralized configuration is generally only suitable for connecting I/O
modules (DI, DO, AI, AO) and some intelligent I/O modules (IPs) in the
EU (see the Configuring Aids in the catalog and Chapter 4).

S The line length between the IM in the CC and the last IM in the EU must
not exceed 2 m.

2-4

System Manual
C79000-G8576-C199-06

Centralized and Distributed Configuration of a Programmable Controller

2.2.2

Installing a PLC with Distributed Configuration
To install a PLC in a distributed configuration, you have a choice of
parallel/symmetrical and serial communication. The following table shows
which interfaces and connecting cables can be used to connect the various
expansion units (EUs/ERs) to the CC in a distributed configuration.

Interface Module
in the CC

Expansion Unit

Interface Module in
the EU

Connecting Cable
Max. Permiss. Line Length

IM 301-3
6ES5 301-3AB13
(not for S5-155H)

EU 183U
ER 701-2
ER 701-3

IM 310 1)
6ES5 310-3AB11

IM 301-5
6ES5 301-5CA12

EU 183U
EU 185U

IM 310 1)
6ES5 310-3AB11

IM 304
6ES5 304-3UB11

ER 701-2
ER 701-3
EU 183U
EU 185U

IM 314 1)
6ES5 314-3UA11

6ES5 721-0xxxx
1 m to 600 m

IM 308
6ES5 308-3UA12

ER 701-2
ER 701-3
EU 183U
EU 185U

IM 318-3
6ES5 318-3UA11

6ES5 707-5AA00
V45551-F21-B5
up to 3000 m

ET 100U
(Catalog ST 52.1)
ICM 560
ET 200

IM 318-8
6ES5 318-8MA12
–
IM 318-B
6ES5 318-8MB11

ER 701-2
ER 701-3
EU 183U
EU 185U

IM 317
6ES5 317-3UA11
IM 317
6ES5 317-3UA11

IM 308-B
6ES5 308-3UB11
IM 307
6ES5 307-3UA11

1)

6ES5 721-0xxxx
1 m to 200 m

Cable connection
6ES5 722-2xxxx
Fiber optic
p cable up
p to 1500 m

The last IM 310 or IM 314 always requires a 6ES5 760-1AA11 terminator.

The ER 701-2 and ER 701-3 always additionally require an IM 306 for
communication via an IM 304, IM 307 or IM 308.
To install a PLC in a distributed configuration, you must observe the
following conditions:

S With the IM 301/IM 310 pair of interface modules, you can only use I/O
modules (DI, DO, AI, AO) and IPs without page addressing in the EUs.

S With the IM 304/314 pair of interface modules, you can use all IPs, CPs
and I/O modules in the EU 185U.
Note
The IM 307/317, IM 308/318 and IM 308-B/318-B each have their own
manual (see catalog).

System Manual
C79000-G8576-C199-06

2-5

Centralized and Distributed Configuration of a Programmable Controller

2.3

Examples
Given in the following are some examples of centralized and distributed
configuration of various SIMATIC S5 components.
3 EUs max.
EU 184U

IM 312-5

4 EUs max.
EU 184U

IM 312-5

IM 312-3

EU183U

6ES5 760-0AB11
EU 184U

IM 312-5
EU183U
IM 312-3
IM 300-5
IM 300-3

CC S5-135U/155U

Figure 2-2

CC S5-135U/155U

Centralized Configuration of an S5-135U/155U with the IM 300
and IM 312

3 ERs max.
ER 701-1

IM 306

ER 701-1

IM 306

ER 701-1

IM 306

IM 300-5LB

CC S5-135U/155U
Figure 2-3

2-6

Centralized Configuration of an S5-135U/155U with ER 701s

System Manual
C79000-G8576-C199-06

Centralized and Distributed Configuration of a Programmable Controller

6ES5 721-0xxx0
EU185U
IM 314

EU 185U
4 EUs max.

IM 314

6ES5 760-1AA11
IM 304

600m max.

CC S5-135U/155U
EU 185U

EU185U
IM314

4 EUs max.

IM 314

6ES5 721-0xxx0
6ES5 760-1AA11

Figure 2-4

Distributed Configuration of an S5-135U/155U with the IM 304 and IM 314

6ES5 760-0AB11

IM 312-3

EU 183U

6ES5 760-0AB11 IM 312-3 6ES5760-0AB11 IM312-3
EU 183U

EU 183U

EU 183U

EU 183U

EU 183U

EU 183U

EU 183U

EU 183U

IM 301-3

CC S5-135U/155U

EU 183U

IM 310-3

Figure 2-5

EU 183U

IM 310-3
6ES5 721-0xxx0

IM 300-3

IM 300-3

6ES5 760-0AA11

Distributed Configuration of an S5-135U/155U with Expansion Units in Centralized Configuration

System Manual
C79000-G8576-C199-06

2-7

Centralized and Distributed Configuration of a Programmable Controller

2-8

System Manual
C79000-G8576-C199-06

3

Installation Guidelines

The Installation Guidelines provide you with information for the
interference-free installation of the SIMATIC S5-135U/155U programmable
controllers.
This chapter describes the following:
Paths which serve for interference pickup in programmable controllers,
and five rules for ensuring electromagnetic compatibility (EMC)
Interference-free installation of the programmable controllers
Cable routing, the connecting of cable shields and equipotential bonding
between equipment
The power supplies for control and load circuits, and the different
grounding concepts
Shielding and grounding for the connection of centralized and distributed
expansions and monitors to programmable controllers
The selection and design of cabinets

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Description

Page

3.1

Principles of Installation of Systems for EMC

3-2

3.2

Installation of Programmable Controllers for EMC

3-8

3.3

Wiring of Programmable Controllers for EMC

3-12

3.4

Power Supplies for Programmable Controllers and I/Os

3-20

3.5

Interference-Free Installation of Centralized and
Distributed Interface Circuits

3-28

3.6

Interference-Free Connection of Monitors

3-30

3.7

Selection and Installation of Cabinets with SIMATIC S5

3-33

3-1

Installation Guidelines

3.1

Principles of Installation of Systems for EMC

What Does EMC
Mean?

Electromagnetic compatibility (EMC) is understood to mean the capability of
electrical equipment to operate correctly in a defined electromagnetic
environment, without being affected by the environment and without
affecting the environment to an unacceptable degree.
All SIMATIC S5 products have been developed for applications in harsh
industrial environments and meet high requirements for EMC. Before
installing the control system, however, you should still carry out EMC
planning and involve possible interference sources in the assessment.
Described in the following chapter are
the various paths over which interference can be picked up in the PLC,
typical interference sources and their coupling mechanisms,
basic rules for ensuring EMC.

3.1.1

Overview of Possible Types of Interference
Electromagnetic interference can be picked up over different paths by the
programmable controller:

Fields

SINEC Bus System

Programmable
Controller

I/O Signal Lines

Power Supply
Protective Conductor

Figure 3-1

3-2

Electromagnetic Interference with Programmable Controllers

System Manual
C79000-G8576-C199-06

Installation Guidelines

Depending on the propagation medium (conducted or non-conducted
interference) and distance from the source, interference can be picked up by
the programmable controller via different coupling mechanisms.
A distinction is made between the following:
Direct coupling
Capacitive coupling
Inductive coupling
Radiated interference

System Manual
C79000-G8576-C199-06

3-3

Installation Guidelines

Coupling
Mechanisms and
Typical
Interference
Sources at a
Glance

Shown in the following table are the four different coupling mechanisms,
their causes, and possible interference sources.

Cause

Coupling Mechanism
Direct Coupling
Interference

Typical Interference Sources

Direct or metallic coupling
always
l
occurs when
h two circuits
i i
have a common conductor

Switched devices (supply
affected
ff
d bby iinverters and
d
external power supply units)
Motors being started
Different potentials of
component cases with a
common power supplys
Static discharges

Capacitive or electrical coupling
occurs bbetween conductors
d
which are at different potentials.

Interference pickup via
parallel
ll l signal
i l cables
bl

Direct Coupling
Path

SIMATIC S5

Capacitive Coupling

Interference

Capacitive Coupling
Path

The degree of coupling is
proportional to the voltage
variation as a function of time.

Static discharge of the
operator
Contactors

SIMATIC S5

Inductive Coupling
Interference

Inductive
Coupling Path
Signal

Inductive or magnetic coupling
occurs bbetween two conductor
d
loops through which current is
flowing. Interference voltages
are induced by the magnetic
fluxes associated with the
currents. The degree of coupling
is proportional to the current
variation as a function of time.

Transformers, motors,
electric
l i welders
ld
Parallel AC supply cables
Cables whose currents are
switched⁄
Signal cables with a high
frequency
Unconnected coils

SIMATIC S5

3-4

System Manual
C79000-G8576-C199-06

Installation Guidelines

Coupling Mechanism
Radiated Interference

Interference

Cause
There is a radiation path when a
conductor
d
iis subjected
bj
d to an
electromagnetic wave.
Impinging of the wave results in
induced currents and voltages.

Typical Interference Sources
Local transmitters
(
(e.g.
two-way radios)
di )
Spark gaps (spark plugs,
collectors in electric motors,
welders)

Radiation Path

SIMATIC S5

System Manual
C79000-G8576-C199-06

3-5

Installation Guidelines

3.1.2

The Most Important Basic Rules for Ensuring EMC
It is often sufficient to comply with a few elementary rules for ensuring
EMC. When installing the control system, therefore, observe the following
five basic rules.
When installing the programmable controllers, provide large-area good
quality grounding of the inactive metal parts (see Section 3.2).
Make a large-area low-impedance interconnection of all inactive metal
parts.
For screw connections on painted and anodized metal parts, either use
special contact washers or remove the insulating protective layers.
If possible, do not use aluminum parts. Aluminum oxidizes easily and is
therefore less suitable for grounding.
Make a central connection between the chassis ground and the
ground/protective ground conductor system.

Ensure proper routing of lines when wiring (see Sections 3.3.1 and 3.3.2).
Arrange the cabling in line groups. (AC power cable, power supply lines,
signal lines, data lines)
Always install AC power cables and signal or data lines in separate ducts
or bunches.
Route the signal and data lines as closely as possible to grounded surfaces
such as cabinet elements, metal bars and cabinet panels.

Ensure that cable shields are properly secured (see Section 3.3.3).
Data lines must be shielded. The shield should be connected at both ends.
Analog lines must be shielded. For the transfer of signals with low
amplitudes, it may be advisable to connect the shield at only one end.
Provide the line shields with a large-area connection to a shield/protective
conductor bar immediately after the cabinet inlet, and secure the shields
with cable clamps. Route the grounded shield as far as the module
without interruption, but do not connect the shield there again.
Ensure that the shield/protective ground bar has a low-impedance
connection to the cabinet.
Use metal or metallized connector cases for shielded data lines.

3-6

System Manual
C79000-G8576-C199-06

Installation Guidelines

Employ special EMC measures for particular applications (see
Section 3.3.4).
Fit quenching elements to all inductances which are not controlled by
SIMATIC S5 modules.
Use incandescent bulbs for illuminating cabinets, and avoid fluorescent
lamps.

Create a standard reference potential; ground all electrical apparatus if
possible (see Sections 3.4 and 3.5).
Use specific grounding measures. Grounding of the control system is a
protective and functional measure.
System parts and cabinets with central controllers and expansion units
should be connected to the ground/protective conductor system in star
configuration. This serves to avoid the creation of ground loops.
In the case of potential differences between system parts and cabinets,
install equipotential bonding conductors of sufficient rating.

System Manual
C79000-G8576-C199-06

3-7

Installation Guidelines

3.2

Installation of Programmable Controllers for EMC
Measures for suppressing interference voltages are often applied only when
the control system is already operational and proper reception of a useful
signal is impaired. The reason for such interference is usually inadequate
reference potentials caused by mistakes in equipment assembly. Described in
the following sections are:
Basic rules for grounding the inactive metal parts
Examples of cabinet assembly for EMC
Example of rack and wall mounting for EMC

3.2.1

Basic Rules for Assembling and Grounding the Inactive Metal
Parts
Ensure wide-area chassis grounding of the inactive metal parts when
mounting the equipment. Properly implemented grounding creates a uniform
reference potential for the control system, and reduces the effects of
picked-up interference.
Chassis grounding is understood to mean the electrical connection of all
inactive parts. The entirety of all interconnected inactive parts is the chassis
ground.
Inactive parts are conductive parts which are electrically isolated from active
parts by basic insulation, and can only develop a voltage in the event of a
fault.
The chassis ground must not develop a dangerous touch voltage, even in
the event of a fault. The ground must therefore be connected to the protective
ground conductor. To prevent ground loops, locally separated ground
elements such as cabinets, structural and machine parts, must always be
connected to the protective ground system in star configuration.
Ensure the following when chassis grounding:
Connect the inactive metal parts with the same degree of care as the
active parts.
Ensure low-impedance metal-to-metal connections, e.g. with large-area
good quality contact.
When you are incorporating painted or anodized metal parts in the
grounding, these insulating protective layers must be penetrated. Use
special contact washers or remove the insulating layer.
Protect the connection points from corrosion, e.g. with grease.
Movable grounded parts such as cabinet doors must be connected via
flexible grounding strips. The grounding strips should be short and have a
large surface because the surface is decisive in providing a path to ground
for high-frequency interference.

3-8

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.2.2

Example of Cabinet Assembly for EMC
The example of cabinet assembly in the figure shows the various measures,
the grounding of inactive metal parts and the connection of shielded cables.
This example applies only to grounded operation. Follow the points
numbered in the figure during assembly.

1

2

3

4
5
6
7
8
Figure 3-2

Example of Cabinet Assembly for EMC

System Manual
C79000-G8576-C199-06

3-9

Installation Guidelines

À
Á
Â
Ã
Ä
Å
Æ

Ç

3-10

Grounding strips
If there are no large-area metal-to-metal connections, you must
connect inactive metal parts such as cabinet doors and supports
with grounding strips. These should be short and have a large surface.
Cabinet members
The cabinet members should have a large-area connection to the
cabinet housing (metal-to-metal connection).
Mounting bracket for subrack
There must be a large-area metal-to-metal connection between
cabinet member and mounting bracket.
Signal lines
With shielded signal lines, the shield must be secured to the
protective conductor bar or an additionally fitted shield bar using
large-area cable clamps.
Cable clamp
The cable clamp must enclose and make contact with the shield braid
over a large area.
Shield bar
This bar must have a large-area connection to the cabinet members
(metal-to-metal connection). It serves for grounding the cable shields.
Protective conductor bar
The protective conductor bar must have a large-area connection to
the cabinet members (metal-to-metal connection). The protective
conductor bar must be connected to the protective conductor system
via an external conductor (at least 10 mm2 ). This is essential for
providing a reliable path to ground for fault currents and interference
currents.
Conductor to the protective conductor system (ground point)
The conductor must have a large-area connection to the protective
conductor system (ground point).

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.2.3

Example of Rack and Wall Mounting for EMC
To operate your control system in a low-interference environment whilst
observing the permissible ambient conditions (see “Technical
Specifications”), you can mount the programmable controllers on racks or
directly on walls.
Picked-up interference should be given a path to large metal surfaces. You
should therefore secure standard sectional rails, shield and protective
conductor bars to metal structural elements. For wall mounting in particular,
installation on reference potential surfaces made of sheet steel has proved
advantageous.
When installing shielded cables, provide a shield bar for connecting the cable
shields. The shield bar can also be the protective conductor bar.
Ensure the following for rack and wall mounting:

S Suitable contacting aids should be used on painted and anodized metal
parts. Use special contact washers or remove the insulating protective
layers.
S Provide large-area, low-impedance metal-to-metal connections when
securing the shield/protective conductor bar.
S AC conductors must be covered.

Reference Potential
Surface

Shielded Signal
Line
Cable Clamp for
Shield Contact

Shield/Protective
Conductor Bar

Connection to
P. Ground: 10 mm@

Figure 3-3

Wall Mounting of an S5-135/155U PLC

System Manual
C79000-G8576-C199-06

3-11

Installation Guidelines

3.3

Wiring of Programmable Controllers for EMC
The following section describes:
Routing of cables within and outside cabinets
Equipotential bonding between devices
Single and double-ended connection of cable shields
Checklist for electromagnetically compatible installation

3.3.1

Routing of Cables
This section covers the routing of bus, signal and supply lines. The purpose
cable routing is to suppress crosstalk between cables laid in parallel.

Routing of Cables
Within and
Outside Cabinets

For electromagnetically compatible routing of cables and lines, it is
expedient to subdivide the lines into the following line groups and lay the
groups separately.

Group A
Shielded bus and data lines (for programmer, OP, SINEC L1, SINEC L2,
printer, etc.)
Shielded analog lines
Unshielded lines for DC voltage v 60 V
Unshielded lines for AC voltage v 25 V
Coaxial cables for monitors
Group B
Unshielded lines for DC voltage > 60V and v 400V
Unshielded lines for AC voltage > 25V and v 400V
Group C
Unshielded lines for DC and AC voltage > 400V
Group D
Lines for SINEC H1
From the combination of individual groups in the following table, you can
read off the conditions for laying the line groups.
Group A
Group A
Group B
Group C
Group D

3-12





Group B

Group C

Group D















System Manual
C79000-G8576-C199-06

Installation Guidelines

Legend for the table
Lines can be laid in common bundles or cable ducts.

Routing of Cables
Outside Buildings



Lines must be laid in separate bundles or cable ducts (without
minimum clearance).



Lines within cabinets must be laid in separate bundles or cable
ducts; outside the cabinets but within buildings, they must be laid
over separate cable routes with a clearance of at least 10 cm.



Lines must be laid in separate bundles or cable ducts with a
clearance of at least 50 cm.

Outside buildings, lay the lines on metal cable trays if possible. Provide the
joints between cable trays with an electrical connection and ground the cable
trays.
When laying lines outside buildings, you must observe the valid lightning
protection and grounding measures. The following applies in general:

Lightning
Protection

!

Caution
Where cables and lines for SIMATIC S5 controllers are to be laid
outside buildings, you must apply measures for internal and external
lightning protection.

Outside the buildings, lay your lines either
in metal conduit grounded at both ends,
or
in concreted cable ducts with continuously connected reinforcement.
Protect the signal lines from overvoltages by means of
varistors
or
inert gas-filled surge diverters.
Fit these protective devices at the cable entry into the building.
Note
Lightning protection measures always require an individual assessment of
the entire installation. For clarification, please consult your Siemens regional
office or a company specializing in lightning protection.
Equipotential
Bonding

System Manual
C79000-G8576-C199-06

Ensure adequate equipotential bonding between the connected equipment
(see Section 3.3.2).

3-13

Installation Guidelines

3.3.2

Equipotential Bonding
Between separate sections of an installation, potential differences can
develop if
S programmable controllers and I/O devices are connected via a
non-floating link, or
S cable shields are connected at both ends and are grounded at different
parts of the system.
Different AC supplies, for example, can cause potential differences. These
differences must be reduced by installing equipotential bonding conductors to
ensure functioning of the electronic components.
The following points must be observed for equipotential bonding:
S The lower the impedance of the equipotential bonding conductor, the
greater is the effectiveness of equipotential bonding.
S Where shielded signal lines are laid between the relevant sections of the
system and connected at both ends to the ground/protective conductor, the
impedance of the additional equipotential bonding conductor must not
exceed 10 % of the shield impedance.
S The cross-section of the equipotential bonding conductor must be rated
for the maximum circulating current. The following cross-sections of
copper have proved to be satisfactory in practice:
–16 mm@ of copper for equipotential bonding conductors
of up to 200 m in length
–25 mm@ of copper for equipotential bonding conductors
of more than 200 m in length.
S Use copper or zinc-plated steel for equipotential bonding conductors.
They must be given a large-area connection to the ground/protective
conductor and protect it from corrosion.
S The equipotential bonding conductor should be laid so that the smallest
possible areas are enclosed between the equipotential bonding conductor
and signal lines.

Signal Line
EquipotentialBonding Conductor

Figure 3-4

3-14

Routing of Equipotential Bonding Conductor and Signal Line

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.3.3

Shielding of Cables and Lines
Shielding is a method of attenuating magnetic, electrical or electro-magnetic
interference fields. Interference currents on cable shields are given a path to
ground via the shield bar which is electrically connected to the housing. A
low-impedance connection to the protective conductor is particularly
important so that these interference currents themselves do not become an
interference source.
Where possible, only use lines with a braided shield. The coverage density of
the shield should be more than 80 %. Avoid lines with a foil shield because
the foil can be very easily damaged by tensile strain and compression during
fitting; this results in reduced effectiveness of the shield.
As a rule, line shields should always be connected at both ends. This is the
only way to achieve a good degree of interference suppression in the higher
frequency region.
Only in exceptional cases should the shield be connected at one end only, as
this only achieves attenuation of the low frequencies. Single-ended shield
connection may be more advantageous when:
an equipotential bonding conductor cannot be laid;
analog signals (of a few mV or mA) are to be transmitted;
foil (static) shields are used.
With data lines for serial communication, always use metal or metallized
connectors. Secure the shield of the data line to the connector case. Do not
connect the shield to Pin 1 of the connector.
For stationary operation, it is advisable to fully strip the insulation from the
shielded cable and connect it to the shield/protective conductor bar.
Note
In the event of potential differences between ground points, a circulating
current may flow through the shield connected at both ends. In this case,
install an additional equipotential bonding conductor (see Section 3.3.2).

System Manual
C79000-G8576-C199-06

3-15

Installation Guidelines

Please observe the following points when connecting the shield:
Use metal cable clamps for securing the braided shield. The clamps must
enclose the shield over a large area and provide a good contact.
Connect the shield to a shield bar immediately after the cable entry into
the cabinet. Route the shield as far as the module but do not connect it
there again.

ÎÎ
ÎÎ

Figure 3-5

3-16

ÎÎÎÎ
Î
ÎÎ

Î
Î
Î

ÎÎ
Î
ÎÎ
Î
Î
ÎÎÎÎ
ÎÎ

Example of Securing Shielded Lines with Cable Clamps

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.3.4

Special Measures for Interference-Free Operation

Fitting Quenching
Elements to
Inductances

As a rule, inductances such as contactor or relay coils controlled by
SIMATIC S5 do not require external quenching elements in the circuit,
because the quenching elements are already integrated in the modules.
Inductances should only be fitted with quenching elements
when SIMATIC S5 output currents can be switched off by additionally
fitted contacts, such as relay contacts. In this case the integrated
quenching elements in the modules are no longer effective;
if they are not controlled by SIMATIC S5 modules.
You can place freewheel diodes, varistors or RC networks in circuit with
inductances.

Circuitry for DC-Operated
Inductances
With Diode

Figure 3-6

With Zener Diode

Circuitry for AC-Operated
Inductances
With Varistor

With RC Network

Quenching Circuits for Inductances

System Manual
C79000-G8576-C199-06

3-17

Installation Guidelines

AC Power
Connection for
Programmers

A power socket should be fitted in each cabinet for the AC supply to
programmers. The sockets should be powered from the distribution system to
which the protective conductor for the cabinet is also connected.

Cabinet Lighting

Use incandescent bulbs, such as LINESTRA lamps, for cabinet lighting.
Avoid using fluorescent lamps because they generate interference fields. If
the use of fluorescent lamps cannot be avoided, apply the measures shown in
the following figure.

Screen Over the Lamp

Shielded Cable
Metal-Enclosed Switch

AC Filter or
Shielded Power Cable

Figure 3-7

3-18

Measures for Interference Suppression of Fluorescent Lamps in a
Cabinet

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.3.5

Checklist for the Electromagnetically Compatible Installation of
Control Systems

EMC Measures
Connection of inactive parts

Notes
(Section 3.2)

Check, in particular, the connections on:
Subracks
Cabinet members
Shield and protective conductor bars
Do all inactive metal parts have a large-area, low-impedance
interconnection and ground?
Is there a satisfactory connection to the ground/protective conductor
system?
Have insulating layers on painted and anodized surfaces been
removed, or have special contact washers been used for the
connections?
Are connections protected from corrosion, e.g. by grease?
Are cabinet doors connected to the cabinet element with grounding
strips?
Routing of cables

(Section 3.3.1)

Cabling subdivided into line groups?
Supply cables (230 to 400 V) and signal lines laid in separate ducts or
bundles?
Equipotential bonding

(Section 3.3.2)

With a separate arrangement, check that the equipotential bonding
conductor has been correctly laid.
Shielding of cables

(Section 3.3.3)

Have metal connectors been used throughout?
Are all analog and data lines shielded?
Are line shields connected to the shield or protective conductor bar at
the cabinet entry?
Are line shields secured with cable clamps over a large area and at
low impedance?
Are line shields connected at both ends where possible?
Inductances

(Section 3.3.4)

Are contactor coils which are switched via contacts, fitted with
quenching elements?

System Manual
C79000-G8576-C199-06

3-19

Installation Guidelines

3.4

Power Supplies for Programmable Controllers and I/Os
This section describes:
Which circuits you must distinguish in the control system and which
demands are made on the power supply.
Connection and grounding concept with higher-level infeed from
grounded, centrally grounded and ungrounded supplies.
Connecting the power supply to non-isolated and isolated modules.

3.4.1

Power Supplies for Control Systems with SIMATIC S5
For control systems with SIMATIC S5, you will need:
A power supply for the internal PLC circuits (control power supply)
and a load power supply for the input and output circuits.

Power Supply for
the PLC Circuits

The power supply for the internal PLC circuits powers the CPU and the
modules used.
Note
Ensure that the control power supply is not overloaded. Make a current
addition and estimate the current drawn by all modules.

Load Power
Supply for the I/Os

!

3-20

The load power supply feeds the input and output circuits (load circuits) as
well as sensors and actuators. Only a power supply which offers safe
electrical isolation from the AC system may be used for the 24 V DC supply.
Caution
Only safety-separated low voltage DC v 60 V may be used for the 24 V DC
supply. The safety separation can be implemented according to the
requirements of, amongst other sources, VDE 0100, Part 410/HD
384-4-41/IEC 364-4-41 (functional extra-low voltage with safety separation)
or VDE 0805/EN 60950/IEC 950 (safety extra-low voltage SELV) or VDE
0106, Part 101.

System Manual
C79000-G8576-C199-06

Installation Guidelines

Ratings of Load
Power Supplies

The electronic short-circuit protection of digital output modules only
responds when 3-times the rated current is exceeded. You should therefore so
design the load power supply units that the unit can supply the current
required for shutting down in the event of a short-circuit at one output.
In the event of short-circuits at digital outputs, if the load power supply is not
adequately rated, a current which is higher than the rated current can flow for
a longer period without responding of the electronic short-circuit protection
of the DQ module. Operation in the overload region can destroy the module.

Load Power
Supply for
Non-Floating
Modules

Load Power
Supply for
Floating Modules

If you use non-floating modules, you must create a common reference
potential for the internal control circuits of the PLC and for the load circuits.
The reference potential of the load power supply should therefore be
connected to the ground terminal of the PLC (PE or protective conductor
terminal). The ground terminal is permanently connected to the internal
reference potential of the controller.

Note
If you use switched-mode power supply units for floating analog modules
and BEROs, you must fit an AC system filter to the input of the power
supply.

3.4.2

Connecting the Programmable Controller and Load Power
Each of the following figures shows a circuit example for connecting the
control and load power supplies as well as the grounding concept for
operation from:
Grounded supplies
Centrally grounded supplies
Ungrounded supplies
When assembling the control system, observe the following explanations.
The text contains identification numbers relating to Figures 3-8 to 3-10.

Main Switch and
Protection

For the programmable controller, sensors and actuators, you must fit a
main switch to DIN VDE 0113, Part 1, or an isolating device to DIN
VDE 0100, Part 460. If an AC plug is used as the isolating device, the
socket must be in the vicinity of the central controller and must be easily
accessible (VDE 0805, 1.7.2). These devices are not required in the case
of a subsystem where the appropriate devices are fitted at a higher level.
The circuits for sensors and actuators can be given group protection for
short-circuit and/or overload . According to VDE 0100, Part 725,
single-phase protection is required; and all-phase protection to DIN VDE
0113, Part 1.

System Manual
C79000-G8576-C199-06

3-21

Installation Guidelines

Load Power
Supply

For 24 V DC load circuits, you require a load power supply unit with
safety separation. If an AC plug is used as the isolating device, the socket
must be in the vicinity of the central controller and easily accessible
(VDE 0805, 1.7.2).
Unregulated load power supply units require a reservoir capacitor
(rated at 200 mF per 1 A load current). Connect the capacitor in parallel
with the output terminals of the load power supply.
According to DIN VDE 0113, Part 1, control systems with more than five
items of electromagnetic apparatus require isolation by a transformer;
according to DIN VDE 0100, Part 725, it is recommended .

Grounding
Load power supplies should be grounded if possible . Provide a
detachable connection to the protective conductor at the load power
supply unit (terminal L- or M) or on the secondary side of the isolating
transformer.

!

Caution
For ungrounded power supplies, you must provide insulation monitoring if⁄
hazardous system states can be caused by double faults;
there is no safety separation;
circuits are operated with voltages of more than 120 V DC;
circuits are operated with voltages of more than 50 V AC.

3-22

System Manual
C79000-G8576-C199-06

Installation Guidelines

Operating a
Programmable
Controller with
Process I/Os from
a Grounded
Supply

L1
L2
L3
N
PE

Operation from grounded power supplies offers the best rejection of
interference.

Low-Voltage Distribution
e.g. TN-S System

Cabinet

Programmable Controller

Control Power Supply
AC
DC

L+
L–

L+/L1

L1
N

L–/N

Uint
PS
0V

PE

CPU

Non-Float- Non-Float- Floating
ing Input ing Output Input

Floating
Output

PE

Protective Conductor Bar
in Cabinet





AC
AC


AC
DC


AC
DC




Process I/Os

24 to 230 V AC Load Supply
for AC Modules


5 to 60 V DC Load Supply for
Non-Floating DC Modules




5 to 60 V DC Load Supply
for Floating DC Modules

Figure 3-8

Operating a Programmable Controller with Process I/Os from a Grounded Supply

System Manual
C79000-G8576-C199-06

3-23

Installation Guidelines

Operating a
Programmable
Controller with
Process I/Os from
a Centrally
Grounded Supply

In systems with their own transformers or generators, the PLC is connected
to the central ground. A detachable connection should be provided so that
ground faults can be measured.
The PLC should be insulated from cabinet/protective conductor potential. To
maintain this isolated arrangement, all connected devices must be operated
with capacitive grounding or ungrounded. For this reason, programmers
should only be powered via an isolating transformer.

Higher-Level Supply
L1
L2
L3

Detachable Connection for
Measurement
Purposes

Programmable Controller, Insulated Arrangement

Cabinet

Central Ground,
e.g. Foundation
Ground

Control Power Supply
AC

L+/L1

L+
L-

DC

U int

L–/N

L1
N

PS

CPU

0V

PE

Non-Floating Input

Non-Floating Output

Floating
Input

Floating
Output

PE

Protective Conductor Bar in Cabinet,
Insulated Arrangement





AC
AC


AC




Process I/Os
24 to 230 V AC Load Supply for AC Modules



DC

5 to 60 V DC Load Supply for Non-Floating DC Modules


AC





DC

5 to 60 V DC Load Supply for Floating DC Modules
L1 L2 L3 N

Figure 3-9

3-24

Operating a Programmable Controller with Process I/Os from a Centrally Grounded Supply

System Manual
C79000-G8576-C199-06

Installation Guidelines

Operating a
Programmable
Controller with
Process I/Os from
an Ungrounded
Supply

L1
L2
L3
PE

In cases in which the higher-level power supply is not grounded, you must
connect the programmable controller to a separate protective
conductor/ground (e.g. foundation ground). Operation of the PLC with
non-floating power supplies is not allowed.
When connecting the power supplies, please note:
In 3 x 230 V systems, you may connect the power supply directly to two
phases.

Low-Voltage Distribution,
e.g. IT System (3 X 230V)

ProgrammableController

Schrank

Control Power Supply
AC
DC

L+
L–

L+/L1

L1
L2

L–/L2

PS

Uint

CPU

0V

PE

Non-Float- Non-Float- Floating
ing Input
ing Output Input

Floating
Output

PE

Protective Conductor Bar
in Cabinet

Protective
Conductor
Grounding





AC
AC


AC




Process I/Os

24 to 230 V AC Load Supply
for AC Modules



DC


AC

5 to 60 V DC Load Supply
for Non-Floating DC Modules





DC

5 to 60 V DC Load Supply
for Floating DC Modules
Figure 3-10

Operating a Programmable Controller with Process I/Os from an Ungrounded Supply

In 3 x 400 V systems, a connection between phase and neutral conductor is
not allowed (excessively high voltage in the event of a ground fault).
Intermediate transformers should be used in these systems.

System Manual
C79000-G8576-C199-06

3-25

Installation Guidelines

3.4.3

Connecting Non-Floating or Floating Modules
Shown in the following sections are the specical features when installing
non-floating and floating modules.

Installation with
Non-Floating
Modules

In an installation with non-floating modules, the reference potentials of the
control circuit (0 Vint) and load circuits (0 Vext) are electrically connected.
The reference potential of the control circuit (0 Vint) is given by the PE or
protective conductor terminal and must be connected to the reference
potential of the load circuit via an externally laid conductor.
Shown in the following figure is a simplified installation with non-floating
modules. The arrangement is independent of the grounding concept. The
connections for grounding are therefore not drawn.

Uint
Data
0V

CPU

PS
1L+
1L–
PE
Control Power
Supply

DI

DQ

External Connection for a
Standard Reference Potential

2L+
2L–
DC 24 V Load Power Supply

Figure 3-11

Simplified Representation of an Installation with Non-Floating Modules

The voltage drop on line must not exceed 1 V. Otherwise there will be a
shift in reference potentials resulting in module malfunctions.

3-26

System Manual
C79000-G8576-C199-06

Installation Guidelines

Note
For 24 V DC digital output modules with electronic short-circuit protection,
you must ensure that the reference potential of the load power supply is
connected to terminal L- of the module. If this connection is missing (e.g.
open-circuit), a typical current of 15 mA can flow at the outputs. This output
circuit is sufficient
to prevent energized contactors or relays from being released
and to energize high-resistance loads (e.g. miniature relays).

Installation with
Floating Modules

With floating modules the control circuit and load circuit are metallically
isolated.
An arrangement with floating modules is required
for all AC load circuits and
for DC load circuits which cannot be coupled. The reasons are, for
example, different reference potentials of the sensors or grounding of the
positive terminal of a battery.
Shown in the following figure is a simplified installation with floating
modules. The arrangement is independent of the grounding concept. The
connections for grounding are therefore not drawn.
Uint
Data
0V

CPU

PS

DI

DQ

1L+
1L–
PE
24 V DC Control Power Supply

2L+
2L–

L1
N

24 V DC Load Power Supply

Figure 3-12

230 V AC Load Power Supply

Simplified Representation of an Arrangement with Floating Modules

System Manual
C79000-G8576-C199-06

3-27

Installation Guidelines

3.5

Interference-Free Installation of Centralized and Distributed
Interface Circuits
Subjects described in the following sections are the shielding and grounding
concept with centralized and distributed interface circuits.
Information on component selection, the mechanical arrangement and wiring
can be found in the appropriate reference manuals for the interface modules.
Note
If you use components which are not approved for the installation of a
centralized or distributed interface circuit, interference rejection may be
impaired.

3.5.1

Interference-Free Installation of Centralized Interface Circuits
When you connect the central controller and expansion unit centrally via
suitable interface modules, no particular shielding and grounding measures
are required. Ensure, however, that
all subracks are interconnected at a low resistance;
the subracks in a grounded arrangement have star-configuration
grounding;
the contact springs of the modules are clean and not bent, which could
affect the path to ground for interference currents.

3.5.2

Interference-Free Installation of Distributed Interface Circuits
If you interconnect the central controller and expansion unit in a distributed
arrangement using suitable interface modules, no particular shielding and
grounding measures are usually required. Only in industrial environments
with an extremely high level of interference is there a need for special
shielding and grounding.
In these cases, please observe the following points:
Cable shields should be connected to the shield bar in the cabinet,
immediately after the cable inlet;
- insulation is fully stripped from the cable for the purpose;
- braided shields are secured to the shield bar with as large an area as
possible (e.g. with metal ties which enclose the shield over a large
area).
Shield bars should be connected to the frame or cabinet panel over a large
area.
Cable shields should be connected to the cabinet conductor.

3-28

System Manual
C79000-G8576-C199-06

Installation Guidelines

With distributed interfacing (IM 304/IM 314 and IM 301/IM 310), ensure
that the VDE specifications for laying the protective ground are complied
with; distributed interfacing is non-floating.
The measures described above are shown in the following figure. If the
permissible potential difference between ground points can be exceeded, you
must install an equipotential bonding conductor (cross-section w 16 mm2 of
copper).

CC

EU
IM 304

IM 314

Shield/Protective
Conductor Bar

<7V

Figure 3-13

Shielding and Grounding the Connecting Cable

Special Features

System Manual
C79000-G8576-C199-06

With distributed interfacing, you must use the prefabricated connecting
cables. You may have excess lengths of up to 100 m when installing the
connecting cable. These excess lengths must be bifilar-wound and deposited
at a point which is protected from electromagnetic interference.

3-29

Installation Guidelines

3.6

Interference-Free Connection of Monitors
These sections cover the following topics:
Floating connection of cables at video inputs
Shielding and grounding concept
Information on selecting the components can be found in Catalog ST80.

3.6.1

Interference-Free Connection of a Monitor to the CP of the S5
Controller
Operator control and process monitoring systems from the COROS product
family can be used with monitor connections. The physical arrangement of
apparatus and the interference level of the environment are important for the
interference-free connection of monitors to SIMATIC S5 control systems.
The choice of monitor and video cables is governed by the following:
Whether the monitor and PLC are to be operated under low-interference
conditions or
under industrial conditions.

Operation of the
Monitor and PLC
under
Low-Interference
Conditions

Where the monitor and PLC are installed under low-interference
environmental conditions and operated over short distances, the monitor and
PLC are at almost the same ground potentials. Interference and ground loop
disturbances are therefore not expected.
In these cases, you can drive the monitor both via TTL signals and via analog
signals. Digital cables or single-shielded coaxial cables can be used to
transmit the video signals. Note that the braided shield of the coaxial cable
serves as the return conductor and must not be connected to the shield bar.
The monitor and communication processor (CP) are interconnected without
additional shielding and grounding.

Operation of the
Monitor and PLC
under Industrial
Conditions

3-30

Where the monitor and PLC are installed under harsh industrial conditions
and operated over great distances, the devices may be at different ground
potentials. These different ground potentials may cause interference and
ground loop disturbances.

System Manual
C79000-G8576-C199-06

Installation Guidelines

In these cases, double-shielded coaxial cables (triaxial cables) must be used
to transmit the video signals. The inner braided shield of the coaxial cable
serves as the return conductor and must not be connected to the shield bar.
The outer braided shield provides a path to ground for interference currents
and must be incorporated in the shielding and grounding measures.
To avoid ground loops, the electronics ground and housing ground of the
monitor must be independent. This requirement is met when:
The electronics and housing grounds of the monitor are metallically
isolated,
or the electronics and housing grounds are connected via a
voltage-dependent resistor (VDR) fitted by the manufacturer of the
monitor.

3.6.2

Shielding and Grounding
If the monitor and PLC are used under harsh industrial conditions, you must
ensure the following at the PLC end:
Cables shields should be connected to the shield bar in the cabinet,
immediately after the cable inlet;
- the video cables should be fully stripped;
- the outer braided shield should be secured to the shield bar of the
PLC over as large an area as possible (e.g. with metal ties which
enclose the shield or with cable clamps).
Shield bars should be connected to the frame or cabinet panel over a large
area.
Shield bars should be connected to the ground point of the cabinet.

You must ensure the following at the monitor end:
Separate the electronics ground and housing ground.
- Remove the jumper at the monitor to separate the two grounds.
- Fit touch protection at the video sockets because hazardous touch
voltages of more than 40 V may be present at the sockets after
separation of the grounds.
Connect the ground clamp of the monitor to the protective conductor.
Connect the cable shields to the ground clamp of the monitor;
- fully strip the video cables;
- secure the outer braided shield to the ground clamp of the
monitor over a large area.

System Manual
C79000-G8576-C199-06

3-31

Installation Guidelines

Shown in the following figure is a simplified representation of the shielding
and grounding measures for installing the monitor and PLC.

CP
Monitor with
Separate
Electronics and
Housing Grounds

Shield/
Protective
Conductor
Bar

Figure 3-14

3-32

External Shield
Connected to
Ground Clamp

Shielding and Grounding for a Distributed Arrangement of Monitor and PLC

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.7

Selection and Installation of Cabinets with SIMATIC S5
The following criteria must be observed when selecting and dimensioning a
cabinet:
Ambient conditions at the point of installation of the cabinet
Clearances for power supplies and subracks
Total power dissipation of components in the cabinet
The ambient conditions at the point of installation of the cabinet
(temperature, humidity, dust, effects of chemicals) govern the required
degree of protection of the cabinet (IP XX) as shown in the following figure.
Further information on types of protection can be found in IEC 529.

System Manual
C79000-G8576-C199-06

3-33

Installation Guidelines

3.7.1

Types of Cabinet
The following table provides on overview of the most common types of
cabinet. It also shows the principle of heat removal, as well as the estimated,
maximum achievable power loss removal and the type of protection* .
Open Cabinets

Closed Cabinets

Through-ventilation by
natural convection

Increased
through-ventilation

Natural convection

Forced circulation
using fan assembly,
enhanced natural
convection

Forced circulation
using heat exchanger,
external ventilation
inside and outside

Heat removal primarily
by natural thermal
convection, small
portion via the cabinet
wall

Increased heat removal
through increased air
movement

Heat removal only
through the cabinet
wall; only low power
dissipation permissible.
Heat accumulation
usually occurs in the
top of the cabinet.

Heat removal only via
the cabinet wall. Forced
ventilation of the
internal air results in
improved heat removal
and prevention of heat
accumulation.

Heat removal through
exchange between
heated internal air and
cool outside air. The
increased surface of the
folded-area sectional
wall of the heat
exchanger and forced
circulation of internal
and external air permit
good heat output.

Type of protect. IP 20

Type of protect. IP 20

Type of protect. IP 54

Type of protect. IP 54

Type of protect. IP 54

Typical removable power dissipation under the following boundary conditions:
Cabinet size 2200 x 600 x 600 mm
Temperature difference between external and internal temperature of the cabinet: 20 °C**
Up to 700 W

Up to 2700 W (1400 W
with very fine filter)

*

Up to 260 W

Up to 360 W

Up to 1700 W

The location and ambient conditions are decisive for selection of the type of cabinet protection

( see IEC 529 and DIN 40050).
** For other temperature differences, refer to the temperature characteristics of the cabinet
manufacturer.

3.7.2

Clearances in Cabinets
You must first define the components to be fitted in the cabinet. Then
calculate the total power dissipation of the individual components. The
following stipulations must be observed:
The expansion units can be accommodated with the respective central
controller in one cabinet, or in two or more cabinets (centralized or
distributed).
On account of the required clearances and maximum permissible
installation height for control elements, a maximum of three SIMATIC S5
devices can be arranged one above the other.

3-34

System Manual
C79000-G8576-C199-06

Installation Guidelines

! !(# &""*
 % 
#

)&$%

#

&#
 
 

  !# # $

 % 
#

)&$%

#

&#
 
 	

  !# # $

 % 
#

)&$%

#

&#



  +

 % 
#


$$ '

75 mm min., smaller clearances are possible with a closed cabinet roof and an additional, separate ventilation
roof.
A maximum clearance of 400 mm is possible (50 mm min.) when devices are connected next to one another.
75 mm min. from obstructions (large apparatus) in the air inlet area.
400 mm minimum installation height above access level for control elements, 200 mm for connections.
Maximum installation height for control elements: 2100 mm to DIN VDE 0106, Part 100,
2000 mm to DIN VDE 0113.
Space for air circulation (400 mm deep cabinets are sufficient).
Baffles are recommended to improve the air supply.

Figure 3-15

Clearances in the Cabinet

System Manual
C79000-G8576-C199-06

3-35

Installation Guidelines

Where subracks (CC and EU) are arranged one above the other, the
installation clearances in the following table must be observed.

Upper Subrack

Lower Subrack

S5-135U/ 155U
or
S5-115U
or
S5-90U/ 95U/ 100U

S5-135U

Min. Clearances
75 mm
87 mm if baffle
is used

S5-115U with fan

60 mm

S5-115U without fan

100 mm

S5-90U/ 95U/ 100U

75 mm

Max. Clearances
The maximum clearance
is limited by the lengths
of connecting
g cables for
the
h interface
i
f
modules.
d l

The following two points should be observed to improve the air circulation
within the cabinet:
The expansion unit with the greatest power dissipation to be removed
should be the upper unit.
If subracks of the S5-135U/155U series are installed together with
subracks of the S5-90U to 115U series in one cabinet, the rear panels of
all subracks must be at the same distance from the rear wall of the
cabinet.

3-36

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.7.3

Removal of Power Dissipation from Cabinets
The power dissipation that can be removed from a cabinet is governed by the
cabinet design, its ambient temperature and the arrangement of equipment in
the cabinet.
Shown in the following figure is a diagram with guide values for the
permissible ambient temperature of a cabinet measuring 600 x 600 x 2200
mm, as a function of power dissipation. These values only apply to the
arrangement of equipment in the cabinet as given in Section 3.6.2. Further
details can be found in Catalogs NV21 and ET1.

Ambient Temperature
o
in C
55
50

40
1

30
2
3
20
200
1
2
3

400

600

800

1000

1200
1400 W
Power Dissipation

Closed cabinet with heat exchanger of size 11/6 (920 x 460 x 111 mm)
Cabinet with through-ventilation by natural convection
Closed cabinet with natural convection and forced circulation using fan

Figure 3-16

Maximum Cabinet Ambient Temperature as a Function of Power Dissipation

Note
When fitting the subracks of the S5-135U/155U series, the maximum power
dissipation which can be removed by the fans must not be exceeded. The
maximum removable power dissipation per unit with a supply air
temperature of 55 °C is 250 W. This value is increased by 20 W for each
reduction in supply air temperature by 1 °C.

System Manual
C79000-G8576-C199-06

3-37

Installation Guidelines

!

3.7.4

Caution
Modules with a hard disk drive can only be used at an ambient temperature
of up to 50 °C.

Examples for Determining the Type of Cabinet
The following example shows the maximum permissible ambient
temperature with various cabinet types and the same power dissipation.
Example
The following equipment configuration is given:
1

Central controller

200 W

2

Expansion units, 250 W power dissipation each

500 W

1

Load PS, 24 V/40 A, 6EV1 362-5BK00 (full load)

200 W

Total power disspation

900 W

From Figure 3-16, with a total power dissipation of 900 W, the maximum
ambient temperatures given by the table are as follows:

3-38

Cabinet Design

Max. Permissible Ambient
Temperature

Closed, with natural convection and forced
circulation (Curve 3)

(Operation not possible)

Open with through-ventilation (Curve 2)

Approx. 33 °C

Closed, with heat exchanger (Curve 1)

Approx. 42 °C

System Manual
C79000-G8576-C199-06

Installation Guidelines

3.7.5

Determining the Power Dissipation of Modules
The power dissipation of the modules can be found in the technical
specifications of the catalogs or manuals. If these values are not yet
incorporated in the technical specifications, they can be easily calculated
from the current consumption. The value of current consumption must be
multiplied by the corresponding voltage value.
Examples
CPU 928B Current
consumption

5A/5V

CP 143

Current
consumption

4A/5V
0.5A/15V
0.04A/24V

Current
consumption

1.5A/5V

IM 304

System Manual
C79000-G8576-C199-06

Power dissipation = 25 W
Power dissipation
approx. 21 W
Power dissipation = 7.5 W

3-39

Installation Guidelines

3-40

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units
Power Supply Units

4

The S5-135U/155U programmable controller comprises a central controller
(CC) and, depending on the configuration, one or more expansion units
(EUs). Expansion units are connected when there are unsufficient central
controller slots, or when you wish to position I/O modules as closely to the
process as possible (see also Chapter 2).
With the central controllers and some expansion units, the modules are
directly powered and cooled via the integrated power supply plug-in module.
With all other expansion units, power is supplied via the IMs from the CC
(see also Chapter 7).

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Description

Page

4.1

S5-135U/155U Central Controller

4-2

4.2

Expansion Units

4-15

4.3

Power Supply Units

4-19

4.4

6ES5 955-3NA12 Power Supply Unit

4-57

4.5

Fan Submodules

4-70

4-1

Central Controllers and Expansion Units Power Supply Units

4.1

S5-135U/155U Central Controller
This description applies to the S5-135U/155U CC with the following power
supply units.
Order No. of the CC

4.1.1

With Power Supply Unit

Input Voltage

6ES5 188-3UA12

6ES5 955-3LC42

120 V/230 V AC, 18 A

6ES5 188-3UA22
6ES5 188-3UA32

6ES5 955-3LF42
6ES5 955-3NC42

120 V/230 V AC, 40 A
24 V DC, 18 A

6ES5 188-3UA52

6ES5 955-3NF42

24 V DC, 40 A

6ES5 135-3UA42

6ES5 955-3NA12

24 V DC, 10 A

Technical Description

Assembly of a
Central Controller

The S5-135U/155U CC consists of a housing with backplane bus to accept
the individual modules, and a power supply unit with fans to power and cool
the modules. Shown in the following figure are the most important parts of a
central controller.
1)

8)

5)
6)

4)

7)

2)

Figure 4-1

3)

9)
10)

Assembly of a Central Controller

1. Housing with 21 slots for modules
2.
3.
4.
5.
6.
7.
8.
9.
10.

4-2

Power supply unit with fans
Battery compartment
Cable duct
Locking bar
Mounting bracket
Sectional rail for individually locking the modules
Backplane bus
Filter subdrawer (optional)
Rechargeable battery

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Housing

The housing consists of bolted sheet-steel sections with ventilation openings
at the top and bottom. The housing contains the bus PCB for electrical and
logical interconnection of the modules. All the slots have guiderails which
accept the modules. Male and female connectors are thus precisely
positioned. There is a locking bar at the top of the housing to prevent the
modules from becoming accidentally detached. Modules with individual
locking are secured in the lower sectional rail. There is a cable duct for
incoming and outgoing cables at the front of the housing.

Power Supply Unit

The power supply unit with the fans is situated in the lower part of the central
controller frame. Depending on the type of power supply, the input voltage is
either 24 V DC or 230/120 V AC. The AC version can be adjusted to the
required AC voltage with a selector switch.
The following table shows which modules can be inserted at which slots.

Modules and Slot
Assignments in
the S5-135U/155U
CC

Slot No. 3

11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163

Module Type
923 coordinator
CPU 922/
CPU 928-3UA21/
CPU 928B-3UB21
CPU 928, CPU 928B
CPU 948
CP 5XX, CP 143,
CP 5430, CP 5431 1)
IM 300-5
IM 301-5 2)
IM 300-3, IM 301-3
IM 304, IM 308, IM 308B
IM 307 1) 3)
DI, DQ,
AI, AQ 1)
IP 241USW, IP 244,
IP 246, IP 247, IP 252 1)
IP 240, IP 241, IP 242,
IP 242A, IP 242B, IP 243,
IP 281 1) 4) 5)
IP 245
IP 257 6)
IP 260,
IP 261
Load power supply
-951 1)
Electrical connection

System Manual
C79000-G8576-C199-06

Mechanical width

4-3

Central Controllers and Expansion Units Power Supply Units

1) Allow for particular module widths; additional slots to the right may be occupied (see Catalog ST 54.1).
2) In the CC with Order No. 6ES5 135-3UA41, only at Slot 163
3) Observe jumper setting on the IM 307; interrupt transmission is only possible at Slots 107 to 131.
4) Operation at Slots 27, 43, 59, 139, 147 is only possible with severely restricted functions, because no interrupts are wired.
5) IP 243 without D/A or A/D converter can be used at Slots 27, 43, 59, 139 and 147.
6) Allow 1 to 4 slots for the DI/DQ 482 to the right of the IP 257.

Caution

!

Do not insert modules at slots which are not intended for them, otherwise
these or other modules may be destroyed.
The following table shows which slots have particular characteristics. The
manuals for the individual modules explain how these characteristics can be
utilized.
Slot No. 3

Characteristic
PG Mux
possible 1)

11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163

0

1

2

3

4

5

6

7

Interrupt source
(process interrupt)
Battery backup
24 V supply
15 V supply
1) The numbers indicate the station numbers for programmer (PG) communication via PG multiplexers
of the COR 923C.

4-4

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

The modular packaging technique allows variable configuration of a CC with
modules and its adaptation to the particular automation task.
The various modules carry out the following tasks:

S CPU
The CPU processes the input signals of the PLC according to the user
program, and emits the results as output signals. The following CPUs can
be used in the S5-135U/155U PLC
– CPU 948
– CPU 928B
– CPU 928
– CPU 922

S Coordinators
By using a coordinator, you can configure the S5-135U/155U as a
multiprocessor controller with up to four task-oriented CPUs in different
combinations. Each CPU processes its program independently of the
others.

S I/O modules
The I/O modules provide the link to the process.

S IP module
The intelligent I/O modules (signal pre-processing modules) off-load the
CPU by independently executing compute-intensive tasks such as
controlling, counting and positioning.

S Interface modules (IMs)
If your CC has insufficient slots to insert all the modules required for your
automation task, you can increase the number of modules with expansion
units. The IM modules provide the link between central controller and
expansion units.

S CP module
CP modules allow point-to-point communication for data interchange
between two PLCs, between one PLC and an external unit, between one
PLC and a SINEC bus system or between one PLC and the COROS
operator control and process monitoring system. You can use additional
CP modules, such as the CP 581, CP 516, for the acquisition, storage,
administration and preprocessing of large volumes of data.

S VP module
VP modules enable the local acquisition and displaying (visualization) of
process data of a PLC of the SIMATIC S5.

System Manual
C79000-G8576-C199-06

4-5

Central Controllers and Expansion Units Power Supply Units

4.1.2

Installation

Installing the
Central Controller

The S5-135U/155U CC is designed for installation in cabinets, on racks and
walls. The S5-135/155U CC must only be accessible from the front for
connection and maintenance work.
Consult the Installation Guidelines in Chapter 4 for planning and
implementing the installation with respect to EMC.
Shown in the following figures are the important dimensions in mm for
installation of a CC.

482.6
465
310

440
225

SIMATICS5135U

0
5

266.35

328

44
127.5
138.4

432

221.8
459

260.9
265.9
SIMATICS5

SIEMENS

Filter Subdrawer

Figure 4-2

4-6

Mounting Dimensions of an S5-135U/155U Central Controller

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

An air supply as shown in the following illustration must be ensured.

Locking Bar
Exhaust
air

Exhaust
air

ÈÈ
ÈÈÈ
È
ÈÈ
ÈÈÈ
È
ÈÈÈÈÈÈÈÈÈ
ÈÈ
ÈÈ
ÈÈ
ÈÈ
ÈÈ
+

+

Rear Panel

Shield

+

Bus Connector

Guide Rail

ÈÈ
ÈÈÈÈÈÈÈÈÈ
ÈÈÈÈÈÈÈÈÈÈÈ

Bus PCB

Cable
Duct

+

ÈÈ
ÈÈ
ÈÈ
ÈÈ
ÈÈ
ÈÈÈÈÈ
ÈÈ ÈÈÈÈÈ
ÈÈÈÈÈ
ÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈ
ÈÈÈÈÈÈÈÈÈÈÈÈÈÈÈ
Fan

Heat Sink

Supply air

Filter Subdrawer
1)
d

Exhaust air

Additional PLC or EU
Baffle

Figure 4-3

Air Supply to the Central Controller
1)

System Manual
C79000-G8576-C199-06

d: Clearance > 87 mm when a baffle is used
d: Clearance > 89 mm when a filter subdrawer is fitted
d: Clearance > 75 mm without filter subdrawer

4-7

Central Controllers and Expansion Units Power Supply Units

You can use the mounting brackets on the subrack for installation in cabinets,
on racks and walls. Use M6 bolts or, for wall mounting, screws of suitable
size.
One person can carry out the installation work.
The mounting brackets can be fitted to the housing in the following ways:

5

32

16

Flush

Figure 4-4

Fitting the
Modules

Methods of Fitting the Mounting Brackets

The dimensions of the modules for the S5-135U/155U PLC comply with the
double-height Eurocard format (h x d = 233.4 x 160 mm).
There are modules with different mounting width. For example:
Slots Occupied

SPS 1)

Front Plate Width in mm

Example

1

1 1/3

20.3

CPU 922

2

2 2/3

40.6

CPU 948

4

1/3

81.3

CP 580

5

1) SPS standard-plug-in station: 1 SPS = 15.24 mm

4-8

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Proceed as follows to fit the modules:
Step

Action

1

Disconnect the CC from system power.

2

Slacken the two screws with which the locking bar is fixed to the subrack.

3

Pull the locking bar forward to its end stop.
–

The rail swivels up.

4

If there is a locking pin on the lower part of the module, turn it to the
horizontal position.

5

Grasp the module at the front plate, insert it into the lower and upper
guide rails and push it in.
–

6

The connectors at the rear will engage in the sockets on the
backplane bus, and the release lever on the lower part of the
module will be horizontal.

If a locking pin is fitted, push it in and rotate it 90 degrees.
–

If you have correctly fitted the module so far, it should no longer
be possible to pull it out of the subrack.

7

Swivel the locking bar down and push it back into the subrack.

8

Retighten the two screws on the locking bar.

Some I/O modules can also be fitted or removed during operation. Consult
the reference manuals for the I/O modules, under “Release circuit.”
Free slots can be covered with dummy front plates. This improves the flow of
cooling air in the unit. See the ordering information for order numbers.
Connections of
CPUs, CPs and
IMs

The connecting cables of CPUs, communication processors and EU interface
modules are connected with metal front connectors.
There are two types of metal front connector:
A metal front connector with slide lock is secured after plugging it in,
by sliding the lock downward.
A metal front connector with milled screws is secured to the unit with
the screws.
Note
Ensure that the connectors are assigned to the correct modules to avoid
damage.
The connection of signal lines for the I/O modules is described in Chapters 8
and 9.

System Manual
C79000-G8576-C199-06

4-9

Central Controllers and Expansion Units Power Supply Units

4.1.3

Startup
Start up the CC in the sequence of steps given here. This will take you up to
the first trial run of the CPU. Given in parentheses are references to the
chapters of the manual in which the subject is explained in detail.
To ensure a straightforward sequence for the startup, commence with one
CPU and no EUs.
Proceed according to the following steps to place the CC in operation:
Step

4-10

Action

1

Install the PLC so that the supply of air and exhaust air are unimpeded. If
you fit two or more units (CC and EU) in one cabinet, observe the
clearances and use baffles where necessary (see Chapter 3).

2

Fit a lithium battery (see Sections 4.3 and 4.4) or connect an external
backup battery and connect the rechargeable battery.

3

Fit the CPU and set the mode switch to STOP.

4

Connect the power supply and connect the 24 V DC load supply to the
monitoring input. Check the setting of the voltage selector switch (on 230/
120 VAC power supplies). Fit a protective cover over the AC terminals.

5

Switch on the power and, if present, the 24 V load supply.
Position the “Power” switch I.
Reaction: Green LED “Power Supply ok” in the “DC 5 V” field and in the
“DC 15/24 V” field light up.

6

Hold the CPU switch in the OVERALL RESET position and move the
switch from STOP to RUN.
Reaction: The “Stop” LED flashes rapidly.

7

Repeat Step 6.
Reaction: The “Stop” LED lights up constantly.

8

Keep the pushbutton in the RESET position and move the switch from
STOP to RUN.
Reaction: Green “Run” LED lights up, “BASP” LED (output inhibit) goes
off.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Startup and
Validity Check

The following flowchart provides an overview of the sequence for startup
and validity check of a CC with CPU inserted and with no user program. For
the CPU 948, all steps relating to the memory submodule are skipped.

Insert memory submodule in
CPU (not with the CPU 948)

CPU at “STOP”

Connect power supply unit

Switch on supply voltage

PS:
LED “DC5V”

No

and “DC 24V” on, all

PS:
Correctly wired?
Voltage Present?

No

others off
Replace bty
compartment

Yes

No

Yes

CPU:
LED “BASP” on
LED “STOP” flashing fast
all others off

Yes
Press
RESET
LED off

LED “RB
Low” on

No
Replace
rechargeable
battery

Yes

Yes
No
Press
RESET
LED off

LED “MB

Yes

Low” on

Check backup bty
and replace
if necessary

Fault
corrected

CPU general reset

Yes

LED “Fan
Fault” on

Check
Fan

No

Fault
corrected

No
Replace PS

Check load
voltage
connection

LED
“Voltage
Low” on

CPU:
LED “STOP” on
LED “BASP” on
all others off

No

CPU:
LED ”BASP” on
LED “STOP” flashing fast
all others
off

Replace CPU
or
repeat startup

No

Yes

Yes

Reset CPU: Set to “Reset,”
switch from “STOP” to “RUN”

Memory
submodule:
correctly inserted?

No

Insert memory
submodule correctly

Yes
CPU:
LED “RUN” on,
LED “BASP” off

Replace memory submodule
No

Yes
Unit O.K.

Figure 4-5

Startup

System Manual
C79000-G8576-C199-06

4-11

Central Controllers and Expansion Units Power Supply Units

4.1.4

Repair Guidelines
If measurements or testing become necessary whilst the unit is operational,
accident prevention regulations VBG 4.0 must be observed, especially the
permissible actions when working on active parts.
Only use tools that are suitable and approved for working on electrical
equipment.

S Repair of an automation system may only be carried out by the
SIEMENS customer service or by qualified personnel (see above).

S Always disconnect the AC power plug or open the isolating switch before
opening the unit. Wait at least 8 minutes before pulling out and opening a
power supply unit (see Section 4.2.3).

S Parts or components of a central controller may only be replaced by types
listed in Catalog ST 54.1 or in the appendix to this manual.

S Fuses may only be replaced by the same type.
S Instructions for maintenance of the individual components can be found
in the relevant chapters of this manual.

!

4-12

Warning
Unauthorized opening and improper repairs can result in death or serious
personal injury as well as considerable damage.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.1.5

Technical Specifications
Important for the USA and Canada
The following approvals have been granted for the central controllers and
expansion units:

S UL Listing Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E85972

S CSA Certification Mark
Canadian Standards Association (CSA) to Standard
C 22.2 No. 142, Report LR 63533C
Unit safety
The unit complies with:

VDE 0160, IEC 1131-2

Protection against overvoltage
Overvoltage Class 2 (not with PS -3NA12)

VDE 0160 A1

Class of protection

I

Type of protection
(when empty slots are covered by dummy front plates)

IP 20 to IEC 529/DIN 40050

Climatic ambient conditions (tested to DIN IEC 68-2/-1/2/3)
Ambient temperature in operation
(supply air measured at lower air inlet of the unit)

0 to 55 °C

Transportation and storage temperature

- 40 to 70 °C

Temperature variation:
in operation
during transportation and storage
(when delivered at less than 0 oC, at least 3 h

10 K/h max.
20 K/h max.

acclimatization because of possible
condensation)
95% max. at 25 °C, no condensation

Relative humidity:
in operation, during transportation and
storage
Altitude:
in operation

- 1000 m to + 1500 m above sea level
(1080 hPa to 860 hPa)

during transportation and storage

- 1000 m bis + 3500 m above sea level
(1080 hPa to 660 hPa)

Pollutants:
SO2

0,5 cm 3 / m 3, 4 days

H2S

0,1 cm 3 / m 3, 4 days

Mechanical ambient conditions (tested to DIN IEC 68-2-6)
Vibration during operation

System Manual
C79000-G8576-C199-06

10 to58 Hz (const. amplitude 0.075 mm)
58 to 500 HZ (const. acceleration 1g)

4-13

Central Controllers and Expansion Units Power Supply Units

Noise immunity, electromagnetic compatibility (EMC)
RFI suppression
Limit value class
Conducted interference on AC supply lines (230 V AC)
to EN 61000-4-4 / IEC 1000-4-4 (burst)
to IEC 1000-4-5
between two lines (ms pulses)

To EN 55011
A 2)
2 kV
1 kV
2 kV

between line and ground (ms pulses)
DC supply lines (24 V supply) to EN 61000-4-4 / IEC 1000-4-4
(burst)

2 kV

Signal lines to EN 61000-4-4 / IEC 1000-4-4 (burst)

2 kV 1)

Immunity to discharge of static electricity to EN 61000-4-2 /
IEC 1000-4-2 (ESD) 2)

Immunity of 4 kV contact discharge
(8 kV air discharge) is ensured with proper
installation (see Chapter 3).

Immunity to electromagnetic RF field 2)
amplitude modulated to ENV 50140 / IEC 1004-4-3

80 to 1000 MHz
10 V/m
80% AM (1 kHz)

Immunity to electromagnetic RF field 2)
pulse-modulated to ENV 50204

900 MHz
10 V/m
50% ED

Immunity to high-frequency sinusoidal to ENV 50141

0.15 to 80 MHz
10 V
80% AM

Mechanical data
Mechanical requirements

Installation in stationary equipment, subject to
vibration; installation on ships and in vehicles if
special installation rules are observed, but not on
the engine.

Weight

approx. 14 kg

Dimensions (W x H x D)

482.6 x 432 x 310 mm

1)
2)

4-14

Signal lines which do not serve to control the process, for example connections to the external I/O etc.: 1 kV
When cabinet door is closed.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.2

Expansion Units
This chapter contains information on the application, installation and
operation of the following expansion units.
Order No. of Expansion Unit

Interface Modules

Power Supply or Fan Subassembly

6ES5 183-3UA13
6ES5 183-3UA22

6ES5 955-3LC42
6ES5 955-3NC42

6ES5 184-3UA11
6ES5 184-3UA21

230/120 V AC fan subassembly
24 V DC fan subassembly

6ES5 185-3UA13
6ES5 185-3UA23
6ES5 185-3UA33
6ES5 185-3UA43

6ES5 955-3LC42
6ES5 955-3NC42
6ES5 955-3LF42
6ES5 955-3NF42

6ES5 187-5UA11

–

Various interface modules (IMs) are available for communication between
the CC and EUs and between EUs. Data transmission between CC and EU,
and therefore between CPU and I/O module, is governed by the IM. A
description of interface modules is given in Chapter 7.
The following table contains information on available types of expansion unit
with their main features.
EU Type

EU 183

EU 184

EU 185

EU 187

Own power supply

yes

no

yes

no

With fan

yes

yes

yes

no

With cable duct

yes

yes

yes

no

Number of slots

21

21

21

11

Pluggable modules:
DI/DQ
AI/AQ
IP without page
IP with page
CP

yes
yes
yes
no
no

yes
yes
yes
no
no

yes
yes
yes
yes
yes

yes
yes
no
no
no

With interrupt processing

no

no

no

no

Version

System Manual
C79000-G8576-C199-06

4-15

Central Controllers and Expansion Units Power Supply Units

4.2.1

Technical Description of the Expansion Units
The design of the EUs is comparable to that of the CC: they comprise a
compact housing with a type-dependant number of slots for modules and,
according to the type of EU, a cable duct, an integral power supply unit or
fan subassembly.
The mounting dimensions of the EU 183U, EU 184U and EU 185U are the
same as those of the 135U/155U CC (see Figs. 4-3 and 4-4). The EU 187U
has neither power supply unit nor cable duct. Its overall height and depth are
therefore different from those mounting dimensions of the other EUs.

440

225

266

SIMATICS5135U

Figure 4-6

Mounting Dimensions of the EU 187U

Modules and Slot
Assignments of
the Expansion
Units

The following tables show which modules can be inserted at which slots.

Modules and slot assignments of the EU 183U
Slot No.

3

11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163

Module type
IM 300
IM 310, IM 314,
IM 318
IM 317
IM 312-3
DI, DQ,
AI, AQ
Signal pre-processing
modules (IPs)

See current Catalog ST 54.1 for slot numbers

Monitoring
module 313

4-16

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Modules and slot assignments of the EU 184U
Slot No.

3

11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163

Module type
IM 312-5
DI, DQ,
AI, AQ
Signal pre-processing
modules (IPs)
Monitoring
module 313

See current catalog ST 54.1 for slot numbers

Modules and slot assignments of the EU 185U
Slot No.
Module type

3

11 19 27 35 43 51 59 67 75 83 91 99 107 115 123 131 139 147 155 163

Coordinator 923 C
Communikation
processors (CPs)
IM 314 R
IM 300
IM 310, IM 134
IM 318
IM 317
IM 308
DI, DQ,
AI, AQ
Signal pre-processing
modules (IPs)
Monitoring
module 313

See current catalog ST 54.1 for slot numbers

Slots 19 to 75 are programmer MUX-capable

Modules and slot assignments of the EU 187U
Slot No.
Module type
IM 312-5

3

19

35

51

67

83

99

115

131

147

163

DI, DQ,
AI, AQ
Monitoring
module 313

System Manual
C79000-G8576-C199-06

4-17

Central Controllers and Expansion Units Power Supply Units

4.2.2

Installing the Expansion Units
Like a CC, the EUs are designed for installation in cabinets, in racks and on
walls. To install an expansion unit, therefore, refer to the description for the
CC and Chapter 3.

4.2.3

Technical Specifications of the Expansion Units
S The technical specifications of the expansion units are the same as those
of the central controller except for the following (see Section 4.1.5).

4-18

S Weight

EU 183U: approx. 14 kg
EU 184U: approx. 13 kg
EU 185U: approx. 14 kg
EU 187U: approx. 11 kg

S Dimensions:

EU 187U: 440 x 266 x 225 mm

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.3

Power Supply Units
Power supply units are part of the S5-135U/155U central controllers and of
the EU 183 and EU 185 expansion units.

4.3.1

Product Overview
The following section provides an overview of power supply types, their
functions, LEDs and controls and their inputs and outputs.

Power Supply
Types

Your CC/EU contains one of the following power supply units (PSUs):
Type of PSU
(Designation)

Input
Voltage

6ES5 955-3LC42

120 V AC
230 V AC
(selectable)

5V/18A DC
15V/0.5A DC
24V/1A DC

Central controller
6ES5 188-3UA12
Expansion units
6ES5 183-3UA13
6ES5 185-3UA13

6ES5 955-3LF42

120 V AC
230 V AC
(selectable)

5V/40A DC
15V/2A DC
24V/2.8A DC

Central controller
6ES5 188-3UA22
Expansion units
6ES5 185-3UA33

6ES5 955-3NC42

24 V DC

5V/18A DC
15V/0.5A DC
24V/1A DC

Central controller
6ES5 188-3UA32
Expansion units
6ES5 183-3UA22
6ES5 185-3UA23

6ES5 955-3NF42

24 V DC

5V/40A DC
15V/2A DC
24V/2.8A DC

Central controller
6ES5 188-3UA52
Expansion units
6ES5 185-3UA43

Output Voltage

Application

The 5 V and 15 V output voltages are regulated; the 24 V output voltage has
coarse stabilization.
All four power supply units have safe electrical separation according to
VDE 0805/EN 60950.
Note
Power supply units are exclusively adapted to operation with CCs/EUs.

System Manual
C79000-G8576-C199-06

4-19

Central Controllers and Expansion Units Power Supply Units

Basic Functions

The power supply units offer the following functions:

S System power supply
All the system voltages required for operation of the modules in a CC or
EU are supplied.

S Power supply for backup (in the CC and EU 185):
A lithium battery or an external battery ensure data backup when the
system voltage is switched off or fails.
– The lithium battery remains in the CC/EU and ensures backup, even
during replacement of the power supply unit
– Instead of the lithium battery, an external battery can be connected for
data backup purposes. Situated on the front plate of the power supply
unit are two sockets to connect an external battery.
The rechargeable battery (in the power supply) continues to back up while
either the lithium battery or external battery is being replaced or fails,
ensuring that no data are lost.

S Heat removal
Three independent fans which are individually replaceable during
operation remove the dissipated power. If a fan fails, the supply voltage
for this fan is switched off and the other two fans continue operation at
increased speed.

Monitoring
Functions

The power supply units contain monitoring functions to detect the following
faults:

S Failure of system voltage
S Failure of output voltages
S Failure of an externally applied 24 V DC load voltage (voltage monitor)
S Fan failure or inadequate air flow
S Lithium battery failure
S Rechargeable battery failure
In this context, a voltage failure is equivalent to a drop of the monitored
voltage below a preset limit (see Section 4.3.6 of the Technical
Specifications).

Signaling
Functions

The failure of a monitored function is signaled by the power supply units:

S via LED indicators on the front plate;
S via relays with which signaling circuits can be switched;
S via signals to the S5 bus.

4-20

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Inputs and
Outputs

Based on the example of the 6ES5 955-3LF41 power supply unit, the
following figure shows the arrangement of inputs and outputs on the front
plate of the power supply units:

SIEMENS

1

L1

N

2

3

4

5

I
I

+

–

6

7

Warning
Alarm
max. AC 250 V/ 3A

Warning
max. AC 250V/3A

Alarm

8

+
–

9 10

11 12 13

14 15 16

Unlock
Fan3/Res.Batt

Unlock
Fan2

Unlock
Fan 1

+
–

Output
DC 24V 2,8A
3V=40A
5Vo.k.
15Vo.k.
24Vo.k.

Fault

Ext.Batt.
DC 4,5V

DC 5/15/24V
Internal

Battery

MB low
RB low
Batt.+Fan

Power

Fan

Fan1
Fan2
Fan3

Input
DC 24V Ext.

EN UH
CAUTION!
Voltage
Disconnect
selector
before
removing
power supply!

Voltage low

1 2 3 4 5 6 7 8 9 10

6ES5955-3LF42

AC120V4,5A
AC230V2,6A

Voltage Monitor

Reset

Enable
Power supply

AC line 50/60 Hz

.

+

–

17 18

Batt. 3,6V/5Ah
Use battery holder
C98100-A1155-B21
only!
Replace by
trained personnel
only!

The following table provides an overview of the labelling and purpose of the
inputs and outputs:
ID

System Manual
C79000-G8576-C199-06

Label

Element

Purpose

A

AC 120V 4.5A
AC 230V 2.6A

Screw terminals
1, 2, 3

AC connection and protective conductor

B

EN

Screw terminal 4

Enable Power Supply
Control input for power supply

C

UH

Screw terminal 5

Supply for EN

D

Input
DC 24V Ext.

Screw terminals
6 and 7

Voltage Monitor
Monitors 24 V load voltage for > 16 V

E

Fan Warning
max. 250V/3A

Screw terminals
8, 9, 10 (relay)

Indicates failure of a fan

F

Fan Alarm
max. 250V/3A

Screw terminals
11, 12, 13
(relay)

Indicates failure of at least two fans and
inadequate air flow; if jumper set
accordingly, output enable is the second
signal source

G

Battery
Warning
max. 250V/3A

Screw terminals
14, 15, 16
(relay)

Indicates that lithium battery or
rechargeable battery has dropped below
limit

H

3V = 40A

2 test sockets

Current measurement sockets for test
purposes only; no continuous operation;
linearity range 0.5 V/6.6 A to 3 V/40 A

I

Output
DC 24V 2.8A

Screw terminals
17, 18

Enable voltage for I/O modules

J

Ext.Batt.
DC 4.5V

2 input sockets

Input for an external 4.5 V backup
voltage

4-21

Central Controllers and Expansion Units Power Supply Units

LEDs and Controls

Apart from the jumpers, the LEDs and controls of the power supply unit are
fitted on the front plate. The following figure shows their locations:

SIEMENS

L1
1

2

4

I
I

3

5

+

–

6

7

8

9 10

11 12 13

14 15 16

+

.

A

D F
C E G

B

–

17 18

Unlock
Fan3/Res.Batt

Unlock
Fan2

Unlock
Fan 1

+
–

3V=40A
5Vo.k.
15Vo.k.
24Vo.k.

Alarm

+
–

Output
DC 24V 2,8A

Warning
max. AC 250V/3A

Batt.+Fan

Warning
Alarm
max. AC 250 V/ 3A

MB low
RB low

Power

N

Fault

Ext.Batt.
DC 4,5V

DC 5/15/24V
Internal

Battery

Reset

Input
DC 24V Ext.

EN UH
CAUTION!
Voltage
Disconnect
selector
before
removing
power supply!

Fan

Fan1
Fan2
Fan3

1 2 3 4 5 6 7 8 9 10

6ES5955-3LF42

AC120V4,5A
AC230V2,6A

Voltage Monitor

Voltage low

Enable
Power supply

AC line 50/60 Hz

Batt. 3,6V/5Ah
Use battery holder
C98100-A1155-B21
only!
Replace by
trained personnel
only!

I
K M
L
H J

The labelling and purpose of the LEDs and controls are given in the
following table:
ID

Element

Purpose

A

Voltage
selector 1)

Switch

Voltage selector switch:
choice of 120 V or 230 V

B

Power

Switch

Standby On/Off switch (not system
On/Off switch)

C

Voltage low

Red LED

Low voltage at load voltage monitor input

D

Fan 1

Red LED

Failure of Fan 1

E

Fan 2

Red LED

Failure of Fan 2

F

Fan 3

Red LED

Failure of Fan 3

G

Alarm

Red LED

Indicates failure of at least two fans of
insufficient air flow

H

MB low

Yellow LED

Lithium battery/external battery voltage
below preset limit (3V)

I

RB low

Yellow LED

Rechargeable battery voltage below preset
limit (3V)

J

Reset Batt.+Fan

Pushbutton

Reset of LEDs D, E, F, G, H, I when fault
cleared

K

5V o.k.

Green LED

Lights up to indicate output voltage
within permissible range

L

15V o.k.

Green LED

Lights up to indicate output voltage
within permissible range

M

24V o.k.

Green LED

Lights up to indicate output voltage
within permissible range

1)

4-22

Label

Only on the 6ES5 955-3LC42 and 6ES5 955-3LF42

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.3.2

Setting and Connecting the Power Supply Unit
Before starting up your power supply unit, you must carry out certain steps
according to your requirements with respect to power supply behavior in the
event of a fault.
Power supply units are delivered in the following state:

S Fitted in the CC or EU frame which you ordered
S With preset jumpers
S AC line voltage set to 230 V (-3LC42, -3LF42)
If you wish to retain this setting, you can skip Steps 2 to 4 and 9.
If you do not wish to fit a filter subdrawer, skip step 8.
Step

System Manual
C79000-G8576-C199-06

Action

1

Check the setting and cabling

2

Remove the power supply unit

If required

3

Set the jumpers

If required

4

Fit the power supply unit

If required

5

Wire the power supply unit to the installation (including
fitting an isolating device to disconnect the AC line
voltage)

6

Fit the lithium battery

7

Remove the right-hand fan and connect the rechargeable
battery

8

Fit the filter subdrawer

If required

9

Set the voltage selector switch

If required

10

Switch the PSU on for the first time

4-23

Central Controllers and Expansion Units Power Supply Units

Brief Instructions
for Startup

The following table shows the procedure for placing the power supply unit
(PSU) in operation without changing the jumper setting:
Stage

Description

1

Fit the PLC, allowing for clearances for access in the event of repairs
and for adequate ventilation. Observe chassis grounding.

2

Fit the lithium battery (if available) in the battery compartment on the
right front of the power supply unit (ensure correct polarity).
Hinweis: Die Lithium-Batterie müssen Sie getrennt bestellen (siehe
Bestellhinweise).

3

Remove the right-hand fan subassembly, plug in the red positive lead of
its rechargeable battery and reinsert the fan.

4

Check that the voltage selector switch is set to your desired voltage.

5

Connect the 24 V load voltage leads to the “Voltage Monitor” terminals.

6

When connecting the AC leads, fit an isolating device to isolate the
power supply unit from the AC line voltage.

7

Connect the primary voltage leads and the protective conductor.

8

Switch on the primary voltage and the 24 V load voltage.

9

Use the “Power” switch to switch on the power supply unit.

10

If the required basic load is in circuit, no red LED lights up and the
power supply unit is operational.

All activities relating to startup of the power supply units are described in
detail on the following pages.

4-24

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Establishing the
Jumper Settings

The power supply unit is delivered with the settings shown in bold print in
the following table.
Mark your chosen settings in the right-hand column and use this chart for the
subsequent implementation.

Function Selection

Jumper

Setting

Application/Note

(X)

Battery monitor
–

switched on for
rechargeable battery and battery

MM - NN
MA - NA

closed
closed

Redundant backup

–

switched on for battery and
off for rechargeable battery

MM - NN
MA - NA

closed
open

If, for example, no redundance is
required in backup, i.e. the rechargeable
battery is missing

–

switched off

MM - NN
MA - NA

open
irrelevant

For example, monitoring is not needed
for EU without backup

Reaction of battery monitoring
following battery failure
–

/BAU signal active following
return of line voltage

MB - NB

open

–

/BAU signal active following
return of line voltage and during
operation

MB - NB

closed

The possibility of evaluating the battery
monitoring during operation is
dependent on the CPU in use

After failure of more than one fan or
inadequate air flow
–

PSU shutdown

F-R

closed

–

No PSU shutdown

F-R

open

Caution: To prevent overheating of
modules, the PSU must be shut down
after 60 s at the latest (for example, by
time relay)

Voltage monitor
–

switched off

BA-EX

closed

Monitoring of load voltage input
switched off

–

switched on

BA-EX

open

Monitoring of load voltage input
switched on

Relay alarm
–

driven by fan monitor and
output inhibit

BB-AA

closed

–

driven only by fan monitor

BB-AA

open

System Manual
C79000-G8576-C199-06

Fault message
g initiated by
y fan
f il /
failure/output
iinhibit
hibi active;
i can bbe
signaled to control room, for example.
Fault message initiated by fan failure;
can be signaled to control room, for
example.

4-25

Central Controllers and Expansion Units Power Supply Units

Function Selection

Jumper

Setting

Application/Note

(X)

Mains buffering
FX-VA
6-22

closed
closed

A stored energy time of 5 to 10 ms is
guaranteed in the event of a power
failure.
The stored energy time is dependent on
the input voltage and the load.

FX-VA
6-22

closed
open

A stored energy time of 20 to 30 ms is
guaranteed in the event of a power
failure.
The stored energy time is not dependent
on the input voltage and the load.

FX-VA
6-22

open
irrelevant

A stored energy time of w 20 ms is
guaranteed in the event of a power
failure.
The stored energy time is dependent on
the input voltage and the load.

If your selection is the same as all the settings marked in bold print, you need
not change the jumper settings.

Establishing the
Wiring

Wiring of the power supply unit must be planned within the scope of wiring
of the entire control system. The information required for the purpose and
decision-making aids, for example, for local or central grounding, can be
found in Chapter 3: Installation Guidelines.

Establishing the
Signaling Circuits

Three relay outputs allow you to install additional external signaling circuits
for fault states, for example, to connect a cabinet lamp or horn.
The following table contains the information required on the relay states:

Relay
(Normal Operational State)

(Fault State/Idle State)

Warning

All fans are in order.

One or more fans have failed.

Alarm

Adequate air flow, at least two fans are running.

Inadequate air flow or at least two fans have
failed.

BatteryWarn Lithium battery and rechargeable battery are in
ing
order (Ubatt ext not connected).

4-26

Lithium battery or rechargeable battery has failed
(no Ubatt ext ).

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Setting up the
Control Input for
the Power Supply

The following applies to input EN (Enable Power Supply):

S Input EN monitors the voltage for < 3.6 V; it enables the output voltage at
3.2 V.

S If two or more units are to be controlled jointly, connect input EN of the
PSU in the central controller to the EN inputs of the PSUs in the
expansion unit. Connect the auxiliary voltage UH, for example, to these
inputs. In the event of failure of the PSU in the central controller, all units
will then be switched off with the appropriate jumper settings.
Not more than 7 EN inputs may be connected to one UH output (front
terminal).

Establishing the
Cables

The following applies to selecting the cables for the terminals:

Terminals
Power supply
AC line

DC line

Cabling

Max. Permissible Conductor Cross-Sections

Phase

L1

4 mm2 solid or 2.5 mm2 flexible

Neutral

N

4 mm2 solid or 2.5 mm2 flexible

Protective cond.

PE

4 mm2 solid or 2.5 mm2 flexible

Positive

L+

4 mm2 solid or 2.5 mm2 flexible

Chassis 0 V

M

4 mm2 solid or 2.5 mm2 flexible

Protective cond.

PE

4 mm2 solid or 2.5 mm2 flexible

Load voltage input (Voltage 24 V input (may be omitted if jumper 4 mm2 solid or 2.5 mm2 flexible
monitor, Ext. 24 V DC)
BA-EX is closed)
Enable power supply

Set jumper from EN-UH or apply
w 3.2 V voltage at EN, with respect
to output chassis ground

4 mm2 solid or 2.5 mm2 flexible

Relay terminals, also
suitable to 230 V AC / 3 A

4 mm2 solid or 2.5 mm2 flexible

Monitor output for 24 V

4 mm2 solid or 2.5 mm2 flexible

Note
A voltage of more than 50 V must not develop between the output voltages
and the protective conductor potential.

System Manual
C79000-G8576-C199-06

4-27

Central Controllers and Expansion Units Power Supply Units

Removing the
Power Supply Unit
When to Remove
the PSU

You must remove the power supply unit if you:

S change the jumper settings
S send the power supply unit in for repair.

!

Caution
Power supply units may only be removed when power is switched off.
If 230 V I/O modules are fitted, you must ensure before removing the power
supply unit that the subrack is grounded when the PSU is removed, or the
230 V supply for these modules is switched off.

When the power supply unit is removed, the connection between backup
battery and backplane bus remains; this ensures backup of the user program.

How to Remove
the PSU

Proceed according to the following steps to remove the power supply unit:
Step
1

Switch the Power switch off
(standby On/Off).

2

Disconnect the power supply unit form the AC line voltage.

3

Detach the connections of all leads from the front terminals.

4

Important
p
Before pulling out the PSU, wait at least 8 minutes after switching off the
power so that the electrolytic capacitors can discharge.

!

4-28

Action

5

Slacken the fixing screws on the left and right of the PSU.

6

Pull the PSU out.
There are grips to pull it out under the unlock fan openings.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Setting the
Jumpers
Locations of
Jumpers

The jumper locations are given in the following figure:

NB MB
MA NA

F
R

NN MM

BB
BB AA
AA

Setting the
Jumpers

FX

22

VA

EX
EX BA

To change the jumper settings, it is best to use pincers or a fine screwdriver.
Proceed as follows to change the jumper settings:
IF...

System Manual
C79000-G8576-C199-06

6

THEN...

You wish to open the jumper,

press the flexible jumper wire down and
pull it out.

You wish to close the jumper,

press the flexible jumper wire down and
insert it.

4-29

Central Controllers and Expansion Units Power Supply Units

Fitting the Power
Supply Unit

!

Caution
For safety reasons, the power supply unit may only be operated in the
housing provided for the purpose.
The protective conductor must always be connected.

How to Fit the PSU

After carrying out setting, installation and repair work, proceed according to
the following steps to refit the power supply unit in the frame:
Step

Action

1

Push the PSU into the guide rails until it locks in place. You can use one
hand to support the PSU from below; this facilitates fitting in the guide
rails.

2

Secure the PSU with the fixing screws on the left and right of the unit.

!

Caution
Since the fixing screws also provide the protective conductor connection to
the subrack, they must be tightened before the power cable is connected.

Wiring the Power
Supply Unit
How to Wire
the PSU

Wiring of the PSU is carried out within the scope of overall wiring for your
controller, according to your requirements and the section entitled
“Establishing the settings and cabling.”
Terminals with dangerous touch-voltages must be covered with caps. Use
only the original self-tapping screws provided when you fit the caps for the
first time.

4-30

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Starting up with a
Lithium Battery
When do you
Require a Lithium
Battery?

Whether or not you require a lithium battery depends on what type of backup
you require for your system. The following table will help you to decide.
IF...

THEN...

You require long backup times and do not want to
supply an external backup voltage,

you need a lithium battery.

You require redundant backup and do not want to
supply an external backup voltage,

you need a lithium battery.

Short backup times are sufficient,

you do not need a lithium
battery.

You do not require redundant backup,

you do not need a lithium
battery.

The lithium battery must be ordered separately (see Ordering Information).
Notes Relating to
the Lithium Battery

!

The backup battery (type C) contains lithium (more than 0.5 g) and is
delivered separately from the power supply unit, because of special shipping
regulations.
Depending on the manufacturer, the battery’s plus pole may have a protective
cover. You must remove this cover before you place the battery in the battery
compartment.
Caution
Improper replacement of the battery can result in the danger of explosion.
If should only be replaced by the same type or an equivalent one
recommended by the manufacturer. Used batteries should be disposed of
according to the manufacturer’s instructions.
The backup battery must be fitted before the programmable controller is
started up. Without a backup voltage, the PLC will remain in the Stop state
after system voltage is switched on.
Only use battery compartments marked -A1155-B21 (red label).

How to Fit the
Lithium Battery

Fit the lithium battery in the following steps:
Step

System Manual
C79000-G8576-C199-06

Action

1

Slide the battery compartment cover (A) downwards.

2

Pull the battery compartment (B) out.

3

Insert the lithium battery in the battery compartment.
Important: Ensure correct polarity.

4

Slide the battery compartment in.

5

Close the cover.

4-31

Central Controllers and Expansion Units Power Supply Units

+

*

Battery Compartment (B)

Cover (A)

!

Warning
Risk of danger to persons and property, danger of giving off harmful
substances.
If handled incorrectly, a lithium battery can explode. If disposed of
incorrectly, old lithium batteries can release harmful substances. You must
therefore observe the following guidelines:
S Do not throw new or discharged batteries onto a fire and do not solder
onto the body of the cell (max. temperature 100 °C (212 5F)). Do not
recharge them. Order your replacement battery from Siemens only (for
order number see ordering instructions). This ensures that you only use a
short-circuit-protected type.

S The lithium battery is subject to regulations for hazardous materials. You
should observe these regulations when you ship the battery, for example,
by using the original packaging.
Used batteries should be returned to the manufacturer or a recycling
station if possible or disposed of as hazardous waste. The guidelines for
transporting hazardous materials should be observed.

Starting Up
without a Lithium
Battery

If you want to start up one of the central controllers or expansion units
without a battery, you can do either of the following:

S You can connect only the rechargeable battery, or
S You can supply an external backup voltage.

Supplying an
External Backup
Voltage

4-32

Apply a backup voltage of 4.5 V DC via the input sockets labelled “Ext.Batt.
DC 4.5 V.” The input sockets are situated on the front panel of the power
supply. Ensure that you have the correct polarity.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Removing the
Right-Hand Fan
and Connecting
the Rechargeable
Battery
Location of Fans
and Rechargeable
Battery

The three fans are situated under the power supply unit. The rechargeable
battery is fitted in the right-hand fan subassembly.

How to Connect
the Rechargeable
Battery

Proceed according to the following steps:

Releasing the Fan
Lock

Step

Action

Result

1

Place one hand under the right-hand
fan; with the other hand, insert a
screwdriver (DIN 5265, blade width
3.5-6.5 mm) into the right-hand unlock
fan opening.

When the screwdriver is pulled
out, the snap hook is released. By
pulling on the round hole on the
underside of the fan subassembly
it swings down and can be pulled
out.

2

Connect the red connecting cable to the
battery.

The battery is connected.

3

Insert the fan subassembly in the
housing with the tab situated at the rear,
and swivel it up.

The fan subassembly locks in
place.

The following figure shows how to release the fan lock:

3 4 5 6 7 8 910

SIEMENS

Batt.3,6V/5Ah

1 2

Use battery holder
C98100-A1155-B21
only!
Unlock
fan

System Manual
C79000-G8576-C199-06

Unlock
fan

Unlockfan

Replace by
trained personnel
only!

4-33

Central Controllers and Expansion Units Power Supply Units

Fitting the Filter
Subdrawer
Option

The filter subdrawer with fixing grid, two plug-in guide rails and the
corresponding filter mats are available as an option (see the ordering
instructions for the order numbers).

Where to Fit the
Filter Subdrawer

To insert a filter, you must secure the filter subdrawer to the lower side of the
power supply unit housing.

How to Fit the
Filter Subdrawer

Proceed as follows:
Step

Action

1

Install the guide rails in such a way that the round tabs fit into the
corresponding openings on the lower side of the PSU.

2

Insert a filter mat in the filter subdrawer and secure it with the enclosed
fixing grid.

3

Position the filter subdrawer in the guide rails, push it back and swivel it up
so that it locks in place.

Setting the Voltage
Selector Switch

How to Set the
Voltage Selector
Switch

On the AC power supply units, the voltage selector switch is situated on the
front plate and marked Voltage Selector. You can select a voltage of 120 V or
230 V. The factory setting is 230 V.
Set the voltage according to your requirements
Step

4-34

Action

1

Disconnect the power supply unit from the line voltage.

2

Use a screwdriver to remove the transparent cover.

3

Set the voltage selector switch to your required voltage.

4

Refit the transparent cover.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Switching on the
Power Supply Unit
for the First Time

!

How to Switch On
the Power Supply
Unit

Caution
If you have set the voltage selector switch to 120 V, but the actual voltage
value is 230 V, the power supply unit may be damaged when line voltage is
switched on.

When you have made all the settings, switch the power supply unit on as
follows:
Step

Action

Result

1

Switch the power supply unit
on with the Power switch.

2

Switch the system voltage on.

If the required basic load (see Section
4.4.6, Technical Specifications) is in
circuit, the power supply unit will start.
The green LEDs

“5V o.k.”
“15V o.k.”
“24V o.k.” light up.

The fans run.

After a maximum of 6 minutes, the rechargeable battery has been charged
sufficiently for you to be able to start up the central controller or the
expansion unit.
The charge time for the rechargeable battery can be up to 46 hours,
depending on how low the battery was. Note that during this time, backup
using the rechargeable battery is restricted.
Once the rechargeable battery is fully charged, the following load-dependent
backup times apply:

System Manual
C79000-G8576-C199-06

Ibackup mA

0.25

1

2

3

4

5

Backup time in weeks

18.8

6.3

3.4

2.3

1.7

1.4

4-35

Central Controllers and Expansion Units Power Supply Units

4.3.3

Fault Indications/Fault Diagnostics
This section explains where and how faults are indicated, and how to
interpret the LEDs.

Where are Faults
Indicated?

Faults of the system power supply, load power supply, battery supply and
fans are indicated by LEDs on the front plate of the power supply unit.

How are Faults
Indicated and
Interpreted?

When all monitoring circuits are switched on (jumper settings), the following
indications can appear:
LED Indication

Cause

Action

“Voltage low” LED lights
up.

The voltage at the voltage monitor is
less than 14 V.

“MB low” LED lights up.

The lithium battery has failed or the
battery compartment is faulty.
(Precondition: no external bty voltage
is present).

Replace backup
battery or battery
compartment

“RB low” LED lights up.

The rechargeable battery has failed.

Replace
rechargeable
battery

“Fan 1” LED lights up.

The speed of Fan 1 has dropped or
Fan 1 has stopped.

Replace fan

“Fan 2” LED lights up.

The speed of Fan 2 has dropped or
Fan 2 has stopped.

Replace fan

“Fan 3” LED lights up.

The speed of Fan 3 has dropped or
Fan 3 has stopped.

Replace fan

At least 2 “Fan” LEDs light
up as well as the “Alarm”
LED.

At least 2 fans have failed.

Replace fan

All 3 “Fan” LEDs flash and
the “Alarm” LED lights up.

The air flow is inadequate.

Replace filter
mat

The fan error is indicated approximately 6 s after the monitoring circuits are
switched on or 6 s after a reset is performed.

4-36

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Other Faults

Other faults can be indicated by the green LEDs on the front plate going off.
LEDs
Green LEDs go off
and the power
supply
l ffails.
il

System Manual
C79000-G8576-C199-06

Possible Cause
The Enable jumper is
out of place

Action
Check the jumper.

Latching Off-switching Switch the supply voltage off and on
by overvoltage at
again. If this does not clear the fault,
output
there is an internal fault.
Internal fault in the
PSU

Send in the PSU for repair.

Base load too low

Increase the base load

4-37

Central Controllers and Expansion Units Power Supply Units

Fans and Fan
Monitoring

Causes
Fans

The following table contains several examples.
Requirement:
Enable EN present, jumper F - R closed
LED Indication

Air filter/
air flow

Fan1 to Fan3

All fans in
order

In order

All LEDs dark

One fan
failed

In order

Two fans
failed

In order

All fans in
order

Dirty/halved All LEDs
flashing

Relay
Fan
Warning

Alarm
Dark

Reaction
Fan
Alarm

-

–

5 V, 15 V, 24 V present,
fans 1 to 3 running

Corresponding Dark
LED lit

Active

–

5 V, 15 V, 24 V present,
faulty fan switched off, the other two
fans running at increased speed

Corresponding Lit
LEDs lit

Active

Active

Power supply switches off

–

Active

Power supply switches off

Lit

Requirement:
Enable EN present, jumper F - R open
Causes
Fans

LED Indication
Air filter/
air flow

Fan1 to Fan3

All fans in
order

In order

All LEDs dark

One fan
failed

In order

Two fans
failed

In order

All fans in
order

Dirty/halved All LEDs
flashing

Relay
Alarm
Dark

Fan
Warning

Reaction
Fan
Alarm

–

–

5 V, 15 V, 24 V present,
fans 1 to 3 running

Corresponding Dark
LED lit

Active

–

5 V, 15 V, 24 V present,
faulty fan switched off, the other two
fans running at increased speed

Corresponding Lit
LEDs lit

Active

Active

5 V, 15 V, 24 V present,
faulty fans switched off, one fan
running at increased speed

–

Active

5 V, 15 V, 24 V present,
fans 1 to 3 running

Lit

Note:
When the jumper “BB - AA” is closed the relay “Fan Alarm” is also
activated by the “output inhibit” signal (BASP via BASPA).

4-38

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Rechargeable
Battery and
Battery Monitoring

The following table contains several examples.

Causes
Rechargeable
Battery

Relay
Battery or external
supply

Jumpers

LED Indication

Battery
Warning

RB

MB

/BAU

In Order

In Order

MA-NA closed
MM-NN closed
MB-NB open

–

Dark

Dark

Inactive

Faulty

In Order

MA-NA closed
MM-NN closed
MB-NB open

Active

Lit

Dark

Inactive

In Order

Faulty

MA-NA closed
MM-NN closed
MB-NB open

Active

Dark

Lit

Inactive

Faulty

Faulty

MA-NA offen
MM-NN closed
MB-NB open

Active

Lit

Lit

Active

Not monitored

In Order

MA-NA open
MM-NN closed
MB-NB open

–

Dark

Dark

Inactive

Not monitored

Faulty

MA-NA open
MM-NN closed
MB-NB open

Active

Dark

Lit

Active

Not monitored

Not monitored

MA-NA irrelevant
MM-NN open
MB-NB open

–

Dark

Dark

Inactive

Note:
Jumper MB - NB open: when line voltage returns the signal /BAU (battery
failure) is activated by a corresponding error.
Jumper MB - NB closed: when line voltage returns and during operation the
signal /BAU (battery failure) is activated by a corresponding error.

System Manual
C79000-G8576-C199-06

4-39

Central Controllers and Expansion Units Power Supply Units

4.3.4

Maintenance and Repairs

Lithium Battery

The lithium battery should be replaced when a battery failure is indicated.
The backup times of the lithium battery are given in the following table:
Ibackup mA

0.25

1

2

3

4

5

New battery,
backup time in weeks

81.5

27.4

14.5

9.9

7.5

6.0

Battery 3 years old,
backup time in weeks

64.2

21.6

11.5

7.8

5.9

4.8

Fans

If a fan fails, replace it as quickly as possible. The behavior of the power
supply in the event of fan failure is described in Section 4.3.5.

Rechargeable
Battery

The rechargeable battery should be replaced at regular intervals (service life
of 6 years at 40 oC (104 oF) ambient temperature). With a failed power
supply and failed battery, the backup times of the rechargeable battery are as
follows:

Filter Mat

4-40

Ibackup mA

0.25

1

2

3

4

5

Backup time in weeks

18.8

6.3

3.4

2.3

1.7

1.4

The replacement intervals for the filter mat (with the air filter option) depend
on the ambient conditions under which the power supply unit is in operation.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Replacing the
Lithium Battery

The lithium battery can be replaced without memory loss if the PSU is
switched on, the rechargeable battery is in order or you apply an external
(4.5 V) voltage to the “Ext.Batt.” terminals.

How to Replace
the Lithium Battery

Replace the lithium battery in the following steps:
Step

Action

1

Slide the battery compartment cover down.

2

Pull the battery compartment out.

3

Remove the old lithium battery from the battery compartment by inserting a
screwdriver through a hole in the compartment base to push the battery
upwards.

4

Insert the new lithium battery in the battery compartment
Important:
Ensure correct polarity.

5

Slide the battery compartment in.

6

Close the cover.

7

Press the Reset button.
Result (only with PSU on):
– “MB low” LED goes off.
– Contacts 14 and 15 of the
Battery Warning relay are bridged.

Replacing a Fan

Location of the
Fans

The three fans are situated at the bottom of the power supply unit and can be
individually replaced during operation.

Before
Replacement

If you operate your power supply with a filter, you must first release the filter
subdrawer and pull it out before you can replace a fan (see Section entitled
“Replacing the Filter Mat”).

System Manual
C79000-G8576-C199-06

4-41

Central Controllers and Expansion Units Power Supply Units

How to Replace a
Fan

The following steps are necessary to replace a fan:
Step

Action

Result

1

Place one hand under the fan
you wish to replace, and use the
other hand to insert a
screwdriver (DIN 5265, blade
width 3.5-6.5 mm) into the
unlock fan opening.

When the screwdriver is pulled
out, the snap hook is released.
By pulling on the round hole on
the underside of the fan subassembly it swings down and
can be pulled out.

2

– If this is not the right-hand fan subassembly, go directly to
Step 3 after removing the old fan subassembly.
– If this is the right-hand fan subassembly, proceed as follows:

3

4-42

Step

Action

2a

Unscrew the rechargeable bty from below.

2b

Disconnect the connecting cable.

2c

Insert the rechargeable bty in the new fan
subassembly (see section entitled “Replacing the
rechargeable battery”) and reconnect the
connecting cable.
Important:
Ensure correct polarity.

Insert the new fan subassembly
with the tab at the rear into the
housing, and swivel it up.

The fan subassembly locks in
place.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Releasing the Fan
Lock

The following figure shows how to release the fan lock:

3 4 5 6 7 8 910

SIEMENS

Batt.3,6V/5Ah

1 2

Use battery holder
C98100-A1155-B21
only!
Unlock
fan

After Replacement

Unlock
fan

Replace by
trained personnel
only!

After replacement, press the Reset button, the monitor will become active 6
secs after the Reset button is pressed.
IF...

System Manual
C79000-G8576-C199-06

Unlockfan

THEN...

the relevant “Fan” LED goes off,

the fan is correctly installed.

the relevant “Fan” LED does not go off,

the fan is incorrectly installed. Make a
step-by-step check to ensure correct
replacement.

the relevant “Fan” LED goes off but the
“Warning” relay does not pick up,

another fan has failed and another “Fan”
LED lights up. Replace the second fan
also.

4-43

Central Controllers and Expansion Units Power Supply Units

Replacing the
Rechargeable
Battery
Location of the
Rechargeable
Battery

!

The rechargeable battery is situated in the right-hand fan subassembly.
Caution
Do not place the rechargeable battery in contact with fire or heat and do not
short-circuit it.
The rechargeable battery must not be destroyed or disassembled!
Nickel-cadmium batteries contain an alkali electrolyte which can harm the
skin and damage clothing.
If your skin or your eyes make contact with the electrolyte, rinse
immediately with clean water and consult a doctor.

Before
Replacement

If you operate your power supply with a filter, you must first release the filter
subdrawer and pull it out before dismantling the right-hand fan and replacing
the rechargeable battery (see section entitled “Replacing the Filter Mat.”

How to Replace
the Rechargeable
Battery

The rechargeable battery can be replaced during operation. Proceed as
follows:
Step

Action

1

Insert a screwdriver (DIN 5265, blade width 3.5-6.5 mm) into the
right-hand unlock fan opening.

2

Swing the right-hand fan subassembly out (by placing your finger in the
round opening on the underside at the front and pulling downwards).
Result:

“Fan 3” LED indicates failure of the right-hand fan and
the other two fans operate at increased speed.

3

Slacken the screws on the bottom of the fan subassembly and pull out the
rechargeable battery.

4

Disconnect the connecting cable of the rechargeable battery.

5

Connect the cable to the new rechargeable battery.
Important:
Ensure correct polarity (red terminal on plus, black terminal on minus, see
figure “Replacing the rechargeable battery in the fan subassembly”).

6

Insert the new rechargeable battery pack in the left-front part of the fan
subassembly (plus pole to the right). Ensure that the black connecting cable
is lying on the floor of the battery compartment when you insert the battery.
Secure it with the screws from below.

7

Insert the fan subassembly with the tab at the rear into the housing and
swivel it up until it locks in place.

8

Press the Reset button.
With a fully discharged battery, the message can only be acknowledged
after at least 6 minutes.

4-44

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

After Replacement

The recharging time for the battery may be up to 46 hours, depending on its
state of charge. Please note that backup via the battery is only possible within
limits during this time.
If the rechargeable battery does not work after replacement, there may be the
following faults:
IF...

THEN...

“RB low” LED does not go off after the rechargeable battery is incorrectly connected
6 minutes,
or faulty or the charging circuit in the PSU is
faulty.
“RB low” LED goes off but the
relay does not pick up,

the battery has failed and the yellow “MB low”
LED lights up or the battery compartment is
faulty.

Replacing the
Rechargeable
Battery in the Fan
Subassembly

Fan
subassembly

red
Rechargeable
battery

Hole
black

System Manual
C79000-G8576-C199-06

4-45

Central Controllers and Expansion Units Power Supply Units

Replacing the
Filter Mat
Inadequate Air
Flow

If the filter mat is clogged and the power supply unit no longer receives
sufficient air, the “Alarm” LED lights up, LEDs for “Fan 1,” “Fan 2” and
“Fan 3” flash and the “Alarm” relay picks up. The fault can be cleared by
replacing the filter mat (see ordering information for the order number).

How to Replace
the Filter Mat

Correct the fault in the following steps:
Step

Action

1

Release the filter subdrawer.

2

Swivel the filter subdrawer downwards and pull it forwards and out.

3

Remove the old filter mat.

4

Insert a new filter mat in the filter subdrawer.

5

Place the distance grid on the new filter mat.

6

Insert the filter subdrawer in the guide rails, slide it back and swivel it up so
that it locks in place.

7

Press the Reset button.
Result:

4-46

– Fault LEDs for “Alarm,” “Fan 1,” “Fan 2” and
“Fan 3” go off.
– Contacts 11 and 12 are closed in the “Alarm” relay.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Replacing a Power
Supply Unit

If it should be necessary to replace the power supply unit in a system during
commissioning or during operation, we recommend you proceed as follows:
Requirement:
Redundant backup, “Spare power supply” without rechargeable battery
(standard spare part).
The lithium battery in the rack is in full working order.
Step

Action

1

Disconnect the faulty power supply from the system voltage and remove it.

2

Set the jumpers on the spare power supply according to your needs.

3

Push the spare power supply into the rack and screw it in place.

4

Remove the right-hand fan subassembly from the defective power supply.

5

Remove the rechargeable battery from the fan sub- assembly.

6

Replace the right-hand fan subassembly in the defective power supply.

7

Remove the right-hand fan subassembly from the spare power supply.

8

Connect up the spare power supply.

9

Switch on the system voltage and the power supply in any order.
Reaction:
– The system runs up
– Both fans run at an increased speed
– The LEDs “Fan 3” and “RB low” light up.

10

Insert the rechargeable battery in the fan subassembly and connect it up.

11

Reinsert the right-hand fan subassembly.

12

After the system has run up, press the reset switch on the spare power
supply.
Reaction:
– The LED “Fan 3” goes out
– The fans run at their normal speed again
– The LED “RB low” shows the charge state of the rechargeable battery.

System Manual
C79000-G8576-C199-06

4-47

Central Controllers and Expansion Units Power Supply Units

Requirement:
Redundant backup, “Spare power supply” with rechargeable battery. The
lithium battery in the rack in in full working order.
Step

Action

1

Disconnect the faulty power supply from the system voltage and remove it.

2

Set the jumpers on the spare power supply according to your needs.

3

Push the spare power supply into the rack and screw it in place.

4

Remove the right-hand fan subassembly from the spare power supply.

5

Connect up the replacement power supply.

6

Switch on the system voltage and the power supply in any order.
Reaction:
– The system runs up
– Both fans run at an increased speed
– The LEDs “Fan 3” and “RB low” light up.

7

Reinsert the right-hand fan subassembly.

8

After the system has run up, press the reset switch on the spare power
supply.
Reaction:
– The LED “Fan 3” goes out
– The fans run at their normal speed again
– The LED “RB low” shows the battery charge state.

Requirement:
No backup
Step

Action

1

Disconnect the faulty power supply from the system voltage and remove it.

2

Set the jumpers on the spare power supply according to your needs.

3

Push the spare power supply into the rack and screw it in place.

4

Connect up the spare power supply.

5

Switch on the system voltage and the power supply in any order.
Reaction:
– The system runs up.

4-48

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.3.5

Description of Internal Sequences in the Power Supply Unit
Given in this section is background information on internal sequences in the
power supply unit.

Behavior Upon
Failure of the
System Supply
When the System
Supply Fails

Redundant Data
Backup

The behavior of the power supply unit after a system supply failure is
governed by the duration of the failure:
IF the system supply failure...

THEN...

is shorter than the stored energy time
for power failure

the PSU output voltages are within tolerance
ranges; no indication appears on the front plate
and no signal is sent to the S5 bus.

is longer than the stored energy time
for power failure

a data save routine is initiated on the
CPU/CPUs and an output inhibit is issued.

To ensure data backup, your CC and EU 185 are provided with a lithium
battery, and the power supply unit with a rechargeable battery.
In the event of system supply failure or switch-off, data backup is provided
by the lithium battery and, in the event of battery failure, by the rechargeable
battery which is permanently recharged to remain constantly operative.
After replacement of a defective lithium battery, the new one resumes data
backup and you must acknowledge the fault LED on the front panel.
As the rechargeable battery is withdrawn during the replacement of a power
supply unit, data backup is temporarily performed by the lithium battery.

System Manual
C79000-G8576-C199-06

4-49

Central Controllers and Expansion Units Power Supply Units

Behavior Upon
Failure of Fans
Failure Indication

If a fan fails (its speed decreases) a fault is indicated, i.e. the red LED
assigned to the fan lights up:
“Fan 1” LED = left fan failed
“Fan 2” LED = middle fan failed
“Fan 3” LED = right fan failed

If a Fan Fails

If a fan fails, the following takes place:
Stage
1

If Another Fan
Fails

A fan fails.
Result:

!

4-50

– The red LED assigned to the fan lights up.

2

Contacts 9 and 10 in the “Warning” relay are closed.

3

The faulty fan is switched off.

4

The other two fans operate at increased voltage and an audibly higher
speed.

If another fan fails, the following takes place:
Stage

Resetting the Fault
Message

Description

Description

5

Another fan fails.
Result:
– The red LED assigned to the fan lights up.

6

Contacts 12 and 13 in the “Alarm” relay are closed.
Result:
– “Alarm” LED lights up.
– Two “Fan”-red LEDs light up.

7

A data save routine is started and, with the appropriate jumper setting, an
output inhibit is issued.

8

The power supply switches off, with the appropriate jumper setting.

When the fault has been cleared (faulty fan replaced, filter mat replaced),
you can reset the fault messages by pressing the Reset button.
Caution
You can suppress the shutdown of the power supply by opening jumper F-R.
In this case, you must ensure that the power supply is switched off after 60
secs at the latest. This can be achieved with a time relay, for example. This
prevents modules from overheating and being damaged.

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.3.6

Technical Specifications of the Power Supply Units
Important for the USA and Canada
The following approval has been obtained:
UL-Recognition-Mark (for USA)
Underwriters Laboratories (UL) to
Standard UL 508, Report E 143289
CUL-Recognition-Mark (for Canada) to
Canadian National Standard C 22.2, No. 142, Report E 143289
6ES5 955-3LC42

6ES5 955-3LF42

Safety Specifications

The power supply units comply with safety specifications VDE 0805 /
EN 60950 / IEC 950 / VDE 0160 and VDE 0106 Part 101.

Shock protection

only insured in the installed state

Data for EMC in the installed state

see technical specifications of the S5-135U/155U CC

Safe isolation

is ensured.

Input
Rated input voltage

120 V (93-132 V) AC
230 V (187-264 V) AC

120 V (93-132 V) AC
230 V (187-264 V) AC

Rated input frequency

50/60 Hz (47-63 Hz)

50/60 Hz (47-63 Hz)

Input current Ii/p
at rated loed and rated Vi/p = 120V
= 230V

2.5 Arms
1.5 Arms

4.5 Arms
2.6 Arms

Peak inrush current I i/p max

26 A for 2 s, otherwise < 5 A
(repetition rate 100 secs)

25 A for 2 ms
(repetition rate 100 secs)

I@t value of inrush current

4 A@s

5.2 A@s

Efficiency at rated load (with fans) and Vi/p
¢ 230/120 V AC

> 0.63

> 0.68

Max. heat dissipation at rated load at
Vo/p1, Vo/p2, Vo/p3 (with fans)

80 W

147 W

Efficiency at rated load (without fans) and
Vi/p ¢ 230/120 V AC

0.70

0.71

Max. heat dissipation (without fans)

53 W

123 W

Stored energy time during power failure at
rated load and
Vi/p ¢ 187/93 V AC (adjustable)

>20 ms
20 ms
5 ms

>20 ms
20 ms
5 ms

Input fuse

Wickmann G 19343-T4A/250V,
500 A@s

Wickmann G 19340-8A/250V,
200 A@s

External battery supply

4.5 V

4.5 V

System Manual
C79000-G8576-C199-06

4-51

Central Controllers and Expansion Units Power Supply Units

6ES5 955-3LC42

6ES5 955-3LF42

Output 1
Rated output voltage Vo/pN1

5.1 V DC $ 1.2%

5.1 V DC $ 1.2%

Rated output current Io/pN1

18 A

40 A

Basic load

0.5 A

1.6 A (typical)
3.1 A (worst case)

Ripple

v 1% of Vo/p1

v 1% of Vo/p1

Spikes

v 4% of Vo/p1

v 4% of Vo/p1

Static voltage tolerances
– at 95% load variation
– at 15% variation of Vi/p
– at temperature variation / 1K

v 0.005% of Vo/p1
v 0.0005% of Vo/p1
v 0.02% of Vo/p1

v 0.08% of Vo/p1
v 0.0005% of Vo/p1
v 0.02% of Vo/p1

Dynamic voltage tolerances
at load surge 50% to 100% Ii/oN
– overshoot
– settling time

v 3% of Vo/p1
v 5 ms

v 3% of Vo/p1
v 5 ms

Maximum permitted capacity

100 mF

750 mF

Voltage Monitor

Monitors voltage for
< 14 V and > 16 V

Monitors voltage for
< 14 V and > 16 V

Overvoltage shutdown Vo/p1

6V $ 5%

6V $ 5%

Undervoltage signal Vo/p1

4.75 V + 3%

4.75 V + 3%

Current limiting for overload

1.0 to 1.2 Io/pN1

1.0 to 1.2 Io/pN1

Test sockets for Io/p1

On front plate (3 V ¢ 18 A)
linearity range:
0.5 V/2.8 A to 3 V/18 A

On front plate (3 V ¢ 40 A)
linearity range:
0.5 V/6.6 A bis 3 V/40 A

Signaling section

Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250V/3A

Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250V/3A

Green LED: “5V o.k.” for Vo/p1

LED lights up if
4.75 V < Vo/p1

LED lights up if
4.75 V < Vo/p1

Rated output voltage Vo/pN2

DC 24 V (+ 25%, -12.5%)

DC 24 V (+ 25%, -12.5%)

Rated output current Io/pN2

1A

2.8 A

Total current X2 and front terminals

1 A max.

2.8 A max.

Ripple

v 1% of Vo/p2

v 1% of Vo/p2

Spikes

v 2% of Vo/p2

v 2% of Vo/p2

Current limiting for overload

1 to 1.3 Io/pN2

1 to 1.3 Io/pN2

Green LED “24V o.k.” for Vo/p2

LED lights up if
Vo/p2 > 19.9 V to 21.1 V

LED lights up if
Vo/p2 > 19.9 V to 21.1 V

Maximum permitted capacity

0.2 mF

0.8 mF

Protection and monitoring

Output 2

Protection and monitoring

4-52

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

6ES5 955-3LC42

6ES5 955-3LF42

Output 3
Rated output voltage Vo/pN3

15 V DC ($ 5%)

15 V DC ($ 5%)

Rated output current Io/pN3

0.5 A

2A

Ripple

v 1% of Vo/p3

v 1% of Vo/p3

Spikes

v 3% of Vo/p2

v 3% of Vo/p2

Overvoltage shutdown Vo/p3

17 V $ 5%

17 V $ 5%

Current limiting for overload

1 to 1.5 Io/pN3
During startup 4 IAN3 for 40 ms

1 to 1.5 Io/pN3

Green LED “15V o.k.” for Vo/p3

LED lights up if
14.2 to 14.7 V < UA3< 16.1 to
17.9 V

LED lights up if 14.2 to 14.7 V <
UA3< 16.1 to 17.9 V

Maximum permitted capacity

10 mF

10 mF

Protection and monitoring

Backup battery
Type
Capacity
No-load voltage
Voltage under load
Storage life
Service life in operation
(see Section 4.3.4 for backup times)

Lithium thionyl chloride
5 Ah
3.6 V
3.4 V
approx. 10 years
3 years max.

Rechargeable battery
Type
Capacity
Rated voltage
Service life in operation
(see Section 4.3.4 for backup times)
Protection against exhaustive discharge

Nickel cadmium
1.2 Ah
3.6 V
6 years at 40°C (104 °F)

Service life of fans

approx. 50.000 h at 40°C

approx. 50.000 h at 40°C

Weight

approx. 5.8 kg

approx. 5.8 kg

Noise emission

58 dBA

58 dBA

Environmental data

See technical specifications of the S5-135U/155U CC

System Manual
C79000-G8576-C199-06

yes

4-53

Central Controllers and Expansion Units Power Supply Units

6ES5 955-3NC42

6ES5 955-3NF42

Safety Specifications

The power supply units comply with safety specifications VDE 0805 /
EN 60950 / IEC 950 / VDE 0160 and VDE 0106 Part 101.

Shock protection

only ensured in the installed state.

Data for EMC in the installed state

See technical specifications of the S5-135U/155U CC

Safe electrical separation

is ensured. 1)

Input
Rated input voltage
(including ripple)

24 V DC (19.2 - 33 V)

24 V DC (19.2 - 33 V)

Input current Ii/p
at rated load and rated Vi/p = 24 V

9.5 A

20 A

Polarity reversal protection

yes

yes

Reak inrush current I i/pmax

100 A for 1 ms

200 A for 1 ms

I@t value of inrush current

2.7 A@s

18 A@s

Efficiency at rated load (with fans) and
Vi/p ¢ 24V

0.60

0.67

Max. heat dissipation at rated load
(with fans) at Vo/p1, Vo/p2, Vo/p3

90 W

153 W

Efficiency at rated load (without fans) and
Vi/p ¢ 230/120 V AC

0.65

0.70

Max. heat dissipation (without fans)

66 W

129 W

Stored energy time during power failure
at rated load and Vi/p ¢ 19.2 V DC
(adjustable)

>20 ms
20 ms
5 ms

>20 ms
20 ms
5 ms

Input fuse

Littlefuse 322020, 220 A@s

Littlefuse 322030, 620 A@s

Extenal battery supply

4.5 V

4.5 V

Rated output voltage Vo/pN1

5.1 V DC $ 1.2%

5.1 V DC $ 1.2%

Rated output current Io/pN

18 A

40 A

Basic load

0.5 A

1.6 A (typical)
3.1 A (worst case)

Ripple

v 1% of Vo/p1

v 1% of Vo/p1

Spikes

v 4% of Vo/p1

v 4% of Vo/p1

Static voltage tolerances
– at 95% load variation
– at 15% variation of Vi/p
– at temperature variation / 1K

v 0.08% of Vo/p1
v 0.0005% of Vo/p1
v 0.02% of Vo/p1

v 0.08% of Vo/p1
v 0.0005% of Vo/p1
v 0.02% of Vo/p1

Dynamic voltage tolerances
at load surge from 50% to 100% Io/pN
– overshoot
– settling time*

v 3% of Vo/p1
v 5 ms

v 3% of Vo/p1
v 5 ms

Output 1

1) These power supply units have a separation between the input circuit (24 VDC) and the secondary circuit which fulfills the
requirements for 230 VAC.

4-54

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

6ES5 955-3NC42

6ES5 955-3NF42

Protection and monitoring
Voltage Monitor

Monitors voltage for
<14 V and >16 V

Monitors voltage for
<14 V and >16 V

Overvoltage shutdown Vo/p1

6 V $ 5%

6 V $ 5%

Undervoltage signal Vo/p1

4.75 V + 3%

4.75 V + 3%

Current limiting for overload

1.0 to 1.2 Io/pN1

1.0 to 1.2 Io/pN1

Test sockets for Io/p1 on front plate

(3 V ¢ 18 A)
linearity range 0.5 V/2.8 A
to 3 V/18 A

(3 V ¢ 40 A)
linearity range 0.5 V/6.6 A
to 3 V/40 A

Signaling section

Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250 V/3 A

Signals for SIMATIC S5,
relays “Fan Warning, Fan Alarm,
Warning” 250 V/3 A

Green LED: “5V o.k.” for Vo/p1

LED lights up if
4.75 V < Vo/p1

LED lights up if
4.75 V < Vo/p1

Rated output voltage Vo/pN2

DC 24 V (+ 25%, -12.5%)

DC 24 V (+ 25%, -12.5%)

Rated output current Io/pN2

1A

2.8 A

Total current X2 and front terminals

1 A max.

2.8 A max.

Ripple

v 1% of Vo/p2

v 1% of Vo/p2

Spikes

v 2% of Vo/p2

v 2% of Vo/p2

Current limiting for overload

1 to 1.3 Io/pN2

1 to 1.3 Io/pN2

Green LED: “24V o.k.” for Vo/p2

LED lights up if
Vo/p2 > 19.9 V to 21.1 V

LED lights up if
Vo/p2 > 19.9 V to 21.1 V

Maximum permitted capacity

0.2 mF

0.8 mF

Rated output voltage Vo/pN3

DC 15 V ($ 5%)

DC 15 V ($ 5%)

Rated output current Io/pN3

0.5 A

2A

Ripple

v 1% of Vo/p3

v 1% of Vo/p3

Spikes

v 3% of Vo/p2

v 3% of Vo/p2

Maximum permitted capacity

100 mF

750 mF

Overvoltage shutdown Vo/p1

17 V $ 5%

17 V $ 5%

Current limiting for overload

1 to 1.5 IAN3
During startup 4 IAN3 for 40 ms

1 to 1.5 IAN3

Green LED: “15V o.k.” for Vo/p3

LED lights up if 14.2 to 14.7 V <
Vo/p3 < 16.1 to 17.9 V

LED lights up if 14.2 to 14.7 V <
Vo/p3 < 16.1 to 17.9 V

Maximum permitted capacity

10 mF

10 mF

Output 2

Protection and monitoring

Output 3

Protection and monitoring

System Manual
C79000-G8576-C199-06

4-55

Central Controllers and Expansion Units Power Supply Units

6ES5 955-3NC42

6ES5 955-3NF42

Backup battery
Type
Capacity
No-load voltage
Voltage under load
Storage life
Service life in operation
(see Section 4.3.4 for backup times)

Lithium thionyl chloride
5 Ah
3.6 V
3.4 V
approx. 10 years
3 years max.

Rechargeable battery
Type
Capacity
Rated voltage
Service life in operation
(see Section 4.3.4 for backup times)
Protection against exhaustive discharge

Nickel cadmium
1.2 Ah
3.6 V
6 years at 40 °C (104 °F)

Service life of fans

approx. 50.000 h at 40 °C

approx. 50.000 h at 40 °C

Weight

approx. 5.8 kg

approx. 5.8 kg

Noise emission

58 dBA

58 dBA

Environmental data

See technical specifications of the S5-135U/155U CC

4-56

yes

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.4

6ES5 955-3NA12 Power Supply Unit
Your 135U central controller (6ES5 135-3UA41) contains the following
power supply unit (PSU):
Type of PSU
Designation
6ES5 955-3NA12
(primary/secondary,
non-floating)

4.4.1

Input Voltage
24 V DC

Output Voltage
5 V/10 A DC
permissible range 0 to 10 A
24 V/0.8 A DC
permissible range 0 to 0.8 A

Technical Description
The power supply unit offers the following functions:

S System power supply
All system voltages needed to operate the CC are supplied. The 15 V
supply needed to operate the SINEC H1 system can be incorporated in the
power supply unit by fitting an auxiliary submodule.

S Data backup
A lithium battery ensures data backup when power is switched off or
fails.

S Heat dissipation
The power dissipation is removed by fans.

System Manual
C79000-G8576-C199-06

4-57

Central Controllers and Expansion Units Power Supply Units

LEDs and Controls

DC Line

The following indicators and controls are arranged on the front plate:

Monitor Output

24V DC
+
-

L+ M

Disconnect
before removing
power supply!

1
ID

Label

Element

2 3

4 5 6 78 9

10

Purpose

1

Fan Fault

Red LED

The LED lights up to indicate a fan fault. The PSU then switches off (jumper
F-R closed). If, for technical reasons, you cannot immediately switch off the
PLC, you must open jumper F-R. However, switch off the PLC after 60 s at
the latest (overheating of modules).

2

Batt. Low

Yellow
LED

The LED lights up if the battery voltage has dropped below 2.7 V; the data
stored in the RAM may be lost after “Power OFF/ON.”

3

Reset

Button

If the PLC is in the “Power OFF” state, the battery must be replaced after
“Power ON” when the “Batt. Low” LED is lit. You must press the Reset
button after changing the battery.

4

Power Supply
o.k.

Green
LED

The LED lights up when the 5 V output voltage is present.

5

Test 5 V

Test socket

To measure output voltage Vo/p1
(standard setting: 5.1 V DC $ 0.5%)

6

3 V = 10 A

Test socket

To measure output Io/p1
(3 V = max. output current of the PSU)
linearity range 0.5 V/1.6 A to 3 V/40 A

7

Power Supply
o.k. (Bus)

Green
LED

The LED lights up to indicate presence of the 15 V output voltage (if the 15
V auxiliary submodule is fitted) and 24 V output voltage

8

DC 15V/24V
(Bus)

Test
sockets

a) To measure output voltage Vo/p2
(24 V DC +25 %/-24 %)
b) To measure output voltage Vo/p3
(15 V DC $ 5 %, provided that 15 V aux. submodule is fitted)

9

Power Supply
o.k. (terminal)

LED

The green LED lights up to indicate presence of the output voltage at the “DC
24 V” terminal for the enable supply.

10

Batt. 3.4V/5Ah

Battery
drawer

The backup battery is arranged so that it can be replaced during operation and
the PSU can be replaced during battery backup without the backup voltage
being interrupted.

4-58

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Terminals

DC Line

Monitor Output

24V DC
+
-

Disconnect
before removing
power supply!

L+M

12 3

ID

Label

4

2 52

Element

62

7

Purpose

1

Protective conductor terminal for PSU module and housing.

2

Strain reliefs for connecting cables, with metal contact surface for cable
shields.

3

DC Line

Screw
terminals

System connection, 24 V input voltage

4

Monitor Output

Relay
output

Standstill of one or both fans is signaled via LED and relay contact, and
results in shutdown of output voltages (can be shut down via jumper F-R of
the PSU; then only relay signal and LED indication).

5

Enable Power
supply

Input/
output

No voltage at the EN input results in shutdown of the PSU. Not more than
7 EN inputs may be driven with one UH output (front terminal).

6

DC 24 V; 0.4 A

Output

This output can be used to power the enable inputs of the U Periphery.

7

Ext.Batt. 3.4 V

Sockets

Sockets for external 3.4 V backup voltage.

!

15 V Auxiliary
Submodule

System Manual
C79000-G8576-C199-06

Caution
Observe the appropriate VDE specifications, especially VDE 0100. The
terminals at the front are suitable for a conductor cross-section of up to
4 mm2, solid, or 2.5 mm2, flexible. Ensure adequate strain relief of the
connections.

You can add a 15 V auxiliary submodule to the 6ES5 955-3NA12 power
supply unit (for example, if you wish to use SINEC H1). The auxiliary
submodule produces a stabilized 15 V output voltage from the 24 V output
voltage. The auxiliary submodule is short-circuit protected. The output
voltage is monitored. If the voltage is too low, the green “15/24 V o.k.” LED
on the front plate goes off. If the voltage is too high, the output is
short-circuited by a thyristor.

4-59

Central Controllers and Expansion Units Power Supply Units

4.4.2

Setting the Power Supply Unit

Locations of
Jumpers

The figure shows the jumper settings when the unit is delivered.

Connector
X1

Connector
X2

F NN

R MM
RR
LL

Front Plate

Functions of the
Jumpers

The jumper settings in bold print indicate the status when the unit is
delivered.
Function

Jumpers

Battery monitor (BAU) On

NN-MM closed

Battery monitor (BAU) Off

NN-MM open

PSU shutdown after fan fault

F-R closed

No PSU shutdown after fan fault (only LED
indication, relay signal)

F-R open

Battery fault will be indicated by fault state of the
signaling relay (contacts 2-3 closed).

RR-LL closed

Battery undervoltage (< 2.7V)
results in
battery fault signal (jumper
MM-NN).
Apart from “Batt. Low” LED
and output
relay can be
PSU

of signal BAU, the signaling
activated as of Version 6 of the

RR-LL open

Battery fault will not be indicated by fault state of the
signaling relay

4-60

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Setting the Fan
Monitor

You can set jumper F-R on the power supply units to choose whether or not
the air flow monitor should switch off the internal supply voltage Vo/p (5 V)
when a fan fails.

S Jumper F-R closed: Vo/p shutdown (signaled by contact)
S Jumper F-R open: no Vo/p shutdown (signaled by contact)
If one or both fans are at standstill, the signaling relay drops out (monitor
output). The “Fan Fault” LED lights up simultaneously.

S Relay contacts 2-1 closed: fan running
S Relay contacts 2-3 closed: fan failure
Relay contacts 2-3 closed; this is also the normally closed contact during
power OFF (failsafe).

!

System Manual
C79000-G8576-C199-06

Caution
If an immediate shutdown is not possible, jumper F-R must be opened. In
this case you must ensure that the power supply is switched off after 60 s at
the latest. This can be achieved with a time relay, for example. It avoids
overheating and destruction of modules.

4-61

Central Controllers and Expansion Units Power Supply Units

Setting the Backup
Battery Monitor

As of Version 6 of PSU 6ES5 955-3NA12, you can set jumper RR-LL to
choose whether the signaling relay (monitor output) should switch in the
event of battery failure as well as fan failure:

S Jumper RR-LL open (state when delivered): relay will signal only a fan
failure

S Jumper RR-LL closed: relay will signal a fan and battery failure.
If the backup voltage fails or a fan is at standstill, or in both cases, the
signaling relay will drop out (monitor output). The “Batt. Low” LED will
also light up.

S Relay contacts 2-1 closed: battery backup voltage in order and fan
running

S Relay contacts 2-3 closed: backup voltage under 2.7 V or fan failure
Note
The signaling relay in the power supply unit will drop out in the event of a
fan fault or backup battery fault. The user’s circuitry for the signaling relay
must therefore be suitable for both types of fault.
If the signaling relay drops out because of a backup battery fault and the
programmable controller is therefore switched off, the program in the main
memory may be lost. Loss of program can be avoided if an external backup
voltage (3.4 V) is present at the sockets on the front plate of the power
supply unit during shutdown of the programmable controller.

4-62

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

4.4.3

Installation
To install the power supply unit, push it into the rack. Press it in firmly until
the front plate is at the rack. The spring pressure of the contact elements must
be overcome. Then tighten the two screws to the left and right of the front
plate in the rack. The protective conductor jumper on the left must be
permanently connected to the front plate terminal and the central rack.

!

Caution
Power supply units may only be removed when no power is applied.

When the power supply unit is pulled out, the connection between backup
battery and backplane bus is retained; the backup supply for the modules is
thus ensured.

Installing the 15 V
Auxiliary
Submodule

The auxiliary submodule (see ordering information for order number) may
only be inserted when the power is off.
Remove the power supply unit, fit the 15 V auxiliary submodule at the
location shown in the following figure.

Connector
X1

Connector
X2
Transformer

AA
BB
Space for
LL
RR
Auxiliary
Submodule
Front Plate

System Manual
C79000-G8576-C199-06

4-63

Central Controllers and Expansion Units Power Supply Units

4.4.4

Operation
Before placing the power supply unit in operation, please comply with the
following.

General Notes on
the Power Supply
Unit

S This power supply unit does not have potential isolation between its
primary and secondary circuits.

S No voltage of more than 50 V may develop between the power supply
outputs and the protective conductor of the power supply unit.

S The protective conductor must always be connected, as must the jumper
between CC rack and front plate of the power supply unit.

S In the event of overvoltage of the internal DC supply voltages
Vo/p1 = +5 V and Vo/p3 = +15 V, the power supply unit is switched off
retentively. There is a voltage of v0.5 V at Vo/p1 and Vo/p3 in the Off
state (see Section 4.4.6, Technical Specifications, for overvoltage
shutdown).
The storage flip-flop is reset by switching the external supply voltage off
and on again, and the power supply unit is again operational if the
overvoltage was not the result of an internal fault.

S You can insert an air filter with filter holder in the bottom of the housing
of the power supply unit.

S Observe the voltage level of 3.4 V and correct polarity when applying an
external backup voltage.

S Before startup, a lithium backup battery must be fitted or an external
backup battery with a voltage level of 3.4 V DC must be connected.
Without a backup battery, the programmable controller will remain in the
Stop state when system voltage has been switched on. The backup battery
must be fitted for startup. Press the RESET button, then perform an
OVERALL RESET.

S The jumper from terminals UH to EN will enable the power supply. You
can lock out the PLC in the event of a fault by means of suitable circuitry
between the monitoring outputs and the EN inputs.

4-64

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Fault Indications/
Diagnostics

Power supply faults are indicated via relay contacts and LEDs.
The following table shows when the relay contacts are open or closed:
Power Supply

Relay Contacts 1-2

Relay Contacts 2-3

Switched off

Open

Closed

In normal operation

Closed

Open

During fault

Open

Closed

The LEDs indicate the following faults:
LED

System Manual
C79000-G8576-C199-06

Cause

Action

“Fan Fault” LED
lights up.

A fan fault has occurred.

Replace fan

“Batt. low” LED
lights up.

The battery voltage has dropped below
2.7 V.

Replace backup
battery

4-65

Central Controllers and Expansion Units Power Supply Units

4.4.5

Maintenance

Replacing the
Lithium Battery

!

Caution
Incorrect replacement of the battery can result in the danger of explosion.
It should only be replaced by the same type or an equivalent type
recommended by the manufacturer. Used batteries should be disposed of
according to the manufacturer’s instructions.

You can replace the backup battery without loss of data if the power supply
unit is switched on, or if you apply an external voltage (3.4 V) at the “Ext.
Batt.” sockets. The backup battery must be replaced every 3 years at the
latest, irrespective of memory configuration and backup operation. Replace
the battery as follows:
Step

Action

1

Pull the cover downwards.

2

Pull the battery submodule forwards and out, and remove it.

3

Replace the battery.

4

Ensure correct polarity.

5

Once the new battery is fitted and system voltage is On, press the Reset
button on the power supply unit.

Battery
Submodule
+
Sockets for External
Backup Voltage

*

Battery Submodule

Cover

Only use battery submodules with the order number 6XG3 400-2CK00.

4-66

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

!

!

Caution
Ensure correct polarity when inserting the battery or applying backup
voltage.

Warning
Risk of danger to persons and property, danger of giving off harmful
substances.
If handled incorrectly, a lithium battery can explode. If disposed of
incorrectly, old lithium batteries can release harmful substances. You must
therefore observe the following guidelines:
S Do not throw new or discharged batteries onto a fire and do not solder
onto the body of the cell (max. temperature 100 °C (212 °F)). Do not
recharge them. Order your replacement battery from Siemens only (for
order number see ordering instructions). This ensures that you only use a
short-circuit-protected type.

S The lithium battery is subject to regulations for hazardous materials. You
should observe these regulations when you shipthe battery, for example,
by using the original packaging. Used batteries should be returned to the
manufacturer or a recycling station if possible or disposed of as
hazardous waste. The guidelines for transporting hazardous materials
should be observed.

Replacing the
Fans

The expected service life of the fans (see Technical Specifications) depends
on their operating time, ambient temperature and ambient conditions. In the
event of fan failure during operation, subsequent damage to modules, for
example, is avoided by the activated fan monitor (jumper F-R closed); the
power supply unit is switched off.
In individual cases, a preventive replacement of fans at suitable intervals may
be advisable. Proceed as follows to replace the fans:
Step

Action

1

Disconnect power from the power supply.

2

Remove the power supply.

3

Slacken the fixing screws of the fans.

4

Pull off the plug-in contacts of the fan supply.

5

Connect the plug-in contacts of the new fans.

6

Tighten the fixing screws of the fans.

7

Refit the power supply.

8

Switch the power supply on.

The order numbers for the backup battery and fan unit can be found in the
ordering information.

System Manual
C79000-G8576-C199-06

4-67

Central Controllers and Expansion Units Power Supply Units

4.4.6

Technical Specifications
Important for the USA and Canada
The following approvals habe been obtained:
S UL-Recognition-Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E 116536
S CSA-Certification-Mark
Canadian Standard Association (CSA) to
Standard C 22.2 No. 142, Report LR 63534

Safety Specifications

The power supply unit complies with safety specifications
VDE 0805 / EN 60950 / IEC 950 / VDE 0160 and VDE
0106 Part 101.

Input
Rated input voltageVi/pN

DC 24 V +25% / -16.66%

Undervoltage signal Vi/p

v 20 V DC

Input current Ii/pN
at rated load and Vi/pN = 24 V DC

4.8 A

Inrush current peak Ii/pmax

100 A

I@t value of inrush current

20 A@s

Efficiency at rated load and Vi/pN = 20 V
without fan
with fan

0.71 typical
0.60 typical

Stored energy time for power failure

> 5 ms

Input fuse

6 A fast; 250 V; 6.3 x 32 mm

Output 1
Rated output voltage Vo/pN1

5.1 V DC $ 0.5%

Rated output current Io/pN1

10 A

Ripple

v 1% of Vo/p1

Static voltage tolerances
at 10% load variation
at 5% variation of UE
at temperature variation /1 K

v 0.02% of Vo/p1
v 0.04% of Vo/p1
v 0.02% of Vo/p1

Dynamic voltage tolerances
at load surge from 50 % to 100 %
overshoot
settling time
Protection and monitoring
Overvoltage shutdown Vo/p1
Undervoltage signal Vo/p1
Current limiting for overload
Test sockets for
Vo/p1

v 5% of Vo/p1
v 5 ms
6 V $ 5%
4.75 V + 5%
1.05 to 1.15 Io/pN1
On front plate
On front plate (3 V ¢ 10 A)
Linearity range 0.5 V/1.6 A to 3 V/10 A

Io/p1
Signaling section

4-68

Signals for SIMATIC S5

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Output 2 (bus)
Rated output voltage Vo/p2

24 V DC +25% / -20%

Rated output current Io/p2

0.8 A

Total current rating
24V-/ 15V output

v 0.8 A

Ripple

Input voltage ripple

Protection and monitoring
Fuse for overcurrent protection
Test sockets for Vo/p2
– green LED 15V/24V o.k. for Vo/p2 (fuse monitor)

1.5 A fast; 250 V; 6.3 x 32 mm
on front plate (24 V test)
The LED lights up when Vo/p2 > 17.9 to 18.5 V

Output 2 (front)
Rated output voltage Vo/pN4

24 V DC +25% / -24%

Rated output current Io/pN4

0.4 A

– Capacitive load

< 100 nF

Protection and monitoring
Overcurrent protection by current limiting Io/p4
Test sockets for Vo/p2
– green LED 24V o.k. for Vo/p4

> 0.44 A
on front plate (24 V test)
The LED lights up when Vo/p4 > 16 V $ 20%

Total current rating of 24 V voltages (bus and front)

must not exceed 0.8 A

Output 3 with 15 V auxiliary submodule
Rated output voltage Vo/pN3

15 V DC $ 5%

Rated output current Io/pN3

0.5 A

Ripple

v 5% of Vo/pN3

Protection and monitoring
Overvoltage protection (output is short-circuited
at Vo/p3)
Undervoltage signal (LED 15V/24V o.k.
on front plate goes off at)
Overcurrent protection Io/p3 by current limiting
Test socket for Vo/p3

w 18.5 V
v 14 V $ 3%
> 0.5 to 1.5 A
on front plate (15 V test)

Fans
Fan type

2 axial fans

Input voltage

24 V DC

Flow rate per fan

160 m3/h (no-load value)

Fan monitoring

Air flow monitoring with PTC thermistors as sensors;
stoppage of one or both fans is detected and signaled to the
exterior via Fan Fault LED and relay contacts, and results
in shutdown of output voltage (switched off via jumper
F-R).

Expected service life of a fan

30 000 to 40 000 h typical at 55 oC;
40 000 to 50 000 h typical at 30 oC;

Isolation primary/sekondary
and test voltages

No

Weight

3.75 kg

Environmental data

See technical specifications of the S5-135U/155U CC

RFI suppression

DIN VDE 0871, A

System Manual
C79000-G8576-C199-06

4-69

Central Controllers and Expansion Units Power Supply Units

4.5

Fan Submodules

4.5.1

Technical Description
The fan submodule variants 6ES5 988-3LA11 (230 V AC) and
6ES5 988-3NA11 (24 V DC) are described in the following section.
A fan submodule has the following function:

S Heat dissipation
The fan submodule dissipates any excess heat created in the central
controller or expansion unit.

Connections and
LEDs

The following terminals and LEDs are fitted on the front plate (the front
plate of the -3LA11 is shown as an example):

SIEMENS
Monitor Output

5 6
4
3

L1 N

CAUTION!
Disconnect
before
removing
power supply!
Voltage selector
inside the unit!

Fan
Fault

1 23

1 2

6ES5 988-3LA11

Relay max.
250V AC/3A

AC 230V

7 8

9 10

AC line

Use copper wire 60/75° C only!
Tightening torque: terminals 0,8Nm/

ID

Label

Element

1,8 Nm

Purpose

1

Protective conductor terminal for fan submodule and housing.

2

ZStrain reliefs for connecting cables, with metal contact surface for cable
shields.

3

230V AC

24V DC

Screw
terminals
L1, N

AC connection

Screw
terminals + –

24 V DC supply

(details for -3LA11)

(details for -3NA11)
4

Monitor Output Relay output

Standstill of one or both fans is signaled via LED and relay contact.

5

Fan Fault

The LED lights up to indicate a fan fault.

4-70

Red LED

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

!

Observe the appropriate VDE specifications, especially VDE 0100. The
terminals at the front are suitable for a conductor cross-section of 4 mm2
solid or 2.5 mm2 flexible. Ensure adequate strain relief for the connections.

DThe figure shows the setting of the voltage selector switch when delivered
(230 V).

230V

Position of the
Voltage Selector
Switch and the
Fuse

Caution

S13

F12

Front plate
1

System Manual
C79000-G8576-C199-06

2

ID

Element

Purpose

1

Fuse F12

Protecting the fan submodule against overload

2

Voltage selector switch
S13 (-3LA11 only)

Setting the fan submodule -3LA11 for the
available line voltage: (115 V or 120 V or 230 V)

4-71

Central Controllers and Expansion Units Power Supply Units

4.5.2

Setting and Connecting the Fan Submodule
Before starting up your fan submodule, you must perform certain steps
according to your requirements with respect to fan submodule behavior in the
event of a fault.
The fan submodule is delivered in the following state:

S Fitted in the CC or EU frame you ordered
S AC line voltage set to 230 V
If you wish to retain this setting, you can skip Steps 2 to 5.
Step

Action

1

Check the setting and cabling

2

Remove the fan submodule

If required

3

Fit the fan submodule

If required

4

Wire the fan submodule to the installation (including fitting
an isolating device to disconnect the AC line voltage)

5

On the -3LA11 set the voltage selector switch (factory
setting 230 V)

6

Switch on the fan submodule for the first time

If required

Establishing the
Wiring

Wiring of the fan submodule must be planned within the scope of wiring the
entire control system. The information required for the purpose and
decision-making aids (for example, for local or central grounding) can be
found in Chapter 3, Installation Guidelines.

Establishing the
Signaling Circuits

Two relay outputs allow you to install additional external signaling circuits
for fault states, for example, to connect a cabinet lamp or horn.

4-72

System Manual
C79000-G8576-C199-06

Central Controllers and Expansion Units Power Supply Units

Selecting Cables

The following applies to selecting the cables for the terminals:

Terminals

Power supply AC line

Cabling

Max. Permissible Cable
Cross-Sections

Phase

L1

4 mm2 solid or 2.5 mm2
flexible

Neutral

N

4 mm2 solid or 2.5 mm2
flexible

Protective conductor

4 mm2 solid or 2.5 mm2
flexible
4 mm2 solid or 2.5 mm2
flexible

Relay terminals, also suitable
to 230 V AC / 3 A

Installing and
Removing the Fan
Submodule

For installing and removing the fan submodule, refer to the instructions in
Section 4.3.2 on the power supply unit. These also apply in principle here.

Wiring up the Fan
Submodule

FFor wiring up the fan submodule, refer to the instructions in Section 4.3.2
on the power supply unit. These also apply in principle here.

Switching on the
Fan Submodule
for the First Time

The fan submodule is switched on when the line voltage for the central
controller or expansion unit is switched on.

!

Fault Indications/
Fault Diagnostics

Caution
If you have set the voltage selector switch on the -3LA11 to 120 V, but the
actual voltage value is 230 V, the fan submodule may be damaged when line
voltage is switched on.

Fan submodule faults are indicated via relay contacts (“Monitor Output”) and
an LED.
The following table shows when the relay contacts are open or closed:
Fan Submodule

Relay Contact 1-2

Relay contact 2-3

Switched off

open

closed

In normal operation

closed

open

During fault

open

closed

In the case of a fault, the red LED “Fan Fault” lights up.

System Manual
C79000-G8576-C199-06

4-73

Central Controllers and Expansion Units Power Supply Units

4.5.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:

S UL-Recognition-Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E 116536

S CSA-Certification-Mark
Canadian Standard Association (CSA) to
Standard C 22.2 No. 142, Report LR 63534
6ES5 988-3LA11

6ES5 988-3NA11

Safety Specifications

The power supply units comply with safety specifications
VDE 0805 / EN 60950 / IEC 950 / VDE 0160 and VDE
0106 Part 101.

Shock protection

Only ensured in the installed state.

Data for EMC in the installed state

See technical specifications of the S5-135U/155U CC

Safe isolation

Is ensured.

Input
Rated input voltage

110 V AC (93.5-121 V),
220 V AC (187-242 V)

24 V DC (20 - 30 V)

Input frequency

50/60 Hz (48-63 Hz)

–

Input current Ii/pN

approx. 0.48 A
(and Vi/pN = 120 V)
approx. 0.24 A
(and Vi/pN = 230 V)

approx. 1 A

Peak inrush current Ii/pmax

<5A

< 10 A

Max. heat dissipation at rated load (with fans)

approx. 52 W

approx. 24 W

Max. heat dissipation at rated load (without fans)

approx. 12 W

approx. 9 W

Stored energy time during power failure

> 20 ms

Input fuse

1.5 A fast; 250 V; 2.4 A2s

Service life

approx. 42.000 h at 40 oC

Weight

approx. 4 kg

Environmental data

See technical specifications of the S5-135U/155U CC

4-74

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory
Submodules, Interface Submodules

5

This chapter contains information on the CPUs, memory cards, modules and
submodules which you can use in your programmable controller.
The following CPUs may be fitted in an S5-135U/155U central controller:
CPU 948
CPU 928B
CPU 928
CPU 922.
A programmable controller containing a CPU 948 is known as an S5-155U
PLC. A programmable controller containing CPUs 928B, 928 and/or 922
(and not the CPU 948) is known as an S5-135U PLC.
You can fit a flash EPROM memory card containing your user program in the
CPU 948, 928B -3UA21 and 928 -3UA21. For the CPUs 928B, 928 and 922,
there are RAM or EPROM submodules for the purpose.
CPUs 948 and 928B have, apart from the programmer interface, a second
serial interface. An interface submodule is required for physical adaptation.

Chapter
Contents

System Manual
C79000-G8576-C199-06

Section

Description

Page

5.1

CPU 948B -3UA13 or CPU 948B -3UA23

5-2

5.2

CPU 948

5-17

5.3

CPU 928B -3UB21

5-30

5.4

CPU 928B

5-42

5.5

CPU 928 -3UA21

5-54

5.6

CPU 928

5-62

5.7

CPU 922

5-71

5.8

374 Flash EPROM Cards

5-80

5.9

376 Memory Submodules

5-82

5.10

377 Memory Submodules

5-84

5.11

Interface Submodules

5-92

5-1

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.1

CPU 948B -3UA13 or CPU 948B -3UA23
This section contains the hardware description and technical specifications of
the CPU 948B -3UA13 or the CPU 948B -3UA23.
Details on programming the CPU 948 can be found in the CPU 948
Programming Guide.

5.1.1

Technical Description
This section contains information on the application, design and structure of
the CPU 948.

Application

You can use the CPU 948 in single and multiprocessor operation in the
S5-135U/155U central controller (see Chapter 6).
There are two versions of CPU 948:
The CPU 948-1 offers 640 Kbytes of internal user memory (RAM).
The CPU 948-2 offers 1664 Kbytes of internal user memory (RAM).

As an external memory medium, you can use a memory card 374.

The following program processing levels are possible:
Cyclic
Time-controlled (9 different timebases, real-time controlled, timeout)
Interrupt-driven from the S5 bus (8 process interrupts at block boundaries
via IB0 or, alternatively, 4 system interrupts)
Soft STOP.

Design

5-2

The electronic circuitry of the CPU 948B is on one PCB in the double
Eurocard format. The front plate width is 1 1/3 standard plug-in stations, i.e.
20 mm. In the central controller rack, the CPU 948B -3UA13 or the
CPU 948B -3UA23 occupies one slot.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.1.2

Installation and Startup

Jumper Settings

There are four system interrupts for interrupt-driven program processing with
the CPU 948:
INTA/B/C/D (depending on the CPU slot, see also Section 4.1.1)
INTE
INTF
INTG.
The interrupts you wish to use must be enabled by inserting the jumper plugs
provided. The jumper socket is situated on the basic board above the
receptacle for the memory card. The exact location is given in Figure 5-1:

Figure 5-1

Location of Jumper Socket

If you want to operate an IM308C in the IM3/IM4 area and additional digital
or analog modules in the central controller, you must insert the jumper shown
in Figure 5-1.

System Manual
C79000-G8576-C199-06

5-3

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Note
All other jumpers on the CPU 948B -3UA13 or the CPU 948B -3UA23 are
required for quality testing by the manufacturer. You must not change these
jumper settings.

Removing and
Inserting the
Module

!
Insertion

Caution
Switch off the power supply before removing or inserting the module.

Proceed as follows to insert the CPU in the central controller:
Step

Action

1

Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U CC from slot 11.

3

Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.

4

Press the locking pin inwards on the bottom of the module and
rotate it 90 clockwise.

5

Secure the upper locking bar.

Note
If you install the CPU 948 -3UA13 or the CPU 948 -3UA23 as the
replacement for a double-width CPU 948, you must cover the slot which has
been freed up with a blanking plate.

5-4

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Removal

Proceed as follows to remove the CPU:
Step

Action

1

Release the upper locking bar of the central controller.

2

Release the locking pin of the module.

3

Press the release lever downwards and pull the module forwards
and out of the central controller.

Note
Only operate the CPU 948 -3UA13 or the CPU 948 -3UA23 with the
submodule receptacle closed. You close it either by fitting an interface
submodule or with the cover supplied.

System Manual
C79000-G8576-C199-06

5-5

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Controls and
Indicators

The controls and indicators are arranged on the front plate of the CPU
module:

CPU 948U

Fault Indicator LED (red)

QVZ

ADF

Receptacle for
User Memory Submodule

ZYK

BASP

SI1 Interface Fault Indicator LED (red)
SI1

SI2 Interface Fault Indicator LED (red)
SI2
RUN

RUN LED (green)
Mode Switch

STOP
S–F

STOP LED (red)
SYS FAULT LED (red)

RESET

Momentary-Contact Mode Switch
OVRESET

PG Interface, 15-Pin
Interface SI1

SIEMENS

6ES5948-3UA13

Order Number and Version

Release Lever
Locking Pin

Figure 5-2

5-6

Front Plate of the CPU 948-3UA13 or the CPU 948-3UA23

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Mode Switch

The mode switch has two settings:

RUN

In the RUN setting, the CPU 948 processes the user program when the green
RUN LED is lit.

STOP

The CPU 948 goes to the stop state when you switch from RUN to STOP.
The red STOP LED then lights up.

MomentaryContact Mode
Switch

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch:

OVERALL RESET

Momentary-contact switch down
With an overall reset, all RAM areas are erased and initialized (both on the
CPU and on a RAM submodule).

RESET

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Restart

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters, and the process image
are retained during stoppage of the CPU.

System Manual
C79000-G8576-C199-06

5-7

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Status Indicators

Given in the following overview are the functions of the RUN, STOP and
SYS FAULT status LEDs.
The STOP LED indicates a soft stop; the SYS FAULT LED indicates a hard
STOP.
The CPU 948 can process a user program (OB 39) cyclically at the soft
STOP, but the digital outputs remain inhibited. At the hard STOP, no program
can run and the CPU has “stopped.” This state can only be exited by
switching the system voltage off and on again.

5-8

RUN
LED

STOP
LED

SYS
Status
FAULT
LED

on

off

off

The CPU is in the RUN state (cyclic
operation).

on

on

on

Appears briefly after power-up of the unit.

off

off

off

CPU is in the initial start or program check
state.

off

on

off

CPU is in the soft STOP state.

off

rapid
flashing

off

CPU is in the soft STOP state.
Overall reset has been requested by switch or
from the operating system.

off

slow
flashing

off

CPU is in the soft STOP state. An error has
occurred; see the CPU 948 Programming
Guide for possible causes.

off

off

on

CPU is in the hard STOP state. No program
processing is taking place. You can only exit
from this state by switching the system
voltage off and on again.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

LEDs for Fault
Indication and
Signaling

Given in the following overview are the causes for LEDs lighting up:
QVZ LED
on

A module addressed by the program no longer acknowledges
although/because
it either acknowledged in single-processor operation upon
restart of the CPU 948 in the area of the process image
(IB0 to 127, QB0 to 127) and has been entered as present
in the so-called 9th track;
or it has been entered in multi or single-processor
operation in DB 1 (address list) and has been recognized
as present during the restart;
or it was addressed in direct access by operations LPY,
LPW, TPY, TPW, LOY, LOW, TOY, TOW;
or the data handling blocks cannot access the module.
Possible causes:
Module failure
Module removed during operation, in the STOP state or in
the Off state without subsequent restart.
A timeout occurred during access to the user memory.

ADF LED
on

The user program has referred to an address in the process
image under which no module was inserted in the I/Os or was
not entered in DB 1 during the last restart.

ZYK LED
on

The preset cycle time monitor has responded and cyclic
program processing is interrupted.

BASP LED
on

Command output is inhibited and the digital outputs will be
directly switched to the safe state (0).

A detailed description of interrupt and error handling can be found in the
CPU 948 Programming Guide.

System Manual
C79000-G8576-C199-06

5-9

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Fault LEDs SI1
and SI2

LEDs SI1 and SI2 indicate faults in communication via interfaces SI1
and SI2:

LED SI1

LED SI2 Cause

on

on

Communication is not possible at both interfaces.
Internal fault.

on

off

SI1:
No communication possible.
Internal fault.
SI2:
Interface is initialized and ready.
LED SI2 is always off if no interface module is
inserted.

off

on

SI1:
Interface is initialized and ready.
SI2:
No communication possible. Wrong module
inserted or internal fault.

off

off

Both interfaces are initialized and ready.
LED SI2 is always off if no interface module is
inserted.

5-10

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The module must be inserted at the correct slot in the central controller. The
backup battery must be fitted and in order for the CPU to start.

Overall Reset

Proceed as follows:
Step

1)
2)

Action

Result

1

Set the mode switch to STOP

2

Switch the system voltage on. The following LEDs must light
up on the CPU:
– Red STOP LED
(flashing rapidly)
– Red BASP 2) LED

3

Hold the MC 1) switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.

The red STOP LED is now
permanently lit.

MC: Momentary-contact
BASP: Command output inhibit

If the red SYS FAULT LED also lights up, an error has occurred during
overall reset. In this case the measures described must be repeated. If
necessary, switch the system voltage off and on again. If the LED is still lit,
the module is faulty.

Reset

Continue as follows:
Step

Action

1

Set the mode switch to STOP.

2

Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.

Result

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

The CPU is now in the RUN state
but still has no user program.

System Manual
C79000-G8576-C199-06

5-11

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Restart

You can also carry out a manual restart of the CPU 948 with the mode
switch. The CPU 948 Programming Guide will indicate when a manual
restart is permissible.
Step
1

Action

Result

Set the mode switch from
STOP to RUN

– Red STOP LED goes off
– RUN LED lights up
– Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.

5-12

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.1.3

Interfaces of the CPU 948
This section contains information on the interfaces of the CPU 948.

PG interface SI1

You can use the PG interface on the CPU 948 either via the front connector
or via the 923C coordinator module and the S5 bus.
Note
Simultaneous operation of the PG interface via the front connector of the
CPU 948 and via the 923C coordinator is not possible. Switching the PG
online without a job request is already sufficient to operate the interface.
Electrically, it is merely a PG interface which can be operated via two
different terminals.
The connection to the PG can be established in every operational state of the
CPU.

Second Interface
SI2

You can optionally use the second interface of the CPU 948 -3UA13 or the
CPU 948 -3UA23 as:
A PG interface (for PG and operator panels)
Interface for the RK 512 computer link
Interface for data transmission with procedures 3964/3964R
Interface for data transmission with the “open driver”
Interface for data transmission via the SINEC L1 bus.
To utilize the second interface as the PG interface, you need the
PG submodule.
You need one of the following interface submodules for the RK 512
computer link, for data transmission with procedures 3964/3964R and for
data transmission with the “open driver”:
V.24 submodule (RS 232C)
TTY submodule
RS422 A/485 submodule (only in the RS422 A module).
To utilize the second interface for data transmission via the SINEC L1 bus,
you need the
SINEC L1 submodule.
The CPU 948 -3UA13 or the CPU 948 -3UA23 is delivered without an
interface submodule. You can operate the CPU 948 -3UA13 or the CPU 948
-3UA23 without an integral interface submodule. The opening to accept a
submodule in the front plate is closed by a cover. Only remove the cover to
fit an interface submodule.
A description of interface submodules can be found in Section 5.11, and the
order numbers in the ordering information.
A detailed description of the second interface can be found in the
CPU 928B/CPU 948 Communication Manual.

System Manual
C79000-G8576-C199-06

5-13

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Communication
via Backplane Bus
with SINEC H1

A PG-PLC link via SINEC H1 allows very advanced communication
between the partners. For example, the user software can be loaded into the
CPU 948 up to eight-times faster than with serial communication.
For this link you will need, in addition to the CPU 948, a CPU 143 (Version
w 2.1) in the PLC and a PG7xx with SINEC H1 connection and the STEP 5
single-tasking software from Version 6.0 or multi-tasking from Version 2.0.
Note
You cannot implement communication via SINEC H1 in parallel with the
serial interfaces.

Communication via SINEC H1 is described in detail in the CPU 948
Programming Guide.

5-14

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.1.4

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:

S UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972

S CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection

IP 00

Climatic ambient conditions

See Technical Specifications of the S5-135U/155U CC

Mechanical ambient conditions

See Technical Specifications of the S5-135U/155U CC

Noise immunity, electromagnetic
compatibility (EMC)

See Technical Specifications of the S5-135U/155U CC

Supply voltage

5V$5%
24 V + 25 %/ –17 %

Current consumption at 5 V

1.5 A typical

Backup voltage

3.4 V

Backup current

20 mA typical (at 25 _C)
P area

O area

IM3 area

IM4 area

Total

Digital inputs with process image
Digital inputs without process image
or analog inputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Digital outputs with process image
Digital outputs without process image
or analog outputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Flags

2048

S flags

32768

Timers

256

Counters

256

Size of user memory

64 x 2!) bytes max., RAM

Transmission rate of the serial PG interface

9600 bps

Program blocks PB

256

Sequence blocks SB

256

Function blocks FB

256

Function blocks FX

256

System Manual
C79000-G8576-C199-06

5-15

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Data blocks DB

256, of which 253 are freely available

Data blocks DX

256, of which 253 are freely available

Organization blocks OB

OB 1 to 39 (interfaces for operating system)

Integrated special function organization
blocks OB

OB 121, 122, 124-126, 131-133, 141-143, 150, 151, 153, 200,
202-205, 222, 223, 254, 255

Integrated serial interface

PG interface

Optional serial interface

Via interface submodules, optionally as V.24, TTY, RS422 A/485
submodule, SINEC L1 or PG interface

Backplane bus

S5 bus

Dimensions (w x h x d)

20.32 x 233.4 x 160 mm

Weight

Approx. 0.6 kg

5-16

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.2

CPU 948
This section contains the hardware description and the technical
specifications of the CPU 948.
Details on programming the CPU 948 can be found in the CPU 948
Programming Guide.

5.2.1

Technical Description
This section contains information on the application, design and structure of
the CPU 948.

Application

You can use the CPU 948 in single and multiprocessor operation in the
S5-135U/155U central controller (see Chapter 6).
There are two versions of CPU 948:
The CPU 948-1 offers 640 Kbytes of internal user memory (RAM).
The CPU 948-2 offers 1664 Kbytes of internal user memory (RAM).
A SIMATIC S5 flash EPROM memory card (known as a memory card for
short in the following) can be inserted in the CPU 948 as the storage medium
for user program and user data. The contents of the memory card are copied
into the internal RAM of the CPU upon overall reset.
The programming language is STEP 5 (LAD, CSF, STL, SCL). The CPU 948
processes all STEP 5 operations at very high speed, and uses fast
floating-point arithmetic.
The following program processing levels are possible:
Cyclic
Time-controlled (9 different timebases, real-time controlled, timeout)
Interrupt-driven from the S5 bus (8 process interrupts at block boundaries
via IB0 or, alternatively, 4 system interrupts)
Soft STOP.

Design

System Manual
C79000-G8576-C199-06

The electronic circuitry of the CPU 948, including the RAM, is on two PCBs
of double Eurocard format which are screwed to each other. The two PCBs
must not be separated. The front plate width of the module is 2 2/3 standard
plug-in stations, i.e. 40 mm. In the central controller rack, the CPU 948
occupies two slots.

5-17

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.2.2

Installation and Startup
This section explains the installation and removal of the module in the CC,
controls and indicators on the front plate of the CPU, and the procedure for
module startup.

Jumper Settings

There are four system interrupts for interrupt-driven program processing with
the CPU 948:
INTA/B/C/D (depending on the CPU slot, see also Section 4.1.1)
INTE
INTF
INTG.
The interrupts you wish to use must be enabled by inserting the jumper plugs
provided. The jumper socket is situated on the basic board above the
receptacle for the memory card. The exact location is given in Figure 5-3:

INTG
INTF
INTE
INTA/B/C/D

View of underside of module

Front panel

Jumper

Figure 5-3

Location of Jumper Socket

Location of an Additional Jumper for the
Functions Described Below

If you want to operate an IM308C in the IM3/IM4 area and additional digital
or analog modules in the central controller, you must insert the jumper shown
in Figure 5-3.

5-18

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Note
All other jumpers are required for quality testing by the manufacturer. You
must not change these jumper settings.

Removing and
Inserting the
Module

!

Caution
Switch off the power supply before removing or inserting the module.
The basic board and expansion board of the CPU 948 are one unit and must
not be separated.

Insertion

Proceed as follows to insert the CPU in the central controller:

Step

Removal

1

Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U PLC from the extreme left
at slot 11.

3

Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.

4

Press the locking pin inwards on the bottom of the module and
rotate it 90 clockwise.

5

Secure the upper locking bar.

Proceed as follows to remove the CPU:
Step

System Manual
C79000-G8576-C199-06

Action

Action

1

Release the upper locking bar of the central controller.

2

Release the locking pin of the module.

3

Press the release lever downwards and pull the module forwards
and out of the central controller.

5-19

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Controls and
Indicators

The controls and indicators are arranged on the front plate of the CPU
module:

S5-155U

CPU948

Receptacle for
Memory Card

RUN

Mode Switch

STOP
RUN

LED (green)

STOP

LED (red)

SYS FAULT

LED (red)

RÜCKSETZEN
RESET

Momentary-Contact Mode Switch
URLÖSCHEN
OVERALL
RESET
QVZ
ADF
ZYK

INIT
SI1
SI2

SIEMENS

6ES5948–3UA11

BASP
SI1

Fault Indicator LEDs (red)
Fault Indicator LED (red)
Interface Fault Indicator LEDs (red)
Interface SI1
PG Interface, 15-Pin

SI2

Second Serial Interface SI2
Receptacle for Interface Module

Oder Number and Version
Release Lever

Locking Pin

Figure 5-4

5-20

Controls and Indicators of the CPU 948

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Mode Switch

The mode switch has two settings:

RUN

In the RUN setting, the CPU 948 processes the user program when the green
RUN LED is lit.

STOP

The CPU 948 will go to a soft STOP when you switch over from RUN to
STOP. The red STOP LED will then light up.

MomentaryContact Mode
Switch

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch and the mode changeover switch:

OVERALL RESET

Momentary-contact switch down
During an overall reset, the internal RAM is re-initialized, i.e. existing data
will be erased and the contents of the memory card, if present, will be copied
into the internal RAM.

Reset

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Restart

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters and the process image are
retained during stoppage of the CPU.

System Manual
C79000-G8576-C199-06

5-21

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Status Indicators

Given in the following overview are the functions of the RUN, STOP and
SYS FAULT status LEDs.
The STOP LED indicates a soft stop; the SYS FAULT LED indicates a hard
STOP.
The CPU 948 can process a user program (OB 39) cyclically at the soft
STOP, but the digital outputs remain inhibited. At the hard STOP, no program
can run and the CPU has “stopped.” This state can only be exited by
switching the system voltage off and on again.

5-22

RUN
LED

STOP
LED

SYS
Status
FAULT
LED

on

off

off

The CPU is in the RUN state (cyclic
operation).

on

on

on

Appears briefly after power-up of the unit.

off

off

off

CPU is in the initial start or program check
state.

off

on

off

CPU is in the soft STOP state.

off

rapid
flashing

off

CPU is in the soft STOP state.
Overall reset has been requested by switch or
from the operating system.

off

slow
flashing

off

CPU is in the soft STOP state. An error has
occurred; see the CPU 948 Programming
Guide for possible causes.

off

off

on

CPU is in the hard STOP state. No program
processing is taking place. You can only exit
from this state by switching the system
voltage off and on again.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

LEDs for Fault
Indication and
Signaling

Given in the following overview are the causes for LEDs lighting up:
QVZ LED
on

A module addressed by the program no longer acknowledges
although/because
it either acknowledged in single-processor operation upon
restart of the CPU 948 in the area of the process image
(IB0 to 127, QB0 to 127) and has been entered as present
in the so-called 9th track;
or it has been entered in multi or single-processor
operation in DB 1 (address list) and has been recognized
as present during the restart;
or it was addressed in direct access by operations LPY,
LPW, TPY, TPW, LOY, LOW, TOY, TOW;
or the data handling blocks cannot access the module.
Possible causes:
Module failure
Module removed during operation, in the STOP state or in
the Off state without subsequent restart.
A timeout occurred during access to the user memory.

ADF LED
on

The user program has referred to an address in the process
image under which no module was inserted in the I/Os or was
not entered in DB 1 during the last restart.

ZYK LED
on

The preset cycle time monitor has responded and cyclic
program processing is interrupted.

BASP LED
on

Command output is inhibited and the digital outputs will be
directly switched to the safe state (0).

INIT LED
on

This LED is continuously lit for a short time during
initialization after power ON and during operation in the
event of system faults.

A detailed description of interrupt and error handling can be found in the
CPU 948 Programming Guide.

System Manual
C79000-G8576-C199-06

5-23

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Fault LEDs SI1
and SI2

LEDs SI1 and SI2 indicate faults in communication via interfaces SI1
and SI2:

LED SI1

LED SI2 Cause

on

on

Communication is not possible at both interfaces.
Internal fault.

on

off

SI1:
No communication possible.
Internal fault.
SI2:
Interface is initialized and ready.
LED SI2 is always off if no interface module is
inserted.

off

on

SI1:
Interface is initialized and ready.
SI2:
No communication possible. Wrong module
inserted or internal fault.

off

5-24

off

Both interfaces are initialized and ready. LED SI2
is always off if no interface module is inserted.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The modules must be inserted at the correct slots in the central controller.
The backup battery must be fitted and in order for the CPU to start.

Overall Reset

Proceed as follows:
Step

Action

Resultat

1

Set the mode switch to STOP.

2

Switch the system voltage on. The following LEDs must light
up on the CPU:
– Red STOP LED (flashing
rapidly)
– Red INIT LED, briefly
– Red BASP 2) LED

3

Hold the MC 1) switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.

Die rote LED “STOP” zeigt nun
Dauerlicht.

1) MC: Momentary-contact
2) BASP: Command output inhibit

If the red SYS FAULT LED also lights up, an error has occurred during
overall reset. In this case the measures described must be repeated. If
necessary, switch the system voltage off and on again.
If the LED is still lit, the module is faulty.

Reset

Continue as follows:
Step

Action

4

Set the mode switch to STOP.

5

Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.

Result

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

The CPU is now in the RUN state
but still has no user program.

System Manual
C79000-G8576-C199-06

5-25

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Restart

You can also carry out a manual restart of the CPU 948 with the mode
switch. The CPU 948 Programming Guide will indicate when a manual
restart is permissible.
Step
1

Action

Result

Set the mode switch from
STOP to RUN

– Red STOP LED goes off
– RUN LED lights up
– Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.

5-26

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.2.3

Interfaces of the CPU 948
This section contains information on the interfaces of the CPU 948.

PG Interface SI1

You can use the PG interface on the CPU 948 either via the front connector
or via the 923C coordinator module and the S5 bus.
Note
Simultaneous operation of the PG interface via the front connector of the
CPU 948 and via the 923C coordinator is not possible. Switching the PG
online without a job request is already sufficient to operate the interface.
Electrically, it is merely a PG interface which can be operated via two
different terminals.

The connection to the PG can be established in every operational state of the
CPU.

Interface SI2

You can also use the second interface of the CPU 948 as a PG interface.
Physical adaptation is achieved with a PG module (see also Section 5.9,
Interface Submodules).
A detailed description of PG interfaces can be found in the CPU 948
Programming Guide.

Communication
via Parallel
Backplane Bus
with SINEC H1

A PG-PLC link via SINEC H1 allows very advanced communication
between the partners. For example, the user software can be loaded into the
CPU 948 up to eight-times faster than with serial communication.
For this link you will need, in addition to the CPU 948, a CPU 143 (Version
w 2.1) in the PLC and a PG7xx with SINEC H1 connection and the STEP 5
single-tasking software from Version 6.0 or multi-tasking from Version 2.0.
Note
You cannot implement communication via SINEC H1 in parallel with the
serial interfaces.

Communication via SINEC H1 is described in detail in the CPU 948
Programming Guide.

System Manual
C79000-G8576-C199-06

5-27

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.2.4

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533

Degree of protection

IP 00

Climatic ambient conditions

See Technical Specifications of the S5-135U/155U CC

Mechanical ambient conditions

See Technical Specifications of the S5-135U/155U CC

Noise immunity, electromagnetic
compatibility (EMC)

See Technical Specifications of the S5-135U/155U CC

Supply voltage

5V"5%

Current consumption at 5 V

3.6 A typical

Backup voltage

3.4 V

Backup current

10 mA typical (at 25 °C)

P area

O area

IM3 area

IM4 area

Total

Digital inputs with process image
Digital inputs without process image or
analog inputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Digital outputs with process image
Digital outputs without process image or
analog outputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Flags

2048

S flags

32768

Timers

256

Counters

256

Size of user memory

640 or 1664 Kbyte RAM

Transmission rate of serial PG interface

9600 bps

Program blocks PB

256

Sequence blocks SB

256

Function blocks FB

256

Function blocks FX

256

5-28

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Data blocks DB

256, of which 253 are freely available

Data blocks DX

256, of which 253 are freely available

Organization blocks OB

OB 1 to 39
(interfaces for operating system)

Integrated special function organization
blocks OB

OB 121, 122, 124-126, 131-133, 141-143, 150, 151, 153, 200,
202-205, 222, 223, 254, 255

Integrated serial interface

PG interface

Optional serial interface

PG interface with PG submodule

Backplane bus

S5 bus

Dimensions (w x h x d)

40.6 x 233.4 x 160 mm

Weight

Approx. 1 kg

System Manual
C79000-G8576-C199-06

5-29

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.3

CPU 928B -3UB21
This section contains the hardware description and technical specifications of
the CPU 928B -3UB21.
Details on programming the CPU 928B -3UB21 can be found in the
CPU 928B -3UB21 Programming Guide.

5.3.1

Technical Description

Application

You can use the CPU 928B in single and multiprocessor operation in the
S5-135U/155U central controller (see Chapter 6). Up to four CPUs can be
used.
The CPU 928B is universally applicable, ensuring both very fast bit
processing and very fast word processing.
The following program processing levels are possible:
Cyclic
Time-controlled (9 different timebases)
Real-time controlled
Interrupt-driven (hardware interrupt)
Delayed
The programming language is STEP 5.

Design

The electronic circuitry of the CPU 928B is on one PCB in the double
Eurocard format. The board provides the connection to the S5 bus via two
backplane connectors.
The front plate width is 1 1/3 standard plug-in stations.

5-30

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

User Memory

For storage of your program, user memory in the form of RAM is integrated
on the board. You can store up to 64 x 210 bytes of code and data blocks here.
For data blocks, the CPU 928B additionally has an integrated DB RAM of
46 3/4 x 210 bytes.

Memory Card

As an external memory medium for user programs and user data, you can use
a memory card 374 with Flash EPROM.

PG Interface SI1

There are two independent interfaces on the front of the CPU 928B.
You can connect programmers and OPs to the first interface. This PG
interface SI1 is permanently installed on the CPU.
You can use PG interface SI1 either via the front connector of the CPU 928B
or via the front connector of the 923C coordinator module.

Note
Simultaneous operation of PG interface SI1 via the front connector of the
CPU 928B and of the coordinator is not possible. Electrically, it is merely a
PG interface which can be operated via two different terminals. Switching
the programmer online without a job request is already sufficient to operate
the interface. If you wish to utilize a second PG interface for connection of a
PG or OP, the connection must be made via the second PG interface with the
PG submodule.

Apart from PG interface SI1, the second interface SI2 can also be used as a
PG interface in parallel with the first one. You can only use the second PG
interface via the front connector of the PG submodule on the CPU 928B.
A detailed description of operations with the two PG interfaces can be found
in the CPU 928B -3UB21 Programming Guide.
The connection to the PG can be established with the CPU in any operational
state.

System Manual
C79000-G8576-C199-06

5-31

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Second Interface
SI2

You can optionally use the second interface of the CPU 928B as:
A PG interface (for PG and operator panels)
Interface for the RK 512 computer link
Interface for data transmission with procedures 3964/3964R
Interface for data transmission with the “open driver”
Interface for data transmission via the SINEC L1 bus (from Version 6ES5
928-3UB12).
To utilize the second interface as the PG interface, you need the
RG submodule
You need one of the following interface submodules for the RK 512
computer link, for data transmission with procedures 3964/3964R and for
data transmission with the “open driver”:
V.24 submodule (RS 232C)
TTY submodule
RS422 A/485 submodule (only in the RS422 A mode).
To utilize the second interface for data transmission via the SINEC L1 bus,
you need the
SINEC L1 submodule (from Version 6ES5 928-3UB12).
The CPU 928B is delivered without an interface submodule. You can operate
the CPU 928B without an integral interface submodule. The opening to
accept a submodule in the front plate is closed by a cover. Only remove the
cover to fit an interface submodule.
A description of interface submodules can be found in Section 5.11, and the
order numbers in the ordering information.
A detailed description of the second interface can be found in the
CPU 928B/CPU 948 Communication Manual.

Process Interrupt
Processing

There is an interrupt line in the PLC for each CPU. It can be used when the
reaction to an event must occur with higher priority than the reaction to other
events.
To process an interrupt, cyclic program processing is interrupted and the
program stored in OB 2 (OB for interrupt processing) is inserted (refer to the
CPU 928B -3UB21 Programming Guide for further details).
This interrupt-driven program processing is only possible using an
interrupt-capable digital input module or a suitable operating CP/IP module.
No jumper setting on the CPU 928B is required. Please note, however, that
the usable interrupt line on the backplane bus depends on the CPU slot and
must be set accordingly on the I/O module (see Section 4.1).

5-32

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.3.2

Installation and Startup

Jumper Settings
Note
All jumpers on the CPU 928B are required by the manufacturer for quality
testing. You must not change the jumper settings.

Removing and
Inserting the
Module

!
Insertion

Caution
Switch off the power supply before removing or inserting the module.

Proceed as follows to insert the CPU in the central controller:
Step

Action

1

Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U from slot 11.

3

Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.

4

Press the locking pin inwards on the bottom of the module and
rotate it 90 clockwise.

5

Secure the upper locking bar.

Note
If you install the CPU 928B -3UB21 as the replacement for a double-width
CPU 928 or 928B, you must cover the slot which has been freed up with a
blanking plate.

System Manual
C79000-G8576-C199-06

5-33

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Removal

Proceed as follows to remove the CPU:
Step

Action

1

Release the upper locking bar of the central controller.

2

Release the locking pin of the module.

3

Press the release lever downwards and pull the module forwards
and out of the central controller.

Note
Only operate the CPU 928B with the submodule receptacle closed. You
close it either by fitting an interface submodule or with the cover supplied.

5-34

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Controls and
Indicators

The controls and indicators are arranged on the front plate of the CPU
module:

CPU 928B

Fault Indicator LEDs (red)

QVZ

ADF

Receptacle for
User Memory Submodule

ZYK

BASP

RUN

LEDs (green)
Mode Switch

STOP

LED (red)

RESET

Momentary-Contact Mode Switch
OVERALL
RESET

Interface Fault Indicator LED (red)
Interface 1
PG Interface, 15-Pin
Interface SI 1

Interface Fault Indicator LED (red)
Interface 2
Order Number and Version

Receptacle for Interface Submodule
Interface SI 2

SIEMENS

6ES5928-3UB21

SI2

Release Lever
Locking Pin
Figure 5-5

System Manual
C79000-G8576-C199-06

Front Plate of the CPU 928B-3UB21

5-35

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Mode Switch

The mode switch has two settings:

RUN

In the RUN setting, the CPU 928B processes the user program when the
green RUN LED is lit.

STOP

The CPU 928B goes to the stop state when you switch from RUN to STOP.
The red STOP LED then lights up.

MomentaryContact Mode
Switch

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch:

OVERALL RESET

Momentary-contact switch down
With an overall reset, all RAM areas are erased and initialized (both on the
CPU and on a RAM submodule).

Reset

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Restart

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters and the process image are
retained during stoppage of the CPU.

5-36

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Status Indicators
RUN
LED

STOP
LED

Status

on

off

The CPU is in the RUN state.

off

on

The CPU is in the STOP state. After a stop
request by switch or PG function, the STOP LED
is continuously lit because the transition to the
STOP state was requested by the user or, in
multiprocessor operation, by another CPU, and
was not caused by the CPU itself.

off

off

The CPU is in the INITIAL START or program
check state.

off

slow
flashing

The CPU is in the STOP state. The CPU has
caused a transition to the STOP state (possibly
also for the other CPUs). If you set the mode
switch to STOP, the flashing LED becomes
continuously lit.

off

rapid
flashing

The CPU is in the STOP state. An overall reset
has been requested. This request can be initiated
by the CPU itself or by operator action.

LEDs for Fault
Indication and
Signaling
QVZ LED
on

During direct access or process image update, a module
addressed by the program no longer acknowledges although
either it has acknowledged in single-processor operation
upon reset of the CPU 928B in the area of the process
image (IB 0 to 127, QB 0 to 127) and has been entered as
present in the “9th track” (see Programming Guide,
CPU 928B -3UB21),
or it has
h been
b
entered
t d iin DB 1 ((address
dd
li
list)
t) iin
multiprocessor or single-processor operation and has been
recognized as present during the reset.
Possible causes
Module failure.
Module was pulled out during operation, in the STOP
state or in the Off state without a subsequent reset.

System Manual
C79000-G8576-C199-06

5-37

CPUs, Memory Cards, Memory Submodules, Interface Submodules

ADF LED
on

The user program has referenced an I/O address in the
process image under which no module is inserted.

ZYK LED
on

The maximum cycle monitoring time has been exceeded.

BASP LED
on

Command output is inhibited and the digital outputs will be
directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the
CPU 928B -3UB21 Programming Guide.
LED SI1

LED SI2 Cause

on

on

No communication possible at both interfaces.
Internal error.

on

off

SI1:
No communication possible.
Internal error.
SI2:
If used, interface is initialized and ready.

off

on

SI1:
Interface is initialized and ready.
SI2:
No communication possible.
Wrong interface submodule inserted or wrong
parameters for interface or internal error.

off

5-38

off

First interface and, if used, second interface are
initialized and ready.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The modules must be inserted at the correct slots in the central controller.
The backup battery must be fitted and in order for the CPU to start.

Overall Reset
Step

1)
2)

Action

Result

1

Set the mode switch to STOP

2

Switch the system voltage on. The following LEDs must light
up on the CPU:
– Red STOP LED
(flashing rapidly)
– Red BASP2) LED

3

Hold the MC1) switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.

The red STOP LED is now
permanently lit.

MC: Momentary-contact
BASP: Command output inhibit

Reset
Step

Restart

Action

1

Set the mode switch to STOP.

2

Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.

Result

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

The CPU is now in the RUN state
but still has no user program.

You can also carry out a manual restart of the CPU 928B with the mode
switch. The CPU 928B -3UB21 Programming Guide will indicate when a
manual restart is permissible.
Step
3

Action

Result

Set the mode switch from
STOP to RUN.

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.

System Manual
C79000-G8576-C199-06

5-39

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.3.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:

S UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972

S CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection

IP 00

Climatic ambient conditions

See Technical Specifications of the S5-135U/155U CC

Mechanical ambient conditions

See Technical Specifications of the S5-135U/155U CC

Noise immunity, electromagnetic
compatibility (EMC)

See Technical Specifications of the S5-135U/155U CC

Supply voltage

5V$5%
24 V + 25 %/ –17 %

Current consumption at 5 V

0.5 A typical

Current consumption at 24 V

760 mA max.

Backup voltage

3.4 V

Backup current

20 mA typical (at 25 _C)
P area

O area

IM3 area

IM4 area

Total

Digital inputs with process image
Digital inputs without process image
or analog inputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Digital outputs with process image
Digital outputs without process image
or analog outputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Flags

2048

S flags

8192

Timers

256

Counters

256

Size of user memory

64 x 2!) bytes max., RAM

DB RAM

46 x 2!) bytes

Transmission rate of the serial PG interface

9600 bps

Program blocks PB

256

Sequence blocks SB

256

Function blocks FB

256

Function blocks FX

256

Data blocks DB

256, of which 253 are freely available

Data blocks DX

256, of which 253 are freely available

5-40

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Organization blocks OB

OB 1 to 39 (interfaces for operating system)

Integrated special function organization
blocks OB

See Pocket Guide

Integrated serial interface

PG interface

Optional serial interface

Via interface submodules, optionally as V.24, TTY, RS 422A/485 or
PG interface,
SINEC L1 interface from Version 6ES5 928-3UB12

Backplane bus

S5 bus

Dimensions (w x h x d)

20.32 x 233.4 x 160 mm

Weight

Approx. 0.6 kg

System Manual
C79000-G8576-C199-06

5-41

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.4

CPU 928B
This section contains the hardware description and technical specifications of
the CPU 928B.
Details on programming the CPU 928B can be found in the CPU 928B
Programming Guide.

5.4.1

Technical Description

Application

You can use the CPU 928B in single and multiprocessor operation in the
S5-135U/155U central controller (see Chapter 6). Up to four CPUs can be
used.
The CPU 928B is universally applicable, ensuring both very fast bit
processing and very fast word processing:
Cyclic
Time-controlled (9 different timebases)
Real-time controlled
Interrupt-driven (hardware interrupt)
Delayed (from Version 6ES5 928-3UB12)
The programming language is STEP 5.

Design

The electronic circuitry of the CPU 928B is on two PCBs (basic and
expansion boards) in the double Eurocard format. Both PCBs are screwed
together, linked via connectors, and must not be separated. The basic board
provides the connection to the S5 bus via two backplane connectors.
The front plate width is 2 2/3 standard plug-in stations.

5-42

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

User Memory

You require a user memory submodule (RAM or EPROM) for storage of your
program. You can store up to 64 x 210 bytes of code and data blocks here. For
data blocks, the CPU 928B additionally has an integrated DB RAM of 46 x
210 bytes.
A description of the memory submodules can be found in Sections 5.9 and
5.10; order numbers are given in the ordering information.

PG Interface SI1

There are two independent interfaces on the front of the CPU 928B.
You can connect programmers and OPs to the first interface. This PG
interface SI1 is permanently installed on the CPU.
You can use PG interface SI1 either via the front connector of the CPU 928B
or via the front connector of the 923C coordinator module.
Note
Simultaneous operation of PG interface SI1 via the front connector of the
CPU 928B and of the coordinator is not possible. Electrically, it is merely a
PG interface which can be operated via two different terminals. Switching
the programmer online without a job request is already sufficient to operate
the interface. If you wish to utilize a second PG interface for connection of a
PG or OP, the connection must be made via the second PG interface with the
PG submodule.

Apart from PG interface SI1, the second interface SI2 can also be used as a
PG interface in parallel with the first one. You can only use the second PG
interface via the front connector of the PG submodule on the CPU 928B.
A detailed description of operations with the two PG interfaces can be found
in the CPU 928B Programming Guide.
The connection to the PG can be established with the CPU in any operational
state.

System Manual
C79000-G8576-C199-06

5-43

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Second Interface
SI2

You can optionally use the second interface of the CPU 928B as:
A PG interface (for PG and operator panels)
Interface for the RK 512 computer link
Interface for data transmission with procedures 3964/3964R
Interface for data transmission with the “open driver”
Interface for data transmission via the SINEC L1 bus (from Version 6ES5
928-3UB12).
To utilize the second interface as the PG interface, you need the
PG submodule.
You need one of the following interface submodules for the RK 512
computer link, for data transmission with procedures 3964/3964R and for
data transmission with the “open driver”:
V.24 submodule (RS 232C)
TTY submodule
RS422 A/485 submodule (only in the RS422 A module).
To utilize the second interface for data transmission via the SINEC L1 bus,
you need the
SINEC L1 submodule (from Version 6ES5 928-3UB12).
The CPU 928B is delivered without an interface submodule. You can operate
the CPU 928B without an integral interface submodule. The opening to
accept a submodule in the front plate is closed by a cover. Only remove the
cover to fit an interface submodule.
A description of interface submodules can be found in Section 5.11, and the
order numbers in the ordering information.
A detailed description of the second interface can be found in the CPU 928B
Communication Manual.

Process Interrupt
Processing

There is an interrupt line in the PLC for each CPU. It can be used when the
reaction to an event must occur with higher priority than the reaction to other
events.
To process an interrupt, cyclic program processing is interrupted and the
program stored in OB 2 (OB for interrupt processing) is inserted.
(Refer to the CPU 928B Programming Guide for further details.)
This interrupt-driven program processing is only possible using an
interrupt-capable digital input module or a suitable operating CP/IP module.
No jumper setting on the CPU 928B is required. Please note, however, that
the usable interrupt line on the backplane bus depends on the CPU slot and
must be set accordingly on the I/O module (see Section 4.1).

5-44

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.4.2

Installation and Startup

Jumper Settings
Note
All jumpers on the CPU 928B are required by the manufacturer for quality
testing. You must not change the jumper settings.

Removing and
Inserting the
Module

!

Insertion

Caution
Switch off the power supply before removing or inserting the module. The
basic board and expansion board of the CPU 928B are one unit and must not
be separated.

Proceed as follows to insert the CPU in the central controller:
Step

System Manual
C79000-G8576-C199-06

Action

1

Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U from slot 11.

3

Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.

4

Press the locking pin inwards on the bottom of the module and
rotate it 90o clockwise.

5

Secure the upper locking bar.

5-45

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Removal

Proceed as follows to remove the CPU:
Step

Action

1

Release the upper locking bar of the central controller.

2

Release the locking pin of the module.

3

Press the release lever downwards and pull the module forwards
and out of the central controller.

Note
Only operate the CPU 928B with the submodule receptacle closed. You
close it either by fitting an interface submodule or with the cover supplied.

5-46

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Controls and
Indicators

The controls and indicators are arranged on the front plate of the CPU
module:

CPU 928B

Receptacle for
User Memory Submodule

RUN

Mode Switch

STOP

LED (green)
RUN
STOP

LED (red)

RÜCKSETZEN
RESET

Momentary-Contact Mode Switch
URLÖSCHEN
OVERALLRESET

Fault Indicator LEDs (red)
QVZ

SI1

ADF

SI2

SIEMENS 6ES5928-3UB12

ZYK
BASP
SI2

SI1

Interface Fault Indicator LEDs (red)
Interface 1
Interface 2
Order Number and Release

Receptacle for Interface Submodule
Interface SI 2

PG Interface, 15-Pin
Interface SI 1
Release Lever
Locking Pin

Figure 5-6

System Manual
C79000-G8576-C199-06

Front Plate of the CPU 928B

5-47

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Mode Switch

The mode switch has two settings:

RUN

In the RUN setting, the CPU 928B processes the user program when the
green RUN LED is lit.

STOP

The CPU 928B goes to the stop state when you switch from RUN to STOP.
The red STOP LED then lights up.

MomentaryContact Mode
Switch

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch:

OVERALL RESET

Momentary-contact switch down
With an overall reset, all RAM areas are erased and initialized (both on the
CPU and on a RAM submodule).

RESET

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Restart

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters and the process image are
retained during stoppage of the CPU.

5-48

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Status Indicators
RUN
LED

STOP
LED

Status

on

off

The CPU is in the RUN state.

off

on

The CPU is in the STOP state. After a stop
request by switch or PG function, the STOP LED
is continuously lit because the transition to the
STOP state was requested by the user or, in
multiprocessor operation, by another CPU, and
was not caused by the CPU itself.

off

off

The CPU is in the INITIAL START or program
check state.

off

slow
flashing

The CPU is in the STOP state. The CPU has
caused a transition to the STOP state (possibly
also for the other CPUs). If you set the mode
switch to STOP, the flashing LED becomes
continuously lit.

off

rapid
flashing

The CPU is in the STOP state. An overall reset
has been requested. This request can be initiated
by the CPU itself or by operator action.

LEDs for Fault
Indication and
Signaling
QVZ LED
on

During direct access or process image update, a module
addressed by the program no longer acknowledges although
either it has acknowledged in single-processor operation
upon reset of the CPU 928B in the area of the process
image (IB 0 to 127, QB 0 to 127) and has been entered as
present in the “9th track” (see Programming Guide, CPU
928B),
or it has
h been
b
entered
t d iin DB 1 ((address
dd
li
list)
t) iin
multiprocessor or single-processor operation and has been
recognized as present during the reset.
Possible causes
Module failure.
Module was pulled out during operation, in the STOP
state or in the Off state without a subsequent reset.

System Manual
C79000-G8576-C199-06

5-49

CPUs, Memory Cards, Memory Submodules, Interface Submodules

ADF LED
on

The user program has referenced an I/O address in the
process image under which no module is inserted.

ZYK LED
on

The maximum cycle monitoring time has been exceeded.

BASP LED
on

Command output is inhibited and the digital outputs will be
directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the
CPU 928B Programming Guide.

LED SI1

LED SI2 Cause

on

on

No communication possible at both interfaces.
Internal error.

on

off

SI1:
No communication possible. Internal error.
SI2:
If used, interface is initialized and ready.

off

on

SI1:
Interface is initialized and ready.
SI2:
No communication possible.
Wrong interface submodule inserted or wrong
parameters for interface or internal error.

off

5-50

off

First interface and, if used, second interface are
initialized and ready.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The modules must be inserted at the correct slots in the central controller.
The backup battery must be fitted and in order for the CPU to start.

Overall Reset
Step

1)
2)

Action

Result

1

Set the mode switch to STOP.

2

Switch the system voltage on. The following LEDs must light
up on the CPU:
– Red STOP LED (flashing
rapidly)
– Red BASP2) LED

3

Hold the MC1) switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.

The red STOP LED is now
permanently lit.

MC: Momentary-contact
BASP: Command output inhibit

Reset
Step

Restart

Action

1

Set the mode switch to STOP.

2

Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.

Result

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

The CPU is now in the RUN state
but still has no user program.

You can also carry out a manual restart of the CPU 928B with the mode
switch. The CPU 928B Programming Guide will indicate when a manual
restart is permissible.
Step
3

Action

Result

Set the mode switch from
STOP to RUN.

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.

System Manual
C79000-G8576-C199-06

5-51

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.4.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:

S UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972

S CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection

IP 00

Climatic ambient conditions

See Technical Specifications of the S5-135U/155U CC

Mechanical ambient conditions

See Technical Specifications of the S5-135U/155U CC

Noise immunity, electromagnetic
compatibility (EMC)

See Technical Specifications of the S5-135U/155U CC

Supply voltage

5V$5%
24 V + 25 %/ -17 %

Current consumption at 5 V

5 A typical

Current consumption at 24 V

760 mA max.

Backup voltage

3.4 V

Backup current

20 mA typical (at 25 _C)
P area

O area

IM3 area

IM4 area

Total

Digital inputs with process image
Digital inputs without process image
or analog inputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Digital outputs with process image
Digital outputs without process image
or analog outputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Flags

2048

S flags

8192

Timers

256

Counters

256

Size of user memory

64 x 2!) bytes max., EPROM or RAM

DB RAM

46 x 2!) byte

Transmission rate of the serial PG interface

9600 bps

Program blocks PB

256

Sequence blocks SB

256

Function blocks FB

256

Function blocks FX

256

Data blocks DB

256, of which 253 are freely available

Data blocks DX

256, of which 253 are freely available

5-52

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Organization blocks OB

OB 1 to 39 (interfaces for operating system)

Integrated special function organization
blocks OB

See Pocket Guide

Integrated serial interface

PG interface

Optional serial interface

Via interface submodules, optionally as V.24, TTY, RS 422A/485 or
PG interface
SINEC L1 interface from Version 6ES5 928-3UB12

Backplane bus

S5 bus

Dimensions (w x h x d)

40.64 x 233.4 x 160 mm

Weight

Approx. 1 kg

System Manual
C79000-G8576-C199-06

5-53

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.5

CPU 928 -3UA21
This section contains the hardware description and technical specifications of
the CPU 928 -3UA21.
Details on programming the CPU 928 can be found in the CPU 928
Programming Guide.

5.5.1

Technical Description

Application

You can use the CPU 928 in single and multiprocessor operation in the
S5-135U/155U central controller (see Chapter 6). Up to four CPUs can be
used.
The CPU 928 is universally applicable, ensuring both very fast bit processing
(optimized for open-loop tasks) and word processing (optimized for
closed-loop tasks).
The following program processing levels are possible:
Cyclical
Time-controlled (9 different timebases)
Interrupt-driven (hardware interrupt)

The programming language is STEP 5.

Design

The electronic circuitry of the CPU 928 is on one PCB in the double
Eurocard format. The board provides the connection to the S5 bus via two
backplane connectors.
The front plate width is 1 1/3 standard plug-in stations.

5-54

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

User Memory

For storage of your program, user memory in the form of RAM is integrated
on the board. You can store up to 64 x 210 bytes of code and data blocks here.
For data blocks, the CPU 928 additionally has an integrated DB RAM of 46 x
210 bytes.
Note
The DB RAM is loaded with DB/DX blocks when the user memory is full.

Process Interrupt
Processing

There is an interrupt line (IR) in the PLC for each CPU. It can be used when
the reaction to one or more events must occur with higher priority than the
reaction to other events.
To process a process interrupt, cyclic program processing is interrupted and
the program stored in OB 2 (OB for interrupt processing) is inserted. (Refer
to the CPU 928 Programming Guide for further details.)
This interrupt-driven program processing is only possible using an
interrupt-capable digital input module (e.g. 6ES5 432-...) or a CP/IP module
which operates in this way.

System Manual
C79000-G8576-C199-06

5-55

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.5.2

Installation and Startup

Removing and
Inserting the
Module

!
Insertion

Caution
Switch off the power supply before removing or inserting the module.

Proceed as follows to insert the CPU in the central controller:
Step

Action

1

Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U from slot 11.

3

Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.

4

Press the locking pin inwards on the bottom of the module and
rotate it 90o clockwise.

5

Secure the upper locking bar.

Note
If you install the CPU 928 -3UA21 as the replacement for a double-width
CPU, you must cover the slot which has been freed up with a blanking plate.

Removal

Proceed as follows to remove the CPU:
Step

5-56

Action

1

Release the upper locking bar of the central controller.

2

Release the locking pin of the module.

3

Press the release lever downwards and pull the module forwards
and out of the central controller.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Controls and
Indicators

The controls and indicators are arranged on the front plate of the CPU
module:

CPU 928A

Fault Indicator LEDs (red)

QVZ
ADF

Receptacle for
User Memory Submodule

ZYK
BASP

RUN

LED (green)
Mode Switch

STOP
RESET

LED (red)
Momentary-Contact Mode Switch

OVERALL
RESET

SI1

Interface Fault Indicator LED (red)

SIEMENS ES5928-3UA21

PG Interface, 15-Pin

Order Number and Version

Release Lever
Locking Pin

Figure 5-7

System Manual
C79000-G8576-C199-06

Front Plate of the CPU 928 -3UA21

5-57

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Mode Switch

The mode switch has two settings:

RUN

In the RUN setting, the CPU 928-3UA21 processes the user program when
the green RUN LED is lit.

STOP

The CPU 928-3UA21 goes to the stop state when you switch from RUN to
STOP. The red STOP LED then lights up.

MomentaryContact Mode
Switch

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch:

OVERALL RESET

Momentary-contact switch down
With an overall reset, all RAM areas are erased and initialized.

RESET

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Restart

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters and the process image are
retained during stoppage of the CPU.

Status Indicators

5-58

RUN
LED

STOP
LED

Status

on

off

The CPU is in the RUN state.

off

on

The CPU is in the STOP state. After a stop
request by switch or PG function, the STOP LED
is continuously lit because the transition to the
STOP state was requested by the user or, in
multiprocessor operation, by another CPU, and
was not caused by the CPU itself.

off

off

The CPU is in the INITIAL START or program
check state.

off

slow
flashing

The CPU is in the STOP state. The CPU has
caused a transition to the STOP state (possibly
also for the other CPUs). If you set the mode
switch to STOP, the flashing LED becomes
continuously lit.

off

rapid
flashing

The CPU is in the STOP state. An overall reset
has been requested. This request can be initiated
by the CPU itself or by operator action.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

LEDs for Fault
Indication and
Signaling
QVZ LED
on

During direct access or process image update, a module
addressed by the program no longer acknowledges although
either it has acknowledged in single processor operation
upon reset of the CPU 928 in the area of the process
image (IB 0 to 127, QB 0 to 127) and has been entered as
present in the “9th track” (see Programming Guide,
CPU 928),
or it has
h been
b
entered
t d iin DB 1 ((address
dd
li
list)
t) iin
multiprocessor or single-processor operation and has been
recognized as present during the reset.
Possible causes
Module failure.
Module was pulled out during operation, in the stop state
or in the Off state without a subsequent reset.

ADF LED
on

The user program has referenced an I/O address under which
no module is inserted.

ZYK LED
on

The maximum cycle time has been exceeded.

BASP LED
on

Command output is inhibited and the digital outputs will be
directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the
CPU 928 Programming Guide.

System Manual
C79000-G8576-C199-06

5-59

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The module must be inserted at the correct slot in the central controller. The
backup battery must be fitted and in order for the CPU to start.

Overall Reset
Step

1)

Action

Result

1

Set the mode switch to STOP

2

Switch the system voltage on. The following LEDs must light
up on the CPU:
– Red STOP LED (flashing
rapidly)
– Red BASP LED

3

Hold the MC1) switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.

The red STOP LED is now
permanently lit.

MC: Momentary-contact

Reset
Step

Restart

Action

1

Set the mode switch to STOP.

2

Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.

Result

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

The CPU is now in the RUN state
but still has no user program.

You can also carry out a manual restart of the CPU 928-3UA21 with the
mode switch. The CPU 928 Programming Guide will indicate when a manual
restart is permissible.
Step
1

Action

Result

Set the mode switch from
STOP to RUN.

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.

5-60

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.5.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:

S UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972

S CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection

IP 00

Climatic ambient conditions

See Technical Specifications of the S5-135U/155U CC

Mechanical ambient conditions

See Technical Specifications of the S5-135U/155U CC

Noise immunity, electromagnetic
compatibility (EMC)

See Technical Specifications of the S5-135U/155U CC

Supply voltage

5V$5%

Current consumption at 5 V

0.5 A typical

Backup voltage

3.4 V

Backup current

20 mA typical (at 25 _C)
P area

O area

IM3 area

IM4 area

Total

Digital inputs with process image
Digital inputs without process image
or analog inputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Digital outputs with process image
Digital outputs without process image
or analog outputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Flags

2048

Timers

256

Counters

256

Size of user memory

max. of 64 x 210 words, RAM

DB RAM

46 x 210 bytes

Transmission rate of serial PG interface

9600 bps

Program blocks PB

256

Sequence blocks SB

256

Function blocks FB

256

Function blocks FX

256

Data blocks DB

256, of which 253 are freely available

Data blocks DX

256, of which 253 are freely available

Organization blocks OB

OB 1 to 39 (interfaces for operating system)

Integrated special function organization
blocks OB

See Pocket Guide

Dimensions (w x h x d)

20.32 x 233.4 x 160 mm

Weight

Approx. 0.6 kg

System Manual
C79000-G8576-C199-06

5-61

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.6

CPU 928
This section contains the hardware description and technical specifications of
the CPU 928.
Details on programming the CPU 928 can be found in the CPU 928
Programming Guide.

5.6.1

Technical Description

Application

You can use the CPU 928 in single and multiprocessor operation in the
S5-135U/155U central controller (see Chapter 6). Up to four CPUs can be
used.
The CPU 928 is universally applicable, ensuring both very fast bit processing
(optimized for open-loop tasks) and word processing (optimized for
closed-loop tasks).
The following program processing levels are possible:
Cyclical
Time-controlled (9 different timebases)
Interrupt-driven (hardware interrupt)
The programming language is STEP 5.

Design

The CPU 928 comprises two PCBs (PCB 1 and PCB 2) in the double
Eurocard format, in a sandwich assembly. The two PCBs have plug-in
interconnections and are bolted together as a unit when delivered. PCB 2
serves as the basic board which provides the connection to the S5 bus via two
backplane connectors.
The front plate width is 2 2/3 standard plug-in stations.

5-62

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

User Memory

You require a user memory submodule (RAM or EPROM) for storage of your
program. You can store up to 64 x 210 bytes of code and data blocks here. For
data blocks, the CPU 928 additionally has an integrated DB RAM of 46 x 210
bytes.
Note
The DB RAM is loaded with DB/DX blocks when the RAM submodule is
full or an EPROM submodule is plugged in.

A description of the memory submodules can be found in Sections 5.9 and
5.10; order numbers are given in the ordering information.

Process Interrupt
Processing

There is an interrupt line (IR) in the PLC for each CPU. It can be used when
the reaction to one or more events must occur with higher priority than the
reaction to other events.
o process an interrupt, cyclic program processing is interrupted and the
program stored in OB 2 (OB for interrupt processing) is inserted.
(Refer to the CPU 928 Programming Guide for further details.)
This interrupt-driven program processing is only possible using an
interrupt-capable digital input module (e.g. 6ES5 432-...) or a CP/IP module
which operates in this way.

System Manual
C79000-G8576-C199-06

5-63

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.6.2

Installation and Startup

Removing and
Inserting the
Module

!

Caution
Switch off the power supply before removing or inserting the module.
The basic board and expansion board of the CPU 928 are one unit and must
not be separated.

Insertion

Proceed as follows to insert the CPU in the central controller:
Step

Removal

1

Release the upper locking bar of the central controller and ensure
that the locking pin for the module is correctly positioned with the
slot-head horizontal.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U from slot 11.

3

Push the module evenly into the guide rail until the lever over the
locking pin is horizontal.

4

Press the locking pin inwards on the bottom of the module and
rotate it 90o clockwise.

5

Secure the upper locking bar.

Proceed as follows to remove the CPU:
Step

5-64

Action

Action

1

Release the upper locking bar of the central controller.

2

Release the locking pin of the module.

3

Press the release lever downwards and pull the module forwards
and out of the central controller.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Controls and
Indicators

The controls and indicators are arranged on the front plate of the CPU
module:

Receptacle for
User Memory Submodule

RUN

Mode Switch

STOP

LED (green)
RUN
STOP

LED (red)

RÜCKSETZEN
RESET

Momentary-Contact Mode Switch
URLÖSCHEN
OVERALL
RESET

Fault Indicator LEDs (red)

SIEMENS 6ES5928-3UA12

QVZ
ADF
ZYK
BASP

Order Number and Version

PG Interface, 15-Pin

Release Lever
Locking Pin

Figure 5-8

System Manual
C79000-G8576-C199-06

Front Plate of the CPU 928

5-65

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Mode Switch

The mode switch has two settings:

RUN

In the RUN setting, the CPU 928 processes the user program when the green
RUN LED is lit.

STOP

The CPU 928 goes to the stop state when you switch from RUN to STOP.
The red STOP LED then lights up.

MomentaryContact Mode
Switch

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch:

OVERALL RESET

Momentary-contact switch down
With an overall reset, all RAM areas are erased and initialized (both on the
CPU and on a RAM submodule).

RESET

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Restart

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters and the process image are
retained during stoppage of the CPU.

5-66

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Status Indicators

System Manual
C79000-G8576-C199-06

RUN
LED

STOP
LED

Status

on

off

The CPU is in the RUN state.

off

on

The CPU is in the STOP state. After a stop
request by switch or PG function, the STOP LED
is continuously lit because the transition to the
STOP state was requested by the user or, in
multiprocessor operation, by another CPU, and
was not caused by the CPU itself.

off

off

The CPU is in the INITIAL START or program
check state.

off

slow
flashing

The CPU is in the STOP state. The CPU has
caused a transition to the STOP state (possibly
also for the other CPUs). If you set the mode
switch to STOP, the flashing LED becomes
continuously lit.

off

rapid
flashing

The CPU is in the STOP state. An overall reset
has been requested. This request can be initiated
by the CPU itself or by operator action.

5-67

CPUs, Memory Cards, Memory Submodules, Interface Submodules

LEDs for Fault
Indication and
Signaling
QVZ LED
on

During direct access or process image update, a module
addressed by the program no longer acknowledges although
either it has acknowledged in single processor operation
upon reset of the CPU 928 in the area of the process
image (IB 0 to 127, QB 0 to 127) and has been entered as
present in the “9th track” (see Programming Guide,
CPU 928),
or it has
h been
b
entered
t d iin DB 1 ((address
dd
li
list)
t) iin
multiprocessor or single-processor operation and has been
recognized as present during the reset.
Possible causes
Module failure.
Module was pulled out during operation, in the stop state
or in the Off state without a subsequent reset.

ADF LED
on

The user program has referenced an I/O address under which
no module is inserted.

ZYK LED
on

The maximum cycle time has been exceeded.

BASP LED
on

Command output is inhibited and the digital outputs will be
directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the
CPU 928 Programming Guide.

5-68

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The modules must be inserted at the correct slots in the central controller.
The backup battery must be fitted and in order for the CPU to start.

Overall Reset
Step

1)

Action

Result

1

Set the mode switch to STOP

2

Switch the system voltage on. The following LEDs must light
up on the CPU:
– Red STOP LED (flashing
rapidly)
– Red BASP LED

3

Hold the MC1) switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.

The red STOP LED is now
permanently lit.

MC: Momentary-contact

Reset
Step

Restart

Action

1

Set the mode switch to STOP.

2

Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.

Result

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

The CPU is now in the RUN state
but still has no user program.

You can also carry out a manual restart of the CPU 928 with the mode
switch. The CPU 928 Programming Guide will indicate when a manual
restart is permissible.
Step
1

Action

Result

Set the mode switch from
STOP to RUN.

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.

System Manual
C79000-G8576-C199-06

5-69

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.6.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:

S UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972

S CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection

IP 00

Climatic ambient conditions

See Technical Specifications of the S5-135U/155U CC

Mechanical ambient conditions

See Technical Specifications of the S5-135U/155U CC

Noise immunity, electromagnetic
compatibility (EMC)

See Technical Specifications of the S5-135U/155U CC

Supply voltage

5V$5%

Current consumption at 5 V

3.5 A typical

Backup voltage

3.4 V

Backup current without user RAM
submodule

20 mA typical (at 25 _C)
P area

O area

IM3 area

IM4 area

Total

Digital inputs with process image
Digital inputs without process image
or analog inputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Digital outputs with process image
Digital outputs without process image
or analog outputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Flags

2048

Timers

256

Counters

256

Size of user memory

max. of 64 x 210 words, EPROM or RAM

DB RAM

46 x 210 bytes

Transmission rate of serial PG interface

9600 bps

Program blocks PB

256

Sequence blocks SB

256

Function blocks FB

256

Function blocks FX

256

Data blocks DB

256, of which 253 are freely available

Data blocks DX

256, of which 253 are freely available

Organization blocks OB

OB 1 to 39 (interfaces for operating system)

Integrated special function Organization
blocks OB

See Pocket Guide

Dimensions (w x h x d)

40.64 x 233.4 x 160 mm

Weight

Approx. 1 kg

5-70

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.7

CPU 922
This section contains the hardware description and technical specifications of
the CPU 922 (also known as the R processor).
Details on programming can be found in the CPU 922 Programming Guide.

5.7.1

Technical Description

Application

You can use the CPU 922 in single and multiprocessor operation in the
S5-135U/155U CC (see Chapter 6). Up to four CPUs can be used.
The CPU 922 is particularly suitable for word processing (closed-loop
control and arithmetic calculation). Binary signal processing is also possible.
The following program processing levels are possible:
Cyclic
Time-controlled (1 timebase)
Interrupt-driven (hardware interrupt).
The programming language is STEP 5.

Design

The module is designed as a plug-in PCB of double Eurocard format. The
module provides the connection to the S5 bus via two backplane connectors.
The front plate width is 1 1/3 standard plug-in stations.

System Manual
C79000-G8576-C199-06

5-71

CPUs, Memory Cards, Memory Submodules, Interface Submodules

User Memory

You require a user memory submodule (RAM or EPROM) for storage of your
program. You can store up to 64 x 210 bytes of code and data blocks here.
For data blocks, the CPU 922 additionally has an integrated DB RAM of
22 x 210 bytes.
Note
The DB RAM is only loaded with DB/DX blocks when the RAM submodule
is full or an EPROM submodule is inserted.

A description of the memory submodules can be found in Sections 5.9 and
5.10; order numbers are given in the ordering information.

Process Interrupt
Processing

There is an interrupt line (IR) in the S5-135U/155U PLC for each CPU. It
can be used when the reaction to one or more events must occur with higher
priority than the reaction to other events.
To process an interrupt, cyclic program processing is interrupted and the
program stored in OB 2 is inserted. Refer to the CPU 922 Programming
Guide for further details.
This interrupt-driven program processing is only possible using an
interrupt-capable digital input module (e.g. 6ES5 432-...) or a suitably
operating CP/IP module.

5-72

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.7.2

Installation and Startup

Removing and
Inserting the
Module

!
Insertion

Caution
Switch off the power supply before removing or inserting the module.

Proceed as follows to insert the CPU in the central controller:
Step

Removal

1

Release the upper locking bar of the central controller.

2

Select the correct slot (based on the labelling of the locking bar).
Insert the CPUs in the S5-135U/155U from slot 11.

3

Push the module evenly into the guide rail.

4

Secure the upper locking bar.

Proceed as follows to remove the CPU:
Step

System Manual
C79000-G8576-C199-06

Action

Action

1

Release the upper locking bar of the central controller.

2

Use the grips and gentle upward and downward motion to pull the
CPU forwards out of the CC.

5-73

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Controls and
Indicators

The controls and indicators are arranged on the front plate of the CPU
module:

Grip

Receptacle for
User Memory Submodule

RUN

Mode Switch
STOP

LED (green)
RUN
STOP
RÜCKSETZEN
RESET

LED (red)

Momentary-Contact Mode Switch
URLÖSCHEN
OVERALL
RESET

Fault Indicator LEDs (red)
QVZ

SIEMENS

6ES5922-3UA11

ADF
ZYK
BASP

Order Number and Version

PG Interface, 15-Pin

Grip

Figure 5-9

5-74

Front Plate of the CPU 922

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Mode Switch

The mode switch has two settings:

RUN

In the RUN setting, the CPU 922 processes the user program when the green
RUN LED is lit.

STOP

The CPU 922 goes to the stop state when you switch from RUN to STOP.
The red STOP LED then lights up.

MomentaryContact Mode
Switch

You can initiate the Overall Reset, Reset and Restart functions with the
momentary-contact mode switch:

OVERALL RESET

Momentary-contact switch down
With an overall reset, all RAM areas are erased and initialized (both on the
CPU and on a RAM submodule).

Reset

Momentary-contact switch up
During a reset, all flags, timers, counters and the process image will be
erased. OB 20 will be invoked. Processing of the user program will start from
the beginning again.

Restart

Momentary-contact switch at midpoint
With a restart, processing of the user program will continue from the point of
interruption. The statuses of flags, timers, counters and the process image are
retained during stoppage of the CPU.

System Manual
C79000-G8576-C199-06

5-75

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Status Indicators

5-76

RUN
LED

STOP
LED

Status

on

off

The CPU is in the RUN state.

off

on

The CPU is in the STOP state. After a stop
request by switch or PG function, the STOP LED
is continuously lit because the transition to the
STOP state was requested by the user or, in
multiprocessor operation, by another CPU, and
was not caused by the CPU itself.

off

off

The CPU is in the INITIAL START or program
check state.

off

slow
flashing

The CPU is in the STOP state. The CPU has
caused a transition to the STOP state (possibly
also for the other CPUs). If you set the mode
switch to STOP, the flashing LED becomes
continuously lit.

off

rapid
flashing

The CPU is in the STOP state. An overall reset
has been requested. This request can be initiated
by the CPU itself or by operator action.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

LEDs for Fault
Indication and
Signaling
QVZ LED
on

During direct access or process image update, a module
addressed by the program no longer acknowledges although
either it has acknowledged in single processor operation
upon reset of the CPU 922 in the area of the process
image (IB 0 to 127, QB 0 to 127) and has been entered as
present in the “9th track” (see Programming Guide,
CPU 922),
or it has
h been
b
entered
t d iin DB 1 ((address
dd
li
list)
t) iin
multiprocessor or single-processor operation and has been
recognized as present during the reset.
Possible causes
Module failure.
Module was pulled out during operation, in the stop state
or in the Off state without a subsequent reset.

ADF LED
on

The user program has referenced an I/O address under which
no module is inserted.

ZYK LED
on

The maximum cycle time has been exceeded.

BASP LED
on

Command output is inhibited and the digital outputs will be
directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the
CPU 922 Programming Guide.

System Manual
C79000-G8576-C199-06

5-77

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The modules must be inserted at the correct slots in the central controller.
The backup battery must be fitted and in order for the CPU to start.

Overall Reset
Step

1)

Action

Result

1

Set the mode switch to STOP

2

Switch the system voltage on. The following LEDs must light
up on the CPU:
– Red STOP LED (flashing
rapidly)
– Red BASP LED

3

Hold the MC1) switch in the
OVERALL RESET setting
and simultaneously set the
mode switch from STOP to
RUN.

The red STOP LED is now
permanently lit.

MC: Momentary-contact

Reset
Step

Restart

Action

1

Set the mode switch to STOP.

2

Hold the MC switch in the
RESET setting and
simultaneously set the mode
switch from STOP to RUN.

Result

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

The CPU is now in the RUN state
but still has no user program.

You can also carry out a manual restart of the CPU 922 with the mode
switch. The CPU 922 Programming Guide will indicate when a manual
restart is permissible.
Step
1

Action

Result

Set the mode switch from
STOP to RUN.

–
–
–

Red STOP LED goes off
Green RUN LED lights up
Red BASP LED goes off

For maintenance purposes or in the event of a fault, this startup without user
program in single-processor operation can serve to establish whether the CPU
is operating without errors.

5-78

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.7.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:

S UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972

S CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection

IP 00

Climatic ambient conditions

See Technical Specifications of the S5-135U/155U CC

Mechanical ambient conditions

See Technical Specifications of the S5-135U/155U CC

Noise immunity, electromagnetic
compatibility (EMC)

See Technical Specifications of the S5-135U/155U CC

Supply voltage

5V$5%

Current consumption at 5 V

2.2 A typical

Backup voltage

3.4 V

Backup current without user RAM
submodule

20 mA typical (at 25 _C)
P area

O area

IM3 area

IM4 area

Total

Digital inputs with process image
Digital inputs without process image
or analog inputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Digital outputs with process image
Digital outputs without process image
or analog outputs

1024 max.
1024 max.
64 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

–
2048 max.
128 max.

1024 max.
7168 max.
448 max.

Flags

2048

Timers

128

Counters

128

Size of user memory

max. of 64 x 210 words, EPROM or RAM

DB RAM

22 x 210 bytes

Transmission rate of serial PG interface

9600 bps

Program blocks PB

256

Sequence blocks SB

256

Function blocks FB

256

Function blocks FX

256

Data blocks DB

256, of which 253 are freely available

Data blocks DX

256, of which 253 are freely available

Organization blocks OB

OB 1 to 39 (interfaces for operating system)

Integrated special function
Organization blocks OB

See Pocket Guide

Dimensions (w x h x d)

20.32 x 233.4 x 160 mm

Weight

Approx. 0.5 kg

System Manual
C79000-G8576-C199-06

5-79

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.8

374 Flash EPROM Cards
This section provides a summary
of the use of the 374 flash EPROM cards (known as the 374 memory
cards in the following) in the CPU 948, CPU 928B-3UB21 and
CPU 928-3UA21
and of the technical specifications.

5.8.1

Technical Description
The 374 memory card serves as a storage medium for user programs and user
data. It contains electrically erasable flash EPROMs.
The 374 memory card is available in the following capacities:
256 Kbytes
512 Kbytes
1024 Kbytes
2048 Kbytes
4096 Kbytes

Ordering
Information

5.8.2

The order numbers for the SIMATIC S5 memory cards can be found in the
ordering information.

Notes on Operation

Programming a
Memory Card

You can program and erase the 374 memory card off-line on the SIMATIC S5
programmers. The link to the PG is provided by a special connector or
programming adapter, into which the memory card is inserted. A description
of EPROM programming can be found in the STEP 5 manual.

Inserting and
Removing a
Memory Card

Memory cards can be inserted and removed at any time, even whilst the CPU
is running, as long as they are not being accessed (see the CPU 948
Programming Guide).

Loading Data

The contents of the memory cards are only copied automatically into the
internal RAM of the CPU upon overall reset of the CPU.

Erasing a Memory
Card

Memory cards are electrically erasable.

5-80

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.8.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533

System Manual
C79000-G8576-C199-06

Supply voltage during a read operation

+5 V $ 5 %

Current consumption during a read
operation (at 5 V)

200 mA max.

Access time tACC

200 ns

Operating temperature

0 to 55 °C

Storage temperature

– 40 °C to 70 °C

Relative humidity

Up to 95 % at 25 °C, no condensation

Number of programming cycles

10,000

Dimensions (H x D x W)

54 x 85 x 5 mm

Weight

Approx. 50 g

5-81

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.9

376 Memory Submodules
This section provides a summary
of the use of the 376 memory submodules in the 928B (up to -3UB12),
928 (up to -3UA12) and 922 CPUs,
and of the technical specifications.
Note
You cannot use the memory submodule 376 for the CPU 928B from version
3UB21, nor for the CPU 928 from version 3UA21.

5.9.1

Technical Description
The 376 memory submodules serve as a storage medium for user programs
and user data. They contain UV-erasable CMOS EPROMs. 376 memory
submodules are available in the following capacities:
16 Kbytes
32 Kbytes
64 Kbytes

Ordering
Information

5.9.2

The order numbers for the SIMATIC S5 memory submodules can be found in
the ordering information.

Notes on Operation

Programming
the Memory
Submodules

!

Inserting a
Memory
Submodule

You program the 376 memory submodules off-line on the SIMATIC S5
programmers. The link to the PG is provided by the EPROM programming
interface integrated in the PG.
A description of EPROM programming can be found in the STEP 5 manual.
Use an adhesive label to cover the EPROM window (erasing window) after
programming.
Caution
CMOS memory submodules are destroyed by programming with the wrong
programming number. A list of valid order numbers (MLFBs) and
programming numbers can be found in your STEP 5 software in the EPROM
package.

Before inserting a 376 memory submodule in the module receptacle of the
CPU,
set the CPU mode switch to STOP
and switch off the PLC (Power Off).

Erasing a Memory
Submodule

5-82

376 memory submodules can be erased with a UV eraser. Before erasing,
remove the plastic cover and the adhesive label from the erasing window.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.9.3

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533

System Manual
C79000-G8576-C199-06

Supply voltage during a read operation

+5 V " 5 %

Current consumption during a read
operation (at 5 V)

200 mA max.

Access time tACC

250 ns

Operating temperature

0 to 55 °C

Storage temperature

– 40 °C to 70 °C

Relative humidity

Up to 95 % at 25 °C, no condensation

Number of programming cycles

10,000

Dimensions (H x D x W)

54 x 58 x 14 mm

Weight

Approx. 40 g

5-83

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.10 377 Memory Submodules
This section provides a summary
of the use of the 377 memory submodules in the 928B (up to -3UB12),
928 (up to -3UA12) and 922 CPUs,
and of the technical specifications.
Note
You cannot use the memory submodule 377 for the CPU 928B from version
3UB21, nor for the CPU 928 from version 3UA21.

5.10.1

Technical Description
377 memory submodules (RAM submodules) are available with or without
battery backup in the following capacities:
Without Battery Backup

With Battery Backup

16 Kbytes

64 Kbytes

32 Kbytes
64 Kbytes
The order numbers for the 377 memory submodules can be found in the
ordering information.

5.10.2

Notes on Operation

Loading RAM
Submodules

5-84

377 memory submodules are loaded online (from the PG) in the CPU. A
description of loading the individual submodules or the entire program can
be found in the STEP 5 manual.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.10.3

RAM Submodules with Battery Backup
RAM submodules with battery backup are used when the contents of the
memory submodules must be retained even outside the CPU. You can then
remove the battery-backed 377 memory submodule from the CPU without
loss of data. An integral battery protects the submodule from data loss, and
ensures that the data will be retained until the RAM submodule is used again.
Note
The RAM submodule with battery backup is not a substitute for an EPROM
submodule. The contents can be overwritten by a STEP 5 program. The
battery can discharge if the submodule is at standby for a long time. This can
result in the loss of data.

To protect the battery, the 377 memory submodule has a cover on both sides.
The button cell battery with terminal lugs is secured on the submodule with
screws on two holders. When the grip is swivelled in, you can see the battery
fault LED.

Operational States

There are three different operational states for the RAM submodule with
battery backup:

Normal Operation

In this state
the battery-backed RAM submodule is in the CPU;
the programmable controller (PLC) is switched on (Power On);
and neither the backup battery of the PLC nor the battery of the RAM
submodule is supplying power.
Note
The RAM submodule must not be inserted or removed during the RUN state;
this can result in data corruption, loss of data or CPU malfunctions.

System Manual
C79000-G8576-C199-06

5-85

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Standby Operation

In this standby state of the unit
the battery-backed RAM submodule is in the CPU;
the PLC is switched off (Power Off);
the backup battery of the PLC is providing backup of the RAM
submodule;
the submodule battery is not supplying power.
Note
It is only possible to insert and remove the RAM submodule in this state
without data corruption.

If the backup battery in the PLC fails in this state, the submodule battery
provides backup of the RAM submodule. This prevents loss of data.

Submodule
Standby

In this standby state of the submodule
the RAM submodule has been removed from the CPU;
the submodule battery is providing backup of the RAM submodule;
the contents of the battery-backed RAM are retained.

Battery Monitoring
and Battery Fault

The battery of the battery-backed RAM submodule is monitored. When the
RAM submodule goes to normal operation (battery-backed RAM is in the
CPU, supply voltage of the PLC is switched on), the battery monitor on the
submodule detects the following faults:
Submodule battery is not present.
Submodule battery is faulty (voltage less than 2.6 V).
The red battery fault LED on the front of the submodule is continuously lit.
Note
A temporary voltage drop of the submodule battery in the standby state, e.g.
caused by storage below 0 oC or a battery change, is not detected by the
battery monitor if the voltage dip is corrected by plugging in the RAM
submodule and switching on the PLC. However, the voltage dip may have
led to a loss or corruption of RAM submodule data.

5-86

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Inserting or
Replacing the
Backup Battery

Before the RAM submodule with battery backup is started for the first time,
you must insert the battery provided. This is delivered separately to protect it
from premature discharge. Proceed according to the following steps:
Step

Action

1

Open the upper side of the cover by releasing the snap-on catch.
Grasp the cover within the clearance from the PCB and pull it up.

2

Insert the submodule battery and secure it with a screw on the left
and on the right. Ensure correct polarity (+/-).

3

Close the cover again.

Battery
M 2.5 Screw

Battery
Fault LED

Grip

Figure 5-10

!

Mounting Location for Backup Battery

Caution
Improper replacement of the battery can result in explosion hazard.
It should only be replaced by the same type or an equivalent one
recommended by the manufacturer. Used batteries should be disposed of
according to the manufacturer’s instructions.

System Manual
C79000-G8576-C199-06

5-87

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Proceed as follows to replace the submodule battery:
Step

Action

1

Open the upper side of the cover by releasing the snap-on catch.

2

Slacken the screws on the left and right of the battery.

3

Replace the submodule battery and secure the new battery with
screws, observing the polarity.

4

Close the cover again.

Using the RAM
Submodule with
Battery Backup

!

Caution
EPROM-battery-backed RAM submodules must not be programmed via the
EPROM interface of the PG, otherwise they can be destroyed.
Before inserting or removing the RAM submodule into or out of the CPU,
switch the PLC power supply off: this is to ensure that data of the RAM
submodule are not corrupted.

Inserting
Unprogrammed
Memory
Submodules

Initial situation:
The CPU is in the programmable controller.
The power supply of the PLC is switched off.
The mode switch of the CPU is at STOP.

Step

5-88

Action

1

First insert the battery in the RAM submodule.

2

Insert the RAM submodule in the CPU.

3

Switch the power supply of the programmable controller on.

4

Carry out an overall reset.

5

Connect your programmer (PG) to the CPU.

6

When the user program has been loaded into the RAM
submodule, reset the CPU.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Inserting
Programmed
Memory
Submodules

Since the contents of the inserted RAM submodule are erased with each
overall reset, proceed as follows when using programmed RAM submodules
whose contents are not to be erased:
Initial situation:
The CPU is in the programmable controller.
The power supply of the PLC is switched off.
The mode switch of the CPU is at STOP.
Step

Removing Memory
Submodules

Action

1

Insert another, unprogrammed memory submodule in the CPU.

2

Switch the power supply on.

3

Carry out an overall reset.

4

Switch the power supply off.

5

Remove the unprogrammed memory submodule.

6

Insert the programmed memory submodule.

7

Switch the power supply on.

8

Carry out a reset.

Before removing the RAM submodule, check whether the battery is still in
order: if the battery fault LED on the RAM submodule is lit whilst the PLC
supply voltage is switched on, the contents of the RAM submodule will be
lost when it is removed.
Initial situation:
The CPU is in the RUN state.
Step

System Manual
C79000-G8576-C199-06

Action

1

Set the CPU mode switch to STOP.

2

Switch the power supply off.

3

Remove the memory submodule.

5-89

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.10.4

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533

All 377 Memory
Submodules
Supply voltage

+5 V  5 %

Operating temperature

0 to 55 °C

Storage temperature

– 40 °C to 70 °C

Relative humidity

Up to 95 % at 25 °C, no
condensation

Number of programming cycles

10,000

Dimensions (H x D x W)

54 x 58 x 14 mm

Weight

Approx. 40 g / 60 g

Submodules
without Battery
Backup

5-90

Current consumption
(at 5 V)

100 mA max. (16/64 Kbytes)
200 mA max. (32 Kbytes)

Backup current/standby

Approx. 20 mA typ. (16/64 Kbytes)
Approx. 40 mA typ. (32 Kbytes)

Backup voltage/
UCMOS

2.7 V to 3.6 V

Access time tACC

150 ns (16/64 Kbytes)
200 ns (32 Kbytes)

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Submodules with
Battery Backup

System Manual
C79000-G8576-C199-06

Current consumption
(at 5 V)

140 mA max.

Backup current

13 mA typ.

Backup voltage/
UCMOS

2.7 V to 3.6 V

Submodule battery

Lithium button cell 3 V/200 mAh Type CR 2430
(LF-1/2W) from VARTA

Backup time

1 year min. at 25 oC

Access time tACC

150 ns

5-91

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11 Interface Submodules
The second serial interface of the CPU 928B can be optionally used as:
A PG interface (for PG and operator panels)
An interface for the RK 512 computer link
An interface for data transmission with procedures 3964/3964R
An interface for data transmission with the “open driver”
An interface for data transmission via the SINEC L1 bus (from Version
6ES5 928-3UB12)

The second serial interface of the CPU 948 can be used as:
A PG interface (for PG and operator panels)

Using the Interface
Submodules

5-92

To use the second interface as ...

... you require ...

a PG interface

the PG submodule

an interface for data transmission
with
RK 512 computer link,
procedures 3964/3964R
or “open driver”

the V.24 (RS 232C)
or TTY
or RS 422 A/485 submodule
(only in RS 422 A mode)

an interface for data transmission
via the SINEC L1 bus

the SINEC L1 submodule

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11.1

Installing and Removing the Interface Submodules
To use an interface submodule, you must first install it in the CPU (outside
the central controller).

!

Installation

Caution
Switch off the power supply of the programmable controller before
removing the CPU.

Install your interface submodule in the following steps:
Step
1

Action
Check the jumper settings of your interface submodule:
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule

See
See
See
See
See

Section
Section
Section
Section
Section

5.11.2
5.11.3
5.11.4
5.11.5
5.11.6.

When the interface submodule is delivered, the jumpers are
already set so that you can usually fit it immediately.

System Manual
C79000-G8576-C199-06

2

Switch off the power supply of your PLC.

3

Remove the CPU.

4

Remove both screws on the submodule slot.

5

Remove the coverplate.

6

Insert the interface submodule through the front plate into the
plug-in connector (components in the same direction as the CPU).

7

Secure the submodule with the two screws (see step 4).

8

Insert the CPU in the central rack.

9

Switch on the power supply of your PLC again.

5-93

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Removal

Remove your interface submodule in the following steps:
Step

Action

1

Switch off the power supply of your PLC.

2

Remove the CPU from the central controller.

3

Slacken the two locking screws of the submodule and pull it out
of the receptacle.

4

Fit another submodule (as already described) or close the
receptacle with its cover. Use the fixing screws of the submodule.

5

Insert the CPU in the central controller.

6

Switch the power supply of your PLC on again.

Note
Since the interface module is secured to the CPU with screws, interference
pulses are given a path to ground via the shield of the CPU.

5-94

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11.2

PG Submodule
By means of the PG submodule, you can use the second interface of the CPU
as the PG interface and equally privileged with the first interface.

Application

Circuitry

The PG submodule can be inserted in the following CPUs:
Interface Submodule

For Use With

PG submodule

CPU 928B
CPU 948

The PG submodule is equipped with a transmitter and a receiver for 20 mA
current loop signals. The loop current is always fed in from the PG. The
following figure shows the circuitry for current loop signals of the standard
cable:

+

+

–

–
–

Receiver

Transmitter
–

+
–

Transmitter
+
CPU with
PG Module
Current Direction Arrows

+
+
Receiver
–
PG

Figure 5-11

Data Transmission
Rate

System Manual
C79000-G8576-C199-06

PG Submodule: Loop Current Direction

The rate for data transmission via the PG interface is always 9600 bps.

5-95

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Pin Assignments
of the PG
Submodule

Given in the following table are the pin assignments of the 15-pin
subminiature D-type connector in the front plate of the PG submodule:

Pin

15

8

Current Remarks
Direction

1

Housing/GND/GNDext

2

– RxD

3

VPG + 5 V_

4

+ 24 V from bus

5

0 V GND/GNDint

6

+ TxD

²

7

– TxD

³

8

Housing/GND/GNDext

9

+ RxD

²

10

24 V GND

²

Current return

11

20 mA

³

Current source, transmitter

12

GND/GNDint

13

20 mA

³

Current source, receiver

14

VPG + 5 V_

15

0 V GND/GNDint

9
1

Designation

³

²: From partner to CPU
³: From CPU to partner

5-96

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Jumper Settings
on the PG
Submodule

When the PG submodule is delivered, the jumpers are set as shown in the
following figure. As a rule, therefore, you can use the PG submodule
immediately.

Front Connector
15-Pin Sub. D-Type

J1
3
2
1

Backplane Connector

Figure 5-12

PG Submodule: Jumper Settings when Delivered

J1 is set to select whether the PG submodule is to be operated in the
CPU 928B/CPU 948 or in the CPU 945:
1
J1

System Manual
C79000-G8576-C199-06

2

3
Operation in CPU 928B/CPU 948
Operation in CPU 945

5-97

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Standard
Connecting Cable
for the PB
Submodule

Standard cables for connecting the PG submodule in the CPU to the PG are
available from Siemens in various lengths, up to 1000 m.
Order numbers and lengths can be found in the ordering information.

Connecting cable: CPU - PG

CPU SI1 or
SI2 with PG Submodule

Receiver

Transmitter

PG 675/685 or
Adapter to PG 7xx

9

+ RxD

+ 20 mA

22

2

– RxD

+ TxD

10

– TxD

12

– 20 mA

23

+ 20 mA

20

+ RxD

6
8

6

+ TxD

– RxD

7

– TxD

– 20 mA

8
1

21

–12V
+12V

–12V

24
Shield

25

K1

17

K2

4

K3

3
2

5-98

Transmitter

Receiver

Housing, GND

Figure 5-13

+12V

Housing, GND

Transmission
Rate Setting

PG Submodule: Standard Connecting Cable

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11.3

V.24 Submodule
The V.24 submodule is used with the RK 512 computer link, data
transmission with procedures 3964/3964R, data transmission with the “open
driver.”

Application

Circuitry

The V.24 submodule can be inserted in the following CPU:
Interface Submodule...

For use With ...

V.24 submodule

CPU 928B
CPU 948

The following figure shows the circuitry for the V.24 interface (transmit and
receive lines):

Device 1

Device 2

GND

GND

TxD

TxD

RxD

RxD

Shield

Figure 5-14

Shield

V.24 Interface

Apart from the transmit and receive lines, the V.24 submodule has a number
of control and signaling lines to CCITT Recommendation V.24/V.28.
However, these control signals are not needed and not used for the standard
procedures of communication types RK 512, 3964/3964R and “open driver.”
(Exception: RTS/CTS with the “open driver”).
The following applies to V.24 signals:
Logic 0 is represented by a voltage

Uw +3V

Logic 1 is represented by a voltage

Uv –3V

If you fabricate the connecting cables yourself, note that unused inputs at the
partner station may have to be connected to quiescent potential. Further
details can be found in the appropriate manuals and in CCITT
Recommendations V.24/V.28.

System Manual
C79000-G8576-C199-06

5-99

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Data Transmission
Rate

A maximum of 19200 bps is permissible for data transmission with the V.24
submodule.

Pin Assignments
of the V.24
Submodule

The following table shows the pin assignments of the 25-pin subminiature
D-type connector in the front plate of the V.24 submodule:
Pin

13

Des. to
DIN
66020

Des. to
CCITT
V.24

1

Int. Abbre- Input/
viation
Output

Remarks

Shield

25

14
1

2

D1

103

TxD

Output

3

D2

104

RxD

Input

4

S2

105

RTS

Output

5

M2

106

CTS

Input

6

M1

107

DSR

Input

7

E2

102

GND

8

M5

109

DCD

18

PS3

141

20

S1.2

108.2

DTR

Output

22

M2

125

RI

Input

23

S4

111

Output

25

PM1

142

Input

Input
Output

Not supported

Not supported

The signal numbering complies with DIN 66020 (V.24/RS 232C); the signal
designations are the abbreviations used internationally (RS 232C).

5-100

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Jumper Settings of
the V.24
Submodule

When the V.24 submodule is delivered, the jumpers are set as shown in the
following figure. As a rule, you can therefore use the V.24 submodule
immediately.

Front Connector
25-Pin Sub. D-Type

Br9
Br6
J3
Br5
J4
J2
Br8
J1

Br7

Backplane Connector

Figure 5-15

V.24 Submodule: Jumper Settings when Delivered

You can change over the polarity of the transmit and receive data with
jumpers J3 and J5.
1

System Manual
C79000-G8576-C199-06

2

3

J3

Transmit data in normal polarity
Transmit data negated

J5

Receive data in normal polarity
Received data negated

5-101

CPUs, Memory Cards, Memory Submodules, Interface Submodules

With jumper J6, you can set all V.24 receivers so that you only require
positive-going signals (positive voltage region).
1

2

3
All received signals must be at
V.24 signal level.
All received signals can be in the
positive voltage region.

J6

With the submodule 0AA23, bridge 6 has no function; all signals can lie in
the positive range (corresponds to bridge setting 2-3).
With jumper J9, CTS can be set permanently to quiescent potential, i.e.
switched through from the front connector.
1

2

3

J9

Standard Connecting Cables of the
V.24 Submodule

CTS at quiescent potential CTS at
pin 5

Standard cables for connecting the V.24 submodule of the CPU to the partner
station are available from Siemens in various lengths, up to16 m.
Order numbers and lengths can be found in the ordering information.
Connecting cable for CPU, CP 524, CP 525, CP 544
CPU, CP524/525, CP544

CPU, CP524/525, CP544
Receiver

Transmitter
3

RxD

TxD

2

2

TxD

RxD

3

Transmitter

Receiver

7

7
Housing, GND

Figure 5-16

5-102

1

Shield

1

Housing, GND

V.24 Submodule: Connecting Cable for CPU, CP 524, CP 525, CP 544

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Connecting cable: CPU - N10 modem

CPU

Modem N10

Receiver

Transmitter

3

RxD

TxD

3

2

TxD

RxD

2

Transmitter

Receiver
7

7
1

1

Shield

Housing,GND

Figure 5-17

RTS

4

CTS

5

V.24 Submodule: Connecting Cable for CPU - N10 Modem

System Manual
C79000-G8576-C199-06

5-103

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Connecting cable: CPU - DR 210/211, DR 230/231
You can use this connecting cable both with the V.24 and with the TTY
submodule. Ensure that you have the same type of interface in the CPU and
in the printer.

CPU

TTY Assignments

DR 210/211, DR 230/231
13

21

14

18

10

10

19

9

5

CTS

Busy

TTY Assignments

25

Receiver

Transmitter
3

RxD

TxD

2

2

TxD

RxD

3

Transmitter

Receiver
7
1

7
Shield

1

Housing, GND

Figure 5-18

5-104

Housing

V.24 Submodule: Connecting Cable for CPU - DR 210/211, DR 230/231

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Wiring of a connecting cable for RTS/CTS flow control
CPU

CPU
Receiver

Transmitter
3

RxD

2

TxD

TxD

2

RxD

3

Transmitter

Receiver

RTS

4

4

RTS

CTS

5

5

CTS

7

7

1

Shield

1

Housing, GND

Figure 5-19

Housing, GND

Example of a Connecting Cable: CPU - CPU for RTS/CTS Flow Control

System Manual
C79000-G8576-C199-06

5-105

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11.4

TTY Submodule
The TTY submodule is for use with the RK 512 computer link, data
transmission with procedures 3964/3964R, data transmission with the “open
driver.”
The TTY submodule complies with DIN 66 258, Part 1.

Application

Circuitry

The TTY submodule can be inserted in the following CPU:
Interface Submodule ...

For Use With ...

TTY submodule

CPU 928B
CPU 948

The TTY submodule is equipped with a transmitter and receiver for 20 mA
current loop signals. Shown in the following figure is the typical circuitry for
current loop signals.

–

+

+
+

–
–

–

+

Transmitter

Receiver

+
–
Receiver

Transmitter
+

–
Current Direction Arrows

Figure 5-20

TTY Submodule: Loop Current Direction

The loop current can be fed in both by the TTY submodule and by the
partner station. Only the side supplying the current is non-floating.

!

5-106

Caution
With longer line lengths, you should arrange your line so that the transmitter
always supplies the current.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

The TTY submodule feeds in the current (20 mA) via jumpers in the
connector of the standard connecting cable. The 24 V required for generation
of loop current is taken from the power supply of the PLC. In the quiescent
state, with a correct loop current connection, there should be a flow of 20 mA
(= logic 1). When the current is interrupted there is a logic 0.
The following applies to the TTY signals:
Logic 0 is represented by: no current
Logic 1 is represented by: current (20 mA)

Data Transmission
Rate

A maximum of 9600 bps is permissible for data transmission with the TTY
submodule.

Pin Assignments
of the TTY
Submodule

Shown in the figure are the pin assignments of the 25-pin subminiature
D-type connector in the front plate of the TTY submodule:
Pin

13
25

14
1

Designation

Current
direction

Remarks

1

Shield

9

24 V
external

10

+ TxD

²

12

+ 20 mA

³

13

+ RxD

²

14

– RxD

³

16

+ 20 mA

³

19

– TxD

³

21

– 20 mA

²

Current return

24

– 20 mA

²

Current return

This connection is changed over between
24 V internal and 24 V external with
jumper J3 (see next page).

Current source, transmitter

Current source, receiver

² : Input
³ : Output

System Manual
C79000-G8576-C199-06

5-107

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Jumper Settings
on the TTY
Submodule

When the TTY submodule is delivered, the jumpers are set as shown in the
following figure. As a rule, therefore, you can use the TTY submodule
immediately.

Front Connector
25-Pin Sub. D-Type

J3
3

2

1

J4

J2

J1
1
2
3

Backplane Connector

Figure 5-21

TTY Submodule: Jumper Settings when Delivered

The polarity of the transmit and receive data is changed over with jumpers J1
and J2:
1

2

3

J1

Transmit data negated
Transmit data in normal polarity

J2

Receive data in normal polarity
Receive data negated

The 24 V source voltage for generation of the loop current can be allocated
with jumper J3:
1
J3

5-108

2

3
24 V will be applied from Pin 9 of
the sub. D connector
24 V will be applied from the
backplane connector (internally)

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Standard Connecting Cables for the
TTY Submodule

Standard cables for connecting the TTY submodule in the CPU to the partner
station are available from Siemens in various lengths, up to 1000 m.
Order numbers and lengths can be found in the ordering information.
Connecting cable for CPU, CP 524, CP 525, CP 544
CPU, CP 524/525, CP544

CPU, CP 524/525, CP 544
13

+RxD

–TxD

19

14

–RxD

+TxD

10

21

–20mA

+20mA

12

12

+20mA

–20mA

21

10

+TxD

–RxD

14

19

–TxD

+RxD

13

Receiver

+24V

+24V

Transmitter

Housing, GND

Figure 5-22

1

Transmitter

Shield

1

Receiver

Housing, GND

TTY Submodule: Connecting cable for CPU, CP 524, CP 525, CP 544

System Manual
C79000-G8576-C199-06

5-109

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Connecting Cable: CPU - IM 512
To generate loop current, the IM 512 must be supplied with 24 V at the
subminiature D-type connector in the front plate.

IM 512

CPU
13

+ RxD

– TxD

14

14

– RxD

+ TxD

2

+ 20mA

5

– 20mA

17

+ 20mA

6

– 20mA

18

Receiver

Transmitter

10

+ TxD

– RxD

19

– TxD

+ RxD

+ 24 V

+ 24 V

15

Transmitter

Receiver
1

3

Shield

Housing, GND

Housing

2

2

23
11
24
12

2

Figure 5-23

5-110

0

Device ID

25
13

TTY Submodule: Connecting Cable CPU - IM 512

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Connecting cable: CPU - DR 210/211, DR 230/231
You can use this connecting cable with both the TTY and the V.24
submodule. Ensure that you have the same type of interface in the CPU and
in the printer.
CPU

Receiver

DR 210/211, DR 230/231
13

+RxD

+20mA

21

14

–RxD

+TxD

18

+24V

Transmitter
10
Transmitter
19

+TxD

+20mA

10
+24V

–TxD

9

+RxD

Receiver

5

25

3

2

V.24 Assignments

V.24 Assignments
2

3

7

7

1

Shield

1

Housing,GND

Figure 5-24

Housing

TTY Submodule: Connecting Cable CPU - DR 210/211, DR 230/231

System Manual
C79000-G8576-C199-06

5-111

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11.5

RS422 A/485 Submodule
The RS422 A/485 submodule is for use exclusively in the RS422 A mode
with the RK 512 computer link, data transmission with procedures
3964/3964R, data transmission with the “open driver.”

Application

Circuitry

The RS422 A/485 submodule can be inserted in the following CPU:
Interface Submodule ...

For Use With ...

RS422 A/485 submodule

CPU 928B
CPU 948

With the above types of communication, the RS422 A/485 submodule can
only be used in full duplex operation implemented by hardware.
The electrical characteristics are governed by EIA Standard RS422 A
(CCITT Recommendation V.11).
Shown in the following figure is the circuitry for the interface (transmit and
receive lines):
Device 1

Device 2

GND

GND

T(A)

T(A)

T(B)

T(B)

R(A)

R(A)

R(B)

R(B)

Shield

Figure 5-25

Shield

RS422 A/485 Submodule: Full Duplex Operation

Apart from the transmit and receive lines, the RS422 A/485 submodule has a
number of control and signaling lines to CCITT Recommendation X.24 and
ISO 8481. In association with the above types of communication, however,
these control and message signals are not required and need therefore not be
wired. The RS422 A/485 is a differential voltage interface and therefore
exhibits higher rejection of interference than a TTY or V.24 interface.
The following applies to the signals to EIA Standard RS422 A (V.11):
Logic 0 (ON) corresponds to: VA > VB
Logic 1 (OFF) corresponds to: VA < VB
In the RS422 A/485 submodule, the interface signals are isolated from the
supply voltage of the PLC.

5-112

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Data Transmission
Rate

A maximum of 19200 bps is permissible for data transmission with the
RS422 A/485 submodule when used in a CPU.

Pin Assignments
of the RS422 A/485
Submodule

Shown in the following figure are the pin assignments of the 15-pin
subminiature D-type connector in the front plate of the RS422 A/485
submodule:
Pin

8
15

Des. to
CCITT V.24

Input/
Output

1

Shield

2

T(A)

Output

3

C(A)

Output

4

R(A)

Input/Output

5

I(A)

Input

6

S(A)

Input

7

B(A)

Output

8

GND

9

T(B)

Output

10

C(B)

Output

11

R(B)

Input/Output

12

I(B)

Input

13

S(B)

Input

14

B(B)

Output

15

X(B)

Input

Remarks

In full duplex operation, only data
can be received on this two-wire
line.

9
1

System Manual
C79000-G8576-C199-06

In full duplex operation, only data
can be received on this two-wire
line.

5-113

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Jumper Settings
on the
RS422 A/485
Submodule

When the submodule is delivered, the jumpers are set as shown in the
following figure. As a rule, therefore, you can use the RS 422 A/485
submodule immediately.

Front Connector

19

1

20

2

11

1

12

2

X3

X4

Figure 5-26

RS422-A/485 Submodule: Jumper Settings when Delivered

With the jumpers on the switch row X3 you can remove the preset for
recognizing a break state from the two-wire line R.
When delivered, the two-wire line R is preset with the jumpers 12-14 and 4-6
so that the break state can be recognized. Pin 4 (R(A)) of the front connector
lies above a resistance on +5 V. Pin 11 (R(B)) of the front connector lies
above a resistance on ground.

If you replug the jumpers on 10-12 and 6-8, the two-wire line R is preset as
follows: pin 4 (R(A)) of the front connector lies above a resistance on
ground. Pin 11 (R(B)) of the front connector lies above a resistance on +5 V.
The break state cannot be recognized.

5-114

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

If you unplug the jumpers 12-14 and 4-6, the two-wire line R is not preset
and the break state cannot be recognized clearly.

With the following jumper setting you can switch over the data direction on
the two-wire line R:

Jumper 16-18: setting for full duplex operation. Data can only be received
on the two-wire line R (default).
Jumper 18-20: setting for half duplex operation. Data can be transmitted or
received on the two-wire line R (special driver required).
With the following jumper setting you can switch the two-wire line B as an
input or an output.

Jumper 17-19: two-wire line B is switched as an output. The line X(B) can
be used as an input. X(A) is connected to ground (default).
Jumper 15-17: two-wire line B is switched as an input. The line X(B) cannot
be used.
With the following jumper setting you can either place the signal /PS3 or the
internal transmitting frequency (TxCint) on the two-wire line B. The
two-wire line B must be switched as an output.

Jumper 2-4: the signal /PS3 can be transmitted via the two-wire line B
(default).
Jumper 4-6: the internal transmitting frequency TxCint can be transmitted
via the two-wire line B.

System Manual
C79000-G8576-C199-06

5-115

CPUs, Memory Cards, Memory Submodules, Interface Submodules

With the following jumper setting you can use the frequency transmitted via
the two-wire line S as the receive frequency.

Jumper 7-9 removed: frequency on input S is not used as the receive
frequency (default).
Jumper 7-9 plugged: frequency on input S is used as the receive frequency.
With the following jumper setting you can switch the transmit and receive
frequencies.

Jumpers 8-10, 1-3: the internal transmit frequency (TxCint) is used as the
transmit and receive frequency (default).
Jumpers 10-12, 1-3: the internal transmit frequency (TxCint) is used as the
transmit frequency and the internal receive frequency (RxCint) is used as the
receive frequency.
Jumpers 8-10, 3-5: the frequency transmitted via the two-wire line S is used
as the transmit and receive frequency.
Jumpers 10-12, 3-5: the frequency transmitted via the two-wire line S is
used as the transmit frequency, the internal receive frequency (RxCint) is
used as the receive frequency. With the following jumper setting you can set
the submodule for synchronous transmission with frequency control
according to the DIN draft ISO 8481. The two-wire line B (identifier X to
ISO 8481) must be switched as an output.

Jumpers 1-3, 4-6, 7-9: the internal transmit frequency (TxCint) is used as
the transmit frequency. The internal transmit frequency is simultaneously
transmitted on the two-wire line B.

5-116

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Standard
Connecting Cables
for the
RS422-A/485
Submodule

Standard cables for connecting the RS422 A/485 submodule in the CPU
to the partner station are available from Siemens in various lengths, up to
1200 m.
The order numbers and lengths can be found in the ordering information.

Connecting cable for CPU, CP 524, CP 544

CPU, CP 524, CP 544

CPU, CP 524, CP 544
4

2

T(A)

R(A)

9

T(B)

R(B)

11

4

R(A)

T(A)

2

11

R(B)

T(B)

9

8

G

G

Transmitter

Receiver

Receiver
GND

Transmitter

1
Housing, GND

Figure 5-27

Shield

8

GND

1
Housing, GND

RS422-A/485 Submodule: Connecting Cable for CPU, CP 524, CP 544

System Manual
C79000-G8576-C199-06

5-117

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11.6

SINEC L1 Submodule
The SINEC L1 submodule is for use with data transmission via the
SINEC L1 bus.

Application

Circuitry

The SINEC L1 submodule can be inserted in the following CPU:
Interface Submodule ...

For Use With ...

SINEC L1 submodule

CPU 928B, from Version 6ES5 928-3UB12
CPU 948

The SINEC L1 submodule is equipped with a transmitter and a receiver for
20 mA current loop signals. Shown in the following figure is the circuitry for
the current loop signals:

+

+

–

–
–

–

+
–

Receiver

Transmitter

Transmitter
+
CPU with
SINEC L1
Submodule
Current Direction Arrows

Figure 5-28

Data Transmission
Rate

5-118

+
+
Receiver
–
Partner

SINEC L1 Submodule: Loop Current Direction

Data transmission via the SINEC L1 interface always takes place at
9600 bps.

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Pin Assignments
of the SINEC L1
Submodules

Shown in the following figure are the pin assignments of the 15-pin
subminiature D-type connector in the front plate of the SINEC L1
submodule:
Pin

15

8

9
1

Designation

Current Remarks
Direction

1

Housing/GND/GNDext

2

– RxD

3

VPG + 5 V_

4

+ 24 V from bus

5

24 V ground

6

+ TxD

²

7

– TxD

³

8

Housing/GND/GNDext

9

+ RxD

²

10

24 V ground

²

Current return

11

20 mA

³

Current source, transmitter

12

24 V ground

13

20 mA

³

Current source, receiver

14

VPG + 5 V_

15

24 V ground

³

²: from partner to CPU
³: from CPU to partner

System Manual
C79000-G8576-C199-06

5-119

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Jumper Settings
on the SINEC L1
Submodule

When the SINEC L1 submodule is delivered, the jumpers are set as shown in
the following figure. As a rule, therefore, you can use the SINEC L1
submodule immediately.

Front Connector
15-Pin Sub. D-Type

X8
X7

X10
X9
X6

3

2

1

Backplane Connector

Figure 5-29

BT 777 Bus
Terminal

SINEC L1 Submodule: Jumper Settings when Delivered

The connection to the SINEC L1 bus system is provided by the BT 777 bus
terminal. A detailed description of the bus terminal can be found in the
manual entitled “SINEC L1 Bus System,” 6ES5 998-7LA11).
The order number can be found in the ordering information.

5-120

System Manual
C79000-G8576-C199-06

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Connecting Cable
for Point-to-Point
Communication

If the CPU communicates as master in a point-to-point link with a slave, a
connecting cable can be used instead of the bus terminal.
Shown in the following figure is connecting cable for point-to-point
communication from the SINEC L1 submodule in the CPU to a partner.

Connecting cable: CPU - partner (point-to-point communication)

e.g. CPU 928B, 941...945
CPU 102, 103, AG 90U/95U

CPU 928B
9

+ RxD

– TxD

2

– RxD

+ TxD

6

15

M

+ 20 mA

11

11

+ 20 mA

7

Receiver

+ 24V

Transmitter

M

+ 24V
15

6

+ TxD

– RxD

2

7

– TxD

+ RxD

9

Transmitter

Housing, GND

Figure 5-30

Receiver
1

Shield

1

Housing, GND

SINEC L1 Submodule: Connecting Cable for Point-to-Point Communication via the SINEC L1
Submodule

System Manual
C79000-G8576-C199-06

5-121

CPUs, Memory Cards, Memory Submodules, Interface Submodules

5.11.7

Technical Specifications of the Interface Submodules
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
Degree of protection

IP 00

Ambient temperature
in operation
for transporation and storage

0 to +55 °C
– 40 to +70 °C

Relative humidity

95% max. at 25 °C, no condensation

Supply voltage

5V $ 5%
24V + 25%/– 17%

Transmission rate
PG submodule
V.24 submodule
TTY submodule
RS422-A/485 submodule
SINEC L1 submodule

9 600 bps fixed
19 200 bps max.
9600 bps max.
19 200 bps max.
(when submodule is used in a CPU)
9600 bps fixed

Front connector, female
PG, RS422 A/485, SINEC L1
submodule
V.24, TTY submodule

15-pin Cannon

Transmission cable

Shielded four-wire line (five-wire line for
RS422 A) with braided shield and metal
housing on connector, grounding required at
both ends.

25-pin Cannon

Line length
PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule

1000 m max.
16 m max.
1000 m max.
1200 m max.
1000 m max.

Current consumption at 5 V/24 V

5V

24 V

PG submodule
V.24 submodule
TTY submodule
RS422 A/485 submodule
SINEC L1 submodule

40 mA max.
0.2 A max.
0.1 A max.
0.5 A max.
170 mA max.

380 mA
–
60 mA
–
100 mA

Design
Dimensions (WxHxD)

16.3 mm x 60 mm x 102.7 mm

Weight
per interface submodule

5-122

Approx. 0.1 kg

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

6

This chapter explains how to install multiprocessor operation in the
S5-135U/155U programmable controller and start operations.
You will require the 923A or 923C coordinator module. The technical
functions of these modules are described.

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Description

Page

6.1

Introduction

6-2

6.2

Starting the Multiprocessor Operation

6-3

6.3

Coordinator Modes

6-13

6.4

923A Coordinator Module

6-15

6.5

923C Coordinator Module

6-18

6.6

Technical Specifications of the Coordinators

6-28

6-1

Multiprocessor Operation/Coordinators

6.1

Introduction
The S5-135U/155U is a member of the SIMATIC S5 family of programmable
(logic) controllers. The PLC can be used both in single and in multiprocessor
operation with up to four CPUs.

Slots Occupied

You can arbitrarily combine the CPUs in the central controller at the CPU
slots.
CPU

Slot Requirement

CPU 948/CPU 928B/CPU 928

2 slots

CPU 922

1 slot

In multiprocessor operation, each CPU processes its individual user program
independently of the other CPUs.
The common S5 bus serves for data interchange with I/O modules, CPs, IPs
and other CPUs. In multiprocessor operation, access of the CPUs to the S5
bus is controlled by a coordinator. The functioning of this module is
described in Sections 6.5 and 6.6.
For an explanation of data interchange between CPUs in multiprocessor
operation and the arrangement of your STEP 5 program, please consult the
Programming Guide for your CPU.

Coordinator

A coordinator is required in multiprocessor operation. The following are
available for the S5-135U/155U PLC:
923A coordinator (COR A)
and
923C coordinator (COR C).
The coordinator allocates to the CPUs the time divisions in which they can
access the S5 bus (bus enable time), and contains the global memory for data
interchange between the CPUs via communication flags. Additionally, the
COR C contains another memory with four pages for the “multiprocessor
communication” function as well as a serial PG interface with PG
multiplexer function (PG MUX).

6-2

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

6.2

Starting the Multiprocessor Operation
This section guides you through the installation and startup of multiprocessor
operation; the following is assumed:
You are familiar with the use and programming of individual modules in
single-processor operation. If this is not the case, please consult the
relevant chapters in this manual and in the appropriate Programming
Guides.
Note
As soon as a coordinator is inserted in the S5-135U/155U central controller,
all CPUs are automatically in multiprocessor operation irrespective of the
number of inserted CPUs. Even if the coordinator is only operated with one
CPU, the conditions for multiprocessor operation apply to this CPU (DB 1
required, DX 0 possibly required, etc.).

Procedure,
Overview

You can use up to four CPUs in the S5-135U/155U programmable controller.
The permissible slots are indicated in Chapter 4.
Startup can be subdivided into the following steps:
Step

System Manual
C79000-G8576-C199-06

Action

1

Set the number of CPUs (inserted from the left) on the
coordinator.

2

If you use communication flags on CPs: Mask out the
communication flag areas on the coordinator.

3

Insert the CPUs and the coordinator in the slots provided in the
central controller. The CC must be disconnected from system
voltage.

4

Switch on the system voltage and Power switch on the power
supply unit.

5

Execute an OVERALL RESET on all CPUs.

6

Load your STEP 5 user programs in all CPUs (including DB 1,
additionally DX 0 for the CPU 948).

7

Execute a RESET on all CPUs.

8

Set the mode switch of the coordinator from the STOP to RUN or
TEST setting.

6-3

Multiprocessor Operation/Coordinators

Setting the
Jumpers

Shown in Figures 6-1 and 6-2 are the locations of jumpers and switches on
the modules, at which the settings required for startup must be made.
Note
The settings of jumpers which are not described in the following text must
not be changed.

16

9

1

8

16

9

1

8

EP 2

EP 7
J2

X1

J1
Mode Switch
(RUN,STOP,TEST)

16

9

1

8

EP 43

16

9

1

8

EP 45

Figure 6-1

6-4

X2

EP 62

EP 63
16

9

16

9

1

8

1

8

Location of Jumpers on the 923A Coordinator (when Delivered)

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

S1

8

1

9

16

EP 60
(JR)

S2
S3

8

on off

1

EP 61
(JX)

X1
9

16

Mode Switch
(RUN,STOP,TEST)

X6
X5

X4

off on

8

1

9

16

EP 64
(JU)

8

1
EP 62
(JY)

9

X2

16

off on

8

1

9

16

EP 63
(JZ)
Front View
S1, S2, S3

Figure 6-2

Location of Jumper Sockets and Switches on the 923A Coordinator and Front View of Switches S1 to
S3 (when Delivered)

System Manual
C79000-G8576-C199-06

6-5

Multiprocessor Operation/Coordinators

The individual actions are explained in more detail in the following.

Step 1

Setting the number of occupied CPU slots on the coordinator:

923A Coordinator
Number of CPUs used

Jumper(s) at EP 62

2

7 - 10; 8 - 9

3

7 -10

4

8-9

1)

923C Coordinator
Coded by inserting only one DIL switch S1.4, S1.5 or S1.6 in the front
plate recess: (see Figure 6-2)
DIL S.

on

S1.1
S1.2
S1.3
S1.4
S1.5
S1.6
1)

Step 2

x
x
x
x
x
x

Effect
–
–
Enable test mode
No. of occupied CPU slots = 2 1)
No. of occupied CPU slots = 3
No. of occupied CPU slots = 4

Setting when delivered

Setting the communication flag areas:
IF ...
you use
communication flag
areas on CPs (please
consult the relevant
manuals),

6-6

off

THEN ...
you must mask out these areas (blocks) on the
coordinator without fail, to avoid duplicated
addressing of the communication memory.
The 256 communication flag bytes can be masked
out in groups of 32. You do this by removing
jumpers at coding socket EP 7 on Coordinator A
(see Figure 6-1 for location) or EP 60 on
Coordinator C (see Figure 6-2).

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

16

9

8

1

8

9

1

16

EP 60

EP 7

When the unit is delivered, all communication flag areas are activated
(see above):
On Coordinator A
On Coordinator C
Jumper
8-9
7 - 10
6 - 11
5 - 12
4 - 13
3 - 14
2 - 15
1 - 16

Examples

by jumpers at EP 7
by jumpers at EP 60

Comm. Flag Byte
0 to 31
32 to 63
64 to 95
96 to 127
128 to 159
160 to 191
192 to 223
224 to 255

Address
F200H to F21FH
F220H to F23FH
F240H to F25FH
F260H to F27FH
F280H to F29FH
F2A0H to F2BFH
F2C0H to F2DFH
F2E0H to F2FFH

Jumper inserted:

area activated (coordinator
acknowledges in this area)

Jumper not inserted:

area masked out (coordinator
does not acknowledge in this area)

You wish to mask out the four communication flag areas with the highest
addresses on COR A:
16

9

1

8

EP7

Address F200H to F27FH
Activated (Jumper Inserted)

Address F280H to F2FFH
Masked Out (Jumper Open)

Figure 6-3

System Manual
C79000-G8576-C199-06

Example of Addressing the Communication Memory on COR A

6-7

Multiprocessor Operation/Coordinators

You wish to mask out the four communication flag areas with the highest
addresses on COR C:

Address F200H to F27FH
Activated (Jumper Inserted)
Address F280H to F2FFH
Masked Out (Jumper Open)
8

1

9

16

EP 60

Figure 6-4

Step 3

Example of Addressing the Communication Memory on COR C

Inserting CPUs and coordinator in the central controller:
Precondition: The central controller is not yet switched off.
Substep

Reaction

3a

Insert the CPUs and coordinator
in the relevant slots.

none

3b

Insert all EPROM or RAM submodules in the CPUs according
to the configuration. The
EPROM submodules must have
been previously programmed
with a PG.

none

Set all mode switches on the
CPUs and on the coordinator to
STOP.

none

3c

6-8

Action

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

Step 4
Action
Switch the supply voltage on.

Reaction
1. The red STOP LEDs flash
rapidly on all CPUs to indicate:
Overall reset requested.
2. If the test mode is not set at the
coordinator (see Section 6.3)
and the mode switch is not at
the TEST setting:
The red BASP (output inhibit)
LED is permanently lit to
indicate: Digital outputs are
inhibited.

Possible Faults

Symptom:
On some CPUs the STOP LED is not lit; the other CPUs are requesting
OVERALL RESET. All CPUs are emitting the BASP (output inhibit) signal.
Remedy:
Check the setting for the number of occupied CPU slots on the coordinator.
Are the CPUs inserted at suitable slots?

Step 5

Executing an OVERALL RESET on all CPUs:
Ensure that the mode switch on the coordinator is set to STOP. (Precondition:
Steps 3 and 4 have been fully executed.
Action

Reaction

Execute the OVERALL RESET for
each individual CPU:

The red STOP LEDs on the CPUs at
which the OVERALL RESET was
executed, light up continuously.
Hold the MC 1) mode switch in the
Each CPU additionally emits the
OVERALL RESET setting; simulta- output inhibit signal (BASP LED
neously set the mode switch from
continuously lit).
STOP to RUN and back to STOP.

1)

System Manual
C79000-G8576-C199-06

MC: Momentary-contact

6-9

Multiprocessor Operation/Coordinators

Step 6

Loading STEP 5 user programs in all CPUs:
Recommended precondition: The programs of the individual CPUs have
already been tested in single-processor operation.
For details of loading STEP 5 blocks and using the different types of
memory, please consult the relevant Programming Guides of the CPUs and
your PG Manual.
Prerequisites
What?

Where?

Data block DB 1 must be present for I/O allocation.

in all
CPUs 1)

Data block DX 0 must additionally be present at
CPU 948.

only in
CPU 948

The mode for “Process interrupts via IB 0 = off” must
be set in DX 0.
To start multiprocessor operation immediately with all
CPU programs, you must now load your programs into
the individual CPUs.

into the
desired
CPU 1)

After completing these steps, however, you can load
individual programs into certain CPUs.
1. You must only load the blocks for CPUs with RAM operations; for EPROM operation, the
inserted EPROMs must contain your user program with DB 1 (DX 0).
Data blocks which you have provided for dynamic data storage must be copied after a
RESET by program into the RAM.

Reaction
There is no change in the reactions of Step 4 (each CPU still emits the
output inhibit signal: the BASP LED is continuously lit).

6-10

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

Step 7

Executing a RESET at all CPUs:
Action

Reaction

Execute a RESET at each individual
CPU:
Hold the MC 1) mode switch at the
RESET setting; simultaneously set the
mode switch from STOP to RUN.

The red STOP LED on each CPU
is continuously lit; each CPU
emits the output inhibit signal.
The CPUs are in the wait state.

1)

Possible Faults

MC: Momentary-contact

Symptom 1:
The STOP LED of one CPU flashes slowly. When the control bits of this
CPU are read out with the programmer, “DB 1 error” is marked in addition to
the usual information. There is no output of an ISTACK.

Remedy:
Check whether data block DB1 in the CPU was correctly loaded and
programmed.

Symptom 2:
After execution of a RESET:
Undefined states or faults occur at the CPUs (e.g. after a RESTART at
CPU 922, it goes to the RUN state although the other CPUs are still at
STOP).

Remedy:
Verify the following points:
Is the coordinator inserted?
Are all modules correctly inserted (engaged)?
Are all modules at the correct slots?

System Manual
C79000-G8576-C199-06

6-11

Multiprocessor Operation/Coordinators

Step 8

Setting the coordinator mode switch to RUN or TEST:
IF ...

Reaction

You do not wish to
Set the coordinator
work in the test mode 1) mode switch from
STOP to RUN.

The green RUN LEDs
of all CPUs are
continuously lit. All
CPUs simultaneously
go into the cycle. The
output inhibit signal is
not emitted (BASP
LED = off).

You wish to work in the Set the coordinator
test mode (it must be
mode switch from
enabled on the
STOP to TEST.
coordinator) 1)

Set the coordinator
mode switch from
STOP to TEST.

1)

Possible Faults

THEN ...

Test mode and setting: see Section 6.3

Symptom:
All CPUs remain in the Stop state.
Remedy:
Check whether the mode switches of all CPUs are set to RUN.
A subsequent start of individual CPUs is not possible. Switch the coordinator
back to STOP. Execute a RESET at all CPUs and then switch the coordinator
to RUN again.
Note
During the starting phase (processing of the start OBs) the STOP and RUN
LEDs remain off at all CPUs. The RUN LED only lights up continuously
when the CPUs go over to cyclic program processing.

Notes Relating to
Multiprocessor
Start

When the coordinator is switched from STOP to TEST, only the CPUs
whose switches are at the RUN setting will operate in the test mode.
If the 923C coordinator is used and the PG interface on the front plate is
not connected to the PG and switched online, the IF FAULT LED lights
up on the 923C coordinator. The indicator can be ignored in this case.

6-12

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

6.3

Coordinator Modes

The Stop State

If, when the supply voltage is switched on, the coordinator mode switch is at
STOP or another stop request is pending, the CPUs remain in the Stop state.

Startup

AUTOMATIC RESET or
AUTOMATIC RESTART
If, when the supply voltage is switched on, the coordinator mode switch is at
RUN, an AUTOMATIC RESET or AUTOMATIC RESTART (depending on
DX 0 setting) will take place as long as the mode switches of the CPUs are
also at RUN and the PLC was previously in cyclic operation.
MANUAL START
When you set the coordinator mode switch from STOP to RUN, the CPUs
will execute a start if this was already prepared at all CPUs by appropriate
switch actuation, i.e. the CPUs are in the wait state. As required by the user,
the type of start can be the same for all CPUs or arbitrarily different.
After the start synchronization by the system programs, the CPUs
simultaneously go to RUN (cyclic operation).

Normal Operation
and Stop in the
Event of Faults

The transition of individual CPUs is synchronized - as long as the preset
“start synchronization” in the relevant CPUs has not been changed by DX 0
programming - i.e. only when each CPU has ended its start do all CPUs
jointly go to cyclic program processing.
If the coordinator mode switch is at the RUN setting and one CPU goes to
the Stop state, all the other CPUs also go to the Stop state. The red STOP
LED(s) on the CPU(s) causing the Stop state flash slowly; the STOP LEDs of
the other CPUs are continuously lit.
Apart from any indication with fault LEDs on the CPU which is the cause, all
CPUs emit the BASP (output inhibit) signal.

System Manual
C79000-G8576-C199-06

6-13

Multiprocessor Operation/Coordinators

Test Mode

!

Warning
Since, in the test mode, no CPU can emit a BASP (output inhibit) in the
event of a fault, the test mode must be switched to the inactive state
without fail after completion of startup to avoid a critical or even
hazardous system state.
Before you can go into the test mode with the TEST switch, you have to
enable it on the module. This is achieved differently with the 923A and 923C
coordinators.

Enabling the Test
Mode with the
923A

Insert jumper 3 - 14 on coding socket EP 45 as shown in the following
sketch.
16

9

14

EP 45

923A Coordinator
1

Enabling the Test
Mode with the
923C
Reaction of the
CPUs

3

8

Set DIL switch S1.3 from Off to On (the following table shows the DIL
switches as delivered; see also Figure 6-2).

DIL S.
S1.1
S1.2
S1.3
S1.4
S1.5
S1.6

on

off
x
x
x

x
x
x

Effect
–
–
Test mode
No. of occupied CPU slots = 2
No. of occupied CPU slots = 3
No. of occupied CPU slots = 4

When the coordinator mode switch is set from STOP to TEST, the CPUs can
be started individually. There is therefore no synchronized transition to
cyclic program processing. The output of signal BASP is suppressed on all
CPUs, even if there is an error.
f an error occurs with a CPU switched to RUN, only this one goes to the Stop
state in the test mode. The error is indicated by slow flashing of the CPU’s
STOP LED. The error at this CPU does not affect other CPUs.
If the test mode is not activated, a changeover from STOP to TEST does not
result in any reaction of the CPUs.

6-14

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

6.4

6.4.1

923A Coordinator Module

Technical Description
This section contains information on the application, design and principle of
operation of the 923A coordinator.

Application

The 923A coordinator module is intended for operation in the S5-135U/155U
PLC. It is required in multiprocessor operation and has the following
functions:
Bus arbitration
To coordinate multiprocessor operation, i.e. the simultaneous use of two
to four CPUs (CPU 928B, CPU 928 or CPU 922).
Communication memory
for the interchange of data between CPUs via communication flags.

Note
The 923A coordinator module cannot be used in multiprocessor operation if
a CPU 948 is fitted in the 135U/155U PLC. If you execute global memory
access in multiprocessor operation (I/O area with addresses 0000H-EFFFH)
with the CPU 928B and/or the CPU 928, you must use the COR 923C as the
coordinator.

Design

The COR 923A is designed as a plug-in PCB of double Eurocard format.
Two 48-way Series 2 blade connectors serve to connect the PCB to the S5
bus in the subrack.
The front plate width is 1 1/3 standard plug-in stations.
A three-position mode switch is fitted in the front plate for operator
functions.

System Manual
C79000-G8576-C199-06

6-15

Multiprocessor Operation/Coordinators

Principle of
Operation

Bus arbitration
The COR 923A cyclically allocates a bus enable signal to each of the two to
four CPUs in the S5-135U/155U PLC. Only during this time can the relevant
CPU utilize the common S5 bus.
The assignment of bus enable signals takes place in time-division multiplex
operation. On the COR 923A, you set the number of CPUs with jumpers. The
enable time for access to the S5 bus is preset at 2 ms for all CPUs. If the bus
enable signal has been emitted by the coordinator for a CPU, this CPU can
extend the enable time with the bus lock signal. However, the user has no
influence on this.
The bus enable assignment sequence begins with CPU 1 after the
Reset signal is removed by the power supply, and enables the CPUs
in the following order according to the preset number of CPUs:
CPU 1, CPU 2, CPU 3, CPU 4, CPU 1, CPU 2 etc. (see Figure 6-5)

Bus Enable for:
CPU1

2 µs

CPU2

CPU3
2µ s +
Bus Lock

CPU4

Bus Lock

Reset

CPUs in Operation
Time
Figure 6-5

Timing Sequences of the Bus Signals

Communication memory
The communication memory comprises a central battery-backed RAM in the
PLC. It has two areas: the communication flags and the semaphores.
The communication flags on the COR 923A allow the cyclic interchange of
data between the CPUs. The semaphores are mainly used to coordinate the
exchange of data in the I/O area.

6-16

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

Please consult the Programming Guides of the CPUs to program these
functions.

6.4.2

Settings on the Coordinator

User Control

A three-stage mode switch on the front plate serves for user control; it has the
settings RUN, STOP and TEST.
The functions of the mode switch and its use are explained in Sections 6.2
and 6.3.

Mode switch for
RUN, STOP and TEST

Figure 6-6

System Manual
C79000-G8576-C199-06

Front Plate of the COR 923 A

6-17

Multiprocessor Operation/Coordinators

6.5

6.5.1

923C Coordinator Module

Technical Description
This section contains information on the application, design and principle of
operation of the 923C coordinator.

Application

The 923C coordinator module can be used in the S5-135U/155U
programmable controller and in the EU S5-185U expansion unit. There are
three main task areas which are, to some extent, independent:
Bus arbitration (only in the central controller)
To coordinate multiprocessor operation, i.e. the simultaneous use of two
to four CPUs (CPU 948, CPU 928B, CPU 928, CPU 922).
Communication memory (only in the central controller)
For the interchange of data between CPUs via communication flags and
data blocks.
Central programmer connection (PG MUX)
For the programming and startup of up to 8 modules via one PG
connection.
To program a programmable controller via the SINEC H1 or SINEC
L1/L2 bus, connect the SINEC CP to the PG connection of the COR C
using the 725 cable (“swing” cable).

6-18

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

Design

The COR 923C is designed as a plug-in PCB in double Eurocard format.
Two 48-way Series 2 blade connectors serve to connect the module to the S5
bus in the subrack.
The front plate width is 1 1/3 standard plug-in stations.
A mode switch with three settings is fitted in the front plate for other
operator functions.
Faults are indicated by five small red LEDs.
There is a recess with cover in the upper third of the front plate. By removing
the cover, you can operate the DIL switches to set parameters for the module.
You can connect the COR 923C via a 15-pin front connector to a
programmer, OP, operator control panel or the CP 530 and CP 143.

Principle of
Operation

The COR 923C cyclically allocates a bus enable signal to each of the two to
four CPUs in the S5-135U/155U PLC. Only during this time can the relevant
CPU utilize the common S5 bus.
The assignment of bus enable signals takes place in time-division multiplex
operation. On the COR 923C, you set the number of CPUs with DIL
switches. The enable time for access to the S5 bus is preset at 2 ms for all
CPUs. If the bus enable signal has been emitted by the coordinator for a
CPU, this CPU can extend the enable time with the bus lock signal. However,
the user has no influence on this.
The bus enable assignment sequence begins with CPU 1 after the Reset
signal is removed by the power supply, and enables the CPUs in the
following order according to the preset number of CPUs:
CPU 1, CPU 2, CPU 3, CPU 4, CPU 1, CPU 2 etc. (see Figure 6-7)

System Manual
C79000-G8576-C199-06

6-19

Multiprocessor Operation/Coordinators

Bus Enable for:
CPU1

2µs

CPU2

CPU3

2µs +
Bus Lock

CPU4

Bus Lock

Reset
CPUs in Operation
Time
Figure 6-7

Timing Sequences of the Bus Control Signals

Monitoring for continuous bus assignment
The bus lock signal can only be emitted by the CPU which has already
received a bus enable signal from the COR 923C. The bus enable time is
extended by the duration of the bus lock signal for the CPU (see Figure 6-7).
The factory setting for monitoring of the bus lock signal is 2 ms. If the signal
remains active for a longer duration, the COR 923C emits a signal which
results in a Stop of all CPUs.
The CPU which emitted the bus lock signal for too long a duration, is marked
by the CPU in a readable register under address FEFFH (fault register, see
Figure 6-8). The assigned BUS FAULT LED in the front plate of the COR
923C lights up. The register is cleared and the LED goes off again when the
signal which led to the Stop state becomes inactive.

Communication memory
The communication memory comprises a central battery-backed RAM in the
PLC. It has three areas: 1) the communication flags (256 bytes), 2) the
semaphores (32), and 3) four memory pages.
The communication flags are located in memory area F200H to F2FFH. The
communication flags enable the cyclic interchange of small volumes of data
between the CPUs in the S5-135U/155U PLC. The four memory pages serve
for the exchange of data blocks between CPUs.
Please consult the Programming Guides of the CPUs to program these two
functions.

6-20

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

The semaphores are used to coordinate the CPUs for access to the same I/O
address (see Programming Guides, operations SES and SEF).

F200H
Communication Flags
F300H
Synchronization Area
for Operating Systems
F400H
Page Memory for
Data Blocks

Page
No. 252

Page
No. 253

Page
No. 254

Page
No. 255

F7FFH
Vector Register for
Page Selection,
Fault Register

Figure 6-8

FEFFH

Areas of the Communication Memory on the S5 Bus

Addressing method for the page memory (vector register)
The vector register serves to form subaddresses of several memories in a
common address area. The register is an 8-bit register which is written to
under address FEFFH. It cannot be read out.
The page memory contains four pages of 1 Kbyte. An identification number
is assigned to each page. These are the numbers 252, 253, 254 and 255.
These numbers are permanently set on the COR 923C and cannot be
changed. You must not use these numbers on other modules (CP, IP) in the
same PLC otherwise double addressing will occur.
When the supply voltage is switched on, the vector register is cleared. The
vector register then has the number 0H.
The transfer of data to and from this memory is implemented with special
functions of the CPU. You can find these functions in the appropriate
Programming Guides.

PG Multiplexer

System Manual
C79000-G8576-C199-06

The PG interface of the COR 923C can be switched over to eight different
serial interfaces via the path selection of the PG software.
The multiplex interfaces have TTL level and are wired to the other modules
via the backplane connector and backplane.

6-21

Multiprocessor Operation/Coordinators

Selection Method
for the Serial
Interfaces

Station numbers are assigned to all the modules to be served by the
multiplexer in the unit. These numbers must be within the range 1 to 31
(decimal). You set the lowest of these numbers, the base address, with DIL
switch S2 in binary code. The maximum of eight numbers are allocated to
the slots of the PLC (see following table).
All eight numbers or slots are assigned to switch S3: the lowest number to
switch S3.1, and the highest number to switch S3.8. The setting of station
numbers and the base address are described in more detail in Section 6.5.2.
Switch

Slot

S3.1
S3.2
S3.3
S3.4
S3.5
S3.6
S3.7
S3.8

11
27
43
59
75
83
91
99

Station No.
Base address
Base address + 1
Base address + 2
Base address + 3
Base address + 4
Base address + 5
Base address + 6
Base address + 7

If slots are not occupied or if you wish to operate modules via their own front
connectors, you must delete the numbers assigned to the corresponding slots
with switch S3.
Note
For a module operated via the multiplexer, the front connector of the PG
interface of the CPU must not be plugged in. With CPUs 948 and 928B,
this only applies to the integrated PG interface SI 1.

6-22

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

6.5.2

Settings on the Coordinator

Indicators and
Controls

Shown in Figure 6-9 are all the indicators and controls on the front plate of
the COR 923C.

Setting the Coordination Section:
S1.3 to enable/lock out the “Test” mode
S1.4 to S1.6 to set the number of CPUs
Setting the PG Multiplexer:
S2.2 to S2.6: Base address
S3.1 to S3.8: Activating the slots to be served by the COR923C

Mode switch for RUN, STOP and TEST
“BUS FAULT” LEDs
These are allocated to the relevant CPUs and light up when the max. value of
monitored bus access time is exceeded.
“IF FAULT” LED
indicates fault at the serial interface.
If the interface is not in use, the LED is permanently lit.
PG interface, 15-pin

Figure 6-9

Front plate of the COR 923C

Mode Switch

The mode switch on the front plate can be set to RUN, STOP and TEST.
Please refer to Sections 6.2 and 6.3 for its functions and use.

System Manual
C79000-G8576-C199-06

6-23

Multiprocessor Operation/Coordinators

Setting the DIL
Switches
Note
On switch S1, the On position is on the left; on switches S2 and S3, however,
it is on the right (see Figure 6-10).

on off

off on

off

Figure 6-10

Coordination
Section (Number
of CPUs)

on

DIL Switches on the COR 923C (Settings when Delivered)

You set the number of CPUs present in the PLC with the 3 DIL switches S1.4
to S1.6. You may only set one switch.
The factory setting is “Number of CPUs = 2” (see below).
Factory setting:

Setting

Switch
on

off

S1.1

x

–

S1.2

x

–

S1.3

x

S1.4

6-24

Meaning

x

Test mode (see also Sec. 6.3)
Number of CPUs = 2

S1.5

x

Number of CPUs = 3

S1.6

x

Number of CPUs = 4

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

PG Multiplexer:
Base Address

You set a base address from 1 to 31 with DIL switch S2. You can reference
the modules selected by the multiplexer under this address and the following
seven addresses. The base address results from the sum of binary
significances activated by the On setting of the switch.
Factory setting:
Setting

Switch
off

on

’0’

’1’

S2.1

x

–

S2.2

x

Significance 16

S2.3

x

Significance 8

S2.4

x

Significance 4

S2.5

x

Significance 2

S2.6

PG Multiplexer:
Activating
Addesses

Meaning

x

Significance 1 (base address = 1)

You use switch S3 to activate the numbers and slots to be reached via the
COR 923C.
Factory setting:
Setting

Switch
off

Meaning
on

Slot No. in the
S5 135U/155U
S5-135U/155U

S3.1

x

Base address + 0

11

S3.2

x

Base address + 1

27

S3.3

x

Base address + 2

43

S3.4

x

Base address + 3

59

S3.5

x

Base address + 4

75

S3.6

x

Base address + 5

83

S3.7

x

Base address + 6

91

S3.8

x

Base address + 7

99

An example for setting the PG multiplexer is given on the following page.

System Manual
C79000-G8576-C199-06

6-25

Multiprocessor Operation/Coordinators

Example of
Address Activation

You wish to reference modules at Slots 11, 59, 75 and 99 in the
S5-135U/155U PLC via the COR 923C, from base address 10.
Setting the base address:
Setting

Switch
off

Meaning
on
Base address:

S2.1

x

S2.2

x

S2.3

–
Significance 16
x

Significance 8

S2.4

x

Significance 4

S2.5

x

Significance 2

S2.6

x

8

+

2

=

10

Significance 1

Activating the required slots for the S5-135U/155U PLC:
Setting

Switch
off
S3.1

Slot No. in the
S5-135U/155U

Operable Slots

End
Address

Base address + 0

11

11

10

Meaning
on
x

S3.2

x

Base address + 1

27

S3.3

x

Base address + 2

43

S3.4

x

Base address + 3

59

59

13

S3.5

x

Base address + 4

75

75

14

99

17

S3.6

x

Base address + 5

83

S3.7

x

Base address + 6

91

Base address + 7

99

S3.8

6-26

x

System Manual
C79000-G8576-C199-06

Multiprocessor Operation/Coordinators

Jumpers to
Switch off the
Coordination
Signals

All the output signals required for coordination (arbitration) can be
interrupted by removing a jumper plug. This is necessary to operate the COR
923C as a PG multiplexer in the EU S5-185U.

Coordination Section
in operation

out of operation

All jumpers of EP 61 closed

All jumpers of EP 61 open

8

1

9

16

EP 61

When the unit is delivered, all jumpers are closed.

Fault Register

The fault register is an 8-bit register and is readable by the CPU under
address FEFFH. The register is written to by the bus monitor in the event of a
bus error. Each CPU is assigned one bit of the fault register which is set to 1
in the event of an error. The register is cleared each time the Stop signal
becomes inactive.

7

4
Not assigned

3

2

1

0
Fault register FEFFH
Bit = 1: Bus error from CPU 1
Bit = 2: Bus error from CPU 2
Bit = 3: Bus error from CPU 3
Bit = 4: Bus error from CPU 4

The fault register can be read by all CPUs, allowing central functions to be
initiated.
Note
The fault register and the page register are at address FEFFH (FFEFFH with
the CPU 948). The page register is addressed by writing to FEFFH, and the
fault register is addressed by reading out FEFFH.

System Manual
C79000-G8576-C199-06

6-27

Multiprocessor Operation/Coordinators

6.6

Technical Specifications of the Coordinators
Important for the USA and Canada
The following approvals have been obtained:

S UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972

S CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533
923A Coordinator
Degree of protection

923C Coordinator
IP 00

Operating temperature

0 to +55 _C

Transportation and storage
temperature

40 to +70 _C

Relative humidity

95% max. at +25 _C, no condensation

Operating altitude

3500 m max. above sea level

Supply voltage

5 V $ 5%

5 V $ 5%
24 V +25%/ –15%

Current consumption at 5 V

0.5 A typical

1.1 A typical

Current consumption at 24 V

–

Minimum backup voltage
Backup current

60 mA
2.7 V
2 mA typical

100 nA typical

Acknowledgement time for
access to communication
memory via S5 Bus

320 ns typical

Transmission rate of the serial
interface

–

9600 bps

Transmission cable

–

Shielded 4-wire line, PG
connecting cable

Transmission range

–

1 km max. at 9600 bps

Weight
Dimensions (W x H x D)

6-28

Approx. 0.3 kg
20.32 x 233.4 x 160 mm

System Manual
C79000-G8576-C199-06

7

Interface Modules

Various interface modules (IMs) are available for communication between a
central controller and expansion units, and between expansion units.
Interface modules in the central controller are known as EU interface
modules; those inserted in an EU are known as CC interface modules.
This chapter describes the EU interface modules:
IM 300-3, IM 300-5, IM 301-3, IM 301-5 and IM 304
as well as the CC interface modules:
IM 312-3, IM 312-5, IM 310 and IM 314
Other IMs such as the IM 307-IM 317 and the IM 308-IM 318 are described
in separate manuals (see Catalog ST 54.1). The IM 306 CC interface module
is described in the S5-115U PLC manual.
A general overview of the applications of individual IMs can be found in
Chapter 2: “Centralized and Distributed Configuration of a Programmable
Controller.”

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Description

Page

7.1

The 300 and 312 Interface Modules

7-2

7.2

The 301 and 310 Interface Modules

7-9

7.3

The 304 and 314 Interface Modules

7-13

7.4

Technical Specifications

7-20

7-1

Interface Modules

7.1

The 300 and 312 Interface Modules
The 300 and 312 interface modules are used for centralized connection of
I/O modules and signal preprocessing modules (IPs) to a CC via the
following expansion units (allowing for possible configurations):
EU 183U
EU 184U
EU 185U (only input/output modules)
EU 187U
ER 701-1
Additionally, you can utilize these IMs for secondary communication, i.e.
additional EUs can be connected in a centralized arrangement to an EU 183U
or EU 185U in distributed configuration. Up to four IM 300s can be used in
one CC, up to two of which may be IM 300-5s. You can use one IM 300 in
an EU 183U or EU 185U.

Application of the
IM 300 and IM 312

An IM 300 EU interface module is complemented by an IM 312 or
IM 306 CC interface module. Use the following IMs, depending on the
connected EU:
EU Interface Module

EU Type

CC Interface Module

IM 300-5 C
(6ES5 300-5CA11)

EU 184U, EU 187U

IM 312-5

IM 300-3
(6ES5 300-3AB11)

EU 183U
EU 185U (only I/O
modules)

IM 312-3

IM 300-5 L
(6ES5 300-5LB11)

ER 701-1

IM 306

There are two versions of IM 312-3 and IM 312-5. They differ in the length
of permanently connected cable:

7-2

Order No.

Cable Length

6ES5 312-5CA1X
6ES5 312-5CA2X

0.5 m
1.5 m

6ES5 312-3AB1X
6ES5 312-3AB3X

0.5 m
0.95 m

System Manual
C79000-G8576-C199-06

Interface Modules

Connecting the
EU 184U and
EU 187U

For one IM 300-5, you can connect up to three EUs to a CC or EU in
distributed arrangement (see Figures 7-5 and 7-6). The EUs are supplied with
operating voltage via the IMs. Any free connections on the IM 300-5 and the
last IM 312-5 require no terminator.
Note
The maximum permissible current over each connection of the
IM 300-5CA11 is 5 A.

Connecting the
EU 183U, EU 185U

You can connect up to four EUs to each IM 300-3. The last IM 312-3
requires a terminator.

Connecting the
ER 701-1

You can connect up to three ERs to each IM 300-5L (-5LB11). The ERs are
supplied with operating voltage via the IMs.
Note
The maximum permissible current over each connection of the
IM 300-5LB11 is 2 A.

The connection of central controller and expansion unit to the IM 300-5LB11
is provided exclusively by the 705-0 connecting cable. It is available in two
lengths: 0.5 m and 1.5 m (refer to the ordering information for order
numbers).

Addressing

When the IM 300s are used in the S5-135U/155U PLC, the input/output
modules can be addressed in the normal (P) and extended (O) areas.
You may only set module addresses in the EU which are not used in the CC.
This applies to both areas.

System Manual
C79000-G8576-C199-06

7-3

Interface Modules

7.1.1

Indicators and Controls
IM 300-3:
I/O Module Failure LED
This LED lights up if the supply of power to the connected EUs has failed
and/or the connecting cable is open-circuit.
IM 300-5 (-5CA11):
I/O Module Failure LEDs
LEDs LD1 and/or LD2 light up if a module inserted in the EU no longer
responds to an access by the CPU.
The IM 312 has no indicators or controls.

34

18

34

1

18

1

34

50 33 17

50 33 17

I/O Module
Failure

18

1

50 33 17

I/O Module
Failure
Fault

Fault

Fault

34

50

IM300-3
Figure 7-1

7-4

18

33

1

17

IM300-5

IM312

Front Plates of the IM 300 and IM 312

System Manual
C79000-G8576-C199-06

Interface Modules

7.1.2

Modes/Jumper Assignments of the IM 300

Jumper
Assignments

IM 300-3

16

9

1

8

12

X3

X1

LED 1

X2

J1

Figure 7-2

Purpose of the
Jumpers

Location of Jumpers on the IM 300-3 (when Delivered)

You must insert an additional jumper 4-13 at location 12 for address setting
in the extended I/O area (O area).
Jumper 1 is open and has no function for operation in the S5-135U/155U
PLC.

System Manual
C79000-G8576-C199-06

7-5

Interface Modules

Jumper
Assignments

IM 300-5 (-5CA11)

16

9

1

8

4

X3

J1

X1
J2
J3

LED1
LED2

X2

X4

J8

Figure 7-3

Location of Jumpers on the IM 300-5 (-5LB11) (when Delivered)

You must insert jumper 8-9 at location 4 for address setting in the extended
I/O area (O area). All other jumpers must remain in their factory settings.

7-6

System Manual
C79000-G8576-C199-06

Interface Modules

Jumper
Assignments

IM 300-5 (-LB11)

M1
P1
X3

X1

X2
X4
Q1 Q2 Q3 Q4 Q5

Figure 7-4

Location of Jumpers on the IM 300-5 (-5LB11) (when Delivered)

You must insert jumpers Q1 to Q4 for addressing in the normal (P) area.
If you insert jumper Q5, the “I/Os not ready” message will be relayed to the
CPU.
All other jumpers must remain in their factory settings.
Shown in the following figures is the centralized communication between
central controller and expansion units, with and without supply of power via
the IM 300 and IM 312.

System Manual
C79000-G8576-C199-06

7-7

Interface Modules

EU183U

IM 312-3

EU183U

IM 312-3

EU183U

IM 312-3

EU183U

IM 312-3

S5-135U/155U
CC

IM 300-3

Centralized Communication Between Central Controller and Expansion Units with a Power Supply
Unit

IM312-5

EU 184U
EU 187U

IM312-5

EU 184U
EU 187U

IM312-5

With this arrangement, the two
cabinets must be electrically
interconnected.

Total Length of Lines 2 m max.

EU 184U
EU 187U

EU 184U
EU 187U

5 A max.

Figure 7-5

Total Length of Lines 2 m max.

Terminator

S5-135U/155U
CC

IM 312-5

(0.5m)

EU 184U
EU 187U

IM300-5

IM 312-5

5 A max.
(1.5m)

Figure 7-6

Centralized Communication Between Central Controller and Expansion Units without a Power Supply
Unit

The EU with the highest current consumption should be positioned as closely
as possible to the CC.

7-8

System Manual
C79000-G8576-C199-06

Interface Modules

7.2

The 301 and 310 Interface Modules
The IM 301 is used to connect I/O modules and signal preprocessing modules
(IPs) to a CC in a distributed arrangement (allowing for possible
configurations) via an
EU 183U
EU 185U (only input/output modules)
expansion unit.
You can connect up to four EUs to a CC in distributed arrangement via the
IM 301. If you use the 721 connecting cable, the total cable length from the
CC to the last EU may be up to 200 m. The distributed connection is made
via the lower front connector of the module. Use the IM 310 interface
module in the EU to be connected in a distributed arrangement:
EU Interface Module

EU Type

CC Interface Module

IM 301

EU 183U,
EU 185U (only I/O
modules)

IM 310

Apart from the distributed EUs, you can connect the following expansion
units in a centralized arrangement:
EU 183U
EU 184U
EU 187U
The centralized connection is made via the upper front connector of the
module. Use the following interface modules, according to the EU to be
connected in a centralized arrangement:
EU Interface Module

EU Type

CC Interface Module

IM 301-5

EU 184U, EU 187U

IM 312-5

IM 301-3

EU 183U

IM 312-3

Unused centralized connections of the IM 301-3 and unused distributed
connections of the IM 301-3 and IM 301-5 must be terminated with
terminators. The same applies to the last IM 310.
You may only set module addresses in the EU which you are not yet using in
the CC. This applies to the normal (P) and extended (O) areas.

System Manual
C79000-G8576-C199-06

7-9

Interface Modules

7.2.1

Indicators and Controls
IM 301:
Fault LEDs
When the CPU is restarted, the red LED 1 and/or LED 2 lights up if the
internal supply voltage (5 V DC) or external load voltage (24 V DC) fails.
The IM 310 has no indicators or controls.

34 18 1

34 18 1

Centralized
Connection

50 33 17

50 33

Fault

17

Fault

Fault

34

18

34

1

18

1

Distributed
Connection

50 33 17

IM 301
Figure 7-7

7-10

50 33

17

IM 310

Front Plate of the IM 301 and IM 310

System Manual
C79000-G8576-C199-06

Interface Modules

7.2.2

Modes/Jumper Assignments of the IM 301

Jumper
Assignments
16

9

1

8

7

X3

J3

LED1

X1

16

9

1

8

27

LED2

J4 *)

X4

X2

J1

*) Not on the IM 301-5

Figure 7-8

Location of Jumpers on the IM 301 (when Delivered)

You must insert jumper 8-9 at location 7 for address setting on the extended
I/O area (O area). All other jumpers must remain in the factory settings.

System Manual
C79000-G8576-C199-06

7-11

Interface Modules

The following figures show distributed communication between central
controller and expansion units via the IM 301 and IM 310.
Additional EU 184U, EU 187U
(Centralized)

Additional EU 183U
(Centralized)

EU 183U

IIM312–3

760–0AB11
Terminator

EU183U

IM 312–5

IM 310

IM 310

CC
S5–135U/155U

EU 184U
EU 187U

IIM312–3

IM301–3
EU 183U

IM300–3

EU 183U

IM 300–5

760–0AA11 Terminator
All 721 Connecting Cables
To Additional Expansion Cabinets
(up to 4 per IM 301)

200m max.

Figure 7-9

Connection of EU 183Us to the Central Controller via the IM-301-3

Additional EU 184U, EU187U
(Centralized)

Additional EU 184U, EU 187U
(Centralized)

EU 184U
EU 187U

IM 312–5

EU 183U

EU 187U

IM 310

S5–135U/155U
CC

EU 184U

IM 312–3

IM 301–5
EU 183U

IM 312–5

IM 310

IM 300–3

760–0AA11
Terminator

EU 183U

IM 300–5

760–0AA11 Terminator
All 721 Connecting Cables
to Additional Expansion Cabinets
(up to 4 per IM 301)

Figure 7-10

7-12

Connection of EU 184/EU 187 U to the Central Controller via the M 301-5

System Manual
C79000-G8576-C199-06

Interface Modules

7.3

The 304 and 314 Interface Modules
The IM 304 and IM 314 are used to connect I/O modules, signal
preprocessing modules (IPs) and communication processors (CPs) to a CC in
a distributed arrangement via the
EU 185U
ER 701-3
expansion units.
You can also use the IM 304 and IM 314 to connect I/O modules to a CC in a
distributed arrangement via the
EU 183U
ER 701-2
expansion units.

Line Length

You can connect up to two-times four EUs in a distributed arrangement via
one IM 304. If you utilize the 721 connecting cable, the total line length from
the CC to the last EU may be 600 m per run. You can connect additional EUs
in a centralized arrangement to the distributed EUs.
You can insert up to four IM 304s in one CC.
The IM 304 EU interface module is complemented by the IM 314 CC
interface module. In fault-tolerant systems, you must use the IM 314R CC
interface module together with the IM 304 (refer to the S5-155H manual).

EU Type

EU Interface Module

CC Interface Module

EU 183U
EU 185U
ER 701-2
ER 701-3

IM 304

IM 314

You may only set module addresses in the EU which you do not use in
the CC. This also applies when the EU is addressed in the extended (O) area,
IM3 area or IM4 area.

System Manual
C79000-G8576-C199-06

7-13

Interface Modules

7.3.1

Indicators and Controls
Fault LEDs
A FAULT LED lights up
if the power supply fails in an expansion unit;
if there is no terminator at the last IM 314;
in the event of a cable open-circuit or wrong setting of DIL switch S3 for
the IM 304;
or if an EU which is ready and operational is connected to an interface
which is switched off.

34

18

34

1

18

1

Interface (X3)

50 33 17

Fault Signal:
Interface (X3) Faulty

50 33 17

Fault

Fault

34

18

1

Fault Signal:
Interface (X4) Faulty

34

18

1

Interface(X4)

50

33 17

IM 304
Figure 7-11

7-14

50

33

17

IM 314

Front Plates of the IM 304 and IM 314

System Manual
C79000-G8576-C199-06

Interface Modules

7.3.2

Modes/Jumper Assignments of the IM 304
You must match the IM 304 to the cable length with jumper X11.

Jumper Plug X11
9 7 5 3 1

Jumper
Location
Cable Length

9 7 5 3 1

9 7 5 3 1

9 7 5 3 1

9 7 5 3 1

*)
10 8 6 4 2

10 8 6 4 2

10 8 6 4 2

10 8 6 4 2

10 8 6 4 2

10m max.

100m max.

100 to 250m

250 to 450m

450 to 600m

*)

This setting is only permissible for IM 304 - IM 324R communication in the S5-155H PLC.

The longest communication path, i.e. the sum of cable lengths at interface of
X3 or X4, is governed by the location of jumper X11.

Jumper
Assignments

X1

X3
X22

LED2

ON
OFF

Jumper X21/X22
set to OFF if no
expansion unit is
connected.

OFF ON

X13

ON
OFF

S3
X21

LED1

1
2
3

X14
X4

1
2
3

9 753 1

10 8 6 4 2

X12

321

X15 X2

X11

Figure 7-12

System Manual
C79000-G8576-C199-06

Location of Jumpers on the IM 304 (when Delivered)

7-15

Interface Modules

Purpose of the
Jumpers

Function

Jumper Settings

Interface X3/X4
– Switched on
– Switched off 1)

X22/X21 at “ON”
X22/X21 at “OFF”

“I/Os not ready” message relayed
– no
– yes

X15 no jumpers
X15 jumper 1-2

ON
OFF
ON
OFF

1
2
3
1
2
3

“I/Os not ready” message when
– 1 interface not ready
– 2 interfaces not ready

X14 jumper 1-2
X14 jumper 2-3

Set cable length between 304 / 314
– 0 to 100 m
– 100 to 250 m
– 250 to 450 m
– 450 to 600 m

X11
Jumper 3-4
Jumper 5-6
Jumper 7-8
Jumper 9-10

1
2
3
1
2
3

9 7 5 3 1

10 8 6 4 2
1)

Jumper X22 is assigned to interface X3.
Jumper X21 is assigned to interface X4

All other jumpers and switches must remain at the factory settings.

7-16

System Manual
C79000-G8576-C199-06

Interface Modules

7.3.3

Modes/Jumper Assignments of the IM 314

Jumper
Assignments

Set the jumpers according to the expansion unit in use.

Operation in the EU 185U
21

321

off

S1

21
J1

on

J2

J1

Operation in the EU1 83U

X3

321

J2

off

S1

on

X1
X3

J3

X4

321

X2

X4

321
J3

X1

X2

Operation in the ER 701-2, ER 701-3 (S5-115U)
21

off

321

J1

J2

S1

on

X1

X3

321
J3

X4

Figure 7-13

X2

Location of Jumpers on the IM 314

System Manual
C79000-G8576-C199-06

7-17

Interface Modules

Setting the
Addresses
I/O Area Address

Switch Setting
0 = OFF, 1 = ON

P area: F000 - F0FF

S1:

0000

O area: F100 - F1FF

0001

IM3 area:FC00 - FCFF

1100

IM4 area:FD00 - FDFF

1101

*)

irrelevant
n
i
c
h
t
r
e
l
ev
a
n
t

OFF
ON

*) Factory setting

The I/O area address is set on the IM 314. This setting applies only to the
digital and analog I/O modules.
Address areas P, O, IM3 and IM4 are available. To address the digital and
analog I/O modules in these areas, set the switches by depressing the
individual rockers.
In the STEP 5 standard operation set, you only address the P and O areas.
Module addresses used in the CC cannot be used in the EU in the P area, O
area, IM3 area and IM4 area.
If you do not insert I/O modules in the central controller, an address space of
256 bytes is available in each I/O area for input/output addresses.
The following figure shows communication between the central controller
and expansion units via the IM 304 and IM 314.

7-18

System Manual
C79000-G8576-C199-06

Interface Modules

Additional EU 184U, EU 187U
(Centralized)

EU 183U

IM 312–3

IIM 314

EU 183U

IM 312–3

IM 300–3

EU 183U

IM 300–3

EU 185U

EU 185U

IM 312–5

IM 314

IM 314

EU 183U

EU 184U
EU 187U

EU 183U

IM 300–5

EU 185U

760–1AA11 Terminator

All 721 Connecting Cables

EU 183U

IM 312–3

IM314

IM304

IM 312–5

IM 314

EU 183U
S5–135U/155U
CC

EU 184U
EU 187U

EU 185U

IM 300–3

EU 183U

IM 300–5

EU 185U

760–1AA11 Terminator

All 721 Connecting Cables
To Additional Expansion Cabinets (Distributed)
(up to 4 per IM 304)

600m max.

Figure 7-14

Communication Between Central Controller and Expansion Units via the IM 304/IM 314

System Manual
C79000-G8576-C199-06

7-19

Interface Modules

7.4

Technical Specifications
Important for the USA and Canada
The following approvals have been obtained:
UL Listing Mark
Underwriters Laboratories (UL) to
Standard UL 508, Report E85972 and E116536 for the IM 300-5LB11
CSA Certification Mark
Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533C and LR 48323 for the IM 300-5LB11
Given in the following are the technical specifications of the IMs and pin
assignments of the connecting cable and terminator.

General Specifications
Degree of protection

IP 20

Insulation class

C to VDE 0160

Operating temperature

0 to 55 oC

Transportation and storage temperature

– 40 to 70 oC

Relative humidity

95 % max. at 25 oC, no condensation

Mechanical requirements

see description of central controllers

Supply voltage (internal)

5V+5%

Specifications for Specific IMs
Interface
module

IM 300

IM 300
(-5CA)

IM 300
(-5LB)

IM 301
(-5CA)

IM 301
(-3AB)

IM 304

IM 310

IM 312

IM 314

Max. current consumption

0.6 A

0.6 A

50 mA 0.75 A

0.75 A

1.2 A

0.7 A

0.2 A

1.0 A

Max. current per interface

–

5A

2A

–

–

–

–

–

Weight,
approx.

0.35 kg

0.35 kg

0.25 kg 0.3 kg

0.3 kg

0.35 kg 0.3 kg

7.4.1

5A

0.35 kg 0.3 kg

6ES5 721 Connecting Cable
The 6ES5 721-xxx connecting cable is intended for interconnection of the
CC/EUs. Refer to the catalog for the SIMATIC length codes.

7-20

System Manual
C79000-G8576-C199-06

Interface Modules

. 34
. 1

Connector
Terminal
50-Way
20
21
4
5
18
19
2
3
24
25
8
9
22
23
6
7
26
27
10
11
42
43
44
45
28
29
12
13
46
47
30
31
34
35
36
37
38
39
40
41
48
49
14
15
32
33

–
Figure 7-15

50 .
.
17

.
1
34 .

. 17
. 50

Bundle
ID Sheath

ID Foil

1

rd

Red
No. 16
2

gn

Green
No. 17
3

wh

Yellow
No.18
4

wh

Brown
No.19
5

wh

Black
No.20
rd

6
Blue
No.21
Shield

Core
Color
wh
br
gn
ye
gr
pk
bl
rd
wh
br
gn
ye
gr
pk
bl
rd
wh
br
gn
ye
gr
pk
bl
rd
wh
br
gn
ye
gr
pk
bl
rd
wh
br
gn
ye
gr
pk
bl
rd
wh
br
gn
ye
gr
pk

Connector
50polig Terminal
20
21
4
5
18
19
2
3
24
25
8
9
22
23
6
7
26
27
10
11
42
43
44
45
28
29
12
13
46
47
30
31
34
35
36
37
38
39
40
41
48
49
14
15
32
33

–

Conductor Assignments of the 721 Connecting Cable

System Manual
C79000-G8576-C199-06

7-21

Interface Modules

7.4.2

6ES5 7602 Terminator
The IM 314 of the last expansion unit of each run is terminated with the
6ES5 760-1AA11 terminator. The IM 312 and IM 301-3 (with a free
centralized connection) is terminated with the 6ES5 760-0AB11 terminator.
The IM 301-3 (with a free distributed connection) is terminated with the
6ES5 760-0AA11 terminator.

1

17

34

Connector
Pin

50

180-ohm-Resistor
or Jumper

Connector
Pin

Connector
Pin

180-ohm-Resistor
or Jumper

Connector
Pin

28

8

28

8

29

9

29

9

26

6

26

6

27

7

27

7

46

4

46

4

47

5

47

5

44

2

44

2

45

3

45

3

42

24

42

24

43

25

43

25

38

22

38

39

23

39

34

20

34

35

21

35

36

18

36

37

19

37

40

12

40

41

13

41

22
1)

23
20

1)

21
18

1)

19
12

1)

13

10

48

16

11

49

50

30

15

30

15 / 49

31

16

31

14 / 48

10
2)

11

14
6ES5 760–0AA11
Connector
Pin

180-ohm-Resistor
or Jumper

50
Connector
Pin

5

6

12

22

1)100 ohms
2)200 ohms
6ES5 760–1AA11

6ES5 760–0AB11

Figure 7-16

7-22

Pin Assignments of the 760 Terminator

System Manual
C79000-G8576-C199-06

8

Digital Input/Output Modules

Described in this chapter are the installation, wiring and operation of digital
input modules and digital output modules. The 432 digital input module and
the 482 digital input/output module have special features. These are
discussed in separate sections. The technical specifications and front
connector assignments for the individual modules are shown at the end of
this chapter.

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Description

Page

8.1

Technical Description

8-2

8.2

Installation and Startup

8-14

8.3

Common Technical Specifications

8-28

8.4

Specification Sheets for the Modules

8-30

8-1

Digital Input/Output Modules

8.1

Technical Description
The description below applies to the following modules:

Type of Modules

Inputs/Outputs

Input/Output
C
Current
t

Isolation/ Groups *)

Number

Rated Voltage

32
32
16
32
32
16
16
8

24 V DC
24 V DC
24 to 60 V DC
24 V DC/alarm
5 to 15 V DC
24 to 60 V AC
115 to 230 V AC
115 to 230 V AC

8.5 mA
7.0 mA
4.5 to 7.5 mA
8.5 mA
1.3 mA
15 to 25 mA
15 to 25 mA
15 to 25 mA

no
yes
yes
yes
yes
yes
yes
yes

–
1
16
4
1
2
2
8

32
32
16
16
16
16
8
16
16
16

24 V DC
24 V DC
24 V DC
24 V DC
24 to 60 V AC
115 to 230 V AC
115 to 230 V AC
24 to 60 V DC
60 V relay
250 V AC relay

0.5 A
0.5 A
2.0 A
2.0 A
2.0 A
2.0 A
2.0 A
0.5 A
0.5 A
5A

no
yes
yes
yes
yes
yes
yes
yes
yes
yes

–
1
16
1
2
2
8
16
16
2

24 V DC

8.5 mA (inputs)
0.5 A (outputs)

yes

1

Digital input modules
6ES5 420-4UA13/14
6ES5 430-4UA13/14
6ES5 431-4UA12
6ES5 432-4UA12
6ES5 434-4UA12
6ES5 435-4UA12
6ES5 436-4UA12
6ES5 436-4UB12
Digital output modules
6ES5 441-4UA13/14
6ES5 451-4UA13/14
6ES5 453-4UA12
6ES5 454-4UA13/14
6ES5 455-4UA12
6ES5 456-4UA12
6ES5 456-4UB12
6ES5 457-4UA12
6ES5 458-4UA12
6ES5 458-4UC11

Digital input/output modules
6ES5 482-4UA11

*)

16 inputs and
16 outputs or
24 inputs and
8 outputs

All inputs and outputs having a common 0 V ground form a group.

Technical specifications which are common to all modules are given in
Section 8.3. The special technical specifications for all modules can be found
in Section 8.4.

I/O Modules

8-2

Digital input and digital output modules are I/O modules which allow the
processing of widely differing process signals with the S5-135U/155U
programmable controller. They can also be used via an adapter casing in the
S5-115U PLC.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Digital Input
Modules

A digital input module converts the process signals to the internal signal
level in the module. Interference is suppressed by the input circuitry, and the
logic states at the inputs are indicated with LEDs on the front strip of the
module. With most digital input modules (except the 420), the signals are
isolated from the central ground point when received. Inputs relating to the
same group are isolated from inputs of another group, but not from each
other.

Digital Output
Modules

The control signals processed in the PLC are output via digital output
modules at a signal level suitable for the actuator, e.g. contactor, solenoid
valve, etc. For the voltages and currents required in the process, modules
with appropriate output circuitry are available.
With most digital output modules (except the 441), the signals are isolated
from the central ground point when relayed to the outputs. Outputs relating to
the same group are isolated from outputs of another group, but not from each
other.

BASP

If a digital output module receives a “command output inhibit” (BASP, cf.
Programming Guide and Chapter 4) from the CPU, the outputs are set to
zero.
When the supply voltage of the central controller or expansion unit has been
switched on or when the CPU is at STOP, the outputs are set to zero.

Signal Output,
Short-Circuit
Detection

Signal output H+ on digital output modules for direct voltage emits a signal
when a short-circuit to ground (L-) or overcurrent has been detected at one or
more outputs currently at logic 1. Only short-circuits which are effective for
more than 0.5 to 1 s are detected. Short-circuits are only detected at
connected outputs. The signal outputs are decoupled by diodes. Up to 16
outputs can be connected in parallel. Ensure that isolation is not defeated by
the parallel connection of outputs.
To ensure functioning of the signal output, you must connect terminal 1L+ to
24 V on the 441, 451 and 454 modules. On the 453 and 457 modules, the
floating signal output must be powered separately.

System Manual
C79000-G8576-C199-06

8-3

Digital Input/Output Modules

8.1.1

Design
The modules are designed as plug-in PCBs for central controllers and
expansion units with backplane connector and with a blade connector to
accept a plug-in front connector. The front connector has screw or crimp
terminals and is available separately; you can connect the process signal lines
to it directly.

LED Indicators

Fitted to each module is a strip with green LEDs to indicate the logic states
of inputs or outputs. The LEDs are arranged in bytes and marked bit 0 to 7.
Output modules for direct voltage additionally have red LEDs to indicate
short-circuits between output lines and ground (L-) within a group. Output
modules for alternating voltage have red LEDs to indicate a fuse failure.

Addressing Switch

Fitted on each module is an addressing switch with six, seven or eight
rockers to set the module address.
The modules are protected on both sides by covers.

Addressing Switch
Blade Connector

Front Connector

LEDs
Figure 8-1

8-4

Digital Input Module

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

8.1.2

Function of the Enable Inputs
The digital input/output modules have an enable circuit. You can use the
enable inputs to implement electrical interlocks for certain modules or switch
off individual modules, whilst the PLC is in operation.
This means that:
The module can no longer be addressed by the user program.
All outputs of digital output modules are set to zero.
Modules which are switched off can be removed or inserted during operation.
If this is not necessary, operate the module with the enable input switched
off.

With an Active
Enable Input

On digital input/output modules with DC voltage inputs or outputs, the
enable circuit requires that enable inputs F+ and F- be wired in the front
connector. Enabling is achieved by applying an external voltage to inputs
F+/F-. Modules for AC voltage have a wire jumper in the front connector.
When the front connector is swivelled away from the front strip of the
module, the supply of power to the enable input is interrupted, i.e. the wire
jumper in the front connector is removed; the module is switched off and can
no longer be addressed by the user program.
When the front connector is swivelled away, i.e. the voltage is removed from
the enable inputs, a timeout (QVZ) occurs at the CPU (see the Programming
Guide for the particular CPU).
Apart from the 6ES5 458-4UC11 digital output module, all digital
input/output modules additionally offer the facility for changing the enable
mode. The modules have a jumper accessible from above in the vicinity of
the addressing switch (see Figure 8-2).

Enable Jumper

Figure 8-2

System Manual
C79000-G8576-C199-06

Location of the Enable Jumper

8-5

Digital Input/Output Modules

Jumper inserted:
Jumper open:

Enable input (F+/F-) active (factory setting)
Enable input (F+/F-) switched off

With Enable Input
Switched Off

If removal and insertion of modules during operation is not required, you
must remove the plug-in jumper for changeover of the enable mode. Wiring
of the enable inputs (F+/F-) can then be dispensed with.

Examples of
Functioning of the
Enable Inputs

Almost power-free shutdown of individual subprocesses, i.e. outputs of
various modules can be operated from a common load supply and yet
activated separately.
The load voltage of each individual module can be monitored without
additional circuitry. Any reactions to failure of the load voltage can be
programmed in the QVZ (timeout) organization block.
You must observe the following when configuring systems:
Switching on

At the latest 100 ms after power-up of the PLC, the voltage must be
present at the enable inputs of the I/O modules.

Switching off

When the PLC has been switched off, the voltage at the enable inputs of the I/O modules must still be present as long as voltage is
applied to the CC/EU.

You should observe the following instructions for switching off PLCs and
equipment for supplying power to the enable inputs:
24 V supply for CC/EU and I/Os

a)
I/O Modules

Battery
b)

F+
CC/EU

24V Power Supply
24 V DC

L+

L+

Enable supply from:
a) Battery
b) Terminals for 24 V on the front plate of the power supply

8-6

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Separate or
Common
Shutdown of the
CC/EU and Load
Power Supply

When there is a need to switch off the load power supply separately without
affecting the enabling of modules, there are the following possibilities for
producing the enable voltage. These exist even when the power supply is
used without an additional capacitor and common shutdown.
230 V AC supply for CC/EU and load power supply

b)

a)

I/O Modules

–951

Battery
c)

F+
CC/EU

L+

Power Supply

L+

230V AC
Load Power Supply 24V

Enable supply from:
a) 6ES5 951-4LB11 load power supply
b) Battery
c) Terminals for 24 V on the front plate of the power supply

Common
Shutdown of the
CC/EU and Load
Power Supply with
a 230 V AC Supply

Proper functioning is ensured if the 24 V load power supply has an output
capacitance of at least 4700 mF per 10 A of load current.
Other units (load power supply for 20 or 40 A) which do not meet this
condition can be adapted to this requirement by connecting a 10000 mF/40 V
capacitor in parallel.

I/O Modules

F+
CC/EU
L+
Power Supply
10000µF/
40V

230V AC

Load Power Supply 24V

System Manual
C79000-G8576-C199-06

8-7

Digital Input/Output Modules

8.1.3

Special Features of the 432 Digital Input Module
The 432 digital input module accepts 32 process signals and emits a process
alarm if the logic state at one of its inputs changes.
You can operate the module in the following modes:

Modes
without process alarm (“normal” digital input module)
with initiation of a process alarm via interrupt
with initiation of a process alarm via IB 0 (only in conjunction with
CPU 948)
To operate the module with process alarm via IB 0, you must address it in the
normal (P) area from byte 128 because
the automatic updating of the process image might acknowledge a process
alarm without the system program having detected and interpreted this
alarm;
only modules addressed in the normal (P) area can initiate a process
alarm via IB 0.
Reaction Time

The time for reaction of the module to a process alarm is mainly determined
by the input circuitry. You can set the reaction time to one of the values
0.3 ms, 1 ms or 3 ms with switch S5. Note that the filtering effect decreases
with shorter reaction times, and interference may be received as useful
signals (effect of the line length, see the technical specifications).

Operation without
Process Alarm

To operate the module without process alarm, you can insert it at any slot for
I/O modules and address it in the entire I/O area. If you address it in the area
PB/PY 0 to PB/PY 124, it will be within the automatic updating of the
process image.

Settings on the
Module

Make the following settings on the module to operate it without process
alarm:
Step

Action

1
2

Open jumpers X3 and X4
Set switch rows S1 and S2 to Off
S2

S1

Figure 8-3

0

IR-A

0

Bit 0

1

IR-B

1

Bit 1

2

IR-C

2

Bit 2

3

IR-D

3

Bit 3

4

IR-E

4

Bit 4

5

IR-F

5

Bit 5

:OFF

6

IR-G

6

Bit 6

:ON

7

INT

7

Bit 7

Switch Settings for Operation without Process Alarm

The setting for switch row S3 is arbitrary in this mode.

8-8

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Operation with
Process Alarm via
Interrupt

To operate the 432 digital input module with process alarm via an interrupt,
you must either operate it in the CC where only certain slots have interrupt
lines (see Chapter 4), or in an interrupt-capable EU connected to the CC with
IM 307 - IM 317 interfacing (see also the IM 307 - IM 317 manual). In the
CC, you may only operate the module in this mode at slots with an interrupt
line (interrupt source).
So that the module can initiate a process alarm for a change of logic state, the
alarm must be processed by an alarm routine (alarm OB) in the user program,
with automatic acknowledgement of the alarm. To avoid loss of an alarm, it
must not be possible for the alarm OB to be interrupted by process alarms.
The CPU must process the process alarms with level triggering (see
Programming Guide of the CPU).

Scanning the
Process Inputs

Example:
Program the following operations in the corresponding alarm OB:
L
T
L
T

PW132
FW10
PW134
FW12

(load I/O word)
(transfer flag word)
etc.

Only the flag word may be accessed during the cyclic program.
Accessing the I/O bytes in the process image will result in alarm loss.
Addressing of the module must therefore be above address 127. Double
accessing of I/O bytes, even from different CPUs, is not permissible (alarm
loss).
The four I/O bytes of a module must be scanned successively and in
ascending order. The scanning of byte n inhibits all input circuits of the
module, and the scanning of byte (n + 3) enables them again.

Settings on the
Module

System Manual
C79000-G8576-C199-06

Make the following settings on the module to operate it with a process alarm
via interrupt:

Step

Action

1

Open jumper X4 and close jumper X3.

2

Set the interrupt line at switch row S1: the switch relating to the
desired interrupt line should be set to On. Set all other switches
to Off. You can set the same interrupt line on several modules.

3

Set switch row S2 to Off.

4

Set switch row S3 to choose whether the interrupt is to be initiated with a positive-going (leading) or negative-going (trailing)
edge. The setting of a pair of switches applies to an entire byte.

8-9

Digital Input/Output Modules

S1

: OFF
: ON

0
1
2
3
4
5
6
7

S3

S2
IR-A
IR-B
IR-C
IR-D
IR-E
IR-F
IR-G
INT

0
1
2
3
4
5
6
7

Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7

0
1
2
3
4
5
6
7

}
}
}
}

Byte 3
Byte 2
Byte 1
Byte 0

Process Interrupt via IR-C
Byte 0: Positive-Going Edge
Byte 1: Negative-Going EdgeByte 2: Both Edges
Byte 3: No Process Interrupt

Figure 8-4

Switch Settings for Operation with Process Alarm via Interrupt (Example)

Operation with
Process Alarm
via IB 0

In this mode, a process alarm is initiated via input byte IB 0. This mode is
only possible in conjunction with a CPU 948 in single-processor operation.
To operate the 432 digital input module with process alarm via IB 0, you can
insert it at any I/O slot.
When you use the module in the CC, you must not set any other input
module to address 0 (i.e. neither in the normal (P) nor in the extended (O)
area).
If you use the module in an EU which is addressed in the normal area, you
must not set any other input module in the EU to address 0 in the normal
area.
So that the module can initiate a process alarm for a change of logic state, the
alarm must be processed by an alarm routine (alarm OB) in the user program,
with automatic acknowledgement of the alarm. To avoid loss of an alarm, it
must not be possible for the alarm OB to be interrupted by process alarms.
The CPU must process the process alarms with level triggering (see
Programming Guide of the CPU).

Scanning the
Process Inputs

Example:
Program the following in the alarm OB which you have preset with byte IB 0
and switch S2:
L
T
L
T

8-10

PW128
FW0
PW130
FW2

(load I/O word)
(transfer flag word)
etc.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Only the flag word (FW) may be accessed during the cyclic program.
Accessing the I/O bytes in the process image will result in alarm loss.
Addressing of the module must therefore be above address 127. Double
accessing of I/O bytes, even from different CPUs, is not permissible (alarm
loss).
The four I/O bytes of a module must be scanned successively and in
ascending order. The scanning of byte n inhibits the input circuit of the
module, and the scanning of byte (n + 3) enables them again.

Settings on the
Module

Make the following settings on the module to operate it with a process alarm
via IB 0:
Step

Action

1

Insert jumpers X3 and X4

2

Set switch row S1 to Off.

3

Set bit 0 on switch row S2 to On, and all other switches to Off.

4

Set switch row S3 to choose whether the interrupt is to be initiated with a positive-going (leading) or negative-going (trailing) edge. The setting of a pair of switches applies to an entire
byte.

S1

S3

S2

0

IR-A

0

Bit 0

0

1

IR-B

1

Bit 1

1

2

IR-C

2

Bit 2

2

3

IR-D

3

Bit 3

3

4

IR-E

4

Bit 4

4

5

IR-F

5

Bit 5

5

:OFF

6

IR-G

6

Bit 6

6

:ON

7

INT

7

Bit 7

7

}

}

Byte 3

Byte 2

}

Byte 1

}

Byte 0

Byte 0: Positive-Going Edge
Byte 1: Negative-Going EdgeByte 2: Both Edges
Byte 3: No Process Interrupt

Figure 8-5

Switch Settings for Operation with Process Alarm via IB 0 (Example)

System Manual
C79000-G8576-C199-06

8-11

Digital Input/Output Modules

Using Two or More
432 Digital Input
Modules with
Process Alarm
via IB 0

You can use up to eight 432 digital input modules with process alarm via
IB 0 in one PLC. The modules must all be inserted in the CC or in the same
EU for error-free acknowledgement of address 0. Each module reserves one
bit in IB 0. You must set one module to bit 0 on switch row S2; on the other
modules you must remove jumper X3 and set one of the other bits 2 to 8.
The module you have set to bit 0 is known as the master, and the other
modules are slaves. On the master module, you must additionally set the
number of slave modules on switch row S2. Refer to the labeling on the
module cover.

Using the 432
Digital Input
Module with other
AlarmGenerating
Modules

You can also use the 432 digital input module with process alarm together
with other alarm-generating modules.
To operate the module with process alarm via interrupt, you must observe the
following:
f a process alarm is generated via an interrupt, the I/O words of all 432
digital input modules involved in this process alarm must be read in the
alarm-processing OB; with IPs, the process alarms must be acknowledged
(refer to the manuals of the IPs).
The modules must be inserted at interrupt-capable slots (see Chapter 4).
To operate the module with process alarm via IB 0, you must observe the
following:
You may use up to eight alarm-generating modules.
The modules must all be inserted in the CC or all in the same EU.
You must operate the 432 module as the master. If you use two or more
432 digital input modules with other alarm-generating modules, you must
operate one 432 as the master and all others as slaves.

8.1.4

Special Features of the DI/DQ 482
The DI/DQ 482 digital input/output module is an I/O module which allows
the processing of process signals in conjunction with the IP 257, with the
S5-135U/155U PLC and the EU 185U (see the IP 257 manual). Described in
the following is the operation of the DI/DQ 482 without IP 257.
The DI/DQ 482 has 32 channels which are jointly isolated, i.e. there is no
subdivision into groups in the module. Channels 0.0 to 0.7 are digital outputs,
Channels 2.0 to 3.7 are digital inputs; Channels 1.0 to 1.7 can be optionally
and individually operated as inputs or outputs.

8-12

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Changeover of the
I/O byte

The operation of Channels 1.0 to 1.7 as inputs or outputs merely depends on
the user program. You define the byte as an input with a read access to the
DI/DQ; you define the byte as an output with a write access. The
double-function of the byte also allows the output byte to be read out.
Unused channels should not be wired nor addressed by program. When these
channels are used as inputs, it should be noted that the corresponding bits in
the output register remain at logic 0. This resetting of output registers is
executed automatically after power-up of the PLC or EU.
Note
When at least one of Channels 1.0 to 1.7 is operated as an input, the
connected sensors and the 1L+ terminal must have the same power supply. If
this is not the case, the input voltage acts on the 1L+ terminal. The resultant
supply to the output amplifiers of Channels 0.0 to 1.7 causes currents to be
drawn via the wired input terminal; these currents may assume different
values, depending on the control states of the outputs.

With the DI/DQ 482, you must set slide switch S2 to setting 1 for operation
without the IP 257.

Slide Switch S2

Local Bus Interface
Figure 8-6

System Manual
C79000-G8576-C199-06

Slide Switch S2 on the DI/DQ 482

8-13

Digital Input/Output Modules

8.2

Installation and Startup
This section describes how to prepare digital input/output modules for
installation, and how to install and wire them.

8.2.1

Setting the Module Address
You set the module address on the addressing switch. This also establishes
the necessary assignments between user program and process connection.
The address of the digital input modules (input bytes IB 0 to 255 or 252 for
the DI/DQ 482) and digital output modules (output bytes QB 0 to 255 or 252
for the DI/DQ 482) is the sum of the binary significances established by
depressing the individual rockers in the On setting ( ).
The modules are addressed by the STEP 5 program under their parameters
(byte address).

Labeling Field

You can affix the adhesive label with the desired module address on a
labeling field under the addressing switch. Suitable labels are supplied with
the CC.
The switch rockers with which the module address (IB n or QB n) is
specified as a decimal number, are marked by dots on the label.
Do not use a pencil to set the addressing switch.

8-14

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

On Setting
(Switch Pressed)

Addressing Switch

Labeling Field for the
Module Address and
Marked Switch Settings

Figure 8-7

2
1

Address Bit

ADB0

Binary Significance
of the Address Bit

ADB1

16

32

8
4
ADB2

ADB3

ADB4

ADB5

ADB6

ADB7

128
64

Address (Decimal)

Labeling of the Addressing Switch (Extract from Module Labeling)

The address byte under which the module is referenced by the STEP 5
program is independent of the slot.

Start Address

For modules with 16 or 32 inputs or outputs, i.e. 2 or 4 bytes, only the lowest
address (start address) is set for the first byte. The addresses of the following
bytes of the same module are decoded on the module.
If, for example, the address 20 is set for a 16-bit module (2 bytes), the
following address 21 is decoded internally and is no longer available. The
next free address would be 22.
For a 32-bit module (4 bytes) with start address 20, addresses 21, 22 and 23
would be decoded internally. The next free address would be 24.
Addresses already assigned must not be set again.
However, digital input and output modules may be given the same address
because they are referenced by different commands in the user program.

System Manual
C79000-G8576-C199-06

8-15

Digital Input/Output Modules

Example
Digital input module with 8 inputs (IB 23) or
digital output module with 8 outputs (QB 23).
The address is the sum of binary significances set with the individual coding
switches:
23 = 1 + 2 + 4 + 16 = 20 + 21 + 22 + 24

On Setting
(Switch Pressed)

2
1
ADB1

ADB0

16

8
4
ADB2

ADB3

ADB4

32
ADB5

ADB6

ADB7

128
64

IB 23 (or QB 23)

Example
Digital input module with 32 inputs (IB 80) or
digital output module with 32 outputs (QB 80).
The address is the sum of binary significances set with the individual coding
switches:
80 = 16 + 64 = 24 + 26

On Setting
(Switch Pressed)

8-16

8
4

2
1

ADB3

ADB1

ADB0

16
ADB4

ADB2

32
ADB5

ADB6

128
64
ADB7

IB 80 (or QB 80)

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

The following table is an overview of settings for addressing digital
input/output modules.

128
64
32
16

Significance

Byte Address

1
2
4
8
0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53 54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93

94

95

96

97

98

99 100 101 102 103 104 105 106 107 108 109 110 111

112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127
128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143
144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159
160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175

1)

176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191
192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207
208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223
224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239
240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
8 Channels x
16 Channels x
32 Channels x

x

x
x

x

x
x
x

x

x
x

x

x
x
x

x

x
x

x

x
x
x

x

x
x

x

1) Address range for digital input and digital output modules
whose signals are not routed via the process image.

Significance

System Manual
C79000-G8576-C199-06

128
64
32
16
8
4
2
1

Switch Setting
On

8-17

Digital Input/Output Modules

8.2.2

Removing and Inserting Modules

!

Warning
When removing and inserting the front connector during operation,
hazardous voltages of more than 25 V AC or 60 V DC may be present at the
module pins. When this is the case at the front connector, live modules may
only be replaced by electrical specialists or trained personnel in such a way
that the module pins are not touched. During operation, the front connector
and module must not be removed or inserted without the enable jumper or
active enable circuit.

Install a digital input/output module as follows:

8-18

Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and out.

2

Insert the module at the desired slot in the subrack and push it
back in the guides.

3

Latch the module by rotating the locking pin by 90° at the
lower end of the module.

4

Engage the front connector on the support pin of the module
and swivel it up. The width of the support pin also provides
keying to prevent front connectors from being fitted to the
wrong modules (e.g. 230 V AC front connector on 24 V DC
modules).

5

Tighten the screw in the upper part of the front connector.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Remove a digital input/output module as follows:
Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and out.

2

Slacken the screw in the upper part of the front connector.
This causes the front connector to be pressed out of the female
connector of the module. Contacts F+ and F- of the enable input at the upper end of the front connector are thus opened first.

3

Swing the front connector out and lift it away from the support
pin of the module.

4

Release the module, if necessary, by rotating the locking pin by
90o. You can pull the module out of the subrack with a grip
which swivels outwards.

6

Module
1

Front Connector

5
3
Figure 8-8
1
2
3
4
5
6

Wiring

System Manual
C79000-G8576-C199-06

2

4

Support Mount
Support Pin

Module with Front Connector

Screw
Locking pin
Support mount
Support pin
Grip
Backplane connector

Comply with VDE Specifications 0100 and 0160 to carry out the wiring of
the supply and signal lines which are to be connected to the programmable
controllers and front connectors of the modules. Detailed information on the
supply of power, cabinet assembly, cabinet ventilation, cabinet wiring and
protective measures can be found in Chapter 3.

8-19

Digital Input/Output Modules

8.2.3

Marking of Modules
For the marking of modules and front connectors, a set of labels is supplied
with the modules for the labeling, and a set of labels with the addresses is
supplied with the central controller. Figure 8-9 shows the locations of the
labels. The self-adhesive address label is pre-printed. You can mark the strips
to identify the signal line terminals.
1

Figure 8-9
1

2

3
4
5

8-20

2 4

1

5

3

Marking and Labeling of Modules

Address label with the module address (output byte QB n or input byte IB n) under
which the module is addressed by the STEP 5 program (address labels are supplied
with the PLC), and for marking the addressing switch settings
Labeling strip with the product designation which is color-coded to distinguish
between the various module types, as well as fields to mark the version and for
user-related labeling of channels.
Color codes:
Digital inputs for DC voltage
blue
Digital inputs for AC voltage
red
Digital outputs for DC voltage
green
Digital outputs for AC voltage
orange
Update the version when replacing modules!
Label with module address and marking of the required settings for the addressing
switch
Labeling strip for terminal designations or connection diagrams for the front connector
Name plate

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

8.2.4

Connecting the Signal Lines
The modules have 20 or 42-way blade connectors with contact blades
measuring 2.4 x 0.8 mm. Front connectors for 20 and 40 mm mounting width
with crimp connection and 40 mm mounting width with screw connection are
provided to connect the signal lines (screwdriver blade width: 3.5 mm,
maximum torque: 0.8 Nm).
Use stranded conductor to facilitate handling of the front connector.
When the crimp contact is inserted in the plastic body of the front connector,
a click can clearly be heard. This indicates that the contact is engaged. For
jumpering or to correct the wiring, you can remove the contacts with a
releasing tool (see ordering information) without having to pull out the front
connector.
Ferrules are not required for screw connections, because the screw terminals
are provided with wire protection. You can use ferrules of 7 mm in length to
DIN 46228. The maximum terminal area is 2 x 2.5 mm2.

Terminal
Type

Crimp
Connection

Screw
Connection

Connector
Type 6ES5
497497

Max.
No of
No.
ConCon
tacts

Cross-Sec. of
Signal or Supply Conductor

4UA12

42

0.5 to 1.5 mm2

4UA22

42

4UA42

Front
Connector
Width

Module 6ES5-

5 to 60 V DC

20 mm

420. 430.
431, 432.
434, 441,
451, 454-14,
458

0.5 to 1.5 mm2

5 to 60 V DC

40 mm

453, 454, 457

20

0.5 to 1.5 mm2

24 to 230 V AC

40 mm

435, 436, 455, 456

4UB12
4UB32

42

0.5 to
2 x 2.5 mm2

5 to 60 V DC

40 mm
20 mm

420. 430. 431, 432. 434, 441,
451, 453, 454, 457, 458

4UB22

25

0.5 to
2 x 2.5 mm2

5 to 60 V DC

40 mm

454

4UB42

20

0.5 to
2 x 2.5 mm2

24 to 230 V AC

40 mm

435, 436, 455, 456

!

System Manual
C79000-G8576-C199-06

Connector for
Rated Voltage

For Operation
With Fan

Without Fan
–

420. 430.
431, 432.
434, 441,
451, 453,
454, 457,
458

Caution
Only extra-low voltage v 60 V DC with safety separation from system
voltage may be used for the 24 V DC supply and for the 24 V DC input
signals. Safety separation can be implemented to the requirements of,
amongst other sources, VDE 0100 Part 410/HD 384-4-41/IEC 364-4-41
(as functional extra-low voltage with safety separation) or
VDE 0805/EN 60950/IEC 950 (as safety extra-low voltage SELV) or
VDE 0106 Part 101.

8-21

Digital Input/Output Modules

8.2.5

Connection of Outputs in Parallel and Switching On the Load via
a Contact

!
Digital Output
Modules for DC
Voltage

Caution
The parallel connection of outputs to increase the load is not permissible.

Outputs of modules with the same load voltage supply may be connected in
parallel without additional circuitry.
An external diode must be fitted to the output lines of modules fed from
different load voltage supplies (exception: 453, 457). In the case of different
logic states of the two outputs, the maximum permissible output current
corresponds to that of the lower stage.
The contact (e.g. for manual operation) is connected to one of the two L+.

Manual
2L+

A1

A2

Output 1

1L+
Output 2
1L–

2L–
Load

Figure 8-10

Parallel Connection of Outputs for DC Voltage Outputs

Digital Output
Modules for AC
Voltage

8-22

Outputs can be connected in parallel without increasing the load if they are
connected to the same phase (L) and the same neutral conductor (N).
The load must be at least 50 mA per output to keep to the permissible
residual voltage at logic 0. The maximum switching current of 2 A per load
must not be exceeded.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

The load can also be switched via a contact.

Phase (L)

ELR

Manual

ELR = Electronic Load Relay

ELR

Output 2

Output 1

Load
Neutral (N)
Figure 8-11

Parallel Connection of Outputs for AC Voltage Outputs

Connection of
Input/Output
Modules to Two
Power Supply Units

Given here are two examples of the feeding of inputs and outputs of different
modules from two power supply units.
With non-floating input/output modules, the negative terminals (L-) of the
power supply units are connected to reference potential (PE) because the
inputs of the 420 module are referred to chassis ground.

Central Ground Point
or Rack or the CC/EU
Reference Potential

DI
e.g. 420
I I

0V

0V

DI
e.g. 420
I I I

I I

0V
DQ
e.g. 441
L QQQ L Q Q
+
+

I I

L
+

DQ
e.g. 441
Q
L Q
+

0V
Q

and Connection
to Protective
Conductor (PE)

2L+
1L+

AC
230V

AC
230V

+
_

DC
24V

Figure 8-12

+
_

L

_

DC
24V

Feeding of Non-Floating Input/Output Modules from Two Power Supply Units

System Manual
C79000-G8576-C199-06

8-23

Digital Input/Output Modules

With isolated input/output modules the supply voltage is applied separately
to the individual modules.

Reference Potential

e.g.430 DI
LI I
+

0V
L
_

e.g.431

DI

I L
_ I L_ I L_

e.g.451

0V

DQ

L Q Q Q L_ L Q Q
+
+

I L_ I L_

0V

e.g.453

DQ

LQ LQ
+
+

0V
LQ LQ
+
+

and Connection
to Protective
Conductor (PE)

1L _
1L+
2L+
_
2L

AC
230V

+

DC
24V

Figure 8-13

_

AC
230V

+
_

DC
24V

Feeding of Isolated Input/Output Modules from Two Power Supply Units

With isolated modules, the inputs or outputs can be fed from two separate
power supply units in isolation groups created by the internal distribution in
the module.
Note that when inputs or outputs from two isolated groups are connected to
one power supply unit, isolation between the groups is defeated.

8.2.6

Short-Circuit Protection and Fusing
With digital output modules for DC voltage, fuses are provided on the
module, in addition to the electronic short-circuit protection, for the wiring
cables and to protect the module. The fuses also provide protection against
reversal of supply voltage connections and can only be replaced at the
factory.
The electronic short-circuit protection guaranteed in the technical
specifications applies to a resistance which is lower than the specified,
maximum permissible line resistance.
In the event of a short-circuit, two to three-times the rated output current
flows briefly at the output before the switched electronic short-circuit
protection becomes effective. When selecting the load power supply units,
therefore, allow for the increased short-circuit current as well as all
connected output loads (observe the coincidence factor). With unregulated
load power supplies, this overcurrent is generally ensured. With regulated
load power supplies, especially at low output power levels (up to 20 A), you
must allow for a corresponding overcurrent.

8-24

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

8.2.7

Arc-Quenching for Inductive Loads

Note
Digital output modules have integrated circuits on the module to quench
inductive loads (refer to the technical specifications of the output modules).

Exception: The 458 digital output module allows the switching of inductive
loads with contact protection submodules.
The integrated circuits on the modules for quenching inductive loads are
disabled if the load circuits are interrupted, either
operationally by contacts and switches,
or by fuses in the event of a fault.
This can result in excessive, inductive breaking voltages which put fault-free
operation at risk.
You can prevent this with additional, external quenching circuitry for the
inductive loads.

DC Voltage

L+

Digital Output

AC Voltage

L

Digital Output

ELR

ELR

ELR

Contact, Switch
Contactor,
Solenoid Valve, etc.

L–

N

Quenching Device
(Diode, Zener Diode, R/C Network or Varistor)

Figure 8-14

Quenching of Inductive Loads when the Load Circuit is Opened

System Manual
C79000-G8576-C199-06

8-25

Digital Input/Output Modules

External
Quenching
Circuitry

External quenching circuitry is needed when
the switching frequency of an output is greater than that specified in the
technical specifications (thermal stress of the integrated circuit for
quenching inductive loads);
disconnection of output lines can be expected;
disconnection of the supply line can be expected.
When selecting or designing the quenching circuitry, the technical
specifications for the digital output should be taken into account. These are:
The permissible overvoltage for the supply voltage (see Section 8.3
“Common Technical Specifications”)
Inductive breaking voltage of the output (see Section 8.4 “Description of
Individual Modules”)

Switching
Frequency of the
Output is Higher
than the
Permissible Value

An external quenching circuit only provides thermal relief if its quenching
voltage is lower than the breaking voltage specified for the module, allowing
for unfavorable supply voltage conditions.
Example:

453 digital output

Inductive breaking voltage L+ - 47 V (tech. specifications)
Max. supply voltage L+ = 30 V
Quenching voltage referred to L- (0 V ground) is - 17 V
The quenching device must be rated at approximately 15 V and the switched
load current, e.g. 1 A.

Disconnecting the
Load Circuit

A quenching device rated for the induced breaking current must be provided
at the load (see Figure 8-14).
The quenching voltage at the load is independent of the module. The
quenching devices must also ensure that the overvoltages at the switch and in
the wiring do not exceed the disturbance voltage and voltage hazard limits
permissible to VDE/IEC.

Disconnecting the
Supply Line L+
and L

The following applies to digital outputs for DC voltage:
In general, load power supplies should be switched on the primary side to
utilize the low-resistance secondary winding and smoothing capacitors of the
power supply for energy compensation in the dropping of inductive loads.
The load power supply switch should only be considered as a circuit breaker.

Switched-Through
Outputs

With switched-through digital outputs and disconnection of the supply line
L+, the output current is maintained during the quenching time by capacitors
and the reverse voltage protection diode on the module. This severe electrical
stress of the module should be avoided during operations, because it can
result in a fault in the long term.

8-26

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Two-Wire Switches

With two-wire switches and AC voltage outputs:
Disconnection of the supply voltage during operation is not permissible
without additional protective circuitry. Quenching of the inductive load is
achieved here via the load power supply unit or system. Since, as two-wire
switches, the outputs have no L-/N (0 V ground) terminal, the inductive load
cannot be quenched on the module when the supply line is disconnected.
With the 453 and 457 modules using two-wire switches, the overvoltages can
result in destruction of the module.
If the load voltage must be switched for safety reasons, you must provide
external quenching circuitry at each inductive load (see Figure 8-15).
Instead, with the 453 and 457 modules using two-wire switches, you can
insert a quenching device (diode) with adequate ratings after contact K from
the L+ line to L-.

DC Voltage
Common Diode
only on 453/457

AC Voltage
L+

L

Contact, Switch

Digital Output

Digital Output

ELR

ELR

ELR

Contactor,
Solenoid Valve, etc.

L–

N
Quenching Device
(Diode, Zener Diode, R/C Network or Varistor)

Figure 8-15

Quenching of Inductive Loads when Switching the Supply Line L+ and L

System Manual
C79000-G8576-C199-06

8-27

Digital Input/Output Modules

8.3

Common Technical Specifications
Important for the USA and Canada
The following approvals have been obtained for all the modules listed in this
chapter:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972
CSA Certification Mark
Canadian Standard Association (CSA) to
Standard C 22.2 No. 142, Report LR 63533

Valid safety specifications

VDE 0160

Class of protection

I

Degree of protection

IP 20 to IEC 529/DIN 40050 when empty slots are covered
by dummy front plates

Climatic ambient conditions
Operation in equipment with fan

0 to 55 C

Operation in equipment without fan (module clearance: 40 mm)

0 to 55 C
Supply air measured at lower inlet of power supply; for a
cabinet assembly, note that the removable power dissipation
depends on the cabinet design, its ambient temperature and
arrangement of equipment.

Transportation and storage temperature

–40 to 70 C

Temperature variation
in operation
transportation and storage

10 K/h max.
20 K/h max.
(When delivered under 0 oC, allow 3 h min. settling time on
account of possible condensation)

Relative humidity
in operation
transportation and storage

95 % max. at 25 oC, no condensation
95 % max. at 25 oC, no condensation

Site altitude
in operation
transportation and storage

–1000 m to +1500 m
–1000 m to +3500 m

Polluants
S02
H2S

0.5 ppm max. (rel. humidity under 60 %)
0.1 ppm max. (rel. humidity under 60 %)

Mechanical ambient conditions
Vibration in operation

10 to 58 Hz (const. amplitude 0.15 mm)
58 to 500 Hz (const. acceleration 2 g)

Mechanical requirements

Installation in stationary equipment which is not free from
vibrations; installation on ships and vehicles, allowing for
special installation specifications, but not on the engine

Operand identifiers
for inputs

I = Input

for outputs

Q = Output

Parameters

8-28

0.0 to 255.7

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Terminals
Rated DC voltage of module

L+

Reference potential for DC voltage

L–

Rated AC voltage of module

L

Reference potential for AC voltage

N

Permissible line length for digital output modules

Allow for the line resistance and tolerance of the supply
voltage for the relevant output current.

Enable inputs

F+
F–
(Enable voltage according to the rated voltage of the module)

Short-circuit signaling output (only when the shortcircuited output is at logic 1)

H+
(Supply for 1L+, referred to L- of the module)

Max. permissible supply voltage
for rated voltage 24 V DC (L+/L-) 1)
for rated voltage 60 V DC (L+/L-) 1)
for rated voltage 115 V/230 V AC (L/N)

36 V DC for 100 ms
90 V DC for 100 ms
276 V AC for 100 ms

Supply voltage ripple Vpp referred to rated DC voltage

15 % max. 2)

Interference suppression at digital inputs

v 1.5 ms 3)

Interference pulse length at digital outputs

v 1.5 ms 3) 4)

Circuitry for inductive loads:

Protective devices to limit the breaking voltage are provided
on the digital output modules. Additional protective circuitry for the load is only required in exceptional cases.
Exception: 458 digital output module

Switching of capacitive loads:

50 nF max. at full load

Safety tests
Surge voltage test to IEC 255-4

DC: Input/output to L-: Vp = 1 kV, 1.2/50 ms
AC: Input/output to L-: Vp = 2.5 kV, 1.2/50 ms

RFI test to IEC 255-4

DC: Input/output to L-: Vp = 1 kV, 1 MHz
AC: Input/output to L-: Vp = 2.5 kV, 1 MHz

Safety test for the -4UA13/-4UA14 modules

1)
2)
3)
4)

Immunity from conducted interference on signal
line

1 kV to IEC 801-4 (burst) for -4UA13 module
2 kV to IEC 801-4 (burst) for -4UA14 module

Immunity from discharge of static electricity

8 kV discharge in air to IEC 801-2, equivalent to 4 kV contact discharge (see Chap. 3 and page 4-16)
6 kV contact discharge for -4UA14 module

Supply and signal voltages must be produced as functional voltage with safety separation.
The supply voltage range values are limit values. They include ripple.
If not otherwise specified
Must be bridged by the signal receiver

System Manual
C79000-G8576-C199-06

8-29

Digital Input/Output Modules

8.4

Specification Sheets for the Modules
The common technical specifications are given in Section 8.3.

8.4.1

6ES5 420-4UA13/4UA14 Digital Input Module
–4UA13

Rated input voltage

24 V DC

Number of inputs

32

Isolation

no

Input voltage
for logic 0
for logic 1

–33 to 5 V
13 to 33 V

Rated input current

8.5 mA

Input frequency

100 Hz max.

Delay time

3 ms typical (1.4 to 5 ms)

Input resistance

2.8 kilohms typical

Coincidence factor (total load capability)

100 %

Permissible line length

600 m max., unshielded;
1000 m max., shielded

–4UA14

Power supply
Digital section from system bus

5 V, 80 mA typical

Supply voltage for 2-wire BERO

22 to 33 V

Power dissipation (rated operation)

7.0 W

5 V, 30 mA typical

Enable input (F+/F–)
Rated input voltage

24 V DC

Input voltage
for logic 0
for logic 1

–33 to 5 V
13 to 33 V

Rated input current

5 mA

Permissible line length

200 m max.

Mechanical specifications
Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.4 kg

8-30

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of
Process Signal
Lines

Front Strip
LED

Block Diagram of
Module Inputs

Pin
x20

L+

1I0.0
1I0.1
1I0.2
1I0.3
1I0.4
1I0.5
1I0.6
1I0.7
1I1.0
1I1.1
1I1.2
1I1.3
1I1.4
1I1.5
1I1.6
1I1.7

1I2.0
1I2.1
1I2.2
1I2.3
1I2.4
1I2.5
1I2.6
1I2.7
1I3.0
1I3.1
1I3.2
1I3.3
1I3.4
1I3.5
1I3.6
1I3.7

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

t

1)

(1) I 1.5

2)
2)

Input 5 (5th bit);
0 to 7 possible

t

g
g
g
g
g
g
g
g

t

Address of input byte
(1st byte);
0 to 255 possible
t

I = Input

t

1st group (not specified
in the address)

2)

g
g
g
g
g
g
g
g

Data Memory and S5 Bus Control

F+

Example of connection designation
for an input:

t
2)
2)
2)
2)

t

g
g
g
g
g
g
g
g

t
2)

t

g
g
g
g
g
g
g
g

t
M

ext.

M

ext.

(L–)
g
=
Green LED (status indicator)
F+
=
Enable input
Connect L- of the power supply unit to the reference potential (PE).
1)

2)

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. Even when this terminal is connected to input voltages, the clearances in air
and leakage paths remain adequate to UL, CSA and VDE.

System Manual
C79000-G8576-C199-06

8-31

Digital Input/Output Modules

8.4.2

6ES5 430-4UA13/4UA14 Digital Input Module

–4UA13
Rated input voltage

24 V DC

Number of inputs

32

Isolation

Yes, 1 group with 32 inputs

Input voltage
for logic 0
for logic 1 1)

–3 to 7 V
13 to 33 V

Rated input current

7.0 mA

Input frequency

100 Hz max.

Delay time

4 ms typical (2.5 to 6.5 ms)

Input resistance

3.3 kilohms typical

Coincidence factor (total load capability)

100 %

Permissible line length

600 m max., unshielded;
1000 m max., shielded

–4UA14

–33 to 7 V
13 to 33 V

3 ms typical (1.4 to 5.0 ms)

Power supply
Digital section from system bus

5 V, 100 mA typical

5 V, 30 mA typical

Supply voltage for 2-wire BERO

22 to 33 V

Supply voltage L+/L–

24 V (20 to 30 V)

L+ to terminal 3 not required

Current consumption from L+/L–

Approx. 100 mA

L+ not required

Power dissipation (rated operation)

8.3 W

5.6 W

Enable input (F+/F–)
Rated input voltage

24 V DC

Input voltage
for logic 0
for logic 1

–33 to 5 V
13 to 33 V

Rated input current

5 mA

Permissible line length

200 m max.

Voltage test to VDE 0160

Between group and ground point: 1250 V AC

Mechanical specifications
Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.4 kg

1)

8-32

Polarity reversal for up to 8 inputs per module is permissible.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

F–
L+ 4)
1I0.0
1I0.1
1I0.2
1I0.3
1I0.4
1I0.5
1I0.6
1I0.7

L+

1I1.0
1I1.1
1I1.2
1I1.3
1I1.4
1I1.5
1I1.6
1I1.7
L–

1I2.0
1I2.1
1I2.2
1I2.3
1I2.4
1I2.5
1I2.6
1I2.7
1I3.0
1I3.1
1I3.2
1I3.3
1I3.4
1I3.5
1I3.6
1I3.7
L–
3)

g
=
F+/F- =
1)

2)
3)
4)

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

LED

Block Diagram of
Module Inputs

Pin

Example of connection designation
for an input:
x20

t

1)

Input 5 (5th bit);
0 to 7 possible

L+

t

g
g
g
g
g
g
g
g

(1) I 3.5

Address of input byte
(3rd byte);
0 to 255 possible
I = Input
t

1st group (not specified
in the address)

2)

t

g
g
g
g
g
g
g

Data Memory and S5 Bus Control

F+

L+
L–

Front Strip

t
g
2)

L–

2)
2)

t

g
g
g
g
g
g
g
g

t
2)

g
g
g
g
g
g
g
g

t

Isolation

Connection of
Process Signal
Lines

t
L–

Shield

Green LED (status indicator)
Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. Even when this terminal is connected to input voltages, the clearances in air and
leakage paths remain adequate to UL, CSA and VDE.
By connecting L- to pin 42, a leading and trailing connection to ground is established on the module when it is plugged in
and removed.
L+ to terminal 3 is not required for -4UA14.

System Manual
C79000-G8576-C199-06

8-33

Digital Input/Output Modules

8.4.3

6ES5 431-4UA12 Digital Input Module

Rated input voltage

24 to 60 V DC

Number of inputs

16

Isolation

Yes, 16 inputs

Input voltage
for logic 0
for logic 1

–33 to 8 V
13 to 72 V

Rated input current

4.5 to 7.5 mA (24 to 60 V DC)

Input frequency

100 Hz max.

Delay time

3 ms typical (1.4 to 5 ms)

Coincidence factor (total load capability)

100 %

Permissible line length

400 m max. unshielded;
1000 m max. shielded

Power supply
Digital section from system bus

5 V, 90 mA typical

Supply voltage for 2-wire BERO

22 to 72 V

Power dissipation (rated operation)

2.2 to 7.7 W (24 to 60 V)

Enable input (F+/F–)
Rated input voltage

24 to 60 V DC

Input voltage
for logic 0
for logic 1

–72 to 8 V
13 to 72 V

Rated input current

5 mA (at 48 V DC)

Permissible line length

200 m max.

Voltage test to VDE 0160

Between two groups: 1250 V AC
Between group and ground point: 1250 V AC

Mechanical specifications
Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.4 kg

8-34

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

L+
L–

F+
F–

1L+
1L–
2L+
2L–
3L+
3L–
4L+
4L–

1I0.0
– 1I0.0
+ 2I0.1
– 2I0.1
+ 3I0.2
– 3I0.2
+ 4I0.3
– 4I0.3
+

5L+
5L–
6L+
6L–
7L+
7L–
8L+
8L–

5I0.4
– 5l0.4
+ 6I0.5
– 6I0.5
+ 7I0.6
– 7I0.6
+ 8I0.7
– 8I0.7
+

9L+
9L–
10L+
10L–
11L+
11L–
12L+
12L–
13L+
13L–
14L+
14L–
15L+
15L–
16L+
16L–

g
=
F+/F- =
1)

2)
3)

9I1.0
– 9I1.0
+ 10I1.1
–10I1.1
+ 11I1.2
–11I1.2
+ 12I1.3
–12I1.3
+

+
–
+
–
+
–
+
–

13I1.4
13I1.4
14I1.5
14I1.5
15I1.6
15I1.6
16I1.7
16I1.7

Front Strip
LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Block Diagram of
Module Inputs

Pin

Example of connection designation
for an input:
x20

t

1)

2)

Input 7 (7th bit);
0 to 7 possible

t

g

(8) I 0.7

g

Address of input byte
(byte 0);
0 to 255 possible

g
g

t

I = Input

2)

8th group (not specified
in the address)

t

g
g
g

Data Memory and S5 Bus Control

Connection of
Process Signal
Lines

t

g
2)
3)
3)
2)

g

t

g
g
t

g
2)

t

g
g
g

t

g
2)

Shield

Green LED (status indicator)
Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. When this terminal is connected to the input voltages, the clearances in air and
leakage paths are no longer adequate to UL and CSA, but comply with VDE.
The terminal is not connected internally. When this terminal is connected to the input voltages, the clearances in the air and
leakage paths remain adequate to UL, CSA and VDE.

System Manual
C79000-G8576-C199-06

8-35

Digital Input/Output Modules

8.4.4

6ES5 432-4UA12 Digital Input Module

Rated input voltage

24 V DC

Number of inputs

32

Isolation

Yes, 4 groups of 8 inputs

Input voltage
for logic 0
for logic 1

–33 to 5 V
13 to 33 V

Rated input current

8.5 mA

Input frequency

100 Hz / 300 Hz / 1 kHz max.

Delay time 1)

3 ms / 1 ms / 0.3 ms typical
(1.5 to 4.8 ms/0.5 to 1.6 ms/0.15 to 0.48 ms)

Input resistance

2.8 kilohms typical

Coincidence factor (total load capability)

100 %

Permissible line length

600 m max. unshielded (3 ms);
200 m max. unshielded (1 ms);
50 m max. unshielded (0.3 ms)

Power supply
Digital section from system bus

5 V, 200 mA typical

Supply voltage for 2-wire BERO

22 to 33 V

Power dissipation (rated operation)

7.5 W

Enable input (F+/F–)
Rated input voltage

24 V DC

Input voltage
for logic 0
for logic 1

–33 to 5 V
13 to 33 V

Rated input current

5 mA

Permissible line length

200 m max.

Voltage test to VDE 0160

Between two groups: 1250 V AC
Between group and ground point: 1250 V AC

Mechanical specifications
Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.55 kg

1)

8-36

Selectable in bytes with switch S5

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

L+
L–

1L+

F+
F–
1I0.0
1I0.1
1I0.2
1I0.3
1I0.4
1I0.5
1I0.6
1I0.7

1L–
2L+

2I1.0
2I1.1
2I1.2
2I1.3
2I1.4
2I1.5
2I1.6
2I1.7

2L–

3L+

3L–
4L+

4L–

3I2.0
3I2.1
3I2.2
3I2.3
3I2.4
3I2.5
3I2.6
3I2.7
4I3.0
4I3.1
4I3.2
4I3.3
4I3.4
4I3.5
4I3.6
4I3.7

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Front Strip

Block Diagram of
Module Inputs

LED Pin

Example of connection designation
for an input:
x20

t

1)

3)

Input 5 (5th bit);
0 to 7 possible

t

g
g
g
g
g
g
g
g

(4) I 3.5

Address of input byte
(3rd byte);
0 to 255 possible
t

I = Input

g
g
g
g
g
g
g

t

4th group (not specified in the address)

g

t

Data Memory and S5 Bus Control

Connection of
Process Signal
Lines

3)
4)
3)
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g

t

t
t

t
Shield

g
=
Green LED (status indicator)
F+/F- =
Enable input
1)
Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
2)
Only 128 to 255 permissible with group signal and interrupt.
3)
The terminal is not connected internally. When this terminal isconnected to the input voltages, the clearances in air and
leakage paths are no longer adequate to UL and CSA, but comply with VDE.
4)
The terminal is not connected internally. When this terminal is connected to the input voltages, the clearances in air and
leakage paths remain adequate to UL, CSA and VDE.

System Manual
C79000-G8576-C199-06

8-37

Digital Input/Output Modules

Labeling for module cover:
Mark the switch settings in the free fields.
X3
Master (on)
Slave (off)

Byte

3 ms

Delay-Time
1 ms
0.3 ms

X4
Group Signal
active (on)
inactive (off)

S5

3
2
1
0

Edge Trigger

S3
S1

3
2
1
0
Byte

Interrupt
IRA
IRB
IRC
IRD
IRE
IRF
IRG
INT

Group Signal
Master submodule (Jumper X3 on)
Data- without 1
bit
Slave Slave

2
Slave

3
Slave

4
Slave

5
Slave

6
Slave

Slave submodule (Jumper X3 off)
7
1.Slave 2.Slave 3.Slave 4.Slave 5.Slave 6.Slave 7.Slave
Slave
o.1
0.2
0.3
0.4
0.5
0.6
0.7

S2

0
1
2
3
4
5
6
7

8-38

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

8.4.5

6ES5 434-4UA12 Digital Input Module

Rated input voltage (LH+)

DC 5 to 15 V

Rated input voltage (L+)

DC 12 to 24 V (NAMUR) 1)

Number of inputs

32

Isolation

Yes, 1 group of 32 inputs

Input voltage TTL:

for logic 0
CMOS:

Rated input current

TTL:
CMOS:
NAMUR:

for logic 1
for logic 0
for logic 1

0 to 0.8 V
2.4 to 5.0 V
0 V to 0.3 x LH+
0.7 V x LH+ to 1 x LH+

for logic 0
for logic 1
for logic 0
for logic 1
for logic 0
for logic 1

–1 mA
0.1 mA or open input
–1 to –3 mA (5 to 15 V)
0.1 to 0.3 mA (5 to 15 V)
v 1.2 mA
w 2.1 mA

Internal resistance

1 kilohm typical

Line resistance

50 ohms max.

Input frequency

100 Hz max.

Delay time
for positive-going edge
for negative-going edge

3 ms typical (1.4 to 5 ms)
3 ms typical (1.4 to 5 ms)

Coincidence factor (total load capability)

100 %

Permissible line length

200 m max. unshielded
600 m max. unshielded

TTL/CMOS
NAMUR

Power supply
Digital section from system bus

5 V, 80 mA typical

Supply voltage L+/L–

24 V (20 to 30 V)

Current consumption at L+/L–

100 mA each

Current consumption at LH+/LH–

150 mA each at 15 V input voltage

Current output from LH+/LH–

120 mA each at 8.5 V sensor supply (NAMUR) 2)

Power dissipation (rated operation)

5.5 W

Enable input (F+/F–)
Rated input voltage

5/ 15/ 24 V DC

Input voltage

–15 to 2 V
4 to 33 V

for logic 0
for logic 1

Rated input current

5 mA

Permissible line length

100 m max.

Voltage test to VDE 0160

Between group and ground point: 1250 V AC

Mechanical specifications

1)
2)

Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.45 kg

NAMUR = Sensor with current output to DIN 19234, Standards Committee for Measurement and Control.
However, the module is not intrinsically safe.
The current consumption from L+/L- increases accordingly.

System Manual
C79000-G8576-C199-06

8-39

Digital Input/Output Modules

Connection for supply voltage,
jumpers and sensor supply in groups of 2 bytes
(16 inputs each)

Byte 0 + 1
Byte
y 2+3

1L+ Terminal 3
2L+ Terminal 24

1LH+ Terminal 12
2LH+ Terminal 33

1LH– Terminal 22
2LH– Terminal 23

NAMUR

Connect to L+
(24 V supply)

Output for sensor
supply

Jumper to L–
Terminal 21

CMOS

open

Connect to 5 to 15 V
supply

open

TTL

open

Connect to 5 V supply

open

Type of
Sensor

The types of sensor can be arbitrarily mixed in groups of 16 inputs.
With CMOS TTL sensors, open inputs are at logic 1 (LED is lit).

8-40

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of NAMUR Sensors

Sensor Supply +/–
TTL
: LH+ = 5V
L– = 0V
CMOS
: LH+ = 5...15V
L– = 0V

NAMUR

.
.
.
.
.
.

.
.
.
.
.

L–

L+
NAMUR

.
.
.
.
.
.

.
.
.
.
.

L–

F+
F–
1L+
1I0.0
1I0.1
1I0.2
1I0.3
1I0.4
1I0.5
1I0.6
1I0.7
1LH+
1I1.0
1I1.1
1I1.2
1I1.3
1I1.4
1I1.5
1I1.6
1I1.7
L–
1LH–
2LH–
2L+
1I2.0
1I2.1
1I2.2
1I2.3
1I2.4
1I2.5
1I2.6
1I2.7
2LH+
1I3.0
1I3.1
1I3.2
1I3.3
1I3.4
1I3.5
1I3.6
1I3.7

Front Strip

Connection of
Process Signal Lines
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

LH+
L–
TTL/CMOS
+_
.
.
.
.
.
.
+
_
LH+
+
_
.
.
.
.
.
NAMUR–
and

+
L– _

F+
F–
Q 1I0.0
1I0.1
1I0.2
1I0.3
1I0.4
1I0.5
1I0.6
Q 1I0.7
Q 1LH+
1I1.0
1I1.1
1I1.2
1I1.3
1I1.4
1I1.5
1I1.6
Q 1I1.7
L–

TIL/CMOS
Sensors

TTL/CMOS Q 1I2.0
+
_
1I2.1
.
1I2.2
connected
.
1I2.3
.
in groups of 16)
1I2.4
.
1I2.5
.
1I2.6
.
+
Q 1I2.7
_
2LH+
LH+
Q 1I3.0
+
_
1I3.1
.
1I3.2
.
1I3.3
.
1I3.4
.
1I3.5
.
1I3.6
Q 1I3.7
+
_
L–
(can be

LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Pin

Block Diagram of
Module Inputs
x20
1)

t

g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g

t

t
t

Data Memory and S5 Bus Control

Connection of
Process Signal
Lines

t
L–

g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g

t

t
t

Isolation

Sensor Supply LH+
from L+ = 24V

L+
L–
L+

Sensors with TTL- and/or
CMOS Outputs

t
L–

Shield

Example of connection designation for an input:
(1) I 3.5
Input 5 (5th bit);
0 to 7 possible

g
=
Green LED (status indicator)
F+/F- =
Enable input
1)
Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.

Address of input byte
(1st byte);
0 to 255 possible
I = Input
1st group (not specified in the address)

System Manual
C79000-G8576-C199-06

8-41

Digital Input/Output Modules

8.4.6

6ES5 435-4UA12 Digital Input Module

Rated input voltage

24 to 60 V AC (47 to 63 Hz)

Number of inputs

16

Isolation

Yes, 2 groups of 8 inputs

Input voltage
for logic 0
for logic 1

0 to 15 V AC
20 to 72 V AC

Rated input current
bei AC 48 V
bei AC 60 V

15 mA typical
20 mA typical

Input current for 2-wire BERO
for logic 0
for logic 1

v 5 mA
w 10 mA

Input frequency

20 Hz max. as pulse train

Delay time
for positive-going edge
for negative-going edge

5 ms typical (2 to 15 ms)
20 ms typical (10 to 25 ms)

Input resistance

3 kilohms typical

Coincidence factor (total load capability)
ventilated
not ventilated

Permissible line length

100 %
75 % at 60 V;
100 % at 35 o C;
100 % at 30 V
600 m max. unshielded
1000 m max. shielded

Power supply
Digital section from system bus

5 V, 100 mA typical

Power dissipation (rated operation)

3.5 W at 24 V, 18.0 W at 60 V

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between two groups: 2000 V AC;
Between group and ground point: 1500 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.55 kg

8-42

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of
Process Signal
Lines
F+
1
F–
2

1I0.1
1I0.2
1I0.3
1I0.4
1I0.5
1I0.6
1I0.7

2N

2N

2L

2I1.0
2I1.1
2I1.2
2I1.3
2I1.4
2I1.5
2I1.6
2I1.7

t

Example of connection designation for
an input:
x20
(2) I 1.2
1)

4

Input 2 (2nd bit);
0 to 7 possible

6

g

t

8

g

t

10

g

t

12

g

t

14

g

t

16

g

t

18

g

t

20

g

t

27

g

t

29

g

t

31

g

t

33

g

t

35

g

37

g

t

39

g

t

41

g

t

Address of input byte
(1st byte);
0 to 255 possible
I = Input
2nd group (not specified
in the address)

25

Data Memory and S5 Bus Control

1I0.0

+5V

Isolation

1N

Block Diagram of
Module Inputs

t

Isolation

1N

Front Strip
LED Pin

Shield

g
=
Green LED (status indicator)
F+/F- =
Enable input (jumper in front connector)
1)
Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.

System Manual
C79000-G8576-C199-06

8-43

Digital Input/Output Modules

8.4.7

6ES5 436-4UA12 Digital Input Module

Rated input voltage

115 to 230 V AC (47 to 63 Hz)

Number of inputs

16

Isolation

Yes, 2 groups of 8 inputs

Input voltage
for logic 0
for logic 1

0 to 60 V AC
90 to 264 V AC

Rated input current
at 115 V AC
at 230 V AC

15 mA typical
25 mA typical
(2-wire-BERO can be connected)

Input frequency

20 Hz max. as pulse train

Delay time
for positive-going edge
for negative-going edge

5 ms typical (2 to 15 ms)
20 ms typical (10 to 25 ms)

Input resistance

10 kilohms typical

Coincidence factor (total load capability)
ventilated
not ventilated

Permissible line length

100 %
75 % at 230 V AC;
100 % at 35 oC;
100 % at 115 V AC
600 m max. unshielded
1000 m max. shielded

Power supply
Digital section from system bus

5 V, 100 mA typical

Power dissipation (rated operation)

3.5 W at 115 V, 17.0 W at 230 V

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between two groups: 2000 V AC;
Between group and ground point: 1500 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.55 kg

8-44

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of
Process Signal
Lines

Front Strip
LED

Block Diagram of
Module Inputs

Example of connection designation for
an input:

Pin
+5V

(1) I 0.4

F+
F–

1
2

1N

1N

4

1L

1I0.0

6

g

t

1I0.1

8

g

t

1I0.2

10

g

t

I = Input

1I0.3

12

g

t

1I0.4

14

g

1st group (not specified in the address)

t

1I0.5

16

g

t

1I0.6

18

g

t

1I0.7

20

g

t

2N

2N

25

2L

2I1.0

27

g

t

2I1.1

29

g

t

2I1.2

31

g

t

2I1.3

33

g

t

2I1.4

35

g

t

2I1.5

37

g

t

2I1.6

39

g

t

2I1.7

41

g

t

x20

t

1)

Input 4 (4th bit);
0 to 7 possible

Data Memory and S5 Bus Control

Isolation

Isolation

Address of input byte
(byte 0);
0 to 255 possible

Shield
g
=
Green LED (status indicator)
F+/F- =
Enable input (jumper in front connector)
1)
Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.

System Manual
C79000-G8576-C199-06

8-45

Digital Input/Output Modules

8.4.8

6ES5 436-4UB12 Digital Input Module

Rated input voltage

115 to 230 V AC (47 to 63 Hz)

Number of inputs

8

Isolation

Yes, 8 inputs

Input voltage
for logic 0
for logic 1

0 to 60 V AC
90 to 264 V AC

Rated input current
at 115 V AC
at 230 V AC

15 mA typical
25 mA typical
(2-wire-BERO can be connected)

Input frequency

20 Hz max. as pulse train

Delay time
for positive-going edge
for negative-going edge

5 ms typical (2 to 15 ms)
20 ms typical (10 to 25 ms)

Input resistance

10 kilohms typical

Coincidence factor (total load capability)

100 %

Permissible line length

600 m max. unshielded
1000 m max. shielded

Power supply
Digital section from system bus

5 V, 80 mA typical

Power dissipation (rated operation)

2.0 W at 115 V, 8.5 W at 230 V

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between two groups: 2000 V AC;
Between group and ground point: 1500 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.5 kg

8-46

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of
Process Signal
Lines

LED

F–

1
2

1N

1N

4

1L

1I0.0

6

2N

2N

8

2L

2I0.1

3N

3N

3L

3I0.2

14

4N

4N

16

4L

4I0.3

18

10

Block Diagram of
Module Inputs

Pin

+5V
t

Example of connection designation for
an input:
x20
1)

Input 5 (5th bit);
0 to 7 possible
g

t

g

Address of input byte
(byte 0);
0 to 255 possible

t

I = Input

12
g

t

g

t

20

5N

5N

5L

5I0.4 27

6N

6N

6L

6I0.5 31

7N

7N

7L

7I0.6 35

8N

8N

8L

8I0.7 39

(6) I 0.5

6th group (not specified in the address)

Data Memory and S5 Bus Control

F+

Front Strip

2)

25
t

g

29
g

t

g

t

g

t

33

37

41

2)

Shield

g
=
Green LED (status indicator)
F+/F- =
Enable input (jumper in front connector)
1)
Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
2)
The terminal is not connected internally. When this terminal is connected to input voltages, the clearances in air and
leakage paths remain adequate to UL, CSA and VDE.

System Manual
C79000-G8576-C199-06

8-47

Digital Input/Output Modules

8.4.9

6ES5 441-4UA13/4UA14 Digital Output Module
–4UA13

Rated supply voltage L+

24 V DC

Number of outputs

32, short-circuit protected 1)

Isolation

no

Range for supply voltage

20 to 30 V DC

Fusing

6.3 A slow,
1 fuse per 8 outputs

–4UA14

7 A, fast, 1 fuse per 8 outputs

Output voltage
for logic 1
for logic 0

L+ -1.5 V min.
3 V max.

Switching current (resistive, inductive load)

5 mA to 0.5 A

Residual current at logic 0

0.5 mA max.

Switching current for lamps

0.22 A max. (5 W)

Switching frequency
with resistive load
with inductive load

100 Hz max.
2 Hz max. at 0.3 A, 0.5 Hz max. at 0.5 A

Breaking voltage (inductive)

Limited to L+ – 47 V

Total switching current

4 A max. per 8 outputs

Coincidence factor (total load capability)
ventilated
not ventilated

100 %
50 %; 100 % up to 35 oC

Permissible line length

400 m max. unshielded

Limited to L+ –55 V

Power supply
Digital section from system bus

5 V, 80 mA typical

Current consumption from L+/L–

24 V, 150 mA typical

24 V, 200 mA typical

Power dissipation (rated operation)

17.0 W

6.4 W

Enable input (F+/F–)
Rated input voltage

24 V DC

Input voltage
for logic 1
for logic 0

13 to 33 V
– 33 to 5 V

Rated input current

5 mA

Permissible line length

200 m max.

Short-circuit monitoring
Indicator for signaling output (H+)

Red LED for every 8 outputs

Output voltage
referred to L– (with feed at 1L+)
for logic 1
for logic 0

1L+ – 5 V min.
3 V max.

Switching current

10 mA max., limited

1L+ –1.5 V min.
3 V max.

Mechanical specifications
Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.45 kg

1)

8-48

Short-circuit protection responds with line resistance v 15 ohms, irrelevant for the –4UA14 .

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

L+
L–

1L+
1Q0.0
1Q0.1
1Q0.2
1Q0.3
1Q0.4
1Q0.5
1Q0.6
1Q0.7
1Q1.0
1Q1.1
1Q1.2
1Q1.3
1Q1.4
1Q1.5
1Q1.6
1Q1.7
H–

L+

H+
2L+
2Q2.0
2Q2.1
2Q2.2
2Q2.3
2Q2.4
2Q2.5
2Q2.6
2Q2.7
2Q3.0
2Q3.1
2Q3.2
2Q3.3
2Q3.4
2Q3.5
2Q3.6
2Q3.7

Front Strip
LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Pin

Block Diagram of
Module Inputs
x20

t
2)

r
g
g
g
g
g
g
g
g
r
g
g
g
g
g
g
g
g

1)

F2
F1

Output 6 (6th bit);
0 to 7 possible
Address of output byte
(2nd byte);
0 to 255 possible
Q = Output
2)

2nd terminal L+ (not
specified in the address)

2)
ShortCircuit
2)

r
g
g
g
g
g
g
g
g
r

Example of connection designation
for an output:
(2) Q 2.6

F4
F3

Data Memory and S5 Bus Control

Connection of
Process Signal
Lines
L+
F+

2)

g
g
g
g
g
g
g
g
Mext.

g
=
Green LED (status indicator)
r
=
Red LED (short-circuit indicator)
F+
=
Enable input, referred to 0 V ground
Connect L- of the power supply unit to the reference potential (PE).
1)
Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
2)
The terminal is not connected internally. When this terminal is connected to the output voltages, the clearances in air
and leakage paths are no longer adequate to UL and CSA, but comply with VDE.

System Manual
C79000-G8576-C199-06

8-49

Digital Input/Output Modules

8.4.10

6ES5 451-4UA13/4UA14 Digital Output Module

Rated supply voltage L+
Number of outputs
Isolation
Range for supply voltage
Fusing

–4UA13
24 V DC
32, short-circuit protected 1)
Yes, 1 group of 32 outputs
20 to 30 V DC
6.3 A slow
1 fuse per 8 outputs

Output voltage
for logic 1
for logic 0

L+ – 1,5 V min.
3 V max.

Switching current
(resistive, inductive load)
Residual current at logic 0

5 mA to 0.5 A
0.5 mA max.

Switching current for lamps
Switching frequency
with resistive load
with inductive load

0.22 A max. (5 W)

Breaking voltage (inductive)
Total switching current

Limited to L+ – 47 V
4 A max. per 8 outputs

Coincidence factor (total load capability)
ventilated
not ventilated

100 %
50 %; 100 % up to 35 oC

7 A fast
1 fuse per 8 outputs

100 Hz max.
2 Hz max. at 0.3 A; 0.5 Hz max. at 0.5 A

Permissible line length
Power supply
Digital section from system bus

400 m max. unshielded

Current consumption from L+/L–
Power dissipation (rated operation)
Enable input (F+/F–),
Rated input voltage

24 V, 150 mA typical
17.0 W

Limited to L+ –55 V

5 V, 80 mA typical
24 V, 200 mA typical
6.4 W

24 V DC

Input voltage
for logic 1
for logic 0

13 to 33 V
– 33 to 5 V

Rated input current
Permissible line length

5 mA
200 m max.

Short-circuit monitoring
Indicator for signaling output (H+)
Output voltage
referred to L– (with feed at 1L+)
for logic 1
for logic 0

–4UA14

Red LED for every 8 outputs

1L+ – 5 V min.
3 V max.

1L+ –1,5 V min.
3 V max.

Switching current

10 mA max. limited

Voltage test to VDE 0160
Mechanical specifications
Dimensions (W x H x D)
Weight

Between group and ground point: 1250 V AC

1)

8-50

20 mm x 255 mm x 195 mm
Approx. 0.45 kg

Short-circuit protection responds with line resistance v 15 ohms, irrelevant for the –4UA14 .

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

L–
H–
L+

g
=
r
=
F+/F- =
1)

2)
3)

F+
1
F–
2
1L+
3
1Q0.0 4
1Q0.1 5
1Q0.2 6
1Q0.3 7
1Q0.4 8
1Q0.5 9
1Q0.6 10
1Q0.7 11
12
1Q1.0 13
1Q1.1 14
1Q1.2 15
1Q1.3 16
1Q1.4 17
1Q1.5 18
1Q1.6 19
1Q1.7 20
21
H+ 22
23
2L+
24
2Q2.0 25
2Q2.1 26
2Q2.2 27
2Q2.3 28
2Q2.4 29
2Q2.5 30
2Q2.6 31
2Q2.7 32
33
2Q3.0 34
2Q3.1 35
2Q3.2 36
2Q3.3 37
2Q3.4 38
2Q3.5 39
2Q3.6 40
2Q3.7 41
L–
42
3)

LED

Block Diagram of
Module Inputs

Pin
x20

t
r
g
g
g
g
g
g
g
g
r
g
g
g
g
g
g
g
g

(1) Q 1.6

1)

F2
F1

Output 6 (6th bit);
0 to 7 possible
Address of output byte
(1st byte);
0 to 255 possible
Q = Output
2)

1st terminal L+ (not
specified in the address)

L–
ShortCircuit
2)

r
g
g
g
g
g
g
g
g
r
g
g
g
g
g
g
g
g

Example of connection designation
for an output:

Data Memory and S5 Bus Control

L+
L–
L+

Front Strip

F4
F3

2)

Isolation

Connection of
Process Signal
Lines

L–
Shield

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. When this terminal is connected to the output voltages, the clearances in air
and leakage paths are no longer adequate to UL and CSA, but comply with VDE.
By connecting L- to pin 42, a leading and trailing connection to 0 V ground is created on the module when it is inserted
and removed.

System Manual
C79000-G8576-C199-06

8-51

Digital Input/Output Modules

8.4.11

6ES5 453-4UA12 Digital Output Module

Rated supply voltage L+
Number of outputs (decoupled via diodes)
Isolation

24 V DC
16, short-circuit protected 1)
Yes, 16 outputs

Range for supply voltage
Fusing
Output voltage
for logic 1:

20 to 30 V DC
16 x 2.5 A, slow
L+ – 2.5 V min.
2.5 V max.
3 V max.
L+ – 3 V min.

for logic 0:

(L+)-Switch
(L–)-Switch
(L+)-Switch
(L–)-Switch

Switching current (resistive, inductive load)

10 mA to 2.0 A 2)

Residual current at logic 0
Switching current for lamps
Switching frequency
with resistive load
with inductive load

1 mA max.
0.45 A max. (10 W)
100 Hz max.
0.2 Hz max. at 1 A; 0.1 Hz at 2 A

Breaking voltage (inductive)
Total switching current
Coincidence factor (total load capability)
ventilated
not ventilated

Limited to L+ – 47 V
4 A max. 8 outputs

Permissible line length

400 m max., unshielded

Power supply
Digital section from system bus
Power dissipation (rated operation)
Enable input (F+/F–)

5 V, 120 mA typical
49.0 W

Rated input voltage
Input voltage
for logic 1
for logic 0
Rated input current
Permissible line length

24 V DC
13 to 33 V
– 33 to 5 V
5 mA
200 m max.

Short-circuit monitoring
Indicator for signaling output (H+, H–), floating
Output voltage as L+ switch
for logic 1
for logic 0
Switching current
Voltage test to VDE 0160

100 %
25 %; 50 % to 20 oC

Red LED for 16 outputs
L+ – 5 V min.
3 V max.
10 mA max., short-circuit protected
Between two groups: 1250 V AC
Between group and ground point: 1250 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.6 kg

1)
2)

8-52

Short-circuit protection responds with line resistance v 3.6 ohms.
One digital input is permissible as minimum load.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

L+

F+

L–

F–

1L+
1L–
2L+
2L–
3L+
3L–
4L+
4L–

+ 1Q0.0
– 1Q0.0
+ 2Q0.1
– 2Q0.1
+ 3Q0.2
– 3Q0.2
+ 4Q0.3
– 4Q0.3

5L+
5L–
6L+
6L–
7L+
7L–
8L+
8L–

+ 5Q0.4
– 5Q0.4
+ 6Q0.5
– 6Q0.5
+ 7Q0.6
– 7Q0.6
+ 8Q0.7
– 8Q0.7
H +
H–

9L+
9L–
10L+
10L–
11L+
11L–
12L+
12L–
13L+
13L–
14L+
14L–
15L+
15L–
16L+
16L–

g
=
r
=
F+/F- =
1)

2)

+ 9Q1.0
– 9Q1.0
+ 10Q1.1
– 10Q1.1
+ 11Q1.2
– 11Q1.2
+ 12Q1.3
– 12Q1.3
+ 13Q1.4
– 13Q1.4
+ 14Q1.5
– 14Q1.5
+ 15Q1.6
– 15Q1.6
+ 16Q1.7
– 16Q1.7

Front Strip
LED
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Block Diagram of
Module Inputs
Pin

Example of connection designation
for an output:
x20

t

1)

(7) Q 0.6

2)

r
g

F1

Output 6 (6th bit);
0 to 7 possible

g

Address of output byte
(byte 0);
0 to 255 possible

g
g

Q = Output
2)

7th terminal L+ (not
specified in the address)

F5

g
g
g
g

2)

Short-circuit
2)

F9

g
g
g

Data Memory and S5 Bus Control

Connection of
Process Signal
Lines

g
2)

F13

g
g
g
g
2)

Shield

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. When this terminal is connected to the output voltages, the clearances in air and
leakage paths are no longer adequate to UL and CSA, but comply with VDE.

System Manual
C79000-G8576-C199-06

8-53

Digital Input/Output Modules

8.4.12

6ES5 454-4UA13/4UA14 Digital Output Module

–4UA13
Rated supply voltage L+

24 V DC

Number of outputs

16, short-circuit protected 1)

Isolation

Yes, 1 group of 16 outputs

Range for supply voltage

20 to 30 V DC

Fusing

6.3 A, slow
1 fuse per 4 outputs

Output voltage

for logic 1
for logic 0

10 mA to 2 A 2)

Residual current at logic 0

1 mA max.

Switching frequency

7 A, fast
1 fuse per 4 outputs

L+ – 2 V min.
3 V max.

Switching current (resistive, inductive load)
Switching current for lamps

–4UA14

0.45 A max. (10 W)
with resistive load
with inductive load

100 Hz max.
0.2 Hz max. at 1 A; 0.1 Hz at 2 A

Breaking voltage (inductive)

Limited to L+ – 47 V

Total switching current

4 A max. per 4 outputs

Coincidence factor (total load capability)

50 %

Permissible line length

400 m max., unshielded

Limited to L+ –55 V

Power supply
Digital section from system bus

5 V, 100 mA typical

Current consumption from L+/L–

24 V, 100 mA typical

24 V, 120 mA typical

Power dissipation (rated operation)

17.5 W

10 W

Enable input (F+/F–)
Rated input voltage
Input voltage

24 V DC
for logic 1
for logic 0

13 to 33 V
– 33 to 5 V

Rated input current

5 mA

Permissible line length

200 m max.

Short-circuit monitoring
Indicator for signaling output (H+)
Output voltage , referred to L–
(with feed at 1L+) for logic 1
for logic 0

Red LED for 4 outputs
1L+ – 5 V min.
3 V max.

1L+ –1,5 V min.

Switching current

10 mA max., limited

Voltage test to VDE 0160

Between group and ground point: 1250 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.55 kg

1)
2)

8-54

20 mm x 255 mm x 195 mm

Short-circuit protection responds with line resistance v 4,75 ohmd, irrelevant for the –4UA14.
One digital input is permissible as minimum load.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Front Strip
LED

2Q0.4
2Q0.5
2Q0.6
2Q0.7
2L+

L+
L–
H–
L+

H+
3L+
3Q1.0
3Q1.1
3Q1.2
3Q1.3

4Q1.4
4Q1.5
4Q1.6
4Q1.7
4L+
L–

L+

11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Pin

x20
t

r
g

1)

(4) Q 1.6

F1

Output 6 (6th bit);
0 to 7 possible

2)
g

Address of output byte
(1st byte);
0 to 255 possible

2)
g
2)
g
r
g

Example of connection designation
for an output:

Q = Output

2)
2)

4th terminal L+ (not
specified in the address)

2)
g
2)
g
2)
g

Data Memory and S5 Bus Control

1
2
3
4
5
1Q0.1 6
7
1Q0.2 8
9
1Q0.3 10

Block Diagram of
Module Inputs

F2
ShortCircuit

r
g

2)
F3
2)

g
2)
g
2)
g
r
g

2)
2)
2)

g
2)
g
2)
g

Isolation

Connection of
Process Signal
Lines
L+
F+
L–
F–
L+
1L+
1Q0.0

F4
L–

Shield
g
=
r
=
F+/F- =
1)

2)

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. When this terminal is connected to the output voltages, the clearances in air and
leakage paths are no longer adequate to UL and CSA, but comply with VDE.

System Manual
C79000-G8576-C199-06

8-55

Digital Input/Output Modules

8.4.13

6ES5 455-4UA12 Digital Output Module

Rated supply voltage L

24 to 60 V AC (47 to 63 Hz)

Number of outputs

16, conditional short-circuit protection 1)

Isolation

Yes, 2 groups of per 8 outputs

Range for supply voltage

20 to 72 V AC

Fusing

6.3 A, fast; 1 fuse per 4 outputs

Output voltage
for logic 1
for logic 0

L– 1.5 V min.
7.5 V max.

Residual current at logic 0

5 mA max.

Switching current (resistive, inductive load)
ventilated
not ventilated

40 mA to 2 A; 6 A max. per 4 outputs
40 mA to 1 A; 4 A max. per 4 outputs

Switching current for lamps
ventilated
not ventilated

40 mA to 2 A; 2.5 A max. per 4 outputs
40 mA to 1 A; 2.5 A max. per 4 outputs

Max. inrush current for
≤ 3 ms
≤ 20 ms
≤ 50 ms

25 A/group
15 A/group
13 A/group

Permissible line length

300 m max. unshielded

Power supply
Digital section from system bus

5 V, 100 mA typical

Power dissipation (rated operation)

39.0 W

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between two groups: 2000 V AC
Between group and ground point: 1500 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.7 kg

1)

8-56

Protected by a fuse.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of
Process Signal
Lines

Front Strip
LED

F+
F–

Block Diagram of
Module Inputs

Example of connection designation
for an output:

Pin
+5V

1
2

x20

t

(2) Q 1.2

1)

1L

1L

4

r
r

1N

1Q0.0

6

g

1Q0.1

8

g

Address of output byte
(1st byte);
0 to 255 possible

1Q0.2 10

g

Q = Output

12

g

14

g

2nd terminal L+ (not
specified in the address)

16

g

18

g

20

g

1Q0.5
1Q0.6
1Q0.7

r
2L

2N

2Q1.0

25

r

27

g

29

g

31

g

33

g

2Q1.4 35

g

2Q1.5

37

g

39

g

41

g

2Q1.1
2Q1.2
2Q1.3

2Q1.6
2Q1.7

F4
F3

Isolation

2L

Data Memory and S5 Bus Control

1Q0.4

F1

Isolation

1Q0.3

Output 2 (2nd bit);
0 to 7 possible

F2

Shield
g
=
r
=
F+/F– =
1)

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.

System Manual
C79000-G8576-C199-06

8-57

Digital Input/Output Modules

8.4.14

6ES5 456-4UA12 Digital Output Module

Rated supply voltage L

115 to 230 V AC (47 to 63 Hz)

Number of outputs

16, conditional short-circuit protection 1)

Isolation

Yes, 2 groups of 8 outputs

Range for supply voltage

88 to 264 V AC

Fusing

6.3 A fast; 1 fuse per 4 outputs

Output voltage
for logic 1
for logic 0

L– 1.5 V min.
30 V max.

Residual current at logic 0

5 mA max.

Switching current (resistive, inductive load)
ventilated
not ventilated

40 mA to 2 A; 2) 6 A max. per 4 outputs
40 mA to 1 A; 2) 4 A max. per 4 outputs

Switching current for lamps
ventilated
not ventilated

40 mA to 2 A; 2.5 A max. per 4 outputs
40 mA to 1 A; 2.5 A max. per 4 outputs

Contactor size
per fuse group

for all outputs

0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC;
00 (Type 3TJ ..) to 10 (Type 3TB54) at 115 V AC;
0 (Type 3TB40) to 8 (Type 3TB52) at 230 V AC;
00 (Type 3TJ ..) to 4 (Type 3TB48) at 115 V AC;

Max. inrush current for
≤ 3 ms
≤ 20 ms
≤ 50 ms

25 A/group
15 A/group
13 A/group

Permissible line length

300 m max. unshielded

Power supply
Digital section from system bus

5 V, 100 mA typical

Power dissipation (rated operation)

39.0 W

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between two groups: 2000 V AC
Between group and ground point: 1500 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.7 kg

1)
2)

8-58

Protected by a fuse
Contactors of Series 3TJ can only be operated at 115 V AC.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

LED

Block Diagram of
Module Inputs
+5V

1
2

x20

t

1L

1L

4

r
r

1N

1Q0.0

6

g

1Q0.1

8

g

1Q0.2 10

g

1Q0.3 12

g

1Q0.4 14

g

1Q0.5 16

g

1Q0.6 18

g

1Q0.7 20

g

2L

2L

25

r
r

2N

2Q1.0 27

g

2Q1.1 29

g

2Q1.2 31

g

2Q1.3 33

g

2Q1.4 35

g

2Q1.5 37

g

2Q1.6 39

g

2Q1.7 41

g

Example of connection designation
for an output:

Pin

(2) Q 1.6

1)

F2
F1

Output 6 (6th bit);
0 to 7 possible
Address of output byte
(1st byte);
0 to 255 possible
Q = Output

F4
F3

Data Memory and S5 Bus Control

2nd terminal L+ (not
specified in the address)

Isolation

F+
F–

Front Strip

Isolation

Connection of
Process Signal
Lines

Shield

g
=
r
=
F+/F– =
1)

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.

System Manual
C79000-G8576-C199-06

8-59

Digital Input/Output Modules

8.4.15

6ES5 456-4UB12 Digital Output Module

Rated supply voltage L

115 to 230 V AC (47 to 63 Hz)

Number of outputs

8, conditional short-circuit protection 1)

Isolation

Yes, 8 outputs

Range for supply voltage

88 to 264 V AC

Fusing

3.5 A fast; 1 fuse per output

Output voltage
for logic 1
for logic 0

L– 1.5 V min.
30 V max.

Residual current at logic 0

5 mA max.

Switching current (resistive, inductive load)
ventilated
not ventilated

40 mA to 2 A; 2)
40 mA to 1 A; 2)

Switching current for lamps
ventilated
not ventilated

40 mA to 2 A;
40 mA to 1 A;

Contactor size

0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC;
00 (Type 3TJ ..) to 8 (Type 3TB52) at 115 V AC;

Max. inrush current for
≤ 3 ms
≤ 20 ms
≤ 50 ms

16 A
8A
6.5 A

Switching capacity per module
for UL
for CSA

1440 VA max.
2000 VA max.

Permissible line length

300 m max. unshielded

Power supply
Digital section from system bus

5 V, 100 mA typical

Power dissipation (rated operation)

18.0 W

Enable input (F+/F–)

Jumper in front connector

Voltage test to VDE 0160

Between two groups: 2000 V AC
Between group and ground point: 1500 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.6 kg

1)
2)

8-60

Protected by a fuse.
Contactors of Series 3TJ can only be operated at 115 V AC.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of
Process Signal
Lines

Front Strip
LED

Block Diagram of
Module Inputs

Example of connection designation
for an output:

Pin
+5V

F+

1

F–

2

1L

1L

4

r

1N

1Q0.0

6

g

2L

2L

8

r

2N

2Q0.1

10

g

Q = Output

3L

3L

12

r

3N

3Q0.2

14

g

3rd terminal L+ (not
specified in the address)

4L

4L

16

r

4N

4Q0.3

18

g

t

Address of output byte
(byte 0);
0 to 255 possible

F5

5L
25

5N

5Q0.4
27

6L

6L

6N

6Q0.5

7L

7L

29
31
33
7N

7Q0.6

8L

8L

35
37

8N

8Q0.7

Output 2 (2nd bit);
0 to 7 possible

F1

Data Memory and S5 Bus Control

5L

39
41

(3) Q 0.2

1)

2)

20

x20

r
g

r
g

r
g
F8
r
g
2)
Shield

g
=
r
=
F+/F– =
1)

2)

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input (jumper in front connector)

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. If this terminal is connected to the output voltage, the clearances in air and
leakage paths remain adequate to UL, CSA and VDE.

System Manual
C79000-G8576-C199-06

8-61

Digital Input/Output Modules

8.4.16

6ES5 457-4UA12 Digital Output Module

Rated supply voltage L+

24 to 60 V DC

Number of outputs (decoupled via diodes)

16, short-circuit protected 1)

Isolation

Yes, 16 outputs

Range for supply voltage

20 to 72 V DC

Fusing
Output voltage

16 x 1 A, slow
for logic 1:
for logic 0:

(L+)-Switch
(L–)-Switch
(L+)-Switch
(L–)-Switch

L+ – 2.5 V min.
2.5 V max.
3 V max.
L+ – 3 V min.

Switching current (resistive, inductive load)

5 mA to 0.5 A 2)

Residual current at logic 0

1 mA max.

Switching current for lamps
Switching frequency

0.22 A max. (5 W)
with resistive load
with inductive load

100 Hz max.
2 Hz max. at 0.5 A

Breaking voltage (inductive)

Limited to L+ – 75 V 3)

Coincidence factor (total load capability)
ventilated
not ventilated

100 %
50 %; 100 % up to 35 oC

Permissible line length

400 m max. unshielded

Power supply
Digital section from system bus

5 V, 120 mA typical

Power dissipation (rated operation)

13.0 W

Enable input (F+/F–)
Rated input voltage

24 to 60 V DC

Input voltage

for logic 1
for logic 0

13 to 72 V
– 72 to 8 V

Rated input current

at 24 V DC
at 48 V DC
at 60 V DC

2.5 mA
5 mA
6.5 mA

Permissible line length

200 m max.

Short-circuit monitoring
Indicator for signaling output (H+, H–)

Red LED for 16 outputs

Output voltage as L+ switch
for logic 1
for logic 0

L+ – 5 V min.
3 V max.

Switching current

10 mA max., short-circuit protected

Voltage test to VDE 0160

Between two groups: 1250 V AC;
Between group and ground point: 1250 V AC

Mechanical specifications
Dimensions (W x H x D)

40 mm x 255 mm x 195 mm

Weight

Approx. 0.6 kg

1)
2)
3)

8-62

Short-circuit protection responds with line resistance 9 ohms at 24 V DC, 30 ohms at 60 V DC.
One digital input is permissible as minimum load.
At L+ voltages of more than 72 V, the logic 0 of the output can rise to 13 V. A digital input follower will interpret this signal
as a logic 1 (possible fault).

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

Connection of
Process Signal
Lines
F+

L–

F–
+ 1Q0.0

1L+
1L–

– 1Q0.0

2L+

+ 2Q0.1

2L–

– 2Q0.1

3L+

+ 3Q0.2

3L–

– 3Q0.2

4L+

+ 4Q0.3

4L–

– 4Q0.3

5L+

+ 5Q0.4

LED

– 5Q0.4

6L+

+ 6Q0.5

6L–

– 6Q0.5

7L+

+ 7Q0.6

7L–

– 7Q0.6

8L+

+ 8Q0.7

8L–

– 8Q0.7

r

4

g

H–
9L+

+ 9Q1.0

9L–

– 9Q1.0

10L+

+ 10Q1.1

10L–

– 10Q1.1

11L+

+ 11Q1.2

11L–

– 11Q1.2

12L+

+ 12Q1.3

12L–

– 12Q1.3

13L+

+ 13Q1.4

6
8

g

– 13Q1.4

14L+

+ 14Q1.5

14L–

– 14Q1.5

15L+

+ 15Q1.6

15L–

– 15Q1.6

16L+

+ 16Q1.7

16L–

– 16Q1.7

Address of output byte
(byte 0);
0 to 255 possible

g

9
10

(7) Q 0.6
Output 6 (6th bit);
0 to 7 possible

7

g

Q = Output

11
13

g

2)
F5

7th terminal L+ (not
specified in the address)

14
15

g

16
17

g

18
19

g

20
2)
Short-Circuit

22
23
24
25

g

2)
F9

26
27

g

28
29

g

30
31

g

32
33

13L–

2)
F1

5

21
H+

1)

2
3

Example of connection designation
for an output:
x20

t

1

12
5L–

Block Diagram of
Module Inputs

Pin

Data Memory and S5 Bus Control

L+

Front Strip

34

g

2)
F13

35
36

g

37
38

g

39
40

g

41
42

2)
Shield

g
r
F+

=
=
=

1)

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. When this terminal is connected to the output voltages, the clearances in air
and leakage paths are no longer adequate to UL and CSA, but comply with VDE.

2)

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input)

System Manual
C79000-G8576-C199-06

8-63

Digital Input/Output Modules

8.4.17

6ES5 458-4UA12 Digital Output Module

Rated supply voltage L

24 V DC

Number of outputs

16

Isolation

Yes, 16 outputs

Range for supply voltage

20 to 30 V DC

Fusing

16 x 1 A, slow 1)

Output

Relay contacts

Service life of contacts

108 cycles

Switching capacity with resistive load
with RC element module
without RC element module

60 V DC/48 V AC, 0.5 A 2)
60 V DC/48 V AC, 70 mA

Switching current with inductive load
with RC element module and external
suppressor circuit

0.5 A max.

Switching current for lamps

0.1 A max. with RC element module

Switching frequency with resistive load
with inductive load

100 Hz max. (pick-up 1 ms, drop-out 1 ms)
10 Hz max. up to 50 mA,
2 Hz max. up to 0.3 A,
0.5 Hz max. up to 0.5 A

Coincidence factor (total load capability)

100 %

Permissible line length

400 m max., unshielded

Power supply
Digital section from system bus

5 V, 80 mA typical

Current consumption from L+/L–

200 mA typical

Power dissipation (rated operation)

5.2 W

Enable input (F+/F–)
Rated input voltage

24 V DC

Input voltage
for logic 1
for logic 0

13 to 33 V
–33 to 5 V

Rated input current

5 mA

Permissible line length

200 m max.

Voltage test to VDE 0160

Between two groups: 500 V AC
Between group and ground point: AC 500 V

Mechanical specifications
Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.45 kg

1)
2)

8-64

The fuse does not protect the contacts. The relay must be replaced after an overload.
50 V/0.5 A max. resistive load for UL

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

F+

L–
L+

F–
L+

F1

g

F2

6
– 2Q0.1 7
+ 3Q0.2 8
– 3Q0.2
9
+ 4Q0.3 10
– 4Q0.3
11

g

1L

– 1Q0.0
+ 2Q0.1

3L
3L
4L
4L

t

2
4
5

+

1Q0.0

6L
7L
7L
8L
8L
L–

+ 5Q0.4
13
–
5Q0.4 14
+ 6Q0.5
15
– 6Q0.5
16
+
7Q0.6 17
–
7Q0.6 18
+
8Q0.7 19
– 8Q0.7
20
L–
21

9L
10L
10L
11L
11L
12L
12L
13L
13L
14L
14L
15L
15L
16L
16L

24
9Q1.0 25
– 9Q1.0
26
+ 10Q1.1
27
– 10Q1.1
28
+ 11Q1.2
29
– 11Q1.2
30
+ 12Q1.3
31
– 12Q1.3
32
+

33
+ 13Q1.4
34
– 13Q1.4
35
+
14Q1.5 36
– 14Q1.5
37
+
15Q1.6 38
– 15Q1.6
39
+
16Q1.7 40
–
16Q1.7 41

(7) Q 0.6

1)
498

Output 6 (6th bit);
0 to 7 possible
Address of output byte
(byte 0);
0 to 255 possible

g

Q = Output
g

2)
F6

7th terminal L+ (not
specified in the address)

498

g
g
g

2)

22
23
9L

x35

g

12

5L
5L
6L

Example of connection designation
for an output:

Pin

1
3

1L
2L
2L

LED

Block Diagram of
Module Inputs

Data Memory and S5 Bus Control

L+

Front Strip

3)

g

2)
F10

498

g
g
g

g

498
F

R
47R
C
47NF

2)
F14

498

4x

g
g
g

42

2)

Isolation

Connection of
Process Signal
Lines

Shield

g
r
F+

=
=
=

1)

Changeover of enable mode with jumper X35:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.
The terminal is not connected internally. When this terminal is connected to the output voltages, the clearances in air and
leakage paths are no longer adequate to UL and CSA, but comply with VDE.
The terminal is not connected internally. If this terminal isconnected to the output voltages, the clearances in air and
leakage paths remain adequate to UL, CSA and VDE.

2)
3)

Green LED (status indicator)
Red LED (short-circuit indicator)
Enable input

System Manual
C79000-G8576-C199-06

8-65

Digital Input/Output Modules

External Suppressor
Circuitry for
Inductive Load

Front Strip
498
For DC Voltage:
Current Sinking

L+

RC Element Module
498-1AB11

Load

60V DC max.
L–

Diodew100V,1A

L+
Switching to P

60 V DC max.

Diodew100V,1A

L–
Load

L
For AC Voltage:

48 Vms max.

Z. Diode 82V, 5W

N
Load

8-66

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

8.4.18

6ES5 458-4UC11 Digital Output Module

Rated supply voltage L

24 V DC (pins 22, 23)

Number of outputs

16

Isolation

Yes, 2 groups of 8 outputs

Range for supply voltage of the relays

20 to 30 V DC

Ausgang

Relay contacts

Service life of contacts

Approx. 105 cycles at 230 V AC/5A
Approx. 107 cycles mechanical

Switching capacity of the contacts
with resistive load

with inductive load

5.0 A at 250 V AC
5.0 A at 30 V DC
0.3 A at 115 V DC
1.5 A at 250 V AC
1.0 A at 30 V DC
0.08 A at 115 V DC

Max. rating per group P0/P1

8.0 A

Switching frequency
with resistive load
with inductive load

10 Hz max.
2 Hz max.

Permissible line length

400 m max., unshielded

Power supply
Digital section from system bus

5 V, 120 mA typical (all outputs active)

Current consumption from L+/L–

250 mA typical (all outputs active)

Power dissipation (rated operation)

6.6 W

Enable input (F+/F–)
Rated input voltage

24 V DC

Input voltage
for logic 1
for logic 0

13 to 33 V
–33 to 5 V

Rated input current

5 mA

Permissible line length

200 m max.

Voltage test to VDE 0160

Between two groups: 2000 V AC
Between group and ground point: 1500 V AC

Mechanical specifications
Dimensions (W x H x D)

20 mm x 255 mm x 195 mm

Weight

Approx. 0.7 kg

System Manual
C79000-G8576-C199-06

8-67

Digital Input/Output Modules

Connection of
Process Signal
Lines

Front Strip

Block Diagram of
Module Inputs

Example of connection designation
for an output:
(2) Q 1.6

LED Pin
3

L+

F+

1

L–

F–

2

P0

t

2

1

x2
1)

4

L+
L–

1Q0.0

6

g

1Q0.1

8

g

Address of output
byte (1st byte);
0 to 255 possible

1Q0.2

10

g

Q = Output

1Q0.3

12

g

1Q0.4

14

g

2nd terminal L+ (not
specified in the address)

1Q0.5

16

g

1Q0.6

18

g

1Q0.7

20

g

L+

22

L–

23

Data Memory and S5 Bus Control

M0

F1

P1

2Q1.0 27

g

2Q1.1

29

g

2Q1.2

31

g

2Q1.3

33

g

2Q1.4

35

g

2Q1.5

37

g

2Q1.6

39

g

2Q1.7

41

g

Isolation

25

M1

Output 6 (6th bit);
0 to 7 possible

Shield

g
=
F+/F- =
P0/M0 =
P1/M1 =
L+/L- =
1)

8-68

Green LED (status indicator)
Enable input
Group of 8/load supply voltage (1st group)
Group of 8/load supply voltage (2nd group)
Relay supply voltage (24 V DC)

Changeover of enable mode with jumper X2: 1 - 2
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.

System Manual
C79000-G8576-C199-06

Digital Input/Output Modules

8.4.19

6ES5 482-4UA11 Digital Input/Output Module

Rated supply voltage L+
Rated input voltage
Inputs
Number of inputs
Isolation
Input voltage
for logic 0
for logic 1
Rated input current
Delay time
Input resistance
Coincidence factor (total load capability)
Permissible line length
Supply voltage for 2-wire BERO
Power supply
Digital section from system bus
Outputs
Number of outputs
Isolation
Fusing
Output voltage
for logic 1
for logic 0
Switching current
(resistive, inductive load)
Switching frequency
with resistive load
with inductive load
Breaking voltage (inductive)
Total switching current
Coincidence factor (total load capability)
ventilated
not ventilated
Permissible line length
Current consumption from L+/L–
Short-circuit monitoring
Indicator for signaling output (H+)
Output voltage referred to L– (with feed at 1L+)
for logic 1
for logic 0
Switching current
Enable input (F+/F–)
Voltage test to VDE 0160
Mechanical specifications
Dimensions (W x H x D)
Weight
1)

24 V DC
24 V DC
16 min., 24 max.
Yes, 1 group of 32 inputs/outputs
–33 to 5 V
13 to 33 V
8.5 mA typical
0.3 ms typical
2.8 kilohms typical
100 %
50 m max.
22 V to 33 V
5 V, 80 mA typical
8 min., 16 max., short-circuit protected 1)
Yes
6.3 A slow;
1 fuse per 8 outputs
L+ – 1.5 V min.
3 V max.
5 mA to 0.5 A
120 Hz max.
2 Hz max. at 0.3 A; 0.5 Hz max. at 0.5 A
Limited to L+ and – 27 V
4 A max. per 8 outputs
100 %
50 %; 100 % up to 35 oC
400 m max.
24 V, 150 mA typical
Red LED for every 8 outputs
1L+ – 5 V min.
3 V max.
10 mA max. current limiting
Jumper in front connector
Between group and ground point: 1250 V AC
20 mm x 255 mm x 195 mm
Approx. 0.4 kg

Short-circuit protection responds at line resistance v 15 ohms

System Manual
C79000-G8576-C199-06

8-69

Digital Input/Output Modules

Connection of Process Signal Lines
Pin

L+

L–

F+
F–
L+
1Q0.0
1Q0.1
1Q0.2
1Q0.3
1Q0.4
1Q0.5
1Q0.6
1Q0.7
SYNIN
1Q1.0
1Q1.1
1Q1.2
1Q1.3
1Q1.4
1Q1.5
1Q1.6
1Q1.7
L–
H+

1I2.0
1I2.1
1I2.2
1I2.3
1I2.4
1I2.5
1I2.6
1I2.7
SYNOUT
1I3.0
1I3.1
1I3.2
1I3.3
1I3.4
1I3.5
1I3.6
1I3.7

L–

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

x20
1)

Example of connection designation
for an output:
(1) Q 1.6
Output 6 (6th bit);
0 to 7 possible
Address of output byte
(1st byte);
0 to 255 possible
Q = Output
1st terminal L+ (not
specified in the address)

SYSNIN, SYNOUT only relevant for operation with the IP 257
F+/F- =
1)

Enable input

Changeover of enable mode with jumper X20:
Jumper inserted = Enable input active (factory setting)
Jumper open = Enable input inactive.

Switch S2 must be at setting 1.

8-70

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9

Described in this chapter are the installation, wiring and operation of analog
input modules and analog output modules. The individual modules have
special features. These are discussed in separate sections.

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Description

Page

9.1

Technical Description

9-2

9.2

Common Technical Specifications

9-3

9.3

The 460 Analog Input Module

9-4

9.4

The 463 Analog Input Module

9-35

9.5

The 465 Analog Input Module

9-50

9.6

The 466 Analog Input Module

9-77

9.7

The 470 Analog Output Module

9-98

9-1

Analog Input/Output Modules

9.1

Technical Description
The description below applies to the following modules:

Analog Input Modules and Cards
Order No. of the
Module

No. of
Inputs

Isolation/Groups

Range Card (4 Channels)

Order No. of the
Range Card

6ES5 460-4UA13

8

Yes/8 inputs isolated from
0 V and from each other

$12.5/50/500 mV/Pt 100

6ES5 498-1AA11

6ES5 465-4UA12

16/8

No/none

$ 50/500 mV/Pt 100
$1V
$10 V
$20 mA
4 to 20 mA/4-wire trans.
$5 V
4 to 20 mA/4-wire trans.

6ES5 498-1AA11
6ES5 498-1AA21
6ES5 498-1AA31
6ES5 498-1AA41
6ES5 498-1AA51
6ES5 498-1AA61
6ES5 498-1AA71

Analog Input Modules
Order No. of the
Module

No. of
Inputs

Isolation/Groups

Measuring Range

6ES5 463-4UA12
6ES5 463-4UB12,

4

Yes/4 inputs isolated from
0 V and from each other

1 V, 10 V, 20 mA,
4 to 20 mA

6ES5 466-3LA11

16/8

Yes
1.25 V, 2.5 V, 5 V, 10 V
20 mA, 4 to 20 mA

Analog Output Modules
Order No. of the
Module

No. of
Inputs

Isolation/Groups

Output Range

6ES5 470-4UA12

8

Yes/8 outputs from 0 V

$10 V/0 to 20 mA

6ES5 470-4UB12

8

Yes/8 outputs from 0 V

$10 V

6ES5 470-4UC12

8

Yes/8 outputs from 0 V

$1 to 5 V/4 to 20 mA

I/O Modules

Analog input and analog output modules are I/O modules for the input/output
of widely differing, analog process signals for the S5-135U/155U
programmable (logic) controller.
These I/O modules allow the creation of control systems which require the
processing of analog measured variables or continuous input to actuators.

9-2

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.2

Common Technical Specifications
Important for the USA and Canada
The following approvals have been issued:
UL Listing Mark
Underwriters Laboratories (UL) to Standard UL 508, Report E 85972 and
E116536 for the 466-7LA11 analog input module
CSA Certification Mark
Mark Canadian Standard Association (CSA) to Standard C 22.2 No. 142,
Report LR 63533C and LR 48323 for the 466-7LA11 analog input
module

Address range

128 to 255 (0 to 255)

Supply voltage L+
rated value
ripple Vpp
permissible range (including ripple)
reference potential

24 V
3.6 V
20 to 30 V
L–= Mext = 0 V

Voltage for the isolated enable inputs (only required when enable
jumper is inserted)

F+ = + 24 V
F– = 0 V

Line lengths for
Analog input modules with rated input range of
$ 12.5 m, $ 50 mV and Pt 100

50 m max. for shielded cables laid separately
from power system cables (see Chapter 3)

Analog input modules with rated input range of $ 500 mV /
$ 1 / $ 5 / $ 10 V / $ 20 mA, 4 to 20 mA and Pt 100

200 m max., shielded

Analog output modules

200 m max., shielded

Temperature range
in operation
for storage ans transportation

0 to 55 oC
– 40 to 70 oC

Relative humidity

95 % max. at 25 oC, no condensation

Site altitude

3500 m max. above sea level

Dimensions (W x H x D)

20 x 255 x 195 mm

Weight

Approx. 0.4 kg

System Manual
C79000-G8576-C199-06

9-3

Analog Input/Output Modules

9.3

9.3.1

The 460 Analog Input Module

Design
The modules are designed as plug-in PCBs for central controllers and
expansion units with a backplane connector and with a blade connector to
accept a plug-in front connector. You can directly connect the process signal
lines to the front connector, which is available separately, with screw or
crimp terminals.

Addressing
Switch, Mode
Switches

Situated on each module is an addressing switch with six rockers to set the
module address. Analog input modules also have two switches on the side
with eight rockers for setting the mode, and receptacles for range cards.
The modules are protected by covers on both sides.
Addressing Switch
Blade Connector

Front Connector

Mode Switches
Range Cards
Figure 9-1

9.3.2

Analog Input Module

Function of the Enable Input
The 460 module has an enable circuit. You can use the enable inputs to
switch off individual modules whilst the PLC is in operation. This means
that:
The module can no longer be addressed by the user program.
Modules which are switched off can be removed or inserted during operation.
If this is not necessary, operate the module with the enable input switched
off.

9-4

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Enable Input

The enable circuit requires an external 24 V voltage at enable inputs F+/F- in
the front connector. If there is no voltage at F+/F-, the modules will not
acknowledge.
When the front connector is swivelled away from the front strip of the
module, the supply of power to the enable input is interrupted, i.e. the
module is switched off and can no longer be addressed by the user program: a
timeout (QVZ) occurs in the CC.

Switching Off the
Enable Input

The 460 module additionally offers the facility for changing the enable
mode. The module has a jumper accessible from above in the vicinity of the
addressing switch.
When the enable jumper is inserted, you can define the behaviour of the 460
analog input module as follows:
When the enable voltage and load voltage are obtained from the same
load supply, a shutdown of the 24 V load voltage will result in a timeout.
When the enable voltage and load voltage are obtained from different
load supplies, a shutdown of the 24 V load voltage will not result in a
timeout. (With the 460-4UA11/12 modules, a shutdown of the load
voltage will result in a timeout.)
Enable Jumper

Figure 9-2

Enable Input and Enable Jumper

Jumper inserted:
Jumper open:

Enable input (F+/F-) active (factory setting)
Enable input (F+/F-) switched off

Examples of functioning of the enable inputs:
To switch off individual subprocesses, i.e. outputs of various modules can
be operated from a common load supply and yet activated separately.
The load voltage of individual modules can be monitored without
additional circuitry. Any reactions to failure of the load voltage can be
programmed in the QVZ (timeout) organization block.

System Manual
C79000-G8576-C199-06

9-5

Analog Input/Output Modules

Configuring

You must observe the following when configuring systems:
Switching on

At the latest 100 ms after power-up of the PLC, the voltage
must be present at the enable inputs of the I/O modules.

Switching off

When the PLC has been switched off, the voltage at the
enable inputs of the I/O modules must still be present as
long as the internal 5 V voltage is present.

Switching off the
CC

You should observe the following instructions for switching off CCs and
equipment for supplying power to the enable inputs.

Separate or
Common
Shutdown of the
CC/EU and Load
Power Supply

When there is a need to switch off the load power supply separately without
affecting the enabling of modules, there are the following possibilities for
producing the enable voltage. These exist even when the load power supply
is used without an additional capacitor and common shutdown.
230 V AC supply for CC/EU and load power supply

b)

a)
–951

Battery

I/O Modules

c)

F+
CC/EU

L+

Power Supply

L+

230 V AC
Load Power Supply 24V

Supply for the enable inputs from:
a) 6ES5 951-4LB11 load power supply
b) Battery
c) Terminals for 24 V on the front plate of the power supply

9-6

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

24 V supply for CC/EU and I/Os

a)

Battery
b)

I/O Modules
F+
CC/EU

L+

Power Supply 24V

L+

24 V DC

Supply for the enable inputs from:
a) Battery
b) Terminals for 24 V on the front plate of the power supply

Common
Shutdown of the
CC/EU and Load
Power Supply with
a 230 V AC Supply

Proper functioning is ensured if the 24 V load power supply has an output
capacitance of at least 4700 mF per 10 A of load current. Other units which
do not meet this condition can be adapted to this requirement by connecting a
10000 mF / 40 V capacitor in parallel.
I/O Modules
F+
CC/EU
L+
230 V AC

Power Supply

10000µF/
40V

Load Power Supply 24V

System Manual
C79000-G8576-C199-06

9-7

Analog Input/Output Modules

9.3.3

Special Features of the 460 Analog Input Module
The 460 analog input module executes integrating processing of the digital
input signals; periodic system interference is thus suppressed.
You can adapt the process signals, according to the application, to the input
level of the analog-to-digital converter of the module with plug-in range
cards (resistor dividers or shunt resistors).

Broken Wire
Signal

To monitor the sensors connected to the inputs, you can use the
6ES5 498-1AA11 range card (through-connection card) to implement the
“broken wire detection” mode. You can activate broken wire detection for 4
or 8 inputs.
Each time the input value is about to be encoded, a constant current is briefly
(1.6 ms) switched to the input terminals and the resultant current is checked
for a limit value. If a digital voltmeter is used to measure the signal at the
input, these current pulses may appear to indicate fluctuation of the signal.
The encoded value, however, is not affected.

Switching the
Tripping Current to
the Inactive State

If these apparent fluctuations of the signal are disturbing, e.g. during startup,
you can switch the tripping current to the inactive state on the 460 analog
input module: apply + 24 V to pin 24 of the front connector, and 0 V to L-.
You must additionally set the mode switch to “without broken wire
detection.”
In the event of open-circuit of the sensor or its line, the voltage exceeds the
limit and a broken wire is indicated (bit 1 in data byte 1). The
analog-to-digital converter encodes the value 0.
A broken wire signal is only useful when the 6ES5 498-1AA11
through-connection card is used. With all other measurement cards, a broken
wire signal will result in incorrect reactions. Further details relating to the
broken wire signal can be found in Section 9.3.12.

Measuring Range
Exceeded

If the measuring range is exceeded, the overflow bit (bit 20 of the low
byte) is set.

Cyclic Sampling

You have a choice of the cyclic sampling and selective sampling modes.
In the cyclic sampling mode, the module continuously encodes all measured
values. The digitized measured values are stored under the channel-related
address on the module (the high byte under this address, and the low byte
under the next higher address). The measured values can then be read by the
module at any time without waiting. When you operate the module in this
mode, you can set a module address from 0 to 255.

9-8

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Selective Sampling

In the selective sampling mode, a measured value is encoded on the central
initiative of the CPU. At the start of conversion, the module must be
addressed once with a write operation (T PW) by the user program. An active
bit (T = 1) is set during encoding.
With the transition to T = 0, the measured value becomes valid. With
non-constant cycle times, there may be non-periodic measured value
aquisition. If you operate the module in this mode, you must set a module
address from 128 to 255. You can also use the address range from 0 to 127
for selective sampling after appropriate programming in DB 1 of the user
program.

Time-Controlled
Program
Processing

Another method is that of time-controlled program processing. With this
method, certain program segments (e.g. FB 13) are automatically inserted
into program processing at the 100 ms rate by a timecontrolled block (OB 13). A constant timebase is thus achieved.
FB 13

SPRM-B

LEN=22

ABS
SHEET 1

SEGMENT 1
NAME: SELSAMPL
0005

EXAMPLE OF SELECTIVE SAMPLING

:

0006

:

0007

:L

PW128

READ ANALOG VALUE

0008

:T

MW128

IN TO AUX: FLAG FW 128

0009

:A

M 129.2

SCAN ACTIVITY =1?

000A

:JC

= END

IF = 1, JUMP TO END

000B

:T

FW10

IF = 0, MEASURED VALUE IN FW 10

000C

:T

PB128

INITIATE SAMPLING

000D

END

:

(1ST VALUE INVALID AFTER START)

000E
000F

:

0010

:BE

Function Block

You can read analog values of analog input modules with a function block
from the “basic functions” package.

BASP (Output
Inhibit)

The BASP signal is not interpreted by the 460 analog input module.

System Manual
C79000-G8576-C199-06

9-9

Analog Input/Output Modules

9.3.4

Setting the Module Address
You set the module address on the addressing switch. This also establishes
the necessary assignments between user program and process connection.
The module address is the sum of the decimal significances of the switch
rockers in the On setting (Ĥ).
One data word = two data bytes is required to process an input or an output.
A module with 16 inputs therefore reserves 32 byte addresses, and a module
with 8 inputs or outputs reserves 16 byte addresses.

Labeling Field

You can affix the adhesive label with the desired module address on a free
labeling field under the addressing switch.
The switch rockers to be set for the module address specified as a decimal
number (address bit ADB) are marked by dots on the label.
Press the individual rockers of the addressing switch downwards with a
ballpoint pen or similar object, but not a pencil.

On Setting
(Switch Pressed)

Addressing Switch

Free Field for Label with
Module Address and
marked Switch Settngs

ADB1
ADB0

8

16

32

4
2
1

ADB3
ADB2

ADB7

ADB6
ADB5
ADB4

128
64

Address (Decimal)

Decimal Signification of
the Address Bit

Address Bit

ADB0 and ADB1 are not assigned
ADB2 is not connected

Figure 9-3

Labeling of the Addressing Switch

The address under which the module is referenced by the STEP 5 program is
independent of the slot.

Start Address,
Subaddress

9-10

For analog input and analog output modules (8 inputs) only the lowest
address (start address) is set. Other addresses (subaddresses) are decoded on
the module.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Note
The start address of the analog module must be a multiple of the double
channel number.
4 channels : 0, 8, 16, 24, ... 248
8 channels : 0, 16, 32, 48, ... 240

If one of the inputs or outputs (Channel 0 to 7) of a module is to be
addressed, the relevant subaddress must be specified in the program.
The subaddress of the input or output, based on the start address of the
module, is given by:
Start address + 2 x channel no. = subaddress
Example:
Analog input module with 8 inputs
The address is the sum of the significances set with the individual coding
switches.
160 = 128 + 32 = 27 + 25

On Setting
(Switch Pressed)

ADB1
ADB0

8

16

4
2
1

ADB3
ADB2

64
32

ADB7
ADB6
ADB5
ADB4

128

IB 160

A module with 8 inputs (Channel 0 to 7) and start address 160 reserves the
address range from
160 to address 160 + 7 x 2 = 174
In this example, the next free address for another module is 176.
Addresses already assigned must not be set again.

System Manual
C79000-G8576-C199-06

9-11

Analog Input/Output Modules

Addressing for
Cyclic/Selective
Sampling

However, analog input modules and analog output modules may be given the
same address with cyclic sampling because they are distinguished by the user
program. This is not possible with selective sampling.
For cyclic sampling, you can address the module in the address range from 0
to 255, and for selective sampling from 128 to 255. For selective sampling,
you can also use the address range from 0 to 127 after appropriate
programming in DB 1 of the user program.
Example:
On an analog input module with start address 160 (IB 160 = input byte 160),
input channel 3 is to be scanned by the program.

9-12

Step

Action

1

Affix the self-adhesive label with address 160 on the free field under the
addressing switch on the module. ADB 5 and ADB 7 are marked on the
label.

2

Press the appropriate rockers of the addressing switch down on the side
marked by a dot on the module cover. Set the other rockers to the opposite
setting. This way sets the start address of the module.
ADB 5 and ADB 7 results in 25 + 27 = 32 + 128 = 160

3

Enter the address 160 + 3 x 2 = 166 in the program for input channel 3.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.3.5

Removing and Inserting Modules

!

Warning
When removing and inserting the front connector during operation,
hazardous voltages of more than 25 V AC or 60 V DC may be present at the
module pins. When this is the case at the front connector, live modules may
only be replaced by electrical specialists or trained personnel in such a way
that the module pins are not touched.
During operation, the front connector and module must not be removed or
inserted without the enable jumper or active enable circuit.

Install an analog input/output module as follows:

System Manual
C79000-G8576-C199-06

Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Insert the module at the desired slot in the subrack and push it back in the
guides.

3

Latch the module by rotating the locking pin by 90o at the lower end of
the module. It must no longer be possible to pull the module forwards.

4

Engage the front connector on the support pin of the module.
The width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (e.g. front connectors with
115/230 V AC wiring cannot be plugged into analog modules).

5

Tighten the screw in the upper part of the front connector.

9-13

Analog Input/Output Modules

Remove an analog input/output module as follows:
Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Slacken the screw in the upper part of the front connector. This causes the
front connector to be pressed out of the female connector of the module.
Contacts F+ and F- of the enable input at the upper end of the front connector are thus opened first. If the enable input is active, power is removed
from the outputs and the module is isolated from the S5 bus.

3

Swing the front connector out and lift it away from the support pin of the
module.

4

Release the module by rotating the locking pin by 90o at the lower end of
the module. You can pull the module out of the subrack with a grip with
swivels outwards.

6

Module

1

Front
Connector

Support Mount
5

Support Pin

4
2
3

Figure 9-4
1
2
3
4
5
6

Module with Front Connector

Screw
Locking pin
Support mount
Support pin
Grip
Backplane connector

Comply with VDE Specifications 0110 and 0160 to carry out the wiring of
supply and signal lines which are to be connected to the programmable
controllers and front connectors of the modules.
Detailed information on cabinet assembly, cabinet ventilation and protective
measures can be found in Chapter 3.

9-14

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.3.6

Marking of Modules and Front Connectors
For the marking of modules and front connectors, labels are supplied with the
module and central controller; they are affixed as shown in Figure 9-5.

1

Figure 9-5
1
2
3
4
5

System Manual
C79000-G8576-C199-06

2 4

1

5

3

Marking and Labeling of Modules

Label with the module address under which the module is referenced by the STEP 5 program
Labeling strip with the product designation for the module; space to mark the module version
and label the channels
Label with module address and marking of the required settings for the addressing switch
Labeling strip for terminal designations or connection diagrams (strip in the cover of the
front connector)
Name plate

9-15

Analog Input/Output Modules

9.3.7

Connecting the Signal Lines
For connection of the signal lines, front connectors for 20 and 40 mm
mounting width with crimp connection and 40 mm mounting width with
screw connection are available (screwdriver blade width: 3.5 mm, maximum
torque: 0.8 Nm).
Use stranded conductor to facilitate handling of the front connector. Ferrules
are not required for screw connections, because the screw terminals are
provided with wire protection.
When the crimp contact is inserted in the plastic body of the front connector,
a click can clearly be heard. This indicates that the contact is engaged. For
jumpering or to correct the wiring, you can remove the contacts with a
releasing tool (see ordering information) without having to pull out the front
connector.
Ferrules are not required for screw connections, because the screw terminals
are provided with wire protection. You can use ferrules of 7 mm in length to
DIN 46228. The maximum terminal area is 2 x 2.5 mm2.

Terminal
T
Type

Connector
T
Type
6ES 497-

Cross-Section
Max.
N off
No.
Signal or Supply Aux. Jumper
Contacts
Conductor
in Connector

Connector for
R t dV
Rated
Voltage
lt

Mounting Width
off M
Module
d l

1)

Crimp con- -4UA12 2)
nection

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

20 mm

-4UA22 2)

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

40 mm

-4UB12

42

0.5 to 2.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

40 mm

-4UB31

42

0.5 to 1.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

20 mm

Screw connection
ti

1)
2)

!

9-16

Operation
with fan
Operation
O
ti
without fan

To multiply the supply and 0 V ground terminals, and to connect the enable input
The crimp contacts must be ordered separately for these types of connector.

Caution
Only extra-low voltage 60 V DC with safety separation from system voltage
may be used for the 24 V DC supply and for the 24 V DC input signals.
Safety separation can be implemented to the requirements of, amongst other
sources, VDE 0100 Part 410/HD 384-4-41/IEC 364-4-41 (as functional
extra-low voltage with safety separation) or VDE 0805/EN 60950/IEC 950
(as safety extra-low voltage SELV) or VDE 0106 Part 101.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.3.8

Connection of Sensors
Observe the following information when connecting the sensors.

Connection of
Current or Voltage
Sensors

With isolated sensors, it is possible for the measuring circuit to develop a
potential with respect to ground which exceeds the permissible potential
difference UCM (see maximum values of the individual modules). To
prevent this, you must connect the negative potential of the sensor to the
reference potential of the module (0 V bus).
Example:
Temperature measurement on a busbar with insulated thermocouples

Equipotential
Bonding

In the worst case, the measuring circuit can develop an excessively high
potential on account of a static charge or contact resistances. This must be
prevented with an equipotential bonding conductor.
The permissible potential difference (UCM) between the inputs and the 0 V
bus must not be exceeded.
Depending on the system or type of sensor, the potential difference must be
kept in the permissible region with epuipotential bonding.
Analog Input Module

Sensor, Isolated
+
–

M+
A

U

MUX
E
M–

Range
Card for
4 Inputs

#

D

0 V Bus
Equipotential Bonding Conductor

Figure 9-6

Measuring Circuit with Equipotential Bonding Conductor for the 460 Analog Input Module

System Manual
C79000-G8576-C199-06

9-17

Analog Input/Output Modules

Example:
(Special case) The temperature of the busbar of an electroplating bath is to be
measured with an uninsulated thermocouple.

Sensor,
Not Isolated

+
–

+
–

Analog Input Module

M+
A
MUX

UE
M–

Range
Card for
4 Inputs

#

U CM

D

U CM

Figure 9-7

0 V Bus

Measuring Circuit without Equipotential Bonding Conductor for the 460 Analog Input Module

The potential of the busbar with respect to the reference potential of the
module is, for example, 24 V DC. A 460 analog input module with isolated
input is used (UCM = 60 V AC/75 V DC). An equipotential bonding
conductor must not be laid here because it would short-circuit the busbar.

9-18

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.3.9

Connecting a Compensating Box for Thermal E.M.F.
Measurement
If the room temperature fluctuations at the reference point (e.g. in the
terminal box) affect the measurement result and you do not wish to use a
thermostat, you can compensate for the effect of temperature on the reference
point with a compensating box. Between - 10 and + 70 oC, it compensates for
the change in thermal e.m.f. cause by temperature deviation (compensating
box, see Catalog MP 11). Ensure that the compensating box has thermal
contact with the terminals.
If the compensating box is aligned at 20 oC, this must be taken into account
in temperature evaluation (20 oC measuring point temperature = 0 mV).
Pins 22 and 23 are extended on analog input modules as an input for the
compensating voltage. You must select a common input loop for all inputs on
mode switch 2.
The compensating box must be connected in a floating circuit. The power
supply unit of the compensating box must have a grounded shield winding to
avoid AC system interference being picked up. A separate compensating box
with its special power supply unit is required for each analog input module.

Analog Input Module
Terminal Box
Thermocouple

A

M+
M–

–

MUX
Range
Card for
4 Inputs
6ES5 498-1AA11
#

Compensating
Box

+

D
22–
23+

0 V Bus
Power
Supply
for Compensating Box

Figure 9-8

=

~

Connecting a Compensating Box

System Manual
C79000-G8576-C199-06

9-19

Analog Input/Output Modules

9.3.10

Connecting Resistance Thermometers in the Standard Pt 100
Range
The series-connected resistance thermometers (up to 8 Pt 100s) are fed with a
current of 2.5 mA (IC+/IC-) by a constant current generator. The voltage at the
Pt 100’s is picked off at measurement inputs M+ and M-. In this mode, the
whole temperature range of the Pt 100 (-200 °C to +840 °C) is available. The
mode is printed on the cover of the module as follows:
“resistance thermometer uncompensated full range.” Other voltage sensors
can be connected in a floating circuit at the M+/M- inputs of a card which are
not assigned to resistance thermometers (voltage range 500 mV).
+
460 Analog Input Module

Pt 100

Card 1

–

M+
CH0

Pt 100

A

M–
Range
Card for
4 Inputs
6ES5 498-1AA11

CH1

CH2

MUX

#

Pt 100
CH3
0...500 mV

D
Card 2

UCM

CH4
0...500 mV
UCM

Range
Card for
4 Inputs
6ES5 498-1AA11

2)

1)
CH7
Pt 100
IC–

L+
L–

IC+

const.

2.5 mA
0 V Bus

Figure 9-9

1)
2)

Connecting Resistance Thermometers in the Standard Pt 100 Range

If no Pt 100 is connected to CH4 to CH7, other voltages and currents can be measured at these channels with cards
6ES5 498-1AA21, 6ES5 498-1AA31, 6ES5 498-1AA41, 6ES5 498-1AA51, 6ES5 498-1AA61, 6ES5 498-1AA71.
When cards 6ES5 498-1AA41, 6ES5 498-1AA51 or 6ES5 498-1AA71 are used, a short-circuit jumper is not required.

9-20

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.3.11

Connecting Resistance Thermometers in the Extended Pt 100
Range
The series-connected resistance thermometers (up to 8 Pt 100s) are fed with a
current of 2.5 mA (IC+/IC-) by a constant current generator. The voltage at the
Pt 100s is picked off at measurement inputs M+ and M-.
In this mode, the temperature range of approximately -100 °C to +100 °C has
a more accurate resolution. The mode is printed on the cover of the module
as follows: “resistance thermometer compensated low range.”You should
only use the 6ES5 498-1AA11 range card (" 50 mV / 500 mV).
Unused inputs must be connected in parallel to a wired input. In the
following figure, for example, these are the inputs CH4 to CH7.

M+
Ch0
M–
M+
Ch1
M–
M+
Ch2
M–
M+
Ch3
M–
M+
Ch4
M–
M+
Ch5
M–
M+
Ch6
M–
M+
Ch7
M–

6ES54981AA11

6ES54981AA11

Ic–
Ic+

24V
M24V
Figure 9-10

System Manual
C79000-G8576-C199-06

L+

2.5mA

L–

Connecting Resistance Thermometers in the Extended Pt 100 Range

9-21

Analog Input/Output Modules

9.3.12

Broken Wire Signal

Broken Wire
Signal in the
Standard Pt 100
Range

An open-circuit in the lines to a resistance thermometer is indicated as
follows:

Broken Wire at
M+
M–
Pt 100
IC+
IC–
1)

Module Reaction, Encoded Value
0
0
0 1)
0
0

Error Bit E
1
1
1
0
0

With the 460 analog input module, the value 0 is also encoded for the intact Pt 100 resistances
because the auxiliary circuit is interrupted; the error bit will not be set for these channels.

If the mode “without broken wire signal” is selected on the module, an
open-circuit of the resistance thermometer is indicated with an overflow.
Unassigned channels can be used for voltage or current measurement.

Broken Wire
Signal in the
Extended Pt 100
Range

9-22

If a line of the auxiliary circuit (IC+, IC-) is interrupted, the “negative range
limit” is encoded for all inputs and the overflow bit is set to “1.” In the event
of a sensor or measuring line open-circuit, the error bit is additionally set to
“1” for the relevant channel.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.3.13

Connecting Transducers
Two-wire transducer (short-circuit protected supply voltage via the range
card of the analog input module)
L+

L–

Analog Input Module

M+

A

4...20 mA

+

MUX
Range
Card for
4 Inputs
6ES5-498-1AA51

–

M–

#

D

0 V Bus

Four-wire transducer (with separate supply voltage)
Analog Input Module

M+
230 V AC

A

+4...20 mA

+

MUX
Range
Card for
4 Inputs
6ES5-498-1AA71

–

M–

#

D

Do not exceed max. permissible potential difference!

0 V Bus

Four-wire transducer with a two-wire transducer card
M+

L+

L–

Analog Input Module

230 V AC
+

A

0...20 mA

MUX

–
M–

Range
Card for
4 Inputs
6ES5-498-1AA71

#

D

L– (0 Vext)

System Manual
C79000-G8576-C199-06

0 V Bus

9-23

Analog Input/Output Modules

9.3.14

Measured-Value Representation

Digital
Measured-Value
Representation as
Two’s Complement
Units

Input Voltage iin mV
V

(rated input range $ 50 mV)

Byte 0

Byte 1

7
6
5
4 3 2
1 0 7 6 5
4 3 2
212 211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

0
OV

w4096

100.0

0

1

1

1

1

1

1

1

1

1

1

1

1

0/1 0/1 1

Overflow

4095
2049

99.976
50.024

0
0

1
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

2048
2047

50.0
49.976

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1024
1023

25.0
23.976

0
0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1
0
–1

0.024
0.0
–0.024

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

1
0
1

0/1 0/1 0
0/1 0/1 0
0/1 0/1 0

–1023
–1024

– 24.976 1
– 25.0
1

1
1

1
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0

0/1 0/1 0
0/1 0/1 0

–2047
–2048

– 49.976 1
– 50.0
1

1
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0

0/1 0/1 0
0/1 0/1 0

–2049
–4095

– 50.024 1
– 99.976 1

0
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

–4096

–100.0

0

0

0

0

0

0

0

0

0

0

0

1

0/1 0/1 1

Overflow

1

Rated
range

A = Active bit
E = Error bit
OV = Overflow bit

9-24

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Digital
Measured-Value
Representation as
Value and Sign
Units

Input Voltage iin mV
V

(rated input range $ 50 mV)

Byte 0

Byte 1

7
S

6
5
4 3 2
1 0 7 6 5
4 3 2
211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

0
OV

w4096

100.0

0

1

1

1

1

1

1

1

1

1

1

1

1

0/1 0/1 1

Overflow

4095
2049

99.976
50.024

0
0

1
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

2048
2047

50.0
49.976

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1024
1023

25.0
23.976

0
0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1
0
–0
–1

0.024
0.0
0.0
–0.024

0
0
1
1

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

1
0
0
1

0/1
0/1
0/1
0/1

–1023
–1024

– 24.976 1
– 25.0
1

0
0

0
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

0/1 0/1 0
0/1 0/1 0

–2047
–2048

– 49.976 1
– 50.0
1

0
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

0/1 0/1 0
0/1 0/1 0

–2049
–4095

– 50.024 1
– 99.976 1

1
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

–4096

–100.0

1

1

1

1

1

1

1

1

1

1

1

1

0/1 0/1 1

Overflow

1

0/1
0/1
0/1
0/1

0
0
0
0

Rated
range

A = Active bit
E = Error bit
OV = Overflow bit

Bit 212 is interpreted as the sign.

System Manual
C79000-G8576-C199-06

9-25

Analog Input/Output Modules

Measured-Value
Representation for
Resistance
Thermometers in
the Standard Pt
100 Range

The resolution with Pt 100 resistance thermometers is approximately 0.25 oC.
1 ohm  10 units

Units Resistance in Temperohms
ature in
oC

Byte 0

Byte 1

7
S

6 5 4 3 2 1 0 7 6 5 4 3 2
211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

0
OV

0

1

1

1

1

1

1

1

1

1

1

1

1

269.1

0
0

1
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1 0/1 0/1 0
1 0/1 0/1 0

4096

400.0

–

4095
2049

399.90
200.98

–

2048
2047

200.0
199.90

266.5
266.0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0 0/1 0/1 0
1 0/1 0/1 0

1024
1023

100.00
99.90

0
–0.2

0
0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0 0/1 0/1 0
1 0/1 0/1 0

1
0

0.098
0.0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1 0/1 0/1 0
0 0/1 0/1 0

–
–

0/1 0/1 1

Overflow
Overrange

Rated range

A = Active bit
E = Error bit
OV = Overflow bit
S = Sign

When Pt 100 resistance thermometers are connected, the maximum
temperature in the rated range is 266 oC. If it can be ensured that the
temperature does not exceed 850 oC, the input value may extend into the
overrange. The resolution is then 4095 units. Unused inputs can be utilized
for voltage measurements in the 500 mV range (see front connector
assignments).
Extended Pt 100
Range

In addition to the standard Pt 100 range, there is an extended Pt 100 range on
the 460 analog input module. You can select this with the mode switch.
The following is printed on the cover of the module to set the Pt 100 mode:
Standard range: “resistance thermometer uncompensated full range”
Extended range: “resistance thermometer compensated low range”
In this range, the basic resistance of the Pt 100 at 0 oC (100 ohms) is
compensated for on the module. As in the standard range, the Pt 100 is fed
with a constant current of 2.5 mA. Using the overrange (- 100 mV to + 100
mV), this results in a temperature range of approx. -100 °C to + 100 °C.
This measuring range of 200 °C is resolved to 8192 units with the correct
sign for the temperature. One unit thus corresponds to approximately 0.025
°C. If you select the extended Pt 100 range, you can use all 8 analog inputs in
this range only.
You should only use the 6ES5 498-1AA11 range card ($ 50 mV/500 mV).

9-26

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Measured-Value
Representation in
the Extended Pt
100 Measuring
Range (Two’s
Complement)
Units

Pt 100/ohms

Temperatu
i oC
in

Byte 0

Byte 1

7
S

6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
211 210 29 28 27 26 25 24 23 22 21 20 A E OV

w 140.0

0

1

1

1

1

1

1

1

1

1

1

1

1

0 0 1

Overflow

4095
2049

139.99
120.01

103.74 0
51.61 0

1
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0 0 0
0 0 0

Overrange

2048
+1
0
–1
–2048

120.0
100.01
100.0
99.99
80

51.58
0.026
0
–0.026
–50.78

0
0
0
1
1

1
0
0
1
1

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
0
0
1
0

0
1
0
1
0

0
0
0
0
0

–2049
–4095

79.99
60.01

–50.81 1
–100.60 1

0
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0 0 0
0 0 0

Overrange

1

0

0

0

0

0

0

0

0

0

0

0

1

0 0 1

Overflow

>4095

<–4095 v 60

0
0
0
0
0

0
0
0
0
0

Rated range

Broken wire
–4095

Arbitrary

Arbitrary 1

0

0

0

0

0

0

0

0

0

0

0

1

0 0 1

Broken wire
Ic+/Ic-2)

–4095

Arbitrary

Arbitrary 1

0

0

0

0

0

0

0

0

0

0

0

1

0 1 1

Broken wire
Sensor
Measuring
line 1)

1)
2)

Only with broken wire monitor activated, error bit = 1 only for faulty
channel; for sensor broken wire, overflow bit = 1 for all channels
On account of the Pt 100 series circuit, this bit combination always
appears for all channels if the supply line is open-circuit.

A = Active bit
E = Error bit
OV = Overflow bit
S = Sign

System Manual
C79000-G8576-C199-06

9-27

Analog Input/Output Modules

Measured-Value
Representation for
Current Measuring
Ranges from 4 to
20 mA

Measuring range 500 mV; card with 31.25 ohm shunt
(6ES5 498-1AA51/AA71)
The 4 to 20 mA range is resolved to 2048 units at an interval of 512 to 2560.
If you require a representation from 0 to 2048, you must subtract 512 units by
software. Please note the following:
A broken wire signal cannot be emitted.
Detection of the overrange can be achieved by scanning bits 29 and 211.
A broken wire can be detected with currents < 3 mA.

Current Limiting
If you short-circuit the positive and negative terminals of the transducer
when using the 6ES5 498-1AA51 range card (for a two-wire transducer),
the current is limited to about 28 mA. Until the thermal current limiting
circuit responds in the range card (about 3 s), a short-circuit current of
approximately 250 mA flows; this sets the overflow bit for this duration
at all channels.

Units

Input Currentt iin mA
A

Byte 0

Byte 1

7
S

6 5 4 3 2 1 0 7 6 5 4 3 2
211 210 29 28 27 26 25 24 23 22 21 20 A

1 0
E OV

w 4096 w 32.000

0

1

1

1

1

1

1

1

1

1

1

1

1

0/1

0

1

Overflow

4095
3072
3071
2561

31.992
24.0
23.992
20.008

0
0
0
0

1
1
1
1

1
1
0
0

1
0
1
1

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1 0/1
0 0/1
1 0/1
1 0/1

0
0
0
0

0
0
0
0

Overrange
Short-circuit with twowire transducer

2560
2048
512

20.0
16.0
4.0

0
0
0

1
1
0

0
0
0

1
0
1

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0 0/1
0 0/1
0 0/1

0
0
0

0
0
0

511
384
383

3.992
3.0
2.992

0
0
0

0
0
0

0
0
0

0
0
0

1
1
1

1
1
0

1
0
1

1
0
1

1
0
1

1
0
1

1
0
1

1
0
1

1 0/1
0 0/1
1 0/1

0
0
0

0
0
0

Range
underflow

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Broken wire

0/1

Rated range

A = Active bit
E = Error bit
OV = Overflow bit
S = Sign

9-28

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.3.15

Technical Specifications
6ES5 460-4UA13 Analog Input Module

Rated input ranges with cards for every 4 channels
– 6ES5 498-1AA11
– 6ES5 498-1AA21
– 6ES5 498-1AA31
– 6ES5 498-1AA41
– 6ES5 498-1AA51
– 6ES5 498-1AA61
– 6ES5 498-1AA71

$ 12.5 mV/$50 mV/$500 mV/Pt 100
$1V
$ 10 V
$ 5 mA/$ 20 mA
4 to 20 mA for two-wire transducer
$5V
4 to 20 mA for four-wire transducer

Number of inputs

8 voltage/current inputs or
8 resistance inputs (Pt 100)

Measured-valuerepresentation

13 bits (two’s complement) or 12 bits + sign;
$ 2048 units in rated range;
512 to 2560 units for 4 to 20 mA

Measuring principle

Integrating

Isolation

Yes
8 inputs tested with respect to 0 V at 500 V AC

Permissible potential difference between reference potentials 25 V AC/60 V DC max.
of sensors and the module (UCM) and between sensors (channels)
Power Supply
– digital section from system bus
– analog section from load voltage
– enabling for module F+/F– tripping current L+

5 V $ 5 %; 130 mA typical
24 V; approx. 50 mA 1)
24 V; approx. 5 mA
24 V; approx. 5 mA

Constant current source for Pt 100 connection IC+/IC-

2.5 mA; TC = $ 5 x 10–5/K

Integration time

20 ms at 50 Hz; 16 2/3 ms at 60 Hz

Encoding time per measured value

60 ms at 50 Hz; 50 ms at 60 Hz

1)

System Manual
C79000-G8576-C199-06

Plus 20 mA max. per connected two-wire transducer.

9-29

Analog Input/Output Modules

Cycle time for 8 measured values with 2048 units
(max. delay time for measured-value acquisition)
Input resistance (with card) for input ranges:
$12.5 mV/$50 mV/$500 mV/Pt 100
$1 V
$5 V/$10 V
$5 V/$20 mA
4 to 20 mA
Measuring point-related error signal
– for overflow
– for broken wire
Max. permissible input voltage without destruction
Interference suppression for f = n x (50/60 Hz $1 %)
– with common-mode interference
– with differential-modeinterference
Error referred to rated value
– linearity
– tolerance
at w50 mV
at $ 12.5 mV
– polarity reversal error
at w 50 mV
at $12.5 mV
– temperature error

Approx. 0.48 s at 50 Hz

w 10 MW
90 kW
50 kW
25 W
31.25 W
Yes
Yes, configurable
(at $12.5 mV, $ 50 mV $ 500 mV and Pt 100 1) )
$18 V; 75 V for 1 ms max. and duty ratio 1:20
w 100 dB
w 40 dB, interference voltage amplitude
but 100 % max. of measuring range referred to peak value
$ 1 unit
$ 1 unit
$ 3 units
$ 1 unit
$ 2 units
1 x 10 –4 /K

Error caused by modules with input range
$ 1 V/$ 5 V /$ 10 V
$ 20 mA/4 to 20 mA

2 x 10 –3; TC = $ 10 x 10 –5 /K
10 –3; TC = $ 5 x 10 –5 /K

Voltage test to VDE 0160

Between inputs and ground point
tested at 500 V AC

Surge voltage test to IEC 255-4

Between inputs and L-:
Vp = 1 kV, 1.2/50 µs

Extended Pt 100 measuring range
Measuring range including overrange
Resolution
Basic error at T = 25 oC
Operational error at T = 0 to 65 oC
Range card
Environmental specifications

See technical specifications of the S5-135U/155U CC
1)

9-30

Approx. - 100 oC to + 100 oC
0.025 oC per unit
$0.2 oC max.
$0.5 oC max.
6ES5 498-1AA11

In the event of open-circuit of the live IC+ and IC- lines, the digital value 0 is indicated.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Setting the Mode

You select the desired mode of the analog input module by setting mode
switches I and II according to the following table.
Please note that all switch rockers marked with a dot must be set on both
mode switches. To set the desired mode, press the rockers downwards on the
side marked with a dot in the table.

Mode

Mode Switch I
(Digital Section)

Mode Switch II
(Digital Section)

Without reference point compensation

With reference point compensation
Measuring range
Extended Pt 100 measuring range
500 mV; mA (standard Pt 100 measuring
range)
50 mV
Value and sign
Two’s complement

Gain x 1
(normal setting)
Gain x4
Sampling
selective
cyclic
Line frequency
50 Hz
60 Hz
Channels 0 to 3
with broken wire signal
Channels 4 to 7
Channels 0 to 3
without broken wire signal
Channels 4 to 7
X = Switch is not assigned; any switch setting.
Ĥ = Switch setting

System Manual
C79000-G8576-C199-06

9-31

Analog Input/Output Modules

Labeling of switches on the module cover:

mark selected switch
positions here

broken wire detection
channel 4...7
without broken
wire detection

line frequency 60 Hz

singlescanning

SI

cyclicscanning

submodule1
(ch. 0...3)

line frequency 50 Hz

without
compensation
with
compensation
resistance thermometer
compensated low range
500 mV V...ma
resistance thermometer
uncompensated full range
50mV

DATA
FORMAT

broken wire detection
channel 0...3

INPUT RANGE

VOLTAGE
COMPENS.

mark selected switch
positions here

result and sign
two‘s complement

special mode (gain*4)

submodule 2
(ch. 4...7)

GAIN

normal mode (gain*1)

Inserting Range
Cards

Circuit of the
cards, 4x

SII

=press

On one 460 analog input module, you can insert two cards to connect four
inputs each, and secure them with a srew. There are voltage divider, shunt
and through-connection cards for the various ranges.

-1AA11
M+

M–

-1AA21
M+

M–

Range Card Type 6ES5 498–
-1AA31
-1AA41
-1AA51
M+
M+
M+

M–

M–

L+
L–
M–

-1AA61
M+

M–

M–

Mode
500 mV/ mA
Pt 100
+ Gain x 1
Mode
50 mV
+ Gain x 1

" 500 mV
Pt 100

"1 V

" 10 V

" 20 mA

" 50 mV

(" 100 mV)

(" 1 V)

(" 2 mA)

–

(" 500 mV)

–

Mode
500 mV/ mA
+ Gain x 4

(" 125 mV)

(" 250 mV) (" 2.5 V)

(" 5 mA)

–

(" 1.25 V)

–

Mode
50 mV
+ Gain x 4

(" 12.5 mV)

(" 25 mV)

9-32

–

–

4...20mA
2-wire transducer

–

"5V

-1AA71
M+

–

4...20mA
4-wire transducer

–

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

For a defined mode (50 mV or 500 mV) you can insert cards with different
ranges for four inputs, e.g. for the 500 mV mode:
4 inputs, range $ 500 mV; 1 card 6ES5 498-1AA11
4 inputs, range $ 10 V; 1 card 6ES5 498-1AA31

System Manual
C79000-G8576-C199-06

9-33

Analog Input/Output Modules

Front Connector
Assignments

Connection of
Process Signal
Lines
F+

Block Diagram
of the Modules

Pin
1

t

F–
L+

2
3

3
Ch.0

ADU

6
8

8

Ch.1
10

13
+
Ch.2

–

17
19

Comp.–

22

Comp.+

23

3) L+

24
25

+
1)

T 2)Ch.4
27
–
+

1)

34

T 2)Ch.6
–
36

9-34

L–

22

Comp.+

23

L+

24
25

3)
Ch.4

27
29
Ch.5
31

34
Ch.6
36
38
Ch.7
#

I

41
42

Itrip

L–
21

38

Figure 9-11

2)
3)
4)

L+

T 2)Ch.7
–
40

I+
c
I–
c

1)

Itrip

29

+

1)

L–

19
4)
L–
Comp.–

T 2)Ch.5
31
–

+
1)

17
Ch.3

Ch.3

21

L–

15

Range Card 2

4)

13
Ch.2

15

+
1)

10

Data Memory and S5 Bus Control

–

1)

Ch.1

Range Card 1
6ES5 498–1AA51

–

ADU

6

+
1)

t

4

+
– Ch.0

Pin
1
2

4
1)

Block Diagram
of the Modules

Data Memory and S5 Bus Control

L+

Front Strip

Range Card 1

F–

Front Strip

Range Card 2

Connection of
Process Signal
Lines
F+

Voltage or current-input resistance thermometer or connection of two-wire
transducer

I
const.

I

#
40

c+

41
42

c–

I
const.

Front Connector Assignments

Observe permissible potential difference between sensor ground and reference potential of modules or between
sensor grounds.
Two-wire transducer
Only required to switch off the tripping current without broken wire detection; 0 V at L-.
Connect L- to the central ground point (reference potential).

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.4

9.4.1

The 463 Analog Input Module

Design
The modules are designed as plug-in PCBs for central controllers and
expansion units with a backplane connector and with a blade connector to
accept a plug-in front connector. You can directly connect the process signal
lines to the front connector, which is available separately, with screw or
crimp terminals.

Addressing
Switch, Mode
Switches

Situated on each module is an addressing switch with six rockers to set the
module address. Analog input modules also have two switches on the side
with eight rockers for setting the mode, and receptacles for range cards.
The modules are protected by covers on both sides.
Addressing Switch
Blade Connector

Front Connector

Mode Switch

Figure 9-12

9.4.2

Analog Input Module

Function of the Enable Input
The 463 module has an enable circuit. You can use the enable inputs to
switch off individual modules whilst the PLC is in operation. This means
that:
The module can no longer be addressed by the user program.
Modules which are switched off can be removed or inserted during operation.
If this is not necessary, operate the module with the enable input switched
off.

System Manual
C79000-G8576-C199-06

9-35

Analog Input/Output Modules

Enable Input

The enable circuit requires an external 24 V voltage at enable inputs F+/F- in
the front connector. If there is no voltage at F+/F-, the modules will not
acknowledge.
When the front connector is swivelled away from the front strip of the
module, the supply of power to the enable input is interrupted, i.e. the
module is switched off and can no longer be addressed by the user program: a
timeout (QVZ) occurs in the CC.

Switching off the
Enable Input

The -4Ux12 type modules additionally offer the facility for changing the
enable mode. The modules have a jumper accessible from above in the
vicinity of the addressing switch.
Enable Jumper

Figure 9-13

Enable Input and Enable Jumper

Jumper inserted:
Jumper open:

Enable input (F+/F-) active (factory setting)
Enable input (F+/F-) switched off

Examples of functioning of the enable inputs:
To switch off individual subprocesses, i.e. outputs of various modules can
be operated from a common load supply and yet activated separately.
The load voltage of individual modules can be monitored without
additional circuitry. Any reactions to failure of the load voltage can be
programmed in the QVZ (timeout) organization block.

9-36

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Configuring

You must observe the following when configuring systems:
Switching on

At the latest 100 ms after power-up of the PLC, the voltage
must be present at the enable inputs of the I/O modules.

Switching off

When the PLC has been switched off, the voltage at the
enable inputs of the I/O modules must still be present as
long as the internal 5 V voltage is present.

Switching off the
CC

You should observe the following instructions for switching off CCs and
equipment for supplying power to the enable inputs.

Separate or
Common
Shutdown of the
CC/EU and Load
Power Supply

When there is a need to switch off the load power supply separately without
affecting the enabling of modules, there are the following possibilities for
producing the enable voltage. These exist even when the load power supply
is used without an additional capacitor and common shutdown.
230 V AC supply for CC/EU and load power supply
b)

a)

I/O Modules

–951

Battery
c)

F+
CC/EU

L+

Power Supply

L+

230 V AC
Load Power Supply 24V

Supply for the enable inputs from:
a) 6ES5 951-4LB11 load power supply
b) Battery
c) Terminals for 24 V on the front plate of the power supply

System Manual
C79000-G8576-C199-06

9-37

Analog Input/Output Modules

24 V supply for CC/EU and I/Os

a)
I/O Modules

Battery
b)

F+
CC/EU

L+

Power Supply 24V

L+

24 V DC

Supply for the enable inputs from:
a) Battery
b) Terminals for 24 V on the front plate of the power supply

Common
Shutdown of the
CC/EU and Load
Power Supply with
a 230 V AC Supply

Proper functioning is ensured if the 24 V load power supply has an output
capacitance of at least 4700 mF per 10 A of load current. Other units which
do not meet this condition can be adapted to this requirement by connecting a
10000 mF /40 V capacitor in parallel.

I/O Modules

F+
CC/EU
L+
230 V AC

Power Supply

10000µF/40V

Load Power Supply 24V

9-38

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.4.3

Special Features of the 463 Analog Input Module
The 463 analog input module executes integrating processing of the digital
input signals; periodic system interference is thus suppressed.

Adaptation of the
Measuring Range

The measuring range for each channel is adapted by appropriately connecting
the sensors and with jumpers in the front connector of the module (see the
front connector assignments).
Note
The ohmic resistance of the jumper with which the measuring range is set is
also measured. As the resistance of this jumper is not inconsiderable (0.5 to
0.7 ohms in relation to the measuring shunt of 50 ohms) when I/O module
cables with integral connectors and subsequent wiring blocks are used, the
measurement result may be corrupted accordingly.

9.4.4

Setting the Module Address
You set the module address on the addressing switch. This also establishes
the necessary assignments between user program and process connection.
The module address is the sum of the decimal significances of the switch
rockers in the On setting (Ĥ).
One data word = two data bytes is required to process an input or an output.
A module with 4 inputs therefore reserves 8 byte addresses.

Labeling Field

You can affix the adhesive label with the desired module address on a free
labeling field under the addressing switch.
The switch rockers to be set for the module address specified as a decimal
number (address bit ADB) are marked by dots on the label. The unmarked
switches should be switched off.

System Manual
C79000-G8576-C199-06

9-39

Analog Input/Output Modules

Press the individual rockers of the addressing switch downwards with a
ballpoint pen or similar object, but not a pencil.

On Setting
(Switch Pressed)

ADB1
ADB0

8

4
2
1

ADB3
ADB2

ADB7

ADB6
ADB5
ADB4

32

Decimal Significance of
the Address Bit

128
64

Adresse (dezimal)

Free Field for Label with
Module Address and
marked Switch Settings

16

Addressing Switch

Address Bit

ADB0 and ADB1 are not assigned
ADB2 is not connected

Figure 9-14

Labeling of the Addressing Switch

The address under which the module is referenced by the STEP 5 program is
independent of the slot.

Start Address,
Subaddress

For analog input and analog output modules (4 inputs) only the lowest
address (start address) is set. Other addresses (subaddresses) are decoded on
the module.
Note
The start address of the analog module must be a multiple of the double
channel number.
4 channels : 0, 8, 16, 24, ... 248

If one of the inputs or outputs (Channel 0 to 3) of a module is to be
addressed, the relevant subaddress must be specified in the program.
The subaddress of the input or output, based on the start address of the
module, is given by:
Start address + 2 x channel no. = subaddress

9-40

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Example:
Analog input module with 4 inputs
The address is the sum of the significances set with the individual coding
switches.
160 = 128 + 32 = 27 + 25

On Setting
(Switch Pressed)

8

16

32

4
2
1

ADB3
ADB2
ADB1
ADB0

ADB7

ADB6
ADB5
ADB4

128
64

IB 160

A module with 4 inputs (Channel 0 to 3) and start address 160 reserves the
address range from
160 to address 160 + 3 x 2 = 166
In this example, the next free address for another module is 168.
Addresses already assigned must not be set again.

Example:
On an analog input module with start address 160 (IB 160 = input byte 160),
input channel 3 is to be scanned by the program.

System Manual
C79000-G8576-C199-06

Step

Action

1

Affix the self-adhesive label with address 160 on the free field
under the addressing switch on the module. ADB 5 and ADB 7
are marked on the label.

2

Press the appropriate rockers of the addressing switch down on
the side marked by a dot on the module cover. Set the other
rockers to the opposite setting. This way sets the start address of
the module.
ADB 5 and ADB 7 results in 25 + 27 = 32 + 128 = 160

3

Enter the address 160 + 3 x 2 = 166 in the program for input
channel 3.

9-41

Analog Input/Output Modules

9.4.5

Removing and Inserting Modules

!

Warning
When removing and inserting the front connector during operation,
hazardous voltages of more than 25 V AC or 60 V DC may be present at the
module pins. When this is the case at the front connector, live modules may
only be replaced by electrical specialists or trained personnel in such a way
that the module pins are not touched.
During operation, the front connector and module must not be removed or
inserted without the enable jumper or active enable circuit.

Install an analog input/output module as follows:

9-42

Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and out.

2

Insert the module at the desired slot in the subrack and push it
back in the guides.

3

Latch the module by rotating the locking pin by 90o at the
lower end of the module. It must no longer be possible to pull
the module forwards.

4

Engage the front connector on the support pin of the module.
The width of the support pin also provides keying to prevent
front connectors from being fitted to the wrong modules (e.g.
front connectors with 115/230 V AC wiring cannot be plugged
into analog modules).

5

Tighten the screw in the upper part of the front connector.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Remove an analog input/output module as follows:
Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and out.

2

Slacken the screw in the upper part of the front connector. This
causes the front connector to be pressed out of the female connector of the module. Contacts F+ and F- of the enable input at
the upper end of the front connector are thus opened first. If the
enable input is active, power is removed from the outputs and
the module is isolated from the S5 bus.

3

Swing the front connector out and lift it away from the support
pin of the module.

4

Release the module by rotating the locking pin by 90 at the
lower end of the module. You can pull the module out of the
subrack with a grip with swivels outwards.
6

1

Module

Front
Connector

5
4
3

Figure 9-15
1
2
3
4
5
6

Support Mount
Support Pin

2

Module with Front Connector

Screw
Locking pin
Support mount
Support pin
Grip
Backplane connector

Comply with VDE Specifications 0110 and 0160 to carry out the wiring of
supply and signal lines which are to be connected to the programmable
controllers and front connectors of the modules.
Detailed information on cabinet assembly, cabinet ventilation and protective
measures can be found in Chapter 3.

System Manual
C79000-G8576-C199-06

9-43

Analog Input/Output Modules

9.4.6

Marking of Modules and Front Connectors
For the marking of modules and front connectors, labels are supplied with the
module and central controller; they are affixed as shown in Figure 9-16.

1

Figure 9-16
1
2
3
4
5

9-44

2 4

1

5

3

Marking and Labeling of Modules

Label with the module address under which the module is referenced by the STEP 5 program
Labeling strip with the product designation for the module; space to mark the module version
and label the channels
Label with module address and marking of the required settings for the addressing switch
Labeling strip for terminal designations or connection diagrams (strip in the cover of the
front connector)
Name plate

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.4.7

Connecting the Signal Lines
For connection of the signal lines, front connectors for 20 and 40 mm
mounting width with crimp connection and 40 mm mounting width with
screw connection are available (screwdriver blade width: 3.5 mm, maximum
torque: 0.8 Nm).
Use stranded conductor to facilitate handling of the front connector. Ferrules
are not required for screw connections, because the screw terminals are
provided with wire protection.
When the crimp contact is inserted in the plastic body of the front connector,
a click can clearly be heard. This indicates that the contact is engaged. For
jumpering or to correct the wiring, you can remove the contacts with a
releasing tool (see ordering information) without having to pull out the front
connector.
Ferrules are not required for screw connections, because the screw terminals
are provided with wire protection. You can use ferrules of 7 mm in length to
DIN 46228. The maximum terminal area is 2 x 2.5 mm2.

Terminal
T
Type

Connector
T
Type
6ES 497-

Cross-Section
Max.
N off
No.
Signal or Supply Aux. Jumper
Contacts
Conductor
in Connector

Connector for
R t dV
Rated
Voltage
lt

Mounting Width of
M d l
Module

1)

Crimp con- -4UA12 2)
nection

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

20 mm

-4UA22 2)

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

40 mm

-4UB12

42

0.5 to 2.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

40 mm

-4UB31

42

0.5 to 1.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

20 mm

Screw connection
ti

1)
2)

!

System Manual
C79000-G8576-C199-06

Operation
with fan
Operation
O
ti
without fan

To multiply the supply and 0 V ground terminals, and to connect the enable input
The crimp contacts must be ordered separately for these types of connector.

Caution
Only extra-low voltage 60 V DC with safety separation from system voltage
may be used for the 24 V DC supply and for the 24 V DC input signals.
Safety separation can be implemented to the requirements of, amongst other
sources, VDE 0100 Part 410/HD 384-4-41/IEC 364-4-41 (as functional
extra-low voltage with safety separation) or VDE 0805/EN 60950/IEC 950
(as safety extra-low voltage SELV) or VDE 0106 Part 101.

9-45

Analog Input/Output Modules

9.4.8

Measured-Value Representation

Measured-Value
Representation as
Value and Sign
Units

(rated input ranges 0 to 1 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA)

Rated Range

Byte 0

Byte 1

0...10
V

0...1 V
mV

0... 20
mA

4...20
mA 1)

4...20
mA 2)

7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
211 210 29 28 27 26 25 24 23 22 21 20 0 0 0 OV

2047
1536

19.99
15.00

1999
1500

39.98
30.00

35.98
28.00

31.98
24.00

0
0

1
1

1 1 1 1 1 1 1 1 1 1 0 0 0 1
1 0 0 0 0 0 0 0 0 0 0 0 0 1

3)

1535
1280
1025

14.99

1499

29.98

27.98

1001

20.02

20.02

0
0
0

1
1
1

0 1 1 1 1 1 1 1 1 1 0 0 0 0
0 1 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 1 0 0 0 0

4)

10.01

23.98
20.00
16.02

1024
1023
512
511
256
1
0
–1
– 51

10.00
9.99
5.00
4.99

1000
999.02
500.00
499.00
0.976
0
–
0.976
–50

20.00
19.98
10.00
9.98

20.00
19.98
12.00
11.98
4.0156
4
3.9844
3.184

0
0
0
0
0
0
0
1
1

1
0
0
0
0
0
0
1
1

0
1
1
0
0
0
0
1
1

5)

0.02
0
–0.02
–1

16.00
15.98
8.00
7.98
4.00
0.0156
0
–0.015
6
–0.816

0.098
0
–
0.098
– 0.5

1)
2)
3)
4)
5)

0
1
0
1
1
0
0
1
1

0
1
0
1
0
0
0
1
1

0
1
0
1
0
0
0
1
1

0
1
0
1
0
0
0
1
0

0
1
0
1
0
0
0
1
0

0
1
0
1
0
0
0
1
1

0
1
0
1
0
0
0
1
1

0
1
0
1
0
0
0
1
0

0
1
0
1
0
1
0
1
1

0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0

With data format setting 0 to 1023 (switch on module)
With data format setting 256 to 1279 (switch on module)
Overflow
Overrange
Rated range

OV = Overflow bit

Shunt Resistor

A 50 ohm shunt resistor is used for the 0 to 20 mA range; for 4 to 20 mA,
the resistor value is 62.5 ohms.
The shunt resistors are permanently fitted to the 463 analog input module.
Broken wire detection is not possible.
For the 4 to 20 mA current measuring range, a broken wire can be detected
with currents > 3 mA.

Current Limiting

If the positive and negative terminals of the transducer are short-circuited
when two-wire transducers are used (4 to 20 mA), the current is limited to
approximately 28 mA. Until the thermal current limiting circuit responds
(about 3 s) a short-circuit current of about 250 mA flows; this sets the
overflow bit for the short-circuited channel for this duration.

Load Voltage

The failure of the load voltage can be detected from the result of encoding
(values < -51 units).

9-46

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.4.9

Technical Specifications
6ES5 463-4UA12 and 6ES5 463-4UB12 Analog Input Modules

Rated input ranges
(selectable at front connector)

- 0.05 to + 1 V
- 0.5 to + 10 V
-1 to + 20 mA
+ 4 to 20 mA for 2-wire transducer
+ 4 to 20 mA for 4-wire transducer

Number of inputs

4 voltage/current inputs

Measured value representation

11 bits (two’s complement)
1024 units in rated range

Overrange

50 % (with full accuracy)

Error signal for overflow

Yes (upward of 50 % overrange)

Measuring principle

Integrating

Conversion principle

Voltage-frequency conversion

Isolation

Yes, 4 inputs with respect to 0 V and each other

Permissible potential difference between ref. potentials of 25 V AC/60 V DC max.
sensors and module (UCM) and between sensors (channels)
Power Supply
– digital section from system bus
– analog section from load voltage
– enabling of module F+/F-

5 V $ 5 %; 150 mA typical
24 V; approx. 150 mA
24 V; approx. 7 mA

Integration time
– 463-4UA12
– 463-4UB12

20 ms at 50 Hz
16 2/3 ms at 60 Hz

Encoding time per measured value
– 463-4UA12
– 463-4UB12

20 ms at 50 Hz
16 2/3 ms at 60 Hz

Cycle time for 4 measured values (max. delay time of
measured value acquisition)
– 463-4UA12
– 463-4UB12

20 ms at 50 Hz
16 2/3 ms at 60 Hz

Input resistance for input ranges
1V
10 V
20 mA
4 to 20 mA

> 10 MW
90 kW
50 W
62.5 W

Max. permissible input voltage without destruction

$ 30 V; 75V for 1 ms max. and duty ratio 1:10

Interference suppression
– with common-mode interference
– with differential-modeinterference

> 80 dB (f = 0 to 50 kHz)
> 40 dB (Vnoise v 0.1 UN)

Error, referred to
– rated value
– linearity
– tolerance
– temperature error

$ 5 x 10–4
$ 1 unit
$ 3 units
0.6 x 10–4/K

Voltage test to VDE 0160

Between inputs and ground point, and between 2 inputs;
tested at 500 V AC

Surge voltage test to IEC 255-4

Between inputs and L-: Vp = 1kV; 1.2/50 µs

System Manual
C79000-G8576-C199-06

9-47

Analog Input/Output Modules

Setting the Data
Format for the 4 to
20 mA Range

When using the 4 to 20 mA inputs, you can select data representation of 0 to
1023 bits or 256 to 1279 bits by pressing the appropriate switch. You can
choose different data formats for all four input channels.
When the voltage or 0 to 20 mA inputs are used, the relevant switches remain
at the opposite settings.
Labeling of the switch on the module cover:

channel 0
range 4...20 mA
0...1023

channel 1
channel 2
channel 3
1)

range 4...20 mA
256...1279
otherranges
0...1023

channel 3
channel 2
channel 1
channel 0

1) It is advisable to mark the selected switch setting in these fields.

Connecting
Transducers

Transducers are connected to the analog input module via shielded cables of
up to 200 m in length. When they are laid separately from power system
cables, distances of up to 500 m are possible.
An arbitrary mixture of voltage sensor, current sensor, two-wire and
four-wire transducers can be connected. For two-wire transducers, there are
four short-circuit protected supply terminals at the front connector.

!

Caution
To use two-wire transducers, the reference potential (common input) of these
channels must be connected to L-. This defeats the isolation between the
channels and the supply voltage L+/L-.

Note that the bus interface of the module is activated with 24 V via enable
lines F+ and F- at the front connector.

9-48

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Front Connector
Assignments

F+
F–
L+

F+
F–
L+

F+
F–
L+
+

+

5
+ 6

6

+

1
2
3
4

4

MU
+

5
6

–

7
8

– 6
– 7

– 7

– 7

7

+
+
+

14

15

+

– 16

L–

– 16

15

+
– 15
16

– 16

L–

+
+
+

26

27

13

MU

L–

L–

9
10
11
12
13

–

L–

25

MU
+

27

+
– 27

–

28

– 28

–

28

28

–

14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

+
+
+

35

36

+

36

33
34

34

MU

+

35
36

–

37
38

– 36
– 37

– 37

– 37

37

39
40
41
42

Figure 9-17

Block Diagram
of the Module

Pin
t
L+
+
+10V
+1V
Common
Common
0–10V
0–20mA
4–20mA
+
+10V
+1V
Common
Common
0–10V
0–20mA
4–20mA
L–
Ch.0 Ch.1 Ch.2 Ch.3
+

Busansteuerung

F+
F–
L+

Front Strip

Data Memory

F+
F–
L+

Range
Range
4–20mA
4–20mA
(2–wiretransd.) (4–wire ransd.)

Data Memory

Range
0–20mA

+ 15V
4x –

+10V
+1V
Common
Common
0–10V
0–20mA
4–20mA

Data Memory

Range
0–10V

+
+10V
+1V
Common
Common
0–10V
0–20mA
4–20mA

Data Memory

Range
0–1V

+
– 15V

Front Connector Assignments, Sensor Connection, Range Selection

System Manual
C79000-G8576-C199-06

9-49

Analog Input/Output Modules

9.5
9.5.1

The 465 Analog Input Module
Design
The modules are designed as plug-in PCBs for central controllers and
expansion units with a backplane connector and with a blade connector to
accept a plug-in front connector. You can directly connect the process signal
lines to the front connector, which is available separately, with screw or
crimp terminals.

Addressing
Switch, Mode
Switches

Situated on each module is an addressing switch with six rockers to set the
module address. Analog input modules also have two switches on the side
with eight rockers for setting the mode, and receptacles for range cards.
The modules are protected by covers on both sides.
Addressing Switch
Blade Connector

Front Connector

Mode Switch
Figure 9-18

9.5.2

Analog Input Module

Function of the Enable Input
The 465 module has an enable circuit. You can use the enable inputs to
switch off individual modules whilst the PLC is in operation. This means
that:
The module can no longer be addressed by the user program.
Modules which are switched off can be removed or inserted during operation.
If this is not necessary, operate the module with the enable input switched
off.

9-50

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Enable Input

The enable circuit requires an external 24 V voltage at enable inputs F+/F- in
the front connector. If there is no voltage at F+/F-, the modules will not
acknowledge.
When the front connector is swivelled away from the front strip of the
module, the supply of power to the enable input is interrupted, i.e. the
module is switched off and can no longer be addressed by the user program: a
timeout (QVZ) occurs in the CC.

Switching Off the
Enable Input

The 465 module additionally offers the facility for changing the enable
mode. The module has a jumper accessible from above in the vicinity of the
addressing switch.

Enable Jumper

Figure 9-19

Enable Input and Enable Jumper

Jumper inserted: Enable input (F+/F-) active (factory setting)
Jumper open:
Enable input (F+/F-) switched off
Examples of functioning of the enable inputs:
To switch off individual subprocesses, i.e. outputs of various modules can
be operated from a common load supply and yet activated separately.
The load voltage of individual modules can be monitored without
additional circuitry. Any reactions to failure of the load voltage can be
programmed in the QVZ (timeout) organization block.

System Manual
C79000-G8576-C199-06

9-51

Analog Input/Output Modules

Configuring

You must observe the following when configuring systems:
Switching on

At the latest 100 ms after power-up of the PLC, the voltage
must be present at the enable inputs of the I/O modules.

Switching off

When the PLC has been switched off, the voltage at the
enable inputs of the I/O modules must still be present as
long as the internal 5 V voltage is present.

Switching off the
CC

You should observe the following instructions for switching off CCs and
equipment for supplying power to the enable inputs.

Separate or
Common
Shutdown of the
CC/EU and Load
Power Supply

When there is a need to switch off the load power supply separately without
affecting the enabling of modules, there are the following possibilities for
producing the enable voltage. These exist even when the load power supply
is used without an additional capacitor and common shutdown.
230 V AC supply for CC/EU and load power supply

b)

a)

Battery

I/O Modules

–951

c)

F+
CC/EU

L+

Power Supply

L+

230 V AC
Load Power Supply 24V

Supply for the enable inputs from:
a) 6ES5 951-4LB11 load power supply
b) Battery
c) Terminals for 24 V on the front plate of the power supply

9-52

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

24 V supply for CC/EU and I/Os

a)
I/O Modules

Battery
b)

F+
CC/EU

L+

Power Supply 24V

L+

24 V DC

Supply for the enable inputs from:
a) Battery
b) Terminals for 24 V on the front plate of the power supply

Common
Shutdown of the
CC/EU and Load
Power Supply with
a 230 V AC Supply

Proper functioning is ensured if the 24 V load power supply has an output
capacitance of at least 4700 mF per 10 A of load current. Other units which
do not meet this condition can be adapted to this requirement by connecting a
10000 mF / 40 V capacitor in parallel.

I/O Modules

F+
CC/EU
L+
230 V AC

Power Supply

10000µF/40V

Load Power Supply 24V

System Manual
C79000-G8576-C199-06

9-53

Analog Input/Output Modules

9.5.3

Special Features of the 465 Analog Input Module
The 465 analog input module executes integrating processing of the digital
input signals; periodic system interference is thus suppressed.
You can adapt the process signals, according to the application, to the input
level of the analog-to-digital converter of the module with plug-in range
cards (resistor dividers or shunt resistors).

Broken Wire
Signal

To monitor the sensors connected to the inputs, you can use the
6ES5 498-1AA11 range card (through-connection card) to implement the
“broken wire detection” mode. You can activate broken wire detection for 8
or 16 inputs in 16-channel operation, and for 4 or 8 inputs in 8-channel
operation.
Each time the input value is about to be encoded, a constant current is briefly
(1.6 ms) switched to the input terminals and the resultant current is checked
for a limit value. If a digital voltmeter is used to measure the signal at the
input, these current pulses may appear to indicate fluctuation of the signal.
The encoded value, however, is not affected.

Switching the
Tripping Current to
the Inactive State

If these apparent fluctuations of the signal are disturbing, e.g. during startup,
you can switch the tripping current to the inactive state on the 465 analog
input modules: apply + 24 V to pin 24 of the front connector, and 0 V to L-.
You must additionally set the mode switch to “without broken wire
detection.”
In the event of open-circuit of the sensor or its line, the voltage exceeds the
limit and a broken wire is indicated (bit 1 in data byte 1). The
analog-to-digital converter encodes the value 0.
A broken wire signal is only useful when the 6ES5 498-1AA11
through-connection card is used. With all other measurement cards, a broken
wire signal will result in incorrect reactions. Further details relating to the
broken wire signal can be found in Section 9.5.10.

Measuring Range
Exceeded

If the measuring range is exceeded, the overflow bit (bit 20 of the low byte)
is set.

Cyclic Sampling/
Selective Sampling

You have a choice of the cyclic sampling and selective sampling modes.

9-54

In the cyclic sampling mode, the module continuously encodes all measured
values. The digitized measured values are stored under the channel-related
address on the module (the high byte under this address, and the low byte
under the next higher address). The measured values can then be read by the
module at any time without waiting. When you operate the module in this
mode, you can set a module address from 0 to 255.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

In the selective sampling mode, a measured value is encoded on the central
initiative of the CPU. At the start of conversion, the module must be
addressed once with a write operation (T PW) by the user program. An active
bit (T = 1) is set during encoding.
With the transition to T = 0, the measured value becomes valid. With
non-constant cycle times, there may be non-periodic measured value
aquisition. If you operate the module in this mode, you must set a module
address from 128 to 255. You can also use the address range from 0 to 127
for selective sampling after appropriate programming in DB 1 of the user
program.

Time-Controlled
Program
Processing

Another method is that of time-controlled program processing. With this
method, certain program segments (e.g. FB 13) are automatically inserted
into program processing at the 100 ms rate by a timecontrolled block (OB 13). A constant timebase is thus achieved.
FB 13

SPRM-B

SEGMENT 1
NAME: SELSAMPL
0005
0006
0007
0008
0009
000A
000B
000C
000D
000E
000F
0010

END

:
:
:L
:T
:S
:JC
:T
:T
:

LEN=22

ABS
SHEET 1

EXAMPLE OF SELECTIVE SAMPLING

PW128
FW128
F 129.2
= END
FW10
PB128

READ ANALOG VALUE
IN TO AUX: FLAG 128
SCAN ACTIVITY=1?
IF = 1, JUMP TO END
IF = 0, MEASURED VALUE IN FW 10
INITIATE SAMPLING
(1ST VALUE INVALID AFTER START)

:
:BE

Function Block

You can read analog values of analog input modules with a function block
from the “basic functions” package.

BASP (Output
Inhibit)

The BASP signal is not interpreted by the 460 analog input module.

System Manual
C79000-G8576-C199-06

9-55

Analog Input/Output Modules

9.5.4

Setting the Module Address
You set the module address on the addressing switch. This also establishes
the necessary assignments between user program and process connection.
The module address is the sum of the decimal significances of the switch
rockers in the On setting (Ĥ).
One data word = two data bytes is required to process an input. A module
with 8 inputs therefore reserves 16 byte addresses, and a module with 16
inputs or outputs reserves 32 byte addresses.

Labeling Field

You can affix the adhesive label with the desired module address on a free
labeling field under the addressing switch.
The switch rockers to be set for the module address specified as a decimal
number (address bit ADB) are marked by dots on the label.
Press the individual rockers of the addressing switch downwards with a
ballpoint pen or similar object, but not a pencil.

On Setting
(Switch Pressed)

Addressing Switch

Free Field for Label with
Module Address and
marked Switch Settngs

ADB1
ADB0

8

16

32

4
2
1

ADB3
ADB2

ADB7

ADB6
ADB5
ADB4

128
64

Address (Decimal)

Decimal Signification of
the Address Bit

Address Bit

ADB0 and ADB1 are not assigned
ADB2 is not connected

Figure 9-20

Labeling of the Addressing Switch

The address under which the module is referenced by the STEP 5 program is
independent of the slot.

Start Address,
Subaddress

9-56

For analog input and analog output modules (8 or 16 inputs) only the lowest
address (start address) is set. Other addresses (subaddresses) are decoded on
the module.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Note
The start address of the analog module must be a multiple of the double
channel number.
8 channels : 0, 16, 32, 48, ... 240
16 channels : 0, 32, 64, 96, ... 224
If one of the inputs or outputs (Channel 0 to 7 or 0 to 15) of a module is to be
addressed, the relevant subaddress must be specified in the program.
The subaddress of the input or output, based on the start address of the
module, is given by:
Start address + 2 x channel no. = subaddress
Example:
Analog input module with 8 or 16 inputs
The address is the sum of the significances set with the individual coding
switches.
160 = 128 + 32 = 27 + 25

On Setting
(Switch Pressed)

ADB1
ADB0

8

16

4
2
1

ADB3
ADB2

64
32

ADB7
ADB6
ADB5
ADB4

128

IB 160

A module with 8 or 16 inputs (Channel 0 to 7 or 0 to 15) and start address
160 reserves the address range from
160 to address 160 + 7 x 2 = 174
160 to address 160 + 15 x 2 = 190
In this example, the next free address for another module is 176 or 192.
With the 465 analog input module, the size of the address range depends on
the number of channels set (8 or 16).
Addresses already assigned must not be set again.

System Manual
C79000-G8576-C199-06

9-57

Analog Input/Output Modules

Addressing for
Cyclic/Selective
Sampling

However, analog input modules and analog output modules may be given the
same address with cyclic sampling because they are distinguished by the user
program. This is not possible with selective sampling.
For cyclic sampling, you can address the module in the address range from 0
to 255, and for selective sampling from 128 to 255. For selective sampling,
you can also use the address range from 0 to 127 after appropriate
programming in DB 1 of the user program.
Example:
On an analog input module with start address 160 (IB 160 = input byte 160),
input channel 3 is to be scanned by the program.

9-58

Step

Action

1

Affix the self-adhesive label with address 160 on the free field under the
addressing switch on the module. ADB 5 and ADB 7 are marked on the
label.

2

Press the appropriate rockers of the addressing switch down on the side
marked by a dot on the module cover. Set the other rockers to the opposite
setting. This way sets the start address of the module.
ADB 5 and ADB 7 results in 25 + 27 = 32 + 128 = 160

3

Enter the address 160 + 3 x 2 = 166 in the program for input channel 3.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.5.5

Removing and Inserting Modules

!

Warning
When removing and inserting the front connector during operation,
hazardous voltages of more than 25 V AC or 60 V DC may be present at the
module pins. When this is the case at the front connector, live modules may
only be replaced by electrical specialists or trained personnel in such a way
that the module pins are not touched.
During operation, the front connector and module must not be removed or
inserted without the enable jumper or active enable circuit.

Install an analog input/output module as follows:

System Manual
C79000-G8576-C199-06

Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Insert the module at the desired slot in the subrack and push it back in the
guides.

3

Latch the module by rotating the locking pin by 90o at the lower end of
the module. It must no longer be possible to pull the module forwards.

4

Engage the front connector on the support pin of the module. The width
of the support pin also provides keying to prevent front connectors from
being fitted to the wrong modules (e.g. front connectors with 115/230 V
AC wiring cannot be plugged into analog modules).

5

Tighten the screw in the upper part of the front connector.

9-59

Analog Input/Output Modules

Remove an analog input/output module as follows:
Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Slacken the screw in the upper part of the front connector. This causes the
front connector to be pressed out of the female connector of the module.
Contacts F+ and F- of the enable input at the upper end of the front connector are thus opened first. If the enable input is active, power is removed
from the outputs and the module is isolated from the S5 bus.

3

Swing the front connector out and lift it away from the support pin of the
module.

4

Release the module by rotating the locking pin by 90o at the lower end of
the module. You can pull the module out of the subrack with a grip with
swivels outwards.

6

Module

1

Front
Connector

Support Mount
5

Support Pin

4
2
3

Figure 9-21
1
2
3
4
5
6

Module with Front Connector

Screw
Locking pin
Support mount
Support pin
Grip
Backplane connector

Comply with VDE Specifications 0110 and 0160 to carry out the wiring of
supply and signal lines which are to be connected to the programmable
controllers and front connectors of the modules.
Detailed information on cabinet assembly, cabinet ventilation and protective
measures can be found in Chapter 3.

9-60

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.5.6

Marking of Modules and Front Connectors
For the marking of modules and front connectors, labels are supplied with the
module and central controller; they are affixed as shown in Figure 9-5.

1

Figure 9-22
1
2
3
4
5

System Manual
C79000-G8576-C199-06

2 4

1

5

3

Marking and Labeling of Modules

Label with the module address under which the module is referenced by the STEP 5 program
Labeling strip with the product designation for the module; space to mark the module version
and label the channels
Label with module address and marking of the required settings for the addressing switch
Labeling strip for terminal designations or connection diagrams (strip in the cover of the
front connector)
Name plate

9-61

Analog Input/Output Modules

9.5.7

Connecting the Signal Lines
For connection of the signal lines, front connectors for 20 and 40 mm
mounting width with crimp connection and 40 mm mounting width with
screw connection are available (screwdriver blade width: 3.5 mm, maximum
torque: 0.8 Nm).
Use stranded conductor to facilitate handling of the front connector. Ferrules
are not required for screw connections, because the screw terminals are
provided with wire protection.
When the crimp contact is inserted in the plastic body of the front connector,
a click can clearly be heard. This indicates that the contact is engaged. For
jumpering or to correct the wiring, you can remove the contacts with a
releasing tool (see ordering information) without having to pull out the front
connector.
Ferrules are not required for screw connections, because the screw terminals
are provided with wire protection. You can use ferrules of 7 mm in length to
DIN 46228. The maximum terminal area is 2 x 2.5 mm2.

Terminal
T
Type

Connector
T
Type
6ES 497-

Cross-Section
Max.
N off
No.
Signal or Supply Aux. Jumper
Contacts
Conductor
in Connector

Connector for
R t dV
Rated
Voltage
lt

Mounting Width of Mod
l
ule

1)

Crimp con- -4UA12 2)
nection

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

20 mm

-4UA22 2)

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

40 mm

-4UB12

42

0.5 to 2.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

40 mm

-4UB31

42

0.5 to 1.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

20 mm

Screw connection
ti

1)
2)

!

9-62

Operation
with fan
Operation
O
ti
without fan

To multiply the supply and 0 V ground terminals, and to connect the enable input
The crimp contacts must be ordered separately for these types of connector.

Caution
Only extra-low voltage 60 V DC with safety separation from system voltage
may be used for the 24 V DC supply and for the 24 V DC input signals.
Safety separation can be implemented to the requirements of, amongst other
sources, VDE 0100 Part 410/HD 384-4-41/IEC 364-4-41 (as functional
extra-low voltage with safety separation) or VDE 0805/EN 60950/IEC 950
(as safety extra-low voltage SELV) or VDE 0106 Part 101.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.5.8

Connecting a Compensating Box for Thermal E.M.F.
Measurement
If the room temperature fluctuations at the reference point (e.g. in the
terminal box) affect the measurement result and you do not wish to use a
thermostat, you can compensate for the effect of temperature on the reference
point with a compensating box. Between - 10 and + 70 oC, it compensates for
the change in thermal e.m.f. cause by temperature deviation (compensating
box, see Catalog MP 11). Ensure that the compensating box has thermal
contact with the terminals.
If the compensating box is aligned at 20 oC, this must be taken into account
in temperature evaluation (20 oC measuring point temperature = 0 mV).
Pins 22 and 23 are extended on analog input modules as an input for the
compensating voltage. You must select a common input loop for all inputs on
mode switch 2.
The compensating box must be connected in a floating circuit. The power
supply unit of the compensating box must have a grounded shield winding to
avoid AC system interference being picked up. A separate compensating box
with its special power supply unit is required for each analog input module.

Analog Input Module
Terminal Box
Thermocouple

A

M+
M–

–

MUX
Range
Card for
4 Inputs
6ES5 498-1AA11
#

Compensating
Box

+

D
22–
23+

0 V Bus
Power
Supply
for Compensating Box

Figure 9-23

=

~

Connecting a Compensating Box

System Manual
C79000-G8576-C199-06

9-63

Analog Input/Output Modules

9.5.9

Connecting Resistance Thermometers to the 465 Analog Input
Module
The relevant resistance thermometer is fed with a current of 2.5 mA (IC+/IC-)
by a constant current generator via a 6ES5 498-1AA11 card. The voltage at
the Pt 100 is picked off at measurement inputs M+ and M-.
If only inputs 0 to 3 are assigned to resistance thermometers, you can connect
other current and voltage sensors to inputs 4 to 7 by means of a coding key. If
you use the Pt 100 for measurement, you cannot utilize channels 12 to 15.
Channels 8 to 11 supply the resistance thermometers which are connected at
inputs 0 to 3.
Note that the mode of the module is set to the 500 mV voltage range.

9-64

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

465 Analog Input Module
–

Card 1

Pt100

M+

+
CH0

M–
A

2)

Range
Card for
4 Inputs
6ES5-498-1AA11

2)
0...500mV

#
CH3
1)
Card 2

U/I

D
MUX

6ES5498CH4
-1AA11
U
CM

-1AA21
2)

-1AA31

U
CM

-1AA41
2)

-1AA51
-1AA61

2)

-1AA71

CH7

1)
I

const.

IC+
I
C–
2)

2)

Card 3
M+
M–

Range
Card for
4 Inputs
6ES5-498-1AA11
I
const.
2.5mA

2)

Card 4
2)

2)

2)

2)

+5V
Current Source for
Pt 100 Operation

Range
Card for
4 Inputs
6ES5-498-1AA11
-1AA41
-1AA71
2)

Figure 9-24

Connecting a Pt 100

1) When cards 6ES5 498-1AA21, 6ES5 498-1AA31 or 6ES5 498-1AA61 are used, no broken wire signal may be activated for this
group of channels (CH4 to CH7).
2) If cards 6ES5 498-1AA41 or 6ES5 498-1AA71 are used, a short-circuit jumper is not required.

System Manual
C79000-G8576-C199-06

9-65

Analog Input/Output Modules

9.5.10

Broken Wire Signal for Resistance Thermometers
An open-circuit in the lines to a resistance thermometer is indicated as
follows:

Broken Wire at
M+
M–
Pt 100
IC+
IC–

Module Reaction, Encoded Value
0
0
0
0
0

Error Bit E
1
1
1
1
1

If the mode “without broken wire signal” is selected on the module, an
open-circuit of the resistance thermometer is indicated with an overflow.
Unassigned channels can be used for voltage or current measurement if the
current flow outputs relating to the particular measuring channel are shorted
with a wire jumper. Without this jumper, the error bit would be set for this
channel and the value 0 would be encoded.

Broken Wire
Monitoring

When set to “resistance thermometer,” switch 7 of mode switch I of the 465
analog input module allows broken wire monitoring of the IC+ lines to the
resistance thermometer (Pt 100 constant current supply). In the event of
open-circuit of this line, the error bit is set as for the other lines.
At the “voltage/current” (mV/mA) setting, the IC+ lines are not monitored for
broken wire. (The error bit is not set for an open-circuit of this line.) You
should choose this switch setting if you exclusively measure voltages or
currents.

9-66

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.5.11

Connecting Transducers
Two-wire transducer (short-circuit protected supply voltage via the range
card of the analog input module)
L+

L–

Analog Input Module

M+

A

4...20 mA

+

MUX
Range
Card for
4 Inputs
6ES5-498-1AA51

–

M–

#

D

0 V Bus

Four-wire transducer (with separate supply voltage)
Analog Input Module

M+
230 V AC

A

+4...20 mA

+

MUX
Range
Card for
4 Inputs
6ES5-498-1AA71

–

M–

#

D

Do not exceed max. permissible potential difference!

0 V Bus

Four-wire transducer with a two-wire transducer card
M+

L+

L–

Analog Input Module

230 V AC
+

A

0...20 mA

MUX

–
M–

Range
Card for
4 Inputs
6ES5-498-1AA71

#

D

L– (0 Vext)

System Manual
C79000-G8576-C199-06

0 V Bus

9-67

Analog Input/Output Modules

9.5.12

Measured-Value Representation

Digital
Measured-Value
Representation as
Two’s Complement
Units

Input Voltage iin mV
V

(rated input range $ 50 mV)

Byte 0

Byte 1

7
6
5
4 3 2
1 0 7 6 5
4 3 2
212 211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

0
OV

w4096

100.0

0

1

1

1

1

1

1

1

1

1

1

1

1

0/1 0/1 1

Overflow

4095
2049

99.976
50.024

0
0

1
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

2048
2047

50.0
49.976

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1024
1023

25.0
23.976

0
0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1
0
–1

0.024
0.0
–0.024

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

1
0
1

0/1 0/1 0
0/1 0/1 0
0/1 0/1 0

–1023
–1024

– 24.976 1
– 25.0
1

1
1

1
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0

0/1 0/1 0
0/1 0/1 0

–2047
–2048

– 49.976 1
– 50.0
1

1
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0

0/1 0/1 0
0/1 0/1 0

–2049
–4095

– 50.024 1
– 99.976 1

0
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

–4096

–100.0

0

0

0

0

0

0

0

0

0

0

0

1

0/1 0/1 1

Overflow

1

Rated
range

A = Active bit
E = Error bit
OV = Overflow bit

9-68

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Digital
Measured-Value
Representation as
Value and Sign
Units

Input Voltage iin mV
V

(rated input range $ 50 mV)

Byte 0

Byte 1

7
S

6
5
4 3 2
1 0 7 6 5
4 3 2
211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

0
OV

w4096

100.0

0

1

1

1

1

1

1

1

1

1

1

1

1

0/1 0/1 1

Overflow

4095
2049

99.976
50.024

0
0

1
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

2048
2047

50.0
49.976

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1024
1023

25.0
23.976

0
0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0/1 0/1 0
0/1 0/1 0

1
0
–0
–1

0.024
0.0
0.0
–0.024

0
0
1
1

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

0
0
0
0

1
0
0
1

0/1
0/1
0/1
0/1

–1023
–1024

– 24.976 1
– 25.0
1

0
0

0
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

0/1 0/1 0
0/1 0/1 0

–2047
–2048

– 49.976 1
– 50.0
1

0
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

0/1 0/1 0
0/1 0/1 0

–2049
–4095

– 50.024 1
– 99.976 1

1
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

1
1

0/1 0/1 0
0/1 0/1 0

Overrange

–4096

–100.0

1

1

1

1

1

1

1

1

1

1

1

1

0/1 0/1 1

Overflow

1

0/1
0/1
0/1
0/1

0
0
0
0

Rated
range

A = Active bit
E = Error bit
OV = Overflow bit

Bit 212 is interpreted as the sign.

System Manual
C79000-G8576-C199-06

9-69

Analog Input/Output Modules

The resolution with Pt 100 resistance thermometers is approximately 0.25 oC.
1 ohm  10 units

Measured-Value
Representation for
Pt 100 Resistance
Thermometers

Units Resistance in Temperohms 1)
ature in
oC

Byte 0

Byte 1

7
S

6 5 4 3 2 1 0 7 6 5 4 3 2
211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

0
OV

0

1

1

1

1

1

1

1

1

1

1

1

1

269.1

0
0

1
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1 0/1 0/1 0
1 0/1 0/1 0

4096

400.0

–

4095
2049

399.90
200.98

–

2048
2047

200.0
199.90

266.5
266.0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0 0/1 0/1 0
1 0/1 0/1 0

1024
1023

100.00
99.90

0
–0.2

0
0

0
0

1
0

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0
1

0 0/1 0/1 0
1 0/1 0/1 0

1
0

0.098
0.0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1 0/1 0/1 0
0 0/1 0/1 0

–
–

0/1 0/1 1

Overflow
Overrange

Rated range

1) Resistance value PT 100
A = Active bit
E = Error bit
OV = Overflow bit
S = Sign

When Pt 100 resistance thermometers are connected, the maximum
temperature in the rated range is 266 oC. If it can be ensured that the
temperature does not exceed 850 oC, the input value may extend into the
overrange. The resolution is then 4095 units. Unused inputs can be utilized
for voltage measurements in the 500 mV range (see front connector
assignments).

9-70

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Measured-Value
Representation for
Current Measuring
Ranges from 4 to
20 mA

Measuring range 500 mV; card with 31.25 ohm shunt
(6ES5 498-1AA51/AA71)
The 4 to 20 mA range is resolved to 2048 units at an interval of 512 to 2560.
If you require a representation from 0 to 2048, you must subtract 512 units by
software. Please note the following:
A broken wire signal cannot be emitted.
Detection of the overrange can be achieved by scanning bits 29 and 211.
A broken wire can be detected with currents < 3 mA.

Current Limiting
If you short-circuit the positive and negative terminals of the transducer
when using the 6ES5 498-1AA51 range card (for a two-wire transducer),
the current is limited to about 28 mA. Until the thermal current limiting
circuit responds in the range card (about 3 s), a short-circuit current of
approximately 250 mA flows; this sets the overflow bit for this duration
at all channels.

Units

Input Currentt in
i mA
A

Byte 0

Byte 1

7
S

6 5 4 3 2 1 0 7 6 5 4 3 2
211 210 29 28 27 26 25 24 23 22 21 20 A

1 0
E OV

w 4096 w 32.000

0

1

1

1

1

1

1

1

1

1

1

1

1

0/1

0

1

Overflow

4095
3072
3071
2561

31.992
24.0
23.992
20.008

0
0
0
0

1
1
1
1

1
1
0
0

1
0
1
1

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1
0
1
0

1 0/1
0 0/1
1 0/1
1 0/1

0
0
0
0

0
0
0
0

Overrange
Short-circuit with twowire transducer

2560
2048
512

20.0
16.0
4.0

0
0
0

1
1
0

0
0
0

1
0
1

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0 0/1
0 0/1
0 0/1

0
0
0

0
0
0

511
384
383

3.992
3.0
2.992

0
0
0

0
0
0

0
0
0

0
0
0

1
1
1

1
1
0

1
0
1

1
0
1

1
0
1

1
0
1

1
0
1

1
0
1

1 0/1
0 0/1
1 0/1

0
0
0

0
0
0

Range
underflow

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Broken wire

0/1

Rated range

A = Active bit
E = Error bit
OV = Overflow bit
S = Sign

System Manual
C79000-G8576-C199-06

9-71

Analog Input/Output Modules

9.5.13

Technical Specifications
6ES5 465-4UA12 Analog Input Module

Rated input ranges with cards for every 4 channels
– 6ES5 498-1AA11
– 6ES5 498-1AA21
– 6ES5 498-1AA31
– 6ES5 498-1AA41
– 6ES5 498-1AA51
– 6ES5 498-1AA61
– 6ES5 498-1AA71

$ 50 mV/$500 mV/Pt 100
$1V
$ 10 V
$ 20 mA
4 to 20 mA for two-wire transducer
$5V
4 to 20 mA for four-wire transducer

Number of inputs

16 voltage/current inputs or
8 resistance inputs (Pt 100)

Measured-valuerepresentation

13 bits (two’s complement) or 12 bits + sign;
$ 2048 units in rated range;
512 to 2560 units for 4 to 20 mA

Measuring principle

Integrating

Isolation

No

Permissible potential difference between reference potentials $ 1 V max.
of sensors and the module (UCM) and between sensors (channels)
Power Supply
– digital section from system bus
– analog section from load voltage
– enabling for module F+/F– tripping current L+

5 V $ 5 %; 150 mA typical
24 V
24 V; approx. 5 mA
24 V; approx. 5 mA

Constant current source for Pt 100 connection IC+/IC-

2.5 mA; TC = $ 5 x 10–5/K

Integration time

20 ms at 50 Hz; 16 2/3 ms at 60 Hz

Encoding time per measured value

60 ms at 50 Hz; 50 ms at 60 Hz

Cycle time for 8 measured values with 2048 units
(max. delay time for measured-value acquisition)

Approx. 0.48 s at 50 Hz
Approx. 0.48 s at 50 Hz

Input resistance (with card) for input ranges:
$50 mV/$500 mV/Pt 100
$1 V
$5 V/$10 V
$20 mA
4 to 20 mA

w 10 MW
90 kW
50 kW
25 W
31.25 W

9-72

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Measuring point-related error signal
– for overflow
– for broken wire
Max. permissible input voltage without destruction
Interference suppression for f = n x (50/60 Hz $1 %)
– with common-mode interference
– with differential-modeinterference

Yes
Yes, configurable
(at $ 50 mV, $ 500 mV and Pt 100)
$18 V; 75 V for 1 ms max. and duty ratio 1:20
w 86 dB, but $1 V max.
w 40 dB, noise voltage amplitude
but 100 % max. of measuring range
referred to peak value

Error referred to rated value
– linearity
– tolerance
– polarity reversal error
– temperature error

$ 1 unit
$ 1 unit
$ 1 unit
1 x 10 –4 /K

Error caused by cards with input range
$ 1 V/$ 5 V /$ 10 V
$ 20 mA/4 to 20 mA

2 x 10 –3; TC = $ 10 x 10 –5 /K
10 –3; TC = $ 5 x 10 –5 /K

Setting the Mode

You select the desired mode of the analog input module by setting mode
switches I and II according to the following table.
Note that all the rockers of both mode switches marked with a dot must be
set, and some functions are defined by several rockers (e.g. 8- to 16-channel
operation, broken wire signal for 8 or 16 channels).
To activate the desired modes, press the rockers down on the side marked
with a dot.

System Manual
C79000-G8576-C199-06

9-73

Analog Input/Output Modules

Mode

Mode Switch I
(Digital Section)

Mode Switch II
(Digital Section)

Without reference point compensation

With reference point compensation
Measuring range
50 mV
500 mV; Pt 100
Current or
voltage measurement, 16 channels
Pt 100 in 4-wire circuit
8 channels
Current or
voltage measurement, 8 channels
Sampling
selective
cyclic
Line frequency
50 Hz
60 Hz
8 channels

16 channels
Two’s complement

Value and sign
Channels 4 ... 7 (with 8 channels)
Channels 8 ... 15 (with 16 channels)
with broken wire signal
Channels 0 ... 3 (with 8 channels)
Channels 0 ... 7 (with 16 channels)
Channels 0 ... 3 (with 8 channels)
Channels 0 ... 7 (with 16 channels)
without broken wire signal
Channels 4 ... 7 (with 8 channels)
Channels 8 ... 15 (with 16 channels)
mV/mA

Pt 100
x = Switch is not assigned, any switch setting
Ĥ = Switch setting

9-74

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Labeling of switches on the module cover:
voltage/current
with
broken wire
detection

8 channels
16 channels

channel 4–7
channel 8–15

8channels
16channels

channel0–3
channel0–7
resistance thermometer

two’s complement

16 channels ...mV/ ...mA

8 channels/resistance thermom.; mV/mA

50 mV

line frequency 50 CPS

without compensation

single scanning

II.

1)

I.

1)
cyclics canning

with compensation

line frequency 60 CPS

500 mV/ ...mA/ resistance thermometer

16 channels mV; mA

8 channels ...mV/ ...mA/ resist. therm.
voltage/current

result and sign
with out
broken wire
detection

8 channels
16 channels
8 channels
16 channels

resistance thermometer

channel 0–3
channel 0–7
channel 4–7
channel 8–15

*

* consider instruction manual

1)

It is advisable to mark the selected switch setting in these fields.

Inserting Range
Cards

-1AA11
M+

On one 465 analog input module, you can insert four cards for the connection
of four inputs each, and secure them with a screw. There are voltage divider,
shunt and through-connection cards for the various ranges.

-1AA21
M+

Range Card Type 6ES5 498–
-1AA31
-1AA41
-1AA51
M+
M+
M+

Circuit of the
cards 4x
M–
Mode
500 mV/ mA
Pt 100
Mode 50 mV

M–

M–

M–

" 500 mV
Pt 100

"1 V

" 10 V

" 20 mA

" 50 mV

(" 100 mV)

(" 1 V)

(" 2 mA)

L+
L–
M–
4...20mA
2-wire trans.
–

-1AA61
M+

M–
"5V

(" 500 mV)

-1AA71
M+

M–
4...20mA
4-wire trans.
–

For a defined mode (50 mV or 500 mV), you can insert cards with different
ranges for every four inputs, e.g. for the 500 mV mode:
4 inputs, range $ 500 mV; 1 card 6ES5 498-1AA11
8 inputs, range $ 20 mV; 2 cards 6ES5 498-1AA41
Unused inputs must be short-circuited (with Pt 100 operation, this also
applies to the unused current outputs).
Note that the bus interface of the module is activated with 24 V via enable
lines F+ and F- at the front connector.

System Manual
C79000-G8576-C199-06

9-75

Analog Input/Output Modules

Front Connector
Assignments

+
–

1)

+
–

1)

+
–

1)

+
–

1)

+
–

1)

+
–

1)

+
–

26
27
28
29
30
31
32
+

MU –

2)
+

MU –

2)
MU +

2)

–

MU +

2)

I
trip

22
23
24
25

Comp.–
Comp.+
3)L+

–

L–

34
35
36
37
38
39
40
41
42

L+
L–

0 Vgnd (L–)

13
CH.4 14
15
CH.5 16
17
CH.6 18
19
CH.7 20
Comp.–
Comp.+
3) L+

22
23
24
25
CH.0 26
27
CH.1 28
29
CH.2 30
31
CH.3 32
34
CH.4 35
36
CH.5 37
38
CH.6 39
40
CH.7 41

L–

42

t

ADU

I trip

Data Memory and S5 Bus Control

1)

13
14
15
16
17
18
19
20

1
2
3
4
CH.0 5
6
CH.1 7
8
CH.2 9
10
CH.3 11

Range Card 1

+
–

Block Diagram
of the Module

Pin

Range Card 2

1)

ADU

Front Strip

Range Card 3

+
–

7
8
9
10
11

Datenspeicher und S5–Busansteuerung

1)

Range Card 1

1)

+
–

F–
L+

Range Card 2

+
–

F+

Range Card 3

1)

Connection of
Process Signal
Lines

t

Range Card 4

+
–

1
2
3
4
CH.0
5
6

6ES5 498–1AA51

1)

Block Diagram
of the Module

Pin

Measuring Voltage Inputs

F+
F–
L+

Front Strip

Constant Power Supply

Connection of
Process Signal
Lines

Resistance thermometer

Range Card 4

Voltage or current input
or connection of two-wire transducer

0 Vgnd (L–)

CH.15

Figure 9-25

Front Connector Assignments

Two-wire transducers can only be connected in the 500 mV mode.
Connect L- to the central ground point (reference potential).
1)
2)
3)

9-76

Observe permissible potential difference between sensor and reference potential of modules
or between sensors.
Two-wire transducer
Only required to switch off the tripping current without broken wire detection;
(0 V at common ground point with L-).

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.6

The 466 Analog Input Module

9.6.1

Design
The module is designed as a plug-in PCB for central controllers and
expansion units with a backplane connector and with a blade connector to
accept a plug-in front connector. You can directly connect the process signal
lines to the front connector, which is available separately, with screw or
crimp terminals.

9.6.2

Special Features of the 466 Analog Input Module
The 466 analog input module processes the digital input signals by encoding
the instantaneous value; periodic system interference is therefore not
suppressed.

Measuring Range

9.6.3

You select the measuring ranges with a switch setting for every four
channels.

Startup

Introduction

The mode of the 466 analog input module must be set exclusively via
switches on the board. Figure 9-26 shows the designations and locations of
switches on the board.
Front

S8

S7

S5

S1

S6

S9

S2

Backplane Connector for S5 I/O Bus
Figure 9-26

Locations of Mode Switches on the 466 Analog Input Module

Note
The following 43-pin K-type front connectors are required:
6xx3 068 for crimp connection
6xx3 081 for srew connection

System Manual
C79000-G8576-C199-06

9-77

Analog Input/Output Modules

Setting the Type of
Measurement

Measurement with respect to ground/differential measurement
The type of measurement (with respect to ground or differential
measurement) is set with switch S9. The switch settings relate to the
locations on the module shown in Figure 9-26:

Switch Setting S9

Type of Measurement
1

9
ON

Measurement with respect to ground

OFF
1

9
ON

Differential measurement

Current/Voltage
Measurement for
Individual Channel
Groups

OFF

If you have preset differential measurement on switch S9, two channel
groups of four channels each are available. You can configure each channel
group separately for current or voltage measurement.
You set this with switches S5, S6, S7 and S8. Switches S5 and S7 allow three
settings (left, midpoint and right); switches S6 and S8 allow two settings (left
and right). The switch settings relate to the locations on the module shown in
Figure 9-26:
Setting the current/voltage measurement for channel group I
Channel Group I
(Channels 0 to 3)

Switch S5

Switch S6

Current
Voltage

Setting the current/voltage measurement for channel group II
Channel Group II
(Channels 4 to 7)

Switch S7

Switch S8

Current
Voltage

9-78

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

If you have preset measurement with respect to ground on switch S9, four
channel groups of four channels each are available. You can configure each
channel group separately for current or voltage measurement.
This is set with switches S5, S6, S7 and S8. Switches S5 and S7 allow three
settings (left, midpoint and right); switches S6 and S8 allow two settings (left
and right). The switch settings relate to the locations on the module shown in
Figure 9-26:
Setting the current/voltage measurement for channel group I
Channel Group I
(Channels 0 to 3)

Switch S5

Current
Voltage

Setting the current/voltage measurement for channel group II
Channel Group II
(Channels 4 to 7)

Switch S7

Current
Voltage

Setting the current/voltage measurement for channel group III
Channel Group III
(Channels 8 to 11)

Switch S6

Current
Voltage

Setting the current/voltage measurement for channel group IV
Channel Group IV
(Channels 12 to 15)

Switch S8

Current
Voltage

System Manual
C79000-G8576-C199-06

9-79

Analog Input/Output Modules

Setting the
Measuring Range

The 466 analog input module has 12 measuring ranges. For each channel
group (i.e. for every four inputs), you can select a range which is independent
of the other channel groups. You set the ranges with switches S1 and S2.
1

2

3

4

S1
5

6

7

8

1

2

3

4

S2
5

6

7

8
ON
OFF

Channel Group I
(Channel 0...3)

Figure 9-27

Channel Group II
(Channel 4...7)

Channel Group III
(Channel 8...11)

Channel Group IV
(Channel 12...15)

Assignment of Channel Groups to Switches S1 / S2

The same measuring range coding is valid for each channel group. Given in
the following table, therefore, is the setting of the measuring range for only
one channel group. The switch settings relate to the locations on the module
shown in Figure 9-27.
Note that you must additionally set the type of measurement
(current/voltage) with switches S5 to S8!
Setting the measuring range for a channel group (4 channels each)
Range
0 - 20 mA

Switch Setting
ON
OFF

0 - 1.25 V
0 - 2.5 V
0-5V
0 - 10 V
$ 20 mA
$ 1.25 V
$ 2.5 V
$5V
$ 10 V
4 - 20 mA
1-5V

9-80

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Setting the Data
Format

Set the data format by means of switch S9:
Two’s complement
12-bit two’s complement representation
(Range: 0 ... 4095 units (unipolar) or - 2048 ... + 2047 units (bipolar))
Value and sign
11-bit value and 1 sign bit
(Range: 0 ... 4095 units (unipolar) or - 2048 ... + 2047 units (bipolar))
Binary
12-bit binary number
(Range: 0 ... 4095 units for both unipolar and bipolar measured variables)

Data Format

S9 Switch Setting
1

9
ON

Two’s complement

OFF
1

Value and sign

9
ON
OFF

1

Binary

9
ON
OFF

System Manual
C79000-G8576-C199-06

9-81

Analog Input/Output Modules

Setting the Module
Start Address

Before starting up, first indicate via switch S9 whether you intend to use the
466 analog input module with a central controller (CC) or with an expansion
unit (EU).
Refer to the following table:
Setting the module start address (1)
466-3LA11 Module

S9 Switch Setting
9

1

ON
OFF

Operation in CC
1

9

Operation in EU with IM 300/312

ON
OFF
1

9

Operation in EU with IM 301/310

ON
OFF
1

9

Operation in EU with IM 304/314

ON
OFF
1

9

Operation in EU with IM 307/317

ON
OFF
1

Operation in EU with IM 308/318

9-82

9
ON
OFF

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Set the exact start address of the module as shown in the following table.
Setting the module start address (2)
S9 Switch Setting

Module Address

9

1

ON

000

OFF
1

9
ON

016*

OFF
9

1

ON

032

OFF
1

9
ON

048*

OFF
1

9
ON

064

OFF
1

9
ON

080*

OFF
1

9
ON

096

OFF
1

9
ON

112*

OFF
9

1

ON

128

OFF
1

9
ON

144*

OFF
9

1

ON

160

OFF
9

1

ON

176*

OFF
1

9
ON

192

OFF
1

9
ON

208*

OFF
1

ON

224

OFF
1

240*

9

9
ON
OFF

* can only be set for differential measurement

System Manual
C79000-G8576-C199-06

9-83

Analog Input/Output Modules

9.6.4

Removing and Inserting Modules

!

Warning
When removing and inserting the front connector during operation,
hazardous voltages of more than 25 V AC or 60 V DC may be present at the
module pins. When this is the case at the front connector, live modules may
only be replaced by electrical specialists or trained personnel in such a way
that the module pins are not touched.
During operation, the front connector and module must not be removed or
inserted without the enable jumper or active enable circuit.

Install an analog input/output module as follows:

9-84

Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Insert the module at the desired slot in the subrack and push it back in the
guides.

3

Latch the module by rotating the locking pin by 90o at the lower end of
the module. It must no longer be possible to pull the module forwards.

4

Engage the front connector on the support pin of the module. The width
of the support pin also provides keying to prevent front connectors from
being fitted to the wrong modules (e.g. front connectors with 115/230 V
AC wiring cannot be plugged into analog modules).

5

Tighten the screw in the upper part of the front connector.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Remove an analog input/output module as follows:
Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Slacken the screw in the upper part of the front connector. This causes the
front connector to be pressed out of the female connector of the module.
Contacts F+ and F- of the enable input at the upper end of the front
connector are thus opened first. If the enable input is active, power is
removed from the outputs and the module is isolated from the S5 bus.

3

Swing the front connector out and lift it away from the support pin of the
module.

4

Release the module by rotating the locking pin by 90o at the lower end of
the module. You can pull the module out of the subrack with a grip with
swivels outwards.
6

Module

1

Front
Connector

Support Mount
5

Support Pin

4
3

Figure 9-28
1
2
3
4
5
6

2

Module with Front Connector

Screw
Locking pin
Support mount
Support pin
Grip
Backplane connector

Comply with VDE Specifications 0110 and 0160 to carry out the wiring of
supply and signal lines which are to be connected to the programmable
controllers and front connectors of the modules.
Detailed information on cabinet assembly, cabinet ventilation and protective
measures can be found in Chapter 3.

System Manual
C79000-G8576-C199-06

9-85

Analog Input/Output Modules

9.6.5

Marking of Modules and Front Connectors
For the marking of modules and front connectors, labels are supplied with the
module and central controller; they are affixed as shown in Figure 9-29.
1

Figure 9-29
1
2
3
4
5

9-86

2 4

1

5

3

Marking and Labeling of Modules

Label with the module address under which the module is referenced by the STEP 5 program
Labeling strip with the product designation for the module; space to mark the module version
and label the channels
Label with module address and marking of the required settings for the addressing switch
Labeling strip for terminal designations or connection diagrams (strip in the cover of the
front connector)
Name plate

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.6.6

Connecting the Signal Lines
For connection of the signal lines, front connectors for 20 and 40 mm
mounting width with crimp connection and 40 mm mounting width with
screw connection are available (screwdriver blade width: 3.5 mm, maximum
torque: 0.8 Nm).
Use stranded conductor to facilitate handling of the front connector. Ferrules
are not required for screw connections, because the screw terminals are
provided with wire protection.
When the crimp contact is inserted in the plastic body of the front connector,
a click can clearly be heard. This indicates that the contact is engaged. For
jumpering or to correct the wiring, you can remove the contacts with a
releasing tool (see ordering information) without having to pull out the front
connector.
Ferrules are not required for screw connections, because the screw terminals
are provided with wire protection. You can use ferrules of 7 mm in length to
DIN 46228. The maximum terminal area is 2 x 2.5 mm2.

!

System Manual
C79000-G8576-C199-06

Caution
Only extra-low voltage 60 V DC with safety separation from system voltage
may be used for the 24 V DC supply and for the 24 V DC input signals.
Safety separation can be implemented to the requirements of, amongst other
sources, VDE 0100 Part 410/HD 384-4-41/IEC 364-4-41 (as functional
extra-low voltage with safety separation) or VDE 0805/EN 60950/IEC 950
(as safety extra-low voltage SELV) or VDE 0106 Part 101.

9-87

Analog Input/Output Modules

9.6.7

Connecting Sensors to the 466 Analog Input Module
The connections for the 466 analog input module depend on the type of
measurement (with respect to ground or differential measurement).

Measurement with
Respect to Ground

For measurement with respect to ground, all signal lines have a common
reference point. This is achieved by connecting all the M inputs in use to one
point. Since this type of measurement is susceptible to interference, the
signal sources should be arranged in the vicinity of the 466 analog input
module.
16 channels are available; unused channels must be shorted (jumper between
M+ and M-).
The channels have the following designations on the module:
Channel 0:
Channel 1:
:
Channel 15

M0 +
M0 –
M1 +
M1 –
:
M15 +
M15 –

Channels are arranged in groups of four, for which you can set separate
measuring ranges:
Channel group I:
Channel group II:
Channel group III:
Channel group IV:

9-88

Channels 0 to 3
Channels 4 to 7
Channels 8 to 11
Channels 12 to 15

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

The following figure shows the connection of sensors to the module. For
measurement with respect to ground, all the M- connection points are
interconnected internally on the module.

Analog Input Module
M+
U E2

+

M+

–
U E1

MUX

+
M–

–

U ISO

0 V Bus
U E1/2: Input Voltage
U ISO: Potential Difference
: Equipotential; this potential is established by the sensor reference potential
(external reference potential)

Figure 9-30

Connecting Sensors to the 466 Analog Input Module (Measurement with Respect to Ground)

Differential
Measurement

The differential measurement is a method of compensating for interference
on the line. Each signal source is assigned its own signal reference line. The
differential measurement between signal line and signal reference line thus
compensates for the interference acting on both lines.
You must also short-circuit the unused channels with this measuring method
(jumper between M+ and M-).
Differential measurement is required:
if the sensors are at different potentials;
if various signal sources are not close to each other;
if there is a need to measure signals with high precision;
and when a high level of interference is expected.

System Manual
C79000-G8576-C199-06

9-89

Analog Input/Output Modules

The channels have the following designations on the module:
Channel 0:
Channel 1:
:
Channel 7:

M0 +
M0 –
M1 +
M1 –
:
M7 +
M7 –

Channels are arranged in groups of four, for which you can set separate
measuring ranges:
Channel group I:
Channel group II:

Channels 0 to 3
Channels 4 to 7

The following figure shows the connection of sensors to the module.
You must observe the following condition:
UE + UCM < 12 V
(i.e. the sum of the set voltage range and common-mode voltage must be less
than 12 V; current measuring ranges correspond to a voltage of 2.5 V).

M+
U
E2

+
M–

–
+
U
CM2

Analog Input Module

M+

–
U

MUX

+
E1

M–

–
+

U
CM1

0 Vext

–

U
ISO
0 V Bus

U E1/2: Input Voltage
U CM1/2: Common-Mode Voltage
U ISO: Potential Difference
: Equipotential; this potential is established by the sensor reference potential
(external reference potential)

Figure 9-31

9-90

Connecting Sensors to the 466 Analog Input Module (DifferentialMeasurement)

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.6.8

Measured-Value Representation

Measured-Value
Representation
with Various
Ranges

After conversion, the digital result is stored in the module’s RAM.
The bits in both bytes have the following significance:

Byte 0
6

7

2

5

12

2

11

2

3

4
10

2

Byte 1

9

2

2
8

2

7

2

7

0

1
6

2

5

2

4

6

2

5
3

2

2

3

4

2

1

2

0

2

1

0

A

E

OV

Binary Value

Active Bit;

is not assigned

Error Bit;

is set in case of internal error;
in this case, the measured value
is not valid

Overflow Bit;

(is set if the range limit is reached)

Figure 9-32

Digital Result Representation

Bits 0 to 2 in byte 1 have no influence on the measured value, they only give
information on measured-value representation. The following table describes
their significance in more detail.
Bit
OV

*

Significance

Signal Status

Meaning of the
Signal Status

Overflow bit

1

Range exceeded *

E

Error bit

1

Broken wire

A

Active bit

0

Not used

A measuring-point overflow does not affect the overflow bits of the other channels;
i.e. the measured values of unaffected channels are correct and can be evaluated.

Please note the following special features:
Bit 7 in the high byte (212) indicates the sign for bipolar measured-value
representation (two’s complement and value with sign).
Bit 6 in the high byte (211) is not used in the case of bipolar
measured-value representation (no overrange).
The 466 module has no overrange.
Selective sampling is not possible with the 466 module
(active bit is not set).

System Manual
C79000-G8576-C199-06

9-91

Analog Input/Output Modules

Shown in the following tables is the representation of the measured value as
a function of the selected measuring range.

Measuring Range
0-20 mA, 0-5 V and
0-10 V; Unipolar

Units

4095
4094
:
0001
0000

Measured
Value in V
(0 - 5 V)
4.9988
4.9976
:
0.0012
0.0000

Measured
Value in V
(0 - 10 V)
9.9976
9.9951
:
0.0024
0.0000
*

Measured
Value in V
(0 - 20 mA)
19.9951
19.9902
:
0.00488
0.00000

Byte 0 *

Byte 1 *

7 6 5 4 3 2 1 0 7 6 5
212 211 210 29 28 27 26 25 24 23 22

4
21

3
20

0
0

1
1

1
1

0
0

0
0

0
0

1
0
:
1
0

1
1
:
0
0

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

2

1

0

A E O
0
0

0
0

1
0

0
0

0
0

0
1

Same representation for the data formats:
two’s complement, value and sign, binary representation.

A = Active bit
E = Error bit
O = Overflow bit

Two’s
Complement;
Measuring Range
5 V,
20 mA
and
10 V;
Bipolar
Units

2047
2046
:
0001
0000
–0001
:
–2047
–2048

Measured
Value in V
($5 V)
4.9976
4.9951
:
0.0024
0.0000
–0.0024
:
–4.9976
–5.0000

Measured
Value in V
($10 V)
9.9951
9.9902
:
0.0049
0.0000
–0.0049
:
–9.9951
–10.000

Measured
Value in V
($20 mA)
19.9902
19.9804
:
0.00976
0.00000
–0.00976
:
–19.9902
–20.0000

Byte 0 *

Byte 1 *

7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
212 211 210 29 28 27 26 25 24 23 22 21 20 A E O
0
0

0
0

1
1

0
0
1

0
0
1

0
0
1

1
1

1
1

0
0

1
1
:
0
0
1
:
0
0

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0
:
1
0
1
:
1
0

0
0

0
0

1
0

0
0
0

0
0
0

0
0
0

0
0

0
0

0
1

A = Active bit
E = Error bit
O = Overflow bit

9-92

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Value and sign; measuring range $ 5 V, $ 20 mA and $ 10 V; bipolar
Units

2047
2046
:
0001
0000
–0001
:
–2047
–2048

Measured
Value in V
($5 V)

Measured
Value in V
($10 V)

Measured
Value in V
($20 mA)

4.9976
4.9951
:
0.0024
0.0000
–0.0024
:
–4.9976
–5.0000

9.9951
9.9902
:
0.0049
0.0000
–0.0049
:
–9.9951
–10.000

19.9902
19.9804
:
0.00976
0.00000
–0.00976
:
–19.9902
–20.0000

Byte 0 *

Byte 1 *

7 6 5 4 3 2 1 0 7 6 5
212 211 210 29 28 27 26 25 24 23 22

4
21

3
20

0
0

0
0

1
1

0
0
1

0
0
0

0
0
0

1
1

0
1

1
0

1
0
:
1
0
1
:
1
0

1
1
:
0
0
0
:
1
0

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

0
0
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

2

1

0

A E O
0
0

0
0

1
0

0
0
0

0
0
0

0
0
0

0
0

0
0

0
1

A = Active bit
E = Error bit
O = Overflow bit

Binary; measuring range $ 5 V, $ 20 mA and $ 10 V; bipolar
Units

4095
4094
:
2049
2048
2047
:
0001
0000

Measured
Value in V
($5 V)

Measured
Value in V
($10 V)

4.9976
4.9951
:
0.0024
0.0000
–0.0024
:
–4.9976
–5.0000

9.9951
9.9902
:
0.0049
0.0000
–0.0049
:
–9.9951
–10.000

Measured
Value in V
($20 mA)
19.9902
19.9804
:
0.00976
0.00000
–0.00976
:
–19.9902
–20.0000

Byte 0 *

Byte 1 *

7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
212 211 210 29 28 27 26 25 24 23 22 21 20 A E O
0
0

1
1

1
1

0
0
0

1
1
0

0
0
1

0
0

0
0

0
0

1
1
:
0
0
1
:
0
0

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0
:
1
0
1
:
1
0

0
0

0
0

1
0

0
0
0

0
0
0

0
0
0

0
0

0
0

0
1

A = Active bit
E = Error bit
O = Overflow bit

Measuring range 0-1.25 V and 0-2.5 V; unipolar
Units

4095
4094
:
0001
0000

Measured
Value in V
(0 - 1.25 V)
1.2497
1.2494
:
0.0003
0.0000

Measured
Value in V
(0 - 2.5 V)
2.4994
2.4988
:
0.0006
0.0000
*

Byte 0

Byte 1

7
6
5
4 3 2
1 0 7 6 5 4
3 2
212 211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

0
O

0
0

1
1

1
1

0
0

0
0

1
0

0
0

0
0

0
0

0
0

0
0

0
1

1
1
:
0
0

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0
:
1
0

Same representation for the data formats:
two’s complement, value and sign, binary representation.

A = Active bit
E = Error bit
O = Overflow bit

System Manual
C79000-G8576-C199-06

9-93

Analog Input/Output Modules

Two’s complement; measuring range $ 1.25 V and $ 2.5 V; bipolar
Units

2047
2046
:
0001
0000
–0001
:
–2047
–2048

Measured
Value in V
($ 1.25 V)

Measured
Value in V
($ 2.5 V)

1.2494
1.2488
:
0.0006
0.0000
–0.0006
:
–1.2494
–1.2500

2.4988
2.4975
:
0.0012
0.0000
–0.0012
:
–2.4988
–2.5000

Byte 0
7
6
5
4
212 211 210 29
0
0
1
1
0
0
1
1
:
0
0
0
0
0
0
0
0
1
1
1
1
:
1
1
0
0
1
1
0
0

Byte 1

3 2
1 0 7 6 5 4
3
28 27 26 25 24 23 22 21 20
1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 0
:
0 0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0 0
1 1 1 1 1 1 1 1 1

2
A
0
0

1
E
0
0

0
O
1
0

0
0
0

0
0
0

0
0

0
0

0
0
0
:
0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0

0
1

A = Active bit
E = Error bit
O = Overflow bit

Value and sign; measuring range $ 1.25 V and $ 2.5 V; bipolar
Units

2047
2046
:
0001
0000
–0001
:
–2047
–2048

Measured
Value in V
($ 1.25 V)

Measured
Value in V
($ 2.5 V)

1.2494
1.2488
:
0.0006
0.0000
–0.0006
:
–1.2494
–1.2500

2.4988
2.4975
:
0.0012
0.0000
–0.0012
:
–2.4988
–2.5000

Byte 0
7
6
5
4
212 211 210 29
0
0
1
1
0
0
1
1
:
0
0
0
0
0
0
0
0
1
0
0
0
:
1
0
1
1
1
1
0
0

Byte 1

3 2
1 0 7 6 5 4
3
28 27 26 25 24 23 22 21 20
1 1 1 1 1 1 1 1 1
1 1 1 1 1 1 1 1 0
:
0 0 0 0 0 0 0 0 1
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0

2
A
0
0

1
E
0
0

0
O
1
0

0
0
0

0
0
0

1
0

0
0

0
0
0
:
0
0

Byte 0
Byte 1
7
6
5
4 3 2
1 0 7 6 5 4
3 2
212 211 210 29 28 27 26 25 24 23 22 21 20 A

1
E

OV

0
0

1
1

1
1

0
0

0
0

1
0

0
0
0

1
1
0

0
0
0

0
0
0

0
0
0

0
0

0
0

0
0

0
0

0
1

1
0

1
0

1
0

1
0

1
0

1
0

1
0

1
0

0
1

A = Active bit
E = Error bit
O = Overflow bit

Binary; measuring range $ 1.25 V and $ 2.5 V; bipolar
Units

4095
4094
:
2049
2048
2047
:
0001
0000

Measured
Value in V
($ 1.25 V)

Measured
Value in V
($ 2.5 V)

1.2494
1.2488
:
0.0006
0.0000
–0.0006
:
–1.2494
–1.2500

2.4988
2.4975
:
0.0012
0.0000
–0.0012
:
–2.4988
–2.5000
*

1
1

1
1

1
1

1
1

1
1

1
1

1
1

1
1

0
0
1

1
1
:
0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0
1

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

0
0

1
0
:
1
0
1
:
1
0

0

Same representation for the data formats:
two’s complement, value and sign, binary representation.

A = Active bit
E = Error bit
O = Overflow bit

9-94

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.6.9

Technical Specifications
6ES5 466-3LA11 Analog Input Modules

Input ranges

0-20 mA; 4-20 mA; "20 mA;
0-1.25 V; 0-2.5 V; 0-5 V;
1-5 V; 0-10 V;
"1.25 V; "2.5 V; "5 V; "10 V

Number of inputs

16 single or 8 differential inputs in groups of
4 or 2 channels (selectable)
voltage or current measurement

Measuring principle

Instantaneous value encoding

Conversion time

25 ms typical (per channel)

Isolation

Yes

Permissible isolation between sensor ref. potential and
central ground point

25 V AC/60 V DC max.

Supply voltage
internal
external

+ 5 V +/- 5 %
None

Current consumption, internal

0.7 A typical

Encoding time per measured value

250 ms

Duration of cyclic sampling
(cycle time)
for 8 measured values
for 16 measured values

2 ms max.
4 ms max.

Input resistance
voltage measuring range
current measuring range

w 10 M W
125 W

Type of circuit for sensors

Two-wire circuit

Digital representation of the input signal

Selectable, following types of representation:
– 12-bit two’s complement
– 11-bit value with sign
– 12-bit binary

Max. permissible input voltage without destruction

$ 30 V max. (static) or
$ 75 V (pulse for 1 ms max. and duty ratio 1:20)

Interference voltage suppression common-mode interference (Vpp = 1 V)

70 dB min.

Basic error limits
– voltage ranges except for 0-1.25 V; $1.25 V
– current ranges and 0-1.25 V; $1.25 V

System Manual
C79000-G8576-C199-06

0.1 %
0.2 %

9-95

Analog Input/Output Modules

Operational error limit (0 oC ... 60 oC)
– voltage ranges except for 0-1.25 V, $1.25 V
– current ranges and 0-1.25 V, $1.25 V

0.2 %
0.2 %

Error signal
for overflow
for internal error

Yes (overflow bit set)
Yes (error bit (= E bit) set)

Single error
linearity
tolerance
polarity reversal error

0.02 %
0.05 %
0.05 %

Temperature error

0.005 %/K

Insulation rating

To VDE 0160

Line length
- shielded

200 m max.

Front connector

43-way

Power dissipation of module

3.5 W typical

Weight

Approx. 0.4 kg

Rated insulation voltage
(between channels and ground point) tested at

500 V

9-96

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Front Connector
Assignments

Voltage-to-ground measurement

Front Strip

Front Strip

Pin

Pin

1
2 M0+
3 M0–
4 M8–

1
2 M0+
3 Mext
4 Mext

5 M8+
6

5 M0–
6

7 M1+
8 M1–

7 M1+
8 Mext
9 Mext
10
M1–
11

9 M9–
10 M9+
11
12 M2+
13 M2–
14 M10–
15 M10+
16
17 M3+
18 M3–
19 M11–
20 M11+
21
22

12 M2+
13 Mext
14 Mext
15
M2–
16
17
M3+
18 Mext
19
Mext
20 M3–
21
22

23

23

24 M4+
25 M4–
26 M12–
27 M12+

24 M4+
25 Mext
26 Mext
27 M4–

28
29 M5+
30 M5–
31 M13–

28
29 M5+
30 Mext
31 Mext

32 M13+

32 M5–
33
34 M6+

33
34 M6+
35 M6–
36 M14–
37 M14+
38
39 M7+
40 M7–

Figure 9-33

Differential measurement

35 Mext
36 Mext
37 M6–
38

41 M15–

39 M7+
40 Mext
41 Mext

42 M15+

42

M7–

Front Connector Assignments

System Manual
C79000-G8576-C199-06

9-97

Analog Input/Output Modules

9.7
9.7.1

The 470 Analog Output Module
Design
The module is designed as a plug-in PCB for central controllers and
expansion units with a backplane connector and with a blade connector to
accept a plug-in front connector. You can directly connect the process signal
lines to the front connector, which is available separately, with screw or
crimp terminals.

Addressing
Switch, Mode
Switches

Situated on each module is an addressing switch with six rockers to set the
module address.
The modules are protected by covers on both sides.

Addressing Switch
Blade Connector

Front Connector

Figure 9-34

9.7.2

Analog Output Module

Function of the Enable Input
The 470 module has an enable circuit. You can use the enable inputs to
switch off individual modules whilst the PLC is in operation. This means
that:
The module can no longer be addressed by the user program.
On analog output modules, the last analog value to be output is retained.
Modules which are switched off can be removed or inserted during operation.
If this is not necessary, operate the module with the enable input switched
off.

9-98

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Enable Input

The enable circuit requires an external 24 V voltage at enable inputs F+/F- in
the front connector. If there is no voltage at F+/F-, the modules will not
acknowledge.
When the front connector is swivelled away from the front strip of the
module, the supply of power to the enable input is interrupted, i.e. the
module is switched off and can no longer be addressed by the user program: a
timeout (QVZ) occurs in the CC.

Switching Off the
Enable Input

The -4Ux12-type modules additionally offer the facility for changing the
enable mode. The modules have a jumper accessible from above in the
vicinity of the addressing switch.

Enable Jumper

Figure 9-35

Enable Input and Enable Jumper

Jumper inserted: Enable input (F+/F-) active (factory setting)
Jumper open:
Enable input (F+/F-) switched off
Examples of functioning of the enable inputs:
To switch off individual subprocesses, i.e. outputs of various modules can
be operated from a common load supply and yet activated separately.
The load voltage of individual modules can be monitored without
additional circuitry. Any reactions to failure of the load voltage can be
programmed in the QVZ (timeout) organization block.

System Manual
C79000-G8576-C199-06

9-99

Analog Input/Output Modules

Configuring

You must observe the following when configuring systems:
Switching on

At the latest 100 ms after power-up of the PLC, the voltage
must be present at the enable inputs of the I/O modules.

Switching off

When the PLC has been switched off, the voltage at the
enable inputs of the I/O modules must still be present as
long as the internal 5 V voltage is present.
However, you must ensure that the 24 V load supply for
analog output modules is switched off together with the
PLC. If the supply voltage is still present at the modules
and the PLC is switched off, the output values can drift.
(The analog holding elements for the outputs will no longer be refreshed with the current value, because there is no
5 V supply to the modules from the bus.)

Switching Off the
CC

You should observe the following instructions for switching off CCs and
equipment for supplying power to the enable inputs.

Separate or
Common
Shutdown of the
CC/EU and Load
Power Supply

When there is a need to switch off the load power supply separately without
affecting the enabling of modules, there are the following possibilities for
producing the enable voltage. These exist even when the load power supply
is used without an additional capacitor and common shutdown.
230 V AC supply for CC/EU and load power supply

b)

a)
–951

Battery

I/O Modules

c)

F+
CC/EU

L+

Power Supply

L+

230 V AC
Load Power Supply 24V

Supply for the enable inputs from:
a) 6ES5 951-4LB11 load power supply
b) Battery
c) Terminals for 24 V on the front plate of the power supply

9-100

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

24 V supply for CC/EU and I/Os

a)
I/O Modules

Battery
b)

F+
CC/EU

L+

Power Supply 24V

L+

24 V DC

Supply for the enable inputs from:
a) Battery
b) Terminals for 24 V on the front plate of the power supply

Common
Shutdown of the
CC/EU and Load
Power Supply with
a 230 V AC Supply

Proper functioning is ensured if the 24 V load power supply has an output
capacitance of at least 4700 mF per 10 A of load current. Other units which
do not meet this condition can be adapted to this requirement by connecting a
10000 mF / 40 V capacitor in parallel.
I/O Modules
F+
CC/EU
L+
230 V AC

Power Supply

10000µF/
40V

Load Power Supply 24V

System Manual
C79000-G8576-C199-06

9-101

Analog Input/Output Modules

9.7.3

Special Features of the 470 Analog Output Module

BASP (Output
Inhibit)

The BASP signal is not interpreted by the 470 analog output module. Once
output, a value is retained.

Function Block

You can output analog values to the process via analog output modules with a
function block from the “basic functions” package.

9.7.4

Setting the Module Address
You set the module address on the addressing switch. This also establishes
the necessary assignments between user program and process connection.
The module address is the sum of the decimal significances of the switch
rockers in the On setting (Ĥ).
One data word = two data bytes is required to process an input or an output.
A module with 8 inputs or outputs reserves 16 byte addresses.

Labeling Field

You can affix the adhesive label with the desired module address on a free
labeling field under the addressing switch.
The switch rockers to be set for the module address specified as a decimal
number (address bit ADB) are marked by dots on the label.
Press the individual rockers of the addressing switch downwards with a
ballpoint pen or similar object, but not a pencil.

On Setting
(Switch Pressed)

Addressing Switch

Free Field for Label with
Module Address and
marked Switch Settngs

ADB1
ADB0

8

16

32

4
2
1

ADB3
ADB2

ADB7

ADB6
ADB5
ADB4

128
64

Address (Decimal)

Decimal Signification of
the Address Bit

Address Bit

ADB0 and ADB1 are not assigned
ADB2 is not connected

Figure 9-36

Labeling of the Addressing Switch

The address under which the module is referenced by the STEP 5 program is
independent of the slot.

9-102

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Start Address,
Subaddress

For analog output modules ( 8 outputs) only the lowest address (start address)
is set. Other addresses (subaddresses) are decoded on the module.
Note
The start address of an analog module must be a multiple of the double
channel number.
8 channels : 0, 16, 32, 48, ... 240

If one of the outputs (Channel 0 to 7) of a module is to be addressed, the
relevant subaddress must be specified in the program.
The subaddress of the output, based on the start address of the module, is
given by:
Start address + 2 x channel no. = subaddress
Example:
Analog output module with 8 outputs
The address is the sum of the significances set with the individual coding
switches.
160 = 128 + 32 = 27 + 25

On Setting
(Switch Pressed)

ADB1
ADB0

8

16

4
2
1

ADB3
ADB2

64
32

ADB7
ADB6
ADB5
ADB4

128

IB 160

A module with 8 outputs (Channel 0 to 7) and start address 160 reserves the
address range from
160 to address 160 + 7 x 2 = 174
In this example, the next free address for another module is 176.
Addresses already assigned must not be set again.

System Manual
C79000-G8576-C199-06

9-103

Analog Input/Output Modules

Addressing for
Cyclic/Selective
Sampling

However, analog input modules and analog output modules may be given the
same address with cyclic sampling because they are distinguished by the user
program. This is not possible with selective sampling.
For cyclic sampling, you can address the module in the address range from 0
to 255, and for selective sampling from 128 to 255. For selective sampling,
you can also use the address range from 0 to 127 after appropriate
programming in DB 1 of the user program.
Example:
On an analog output module with 8 outputs with start address 144 (IB 144 =
output byte 144), output channel 7 is to be scanned by the program.

9-104

Step

Action

1

Affix the self-adhesive label with address 160 on the free field under the
addressing switch on the module. ADB 4 and ADB 7 are marked on the
label.

2

Press the appropriate rockers of the addressing switch down on the side
marked by a dot on the module cover. Set the other rockers to the opposite
setting. This sets the start address of the module.
ADB 4 and ADB 7 results in 24 + 27 = 16 + 128 = 144

3

Enter the address 144 + 7 x 2 = 158 in the program for input channel 7.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.7.5

Removing and Inserting Modules

!

Warning
When removing and inserting the front connector during operation,
hazardous voltages of more than 25 V AC or 60 V DC may be present at the
module pins. When this is the case at the front connector, live modules may
only be replaced by electrical specialists or trained personnel in such a way
that the module pins are not touched.
During operation, the front connector and module must not be removed or
inserted without the enable jumper or active enable circuit.

Install an analog output module as follows:

System Manual
C79000-G8576-C199-06

Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Insert the module at the desired slot in the subrack and push it back in the
guides.

3

Latch the module by rotating the locking pin by 90o at the lower end of
the module. It must no longer be possible to pull the module forwards.

4

Engage the front connector on the support pin of the module.
The width of the support pin also provides keying to prevent front connectors from being fitted to the wrong modules (e.g. front connectors with
115/230 V AC wiring cannot be plugged into analog modules).

5

Tighten the screw in the upper part of the front connector.

9-105

Analog Input/Output Modules

Remove an analog output module as follows:
Step

Action

1

Release the upper locking bar on the subrack and swivel it upwards and
out.

2

Slacken the screw in the upper part of the front connector. This causes the
front connector to be pressed out of the female connector of the module.
Contacts F+ and F- of the enable input at the upper end of the front connector are thus opened first. If the enable input is active, power is removed
from the outputs and the module is isolated from the S5 bus.

3

Swing the front connector out and lift it away from the support pin of the
module.

4

Release the module by rotating the locking pin by 90o at the lower end of
the module. You can pull the module out of the subrack with a grip with
swivels outwards.

6

Module

1

Front
Connector

Support Mount
5

Support Pin

4
3

Figure 9-37
1
2
3
4
5
6

2

Module with Front Connector

Screw
Locking pin
Support mount
Support pin
Grip
Backplane connector

Comply with VDE Specifications 0110 and 0160 to carry out the wiring of
supply and signal lines which are to be connected to the programmable
controllers and front connectors of the modules.
Detailed information on cabinet assembly, cabinet ventilation and protective
measures can be found in Chapter 3.

9-106

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.7.6

Marking of Modules and Front Connectors
For the marking of modules and front connectors, labels are supplied with the
module and central controller; they are affixed as shown in Figure 9-38.

1

Figure 9-38
1
2
3
4
5

System Manual
C79000-G8576-C199-06

2 4

1

5

3

Marking and Labeling of Modules

Label with the module address under which the module is referenced by the STEP 5 program
Labeling strip with the product designation for the module; space to mark the module version
and label the channels
Label with module address and marking of the required settings for the addressing switch
Labeling strip for terminal designations or connection diagrams (strip in the cover of the
front connector)
Name plate

9-107

Analog Input/Output Modules

9.7.7

Connecting the Signal Lines
For connection of the signal lines, front connectors for 20 and 40 mm
mounting width with crimp connection and 40 mm mounting width with
screw connection are available (screwdriver blade width: 3.5 mm, maximum
torque: 0.8 Nm).
Use stranded conductor to facilitate handling of the front connector. Ferrules
are not required for screw connections, because the screw terminals are
provided with wire protection.
When the crimp contact is inserted in the plastic body of the front connector,
a click can clearly be heard. This indicates that the contact is engaged. For
jumpering or to correct the wiring, you can remove the contacts with a
releasing tool (see ordering information) without having to pull out the front
connector.
Ferrules are not required for screw connections, because the screw terminals
are provided with wire protection. You can use ferrules of 7 mm in length to
DIN 46228. The maximum terminal area is 2 x 2.5 mm2.

Terminal
T
Type

Connector
T
Type
6ES 497-

Cross-Section
Max.
N off
No.
Signal or Supply Aux. Jumper
Contacts
Conductor
in Connector

Connector for
R t dV
Rated
Voltage
lt

Mounting Width of
M d l
Module

1)

Crimp con- -4UA12 2)
nection

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

20 mm

-4UA22 2)

42

0.5 mm 2

0.5 mm 2

5 to 60 V DC

40 mm

-4UB12

42

0.5 to 2.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

40 mm

-4UB31

42

0.5 to 1.5 mm 2

0.5 to 1.0 mm 2

5 to 60 V DC

20 mm

Screw connection
ti

1)
2)

!

9-108

Operation
with fan
Operation
O
ti
without fan

To multiply the supply and 0 V ground terminals, and to connect the enable input
The crimp contacts must be ordered separately for these types of connector.

Caution
Only extra-low voltage 60 V DC with safety separation from system voltage
may be used for the 24 V DC supply and for the 24 V DC input signals.
Safety separation can be implemented to the requirements of, amongst other
sources, VDE 0100 Part 410/HD 384-4-41/IEC 364-4-41 (as functional
extra-low voltage with safety separation) or VDE 0805/EN 60950/IEC 950
(as safety extra-low voltage SELV) or VDE 0106 Part 101.

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.7.8

Connecting Loads to the 470 Analog Output Module
The voltage at the load is measured at a high resistance via the sensor lines
(S+/S-) of voltage output QV, so that voltage drops on the load lines do not
falsify the load voltages. Lines S+(x) and S-(x) should therefore be directly
connected to the load (four-wire circuit). The voltage drops on the lines from
QV(x) to the load and from the load to MANA must not exceed 3 V.
QV(x)
S+(x)
+
Load (Voltage)
–

S – (x)
QI (x) I

+

Load (Current)

–
MANA
Figure 9-39
QV(x)
QI(x)
S+(x)
S- (x)
MANA

Connecting Loads
to Current and
Voltage Outputs

Connecting Loads
Voltage output, voltage on Channels 0 to 7
Current output, current on Channels 0 to 7
Sensor line (+) for Channels 0 to 7
Sensor line (-) for Channels 0 to 7
Ground terminal for the analog section

When current and voltage outputs are used on the 470-4UA/-4UC... analog
output modules, connect the loads as follows:

QV0

QV1

QV2

QV3

S+0

S+1

S+2

S+3

QV4
Jumper
S+4

S–3

S–4

+
–
S–0

+

QI1

QI0
+

–
S–2

+
–

–
M

+

–
S–1

Jumper

QI2

+

QI4

QI3

_

+

–

–

Jumper

Jumper

ANA

M
ANA
Current
Output
Only

Figure 9-40

M

ANA

Not Current
and Not Voltage
Output

Connecting Loads

System Manual
C79000-G8576-C199-06

9-109

Analog Input/Output Modules

If, with voltage outputs, an excessively great voltage drop must be expected
on the lines to the load, you must route the sensor lines S+(x) and S-(x) to the
load.
When voltage outputs are not used, the S+(x) sensor lines in the front
connector must be connected to the corresponding voltage output terminals
(QV(x)) with wire jumpers. The S-(x) sensor lines must be connected to
MANA with wire jumpers.
You must also insert the same jumpers if only current outputs are used.
Unused current outputs may remain open.
The maximum load for the current outputs including line resistance, must not
exceed 300 ohms.

Connecting Loads
to Voltage Outputs

The voltage outputs of the 470 analog output module are wired as follows:

QV0

QV1

QV2

QV3

S+0

S+1

S+2

S+3

Jumper
+
+

+
–

–

S–0

S–1

–
S–2

S–3

Jumper

M
ANA

M
ANA

No Load at QV3

Figure 9-41

Connecting Loads

Four-Wire Circuit

The S+(x) and S-(x) sensor lines must be routed to the load (four-wire
circuit) if the voltage drop on the lines to the load is not negligible. The
common connection for the voltage outputs is MANA. If the voltage drop on
lines to the load is negligible, you can connect S+(x) to QV(x) and S-(x) to
MANA in the front connector.
When voltage outputs are unused, you must insert jumpers in the front
connector, e.g. QV(3) to S+(3) and S-(3) to MANA for unused voltage output
3 (see previous section).

9-110

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

9.7.9

Measured-Value Representation

Digital
Measured-Value
Representation as
Two’s Complement

Units

Output Voltage or Current of the
470 Analog Output Module
-4UA/B12

1280 12.5 V
1025 10.0098 V
1024
1023
512
256
128
64
1
0
–1
– 64
– 128
– 256
– 512
–1024
–1025
–1280

-4UA12

-4UC12

Byte 0

Byte 1

7 6 5 4 3 2 1 0 7 6 5 4 3
211 210 29 28 27 26 25 24 23 22 21 20 x

2
x

1
x

0
x

25.0 mA
6.0 V
24.0 mA
0 1 0 1 0 0 0 0 0 0 0 0 Overrange
20.0195mA 5.004 V 20.016 mA 0 1 0 0 0 0 0 0 0 0 0 1

10.0 V
9.99 V
5.0 V
2.5 V
1.25 V
0.625 V
9.8 mV
0V
– 9.8 mV
– 0.625 V
– 1.25 V
– 2.5 V
– 5.0 V
– 10.0 V

20.0 mA
19.98 mA
10.0 mA
5.0 mA
2.5 mA
1.25 mA
19.5 mA
0 mA
0 mA
0 mA
0 mA
0 mA
0 mA
0 mA

–10.0098V
–12.5 V

0 mA
0 mA

System Manual
C79000-G8576-C199-06

5.0 V
4.995 V
3.0 V
2.0 V
1.5 V
1.25 V
1.004 V
1.0 V
0.996 V
0.75 V
0.5 V
0V
–1V
– 3.0 V

20.0 mA
19.98 mA
12.0 mA
8.0 mA
6.0 mA
5.0 mA
4.016 mA
4.0 mA
3.984 mA
3.0 mA
2.0 mA
0 mA
0 mA
0 mA

– 3.004V0 mA
– 5.0 V 0 mA

0
0
0
0
0
0
0
0
1
1
1
1
1
1

1
0
0
0
0
0
0
0
1
1
1
1
1
1

0
1
1
0
0
0
0
0
1
1
1
1
1
0

0
1
0
1
0
0
0
0
1
1
1
1
0
0

0
1
0
0
1
0
0
0
1
1
1
0
0
0

0
1
0
0
0
1
0
0
1
1
0
0
0
0

0
1
0
0
0
0
0
0
1
0
0
0
0
0

0
1
0
0
0
0
0
0
1
0
0
0
0
0

0
1
0
0
0
0
0
0
1
0
0
0
0
0

0
1
0
0
0
0
0
0
1
0
0
0
0
0

0
1
0
0
0
0
0
0
1
0
0
0
0
0

0
1
0
0
0
0
1 Rated Range
0
1
0
0
0
0
0

1 0 1 1 1 1 1 1 1 1 1 1 Overrange
1 0 1 1 0 0 0 0 0 0 0 0

9-111

Analog Input/Output Modules

9.7.10

Technical Specifications
6ES5 470-4UA12, 6ES5 470-4UB12 and 6ES5 470-4UC12 Analog Output
Modules

Rated output ranges
– 6ES5 470-4UA12
– 6ES5 470-4UB12
– 6ES5 470-4UC12

0 to $10 V and 0 to 20 mA parallel for $1024 units
$10 V for $1024 units
1 to 5 V and 4 to 20 mA parallel for 0 to 1024 units

Number of outputs

8 voltage and current outputs each,
no-load and short-circuit-proof

Isolation

Yes 8 outputs with respect to Mext , M and L+/L–

Measured value representation

12-bit (two’s complement)

Linearity in the range of $1024 units

$ 2 LSB = $ 0.2 %

Operational error limits (0 to 60 oC)

$ 0.6 %

Temperature coefficient for voltage and current outputs

1 x 10–4/K

Permissible overrange

Approx. 25 % ($ 1024 to $ 1272 units)

Fault current at voltage output

Approx. 25 mA

No-load voltage at current output

Approx. 18 V

Load impedance
– at voltage output
– at current output

w 3.3 kW
v 300 W

Delay between data transfer and analog value output
to > 99%

v 5ms

Capacitive load including line capacity
for -4UA12 from version 03 and
for -4UB12 and -4UC12 from version 04:

100 nF max.

Permissible voltage drop on voltage output lines

$ 0.3 V at maximum output voltage

Power supply
– Digital section from system bus
– Analog section from load voltage
– Enabling for module, F+/F-

5 V $ 5 %; approx. 250 mA
24 V; 200 to 400 mA
24 V; approx. 7 mA

Permissible potential difference between reference potential of the load and housing (UCM)

25 V AC / 60 V DC max.

1 mF max.

Voltage test to VDE 0160

Between outputs and housing
tested at 500 V AC

Surge voltage test to IEC 255-4

Between outputs and L–: Vp = 1 kV; 1,2/50 ms

9-112

System Manual
C79000-G8576-C199-06

Analog Input/Output Modules

Front Connector
Assignments

F+
F–
L+
CH.0

CH.1

CH.2

CH.3

v

v

v

v

L–

CH.4

CH.5

CH.6

v

v

v

v
CH.7

M
ANA

Figure 9-42

Front Strip
Pin
1
2
3
4
QV0
5
S+0
6
S–0
7
8
QV1
9
S+1
10
S–1
11
12
13

QV2
14 S+2
15
S–2
16
17
QV3
18 S+3
19
S–3
20
21
22
23
24
25
QV4
26
27 S+4
S–4
28
29
QV5
30
31 S+5
S–5
32
33
34
QV6
35
36 S+6
S–6
37
38
QV7
39
40 S+7
S–7
41

Block Diagram
of the Module

Connection of
Process Signal
Lines
F+

t

F–
L+
U

U

v

CH.0

I

DAU

v

CH.1
#
I

U

U

U

v

CH.2

Data Mamory and S5 Bus Control

Connection of
Process Signal
Lines

470-4UA
470-4UC

I
CH.3

v

I
L–

CH.4

v

I
U

CH.5

v

I
v

U
CH.6
I
U

42

CH.7
I
M
ANA

v

Front Strip
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42

Block Diagram
of the Module
t

U

QV0
S+0
S–0
QI0
QV1
S+1
S–1
QI1
QV2
S+2
S–2
QI2
QV3
S+3
S–3
QI3

QV4
S+4
S–4
QI4
QV5
S+5
S–5
QI5
QV6
S+6
S–6
QI6
QV7
S+7
S–7
QI7

I

DAU
U
#

I
U

I
U

I

U

Data Mamory and S5 Bus Control

470-4UB

I
U

I
U

I
U

I

Front Connector Assignments

System Manual
C79000-G8576-C199-06

9-113

Analog Input/Output Modules

9-114

System Manual
C79000-G8576-C199-06

10

Monitoring Module

This chapter describes the installation, the wiring and the operation of the
monitoring module 6ES5 313-3AA12.

Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Description

Page

10.1

Application

10-2

10.2

Installation

10-6

10.3

Operation

10-8

10.4

Technical Specifications

10-14

10.5

Address Table

10-16

10-1

Monitoring Module

10.1 Application
The monitoring module can be used in the expansion units of the
programmable controllers S5-115U, S5-135U and S5-155U.
The module monitors the data bus, the address bus and the control signals
MEMW/, MEMR/ and RDY/. Faults are displayed via four red LEDs on the
front panel. A group signal is output at the same time via a floating contact.
Following a fault, the module can be reset by means of the RESET key on
the front panel or the RESET input (see Section 10.2.3).

10.1.1

Design
The monitoring module is designed as a plug-in PCB in double Euroformat
with a 32-pin backplane connector for the S5 bus.
A connector for the relay contact and RESET input as well as one green
LED, four red LEDs and a RESET key are located on the front panel.

8 7 65 4 3 2 1

Operation (green LED)

OFF
ON

8 7 654 3 2 1

DB

Control signal fault (red LED)
Address bus fault (red LED)
Data bus fault (red LED)

S5
1s

ADB

OFF
ON
500ms
250ms
125ms

R/W

Command output inhibit (red LED)

QVZ
PESP

BASP

S1
8 7 654 3 2 1

OFF
ON

S2

Bus

RUN

876543 21
OFF
ON

S3
8 7 654 3 2 1

OFF
ON
X4

S4
128
64
32
16
8
4
2
1

RESET key

1
Relay contact
RESET input
6

Figure 10-1

10-2

Location of the Coding Switches

System Manual
C79000-G8576-C199-06

Monitoring Module

10.1.2

Mode of Operation

10.1.3

Block Diagram

Address bus

Address
comparison

S5 Bus

Daten
ausgeben

Address
comparison

S1

Bit
inversion

S2

Read and
compare
data

Preselection
of time

Address
comparison

Time
monitoring

Address
Address
comparison
comparison

S3

S4

Time
monitoring

Time
monitoring

w1
DB

Data bus
MEMR
MEMW
RDY

ADB

Control signal
monitoring

R/W

w1

S

CPKL

R

w1

Edge
BASP

X4/4

RESET input

RUN
X4/3

X4/5

L+ (24V)

X4/6

L–

internal +5V
internal 0V

X4/2
X4/1
Relay contact

Figure 10-2

Block Diagram

System Manual
C79000-G8576-C199-06

10-3

Monitoring Module

10.1.4

Fault Detection
From an address which has been set at switch S1, the data (55H or AAH) is
read by the CPU from the monitoring module. This data is to be written back
by the CPU to the address set at switch S2. The module inverts the accurate
incoming data bit by bit (from 55H to AAH or vice versa) which is read
again in the next cycle from the address set at S1.

Data Bus Faults

If the data which has been set on the monitoring module is not returned
within the set monitoring time, the module signals a data bus fault.
Detectable faults
Interruptions of the data lines, short circuits to ground and + 5V, short
circuits between adjacent data lines, e.g. DB0-DB1, DB1-DB2 etc.
Non-detectable faults
Short circuits between even data lines DB0-DB2-DB4-DB6 and between odd
data lines DB1-DB3-DB5-DB7.

Address Bus
Faults

The addresses which have been set at switches S3 and S4 are only “listened
to” by the monitoring module, i.e. they do not output an acknowledgement
signal (RDY/) and are not active on the data bus. If one or both addresses are
not accessed again within the monitoring time, the monitoring module
signals an address bus fault.
Detectable / non-detectable faults
The same as for the data bus, if the inverse addresses 85 (55H) and 170
(AAH) have been set at the addressing switches S3 and S4 of all monitoring
modules.

10-4

System Manual
C79000-G8576-C199-06

Monitoring Module

Control Line
Faults

A control line fault (R/W) occurs if
– the write signal (MEMW/) and the read signal (MEMR/) are active
simultaneously,
– the acknowledgement signal (RDY/) is active without a (MEMW/) or
(MEMR/) signal and
– the address line ’peripheral memory’ (PESP’) has not changed from
status “1” to “0.”
Evaluation of the control signal (PESP’) can be turned off with the S5/7
switch. If the module is used in a programmable controller into which only
I/O modules may be inserted (i.e. no memory modules or CPs), this switch
must always be turned off. In this configuration, only I/O accesses to the bus
are performed and the PESP‘ signal always has the status “1.” It should also
be turned off when using the IM 301, IM 302 1), IM 304 and IM 308
interface modules for expansion units since a permanent PESP‘ signal can be
applied to them.

BASP

If a command output inhibit (BASP) is active, the “BASP” LED is lit.

Messages

If one or more faults occur, the corresponding LEDs are lit, the relay contact
commutes and the module no longer acknowledges with the RDY/ signal.
This timeout can be suppressed by opening the S5/8 switch.

10.1.5

Resetting
There are several ways of resetting the module:
– CPKL/ signal = “1” (when the PLC is switched on);
– Trailing edge of the BASP signal (during startup of the PLC or
following return of the load voltage);
– Applying 24 V to the front connector X4 between connections 4
(RESET input) and 6 (L-);
– Linking connections 4 (RESET input) and 5 (L+) with connector X4.

1) In the S5-115U, the monitoring module cannot be used together with the IM 302 / 311 link.

System Manual
C79000-G8576-C199-06

10-5

Monitoring Module

10.2 Installation

10.2.1

Possible Configurations

3 11 19 27 35 43 51 59 67 75 83 91 99 107115 123 131 139147 155163
EU 187
EU 186
EU 185
EU 184
EU 183
EU 182

PS

0

1

2

3

4

5

7

IM

Recommended slots
Possible slots

ER 2
ER 3

10.2.2

6

Removing and Inserting
The module is pulled out by holding the handles and gently lifting and
lowering while pulling towards you. The monitoring module may only be
removed or inserted if the expansion unit is switched off.

10-6

System Manual
C79000-G8576-C199-06

Monitoring Module

10.2.3

Connecting the RESET Input

RESET input (floating) with external 24-V supply
1
2

Relay contact

3
L+

4
5

L–

6

RESET input
L+ (24V)
L–

RESET input (floating) with internal 24-V suppy
1
2

Relay contact

3
4
5
6

10.2.4

L+ (24V)
L–

Switch Positions of the Relay Contact

Contact not actuated (idle) or fault

Contact actuated (operational)

1

1

2

2

3

3

4

4

5

5

6

6

Contact 1-3 closed

10.2.5

RESET input

Contact 1-2 closed

Installation Guidelines
The module is to be wired according to the VDE regulations 0100, 0110 and
0160.
Detailed information on power supply, cabinet design, cabinet ventilation,
cabinet wiring and protective measures can be found in Chapter 3.

System Manual
C79000-G8576-C199-06

10-7

Monitoring Module

10.3 Operation

Switch S1 (Read)
and S2 (Write)

The addresses set at these switches are acknowledged by the monitoring
module with RDY/ and are therefore not to be used again for inputs and
outputs in this programmable controller (double addressing is not allowed).

Switch S3 (Listen)
and S4 (Listen)

No acknowledgement signal (RDY/) is returned by the monitoring module to
the addresses set the switches S3 and S4. These addresses must be accessed
by the programmable controller as input or output addresses. This means that
they must be occupied by I/O modules or by one monitoring module at
switches S1 and S2. These modules must have been inserted into the last
expansion unit.
To achieve optimum address bus monitoring, inverse addresses should be
used [e.g. 85 (55H) 2) and 170 (AAH)]. It is advisable to make sure that the
setting of switches S3 and S4 is the same on all monitoring modules used.
The setting of switches S1and S2 as well S3 and S4 should be the same on
the monitoring module in the last expansion unit.

Switch

S1

Input address
can be accessed
using MEMR/
(READ)
*

S2

1)

10-8

Output address can be accessed using MEMW/
(WRITE)

Acknowledged by
module with
RDY/
*

*

S3

*

*

S4

*

*

*

Select addresses 213 (D5H) and 170 (AAH) when using the module in the S5-115U.
For exceptions refer to page 10 - 13.

System Manual
C79000-G8576-C199-06

Monitoring Module

Example:

EU183U
EU184U
EU187U

IM 312

IM 312

CC 115U
CC 135U
CC 155U

System Manual
C79000-G8576-C199-06

IM 301
IM 304
IM 308

IM 310
IM 314
IM 318

IM 300

IM 300

IM 312

IM 312

IM 312
IM 312

Central
controllers

IM 312
IM 312

MM 313

IM 312

3rd monitoring module 313
in the last expansion unit

IM 312

MM 313

IM 312

2nd MM
313

IM 312

1st MM
313

MM 313

Expansion units

IM 310
IM 314
IM 318
EU183U
EU185U

10-9

Monitoring Module

10.3.1

Addressing

Example 1

S5-130K, S5-135U or S5-155U
1st MM

2nd MM

3rd MM in the
last EU

S1 e.g.

127

(7FH)

3)

e.g.

126

(7EH)

3)

85

(55H)

4)

S2 e.g.

127

(7FH)

3)

e.g.

126

(7EH)

3)

170

(AAH)

4)

S3

85

(55H)

5)

85

(55H)

5)

85

(55H)

5)

S4

170

(AAH)

5)

170

(AAH)

5)

170

(AAH)

5)

User program in OB 1 or FB 0
without S5-DOS

with S5-DOS

L

EB

127

L

PY

127

T

AB

127

T

PY

127

L

EB

126

L

PY

126

T

AB

126

T

PY

126

L

EB

85

L

PY

85

T

PB

170

T

PY

170

BE

BE

3)

Possible addresses 0 (00H) to 255 (FFH)

4)

To achieve optimum fault detection, set the inverse addresses 85 (55H) and 170 (AAH) at S1 and S2.

5)

Since the addresses of the monitoring module switches S3 and S4 are not acknowledged, this must be done by the
monitoring module contained in the last expansion unit (the most remote from the central controller). The addresses
85 (55H) or 170 (AAH) of this monitoring module must be coded at switches S1 or S2, respectively.
These addresses may no longer be occupied for I/O tasks.

10-10

System Manual
C79000-G8576-C199-06

Monitoring Module

Example 2

S5-115U
S1 e.g.

128

(80H)

6)

e.g.

129

(81H)

6)

213

(D5H)

6)

S2 e.g.

128

(80H)

6)

e.g.

129

(81H)

6)

170

(AAH)

6)

S3

213

(D5H)

7)
8)

213

(D5H)

7)8)

213

(D5H)

7)8)

S4

170

(AAH)

7)

170

(AAH)

7)

170

(AAH)

7)

User program in OB 1 or FB 0
without S5-DOS

with S5-DOS

L

PB

128

L

PY

128

T

PB

128

T

PY

128

L

PB

129

L

PY

129

T

PB

129

T

PY

129

L

PB

213 8)

L

PY

213 8)

T

PB

170

T

PY

170

BE

BE

6) When using the monitoring module in the S5-115U, always select addresses > 127 since that is the only way to address
byte to byte.
7) To achieve maximum fault detection, select inverse addresses > 127, e.g. 213 (D5H) and 170 (AAH). In this combination,
the address bit ADB 7 is not monitored.
8) If ADB 7 is also to be monitored, the address 84/85 (54H/55H) in the last expansion unit must be occupied by an input or
output module and cyclically accessed by the user program. Set address 85 (55H) in place of 213 (D5H) at switch S3 of all
monitoring modules. Select any address between 128 (80H) and 255 (FFH) for switch S1 of the monitoring module in the
last expansion unit. As an alternative, you may access the address at S1 of the monitoring module in the last expansion unit via
direct access (without process image) using L PB 85 or L PY 85. Then, the addresses 84 and 85 (54H) and (55H) in the process
image may no longer be used by other inputs. The address at S3 of all monitoring modules is then also to be set to 85 (55H).

System Manual
C79000-G8576-C199-06

10-11

Monitoring Module

10.3.2

Setting the Address Switches S1, S2, S3, S4
The addresses are set as one-byte addresses as in the case of I/O modules.
8

7

6

5

4

3

2

1
OFF
ON
ADB 0 Significance 1
ADB 1 Significance 2
ADB 2 Significance

4

ADB 3 Significance

8

ADB 4 Significance 16
ADB 5 Significance 32
ADB 6 Significance 64
ADB 7 Significance 128

The significance of the rockers pressed down to ON at the switches must be
added.

Example

Address 85 is to be set.

rockers to be pressed down to ON

Significance

1 (ADB 0)

1

3 (ADB 2)

4

5 (ADB 4)

16

7 (ADB 6)

8

7

6

5

4

3

64
85

2

1
OFF
ON

10-12

System Manual
C79000-G8576-C199-06

Monitoring Module

10.3.3

Setting the Switch S5

8 7 6 5 4 3 2 1
OFF
ON
ON: RDY/ is suppressed in case of fault
OFF: RDY/ is also output in case of fault
When BASP is active (“1” signal)
RDY/ is always output

ON: PESP‘ monitoring on

Monitoring time

1s
500ms
250ms
125ms

Select the monitoring time (between 125 ms and 1 s) by switching one of the
switches S5/1 to S5/4 to ON. If none of the four switches S5/1 to S5/4 is in
the ON position, for safety reasons the monitoring time has been set to 1 s.
If serial interface modules and the link between IM 304 and IM 314 are used,
the PESP‘ monitoring is to be switched off (see Section 10.1.4: Control line
faults).
Should the acknowledgement signal (RDY/) not be suppressed in the event of
a fault, the switch S5/8 must be in the OFF position.
When a BASP signal is active, the RDY/ signal will always be output.

System Manual
C79000-G8576-C199-06

10-13

Monitoring Module

10.4 Technical Specifications

Power supply
Supply voltage of the system bus
Power consumption

+5V 5%
450 mA max.

RESET input
Rated input voltage
Electrical isolation
Input voltage
for signal 0
for signal 1
Input current
Permissible cable length

24 V DC
Yes
–33 to + 5 V DC
or input open
+13 to + 33 V DC
8.5 mA
100 m max. unscreened

Sensor supply for RESET input
Rated output voltage
Electrical isolation
Output voltage
Output current

24 V DC
Yes
20 to 30 V DC
short-circuit proof to L–
20 mA max.

Relay contact
Loading of contact with resistive load
or inductive load

30 V DC/ 1 A max.

Safety test
Voltage test acc. to VDE 0160
Relay contacts referred to internal
RESET input referred to internal
RESET input referred to relay contacts
Surge voltage test acc. to IEC 255-4
Input referred to ground

500 r.m.s.
500 r.m.s.
500 r.m.s.
1kV; 1.2/50 ms

Interference test
Radio interference test acc. to IEC 255-4
Radio interference test acc. to IEC 65 (Co) 39

Input referred to ground: 1 kV; 1 MHz
Input referred to ground: 1 kV; burst

Mechanical data
Dimensions (w x h x d)
Weight

10-14

20 mm x 243 mm x 193 mm
270g

System Manual
C79000-G8576-C199-06

Monitoring Module

Ambient conditions
Operating temperature
Storage and transportation temperature
Relative humidity
Operating altitude
Vibration acc. to IEC 68-2-6
Shock acc. to IEC 68-2-27

0 to + 60 oC
–25 to + 70 oC
max. 95 % at 25 oC; no condensation
max. 3500 m above sea level
10 to 57 Hz, 0.15 mm; 57 to 500 Hz, 2 g
12 shocks, half-sine; 15 g / 11 ms

Pin assignment of bus connector X1

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

System Manual
C79000-G8576-C199-06

b

z

0V
PESP’
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
–
–
–
–
BASP
0V

5V
–
CPKL/
MEMR/
MEMW/
RDY/
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7
–
0V

10-15

Monitoring Module

10.5 Address Table

128
64
32
16

Significance

Byte address

1
2
4
8
0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

65

66

67

68

69

70

71

72

73

74

75

76

77

78

79

80

81

82

83

84

85

86

87

88

89

90

91

92

93

94

95

96

97

98

99 100 101 102 103 104 105 106 107 108 109 110 111

112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127
128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143
144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159
160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175
176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191
192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207
208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223
224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239
240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255

Switch position

10-16

4
2
1

128
64
32
16
8

ON

System Manual
C79000-G8576-C199-06

Connector Assignments

11

In this chapter are the connector assignments of the
backplane for the central controllers and expansion units
power supplies
backplane connectors and front connectors of the CPUs, coordinators
and IMs.

System Manual
C79000-G8576-C199-06

11-1

Connector Assignments

Connector assignments of the backplane of the S5-135U/155U CC
Slot 3,
COR, I/O
Backplane
l
conn. 1

Backplane
conn. 2

Slot 11, 27, 43, 59
CPU, CP, I/O, IP

Pin
N
No.

Rin Row
z

b

d

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
PL
RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7

M5 V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5 V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
DB 12
DB 13
DB 14
DB 15

M5 V
DB 8
DB 9
DB 10
DB 11
PL
PL
PL
PL
PL
PL
PL
PL
PL
M24 V 2)
M5 V

PL

NAU
BAU
RESETA
PEU
GEP
PL
M24 V 2)
P24 V

Pin
N
No.

Rin Row
z

b

UBAT
ADB 12
ADB 13
ADB 14
ADB 15
PL
PL
PL
PL
PL
PL
PL
DSI
PL
BASPA

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
PL
RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7
PL
PL

M5 V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5 V

PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
PL
M24 V 2)
P15 V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
DB 12
DB 13
DB 14
DB 15
M5 V
NAU
BAU

M5 V
DB 8
DB 9
DB 10
DB 11

PEU
GEP
PL
M24 V 2)
P24 V

d

PL
PL
M5 V
PL
PL
M5 V
PL
PL
M24 V 2)
M5 V

UBAT
ADB 12
ADB 13
ADB 14
ADB 15
IRx 1)

IRE
IRF
IRG
DSI
PL
BASPA

M5 V

PL
PL
PL
M24 V 2)
P15 V

Abbreviations:
IM-V – IM slot with additional power supply output
IRQ – Interrupt source (module which generates the interrupt)
PL – Private line
1)
2)

11-2

See pin designations for the interrupt signals
M24 V also serves as the return line for P15 V.

System Manual
C79000-G8576-C199-06

Connector Assignments

Slot 19, 35, 51, 67, 75, 83, 91, 99
CP, IP, I/O, IRQ
Backplane
l
conn. 1

Backplane
conn. 2

PinN
No.

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
PL
RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7
PL

M5 V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5 V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
DB 12
DB 13
DB 14
DB 15

M5 V
DB 8
DB 9
DB 10
DB 11

NAU
BAU

PL
PL

Slot 107, 115, 123, 131
CP, IP, I/O, IM307 (IRQ)

d
UBAT
ADB 12
ADB 13
ADB 14
ADB 15
IRA
IRB
IRC
IRD
IRE
IRF
IRG
DSI
BASPA

PL
PL

PL *

PL *
PL
M24 V 1)
M5 V

PL
PL
M24 V 1)
P15 V

GEP
PL
M24 V 1)
P24 V

PL *

= Only at slots 75, 83, 91 and 99

2)

M24 V also serves as the return line for P15 V.

System Manual
C79000-G8576-C199-06

PinN
No.

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
PL
RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7
PL

M5 V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5 V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
DB 12
DB 13
DB 14
DB 15

M5 V
DB 8
DB 9
DB 10
DB 11

NAU
BAU
RESETA

PL
PL
PEU
PL
PL

d
UBAT
ADB 12
ADB 13
ADB 14
ADB 15
IRA
IRB
IRC
IRD
IRE
IRF
IRG
DSI
BASPA

GEP
PL
M24 V 1)
P24 V

PL
M24 V 1)
M5 V

PL
PL
M24 V 1)
P15 V

11-3

Connector Assignments

Slot 139, 147
I/O, IM, IP without page addressing
Backplane
conn. 1

Backplane
conn. 2

PinNo
No.

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
PL
RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7

M5 V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5 V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
DB 12
DB 13
DB 14
DB 15

M5 V
DB 8
DB 9
DB 10
DB 11

RESETA

PEU

M5 V
M5 V
M5 V
M5 V
M5 V
M5 V

M5 V
M5 V
M5 V
M5 V
M5 V
M5 V

Slot 155, 163
I/O, IM

d

ADB 12
ADB 13
ADB 14
ADB 15

M5 V
M5 V
M5 V
M5 V
M5 V
M5 V
M5 V
BASPA

PinNo
No.

Pin Row
z

b

d

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
PL
RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7

M5 V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5 V

P5 V
ADB 12
ADB 13
ADB 14
ADB 15
P5 V
P5 V
M5 V
M5 V
M5 V
M5 V
M5 V
M5 V
M5 V
BASPA

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

P5 V
DB 12
DB 13
DB 14
DB 15
P5 V
P5 V
P5 V
RESETA

M5 V
DB 8
DB 9
DB 10
DB 11
P5 V
P5 V
P5 V
PEU

M5 V
M5 V
M5 V
M5 V
M5 V
M5 V

M5 V
M5 V
M5 V
M5 V
M5 V
M5 V

Pin designation of the interrupt signals on the backplane
Interrupt Sink

Interrupt Source

Module

CPU 1

CPU 2

CPU 3

CPU 4

I/Os/CP/IP

Slot No.

11

27

43

59

19, 35, 51, 67-131

1d 14
1d 22
1d 24
1d 26

1d 14
1d 16
1d 18
1d 20
1d 22
1d 24
1d 26

Signal
IRA
IRB
IRC
IRD
IRE (CPU 948 only)
IRF (CPU 948 only)
IRG (CPU 948 only)

11-4

1d 14
1d 14
1d 14
1d 22
1d 24
1d 26

1d 22
1d 24
1d 26

1d 22
1d 24
1d 26

System Manual
C79000-G8576-C199-06

Connector Assignments

Connector assignments of the backplane for the EU 183U, 184U, 187 U

Backplane
p
conn. 1

Backplane
p
conn. 1

Backplane
conn. 2

I/O Modules
EU
Slot
183U
11 to 155
184U
3 to 155
187U
3 to 147
Pin
Pin Row
N
No.
z
2
+ 5V
4
–
6
CPKL
8
MEMR
10
MEMW
RDY
12
DB0
14
DB1
16
DB2
18
DB3
20
DB4
22
DB5
24
DB6
26
DB7
28
–
30
–
32

IM 312-5
EU
Slot
184U
163
187U

IM 300-3 and -5 / 312-3
EU
Slot
183U 163
PinPin Row
N
No.
z
b
2
+ 5V
0V
4
–
PESP
6
CPKL
ADB0
8
MEMR
ADB1
10
MEMW
ADB2
RDY
12
ADB3
DB0
14
ADB4
DB1
16
ADB5
DB2
18
ADB6
DB3
20
ADB7
DB4
22
0V
DB5
24
0V
DB6
26
0V
DB7
28
0V
EANK
30
BASP
–
32
0V
2
+ 5V
0V
4
–
–
6
–
–
8
–
–
10
–
–
12
+5V
+5V
14
+5V
+5V
16
+5V
+5V
18
CPKLA
NAU
–
–
20
0V
0V
22
0V
0V
24
0V
0V
26
0V
0V
28
0V
0V
30
0V
0V
32

System Manual
C79000-G8576-C199-06

Pin
N
No.

b
0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
0V
0V
0V
0V
BASP
0V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

d
Shield
+5V
–
–
–
–
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
BASPA
–
0V
–
–
–
+5V
+5V
+5V
–
–
–
–
–
–
–
–

Pin Row
z
+ 5V
–
CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
–
0V

b
0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
0V
0V
0V
0V
BASP
0V

IM 310, IM 314, IM 317, IM 318
EU
Slot
183U 3
PinPin Row
N
No.
z
b
2
+ 5V
0V
4
Takt
PESP
6
CPKL
ADB0
8
MEMR
ADB1
10
MEMW
ADB2
RDY
12
ADB3
DB0
14
ADB4
DB1
16
ADB5
DB2
18
ADB6
DB3
20
ADB7
DB4
22
0V
DB5
24
0V
DB6
26
0V
DB7
28
0V
–
30
BASP
–
32
0V
2
+ 5V
0V
4
–
–
6
–
–
8
–
–
10
–
–
12
+5V
+5V
14
+5V
+5V
16
+5V
+5V
18
CPKLA
NAU
–
–
20
0V
0V
22
0V
0V
24
0V
0V
26
0V
0V
28
0V
0V
30
0V
0V
32

d
Shield
+5V
+5V
+5V
+5V
+5V
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
0V

d
Shield
+5V
–
–
–
–
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
BASPA
–
0V
–
–
–
+5V
+5V
+5V
–
–
–
–
–
–
–
–

11-5

Connector Assignments

Connector assignments of the backplane for the EU 185U
IM 310 and IM 314
I/O Module
Slot 3
PinNo.
Backplane
conn. 1

Backplane
conn. 2

11-6

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

Pin Row
z
+5V
RESET
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
DSI
+5V
DB12
DB13
DB14
DB15

923C Coordinator
I/O Module
Slot 11
b
0 V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
0V

RESETA

0V
DB8
DB9
DB10
DB11
+ 5V
+ 5V
+ 5V
NAU

0V
0V
0V
0V
0V
0V

0V
0V
0V
0V
0V
0V

d

ADB12
ADB13
ADB14
ADB15

0V
0V
0V
0V
0V
0V
0V
BASPA
0V
RESET

PinNo.
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

Pin Row
z
+5V
RESET
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7

+5V
DB12
DB13
DB14
DB15
NAU
BAU
RESETA
PEU
GEP

M2
+ 24V

b
0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
0V
0 V
DB8
DB9
DB10
DB11
RxDS6
TxDS6
RxDS4
TxDS4

RxDS2
TxDS2
M2
0V

d
UBAT
ADB12
ADB13
ADB14
ADB15

DSI
BASPA

RxDS8
TxDS8
RxDS7
TxDS7
RxDS5
TxDS5
RxDS3
TxDS3
RxDS1
TxDS1
SPRxD
M2
+ 15 V

System Manual
C79000-G8576-C199-06

Connector Assignments

Communication Processor
Intelligent I/Os
I/O Module
Slots 19 to 75
PinNo.
Backplane
conn. 1

Backplane
conn. 2

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

Pin Row
z
+5V
RESET
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7

+5V
DB12
DB13
DB14
DB15

b
0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
0V

Communication Processor
Intelligent I/Os
I/O Module
Slots 83 to 139
d
UBAT
ADB12
ADB13
ADB14
ADB15

DSI
BASPA

0V
DB8
DB9
DB10
DB11

NAU
BAU

PEU
GEP

TxDSn
RxDSn

M2
+ 24 V

System Manual
C79000-G8576-C199-06

M2
0V

SPRxD
M2
+15 V

PinNo.
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

Pin Row
z
+5V
RESET
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7

+5V
DB12
DB13
DB14
DB15

b
0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
0V

d
UBAT
ADB12
ADB13
ADB14
ADB15

DSI
BASPA

0V
DB8
DB9
DB10
DB11

NAU
BAU

PEU
GEP

M2
+ 24 V

M2
0V

M2
+ 15 V

11-7

Connector Assignments

IM 314 R
I/O Module
Slot 147, 155
PinNo.
Backplane
conn. 1

Backplane
conn. 2

11-8

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

Pin Row
z
+5V

IM 300
I/O Module
Slot 163

0V

b
0 V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
0V

+5V
NA0
NA1
NA2
NA3

0V
SA0
SA1
SA2
SA3

RESET
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7

RESETA

NAU

0V
0V
0V
0V
0V
0V

0V
0V
0V
0V
0V
0V

d
Shield
ADB12
ADB13
ADB14
ADB15

0V
BASPA
0V
RESET

PinNo.
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

Pin Row
z
+5V
RESET
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7

b
0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
0V

+5V

0 V

+ 5V
+ 5V
+ 5V
RESETA

+ 5V
+ 5V
+ 5V
NAU

0V
0V
0V
0V
0V
0V

0V
0V
0V
0V
0V
0V

d
+5V
ADB12
ADB13
ADB14
ADB15
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
BASPA

System Manual
C79000-G8576-C199-06

Connector Assignments

Connector assignments of the power supply units

Connector X1

The terminals for the supply lines between the power supply unit and the
backplane are in an 8-way connector (Connector X1) at the rear of the unit.
The following figures show the connector assignments.
5V/18A power supply units
Pins 4 to 6 are not fitted.

M2 (0V)

1

2

5V/18A

3

4

5

6

7

8

5V/40A power supply units

M2 (0V)

1

Connector X2

2

5V/40A

3

4

5

6

7

8

The signal terminals of the power supply unit are in a 37-way connector
(Connector X2) at the rear of the unit.
The following figure shows the connector assignments. Pins 8 and 9 are
reserved.

RESETA

GEP
reserved

DSI
NAU

1

2

3

4

BASPA

5

6

7

8 9

BAU

RESET

10 11 12 13 14 15 16 17 18 19

M2 (0V)

+15V

24V

U-BATT

20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

System Manual
C79000-G8576-C199-06

11-9

Connector Assignments

Connector assignments of the 6ES5 955-3NA12 power supply unit

Connector X1

The terminals of the supply lines between the power supply unit and the
backplane are in an 8-way connector (subminiature, fitted with 8 high-current
contacts, Series D to MIL-C24308).

M2 (0V)
1

Connector X2

2

5V/10A
3

4

5

6

7

8

The signal terminals of the power supply unit are in a 37-way connector
(plug connector, 37-way, Series D to MIL-C24308).

RESET A
DSI
GEP
RESET
DS
NAU HOLD
1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19
24V/0.8A

+15 V
BASP

BASP A IR

U BATT

RESIN CPKL BAU RLSA

M2 (0V)

–15V
unassigned

20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

11-10

System Manual
C79000-G8576-C199-06

Connector Assignments

Assignments of the backplane connector CPU 948

Backplane
conn. 1

Backplane
conn. 2

Pin
No.
N

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V
DB 12
DB 13
DB 14
DB 15
M5V
NAU
BAU
+5V

System Manual
C79000-G8576-C199-06

RESET
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
HALT

PEU
GEP

M 24 V
+ 24 V

M5V
DB8
DB9
DB 10
DB 11
PGBUSX
PGBUSY
M5V
STEU
STOPPA
M5V
RxD
PERO
M 24 V
M5V

d
UBAT
ADB 12
ADB 13
ADB14
ADB 15
IR

IRE
IRF
IRG
DSI
BUSEN
BASPA

M5V

TxD
TEST
M 24V

11-11

Connector Assignments

Assignments of the backplane connector CPU 928B

Pin
No.
N
Backplane
conn. 1

Backplane
conn. 2

11-12

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V
DB 12
DB 13
DB 14
DB 15
M5V
NAU
BAU
+5V

CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
HALT

PEU
GEP

M 24 V
+ 24 V

M5V
DB8
DB9
DB 10
DB 11

M5V
STEU
STOPPA
M5V
RxD
PERO
M 24 V
M5V

d
UBAT
ADB 12
ADB 13
ADB14
ADB 15
IR

DSI
BUSEN
BASPA

M5V

TxD
TEST

System Manual
C79000-G8576-C199-06

Connector Assignments

Assignments of the backplane connectorCPU 928

Pin
No.
N
Backplane
conn. 1

Backplane
conn. 2

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V
DB 12
DB 13
DB 14
DB 15
M5V
NAU
BAU
+5V

System Manual
C79000-G8576-C199-06

CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
HALT

PEU
GEP

M 24 V
+ 24 V

M5V
DB8
DB9
DB 10
DB 11

M5V
STEU
STOPPA
M5V
RxD
PERO
M 24 V
M5V

d
UBAT
ADB 12
ADB 13
ADB14
ADB 15
IR

DSI
BUSEN
BASPA

M5V

TxD
TEST

11-13

Connector Assignments

Assignments of the backplane connector CPU 922

Pin
No.
N
Backplane
conn. 1

Backplane
conn. 2

11-14

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V
CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
QUITT
HALT

M5V
PESP
ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
M5V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V

d
UBAT
ADB 12
ADB 13
ADB14
ADB 15
IR

DSI
BUSEN
BASPA

M5V

M5V
NAU
BAU

PEU
GEP

M 24 V
+ 24 V

M5V
STEU
STOPPA
M5V
RxD
PERO
M 24 V
M5V

TxD
TEST

System Manual
C79000-G8576-C199-06

Connector Assignments

Assignments of the CPU front connector (PG interface)

System Manual
C79000-G8576-C199-06

Pin No.

Designation

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Housing/0 V/0Vext
RxD
VPG + 5 V DC
+ 24 V from bus
0 V/0 Vint
TxD
TxD
Housing/0 V/0Vext
RxD
24 V ground
20 mA/transmitter
0 V/0 Vint
20 mA/receiver
VPG + 5 V DC
0 V/0 Vint

11-15

Connector Assignments

Assignments of the backplane connector: 923A coordinator

Pin
No.
N
Backplane
conn. 1

Backplane
conn. 2

11-16

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V

RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7

ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11

HALT

M5V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V

d
UBAT

BUSEN 1
BUSEN 2
BUSEN 3
BUSEN 4

DSI

NAU

STEU
STOPPA
TEST
PERO
M5V

System Manual
C79000-G8576-C199-06

Connector Assignments

Assignments of the backplane connector: 923C coordinator

Pin
No.
N
Backplane
conn. 1

Backplane
conn. 2

Pin Row
z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V

RESET
MEMR
MEMW
RDY
DB 0
DB 1
DB 2
DB 3
DB 4
DB 5
DB 6
DB 7

ADB 0
ADB 1
ADB 2
ADB 3
ADB 4
ADB 5
ADB 6
ADB 7
ADB 8
ADB 9
ADB 10
ADB 11

HALT

M5V

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V

M5V

System Manual
C79000-G8576-C199-06

NAU

RxD 6
TxD 6
RxD 4
TxD 4
STEU
STOPPA

d
UBAT
ADB 12
ADB 13
ADB 14
ADB 15
BUSEN 1
BUSEN 2
BUSEN 3
BUSEN 4

DSI

RxD 8
TxD 8
RxD 7
TxD 7
RxD 5
TxD 5
RxD 3
TxD 3
RxD 1
TxD 1
TEST

PERO
M 24 V
M5V

M5V

11-17

Connector Assignments

Assignments of the front connector for the coordinators

11-18

Pin No.

Designation

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Housing/0 V/0Vext
Receiver TTY(-)
Private line
+24 V
Private line
Transmitter TTY (+)
Transmitter TTY (-)
Housing/0 V/0Vext
Receiver TTY (+)
24 V ground (20 mA (-) current sources)
20 mA (+) current source
Private line
20 mA (+) current source
Private line
Private line

System Manual
C79000-G8576-C199-06

Connector Assignments

Assignments of the backplane connectors of the IMs

B
a
c
kp
l
a
n
e
c
o
n
n
1
B
a
c
kp
l
a
n
e
c
o
n
n
2

IM 300-3

IM 300-5

IM 300-5L

IM 301-3

Pin Row

Pin Row

Pin Row

Pin Row

Pin

z

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

b

d

z

+5V
0V
–
PESP
CPKL ADB0
MEMR ADB1
MEMW ADB2
RDY ADB3
DB0
ADB4
DB1
ADB5
DB2
ADB6
DB3
ADB7
DB4
0V
DB5
0V
DB6
0V
DB7
0V
–
BASP
–
0V

Shield
–
–
–
–
–
–
–
0V
0V
0V
0V
0V
0V
0V
–

+5V
–
–
–
–
–
–
–
–
–
0V
0V
0V
0V
0V
0V

–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

–
–
–
–
–
–
–
–
NAU
–
0V
0V
0V
0V
0V
0V

System Manual
C79000-G8576-C199-06

b

d

z

b

d

z

+5V
0V
–
PESP
CPKL ADB0
MEMR ADB1
MEMW ADB2
RDY ADB3
DB0
ADB4
DB1
ADB5
DB2
ADB6
DB3
ADB7
DB4
ADB 8
DB5
ADB 9
DB6
ADB 10
DB7
ADB 11
–
BASP
0V
0V

Shield
+5V
–
–
–
–
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
–

+5V
–
RESET
MRD
MWR
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
–
–

M
PESP
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
M
–

–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

+5V
0V
–
PESP
CPKL ADB0
MEMR ADB1
MEMW ADB2
RDY ADB3
DB0
ADB4
DB1
ADB5
DB2
ADB6
DB3
ADB7
DB4
ADB 8
DB5
ADB 9
DB6
ADB 10
DB7
ADB 11
–
BASP
–
0V

Shield
–
–
–
–
–
–
–
0V
0V
0V
0V
0V
0V
0V
–

+5V
–
–
–
–
+5V
+5V
+5V
–
–
0V
0V
0V
0V
0V
0V

–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

+5V
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

M
–
–
–
–
–
–
–
PEU
–
–
–
–
–
–
M

–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

+5V
–
–
–
–
+5V
+5V
+5V
–
–
0V
0V
0V
0V
0V
0V

–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

–
–
–
–
–
+5V
+5V
+5V
–
–
0V
0V
0V
0V
0V
0V

b

–
–
–
–
–
+5V
+5V
+5V
NAU
–
0V
0V
0V
0V
0V
0V

d

11-19

Connector Assignments

IM 301-5

B
a
c
kp
l
a
n
e
c
o
n
n
1

B
a
c
kp
l
a
n
e
c
o
n
n
2

11-20

IM 304

Pin

Pin Row
z

b

d

Pin Row
z

b

d

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V
–
CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
–
0V
+5V
–
–
–
–
+5V
+5V
+5V
–
–
0V
0V
0V
0V
0V
0V

0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB 8
ADB 9
ADB 10
ADB 11
BASP
0V
–
–
–
–
–
+5V
+5V
+5V
NAU
–
0V
0V
0V
0V
0V
0V

Shield
+5V
–
–
–
–
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

+5V
–
CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
–
–
+5V
DB12
DB13
DB14
DB15
–
PEU *
–
–
–
–
–
–
–
–
–

M
–
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
ADB8
ADB9
ADB10
ADB11
BASP
M
M
DB8
DB9
DB10
DB11
–
–
–
PEU *
–
–
–
–
–
–
M

–
–
ADB 12
ADB 13
ADB14
ADB15
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–

System Manual
C79000-G8576-C199-06

Connector Assignments

B
a
c
kp
l
a
n
e
c
o
n
n
1
B
a
c
kp
l
a
n
e
c
o
n
n
2

IM 310-3

IM 312-3

IM 312-5

IM 314

Pin Row

Pin Row

Pin Row

Pin Row

Pin

z

b

d

z

b

d

z

b

d

z

b

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V
–
CPKL
MEMRA
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
–
–

0V
PESP
ADB0
DB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
–
–
–
–
BASP
0V

Shield+
+5V
–
–
–
–
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
–

+5V
–
CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
NAU
–

0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
–
–
–
–
BASP
0V

–
+5V
+5V
+5V
+5V
+5V
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
BASPA

+5V
–
CPKL
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
–
–

0V
PESP
ADB0
ADB1
ADB2
ADB3
ADB4
ADB5
ADB6
ADB7
–
–
–
–
BASP
0V

–+
+5V
+5V
+5V
+5V
+5V
+5V
+5V
0V
0V
0V
0V
0V
0V
0V
–

+5V
–
CPKLa
MEMR
MEMW
RDY
DB0
DB1
DB2
DB3
DB4
DB5
DB6
DB7
DSI
–

M
–
PESP +5V
ADB0 ADB12
ADB1 ADB13
ADB2 ADB14
ADB3 ADB15
ADB4 –
ADB5 –
ADB6 –
ADB7 –
ADB8 –
ADB9 –
ADB10–
ADB11–
BASP –
M
–

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32

+5V
–
–
–
–
–
–
–
CPKLA
–
0V
0V
0V
0V
0V
0V

0V
–
–
–
–
–
–
–
NAU
–
0V
0V
0V
0V
0V
0V

+5V
DB12
DB13
DB14
DB15
–
–
–
CPKLA
–
M
M
M
M
M
M

M
DB8
DB9
DB10
DB11
+5V
+5V
+5V
NAU
–
M
M
M
M
M
M

System Manual
C79000-G8576-C199-06

–
US
–
–
–
+5V
+5V
+5V
–
–
–
–
–
–
–
–

d

–
–
CPKLe
–
–
–
–
–
–
–
–
–
–
–
–
–

11-21

Connector Assignments

Assignments of the front blade connectors
IM 300-3

IM 300-5C

Pin
No.

Blade Connector 3

Blade Connector 3

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

Shield
–
–
–
+PEU
– PEU
ADB1
ADB4
ADB7
DB1
DB4
0V
0V
0V
0V
0V
Shield
–
–
–
+ ZGU
– ZGU
ADB0
ADB3
ADB6
0V
DB3
DB6
0V
0V
0V
0V
0V
–
–
CPKL
MEMR
MEMW
PESP
ADB2
ADB5
DB0
DB2
DB5
DB7
RDY
BASP
–
0V
0V

0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 1
ADB 4
ADB 7
DB 1
DB 4
0V
0V
0V
0V
0V
0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 0
ADB 3
ADB 6
0V
DB 3
DB 6
0V
0V
0V
0V
0V
+5V
FAKT
CPKL
MEMR
MEMW
PESP
ADB 2
ADB 5
DB 0
DB 2
DB 5
DB 7
RDY
BASP
EANK
0V
0V

IM 300-5L

IM 301

Blade Connector 4

Blade Connector 3, 4

Blade Connector 3

Blade Connector 4

Blade Connector 3

Blade Connector 4

0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 1
ADB 4
ADB 7
DB 1
DB 4
0V
0V
0V
0V
0V
0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 0
ADB 3
ADB 6
0V
DB 3
DB 6
0V
0V
0V
0V
0V
+5V
FAKT
CPKL
MEMR
MEMW
PESP
ADB 2
ADB 5
DB 0
DB 2
DB 5
DB 7
RDY
BASP
EANK
0V
0V

Shield
+5V
+5V
+5V
PEU1
PEU2
ADB1
ADB4
ADB7
DB1
DB4
M
M
M
M
M
Shield
+5V
+5V
+5V
+5V
+5V
ADB0
ADB3
ADB6
M
DB3
DB6
M
M
M
M
M
+5V

Shield
–
–
–
+PEU
– PEU
ADB1
ADB4
ADB7
DB1
DB4
0V
0V
0V
0V
0V
Shield
–
–
–
– ZGU
+ ZGU
ADB0
ADB3
ADB6
0V
DB3
DB6
0V
0V
0V
0V
0V
–
–
CPKL
MEMR
MEMW
PESP
ADB2
ADB5
DB0
DB2
DB5
DB7
RDY
BASP
–
0V
0V

Shield
+ ADB 4
– ADB 4
+ ADB 5
– ADB 5
+ ADB 6
– ADB 6
+ ADB 7
– ADB 7
+ DB 6
– DB 6
+ DB 7
– DB 7
+ PEU
– PEU
Rg 0
Shield
+ ADB 0
– ADB 0
+ ADB 1
– ADB 1
+ ADB 2
– ADB 2
+ ADB 3
– ADB 3
+ DB 3
– DB 3
+ DB 4
– DB 4
+ DB 5
– DB 5
+ ZGU
– ZGU
+ MEMR
– MEMR
+ MEMW
– MEMW
+ PESP
– PESP
+ BASP
– BASP
+ DB 0
– DB 0
+ DB 1
– DB 1
+ DB 2
– DB 2
+ RDY
– RDY
0V

+ AD 12
– AD 12
+ AD 13
– AD 13
+ AD 14
– AD 14
+ AD 15
– AD 15
+ AD 6
– AD 6
+ AD 7
– AD 7
+ PEU
– PEU
–
–
+ AD 8
– AD 8
+ AD 9
– AD 9
+ AD 10
– AD 10
+ AD 11
– AD 11
+ AD 3
– AD 3
+ AD 4
– AD 4
+ AD 5
– AD 5
+ ZGU
– ZGU
+ MEMR
– MEMR
+ MEMW
– MEMW
+ ALE
– ALE
+ BASP
– BASP
+ AD0
– AD 0
+ AD 1
– AD 1
+ AD 2
– AD 2
+ RDY
– RDY
–

+ AD 12
– AD 12
+ AD 13
– AD 13
+ AD 14
– AD 14
+ AD 15
– AD 15
+ AD 6
– AD 6
+ AD 7
– AD 7
+ PEU **
– PEU **
0V
–0V
+ AD 8
– AD 8
+ AD 9
– AD 9
+ AD 10
– AD 10
+ AD 11
– AD 11
+ AD 3
– AD 3
+ AD 4
– AD 4
+ AD 5
– AD 5
(ZGU/
PAR) *
+ MEMR
– MEMR
+ MEMW
– MEMW
+ ALE
– ALE
(BASP/
PAF) *
+ AD0
– AD 0
+ AD 1
– AD 1
+ AD 2
– AD 2
+ RDY
– RDY
–

RESET
MRD
MWR
PESP
ADB2
ADB5
DB0
DB2
DB5
DB7
RDY
BASP
M
M

IM 304

* For parallel communication with the IM 324U
** No signal in parallel communication

11-22

System Manual
C79000-G8576-C199-06

Connector Assignments

Pin
No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

IM 310-3

IM 312-3

Blade Connector 3

Blade Connector 4

Blade Connector 3

Blade Connector 3

Blade Connector 4

Blade Connector 3

Blade Connector 4

0Vext
+ ADB 4
– ADB 4
+ ADB 5
– ADB 5
+ ADB 6
– ADB 6
+ ADB 7
– ADB 7
+ DB 6
– DB 6
+ DB 7
– DB 7
+ PEU
– PEU
–
0Vext
+ ADB 0
– ADB 0
+ ADB 1
– ADB 1
+ ADB 2
– ADB 2
+ ADB 3
– ADB 3
+ DB 3
– DB 3
+ DB 4
– DB 4
+ DB 5
– DB 5
+ ZGU
– ZGU
+ MEMR
– MEMR
+ MEMW
– MEMW
+ PESP
– PESP
+ BASP
– BASP
+ DB 0
– DB 0
+ DB 1
– DB 1
+ DB 2
– DB 2
+ RDY
– RDY
–

0Vext
+ ADB 4
– ADB 4
+ ADB 5
– ADB 5
+ ADB 6
– ADB 6
+ ADB 7
– ADB 7
+ DB 6
– DB 6
+ DB 7
– DB 7
+ PEU
– PEU
5V
0Vext
+ ADB 0
– ADB 0
+ ADB 1
– ADB 1
+ ADB 2
– ADB 2
+ ADB 3
– ADB 3
+ DB 3
– DB 3
+ DB 4
– DB 4
+ DB 5
– DB 5
+ ZGU
– ZGU
+ MEMR
– MEMR
+ MEMW
– MEMW
+ PESP
– PESP
+ BASP
– BASP
+ DB 0
– DB 0
+ DB 1
– DB 1
+ DB 2
– DB 2
+ RDY
– RDY
0V

Shield
–
–
–
+ PEU
– PEU
ADB1
ADB4
ADB7
DB1
DB4
0V
0V
0V
0V
0V
Shield
–
–
–
– ZGU
+ ZGU
ADB0
ADB3
ADB6
0V
DB3
DB6
0V
0V
0V
0V
0V
–
–
CPKL
MEMR
MEMW
PESP
ADB2
ADB5
DB0
DB2
DB5
DB7
RDY
BASP
–
0V
0V

0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 1
ADB 4
ADB 7
DB 1
DB 4
0V
0V
0V
0V
0V
0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 0
ADB 3
ADB 6
0V
DB 3
DB 6
0V
0V
0V
0V
0V
+5V
–
CPKL
MEMR
MEMW
PESP
ADB 2
ADB 5
DB 0
DB 2
DB 5
DB 7
RDY
BASP
–
0V
0V

0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 1
ADB 4
ADB 7
DB 1
DB 4
0V
0V
0V
0V
0V
0Vext
+ 5V
+ 5V
+ 5V
+ 5V
+ 5V
ADB 0
ADB 3
ADB 6
0V
DB 3
DB 6
0V
0V
0V
0V
0V
+5V
–
CPKL
MEMR
MEMW
PESP
ADB 2
ADB 5
DB 0
DB 2
DB 5
DB 7
RDY
BASP
–
0V
0V

+ AD 12
– AD 12
+ AD 13
– AD 13
+ AD 14
– AD 14
+ AD 15
– AD 15
+ AD 6
– AD 6
+ AD 7
– AD 7
PEUa
PEUa
–
–
+ AD 8
– AD 8
+ AD 9
– AD 9
+ AD 10
– AD 10
+ AD 11
– AD 11
+ AD 3
– AD 3
+ AD 4
– AD 4
+ AD 5
– AD 5
ZGUe
ZGUe
+ MEMR
– MEMR
+ MEMW
– MEMW
+ ALE
– ALE
+ BASP
– BASP
+ AD0
– AD 0
+ AD 1
– AD 1
+ AD 2
– AD 2
+ RDY
– RDY
–

+ AD 12
– AD 12
+ AD 13
– AD 13
+ AD 14
– AD 14
+ AD 15
– AD 15
+ AD 6
– AD 6
+ AD 7
– AD 7
PEUe
PEUe
0V
0V
+ AD 8
– AD 8
+ AD 9
– AD 9
+ AD 10
– AD 10
+ AD 11
– AD 11
+ AD 3
– AD 3
+ AD 4
– AD 4
+ AD 5
– AD 5
ZGUa
ZGUa
+ MEMR
– MEMR
+ MEMW
– MEMW
+ ALE
– ALE
+ BASP
– BASP
+ AD0
– AD 0
+ AD 1
– AD 1
+ AD 2
– AD 2
+ RDY
– RDY
+5V

System Manual
C79000-G8576-C199-06

IM 312-5C

IM 314

11-23

Connector Assignments

11-24

System Manual
C79000-G8576-C199-06

A

Appendix
Given in the Appendix are the
Ordering Information on products mentioned in this manual
References for further reading

System Manual
C79000-G8576-C199-06

A-1

Appendix

Ordering Information
Given in this section are the order numbers for the products mentioned and/or
described in the System Manual. The order numbers are arranged according
to the chapters in which the corresponding products are mentioned.

For Chapter 4
Central Controllers
with power supply unit
6ES5 955-3LC42
6ES5 955-3LF42
6ES5 955-3NC42
6ES5 955-3NF42

6ES5
6ES5
6ES5
6ES5

with power supply unit
6ES5 955-3NA12

6ES5 135-3UA42

188-3UA12
188-3UA22
188-3UA32
188-3UA51

Expansion Units
with power supply unit
6ES5 955-3LC42
with power supply unit
6ES5 955-3LF42
with power supply unit
6ES5 955-3NC42

A-2

6ES5 183-3UA13
6ES5 185-3UA13
6ES5 185-3UA33
6ES5 183-3UA22
6ES5 185-3UA23

with power supply unit
6ES5 955-3NF42

6ES5 185-3UA43

with fan module
230/120V AC
24V DC

6ES5 184-3UA11
6ES5 184-3UA21

without power supply or fan module

6ES5 187-5UA11

Baffle

6ES5 981-0DA11

Dummy front plates
width 1 slot
width 2 slots

6XF2 008-6KB00
6XF2 016-6KB00

System Manual
C79000-G8576-C199-06

Appendix

Power Supply Units
230/120 V AC, isolated, 5 V DC/18 A
230/120 V AC, isolated, 5 V DC/40 A
24 V DC, isolated, 5 V DC/18 A
24 V DC, isolated, 5 V DC/40 A

955-3LC42
955-3LF42
955-3NC42
955-3NF42

Lithium backup battery 3.6 V

6EW1 000-7AA (with
EWK LZ S2)

Rechargeable battery with two screws

6ES5 980-0NC11
(with EWK LZ S2)

Fan subassembly with fan and
terminals for rechargeable battery

6ES5 988-3NB41
(with WKF RZF)

Filter holder, guides, 10 filter mats

6ES5 981-0FA41 (with
WKF RZF)

Filter mats (10)

6ES5 981-0EA41
(with WKF RZF)

Battery compartment

C98130-A1155-B21
(with WKF RZF)
C98130-A1155-B20
(with WKF RZF)

Battery compartment holder
Battery compartment and battery
compartment holder

C98130-A1155-A7
(with WKF RZF)

Fuses for 3LC41 4 A, slow, 250 V
Fuses for 3LF41 8 A, fast, 250 V
Fuses for 3NC41 20 A, super-fast, 65 V
Fuses for 3NF41 30 A, super-fast, 65 V

C97327-Z1006-C130
C98327-S1001-C23
C98327-S1001-C19
C98327-S1001-C24
(with WKF RZF)

Caps for terminals (4)

C98130-A1102-C49
(with WKF RZF)

951 load power supply module
230/120 V AC, isolated, 24 V/4 A
Fuse, 1 A slow
Fuse, 2 A slow
Front connector, 20-way
for crimp connection, 40 mm
Spring contacts
Front connector, 20-way
for screw connection, 40 mm
24V DC, not isolated, 10A
15 V auxiliary submodule
Battery module
Fan unit
Backup battery

System Manual
C79000-G8576-C199-06

6ES5
6ES5
6ES5
6ES5

6ES5 951-4LB11
W79054-L4011-T100
W79054-L4011-T200
6ES5 497-4UA42
6XX3 070
6ES5 497-4UB42
6ES5 955-3NA12
6ES5 956-0AA12
6XG3 400-2CK00
6ES5 988-3NA11
6EW1 000-7AA

A-3

Appendix

For Chapter 5
CPUs
CPU 948-1 (640 Kbyte user memory)
CPU 948-2 (1664 Kbyte user memory)

6ES5 948-3UA11
6ES5 948-3UA21

CPU 928B

6ES5 928-3UB12
6ES5 928-3UB21

CPU 928

6ES5 928-3UA12
6ES5 928-3UA21

CPU 922

6ES5 922-3UA11

374 Memory Cards
256 Bbytes
512 Bbytes
1028 Bbytes
2048 Bbytes
4112 Bbytes

6ES5 374-2FH21
6ES5 374-2FJ21
6ES5 374-2FK21
6ES5 374-2FL21
6ES5 374-2FM21

376 Memory Cards
16 Bbytes
32 Bbytes
64 Bbytes

6ES5 376-0AA11
6ES5 376-0AA21
6ES5 376-0AA31

377 Memory Cards
16
32
64
64

Bbytes
Bbytes
Bbytes
Kbytes (with backup battery)
Backup battery

6ES5
6ES5
6ES5
6ES5
6ES5

377-0AA11
377-0AA21
377-0AA32
377-0BA31
980-0DA11

6ES5
6ES5
6ES5
6ES5
6ES5

752-0AA53
752-0AA12
752-0AA22
752-0AA42
752-0AA62

Interface Submodules
PG submodule
TTY submodule for 20 mA current loop
V.24 (RS-232C) submodule
RS422-A/485 submodule
SINEC L1 submodule
Cover for submodule receptacle

C79458-L957-B51

BT 777 bus terminal

6ES5 777-xxx00

Standard connecting cables
CPU 948/928B - PG 7xx
CPU 928B - CP 544/525/524
(RS422-A/485)
CPU 928B - CP 544/525/524 (TTY)
CPU 928B - CP 544/525/524 (V.24)
CPU 928B - DR 210/DR 211
DR 230/DR 231
(TTY/V.24)

6ES5 734-2xxx0
6ES5 725-7xxx0
6ES5 726-1xxx0
6ES5 726-8xxx0

6ES5 726-5xxx0

(xxx = SIMATIC length code, see Catalog)

A-4

System Manual
C79000-G8576-C199-06

Appendix

For Chapter 6
Coordinators
923A coordinator

6ES5 923-3UA11

923C coordinator

6ES5 923-3UC11

Coding plug
Front cover
Connecting cable for CP 530, 143 and 5430
0.9 m
2.5 m

C79334-A3011-B12
C79451-A3079-C251
6ES5 725-0AK00
6ES5 725-0BC50

For Chapter 7
Interface Modules
IM 300-3

6ES5 300-3AB11

IM 300-5C

6ES5 300-5CA11

IM 300-5L

6ES5 300-5LB11

IM 301-3

6ES5 301-3AB13

IM 301-5

6ES5 301-5CA12

IM 304

6ES5 304-3UB11

IM 310

6ES5 310-3AB11

IM 312-3 (0.5 m)
IM 312-3 (0.95 m)

6ES5 312-3AB11
6ES5 312-3AB31

IM 312-5 (0.5 m)
IM 312-5 (1.5 m)

6ES5 312-5CA11
6ES5 312-5CA21

IM 314

6ES5 314-3UA11

IM 314R

6ES5 314-3UR11

Connecting cable
(xxx = SIMATIC length code,
see Catalog)

System Manual
C79000-G8576-C199-06

6ES5-721-0xxx

Connecting cable for IM 300-5LB11
Length 0.5 m
Length 1.5 m

6ES5 705-0AF00
6ES5 705-0BB0

Terminator
for IM 314
for IM 312 and IM 301-3
for IM 301-3

6ES5 760-1AA11
6ES5 760-0AB11
6ES5 760-0AA11

A-5

Appendix

For Chapter 8
Digital Input/Output Modules
Modules

Adhesive Label

6ES5
6ES5
6ES5
6ES5
6ES5
6ES5
6ES5
6ES5
6ES5
6ES5
6ES5
6ES5
6ES5

420-4UA13
430-4UA13
431-4UA12
432-4UA12
434-4UA12
435-4UA12
436-4UA12
436-4UB12
441-4UA13
451-4UA13
453-4UA12
454-4UA13
455-4UA12

C79451-A3079-C751
C79451-A3079-C752
C79451-A3079-C732
C79451-A3079-C733
C79451-A3079-C734
C79451-A3079-C735
C79451-A3079-C736
C79451-A3079-C737
C79451-A3079-C753
C79451-A3079-C755
C79451-A3079-C740
C79451-A3079-C756
C79451-A3079-C742

6ES5
6ES5
6ES5
6ES5
6ES5
6ES5

456-4UA12
456-4UB12
457-4UA12
458-4UA12
458-4UC11
482-4UA11

C79451-A3079-C743
C79451-A3079-C744
C79451-A3079-C727
C79451-A3079-C745
E89100-B2749-C100
C79451-A3079-C749

Front Connectors
Crimp terminals, single-width, 42-way
Crimp terminals, double-width, 42-way
Crimp terminals, double-width, 20-way

6ES5 497-4UA12
6ES5 497-4UA22
6ES5 497-4UA42

Screw terminals, single-width, 42-way
Screw terminals, double-width, 42-way
Screw terminals, double-width, 25-way

6ES5 497-4UB31
6ES5 497-4UB12
6ES5 497-4UB22

Screw terminals, double-width, 20-way

6ES5 497-4UB42

IP 257

6ES5 257-4UA11

Local bus for DI/DQ 482

6ES5 751-2AA11

Mini spring contacts (250 single contacts)

6XX3070

Crimping tool

6XX3071

Ferrules to DIN 46228

A-6

Extraction (releasing) tool

6ES5 497-4UC11

Set of labels for addresses

6ES5 497-4UD11

Coding jumper (to change over the enable mode)

W79070-G2602-N2

Fuse for 6ES5 456-4UB12
3.5 A, fast/250 V UL/CSA

W79054-L1021-F350

System Manual
C79000-G8576-C199-06

Appendix

Fuse for 6ES5 455-4UA12 and 6ES5 455-4UA12
6.3 A, fast/250 V
Fuse for 6ES5 482-4UA11
6.3 A/125 V

W79054-L1011-F630
W79054-M1041-T630

Light guide K for front connector with crimp terminal

6ES5 497-4UL11

Light guide S for front connector with screw terminal

6ES5 497-4UL21

For Chapter 9
Analog Input/Output Modules
Modules

Adhesive Labels

6ES5
6ES5
6ES5
6ES5
6ES5
6ES5

C79451-A3079-C723
C79451-A3079-C746
C79451-A3079-C748
C79451-A3079-C724
C79451-A3079-C725
C79451-A3079-C726

460-4UA13
463-4UA12
465-4UA12
470-4UA12
470-4UB12
470-4UC12

Front Connectors
Crimp terminals, single-width, 42-way
Crimp terminals, double-width, 42-way
Crimp terminals, double-width, 20-way

6ES5 497-4UA12
6ES5 497-4UA22
6ES5 497-4UA42

Screw terminals, single-width, 42-way
Screw terminals, double-width, 42-way
Screw terminals, double-width, 25-way

6ES5 497-4UB31
6ES5 497-4UB12
6ES5 497-4UB22

Screw terminals, double-width, 20-way

6ES5 497-4UB42

Mini spring contacts (250 single contacts)

6XX3070

Crimping tool

6XX3071

Ferrules to DIN 46228

System Manual
C79000-G8576-C199-06

Extraction (releasing) tool

6ES5 497-4UC11

Set of labels for addresses

6ES5 497-4UD11

A-7

Appendix

Range Cards

A-8

Modules

Features

Range Card

6ES5 460-4UA13
6ES5 465-4UA12

$ 12.5/50/500mV/Pt 100
$ 50/500mV/Pt 100
$ 1V
$ 5V
$ 10V
$ 20mA
4 to 20mA/2-wire
transducer
4 to 20mA/4-wire
transducer

6ES5 498-1AA11
6ES5 498-1AA11
6ES5 498-1AA21
6ES5 498-1AA61
6ES5 498-1AA31
6ES5 498-1AA41
6ES5 498-1AA51
6ES5 498-1AA71

System Manual
C79000-G8576-C199-06

Appendix

Further Reading

Hans Berger:
Automating with the SIMATIC S5-135U
Siemens AG A19100-L531-F505-X-7600

Hans Berger:
Automating with the SIMATIC S5-155U
Siemens AG A19100-L531-F177-X-7600

Catalog ST 54.1

Programmable Controllers
S5-135U, S5-155U and S5-155H

Catalog ST 50

SIMATIC S5
Programmable Controllers

Catalog ST 59

SIMATIC S5
Programmers

Catalogs ET 1.4 and ET 3

6EV1 Power Supply Units

Guidelines for Handling
Electrostatically Sensitive Devices:
at the end of this manual

S5-155U Programmable Controller
CPU 948
Programming Guide
6ES5 998-3PR21

System Manual
C79000-G8576-C199-06

A-9

Appendix

S5-135U Programmable Controller
CPU 928B
Programming Guide
6ES5 998-2PR21

S5-135U Programmable Controller
CPU 928B
Communication
6ES5 998-2UL22

S5-135U Programmable Controller
CPU 928
Programming Guide
6ES5 998-1PR21

S5-135U Programmable Controller
CPU 922
Programming Guide
6ES5 998-0PR21

STEP 5
C79000-G8576-C140

IP 257
6ES5 998-2EA21

A-10

System Manual
C79000-G8576-C199-06

Guidelines for Handling
Electrostatically-Sensitive Devices (ESD)
Chapter
Overview

System Manual
C79000-G8576-C199-06

Section

Contents

B
Page

B.1

What is ESD?

B-2

B.2

Electrostatic Charging of Persons

B-3

B.3

General Protective Measures Against Electrostatic Discharge
Damage

B-4

B-1

Guidelines for Handling Electrostatically-Sensitive Devices (ESD)

B.1

What is ESD?

Definition

All electronic modules are equipped with large-scale integrated ICs or
components. Due to their design, these electronic elements are very sensitive
to overvoltages and thus to any electrostatic discharge.
These Electrostatically- Sensitive Devices are commonly referred to by the
abbreviation ESD.
Electrostatically-sensitive devices are labeled with the following symbol:

!

B-2

Caution
Electrostatically-sensitive devices are subject to voltages that are far below the voltage
values that can still be perceived by human beings. These voltages are present if you
touch a component or the electrical connections of a module without previously being
electrostatically discharged. In most cases, the damage caused by an overvoltage is not
immediately noticeable and results in total damage only after a prolonged period of
operation.

System Manual
C79000-G8576-C199-06

Guidelines for Handling Electrostatically-Sensitive Devices (ESD)

B.2

Electrostatic Charging of Persons

Charging

Every person with a non-conductive connection to the electrical potential of
its surroundings can be charged electrostatically.
Figure B-1 shows you the maximum values for electrostatic voltages which
can build up on a person coming into contact with the materials indicated in
the figure. These values are in conformity with the specifications of
IEC 801-2.

Voltage in kV
(kV)
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1

1

1

Synthetic material

2

Wool

3 Antistatic material, for
example, wood, or
concrete

2
3
5 10 20 30 40 50 60 70 80 90 100

Figure B-1

System Manual
C79000-G8576-C199-06

Relative air humidity in %

Electrostatic Voltages which can Build up on a Person

B-3

Guidelines for Handling Electrostatically-Sensitive Devices (ESD)

B.3

General Protective Measures Against Electrostatic Discharge
Damage

Ensure Sufficient
Grounding

Make sure that the personnel, working surfaces, and packaging are
sufficiently grounded when handling electrostatically-sensitive devices.
You thus avoid electrostatic charging.

Avoid Direct
Contact

You should touch electrostatically-sensitive devices only if it is unavoidable
(for example, during maintenance work). Hold modules without touching the
pins of components or printed conductors. In this way, the discharged energy
cannot affect the sensitive devices.
If you have to carry out measurements on a module, you must discharge your
body before you start the measurement by touching grounded metallic parts.
Use grounded measuring devices only.

B-4

System Manual
C79000-G8576-C199-06

Index
A
Address label, 8-20
Addressing
cyclic sampling, 9-12, 9-58, 9-104
selective sampling, 9-12, 9-58, 9-104
Addressing switch
analog input/output modules, 9-4, 9-35,
9-50, 9-98
digital input/output modules, 8-4
Air filter, 4-64
Application
COR 923A, 6-15
COR 923C, 6-18
CPU 922, 5-71
CPU 928, 5-62
CPU 928 -3UA21, 5-54
CPU 928B, 5-42
CPU 928B -3UB21, 5-30
CPU 948, 5-17
CPU 948 -3UA13, 5-2
CPU 948 -3UA23, 5-2
Auxiliary submodule, 15 V, 4-63

B
Backup battery
power supply units, 4-31
PSU 6ES5 955-3NA12, 4-66
RAM submodules 377, 5-87
Base address, 6-25
setting, 6-22
Basic functions, power supply units, 4-20
BASP
analog input modules, 9-9, 9-55, 9-102
digital input modules, 8-3
digital output modules, 8-3
BASP signal, 6-14
Battery voltage
power supply units, 4-21
PSU 6ES5 955-3NA12, 4-58, 4-70
Broken wire monitoring, extended Pt 100
measuring range, 9-22, 9-66

System Manual
C79000-G8576-C199-06

Broken wire signal, 9-8, 9-54
Bus arbitration, 6-15, 6-16, 6-18, 6-19
Bus enable, 6-16, 6-19
Bus enable assignment, 6-16
sequence, 6-19
Bus enable signal, 6-16, 6-19
Bus lock signal, 6-20
Bus PCB, 4-3

C
Cabinet assembly, for EMC, 3-8
Cable clamps, 3-15
Cable duct, 4-3
Cables, power supply units, 4-27
Cabling, fan submodule, 4-73
Central controller, installing, 4-6
Central grounding, 3-23
Central programmer connection, 6-18
Centrally grounded supply, 3-23
Checklist, EMC measures, 3-18
Communication flag area, 6-7
Communication flag areas, setting, 6-6
Communication flags, 6-15, 6-16, 6-20
Communication memory, 6-15, 6-16, 6-18
addressing, 6-6, 6-7
Compensating box, connection, 9-19, 9-63
Connecting loads, 9-109, 9-110
Connector assignment
6ES5 955-3NA12 power supply unit, 11-10
coordinator 923 A, 11-16
coordinator 923 C, 11-17
CPU 922, 11-14
CPU 928, 11-13
CPU 928B, 11-12
CPU 948, 11-11
front connector of the CPUs (PG interface),
11-15
front connectors of the coordinators, 11-18
IMs, 11-19
power supply units, 11-9
PSU 6ES5 955-3NA12, 11-10

Index-1

Index

Connector assignments, power supply units,
11-9
Connector assignments of the backplane
EU 183U, EU 184U, EU 187U, 11-5
EU 185U, 11-6
S5-135U/155U CC, 11-2
Controls and indicators
COR 923C, 6-23
CPU 922, 5-74
CPU 928, 5-65
CPU 928 -3UA21, 5-57
CPU 928B, 5-35, 5-47
CPU 948, 5-20
CPU 948 -3UA13, 5-6
CPU 948 -3UA23, 5-6
IM 300, 7-4
IM 301, 7-10
IM 304, 7-14
PSU 6ES5 955-3NA12, 4-58
Coordinator
location of jumper sockets, 6-4
modes, 6-13
normal operation, 6-13
stop in the event of fault, 6-13
test mode, 6-14
COR 923A, 6-6
application, 6-15
design, 6-15
mode switch, 6-17
principle of operation, 6-16
COR 923C, 6-6, 6-12, 6-15
activating addresses, 6-25
application, 6-18
controls, 6-23
design, 6-19
indicators, 6-23
principle of operation, 6-19
setting the coordination section, 6-24
setting the DIL switches, 6-24
setting the PG multiplexer, 6-25
switching off the coordination signal, 6-27
Coupling
capacitive coupling, 3-4
direct coupling, 3-4
inductive coupling, 3-4
mechanisms, 3-3
radiated interference, 3-4
Current limiting, two-wire transducers, 9-46
Current sensors, connection, 9-17
Current/voltage measurement, 9-78
Cyclic program processing, 6-13, 6-14
Cyclic sampling, 9-8, 9-54

Index-2

D
Data format, setting, 9-48, 9-81
Design
COR 923A, 6-15
COR 923C, 6-19
CPU 922, 5-71
CPU 928, 5-62
CPU 928 -3UA21, 5-54
CPU 928B, 5-42
CPU 928B -3UB21, 5-30
CPU 948, 5-17
CPU 948 -3UA13, 5-2
CPU 948 -3UA23, 5-2
Differential measurement, 9-78, 9-89
Distributed arrangement of monitor and PLC,
3-30
Double addressing, 6-6, 6-21

E
Electrical connection with process I/Os, 3-22
Electromagnetic compatibility, 3-2
EMC, basic rules, 3-5
EMC measures, specific, 3-16
Enable, switching off, 9-5
Enable circuit, digital input/output modules, 8-5
Enable input, 9-5, 9-36, 9-51, 9-99
switching off, 9-99
Enable inputs, functioning, 8-6
Enable switching off, 9-36, 9-51
Enable time, 6-16, 6-19
Equipotential bonding conductor, 3-13, 9-17
Example of an electrical installation, 3-22

F
Fan, 4-3
failure, 4-50
removing, 4-33
replacing, 4-41, 4-67
Fan lock, releasing, 4-33
Fan submodule
connecting, 4-72
setting, 4-72
Fault detection, monitoring module, 10-4
Fault indications
power supply units, 4-36
PSU 6ES5 955-3NA12, 4-65
Fault LEDs, fan submodule 6ES5 988-3LA11,
4-73

System Manual
C79000-G8576-C199-06

Index

Fault register, 6-27
FB 40 function block, 9-9, 9-55, 9-102
Filter mat, replacing, 4-46
Filter subdrawer, fitting, 4-34
Floating modules, 3-26
Four-wire circuit, 9-110
Front connector, 4-9, 6-19
463 analog input module, 9-49
466 analog input module, 9-97
470 analog input module, 9-98
Front panel, monitoring module, 10-2
Front plate, 6-19
CPU 922, 5-74
CPU 928, 5-65
CPU 928 -3UA21, 5-57
CPU 928B, 5-47
CPU 928B -3UB21, 5-35
CPU 948, 5-20
fan submodule 6ES5 998-3LA11, 4-70
power supply units, 4-21
PSU 6ES5 955-3NA12, 4-58
Front plate width, 6-15, 6-19
Full duplex operation, RS422 A/485 submodule,
5-112
Fusing, 3-20, 8-24

G
Global memory access, 6-15
Grounding
distributed arrangement of monitor and PLC,
3-30
inactive metal parts, 3-5, 3-7
PLCs, 3-22

I
I/O byte, changeover, DI/DQ 482, 8-13
I/O modules, 8-2
analog input/output modules, 9-2
digital input/output modules, 8-2
Individual locking, 4-3
Inductive loads, 8-25
Inputs/outputs
fan submodule 6ES5 988-3LA11, 4-70
power supply units, 4-21
PSU 6ES5 955-3NA12, 4-59
Installing, monitoring, 10-2
Interchange of data, 6-15

System Manual
C79000-G8576-C199-06

Interface submodules
installing, 5-93
PG submodule, 5-95
removing, 5-94
RS422 A/485 submodule, 5-112
SINEC L1 submodule, 5-118
TTY submodule, 5-106
use, 5-92
V.24 submodule, 5-99
Interfaces
CPU 928B, 5-43
CPU 928B -3UB21, 5-31
CPU 948, 5-13, 5-27
CPU 948 -3UA13, 5-13
CPU 948 -3UA23, 5-13
Interference, 3-2
measures for interference-free operation,
3-16
Interference source, 3-4
Interference-free installation
centralized interface circuits, 3-27
distributed interface circuits, 3-27

J
Jumper settings
COR 923A, 6-4
COR 923C, 6-4, 6-27
CPU 928B, 5-33, 5-45
CPU 948, 5-18
CPU 948 -3UA13, 5-3
CPU 948 -3UA23, 5-3
IM 300-3, 7-5
IM 300-5, 7-6, 7-7
IM 301, 7-11
IM 304, 7-15
IM 314, 7-17
PG submodule, 5-97
power supply units, 4-25
PSU 6ES5 955-3NA12, 4-60
RS422 A/485 submodule, 5-114
SINEC L1 submodule, 5-120
TTY submodule, 5-108
V.24 submodule, 5-101

L
Labeling field, 8-14, 9-10, 9-39, 9-56, 9-102

Index-3

Index

LEDs
COR 923C, 6-23
CPU 922, 5-76
CPU 928 , 5-67
CPU 928 -3UA21, 5-58
CPU 928B, 5-37, 5-49
CPU 948, 5-23
CPU 948 -3UA13, 5-9
CPU 948 -3UA23, 5-9
digital input/output modules, 8-4
fan submodule 6ES5 99-3LA11, 4-70
monitoring module, 10-2
power supply units, 4-36
PSU 6ES5 955-3NA12, 4-65
LEDs and controls, power supply units, 4-22
LEDs for fault indication and signaling
CPU 922, 5-77
CPU 928, 5-68
CPU 928B, 5-49
CPU 928 -3UA21, 5-59
CPU 928B -3UB21, 5-37
CPU 948, 5-23
CPU 948 -3UA13, 5-9
CPU 948 -3UA23, 5-9
Lightning protection, 3-12
Lithium battery
fitting in PSU, 4-31
replacing, 4-41
Load circuit, disconnecting, 8-26
Load power supply, 3-19
Load voltage, 9-46
Loads, connection, 9-109
Location of jumpers
power supply units, 4-29
PSU 6ES5 955-3NA12, 4-60
Locking bar, 4-3

M
Main switch, 3-20
Measured-value representation
current measuring range 4 to 20 mA, 9-28,
9-71
different measuring ranges, 9-91
output current/voltage, 9-111
Pt 100, 9-26, 9-70
two’s complement, 9-24, 9-68
Measurement with respect to ground, 9-78, 9-88
Measuring range
466 analog input module, 9-77
setting, 9-80
Measuring range exceeded, 9-8, 9-54

Index-4

Memory cards 374, 5-80
erasing, 5-80
inserting, 5-80
programming, 5-80
Memory page, 6-20
Memory submodules 376, 5-82
erasing, 5-82
inserting, 5-82
programming, 5-82
Memory submodules 377, 5-84
backup battery, 5-87
inserting, 5-88
programming, 5-84
removing, 5-89
with battery backup, 5-85
Mode, setting, 9-31, 9-73
Mode switch, 6-17, 6-23, 9-4, 9-35, 9-50, 9-98
coordinator, 6-13
COR 923A, 6-17
COR 923C, 6-23
CPU 922, 5-75
CPU 928 , 5-66
CPU 928 -3UA21, 5-58
CPU 928B , 5-48
CPU 928B -3UB21, 5-36
CPU 948, 5-21
CPU 948 -3UA13, 5-7
CPU 948 -3UA23, 5-7
Module, mounting width, 4-8
Momentary-contact mode switch
CPU 922, 5-75
CPU 928 , 5-66
CPU 928B, 5-48
CPU 928 -3UA21, 5-58
CPU 928B -3UB21, 5-36
CPU 948, 5-21
CPU 948 -3UA13, 5-7
CPU 948 -3UA23, 5-7
Monitor connection, 3-29
Monitoring for bus assignment, 6-20
Monitoring function, power supply units, 4-20
Mounting in cabinets, 3-8
Mounting on racks, 3-10
Mounting on walls, 3-10
Multiplex interface, 6-21
Multiprocessor operation, 1-1, 6-2, 6-15
starting, 6-3
startup phase, 6-12

N
Non-floating modules, 3-25

System Manual
C79000-G8576-C199-06

Index

O
Operator functions, 6-15
Outputs, 8-22
parallel connection, 8-22
Overall reset
CPU 922, 5-75, 5-78
CPU 928, 5-69
CPU 928 , 5-66
CPU 928B, 5-48
CPU 928B , 5-51
CPU 928 -3UA21, 5-58, 5-60
CPU 928B -3UB21, 5-36, 5-39
CPU 948, 5-21, 5-25
CPU 948 -3UA13, 5-7, 5-11
CPU 948 -3UA23, 5-7, 5-11

P
Page memory, 6-21
PG interfaces
CPU 928B, 5-31, 5-43
CPU 948, 5-27
CPU 948 -3UA13, 5-13
CPU 948 -3UA23, 5-13
PG multiplexer, of COR 923C, 6-21
PG MUX, 6-27
PG submodule, 5-95
Pin assignments
PG submodule, 5-96
RS422 A/485 submodule, 5-113
SINEC L1 submodule, 5-119
TTY submodule, 5-107
V.24 submodule, 5-100
Power dissipation, in cabinets, 3-35
Power supplies
AC, 3-21
centrally grounded, 3-23
control circuits, 3-19
grounded, 3-22
load circuits, 3-19
ungrounded, 3-24
Power supply
failure, 4-49
for programmable controllers, 3-17
types, 4-19

System Manual
C79000-G8576-C199-06

Power supply unit, 4-3
connecting, 4-23
fitting, 4-30
removing, 4-28
setting, 4-23
switching on, 4-35
Process inputs, scanning, 8-9, 8-10
Process interrupt processing
CPU 922, 5-72
CPU 928, 5-63
CPU 928 -3UA21, 5-55
CPU 928B, 5-44
CPU 928B -3UB21, 5-32
Processing levels
CPU 922, 5-71
CPU 928, 5-62
CPU 928 -3UA21, 5-54
CPU 928B, 5-30, 5-42
CPU 948, 5-17
CPU 948 -3UA13, 5-2
CPU 948 -3UA23, 5-2
Programmable controller
power supply, 3-17, 3-23
validity check, 4-11
Protection, 3-20
Pt 100, connection, 9-65
Pt 100 measuring range, 9-26

Q
Quenching circuitry, 8-25
Quenching devices, selection, connection, 8-26

R
Radiated interference, 3-4
Rechargeable battery, connecting, 4-33
Reference potential, 3-6

Index-5

Index

Removing and inserting
CPU 922 , 5-73
CPU 928 -3UA21, 5-56
CPU 928 , 5-64
CPU 928B, 5-45
CPU 928B -3UB21, 5-33
CPU 948, 5-19
CPU 948 -3UA13, 5-4
CPU 948 -3UA23, 5-4
modules, 8-18, 9-13, 9-42, 9-59, 9-84, 9-105
monitoring module, 10-6
Replacing the battery
power supply units, 4-41
PSU 6ES5 955-3NA12, 4-66
RESET
automatic, 6-13
CPU 948, 5-21
Reset
CPU 922, 5-75, 5-78
CPU 928, 5-69
CPU 928 , 5-66
CPU 928 -3UA21, 5-58, 5-60
CPU 928B, 5-48
CPU 928B -3UB21, 5-36, 5-39, 5-51
CPU 948 -3UA13, 5-7, 5-11
CPU 948 -3UA23, 5-7, 5-11
Resistance thermometers, connection, 9-20
Restart, 5-51
automatic, 6-13
CPU 922, 5-75, 5-78
CPU 928, 5-69
CPU 928 , 5-66
CPU 928B, 5-48
CPU 928 -3UA21, 5-58
CPU 928B -3UB21, 5-36, 5-39
CPU 948, 5-21, 5-25
CPU 948 -3UA13, 5-7, 5-12
CPU 948 -3UA23, 5-7, 5-12
Routing of lines, 3-5
RS422 A/485 submodule, 5-112
Rules for ensuring EMC, 3-5

S
S5 bus, 6-16
Selective sampling, 9-9, 9-54
Semaphores, 6-16, 6-20
Sensors, connection, 9-48, 9-89
Serial interface, 6-21
selection method, 6-22

Index-6

Shielding, 3-14
distributed arrangement of monitor and PLC,
3-30
Shielding of cables/lines, 3-14
Short-circuit protection, 8-24
Signal lines, connection, 8-21, 9-16, 9-45, 9-62,
9-87, 9-108
Signal output, 8-3
Signaling circuits
fan submodule, 4-72
of the power supply units, 4-26
Signaling function, power supply units, 4-20
SINEC H1 LAN, routing of cables, 3-11
SINEC L1 LAN, routing of cables, 3-11
SINEC L1 submodule, 5-118
SINEC L2 LAN, routing of cables, 3-11
Slot, 6-22
setting the number of CPU slots, 6-6
Slots, slots required by CPU, 1-1, 6-2
Standard connecting cables
PG submodule, 5-98
RS422 A/485 submodule, 5-117
TTY submodule, 5-109
V.24 submodule, 5-102
Start, 6-13
manual, 6-13
Start address, 8-15
Start address, subaddress, analog input/output
modules, 9-10, 9-40, 9-56, 9-103
Startup
CPU 922, 5-78
CPU 928 , 5-69
CPU 928 -3UA21, 5-60
CPU 928B, 5-39, 5-51
CPU 948, 5-25
CPU 948 -3UA13, 5-11
CPU 948 -3UA23, 5-11
Startup of CC, brief instructions, 4-10
Startup of the programmable controller, 4-10
Station number, 6-22
Status indicators
CPU 922, 5-76
CPU 928 , 5-67
CPU 928B, 5-49
CPU 928 -3UA21, 5-58
CPU 928B -3UB21, 5-37
CPU 948, 5-22
CPU 948 -3UA13, 5-8
CPU 948 -3UA23, 5-8
Stop state, 6-13

System Manual
C79000-G8576-C199-06

Index

Supply line L+ and L, disconnecting, 8-26
Systems, installation to EMC requirements, 3-2

T
Technical specifications
374 memory cards, 5-81
376 memory submodules, 5-83
377 memory submodules, 5-90
420 digital input module, 8-30
430 digital input module, 8-32
431 digital input module, 8-34
432 digital input module, 8-36
434 digital input module, 8-39
435 digital input module, 8-42
436-4UA12 digital input module, 8-44
436-4UB12 digital input module, 8-46
441 digital output module, 8-48
451 digital output module, 8-50
453 digital output module, 8-52
454 digital output module, 8-54
455 digital output module, 8-56
456-4UA12 digital output module, 8-58
456-4UB12 digital output module, 8-60
457 digital output module, 8-62
458-4UA12 digital output module, 8-64
458-4UC11 digital output module, 8-67,
8-69
coordinators, 6-28
CPU 922, 5-79
CPU 928, 5-70
CPU 928 -3UA21, 5-61
CPU 928B, 5-40, 5-52
CPU 948, 5-28
CPU 948 -3UA13, 5-15
CPU 948 -3UA23, 5-15
expansion units, 4-18
fan submodule 6ES5 998-3LA11, 4-74
interface modules, 7-20
interface submodules, 5-122
monitoring module, 10-14
power supply units, 4-51
PSU 6ES5 955-3NA12, 4-68

System Manual
C79000-G8576-C199-06

Time-controlled program processing, 9-9, 9-55
Time-division multiplex operation, 6-16, 6-19
Transducers, connection, 9-23, 9-67
Tripping current, 9-8, 9-54
TTY submodule, 5-106
Two-wire switches, 8-27

V
V.24 interface, 5-99
V.24 submodule, 5-99
Vector register, 6-21
Voltage selector switch, setting, 4-34
Voltage sensors, connection, 9-17

W
Wall mounting, 3-10
Wiring, 8-19

Index-7

Index

Index-8

System Manual
C79000-G8576-C199-06

Siemens AG
A&D AS E 81
Oestliche Rheinbrueckenstr. 50
D-76181 Karlsruhe
Federal Republic of Germany

From:
Your Name: _ _ _ _
Your Title: _ _ _ _
Company Name:
_
Street:
_
City, Zip Code_
Country:
_
Phone:
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

_
_
_
_
_
_
_

Please check any industry that applies to you:


Automotive



Pharmaceutical



Chemical



Plastic



Electrical Machinery



Pulp and Paper



Food



Textiles



Instrument and Control



Transportation



Nonelectrical Machinery



Other _ _ _ _ _ _ _ _ _ _ _



Petrochemical

System Manual
6ES5998-0SH21-06

1

Remarks Form
Your comments and recommendations will help us to improve the quality and usefulness
of our publications. Please take the first available opportunity to fill out this questionnaire
and return it to Siemens.

Please give each of the following questions your own personal mark within the range
from 1 (very good) to 5 (poor).
1.

Do the contents meet your requirements?

2.

Is the information you need easy to find?

3.

Is the text easy to understand?

4.

Does the level of technical detail meet your requirements?

5.

Please rate the quality of the graphics/tables:

Additional comments:
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _

2

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

_
_
_
_
_
_
_
_
_
_
_
_

System Manual
6ES5998-0SH21-06



Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.2
Linearized                      : No
Create Date                     : 1998:12:07 11:30:50
Producer                        : Acrobat Distiller 3.02
Author                          : Zahn Dany (A&D AS E81)
Creator                         : Interleaf, Inc.
Title                           : S5-135U/155U
Subject                         : Systemhandbuch
Keywords                        : 6ES5998-0SH21-06
Modify Date                     : 1998:12:17 12:08:59
Page Count                      : 560
Page Mode                       : UseOutlines
EXIF Metadata provided by EXIF.tools

Navigation menu